Datasheet 1011 mtl7706+
Datasheet 1011 mtl7706+
Datasheet 1011 mtl7706+
Technical data
February 2018
MTL intrinsic safety solutions EPS7700 Rev 13
MTL7700 range
DIN-rail mounting safety barriers
• Removable terminals
• Bussed power feed to other modules
• Relay and solid state switch modules
• Dual channel variants – 6.3mm per channel
• Proximity detector inputs
• Electronic fusing
• Direct replacement for MTL700 range
barriers
• Compatible terminal numbering and safety
descriptions
Since its introduction in 1984 the MTL700 range has established MTL7700 active modules are protected with an electronic fuse for the
itself as the worldwide standard for safety barriers. Known for its quality majority of applications. The MTL7798 active fused, power feed module
and reliability, the MTL700 range is widely used in applications all over can protect up to 40 other modules using the bussed power facility and
the world. provides a clear indication of a trip condition via a red LED.
The MTL7700 range follows closely in the footsteps of the MTL700, The MTL774X range of barriers offer a NAMUR compatible input and a
but as a DIN rail mounting barrier, providing quick and easy installation choice of relay or solid state output. The solid state outputs are floating
without the need for special hardware. so switching to ground or from a power rail into an input is also possible.
The solid state interface also provides a high frequency transfer for use
Removable terminals are used for ease of installation, maintenance
in flow or rotation applications.
and for providing a loop disconnect by simply unplugging the terminals
from the side of the module. Wire entry is also angled to assist wiring Dual channel relay or solid state modules offer the highest packing
within limited space enclosures. density with only 6.3mm per channel and when used in conjunction with
the power bus, offer users the minimum of wiring with the maximum
MTL7700 barriers clamp simply and securely onto standard T-section
packing density and the lowest cost per channel.
DIN rail, simultaneously making a reliable IS earth connection.
For applications where field power is required for switch inputs
or 2-wire transmitters, the MTL7700 range provides a bussed power
feed facility. When used in conjunction with the MTL7798 power feed
module the user has a fully protected, electronically fused supply to
many barriers with no additional wiring required.
a Terminals 3 & 7 connected together * Diagrams show positive versions. All diodes reversed on negative versions. Additional diodes fitted on ac versions.
2 EPS7700 Rev 13
DRAFT 01 February 2018
The safety description of a barrier, eg ‘10V 50Ω 200mA’, refers to the (13AWG). Hazardous-area terminals are identified by blue labels.
maximum voltage of the terminating Zener or forward diode while the Removal force >15N
fuse is blowing, the minimum value of the terminating resistor, and the
corresponding maximum short-circuit current. It is an indication of the Colour coding of barrier label
fault energy that can be developed in the hazardous area, and not of the Grey: non-polarised
working voltage or end-to-end resistance. Red: positive polarity (MTL7706 negative to transmitter )
2. Polarity Black: negative polarity
Barriers may be polarised + or –, or non-polarised (‘ac’). Polarised White: dummy barrier, MTL7799
barriers accept and/or deliver safe-area voltages of the specified
polarity only. Non-polarised barriers support voltages of either polarity Weight
applied at either end. 140g approx
continuously between the safe-area terminal of any barrier channel
and earth at 20°C without blowing the fuse. For ‘basic’ barriers, it is
specified with the hazardous-area terminal open circuit; if current is
drawn in the hazardous area, the maximum voltage for these barriers
is reduced. The ‘ac’ channels of ‘basic’ barriers and most channels of
overvolt-protected barriers withstand voltages of the opposite polarity
also – see circuit diagrams.
6. Fuse rating
The greatest current that can be passed continuously (for 1000 hours at
35°C) through the fuse.
7. Star connection
In star-connected barriers, the two channels are interlocked such that
the voltage between them cannot exceed the working voltage, Vwkg:
this allows for higher cable capacitance or inductance.
8. Maximum safe-area voltage (Um) MTL7700 RANGE
KEY
BARRIERS SUMMARISED
The maximum permissible safe-area voltage (Um) for MTL7700 range
barriers is 250V ac/dc. TYPE APPLICATION KEY BARRIER
Analogue Resistance temperature detectors 7756ac
input (low-level) Thermocouples, ac sensors 7760ac
Analogue 7706+
input (high-level) Transmitters, 2-wire, 4/20mA 7787+
Analogue Controller outputs, one line earthed 7728+
output Controller outputs, neither line earthed 7787+
Digital (on/off) 7787+
Switches
input 7741/3
Digital (on/off) Solenoids, alarms, LEDs 7728
output
3 EPS7700 Rev 13
DRAFT 01 February 2018
4 EPS7700 Rev 13
DRAFT 01 February 2018
BASIC CIRCUIT
MTL7742 proximity sensor or switch input with solid
state output
Hazardous Area Safe Area
The MTL7742 is a single channel switch/prox input barrier with an open
collector solid state interface to the safe area equipment. The solid
state switch is especially useful for high frequency switching apparatus
including pulse and rotational sensors. The power bus terminal can
be used to connect power to the module and the input power supply
range makes the module suitable for use with unregulated supplies.
BASIC CIRCUIT
ADDITIONAL SPECIFICATION Hazardous Area Safe Area
Safety description
Safety description
10V 19mA
Supply voltage
5 EPS7700 Rev 13
DRAFT 01 February 2018
BASIC CIRCUIT
Hazardous Area Safe Area Bussed power
1
LFD LFD
2
620R +3 COM
5
CH1
10K 6
4
ADDITIONAL SPECIFICATION
Safety description
10V 19mA
Supply voltage
22.9 to 30V dc with respect to earth
Input characteristics
Output energised if input >2.1mA(<2kΩ)
Output de-energised if input <1.2mA(>10kΩ)
LFD relay + Red LED
Energised if input <50µA or <100Ω
6 EPS7700 Rev 13
DRAFT 01 February 2018
MTL7700 range barriers protect devices located in all normally occurring
explosive atmospheres, including air/flammable gas mixtures, dusts
MTL7700 RANGE BARRIER and fibres. Applications covered include the protection of installations
incorporating uncertified devices (‘simple apparatus’) such as thermocouples,
APPLICATIONS switches and resistive sensors, or separately certified ‘energy storing’
(or ‘voltage producing’) apparatus including ac sensors, transmitters and
current-to-pneumatic (I/P) converters. Recommended choices for specific
applications are discussed briefly in the following pages.
3 1 Power +26V
4 MTL7788R+ 2
1-5V
250Ω
7 EPS7700 Rev 13
DRAFT 01 February 2018
RTDs
Hazardous Safe
For 3-wire RTDs, a single MTL7755ac barrier is the most economical Area Area
choice. This is suitable for use with a floating bridge – the two leads
from the bridge arms are protected by the barrier with the third (supply)
lead being earthed through the barrier. The barrier has a low end-to- 1
3
end resistance of only 19Ω/channel to minimise span changes and its
4 2
channels track within 0.15Ω (between –20°C and +60°C) to minimise MTL7755ac
zero shift with temperature.
Receiver
If the bridge circuit is already earthed, the third barrier channel provided
by an MTL7756ac is needed. For extreme accuracy, 3 channels and 3 1
an earth-free bridge can be used, a configuration that cancels out the 4 2
small errors due to barrier leakage. MTL7756ac
7 5
Channels 1 and 2 (those between terminals 1 & 2 and 3 & 4 respectively)
track to within 0.15Ω (between –20°C and 60°C). Receiver
3 1
4 2
MTL7755ac
MTL7761ac
STRAIN-GAUGE BRIDGES
Single strain-gauge bridges
This shows an arrangement using two or three barriers, which is safe
in IIC gases.
With the MTL7761ac, the circuit is powered from a 12V (±6V), 214Ω
(107Ω + 107Ω) source. If the resistive bridge elements are 230Ω,
then the voltage applied to the bridge will be 6.2V, and if the bridge
resistances are 350Ω, then the bridge's applied voltage will be 7.4V.
An MTL7764ac can be used to sense the bridge supply voltage.
8 EPS7700 Rev 13
DRAFT 01 February 2018
Using 350Ω bridge systems, the following voltages are available from
an MTL7766Pac with a ±10V supply:
1 bridge: 13.11V
2 bridges: 9.75V 3 1
+
4 2 Sense
MTL7761Pac —
3 1
4 2 Output (mV)
MTL7761Pac
ANALOGUE OUTPUTS
Controller outputs (I/P converters)
The single-channel MTL7728+ with a voltage drop of 6.66V at 20mA
is the recommended choice for most controller outputs. Higher-power 3 1
versions are available: the MTL7728P+ (5.1V drop) is suitable for IIC 4 MTL7728+ 2
applications; the MTL7729P+ (3.68V drop) for IIB applications.
For controllers with an output circuit separated from the 0V rail by the 3 1
control transistor, the 2-channel MTL7787+ is the preferred choice as 4
MTL7787+ 2
MTL7787P+
the return channel can handle up to 26.6V allowing the control signal to
be turned off completely. The voltage drop is 8.1V at 20mA. A higher-
power version of the latter, the MTL7787P+, is also available. The
return channel of these barriers handle up to 26.4V and the maximum
voltage drop is only 6.38V.
3 1
MTL7787+
4 2
MTL7787P+
The MTL7787+ and MTL7787P+ are also suitable for controllers
containing a resistor which enables the return current to be monitored
9 EPS7700 Rev 13
DRAFT 01 February 2018
Power Bus
3 1 Power +26.6V
4 2 Logic signal
7 MTL7789+ 5 Power +26.6V
8 6 Logic signal
Switches / Proximity detectors
Eaton's MTL range of new switch/prox input barriers provide the user
with a choice of relay and solid state outputs in single and dual channel 3 1
4 2
versions.
7 MTL7741 5
The MTL7741 is single channel with a changeover relay output. 8 6
The MTL7742 has a single channel solid state switch that can be
3 1
configured to switch from a power rail or down to ground. This is also 4 2
ideal for high switching frequency applications. MTL7742 5
6
3 1
The MTL7743 and MTL7744 are dual channel versions affording very 4 2
MTL7743
high packing densities. Power must be provided to these modules 7 MTL7744 5
Power Bus
10 EPS7700 Rev 13
DRAFT 01 February 2018
3 1
+26V
4 MTL7707+ 2
MTL7787+
MTL7787P+ 0V
POSITIVE DC SYSTEMS
Low-level to 12V dc systems 1
3
The two channels of the MTL7764+ and MTL7767+ can be combined +10V/+12V
4 MTL7764+ 2
safely in IIC. MTL7767+ +10V/+12V
0V
The MTL7764+ can be used for low-level logic return signals whilst the
MTL7767+ is used for 6V dc and 12V dc systems.
3 1
18V dc systems +19.6V
The single-channel MTL7722+ is recommended for 18V dc systems. 4
MTL7722+
2
0V
AC AND DC SYSTEMS
High-level ac and dc systems 1
3
The versatile star-connected MTL7765ac and MTL7778ac allow Vwkg MTL7765ac
to be developed from each channel to ground but only allow Vwkg to
4
MTL7778ac
2 12V/24V
be developed between channels. This provides some common-mode 0V
voltage capability and can allow higher cable parameters to be used.
11 EPS7700 Rev 13
DRAFT 01 February 2018
MTL7745
MTL7787+
MTL7787P+
MTL7788+
MTL7788R+
3 1
MTL7789+
4 2
7 5 Contact
8 6 signals
12 EPS7700 Rev 13
DRAFT 01 February 2018
ACCESSORIES
135mm
TGL7700
TAG57
82mm
when using IMB57
as a central support
ERB57O
IMB57
28mm
10mm earth
clamp
ETM7
ERL7
14mm earth-rail
ETL7000 66mm 15mm
clamp
THR2/THR7000
ISP7000
ERB57S
ERB57O Earth-rail bracket, offset
in lower position
Nickel-plated; supplied with two push fasteners, one 14mm earth-rail
2
clamp and one 10mm earth clamp for cables ≤16mm .
3mm
MOUNTING/EARTHING ACCESSORIES
MTL7700 range barriers mount easily and quickly onto standard DIN rail
which also acts as the intrinsically safe earth. 10mm
133.5mm
10mm 14mm
27 35
43.5
Ø4.4 M4 x 16 48 over
10 DIN rail
62
20
14.6
50
5mm
13 EPS7700 Rev 13
DRAFT 01 February 2018
14 EPS7700 Rev 13
DRAFT 01 February 2018
APPROVALS
(for the latest certificate information and cable parameters, see www.mtl-inst.com/certificates)
Region UK UK USA Canada/USA Japan
(Authority) (BASEEFA) (BASEEFA) (FM) (CSA) (TIIS)
Systems
Standard EN 60079-0:2012 EN 50039 3600, 3610 entity CAN/CSA E60079 See Certificates
EN 60079-11:2012 3611, 3810 UL698, UL913, UL1604
IEC60079, C22.2
Approved for [Ex ia Ga] IIC Ex ia IIC AIS/I,II,III/1/Entity Class 1, Div 2, Gps A,B, Ex (ia) IIC
[Ex ia Ga] IIB ‡ Ex ia IIB ‡ ABCDEFG- SCI-942; C,D; Ex nA [ia] IIC T4 Ex (ia) IIB ‡
[Ex ia Da] IIIC NI/I/2/ABCD/T4 Class 1, Zone 2, AEx nA
[I/0] AEx[ia]IIC – IIC T4
SCI-942 Entity;
NI/1/2/IIC/T4
Ta=60ºC except †
where Ta=65ºC
Note: For FM compliance, the MTL7700 range of barriers shall be installed in compliance with the enclosure, mounting, spacing and
segregation requirements of the ultimate application.
‡ Certified to CENELEC IIB/FM Grps C-G only.
† USA (FM) Ta = 65°C See "Approved for" above
15 EPS7700 Rev 13
DRAFT 01 February 2018
The given data is only intended as a product description and should not be regarded as a legal
warranty of properties or guarantee.
In the interest of further technical developments, we reserve the right to make design changes.