ACS880-307 - A018 - HW Manual - A - A4
ACS880-307 - A018 - HW Manual - A - A4
ACS880-307 - A018 - HW Manual - A - A4
Hardware manual
ACS880-307 +A018 diode supply units
List of related manuals
General drive manuals Code (English)
Safety instructions for ACS880 multidrive cabinets and 3AUA0000102301
modules
Mechanical installation instructions for ACS880 multidrive 3AUA0000101764
cabinets
Electrical planning instructions for ACS880 multidrive 3AUA0000102324
cabinets and modules
ACS-AP-x Assistant control panels User's manual 3AUA0000085685
You can find manuals and other product documents in PDF format on the Internet. See section
Document library on the Internet on the inside of the back cover. For manuals not available in the
Document library, contact your local ABB representative.
Hardware manual
ACS880-307 +A018
diode supply units
Table of contents
3. Electrical installation
5. Start-up
Table of contents
3. Electrical installation
Contents of this chapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Basic electrical safety precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Checking the insulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Supply unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Supply cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Connecting the input power cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Connection diagram – 6-pulse supply unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Connection diagram – 12-pulse supply unit (option +A004) . . . . . . . . . . . . . . . . . . . 42
Connection procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Connecting the external power supply cable for the auxiliary circuit (option +G307) . . 45
Wiring the functional safety options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Connecting the control cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Control cable connection procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Grounding the outer shields of the control cables at the cabinet lead-through . . 46
Routing the control cables inside the cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Connecting a PC to the supply unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
4. Installation checklist
Contents of this chapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
5. Start-up
Contents of this chapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Start-up procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Basic checks with no voltage connected . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Connecting voltage to input terminals and auxiliary circuit . . . . . . . . . . . . . . . . . . 54
Setting the supply unit parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Switching the supply unit on . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
On-load checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Switching off the drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Disconnecting and temporary grounding the drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Disconnecting – excluding the input power cable terminals . . . . . . . . . . . . . . . . . . . 56
Disconnecting – including the input power cable terminals . . . . . . . . . . . . . . . . . . . . 56
6. Maintenance
Contents of this chapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Maintenance intervals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Cleaning the interior of the cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Cleaning the air inlet meshes – IP22 and IP42 (option +B054) . . . . . . . . . . . . . . . . 59
Replacing the inlet (door) filters – IP54 (option +B055) . . . . . . . . . . . . . . . . . . . . . . 60
Replacing the outlet (roof) filters – IP54 (option +B055) . . . . . . . . . . . . . . . . . . . . . . 61
Power connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Tightening the power connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Checking and replacing the D7T module DC fuses . . . . . . . . . . . . . . . . . . . . . . . . . 62
Checking and replacing the D8T module DC fuses . . . . . . . . . . . . . . . . . . . . . . . . . 63
Checking and replacing AC fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Fans . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
7
7. Technical data
Contents of this chapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Derating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Ambient temperature derating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Altitude derating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Supply module types and frame sizes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Module DC fuses (internal) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Module-specific AC fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Fuses on CVAR board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Dimensions and weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Free space requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Losses, air flow, efficiency and noise . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Terminal and lead-through data for the input power cable . . . . . . . . . . . . . . . . . . . . . . . 92
400 mm incoming cubicle – main switch (+F253) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
600 mm incoming cubicle – main switch (+F253), 6-pulse . . . . . . . . . . . . . . . . . . . . . 93
600 mm incoming cubicle – main switch (+F253), 12-pulse (+A004) . . . . . . . . . . . . . 94
600 mm incoming cubicle – main breaker (+F255) . . . . . . . . . . . . . . . . . . . . . . . . . . 95
1000 mm incoming cubicle – main breaker (+F255) . . . . . . . . . . . . . . . . . . . . . . . . . 96
Electrical power network specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Control unit connection data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Efficiency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Protection classes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Ambient conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Materials . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Disclaimer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Markings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Tightening torques . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Cable lugs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Electrical connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Mechanical connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Insulation supports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
8
8. Control unit
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Control unit layout and connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
Default I/O connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
Additional remarks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Additional DIIL input (XDI:7) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Drive-to-drive link (X2D2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Safety functions (X12) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
SDHC memory card slot (X205) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
Control unit connector data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
Further information
Product and service inquiries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
Product training . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
Providing feedback on ABB Drives manuals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
Document library on the Internet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
Introduction to the manual 9
1
Introduction to the manual
Applicability
The manual is applicable to the cabinet-installed ACS880-307 +A018 diode supply units
that form a part of an ACS880 multidrive system.
Safety instructions
Follow all safety instructions delivered with the drive.
• Read the complete safety instructions before you install, commission, use or
service the drive. The complete safety instructions are given in ACS880 multidrive and
multidrive modules safety instructions [3AUA0000102301 (English)].
• Read the software-function-specific warnings and notes before changing the
default settings of the function. For each function, the warnings and notes are given in
the section describing the related user-adjustable parameters.
• Read the task-specific safety instructions before starting the task. See the section
describing the task.
Target audience
This manual is intended for people who plan the use of, install, start-up, use or service
multidrives. Read the manual before working on the drive. You are expected to know the
fundamentals of electricity, wiring, electrical components and electrical schematic
symbols.
10 Introduction to the manual
Related documents
The multidrive user documentation consists of technical drawings and a set of manuals.
The technical drawings are tailor-made for each drive. The composition of the manual set
depends on the composition of the drive, eg, which supply unit type, options and inverter
control program has been ordered by the customer. The manuals have been listed on the
back of the front cover.
Auxiliary control cubicle The cubicle with auxiliary devices such as auxiliary voltage circuit breakers,
control electronics, measurement boards, etc.
DI Digital input
Diode supply module Diode (or diode-thyristor) rectifier and related components enclosed inside a
metal frame or enclosure. Intended for cabinet installation.
Diode supply unit Diode supply modules under control of one control board, and related
components. See Diode supply module.
Frame (size) Physical size of the diode supply module, for example, D7T.
Term/Abbreviation Description
Inverter Converts direct current and voltage to alternating current and voltage.
Inverter module Inverter bridge, related components and drive DC link capacitors enclosed
inside a metal frame or enclosure. Intended for cabinet installation.
Inverter unit Inverter module(s) under control of one control board, and related components.
One inverter unit typically controls one motor. See Inverter module.
I/O Input/Output
Multidrive Drive for controlling several motors which are typically coupled to the same
machinery. Includes one supply unit, and one or several inverter units.
Rectifier Converts alternating current and voltage to direct current and voltage. See
Diode supply module.
2
Operation principle and
hardware description
Operation principle
The heart of the diode supply unit is a diode-thyristor bridge. It rectifies three-phase AC
current to direct current for the intermediate DC link of the drive. The intermediate DC link
supplies the inverters that run the motor. There can be one inverter unit only (single drives)
or several inverter units (multidrives) connected to the intermediate circuit. The AC choke
smoothens the current waveform in the power supply network and voltage in the DC link of
the drive.
The main difference between the ordinary diode-diode bridge and the controlled diode-
thyristor bridge is the controllability. You cannot control the operation of the diodes but you
can control the thyristors. By controlling the thyristors, you can limit the AC current of the
drive at the power up without additional charging circuit in the supply unit or in inverter
units.
14 Operation principle and hardware description
There are two control modes for the upper leg thyristor firing: the charging mode and the
normal mode:
• The charging mode is in operation a short period after the power switch on: the supply
control program controls the thyristor firing angle gradually from a large value towards
zero while the intermediate circuit capacitors located in the inverter module(s) get
charged.
• In the normal mode, the thyristor firing angle is 0 degrees: The thyristors operate as
diodes.
The following figure shows a simplified main circuit diagram of the rectifier bridge.
2
+
4
Uc
1 4
Description
1. Diodes. The diodes connect the AC terminals in cyclic sequence to the lower DC busbar (-).
2. Thyristors. The thyristors connect the AC line terminals in cyclic sequence to the upper DC busbar (+).
3. AC choke
4. DC fuses
Operation principle and hardware description 15
6-pulse connection
3
1 2
12-pulse connection
3
1 2
No. Description
1. Supply transformer
2. Switching equipment
~3
5 5 5
1
8 2
6 6 6
9 3
M M M
7 3~ 3~ 3~
No. Description
2. AC fuses
7. Motor
A B C D E
Description
A Auxiliary control cubicle (ACU). Contains control electronics and customer I/O connections. See
page 18.
B Incoming cubicle (ICU). Contains the power input cable terminals and switchgear. See pages 20
and 21.
C Supply module cubicle. Contains two D8T supply modules. See pages 22, 23 24 and 25
D Inverter module cubicle. Contains two R8i inverter modules. As standard, the motor cables are run
from each inverter module. See ACS88-107 inverter units Hardware manual
[3AUA0000102519 (English)].
E Inverter control cubicle. Contains inverter control unit.
18 Operation principle and hardware description
2 3 4
1 6
5
15
16
8 10
19
12
9 17
11
13
14 18
Operation principle and hardware description 19
Q130
19 X60, X61 Terminal blocks, emergency stop circuits (option, on side plate)
20 Operation principle and hardware description
No. Description
1. Main switch-disconnector handle
2. earthing/grounding switch handle
(Q9, option +F259)
3. Auxiliary voltage switch handle
4
4. Selector switch for V meter (option
12
+G334)
5. Grounding busbar (PE)
3
11 6. Input power cable terminals
(1L1…2L3)
7. Main switch-disconnector (Q1)
10
8. Grounding/earthing switch (Q9,
option +F259)
9. Main AC fuses (F1…3)
9
10. Main contactor (Q2, option +F250)
11. Auxiliary voltage switch (Q21)
2 12. Cubicle cooling fan
8
5
Operation principle and hardware description 21
No. Description
1. Main switch-disconnector
handle
3 2. Auxiliary voltage switch
handle
3. Selector switch for V meter
10 10 (option +G334)
4. Grounding (PE) busbar
2
5. Input power cable termi-
9 nals (1L1…2L3)
6. Main switch-disconnectors
8 8 (Q1.1, Q1.2)
7. Main AC fuses
(F1.1…F2.3)
7 7 8. Main contactors (Q2.1,
Q2.2, option +F250)
9. Auxiliary voltage switch
(Q21)
10. Cubicle cooling fans
6
1
4
22 Operation principle and hardware description
No. Description
1. Supply module (See Layout drawing of D7T
supply module on page 26).
2. AC busbars (on back)
2 2 3. DC busbars
3 3
1 1
Operation principle and hardware description 23
No. Description
1. Supply module (See Layout drawing of D8T
supply module on page 27).
2. AC busbars
2
3. DC busbars
1
24 Operation principle and hardware description
No. Description
1. Supply module (See Layout drawing of D8T
supply module on page 27).
2. AC busbars with module-specific AC fuses (no
fuses in 12-pulse 2×D8T supply unit)
2
3. DC busbars
3 3
1 1
Operation principle and hardware description 25
No. Description
1. Supply module (See Layout drawing of D8T
supply module on page 27).
3 3 3
1 1 1
26 Operation principle and hardware description
Front Back
1
5 2
9
7
3
11
10
No. Description
1. AC input busbars
2. DC output busbars
5. Lifting eyes
6. Fan
7. Unpainted fastening hole. Grounding point (PE) between module frame and cabinet frame.
9. Terminal block X50. Auxiliary AC power supply for module. When constant-speed fan is in use: Also
AC power supply for cooling fan.
11. Fibre optic connectors. Communication link to the control unit of the supply unit. When speed-
controlled fan is in use: Communication link to fan control unit.
Operation principle and hardware description 27
Front Back
2
7
9
5
1
3
8
6 11
10
12
No. Description
2. DC output busbars
5. Lifting eyes
6. Fan
7. Unpainted fastening hole. Grounding point (PE) between module frame and cabinet frame.
9. Terminal block X50. Auxiliary AC power supply for module. When constant-speed fan is in use: Also
AC power supply for cooling fan.
11. Fibre optic connectors. Communication link to the control unit of the supply unit. When speed-
controlled fan is in use: Communication link to fan control unit.
12. Wheels
28 Operation principle and hardware description
CLOSE
7
9 FXX
1
FXX
2
3
FXXX
6
5 10
Operation principle and hardware description 29
6. Terminal blocks. See chapter Control unit on 10. Safety option interface (FSO-xx)
page 101.
30 Operation principle and hardware description
4 10 11 12
3 6
9
8
5 12
10. P5.x Voltage meters (optional). One meter in 6-pulse supply unit and two in 12-pulse. Size of the
meters vary. See section Other door controls on page 32.
11. S5.x Selector switches for voltage meters (optional). There is one switch in 6-pulse supply unit
and two in 12-pulse. See section Other door controls on page 32.
12 P2.x AC phase current meters (optional). Number of meters depends on option selection. There
are max. 6 meters in 12-pulse unit. See section Other door controls on page 32.
WARNING! The switch does not isolate the input power terminals, AC voltage
meters ((P5), option +G334) or the auxiliary circuit from the power line. To isolate
auxiliary voltage, use the auxiliary voltage switch (Q21). To isolate the input power
terminals and AC voltage meters, open the main breaker of the supply transformer.
Note: The earthing/grounding switch ((Q9), option +F259) and the main switch-
disconnector are electrically interlocked: The earthing/grounding switch can be closed only
when the main switch-disconnector is open. The main switch-disconnector can be closed
only when the earthing/grounding switch is open. That is, only one of the switches can be
closed at a time. To close the switches, you must also have the auxiliary control voltage
on.
WARNING! The earthing/grounding switch (Q9) does not ground the input power
terminals or auxiliary circuits.
Note: The earthing/grounding switch and the main switch-disconnector ((Q1), option
+F253) are electrically interlocked: The earthing/grounding switch can be closed only
when the main switch-disconnector is open. The main switch-disconnector can be closed
only when the earthing/grounding switch is open. That is, only one of the switches can be
closed at a time. To close the switches, you must also have the auxiliary control voltage
on.
PC connection
There is a USB connector on the front of the panel that can be used to connect a PC to the
drive. When a PC is connected to the control panel, the control panel keypad is disabled.
See also section Connecting a PC to the supply unit on page 49.
Fieldbus control
You can control the supply unit through a fieldbus interface if the unit is equipped with an
optional fieldbus adapter (for example, option +K454), and when you have configured the
control program for the fieldbus control with the parameters. For information on the
parameters, see ACS880 diode supply control program firmware manual
[3AUA0000103295 (English)].
Note: To be able to switch the main contactor (Q2) (or breaker) and the supply unit on and
off (Run enable signal) through the fieldbus, the Run enable command at digital input DI2
must be on (1). That is the case when the operating switch (S21) is switched to the on (1)
position.
34 Operation principle and hardware description
3 4 5
2 6
3 4 5
2 6
No. Description
1. Supply module frame size
2. Degree of protection
3. Type designation, see section Type designation keys on page 35.
4. Ratings. See also section Ratings on page 83.
5. Valid markings
6. Serial number. The first digit of the serial number refers to the manufacturing plant. The next four
digits refer to the unit’s manufacturing year and week, respectively. The remaining digits complete the
serial number so that there are no two units with the same number.
Operation principle and hardware description 35
This is a list of options codes. It includes also the standard features. The standard features
are marked with *.
Code Description
Standard Supply Frequency Supply Frequency 50 Hz *
+A013 Supply Frequency Supply Frequency 60 Hz
+A018 Diode-thyristor bridge *
Standard Control Voltage for Relays and Fans 230 VAC *
+G304 Control Voltage for Relays and Fans 115 VAC
+G307 Terminals for External Control Voltage Terminals for External Control Voltage (for UPS)
+G344 Auxiliary Transformer Auxiliary transformer (standard)
Standard Cabinet Construction Industrial Version IEC *
+C121 Cabinet Construction Marine Construction
+C180 Cabinet Construction Seismic design
Standard Standards EN/IEC *
+C134 Standards CSA-approved
+C129 Standards UL-approved
Standard Degree of Protection IP22, UL type 1 *
+B054 Degree of Protection IP42, UL type 1
+B055 Degree of Protection IP54, UL type 12
+C130 Channeled Air Channeled Air Outlet
+C128 Channeled Air Cooling air through bottom
Standard Control Cabling Control cable Bottom *
+H368 Control Cabling Control cable Top
Standard Power Cabling Entry Bottom Entry *
+H351 Power Cabling Entry Top Entry
Standard Motor Cabling Cable lead through (European) *
+H365 Motor Cabling Cable gland plates (Brass 6mm, undrilled)
36 Operation principle and hardware description
Code Description
+H364 Motor Cabling Cable gland plates (Aluminium 3mm, undrilled)
+H358 Motor Cabling Cable gland plates (Steel 3mm, undrilled)
+G314 DC Bus Material Aluminium (standard up to 3200A) *
+G315 DC Bus Material Tin plated copper (option up to 3200ADC, standard *
above)
Standard Supply Conductor Type Cable Supply Conductors *
+G317 Supply Conductor Type Busbar Supply Conductors
standard Wiring materials standard wire material *
+G330 Wiring materials Halogen free wiring
+E202 EMC 1st environment, restricted (max 1000A)
+E210 EMC 2nd Environment
+G301 Cabinet Options Cabinet Lighting
+G300 Cabinet Options Cabinet Heater
+C164 Cabinet options Plinth height 1 (100 mm)
+C176 Cabinet options Door hinges on left side
+C179 Cabinet options Plinth height 2 (200 mm)
+P913 Cabinet options Special color
+Z0010 ACU ACU width 400
+Z0015 ACU ACU width 600
+Z2005 Drive composer pro Drive composer pro (replaces DriveWindow and
DriveDebug)
+K480 Ethernet switch Ethernet switch for PC tool and control network
+K483 Ethernet switch Ethernet switch with optical link for PC tool or control
network
+Z2010 DDCS NDBU-95 (for max. 7 units) including fibre optic link.
Star network
+Z2011 DDCS Fibre optic link (without NDBU-95) Ring network
+F250 Line Options Line Contactor, standard in small power, (always with *
disconnector F253)
+Standard Line Options Disconnector switch (door interlocked), standard in *
small power, (always with line contactor F250)
+F255 Breaker Option Circuit Breaker, standard in high power *
+F285 Earthing Switch Earthing terminals
+F259 Ear hi ng Switch Earthing Switch
+G331 Emergency Stop Emergency Stop Push button on the door (red)
+Q951 Emergency Stop Emergency stop, cat 0 with opening main contactor
with safety relay
+Q952 Emergency Stop Emergency stop, cat 1 with opening main contactor
with safety relay
+Q963 Emergency stop Emergency stop, stop cat 0, with STO with safety
relay
+Q964 Emergency stop Emergency stop, cat 1 with STO with safety relay
+Q979 Emergency stop Emergency Stop, configurable stop cat 0 or 1 with
FSO with STO
+Z150 Emergency Stop Acknowledgment Via control board
+Z160 Emergency Stop Acknowledgment Via AC800M
+Z2025 Emergency Stop Location Standard
+Z2026 Emergency Stop Location Master
Operation principle and hardware description 37
Code Description
+Z2027 Emergency Stop Location Follower
+J410 Panels Drive control panel connection kit
+J412 Panels Common control panel for a line up
+K450 Panels Panel Bus, built with ethernet cable, needs FDPI
option board in each unit, max. 32
+J400 CDP-panel Control Panel AP-I (max. 4 panels on the door)
+J401 LMD-panel Drive Monitoring Display
+G332 Electrical Disconnect Button Electrical disconnect push button on the door (black,
opens main contactor / ACB)
+Q959 Electrical Disconnect Button Supply transformer breaker disconnect push button
(red, wired to terminals) on the door
+Q953 Earth Fault Monitoring Earth Fault Monitoring, Earthed Mains TN
+Q954 Earth Fault Monitoring Earth Fault Monitoring, Unearthed Mains IT
+G336 Arc Monitoring, 1 loop Arc monitoring unit, 1 loop, Rea 101, including cable
+G337 Arc Monitoring Arc monitoring unit, extension for 2 loops, Rea 103,
including cable
+G334 Meters V-meter with selector switch
+G335 Meters A-meter in one phase
+3G335 Meters A-meter in three phases
+G333 Meters kWh-meter
+J411 ON/OFF Control Type Remote Supply Control (from upper controller)
+G343 Special Options Corrosion Classification Coupon in ACU (Purafil
3AUA64044052)
+P913 Special Options Special color
+L501 I/O-Options 1 FIO-01, Digital I/O extension
+L500 I/O-Options 2 FIO-11, Analogue I/O extension
+L515 I/O-Options 4 FEA-03 option module extension adaptor
+L503 I/O-Options 4 FDCO-01, DDCS communication for ZCU-xx
(2xTransmitter/Receiver)
+L509 DDCS RDCO-04 DDCS communication for BCU-xx
(4xTransmitter/Receiver)
+L504 I/O-Options 5 Additional control unit Terminal Block
+K451 FieldBus1 FDNA-01 (DeviceNet)
+K452 FieldBus1 FLON-01 (LonWorks)
+K454 FieldBus1 FPBA-01 (Profibus)
+K458 FieldBus1 FSCA-01 (Modbus RTU)
+K462 FieldBus1 FCNA-01 (Control Net)
+K473 FieldBus1 FENA-01 (Ethernet (EtherNet/IP, Modbus/TCP,
PROFINET)
+K475 FieldBus1 FENA-21 (High performance Ethernet (EtherNet/IP,
Modbus/TCP, PROFINET) Daisy chain
+K457 FieldBus1 FCAN-01 (CANOpen)
+K470 FieldBus1 FEPL-01 (Ether POWERLINK)
+K469 FieldBus1 FECA-01 (EtherCAT)
Standard Speed Controlled fan speed controlled fan *
+C188 DOL cooling fan DOL cooling fan
Standard Documentation Complete documentation, user manuals in memory *
stick
38 Operation principle and hardware description
Code Description
+R716 Documentation Paper copy A4, Complete documentation and user
manuals / Drive Unit
+R717 Documentation Paper copy, circuit diagrams and dimension drawings
A3, other A4, complete documentation 2 and user
manuals / Drive Unit
Standard Language English *
+R701 Language German manuals
+R702 Language Italian manuals
+R705 Language Swedish manuals
+R706 Language Finnish manuals
+R707 Language French manuals
+R708 Language Spanish manuals
+R711 Language Russian manuals
This is a list of options codes. It includes also the standard features. The standard features
are marked with *.
Option codes (plus codes)
+A018 Diode-thyristor bridge *
Electrical installation 39
3
Electrical installation
WARNING! Only qualified electricians are allowed to carry out the work described
in this chapter. Read the safety instructions given in Safety instructions for
ACS880 multidrive cabinets and modules [3AUA0000102301(English)] before
you install, commission, use or service the drive.
40 Electrical installation
WARNING! Do the electrical safety precautions before starting any work on the
installation. If you ignore the precautions, physical injury or death, or damage to
the equipment can occur. Only a qualified electrician is allowed to work on the
installation.
Supply cable
Check the insulation of the supply (input) cable according to local regulations before you
connect it to the drive.
Electrical installation 41
ACS880-307
1)
L1
L2
L3
PE
2)
1)
Fuses or other protection means.
2) Ground
the cable shield 360 degrees at the cable lead-through. See section Connection procedure on
page 43.
Notes:
See section Terminal and lead-through data for the input power cable, page 92 for the dimensions and
tightening torque guidelines.
Use a separate PE conductor in addition if the conductivity of the shields does not meet the requirement for the
PE conductor. See Electrical planning instructions for ACS880 multidrive cabinets and modules
[3AUA0000102324 (English)].
For the cable selection instructions, see Electrical planning instructions for ACS880 multidrive cabinets and
modules [3AUA0000102324 (English)].
42 Electrical installation
1) ACS880-307 +A004
1L1
1L2
1L3
PE
2L1
2L2
2L3
PE
2)
1) Fuses
or other protection means.
2) Ground
the cable shield 360 degrees at the cable lead-through. See section Connection procedure on
page 43.
Notes:
See section Terminal and lead-through data for the input power cable, page 92 for the dimensions and
tightening torque guidelines.
Use a separate PE conductor in addition if the conductivity of the shields does not meet the requirement for the
PE conductor. See Electrical planning instructions for ACS880 multidrive cabinets and modules
[3AUA0000102324 (English)].
For the cable selection instructions, see Electrical planning instructions for ACS880 multidrive cabinets and
modules [3AUA0000102324 (English)].
Electrical installation 43
Connection procedure
The cable lead-through details, and cable connection details are shown in chapter
Terminal and lead-through data for the input power cable, page 92.
WARNING! Only qualified electricians are allowed to do this work. Read the
complete safety instructions of the drive. Ignoring the instructions can cause
physical injury or death, or damage to the equipment.
1. Disconnect the drive from the AC power line and make sure it is safe to start the work.
See section Basic electrical safety precautions on page 40.
2. Open the door of the incoming cubicle.
3. Remove the shrouding covering the input terminals.
4. Peel off 3 to 5 cm of the outer insulation of the cables above the lead-through plate for
360° high-frequency grounding.
5. Prepare the ends of the cables.
6. If fire insulation is used, make an opening in the mineral wool sheet according to the
diameter of the cable.
7. For IP22, IP42 drives: Slide the cables through the lead-throughs with the conductive
sleeves.
8. For IP54 drives: Remove the rubber grommets from the lead-through plate for the
cables to be connected. Cut adequate holes into the rubber grommets. Slide the
grommets onto the cables. Slide the cables through the lead-throughs with the
conductive sleeves and attach the grommets to the holes.
9. Fasten the conductive sleeves to the cable shields with cable ties.
10. Seal the slot between the cable and mineral wool sheet (if used) with sealing
compound (eg, CSD-F, ABB brand name DXXT-11, code 35080082).
11. Tie up the unused conductive sleeves with cable ties.
12. Connect the twisted shields of the cables to the PE busbar of the cabinet. Tighten the
screws to the torque given under Tightening torques (page 100).
13. Connect the phase conductors of the input cable to the L1, L2 and L3 terminals.
Tighten the screws to the torque given under Tightening torques (page 100).
14. Reinstall the shrouding removed earlier.
15. Close the door.
44 Electrical installation
5
PE PE
PE
11
8
Electrical installation 45
WARNING! Only qualified electricians are allowed to do this work. Read the
complete safety instructions of the drive. Ignoring the instructions can cause
physical injury or death, or damage to the equipment.
For the connection diagram, see the delivery-specific circuit diagrams. For the auxiliary
circuit current consumption, see the delivery-specific technical documentation.
WARNING! Only qualified electricians are allowed to do this work. Read the
complete safety instructions of the drive. Ignoring the instructions can cause
physical injury or death, or damage to the equipment.
1. Disconnect the drive from the AC power line and make sure it is safe to start the work.
See section Basic electrical safety precautions on page 40.
2. Run the control cables into the auxiliary control cubicle as described in section
Grounding the outer shields of the control cables at the cabinet lead-through below.
3. Route the control cables as described in section Routing the control cables inside the
cabinet (page 48).
4. Connect the control cables. See the circuit diagrams delivered with the drive.
Grounding the outer shields of the control cables at the cabinet lead-through
Ground the outer shields of all control cables 360 degrees at the EMI conductive cushions
as follows:
1. Loosen the tightening screws of the EMI conductive cushions and pull the cushions
apart.
2. Cut adequate holes to the rubber grommets in the lead-through plate and lead the
cables through the grommets and the cushions into the cabinet.
3. Strip off the cable plastic sheath above the lead-through plate just enough to ensure
proper connection of the bare shield and the EMI conductive cushions.
4. Tighten the two tightening screws (a) so that the EMI conductive cushions (b) press
tightly round the bare shield.
5. Secure the cables mechanically at the lead-through strain relief.
6. Keep the shields continuous as close to the connection terminals as possible.
Electrical installation 47
1 1
View from above
2
1 Tightening screw
2 EMI conductive cushion
3 Strain relief
4 Grommet
5
5 Lead-through plate
4
A B C
A Stripped cable
B Conductive surface of the shield exposed
C Stripped part covered with copper foil
1 Cable shield
2 2
1 2 Copper foil
3
3 Shielded twisted pair
4
4 Grounding wire
48 Electrical installation
Note for top entry of cables: When each cable has its own rubber grommet, sufficient IP
and EMC protection can be achieved. However, if very many control cables come to one
cabinet, plan the installation beforehand as follows:
1. Make a list of the cables coming to the cabinet.
2. Sort the cables going to the left into one group and the cables going to the right into
another group to avoid unnecessary crossing of cables inside the cabinet.
3. Sort the cables in each group according to size.
4. Group the cables for each grommet as follows ensuring that each cable has a proper
contact to the cushions on both sides.
Cable diameter in mm Max. number of cables per grommet
< 13 4
< 17 3
< 25 2
> 25 1
5. Arrange the bunches according to size from thickest to the thinnest between the EMI
conductive cushions.
6. If more than one cable go through a grommet, seal the grommet by applying Loctite
5221 (catalogue number 25551) inside the grommet.
2b
?
USB connected
Stop Loc/Rem Start 1
?
2a
3
50 Electrical installation
Installation checklist 51
4
Installation checklist
Checklist
Check the mechanical and electrical installation of the drive before start-up. Go through
the checklist together with another person.
Disconnect the drive from the AC power line and make sure it is safe to start the work. See
section Basic electrical safety precautions on page 40.
WARNING! Only qualified electricians are allowed to carry out the work described
below. Read the complete safety instructions in Safety instructions for ACS880
multidrive cabinets and modules [3AUA0000102301(English)] before you install,
commission, use or service the drive. Ignoring the instructions can cause physical
injury or death, or damage to the equipment.
52 Installation checklist
Check that…
The ambient operating conditions meet the specifications given in chapter Technical data.
The cabinet is properly fastened to the floor. See section Free space requirements on page 90.
There is sufficient free space around the unit. See Mechanical installation instructions for ACS880
multidrive cabinets [3AUA0000101764 (English)].
If the drive has been stored over one year: The electrolytic DC capacitors in the DC link of the drive
have been reformed. See the separate reforming instructions (available in the Internet or from your
local ABB representative).
There is an adequately sized protective earth (ground) conductor between the drive and the factory
main PE, and the conductor has been connected to the appropriate terminal. Proper grounding has
also been measured according to the regulations.
The supply voltage matches the nominal input voltage of the unit. Check the type designation label.
The input power cable has been connected to the appropriate terminals, the phase order is right, and
the terminals have been tightened. (Pull the conductors to check.)
The control cables (if any) have been connected to the appropriate terminals, and the terminals have
been tightened. (Pull the conductors to check.)
There are no tools, foreign objects or dust from drilling inside the cabinet.
All shrouds and covers are in place. Cabinet doors have been closed.
Start-up 53
5
Start-up
WARNING! Only qualified electricians are allowed to carry out the work described
in this chapter. Read the complete safety instructions in Safety instructions for
ACS880 multidrive cabinets and modules [3AUA0000102301 (English)]. Ignoring
the instructions can cause physical injury or death, or damage to the equipment.
54 Start-up
Start-up procedure
Action
Drive with the earthing/grounding switch ((Q9), option +F259): Make sure that the earthing/grounding
switch is closed.
Note: You cannot close the earthing/grounding switch before the auxiliary circuits are energized and
the main switch disconnector (Q1) is open.
Make sure that the installation has been checked. See chapter Installation checklist on page 51.
Check the settings of breakers/switches in the auxiliary circuits. See delivery-specific circuit diagrams.
If time relays, or relays with delayed make contact or break contact are used, for example, in
emergency stop circuits, check the relay time settings. See delivery-specific circuit diagrams and
safety function specific documentation (if applicable).
Make sure that the voltage settings of the auxiliary voltage transformers are according to the actual
line voltage and desired output voltage. See the delivery-specific circuit diagrams.
Transformer T21 is selected by option +G344; T101 and T111 are present if required by the options
specified by the customer.
Disconnect the unfinished or unchecked 230 VAC cables that lead from the terminal blocks to the
outside of the equipment.
Check that both circuits of STO terminals on the control boards are closed as shown in Default I/O
connections on page 104 (IN1 and IN2 must be connected to OUT). Otherwise the supply unit cannot
start.
Drives with voltage meters ((P5), option +G334): Close the circuit breaker for the voltage meters (F5).
Close the circuit breakers supplying the auxiliary circuits (F22, etc.).
Drive with an external control voltage supply (option +G307): Close the circuit breaker of the external
control voltage supply.
Drive with the earthing/grounding switch ((Q9), option +F259): Open the earthing/grounding switch.
Make sure that the supply unit is in the remote control mode to enable control of the supply unit with
the operating switch (S21). Use Loc/Rem key of the control panel to change the mode.
Start-up 55
Action
Turn the operating switch (S21) to on (1) position to activate the Run enable signal and to switch the
main contactor (Q2) on.
On-load checks
Check that the supply module cooling fan rotates freely in the right direction.
WARNING! Despite of the temporary grounding of the AC busbars after the main
switch-disconnector (Q1), the input power cable terminals are under voltage.
Disconnect and ground them separately when necessary. Do not remove the
shroud in front of the busbars.
6
Maintenance
Maintenance intervals
The recommended maintenance intervals and component replacements are based on
specified operational and environmental conditions. Maintain the drive according to the
recommended maintenance intervals.
Consult your local ABB Service representative for more details on the maintenance. On
the Internet, go to: http://www.abb.com/drivesservices.
Component Years from start-up
1 2 3 4 5 6 7 8 9 10 11 12 …
Cooling
Aging
Connections and
environment
IP22 and IP42 air inlet (door) (I) (I) (I) (I) (I) (I) (I) (I) (I) (I) (I) (I) (I)
meshes
Tightness of terminals (I) (I) (I) (I) (I) (I) (I) (I) (I) (I) (I) (I) (I)
Dustiness, corrosion and (I) (I) (I) (I) (I) (I) (I) (I) (I) (I) (I) (I) (I)
temperature
Supply module heat sink (I) (I) (I) (I) (I) (I) (I) (I) (I) (I) (I) (I) (I)
cleaning
I Visual inspection
(I) Visual inspection if needed in demanding operation conditions: ambient temperature is constantly over
40 ˚C, especially dusty or humid environment, cyclic heavy load, or continuously high load.
R Replacement of component in normal operation conditions: ambient temperature is below 40 °C
(104 °F), clean and non-humid environment, no cyclic heavy load or no continuously high load.
(R) Replacement of component in demanding operation conditions: ambient temperature is constantly over
40 ˚C, especially dusty or humid environment, cyclic heavy load, or continuously high load.
Maintenance 59
Cabinet
Cleaning the interior of the cabinet
WARNING! Only qualified electricians are allowed to do this work. Read the
complete safety instructions of the drive. Ignoring the instructions can cause
physical injury or death, or damage to the equipment.
WARNING! Use a vacuum cleaner with an antistatic hose and nozzle, and wear a
grounding wristband. Otherwise an electrostatic charge might build up and
damage the circuit boards.
1. Disconnect the drive from the AC power line and make sure it is safe to start the work.
See section Basic electrical safety precautions on page 40.
2. Clean the interior of the cabinet. Use a vacuum cleaner and a soft brush.
3. Clean the air inlets and outlets of the fans.
4. Clean the air inlet grating of the door.
5. Close the door.
Cleaning the air inlet meshes – IP22 and IP42 (option +B054)
WARNING! Use a vacuum cleaner with an antistatic hose and nozzle. Using a
normal vacuum cleaner creates static discharges which can damage circuit
boards.
Check the dustiness of the air inlet meshes. If the dust cannot be removed by vacuum
cleaning from outside through the grating holes with a small nozzle, proceed as follows:
1. Recommendation: De-energize the fans by switching off the supply unit.
2. Remove the fasteners at the top of the grating.
3. Lift the grating and pull it away from the door.
4. Remove the mesh by turning the clips gently a little.
5. Vacuum clean the mesh.
6. Reinstall the mesh and grating in reverse order.
2 3 4 6
60 Maintenance
2 3 4
5 6
Maintenance 61
WARNING! De-energize the fans by switching off the supply unit. Make sure that
no restart is possible during the maintenance work. Rotating fan blades can
cause serious hand injury.
1. Remove the front and back gratings of the fan cubicle by lifting them upwards
2. Remove the air filter mat.
3. Place the new filter mat in the grating.
4. Reinstall the grating in reverse order.
Power connections
Tightening the power connections
WARNING! Only qualified electricians are allowed to do this work. Read the
complete safety instructions of the drive. Ignoring the instructions can cause
physical injury or death, or damage to the equipment.
1. Disconnect the drive from the AC power line and make sure it is safe to start the work.
See section Basic electrical safety precautions on page 40.
2. Check the tightness of the cable connections. Use the tightening torques given in
chapter Tightening torques on page 100.
62 Maintenance
Fuses
Checking and replacing the D7T module DC fuses
WARNING! Only qualified electricians are allowed to do this work. Read the
complete safety instructions of the drive. Ignoring the instructions can cause
physical injury or death, or damage to the equipment.
1. Disconnect the drive from the AC power line and make sure it is safe to start the work.
See section Basic electrical safety precautions on page 40.
2. Undo the screws of the cover panel of the module’s DC fuses (a) and lift and remove
the panel.
3. Check the condition of the fuses and replace if necessary.
4. Attach the cover.
2a
Maintenance 63
WARNING! Only qualified electricians are allowed to do this work. Read the
complete safety instructions of the drive. Ignoring the instructions can cause
physical injury or death, or damage to the equipment.
1. Disconnect the drive from the AC power line and make sure it is safe to start the work.
See section Basic electrical safety precautions on page 40.
2. Undo the screws of the cover panel of the module’s DC fuses (a) and lift and remove
the panel.
3. Check the condition of the fuses and replace if necessary.
4. Attach the cover
2a
64 Maintenance
WARNING! Only qualified electricians are allowed to do this work. Read the
complete safety instructions of the drive. Ignoring the instructions can cause
physical injury or death, or damage to the equipment.
1. Disconnect the drive from the AC power line and make sure it is safe to start the work.
See section Basic electrical safety precautions on page 40.
2. Open the door of the supply module (or incoming) cubicle. (Depending on the delivery,
there might be AC fuses in either or both cubicles).
3. Remove the shrouding (a) from in front of the fuses.
4. Slacken the nuts of the headless screws of the fuses so that you can slide out the fuse
blocks. Make note of the order of the washers on the screws.
5. Remove the screws, nuts and washers from the old fuses and attach them to the new
fuses. Make sure to keep the washers in the original order.
6. Insert the new fuses into their slots in the cubicle.Tighten the nuts to torque as follows:
• Cooper-Bussmann fuses: 50 N•m (37 lbf·ft)
• Mersen (Ferraz-Shawmut): 46 N•m (34 lbf·ft)
• Other: Refer to the fuse manufacturer’s instructions.
7. Reinstall the shrouding removed earlier and close the cubicle door.
3a
Maintenance 65
Fans
The lifespan of the cooling fan depends on the running time of the fan, ambient
temperature and dust concentration.
WARNING! Only qualified electricians are allowed to do this work. Read the
complete safety instructions of the drive. Ignoring the instructions can cause
physical injury or death, or damage to the equipment.
1. Disconnect the drive from the AC power line and make sure it is safe to start the work.
See section Basic electrical safety precautions on page 40.
2. Remove the shrouding from in front of the fan.
3. Unplug the power supply cable of the fan.
4. Remove the fastening screws of the fan.
5. Install the new fan in reverse order.
66 Maintenance
WARNING! Only qualified electricians are allowed to do this work. Read the
complete safety instructions of the drive. Ignoring the instructions can cause
physical injury or death, or damage to the equipment.
1. Disconnect the drive from the AC power line and make sure it is safe to start the work.
See section Basic electrical safety precautions on page 40.
2. Remove the shrouding in front of the fan (if any).
3. Disconnect the fan wiring (a).
4. Remove the fastening screws (a) and the finger guard (b) of the fan.
5. Install the new fan in reverse order.
3 4
4b
4a
3a
Maintenance 67
WARNING! Only qualified electricians are allowed to do this work. Read the
complete safety instructions of the drive. Ignoring the instructions can cause
physical injury or death, or damage to the equipment.
1. Disconnect the drive from the AC power line and make sure it is safe to start the work.
See section Basic electrical safety precautions on page 40.
2. Open the cubicle door.
3. Remove the lower support bracket of the module (a).
4. Disconnect the fan wiring from the module: power supply plug (a) and the fibre optic
cables (b).
5. Remove the front cover of the fan holder (a).
6. Support the fan holder (a) from below and pull it to release it from the module.
7. Pull out the fan holder.
8. If you have spare fan without the holder: Remove the fan from the fan holder.
9. Install new fan and the fan holder in reverse order to the above.
3 4 5 6
4a
4b
5a
3a
6a
68 Maintenance
WARNING! Only qualified electricians are allowed to do this work. Read the
complete safety instructions of the drive. Ignoring the instructions can cause
physical injury or death, or damage to the equipment.
1. Disconnect the drive from the AC power line and make sure it is safe to start the work.
See section Basic electrical safety precautions on page 40.
2. Remove the screws holding the front cover plate. Lift the cover plate somewhat to
release it.
3. Disconnect the fan wiring from the module: power supply plug (a) and the fibre optic
cables (b).
4. Remove the front cover (a) of the fan holder.
5. Pull out the fan holder a).
6. If you have spare fan without the holder: Remove the fan from the fan holder.
7. Install new fan and the fan holder in reverse order to the above
3 4 5
3b
3a
5a 4a
Maintenance 69
WARNING! Only qualified electricians are allowed to do this work. Read the
complete safety instructions of the drive. Ignoring the instructions can cause
physical injury or death, or damage to the equipment.
1. Disconnect the drive from the AC power line and make sure it is safe to start the work.
See section Basic electrical safety precautions on page 40.
2. Open the door of the cubicle.
3. Remove the shroud in front of the fan.
4. Remove all ventilation covers (lift and pull) and filters, and finally remove the roof plate
on top of the outlet. Unscrew all necessary screws securing the fan and remove the
fan.
5. Pull the fan unit out.
6. Install a new fan in reverse order.
Supply module
Cleaning the heatsink
The module heatsink fins pick up dust from the cooling air. Clean the heatsink when
necessary. Overtemperature warnings and faults indicate that the heatsink is not clean.
WARNING! Only qualified electricians are allowed to do this work. Read the
complete safety instructions of the drive. Ignoring the instructions can cause
physical injury or death, or damage to the equipment.
1. Disconnect the drive from the AC power line and make sure it is safe to start the work.
See section Basic electrical safety precautions on page 40.
2. Remove the cooling fan of the supply module as described in section Fans elsewhere
in this chapter.
3. Prevent the dust from entering adjoining equipment. If necessary, remove the module
from the cabinet before proceeding.
4. Blow clean and dry compressed air through the module from bottom to top,
simultaneously using a vacuum cleaner at the air outlet to trap the dust.
5. Refit the cooling fan.
WARNING! Only qualified electricians are allowed to do this work. Read the
complete safety instructions of the drive. Ignoring the instructions can cause
physical injury or death, or damage to the equipment.
1. Disconnect the drive from the AC power line and make sure it is safe to start the work.
See section Basic electrical safety precautions on page 40.
2. Open the cubicle door.
3. Remove the shroud.
4. Unplug the plug connector on top of the module (a), and the plug connector and fibre
optic connector in front of the module (b).
5. Remove the lower support bracket of the module.
6. Be careful not to drop anything inside the module while you work on top of the module.
Remove the fastening bolts of the DC busbars (a) and the DC busbars. Remove the
fastening bolts of the AC busbars (b).
7. Remove the cooling fan plug connector (a), fibre optic connectors (b) and the cooling
fan (c). See section Replacing the fan of the D7T supply module on page 67.
8. Remove the side fastening screws of the module on the top (a) and bottom (b).
9. Attach a lifting device to the lifting eyes of the module (a).
10. Remove the upper support bracket of the module (a).
11. Pull the module out of the cabinet carefully. Keep the weight on the lifting device
constantly.
12. Lift the module down onto a pallet.
13. Keep the lifting device attached to the module and attach the module safely to the
pallet.
14. Remove the lifting from the module and move the module away.
15. Install a new module in reverse order. Tighten the fastening screws of the module to
22 N·m (16.2 lbf·ft) and the fastening bolts of the DC output busbars to 70 N·m
(51.6 lbf·ft).
16. Close the cubicle door.
72 Maintenance
3 4 5
4a
4b
6 7
6a
6b
6a
7b
7a
7c
Maintenance 73
8a
8b
9 10 11
9a
9a
10a
74 Maintenance
WARNING! Only qualified electricians are allowed to do this work. Read the
complete safety instructions of the drive. Ignoring the instructions can cause
physical injury or death, or damage to the equipment.
WARNING! Be very careful when you move a module that runs on wheels. The
module is heavy (approximately 175 kg) and have a high center of gravity. It
topples over easily. Ignoring the following instructions can cause physical injury or
death, or damage to the equipment.
• Wear appropriate safety equipment.
• Be careful when removing bolts and washers on top of the module. Do not drop
anything inside the module.
• Do not move the module carelessly.
• When you remove the module, use the module pull-out ramp. Pull the module
carefully out of the cubicle along the ramp. While pulling on the handle, keep a
constant pressure with one foot on the base of the module to prevent the module from
falling on its back. We recommend that you attach a lifting device to the module before
you remove the module and keep it attached while removing.
• When you install a module, use the module pull-out ramp. Keep your fingers away
from the edge of the module front plate to avoid pinching them between the module
and the cubicle. Also, keep a constant pressure with one foot on the base of the
module to prevent the module from falling on its back. We recommend that you attach
a lifting device to the module before you install the module and keep it attached while
installing.
• Do not tilt the module. Do not leave the module unattended on a sloping floor.
• If you lift the module, use only the two lifting eyes on top of the module: one in front
and the other in back. Never lift the module from the hole inside the module (visible
from top). It cannot carry the weight of the whole module.
• Do not use the module pull-out ramp with plinth heights over 50 mm. The ramp is
designed for a plinth height of 50 mm (the standard plinth height of ABB cabinets).
Support the top and Do not tilt! Do not leave the module
bottom of the module! unattended on a sloping floor!
max.
max 50
50 mm mm
Maintenance 75
Do not use this hole for lifting! Mind your fingers! Support the top and bottom
of the module!
NO LIFTING!
5a
5b
Maintenance 77
6 7 8
6a
7a 6a
8a
78 Maintenance
9
Maintenance 79
Control panel
Replacing the control panel battery
1. Turn the lid on the back of the panel counter-clockwise until the lid opens.
2. Replace the battery with a new CR2032 battery.
3. Put the lid back and tighten it by turning it clockwise.
4. Dispose of the old battery according to local disposal rules or applicable laws.
80 Maintenance
Memory unit
After replacing a supply module control unit, the existing parameter settings can be
retained by transferring the memory unit from the defective unit to the new unit.
WARNING! Only qualified electricians are allowed to do this work. Read the
complete safety instructions of the drive. Ignoring the instructions can cause
physical injury or death, or damage to the equipment.
WARNING! Do not remove or insert the memory unit when the control unit is
powered.
1. Disconnect the drive from the AC power line and make sure it is safe to start the work.
See section Basic electrical safety precautions on page 40.
2. Make sure that the control unit is not powered.
3. Undo the fastening screw and pull the memory unit out.
4. Install a memory unit in reverse order.
7
Technical data
Ratings
Supply unit type Nominal No overload Light overload Heavy-duty use
use use
Icontmax IN SN PN ILd PLd Ihd PHd
A DC A AC kVA kW A DC kW DC A DC kW DC
UN = 400 V
6-pulse
ACS880-307-0650A-3+A018 800 653 453 432 768 415 598 323
ACS880-307-0980A-3+A018 1200 980 679 648 1152 622 898 485
ACS880-307-1210A-3+A018 1488 1215 842 804 1428 771 1113 601
ACS880-307-1820A-3+A018 2232 1822 1263 1205 2143 1157 1670 902
ACS880-307-2730A-3+A018 3348 2734 1894 1808 3214 1736 2504 1352
ACS880-307-3640A-3+A018 4464 3645 2525 2411 4285 2314 3339 1803
ACS880-307-4560A-3+A018 5580 4556 3157 3013 5357 2893 4174 2254
ACS880-307-5470A-3+A018 6696 5467 3788 3616 6428 3471 5009 2705
12-pulse
ACS880-307-0910A-3+A004+A018 1116 911 631 603 1071 579 835 451
ACS880-307-1210A-3+A004+A018 1488 1215 842 804 1428 771 1113 601
ACS880-307-1820A-3+A004+A018 2232 1822 1263 1205 2143 1157 1670 902
ACS880-307-2430A-3+A004+A018 2976 2430 1683 1607 2857 1543 2226 1202
ACS880-307-3640A-3+A004+A018 4464 3645 2525 2411 4285 2314 3339 1803
ACS880-307-5470A-3+A004+A018 6696 5467 3788 3616 6428 3471 5009 2705
UN = 500 V
6-pulse
ACS880-307-0650A-5+A018 800 653 566 540 768 518 598 404
ACS880-307-0980A-5+A018 1200 980 849 810 1152 778 898 606
ACS880-307-1210A-5+A018 1488 1215 1052 1004 1428 964 1113 751
ACS880-307-1820A-5+A018 2232 1822 1578 1507 2143 1446 1670 1127
84 Technical data
Definitions
Nominal ratings
Icontmax continuous output (DC) current. No overload capability at 40 °C (104 °F).
IN continuous rms input (AC) current. No overload capability at 40 °C (104 °F).
SN nominal apparent power
PN nominal active power
Light-overload use (10% overload capability) ratings
ILd continuous current. 10% overload is allowed for one minute every 5 minutes.
PLd active power in light-overload use
Heavy-duty use (40% overload capability) ratings
IHd continuous current. 40% overload is allowed for one minute every 5 minutes.
PHd active power in heavy-duty use
Technical data 85
Derating
Ambient temperature derating
In the temperature range +40…50 °C (+104…122 °F), the rated output current is derated
by 1% for every added 1 °C (1.8 °F). The output current can be calculated by multiplying
the current given in the rating table by the derating factor (k):
1.00
0.90
0.80
+40 °C +50 °C T
+104 °F +122 °F
Altitude derating
At altitudes 0 … 2000 m (6561.7 ft) - no derating. For derating at altitudes over 2000 m
(6561.7 ft), contact ABB.
86 Technical data
Fuses
Module DC fuses (internal)
Supply unit type Type Pcs. Manuf. UN IN Size I2t
V A A2 sec
UN = 400 V
6-pulse
ACS880-307-0650A-3+A018 170M5499 4 Bussmann 1250 900 2 1750000
ACS880-307-0980A-3+A018 170M5499 4 Bussmann 1250 900 2 1750000
ACS880-307-1210A-3+A018 170M5499 8 Bussmann 1250 900 2 1750000
ACS880-307-1820A-3+A018 170M5499 8 Bussmann 1250 900 2 1750000
ACS880-307-2730A-3+A018 170M5499 12 Bussmann 1250 900 2 1750000
ACS880-307-3640A-3+A018 170M5499 16 Bussmann 1250 900 2 1750000
ACS880-307-4560A-3+A018 170M5499 20 Bussmann 1250 900 2 1750000
ACS880-307-5470A-3+A018 170M5499 24 Bussmann 1250 900 2 1750000
12-pulse
ACS880-307-0910A-3+A004+A018 170M4908 4 Bussmann 1000 700 1 755000
ACS880-307-1210A-3+A004+A018 170M5499 8 Bussmann 1250 900 2 1750000
ACS880-307-1820A-3+A004+A018 170M5499 8 Bussmann 1250 900 2 1750000
ACS880-307-2430A-3+A004+A018 170M5499 16 Bussmann 1250 900 2 1750000
ACS880-307-3640A-3+A004+A018 170M5499 16 Bussmann 1250 900 2 1750000
ACS880-307-5470A-3+A004+A018 170M5499 24 Bussmann 1250 900 2 1750000
UN = 500 V
6-pulse
ACS880-307-0650A-5+A018 170M5499 4 Bussmann 1250 900 2 1750000
ACS880-307-0980A-5+A018 170M5499 4 Bussmann 1250 900 2 1750000
ACS880-307-1210A-5+A018 170M5499 8 Bussmann 1250 900 2 1750000
ACS880-307-1820A-5+A018 170M5499 8 Bussmann 1250 900 2 1750000
ACS880-307-2730A-5+A018 170M5499 12 Bussmann 1250 900 2 1750000
ACS880-307-3640A-5+A018 170M5499 16 Bussmann 1250 900 2 1750000
ACS880-307-4560A-5+A018 170M5499 20 Bussmann 1250 900 2 1750000
ACS880-307-5470A-5+A018 170M5499 24 Bussmann 1250 900 2 1750000
12-pulse
ACS880-307-0910A-5+A004+A018 170M4908 4 Bussmann 1000 700 1 755000
ACS880-307-1210A-5+A004+A018 170M5499 8 Bussmann 1250 900 2 1750000
ACS880-307-1820A-5+A004+A018 170M5499 8 Bussmann 1250 900 2 1750000
ACS880-307-2430A-5+A004+A018 170M5499 16 Bussmann 1250 900 2 1750000
ACS880-307-3640A-5+A004+A018 170M5499 16 Bussmann 1250 900 2 1750000
ACS880-307-5470A-5+A004+A018 170M5499 24 Bussmann 1250 900 2 1750000
UN = 690 V
6-pulse
ACS880-307-0570A-7+A018 170M5499 4 Bussmann 1250 900 2 1750000
ACS880-307-0820A-7+A018 170M5499 4 Bussmann 1250 900 2 1750000
ACS880-307-1060A-7+A018 170M5499 8 Bussmann 1250 900 2 1750000
ACS880-307-1520A-7+A018 170M5499 8 Bussmann 1250 900 2 1750000
ACS880-307-2280A-7+A018 170M5499 12 Bussmann 1250 900 2 1750000
ACS880-307-3040A-7+A018 170M5499 16 Bussmann 1250 900 2 1750000
ACS880-307-3800A-7+A018 170M5499 20 Bussmann 1250 900 2 1750000
ACS880-307-4560A-7+A018 170M5499 24 Bussmann 1250 900 2 1750000
12-pulse
ACS880-307-0760A-7+A004+A018 170M4908 4 Bussmann 1000 700 755000
ACS880-307-1060A-7+A004+A018 170M5499 8 Bussmann 1250 900 2 1750000
ACS880-307-1520A-7+A004+A018 170M5499 8 Bussmann 1250 900 2 1750000
ACS880-307-2130A-7+A004+A018 170M5499 16 Bussmann 1250 900 2 1750000
ACS880-307-3040A-7+A004+A018 170M5499 16 Bussmann 1250 900 2 1750000
ACS880-307-4560A-7+A004+A018 170M5499 24 Bussmann 1250 900 2 1750000
3AXD00000601909.XLS.C
88 Technical data
Module-specific AC fuses
Supply unit type Supply module Fuse
Type Size Type Manuf. Qty
UN = 400 V
6-pulse
ACS880-307-0650A-3+A018 ACS880-304-0650A-3+A018 D8T 170M6415 Cooper Buss. 3
ACS880-307-0980A-3+A018 ACS880-304-0980A-3+A018 D8T 170M6419 Cooper Buss. 3
ACS880-307-1210A-3+A018 ACS880-304-0650A-3+A018 2xD8T 170M6415 Cooper Buss. 6
ACS880-307-1820A-3+A018 ACS880-304-0980A-3+A018 2xD8T 170M6419 Cooper Buss. 6
ACS880-307-2730A-3+A018 ACS880-304-0980A-3+A018 3xD8T 170M6419 Cooper Buss. 9
ACS880-307-3640A-3+A018 ACS880-304-0980A-3+A018 4xD8T 170M6419 Cooper Buss. 12
ACS880-307-4560A-3+A018 ACS880-304-0980A-3+A018 5xD8T 170M6419 Cooper Buss. 12
ACS880-307-5470A-3+A018 ACS880-304-0980A-3+A018 6xD8T 170M6419 Cooper Buss. 18
12-pulse
ACS880-307-0910A-3+A004+A018 ACS880-304-0490A-3+A018 2xD7T 170M6412 Cooper Buss. 6
ACS880-307-1210A-3+A004+A018 ACS880-304-0650A-3+A018 2xD8T 170M6415 Cooper Buss. 6
ACS880-307-1820A-3+A004+A018 ACS880-304-0980A-3+A018 2xD8T 170M6419 Cooper Buss. 6
ACS880-307-2430A-3+A004+A018 ACS880-304-0650A-3+A018 4xD8T 170M6415 Cooper Buss. 12
ACS880-307-3640A-3+A004+A018 ACS880-304-0980A-3+A018 4xD8T 170M6419 Cooper Buss. 12
ACS880-307-5470A-3+A004+A018 ACS880-304-0980A-3+A018 6xD8T 170M6419 Cooper Buss. 18
UN = 500 V
6-pulse
ACS880-307-0650A-5+A018 ACS880-304-0650A-5+A018 D8T 170M6419 Cooper Buss. 3
ACS880-307-0980A-5+A018 ACS880-304-0980A-5+A018 D8T 170M6419 Cooper Buss. 3
ACS880-307-1210A-5+A018 ACS880-304-0650A-5+A018 2xD8T 170M6419 Cooper Buss. 6
ACS880-307-1820A-5+A018 ACS880-304-0980A-5+A018 2xD8T 170M6419 Cooper Buss. 6
ACS880-307-2730A-5+A018 ACS880-304-0980A-5+A018 3xD8T 170M6419 Cooper Buss. 9
ACS880-307-3640A-5+A018 ACS880-304-0980A-5+A018 4xD8T 170M6419 Cooper Buss. 12
ACS880-307-4560A-5+A018 ACS880-304-0980A-5+A018 5xD8T 170M6419 Cooper Buss. 15
ACS880-307-5470A-5+A018 ACS880-304-0980A-5+A018 6xD8T 170M6419 Cooper Buss. 18
12-pulse
ACS880-307-0910A-5+A004+A018 ACS880-304-0490A-5+A018 2xD7T 170M6412 Cooper Buss. 6
ACS880-307-1210A-5+A004+A018 ACS880-304-0650A-5+A018 2xD8T 170M6419 Cooper Buss. 6
ACS880-307-1820A-5+A004+A018 ACS880-304-0980A-5+A018 2xD8T 170M6419 Cooper Buss. 6
ACS880-307-2430A-5+A004+A018 ACS880-304-0650A-5+A018 4xD8T 170M6419 Cooper Buss. 12
ACS880-307-3640A-5+A004+A018 ACS880-304-0980A-5+A018 4xD8T 170M6419 Cooper Buss. 12
ACS880-307-5470A-5+A004+A018 ACS880-304-0980A-5+A018 6xD8T 170M6419 Cooper Buss. 18
UN = 690 V
6-pulse
ACS880-307-0570A-7+A018 ACS880-304-0570A-7+A018 D8T 170M6414 Cooper Buss. 3
ACS880-307-0820A-7+A018 ACS880-304-0820A-7+A018 D8T 170M6417 Cooper Buss. 3
ACS880-307-1060A-7+A018 ACS880-304-0570A-7+A018 2xD8T 170M6414 Cooper Buss. 6
ACS880-307-1520A-7+A018 ACS880-304-0820A-7+A018 2xD8T 170M6417 Cooper Buss. 6
ACS880-307-2280A-7+A018 ACS880-304-0820A-7+A018 3xD8T 170M6417 Cooper Buss. 9
ACS880-307-3040A-7+A018 ACS880-304-0820A-7+A018 4xD8T 170M6417 Cooper Buss. 12
ACS880-307-3800A-7+A018 ACS880-304-0820A-7+A018 5xD8T 170M6417 Cooper Buss. 15
ACS880-307-4560A-7+A018 ACS880-304-0820A-7+A018 6xD8T 170M6417 Cooper Buss. 18
12-pulse
ACS880-307-0760A-7+A004+A018 ACS880-304-0410A-7+A018 2xD7T PC31UD69V700TF Mersen 6
ACS880-307-1060A-7+A004+A018 ACS880-304-0570A-7+A018 2xD8T 170M6414 Cooper Buss. 6
ACS880-307-1520A-7+A004+A018 ACS880-304-0820A-7+A018 2xD8T 170M6417 Cooper Buss. 6
ACS880-307-2130A-7+A004+A018 ACS880-304-0570A-7+A018 4xD8T 170M6414 Cooper Buss. 12
ACS880-307-3040A-7+A004+A018 ACS880-304-0820A-7+A018 4xD8T 170M6417 Cooper Buss. 12
ACS880-307-4560A-7+A004+A018 ACS880-304-0820A-7+A018 6xD8T 170M6417 Cooper Buss. 18
> 400 mm
(15.75 in.)
IP22/42 IP54
Technical data 91
Front Side
Above
Technical data 93
Front Side
Above
94 Technical data
Front Side
Above
Technical data 95
Front Side
Above
96 Technical data
Front Side
Above
Technical data 97
Efficiency > 99% See section Losses, air flow, efficiency and noise on page 91.
Protection classes
Degrees of protection IP22 (standard), IP42 (option +B054), IP54 (option +B055)
(IEC/EN 60529)
Enclosure types (UL50) UL Type 1 (standard), UL Type 1 Filtered (option +B054), UL Type 12 (option
+B055). For indoor use only.
Overvoltage category III
(IEC 60664-1)
Protective class I
(IEC/EN 61800-5-1)
Ambient conditions
The unit is to be used in a heated indoor controlled environment.
Operation Storage Transportation
Altitude above sea level 0…2000 m - -
For altitudes over 2000 m, contact ABB. -
Temperature 0…+40°C (+32 …+104°F), -40…+70°C -40…+70°C
no condensation allowed (-104 … +158°F) (-104 … +158°F)
+40…+50°C (+104…+122°F) derating 1% /1°C (+33.8°F) above 40°C (+104°F).
For more information, see Ambient temperature derating on page 85.
Relative humidity Maximum 95%, no Maximum 95%, no Maximum 95%, no
condensation allowed condensation allowed condensation allowed
98 Technical data
Vibration 10…58 Hz, max. For modules and cabinets For cabinet package:
IEC 60068-2-6:2007, 0.075 mm displacement in packages: IEC/EN IEC/EN 60721-3-1:1997
amplitude 60721-3-1:1997 Classification of
EN 60068-2-6:2008
Classification of environmental conditions -
Environmental testing Part 58…150 Hz 10 m/s2
environmental conditions - Part 3: Classification of
2-6: Tests -Test Fc:
Part 3: Classification of groups of environmental
Vibration sinusoidal
groups of environmental parameters and their
parameters and their severities - Section 2:
severities - Section 1: Transportation
Storage
Shock Not allowed With packing max. With packing max.
IEC 60068-2-27:2008 100 m/s (330 ft./s ) 11 ms 100 m/s2 (330 ft./s2) 11 ms
2 2
EN 60068-2-27:2009
Environmental testing - Part
2-27: Tests - Test Ea and
guidance: Shock
Contamination IEC/EN 60721-3-3:2002: IEC 60721-3-1 IEC 60721-3-2
Classification of
environmental conditions -
Part 3-3: Classification of
groups of environmental
parameters and their
severities Stationary use
of weather protected
locations
Chemical gases: Class Chemical gases: Class Chemical gases: Class
3C2 1C2 2C2
Solid particles: Class 3S1 Solid particles: Class 1S3 Solid particles: Class 2S2
with IP20/21, 3S2 with (packing must support this,
higher IP class otherwise 1S2)
No conductive dust
allowed.
Cooling
Method Forced air-cooling (fans)
Air flow See Losses, air flow, efficiency and noise, page 91
Materials
Cabinet Hot-dip zinc coated 1.5 mm thick steel sheet (thickness of coating approximately
20 micrometers). Polyester thermosetting powder coating (thickness
approximately 80 micrometers) on visible surfaces, color RAL 7035 and RAL
9017. PC/ABS 3 mm, color NCS 1502-Y (RAL 9002 / PMS 1C Cool Grey).
Busbars Tin-plated copper
Air filters of IP54 units Inlet (door) Outlet (roof)
Camfil/airComp 300-50 Camfil/airTex G150
288 mm x 521 mm 2 pcs: 398 mm x 312 mm
688 mm x 521 mm
Fire safety of materials Insulating materials and non-metallic items mostly self-extinctive
(IEC 60332-1)
Technical data 99
Standards
See Electrical planning instructions for ACS880 multidrive cabinets and modules [3AUA0000102324
(English)].
Markings
See Electrical planning instructions for ACS880 multidrive cabinets and modules [3AUA0000102324
(English)].
Disclaimer
The manufacturer shall have no obligation with respect to any product which (i) has been
improperly repaired or altered; (ii) has been subjected to misuse, negligence or accident;
(iii) has been used in a manner contrary to the manufacturer’s instructions; or (iv) has
failed as a result of ordinary wear and tear.
100 Technical data
Tightening torques
Unless a tightening torque is specified in the text, the following torques can be used.
Cable lugs
Size Max. torque Note
N·m
M8 15 Strength class 8.8
M10 32 Strength class 8.8
M12 50 Strength class 8.8
Electrical connections
Size Torque Note
N·m
M3 0.5 Strength class 4.6...8.8
M4 1 Strength class 4.6...8.8
M5 4 Strength class 8.8
M6 9 Strength class 8.8
M8 22 Strength class 8.8
M10 42 Strength class 8.8
M12 70 Strength class 8.8
M16 120 Strength class 8.8
Mechanical connections
Size Max. torque Note
N·m
M5 6 Strength class 8.8
M6 10 Strength class 8.8
M8 24 Strength class 8.8
Insulation supports
Size Max. torque Note
N·m
M6 5 Strength class 8.8
M8 9 Strength class 8.8
M10 18 Strength class 8.8
M12 31 Strength class 8.8
Control unit 101
8
Control unit
General
The ACS880 drive utilizes BCU-x2 control units. The BCU-x2 consists of a BCON-12
control board (and a BIOC-01 I/O connector board and power supply board) built in a
metal housing.
The supply and inverter units are each controlled by a dedicated BCU-x2 control unit. The
designation of the supply control unit is A51; the inverter control unit is A41. The supply
control unit is located in the auxiliary control cubicle (see the layout drawings in chapter
Layout drawing of an auxiliary control cubicle on page 18), and connect to the supply
module(s) by fiber optic cables.
In this manual, the name “BCU-x2” represents the control unit types BCU-02 and BCU-12
These have a different number of power module connections but are otherwise similar.
102 Control unit
Description
I/O I/O terminals (see following diagram)
7-segment display
Multicharacter indications are displayed as repeated
sequences of characters
(“U” is indicated briefly before “o”.)
Control program startup in progress
Description
XAI Analog inputs
XAO Analog outputs
XDI Digital inputs, Digital input interlock (DIIL)
XRO3 XDIO Digital input/outputs
XD24 XPOW
XD2D Drive-to-drive link
XD24 +24 V output (for digital inputs)
XRO2 XETH Ethernet port (eg. for PC communication)
XDIO XAO
XPOW External power input
XRO1 Relay output RO1
XRO1 XRO2 Relay output RO2
XRO3 Relay output RO3
XDI XAI XSTO Safe torque off connection (input signals)
X485 XSTO OUT Not in use
X13 Control panel / PC connection
X485 Not in use
XD2D XSTO XSTO V1T/V1R, Fiber optic connection to inverter modules 1 and
OUT V2T/V2R 2 (VxT = transmitter, VxR = receiver)
V3T/V3R Fiber optic connection to inverter modules 3…7
… (BCU-12/22 only)
V7T/V7R (VxT = transmitter, VxR = receiver)
V8T/V8R Fiber optic connection to inverter modules 8…12
… (BCU-22 only)
V12T/V12R (VxT = transmitter, VxR = receiver)
1)
Use of the signal in the control program. The use is fixed and it cannot be changed by a parameter.
2)
Default use of the signal in the control program. The use can be changed by a parameter. For the delivery-
specific use, see the delivery-specific circuit diagrams.
3)
Current [0(4)…20 mA, Rin = 100 ohm] or voltage [0(2)…10 V, Rin > 200 kohm] input selected by switch AI1.
Change of setting requires reboot of control unit.
4)
Current [0(4)…20 mA, Rin = 100 ohm] or voltage [0(2)…10 V, Rin > 200 kohm] input selected by switch AI2.
Change of setting requires reboot of control unit.
5)
Must be set to ON when the unit is the first or last unit on the drive-to-drive (D2D) link.
6)
Total load capacity of these outputs is 4.8 W (200 mA at 24 V) minus the power taken by DIO1 and DIO2.
7)
Determines whether DICOM is separated from DIOGND (ie. common reference for digital inputs floats).
DICOM = DIOGND ON: DICOM connected to DIOGND. OFF: DICOM and DIOGND separate. See section
Ground isolation diagram on page 108.
8) This input only acts as a true Safe torque off input in control units controlling a motor. In other applications
(such as a supply or brake unit), de-energizing the IN1 and/or IN2 terminal will stop the unit but not constitute a
true safety function.
Additional remarks
Additional DIIL input (XDI:7)
On both the supply and inverter units, the DIIL input is used for the connection of safety
circuits. The input is parametrized to stop the unit when the input signal is lost.
XD2D
XD2D
B 1
A 2
BGND 3
Shield 4
B 1
A 2
BGND 3
Shield 4
B 1
A 2
BGND 3
Shield 4
DIOx
RL
DIOGND
Reference voltage for analog inputs Connector pitch 5 mm, wire size 2.5 mm2
+VREF and -VREF 10 V ±1% and –10 V ±1%, Rload 1…10 kohm
(XAI:1 and XAI:2)
Control unit 107
Analog inputs AI1 and AI2 Connector pitch 5 mm, wire size 2.5 mm2
(XAI:4 … XAI:7). Current input: –20…20 mA, Rin = 100 ohm
Current/voltage input mode selection by Voltage input: –10…10 V, Rin > 200 kohm
jumpers. Differential inputs, common mode range ±30 V
Sampling interval per channel: 0.25 ms
Hardware filtering: 0.25 ms, adjustable digital filtering up to 8 ms
Resolution: 11 bit + sign bit
Inaccuracy: 1% of full scale range
Analog outputs AO1 and AO2 Connector pitch 5 mm, wire size 2.5 mm2
(XAO) 0…20 mA, Rload < 500 ohm
Frequency range: 0…500 Hz
Resolution: 11 bit + sign bit
Inaccuracy: 2% of full scale range
Drive-to-drive link Connector pitch 5 mm, wire size 2.5 mm2
(XD2D) Physical layer: RS-485
Termination by jumper
RS-485 connection Connector pitch 5 mm, wire size 2.5 mm2
(X485) Physical layer: RS-485
Safe torque off connection Connector pitch 5 mm, wire size 2.5 mm2
(XSTO)
Input voltage range: -3…30 V DC
Logic levels: “0” < 5 V, “1” > 17 V
For the unit to start, both connections must be “1”
Current consumption: 55 mA (continuous)
EMC (immunity) according to IEC 61326-3-1
Safe torque off output Connector pitch 5 mm, wire size 2.5 mm2
(XSTO OUT)
To STO connector of inverter module.
Control panel connection Connector: RJ-45
(X13) Cable length < 3 m
Ethernet connection Connector: RJ-45
(XETH)
SDHC memory card slot Memory card type: SDHC
(SD CARD) Maximum memory size: 4 GB
108 Control unit
XPOW
+24VI 1
GND 2
+24VI 3
GND 4
XAI
+VREF 1
-VREF 2
AGND 3
AI1+ 4
AI1- 5 Common mode voltage between
AI2+ 6 each AI input and AGND is
AI2- 7 +30 V
XAO
AO1 1
AGND 2
AO2 3
AGND 4
XD2D
B 1
A 2
BGND 3
SHIELD 4
XRO1, XRO2, XRO3
NC 11
COM 12
NO 13
NC 21
COM 22
NO 23
NC 31
COM 32
NO 33
XD24
+24VD 1 *Ground selector (DICOM = DIOGND)
DICOM 2 settings
+24VD 3
All digital inputs and outputs share a
DIOGND 4
XDIO common ground.
DIO1 1 Ground of digital inputs DI1…DI5 and
DIO2 2 DIIL (DICOM) is isolated from the
DIOGND 3
DIO signal ground (DIOGND) (insulation
DIOGND 4
voltage 50 V).
XDI
DI1 1 *
DI2 2
DI3 3
DI4 4
DI5 5
DI6 6
DIIL 7
XSTO
OUT1 1
SGND 2 Ground
IN1 3
IN2 4
Further information
Product and service inquiries
Address any inquiries about the product to your local ABB representative, quoting the type
designation and serial number of the unit in question. A listing of ABB sales, support and
service contacts can be found by navigating to www.abb.com/searchchannels.
Product training
For information on ABB product training, navigate to www.abb.com/drives and select
Training courses.
www.abb.com/drives
www.abb.com/drivespartners