Control Narrative Reference Information
Control Narrative Reference Information
The heating value is essential to tell the Heater Duty Controller how much
fuel gas is necessary to maintain the required heat input. There are
several technologies such as Thermal conductivity, gas chromatography
and Wobbe index Analyzers available today to provide heating value of
the gas.
Wobbe index is calculated from heating value and specific density of the
flue gas, according to ISO EN 6976-2005.
Cracking Furnace/Heater’s Burners – Heater Duty Controller
Where,
• Cf= Compensating Factor
• Design Press = P
• Design temperature = T
• Reference Pressure = Pb (42.67 PSI-g)
• Reference Temperature = Tb (100Deg F )
• Absolute Temperature = To (273.15 Deg Farenheit)
Cracking Furnace/Heater’s Burners – Low Pressure Override scenario
In Low Fuel Gas Pressure Scenario, Burner Fuel Gas Pressure Controller
overrides Heating Duty Controller, opening the valve to allow minimum
firing rate of the burners.
Additionally, this pressure controller has been furnished with Burner Firing
Control during heater start-up and decoke, when the fuel flow rates are
less than the minimum turn down limitations of fuel flow meter.
Schematic and Control Narrative
Displayed on the screen are the tag IDs, controller and function blocks for the P&ID for your reference.