RECONECTADOR Pomanique
RECONECTADOR Pomanique
RECONECTADOR Pomanique
ZXVacuumAutoRecloser
15.5kV,27kVand38kV
Introduction & Benefits
Pomanique’s ZX-Series three-phase, Controlled Arc Fault Venting ability
electronically controlled, vacuum- - Adoptvacuuminterrupters,thereclosercanquenchtheAcrfault
interrupting distribution automation switch
Withinveryshorttime.
provides reliable, economical switching,
sectionalizing, advanced metering, and - TheAFVrecognizesless-than-criticalinstantaneousovercurrent,so
automation systems for distribution duringthedesignofRecloser,thearcfaultcontainmentandventing
circuits rated up to 38 kV. hasbeenamandtoryrequirement.
Switch operations are programmed in an - By control of speed of open operation to at least 1.2m/s,the recloser
electronic control with accurate interrupter can vent the arc fault effectively.
characteristics and a host of advanced
-
features. When system requirements
change, program settings are easily High reliability
altered with no sacrifice of accuracy or ― Pomaniquedesignedasimple,magneticallyactuatedoperating
consistency. mechanismthatcoulddependablyoperatewithonlyonemovingpart.
― VacuuminterruptertechnologymakeZXrecloserwithmaximum
Pomanique’s reclosers meet all the
reliabilityandminimalmaintenance.
requirements for outdoor use in
accordance with the IEEE C37.60 and
IEC 62271-111.
─ 1 ─
Switch unit description
Recloser principle
Reclosersareusedinoverheadlinesandinsubstations.Likecircuit-breakers
theyarecapableofswitchingnormalandfaultcurrents.Theyareequipped
withsensorsandcontrollerbeingtheprotectionandcontroldevice.Incase
of a temporary line fault, they can trip and reclose up to four times, thus
avoidinglongernetworkinterruptions.
Recloser cycle
Incaseofanetworkfault,therecloseropensandreclosesseveraltimes.In
case of temporary faults, the automatic reclosing significantly reduces the
outage times. While the trip settings for each operation can be set
individually.
Design of switch unit
Each vacuum interrupter is embedded in a solid-insulated pole made of
weather-proof cycloaliphatic epoxy-resin. The vacuum interrupter is
verticallymountedinsidethepole,providingalongservicelife.Eachpoleis
equipped with an integrated current transformer and a resistive voltage
sensor.
Operating mechanism
The recloser is operated by a magnetic actuator,the actuator is a bi-stable
system, locked in the end positions by permanent magnets.If not in
operation,themagnetcoilsdonotconsumeanypower.
The operating mechanism housing is made of stainless steel for outdoor
applications.italsoaccommodatesthepositionindicatorandamechanical
operationscounter.
Lockouthandle-pushin
Mechanical lockout (closeposition)
The recloser can be tripped manually. If the handle is pulled, the recloser
opens and is simultaneously locked out electrically and mechanically. The
handlestaysextended,thusindicatingtheinterlockedstate.
To close the recloser again, the handle must first be pushed back to the
operationpositioninordertoreleasethelockout.Thenthereclosercanbe
closedelectricallyviathecontroller.
Lockouthandle-pulled
(openposition)
— 2 —
Controller description
Controller)78R200
TheMicroprocessorBasedcontroller FTU-R200provideprotection,control,
instrumentation and metering with integrated input and output logic, data
logging&faultreports.
Communication access to controller functionality is via electrical RS485 port
for remote connection. Additional rear port options including RS232 port is
available.
Thecontrollerismountedinthecontrolcubicle.Alongwiththecontroller,this
cubicle also contains the auxiliary power supply with batteries for
uninterruptiblepowersupply,electronicboardsandcircuitbreakers.
The controller contains a large number of protection functions (elements)
whichcanbeselectedordeselectedthroughthemenudrivendisplay.
Enhanced features
― Analysisofcurrent/voltagenormal&negativesequenceforpowerquality
monitoring.
― RecordingofPQMwithfaultwaveformof128samplingand20cycles.
― Harmonicsanalysisofelectricdata.
― MonitoringofSag,Swell,Interruption,over&lowvoltage,unbalanceand
etc.
― Improvementoffaultdetectionalgorithm.
― Automaticisolationoffaultedsectionsiteandinterconnectionwithother
healthysection.
― Improvedmeasuringaccuracy
― Multi-Protocol support. (DNP3.0, MODBUS,IEC60870-5-101/104
― Userprogrammablelogic(PLC)support.
Cubicle
The cubicle includes the complete electronics, the protection relay and the
UPS system of the recloser. Additional components and features can be
selectedviaorder.
— 3 —
General Protection Features
Ground-HCTPickupLevel:25~10000A(step:1A)
Ground-HCTAdder:0.01~2(step:0.01sec)
— 4 —
General Protection Features
Recording Commmunication Interface
Events RS 232C #1
Totallymorethan32,000eventsarestoredandlisted. On FRTU left-side (inside the inner door)
I/Oevents(1024)/Functionalevents(30000)/System SCADAorDASystemCommunicationInterface
events(256) ThroughCable/Wireless/FiberOpticModems
Faultevents(256)/PQMevent(256)/DemandprofileI,P,Q Functions
(6144)/Maximumdemandprofile(1024) RemoteOperation(Control,StatusMonitoring,
Fault Waveform Tele-metering)
Upto4faultsarestored.(32samples/cycle,240 RemoteSetting(optional)
cycles/record) FileTransfer(Event&FaultData;DNPprotocolonly)
GraphicalDisplayinAnalysisTool:Ia,Ib,Ic,In,Va,Vb,Vc Protocols
Load Profiling DNP3.0(Level2)orIEC60870-5-101(optional)
Demand&DailyMaximumCurrent:Ia,Ib,Ic,In Baud Rate
Demand&DailyMaximumPower:kW,kVAR(A/B/C/3-ph) 1200~19200bps
AveragingInterval:5/10/15min Address
GraphicalDisplayinAnalysisTool MasterAddress:0~65534
SlaveAddress:0~65534
Local / Remote : Control Position (only locally changeable)
Open/Close : Switch Body Status Change Command RS 232C Port #2
DO (Direct Operate) and SBO (Select Before Operate) On FRTU Front Panel
are supported. Setting&Configuration,Maintenance,RecordedData
Reset : Annunciator Manual Reset Command AnalysisThroughSetting&AnalysisTool
Battery Test : Battery & Charger Circuit Check Functions
Protection Function Blocking SettingandConfigurationChange(BatchJob)
User Configurable DO Points (reserved) : 2 ProtocolMonitor(CommunicationFrameCheck)
Real-timeDisplay:MeasurementandStatusData
Others EventListandFaultOscillograph
DemandLoadProfiling&GraphicalDisplay
RTC (Real Time Clock) : YYYY/MM/DD hh:nn:ss
FRTUFirmwareDownload
SOE (Sequence of Event) Time Resolution : 1 msec
Protocols
Digital Filtering & Dead-band Setting for Analog Inputs
Modbus
Calibration (Correction Factor) : Factory Setting only
Baud Rate
Ia, Ib, Ic, In, Va, Vb, Vr, Vs, Vt
1200~19200bps
Factor Magnitude: 0.500~1.500
Connector Type
Phase Angle: 0.000~359.9°
DB9Female
— 5 —
ZX15-800-16H TECHNICAL DATA
Technical data
Clearance, phase-to-phase
Rated continuous current
Impedance μΩ between
connections
closing time
voltage
current
Weight
earth
earth
Ir Tk Isc Ima Up Ud
A s kA kA kV kV μΩ mm mm mm kg A A ms
ZX15-630-12-N 630 3 12.5 31.5 110 50 50 850 320 270 130 2 10 60/60
ZX15-800-12-N 800 3 12.5 31.5 110 50 50 850 320 270 130 2 10 60/60
27kV
Ir Tk Isc Ima Up Ud
50/60Hz
A s kA kA kV kV μΩ mm mm mm kg A A ms
ZX27-630-12-N 630 3 12.5 31.5 125 60 50 850 320 270 140 5 25 60/60
ZX27-800-12-N 800 3 12.5 31.5 125 60 50 850 320 270 140 5 25 60/60
38kV
Ir Tk Isc Ima Up Ud
50/60Hz
A s kA kA kV kV μΩ mm mm mm kg A A ms
ZX38-630-12-N 630 3 12.5 31.5 170 70 50 1290 320 350 150 5 40 60/60
ZX38-800-12-N 800 3 12.5 31.5 170 70 50 1290 320 350 150 5 40 60/60
-7-
Dimension drawings
A B C D E F
15.5kV mm 460 380 850 508 270 970
27kV mm 460 380 850 508 270 970
38kV mm 512 380 970 590 270 970