SINAMICS V90PN

Position Control with


HSP in S7-1500
Siemens
SINAMICS V90PN / HSP / TIA V15.1 Industry
Online
https://support.industry.siemens.com/cs/ww/en/view/109739053 Support
Legal information

Legal information
Use of application examples
Application examples illustrate the solution of automation tasks through an interaction of several
components in the form of text, graphics and/or software modules. The application examples are
a free service by Siemens AG and/or a subsidiary of Siemens AG ("Siemens"). They are
non-binding and make no claim to completeness or functionality regarding configuration and
equipment. The application examples merely offer help with typical tasks; they do not constitute
customer-specific solutions. You yourself are responsible for the proper and safe operation of the
products in accordance with applicable regulations and must also check the function of the
respective application example and customize it for your system.
Siemens grants you the non-exclusive, non-sub licensable and non-transferable right to have the
application examples used by technically trained personnel. Any change to the application
examples is your responsibility. Sharing the application examples with third parties or copying the
application examples or excerpts thereof is permitted only in combination with your own products.
The application examples are not required to undergo the customary tests and quality inspections
of a chargeable product; they may have functional and performance defects as well as errors. It is
your responsibility to use them in such a manner that any malfunctions that may occur do not
result in property damage or injury to persons.

Disclaimer of liability
Siemens shall not assume any liability, for any legal reason whatsoever, including, without
limitation, liability for the usability, availability, completeness and freedom from defects of the
application examples as well as for related information, configuration and performance data and
any damage caused thereby. This shall not apply in cases of mandatory liability, for example
under the German Product Liability Act, or in cases of intent, gross negligence, or culpable loss of
life, bodily injury or damage to health, non-compliance with a guarantee, fraudulent
non-disclosure of a defect, or culpable breach of material contractual obligations. Claims for
damages arising from a breach of material contractual obligations shall however be limited to the
© Siemens AG 2020 All rights reserved

foreseeable damage typical of the type of agreement, unless liability arises from intent or gross
negligence or is based on loss of life, bodily injury or damage to health. The foregoing provisions
do not imply any change in the burden of proof to your detriment. You shall indemnify Siemens
against existing or future claims of third parties in this connection except where Siemens is
mandatorily liable.
By using the application examples you acknowledge that Siemens cannot be held liable for any
damage beyond the liability provisions described.

Other information
Siemens reserves the right to make changes to the application examples at any time without
notice. In case of discrepancies between the suggestions in the application examples and other
Siemens publications such as catalogs, the content of the other documentation shall have
precedence.
The Siemens terms of use (https://support.industry.siemens.com) shall also apply.

Security information
Siemens provides products and solutions with Industrial Security functions that support the secure
operation of plants, systems, machines and networks.
In order to protect plants, systems, machines and networks against cyber threats, it is necessary
to implement – and continuously maintain – a holistic, state-of-the-art industrial security concept.
Siemens’ products and solutions constitute one element of such a concept.
Customers are responsible for preventing unauthorized access to their plants, systems, machines
and networks. Such systems, machines and components should only be connected to an
enterprise network or the Internet if and to the extent such a connection is necessary and only
when appropriate security measures (e.g. firewalls and/or network segmentation) are in place.
For additional information on industrial security measures that may be implemented, please visit
https://www.siemens.com/industrialsecurity.
Siemens’ products and solutions undergo continuous development to make them more secure.
Siemens strongly recommends that product updates are applied as soon as they are available
and that the latest product versions are used. Use of product versions that are no longer
supported, and failure to apply the latest updates may increase customer’s exposure to cyber
threats.
To stay informed about product updates, subscribe to the Siemens Industrial Security RSS Feed
at: https://www.siemens.com/industrialsecurity.

SINAMICS V90 PN Position Control with HSP in S7-1500


Entry-ID: 109739053, V1.3, 01/2020 2
Table of contents

Table of contents
Legal information ......................................................................................................... 2
1 Introduction ........................................................................................................ 4
2 Solution............................................................................................................... 5
2.1 Solution overview ................................................................................. 5
2.2 Hardware and Software Components .................................................. 6
2.2.1 Validity .................................................................................................. 6
2.2.2 Used Components ................................................................................ 6
3 Basics ................................................................................................................. 7
3.1 Basics regarding SINAMICS V90 PN HSP (Hardware Support
Package) .............................................................................................. 7
3.2 Installation and startup ......................................................................... 8
3.2.1 Hardware installation ............................................................................ 8
3.2.2 Trial-run for V90 PN and 1FL6 motor ................................................... 8
3.3 Install V90 PN HSP in TIA Portal ......................................................... 9
4 Configuration ................................................................................................... 12
4.1 Introduction of the V90PN HSP in TIA portal V15.1 ........................... 12
4.1.1 Add the SINAMICS V90 PN via HSP and start with the
configuration ....................................................................................... 12
4.1.2 Parameters change and download .................................................... 16
© Siemens AG 2020 All rights reserved

4.1.3 Online commissioning and optimization ............................................. 18


4.1.4 Trace function introduction ................................................................. 21
4.1.5 Other related function introduction ..................................................... 24
4.2 Configure PROFINET settings via the TIA Portal .............................. 27
4.2.1 Add S7-1500 into the project .............................................................. 27
4.2.2 Device configuration of the S7-1500 CPU ......................................... 30
Device name and Ethernet address configuration via TIA Portal ...... 30
4.2.3 Connect V90 PN with S7-1500 .......................................................... 32
5 Operation of the application ........................................................................... 33
6 Optional - Basic parameter configuration regarding SINAMICS V90
with V-Assistant ............................................................................................... 41
7 Appendix .......................................................................................................... 43
7.1 Service and support ........................................................................... 43
7.2 Application support ............................................................................. 44
7.3 Links and literature ............................................................................. 44
7.4 Change documentation ...................................................................... 44

SINAMICS V90 PN Position Control with HSP in S7-1500


Entry-ID: 109739053, V1.3, 01/2020 3
1 Introduction

1 Introduction
Introduction
In this manual, the basic application of position control with the TIA-Portal element
V90 “HSP” → Hardware Support Package → of SINAMICS V90 PN will be
described in detail.
The described solution in this document contains SINAMICS V90 HSP in
combination with the necessary commissioning of a SIMATIC S7-1500 PLC.

NOTE V90PN HSP (Hardware Support Package) can be used only in TIA Portal V14 or
further versions.
The V90 HSP can also be connected only to SIMATIC S7-1500 PLCs.

Overview of the automation task


The figure below provides an overview of the automation task.
Figure 1-1
SIMATIC PLC PC/PG
© Siemens AG 2020 All rights reserved

PROFINET IE

Encoder cable

Power cable

Servo Motor
Servo Drive

SINAMICS V90 PN Position Control with HSP in S7-1500


Entry-ID: 109739053, V1.3, 01/2020 4
2 Solution

2 Solution
2.1 Solution overview
Schema Display
The following figure displays the most important components of the solution:
Figure 2-1

IO Supervisor

IO controller
© Siemens AG 2020 All rights reserved

IO device

Delimitation
This application does not include a description of
• PROFINET communication
• SINAMICS V90 PN version
• BOP operation of SINAMICS V90
Basic knowledge of these topics is assumed.

Required knowledge
Basic knowledge on TIA Portal is assumed.

SINAMICS V90 PN Position Control with HSP in S7-1500


Entry-ID: 109739053, V1.3, 01/2020 5
2 Solution

2.2 Hardware and Software Components


2.2.1 Validity

This application example is valid for


• TIA Portal V15.1
• S7-1500 CPU
• SINAMICS V90PN FW V10300
• HSP_V15.1_0185_001_V90_PN
• SIMOTICS S-1FL6 Li motor

2.2.2 Used Components

The application was generated with the following components:

Hardware components
Table 2-1
Component No. Article number Note
SIMATIC S7-1500 1 6ES7511-1TK01-0AB0 V2.1
CPU 1511T-1PN
SINAMICS V90PN 200V 1 6SL3210-5FB10-1UF0 100W
© Siemens AG 2020 All rights reserved

SIMOTICS S-1FL6 Li motor 1 1FL6024-2AF21-1AA1 100W

Standard software components


Table 2-2
Component No. Article number Note
TIA Portal 1 V15.1
HSP_V15_0185_001_V90_PN 1 V15.1, see \3\
SINAMICS V-ASSISTANT 1 V1.05.05, see \4\

Sample files and projects


The following list includes all files and projects that are used in this example.
Table 2-3
Component Note
109739053_Sinamics_V90PN_HSP_with_S7-1500_Position_ Project file
control_TIAP15_1.zip
109739053_PosControl_V90_S7-1500_DOC_de_V1.3.pdf Reference
document

SINAMICS V90 PN Position Control with HSP in S7-1500


Entry-ID: 109739053, V1.3, 01/2020 6
3 Basics

3 Basics
3.1 Basics regarding SINAMICS V90 PN HSP (Hardware
Support Package)
The SINAMICS V90 PN supports the following main telegrams:
• Standard telegram 1
• Standard telegram 2
• Standard telegram 3
• Standard telegram 5
• Standard telegram 102
• Standard telegram 105

The SINAMICS V90 PN also supports the supplementary telegram 750, but it can
only be used together with a main telegram, such as telegram 3 and telegram 105.
If V90 PN HSP is used for applications then the TO (Technology Object) inside of
the SIMATIC S7-1500 must be used.
The V90 PN HSP contains a predefined telegram 105 in its configuration
which can be used in different kind of applications (positioning, speed
control …).
© Siemens AG 2020 All rights reserved

NOTE The telegram configuration which has been implemented inside of the V90 HSP
element cannot be changed by the user.

NOTE Telegram 750 only could be used in V90 PN FW V1.03 or above version.

SINAMICS V90 PN Position Control with HSP in S7-1500


Entry-ID: 109739053, V1.3, 01/2020 7
3 Basics

3.2 Installation and startup


3.2.1 Hardware installation

The figure below shows the hardware configuration of the application:

CAUTION Wrong wiring can damage the drive!


In this application, the one phase 230V power supply is used. It is a must for you
to check the supply voltage; otherwise, the drive can be damaged!

Figure 3-1
© Siemens AG 2020 All rights reserved

3.2.2 Trial-run for V90 PN and 1FL6 motor

Table 3-1 Trial-run


No. Action Remarks
1. Set drive parameter p29108 to be “1”. JOG function is enabled when p29108 = “1”
2. Switch to JOG menu with drive BOP operation.
3. Press or button to run the motor. Check if the motor can run properly.

SINAMICS V90 PN Position Control with HSP in S7-1500


Entry-ID: 109739053, V1.3, 01/2020 8
3 Basics

3.3 Install V90 PN HSP in TIA Portal


Install V90 PN HSP in TIA Portal as follows:

NOTE The V90 PN HSP file can be downloaded from the following SIOS entry:
https://support.industry.siemens.com/cs/ww/en/view/72341852

Table3-1
No. Action Remarks
1. Open the TIA Portal software and click the “project view”
© Siemens AG 2020 All rights reserved

2. Click the “Options” and select the “Support packages”

SINAMICS V90 PN Position Control with HSP in S7-1500


Entry-ID: 109739053, V1.3, 01/2020 9
3 Basics

No. Action Remarks


3. Add the file from system

4. Check the “HSP0185 SINAMICS V90 V1.0“ and then click on “Install“
© Siemens AG 2020 All rights reserved

5. Close the TIA-Portal when this notes appears:

SINAMICS V90 PN Position Control with HSP in S7-1500


Entry-ID: 109739053, V1.3, 01/2020 10
3 Basics

No. Action Remarks


6. After closing the TIA Portal → click “Continue“

7. Click the “Restart“ button and finish the installation of the Hardware
Support Package.
© Siemens AG 2020 All rights reserved

SINAMICS V90 PN Position Control with HSP in S7-1500


Entry-ID: 109739053, V1.3, 01/2020 11
4 Configuration

4 Configuration
In this section, the configuration for the example position control with V90 PN HSP
will be described in detailed.

4.1 Introduction of the V90PN HSP in TIA portal V15.1


4.1.1 Add the SINAMICS V90 PN via HSP and start with the configuration

Table 4-1
No. Action Remarks
1. Open the TIA Portal and create a new project:

2. Switch to Project view


© Siemens AG 2020 All rights reserved

SINAMICS V90 PN Position Control with HSP in S7-1500


Entry-ID: 109739053, V1.3, 01/2020 12
4 Configuration

No. Action Remarks


3. 1. Double-click the node “Devices & networks” from the project tree Note: The used
2. Select in the right side panel select the “Hardware catalog” tab V90 PN drive in
3. Click on “Drives & starters”-> “SINAMICS drives”-> “SINAMICS V90 PN” this example is
and then select the version of the used SINAMICS V90 PN drive “V90PN,1AC/3AC
200V-240V,
0.1kW”.
© Siemens AG 2020 All rights reserved

4. Double click the “V90PN,1AC/3AC 200V-240V,0.1kW”

SINAMICS V90 PN Position Control with HSP in S7-1500


Entry-ID: 109739053, V1.3, 01/2020 13
4 Configuration

No. Action Remarks


5. Select the corresponding MLFB and the corresponding V90 PN drive In this application
firmware version: the drive “6SL3210-
5FB10-1UF0” is
selected (0.1KW /
200V drive and the
V90 PN firmware is
V1.3)
© Siemens AG 2020 All rights reserved

6. Drag the V90PN to the network view:

SINAMICS V90 PN Position Control with HSP in S7-1500


Entry-ID: 109739053, V1.3, 01/2020 14
4 Configuration

No. Action Remarks


7. Double click the V90PN to enter the properties field: Example:
Here, you can configure information about the device name, Ethernet Profinet device
address… name: v90pn1
IP- address:
192.168.0.2
© Siemens AG 2020 All rights reserved

SINAMICS V90 PN Position Control with HSP in S7-1500


Entry-ID: 109739053, V1.3, 01/2020 15
4 Configuration

4.1.2 Parameters change and download

You can use V90PN HSP to do the parameters commissioning such as selecting the motor and
encoder, setting the line supply voltage, brake control and so on.
Table 4-2
No. Action Remarks
1. Click on the parameters from project tree as below:
© Siemens AG 2020 All rights reserved

2. After clicking the parameter, you will see the parameter setting: You can adapt
the para-
meters via the
shown
options.

SINAMICS V90 PN Position Control with HSP in S7-1500


Entry-ID: 109739053, V1.3, 01/2020 16
4 Configuration

No. Action Remarks


3. After finishing the parameter setting you can download it via the selection
“Ungrouped devices”:
© Siemens AG 2020 All rights reserved

SINAMICS V90 PN Position Control with HSP in S7-1500


Entry-ID: 109739053, V1.3, 01/2020 17
4 Configuration

4.1.3 Online commissioning and optimization

Table4-3
No. Action Remarks
1. Select the V90 PN device → right click and select “Go online”:
© Siemens AG 2020 All rights reserved

2. Click on the “Commissioning” and then get the master control access:

3. If the
communication is
not stable, you can
increase the
monitoring time to
for example
3000ms.

SINAMICS V90 PN Position Control with HSP in S7-1500


Entry-ID: 109739053, V1.3, 01/2020 18
4 Configuration

No. Action Remarks


4. Click on the Switch on and use the JOG button to test the drive.

5. Change the control panel to the optimization panel as below: Note:


In this
optimization
panel you can
change the
dynamic
parameters for
the optimization
run.
© Siemens AG 2020 All rights reserved

If there is a need
for a more
detailed
configuration you
can click the
extended settings
and get more
options. (This
optimization is
similar as one
button tuning in
V90 V-Assistant)

6. Click on the “start optimization” and then waiting for the motor optimization
run. When it has been finished, the new dynamic values can be saved in the
drive.

SINAMICS V90 PN Position Control with HSP in S7-1500


Entry-ID: 109739053, V1.3, 01/2020 19
4 Configuration

No. Action Remarks


7. After above operations the changes inside of the online drive should be saved If the upload
in the offline project. button is not
Click on the “v90pn1” and then click on “upload from device”: available then
disconnect the
engineering from
the drive (“Go
offline”) and
upload the drive
in the offline
project.
© Siemens AG 2020 All rights reserved

SINAMICS V90 PN Position Control with HSP in S7-1500


Entry-ID: 109739053, V1.3, 01/2020 20
4 Configuration

4.1.4 Trace function introduction

If it’s necessary to trace the signals of drive or motor during the commissioning,
then the trace function of TIA portal can be used.
Table4-4
No. Action Remarks
1. Add the trace configuration in project tree:
© Siemens AG 2020 All rights reserved

2. Select the signals which you want to trace and define the recording
conditions:

SINAMICS V90 PN Position Control with HSP in S7-1500


Entry-ID: 109739053, V1.3, 01/2020 21
4 Configuration

No. Action Remarks


3. There are several signals which can be traced:

4. After finish the configuration, you should download the trace configuration:
© Siemens AG 2020 All rights reserved

SINAMICS V90 PN Position Control with HSP in S7-1500


Entry-ID: 109739053, V1.3, 01/2020 22
4 Configuration

No. Action Remarks


5. Click on the diagram and then click on the active recording button:

6. After finish the recording, you can use the buttons of the tool to zoom in, zoom out
and others operation.
© Siemens AG 2020 All rights reserved

SINAMICS V90 PN Position Control with HSP in S7-1500


Entry-ID: 109739053, V1.3, 01/2020 23
4 Configuration

4.1.5 Other related function introduction

NOTE The setup for the Profinet parameters like device name and IP address can be
setup via the V90 PN HSP element in the project tree under “Online &
diagnostic” → Functions → Assign …
It is also possible to set the Profinet parameters via the TIA-Portal live list
(Project tree →Online access → *….LAN adapter → “Online & diagnostic” →
Functions → Assign …).

NOTE With the V90 PN HSP element you can check the drive for alarm and fault
information, acknowledge faults and save or reset the drive.

Table4-5
No. Action Remarks
1. Click on the V90pn1 and go online:
© Siemens AG 2020 All rights reserved

SINAMICS V90 PN Position Control with HSP in S7-1500


Entry-ID: 109739053, V1.3, 01/2020 24
4 Configuration

No. Action Remarks


2. Click on the diagnostics → you can see the information of the drive:
© Siemens AG 2020 All rights reserved

3. Click on the Active messages → you can acknowledge faults:

SINAMICS V90 PN Position Control with HSP in S7-1500


Entry-ID: 109739053, V1.3, 01/2020 25
4 Configuration

No. Action Remarks


4. Click on “Save/reset” → you can select the save/restart function:
© Siemens AG 2020 All rights reserved

5. Setup the Profinet device name / IP address:

SINAMICS V90 PN Position Control with HSP in S7-1500


Entry-ID: 109739053, V1.3, 01/2020 26
4 Configuration

4.2 Configure PROFINET settings via the TIA Portal


4.2.1 Add S7-1500 into the project

Table4-6
No. Action Remarks
1. Switch to Project view
© Siemens AG 2020 All rights reserved

2. Double-click the node “Add new device” from the Device tree:

SINAMICS V90 PN Position Control with HSP in S7-1500


Entry-ID: 109739053, V1.3, 01/2020 27
4 Configuration

No. Action Remarks


3. In here, if you know the detailed information about the S7-1500
modules, you can directly find the type and add it into the project:
© Siemens AG 2020 All rights reserved

4. Otherwise, you can add an unspecified CPU1500 into the project:

SINAMICS V90 PN Position Control with HSP in S7-1500


Entry-ID: 109739053, V1.3, 01/2020 28
4 Configuration

No. Action Remarks


5. If an unspecified 1500 CPU has been added, you can detect the Optional: only in case
connected CPU by clicking the “Detect” and search it with online of unspecified CPU
access 1500

6. Start the search by clicking the “Start search” button, and the
connected S7-1500 CPU will be found if the PROFINET network
communication works properly:
© Siemens AG 2020 All rights reserved

7. Press “Detect” button to detect the connected CPU:

SINAMICS V90 PN Position Control with HSP in S7-1500


Entry-ID: 109739053, V1.3, 01/2020 29
4 Configuration

4.2.2 Device configuration of the S7-1500 CPU

Device name and Ethernet address configuration via TIA Portal


Table4-3
No. Action Remarks
1. Click on “Online access” to find the accessible devices, and under the PLC
device click on “Online&diagnostics”:

2. In this new window select “Functions” and change “IP Address” and Note: in this project
“Subnet mask” and then click on “Assign IP address”: the IP address:
192.168.0.1 and
Subnet mask:
255.255.255.0 will
be used
© Siemens AG 2020 All rights reserved

3. Click on “Assign PROFINET device name”, write the name on the field and
click on “Assign name”

SINAMICS V90 PN Position Control with HSP in S7-1500


Entry-ID: 109739053, V1.3, 01/2020 30
4 Configuration

No. Action Remarks


4. Double click the “Devices&networks”-> “Device view” and select S7-1511T
CPU

5. Double click the S7-1511T CPU to enter the properties field: Device
Here, you can configure information about the device name, Ethernet name:1511T,
address… Ethernet
address:192.168.0.1
© Siemens AG 2020 All rights reserved

SINAMICS V90 PN Position Control with HSP in S7-1500


Entry-ID: 109739053, V1.3, 01/2020 31
4 Configuration

4.2.3 Connect V90 PN with S7-1500

Table4-7
No. Action Remarks
1. In the network view, click the “Not assign” and select “1511t.PROFINET
Interface_1”:
© Siemens AG 2020 All rights reserved

2. Configure the topology between V90PN and S7-1511T, switch to the If IRT
topology view: communication is
selected, topology
is necessary.

3. Configure the topology according to the actual wiring connection and In this example, the
dragging and dropping: X1 Port 1 of the S7-
1500 CPU is
connected to the
port 1 at the drive
side.

SINAMICS V90 PN Position Control with HSP in S7-1500


Entry-ID: 109739053, V1.3, 01/2020 32
5 Operation of the application

5 Operation of the application


In the following paragraph, we will use TO (Technology Object) of positioning axis
for commissioning.

Table 5-1
No. Action Remarks
1. Add a new object by double-click “Add new object” from the project tree:

2. Select the “TO_Positioning” from the “Motion Control” list:


© Siemens AG 2020 All rights reserved

SINAMICS V90 PN Position Control with HSP in S7-1500


Entry-ID: 109739053, V1.3, 01/2020 33
5 Operation of the application

No. Action Remarks


3. When a new object has been added successfully, the object node is added into
the device tree and the configuration panel for this newly added axis is opened:

4. Make configurations step by step. In this example, we firstly need to configure


the drive under the hardware interface:
© Siemens AG 2020 All rights reserved

5. Right-click the OB91 and select the properties and change the cycle time to V90 PN IRT
2ms communication
time is 2ms.

6. Compile the project and then download it into device.

SINAMICS V90 PN Position Control with HSP in S7-1500


Entry-ID: 109739053, V1.3, 01/2020 34
5 Operation of the application

No. Action Remarks


7. Switch to the commissioning panel by double-clicking the “Commissioning”
under the technology object tree:

8. Click the “Activate” button:

9. Set the monitoring time for the master control. In this example, we use the
default 2000 ms. Click “Yes” button to proceed:
© Siemens AG 2020 All rights reserved

10. Click the “Enable” button to make servo drive at SON state:

SINAMICS V90 PN Position Control with HSP in S7-1500


Entry-ID: 109739053, V1.3, 01/2020 35
5 Operation of the application

No. Action Remarks


11. Here you can select an operating mode from the drop list:

12. Select the operating mode “Set home position”:


© Siemens AG 2020 All rights reserved

13. Press the “Start” button and then current position is set as the home position.
After that, the axis status indicates that the homing operation has been finished:

14. Select the operating mode “Positioning relative”:

15. Input “100” into the distance field:

SINAMICS V90 PN Position Control with HSP in S7-1500


Entry-ID: 109739053, V1.3, 01/2020 36
5 Operation of the application

No. Action Remarks


16. Press “Backward” or “Forward” button, and then the motor starts running to
the relative position of 100 mm. The current position and speed values are
indicated in the “Current values” field:

17. Switch to offline mode and open the main program block OB1.
18. Program with the technology instructions at the right side:
© Siemens AG 2020 All rights reserved

SINAMICS V90 PN Position Control with HSP in S7-1500


Entry-ID: 109739053, V1.3, 01/2020 37
5 Operation of the application

No. Action Remarks


19. Program as follows:
© Siemens AG 2020 All rights reserved

20. Compile and load the project into devices.


21. Switch to online mode and activate the monitoring function.

SINAMICS V90 PN Position Control with HSP in S7-1500


Entry-ID: 109739053, V1.3, 01/2020 38
5 Operation of the application

No. Action Remarks


22. Modify M10.1 to 1 to make drive SON:
© Siemens AG 2020 All rights reserved

23. Modify M10.4 to 1 to perform homing:

SINAMICS V90 PN Position Control with HSP in S7-1500


Entry-ID: 109739053, V1.3, 01/2020 39
5 Operation of the application

No. Action Remarks


24. Modify M10.6 to 1 to perform relative positioning for 100 mm with the speed of
50 mm/s:
© Siemens AG 2020 All rights reserved

25. Modify M10.7 to 1 to move to absolute position of 1000 mm with the speed of
200 mm/s:

SINAMICS V90 PN Position Control with HSP in S7-1500


Entry-ID: 109739053, V1.3, 01/2020 40
6 Optional - Basic parameter configuration regarding SINAMICS V90 with V-Assistant

6 Optional - Basic parameter configuration


regarding SINAMICS V90 with V-Assistant

NOTE The usage of the V-Assistant is normally not necessary by working with the
Hardware Support Package of the V90 PN because every necessary part of the
drive commissioning can be made via TIA-Portal and the Hardware Support
Package.

Configure PROFINET settings via SIANMICS V-ASSISTANT


Table 6-1
No. Action Remarks
1. Click “Set PROFNET”. Open V-
Assistant and
open connect
for example
directly to the
drive via USB.
© Siemens AG 2020 All rights reserved

2. Click “Select telegram”,Select the “Specified telegram with S7-1500” – this The default
telegram
options contains the SIEMENS telegram 105 from the telegram list.
setting in the
drive is
SIEMENS
telegram 105.
This will be
also the
default option
after making a
factory reset.

SINAMICS V90 PN Position Control with HSP in S7-1500


Entry-ID: 109739053, V1.3, 01/2020 41
6 Optional - Basic parameter configuration regarding SINAMICS V90 with V-Assistant

No. Action Remarks


3. Click “Configure network” and set the Profinet Name of Station – in this
example it is “V90pn1” as the device name. Setup the application defined IP –
address – in this example it is “192.168.0.2” as the IP address. And then click
“Save and active”

4. Click on the RAM to ROM button and then restart the drive
© Siemens AG 2020 All rights reserved

SINAMICS V90 PN Position Control with HSP in S7-1500


Entry-ID: 109739053, V1.3, 01/2020 42
7 Appendix

7 Appendix
7.1 Service and support
Industry Online Support
Do you have any questions or need assistance?
Siemens Industry Online Support offers round the clock access to our entire
service and support know-how and portfolio.
The Industry Online Support is the central address for information about our
products, solutions and services.
Product information, manuals, downloads, FAQs, application examples and videos
– all information is accessible with just a few mouse clicks:
https://support.industry.siemens.com/

Technical Support
The Technical Support of Siemens Industry provides you fast and competent
support regarding all technical queries with numerous tailor-made offers
– ranging from basic support to individual support contracts. Please send queries
to Technical Support via Web form:
https://www.siemens.com/industry/supportrequest
© Siemens AG 2020 All rights reserved

SITRAIN – Training for Industry


We support you with our globally available training courses for industry with
practical experience, innovative learning methods and a concept that’s tailored to
the customer’s specific needs.
For more information on our offered trainings and courses, as well as their
locations and dates, refer to our web page:
https://www.siemens.com/sitrain

Service offer
Our range of services includes the following:
• Plant data services
• Spare parts services
• Repair services
• On-site and maintenance services
• Retrofitting and modernization services
• Service programs and contracts
You can find detailed information on our range of services in the service catalog
web page:
https://support.industry.siemens.com/cs/sc

Industry Online Support app


You will receive optimum support wherever you are with the "Siemens Industry
Online Support" app. The app is available for iOS and Android:
https://support.industry.siemens.com/cs/ww/en/sc/2067

SINAMICS V90 PN Position Control with HSP in S7-1500


Entry-ID: 109739053, V1.3, 01/2020 43
7 Appendix

7.2 Application support


Siemens Ltd., China
DF M3-BF GMC

No. 18 Siemens Road


Jiangning Development Zone
Nanjing, 211100
China
mailto: mc_gmc_mp_asia.cn@siemens.com

7.3 Links and literature


Table 7-1
No. Topic
\1\ Siemens Industry Online Support
https://support.industry.siemens.com
\2\ Link to this entry page of this application example
https://support.industry.siemens.com/cs/ww/en/view/109739053
© Siemens AG 2020 All rights reserved

\3\ Support Packages for the hardware catalog in the TIA Portal (HSP)
https://support.industry.siemens.com/cs/ww/en/view/72341852
\4\ SINAMICS V-ASSISTANT Commissioning tool
https://support.industry.siemens.com/cs/ww/en/view/109738387

7.4 Change documentation


Table 7-2
Version Date Modifications
V1.0 03/2016 First version
V1.1 05/2020 Update to TIA Portal V15
V1.2 07/2018 Use of HSP for V90PN in TIA Portal V15
V1.3 01/2020 Update to TIA Portal V15.1

SINAMICS V90 PN Position Control with HSP in S7-1500


Entry-ID: 109739053, V1.3, 01/2020 44