Hattersley Balancing Coefficients
Hattersley Balancing Coefficients
Hattersley Balancing Coefficients
Fig. M2000
Nom
Size mm 50 65 80 100 125 150 200
Flow Kv 71.91 155.9 217.3 380.2 576.6 830.8 1412
Headloss Factor 0.45 0.4 0.4 0.35 0.35 0.35 0.35
Kvs 48.24 98.58 137.4 224.9 341.1 491.5 835.4
Nom
Size mm 250 300 350 400 450 500 600
Flow Kv 2116 3073 3810 4968 6087 7958 11621
Headloss Factor 0.35 0.35 0.35 0.35 0.35 0.35 0.35
Kvs 1252 1818 2254 2939 3601 4708 6875
Fig. M3000
Nom
Size mm 50 65 80 100 125 150 200 250 300
Flow Kv - 155.9 217.3 380.2 576.6 830.8 1412 2116 3073
Headloss Factor - 0.4 0.4 0.35 0.35 0.35 0.35 0.35 0.35
Kvs - 98.58 137.4 224.9 341.1 491.5 835.4 1252 1818
Fig. MH733
Nom
Size mm 50 65 80 100 125 150 200 250 300
Flow Kv (fully open) - 85 111 146 250 380 600 1211 1521
Fig. MH737
Nom
Size mm 50 65 80 100 125 150 200 250 300
Flow Kv (fully open) - 85 111 146 250 380 600 1211 1521
Fig. 5953G
Nom
Size mm 50 65 80 100 125 150 200 250 300
Headloss Factor 0.45 0.4 0.4 0.35 0.35 0.35 0.35 0.35 0.35
Kvs 48.24 98.58 137.4 224.9 341.1 491.5 835.4 1252 1818
Fig. 5973G
Nom
Size mm 50 65 80 100 125 150 200 250 300
Headloss Factor 0.45 0.4 0.4 0.35 0.35 0.35 0.35 0.35 0.35
Kvs 48.24 98.58 137.4 224.9 341.1 491.5 835.4 1252 1818
Every effort has been made to ensure that the information contained in this publication is accurate at the time of publishing.
010316
Hattersley Ltd assumes no responsibility or liability for typographical errors or omissions or for any misinterpretation of the
information within the publication and reserves the right to change without notice.
Headloss Factor % The headloss of the DRV is obtained from the graph at the fully
The headloss across a metering station is less than the open position at the particular design flow rate. The total
differential pressure (¢P) signal indicated at the pressure headloss of the metering station and DRV (commissioning set),
tappings as shown on the metering station flow charts. when directly coupled or independently located, is the
The value of headloss for the metering station is shown summation of the two separate values.
as a percentage of the signal in the tables below.
Fig.1000 / Fig.1000S
Nom
Size mm 15 22 28 32 40 50
Flow Kv 2.244 5.4 9.63 21.68 34.38 71.1
Headloss Factor 0.75 0.6 0.6 0.5 0.45 0.45
Kvs 1.943 4.181 7.46 15.33 23.06 47.7
*Fig.1000S refers to DN15 only.
Every effort has been made to ensure that the information contained in this publication is accurate at the time of publishing.
270916
Hattersley Ltd assumes no responsibility or liability for typographical errors or omissions or for any misinterpretation of the
information within the publication and reserves the right to change without notice.
Fig. 1200DR
Nom
Size mm 15 20 25 35 40 50
Flow Kv 4.74 9.96 18.46 26.71 42.15 70.95
Every effort has been made to ensure that the information contained in this publication is accurate at the time of publishing.
081116
Hattersley Ltd assumes no responsibility or liability for typographical errors or omissions or for any misinterpretation of the
information within the publication and reserves the right to change without notice.