Protastructure Design Guide Loading Generator
Protastructure Design Guide Loading Generator
Protastructure Design Guide Loading Generator
Loading Generator
Version 1.0 5 October 2020
asiasupport@protasoftware.com
globalsupport@protasoftware.com
Page - 2
Limitation of Prota shall not be held responsible for any losses caused by
Responsibilities documentation, software or usage errors.
Table of Contents
Scope ....................................................................................................................................................... 4
Dead and Live Load Cases .................................................................................................................... 4
Roof Live Load Cases............................................................................................................................ 4
Construction Stages Load Cases .......................................................................................................... 5
Seismic Loading ................................................................................................................................... 5
Wind Loading ....................................................................................................................................... 5
Minimum Horizontal Loading .............................................................................................................. 6
Soil Pressure ........................................................................................................................................ 6
Loading Combinations According to Design and Seismic Codes .......................................................... 7
Scope
ProtaStructure can automatically generate the load combinations as required by different design codes.
To generate load combinations automatically use the Loading Generator under Analysis > Building
Analysis > Load Combinations. This document explains the different options in the loading generator.
Pattern live loads are optional. By default, only odd and even loaded span pattern is used. You can
optionally check the other three patterns and include in the combinations.
Separate pattern load cases are generated for each orthogonal direction if “Direction Dependent
Pattern Loading” is checked.
By checking these options, you can define individual load cases for "Roof Live Load (Qr, Lr in ASCE-based
specifications)", "Snow Load (S)" and / or "Rain Load (R)" instead of "Live Load State (Q)" to roof level
slabs and elements (such as roof cladding, purlin, beam.). For example, if you check the Roof and Snow
Load fields, a different set of combinations (in the form of Qr or S or R) will be generated for each of
these load cases. Even if you assign loads for all of them, these three load cases will not be automatically
considered in the same combination simulatenously. However, you are free to consider these at the
same time by editing any combination.
Page - 5
In some codes (eg Eurocode) these load cases are applied with different coefficients (as Qr and S or Qr
and R). No codes apply snow and rain loads together.
If you define a load in the "Live Load (Q)" field together with "Roof Live Load (Qr)" for a member at roof
level, both of these loads will be applied together. Therefore, a load should not be defined in the "Q"
field for such elements, unless specifically preferred.
Seismic Loading
Four load cases (Ex +, Ex-, Ey +, Ey-) including positive and negative eccentricities are defined for
earthquake loads calculated in accordance with the selected earthquake codes. The "+" and "-" signs in
the load case labels indicate the side of the eccentricity with respect to floor mass center. (i.e. rotating
the floor CW or CCW)
All seismic codes require to include and additional combination, 0.9G + E, that may yield more critical
results where G acts favorably. You can optionally include this in loading generator.
Wind Loading
Generally, two load cases are sufficient for the wind loads for standard buildings where windward and
leeward facades are similar. Load combinations are automatically created separately for the positive
and negative directions.
However, it is necessary to use different load cases in positive and negative directions to define the wind
load, especially for the buildings with different windward and leeward facade areas, the cladding and
purlins on the sloping roofs of steel structures, and the girts on their surfaces. For this purpose, you can
define 4 load cases by using the "Define Different Negative Load States" option.
Page - 6
In the ASCE-based wind loading definition, 4 load cases (Wx, Wmx, Wy, Wmy) are generated by default
since the torsion moment is calculated for each direction. If you use the "Define Different Negative Load
Cases" option, you can use 8 load cases by creating separate load cases for the negative directions.
Soil Pressure
You can check the “Soil Pressure” load cases to describe the soil pressure effects. (For example, span
loads applied to the basement shearwalls, or storey loads defined by storey loads editor)
In case the soil pressure is unilateral, it is sufficient to define one or two load cases. By checking the
option for relevant direction, you can create soil pressure load cases and associated combinations.
Design codes suggest different combination coefficients for the soil load cases for situations where the
soil pressure is applied favorably or unfavorably with other horizontal loads. In this case, you must
specify the direction in which the load is applied. For example, if "negative" is selected for the direction
of 1, the soil load coefficient will be "0.9" in the earthquake loading in the positive direction, and "1.6"
in the earthquake loading in the same negative direction.
However, if you want to define different positive and negative load cases in both directions, you can
check the "Define Different Negative Load States" option to create 4 load states (Hx, H-x, Hy, H-y).
Page - 7
TS500, TBDY2018
Prime G Q Qr, R, S W E H
Effect
G G N/A
G+Q Q 1.4 1.6 1.6 1.6
G+Q+(Qr, R, S) R N/A
G+(Qr, R, S)+W R N/A
G+W W 1 1 1 1.3
G+W W 0.9 1.3
G+L+E+Ev+S E 1 1 0.2S 1
G+E+Ev E 0.9 1 1
Page - 8
Eurocodes
ProtaStructure supports Equation 6.10 for strength design combinations (STR) and Equation 9.10 for
seismic combinations.
ψ0 ψ1 ψ2
Office Areas, 0.7 0.5 0.3
Accessible Roofs, 0.7 0.5 0.3
Snow (H>1000 m), 0.7 0.5 0.2
Snow (H<1000 m), 0.5 0.2 0
Wind, 0.6 0.2 0
Page - 9
ɣG 1.35 Unfavorable
ɣG 1.1 Favorable
ɣQ 1.5 Unfavorable
ɣQ 0 Favorable
Accompan
Leading
ying
Variable G Q QRoof S Rain W N E H
Variable
Effect
Effect
G
G+Q Q 1.35 1.5 1.5 1 1.35
G+Q+S Q S 1.35 1.5 1.5 1.05 1 1.35
G+S+Q S Q 1.35 1.05 1.05 1.5 1 1.35
G+Q+R Q R 1.35 1.5 1.5 1.05 1 1.35
G+R+Q R Q 1.35 1.05 1.05 1.5 1 1.35
G+Q+S+W Q S, W 1.35 1.5 1.5 1.05 0.9 1 1.35 - 1
G+S+Q+W S Q, W 1.35 1.05 1.05 1.5 0.9 1 1.35 - 1
G+W+Q+S W Q, S 1.35 1.05 1.05 1.05 1.5 1 1.35 - 1
G+Q+R+W Q R, W 1.35 1.5 1.5 1.05 0.9 1 1.35 - 1
G+R+Q+W R Q, W 1.35 1.05 1.05 1.5 0.9 1 1.35 - 1
G+W+Q+R W Q, R 1.35 1.05 1.05 1.05 1.5 1 1.35 - 1
G+W (G W
1.1 1.5 1 1.35 - 1
favorable) (unfavorable)
G+E+Q+S E Q, S 1 0.3 0.3 0.2 1 1
G+E+Q+R E Q, R 1 0.3 0.3 0.2 1 1
Page - 10
Thank You…
Thank you for choosing the ProtaStructure Suite product family.
It is our top priority to make your experience excellent with our software technology solutions.
Should you have any technical support requests or questions, please do not hesitate to contact us at all
times through globalsupport@protasoftware.com and asiasupport@protasoftware.com
Our dedicated online support center together with our responsive technical support team is available
to help you get the most out of Prota’s technology solutions.