DK9203A2 - PV350b User Manual ENG
DK9203A2 - PV350b User Manual ENG
DK9203A2 - PV350b User Manual ENG
User manual
DK9203A2
PV350b pellet burner p 2/36
Table of Contents
Tables................................................................................................................................................3
Safety precautions.............................................................................................................................4
Warnings...........................................................................................................................................4
Notice................................................................................................................................................4
1 Set of components..........................................................................................................................6
2 General description........................................................................................................................7
2.1 Safety devices......................................................................................................................10
2.2 Pellets...................................................................................................................................10
3 Installation...................................................................................................................................11
3.1 Prerequisites.........................................................................................................................11
3.2 Burner installation................................................................................................................13
3.3 Powder extinguishing system..............................................................................................15
3.4 External auger......................................................................................................................15
3.5 Pellet storage........................................................................................................................16
3.6 Electrical connections..........................................................................................................16
3.7 External inverters.................................................................................................................17
3.8 Internet module....................................................................................................................17
3.9 Initial start-up.......................................................................................................................17
4 Optional components...................................................................................................................18
4.1 Error output..........................................................................................................................18
4.2 Flue gas fan..........................................................................................................................18
Burner setup...............................................................................................................................19
Inverter setup.............................................................................................................................19
4.3 Oxygen sensor......................................................................................................................20
4.4 Ash removal system.............................................................................................................20
4.5 External boiler temperature sensor (TMP1 or X23)............................................................21
4.6 External boiler pressure sensor (TMP1 or X23)..................................................................22
5 Operation and service..................................................................................................................23
5.1 User interface.......................................................................................................................23
5.2 Starting and stopping...........................................................................................................24
5.3 Fuel refilling.........................................................................................................................24
5.4 Status and parameters..........................................................................................................24
5.5 Regular maintenance............................................................................................................32
6 Annex 1 Electrical connections...................................................................................................33
6.1 Fuses....................................................................................................................................35
7 Warranty.......................................................................................................................................36
PV350b pellet burner p 3/36
Tables
Safety precautions
Do not start the burner before it is connected to the boiler and the boiler is connected to the
chimney.
It is recommended to wear a respirator while handling pellets.
The boiler room where the burner is installed must fulfil all rules and recommendations given by
authorities.
All electrical connections must be done by trained professionals.
No flammable materials must be stored near the burner.
Warnings
Changing the construction of the burner without written permission from the manufacturer is
forbidden.
Use only spare parts provided or approved by the manufacturer in order to avoid any damage to
the burner and dangers resulting from it.
Welding is allowed only after disconnecting the burner from electric supply. The circuit board
must be removed from the burner.
Do not open any boiler door while the burner is in operation.
Notice
Manufacturer of burner has right to make changes in construction of burner and its firmware.
Burner corresponds to following directives and standards:
Directive 2004/108/EC
Directive 2006/95/EC
Directive 2001/95/EC
Directive 2006/42/EC
EN 15270 2008
EN 230 2005
EN 60370-2-5 2002
1 Set of components
2 General description
PV350b is a burner of wooden pellets (sawdust granules) that is intended for heating of the industrial
and public buildings. Only 6 or 8mm wooden pellets can be used to run this burner. You cannot use any
other form of fuel. Unique design of the burning chamber allows using industrial pellets run the burner.
The construction allows burner to be used with different boilers: liquid fuel, solid fuel and universal
boilers. The burner is connected to the boiler by using a connection plate.
The burner is equipped with a melting hose, extinguishing system and auxiliary battery for protection
against back-burning. Main technical data is gicen in Table 1 and Figure 1.
Table 1 Technical data of burner
Nr Name Description
1 Back wall fire brick To cover back side of burning chamber.
2 Arc fire bricks 6pcs To cover the top of burning chamber.
3 Side fire bricks 4pcs To cover the sides of burning chamber.
4 Burning chamber Place of gasification and burning of pellets.
5 Grates 2+3pcs Moving grates to remove ash from the burning chamber. 2 grates with
smaller hole are placed before 3 grates with bigger holes.
6 Igniter 2pcs Electrical heating element to ignite pellets.
7 Internal feeder spiral Transports pellets to the burning chamber. The feeder is connected to
feeder motor with little slack. It prolongs motor and feeder lifetime. Do not
over tighten the feeder connection.
8 Secondary fan Blows burning air into burning chamber according to burner’s actual
power.
9 Feeder motor Rotates internal feed screw. The feeder is connected to feeder motor with
little slack in order to avoid the auger get stuck.
10 Burner’s socket To internal and external electrical connections.
11 User interface Enable to navigate in burner menus and change parameter values.
12 User interface screen 4-row LCD screen to move in menus, set up and change parameter values.
13 Air box To control air input and fixate burner to boiler’s door.
14 Fixating flange To adapt fixation of burning chamber to boiler’s door.
15 Flame sensor Optical sensor (photocell) to detect flame in burning chamber.
16 Powder To fast extinguishing of fire in feeder’s tube.
extinguishing system
17 Fuel level sensor Optical sensor, which signal starts external auger. Sensor consists of
sender – receiver pair.
18 Internet module Gives possibility to observe and control the functioning of the burner over
the internet.
19 Backup battery 2pcs Enables to complete the burning procedure if mains supply lost. It is a
safety measure against back-burning and takes approx. 30min.
20 Linear motor Moves grates in order to remove ash from burning chamber.
21 Controller board Controls the functioning of the burner.
22 Primary fan Blows burning air into burning chamber according to burner’s actual
power.
23 Burners input tube To be connected via hose with external auger. Supplies burner with pellets.
The back-burning is the biggest danger risk at burners working procedure. Back-burning appears when
usual pressure or draught conditions have changed in boiler’s combustion chamber. There are several
reasons for such changes.
In order to secure operational and fire safety the burner PV350b is equipped with following safety
devices:
Back up batteries. Enable to safely empty the pellets inside the burners internal tube into the
burning chamber in case of unexpected power outage.
Melting hose. The external auger is connected to the burner with a special hose (Ø 76mm), which is
made from easily melding polyurethane material that interrupts when back-burning takes place.
Such measurement avoids entrance of the flame from the burner into external auger and pellets
Powder extinguishing system. Enables to extinguish the fire inside the burner internal tube by filling
it with extinguishing powder when the burner has overheated or burned back due to some fault.
2.2 Pellets
Wooden pellets or saw dust granules are concentrated and homogenized wooden fuel made from
sawdust and cutter shavings. Pellets are pressed with high temperature. No extra materials are added,
pellets are held together by a natural ingredient found in wood – lignin. Pellets are neutral, renewable
fuel. Its burning doesn’t spoil CO2 balance in the atmosphere. Not only premium but also the industrial
pellets can be used in PV350b. Pellets must be stored in a dry and ventilated room. Some key data for
industrial and premium wooden pellets are given in Table 3.
3 Installation
3.1 Prerequisites
In order to install the burner, the boiler must meet the following requirements:
It is recommended to use three pass boilers.
The construction of the boiler must make it possible to open the door of the boiler with the
burner connected and removing ash from the furnace. If the door of the boiler is too narrow for
opening it together with the burner, then extra hinges must be mounted.
The boiler must be positioned in a way that there is enough space for cleaning the burner, the
boiler, the smoke pipe and removing the ash.
The burning chamber must not touch the bottom of the boilers furnace (min 10cm distance
needed).
To ensure negative pressure in the furnace, a flue gas fan should be installed.
Boiler room must provide constant air supply of 500 m³ per hour (ca. 400 cm2 air inlet opening).
The boiler room where the burner is installed must fulfil all rules and recommendations given by
local authorities.
In order to install the burner to the boiler door, there must be mounting holes as shown below.
Note: If the burner is installed to the boiler, the door or the installation flange´s thickness should be 8-
14mm.
Minimum dimensions:
L1 ≥700mm
H ≥600mm
Pellet burners need regular cleaning and therefore boiler construction must allow easy opening of
boiler’s door without removing the burner. The minimum size of opening in boiler’s door depends on the
position of door hinges. Figure 5 below illustrates the situation. Point C is critical point. In order to keep
door width minimum and boiler’s door opening small, a double hinge solution can be used. As double
hinges add another degree of moving-freedom, door must be fastened on both sides. Slide-out doors
with guide rails is also an option.
1
NR.1 Connect the flange with M12
bolts to the boilers door. Bolt
length should be chosen according
2
to the doors thickness.
Figure 7
PV350b pellet burner p 14/36
Figure 8
5
5
Figure 9
PV350b pellet burner p 15/36
All PV350b burners, that are manufacture later than the 1. January 2017 are equiped with powder
extinguishing system. System is autonomous and only requires removing the safety latch. NB! Before
activating the system please read the user manual.
Activating the system before reading the manual is forbiden and could result in an
accidental opening of the extinguisher !!!
3.4 External auger
The external auger transports pellets from the pellet container to the burner. The auger is controlled by
burner. The auger is connected to the burner with a special hose (∅ 76mm), which is made from easily
melting polyurethane material that melts when back-burning takes place. The hose acts as a safety
measure against back-burning. PV350b pellet burner´s fuel consumption at full power is about 77 - 80 kg
of pellets per hour (1,3 kg per minute ). External auger´s productivity must be at least 120kg of pellets
per hour. The auger can be fixed to the storage or a ceiling depending on the conditions at the installation
site.
>20cm
>60cm
>65 o
max45 o
Pellets must be stored in a dry and ventilated room that is separated from the boiler room. A tailor made
silo for particular storage is recommended. All safety regulation must be taken into consideration
according to the local laws. It is recommended to wear a respirator when handling pellets. Refilling must
be carried out before the storage runs empty.
Burner gets its main supply from 230V single phase supply (socket X11), but also needs 400V 3-phase to
socket X12 to run inverters and augers. Boiler should be equipped with thermostat or external switch
what has to be connected to pins T1 and T2 in 7- pole plug X11 for turning on/off the pellet burner. Auger
motors contactors are equipped with motor thermal protection, which prevent motor from overheating.
As soon as the nominal current of the sensor set-point is exceeded, the relay detects this variation and
the output relay cuts off the power to the motor. Burner can be equipped with optional lambda sensor. It
provides efficient control for optimal performance concentrating emissions and burning efficiency.
Flue gas fan can be controlled by external inverter. Following configuration must be made:
Before connecting the external inverter pleas look into the connection diagram.
Every PV350b burner has an internet module in standard equipment. It is located next to the burner
controller under the red cover. The module itself is connected to the MOD1 connector, located on the
controller. For the internet module to work, it has to be connected to the internet with a CAT5 cable. To
observe and control the burner, you have to login in to the page: „cloud.pelltech.eu”. Login data can be
found on the module. To get more info about the internet module, please read the instruction manual or
contact your local reseller.
4 Optional components
PV350b burner has built in error output what gives 230 VAC tension (NO) to 7-pole socket’s S3 connector
or interrupts it (NC) if burner delivers any error message (E16 FLAME, E48 BATTERY,E24 IGNITION etc).
Device (motor, modem etc) up to 5A@230VAC can be connected to circuit. PAR50 defines weather error
output is closed or open during error appearance. Depending on NO or NC selection values in PAR50
have to be changed.
The burner needs stable under-pressure in burning chamber for its correct operation. Simplest way to
assure this is to use the flue gas fan between boiler and chimney. With flue gas fan the burner can control
and hold constant under-pressure. In order to control flue gas the PAR60 value has to be set to”2”
Inverter. Selected flue gas fan must provide transmission of the maximum flue gas amount and exceed
the pressure provided by boiler, ash cyclone and chimney. The flue gas capacity for burned pellets can be
calculated by simplified formula.
Burner setup
Depending on burner’s configuration (weather inverter included or not) the electrical connections may
be different. In case the frequency inverter has already been installed in factory to the burner, the flue
gas fan can be directly connected to the burner through connector X21. Fan must be connected to burner
with 3-wire cable (3x1. 5mm²). Internal inverter output is 3 x 240V. Flue gas fan motor has to be
connected as delta.
In case the burner is ordered without Flue gas inverter, the external inverter for flue gas fan can be used.
Inverter must be selected according to fan motor’s parameters and available power supply. The inverter
must be switched to sink logic (negative common).
To connect the external inverter with burner there is connector X20 with 3 output signals:
• T1 - burner DC common (ground), must be connected with external inverter input common.
• 3 – inverters “run” command, must be connected with F (forward) pin on inverter input. Burner
will connect this pin to ground when fan must run.
• B4 – 0… 10V output for fan speed, must be connected with inverter analog input.
Inverter setup
Inverter parameters are set up at factory for automatic control. To test flue gas fan manually:
1. Press Easy button on inverter
2. Press dial button and change settings :
a. CN0D “0”
b. FN0D “0”
c. F127 “0”
PV350b pellet burner p 20/36
To use the oxygen sensor for measuring the oxygen levels in the flue gases, two parameters have to be
adjusted in the parameters menu: PAR66 and PAR67.
For lambda sensor EP0006, the PAR66 value has to be set to “1”. Some third party oxygen amount
sensors use 4…20mA output for 0…20% oxygen. In this case, value “2” must be selected.
If PAR66 is set to “0” (no sensor), secondary fan is driven by air table set in PAR31 – PAR36. Secondary fan
also switches back to air table if oxygen level reading is below 1.5% or over 19%. Oxygen sensor should
be placed into smoke tubing after the boiler. Placement has to be chosen so that the turbulance of the
gases is minimal in that place. That means that it isn’t recommended to place the sensor after tight turns
or other measuring equipment.
Oxygen level can be seen in INFO-menu next to pressure reading. The value on the screen must be
divided by 10 to get the real value. For example “O2=113” means oxygen level value 11.3%.
The burner is capable to control boilers ash removal auger and scrapes. To do that burner has a 3phase or
a 1 phase output connectors where you can connect the ash removal system motors. Connector X29 has
one motor 3 phase output and X25 is able to control two 1 phase motors.
PV350b pellet burner p 21/36
External temperature sensor enables the burner to maintain constant boiler’s water temperature. For
that external temperature sensor has to be installed to relevant place on boiler and external sensor to be
connected to connector TMP1 or X23. In parameters menu PAR53 value has to be chosen “1”.
When temperature holding status is activated, then burner will change its power according to water
temperature and speed of temperature changing. Burner starts to change its power when BURNING
status has lasted longer than set in PAR15. Power is changed according to next parameters: PAR 17
defines the time between power raises, PAR 18 defines the time between power lowering.
Temperature sensor could be PT100, sensor with mA output or a sensor provided by the burner
manufacturer. Different sensors need different hardware that can be selected with JP1 and JP2.
Configuration for sensors is as followed:
PT100
PV350b pellet burner p 22/36
External pressure sensor enables the burner to maintain constant pressure in boiler. For that external
pressure sensor has to be installed to relevant place on boiler and external sensor to be connected to
connector TMP1 or X23. In parameters menu PAR53 value has to be chosen larger than “1o”.
When pressure holding status is activated, then burner will change its power according to boiler pressure
and speed of pressure changing. Burner starts to change its power when BURNING status has lasted
longer than set in PAR15. Power is changed according to next parameters: PAR 17 defines the time
between power raises, PAR 18 defines the time between power lowering.
The burner is controlled by user interface on the front panel. LCD screen (1) displays settings menu, event
log and actual statuses of the burner. Yellow LED (2) shows the presence of flame in burning chamber. In
case it blinks, the burner is out of normal operation. Green LED (6) indicates existence of fuel in the
burner. To move in menus, use up and down (↑↓) buttons, to change parameter, press OK, to go back to
STATUS menu press left button. On Figure 12 are described additional parts on the burner cover.
To turn on the burner, turn on the boiler main switch. If burner displays STOPPED, then go to STATUS
menu and change parameter BURNER from OFF to ON. The display shows WAITING. Now turn boiler
thermostat to desired temperature. The burner will go to TESTING and then to LOADING-state. If this is
the first run, external auger needs to fill up with pellets. It may take as long as 20minutes.
To stop the burner, set BURNER from ON to OFF in main menu. Now the burner will burn all pellets in
burning chamber and turn safely to standby.
STATUS menu displays the changes:
BURNING → END BURN → END BLOW → STOPPED
The stopping procedure may take up to 30 minutes.
Attention! If necessary the burners working command can be switched from ON to OFF with the switch
on the burner cover.
Caution! Do not turn off mains power to terminate burning process. Use the boilers thermostat for that.
In order to complete burning procedure safely let the burner to burn all fuel in burning chamber. Never
leave burner unattended when you had to stop boilers work by switching off main power.
Fuel container has to be refilled before its runs out. The fuel can be added any time to container. If
container runs out before refilling, refill it and restart the burner. The start-up takes now longer about 20
minutes, because external auger has to be filled with pellets like on initial start-up. Turn burner from
BURNER menu ON. Vice versa the “E04 PELLETS” error is displayed, because loading time is exceeded.
PV350b pellet burner operates in many different states, which are called “Status”. Log screen STATUS
menu displays last and actual events (burner statuses) and their duration. Burner changes its statuses
based on received input signals from sensors and values set by user. The statuses in typical working order
of cycles are given in Table 8. The duration of all actions are in form mm:ss (’m’ in the middle), hh:mm
(’h’ in the middle) or dd:hh (‘d’ in the middle). For example: ’IGNITING 01m25“means the burner ignition
state lasted 1 minute and 25 second.
Lower row of the log shows burner’s current state. To reach the lower row, press the “down”(↓) button,
until you reach the lower row with current state. The duration of current state updates every second or
every minute. Changed data blinks.
PV350b pellet burner p 25/36
Boiler’s thermostat is switched on, testing the battery, fans, feeder and draught in
TESTING
progress.
LOADING Loading pellets with auger into burner and by feeder into burning chamber.
PRE-BURN Flame is recognized, small amount of pellets are added by feeder auger.
END BLOW Pellet coals in burning chamber are burnt, flame has disappeared.
At WAITING status, the burner waits for boiler’s thermostat switching on. There is no time limit for
WAITING status. Only feeder auger is working periodically at WAITING status and makes works for one
second after every 2 minutes. With this feeder augers spiral cleans feeder’s tube from wastes.
When boilers thermostat switches on, burner will go to TESTING.
At TESTING status, burner‘s integrity and important device functioning are checked. List of tests is given
in Table 9 .
PV350b pellet burner p 26/36
At CLEANING status, the linear motor (actuator) moves the grates and pushes the ash and residues out of
burning chamber.
The CLEANING cycle might be divided into 2 steps:
1. Grates are pulled fully into the burning chamber’s burner side.
2. Grates are pushed fully out to end of boiler’s side.
3. Grate are pulled into the starting position
At the LOADING status, external auger is turned on. When pellet level in the burner reaches to level
sensors, feeder auger is started. Feeder auger loads necessary amount of fuel needed for ignition into
burning chamber. Anount of fuel loaded is measured by counting the feeders working time. LOADING
cycle will end when feeder has worked the time defined in PAR24.
PV350b pellet burner p 27/36
In LOADING state the auger holds permanent fuel level in burner pellet inlet. Depengin on the level
sensors signal, the auger is switched on and off. Feeder’s work also depends on level sensors. Maximum
loading time is limited to 20 minutes after first start or error, because long auger systems need some time
to fill up. In next loadings, maximum time is limited to 5 minutes. If maximum loading time is exceeded
and silo selection function is used, the burner will switch loading over to the second auger. In single silo
system, error E04 PELLETS is displayed.
At IGNITING cycle the igniter is heated up and fan blows hot air on pellets in burning chamber. Hot air
ignites pellets. Igniter is working periodically at ignition time in order to avoid its overheating.
Igniter is pre-heated already in the end of loading cycle, 20 seconds before the loading feed end. If the
igniter has been turned on for more than 1 minute at loading time, the it will be turned off.
The purpose of PRE-BURN status is to create stable flame and assure effective pellets burning procedure
after ignition. Minimum fuel amount is added periodically at pre-burn time. Fans are working with same
speed as at IGNITION.
HEAT UP cycle is needed to slow down heating up of the burning chamber’s ceramic stones in order to
minimize their thermal stress and thus prolong their lifetime.
When HEAT UP is in mode ON - burner stops HEAT UP cycle after heat up time set in PAR70 is exceeded.
When HEAT UP is in AUTO mode - burner stops HEAT UP cycle after time set in PAR70 is exceeded or
stone temperature is higher than set in PAR72.
Power
level
7
6 Power level can be selected in main menu. Power
Selected power
5 level selection for burning time can be automatic
4 or fixed on some main level. When power level is
3 fixed, the power is slowly raised to selected level
2 and will be there until boiler thermostat switches
1 off.
Par 17
Burning time
2 2 2 min
In Automatic Power mode (POWER = AUTO in main menu), the operation power is selected automatically
depending on burning cycle length.
Power level
Figure 15
14 SLOW
BurningDOWN
procedure
modewhen power selection = AUTO
PV350b pellet burner p 30/36
In SLOW DOWN mode, the burner power is reduced step-by-step to 1 level after boiler thermostat is
switched OFF. This mode can be used only in systems with high and stable power demand. Using SLOW
DOWN mode in systems with low thermal inertia or unstable power demand, there will be risk of system
overheating. The SLOW DOWN mode is recommended to use together with HOLD FLAME. “SLOW
DOWN” mode can be switched ON or OFF from main menu.
Power
level
Thermostat ON
7
Thermostat OFF
6
Operation power
5
4 Par 17
3 Par 18
2
„Burn end“
1
OR
„Slow „Hold flame“
„Burning“ down“ „Burning“ „Slow down“
Status/time
The purpose of HOLD FLAME mode is to avoid burner start-up procedures i.e TESTING, CLEANING,
LOADING, IGNITING etc. every time, when burner is switched on from boiler thermostat. In HOLD FLAME
mode, minimum fuel and air amount are delivered to burning chamber. HOLD FLAME mode can be
switched on from burner main menu. When HOLD FLAME is set to AUTO, burner will turn the mode ON
or OFF depending on WAITING time:
If WAITING (time between END BLOW and boiler thermostat switched on) is shorter than set in PAR
11, then HOLD FLAME mode will be switched on.
If HOLD FLAME time is longer than set in PAR12, HOLD FLAME mode is switched off.
HOLD FLAME is also used as intermediate state before CLEANING or after SLOW DOWN.
The END BURN cycle helps securely to stop burning procedure in burning chamber of burner. All pellets
inside the burning chamber and feeder tubes will be burnt. Amounts of pellets delivered and fan rotation
speed (power level) are same as in BURNING status. If burner goes to END BURN from other states (e. g.
HOLD FLAME), the first power level is selected. Burner works in END BURN until feeder tube is empty -
feeder has worked as long as described in PAR26.
The END BLOW cycle is needed to burn finally all unburned pellet coals in the burning chamber. Burner
will wait for flame disappearing in burning chamber. In PAR27 is fixed the end blow time, i.e. the time
how long the fans continue to blow after flame’s disappearing.
The burning chamber of pellet burner PV350b is equipped with automatic self-cleaning and ash removing
systems. When system works regularly, there is no need to clean the burning chamber separately. Still the
corners and edges of the burning chamber should be monitored for ash and other deposits. If needed
cleaning must be done. Only the boiler needs regular cleaning and maintenance. Despite burner has self-
cleaning ash removing system, nevertheless the ash collects under and on grates. That’s why at least
twice a heating period the grates need cleaning. The frequency of maintenance depends on quality of
pellets and intensity of heating.
Despite burner has self-cleaning system the boiler has to be cleaned from collected ash and non-
burning residues. Manufacturer of pellet burners don’t prescribe time period between cleaning.
The ash and non-burning residues are perfect heat insulators. If burning chamber is surrounded with
ash and non-burning residues so its normal ventilation is distracted. It causes fast overheating, out-
burning and deformation of the burning chamber.
ATTENTION! BOILER HAS TO BE CLEANED FROM ASH AND NON-BURNING RESIDUES BEFORE THEY GET
IN TOUCH WITH BURNERS BURNING CHAMBER.
Figure 16
PV350b pellet burner p 35/36
6.1 Fuses
7 Warranty
Warranty objects in this context are pellet burner PV350b and supplied auger.
Producer gives 2 years warranty from the date of sale for the PV350b burner and supplied auger.
Warranty is valid when user had not made changes in the construction and setup of the burner.
Warranty does not cover defects caused by an accident, misuse, abuse, improper installation or
operation, lack of reasonable care, unauthorized medication, loss of parts, tampering, attempted repair
by a not authorized person, mains errors or using poor quality fuel.
Warranty is valid only if the installers memorandum is filled in and sent or brought to the office of
Pelltech OÜ Sära tee 3, Peetri, Rae vald, 75312 Harjumaa ESTONIA
Installation date:
Installer: Name / Company name / Phone/ e-mail/ Signature
Installation protocol must be filled in web at cloud.pelltech.eu or on paper. Photo of the filled form must be sent to
siim@pelltech.eu . Without photo or filled form in internet, the warranty is void.