CODE MODEL
C9511300 RL 28/M
C9511320 RL 28/M
C9512353 RL 38/M
C9512300 RL 38/M
C9512301 RL 38/M
C9512310 RL 38/M
C9512320 RL 38/M
C9513303 RL 50/M
C9513353 RL 50/M
C9513300 RL 50/M
C9513301 RL 50/M
C9513310 RL 50/M
1
GUARANTEE AND RESPONSIBILITY SAFETY AND PREVENTION
The manufacturer guarantees its new products from the installation date,
in accordance with the regulations in force and/or the sales contract. At INTRODUCTION
the moment of the first start-up, check that the burner is integral and com-
The burners have been designed and built in compliance with current
plete.
regulations and directives, applying the known technical rules of safety
Failure to observe the information given in this manual, op- and envisaging all the potential danger situations.
erating negligence, incorrect installation and carrying out It is necessary, however, to bear in mind that the imprudent and clumsy
WARNING of non authorised modifications will result in the annulment use of the equipment may lead to situations of death risk for the user or
by the manufacturer of the guarantee that it supplies with third parties, as well as the damaging of the burner or other items. Inat-
the burner. tention, thoughtlessness and excessive confidence often cause acci-
In particular, the rights to the guarantee and the responsibility will no lon- dents; the same applies to tiredness and sleepiness.
ger be valid, in the event of damage to things or injury to people, if such It is a good idea to remember the following:
damage/injury was due to any of the following causes: - The burner must only be used as expressly described. Any other use
- incorrect installation, start-up, use and maintenance of the burner; should be considered improper and therefore dangerous.
- improper, incorrect or unreasonable use of the burner;
- intervention of unqualified personnel; In particular:
- carrying out of unauthorised modifications on the equipment;
it can be applied to boilers operating with water, steam, diathermic oil,
- use of the burner with safety devices that are faulty, incorrectly and to other uses expressly named by the manufacturer;
applied and/or not working;
the type and pressure of the fuel, the voltage and frequency of the elec-
- installation of untested supplementary components on the burner;
trical power supply, the minimum and maximum deliveries for which the
- powering of the burner with unsuitable fuels; burner has been regulated, the pressurisation of the combustion cham-
- faults in the fuel supply system; ber, the dimensions of the combustion chamber and the room tempera-
- use of the burner even following an error and/or an irregularity; ture must all be within the values indicated in the instruction manual.
- repairs and/or overhauls incorrectly carried out; - Modification of the burner to alter its performance and destinations is
- modification of the combustion chamber with inserts that prevent the not allowed.
regular development of the structurally established flame; - The burner must be used in exemplary technical safety conditions.
- insufficient and inappropriate surveillance and care of those burner Any disturbances that could compromise safety must be quickly elim-
components most likely to be subject to wear and tear; inated.
- the use of non-original components, including spare parts, kits, - Opening or tampering with the burner components is not allowed,
accessories and optional; apart from the parts requiring maintenance.
- force majeure. - Only those parts envisaged by the manufacturer can be replaced.
The manufacturer furthermore declines any and every responsibili- The manufacturer guarantees safety and proper function-
ty for the failure to observe the contents of this manual. ing only if all burner components are intact and positioned
WARNING correctly.
PERSONNEL TRAINING
The user is the person, body or company that has acquired the machine
and intends to use it for the specific purpose. He is responsible for the
machine and for the training of the people working around it.
The user:
- undertakes to entrust the machine exclusively to suitably trained and
qualified personnel;
- undertakes to inform his personnel in a suitable way about the appli-
cation and observance of the safety instructions. With that aim, he
undertakes to ensure that everyone knows the use and safety
instructions for his own duties;
- Personnel must observe all the danger and caution indications
shown on the machine.
- Personnel must not carry out, on their own initiative, operations or
interventions that are not within their province.
- Personnel must inform their superiors of every problem or dangerous
situation that may arise.
- The assembly of parts of other makes, or any modifications, can alter
the characteristics of the machine and hence compromise operating
safety. The manufacturer therefore declines any and every responsi-
bility for any damage that may be caused by the use of non-original
parts.
2
TECHNICAL DATA
MODEL RL 28/M RL 38/M RL 38/M RL 50/M RL 50/M
Output (1) High MBtu/hr (3) 630 - 1260 896 - 1708 896 - 1708 1120 - 2240 1120 - 2240
GPH 4.5 - 9 6.4 - 12.2 6.4 - 12.2 8 - 16 8 - 16
Low MBtu/hr (3) 336 - 630 378 - 896 378 - 896 490 - 1120 490 - 1120
GPH 2.4 - 4.5 2.7 - 6.4 2.7 - 6.4 3.5 - 8 3.5 - 8
Fuel # 2 fuel oil
Operation Low - high or modulating
Nozzle number 1 (nozzle with return)
Standard applications Boilers: water, steam, thermal oil
Ambient temperature °F 32 - 104 (0 - 40 °C)
Combustion air temperature °F max 140 (60 °C)
Main power supply (+/- V/Ph/Hz 120/1/60 208-230 / 460 / 575 / 3/ 60 120-230/1/60
10%)
Fan motor rpm 3400 3400 3400 3400 3400
W - HP 370 - 0.5 370 - 0.5 550 - 0.75 550 - 0.75 550 - 0.75
V 120 120 208 - 230 / 460 / 575 208 - 230 / 460 / 575 120 - 230
A 5.2 5.2 3.2 - 1.6 - 1.3 3.2 - 1.6 - 1.3 9.8 - 4.9
Motor capacitor µF 45 20
Ignition transformer V1 - V2 120 V - 2 x 5 kV
I1 - I2 3.7 A - 35 mA
Pump delivery (at 290 PSI) GPH 32
pressure range PSI 145 - 290
fuel temperature °F max 140 (60 °C)
Electrical power consumption W max 550 600 700 800 750
Electrical protection NEMA 1
Noise levels (2) dBA 68 70 70 75 75
(1) Reference conditions: Ambient temperature 68 °F (20 °C) - Barometric pressure 394” W.C. - Altitude 329 ft.
(2) Sound pressure measured in manufacturer’s combustion laboratory, with burner operating on test boiler and at maximum rated output.
(3) Equivalent Btu values based on 1 USGPH = 140,000 Btu/hr.
Burner models designations
Model RIELLO Code RBNA Code Voltage Flame safeguard
C9511300
RL 28/M 3471070 120/1/60 Burner mounted
C9511320
3471270 C9512353 120/1/60
C9512300 208-230/460/3/60
RL 38/M C9512301 Burner mounted
3471470
C9512310 575/3/60
C9512320
C9513303 120/1/60
3471675
C9513353
RL 50/M C9513300 208-230/460/3/60 Burner mounted
3471670 C9513301 575/3/60
C9513310
ACCESSORIES (optional):
Modulating control kit
Two components should be ordered:
• modulating control to install on the burner;
• probe to install on the boiler.
PARAMETER TO BE CHECKED PROBE MODULATING CONTROL
Range Type Code Type Code
Temperature - 212...+ 932 °F (- 100...+ 500 °C) PT 100 3010110 RWF50 20082208
Pressure 0...36.3 PSI (0...2.5 bar) Probe with output 3010213 RWF55 20099657
0...232 PSI (0...16 bar) 4...20 mA 3010214
3
BURNER DESCRIPTION (A)
1 Ignition electrodes
2 Combustion head
3 Screw for combustion head adjustment
4 Flame sensor (cad sensor)
5 Screw for fixing fan to flange
6 Servomotor provides adjustment of fuel delivery reg-
ulator and of air damper. When the burner is not op-
erating the air damper is fully closed in order to
reduce heat dispersion from the boiler due to the flue
D2533
draft which draws air from the fan suction inlet.
7 Slide bars for opening the burner and inspecting the
combustion head
8 Safety solenoid valve
9 Pump delivery valve
10 Valve on nozzle return
11 Pressure regulator on nozzle return
12 Pump
13 Plate prearranged to drill 4 holes for the passage of
hoses and electrical cables.
14 Air damper
15 Non-drip nozzle holder
22
16 Fan pressure test point
17 Boiler mounting flange
18 Flame stability disk
19 Flame inspection window
D851 20 Power switch for different operation:
automatic - manual - off
Button for:
power increase - power reduction
21 Motor contactor and thermal overload with reset but-
ton (RL 38 - 50/M)
22 Extensions for slide bars 7)
23 Flame safeguard with lock-out pilot light and lock-out
reset button
24 Terminal strip
25 High oil pressure switch
26 Pump pressure adjustment
27 Pressure gauge for pressure on nozzle return
28 Protection (for RL 50/M single-phase burner)
inch E F G H (1)
RL 28/M 5 1/2 ” 13 27/32 ” 2 1/16 ” 26 15/32 ” - 31 3/4 ”
RL 38/M 5 1/2 ” 13 27/32 ” 2 1/16 ” 26 15/32 ” - 31 3/4 ”
RL 50/M three-phase 5 31/32 ” 13 27/32 ” 2 1/16 ” 26 15/32 ” - 31 3/4 ”
RL 50/M single-phase 5 31/32 ” 13 27/32 ” 2 1/16 ” 26 15/32 ” - 31 3/4 ”
(C)
(1) Blast tube: short - long (obtainable with the kit)
4
FIRING RATES (A)
During operation, burner output varies between:
Furnace pressure “ WC
RL 28/M • MINIMUM OUTPUT : area A
• MAXIMUM OUTPUT : area B
Graphs (A):
Horizontal axis : Burner output
Vertical axis : Heater furnace pressure
The firing rate may be found by plotting a vertical line
from the desired delivery and a horizontal line from the
A B pressure in the combustion chamber. The intersection of
these two lines is the firing rate which must lie within
area A, for MIN output, and within area B, for MAX out-
put.
Important:
The FIRING RATE area values have been obtained
considering a surrounding temperature of 68 °F (20 °C),
and an atmospheric pressure of 394” W.C. and with the
combustion head adjusted as shown on page 6.
Furnace pressure “ WC
RL 38/M
Note:
The FIRING RATE areas given in figure (A) have been
reduced by 10% with respect to the maximum range that
can be reached.
Consult Appendix on page 22 for operation at different
ambient temperatures and / or altitudes.
A B
MINIMUM FURNACE DIMENSIONS
The firing rates were set in relation to certified test boil-
ers.
Figure below indicates the diameter and length of the
test combustion chamber.
Example:
output 1388 MBTU/h:
RL 50/M diameter 20 inch - length 4.9 ft.
Furnace pressure “ WC
Diameter (inches)
A B
D2918
(A) D2526
INSTALLATION
BOILER PLATE (B)
Drill the combustion chamber mounting plate as shown in
inch A B C (B). The position of the threaded holes can be marked
using the burner head gasket supplied with the burner.
RL 28/M 65/16“ 813/16“ 3/8 W BLAST TUBE LENGTH (C)
RL 38/M 65/16“ 813/16“ 3/8 W The length of the blast tube 7) must be selected accord-
ing to the indications provided by the manufacturer of
RL 50/M 65/16“ 813/16“ 3/8 W the boiler, and in any case it must be greater than the
thickness of the boiler door complete with its insulation.
D455
(B) The range of lengths available, (inch), is as follows:
Blast tube 7): RL 28/M RL 38/M RL 50/M
• short 915/32“ 915/32“ 915/32“
• long 1313/16“ 1313/16“ 1313/16“
For boilers with front flue passes 10) or flame inversion
chambers, protective insulation 8) must be inserted be-
tween the boiler refractory 9) and the blast tube 7).
This protective insulation must not compromise the ex-
traction of the blast tube.
For boilers having a water-cooled front the insulation 8)-
9)(C) is not required unless it is required by the boiler
manufacturer.
SECURING THE BURNER TO THE BOILER (C)
Disassemble the blast tube 7) from the burner 4) by pro-
ceeding as follows:
- remove the screws 2) from the two slide bars 3).
- Remove the screw 1) fixing the burner 4) to the flange 5).
- Withdraw the blast tube 7) complete with flange 5) and
D2527 slide bars 3).
Secure flange 5)(C) to the boiler plate inserting the sup-
plied gasket 6). Use the 4 screws provided after having
(C) protected the thread with an antilocking product.
The burner-boiler seal must be airtight.
5
CHOICE OF NOZZLE (A)
1 2 3 4
A3 - A4 GPH PSI PSI It is advisable to replace nozzles once a year
during periodical maintenance.
15 4.2 290 246.5
20 6.4 290 246.5 The use of nozzles other than those specified by
30 7.7 290 217.5 the Manufacturer and inadequate regular
40 9.6 290 232 maintenance may result into emission limits
50 10.6 290 232 non-conforming to the values set forth by the
60 13.4 290 232 regulations in force, and in extremely serious
70 16 290 217.5 cases, into potential hazards to people and
D855 objects.
(A) (B) The Manufacturer shall not be liable for any
such damage arising from non-observance of
the requirements contained in this manual.
(G)
6
FUEL SUPPLY
Double-pipe circuit (A)
The burner is equipped with a self-priming pump which
7 5 is capable of supplying itself within the limits listed in the
V
Distance “P” must not exceed 33 ft in order to avoid sub-
P
jecting the pump’s seal to excessive strain; distance "V"
must not exceed 13 ft in order to permit pump self-prim-
ing even when the tank is almost completely empty.
6 The tank lower than the burner B
1 Pump suction values higher than 13 “Hg must not be ex-
+H
ceeded because at higher levels gas is released from the
10 cm
2 fuel, the pump starts making noise and its working life-
span decreases.
It is good practice to ensure that the return and suction
lines enter the burner from the same height; in this way it
4 will be less probable that the suction line fails to prime or
5 3 stops priming.
The loop circuit
A loop circuit consists of a loop of piping leaving and
returning to the tank with an auxiliary pump that circu-
lates the fuel under pressure. A branch connection from
7
the loop goes to feed the burner. This circuit is
extremely useful whenever the burner pump does not
succeed in self-priming because the tank distance and/
-H
(B) D2531
7
SERVOMOTOR (A)
ORANGE CAM The servomotor provides simultaneous adjustment of the
air damper 11)(B) page 9 and the pressure regulator 9)
BLUE CAM by means of a double variable profile cam, 4) and 7). The
servomotor rotates through 90° in 25 seconds.
RED CAM
Do not alter the factory setting for the cams; simply
check that they are set as indicated below:
Red cam : 90°
Limits rotation toward maximum position.
Blue cam : 0°
Limits rotation toward the minimum position. When the
burner is shut down the air damper must be closed: 0°.
Orange cam : 15°
Adjusts the ignition position and the MIN output.
RESET
PUMP (B)
1 - Suction 1/4” NPT
2 - Return 1/4” NPT
3 - Pressure gauge attachment G 1/8”
4 - Vacuum gauge attachment G 1/8”
D2522 5 - Pressure adjustment screw
(A) A - Min. delivery rate at 290 PSI pressure
B - Delivery pressure range
SUNTEC AL 95 C
C - Max. suction pressure
D - Viscosity range
E - Max fuel oil temperature
F - Max. suction and return pressure
G - Pressure calibration in the factory
H - Filter mesh width
PUMP PRIMING
• Before starting the burner, make sure that the tank
return line is not clogged. Obstructions in the line
could cause the seal located on the pump shaft to
break.
• In order for self-priming to take place, one of the
screws 3)(B) of the pump must be loosened to bleed
D2286 off the air contained in the suction line.
• Start the burner by closing the control circuit with
switch 1)(C) in the "MAN" position. As soon as the
burner starts, check the direction of rotation of the fan
blade, by looking through the flame inspection window
19)(A)p.4.
• The pump can be considered primed when the fuel oil
AL 95 C starts coming out of the screw 3). Stop the burner:
switch 1)(C) set to "OFF" and tighten the screw 3).
A GPH 32 The time required for this operation depends upon the
diameter and length of the suction tubing. If the pump
B PSI 145 - 290
fails to prime at the first cycle of the burner and the
C “Hg 13
burner locks out, wait approx. 15 seconds, reset the
D cSt 2 - 12 burner, and then repeat the starting operation as often
E °F - °C 140 - 60 as required. After 5 or 6 starting operations allow 2 or 3
F PSI 29 minutes for the transformer to cool.
G PSI 290
H inch 0,006 Important
The priming operation is possible because the pump is
(B) already full of fuel when it leaves the factory. If the pump
has been drained, fill it with fuel through the opening for
the vacuum gauge prior to starting; otherwise, the pump
1 2 will seize. Whenever the length of the suction piping
exceeds 66 - 99 ft, the supply line must be filled using a
separate pump.
D791
(C)
8
BURNER FIRING
1 2
Close load controls and set switch 1)(A) to “MAN”.
After burner firing a complete burner adjustment should
be performed.
BURNER CALIBRATION
(A) D791
All the installation, maintenance and
disassembly operations must be carried
out with the electricity supply
DANGER disconnected.
The installation of the burner must be
carried out by qualified personnel, as
indicated in this manual and in compliance
with the standards and regulations of the
WARNING
laws in force.
1 - MAX power
Max output of the burner must be set within the firing rate
range shown on page 5.
In the above instructions we left the burner running in
MIN output operation. Now press button 2)(A) “+” until
servomotor arrives at 90°.
(B) D2523
Adjusting the nozzle flow rate
The nozzle flow rate varies according to the fuel pres-
Type A4 sure on the nozzle return. Diagram (C) indicates this
relationship for type A4 return flow nozzles with pump
delivery pressure of 290 PSI.
Diagrams (C):
Horizontal axis : GPH, nozzle flow rate
Vertical axis : PSI, nozzle return pressure
NOTE
With a pump delivery pressure of 290 PSI, the pressure
on the nozzle return must not exceed 246.5 PSI.
The pressure difference between pump delivery and
nozzle return must be at least 43.5 PSI. With smaller
pressure differences, the pressure on the nozzle return
can be unstable.
To fix the maximum nozzle flow rate, vary the final profile
on the upper cam 7)(B) via the screws 8).
The nozzle return pressure value is indicated by the
pressure gauge 10).
Key (B)
1 Servomotor
2 Reset
3 Servomotor cover
4 Cam for controlling air damper
The values indicated in the curves, refer to the data printed on the nozzle.
5 Cam 4) adjustable screws
6 Opening for access to screws 5)
(C) D2321 7 Cam for controlling pressure regulator
8 Cam 7) adjustable screws
9 Pressure regulator
10 Gauge for pressure on nozzle return
11 Air damper
12 Index
9
Adjusting air delivery
Two shutters 1) and 2) are provided to adjust the air.
These shutters are factory set to maximum opening.
Firstly, with burner at maximum operation, adjust shutter
2) which must be closed gradually until optimum com-
bustion is obtained. If total closure of shutter 2) is not suf-
ficient, also close shutter 1) (secondly) as follows:
vary the final profile of the lower cam 4)(B) via the screws
5) inside the opening 6).
If the burner is operated at maximum power, the fan air
may not be sufficient even with both shutters 1) and 2)
fully open. In this case, remove shutter 2) and adjust the
air using shutter 1) only as described above.
Cams 7) - 4)(B):
- tighten screws 8)-5) to increase air delivery;
- unscrew screws 8)-5) to reduce air delivery.
(A) D871
2 - MIN power
The MIN power must be chosen from within the working
range given on page 5. Press the “-” button 2)(A) page 9
and keep it pressed until the servomotor has reached
15° (factory setting).
Nozzle flow rate adjustment
The nozzle flow rate is given in diagram (C)p.9 corre-
sponding to the pressure on the nozzle return read on
the pressure gauge 10)(B). To vary the nozzle minimum
flow rate, modify the initial profile of the upper cam 7)(B)
via the screws 8).
Adjusting air delivery
Modify the initial profile of the lower cam 4)(B) via the
screws 5) inside the opening 6).
If possible, do not rotate the first screw as this is the one
that provides for total closure of the air damper.
3 - INTERMEDIATE power
Air/oil flow rate adjustment
Slightly press the "+" button 2)(A) page 9 so that a new
screw 5)(B) appears inside the opening 6)(B).
Adjust screw 8)(B) which varies the profile of the upper
cam 7) and the corresponding screw 5) which controls
the lower cam 4) until you obtain optimum combustion.
Proceed in the same way with the next screws except for
the last one, previously adjusted to obtain maximum
power.
Ensure that variation of the cams profile is gradual.
Turn the burner off via switch 1)(A) page 9, OFF posi-
tion, release the cam with variable profile by pressing
the reset button 2)(B) and check that the movement is
smooth by manually rotating the cam backwards and
forwards several times.
NOTE
(B) D2523
Red and blue cams of the servomotor do not require ad-
justment. Only orange cam may need adjusting.
The servomotor follows the adjustment of cam III only
when the cam angle is reduced. If you need to increase
the cam angle (15..16..17°..), first increase the servomo-
tor angle via the "+" button, then increase the angle of
orange cam and finally reset the servomotor to the MIN
power position via the “-” button.
10
SEQUENCE OF OPERATION
Full Modulation
Switching times are given in seconds, in the burner
start-up sequence.
LAL 2.25
t1 18 t5 optional
t2 4 t6 optional
t3 2 t7 12
t4 12 t8 4
D2882
(A)
Low-High
D2883
(B)
11
BURNER OPERATION
FIRING FAILURE
If the burner does not fire, it goes into lock-out within 5 s
of the opening of the fuel oil valve.
FIRING FAILURE
If the flame should go out for accidental reasons during
operation, the burner will lock out in 1 s.
12
BURNER FAULT INDICATIONS
No start One of the contacts has not closed - Air damper opened.
The limit switch (blue cam) for the closed position do not
supply voltage from terminal 11 to terminal 8.
- The contact of the limit thermostat or any other switching
devices in the control loop of terminal 4 to terminal 5 are
opened.
Interruption of start-up sequence OPEN signal of changeover limit switch (red cam) has not been delivered to terminal 8
Terminals 6, 7 and 15 remain under voltage until fault has been corrected
Interruption of start-up sequence Position signal of auxiliary switch (orange cam) for the low
flame position has not been delivered to terminal 8
13
MAINTENANCE
All the installation, maintenance and
disassembly operations must be carried
PERICOLO out with the electricity supply disconnected.
The installation of the burner must be
carried out by qualified personnel, as
indicated in this manual and in compliance
ATTENZIONE with the standards and regulations of the
laws in force.
Combustion
An analysis of the flue gases at the boiler outlet is
required. Significant differences with respect to the pre-
vious measurements indicate the points where more
D482 care should be exercised during maintenance.
(A) Pump
The pump delivery pressure must be stable at 290 PSI.
The suction must be less than 6.5 PSI.
Unusual noise must not be evident during pump opera-
tion.
If the pressure is found to be unstable or if the pump runs
noisily, the flexible hose must be detached from the line
filter and the fuel must be sucked from a tank located
near the burner. This test permits the cause of the anom-
aly to be traced to either the suction line or the pump.
If the pump is found to be responsible, check to make
sure that the filter is not dirty. The vacuum gauge is in-
stalled up-line from the filter and consequently will not in-
dicate whether the filter is clogged or not.
If the problem lies in the suction line, check to make sure
that the filter is clean and that air is not entering the pip-
ing.
Servomotor
Disengage servomotor and turn it backward and forward
by hand to make sure it is free moving.
Filters (A)
Check the following filters:
D484
• on line 1) • in pump 2) • at nozzle 3),
and clean or replace as required.
(B) D2532 (C) If rust or other impurities are observed inside the pump,
use a separate pump to suck out any water and other
impurities that may have deposited on the bottom of the
tank.
Combustion head
Check to make sure that all the parts of the combustion
head are in good condition, positioned correctly, free of
all impurities, and that no deformation has been caused
by operation at high temperatures.
Nozzle
Do not clean the nozzle orifices.
It is advisable to replace nozzles once a year during
periodical maintenance. Combustion must be checked
after the nozzles have been changed.
Flame sensor (cad sensor) (B)
Clean the glass cover from any dust that may have
accumulated. Flame sensor 1) is held in position by a
pressure fit and can therefore be removed by pulling it
outward.
(D) D875 Flame inspection window (C)
Clean the glass.
Flexible hoses
Check to make sure that the flexible hoses are still in
good condition.
Fuel tank
Every 5 years, or whenever necessary, suck out any
water or other impurities present on the bottom of the
tank using a separate pump.
Burner
Make sure that the screws are fully tightened.
TO OPEN THE BURNER (D):
- switch off the electrical power.
- Remove screw 1 and withdraw the casing 2).
- Unscrew screw 3).
- Fit the two extensions 4) supplied with the burner onto
the slide bars 5) (models with long blast tube).
- Pull part A backward keeping it slightly raised to avoid
damaging the disk 6) on blast tube 7).
X Fuel pump and/or couplings replacement (E)
dimension See fig. (E). Dimension X should be set as follows:
RL28/M - 1/4“
(E) D2854 RL38/M - 3/16“
RL50/M - 5/16“
14
APPENDIX - ELECTRICAL CONNECTIONS
The electrical wirings must be carried out in conformity with the regulations in force in the countries of destination, and by
qualified personnel.
Riello S.p.A. cannot accept any responsibility for modifications or connections other than those shown in these diagrams.
WARNING
IMPORTANT
The burner is factory set for low - high operation and it must be connected to the OCR control device to control fuel oil valve V2.
If on - off operation is required, instead of control device OCR install a jumper lead between terminals T6 and T8 of burner terminal strip.
NOTES
A B C D E A B C D E
120V 230 V
The RL 28/M - 38/M - 50/M burners have been type-approved for intermittent operation. This means they should compulsorily be stopped at
least once every 24 hours to enable the control box to check its own efficiency at start-up. Burner halts are normally provided for automati-
cally by the boiler load control system.
If this is not the case, a time switch should be fitted in series to OC to provide for burner shut-down at least once every 24 hours.
- Do not invert the neutral with the phase wire in the electricity supply line.
- Only use original spare parts to replace the components.
WARNING
15
APPENDIX - PROCEDURE TO REFER BURNER OPERATING CONDITION AT AN ALTITUDE AND/OR AT A COM-
BUSTION SUPPORTER AIR TEMPERATURE DIFFERENT TO THE STANDARD VALUES (328 FT ABOVE SEA
LEVEL, 68 °F).
AIR TEMPERATURE
Altitude Altitude bar. press. bar. press. 0 5 10 15 20 25 30 40 °C
ft a.s.l. m a.s.l. "w.c. mbar 32 41 50 59 68 77 86 104 °F
0 0 399 1013.00 1.087 1.068 1.049 1.031 1.013 0.996 0.980 0.948
328 100 394 1000.00 1.073 1.054 1.035 1.017 1.000 0.983 0.967 0.936
1.000 305 385 977.40 1.049 1.030 1.012 0.994 0.977 0.961 0.945 0.915
2.000 610 371 942.80 1.012 0.994 0.976 0.959 0.943 0.927 0.912 0.883
3.000 915 358 908.20 0.975 0.957 0.940 0.924 0.908 0.893 0.878 0.850
4.000 1.220 345 875.80 0.940 0.923 0.907 0.891 0.876 0.861 0.847 0.820
5.000 1.525 332 843.50 0.905 0.889 0.873 0.858 0.844 0.829 0.816 0.790
6.000 1.830 320 811.85 0.871 0.856 0.841 0.826 0.812 0.798 0.785 0.760
7.000 2.135 307 779.80 0.837 0.822 0.807 0.793 0.780 0.767 0.754 0.730
8.000 2.440 294 747.80 0.803 0.788 0.774 0.761 0.748 0.735 0.723 0.700
F - Correction factor of discharge head and delivery in relation to temperature and altitude.
Reference conditions:
Example
Using the , for an altitude of 3000 ft and an air temperature of 68 °F, an F factor value is obtained equal to 0.908;
if the capacity at the boiler furnace is Qfoc = 4.500 Mbtu/h, the correct output will be equal to:
Qburner = Qfoc / F = 4.500 / 0.908 = 4.956 Mbtu/h
16
APPENDIX - SPARE PARTS LIST
88
33
42
17
3471070
3471470
3471470
3471270
3471670
3471670
3471675
N. CODE DESCRIPTION BURNER SERIAL NUMBER
*
1 3012985 • FAN C
1 3012986 • • • FAN C
1 3003760 • • • FAN C
2 3003758 • • • • • • • DRIVE COUPLING A
3 3003830 • • • • • • • SOUND DAMPING
4 3012090 • • • • • • • AIR INTAKE
5 3013030 • • • • • • • PUMP C
6 3012063 • • • • • • • GRADUATE SECTOR
7 3003879 • • • • • • • SPRING 02394000000 A
8 3003843 • • • • • • • SCREW C
9 3012064 • • • • • • • LEVER 02394000000 C
10 3003841 • • • • • • • BEARING B
11 3012988 • • CAPACITOR 45 µF
11 20063531 • CAPACITOR 20 µF
12 3003763 • • • • • • • INSPECTION WINDOW
13 3003776 • • • • • • • SCREW
14 3012987 • • • • • • COVER
14 3013873 • COVER
15 3003766 • • • • • • • SCREW
16 3007627 • • • • • • • MEMBRAN
17 3012953 • • • • • • • SOCKET
18 3007079 • • • • • • • SEAL C
19 3013037 • • • • • • • CONNECTOR C
20 3012622 • • • • • • • DRIVE DISK
21 3012993 • • MOTOR 120V C
21 3012994 • • • MOTOR 208-230/460V C
21 3013057 • • MOTOR 575V C
21 3013869 • MOTOR 120V C
22 3003777 • • • • • • • BAR C
23 3003778 • • • • • • • SHORT SHAFT
24 3006216 C5360027 • • • • • • • FLAME SENSOR A
25 3003780 • • • • • • • FAIRLEAD
26 3012933 C5830009 • • • • • • • CONTROL BOX LAL 2.25 B
27 3012127 • • • • • • • SPACER
28 3012991 • • • OVERLOAD 208-230/460V C
29 3012989 • • CONTACTOR C
29 3012990 • • • • CONTACTOR C
29 20049911 • CONTACTOR C
30 3012747 • • • • • • SUPPORT
30 3013871 • SUPPORT
31 3012938 • • • • • • • TRANSFORMER C
32 3012080 • • • • • • • SWITCH C
33 3012092 • • • • • • • SUPPORT
34 3003082 • • • • • • • FILTER A
35 3012089 • • • • • • FRONT SHIELD
35 3013872 • FRONT SHIELD
36 3012094 • • • • • • • SUPPORT
37 3012095 • • • • • • • NUT
18
3471070
3471470
3471470
3471270
3471670
3471670
3471675
N. CODE DESCRIPTION BURNER SERIAL NUMBER
*
38 3012995 • • • • • • • H.T.LEAD A
39 3003081 • • • • • • • SEAL C
40 3003796 • • • • • • • ELECTRODE A
41 3003495 • • • • • • • U BOLT
42 20066897 • • • • • • • NOZZLE HOLDER ASSEMBLY C
43 3013874 • PROTECTION
44 3003797 • • • • • • • CONTROL DEVICE
45 3003798 • • • • FRONT PIECE
45 3003838 • • • FRONT PIECE
46 3012098 • SQUARE
46 3012099 • • • SQUARE
46 3012100 • • • SQUARE
47 3003805 • • • • SHUTTE C
47 3003806 • • • SHUTTER C
48 3012101 • END CONE B
48 3012102 • • • END CONE B
48 3012103 • • • END CONE B
49 3013064 • • • • • • • CONNECTOR C
50 3003893 • • • • • • • CONNECTOR C
51 3012104 • DIFFUSER DISC A
51 3012106 • • • DIFFUSER DISC A
51 3012108 • • • DIFFUSER DISC A
52 3012110 • • • • • • • ANCHOR PLATE
53 3012111 • • • • • • • HALF-SHELL
54 3013016 • • • • • • • COIL B
55 3013015 • • • • • • • LEAD A
56 3012112 • • • • • • • TUBE
57 3012113 • • • • • • • TUBE
58 3012114 • • • • • • • SHORT SHAFT
59 3012115 • • • • • • • LEVER C
60 3012116 • • • • • • • BEARING
61 3012117 • • • • • • • ANCHOR PLATE
62 3012118 • • • • • • • CAM ASSEMBLY
63 3013005 • • • • • • • STUD
64 3013032 • • • • • • • SUPPORT
65 3013008 • • • • • • • SERVOMOTOR B
66 3013033 • • • • • • • SHAFT
67 3012121 • • • • • • • SEAL C
68 3012122 • • • • • • • MODULATOR B
69 3012123 • • • • • • • CONNECTOR C
70 3007077 • • • • • • • SEAL C
71 3012617 • • • • • • • SCREW C
72 3006140 • • • • • • • PRESSURE GAUGE A
73 3007169 • • • • • • • O RING A
74 3013034 • • • • • • • AIR DAMPER ASSEMBLY
75 3012124 • • • • • • • TUBE
76 3006540 • • • • • • • NEEDLE VALVE B
77 3012952 • • • • • • • NEEDLE VALVE B
19
3471070
3471470
3471470
3471270
3471670
3471670
3471675
N. CODE DESCRIPTION BURNER SERIAL NUMBER
*
78 3013035 • • • • • • • CONNECTOR C
79 3013036 • • • • • • • CONNECTOR C
80 3009087 • • • • • • • CONNECTOR C
81 3006720 • • • • • • • CONNECTOR C
82 3006722 • • • • • • • CONNECTOR C
83 3013058 • • • • • • • CONNECTOR C
84 3012954 • • • • • • • SCREW C
85 3012384 • • • • • • • OIL PRESSURE SWITCH B
86 3012950 C5360001 • • • • • • • CONTROL BOX BASE
87 3013478 • • • • • • • SPRING - LEVER 02404000001 A
88 20088026 • • • • • • • NOZZLE HOLDER C
*
ADVISED PARTS
A = Spare parts for minimum fittings
A+B = Spare parts for basic safety fittings
A+B+C = Spare parts for extended safety fittings
20
BURNER START UP REPORT
OIL OPERATION
Oil supply pressure: CO2: Low Fire High Fire
Oil suction pressure: O2: Low Fire High Fire
Control Power Supply: CO: Low Fire High Fire
Burner Firing Rate: NOX: Low Fire High Fire
Low Fire Flame Signal: Net Stack Temp - Low Fire: High Fire
High Fire Flame Signal: Comb. Efficiency - Low Fire: High Fire
Low Fire Nozzle Size: Overfire Draft:
High Fire Nozzle Size: Smoke number:
CONTROL SETTINGS
Operating Setpoint: Low Oil Pressure:
High Limit Setpoint: High Oil Pressure:
Flame Safeguard Model
Low Gas Pressure:
Number:
High Gas Pressure: Modulating Signal Type:
NOTES
21
RIELLO S.p.A.
I-37045 Legnago (VR)
Tel.: +39.0442.630111
http:// www.riello.com