ACS800-67 Wind Turbine Converters: System Description and Start-Up Guide
ACS800-67 Wind Turbine Converters: System Description and Start-Up Guide
ACS800-67 Wind Turbine Converters: System Description and Start-Up Guide
Firmware manuals
ACS800 IGBT supply control program firmware manual 3AFE68315735
ACS800 grid-side control program firmware manual 3AUA0000075077
ACS800-67(LC) doubly-fed induction generator control 3AUA0000071689
program firmware manual
Option manuals
Manuals for fieldbus adapters, etc.
Table of contents
Table of contents
2. System description
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
ACS800-67 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Wind turbine system with low voltage stator (690 V) . . . . . . . . . . . . . . . . . . . . . . . 15
Wind turbine system with medium voltage stator (> 1000 V) . . . . . . . . . . . . . . . . . 15
Converter system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Control of generator power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Operational speed range of a typical wind turbine . . . . . . . . . . . . . . . . . . . . . . . . . 19
Wind turbine system operating speed area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Control of torque and reactive power via rotor-side converter . . . . . . . . . . . . . . . . 21
Control of torque and reactive power via grid-side converter . . . . . . . . . . . . . . . . 25
Overview of converter interfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Converter control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
PLC interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Fieldbus control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Grid codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Example of grid code regulations in different countries . . . . . . . . . . . . . . . . . . . . . . . 30
Example limit curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Description of parameter settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Grid fault ride-trough capability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Grid support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Grid support areas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Grid support example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Stator circuit connection to grid . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Stator breaker only (par. 16.20 GRID CONNECT MODE set to MCB3) . . . . . . . . . . 36
Main circuit breaker (par. 16.20 GRID CONNECT MODE set to MCB1+MCB3/A) . . 37
Main circuit breaker (par. 16.20 GRID CONNECT MODE set to MCB1+MCB3/B) . . 37
Stator contactor (par. 16.20 GRID CONNECT MODE set to MCB1+MCB3/C) . . . . . 38
Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Grid connection procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Phasing checks executed at start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Grid phasing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
6
Encoder phasing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Stator phasing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Rotor phasing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
5. Practical examples
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Setting up the fieldbus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Fieldbus interfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Entering start-up data and torque settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Calculating/setting the motor nominal torque . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Torque set-point . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Stator current and voltage measurement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
NUIM-6x voltage measurement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
NUIM-1x voltage measurement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
7
Further information
Product and service inquiries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
Product training . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
Providing feedback on ABB manuals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
About this manual 9
1
About this manual
Applicability
This manual describes the standard ACS800-67 wind turbine converter but it can be
applied to customized units as well.
The control programs referred to in this manual are
• grid-side converter control programs:
• IGBT supply control program IXXR72xx (NUIM board in use) or
• grid-side control program IWXR74xx (NAMU / BAMU board in use)
• rotor-side converter control programs:
• doubly-fed induction generator control program AJXC24xx.
Safety instructions
Converter hardware manual ACS800-67 wind turbine converters for asynchronous slip
ring generators hardware manual [3AFE68392454 (English)] contains the general safety
instructions that must be followed during installation, start-up, maintenance and use of the
converter.
10 About this manual
Target audience
This manual is intended for people who conduct start-ups and operate with the converter.
Read the manual before working on the converter. You are expected to know the
fundamentals of electricity, wiring, electrical components and electrical schematic
symbols.
In all deliveries ACS800-67 wind turbine converters for asynchronous slip ring generators
hardware manual [3AFE68392454 (English)]
This manual covers the following subjects about the converter:
• safety
• operation basics
• hardware description
• mechanical installation
• electrical installation
• installation checklist
• maintenance
• technical data.
In deliveries with ACS800 IGBT supply control program firmware manual [3AFE68315735 (English)]
IGBT supply
control program This manual describes the program controlling the grid-side converter. The following
IXXR72xx subjects apply to the grid-side converter of the wind turbine converter as such:
• actual signals and parameters
• fault tracing.
In deliveries with Grid-side control program for ACS800 wind turbine converters firmware manual
grid-side control [3AUA0000075077 (English)]
program This manual describes the program controlling the grid-side converter. The following
IWXR74xx subjects apply to the grid-side converter of the wind turbine converter as such:
• signals and parameters
• fault tracing.
In all deliveries ACS800-67(LC) doubly-fed induction generator control program firmware manual
[3AUA0000071689 (English)]
This manual describes the program controlling the rotor-side converter. The following
subjects apply to the rotor-side converter of the wind turbine converter as such:
• signals and parameters
• fault tracing.
With the option Option manuals
The option manuals describe the options.
DriveWindow
DriveWindow 2 user’s manual [3BFE64560981 (English)] describes the use of the
DriveWindow PC tool.
12 About this manual
Further information
Address any inquiries about the product to your local ABB representative, quoting the type
code and serial number of the unit. If the local ABB representative can not be contacted,
address inquiries to nearest country that has support for wind turbine converters. See
detailed contact information from the back cover of this manual.
In case of fault situations, ensure that the information stated below is available to get fast
problem solving assistance:
• fault logger data
• data logger files (data logger 1 and data logger 2) from grid-side and rotor-side
converter control programs
• parameter files from the grid-side and rotor-side converter control programs.
In DriveWindow,
• save the parameters with File / Parameters / Save as command to a .dwp file (for
instructions, see page 100)
• copy the fault data from the Fault logger view and paste it to a .txt file
• copy the graphs from the Data logger view.
Abbreviation Explanation
BAMU Auxiliary measurement unit
DFIG Doubly-fed induction generator
DTC Direct Torque Control
Grid-side A converter that is connected to the electrical power network (grid) and is capable of
converter transferring energy from the converter DC link to the grid and vice versa. The grid-side
converter is also called ISU (see ISU).
IGBT Insulated gate bipolar transistor
ISU IGBT supply unit. IGBT supply modules under control of one control board, and related
components.
INU Inverter unit. Inverter module(s) under control of one control board, and related
components. One INU typically controls one generator.
LVRT Low-voltage ride-through
NAMU Auxiliary Measuring Unit. Performs voltage measurement for RMIO board of the grid-
side converter.
NUIM Voltage and Current Measurement Unit. Performs voltage and current measurement for
AMC board.
MCB Main circuit breaker
PLC Programmable logic controller
PWM Pulse width modulation
Rotor-side A converter that is connected to the generator rotor and controls its operation. The rotor-
converter side converter is also called INU (see INU).
RUSB USB-DDCS adapter
Wind turbine A converter for controlling AC generators in wind turbine applications.
converter
WTC Wind turbine controller
System description 13
2
System description
General
Variable-speed wind turbine concepts can be divided in two main categories, wind turbine
systems equipped with a doubly-fed asynchronous generator or wind turbine systems
equipped with an induction generator like squirrel-cage-, synchronous- or permanent
magnet synchronous generator. Difference between these concepts is that in doubly-fed
systems one-third of the rated generator power is fed through the wind turbine converter to
the 3-phase electrical power network (grid) while in systems equipped with eg, permanent
magnet synchronous generators whole power is fed through the wind turbine converter to
the electrical power network.
In wind power applications, the doubly-fed asynchronous generator rotor is accelerated by
the wind and the mechanical speed is controlled by the pitch of the blades to stay within
the operating speed range until the wind turbine converter is started. In order to stop the
wind turbine converter, the breaker(s) is/are opened and the rotor is braked to standstill by
pitch control and mechanical brakes. Doubly-fed systems have typically a gear box for
coupling the generator shaft to turbine hub, active control of turbine blade pitch for
maximizing production and controlling mechanical speed, and variable speed operation
depending on the rating of the wind turbine converter relative to turbine rating (eg, ±30% of
the generator synchronous speed).
14 System description
The main components of a wind turbine system are presented in the picture below.
Gear box
Rotor
Wind turbine converter
Nacelle
Generator Blade
Transformer Yaw motors
ACS800-67
ACS800-67 is air-cooled four-quadrant wind turbine converter for wind turbine
applications. The converter can be located up in the nacelle or in down tower of the wind
turbine.
The converter allows independent control of real and reactive flow in either direction (grid
to rotor), or confined to unidirectional (rotor to grid) real power flow. In doubly-fed systems
the stator circuit of the doubly-fed induction generator (DFIG) is connected via stator circuit
breaker to the 3-phase electrical power network while the rotor circuit is connected to a
wind turbine converter via slip rings.
When the rotor is accelerated by the wind and the speed is controlled by the pitch of the
blades, the converter can be controlled either in torque control mode or in active power
control mode. If rotor mechanical speed is within acceptable area, the converter can be
started. When the grid-side converter has charged the intermediate DC link properly
(MCB2 closed), and the rotor-side converter has magnetized the generator rotor properly
(correct voltage magnitude and phase sequence between the stator and grid), stator circuit
breaker/contactor can be closed (MCB3), and the converter is ready to operate and deliver
power to the 3-phase electrical power network.
In order to stop the converter, the breakers (MCB2 and MCB3) are opened and the rotor is
braked to standstill by pitch control and mechanical brakes. Block diagrams of the wind
turbine system are shown below. The system includes a doubly-fed AC induction
generator and the wind turbine converter.
System description 15
9 12 11
10
1)
4 6 17
ABRU 16
8
R2
1
7
3 INU ISU LCL MCB2
ACBU 14
CONVERTER CTRL
R2
15
WIND TURBINE CTRL
2
1) Optional in ACS800-67
11
9 12 13
5 MCB3
MCB
4 17
6
ABRU
8
R2
1
7
3 INU ISU LCL MCB2
ACBU
14
CONVERTER CTRL
R2
15
WIND TURBINE CTRL
2
Converter system
Doubly-fed asynchronous generators are essentially wound rotor induction machines with
variable frequency excitation of the rotor circuit, incorporating rotor via frequency
converter. Ability to convert mechanical energy into electrical energy (or vice versa) is
based on electromagnetic induction. In wind power applications, the doubly-fed
asynchronous generator is controlled to operate as generator quadrature, and thus the
generator stator will always generate energy to the 3-phase electrical power network.
Wind turbine converter consists of two parts, ie, rotor-side converter and grid-side
converter. Between these two converters, a DC link capacitor is placed as an energy
storage in order to keep the voltage variations (or ripple) in the DC link small. Both
converters are controlled independently by internal control firmware based on Direct
Torque Control (DTC) technology.
The grid-side converter is an IGBT based module equipped with AC (optional) and DC
fuses and an LCL filter that suppresses the line harmonics of voltage and current. The
grid-side converter is controlled by RDCU-12 control unit with the grid-side control
program. The rotor-side converter consists of IGBT based modules and is controlled by
NDCU-33CX control unit with the doubly-fed induction generator control program. The
control unit also controls the grid-side converter via a fiber optic link.
With the rotor-side converter, it is possible to control the torque or the speed of the
generator and also the power factor at the stator terminals. The grid-side converter keeps
the DC link voltage constant. Wind turbine systems equipped with doubly-fed
asynchronous generator, the stator always generates energy to the 3-phase electrical
power network, however the direction of the power produced by the rotor depends on the
sign of the slip frequency. When the slip frequency is positive (sub-synchronous
operation), the energy is taken from the 3-phase electrical power network through the grid-
side converter and fed by the rotor-side converter to the rotor via slip rings. In sub-
synchronous operation, a part of the stator generated power is circulated back to the rotor.
These power flows are shown in the picture below.
System description 17
Pact = 3 U I cos
2
Qact = 3 U I 1 - cos
Pgrid = Pstator + PISU
Pstator Pgrid
P = T · Optional
I T
P vwind3
MCB3 MCB1 MCB
PISU
PINU
ABRU
R2
ACBU
CONVERTER CTRL
R2
Below is a power versus speed curve example of a doubly-fed induction generator that
has a synchronous speed of 1000 rpm and nominal speed of 1150 rpm.
250
-250
-500
-750
Active power (kW)
-1000
-1250
-1500
-1750
-2000
-2250
-2500
-2750
1000
1050
1200
1250
1300
1350
1400
1450
1500
550
600
650
700
750
800
850
900
950
1100
1150
Generator rotor speed (rpm) Turbine power delivered to electrical power network (kW)
2000 3600
1900 3200
Power optimization Power limitation
1800 2800
1700 2400
1600 2000
1500 1600
1400 1200
1300 800
1200 400
0 0
0 5 10 15 20 25 30 35
Wind speed (m/s)
Cut-in speed Cut-out speed
System description 19
cp( , )
Pw = · · Ar · vw3
2
where
Pw wind power
air density
Ar rotor surface
vw wind speed.
There is a minimum wind speed at which power generation is reasonable (cut-in speed)
and a maximum speed at which the turbine can be operated safely (cut-out speed). At a
certain wind speed, the turbine controller must limit the rotor speed by changing the pitch
angle.
20 System description
nmin nmax
n1 nA nsync nr n2 n3 nB
2200 2200
1800 1800
Rotor voltage (V)
1600 1600
1400 1400
1200 1200
1000 1000
Umax
800 800
Ucont.max
600 Converter Converter 600
operation is not operation is not
400 allowed allowed 400
200 200
0 0
0 300 600 900 1200 1500 1800 2100 2400 2700 3000
Rotor speed (rpm)
In operating range n1…n3 the rotational speed is under normal operating conditions.
Generator rotational speeds:
nmin = minimum rotor speed which may never be reached, not even momentarily 1)
nmax = maximum rotor speed which may never be exceeded, not even momentarily 1)
n1 = minimum rotor speed when the converter is tripped due to underspeed (30.10 UNDERSPEED LIMIT
level) ie, torque will be controlled to zero and all breaker(s)/contactor(s) are opened 2)
n2 = rotational rotor speed deviation upwards or downwards with nominal power production within standard
tolerance
n3 = maximum speed when the converter is tripped due to overspeed (30.09 OVERSPEED LIMIT level) ie,
torque will be controlled to zero and all breaker(s)/contactor(s) are opened 2)
nA = cut-in speed equals to the converter minimum operating speed while converter starts and generator
stator synchronisation is allowed (20.21 SWITCH ON SPEED and 20.22 SWITCH OFF SPEED
levels)
nB = cut-out speed ie, the speed at which the turbine control system must immediately shut down the wind
turbine
nr = rated speed ie, rotational speed at rated wind speed to generate nominal power to electrical power
network
nsync = generator synchronous speed
1) Activation speed ie, the rotational speed at which the turbine safety system must be triggered immediately
(wind turbine and pitch level protection)
2) If the speed is below (n1) or outside (n3) the speed area, the converter may be damaged due to high rotor
voltage during the shutdown procedure. Generator stator synchronisation to electrical power network is not
allowed in any circumstances and grid disconnection is always required.
System description 21
stator current.
min BAMU
Switching frequency
(optional)
Pref Hysteresis band control
Torque bits
22 System description
NDCU
=
Flux sector identification ASIC INU
Actual flux Switch position commands
Optimum ~
pulse
Flux bit selector
Flux reference Two level hysteresis control crowbar
Actual flux
max Switching frequency
ref
min Torque bits
vector is controlled by the torque error and the radial motion of the flux is controlled by the
The basic DTC block selects the inverter switch states so that tangential motion of the flux
flux error. The torque reference is supplied by the WTC. The torque feedback is calculated
by using stator-side quantities (at grid frequencies) ie, by a cross product of stator flux and
System description 23
The rotor-side flux reference is chosen to achieve the desired power factor at the stator
terminals. The operating flux level of the stator flux is completely dependent on the grid
voltage and therefore the rotor flux reference is dependent on actual stator flux. The figure
below shows the vector diagram of stator voltage, current and flux and rotor flux at leading
and lagging power factors when the stator is regenerating to the electrical power network.
Is Iqs
Ids Us
Us
Ids
Is Iqs
Ȍ s
Ȍ r
Ȍ r
Ȍ s
Symbol Description
Us stator voltage
r
rotor flux
Ȍ
s stator flux
Ȍ
Is stator current
Ids d-axis current of the Is
Iqs q-axis current of the Is
Using stator voltage (and therefore the stator flux) as reference axis, torque is proportional
to the product of Ids and Ȍ s . The magnitude and sign of Iqs determine the type of
reactive (lagging or leading) power drawn by the stator.
24 System description
An example curve of maximum reactive power capability as a function of the active power
(power factor about 0.95 capacitive and 0.86 inductive) is shown below. Reactive power
capability depends on the characteristics of the generator.
Q (p.u.)
Capacitive
0.75
0.5
Reactive 0 P (p.u.)
power 0 0.25 0.5 0.75 1.00
capability at
nominal power -0.25
-0.5
-0.75
-1.00
-1.25
Inductive
Q (p.u.)
System description 25
uL
X = j L
I
u2
U1
u1
iD
i
U2
iQ
Symbol Description
U1 grid voltage
U2 grid-side converter voltage
Power transfer equation between the network and the grid-side converter is following:
U1U2
P= sin
X
26 System description
Reactive power is transferred only if there is an amplitude difference between the two
voltage vectors. Reactive power transfer equation is following:
U12 U1U2
Q= cos
X X
For the desirable magnitude and direction of the power and reactive power flow, the length
of the converter voltage vector and its phase angle (with respect to the grid voltage vector)
must be controlled. The DC voltage is controlled by keeping the power (energy) balance
between the grid and grid-side converter in the DC link constant. The sign of the angle
determines the direction of the power flow. The output AC voltage is controlled by setting
the length of the flux reference to correspond to the desired output voltage level producing
cosfii = 1.0.
The grid-side converter can control reactive power independently of speed and active
power. The maximum reactive current capacity is approximately 80% of the active current
capacity and depends on the rating of the grid-side converter and on the electrical power
network voltage. An example curve of reactive power capability as a function of the active
power is shown below.
Q (p.u.)
0.75
0.5
Converter nominal power
0.25
Reactive
power
capability at 0 P (p.u.)
0 0.25 0.5 0.75 1.00
nominal power
-0.25
-0.5
-0.75
System description 27
Converter control
General
The WTC operates as the overriding controller of the converter. It is connected to the
NDCU control unit of the rotor-side converter via fieldbus. The rotor-side converter control
program controls the rotor-side power modules according to the references and
commands sent by the overriding controller.
PLC interface
The converter can be connected to an external control system – usually a PLC controller –
via a fieldbus adapter connected to channel CH0 of the NDCU control unit.
The following diagram shows the PLC interface:
PLC
WTC
NETA-01 (optional)
Fieldbus
Other Other
devices devices
CH3 CH4
RDCU NDCU Fieldbus adapter
CH0 Nxxx
CH0 CH2
Data Flow
Control Word (CW)
References
Process I/O (cyclic)
Status Word (SW)
Actual values
The converter can be set to receive all of its control information through the fieldbus
interface, or the control can be distributed between the fieldbus interface and other
available sources, eg, digital and analog inputs.
System description 29
Fieldbus control
Fieldbus control of the grid-side converter is performed via the rotor-side converter NDCU
control unit. The principle of reference and actual value chains in the control are shown in
the diagram below. For details, see ACS800-67(LC) doubly-fed induction generator control
program firmware manual [3AUA0000071689 (English)].
Faults
Alarms
30 System description
Grid codes
Grid codes specify static and dynamic requirements to be fulfilled by a wind power
installation. Static requirements mainly determine the voltage control and power control
during normal operation. Most of the recent grid codes include also power quality
requirements such as harmonics distortion limits, flicker etc. Dynamic requirements define
the dynamic behavior of a wind turbine or wind farm under grid disturbance. One of the
most important dynamic requirements is grid fault ride-through capability of the wind power
generator. Grid fault ride-through means that instead of disconnection, the wind
generators have to stay connected to the electrical power network for a certain period.
Grid fault ride-through requirements define:
• how long a grid fault (eg, voltage dip/sag or swell) can last
• how to operate under a balanced (symmetrical) grid fault
• how to operate under an unbalanced (unsymmetrical) grid fault.
The power train concept can be used to find the optimal solution when balancing the
connection requirements and costs of installation. The selection of electrical power train
components (a pitch system, generator, frequency converter and transformer) has effect
on the capability of an individual turbine to comply with the grid code requirements.
Although the converter has an important role in enabling the wind turbine to fulfill the grid
code requirements, it is highly dependent on how the whole wind turbine system and its
process is functioning (the wind turbine controller, pitch system, UPS etc.). The turbine
manufacturer is responsible for fulfilling the requirements of the transmission or
distribution system operator.
100
Tripping required/allowed
Limit line 2
Normal operation
0
0 t1 t2 t3 Time
Fault occurs
Optional
ABRU DC chopper
R2
(optional)
ACBU
CONVERTER CTRL
R2
With the crowbar and the DC chopper, the wind turbine is capable of handling fault
situations like rotor overspeed, short interruptions, voltage dips/sags and swells. With
these energy absorbers, the converter is capable of meeting even the most strictest grid
fault ride-through requirements in accordance with international grid codes.
34 System description
Grid support
In the grid support function, the grid is supported by feeding reactive current to it. The
reactive current reference is defined as a function of the grid voltage. Six different voltage
levels can be defined. Examples of setting the grid support parameters are shown in the
diagrams below. For further information, see ACS800-67(LC) doubly-fed induction
generator control program firmware manual [3AUA0000071689 (English)].
Igs (%)
100
32.20 GS IQREF LEVEL 4
Ugrid (p.u)
0 1.0
-100
Igs (%)
100
P4 P3
75
50
P2
25
P1
Ugrid (p.u)
-25
P5
-50
P6
Ugrid (p.u)
1.5 P6
Igs (%)
P5 P5
1.0 100
Ugrid
P1
P1
P2 P2
0.5 50
P3 P3
Iqref
P4 32.23 GS AFTER DIP
0
t
32.24 GS TIME AFTER DIP
-50
36 System description
Stator breaker only (par. 16.20 GRID CONNECT MODE set to MCB3)
The configuration below is used when the stator is connected to the grid by the breaker
(MCB3) only.
Turbine
transformer
MCB3
MCB2
ISU INU
Turbine
transformer
MCB1 MCB3
G
MCB2
ISU INU
Turbine
transformer
MCB1 MCB3
G
MCB2
ISU INU
Turbine
transformer
MCB1 MCB3
MCB2
ISU INU
The breaking device type for the grid connection is defined by parameter 20.27 CONT
OPEN CUR.
• 0 A = main circuit breaker or medium voltage circuit breaker MCB3 is used for
disconnecting stator from grid
• > 0 A = contactor MCB3 is used for disconnecting stator from grid.
When parameter value [> 0 A] is selected, the converter can be disconnected from the grid
in two ways depending on a parameter setting:
• If measured current 06.29 STATOR IS NO FILT is below the parameter value, the
converter uses the stator contactor only.
• If measured current 06.29 STATOR IS NO FILT is above the parameter value, the
converter first opens the breaker and, after a short time, the stator contactor.
The parameter value is compared to unfiltered stator rms value. Since the unfiltered value
always contains a certain amount of noise, it is recommended to set the parameter to a
value of contactor nominal current +15%. See the delivery specific circuit diagrams.
Settings
Parameter 20.27 CONT OPEN CUR.
In case of one contactor, the value for parameter 20.27 CONT OPEN CUR is the nominal
current of the contactor.
System description 39
Turbine
transformer
MCB3
MCB2
ISU INU
A typical procedure required to connect the wind generator to the grid is as follows:
• The system is operational if the rotor speed is in the predetermined normal operating
range (eg, from 70% to 130% of the synchronous speed).
• MCB2 is closed to start the converter and to establish the DC link for the rotor-side
converter. MCB3 is still open.
• The rotor-side converter measures the grid voltage (input side of MCB3) and the stator
voltage.
• The rotor-side converter shifts to synchronization mode. The rotor-side converter
magnetizes the rotor windings so that the induced stator voltage is synchronized with
the grid voltage (same frequency and magnitude as for the grid voltage).
• MCB3 is closed and the controller shifts to the torque control mode. Now it is ready to
accept the user's torque and power factor (pf) commands. The net power generated to
the grid (from the stator port + the rotor port) is relative to the product of the torque and
the mechanical speed.
The normal shut-down procedure is as follows:
• The system is assumed to be in the torque control mode and the rotor speed in the
predetermined normal operating range (eg, from 70% to 130% of the synchronous
speed).
• After receiving the shut-down command, converter program sets the rotor-side
converter torque reference to zero and power factor command to 1. (Under these
conditions the stator current is zero.)
• MCB3 is opened when the converter detects 0 voltage and 0 current across it.
• The rotor-side converter and then the grid-side converter modulation is stopped.
40 System description
Grid Stator
U V W U V W
NUIM-6x
The following checks are automatically executed at start-up in the order in which they are
listed:
Grid phasing
Grid flux is a measured quantity. The angle of the flux is calculated. The angle is derivated
and filtered. As a result, angular speed of the grid flux is received. If the speed is negative,
the grid phasing is incorrect.
Encoder phasing
The generator actual speed is received from the encoder speed feedback. If the direction
is negative, the encoder phasing is wrong.
Note: This check is executed only if RUN command has been issued.
Stator phasing
During normal operation, the grid flux and the stator flux rotate clockwise at the grid
frequency. If the sum of the rotor flux speed and slip does not rotate at the frequency of the
stator flux, the stator phasing is incorrect.
Note: The rotation speed of the rotor flux is independent of whether the rotor phasing is
correct or not.
Rotor phasing
The dot product between the two flux vectors is approximately +1 when the rotor phasing
is correct and approximately -1 when the rotor phasing is incorrect.
Start-up with low voltage stator 41
3
Start-up with low voltage stator
Stator breaker
ISU INU
Note: Grid-side converters are delivered with one of the following grid voltage
measurement methods:
• The grid-side converter receives the voltage measurement data from the rotor-side
converter. (The rotor-side converter is only fitted with an NUIM board.)
• The grid-side converter is fitted with a dedicated measurement board, NAMU / BAMU.
Each method requires a different grid-side converter control program version. The first
method requires version IXXR7260 with Adaptive program version IZXX0169.AP (or later
versions) while the second requires version IWXR7300 with Adaptive program version
00595631_C.AP (or later versions).
The grid-side converter parameter settings in the start-up procedure below differ
depending on which grid voltage measurement method is used.
42 Start-up with low voltage stator
WARNING! The generator may not be connected to the grid when the rotor is not
rotating. The rotor speed must be in the operational speed area (normally
70…130% of the generator nominal speed). Otherwise grid connection is not
allowed by the converter control program.
Note: For testing purposes the rotor-side converter can be started without closing the
stator breaker at zero speed. Note that the control program is not able to execute the
commissioning check routines at zero speed. The grid-side converter can be tested even
though the generator is not rotating.
Before you start, ensure you have the generator data sheet on hand.
Safety
The start-up may only be carried out by a qualified electrician.
The safety instructions must be followed during the start-up procedure. See ACS800-67 wind
turbine converters for asynchronous slip ring generators hardware manual [3AFE68392454
(English)].
Check the installation. See the installation checklist in the converter hardware manual.
Power-up
Connect fibre optic cables temporarily between channel CH3 of the rotor-side converter NDCU unit
and the DDCS Communication (RUSB-02) card or PCMCIA card.
If an active crowbar is in use (optional), the crowbar test requires communication with the NDCU
unit of the rotor-side converter and RDCU unit of the grid-side converter: Connect the fibre optic
cables in a ring connection between channel CH3 of the NDCU unit and channel CH3 of the RMIO
board and the DDCS Communication (RUSB-02) card or PCMCIA card.
When a PCMCIA card is used, follow the instructions included in the DriveWindow kit.
Enter the generator data from the generator data sheet. For more
information, see section Generator data on page 81.
• maximum allowed long time rotor current limit (for reactive power 99.16 MOTOR NOM IM
supervision) IM
R2PH-
R r = -----------------
U 2 2
--------
U 1
• maximum measurable stator flux. See section Stator current and 99.27 MAX MEAS FLUX
voltage measurement on page 79.
Define the maximum measurable stator current (depends on the used 99.28 MAX MEAS IS
current transformer). See section Stator current and voltage
measurement on page 79.
44 Start-up with low voltage stator
Select the communication profile used by the converter. For more 16.11 COMM PROFILE
information see section ABB Drives communication profile on page
90.
Set parameter limits in group 20 LIMITS according to the process 20.05 USER POS TORQ
requirements. LIM
20.05 USER POS TORQ LIM defines the motoring torque limit 20.06 USER NEG TORQ
20.06 USER NEG TORQ LIM defines the generating torque limit. LIM
20.21 SWITCH ON
SPEED
20.22 SWITCH OFF
SPEED
Select the reactive power reference type 23.04 REACT POW REF
(PERCENT/KVAR/PHII/COSPHII). SEL
Activate the external communication by setting parameter 98.02 98.02 COMM MODULE
COMM MODULE to FBA DSET 10.
Set the fieldbus adapter data according to the used external control 51 MASTER ADAPTER
system.
Note: The configuration parameters are not visible if the module is
not connected or activated in the control program. See appropriate
adapter hardware manual.
Activate the fieldbus adapter supervision toggle bit (if needed). 70.25 TOGGLE BIT SEL
70.26 TOGGLE
ADDRESS SEL
Define the current limit and breaking device type for the grid 20.27 CONT OPEN CUR
connection between stator and grid.
0 A = air circuit breaker used for disconnecting stator from grid.
> 0 A = contactor is used for disconnecting stator from grid.
If stator current exceeds given value at the time disconnection is
requested, then the wind turbine converter first opens the breaker in
front of the contactor, then the contactor shortly later.
Check that the breaker/contactor configuration of the converter is set 16.20 GRID CONNECT
correctly according to the delivery. For configurations available and MODE
corresponding parameter settings, see section Stator circuit
connection to grid on page 36.
Time setting
Set rotor-side converter 16.01 PARAM LOCK to OFF. 16.01 PARAM LOCK
Set the date and time as follows:
• Set parameter 95.07 RTC MODE value to SET. 95.07 RTC MODE
• Check/adjust the date and time by parameters 95.01…95.06. 95.01…95.06
• Set parameter 95.07 RTC MODE value to SHOW.
Digital inputs
Check that all digital inputs are connected properly. 01.15 DI STATUS
Set parameter 21.01 ISU LOCAL CTR WORD to 9 (hex), ie, 1001 21.01 ISU LOCAL CTR
(bin): Grid-side converter starts charging the DC capacitors, closes WORD
the main contactor and starts modulating.
Check the grid-side converter status. Note: Only the three least 05.10 ISU STATUS WORD
significant bits are relevant in this case.
231H (1000110001 bin) before the grid-side converter is started
737H (11100110111 bin) when the grid-side converter is running
238H (1000111000 bin) when the grid-side converter has tripped on a
fault.
Check that the Voltage and Current Measurement Unit NUIM-6x 01.05 NET FREQUENCY
functions, ie, the grid frequency is positive and the grid voltage is 01.11 MAINS VOLTAGE
correct.
Stop the grid-side converter by setting parameter 21.01 ISU LOCAL 21.01 ISU LOCAL CTR
CTR WORD to 0 (hex). WORD
Check the functioning of the crowbar by starting and stopping the 01.15 DI STATUS
grid-side converter. (Parameter 21.01 ISU LOCAL CTR WORD
setting 9 (hex) = START and 0 (hex) = STOP)
When DC voltage is 0 V, 01.15 DI STATUS bit 4 value must be 0
(ie, crowbar inactive). 01.15 DI STATUS = 1303 (hex)
When DC voltage exceeds 100 V, 01.15 DI STATUS bit 4 value must
be 1 (ie, crowbar active). 01.15 DI STATUS = 1713 (hex)
If the converter is NOT equipped with an active crowbar, continue to the next section.
Activate the active crowbar by setting rotor-side converter parameter 31.01 CROWBAR HW
31.01 CROWBAR HW TYPE according to the type of active crowbar TYPE
in use.
Note: If the converter is equipped with an active crowbar, it must
always be activated by parameter 31.01 even when low voltage ride
through (LVRT) and / or grid support is not used.
Start the grid-side converter by setting parameter 21.01 ISU LOCAL 21.01 ISU LOCAL CTR
CTR WORD to 9 (hex). WORD
Check the communication between the rotor-side converter and the 06.13 CB IGBT TEMP
active crowbar:
The communication is OK if the temperature of the crowbar is about
25…40 °C and the converter does not trip for crowbar communication
time-out.
46 Start-up with low voltage stator
NUIM board in use (grid-side converter control program 01.11 MAINS VOLTAGE
IXXR72xx):
Check grid-side converter parameter 01.11 MAINS VOLTAGE value
(= mains voltage received from the rotor-side converter). If the
voltage level is correct, communication between rotor-side and grid-
side converters is OK.
Check grid-side converter mains voltage measurement phase See grid-side converter
sequence: parameter list:
Monitor the following grid-side converter signals with DriveWindow 16.03 PASS CODE
datalogger with 1 ms time level, when grid-side converter is started: 138.02 FLUX X NET ACT
NUIM board in use (grid-side converter control program 138.03 FLUX Y NET ACT
IXXR72xx):
161.04 FLUX X ACT
138.02 FLUX X NET ACT
138.03 FLUX Y NET ACT 161.05 FLUX Y ACT
161.04 FLUX X ACT
161.05 FLUX Y ACT
Start DriveWindow datalogger and trigger manually. Upload
datalogger information:
If parameter 138.02 FLUX X NET ACT and 161.04 FLUX X ACT
signals are in phase and parameter 138.03 FLUX Y NET ACT and
161.05 FLUX Y ACT signals are in phase, the flux measurement is
OK.
NAMU / BAMU board in use (grid-side converter control program 02.22 FLUX X NET ACT
IWXR74xx): 02.23 FLUX Y NET ACT
02.22 FLUX X NET ACT 02.20 FLUX X ACT
02.23 FLUX Y NET ACT
02.21 FLUX Y ACT
02.20 FLUX X ACT
02.21 FLUX Y ACT
Start DriveWindow datalogger and trigger manually. Upload
datalogger information:
If parameter 02.22 FLUX X NET ACT and 02.20 FLUX X ACT signals
are in phase and parameter 02.23 FLUX Y NET ACT and 02.21
FLUX Y ACT signals are in phase, the flux measurement is OK.
Note: If this test fails, grid-side converter grid voltage cabling must be
checked. See the converter hardware manual.
Stop the grid-side converter by setting parameter 21.01 ISU LOCAL 21.01 ISU LOCAL CTR
CTR WORD to 0. WORD
Check the grid-side converter parameters. See the grid-side
converter parameter list in ACS800-67(LC) doubly-fed induction
generator control program firmware manual [3AUA0000071689
(English)].
Disable the main circuit breaker function by setting parameter 21.02 21.02 DISABLE MCB
DISABLE MCB CLOSE to YES (the rotor-side converter CLOSE
synchronizes to the grid but does not close the main circuit breaker).
Start the converter with zero speed with the DriveWindow START 06.11 CB BRIDGE
button. VOLTAGE
Check crowbar measurements after the DC link has been charged: 06.12 CB IGBT VOLTAGE
Measurements are OK, if parameter 06.11 CB BRIDGE VOLTAGE 06.13 CB IGBT TEMP
and 06.12 CB IGBT VOLTAGE values are higher than the DC link
voltage (01.10 DC VOLTAGE) and parameter 06.13 CB IGBT TEMP
value is approximately 25…40 °C.
The following figure shows the active crowbar voltages when manual triggering is used.
Set the Low Voltage Ride Through function and Grid Support function Grid support function can
parameters. Values must be set according to the selected grid code. be tuned by parameters in
See ACS800-67(LC) doubly-fed induction generator control program group 32 LV RIDE-
firmware manual [3AUA0000071689 (English)]. THROUGH.
Set parameter 30.13 DI7 EXT EVENT to NO. (grid-side converter 30.13 DI7 EXT EVENT
par.)
The DC chopper function can be tested by feeding a short UDC voltage pulse to RMIO (grid-side converter).
Set RMIO (grid-side converter) DC voltage ref limit 113.01 DC REF MAX
113.01 DC REF MAX to 1150 V.
Set parameter 21.06 PULSE LENGTH [sec] to eg, 0.5 sec. 21.06 PULSE LENGTH
(rotor-side converter par.) [sec]
If the grid-side converter generates power to the DC chopper and the UDC voltage does not reach
PULSE VALUE [V], then the DC chopper test is passed.
When the test is passed, restore parameter 137.02 MOT POWER 137.02 MOT POWER
LIMIT (ISU) to 150% and parameter 113.01 DC REF MAX to LIMIT
1073.39 V. 113.01 DC REF MAX
Check that the wind turbine rotates the rotor speed within acceptable 01.01 MOTOR SPEED
range (approximately 1200…1700 rpm).
K??
K??
K???
??
??
??
??
?
? K } > | K?
[??
The following figure represent synchronization at 1300 rpm speed (under speed synchronization).
06.08 STATOR Y FLUX is synchronized to 06.06 GRID Y FLUX and 06.07 STATOR U FLUX is
synchronized to 06.06 GRID U FLUX.
0607
064
0608
060
060
063
Enable the main circuit breaker function by setting parameter 21.02 21.02 DISABLE MCB
DISABLE MCB CLOSE to NO. Check that the main circuit breaker CLOSE
operates correctly.
Check the stator current measurement by giving a small torque 25.04 TORQUE REF A
(25.04 TORQUE REF A) reference, eg, 15%. The current 01.02 GENERATOR
measurement is correct if the actual torque value TORQUE
01.02 GENERATOR TORQUE follows the given reference.
Check wiring.
Close the damper (T100 power off) and connect the auxiliary
voltages.
• Check that A42: UAO2 = 0 V.
Set temporarily parameter 15.06 ANALOGUE OUTPUT 2 setting 112 15.06 ANALOGUE
to 1910. OUTPUT 2
Check that operation of the damper follows the graph shown below by writing values to parameter
1910 (this parameter imitates PP TEMP values):
• 1910< 18 damper closed
• 1910 > 18 damper starts to open, see the graph
• 1910 = 50 damper fully open, plate in 90° position.
AO2
U500ohm
Mech.
position
Position
feedback
PP TEMPERATURE
Close FF005.
Check that the air damper starts to open when the converter PP
TEMP starts to increase. You can monitor signals by means of
DriveWindow:
• 01.12 PP TEMPERATURE
• 15.06 ANALOGUE OUTPUT 2 (damper control)
• 05.07 ISU AI1 [V] (damper position is monitored via this signal).
Final settings
Disable the parameter lock by setting parameter 16.03 PASS CODE 16.03 PASS CODE
to 358 or 564 in rotor-side and grid-side converter.
Note: Not needed with grid-side converter control program
IWXR74xx.
Set the stator current fault trip limit to 0 A. 30.04 STATOR CURR
TRIP
Make special parameter settings (if any) according to eg, grid code.
See section Setting the parameters according to grid code on page
108.
Lock the parameter settings by setting parameter 16.01 PARAM 16.01 PARAM LOCK
LOCK to ON in rotor-side converter.
Note: Not needed with grid-side converter control program
IWXR74xx.
4
Start-up with medium voltage
stator
12 kV
G
690 V
ISU INU
Note: Grid-side converters are delivered with one of the following grid voltage
measurement methods:
• The grid-side converter receives the voltage measurement data from the rotor-side
converter. (The rotor-side converter is only fitted with an NUIM board.)
• The grid-side converter is fitted with a dedicated measurement board, NAMU / BAMU.
Each method requires a different grid-side converter control program version. The first
method requires version IXXR7260 with Adaptive program version IZXX0169.AP (or later
versions) while the second requires version IWXR7300 with Adaptive program version
00595631_C.AP (or later versions).
The grid-side converter parameter settings in the start-up procedure below differ
depending on which grid voltage measurement method is used.
56 Start-up with medium voltage stator
WARNING! The generator may not be connected to the grid when the rotor is not
rotating. The rotor speed must be in the operational speed area (normally
70…130% of the generator nominal speed). Otherwise grid connection is not
allowed by the converter control program.
Note: For testing purposes the rotor-side converter can be started without closing the
stator breaker at zero speed. Note that the control program is not able to execute the
commissioning check routines at zero speed. The grid-side converter can be tested even
though the generator is not rotating.
Before you start, ensure you have the generator data sheet on hand.
Safety
The start-up may only be carried out by a qualified electrician.
The safety instructions must be followed during the start-up procedure. See ACS800-67 wind
turbine converters for asynchronous slip ring generators hardware manual [3AFE68392454
(English)].
Check the installation. See the installation checklist in the converter hardware manual.
Power-up
Connect fibre optic cables temporarily between channel CH3 of the rotor-side converter NDCU unit
and the DDCS Communication (RUSB-02) card or PCMCIA card.
If an active crowbar is in use (optional), the crowbar test requires communication with the NDCU
unit of the rotor-side converter and RDCU unit of the grid-side converter: Connect the fibre optic
cables in a ring connection between channel CH3 of the NDCU unit and channel CH3 of the RMIO
board and the DDCS Communication (RUSB-02) card or PCMCIA card.
When a PCMCIA card is used, follow the instructions included in the DriveWindow kit.
Enter the generator data from the generator data sheet. For more
information, see section Generator data on page 81.
• maximum allowed long time rotor current limit (for reactive power 99.16 MOTOR NOM IM
supervision) IM
R r = R2PH
------------------
U 2 2
--------
U 1
• maximum measurable stator flux. See section Stator current and 99.27 MAX MEAS FLUX
voltage measurement on page 79.
Define the maximum measurable stator current (depends on the used 99.28 MAX MEAS IS
current transformer). See section Stator current and voltage
measurement on page 79.
58 Start-up with medium voltage stator
Select the communication profile used by the converter. For more 16.11 COMM PROFILE
information see section ABB Drives communication profile on page
90.
Set parameter limits in group 20 LIMITS according to the process 20.05 USER POS TORQ
requirements. LIM
20.05 USER POS TORQ LIM defines the motoring torque limit 20.06 USER NEG TORQ
20.06 USER NEG TORQ LIM defines the generating torque limit. LIM
20.21 SWITCH ON
SPEED
20.22 SWITCH OFF
SPEED
Select the reactive power reference type 23.04 REACT POW REF
(PERCENT/KVAR/PHII/COSPHII). SEL
Activate the external communication by setting parameter 98.02 98.02 COMM MODULE
COMM MODULE to FBA DSET 10.
Set the fieldbus adapter data according to the used external control 51 MASTER ADAPTER
system.
Note: The configuration parameters are not visible if the module is
not connected or activated in the control program. See appropriate
adapter Hardware Manual.
Activate the fieldbus adapter supervision toggle bit (if needed). 70.25 TOGGLE BIT SEL
70.26 TOGGLE
ADDRESS SEL
Define the current limit and breaking device type for the grid 20.27 CONT OPEN CUR
connection between stator and grid.
0 A = Medium voltage circuit breaker used for disconnecting stator
from grid.
Check that the breaker/contactor configuration of the converter is set 16.20 GRID CONNECT
correctly according to the delivery. For configurations available and MODE
corresponding parameter settings, see section Stator circuit
connection to grid on page 36.
Time setting
Set rotor-side converter 16.01 PARAM LOCK to OFF. 16.01 PARAM LOCK
Set the date and time as follows: 95.07 RTC MODE
• Set parameter 95.07 RTC MODE value to SET. 95.01…95.06
• Check/adjust the date and time by parameters 95.01…95.06.
• Set parameter 95.07 RTC MODE value to SHOW.
Digital inputs
Check that all digital inputs are connected properly. 01.15 DI STATUS
Start-up with medium voltage stator 59
Set parameter 21.01 ISU LOCAL CTR WORD to 9 (hex), ie, 1001 21.01 ISU LOCAL CTR
(bin): grid-side converter starts charging the DC capacitors, closes WORD
the main contactor and starts modulating.
Check the grid-side converter status. Note: Only the three least 05.10 ISU STATUS WORD
significant bits are relevant in this case.
231H (1000110001 bin) before the grid-side converter is started
737H (11100110111 bin) when the grid-side converter is running
238H (1000111000 bin) when the grid-side converter has tripped on a
fault.
Check that the Voltage and Current Measurement Unit NUIM-6x 01.05 NET FREQUENCY
functions, ie, the grid frequency is positive and the grid voltage is 01.11 MAINS VOLTAGE
correct.
Stop the grid-side converter by setting parameter 21.01 ISU LOCAL 21.01 ISU LOCAL CTR
CTR WORD to 0 (hex). WORD
Check the functioning of the crowbar by starting and stopping the 01.15 DI STATUS
grid-side converter. (Parameter 21.01 ISU LOCAL CTR WORD
setting 9 (hex) = START and 0 (hex) = STOP)
When DC voltage is 0 V, 01.15 DI STATUS bit 5 value must be 0
(ie, crowbar inactive). 01.15 DI STATUS = 1303 (hex)
When DC voltage exceeds 100 V, 01.15 DI STATUS bit 4 value must
be 1 (ie, crowbar active). 01.15 DI STATUS = 1713 (hex)
Enable the grid-side converter parameter lock by setting parameter 16.03 PASS CODE
16.03 PASS CODE to 2303. Parameter groups 100…202 become
visible when the parameter lock is enabled.
Set grid-side converter 16.01 PARAM LOCK to OFF. 16.01 PARAM LOCK
If the converter is NOT equipped with an active crowbar, continue to the next section.
Activate the active crowbar by setting rotor-side converter parameter 31.01 CROWBAR HW
31.01 CROWBAR HW TYPE according to the type of active crowbar TYPE
in use.
Note: If the converter is equipped with an active crowbar, it must
always be activated by parameter 31.01 even when low voltage ride
through (LVRT) and / or grid support is not used.
Start the grid-side converter by setting parameter 21.01 ISU LOCAL 21.01 ISU LOCAL CTR
CTR WORD to 9 (hex). WORD
Check the communication between the rotor-side converter and the 06.13 CB IGBT TEMP
active crowbar:
The communication is OK if the temperature of the crowbar is about
25…40 °C and the converter does not trip for crowbar communication
time-out.
60 Start-up with medium voltage stator
NUIM board in use (grid-side converter control program 01.11 MAINS VOLTAGE
IXXR72xx):
Check grid-side converter parameter 01.11 MAINS VOLTAGE value
(= mains voltage received from the rotor-side converter). If the
voltage level is correct, communication between rotor-side and grid-
side converters is OK.
Check grid-side converter mains voltage measurement phase See grid-side converter
sequence: parameter list:
Monitor the following grid-side converter signals with DriveWindow 16.03 PASS CODE
datalogger with 1 ms time level, when grid-side converter is started: 138.02 FLUX X NET ACT
NUIM board in use (grid-side converter control program 138.03 FLUX Y NET ACT
IXXR72xx):
161.04 FLUX X ACT
138.02 FLUX X NET ACT
138.03 FLUX Y NET ACT 161.05 FLUX Y ACT
161.04 FLUX X ACT
161.05 FLUX Y ACT
Start DriveWindow datalogger and trigger manually. Upload
datalogger information:
If parameter 138.02 FLUX X NET ACT and 161.04 FLUX X ACT
signals are in phase and parameter 138.03 FLUX Y NET ACT and
161.05 FLUX Y ACT signals are in phase, the flux measurement is
OK.
NAMU / BAMU board in use (grid-side converter control program 02.22 FLUX X NET ACT
IWXR74xx): 02.23 FLUX Y NET ACT
02.22 FLUX X NET ACT 02.20 FLUX X ACT
02.23 FLUX Y NET ACT
02.21 FLUX Y ACT
02.20 FLUX X ACT
02.21 FLUX Y ACT
Start DriveWindow datalogger and trigger manually. Upload
datalogger information:
If parameter 02.22 FLUX X NET ACT and 02.20 FLUX X ACT signals
are in phase and parameter 02.23 FLUX Y NET ACT and 02.21
FLUX Y ACT signals are in phase, the flux measurement is OK.
Note: If this test fails, grid-side converter grid voltage cabling must be
checked. See the converter hardware manual.
Stop the grid-side converter by setting parameter 21.01 ISU LOCAL 21.01 ISU LOCAL CTR
CTR WORD to 0. WORD
Check the grid-side converter parameters. See chapter ACS800-
67(LC) doubly-fed induction generator control program firmware
manual [3AUA0000071689 (English)].
Disable the main circuit breaker function by setting parameter 21.02 21.02 DISABLE MCB
DISABLE MCB CLOSE to YES (the rotor-side converter CLOSE
synchronizes to the grid but does not close the main circuit breaker).
Start the converter with zero speed with the DriveWindow START 06.11 CB BRIDGE
button. VOLTAGE
Check crowbar measurements after the DC link has been charged: 06.12 CB IGBT VOLTAGE
Measurements are OK, if parameter 06.11 CB BRIDGE VOLTAGE 06.13 CB IGBT TEMP
and 06.12 CB IGBT VOLTAGE values are higher than the DC link
voltage (01.10 DC VOLTAGE) and parameter 06.13 CB IGBT TEMP
value is approximately 25…40 °C.
The following figure shows the active crowbar voltages when manual triggering is used.
The figure depicts, the voltage with a 400 V unit. With a 690 V unit, the basic voltage level would be
approximately 1250 V.
Set the Low Voltage Ride Through function and Grid Support function Grid support function can
parameters. Values must be set according to the selected grid code. be tuned by parameters in
See ACS800-67(LC) doubly-fed induction generator control program group 32 LV RIDE-
firmware manual [3AUA0000071689 (English)]. THROUGH.
Check that the wind turbine rotates the rotor speed within acceptable 01.01 MOTOR SPEED
range (approximately 900...1100 rpm).
N ,
+*
O1POQ +*-?O1POQ +*O1POQ
+*A-CPQ +*A-CPQ +*-E11 P)(*Q
0607
064
0608
060
060
063
Enable the main circuit breaker function by setting parameter 21.02 21.02 DISABLE MCB
DISABLE MCB CLOSE to NO. Check that the main circuit breaker CLOSE
operates correctly.
Check the stator current measurement by giving a small torque 25.04 TORQUE REF A
(25.04 TORQUE REF A) reference, eg, 15%. The current 01.02 GENERATOR
measurement is correct if the actual torque value TORQUE
01.02 GENERATOR TORQUE follows the given reference.
Check wiring.
Close the damper (T100 power off) and connect the auxiliary
voltages.
• Check that A42: UAO2 = 0 V.
Set temporarily parameter 15.06 ANALOGUE OUTPUT 2 setting 112 15.06 ANALOGUE
to 1910. OUTPUT 2
Check that operation of the damper follows the graph shown below by writing values to parameter
1910 (this parameter imitates PP TEMP values):
• 1910< 18 damper closed
• 1910 > 18 damper starts to open, see the graph
• 1910 = 50 damper fully open, plate in 90° position.
AO2
U500ohm
Mech.
position
Position
feedback
PP TEMPERATURE
Close FF005.
Check that the air damper starts to open when the converter PP
TEMP starts to increase. You can monitor signals by means of
DriveWindow:
• 01.12 PP TEMPERATURE
• 15.06 ANALOGUE OUTPUT 2 (damper control)
• 05.07 ISU AI1 [V] (damper position is monitored via this signal).
Final settings
Disable the parameter lock by setting parameter 16.03 PASS CODE 16.03 PASS CODE
to 358 or 564 in rotor-side and grid-side converter.
Note: Not needed with grid-side converter control program
IWXR74xx.
Set the stator current fault trip limit to 0 A. 30.04 STATOR CURR
TRIP
Make special parameter settings (if any) according to eg, grid code.
See section Setting the parameters according to grid code on page
108.
Lock the parameter settings by setting parameter 16.01 PARAM 16.01 PARAM LOCK
LOCK to ON in rotor-side converter.
Note: Not needed with grid-side converter control program
IWXR74xx.
Starting sequence
The following figures present the starting sequences for the ABB drives profile and the
Profile B. (Profile is selected by parameter 16.11 COMM PROFILE.)
Terms and abbreviations used in the figures:
Term/Abbreviation Information
Grid connected
4 13
0
1 Stop sequence
2
3 RUN 7 10
MCW 7.01
4
5
6
7 RESET
8
9
3
0 RDYON
1 RDYRUN (ready) 6
2 RDYREF (operational) 9
3 TRIPPED
4
5
6
MSW 8.10
7 ALARM
8
9
11 MCB3 STATUS
12
13
14 TOGGLE BIT Time
15
Start-up with medium voltage stator 69
Profile B
ISU modulation 9 13 16
10
INU modulation
Syncr. to grid
Grid connection
Grid connected
15
0 1) 5
1 Stop sequence
2
3 RUN 4 12
MCW 7.01
4
5
6
7 RESET
8
9
0 RDYON
1 RDYRUN (ready) 3
2 RDYREF (operational) 11
3 TRIPPED
4
5
MSt W 8.10
6
7
8
9
11 MCB3 STATUS
12
13
14 TOGGLE Time
15
Actual speed
20.21 SWITCH ON SPEED
1)
Bit 0 is not used in this profile.
70 Start-up with medium voltage stator
Start-up measurements
The start-up measurements described in this section give useful information if a problem is
detected during the start-up. These measurements are not normally required during the
start-up procedure.
Phase U test
,
, - ( , -
,
,
/12345@
,
( D , -
(
/128457
D
Phase W test
06
06
100
80
60
40
0
0 1 2 3 4 5 6 7 8 9 10
-20
-40
-60
-100
1200 120
1.10 DC VOLTAGE [v]
1000 100
800 80
1.11 MAINS VOLTAGE [V]
600 60
200 20
1400
1.01 MOTOR SPEED [rpm]
1200
800
1.11 MAINS VOLTAGE [V]
600
-200
1. Grid-side converter is started and DC link charging begins. DC link voltage starts to
increase and auxiliary power is connected to the rotor-side converter. After these
actions, the converter signals can be monitored.
2. Grid-side converter charging is finished. Modulation of both converters starts. Stator
voltage increases near to the measured grid voltage.
3. DC voltage increases to its maximum if the rotor speed is near the lowest possible
start speed.
4. The converter software adjusts the stator voltage in order to minimise current
transients during grid connection.
5. Main circuit breaker is closed.
Start-up with medium voltage stator 75
50
0
0 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.1
-50
-100
06.01 STATOR IU [%]
06.08 STATOR Y FLUX [%] 06.04 ROTOR IY [%]
-150
150
Without load
06.01 STATOR IU [%] 06.05 ROTOR IU [%] 06.07 STATOR U FLUX [%]
100
50
0
0 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.1
-50
-100
06.02 STATOR IY [%]
06.04 ROTOR IY [%]
06.08 STATOR Y FLUX [%]
-150
76 Start-up with medium voltage stator
Practical examples 77
5
Practical examples
Torque set-point
Torque is limited by parameters 20.05 USER POS TORQ LIM and 20.06 USER NEG
TORQ LIM. The parameters should be set to values which are achievable with the
generator-drive current capacity combination defined in the design.
If the torque reference given by the turbine controller is too high (ie, the pull-out torque of
the generator or current capacity of the converter have been reached), the converter will
limit the torque.
In extreme cases, if the torque reference is remarkably higher than what is allowed by the
generator-drive current capacity combination, and the limitation of current by limiting
torque does not succeed, the converter will trip on overcurrent. It stops operation
immediately and the torque on the generator shaft disappears. Necessary overspeed and
safety system dynamics margins must be maintained in the system design.
Practical examples 79
shown below. In this example the parameter 16.20 GRID CONNECT MODE is set to
MCB1+MCB3/B.
P1,K P2,L
L1 L1 U2 U1
S1,k S2,l
L2 MCB1 L2 V2 MCB3 V1
P1,K P2,L
L3 L3 W2 W1
S1,k S2,l
Optional
X2:1
X2:2
X1:1
X1:2
NUIM NDCU
V1
W1
U1
L1
L2
L3
L U2 K
MCB2 C
L
ISU INU V2 L DFIG
W2 M
The maximum measurable stator current must be set by a parameter. The value is
calculated with the following equation:
4,5 V
99.28 MAX MEAS IS = ----------------------------------- ⋅ CT
2,73333 ohm
Generator data
Generator rating plate equivalent circuit parameters
The equivalent circuit of the generator is shown below. Note that the equivalent circuit is to
be are derived looking from the stator-side ie, the voltages and currents are reflected on
the stator-side. To calculate the equivalent rotor circuit parameters (resistance and
inductance) from the rotor-side to stator-side, appropriate stator-to-rotor conversion ratio
information should be used.
j s Ȍ ss Ȍ ms -j r Ȍ rs
Uss Lms Urs
Ȍ ss Ȍ rs
Since the application measures both rotor- and stator-side quantities, the identification run
method is not used with doubly-fed induction generator control. The control needs to be
given the following data (from the generator data sheet) manually.
Generator data Parameter
Rated stator voltage 99.02 MOTOR NOM VOLTAGE
Rated stator current 99.03 MOTOR NOM CURRENT
Rated stator frequency 99.04 MOTOR NOM FREQ
Rated generator nominal speed 99.05 MOTOR NOM SPEED
(rotor short-circuited) Note: As generator, positive slip.
Rated generator power 99.06 MOTOR NOM POWER
Note: See the calculations below.
P.F (rotor short-circuited) 99.12 MOTOR NOM COSFII
Generator synchronous speed 99.14 MOTOR SYNC SPEED
82 Practical examples
Note: Some generator manufacturers give equivalent circuit data for delta connection. In
that case the given reactance values must be divided by three.
Practical examples 83
99.15 MOTOR OPEN Defines the open-circuit Locked rotor voltage Transformation ratio
CKT V voltage of the rotor. That in data sheet. between the stator and the
is, rotor voltage without rotor. Defined when rotor
load when nominal voltage shaft is mechanically
is connected to the stator locked and nominal stator
and the rotor is locked (U2 voltage is fed to the stator
on the generator data windings.
sheet).
99.16 MOTOR NOM Defines the maximum limit The limit for rotor current The maximum limit of the
IM of the rotor current to avoid protection. rotor current defined by the
generator overheating. Select from the data sheet generator supplier.
If the rotor current exceeds • largest rotor current in
the value of parameter the calculated operation
99.16, the capacitive points, or
reactive power is ramped
• maximum rotor current
down until the current has
decreased below the value
of the parameter 99.16.
99.21 Rs Defines the stator Stator resistance (Rs) of DFIG characteristics value
resistance. equivalent circuit
99.22 X1S Defines the stator leakage Stator leakage reactance DFIG characteristics value
reactance. of equivalent circuit
99.23 X2S Defines the rotor leakage Rotor leakage reactance DFIG characteristics value
reactance reduced to the of equivalent circuit
stator side.
84 Practical examples
Example:
Nominal operating point: Wind turbine nominal power is 1600 kW, wind turbine nominal
speed is 1770 rpm and generator nominal speed is 1511 rpm.
With 100% torque reference at 1770 rpm, the wind turbine output is 1600 kW, when
parameter 99.06 MOTOR NOM POWER value is
99.06 MOTOR NOM POWER = (1511 rpm · 1600 kW) / 1770 rpm = 1365 kW.
Note: If the equivalent circuit values are given for delta connection, the values for
parameters 99.21 Rs, 99.22 X1S, 99.23 X2S, 99.24 XM and 99.25 Rr must be divided by
three.
X2 ı ’ and R2’ must be reduced to the stator reference frame. Reducing is marked with ‘
and it is calculated as shown below.
X2 ı
99.23 X2S =
99.15 MOTOR OPEN CKT V 2
R2
99.25 Rr =
99.15 MOTOR OPEN CKT V 2
If only generator rating plate values are known, such rating plate values are needed that
are given when rotor is short-circuited. Power factor must be below 1. First magnetizing
current of the generator is calculated as shown below:
99.16 MOTOR NOM IM = 99.03 MOTOR NOM CURRENT· 1 - 99.12 MOTOR NOM COSFII2
The rotor resistance Rr (rotor-side converter parameter 99.25 Rr) reduced to the stator
reference frame (R2PH on the ABB generator equivalent circuit data) is calculated with the
following equation:
R2PH
99.25 Rr =
99.15 MOTOR OPEN CKT V 2
X1S and X2S are typically about 5% of the Xm. Rs and Rr are typically about 0.5% of the
Xm.
Practical examples 87
Electrical
power
network
Example
ABB wind turbine generator 3.05 MW, stator voltage 12 kV, 60 Hz
Generator type code AML 630L6A BAFT
Generator type Slip ring generator
Mounting designation IM 1001
Protected by enclosure/slip ring unit IP 54/23
Method of cooling IC 616
Insulation Class F
Standards IEC
Ambient temperature -20 °C…+50 °C
-30 °C…+50 °C
Altitude, max. 1000 m.a.s.l.
Doubly-fed operation
Duty type S1
Temp. rise F (RES)
Connection of stator winding Star
Rated output 3050 kW
Par. 99.12 Rated power factor 1.0
Par. 99.02 Voltage 12 kV
Par. 99.04 Frequency 60 Hz
Speed 1320 rpm
Par. 99.03 Stator current 134 A
Par. 99.15 Open circuit voltage 1722 V
Rotor voltage 177 V
Rotor current 989 A
Efficiency at rated load with fan 96.1%
Connection of rotor winding Star
Rotor resistance/phase 0.0035 ohm
Rotor short-circuited
Rated torque -22753 N·m
Par. 99.06 Load characteristics as induction machine Load % Current A Efficiency % Power factor
(2770 kW) 100 156 96.4 0.86
75 120 96.4 0.83
50 87 95.9 0.77
Direction of rotation Uni-directional
Weight of rotor Approximately 5900 kg
Total weight of generator 13470 kg
Inertia rotor / load Approximately 400 kgm2
Bearings Antifriction
Practical examples 89
X1 R1 X2’ R2’ / s
UN / 3 RFe Xm
* Par. 99.16
However, if higher current is needed to use for a short period (defined by the supplier of
the generator), a higher limit can be used. The PLC must supervise the temperatures of
the generator and avoid overheating it.
90 Practical examples
Transient loading points (load cycle transient time / 60 min) refer to specification PDC0198
(revision G, chapter 7.3, page 12).
U [V] F [Hz] N [rpm] P [kW] p.f. Ir [A] Ur [V] Tran. time Max. amb.
11760 60 1260 3380 1 1157 83 10 min 50 °C
12000 60 1260 3380 1 1138 85 10 min 50 °C
12240 60 1260 3380 1 1119 86 10 min 50 °C
11760 60 1320 3545 1 1158 174 10 min 50 °C
12000 60 1320 3545 1 1139 178 10 min 50 °C
12240 60 1320 3545 1 1120 181 10 min 50 °C
11760 60 1380 3875 1 1207 266 10 min 50 °C
12000 60 1380 3875 1 1187 271 10 min 50 °C
12240 60 1380 3875 1 1167 277 10 min 50 °C
Starting sequence
See section Starting sequence on page 67.
Practical examples 91
crowbar triggered
MCB internal trip
torque reduction
ISU RDYREF
OFF 2 N STA
MCB ON
RESET
remote
tripped
rdyrun
rdyref
rdyon
alarm
RUN
ON
-
b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0 b7 b3 b0
1 RUN=1 Device is running. 1 0 1 0 1 0 0 0 0 1 0 1 1 1 0 1 0
2 Device is tripped for any reason, 0 0 0 0 1 0 0 0 0 1 1 0 0 0 0 1 0
stator is immediately
disconnected from the grid and
after that ISU is disconnected
from the grid.
3 RUN=0 Run command must be 0 0 0 0 1 0 0 0 0 1 1 0 0 0 0 0 0
removed.
4 RESET=1 Fault is reseted. 0 0 0 0 1 0 0 0 0 1 0 0 0 1 1 0 0
5 RESET=0 RESET command must be 0 0 0
removed.
crowbar triggered
MCB internal trip
torque reduction
ISU RDYREF
OFF 2 N STA
MCB ON
RESET
remote
tripped
rdyrun
rdyref
rdyon
alarm
RUN
ON
-
4 13
0
1 Stop sequence
2
3 RUN 7 10
MCW 7.01
4
5
6
7 RESET
8
9
3
0 RDYON
1 RDYRUN (ready) 6
2 RDYREF (operational) 9
3 TRIPPED
4
5
6
MSW 8.10
7 ALARM
8
9
11 MCB ON
12
13
14 TOGGLE BIT Time
15
Practical examples 93
crowbar triggered
MCB internal trip
torque reduction
ISU RDYREF
OFF 2 N STA
MCB ON
RESET
remote
tripped
rdyrun
rdyref
rdyon
alarm
RUN
ON
-
b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0 b7 b3 b0
1 RUN, ON Device is at a standstill, no fault. 0 0 0 0 1 0 0 0 0 1 0 0 0 1 0 0 0
=0
2 ON=1 DC bus is charged, ISU 1 0 0 0 1 0 0 0 0 1 0 0 0 1 0 0 1
contactor is closed and ISU
modulation is started.
When speed is above SWITCH- 1 0 0 0 1 0 0 0 0 1 0 0 1 1 0 0 1
ON speed.
3 RUN=1 INU is started, synchronised to 1 0 1 0 1 0 0 0 0 1 0 1 1 1 0 1 1
the grid and stator is connected
to the grid.
4 RUN=0 Stator current is controlled to 1 0 0 0 1 0 0 0 0 1 0 0 1 1 0 0 0
zero, stator is disconnected from
the grid and INU modulation is
stopped.
5 ON=0 ISU modulation is stopped, ISU 0 0 0 0 1 0 0 0 0 1 0 0 1 1 0 0 0
contactor is opened and DC bus
is discharged.
6 When speed is below SWITCH- 0 0 0 0 1 0 0 0 0 1 0 0 0 1 0 0 0
OFF speed.
Datasets
The datasets used for transmitting and receiving actual signals and parameters are shown
in ACS800-67(LC) doubly-fed induction generator control program firmware manual
[3AUA0000071689 (English)].
Fieldbus signals
For signals used in the software interface with a specific fieldbus, refer to the software
interface specification delivered with the converter.
94 Practical examples
7. Go to the Network tab and check that the Connected to Tool Channel (Ch3) is
selected.
8. If the converter has only one rotor-side converter and one grid-side converter, select
network type Ring.
9. Save settings by clicking OK and rebooting the module.
96 Practical examples
5 6
Backup Package
A Backup Package is similar to a Loading Package. It is a single PC file with a filename
extension of .BPG.
A Backup Package can be opened, saved, saved with a new name and closed. Backup
and restore commands can be performed only if a Backup Package is open.
98 Practical examples
2
1
4 5
7
100 Practical examples
Note: If the converter is running while the parameter file is saved, it will not be possible to
edit the parameters off-line. The parameter file remains in the read-only status. Therefore,
create always a full Backup Package for backup purposes. See section Creating a full
Backup Package and saving it in .BPG format on page 96.
Practical examples 101
1 3
Contact ABB
102 Practical examples
97.01 DEVICE NAME INU 800 xxxx_7LC Use the correct converter type
In addition, the fieldbus module settings must be made. See the ACS800-67(LC) doubly-
fed induction generator control program firmware manual [3AUA0000071689 (English)].
104 Practical examples
Grid-side converter
No. Name Factory setting
Power cabinet
Encoder
106 Practical examples
Power cabinet
Encoder
Practical examples 107
Parameter Setting
32.35 PRIORITY t<t4 Iq > Ip
32.36 PRIORITY t>t4 Iq > Power
32.37 P/Q UNSYM DIS 62%
32.38 P/Q UNSYM ENA 60%
32.41 ENVELOPE PAR SEL PAR 2
32.66 RT OF LEVEL1 51.5
32.67 RT OFTIME1 1.5
32.68 RT OF LEVEL2 51.5
32.69 RT OF TIME2 1.5
32.70 RT OF LEVEL3 51.5
32.71 RT OF TIME3 1.5
32.72 RT OF LEVEL4 51.5
32.73 RT OF TIME4 1.5
32.74 RT OF LEVEL5 51.5
32.75 RT UF LEVEL1 47.5
32.76 RT UFTIME1 4.5
32.77 RT UF LEVEL2 47.5
32.78 RT UF TIME2 4.5
32.79 RT UF LEVEL3 47.5
32.80 RT UF TIME3 4.5
32.81 RT UF LEVEL4 47.5
32.82 RT UF TIME4 4.5
32.84 RT UF LEVEL5 47.5
146.15 UC TRQREF OFF LVL 1250 V 1200V
146.16 MAX AUTO-RESTART 25 25
146.20 CB OV TRIP LEVEL 0 V 0
Practical examples 111
UK grid code
Parameter Setting
Control program AJXC2330 (or newer) parameters:
30.03 EARTH FAULT LEVEL 3
30.04 STATOR CURR TRIP 0A
30.05 AC OVERVOLT TRIP 793.5 V
30.06 AC UNDERVOLT TRIP 0V
30.07 AC OVERFREQ TRIP 53 Hz
30.08 AC UNDERFREQ TRIP 47 Hz
32.01 GRID SUPPORT MODE MAX. Up-p
32.02 RT MONITOR SIGNAL MIN. Up-p
32.03 RT U/Un LEVEL1 90%
32.04 RT U/Un LEVEL2 15%
32.05 RT U/Un LEVEL 3 80%
32.06 RT U/Un DELTA t1 1200 ms
32.07 RT U/Un DELTA t2 140 ms
32.08 RT U/Un DELTA t3 2500 ms
32.09 RT U/Un DELTA t4 140 ms
32.10 RT U/Un LEVELHYST 5%
32.11 GS U/Un LEVEL 1 90%
32.12 GS U/Un LEVEL 2 80%
32.13 GS U/Un LEVEL 3 25%
32.14 GS U/Un LEVEL 4 15%
32.15 GS U/Un LEVEL 5 110%
32.16 GS U/Un LEVEL 6 120%
32.17 GS IQREF LEVEL 1 0%
32.18 GS IQREF LEVEL 2 112%
32.19 GS IQREF LEVEL 3 112%
32.20 GS IQREF LEVEL 4 112%
32.21 GS IQREF LEVEL 5 -20%
32.22 GS IQREF LEVEL 6 -40%
32.23 GS AFTER DIP 0%
32.24 GS TIME AFTER DIP 0 ms
32.25 KVAR RISE TIME 50 ms
32.26 TORQUE RISE TIME 49.9988 ms
32.27 Imax/In (LVRT) 124%
32.28 TMIN/TN (LVRT) 0.999975%
32.29 Ip max/In (LVRT) 118%
32.30 IR MAX PEAK LEVEL 1777.68 A
32.31 IR MAXSLOPE SCALE 507.903 A
32.32 U- / U+ START DIS 80%
32.33 U(RMS) START DIS 9.99999%
32.34 RT U/Un DELTA t5 180 s
32.35 PRIORITY t<t4 Iq > Ip
32.36 PRIORITY t>t4 Ip > Iq
32.37 P/Q UNSYM DIS 62%
112 Practical examples
Parameter Setting
32.38 P/Q UNSYM ENA 60%
Control program IWXR7300 (or newer) parameters:
40.01 RT ENABLE ON
40.02 NAMU BOARD ENABLE ON
40.04 PHASE MEAS ENA ON
40.05 UAC CTRL SEL RMS VOLTAGE
40.09 RT U/Un MOD STOP 9.99999%
40.10 RT U/Un LEVEL1 90%
40.11 RT U/Un LEVEL2 0%
40.12 RT U/Un LEVEL3 70%
40.13 RT U/Un DELTA t1 3000 ms
40.14 RT U/Un DELTA t2 600 ms
40.15 RT U/Un DELTA t3 20000 ms
40.20 TRP VOLT PEAK 130%
40.21 TRP VOLT LEV 120%
40.22 TRP VOLT TIME 20 ms
40.23 TRP VOLT SEL RMS VOLTAGE
41.01 GRID SUPPORT MODE OFF
41.02 GS HIGHEST U ENA ON
41.03 GS U/Un LEVEL 1 100%
41.04 GS U/Un LEVEL 2 50%
41.05 GS U/Un LEVEL 3 25%
41.06 GS U/Un LEVEL 4 15%
41.07 GS IQREF LEVEL 1 0%
41.08 GS IQREF LEVEL 2 100%
41.09 GS IQREF LEVEL 3 100%
41.10 GS IQREF LEVEL 4 100%
Tracing the source of warnings, limits and faults 113
6
Tracing the source of warnings,
limits and faults
Warnings
Abnormal statuses are indicated by the warning words and messages.
Limits
The converter control programs limit, for example, current, torque, power, speed and
overvoltage. The performance of the limiters can be controlled by parameters.
Torque limit
The converter calculates shaft torque every 25 microsecond.
Torque is typically limited when
• the limit defined by parameter 20.05 USER POS TORQ LIM is met
• some factor in the torque reference chain requires it.
Power limit
Parameters 20.17 P MOTORING LIM and 20.18 P GENERATING LIM define the
maximum allowed power flows.
114 Tracing the source of warnings, limits and faults
Faults
The converter protects itself with many functions. When a protection function is activated,
the converter is immediately stopped (tripped) to avoid damages. A fault does not
necessary mean that there is any material failure in the converter.
Monitor the following grid-side converter signals with DriveWindow Datalogger at 1 ms intervals:
If signals 138.02 FLUX X NET ACT and 161.04 FLUX X ACT are in phase and signals 138.03 FLUX
Y NET ACT and 161.04 FLUX Y ACT are in phase, the measurement phase sequence is OK.
Note: If the signals are not in phase, check the grid voltage measurement cabling of the grid-side
converter measuring unit and correct the phase sequence. See the converter hardware manual.
116 Tracing the source of warnings, limits and faults
Monitor the following grid-side converter signals with DriveWindow Datalogger at 1 ms intervals:
If signals 02.22 FLUX X NET ACT and 02.20 FLUX X ACT are in phase and signals 02.23 FLUX Y
NET ACT and 02.21 FLUX Y ACT are in phase, the measurement phase sequence is OK.
Note: If the signals are not in phase, check the grid voltage measurement cabling of the grid-side
converter NAMU / BAMU board and correct the phase sequence. See the converter hardware
manual.
Tracing the source of warnings, limits and faults 117
Faults in measurements
Fault Cause What to do
Pulse encoder pulses or zero Generator overcurrent If the encoder is of unisolated type, check that the
pulse are missing or wrong fault cable is grounded only on converter side.
Speed / position / In case of wrong encoder direction, check the
RTAC module fault pulse encoder phasing (A/B channels).
Check the type and connection of the encoder;
differential encoder is recommended.
Current value is wrong. Faulty current Check the current transformer.
Torque actual value does not transformer inside Check the values in parameter group 99.
correspond to the reference power module
value. Wrong values in
There is reactive power without parameter group 99 in
reference. the rotor-side converter
control program
Torque oscillates and
overcurrent fault occurs.
Current imbalance fault
Earth fault
118 Tracing the source of warnings, limits and faults
Further information
Product and service inquiries
Address any inquiries about the product to your local ABB representative, quoting the type
designation and serial number of the unit in question. A listing of ABB sales, support and
service contacts can be found by navigating to www.abb.com/searchchannels.
Product training
For information on ABB product training, navigate to new.abb.com/service/training.
www.abb.com/windconverters