Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

City 2

Download as pdf or txt
Download as pdf or txt
You are on page 1of 27

INDEX

ENGLISH
IMPORTANT REMARKS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
DECLARATION OF CONFORMITY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
TECHNICAL SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
DESCRIPTION OF THE CONTROL UNIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
POWER SUPPLY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
LOW VOLTAGE OUTPUT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
COURTESY LIGHTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
PHOTOCELLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
SAFETY RIBBONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
LOCK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
LIMIT SWITCH AND ENCODER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
STOP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
ACTIVATION INPUTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
PLUG IN RECEIVER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
EXTERNAL AERIAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
ADI INTERFACE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
ELECTRIC CONNECTIONS TABLE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
CONTROL PANEL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34
USE OF THE DOWN, MENU AND UP KEYS FOR PROGRAMMING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34
QUICK CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34
LOADING OF DEFAULT PARAMETERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34
SELF-LEARNING OF WORKING TIMES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .35
Obstacle sensor operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36
CONTROL UNIT CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36
READING OF CYCLE COUNTER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .48
OPERATION DEFECTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49
CITY2+ FUNCTION TABLE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .50

27
IMPORTANT REMARKS DECLARATION OF CONFORMITY
For any installation problem please contact our Customer Service V2 S.p.A. hereby declare that CITY2+ products conform to the
at the number +39-0172.812411 operating Monday to Friday essential requirements established in the following directives:
from 8:30 to 12:30 and from 14:00 to 18:00.
- 89/336/CEE (EMC Directive in accordance with standards
V2 has the right to modify the product without previous EN 55014-1, EN 55014-2, EN 61000-3-2, 61000-3-3)
notice; it also declines any responsibility to damage or - 2006/95/CEE (Low Voltage Directive in accordance with
ENGLISH

injury to people or things caused by improper use or standards EN 60335-1 + EN 60335-2-103)


wrong installation. - 99/05/CEE (Radio Directive in accordance with standard

 Please read this instruction manual very carefully


EN 301 489-3)

before installing and programming your control unit. Racconigi, 12/01/2009


V2 S.p.A. legal representative.
• This instruction manual is only for qualified technicians, Antonio Cristina
who specialize in installations and automations.
• The contents of this instruction manual do not concern the
end user. TECHNICAL SPECIFICATIONS
• Every programming and/or every maintenance service
should be done only by qualified technicians. CITY2+
Power supply 230VAC - 50Hz
AUTOMATION MUST BE IMPLEMENTED IN COMPLIANCE
WITH THE EUROPEAN REGULATIONS IN FORCE: Max total load 250W
Max load for each motor 150W
EN 60204-1 (Machinery safety. electrical equipment of
Duty clcle 40%
machines, part 1: general rules)
EN 12445 (Safe use of automated locking devices, Max accessories load 24Vdc 15W
test methods) Working temperature -20 ÷ +60°C
EN 12453 (Safe use of automated locking devices,
requirements) Protection fuse F1 = 2,5A
Dimensions 295 x 230 x 100 mm
• The installer must provide for a device (es. magnetotermical
Weight 3000g
switch) ensuring the omnipolar sectioning of the equipment
from the power supply. Protection IP55
The standards require a separation of the contacts
of at least 3 mm in each pole (EN 60335-1).

• After making connections on the terminal board, use one DESCRIPTION OF THE CONTROL UNIT
hose clamp to fix dangerous voltage wires near the terminal
The digital control unit CITY2+ is an innovative V2 product that
board and another hose clamp to fix safety low voltage wires
guarantees a safe and reliable automation of leaf swing or
used for accessories connection; this way, in case of
sliding gates.
accidental detachment of a conducting wire, dangerous
voltage parts will not come into contact with safety low
CITY2+ is provided with a display that, not only makes
voltage ones.
programming simple, but also allows a continuous monitoring of
the input statuses; in addition, thanks to a menu structure, the
• The plastic case has an IP55 insulation; to connect flexible
working schedule and the operation logic can be set easily.
or rigid pipes, use pipefittings having the same insulation
level.
In compliance with the European standards concerning
electrical safety and electromagnetic compatibility
• Installation requires mechanical and electrical skills,
(EN 60335-1, EN 50081-1 and EN 50082-1) it has been
therefore it shall be carried out by qualified personnel only,
equipped with the low voltage circuit total electric insulation
who can issue the Compliance Certificate concerning the
(motors included) from the network voltage.
whole installation (EEC Machine Directive 89/392, Annex IIA).
Other characteristics:
• The automated vehicular gates shall comply with the
• Power supply protected from short circuits within the
following rules: EN 12453, EN 12445, EN 12978 as well
controller, on the motors and on the connected accessories.
as any local rule in force.
• Adjustment of the power by partializing the current.
• Detecting obstacles by monitoring the current on the motors
• Also the automation upstream electric system shall comply
(current sensing probe)
with the laws and rules in force and be carried out
• Automatic learning of the operation time.
workmanlike.
• Tests for safety devices (photocells, safety ribbons and
mosfet) before each opening.
• The door thrust force adjustment shall be measured
• Deactivation of safety inputs through the configuration
by means of a proper tool and adjusted according to
menu: no jumper is required for terminals concerning safety
the max. limits, which EN 12453 allows.
devices that have not been installed, yet. You will only need
to disable this function from its relevant menu.
• We recommend to make use of an emergency
• The device can operate without mains power, by using the
button, to be installed by the automation (connected
optional battery pack (code 161212).
to the control unit STOP input) so that the gate may
• Low voltage output that can be used for a signal light or a
be immediately stopped in case of danger.
24 V flashing light.
• Auxiliary relay with programmable logic for courtesy light,
• Always remember to connect the earth according to
flashing light or other use.
current standards (EN 60335-1, EN 60204-1). 28
INSTALLATION PHOTOCELLS
Installation of control unit and safety devices must be carried out The control unit considers two kinds of photocells, depending on
with power disconnected. the terminal to which they are connected:

• Photocell 1: that is to say, photocells installed on the gate


POWER SUPPLY inner side, which are active both during the opening and the
The control unit must be fed by a 230V closing phase. When photocells 1 operate, the control unit

ENGLISH
50Hz (120V - 50/60Hz for the 120V stops the gate; as soon as the photocell beam is free, the
models) electric line, protected by a control unit will open the gate completely.


differential magnetothermal switch
complying with the law WARNING: Type 1 photocells must be installed so that
provisions in force.
they completely cover the opening area of the gate.
Connect the power supply wires to
• Photocell 2: that is to say, photocells installed on the
terminals L and N on the board located
external gate side and which are active during the closing
next to the transformer.
phase only. When photocells 2 operate, the control unit
opens the gate immediately, without waiting for release.

CITY2+ control unit supplies a 24Vdc power supply to photocells


LOW VOLTAGE OUTPUT and it can perform a photocell operation test before starting the
The CITY2+ controller has a 24 V DC output that allows gate opening phase. Photocell power terminals are protected by
connections to a load up to 15 W. an electronic fuse that stops current in case of overload.
This output can be used to connect a signal light that indicates
that status of the gate, or for a low voltage flashing light. • Connect power supply cables of photocells transmitter
between terminals K7 and K8 of the control unit.
Connect the low voltage signal light or flashing light wires to
terminals Z1 (+) and Z2 (-). • Connect power supply cables of photocells receiver
between terminals K6 and K7 of the control unit.
CAUTION: Pay attention to the polarity of the connected
device if necessary. • Connect receiver output of photocells 1 between terminals L7
and L11 of the control unit and receiver output of photocells
2 between terminals L8 and L11 of the control unit.
Use outputs having normally closed contact.

COURTESY LIGHTS
Thanks to the output COURTESY LIGHT the control unit


allows the connection of an electric appliance (e.g. courtesy
light or garden lights), controlled automatically or by means of WARNING:
the special transmitter key.
• if several couples of same kind photocells are mounted,
their outputs must be connected in series.
The courtesy light terminals can be alternatively used for a 230 V
• In case of reflection photocells, power supply must be
flashing light with integrated flasher.
connected to terminals K7 and K8 of the control unit to
CAUTION: When the controller is operating on battery
carry out the operation test.
power, the 230 V flashing light will not work.

The output COURTESY LIGHT is a simple N.O. contact with no


power supply.

Connect the cables to terminals B1 and B2.

29
SAFETY RIBBONS LIMIT SWITCH AND ENCODER
The control unit considers two kinds of safety ribbons, The CITY2+ controller can control the gate's travel using a limit
depending on the terminal to which they are connected: switch and/or an encoder.

• Type 1 (fixed): they are mounted on walls or on other fixed  CAUTION: The use of these devices is strongly
obstacles that are approached by the gate doors during the recommended to ensure that the gate opens and closes
opening phase. When type 1 safety ribbons operate during correctly.
ENGLISH

the gate opening phase, the control unit will close the doors The speed of operation of the DC motors can be conditioned by
for 3 seconds, then it stands still; when type 1 safety ribbons variations in mains power, atmospheric conditions, and friction of
operate during the gate closing phase, the control unit will the gate.
stand still immediately. The direction of the gate at next Furthermore, encoders also allow the controller to determine if
command of START or PEDESTRIAN START depends upon the the gate stops in an irregular position due to an obstacle.
parameter STOP (it inverts or continues the motion).
If the input STOP is disabled, the command makes the motion For encoder operation, it is required that the closure position for
continue in the same direction. each section of the gate be detectable using a limit switch sensor
or a mechanical stop.
• Type 2 (mobile): they are mounted to the door ends. Each time the controller is turned on, to realign the encoders, the
When type 2 safety ribbons operate during the gate opening gate is closed until it reaches the limit switch or the mechanical
phase, the control unit will stand still immediately; when stop.
type 2 safety ribbons operate during the gate closing, the
control unit will open the doors for 3 seconds, then it will
stand still. The direction of the gate at next command of
START or PEDESTRIAN START depends upon the parameter
STOP (it inverts or continues the motion). If the input STOP
is disabled, the command makes the motion continue in the
same direction.
GATES WITH TWO PANELS
Both the input can manage the classic safety edge with n.c. For gates with two panels, limit switches and encoders share the
contact and the conductive rubber safety edge with 8,2 kohm same terminals so it is not possible to install both of these devices
nominal resistance. at the same time.

Connect type 1 safety ribbons cables between terminals L9 and Installation of limit switch
L11 of the control unit. • Connect the open limit switch to motor 1 using terminals
Connect type 2 safety ribbons cables between terminals L10 K1 and K5
and L11 of the control unit. • Connect the close limit switch to motor 1 using terminals
K2 and K5
• Connect the open limit switch to motor 2 using terminals
K3 and K5
• Connect the close limit switch to motor 2 using terminals
K4 and K5

Installation of encoders
In order to meet the requirements of the EN12978 rules, it is • Connect the power source for both encoders to terminals
necessary to install safety edges controlled by a control unit K5 and K6
continuously checking the proper working. If using control units • Connect the encoder outputs to motor 1 using terminals
suited to the test by power outage, connect the power supply K3 and K4
cables of the control unit between terminals K7 and K8 of the • Connect the encoder outputs to motor 2 using terminals
control unit. K1 and K2
Otherwise, connect them between terminals K6 and K7.


Check that the two pairs of wires have been correctly connected
WARNING: and after installation proceed as follows:
1. Disable encoder operation (Enco menu)
• Make use of safety ribbons having outputs with normally 2. Set a meaningful open delay (r.AP menu)
close contact.
• Outputs of same kind safety ribbons must be connected in NOTE: The default settings in the controller satisfy points
series. 1 and 2.

3. Give a START command:


LOCK - If both gate panels move, the wires are connected correctly
An electric lock can be assembled on the gate, to ensure a good - If Err7 appears on the display once panel 1 starts to move,
closing of doors. Make use of a 12V lock. invert the wires connected to terminals K3 and K4
- If Err7 appears on the display once panel 2 starts to move,
Connect lock cables to terminals K9 and K10 of the control unit. invert the wires connected to terminals K1 and K2

30
GATES WITH SINGLE PANELS • Timer mode: it is similar to the standard mode but the gate
Installation of limit switch stays open (completely or partially) while the contact is
• Connect the open limit switch to terminals K1 and K5 closed on input; as soon as the contact is open the pause
• Connect the close limit switch to terminals K2 and K5 time count down will start, after which the gate will be
closed again. This function allows programming the gate
Installation of encoder opening time during the day, by making use of an external
• Connect the power source for the encoder to terminals timer. Automatic closing must be enabled.
K5 and K6

ENGLISH
• Connect the encoder output to terminals K3 and K4 In all modes, inputs must be connected to devices having
normally open contacts.
Check that the two encoder wires have been correctly connected
and after installation proceed as follows: Connect cables of device controlling the first input between
1. Disable encoder operation (Enco menu) terminals L3 and L6 of the control unit.
2. Set a meaningful open delay (r.AP menu) Connect cables of device controlling the second input between
terminals L4 and L6 of the control unit.
NOTE: The default settings in the controller satisfy points
1 and 2.

3. Give a START command:


- If the gate moves, the wires are connected correctly
- If Err7 appears on the display once the gate starts to move,
invert the wires connected to terminals K3 and K4 The first input function can also be activated by pressing UP key
outside the programming menu or by means of a remote control
stored on channel 1 (see relevant instructions of MR1 receiver).
STOP
For a better safety, you can fit a stop switch that will cause the The second input function can also be activated by pressing
immediate gate stop when activated. This switch must have a DOWN key outside the programming menu or by means of a
normally close contact that will get open in case of operation. remote control stored on channel 2.
In case the stop switch is operated while the gate is open, the
automatic closing function will always be disabled. To close the
gate again, you will need a start command (if the start function PLUG IN RECEIVER
in pause is disabled, it will be temporarily enabled to allow the CITY2+ control unit is suitable for plugging in a Personal Pass
gate release). MR1 receiver having a high-sensitivity super-heterodyne
architecture.
Connect the stop switch cables between terminal L5 and L6 of
the control unit.
 WARNING: it is necessary to turn off the control unit
power before doing the operations mentioned here below. Pay
attention to the way you connect the removable modules.

MR1 module receiver is provided with 4 channels and each of


them is suitable for a command of CITY2+ control unit:
The stop switch function can be activated by means of a CHANNEL 1 쩚쩛 START
remote control stored on channel 3 (see relevant instructions of CHANNEL 2 쩚쩛 PEDESTRIAN START
MR1 receiver) The command STOP from remote is operative CHANNEL 3 쩚쩛 STOP
also if the input STOP of the terminal board is disabled. CHANNEL 4 쩚쩛 COURTESY LIGHT

ACTIVATION INPUTS
 WARNING: Before programming 4 channels and function
logics read carefully the instructions of MR1.
CITY2+ control unit is equipped with two activation inputs,
whose operation depends on the programmed operation modes
(see Strt item of programming menu):

• Standard mode: a command being on the first input will


cause the complete opening of the gate (start); a command
being on the second input will cause the partial opening of
the gate (pedestrian start).

• Open/Close command and manned operation:


a command on the first input always controls the gate
opening, while a command on the second input always
controls the gate closing.
In Open/Close mode, there is an impulse command, that is
to say that an impulse will cause the complete gate opening
or closing.
In manned operation, there is a monostable command, that
is to say, the gate will be opened or closed as long as the
contact is closed and it will immediately stop as the contact
is open.

31
EXTERNAL AERIAL
We suggest to use the external aerial (model: ANSGP433) in
order to guarantee the maximal range.
ELECTRIC CONNECTIONS TABLE
Connect the antenna hot pole to terminal L1 of the control unit
and the braiding to terminal L2. L1 Antenna
L2 Antenna shield
ENGLISH

Opening control for the connection of control


L3
devices with N.O. contact

Opening controls for pedestrian access for the


L4
connection of control devices with N.O. contact
INTERFACE
The ADI (Additional Devices Interface) interface of the control L5 Stop command. N.C. contact
unit CITY2+ allows the connection to V2 optional modules.
L6 Common (-)
Refer to V2 catalogue or to the technical sheets to see which L7 Photocells type 1. N.C. contact
optional modules with ADI interface are available for this control
unit. L8 Photocells type 2. N.C. contact

 WARNING: Please read the instructions of each single


L9
L10
Safety ribbons type 1 (fixed). N.C. contact
Safety ribbons type 2 (mobile). N.C. contact
module to install the optional modules.
L11 Common (-)
K1 Open limit switch motor 1
Encoder motor 2
K2 Close limit switch motor 1
K3 Open limit switch motor 2
Encoder motor 1
K4 Close limit switch motor 2
K5 Common (-)
Power output +24Vdc for photocells and other
K6
accessories
K7 Common for accessories power supply
Photocell/optical edge TX power supply for
K8
functional test
K9 - K10 LOCK 12V
Z1 - Z2 24 V courtesy light or flashing light
Z3 - Z4 Motor 1
Z5 - Z6 Motor 2
B1 - B2 230VAC courtesy light or flashing light

Interface

It shows that there is an overload on accessories


OVERLOAD
power supply
BAT+ + Pole of optional battery pack (code 161212)
BAT- - Pole of optional battery pack (code 161212)

L Power phase 230 VAC / 120VAC


N Neutral 230 VAC / 120VAC

MAINS It shows that the control unit is power supplied

32
ENGLISH
CONTROL PANEL USE OF THE DOWN, MENU AND
When power is on, the control unit checks that display correctly
operates by switching on all segments for 1.5 sec. 8.8.8.8.
UP KEYS FOR PROGRAMMING
Firmware version, e.g. Pr I.0, will be viewed in the following 1.5 Programming of the functions and times of the controller is
sec. Panel will be viewed upon completion of this test. performed using a special configuration menu that is accessed and
explored using 3 keys, DOWN, MENU, and UP, which are located
below the display.
ENGLISH

CAUTION: Except in the configuration menu, pressing the


UP key activates a START command and pressing the DOWN
key activates a START PEDESTRIAN command.

To activate the programming modes (the display must show the


control panel), press and hold down the MENU key until -PrG
appears on the display.

Hold down the MENU key to scroll through the 4 main menus:
-PrG CONTROLLER PROGRAMMING
-Cnt COUNTERS
-APP SELF-LEARNING TIME AND FORCE
The control panel represents the physical status of the -dEF LOAD DEFAULT PARAMETERS
terminal board contacts and of the program mode keys: if the
upper vertical segment is on, the contact is closed; if the lower To enter one of the four main menus, just release the MENU key
vertical segment is on, the contact is open (the above picture when the menu you want appears on the display.
shows an instance where the inputs LIMIT SWITCH, PHOTOCELL 1,
PHOTOCELL 2, SAFETY RIBBONS 1, SAFETY RIBBONS 2 and STOP To move through the four main menus, press the UP and DOWN
have all been correctly connected). keys to scroll through the various items. Press the MENU key to
display the current value of the selected item and change it if
Points being among display digits show the status of needed.
programming push-buttons: as soon as a push-button is pressed,
its relevant point turns on.

The arrows on the left of the display show the state of the start
QUICK CONFIGURATION
inputs. The arrows light when the related input is closed. This paragraph concerns a quick procedure to set the control unit
and set it at work immediately.
The arrows on the display right side show the gate status:
We recommend following these instructions, in order to
• The highest arrow turns on when the gate is into its opening check quickly the correct operation of control unit, motor
phase. If it blinks, it means that the opening has been and accessories, and then changing the configuration in
caused by a safety device (border or obstacle detector). case of any non-satisfactory parameter.

• The central arrow shows that the gate is on pause. If it 1. Call up the default configuration: see paragraph “LOADING
blinks, it means that the time countdown for the automatic OF DEFAULT PARAMETERS”
closing has been activated.
CAUTION: If there is only one motor, set the open time, t.AP2,
• The lowest arrow blinks when the gate is into its closing to zero in order to inform the controller that the parameters for
phase. If it blinks, it means that the closing has been motor 2 do not need to be considered.
caused by a safety device (border or obstacle detector).
2. Set items StoP, Fot1, Fot2, CoS1, CoS2 according to the
safety devices installed on the gate.

3. Start the self-learning cycle: see paragraph “SELF-LEARNING


OF WORKING TIMES “

4. check that the automation work properly and if necessary


modify the configuration of the desired parameters. For the
position of the item menus inside the main menu and for the
options related to each item menu, refer to the paragraph
“CONFIGURATION OF THE CONTROL UNIT”.

34
LOADING OF DEFAULT 4. Press the MENU key to start the self-learning cycle for the
work cycle times:
PARAMETERS
CAUTION: This procedure varies based on the number of gate
If necessary, it is possible to restore all the parameters to their
panels and travel control devices installed.
standard or default value (see table at the end)
If there is no limit switch or encoder installed, only points 4.4

 and 4.5 are performed. If there is only one motor (t.AP2 = 0),

ENGLISH
WARNING: This procedure causes the loss of all the the procedure starts from point 4.3
customized parameters, therefore it has been put outside the
configuration menu, to reduce the possibility of executing it by 4.1 Gate panel 1 is opened for a few seconds
mistake. 4.2 Gate panel 2 is closed until one of the following
conditions occurs:
1. Press and hold down the MENU key until the -dEF appears - it reaches the limit switch
on the display - The obstacle sensor or the encoder detect that the
gate panel is jammed
2. Release the MENU key: the display will show ESC (press the - A START command is given
MENU key only if you want to leave this menu) This position is memorized as the close point for gate
panel 2.
3. Press the DOWN key: dEF will appear on the display. 4.3 Gate panel 1 is closed until one of the conditions listed
in point 4.2 occur:
4. Press the MENU key: no will appear on the display. This position is memorized as the close point for gate
panel 1.
5. Press the DOWN key: Si will appear on the display. 4.4 Each gate panel is opened. The operation ends when
once of the conditions indicated in point 4.2 occur (the
6. Press the MENU key: All of the parameters are returned to first START stops gate panel 1, the second START stops
their default values and the display shows the control panel gate panel 2).
The time required is memorized as the open time.
4.5 Each gate panel is closed. The operation ends when one
of the conditions indicated in point 4.2 occurs or when
the closed position is reached.
The time required is memorized as the close time.

5. The display shows the value recommended for the obstacle


sensor of motor 1. If no operations are performed for
20 seconds, the controller exits the programming phase
without saving the recommended value.

6. The recommended value can be changed using the UP and


DOWN keys. Press the MENU key to confirm the value
displayed and the display will show SEn1

7. Press the DOWN key: The display will show SEn2. Press the
MENU key to display the recommended value for the obstacle
sensor for motor 2, which can be changed in a similar manner
as that for SEn1.

SELF-LEARNING OF WORKING 8. Hold down the DOWN key until the FinE appears on the
display, then press the MENU key, select Si and press the
TIMES MENU key to exit programming and save the values for the
This menu allows the automatic learning of the times necessary sensors.
to open and close the gate.
During this phase, the control unit memorizes also the forces CAUTION: If the controller exits programming due to time out
necessary to open and close the gate: these values will be (1 minute), the obstacle sensors return to the values that were
activated by using the obstacle sensor. set prior to performing self-learning.
The encoder positions are also saved, if enabled.


The open/close times and the encoder positions are always
CAUTION: Before continuing, make certain that the saved.
limit switch(es) and encoder(s) have been installed
correctly. Limit switches and encoders, if installed, must be
enabled using the specific menu.

1. Press and hold down the MENU key until the -APP appears on
the display

2. Release the MENU key: the display will show ESC (press the
MENU key only if you want to leave this menu)

3. Press the DOWN key: t.LAv will appear on the display.

35
OBSTACLE SENSOR OPERATION Time menu setup
Time menus allow setting a function duration. When you enter
CITY2+ control unit is equipped with a sophisticated system that into a time menu, the current setup value will be viewed; the
allows detecting if there is any obstacle stopping the gate display mode depends on the current value:
motion. This system is based on the measurement of the current
absorbed by the motor: a sudden increase of the absorption • times being lower than one minute will be viewed as follows:
indicates the presence of an obstacle.
ENGLISH

CAUTION: The obstacle sensor is disabled by default and must


be enabled using the specific menu items, SEn1 and SEn2.
each time you press UP key, current time value increases of
Detection is performed at both normal speed and slow speed. half a second; vice versa, each time you press the DOWN
The threshold of the sensor is automatically adjusted. key, current time value decreases of half a second.

WARNING: if either the limit switches or the slowing down are • Times between 1 and 10 minutes will be viewed as follows:
disabled, when detected an obstacle the control unit stops the
opening or closing phase without inverting the motion.

CONTROL UNIT each time you press UP key, current time value increases of 5
seconds; vice versa, each time you press the DOWN key,
CONFIGURATION current time value decreases of 5 seconds.

The configuration menu -PrG consists in a list of configurable • Times being more than 10 minutes will be viewed as follows:
items; the display shows the selected item.
By pressing DOWN, you will pass to the next item; by pressing
UP, you will return to the previous item.
By pressing MENU, you can view the current value of selected
item and possibly change it. each time you press UP key, current time value increases of
The last menu item (FinE) allows storing the carried out half a minute; vice versa, each time you press the DOWN key,
changes and going back to the control unit normal operation. current time value decreases of half a minute.
You must exit from programming mode through this menu item
if you do not want to lose your configuration. By holding down the UP key, you can quickly increase the time
value, up to reach the max. value allowed for this item. Vice
WARNING: in case no operation is carried out for more versa, by holding down the DOWN key, you can quickly decrease
than one minute, the control unit exits from the the time value down to reach 0.0”.
programming mode without saving any of your setups and
changes, which will get lost. In some circumstances, setting the value to 0 means that the
relevant function is disabled, in this case, ‘no’ will appear instead
By holding down the DOWN key, configuration menu items will of 0.0”.
scroll fast, until item FinE is viewed. Viceversa, by holding down
the UP key, items will scroll fast backwards until item t.AP1 is By pressing on MENU you will confirm the displayed value and
viewed. you will return to the configuration menu.

In this way, you can quickly reach either the top or Value menu setup
bottom of the list. Value menus are similar to time menus; however, the setup value
can be any number.
There are the following three kinds of menu items: By holding down UP or DOWN keys, the value will increase or
• Function menu decrease slowly.
• Time menu
• Value menu

Function menu setup


Function menus allow selecting a function from among a group
of available options. When you enter into a function menu, the
current active option will be viewed; you can scroll all available
options through DOWN and UP keys. By pressing the MENU key,
you will activate the option viewed and you will return to the
configuration menu.

36
Leaf 1 opening time
Motor 1 will be operated for the setup time in the opening phase;
in case there is an obstacle or the end of stroke operates, the control

ENGLISH
unit can stop the opening phase before the relevant time expires.

Leaf 2 opening time


Motor 2 will be operated for the setup time in the opening phase;
In case there is an obstacle or the end of stroke operates, the control
unit can stop the opening phase before the relevant time expires.

 WARNING: if motor 2 is not connected, this time must be set to


zero; in this circumstance, the control unit will not consider all
configurations of motor 2 and door phase difference times as well.

Partial opening time (pedestrian access)


When the control unit receives a Start Pedestrian command, it will open
leaf 1 only, for a shorter time. Max allowed time to be setup is
1 minute.

Leaf 1 closing time


Motor 1 will be operated for the setup time in the closing phase;
In case there is an obstacle or the end of stroke operates, the control
unit can stop the opening phase before the relevant time expires.
To avoid that the door does not close completely, we recommend to
setup a longer time than t.AP1 opening time.

Leaf 2 closing time


Motor 2 will be operated for the setup time in the closing phase;
the control unit can stop the opening phase before the relevant time
expires, in case there is an obstacle or the end of stroke operates.
To avoid that the door does not close completely, we recommend to
setup a longer time than t.AP2 opening time.

37
Partial closing time (pedestrian access)
When the control unit receives a Start Pedestrian command, it will use
this time to close the gate. Max allowed time to be setup is 1 minute.
ENGLISH

To avoid that the door does not close completely, we recommend to


setup a longer time than t.APP opening time.

Leaf 2 closing time during pedestrian cycle


During a partial opening cycle (pedestrian access) leaf 2 may move
slightly because of the wind or its own weight; in this case at closing
time leaf 1 could hit leaf 2 and the gate would remain not perfectly
closed.
To avoid this, in the last seconds of the cycle a light closing force is
applied to leaf 2 too. If the set time is greater than the time required to
close leaf 1, leaf2 is driven at reduced power all the closing time long.

Opening door delay


During the opening phase, leaf 1 must start moving before leaf 2, to
avoid that both doors may collide. Leaf 2 opening will be delayed for
the setup time.

If you set the opening door delay to zero, the control board does not
execute the control of the correct leaves closing order.

Closing door delay


During the closing phase, leaf 1 must start moving after leaf 2, to avoid
that both doors may collide. Door 1 closing will be delayed for the setup
time.

Lock time
Before the opening phase begins, the control unit will energize the
electric lock in order to release it and enable the gate motion.
t.SEr time will fix the energizing time.

 WARNING: in case the gate has no electric lock, set the value 0
(‘no’ will appear on display).

38
Silent Locking Mode
This menu allows you to select the silent operation mode for the electric
lock.

Si Silent Mode (100 Hz)


no Standard Mode (50 Hz)

ENGLISH
CAUTION: In silent mode, the voltage supplied to the lock has a higher
frequency in order to make the locking less noisy.
In some cases, there may be problems when unlocking. If problems
should occur, select the Standard mode.

Lock advance time


While the electric lock is energized, the gate will stay standstill for t.ASE
time, to make its release easier.
In case t.ASE is lower than t.SEr, the lock energizing will go on while
the doors will start moving.

 WARNING: in case the gate has no electric lock, set the value 0.

Backlash time
It could be useful to give a closing command to motors, to help the
electric lock release.
The control unit controls the motors in reduced power in closing
direction for the setup time.
The backlash precedes the electric lock release. It is possible to reverse the
order by setting a lock advance time higher then the backlash one.

 WARNING: in case the gate has no electric lock, set the value 0.

Pre-blinking time
Before any gate movement, blinker will be activated for t.PrE time, to
warn about the incoming motion.

Motor 1 power
This menu allows adjusting the motor 1 power.
The displayed value is the percentage of max. motor power.

39
Motor 2 power
This menu allows adjusting the motor 2 power.
ENGLISH

The displayed value is the percentage of max. motor power.

Power Motor 1 during slow-down phase


This menu allows you to regulate the power of motor 1 during the
slow-down phase.
The value displayed represents the percentage of the maximum motor
power.

Power Motor 2 during slow-down phase


This menu allows you to regulate the power of motor 2 during the
slow-down phase.
The value displayed represents the percentage of the maximum motor
power.

Maximum motor power during battery operation


During battery operation, the controller is powered with a lower voltage
compared to mains power. For this reason, the power of the motors is
reduced compared to normal operation and may not be sufficient to
move the gate panels effectively.

This menu allows you to activate the motors at their maximum power
during battery operation.

Si Maximum motor power


no Motor power at the parameters set in the Pot1
and Pot2 menus.

Start off
When the gate is standstill and it begins moving, the initial inertia must
be faced, therefore, if your gate is quite heavy, its doors could not
move.
In case the SPUn (pickup) function is activated, for the first 2 seconds of
motion of each door, the control unit will ignore both Pot1 and Pot2
values and it will give motors the maximum power command in order to
overcome the gate inertia.

40
Starting ramp
In order not to stress too much the motor, when the motion starts the
power is gradually increased, until reached the set value or 100% if the
take-off is enabled.

ENGLISH
Higher is the set value, longer the length of time of the ramp, that is the
time necessary to reach the value of nominal power.

Enable the Obstacle Sensor for Motor 1


This menu allows you to regulate the sensitivity of the obstacle sensor
for motor 1. When the current absorbed by the motor exceeds the set
value, the controller detects an alarm.

If set to 0.0A, this function is disabled.

For the sensors operation, please see the paragraph dedicated to it


(page 36).

Enable the Obstacle Sensor for Motor 2


This menu allows you to regulate the sensitivity of the obstacle sensor
for motor 2. When the current absorbed by the motor exceeds the set
value, the controller detects an alarm.

If set to 0.0A, this function is disabled.

For the sensors operation, please see the paragraph dedicated to it


(page 36).

Slowing down time


In case this function is enabled, during the last seconds of motion of
each door, the control unit will give motors a reduced power command,
to avoid a strong impact with the stop end. t.AP1 is the max. allowed
time.

 WARNING:
• In case the self-learning function of working times is NOT used, we
recommend disabling the slowing down function in order to
measure both opening and closing times, and to enable it again once
the setup has been carried out. The control unit will automatically
consider the working time delay caused by the slowing down.
• If partial opening time t.APP is shorter than t.AP1, there will be no
slowing down during the pedestrian cycle opening.

Fast closing time after slowing down


If a slowing time other than 0 is set up, it could be likely that the gate
speed is not enough for the lock to fasten during the closing phase.
In case this function is enabled, once the slowing down phase is
finished, the control unit will give a normal speed command (that is to
say, with no slowing down) for the set up time, and then it will open
the gate for a second fraction, to avoid leaving the motor under stress.

 WARNING: in case the gate has no electric lock, set the value 0.

41
Start command during the opening phase
This menu allows fixing the control unit conduct in case it receives a
Start command during the opening phase.
ENGLISH

PAUS The gate stops and goes to pause.


ChiU The gate immediately starts closing.
no The gate go on with the opening phase (command is ignored).

Select option PAUS, to set up the “step-by-step” operation logic.


Select option ‘no’, to set up the ‘always open’ operation logic.

Start command during the closing phase


This menu allows fixing the control unit conduct in case it receives a
Start command during the closing phase.

StoP The gate stops and its cycle is considered as finished.


APEr The gate opens again.

Select option StoP, to set up the “step-by-step” operation logic.


Select option APEr, to set up the ‘always open’ operation logic.

Start command during the pause


This menu allows fixing the control unit conduct in case it receives a
Start command when the gate is open during its pause phase.

ChiU the gate starts closing.


no command is ignored.
PAUS The pause time is reset (Ch.AU)

Select option ChiU, to set up the “step-by-step” operation logic.


Select option ‘no’, to set up the ‘always open’ operation logic.
Apart from selected option, the start command lets the gate close if it
has been stopped by a stop command or if the automatic closing was
not enabled.

Pedestrian Start during the partial opening phase


This menu allows fixing the control unit conduct in case it receives a
Pedestrian Start command during the partial opening phase.

PAUS The gate stops and goes to pause.


ChiU the gate immediately starts closing.
no the gate goes on with the opening phase (command is ignored).

 WARNING: a Start command in any phase of partial opening will


cause the total opening; the Start Pedestrian command is always
ignored during a total opening.

42
Automatic closing
During the automatic operation, the control unit will automatically close
the gate when a set-up time expires.
The Start command, if enabled by St.PA menu, allows closing the gate
before the set up time expires.
In semi-automatic operation, that is to say, if the automatic closing

ENGLISH
function is disabled by setting the value to zero ('no' will be displayed),
the gate can be closed through the start command only: in this case,
St.PA menu setup will be ignored.
If the control unit receives a Stop command when the gate is in pause,
it will automatically pass to the semi-automatic operation.

Closing after transit


During the automatic operation, the pause count down starts from the
set up value each time a photocell operates during the pause.
If the photocell operates during the opening time, this time will be
immediately stored as pause time.
This function allows having a fast closing as soon as transit through the
gate is completed, therefore, a time shorter than Ch.AU is
generally used.
Ch.AU will be used when ‘no’ is set up.
As for semi-automatic operation, this function is not active.

Pause after transit


In order to let the gate open for the shortest possible time, it is possible
to stop the gate once the passage before the photocells is detected. If
the automatic working is enabled, the time of the pause is Ch.tr.
If the photocells are type 1 and type 2, the gate enters the phase of
pause only after the detections before both the photocells.

Courtesy lights
This menu allows setting the automatic operating of the courtesy
lights during the opening cycle of the gate.

NOTE: If the output is used to drive a flashing light (with internal


flasher) select CiCL.

t.LUC the relay is enabled at the receiving of a control of start


or pedestrian start; choosing this option, a submenu is
entered – it allows to set the length of the activation of
the relay from 0.0” to 20’0 (default 1’00). At the time
limit, the relay is disabled.
no the relay of the courtesy lights is not automatically
activated
CiCL the relay is activated during the motion of the gate;
when the gate stops (closed or open) the relay is on all
the time t.LUC long (set in the submenu t.LUC)
If the option LP.PA is activated, the relay is on also
during the pause time

43
Auxiliary channel
This menu allows setting the operating of the relay of the lighting of the
courtesy lights by means of a remote control stored on the channel 4 of
the receiver.
ENGLISH

tiM the relay is activated receiving the transmission of the


remote control; it is disabled after the time set for the
parameter t.LUC inside the menu LUCi
Mon the relay is activated for all the length of the
transmission of the remote control. Releasing the key of
the remote control the relay is deactivated
biSt the status of the relay changes at each transmission of
the remote control

Low Voltage Output Setup


This menu allows you to set the operation of the low voltage output.

no Not used
FLSh Flasher operation (fixed frequency)
WL Indicator light operation: Indicates the status of the gate in
real-time. The type of blinking indicates the four possible
conditions:
- GATE STOPPED: Light off
- GATE IN PAUSE: the light is on, fixed
- GATE OPENING: the light blinks slowly (2 Hz)
- GATE CLOSING: the light blinks quickly (4 Hz)

Blinker during pause time


Blinker usually operates during the gate motion only; however, if this
function is enabled, blinker will be on during the pause time too.

The flasher may be either in the device connected to the LUCI output
(setting the CiCL parameter in the LUCi menu) or the device connected
to the low voltage output (setting the FLSh parameter in the SPiA
menu).

Start input function


This menu allows selecting input operation modes (see paragraph
“Activation inputs”):

StAn Start and Pedestrian Start input standard operation,


according to menu setups.

no Start inputs from terminal board are disabled. Radio inputs


operate in StAn mode.

AP.CH Start impulse always controls the opening phase, Pedestrian


Start always controls the closing phase.

PrES Manned operation; the gate will open as long as the Start
input stays closed and it will close as long as Pedestrian
Start stays closed.

oroL Timer-operation; the gate stays open while the Start input or
Pedestrian Start input is closed; as soon as the contact
opens, the pause count down will start.
44
Stop Input
This menu permits to select the functions associated to the
command of STOP.

no The input STOP is not available.

ENGLISH
ProS The input STOP stops the gate: pressing the command START
the gate continues the motion.
invE The command STOP stops the gate: at the next START the
gate starts moving in the opposite direction.

The setting of parameter STOP determines also in which direction the


gate will move at the next START, if it has stopped because of an
intervention of the safety edges or the obstacle sensor. If you set no, the
START command restarts the motion in the same direction.

NOTE: during the pause, the STOP command will stop the pause time
count, the next START command will always close the gate.

Photocell 1 input
This menu allows enabling the input for type 1 photocells, that is to say,
photocells active both during the opening and closing phase (see
paragraph “Installation”).

no Input disabled (ignored by the control unit).


No jumper with the common is required.
AP.CH Input enabled.

Photocell 2 input
This menu allows enabling the input for type 2 photocells, that is to say,
photocells non active during the opening phase (see paragraph
“Installation”).

no Input disabled (ignored by the control unit).


No jumper with the common is required.
CF.CH Input enabled even at standstill gate too: the opening
movement does not start if photocell is interrupted.
CH Input enabled for the closing phase only.
Warning: if you select this option, you must disable photocell
test.

Test of the photocells


In order to achieve a safer operation for the user, the unit performs a
photocells operational test, before a normal working cycle.
If no operational faults are found, the gate starts moving.
Otherwise, it will stand still and the flashing light will stay onfor 5 sec.
The whole test cycle lasts less than one second

 WARNING: V2 suggests to keep activated the test of the


photocells in order to grant a higher safety of the system.

45
Safety ribbon 1 input
This menu allows enabling the input for type 1 safety ribbon, that is to
say, fixed ribbons (see paragraph “Installation”).
ENGLISH

no input disabled (ignored by the control unit).


AP Input enabled during the opening and disabled during the
closure
APCH Input enabled in opening and closure

Safety ribbon 2 input


This menu allows enabling the input for type 2 safety ribbon, that is to
say mobile ribbons (see paragraph “Installation”).

no input disabled (ignored by the control unit).


No jumper with the common is required.
Ch Input enabled during closure and disabled during opening
APCH Input enabled in opening and closure

Test of the safety edges


This menu allows setting the method of control of the safety edges
working.

no Test disabled
Foto Test enabled for optical safety edges
rESi Test enabled for conductive rubber safety edges

 WARNING: V2 suggests to keep activated the test of the


photocells in order to grant a higher safety of the system.

End of Stroke Inputs


The CITY2+ controller permits the connection of 4 normally closed (NC)
limit switches that are activated by the gates movement and indicate to
the controller if the gate has reached the completely open or closed
position.

Si end of stroke inputs are enabled


no end of stroke inputs are disabled

46
Encoder Input
The CITY2+ controller allows connection to encoders that provide the
controller with the position of the gate panels

ENGLISH
Si The encoder inputs are enabled
no The encoder inputs are disabled

Anti-skid
When an opening or closing operation is interrupted by a command or
for the intervention of the photocell, the set-up time for the opposite
movement would be excessive, so the control unit operates the motors
only for the time necessary to recover the actually covered journey. This
could be not sufficient, particularly in the case of very heavy gates, as
because of the inertia at the inversion moment the gate runs an extra
space in the previous direction that the control unit is not able to take
into account.
If after an inversion the gate does not return exactly to the starting
position, it is possible to set an anti-skid time that is added to the time
calculated by the control unit in order to recover the inertia.

 WARNING: When the encoders are installed and enabled, it is not


necessary to enable the anti-skid as the controller is able to detect when
the gate is in the maximum open or closed position.

End of Programming
This menu allows to finish the programming (both default and
personalized) saving the modified data into memory.

no Further corrections to carry out: do not quit the programming.


Si End of programming.

THE INSERTED DATA HAVE BEEN MEMORIZED: THE CONTROL


UNIT IS READY TO BE USED.

47
READING OF CYCLE COUNTER DOWN key, the current counter value will be rounded up or
down to thousands, any following pressure will have the setup
CITY2+ control unit counts the completed opening cycles of the be increased or decreased of 1000 units. The previous
gate and, if requested, it shows that service is required after a displayed count will get lost.
fixed number of cycles.

There are two counters available:


Signal of service required
• A totalizing counter for completed opening cycles that
ENGLISH

As soon as the counter of cycles before the next request for


cannot be zeroed (option “tot” of item “Cont”)
service is zero, the control unit shows the request for service
• A downward counter for the number of cycles before the
through an additional 5-second pre-blinking.
next request for service (option “SErv” of item “Cont”). This
counter can be programmed according to the desired value.

The side scheme shows how to read the totalizing counter, how
 WARNING: service operations shall be carried out by
to read the number of cycles before the next service is required as qualified staff only. This signal will be repeated at each
well as how to program the number of cycles before the next opening cycle, until the installer enters into the counter reading
request for service (as for the example shown, the control unit and setup menu, and possibly programs the number of cycles
completed no. 12451 cycles and there are no. 1322 cycles before after which the next service will be requested.
the next service request. In case no new value is setup (that is to say that the counter
value is left at zero), the signalling function for the service
Area 1 is the reading of the total number of completed cycles; request will be disabled and no signal will be repeated anymore.
through Up and Down keys, you can alternate the display of
thousands or units.

Area 2 is the reading of the number of cycles before the next


request for service: its value is rounded down to the hundreds.

Area 3 is the setup of this latter counter; if you press once UP or

48
OPERATION DEFECTS Error 4
When a Start command is given and the
This paragraph shows some possible operation defects, along gate does not open (or does a partial
with their cause and applicable remedy. opening) and the display shows:

MAINS led does not switch on It means that the end of stroke is damaged or that the wiring
It means that there is no voltage on CITY2+ control unit card. that connects the sensor to the control unit is broken.
1. Before acting on the control unit, disconnect through the

ENGLISH
Change the end of stroke sensor or the broken wiring.
disconnecting switch on the power line and remove the If the error persists send the control unit to V2 S.p.A. for repair.
power supply terminal.
2. Be sure that there is no voltage break upstream the control Error 5
unit. Once given a start control, the gate does
3. Check whether the fuse is burnt-out, if so replace it with not open and the display shows:
same value.
It means that the test of the safety edges failed.
OVERLOAD led is on Check that the menu of the test of safety edges (CO.tE) have
It means that there is an overload on accessory power supply. been set correctly.
1. Remove the extractable part containing terminals K1 to K10. Check that the safety edges enabled from the menu are
OVERLOAD led will switch off. installed.
2. Remove the overload cause.
3. Reinsert the terminal board extractable part and check that Error 7
this led is not on again. This indicates an error in the encoders'
operation.
Too long pre-blinking
When a Start command is given and the blinker switches on There are three possible causes:
immediately but the gate is late in opening, it means that the 1. With the encoders connected, even if they are not enabled,
setup cycle count down expired and the control unit shows that for a few instants after movement of a gate panel. This means
service is required. that the connection to the encoder for that gate panel is
reversed. Exchange terminal K1 with K2, or K3 with K4
FLAT BATTERY 2. With the encoders enabled, once a START command is
In absence of line voltage the gate does received: This means that the encoders have not been
not open and on the display flashes the initialized. For the encoders to operate correctly, the
message: self-learning procedure must be performed.
3. With the encoders enabled and initialized, a few seconds after
This means that the buffer batteries do not have sufficient power movement begins: This means that an encoder is correctly
to open the gate. It is necessary to wait for the return of mains operating. Encoder malfunction or broken connection.
power, or to replace the drained batteries with new ones.
Error 8
Error 1 When executing a self-learning function
The following writing appears on display the control is refused and the display
when you exit from programming: shows:
It means that the setting of the control unit is not compatible
It means that changed data could not be stored. with the requested function. In order to execute the self-learning
This kind of defect has no remedy and the control unit must be it is necessary that the Start inputs are enabled in standard
sent to V2 S.p.A. for repair. mode; to survey the currents of the motor it is also necessary
that the length of the opening and closure are at least of 7,5
Error 2 second.
When a Start command is given and the
gate does not open and the display shows: Errore 9
When you are trying to change the control
It means that triac test failed. unit setups and the the display shows:
Before sending the control unit to V2 S.p.A. for repair, be sure
that motors have been properly connected. It means that programming was locked by means of the
programming lock key (code CL1).
Error 3 To change the settings it is necessary to insert in the
When a Start command is given and the connector of the ADI interface the same key used to activate
gate does not open and the display shows: the programming lock.

It means that the photocell test failed.


1. Be sure that no obstacle interrupted the photocell beam
when the Start command was given.
2. Be sure that photocells, as enabled by their relevant menus,
have been installed actually.
3. If you have photocells 2, be sure that Fot2 menu item is on
CF.CH.
4. Be sure that photocells are powered and working; when you
interrupt their beam, you should hear the relay tripping.

49
CITY2+ FUNCTION TABLE
MEMO
DISPLAY DATA DESCRIPTION DEFAULT
DATA
t.AP1 0.0’’ ÷ 5’.00 Open time gate panel 1 22.5’’
t.AP2 0.0" ÷ 5’.00 Open time gate panel 2 22.5’’
ENGLISH

t.APP 0.0" ÷ 1’.00 Open time pedestrian gate 6.0’’


t.Ch1 0.0" ÷ 2’.00 Close time gate panel 1 23.5’’
t.Ch2 0.0" ÷ 2’.00 Close time gate panel 2 23.5’’
t.ChP 0.0" ÷ 1’.00 Close time pedestrian gate 7.0’’
t.C2P 0.5" ÷ 2’.00 Close time gate panel 2 during pedestrian cycle 2.0’’
no - Function disabled
r.AP 0.0"÷ 1’.00 Open gate delay 1.0’’
r.Ch 0.0" ÷ 1’.00 Close gate delay 3.0’’
t.SEr 0.5" ÷ 1’.00 Electric lock activation time 2.0’’
no - The lock is not excited (corresponds to a value of 0)
SEr.S Si / no Silent Locking Mode Si
t.ASE 0.0" ÷ 1’.00 Advance lock time 1.0’’
t.inv 0.5" ÷ 1’.00 Pressure surge time no
no - Pressure surge disabled (corresponds to a value of 0)
t.PrE 0.5" ÷ 1’.00 Advance Blinking Time 1.0’’
no - Advance blinking disabled (corresponds to a value of 0)
Pot1 30 ÷ 100% Power motor 1 100
Pot2 30 ÷ 100% Power motor 2 100
Po.r1 0 ÷ 70% Power motor 1 during slow-down phase 50
Po.r2 0 ÷ 70% Power motor 2 during slow-down phase 50
P.bAt Si / no Maximum motor power during battery operation Si
SPUn Si / no Breakaway Si
rAM 0÷6 Starting ramp 4
SEn1 0.0A ÷ 14.0A Obstacle Sensor for Motor 1 0.0A
SEn2 0.0A ÷ 14.0A Obstacle Sensor for Motor 2 0.0A
t.rAL 0.5"÷22.5" Slow-down time (b-2) no
no - Slow-down disabled
t.CVE 0.0" ÷ 3.0" Fast close time after slow-down during closure 0.0’’
St.AP Start on open PAUS
no - The START command is not received
ChiU - The gate closes
PAUS - The gate goes into pause
St.Ch Start on close StoP
Stop - The gate finishes the cycle
APEr - The gate opens again
St.PA Start on pause ChiU
no - The START command is not received
ChiU - The gate closes
SPAP Pedestrian start on open PAUS
no - The P. START command is not received
ChiU - The gate closes
PAUS - The gate goes into pause
Ch.AU Automatic re-close. no
no - Automatic re-close is activated (corresponds to a value of 0)
0.5"÷ 20.0' - The gate recloses after the set time
Ch.tr Closure after passage no
no - Closure after passage disabled (load Ch.AU)
0.5"÷ 20.0' - The gate recloses after the set time
PA.tr no / Si Pause after passage no
CITY2+ FUNCTION TABLE
MEMO
DISPLAY DATA DESCRIPTION DEFAULT
DATA
LUCi Courtesy lights CiCL
t.LUC - Timed operation (from 0 to 20 min)

ENGLISH
no - Function disabled
CiCL - On for the entire cycle duration
AUS Auxiliary channel Mon
tiM - Timed operation (from 0 to 20 s)
biSt - Bistable operation
Mon - Monostable operation
SPiA Low Voltage Output Setup no
no - Not used
FLSh - Flashing light operation
W.L. - Indicator light operation
LP.PA no / Si Flasher in pause no
Strt START Input
no - Inputs from terminal strip disabled
StAn - Standard operation
AP.CH - Separate open and close commands
PrES - Manned operation
oroL - Timer Operation
StoP STOP Input no
no - The input is disabled: the STOP command is not received
invE - The STOP command stops the gate: The next START inverts the direction
ProS - The STOP command stops the gate: The next START does not invert the direction
Fot 1 PHOTO 1 Input no
APCh - Acts like active photocell on open and close
no - Disabled
Fot 2 PHOTO 2 Input CHCh
CFCh - Acts like active photocell on close and with gate stopped
no - Disabled
Ch - Functions like active photocell only on close
Ft.tE no / Si Photocells test no
CoS1 Safety device 1 input (stationary safety device) no
no - Input not enabled
AP - Input active only on open
APCH - Input active on open and close
CoS2 Safety device 2 input (mobile safety device) no
no - Input not enabled
CH - Input active only on close
APCH - Input active on open and close
Co.tE Operational test of safety devices no
no - Test disabled
Foto - Test enabled for optical safety devices
rESi - Test enabled for resistive rubber safety devices
FC.En no / Si Limit switch inputs no
EnCo no / Si Encoder Input no
ASM 0.5” ÷ 3.0” Anti-skid no
no - Function disabled
FinE End of programming no
no - Do not exit programming menu.
Si - Exit from programming menu and save the parameters set.
51
ENGLISH

52
INDEX

FRANÇAIS
CONSEILS IMPORTANTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .54
DÉCLARATION DE CONFORMITÉ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .54
CARACTÉRISTIQUES TECHNIQUES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .54
DESCRIPTION DE LA CENTRALE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .54
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .55
ALIMENTATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .55
SORTIE EN BASSE TENSION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .55
LUMIERES DE COURTOISIE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .55
PHOTOCELLULE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .55
BARRES PALPEUSES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .56
CERRURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .56
FIN DE COURSE ET ENCODEUR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .56
STOP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .57
ENTREES DE COMMANDE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .57
RECEPTEUR EMBROCHABLE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .57
ANTENNE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .58
INTERFACE ADI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .58
TABLEAU BRANCHEMENTS ELECTRIQUES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .58
PANNEAU DE CONTROLE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .60
EMPLOI DES TOUCHES DOWN ET UP POUR LA PROGRAMMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .60
CONFIGURATION RAPIDE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .60
CHARGEMENT DES PARAMÈTRES PAR DÉFAUT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .61
AUTO-APPRENTISSAGE DES TEMPS DE TRAVAIL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .61
FONCTIONNEMENT DU DÉTECTEUR OBSTACLES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .62
CONFIGURATION DE L'ARMOIRE DE COMMANDE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .62
LECTURE DU COMPTEURS DE CYCLES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .74
ANOMALIE DE FONCTIONNEMENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .75
TABELLA FUNZIONI CITY2+ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .76

53

You might also like