I TRAK
I TRAK
I TRAK
Original Instructions
iTRAK System
Bulletin 2198T
Important User Information
Read this document and the documents listed in the additional resources section about installation, configuration, and
operation of this equipment before you install, configure, operate, or maintain this product. Users are required to
familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws,
and standards.
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are
required to be carried out by suitably trained personnel in accordance with applicable code of practice.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may
be impaired.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from
the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or
liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or
software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation,
Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous
environment, which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property
damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
IMPORTANT Identifies information that is critical for successful application and understanding of the product.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous
voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may
reach dangerous temperatures.
ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to
potential Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL
Regulatory requirements for safe work practices and for Personal Protective Equipment (PPE).
Table of Contents
Preface
Summary of Changes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Conventions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Appropriate Use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Chapter 1
Start About the iTRAK System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Motor Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Mover. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Support Frame . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Power Supplies. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
iTRAK Bus Conditioner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Gateway . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Digital USB I/O Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Catalog Number Explanation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Risk Assessment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
General Assembly Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Machine Guarding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Avoid Accidents, Injury, and Property Damage . . . . . . . . . . . . . . 21
Avoid Electrical Shock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Pinch Point Hazard. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Protection Against Contact with Hot Parts. . . . . . . . . . . . . . . . . . 22
Protection Against Magnetic and Electromagnetic
Fields During Installation and Use . . . . . . . . . . . 22
Safe Magnet Handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Chapter 2
Track Installation Install the Track . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Before You Begin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Mount an Oval Track. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Install the Lubrication System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
What You Need . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Mount the Lubricator Pumps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Wiring Lubrication Pump. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Lubrication Pump Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Lubrication Volume Calculation. . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Chapter 3
Connect Your iTRAK System to a Typical iTRAK System with an iTRAK Power Supply . . . . . . . . . . . 37
Kinetix 5700 iTRAK Power Design Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Determine the Number iTRAK Power Supplies Required . . . . 40
Supply
Output Bus Current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
24V Control Power. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
iTRAK Power Supply Output Power Connections . . . . . . . . . . . 41
Maximum iTRAK Power Supply to iTRAK Module
Cable Length . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Choose a 2198-Pxxx Kinetix 5700 Power Supply . . . . . . . . . . . . . 43
Shunting Capacity. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Kinetix 5700 System Design. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Cabinet. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Ethernet Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Wire the iTRAK System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Using Multiple iTRAK Power Supplies . . . . . . . . . . . . . . . . . . . . . 45
iTRAK Power Supply Connector Data . . . . . . . . . . . . . . . . . . . . . . . . . 48
Wiring Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Wire the iTRAK Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Wire the Digital Input Connector . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Wire the iTRAK PS Ready (IR) connector . . . . . . . . . . . . . . . . . . 53
Wire the iTRAK Power Supply DC Bus and Control
Power Output Connectors . . . . . . . . . . . . . . . . . . 54
Apply the iTRAK Power Cable Shield Clamp . . . . . . . . . . . . . . . . . . . 55
Wire the Digital USB I/O Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Wire the Gateway . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
iTRAK Power Supply Wiring Example . . . . . . . . . . . . . . . . . . . . . . . . . 59
Cable Preparation for iTRAK Power Supply Output
Power Cables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Logix Designer Application Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Chapter 4
Install Your System with a Typical System Configuration Using a PCM . . . . . . . . . . . . . . . . . . . . 65
Power Control Module About the Power Control Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
PCM Status Indicators. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
PCM Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
PCM Connector Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
About the Gateway. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Plan Your System Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Install the Power Control Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Install the Gateway Enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Connect Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Chapter 5
Power on Your System Before You Power On the Track. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Identify Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Identify Firmware Revision. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Configure and Customize Project File. . . . . . . . . . . . . . . . . . . . . . . 78
Apply Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Kinetix 5700 iTRAK Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . 78
Power Control Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Commission with Programming Manual . . . . . . . . . . . . . . . . . . . . . . . . 82
Chapter 6
Maintenance Before You Begin. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Preventive Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Cleaning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Add or Replace Components. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
Install or Remove a Position Magnet Assembly. . . . . . . . . . . . . . . 84
Magnet Plate Assembly Installation . . . . . . . . . . . . . . . . . . . . . . . . . 86
Install or Replace a Mover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Replace a Straight Motor Module . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
Replace a Curved Motor Module . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Update Gateway Firmware. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
Firmware Update Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . 104
Downgrading Firmware. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
Update Motor Module Firmware. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
Lubrication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Initial Lubrication. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
Lubrication During Normal Operation . . . . . . . . . . . . . . . . . . . . . . . . 106
Replace Mover Lubrication Wipers . . . . . . . . . . . . . . . . . . . . . . . . 106
Replace Lower Mover Bearing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
Circuit Breakers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
Chapter 7
Troubleshooting Errors Codes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
Chapter 8
Functional Safety Important Safety Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
Category 3 Requirements according to EN ISO 13849-1 . . . . . . . . 121
Stop Category Definition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
Performance Level and Safety Integrity Level (SIL). . . . . . . . . . . . . . 122
Safety Distance Calculations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
Functional Safety Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
Considerations for Category 1 Stop. . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
Overall System Stopping Performance . . . . . . . . . . . . . . . . . . . . . . . . . 123
Schematic and Block Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
iTRAK Power Supply. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
Power Control Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
Chapter 9
Compatibility Motor Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
Movers and Magnets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128
Gateways . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128
Power Supplies. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128
Controllers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128
Appendix A
Label Placement Safety Labels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133
This manual is intended for engineers or technicians that are directly involved
with the design, installation, and wiring of the iTRAK system, and
programmers who are directly involved in the operation, field maintenance,
and integration of this system with the EtherNet/IP™ communication module
or controller.
If you do not understand the basics of the iTRAK system, contact your
Rockwell Automation sales representative for information on available training
courses.
Summary of Changes This manual contains new and updated information as indicated in the
following table.
Topic Pages
Corrected pin numbers in the table entitled IDC and ICP Connector Wiring. 55
Corrected pin numbers in the wiring diagram entitled Connecting an iTRAK Power Supply to a System. 59
Corrected pin numbers in the wiring diagram entitled Kinetix® 5700 iTRAK Power Supply Safety Circuit 124
Block Diagram.
Conventions These conventions are used throughout this manual: Bulleted lists provide
information, not procedural steps. Numbered lists provide steps or hierarchical
information.
Appropriate Use Read and understand the safety instructions before using the iTRAK system
and review Label Placement on page 129.
ATTENTION: Incorrect use of the products can cause personal injury and
property damage.
Additional Resources These documents contain additional information concerning related products
from Rockwell Automation.
Resource Description
iTRAK System Technical Data, publication 2198T-TD001 Product specifications for Rockwell Automation iTRAK system components, with
performance, environmental, certifications, load force, and dimension drawings.
Product specifications for Kinetix Integrated Motion over the EtherNet/IP network,
Kinetix® Servo Drives Specifications Technical Data, publication KNX-TD003 Kinetix 5700 iTRAK Power Supply, Integrated Motion over sercos interface, EtherNet/IP
networking, and component servo drive families.
Kinetix 5700 iTRAK Power Supply Installation Instruction, publication 2198T-IN001 Provides information for wiring and connecting the Kinetix 5700 iTRAK power supply to
the iTRAK system.
iTRAK System Programming Manual, publication 2198T-PM001 Provides information on how to commission and program an iTRAK system.
3D CAD Models of iTRAK Components 2198T-3DCAD.zip. Provides 2D outline, assembly, and system drawings, STEP files for the movers and motor
https://motionanalyzer.rockwellautomation.com/Products/iTrak modules, and hyper links to complete systems STEP files.
ControlLogix® System User Manual, publication 1756-UM001 Details how to configure, program, and operate a 1756 ControlLogix system, and provides
technical specifications
System Design for Control of Electrical Noise Reference Manual, Information, examples, and techniques that are designed to minimize system electrical
publication GMC-RM001 noise failures.
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1 Provides general guidelines for installing a Rockwell Automation industrial system.
Product Certifications website, http://www.rockwellautomation.com/global/ Provides declarations of conformity, certificates, and other certification details.
certification/overview.page
Start
Use this chapter to become familiar with the design, installation, and safety
requirements for iTRAK® systems.
Topic Page
About the iTRAK System 9
Motor Module 12
Mover 14
Support Frame 15
Power Supplies 16
iTRAK Bus Conditioner 16
Gateway 17
Digital USB I/O Module 17
Catalog Number Explanation 18
Safety Information 19
About the iTRAK System The iTRAK system is composed of motor modules, mounting plates, bearing
rails, and movers. The motor modules are an integrated drive motor system
with feedback. Mounting plates can be attached to the sides of motor modules
and bearing rails can be attached to the mounting plates. Movers have
independent linear motor magnets and bearings, and multiple movers can be
operated on a motor module at any time. Movers can be synchronized or
independently controlled, however they are programmed.
The motor modules are available with both straight and curved motors, and
more movers can be added as the system grows. The movers can be stopped and
positioned on the curves with high accuracy. When the curves are applied to
create an oval, new machine shapes and dynamic performances are possible.
The iTRAK system can be arranged and mounted in many configurations,
including horizontal carousel, vertical over-under, and stand-up configurations.
The system is modular, scalable, and can be expanded to well over 10 meters.
Even on large systems, each mover still retains independent servo control. The
system can also be built into other geometries such as rectangles.
The iTRAK system can produce high speeds and high forces. The different
combinations of magnet sizes and motor coil sizes produce nine different force
speed options.
3 5 6
7
9 8
10
11
12
You can power your system with a Power Control Module (PCM), which is a
fixed output power supply, or a scalable Kinetix 5700 power supply system.
The typical system configuration for a PCM powered iTRAK system is shown
in Typical System Configuration Using a PCM on page 65. The typical system
configuration for Kinetix 5700 power supply powered iTRAK system is shown
in Typical iTRAK System with an iTRAK Power Supply on page 37.
Motor Module Your system has two types of motor modules. Figure 2 shows the features of the
straight motor module and Figure 3 shows the features of the curved motor
module.
2198T-L16-T0504-AOON-2E1E-NS,
Straight Motor Module is shown. 1
8
3
7
4
6
5
2198T-L16-T0504-B09R-2E1E-NS,
Right Curved Motor Module is shown. 3
2
8 1
6 7
DRIVE ENABLED
DANGER
Hazardous Voltage Inside
Power Off. Lockout/Tagout and
wait 5 minutes
WARNING
Magnetic Field
Can be harmful to
pacemaker wearers
CAUTION Right
Metal Surfaces May be Hot
Do not touch
Power Off. Allow to cool down
CAUTION
PINCH POINTS NEARBY
Sudden motion. Stand Clear
Power Off. Lockout/Tagout
B624958
Mover Movers are available in nine sizes, each with their own force-speed curve. Your
system only has one size of mover installed.
4
3
2
1
Shown here is a 2198T-VT0510-A mover and position magnet assembly. Your mover can look
slightly different, but will have similar components.
Support Frame The iTRAK system track has a frame to support the motor modules and
bearing rails. Figure 7 shows the main components that are used to construct a
single-base plate support structure.
1
1
2
Item Description
1 Curved top plate
2 Straight top plate
3 Base plate
4 Spine bar
5 Mounting plate
6 Notched mounting plate
Systems that are greater that 2.4 m (8.2 ft) in length use a multi-plate design for
items 2, 3, 4. See https://ramotionanalyzer.blob.core.windows.net/3dmodels/
2198T-3DCAD.zip for more detail.
Power Supplies The iTRAK system can be powered using a preconfigured Power Control
Module (PCM) with fixed output wattage or with a scalable Kinetix 5700
iTRAK power supply as part of a Kinetix 5700 system. Details and installation
instructions on for the use of the two power supplies are covered in Chapter 3
and Chapter 4.
iTRAK Bus Conditioner The bus conditioner module is mounted near the iTRAK for each power cable
when using the iTRAK power supply. The packaging for the bus conditioner is
intended to be mounted in the same environments as the iTRAK system. It
incorporates additional filtering and capacitance to improve the dynamic servo
response and increase reliability of the system.
Item Description
1 Cable and connector to track system
2 Vent
3 Module
4
3
1
2 2
Digital USB I/O Module The digital USB I/O module provides an interface between the power supply
that is used by your system and the gateway. This module is integrated in a
gateway cabinet and must be included in your system when using Kinetix 5700
iTRAK power supply.
4
1 3
The status indicator indicates powers and data transmissions. When the status
indicator is in an illuminated steady green state, the module is successfully
connected to the gateway computer and the operating system has detected and
configured it. When the status indicator blinks continuously, there is data
being transmitted over the USB bus.
Catalog Number Explanation Use the following key to identify your iTRAK system and its options.
Safety Information Follow all safety information that is presented in this section while working
with or near an iTRAK system.
The iTRAK system is partly completed machinery. This machinery must not
be put into service until the final machinery into which it is to be incorporated
has been declared in conformity with relevant provisions of the Machinery
Directive.
Risk Assessment
A risk assessment must be prepared for the installation of the machine, within
its application conditions, and with the system components installed. As a
result of the risk assessment, you must provide for monitoring functions and
higher-level measurement for personal safety. The safety regulations applicable
to the installation of the machine must be considered. Unintended machine
movements or other malfunctions are possible if safety devices are disabled,
bypassed, or not activated.
Machine Guarding
The movers can have high acceleration and carry application loads. The movers
experience more acceleration in the curved sections of the track due to vector
directional changes. Machine guards and safety enclosures must be
implemented to offer protection to personnel. The shielding and enclosure
must be designed to help protect against tangential projectiles along the system
perimeter.
ATTENTION: The PCM, motor modules, Kinetix 5700 iTRAK power supply,
and the bus conditioner require 5 minutes to discharge before electrical you
handle wire and cable connections.
See Safety Label Placement on page 129 for location of Hot Surface label.
• Do not touch hot surfaces such as brake resistors, heat sinks, power
supply units, drive controllers, motors, windings, and laminated cores.
• Temperatures of the track motor-stator covers can be higher than 60° C
(140° F) during or after operation.
• After powering down the motor modules, let them cool before
touching. Motor modules can require 140 minutes to cool.
• After powering down switching chokes, power supply units, and drive
controllers, let them cool for 15 minutes before touching.
See Safety Label Placement on page 129 for location of series A motor module
labels.
The motor modules, when in use, and permanent motors magnets pose a
danger to persons with heart pacemakers, metal implants, and hearing aids.
ATTENTION: The mover uses strong magnets. There is a risk of health hazard
for persons with heart pacemakers, metal implants, and hearing aids while
in proximity of magnetic and magnetic-field producing components. The
magnetic field that is generated can disrupt the functionality of automatic-
implantable cardioverter defibrillators (AICD). People with cardiac
pacemakers must not work near the iTRAK system.
The movers of the iTRAK system contain components with strong magnetic
fields. The motor modules also produce magnetic fields while movers are being
commanded. This section shows the strength of the field for an enabled mover,
uninstalled mover, and an uninstalled position magnet.
When motion is present on the system, the magnetic field does not exceed
0.05 mT at 500 mm (19.7 in.) in any direction from the track. Ferrous metals
can influence the magnetic field direction and strength. For the most accurate
data, measure the magnetic field strength on a track that is installed in its final
configuration.
To avoid the interaction with magnetic field, Table 6 shows the magnetic field
strength versus distances from the center point of an uninstalled mover.
Table 6 - Magnetic Field Strength of an Uninstalled Mover
Cat. No. Magnetic Strength
0.05 mT 0.1 mT 0.5 mT
L (+/–) W+ W- H (+/–) L (+/–) W+ W- H (+/–) L (+/–) W+ W- H (+/–)
mm (in.) mm (in.) mm (in.) mm (in.) mm (in.) mm (in.) mm (in.) mm (in.) mm (in.) mm (in.) mm (in.) mm (in.)
2198T-VT0505-A 180 (7.1) 145 (5.7) 310 (12.2) 90 (3.5) 140 (5.5) 120 (4.7) 130 (5.1) 70 (2.8) 90 (3.5) 65 (2.6) 95 (3.7) 55 (2.1)
2198T-VT0510-A 215 (8.5) 175 (6.9) 375 (14.8) 140 (5.5) 180 (7.1) 135 (5.3) 260 (10.2) 120 (4.7) 125 (4.9) 70 (2.8) 140 (5.5) 55 (2.1)
2198T-VT0515-A 220 (8.7) 190 (7.5) 320 (12.6) 140 (5.5) 190 (7.5) 145 (5.7) 190 (7.5) 130 (5.1) 140 (5.5) 70 (2.8) 100 (3.9) 50 (2.0)
2198T-VT1005-A 170 (6.7) 200 (7.9) 230 (9.1) 165 (6.5) 120 (4.7) 150 (5.9) 160 (6.3) 145 (5.7) 70 (2.8) 60 (2.4) 110 (4.3) 75 (3.0)
2198T-VT1010-A 230 (9.1) 200 (7.9) 360 (14.2) 165 (6.5) 200 (7.9) 150 (5.9) 255 (10.0) 150 (5.9) 150 (5.9) 70 (2.8) 135 (5.3) 80 (3.1)
2198T-VT1015-A 260 (10.2) 200 (7.9) 300 (11.8) 170 (6.7) 220 (8.7) 155 (6.1) 200 (10.0) 150 (5.9) 150 (5.9) 85 (3.3) 120 (4.7) 80 (3.1)
2198T-VT1505-A 180 (7.1) 255 (10.0) 310 (12.2) 240 (9.4) 140 (5.5) 180 (7.1) 190 (7.5) 220 (8.7) 90 (3.5) 65 (2.6) 125 (4.9) 95 (3.7)
2198T-VT1510-A 245 (9.6) 225 (8.9) 375 (14.8) 190 (7.5) 220 (8.7) 165 (6.5) 260 (10.2) 180 (7.1) 175 (6.9) 70 (2.8) 140 (5.5) 105 (4.1)
2198T-VT1515-A 300 (11.8) 210 (8.3) 320 (12.6) 200 (7.9) 250 (9.8) 165 (6.5) 210 (8.3) 170 (6.7) 160 (5.9) 85 (3.3) 140 (5.5) 110 (4.3)
To avoid the interaction with magnetic field, Table 7 shows the magnetic field
strength versus distances from the center point of a mover that is installed on a
track.
Table 7 - Magnetic Field Strength of an Installed Mover, Enabled at Zero Speed
Cat. No. Magnetic Strength
0.05 mT 0.1 mT 0.5 mT
L (+/–) W H (+/–) L (+/–) W H (+/–) L (+/–) W H (+/–)
mm (in.) mm (in.) mm (in.) mm (in.) mm (in.) mm (in.) mm (in.) mm (in.) mm (in.)
2198T-VT0505-A 220 (8.7) 125 (4.9) 125 (4.9) 195 (7.7) 95 (3.7) 70 (2.8) 75 (3.0) 40 (1.6) 55 (2.2)
2198T-VT0510-A 250 (9.8) 95 (3.7) 130 (5.1) 210 (8.3) 60 (2.4) 120 (4.7) 120 (4.7) 20 (0.8) 55 (2.2)
2198T-VT0515-A 300 (11.8) 150 (5.9) 140 (5.5) 220 (8.7) 100 (3.9) 130 (5.1) 120 (4.7) 30 (1.2) 60 (2.4)
2198T-VT1005-A 330 (13.0) 125 (4.9) 170 (6.7) 175 (6.9) 95 (3.7) 130 (5.1) 75 (3.0) 40 (1.6) 70 (2.8)
2198T-VT1010-A 340 (13.4) 130 (5.1) 165 (6.5) 190 (7.5) 100 (3.9) 125 (4.9) 100 (3.9) 40 (1.6) 65 (2.6)
2198T-VT1015-A 360 (14.2) 130 (5.1) 170 (6.7) 290 (11.4) 105 (4.1) 130 (5.1) 130 (5.1) 40 (1.6) 105 (4.1)
2198T-VT1505-A 440 (17.3) 125 (4.9) 215 (8.5) 195 (7.7) 95 (3.7) 190 (7.5) 75 (3.0) 40 (1.6) 85 (3.3)
2198T-VT1510-A 430 (16.9) 165 (6.5) 200 (7.9) 210 (8.3) 140 (5.5) 130 (5.1) 120 (4.7) 60 (2.4) 70 (2.8)
2198T-VT1515-A 420 (16.5) 150 (5.9) 200 (7.9) 360 (14.2) 110 (4.3) 130 (5.1) 140 (5.5) 50 (2.0) 150 (5.9)
ATTENTION: The strong magnets of the mover can attract metal objects that
are in its proximity. When you handle and install, maintain distance between
the mover and ferrous metal mounting surfaces or structures.
Maintenance personnel must avoid the use of metallic tools and secure items
such as badge clips and other personnel effect that could be attracted to the
strong magnetic field.
Strong magnets can erase magnetic media. Never let credit cards or electronic
media contact or come near the mover or iTRAK system.
Wood or Cardboard
Magnet Plate
Magnet plates that are covered with a keeper are fairly safe to handle. They
must be kept at least 305 mm (12 in.) away from other magnet plates and other
ferrous metal parts such as hardware and tools.
Magnet plates without keepers must be kept a minimum of 1 m (3.3 ft) away
from other magnet plates and ferrous metal parts.
Notes:
Track Installation
Use this chapter to install an iTRAK® system track and lubrication system.
Topic Page
Install the Track 27
Install the Lubrication System 32
ATTENTION: Before you start the installation of the system, read the
See Safety Information on page 19 to reduce the risk of injury and property
damage.
Install the Track Use the following sections as guide for the installation of your preassembled
track. Your track can be made with more or less motor modules than are shown
in these procedures, but the same principles apply.
IMPORTANT Be sure that the lifting machinery can lift the load.
2. Make sure that the mounting surface supports the track evenly so that it
is free of mechanical stress and distortion.
If mounting the iTRAK track directly to mounting surface, make sure
that the mounting surface has a flatness of 0.05 mm per 300 x 3 00 mm
(0.002 in. per 11.8 x 11.8 in.). For systems longer than 2400 mm
(94.48 in.), we recommended that you use leveling feet between iTRAK
mounting plates and the mounting surface.
3. Unpack track sections within the crate so that the lifting slots are easily
accessible.
Lifting Slots
Lifting Slots
500.0
(19.7)
450.0 12.7
(17.7) (0.5)
90.0
(3.5) 45.0
(1.8)
25.0
(1.0) 4X 13.5 2X TAP M16 X 2.0
(0.53)
Mounting Plate
Mounting Surface
Leveling Feet
Install the Lubrication Catalog number 2198T-AL-SYS iTRAK Lubrication System, comes with a
coil of tubing to connect system fittings to the remotely located pumps and
System system fittings. The assembled pumps have push-to-connect connectors with
plugs. These plugs help prevent oil from leaking during shipment. You remove
these plugs when you are ready to connect the tubing. The pump fittings
contain a check valve to help prevent backflow when a replacement reservoir is
installed.
The reservoir uses a straight 1/4 BSPP thread. A sealing washer is supplied
with the support bracket. Do not use Teflon tape at this joint.
IMPORTANT The lubrication tubes that are provided in your iTRAK system are all of equal
length, the equal length splits the flow evenly and avoids back flow. Do not
modify their length.
For systems installed horizontally, the shared lube ports are for the top rail. For
systems installed vertically or stand up, the shared ports are for the highest
weep holes on the upper and lower rail.
3 2
1
2
1
4
5
4
7
3
Use a maximum of 10 m
(32.8 ft) tubing per pump.
5
4 12
11
10
7 8
5 6
45.4 95.25
(2.0) (3.75)
127.0
(5.0)
Connect the power cable the 24V I/O port of your controller.
1 BROWN
4 2 +24V
M8 2 WHITE Not Used
Connector 3 BLUE GND
4 BLACK
3 1 Not Used
An initial coating of oil is required on the entire track before operating the
iTRAK and auto lubrication systems.
IMPORTANT The mover wheels and lubrication wipers help to distribute the oil on the
track. The movers must be in motion when the pump is activated, otherwise
the oil drips away.
To calculate the volume of oil that is required to coat the running surfaces of
the iTRAK system with 0.025 mm (0.001 in.) thickness of oil.
Where,
Notes:
This chapter contains information for designing a system that uses the iTRAK®
power supply, including connectivity to the motor modules, the USB I/O, and
the gateway.
The iTRAK power supply derives bus power for and distributes control power
to the iTRAK system. It is a Kinetix® 5700 component, and is designed to work
with the 2198-Pxxx Kinetix 5700 power supplies as part of a Kinetix 5700
system.
Topic Page
Typical iTRAK System with an iTRAK Power Supply 37
Design Guidelines 40
iTRAK Power Supply Connector Data 48
Wiring Requirements 51
Wire the iTRAK Power Supply 52
Apply the iTRAK Power Cable Shield Clamp 55
Wire the Digital USB I/O Module 56
Wire the Gateway 57
iTRAK Power Supply Wiring Example 59
Cable Preparation for iTRAK Power Supply Output Power Cables 60
Logix Designer Application Support 63
Typical iTRAK System with an The iTRAK power supply interfaces to the gateway computer via a USB I/O
module. The gateway sends enable and disable signals and clears faults for
iTRAK Power Supply iTRAK power supply. The iTRAK power supply reports its status through a
relay that the USB I/O monitors.
There is sample code for Logix Designer that provides code for the gateway
computer to control the iTRAK power supply and interface to the rest of the
Kinetix 5700 system. See Logix Designer Application Support on page 63 for
more information.
EtherNet/IP
6 7
LNK1 LNK2 NET OK
5 Branch Protection,
2
Disconnect,
1
6 1
11
10
12
13
6 18
15 16 17
19 24
14
23
20
22
21
(1) See Kinetix 5700 Servo Drives User Manual. publication 2198-UM002, for more information on theses components.
For detailed information on the installation and how to wire the iTRAK power
supply into a Kinetix 5700 system, see the Kinetix 5700 Servo Drives User
Manual, publication 2198-UM002. The Kinetix 5700 Servo Drives User
Manual publication contains the information that is needed for using the other
parts of the Kinetix 5700 system, including:
• 2198-Pxxx Kinetix 5700 power supply
• Other Kinetix 5700 components that can be part of your Kinetix 5700
system
• Branch protection, disconnect, and line filter hardware
• Enclosure requirements
• Requirements for EMC and agency compliance
• Kinetix 5700 hardware mounting
• Bonding, wire routing, EMC considerations
As shown in Figure 18, components of the iTRAK power supply based system
include items that are listed in Table 10.
Table 10 - Components of an iTRAK System Using an iTRAK Power Supply
Item Description
iTRAK track Frame, bearings, motor modules, and movers.
iTRAK power supply, bus conditioner, Creates bus voltages and distributes control power for the iTRAK
and power cables system.
Kinetix 5700 power supply Creates the bus voltage that is used by other Kinetix 5700 modules,
including the iTRAK power supply.
Gateway and communication cables Controls and coordinates iTRAK motor modules, provides an interface
for them to the Logix system. In systems with an iTRAK power supply,
the gateway also enables, disables, and clears the faults for the iTRAK
power supply.
USB I/O module The USB I/O module serves as the physical input and output interface
between the iTRAK power supply and gateway computer.
Other Kinetix 5700 components and Other components that are used in your Kinetix 5700 system and other
related hardware hardware that is used for connecting the Kinetix 5700 system to three-
phase input power, as needed for branch protection, filtering,
contactor, and other functions.
Design Guidelines Use the following guidelines to help design the iTRAK system that includes an
iTRAK power supply.
The number of iTRAK power supplies can be scaled to match the power needs
of the iTRAK system closely. Additional iTRAK power supplies can be added
to the system as needed. The following factors impact the number of iTRAK
power supplies required for a system.
• Output Bus current
• 24V Control Current
• Cable length
If needed, See Using Multiple iTRAK Power Supplies for information on how
to connect a system with multiple iTRAK power supplies.
Sizing is the process of determining the required size and quantity of power
hardware components and motors modules for an application. Sizing an
iTRAK system involves many variables. Call a Rockwell Automation
application engineer to size your system.
The following criteria must be met for the operation of the system.
• Sufficient current can be delivered.
• The required voltage is maintained at the input to the iTRAK power
supply.
• Maximum iTRAK power supply input current is never exceeded.
• Maintaining an acceptable voltage drop from the iTRAK power supply
to the iTRAK motor modules, see the Maximum iTRAK Power Supply
to iTRAK Module Cable Length.
The iTRAK power supply uses 24V control power to run all low voltage
circuits and it distributes 24V control power to the iTRAK motor modules
that are connected to it.
Determine the amount of current required; add the current draw of the
iTRAK power supply to the current used by each of the motor modules that
are connected to that iTRAK power supply. Make sure that you include all
iTRAK motor modules that are connected to both the A and B outputs. When
designing the system, be sure to account for the 16 A pass through limit of the
iTRAK power supply to the iTRAK motor modules. See iTRAK System
Technical Data, publication 2198T-TD001 for the amount of current required
for the iTRAK power supply and the iTRAK motor modules.
Input Voltage
By using multiple cables the iTRAK power supply can deliver control power to
more iTRAK motor modules, see Maximum iTRAK Power Supply to iTRAK
Module Cable Length.
See Table 13 to determine the maximum length of a power cable that is based
on the number of motor modules that are connected to it at the minimum
control power input voltage. This table is for 2198T-CHBFLS8-12AAxx
cables, which are the only cables supported.
Cables between the iTRAK power supply and the iTRAK system are limited
to 30 m (98 ft).
The cable length calculations are made separately for output A and B.
The iTRAK power supply connects to the Kinetix 5700 DC-bus created by
the 2198-Pxxx, Kinetix 5700 power supply. The Kinetix 5700 power supply
must be sufficiently sized to support the iTRAK power supply load and any
other servo drive load.
The iTRAK power supply creates two power buses that are used by iTRAK
motor modules. The topology of the iTRAK motor modules uses the center
voltage bus as a return, and the upper and lower as sources.
Once the output current requirements of the iTRAK power supplies are
known, the amount of power that is required from the Kinetix 5700 power
supply for the iTRAK power supplies is calculated by using this equation.
P (Watts) = Output Current * (Nominal Bus Voltage 1 + Nominal Bus Voltage 2) + iTRAK Power Supply Losses
Any other Kinetix 5700 components that are connected to the Kinetix 5700
power supply bus must also be added to this number.
Table 15 shows the nominal bus voltages and currents of the iTRAK power
supply.
The Kinetix 5700 power supply that is used must be able to deliver the total
power to be consumed. The Kinetix 5700 Servo Drives User Manual,
publication 2198-UM002, has more information.
Verify that the shunting capacity of the system that the 2198-Pxxx Power
Supply manages is not exceeded. For further details, see Shunting Capacity.
Shunting Capacity
The iTRAK power supply can move regenerative energy from the iTRAK
system back to the Kinetix 5700 DC bus. The Kinetix 5700 power supply
turns on a shunt to limit DC bus voltage if the DC bus voltage gets too high.
The amount of shunting capacity available depends on which 2198-Pxxx
Kinetix 5700 power supply that is used and whether an external shunt is
present. See the Kinetix 5700 Servo Drives User Manual, publication
2198-UM002, for more information on shunting capacity.
See the Kinetix 5700 Servo Drives User Manual, publication 2198-UM002,
for information regarding design of these Kinetix 5700 components.
Cabinet
Ethernet Connection
Connection to the EtherNet/IP™ network is not required during runtime for
the iTRAK power supply. An Ethernet connection is required when
downloading firmware updates by using ControlFLASH™ software.
2 2 2 2 2 2 2 4
3
2198-Pxxx 2198T-W25K-ER
Kinetix 5700 Kinetix 5700 3
Power Supply iTRAK Power
Supply
Output Output
A B
1 3
4 2 2 2 2 2 2 3
1
Item Description
1 2198T-CHBFLS8-12AAxx, iTRAK power supply to motor module cable
2 2198T-CHBP8S8-12P3, power cable
3 2198T-CHBP8S8-12P6, power cable
4 2198T-WBCMOD, iTRAK bus conditioner
See the Kinetix 5700 Servo Drives User Manual, publication 2198-UM002,
for details on how to wire the rest of the Kinetix 5700 system. Information on
how to wire to the iTRAK power supply is found in Wire the iTRAK Power
Supply on page 52.
When using multiple iTRAK power supplies, the system must be parsed into
separate electrical pieces for each of the iTRAK power supplies.
The iTRAK power supply is not designed to have the output buses of multiple
power supplies connected together to create one bus of higher current capacity.
IMPORTANT In systems that use multiple iTRAK power supplies, make sure that the
output bus of one power supply is never connected to the output bus of
another power supply.
Use the following scenario to understand the use of multiple iTRAK power
supplies for systems that require a higher current draw. In this example, part of
the track has a high-power demand, and the rest of the track has a lower power
demand. In this case iTRAK power supply 1 powers the first group of ten
motor modules, while iTRAK power supply 2 provides power to the remaining
six motor modules. The DC buses of these two groups are electrically isolated
from each other as shown in Figure 20.
3 2 2 2 4 2 3
3
2198T-W25K-ER 2198T-W25K-ER
2198-Pxxx Kinetix 5700 3
Kinetix 5700 Kinetix 5700
iTRAK Power iTRAK Power
Power Supply Supply 1 Supply 2
Output Output Output Output
A B A B
1 1
4 2 2 2 2 4 3
1
Item Description
1 2198T-CHBFLS8-12AAxx, iTRAK power supply to motor module cable
2 2198T-CHBP8S8-12P3, power cable
3 2198T-CHBP8S8-12P6, power cable
4 2198T-WBCMOD iTRAK bus conditioner
One gateway can interface to multiple iTRAK power supplies through the
Digital USB I/O Module. When you use this configuration, connect the
Enable and Clear Fault signals in parallel, and connect the IPS Ready signal in
series through all iTRAK power supplies as shown in Figure 21.
Figure 21 - Wiring Multiple iTRAK Power Supplies to the Digital USB I/O Module
2198T-W25K-ER 2198T-GUSB
Kinetix 5700 iTRAK Digital USB I/O
Power Supply 1 Module
1 ENABLE
IN1 OUT 00 NO
2 (1)
COM 24V COM 24V OUT 00 C
Digital Input 3 CLEAR FAULT
(IOD) Connector
IN2 OUT 01 NO
4 (1)
COM 24V COM 24V OUT 01 C
5
SHLD SHIELD
iPS READY
ITRAK Power Supply - 24V COM IN00 A
Ready (IR) Connector + 24V IN00 B USB
Port
2198T-W25K-ER
Kinetix 5700 iTRAK
Power Supply 2
1 ENABLE
IN1
2 (1)
COM 24V COM
Digital Input 3 CLEAR FAULT USB
(IOD) Connector IN2 Port
4 (1)
COM 24V COM 2198T-Gxx-xxx-E
Gateway
SHLD SHIELD
- IPS READY
ITRAK Power Supply
Ready (IR) Connector + IPS READY IN
(1) Only one connection to 24V Com is required for each iTRAK power supply. Either pin 2 or pin 4 must be connected, it is not necessary to
connect both.
6 6
MOD– 7
NET– 8
5700
9 16
10 17
5 2
4 1 11
12 DC+
18
I/O
1 6
19
1 6
3
2 7
-
13
3 8
4 9
IPS RDY
5
5 10
10
+
14
DC-
15
IN 24V -
IN 24V +
18
20
21
2 2
Table 18 - Control Input Power (CP) and Control Output Power A and B (ICP) Connectors Pinout
Pin Description Signal 2
1 Control Input Power (CP) Connector
2 24V common 24V-
1 24V power supply, customer-supplied 24V+
2 1
3 DC high voltage H
L
2 DC low voltage L
DC-
Wiring Requirements
The wire must be copper with 75 °C (167 °F) minimum rating. Phasing of the mains AC power
is arbitrary and earth ground connection is required for safe and proper operation.
IMPORTANT The National Electrical Code and local electrical codes take precedence over the values and
methods provided.
Wire the iTRAK Power Supply The following sections cover wiring the iTRAK power supply to an iTRAK
system.
For information on how to wire to the input control power (CP) connector
and connect the DC-power bus links, see the Kinetix 5700 Servo Drives User
Manual, publication 2198-UM002.
The digital inputs are part of a required I/O interface with the gateway. The
digital inputs are connected to the gateway through the digital USB I/O
module.
1 6 1
I/O
6
2 7
iPS RDY
3 8 5 10
4 9
5 10
The iTRAK PS relay output is part of a required I/O interface with the
gateway and is connected to the gateway through the digital USB I/O module.
2198T-W25-ER
iTRAK Power Supply
MOD
NET
(front view)
I/O
1 6
- iPS RDY
5 10
Wire the iTRAK Power Supply DC Bus and Control Power Output
Connectors
The iTRAK power supply uses one cable, 2198T-CHBFLS8-12AAxx, to
connect to the iTRAK system. The single cable terminates at two connectors
on the iTRAK power supply: one for iTRAK control power (ICP) and one for
iTRAK DC bus power (IDC). Two sets of these connectors, referenced as A
and B, are provided on the iTRAK power supply to allow using two cables for
larger iTRAK systems.
ATTENTION: Make sure that the iTRAK power connections are correct when
wiring the plugs and that the plug is fully engaged in the module connector.
Incorrect wiring, polarity, or loose wiring can cause an explosion or damage
equipment.
2 1 H L DC- 2 1 H L DC-
2198T-W25K-ER
iTRAK Power Supply
(right side view)
2198T-W25K-ER
iTRAK Power Supply
(bottom view)
DC-bus output power A and B (1) IDC-4 GND Green/Yellow 2.5…6.0 10.0 (0.39) 0.7…0.8
IDC-3 H Brown (12…10) (6.1…7.0)
IDC-2 L Black
IDC-1 DC- Blue
(1) The iTRAK control power (ICP) and iTRAK DC bus output (IDC) connections must be made using catalog number 2198T-CHBFLS8-12AAxx.
Apply the iTRAK Power Cable Factory-supplied 2198T-CHBFLS8-12AAxx iTRAK cables are shielded. The
braided cable shield must terminate at the iTRAK power supply when
Shield Clamp installed. A small portion of the cable jacket has been removed to expose the
shield braid. The exposed area must be clamped by using the clamp on the
bottom front of the iTRAK power supply.
This procedure assumes that you have completed wiring your IDC and ICP
connectors and are ready to apply the cable shield clamp.
Wire the Digital USB I/O The digital inputs and output from the iTRAK power supply communicate
with the gateway through the 2198T-GUSB Digital USB I/O Module.
Module
To access the connectors, do the following.
1. Remove the four Phillips head screws that secure the cover.
2. Remove the cover.
2198T-GUSB Digital
USB I/O Module with
cover removed
(top view).
A B
OUT 01 C
OUT 01 NO
OUT 00 C OUT 00 NO IN00
Digital Outputs
Digital Inputs
2198T-GUSB Digital
USB I/O Module.
Wire the Gateway Wire the gateway with 24V power input, a machine Ethernet connection, the
USB cable from the digital USB I/O module and a communication cable from
each of the motor modules.
2198T-G01-016-E
Gateway is shown.
USB 2.0
(1) Make only this connection. Do not use any other Ethernet ports for machine Ethernet.
Motor module 0 can be any motor module in the system, but they must be
sequentially numbered counterclockwise facing the position sensing surface.
13 12 11 10 9 8 7
14
15
6
0 1 2 3 4 5
Remove Loop
Back Connector
7 6 5 4 3 2 1 0
2198T-G01-016-E
Gateway is shown.
8 9 10 11 12 13 14 15
2198-Pxxx 2198T-W25K-ER
Kinetix 5700 Kinetix 5700 iTRAK
DC-bus Power Supply Power Supply
Cable Shield
Clamp
DC- DC-
DC-
DC+ Shunt Power L L
(RC) Connector L DC Power Bus A to iTRAK
SH H H Motor Modules
DC Power Bus A A H
(IDC) Connector
1 24V +
24V + Control Power A to iTRAK
2 24V - Motor Modules
24V - Do not connect DC Power Bus
A and B in parallel to another
Bonded Cabinet DC Bus Bar iTRAK power supply on the
100 mm link
Ground Bus (1) same daisy chain.
DC+ DC+ DC Bus
DC- DC- (DC) Connectors
DC- DC- DC-
L L DC Power Bus B to iTRAK
Optional L Motor Modules
2198-TCON-24VDCIN36 DC Power Bus B H H
Chassis H
24V Input Power (IDC) Connector B
Wiring Connector
1 24V + Control Power B to iTRAK
Customer Supplied 1 24V + Motor Modules
+24V +24V Control Power 2 24V -
+24V DC 2 24V -
24V_COM 24V_COM (CP) Connectors
Power Supply (1)
Optional
2198T-W25K-P-T
T-connectors and Bus Bars
1
USB I/O
IN1
2 1
COM Digital Input ENABLE OUT 00 NO
3 (IOD) Connector
IN2 2 (2)
4
SHLD
COM 24V COM 24V OUT 00 C
Digital Input 3
(IOD) Connector
CLEAR OUT 01 NO
FAULT
4 (2)
Connect EN–
COM 24V COM 24V OUT 01 C
contactor enable CONT EN– Contactor Enable 5
(1) EN+ (CED) Connector SHLD SHIELD
circuitry CONT EN+
- IN00 A
iTRAK Power Supply RDY- IPS READY 24V COM
Ready (IR) Connector +
Three-phase Input RDY+ IN00 B
(IPD) Connector
For multiple iTRAK power supplies,
PE Ground PE Ground see Wiring Multiple iTRAK Power
L3 L2 L1 Supplies to the Digital USB I/O
Module on page 47
Cable Preparation for iTRAK Follow these instructions to prepare the wires for creating custom length
2198T-CHBFLS8-12Axx cables.
Power Supply Output Power
Cables These instruction steps assume that the cable has already been cut to the
desired length.
32 mm 43 mm (1.7 in.)
(1.26 in.) Trim filler material.
5. Pull back the outer braided shield and carefully create an opening in the
braid as close as possible to where the outer jacket ends.
6. Feed the internal shielded twisted pair through the opening in the outer
braided shield, and pull it through tight.
The shielded twisted pair is now outside of the main braided shield and
the two shields are in contact.
(Rotated View)
7. To hold the wires together, bundle the group of four wires with the
previously trimmed filler material and slip on a 45 mm (1.8 in.) length
piece of shrink tube.
8. Slide previously trimmed piece of the outer braided shield over the
entire bundle, butt it up to the cable jacket, pull tight, then trim the
piece so it is approximately 75 mm (2.9 in.) long.
75 mm
(3 in.)
10. Place a 23 mm (0.9 in.) length piece of adhesive-lined shrink tube over
the cable so that a 35 mm (length of shielded braid is left exposed.
64 mm 138 mm
(2.5 in.) (5.4 in.)
75 mm
(3 in.)
35 mm 23 mm
(1.4 in.) (.09 in.)
Adhesive lined heat shrink two
Jacket
11. Trim the braided shield on the twisted-pair shield back 40 mm (1.6 in.)
from the end of the wires.
12. Place a 20 mm (0.79 in.) length piece of shrink tube over the twisted
pair approximately 30 mm (1.18 in.) from the end of the wires.
13. Strip the individual wires back 9 mm (0.35 in.).
64 mm 138 mm
(2.5 in.) (5.4 in.)
Exposed Ring cut
Shield Heat 9 ± 0.1 mm insulation six
13 mm Shrink (0.5 ± 0.004 in.) places.
(0.5 in.)
Label wires 6
places.
35 mm 23 mm
(1.4 in.) (.09 in.) 9 ± 0.1 mm
30 mm
Heat (1.18 in.) (0.5 ± 0.004 in.)
Jacket
Shrink 20 mm (0.787 in.) long heat
shrink over twisted pair.
Logix Designer Application The Studio 5000 Logix Designer® application controller program necessary to
support the iTRAK power supply is provided in the Pxx_IPS_Support
Support program. The code performs the following functions.
• Sends the power supply type for PCM or iTRAK power supply to the
gateway.
• Sends the DC-bus power supply DCBusUPStatus to the gateway. The
bus up status is used by the gateway to gate the iTRAK power supply
Enable signal.
• Monitors DC-bus power supply DCBusUnload in the sample code to
trigger stopping actions.
The code also provides examples for disabling the iTRAK power supply via the
gateway.
Name the DC-bus power supply axis DFE. If you use a name other then DFE,
update the DFE tags to match the name that is given to the DC-bus power
supply.
IMPORTANT You must import Pxx_IPS_Support program into the same task as the
iTRAK_IO code.
You can obtain the Studio 5000 Logix Designer controller ladder code by
going to the Rockwell Automation Knowledgebase article 778917.
IMPORTANT Do not add the iTRAK power supply to Logix I/O tree. If you do, unexpected
results can occur.
Notes:
The power control module (PCM) is a fully wired and assembled cabinet. It
accepts main power and provides bus power for the motor modules and logic
power for the gateway and motor modules. It includes disconnects, fuses, and
USB I/O module. It has pre-wired functional safety features such as an E-stop
and reset circuit.
Topic Page
Typical System Configuration Using a PCM 65
About the Power Control Module 67
About the Gateway 73
Plan Your System Installation 75
Install the Power Control Module 75
Install the Gateway Enclosure 75
Connect Cables 75
Figure 31 shows a typical iTRAK® system that uses a PCM. Your system can
vary in the quantity and layout of each component, but all follow the same
concept.
5
14
7
13
9 12
10 11
9
8
15
4
2 3
1
About the Power Control Figure 32 shows a typical power control module (PCM). Your system can
differ in the layout and the number of connectors, but has the same
Module components.
2 5
7
8
9
10 3
12 11
If any of the status indicators do not light when expected, check the associated
circuit breakers. See Circuit Breakers on page 111.
ATTENTION: If the ESR and GSR safety relays appear to be faulty, contact
Rockwell Automation for service. Do not attempt to service or repair ESR and
GSR safety relays.
PCM Dimensions
1181.4
(46.5)
1219
(48.0)
329 762
(13.0) (30.0)
Side View Front View
(4X) Ø 6.35 (0.25)
Rear Mounting Holes
The PCM has external connections to the E-stop, guard, reset switches, and
monitoring capabilities. This section shows the wiring information that you
can use to add more safety switches and monitoring capability.
The PCM connectors for external E-stop switch (P5), guard switch (P4), reset
switch (P3), and monitor (P2), use the connectors that are supplied with the
system.
S04 Reset
Reset
A A 14 13
B B
C C 14 13
D D
Figure 35 shows the pinout for the E-stop and guard connectors.
External
Emergency Stop
A A
B B
104 C C
D D
E E
E and F Dry NC
F F Contact
B B
C C
D D
E E
E and F Dry NC
F F Contact
MOA A F
MOB B G E MOE
MOC C D MOD
M01
BLU M0A
A 11 14
R2A
BLU M0B
11 14
B R2B
BLU M0C
11 14
C R2C
BLU M0D
11 14
D R2D
BLU M0E
E
4 PS02 Undervoltage 3 11 18 26
8 PS01 Undervoltage 7 15 22 30
E 24V A
F
F 24V Common
GND
GND PE
About the Gateway Figure 42 shows a typical 16-port gateway. Your system can differ in the layout
and the number of connectors, but has the same components.
4 5 6
3
2
Item Description
1 Gateway (P6) to PCM (P7) cable connector
2 Ethernet ports
3 Gateway computer
4 Wire terminals
5 USB I/O
7
6 Ethernet hub
7 Wiring glands
469.9
(18.50) 228.6 508
4X Ø 0.44 (9.00) (20.00)
Rear Mounting Holes
469.9 508
(18.50) (20.00)
4 PS02 Undervoltage 3 11 18 26
8 PS01 Undervoltage 7 15 22 30
Plan Your System Installation Choose the location for system components by following these considerations:
• operator access to emergency stop switch on the power control module
(PCM)
• operator and maintenance access to movers, motor modules, power
control module, and gateway
• cable lengths
• vibration free surfaces
Connect Cables Your system comes with the power bus and communication cables. You are
required to route and connect them to the motor modules, PCM, and gateway.
To connect these cables following the system diagram.
The motor module-to-motor module power-bus jumper cables and the power-
bus terminator are already installed.
1. Browse to https://motionanalyzer.rockwellautomation.com/Products/
iTrak.
2. Click 3D CAD Models of iTRAK Components.
3. Open 2198T-3DCAD.zip.
4. Double-click 2D Outline and Assembly Drawings.
5. Double-click C806607-3-X_REVA.
6. Click Open.
IMPORTANT Help protect cables from stress and damage during use of the
system.
1. Route and connect the power bus cables from the appropriate motor
module to the PCM.
See your system diagram to determine power bus cable that is required
for each motor module. Power bus cables are labeled on the ends of cable
next to the SpeedTec connector.
2. In the gateway enclosure, remove the loopback connector from the
number seven communication port.
If the number of motor modules in your system is 16, 32, 48, or 64, and
you have an equal number of motor modules, you can discard the loop
back connector. If it is not, save the loop back connector for use in
step 4.
3. Route and connect communication cables from the motor modules to
the gateway.
The communication cables are labeled with the motor module number
0…63 depending on the number of motor modules in your system. Be
sure to pass the cable through the cable gland of the gateway. Each gland
can take up to 10 cables.
4. If the number of motor modules is not equal to 16, 32, 48, or 64, install
the loop back connector in the next available communication port.
5. Secure the communication cables to the cable gland by using the Skintop
cube. See Lapp Kable instructions BS09/3878-3
6. Connect the PCM to mains power line.
Use minimum of 10 mm2(8 AWG) copper for the ground wire.
7. Connect your personal computer and Allen-Bradley® controller to the
gateway Ethernet ports.
Use this chapter to power on your system by using a Kinetix® 5700 system or a
PCM.
Topic Page
Before You Power On the Track 77
Apply Power 78
Commission with Programming Manual 82
Before You Power On the There are some items that you can review before the system is powered that can
speed up the time to commission your system.
Track
Identify Controller
The controller that you use determines which type of Starter Project is best suited
for your application. Consider the memory requirements, axis count, and motion
task utilization when choosing the catalog number of controller. Integrated
Architecture® Builder from Rockwell Automation can help you size the
application and estimate which controller is properly suited for you; see
Knowledgebase Article 1040301, How to size an iTRAK® in IAB? for more
information.
To update your motor module firmware see Update Motor Module Firmware on
page 104
When you download the firmware revision from the Rockwell Automation
Product Compatibility and Download Center, the software files for Studio 5000®
Logix Designer are included. Choose the appropriate project file that is based on
the features and controller for that firmware revision.
Apply Power There are different sequences to follow that depend on the type power supply
that you have in your system. For Kinetix 5700 systems, see Kinetix 5700 iTRAK
Power Supply section. For PCM systems, see Power Control Module section.
SELF-TEST SELF-TEST
FW REV: x.x.xxxxxxx FW REV: x.x.xxxxxxx
75% until the test is complete… 100%
When the Kinetix 5700 power supply is ready, the contactor enable relay is
closed so that main power can be applied to the Kinetix 5700 system bus.
4. Apply bus voltage.
The bus voltage is applied to the system when the appropriate commands
are sent from the processor to the gateway. This action triggers the
Kinetix 5700 iTRAK power supply via the USB I/O module. See the
Motion Commands section of the iTRAK Programming Manual,
publication 2198T-PM001, for more information.
After main bus voltage is applied to the system and the command motor
power is sent from the processor to the gateway, look for following status
indicators.
For the series B motor modules, all three status indicators are solidly
illuminated green. The series B status indicator uses different
nomenclature. The Drive Enabled status indicator on series B motor
modules replaced Motor Power status indicator on a series A motor
module.
CONTROL POWER
COMMUNICATION
DRIVE ENABLED
DANGER
Hazardous Voltage Inside
For the gateway, there are no physical status indicators on the gateway that
would notify that it is ready for motion. The status indicators are displayed
in the Logix Designer application, which is discussed in the next section.
In the Logix Designer application, there are numerous status indicators
that verify the iTRAK is ready for motion.
If the gateway is not ready, the I/O OK status indicator turns to a flashing
green and say I/O NOT RESPONDING.
Under the Controller Tags, the iTRAK_Control tags are displayed.
Under the iTRAK_Control tag, there are three subsets of tags, .Cmd,
.Status, and .Data are displayed.
Commission with Configure, tune, and program the iTRAK system by following the instructions in
the iTRAK Programming Manual, publication 2198T-PM001.
Programming Manual
Maintenance
This chapter contains information for on how to care for your system, replace
component, and update firmware.
Topic Page
Before You Begin 83
Preventive Maintenance 83
Add or Replace Components 84
Update Gateway Firmware 102
Update Motor Module Firmware 104
Lubrication 105
Circuit Breakers 111
Before You Begin Before you attempt maintenance on the system, do the following.
• Make sure that the movers are motionless.
• Disconnect electrical power to the system by using the master switch
and lockout.
Bearing Rail
Track Components
Clean the following surfaces with isopropyl alcohol and soft lint free cloth.
• position sensor
• top and bottom plates
• motor module coil
If there is ferrous debris on the magnet plates, remove them with the sticky side
of duct tape or clay.
Add or Replace Components The following procedures show you how to install or replace system
components.
Position magnet assemblies can be replaced while the mover is on the track.
Remove the shoulder socket head cap screws that secure the position magnet
assembly to the mover by using a 2.5 mm Allen wrench.
1. Clean shoulder socket-head cap screws and apply fresh Loctite 222.
2. Install position magnet assembly onto the mover with shoulder socket-
head cap screws by using 2.5 mm Allen wrench, torque to 0.85 N•m
(7.5 lb•in)
3. Check that the polarity of position magnets alternate between north
and south on adjacent movers.
You can check the polarity by examining the color of the magnets.
Item Description
1 Shoulder Socket-Head Cap Screws
2 Position Magnet Assembly
3 Mover
ATTENTION: If you are using your own design for a mover, make sure of the
following.
• The mounting hardware is not too long that it protrudes past or pops
through the magnet plate.
• Be sure to use all mounting holes. By using all mounting holes, the magnet
maintains correct orientation of north-south magnet polarity.
Item Description
1 Magnet plate assembly
2 Flat head cap screw
3 Socket head cap screw
Choose an accessible curved section of the track, Position the mover that you
want to replace over a straight motor module next to the curved section. Move
all other movers off the curved end of the track.
Bottom curved
bearing rail is not
shown.
3. Remove the curved bearing rails by pulling parallel to the track away
from the straight bearing rails.
ATTENTION: Avoid bending the bearing-rail key. Do not lift the curve
bearing rail up until the bearing-rail keys have cleared the straight
bearing-rail key slot.
ATTENTION: When removing or installing the mover, keep the mover square
to the fixtures and take care not to damage the felt surfaces of the
lubrication wiper assemblies.
9. Install the curved bearing rails by holding them parallel to the track and
aligning the bearing rail keys with the bearing-rail key slots on the
straight bearing rails. Slide the bearing rails keys into straight bearing-
rail key slots.
10. Torque the middle screws to 22 N•m (16.2 lb•ft) by using 5 mm Allen
wrench; leave the two screws on each end of the curved rail loose.
11. If necessary, align the straight and curve rails by adjusting the set screws
on the ends of the curved rails to within 0.0127 mm (0.0005 in.) by
using 2.5 mm Allen wrench.
12. Torque the remaining screws to 22 N•m (16.2 lb•ft) by using 5 mm
Allen wrench.
End Screws
13. Install the position magnet assembly by following the procedure Install
or Remove a Position Magnet Assembly on page 84.
1. Remove the socket head cap screws M6 x 20 that secure the rails above
and below the module you are replacing.
3
4
Item Description
1 Upper rail
2 Module to be replaced
3 Lower rail
4 Socket head cap screws M6 x 20
2
3
Item Description
1 Motor module
2 Motor module shim
3 Shoulder bolts, shoulder Ø 20 x 10, thread M8 x 25 (x4)
4 Socket head cap screw M8 x 25 (x4)
9. Loosely secure the top and bottom straight rails in position by using all
socket head cap screws M6 x 20.
Be sure to minimize gap between rails.
10. Torque screws to 16 N•m (11.8 lb•ft) by using 5 mm Allen wrench.
11. Update motor module firmware, see Update Motor Module Firmware
on page 104.
1. Move movers away from the area where the curved module is to be
replaced.
If you have to remove the movers follow steps in Install or Replace a
Mover on page 88.
2. Remove all M6 x 20 socket head cap screws from the curved bearing rails
on the top and bottom of the track by using a 5 mm Allen wrench..
1
Item Description
1 Socket head cap screws M6 x 20
2 Curved motor module to be replaced
3. Remove the top and bottom curved bearing rail by pulling parallel to the
track away from the straight bearing rails.
ATTENTION: Avoid bending the bearing key. Do not lift the curve
bearing rail up until the bearing keys have cleared the straight
bearing rail key slot.
3
2
Item Description
1 Top curved rail
2 Bottom curved rail
3 Bearing rail key (X4)
4. Remove the socket head cap screws M6 x 20 that secure the straight rails
to the curved top plate and the bottom straight rail that is located below
the adjacent straight motor module by using a 5 mm Allen wrench and
remove the straight rails.
1
2
4
3
Before removing the curved motor module, the straight motor module
located next to it must be removed to clear the removal of the curved
motor module.
5. Remove the adjacent straight motor module by following the procedure
to Replace a Straight Motor Module on page 92.
2 4
3
6.
7. Remove the socket head cap screws and shoulder bolts that secure the
top curved plate to the curved modules by using a 6 mm Allen wrench
and remove the top curved plate.
1 2
5
3
4
8. Remove the bottom socket-head cap screws and shoulder bolts that
secure the curved module to the base plate by using 6 mm Allen wrench.
9. Remove motor module shim.
10. Move the curved motor module towards the end of the iTRAK system
about 25.4 mm (1 in.) and disconnect the cables.
11. Lift the curved module straight up and out.
3
2
Place within 25 mm
(1 in.) of final position
4
3
4. Move the replacement curved motor module into its final position.
5. Bolt the curved motor module to the base plate from the bottom.
Torque shoulder bolt screws to 13 N•m (9.6 lb•ft) and torque M8
socket head cap screws to 22 N•m (16.2 lb•ft).
6. Place shim on top as shown
1 2
Item Description
1 Shoulder Bolts
2 Socket Head Cap Screws
3 Top Curved Plate
10. Loosely secure the top and bottom straight rails in position by using all
screws.
Be sure to minimize gap between rails.
11. Torque screws to 16 N•m (11.8 lb•ft) by using 5 mm Allen wrench.
Upper Straight Rails
12. Place the curved top and bottom rails in position by sliding them into
the bearing key slots and loosely attach by using all screws.
13. Torque the middle screws to 16 N•m (11.8 lb•ft) by using 5 mm Allen
wrench leave the two screws on each end of the curved rail loose.
14. Align the straight and curve rails by adjusting the set screws on the ends
of the curved rails to within 0.0127 mm (0.0005 in.) by using 2.5 mm
Allen wrench.
15. Torque the remaining screws to 16 N•m (11.8 lb•ft) by using 5 mm
Allen wrench.
1
Item Description
1 End bolts
2 Socket head cap screws
3 Set screws (X4)
16. Update motor module firmware, see Update Motor Module Firmware
on page 104.
Update Gateway Firmware To update the firmware using iTFlash, do the following.
Ethernet Ports
4. From the dialog box, change the base IP address if needed, and click the
Update Gateway and Section Firmware with iTFlash button.
The software copies files to the system over the network. It can take up
to ten minutes.
TIP If the dialog box has not appeared within 5 minutes of running
iTFlash.exe, see the Firmware Update Troubleshooting section.
5. If you are changing to revision 1.099 or earlier, when the iTFlash Success
dialog box is displayed, wait at least 1 minute, and cycle power on the
gateway to restart it.
In revisions greater than 1.099, the gateway automatically restarts itself.
TIP If the iTFlash failed dialog box comes up, see the
Firmware Update Troubleshooting section.
In some rare cases when iTFlash has been previously executed, extra steps can
be required to complete the installation. Follow this procedure if the operation
failed.
Downgrading Firmware
Update Motor Module To update the firmware of a newly installed motor module, do the following.
Firmware 1. Disconnect the communication cable to the new motor module.
2. Power on the gateway.
3. To update all existing motor modules to 2198T-VTxx05-A firmware,
toggle Cmd.FlashSections50mm.
4. Power down the gateway.
5. Plug in the communication cable for the new motor module.
6. Power on the gateway.
7. Toggle Cmd.FlashSectionsxxxmm that corresponds to the mover type
you have. There are three types of movers:
2198T-VTxx05-A
2198T-VTxx10-A
2198T-VTxx15-A.
Lubrication The bearings are an open system that requires continuous lubrication. To avoid
breakdown of the lubrication, the bearings must have a film of oil on them.
Typically indications of breakdown are discoloration and excessive wear on the
inner and outer bearing surfaces. The interval to resupply the lubrication
depends on the length of stroke, duty cycle, and environmental factors. Use 68
viscosity mineral oil, such as Kluber 4 UH1-68N, to lubricate the bearing rails.
3 6
Items Description
1 Spine bar
2 Top inner lubrication tube
3 Top outer lubrication tube
4 Bottom outer lubrication tube
5 Y-split push-to-connect tube connector
6 Plug
7 Straight push-to-connect tube connector
Initial Lubrication During first-time start or when rails have been completely cleaned do the
following.
It is normal for some of the oil to become black, but you must not see
signs of rusting or burnt grease, which is a sign of missing lubrication.
Lubrication During Normal Lubrication amounts and frequency during normal operation depend on many
factors including length of track, number of movers, application motion
Operation profile, cleanliness of the operating environment and other factors. Table 36 is
a rough guideline that must be adjusted for each application strike a balance
between keep a thin film of oil on the rail contact surfaces and over lubrication
that causes excess oil splatter.
Table 36 - Lubrication Examples
System Length Amount of Movers Pump Volume Time Interval
mm (ft) cc (oz) in Hours
800…2400 (2.6…7.9) 1…12 0.7 (0.002)
2400…4800 (7.9…15.7) 1…12 1.4 (0.047) 2
5200…10000 (17.1…32.8) 24…36 2.8 (0.095)
The values in Table 36 are guidelines only; monitor the rails every few hours
until a quantity and frequency can be established for the current application. It
is best to have a higher frequency with lower amounts of oil dispense to allow
the oil to coat the rails evenly.
For systems with large number of movers, increase the pump volume by 1…2 cc
(0.034…0.068 oz).
2
3
Item Description
1 Inner Track Lubrication Wiper Assembly
2 Socket Head Cap Screw (x3)
3 Outer Track Lubrication Wiper Assembly (x2)
The top four bearings are not field replaceable. For further information contact
a Rockwell Automation sales representative. There are two procedures for
replacing the lower bearings. The first one is for 2198T-VTxx05-A movers and
the second is for 2198T-VTxx10-A and 2198T-VTxx15-A wide movers.
Use the following procedure for movers with these catalog numbers.
• 2198T-VT0505-A
• 2198T-VT1005-A
• 2198T-VT1505-A
Item Description
1 Vee-wheel with integrated bearing
2 Lock nut
Use the following procedure for movers with these catalog numbers.
• 2198T-VT0510-A
• 2198T-VT0515-A
• 2198T-VT1010-A
• 2198T-VT1015-A
• 2198T-VT1510-A
• 2198T-VT1515-A
Bottom Plate
M6 x 30 Screws
Shim
Circuit Breakers Use Figure 45 to locate circuit breakers in the PCM. Before accessing the
PCM, read the following.
• Do not touch hot surfaces such as brake resistors, heat sinks, power
supply units, drive controllers.
• After powering down switching chokes, power supply units, and drive
controllers, let them cool for 15 minutes before touching.
112
Chapter 6
14
1
INPUT
A2
12
41
8
11
4
44
31
42
7
34
3
32
10
21
13
Maintenance
INPUT
6
11
9
2
24
A1
22
14
1
12
2
3
4
5
6
shock.
High voltage may
DANGER
Risk of electrical
exist up to 5 minutes
after removing power.
7
Troubleshooting
Use the system reported errors in this section to diagnose iTRAK® system
problems.
Topic Page
Errors Codes 113
Errors Codes The iTRAK system can generate errors from the Gateway or from the motor
modules. The error codes are pushed from those devices to tags in the control
structure. These error codes are in addition the Logix Designer application
generated codes. Error codes from the motor module are displayed in
iTRAK_Control.Status tag.
Functional Safety
The iTRAK® components do not have Safe Torque Off or any other features
that are described in EN 61800-5-2. When combined into a system,
implement safety functions to prevent motor actuation. Remove the AC power
by using similar methods that are used for variable frequency drives that do not
have Safe Torque Off. The safety function subsystem that is described here
explains how to wire contactors for the successful removal of power to the
iTRAK system.
Topic Page
Important Safety Considerations 121
Category 3 Requirements according to EN ISO 13849-1 121
Stop Category Definition 122
Performance Level and Safety Integrity Level (SIL) 122
Safety Distance Calculations 122
Functional Safety Description 122
Considerations for Category 1 Stop 123
Overall System Stopping Performance 123
Schematic and Block Diagrams 124
Stop Category Definition Stop Category 0 as defined in IEC 60204 is achieved with immediate removal
of power that produces actuator motion.
Stop Category 1 as defined in IEC 60204 is achieved with the delayed removal
of power that produces actuator motion, to facilitate the controlled stoppage of
elements that move.
Performance Level and For safety-related control systems, Performance Level (PL), according to
EN ISO 13849-1, and SIL levels, according to IEC 61508 and IEC 62061.
Safety Integrity Level (SIL) Include a rating of the ability of the system to perform its safety functions. All
safety-related components of the control system must be included in both a
risk assessment and the determination of the achieved levels.
See the EN ISO 13849-1, IEC 61508, and IEC 62061 standards for complete
information on requirements for PL and SIL determination.
Safety Distance Calculations Detailed calculation of a proper safety distance is beyond the scope of this
document, but here are some considerations to follow.
System safeguards must be in place such that a person cannot reach a hazardous
motion before the safeguarding system has brought that hazardous motion to a
halt. These issues are addressed in safety standards relevant to this application
that are listed here.
• IS0 14119 Safety of machinery - Interlocking devices that are associated
with guards - Principles for design and selection.
• ISO 13855 Safety of machinery - Positioning of safeguards regarding the
approach speeds of parts of the human body.
• ANSI B11.19 Performance Criteria for Safeguarding.
Functional Safety The safety logic device, such as a configurable safety relay or programmable
safety automation controller, monitors the safety input device, such as a door
Description switch or emergency stop button, for commands, proper operation, and safety
demands. The safety logic device must monitor itself for any internal faults.
When actuated, the safety logic device sends a safety stop command to the
motion control device and start the configurable timer. During this time, the
iTRAK system must decelerate to zero speed.
When the timer expires, power is removed from the safety output contactors
that remove power that produces motion from the iTRAK system. If the track
is in motion, it coasts to a stop.
The safety logic device must monitor the contactors for welded contacts via
feedback from two normally closed contacts in a series, one from each
contactor, in the reset circuit. If a contact is welded, the normally closed
contact is held open, which breaks the reset circuit. The system must not be
restarted until appropriate measures have been taken.
Considerations for Category 1 If there is a malfunction, it is possible that stop category 0 can occur. When
designing the machine application, timing and distance must be considered for
Stop a coast to stop and the possibility of the loss of control of a vertical load. The
malfunction that causes this condition maybe when a signal to the output
contactor coil were to go low. A low can happen when a wire falls off or control
power fails before the iTRAK system has a chance to come to a complete stop.
Use additional protective measures if this occurrence can introduce
unacceptable risks to personnel.
Overall System Stopping ISO 14119 6.2.1 stipulates that the overall system stopping time for a
hazardous machine that is safeguarded by an interlock must be less than the
Performance access time. If the overall system stopping performance is equal to or greater
than the access time, an interlock with guard locking must be used, the distance
from the safeguard to the hazard must be increased, or another, more suitable
method must be used to safeguard the hazard.
The response and reaction times can be taken from the product support
literature.
The sum response and reaction time of the safety logic devices, output
contactors, and worst-case, coast-to-stop portion of the overall system-
stopping performance is the same regardless of the input device used.
It is useful to estimate how fast the hazardous motion must coast to a stop
before the safeguarded system is available for testing.
Schematic and Block These simplified schematic diagrams are intended to inform qualified
engineers on how to structure a safety system around the iTRAK system. They
Diagrams are not considered complete.
The block diagram that is shown in Figure 46 is an outline schematic for the
safety circuit to use with a system that uses an iTRAK power supply.
Figure 46 - Kinetix® 5700 iTRAK Power Supply Safety Circuit Block Diagram
2198-P070 2198T-W25K-ER
Kinetix 5700 Kinetix 5700
Bonded Cabinet DC-bus Power Supply iTRAK Power Supply
Ground Bus *
Cable Shield
Clamp
DC-
DC-
Chassis DC+ Shunt Power L
(RC) Connector DC-bus Power Output A L
SH H
(IDC) Connector H
Customer Supplied and Control Power Output A
+24V DC (ICP) Connector 1 24V +
Power Supply * 24V +
2 24V -
24V -
When the iTRAK system is used with a pre-assembled power control module,
the safety logic devices and safety output contactors are pre-wired in the
cabinet. You are responsible for wiring safety input devices to the appropriate
connectors on the cabinet. The safety circuit wiring schematic included in a
pre-assembled cabinet is shown in Figure 47.
CONTACT External
Reset
(P3)
CGS01 S11
A2 S33 A1
COM 24V
Guard Stop 1 2
A
External B 14 S12 Relay S34 13
CGS02 C
Guard Stop D
k2 k1
S21 14 13 23
(P4) E
24
24 23 41
34 33
E and F DRY F
NC 34 S22 42 41 42 33
CONTACT
Circuit
Protection
L3 3
28 320V
PS01 L2 2
29 0V L1 1
324…528V AC rms
Three-phase Input
A
L3 3
B 28 160V
ITP00…ITP07 29 0V
PS02 L2 2 Safety
C L1
To Motor Module D
1 Contactors
E
Circuit
F Protection
Notes:
Compatibility
Motor Modules Bulletin 2198T iTRAK motor modules are compatible and can be mixed
mechanically, regardless of the series.
• If you have any series B modules in your system, the minimum firmware
revision for the entire system is 1.107.
• There are minor differences in labeling and appearance but the modules
are functionally the same.
Bulletin IT3 iTRAK motor modules have limited compatibility with the
Bulletin 2198T iTRAK motor modules.
• Bulletin IT3 iTRAK motor modules have higher cogging force in the
motors and can require modifications to the tuning when replacing with
Bulletin 2198T iTRAK motor modules.
• If a Bulletin 2198T iTRAK motor module is replacing s a Bulletin IT3
iTRAK motor module, all similar modules that are adjacent must be
replaced also.
– If replacing one curve module, the adjacent curve module must be
replaced also. The straights and opposite curve can stay.
– If replacing a straight module, all of straight modules between the
nearest curve modules must also be replaced. The opposite straights
and curves can stay in the system.
• All modules must be updated to the same firmware revision that the
newest module requires.
• Contact ICTSupport@ra.rockwell.com before making any Bulletin IT3
to Bulletin 2198T migrations for additional support.
Movers and Magnets Mover magnets on a track must all be the same size and geometry. All mover
magnets are compatible with all motor modules of the same frame size.
Gateways Two styles of gateways are supported for the iTRAK system.
Generation one gateways are compatible with all motor module types and
firmware revisions.
Generation two gateways are compatible with all motor module types, from
firmware revision 1.100 and later for tracks smaller than 16 motor modules and
firmware revision 1.108 for larger tracks.
Power Supplies Two styles of power supplies are supported for the iTRAK system. They must
not be used on the same system.
If you are using the Kinetix® 5700 iTRAK power supply, you must use firmware
revision 1.110 or later and the associated ladder logic that is referenced in
Knowledgebase Article 778917. If using a Kinetix 5700 iTRAK Power Supply at
lower firmware revisions, contact ICTSupport@ra.rockwell.com for assistance
and sizing.
Controllers The iTRAK system is designed to work with the controllers that are shown in
Table 40.
Table 40 - Compatible Controllers
Platform Controller
ControlLogix® 5580 (1)
5570 (2)
CompactLogix™ 5380 (1) (3)
5370 (3)
5480 (1)
(1) The minimum firmware revision to use these processors is 1.103.
(2) The communication to the gateway must be through 1756-ENxT modules capable of Integrated
Motion on EtherNet/IP™.
(3) The memory requirements and CPU utilization of typical iTRAK applications can reduce the possible
catalog numbers available in these families. Work with Rockwell Automation application
engineering to determine suitability.
Label Placement
Use this chapter to understand the safety labels and what is on a safety label if it
is unlegible.
Topic Page
Safety Labels 129
Safety Labels The following safety-identification labels are affixed to the iTRAK® system. To
help prevent injury and damage to the system, review the safety labels, their
details, and locations before using the system.
B
CAUTION
Heavy Obje
H CONTRO
COMMU
NICATIO
DRIVE ENABLE
L POWER
Two perso ct D
C
n
required. lift WARNIN DANGER
Hazardous
Power Off. Voltage Inside
G Lockout/Ta
wait 5 minutes gout and
Hazardou WARNING
WARNING
wearers
E
Disconnect
A
CAUTION
before openpower Metal Surfaces
Do not touch May be Hot
CAUTION ing Power Off.
Allow to
cool down
CAUTION
Hot Surfa PINCH POINTS
NEARBY
ce. B624958
Sudden
motion.
Power Off. Stand
Lockout/Ta Clear
Do not touc gout
h.
CAUTION
Sudden machin
injury. e motion
can cause
Stand clear
Pinch Point.
Keep clear
when machin
during operatio
e is in motion
n.
.
D 3
1 1
C WARNING
HAZARDOUS
VOLTAGE.
F
Disconnect power
before opening.
GER
DAN
Do not touch.
TAGE
HIGH VOL
Hot Surface.
CAUTION
req per Ob
Twoavy
He
uire son jec
CA
d. lift t
UT
A
IO
N
H
t and
ER
befoonn
Discde. ous
ING
insi ard
ER
e
agou
Haz
ATION
n
wait r Off. Lock ge Insid
dow
be Hot
N
L POW
DANG
agou r
5 minu out/T
re ect
BLED
out/T Clea
ION
t
IO
WA
to cool
WARN
Keep Point. when
ope pow
Pinch clear
Stand
ers
Powerdous Volta
Sudde
MUNIC
Lock d
make ful to
r wear
TRO
ENA
clear
CAUT
ning er
Allow
Do notl Surfaces
pacebe harm
volt
during
CA
r Off. h
CON
ING
DRIVE
COM
SuddH POIN
Haza
age
e motion
UT
operat
Mag
machin
Meta
PINC
ion.
ION
e is
can
in motion
cause
958
.
B624
2 4
2
DANGER
Risk of electrical
shock.
High voltage may
exist up to 5 minutes
G
after removing power.
Location
Hot Surface Series A Motor A Indicates that the surface can be hot enough to burn if touched.
Module CAUTION
Hot Surface.
Do not touch.
Heavy Object Series A and B B Components with this label are 22.7 kg (50.0 lb) or more and
Motor Modules CAUTION require two people to lift.
Heavy Object
Two person lift
required.
Hazardous Voltage Series A Motor C Do not open PCM, motor module, or right angle connectors while
Module and PCM WARNING the cables are connected. Lockout/tagout if access to the motor
Hazardous voltage
inside.
module is required during maintenance.
Disconnect power
before opening.
Automated Machinery Series A Motor D Movers can make as sudden and unexpected movements while
and Pinch Points Module CAUTION the system is powered. Lock-out/tag out before servicing.
Sudden machine motion can cause
injury.
Stand clear when machine is in motion.
Pinch Point.
Keep clear during operation.
Magnet and Pinch Points Mover E The mover uses strong magnets. The magnetic field that is
WARNING
PINCH POINTS
Moving parts Lockout/Tagout
generated can disrupt the functionality of automatic- implantable
Magnetic field locate in this area cardioverter defibrillators (AICD). People with cardiac pacemakers
Can be harmful to pacemakers and
other sensitive equipment must not work near the iTRAK system. The strong magnets of the
mover can attract metal objects that are in its proximity. When
you handle and install maintain distance between the mover and
ferrous metal mounting surfaces or structures.
Maintenance personnel must avoid the use of metallic tools and
secure items such as badge clips other personnel effect that could
be attracted to the strong magnetic field.
Strong magnets can erase magnetic media. Never let credit cards
or electronic media contact or come near the mover or iTRAK
system.
Pinch points exist between adjacent movers and motor modules
and movers. Keep your hands clear of a system under power.
High Voltage PCM F The power control module can have voltages greater than 240V
present inside the cabinet and at the connectors.
DANGER
HIGH VOLTAGE
Location
High Voltage PCM G The capacitors inside the PCM can have high voltage present for 5
(capacitors) DANGER minutes. Do not attempt to service the PCM until 5 minutes after
Risk of electrical
power has been removed.
shock.
High voltage may
exist up to 5 minutes
after removing power.
Unified Safety Label Series B Motor H See Safety Information on page 19 for details on danger,
Module warnings, and cautions on this label.
CONTROL POWER
COMMUNICATION
DRIVE ENABLED
DANGER
Hazardous Voltage Inside
Power Off. Lockout/Tagout and
wait 5 minutes
WARNING
Magnetic Field
Can be harmful to
pacemaker wearers
CAUTION
Metal Surfaces May be Hot
Do not touch
Power Off. Allow to cool down
CAUTION
PINCH POINTS NEARBY
Sudden motion. Stand Clear
Power Off. Lockout/Tagout
B624958
Notes:
Numerics C
2198T-A01 88 cable
2198T-AL-SYS 105 installation 75
configuration 35 cable gland
installation 32 installation 76
2198T-CHBFLS8-12AAxx 42, 45, 46 cable installation 75
2198T-CHBFLS8-12Axx circuit breaker
installation 54 10 kW power control module type 2 112
2198T-CHBP8S8-12P3 45, 46 cleaning 83
2198T-CHBP8S8-12P6 45, 46 commission 82
2198T-G02-016-E 17 compatibility
2198T-GUSB 17, 47, 56 controller 128
2198T-Gxx-xxx-E 47 gateway 128
2198T-L16-Txx04-AOON-2E1E-NS 12 motor module 127
mover 128
2198T-L16-Txx04-B09x-2E1E-NS, 12 power supply 128
2198T-L16-Txxxx-A00N-2E1E-NS 92 component description
2198T-L16-Txxxx-B09x-2E1E-NS 94 curved motor module 12, 38, 66
2198T-M0505-A000 86 gateway 38, 65, 66
2198T-NN-318 84 gateway enclosure 74
2198T-NS-318 84 mover 14, 38, 66
power control module 65, 66, 67
2198T-VT0505-A 108 straight motor module 12, 38, 65, 66
2198T-VT0515-A 109 connector locations
2198T-VT1005-A 108 digital USB I/O 56
2198T-VT1010-A 109 gateway 57
2198T-VT1015-A 109 iTRAK power supply 48
2198T-VT1505-A 108 contoller
2198T-VT1510-A 109 compatability 128
2198T-VT1515-A 109
2198T-VTxxxx- 88 D
2198T-VTxxxx-A 14, 84 description
2198T-W25K-ER 16, 47, 48
2198T-WBCMOD 16, 46 iTRAK power supply 48
2198T-WPCM-08 16 dimensions
gateway enclosure 74
PCM 69
A
automatic implantable cardioverter
defibrillator (AICD) 130
E
enclosure
Ethernet ports 102
B error codes 113
bearing e-stop
installation 108 circuit schematic 71
block diagram pinout 70
Ethernet
iTRAK power supply 38
iTRAK power supply safety 124 ports 102
bus cable
preparation 60 F
resisitve loss 42
bus conditioner 38 firmware
description 16 downgrade 104
installation 45, 46 update gateway 102
bus reset 68 update motor module 104
update troubleshooting 104
G lubrication
gateway 75 first time 106
frequency 106
compatability 128 Kluber 4-UH1-68N 84
installation 75 straight nipple fittings 32
weight 75 weep holes 32
wire 57 lubrication pump
gateway enclosure
configuration 35
description 74 description 33
dimension 74 installation 33
guard mounting dimensions 34
circuit schematic 71 volume calculation 35, 106
pinout 70 wire 34
lubrication system
installation
I horizontal 32
installation vertical 32
bus conditioner 45
lubricaiton system horizontal 32
lubricaiton system vertical 32 M
multiple iTRAK power supplies 45 magnet plate
multiple segments 30 handeling 25
track 27 install 86
installation bus conditioner 46 magnetic field strength 22, 25
instructions magnetic plate
bus cable preparation 60 screws 86
installation 27, 75 mechanical and servo components 10
bearings 108 monitor
cable gland 76
cables 75 circuit schematic 72
pinout 70
curved motor module 94
motor module
gateway 75
lubrication wiper 106 compatability 127
magnet plate 86 firmware update 104
mover 88 installation
planning 27, 75 curved 94
position magnet 84 straight 92
power control module 75 numbering 57
straight motor module 92 mount 75
iTRAK power supply gateway 75
block diagram 38 PCM 75
connectors 48 track 27
description 48 mounting holes 29
multiple 45 mover
safey circuit 124 compatability 128
status indicators 78, 79 description 14
wire 59 installation 88
wirirng requirements 51 magnetic field strength 22
replace 88
L
label N
series B motor module 13 number motor modules 57
labels
automated machinery 130
high voltage 130 P
hot surface 130 PCM
series A motor module 13
strong magnets 22 mount 75
leveling feet 30 safety circuit 125
status indicators 68
lifting slots 29 weight 75
loop back connector 58 PCM dimensions 69
pinout U
e-stop 70 USB I/O
gateway to PCM cable 74
guard 70 description 17
monitor 70 wire 56
reset 70
position magnet
magnetic field strength 24
W
power control module warning
circuit breaker automatic implantable cardioverter
10 kW type 2 112 defibrillator (AICD) 130
description 67 powerful forces 130
installation 75 weight
power supply gateway 75
compatability 128 PCM 75
track 28
wire
R gateway 57
replace iTRAK power supply 59
multiple 46
curved motor module 94 single 45
mover 88
lubrication pump 34
position magnet 84
USB I/O 56
reset
bus 68
circuit schematic 70
pinout 70
S
safety
automated machinery 130
handling 27
heat 130
high voltage 130
machine guarding 19
risk assessment 19
strong magnets 22
schematic
e-stop circuit 71
guard circuit 71
monitor circuit 72
power control module safety 125
reset circuit 70
series A
labels 13
series B
label 13
status indicators
iTRAK power supply 78, 79
PCM 68
series A motor module 13
series B motor module 13
T
tags
controller 81
track
installation 27
weight 28
Notes:
Technical Support Center Knowledgebase Articles, How-to Videos, FAQs, Chat, User https://rockwellautomation.custhelp.com/
Forums, and Product Notification Updates.
Local Technical Support Phone Numbers Locate the phone number for your country. http://www.rockwellautomation.com/global/support/get-support-now.page
Find the Direct Dial Code for your product. Use the code to
Direct Dial Codes route your call directly to a technical support engineer. http://www.rockwellautomation.com/global/support/direct-dial.page
Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete the
How Are We Doing? form at http://literature.rockwellautomation.com/idc/groups/literature/documents/du/ra-du002_-en-e.pdf.
Rockwell Automation maintains current product environmental information on its website at http://www.rockwellautomation.com/rockwellautomation/about-us/sustainability-ethics/product-environmental-compliance.page.
Allen-Bradley, CompactLogix ,ControlFLASH, ControlLogix, Integrated Architecture, iTRAK, Kinetix, Rockwell Software, Rockwell Automation, Studio 5000, and Studio 5000 Logix Designer are trademarks of Rockwell Automation, Inc.
EtherNet/IP is a trademark of ODVA, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400