Protection Relays

Voltage Monitoring Relays

460-XXX-SP SERIES
Single-phase voltage monitor

Description
The 460-100-SP is used on 95–120 V ac, 50*/60 Hz single-phase
motors and the 460-200-SP is used on 190–240 V ac, 50*/60 Hz
single-phase motors to protect them from damaging high and
low voltage conditions. An adjustment knob allows the user to
set a 1–500 second restart delay. The variable restart delay is
also a power-up delay and can be utilized to stagger-start motors
on the same system.
A unique microcontroller-based, voltage-sensing circuit
constantly monitors the voltage to detect harmful power
line conditions. When a harmful condition is detected, the
MotorSaver’s output relay is deactivated after a specified trip
delay. The output relay reactivates after power line conditions
return to an acceptable level and a specified amount of time has
elapsed (restart delay). The trip delay prevents nuisance tripping
due to rapidly fluctuating power line conditions.

Features & Benefits


FEATURES BENEFITS
Proprietary Constant monitoring of voltage to detect harmful
Wiring Diagram microcontroller
based circuitry power line conditions, even before a motor starts

Fixed trip delay 4 s Prevents nuisance tripping due to rapidly fluctuating


power line conditions
Adjustable restart Allows staggered start up of multiple motors on the
delay (1–500s) same system to prevent a low voltage condition

Advanced LED indication Provides diagnostics which can be used for


troubleshooting and to determine relay status
DIN rail or surface Allows flexibility for panel assembly
mountable

Ordering Information
MODEL LINE VOTAGE

460-100-SP 95–120 V ac

460-200-SP 190–240 V ac

© 2020 Littelfuse, Inc. Rev: 2-A-061220


1-A-062716
www.littelfuse.com/
www.littelfuse.com/460xxxsp
Protection Relays
Voltage Monitoring Relays

460-XXX-SP SERIES

Specifications Standards Passed


Electrostatic Discharge (ESD) IEC 61000-4-2, Level 3, 6 kV contact, 8 kV air
Input Characteristics
Radio Frequency Immunity,
Line Voltage
Radiated 150 MHz, 10 V/m
460-100-SP 95–120 V ac
Fast Transient Burst IEC 61000-4-4, Level 3, 3.5 kV input power
460-200-SP 190–240 V ac
and controls
Frequency 50*/60 Hz
Surge
Functional Characteristics
IEC IEC 61000-4-5, Level 3, 4 kV line-to-line;
Low Voltage (% of setpoint):
Level 4, 4 kV line-to-ground
Trip 90 % ±1 %
ANSI/IEEE C62.41 Surge and Ring Wave Compliance to a
Reset 93 % ±1 %
level of 6 kV line-to-line
High Voltage (% of setpoint)
Hi-potential Test Meets UL 508 (2 x rated V +1000 V for 1 min)
Trip 110 % ±1 %
Safety Marks
Reset 107 % ±1 %
UL UL 508 (File #E68520)
Trip Delay Time
Enclosure Polycarbonate
Low or High Voltage 4 seconds fixed
Dimensions H 88.9 mm (3.5”); W 52.93 mm (2.084”);
Restart Delay Time
D 59.69 mm (2.35”)
After a Fault 1–500 seconds adjustable
Weight 0.9 lb. (14.4 oz., 408.23 g)
After a Complete Power Loss 1–500 seconds adjustable
Mounting Method 35 mm DIN rail or Surface Mount
Output Characteristics
(#6 or #8 screws)
Output Contact Rating
(1 Form C)
*Note: 50 Hz will increase all delay timers by 20 %
Pilot Duty 480 VA @ 240 V ac, B300
General Purpose 10 A @ 240 V ac
General Characteristics
Ambient Temperature Range
Operating -40° to 70°C (-40° to 158°F)
Storage -40° to 80°C (-40° to 176°F)
Maximum Input Power 6W
Class of Protection IP20, NEMA 1 (finger safe)
Relative Humidity 10–95%, non-condensing per IEC 68-2-3
Terminal Torque 4.5 in.-lbs.
Wire Type Stranded or solid 12–20 AWG, one per terminal