Rotonivo ® Level limit switch


Series RN 3000 / 6000
Technical information / Instruction manual
Table of contents
2
Page

Safety notes / Technical support 2

---------------------------------------------------------------------------------------------------------
3
Introduction 3

---------------------------------------------------------------------------------------------------------

Function 4
4
---------------------------------------------------------------------------------------------------------

Technical data 6

---------------------------------------------------------------------------------------------------------

Approvals 14 5
---------------------------------------------------------------------------------------------------------

Options 15

--------------------------------------------------------------------------------------------------------- 6
Mounting 16
---------------------------------------------------------------------------------------------------------

Electrical installation 20

--------------------------------------------------------------------------------------------------------- 7
Signal and alarm output 25

---------------------------------------------------------------------------------------------------------

Setting / Sensitivity 28 8
---------------------------------------------------------------------------------------------------------

Maintenance 29

---------------------------------------------------------------------------------------------------------
9
Notes for use in Hazardous Locations 30

---------------------------------------------------------------------------------------------------------

Disposal 32
10

Subject to technical change We assume no liability for typing errors.


All dimensions in mm (inches). Different variations than specified are possible.
Please contact our technical consultants.
11

12
RN 3000 / 6000 gi011015 page 1
1
Rotonivo ® Level limit switch
Series RN 3000 / 6000
Technical information / Instruction manual
Safety notes / Technical support
2
Notes
• Installation, maintenance and commissioning may be accomplished only by qualified technical personnel.
• The product must be used only in the manner outlined in this instruction manual.

3
Special attention must be paid to warnings and notes as follows:

WARNING
4
Relates to a caution symbol on the product: A failure to observe the necessary
precautions can result in death, serious injury and/or considerable material damage.

WARNING

5 Relates to a caution symbol on the product: Risk of electric shock

WARNING

6 A failure to observe the necessary precautions can result in death, serious injury
and/or considerable material damage.

This symbol is used, when there is no corresponding caution symbol on the product.

A failure to observe the necessary precautions can result in considerable material


7 CAUTION damage.

Safety symbols
8
In manual and on Description
product
CAUTION: refer to accompanying documents (manual) for details.

9 Earth (ground) Terminal

Protective Conductor Terminal

10
Technical support
Please contact your local supplier (for address see www.uwt.de). Otherwise you can contact:

11 UWT GmbH Tel.: 0049 (0)831 57123-0


Westendstr. 5 Fax: 0049 (0)831 76879
D-87488 Betzigau info@uwt.de
www.uwt.de

12
page 2 gi011015 RN 3000 / 6000
1
Rotonivo ® Level limit switch
Series RN 3000 / 6000
Technical information / Instruction manual
Introduction

Applications 2

The ROTONIVO is an electromechanical Level limit switch and The ROTONIVO is normally screwed into the lateral container
is used for level monitoring of bulk goods. wall so that it is in level with the filling height to be registered and
monitored.
The units can be delivered with a wide range of Ex-approvals 3
for use in Hazardous Areas. The device can also be mounted from the top of the container. In
this case an extension piece is used to mount the probe level with
They can be equipped for process over- and lowpressure and the height to be registered.
also for very high or low process temperatures.
The length of the probe can be up to 4m (158") with an extension
Selected applications: tube or up to 10m (394“) with an extension rope.
4
• building materials industry The use of a sliding sleeve for the version RN 3002 / 6002 is
lime, styrofoam, moulding sand, etc. recommended so that the switch point can be changed easily
• food industry during operation of the device.
milk powder, flour, salt, etc.
• plastics industry
plastics granules etc.


timber industry
chemical industry
5
• mechanical engineering

6
RN 3001
RN 3002-rope
RN 3002 RN 6001
RN 6002-rope
RN 6002 with pendulum shaft

optional
sliding RN 3001 7
sleeve RN 6001

RN 3004
RN 6004
10
RN 3003
RN 6003

11

12
RN 3000 / 6000 gi011015 page 3
1
Rotonivo ® Level limit switch
Series RN 3000 / 6000
Technical information / Instruction manual
Function

2 A measuring vane is driven by a synchronous motor. The Fail safe alarm


bearing of the motor inside the housing allows it to swing. The With the option fail safe alarm it is possible to recognize a fault of
motor is fixed to a switching lug. the unit in time and to initiate an alarm relay. The following faults
are observed:
If the vane is uncovered, a spring pulls the motor and switching
lug to the left position (figure 1). • Motor
• Gear
3 When material covers the vane and thus stops the rotation, the • Electronic for motor power supply
motor and switching lug swings to the right position (figure 2). • Supply voltage failure
The signal output indicates "covered" and the motor is stopped. • Defect of the connecting wires

When the vane becomes uncovered due to falling material, Functional safety SIL2 (IEC 61508)
the spring pulls the motor and switching lug back to the left With option Functional safety the unit observes the motor, gear
position (figure 1). The motor is started and the signal output and electronic. The result of this diagnostics is present on the
4 indicates "uncovered". signal output, which states the full/ empty condition.

Switchable signal output (Fail safe high /low)


With version "Universal voltage", "PNP" and optional "AC" a
Switch for Switching Switch for
switchable signal output FSH/FSL is integrated.
signal output lug motor stop
Signal output delay:
5 The version "Universal voltage" and "PNP" has an integrated
adjustable delay for the signal output.

6 Figure 1

7
Figure 2

Selection guide
8 RN 3001 RN 3001 RN 3002 RN 3002-rope RN 3003 RN 3004
RN 6001 RN 6001 RN 6002 RN 6002-rope RN 6003 RN 6004
pendulum shaft

Full detector x x* x x x x

10 Demand detector x x* x x
Empty detector x x* x x
Vertical mounting x x x x* x
Oblique from the top x x** x
Horizontal mounting x x x
11 Oblique from the bottom x x

* consider max. permitted mech. traction force


** only with option "bearing at tube end"

12
page 4 gi011015 RN 3000 / 6000
1
Rotonivo ® Level limit switch
Series RN 3000 / 6000
Technical information / Instruction manual
Function
2
Shaft sealing and metal material

Application Sealing material (1) Metal Bearing

NBR FPM (Viton) PTFE Aluminium Stainless steel (2) Stainless steel 3
(Teflon) 1.4301/ SS 304

Animal feed press x x x


Synthetic granules, powders x x
Salt x x x
Dust filter (temp. up to 392°F) x x 4
Dust filter (temp. up to 302°F) x x
Bitumen x x
Cement x x
Wood chip dryer x x
Pressure conveying vessel, 8bar x x 5
Sugar x x
Flour x x
Carbon black x x

(1)
Delivered in version with process temperature and process pressure as following (see also option pos.17): 6
NBR: max 80°C and max. 0.8bar
FPM (Viton): max. 150°C and max. 0.8bar
PTFE (Teflon): max. 250°C and max. 0.8bar
max. 80°C/ 150°C/ 250°C and max. 5bar/ 10bar
(2)
In particular cases 1.4404 (SS316L) is recommended

7
Electronic
RN 3000
Output signal
Power supply FSH/ Adjustable Fail safe
SPDT (1) DPDT PNP
FSL (2) delay alarm 8
AC version 24V or 48V or 115V or 230V AC • - - - - -
DC version 24V DC • - - - - -
DC version 24V DC PNP - - • • • -
Universal
24V DC / 22...230V AC • - - • • option
voltage
RN 6000
9
Output signal
Power supply FSH/ Adjustable Fail safe
SPST SPDT (1) DPDT PNP
FSL (2) delay alarm
AC version 24V or 48V or 115V or 230V AC - • - - - - -
DC version 24V DC - • - - - - -
10
Universal
24V DC / 22...230V AC - - • (3) - • • option
voltage
Universal
24V DC / 22...230V AC • • (4) - - • • -
voltage SIL2

(1)
Microswitch, with Universal voltage Relais 11
(2)
Switchable signal output (Fail safe high /low)
(3)
For Ex approval "Increased safety" (pos.2 C,R,S) not in combination with option Fail safe alarm
(4)
Additional output, not SIL conform

12
RN 3000 / 6000 gi011015 page 5
1
Rotonivo ® Level limit switch
Series RN 3000 / 6000
Technical information / Instruction manual
Technical Data
2 Dimensions
Housing versions

Series RN 3000 Series RN 6000


Standard Standard
3

5
Series RN 6000
de explosionproof with increased Series RN 6000
safety terminal box d flameproof /explosionproof

8 Extensions

RN ..001

9 Process
temperature
A

150°C (302°F) 200mm (7.87”)

250°C (482°F) 200mm (7.87”)

350°C (662°F) 300mm (11.8”)

600°C (1112°F) 400mm (15.7”)

10

11 Thread / Flange Temperature Triclamp


extended shaft

12
page 6 gi011015 RN 3000 / 6000
1
Rotonivo ® Level limit switch
Series RN 3000 / 6000
Technical information / Instruction manual
Technical Data
2
RN ..002
Process
A
temperature

150°C (302°F) 200mm (7.87”)

250°C (482°F) 200mm (7.87”)

350°C (662°F) 300mm (11.8”) 3


600°C (1112°F) 400mm (15.7”)

5
Without sealing
and bearing at
tube end (see also
option pos. 32) Temperature
Thread / Flange
extended shaft Triclamp
6
RN ..002 rope

Type standard (pos.1 C) Type reinforced (pos.1 H)


(max. 4kN load) (max. 28kN load)
7

10

Temperature
extended shaft
350 / 600°C
(662/ 1112°F)
11
Temperature
extended shaft
150 / 250°C
Thread / Flange Thread / Flange (302 / 482°F)

12
RN 3000 / 6000 gi011015 page 7
1
Rotonivo ® Level limit switch
Series RN 3000 / 6000
Technical information / Instruction manual
Technical Data
2 RN ..003 Process
B
temperature

80°C (176°F) 10mm


0.8 bar (11.6psi) (0.39”)

80°C (176°F) 75mm


5/ 10bar (73/ 145psi) (2.95”))

3
150/ 250°C
(302/ 482°F) 210mm
0.8/5/10 bar (8.27”)
(11.6/73/145psi)

Material C

steel ø55mm (2.17”)


4 aluminium ø60mm (2.36”)

Vane D

50mm x ..mm
139mm (5.47”)
(1.97” x ..”)

98mm x ..mm
Temperature
5
187mm (7.36”)
(3.86” x ..”)
extended shaft

RN ..004
Process
A
temperature

6 150°C (302°F) 200mm (7.87”)

250°C (482°F) 200mm (7.87”)

350°C (662°F) 300mm (11.8”)

600°C (1112°F) 400mm (15.7”)

Thread / Flange Temperature extended Triclamp


shaft
9
RN 3005

10

Process
connection
11

12
page 8 gi011015 RN 3000 / 6000
1
Rotonivo ® Level limit switch
Series RN 3000 / 6000
Technical information / Instruction manual
Technical Data

Measuring vanes code B,C,E,F,G,I


2
code P
rectangular vane notched 40x80

code type a b
B rectangular 50mm (1.97'') 98mm (3.86'')
C rectangular 50mm (1.97'') 150mm (5.90')
E
F
rectangular
rectangular
50mm (1.97'')
98mm (3.86'')
250mm (9.84'')
98mm (3.86'')
3
G rectangular 98mm (3.86'') 150mm (5.90'')
I rectangular 98mm (3.86'') 250mm (9.84')

code K b=37mm (1,46")


code A
boot shaped vane 40x98
hinged vane 98x200 double for 1½“ / 1¼“ 4
sided
b=28mm (1,1")
for 1" / M32x1,5

to lead in 1½“ socket


(length of socket
max. 40mm (1.57”))
5

code D
code S
hinged vane 98x100 single sided
b=37mm (1,46")
für 1½“ / 1¼“
6
boot shaped vane 35x106
b=28mm (1,1")
for 1" / M32x1,5

to lead in 1¼ “ socket
(length of socket
max. 40mm (1.57”)) 7

code R
boot shaped vane 28x98 8
to lead in 1“ or
M32x1.5 socket
(max. 40mm (1.57”))
Insertion of the hinged vane spring
through a long socket
9

code M
10
code J
boot shaped vane rubber vane 98x250
to lead in M30
26x77
socket (max.
40mm (1.57”))

11

12
RN 3000 / 6000 gi011015 page 9
1
Rotonivo ® Level limit switch
Series RN 3000 / 6000
Technical information / Instruction manual
Technical Data
2
Electrical data

Connection terminals see page 23/24


Cable entry M20 x 1,5 screwed cable gland
NPT 1/2“ conduit connection
3 NPT 3/4” conduit connection (only RN 6000)

Clamping range (diameter) of the factory provided cable glands:


M20 x 1.5: 6 .. 12mm (0,24 .. 0,47")
Protection class I
III (Version 24V DC PNP)
4 Overvoltage category II
Pollution degree 2 (inside housing)

Power supply see page 23/24

Installed load see page 23/24

Signal and alarm output see page 23/24


5
Isolation Power to signal and alarm output: 2225 Vrms
Signal output to signal output (DPDT): 2225Vrms
Indicating light By built-in LED (apart form AC version)

Mechanical data
6
Housing Aluminium housing, powdercoated, RAL 5010 gentian blue
RN3000: optional plastic PA6 GF, RAL 5010 gentian blue
Seal between housing and lid: NBR
Seal between housing and process connection: NBR
Nameplate: poyester film
7 Degree of protection RN 3000: IP 66*

RN 6000: IP 66*

Types with process connection and extension in stainless steel:


IP 66*, NEMA Type 4X (not for: RN 600x with process temperature ≥ 150°C (302°F),
RN 6002 with sliding sleeve, RN 6003)
8 * IEC/EN/NBR 60529
Process connection Material: aluminium or stainless steel, 1.4301 (304) / 1.4305 (303) / 1.4541 (321) or stainless steel
1.4404 (316L)
Thread: Metric or G (DIN 228) or NPT (tapered ANSI B 1.20.1) according to selection
Triclamp
Flanges: according to selection

9 Vane shaft and


measuring vane
Material: stainless steel, 1.4301 (304) / 1.4305 (303) or stainless steel 1.4404 (316L)

Tolerance length "L“ ± 10mm (± 0.39“)

Bearing Ball bearing, dust-tight

Sealing Radial rotary shaft sealing

10 Material: NBR (Acrylnitril-Butadien-rubber)


FPM (Viton)
PTFE (Teflon)
Graphite based (version 600°C/1112°F)

See also selection guide on page 5.

11 Friction clutch Protects the gear unit against impacts of the measuring vane

Speed of measuring vane 1 rotation or 5 rotations per minute


Sound level max. 50dBA

12
page 10 gi011015 RN 3000 / 6000
1
Rotonivo ® Level limit switch
Series RN 3000 / 6000
Technical information / Instruction manual
Technical Data
Overall weight
RN 3000 Version Extension
2
(ca.)
80°C 150/250/600°C
(176°F) (302/482/662°F)
Aluminium * Stainl. steel * Aluminium Stainl. steel *
RN 3001 1.2kg 1.5kg +1.2kg - -
(2.6 lbs) (3.3 lbs) (+2.6 lbs) 3
RN 3002 1.3kg 1.6kg +1.2kg +1.3kg/m +2,7kg/m
(2.9 lbs) (3.5 lbs) (+2.6 lbs) (+2.9 lbs per 39.3“) (+5.9 lbs per 39.3“)

RN 3002- 2.1kg 2.4kg +1.2kg - +0,25kg/m


rope (4.6 lbs) (5.3 lbs (+2.6 lbs) (+0.6 lbs per 39.3“)

3.7kg** 6.1kg** +1.2kg +0.4kg/100mm +0.6kg/100mm 4


RN 3003 (8.1 lbs) (13.4 lbs) (+2.6 lbs) (+0.9 lbs per 3.93”) (+1.3 lbs per 3.93”)

1.3kg 1.6kg +1.2kg +0.15kg/100mm +0.3kg/100mm


RN 3004 (2.9 lbs) (3.5 lbs) (+2.6 lbs) (+0.3 lbs per 3.93”) (+0.7 lbs per 3.93”)

1.3kg 1.6kg
RN 3005 (2.9 lbs) (3.5 lbs) 5

* Process connection
** Version with flange 150x150x12mm (5.9x5.9x0.47”), L=250mm (9.84”)
All weights are without flanges (except RN 3003) and smallest measuring vane.
6

RN 6000 Version Extension


80°C 150/250/600°C
(176°F) (302/482/1112°F)
Aluminium * Stainl. steel * Aluminium Stainl. steel *
7
RN 6001 1.5kg 1.8kg +12kg - -
(3.3 lbs) (4.0 lbs) (+2.6 lbs)

RN 6002 1.6kg 1.9kg +1.2kg +1.3kg/m +2,7kg/m


(3.5 lbs) (4.2 lbs) (+2.6 lbs) (+2.9 lbs per 39.3“) (+5.9 lbs per 39.3“)
8
RN 6002- 2.4kg 2.7kg +1.2kg - +0.25kg/m
rope (5.3 lbs) (5.9 lbs) (+2.6 lbs) (+0.6 lbs per 39.3“)

4.0kg** 6.4kg** +1.2kg +0.4kg/100mm +0.6kg/100mm


RN 6003 (8.8 lbs) (14.1 lbs) (+2.6 lbs) (+0.9 lbs per 3.93”) (+1.3 lbs per 3.93”)

RN 6004
1.6kg
(3.5 lbs)
1.9kg
(4.2 lbs)
+1.2kg
(+2.6 lbs)
+0.15kg/100mm
(+0.3 lbs per 3.93”)
+0.3kg/100mm
(+0.7 lbs per 3.93”)
9

All mentioned weights are with Standard-housing.


By use of de-housing: +1.4kg (+3.1lbs)
d-housing: +1.0kg (+2.2lbs) 10
* Process connection
** Version with flange 150x150x12mm (5.9x5.9x0.47”), L=250mm (9.84”)
All weights are without flanges (except RN 6003) and smallest measuring vane.

11

12
RN 3000 / 6000 gi011015 page 11
1
Rotonivo ® Level limit switch
Series RN 3000 / 6000
Technical information / Instruction manual
Technical Data
2
Operating conditions
RN3000:
Ambient temp. (housing) /
process temperature

5 -40°C (-40°F) ambient and process temperature for version with heating of housing (pos. 26)
-40°C (-40°F) ambient temperature not for version with plastic housing in Ex Version
+350/600°C (+662/1112°F) process temperature not for version RN 3003, not for Ex-approvals
For versions with Ex-approvals: see remarks on page 31.

RN6000:
6 Ambient temp. (housing) /
process temperature

8
-40°C (-40°F) ambient and process temperature for version with heating of housing (pos. 26)
+350/600°C (+662/1112°F) process temperature not for version RN6003, not for Ex-approvals
For versions with Ex-approvals: see remarks on page 31.

Ventilation Ventilation is not required


9
Min. powder density / see section “Sensitivity” on page 28
sensitivity
Output signal delay Version AC, DC Universal voltage
Sensor free -> covered* ca. 1.3 sec ca. 1,5 sec + 0 ..20 sec adjustable
Sensor covered -> free ca. 0.2 sec ca. 0,2 sec + 0 ..60 sec adjustable
10 *after blocking of the masuring vane
Features of bulk material Hardly any limitations.

11

12
page 12 gi011015 RN 3000 / 6000
1
Rotonivo ® Level limit switch
Series RN 3000 / 6000
Technical information / Instruction manual
Technische Daten

Max. permitted RN 3001 / 6001: RN 3002/ 6002


2
mechanical torque RN 3004/ 6004:
max. 50 Nm*
Steel: max. 500 Nm*
Alu: max. 180 Nm*
max. 50 Nm*
3
RN 3003 / 6003: Steel: max. 600 Nm*
Alu: max. 250 Nm*

5
* at 40°C
For version with reinforced rib on request

Protective measures in case of high load: mounting of an protective canopy above the probe
(horizontal installation) or fixing of the extension tube.

6
Max. tractive force RN 3001 / 6001 pendulum shaft: 400N (only applicabel as full detector)
RN 3002 / 6002-rope: 4kN (type standard) 28kN (type reinforced)
Max. process pressure -0.9 .. +0.8bar (-13.1 .. 11.6psi) or -0.9 .. +5 bar (-13.1 .. 73psi) or -0.9 .. +10 bar (-13.1 .. 145psi)
-0.1 .. +0.1bar (-1.5 ..1.5psi) for 600°C (1112°F) version
For pressure over 0.8 bar (11.6psi) the Teflon sealing is used.
For versions with Ex-approvals: see remarks on page 30.
Vibration 1.5 (m/s2) 2 /Hz according to EN 60068-2-64
7
Relative Humidity 0-100%, suitable for outdoor use

Altitude max. 2.000m (6.562ft)

Expected product Following parameters have a negative influence on the expected product lifetime:
8
lifetime High ambient- and process temperature, corrosive environment, high vibration, high flow rate of
abrassive bulk material passing the sensor element, high amount of measurement cycles..

9
Transport and storage
Transport Observe the instructions as stated on the transport packing, otherwise the products may get
damaged.

Transport temperature: -40 .. +80 °C (-40 .. +176 °F) 10


Transport humidity: 20 .. 85 %

Transport incoming inspections must be caried out to check for possible transport damage.

Storage Products must be stored at a dry and clean place.


They must be protected from influence of corrosive enviroment, vibration and exposure to direct
sunlight. 11
Storage temperature: -40 .. +80 °C (-40 .. +176 °F)
Storage humidity: 20 .. 85 %

12
RN 3000 / 6000 gi011015 page 13
1
Rotonivo ® Level limit switch
Series RN 3000 / 6000
Technical information / Instruction manual
Approvals
2

RN 6000
RN 3000

General Purpose * • • CE EN 61010-1 (IEC/CB)


(Ordinary Locations)
3 •

FM
CSA
• TR-CU

Hazardous Locations * • • ATEX Dust explosion ATEX II 1/2 D Ex t IIIC T! Da/Db IP6X

• Gas explosion flameproof ATEX II 2G Ex d IIC T! Gb


4 • flameproof / increased safety ATEX II 2G Ex de IIC T! Gb

• • IEC-Ex Dust explosion IEC-Ex t IIIC T! Da/Db IP6X

• Gas explosion flameproof IEC-Ex d IIC T! Gb


• flameproof / increased safety IEC-Ex de IIC T! Gb

• FM Dust explosion Cl. II, III Div. 1 Gr. E,F,G


5
• Gas explosion flameproof XP Cl. I Div. 1 Gr. B-D
Cl. I Zone 1 AEx d IIC
• Gas explosion flameproof / increased safety Cl. I Zone 1 AEx de IIC

• CSA Dust explosion Cl. II, III Div. 1 Gr. E,F,G


Ex DIP A20/21
6 • Gas explosion flameproof XP Cl. I Div. 1 Gr. B-D
Cl. I Zone 1 Ex d IIC
• Gas explosion flameproof / increased safety Cl. I Zone 1 Ex de IIC

• TR-CU Dust explosion DIP A20/ A21

• • INMETRO Dust explosion Ex ta/tb IIIC T! Da/Db IP6X


7 Gas explosion flameproof Ex d IIC T! Gb

Gas explosion flameproof / increased safety Ex de IIC T! Gb


Detailed allocation of types and electronic modules to approvals: see selection list.

Functional safety • SIL 2 (IEC 61508)


8 The Safety Manual RN6000 must be considered when using the units in safety systems.
EMC • • EN 61326 -A1
Hygiene* • • EHEDG
Food grade material • • According to directive 1935/2004/EC
RoHS Conform • • According to directive 2011/65/EU
9 Pressure Equipment The units are not subject to this directive, because they are classified as „pressure-keeping
Directive (97/23/EC) equipment“ and do not have a pressurized housing (see Art.1, clause 2.1.4).
The units are designed and manufactured in accordance to the Pressure Equipment Directive.

The unit is NOT intended for use as a "equipment part with safety function" (Art.1, clause 2.1.3).
If the units should be used as "equipment part with safety function", please contact the
manufacturer.
10 * Depending on selected version

11

12
page 14 gi011015 RN 3000 / 6000
1
Rotonivo ® Level limit switch
Series RN 3000 / 6000
Technical information / Instruction manual
Options

Weather protection If the measuring device is used outdoors, the use of the
2
cover weather protection cover is recommended. It protects the
device from all atmospheric influences such as:
• rain water
• condensation water
• excessively high temperatures due to insolation
• excessively low temperatures in winter
3
Material: PE, weather and temperature stable

Not available for housing version d and de.


For use in Hazardous Locations: only permitted for zone 2 and
22 or Division 2.

Sliding sleeve RN 3002 / 6002 Process connection and material as 4


chosen

Version with selection code pos. 30:


Only for applications without process pressure.
Not available for Ex-approvals.

Version with selection code pos. 31: For applications with


process pressure. Sealing material to the extension tube:
5
viton.

Mounting set Screws and washers for fixing the unit on a flange.

Flat gasket On the face sealing of the process connection thread.


Incl. sealing face for version with G 1 1/2" thread.
6
Not available for 600°C version.

LED To see the indicating light on the electronic module from 7


(Glass window in lid) outside. LED

Not available for housing version d and de.

Glass window

8
Bulb in cable gland Bright indicating light seen from outside.

Not available for use in Hazardous Locations.

9
Plug Used instead of cable gland.
Not available for use in Hazardous Locations and FM / CSA general purpose.
Connection of the plug wires to the internal terminals of the unit must be done on site or according to
customer demands.

Valve connector (incl. mating plug) 10


4-pole (incl. PE), max. 230V, enclosure plastic, IP65

Plug M12 (without mating plug)


4-pole, max. 25V or 5 -pole , max. 60V
Enclosure brass, IP67

Plug Han 4A (incl. mating plug) 11


5-pole (incl. PE), max. 230V, enclosure zinc, IP65

12
RN 3000 / 6000 gi011015 page 15
1
Rotonivo ® Level limit switch
Series RN 3000 / 6000
Technical information / Instruction manual
Options / Mounting
2 EHEDG approval EHEDG conform design (material and construction in
contact with the process).

Approved with flush welding socket


Material: aluminium or 1.4301(304) or 1.4404 (316L)
(details see: mounting instructions EHEDG version, page
17).
3

Food grade material Food grade material in contact with the process food (sealing and grease FDA conform). The option
4 does not automatically implement a food conform design (food conform gaps, surface and radiuses).

Mounting

5 General Safety Instructions


Process pressure Improper installation may result in loss of process pressure.

Chemical resistance Materials of construction are choosen based on their chemical compatibility (or inertness) for
against the medium general purposes. For exposure to specific environments, check with chemical compatibility
charts before installing.
6
Mechanical load The torque at the fastening spot must not exceed the specified ratings. See page 12 for details.

Mounting location Keep away from incoming material and from silo walls.
The installation has to be carried out, that the sensor elements cannot hit the wall of the silo. The
flow of the medium and fixtures in the container must be considered. This is especially important
7 for extension length of more than 3000mm (118“)

Sliding sleeve Tighten both straining screws M8 with 20 Nm


to obtain resistance against pressure

Flange mounting A plastic seal must be used to tighten the flange.


9 EHEDG-approval / The materials are available for the use under normal and predictable applications (according to
Food grade material directive 1935/2004 Art.3). Other conditions can influence the safety.

Additional Safety Instructions for Hazardous Locations


10
Installation regulations For devices to be used in Hazardous Locations the respective valid installation regulations must
be observed.

Sparks The installation has to be done in a way, that mechanical friction or impact does not cause
sparks between the aluminium enclosure and steel.
11

12
page 16 gi011015 RN 3000 / 6000
1
Rotonivo ® Level limit switch
Series RN 3000 / 6000
Technical information / Instruction manual
Mounting

Mounting instructions 2

Rotatable housing
The housing can be rotated against the Threaded connection
threaded connection after mounting.

RN 6000: For the d- and de- housing:


3
Fixing screw must be unfastened
to enable rotation. Fix the screw
again, when the housing has the
right position.
Fixing screw
Housing
4
Direction of the cable glands When the unit is mounted from the side, ensure, that the cable glands face downwards and are
closed
to avoid water penetration into the housing.

Sealing Seal the process connection thread with teflon tape against process pressure.
Alternative use of a flat gasket is possible (option pos. 15)
5
Precaution for later Use teflon tape to avoid seizing of aluminium process connection thread with the socket
dismounting
EHEDG-Approval Seal the thread with teflon tape against process pressure.

Metal-metal sealing:
• The support muß be plane and without any gap. No teflon tape (or similar) is allowed to be in
between.
• Fixing torque 100Nm
6
The quality of the welding with the container wall must be according to the respective
regulations (e.g. gaps, transitions, surface finish).
A
Length of extension L
28mm
RN ..001
Flush welding
7
(1.1”)
socket RN ..002/ 38mm
RN ..004 (1.5”)

metal-metal seal thread with welding with


sealing teflon tape container wall
9
Dimension of flush welding socket (for optional on site manufacturing):

Surfaces in contact with Section A Section B


process Ra <=0.8um

10

Dimensions in mm
11
* suggested values
(in brackets values to be
adhered bindingly)

12
RN 3000 / 6000 gi011015 page 17
1
Rotonivo ® Level limit switch
Series RN 3000 / 6000
Technical information / Instruction manual
Mounting
2 RN 3001
RN 6001
A Full detector vertical and oblique from the top
max. „L“ = 600 mm (23.62”)

B With pendulum shaft or rope extension: Full detector


vertical from the top. Observe max. pulling force.
3
C Full detector horizontal
max. „L“ = 300 mm (11.8”)

D Demand or empty detector horizontal


max. „L“ = 150 mm (5.9”)
Protective angle recommended depending on load.
4
E Empty detector oblique from the bottom
max. „L“ = 150 mm (5.9”)
Protective angle recommended depending on load.

Horizontal mounting: Boot shaped vane recommended (min.


mech. load, because the vane aligns to the movement of the
5 material).

RN 3002
RN 6002 A Full detector vertical from the top
max. „L“ = 3.000 mm (118“)

Remark:
6 Deviation up to max. 10° from vertical installation with option
„Bearing at tube end“ possible.

B Full detector vertical from the top


max. „L“ = 4.000 mm (158“)

7 Support from side recommended.

RN 3002-Rope
RN 6002-Rope A Full detector vertical
9 B Demand detector vertical

C Empty detector vertical

max. „L“ = 10.000 mm (394“)


Observe max. tractive force.
10

11

12
page 18 gi011015 RN 3000 / 6000
1
Rotonivo ® Level limit switch
Series RN 3000 / 6000
Technical information / Instruction manual
Mounting

RN 3003
2
RN 6003 A Full detector horizontal

B Demand detector horizontal

C Empty detector horizontal

Protective angle recommended depending on load. 3

5
RN 3004
RN 6004 A Full detector vertical and oblique from the top

B Full detector horizontal

C Demand or empty detector horizontal


Protective angle recommended depending on load.
6
D Empty detector oblique from the bottom
Protective angle recommended depending on load.

Horizontal mounting: Boot shaped vane recommended


(min. mech. load, for the vane aligns to the movement of the
material). 7

10

11

12
RN 3000 / 6000 gi011015 page 19
1
Rotonivo ® Level limit switch
Series RN 3000 / 6000
Technical information / Instruction manual
Electrical installation
2 General Safety Instructions

Handling In the case of improper handling or handling malpractice, the electric safety of the device cannot be
guaranteed.

Installation regulations The local regulations or VDE 0100 (Regulations of German Electrotechnical Engineers) must be
3 observed.
WIth use of 24V supply voltage, an approved power supply with reinforced insulation to mains is
required.

Fuse Use a fuse as stated in the connection diagrams (see pages 23 and 24).

RCCB protection In the case of a fault, the supply voltage must be automatically switched off by a RCCB protection
4 switch to protect against indirect contact with dangerous voltages.

Power supply switch A voltage disconnection switch must be provided near the device.

Wiring diagram The electrical connections are made in accordance with the wiring diagram.

Supply voltage Compare the supply voltage applied with the specifications given on the electronic module and name
5 plate before switching the device on.

Cable gland The screwed cable gland and closing element must have following specifications:
Ingress protection IP66, temperature range from -40°C to +70°C, UL or VDE or INMETRO certified
(depending on the country where the unit is installed), pull relief. Make sure that the screwed cable
gland safely seals the cable and that it is tight (danger of water intrusion). Cable glands that are not
used have to be sealed with a blanking element.
The diameter of the field wiring cable has to match to the clamping range of the used cable gland.
6
Conduit system In case of using a conduit system (with NPT thread) instead of a cable gland the regulations of the
country, where the unit is installed, must be observed. The conduit must have a tapered thread either
NPT1/2“ or NPT3/4” in accordance with the unit and ANSI B 1.20.1. Not used inlets must be closed
tight with a metal blanking element.

Field wiring cables • The diameter has to match to the clamping range of the used cable gland.
7 • The cross section has to match with the clamping range of the connection terminals and consider
the max. current.
• All field wirings must have insulation suitable for at least 250V AC.
• The temperature rating must be at least 90°C (194°F).
• If higher immunity interferences as specified in the stated EMC standards are present (see chapter
approval), a shielded cable is required, otherwise an unshielded instrumentation cable is satisfactory.

8 Guiding the cables in the Cut the field wiring cables to appropriate length to fit properly into the terminal box.
terminal box
Microswitch protection Provide protection for microswitch contacts to protect the device against inductive load surges.

Protection against static The housing of the unit must be grounded to avoid static charging of the unit. This is particularly
charging important for applications with pneumatic conveying and non-metallic containers.

Additional Safety Instructions for Hazardous Locations

10 External equipotential RN 3000 RN 6000


bonding terminal

Connect to equipotential
bonding of the plant

11

12
page 20 gi011015 RN 3000 / 6000
1
Rotonivo ® Level limit switch
Series RN 3000 / 6000
Technical information / Instruction manual
Electrical installation

Field wiring A strain relief must be provided for the field wiring cables, when the device is installed with the factory
2
provided cable glands.

Field wiring terminals for Fixing torque : 0,5-0,6Nm


“de” housing Remove wire isolation: 9mm

Cable glands and Installation according to the regulations of the country, where the product is installed.
conduit system 3
for ATEX / IEC-Ex Not used entries have to be closed with blanking elements certified for this purpose.
INMETRO / TR-CU
(Dust and Gas Hazardous Where available the factory provided parts must be used.
Locations)
A strain relief must be provided for the field wiring cables, when the device is installed with the factory
provided cable glands.
4
The diameter of the field wiring cable must match to the clamping range of the cable clamp.

If other than the factory provided parts are used, following must be ensured:
The parts must have an approval adequate to the approval of the level sensor (certificate and type of
protection).
The approved temperature range must be from the min. ambient temperature of the level sensor to the
max. ambient temperature of the level sensor increased by 10 Kelvin.
The parts must be mounted according to the instructions of the supplier.
5
Installation of a flameproof/ explosion proof enclosure with a conduit system:
In a conduit system single electric conductors are installed in a certified pipe system. This pipe system
is in a flameproof / explosion proof construction as well. The flameproof / explosion proof enclosure
and the pipe system needs to be sealed from each other by a certified flameproof seal of a type “d”
or explosion proof of a type “XP”.This seals shall be installed directly in or at the conduit entries of the
flameproof / explosion proof enclosure. Not used entries have to be closed with blanking elements 6
certified for this purpose (flameproof type “d” or explosion proof type “XP”).

Conduit system for General requirements:


FM and CSA In addition the regulations of the country must be observed. The used flameproof seals and blanking
(Dust and Gas Hazardous elements must have an adequate type approval and a temperature range of at least –40°C (-40°F)
Locations) to +80°C (176°F). In addition they shall be suitable for the conditions and correctly installed. Where
available the provided original parts of the manufacturer must be used. 7
Installation of a flameproof enclosure “d” with a conduit system:
In a conduit system single electric conductors are installed in a certified pipe system. This pipe system
is in a flameproof construction as well. The flameproof enclosure “d” and the pipe system needs to be
sealed from each other by a certified flameproof seal. Conduit entries of a flameproof enclosure “d”
shall have installed the flameproof seal within 18 inches from the enclosure wall. Not used entries have
to be closed with adequate blanking elements of a certified flameproof type AEx Cl.1 Div.1 A. 8
Commissioning Commissioning only with closed lid.

Opening the lid Units with Dust Explosion approval:


Before opening the lid take care, that no dust deposits or whirlings are present.
Do not remove the lid (cover) while circuits are alive.

RN 6000:
9
Units with flameproof GasExplosion approval (d-housing):
To prevent ignition of hazardous atmospheres, do not remove the lid (cover) while circuits are alive.

10

11

12
RN 3000 / 6000 gi011015 page 21
1
Rotonivo ® Level limit switch
Series RN 3000 / 6000
Technical information / Instruction manual
Electrical installation
2 Connection

RN 3000: Standard housing

Connecting
4 terminals

6 RN 6000: Standard and d-housing de-housing

Connection is done directly Connection is done on the terminals


on the PCB inside the increased safety area.

7
Motor is
internally
connected to
the housing
(grounded)

8 Protective
conductor
Connecting
Connection terminal
terminals
terminals

9 Protective
conductor
terminal

10

11

12
page 22 gi011015 RN 3000 / 6000
1
Rotonivo ® Level limit switch
Series RN 3000 / 6000
Technical information / Instruction manual
Electrical installation Series RN 3000

Version: Power supply:


2
- AC
- DC • AC version:
- Universal voltage 24V or 48V or 115V or 230V 50/60Hz max. 4VA
All voltages ±10% (1) max.1.5mm²
Supply voltage as selected. (AWG16)
External fuse: max 10A, fast or slow, HBC, 250V
3
• DC version:
24V DC ±15% (1) max. 2.5W
External fuse: not required

• Universal voltage:
24V DC ±15% (1) max.4W
22 .. 230V 50/60Hz ±10% (1) max.10VA 4
External fuse: not required

(1)
including ±10% of EN 61010

Alarm Signal
Signal and alarm output: L N PE*
output (2) output
+ - 5
Micro switch or relay, SPDT contact Power supply
max. 250V AC, 2A, 500VA (cosj = 1)
max. 300V DC, 2A, 60W With option Fail safe
(2)

External fuse: max 10A, fast or slow, HBC, 250V alarm (rotation control)
Contact open when de-energised

6
Version: Power supply:
- PNP
24V DC ±15% (1)
including ±10% of EN 61010
(1)

Input current: max. 0.6A


max.1.5mm²
Signal output: (AWG16) 7
Load max.0.4A
Output voltage equal to input voltage, drop <2,5V
Open collector
Protected against short circuit and overload

8
+ - Load PE*
Power
supply

10

11
* Protection against static charge:
The PE terminal of the unit must be grounded to avoid static charging of the unit.
This is particularly important for applications with pneumatic conveying.

12
RN 3000 / 6000 gi011015 page 23
1
Rotonivo ® Level limit switch
Series RN 3000 / 6000
Technical information / Instruction manual
Electrical installation Series RN 6000
2 Version: Power supply:
- AC
max.4mm²
- DC • AC version:
(AWG12)
24V or 48V or 115V or 230V 50/60Hz max. 4VA
All voltages ±10% (1)
Supply voltage as selected.
3 External fuse: max 10A, fast or slow, HBC, 250V

• DC version:
24V DC ±15% (1) max. 2.5W
External fuse: not required

(1)
including ±10% of EN 61010

4 Signal output: Signal L N PE


output + -
Micro switch, SPDT contact Power supply
max. 250V AC, 5A, non inductive
max. 30V DC, 4A, non inductive
External fuse: max 10A, fast or slow, HBC, 250V
5
max.4mm²
(AWG12)
Version: Power supply:
- Universal voltage
(without SIL 2) 24V DC ±15% (1) max.4W
6 22 .. 230V 50/60Hz ±10% (1) max.10VA

(1)
including ±10% of EN 61010

Signal and alarm output:


Relay DPDT contact
7 max. 250V AC, 5A, non inductive;
max. 30V DC, 4A, non inductive
External fuse: max 10A, fast or slow, HBC, 250V
Signal output DPDT Alarm L N PE
output (2) + -
Power supply
(2)
With option Fail safe alarm (rotation control)
8 Contact open when de-energised

max.4mm²
Version: Power supply: (AWG12)
- Universal voltage
SIL 2 24V DC ±15% (1) max.4W
9 22 .. 230V 50/60Hz ±10% (1) max.10VA

(1)
including ±10% of EN 61010

Signal output:
Relay SPST/ SPDT
10 max. 250V AC, 5A, non inductive;
max. 30V DC, 4A, non inductive
External fuse: max 10A, fast or slow, HBC, 250V
additional Signal output L N PE
Signal output SPST + -
SPDT SIL conform Power supply
not SIL conform
11
* Protection against static charge:
The PE terminal of the unit must be grounded to avoid static charging of the unit.
This is particularly important for applications with pneumatic conveying.

12
page 24 gi011015 RN 3000 / 6000
1
Rotonivo ® Level limit switch
Series RN 3000 / 6000
Technical information / Instruction manual
Signal and alarm output

Overview Overview of signal and alarm output for the different electronic versions: see page 5 2

Signal output: Version • RN 3000: AC, DC


Switching logic • RN 6000: AC, DC

RN 3000 RN 6000 3
DC DC

green

red red

Version • RN 3000: Universal voltage, PNP


• RN 6000: Universal voltage (without SIL 2)

6
FSH: Use this setting when sensor is used as a full detector.
Power failure or line break is regarded as „full“ signal (protection against overfilling).

FSL: Use this setting when sensor is used as an empty detector.


Power failure or line break is regarded as „empty“ signal (protection against running dry).

8
LED

yellow green
9

LED

10

green yellow Factory setting: FSL

11
Power
failure

12
RN 3000 / 6000 gi011015 page 25
1
Rotonivo ® Level limit switch
Series RN 3000 / 6000
Technical information / Instruction manual
Signal and alarm output
2
Version • RN 6000: Universal voltage SIL 2

FSH: Use this setting when sensor is used as a full detector.


Power failure or line break is regarded as „full“ signal (protection against overfilling).

3 FSL: Use this setting when sensor is used as an empty detector.


Power failure or line break is regarded as „empty“ signal (protection against running dry).

5 yellow green

LED

6
Factory setting: FSL
green yellow

Power
7 failure

10

11

12
page 26 gi011015 RN 3000 / 6000
1
Rotonivo ® Level limit switch
Series RN 3000 / 6000
Technical information / Instruction manual
Signal and alarm output

Signal output: 2
Sensor covered -> free
Delay Factory setting = 3 sec

Sensor free -> covered


Factory setting = 1 sec
4

Switching and timing behaviour:


Alarm output If the sensor is not covered, the rotating paddle shaft will send pulses at 20 sec
(Fail safe alarm, intervals. In case of fault, the pulses are missed. After 30 sec the alarm relay will open.
Rotation control)
5
RN 3000 yellow or green
(see page before) red
Universal voltage

LED

6
No fault Fault

7
RN 6000
Universal voltage yellow or green
(see page before) red
(without SIL 2)

8
LED

No fault Fault

RN3000 RN6000
Connection example:

Full detector with maximum safety:


The output signal opens in case of:
• full signal or 10
• failure of supply voltage or
• defect of the connection wires or
• defective unit
Signal output

11

12
RN 3000 / 6000 gi011015 page 27
1
Rotonivo ® Level limit switch
Series RN 3000 / 6000
Technical information / Instruction manual
Settings: Sensitivity
2
Adjustment of The spring is adjustable in 3 positions. It should be changed only if necessary.
the spring „Fine“: for light material
„Medium“: suitable for nearly every material (factory setting)
„Coarse“: for very sticky material

The spring can be changed via a small plier.


3
RN 3000 RN 6000

4
Spring

5
fine
medium coarse

6
Sensitivity The table shows approximate values for the minimum densities, at which a normal function should be possible.

*Minimum density in g/l = kg/m³ (lb/ft³) (without guarantee)


Vane completely covered with bulk
Bulk material covers vane up to 100mm (3.93“)
7 Vane
material
Spring adjustment Spring adjustment
medium medium
fine fine
(factory setting) (factory setting)
Boot shaped vane 40x98 200 (12) 300 (18) 100 (60) 150 (9)

8 Boot shaped vane 35x106 200 (12) 300 (18) 100 (60) 150 (9)
Boot shaped vane 28x98 300 (18) 500 (30) 150 (9) 200 (12)
Boot shaped 26x77 350 (21) 560 (33) 200 (12) 250 (15)

Vane 50x98 300 (18) 500 (30) 150 (9) 250 (15)

Vane 50x150 80 (4.8) 120 (7.2) 40 (2.4) 60 (3.6)


9 Vane 50x250 30 (1.8) 50 (3) 15 (0.9) 25 (1.5)

Vane 98x98 100 (60) 150 (9) 50 (3) 75 (4.5)

Vane 98x150 30 (1.8) 50 (3) 15 (0.9) 25 (15)


Vane 98x250 20 (1.2) 30 (1.8) 15 (0.9) 15 (0.9)

10 Hinged vane 98x200 b=37 double sided 70 (4.2) 100 (60) 35 (2.16) 50 (3)
Hinged vane 98x200 b=28 double sided 100 (60) 150 (9) 50 (3) 75 (4.5)
Hinged vane 98x100 b=37 single sided 200 (12) 300 (18) 100 (60) 150 (9)
Hinged vane 98x100 b=28 single sided 300 (18) 500 (30) 150 (9) 250 (15)
The above mentioned data is a guideline and is for loose, non compacted material.
11 During the filling the bulk density can change (e. g. for fluidised material).
*For versions with option 26 (heating of housing) the above mentioned data must be multiplied by 1.5.

12
page 28 gi011015 RN 3000 / 6000
1
Rotonivo ® Level limit switch
Series RN 3000 / 6000
Technical information / Instruction manual
Maintenance

Opening the lid (cover) Before opening the lid for maintenance reasons observe following items:
2
• Do not remove the lid while circuits are live.
• No dust deposits or whirlings are present.
• No rain can enter into the housing.

Frequent check of the To ensure durable safety in hazardous locations and with electrical safety, following items must be
unit checked frequently depending on the application:
• Mechanical damage or corrsion of any components (housing side and sensor side) and of the field 3
wiring cables.
• Thight sealing of the process connection, cable glands and enclosure lid..
• Properly connected external PE cable (if present).

Cleaning If cleaning is required by the application, following must be observed:


• Cleaning agent must comply with the materials of the unit (chemical resistance). Mainly the shaft
sealing, lid sealing, cable gland and the surface of the unit must be considered. 4
The cleaning process must be done in a way, that:
• The cleaning agent cannot enter into the unit through the shaft sealing, lid sealing or cable gland.
• No mechanical damage of the shaft sealing, lid sealing, cable gland or other parts can happen.

A possible accumulation of dust on the unit does not increase the maximum surface temperature and
must therefore not be removed for purposes of maintaining the surface temperature in hazardous 5
locations.

Function test A frequent function test may be required depending on the application.
Observe all relevant safety precautions related with a safe work depending on the application (e.g.
hazardous locations, hazardous bulk material, electrical safety, process pressure).

This test does not proof if the sensor is sensitive enough to measure the material of the application. 6
Function test is done by stopping the rotating paddle with appropriate means and monitor if a correct
change of the signal output from uncovered to covered happens.

Production date The production date can be traced by the serial number on the typeplate. Please contact the
manufacturer or your local distrubutor.
7
Spare parts All available spare parts are stated in the selection list.

10

11

12
RN 3000 / 6000 gi011015 page 29
1
Rotonivo ® Level limit switch
Series RN 3000 / 6000
Technical information / Instruction manual
Notes for use in Hazardous Locations
2 Zone classification
Useable in zone ATEX IEC-Ex / INMETRO
Category Equipement Protection
Level (EPL)
Dust applications 20, 21, 22 1D Da
3 21, 22
22
2D
3D*
Db
Dc *) in case of conductive dust
Gas applications 0, 1, 2 1G Ga additional requirements for
1, 2 2G Gb the installation are necessary.
2 3G Gc

4 General Notes

Marking Devices with Ex approval are marked on name plate.

Process pressure The device construction allows process over-pressure up to 0.8/5/10 bar (11.6/73/145psi) (see name
plate). These pressures are allowed for test purposes. The definition of the Ex approvals are only
5 valid for a container-over-pressure between -0.2..+0.1 bar (-2.9..+1.45psi).
For higher or lower pressures the approvals are not valid.

Process and ambient The permitted temperature ranges are marked on the name plate.
temperature

6
Permitted zones for mounting in partition wall

RN 3000 RN 6000 RN 6000 RN 6000


Standard Standard de-housing d-housing
7 housing housing

Version with Version


d- and de-housing with
(flameproof / Standard
8 increased safety) housing

EPL *
Gb Db Db

Category ** 2G 2D 2D
Zone 1 21 21
9
EPL *
Gb Da Da

Category **
2G 1D 1D
RN 3001
Zone 1 20 20 RN 6001
10
* for IEC-Ex / INMETRO
RN 3003
** for ATEX
RN 6003

RN 3002
RN 3004
11 RN 6002
RN 6004
RN 3002-rope
RN 6002-rope

12
page 30 gi011015 RN 3000 / 6000
1
Rotonivo ® Level limit switch
Series RN 3000 / 6000
Technical information / Instruction manual
Notes for use in Hazardous Locations

Max. Surface Temperature and Temperature Code 2

The temperature marking on the name plate refers to the instruction manual.
In the following tables the relevant temperature ratings are shown.

The maximum surface temperature (resp. temperature class) is the warmest temperature of the unit which could occur during
malfunction (according to Ex-definition). 3

Enclosure directly mounted to the process connection 4


Temperature Temperature
Max. ambient Max. process Max. surface
class class
temperature* temperature temperature
(Division system) (Zone system)
90°C (194°F) T5 T5 Ambient side
30°C (86°F) 50°C (122°F)
120°C (248°F) (1) T4A (1) T4 (1)
100°C (212°F) T5
40°C (104°F) 60°C (140°F)
120°C (248°F) (1) T4A (1)
T4 Process side 5
110°C (230°F)
50°C (122°F) 70°C (158°F) T4A T4
120°C (248°F) (1)
RN3000:
60°C (140°F)
80°C (176°F) 120°C (248°F) T4A T4
RN6000:
50°C (122°F)
*Ambient temperature derating see page 12 6

Enclosure mounted offset to the process connection


Temperature Temperature
Max. ambient Max. process Max. surface
class class
temperature temperature temperature
(Division system) (Zone system)
90°C (194°F) 120°C (248°F) T4A T4 7
100°C (212°F) 120°C (248°F) T4A T4
110°C (230°F) 120°C (248°F) T4A T4
120°C (248°F) 120°C (248°F) T4A T4
130°C (266°F) 130°C (266°F) T4 T4
140° C (284°F) 140° C (284°F) T3C T3
8
150° C (302°F) 150° C (302°F) T3C T3
RN3000: Ambient side
160° C (320°F) 160° C (320°F) T3C T3
60°C (140°F)
170° C (338°F) 170° C (338°F) T3A T3
RN6000:
50°C (122°F) 180° C (356°F) 180° C (356°F) T3A T3 Process side
190° C (374°F) 190° C (374°F) T3 T3
200° C (392°F) 200° C (392°F) T3 T2 9
210° C (410°F) 210° C (410°F) T2D T2
220° C (428°F) 220° C (428°F) T2C T2
230° C (446°F) 230° C (446°F) T2C T2
240° C (464°F) 240° C (464°F) T2B T2
250° C (482°F) 250° C (482°F) T2B T2
10
(1)
With use of electronic "Universal voltage"

11

12
RN 3000 / 6000 gi011015 page 31
1
Rotonivo ® Level limit switch
Series RN 3000 / 6000
Technical information / Instruction manual
Disposal
2 The product consists of materials which can be recycled, details of the used materials see chapter "Technical data - mechanical
data". Recycling must be done by a specialised recycling company.