Magis Combo 4 v2
Magis Combo 4 v2
Magis Combo 4 v2
3
Dear Customer
Congratulations for having chosen a top-quality Immergas product, able to assure well-being and safety for a long period of time. As an Im-
mergas customer you can also count on a Qualified Authorised After-Sales Technical Assistance Centre, prepared and updated to guarantee
constant efficiency of your appliance. Read the following pages carefully: you will be able to draw useful tips on the proper use of the device,
compliance with which will confirm your satisfaction with the Immergas product.
For assistance and routine maintenance, contact Authorised Technical Service Centres: they have original spare parts and are specifically
trained directly by the manufacturer.
Thermal systems must undergo periodic maintenance and scheduled checks of the energy efficiency in compliance with national,
regional or local provisions in force.
The company IMMERGAS S.p.A., with registered office in via Cisa Ligure 95 42041 Brescello (RE), declares that the design, manufac-
turing and after-sales assistance processes comply with the requirements of standard UNI EN ISO 9001:2015.
For further details on the product CE marking, request a copy of the Declaration of Conformity from the manufacturer, specifying the
appliance model and the language of the country.
The manufacturer declines all liability due to printing or transcription errors, reserving the right to make any modifications to its tech-
nical and commercial documents without forewarning.
4
GENERAL RECOMMENDATIONS
This book contains important information for the:
Installer (section 1);
User (section 2);
Maintenance Technician (section 3).
• The user must carefully read the instructions in the specific section (section 2).
• The user must limit operations on the appliance only to those explicitly allowed in the specific section.
• Every operation carried out on the heat pump (e.g. set up, inspection, installation and commissioning), must mandatorily be
performed by authorised personnel alone and in possession of a technical engineering or professional degree qualifying them to
perform these tasks. They must also have attended a refresher course acknowledged by competent authorities. This particularly
applies to personal specialised in C.H. and air-conditioning systems and qualified electricians who, due to their specialised trai-
ning, skills and experience are experts in the correct installation and maintenance of C.H., cooling and air-conditioning sy-
stems.
• The appliance must be installed by qualified and professionally trained personnel.
• The instruction booklet is an integral and essential part of the product and must be given to the new user in the case of transfer or suc-
cession of ownership.
• It must be stored with care and consulted carefully, as all of the warnings provide important safety indications for installation, use and
maintenance stages.
• In compliance with the legislation in force, the systems must be designed by qualified professionals, within the dimensional limits
established by the Law. Installation and maintenance must be performed in compliance with the regulations in force, according to the
manufacturer's instructions and by professionally qualified staff, meaning staff with specific technical skills in the plant sector, as pro-
vided for by Law.
• Improper installation or assembly of the Immergas device and/or components, accessories, kits and devices can cause unexpected
problems for people, animals and objects. Read the instructions provided with the product carefully to ensure proper installation.
• This instructions manual provides technical information for installing Immergas products. As for the other issues related to the instal-
lation of products (e.g. safety at the workplace, environmental protection, accident prevention), it is necessary to comply with the pro-
visions of the standards in force and the principles of good practice.
• All Immergas products are protected with suitable transport packaging.
• The material must be stored in a dry place protected from the weather.
• Damaged products must not be installed.
• Maintenance must be carried out by skilled technical staff. For example, the Authorised Service Centre that represents a guarantee of
qualifications and professionalism.
• The appliance must only be destined for the use for which it has been expressly declared. Any other use will be considered improper and
therefore potentially dangerous.
• If errors occur during installation, operation and maintenance, due to non-compliance with technical laws in force, standards or in-
structions contained in this booklet (or however supplied by the manufacturer), the manufacturer is excluded from any contractual
and extra-contractual liability for any damages and the device warranty is invalidated.
• In the event of malfunctions, faults or incorrect operation, turn the appliance off and contact an authorised company (e.g. the Authori-
sed Technical Assistance Centre, which has specifically trained staff and original spare parts). Do not attempt to modify or repair the
appliance alone.
5
SAFETY SYMBOLS USED
GENERIC HAZARD
Strictly follow all of the indications next to the pictogram. Failure to follow the indications can generate hazard situations
resulting in possible harm to the health of the operator and user in general, and/or property damage.
ELECTRICAL HAZARD
Strictly follow all of the indications next to the pictogram. The symbol indicates the appliance’s electrical components or, in
this manual, identifies actions that can cause an electrical hazard.
WARNINGS
Strictly follow all of the indications next to the pictogram. Failure to follow the indications can generate hazard situations
resulting in possible minor injuries to the health of both the operator and the user in general, and/or slight material damage.
ATTENTION
Read and understand the instructions of the appliance before carrying out any operation, carefully following the in-
structions given. Failure to observe the instructions may result in malfunction of the unit.
INFORMATION
Indicates useful tips or additional information.
DISPOSAL WARNING
The user must not dispose of the appliance at the end of its service life as municipal waste, but send it to appropriate
collection centres.
SAFETY GLOVES
EYE PROTECTION
SAFETY FOOTWEAR
6
1 INSTALLING THE INDOOR UNIT Only a professionally enabled company is authorised to
install Immergas appliances.
1.1 DESCRIPTION OF THE PRODUCT.
The wall surface must be smooth, without any protru-
Magis Combo 4-6-9 V2 is a hybrid heat pump consisting of:
INSTALLER
sions or recesses enabling access to the rear part. They
- Magis Combo 4-6-9 V2 indoor unit;
are not designed to be installed on plinths or floors
- Audax Pro 4-6-9 V2 outdoor condensing unit.
(Fig. 1).
Magis Combo V2 is perfectly operational only if the two units are
correctly powered and interconnected.
The Magis Combo V2 indoor unit was designed solely for wall Installation must be carried out according to regulation
mounted installation for heating and air conditioning and to pro- standards, current legislation and in compliance with
duce domestic hot water for domestic use and similar purposes. local technical regulations and the required technical
In order to operate properly, it must be paired with an Audax Pro procedures.
V2 condensing unit; as such, all the provisions regarding the sa-
fety and use of both appliances must be respected.
It is forbidden to install appliances removed from other
systems.
1.2 INSTALLATION WARNINGS The manufacturer declines all liability in the event of
damage caused by appliances removed from other sy-
Operators who install and service the ap- stems or for any non-conformities with such equipment.
pliance must wear the personal protecti-
ve equipment required by applicable law.
USER
The place of installation of the appliance and relative
Immergas accessories must have suitable features (tech-
nical and structural), such as to allow for (always in safe,
efficient and comfortable conditions):
MAINTENANCE TECHNICIAN
- installation (according to the provisions of technical
legislation and technical regulations);
- maintenance operations (including scheduled, perio-
dic, routine and special maintenance);
- removal (to outdoors in the place for loading and tran-
sporting the appliances and components) as well as OK
the eventual replacement of those with appliances
and/or equivalent components. 1
7
The appliance operates with R32 refrige- Keep all flammable objects away from the appliance (pa-
rant gas. per, rags, plastic, polystyrene, etc.).
This gas is ODOURLESS.
Pay the utmost attention
INSTALLER
Strictly follow the instruction handbook Do not put household appliances under the indoor unit
of the UE Audax Pro outdoor unit before as they could be damaged if the safety valve trips or if the
installation and any type of operation on hydraulic fittings leak. Otherwise, the manufacturer
the chiller line. cannot be held liable for any damage to the household
appliances.
R32 refrigerant gas belongs to the low For the aforementioned reasons, we recommend not
flammability refrigerant category: class placing furnishings, furniture, etc. under the indoor
A2L according to standard ISO 817. It unit.
guarantees high performance with low
environmental impact. The new gas re- Any modification to the appliance that is not explicitly
duces the potential environmental im- indicated in this section of the booklet is forbidden.
pact by one third compared to R410A,
having less effect on global warning
(GWP 675). In the event of malfunctions, faults or incorrect opera-
USER
immediately.
Packing materials (staples, nails, plastic bags, polystyre-
ne foam, etc.) constitute a hazard and must be kept out of
the reach of children.
If the appliance is installed inside or between cabinets,
ensure sufficient space for routine servicing; for mini-
mum installation distances, see Fig. 3.
8
Installation standards
This indoor unit can be installed outdoors in a partially Installation is also forbidden in places/
protected area. rooms that constitute public areas of
A partially protected area is one in which the indoor unit apartment buildings such as cellars, en-
is not exposed to the direct action of the weather (rain, trance halls, attics, lofts, etc., unless
INSTALLER
snow, hail, etc.). otherwise provided for by local regula-
tions in force.
USER
Do not install on the vertical projection
of hobs.
MAINTENANCE TECHNICIAN
ls, etc.).
TECHNICAL DATA
9
They must be connected to a central heating system and
Pay attention not to generate sparks as
domestic hot water circuit suited to their performance
follows: and capacity.
– Do not remove the fuses while the unit
is on.
INSTALLER
The plugs (standard supply) are only to be used to fix the indoor Failure to comply with the above implies
unit to the wall; they only ensure adequate support if inserted cor- personal responsibility and invalidates
rectly (according to technical standards) in walls made of solid or the warranty.
semi-hollow brick or block. In the case of walls made from hollow
USER
10
1.3 MAIN DIMENSIONS
INSTALLER
Key (Fig. 2):
V - Electric connection
G - Gas supply
AC - Domestic hot water outlet
AF - Domestic hot water inlet
SC - Condensate drain (minimum internal
diameter Ø 13 mm)
R - System return
M - System flow
LP - Chiller line - liquid phase
GP - Chiller line - gaseous phase
USER
(mm) (mm) (mm)
787 440 400
CONNECTIONS
DOMESTIC
LINE
GAS HOT SYSTEM
CHILLER LINE
WATER
LP GP G AC - AF R-M
SAE 1/4” SAE 5/8” 3/4” 1/2” 3/4”
MAINTENANCE TECHNICIAN
2
D - 30 mm
E - 350 mm
11
1.5 ANTIFREEZE PROTECTION Indoor unit anti-freeze protection (both -5°C and -15°C) is only
ensured if:
Minimum temperature -5°C - indoor unit and outdoor unit are properly connected to each
The indoor unit comes standard with an anti-freeze function that other and to the electrical power supply circuits;
activates the outdoor unit when the temperature of the water insi- - the units are continuously powered;
INSTALLER
12
1.6 INDOOR UNIT CONNECTION UNIT 1.7 HYDRAULIC CONNECTION
- The hydraulic connection unit is standard supplied with Magis In order not to void the warranty, before making indoor
Combo V2. Make the hydraulic connection as shown below, unit connections, carefully clean the heating system (pi-
making sure to protect the system flow and return pipes with pes, radiators, etc.) with special pickling or de-scaling
their supplied insulating sheaths.
INSTALLER
products to remove any deposits that could jeopardise
- The R32 circuit wall connection unit is supplied as an extra kit. proper hydronic module operation.
Connect the circuit, following the instructions provided in the
outdoor unit instructions booklet.
USER
R M
AF
AC SC
V G
M
SC R
LP GP
MAINTENANCE TECHNICIAN
GP AF
G AC
LP
4 5
The hydraulic connection kit includes (Fig. 4): Key (Fig. 5):
2 - Adjustable expansion bolts V - Electric connection
2 - indoor unit support hooks G - Gas supply
1 - Gas supply pipe Ø 18 (G) AC - Domestic hot water outlet
1 - x 1/2” cold water inlet pipe (AF) AF - Domestic hot water inlet
1 - x 1/2” hot water infeed pipe (AC) SC - Condensate drain (minimum internal diameter Ø 13 mm)
1 - x 1/2” ball valve (AF) R - System return
1 - 3/4” system return pipe (R) M - System flow
1 - 3/4” system flow pipe (M) LP - Chiller line - liquid phase
1 - 3/4” ball valve (M) GP - Chiller line - gaseous phase
3 - Insulating sheath for system pipes (R - M)
1 - x 1/2” telescopic fitting (AC)
1 - x 3/4” telescopic fitting (R)
TECHNICAL DATA
13
3 bar safety valve Water connections must be made in a rational way using the cou-
The drain of the safety valve must always be properly conveyed to a plings on the indoor unit template.
draining funnel; consequently, in case of valve operation, the lea- The manufacturer declines all liability in the event of
ked fluid will end up in the sewer system. damage caused by the installation of an automatic filling
Condensate drain system.
INSTALLER
d
TECHNICAL DATA
c 1
a
1
1
1 2
b a
a
a
6
14
1.9 ELECTRICAL CONNECTION
If the power cable is damaged, contact a
qualified company (e.g. the Authorised
Disconnect power to the unit before ma- Technical Assistance Centre) for its re-
king any electrical connections. placement to avoid a hazard.
INSTALLER
The appliance has an IPX4D degree of protection; electrical safety
of the appliance is achieved only when it is properly connected to
The power cable must follow the prescribed route (Par. 1.7); avoi-
an efficient earthing system, as specified by current safety stan-
ding contact with the side of the frame.
dards.
If the fuses on the circuit boards need to be replaced, this must also
The manufacturer declines any responsibility for dama- be done by qualified personnel: use a F3.15A H250V fuse on the
ge or physical injury caused by failure to connect the in- P.C.B.
door unit to an efficient earthing system or failure to For the main power supply to the appliance, never use adapters,
comply with the IEC reference standards. multiple sockets or extension leads.
Make the various electrical connections according to your needs
Connection cables must respect the prearranged routes. (Fig. 7, 8):
Use 3 clips (c) (not supplied) to group the individual cables (max.
Outdoor unit electrical connection
1.5 mm2 into the lower terminal board.
The indoor unit must be coupled to an Audax Pro V2 outdoor unit
Use the specific fairleads (d) on the left side, making sure to put at
by connecting terminals F1 and F2 as shown in the wiring dia-
most 2 multi-polar cables (max 3 x 1 mm2) in each fairlead.
gram (Fig. 8). The Audax Pro V2 outdoor unit is powered at 230 V,
USER
The figure 6 shows cables in a hypothetical connection. To make
independently from the indoor unit.
the connections based on your own requirements, see the in-
Configure the indoor unit parameters as indicated in paragraph
structions below.
(Parag. 3.12).
Open the control panel connections compartment (Fig. 6).
Photovoltaic system installation
To carry out electrical connections, all you have to do is open the
Connecting the product to a photovoltaic system enhances use of
connections compartment as follows.
the outdoor unit when the photovoltaic panels are operating. Car-
1. Remove the front panel.
ry out the connection as indicated (Fig. 7).
2. Disassemble the cover.
3. Loosen the screws (a). Dehumidifiers
4. Remove the cover (b) from the control panel (c). Carry out the connection as indicated (Fig. 8). To complete the
MAINTENANCE TECHNICIAN
At this point, you can access the terminal board. connection operations, insert the 2-relay Board optional kit.
Also ensure that the electrical installation corresponds to maxi-
mum absorbed power specifications as shown on the indoor unit It is compulsory to set up separate lines
data-plate. with different power supply voltages,
Indoor units are supplied complete with a “Y” type power cable particularly it is essential to separate the
without plug. very low voltage connections from the
230 V ones.
The power supply cable must be con- No product pipes must ever be used to
nected to a 230V ±10% / 50Hz mains sup- earth the electric system or telephone li-
ply respecting L-N polarity and earth nes.
connection; this network must also have Ensure elimination of this risk before
a multi-pole circuit breaker with class III making the indoor unit electrical con-
overvoltage category in compliance with nections.
installation regulations.
The indoor unit can be electrically con-
To protect from possible dispersions of nected to outdoor units with very low vol-
DC voltage, it is necessary to provide a tage safety circuits (SELV)
TECHNICAL DATA
15
Low voltage electrical connection diagram.
INSTALLER
2 3
6
1
USER
1
MAINTENANCE TECHNICIAN
4
5
7
Terminal 87
0V Close Winter
230V Open Summer with cooling
A 3rd zone (mixed) can also be managed on the system by means The zone 3 dehumidifier, if any, will be managed by means of the
of the configurable relay interface kit (optional). configurable relay interface kit, which the zone 3 mixer will also
In this case, the zone 3 pump must be connected according to dia- be connected to.
gram (M10-3).
16
stalling 2-relay board (optional).
Electrical connection diagram (very low voltage).
8
Key (Fig. 8):
A13 - System manager (optional) A32-2 - Zone 2 remote panel (optional) S20-1 - Zone 1 room thermostat (optional)
A16-1 - Zone 1 dehumidifier (optional with dehumidifier A32-3 - Zone 3 remote panel (optional) S20-2 - Zone 2 room thermostat (optional)
management board) B3-2 - Zone 2 flow probe (optional) S20-3 - Zone 3 room thermostat (optional)
17
Remove jumper X40-1 before the electrical connection of the
TECHNICAL DATA MAINTENANCE TECHNICIAN USER INSTALLER
1.10 ROOM CHRONO-THERMOSTATS 1.11 MODBUS TEMPERATURE AND
(OPTIONAL) HUMIDITY ROOM PROBES (OPTIONAL)
The indoor unit is prepared for the application of room chro- The temperature and humidity probe is used to detect room hu-
no-thermostats or remote controls, which are available as optio- midity and to calculate the relative dew point by regulating the
nal kits (Fig. 9). flow temperature during the cooling phase.
INSTALLER
A maximum of 3 temperature controllers can be applied directly Connect the appliance as shown (Fig. 8).
to the appliance.
DIP-Switch configuration table
All Immergas chrono-thermostats are connected with 2 wires
only.
Carefully read the user and assembly instructions contained in
DIP 1-5 DIP 6-7 DIP 8
the accessory kit. ON
Carry out the connection as indicated (Fig. 8).
batteries.
On/Off chrono-thermostat electrical connection (Optional). ON
Zone 3
The operations described below must be (Address
performed after having removed the vol- 133)
tage from the appliance. 1 2 3 4 5
ON
TECHNICAL DATA
DIP 8
9600 bit/s
(Speed)
18
1.12 REMOTE ZONE CONTROL (OPTIONAL) 1.15 EXTERNAL TEMPERATURE PROBE
This remote device is used to adjust the setpoints and to view the
(OPTIONAL)
main information of the zone where it was configured. In the outdoor unit there is an external probe as standard.
Connect as shown (Fig. 8); This can be used as an external probe of the heat pump.
To correctly configure the device, set the parameters as described If the outdoor unit is positioned in an area that is not suitable for
INSTALLER
below: temperature reading, it is advisable to use an additional external
probe (Fig. 10) which is available as an optional kit.
Refer to the relative instruction sheet for positioning of the exter-
Assistance Menu -> Device configuration
nal probe.
Zone 1 = 41 For the proper operation of the optional probe it must be con-
Slave address: Address to configure according to
Zone 2 = 42 nected where envisaged (Fig. 8) and then it must be enabled (Pa-
the zone where the device is installed
Zone 3 = 43 rag. 3.12).
Baud Rate 9600
Parity bit Even Once the probe is enabled, switch the ap-
Stop bits 1 pliance off and back on.
Heat pump control NO
For correct operation it is necessary to install the jumper The presence of the external probe allows the system flow tempe-
on the thermostat of the zone associated to the panel. rature to be set automatically based on the outdoor temperature in
If necessary, this jumper can be replaced with a safety order to adapt the heating or cooling provided to the system.
thermostat. The system flow temperature is determined by the setting on the
USER
“Heat regulation” menu and by the “User” menu for the offset va-
lues based on the curves shown in the diagram (Parag. 1.16).
If the system is divided into two or three zones, the flow
temperature is calculated based on the zone with the hi-
gher temperature in central heating mode and with the
lower temperature in cooling mode.
99
MAINTENANCE TECHNICIAN
trol panel (Fig. 8).
128 37
9
45
19
1.16 TEMPERATURE CONTROL SETTING The curves (Fig. 11, 13, 12, 14, 15, 16) show the default settings in
the various operating modes available both with external probe
By setting the parameters in the “Heat regulation” menu, you can
and without.
adjust how the system operates.
INSTALLER
R04
U03 (U16)
R08
(R23) U04
R05 R09
USER
(R24)
(U17)
U05 U06
R13 (R28)
R17
R16
(R27)
R12
Key (Fig. 11,12,13,14) U 05 - Offset value compared to the curve set by the external probe
Rxx - “Temperature control” menu parameter on cooling zone 1
TE - External temperature U 06 - Offset value compared to the curve set by the external probe
TECHNICAL DATA
20
Flow temperature in central heating mode 1.17 IMMERGAS FLUE SYSTEMS
without external probe Immergas supplies various solutions separately from the indoor
units regarding the installation of air intake terminals and flue
exhaust, which are fundamental for indoor unit operation.
INSTALLER
The indoor unit must be installed with an original Im-
mergas “Green Range” inspectionable air intake system
Z1 and flue gas extraction system made of plastic, with the
1 exception of configuration C6, as required by the regula-
tions in force and by the product’s approval. This flue can
be identified by an identification mark and special di-
stinctive marking bearing the note "only for condensa-
Z2 (Z3) tion boilers".
U01
(U14) For non-original flue system, refer to the technical data
of the appliance.
15
Flow temperature in cooling mode The plastic pipes cannot be installed outdoors, for tracts
without external probe longer than 40 cm, without suitable protection from UV
rays and other atmospheric agents.
USER
Resistance factors and equivalent lengths
Each flue component has a Resistance Factor based on experimen-
tal tests and specified in the table below.
Z2 (Z3) The Resistance Factor for individual components is independent
U02
(U15) from the type of boiler on which it is installed and has a dimen-
sionless size.
It is however, conditioned by the temperature of the fluids that
Z1 pass through the pipe and therefore, varies according to applica-
2
tions for air intake or flue exhaust.
MAINTENANCE TECHNICIAN
16 Each single component has a resistance corresponding to a cer-
tain length in metres of pipe of the same diameter; the so-called
Key (Fig. 15,16) equivalent length, can be obtained from the ratio between the re-
1 - Central Heating Set lative Resistance Factors.
2 - Cooling Set All indoor units have an experimentally obtainable maximum
TE - External temperature Resistance Factor equal to 100.
TM - Flow temperature
U 01 - Zone 2 flow temperature in "User" menu central heating
mode
U 02 - Zone 2 flow temperature in "User" menu cooling mode
U 14 - Zone 3 flow temperature in "User" menu central heating
mode
U 15 - Zone 3 flow temperature in "User" menu cooling mode
Zx - Heating system zone
TECHNICAL DATA
21
The maximum Resistance Factor allowed corresponds to the resi-
stance encountered with the maximum allowed pipe length for For safety purposes, do not obstruct the
each type of Terminal Kit. indoor unit’s intake/exhaust terminal,
This information allows calculations to be made to verify the pos- not even temporarily
sibility of setting up various flue configurations. The various parts of the flue system must
INSTALLER
B
17
every 3 metres.
- gasket (B) without notches, to use for extensions.
If necessary, to ease the push-fitting, spread the elements with
commonly-used talc. Installation inside the recessed frame
Extension pipes and concentric elbows push-fittings. In this mode, install the flue according to your needs using the ap-
To install push-fitting extensions with other elements of the flue, propriate pre-sections in the frame to exit from its clearances.
proceed as follows:
- Install the concentric pipe or elbow with the male side (smooth)
on the female side (with lip seal) to the end stop on the previou-
sly installed element in order to ensure sealing efficiency of the
MAINTENANCE TECHNICIAN
coupling.
If the exhaust terminal and/or extension concentric pipe
needs shortening, consider that the internal duct must
always protrude by 5 mm with respect to the external
duct.
TECHNICAL DATA
22
1.18 TABLES OF RESISTANCE FACTORS AND EQUIVALENT LENGTHS OF “GREEN RANGE” FLUE
SYSTEM COMPONENTS
Equivalent
INSTALLER
Resistance
length
TYPE OF DUCT factor
in m of concentric
(R)
pipe Ø 80/125
USER
90° concentric bend Ø 80/125 with inspection 3,4 1,6
MAINTENANCE TECHNICIAN
TECHNICAL DATA
23
Equivalent Equivalent
Resistance Equivalent Equivalent
length in m length in m
TYPE OF DUCT factor length in m length in m
of concentric pipe of concentric pipe
(R) of pipe Ø 80 of pipe Ø 60
Ø 60/100 Ø 80/125
Concentric pipe Intake m 6.4 Intake m 7.3
INSTALLER
terminal Ø 80 m 1
Intake terminal Intake m 2.2 m 0,35 Intake m 2.5 m1
Ø 80
Exhaust m 0.6
Exhaust terminal Exhaust m 1.9 m 0,3 Exhaust m 1.6 m 0,9
Ø 80
Intake m 1.9 m 0,3 Intake m 2.2 m 0,9
90° bend Ø 80 Exhaust m 0.8
Exhaust m 2.6 m 0,4 Exhaust m 2.1 m 1,2
Intake m 1.2 m 0,2 Intake m 1.4 m 0,5
45° bend Ø 80 Exhaust m 0.5
Exhaust m 1.6 m 0,25 Exhaust m 1.3 m 0,7
Pipe Ø 60 m 1 for Intake m 3.8
Exhaust m 3.3 m 0,5 Exhaust m 1.0 m 1,5
ducting Exhaust m 2.7
90° bend Ø 60 for Intake m 4.0
Exhaust m 3.5 m 0,55 Exhaust m 1.1 m 1,6
ducting Exhaust m 2.9
Intake m 2.6 Intake m 3
Reduction Ø 80/60 m 0,4 Exhaust m 0.8 m 1,2
Exhaust m 2.6 Exhaust m 2.1
Terminal complete Intake m 14
with vertical
Exhaust m 12.2 m 1,9 Exhaust m 3.7 m 5,8
TECHNICAL DATA
24
1.19 OUTDOOR INSTALLATION IN Max. length of exhaust duct.
PARTIALLY PROTECTED AREA The flue pipe (both vertical or horizontal) can be extended to a
max. length of 30 linear metres.
A partially protected area is one in which the appliance
Coupling of extension pipes.
is not exposed to the direct action of the weather (rain,
To install push-fitting extensions with other elements of the flue,
INSTALLER
snow, hail, etc.).
proceed as follows: Couple the pipe or elbow with the male side
(smooth) in the female side (with lip seal) to the end stop on the
If the appliance is installed in a place where the ambient previously installed element. This will ensure sealing efficiency of
temperature drops below -5°C, use the optional antifre- the coupling.
eze kit, checking the ambient operating temperature
Configuration without cover kit in a partially protected
range shown in the technical data table in this in-
location (type C boiler).
struction booklet.
By leaving the side plugs fitted it is possible to install the appliance
externally without the cover kit.
Installation takes place using the Ø 60/100 and Ø 80/125 concen-
Configuration type B, open chamber and fan assisted (B23 or tric intake/ exhaust kits. Refer to the paragraph on indoor instal-
B53). lation.
Using the relevant cover kit, direct air intake is possible and flue In this configuration the upper cover kit guarantees additional
gas is exhausted into a single flue or directly to the outside. In this protection for the boiler. It is recommended but not compulsory.
configuration it is possible to install the indoor unit in a partially The Ø 80/80 separating device cannot be used in this configura-
protected place. In this configuration the indoor unit is classified tion (coupled with the cover kit).
as type B.
USER
With this configuration:
- air intake takes place directly from the environment in which
the appliance is installed (external);
- the flue gas exhaust must be connected to its own single chim-
ney (B23) or ducted directly outside via a vertical terminal for
direct exhaust (B53) or via an Immergas ducting system (B53).
The technical regulations in force must be respected.
Cover kit assembly (Fig. 18).
Remove the two plugs from the two lateral holes.
MAINTENANCE TECHNICIAN
Install the Ø 80 outlet flange on the central hole of the boiler, ta-
king care to insert the gasket supplied with the kit and tighten by
means of the screws provided.
Install the upper cover, fixing it using the 4 screws present in the
kit, positioning the relevant gaskets. 18
Engage the 90° Ø 80 bend with the male end (smooth) in the fema-
le end (with lip seal) of the Ø 80 flange unit to the end stop. Intro-
duce the gasket, making it run along the bend. Fix it using the me-
tal sheet plate and tighten by means of the clips present in the kit,
making sure to block the 4 gasket flaps.
Fit the male end (smooth) of the exhaust pipe into the female end
of the 90° Ø 80 bend, making sure that the relevant wall sealing
plate is already fitted; this will ensure hold and joining of the ele-
ments making up the kit.
TECHNICAL DATA
25
INSTALLER
USER
19
MAINTENANCE TECHNICIAN
20
26
1.20 CONCENTRIC HORIZONTAL KIT Mounting the horizontal intake-exhaust kit Ø 60/100 (Fig. 21)
INSTALLATION 1. Install the curve with flange (2) on the central hole of the indo-
or unit, positioning gasket (1) with the circular projections
Type C configuration, sealed chamber and fan assisted downwards in contact with the indoor unit flange, and tighten
The position of the terminal (in terms of distances from openings, using the screws contained in the kit.
INSTALLER
overlooking buildings, floor, etc.) must be in compliance with the 2. Fit the Ø 60/100 (3) concentric terminal pipe with the male
regulations in force. side (smooth) to the female side of the bend (2) up to the end
This terminal is connected directly to the outside of the building stop, making sure that the internal and external wall sealing
for air intake and flue gas exhaust. plates have been fitted; this will ensure sealing and joining of
The horizontal kit can be installed with the rear, right side, left side the elements making up the kit.
or front outlet.
For installation with frontal outlet, one must use the fixing plate C13
and a concentric bend coupling in order to ensure sufficient space
to carry out the tests required by law upon commissioning.
External grid
Both the Ø 60/100 and Ø 80/125 intake/exhaust terminal, if pro- 2
perly installed, is pleasant to look at on the outside of the building.
Make sure that the external silicone wall sealing plate is properly 1 3
inserted in the wall. 4
5
For correct functioning of the system the terminal with
grid must be installed correctly ensuring that, the "high"
USER
indication present on the terminal is respected on in- 21
stallation.
The kit includes (Fig. 21):
No.1 Gasket (1)
No.1 Concentric bend Ø 60/100 (2)
No.1 Int./exhaust concentric terminal Ø 60/100 (3)
No.1 Internal wall sealing plate (4)
No.1 External wall sealing plate (5)
Extensions for Ø 60/100 horizontal kit. Kit assembly (Fig. 22)
This configuration corresponds to a resistance factor of 100.
MAINTENANCE TECHNICIAN
The kit with this configuration can be extended up to a max. hori-
zontal length of 12.9 m including the terminal with grid and
excluding the concentric bend leaving the indoor unit; this confi-
guration offers a resistance factor of 100. In this case specific ex-
tensions must be requested.
In this case the special extensions must be requested.
Immergas also provides a Ø 60/100 simplified terminal, which in
combination with its extension kits allows you to reach a maxi-
mum extension of 11.9 metres.
C13
TECHNICAL DATA
22
27
Mounting the horizontal intake-exhaust kit Ø 80/125 (Fig. 23) Extensions for Ø 80/125 horizontal kit. Kit assembly (Fig. 24)
To install the kit Ø 80/125 one must use the flanged adapter kit in The kit with this configuration can be extended up to a max. len-
order to install the flue system Ø 80/125. gth of 32 m, including the terminal with grid and excluding the
1. Install the flanged adaptor (2) on the central hole of the indoor concentric bend leaving the indoor unit.
unit, positioning gasket (1) with the circular projections If additional components are assembled, the length equivalent to
INSTALLER
downwards in contact with the indoor unit flange, and tighten the maximum allowed must be subtracted.
using the screws contained in the kit. In this case the special extensions must be requested.
2. Engage the bend (3) with the male side (smooth) to the end stop
on the adapter (1). C13
3. Fit the Ø 80/125 (5) concentric terminal pipe with the male
side (smooth) to the female side of the bend (4) (with lip seals)
up to the end stop, making sure that the internal (6) and exter-
nal wall sealing plates (7) have been fitted; this will ensure sea-
ling and joining of the elements making up the kit.
C13
24
3
USER
2 4
5 1.21 CONCENTRIC VERTICAL KIT
6 INSTALLATION
1
The Kit Ø 80/125 includes (Fig. 23): prox. 25°) and the height between the terminal cap and
No.1 Concentric bend Ø 80/125 at 87° (3) half-shell (374 mm for Ø 60/100 and 260 mm for
No.1 Int./exhaust concentric terminal Ø 80/125 (4) Ø 80/125) must always be observed.
No.1 Internal wall sealing plate (5)
No.1 External wall sealing plate (6) Mounting the vertical kit with aluminium tile Ø 60/100
The remaining kit components must not be used (Fig. 25)
1. Install the concentric flange (2) on the central hole of the indo-
or unit, positioning gasket (1) with the circular projections
downwards in contact with the indoor unit flange.
2. Tighten the concentric flange with the screws in the kit.
3. Replace the tiles with the aluminium sheet (4), shaping it to
ensure that rainwater runs off.
4. Position the fixed half-shell (6) on the aluminium tile.
5. Insert the intake-exhaust pipe (5).
6. Fit the Ø 60/100 concentric terminal pipe with the male side
(5) (smooth) into the flange (2) up to the end stop, making sure
that the wall sealing plate has been fitted (3); this will ensure
sealing and joining of the elements making up the kit.
TECHNICAL DATA
28
C33 Mounting the vertical kit with aluminium tile Ø 80/125
(Fig. 27)
To install the kit Ø 80/125 one must use the flanged
adapter kit in order to install the flue system Ø 80/125.
INSTALLER
5
7
1. Install the concentric flange (2) on the central hole of the indo-
4 6 or unit, positioning gasket (1) with the circular projections
downwards in contact with the indoor unit flange.
2. Tighten the concentric flange with the screws in the kit.
3. Replace the tiles with the aluminium sheet (4), shaping it to
ensure that rainwater runs off.
4. Position the fixed half-shell (5) on the aluminium tile;
3 5. Insert the intake-exhaust terminal (7);
6. Fit the Ø 80/125 concentric terminal pipe with the male side
(smooth) to the female side of the adapter (1) (with lip seals) up
2
to the end stop, making sure that the wall sealing plate (3) has
been fitted; this will ensure sealing and joining of the elements
1
making up the kit.
25 C33
USER
The kit includes (Fig. 25):
No.1 Gasket (1)
7
No.1 Female concentric flange (2)
No.1 Wall sealing plate (3) 6
No.1 Aluminium tile (4)
No.1 Intake/exhaust concentric pipe Ø 60/100 (5) 5
No.1 Fixed half-shell (6)
No.1 Mobile half-shell (7) 4
Extensions for Ø 60/100 vertical kit (Fig. 26)
MAINTENANCE TECHNICIAN
The kit with this configuration can be extended up to a max. verti-
cal straight length of 14.4 m including the terminal. This configu-
ration corresponds to a resistance factor of 100. In this case speci- 3
fic extensions must be requested.
2
C33
1
27
26
29
Extensions for Ø 80/125 vertical kit (Fig. 28) 6. Fit the intake terminal (6) with the male side (smooth) in the
The kit with this configuration can be extended to a max. straight female side of the bend (5) up to the end stop, ensuring that the
vertical length of 32 m, including the terminal. If additional com- internal and external wall sealing plates are fitted
ponents are assembled, the length equivalent to the maximum al- 7. Fit the exhaust pipe (9) with the male end (smooth) to the fe-
lowed must be subtracted. In this case the special extensions must male end of the bend (5) up to the end stop; making sure that
INSTALLER
be requested. the internal wall sealing plate has been fitted, this will ensure
sealing and joining of the elements making up the kit.
C33
C53* - C83
5 5 6
7
8
7 S
9
4 A
3
1 2
29
The kit includes (Fig. 29):
No.1 Exhaust gasket (1)
USER
exhaust to exit from the chimney, flue or intubated duct through “green range” roof discharge terminal.
divided flue exhaust and air intake pipes. The configuration on walls opposite the building is not allowed.
Combustion products are expelled from pipe (S) (in plastic, so as
to resist acid condensate). Installation clearances (Fig. 30)
Air is taken in through duct (A) for combustion (this is also in pla- The minimum installation clearance measurements of the Ø
stic). 80/80 separator terminal kit have been stated in some limit condi-
The intake pipe (A) can be installed either on the right or left hand tions.
side of the central exhaust pipe (S).
C 43
Both ducts can be routed in any direction.
Mounting the separator kit Ø 80/80 (Fig. 29):
1. Install the flange (4) on the central hole of the indoor unit, po-
sitioning gasket (1) with the circular projections downwards
in contact with the indoor unit flange.
2. Tighten with the hexagonal head and flat point screws provi-
ded in the kit.
3. Replace the flat flange present in the lateral hole with respect to
the central one (according to needs) with the flange (3), posi-
tioning the gasket (2) already present in the indoor unit in
TECHNICAL DATA
between.
4. Tighten with the supplied self-tapping screws with drill bit.
5. Fit the bends with male side (smooth) (5) in the female side of
the flanges (3 and 4).
30
30
Extensions for separator kit Ø 80/80 Mounting the C9 adapter kit (Fig. 33)
The maximum vertical straight length (without bends) that can be (Version Ø 125 only) before assembly check the gaskets
used for Ø 80 intake and exhaust pipes is 41 metres, regardless are in the right position.
from whether they are used for intake or exhaust. In the event component lubrication (already carried out
The maximum horizontal straight length (with bend in suction by the manufacturer) is not sufficient, remove the resi-
INSTALLER
and in exhaust) that can be used for Ø 80 intake and exhaust pipes dual lubricant using a dry cloth, then to ease fitting coat
is 36 metres, regardless from whether they are used for intake or the parts with common or industrial talc.
exhaust.
Please note the type of installation C43 must be done with a natural
draught flue.
To favour the removal of possible condensate forming in
To favour the removal of possible condensate forming in
the exhaust pipe, tilt the pipes towards the indoor unit
the exhaust pipe, tilt the pipes towards the indoor unit
with a minimum slope of 1.5% (Fig. 31)
with a minimum slope of 1.5% (Fig. 31)
USER
4. Calculate the distances between the indoor unit drain and the
System composition
bend of the ducting system.
The system must be combined with the following components
5. Prepare the boiler flue system, making sure that the internal
(sold separately) to be functional and complete:
pipe of the concentric kit is fitted up to the end stop in the
- kit C93 Ø 100 or Ø 125 version;
ducting system curve (Height "X" Fig. 34), whereas the exter-
- rigid ducting Ø 60 and Ø 80 and flexible Ø 50 and Ø 80 kit;
nal pipe must reach the end stop of the adapter (1).
- flue exhaust kit Ø 60/100 or Ø 80/125 configured according to
6. Mount the cover (A) complete with adaptor (1) and caps (6) on
the installation and type of indoor unit.
the wall.
7. Assemble the flue system to the ducting system.
Once all components have been assembled properly, the exhaust
MAINTENANCE TECHNICIAN
fumes will be expelled via the ducting system; the combustion air
for normal indoor unit operation will be aspirated directly by the
shaft (Fig. 34).
S A
31
31
Technical data
The dimensions of the shafts must ensure a minimum gap betwe-
en the outer wall of the smoke duct and the inner wall of the shaft:
30 mm for circular section shafts and 20 mm in the event of a
square section shaft (Fig. 32).
INSTALLER
C93
1 2
A X
12 3 9
MAINTENANCE TECHNICIAN
8
3 6
6 7
4 5
11
10
33
32
1.24 DUCTING OF FLUES OR TECHNICAL You can also install an additional Ø 50 flexible ducting
SLOTS system the specifications of which are found on the rele-
Ducting is an operation through which, via the introduction of vant instructions sheet inside the kit.
one or more relevant pipes, one achieves a system for the evacua-
tion of the combustion products of a gas appliance, made up from
INSTALLER
the coupling of an existing or new ducting pipe with a chimney,
C53
flue or technical slot (also in new buildings) (Fig. 35).
Ducting requires ducts declared to be suitable for the purpose by
the manufacturer, following the installation and user in-
structions, provided by the manufacturer and the requirements of
the regulations in force.
Immergas ducting systems
The Ø 60 rigid, Ø 50 and Ø 80 flexible and Ø 80 rigid
“Green Range” ducting systems must only be used for
domestic use and with Immergas condensing boilers.
USER
end of work and on commissioning of the ducted system.
The instructions in the project or technical report must likewise
be followed, in cases provided for by the standard and current te-
chnical regulations.
To guarantee reliability and operation over time of the ducting
system, make sure:
- it is used in average atmospheric and environmental condi-
tions, according to current regulations (absence of combustion 35
products, dusts or gases that can alter the normal thermophysi-
cal or chemical conditions; existence of temperatures coming
MAINTENANCE TECHNICIAN
within the standard range of daily variation, etc.).
- Installation and maintenance must be performed according to 1.25 CONFIGURATION TYPE B, OPEN
the indications supplied by the manufacturer included with the CHAMBER AND FAN ASSISTED FOR
“green range” ducting system chosen and in compliance with INDOORS
the regulations in force.
The appliance can be installed inside buildings in B23 or B53 mode;
- The maximum length specified by the manufacturer must be
in this case, all technical rules and national and local regulations
respected; in this regard:
in force, must be complied with.
• The max. possible length of the Ø 60 rigid ducting vertical
For installation, the cover kit must be used, referred to in
section is equal to 22 m. This length is obtained considering
(Par. 1.19).
the complete Ø 80 exhaust terminal, 1 m of Ø 80 pipe in
exhaust, two 90° Ø 80 bends at indoor unit outlet.
• The max. possible length of the Ø 80 flexible ducting vertical
section is equal to 18 m. This length is obtained considering
the Ø 80 complete exhaust terminal, 1 m of Ø 80 pipe in
exhaust, two 90° Ø 80 bends at indoor unit outlet for con-
necting to the ducting system and two direction changes of
the flexible hose inside the chimney/technical slot.
• The max. possible length of the Ø 80 rigid ducting vertical
TECHNICAL DATA
33
1.26 FLUE EXHAUST TO FLUE/CHIMNEY. 1.27 FLUES, CHIMNEYS AND CHIMNEY CAPS.
Flue exhaust does not necessarily have to be connected to a bran- The flues, chimneys and chimney caps for the evacuation of com-
ched type traditional flue for type B appliances with natural drau- bustion products must be in compliance with applicable stan-
ght (CCR). dards.
The flue exhaust, for indoor units installed in C configuration, can Chimneys and roof-installed exhaust terminals must comply
INSTALLER
be connected to a special LAS type multiple flue. with the outlet height and with the distance from technical volu-
For B23 configurations, exhaust is only allowed into individual mes set forth by the technical standards in force.
chimney or directly into the external atmosphere via a relevant
terminal, unless otherwise provided by local regulations.
The multiple flues and the combined flues must also only be con-
nected to type C appliances of the same type (condensation), ha-
ving nominal heat inputs that do not differ by more than 30% less
with respect to the maximum that can be attached and powered by
the same fuel.
The thermo-fluid dynamic features (flue flow rate, % of carbon
dioxide, % humidity etc.) of the appliances attached to the same
multiple flues or combined flues, must not differ by more than 10%
with respect to the average indoor unit attached.
Multiple and combined flues must be specially designed accor-
ding to the calculation method and requirements of the standards
(such as UNI 13384), by professionally qualified technical staff.
USER
36
34
1.28 WATER TREATMENT PLANT FILLING
As already mentioned in the previous paragraphs, a treatment of
the thermal and domestic system water is required, in compliance
with the local standards in force.
The parameters that influence the duration and proper operation Y
INSTALLER
of the heat exchanger are the water's PH, total hardness, conducti-
vity, and oxygen, together with the system's processing residues
(any welding residues), any oil present and corrosion products
that can, in turn, cause damage to the heat exchanger.
In order to prevent this from happening, you are recommended
to: X
37
- clean the system with clean water to eliminate solid residues
before installation on new and old systems;
- clean the system with a chemical treatment: Key (Fig. 37):
X - Total water hardness °F
• clean the new system with a suitable cleaning device (for
Y - Litres of system water
example Sentinel X300, Fernox Cleaner F3 or Jenaqua 300)
combined with thorough washing; The graph refers to the entire life cycle of the system. The-
• clean the old system with a suitable cleaning device (for refore, also consider scheduled and unscheduled main-
example Sentinel X400 or X800, Fernox Cleaner F3 or Jena- tenance, which involves emptying and filling the said
qua 400) combined with thorough washing; system.
- Check the maximum total hardness and quantity of filling wa-
USER
ter referring to the graphics (Fig. 37); if the contents and hard-
ness of the water are below the indicated curve, no specific treat-
ment is required; otherwise, to limit the content of calcium
carbonate, you must provide for water-filling treatment.
- If it is necessary to provide for water treatment, it should be done
through complete desalination of the filling water. As opposed
to the complete softening process, desalinating the water com-
pletely not only removes hardening agents (Ca, Mg), but also
eliminates all other minerals to reduce water-filling conductivi-
ty up to 10 microsiemens/cm. Given its low conductivity, desali-
MAINTENANCE TECHNICIAN
nated water does not only prevent the formation of lime scale,
but also serves as protection against corrosion.
- Insert a suitable inhibitor / passivator (for example Sentinel
X100, Fernox Protector F1, or Jenaqua 100); if required, also in-
sert appropriate antifreeze (such as for example Sentinel X500,
Fernox Alphi 11 or Jenaqua 500).
- Check electrical conduction of the water, which should be hi-
gher than 2000 μs/cm in the case of treated water and lower than
600 μs/cm in the case of non-treated water.
- To prevent corrosion, the water system's PH should be between
7.5 and 9.5.
- Check the maximum content of chlorides, which should be less
than 250 mg/l.
For quantities and methods of use of water-treatment
products, refer to the instructions provided by their ma-
nufacturer.
TECHNICAL DATA
35
1.29 SYSTEM FILLING 1.31 GAS SYSTEM START-UP.
Once the indoor unit is connected, fill the system using the filling To start up the system, refer to the technical standards in force.
cock (Fig. 42). This divides the systems and, therefore, the commissioning ope-
Filling must be done slowly to allow the air bubbles in the water to rations, into three categories: new systems, modified systems, re-
escape through the vents in the indoor unit and the heating and activated systems.
INSTALLER
To this end, the minimum amount of water to guarantee is 30 li- operating limits in cooling mode
tres for any type of system and in any operating mode.
39
TE = External temperature
TM = Flow temperature
36
1.33 COMMISSIONING THE INDOOR UNIT
(IGNITION, ONLY WHEN PAIRED WITH After installation, check for leaks. Toxic
AN OUTDOOR UNIT) gas could be generated if the unit comes
into contact with a source of ignition,
To commission the indoor unit (the operations listed below must such as thermal fan, stove and cylinders.
only be performed by qualified personnel and in the presence of
INSTALLER
Make sure that only refrigerant recovery
staff only): cylinders are used.
1. check that the internal system is properly sealed according to
the specifications set forth by regulations in force;
2. Make sure that the type of gas used corresponds to indoor unit
settings;
3. check that there are no external factors that may cause the for-
mation of fuel pockets;
4. Check that the gas flow rate and the relative pressure values
comply with those indicated in the booklet;
5. Switch the indoor unit on and check correct ignition;
6. ensure that the safety device intervenes in the event of gas sup-
ply failure and check the relative intervention time;
7. check connection to a 230V-50Hz power mains, correct L-N
polarity and the earthing connection;
8. Check the intervention of the main switch located upstream
from the indoor unit and in the indoor unit.
USER
9. check that the intake/exhaust terminals are not obstructed
and that they are installed properly;
The system must not be started up if even only one of the
checks should be negative.
MAINTENANCE TECHNICIAN
TECHNICAL DATA
37
1.34 CIRCULATION PUMP Pump LED.
The LED flashes green when the pump is powered and the pwm
The indoor unit is supplied with two circulator pumps, one for the
control signal is connected.
heat generator and another for the heat pump mode.
Circulator pumps run at variable speeds and operate as follows: The LED lights up steady green when the pump is powe-
- Fixed ("A 05" = 0): The heat circulator pump speed is fixed and red and the signal cable disconnected. In these condi-
INSTALLER
corresponds to parameter "A 04". The heat generator circulator tions the pump works at maximum and without control.
pump speed is fixed and corresponds to parameter "A 19".
- ΔT constant ("A 05" = 5 K): the heat circulator pump speed va- If the pump detects an alarm, the LED switches from green to red;
ries to maintain ΔT = 5 K constant between the system flow and this can mean one of the following failures:
return. Also, you can adjust the pump operating range, by set- - low supply voltage;
ting the maximum speed “A 04” and the minimum speed “A 03”. - rotor seized;
The heat generator circulator pump speed varies to maintain ΔT - electrical error.
= "A 05" constant between the system flow and return. Also, you For a detailed description of the meaning of the red LED, refer to
can adjust the pump operating range, by setting the maximum (Parag. 3.12).
speed “A 19” and the minimum speed “A 18”. The LED, in addition to being green or red, can also re-
For proper system operation, make sure that the mini- main off.
mum flow rate in operating conditions never drops be- It is normal for the LED to be off when the pump is not
low 500 l/h. powered, whereas with the pump powered, the LED
must be lit: if switched off, it means there is a fault.
USER
Pump release.
If after a long period of inactivity, the circulator is blocked, adjust
the screw in the centre of the head in order to manually release the
motor shaft.
Take great care during this operation to avoid damage to the mo-
tor.
80 80
70 70
60 60
1
50 50
A B
Y1 40 40 Y2
30 30
20 20
10 2 10
TECHNICAL DATA
0 0
0 200 400 600 800 1000 1200 1400 1600
X1
40
Key (Fig. 40): 1 = Maximum speed (100%) A = Head available to the system
X1 = Flow rate (l/h) 2 = Minimum speed (70%) B = Power absorbed by the circulator
Y1 = Head (kPa) pump (dotted area)
Y2 = Circulator pump absorbed power
(W)
38
Head available to system (Heat pump circuit)
80 80
INSTALLER
70 70
1
60 60
A B
50 50
Y1 40 40 Y2
30 30
20 20
10 10
USER
0
2
0
0 200 400 600 800 1000 1200 1400 1600 1800 2000
X1
41
MAINTENANCE TECHNICIAN
Key (Fig. 41): 1.35 KITS AVAILABLE ON REQUEST
X1 = Flow rate (l/h)
- 2 zone kit (1 direct and 1 mixed). Should it be necessary, you can
Y1 = Head (kPa)
install the zone kit, which allows you to divide the heating sy-
Y2 = Circulator pump absorbed power (W)
stem into two separate zones - one direct and one mixed.
- Configurable relay interface kit. The module is set up for a relay
1 = Maximum speed (100%)
board, which amplifies the appliance features and, thus, the
2 = Minimum speed (45%)
operating possibilities.
- 2-relay board kit. The hydronic module can manage up to two
A = Head available to the system
dehumidifiers. A 2 relay board that manages dehumidifier
B = Power absorbed by the circulator pump (dotted area)
enabling is available to pair the appliances.
- R32 circuit connection kit. For R32 circuit wall connections,
there is a kit with the two pipes necessary to create the circuit.
The above-mentioned kits are supplied complete with
instructions for assembly and use.
TECHNICAL DATA
39
1.36 MAIN COMPONENTS
9 10 37 38
INSTALLER
11
12
13
36
7
14
15
6 16
35
17
USER
5 18 34
19 39
4
20
3
21
22
2
23
1
MAINTENANCE TECHNICIAN
24
33 32 31 30 29 28 27 26 25 40
42
40
2 INSTRUCTIONS FOR USE AND
MAINTENANCE
Do not take apart or tamper with the intake and exhaust
pipes.
2.1 GENERAL RECOMMENDATIONS Only use the user interface devices listed in this section
INSTALLER
of the booklet.
Never expose the indoor unit to direct va-
pours from a hob.
Do not climb on the appliance, do not use
the appliance as a support base.
The device can be used by children at least 8 years old as
well as by persons with reduced physical, sensory or
mental capabilities, or lack of experience or required
knowledge, provided that they are under surveillance, The use of components involving use of
or after they have been instructed relating to the safe use electrical power requires some funda-
and have understood the potential dangers. mental rules to be observed such as:
Children must not play with the appliance.
Cleaning and maintenance destined to be performed by
– do not touch the appliance with wet or
the user can not be carried out by unsupervised chil- moist parts of the body; do not touch
dren. when barefoot;
– never pull electrical cables or leave the
appliance exposed to atmospheric
USER
agents (rain, sunlight, etc.);
For safety purposes, check that the air in- – the appliance power cable must not be
take/flue exhaust terminals (if fitted) are replaced by the user;
not blocked.
– in the event of damage to the cable, swi-
tch off the appliance and contact exclu-
sively qualified staff for replacement;
If temporary shutdown of the indoor unit is required, – if the appliance is not to be used for a
proceed as follows: certain period, disconnect the main
a) drain the heating system if antifreeze is not used;
MAINTENANCE TECHNICIAN
indoor unit external switch.
b) shut-off all electrical, water and gas supplies.
41
If you smell gas in the building:
– close the gas meter interception device
or the main interception device;
– if possible, close the gas interception
INSTALLER
42
To preserve the system's integrity and keep the safety fe-
atures, performance and reliability, which distinguish
the assembly, unchanged over time, you must execute
maintenance operations on a yearly basis in compliance
INSTALLER
with what is stated in the relative point at “annual check
and maintenance of the appliance”, in compliance with
national, regional, or local standards in force.
USER
2.2 CONTROL PANEL
MAINTENANCE TECHNICIAN
43
43
2.3 SYSTEM USE Summer and DHW heating in progress mode
Before ignition, make sure the system is full of water,
checking that the pressure gauge needle (6) points to a
value between 1 and 1.2 bar and make sure that the
INSTALLER
For example the same request (i.e. domestic hot water (14).
request) can be satisfied by the use of outdoor unit, In this mode the protection functions available in stand-by mode
shown by its symbol ( ), or by the heat generator ( ). such as the antifreeze function etc are also guaranteed.
Winter and room central heating in progress mode
Summer
In this mode, the system only works to produce domestic hot wa-
ter, the temperature is set using the buttons (4) and the correspon-
MAINTENANCE TECHNICIAN
45
Central heating or
Winter On OFF
OFF ON (DHW)
Production of DHW and central heating or
ON (Central heating) ON (DHW)
Production of Domestic Hot Water OFF ON
Air conditioning Room cooling ON OFF
ON (Cooling) ON (DHW)
44
Air conditioning Dehumidify
In this mode, the system works both to produce DHW and to cool If the system is coupled to a humidistat (optional) or a humidity
the room. temperature sensor or a remote zone panel (optional), you can
The temperature of the DHW is always regulated via buttons (4), manage the room humidity in summer air conditioning mode.
the central heating temperature is regulated via buttons (5) and – If coupled to a humidistat, set the degree of humidity on the hu-
INSTALLER
the relative temperature is shown on the display by the indicator midistat itself (see the instruction booklet).
(14). – If coupled to a humidity temperature sensor, set the humidity
From here on, the system works automatically. If there are no re- percentage in the relative user menu.
quests (room central heating, DHW production or cooling), the – If coupled to a zone remote panel, set the humidity percentage in
system goes into the “stand-by” function. the relative user menu of the control panel or directly in the
Each time the outdoor unit ignites, the display shows the corre- menu of the panel (see instruction booklet).
sponding symbol (8) with the corresponding power scale (10).
Air conditioning and Dehumidification active mode
In this mode the protection functions available in stand-by mode
such as the antifreeze function etc are also guaranteed.
Air conditioning and room cooling in progress mode
USER
47
MAINTENANCE TECHNICIAN
The system is set up to use the outdoor unit external probe or an
optional external probe.
With the external probe connected, the system flow temperature
for room heating and air conditioning is managed by the external
probe based on the outdoor temperature measured (Parag. 1.15).
You can change the flow temperature by choosing the offset value
in the specific user menu.
TECHNICAL DATA
45
“Stand-by” Mode System operating with outdoor unit disabled
Press button (1) repeatedly until the symbol appears. The sy- You can disable the outdoor unit through a prearranged con-
stem remains off from this moment, though the antifreeze, pump nection.
anti-block and 3-way function and signalling of any anomalies Disabling occurs when contact "S41" closes (Fig. 7).
are guaranteed. This status is signalled by the flashing of the symbol “Outdoor unit
INSTALLER
set inactivity period, the brightness drops until only the active
symbols are displayed. The lighting mode can be varied via para-
meter t8 in the P.C.B. programming menu. 48
46
2.4 FAULT AND ANOMALY SIGNALS
The indoor unit signals any anomalies by flashing a code on the
display (14) according to the following table.
INSTALLER
Error
Anomaly signalled Cause Hydronic module status / Solution
Code
In the event of request of room central heating or domestic
hot water production, the heat generator does not switch on
E1 No ignition block within the preset time. Upon appliance commissioning or Press the Reset button (1) (4).
after extended downtime, it may be necessary to eliminate
the block.
Safety thermostat
block (overheating), During normal operation, if a fault causes excessive
E2 flame control or flue overheating internally, the indoor unit goes into overhea- Press the Reset button (1) (2).
gas thermofuse ting block.
anomaly
The P.C.B. detects a fault on the gas valve supply. Check its
Contacts resistance
E4 connection. (the anomaly is detected and displayed only in (1) (4).
block
USER
the event of a request).
Heat generator flow The board detects an anomaly on the NTC heat generator
E5 The system does not start (1).
probe anomaly flow probe.
The board detects an anomaly on the domestic hot water The heat generator continues to
E6 DHW probe fault NTC probe. In this case the antifreeze function is also inhi- produce domestic hot water but not
bited. with optimal performance (1) (4).
Attention: the fault may be reset up to
5 times consecutively, after which the
function in inhibited for at least one
E8 Maximum N° of resets Number of allowed resets already performed. hour. One attempt is gained every
MAINTENANCE TECHNICIAN
hour for a maximum of 5 attempts. By
switching the appliance on and off
again, the 5 attempts are re-acquired.
Check on the heat generator pressure
Water pressure inside the central heating circuit that is suf-
Insufficient system gauge that the system pressure is
E 10 ficient to guarantee the correct operation of the heat gene-
pressure between 1-1.2 bar and restore the
rator is not detected.
correct pressure if necessary.
(1) If the shutdown or fault persists, contact an authorised company (e.g. Authorised After-Sales Technical Assistance Centre)
(2) The anomaly can only be verified in the list of errors in the “Information” menu.
(3) The heat pump mode does not start, the heat generator stays active to satisfy the room heating and domestic hot water pro-
duction requests.
(4) The heat generator does not start, the heat pump mode stays active to satisfy the ongoing requests.
TECHNICAL DATA
47
Error
Anomaly signalled Cause Hydronic module status / Solution
Code
If normal conditions are restored, the
If the board detects an anomaly or incongruity on the
E 15 Configuration error heat generator restarts without having
electric wiring, the appliance will not start.
to be reset (1).
INSTALLER
E 16 Fan anomaly This occurs if the fan has a mechanical or electrical fault. Press the Reset button (1) (4).
This occurs in the event of a leak on the detection circuit or
E 20 Parasite flame block Press the Reset button (1) (4).
anomaly in the flame control unit.
Heat generator return The board detects an anomaly on the heat generator return
E 23 The system does not start (1) (4).
probe anomaly NTC probe.
If normal conditions are restored, the
Push button control
E 24 The board detects an anomaly on the pushbutton panel. system restarts without having to be
panel anomaly
reset (1).
The board detects an anomaly on the system flowmeter. The system does not start (1) (3).
System flowmeter
E 26 Make sure the booster pump (optio-
anomaly Booster pump, if any, always working. nal) only activates when requested.
This happens when the hydronic module overheats due to
poor water circulation in the primary circuit. The causes
can be:
Circulation - low system circulation; check that no shut-off devices are Check system circulation and
E 27 closed on the central heating circuit and that the system is flowmeter.
insufficient
USER
48
Error
Anomaly signalled Cause Hydronic module status / Solution
Code
Safety thermostat During normal operation, if an anomaly causes excessive
The unit does not meet the zone
E 35 intervention Mixed overheating of the flow temperature in the mixed zone 3,
central heating requirement (1).
zone 3 the unit indicates the malfunction.
INSTALLER
If normal conditions are restored, the
Low power supply This occurs when the power supply voltage is lower than the
E 37 system restarts without having to be
voltage allowed limits for correct system operation.
reset (1).
This occurs when the heat generator is ignited correctly
If normal conditions are restored, the
and the burner flame switches off unexpectedly; a new at-
E 38 Loss of flame signal generator restarts without having to
tempt at ignition is performed and if normal conditions are
be reset (1) (2) (4).
restored, the generator does not have to be reset.
Press the Reset button, before
Block due to loss of This occurs if the “Flame signal loss” error occurs many ti-
E 43 restarting, the heat generator will run
flame signal mes in a row within a preset period (E38).
a post-ventilation cycle (1) (4).
The board detects a sudden and unexpected rise in ΔT
between the system flow probe and return probe, the heat If normal conditions are restored, the
E 45 ΔT high generator limits the burner output to prevent damaging the heat generator restarts without having
condensing module; when the correct ΔT has been resto- to be reset (1) (4).
red, the heat generator returns to normal operation.
High temperature Make sure that water circulates
USER
block on heat This occurs when the heat exchanger return circuit reaches properly in the heat generator and that
E 49
generator return a temperature that is too high. the three-way valve works properly.
probe Press the Reset button (1) (4).
External probe In the event the external probe is not connected or is faulty,
E 50 Check the external probe connection.
missing or faulty the anomaly is indicated.
Puffer probe anomaly
E 54 The board detects an anomaly on the puffer probe. Puffer mode is disabled (1).
(optional)
P.C.B. malfunction This occurs in the event of malfunctions of the P.C.B. that
E 80 Press the Reset button (1) (4).
block controls the gas valve.
Block - maximum no. The maximum number of software errors possible has been
MAINTENANCE TECHNICIAN
E 98 Press the Reset button (1) (4).
of software errors reached.
E 99 General block A heat generator anomaly has been detected. Press the Reset button (1) (4).
Zone 1 device offline
E 121 The device connected to zone 1 is offline. (1).
alarm
(1) If the shutdown or fault persists, contact an authorised company (e.g. Authorised After-Sales Technical Assistance Centre)
(2) The anomaly can only be verified in the list of errors in the “Information” menu.
(3) The heat pump mode does not start, the heat generator stays active to satisfy the room heating and domestic hot water pro-
duction requests.
(4) The heat generator does not start, the heat pump mode stays active to satisfy the ongoing requests.
TECHNICAL DATA
49
Error
Anomaly signalled Cause Hydronic module status / Solution
Code
Zone 2 device offline
E 122 The device connected to zone 2 is offline. (1).
alarm
Zone 3 device offline
INSTALLER
Liquid phase probe The board detects an anomaly on the liquid phase NTC
E 179 The system does not start (1) (3).
anomaly probe.
The system does not start, see the
E 182 Outdoor unit alarm An anomaly appears on the outdoor unit. anomaly on the outdoor unit and its
instructions booklet (1) (3).
During this time, room heating/air
Outdoor unit in test conditioning and domestic hot water
E 183 A signal notifies that the outdoor unit is in test mode.
mode production requirements cannot be
met.
(1) If the shutdown or fault persists, contact an authorised company (e.g. Authorised After-Sales Technical Assistance Centre)
(2) The anomaly can only be verified in the list of errors in the “Information” menu.
(3) The heat pump mode does not start, the heat generator stays active to satisfy the room heating and domestic hot water pro-
duction requests.
(4) The heat generator does not start, the heat pump mode stays active to satisfy the ongoing requests.
TECHNICAL DATA
50
Error
Anomaly signalled Cause Hydronic module status / Solution
Code
Communication
A signal notifies an anomaly due to a communication pro- Have the electrical connection
E 184 down with outdoor
blem between the indoor unit and the outdoor unit. between the units checked (1) (3).
unit
INSTALLER
Have the electrical connection
Communication Communication anomaly between P.C.B. and ignition bo-
E 185 between the components checked (1)
alarm ard.
(4).
Igniter voltage
E 186 An anomaly appears on the ignition board. (1) (4).
anomaly
Heat pump return The board detects an anomaly on the heat pump return
E 187 (1) (3).
probe anomaly NTC probe.
Request with
A heating or cooling request is made with an outdoor tem-
E 188 temperature out of (1) (3).
perature exceeding the operating limits (Parag. 1.32).
range
Time out alarm with If communication between the printed circuit boards is
E 189 (1) (3).
interface board lost, an anomaly is signalled.
The system does not start (1).
E 190 Interface board alarm An anomaly is reported on the interface board.
See communication board errors.
Heat pump flow probe The board detects an anomaly on the NTC heat pump flow
E 192 (1) (3).
anomaly probe.
USER
Appliance in test The system continues operating
E 193 A signal notifies that the appliance is in test mode.
mode properly.
A signal notifies that the outdoor unit has been disabled The system continues operating
E 194 Outdoor unit disabled
through the appropriate input in the terminal board. properly.
Liquid phase probe
Check proper operation of the cooling
E 195 low temperature Too low temperature is detected in the liquid phase.
circuit (1) (3).
anomaly
High temperature
Excessively high temperature is detected in the flow circuit
E 196 block on heat pump Check the hydraulic circuit (1) (3).
of the heat pump.
flow
MAINTENANCE TECHNICIAN
Interface board An incorrect interface board configuration has been de-
E 197 The system does not start (1)
configuration error tected.
(1) If the shutdown or fault persists, contact an authorised company (e.g. Authorised After-Sales Technical Assistance Centre)
(2) The anomaly can only be verified in the list of errors in the “Information” menu.
(3) The heat pump mode does not start, the heat generator stays active to satisfy the room heating and domestic hot water pro-
duction requests.
(4) The heat generator does not start, the heat pump mode stays active to satisfy the ongoing requests.
TECHNICAL DATA
51
Interface board anomalies list On the interface board, the error is displayed with an “E” + error
If the outdoor unit is faulty, the error code is signalled on the con- code, showing a sequence of two digits.
trol panel (Fig. 43) and on the interface board (see paragraph "In- For example:
terface board - 7-segment display"). The failure is signalled in dif- Error 101 is displayed as follows: E1 alternated with 01.
ferent ways. The following is the list of alarms as displayed on the control pa-
INSTALLER
On the control panel, the error is displayed with an “A” + error nel.
code.
(1)
Check wiring of communication between the two boards.
Communication error between Inverter and main Replace the main board.
A203
board of the outdoor unit Replace the inverter board
(1)
Check the position of the sensor.
Check the relative wiring
A221 Outdoor unit air temperature sensor error
Replace the sensor
(1)
Check the position of the sensor.
Check the relative wiring
A231 Condenser temperature sensor error
Replace the sensor
(1)
Check the position of the sensor.
A251 Discharge temperature sensor error Check the relative wiring
Replace the sensor
TECHNICAL DATA
52
Error Code Anomaly signalled Indoor unit status / Solution / Solution
Check the chiller cycle.
A403 Freezing detection (during cooling operation) Check the temperatures of the plate heat exchanger
(1)
INSTALLER
Check the chiller cycle.
Check the compressor connections.
Protection of outdoor unit when in overload
A404 Check the resistances between the different phases of the compres-
(during safety start-up, normal operating status)
sor
(1)
Check the chiller cycle
A407 Compressor not working due to high pressure
(1)
A416 The compressor discharge is overheated (1)
A430 Outdoor unit EEV operation error (1)
A425 Not used on this model (1)
Central heating blocked (outdoor temperature
A440 (1)
beyond 35°C)
A441 Cooling blocked (outdoor temperature below 9°C) (1)
A458 Error of outdoor unit fan no.1 1
Check the chiller cycle.
USER
Check the compressor connections.
A461 Compressor start-up error (Inverter) Check the resistances between the different phases of the compres-
sor
(1)
Check the inlet current.
Check the refrigerant charge.
A462 Inverter total current overload error
Check normal operation of the fan.
(1)
MAINTENANCE TECHNICIAN
Check the compressor sensor.
A463 Compressor overheated sensor
(1)
Check the compressor connections and its normal operation.
Check the refrigerant charge.
Check whether there are obstacles around the outdoor unit.
A464 Inverter IPM current overload error
Check whether the service valve is open.
Check whether the installation pipes are mounted properly.
(1)
Check the compressor connections and its normal operation.
Check the resistances between the different phases of the compres-
A465 Compressor overload error
sor.
(1)
Check the input voltage.
A466 Low voltage error of DC circuit Check the power connections.
(1)
Check the compressor connections.
TECHNICAL DATA
53
Error Code Anomaly signalled Indoor unit status / Solution / Solution
Check the power connector of the inverter board.
A469 Voltage sensor error of DC circuit (inverter) Check the connectors RY21 and R200 of the inverter board.
(1)
INSTALLER
54
Error Code Anomaly signalled Indoor unit status / Solution / Solution
Indoor unit error
A906 Not used Check indoor unit
(1)
INSTALLER
Indoor unit error
A911 Not used Check indoor unit
(1)
Indoor unit error
A912 Not used Check indoor unit
(1)
Indoor unit error
A916 Not used Check indoor unit
(1)
Indoor unit error
A919 Not used Check indoor unit
(1)
(1) If the shutdown or fault persists, contact an authorised company (e.g. Authorised After-Sales Technical Assistance Centre)
USER
MAINTENANCE TECHNICIAN
TECHNICAL DATA
55
2.5 PARAMETERS AND INFORMATION To scroll through the menu items and to edit the values, use the
MENU heating temperature control buttons (5). Pressing the “OK” but-
ton (1) confirms the parameter, while pressing the “ESC” button
Information menu (3) goes back to the previous menu or exits.
Pressing the “MENU” button (2), the display cyclically shows the A minute after the last operation, the system automatically exits
INSTALLER
“Data” menu, “User” menu and a menu protected by a “0000” ac- any of the menus.
cess code with the first flashing digit reserved for a qualified tech- The menus of the control panel, found in the booklet, re-
nician. fer to rev. 3.0 of the P.C.B. firmware.
To access an individual menu, once it appears, press the “OK” but-
ton (1).
Data Menu.
Parameter ID Description Range
D 01 Combustion signal ( x 0.1 μA) 0 ÷ 99 μA
Temperature of the instant heating thermal generator flow outgoing from the heat generator pri-
D 02 0 ÷ 99°C
mary exchanger
USER
56
Parameter ID Description Range
D 44 Zone 2 humidistat (if zone 2 humidistat active) OFF - ON
D 45 Dehumidifier zone 1 OFF - ON
D 46 Dehumidifier zone 2 OFF - ON
INSTALLER
D 47 Zone 1 circulator pump OFF - ON
D 48 Zone 2 circulator pump OFF - ON
D 49 Central heating / cooling system separation 3-way (CL = cooling, HT = heating) CL - HT
D 51 Zone 1 remote panel OFF - ON
D 52 Zone 2 remote panel OFF - ON
D 53 System setting with remote connection in zone 1 5 ÷ 80°C
D 54 System setting with remote connection in zone 2 5 ÷ 80°C
D 55 Zone 1 thermostat OFF - ON
D 56 Zone 2 thermostat OFF - ON
D 61 System model definition ( MP = Magis Pro; MCI = Magis Combo; MCP = Magis Combo Plus) MP - MCI - MCP
D 62 Communication with outdoor unit interface board OFF - ON
D 63 Communication with other Immergas devices OFF - ON
D 71 External unit operating frequency 0 ÷ 150 Hz
USER
D 72 Compressor temperature -20 ÷ 200 °C
D 73 Compressor discharge temperature -20 ÷ 100 °C
D 74 Evaporator coil temperature -20 ÷ 100 °C
Outdoor unit compressor absorption (make sure the value reading refers to the inverter and there-
D 75 0 ÷ 10 A
fore not a value read with an amperometric clamp)
D 76 Outdoor unit fan speed 0 ÷ 100 rpm
D 77 Electronic expansion valve position 0 ÷ 2000
D 78 4-way side (CL = cooling, HT = heating) HT / CL
D 79 Temperature detected by the external probe of the outdoor unit -55°÷ +45°C
MAINTENANCE TECHNICIAN
D 80 Heat pump status (reserved for Technical Assistance Service) 0 ÷ 255
D 91 P.C.B. software version 30
D 92 Ignition board software version
D 97 Heat pump demand status (reserved for Technical Assistance Service) 0 ÷ 999
Thermal generator demand status (reserved for Authorised After-Sales Technical Assistance
D 98 0 ÷ 999
Centre)
D 99 System state (reserved to Authorised After-Sales Technical Assistance Centre) 0 ÷ 999
D101 Zone 3 flow temperature (if applicable) 1 ÷ 99
D102 Zone 3 relative humidity (if available) 1 ÷ 99
D103 Zone 3 humidistat (if present) OFF - ON
D104 Zone 3 dehumidifier (if present) OFF - ON
TECHNICAL DATA
57
Parameter ID Description Range
D105 Zone 3 circulator pump OFF - ON
D106 Zone 3 remote panel OFF - ON
D107 Zone 3 setpoint 1 ÷ 99
INSTALLER
User Menu.
Parameter Customised
Description Range Default
ID value
U 01 Zone 2 heating flow set point in case of no thermal regulation (“R 01” = OFF). 20 ÷ 80°C 25
U 02 Zone 2 cooling flow set point in case of no thermal regulation (“R 01” = OFF) 5 ÷ 25 °C 20
U 03 Zone 1 central heating offset You can edit the flow temperature with respect to - 15 ÷ + 15 °C 0
the external probe regulation curve in central hea-
U 04 Zone 2 central heating offset - 15 ÷ + 15 °C 0
ting mode (Parag. 1.16, Offset value)
U 05 Zone 1 cooling offset You can edit the flow temperature with respect to - 15 ÷ + 15 °C 0
the external probe regulation curve in cooling sta-
U 06 Zone 2 cooling offset - 15 ÷ + 15 °C 0
ge (Parag. 1.16, Offset value)
TECHNICAL DATA
58
Parameter Customised
Description Range Default
ID value
U 07 Zone 1 humidity setting The humidity temperature sensor (optional) defi- 30 ÷ 70 % 50
U 08 Zone 2 humidity setting nes room humidity in the corresponding area 30 ÷ 70 % 50
INSTALLER
This function can only be activated if CARV2 (op-
tional) is available.
Activating the function allows you to reduce the
compressor frequency during the outdoor unit
operation in the time slot set in the U 12 and U 13
U 11 Night function OFF - ON OFF
parameters.
Make sure the additional power sources needed to
meet potential requirements that may present
themselves during active operation are available
(e.g. additional resistances)
U 12 Night function enabling time 0 ÷ 23 0
U 13 Night function disabling time 0 ÷ 23 0
U 14 Zone 3 heating flow set point in case of no thermal regulation (“R 01” = OFF). 20 ÷ 80 °C 25
U 15 Zone 2 cooling flow set point in case of no thermal regulation (“R 01” = OFF) 5 ÷ 25 °C 20
U 16 Zone 3 central heating offset - 15 ÷ + 15 °C 0
USER
U 17 Zone 3 cooling offset - 15 ÷ + 15 °C 0
U 18 Zone 3 humidity setpoint 30 ÷ 70 50
U 21 Hour setting (internal clock) 0 - 23 hours
U 22 Minutes setting (internal clock) 0 - 59 minutes
Mo-Tu-We-
U 23 Day of the week
Th- Fr-Sa-Su
U 24 Current day 1 ÷ 31
U 25 Current month 1 ÷ 12
MAINTENANCE TECHNICIAN
U 26 Current year 00 ÷ 99
U 32 Start time of the DHW recirculation function (do not use) 0 - 23 hours
U 33 Start time of the DHW recirculation function (do not use) 0 - 23 hours
In the case of new central heating systems and in
particular mode for floor systems, it is very impor-
tant that de-aeration is performed correctly. The
function consists of the cyclic activation of the
pump (100 s ON, 20 s OFF) and the 3-way valve
U 50 Venting OFF - ON OFF
(120 s D.H.W., 120 s heating system).
The function lasts for 18 hours and it is possible to
stop it by pressing “ESC” and setting the function
on “OFF”. Activation of the function is signalled
by the countdown shown on the indicator (14).
TECHNICAL DATA
The parameters referring to zone 2 can only be displayed The parameters referring to zone 3 can only be displayed
if there is a zone 2 on the system and it is configured cor- if there is a zone 3 on the system and it is configured cor-
rectly. rectly.
59
2.6 INDOOR UNIT SHUTDOWN All information relative to the antifreeze protection is stated in
(Parag. 1.5).
Switch the indoor unit off by putting it in “off” mode, disconnect
In order to guarantee the integrity of the appliance and the dome-
the omnipolar switch outside of the indoor unit and close the gas
stic hot water heating system in areas where the temperature
cock upstream from the appliance.
drops below zero, we recommend protecting the central heating
INSTALLER
Never leave the indoor unit switched on if left unused for prolon-
system using anti-freeze liquid and installing the Immergas Anti-
ged periods.
freeze Kit in the indoor unit.
In the case of prolonged inactivity (second case), we also recom-
2.7 RESTORE CENTRAL HEATING SYSTEM mend that:
PRESSURE - to switch off the power supply;
- completely empty the central heating circuit and the indoor
1. Periodically check the system water pressure (the indoor unit domestic hot water circuit. In systems that are drained fre-
unit’s pressure gauge hand must indicate a value between 1 quently, filling must be carried out with suitably treated water to
and 1.2 bar). eliminate hardness that can cause lime-scale.
2. If the pressure is less than 1 bar (with the system cold), you
must restore it using the cock located at the bottom of the unit
(Parag. 1.36). 2.11 CLEANING THE CASE
3. Close the cock after the operation.
1. Use damp cloths and neutral detergent to clean the indoor unit
4. If the pressure reaches values around 3 bar, there is a risk of
casing.
tripping the safety valve (in this case, remove water from a ra-
diator air vent valve until a pressure of 1 bar is achieved, or ask Never use abrasive or powder detergents.
for assistance from professionally qualified personnel).
USER
(OPTIONAL)
If fluid containing glycol was added to the system circu-
it, make sure it is recovered and disposed of in accordan- For general operation of the zone remote panel, see the relative in-
ce with standard EN 1717. struction booklet.
The settings on the remote panel, such as operating mode, flow
setting, humidity setting etc. are synchronised with those on the
control panel.
2.9 EMPTYING THE D.H.W. CIRCUIT Moreover, the control panel is not disabled if there is any zone re-
mote panel.
To do this, always close the domestic cold water inlet upstream of
the appliance.
Open any domestic hot water tap to discharge the pressure from
the circuit.
60
3 INSTRUCTIONS FOR
MAINTENANCE AND INITIAL
CHECK
R32 refrigerant gas belongs to the low
flammability refrigerant category: class
A2L according to standard ISO 817. It
guarantees high performance with low
INSTALLER
3.1 GENERAL RECOMMENDATIONS environmental impact. The new gas re-
duces the potential environmental im-
Operators who install and service the ap- pact by one third compared to R410A,
pliance must wear the personal protecti- having less effect on global warning
ve equipment (PPE) required by appli- (GWP 675).
cable law.
The list of possible PPE is not complete as
they are indicated by the employer.
3.2 INITIAL CHECK
To commission the package, you must:
- make sure that the type of gas used corresponds to indoor unit
Before carrying out any maintenance settings;
work, make sure that: - check connection to a 230V-50Hz power mains, correct L-N
– you have disconnected the power to the polarity and the earthing connection;
- make sure the central heating system is filled with water and the
appliance;
USER
indoor unit pressure gauge reads a pressure of 1-1.2 bar;
– you have discharged the pressure from - check that the air vent valve cap is open and that the system is
the system and domestic hot water cir- well-vented;
cuit. - switch the indoor unit on and check correct ignition;
- check the Δp gas values in domestic hot water and central hea-
Supply of spare parts ting modes;
The device’s warranty shall be rendered null and void if - check the CO2 flow rate in the flue:
unapproved or unsuitable parts are used for maintenan- • maximum
ce or repairs. These will also compromise the product’s • minimum
compliance, and the said product may no longer be valid - check activation of the safety device in the event of no gas, as
MAINTENANCE TECHNICIAN
and fail to meet the current regulations. in regard to the well as the relative activation time;
above, only use original Immergas spare parts when re- - make sure the chiller circuit has been filled according to what is
placing components. described in the Audax Pro V2 condensing unit instructions
booklet;
- check the activation of the main switch located upstream of the
indoor unit;
If additional documentation needs to be consulted for - check that the intake and/or exhaust terminals are not blocked;
extraordinary maintenance, contact the Authorised - ensure activation of all adjustment devices;
After-Sales Service. - seal the gas flow regulation devices (if the settings are changed);
- ensure production of domestic hot water;
- check the tightness of the hydraulic circuits;
The appliance operates with R32 refrige- - check ventilation and/or aeration of the installation room whe-
rant gas. re provided.
This gas is ODOURLESS. Even if just one single safety check provi-
Pay the utmost attention des a negative result, do not commission
Strictly follow the instruction handbook the system.
of the UE Audax Pro outdoor unit before
TECHNICAL DATA
61
3.3 YEARLY APPLIANCE CHECK AND • the power supply wires must be housed in the cable glands;
MAINTENANCE • there must be no traces of blackening or burning.
- Check correct lighting and operation.
The following checks and maintenance should be per- - Ensure correct calibration of the burner in domestic water and
formed once a year to ensure operation, safety and effi- central heating phases.
INSTALLER
ciency of the appliance over time. - Check correct operation of control and adjustment devices and
in particular:
• system control thermostat intervention;
- Clean the flue side of the heat exchanger. • domestic hot water control thermostat intervention.
- Clean the main burner. - Check sealing efficiency of gas circuit and the internal system.
- Check the correct positioning, integrity and cleanliness of the - Check the intervention of the device against no gas ionisation
detection and ignition electrode; remove any oxide present. flame control. Intervention time must be less than 10 seconds.
- If deposits are detected in the combustion chamber they must - Check chiller line connections.
be removed and the heat exchanger coils must be cleaned using - Check mesh filter on system return
nylon or broomcorn brushes; it is forbidden to use brushes - Check the correct flow rate on plate heat exchanger.
made of metal or other materials that may damage the combu- - Check the integrity of the internal insulation.
stion chamber. It is also forbidden to use alkaline or acid deter- We recommend regularly inspecting the finned air coils
gents. to check the level of fouling.
- Check the integrity of the insulating panels inside the combu-
stion chamber and if damaged replace them.
- Visually check for water leaks or oxidation from/on con-
nections and traces of condensate residues inside the sealed
USER
chamber.
- Check the contents of the condensate drain trap.
- Visually check that the siphon is properly filled with condensate
and top it up if necessary.
- Check that there are no material residues in the condensate
drain siphon clogging the condensate passage; also check that
the entire condensate drainage circuit is clear and efficient.
- In the event of obstructions (dirt, sediment, etc.) with conse-
quent leakage of condensate in the combustion chamber, one
MAINTENANCE TECHNICIAN
62
This depends on the environment where the unit is installed. The
level of fouling will be worse in urban and industrial sites, as well
as near trees that lose their leaves.
There are two maintenance levels to clean the coils:
- If the air heat exchangers are encrusted, clean them gently with
INSTALLER
a brush in a vertical direction.
- Turn off the fans before working on the air heat exchangers.
- To perform this type of intervention, stop the unit only if the
maintenance considerations allow it.
- Perfectly clean air heat exchangers ensure an optimal operation
of the unit. When the air heat exchangers begin to encrust, they
must be cleaned. The cleaning frequency depends on the season
and location of the unit (ventilated, wooded, dusty, etc.).
Clean the air coil using suitable products.
Do not use pressurised water without a large diffuser. Do
not use high-pressure cleaners for Cu/Cu and Cu/Al air
coils.
Concentrated and/or rotating water jets are strictly
prohibited.
Never use fluid with a temperature above 45°C to clean
the air heat exchangers.
USER
Proper and frequent cleaning (approx. every three mon-
ths) prevents 2/3 of corrosion problems.
MAINTENANCE TECHNICIAN
TECHNICAL DATA
63
3.4 HYDRAULIC DIAGRAM Key (Fig. 49):
1 - D.H.W. flow switch
2 - Condensate drain trap
3 - Gas valve
4 - Gas valve outlet pressure point (P3)
INSTALLER
G - Gas supply
SC - Condensate drain
LP - Chiller line - liquid phase
TECHNICAL DATA
64
3.5 WIRING DIAGRAM
INSTALLER
1
2 3
USER
50
MAINTENANCE TECHNICIAN
A17-1 - Modbus zone 1 temp./humidity probe (optional)
A17-2 - Modbus zone 2 temp./humidity probe (optional)
A17-3 - Modbus zone 3 temp./humidity probe (optional)
BR - Brown
G - Green
GY - Grey
G/Y - Yellow/Green
P - Viola
PK - Pink
R - Red
51
65
INSTALLER
Z
USER
MAINTENANCE TECHNICIAN
52
66
INSTALLER
USER
MAINTENANCE TECHNICIAN
53
W - White
Y - Yellow
W/BK - White/Black
67
Key (Fig. 54):
A2 - P.C.B.
A7 - Three-relay board (Optional)
G4 - 24 Vdc power supply unit
INSTALLER
54
MAINTENANCE TECHNICIAN
55
68
INSTALLER
USER
56
MAINTENANCE TECHNICIAN
Key (Fig. 56): Colour code key (Fig. 56):
A7 - Three-relay board (optional) BK - Black
A22 - Condensing unit interface board BL - Blue
B2 - D.H.W. probe BR - Brown
B27 - Liquid phase probe G - Green
G4 - 24 Vdc power supply unit GY - Grey
R14 - Resistance configuration G/Y - Yellow/Green
S4 - D.H.W. flow switch OR - Orange
P - Viola
PK - Pink
R - Red
W - White
Y - Yellow
W/BK - White/Black
TECHNICAL DATA
69
P.C.B.
Key (Fig. 57):
1 - F 3.15A H250V fuse
INSTALLER
USER
57
SW4 SW5
ON
OFF
1 2 3 4
CN4
TECHNICAL DATA
CN3 CN2
RED BLK
58
70
Interface board - indicator LED
LED
INSTALLER
CN4
Y-GRN
RED
YEL
Y-GRN
RED
YEL
CN3 CN2
RED BLK
USER
59
Key (Fig. 59): Green LED flashing = Communication between interface board and
Red LED flashing = Communication between interface board and outdoor unit valid
P.C.B. valid Yellow LED = Not Used
MAINTENANCE TECHNICIAN
SEGMENTS
VALID COMMUNICATION
E101
60
71
3.7 TROUBLESHOOTING
Maintenance operations must be carried out by an au-
thorised company (e.g. Authorised After-Sales Techni-
cal Assistance Centre).
INSTALLER
installed.
Frequent trips of the Lack of water in the boiler, poor water cir- Check on the pressure gauge that the system pressure is within establi-
overheating safety device culation in the system or blocked circula- shed limits. Check that the radiator valves are not closed and also the
thermostat function. ting pump (Par. 1.34). functionality of the pump.
Dirt or combustion products deposited in- Check that there are no residues of material blocking the flow of
Siphon blocked
side. condensate.
Check that there are no residues of material blocking the flow of
Heat exchanger blocked. Obstruction of the siphon.
condensate.
Check the opening of the cap of the air vent valve (Par. 1.36). Make sure
the system pressure and expansion vessel pre-charge values are within
Abnormal noises in the
Air in the system. the set limits. The factory-set pressure values of the expansion vessel
system
must be 1.0 bar, the value of system pressure must be between 1 and 1.2
bar.
Use the manual air vent valve (Par. 1.36) to eliminate any air present in
Abnormal noises in the
Air in the module. the condensation module. When the operation has been performed,
condensation module
close the manual vent valve.
Poor production of Clogged condensing module or D.H.W. Contact After-Sales Assistance Service that has procedures to clean the
D.H.W. exchanger. module or D.H.W. heat exchanger.
TECHNICAL DATA
Poor production of Contact the Authorised After-Sales Assistance Service that has
DHW heat exchanger clogged.
D.H.W. procedures to clean the D.H.W. heat exchanger.
72
3.8 GAS VALVE These adjustments must be made with reference to the type of gas
used, following that given in the table in the indoor unit manual.
The gas valve (Fig. 61) is equipped with functioning status signal
LED (5), the LEDs are under the transparent protection cover (4). Checks following conversion to another type of gas.
After having made sure that the conversion is complete and that
INSTALLER
the calibration has been successful, you must make sure that:
Colour Status - there is no flame in the combustion chamber;
Off Gas valve not powered - the burner flame is not too high or low and that it is stable (does
Green Gas valve powered and working not detach from burner);
Red Gas valve powered and not working
The pressure testers used for calibration
should be perfectly closed and there
4 P1 should be no leaks from the gas circuit.
T
OU
Maintenance operations must be carried out by an au-
thorised company (e.g. Authorised After-Sales Techni-
P3
IN
cal Assistance Centre).
2
12
5 3
3.10 FAN SPEED CALIBRATION
USER
1
61
Verification and calibration are necessary, in the case of
Key (Fig. 61): transformation to other types of gas, in the extraordi-
1 - Gas valve inlet pressure point
nary maintenance phase with replacement of the PCB,
2 - Gas valve outlet pressure point
air/gas circuit components or in the case of installations
3 - Off/Set adjustment screw
with flue extraction systems, with horizontal concentric
4 - Transparent protection cover
pipe measuring more than 1 metre.
5 - Gas valve status signal display
12 - Outlet gas flow rate adjuster The indoor unit heat output is correlated to the length of the air
intake and flue exhaust pipes.
MAINTENANCE TECHNICIAN
This decreases with the increase of pipe length.
3.9 CONVERTING THE HEAT GENERATOR The indoor unit leaves the factory adjusted for minimum pipe
TO OTHER TYPES OF GAS length (1m). It is therefore necessary, especially in the case of ma-
ximum pipe extension, to check the Δp gas values after at least 5
The gas conversion operation must be carried out by an
minutes of the burner operating at nominal heat output, when the
authorised company (e.g. Authorised Technical Assi-
temperatures of the intake air and exhaust flue gas have stabilised.
stance Service).
Adjust the nominal and minimum output in the domestic hot
water and central heating modes according to the values in the
If the appliance needs to be converted to a different gas type to that table in the indoor unit manual using the differential manometers
specified on the data plate, request the relative conversion kit for connected to the Δp gas pressure points (Det. 9-Fig. 42).
quick and easy conversion. Enter the configurations menu and regulate the following para-
To convert to another type of gas the following operations are re- meters (Parag. 3.12);
quired: - DHW minimum no. of fan revs “S 00”;
- disconnect power to the appliance; - DHW maximum no. of fan revs “S 01”;
- replace the nozzle positioned between the gas pipe and the air/ - delete ignition stage "S 02".
gas mixing sleeve, taking care to remove the voltage from the
appliance during this operation;
- re-power the appliance;
TECHNICAL DATA
73
Listed below are the default settings featured:
CO2 value is that specified in the table, otherwise adjust the screw
(Det. 3Fig. 61)(Off-Set adjuster).
To increase the CO2 value, turn the adjustment screw (3) in a
clockwise direction and vice versa to decrease it.
Calibration of maximum CO2 (nominal central heating
output).
On completion of the adjustment of the minimum CO2 keeping
the chimney sweep function active, take the heating selector swi-
tch to maximum (increase the value until “99” is seen on the di-
splay).
To have an exact value of CO2 the technician must insert the sam-
pling probe to the bottom of the sample point, then check that the
CO2 value is that specified in the table below, otherwise adjust the
screw (Det. 12Fig. 61)(gas flow rate regulator).
To increase the CO2 value, turn the adjustment screw (12) in a
clockwise direction and vice versa to decrease it.
At every adjustment variation on the screw 12 it is necessary to
wait for the heat generator to stabilise itself at the value set (about
TECHNICAL DATA
30 sec.).
74
3.12 P.C.B. PROGRAMMING Once you have accessed programming, you can scroll through the
parameters in the “System” menu.
The water heater is set up for possible programming of several
Using the “central heating regulation” button, select the parame-
operation parameters. By modifying these parameters as descri-
ter and edit the value.
bed below, the system can be adapted according to specific needs.
To save the parameter change, press the “OK” button.
INSTALLER
To access the programming phase, press the “MENU” button (2)
Wait for 1 minute or press the “ESC” button (3) to exit program-
until the “Password” menu appears. Enter the password, modify
ming mode.
the numerical values using the “central heating regulation” but-
tons (5) and confirm with the “OK” button (1).
Parameter Customised
Description Range Default
ID value
Defines the minimum operating
A 03 Minimum speed 0 ÷ 100 % 100
speed of the system circulator pump
Defines the maximum operating
A 04 Maximum fixed speed 45 ÷ 100 % 100
speed of the system circulator pump
0 = Fixed
(See Parag. “Circulation pump”)
A 05 Circulator mode 0 - 25 °C 0
5 - 25 K = ΔT constant
USER
(See Parag. “Circulation pump”)
Establishes the outdoor unit model
paired with the hydronic module. If
A 11 Outdoor unit model OFF - 4 - 6 - 9 9
set to OFF, only the integrated
generators are activated.
Enables the automatic vent function.
A 12 System vent This function activates as soon as the OFF - ON ON
unit is powered.
Defines the number of zones in the
A 13 Number of zones 1–2–3 1
MAINTENANCE TECHNICIAN
heating system
Zone 2 max temperatu- Defines the maximum temperature
A 14 20 ÷ 80 °C 45
re acceptable by zone 2
Zone 3 max temperatu- Defines the maximum temperature
A 15 20 ÷ 80 °C 45
re acceptable by zone 3
SE = Temperature - humidity
sensor
Defines the type of control on zone 1 ST = Humidistat
A 16 Zone 1 humidity sensor ST #V#
humidity RP = Remote Panel
RPH = Remote Panel with
Humidistat
SE = Temperature - humidity
sensor
Defines the type of control on zone 2 ST = Humidistat
A 17 Zone 2 humidity sensor ST #V#
humidity RP = Remote Panel
RPH = Remote Panel with
Humidistat
Heat generator
TECHNICAL DATA
75
Customised
Parameter ID Description Range Default
value
485 = Do not use
A 22 BMS communication setting OFF - 485 - UC OFF
UC = Do not use
INSTALLER
SE = Tempera-
ture - humidity
sensor
ST = Humidi-
Defines the type of control on zone 3 stat
A 23 Zone 3 humidity sensor ST #V#
humidity RP = Remote
Panel
RPH = Remote
Panel with
Humidistat
Allows you to enable the Dominus remote
A 30 Dominus enabling OFF – ON OFF
device
RT = Room
thermostat
Room thermostat / Remote panel / Remote RP = Remote
A 31 Zone 1 room thermostat panel with Thermostat. Panel RT
This defines temperature control in zone 1 RPT = Remote
USER
thermostat
Room thermostat / Remote panel / Remote RP = Remote
A 33 Zone 3 room thermostat panel with Thermostat. Panel RT
This defines temperature control in zone 3 RPT = Remote
panel with Ther-
mostat
Allows to determine heating, cooling mode
A 41 Zone 1 heating / cooling enable HT / CL / H – C H-C
or both of zone 1
Allows to determine heating, cooling mode
A 42 Zone 2 heating / cooling enable HT / CL / H – C H-C
or both of zone 2
Allows to determine heating, cooling mode
A 43 Zone 3 heating / cooling enable HT / CL / H – C H-C
or both of zone 3
TECHNICAL DATA
76
Parameter Customised
Description Range Default
ID value
Defines the maximum heat output percentage of
P 00 DHW max the heat generator during the D.H.W. phase 0 - 100 % 100 %
INSTALLER
compared to the maximum heat output available
Defines the minimum heat output percentage of
P 01 Min C.H. the heat generator during the C.H. phase compa- 0 – P 02 % 0
red to the maximum heat output available
Defines the minimum heat output percentage of
P 02 Central heating max the heat generator during the C.H. phase compa- 0 - 100 % 85 %
red to the maximum heat output available
The hydronic module is set up to operate with a
configurable relay board (optional)
0 = Off
1 = DHW recirculation
P 03 Relay 1 (optional) 0÷5 0
2 =General alarm
3 = Central heating / cooling mode active
4 = Puffer mode active
5 = Dehumidifier zone 3
The hydronic module is set up to operate with a
USER
configurable relay board (optional)
0 = Off
1 = DHW recirculation
P 04 Relay 2 (optional) 0÷5 0
2 =General alarm
3 = Central heating / cooling mode active
4 = Puffer mode active
5 = Zone 3 mixing valve closing
The hydronic module is set up to operate with a
configurable relay board (optional)
MAINTENANCE TECHNICIAN
0 = Off
1 = DHW recirculation
P 05 Relay 3 (optional) 0÷5 0
2 =General alarm
3 = Central heating / cooling mode active
4 = Puffer mode active
5 = Zone 3 mixing valve opening
If the reading of the external probe is not accurate,
P 07 External probe correction it is possible to correct it in order to compensate -9 ÷ 9 K 0
any environmental factors
Gen. thermal DHW setpoint The DHW flow setpoint of the thermal generator is
P 11 2 ÷ 30 °C 20
offset calculated by adding P011 to the DHW setpoint
DHW electric resistance
P 12 Call Immergas technical service assistance 5 ÷ 50 °C 10
tripping offset
Allows to correct the heating mode demand
P 23 Heat setpoint correction setpoint in presence of dispersions or system 0 ÷ 10°C 0
decoupling circuits
Allows to correct the cooling mode demand
TECHNICAL DATA
77
Parameter Customised
Description Range Default
ID value
This establishes the ignition and shutdown mode
of the appliance in DHW mode.
INSTALLER
systems (e.g. zone systems with motorised valves, (10 sec step)
etc.), it may be necessary to delay ignition.
Establishes the display lighting mode.
AU: the display lights up during use and dims after
15 seconds of inactivity, in case of anomaly the
T 08 Display lighting AU - OFF - ON AU
display works in flashing mode.
OFF: display lighting is always off.
ON: display lighting is always on.
Establishes what the indicator displays 14 (Fig. 12).
“Summer” mode:
ON: active circulator, this displays the flow
temperature, with circulator off the indicator is off
OFF: the indicator is always off
T 09 Display “Winter” and “cooling” mode: ON - OFF ON
ON: active circulator, this displays the flow
temperature, with circulator off the set value is
displayed on the central heating selector
OFF: this always displays the value set on the
TECHNICAL DATA
78
Parameter Customised
Description Range Default
ID value
T11 Do not use 0 ÷ 36 0
Screed heating - days at Defines the time spent at minimum operating
T 21 0 ÷ 7 days 3
INSTALLER
minimum temperature temperature during the active function
T 22 Screed heating - ascent gradient Defines the ascent gradient of the temperature 0 - 30°C / day 30
Screed heating - days at Defines the time spent at maximum operating
T 23 0 ÷ 14 days 4
maximum temperature temperature during the active function
Screed heating - descent
T 24 Defines the descent gradient of the temperature 0 - 30°C / day 30
gradient
Parameter Customised
Description Range Default
ID value
Defines if and which external probe is used to
manage the system. OFF = no external probe is
used
R 01 External probe OFF - OU - IU OU
OU = external probe on the condensing unit
USER
IU = optional external probe connected to the
hydronic module
Outdoor temperature for max Establishes the outdoor temperature at which to
R 02 -15 ÷ 25 °C -5
CH flow zone 1 have the maximum flow temperature of zone 1.
Outdoor temperature for min Establishes the outdoor temperature at which to
R 03 -15 ÷ 25 °C 25
CH flow zone 1 have the minimum flow temperature of zone 1.
Zone 1 maximum central Defines the maximum flow temperature in zone 1
R 04 20 ÷ 80 55
heating room central heating mode
Zone 1 minimum central Defines the minimum flow temperature in zone 1
R 05 20 ÷ 80 25
heating room central heating mode
MAINTENANCE TECHNICIAN
Outdoor temperature for Zone 2
Establishes the outdoor temperature at which to
R 06 low temperature zone max. CH -15 ÷ 25 °C -5
have the maximum flow temperature of zone 2
flow
Outdoor temperature for Zone 2
Establishes the outdoor temperature at which to
R 07 low temperature zone min. CH -15 ÷ 25 °C 25
have the minimum flow temperature of zone 2
flow
Zone 2 low temperature zone Defines the maximum flow temperature in zone 2
R 08 20 ÷ 80 45
maximum central heating room central heating mode
Zone 2 low temperature zone Defines the minimum flow temperature in zone 2
R 09 20 ÷ 65 25
minimum central heating room central heating mode
Establishes the maximum outdoor temperature at
Zone 1 outdoor temperature for
R 10 which to have the minimum flow temperature in 20 ÷ 40 35
minimum cooling flow
zone 1 cooling mode
Establishes the minimum outdoor temperature at
Outdoor temperature for Zone 1
R 11 which to have the maximum flow temperature in 20 ÷ 40 25
maximum cooling flow
zone 1 cooling mode
Defines the minimum flow temperature in zone 1
R 12 Zone 1 minimum cooling 05 ÷ 20 7
room cooling mode
TECHNICAL DATA
79
Parameter Customised
Description Range Default
ID value
Outdoor temperature for Zone 2
Establishes the outdoor temperature at which to
R 15 low temperature zone max 20 ÷ 40 25
have the maximum flow temperature of zone 2
INSTALLER
cooling flow
Zone 2 low temperature zone Defines the minimum flow temperature in zone 2
R 16 05 ÷ 20 18
minimum cooling room cooling mode
Zone 2 low temperature zone Defines the maximum flow temperature in zone 2
R 17 05 ÷ 25 20
maximum cooling room cooling mode
Outdoor temperature for max Establishes the outdoor temperature at which to
R 21 -15 ÷ 25 -5
CH flow zone 3 have the maximum flow temperature of zone 3
Outdoor temperature for min Establishes the outdoor temperature at which to
R 22 -15 ÷ 25 25
CH flow zone 3 have the minimum flow temperature of zone 3
Zone 3 maximum central Defines the maximum flow temperature in zone 3
R 23 20 ÷ 65 45
heating room central heating mode
Zone 3 minimum central Defines the minimum flow temperature in zone 3
R 24 20 ÷ 65 25
heating room central heating mode
Outdoor temperature for Zone 3
Establishes the outdoor temperature at which to
R 25 low temperature zone min 20 ÷ 40 35
have the minimum flow temperature of zone 3
cooling flow
Outdoor temperature for Zone 3
Establishes the outdoor temperature at which to
USER
Integration menu.
MAINTENANCE TECHNICIAN
Parameter Customised
Description Range Default
ID value
Allows you to enable an alternative power source
I 01 DHW integration enabling OFF - AL AL
(AL) to integrate domestic hot water heating
Using this function, you can enable an alternative
I 02 System integration enabling (AL) power source to integrate heating system OFF - AL AL
central heating
Establishes the maximum amount of time before
I 04 Central heating max wait time 1 - 255 minutes 30
activating central heating integration
Establishes how to integrate the heat generator to
I 05 Integration activation mode the outdoor unit, you can choose between “AU” AU - MA AU
automatic and “MA” manual
Establishes the outdoor temperature under which
I 06 Activation temperature -15 ÷ 35 °C 2
central heating integration is enabled
Establishes a temperature range around the
I 07 Activation band calculated temperature to determine which 0 ÷ 10 °C 4
generator to switch on
TECHNICAL DATA
I 08 Not used
Displays the hours of operation performed by the
I 11 Outdoor unit operating hours
outdoor unit
Indoor central heating unit Displays the hours of operation by the indoor
I 12
hours of operation central heating unit
Indoor D.H.W. unit hours of Displays the hours of operation by the indoor unit
I 13
operation in DHW
80
Maintenance menu.
Accessing this menu, the unit goes into stand-by. By selecting
every single parameter, you can activate a specific function for
each load.
INSTALLER
Parameter Customised
Description Range Default
ID value
Heat pump circuit circulator Establishes the circulator speed linked to the heat
M 02 0 - 100% 0
speed pump circuit
DHW-CH-
M 03 Heat generator 3-way circuit Moves the 3-way motor from system to DHW DHW
MD
M 04 Cooling 3-way Moves the cooling circuit 3-way motor OFF - ON OFF
Heat generator circuit circulator Establishes the circulator speed linked to the heat
M 06 0 - 100% 0
speed generator
M 07 Not used Not used
M 08 Zone 1 outdoor circulator pump Enables the zone 1 outdoor circulator pump OFF - ON OFF
M 09 Zone 2 outdoor circulator pump Enables the zone 2 outdoor circulator pump OFF - ON OFF
OFF - OPEN
M 10 Mixer zone 2 Establishes zone 2 mixing valve positioning OFF
- CLOSE
USER
M 11 DHW electrical resistance Enables the DHW integrated electrical resistance OFF - ON OFF
Central heating electrical Enables the room central heating integrated
M 12 OFF - ON OFF
resistance electrical resistance
M 13 Dehumidifier zone 1 Enables the dehumidifier in zone 1 OFF - ON OFF
M 14 Dehumidifier zone 2 Enables the dehumidifier in zone 2 OFF - ON OFF
M 15 Relay 1 Enables relay 1 on the 3-relay board OFF - ON OFF
M 16 Relay 2 Enables relay 2 on the 3-relay board OFF - ON OFF
M 17 Relay 3 Enables relay 3 on the 3-relay board OFF - ON OFF
M 18 Zone 3 outdoor circulator pump Enables the zone 3 outdoor circulator OFF - ON OFF
MAINTENANCE TECHNICIAN
M 19 Dehumidifier zone 3 Enables the dehumidifier in zone 3 OFF - ON OFF
OFF - OPEN
M 20 Zone 3 mixing valve Establishes zone 3 mixing valve positioning OFF
-CLOSE
TECHNICAL DATA
81
3.13 "CHIMNEY SWEEP” FUNCTION 3.17 PHOTOVOLTAIC FUNCTION
If activated, this function makes the indoor unit work at an adju- Should the photovoltaic contact (contact “S 39” Fig. 8) be closed,
stable power. In this state all adjustments are excluded and only the minimum outdoor temperature is temporarily set at -15°C.
the safety thermostat and the limit thermostat remain active.
INSTALLER
The indoor unit has a function that starts the pump at least once The voltage output is active when the appliance is in Air-conditio-
every 24 hours for the duration of 30 seconds in order to reduce the ning mode.
risk of the pump becoming blocked due to prolonged inactivity.
82
3.22 SCREED HEATER FUNCTION 3.23 SOLAR PANELS COUPLING FUNCTION
The indoor unit is equipped with a function to perform the ther- The indoor unit is prepared to receive pre-heated water from a sy-
mal shock on new radiant panel systems, as required by the appli- stem of solar panels up to a maximum temperature of 65°C. In any
cable standard. case, it is always necessary to install a mixing valve on the hydrau-
INSTALLER
Contact the manufacturer of the radiant panels for the lic circuit upstream of the indoor unit, on the cold water inlet.
thermal shock characteristics and its correct execution. To optimise the operation, the solar inlet probe kit is available on
request (see wiring diagram Fig. 8).
To enable the use of the probe it is necessary to set parameter
T03>0.
To be able to activate the function there must be no re- This kit allows you to connect a probe on the domestic cold water
mote control connected, while in case of system divided inlet pipe of the indoor unit, to prevent unnecessary start-ups in
into zones it must be properly connected, both hydrauli- systems with water heating through solar systems or alternative
cally and electrically. sources.
The indoor unit will not turn on if the inlet water is sufficiently hot.
The active zone pumps are those with ongoing requests, made via We recommend setting parameter T03 (solar delay timer) at a
the room thermostat input. time sufficient to let the water inside the D.H.W. circuit upstream
The function is activated from indoor unit in stand-by by pressing of the indoor unit drain.
and holding the buttons “Reset” and “Mode” for more than 5 se- The greater the distance from the storage tank, the longer wait
conds (Fig. 62). time will have to be set.
The standard function lasts in total 7 days - 3 days at the lowest With these adjustments made, when a domestic withdrawal is re-
temperature set and 4 days at the highest temperature set (Fig. 8). quested, once the time set on parameter “T03” has passed, if the
USER
Duration can be changed by changing the value of parameters "T water entering the indoor unit is at a temperature that is equal to or
22" and "T24". greater than that set, the indoor unit will not turn on.
After activating the function, the lower set (range 20 ÷ 45 °C de- In order for the indoor unit to work properly, the tempe-
fault = 25 °C) and the higher set (range 25 ÷ 55 °C default = 45 °C) rature selected on the mixing valve must be 5°C higher
appear in sequence. than the temperature selected on the indoor unit control
The temperature is selected by means of the buttons “+” and “-” of panel.
the system side ( ) and confirmed by pressing the button
“Mode”.
The display now shows the countdown of days alternated with the
current flow temperature, as well as the normal operating symbols
MAINTENANCE TECHNICIAN
of the indoor unit.
In case of failure, the function is suspended and will resume when
normal operating conditions are reset from the point where it was
interrupted.
Key (Fig. 63):
In case of power failure, the function is suspended.
(A) - Upper set
When the time expires, the indoor unit automatically goes back to
(B) - Lower set
“Stand-by” mode, the function can also be stopped by pressing the
(C) - Days
button “Mode”.
(A)
TECHNICAL DATA
(B)
(C)
62 63
83
3.24 DEHUMIDIFICATION FUNCTION 3.27 PUFFER IN PREHEATING FUNCTION
Dehumidification can be performed according to two different In the presence of an inertial storage tank heated by other sources
types of devices: of heat, following a central heating demand, it is possible to pre-
1) Humidistat; vent the generators from being activated by using hot water co-
INSTALLER
84
3.30 GENERATOR MANAGEMENT
Central heating mode
Following a request in room heating mode, the electronic system
decides, depending on the external temperature and set point
INSTALLER
configured, whether to activate heat pump mode, or (with “free-
zing” external temperatures) the heat generator (Fig. 64).
The management electronics select which heat source to be used
according to the combination of “I” family parameters. The heat
generator could also switch on also when external conditions are
favourable; this can take place after a time proportional to the pa-
rameter.
Alternatively, you can also set a fixed switching outdoor tempera-
ture (manual mode in the parameter "I 05" setting the temperatu-
re with "I 06"). The D.H.W. demand is met by the heat generator,
even simultaneously with a system demand which is met by the
heat pump mode.
To protect the appliance the heat pump might start up
even if the appliance is in the heat generator exclusive
operating zone.
USER
Operation in central heating mode
Y
Max
MAINTENANCE TECHNICIAN
65 °C A
B C
Min X
-15 Te1 Te2 25
64
Key (Fig. 64): The Te1 and Te2 values are determined by the logic of the product
TECHNICAL DATA
X - Outside temperature board (Setting manual mode "I 05" = "MA" the value of "Te1" is the
Y - Central heating setting same as "I 06" and the value of "Te2" is the same as "I 06" + 5 °C).
A - Exclusive heat generator operation * = The heat pump will then restart, thereby creating an alterna-
B - Heat pump operation (if after activation time the set tempe- ting mechanism between the two generators.
rature is not reached the heat generator starts)*
C - Heat pump operation (if after activation time multiplied by 2
the set temperature is not reached the heat generator star-
ts)*
85
3.31 CASING REMOVAL Front panel (Fig. 66)
- Open the protection door (e1) pulling it towards you.
To facilitate hydronic module maintenance, the casing can be
- Remove the cover caps (c) and loosen screws (d).
completely removed as follows:
- Pull the front panel (e) towards you and release it from its lower
Lower grid (Fig. 65) seat.
INSTALLER
4
3
3
2
USER
d e
c
2
4 5
a
d
c
a b
1 e1
1
65 66
MAINTENANCE TECHNICIAN
8 8
7
TECHNICAL DATA
6 7
6
g f
67
86
Control panel (Fig. 68) Sides (Fig. 70)
- Press the hooks on the side of the control panel (i). - Unscrew the side (k) fastening screws (l).
- Tilt the control panel (i) towards you. - Remove the sides by extracting them from their rear seat (Ref.
The control panel (i) can rotate until the support cord (j) is com- X).
pletely extended.
INSTALLER
- If the left side needs to be removed, unhook the support cord (j)
from the control panel and proceed as follows.
9 10
USER
i
11
j
9
MAINTENANCE TECHNICIAN
9
68 69
Rif. X
12 X
X
l
X
X
12
13 X
X l
X
TECHNICAL DATA
12 X 13
k X
12
70
87
4 TECHNICAL DATA
door unit.
* Central heating mode status: heat exchanger water inlet/re- *** Central heating mode status: inlet/remains at 47 °C/55 °C, out-
mains at 30 °C/35 °C, outdoor air temperature 7 °C db/6 °C wb. door air temperature 7 °C db/6 °C wb. Performance in compliance
Performance in compliance with EN 14511. with EN 14511.
Cooling mode status: heat exchanger water inlet/remains at 23
°C/18 °C, outdoor air temperature 35 °C. Performance in com-
pliance with EN 14511.
* Central heating mode status: heat exchanger water inlet/re-
mains at 40 °C/45 °C, outdoor air temperature 7 °C db/6 °C wb.
Cooling mode status: heat exchanger water inlet/remains at 12
°C/7 °C, outdoor air temperature 35 °C. Performance in com-
pliance with EN 14511.
TECHNICAL DATA
88
Indoor unit data
INSTALLER
Dimensions (Width x Height x Depth) mm 440x787x400
Maximum heating temperature °C 83
Adjustable central heating temperature (max operating
°C -25.. 35
field)
Cooling adjustable temperature (max. operating field) °C 10-40
Domestic hot water adjustable temperature °C 10-65
Domestic hot water adjustable temperature with DHW
°C -
integration resistance (optional)
Water content l 3,1
Expansion vessel volume l 8
Expansion vessel pre-charged pressure bar 1
Hydraulic circuit max. operating pressure bar 3
Head available with 1000 l/h flow rate kPa (m c.a.) 54,0(5,5)
USER
Maximum relay current for zone pumps (inductive
A 1
load)
EEI value - ≤ 0.20 - Det. 3
Equipment electrical system protection - IPX4D
Ambient operating temperature range °C -5 ÷ +40
Ambient operating temperature range with antifreeze
°C -15 ÷ +40
kit (optional)
MAINTENANCE TECHNICIAN
Outdoor unit - Ambient operating temperature range.
89
4.2 MAGIS COMBO 4 V2 PRODUCT FICHE (IN
COMPLIANCE WITH REGULATION
811/2013)
For proper installation of the device, refer to chapter 1 of this bo-
INSTALLER
4
5 5 5
53 5
53
MAINTENANCE TECHNICIAN
58
71 72
Annual energy consumption for the central heating mode (QHE) kWh\year 2768 2243 1125
Room central heating seasonal efficiency ( ηs) ηs % 140 181 235
Nominal heat output kW 4,00 5,00 5,00
TECHNICAL DATA
Annual energy consumption for the central heating mode (QHE) kWh\year 3982 3163 1753
Room central heating seasonal efficiency ( ηs) ηs % 96 128 150
Nominal heat output kW 4,00 5,00 5,00
90
Average temperature table (47/55) average zones
INSTALLER
Water/water heat pump no With additional central heating device no
Brine/water heat pump no Mixed central heating device with heat pump: no
The parameters are declared for average temperature application, except for low temperature heat pumps. The parameters for low temperature heat
pumps are declared for low temperature application
The parameters are declared for average climatic conditions
Element Symbol Value Unit Element Symbol Value Unit
Pnomi- Room central heating seasonal energy
Nominal heat output 5,00 kW ηs 128 %
nale efficiency
Central heating capacity declared with a partial load and indoor Performance coefficient declared with indoor temperature equivalent to
temperature equivalent to 20°C and outdoor temperature Tj 20°C and outdoor temperature Tj
Tj = – 7 °C Pdh 4,4 kW Tj = – 7 °C COPd 2,10 -
Tj = + 2 °C Pdh 2,7 kW Tj = + 2 °C COPd 3,10 -
Tj = + 7 °C Pdh 1,7 kW Tj = + 7 °C COPd 4,46 -
Tj = + 12 °C Pdh 1,9 kW Tj = + 12 °C COPd 5,72 -
Tj = bivalent temperature Pdh 4,4 kW Tj = bivalent temperature COPd 2,10 -
USER
Tj = operating limit temperature Pdh 4,2 kW Tj = operating limit temperature COPd 1,51 -
for air/water heat pumps: for air/water heat pumps:
Tj = – 15 °C Pdh - kW Tj = – 15 °C COPd - -
(se TOL < – 20 °C) (se TOL < – 20 °C)
for air/water heat pumps: Operating limit
Bivalent temperature T biv -7 °C TOL -10 °C
temperature
COPcyc
Central heating capacity cycle intervals Pcych - kW Cycle intervals efficiency o - -
PERcyc
Degradation coefficient Cdh 0,9 - Water heating temperature operating limit WTOL - °C
MAINTENANCE TECHNICIAN
Different mode of energy consumption from the active mode Additional heating appliance
OFF mode POFF 0,000 kW Nominal heat output Psup 24,00 kW
Thermostat mode off PTO 0,010 kW
Standby mode PSB 0,010 kW Type of energy supply voltage fossil fuel
Guard heating mode PCK 0,000 kW
Other items
For air/water heat pumps: nominal air
Capacity control VARIABLE - 2400 m3\h
output to outside
Indoor/outdoor sound level LWA 58 dB For water or brine/water heat pumps:
kWh nominal flow of brine or water, outdoor heat - - m3\h
Annual energy consumption QHE 3163
or GJ exchanger
For mixed central heating appliances with a heat pump
Stated load profile - Water central heating energy efficiency ηwh - %
Daily electrical power consumption Qelec - kWh Daily fuel consumption Qfuel - kWh
Annual energy consumption AEC - kWh Annual fuel consumption AFC - GJ
Contact information Immergas S.p.A. via Cisa Ligure n.95
TECHNICAL DATA
91
4.3 MAGIS COMBO 6 V2 PRODUCT FICHE (IN
COMPLIANCE WITH REGULATION
811/2013)
For proper installation of the device, refer to chapter 1 of this bo-
INSTALLER
5
6 6 6
6 6
MAINTENANCE TECHNICIAN
53 6
53
73 74
Annual energy consumption for the central heating mode (QHE) kWh\year 3305 2692 1254
Room central heating seasonal efficiency ( ηs) ηs % 140 181 236
TECHNICAL DATA
Annual energy consumption for the central heating mode (QHE) kWh\year 4941 3727 1945
Room central heating seasonal efficiency ( ηs) ηs % 93 130 151
Nominal heat output kW 4,80 6,00 5,60
92
Average temperature table (47/55) average zones
INSTALLER
Water/water heat pump no With additional central heating device no
Brine/water heat pump no Mixed central heating device with heat pump: no
The parameters are declared for average temperature application, except for low temperature heat pumps. The parameters for low temperature heat
pumps are declared for low temperature application
The parameters are declared for average climatic conditions
Element Symbol Value Unit Element Symbol Value Unit
Pnomi- Room central heating seasonal energy
Nominal heat output 6,00 kW ηs 130 %
nale efficiency
Central heating capacity declared with a partial load and indoor Performance coefficient declared with indoor temperature equivalent to
temperature equivalent to 20°C and outdoor temperature Tj 20°C and outdoor temperature Tj
Tj = – 7 °C Pdh 5,3 kW Tj = – 7 °C COPd 2,00 -
Tj = + 2 °C Pdh 3,2 kW Tj = + 2 °C COPd 3,23 -
Tj = + 7 °C Pdh 2,1 kW Tj = + 7 °C COPd 4,47 -
Tj = + 12 °C Pdh 1,9 kW Tj = + 12 °C COPd 5,82 -
Tj = bivalent temperature Pdh 5,3 kW Tj = bivalent temperature COPd 2,00 -
USER
Tj = operating limit temperature Pdh 5,0 kW Tj = operating limit temperature COPd 1,80 -
for air/water heat pumps: for air/water heat pumps:
Tj = – 15 °C Pdh - kW Tj = – 15 °C COPd - -
(se TOL < – 20 °C) (se TOL < – 20 °C)
for air/water heat pumps: Operating limit
Bivalent temperature T biv -7 °C TOL -10 °C
temperature
COPcyc
Central heating capacity cycle intervals Pcych - kW Cycle intervals efficiency o - -
PERcyc
Degradation coefficient Cdh 0,9 - Water heating temperature operating limit WTOL - °C
MAINTENANCE TECHNICIAN
Different mode of energy consumption from the active mode Additional heating appliance
OFF mode POFF 0,000 kW Nominal heat output Psup 24,00 kW
Thermostat mode off PTO 0,010 kW
Standby mode PSB 0,010 kW Type of energy supply voltage fossil fuel
Guard heating mode PCK 0,000 kW
Other items
For air/water heat pumps: nominal air
Capacity control VARIABLE - 2580 m3\h
output to outside
Indoor/outdoor sound level LWA 60 dB For water or brine/water heat pumps:
kWh nominal flow of brine or water, outdoor heat - - m3\h
Annual energy consumption QHE 3727
or GJ exchanger
For mixed central heating appliances with a heat pump
Stated load profile - Water central heating energy efficiency ηwh - %
Daily electrical power consumption Qelec - kWh Daily fuel consumption Qfuel - kWh
Annual energy consumption AEC - kWh Annual fuel consumption AFC - GJ
Contact information Immergas S.p.A. via Cisa Ligure n.95
TECHNICAL DATA
93
4.4 MAGIS COMBO 9 V2 PRODUCT FICHE (IN
COMPLIANCE WITH REGULATION
811/2013)
For proper installation of the device, refer to chapter 1 of this bo-
INSTALLER
7 8 7
8 9 8
8 9 8
53 53
MAINTENANCE TECHNICIAN
75 76
Annual energy consumption for the central heating mode (QHE) kWh\year 5243 3949 1855
Room central heating seasonal efficiency ( ηs) ηs % 138 176 242
Nominal heat output kW 8,00 9,00 9,00
TECHNICAL DATA
Annual energy consumption for the central heating mode (QHE) kWh\year 7223 5054 2709
Room central heating seasonal efficiency ( ηs) ηs % 93 128 155
Nominal heat output kW 7,00 8,00 8,00
94
Average temperature table (47/55) average zones
INSTALLER
Water/water heat pump no With additional central heating device no
Brine/water heat pump no Mixed central heating device with heat pump: no
The parameters are declared for average temperature application, except for low temperature heat pumps. The parameters for low temperature heat
pumps are declared for low temperature application
The parameters are declared for average climatic conditions
Element Symbol Value Unit Element Symbol Value Unit
Pnomi- Room central heating seasonal energy
Nominal heat output 8,00 kW ηs 128 %
nale efficiency
Central heating capacity declared with a partial load and indoor Performance coefficient declared with indoor temperature equivalent to
temperature equivalent to 20°C and outdoor temperature Tj 20°C and outdoor temperature Tj
Tj = – 7 °C Pdh 7,1 kW Tj = – 7 °C COPd 1,76 -
Tj = + 2 °C Pdh 4,3 kW Tj = + 2 °C COPd 3,32 -
Tj = + 7 °C Pdh 2,8 kW Tj = + 7 °C COPd 4,62 -
Tj = + 12 °C Pdh 2,6 kW Tj = + 12 °C COPd 5,88 -
Tj = bivalent temperature Pdh 7,1 kW Tj = bivalent temperature COPd 1,76 -
USER
Tj = operating limit temperature Pdh 4,9 kW Tj = operating limit temperature COPd 1,35 -
for air/water heat pumps: for air/water heat pumps:
Tj = – 15 °C Pdh - kW Tj = – 15 °C COPd - -
(se TOL < – 20 °C) (se TOL < – 20 °C)
for air/water heat pumps: Operating limit
Bivalent temperature T biv -7 °C TOL -10 °C
temperature
COPcyc
Central heating capacity cycle intervals Pcych - kW Cycle intervals efficiency o - -
PERcyc
Degradation coefficient Cdh 0,9 - Water heating temperature operating limit WTOL - °C
MAINTENANCE TECHNICIAN
Different mode of energy consumption from the active mode Additional heating appliance
OFF mode POFF 0,000 kW Nominal heat output Psup 24,00 kW
Thermostat mode off PTO 0,010 kW
Standby mode PSB 0,010 kW Type of energy supply voltage fossil fuel
Guard heating mode PCK 0,000 kW
Other items
For air/water heat pumps: nominal air
Capacity control VARIABLE - 3960 m3\h
output to outside
Indoor/outdoor sound level LWA 64 dB For water or brine/water heat pumps:
kWh nominal flow of brine or water, outdoor heat - - m3\h
Annual energy consumption QHE 5054
or GJ exchanger
For mixed central heating appliances with a heat pump
Stated load profile - Water central heating energy efficiency ηwh - %
Daily electrical power consumption Qelec - kWh Daily fuel consumption Qfuel - kWh
Annual energy consumption AEC - kWh Annual fuel consumption AFC - GJ
Contact information Immergas S.p.A. via Cisa Ligure n.95
TECHNICAL DATA
95
4.5 PARAMETERS FOR FILLING IN THE The remaining values must be obtained from the technical data
PACKAGE FICHE sheets of the products used to make up the assembly (e.g. solar de-
vices, integration indoor unit, temperature controllers).
Should you wish to install an assembly starting from the Magis
Use sheet (Fig. 78) “assemblies” related to the central heating fun-
Combo V2 package, use the package fiche shown in (Fig. Parame-
ction (e.g.: heat pump + temperature controller).
INSTALLER
Facsimile for filling in the package fiche for room central heating systems.
‘I’ %
USER
Supplementary boiler
(%)
From boiler board
( - ‘I’ ) x “II” = - %
MAINTENANCE TECHNICIAN
Solar contribution
From the board of the solar device tank
A* = 0.95, A = 0.91,
Dimensions of the Volume of the
manifold (in %) B = 0.86, C = 0.83,
manifold (in m2) tank (in m3)
D-G = 0.81
climate conditions %
climate conditions
G F E D C B A A+ A++ A+++
< 30 % 30 % 34 % 36 % 75 % 82 % 90 % 98 % 125 %150 %
TECHNICAL DATA
the heat loss in the distribution system and the size of the products compared to the size and
features of the building.
77
96
Parameters to fill in the low temperature package fiche (30/35) Parameters to fill in the average temperature package fiche
(47/55)
Magis Combo 4 V2
Magis Combo 4 V2
Parameter Colder zones Average zones Hotter zones
INSTALLER
Parameter Colder zones Average zones Hotter zones
"I" 140 181 235
"II" * * * "I" 96 128 150
"III" 6,68 5,35 5,35 "II" * * *
"IV" 2,61 2,09 2,09 "III" 6,68 5,35 5,35
"IV" 2,61 2,09 2,09
Magis Combo 6 V2
Magis Combo 6 V2
Parameter Colder zones Average zones Hotter zones
Parameter Colder zones Average zones Hotter zones
"I" 140 181 236
"II" * * * "I" 93 130 151
"III" 5,57 4,45 4,77 "II" * * *
"IV" 2,18 1,74 1,87 "III" 5,57 4,45 4,77
"IV" 2,18 1,74 1,87
USER
Magis Combo 9 V2
Magis Combo 9 V2
Parameter Colder zones Average zones Hotter zones
Parameter Colder zones Average zones Hotter zones
"I" 138 176 242
"II" * * * "I" 93 128 155
"III" 3,34 2,97 2,97 "II" * * *
"IV" 1,31 1,16 1,16 "III" 3,82 3,34 3,34
MAINTENANCE TECHNICIAN
"IV" 1,49 1,31 1,31
* to be determined according to Regulation 811/2013 and transient
calculation methods as per Notice of the European Community * to be determined according to Regulation 811/2013 and transient
no. 207/2014. calculation methods as per Notice of the European Community
no. 207/2014.
TECHNICAL DATA
97
Room central heating system package fiche.
____ %
INSTALLER
Supplementary boiler
(%)
From boiler board
( - ______ ) x _____ = - %
Solar contribution
USER
climate conditions
G F E D C B A A+ A++ A+++
< 30 % 30 % 34 % 36 % 75 % 82 % 90 % 98 % 125 %150 %
% %
TECHNICAL DATA
the heat loss in the distribution system and the size of the products compared to the size and
features of the building.
78
98
99
Cod. 1.045257ENG - rev. ST.005156/000 - 12/20
This instruction booklet is made
of ecological paper.
immergas.com
Immergas S.p.A.
42041 Brescello (RE) - Italy
Tel. 0522.689011
Fax 0522.680617