Design HVAC System For Commercial Hospital
Design HVAC System For Commercial Hospital
Design HVAC System For Commercial Hospital
ADEB HASAN
MOHAMMED AL-GAORI
MOATH RADMAN
Supervised
by :
DR. ABDULJALIL AL-ABIDI
Outline :
Introduction 1
Duct design 5
Conclusions
&Recommendations 9
Introduction 1 120
100
www.bluehatmechanical.com
Introduction 1
h t t p s : / / w w w. h y d r o l - e a r t h - s y s t - s c i . n e t / 1 7 / 3 9 3 7 / 2 0 1 3 /
Problem statement 2
K Thickness
Layer
W /m.°C (mm)
Soft stone 1.05 150
A) Manual Method
B) Technical Method
Cooling loads calculation 3
𝐷𝑅
𝑇𝑜𝑚 = 𝑇𝑜 − = 23.75
2
𝑊
𝑄𝑙𝑖𝑔ℎ𝑡 =𝑄 𝐴 = 581 𝑊 3
𝑚2
Q __h
inf il =mf(hi o) =27.6 W 6
𝑉𝑓
Qv=( ) (h -h ) =6650 W 7
𝑣𝑜 * o i
The Total Heat Gain
𝑄𝑡𝑜𝑡𝑎𝑙 = 𝑄 𝑠𝑜𝑙𝑎𝑟 𝑒𝑓𝑓𝑒𝑐𝑡𝑠 + 𝑄𝑡𝑟𝑎𝑛𝑠 + 𝑄𝑙𝑖𝑔ℎ𝑡 + 𝑄𝑜𝑐𝑐𝑢𝑝 + 𝑄𝑒𝑞𝑢𝑖𝑝 + 𝑄𝑖𝑛𝑓𝑖𝑙 + =8.34 KW =2.385 TR
SketchUp
First
SketchUp creates and the
building geometry in REVIT
and gives the defining for
each zone
Second
separate the departments
into spaces and collect spaces
to zones
Such as OP-Z1 and we do
that for all the building
Cooling loads calculation 3
Cooling loads calculation 3
REVIT input data
2.8m
Validation
Load (Kw) Manual method Technical method
Error = 3.2%
Types of ducts
Rectangular or square
Round
Flexible Duct work
Round rectangular
Flexible
Duct design 4
Duct insulation
Duct sizer
Exhaust duct
Duct accessories
Balancing damper
To control the flow rate reducing or
increasing the airflow depending upon
conditions
Duct design 4
FILTERS
To eliminate particles
Filter Design Factors
1. Degree of air cleanliness required.
2. Particulate/contaminate size and form (solid or aerosols).
4. Cost (initial and maintenance).
5. Space requirements.
6. Pressure loss/energy use.
HEPA filter
Efficiency of HEPA filter reach
to 99.997%
Pressure loss reach to 249 pa
Duct design 4
Duct design 4
Duct design 4
After drawing and calculating
duct the main ducts detail
Roof top fan units Actual flow rate Actual Pressure
(m3/s) drop (Pa)
Mechanical supply 1.056 123.64
air (1)
Mechanical supply 1.08 314.67
air (2)
Mechanical 1.9274 334.62
A B
Pipe design 5
Closed system
a closed system is one in which the flow of water is not exposed
to the atmosphere at any point.
Piping Material
Steel- Schedule 40
Pipe design 5
Manual calculation
Pipe design 5
Section Component Diameter Flow Velocity Equivalent NO. of Total ∆P ∆P
Result of manual (mm) rate )m/s) length component length (pa/m) )pa)
(kg/s) (mm) (mm
calculation
)
Input Data
Output data
Pipe design 5
𝐶𝑝 = 4.186 k J/ kg °C
For FCU01 the zone load 𝑸𝒄𝒄 = 8.688kw …. 𝒎 ሶ = 0.415 L/s
𝑇𝑜𝑢𝑡 = 12 0 C 𝑇𝑖𝑛 = 7 oC
Pipe design 5
F.C.U. Spaces Q(W) V(L/s) mw(L/s)
Pipe accessories
Pressure gauge (on chiller)
Temperature gauge
Gate valve
Pressure regulating valve
Butterfly valve
Balancing valve
Strainer
Pipe design 5
Air Separator
Air separator is removing the air from pipes system because air
create noise in the system and causes corrosion in pump
impellers.
Expansion tank
Supply
Return
Pipe design 5
Pump Sizing
centrifugal pump designs which are the most common
types used in comfort air conditioning.
∆𝒑 = 𝜌𝑔ℎ
ℎ = 81.34 𝑚
Pipe design 5
Pump selection
Terminal units 6
Fan-Coil Unit
475 L/s
Terminal units 6
Fan
Cooling Coil
Filters
Terminal units 6
Selection of
absorption chiller
Absorption chiller 8
Absorption chiller 8
Efficiency of evacuated
tube
Absorption chiller 8
Thermann TH-30 Collector Specification Source:[ Apricus ,technical manual, March2014]
Absorption chiller 8
Absorption chiller 8
Item Result
𝑸𝑺
𝑨𝑪 = Qe 369 kW
𝛈𝐬𝐨𝐥𝐚𝐫 𝐈𝐦𝐚𝐱
Qg 473.1 kW
𝑨𝒄 Qs 333.2 Kw
𝑨𝒄 = 𝒏𝑨𝒆 → 𝒏 = 504.9 𝑚2
𝑨𝒆 Ac
Ag 792 𝑚2