Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

FMDS0834

Download as pdf or txt
Download as pdf or txt
You are on page 1of 119

FM Global

Property Loss Prevention Data Sheets 8-34


July 2017
Interim Revision July 2023
Page 1 of 119

PROTECTION FOR AUTOMATIC STORAGE AND RETRIEVAL SYSTEMS

Table of Contents
Page

1.0 SCOPE ..................................................................................................................................................... 7


1.1 Changes ............................................................................................................................................ 7
1.2 How to Use this Data Sheet .............................................................................................................. 7
2.0 LOSS PREVENTION RECOMMENDATIONS ........................................................................................ 9
2.1 General Recommendations for All Automatic Storage and Retrieval Systems ................................ 9
2.1.1 FM Approved Equipment, Materials, and Services ................................................................. 9
2.1.2 Construction and Location ...................................................................................................... 9
2.1.3 Occupancy ............................................................................................................................... 9
2.1.4 Protection .............................................................................................................................. 10
2.1.5 Final Extinguishment ............................................................................................................. 12
2.1.6 Electrical Systems for ASRS Storage Arrangements ............................................................ 13
2.1.7 Control Systems for ASRS Storage Arrangements .............................................................. 13
2.2 Horizontal-Loading Automatic Storage and Retrieval Systems (ASRS) Using Small
Containers or Small Trays ............................................................................................................... 14
2.2.1 General Guidelines for Horizontal-Loading ASRS Storage Arrangements ........................... 14
2.2.2 Protection of Horizontal-Loading Shuttle ASRS Storage Arrangements Where
Closed-Top, Noncombustible, Solid-Walled Containers, or FM Approved,
Non-Propagating, Open-Top Containers are Being Used .................................................... 20
2.2.3 Protection of Horizontal-Loading Shuttle ASRS Storage Arrangements Using (1)
Closed-Top Combustible Containers, or (2) Products that Do Not Collect Water that are
Stored on Trays .................................................................................................................... 20
2.2.4 Protection of Horizontal-Loading Shuttle ASRS Storage Arrangements Where
Open-Top, Combustible Containers are Being Used ............................................................ 48
2.2.5 Protection of Horizontal-Loading, Mini-Load ASRS Storage Arrangements Where
Closed-Top, Noncombustible, Solid-Walled Containers, or FM Approved,
Non-Propagating, Open-Top Containers are Being Used .................................................... 61
2.2.6 Protection of Horizontal-Loading Mini-Load ASRS Storage Arrangements Using (1)
Closed-Top Combustible Containers, or (2) Products that Do Not Collect Water that are
Stored on Trays .................................................................................................................... 61
2.2.7 Protection of Horizontal-Loading, Mini-Load ASRS Storage Arrangements Where
Open-Top, Combustible Containers are Being Used ............................................................ 75
2.3 Top-Loading Automatic Storage and Retrieval Systems (TL-ASRS) .............................................. 88
2.3.1 General Guidelines for TL-ASRS Storage Arrangements ..................................................... 88
2.3.2 Drainage ................................................................................................................................ 88
2.3.3 Robots and Robot Holding Areas ......................................................................................... 88
2.3.4 Fire Detection ........................................................................................................................ 88
2.3.5 Protection of Noncombustible Solid-Walled Containers ....................................................... 89
2.3.6 Protection of Combustible Solid-Walled Containers ............................................................. 92
2.3.7 Protection of Non-Solid-Walled Containers ......................................................................... 103
2.4 Vertically Enclosed Automatic Storage and Retrieval System Storage Arrangements ................ 107
2.4.1 General ................................................................................................................................ 107
2.4.2 Storage Trays for Vertically Enclosed Storage Units .......................................................... 107
2.4.3 Protection Options for Vertically Enclosed Storage Units ................................................... 108
2.4.4 Final Extinguishment – Small Hose Connection Stations ................................................... 110
3.0 SUPPORT FOR RECOMMENDATIONS ............................................................................................ 110
3.1 Description of Automatic Storage and Retrieval Systems (ASRS) .............................................. 110

©2017-2023 Factory Mutual Insurance Company. All rights reserved. No part of this document may be reproduced,
stored in a retrieval system, or transmitted, in whole or in part, in any form or by any means, electronic, mechanical,
photocopying, recording, or otherwise, without written permission of Factory Mutual Insurance Company.
8-34 Protection for Automatic Storage
Page 2 FM Global Property Loss Prevention Data Sheets

3.1.1 Mini-Load ASRS Storage Arrangements ............................................................................. 110


3.1.2 Top-Loading ASRS Storage Arrangements ......................................................................... 111
3.1.3 Vertically Enclosed ASRS Storage Arrangements .............................................................. 114
3.2 Loss History of Automatic Storage and Retrieval Systems (ASRS) ............................................. 114
4.0 REFERENCES .................................................................................................................................... 115
4.1 FM Global .................................................................................................................................... 115
4.2 Other .............................................................................................................................................. 115
APPENDIX A GLOSSARY OF TERMS ..................................................................................................... 115
APPENDIX B DOCUMENT REVISION HISTORY .................................................................................... 117

List of Figures
Fig. 1. Summarized guidance on how to navigate Data Sheet 8-34 ............................................................. 8
Fig. 2. Example of a shuttle horizontal-loading ASRS ................................................................................. 14
Fig. 3. Example of a mini-load ASRS having angle irons that support the trays and/or containers ........... 15
Fig. 4. Horizontal IRAS Arrangement for Closed-Top Combustible Containers, or Storage Trays
within a Shuttle ASRS Where Rack Row Depths Do Not Exceed 3 ft (0.9 m) per Table 14
and the Maximum Allowable Horizontal Spacing is 2-1/2 ft (0.75 m) .............................................. 32
Fig. 5. Horizontal IRAS Arrangement for Closed-Top Combustible Containers, or Storage on Trays
within a Shuttle ASRS Where Rack Row Depths Do Not Exceed 3 ft (0.9 m) per Table 14,
and the Maximum Allowable Horizontal Spacing is 5 ft (1.5 m) ...................................................... 32
Fig. 6. Horizontal IRAS Arrangement for Closed-Top Combustible Containers, or Storage on Trays
within a Shuttle ASRS Where Rack Row Depths Do Not Exceed 6 ft (1.8 m) per Table 14
and the Maximum Allowable Horizontal Spacing is 2-1/2 ft (0.75 m) .............................................. 32
Fig. 7. Horizontal IRAS Arrangement for Closed-Top Combustible Containers, or Storage on Trays
within a Shuttle ASRS Where Rack Row Depths Do Not Exceed 6 ft (1.8 m) per Table 14
and the Maximum Allowable Horizontal Spacing is 5 ft (1.5 m) ...................................................... 33
Fig. 8. Horizontal IRAS Arrangement Without Face Sprinklers for Closed-Top Combustible
Containers, or Storage on Trays within a Shuttle ASRS Where Rack Row Depths Do Not
Exceed 6 ft (1.8 m) per Table 14 and the Maximum Allowable Horizontal Spacing is 5 ft (1.5 m) . 33
Fig. 9. Horizontal IRAS Arrangement for Closed-Top Combustible Containers, or Storage on Trays
within a Shuttle ASRS Where the Overall Rack Depths Do Not Exceed 14 ft (4.3 m) per
Table 14 and the Maximum Allowable Horizontal Spacing is 2-1/2 ft (0.75 m) ............................... 33
Fig. 10. Horizontal IRAS Arrangement for Closed-Top Combustible Containers, or Storage on Trays
within a Shuttle ASRS Where the Overall Rack Depths Do Not Exceed 14 ft (4.3 m) per
Table 14 and the Maximum Allowable Horizontal Spacing is 5 ft (1.5 m) ..................................... 34
Fig. 11. Horizontal IRAS Arrangement for Closed-Top Combustible Containers, or Storage on Trays
within a Shuttle ASRS Where the Overall Rack Depths Do Not Exceed 9 ft (2.7 m) per Table
14 and the Maximum Allowable Horizontal Spacing is 5 ft (1.5 m) ............................................... 34
Fig. 12. Horizontal IRAS Arrangement for Closed-Top Combustible Containers, or Storage on Trays
within a Shuttle ASRS Where Rack Row Depths Exceed 6 ft (1.8 m) in Depth per Table 14
and the Maximum Allowable Horizontal Spacing is 2-1/2 ft (0.75 m) ............................................ 35
Fig. 13. Horizontal IRAS Arrangement for Closed-Top Combustible Containers, or Storage on Trays
within a Shuttle ASRS Where Rack Row Depths Exceed 6 ft (1.8 m) in Depth per Table 14
and the Maximum Allowable Horizontal Spacing is 5 ft (1.5 m) .................................................... 35
Fig. 14. Horizontal IRAS Arrangement for Open-Top Combustible Containers within a Shuttle ASRS
Where Rack Row Depths Do Not Exceed 3 ft (0.9 m) and the Maximum Horizontal Spacing
is 2-1/2 ft (0.75 m) per Table 22 .................................................................................................... 51
Fig. 15. Horizontal IRAS Arrangement for Open-Top Combustible Containers within a Shuttle ASRS
Where Rack Row Depths Do Not Exceed 3 ft (0.9 m) and the Maximum Horizontal Spacing
is 2 ft (0.60 m) per Table 22 ........................................................................................................... 51
Fig. 16. Horizontal IRAS Arrangement for Open-Top Combustible Containers within a Shuttle ASRS
Where Rack Row Depths Do Not Exceed 3 ft (0.9 m) and the Maximum Horizontal Spacing is
4 ft (1.2 m) per Table 22 ................................................................................................................ 51
Fig. 17. Horizontal IRAS Arrangement for Open-Top Combustible Containers within a Shuttle ASRS
Where Rack Row Depths Do Not Exceed 6 ft (1.8 m) and the Maximum Horizontal Spacing
is 2-1/2 ft (0.75 m) per Table 22 .................................................................................................... 52

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


Protection for Automatic Storage 8-34
FM Global Property Loss Prevention Data Sheets Page 3

Fig. 18. Horizontal IRAS Arrangement for Open-Top Combustible Containers within a Shuttle ASRS
Where Rack Row Depths Do Not Exceed 6 ft (1.8 m) and the Maximum Horizontal Spacing
is 2 ft (0.60 m) per Table 22 ........................................................................................................... 52
Fig. 19. Horizontal IRAS Arrangement for Open-Top Combustible Containers within a Shuttle ASRS
Where Rack Row Depths Do Not Exceed 6 ft (1.8 m) and the Maximum Horizontal Spacing is
4 ft (1.2 m) per Table 22 ................................................................................................................ 53
Fig. 20. Horizontal IRAS Arrangement for Open-Top Combustible Containers within a Shuttle ASRS
Where the Overall Rack Depths Do Not Exceed 14 ft (4.3 m) and the Maximum Horizontal
Spacing is 2-1/2 ft (0.75 m) per Table 22 ...................................................................................... 53
Fig. 21. Horizontal IRAS Arrangement for Open-Top Combustible Containers within a Shuttle ASRS
Where the Overall Rack Depths Do Not Exceed 14 ft (4.3 m) and the Maximum Horizontal
Spacing is 2 ft (0.60 m) per Table 22 ............................................................................................ 54
Fig. 22. Horizontal IRAS Arrangement for Open-Top Combustible Containers within a Shuttle ASRS
Where the Overall Rack Depths Do Not Exceed 14 ft (4.3 m) and the Maximum Horizontal
Spacing is 4 ft (1.2 m) per Table 22 .............................................................................................. 54
Fig. 23. Horizontal IRAS Arrangement for Open-Top Combustible Containers within a Shuttle ASRS
Where Rack Row Depths Exceed 6 ft (1.8 m) and the Maximum Horizontal Spacing is 2-1/2 ft
(0.75 m) per Table 22 ..................................................................................................................... 55
Fig. 24. Horizontal IRAS Arrangement for Open-Top Combustible Containers within a Shuttle ASRS
Where Rack Row Depths Exceed 6 ft (1.8 m) and the Maximum Horizontal Spacing is 2 ft
(0.60 m) per Table 22 ..................................................................................................................... 55
Fig. 25. Horizontal IRAS Arrangement for Open-Top Combustible Containers within a Shuttle ASRS
Where Rack Row Depths Exceed 6 ft (1.8 m) and the Maximum Horizontal Spacing is 4 ft
(1.2 m) per Table 22 ....................................................................................................................... 56
Fig. 26. Horizontal IRAS Arrangement for Closed-Top Combustible Containers, or Storage on Trays
within a Mini-Load ASRS Where Rack Row Depths Do Not Exceed 3 ft (0.9 m) and the
Maximum Horizontal Spacing is 2-1/2 ft (0.75 m) per Table 31 .................................................... 67
Fig. 27. Horizontal IRAS Arrangement for Closed-Top Combustible Containers, or Storage on Trays
within a Mini-Load ASRS Where Rack Row Depths Do Not Exceed 3 ft (0.9 m) and the
Maximum Horizontal Spacing is 5 ft (1.5 m) per Table 31 ............................................................ 67
Fig. 28. Horizontal IRAS Arrangement for Closed-Top Combustible Containers, or Storage on Trays
within a Mini-Load ASRS Where Rack Row Depths Do Not Exceed 6 ft (1.8 m) and the
Maximum Horizontal Spacing is 2-1/2 ft (0.75 m) per Table 31 .................................................... 67
Fig. 29. Horizontal IRAS Arrangement for Closed-Top Combustible Containers, or Storage on Trays
within a Mini-Load ASRS Where Rack Row Depths Do Not Exceed 6 ft (1.8 m) and the
Maximum Horizontal Spacing is 5 ft (1.5 m) per Table 31 ............................................................ 68
Fig. 30. Horizontal IRAS Arrangement for Closed-Top Combustible Containers, or Storage on Trays
within a Mini-Load ASRS Where the Overall Rack Depths Do Not Exceed 14 ft (4.3 m)
and the Maximum Horizontal Spacing is 2-1/2 ft
(0.75 m) per Table 31 ..................................................................................................................... 68
Fig. 31. Horizontal IRAS Arrangement for Closed-Top Combustible Containers, or Storage on Trays
within a Mini-Load ASRS Where the Overall Rack Depths Do Not Exceed 14 ft (4.3 m)
and the Maximum Horizontal Spacing is 5 ft (1.5 m) per Table 31 ............................................... 69
Fig. 32. Horizontal IRAS Arrangement for Closed-Top Combustible Containers, or Storage on Trays
within a Mini-Load ASRS Where Rack Row Depths Exceed 6 ft (1.8 m) in Depth and the
Maximum Horizontal Spacing is 2-1/2 ft (0.75 m) per Table 31 .................................................... 69
Fig. 33 Horizontal IRAS Arrangement for Closed-Top Combustible Containers, or Storage on Trays
within a Mini-Load ASRS Where Rack Row Depths Exceed 6 ft (1.8 m) in Depth and the
Maximum Horizontal Spacing is 5 ft (1.5 m) per Table 31 ............................................................. 70
Fig. 34. Horizontal IRAS Arrangement for Open-Top Combustible Containers within a Mini-Load ASRS
Where Rack Row Depths Do Not Exceed 3 ft (0.9 m) and the Maximum Horizontal Spacing is
2-1/2 ft (0.75 m) per Table 39 ........................................................................................................ 79
Fig. 35. Horizontal IRAS Arrangement for Open-Top Combustible Containers within a Mini-Load ASRS
Where Rack Row Depths Do Not Exceed 3 ft (0.9 m) and the Maximum Horizontal Spacing
is 2 ft (0.60 m) per Table 39 ........................................................................................................... 79
Fig. 36. Horizontal IRAS Arrangement for Open-Top Combustible Containers within a Mini-Load ASRS
Where Rack Row Depths Do Not Exceed 3 ft (0.9 m) and the Maximum Horizontal Spacing is
4 ft (1.2 m) per Table 39 ................................................................................................................ 79

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


8-34 Protection for Automatic Storage
Page 4 FM Global Property Loss Prevention Data Sheets

Fig. 37. Horizontal IRAS Arrangement for Open-Top Combustible Containers within a Mini-Load ASRS
Where Rack Row Depths Do Not Exceed 6 ft (1.8 m) and the Maximum Horizontal Spacing
is 2-1/2 ft (0.75 m) per Table 39 .................................................................................................... 80
Fig. 38. Horizontal IRAS Arrangement for Open-Top Combustible Containers within a Mini-Load ASRS
Where Rack Row Depths Do Not Exceed 6 ft (1.8 m) and the Maximum Horizontal Spacing
is 2 ft (0.60 m) per Table 39 ........................................................................................................... 80
Fig. 39. Horizontal IRAS Arrangement for Open-Top Combustible Containers within a Mini-Load ASRS
Where Rack Row Depths Do Not Exceed 6 ft (1.8 m) and the Maximum Horizontal Spacing is
4 ft (1.2 m) per Table 39 ................................................................................................................ 81
Fig. 40. Horizontal IRAS Arrangement for Open-Top Combustible Containers within a Mini-Load ASRS
Where the Overall Rack Depths Do Not Exceed 14 ft (4.3 m) and the Maximum Horizontal
Spacing is 2-1/2 ft (0.75 m) per Table 39 ...................................................................................... 81
Fig. 41. Horizontal IRAS Arrangement for Open-Top Combustible Containers within a Mini-Load ASRS
Where the Overall Rack Depths Do Not Exceed 14 ft (4.3 m) and the Maximum Horizontal
Spacing is 2 ft (0.60 m) per Table 39 ............................................................................................ 81
Fig. 42. Horizontal IRAS for Open-Top Combustible Containers within a Mini-Load ASRS Where the
Overall Rack Depths Do Not Exceed 14 ft (4.3 m) and the Maximum Horizontal Spacing is
4 ft (1.2 m) per Table 39 ................................................................................................................ 82
Fig. 43. Horizontal IRAS Arrangement for Open-Top Combustible Containers within a Mini-Load ASRS
Where Rack Row Depths Exceed 6 ft (1.8 m) and the Maximum Horizontal Spacing is
2-1/2 ft (0.75 m) per Table 39 ........................................................................................................ 82
Fig. 44. Horizontal IRAS Arrangement for Open-Top Combustible Containers within a Mini-Load ASRS
Where Rack Row Depths Exceed 6 ft (1.8 m) and the Maximum Horizontal Spacing is
2 ft (0.60 m) per Table 39 .............................................................................................................. 82
Fig. 45. Horizontal IRAS Arrangement for Open-Top Combustible Containers within a Mini-Load ASRS
Where Rack Row Depths Exceed 6 ft (1.8 m) and the Maximum Horizontal Spacing is 4 ft
(1.2 m) per Table 39 ....................................................................................................................... 83
Fig. 46. Examples of Potential Robot Holding Areas .................................................................................. 89
Fig. 47. Examples of a TL-ASRS arrangement showing maximum 100 ft (30 m) depth in one direction . 93
Fig. 48. Example of solid-floored elevated mezzanine levels when span of TL-ASRS exceeds 100 ft
(30 m) in each direction ................................................................................................................... 94
Fig. 49. Examples showing the use of vertical barriers within a TL-ASRS arrangement ........................... 96
Fig. 50. Example of TL-ASRS arrangement protected by fixed-in-place monitor nozzles installed
on the mezzanines .......................................................................................................................... 97
Fig. 51. Example of TL-ASRS arrangement protected by fixed-in-place monitor nozzles installed
at ceiling level .................................................................................................................................. 98
Fig. 52. Establishing storage subdivisions within TL-ASRS ...................................................................... 104
Fig. 53. Positioning of void spaces under ceiling sprinklers ...................................................................... 104
Fig. 54. Example of a TL-ASRS arrangement showing maximum 100 ft (30 m) depth in one direction .. 106
Fig. 55. Example of solid-floored elevated mezzanine levels when span of TL-ASRS exceeds 100 ft
(30 m) in each direction ................................................................................................................. 107
Fig. 56. Example of a vertically enclosed ASRS storage unit .................................................................... 108
Fig. 57. Example of open-top plastic containers in mini-load ASRS storage arrangementi ..................... 111
Fig. 58. Example of an empty mini-load ASRS storage arrangement where rack uprights are about 2
to 3 in. (50 to 75 mm) wide and about 2 ft (0.6 m) horizontally apart ......................................... 112
Fig. 59. Example of rack-supported ASRS storage arrangement ............................................................. 113
Fig. 60. Example of motorized automated picking robot in a mini-load ASRS storage
arrangement with open-top unexpanded plastic containers ........................................................ 113
Fig. A-1. ASRS rack row depth .................................................................................................................. 115

List of Tables
Table 1. Determining Number of Sprinklers per Branch Line for Ceiling Sprinkler System Hydraulic Design . 12
Table 2. Hose Demand Design and Water Supply Duration ........................................................................ 19
Table 3. Determining Which Ceiling Sprinkler Protection Table to Use for the Protection of
Closed-Top Combustible Containers or Storage Trays .................................................................. 21
Table 4. Ceiling-Level Protection Guidelines on a Wet System for Class 1, 2, and 3 Commodities
Stored Directly on the Support Rails of a Shuttle ASRS; No. of AS @ psi (bar) .......................... 22

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


Protection for Automatic Storage 8-34
FM Global Property Loss Prevention Data Sheets Page 5

Table 5. Ceiling-Level Protection Guidelines on a Dry System for Class 1, 2, and 3 Commodities
Stored Directly on the Support Rails of a Shuttle ASRS; No. of AS @ psi (bar) .......................... 23
Table 6. Ceiling-Level Protection Guidelines on a Wet System for Class 4 and Cartoned Unexpanded
Plastic Commodities Stored Directly on the Support Rails of a Shuttle ASRS; No. of AS @
psi (bar) ........................................................................................................................................... 24
Table 7. Ceiling-Level Protection Guidelines on a Dry System for Class 4 and Cartoned Unexpanded
Plastic Commodities Stored Directly on the Support Rails of a Shuttle ASRS; No. of AS @
psi (bar) ........................................................................................................................................... 25
Table 9. Ceiling-Level Protection Guidelines on a Dry System for Cartoned Expanded Plastic
Commodities Stored Directly on the Support Rails of a Shuttle ASRS; No. of AS @ psi (bar) .... 27
Table 11. Ceiling-Level Protection Guidelines on a Dry System for Uncartoned Unexpanded
Plastic Commodities Stored in a Shuttle ASRS; No. of AS @ psi (bar) ...................................... 29
Table 12. Ceiling-Level Protection Guidelines on a Wet System for Uncartoned Expanded
Plastic Commodities Stored in a Shuttle ASRS; No. of AS @ psi (bar) ...................................... 30
Table 13. Ceiling-Level Protection Guidelines on a Dry System for Uncartoned Expanded Plastic
Commodities Stored in a Shuttle ASRS; No. of AS @ psi (bar) .................................................. 31
Table 14. Recommended Horizontal In-Rack Sprinkler (i.e., IRAS) Arrangements for Closed-Top
Combustible Containers, or Storage on Trays ............................................................................ 31
Table 15. Wet, In-Rack Sprinkler System Designs for the Protection of Closed-Top, Combustible
Containers Stored in a Shuttle ASRS ........................................................................................... 37
Table 15. Wet, In-Rack Sprinkler System Designs for the Protection of Closed-Top, Combustible
Containers Stored in a Shuttle ASRS (continued) ....................................................................... 38
Table 15. Wet, In-Rack Sprinkler System Designs for the Protection of Closed-Top, Combustible
Containers Stored in a Shuttle ASRS (continue) ......................................................................... 39
Table 15. Wet, In-Rack Sprinkler System Designs for the Protection of Closed-Top, Combustible
Containers Stored in a Shuttle ASRS (continued) ....................................................................... 40
Table 16. Dry, In-Rack Sprinkler Designs for the Protection of Closed-Top, Combustible Containers
Stored in a Shuttle ASRS ............................................................................................................. 43
Table 17. Determining the Applicable Protection Table and Ceiling Height for Ceiling Sprinkler Designs
when Wet Ceiling-Level Sprinkler Systems are Supplemented with In-Rack Sprinklers to
Protect Closed-Top Combustible Containers, or Storage on Trays in a Shuttle ASRS .............. 45
Table 17. Determining the Applicable Protection Table and Ceiling Height for Ceiling Sprinkler Designs
when Wet Ceiling-Level Sprinkler Systems are Supplemented with In-Rack Sprinklers to
Protect Closed-Top, Combustible Containers Stored Directly on the Shuttle Rack’s
Horizontal Supporting Rails, or Non-Open Top Storage Maintained on Trays in a Shuttle
ASRS (continued) ......................................................................................................................... 46
Table 18. Determining the Applicable Protection Table and Ceiling Height for Ceiling Sprinkler Designs
when Dry Ceiling-Level Sprinkler Systems are Supplemented with In-Rack Sprinklers to
Protect Closed-Top Combustible Containers, or Storage on Trays in a Shuttle ASRS .............. 47
Table 19. Determining Which Ceiling Sprinkler Protection Table to Use for the Protection of
Horizontal-Loading Shuttle ASRS Storage Arrangements Where Open-Top,
Combustible Containers are Being Used ..................................................................................... 48
Table 20. Wet Sprinkler System Ceiling-Level Protection Guidelines for Open-Top, Combustible
Container Storage up to a Maximum of 10 ft (3.0 m) in a Shuttle ASRS; No. of AS @
psi (bar) ......................................................................................................................................... 49
Table 21. Dry Sprinkler System Ceiling-Level Protection Guidelines for Open-Top, Combustible
Container Storage up to a Maximum of 10 ft (3.0 m) in a Shuttle ASRS; No. of AS @ psi (bar) . 50
Table 22. Recommended Horizontal In-Rack Sprinkler Arrangements for the Protection of
Open-Top, Combustible Containers in a Shuttle ASRS ............................................................... 50
Table 23. Vertical In-Rack Sprinkler Locations and In-Rack Sprinkler Designs for the Protection of
Open-Top, Combustible Containers Stored in a Shuttle System ................................................. 57
Table 23. Vertical In-Rack Sprinkler Locations and In-Rack Sprinkler Designs for the Protection of
Open-Top, Combustible Containers Stored in a Shuttle System (continued) .............................. 58
Table 24. Wet System Ceiling-Level Sprinkler Protection Guidelines, in Combination with In-Rack
Sprinklers, for the Protection of Open-Top, Combustible Containers in a Shuttle ASRS;
No. of AS @ psi (bar) ................................................................................................................... 60
Table 25. Dry System Ceiling-Level Sprinkler Protection Guidelines, in Combination with In-Rack
Sprinklers, for the Protection of Open-Top, Combustible Containers in a Shuttle ASRS;
No. of AS @ psi (bar) ................................................................................................................... 61

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


8-34 Protection for Automatic Storage
Page 6 FM Global Property Loss Prevention Data Sheets

Table 26. Determining Which Ceiling Sprinkler Protection Table to Use for the Protection of
Closed-Top Combustible Containers, or Storage on Trays in a Mini-Load ASRS ...................... 62
Table 27. Ceiling-Level Protection Guidelines on a Wet System for Class 1 - 4, Cartoned Plastics,
and Uncartoned Unexpanded Plastic Commodities Stored in a Mini-Load ASRS; No. of AS
@ psi (bar) .................................................................................................................................... 63
Table 28. Ceiling-Level Protection Guidelines on a Dry System for Class 1 - 4, Cartoned
Plastics, and Uncartoned Unexpanded Plastic Commodities Stored in a Mini-Load ASRS;
No. of AS @ psi (bar) ................................................................................................................... 64
Table 29. Ceiling-Level Protection Guidelines on a Wet System for Uncartoned Expanded
Plastic Commodities Stored in a Mini-Load Type ASRS; No. of AS @ psi (bar) ......................... 65
Table 30. Ceiling-Level Protection Guidelines on a Dry System for Uncartoned Expanded Plastic
Commodities Stored in a Mini-Load ASRS; No. of AS @ psi (bar) ............................................. 66
Table 31. Recommended Horizontal In-Rack Sprinkler (i.e., IRAS) Arrangements for Closed-Top
Combustible Containers, or Storage on Trays in a Mini-Load ASRS ......................................... 66
Table 32. Wet, In-Rack Sprinkler Designs for the Protection of Closed-Top, Combustible Containers
Stored in a Mini-Load Type ASRS ................................................................................................ 71
Table 33. Dry, In-Rack Sprinkler Designs for the Protection of Closed-Top, Combustible Containers
Stored in a Mini-Load Type ASRS ................................................................................................ 72
Table 34. Determining the Applicable Protection Table and Ceiling Height for Ceiling Sprinkler Designs
when Wet Ceiling-Level Sprinkler Systems are Supplemented with In-Rack Sprinklers to
Protect Closed-Top Combustible Containers, or Storage on Trays in a Mini-Load Type ASRS . 74
Table 35. Determining the Applicable Protection Table and Ceiling Height for Ceiling Sprinkler Designs
when Dry Ceiling-Level Sprinkler Systems are Supplemented with In-Rack Sprinklers to
Protect Closed-Top Combustible Containers, or Storage on Trays in a Mini-Load Type ASRS . 75
Table 36. Determining Which Ceiling Sprinkler Protection Table to Use for the Protection of
Horizontal-Loading, Mini-Load ASRS Storage Arrangements Where Open-Top,
Combustible Containers are Being Used ..................................................................................... 76
Table 37. Ceiling-Level Protection Guidelines on a Wet System for Storage in Open-Top,
Combustible Containers in a Mini-Load ASRS up to a Maximum of 10 ft (3.0 m);
No. of AS @ psi (bar) ................................................................................................................... 77
Table 38. Ceiling-Level Protection Guidelines on a Dry System for Storage in Open-Top,
Combustible Containers in a Mini-Load ASRS up to a Maximum of 5 ft (1.5 m);
No. of AS @ psi (bar) ................................................................................................................... 78
Table 39. Recommended Horizontal In-Rack Sprinkler Arrangements for the Protection of
Open-Top, Combustible Containers in a Mini-Load ASRS ........................................................... 78
Table 40. Vertical In-Rack Sprinkler Locations and In-Rack Sprinkler Designs for the Protection of
Open-Top, Combustible Containers Stored in a Mini-Load Type System .................................... 84
Table 40. Vertical In-Rack Sprinkler Locations and In-Rack Sprinkler Designs for the Protection of
Open-Top, Combustible Containers Stored in a Mini-Load Type System (continued) ................ 85
Table 41. Wet System Ceiling-Level Sprinkler Protection Guidelines, in Combination with In-Rack
Sprinklers, for the Protection of Open-Top Combustible Containers in a Mini-Load ASRS;
No. of AS @ psi (bar) ................................................................................................................... 87
Table 42. Dry System Ceiling-Level Sprinkler Protection Guidelines, in Combination with In-Rack
Sprinklers, for the Protection of Open-Top Combustible Containers in a Mini-Load ASRS;
No. of AS @ psi (bar) ................................................................................................................... 88
Table 43. Ceiling-Level Protection Guidelines for TL-ASRS Storage Arrangements Using Open-Top
Solid-Walled Noncombustible Containers ..................................................................................... 91
Table 44. Alternative Ceiling-Level Sprinkler Protection Options for Top-Loading ASRS
Arrangements that Address Final Extinguishment; Maximum Storage Height up to and
Including 20 ft (6.1 m) ................................................................................................................... 94
Table 45. Ceiling-Level Protection Guidelines for TL-ASRS Storage Arrangements Using Open-Top
Solid-Walled Unexpanded Plastic Containers; Storage Height up to and Including 20 ft (6.1 m) . 101
Table 46. Ceiling-Level Protection Guidelines for TL-ASRS Storage Arrangements Using Open-Top
Solid-Walled Unexpanded Plastic Containers; Storage Height in Excess of 20 ft (6.1 m) ........ 102
Table 47. Sprinkler Pressure Requirements for the Protection of Vertically Enclosed ASRS Storage
Units Over 25 ft (7.6 m) and up to 55 ft (16.8 m) Tall ................................................................ 109

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


Protection for Automatic Storage 8-34
FM Global Property Loss Prevention Data Sheets Page 7

1.0 SCOPE
This data sheet provides loss prevention guidelines specific to Class 1, 2, 3, 4, and plastic commodities in
small containers or on small trays for the following:
A. Horizontal-loading (i.e., mini-load and shuttle type) automatic storage and retrieval systems (HL-ASRS)
B. Top-loading automatic storage and retrieval systems (TL-ASRS)
C. Vertically enclosed automatic storage and retrieval systems
See Appendix A for definitions of these storage arrangements.
Note that the following automatic storage and retrieval system (ASRS) conditions are outside the scope of
this data sheet and currently do not have any known protection options:
• ASRS arrangements that use expanded plastic trays and/or containers
• ASRS arrangements that use non-solid (gridded) bottom, open-top containers in either a horizontal-
loading or top-loading ASRS storage arrangement
• Commodity hazards higher than plastics, such as Level 2 and 3 aerosols, ignitable liquids, flammable
gasses, and other special hazards

1.1 Changes
July 2023. Interim revision. Significant changes include the following:
A. The scope of this data sheet was modified to indicate that it applies to material handling of small
containers and small trays; (see Appendix A for a definition of these terms).
B. The generic term "horizontal-loading" has been introduced to address both mini-load and shuttle type
(i.e., shuttle) ASRS storage arrangements.
C. Previously, this data sheet referenced FM Global Property Loss Prevention Data Sheet 8-9, Storage
of Class 1, 2, 3, 4, and Plastic Commodities, for protection guidelines of (1) closed-top containers stored
directly on the rail supports of a shuttle ASRS and (2) closed-top storage maintained on trays within a
shuttle or mini-load type ASRS. Those protection guidelines have now been added to this data sheet, so
the user can obtain the needed recommendations here.
D. The guidelines for adequately vented open-top containers used in horizontal-loading ASRS storage
arrangements have been removed from this data sheet based on recent successful test results with
solid-walled, open-top plastic containers.
E. Guidelines for open-top noncombustible containers in a horizontal-loading ASRS storage arrangement
have been temporarily removed. Once an Approval Standard for FM Approved “non-propagating
containers” specific to horizontal-loading ASRS arrangements is developed, protection guidelines for these
containers will be reintroduced into the data sheet.

1.2 How to Use this Data Sheet


As with any FM Global property loss prevention data sheet, a complete and comprehensive understanding
of the information in this document can only be achieved by a thorough review of its contents. However,
the following flowchart in Figure 1 is intended to assist the user with an understanding of how best to navigate
this data sheet for the specific automatic storage and retrieval system (ASRS) being installed.

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


8-34 Protection for Automatic Storage
Page 8 FM Global Property Loss Prevention Data Sheets

Review Section 1.0


(Scope) of Data Sheet
8-34 to determine if this
data sheet is applicable

See the general


guidelines in Section 2.1

Will the
ASRS storage
arrangement be Yes See the protection
Vertically Enclosed guidelines in Section 2.4
per Appendix A?

No

Will the Will the Will the See Sections 2.3.1 through
ASRS storage Yes containers be containers be No 2.3.4 for general
No
arrangement be solid-walled and solid-walled and recommendations. See the
Top-Loading (see noncombustible? combustible? protection guidelines in
Appendix A )? Section 2.3.7

Yes Yes
No
See Sections 2.3.1 through See Sections 2.3.1 through
2.3.4 for general 2.3.4 for general
recommendations. See the recommendations. See the
protection guidelines in protection guidelines in
Section 2.3.5 Section 2.3.6

Will the Will the


Will the See Sections 2.2.1
ASRS storage Will the
Yes ASRS storage containers be for general
arrangement be Yes No containers be No
arrangement be noncombustible closed- recommendations. See the
Horizontal-Loading (see combustible
Shuttle type (see top or non- protection guidelines in
Appendix A)? closed-top?
Appendix A)? propogating? Section 2.2.4

No No
Yes Yes

Will the
The ASRS arrangement is ASRS storage See Sections 2.2.1 See Sections 2.2.1
No for general for general
outside the scope of Data arrangement be
Sheet 8-34 Mini-Load type (see recommendations. See the recommendations. See the
Appendix A)? protection guidelines in protection guidelines in
Section 2.2.2 Section 2.2.3

Yes

Will the See Sections 2.2.1


containers be Will the
No containers be No for general
noncombustible closed- recommendations. See the
top or non- combustible
closed-top? protection guidelines in
propogating? Section 2.2.7

Yes Yes

See Sections 2.2.1 See Sections 2.2.1


for general for general
recommendations. See the recommendations. See the
protection guidelines in protection guidelines in
Section 2.2.5 Section 2.2.6

Fig. 1. Summarized guidance on how to navigate Data Sheet 8-34

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


Protection for Automatic Storage 8-34
FM Global Property Loss Prevention Data Sheets Page 9

2.0 LOSS PREVENTION RECOMMENDATIONS

2.1 General Recommendations for All Automatic Storage and Retrieval Systems
Coordinate the facility’s construction, occupancy, and protection details in the planning stages so they are
all compatible.

2.1.1 FM Approved Equipment, Materials, and Services


Use FM Approved equipment, materials, and services whenever they are applicable and available. For a
list of products that are FM Approved, see the Approval Guide, an online resource of FM Approvals.

2.1.2 Construction and Location


2.1.2.1 Construct storage facilities in accordance with the relevant FM Global property loss prevention data
sheets (i.e., data sheets). See the 1-series data sheets for guidelines relevant to the construction features
of most storage facilities.
2.1.2.2 Adhere to the recommendations in the relevant data sheet to ensure the construction features of
the facility are compatible with the ceiling-level storage sprinkler being used.

2.1.2.3 Building Structural Steel Protection


Adhering to the design guidelines in this data sheet eliminates the need for both building column and overhead
steel protection.
2.1.2.4 See Data Sheet 2-0, Installation Guidelines for Automatic Sprinklers, for guidelines specific to:
• Heat and smoke vents
• Airflow from ventilation systems
• Draft curtains

2.1.2.5 Additional Weight Due to Collection of Sprinkler Discharge


When open-top, combustible containers are maintained in a horizontal-loading ASRS storage arrangement,
account for the potential increased weight load on the storage structure and supporting floor from the
collection of sprinkler discharge within the containers. Assume that:
1. One-half of the containers stored vertically below the in-rack sprinklers will be filled with water, and
2. One-half of the containers stored vertically below the in-rack sprinklers will be consumed during a fire
event

2.1.3 Occupancy

2.1.3.1 Commodity Hazard


2.1.3.1.1 Use FM Global Property Loss Prevention Data Sheet (i.e., Data Sheet) 8-1, Commodity
Classification, to determine the commodity classification of the products being maintained within the ASRS
storage arrangement.
2.1.3.1.2 Protection guidelines offered in this data sheet are limited to commodities that are indicated by
Data Sheet 8-1 as being Class 1, 2, 3, 4, or plastic.
2.1.3.1.3 Design the sprinkler protection for the ASRS storage arrangement using the most severe commodity
hazard present, taking into consideration both the products being stored and the composition of the product
material handling (i.e., trays and/or containers).

2.1.3.2 Clearances Between Storage and Sprinkler Deflectors


2.1.3.2.1 Maintain a minimum 3 ft (0.9 m) clearance between the top of the storage and the deflectors of
standard-coverage ceiling-level sprinklers.
2.1.3.2.2 Maintain a minimum 5 ft (1.5 m) clearance between the top of the storage and the deflectors of
extended-coverage, ceiling-level sprinklers.

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


8-34 Protection for Automatic Storage
Page 10 FM Global Property Loss Prevention Data Sheets

2.1.3.2.3 Maintain a minimum 4 in. (100 mm) clearance between the top of the storage and the deflectors
of in-rack sprinklers.

2.1.4 Protection
2.1.4.1 In addition to the recommendations in this data sheet, follow the sprinkler, ceiling and in-rack,
installation guidelines indicated for Storage sprinklers in FM Global Property Loss Prevention Data Sheet
(i.e., Data Sheet) 2-0, Installation Guidelines for Automatic Sprinklers, including recommendations specific
to:
1. Temperature rating of the ceiling sprinklers based on the ambient temperature of the protected area
2. Linear and area spacing of the ceiling sprinklers based on unobstructed or obstructed ceiling
construction
3. Mixing of ceiling sprinklers on the same sprinkler system
4. Obstruction of ceiling sprinkler discharge
2.1.4.2 For facilities located in earthquake-prone regions, refer to FM Global Property Loss Prevention Data
Sheet (i.e., Data Sheet) 2-8, Earthquake Protection for Water-Based Fire Protection Systems.
2.1.4.3 In addition, see Data Sheet 3-0, Hydraulics of Fire Protection Systems, for guidelines on calculating
the sprinkler designs obtained from this data sheet.
2.1.4.4 The units for sprinkler K-factor used throughout this data sheet are gpm/psi0.5 ([L/min]/bar0.5).

2.1.4.5 Ceiling Sprinkler Designs

2.1.4.5.1 Ceiling-Level Sprinkler Protection Design Format


The ceiling-level sprinkler system design options provided in the protection tables of this data sheet use a
design format based on an indicated number of operating sprinklers at a given minimum operating pressure
from the hydraulically most remote sprinkler. Do not interpolate or adjust the protection values obtained from
these tables.

2.1.4.5.2 Minimum Ceiling Design Area


2.1.4.5.2.1 Unobstructed Ceiling Construction
The minimum design area (i.e., the number of sprinklers in the design multiplied by the spacing of the
sprinklers) is as follows:
1. 576 ft2 (53.5 m2) when the number of sprinklers in the indicated design is 9
2. 640 ft2 (59.5 m2) when the number of sprinklers in the indicated design is 10
3. 768 ft2 (71.3 m2) when the number of sprinklers in the indicated design is 12 or more
Increase the number of sprinklers in the ceiling design, when applicable, to meet or exceed the required
minimum design area.
2.1.4.5.2.2 Obstructed Ceiling Construction
When ceiling sprinklers can be installed under the ceiling structural members in the presence of obstructed
ceiling construction, follow the guidelines for minimum ceiling design area indicated in Section 2.1.4.5.2.1.
When ceiling sprinklers are required in every channel created by obstructed ceiling construction, and the linear
and area sprinkler spacing is in accordance with Data Sheet 2-0, a minimum ceiling design area is not
applicable.

2.1.4.5.3 Non-ASRS Areas Adjacent to an ASRS Storage Area


2.1.4.5.3.1 Provide separation between the ASRS storage area and any adjacent non-ASRS areas by either
full-height walls or minimum 2 ft (0.6 m) deep draft curtains.
2.1.4.5.3.2 Separation between the ASRS storage area and any adjacent non-ASRS areas, as recommended
in Section 2.1.4.5.3.1, is not needed when:
1. Both the ASRS storage area and the adjacent non-ASRS area require the same ceiling-level sprinkler
design and use the same RTI rated sprinklers, or

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


Protection for Automatic Storage 8-34
FM Global Property Loss Prevention Data Sheets Page 11

2. The ceiling-level sprinkler system designs are different, but the ceiling-level sprinkler system with the
higher demand has been extended one sprinkler or one branch line, depending on how the sprinkler
piping is arranged, into the area requiring the lower ceiling-level sprinkler demand. Note that if the
ceiling-level sprinklers protecting the two adjacent areas have different RTI ratings (i.e., quick-response
and standard-response), then a minimum 2 ft (0.6 m) deep draft curtain is needed as separation between
these two sprinkler types.

2.1.4.5.4 Number of Sprinklers per Branch Line for Ceiling-Level Sprinkler System Calculations
Instead of using the calculation methods in Data Sheet 3-0, use Table 1 to determine the number of
ceiling-level sprinklers needed per branch line for hydraulic calculation purposes. Use Data Sheet 3-0 for
all other means of determining the flow and pressure required for a sprinkler system.
When using Equation 1 or Equation 2, if the result is not a whole number, round to the nearest whole number
using normal rounding methods (i.e., round down for 0.49 or less; round up for 0.50 and greater).
Equation 1: Number of Sprinklers per Branch Line in Design Area, Ceiling Slope ≤ 1 in 12 = (1.2 / SAVG)
x SQRT ([Number of Sprinklers in Ceiling Design x SAVG x LAVG])
Where:
SAVG = Average on-line spacing used within the calculated sprinkler system.
LAVG = Average between line spacing used within the calculated sprinkler system.
Equation 2: Number of Sprinklers per Branch Line in Demand Area, 1 in 12 < Ceiling Slope
≤ 2 in 12 = (1.4 / SAVG) x SQRT ([Number of Sprinklers in Ceiling Design x SAVG x LAVG])
Where:
SAVG = Average on-line spacing used within the calculated sprinkler system.
LAVG = Average between line spacing used within the calculated sprinkler system.
Note that the average distance is indicated for Equations 1 and 2 to account for fluctuations in spacing due
to the presence of ceiling structural members or similar potential obstructions. The most common sprinkler
spacing can be used when sprinkler spacing values are generally consistent.

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


8-34 Protection for Automatic Storage
Page 12 FM Global Property Loss Prevention Data Sheets

Table 1. Determining Number of Sprinklers per Branch Line for Ceiling Sprinkler System Hydraulic Design
Number of
Number. of Ceiling Sprinkler Sprinklers per
Sprinklers in Ceiling Sprinkler Maximum Ceiling Ceiling On-Line Spacing, Branch Line in
Ceiling Design Type Slope Construction Type ft (m) Design Area
6 Extended 2 in 12 Any Any 3
Coverage 4 in 12 Unobstructed Any See Equation 1
Obstructed Any See Equation 2
8 Extended 1 in 12 Any ≤ 12 (3.7) 4
Coverage > 12 (3.7) 3
2 in 12 Any Any 4
4 in 12 Unobstructed Any See Equation 1
Obstructed Any See Equation 2
9 Standard 2 in 12 Any Any 3
Coverage 4 in 12 Unobstructed Any See Equation 1
Obstructed Any See Equation 2
Extended 2 in 12 Any Any 4
Coverage 4 in 12 Unobstructed Any See Equation 1
Obstructed Any See Equation 2
10 Standard 1 in 12 Any < 10 (3.0) 4
Coverage ≥ 10 (3.0) 3
2 in 12 Any Any 4
4 in 12 Unobstructed Any See Equation 1
Obstructed Any See Equation 2
Extended 1 in 12 Any Any See Equation 1
Coverage 2 in 12 Any Any See Equation 2
4 in 12 Unobstructed Any See Equation 1
Obstructed Any See Equation 2
12 Standard 2 in 12 Any Any 4
Coverage 4 in 12 Unobstructed Any See Equation 1
Obstructed Any See Equation 2
Extended 1 in 12 Any Any See Equation 1
Coverage 2 in 12 Any Any See Equation 2
4 in 12 Unobstructed Any See Equation 1
Obstructed Any See Equation 2
> 12 Any 1 in 12 Any Any See Equation 1
2 in 12 Any Any See Equation 2
4 in 12 Unobstructed Any See Equation 1
Obstructed Any See Equation 2

2.1.5 Final Extinguishment


Establish a pre-incident plan in cooperation with the local fire service and your local FM Global Engineering
Operations Center to address a means of achieving final extinguishment of a fire originating within the ASRS
storage array. See FM Global Property Loss Prevention Data Sheet (i.e., Data Sheet) 10-1, Pre-Incident
Planning, for general guidelines related to a pre-incident plan.
At a minimum, consider the following:
1. How access will be achieved to a fire anywhere within the storage array
2. How will the storage array be disassembled, if required, and what equipment will be needed to get to
the seat of the fire
3. How many storage containers may be removed from the storage array to get to the seat of the fire
and where they will be placed during this process
4. What resources will be needed and how they can be implemented for restoration of the storage array
to minimize business interruption

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


Protection for Automatic Storage 8-34
FM Global Property Loss Prevention Data Sheets Page 13

5. Identifying and providing operational guidance on the specialized firefighting equipment, such as hose
station connections, fixed-in-place monitors, visible or infrared cameras, remote monitor nozzle steering
mechanisms, etc., installed at the facility for protection of the ASRS storage array
In addition, free training is available on the FM Global Fire Service Learning Network in multiple languages
at www.fmglobalfireserviceresources.com. The network provides several different training modules and has
a module specific to pre-incident planning at a facility with a TL-ASRS. The training is free and available to the
fire service, facility owners/managers or anyone that would like to learn more about fire protection systems
and firefighting operations in sprinklered properties.

2.1.6 Electrical Systems for ASRS Storage Arrangements


2.1.6.1 Design the robot’s overall electrical system in accordance with the applicable international electrical
safety standard, such as IEC 60950-1.
2.1.6.2 If lithium ion batteries are used in the robot’s system, use batteries that have passed a thermal runaway
propagation test in accordance with IEC 62619 or equivalent industrial standard.
2.1.6.3 Follow the manufacturer’s periodic maintenance and testing program of the battery charging contacts,
looking for any potential signs of arcing. If such a program is not offered by the manufacturer, perform weekly
visual inspections. Increase the frequency if operating history indicates arcing is a possibility. Take corrective
action when signs of arcing start to appear.
2.1.6.4 Replace the battery-charging contacts when they approach the end of cycle life to remove the potential
for overheating.
2.1.6.5 At a minimum, on an annual basis conduct infrared scanning for all ASRS electrical components while
the system is in normal operation including, when applicable, the charging operation.
2.1.6.6 Establish an alarm management program in accordance with FM Global Property Loss Prevention
Data Sheet 10-8, Operators. Prioritize critical alarms including a robot power board hardware failure alarm as
well as robot battery management system temperature and state of health indicators, when the robots are
battery powered.
2.1.6.7 For robots powered by batteries, establish a robot battery system replacement program for aged
batteries. Review the battery replacement program regularly and include, at a minimum, the following
components:
1. Regular monitoring of the state of health of batteries which is generally available through the BMS,
particularly for li-ion batteries.
2. The OEM design life expectancy of the batteries. This will be based on the number of years and the
number of cycles that the battery is expected to perform adequately. After this point, the batteries will
have performance deterioration (i.e., capacity decrease) due to aging condition, the likelihood of
thermal runaway will also increase, and the batteries should be replaced.
3. When replacing a Li-ion battery with a different chemistry, consult with the battery and equipment OEM
to ensure matching of performance such as voltage between the charger and the level required by
the Li-ion battery packs and their battery management systems. Do not replace lead-acid batteries with
Li-ion batteries.
2.1.6.8 Implement a Management of Change (MOC) procedure in accordance with FM Global Property Loss
Prevention Data Sheet 7-43, Process Safety, for any major changes planned for the ASRS electrical system.

2.1.7 Control Systems for ASRS Storage Arrangements


To minimize potential property damage and business interruption due to loss of the control systems
responsible for the operation of the ASRS storage system, review and implement the recommendations
outlined in FM Global Property Loss Prevention Data Sheet 7-110, Industrial Control Systems, that are
applicable to the facility’s ASRS.

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


8-34 Protection for Automatic Storage
Page 14 FM Global Property Loss Prevention Data Sheets

2.2 Horizontal-Loading Automatic Storage and Retrieval Systems (ASRS) Using Small Containers or
Small Trays

2.2.1 General Guidelines for Horizontal-Loading ASRS Storage Arrangements

2.2.1.1 How to Use Section 2.2


2.2.1.1.1 Section 2.2 provides protection guidelines for horizontal-loading automatic storage and retrieval
systems (ASRS). This type of storage arrangement is further subdivided into two specific types of ASRS
storage: (1) a shuttle ASRS, and (2) a mini-load type ASRS. A shuttle ASRS has horizontal supports that do
not interfere with the flow of sprinkler discharge into the transverse flue space. See Figure 2 for an example
of this storage arrangement. The shuttle system shown in Figure 2 uses metal slats for the support of the
trays or containers; other shuttle systems use mesh type or similar shelving to support the trays or containers.
A mini-load type ASRS uses angle irons, or similar guides, for the support of trays or containers within the
rack structure. See Figure 3 for an example of this storage arrangement.

Fig. 2. Example of a shuttle horizontal-loading ASRS

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


Protection for Automatic Storage 8-34
FM Global Property Loss Prevention Data Sheets Page 15

Fig. 3. Example of a mini-load ASRS having angle irons that support the trays and/or containers

2.2.1.1.2 What differentiates horizontal-loading ASRS storage arrangements from traditional pallet load
storage rack arrangements include:
1. Rack uprights in a mini-load type ASRS that are typically only about 2 ft (0.6 m) apart horizontally as
opposed to about 8 ft (2.4 m),
2. Tiers that are only about 12 to 18 in. (300 to 450 mm) high as opposed to about 5 ft (1.5 m),
3. Product handling that consists of 18 in. x 24 in. (450 mm x 600 mm) trays or open-top containers as
opposed to 4 ft x 4 ft (1.2 m x 1.2 m) pallets,
4. Material handling support in mini-load type ASRS storage arrangements which is accomplished by angle
irons as opposed to horizontal supports.
While bullet points 1 through 4 create a unique storage arrangement for horizontal-loading ASRS, it is the
presence of the angle irons within the mini-load ASRS rack structure that has a major impact on the protection
requirements for them. This is because the angle irons divert most of the sprinkler discharge out to the face
of the rack, thus limiting the amount of sprinkler discharge that can be distributed into the transverse flue
spaces of the storage rack.
2.2.1.1.3 To determine recommendations for the protection of products stored within a horizontal-loading
ASRS storage array, use the following generic procedure:
1. See Section 2.1 for general recommendations that apply to all ASRS storage arrangements, including
construction, occupancy, protection and final extinguishment.
2. See Section 2.2.1 for additional general recommendations that apply specifically to horizontal-loading
ASRS storage arrangements.
3. Obtain the specific protection guidelines from the applicable section for the type of storage being
maintained within the horizontal-loading ASRS.
The applicable sections are as follows:
A. Section 2.2.2 for shuttle ASRS arrangements that use closed-top, noncombustible, solid-walled
containers or FM Approved, non-propagating, open-top containers.

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


8-34 Protection for Automatic Storage
Page 16 FM Global Property Loss Prevention Data Sheets

B. Section 2.2.3 for shuttle ASRS arrangements that use either (1) products that do not collect water that
are stored on trays, or (2) closed-top combustible containers.
C. Section 2.2.4 for shuttle ASRS arrangements that use either (1) open-top cardboard or unexpanded
plastic containers, or (2) products or containers that collect water and are stored on trays.
D. Section 2.2.5 for mini-load ASRS arrangements that use closed-top, noncombustible, solid-walled
containers or FM Approved, non-propagating, open-top containers
E. Section 2.2.6 for mini-load ASRS arrangements that use either (1) products that do not collect water
that are stored on trays, or (2) closed-top combustible containers.
F. Section 2.2.7 for mini-load ASRS arrangements that use either (1) open-top cardboard or unexpanded
plastic containers, or (2) products or containers that collect water and are stored on trays.
2.2.1.1.4 The protection of expanded plastic trays or expanded plastic containers in a mini-load type of
horizontal-loading ASRS storage array is outside the scope of this data sheet.

2.2.1.2 Information Needed


To determine the protection options available within Section 2.2, the following information is needed:
1. Maximum commodity hazard to be protected (see Data Sheet 8-1, Commodity Classification)
2. Depth of the ASRS unit (rack row depth; see Appendix A for a definition of this term)
3. Material composition (i.e., chemical construction) of the trays and/or containers used for material
handling
4. Type of containers (closed-top, solid-walled open-top, and non-solid walled open-top)
5. Transverse flue space width
6. Horizontal distance between transverse flue spaces
7. Longitudinal flue space width (if provided)
8. Tier height
9. Maximum storage height
10. Maximum ceiling height over the storage area

2.2.1.3 General Construction Features for Horizontal-Loading ASRS Storage Arrangements


2.2.1.3.1 Properly anchor all horizontal-loading ASRS rack structures to prevent them from falling over and
causing nearby racks to fall over (i.e., a “domino” effect). Take into consideration the effects of rack loads,
the additional load created by the collection of fire protection water by the stored commodity and its container
(see Section 2.1.2.5), the weight of water-filled, in-rack sprinkler piping (if provided), any seismic conditions
(see FM Global Property Loss Prevention Data Sheet [i.e., Data Sheet] 1-2, Earthquakes) and the type of
flooring to which the rack structure will be anchored to. Retain a qualified structural engineer to perform the
analysis and design of any anchoring of the storage racks.
2.2.1.3.2 Design horizontal-loading ASRS rack-supported structures taking into consideration the effects of
weather (wind, snow, rain, hail, etc.), rack loads, seismic conditions (see Data Sheet 1-2), and the additional
load created by the stored commodity and/or its container collecting or absorbing fire protection water (see
Section 2.1.2.5), the weight of water-filled sprinkler piping (from ceiling or in-rack sprinklers), and any other
loads to which the rack or structure may be exposed.

2.2.1.4 General Occupancy Features for Horizontal-Loading ASRS Storage Arrangements –


Transverse Flue Spaces
2.2.1.4.1 When measuring for the net width of a transverse flue space, account for the width of any angle
irons or alignment guides, located between containers or trays, that are pitched at an angle less than 30º.
2.2.1.4.2 Transverse Flue Spaces a Nominal 2 ft (0.6 m) Apart: Where the horizontal distance between
transverse flue spaces is a nominal 2 ft (0.6 m) or less, transverse flue spaces are considered adequate
when:
1. Minimum 2 in. (50 mm) gross wide transverse flue spaces are provided between containers or trays
for transverse flue spaces at rack uprights, and
2. Minimum 2 in. (50 mm) net wide vertically aligned transverse flue spaces are provided between
containers or trays for transverse flue spaces that are not at rack uprights.

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


Protection for Automatic Storage 8-34
FM Global Property Loss Prevention Data Sheets Page 17

2.2.1.4.3 Transverse Flue Spaces a Nominal 4 ft (1.2 m) Apart: Where the horizontal distance between
transverse flue spaces is a nominal 4 ft (1.2 m) or less, transverse flue spaces are considered adequate when:
1. Minimum 3 in. (75 mm) gross wide transverse flue spaces are provided between containers or trays
for transverse flue spaces at rack uprights, and
2. Minimum 3 in. (75 mm) net wide vertically aligned transverse flue spaces are provided between
containers or trays for transverse flue spaces that are not at rack uprights.
2.2.1.4.4 Transverse Flue Spaces a Nominal 10 ft (3.0 m) Apart: Where the horizontal distance between
transverse flue spaces is a nominal 10 ft (3.0 m) or less, transverse flue spaces are considered adequate
when:
1. Minimum 6 in. (150 mm) gross wide transverse flue spaces are provided between containers or trays
for transverse flue spaces at rack uprights, and
2. Minimum 6 in. (150 mm) net wide vertically aligned transverse flue spaces are provided between
containers or trays for transverse flue spaces that are not at rack uprights.
2.2.1.4.5 In-rack sprinklers and vertical barriers are needed when the guidelines indicated in Sections
2.2.1.4.2, 2.2.1.4.3, or 2.2.1.4.4 are not met. However, vertical barriers can be avoided when:
1. The transverse flue spaces are not vertically aligned, but the width of the transverse flue spaces is in
accordance with Section 2.2.1.4.2, 2.2.1.4.3, and 2.2.1.4.4, or
2. The width of the transverse flue spaces is not in accordance with Sections 2.2.1.4.2, 2.2.1.4.3, and
2.2.1.4.4, but the net width of the transverse flue spaces is at least 2 in. (50 mm).
2.2.1.4.6 When Section 2.2.1.4.5 indicates that vertical barriers are needed, install the vertical barriers at
rack uprights on maximum 10 ft (3.0 m) horizontal spacing. Arrange the vertical barriers to cover the entire
depth of the rack row as well as the entire storage height located between each vertical level of in-rack
sprinklers. Note that the vertical barriers do not need to extend into the roughly 1 ft (0.3 m) high horizontal
space where in-rack sprinklers are being installed.

2.2.1.5 General Protection Guidelines for Horizontal-Loading ASRS Storage Arrangements

2.2.1.5.1 Sprinkler System Types


2.2.1.5.1.1 Ceiling-Level Sprinkler System Types
1. Depending on the ambient temperature of the ASRS area being protected, ceiling-level sprinkler systems
can be:
a. Wet-pipe sprinkler systems
b. Antifreeze solution sprinkler system consisting of a 20% to 30% propylene or up to 35% glycerin
c. Dry-pipe sprinkler systems
d. Non-interlocked, single-interlocked, or double-interlocked preaction sprinkler systems
e. Refrigerated area sprinkler systems, or
f. Vacuum-type sprinkler systems
2. A ceiling-level sprinkler system consisting of 20% to 30% concentration of propylene glycol in water
or a glycerin solution with a concentration up to 35% in water is acceptable for ambient temperatures
between 32ºF (0°C) and 40°F (4°C). Wet-pipe sprinkler system designs can be utilized for ceiling
sprinkler systems having these anti-freeze solution concentrations.
3. The maximum water delivery time for all ceiling-level dry-pipe and similar sprinkler systems is 40
seconds upon the operation of the hydraulically most remote 4 sprinklers (2 sprinklers on 2 lines).
4. When installing a preaction, refrigerated area, or vacuum-type sprinkler system, see Data Sheet 2-0
for recommendations pertaining to the sprinkler system’s activating detection system.
5. Ceiling sprinkler designs for single-interlocked preaction sprinkler systems can be either classified as
“wet-pipe” or “dry-pipe,” depending on the installation of the activating detection system. See Data Sheet
2-0 to determine the installation requirements needed for the detection system to achieve a sprinkler
system design classification of wet pipe. Design the single-interlocked preaction system using the
dry-pipe sprinkler system designs when the detection installation is not in compliance with the

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


8-34 Protection for Automatic Storage
Page 18 FM Global Property Loss Prevention Data Sheets

recommendations provided in Data Sheet 2-0 for a wet-pipe sprinkler system design.
6. See Data Sheet 2-0 for additional recommendations related to the specific sprinkler system type that
is to be installed.
2.2.1.5.1.2 In-Rack Sprinkler System Types
1. Depending on the ambient temperature of the ASRS area being protected, in-rack sprinkler systems
can be:
a. Wet-pipe sprinkler systems
b. Antifreeze solution sprinkler system consisting of 20% to 25% propylene, or 30% to 35% glycerin
c. Dry-pipe sprinkler systems
d. Non-interlocked, single-interlocked, or double-interlocked preaction sprinkler systems
e. Refrigerated area sprinkler systems, or
f. Vacuum-type sprinkler systems
2. An in-rack sprinkler system consisting of 20% to 25% concentration of propylene glycol in water or a
glycerin solution with a concentration of 30% to 35% in water is acceptable for ambient temperatures
between 32°F (0°C) and 40°F (4°C). Wet-pipe sprinkler system designs can be used for in-rack
sprinkler systems having these anti-freeze solution concentrations.
3. Except for wet-pipe sprinkler systems and the anti-freeze solution sprinkler systems outlined above,
use dry-pipe sprinkler system designs for all other in-rack sprinkler system types.
4. The maximum water delivery time for all in-rack sprinkler dry-pipe and similar sprinkler systems is 40
seconds upon the operation of the hydraulically most remote in-rack sprinkler.
5. When installing a preaction or refrigerated area sprinkler system, see Data Sheet 2-0 for
recommendations pertaining to the sprinkler system’s activating detection system.
6. See Data Sheet 2-0 for additional recommendations related to the specific sprinkler system type that
is to be installed.

2.2.1.5.2 Sprinklers
2.2.1.5.2.1 Ceiling-Level Sprinklers
Install FM Approved, Storage ceiling-level sprinklers having the attributes indicated in the applicable
horizontal-loading ASRS protection tables.
2.2.1.5.2.2 In-Rack Sprinklers
When in-rack sprinklers are required, install FM Approved, quick-response, 160ºF (70ºC) nominally rated,
Storage sprinklers having the appropriate K-factor value indicated in the applicable horizontal-loading ASRS
in-rack sprinkler protection table. Note that if not specifically indicated, in-rack sprinklers can be either
pendent or upright.

2.2.1.6 Hose Demand Design and Water Supply Duration for Horizontal-Loading ASRS Storage
Arrangements
See Table 2 to determine the hose demand design and the water supply duration for either (1) a ceiling-only
sprinkler system arrangement, or (2) a ceiling and in-rack sprinkler system arrangement where the two
sprinkler systems must be hydraulically balanced.

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


Protection for Automatic Storage 8-34
FM Global Property Loss Prevention Data Sheets Page 19

Table 2. Hose Demand Design and Water Supply Duration


Number of Sprinklers in the
Ceiling Sprinkler System
Ceiling Sprinkler Type Design Hose Demand, gpm (L/min) Water Supply Duration, min
Standard-Coverage 12 or less 250 (950) 60
13 to 19 500 (1,900) 90
20 or more 500 (1,900) 120
Extended-Coverage 6 or less 250 (950) 60
7 to 9 500 (1,900) 90
10 or more 500 (1,900) 120

2.2.1.7 Fire Detection for Horizontal-Loading ASRS Storage Arrangements


2.2.1.7.1 Install a FM Approved ceiling-level fire detection system over the horizontal-loading ASRS storage
area in accordance with FM Global Property Loss Prevention Data Sheet (i.e., Data Sheet) 5-48, Automatic
Fire Detection.
2.2.1.7.2 When the ceiling construction over the storage area is considered obstructed per Data Sheet 2-0,
install the detectors on the same maximum spacing indicated for the ceiling-level sprinklers using an
obscuration rate that is in accordance with the detection system manufacturer’s guidelines.
2.2.1.7.3 Arrange the fire detection system upon activation to:
1. send an alarm to a constantly attended location, and
2. automatically shut-down the operations of the ASRS robots
2.2.1.7.4 A ceiling-level fire detection system over the horizontal-loading ASRS storage area is not needed
when Closed-Top, Noncombustible, Solid-Walled Containers are used throughout the ASRS storage array.

2.2.1.8 Final Extinguishment: Small Hose Connection Stations


2.2.1.8.1 To aid in manual firefighting efforts and after-extinguishment mop-up operations, install small hose
connection stations near the access points to the horizontal-loading ASRS storage aisles for the fire service.
Consult with the local fire service or authority having jurisdiction to determine their recommendations
regarding the following:
1. The use of wet-barrel or dry-barrel stations
2. The size of the hose connections
3. The horizontal distance between stations
2.2.1.8.2 Design the small hose connection station system to provide a minimum flow of 50 gpm (190 L/min)
from each of the two most hydraulically remote stations (100 gpm [380 L/min] total).
2.2.1.8.3 Arrange the water supplies feeding these stations in one of the following ways:
1. A piping system dedicated solely for the small hose connection stations, or
2. Piping that connects the stations to a sprinkler system different than the one protecting the ASRS storage
area
2.2.1.8.4 The installation of small hose connection stations can be avoided:
1. When noncombustible solid-walled containers are used throughout the ASRS storage array, or
2. At the documented discretion of the local authority having jurisdiction.

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


8-34 Protection for Automatic Storage
Page 20 FM Global Property Loss Prevention Data Sheets

2.2.2 Protection of Horizontal-Loading Shuttle ASRS Storage Arrangements Where Closed-Top,


Noncombustible, Solid-Walled Containers, or FM Approved, Non-Propagating, Open-Top Containers
are Being Used

2.2.2.1 Protection of Horizontal-Loading Shuttle ASRS Storage Arrangements Where Closed-Top,


Noncombustible, Solid-Walled Containers are Being Used
2.2.2.1.1 Automatic sprinkler protection can be designed for the surrounding occupancy hazard when
Closed-Top, Noncombustible, Solid-Walled Containers are used throughout the entire horizontal-loading
ASRS storage array.
2.2.2.1.2 Where closed-top, noncombustible, solid-walled containers are being used, but not throughout the
entire storage array, provide protection in accordance with the worst-case container or tray being used.

2.2.2.2 Protection of Horizontal-Loading, Shuttle ASRS Storage Arrangements Where FM Approved,


Non-Propagating Open-Top Containers are Being Used (Reserved)
Protection guidelines for FM Approved, non-propagating, open-top containers will be provided upon the
release of a FM Approval Standard specific to these types of containers.

2.2.3 Protection of Horizontal-Loading Shuttle ASRS Storage Arrangements Using (1) Closed-Top
Combustible Containers, or (2) Products that Do Not Collect Water that are Stored on Trays
The protection guidelines in Section 2.2.3 apply only to storage that is not considered open-top, whether
stored directly on the support rails of the ASRS or on trays. Such products will be subsequently referred to
in Section 2.2.3 as “storage on trays”. If the product or containers allow for water collection, use the protection
guidelines provided in Section 2.2.4.
Section 2.2.3 is organized as follows:
• Section 2.2.3.1 determines if a ceiling-only protection option is available and, if it is, the recommended
ceiling-only protection designs.
• Section 2.2.3.2 determines the recommended designs when both ceiling and in-rack sprinklers are installed.
This section is further broken down into the following subsections:
- Section 2.2.3.2.1 provides acceptable horizontal in-rack sprinkler arrangements.
- Section 2.2.3.2.2 provides both the acceptable vertical in-rack sprinkler arrangements as well as the
corresponding in-rack sprinkler system design.
- Section 2.2.3.2.3 provides the acceptable ceiling sprinkler system design with the chosen in-rack sprinkler
system arrangement.

2.2.3.1 Ceiling-Only Sprinkler System Design Criteria for Closed-Top Combustible Containers, or
Storage on Trays
2.2.3.1.1 A ceiling-only sprinkler system protection scheme is possible when:
1. Adequately aligned transverse flue spaces as outlined in Section 2.2.1.4 are provided, and
2. For Class 1 through 4, cartoned plastics, and uncartoned unexpanded plastics, minimum 3-1/2 ft
(1.1 m) wide aisles are provided for ceiling heights not exceeding 30 ft (9.1 m), and
3. Minimum 4 ft (1.2 m) wide aisles are provided when:
a. Uncartoned, expanded plastics are stored in the racks, or
b. The ceiling height exceeds 30 ft (9.1 m) (unless indicated otherwise by a footnote at the bottom of
the applicable protection table), and
4. For the given material handling scenario outlined in this section, ceiling-only protection is provided per
the applicable protection table (Tables 4 through 13) for the specific sprinkler being installed at ceiling
level, and
5. The water supply can provide the flow and pressure requirements for the protection option chosen
from the applicable protection table.

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


Protection for Automatic Storage 8-34
FM Global Property Loss Prevention Data Sheets Page 21

If the conditions outlined in (1) through (5) cannot be met, see Section 2.2.3.2 regarding the guidelines for
installing in-rack sprinklers in combination with ceiling-level sprinklers.
2.2.3.1.2 When a ceiling-only protection scheme is acceptable per items (1) through (5) in Section 2.2.3.1.1,
use Table 3 to determine which protection table provides the recommended ceiling sprinkler design,
depending on the commodity hazard, the type of material handling being used (i.e., directly on the rack’s
horizontal supporting rails or on trays) and the type of ceiling sprinkler system (i.e., wet or dry) being installed.
2.2.3.1.3 See Section 2.2.1.6 to determine the ceiling sprinkler’s hose demand design and water supply
duration.
2.2.3.1.4 See Section 2.1.4.5.4 to determine the number of sprinklers per branch line for ceiling-level sprinkler
calculations.

Table 3. Determining Which Ceiling Sprinkler Protection Table to Use for the Protection of Closed-Top Combustible
Containers or Storage Trays
Commodity Classification
(No Open-Top Containers Ceiling Sprinkler System
Material Handling Method Permitted) Type Protection Table to Use
Directly on Supporting Rails Class 1 through Class 3 Wet 4
Dry 5
Class 4 and Cartoned Wet 6
Unexpanded Plastics Dry 7
Cartoned Expanded Wet 8
Plastics Dry 9
Uncartoned Unexpanded Wet 10
Plastics Dry 11
Uncartoned Expanded Wet 12
Plastics Dry 13
On Trays Class 1 through 4, Wet 10
Cartoned Plastics, and Dry 11
Uncartoned Unexpanded
Plastics
Uncartoned Expanded Wet 12
Plastics Dry 13
Note: In Tables 4 through 12, the ceiling-level protection options highlighted in green represent those for which the hose stream demand
is 250 gpm (950 L/min) and the sprinkler system duration is 1 hour.

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


Table 4. Ceiling-Level Protection Guidelines on a Wet System for Class 1, 2, and 3 Commodities Stored Directly on the Support Rails of a Shuttle ASRS; No. of AS @ psi (bar)

Page 22
8-34
Wet System, 160°F (70°C) Nominally Rated, Upright
Max. Wet System, 160˚F (70˚C) Nominally Rated, Pendent Sprinklers Sprinklers
Ceiling Quick-Response Standard-Response Quick-Response Standard-Response
Height, K11.2 K14.0 K16.8 K22.4 K25.2 K25.2EC K28.0 K33.6 K11.2 K14.0 K19.6 K25.2 K11.2 K14.0 K16.8 K25.2EC K11.2 K16.8 K25.2
ft (m) (K160) (K200) (K240) (K320) (K360) (K360EC) (K400) (K480) (K160) (K200) (K280) (K360) (K160) (K200) (K240) (K360EC) (K160) (K240) (K360)
10 12 @ 9 @ 7 9 @ 7 9@ 9@ 6 @ 20 9@ 9@ 12 @ 9 @ 7 9@ 9 @ 7 12 @ 9 @ 7 9 @ 7 6 @ 20 12 @ 9 @ 7 9 @ 7
(3.0) 7 (0.5) (0.5) (0.5) 20 20 (1.4) 40 55 7 (0.5) (0.5) 16 (0.5) 7 (0.5) (0.5) (0.5) (1.4) 7 (0.5) (0.5) (0.5)
(1.4) (1.4) (2.8) (3.8) (1.1)
20 12 @ 12 @ 12 @ 9@ 9@ 6 @ 20 9@ 9@ 12 @ 12 @ 9@ 9@ 12 @ 12 @ 12 @ 6 @ 20 12 @ 12 @ 12 @
(6.1) 10 7 (0.5) 13 20 20 (1.4) 40 55 10 7 (0.5) 16 10 10 7 (0.5) 7 (0.5) (1.4) 10 7 (0.5) 7 (0.5)
©2017-2023 Factory Mutual Insurance Company. All rights reserved.

(0.7) (0.9) (1.4) (1.4) (2.8) (3.8) (0.7) (1.1) (0.7) (0.7) (0.7)
25 15 @ 12 @ 12 @ 9@ @ 20 6 @ 22 9@ 9@ 15 @ 15 @ 9@ 9@ 15 @ 12 @ 12 @ 6 @ 22 15 @ 15 @ 10 @
(7.6) 16 16 11 20 (1.4) (1.5) 40 55 16 10 16 10 16 16 11 (1.5) 16 7 (0.5) 20
(1.1) (1.1) (0.8) (1.4) (2.8) (3.8) (1.1) (0.7) (1.1) (0.7) (1.1) (1.1) (0.8) (1.1) (1.4)
30 18 @ 12 @ 12 @ 9@ 9@ 6 @ 30 9@ 9@ 18 @ 18 @ 9@ 9@ 18 @ 12 @ 12 @ 6 @ 30 18 @ 18 @ 12 @
(9.1) 50 50 35 20 20 (2.1) 40 55 50 32 16 10 50 50 35 (2.1) 50 22 20

Protection for Automatic Storage


(3.5) (3.5) (2.4) (1.4) (1.4) (2.8) (3.8) (3.5) (2.2) (1.1) (0.7) (3.5) (3.5) (2.4) (3.5) (1.5) (1.4)
35 12 @ 12 @ 12 @ 12 @ 6 @ 60 9@ 9@ 15 @ 9@ 8 @ 40
(10.7) 75 52 29 23 (4.1) 40 55 25 30 (2.8)
(5.2) (3.6) (2.0) (1.6) (2.8) (3.8) (1.7) (2.1)

FM Global Property Loss Prevention Data Sheets


40 12 @ 12 @ 9@ 9@ 9@ 9@ 9@
(12.2) 75 52 50 40 40 55 30
(5.2) (3.6) (3.5) (2.8) (2.8) (3.8) (2.1)
50 10 @ 10 @ 10 @ 9@
(15.2) 63 50 40 55
(4.3)a,c (3.5)a,c (2.8)a,c (3.8)a
55 9@ 9@
(16.8) 80 55
(5.5)b,c (3.8)a
a
Minimum 6 ft (1.8 m) wide aisles needed
b
Minimum 8 ft (2.4 m) wide aisles needed
c
Maximum vertical distance of sprinkler’s thermal element below ceiling is 13 in. (325 mm)
Protection for Automatic Storage 8-34
FM Global Property Loss Prevention Data Sheets Page 23

Table 5. Ceiling-Level Protection Guidelines on a Dry System for Class 1, 2, and 3 Commodities Stored Directly on the
Support Rails of a Shuttle ASRS; No. of AS @ psi (bar)
Dry System, 280°F (140°C) Nominally Rated, Upright Sprinklers
Max. Ceiling Height, Standard-Response
ft (m) K11.2 (K160) K16.8 (K240) K25.2 (K360) K33.6 (K480)
10 (3.0) 16 @ 7 (0.5) 16 @ 7 (0.5) 16 @ 7 (0.5) 16 @ 50 (3.5)
20 (6.1) 16 @ 10 (0.7) 16 @ 7 (0.5) 16 @ 7 (0.5) 16 @ 50 (3.5)
25 (7.6) 20 @ 16 (1.1) 20 @ 7 (0.5) 20 @ 7 (0.5) 20 @ 50 (3.5)
30 (9.1) 25 @ 50 (3.5) 25 @ 22 (1.5) 25 @ 10 (0.7) 25 @ 50 (3.5)
40 (12.2) 24 @ 15 (1.0)a 12 @ 50 (3.5)b
b
45 (13.7) 12 @ 50 (3.5) 12 @ 50 (3.5)b
c
50 (15.2) 15 @ 50 (3.5)
c
55 (16.8) 16 @ 50 (3.5)
a
Minimum 4 ft (1.2 m) wide aisle and maximum 25 second water delivery time is needed. An acceptable alternative design
is 12 AS @ 50 psi (3.5 bar), but a minimum 6 ft (1.8 m) wide aisle and a maximum 20 second water delivery time is
needed.
b
Minimum 6 ft (1.8 m) wide aisle and maximum 20 second water delivery time is needed.
c
Minimum 8 ft (2.4 m) wide aisle and maximum 20 second water delivery time is needed.

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


Table 6. Ceiling-Level Protection Guidelines on a Wet System for Class 4 and Cartoned Unexpanded Plastic Commodities Stored Directly on the Support Rails of a Shuttle ASRS;

Page 24
8-34
No. of AS @ psi (bar)
Wet System, 160°F (70°C) Nominally Rated, Upright
Max. Wet System, 160°F (70°C) Nominally Rated, Pendent Sprinklers Sprinklers
Ceiling Quick-Response Standard-Response Quick-Response Standard-Response
Height, K11.2 K14.0 K16.8 K22.4 K25.2 K25.2EC K28.0 K33.6 K11.2 K14.0 K19.6 K25.2 K11.2 K14.0 K16.8 K25.2EC K11.2 K16.8 K25.2
ft (m) (K160) (K200) (K240) (K320) (K360) (K360EC) (K400) (K480) (K160) (K200) (K280) (K360) (K160) (K200) (K240) (K360EC) (K160) (K240) (K360)
10 12 @ 9 @ 7 9 @ 7 9@ 9@ 6 @ 20 9@ 9@ 12 @ 9 @ 7 9@ 9 @ 7 12 @ 9 @ 7 9 @ 7 6 @ 20 12 @ 9 @ 7 9 @ 7
(3.0) 7 (0.5) (0.5) (0.5) 20 20 (1.4) 40 55 7 (0.5) (0.5) 16 (0.5) 7 (0.5) (0.5) (0.5) (1.4) 7 (0.5) (0.5) (0.5)
(1.4) (1.4) (2.8) (3.8) (1.1)
15 15 @ 12 @ 12 @ 9@ 9@ 6 @ 20 9@ 9@ 15 @ 12 @ 9@ 10 @ 15 @ 12 @ 12 @ 6 @ 20 15 @ 12 @ 10 @
©2017-2023 Factory Mutual Insurance Company. All rights reserved.

(4.6) 16 16 11 20 20 (1.4) 40 55 16 16 16 7 (0.5) 16 16 11 (1.4) 16 11 7 (0.5)


(1.1) (1.1) (0.8) (1.4) (1.4) (2.8) (3.8) (1.1) (1.1) (1.1) (1.1) (1.1) (0.8) (1.1) (0.8)
20 12 @ 12 @ 12 @ 9@ 9@ 6 @ 22 9@ 9@ 12 @ 12 @ 9@ 12 @ 12 @ 12 @ 12 @ 6 @ 22 12 @ 12 @ 12 @
(6.1) 30 18 13 20 20 (1.5) 40 55 30 16 16 7 (0.5) 30 16 13 (1.5) 30 13 7 (0.5)
(2.1) (1.2) (0.9) (1.4) (1.4) (2.8) (3.8) (2.1) (1.1) (1.1) (2.1) (1.1) (0.9) (2.1) (0.9)
25 15 @ 9@ 9@ 9@ 9@ 6 @ 22 9@ 9@ 15 @ 12 @ 9@ 12 @ 15 @ 12 @ 12 @ 6 @ 22 15 @ 15 @ 12 @

Protection for Automatic Storage


(7.6) 65 35 24 20 20 (1.5) 40 55 65 50 16 10 65 50 35 (1.5) 65 29 20
(4.5) (2.4) (1.7) (1.4) (1.4) (2.8) (3.8) (4.5) (3.5) (1.1) (0.7) (4.5) (3.5) (2.4) (4.5) (2.0) (1.4)
30 12 @ 12 @ 9@ 9@ 6 @ 30 9@ 9@ 9@ 12 @ 6 @ 30 12 @
(9.1) 50 35 20 20 (2.1) 40 55 16 15 (2.1) 20

FM Global Property Loss Prevention Data Sheets


(3.5) (2.4) (1.4) (1.4) (2.8) (3.8) (1.1) (1.0) (1.4)
35 12 @ 12 @ 12 @ 12 @ 6 @ 60 9@ 9@ 15 @ 9@ 8 @ 40
(10.7) 75 52 29 23 (4.1) 40 55 25 30 (2.8)
(5.2) (3.6) (2.0) (1.6) (2.8) (3.8) (1.7) (2.1)
40 12 @ 12 @ 9@ 9@ 9@ 9@ 9@
(12.2) 75 52 50 40 40 55 30
(5.2) (3.6) (3.5) (2.8) (2.8) (3.8) (2.1)
50 10 @ 10 @ 10 @ 9@
(15.2) 63 50 40 55
(4.3)a,c (3.5)a,c (2.8)a,c (3.8)a
55 9@ 9@
(16.8) 80 55
(5.5)b,c (3.8)a
a
Minimum 6 ft (1.8 m) wide aisles needed
b
Minimum 8 ft (2.4 m) wide aisles needed
c
Maximum vertical distance of sprinkler’s thermal element below ceiling is 13 in. (325 mm)
Protection for Automatic Storage 8-34
FM Global Property Loss Prevention Data Sheets Page 25

Table 7. Ceiling-Level Protection Guidelines on a Dry System for Class 4 and Cartoned Unexpanded Plastic Commodities
Stored Directly on the Support Rails of a Shuttle ASRS; No. of AS @ psi (bar)
Dry System, 280°F (140°C) Nominally Rated, Upright Sprinklers
Max. Ceiling Height, Standard-Response
ft (m) K11.2 (K160) K16.8 (K240) K25.2 (K360) K33.6 (K480)
10 (3.0) 16 @ 7 (0.5) 16 @ 7 (0.5) 16 @ 7 (0.5) 16 @ 50 (3.5)
15 (4.6) 20 @ 16 (1.1) 20 @ 7 (0.5) 20 @ 7 (0.5) 20 @ 50 (3.5)
20 (6.1) 20 @ 30 (2.1) 20 @ 13 (0.9) 20 @ 7 (0.5) 20 @ 50 (3.5)
25 (7.6) 20 @ 65 (4.5) 20 @ 29 (2.0) 20 @ 13 (0.9) 20 @ 50 (3.5)
30 (9.1) 30 @ 20 (1.4) 30 @ 50 (3.5)

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


Table 8. Ceiling-Level Protection Guidelines on a Wet System for Cartoned Expanded Plastic Commodities Stored Directly on the Support Rails of a Shuttle ASRS;

Page 26
8-34
No. of AS @ psi (bar)
Wet System, 160°F (70°C) Nominally Rated, Upright
Max. Wet System, 160°F (70°C) Nominally Rated, Pendent Sprinklers Sprinklers
Ceiling Quick-Response Standard-Response Quick-Response Standard-Response
Height, K11.2 K14.0 K16.8 K22.4 K25.2 K25.2EC K28.0 K33.6 K11.2 K14.0 K19.6 K25.2 K11.2 K14.0 K16.8 K25.2EC K11.2 K16.8 K25.2
ft (m) (K160) (K200) (K240) (K320) (K360) (K360EC) (K400) (K480) (K160) (K200) (K280) (K360) (K160) (K200) (K240) (K360EC) (K160) (K240) (K360)
10 15 @ 15 @ 15 @ 9@ 9@ 6 @ 20 9@ 9@ 15 @ 15 @ 12 @ 15 @ 15 @ 15 @ 15 @ 6 @ 20 15 @ 15 @ 15 @
(3.0) 10 7 (0.5) 7 (0.5) 20 20 (1.4) 40 55 10 7 (0.5) 19 7 (0.5) 10 7 (0.5) 7 (0.5) (1.4) 10 7 (0.5) 7 (0.5)
(0.7) (1.4) (1.4) (2.8) (3.8) (0.7) (1.1) (0.7) (0.7)
©2017-2023 Factory Mutual Insurance Company. All rights reserved.

20 18 @ 12 @ 12 @ 9@ 9@ 9 @ 21 9@ 9@ 18 @ 15 @ 15 @ 15 @ 18 @ 12 @ 12 @ 8 @ 35 18 @ 15 @ 15 @
(6.1) 28 18 13 20 20 (1.4) 40 55 28 18 16 7 (0.5) 28 50 35 (2.4) 28 22 10
(1.9) (1.2) (0.9) (1.4) (1.4) (2.8) (3.8) (1.9) (1.2) (1.1) (1.9) (3.5) (2.4) (1.9) (1.5) (0.7)
25 12 @ 12 @ 10 @ 9@ 8 @ 60 9@ 9@ 15 @ 15 @ 15 @ 12 @ 12 @
(7.6) 35 24 20 20 (4.1) 40 55 50 25 15 50 35
(2.4) (1.7) (1.4) (1.4) (2.8) (3.8) (3.5) (1.7) (1.0) (3.5) (2.4)
30 12 @ 12 @ 12 @ 12 @ 12 @ 12 @

Protection for Automatic Storage


(9.1) 50 35 25 20 40 55
(3.5) (2.4) (1.7) (1.4) (2.8) (3.8)
40 12 @ 12 @ 12 @ 12 @
(12.2) 75 60 49 55

FM Global Property Loss Prevention Data Sheets


(5.2) (4.1) (3.4) (3.8)
Protection for Automatic Storage 8-34
FM Global Property Loss Prevention Data Sheets Page 27

Table 9. Ceiling-Level Protection Guidelines on a Dry System for Cartoned Expanded Plastic Commodities Stored Directly
on the Support Rails of a Shuttle ASRS; No. of AS @ psi (bar)
Dry System, 280°F (140°C) Nominally Rated, Upright Sprinklers
Max. Ceiling Height, Standard-Response
ft (m) K11.2 (K160) K16.8 (K240) K25.2 (K360) K33.6 (K480)
10 (3.0) 20 @ 10 (0.7) 20 @ 7 (0.5) 20 @ 7 (0.5) 20 @ 50 (3.5)
20 (6.1) 20 @ 50 (3.5) 20 @ 22 (1.5) 20 @ 10 (0.7) 20 @ 50 (3.5)

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


Table 10. Ceiling-Level Protection Guidelines on a Wet System for Uncartoned Unexpanded Plastic Commodities Stored in a Shuttle ASRS; No. of AS @ psi (bar)

Page 28
8-34
Wet System, 160°F (70°C) Nominally Rated, Upright
Max. Wet System, 160°F (70°C) Nominally Rated, Pendent Sprinklers Sprinklers
Ceiling Quick-Response Standard-Response Quick-Response Standard-Response
Height, K11.2 K14.0 K16.8 K22.4 K25.2 K25.2EC K28.0 K33.6 K11.2 K14.0 K19.6 K25.2 K11.2 K14.0 K16.8 K25.2EC K11.2 K16.8 K25.2
ft (m) (K160) (K200) (K240) (K320) (K360) (K360EC) (K400) (K480) (K160) (K200) (K280) (K360) (K160) (K200) (K240) (K360EC) (K160) (K240) (K360)
10 15 @ 15 @ 15 @ 9@ 9@ 6 @ 20 9@ 9@ 15 @ 15 @ 12 @ 15 @ 15 @ 15 @ 15 @ 6 @ 20 15 @ 15 @ 15 @
(3.0) 10 7 (0.5) 7 (0.5) 20 20 (1.4) 40 55 10 7 (0.5) 16 7 (0.5) 10 7 (0.5) 7 (0.5) (1.4) 10 7 (0.5) 7 (0.5)
(0.7) (1.4) (1.4) (2.8) (3.8) (0.7) (1.1) (0.7) (0.7)
15 15 @ 12 @ 12 @ 9@ 9@ 6 @ 60 9@ 9@ 15 @ 12 @ 12 @ 12 @ 15 @ 15 @ 15 @ 8 @ 35 15 @ 15 @ 15 @
©2017-2023 Factory Mutual Insurance Company. All rights reserved.

(4.6) 50 32 22 25 20 (4.1) 40 55 50 50 25 15 50 32 22 (2.4) 50 22 10


(3.5) (2.2) (1.5) (1.7) (1.4) (2.8) (3.8) (3.5) (3.5) (1.7) (1.0) (3.5) (2.2) (1.5) (3.5) (1.5) (0.7)
20 9@ 9@ 9@ 9@ 6 @ 60 9@ 9@ 12 @ 12 @ 12 @
(6.1) 50 35 25 20 (4.1) 40 55 50 25 15
(3.5) (2.4) (1.7) (1.4) (2.8) (3.8) (3.5) (1.7) (1.0)
25 10 @ 10 @ 10 @ 10 @ 10 @ 10 @
(7.6) 50 35 25 20 40 55

Protection for Automatic Storage


(3.5) (2.4) (1.7) (1.4) (2.8) (3.8)
30 15 @ 15 @ 10 @ 10 @ 10 @ 10 @
(9.1) 50 35 50 40 40 55
(3.5) (2.4) (3.5) (2.8) (2.8) (3.8)

FM Global Property Loss Prevention Data Sheets


40 12 @ 12 @ 12 @ 12 @
(12.2) 75 60 49 55
(5.2) (4.1) (3.4) (3.8)
Protection for Automatic Storage 8-34
FM Global Property Loss Prevention Data Sheets Page 29

Table 11. Ceiling-Level Protection Guidelines on a Dry System for Uncartoned Unexpanded Plastic Commodities Stored
in a Shuttle ASRS; No. of AS @ psi (bar)
Dry System, 280°F (140°C) Nominally Rated, Upright Sprinklers
Max. Ceiling Height, Standard-Response
ft (m) K11.2 (K160) K16.8 (K240) K25.2 (K360) K33.6 (K480)
10 (3.0) 20 @ 10 (0.7) 20 @ 7 (0.5) 20 @ 7 (0.5) 20 @ 50 (3.5)
15 (4.6) 20 @ 50 (3.5) 20 @ 22 (1.5) 20 @ 10 (0.7) 20 @ 50 (3.5)

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


Table 12. Ceiling-Level Protection Guidelines on a Wet System for Uncartoned Expanded Plastic Commodities Stored in a Shuttle ASRS; No. of AS @ psi (bar)

Page 30
8-34
Wet System, 160°F (70°C) Nominally Rated, Upright
Max. Wet System, 160°F (70°C) Nominally Rated, Pendent Sprinklers Sprinklers
Ceiling Quick-Response Standard-Response Quick-Response Standard-Response
Height, K11.2 K14.0 K16.8 K22.4 K25.2 K25.2EC K28.0 K33.6 K11.2 K14.0 K19.6 K25.2 K11.2 K14.0 K16.8 K25.2EC K11.2 K16.8 K25.2
ft (m) (K160) (K200) (K240) (K320) (K360) (K360EC) (K400) (K480) (K160) (K200) (K280) (K360) (K160) (K200) (K240) (K360EC) (K160) (K240) (K360)
10 15 @ 15 @ 15 @ 9@ 9@ 6 @ 20 9@ 9@ 15 @ 15 @ 12 @ 15 @ 15 @ 15 @ 15 @ 6 @ 20 15 @ 15 @ 15 @
(3.0) 10 7 (0.5) 7 (0.5) 20 20 (1.4) 40 55 10 7 (0.5) 16 7 (0.5) 10 7 (0.5) 7 (0.5) (1.4) 10 7 (0.5) 7 (0.5)
(0.7) (1.4) (1.4) (2.8) (3.8) (0.7) (1.1) (0.7) (0.7)
15 15 @ 12 @ 12 @ 9@ 9@ 8 @ 35 9@ 9@ 15 @ 15 @ 15 @ 15 @ 15 @ 15 @ 15 @ 8 @ 35 15 @ 15 @ 15 @
(4.6) 50 32 22 25 20 (2.4) 40 55 50 32 16 10 50 32 22 (2.4) 50 22 10
©2017-2023 Factory Mutual Insurance Company. All rights reserved.

(3.5) (2.2) (1.5) (1.7) (1.4) (2.8) (3.8) (3.5) (2.2) (1.1) (0.7) (3.5) (2.2) (1.5) (3.5) (1.5) (0.7)
25 12 @ 12 @ 9@ 9@ 9@ 9@
(7.6) 75 52 32 25 40 55
(5.2) (3.6) (2.2) (1.7) (2.8) (3.8)
30 12 @ 12 @ 12 @ 12 @ 12 @ 12 @
(9.1) 100 70 50 40 40 55

Protection for Automatic Storage


(6.9) (4.8) (3.5) (2.8) (2.8) (3.8)
40 20 @ 20 @ 20 @
(12.2) 75 61 55
(5.2) (4.2) (3.8)

FM Global Property Loss Prevention Data Sheets


Protection for Automatic Storage 8-34
FM Global Property Loss Prevention Data Sheets Page 31

Table 13. Ceiling-Level Protection Guidelines on a Dry System for Uncartoned Expanded Plastic Commodities Stored in
a Shuttle ASRS; No. of AS @ psi (bar)
Dry System, 280°F (140°C) Nominally Rated, Upright Sprinklers
Max. Ceiling Height, Standard-Response
ft (m) K11.2 (K160) K16.8 (K240) K25.2 (K360) K33.6 (K480)
10 (3.0) 25 @ 10 (0.7) 25 @ 7 (0.5) 25 @ 7 (0.5) 25 @ 50 (3.5)
15 (4.6) 25 @ 50 (3.5) 25 @ 22 (1.5) 25 @ 10 (0.7) 25 @ 50 (3.5)

2.2.3.2 Ceiling and In-Rack Sprinkler System Design Criteria for Closed-Top Combustible Containers,
or Storage on Trays
In-rack sprinklers are needed in combination with ceiling-level sprinklers when the guidelines from Section
2.2.3.1.1 are not met. Determine the recommended in-rack sprinkler horizontal arrangement in Section
2.2.3.2.1, the in-rack sprinkler vertical location and system design in Section 2.2.3.2.2, and the available
ceiling-level sprinkler designs in Section 2.2.3.2.3.

2.2.3.2.1 Horizontal Arrangement of In-Rack Sprinklers for the Protection of Closed-Top Combustible
Containers, or Storage on Trays in a Shuttle ASRS
Use Table 14 to determine the recommended horizontal in-rack sprinkler arrangements for the storage rack
to be protected.

Table 14. Recommended Horizontal In-Rack Sprinkler (i.e., IRAS) Arrangements for Closed-Top Combustible Containers,
or Storage on Trays
Adequate
Transverse Applicable
Overall Flue Spaces Horizontal
Maximum Provided per IRAS
Rack Row Rack Depth, Section IRAS Commodity Ceiling Aisle Width, Arrangement
Depth, ft (m) ft (m) 2.2.1.4? System Type Hazards Height, ft (m) ft (m) Figures
Up to 3 (0.9) 3 (0.9) No Wet or Dry Any Any Any 4
Yes Wet or Dry Any Any Any 4 or 5
Up to 6 (1.8) 6 (1.8) No Wet or Dry Any Any Any 6
Yes Wet or Dry Any ≤ 30 (9.1) < 3.5 (1.1) 6 or 7
Up to > 30 (9.1) < 4 (1.2) 6 or 7
Cartoned
Plastics
Any ≤ 30 (9.1) ≥ 3.5 (1.1) 6, 7 or 8
Up to > 30 (9.1) ≥ 4 (1.2) 6, 7 or 8
Cartoned
Plastics
Uncartoned > 30 (9.1) Any 6 or 7
Plastics
9 (2.7) No Wet or Dry Any Any Any 9
Yes Wet Up to ≤ 30 (9.1) < 3.5 (1.1) 9 or 10
Cartoned ≥ 3.5 (1.1) 9, 10 or 11
Plastics > 30 (9.1) < 4 (1.2) 9 or 10
≥ 4 (1.2) 9, 10 or 11
Uncartoned Any Any 9 or 10
Plastics
Dry Any Any Any 9 or 10
14 (4.3) No Wet or Dry Any Any Any 9
Yes Wet or Dry Any Any Any 9 or 10
Over 6 (1.8) Over 6 (1.8) No Wet or Dry Any Any Any 12 with
Vertical
Barriers
Yes Wet or Dry Any Any Any 13

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


8-34 Protection for Automatic Storage
Page 32 FM Global Property Loss Prevention Data Sheets

Tray or Closed-Top
Max. 2-1/2 ft
Container
(0.75 m)

Max
18 in. Max
1 2 3 4 5 6 7 8 3 ft
(450 mm)
(0.9 m)

The in-rack sprinkler numbers represent which IRAS


sprinklers to include in the hydraulic design
depending on the number of in-rack sprinklers
indicated for the in-rack sprinkler design Note: The in-rack sprinklers do not need
to align with the transverse flue spaces
located between the rack uprights

Fig. 4. Horizontal IRAS Arrangement for Closed-Top Combustible Containers, or Storage Trays within a Shuttle ASRS
Where Rack Row Depths Do Not Exceed 3 ft (0.9 m) per Table 14 and the Maximum Allowable Horizontal Spacing is 2-1/2
ft (0.75 m)

Tray or Closed-Top
Max. 5 ft
Container
(1.5 m)

Max
18 in. Max
1 2 3 4 5 6 7 8 3 ft
(450 mm)
(0.9 m)

The in-rack sprinkler numbers represent which IRAS


sprinklers to include in the hydraulic design
depending on the number of in-rack sprinklers
indicated for the in-rack sprinkler design

Fig. 5. Horizontal IRAS Arrangement for Closed-Top Combustible Containers, or Storage on Trays within a Shuttle ASRS
Where Rack Row Depths Do Not Exceed 3 ft (0.9 m) per Table 14, and the Maximum Allowable Horizontal Spacing is
5 ft (1.5 m)

Note: The in-rack sprinklers do not need Tray or Closed-Top


to align with the transverse flue spaces Max. 2-1/2 ft Container
located between the rack uprights (0.75 m)

Max
18 in.
(450 mm) 1 3 5 7

Max
6 ft
(1.8 m)

2 4 6 8

The in-rack sprinkler numbers represent which IRAS


sprinklers to include in the hydraulic design
depending on the number of in-rack sprinklers
indicated for the in-rack sprinkler design

Fig. 6. Horizontal IRAS Arrangement for Closed-Top Combustible Containers, or Storage on Trays within a Shuttle ASRS
Where Rack Row Depths Do Not Exceed 6 ft (1.8 m) per Table 14 and the Maximum Allowable Horizontal Spacing is
2-1/2 ft (0.75 m)

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


Protection for Automatic Storage 8-34
FM Global Property Loss Prevention Data Sheets Page 33

Tray or Closed-Top
Max. 5 ft Container
(0.75 m)

Max
18 in.
(450 mm) 1 3 5 7

Max
6 ft
(1.8 m)

2 4 6 8

The in-rack sprinkler numbers represent which IRAS


sprinklers to include in the hydraulic design
depending on the number of in-rack sprinklers
indicated for the in-rack sprinkler design
Fig. 7. Horizontal IRAS Arrangement for Closed-Top Combustible Containers, or Storage on Trays within a Shuttle ASRS
Where Rack Row Depths Do Not Exceed 6 ft (1.8 m) per Table 14 and the Maximum Allowable Horizontal Spacing is 5
ft (1.5 m)

Tray or Closed-Top
Max. 5 ft
Container
(1.5 m)

Max
1 2 3 4 5 6 7 8 6 ft
(1.8 m)

IRAS
The in-rack sprinkler numbers represent which sprinklers
to include in the hydraulic design depending on the
number of in-rack sprinklers indicated for the in-rack
sprinkler design

Fig. 8. Horizontal IRAS Arrangement Without Face Sprinklers for Closed-Top Combustible Containers, or Storage on Trays
within a Shuttle ASRS Where Rack Row Depths Do Not Exceed 6 ft (1.8 m) per Table 14 and the Maximum Allowable
Horizontal Spacing is 5 ft (1.5 m)

Note: The in-rack sprinklers do not need


Tray or Closed-Top
to align with the transverse flue spaces
Container Max. 2-1/2 ft
located between the rack uprights
(0.75 m)

Max
18 in.
(450 mm) 1 3 5 7

Max
5 ft
(1.5 m)

Max
2 ft 2 4 6
2 2
8
(0.6 m)

The in-rack sprinkler numbers represent which


sprinklers to include in the hydraulic design IRAS
depending on the number of in-rack sprinklers
indicated for the in-rack sprinkler design

Fig. 9. Horizontal IRAS Arrangement for Closed-Top Combustible Containers, or Storage on Trays within a Shuttle ASRS
Where the Overall Rack Depths Do Not Exceed 14 ft (4.3 m) per Table 14 and the Maximum Allowable Horizontal Spacing
is 2-1/2 ft (0.75 m)

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


8-34 Protection for Automatic Storage
Page 34 FM Global Property Loss Prevention Data Sheets

Tray or Closed-Top
Container Max. 5 ft
(1.5 m)

Max
18 in.
(450 mm) 1 3 5 7

Max
5 ft
(1.5 m)

Max
2 ft 2 4 6
2 2
8
(0.6 m)

The in-rack sprinkler numbers represent which


sprinklers to include in the hydraulic design IRAS
depending on the number of in-rack sprinklers
indicated for the in-rack sprinkler design

Fig. 10. Horizontal IRAS Arrangement for Closed-Top Combustible Containers, or Storage on Trays within a Shuttle ASRS
Where the Overall Rack Depths Do Not Exceed 14 ft (4.3 m) per Table 14 and the Maximum Allowable Horizontal Spacing
is 5 ft (1.5 m)

Tray or Closed-Top
Container Max. 5 ft
(1.5 m)

Max Max
1 ft 2
1 2 3
2 2
4 5 6 7 8 9 ft
(0.3 m) (2.7 m)

The in-rack sprinkler numbers represent which


sprinklers to include in the hydraulic design IRAS
depending on the number of in-rack sprinklers
indicated for the in-rack sprinkler design

Fig. 11. Horizontal IRAS Arrangement for Closed-Top Combustible Containers, or Storage on Trays within a Shuttle ASRS
Where the Overall Rack Depths Do Not Exceed 9 ft (2.7 m) per Table 14 and the Maximum Allowable Horizontal Spacing
is 5 ft (1.5 m)

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


Protection for Automatic Storage 8-34
FM Global Property Loss Prevention Data Sheets Page 35

Tray or Closed-Top Max


Container 2-1/2 ft
(0.75 m) IRAS

Max
18 in.
(450 mm) 2
1 3
2 5 7

Over
2 2
4 6 8 6 ft
(1.8 m)

Max. 5 ft
(1.5 m)

The in-rack sprinkler numbers represent which Note: The in-rack sprinklers do not need
sprinklers to include in the hydraulic design to align with the transverse flue spaces
depending on the number of in-rack sprinklers located between the rack uprights
indicated for the in-rack sprinkler design

Fig. 12. Horizontal IRAS Arrangement for Closed-Top Combustible Containers, or Storage on Trays within a Shuttle ASRS
Where Rack Row Depths Exceed 6 ft (1.8 m) in Depth per Table 14 and the Maximum Allowable Horizontal Spacing is
2-1/2 ft (0.75 m)

Tray or Closed-Top Max


Container 5 ft
(1.5 m) IRAS

Max
18 in.
(450 mm) 2
1 3
2 5 7

Over
2 2
4 6 8 6 ft
(1.8 m)

Max. 5 ft
(1.5 m)

The in-rack sprinkler numbers represent which


sprinklers to include in the hydraulic design
depending on the number of in-rack sprinklers
indicated for the in-rack sprinkler design

Fig. 13. Horizontal IRAS Arrangement for Closed-Top Combustible Containers, or Storage on Trays within a Shuttle ASRS
Where Rack Row Depths Exceed 6 ft (1.8 m) in Depth per Table 14 and the Maximum Allowable Horizontal Spacing is
5 ft (1.5 m)

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


8-34 Protection for Automatic Storage
Page 36 FM Global Property Loss Prevention Data Sheets

2.2.3.2.2 Vertical Location of In-Rack Sprinklers and In-Rack Sprinkler System Designs for the
Protection of Closed-Top Combustible Containers, or Storage on Trays
2.2.3.2.2.1 Storage Racks Not Requiring Vertical Barriers
1. When Section 2.2.1.4 indicates that vertical barriers are not required due to transverse flue spaces
being provided, use the following tables to determine the allowable in-rack sprinkler vertical locations,
as well as the corresponding recommended in-rack sprinkler design:
A. Table 15: Wet, In-Rack sprinkler system protecting a shuttle ASRS, or
B. Table 16: Dry, In-Rack sprinkler system protecting a shuttle ASRS
2. Any green highlighted protection cell within Table 15 represents (1) an arrangement where the in-rack
sprinkler system and the ceiling sprinkler system do not need to be hydraulically balanced at their point
of connection, and (2) a potential design where the top in-rack sprinkler tier level can represent a virtual
floor. The ceiling sprinkler system can be designed using the applicable protection table (i.e., Tables
4 through 13, depending on the commodity hazard being protected) with a ceiling height obtained by
taking the vertical distance between the top level of in-rack sprinklers and the actual ceiling above.
However, for this option to be applicable, the aisle width must be acceptable for a ceiling-only protection
option as indicated in Section 2.2.3.1.1.
3. While the in-rack sprinkler designs given in Tables 15 and 16 are based on flow, the corresponding
design pressure for the chosen in-rack sprinkler cannot be less than 7 psi (0.5 bar). When the design
pressure will be less than 7 psi (0.5 bar), use a minimum pressure of 7 psi (0.5 bar) for design
purposes, regardless of the in-rack sprinkler’s K-factor value.
2.2.3.2.2.2 Storage Racks Requiring Vertical Barriers
When Section 2.2.1.4 indicates that vertical barriers are required due to the lack of acceptable transverse
flue spaces, install the in-rack sprinklers vertically using the design guidelines indicated in Section 2.2.3.2.2.1.
However, include all the in-rack sprinklers installed between the vertical barriers in the in-rack sprinkler
design.
For example, if a wet, in-rack sprinkler system is being used to protect Class 3 commodity being stored within
a shuttle ASRS protected with in-rack sprinklers per Figure 6, and the number of in-rack sprinklers between
the vertical barriers is 9; the design for the in-rack sprinkler system would be per Table 15 and could use
either (1) 9 IRAS @ 30 gpm (115 L/min), which would require the ceiling and in-rack system to be hydraulically
balanced, or (2) 9 IRAS @ 65 gpm (250 L/min), which would avoid the need for the ceiling and in-rack
sprinkler system to be hydraulically balanced.

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


Protection for Automatic Storage 8-34
FM Global Property Loss Prevention Data Sheets Page 37

Table 15. Wet, In-Rack Sprinkler System Designs for the Protection of Closed-Top, Combustible Containers Stored in a
Shuttle ASRS
Hydraulically
Max. Min. IRAS Balance
Recommended Vertical Flow IRAS
Horizontal IRAS Maximum Distance Max. Ceiling Design, System with
Arrangement per Commodity Between Height, ft gpm Min. IRAS No. of IRAS Ceiling
Table 14 Hazard IRAS, ft (m) (m) (L/min)* K-factor in Design System?
Figure 4 Class 3 10 (3.0)** DNA 30 (115) 5.6 (80) 6 if one Yes
IRAS level
or 10 (5 on
top 2 levels)
65 (250) 14.0 (200) 5 on top No
Pendent IRAS level
Cartoned 10 (3.0)** DNA 30 (115) 5.6 (80) 8 if one Yes
Unexpanded IRAS level
Plastics or 14 (7 on
top 2 levels)
65 (250) 14.0 (200) 5 on top No
Pendent IRAS level
Cartoned 10 (3.0)** DNA 30 (115) 5.6 (80) 8 if one Yes
Expanded IRAS level
Plastics or 14 (7 on
top 2 levels)
100 (380) 14.0 (200) 5 on top No
Pendent IRAS level
Uncartoned 10 (3.0)** DNA 30 (115) 5.6 (80) 8 if one Yes
Unexpanded IRAS level
Plastics or 14 (7 on
top 2 levels)
120 (455) 22.4 (320) 5 on top No
Pendent IRAS level
Uncartoned 10 (3.0)** DNA 30 (115) 5.6 (80) 8 if one Yes
Expanded IRAS level
Plastics or 14 (7 on
top 2 levels)
120 (455) 22.4 (320) 5 & 2 on No
Pendent top IRAS
level***

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


8-34 Protection for Automatic Storage
Page 38 FM Global Property Loss Prevention Data Sheets

Table 15. Wet, In-Rack Sprinkler System Designs for the Protection of Closed-Top, Combustible Containers Stored in a
Shuttle ASRS (continued)
Hydraulically
Max. Min. IRAS Balance
Recommended Vertical Flow IRAS
Horizontal IRAS Maximum Distance Max. Ceiling Design, System with
Arrangement per Commodity Between Height, ft gpm Min. IRAS No. of IRAS Ceiling
Table 14 Hazard IRAS, ft (m) (m) (L/min)* K-factor in Design System?
Figures 5 or 7 Class 3 25 (7.6)** DNA 30 (115) 5.6 (80) 6 if one Yes
IRAS level
or 10 (5 on
top 2 levels)
30 (9.1) DNA 65 (250) 14.0 (200) 4 on top No
Pendent IRAS level
40 (12.2) DNA 120 (455) 22.4 (320) 4 on top No
Pendent IRAS level
Cartoned 20 (6.1)** DNA 30 (115) 5.6 (80) 8 if one Yes
Unexpanded IRAS level
Plastics or 14 (7 on
top 2 levels)
30 (9.1) DNA 65 (250) 14.0 (200) 4 on top No
Pendent IRAS level
40 (12.2) DNA 120 (455) 22.4 (320) 4 on top No
Pendent IRAS level
Cartoned 15 (4.6)** DNA 30 (115) 5.6 (80) 8 if one Yes
Expanded IRAS level
Plastics or 14 (7 on
top 2 levels)
30 (9.1) DNA 100 (380) 14.0 (200) 4 on top No
Pendent IRAS level
Uncartoned 10 (3.0)** DNA 30 (115) 5.6 (80) 8 if one Yes
Unexpanded IRAS level
Plastics or 14 (7 on
top 2 levels)
30 (9.1) DNA 120 (455) 22.4 (320) 4 on top No
Pendent IRAS level
Uncartoned 10 (3.0)** DNA 30 (115) 5.6 (80) 8 if one Yes
Expanded IRAS level
Plastics or 14 (7 on
top 2 levels)
30 (9.1) DNA 120 (455) 22.4 (320) 4 & 2 on No
Pendent top IRAS
level***

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


Protection for Automatic Storage 8-34
FM Global Property Loss Prevention Data Sheets Page 39

Table 15. Wet, In-Rack Sprinkler System Designs for the Protection of Closed-Top, Combustible Containers Stored in a
Shuttle ASRS (continue)
Hydraulically
Max. Min. IRAS Balance
Recommended Vertical Flow IRAS
Horizontal IRAS Maximum Distance Max. Ceiling Design, System with
Arrangement per Commodity Between Height, ft gpm Min. IRAS No. of IRAS Ceiling
Table 14 Hazard IRAS, ft (m) (m) (L/min)* K-factor in Design System?
Figure 6 Class 3 10 (3.0)** DNA 30 (115) 5.6 (80) 6 if one Yes
IRAS level
or 10 (5 on
top 2 levels)
65 (250) 14.0 (200) 6 on top No
Pendent IRAS level
Cartoned 10 (3.0)** DNA 30 (115) 5.6 (80) 8 if one Yes
Unexpanded IRAS level
Plastics or 14 (7 on
top 2 levels)
65 (250) 14.0 (200) 6 on top No
Pendent IRAS level
Cartoned 10 (3.0)** DNA 30 (115) 5.6 (80) 8 if one Yes
Expanded IRAS level
Plastics or 14 (7 on
top 2 levels)
100 (380) 14.0 (200) 6 on top No
Pendent IRAS level
Uncartoned 10 (3.0)** DNA 30 (115) 5.6 (80) 8 if one Yes
Unexpanded IRAS level
Plastics or 14 (7 on
top 2 levels)
120 (455) 22.4 (320) 6 on top No
Pendent IRAS level
Uncartoned 10 (3.0)** DNA 30 (115) 5.6 (80) 8 if one Yes
Expanded IRAS level
Plastics or 14 (7 on
top 2 levels)
120 (455) 22.4 (320) 6 & 2 on No
Pendent top IRAS
level***
*The indicated in-rack sprinkler design flow is based on a minimum 9 in. (225 mm) vertical distance between storage tier levels. If the vertical
distance between vertical tier levels is less than 9 in. (225 mm), add 20 gpm (75 L/min) to the indicated design flow.
**The maximum storage height above the top in-rack sprinkler level is 10 ft (3.0 m)
***The design “X & Y” accounts for X in-rack sprinklers in the most remote storage rack as well as the most remote Y in-rack sprinklers
in an adjacent storage rack. However, if the aisle width is 8 ft (2.4 m) or greater, the design does not have to account for the Y in-rack
sprinklers in the adjacent rack.

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


8-34 Protection for Automatic Storage
Page 40 FM Global Property Loss Prevention Data Sheets

Table 15. Wet, In-Rack Sprinkler System Designs for the Protection of Closed-Top, Combustible Containers Stored in a
Shuttle ASRS (continued)
Hydraulically
Max. Min. IRAS Balance
Recommended Vertical Flow IRAS
Horizontal IRAS Maximum Distance Max. Ceiling Design, System with
Arrangement per Commodity Between Height, ft gpm Min. IRAS No. of IRAS Ceiling
Table 14 Hazard IRAS, ft (m) (m) (L/min)* K-factor in Design System?
Figures 8 or 11 Class 3 10 (3.0)** DNA 30 (115) 5.6 (80) 6 if one Yes
IRAS level
or 10 (5 on
top 2 levels)
25 (7.6)** 30 (9.1) 30 (115) 5.6 (80) 6 if one Yes
IRAS level
or 10 (5 on
top 2 levels)
Cartoned 10 (3.0)** DNA 30 (115) 5.6 (80) 8 if one Yes
Unexpanded IRAS level
Plastics or 14 (7 on
top 2 levels)
20 (6.1)** 30 (9.1) 30 (115) 5.6 (80) 8 if one Yes
IRAS level
or 14 (7 on
top 2 levels)
Cartoned 15 (4.6)** 30 (9.1) 30 (115) 5.6 (80) 8 if one Yes
Expanded IRAS level
Plastics or 14 (7 on
top 2 levels)
Uncartoned 10 (3.0)** 30 (9.1) 30 (115) 5.6 (80) 8 if one Yes
Expanded IRAS level
Plastics or 14 (7 on
top 2 levels)

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


Protection for Automatic Storage 8-34
FM Global Property Loss Prevention Data Sheets Page 41

Table 15. Wet, In-Rack Sprinkler System Designs for the Protection of Closed-Top, Combustible Containers Stored in a
Shuttle ASRS (continued)
Hydraulically
Max. Min. IRAS Balance
Recommended Vertical Flow IRAS
Horizontal IRAS Maximum Distance Max. Ceiling Design, System with
Arrangement per Commodity Between Height, ft gpm Min. IRAS No. of IRAS Ceiling
Table 14 Hazard IRAS, ft (m) (m) (L/min)* K-factor in Design System?
Figures 9 or 12 Class 3 10 (3.0)** DNA 30 (115) 5.6 (80) 6 if one Yes
IRAS level
or 10 (5 on
top 2 levels)
65 (250) 14.0 (200) 6 on top No
Pendent IRAS level
Cartoned 10 (3.0)** DNA 30 (115) 5.6 (80) 8 if one Yes
Unexpanded IRAS level
Plastics or 14 (7 on
top 2 levels)
65 (250) 14.0 (200) 6 on top No
Pendent IRAS level
Cartoned 10 (3.0)** DNA 30 (115) 5.6 (80) 8 if one Yes
Expanded IRAS level
Plastics or 14 (7 on
top 2 levels)
100 (380) 14.0 (200) 6 on top No
Pendent IRAS level
Uncartoned 110 (3.0)** DNA 30 (115) 5.6 (80) 8 if one Yes
Unexpanded IRAS level
Plastics or 14 (7 on
top 2 levels)
120 (455) 22.4 (320) 6 on top No
Pendent IRAS level
Uncartoned 10 (3.0)** DNA 30 (115) 5.6 (80) 8 if one Yes
Expanded IRAS level
Plastics or 14 (7 on
top 2 levels)
120 (455) 22.4 (320) 6 & 4 on No
Pendent top IRAS
level***

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


8-34 Protection for Automatic Storage
Page 42 FM Global Property Loss Prevention Data Sheets

Table 15. Wet, In-Rack Sprinkler System Designs for the Protection of Closed-Top, Combustible Containers Stored in a
Shuttle ASRS (continued)
Hydraulically
Max. Min. IRAS Balance
Recommended Vertical Flow IRAS
Horizontal IRAS Maximum Distance Max. Ceiling Design, System with
Arrangement per Commodity Between Height, ft gpm Min. IRAS No. of IRAS Ceiling
Table 14 Hazard IRAS, ft (m) (m) (L/min)* K-factor in Design System?
Figures 10 or 13 Class 3 25 (7.6)** DNA 30 (115) 5.6 (80) 6 if one Yes
IRAS level
or 10 (5 on
top 2 levels)
30 (9.1) DNA 65 (250) 14.0 (200) 6 on top No
Pendent IRAS level
40 (12.2) DNA 120 (455) 22.4 (320) 6 on top No
Pendent IRAS level
Cartoned 20 (6.1)** DNA 30 (115) 5.6 (80) 8 if one Yes
Unexpanded IRAS level
Plastics or 14 (7 on
top 2 levels)
30 (9.1) DNA 65 (250) 14.0 (200) 6 on top No
Pendent IRAS level
40 (12.2) DNA 120 (455) 22.4 (320) 6 on top No
Pendent IRAS level
Cartoned 15 (4.6)** DNA 30 (115) 5.6 (80) 8 if one Yes
Expanded IRAS level
Plastics or 14 (7 on
top 2 levels)
30 (9.1) DNA 100 (380) 14.0 (200) 6 on top No
Pendent IRAS level
Uncartoned 10 (3.0)** DNA 30 (115) 5.6 (80) 8 if one Yes
Unexpanded IRAS level
Plastics or 14 (7 on
top 2 levels)
30 (9.1) DNA 120 (455) 22.4 (320) 6 on top No
Pendent IRAS level
Uncartoned 10 (3.0)** DNA 30 (115) 5.6 (80) 8 if one Yes
Expanded IRAS level
Plastics or 14 (7 on
top 2 levels)
30 (9.1) DNA 120 (455) 22.4 (320) 6 & 4 on No
Pendent top IRAS
level***
* The indicated in-rack sprinkler design flow is based on a minimum 9 in. (225 mm) vertical distance between storage tier levels. If the vertical
distance between vertical tier levels is less than 9 in. (225 mm), add 20 gpm (75 L/min) to* the indicated design flow.
** The maximum storage height above the top in-rack sprinkler level is 10 ft (3.0 m)
*** The design “X & Y” accounts for X in-rack sprinklers in the most remote storage rack as well as the most remote Y in-rack sprinklers
in an adjacent storage rack. However, if the aisle width is 8 ft (2.4 m) or greater, the design does not have to account for the Y in-rack
sprinklers in the adjacent rack.

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


Protection for Automatic Storage 8-34
FM Global Property Loss Prevention Data Sheets Page 43

Table 16. Dry, In-Rack Sprinkler Designs for the Protection of Closed-Top, Combustible Containers Stored in a Shuttle
ASRS
Max. Hydraulically
Vertical Min. IRAS Balance
Distance Flow IRAS
Recommended Maximum Between Max. Ceiling Design, System with
IRAS Arrangement Commodity IRAS, ft Height, ft gpm Min. IRAS No. of IRAS Ceiling
per Table 14 Hazard (m)* (m) (L/min)** K-factor in Design System?
Figures 4, 5, 6, 7, Class 3 25 (7.6) DNA 30 (115) 5.6 (80) 6 if one Yes
9, 10, 12, or 13 IRAS level
or 10 (5 on
top 2 levels)
Cartoned 20 (6.1) DNA 30 (115) 5.6 (80) 8 if one Yes
Unexpanded IRAS level
Plastics or 14 (7 on
top 2 levels)
Cartoned 15 (4.6) DNA 30 (115) 5.6 (80) 8 if one Yes
Expanded IRAS level
Plastics or 14 (7 on
top 2 levels)
Uncartoned 10 (3.0) DNA 30 (115) 5.6 (80) 8 if one Yes
Expanded IRAS level
Plastics or 14 (7 on
top 2 levels)
Figures 8 or 11 Class 3 25 (7.6) 30 (9.1) 30 (115) 5.6 (80) 6 if one Yes
IRAS level
or 10 (5 on
top 2 levels)
Cartoned 20 (6.1) 30 (9.1) 30 (115) 5.6 (80) 8 if one Yes
Unexpanded IRAS level
Plastics or 14 (7 on
top 2 levels)
Cartoned 15 (4.6) 30 (9.1) 30 (115) 5.6 (80) 8 if one Yes
Expanded IRAS level
Plastics or 14 (7 on
top 2 levels)
Uncartoned 10 (3.0) 30 (9.1) 30 (115) 5.6 (80) 8 if one Yes
Expanded IRAS level
Plastics or 14 (7 on
top 2 levels)
*The maximum storage height above the top in-rack sprinkler level is 10 ft (3.0 m).
**The indicated in-rack sprinkler design flow is based on a minimum 9 in. (225 mm) vertical distance between storage tier levels. If the vertical
distance between vertical tier levels is less than 9 in. (225 mm), add 20 gpm (75 L/min) to the indicated design flow.

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


8-34 Protection for Automatic Storage
Page 44 FM Global Property Loss Prevention Data Sheets

2.2.3.2.3 Ceiling Sprinkler System Designs in Combination with In-Rack Sprinklers for the Protection
of Closed-Top Combustible Containers, or Storage on Trays
2.2.3.2.3.1 For wet ceiling sprinkler systems, when Table 15 or Section 2.2.3.2.2.2 indicates the storage height
above the top in-rack sprinkler level be limited to 10 ft (3.0 m), use Table 17 to determine how to obtain the
ceiling sprinkler system design. If a protection option is not available from the applicable protection table,
either:
1. Install a flat, continuous, noncombustible false ceiling capable of withstanding an uplift pressure of 3
lb./ft² (14.4 kg/m²) over, and for a minimum of 15 ft (4.6 m) beyond, the ASRS storage area in all
directions, with sprinklers installed underneath the false ceiling in accordance with Table 17, or
2. Install in-rack sprinklers over the top of storage and design the ceiling sprinkler system per Table 17.
2.2.3.2.3.2 For wet ceiling sprinkler systems, when Section 2.2.3.2.2.2 is not applicable and Table 15 does
not limit the storage height above the top in-rack sprinkler level, the ceiling sprinkler system can be designed
using the applicable protection table (i.e., Tables 4, 6, 8, 10, and 12, depending on the commodity hazard
being protected). The ceiling height to be used in the protection table is obtained by taking the vertical
distance between the top in-rack sprinkler level and the ceiling. Note that if no storage is to be maintained
above the top in-rack sprinkler level, the ceiling design can be determined using the lowest ceiling height given
in the protection table.
2.2.3.2.3.3 For dry ceiling sprinkler systems, use Table 18 to determine how to obtain the ceiling sprinkler
system design. If a protection option is not available from the applicable protection table, either:
1. Install a flat, continuous, noncombustible false ceiling, capable of withstanding an uplift pressure of 3
lb/ft² (14.4 kg/m²), over the ASRS storage area and for a minimum of 15 ft (4.6 m) beyond the ASRS
area in all directions with sprinklers installed underneath the false ceiling in accordance with Table 18,
or
2. Install in-rack sprinklers over the top of storage and design the ceiling sprinkler system per Table 18.
2.2.3.2.3.4 See Section 2.2.1.6 to determine the ceiling sprinkler’s hose demand design and water supply
duration.
2.2.3.2.3.5 See Section 2.1.4.5.4 to determine the number of sprinklers per branch line for ceiling-level
sprinkler calculations.

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


Protection for Automatic Storage 8-34
FM Global Property Loss Prevention Data Sheets Page 45

Table 17. Determining the Applicable Protection Table and Ceiling Height for Ceiling Sprinkler Designs when Wet
Ceiling-Level Sprinkler Systems are Supplemented with In-Rack Sprinklers to Protect Closed-Top Combustible Containers,
or Storage on Trays in a Shuttle ASRS
Max.
Max. Storage Clearance
Height Between Top
Maximum Material Above Top of Storage Applicable
Commodity Handling IRAS Level, and Ceiling, Protection Applicable Ceiling Height to Use in
Hazard Method ft (m) ft (m) Table to Use Indicated Protection Table, ft (m)
Class 3 Directly on 0 (0) Any 4 10 (3.0)
Supporting 5 (1.5) 5 (1.5) 4 10 (3.0)
Rails 20 (6.1) 4 20 (6.1)
> 20 (6.1) 4 Vertical distance between top IRAS level
and ceiling
10 (3.0) Any 4 Vertical distance between top IRAS level
and ceiling
On Trays 0 (0) Any 10 10 (3.0)
5 (1.5) 5 (1.5) 10 10 (3.0)
10 (3.0) 10 15 (4.6)
20 (6.1) 10 20 (6.1)
> 20 (6.1) 10 Vertical distance between top IRAS level
and ceiling
10 (3.0) Any 10 Vertical distance between top IRAS level
and ceiling
Cartoned Directly on 0 (0) Any 6 10 (3.0)
Unexpanded Supporting 5 (1.5) 5 (1.5) 6 10 (3.0)
Plastics Rails 10 (3.0) 6 15 (4.6)
20 (6.1) 6 20 (6.1)
> 20 (6.1) 6 Vertical distance between top IRAS level
and ceiling
10 (3.0) Any 6 Vertical distance between top IRAS level
and ceiling
On Trays 0 (0) Any 10 10 (3.0)
5 (1.5) 5 (1.5) 10 10 (3.0)
10 (3.0) 10 15 (4.6)
20 (6.1) 10 20 (6.1)
> 20 (6.1) 10 Vertical distance between top IRAS level
and ceiling
10 (3.0) Any 10 Vertical distance between top IRAS level
and ceiling
Cartoned Directly on 0 (0) Any 8 10 (3.0)
Expanded Supporting 5 (1.5) 5 (1.5) 8 10 (3.0)
Plastics Rails 20 (6.1) 8 20 (6.1)
> 20 (6.1) 8 Vertical distance between top IRAS level
and ceiling
10 (3.0) Any 8 Vertical distance between top IRAS level
and ceiling
On Trays 0 (0) Any 10 10 (3.0)
5 (1.5) 5 (1.5) 10 10 (3.0)
10 (3.0) 10 15 (4.6)
20 (6.1) 10 20 (6.1)
> 20 (6.1) 10 Vertical distance between top IRAS level
and ceiling
10 (3.0) Any 10 Vertical distance between top IRAS level
and ceiling

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


8-34 Protection for Automatic Storage
Page 46 FM Global Property Loss Prevention Data Sheets

Table 17. Determining the Applicable Protection Table and Ceiling Height for Ceiling Sprinkler Designs when Wet
Ceiling-Level Sprinkler Systems are Supplemented with In-Rack Sprinklers to Protect Closed-Top, Combustible Containers
Stored Directly on the Shuttle Rack’s Horizontal Supporting Rails, or Non-Open Top Storage Maintained on Trays in a
Shuttle ASRS (continued)
Max.
Max. Storage Clearance
Height Between Top
Maximum Material Above Top of Storage Applicable
Commodity Handling IRAS Level, and Ceiling, Protection Applicable Ceiling Height to Use in
Hazard Method ft (m) ft (m) Table to Use Indicated Protection Table, ft (m)
Uncartoned Directly on 0 (0) Any 10 10 (3.0)
Unexpanded Supporting 5 (1.5) 5 (1.5) 10 10 (3.0)
Plastics Rails or On 10 (3.0) 10 15 (4.6)
Trays 20 (6.1) 10 20 (6.1)
> 20 (6.1) 10 Vertical distance between top IRAS level
and ceiling
10 (3.0) Any 10 Vertical distance between top IRAS level
and ceiling
Uncartoned Directly on 0 (0) Any 12 10 (3.0)
Expanded Supporting 5 (1.5) 5 (1.5) 12 10 (3.0)
Plastics Rails or On 10 (3.0) 12 15 (4.6)
Trays 20 (6.1) 12 25 (7.6)
> 20 (6.1) 12 Vertical distance between top IRAS level
and ceiling
10 (3.0) Any 12 Vertical distance between top IRAS level
and ceiling

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


Protection for Automatic Storage 8-34
FM Global Property Loss Prevention Data Sheets Page 47

Table 18. Determining the Applicable Protection Table and Ceiling Height for Ceiling Sprinkler Designs when Dry
Ceiling-Level Sprinkler Systems are Supplemented with In-Rack Sprinklers to Protect Closed-Top Combustible Containers,
or Storage on Trays in a Shuttle ASRS
Applicable Ceiling
Max. Clearance Height to Use in
Maximum Max. Storage Between Top of Applicable Indicated
Commodity Material Handling Height Above Top Storage and Protection Table Protection Table,
Hazard Method IRAS Level, ft (m) Ceiling, ft (m) to Use ft (m)
Class 3 Directly on 0 (0) Any 5 10 (3.0)
Supporting Rails 5 (1.5) 5 (1.5) 5 20 (6.1)
20 (6.1) 5 25 (7.6)
10 (3.0) 5 (1.5) 5 25 (7.6)
20 (6.1) 5 30 (9.1)
On Trays 0 (0) Any 5 20 (6.1)
5 (1.5) 5 (1.5) 11 10 (3.0)
10 (3.0) 11 15 (4.6)
10 (3.0) 5 (1.5) 11 15 (4.6)
Cartoned Directly on 0 (0) Any 7 10 (3.0)
Unexpanded Supporting Rails 5 (1.5) 5 (1.5) 5 20 (6.1)
Plastics 10 (3.0) 7 15 (4.6)
20 (6.1) 7 20 (6.1)
10 (3.0) 5 (1.5) 7 20 (6.1)
20 (6.1) 7 25 (7.6)
On Trays 0 (0) Any 5 20 (6.1)
5 (1.5) 5 (1.5) 11 10 (3.0)
10 (3.0) 11 15 (4.6)
10 (3.0) 5 (1.5) 11 15 (4.6)
Cartoned Directly on 0 (0) Any 5 20 (6.1)
Expanded Supporting Rails 5 (1.5) 5 (1.5) 5 20 (6.1)
Plastics 20 (6.1) 9 20 (6.1)
10 (3.0) 5 (1.5) 9 20 (6.1)
10 (3.0) 7 25 (7.6)
On Trays (0) Any 5 20 (6.1)
5 (1.5) 5 (1.5) 11 10 (3.0)
10 (3.0) 11 15 (4.6)
10 (3.0) 5 (1.5) 11 15 (4.6)
Uncartoned Directly on 0 (0) Any 11 10 (3.0)
Unexpanded Supporting Rails 5 (1.5) 5 (1.5) 11 10 (3.0)
Plastics or On Trays 10 (3.0) 11 15 (4.6)
10 (3.0) 5 (1.5) 11 15 (4.6)
Uncartoned Directly on 0 (0) Any 11 10 (3.0)
Expanded Supporting Rails 5 (1.5) 5 (1.5) 13 10 (3.0)
Plastics or On Trays 10 (3.0) 13 15 (4.6)
10 (3.0) 5 (1.5) 13 15 (4.6)

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


8-34 Protection for Automatic Storage
Page 48 FM Global Property Loss Prevention Data Sheets

2.2.4 Protection of Horizontal-Loading Shuttle ASRS Storage Arrangements Where Open-Top,


Combustible Containers are Being Used
Note that the protection of expanded plastic containers is outside the scope of this data sheet.
Section 2.2.4 is organized as follows:
• Section 2.2.4.1 determines if a ceiling-only protection option is available and, if it is, the recommended
ceiling-only protection designs.
• Section 2.2.4.2 determines the recommended designs when both ceiling and in-rack sprinklers are installed.
This section is further broken down into the following subsections:
- Section 2.2.4.2.1 provides acceptable horizontal in-rack sprinkler arrangements.
- Section 2.2.4.2.2 provides both the acceptable vertical in-rack sprinkler arrangements as well as the
corresponding in-rack sprinkler system design.
- Section 2.2.4.2.3 provides the acceptable ceiling sprinkler system design with the chosen in-rack sprinkler
system arrangement.

2.2.4.1 Ceiling-Only Sprinkler System Design Criteria for Horizontal-Loading Shuttle ASRS Storage
Arrangements Using Open-Top, Combustible Containers
2.2.4.1.1 A ceiling-only sprinkler system protection scheme is possible when:
1. Adequate vertically aligned transverse flue spaces are provided as outlined in Section 2.2.1.4, and
2. The storage height does not exceed 10 ft (3.0 m), and
3. A ceiling-only protection is provided in the applicable protection table (Tables 20 and 21) for the specific
sprinkler being installed at ceiling level, and
4. The water supply can provide the flow and pressure requirements for the protection option chosen
from the applicable protection table.
If the conditions outlined in (1) through (4) cannot be met, see Section 2.2.4.2 regarding the guidelines for
installing in-rack sprinklers in combination with ceiling-level sprinklers.
2.2.4.1.2 When a ceiling-only protection scheme is acceptable per items (1) through (4) in Section 2.2.4.1.1,
use Table 19 to determine which protection table to use for obtaining the recommended ceiling sprinkler
design depending on the commodity hazard and the type of ceiling sprinkler system (i.e., wet or dry) being
installed.

Table 19. Determining Which Ceiling Sprinkler Protection Table to Use for the Protection of Horizontal-Loading Shuttle
ASRS Storage Arrangements Where Open-Top, Combustible Containers are Being Used
Commodity Classification Ceiling Sprinkler System Type Protection Table to Use
Class 1 through 4, Cartoned Plastics, Wet 20
and Uncartoned Plastics Dry 21
Note: In Table 19, the ceiling-level protection options highlighted in green represent those for which the hose stream demand is 250 gpm
(950 L/min) and the sprinkler system duration is 1 hour.

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


Table 20. Wet Sprinkler System Ceiling-Level Protection Guidelines for Open-Top, Combustible Container Storage up to a Maximum of 10 ft (3.0 m) in a Shuttle ASRS; No. of AS

FM Global Property Loss Prevention Data Sheets


Protection for Automatic Storage
@ psi (bar)
Wet System, 160°F (70°C) Nominally Rated, Upright
Max. Wet System, 160°F (70°C) Nominally Rated, Pendent Sprinklers Sprinklers
Ceiling Quick-Response Standard-Response Quick-Response Standard-Response
Height, K11.2 K14.0 K16.8 K22.4 K25.2 K25.2EC K28.0 K33.6 K11.2 K14.0 K19.6 K25.2 K11.2 K14.0 K16.8 K25.2EC K11.2 K16.8 K25.2
ft (m) (K160) (K200) (K240) (K320) (K360) (K360EC) (K400) (K480) (K160) (K200) (K280) (K360) (K160) (K200) (K240) (K360EC) (K160) (K240) (K360)
10 25 @ 12 @ 12 @ 9@ 9 @ 12 @ 38 9 @ 9@ 25 @ 25 @ 25 @ 25 @ 25 @ 25 @ 25 @ 12 @ 38 25 @ 25 @ 25 @
(3.0) 50 25 18 20 20 (2.6) 40 55 50 32 16 10 50 32 18 (2.6) 50 18 10
(3.5) (1.7) (1.2) (1.4) (1.4) (2.8) (3.8) (3.5) (2.2) (1.1) (0.7) (3.5) (2.2) (1.2) (3.5) (1.2) (0.7)
15 12 @ 12 @ 12 @ 10 @ 9@ 9@
©2017-2023 Factory Mutual Insurance Company. All rights reserved.

(4.6) 50 35 20 20 40 55
(3.5) (2.4) (1.4) (1.4) (2.8) (3.8)
20 12 @ 12 @ 12 @ 12 @ 9@ 9@
(6.1) 75 52 29 23 40 55
(5.2) (3.6) (2.0) (1.6) (2.8) (3.8)

Page 49
8-34
8-34 Protection for Automatic Storage
Page 50 FM Global Property Loss Prevention Data Sheets

Table 21. Dry Sprinkler System Ceiling-Level Protection Guidelines for Open-Top, Combustible Container Storage up to
a Maximum of 10 ft (3.0 m) in a Shuttle ASRS; No. of AS @ psi (bar)
Dry System, 280°F (140°C) Nominally Rated, Upright Sprinklers
Max. Ceiling Height, ft Standard-Response
(m) K11.2 (K160) K16.8 (K240) K25.2 (K360) K33.6 (K480)
10 (3.0) 30 @ 50 (3.5) 30 @ 18 (1.2) 30 @ 10 (0.7) 30 @ 50 (3.5)

2.2.4.1.3 See Section 2.2.1.6 to determine the ceiling sprinkler’s hose demand design and water supply
duration.
2.2.4.1.4 See Section 2.1.4.5.4 to determine the number of sprinklers per branch line for ceiling-level sprinkler
calculations.

2.2.4.2 Ceiling and In-Rack Sprinkler System Design Criteria for Horizontal-Loading Shuttle ASRS
Storage Arrangements Using Open-Top, Combustible Containers
In-rack sprinklers are needed in combination with ceiling-level sprinklers when the guidelines from Section
2.2.4.1.1 are not met. Determine the recommended in-rack sprinkler horizontal arrangement in Section
2.2.4.2.1, the in-rack sprinkler vertical location and system design in Section 2.2.4.2.2, and the available
ceiling-level sprinkler designs in Section 2.2.4.2.3.

2.2.4.2.1 Horizontal Arrangement of In-Rack Sprinklers for the Protection of Open-Top, Combustible
Containers in a Shuttle ASRS
Use Table 22 to determine the recommended horizontal in-rack sprinkler arrangement for the storage rack
to be protected.

Table 22. Recommended Horizontal In-Rack Sprinkler Arrangements for the Protection of Open-Top, Combustible
Containers in a Shuttle ASRS
Adequate Transverse Applicable Horizontal
Rack Row Depth, ft Overall Maximum Flue Spaces Provided Open-Top Container IRAS Arrangement
(m) Rack Depth, ft (m) per Section 2.2.1.4? Composition Figures
Up to 3 (0.9) 3 (0.9) No Cardboard or 14
Unexpanded Plastic
Yes Cardboard 15
Unexpanded Plastic 16
Up to 6 (1.8) 6 (1.8) No Cardboard or 17
Unexpanded Plastic
Yes Cardboard 18
Unexpanded Plastic 19
14 (4.3) No Cardboard or 20
Unexpanded Plastic
Yes Cardboard 21
Unexpanded Plastic 22
Over 6 (1.8) Over 6 (1.8) No Cardboard or 23 with Vertical
Unexpanded Plastic Barriers
Yes Cardboard 24
Unexpanded Plastic 25

2.2.4.2.2 Vertical Location of In-Rack Sprinklers and In-Rack Sprinkler System Designs for the
Protection of Open-Top, Combustible Containers in a Shuttle ASRS
2.2.4.2.2.1 Storage Racks Not Requiring Vertical Barriers
1. When Section 2.2.1.4 indicates that vertical barriers are not required due to transverse flue spaces
being provided, use Table 23 to determine the allowable in-rack sprinkler vertical locations as well as
the corresponding recommended in-rack sprinkler design.

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


Protection for Automatic Storage 8-34
FM Global Property Loss Prevention Data Sheets Page 51

Max. 2-1/2 ft Open-Top


(0.75 m) Container

Max
18 in. Max
1 2 3 4 5 6 7 8 3 ft
(450 mm)
(0.9 m)

The in-rack sprinkler numbers represent which IRAS


sprinklers to include in the hydraulic design
depending on the number of in-rack sprinklers
indicated for the in-rack sprinkler design Note: The in-rack sprinklers do not need
to align with the transverse flue spaces
located between the rack uprights

Fig. 14. Horizontal IRAS Arrangement for Open-Top Combustible Containers within a Shuttle ASRS Where Rack Row
Depths Do Not Exceed 3 ft (0.9 m) and the Maximum Horizontal Spacing is 2-1/2 ft (0.75 m) per Table 22

Open-Top
Max. 2 ft
Container
(0.6 m)

Max
18 in. Max
1 2 3 4 5 6 7 8 3 ft
(450 mm)
(0.9 m)

The in-rack sprinkler numbers represent which IRAS


sprinklers to include in the hydraulic design
depending on the number of in-rack sprinklers
indicated for the in-rack sprinkler design

Fig. 15. Horizontal IRAS Arrangement for Open-Top Combustible Containers within a Shuttle ASRS Where Rack Row
Depths Do Not Exceed 3 ft (0.9 m) and the Maximum Horizontal Spacing is 2 ft (0.60 m) per Table 22

Max. 4 ft Open-Top
(1.2 m) Container

Max
18 in. Max
1 2 3 4 5 6 7 8 3 ft
(450 mm)
(0.9 m)

The in-rack sprinkler numbers represent which IRAS


sprinklers to include in the hydraulic design
depending on the number of in-rack sprinklers
indicated for the in-rack sprinkler design

Fig. 16. Horizontal IRAS Arrangement for Open-Top Combustible Containers within a Shuttle ASRS Where Rack Row
Depths Do Not Exceed 3 ft (0.9 m) and the Maximum Horizontal Spacing is 4 ft (1.2 m) per Table 22

2. Limit the storage height above the top in-rack sprinkler level to a maximum height of 10 ft (3.0 m).
3. While the in-rack sprinkler designs given in Table 23 are based on flow, the corresponding design
pressure for the chosen in-rack sprinkler cannot be less than 7 psi (0.5 bar). When the design pressure
will be less than 7 psi (0.5 bar), use a minimum pressure of 7 psi (0.5 bar) for design purposes,
regardless of the in-rack sprinkler’s K-factor value.

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


8-34 Protection for Automatic Storage
Page 52 FM Global Property Loss Prevention Data Sheets

Note: The in-rack sprinklers do not need Open-Top


to align with the transverse flue spaces Max. 2-1/2 ft
(0.75 m) Container
located between the rack uprights

Max
18 in.
(450 mm) 1 3 5 7

Max
6 ft
(1.8 m)

2 4 6 8

The in-rack sprinkler numbers represent which IRAS


sprinklers to include in the hydraulic design
depending on the number of in-rack sprinklers
indicated for the in-rack sprinkler design

Fig. 17. Horizontal IRAS Arrangement for Open-Top Combustible Containers within a Shuttle ASRS Where Rack Row
Depths Do Not Exceed 6 ft (1.8 m) and the Maximum Horizontal Spacing is 2-1/2 ft (0.75 m) per Table 22

Max. 2 ft Open-Top
(0.6 m) Container

Max
18 in.
(450 mm) 1 3 5 7

Max
6 ft
(1.8 m)

2 4 6 8

The in-rack sprinkler numbers represent which IRAS


sprinklers to include in the hydraulic design
depending on the number of in-rack sprinklers
indicated for the in-rack sprinkler design

Fig. 18. Horizontal IRAS Arrangement for Open-Top Combustible Containers within a Shuttle ASRS Where Rack Row
Depths Do Not Exceed 6 ft (1.8 m) and the Maximum Horizontal Spacing is 2 ft (0.60 m) per Table 22

2.2.4.2.2.2 Storage Racks Requiring Vertical Barriers


When Section 2.2.1.4 indicates that vertical barriers are required due to the lack of acceptable transverse
flue spaces, install the in-rack sprinklers vertically using the design guidelines indicated in Section 2.2.4.2.2.1.
However, include all of the in-rack sprinklers installed between the vertical barriers in the in-rack sprinkler
design.
For example, if a wet, in-rack sprinkler system is being used to protect open-top, unexpanded plastic
containers being stored within a shuttle ASRS which is to be protected with in-rack sprinklers per Figure 17,
and the number of in-rack sprinklers between the vertical barriers is nine, then the design for the in-rack
sprinkler system would be per Table 23 and would be based on 9 IRAS @ 100 gpm (380 L/min) instead of
6 IRAS @ 100 gpm (380 L/min).

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


Protection for Automatic Storage 8-34
FM Global Property Loss Prevention Data Sheets Page 53

Max. 4 ft Open-Top
(1.2 m) Container

Max
18 in.
(450 mm) 1 3 5 7

Max
6 ft
(1.8 m)

2 4 6 8

The in-rack sprinkler numbers represent which IRAS


sprinklers to include in the hydraulic design
depending on the number of in-rack sprinklers
indicated for the in-rack sprinkler design

Fig. 19. Horizontal IRAS Arrangement for Open-Top Combustible Containers within a Shuttle ASRS Where Rack Row
Depths Do Not Exceed 6 ft (1.8 m) and the Maximum Horizontal Spacing is 4 ft (1.2 m) per Table 22

Note: The in-rack sprinklers do not need


Open-Top
to align with the transverse flue spaces
Container Max. 2-1/2 ft
located between the rack uprights
(0.75 m)

Max
18 in.
(450 mm) 1 3 5 7

Max
5 ft
(1.5 m)

Max
2 ft 2 4 6
2 2
8
(0.6 m)

The in-rack sprinkler numbers represent which


sprinklers to include in the hydraulic design IRAS
depending on the number of in-rack sprinklers
indicated for the in-rack sprinkler design

Fig. 20. Horizontal IRAS Arrangement for Open-Top Combustible Containers within a Shuttle ASRS Where the Overall
Rack Depths Do Not Exceed 14 ft (4.3 m) and the Maximum Horizontal Spacing is 2-1/2 ft (0.75 m) per Table 22

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


8-34 Protection for Automatic Storage
Page 54 FM Global Property Loss Prevention Data Sheets

Open-Top
Container Max. 2 ft
(0.6 m)

Max
18 in.
(450 mm) 1 3 5 7

Max
5 ft
(1.5 m)

Max
2 ft 2 4 6
2 2
8
(0.6 m)

The in-rack sprinkler numbers represent which


sprinklers to include in the hydraulic design IRAS
depending on the number of in-rack sprinklers
indicated for the in-rack sprinkler design

Fig. 21. Horizontal IRAS Arrangement for Open-Top Combustible Containers within a Shuttle ASRS Where the Overall
Rack Depths Do Not Exceed 14 ft (4.3 m) and the Maximum Horizontal Spacing is 2 ft (0.60 m) per Table 22

Open-Top
Container Max. 4 ft
(1.2 m)

Max
18 in.
(450 mm) 1 3 5 7

Max
5 ft
(1.5 m)

Max
2 ft 2 4 6
2 2
8
(0.6 m)

The in-rack sprinkler numbers represent which


sprinklers to include in the hydraulic design IRAS
depending on the number of in-rack sprinklers
indicated for the in-rack sprinkler design

Fig. 22. Horizontal IRAS Arrangement for Open-Top Combustible Containers within a Shuttle ASRS Where the Overall
Rack Depths Do Not Exceed 14 ft (4.3 m) and the Maximum Horizontal Spacing is 4 ft (1.2 m) per Table 22

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


Protection for Automatic Storage 8-34
FM Global Property Loss Prevention Data Sheets Page 55

Note: The in-rack sprinklers do not need


Max
Open-Top 2-1/2 ft to align with the transverse flue spaces
Container (0.75 m) located between the rack uprights

Max
18 in.
(450 mm) 2
1 3
2 5 7

Over
2 2
4 6 8 6 ft
(1.8 m)

Max. 4 ft
(1.2 m)

The in-rack sprinkler numbers represent which


sprinklers to include in the hydraulic design IRAS
depending on the number of in-rack sprinklers
indicated for the in-rack sprinkler design

Fig. 23. Horizontal IRAS Arrangement for Open-Top Combustible Containers within a Shuttle ASRS Where Rack Row
Depths Exceed 6 ft (1.8 m) and the Maximum Horizontal Spacing is 2-1/2 ft (0.75 m) per Table 22

Open-Top Max
Container 2 ft
(0.6 m) IRAS

Max
18 in.
(450 mm) 2
1 3
2 5 7

Over
2 2
4 6 8 6 ft
(1.8 m)

Max. 4 ft
(1.2 m)

The in-rack sprinkler numbers represent which


sprinklers to include in the hydraulic design
depending on the number of in-rack sprinklers
indicated for the in-rack sprinkler design

Fig. 24. Horizontal IRAS Arrangement for Open-Top Combustible Containers within a Shuttle ASRS Where Rack Row
Depths Exceed 6 ft (1.8 m) and the Maximum Horizontal Spacing is 2 ft (0.60 m) per Table 22

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


8-34 Protection for Automatic Storage
Page 56 FM Global Property Loss Prevention Data Sheets

Max
Open-Top 4 ft
Container (1.2 m) IRAS

Max
18 in.
(450 mm) 2
1 3
2 5 7

Over
2 2
4 6 8 6 ft
(1.8 m)

Max. 4 ft
(1.2 m)

The in-rack sprinkler numbers represent which


sprinklers to include in the hydraulic design
depending on the number of in-rack sprinklers
indicated for the in-rack sprinkler design

Fig. 25. Horizontal IRAS Arrangement for Open-Top Combustible Containers within a Shuttle ASRS Where Rack Row
Depths Exceed 6 ft (1.8 m) and the Maximum Horizontal Spacing is 4 ft (1.2 m) per Table 22

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


Protection for Automatic Storage 8-34
FM Global Property Loss Prevention Data Sheets Page 57

Table 23. Vertical In-Rack Sprinkler Locations and In-Rack Sprinkler Designs for the Protection of Open-Top, Combustible
Containers Stored in a Shuttle System
Maximum Minimum
Vertical IRAS Hydraulically
Recommended Distance Design Balance IRAS
IRAS Open-Top Maximum IRAS Between Flow, Minimum System with
Arrangement Container Commodity System IRAS, ft gpm IRAS No. of IRAS Ceiling
per Table 22 Composition Classification Type (m) (L/min)* K-factor in Design System?
Figure 14 Cardboard or Any Wet 10 (3.0) 100 11.2 4 on top No
Unexpanded (380) (160) IRAS level
Plastic Dry 10 (3.0) 100 11.2 8 if one IRAS Yes
(380) (160) level or 14
Upright (7 on top 2
levels)
Figure 15 Cardboard Class 3 Wet 10 (3.0) 60 (230) 11.2 4 on top No
(160) IRAS level
15 (4.6) 100 14.0 6 on top No
(380) (200) IRAS level
Pendent
Dry 10 (3.0) 60 (230) 11.2 8 if one IRAS Yes
(160) level or 14
(7 on top 2
levels)
15 (4.6) 100 14.0 8 if one IRAS Yes
(380) (200) level or 14
Upright (7 on top 2
levels)
Uncartoned Wet 10 (3.0) 100 11.2 4 on top No
Expanded (380) (160) IRAS level
Plastic 15 (4.6) 140 22.4 6 on top No
(530) (320) IRAS level
Pendent
Dry 10 (3.0) 100 11.2 8 if one IRAS Yes
(380) (160) level or 14
Upright (7 on top 2
levels)
Figure 16 Unexpanded Any Wet 10 (3.0) 100 11.2 4 on top No
Plastic (380) (160) IRAS level
15 (4.6) 140 22.4 6 on top No
(530) (320) IRAS level
Pendent
Dry 10 (3.0) 100 11.2 8 if one IRAS Yes
(380) (160) level or 14
Upright (7 on top 2
levels)
* The indicated in-rack sprinkler design flow is based on a minimum 9 in. (225 mm) vertical distance between storage tier levels. If the vertical
distance between vertical tier levels is less than 9 in. (225 mm), add 20 gpm (75 L/min) to the indicated design flow.

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


8-34 Protection for Automatic Storage
Page 58 FM Global Property Loss Prevention Data Sheets

Table 23. Vertical In-Rack Sprinkler Locations and In-Rack Sprinkler Designs for the Protection of Open-Top, Combustible
Containers Stored in a Shuttle System (continued)
Maximum Minimum
Vertical IRAS Hydraulically
Recommended Distance Design Balance IRAS
IRAS Open-Top Maximum IRAS Between Flow, Minimum System with
Arrangement Container Commodity System IRAS, ft gpm IRAS No. of IRAS Ceiling
per Table 22 Composition Classification Type (m) (L/min)* K-factor in Design System?
Figures 17 or Cardboard or Any Wet 10 (3.0) 100 11.2 6 on top No
20 Unexpanded (380) (160) IRAS level
Plastic Dry 10 (3.0) 100 11.2 8 if one IRAS Yes
(380) (160) level or 14
Upright (7 on top 2
levels)
Figures 18, Cardboard Class 3 Wet 10 (3.0) 60 (230) 11.2 6 on top No
21, or 24 (160) IRAS level
15 (4.6) 100 14.0 6 on top No
(380) (200) IRAS level
Pendent
Dry 10 (3.0) 60 (230) 11.2 8 if one IRAS Yes
(160) level or 14
Upright (7 on top 2
levels)
15 (4.6) 100 14.0 8 if one IRAS Yes
(380) (200) level or 14
Upright (7 on top 2
levels)
Uncartoned Wet 10 (3.0) 100 11.2 6 on top No
Expanded (380) (160) IRAS level
Plastic 15 (4.6) 140 22.4 6 on top No
(530) (320) IRAS level
Pendent
Dry 10 (3.0) 100 11.2 8 if one IRAS Yes
(380) (160) level or 14 (7
Upright on top 2
levels)
Figures 19, Unexpanded Any Wet 10 (3.0) 100 11.2 6 on top No
22, or 25 Plastic (380) (160) IRAS level
15 (4.6) 140 22.4 6 on top No
(530) (320) IRAS level
Pendent
Dry 10 (3.0) 100 11.2 8 if one IRAS Yes
(380) (160) level or 14
Upright (7 on top 2
levels)
Figure 23 Cardboard or Any Wet 10 (3.0) 100 11.2 8 on top No
Unexpanded (380) (160) IRAS level
Plastic Dry 10 (3.0) 100 11.2 8 if one IRAS Yes
(380) (160) level or 14
Upright (7 on top 2
levels)
* The indicated in-rack sprinkler design flow is based on a minimum 9 in. (225 mm) vertical distance between storage tier levels. If the vertical
distance between vertical tier levels is less than 9 in. (225 mm), add 20 gpm (75 L/min) to the indicated design flow.

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


Protection for Automatic Storage 8-34
FM Global Property Loss Prevention Data Sheets Page 59

2.2.4.2.3 Ceiling Sprinkler System Designs in Combination with In-Rack Sprinklers for the Protection
of Open-Top, Combustible Containers in a Shuttle ASRS
2.2.4.2.3.1 Use Table 24 to determine the wet ceiling-level sprinkler system designs in combination with
in-rack sprinklers. If a protection option is not available from the applicable protection table, either:
1. Install a flat, continuous, noncombustible false ceiling, capable of withstanding an uplift pressure of 3
lb/ft² (14.4 kg/m²), over the ASRS storage area and for a minimum of 15 ft (4.6 m) beyond the ASRS
area in all directions with sprinklers installed underneath the false ceiling in accordance with Table 24,
or
2. Install in-rack sprinklers over the top of storage and design the ceiling sprinkler system per Table 24.
2.2.4.2.3.2 Use Table 25 to determine the dry ceiling-level sprinkler system designs in combination with in-rack
sprinklers. If a protection option is not available from the applicable protection table, either:
1. Install a flat, continuous, noncombustible false ceiling, capable of withstanding an uplift pressure of 3
lb/ft² (14.4 kg/m²), over the ASRS storage area and for a minimum of 15 ft (4.6 m) beyond the ASRS
area in all directions with sprinklers installed underneath the false ceiling in accordance with Table 25,
or
2. Install in-rack sprinklers over the top of storage and design the ceiling sprinkler system per Table 25.
2.2.4.2.3.3 The ceiling-level sprinkler system designs in Tables 24 and 25 are determined using the vertical
distance between the top in-rack sprinkler level and the maximum ceiling height above the ASRS protected
area.
2.2.4.2.3.4 See Section 2.2.1.6 to determine the ceiling sprinkler’s hose demand design and water supply
duration.
2.2.4.2.3.5 See Section 2.1.4.5.4 to determine the number of sprinklers per branch line for ceiling-level
sprinkler calculations.

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


Table 24. Wet System Ceiling-Level Sprinkler Protection Guidelines, in Combination with In-Rack Sprinklers, for the Protection of Open-Top, Combustible Containers in a Shuttle ASRS;

Page 60
8-34
No. of AS @ psi (bar)
Max. Max.
Storage Vertical Ceiling-Level Sprinkler Protection Options for Shuttle ASRS Arrangements with Open-Top, Combustible Containers; No. of AS @ psi (bar)
Height Distance Wet System, Pendent Storage Sprinklers, 160°F (70°C) Wet System, Upright Storage Sprinklers, 160°F (70°C)
Above Between
Quick-Response Standard-Response Quick-Response Standard-Response
Top Top IRAS
IRAS Level and 11.2 14.0 16.8 22.4 25.2 25.2EC 28.0 33.6 11.2 14.0 19.6 25.2 11.2 14.0 16.8 25.2EC 11.2 16.8 25.2
Level, Ceiling, ft (160) (200) (240) (320) (360) (360EC) (400) (480) (160) (200) (280) (360) (160) (200) (240) (360EC) (160) (240) (360)
ft (m) (m)
0 (0) Any 20 @ 9@ 9@ 9@ 9@ 6 @ 20 9@ 9@ 20 @ 9@ 9@ 9@7 20 @ 9@ 9@ 6 @ 20 20 @ 9@ 9@7
©2017-2023 Factory Mutual Insurance Company. All rights reserved.

7 20 20 20 20 (1.4) 40 55 7 20 16 (0.5) 7 20 20 (1.4) 7 20 (0.5)


(0.5) (1.4) (1.4) (1.4) (1.4) (2.8) (3.8) (0.5) (1.4) (1.1) (0.5) (1.4) (1.4) (0.5) (1.4)
5 10 (3.0) 20 @ 12 @ 12 @ 9@ 9@ 10 @ 9@ 9@ 20 @ 20 @ 20 @ 20 @ 20 @ 20 @ 20 @ 10 @ 20 @ 20 @ 20 @
(1.5) 30 25 18 20 20 22 (1.0) 40 55 30 18 16 7 30 18 13 22 (1.0) 30 13 7
(2.1) (1.7) (1.2) (1.4) (1.4) (2.8) (3.8) (2.1) (1.2) (1.1) (0.5) (2.1) (1.2) (0.9) (2.1) (0.9) (0.5)
15 (4.6) 25 @ 10 @ 10 @ 9@ 9@ 12 @ 9@ 9@ 25 @ 25 @ 25 @ 25 @ 25 @ 25 @ 25 @ 12 @ 25 @ 25 @ 25 @
50 35 25 20 20 38 (2.6) 40 55 50 32 16 10 50 32 22 38 (2.6) 50 22 10

Protection for Automatic Storage


(3.5) (2.4) (1.7) (1.4) (1.4) (2.8) (3.8) (3.5) (2.2) (1.1) (0.7) (3.5) (2.2) (1.5) (3.5) (1.5) (0.7)
20 (6.1) 12 @ 12 @ 12 @ 12 @ 9@ 9@
50 35 20 20 40 55
(3.5) (2.4) (1.4) (1.4) (2.8) (3.8)

FM Global Property Loss Prevention Data Sheets


10 15 (4.6) 25 @ 10 @ 10 @ 9@ 9@ 12 @ 9@ 9@ 25 @ 25 @ 25 @ 25 @ 25 @ 25 @ 25 @ 12 @ 25 @ 25 @ 25 @
(3.0) 50 35 25 20 20 38 (2.6) 40 55 50 32 16 10 50 32 22 38 (2.6) 50 22 10
(3.5) (2.4) (1.7) (1.4) (1.4) (2.8) (3.8) (3.5) (2.2) (1.1) (0.7) (3.5) (2.2) (1.5) (3.5) (1.5) (0.7)
20 (6.1) 12 @ 12 @ 12 @ 12 @ 9@ 9@
50 35 20 20 40 55
(3.5) (2.4) (1.4) (1.4) (2.8) (3.8)
Note: The ceiling-level protection options highlighted in green represent those for which the hose stream demand is 250 gpm (950 L/min) and the sprinkler system duration is 1 hour
Protection for Automatic Storage 8-34
FM Global Property Loss Prevention Data Sheets Page 61

Table 25. Dry System Ceiling-Level Sprinkler Protection Guidelines, in Combination with In-Rack Sprinklers, for the
Protection of Open-Top, Combustible Containers in a Shuttle ASRS; No. of AS @ psi (bar)
Ceiling-Level Sprinkler Protection Options for Shuttle ASRS Arrangements
Max. Vertical with Open-Top, Combustible Containers; No. of AS @ psi (bar)
Max. Storage Distance Between Dry System, Upright Storage Sprinklers, 280°F (140°C)
Height Above Top Top IRAS Level Standard-Response
IRAS Level, ft (m) and Ceiling, ft (m) 11.2 (160) 16.8 (240) 25.2 (360) 33.6 (480)
0 (0) Any 25 @ 7 (0.5) 25 @ 7 (0.5) 25 @ 7 (0.5) 25 @ 50 (3.5)
5 (1.5) 10 (3.0) 25 @ 30 (2.1) 25 @ 13 (0.9) 25 @ 7 (0.5) 25 @ 50 (3.5)
15 (4.6) 30 @ 50 (3.5) 30 @ 22 (1.5) 30 @ 10 (0.7) 30 @ 50 (3.5)
10 (3.0) 15 (4.6) 30 @ 50 (3.5) 30 @ 22 (1.5) 30 @ 10 (0.7) 30 @ 50 (3.5)

2.2.5 Protection of Horizontal-Loading, Mini-Load ASRS Storage Arrangements Where Closed-Top,


Noncombustible, Solid-Walled Containers, or FM Approved, Non-Propagating, Open-Top Containers
are Being Used

2.2.5.1 Protection of Horizontal-Loading, Mini-Load ASRS Storage Arrangements Where Closed-Top,


Noncombustible, Solid-Walled Containers are Being Used
2.2.5.1.1 Automatic sprinkler protection can be designed for the surrounding occupancy hazard when
closed-top, noncombustible, solid-walled containers are used throughout the entire horizontal-loading ASRS
storage array.
2.2.5.1.2 Where closed-top, noncombustible, solid-walled containers are to be used, but not throughout the
entire storage array, provide protection in accordance with the worst-case container or tray being used.

2.2.5.2 Protection of Horizontal-Loading, Mini-Load ASRS Storage Arrangements Where FM Approved,


Non-Propagating, Open-Top Containers are Being Used (Reserved)
Protection guidelines for FM Approved, non-propagating, open-top containers will be provided upon the
release of an FM Approval Standard specific to these types of containers.

2.2.6 Protection of Horizontal-Loading Mini-Load ASRS Storage Arrangements Using (1) Closed-Top
Combustible Containers, or (2) Products that Do Not Collect Water that are Stored on Trays
The protection guidelines in Section 2.2.6 apply only to storage that is not considered open-top, whether
stored directly on the support rails of the ASRS or on trays. Such products will be subsequently referred to
in Section 2.2.6 as “storage on trays”. If the product or containers allow for water collection, use the protection
guidelines provided in Section 2.2.7.
Section 2.2.6 is organized as follows:
• Section 2.2.6.1 determines if a ceiling-only protection option is available and, if it is, the recommended
ceiling-only protection designs.
• Section 2.2.6.2 determines the recommended designs when both ceiling and in-rack sprinklers are installed.
This section is further broken down into the following subsections:
- Section 2.2.6.2.1 provides acceptable horizontal in-rack sprinkler arrangements.
- Section 2.2.6.2.2 provides both the acceptable vertical in-rack sprinkler arrangements as well as the
corresponding in-rack sprinkler system design.
- Section 2.2.6.2.3 provides the acceptable ceiling sprinkler system design with the chosen in-rack sprinkler
system arrangement.

2.2.6.1 Ceiling-Only Sprinkler System Design Criteria for Closed-Top Combustible Containers, or
Storage on Trays
2.2.6.1.1 A ceiling-only sprinkler system protection scheme is possible when:
1. Adequately aligned transverse flue spaces are provided as outlined in Section 2.2.1.4, and
2. For Class 1 through 4, cartoned plastics, and uncartoned unexpanded plastics, minimum 3-1/2 ft
(1.1 m) wide aisles are provided for ceiling heights not exceeding 30 ft (9.1 m), and

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


8-34 Protection for Automatic Storage
Page 62 FM Global Property Loss Prevention Data Sheets

3. Minimum 4 ft (1.2 m) wide aisles are provided when:


a. Uncartoned expanded plastics are stored in the racks, or
b. The ceiling height exceeds 30 ft (9.1 m) (unless indicated otherwise by a footnote at the bottom of
the protection table), and
4. Uncartoned plastic products are not stored directly on the mini-load rack’s horizontal supporting rails
(i.e., the products are being stored on trays), and
5. For the given material handling scenario outlined in this section, a ceiling-only protection option is
provided in the applicable protection table (Tables 27 through 30) for the specific sprinkler being
installed at ceiling level, and
6. The water supply can provide the flow and pressure requirements for the protection option chosen
from the applicable protection table.
If the conditions outlined in (1) through (6) cannot be met, see Section 2.2.6.2 regarding the guidelines for
installing in-rack sprinklers in combination with ceiling-level sprinklers.
2.2.6.1.2 When a ceiling-only protection scheme is acceptable per items (1) through (6) in Section 2.2.6.1.1,
use Table 26 to determine which protection table to use for obtaining the recommended ceiling sprinkler
design, depending on the commodity hazard, the type of material handling being used (i.e., directly on the
mini-load rack’s horizontal supporting rails or on trays), and the type of ceiling sprinkler system (i.e., wet or dry)
being installed.
2.2.6.1.3 See Section 2.2.1.6 to determine the ceiling sprinkler’s hose demand design and water supply
duration.
2.2.6.1.4 See Section 2.1.4.5.4 to determine the number of sprinklers per branch line for ceiling-level sprinkler
calculations.

Table 26. Determining Which Ceiling Sprinkler Protection Table to Use for the Protection of Closed-Top Combustible
Containers, or Storage on Trays in a Mini-Load ASRS
Commodity Classification
(No Open-Top Containers Ceiling Sprinkler System
Material Handling Method Permitted) Type Protection Table to Use
Directly on Supporting Rails Class 1 through 4, Wet 27
or On Trays Cartoned Plastics, and Dry 28
Uncartoned Unexpanded
Plastics
Uncartoned Expanded Wet 29
Plastics Dry 30
Note 1. In Tables 27 and 29, the ceiling-level protection options highlighted in green represent those for which the hose stream demand
is 250 gpm (950 L/min) and the sprinkler system duration is 1 hour.

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


Table 27. Ceiling-Level Protection Guidelines on a Wet System for Class 1 - 4, Cartoned Plastics, and Uncartoned Unexpanded Plastic Commodities Stored in a Mini-Load ASRS;

FM Global Property Loss Prevention Data Sheets


Protection for Automatic Storage
No. of AS @ psi (bar)
Wet System, 160°F (70°C) Nominally Rated, Upright
Max. Wet System, 160°F (70°C) Nominally Rated, Pendent Sprinklers Sprinklers
Ceiling Quick-Response Standard-Response Quick-Response Standard-Response
Height, K11.2 K14.0 K16.8 K22.4 K25.2 K25.2EC K28.0 K33.6 K11.2 K14.0 K19.6 K25.2 K11.2 K14.0 K16.8 K25.2EC K11.2 K16.8 K25.2
ft (m) (K160) (K200) (K240) (K320) (K360) (K360EC) (K400) (K480) (K160) (K200) (K280) (K360) (K160) (K200) (K240) (K360EC) (K160) (K240) (K360)
10 15 @ 15 @ 15 @ 9@ 9@ 6 @ 20 9@ 9@ 15 @ 15 @ 12 @ 15 @ 15 @ 15 @ 15 @ 6 @ 20 15 @ 15 @ 15 @
(3.0) 10 7 (0.5) 7 (0.5) 20 20 (1.4) 40 55 10 7 (0.5) 16 7 (0.5) 10 7 (0.5) 7 (0.5) (1.4) 10 7 (0.5) 7 (0.5)
(0.7) (1.4) (1.4) (2.8) (3.8) (0.7) (1.1) (0.7) (0.7)
15 15 @ 12 @ 12 @ 9@ 9@ 6 @ 60 9@ 9@ 15 @ 12 @ 12 @ 12 @ 15 @ 15 @ 15 @ 8 @ 35 15 @ 15 @ 15 @
©2017-2023 Factory Mutual Insurance Company. All rights reserved.

(4.6) 50 32 22 25 20 (4.1) 40 55 50 50 25 15 50 32 22 (2.4) 50 22 10


(3.5) (2.2) (1.5) (1.7) (1.4) (2.8) (3.8) (3.5) (3.5) (1.7) (1.0) (3.5) (2.2) (1.5) (3.5) (1.5) (0.7)
20 9@ 9@ 9@ 9@ 6 @ 60 9@ 9@ 12 @ 12 @ 12 @
(6.1) 50 35 25 20 (4.1) 40 55 50 25 15
(3.5) (2.4) (1.7) (1.4) (2.8) (3.8) (3.5) (1.7) (1.0)
25 10 @ 10 @ 10 @ 10 @ 10 @ 10 @
(7.6) 50 35 25 20 40 55
(3.5) (2.4) (1.7) (1.4) (2.8) (3.8)
30 15 @ 15 @ 10 @ 10 @ 10 @ 10 @
(9.1) 50 35 50 40 40 55
(3.5) (2.4) (3.5) (2.8) (2.8) (3.8)
40 12 @ 12 @ 12 @ 12 @
(12.2) 75 60 49 55
(5.2) (4.1) (3.4) (3.8)

Page 63
8-34
8-34 Protection for Automatic Storage
Page 64 FM Global Property Loss Prevention Data Sheets

Table 28. Ceiling-Level Protection Guidelines on a Dry System for Class 1 - 4, Cartoned Plastics, and Uncartoned
Unexpanded Plastic Commodities Stored in a Mini-Load ASRS; No. of AS @ psi (bar)
Dry System, 280°F (140°C) Nominally Rated, Upright Sprinklers
Max. Ceiling Height, ft Standard-Response
(m) K11.2 (K160) K16.8 (K240) K25.2 (K360) K33.6 (K480)
10 (3.0) 20 @ 10 (0.7) 20 @ 7 (0.5) 20 @ 7 (0.5) 20 @ 50 (3.5)
15 (4.6) 20 @ 50 (3.5) 20 @ 22 (1.5) 20 @ 10 (0.7) 20 @ 50 (3.5)

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


Table 29. Ceiling-Level Protection Guidelines on a Wet System for Uncartoned Expanded Plastic Commodities Stored in a Mini-Load Type ASRS; No. of AS @ psi (bar)

FM Global Property Loss Prevention Data Sheets


Protection for Automatic Storage
Wet System, 160°F (70°C) Nominally Rated, Upright
Max. Wet System, 160°F (70°C) Nominally Rated, Pendent Sprinklers Sprinklers
Ceiling Quick-Response Standard-Response Quick-Response Standard-Response
Height, K11.2 K14.0 K16.8 K22.4 K25.2 K25.2EC K28.0 K33.6 K11.2 K14.0 K19.6 K25.2 K11.2 K14.0 K16.8 K25.2EC K11.2 K16.8 K25.2
ft (m) (K160) (K200) (K240) (K320) (K360) (K360EC) (K400) (K480) (K160) (K200) (K280) (K360) (K160) (K200) (K240) (K360EC) (K160) (K240) (K360)
10 15 @ 15 @ 15 @ 9@ 9@ 6 @ 20 9@ 9@ 15 @ 15 @ 12 @ 15 @ 15 @ 15 @ 15 @ 6 @ 20 15 @ 15 @ 15 @
(3.0) 10 7 (0.5) 7 (0.5) 20 20 (1.4) 40 55 10 7 (0.5) 16 7 (0.5) 10 7 (0.5) 7 (0.5) (1.4) 10 7 (0.5) 7 (0.5)
(0.7) (1.4) (1.4) (2.8) (3.8) (0.7) (1.1) (0.7) (0.7)
15 15 @ 12 @ 12 @ 9@ 9@ 8 @ 35 9@ 9@ 15 @ 15 @ 15 @ 15 @ 15 @ 15 @ 15 @ 8 @ 35 15 @ 15 @ 15 @
(4.6) 50 32 22 25 20 (2.4) 40 55 50 32 16 10 50 32 22 (2.4) 50 22 10
©2017-2023 Factory Mutual Insurance Company. All rights reserved.

(3.5) (2.2) (1.5) (1.7) (1.4) (2.8) (3.8) (3.5) (2.2) (1.1) (0.7) (3.5) (2.2) (1.5) (3.5) (1.5) (0.7)
25 12 @ 12 @ 9@ 9@ 9@ 9@
(7.6) 75 52 32 25 40 55
(5.2) (3.6) (2.2) (1.7) (2.8) (3.8)
30 12 @ 12 @ 12 @ 12 @ 12 @ 12 @
(9.1) 100 70 50 40 40 55
(6.9) (4.8) (3.5) (2.8) (2.8) (3.8)
40 20 @ 20 @ 20 @
(12.2) 75 61 55
(5.2) (4.2) (3.8)

Page 65
8-34
8-34 Protection for Automatic Storage
Page 66 FM Global Property Loss Prevention Data Sheets

Table 30. Ceiling-Level Protection Guidelines on a Dry System for Uncartoned Expanded Plastic Commodities Stored in
a Mini-Load ASRS; No. of AS @ psi (bar)
Dry System, 280°F (140°C) Nominally Rated, Upright Sprinklers
Max. Ceiling Height, ft Standard-Response
(m) K11.2 (K160) K16.8 (K240) K25.2 (K360) K33.6 (K480)
10 (3.0) 25 @ 10 (0.7) 25 @ 7 (0.5) 25 @ 7 (0.5) 25 @ 50 (3.5)
15 (4.6) 25 @ 50 (3.5) 25 @ 22 (1.5) 25 @ 10 (0.7) 25 @ 50 (3.5)

2.2.6.2 Ceiling and In-Rack Sprinkler System Design Criteria for Closed-Top Containers, or Storage
on Trays in a Mini-Load ASRS
In-rack sprinklers are needed in combination with ceiling-level sprinklers when the guidelines from Section
2.2.6.1.1 are not met. Determine the recommended in-rack sprinkler horizontal arrangement in Section
2.2.6.2.1, the in-rack sprinkler vertical location and system design in Section 2.2.6.2.2, and the available
ceiling-level sprinkler designs in Section 2.2.6.2.3.

2.2.6.2.1 Horizontal Arrangement of In-Rack Sprinklers for Closed-Top Containers, or Storage on Trays
in a Mini-Lad ASRS
Use Table 31 to determine the recommended horizontal in-rack sprinkler arrangements for the storage rack
to be protected.

Table 31. Recommended Horizontal In-Rack Sprinkler (i.e., IRAS) Arrangements for Closed-Top Combustible Containers,
or Storage on Trays in a Mini-Load ASRS
Adequate
Transverse Flue Applicable
Overall Spaces Ceiling Aisle Horizontal IRAS
Rack Row Maximum Rack Provided per IRAS System Commodity Height, Width, Arrangement
Depth, ft (m) Depth, ft (m) Section 2.2.1.4? Type Hazards ft (m) ft (m) Figures
Up to 3 (0.9) 3 (0.9) No Wet or Dry Any Any Any 26
Yes Wet or Dry Any Any Any 26 or 27
Up to 6 (1.8) 6 (1.8) No Wet or Dry Any Any Any 28
Yes Wet or Dry Any Any Any 28 or 29
14 (4.3) No Wet or Dry Any Any Any 30
Yes Wet or Dry Any Any Any 30 or 31
Over 6 (1.8) Over 6 (1.8) No Wet or Dry Any Any Any 32 with Vertical
Barriers
Yes Wet or Dry Any Any Any 33

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


Protection for Automatic Storage 8-34
FM Global Property Loss Prevention Data Sheets Page 67

Tray or Closed-Top
Max. 2-1/2 ft
Container
(0.75 m)

Max
18 in. Max
1 2 3 4 5 6 7 8 3 ft
(450 mm)
(0.9 m)

The in-rack sprinkler numbers represent which IRAS


sprinklers to include in the hydraulic design
depending on the number of in-rack sprinklers
indicated for the in-rack sprinkler design Note: The in-rack sprinklers do not need
to align with the transverse flue spaces
located between the rack uprights

Fig. 26. Horizontal IRAS Arrangement for Closed-Top Combustible Containers, or Storage on Trays within a Mini-Load
ASRS Where Rack Row Depths Do Not Exceed 3 ft (0.9 m) and the Maximum Horizontal Spacing is 2-1/2 ft (0.75 m) per
Table 31

Tray or Closed-Top
Max. 5 ft
Container
(1.5 m)

Max
18 in. Max
1 2 3 4 5 6 7 8 3 ft
(450 mm)
(0.9 m)

The in-rack sprinkler numbers represent which IRAS


sprinklers to include in the hydraulic design
depending on the number of in-rack sprinklers
indicated for the in-rack sprinkler design

Fig. 27. Horizontal IRAS Arrangement for Closed-Top Combustible Containers, or Storage on Trays within a Mini-Load
ASRS Where Rack Row Depths Do Not Exceed 3 ft (0.9 m) and the Maximum Horizontal Spacing is 5 ft (1.5 m) per Table
31

Note: The in-rack sprinklers do not need Tray or Closed-Top


to align with the transverse flue spaces Max. 2-1/2 ft Container
located between the rack uprights (0.75 m)

Max
18 in.
(450 mm) 1 3 5 7

Max
6 ft
(1.8 m)

2 4 6 8

The in-rack sprinkler numbers represent which IRAS


sprinklers to include in the hydraulic design
depending on the number of in-rack sprinklers
indicated for the in-rack sprinkler design

Fig. 28. Horizontal IRAS Arrangement for Closed-Top Combustible Containers, or Storage on Trays within a Mini-Load
ASRS Where Rack Row Depths Do Not Exceed 6 ft (1.8 m) and the Maximum Horizontal Spacing is 2-1/2 ft (0.75 m) per
Table 31

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


8-34 Protection for Automatic Storage
Page 68 FM Global Property Loss Prevention Data Sheets

Tray or Closed-Top
Max. 5 ft Container
(0.75 m)

Max
18 in.
(450 mm) 1 3 5 7

Max
6 ft
(1.8 m)

2 4 6 8

The in-rack sprinkler numbers represent which IRAS


sprinklers to include in the hydraulic design
depending on the number of in-rack sprinklers
indicated for the in-rack sprinkler design

Fig. 29. Horizontal IRAS Arrangement for Closed-Top Combustible Containers, or Storage on Trays within a Mini-Load
ASRS Where Rack Row Depths Do Not Exceed 6 ft (1.8 m) and the Maximum Horizontal Spacing is 5 ft (1.5 m) per Table
31

Note: The in-rack sprinklers do not need


Tray or Closed-Top
to align with the transverse flue spaces
Container Max. 2-1/2 ft
located between the rack uprights
(0.75 m)

Max
18 in.
(450 mm) 1 3 5 7

Max
5 ft
(1.5 m)

Max
2 ft 2 4 6
2 2
8
(0.6 m)

The in-rack sprinkler numbers represent which


sprinklers to include in the hydraulic design IRAS
depending on the number of in-rack sprinklers
indicated for the in-rack sprinkler design

Fig. 30. Horizontal IRAS Arrangement for Closed-Top Combustible Containers, or Storage on Trays within a Mini-Load
ASRS Where the Overall Rack Depths Do Not Exceed 14 ft (4.3 m) and the Maximum Horizontal Spacing is 2-1/2 ft
(0.75 m) per Table 31

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


Protection for Automatic Storage 8-34
FM Global Property Loss Prevention Data Sheets Page 69

Tray or Closed-Top
Container Max. 5 ft
(1.5 m)

Max
18 in.
(450 mm) 1 3 5 7

Max
5 ft
(1.5 m)

Max
2 ft 2 4 6
2 2
8
(0.6 m)

The in-rack sprinkler numbers represent which


sprinklers to include in the hydraulic design IRAS
depending on the number of in-rack sprinklers
indicated for the in-rack sprinkler design

Fig. 31. Horizontal IRAS Arrangement for Closed-Top Combustible Containers, or Storage on Trays within a Mini-Load
ASRS Where the Overall Rack Depths Do Not Exceed 14 ft (4.3 m) and the Maximum Horizontal Spacing is 5 ft (1.5 m)
per Table 31

Tray or Closed-Top Max


Container 2-1/2 ft
(0.75 m) IRAS

Max
18 in.
(450 mm) 2
1 3
2 5 7

Over
2 2
4 6 8 6 ft
(1.8 m)

Max. 5 ft
(1.5 m)

The in-rack sprinkler numbers represent which Note: The in-rack sprinklers do not need
sprinklers to include in the hydraulic design to align with the transverse flue spaces
depending on the number of in-rack sprinklers located between the rack uprights
indicated for the in-rack sprinkler design

Fig. 32. Horizontal IRAS Arrangement for Closed-Top Combustible Containers, or Storage on Trays within a Mini-Load
ASRS Where Rack Row Depths Exceed 6 ft (1.8 m) in Depth and the Maximum Horizontal Spacing is 2-1/2 ft (0.75 m)
per Table 31

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


8-34 Protection for Automatic Storage
Page 70 FM Global Property Loss Prevention Data Sheets

Tray or Closed-Top Max


Container 5 ft
(1.5 m) IRAS

Max
18 in.
(450 mm) 2
1 3
2 5 7

Over
2 2
4 6 8 6 ft
(1.8 m)

Max. 5 ft
(1.5 m)

The in-rack sprinkler numbers represent which


sprinklers to include in the hydraulic design
depending on the number of in-rack sprinklers
indicated for the in-rack sprinkler design

Fig. 33 Horizontal IRAS Arrangement for Closed-Top Combustible Containers, or Storage on Trays within a Mini-Load
ASRS Where Rack Row Depths Exceed 6 ft (1.8 m) in Depth and the Maximum Horizontal Spacing is 5 ft (1.5 m) per Table
31

2.2.6.2.2 Vertical Location of In-Rack Sprinklers and In-Rack Sprinkler System Designs for the
Protection of Closed-Top Combustible Containers, or Storage on Trays in a Mini-Load ASRS
2.2.6.2.2.1 Storage Racks Not Requiring Vertical Barriers
1. When Section 2.2.1.4 indicates that vertical barriers are not required due to transverse flue spaces being
provided, use the following tables to determine the allowable in-rack sprinkler vertical locations as well
as the corresponding recommended in-rack sprinkler design:
A. Table 32: Wet, In-Rack sprinkler system protecting a mini-load type ASRS, or
B. Table 33: Dry, In-Rack sprinkler system protecting a mini-load type ASRS
2. The maximum storage height above the top in-rack sprinkler level is 10 ft (3.0 m).
3. While the in-rack sprinkler designs given in Tables 32 and 33 are based on flow, the corresponding design
pressure for the chosen in-rack sprinkler cannot be less than 7 psi (0.5 bar). When the design pressure
will be less than 7 psi (0.5 bar), use a minimum pressure of 7 psi (0.5 bar) for design purposes, regardless
of the in-rack sprinkler’s K-factor value.
2.2.6.2.2.2 Storage Racks Requiring Vertical Barriers
When Section 2.2.1.4 indicates that vertical barriers are required due to the lack of acceptable transverse
flue spaces, install the in-rack sprinklers vertically using the design guidelines indicated in Section 2.2.6.2.2.1.
However, include all of the in-rack sprinklers installed between the vertical barriers in the in-rack sprinkler
design.
For example, if a wet, in-rack sprinkler system is being used to protect cartoned unexpanded plastic
commodity being stored within a mini-load ASRS which is to be protected with in-rack sprinklers per Figure
28, and the number of in-rack sprinklers between the vertical barriers is 9, then the design for the in-rack
sprinkler system would be per Table 32 and would be designed for (1) 9 IRAS @ 60 gpm (230 L/min) as
opposed to 6 IRAS @ 60 gpm (230 L/min).

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


Protection for Automatic Storage 8-34
FM Global Property Loss Prevention Data Sheets Page 71

Table 32. Wet, In-Rack Sprinkler Designs for the Protection of Closed-Top, Combustible Containers Stored in a Mini-Load
Type ASRS
Hydraulically
Max. Balance
Recommended Vertical Min. IRAS IRAS
IRAS Maximum Material Distance Flow System with
Arrangement Commodity Handling Between Design, gpm Min. IRAS No. of IRAS Ceiling
per Table 31 Hazard Method IRAS, ft (m)* (L/min)** K-factor in Design System?
Figure 26 Cartoned Directly on 10 (3.0) 60 (230) 11.2 (160) 5 on top No
Unexpanded Rails or On IRAS level
Plastics Trays 15 (4.6) 100 (380) 14.0 (200) 6 on top No
IRAS level
Cartoned Directly on 10 (3.0) 60 (230) 11.2 (160) 5 on top No
Expanded Rails IRAS level
Plastics On Trays 10 (3.0) 60 (230) 11.2 (160) 5 on top No
IRAS level
15 (4.6) 100 (380) 14.0 (200) 6 on top No
IRAS level
Uncartoned On Trays 10 (3.0) 60 (230) 11.2 (160) 5 on top No
Expanded IRAS level
Plastics
Figure 27 Cartoned Directly on 10 (3.0) 60 (230) 11.2 (160) 4 on top No
Unexpanded Rails or On IRAS level
Plastics Trays 15 (4.6) 100 (380) 14.0 (200) 6 on top No
IRAS level
Cartoned Directly on 10 (3.0) 60 (230) 11.2 (160) 4 on top No
Expanded Rails IRAS level
Plastics On Trays 10 (3.0) 60 (230) 11.2 (160) 4 on top No
IRAS level
15 (4.6) 100 (380) 14.0 (200) 6 on top No
IRAS level
Uncartoned On Trays 10 (3.0) 60 (230) 11.2 (160) 4 on top No
Expanded IRAS level
Plastics
Figures 28, 30, Cartoned Directly on 10 (3.0) 60 (230) 11.2 (160) 6 on top No
or 32 Expanded Rails or On IRAS level
Plastics Trays
Uncartoned On Trays 10 (3.0) 60 (230) 11.2 (160) 6 on top No
Expanded IRAS level
Plastics
Figures 29, 31, Cartoned Directly on 10 (3.0) 60 (230) 11.2 (160) 6 on top No
or 33 Unexpanded Rails or On IRAS level
Plastics Trays 15 (4.6) 100 (380) 14.0 (200) 8 on top No
IRAS level
Cartoned Directly on 10 (3.0) 60 (230) 11.2 (160) 6 on top No
Expanded Rails IRAS level
Plastics On Trays 10 (3.0) 60 (230) 11.2 (160) 6 on top No
IRAS level
15 (4.6) 100 (380) 14.0 (200) 8 on top No
IRAS level
Uncartoned On Trays 10 (3.0) 60 (230) 11.2 (160) 6 on top No
Expanded IRAS level
Plastics
*The maximum storage height above the top in-rack sprinkler level is 10 ft (3.0 m).
**The indicated in-rack sprinkler design flow is based on a minimum 9 in. (225 mm) vertical distance between storage tier levels. If the vertical
distance between vertical tier levels is less than 9 in. (225 mm), add 20 gpm (75 L/min) to the indicated design flow.

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


8-34 Protection for Automatic Storage
Page 72 FM Global Property Loss Prevention Data Sheets

Table 33. Dry, In-Rack Sprinkler Designs for the Protection of Closed-Top, Combustible Containers Stored in a Mini-Load
Type ASRS
Max. Hydraulically
Vertical Min. IRAS Balance
Recommended Distance Flow IRAS
IRAS Maximum Material Between Design, System
Arrangement Commodity Handling IRAS, ft gpm Min. IRAS No. of IRAS in with Ceiling
per Table 31 Hazard Method (m)* (L/min)** K-factor Design System?
Figure 26 Cartoned Directly on 10 (3.0) 60 (230) 11.2 (160) 6 if one IRAS level or Yes
Unexpanded Rails or On Upright 10 (5 on top 2 levels)
Plastics Trays 15 (4.6) 100 (380) 14.0 (200) 8 if one IRAS level or Yes
Upright 14 (7 on top 2 levels)
Cartoned Directly on 10 (3.0) 60 (230) 11.2 (160) 6 if one IRAS level or Yes
Expanded Rails Upright 10 (5 on top 2 levels)
Plastics On Trays 10 (3.0) 60 (230) 11.2 (160) 6 if one IRAS level or Yes
Upright 10 (5 on top 2 levels)
15 (4.6) 100 (380) 14.0 (200) 8 if one IRAS level or Yes
Upright 14 (7 on top 2 levels)
Uncartoned On Trays 10 (3.0) 60 (230) 11.2 (160) 6 if one IRAS level or Yes
Expanded Upright 10 (5 on top 2 levels)
Plastics
Figure 27 Cartoned Directly on 10 (3.0) 60 (230) 11.2 (160) 4 if one IRAS level or Yes
Unexpanded Rails or On Upright 8 (4 on top 2 levels)
Plastics Trays 15 (4.6) 100 (380) 14.0 (200) 6 if one IRAS level or Yes
Upright 10 (5 on top 2 levels)
Cartoned Directly on 10 (3.0) 60 (230) 11.2 (160) 4 if one IRAS level or Yes
Expanded Rails Upright 8 (4 on top 2 levels)
Plastics On Trays 10 (3.0) 60 (230) 11.2 (160) 4 if one IRAS level or Yes
Upright 8 (4 on top 2 levels)
15 (4.6) 100 (380) 14.0 (200) 6 if one IRAS level or Yes
Upright 10 (5 on top 2 levels)
Uncartoned On Trays 10 (3.0) 60 (230) 11.2 (160) 6 if one IRAS level or Yes
Expanded Upright 10 (5 on top 2 levels)
Plastics
Figures 28, Cartoned Directly on 10 (3.0) 60 (230) 11.2 (160) 6 if one IRAS level or Yes
29, 30, 31, 32, Unexpanded Rails or On Upright 10 (5 on top 2 levels)
33, or 33 Plastics Trays 15 (4.6) 100 (380) 14.0 (200) 8 if one IRAS level or Yes
Upright 14 (7 on top 2 levels)
Cartoned Directly on 10 (3.0) 60 (230) 11.2 (160) 6 if one IRAS level or Yes
Expanded Rails Upright 10 (5 on top 2 levels)
Plastics On Trays 10 (3.0) 60 (230) 11.2 (160) 6 if one IRAS level or Yes
Upright 10 (5 on top 2 levels)
15 (4.6) 100 (380) 14.0 (200) 8 if one IRAS level or Yes
Upright 14 (7 on top 2 levels)
Uncartoned On Trays 10 (3.0) 60 (230) 11.2 (160) 8 if one IRAS level or Yes
Expanded Upright 14 (7 on top 2 levels)
Plastics
*The maximum storage height above the top in-rack sprinkler level is 10 ft (3.0 m).
**The indicated in-rack sprinkler design flow is based on a minimum 9 in. (225 mm) vertical distance between storage tier levels. If the vertical
distance between vertical tier levels is less than 9 in. (225 mm), add 20 gpm (75 L/min) to the indicated design flow.

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


Protection for Automatic Storage 8-34
FM Global Property Loss Prevention Data Sheets Page 73

2.2.6.2.3 Ceiling Sprinkler System Designs in Combination with In-Rack Sprinklers for the Protection
of Closed-Top Combustible Containers, or Storage on Trays in a Mini-Load ASRS
2.2.6.2.3.1 Use Table 34 to determine how to obtain the ceiling sprinkler system design for a wet ceiling
sprinkler system protecting a mini-load type ASRS. If a protection option is not available from the applicable
protection table, either:
1. Install a flat, continuous, noncombustible false ceiling, capable of withstanding an uplift pressure of 3
lb/ft² (14.4 kg/m²), over the ASRS storage area and for a minimum of 15 ft (4.6 m) beyond the ASRS
area in all directions with sprinklers installed underneath the false ceiling in accordance with Table 34,
or
2. Install in-rack sprinklers over the top of storage and design the ceiling sprinkler system per Table 34.
2.2.6.2.3.2 Use Table 35 to determine how to obtain the ceiling sprinkler system design for a dry ceiling
sprinkler system protecting a mini-load type ASRS. If a protection option is not available from the applicable
protection table, either:
1. Install a flat, continuous, noncombustible false ceiling, capable of withstanding an uplift pressure of 3
lb/ft² (14.4 kg/m²), over the ASRS storage area and for a minimum of 15 ft (4.6 m) beyond the ASRS
area in all directions with sprinklers installed underneath the false ceiling in accordance with Table 35,
or
2. Install in-rack sprinklers over the top of storage and design the ceiling sprinkler system per Table 35.
2.2.6.2.3.3 See Section 2.2.1.6 to determine the ceiling sprinkler’s hose demand design and water supply
duration.
2.2.6.2.3.4 See Section 2.1.4.5.4 to determine the number of sprinklers per branch line for ceiling-level
sprinkler calculations.

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


8-34 Protection for Automatic Storage
Page 74 FM Global Property Loss Prevention Data Sheets

Table 34. Determining the Applicable Protection Table and Ceiling Height for Ceiling Sprinkler Designs when Wet
Ceiling-Level Sprinkler Systems are Supplemented with In-Rack Sprinklers to Protect Closed-Top Combustible Containers,
or Storage on Trays in a Mini-Load Type ASRS
Max. Storage Max. Clearance
Maximum Height Above Between Top of Applicable Applicable Ceiling Height
Commodity Material Handling Top IRAS Level, Storage and Protection Table to Use in Indicated
Hazard Method ft (m) Ceiling, ft (m) to Use Protection Table, ft (m)
Cartoned Directly on 0 (0) Any 27 10 (3.0)
Unexpanded Supporting Rails 5 (1.5) 5 (1.5) 27 10 (3.0)
Plastics or On Trays 10 (3.0) 27 15 (4.6)
20 (6.1) 27 20 (6.1)
> 20 (6.1) 27 Vertical distance between
top IRAS level and ceiling
10 (3.0) Any 27 Vertical distance between
top IRAS level and ceiling
Cartoned Directly on 0 (0) Any 29 10 (3.0)
Expanded Supporting Rails 5 (1.5) 5 (1.5) 29 10 (3.0)
Plastics 10 (3.0) 29 15 (4.6)
20 (6.1) 29 25 (7.6)
> 20 (6.1) 29 Vertical distance between
top IRAS level and ceiling
0 (3.0) Any 29 Vertical distance between
top IRAS level and ceiling
On Trays 0 (0) Any 27 10 (3.0)
5 (1.5) 5 (1.5) 27 10 (3.0)
10 (3.0) 27 15 (4.6)
20 (6.1) 27 20 (6.1)
> 20 (6.1) 27 Vertical distance between
top IRAS level and ceiling
10 (3.0) Any 27 Vertical distance between
top IRAS level and ceiling
Uncartoned Directly on 0 (0) Any 27 10 (3.0)
Unexpanded Supporting Rails
Plastics On Trays 0 (0) Any 27 10 (3.0)
5 (1.5) 5 (1.5) 27 10 (3.0)
10 (3.0) 27 15 (4.6)
20 (6.1) 27 20 (6.1)
> 20 (6.1) 27 Vertical distance between
top IRAS level and ceiling
10 (3.0) Any 27 Vertical distance between
top IRAS level and ceiling
Uncartoned Directly on 0 (0) Any 29 10 (3.0)
Expanded Supporting Rails
Plastics On Trays 0 (0) Any 29 10 (3.0)
5 (1.5) 5 (1.5) 29 10 (3.0)
10 (3.0) 29 15 (4.6)
20 (6.1) 29 25 (7.6)
> 20 (6.1) 29 Vertical distance between
top IRAS level and ceiling
10 (3.0) Any 29 Vertical distance between
top IRAS level and ceiling

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


Protection for Automatic Storage 8-34
FM Global Property Loss Prevention Data Sheets Page 75

Table 35. Determining the Applicable Protection Table and Ceiling Height for Ceiling Sprinkler Designs when Dry
Ceiling-Level Sprinkler Systems are Supplemented with In-Rack Sprinklers to Protect Closed-Top Combustible Containers,
or Storage on Trays in a Mini-Load Type ASRS
Applicable Ceiling
Max. Clearance Height to Use in
Maximum Max. Storage Between Top of Applicable Indicated
Commodity Material Handling Height Above Top Storage and Protection Table Protection Table,
Hazard Method IRAS Level, ft (m) Ceiling, ft (m) to Use ft (m)
Cartoned Directly on 0 (0) Any 28 10 (3.0)
Unexpanded Supporting Rails 5 (1.5) 5 (1.5) 28 10 (3.0)
Plastics or On Trays 10 (3.0) 28 15 (4.6)
10 (3.0) 5 (1.5) 28 15 (4.6)
Cartoned Directly on 0 (0) Any 30 10 (3.0)
Expanded Supporting Rails 5 (1.5) 5 (1.5) 30 10 (3.0)
Plastics 10 (3.0) 30 15 (4.6)
10 (3.0) 5 (1.5) 30 15 (4.6)
On Trays 0 (0) Any 28 10 (3.0)
5 (1.5) 5 (1.5) 28 10 (3.0)
10 (3.0) 28 15 (4.6)
10 (3.0) 5 (1.5) 28 15 (4.6)
Uncartoned Directly on 0 (0) Any 28 10 (3.0)
Unexpanded Supporting Rails
Plastics On Trays 0 (0) Any 28 10 (3.0)
5 (1.5) 5 (1.5) 28 10 (3.0)
10 (3.0) 28 15 (4.6)
10 (3.0) 5 (1.5) 28 15 (4.6)
Uncartoned Directly on 0 (0) Any 30 10 (3.0)
Expanded Supporting Rails
Plastics On Trays 0 (0) Any 30 10 (3.0)
5 (1.5) 5 (1.5) 30 10 (3.0)
10 (3.0) 30 15 (4.6)
10 (3.0) 5 (1.5) 30 15 (4.6)

2.2.7 Protection of Horizontal-Loading, Mini-Load ASRS Storage Arrangements Where Open-Top,


Combustible Containers are Being Used
Note that the protection of expanded plastic containers is outside the scope of this data sheet.
Section 2.2.7 is organized as follows:
• Section 2.2.7.1 determines if a ceiling-only protection option is available and, if it is, the recommended
ceiling-only protection designs.
• Section 2.2.7.2 determines the recommended designs when both ceiling and in-rack sprinklers are installed.
This section is further broken down into the following subsections:
- Section 2.2.7.2.1 provides acceptable horizontal in-rack sprinkler arrangements.
- Section 2.2.7.2.2 provides both the acceptable vertical in-rack sprinkler arrangements as well as the
corresponding in-rack sprinkler system design.
- Section 2.2.7.2.3 provides the acceptable ceiling sprinkler system design with the chosen in-rack sprinkler
system arrangement.

2.2.7.1 Ceiling-Only Sprinkler System Design Criteria for Horizontal-Loading, Mini-Load ASRS Storage
Arrangements Using Open-Top, Combustible Containers
2.2.7.1.1 A ceiling-only sprinkler system protection scheme is possible when:
1. Adequate vertically aligned transverse flue spaces are provided as outlined in Section 2.2.1.4, and
2. The storage height does not exceed 10 ft (3.0 m), and
3. A ceiling-only protection option is provided in the applicable protection table (Tables 37 and 38) for
the specific sprinkler being installed at ceiling level, and

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


8-34 Protection for Automatic Storage
Page 76 FM Global Property Loss Prevention Data Sheets

4. The water supply can provide the flow and pressure requirements for the protection option chosen
from the applicable protection table.
If the conditions outlined in (1) through (4) cannot be met, see Section 2.2.7.2 regarding the guidelines for
installing in-rack sprinklers in combination with ceiling-level sprinklers.
2.2.7.1.2 When a ceiling-only protection scheme is acceptable per items (1) through (4) in Section 2.2.7.1.1,
use Table 36 to determine which protection table to use for obtaining the recommended ceiling sprinkler
design, depending on the type of ceiling sprinkler system (i.e., wet or dry) being installed.

Table 36. Determining Which Ceiling Sprinkler Protection Table to Use for the Protection of Horizontal-Loading, Mini-Load
ASRS Storage Arrangements Where Open-Top, Combustible Containers are Being Used
Commodity Classification Ceiling Sprinkler System Type Protection Table to Use
Class 1 through 4, Cartoned Plastics, Wet 37
and Uncartoned Plastics Dry 38
Note: In Table 37, the ceiling-level protection options highlighted in green represent those for which the hose stream demand is 250 gpm
(950 L/min) and the sprinkler system duration is 1 hour.

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


Table 37. Ceiling-Level Protection Guidelines on a Wet System for Storage in Open-Top, Combustible Containers in a Mini-Load ASRS up to a Maximum of 10 ft (3.0 m); No. of AS

FM Global Property Loss Prevention Data Sheets


Protection for Automatic Storage
@ psi (bar)
Wet System, 160°F (70°C) Nominally Rated, Upright
Max. Wet System, 160°F (70°C) Nominally Rated, Pendent Sprinklers Sprinklers
Ceiling Quick-Response Standard-Response Quick-Response tandard-Response
Height, K11.2 K14.0 K16.8 K22.4 K25.2 K25.2EC K28.0 K33.6 K11.2 K14.0 K19.6 K25.2 K11.2 K14.0 K16.8 K25.2EC K11.2 K16.8 K25.2
ft (m) (K160) (K200) (K240) (K320) (K360) (K360EC) (K400) (K480) (K160) (K200) (K280) (K360) (K160) (K200) (K240) (K360EC) (K160) (K240) (K360)
10 25 @ 12 @ 12 @ 9@ 9 @ 12 @ 38 9 @ 9@ 25 @ 25 @ 25 @ 25 @ 25 @ 25 @ 25 @ 12 @ 38 25 @ 25 @ 25 @
(3.0) 50 25 18 20 20 (2.6) 40 55 50 32 16 10 50 32 18 (2.6) 50 18 10
(3.5) (1.7) (1.2) (1.4) (1.4) (2.8) (3.8) (3.5) (2.2) (1.1) (0.7) (3.5) (2.2) (1.2) (3.5) (1.2) (0.7)
15 12 @ 12 @ 12 @ 10 @ 9@ 9@
©2017-2023 Factory Mutual Insurance Company. All rights reserved.

(4.6) 50 35 20 20 40 55
(3.5) (2.4) (1.4) (1.4) (2.8) (3.8)
20 12 @ 12 @ 12 @ 12 @ 9@ 9@
(6.1) 75 52 29 23 40 55
(5.2) (3.6) (2.0) (1.6) (2.8) (3.8)

Page 77
8-34
8-34 Protection for Automatic Storage
Page 78 FM Global Property Loss Prevention Data Sheets

Table 38. Ceiling-Level Protection Guidelines on a Dry System for Storage in Open-Top, Combustible Containers in a
Mini-Load ASRS up to a Maximum of 5 ft (1.5 m); No. of AS @ psi (bar)
Dry System, 280°F (140°C) Nominally Rated, Upright Sprinklers
Max. Ceiling Height, ft Standard-Response
(m) K11.2 (K160) K16.8 (K240) K25.2 (K360) K33.6 (K480)
10 (3.0) 30 @ 50 (3.5) 30 @ 18 (1.2) 30 @ 10 (0.7) 30 @ 50 (3.5)

2.2.7.1.3 See Section 2.2.1.6 to determine the ceiling sprinkler’s hose demand design and water supply
duration.
2.2.7.1.4 See Section 2.1.4.5.4 to determine the number of sprinklers per branch line for ceiling-level sprinkler
calculations.

2.2.7.2 Ceiling and In-Rack Sprinkler System Design Criteria for Horizontal-Loading, Mini-Load ASRS
Storage Arrangements Using Open-Top, Combustible Containers
In-rack sprinklers are needed in combination with ceiling-level sprinklers when the guidelines from Section
2.2.7.1.1 are not met. Determine the recommended in-rack sprinkler horizontal arrangement in Section
2.2.7.2.1, the in-rack sprinkler vertical location and system design in Section 2.2.7.2.2, and the available
ceiling-level sprinkler designs in Section 2.2.7.2.3.

2.2.7.2.1 Horizontal Arrangement of In-Rack Sprinklers for the Protection of Open-Top, Combustible
Containers in a Mini-Load ASRS
Use Table 39 to determine the recommended horizontal in-rack sprinkler arrangement for the storage rack
to be protected.

Table 39. Recommended Horizontal In-Rack Sprinkler Arrangements for the Protection of Open-Top, Combustible
Containers in a Mini-Load ASRS
Adequate Transverse Applicable Horizontal
Rack Row Depth, ft Overall Maximum Flue Spaces Provided Open-Top Container IRAS Arrangement
(m) Rack Depth, ft (m) per Section 2.2.1.4? Composition Figures
Up to 3 (0.9) 3 (0.9) No Cardboard or 34
Unexpanded Plastic
Yes Cardboard 35
Unexpanded Plastic 36
Up to 6 (1.8) 6 (1.8) No Cardboard or 37
Unexpanded Plastic
Yes Cardboard 38
Unexpanded Plastic 39
14 (4.3) No Cardboard or 40
Unexpanded Plastic
Yes Cardboard 41
Unexpanded Plastic 42
Over 6 (1.8) Over 6 (1.6) No Cardboard or 43 with Vertical
Unexpanded Plastic Barriers
Yes Cardboard 44
Unexpanded Plastic 45

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


Protection for Automatic Storage 8-34
FM Global Property Loss Prevention Data Sheets Page 79

Max. 2-1/2 ft Open-Top


(0.75 m) Container

Max
18 in. Max
1 2 3 4 5 6 7 8 3 ft
(450 mm)
(0.9 m)

The in-rack sprinkler numbers represent which IRAS


sprinklers to include in the hydraulic design
depending on the number of in-rack sprinklers
indicated for the in-rack sprinkler design Note: The in-rack sprinklers do not need
to align with the transverse flue spaces
located between the rack uprights

Fig. 34. Horizontal IRAS Arrangement for Open-Top Combustible Containers within a Mini-Load ASRS Where Rack Row
Depths Do Not Exceed 3 ft (0.9 m) and the Maximum Horizontal Spacing is 2-1/2 ft (0.75 m) per Table 39

Open-Top
Max. 2 ft
Container
(0.6 m)

Max
18 in. Max
1 2 3 4 5 6 7 8 3 ft
(450 mm)
(0.9 m)

The in-rack sprinkler numbers represent which IRAS


sprinklers to include in the hydraulic design
depending on the number of in-rack sprinklers
indicated for the in-rack sprinkler design

Fig. 35. Horizontal IRAS Arrangement for Open-Top Combustible Containers within a Mini-Load ASRS Where Rack Row
Depths Do Not Exceed 3 ft (0.9 m) and the Maximum Horizontal Spacing is 2 ft (0.60 m) per Table 39

Max. 2-1/2 ft Open-Top


(0.75 m) Container

Max
18 in. Max
1 2 3 4 5 6 7 8 3 ft
(450 mm)
(0.9 m)

The in-rack sprinkler numbers represent which IRAS


sprinklers to include in the hydraulic design
depending on the number of in-rack sprinklers
indicated for the in-rack sprinkler design Note: The in-rack sprinklers do not need
to align with the transverse flue spaces
located between the rack uprights

Fig. 36. Horizontal IRAS Arrangement for Open-Top Combustible Containers within a Mini-Load ASRS Where Rack Row
Depths Do Not Exceed 3 ft (0.9 m) and the Maximum Horizontal Spacing is 4 ft (1.2 m) per Table 39

2.2.7.2.2 Vertical Location of In-Rack Sprinklers and In-Rack Sprinkler System Designs for the
Protection of Open-Top, Combustible Containers in a Mini-Load ASRS
2.2.7.2.2.1 Storage Racks Not Requiring Vertical Barriers
1. When Section 2.2.1.4 indicates that vertical barriers are not required due to transverse flue spaces
being provided, use Table 40 to determine the allowable in-rack sprinkler vertical locations as well as
the corresponding recommended in-rack sprinkler design.
2. Limit the storage height above the top in-rack sprinkler level to a maximum height of 10 ft (3.0 m).

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


8-34 Protection for Automatic Storage
Page 80 FM Global Property Loss Prevention Data Sheets

Note: The in-rack sprinklers do not need Open-Top


to align with the transverse flue spaces Max. 2-1/2 ft
(0.75 m) Container
located between the rack uprights

Max
18 in.
(450 mm) 1 3 5 7

Max
6 ft
(1.8 m)

2 4 6 8

The in-rack sprinkler numbers represent which IRAS


sprinklers to include in the hydraulic design
depending on the number of in-rack sprinklers
indicated for the in-rack sprinkler design

Fig. 37. Horizontal IRAS Arrangement for Open-Top Combustible Containers within a Mini-Load ASRS Where Rack Row
Depths Do Not Exceed 6 ft (1.8 m) and the Maximum Horizontal Spacing is 2-1/2 ft (0.75 m) per Table 39

Max. 2 ft Open-Top
(0.6 m) Container

Max
18 in.
(450 mm) 1 3 5 7

Max
6 ft
(1.8 m)

2 4 6 8

The in-rack sprinkler numbers represent which IRAS


sprinklers to include in the hydraulic design
depending on the number of in-rack sprinklers
indicated for the in-rack sprinkler design

Fig. 38. Horizontal IRAS Arrangement for Open-Top Combustible Containers within a Mini-Load ASRS Where Rack Row
Depths Do Not Exceed 6 ft (1.8 m) and the Maximum Horizontal Spacing is 2 ft (0.60 m) per Table 39

3. While the in-rack sprinkler designs given in Table 40 are based on flow, the corresponding design
pressure for the chosen in-rack sprinkler cannot be less than 7 psi (0.5 bar). When the design pressure
will be less than 7 psi (0.5 bar), use a minimum pressure of 7 psi (0.5 bar) for design purposes,
regardless of the in-rack sprinkler’s K-factor value.
2.2.7.2.2.2 Storage Racks Requiring Vertical Barriers
When Section 2.2.1.4 indicates that vertical barriers are required due to the lack of acceptable transverse
flue spaces, install the in-rack sprinklers vertically using the design guidelines indicated in Section 2.2.7.2.2.1.
However, include all of the in-rack sprinklers installed between the vertical barriers in the in-rack sprinkler
design.
For example, if a wet, in-rack sprinkler system is being used to protect open-top, unexpanded plastic
containers being stored within a mini-load ASRS which is to be protected with in-rack sprinklers per Figure
37, and the number of in-rack sprinklers between the vertical barriers is 9, then the design for the in-rack
sprinkler system would be per Table 40 and would be based on 9 IRAS @ 100 gpm (380 L/min) instead of
6 IRAS @ 100 gpm (380 L/min).

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


Protection for Automatic Storage 8-34
FM Global Property Loss Prevention Data Sheets Page 81

Max. 4 ft Open-Top
(1.2 m) Container

Max
18 in.
(450 mm) 1 3 5 7

Max
6 ft
(1.8 m)

2 4 6 8

The in-rack sprinkler numbers represent which IRAS


sprinklers to include in the hydraulic design
depending on the number of in-rack sprinklers
indicated for the in-rack sprinkler design

Fig. 39. Horizontal IRAS Arrangement for Open-Top Combustible Containers within a Mini-Load ASRS Where Rack Row
Depths Do Not Exceed 6 ft (1.8 m) and the Maximum Horizontal Spacing is 4 ft (1.2 m) per Table 39

Note: The in-rack sprinklers do not need


Open-Top
to align with the transverse flue spaces
Container Max. 2-1/2 ft
located between the rack uprights
(0.75 m)

Max
18 in.
(450 mm) 1 3 5 7

Max
5 ft
(1.5 m)

Max
2 ft 2 4 6
2 2
8
(0.6 m)

The in-rack sprinkler numbers represent which


sprinklers to include in the hydraulic design IRAS
depending on the number of in-rack sprinklers
indicated for the in-rack sprinkler design

Fig. 40. Horizontal IRAS Arrangement for Open-Top Combustible Containers within a Mini-Load ASRS Where the Overall
Rack Depths Do Not Exceed 14 ft (4.3 m) and the Maximum Horizontal Spacing is 2-1/2 ft (0.75 m) per Table 39

Open-Top
Container Max. 2 ft
(0.6 m)

Max
18 in.
(450 mm) 1 3 5 7

Max
5 ft
(1.5 m)

Max
2 ft 2 4 6
2 2
8
(0.6 m)

The in-rack sprinkler numbers represent which


sprinklers to include in the hydraulic design IRAS
depending on the number of in-rack sprinklers
indicated for the in-rack sprinkler design

Fig. 41. Horizontal IRAS Arrangement for Open-Top Combustible Containers within a Mini-Load ASRS Where the Overall
Rack Depths Do Not Exceed 14 ft (4.3 m) and the Maximum Horizontal Spacing is 2 ft (0.60 m) per Table 39

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


8-34 Protection for Automatic Storage
Page 82 FM Global Property Loss Prevention Data Sheets

Open-Top
Container Max. 4 ft
(1.2 m)

Max
18 in.
(450 mm) 1 3 5 7

Max
5 ft
(1.5 m)

Max
2 ft 2 4 6
2 2
8
(0.6 m)

The in-rack sprinkler numbers represent which


sprinklers to include in the hydraulic design IRAS
depending on the number of in-rack sprinklers
indicated for the in-rack sprinkler design

Fig. 42. Horizontal IRAS for Open-Top Combustible Containers within a Mini-Load ASRS Where the Overall Rack Depths
Do Not Exceed 14 ft (4.3 m) and the Maximum Horizontal Spacing is 4 ft (1.2 m) per Table 39

Note: The in-rack sprinklers do not need


Max
Open-Top 2-1/2 ft to align with the transverse flue spaces
Container (0.75 m) located between the rack uprights

Max
18 in.
(450 mm) 2
1 3
2 5 7

Over
2 2
4 6 8 6 ft
(1.8 m)

Max. 4 ft
(1.2 m)

The in-rack sprinkler numbers represent which


sprinklers to include in the hydraulic design IRAS
depending on the number of in-rack sprinklers
indicated for the in-rack sprinkler design

Fig. 43. Horizontal IRAS Arrangement for Open-Top Combustible Containers within a Mini-Load ASRS Where Rack Row
Depths Exceed 6 ft (1.8 m) and the Maximum Horizontal Spacing is 2-1/2 ft (0.75 m) per Table 39

Open-Top Max
Container 2 ft
(0.6 m) IRAS

Max
18 in.
(450 mm) 2
1 3
2 5 7

Over
2 2
4 6 8 6 ft
(1.8 m)

Max. 4 ft
(1.2 m)

The in-rack sprinkler numbers represent which


sprinklers to include in the hydraulic design
depending on the number of in-rack sprinklers
indicated for the in-rack sprinkler design

Fig. 44. Horizontal IRAS Arrangement for Open-Top Combustible Containers within a Mini-Load ASRS Where Rack Row
Depths Exceed 6 ft (1.8 m) and the Maximum Horizontal Spacing is 2 ft (0.60 m) per Table 39

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


Protection for Automatic Storage 8-34
FM Global Property Loss Prevention Data Sheets Page 83

Max
Open-Top 4 ft
Container (1.2 m) IRAS

Max
18 in.
(450 mm) 2
1 3
2 5 7

Over
2 2
4 6 8 6 ft
(1.8 m)

Max. 4 ft
(1.2 m)

The in-rack sprinkler numbers represent which


sprinklers to include in the hydraulic design
depending on the number of in-rack sprinklers
indicated for the in-rack sprinkler design

Fig. 45. Horizontal IRAS Arrangement for Open-Top Combustible Containers within a Mini-Load ASRS Where Rack Row
Depths Exceed 6 ft (1.8 m) and the Maximum Horizontal Spacing is 4 ft (1.2 m) per Table 39

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


8-34 Protection for Automatic Storage
Page 84 FM Global Property Loss Prevention Data Sheets

Table 40. Vertical In-Rack Sprinkler Locations and In-Rack Sprinkler Designs for the Protection of Open-Top, Combustible
Containers Stored in a Mini-Load Type System
Maximum Hydraulically
Vertical Minimum Balance
Recommended Distance IRAS IRAS
IRAS Open-Top Maximum IRAS Between Design Minimum No. of System with
Arrangement Container Commodity System IRAS, ft Flow, gpm IRAS IRAS in Ceiling
per Table 39 Composition Classification Type (m) (L/min)* K-factor Design System?
Figure 34 Cardboard Any Wet 10 (3.0) 100 (380) 11.2 (160) 4 on top No
or IRAS level
Unexpanded Dry 10 (3.0) 100 (380) 11.2 (160) 8 if one Yes
Plastic Upright IRAS level
or 14 (7
on top 2
levels)
Figure 35 Cardboard Any Wet 10 (3.0) 100 (380) 11.2 (160) 4 on top No
IRAS level
15 (4.6) 140 (530) 22.4 (320) 6 on top No
Pendent IRAS level
Dry 10 (3.0) 100 (380) 11.2 (160) 8 if one Yes
Upright IRAS level
or 14 (7
on top 2
levels)
Figure 36 Unexpanded Any Wet 10 (3.0) 100 (380) 11.2 (160) 4 on top No
Plastic IRAS level
15 (4.6) 140 (530) 22.4 (320) 6 on top No
Pendent IRAS level
Dry 10 (3.0) 100 (380) 11.2 (160) 8 if one Yes
Upright IRAS level
or 14 (7
on top 2
levels)
Figures 37 or Cardboard Any Wet 10 (3.0) 100 (380) 11.2 (160) 6 on top No
40 or IRAS level
Unexpanded Dry 10 (3.0) 100 (380) 11.2 (160) 8 if one Yes
Plastic Upright IRAS level
or 14 (7
on top 2
levels)
* The indicated in-rack sprinkler design flow is based on a minimum 9 in. (225 mm) vertical distance between storage tier levels. If the vertical
distance between vertical tier levels is less than 9 in. (225 mm), add 20 gpm (75 L/min) to the indicated design flow.

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


Protection for Automatic Storage 8-34
FM Global Property Loss Prevention Data Sheets Page 85

Table 40. Vertical In-Rack Sprinkler Locations and In-Rack Sprinkler Designs for the Protection of Open-Top, Combustible
Containers Stored in a Mini-Load Type System (continued)
Maximum Hydraulically
Vertical Minimum Balance
Recommended Distance IRAS IRAS
IRAS Open-Top Maximum IRAS Between Design Minimum No. of System with
Arrangement Container Commodity System IRAS, ft Flow, gpm IRAS IRAS in Ceiling
per Table 39 Composition Classification Type (m) (L/min)* K-factor Design System?
Figures 38, Cardboard Any Wet 10 (3.0) 100 (380) 11.2 (160) 6 on top No
41, or 44 IRAS level
15 (4.6) 140 (530) 22.4 (320) 6 on top No
Pendent IRAS level
Dry 10 (3.0) 100 (380) 11.2 (160) 8 if one Yes
Upright IRAS level
or 14 (7
on top 2
levels)
Figures 39, Unexpanded Any Wet 10 (3.0) 100 (380) 11.2 (160) 6 on top No
42, or 45 Plastic IRAS level
15 (4.6) 140 (530) 22.4 (320) 6 on top No
Pendent IRAS level
Dry 10 (3.0) 100 (380) 11.2 (160) 8 if one Yes
Upright IRAS level
or 14 (7
on top 2
levels)
Figure 43 Cardboard Any Wet 10 (3.0) 100 (380) 11.2 (160) 8 on top No
or IRAS level
Unexpanded Dry 10 (3.0) 100 (380) 11.2 (160) 8 if one Yes
Plastic Upright IRAS level
or 14 (7
on top 2
levels)
* The indicated in-rack sprinkler design flow is based on a minimum 9 in. (225 mm) vertical distance between storage tier levels. If the vertical
distance between vertical tier levels is less than 9 in. (225 mm), add 20 gpm (75 L/min) to the indicated design flow.

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


8-34 Protection for Automatic Storage
Page 86 FM Global Property Loss Prevention Data Sheets

2.2.7.2.3 Ceiling Sprinkler System Designs in Combination with In-Rack Sprinklers for the Protection
of Open-Top, Combustible Containers in a Mini-Load ASRS
2.2.7.2.3.1 Use Table 41 to determine the wet ceiling-level sprinkler system designs in combination with
in-rack sprinklers. If a protection option is not available from the applicable protection table, either:
1. Install a flat, continuous, noncombustible false ceiling, capable of withstanding an uplift pressure of 3
lb/ft² (14.4 kg/m²), over the ASRS storage area and for a minimum of 15 ft (4.6 m) beyond the ASRS
area in all directions with sprinklers installed underneath the false ceiling in accordance with Table 41,
or
2. Install in-rack sprinklers over the top of storage and design the ceiling sprinkler system per Table 41.
2.2.7.2.3.2 Use Table 42 to determine the dry ceiling-level sprinkler system designs in combination with in-rack
sprinklers. If a protection option is not available from the applicable protection table, either:
1. Install a flat, continuous, noncombustible false ceiling, capable of withstanding an uplift pressure of 3
lb/ft² (14.4 kg/m²), over the ASRS storage area and for a minimum of 15 ft (4.6 m) beyond the ASRS
area in all directions with sprinklers installed underneath the false ceiling in accordance with Table 42,
or
2. Install in-rack sprinklers over the top of storage and design the ceiling sprinkler system per Table 42.
2.2.7.2.3.3 The ceiling-level sprinkler system designs in Tables 41 and 42 are determined using the vertical
distance between the top in-rack sprinkler level and the maximum ceiling height above the ASRS protected
area.
2.2.7.2.3.4 See Section 2.2.1.6 to determine the ceiling sprinkler’s hose demand design and water supply
duration.
2.2.7.2.3.5 See Section 2.1.4.5.4 to determine the number of sprinklers per branch line for ceiling-level
sprinkler calculations.

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


Table 41. Wet System Ceiling-Level Sprinkler Protection Guidelines, in Combination with In-Rack Sprinklers, for the Protection of Open-Top Combustible Containers in a Mini-Load

FM Global Property Loss Prevention Data Sheets


Protection for Automatic Storage
ASRS; No. of AS @ psi (bar)
Max. Max.
Storage Vertical Ceiling-Level Sprinkler Protection Options for Mini-Load ASRS Arrangements with Open-Top Combustible Containers; No. of AS @ psi (bar)
Height Distance Wet System, Pendent Storage Sprinklers, 160°F (70°C) Wet System, Upright Storage Sprinklers, 160°F (70°C)
Above Between
Quick-Response Standard-Response Quick-Response Standard-Response
Top Top IRAS
IRAS Level and 11.2 14.0 16.8 22.4 25.2 25.2EC 28.0 33.6 11.2 14.0 19.6 25.2 11.2 14.0 16.8 25.2EC 11.2 16.8 25.2
Level, Ceiling, ft (160) (200) (240) (320) (360) (360EC) (400) (480) (160) (200) (280) (360) (160) (200) (240) (360EC) (160) (240) (360)
ft (m) (m)
0 (0) Any 20 @ 9@ 9@ 9@ 9@ 6 @ 20 9@ 9@ 20 @ 9@ 9@ 9 @ 7 20 @ 9@ 9@ 6 @ 20 20 @ 9@ 9@7
©2017-2023 Factory Mutual Insurance Company. All rights reserved.

7 (0.5) 20 20 20 20 (1.4) 40 55 7 (0.5) 20 16 (0.5) 7 (0.5) 20 20 (1.4) 7 (0.5) 20 (0.5)


(1.4) (1.4) (1.4) (1.4) (2.8) (3.8) (1.4) (1.1) (1.4) (1.4) (1.4)
5 (1.5) 10 (3.0) 20 @ 12 @ 12 @ 9@ 9@ 10 @ 9@ 9@ 20 @ 20 @ 20 @ 20 @ 20 @ 20 @ 20 @ 10 @ 20 @ 20 @ 20 @
30 25 18 20 20 22 (1.0) 40 55 30 18 16 7 (0.5) 30 18 13 22 (1.0) 30 13 7 (0.5)
(2.1) (1.7) (1.2) (1.4) (1.4) (2.8) (3.8) (2.1) (1.2) (1.1) (2.1) (1.2) (0.9) (2.1) (0.9)
15 (4.6) 25 @ 10 @ 10 @ 9@ 9@ 12 @ 9@ 9@ 25 @ 25 @ 25 @ 25 @ 25 @ 25 @ 25 @ 12 @ 25 @ 25 @ 25 @
50 35 25 20 20 38 (2.6) 40 55 50 32 16 10 50 32 22 38 (2.6) 50 22 10
(3.5) (2.4) (1.7) (1.4) (1.4) (2.8) (3.8) (3.5) (2.2) (1.1) (0.7) (3.5) (2.2) (1.5) (3.5) (1.5) (0.7)
20 (6.1) 12 @ 12 @ 12 @ 12 @ 9@ 9@
50 35 20 20 40 55
(3.5) (2.4) (1.4) (1.4) (2.8) (3.8)
10 15 (4.6) 25 @ 10 @ 10 @ 9@ 9@ 12 @ 9@ 9@ 25 @ 25 @ 25 @ 25 @ 25 @ 25 @ 25 @ 12 @ 25 @ 25 @ 25 @
(3.0) 50 35 25 20 20 38 (2.6) 40 55 50 32 16 10 50 32 22 38 (2.6) 50 22 10
(3.5) (2.4) (1.7) (1.4) (1.4) (2.8) (3.8) (3.5) (2.2) (1.1) (0.7) (3.5) (2.2) (1.5) (3.5) (1.5) (0.7)
20 (6.1) 12 @ 12 @ 12 @ 12 @ 9@ 9@
50 35 20 20 40 55
(3.5) (2.4) (1.4) (1.4) (2.8) (3.8)
Note: The ceiling-level protection options highlighted in green represent those for which the hose stream demand is 250 gpm (950 L/min) and the sprinkler system duration is 1 hour.

Page 87
8-34
8-34 Protection for Automatic Storage
Page 88 FM Global Property Loss Prevention Data Sheets

Table 42. Dry System Ceiling-Level Sprinkler Protection Guidelines, in Combination with In-Rack Sprinklers, for the
Protection of Open-Top Combustible Containers in a Mini-Load ASRS; No. of AS @ psi (bar)
Ceiling-Level Sprinkler Protection Options for Mini-Load ASRS Arrangements
Max. Vertical with Open-Top Combustible Containers; No. of AS @ psi (bar)
Max. Storage Distance Between Dry System, Upright Storage Sprinklers, 280°F (140°C)
Height Above Top Top IRAS Level Standard-Response
IRAS Level, ft (m) and Ceiling, ft (m) 11.2 (160) 16.8 (240) 25.2 (360) 33.6 (480)
0 (0) Any 25 @ 7 (0.5) 25 @ 7 (0.5) 25 @ 7 (0.5) 25 @ 50 (3.5)
5 (1.5) 10 (3.0) 25 @ 30 (2.1) 25 @ 13 (0.9) 25 @ 7 (0.5) 25 @ 50 (3.5)
15 (4.6) 30 @ 50 (3.5) 30 @ 22 (1.5) 30 @ 10 (0.7) 30 @ 50 (3.5)
10 (3.0) 15 (4.6) 30 @ 50 (3.5) 30 @ 22 (1.5) 30 @ 10 (0.7) 30 @ 50 (3.5)

2.3 Top-Loading Automatic Storage and Retrieval Systems (TL-ASRS)

2.3.1 General Guidelines for TL-ASRS Storage Arrangements


2.3.1.1 This section provides protection guidelines for TL-ASRS storage arrangements that use open-top,
solid-bottomed containers. It is further subdivided into sections specific to noncombustible open-top,
solid-bottom, solid-walled containers in Section 2.3.5, combustible open-top, solid-bottom, solid-walled
containers in Section 2.3.6, and open-top, solid-bottom, non-solid-walled containers in Section 2.3.7.
2.3.1.2 What differentiates this storage arrangement from other ASRS storage arrangements is that the
containers are loaded and unloaded vertically from the storage array using automated robots that move about
the storage area on an elevated gridded track network. Since material handling is done in a vertical manner,
traditional material-handling equipment, such as fork-lifts, are not required, eliminating the need for aisles
between storage arrays.

2.3.2 Drainage
2.3.2.1 Due to the expected water application duration during a fire event, when possible provide minimum
4 in. (100 mm) high curbing at the perimeter of the storage array in combination with properly designed floor
drainage (account for both ceiling sprinkler discharge and an additional 500 gpm [1900 L/min] for manual
firefighting efforts).
2.3.2.2 The guidelines for drainage in Section 2.3.2.1 are not required when noncombustible solid-walled
containers are used throughout the ASRS storage array.

2.3.3 Robots and Robot Holding Areas

2.3.3.1 Robots
Arrange the robots so they are void of as much exterior combustible materials as possible. Use
noncombustible materials whenever decorative covers, sidings or other similar identification methods are
needed for the robots.

2.3.3.2 Robot Holding Areas


2.3.3.2.1 Establish designated “Robot Holding Areas” anywhere on the storage grid to which all robots can
move upon the activation of the fire detection system outlined in Section 2.3.4. See Figure 46 for an example
of this arrangement.
2.3.3.2.2 Do not designate areas directly above storage grid area access points as Robot Holding Areas.
2.3.3.2.3 Maintain the storage columns directly below the Robot Holding Areas free of combustible storage.
2.3.3.2.4 The guidelines for Robot Holding Areas are not required when noncombustible solid-walled
containers are used throughout the ASRS storage array.

2.3.4 Fire Detection


2.3.4.1 Install a FM Approved ceiling-level very early warning fire detection system over the storage array
accordance with Data Sheet 5-48, Automatic Fire Detection.

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


Protection for Automatic Storage 8-34
FM Global Property Loss Prevention Data Sheets Page 89

Perimeter Mezzanine Level

Top-Loading Robot
ASRS Grid Area Holding
Areas
Yellow Areas Void
of Storage

Perimeter Mezzanine Level

Egress to
Mezzanine Level

Fig. 46. Examples of Potential Robot Holding Areas

2.3.4.2 When the ceiling construction over the storage array is considered unobstructed per Data Sheet 2-0,
Installation Guidelines for Automatic Sprinklers, install the detectors on a spacing that does not exceed 50%
of the maximum allowable spacing indicated in the Approval Guide using an obscuration rate that is in
accordance with the detection system manufacturer’s guidelines.
2.3.4.3 When the ceiling construction over the storage array is considered obstructed per Data Sheet 2-0,
install the detectors using the same spacing as the ceiling-level sprinklers using selecting an obscuration rate
that is in accordance with the detection system manufacturer’s guidelines.
2.3.4.4 Arrange the fire detection system upon activation to:
1. Ssend an alarm to a constantly attended location, and
2. Automatically send the robots to the Robot Holding Area, and
3. Deactivate the robot charging stations
2.3.4.5 The guidelines for fire detection as outlined in Sections 2.3.4.1 through 2.3.4.4 are not required when
noncombustible solid-walled containers are used throughout the ASRS storage array.

2.3.5 Protection of Noncombustible Solid-Walled Containers

2.3.5.1 Ceiling-Level Sprinkler System Types


2.3.5.1.1 Depending on the ambient temperature of the ASRS area being protected, ceiling-level sprinkler
systems can be one of the following:
A. Wet-pipe sprinkler systems
B. Dry-pipe sprinkler systems
C. Non-interlocked or single-interlocked preaction sprinkler systems

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


8-34 Protection for Automatic Storage
Page 90 FM Global Property Loss Prevention Data Sheets

D. Refrigerated area sprinkler systems


E. Antifreeze solution sprinkler systems consisting of a 20% to 30% propylene glycol concentration in
water
2.3.5.1.2 The maximum water delivery time for all dry-pipe and similar sprinkler systems is 40 seconds upon
the operation of the hydraulically most remote 4 sprinklers (2 sprinklers on 2 lines).
2.3.5.1.3 When installing a preaction or refrigerated area sprinkler system, see Data Sheet 5-48, Automatic
Fire Detection, for recommendations pertaining to the sprinkler system’s activating detection system.
2.3.5.1.4 Ceiling sprinkler designs for single-interlocked preaction sprinkler systems can be either classified
as “wet-pipe” or “dry-pipe,” depending on the installation of the activating detection system. See Data Sheet
5-48 to determine the installation requirements needed for the detection system to achieve a sprinkler system
design classification of wet pipe. Design the single-interlocked preaction system using the dry-pipe sprinkler
system designs in Table 43 when the detection installation is not in compliance with the recommendations
provided in Data Sheet 5-48 for a wet-pipe sprinkler system design.
2.3.5.1.5 A ceiling-level sprinkler system consisting of 20% to 30% concentration of propylene glycol in water
is acceptable for ambient temperatures between 32ºF (0ºC) and 40ºF (4ºC).
2.3.5.1.6 When installing an antifreeze sprinkler system consisting of a 20% to 30% concentration of
propylene glycol in water, the ceiling designs indicated for a wet-pipe sprinkler system can be used.
2.3.5.1.7 See Data Sheet 2-0 for additional recommendations related to the installation of all sprinkler system
types and when a refrigerated area sprinkler system is installed.

2.3.5.2 Ceiling-Level Sprinklers


2.3.5.2.1 For ceiling heights up to 55 ft (16.8 m), install FM Approved Storage ceiling-level sprinklers in
accordance with the design guidelines offered in Table 43.
2.3.5.2.2 For ceiling heights over 55 ft (16.8 m), install a flat, continuous noncombustible false ceiling over
the ASRS storage area and for a minimum of 15 ft (4.6 m) beyond it in all directions. Design the false ceiling
to be capable of withstanding a minimum uplift pressure of 3 lb/ft2 (14.4 kg/m2). Provide sprinkler protection
under this false ceiling in accordance with Table 43.
2.3.5.2.3 When elevated mezzanines are present, provide sprinkler protection under them in accordance
with Data Sheet 2-0.

2.3.5.3 Ceiling-Level Sprinkler System Design Criteria


2.3.5.3.1 Use Table 43 to determine the ceiling-level sprinkler system designs for TL-ASRS storage
arrangements using solid-walled noncombustible containers.

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


Table 43. Ceiling-Level Protection Guidelines for TL-ASRS Storage Arrangements Using Open-Top Solid-Walled Noncombustible Containers

FM Global Property Loss Prevention Data Sheets


Protection for Automatic Storage
Ceiling-Level Sprinkler Protection Options for Top-Loading ASRS Arrangements; No. of AS @ psi (bar)
Wet System, Pendent Storage Sprinklers, 160°F (70°C) Wet System, Upright Storage Sprinklers, 160°F (70°C)
Dry System, Upright Storage Sprinklers,
Max. 280°F (140°C)
Ceiling Quick-Response Standard-Response Quick-Response Standard-Response Standard-Response
Height, ft K11.2 K14.0 K16.8 K22.4 K25.2 K25.2EC K28.0 K33.6 K11.2 K14.0 K19.6 K25.2 K11.2 K14.0 K16.8 K25.2EC K11.2 K16.8 K25.2 K11.2 K16.8 K25.2 K33.6
(m) (K160) (K200) (K240) (K320) (K360) (K360EC) (K400) (K480) (K160) (K200) (K280) (K360) (K160) (K200) (K240) (K360EC) (K160) (K240) (K360) (K160) (K240) (K360) (K480)
20 (6.1) 12 @ 10 12 @ 7 12 @ 7 9 @ 20 9 @ 20 6 @ 20 9 @ 40 9 @ 55 12 @ 10 12 @ 7 9 @ 16 9@7 12 @ 10 12 @ 7 12 @ 7 6 @ 20 12 @ 10 12 @ 7 9 @ 7 16 @ 10 16 @ 7 16 @ 7 12 @ 50
(0.7) (0.5) (0.5) (1.4) (1.4) (1.4) (2.8) (3.8) (0.7) (0.5) (1.1) (0.5) (0.7) (0.5) (0.5) (1.4) (0.7) (0.5) (0.5) (0.7) (0.5) (0.5) (3.5)
25 (7.6) 10 @ 30 10 @ 20 10 @ 13 9 @ 20 9 @ 20 6 @ 20 9 @ 40 9 @ 55 10 @ 30 10 @ 20 9 @ 16 10 @ 7 10 @ 30 10 @ 20 10 @ 13 6 @ 20 10 @ 30 10 @ 13 10 @ 7 20 @ 16 20 @ 7 20 @ 7 12 @ 50
(2.1) (1.4) (0.9) (1.4) (1.4) (1.4) (2.8) (3.8) (2.1) (1.4) (1.1) (0.5) (2.1) (1.4) (0.9) (1.4) (2.1) (0.9) (0.5) (1.1) (0.5) (0.5) (3.5)
©2017-2023 Factory Mutual Insurance Company. All rights reserved.

30 (9.1) 18 @ 50 12 @ 50 12 @ 35 9 @ 20 9 @ 20 6 @ 25 9 @ 40 9 @ 55 18 @ 50 18 @ 32 9 @ 16 9 @ 10 18 @ 50 12 @ 50 12 @ 35 6 @ 25 18 @ 50 18 @ 22 12 @ 20 20 @ 25 20 @ 10 20 @ 7 12 @ 50
(3.5) (3.5) (2.4) (1.4) (1.4) (1.7) (2.8) (3.8) (3.5) (2.2) (1.1) (0.7) (3.5) (3.5) (2.4) (1.7) (3.5) (1.5) (1.4) (1.7) (0.7) (0.5) (3.5)
35 (10.7) 9 @ 75 9 @ 52 9 @ 28 9 @ 22 6 @ 60 9 @ 40 9 @ 55 15 @ 25 9 @ 30 9 @ 75 9 @ 52 8 @ 40 20 @ 25 20 @ 10 20 @ 7 12 @ 50
(5.2) (3.6) (1.9) (1.5) (4.1) (2.8) (3.8) (1.7) (2.1) (5.2) (3.6) (2.8) (1.7) (0.7) (0.5) (3.5)
40 (12.2) 9 @ 75 9 @ 52 9 @ 28 9 @ 22 9 @ 40 9 @ 55 9 @ 30 36 @ 55 36 @ 22 12 @ 50 12 @ 50
(5.2) (3.6) (1.9) (1.5) (2.8) (3.8) (2.1) (3.8) ((1.5) (3.5) (3.5)
45 (13.7) 10 @ 63 10 @ 50 10 @ 40 9 @ 55 12 @ 50 12 @ 50
(4.3) (3.5) (2.8) (3.8) (3.5) (3.5)
50 (15.2) 10 @ 63 10 @ 50 10 @ 40 9 @ 55 15 @ 50
(4.3) (3.5) (2.8) (3.8) (3.5)
55 (16.8) 9 @ 80 9 @ 55 16 @ 50
(5.5) (3.8) (3.5)

Page 91
8-34
8-34 Protection for Automatic Storage
Page 92 FM Global Property Loss Prevention Data Sheets

2.3.5.3.2 Hose Demand Design Guidelines


Include a minimum flow of 250 gpm (950 L/min) for the hose demand design.

2.3.5.3.3 Water Supply Duration


Size the water supply feeding the ceiling sprinkler system and the hose stream demand, when taken from
the same water supply, for a minimum of 60 minutes.

2.3.6 Protection of Combustible Solid-Walled Containers

2.3.6.1 Final Extinguishment


2.3.6.1.1 General
2.3.6.1.1.1 Due to the lack of direct access by the local fire service to the fire area, review the
recommendations in this section that are intended to establish a means by which final extinguishment can
be achieved.
2.3.6.1.1.2 At a minimum, implement the recommendations in Sections 2.3.6.1.2, 2.3.6.1.3, and 2.3.6.1.4,
unless indicated otherwise in Section 2.3.6.1.5.
2.3.6.1.1.3 See Section 2.3.6.1.5 for ceiling-level protection options that will allow for the elimination of some
recommendations offered for final extinguishment.
2.3.6.1.1.4 When the guidelines of Section 2.3.6.1.5 are not met, see Sections 2.3.6.1.6 through 2.3.6.1.9
for recommendations to review and discuss with the local fire service to potentially assist with achieving final
extinguishment. Implement those recommendations deemed necessary by either the authority having
jurisdiction or the appropriate representatives from the local fire service.
2.3.6.1.2 Pre-Incident Plan
2.3.6.1.2.1 For TL-ASRS storage arrangements that use solid-walled containers, establish a pre-incident
plan with the local fire service that takes into consideration how the local fire service will gain access to any
point of the ASRS storage grid for final extinguishment purposes. Items to consider, at a minimum, are:
A. Access to the storage grid itself (i.e., removal of any separating walls or fences),
B. A plan to remove storage containers along with a place to put them, and
C. A means of preventing robots from falling from the grid into the storage area.
2.3.6.1.2.2 See Section 2.1.5 for additional guidance on pre-incident planning.
2.3.6.1.3 Storage Arrangement
To allow local fire service access to the fire area, arrange the TL-ASRS storage arrangement as follows:
1. Establish readily accessible, clearly marked designated locations along the side walls of the ASRS
unit that can be used as access points to the storage area. Provide as many access points as possible
to limit the horizontal distance between the access point and the potential fire area within the storage
area.
2. Consider limiting the horizontal distance between one end of the storage array and the opposite end
to a maximum of 100 ft (30 m).
2.3.6.1.4 Mezzanines and/or Platforms
2.3.6.1.4.1 To allow local fire service access adjacent to the top of the storage grid where strategic planning
can occur and hose streams can potentially be applied, install mezzanines and/or platforms at a minimum,
along the longer walls of the ASRS unit at a height equal to or above the storage grid. See Figure 47 for
examples of mezzanines and/or platforms. Note that if the maximum width of the storage array is 50 ft (15
m), then only a single mezzanine and/or platform would be needed. Determine from the local authority having
jurisdiction the minimum width of the mezzanine and/or platform they would require and the minimum number
of access points for each mezzanine and/or platform area.
2.3.6.1.4.2 If the horizontal distances between the ends of the storage array will exceed 100 ft (30 m) in
both directions, in addition to mezzanines and/or platforms install solid-floored elevated mezzanine levels

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


Protection for Automatic Storage 8-34
FM Global Property Loss Prevention Data Sheets Page 93

Top-Loading ASRS Grid Area < 50 ft


Top-Loading ASRS Grid Area < 50 ft
(15 m)
(15 m)

Mezzanine Level Adjacent to ASRS Platform Level Adjacent


to ASRS

Egress to
Egress to
Mezzanine Level
Platform Level

Egress to
Platform Level

Platform Level Adjacent


Mezzanine Level Adjacent to ASRS to ASRS

< 100 ft Top-Loading ASRS Grid Area < 100 ft


Top-Loading ASRS Grid Area (30 m)
(30 m)

Platform Level Adjacent


Mezzanine Level Adjacent to ASRS to ASRS

Egress to Egress to
Mezzanine Level Platform Level

Fig. 47. Examples of a TL-ASRS arrangement showing maximum 100 ft (30 m) depth in one direction

at maximum horizontal distances of 100 ft (30 m) as demonstrated in Figure 48. Arrange the elevated
mezzanines to allow robots the ability to pass underneath them.
2.3.6.1.4.3 The installation of elevated mezzanines can be avoided when:
1. The recommendations outlined in Section 2.3.6.1.5 for ceiling sprinkler designs are met, or
2. Fixed-in-place monitor nozzles and their associated monitoring cameras are installed over the storage
grid area at ceiling level and in accordance with Sections 2.3.6.1.8 and 2.3.6.1.9.
2.3.6.1.4.4 The installation of mezzanines and/or platforms, as well as elevated mezzanines, can be avoided
(if so chosen by the end user) by obtaining written confirmation from the local authority having jurisdiction
and/or local fire service that they would not plan to use these mezzanines during a fire event.
2.3.6.1.5 Alternative Ceiling-Level Sprinkler Protection Options for Final Extinguishment
2.3.6.1.5.1 The recommendations offered in Section 2.3.6.1.4.2 regarding elevated mezzanines as well as
Sections 2.3.6.1.7 through 2.3.6.1.9 (i.e., vertical barriers and fixed-in-place monitor nozzles) can be ignored
when the ceiling sprinkler system is designed and installed in accordance with this section.
2.3.6.1.5.2 Install a wet ceiling sprinkler system. Dry, pre-action, and anti-freeze solution sprinkler systems
are not acceptable.
2.3.6.1.5.3 Install FM Approved storage ceiling-level sprinklers in accordance with the design guidelines
offered in Table 44.

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


8-34 Protection for Automatic Storage
Page 94 FM Global Property Loss Prevention Data Sheets

Egress to Egress to
Platform Level Platform Level

Platform Level Adjacent Platform Level Adjacent


Elevated Mezzanine Level to ASRS to ASRS

Elevated Mezzanine Level

Elevated Mezzanine Level

Elevated Mezzanine Level


Top-Loading Top-Loading
ASRS Grid Area ASRS Grid Area
Top-Loading

Platform
Top-Loading > 100 ft

Level
> 100 ft
ASRS Grid Area ASRS Grid Area (30 m) (30 m)

< 100 ft (30 m) < 50 ft (15 m) < 100 ft (30 m)

Platform Level Adjacent Platform Level Adjacent


to ASRS to ASRS

Egress to Egress to
Platform Level Platform Level

Mezzanine Level Adjacent to ASRS Mezzanine Level Adjacent to ASRS

Mezzanine Level Adjacent to ASRS


Elevated Mezzanine Level

Elevated Mezzanine Level


Elevated Mezzanine Level

Elevated Mezzanine Level

Top-Loading Top-Loading
ASRS Grid Area ASRS Grid Area
Top-Loading Top-Loading > 100 ft > 100 ft
ASRS Grid Area ASRS Grid Area (30 m) (30 m)

< 100 ft (30 m) < 50 ft (15 m) < 100 ft (30 m)

Mezzanine Level Adjacent to ASRS Mezzanine Level Adjacent to ASRS

Egress to Egress to
Mezzanine Level Mezzanine Level

Fig. 48. Example of solid-floored elevated mezzanine levels when span of TL-ASRS exceeds 100 ft (30 m) in each direction

Table 44. Alternative Ceiling-Level Sprinkler Protection Options for Top-Loading ASRS Arrangements that Address Final
Extinguishment; Maximum Storage Height up to and Including 20 ft (6.1 m)
Alternative Ceiling-Level Sprinkler Protection Options for Top-Loading ASRS
Arrangements that Address Final Extinguishment; No. of AS @ psi (bar)
Max. Maximum Vertical Wet Sprinkler System Using Quick-Response 160°F (70°C) Pendent Storage
Ceiling Distance of Sprinkler Sprinklers
Height, ft Thermal Element Below K14.0 K16.8 K22.4 K25.2 K28.0 K33.6
(m) Ceiling, in. (mm) (K200) (K240) (K320) (K360) (K400) (K480)
25 (7.6) 13 (325) 9 @ 50 9 @ 35 9 @ 20 9 @ 20 9 @ 40 9 @ 55
(3.5) (2.4) (1.4) (1.4) (2.8) (3.8)
30 (9.1) 13 (325) 6 @ 120 6 @ 95 6 @ 65
(8.3) (6.6) (4.5)

2.3.6.1.5.4 Include a minimum flow of 250 gpm (950 L/min) for hose demand design.
2.3.6.1.5.5 Size the water supply feeding the ceiling sprinkler system for a minimum duration of two hours.
Include the hose stream demand (inside and outside) for water sizing purposes when it is taken from the
same water supply feeding the ceiling sprinkler system.
2.3.6.1.5.6 For ceiling sprinkler designs from Table 44 that consist of six sprinklers, base the hydraulic
calculation on the operation of two sprinklers flowing on three lines. For ceiling sprinkler designs from Table
44 that consist of nine sprinklers, base the hydraulic calculation on the operation of three sprinklers flowing
on three lines.
2.3.6.1.5.7 As part of the Pre-Incident Plan, arrange for the local fire service and facility personnel to allow
the sprinkler system to operate continuously for a minimum duration of two hours, or until the fire is confirmed
to be extinguished by accessing the fire area within the storage array.
2.3.6.1.5.8 See Data Sheet 2-0, Installation Guidelines for Automatic Sprinklers, for additional
recommendations related to the installation of the ceiling sprinkler system.

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


Protection for Automatic Storage 8-34
FM Global Property Loss Prevention Data Sheets Page 95

2.3.6.1.6 Small Hose Connection Stations


2.3.6.1.6.1 To aid in manual fire-fighting efforts and after-extinguishment mop-up operations, consider the
installation of small hose connection stations near the floor-level access points established for the local fire
service and on the mezzanine levels (perimeter and elevated), if provided. Consult with the local fire service
or authority having jurisdiction to determine their recommendations regarding:
A. The use of wet- or dry-barrel stations, and
B. The size of the hose connections, and
C. The horizontal distance between stations
2.3.6.1.6.2 Design the small hose connection station system to provide a minimum flow of 50 gpm (190 L/min)
from each of the two most hydraulically remote stations (100 gpm [380 L/min] total).
2.3.6.1.6.3 Arrange the water supplies feeding these stations in one of the following ways:
A. A piping system dedicated solely for the small hose connection stations, or
B. Piping that connects the stations to a sprinkler system that is different than the one protecting the ASRS
storage area
2.3.6.1.6.4 The installation of small hose connection stations can be avoided (if so chosen by the end user)
by obtaining written confirmation from the local authority having jurisdiction and/or local fire service that they
would not plan to use the small hose connection stations during a fire event.
2.3.6.1.7 Vertical Barriers
2.3.6.1.7.1 To assist with firefighting efforts, consider the installation of vertical barriers throughout the ASRS
storage area. When vertical barriers are to be provided throughout the storage area, install them as follows:
A. Use minimum 20-gauge (0.9 mm) sheet metal for the vertical barriers
B. Install the barriers from floor level to the top of the storage array
C. Attach the vertical barriers to each of the storage columns with a minimum of 3 tech screws per column
(near the top, middle, and bottom)
D. Provide a minimum 3 in. (75 mm) overlap, sealed with fire-rated silicone, of the barriers with the floor
and all sheet metal joints
E. Where the vertical barriers are required at corners, bend the sheet metal around the corner to avoid
any seams at these locations
2.3.6.1.7.2 Arrange the vertical barriers to limit the subdivided storage area to a maximum size of 1,000 ft2
(93 m2).
2.3.6.1.7.3 Maintain one row of storage on one side and adjacent to each of the vertical barriers free of
combustibles as shown in Figure 49.
2.3.6.1.7.4 To aid with access to the fire area, limit the number of vertical barriers for each subdivided area
to 3 or less as demonstrated in Figure 49.
2.3.6.1.7.5 Vertical barriers would be considered redundant with protection installed in accordance with
Section 2.3.6.1.5, Sections 2.3.6.1.8 and 2.3.6.1.9. As a result, if the protection outlined in Section 2.3.6.1.5
regarding ceiling sprinkler protection, or Sections 2.3.6.1.8 and 2.3.6.1.9 regarding fixed-in-place monitor
nozzles, are implemented, the installation of vertical barriers would not be needed.

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


8-34 Protection for Automatic Storage
Page 96 FM Global Property Loss Prevention Data Sheets

Platform Area Mezzanine Level Adjacent to ASRS

One Row on One One Row on One


Side of Barrier Top-Loading Side of Barrier Top-Loading
Void of Storage ASRS Grid Area Void of Storage ASRS Grid Area

Max. 1,000 ft2 (93m2) Max. 1,000 ft2 (93m2)


Storage Area Between Storage Area Between
Barriers Barriers

Vertical Vertical
Barrier Barrier

Platform Area Mezzanine Level Adjacent to ASRS

Example of segregated areas using Example of segregated areas using


2 vertical barriers 2 vertical barriers

Platform Area Mezzanine Level Adjacent to ASRS

Top-Loading Top-Loading
ASRS Grid Area ASRS Grid Area
One Row on One One Row on One
Side of Barrier Side of Barrier
Void of Storage Void of Storage

Vertical Vertical
Barrier Barrier

Max. 1,000 ft2 (93m2) Max. 1,000 ft2 (93m2)


Storage Area Between Storage Area Between
Barriers Barriers

Platform Area Mezzanine Level Adjacent to ASRS

Example of subdivided areas using 3 Example of subdivided areas using 3


vertical barriers vertical barriers

Fig. 49. Examples showing the use of vertical barriers within a TL-ASRS arrangement

2.3.6.1.8 Fixed-In-Place Monitor Nozzle Protection


2.3.6.1.8.1 To assist with firefighting efforts, consider the installation of fixed-in-place monitor nozzles
throughout the ASRS storage area.
2.3.6.1.8.2 The monitor nozzles can be fixed-in-place either to the mezzanines and/or to the overhead ceiling
structure.
A. When the monitor nozzles are fixed-in-place on the mezzanine structure, position the monitor nozzles
a minimum 7 ft (2.1 m) above the top of the ASRS grid as well at a minimum of 2 ft (0.6 m) below the
underside of the ceiling.
B. When the monitor nozzles are fixed-in-place to the overhead ceiling structure, position the monitor
nozzles so they do not obstruct ceiling sprinkler discharge.
2.3.6.1.8.3 Space the monitor nozzles horizontally as follows:
A. A maximum of 100 ft (30 m) between monitor nozzles, and
B. A maximum of 50 ft (15 m) between a monitor nozzle and the nearest corner of the storage array
See Figures 50 and 51 for an example of this arrangement.

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


Protection for Automatic Storage 8-34
FM Global Property Loss Prevention Data Sheets Page 97

Max. 100 ft (30 m) Max. 50 ft (15 m)

Mezzanine Level Mezzanine Level

< 50 ft
(15 m)

Top-Loading Top-Loading < 100 ft


Top-Loading ASRS Grid Area > 100 ft
(30 m)
ASRS Grid Area ASRS Grid Area (30 m)

< 50 ft
(15 m)

Monitor Nozzle Mezzanine Level

Plan View
Plan View

Ceiling > 2 ft Ceiling > 2 ft


(0.6 m) (0.6 m)
Monitor Monitor
Monitor < 7 ft Monitor
Nozzle Nozzle
Nozzle (2.1 m) Nozzle
Top of Grid > 7 ft
Elevated (2.1 m) Elevated
Perimeter Perimeter
Mezzanine Mezzanine Mezzanine Mezzanine
Level Level Top of Grid

Top-Loading ASRS Removable


Wall
Storage Area Panels Top-Loading ASRS
Storage Area

Floor Floor

< 100 ft (30 m)


Elevation View
Elevation View

Fig. 50. Example of TL-ASRS arrangement protected by fixed-in-place monitor nozzles installed on the mezzanines

2.3.6.1.8.4 Arrange the monitor nozzles to be capable of:


A. Being operated remotely from a dedicated location that will not be affected by a fire involving the ASRS
storage area, and
B. Being operated manually at the monitor nozzle when the monitor nozzles are installed on mezzanines
2.3.6.1.8.5 Design the monitor nozzle system to provide a minimum flow of 200 gpm (760 L/min) from each
of the two most hydraulically remote monitor nozzles (400 gpm [1,520 L/min] total).
2.3.6.1.8.6 Water supplies for the monitor nozzles can be arranged in one of the following methods:
A. A piping system dedicated solely for the monitor nozzles, or
B. From sprinkler systems that are different than the one protecting the ASRS storage area
2.3.6.1.8.7 Fixed-in-place monitor nozzles would be considered redundant with ceiling sprinkler protection
installed in accordance with Section 2.3.6.1.5. As a result, the installation of fixed-in-place monitor nozzles
would not be needed (if so chosen by the end user) when:
A. The recommendations outlined in Section 2.3.6.1.5 are met, or
B. Written confirmation has been obtained from the local authority having jurisdiction and/or local fire
service that they would not plan to use the monitor nozzles during a fire event.
2.3.6.1.9 Visible or Infrared Camera Installation for Fixed-In-Place Monitor Nozzle Operation
2.3.6.1.9.1 To allow for guided discharge of the monitor nozzles to the point of fire origin, install infrared (IR)
cameras over the entire storage grid, in accordance with this section, using dedicated feeds to the remote
location designated for monitor nozzle operation.
2.3.6.1.9.2 Arrange the IR cameras as follows:

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


8-34 Protection for Automatic Storage
Page 98 FM Global Property Loss Prevention Data Sheets

< 100 ft (30 m) < 50 ft (15 m)

Top-Loading ASRS Grid Area > 100 ft


< 100 ft (30 m)
(30 m)

< 50 ft
Monitor Nozzle (30 m)

Plan View

Ceiling
Monitor Monitor
Nozzle Nozzle

Top of Grid
Perimeter Perimeter
Mezzanine Mezzanine

Top-Loading ASRS
Storage Area

Floor

< 100 ft (30 m)

Elevation View
Fig. 51. Example of TL-ASRS arrangement protected by fixed-in-place monitor nozzles installed at ceiling level

A. Install longwave infrared (LWIR) cameras, capable of panning and tilting, that have a spectral range
of 8-12 µm, a minimum spatial resolution of 15 pixels/ft (45 pixels/m), measured at the farthest position from
the camera along the top surface of the storage array, and a field of view (FOV) that does not exceed
25°. Avoid the use of IR cameras that use charge-coupled device (CCD) sensors.
B. Locate the cameras vertically as high as possible over the storage grid while also avoiding obstruction
to the camera’s view. Position the cameras horizontally as close as possible to the halfway mark
in-between the locations of the fixed-in-place monitor nozzles. Maintain a minimum horizontal distance
of 10 ft (3.0 m) from any camera to the nearest fixed-in-place monitor nozzle.
C. Install the cameras so that every column of the storage array can be viewed by a minimum of two
cameras.
D. When possible, incorporate data into the camera view that can communicate to the remote location
operator the specific location of the storage grid the camera is viewing.
2.3.6.1.9.3 The installation of visible imaging cameras can be used in lieu of infrared cameras when:

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


Protection for Automatic Storage 8-34
FM Global Property Loss Prevention Data Sheets Page 99

A. The space between the top of the storage grid and the ceiling will be (1) unconfined so that smoke
can readily escape the ASRS storage area, and (2) the ceiling-level sprinklers will be quick-response,
minimum K14.0 (K200) standard-coverage pendent Storage sprinklers, or
B. The space between the top of the storage grid and the ceiling will be (1) confined so that smoke cannot
readily escape the ASRS storage area, and (2) manually-operated ceiling-level ventilation will be provided
that can be turned on upon fire service arrival to clear the storage grid area of visible smoke.
2.3.6.1.9.4 When permitted by Section 2.3.6.1.8.3, install visible imaging cameras over the entire storage
grid, using dedicated feeds to the remote location designated for monitor nozzle operation, as follows:
A. Install cameras, capable of panning and tilting, that have a minimum spatial resolution of 15 pixels/ft
(45 pixels/m), measured at the farthest position from the camera along the top surface of the storage array.
B. Locate the cameras vertically as high as possible over the storage grid while also avoiding obstruction
to the camera’s view. Position the cameras horizontally as close as possible to the halfway mark
in-between the locations of the fixed-in-place monitor nozzles. Maintain a minimum horizontal distance
of 10 ft (3.0 m) from any camera to the nearest fixed-in-place monitor nozzle.
C. Install the cameras so that every column of the storage array can be viewed by a minimum of two
cameras.
D. When possible, incorporate data into the camera view that can communicate to the remote location
operator the specific location of the storage grid the camera is viewing.
E. Arrange the recording equipment so that review of the video is possible to help identify where flames
have been visually observed.
2.3.6.1.9.5 When fixed-in-place monitor nozzles are being installed, the installation of IR or visible cameras
can be avoided (if so chosen by the end user) at the written discretion of the local authority having jurisdiction
when all the fixed-in-place monitor nozzles are readily accessible during a fire event.

2.3.6.2 Ceiling-Level Sprinkler System Types


2.3.6.2.1 Depending on the ambient temperature of the ASRS area being protected, ceiling-level sprinkler
systems can be:
A. Wet-pipe sprinkler systems
B. Single-interlocked preaction sprinkler systems
C. Antifreeze solution sprinkler systems consisting of a 20% to 30% propylene glycol concentration in
water
2.3.6.2.2 When installing a single-interlocked preaction sprinkler system, install the detection system used
for tripping the sprinkler system on the same spacing as the ceiling sprinklers. See Data Sheet 5-48 for other
recommendations pertaining to the pre-action sprinkler system’s detection.
2.3.6.2.3 A ceiling-level sprinkler system consisting of 20% to 30% concentration of propylene glycol in water
is acceptable for ambient temperatures between 32ºF (0ºC) and 40ºF (4ºC).
2.3.6.2.4 When installing an antifreeze sprinkler system consisting of a 20% to 30% concentration of
propylene glycol in water, the ceiling designs indicated for a wet-pipe sprinkler system can be used.
2.3.6.2.5 See Data Sheet 2-0 for additional recommendations related to the installation of all sprinkler system
types.

2.3.6.3 Ceiling-Level Sprinklers


2.3.6.3.1 For ceiling heights up to 45 ft (13.7 m), install FM Approved, Storage ceiling-level sprinklers in
accordance with the design guidelines offered in Tables 36 and 37.
2.3.6.3.2 For ceiling heights over 45 ft (13.7 m), install a flat, continuous noncombustible false ceiling over
the ASRS storage area and for a minimum of 15 ft (4.6 m) beyond it in all directions. Design the false ceiling
to be capable of withstanding a minimum uplift pressure of 3 lb/ft2 (14.4 kg/m2). Provide sprinkler protection
under this false ceiling in accordance with the height above the floor the ceiling is installed.

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


8-34 Protection for Automatic Storage
Page 100 FM Global Property Loss Prevention Data Sheets

2.3.6.3.3 When elevated mezzanines are present, provide sprinkler protection under them in accordance
with Data Sheet 2-0.

2.3.6.4 Ceiling-Level Sprinkler System Design Criteria


2.3.6.4.1 Use Table 45 to determine the ceiling-level sprinkler system designs for TL-ASRS storage
arrangements using solid-walled combustible containers having a maximum storage height of 20 ft (6.1 m).
2.3.6.4.2 Use Table 46 to determine the ceiling-level sprinkler system designs for TL-ASRS storage
arrangements using solid-walled combustible containers having a storage height that exceeds 20 ft (6.1 m).

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


Table 45. Ceiling-Level Protection Guidelines for TL-ASRS Storage Arrangements Using Open-Top Solid-Walled Unexpanded Plastic Containers; Storage Height up to and Including

FM Global Property Loss Prevention Data Sheets


Protection for Automatic Storage
20 ft (6.1 m)
Ceiling-Level Sprinkler Protection Options for Top-Loading ASRS Arrangements; No. of AS @ psi (bar)
Max. Wet System, Pendent Storage Sprinklers, 160°F (70°C) Wet System, Upright Storage Sprinklers, 160°F (70°C)
Ceiling Quick-Response Standard-Response Quick-Response Standard-Response
Height, K11.2 K14.0 K16.8 K22.4 K25.2 K25.2EC K28.0 K33.6 K11.2 K14.0 K19.6 K25.2 K11.2 K14.0 K16.8 K25.2EC K11.2 K16.8 K25.2
ft (m) (K160) (K200) (K240) (K320) (K360) (K360EC) (K400) (K480) (K160) (K200) (K280) (K360) (K160) (K200) (K240) (K360EC) (K160) (K240) (K360)
20 (6.1) 15 @ 25 9@ 50 9@ 35 9@ 20 9@ 20 7@ 19 9@ 40 9@ 55 15@ 25 15@ 16 15@ 16 15@ 7 15@ 25 10@ 50 10@ 35 7@ 19 15 @ 25 15@ 11 15 @ 7
(1.7) (3.5) (2.4) (1.4) (1.4) (1.3) (2.8) (3.8) (1.7) (1.1) (1.1) (0.5) (1.7) (3.5) (2.4) (1.3) (1.7) (0.8) (0.5)
25 (7.6) 15 @ 50 9@ 50 9@ 35 9@ 20 9@ 20 7@ 38 9@ 40 9@ 55 15@ 50 15@ 32 15@ 16 15@ 10 15@ 50 10@ 50 10@ 35 7@ 38 15 @ 50 15@ 22 15 @ 10
(3.5) (3.5) (2.4) (1.4) (1.4) (2.6) (2.8) (3.8) (3.5) (2.2) (1.1) (0.7) (3.5) (3.5) (2.4) (2.6) (3.5) (1.5) (0.7)
©2017-2023 Factory Mutual Insurance Company. All rights reserved.

30 (9.1) 20 @ 50 9@ 50 9@ 35 9@ 20 9@ 20 10@ 38 9@ 40 9@ 55 20@ 50 20@ 32 20@ 16 20@ 10 20@ 50 10@ 50 10@ 35 10@ 38 20 @ 50 20@ 22 20 @ 10
(3.5) (3.5) (2.4) (1.4) (1.4) (2.6) (2.8) (3.8) (3.5) (2.2) (1.1) (0.7) (3.5) (3.5) (2.4) (2.6) (3.5) (1.5) (0.7)
35 9 @ 75 9@ 52 9@ 29 9@ 23 9@ 40 9@ 55
(10.7) (5.2) (3.6) (2.0) (1.6) (2.8) (3.8)
40 9 @ 75 9@ 52 9@ 29 9@ 23 9@ 40 9@ 55
(12.2) (5.2) (3.6) (2.0) (1.6) (2.8) (3.8)
45 9 @ 75 9@ 60 9@ 50 9@ 55
(13.7) (5.2) (4.1) (3.5) (3.8)

Page 101
8-34
Table 46. Ceiling-Level Protection Guidelines for TL-ASRS Storage Arrangements Using Open-Top Solid-Walled Unexpanded Plastic Containers; Storage Height in Excess of 20 ft

Page 102
8-34
(6.1 m)
Ceiling-Level Sprinkler Protection Options for Top-Loading ASRS Arrangements; No. of AS @ psi (bar)
Max. Wet System, Pendent Storage Sprinklers, 160°F (70°C) Wet System, Upright Storage Sprinklers, 160°F (70°C)
Ceiling Quick-Response Standard-Response Quick-Response Standard-Response
Height, K11.2 K14.0 K16.8 K22.4 K25.2 K25.2EC K28.0 K33.6 K11.2 K14.0 K19.6 K25.2 K11.2 K14.0 K16.8 K25.2EC K11.2 K16.8 K25.2
ft (m) (K160) (K200) (K240) (K320) (K360) (K360EC) (K400) (K480) (K160) (K200) (K280) (K360) (K160) (K200) (K240) (K360EC) (K160) (K240) (K360)
25 (7.6) 15 @ 50 10@ 50 10@ 35 10@ 20 10@ 20 7 @ 38 10 @ 40 10 @ 55 15@ 50 15@ 32 15@ 16 15@ 10 15@ 50 12@ 50 12@ 35 7 @ 38 15 @ 50 15@ 22 15 @ 10
(3.5) (3.5) (2.4) (1.4) (1.4) (2.6) (2.8) (3.8) (3.5) (2.2) (1.1) (0.7) (3.5) (3.5) (2.4) (2.6) (3.5) (1.5) (0.7)
30 (9.1) 20 @ 50 12@ 50 12@ 35 12@ 20 12@ 20 10@ 38 12@ 40 12@ 55 20@ 50 20@ 32 20@ 16 20@ 10 20@ 50 12@ 50 12@ 35 10@ 38 20@ 50 20@ 22 20 @ 10
(3.5) (3.5) (2.4) (1.4) (1.4) (2.6) (2.8) (3.8) (3.5) (2.2) (1.1) (0.7) (3.5) (3.5) (2.4) (2.6) (3.5) (1.5) (0.7)
©2017-2023 Factory Mutual Insurance Company. All rights reserved.

35 12 @ 29 12@ 23 12@ 40 12@ 55


(10.7) (2.0) (1.6) (2.8) (3.8)
40 12 @ 29 12@ 23 12@ 40 12@ 55
(12.2) (2.0) (1.6) (2.8) (3.8)
45 12 @ 75 12@ 60 12@ 50 12@ 55
(13.7) (5.2) (4.1) (3.5) (3.8)

Protection for Automatic Storage


FM Global Property Loss Prevention Data Sheets
Protection for Automatic Storage 8-34
FM Global Property Loss Prevention Data Sheets Page 103

2.3.6.4.3 Hose Demand Design Guidelines


A. Include a minimum flow of 500 gpm (1,900 L/min) for the hose demand design.
B. When both fixed-in-place monitor nozzles are provided in accordance with Section 2.3.6.1.8 and small
hose connection stations are provided in accordance with Section 2.3.6.1.6, account for the 500 gpm (1,900
L/min) hose demand design as follows:
1. Include a flow of 200 gpm (760 L/min) from each of the two most remote monitor nozzles (400 gpm
[1,520 L/min] total) as part of the hose demand design, and
2. Include a flow of 50 gpm (190 L/min) from each of the two most remote small hose connection stations
C. When only fixed-in-place monitor nozzles are provided in accordance with Section 2.3.6.1.8, account for
a flow of 200 gpm (760 L/min) from each of the two most remote monitor nozzles (400 gpm [1,520 L/min]
total) as part of the hose demand design. Account for the remaining 100 gpm (380 L/min) hose demand by
adding it to the overall ceiling sprinkler system demand at the point of its connection to the water supply.
D. When only small hose connection stations are provided in accordance with Section 2.3.6.1.6, account for
a flow of 50 gpm (190 L/min) from each of the two most remote small hose connection stations. Account
for the remaining 400 gpm (1,520 L/min) hose stream allowance by adding it to the overall ceiling sprinkler
system demand at the point of its connection to the water supply.
2.3.6.4.4 Water Supply Duration
Size the water supply feeding the ceiling sprinkler system, the monitor nozzles, and the hose stream demand
(inside and outside), when taken from the same water supply, for the following durations:
A. A minimum of 2 hours for ceiling heights less than or equal to 25 ft (7.6 m), or
B. A minimum of 4 hours for ceiling heights over 25 ft (7.6 m)

2.3.7 Protection of Non-Solid-Walled Containers

2.3.7.1 Storage Arrangement


2.3.7.1.1 Create individual storage subdivisions within the ASRS storage array whose storage footprints are
defined entirely or by a combination of any of the following:
A. A minimum 4 ft (1.2 m) wide void space, or
B. A wall that defines the extent of the ASRS storage array, or
C. An adjacent area where containers can be stored only one high and on the same plane that represents
the maximum storage height within the storage array.
See Figure 52 for a visual representation of these arrangements.
2.3.7.1.2 Determine the size of the storage subdivisions based on the number of operating sprinklers the
water supply can support. See Section 2.3.7.4 for more information on the sprinkler system design.
2.3.7.1.3 Arrange the void spaces between storage subdivisions so ceiling sprinklers are aligned, as close
as possible, over the center of them as shown in Figure 53.
2.3.7.1.4 Limit the storage within each subdivision to a maximum height of 25 ft (7.6 m).

2.3.7.2 Ceiling-Level Sprinkler System Types


2.3.7.2.1 Depending on the ambient temperature of the ASRS area being protected, ceiling-level sprinkler
systems can be one of the following:
A. Wet-pipe sprinkler system
B. Antifreeze solution sprinkler system consisting of a 20% to 30% propylene glycol concentration in water
2.3.7.2.2 A ceiling-level sprinkler system consisting of 20% to 30% concentration of propylene glycol in water
is acceptable for ambient temperatures between 32ºF (0ºC) and 40ºF (4ºC).

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


8-34 Protection for Automatic Storage
Page 104 FM Global Property Loss Prevention Data Sheets

Wall

Subdivided Subdivided
Storage Area Storage Area

Wall
One Container
Min. 4 ft (1.2 m)
High Storage Area Wide Void Space

Top-Loading ASRS Grid Area

Fig. 52. Establishing storage subdivisions within TL-ASRS

Min. 4 ft (1.2 m)
Wide Void Space

Subdivided
Storage Area

Ceiling Sprinklers
Centered Over Void Spaces

Fig. 53. Positioning of void spaces under ceiling sprinklers

2.3.7.2.3 When installing an antifreeze sprinkler system consisting of a 20% to 30% concentration of
propylene glycol in water, the ceiling designs indicated for a wet-pipe sprinkler system can be used.
2.3.7.2.4 See Data Sheet 2-0 for additional recommendations related to the installation of these type sprinkler
systems.

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


Protection for Automatic Storage 8-34
FM Global Property Loss Prevention Data Sheets Page 105

2.3.7.3 Ceiling-Level Sprinklers


2.3.7.3.1 For ceiling heights up to 40 ft (12.2 m), install FM Approved, quick-response, minimum K14.0 (K200)
pendent Storage ceiling-level sprinklers.
2.3.7.3.2 For ceiling heights over 40 ft (12.2 m) and up to 45 ft (13.7 m), install FM Approved, quick-response,
minimum K22.4 (K360) pendent Storage ceiling-level sprinklers.
2.3.7.3.3 For ceiling heights over 45 ft (13.7 m), install a flat, continuous noncombustible false ceiling over
the ASRS storage area and for a minimum of 15 ft (4.6 m) beyond it in all directions. Design the false ceiling
to be capable of withstanding a minimum uplift pressure of 3 lb/ft2 (14.4 kg/m2). Provide sprinkler protection
under this false ceiling in accordance with the height above the floor the ceiling is installed.
2.3.7.3.4 When elevated mezzanines are present, provide sprinkler protection under them in accordance
with Data Sheet 2-0.

2.3.7.4 Ceiling-Level Sprinkler System Design Criteria


2.3.7.4.1 For ceiling heights up to and including 45 ft (13.7 m), provide a minimum flow of 120 gpm (455
L/min) from the most hydraulically remote operating sprinkler over the storage subdivision.
2.3.7.4.2 Size the ceiling sprinkler demand area as follows:
A. For ceiling heights up to and including 40 ft (12.2 m), the demand area includes the sprinklers located
directly over and within 4 ft (1.2 m) horizontally of each subdivided storage area.
B. For ceiling heights over 40 ft (12.2 m) and up to and including 45 ft (13.7 m), the demand area includes
5 more sprinklers than the sprinklers located directly over and within 4 ft (1.2 m) horizontally of each
subdivided storage area.
2.3.7.4.3 When determining the ceiling sprinkler demand area in accordance with Section 2.3.7.4.2, sprinklers
on the opposite side of a full height wall, or on the opposite side of a minimum 2 ft (0.6 m) deep draft curtain
that is installed at the perimeter of the ASRS storage area, do not have to be accounted for in the ceiling
sprinkler design.

2.3.7.5 Hose Demand Design Guidelines


2.3.7.5.1 Include a minimum flow of 500 gpm (1,900 L/min) for the hose demand design.
2.3.7.5.2 When small hose connection stations are provided in accordance with Section 2.3.7.6.2, account
for a flow of 50 gpm (190 L/min) from each of the two most remote small hose connection stations. Account
for the remaining 400 gpm (1,515 L/min) hose stream allowance by adding it to the overall ceiling sprinkler
system demand at the point of its connection to the water supply.

2.3.7.6 Water Supply Duration


Size the water supply feeding the ceiling sprinkler system and the hose stream demand (inside and outside),
when taken from the same water supply, for a minimum 4-hour duration.

2.3.7.7 Final Extinguishment


Due to the lack of direct access by the local fire services to the fire area, recommendations in this section
are intended to establish a means by which final extinguishment can be achieved.

2.3.7.7.1 Storage Arrangement and Mezzanines


A. To allow the fire service to access the top of the storage grid where hose streams can be applied, arrange
the TL-ASRS storage as follows:
1. Limit the horizontal distance between one end of the storage array and the opposite end to a maximum
of 100 ft (30 m) as shown in Figure 54.
2. Install perimeter mezzanines, at a minimum, along the longer walls of the ASRS unit at a height equal
to or above the storage grid as shown in Figure 54. Determine from the local authority having jurisdiction
the minimum width of the mezzanine they would require and the minimum number of access points
for each perimeter mezzanine area.

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


8-34 Protection for Automatic Storage
Page 106 FM Global Property Loss Prevention Data Sheets

3. Establish readily accessible, clearly marked designated locations along the side walls of the ASRS
unit that can be used as access points to the storage area. Provide as many access points as possible
to limit the horizontal distance between the access point and the potential fire area within the storage
area. See Figure 54 for an example of this arrangement.

Perimeter Mezzanine Level

Top-Loading ASRS Grid Area < 100 ft


(30 m)

Perimeter Mezzanine Level

Egress to
Mezzanine Level

Fig. 54. Example of a TL-ASRS arrangement showing maximum 100 ft (30 m) depth in one direction

B. If the horizontal distances between the ends of the storage array will exceed 100 ft (30 m) in both directions,
install solid-floored elevated mezzanine levels that will limit the horizontal distances between mezzanines
to 100 ft (30 m) and the maximum horizontal distances for hose stream application to 50 ft (15 m). Arrange
the elevated mezzanines to allow robots the ability to pass underneath them. See Figure 55 for an example
of this arrangement.
C. The installation of elevated mezzanines, as outlined in Section 2.3.7.7.1(B), can be avoided at the written
discretion of the local authority having jurisdiction.

2.3.7.7.2 Small Hose Connection Stations


A. To aid in manual fire fighting efforts and after-extinguishment mop-up operations, install small hose
connection stations near the floor-level access points established for the local fire service and on the
mezzanine levels (perimeter and elevated). Consult with the local fire service or authority having jurisdiction
to determine their recommendations regarding the following:
1. The use of wet- or dry-barrel stations, and
2. The size of the hose connections, and
3. The horizontal distance between stations.
B. Design the small hose connection station system to provide a minimum flow of 50 gpm (190 L/min) from
each of the two most hydraulically remote stations (100 gpm [380 L/min] total).
C. Arrange the water supplies feeding these stations in one of the following ways:

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


Protection for Automatic Storage 8-34
FM Global Property Loss Prevention Data Sheets Page 107

Perimeter Mezzanine Level

Elevated Mezzanine Level

Elevated Mezzanine Level


Top-Loading Top-Loading
ASRS Grid Area ASRS Grid Area > 100 ft
(30 m)

< 100 ft (30 m)

Perimeter Mezzanine Level

Egress to
Mezzanine Level
Fig. 55. Example of solid-floored elevated mezzanine levels when span of TL-ASRS exceeds 100 ft (30 m) in each direction

1. A piping system dedicated solely for the small hose connection stations, or
2. Piping that connects the stations to a sprinkler system that is different than the one protecting the ASRS
storage area.
D. The installation of small hose connection stations can be avoided at the documented discretion of the
local authority having jurisdiction.

2.3.7.7.3 Pre-Incident Plan


For TL-ASRS storage arrangements that use non-solid-walled containers, establish a pre-incident plan with
the local fire service that takes into consideration how the local fire service will gain access to any point of
the ASRS storage grid for final extinguishment purposes. Items to consider, at a minimum, are:
A. Access to the storage grid itself (i.e., removal of any separating walls or fences),
B. A plan to remove storage containers along with a place to put them, and
C. A means of preventing robots from falling from the grid into the storage area.
See Section 2.1.5 for additional guidance on pre-incident planning.

2.4 Vertically Enclosed Automatic Storage and Retrieval System Storage Arrangements

2.4.1 General
2.4.1.1 Section 2.4 provides protection guidelines for vertically enclosed automatic storage and retrieval
systems (ASRS) storage arrangements. See Figure 56 for an example of this type of storage arrangement.
2.4.1.2 The protection options in this section for a vertically enclosed ASRS storage unit focus solely on the
protection provided within the unit itself. See the applicable FM Global Data Sheet for the surrounding
occupancy hazard to determine recommendations pertaining to the construction, occupancy, and protection
of the area in which the vertically enclosed ASRS storage unit is located.

2.4.2 Storage Trays for Vertically Enclosed Storage Units


2.4.2.1 To help reduce the fire load within a vertically enclosed ASRS storage unit, use trays that are
noncombustible.

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


8-34 Protection for Automatic Storage
Page 108 FM Global Property Loss Prevention Data Sheets

Fig. 56. Example of a vertically enclosed ASRS storage unit

2.4.2.2 To aid in water penetration throughout the vertical height of the vertically enclosed ASRS unit, consider
the use of either trays with gridded bottoms, or trays that are provided with a minimum 10% venting area
uniformly around the sides of the trays a maximum 1 in. (25 mm) above the bottom of the tray.

2.4.3 Protection Options for Vertically Enclosed Storage Units

2.4.3.1 General
2.4.3.1.1 Arrange the vertically enclosed ASRS storage unit for automatic shutdown upon fire/smoke detection
or sprinkler activation.
2.4.3.1.2 If the materials being maintained within the vertically enclosed ASRS storage unit are (a) of high
value, and/or (b) could result in a major interruption to business if damaged, consider the installation of an FM
Approved total flooding gaseous suppression system in accordance with the applicable FM Global 4-Series
Data Sheet to supplement the sprinkler protection recommended in Section 2.4.3.3.

2.4.3.2 Sprinkler System Types


2.4.3.2.1 Depending on the ambient temperature of the area being protected, the sprinkler system protecting
the vertically enclosed ASRS storage unit can be wet-pipe, dry-pipe, preaction, a maximum 30% propylene
glycol antifreeze solution, or a deluge sprinkler system.
2.4.3.2.2 When installing a dry-pipe or similar ceiling-level sprinkler system, the maximum water delivery
time is 40 seconds based on a maximum operation of the most remote 4 sprinklers.
2.4.3.2.3 See Data Sheet 2-0 for additional recommendations related to the installation of the sprinkler system.

2.4.3.3 Protection of Vertically Enclosed ASRS Units

2.4.3.3.1 Vertically Enclosed ASRS Storage Units up to 25 ft (7.6 m) Tall


A. Provide sprinkler protection at the top of a closed-top ASRS unit using minimum K11.2 (K160) Storage
sprinklers on maximum 8 ft (2.4 m) linear spacing and maximum 64 ft2 (6.0 m2) area spacing.
B. If the top of the ASRS unit is open to the surrounding area, reduce the sprinkler spacing to a maximum
4 ft (1.2 m) linear spacing and a maximum 16 ft2 (1.5 m2) area spacing.

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


Protection for Automatic Storage 8-34
FM Global Property Loss Prevention Data Sheets Page 109

C. Design the sprinkler system to account for all sprinklers within the vertically enclosed ASRS storage unit
operating at a minimum flow of 30 gpm (115 L/min) from the most remote sprinkler.

2.4.3.3.2 Vertically Enclosed ASRS Storage Units Over 25 ft (7.6 m) Tall


A. Protection with Sprinklers at the Top of the ASRS Unit Only
1. For closed-top vertically enclosed ASRS units over 25 ft (7.6 m) and up to a maximum height of 55 ft
(16.8 m) tall protected by sprinklers only at the top of the ASRS unit, install quick-response, standard-
coverage, 160°F (70°C) nominally rated, minimum K14.0 (K200) pendent Storage sprinklers on
maximum 8 ft (2.4 m) linear spacing and maximum 64 ft2 (6.0 m2) area spacing.
2. For open-top vertically enclosed ASRS units over 25 ft (7.6 m) and up to a maximum height of 55 ft
(16.8 m) tall protected by sprinklers only at the top of the ASRS unit, install quick-response, standard-
coverage, 160°F (70°C) nominally rated, minimum K14.0 (K200) pendent Storage sprinklers on
maximum 4 ft (1.2 m) linear spacing and maximum 16 ft2 (1.5 m2) area spacing.
3. Design the sprinkler system accounting for all sprinklers within the vertically enclosed ASRS unit
operating at the minimum design pressure indicated in Table 47.

Table 47. Sprinkler Pressure Requirements for the Protection of Vertically Enclosed ASRS Storage Units Over 25 ft (7.6
m) and up to 55 ft (16.8 m) Tall
Maximum
Ceiling Height
of Vertically Wet System, Quick Response, 160°F (70°C), Pendent Storage Sprinklers; Pressure, psi (bar)
Enclosed K14.0 (K200) K16.8 (K240) K22.4 (K320) K25.2 (K360) K28.0 (K400) K33.6 (K480)
ASRS Unit, ft
(m)
30 (9.1) 50 (3.4) 35 (2.4) 20 (1.4) 20 (1.4) 40 (2.8) 55 (3.8)
35 (10.7) 75 (5.2) 52 (3.6) 30 (2.1) 30 (2.1) 40 (2.8) 55 (3.8)
40 (12.2) 75 (5.2) 52 (3.6) 40 (2.8) 40 (2.8) 40 (2.8) 55 (3.8)
45 (13.7) 50 (3.4) 50 (3.4) 40 (2.8) 55 (3.8)
50 (15.2) 63 (4.3) 50 (3.4) 40 (2.8) 55 (3.8)
55 (16.8) 80 (5.5) 55 (3.8)

B. Protection with Ceiling- and Intermediate-Level Sprinklers


1. For closed-top vertically enclosed ASRS units over 25 ft (7.6 m) and up to a maximum height of 55 ft
(16.8 m) tall protected by both ceiling- and intermediate-level sprinklers, provide sprinkler protection within
the ASRS unit as follows:
a. Install sprinklers at the top of the ASRS unit using minimum K11.2 (K160) Storage sprinklers on
maximum 8 ft (2.4 m) linear spacing and maximum 64 ft2 (6.0 m2) area spacing, and
b. Install intermediate levels of quick response, 160°F (70°C) nominally rated, minimum K8.0 (K115)
Nonstorage sidewall or extended-coverage sidewall sprinklers installed at both ends of the ASRS unit.
Locate the intermediate levels of sprinklers on a maximum vertical spacing of 10 ft (3.0 m) while leaving
no more than 15 ft (4.6 m) of storage above the top level of intermediate sprinklers.
c. Design the sprinkler system to account for all sprinklers (ceiling and intermediate) within the vertically
enclosed ASRS storage unit operating at a minimum flow of 30 gpm (115 L/min) from the most remote
sprinkler.
2. If the top of the ASRS unit is open to the surrounding area, reduce the sprinkler spacing indicated in Section
2.4.3.3.2(B)(1)(a) to a maximum 4 ft (1.2 m) linear spacing and a maximum 16 ft2 (1.5 m2) area spacing.

2.4.3.4 Hose Demand and System Duration

2.4.3.4.1 Hose Demand Design


As part of the overall sprinkler system design, include a hose demand allowance of 250 gpm (950 L/min)
for manual intervention.

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


8-34 Protection for Automatic Storage
Page 110 FM Global Property Loss Prevention Data Sheets

2.4.3.4.2 System Duration


Size the water supply for the sprinkler system and the hose demand design, when taken from the same
water supply source, for a minimum duration of 60 minutes.

2.4.4 Final Extinguishment – Small Hose Connection Stations


2.4.4.1 To aid in manual fire fighting efforts and after-extinguishment mop-up operations, install small hose
connection stations near the vertically enclosed ASRS unit. Consult with the local fire service or authority
having jurisdiction to determine their recommendations regarding:
1. The use of wet- or dry-barrel stations,
2. The size of the hose connections, and
3. The horizontal distance between stations
2.4.4.2 Design the small hose connection stations system to provide a minimum flow of 50 gpm (190 L/min)
from each of the two most hydraulically remote stations (100 gpm [380 L/min] total).
2.4.4.3 Arrange the water supplies feeding these stations in one of the following ways:
A. A piping system dedicated solely for the small hose connection stations, or
B. Piping that connects the stations to a sprinkler system that is different than the one protecting the
vertically enclosed ASRS storage unit
2.4.4.4 The installation of small hose connection stations can be avoided at the documented discretion of
the local authority having jurisdiction.

3.0 SUPPORT FOR RECOMMENDATIONS

3.1 Description of Automatic Storage and Retrieval Systems (ASRS)

3.1.1 Mini-Load ASRS Storage Arrangements


Mini-load ASRS typically consist of multiple levels of trays or containers that slide into a rack structure that
use angle irons for material handling support (see Figure 57). The rack structure generally consists of rack
uprights that are somewhat smaller, such as 2 in. (50 mm) wide by 3 in. (75 mm) deep (see Figure 58),
compared to traditional pallet-load type rack uprights. The rack uprights tend to be on the order of 18 in.
(450 mm) to 24 in. (600 mm) horizontally apart parallel to the loading aisle. Tier heights will vary but are usually
from 9 in. (225 mm) to 16 in. (400 mm) in height. While some systems can be small, others are used as
rack-supported structures where they act as the structural support for the building they are in (see Figure
59) and thus can be very tall.
Trays or containers used for product handling are removed from the rack by a motorized automated picking
robot (see Figure 60). Trays and containers are typically constructed of unexpanded plastic; however, some
containers are constructed of noncombustible, cellulosic, or expanded plastic materials. Containers are
usually open-top. The picking robot, located in the aisle on a set of rails, is typically operated via a computer
terminal. The robot can move in three directions: back and forth in the aisle, up and down the height of the
rack, and in and out of the rack when removing or returning a container to its location. Depending on the
size of the system, more than one robot may be used. Aisles are usually a minimum of about 3 ft (0.9 m) wide.
There are various types of containers in which parts may be stored within the retrieval system. For purposes
of providing protection guidelines they have been divided into the following three groups: noncombustible
containers, cellulosic containers, and plastic containers.

3.1.1.1 Noncombustible Containers


These containers are typically painted or galvanized sheet metal. When product is maintained in closed-top,
solid-walled containers, the fire hazard is greatly reduced due to the shielding of the product from direct flame
impingement and therefore in-rack sprinkler protection is not typically required. When the containers are
open-top and have solid walls, the fire growth is typically very slow, and the solid walls help reduce the
likelihood of horizontal fire spread. However, if the container walls or bottoms are non-solid, then heat transfer
is more readily achieved and the protection needed is driven by the product inside the container.

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


Protection for Automatic Storage 8-34
FM Global Property Loss Prevention Data Sheets Page 111

Fig. 57. Example of open-top plastic containers in mini-load ASRS storage arrangementi

3.1.1.2 Cellulosic Containers


These containers are typically single-walled or double-walled thick cardboard. They can be closed-top or
open-top. While the heat release rate of cellulosic containers is less than those made of plastic, they tend
to ignite easier and burn faster than containers constructed from unexpanded plastics. As a result, care is
needed to make sure the horizontal in-rack sprinkler arrangement recommended for them is appropriate
to avoid the fire from growing vertically past the in-rack sprinklers when installed on a wet sprinkler system.
While some cellulosic containers may have venting along the bottom sides of the container perpendicular
to the loading aisle, most containers either have no vents or vents in the bottom of the container, which would
reduce the amount of sprinkler discharge realized in the transverse flue spaces.

3.1.1.3 Unexpanded Plastic Containers


These containers are typically constructed using injection molded plastic; however, containers are sometimes
made of expanded or corrugated plastic. Expanded plastic containers are currently outside the scope of the
data sheet. They are very often open-top but can be closed-top. Care must be taken in classifying closed-top
containers because most of these containers use folding tops that do not seal completely, which allows water
that collects on top of them to drain into the container, thus creating an open-top container hazard.
Unexpanded plastic containers are typically either solid throughout or collapsible where the hinge is located
near the bottom of container. This hinge does allow for water to vent from the container in a timely fashion
provided that the hinge is located close enough to the bottom of the container and the product inside the
container will not block the water from escaping.

3.1.2 Top-Loading ASRS Storage Arrangements

3.1.2.1 General
A top-loading ASRS (TL-ASRS) storage arrangement consists of an open metal grid structure that is
supported by metal columns located at the corner of each of the grid openings. Under each grid opening is
a solid-piled column of storage containers that are vertically aligned due to the angle irons provided on the
metal support columns. The containers used in TL-ASRS storage arrangements are almost always open-top
and made from various plastics, such as polyethylene (HDPE) or polypropylene. The top of the grid acts
as a track across which remotely operated robots transverse; the robots are used to either remove containers

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


8-34 Protection for Automatic Storage
Page 112 FM Global Property Loss Prevention Data Sheets

Fig. 58. Example of an empty mini-load ASRS storage arrangement where rack uprights are about 2 to 3 in. (50 to 75
mm) wide and about 2 ft (0.6 m) horizontally apart

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


Protection for Automatic Storage 8-34
FM Global Property Loss Prevention Data Sheets Page 113

Fig. 59. Example of rack-supported ASRS storage arrangement

Fig. 60. Example of motorized automated picking robot in a mini-load ASRS storage arrangement with open-top
unexpanded plastic containers

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


8-34 Protection for Automatic Storage
Page 114 FM Global Property Loss Prevention Data Sheets

from the storage grid for picking operations, or are used to return containers to their designated storage
location. The track that the robots operate on is about the same width as the flue spaces surrounding each
container.

3.1.2.2 Robot Charging Systems


Robot chargers are connected to AC or DC supply networks. Multiple chargers exist at various locations
around the grid, requiring extensive runs of cables around the grid. The chargers condition the power
(rectification/step down) to a level that is acceptable for the robot. The robots’ batteries may be fixed to chassis
or removable for charging. In designs with fixed batteries, the robot is stationary at the charging station while
the batteries are being charged. In the case of removable batteries, robots deposit the batteries at the
charging station for charging and acquire a fully charged battery at another station to continue operation.
The robot may be powered by an ultra-capacitor during this transition. This leads to a system with higher
uptimes and overall productivity per robot.

3.1.2.3 Batteries
In general, the batteries in use are one of two types: lead-acid or lithium-ion with the latter gaining more
popularity in recent times. For designs with Li-ion batteries, charging rates could be substantially higher than
for the lead acid counterparts. This can put additional stress on the current carrying parts of the battery pack
and charger in addition to the batteries themselves, which tend to heat at higher current levels. A Battery
Management System (BMS) is provided for the safe operation of the Li-ion battery pack.
Batteries use different chemistries. As indicated above, the chemistries typically observed in top-loading ASRS
robots are lead-acid and lithium-ion batteries. Lead-acid batteries are typically of the sealed type. Li-ion
batteries consist of several Li-ion cells (cylindrical or prismatic) connected in series/parallel combination to
meet the voltage, power, and capacity requirements of the application. The battery pack also consist of the
BMS and instrumentation to continuously monitor the battery state of charge, state of health. The BMS also
provides safety operation limits on charge/discharge voltage and currents. The chargers for these Li-ion
batteries follow specific charging profiles depending on the Li-ion chemistry used in the cells.

3.1.3 Vertically Enclosed ASRS Storage Arrangements


Vertically enclosed systems can vary in size but are usually of the “lift” or the “carousel” type. The lift type
uses a robotic picker to store and remove trays that rest on fixed storage supports within the unit and deliver
it to the user, whereas the conveyor type uses a rotating storage arrangement that brings the storage tray
to the user. Typical systems are package units in which metal trays supported on a rack structure are
contained within a metal enclosure.
Systems are often used for storage of parts that are high in value and very prone to heat, smoke, or water
damage, or parts that are low in value but critical for production. Such situations warrant the installation of
supplemental protection to help further reduce loss potentials.

3.2 Loss History of Automatic Storage and Retrieval Systems (ASRS)


Loss experience shows that when there are no major automatic sprinkler system deficiencies, fires in storage
occupancies are controlled by the existing sprinkler system protection arrangement. Major protection
deficiencies include inadequate water supplies, closed or partially closed valves, obstructed sprinkler piping,
missing sprinklers, and ignitable liquid or aerosol protection deficiencies. Protection deficiencies were
identified in all storage losses in which the fire was uncontrolled.
As of 2017, FM Global clients have experienced very few losses involving automatic storage and retrieval
systems (ASRS), but a significant loss involving a rack-supported ASRS took place at a non-client location
on July 13, 2002. Reportedly due to deficient welding and design aspects of the rack framing, a portion of
a rack-structure ASRS storage unit collapsed starting a domino effect with the remaining rack framing in the
warehouse area. Storage in the racking consisted of paper goods, which were then ignited by the building’s
lighting system. The building, which was reportedly 10 stories high and 115,000 ft2 (10,685 m2) in size, was
completely lost.

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


Protection for Automatic Storage 8-34
FM Global Property Loss Prevention Data Sheets Page 115

4.0 REFERENCES

4.1 FM Global
Data Sheet 1-2, Earthquakes
Data Sheet 1-10, Smoke and Heat Venting in One-story Sprinklered Buildings
Data Sheet 2-0, Installation Guidelines for Automatic Sprinklers
Data Sheet 2-1, Corrosion in Automatic Sprinkler Systems
Data Sheet 2-8, Earthquake Protection for Water-Based Fire Protection Systems
Data Sheet 3-0, Hydraulics of Fire Protection Systems
Data Sheet 5-48, Automatic Fire Detection
Data Sheet 7-43, Process Safety
Data Sheet 7-110, Industrial Control Systems
Data Sheet 8-1, Commodity Classification
Data Sheet 8-9, Storage of Class 1, 2, 3, 4 and Plastic Commodities
Data Sheet 10-1, Pre-Incident Planning
Data Sheet 10-8, Operators

4.2 Other
International Electrotechnical Commission (IEC). IEC 60950-1, Information Technology Equipment - Safety
- Part 1: General Requirements.
International Electrotechnical Commission (IEC). IEC 62619, Secondary Cells and Batteries Containing
Alkaline or Other Non-acid Electrolytes - Safety Requirements for Secondary Lithium Cells and Batteries,
for Use in Industrial Applications.

APPENDIX A GLOSSARY OF TERMS


ASRS rack row depth: The horizontal length of storage within a mini-load ASRS storage arrangement,
measured perpendicular to the loading aisle, between (1) the face of the rack, and (2) either the longitudinal
flue space or the back face of the rack when a longitudinal flue space is not provided. See Figure A-1 for
a visual representation of this term.

Fig. A-1. ASRS rack row depth

Automatic Storage and Retrieval System (ASRS): A storage system in which an automated picker (or
robot) retrieves an otherwise stationary shelf, tray or container and brings it to a delivery platform or operator.
Carousel Storage and Retrieval System: A rotating storage system that uses vertically or horizontally
rotating carriers on tracks or chains to move the entire array of stored items, where a summoned shelf or
container stops at a designated access point for the storage or retrieval of goods. See Data Sheet 8-33,
Carousel Storage and Retrieval Systems, for protection guidelines involving these types of storage
arrangements.

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


8-34 Protection for Automatic Storage
Page 116 FM Global Property Loss Prevention Data Sheets

Closed-top container: A container equipped with a solid cover that will prevent water from entering the top.
The cover can be an integral part of container, such as a corrugated cardboard box with folding flaps that
are then sealed closed (typically with glue or packing tape). It can also be a fixed-in-place lid. If a fixed-in-place
lid is used, it needs to be expected to stay in place during a fire event and not allow water to enter the top
of the container.
Fixed-in-place monitor nozzle: A non-portable monitor nozzle that is attached directly to either a floor or
a ceiling structure. The nozzle itself, however, can be moved as needed to direct water discharge to the fire
area.
Horizontal-loading ASRS storage arrangement: An automatic storage and retrieval system where material
handling is conducted in a horizontal plane, similar to standard storage racks, but with robots that load and
unload small containers or trays. There are two types of horizontal-loading ASRS storage arrangements
currently addressed in this standard, which are mini-load and shuttle type ASRS arrangements.
K-factor: Also known as the discharge coefficient, it is a numerical value representing the orifice size of the
sprinkler in combination with the expected flow through the sprinkler orifice at a given pressure value. It is
used to calculate the flow from a sprinkler by taking the square root of the pressure available at the sprinkler
multiplied by the sprinkler’s K-factor. The units for the K-factor are gpm/psi0.5 (Lpm/bar0.5).
Local fire service: The responding personnel, paid or volunteer, whose assigned task would be to provide
final extinguishment of a fire that originates within an ASRS storage array.
Longitudinal flue space: A flue space that is parallel to the loading aisle having a minimum width of 3 in.
(75 mm) and a maximum width of 24 in. (600 mm). Note that any flue space that is parallel to the loading aisle
having a minimum width over 24 in. (600 mm) as an aisle for in-rack sprinkler location purposes.
Mini-load ASRS storage arrangement: An automatic storage and retrieval system that uses trays or small
totes/containers for material handling as opposed to traditional pallet loads. They are differentiated from other
storage racks due to the presence of angle irons, which result in the diversion of sprinkler discharge toward
the face of the rack and away from both the longitudinal and transverse flue spaces. Mini-load ASRS rack
structures typically use rack uprights that are about 18 to 24 in. (450 to 600 mm) horizontally apart and are
about 2 to 3 in. (50 to 75 mm) in size (both width and depth). Tier heights are roughly 1 ft (0.3 m) and product
handling is typically supported on angle irons (see Figure 3).
Modular in-rack sprinkler protection arrangement: An in-rack sprinkler protection arrangement that is
designed to prevent the vertical spread of fire beyond the first level of in-rack sprinklers that the fire
encounters. This in-rack sprinkler arrangement therefore allows the in-rack design to be based on the
operation of a given number of sprinklers at only one level and does not need to account for ceiling sprinkler
operation as part of its design.
Monitor nozzle: A nozzle used for water discharge to a fire area that can turn 360º in a horizontal plane
while also having a limited play in a vertical plane.
Non-solid-walled container (top-loading ASRS): A container that has openings on any of its side walls.
The protection requirements for these types of containers differ from those for solid-walled containers when
maintained in a TL-ASRS storage arrangement.
Open-top container: A container with walls higher than 1 in. (25 mm) that either does not have a top cover
or is not equipped with a cover capable of preventing water from entering the container. Note that this includes
open-top containers filled with product to any height within the container.
Rack structure ASRS storage arrangement: An automatic storage and retrieval system that is similar to
traditional open-frame storage racks except that (1) the horizontal distance between rack uprights is sized for
only one pallet load, and (2) the support within the rack for the pallet loads tends to be either roller-type
conveyors or horizontal supports that are oriented perpendicular to the loading aisle as opposed to parallel
to it. Protection guidelines for these storage arrangements are provided in Data Sheet 8-9, Storage of Class
1, 2, 3, 4 and Plastic Commodities.
Shuttle-type ASRS storage arrangement: An automatic storage and retrieval system that uses trays or
small totes/containers (as opposed to traditional pallet loads) for material handling. What differentiates these
ASRS storage arrangements from mini-load ASRS storage arrangements is the storage racks typically use
slatted shelving (that are void of vertical alignment guides) on which the materials, trays, or containers rest.
As a result, the rack structure does not inherently divert water away from the flue spaces that surround the

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


Protection for Automatic Storage 8-34
FM Global Property Loss Prevention Data Sheets Page 117

stored product, provided the slats do not result in a blocked transverse flue space. Shuttle-type ASRS rack
structures typically use rack uprights that are about 8 to 10 ft (2.4 to 3.0 m) horizontally apart and are about
3 in. (75 mm) in width. Tier heights are roughly 1 to 2 ft (0.3 to 0.6 m).
Small container: A container used in an ASRS storage arrangement, having walls more than 1.25 in.
(32 mm) in height, that is typically either roughly (1) 16 x 24 x 15 in. tall (400 x 600 x 375 mm tall) in size,
or (2) slightly wider in footprint but does not exceed 18 in. (450 mm) in height.
Small tray (i.e., tray): A flat product material handling platform typically about 16 x 24 in. (400 x 600 mm)
in size, that has a vertical lip around its perimeter that does not exceed more than 1.25 in. (32 mm) in height.
Solid-walled open-top container (top-loading ASRS): A container that has no openings on any of its side
walls. The protection requirements for these types of containers differ from those for non-solid-walled
containers when maintained in a TL-ASRS storage arrangement.
Top-loading ASRS (TL-ASRS): An automatic storage and retrieval system that consists of a metal grid
structure under which containers, usually open-top and made of unexpanded plastic, are stacked one on
top of another in vertically aligned columns. They are accessed from the top of the grid by service robots that
have been programmed to either retrieve a specific container for commodity picking purposes, or for
replenishing the amount of commodity maintained within the storage container.
Vertical barrier: A barrier that is typically installed within the transverse flue space of a storage rack for the
purpose of preventing fire from spreading beyond it. It spans the entire height of the rack as well as its depth,
including across any longitudinal flue spaces, from one face of the rack to the other. It is not intended to
span across a material-handling aisle located between storage racks. When used in a mini-load ASRS storage
arrangement, the vertical barrier can consist of either minimum 22-gauge (0.7 mm) sheet metal or minimum
3/8 in. (10 mm) plywood. For vertical barriers installed in a top-loading ASRS storage arrangement, see the
guidelines specified for the barrier in Section 2.3.6.1.7.
Vertically enclosed ASRS: An ASRS unit that typically works with a vertical lift system or a vertical carousel.
The lift system uses a robotic picker that will store and remove trays that rest on fixed storage supports within
the unit and deliver it to the user. The carousel conveyor system uses a rotating storage arrangement that
brings the storage tray to the user. Typical systems are package units where metal trays supported on a rack.

APPENDIX B DOCUMENT REVISION HISTORY


The purpose of this appendix is to capture the changes that were made to this document each time it was
published. Please note that section numbers refer specifically to those in the version published on the date
shown (i.e., the section numbers are not always the same from version to version).
July 2023. Interim revision. Significant changes include the following:
A. The scope of this data sheet was modified to indicate that it applies to material handling of small
containers and small trays; (see Appendix A for a definition of these terms).
B. The generic term "horizontal-loading" has been introduced to address both mini-load and shuttle type
(i.e., shuttle) ASRS storage arrangements.
C. Previously, this data sheet referenced FM Global Property Loss Prevention Data Sheet 8-9, Storage
of Class 1, 2, 3, 4, and Plastic Commodities, for protection guidelines of (1) closed-top containers stored
directly on the rail supports of a shuttle ASRS and (2) closed-top storage maintained on trays within a
shuttle or mini-load type ASRS. Those protection guidelines have now been added to this data sheet, so
the user can obtain the needed recommendations here.
D. The guidelines for adequately vented open-top containers used in horizontal-loading ASRS storage
arrangements have been removed from this data sheet based on recent successful test results with
solid-walled, open-top plastic containers.
E. Guidelines for open-top noncombustible containers in a horizontal-loading ASRS storage arrangement
have been temporarily removed. Once an Approval Standard for FM Approved “non-propagating
containers” specific to horizontal-loading ASRS arrangements is developed, protection guidelines for these
containers will be reintroduced into the data sheet.
January 2023. Interim revision. Significant changes include the following:

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


8-34 Protection for Automatic Storage
Page 118 FM Global Property Loss Prevention Data Sheets

A. The Final Extinguishment section for top-loading ASRS storage arrangements (former Section 2.3.6.4)
was relocated to the beginning of this section and is now Section 2.3.6.1, with the previous sections and
subsections renumbered.
B. A new ceiling sprinkler system design for ceiling heights up to and including 30 ft (9.1 m) was added
in the Final Extinguishment section for top-loading ASRS storage arrangements where final extinguishment
without manual intervention is a possibility.
C. The guidelines in Section 2.2.3 for storage of products on trays within a mini-load type of ASRS storage
arrangement were clarified to apply only to those products that are not maintained in open-top containers.
D. The intended goal of an adequately vented open-top container and how it can potentially be achieved
when used in a top-loading ASRS storage arrangement was added to Section 2.2.4 and Appendix A.
E. Section 2.3.4 was updated to clarify that a very early warning detection system is recommended over
the storage array of a top-loading ASRS storage arrangement.
F .New figures were added to Section 2.3.6 to clarify that the recommended mezzanines did not have
to extend along the entire perimeter of the storage array.
October 2020. Interim revision. Significant changes include the following:
A. The following changes were made to the entire document:
1. Reformatted the sections so Section 2.2 is specific to mini-load ASRS storage arrangements, Section
2.3 is specific to TL-ASRS storage arrangements, and Section 2.4 is specific to vertically enclosed
storage arrangements.
2. Added instructions for users to see Data Sheet 8-9 for the protection of rack structure ASRS storage
arrangements.
3. Noted that protection options for open-top, gridded-bottom containers used within either mini-load
or top-loading ASRS storage arrangements are outside the scope of this data sheet.
B. The following changes were made specific to mini-load ASRS storage arrangements:
1. Moved all the protection options specific to mini-load ASRS storage arrangements to this document
(i.e., users no longer referred to Data Sheet 8-9 for certain storage arrangements)
2. Added new guidelines for solid-walled noncombustible containers.
3. Added dry-pipe sprinkler protection options.
4. Noted that protection options for expanded plastic trays and containers are outside the scope of
this data sheet.
5. Added information on shuttle-type ASRS storage arrangements in Section 2.1 and Appendix A.
C. The following changes were made specific to top-loading ASRS storage arrangements:
1. Noted that protection options for open-top, gridded-bottom containers are outside the scope of this
data sheet.
2. Added protection options for open-top, non-solid walled containers to this data sheet.
3. Added protection options for noncombustible open-top, solid-walled containers to this data sheet.
D. Clarified TL-ASRS storage arrangements regarding what is needed for sprinkler protection (suppression
or control) and what is needed for final extinguishment. Added new sections for each ASRS storage
arrangement specific to final extinguishment.
E. Added definitions to Appendix A to clarify guidance for the various types of containers described in
this data sheet.
January 2020. Interim revision. Significant changes include the following:
A. Added loss prevention guidelines for top-loading ASRS arrangements that use solid-walled (open- and
closed-top containers).
B. Reformatted the document so each ASRS storage arrangement now has its own section.

©2017-2023 Factory Mutual Insurance Company. All rights reserved.


Protection for Automatic Storage 8-34
FM Global Property Loss Prevention Data Sheets Page 119

C. Incorporated the results of recent full-scale fire testing of top-loading automatic storage and retrieval
systems using solid-walled plastic containers.
January 2018. Interim revision. Clarifications were made to section 2.2.4.2, Longitudinal Flue Spaces,
corrected reference to the table in sections 2.2.4.1.3 and 2.3.4.1.2. Also corrections were made to Table 11,
IRAS Design Guidelines.
October 2017. Interim revision. Minor editorial changes were made.
July 2017. This data sheet has been completely rewritten. The following major changes were made:
A. This data sheet now addresses protection options for ASRS vertically enclosed, rack-structure,
mini-load, and other storage arrangements in which the horizontal support for product material handling
uses rails, angle irons, or other similar supporting structures. When in-rack automatic sprinkler (IRAS)
protection is needed, the protection now offered in this data sheet is designed to prevent the fire from
growing vertically past the in-rack sprinkler protection that has been installed. With this arrangement, the
ceiling and in-rack sprinkler systems operate independent of each other and thus do not need to be
hydraulically balanced nor designed with both systems operating concurrently.
B. The term “storage sprinkler” has been incorporated into this data sheet to replace “Control Mode Density
Area (CMDA) sprinkler.”
C. Ceiling-level sprinkler designs now use the “number of sprinklers @ minimum pressure” design format
in place of the previously used “density/demand area” design format.
D. Added terms to Appendix A, Glossary of Terms.
January 2003. Clarification regarding the storage clearance was added.
September 2000. This revision of the document has been reorganized to provide a consistent format.

©2017-2023 Factory Mutual Insurance Company. All rights reserved.

You might also like