Application Manual

3DRE(E)(A), Z3DRE(E)(A)
Proportional pressure reducing valve with integrated digital
electronics

RE29283-FK/03.23, Edition 01
Copyright
© Bosch Rexroth AG Bosch Rexroth AG© 2023
All rights reserved, also regarding any disposal, exploitation, reproduction, editing, distribution, as well
as in the event of applications for industrial property rights.

Liability
The specified data is intended for product description purposes only and shall not be deemed to be
a guaranteed characteristic unless expressly stipulated in the contract. All rights are reserved with
respect to the content of this documentation and the availability of the product.

d0cfe1d8a421f8200a347e8247321ac4, 1, en_US
3DRE(E)(A), Z3DRE(E)(A) 3 / 112

Table of contents
1 About this documentation 12
1.1 Validity of the documentation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
1.2 Required and amending documentation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
1.3 Representation of information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2 Safety instructions 13
2.1 General information on this chapter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2.2 Intended use. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

Table of contents
2.3 Improper use. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
2.4 Qualification of personnel. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
2.5 General safety instructions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
2.6 Personal protective equipment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
2.7 Obligations of the machine end-user. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3 Overview of the pilot-controlled proportional pressure reducing valves
(Z)3DRE(E,A) 16
3.1 General information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
3.2 Valve types. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
3.2.1 (Z)3DREE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
3.2.2 (Z)3DREA with external pressure sensor. . . . . . . . . . . . . . . . . . . . . 17
3.2.3 (Z)3DREA with integrated pressure sensor. . . . . . . . . . . . . . . . . . . . 19
3.3 Optional Bluetooth® dongle. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
3.4 "easy2connect" smartphone app. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
4 Analog interface – connector XH1 22
4.1 Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
4.2 Pressure command value. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
4.2.1 Functional description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
4.2.2 Relevant parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
4.2.3 Setting via "easy2connect". . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
4.3 Actual pressure value. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
4.3.1 Functional description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
4.3.2 Relevant parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
4.3.3 Setting via "easy2connect". . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

RE29283-FK/03.23, Bosch Rexroth AG


Edition 01
4 / 112 3DRE(E)(A), Z3DRE(E)(A)

4.4 Actual current value (solenoid). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35


4.4.1 Functional description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
4.4.2 Relevant parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
4.4.3 Setting via "easy2connect". . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
5 Digital interface - IO-Link - connector XH5 39
5.1 Process data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
5.1.1 General information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
5.1.2 Process data input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
5.1.3 Process data output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
5.1.4 Relevant parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
5.2 Backup/Restore. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
6 Pressure sensor / Actual pressure value detection 42
6.1 Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
6.2 Internal pressure sensor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
6.3 External pressure sensor – interface X2N . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
6.4 Actual pressure value detection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
6.4.1 Functional description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
6.4.2 Relevant parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
6.4.3 Setting via "easy2connect". . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
7 Controller structure (Z)3DREE 48
7.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
7.2 Pressure command value preparation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
7.2.1 Functional description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
7.2.2 Relevant parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
7.2.3 Setting via "easy2connect". . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
7.3 Solenoid current controller. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
7.3.1 Functional description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
7.3.2 Relevant parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
7.3.3 Setting via "easy2connect". . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
8 Controller structure (Z)3DREA 56
8.1 Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
8.2 Pressure command value preparation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
8.2.1 Functional description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
8.2.2 Relevant parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
8.2.3 Setting via "easy2connect". . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62

Bosch Rexroth AG RE29283-FK/03.23, Edition 01


3DRE(E)(A), Z3DRE(E)(A) 5 / 112

8.3 Actual pressure value filtration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62


8.3.1 Functional description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
8.3.2 Relevant parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
8.3.3 "easy2connect" smartphone app. . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
8.4 Closed-loop pressure control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
8.4.1 Functional description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
8.4.2 Relevant parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
8.4.3 Setting via "easy2connect". . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67

Table of contents
8.5 Solenoid current controller. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
8.5.1 Functional description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
8.5.2 Relevant parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
8.5.3 Setting via "easy2connect". . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
9 Parameter descriptions 70
9.1 P-0-0115 - Valve status word. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
9.1.1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
9.1.2 IO-Link mapping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
9.2 P-0-0116 - Valve control word. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
9.2.1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
9.2.2 IO-Link mapping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
9.3 P-0-0120 - Force mode, control word. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
9.3.1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
9.3.2 IO-Link mapping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
9.4 P-0-0190 - Valve electronics operating hours. . . . . . . . . . . . . . . . . . . . . . . . . . 73
9.4.1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
9.4.2 IO-Link mapping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
9.5 P-0-0670.0.3 - Command: Load factory default values. . . . . . . . . . . . . . . . . . 74
9.5.1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
9.5.2 IO-Link mapping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
9.6 P-0-1520 - Valve electronics type. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
9.6.1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
9.6.2 IO-Link mapping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
9.7 P-0-1910.0.1 - IO-Link: Pressure valve control word. . . . . . . . . . . . . . . . . . . . 74
9.7.1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
9.7.2 IO-Link mapping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75

RE29283-FK/03.23, Bosch Rexroth AG


Edition 01
6 / 112 3DRE(E)(A), Z3DRE(E)(A)

9.8 P-0-1910.0.2 - IO-Link: Pressure valve status word. . . . . . . . . . . . . . . . . . . . . 75


9.8.1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
9.8.2 IO-Link mapping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
9.9 P-0-1910.0.3 - IO-Link: Start data storage backup. . . . . . . . . . . . . . . . . . . . . 77
9.9.1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
9.9.2 IO-Link mapping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
9.10 P-0-1910.0.4 - IO-Link: Device ID. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
9.10.1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
9.10.2 IO-Link mapping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
9.11 P-0-2803 - Pressure command value preparation: Resulting pressure com-
mand value. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
9.11.1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
9.11.2 IO-Link mapping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
9.12 P-0-2875.0.7 - Valve: Nominal pressure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
9.12.1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
9.12.2 IO-Link mapping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
9.13 P-0-2878.0.1 - Force mode: Pressure command value. . . . . . . . . . . . . . . . . . 78
9.13.1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
9.13.2 IO-Link mapping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
9.14 P-0-2885.0.1 - Valve electronics temperature. . . . . . . . . . . . . . . . . . . . . . . . . 78
9.14.1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
9.14.2 IO-Link mapping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
9.15 P-0-2885.0.3 - Actual supply voltage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
9.15.1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
9.15.2 IO-Link mapping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
9.16 P-0-2885.0.20 - Diagnostics: Valve communication - Dongle. . . . . . . . . . . . . 78
9.16.1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
9.16.2 IO-Link mapping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
9.17 P-0-2885.0.21 - Diagnostics: Valve communication - IO-Link. . . . . . . . . . . . . 79
9.17.1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
9.17.2 IO-Link mapping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
9.18 P-0-2885.0.22 - Diagnostics: Life counter. . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
9.18.1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
9.18.2 IO-Link mapping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79

Bosch Rexroth AG RE29283-FK/03.23, Edition 01


3DRE(E)(A), Z3DRE(E)(A) 7 / 112

9.19 P-0-2885.0.23 - Diagnostics: Error overview. . . . . . . . . . . . . . . . . . . . . . . . . . 79


9.19.1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
9.19.2 IO-Link mapping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
9.20 P-0-2885.0.24 - Diagnostics: Error overview (permanent). . . . . . . . . . . . . . . 82
9.20.1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
9.20.2 IO-Link mapping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
9.21 P-0-2885.0.30 - Diagnostics: Firmware update status. . . . . . . . . . . . . . . . . . 84
9.21.1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84

Table of contents
9.21.2 IO-Link mapping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
9.22 P-0-2890.0.3 - pressure controller: Slider (controller behavior). . . . . . . . . . 85
9.22.1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
9.22.2 IO-Link mapping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
9.23 P-0-2890.0.4 - pressure controller: Control word. . . . . . . . . . . . . . . . . . . . . . 85
9.23.1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
9.23.2 IO-Link mapping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
9.24 P-0-2890.0.5 - Pressure command value preparation: Gain. . . . . . . . . . . . . . 86
9.24.1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
9.24.2 IO-Link mapping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
9.25 P-0-2890.0.6 - Solenoid current: Offset. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
9.25.1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
9.25.2 IO-Link mapping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
9.26 P-0-2890.0.7 - Solenoid current: P-gain. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
9.26.1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
9.26.2 IO-Link mapping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
9.27 P-0-2890.0.8 - Solenoid current controller: Dither frequency factor. . . . . . . 87
9.27.1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
9.27.2 IO-Link mapping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
9.28 P-0-2890.0.9 - Actual pressure value: Filter frequency. . . . . . . . . . . . . . . . . . 88
9.28.1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
9.28.2 IO-Link mapping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
9.29 P-0-2890.0.10 - pressure controller: Nozzle diameter flow rate. . . . . . . . . . . 88
9.29.1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
9.29.2 IO-Link mapping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88

RE29283-FK/03.23, Bosch Rexroth AG


Edition 01
8 / 112 3DRE(E)(A), Z3DRE(E)(A)

9.30 P-0-2890.0.11 - pressure controller: Spring force flow rate. . . . . . . . . . . . . . 88


9.30.1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
9.30.2 IO-Link mapping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
9.31 P-0-2890.0.12 - pressure controller: Medium density flow rate. . . . . . . . . . . 89
9.31.1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
9.31.2 IO-Link mapping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
9.32 P-0-2890.0.13 - pressure controller: Valve flow rate. . . . . . . . . . . . . . . . . . . . 89
9.32.1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
9.32.2 IO-Link mapping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
9.33 P-0-2892.0.1 - pressure controller: I-gain. . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
9.33.1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
9.33.2 IO-Link mapping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
9.34 P-0-2892.0.2 - pressure controller: P-gain. . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
9.34.1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
9.34.2 IO-Link mapping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
9.35 P-0-2892.0.3 - pressure controller: Gain, active damping. . . . . . . . . . . . . . . 90
9.35.1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
9.35.2 IO-Link mapping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
9.36 P-0-2892.0.4 - pressure controller: Gain, I-term active damping. . . . . . . . . . 90
9.36.1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
9.36.2 IO-Link mapping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
9.37 P-0-2892.0.5 - pressure controller: Integrator switch-off threshold. . . . . . . . 91
9.37.1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
9.37.2 IO-Link mapping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
9.38 P-0-2892.0.6 - Pressure command value preparation: Ramp time positive. . 91
9.38.1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
9.38.2 IO-Link mapping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
9.39 P-0-2892.0.7 - Pressure command value preparation: Ramp time negative. 92
9.39.1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
9.39.2 IO-Link mapping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
9.40 P-0-2892.0.8 - Pressure command value preparation: Filter frequency. . . . 92
9.40.1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
9.40.2 IO-Link mapping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92

Bosch Rexroth AG RE29283-FK/03.23, Edition 01


3DRE(E)(A), Z3DRE(E)(A) 9 / 112

9.41 P-0-2900.1.1 - Analog command value input: Control word. . . . . . . . . . . . . . 92


9.41.1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
9.41.2 IO-Link mapping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
9.42 P-0-2900.1.8 - Analog command value input: Signal range, lower limit. . . . . 93
9.42.1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
9.42.2 IO-Link mapping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
9.43 P-0-2900.1.9 - Analog command value input: Signal range, upper limit. . . . 94
9.43.1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94

Table of contents
9.43.2 IO-Link mapping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
9.44 P-0-2900.1.10 - Analog command value input: Value range, lower limit. . . . 95
9.44.1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
9.44.2 IO-Link mapping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
9.45 P-0-2900.1.11 - Analog command value input: Value range, upper limit. . . . 95
9.45.1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
9.45.2 IO-Link mapping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
9.46 P-0-2900.2.1 Analog actual pressure value input: Control word. . . . . . . . . . 96
9.46.1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
9.46.2 IO-Link mapping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
9.47 P-0-2900.2.8 Analog actual pressure value input: Signal range, lower limit. 97
9.47.1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
9.47.2 IO-Link mapping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
9.48 P-0-2900.2.9 - Analog actual pressure value input: Signal range, upper limit 97
9.48.1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
9.48.2 IO-Link mapping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
9.49 P-0-2900.2.10 - Analog actual pressure value input: Value range, lower limit 98
9.49.1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
9.49.2 IO-Link mapping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
9.50 P-0-2900.2.11 - Analog actual pressure value input: Value range, upper
limit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
9.50.1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
9.50.2 IO-Link mapping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
9.51 P-0-2907.1.1 - Analog command value input: Actual value. . . . . . . . . . . . . . . 99
9.51.1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
9.51.2 IO-Link mapping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100

RE29283-FK/03.23, Bosch Rexroth AG


Edition 01
10 / 112 3DRE(E)(A), Z3DRE(E)(A)

9.52 P-0-2907.2.1 - Analog actual pressure value input: Actual value. . . . . . . . . . 100
9.52.1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
9.52.2 IO-Link mapping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
9.53 P-0-2908.1.1 - Analog actual value output: Actual value. . . . . . . . . . . . . . . . . 100
9.53.1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
9.53.2 IO-Link mapping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
9.54 P-0-2908.1.2 - Analog actual value output: Control word. . . . . . . . . . . . . . . . 101
9.54.1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
9.54.2 IO-Link mapping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
9.55 P-0-2915.0.3 - Actual current value: Solenoid A. . . . . . . . . . . . . . . . . . . . . . . 101
9.55.1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
9.55.2 IO-Link mapping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
9.56 P-0-4028 - Valve: Control word. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
9.56.1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
9.56.2 IO-Link mapping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
9.57 P-0-4073 - IO link: Diagnosis. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
9.57.1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
9.57.2 IO-Link mapping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
9.58 P-0-4085 - Force mode: Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
9.58.1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
9.58.2 IO-Link mapping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
9.59 S-0-0017 - List of all valve parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
9.59.1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
9.59.2 IO-Link mapping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
9.60 S-0-0030 - Firmware version. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
9.60.1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
9.60.2 IO-Link mapping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
9.61 S-0-0140 - Valve designation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
9.61.1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
9.61.2 IO-Link mapping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
9.62 S-0-0192 - List of all configuration parameters. . . . . . . . . . . . . . . . . . . . . . . . 105
9.62.1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
9.62.2 IO-Link mapping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105

Bosch Rexroth AG RE29283-FK/03.23, Edition 01


3DRE(E)(A), Z3DRE(E)(A) 11 / 112

9.63 S-0-0254 - Current parameter set. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105


9.63.1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
9.63.2 IO-Link mapping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
9.64 S-0-0262 - Command: Load default values. . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
9.64.1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
9.64.2 IO-Link mapping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
9.65 S-0-0264 - Command: Save configuration parameters. . . . . . . . . . . . . . . . . . 106
9.65.1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106

Table of contents
9.65.2 IO-Link mapping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
9.66 S-0-0800 - Pressure command value. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
9.66.1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
9.66.2 IO-Link mapping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
9.67 S-0-0809 - Actual pressure value. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
9.67.1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
9.67.2 IO-Link mapping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
9.68 S-0-0814 - Tank pressure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
9.68.1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
9.68.2 IO-Link mapping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
9.69 S-0-0827 - Pressure control deviation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
9.69.1 Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
9.69.2 IO-Link mapping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
10 Appendix 107
10.1 List of addresses. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
Index 109

RE29283-FK/03.23, Bosch Rexroth AG


Edition 01
12 / 112 3DRE(E)(A), Z3DRE(E)(A)
Required and amending documentation

1 About this documentation


1.1 Validity of the documentation
This documentation is valid for the following products:
• Proportional pressure reducing valve, pilot-controlled, with integrated digital electronics (OBED),
type 3DRE(E)(A) and Z3DRE(E)(A)
This functional description is only valid in conjunction with the "Data Sheet 29283" and the
"Operating Instructions 07600-B", see ⮫ Chapter 1.2 “Required and amending documenta-
tion” on page 12.
Read the functional description, in particular ⮫ Chapter 2 “Safety instructions” on page 13
and the above documents, completely before using the proportional pressure reducing valve.

Trademark
Symbol Meaning
Bluetooth® is a registered trademark of Bluetooth SIG, Inc.

Editions of this documentation


Table 1: Editions of this documentation
Edition Status Comment
01 03.23 Initial version

1.2 Required and amending documentation


Before commissioning the product, make sure to have received and fully understood the documenta-
tions identified by the book symbol and observe the instructions included in these documenta-
tions.
Title Document number Document type
Hydraulic valves and hydroelectric pressure switches R.07600-B Operating instruc-
for industrial applications ⮫ https://boschrex- tions
roth.com
Proportional pressure reducing valve, pilot-con- R.29283 Data sheet
trolled, with or without integrated digital electronics ⮫ https://boschrex-
(OBED) roth.com
Bluetooth® dongle type VT-ZBT-1-1X R.30581-B Operating instruc-
⮫ https://boschrex- tions
roth.com
Bluetooth® dongle type VT-ZBT-1-1X R.30581 Data sheet
⮫ https://boschrex-
roth.com

Bosch Rexroth AG RE29283-FK/03.23, Edition 01


3DRE(E)(A), Z3DRE(E)(A) 13 / 112
General information on this chapter

Title Document number Document type


IO Link Manufacturer's declaration of Conformity for DCTC-31000-198 Manufacturer's dec-
Type (Z)3DRE(E)(A) laration of con-
formity
Pressure transducer for hydraulic applications type R.30270-MON Assembly instruc-
HM20 ⮫ https://boschrex- tions
roth.com

1.3 Representation of information

Safety instructions
The safety instructions in the present application documentation contain certain signal words (danger,
warning, caution, notice) and, if applicable, a signal graphic (according to ANSI Z535.6-2011)
The signal word is intended to draw attention to the safety instructions and denotes the severity of the
hazard.
The signal graphic (warning triangle with exclamation mark), which precedes the signal words danger,
warning and caution, indicates hazards for persons.
DANGER In the case of non-compliance with these safety instructions, death or severe
injury will occur.
WARNING In the case of non-compliance with these safety instructions, death or severe
injury may occur.
CAUTION In the case of non-compliance with these safety instructions, minor or mod-
erate injury may occur.
NOTICE In the case of non-compliance with these safety instructions, damage to
property may occur.

Designations
The following designations are used in this documentation:
Designation Meaning
VT-ZBT-1-1X Bluetooth® dongle

2 Safety instructions
2.1 General information on this chapter
The product has been manufactured according to the generally accepted codes of practice. However,
there is still the danger of personal injury and damage to property if you do not observe this chapter and
the safety instructions in this documentation.
• Read this documentation completely and thoroughly before working with the product.
• Keep this documentation in a location where it is accessible to all users at all times.
• Always include the required documentation when passing the product on to third parties.

RE29283-FK/03.23, Bosch Rexroth AG


Edition 01
14 / 112 3DRE(E)(A), Z3DRE(E)(A)
Qualification of personnel

2.2 Intended use


The valve is an electrically pilot-controlled proportional pressure reducing valve with pressure limitation
of the actuator.
The valve is exclusively intended for integration into a machine or system or to be assembled with other
components to form a machine or system. The product may be commissioned only if it is integrated
in the machine/system for which it is designed. The operating conditions and performance limits
specified in the "data sheet" must be observed.
The valve may be used as follows:
• For reducing a system pressure.
The valve may not be used in potentially explosive atmospheres.
The product is only intended for professional use and not for private use. Intended use includes having
read and understood this documentation, especially ⮫ Chapter 2 “Safety instructions” on page 13.

2.3 Improper use


Any use deviating from the intended use is improper and thus not admissible. Improper use voids
any warranty claims. It is also regarded as improper use if the valve is operated outside the indicated
performance limits and operating conditions, especially the required environmental conditions.
Bosch Rexroth AG does not assume any liability for damage caused by improper use. The user assumes
responsibility for all risks surrounding improper use.

2.4 Qualification of personnel


The activities described in this documentation require basic knowledge of mechanics, electrics,
hydraulics and pneumatics as well as knowledge of the appropriate technical terms. For transporting
and handling the product, additional knowledge of how to handle lifting gear and the necessary
attachment devices is required. In order to ensure safe use, these activities may only be carried out
by an expert in the respective field or an instructed person under the direction and supervision of
an expert. Experts are those who can recognize potential dangers and apply the appropriate safety
measures due to their professional training, knowledge and experience, as well as their understanding
of the relevant conditions pertaining to the work to be undertaken. An expert must observe the relevant
specific professional rules and have the necessary expert knowledge.
Expert knowledge means for example for hydraulic products:
• Reading and completely understanding hydraulic schemes,
• in particular, completely understanding the relationships regarding the safety equipment and
• Having knowledge of the function and set-up of hydraulic components.
Bosch Rexroth offers measures supporting training in specific fields. An overview of the
training contents can be found online at:
⮫ https://boschrexroth.com

Bosch Rexroth AG RE29283-FK/03.23, Edition 01


3DRE(E)(A), Z3DRE(E)(A) 15 / 112
Obligations of the machine end-user

2.5 General safety instructions


• Observe the valid regulations on accident prevention and environmental protection.
• Observe the safety regulations and provisions of the country in which the product is used/applied.
• Only use Bosch Rexroth products in a technically perfect condition.
• Observe all information on the product.
• Persons assembling, operating, disassembling or maintaining Rexroth products may not be under
the influence of alcohol, other drugs or medication influencing the ability to react.
• Only use original Bosch Rexroth accessories and spare parts in order to prevent any hazard to
persons due to unsuitable spare parts.

Safety instructions
• Comply with the technical data and environmental conditions specified in the product documenta-
tion.
• The installation or use of inappropriate products in safety-relevant applications could result in unin-
tended operating states which in turn could cause personal injuries and/or damage to property.
Therefore, only use a product for safety-relevant applications if this use is expressly specified
and permitted in the documentation of the product, e.g. in explosion protection zones or in
safety-related parts of control systems (functional safety).
• Do not commission the product until you can be sure that the end product (for example a machine
or system) where the Bosch Rexroth products are installed complies with the country-specific
provisions, safety regulations and standards of the application.

2.6 Personal protective equipment


The machine end-user must provide the personal protective equipment (such as gloves, working shoes,
safety goggles, working clothes, etc...).

2.7 Obligations of the machine end-user


The machine end-user of the product is responsible for ensuring that:
• the product is only used according to the intended use as defined in this documentation.
• the operating personnel are instructed at regular intervals.
• a danger zone is marked, if required.
• the safety measures for the specific area of application of the product are complied with.

IT security
The operation of installations, systems and machines basically requires the implementation of a holistic
IT security concept which is state-of-the-art in terms of technology. Accordingly, Bosch Rexroth prod-
ucts and their properties have to be considered as components of installations, systems and machines
for their holistic IT security concept. Unless otherwise documented, Bosch Rexroth products are
designed for operation in local, physically and logically secured networks with access restrictions for
authorized persons, and they are not classified according to IEC 62443-4-2.

RE29283-FK/03.23, Bosch Rexroth AG


Edition 01
16 / 112 3DRE(E)(A), Z3DRE(E)(A)
Valve types

3 Overview of the pilot-controlled proportional pressure


reducing valves (Z)3DRE(E,A)
3.1 General information
The valves of this valve family are electrically pilot-controlled 3-way pressure reducing valves with
pressure limitation of the actuator. They are used for reducing a system pressure. The valves are
parameterized in accordance with the ordering codes ex works and delivered fully functional. For
optimum adaptation to the hydraulic use of the valve, the "easy2connect" smartphone app, which is
available free of charge, can be used to optimize the parameter setting of the valve (e.g. setting the
pressure control).
The more precise hydraulic functionality of the valve can be taken from the "data sheet
29283".

3.2 Valve types


The following valve types are differentiated in the valve family of pilot-controlled proportional pressure
reducing valves:
• (Z)3DREE
• (Z)3DREA with external pressure sensor
• (Z)3DREA with integrated pressure sensor

3.2.1 (Z)3DREE
The following shows the set-up and function of the valve type (Z)3DREE:

Bosch Rexroth AG RE29283-FK/03.23, Edition 01


3DRE(E)(A), Z3DRE(E)(A) 17 / 112
Valve types

Overview of the pilot-controlled proportional


Digital interface Command
value preparation Current control

pressure reducing valves (Z)3DRE(E,A)


Pressure command value

Actual pressure value Conversion to actual


pressure value

Pressure command value

Actual current value

Analog interface Actual current


Control value
A1 / F1 value

Solenoid

Fig. 1: Overview_(Z)3DREE
On the proportional solenoid, there is the digital on-board electronics (OBED). This is equipped with
one of the following electrical interfaces, via which the command and actual values are exchanged
digitally or analogously with a higher-level control:
• Digital interface L1, IO-Link (connector XH5)
• Analog interface (connector XH1)
– Interface "A1", (command value and actual value 0 ... 10 V)
– Interface "F1", (command value and actual value 4 ... 20 mA)
The pressure command value obtained from the higher-level control is converted in the on-board
electronics into a current command value corresponding to the pressure. This current command value
is preset and regulated as a control value for the proportional solenoid. The predetermined pressure
command value is thus set as the actual pressure value.

3.2.2 (Z)3DREA with external pressure sensor


The following shows the set-up and function of valve type (Z)3DREA with external pressure sensor:

RE29283-FK/03.23, Bosch Rexroth AG


Edition 01
18 / 112 3DRE(E)(A), Z3DRE(E)(A)
Valve types

External pressure
sensor connection
via interface X2N

Digital interface Actual pressure value


Command value Closed-loop Current
pressure
Pressure command value preparation
control control

Actual pressure value

Pressure command value

Actual pressure value

Analog interface Actual Control


current value value
A1 / F1

Solenoid

Fig. 2: Overview_(Z)3DREA
On the proportional solenoid, there is the digital on-board electronics (OBED). This is equipped with
one of the following electrical interfaces, via which the command and actual values are exchanged
digitally or analogously with a higher-level control:
• Digital interface L1, IO-Link (connector XH5)
• Analog interface (connector XH1)
– Interface "A1", (command value and actual value 0 ... 10 V)
– Interface "F1", (command value and actual value 4 ... 20 mA)
The pressure command value obtained from the higher-level control is regulated in the on-board
electronics. The actual pressure value is detected via an external pressure sensor connected to the
interface X2N.
The type HM 20-2X/400-H-C19-0,16-N (R901518764) is recommended as external pressure sensor.
This pressure sensor is factory set.

Bosch Rexroth AG RE29283-FK/03.23, Edition 01


3DRE(E)(A), Z3DRE(E)(A) 19 / 112
Optional Bluetooth® dongle

3.2.3 (Z)3DREA with integrated pressure sensor


The following shows the set-up and function of the valve type (Z)3DREA with integrated pressure
sensor:

Overview of the pilot-controlled proportional


pressure reducing valves (Z)3DRE(E,A)
Digital interface
Command Closed-loop
pressure control Current control
value preparation
Pressure command value

Actual pressure value

Actual pressure value


Pressure command value

Actual pressure value

Analog interface Actual


Control value
A1 / F1 current value

Integrated
Solenoid
pressure sensor

Fig. 3: Overview_(Z)3DREA_Pressure sensor, integrated


On the proportional solenoid, there is the digital on-board electronics (OBED). This is equipped with
one of the following electrical interfaces, via which the command and actual values are exchanged
digitally or analogously with a higher-level control:
• Digital interface L1, IO-Link (connector XH5)
• Analog interface (connector XH1)
– Interface "A1", (command value and actual value 0 ... 10 V)
– Interface "F1", (command value and actual value 4 ... 20 mA)
The pressure command value obtained from the higher-level control is regulated in the on-board
electronics. The actual pressure value is detected by a pressure sensor integrated in the valve.

3.3 Optional Bluetooth® dongle


The digital on-board electronics (OBED) provides a digital service interface for the pressure valve via
an optional Bluetooth® dongle. As an option, the Bluetooth® dongle can be ordered directly with the
pressure valve or retrofitted later (VT-ZBT-1-1X).

RE29283-FK/03.23, Bosch Rexroth AG


Edition 01
20 / 112 3DRE(E)(A), Z3DRE(E)(A)
Optional Bluetooth® dongle

Smartphone app
easy2connect

Optional
Bluetooth® dongle

Fig. 4: Overview_BluetoothDongle
With the "easy2connect" smartphone app, a connection via Bluetooth® to the valve can be established
via the Bluetooth® dongle. Further information on the "easy2connect" smartphone app can be found in
the following chapter.
The Bluetooth® dongle also has an integrated diagnostic LED. The current state of the valve and the
dongle are displayed via different colors and different flashing codes of the diagnostic LED.

Bosch Rexroth AG RE29283-FK/03.23, Edition 01


3DRE(E)(A), Z3DRE(E)(A) 21 / 112
"easy2connect" smartphone app

Integrated

Overview of the pilot-controlled proportional


diagnostic LED

pressure reducing valves (Z)3DRE(E,A)


Fig. 5: Overview_Diagnostic LED
For further information on the Bluetooth® dongle, see the "Data Sheet 30581" or the "Oper-
ating Instructions 30581-B" .

3.4 "easy2connect" smartphone app


If a Bluetooth® dongle is mounted on the digital on-board electronics (OBED) of the valve, a connection
to the valve can be established using the "easy2connect" smartphone app.

The connection to
the valve is
via Bluetooth®

Fig. 6: easy2connect_Connection
The following functionalities are available in the "easy2connect" smartphone app:
• Electronic valve name plate
• Status and diagnosis of the valve
• Force mode, command value presetting via the app

RE29283-FK/03.23, Bosch Rexroth AG


Edition 01
22 / 112 3DRE(E)(A), Z3DRE(E)(A)
Overview

• Optimization of valve parameterization


• Valve and Bluetooth® dongle firmware update
The "easy2connect" smartphone app is available for the iOS and Android operating systems.
The "easy2connect app" can be downloaded from the Apple App Store (iOS) or Google Play
Store (Android).
• Apple App Store
⮫ https://apps.apple.com
• Google Play Store
⮫ https://play.google.com

4 Analog interface – connector XH1


4.1 Overview
The digital on-board electronics (OBED) of the pressure valve can be ordered with different electrical
interfaces. Command and actual values are exchanged with a higher-level control via the interface. A
variant is the analog interface, in which the command and actual values are transmitted in an analog
form.

Actual pressure
value / actual
current value
(Solenoid)

Pressure command
value

Analog interface
connector XH1

Fig. 7: Analog interface_Connector assignment

Bosch Rexroth AG RE29283-FK/03.23, Edition 01


3DRE(E)(A), Z3DRE(E)(A) 23 / 112
Pressure command value

Assignment of the connector XH1


The following table shows the assignment of the individual pins for the analog interface of the
connector XH1:
Pin Interface
Version A1 Version F1
A 24 VDC supply voltage

Analog interface – connector XH1


B 0 V (ground)
C Reference potential actual value on pin F
D Command value 0 … 10 V Command value 4 … 20 mA
E Reference potential command value on pin D
F Actual value 0 … 10 V Actual value 4 … 20 mA
PE Functional ground
The exact electric specification of the analog interface of the connector XH1 can be found in
the "data sheet".

Version A1 and F1
The analog interface of the connector is set ex works, corresponding to the selected order option of the
valve, in version A1 or F1.
• Version A1
In version A1, the pressure command value and the actual pressure value or actual current value
are mapped to a voltage range of 0 to 10 V.
• Version F1
In version F1, the pressure command value and the actual pressure value or actual current value are
mapped to a current range of 4 to 20 mA.

4.2 Pressure command value


4.2.1 Functional description
The pressure command value is predetermined as a voltage or current signal via the pins D and E of the
connector XH1 of the valve. In the OBED, the read-in voltage or the read-in current is mapped into a
corresponding pressure command value. This principle is shown in the following graphic:

RE29283-FK/03.23, Bosch Rexroth AG


Edition 01
24 / 112 3DRE(E)(A), Z3DRE(E)(A)
Pressure command value

Analog input
Analog interface actual value
connector XH1

[bar]

Pressure command value


Voltage
Pressure
x command
value
Current
Type of signal Active
[V],
Analog command value [mA]

Conversion:
analog command value in
pressure command value 0 bar

Cable break
3.3 mA … 3.6 mA Signal error Set
Overload detected error bit
> 30 mA

Signal exceedance Signal error Set


20.3 mA ... 20.6 mA
detected error bit

Fig. 8: Pressure command value1

Type of signal
The type of signal is used to set whether the analog command value of the connector XH1 is predeter-
mined as a voltage signal in the range from 0 to 10 V or as a current signal in the current range from 4 to
20 mA.

Activation bit
The mapping of the voltage or current signal of the analog command value input to the corresponding
pressure command value is activated via the activation bit.

Bosch Rexroth AG RE29283-FK/03.23, Edition 01


3DRE(E)(A), Z3DRE(E)(A) 25 / 112
Pressure command value

Conversion of the analog command value to a pressure command value


The conversion of the analog command value into a pressure command value is shown in detail below:

Pressure command value


[bar]

Analog interface – connector XH1


y2
Value range, upper limit

Analog command
y1
Value range, lower limit value input
x1 x2
[V], [mA]

Signal range, Signal range,


lower limit upper limit

Fig. 9: Pressure command value3


Over the two coordinates x1, y1 (lower limit: signal range, value range) and x2, y2 (upper limit: signal
range, value range) a straight equation is defined. The voltage or current signal currently present at the
analog command value input is converted into the corresponding pressure command value in bar via
this straight equation.

Value range ( y2 - y1 )
Pressure command value (bar ) = ´ (( Command value input ( V or . mA ) - x1) + y 1
Signal range ( x2 - x1 )

Fig. 10: Command pressure value formula

RE29283-FK/03.23, Bosch Rexroth AG


Edition 01
26 / 112 3DRE(E)(A), Z3DRE(E)(A)
Pressure command value

Version A1
When the pressure valve is delivered ex works in version A1, the valve is parameterized so that the
voltage signal range 0 ... 10 V is mapped to a pressure command value range of 0 ... nominal pressure
(in bar) at the analog command value input.

Pressure command value


[bar]

Nominal pressure of the y2


pressure valve (e.g. 200 bar)

Analog command
y1
0 bar value input
x1 x2
[V]
0V 10 V

Fig. 11: Pressure command value4


Example:
Nominal pressure of the valve = 200 bar, command value input = 1 V

200bar
Pressure command value (bar ) = ´ (1V - 0V ) + 0bar = 20bar
10V

Fig. 12: Command pressure value 1 formula

Bosch Rexroth AG RE29283-FK/03.23, Edition 01


3DRE(E)(A), Z3DRE(E)(A) 27 / 112
Pressure command value

Version F1
When the valve is delivered ex works in version F1, the valve is parameterized so that the current signal
range 4 ... 20 mA is mapped to a pressure command value range of 0 ... nominal pressure (in bar) at the
analog command value input.

Pressure command value

Analog interface – connector XH1


[bar]

Nominal pressure of the y2


pressure valve (e.g. 200 bar)

Analog command
y1
0 bar value input
x1 x2
[mA]
4 mA 20 mA

Fig. 13: Pressure command value5


Example:
Nominal pressure of the valve = 200 bar, command value input = 12 mA

200bar
Pressure command value (bar ) = ´ (12mA - 4mA) + 0bar = 100bar
16mA

Fig. 14: Command pressure value 2 formula

Maximum adjustable signal range


As a result of the electronics of the pressure valve, the maximum adjustable signal range of the analog
command value input (lower and upper limit) is limited to certain values which can be taken from the
following table.
Command value input configured Maximum adjustable signal range
as Lower limit Upper limit
Voltage (A1) -0.5 V 10.5 V
Current (F1) 3.2 mA 20.8 mA

RE29283-FK/03.23, Bosch Rexroth AG


Edition 01
28 / 112 3DRE(E)(A), Z3DRE(E)(A)
Pressure command value

Signal monitoring of the command value input (version F1)


In the case of valves which are delivered ex works in version F1, the current signal read in by the
command value input is automatically checked for cable break (-> undercurrent), signal overflow (->
over-current) and overload.
If a cable break or overload has been detected, the pressure command value is set to the value 0 bar
as error reaction and the corresponding error bit is set. When a signal is exceeded, only the associated
error bit is set, the pressure command value is not affected.
Once the error case has been fixed, the pressure command value is restored to normal. This does not
require manual intervention, such as acknowledging the error.
Signal thresholds for cable break, signal exceedance and overload:
The following table shows from which signal threshold a cable break, a signal exceedance or an
overload is detected and automatically acknowledged.
Command Cable break Signal exceedance Overload
value input Identification Acknowledg- Identification Acknowledg- Identification Acknowledg-
configured as ment ment ment
Current (F1) < 3.3 mA ³ 3.6 mA > 20.3 mA £ 20.3 mA > 30 mA 0 mA
The monitoring for cable break, signal exceedance and overload is only active if the signal
range of the command value input (lower and upper limit) is set according to the following
table.
Command value input configured Maximum adjustable signal range
as Lower limit Upper limit
Current (F1) ³ 3.6 mA £ 20.3 mA

4.2.2 Relevant parameters


The following parameters are relevant for mapping the voltage or current signal of the analog command
value input to the corresponding pressure command value.
⮫ Chapter 9.66 “S-0-0800 - Pressure command value” on page 106
⮫ Chapter 9.12 “P-0-2875.0.7 - Valve: Nominal pressure” on page 77
⮫ Chapter 9.19 “P-0-2885.0.23 - Diagnostics: Error overview” on page 79
⮫ Chapter 9.51 “P-0-2907.1.1 - Analog command value input: Actual value” on page 99
⮫ Chapter 9.41 “P-0-2900.1.1 - Analog command value input: Control word” on page 92
⮫ Chapter 9.42 “P-0-2900.1.8 - Analog command value input: Signal range, lower limit” on page 93
⮫ Chapter 9.43 “P-0-2900.1.9 - Analog command value input: Signal range, upper limit” on page 94
⮫ Chapter 9.44 “P-0-2900.1.10 - Analog command value input: Value range, lower limit” on page 95
⮫ Chapter 9.45 “P-0-2900.1.11 - Analog command value input: Value range, upper limit” on page 95

Bosch Rexroth AG RE29283-FK/03.23, Edition 01


3DRE(E)(A), Z3DRE(E)(A) 29 / 112
Pressure command value

4.2.3 Setting via "easy2connect"


In the "easy2connect" smartphone app, the settings for the pressure command value can be adjusted in
the "Command values" screen if the factory settings of the valve are still to be optimized.

Analog interface – connector XH1


Actual value on the analog command value input

Settings for mapping the voltage or current


signal of the analog command value input to
the corresponding pressure command value

Command values screen

Fig. 15: Command values screen

RE29283-FK/03.23, Bosch Rexroth AG


Edition 01
30 / 112 3DRE(E)(A), Z3DRE(E)(A)
Actual pressure value

4.3 Actual pressure value


4.3.1 Functional description
In the case of pressure valves with an integrated or external pressure sensor, the current actual
pressure value is output as a voltage or current signal via the pins C and F of the connector XH1 of
the valve. In the OBED, the actual pressure value currently measured is converted into a corresponding
voltage or current value. This principle is shown in the following figure:

External pressure sensor


Analog
output
Pressure
actual value
sensor error

Analog
interface
[V], [mA]
connector XH1
0V
Analog actual value

0 mA Voltage
Actual
pressure x
value
Active Current
Type of signal
[bar]
Actual pressure value

Conversion:
Actual pressure value -> analog actual value

Integrated pressure sensor

Fig. 16: Actual pressure value1

Type of signal
The type of signal is used to set whether the actual pressure value of the connector XH1 is to be output
as a voltage signal in the range from 0 to 10 V or as a current signal in the current range from 4 to 20 mA
as an analog signal.

Activation bit
The output of the actual pressure value to the analog actual value output is activated via the activation
bit.

Bosch Rexroth AG RE29283-FK/03.23, Edition 01


3DRE(E)(A), Z3DRE(E)(A) 31 / 112
Actual pressure value

Conversion of the actual pressure value into an analog actual value


The following is a detailed illustration of how the actual pressure value currently measured is converted
into the corresponding voltage or current signal at the analog command value output:

Analog actual value


[V], [mA]

Analog interface – connector XH1


Signal range of the
analog actual value output
0 … 10 V, 4 … 20 mA

Signal range offset Actual pressure value


[bar]
0 bar Nominal pressure
of the pressure valve
(e.g. 200 bar)

Fig. 17: Actual pressure value3


The current actual pressure value in bar is converted into the corresponding voltage or current signal at
the analog actual value output via the following straight line equation.

Signal range
Actual value output (V or . mA) = ´ Actual pressure value (bar ) + Offset (Signal range)
Nominal pressure

Fig. 18: Actual pressure value formula

RE29283-FK/03.23, Bosch Rexroth AG


Edition 01
32 / 112 3DRE(E)(A), Z3DRE(E)(A)
Actual pressure value

Version A1
When the pressure valve is delivered ex works in version A1, the pressure valve is parameterized such
that the actual pressure value is mapped in a range of 0 ... nominal pressure (in bar) to a signal range of
0 ... 10 V at the analog actual value output.

Analog actual value


[V]

Signal range 0 … 10 V

Actual pressure value


[bar]
0 bar Nominal pressure
of the pressure valve
(e.g. 200 bar)

Fig. 19: Actual pressure value4


Example:
Nominal pressure of the valve = 200 bar, actual pressure value = 40 bar

10V
Actual value output (V ) = ´ 40bar + 0V = 2V
200bar

Fig. 20: Actual pressure value 1 formula

Bosch Rexroth AG RE29283-FK/03.23, Edition 01


3DRE(E)(A), Z3DRE(E)(A) 33 / 112
Actual pressure value

Version F1
When the pressure valve is delivered ex works in version F1, the pressure valve is parameterized such
that the actual pressure value is mapped in a range of 0 ... nominal pressure (in bar) to a signal range of
4 ... 20 mA at the analog actual value output.

Analog actual value

Analog interface – connector XH1


[mA]

Signal range 4 … 20 mA = 16 mA

Signal range offset = 4 mA Actual pressure value


[bar]
0 bar Nominal pressure
of the pressure valve
(e.g. 200 bar)

Fig. 21: Actual pressure value5


Example:
Nominal pressure of the valve = 200 bar, actual pressure value = 40 bar

16mA
Actual value output ( mA) = ´ 40bar + 4mA = 7,2mA
200bar

Fig. 22: Actual pressure value 2 formula

Pressure sensor error


If there are cable break or overload errors at the pressure sensor, then the voltage or current signal is
output at 0V or 0mA on the actual value output. If the signal is exceeded, the signal at the actual value
output is not affected.

4.3.2 Relevant parameters


The following parameters are relevant for mapping the actual pressure value to the corresponding
voltage or current signal at the analog actual value output.
⮫ Chapter 9.67 “S-0-0809 - Actual pressure value” on page 106
⮫ Chapter 9.12 “P-0-2875.0.7 - Valve: Nominal pressure” on page 77
⮫ Chapter 9.53 “P-0-2908.1.1 - Analog actual value output: Actual value” on page 100

RE29283-FK/03.23, Bosch Rexroth AG


Edition 01
34 / 112 3DRE(E)(A), Z3DRE(E)(A)
Actual pressure value

⮫ Chapter 9.54 “P-0-2908.1.2 - Analog actual value output: Control word” on page 101

4.3.3 Setting via "easy2connect"


In the "easy2connect" smartphone app, the settings for the output of the actual pressure value can be
adjusted in the "Actual values" screen if the factory settings of the valve are still to be optimized.

Actual value on the analog actual value output

Settings for the actual pressure value


output as voltage or current signal on
the analog actual value output

Actual values screen

Fig. 23: Actual values screen

Bosch Rexroth AG RE29283-FK/03.23, Edition 01


3DRE(E)(A), Z3DRE(E)(A) 35 / 112
Actual current value (solenoid)

4.4 Actual current value (solenoid)


4.4.1 Functional description
In the case of pressure valves without a pressure sensor, the current solenoid current (= actual current
value of the solenoid) is output via the pins F and C of the connector XH1 of the valve as a voltage or
current signal. In the OBED, the currently measured solenoid current is converted into a corresponding
voltage or current value. This principle is shown in the following figure.

Analog interface – connector XH1


No pressure sensor!

Analog output
actual value

Analog interface
connector XH1
[V], [mA]
Analog actual value

Voltage
Solenoid
current
Current
Active Type of signal
[mA]
Solenoid current
Conversion:
Solenoid current -> analog actual value

Fig. 24: Actual current value1

Type of signal
The type of signal is used to set whether the solenoid current on the connector XH1 is to be output as an
analog voltage signal in the range from 0 to 10 V or as an analog current signal in the current range from
4 to 20 mA.

Activation bit
The output of the solenoid current to the analog actual value output is activated via the activation bit.

RE29283-FK/03.23, Bosch Rexroth AG


Edition 01
36 / 112 3DRE(E)(A), Z3DRE(E)(A)
Actual current value (solenoid)

Conversion of the actual current value into an analog actual value


The following is a detailed illustration of how the solenoid current currently measured is converted into
the corresponding voltage or current signal at the analog actual value output.

Analog actual value


[V], [mA]

Signal range of the


analog actual value output
0 … 10 V, 4 … 20 mA

Signal range offset Solenoid current


[mA]
0 mA 2000 mA

Fig. 25: Actual current value3


The current actual pressure value in bar is converted into the corresponding voltage or current signal at
the analog actual value output via the following straight line equation.

Signal range
Actual value output (V or . mA ) = ´ Solenoid current ( mA ) + Offset ( Signal range )
2000 mA

Fig. 26: Solenoid current formula

Bosch Rexroth AG RE29283-FK/03.23, Edition 01


3DRE(E)(A), Z3DRE(E)(A) 37 / 112
Actual current value (solenoid)

Version A1
When the pressure valve is delivered ex works in version A1, the pressure valve is parameterized such
that the solenoid current is mapped in a range of 0 ... 2000 mA to a signal range of 0 ... 10 V at the
analog actual value output.

Analog actual value

Analog interface – connector XH1


[V]

Signal range 0 … 10 V

Solenoid current
[mA]
0 mA 2000 mA

Fig. 27: Solenoid current2


Example:
Solenoid current: 500 mA

10V
Actual value output (V ) = ´ 500mA + 0V = 2,5V
2000mA

Fig. 28: Solenoid current 2 formula

RE29283-FK/03.23, Bosch Rexroth AG


Edition 01
38 / 112 3DRE(E)(A), Z3DRE(E)(A)
Actual current value (solenoid)

Version F1
When the pressure valve is delivered ex works in version F1, the pressure valve is parameterized such
that the solenoid current is mapped in a range of 0 ... 2000 mA to a signal range of 4 ... 20 mA at the
analog actual value output.

Analog actual value


[mA]

Signal range 4 … 20 mA = 16 mA

Signal range offset = 4 mA Solenoid current


[mA]
0 mA 2000 mA

Fig. 29: Solenoid current3


Example:
Actual current value = 500 mA

16mA
Actual value output (mA) = ´ 500mA + 4mA = 8mA
2000mA

Fig. 30: Solenoid current 3 formula

4.4.2 Relevant parameters


The following parameters are relevant for mapping the solenoid current to the corresponding voltage or
current signal at the analog actual value output.
⮫ Chapter 9.55 “P-0-2915.0.3 - Actual current value: Solenoid A” on page 101
⮫ Chapter 9.12 “P-0-2875.0.7 - Valve: Nominal pressure” on page 77
⮫ Chapter 9.53 “P-0-2908.1.1 - Analog actual value output: Actual value” on page 100
⮫ Chapter 9.54 “P-0-2908.1.2 - Analog actual value output: Control word” on page 101

4.4.3 Setting via "easy2connect"


In the "easy2connect" smartphone app, there is currently no screen available in which the output of the
solenoid current can be adjusted as a voltage or current signal on the analog actual value output.

Bosch Rexroth AG RE29283-FK/03.23, Edition 01


3DRE(E)(A), Z3DRE(E)(A) 39 / 112
Process data

5 Digital interface - IO-Link - connector XH5


5.1 Process data
5.1.1 General information

Digital interface - IO-Link - connector XH5


The IO-Link process data of the pressure valves consists of a 32-bit rigid mapping of the cyclic data and
is composed of a 32-bit value with input data (-> Process data input) and a 32-bit value with output
data (-> Process data output). The process data is used for both open and closed-loop controlled
pressure valves.

5.1.2 Process data input


The input data consists of the actual pressure value and a 16-bit status word.

RE29283-FK/03.23, Bosch Rexroth AG


Edition 01
40 / 112 3DRE(E)(A), Z3DRE(E)(A)
Process data

IO-Link-Master

MSB LSB
31 16 15 0

Force mode
Reserved

Feedback value

Reserved

Closed-loop pressure control active

Reserved

Command value reached


Reserved

Active parameter set


Ready for operation

Error
Warning
Name Description Valve in operation
Data type
Bit Bit
Value range / comment
offset lenght
Reserved -- -- 30 2
Nominal pressure of the valve
Feedback value Actual pressure value IntegerT 16 14 in bar, factor 0,1
Example: 200 bar -> 0 to 2000
1: Valve ready for operation
Ready for operation BooleanT 15 1
0: Valve not ready for operation
1: Valve control is active Command values are processed
Valve in operation BooleanT 14 1
0: Valve control is not active cylically.
1: Error occured in the valve
Error BooleanT 13 1
0: Nor error in the valve
1: Warning occured in the valve
Warning BooleanT 12 1 For future use.
0: No warning in the valve
Reserved -- -- 10 2
1: Force-Mode aktiv
Force mode BooleanT 9 1
0: Force-Mode nicht aktiv
Closed-loop Closed-loop pressure control can
1: Closed-loop pressure control active
pressure control BooleanT 8 1 only be activated for valves with
0: Open-loop pressure control active
active pressure sensor.
Reserved -- -- 4 4
Command value 1: Pressure command value reached
BooleanT 3 1
reached 0: Pressure command value not reached
Reserved -- -- 2 1
0: Parameter set 0
Active parameter 1: Parameter set 1
Number of the active parameter set UIntegerT 0 2
set 2: Parameter set 2
3: Parameter set 3

Fig. 31: Process data input


In the case of pressure valves without a pressure sensor, instead of the actual pressure value,
the currently effective pressure command value is returned as the actual value.

5.1.3 Process data output


The output data consists of the pressure command value and a 16-bit control word.

Bosch Rexroth AG RE29283-FK/03.23, Edition 01


3DRE(E)(A), Z3DRE(E)(A) 41 / 112
Process data

IO-Link-Master

Digital interface - IO-Link - connector XH5


MSB LSB
31 16 15 0
Reserved

Command value

Enable valve control

Reserved

Activate closed-loop pressure control

Reserved

Reset error

Reserved

Select parameter set


Bit Bit
Name Description Data type Value range / comment
offset length
Reserved -- -- 30 2
Nominal value of the valve
Command value Acual pressure command value IntegerT 16 14 in bar, factor 0,1
Example: 200 bar -> 0 to 2000

Enable valve 1: Valve power stage is active.


BooleanT 15 1
control 0: Valve power stage is not active.
Reserved -- -- 9 6
Activate closed- Closed-loop pressure control
1: Activate closed-loop pressure control
loop pressure BooleanT 8 1 can only be activated for
0: Activate open-loop pressure control
control valves with pressure sensor.
Reserved -- -- 6 2
1: Error reset is active.
Error reset BooleanT 5 1 For future use.
0: Error reset is not active.
Reserved -- -- 2 3
0: Parameter set 0
Select parameter 1: Parameter set 1
Command value of active parameter set UIntegerT 0 2
set 2: Parameter set 2
3: Parameter set 3

Fig. 32: Process data output

5.1.4 Relevant parameters


The following parameters are relevant for cyclic IO-Link communication:
⮫ Chapter 9.7 “P-0-1910.0.1 - IO-Link: Pressure valve control word” on page 74
⮫ Chapter 9.8 “P-0-1910.0.2 - IO-Link: Pressure valve status word” on page 75
⮫ Chapter 9.11 “P-0-2803 - Pressure command value preparation: Resulting pressure command
value” on page 77
⮫ Chapter 9.66 “S-0-0800 - Pressure command value” on page 106
⮫ Chapter 9.67 “S-0-0809 - Actual pressure value” on page 106

RE29283-FK/03.23, Bosch Rexroth AG


Edition 01
42 / 112 3DRE(E)(A), Z3DRE(E)(A)
Internal pressure sensor

5.2 Backup/Restore
IO-Link has a data storage function that makes it easy to swap a device. In this case, certain objects
of the device are linked to the data storage mechanism and these are stored within the IO-Link master
used.
Up to 2048 bytes of object data can be stored per device in the IO-Link master. A checksum is formed
over all objects in order to be able to detect changes in the device. In the event of a change, all data
storage objects can be automatically reloaded into the device during the IO-Link start-up depending on
the configuration in the IO-Link master.
If objects in the device are modified manually, for example, via a Bluetooth connection, a command for
updating the data storage objects can be sent to the IO-Link master (data storage upload request). If
the master receives this command, the master can read and save again all objects linked to the data
storage mechanism, if configured appropriately.
If the user wants to trigger a data storage backup themselves, the command can also be trig-
gered by the IO-Link master (system command "ParamDownloadStore"). The command parameter
"P-0-1910.0.3, Data storage upload request" can be used to start the command via the Bluetooth
connection. If this value is set to "0x3", a data storage backup is requested in the IO-Link device.
As soon as the master has performed the data storage backup, the command parameter is reset to
the value "0". The list of objects associated with the data storage mechanism can be read from the
IO-Link master during the start-up via "Index 0x0003, Subindex 0x05, Index_List" in the device. The
checksum of the data storage objects can be read from the device via "Index 0x0003, Subindex 0x04,
Parameter_Checksum".

6 Pressure sensor / Actual pressure value detection


6.1 Overview
In the case of the pressure valves under closed-loop pressure control, the actual pressure value is
detected depending on the valve type via an internal pressure sensor which is permanently installed in
the valve ex works or via an external pressure sensor which is connected to the valve on the customer
side via the interface XN2.

6.2 Internal pressure sensor


For pressure valves with internal pressure sensor, a pressure sensor is installed permanently ex works
to match the nominal pressure of the valve. The pressure sensor installed in the valve supplies a voltage
signal in the range of 0.1 to 10 V.

Bosch Rexroth AG RE29283-FK/03.23, Edition 01


3DRE(E)(A), Z3DRE(E)(A) 43 / 112
External pressure sensor – interface X2N

Pressure sensor / Actual pressure value detection


Internal
pressure sensor

Fig. 33: Internal pressure sensor

6.3 External pressure sensor – interface X2N


In the case of pressure valves with the connection possibility of an external pressure sensor, this can be
effected via the interface X2N. A sensor can be used as an external pressure sensor, where the actual
pressure value is given as a voltage signal (0 ... 10 V) or as a current signal (4 ...20 mA).

Pressure sensor interface


X2N

Fig. 34: Pressure sensor

Interface X2N assignment


The following table shows the pin assignment of the pressure sensor interface X2N.

RE29283-FK/03.23, Bosch Rexroth AG


Edition 01
44 / 112 3DRE(E)(A), Z3DRE(E)(A)
Actual pressure value detection

Pin Signal Interface


1 Us Voltage supply for the pressure
sensor from the valve supply via
connectors XH1 or XH5
2 IMeas Current input 4 … 20 mA for pres-
sure sensors with current inter-
face
3 GND Reference potential
4 UMeas Voltage input 0 … 10 V for pres-
sure sensors with voltage inter-
face
5 n.c. No connection
The exact electrical specification of the pressure sensor interface X2N can be found in the
corresponding "data sheet".

6.4 Actual pressure value detection


6.4.1 Functional description
The actual pressure value is detected as a voltage signal in valves with an internal pressure sensor, since
a corresponding sensor is permanently installed ex works. In the case of valves with the connection
possibility of an external pressure sensor, the actual pressure value is read in as a voltage or current
signal depending on the sensor type used by the customer. In the OBED, the read-in voltage or the
read-in current is converted into a corresponding actual pressure value. This progress of the actual
pressure value detection is shown in the following figure.

Bosch Rexroth AG RE29283-FK/03.23, Edition 01


3DRE(E)(A), Z3DRE(E)(A) 45 / 112
Actual pressure value detection

Integrated
pressure sensor Analog input
actual pressure

Pressure sensor / Actual pressure value detection


value

[bar]

Actual pressure value


Voltage
Actual pressure
Current x value

Type of signal Active


[V],
Analog actual pressure value [mA]

Conversion:
External analog actual pressure value
in actual pressure value (bar) 0 bar
pressure sensor Cable break
0.04 V ... 0.07 V
X2N 3.3 mA … 3.6 mA
Signal error Pressure
Overload
> 30 mA
detected controller off

Set
error bit

Signal exceedance Signal error Set


10.17 V ... 10.2 V detected error bit
20.3 mA ... 20.6 mA

Fig. 35: Actual pressure value detection

Type of signal
The type of signal is used to set whether the analog actual pressure value is detected as a voltage signal
in the range from 0 to 10 V or as a current signal in the current range from 4 to 20 mA.

Activation bit
The conversion of the voltage or current signal of the analog actual pressure value into V or mA into the
corresponding actual pressure value in bar is activated via the activation bit.

Conversion of the analog actual pressure value (V or mA) into an actual pressure value (bar)
In the following, it is shown in detail how the conversion of the voltage or current signal of the analog
actual pressure value into V or mA into the corresponding actual pressure value into bar takes place in
principle.

RE29283-FK/03.23, Bosch Rexroth AG


Edition 01
46 / 112 3DRE(E)(A), Z3DRE(E)(A)
Actual pressure value detection

Actual pressure value


[bar]

y2
Value range, upper limit

Analog
y1
Value range, lower limit Actual pressure value
x1 x2
[V], [mA]

Signal range, Signal range,


lower limit upper limit

Fig. 36: Conversion of actual pressure value


Over the two points x1, y1 (lower limit: signal range, value range) and x2, y2 (upper limit: signal range,
value range) a straight line equation is defined. This straight line equation is used to convert the actual
analog pressure value into V or mA currently read in into the corresponding actual pressure value in bar.

Value range ( y 2 - y1)


Actual pressure value (bar) = ´ ((Actual pressure value (in V or . mA ) - x1) + y1
Signal range ( x 2 - x1)

Fig. 37: Actual pressure value detection formula


Maximum adjustable signal range:
As a result of the electronics of the pressure valve, the maximum adjustable signal range of the pressure
sensor (lower and upper limit) is limited to certain values which can be taken from the following table.
Pressure sensor interface Maximum adjustable signal range
Lower limit Upper limit
Voltage -0.5 V 10.5 V
Current 3.2 mA 20.8 mA

Pressure sensor signal monitoring


Ex works, the voltage or current signal read in by the pressure sensor is automatically monitored for
cable break (-> undervoltage or current) or signal overrun (-> overvoltage or current). The current
signal is additionally tested for overload.

Bosch Rexroth AG RE29283-FK/03.23, Edition 01


3DRE(E)(A), Z3DRE(E)(A) 47 / 112
Actual pressure value detection

If a cable break or overload has been detected, as an error reaction, the actual pressure value is set
to the value 0 bar and the pressure controller is switched off. Thus, the valve automatically changes
to open-loop pressure control mode. Furthermore, the error bit is set in accordance with the detected
signal error. As soon as the error case is no longer active, the actual pressure value is automatically

Pressure sensor / Actual pressure value detection


regenerated and the closed-loop pressure control activated.
In the event of a signal exceedance, no error reaction takes place; only a corresponding error bit is set.
Signal thresholds for cable break, signal exceedance and overload:
The following table shows from which signal threshold a cable break, a signal exceedance or an
overload is detected and automatically acknowledged.
Pressure Cable break Signal exceedance Overload
sensor inter- Identification Acknowledg- Identification Acknowledg- Identification Acknowledg-
face ment ment ment
Voltage < 0.04 V ³ 0.07 V > 10.2 V £ 10.17 V - -
Current < 3.3 mA ³ 3.6 mA > 20.3 mA £ 20.3 mA > 30 mA 0 mA
The monitoring for cable break, signal exceedance and overload is only active if the signal
range of the pressure sensor (lower and upper limit) is set according to the following table.
Pressure sensor interface Maximum adjustable signal range
Lower limit Upper limit
Voltage ³0.07 V £10.17 V
Current ³3.6 mA £20.3 mA

6.4.2 Relevant parameters


The following parameters are relevant for setting the actual pressure value detection:
⮫ Chapter 9.67 “S-0-0809 - Actual pressure value” on page 106
⮫ Chapter 9.19 “P-0-2885.0.23 - Diagnostics: Error overview” on page 79
⮫ Chapter 9.52 “P-0-2907.2.1 - Analog actual pressure value input: Actual value” on page 100
⮫ Chapter 9.46 “P-0-2900.2.1 Analog actual pressure value input: Control word” on page 96
⮫ Chapter 9.47 “P-0-2900.2.8 Analog actual pressure value input: Signal range, lower limit”
on page 97
⮫ Chapter 9.48 “P-0-2900.2.9 - Analog actual pressure value input: Signal range, upper limit”
on page 97
⮫ Chapter 9.49 “P-0-2900.2.10 - Analog actual pressure value input: Value range, lower limit”
on page 98
⮫ Chapter 9.50 “P-0-2900.2.11 - Analog actual pressure value input: Value range, upper limit”
on page 99

6.4.3 Setting via "easy2connect"


In the "easy2connect" smartphone app, the settings for the actual pressure value detection can be
adjusted in the "Sensor" screen.

RE29283-FK/03.23, Bosch Rexroth AG


Edition 01
48 / 112 3DRE(E)(A), Z3DRE(E)(A)
Overview

Analog actual pressure value of the sensor

Settings for converting the voltage or current


signal of the analog actual pressure value of
the sensor into V or mA into the corresponding
actual pressure value in bar

Sensor screen

Fig. 38: Pressure settings via "easy2connect"


The settings for a pressure valve with internal pressure sensor may only be changed via
the "easy2connect" smartphone app after consulting Bosch Rexroth's service. During the
production of the pressure valve, these are optimally set so that the accuracies specified in the
"data sheet" are achieved during the closed-loop pressure control.

7 Controller structure (Z)3DREE


7.1 Overview
There is no pressure sensor in the pressure valve type (Z)3DREE. Thus, in this valve type closed-loop
pressure control is not possible but only open-loop pressure control. The rough controller structure for
this valve type is shown below.

Bosch Rexroth AG RE29283-FK/03.23, Edition 01


3DRE(E)(A), Z3DRE(E)(A) 49 / 112
Overview

Parameter set

Pressure command Valve on


Digital interface
value preparation
Pressure
command value

Controller structure (Z)3DREE


Effective pressure
Solenoid current
Analog interface command value
controller
Solenoid
A1 / F1
Control value
Filtration Solenoid actual
current value

Filtered solenoid
actual current
value

Fig. 39: Controller structure1

Pressure command value


The pressure command value is cyclically preset to the valve. Depending on the valve type, this takes
place either digitally via the process data (PDout) of the IO-Link interface or as an analog voltage or
current signal via the A1 or F1 interface.

Pressure command value preparation


The settings of the pressure command value preparation (ramps and filters) are parameter set
dependent. This means that the settings (ramps and filters) are adjusted depending on the currently
active parameter set.
Detailed information about the command value preparation can be found in ⮫ Chapter 7.2 “Pressure
command value preparation” on page 51.

Solenoid current actual value filtration


The filtration of the actual current value measured internally in the pressure valve is currently fixed and
cannot be changed.

Solenoid current controller


The solenoid current controller is realized as a PI controller with feedforward control. The solenoid
current controller calculates the associated control value for the solenoid of the pressure valve from the
effective pressure command value predetermined by the command value preparation and the current
solenoid current actual value.
Detailed information on the solenoid current controller can be found in ⮫ Chapter 7.3 “Solenoid
current controller” on page 53.

RE29283-FK/03.23, Bosch Rexroth AG


Edition 01
50 / 112 3DRE(E)(A), Z3DRE(E)(A)
Overview

Parameter set
The pressure valve is supplied with 4 parameter sets, so that the settings for the command value
preparation can be easily adapted to the application of the pressure valve.
Parameter set number Application of the pressure valve
0 Small dead volume
1 Large dead volume
2 User-defined 1 (with small dead volume pre-parameterized ex works)
3 User-defined 2 (with large dead volume pre-parameterized ex works)
In the case of the pressure valve with digital IO-Link interface, the active parameter set is preset
cyclically via the process data (PDout).
In the case of the pressure valve with an analog A1 or F1 interface, the parameter set 1 "Large dead
volume" is set ex works. This can be reconfigured via the "easy2connect" smartphone app.
For application-specific adaptation, it is intended to use parameter sets 2 and 3 first.

Valve on
The output of the control value of the solenoid current controller on the solenoid is only effected when
the "valve on" bit is set. By setting this bit, the output stage of the valve is activated, via which the
solenoid is actuated with the corresponding control value.
In the case of the pressure valve with digital IO-Link interface, the "valve on" bit is cyclically predeter-
mined via the process data (PDout). This means that the bit must be set via IO-Link in order to activate
the output of the control value of the solenoid current controller on the magnet.
In the case of the pressure valve with an analog A1 or F1 interface, the "valve on" bit is set ex works,
so that after the pressure valve is switched on, the output of the control value of the solenoid current
controller to the solenoid takes place immediately.

"easy2connect" smartphone app


In the "easy2connect" smartphone app, the settings for the pressure command value preparation and
for the solenoid current controller can be adjusted in the "Controller" screen.

Bosch Rexroth AG RE29283-FK/03.23, Edition 01


3DRE(E)(A), Z3DRE(E)(A) 51 / 112
Pressure command value preparation

Controller structure (Z)3DREE


Settings for the pressure command
value preparation

Settings for the solenoid current controller

Controller screen

Fig. 40: Controller structure2

7.2 Pressure command value preparation


7.2.1 Functional description
The structure of the pressure command value preparation is shown below.

RE29283-FK/03.23, Bosch Rexroth AG


Edition 01
52 / 112 3DRE(E)(A), Z3DRE(E)(A)
Pressure command value preparation

Parameter set

Pressure command value preparation

Pressure command Resulting pressure


value command value

Command value filter

Command value ramp

Fig. 41: Pressure command value preparation1

Command value ramp


The predetermined pressure command value is guided over a command value ramp to avoid abrupt
changes. Separate ramp times for positive and negative pressure command value changes can be set.
The ramp times are parameter set dependent and can be set individually for each of the 4 available
parameter sets, if the factory settings still have to be optimized.

Command value filter


The predetermined pressure command value can be smoothened via a PT1 filter whose filter frequency
can be adjusted. The filter frequency is also parameter set dependent.

Parameter set
The pressure valve is supplied with 4 parameter sets, so that the settings for the pressure command
value preparation (-> command value ramp and command value filtering) can be easily adapted to the
application of the pressure valve.

7.2.2 Relevant parameters


The following parameters are relevant for setting the pressure command value preparation:
⮫ Chapter 9.66 “S-0-0800 - Pressure command value” on page 106
⮫ Chapter 9.11 “P-0-2803 - Pressure command value preparation: Resulting pressure command
value” on page 77
⮫ Chapter 9.38 “P-0-2892.0.6 - Pressure command value preparation: Ramp time positive”
on page 91
⮫ Chapter 9.39 “P-0-2892.0.7 - Pressure command value preparation: Ramp time negative”
on page 92
⮫ Chapter 9.40 “P-0-2892.0.8 - Pressure command value preparation: Filter frequency” on page 92

Bosch Rexroth AG RE29283-FK/03.23, Edition 01


3DRE(E)(A), Z3DRE(E)(A) 53 / 112
Solenoid current controller

7.2.3 Setting via "easy2connect"


In the "easy2connect" smartphone app, the settings for the pressure command value preparation can
be adjusted in the "Controller" screen.

Controller structure (Z)3DREE


Settings for the pressure command
value preparation

Controller screen

Fig. 42: Pressure command value preparation2

7.3 Solenoid current controller


7.3.1 Functional description
The structure of the solenoid current controller of the pressure valve is shown below.

RE29283-FK/03.23, Bosch Rexroth AG


Edition 01
54 / 112 3DRE(E)(A), Z3DRE(E)(A)
Solenoid current controller

Closed-loop pressure
control on Solenoid current controller
PI controller with feedforward control
Pressure command
value preparation

Effective pressure Command value correction


command value

+ Solenoid
+ - + control value
Pressure controller
Pressure/current curve Factor Dither
Pressure controller frequency
control value factor
Offset

Actual current value

Fig. 43: Solenoid current controller

Pressure command value for solenoid current controller


If closed-loop pressure control is activated, the solenoid current controller receives the control value of
the pressure controller as a command value. In the other case, the pressure command value which is
predetermined by the command value preparation acts directly.
With a pressure valve without a pressure sensor, closed-loop pressure control is not possible.
In this case, the solenoid current controller always receives the command value directly from
the command value preparation.

Pressure/current curve
The pressure command value transferred to the solenoid current controller is converted into the
corresponding solenoid current command value via the pressure/current characteristic.

Solenoid current command value correction


The valve is set ex works over the complete pressure range (→ 0 bar to the nominal pressure of the
valve) for the volume flow specified in the valve data sheet. An optimum adaptation to the actual volume
flow and compensation of the aging of the pressure valve can be effected via the command value
correction by means of a factor and offset.

Solenoid current controller (PI controller with feedforward control)


The actual solenoid current controller is realized as a PI controller with feedforward control. The
solenoid current controller is set for the valve ex works, meaning that the customer is not required to
make any settings.

Dither frequency factor


The control value of the solenoid current controller is output at a superimposed dither frequency to the
magnet of the pressure valve. The dither frequency for the pressure valve is set ex works so that the two
following conditions are optimally met:

Bosch Rexroth AG RE29283-FK/03.23, Edition 01


3DRE(E)(A), Z3DRE(E)(A) 55 / 112
Solenoid current controller

• The dither has as little influence as possible on the amplitude of the actual pressure value.
• A corresponding dynamic of the valve is achieved.
The dither frequency can be adjusted via the factor in such a way that the pressure valve is optimized in
response to one of the conditions:
• Increasing the dynamics of the valve by a smaller dither frequency (→ factor < 1), which results in
a higher pressure amplitude.
• Reduction of the actual pressure value amplitude (→ factor > 1), which results in a worse dynamic

Controller structure (Z)3DREE


of the valve.
Ex works, the factor is set to 1.
A change to the dither frequency should only be made after consultation with the Bosch
Rexroth service department.

7.3.2 Relevant parameters


The following parameters are relevant for mapping the voltage or current signal of the analog command
value input to the corresponding pressure command value.
⮫ Chapter 9.25 “P-0-2890.0.6 - Solenoid current: Offset” on page 86
⮫ Chapter 9.26 “P-0-2890.0.7 - Solenoid current: P-gain” on page 87
⮫ Chapter 9.27 “P-0-2890.0.8 - Solenoid current controller: Dither frequency factor” on page 87

7.3.3 Setting via "easy2connect"


In the "easy2connect" smartphone app, the settings for the solenoid current controller can be adjusted
in the "Controller" screen.

RE29283-FK/03.23, Bosch Rexroth AG


Edition 01
56 / 112 3DRE(E)(A), Z3DRE(E)(A)
Overview

Settings for the command value correction


of the solenoid current controller

Controller screen

Fig. 44: "Controller" screen

8 Controller structure (Z)3DREA


8.1 Overview
In the pressure valve of type (Z)3DREA, the actual pressure value is detected via an internal or external
pressure sensor. Thus, in this valve type, in addition to the open-loop pressure control, a closed-loop
pressure control is also possible. The controller structure for this valve type is shown below.

Bosch Rexroth AG RE29283-FK/03.23, Edition 01


3DRE(E)(A), Z3DRE(E)(A) 57 / 112
Overview

Closed-loop pressure
Parameter set control on
Valve on

Digital
Interface
Pressure command
value preparation
Pressure
command value
Effective pressure

Controller structure (Z)3DREA


Analog command value

Interface
Pressure controller
A1 / F1
Actual pressure
Internal or value filtration Pressure controller
control value
Actual pressure
external value
pressure sensor Filtered actual
pressure value

Pressure sensor
cable break

Solenoid current
controller
Solenoid
Control value
Filtration Solenoid actual
current value

Filtered solenoid
actual current
value

Fig. 45: Controller structure3

Pressure command value


The pressure command value is cyclically preset to the valve. Depending on the valve type, this takes
place either digitally via the process data (PDout) of the IO-Link interface or as an analog voltage or
current signal via the A1 or F1 interface.

Pressure command value preparation


The settings of the pressure command value preparation (ramps and filters) are parameter set
dependent. This means that the settings (ramps and filters) are used depending on the currently
active parameter set.
Detailed information about the command value preparation can be found in ⮫ Chapter 7.2 “Pressure
command value preparation” on page 51.

Actual pressure value


The actual pressure value is detected depending on the valve type via an internal or external pressure
sensor.
Detailed information on detecting the actual pressure value can be found in ⮫ Chapter 6.4 “Actual
pressure value detection” on page 44.

RE29283-FK/03.23, Bosch Rexroth AG


Edition 01
58 / 112 3DRE(E)(A), Z3DRE(E)(A)
Overview

Actual pressure value filtration


The actual pressure value is smoothened via a PT1 filter.
Detailed information about the filtration can be found in ⮫ Chapter 6 “Pressure sensor / Actual pressure
value detection” on page 42.

Pressure controller
The pressure controller is realized as a PI controller with active damping and feedforward control. The
pressure controller can be easily set by using a slider.
The pressure controller calculates the corresponding control value from the effective pressure com-
mand value predetermined by the command value preparation and the actual pressure value currently
detected. When the closed-loop pressure control is activated, this control value is supplied to the
solenoid current controller. The settings of the pressure controller are parameter set dependent. This
means that the settings are used depending on the active parameter set.
Detailed information about the pressure controller can be found in ⮫ Chapter 8.4 “Closed-loop
pressure control” on page 63.

Solenoid current actual value filtration


The filtration of the actual current value measured internally in the pressure valve is currently fixed and
cannot be changed.

Solenoid current controller


The solenoid current controller is realized as a PI controller with feedforward control. The solenoid
current controller receives the control value of the pressure controller as the command value when the
closed-loop pressure control is activated. In the other case, the command value which is predetermined
by the command value preparation acts directly.
The solenoid current controller calculates the associated control value for the solenoid of the pressure
valve from the pressure command value and the current solenoid current actual value.
Detailed information on the solenoid current controller can be found in ⮫ Chapter 7.3 “Solenoid
current controller” on page 53.

Parameter set
The pressure valve is supplied with 4 parameter sets, so that the settings for the command value
preparation can be easily adapted to the application of the pressure valve.
Parameter set number Application of the pressure valve
0 Small dead volume
1 Large dead volume
2 User-defined 1 (with small dead volume pre-parameterized ex works)
3 User-defined 2 (with large dead volume pre-parameterized ex works)
In the case of the pressure valve with digital IO-Link interface, the active parameter set is preset
cyclically via the process data (PDout).

Bosch Rexroth AG RE29283-FK/03.23, Edition 01


3DRE(E)(A), Z3DRE(E)(A) 59 / 112
Overview

In the case of the pressure valve with an analog A1 or F1 interface, the parameter set 1 "Small dead
volume" is set ex works. This can be reconfigured via the "easy2connect" smartphone app.
For application-specific adaptation, it is intended to use parameter sets 2 and 3 first.

Closed-loop pressure control on


The pressure controller of the valve is only active if the "closed-loop pressure control on" bit is also set.

Controller structure (Z)3DREA


Otherwise, the valve is in "open-loop pressure control" mode. In the case of the pressure valve with
digital IO-Link interface, the "closed-loop pressure control on" bit is cyclically predetermined via the
process data (PDout).
This means that the bit must be set via IO-Link for the pressure controller to be active. In the case of
the pressure valve with an analog A1 or F1 interface, the "closed-loop pressure control on" bit is set ex
works, so that the pressure controller is activated immediately after the pressure valve is switched on.

Valve on
The output of the control value of the solenoid current controller on the solenoid is only effected when
the "valve on" bit is set. By setting this bit, the output stage of the valve is activated, via which the
solenoid is actuated with the corresponding control value.
In the case of the pressure valve with digital IO-Link interface, the "valve on" bit is cyclically predeter-
mined via the process data (PDout). This means that the bit must be set via IO-Link in order to activate
the output of the control value of the solenoid current controller on the magnet.
In the case of the pressure valve with an analog A1 or F1 interface, the "valve on" bit is set ex works,
so that after the pressure valve is switched on, the output of the control value of the solenoid current
controller to the solenoid takes place immediately.

Pressure sensor cable break


If a cable break of the pressure sensor is detected, the switch-over into open-loop pressure control
takes place if closed-loop pressure control is currently active. As soon as the cable break is no longer
present, the closed-loop pressure control is again automatically activated.

"easy2connect" smartphone app


In the "easy2connect" smartphone app, the settings for the pressure command value preparation,
for the pressure controller and for the solenoid current controller can be adjusted in the "Controller"
screen.

RE29283-FK/03.23, Bosch Rexroth AG


Edition 01
60 / 112 3DRE(E)(A), Z3DRE(E)(A)
Pressure command value preparation

Settings for the pressure command


value preparation

Settings for the pressure controller

Settings for the solenoid current controller

Controller screen

Fig. 46: Controller structure4

8.2 Pressure command value preparation


8.2.1 Functional description
The structure of the pressure command value preparation is shown below.

Bosch Rexroth AG RE29283-FK/03.23, Edition 01


3DRE(E)(A), Z3DRE(E)(A) 61 / 112
Pressure command value preparation

Parameter set

Pressure command value preparation

Pressure command Resulting pressure

Controller structure (Z)3DREA


value command value

Command value filter

Command value ramp

Fig. 47: Pressure command value preparation1

Command value ramp


The predetermined pressure command value is guided over a command value ramp to avoid abrupt
changes. Separate ramp times for positive and negative pressure command value changes can be set.
The ramp times are parameter set dependent and can be set individually for each of the 4 available
parameter sets, if the factory settings still have to be optimized.

Command value filter


The predetermined pressure command value can be smoothened via a PT1 filter whose filter frequency
can be adjusted. The filter frequency is also parameter set dependent.

Parameter set
The pressure valve is supplied with 4 parameter sets, so that the settings for the pressure command
value preparation (-> command value ramp and command value filtering) can be easily adapted to the
application of the pressure valve.

8.2.2 Relevant parameters


The following parameters are relevant for setting the pressure command value preparation:
⮫ Chapter 9.66 “S-0-0800 - Pressure command value” on page 106
⮫ Chapter 9.11 “P-0-2803 - Pressure command value preparation: Resulting pressure command
value” on page 77
⮫ Chapter 9.38 “P-0-2892.0.6 - Pressure command value preparation: Ramp time positive”
on page 91
⮫ Chapter 9.39 “P-0-2892.0.7 - Pressure command value preparation: Ramp time negative”
on page 92
⮫ Chapter 9.40 “P-0-2892.0.8 - Pressure command value preparation: Filter frequency” on page 92

RE29283-FK/03.23, Bosch Rexroth AG


Edition 01
62 / 112 3DRE(E)(A), Z3DRE(E)(A)
Actual pressure value filtration

8.2.3 Setting via "easy2connect"


In the "easy2connect" smartphone app, the settings for the pressure command value preparation can
be adjusted in the "Controller" screen.

Settings for the pressure command


value preparation

Controller screen

Fig. 48: Pressure command value preparation2

8.3 Actual pressure value filtration


8.3.1 Functional description
The actual pressure value detected via the internal or external pressure sensor is filtered for closed-loop
pressure control. The following figure shows this filtration:

Bosch Rexroth AG RE29283-FK/03.23, Edition 01


3DRE(E)(A), Z3DRE(E)(A) 63 / 112
Closed-loop pressure control

Actual pressure value filtration

Actual pressure Filtered actual


value pressure value

Filtration

Controller structure (Z)3DREA


Fig. 49: 29263-FK_Actual pressure value filtration

Filtration
The actual pressure value detected via the internal or external pressure sensor is smoothened via a
PT1 filter whose filter frequency can be adjusted. The reasonable value range for the filter frequency is
between 10 Hz and 200 Hz.
By increasing the filter frequency, better dynamics in the closed-loop pressure control can be achieved
if the hydraulic conditions for this are fulfilled (e.g. small dead volume).
From the factory, the filter frequency is set as a compromise for the various applications of the
pressure valve (e.g. small dead volume, large dead volume).

8.3.2 Relevant parameters


The following parameters are relevant for setting the filtration of the actual pressure value:
⮫ Chapter 9.67 “S-0-0809 - Actual pressure value” on page 106
⮫ Chapter 9.28 “P-0-2890.0.9 - Actual pressure value: Filter frequency” on page 88

8.3.3 "easy2connect" smartphone app


In the "easy2connect" smartphone app, there is currently no screen available in which the filtration of
the actual pressure value can be set.

8.4 Closed-loop pressure control


8.4.1 Functional description
The structure of the pressure controller of the pressure reducing valve (Z)3DREA is shown below.

RE29283-FK/03.23, Bosch Rexroth AG


Edition 01
64 / 112 3DRE(E)(A), Z3DRE(E)(A)
Closed-loop pressure control

Parameter set

Pressure controller
Feedforward control

PI controller Limitation

Resulting pressure + Output pressure


command value - + controller

P-gain

- -
Filtered actual
pressure value
I-gain

CMP
Switch-off
threshold -

Active damping

Gain
I-term

Gain

Slider
active

Slider
Pressure control
deviation
Pressure command value reached

Status bit “Pressure


CMP SOUND command value reached”
Target window

Fig. 50: Closed-loop pressure control

Pressure controller components


• Feedforward control
• PI controller with switching integrator
• Active damping
• Limitation

Feedforward control
With feedforward control (command value feedforward), the current pressure command value flows
into closed-loop control as a percentage. In this way, the pressure control deviation is minimized.

Bosch Rexroth AG RE29283-FK/03.23, Edition 01


3DRE(E)(A), Z3DRE(E)(A) 65 / 112
Closed-loop pressure control

Feedforward control of the pressure controller is optimally set ex works for the pressure reducing valve
according to the nominal pressure. A customer setting is therefore not currently provided.

PI controller with switching integrator


With the PI controller, the P and I-gains can be set.
The PI controller integrator is automatically switched off if the following condition is met:
(output pressure controller-filtered actual pressure value) > Switch-off threshold Integrator * Nominal

Controller structure (Z)3DREA


pressure dependent switch-off threshold
Nominal value of pressure valve Nominal pressure dependent switch-off threshold
50 bar 10 bar
100 bar 10 bar
200 bar 14 bar
315 bar 22 bar
The integrator of the PI controller is automatically activated again if the above condition is no longer
fulfilled.
Whether the I-term of the control value of the pressure controller is to be frozen or deleted
during the switching off of the integrator is set via the control word of the pressure controller.

Active damping
In the pressure controller, within the framework of active damping, the change in the actual pressure
value (→ velocity) is fed back to closed-loop control with a scaling factor in order to achieve a better
controller behavior. The gain of the active damping and of the I-term can be parameterized.

Slider
With the aid of the slider, the controller behavior of the pressure controller can be easily set between
moderate, balanced and aggressive. When the slider is pressed, the corresponding values for the
following 4 parameters of the pressure controller are calculated at the same time:
• PI controller P-gain
• PI controller I-gain
• Active damping gain
• Active damping I-term gain
The slider can also be disabled so that the 4 parameters can be set independently.

Pressure controller output limit


The output of the pressure controller is fixedly limited to 0% to 115% of the nominal pressure of the
valve. If, for example, the nominal pressure of the valve is 200 bar, the output of the pressure controller
is limited to 0 bar to 230 bar.

RE29283-FK/03.23, Bosch Rexroth AG


Edition 01
66 / 112 3DRE(E)(A), Z3DRE(E)(A)
Closed-loop pressure control

Parameter set
The pressure valve is supplied with 4 parameter sets, so that the parameterization of the pressure
controller can be adapted very simply to the respective application of the pressure valve. The following
settings of the pressure controller are parameter set dependent:
• PI controller P-gain
• PI controller I-gain
• Active damping gain
• Active damping I-term gain
• Slider
• Switch-off threshold of the I-term of the PI controller

Status bit “Pressure command value reached”


The status bit "Pressure command value reached" indicates whether the pressure control deviation (->
difference between pressure command value and actual pressure value) within a target window.
If the pressure control deviation is within the target window, the status bit is set. If the pressure control
deviation leaves the target window for a period of more than 10 ms, the status bit is reset again.
The status bit "Pressure command value reached" is formed when the following conditions are met:
• Enable for the valve is set
• Pressure detection of the valve is active

8.4.2 Relevant parameters


The following parameters are relevant for setting the pressure controller:
⮫ Chapter 9.11 “P-0-2803 - Pressure command value preparation: Resulting pressure command
value” on page 77
⮫ Chapter 9.67 “S-0-0809 - Actual pressure value” on page 106
⮫ Chapter 9.69 “S-0-0827 - Pressure control deviation” on page 107
⮫ Chapter 9.22 “P-0-2890.0.3 - pressure controller: Slider (controller behavior)” on page 85
⮫ Chapter 9.23 “P-0-2890.0.4 - pressure controller: Control word” on page 85
⮫ Chapter 9.33 “P-0-2892.0.1 - pressure controller: I-gain” on page 89
⮫ Chapter 9.34 “P-0-2892.0.2 - pressure controller: P-gain” on page 89
⮫ Chapter 9.35 “P-0-2892.0.3 - pressure controller: Gain, active damping” on page 90
⮫ Chapter 9.36 “P-0-2892.0.4 - pressure controller: Gain, I-term active damping” on page 90
⮫ Chapter 9.37 “P-0-2892.0.5 - pressure controller: Integrator switch-off threshold” on page 91
⮫ Chapter 9.1 “P-0-0115 - Valve status word” on page 70

Bosch Rexroth AG RE29283-FK/03.23, Edition 01


3DRE(E)(A), Z3DRE(E)(A) 67 / 112
Closed-loop pressure control

8.4.3 Setting via "easy2connect"


In the "easy2connect" smartphone app, the settings for the pressure controller can be adjusted in the
"Controller" screen.

Controller structure (Z)3DREA


Relevant process variables for
closed-loop pressure control

Settings for the pressure controller

Controller screen

Fig. 51: 29283-FK_Closed-loop pressure control 2

RE29283-FK/03.23, Bosch Rexroth AG


Edition 01
68 / 112 3DRE(E)(A), Z3DRE(E)(A)
Solenoid current controller

8.5 Solenoid current controller


8.5.1 Functional description
The structure of the solenoid current controller of the pressure valve is shown below.

Closed-loop pressure
control on Solenoid current controller
PI controller with feedforward control
Pressure command
value preparation

Effective pressure Command value correction


command value

+ Solenoid
+ - + control value
Pressure controller
Pressure/current curve Factor Dither
Pressure controller frequency
control value factor
Offset

Actual current value

Fig. 52: Solenoid current controller

Pressure command value for solenoid current controller


If closed-loop pressure control is activated, the solenoid current controller receives the control value of
the pressure controller as a command value. In the other case, the pressure command value which is
predetermined by the command value preparation acts directly.
With a pressure valve without a pressure sensor, closed-loop pressure control is not possible.
In this case, the solenoid current controller always receives the command value directly from
the command value preparation.

Pressure/current curve
The pressure command value transferred to the solenoid current controller is converted into the
corresponding solenoid current command value via the pressure/current characteristic.

Solenoid current command value correction


The valve is set ex works over the complete pressure range (→ 0 bar to the nominal pressure of the
valve) for the volume flow specified in the valve data sheet. An optimum adaptation to the actual volume
flow and compensation of the aging of the pressure valve can be effected via the command value
correction by means of a factor and offset.

Solenoid current controller (PI controller with feedforward control)


The actual solenoid current controller is realized as a PI controller with feedforward control. The
solenoid current controller is set for the valve ex works, meaning that the customer is not required to
make any settings.

Bosch Rexroth AG RE29283-FK/03.23, Edition 01


3DRE(E)(A), Z3DRE(E)(A) 69 / 112
Solenoid current controller

Dither frequency factor


The control value of the solenoid current controller is output at a superimposed dither frequency to the
magnet of the pressure valve. The dither frequency for the pressure valve is set ex works so that the two
following conditions are optimally met:
• The dither has as little influence as possible on the amplitude of the actual pressure value.
• A corresponding dynamic of the valve is achieved.
The dither frequency can be adjusted via the factor in such a way that the pressure valve is optimized in

Controller structure (Z)3DREA


response to one of the conditions:
• Increasing the dynamics of the valve by a smaller dither frequency (→ factor < 1), which results in
a higher pressure amplitude.
• Reduction of the actual pressure value amplitude (→ factor > 1), which results in a worse dynamic
of the valve.
Ex works, the factor is set to 1.
A change to the dither frequency should only be made after consultation with the Bosch
Rexroth service department.

8.5.2 Relevant parameters


The following parameters are relevant for mapping the voltage or current signal of the analog command
value input to the corresponding pressure command value.
⮫ Chapter 9.25 “P-0-2890.0.6 - Solenoid current: Offset” on page 86
⮫ Chapter 9.26 “P-0-2890.0.7 - Solenoid current: P-gain” on page 87
⮫ Chapter 9.27 “P-0-2890.0.8 - Solenoid current controller: Dither frequency factor” on page 87

8.5.3 Setting via "easy2connect"


In the "easy2connect" smartphone app, the settings for the solenoid current controller can be adjusted
in the "Controller" screen.

RE29283-FK/03.23, Bosch Rexroth AG


Edition 01
70 / 112 3DRE(E)(A), Z3DRE(E)(A)
P-0-0115 - Valve status word

Settings for the command value correction


of the solenoid current controller

Controller screen

Fig. 53: "Controller" screen

9 Parameter descriptions
9.1 P-0-0115 - Valve status word
9.1.1 Description
This parameter indicates the current status of the pressure valve.
Status word set-up:
Bit Name / Function Comment
0-1 Reserved
2 Warning
0: no warning
1: Warning active
3-7 Reserved

Bosch Rexroth AG RE29283-FK/03.23, Edition 01


3DRE(E)(A), Z3DRE(E)(A) 71 / 112
P-0-0115 - Valve status word

Bit Name / Function Comment


8-9 Operating mode
0b00: Open-loop pressure con-
trol active
0b01: Closed-loop pressure con-
trol active
0b10: reserved
0b11: reserved

Parameter descriptions
10-11 Reserved
12 Pressure command value reached See also further explanation of
0: Actual pressure value did not the status bit following this table.
reach the pressure command
value
1: Actual pressure value has
reached the pressure command
value according to the defined
target window
13 Error
0: No error
1: Error active
14 Reserved
15 Enable
0: no enable
1: Enable active
Status bit “Pressure command value reached”
The status bit "Pressure command value reached" is formed when the following conditions are met:
• Enable for the valve is set
• Pressure detection of the valve is active
When the status bit is formed, it is tested whether the difference between the pressure command value
and the actual pressure value (pressure control deviation see S-0-0827) lies within a target window.
The target window is permanently set to 2% of the nominal pressure of the valve (e.g. the nominal
pressure of the valve is 200 bar → target window is 4 bar). If the pressure control deviation is within
the target window, the corresponding status bit is set in the valve status (see P-0-0115). If the pressure
control deviation leaves the target window for a period of more than 10 ms, the status bit in the valve
status (see P-0-0115) is reset.

9.1.2 IO-Link mapping


Parameter set Index Subindex
- - -

RE29283-FK/03.23, Bosch Rexroth AG


Edition 01
72 / 112 3DRE(E)(A), Z3DRE(E)(A)
P-0-0116 - Valve control word

9.2 P-0-0116 - Valve control word


9.2.1 Description
This parameter displays the currently effective control word of the pressure valve. This parameter is
described by the corresponding control word of the interface of the pressure valve (→ analog or digital
interface) or the control word of the force mode:
• Pressure valve with analog interface (→ connector XH1): Active control word = P-0-4028
• Pressure valve with digital IO-Link interface (→ connector XH5): Active control word =
P-0-1910.0.1
• Force mode in the pressure valve active: Active control word = P-0-0120
Set-up of the control word:
Bit Name / Function Comment
0-1 Parameter set number
0b00: Parameter set 0
0b01: Parameter set 1
0b10: Parameter set 2
0b11: Parameter set 3
2-7 Reserved
8-9 Operating mode
0b00: Open-loop pressure con-
trol active
0b01: Closed-loop pressure con-
trol active
0b10: reserved
0b11: reserved
10-14 Reserved
15 Enable
0: no enable
1: Enable active

9.2.2 IO-Link mapping


Parameter set Index Subindex
- - -

Bosch Rexroth AG RE29283-FK/03.23, Edition 01


3DRE(E)(A), Z3DRE(E)(A) 73 / 112
P-0-0190 - Valve electronics operating hours

9.3 P-0-0120 - Force mode, control word


9.3.1 Description
When the force mode is active, the parameter is used for the control system of the pressure valve and
is mapped into the control word (→ P-0-0116). To activate the force mode, the corresponding bit must
be set in the parameter P-0-4085.
Set-up of the control word:
Bit Name / Function Comment

Parameter descriptions
0-1 Parameter set number
0b00: Parameter set 0
0b01: Parameter set 1
0b10: Parameter set 2
0b11: Parameter set 3
2-7 Reserved
8-9 Operating mode
0b00: Open-loop pressure con-
trol active
0b01: Closed-loop pressure con-
trol active
0b10: reserved
0b11: reserved
10-14 Reserved
15 Enable
0: no enable
1: Enable active

9.3.2 IO-Link mapping


Parameter set Index Subindex
- - -

9.4 P-0-0190 - Valve electronics operating hours


9.4.1 Description
This parameter displays the operating time of the valve's electronics in seconds. With the aid of this
parameter, the entire duty cycle of the electronics since delivery of the valve can thus be displayed.

9.4.2 IO-Link mapping


Parameter set Index Subindex
- - -

RE29283-FK/03.23, Bosch Rexroth AG


Edition 01
74 / 112 3DRE(E)(A), Z3DRE(E)(A)
P-0-1910.0.1 - IO-Link: Pressure valve control word

9.5 P-0-0670.0.3 - Command: Load factory default values


9.5.1 Description
With this command, the condition as supplied of the valve can be restored in conjunction with
command S-0-262. If the two commands S-0-0262 and P-0-0670.0.3 are executed in sequence, all
configuration parameters of the valve are reset to the delivered condition.
After executing the commands, the S-0-0264 must be actuated so that the reset parameter values are
stored in the valve in a remanent manner.

9.5.2 IO-Link mapping


Parameter set Index Subindex
- - -

9.6 P-0-1520 - Valve electronics type


9.6.1 Description
This parameter displays the type designation of the valve electronics.

9.6.2 IO-Link mapping


Parameter set Index Subindex
- - -

9.7 P-0-1910.0.1 - IO-Link: Pressure valve control word


9.7.1 Description
In this parameter, in the case of pressure valves with digital IO-Link interface (→ connector XH5), the
control word is written which is received by the IO-Link master. The control word received via IO-Link is
mapped into the effective control word of the pressure valve (→ P-0-0116).
Set-up of the control word:
Bit Name / Function Comment
0-1 Parameter set number
0b00: Parameter set 0
0b01: Parameter set 1
0b10: Parameter set 2
0b11: Parameter set 3
2-4 Reserved
5 Delete error For future use
0: Delete error not active
1: Delete error active

Bosch Rexroth AG RE29283-FK/03.23, Edition 01


3DRE(E)(A), Z3DRE(E)(A) 75 / 112
P-0-1910.0.2 - IO-Link: Pressure valve status word

Bit Name / Function Comment


6-7 Reserved
8 Activate closed-loop pressure Closed-loop pressure control can
control only be activated for valves with a
0: Activate open-loop pressure pressure sensor.
control
1: Activate closed-loop pressure
control

Parameter descriptions
9-14 Reserved
15 Enable valve control
0: Valve output stage is not active
1: Valve output stage is active

9.7.2 IO-Link mapping


Parameter set Index Subindex
- 75 0

9.8 P-0-1910.0.2 - IO-Link: Pressure valve status word


9.8.1 Description
In this parameter, for pressure valves with digital IO-Link interface (→ connector XH5), the status word
is written which is transmitted to the IO-Link master.
Status word set-up:
Bit Name / Function Comment
0-1 Parameter set number
0b00: Parameter set 0 active
0b01: Parameter set 1 active
0b10: Parameter set 2 active
0b11: Parameter set 3 active
2 Reserved
3 Pressure command value reached See also further explanation of
0: Actual pressure value did not the status bit following this table.
reach the pressure command
value
1: Actual pressure value has
reached the pressure command
value according to the defined
target window
4-7 Reserved

RE29283-FK/03.23, Bosch Rexroth AG


Edition 01
76 / 112 3DRE(E)(A), Z3DRE(E)(A)
P-0-1910.0.2 - IO-Link: Pressure valve status word

Bit Name / Function Comment


8-9 Closed-loop pressure control Closed-loop pressure control is
active only possible with valves with a
0: Open-loop pressure control pressure sensor.
active
1: Closed-loop pressure control
active
9 Force mode
0: Force mode not active
1: Force mode active
10-11 Reserved
12 Warning For future use
0: No warning in valve
1: Warning in valve
13 Error
0: No error in valve
1: Error in valve
14 Valve in control Pressure command values are
0: Valve control is not active processed cyclically
1: Valve control is active
15 Ready for operation
0: Valve not ready for operation
1: Valve ready for operation
Bit 3 - pressure command value reached:
The "Pressure command value reached" status bit is only set when the difference between the pressure
command value and the actual pressure value is in the defined target window. In addition, the following
conditions must be fulfilled for the status bit to be formed:
• The bit for enabling the valve is set.
• The valve pressure sensor is active.

9.8.2 IO-Link mapping


Parameter set Index Subindex
- 76 0

Bosch Rexroth AG RE29283-FK/03.23, Edition 01


3DRE(E)(A), Z3DRE(E)(A) 77 / 112
P-0-2875.0.7 - Valve: Nominal pressure

9.9 P-0-1910.0.3 - IO-Link: Start data storage backup


9.9.1 Description
This command can be used to trigger a data storage backup. To start the command, set it to "0x3". As a
result, a data storage backup is requested in the IO-Link master. As soon as the master has performed
the data storage backup, the parameter is reset to the value "0".

9.9.2 IO-Link mapping

Parameter descriptions
Parameter set Index Subindex
- 77 0

9.10 P-0-1910.0.4 - IO-Link: Device ID


9.10.1 Description
This parameter displays the current IO-Link valve device ID.

9.10.2 IO-Link mapping


Parameter set Index Subindex
- - -

9.11 P-0-2803 - Pressure command value preparation: Resulting


pressure command value
9.11.1 Description
The parameter indicates the resulting pressure command value at the output of the pressure command
value preparation. It is the input value for the pressure controller when closed-loop pressure control is
active or for the solenoid current controller when the valve is in the open-loop pressure control mode.

9.11.2 IO-Link mapping


Parameter set Index Subindex
- 90 0

9.12 P-0-2875.0.7 - Valve: Nominal pressure


9.12.1 Description
The nominal pressure of the pressure valve can be read out via this parameter.

RE29283-FK/03.23, Bosch Rexroth AG


Edition 01
78 / 112 3DRE(E)(A), Z3DRE(E)(A)
P-0-2885.0.20 - Diagnostics: Valve communication - Dongle

9.12.2 IO-Link mapping


Parameter set Index Subindex
- 83 0

9.13 P-0-2878.0.1 - Force mode: Pressure command value


9.13.1 Description
This parameter sets the pressure command value for force mode.

9.13.2 IO-Link mapping


Parameter set Index Subindex
- - -

9.14 P-0-2885.0.1 - Valve electronics temperature


9.14.1 Description
This parameter displays the temperature of the valve electronics inside the controller housing.

9.14.2 IO-Link mapping


Parameter set Index Subindex
- 72 0

9.15 P-0-2885.0.3 - Actual supply voltage


9.15.1 Description
This parameter displays the valve supply voltage in volts.

9.15.2 IO-Link mapping


Parameter set Index Subindex
- 73 0

9.16 P-0-2885.0.20 - Diagnostics: Valve communication - Dongle


9.16.1 Description
This diagnostic parameter can be used to read out how often the serial connection between the valve
controller and the Bluetooth dongle has been established.

Bosch Rexroth AG RE29283-FK/03.23, Edition 01


3DRE(E)(A), Z3DRE(E)(A) 79 / 112
P-0-2885.0.23 - Diagnostics: Error overview

9.16.2 IO-Link mapping


Parameter set Index Subindex
- - -

9.17 P-0-2885.0.21 - Diagnostics: Valve communication - IO-Link


9.17.1 Description
This diagnostic parameter can be used to read out how often the serial connection between the valve

Parameter descriptions
controller and the IO-Link controller has been established.

9.17.2 IO-Link mapping


Parameter set Index Subindex
- - -

9.18 P-0-2885.0.22 - Diagnostics: Life counter


9.18.1 Description
This parameter provides a free-running 1ms counter. The counter is used exclusively for diagnostic
purposes.

9.18.2 IO-Link mapping


Parameter set Index Subindex
- - -

9.19 P-0-2885.0.23 - Diagnostics: Error overview


9.19.1 Description
This status parameter displays an overview of the errors currently present in the valve. The errors are
represented by individual bits. The status of the bits is updated cyclically.
Status parameter set-up
Bit Name / Function Comment
Analog command value input (→ connector XH1) configured as current input
0 Cable break A cable break is made on the input at a cur-
0: No cable break rent < 3.3 mA detected. See also further
notes on the command value input following
1: Cable break detected
this table.
1 Signal exceedance A signal overflow is detected on the input at
0: No signal overflow a current >= 20.6 mA. See also further notes
on the command value input following this
1: Signal overflow detected
table.

RE29283-FK/03.23, Bosch Rexroth AG


Edition 01
80 / 112 3DRE(E)(A), Z3DRE(E)(A)
P-0-2885.0.23 - Diagnostics: Error overview

Bit Name / Function Comment


2 Overload An overload is detected on the input at a
0: No overload current > 30 mA. See also further notes on
the command value input following this table.
1: Overload detected
3 Reserved
Analog command value input (→ connector XH1) configured as voltage input
4-7 Reserved
Analog actual pressure value input (→ pressure sensor) configured as current input
8 Cable break A cable break is made on the input at a cur-
0: No cable break rent < 3.3 mA detected. See also further
notes on the actual pressure value input fol-
1: Cable break detected
lowing this table.
9 Signal exceedance A signal overflow is detected on the input at a
0: No signal overflow current >= 20.6 mA See also further notes on
the actual pressure value input following this
1: Signal overflow detected
table.
10 Overload An overload is detected on the input at a
0: No overload current > 30 mA. See also further notes on
the actual pressure value input following this
1: Overload detected
table.
11 Reserved
Analog actual pressure value input (→ pressure sensor) configured as voltage input
12 Cable break A cable break is made on the input at a
0: No cable break voltage < 0.04 V detected. + See also further
notes on the actual pressure value input fol-
1: Cable break detected
lowing this table.
13 Signal exceedance A signal overflow is detected on the input at a
0: No signal overflow voltage >= 10.2 V. See also further notes on
the actual pressure value input following this
1: Signal overflow detected
table.
14-15 Reserved
Pressure controller
16-19 Reserved
Firmware
20 Compatibility check error
0: No error
1: Firmware on valve controller and
IO-Link controller are incompatible.
21-23 Reserved
Internal analog input for temperature measurement

Bosch Rexroth AG RE29283-FK/03.23, Edition 01


3DRE(E)(A), Z3DRE(E)(A) 81 / 112
P-0-2885.0.23 - Diagnostics: Error overview

Bit Name / Function Comment


24 Cable break
0: No cable break
1: Cable break detected
25 Signal exceedance
0: No signal overflow
1: Signal overflow detected
26-27 Reserved

Parameter descriptions
Internal analog input for measuring the supply voltage
28 Cable break
0: No cable break
1: Cable break detected
29 Signal exceedance
0: No signal overflow
1: Signal overflow detected
30-31 Reserved
Analog command value input: Configuration and monitoring
The analog command value input (→ connector XH1) is configured as a voltage or current input via the
control word P-0-2900.1.1.
For the command value input, monitoring for cable break, signal overload and overload is only active if
the signal range is set via the parameters P-0-2900.1.8 and P-0-2900.1.9 according to the following
table.
Configuration as Signal range (lower limit) Signal range (upper limit)
P-0-2900.1.8 P-0-2900.1.9
Current >= 3.6 mA <= 20.3 mA
Analog actual pressure value input: Configuration and monitoring
The analog actual pressure value input is configured as a voltage or current input via the control word
P-0-2900.2.1.
For the actual pressure value input, monitoring for cable break, signal overload and overload is only
active if the signal range is set via the parameters P-0-2900.2.8 and P-0-2900.2.9 according to the
following table.
Configuration as Signal range (lower limit) Signal range (upper limit)
P-0-2900.2.8 P-0-2900.2.9
Voltage >= 0.07 V <= 10.17 V
Current >= 3.6 mA <= 20.3 mA

9.19.2 IO-Link mapping


Parameter set Index Subindex
- 114 0

RE29283-FK/03.23, Bosch Rexroth AG


Edition 01
82 / 112 3DRE(E)(A), Z3DRE(E)(A)
P-0-2885.0.24 - Diagnostics: Error overview (permanent)

9.20 P-0-2885.0.24 - Diagnostics: Error overview (permanent)


9.20.1 Description
This status parameter displays an overview of the errors which have occurred since the last time the
valve was switched on. The errors are represented by individual bits. Once set bits are not reset.
Status parameter set-up
Bit Name / Function Comment
Analog command value input (→ connector XH1) configured as current input
0 Cable break A cable break is made on the input at a
0: No cable break current < 3.3 mA detected. See also further
notes on the command value input following
1: Cable break detected
this table.
1 Signal exceedance A signal overflow is detected on the input
0: No signal overflow at a current >= 20.6 mA. See also further
notes on the command value input following
1: Signal overflow detected
this table.
2 Overload An overload is detected on the input at a
0: No overload current > 30 mA. See also further notes
on the command value input following this
1: Overload detected
table.
3 Reserved
Analog command value input (→ connector XH1) configured as voltage input
4-7 Reserved
Analog actual pressure value input (→ pressure sensor) configured as current input
8 Cable break A cable break is made on the input at a
0: No cable break current < 3.3 mA detected. See also further
notes on the actual pressure value input
1: Cable break detected
following this table.
9 Signal exceedance A signal overflow is detected on the input
0: No signal overflow at a current >= 20.6 mA. See also further
notes on the actual pressure value input
1: Signal overflow detected
following this table.
10 Overload An overload is detected on the input at a
0: No overload current > 30 mA. See also further notes
on the actual pressure value input following
1: Overload detected
this table.
11 Reserved
Analog actual pressure value input (→ pressure sensor) configured as voltage input
12 Cable break A cable break is detected on the input at
0: No cable break a voltage < 0.04 V. See also further notes
on the actual pressure value input following
1: Cable break detected
this table.

Bosch Rexroth AG RE29283-FK/03.23, Edition 01


3DRE(E)(A), Z3DRE(E)(A) 83 / 112
P-0-2885.0.24 - Diagnostics: Error overview (permanent)

Bit Name / Function Comment


13 Signal exceedance A signal overflow is detected on the input at
0: No signal overflow a voltage >= 10.2 V. See also further notes
on the actual pressure value input following
1: Signal overflow detected
this table.
14-15 Reserved
Pressure controller
16-19 Reserved
Firmware

Parameter descriptions
20 Compatibility check error
0: No error
1: Firmware on valve controller and
IO-Link controller are incompatible.
21-23 Reserved
Internal analog input for temperature measurement
24 Cable break
0: No cable break
1: Cable break detected
25 Signal exceedance
0: No signal overflow
1: Signal overflow detected
26-27 Reserved
Internal analog input for measuring the supply voltage
28 Cable break
0: No cable break
1: Cable break detected
29 Signal exceedance
0: No signal overflow
1: Signal overflow detected
30-31 Reserved
Analog command value input: Configuration and monitoring
The analog command value input (→ connector XH1) is configured as a voltage or current input via the
control word P-0-2900.1.1.
For the command value input, monitoring for cable break, signal overload and overload is only active if
the signal range is set via the parameters P-0-2900.1.8 and P-0-2900.1.9 according to the following
table.
Configuration as Signal range (lower limit) Signal range (upper limit)
P-0-2900.1.8 P-0-2900.1.9
Current >= 3.6 mA <= 20.3 mA
Analog actual pressure value input: Configuration and monitoring

RE29283-FK/03.23, Bosch Rexroth AG


Edition 01
84 / 112 3DRE(E)(A), Z3DRE(E)(A)
P-0-2885.0.30 - Diagnostics: Firmware update status

The analog actual pressure value input is configured as a voltage or current input via the control word
P-0-2900.2.1.
For the actual pressure value input, monitoring for cable break, signal overload and overload is only
active if the signal range is set via the parameters P-0-2900.2.8 and P-0-2900.2.9 according to the
following table.
Configuration as Signal range (lower limit) Signal range (upper limit)
P-0-2900.2.8 P-0-2900.2.9
Voltage >= 0.07 V <= 10.17 V
Current >= 3.6 mA <= 20.3 mA

9.20.2 IO-Link mapping


Parameter set Index Subindex
- - -

9.21 P-0-2885.0.30 - Diagnostics: Firmware update status


9.21.1 Description
This 32-bit parameter displays status information about individual bits in the event of a firmware
update of the IO-Link subsystem.
Bit Name / Function Comment
0 Initialization
0: Firmware update not started
1: Firmware update started
1 Check firmware integrity
0: no action
1: Saved firmware integrity check started
2 Integrity check status
0: Integrity check failed
1: Integrity check successful
3 Firmware transfer
0: no transfer
1: Firmware is transferred to the subsystem
4 Result of firmware update
0: Unable to complete update
1: Firmware update successfully transferred to subsystem
5 - 18 Internal debug information

Bosch Rexroth AG RE29283-FK/03.23, Edition 01


3DRE(E)(A), Z3DRE(E)(A) 85 / 112
P-0-2890.0.4 - pressure controller: Control word

9.21.2 IO-Link mapping


Parameter set Index Subindex
- - -

9.22 P-0-2890.0.3 - pressure controller: Slider (controller


behavior)
9.22.1 Description

Parameter descriptions
This parameter sets the value of the slider for the pressure controller. Via the slider, the controller
behavior of the pressure controller can be easily set between moderate, balanced and aggressive.

9.22.2 IO-Link mapping


Parameter set Index Subindex
0 100 1
1 100 2
2 100 3
3 100 4

9.23 P-0-2890.0.4 - pressure controller: Control word


9.23.1 Description
Functions of the pressure controller can be activated or deactivated via the control word.
Set-up of the control word:
Bit Name / Function Comment
0-3 Reserved
4 I-term switch-off behavior
0: I-term of the pressure con-
troller is frozen during switching
off.
1: I-term of the pressure con-
troller will be deleted during
switching off.
5 Automatic switch-off of the PI- see also further explanation of the
term control bit following this table
0: not active
1: active
6-7 Reserved

RE29283-FK/03.23, Bosch Rexroth AG


Edition 01
86 / 112 3DRE(E)(A), Z3DRE(E)(A)
P-0-2890.0.6 - Solenoid current: Offset

Bit Name / Function Comment


8 Slider
0: Slider not active
1: Slider active
9-15 Reserved
Bit 5 - Automatic switch-off of the PI-term:
In case of command value jumps, the automatic switch-off of the PI-term of the pressure controller
can be activated via the control bit. After an adjustable closed-loop error has been reached, the PI
controller is automatically switched on again. This feature can prevent the pressure controller from
overshooting in the case of command value jumps. By means of the parameters P-0-2892.0.12 and
P-0-2892.0.13, the height of the command value step at which the switch-off of the PI controller
takes place is predetermined as a function of direction. With the parameters P-0-2892.0.10 and
P-0-2892.0.11, the control deviation is set as a function of direction, at which the PI controller
becomes active again.

9.23.2 IO-Link mapping


Parameter set Index Subindex
0 81 1
1 81 2
2 81 3
3 81 4

9.24 P-0-2890.0.5 - Pressure command value preparation: Gain


9.24.1 Description
This parameter can be used to change the gain of the pressure command value.
Notice: The parameter shall be used only for internal testing purposes of the pressure controller and the
solenoid current controller.

9.24.2 IO-Link mapping


Parameter set Index Subindex
- 93 0

9.25 P-0-2890.0.6 - Solenoid current: Offset


9.25.1 Description
This parameter can be used to set an offset for the solenoid current.

Bosch Rexroth AG RE29283-FK/03.23, Edition 01


3DRE(E)(A), Z3DRE(E)(A) 87 / 112
P-0-2890.0.8 - Solenoid current controller: Dither frequency factor

The valve is set ex works over the complete pressure range (→ 0 bar to the nominal pressure of
the valve) for the optimal volume flow specified in the valve data sheet. Due to the aging of the
pressure valve or due to a volume flow differing from the valve data sheet, this optimum adjustment
no longer fits. This can be corrected accordingly via the offset for the solenoid current and the gain in
P-0-2890.0.7.

9.25.2 IO-Link mapping


Parameter set Index Subindex
- 94 0

Parameter descriptions
9.26 P-0-2890.0.7 - Solenoid current: P-gain
9.26.1 Description
This parameter will set the gain of the solenoid current.
The valve is set ex works over the complete pressure range (→ 0 bar to the nominal pressure of
the valve) for the optimal volume flow specified in the valve data sheet. Due to the aging of the
pressure valve or due to a volume flow differing from the valve data sheet, this optimum adjustment
no longer fits. This can be corrected accordingly via the gain for the solenoid current and the offset in
P-0-2890.0.6.

9.26.2 IO-Link mapping


Parameter set Index Subindex
- 95 0

9.27 P-0-2890.0.8 - Solenoid current controller: Dither frequency


factor
9.27.1 Description
In this parameter is the factor by which the dither frequency calculated by the solenoid current
controller is multiplied.
The dither frequency for the pressure valve is set ex works so that the two following conditions are
optimally met:
• The dither has as little influence as possible on the amplitude of the actual pressure value.
• A corresponding dynamic of the valve is achieved.
The dither frequency can be adjusted via the factor in such a way that the pressure valve is optimized in
response to one of the conditions:
• Increasing the dynamics of the valve by a smaller dither frequency (→ factor < 1), which results in
a higher pressure amplitude.
• Reduction of the actual pressure value amplitude (→ factor > 1), which results in a worse dynamic
of the valve.

RE29283-FK/03.23, Bosch Rexroth AG


Edition 01
88 / 112 3DRE(E)(A), Z3DRE(E)(A)
P-0-2890.0.11 - pressure controller: Spring force flow rate

Ex works, the factor is set to 1.


Attention: A change to the dither frequency should only be made after consultation with the Bosch
Rexroth service department.

9.27.2 IO-Link mapping


Parameter set Index Subindex
- 96 0

9.28 P-0-2890.0.9 - Actual pressure value: Filter frequency


9.28.1 Description
In this parameter, the frequency of the PT1 filter is set, with which the actual pressure value detected
via the pressure sensor is smoothened.

9.28.2 IO-Link mapping


Parameter set Index Subindex
- 91 0

9.29 P-0-2890.0.10 - pressure controller: Nozzle diameter flow rate


9.29.1 Description
This parameter specifies the diameter of the nozzle installed in the pressure valve. This information is
required for the automatic calculation of the flow rate of the pressure valve (see P-0-2890.0.16).

9.29.2 IO-Link mapping


Parameter set Index Subindex
- - -

9.30 P-0-2890.0.11 - pressure controller: Spring force flow rate


9.30.1 Description
This parameter specifies the force of the spring installed in the pressure valve in [bar]. This information
is required for the automatic calculation of the flow rate of the pressure valve (see P-0-2890.0.16).

9.30.2 IO-Link mapping


Parameter set Index Subindex
- - -

Bosch Rexroth AG RE29283-FK/03.23, Edition 01


3DRE(E)(A), Z3DRE(E)(A) 89 / 112
P-0-2892.0.2 - pressure controller: P-gain

9.31 P-0-2890.0.12 - pressure controller: Medium density flow rate


9.31.1 Description
This parameter specifies the density of the oil used in [kg/dm]. This information is required for the
automatic calculation of the flow rate of the pressure valve (see P-0-2890.0.16).

9.31.2 IO-Link mapping


Parameter set Index Subindex

Parameter descriptions
- - -

9.32 P-0-2890.0.13 - pressure controller: Valve flow rate


9.32.1 Description
This parameter specifies the flow rate of the pressure valve to be taken into account in the pressure
controller when the automatic calculation of the flow rate is not activated (see also P-0-2890.0.16).

9.32.2 IO-Link mapping


Parameter set Index Subindex
- - -

9.33 P-0-2892.0.1 - pressure controller: I-gain


9.33.1 Description
This parameter set the I-gain of the pressure controller.

9.33.2 IO-Link mapping


Parameter set Index Subindex
0 101 1
1 101 2
2 101 3
3 101 4

9.34 P-0-2892.0.2 - pressure controller: P-gain


9.34.1 Description
This parameter is used to set the proportional gain (P-gain) of the pressure controller.

RE29283-FK/03.23, Bosch Rexroth AG


Edition 01
90 / 112 3DRE(E)(A), Z3DRE(E)(A)
P-0-2892.0.4 - pressure controller: Gain, I-term active damping

9.34.2 IO-Link mapping


Parameter set Index Subindex
0 102 1
1 102 2
2 102 3
3 102 4

9.35 P-0-2892.0.3 - pressure controller: Gain, active damping


9.35.1 Description
In the pressure controller, within the framework of active damping, the change in the actual pressure
value (→ velocity) is fed back to closed-loop control with a scaling factor in order to achieve a better
controller behavior.
This parameter is used to set the factor by which the change in the actual pressure value is to
be returned. The resulting value is subtracted from the output of the PI controller of the pressure
controller.
Notice: The change in the actual pressure value (→ velocity) is determined with a clock pulse of 1 ms.

9.35.2 IO-Link mapping


Parameter set Index Subindex
0 103 1
1 103 2
2 103 3
3 103 4

9.36 P-0-2892.0.4 - pressure controller: Gain, I-term active


damping
9.36.1 Description
In the pressure controller, within the framework of active damping, the change in the actual pressure
value (→ velocity) is fed back to closed-loop control with a scaling factor in order to achieve a better
controller behavior.
This parameter is used to set the factor by which the change in the actual pressure value is to be
returned to the integrator part of the pressure controller. The resulting value is subtracted from the
input signal of the integrator of the pressure controller.
Notice: The change in the actual pressure value (→ velocity) is detected with a sampling rate of 10 ms.

9.36.2 IO-Link mapping


Parameter set Index Subindex
0 104 1

Bosch Rexroth AG RE29283-FK/03.23, Edition 01


3DRE(E)(A), Z3DRE(E)(A) 91 / 112
P-0-2892.0.6 - Pressure command value preparation: Ramp time positive

Parameter set Index Subindex


1 104 2
2 104 3
3 104 4

9.37 P-0-2892.0.5 - pressure controller: Integrator switch-off


threshold

Parameter descriptions
9.37.1 Description
This parameter set the threshold at which the integrator of the pressure controller is switched off.
Switch-off behavior of the integrator The control word P-0-2890.0.4 defines whether the I-term of
the control value of the pressure controller should be frozen or deleted during the switching off of the
integrator.

9.37.2 IO-Link mapping


Parameter set Index Subindex
0 105 1
1 105 2
2 105 3
3 105 4

9.38 P-0-2892.0.6 - Pressure command value preparation: Ramp


time positive
9.38.1 Description
The pressure command value is guided over a command value ramp to avoid abrupt changes. With this
parameter, the ramp time for positive pressure command value changes is set.

9.38.2 IO-Link mapping


Parameter set Index Subindex
0 106 1
1 106 2
2 106 3
3 106 4

RE29283-FK/03.23, Bosch Rexroth AG


Edition 01
92 / 112 3DRE(E)(A), Z3DRE(E)(A)
P-0-2900.1.1 - Analog command value input: Control word

9.39 P-0-2892.0.7 - Pressure command value preparation: Ramp


time negative
9.39.1 Description
The pressure command value is guided over a command value ramp to avoid abrupt changes. With this
parameter, the ramp time for negative pressure command value changes is set.

9.39.2 IO-Link mapping


Parameter set Index Subindex
0 107 1
1 107 2
2 107 3
3 107 4

9.40 P-0-2892.0.8 - Pressure command value preparation: Filter


frequency
9.40.1 Description
The pressure command value can be smoothened via a PT1 filter. Its filter frequency is set by this
parameter.

9.40.2 IO-Link mapping


Parameter set Index Subindex
0 108 1
1 108 2
2 108 3
3 108 4

9.41 P-0-2900.1.1 - Analog command value input: Control word


9.41.1 Description
This parameter contains the control word for configuring the analog command value input of the
pressure valve on the connector XH1. The analog command value input can be set as a voltage or
current input via the control word.
Set-up of the control word:

Bosch Rexroth AG RE29283-FK/03.23, Edition 01


3DRE(E)(A), Z3DRE(E)(A) 93 / 112
P-0-2900.1.8 - Analog command value input: Signal range, lower limit

Bit Name / Function Comment


0 Activating the command value The conversion of the voltage or
input current signal on the command
0: Not active value input into the pressure com-
mand value (→ S-0-0800) is acti-
1: Active
vated via the activation bit.
1-3 Reserved -
4-5 Type of signal
0b00: Voltage (0-10V)

Parameter descriptions
0b01: Current (4-20mA)
0b10: reserved
0b11: reserved
6-15 Reserved -
Conversion of the analog command value into V or mA into the pressure command value in bar
The voltage in V applied to the command value input or the current applied in mA is converted into a
corresponding pressure command value in bar (→ S-0-0800). The conversion into pressure command
value is defined by the following 4 parameters:
• P-0-2900.1.8
• P-0-2900.1.9
• P-0-2900.1.10
• P-0-2900.1.11
A signal range (e.g. 0-10 V) is defined via the two parameters P-0-2900.1.8 and P-0-2900.1.9,
which is converted to a value range (e.g. 0-100 bar). The value range is set using the parameters
P-0-2900.1.10 and P-0-2900.1.11.

9.41.2 IO-Link mapping


Parameter set Index Subindex
- - -

9.42 P-0-2900.1.8 - Analog command value input: Signal range,


lower limit
9.42.1 Description
In this parameter, the lower limit of the signal range for the analog command value input on the
connector XH1 is set. Depending on the type of signal set in the control parameter P-0-2900.1.1, a
value in V or mA is input in this parameter. This parameter is one of the parameters via which the
conversion of the analog command value into V or mA into the pressure command value into bar is set.
Conversion of the analog command value into V or mA into the pressure command value in bar

RE29283-FK/03.23, Bosch Rexroth AG


Edition 01
94 / 112 3DRE(E)(A), Z3DRE(E)(A)
P-0-2900.1.9 - Analog command value input: Signal range, upper limit

The voltage in V applied to the command value input or the current applied in mA is converted into a
corresponding pressure command value in bar (→ S-0-0800). The conversion into pressure command
value is defined by the following 4 parameters:
• P-0-2900.1.8
• P-0-2900.1.9
• P-0-2900.1.10
• P-0-2900.1.11
A signal range (e.g. 0-10 V) is defined via the two parameters P-0-2900.1.8 and P-0-2900.1.9,
which is converted to a value range (e.g. 0-100 bar). The value range is set using the parameters
P-0-2900.1.10 and P-0-2900.1.11.

9.42.2 IO-Link mapping


Parameter set Index Subindex
- - -

9.43 P-0-2900.1.9 - Analog command value input: Signal range,


upper limit
9.43.1 Description
In this parameter, the upper limit of the signal range for the analog command value input on the
connector XH1 is set. Depending on the type of signal set in the control parameter P-0-2900.1.1, a
value in V or mA is input in this parameter. This parameter is one of the parameters via which the
conversion of the analog command value into V or mA into the pressure command value into bar is set.
Conversion of the analog command value into V or mA into the pressure command value in bar
The voltage in V applied to the command value input or the current applied in mA is converted into a
corresponding pressure command value in bar (→ S-0-0800). The conversion into pressure command
value is defined by the following 4 parameters:
• P-0-2900.1.8
• P-0-2900.1.9
• P-0-2900.1.10
• P-0-2900.1.11
A signal range (e.g. 0-10 V) is defined via the two parameters P-0-2900.1.8 and P-0-2900.1.9,
which is converted to a value range (e.g. 0-100 bar). The value range is set using the parameters
P-0-2900.1.10 and P-0-2900.1.11.

9.43.2 IO-Link mapping


Parameter set Index Subindex
- - -

Bosch Rexroth AG RE29283-FK/03.23, Edition 01


3DRE(E)(A), Z3DRE(E)(A) 95 / 112
P-0-2900.1.11 - Analog command value input: Value range, upper limit

9.44 P-0-2900.1.10 - Analog command value input: Value range,


lower limit
9.44.1 Description
In this parameter, the lower limit of the value range for the analog command value input on the
connector XH1 is set. In this parameter, a value is entered in bar. This parameter is one of the
parameters via which the conversion of the analog command value into V or mA into the pressure
command value into bar is set.

Parameter descriptions
Conversion of the analog command value into V or mA into the pressure command value in bar
The voltage in V applied to the command value input or the current applied in mA is converted into a
corresponding pressure command value in bar (→ S-0-0800). The conversion into pressure command
value is defined by the following 4 parameters:
• P-0-2900.1.8
• P-0-2900.1.9
• P-0-2900.1.10
• P-0-2900.1.11
A signal range (e.g. 0-10 V) is defined via the two parameters P-0-2900.1.8 and P-0-2900.1.9,
which is converted to a value range (e.g. 0-100 bar). The value range is set using the parameters
P-0-2900.1.10 and P-0-2900.1.11.

9.44.2 IO-Link mapping


Parameter set Index Subindex
- - -

9.45 P-0-2900.1.11 - Analog command value input: Value range,


upper limit
9.45.1 Description
In this parameter, the upper limit of the value range for the analog command value input on the
connector XH1 is set. In this parameter, a value is entered in bar. This parameter is one of the
parameters via which the conversion of the analog command value into V or mA into the pressure
command value into bar is set.
Conversion of the analog command value into V or mA into the pressure command value in bar
The voltage in V applied to the command value input or the current applied in mA is converted into a
corresponding pressure command value in bar (→ S-0-0800). The conversion into pressure command
value is defined by the following 4 parameters:
• P-0-2900.1.8
• P-0-2900.1.9
• P-0-2900.1.10
• P-0-2900.1.11

RE29283-FK/03.23, Bosch Rexroth AG


Edition 01
96 / 112 3DRE(E)(A), Z3DRE(E)(A)
P-0-2900.2.1 Analog actual pressure value input: Control word

A signal range (e.g. 0-10 V) is defined via the two parameters P-0-2900.1.8 and P-0-2900.1.9,
which is converted to a value range (e.g. 0-100 bar). The value range is set using the parameters
P-0-2900.1.10 and P-0-2900.1.11.

9.45.2 IO-Link mapping


Parameter set Index Subindex
- - -

9.46 P-0-2900.2.1 Analog actual pressure value input: Control word


9.46.1 Description
This parameter contains the control word for the configuration of the analog input of the pressure valve
to which the internal or external pressure sensor is connected. The analog input can be set as a voltage
or current input via the control word.
Set-up of the control word:
Bit Name / Function Comment
0 Analog input activation The conversion of the voltage or
0: Not active current signal on the analog input
into the actual pressure value (→
1: Active
S-0-0809) is activated via the
activation bit.
1-3 Reserved -
4-5 Type of signal
0b00: Voltage (0-10 V)
0b01: Current (4-20 mA)
0b10: reserved
0b11: reserved
6-15 Reserved -
Conversion of the analog actual pressure value into V or mA into the actual pressure value in bar
A voltage in V or a current in mA is present at the analog input to which the internal or external pressure
sensor of the valve is connected. This voltage or current signal is converted into a corresponding actual
pressure value in bar (→ S-0-0809). The conversion into the actual pressure value is defined by the
following 4 parameters:
• P-0-2900.2.8
• P-0-2900.2.9
• P-0-2900.2.10
• P-0-2900.2.11
A signal range (e.g. 0.1-10 V) is defined via the two parameters P-0-2900.2.8 and P-0-2900.2.9,
which is converted to a value range (e.g. 0-400 bar). The value range is set using the parameters
P-0-2900.2.10 and P-0-2900.2.11.

Bosch Rexroth AG RE29283-FK/03.23, Edition 01


3DRE(E)(A), Z3DRE(E)(A) 97 / 112
P-0-2900.2.9 - Analog actual pressure value input: Signal range, upper limit

9.46.2 IO-Link mapping


Parameter set Index Subindex
- - -

9.47 P-0-2900.2.8 Analog actual pressure value input: Signal range,


lower limit
9.47.1 Description

Parameter descriptions
In this parameter, the lower limit of the signal range for the analog input is set, to which the internal or
external pressure sensor of the valve is connected. Depending on the type of signal set in the control
parameter P-0-2900.2.1, a value in V or mA is input in this parameter. This parameter is one of the
parameters via which the conversion of the analog actual pressure value into V or mA into the actual
pressure value into bar is set.
Conversion of the analog actual pressure value into V or mA into the actual pressure value in bar. A
voltage in V or a current in mA is present at the analog input to which the internal or external pressure
sensor of the valve is connected. This voltage or current signal is converted into a corresponding actual
pressure value in bar (→ S-0-0809). The conversion into the actual pressure value is defined by the
following 4 parameters:
• P-0-2900.2.8
• P-0-2900.2.9
• P-0-2900.2.10
• P-0-2900.2.11
A signal range (e.g. 0.1-10 V) is defined via the two parameters P-0-2900.2.8 and P-0-2900.2.9,
which is converted to a value range (e.g. 0-400 bar). The value range is set using the parameters
P-0-2900.2.10 and P-0-2900.2.11.

9.47.2 IO-Link mapping


Parameter set Index Subindex
- 86 0

9.48 P-0-2900.2.9 - Analog actual pressure value input: Signal


range, upper limit
9.48.1 Description
In this parameter, the upper limit of the signal range for the analog input is set, to which the internal or
external pressure sensor of the valve is connected. Depending on the type of signal set in the control
parameter P-0-2900.2.1, a value in V or mA is input in this parameter. This parameter is one of the
parameters via which the conversion of the analog actual pressure value into V or mA into the actual
pressure value into bar is set.
Conversion of the analog actual pressure value into V or mA into the actual pressure value in bar

RE29283-FK/03.23, Bosch Rexroth AG


Edition 01
98 / 112 3DRE(E)(A), Z3DRE(E)(A)
P-0-2900.2.10 - Analog actual pressure value input: Value range, lower limit

A voltage in V or a current in mA is present at the analog input to which the internal or external pressure
sensor of the valve is connected. This voltage or current signal is converted into a corresponding actual
pressure value in bar (→ S-0-0809). The conversion into the actual pressure value is defined by the
following 4 parameters:
• P-0-2900.2.8
• P-0-2900.2.9
• P-0-2900.2.10
• P-0-2900.2.11
A signal range (e.g. 0.1-10 V) is defined via the two parameters P-0-2900.2.8 and P-0-2900.2.9,
which is converted to a value range (e.g. 0-400 bar). The value range is set using the parameters
P-0-2900.2.10 and P-0-2900.2.11.

9.48.2 IO-Link mapping


Parameter set Index Subindex
- 87 0

9.49 P-0-2900.2.10 - Analog actual pressure value input: Value


range, lower limit
9.49.1 Description
In this parameter, the lower limit of the value range for the analog input is set, to which the internal
or external pressure sensor of the valve is connected. In this parameter, a value is entered in bar. This
parameter is one of the parameters via which the conversion of the analog actual pressure value into V
or mA into the actual pressure value into bar is set.
Conversion of the analog actual pressure value into V or mA into the actual pressure value in bar
A voltage in V or a current in mA is present at the analog input to which the internal or external pressure
sensor of the valve is connected. This voltage or current signal is converted into a corresponding actual
pressure value in bar (→ S-0-0809). The conversion into the actual pressure value is defined by the
following 4 parameters:
• P-0-2900.2.8
• P-0-2900.2.9
• P-0-2900.2.10
• P-0-2900.2.11
A signal range (e.g. 0.1-10 V) is defined via the two parameters P-0-2900.2.8 and P-0-2900.2.9,
which is converted to a value range (e.g. 0-400 bar). The value range is set using the parameters
P-0-2900.2.10 and P-0-2900.2.11.

9.49.2 IO-Link mapping


Parameter set Index Subindex
- 88 0

Bosch Rexroth AG RE29283-FK/03.23, Edition 01


3DRE(E)(A), Z3DRE(E)(A) 99 / 112
P-0-2907.1.1 - Analog command value input: Actual value

9.50 P-0-2900.2.11 - Analog actual pressure value input: Value


range, upper limit
9.50.1 Description
In this parameter, the upper limit of the value range for the analog input is set, to which the internal
or external pressure sensor of the valve is connected. In this parameter, a value is entered in bar. This
parameter is one of the parameters via which the conversion of the analog actual pressure value into V
or mA into the actual pressure value into bar is set.

Parameter descriptions
Conversion of the analog actual pressure value into V or mA into the actual pressure value in bar
A voltage in V or a current in mA is present at the analog input to which the internal or external pressure
sensor of the valve is connected. This voltage or current signal is converted into a corresponding actual
pressure value in bar (→ S-0-0809). The conversion into the actual pressure value is defined by the
following 4 parameters:
• P-0-2900.2.8
• P-0-2900.2.9
• P-0-2900.2.10
• P-0-2900.2.11
A signal range (e.g. 0.1-10 V) is defined via the two parameters P-0-2900.2.8 and P-0-2900.2.9,
which is converted to a value range (e.g. 0-400 bar). The value range is set using the parameters
P-0-2900.2.10 and P-0-2900.2.11.

9.50.2 IO-Link mapping


Parameter set Index Subindex
- 89 0

9.51 P-0-2907.1.1 - Analog command value input: Actual value


9.51.1 Description
This parameter indicates the voltage currently applied to the analog command value input (→ con-
nector XH1) or the current applied.
For this parameter to display a corresponding value, the following conditions must be met:
• The analog command value input was activated via the control parameter P-0-2900.1.1.
• The parameters for converting the analog command value (V or mA) into the pressure command
value in bar are correctly configured. These are the following parameters:
– P-0-2900.1.8
– P-0-2900.1.9
– P-0-2900.1.10
– P-0-2900.1.11
Depending on the type of signal set in the control parameter P-0-2900.1.1, a value in V or mA is
displayed in this parameter.

RE29283-FK/03.23, Bosch Rexroth AG


Edition 01
100 / 112 3DRE(E)(A), Z3DRE(E)(A)
P-0-2908.1.1 - Analog actual value output: Actual value

9.51.2 IO-Link mapping


Parameter set Index Subindex
- - -

9.52 P-0-2907.2.1 - Analog actual pressure value input: Actual


value
9.52.1 Description
This parameter indicates the currently applied voltage or current at the analog input of the pressure
valve to which the internal or external pressure sensor is connected.
In order for a corresponding voltage or current value to be displayed in this parameter, the following
conditions must be met:
• The analog input was activated via the control parameter P-0-2900.2.1.
• The parameters for converting the analog actual pressure value (V or mA) into the actual pressure
value in bar are correctly configured. These are the following parameters:
– P-0-2900.2.8
– P-0-2900.2.9
– P-0-2900.2.10
– P-0-2900.2.11
Depending on the type of signal set in the control parameter P-0-2900.2.1, a value in V or mA is
displayed in this parameter.

9.52.2 IO-Link mapping


Parameter set Index Subindex
- 84 0

9.53 P-0-2908.1.1 - Analog actual value output: Actual value


9.53.1 Description
This parameter indicates the current output voltage or output current at the analog actual value output
of the pressure valve (→ connector XH1).
For this parameter to display a corresponding value, the following conditions must be met:
• The analog actual value output was activated via the control parameter P-0-2900.2.1.
Depending on the type of signal set in the control parameter P-0-2900.2.1, a value in V or mA is
displayed in this parameter.

9.53.2 IO-Link mapping


Parameter set Index Subindex
- - -

Bosch Rexroth AG RE29283-FK/03.23, Edition 01


3DRE(E)(A), Z3DRE(E)(A) 101 / 112
P-0-2915.0.3 - Actual current value: Solenoid A

9.54 P-0-2908.1.2 - Analog actual value output: Control word


9.54.1 Description
This parameter contains the control word for configuring the analog actual value output of the pressure
valve on the connector XH1. The analog actual value output can be set as a voltage or current output via
the control word.
Set-up of the control word:
Bit Name / Function Comment

Parameter descriptions
0 Activation of the actual value The output of the actual pressure
output value to the analog actual value
0: Not active output is activated via the activa-
tion bit.
1: Active
1-3 Reserved -
4-5 Type of signal The type of signal is used to set
0b00: Voltage (0-10 V) whether the actual pressure value
is output as a voltage signal in
0b01: Current (4-20 mA)
the range from 0 to 10 V or as a
0b10: reserved current signal in the current range
0b11: reserved from 4 to 20 mA.
6-15 Reserved -

9.54.2 IO-Link mapping


Parameter set Index Subindex
- - -

9.55 P-0-2915.0.3 - Actual current value: Solenoid A


9.55.1 Description
This parameter displays the current actual current value in the solenoid of the pressure valve. The actual
current value is shown in mA.

9.55.2 IO-Link mapping


Parameter set Index Subindex
- 82 0

RE29283-FK/03.23, Bosch Rexroth AG


Edition 01
102 / 112 3DRE(E)(A), Z3DRE(E)(A)
P-0-4073 - IO link: Diagnosis

9.56 P-0-4028 - Valve: Control word


9.56.1 Description
In this parameter, the control word of the pressure valve is used for pressure valves with an analog
interface (→ connector XH1). This parameter is mapped into the effective control word of the pressure
valve (→ P-0-0116).
Set-up of the control word:
Bit Name / Function Comment
0-1 Parameter set number
0b00: Parameter set 0
0b01: Parameter set 1
0b10: Parameter set 2
0b11: Parameter set 3
2-7 Reserved
8-9 Operating mode
0b00: Open-loop pressure con-
trol active
0b01: Closed-loop pressure con-
trol active
0b10: reserved
0b11: reserved
10-14 Reserved
15 Enable
0: no enable
1: Enable active

9.56.2 IO-Link mapping


Parameter set Index Subindex
- - -

9.57 P-0-4073 - IO link: Diagnosis


9.57.1 Description
This parameter displays the state of the IO interface of the valve as a string.
Displayed string Meaning
"not active" No cyclic data exchange via IO-Link
"cyclic" Cyclic data exchange via IO-Link.

Bosch Rexroth AG RE29283-FK/03.23, Edition 01


3DRE(E)(A), Z3DRE(E)(A) 103 / 112
P-0-4085 - Force mode: Configuration

9.57.2 IO-Link mapping


Parameter set Index Subindex
- 69 0

9.58 P-0-4085 - Force mode: Configuration


9.58.1 Description
This parameter is used to configure the force mode.

Parameter descriptions
Bit Name / Function Comment
0-3 Reserved
4 Valve enable forcing If the bit is set (active), the enable that is
0: Not active set via P-0-0120 is active. Otherwise, the
valve enable which is specified via parameter
1: Active
P-0-4028 (→ pressure valve with analog
interface) or P-0-1910.0.1 (→ pressure
valve with digital IO-Link interface) is active.
5 Parameter set forcing If the bit is set (active), the parameter set
0: Not active that is set via P-0-0120 is active. Otherwise,
the parameter set which is specified via
1: Active
P-0-4028 (→ pressure valve with analog
interface) or P-0-1910.0.1 (→ pressure
valve with digital IO-Link interface) is active.
6 Pressure command value forcing If the bit is set (active), then the pressure
0: Not active command value acts in P-0-2878.0.1. Other-
wise, the pressure command value is active in
1: Active
S-0-0800, which is specified via the analog
interface or the digital IO-Link interface.
7 Operating mode forcing If the bit is set (active), the operating mode
0: Not active that is set via P-0-0120 is active. Otherwise,
the operating mode which is specified via
1: Active
P-0-4028 (→ pressure valve with analog
interface) or P-0-1910.0.1 (→ pressure
valve with digital IO-Link interface) is active.
8-15 Reserved

9.58.2 IO-Link mapping


Parameter set Index Subindex
- - -

RE29283-FK/03.23, Bosch Rexroth AG


Edition 01
104 / 112 3DRE(E)(A), Z3DRE(E)(A)
S-0-0140 - Valve designation

9.59 S-0-0017 - List of all valve parameters


9.59.1 Description
This parameter contains the list with the identifiers of all parameters present in the valve (→ configura-
tion parameters and process parameters). The desired functionality of the valve is set by means of
the configuration parameters (e.g. command value preparation, controller). Current actual values and
states of the valve are displayed via the process parameters (e.g. actual current value, error status)
Parameter list depending on the logged in user
The contents of the list depends on the user currently logged in to the valve and their access rights. The
user currently logged into the valve is displayed in parameter P-0-2909.0.1.

9.59.2 IO-Link mapping


Parameter set Index Subindex
- - -

9.60 S-0-0030 - Firmware version


9.60.1 Description
The parameter contains the firmware version of the valve as a string. The string is structured as follows:
FWA-HYDRVX-<firmware derivative>-<major version>.<minor version>.<patch version>-E1
e.g. FWA-HYDRVX-HVP-1.1.0-E1

9.60.2 IO-Link mapping


Parameter set Index Subindex
- - -

9.61 S-0-0140 - Valve designation


9.61.1 Description
This parameter displays the valve ordering information according to the type key.
Notice: The parameter S-0-1300.0.4 also contains the ordering information of the valve. For compati-
bility reasons, this parameter is currently required in addition to the S-0-1300.0.4.

9.61.2 IO-Link mapping


Parameter set Index Subindex
- - -

Bosch Rexroth AG RE29283-FK/03.23, Edition 01


3DRE(E)(A), Z3DRE(E)(A) 105 / 112
S-0-0262 - Command: Load default values

9.62 S-0-0192 - List of all configuration parameters


9.62.1 Description
This parameter contains the list of all configuration parameters present in the valve. The desired
functionality of the valve is set via the configuration parameters (e.g. command value preparation,
controller). Th configuration parameters for the valve are optimally set ex works and their values are
stored in the valve.
Parameter list depending on the logged in user

Parameter descriptions
The contents of the displayed parameter list depends on the user currently logged in to the valve and
their access rights. The user currently logged into the valve is displayed in parameter P-0-2909.0.1.
Saving the configuration parameters
If configuration parameters are changed, they are not automatically stored, but must be remanently
secured in the valve via command S-0-0264.

9.62.2 IO-Link mapping


Parameter set Index Subindex
- - -

9.63 S-0-0254 - Current parameter set


9.63.1 Description
This parameter indicates which parameter set is currently active. The following assignment applies:
• 0 = parameter set 0 is active
• 1 = parameter set 1 is active
• 2 = parameter set 2 is active
• 3 = parameter set 3 is active

9.63.2 IO-Link mapping


Parameter set Index Subindex
- - -

9.64 S-0-0262 - Command: Load default values


9.64.1 Description
With this command, the condition as supplied of the valve can be restored in conjunction with
command P-0-0670.0.3. If the two commands S-0-0262 and P-0-0670.0.3 are executed in sequence,
all configuration parameters of the valve are reset to the values with which the valve was delivered ex
works.
After executing the commands, the command S-0-0264 must be executed so that the reset parameter
values are stored in the valve in a remanent manner.

RE29283-FK/03.23, Bosch Rexroth AG


Edition 01
106 / 112 3DRE(E)(A), Z3DRE(E)(A)
S-0-0809 - Actual pressure value

When the valve condition as supplied is restored, the admin password is not reset.

9.64.2 IO-Link mapping


System command
130

9.65 S-0-0264 - Command: Save configuration parameters


9.65.1 Description
With this command, the configuration parameters are permanently saved in the valve. The parameter
S-0-0192 contains the list of configuration parameters.

9.65.2 IO-Link mapping


System command
161

9.66 S-0-0800 - Pressure command value


9.66.1 Description
This parameter shows the current pressure command value at which either analog, via the analog
desired value input (→ connector XH1), or digital, via the IO-Link interface (→ connector XH5), is
preset.

9.66.2 IO-Link mapping


Parameter set Index Subindex
- 78 0

9.67 S-0-0809 - Actual pressure value


9.67.1 Description
This parameter displays the current actual pressure value.

9.67.2 IO-Link mapping


Parameter set Index Subindex
- 79 0

Bosch Rexroth AG RE29283-FK/03.23, Edition 01


3DRE(E)(A), Z3DRE(E)(A) 107 / 112
List of addresses

9.68 S-0-0814 - Tank pressure


9.68.1 Description
This parameter is where the tank pressure for the pressure valve is set.
Notice: This parameter is currently only required for the production of the pressure valve to determine
the internal pressure/current characteristic curve.

9.68.2 IO-Link mapping


Parameter set Index Subindex
- 74 0

Appendix
9.69 S-0-0827 - Pressure control deviation
9.69.1 Description
This parameter displays the current pressure control deviation.

9.69.2 IO-Link mapping


Parameter set Index Subindex
- - -

10 Appendix
10.1 List of addresses
Contacts for service and spare parts
Bosch Rexroth AG
Bürgermeister-Dr.-Nebel-Straße 8
97816 Lohr am Main, Germany
Phone +49 (0) 9352/40 50 60
Email: service@boschrexroth.de

Headquarters
Bosch Rexroth AG
Zum Eisengiesser 1
97816 Lohr am Main, Germany
Phone +49 (0) 9352/18-0

RE29283-FK/03.23, Bosch Rexroth AG


Edition 01
108 / 112 3DRE(E)(A), Z3DRE(E)(A)
List of addresses

For questions about the product


Phone +49 (0) 9352/40 30 20
Email my.support@boschrexroth.de

The addresses of our sales and service network and sales organizations can be found at
www.boschrexroth.com/adressen

Bosch Rexroth AG RE29283-FK/03.23, Edition 01


3DRE(E)(A), Z3DRE(E)(A) 109 / 112

Index Pressure sensor / Actual pressure value detection


. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
1, 2, 3 ... Process data. . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
"easy2connect" smartphone app. . . . . . . . . . . 21 Q
(Z)3DREA with external pressure sensor. . . . . 17 Qualification of personnel. . . . . . . . . . . . . . . . . 14
(Z)3DREA with integrated pressure sensor. . . 19
R
(Z)3DREE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
A Relevant parameters. . . . . . . . . . . . . . . . . . 41, 47
Representation of information. . . . . . . . . . . . . 13
About this documentation. . . . . . . . . . . . . . . . . 12 Required and amending documentation. . . . . 12
Actual current value . . . . . . . . . . . . . . . . . . . . . 35
S
Actual pressure value. . . . . . . . . . . . . . . . . . . . . 30
Actual pressure value detection. . . . . . . . . . . . 44 Safety instructions. . . . . . . . . . . . . . . . . . . . . . . 13

Index
Actual pressure value filtration. . . . . . . . . . . . . 62 Solenoid current controller. . . . . . . . . . . . . 53, 68
Analog interface . . . . . . . . . . . . . . . . . . . . . . . . 22 V
Appendix. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
Validity of the documentation. . . . . . . . . . . . . . 12
B Valve types. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Backup/Restore. . . . . . . . . . . . . . . . . . . . . . . . . 42
Bluetooth® dongle. . . . . . . . . . . . . . . . . . . . . . . 19
C
Closed-loop pressure control. . . . . . . . . . . . . . 63
Controller structure (Z)3DREA. . . . . . . . . . . . . 56
Controller structure (Z)3DREE. . . . . . . . . . . . . 48
E
Editions of this documentation. . . . . . . . . . . . . 12
External pressure sensor – interface X2N . . . . 43
G
General information on this chapter. . . . . . . . . 13
General safety instructions. . . . . . . . . . . . . . . . 15
I
Improper use. . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Intended use. . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Internal pressure sensor. . . . . . . . . . . . . . . . . . 42
L
List of addresses. . . . . . . . . . . . . . . . . . . . . . . 107
O
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . 16, 48
P
Parameter descriptions. . . . . . . . . . . . . . . . . . . 70
Pressure command value. . . . . . . . . . . . . . . . . 23
Pressure command value preparation. . . . 51, 60

RE29283-FK/03.23, Bosch Rexroth AG


Edition 01
110 / 112 3DRE(E)(A), Z3DRE(E)(A)

Bosch Rexroth AG RE29283-FK/03.23, Edition 01


3DRE(E)(A), Z3DRE(E)(A) 111 / 112

RE29283-FK/03.23, Bosch Rexroth AG


Edition 01