Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

MM30 Manual - en 00154

Download as pdf or txt
Download as pdf or txt
You are on page 1of 30

Doc.

N° MO-0015-ING
Rev. 4
MM30 Pag. 1 of 30

MICROPROCESSOR
MOTOR PROTECTION RELAY

TYPE

MM30
OPERATION MANUAL

> St.No I< Is>

ROTOR I>> START


STALL INHIBIT

MICROELETTRICA SCIENTIFICA
MILANO ITALY

MODE SELECT +
MULTIFUNCTION
MOTOR PROTECTION
RELAY TYPE -
MM30 PROG.

ENTER/RESET

Copyright 2010 Microener


Doc. N° MO-0015-ING
Rev. 4
MM30 Pag. 2 of 30

INDEX
1 General utilization and commissioning directions___________________________________________ 3
1.1 Storage and transportation____________________________________________________________ 3
1.2 Installation________________________________________________________________________ 3
1.3 Electrical connection________________________________________________________________ 3
1.4 Measuring inputs and power supply_____________________________________________________ 3
1.5 Outputs loading____________________________________________________________________ 3
1.6 Protection earthing__________________________________________________________________ 3
1.7 Setting and calibration_______________________________________________________________ 3
1.8 Safety protection___________________________________________________________________ 3
1.9 Handling__________________________________________________________________________ 3
1.10 Maintenance_______________________________________________________________________ 4
1.11 Fault detection and repair_____________________________________________________________ 4
2 General characteristics and operation_____________________________________________________ 4
2.1 Power supply______________________________________________________________________ 4
2.2 Operation an Algorithms______________________________________________________________ 5
2.2.1 Reference input variable_________________________________________________________ 5
2.2.2 Input quantities_________________________________________________________________ 5
2.2.2.1 Mains Frequency_________________________________________________________ 5
2.2.2.2 Phase current input________________________________________________________ 5
2.2.2.3 Earth Fault current input____________________________________________________ 6
2.2.3 Function and Setting____________________________________________________________ 7
2.2.3.1 F49 – Thermal image______________________________________________________ 7
2.2.3.2 F51LR – Locked Rotor Protection (Rotor jam)___________________________________ 8
2.2.3.3 F46 – Current Unbalance (Negative Sequence current) protection___________________ 8
2.2.3.4 F37 – No-Load Running protection____________________________________________ 8
2.2.3.5 F51 – Overcurrent protection________________________________________________ 9
2.2.3.6 F64 – Earth Fault protection_________________________________________________ 9
2.2.3.7 Limitation of the Stats Number_______________________________________________ 9
2.2.3.8 Starting Sequence control__________________________________________________ 10
2.2.3.9 Autosetting______________________________________________________________ 10
3 Controls and measurements_____________________________________________________________ 11
4 Signalization__________________________________________________________________________ 12
5 Output relays__________________________________________________________________________ 13
6 Serial communication___________________________________________________________________ 13
7 Digital inputs _________________________________________________________________________ 14
8 Test__________________________________________________________________________________ 14
9 Keyboard and display operation__________________________________________________________ 15
10 Reading of measurements and recorded parameters_________________________________________ 16
10.1 ACT. MEAS (Actual measure)______________________________________________ 16
10.2 MAX VAL (Max values)__________________________________________________ 16
10.3 EVENT RECORDING (Last trip)____________________________________________________ 17
10.4 TRIP NUM (Trip number)_________________________________________________ 17
11 Reading of programmed settings and relay’s configuration____________________________________ 17
12 Programming__________________________________________________________________________ 18
12.1 Programming of functions settings____________________________________________________ 18
12.2 Programming the configuration of output relay___________________________________________ 20
13 Manual and automatic test operation______________________________________________________ 21
13.1 W/O TRIP_______________________________________________________________________ 21
13.2 WithTRIP________________________________________________________________________ 21
14 Maintenance___________________________________________________________________________ 21
15 Power frequency insulation test__________________________________________________________ 21
16 Electrical characteristics________________________________________________________________ 22
17 Connection diagram (Standard Output)_____________________________________________________ 23
17.1 Connection Diagram (Double Output)__________________________________________________ 23
18 Wiring the serial communication bus______________________________________________________ 24
19 Change phase current rated input 1A or 5A_________________________________________________ 24
20 Thermal Image curves__________________________________________________________________ 25
21 Inverse time unbalance protection element_________________________________________________ 26
22 Direction for pcb’s draw-out and plug-in___________________________________________________ 27
22.1 Draw-out________________________________________________________________________ 27
22.2 Plug-in__________________________________________________________________________ 27
23 Overall dimensions / Mounting___________________________________________________________ 28
24 Keyboard operational diagram___________________________________________________________ 29
25 Setting’s form_________________________________________________________________________ 30

Copyright 2010 - Microener


Doc. N° MO-0015-ING
Rev. 4
MM30 Pag. 3 of 30

1. General utilization and commissioning directions

Always make reference to the specific description of the product and to the Manufacturer's instruction.
Carefully observe the following warnings.

1.1 - STORAGE AND TRANSPORTATION,

must comply with the environmental conditions stated on the product's instruction or by the applicable
IEC standards.

1.2 - INSTALLATION,

must be properly made and in compliance with the operational ambient conditions stated by the
Manufacturer.

1.3 - ELECTRICAL CONNECTION,

must be made strictly according to the wiring diagram supplied with the Product, to its electrical
characteristics and in compliance with the applicable standards particularly with reference to human
safety.

1.4 - MEASURING INPUTS AND POWER SUPPLY,

carefully check that the value of input quantities and power supply voltage are proper and within the
permissible variation limits.

1.5 - OUTPUTS LOADING,

must be compatible with their declared performance.

1.6 - PROTECTION EARTHING

When earthing is required, carefully check its efficiency.

1.7 - SETTING AND CALIBRATION

Carefully check the proper setting of the different functions according to the configuration of the
protected system, the safety regulations and the co-ordination with other equipment.

1.8 - SAFETY PROTECTION

Carefully check that all safety means are correctly mounted, apply proper seals where required and
periodically check their integrity.

1.9 - HANDLING

Notwithstanding the highest practicable protection means used in designing M.S. electronic circuits,
the electronic components and semiconductor devices mounted on the modules can be seriously
damaged by electrostatic voltage discharge which can be experienced when handling the modules.
The damage caused by electrostatic discharge may not be immediately apparent but the design
reliability and the long life of the product will have been reduced. The electronic circuits reduced by
M.S. are completely safe from electrostatic discharge (8 KV IEC 255.22.2) when housed in their
case; withdrawing the modules without proper cautions expose them to the risk of damage.

Copyright 2010 - Microener


Doc. N° MO-0015-ING
Rev. 4
MM30 Pag. 4 of 30

a. Before removing a module, ensure that you are at the same electrostatic potential
as the equipment by touching the case.

b. Handle the module by its front-plate, frame, or edges of the printed circuit board.
Avoid touching the electronic components, printed circuit tracks or connectors.

c. Do not pass the module to any person without first ensuring that you are both at
the same electrostatic potential. Shaking hands achieves equipotential.

d. Place the module on an antistatic surface, or on a conducting surface which is at


the same potential as yourself.

e. Store or transport the module in a conductive bag.

More information on safe working procedures for all electronic equipment can be found
in BS5783 and IEC 147-OF.

1.10 - MAINTENANCE

Make reference to the instruction manual of the Manufacturer ; maintenance must be carried-out by
specially trained people and in strict conformity with the safety regulations.

1.11 - FAULT DETECTION AND REPAIR

Internal calibrations and components should not be alterated or replaced.


For repair please ask the Manufacturer or its authorised Dealers.

Misapplication of the above warnings and instruction relieves the Manufacturer of any liability.

2. GENERAL CHARACTERISTICS

Input currents are supplied to 3 current transformers: - two measuring phase current (the third current is
computed as vector sum of the two others) - one measuring the earth fault zero-sequence current.
Phase current rated input can be 1 or 5A (Selectable by movable bridges an relay card)
For zero-sequence current taps for 1A and 5A input are provided on relay's terminal board.
Make electric connection in conformity with the diagram reported on relay's enclosure.
Check that input currents are same as reported on the diagram and on the test certificate.
The auxiliary power is supplied by a built-in interchangeable module fully isolated an self protected.

2.1 - POWER SUPPLY

The relay can be fitted with two different types of power supply module :

24V(-20%) / 110V(+15%) a.c. 80V(-20%) / 220V(+15%) a.c.


a) -  b) - 
24V(-20%) / 125V(+20%) d.c. 90V(-20%) / 250V(+20%) d.c.

Before energising the unit check that supply voltage is within the allowed limits.

Copyright 2010 - Microener


Doc. N° MO-0015-ING
Rev. 4
MM30 Pag. 5 of 30

2.2 – Operation and Algorithms

2.2.1 – Reference input variables

Display Description Setting Range Step Unit


NodAd 1 Identification number for connection serial communication 1 - 250 1 1
Fn 50 Hz Mains frequency 50 - 60 10 Hz
In 500Ap Rated primary current of the phase C.Ts. 1 - 9999 1 A
Rated primary current of the C.Ts. or of the tore C.T.
On 500Ap 1 - 9999 1 A
detecting earth fault current
Im 1.0In Motor full-load current (p.u. of phase C.Ts. rated current) 0.1 – 1.5 0.01 In
Ist 6Im Motor start-up current (p.u. of motor full load current) 0.5 – 10 0.1 Im
tst 5s Motor starting time 1 – 120 1 s
Switch-over current of motor starter
Itr0.5Ist Dis – 0.1 – 1 0.1 Ist
(p.u. of motor starting current)
tTr 6s Max switch-over time from start-up 0.5 – 50 0.1 s

2.2.2 – Input quantities

2.2.2.1 – Mains Frequency

The relay can operate either in 50Hz or 60Hz systems.


The rated Mains Frequency “ Fn “ must be set accordingly.

2.2.2.2 – Phase Current inputs

The relay directly displays the r.m.s. value of the Phase Currents “ IA “, “ IB ”, “ IC ” flowing in the
Primary of the input Current Transformers and refers all its measurements to that value.
To make the relay properly working with any C.T., when programming the relay settings we have
to input the value of the Rated Primary Current “ In “ of the phase C.Ts.
Only phase A and C currents are measured, whereas the current of the phase B is computed as
vector summation of the currents of the other two phases.
The algorithm is based on the following considerations coming from well-known vector relations
among the three-phase currents and the zero sequence current.
- In any circumstance – currents balanced or not, sinusoidal or not – it is always true that:

1 IA  IB  IC  I0  0

- When no Earth Fault exists (I0 = 0)

2 
IA  IB  IC  0  IB  IA  IC 
The earth fault protection element is independently supplied by the residual current coming either
from the residual connection of the 3 system C.Ts. or from the core balance C.T.

If any Earth Fault is experienced (I0  0) the Earth Fault Protection Element trips independently
from the phase current measuring elements.
If no Earth Fault is present (I0 = 0), the equation (2) is valid, no matter if currents are balanced or
not, sinusoidal or not.
The third phase current is calculated, in real time, as vector summation of the other two-phase
currents

Copyright 2010 - Microener


Doc. N° MO-0015-ING
Rev. 4
MM30 Pag. 6 of 30

Similarly, the Positive Sequence Current Component “ Id “ and Negative Sequence component
“ Is “, with no Earth Fault, are computed according to the normal equations of the system
symmetrical components, using two currents only:


I A  Id  Is  
I C  α I A  Is α  α

2



Is 3  I C  I A e j120
 
I C  α Id  α Is 
 2
I C  α I A  Id α  α
2

2



Id 3  I C  I A e j120

In case of Earth Fault the Earth Fault Element trips before tripping of the unbalance element.
- During Faults

A) Single phase to earth Fault

Trip of the earth fault element directly measuring the Residual Current.

B) Two Phase Fault

In any case one of the currents directly measured is involved, so the relay trips correctly.

C) Two Phase to Earth Fault

Same as A + B

D) Three Phase Fault

All the three currents are correctly measured (in any case two directly).

2.2.2.3 – Earth Fault Current Input

Same as for the Phase Currents, the relay directly displays the r.m.s. value of the Zero Sequence
Residual Current flowing at the Primary of the Current Transformers.
If the input of the Earth Fault element is supplied by the residual connection of the 3 phase C.Ts.,
we shall set for “On” the same value as “In”.
If the input of the Earth Fault elements is supplied by a separated Core Balance C.T., or by
another CT, “On” value will be the Rated Primary Current of this C.T., normally different from “In”.

The rated Secondary Current of the C.Ts. can be either 1A or 5A.


For the Phase Current inputs, 1A or 5A configuration can be selected by moving the jumpers J1
and J2 provided on the C.T. input card (See § 19).
For the earth Fault current input 1A and 5A taps are provided on relays terminals board: 1A or 5A
configuration is obtained connectively to terminals 32-33 or 32-31 (See connection Diagram § 16)
Example :

 Phase CTs 1500/5A and Core Balance CT 100/1A


 Load In = 1500A and On = 100A
 Configure CT input card with jumpers J1, J2 in the 5A position.
 Connect Earth Fault input to terminals 32-33

Copyright 2010 - Microener


Doc. N° MO-0015-ING
Rev. 4
MM30 Pag. 7 of 30

2.2.3 – Functions and Settings

2.2.3.1 – F49 – Thermal Image (See curves § 20)

The current “ I “ producing motor warming-up is computed as a conventional composition of


Positive Sequence “ Id “ and Negative Sequence “ Is “ components of the motor current.

- Computed current: I  Id2  3Is2

- Allowed overloading time (See Curve § 19)

The trip time delay “ t “ of the thermal element, depends on the warming-up time constant
“ tm “ of the motor, on the previous thermal status (Ip), on the admissible continuous overload
(Ib) and, of course, on the actual load (I)

 (I/Im) 2  (Ip/Im)2 
t  tm In  2
 (I/Im)  (Ib/Im) 
2

tm = (1-60)min.
I = computed current
Ip = preheating current
Ib = continuously admissible current (1-1.3)Im, step 0.01Im
Im = motor rated current (0.1-1.5)In, step 0.1In

- Steady motor cooling-down time constant: to = (1-10)tm, step 1tm

The cooling-down time constant of the motor when running is “tm”; it is automatically changed
to " to " when the motor current drops below 0.1 lm (running/steady motor discrimination
level).

- Thermal prealarm : Ta/n = (50-110)%Tn, step 1%Tn

An alarm signal is issued when the simulated warming exceeds the set percentage of the
motor rated temperature Tn.
Automatic 1% drop out percentage.

- Restart inhibition: Ts/n = (40-100)%Tn, step 1%Tn

To inhibit a new motor starting before cooling down to 99% Ts/n, reset after tripping of the
thermal element takes places when T< 0.99[Ts].

Copyright 2010 - Microener


Doc. N° MO-0015-ING
Rev. 4
MM30 Pag. 8 of 30

2.2.3.2 – F51LR – Locked Rotor Protection (Rotor jam)

At motor starting this function is disabled for the set time “ 2tSt “ : when this time has elapsed, if
current exceeds the set level “ ILR ”, the relay trips with a delay of “ tLR ” sec.

- Current level :

ILR = (1-5)Im, step 0.1Im. lf ILR = DIS. the function is disactivated.


tLR = (1-25)s, step 1s

- Inhibition time of the locked rotor function:

2tSt
tSt = (1-120)s, step 1s = motor start-up time

2.2.3.2 - F46 - Current Unbalance (Negative Sequence Current) protection (See curve 21)

Besides its contribution to the thermal image algorithm, current unbalance also controls another
inverse time element

-Minimum Negative Sequence current operation level

Is> = (0.1-0.8)Im, step 0.1lm. lf ls> = DIS. the function is disactivated.

- Time current curve

tIs> = (1-8)s, step 1s


0.9
Actual trip time delay is given by: t tIs  (tIs  trip time at Is  Im)
Is/Im  0.1
“ Is ” is the actual Negative Sequence Current

2.2.3.4 - F37 - No-Load Running protection

This function performs the protection against no-load running: it is activated by motor under
current.

- Under current level

I< = (0.15-1)Im, step 0,01Im. lf I< = DIS. the function is disactivated.

When current is below 0.1lm in all phases the function is activated.

- Trip time delay:

tI< = (0.1-90)s, step 0.1s.

Copyright 2010 - Microener


Doc. N° MO-0015-ING
Rev. 4
MM30 Pag. 9 of 30

2.2.3.5 - F51 - Overcurrent protection

- Minimum Pick-up Current level in at least one phase :

I> = (1-5)Ist, step 0.1 Ist (limited to 20 times In)


Ist (motor locked rotor current) = (0.5-10)Im, step 0.1Im
lf I> = DIS. the function is disactivated

- Trip time delay

tI> = (0.05-1)s, step 0,01s.

Any of the output relays can be associated to the time delayed element “tI>” as well as to the
instantaneous element “I>” of this function for signalling or for blocking other relays. The
output relay controlled by the I> level remains energized for the time tI> + tBO.
After this delay the relay it is anyhow reset.

tBO = (0.05-0.5)s, step 0.05s.

2.2.3.6 - F64 - Earth Fault protection

- Minimum Pick-up Zero Sequence Residual Current level :

O> = (0.02-2)On, step 0.01On. lf O> = DIS. the function is disactivated.

- Trip time delay:

tO> = (0.05-5)s, step 0.01s.

As for function F51, any of the output relays can also be associated to the instantaneous
element of “O>” level.

2.2.3.7 - Limitation of the Starts Number

- Allowed Number of startings:

St No = (1-60), step 1 lf St No = DIS the number of startings is unlimited.

- Time interval in which the StNo is counted:

tStNo = (1-60)min. step 1 min.


lf during the time “tStN” the “StNo” is attained, a new start is inhibited for the time tBst.

- Restart Inhibition time:

tBst = (1-60)min., step 1min.

On the set tBst= 0 the inhibition is disactivated


On the set tBst= Rm the inhibition is permanent until the RESET key is operated.

Copyright 2010 - Microener


Doc. N° MO-0015-ING
Rev. 4
MM30 Pag. 10 of 30

2.2.3.8 - Starting Sequence Control

During start-up of the motor, the unit can control an output relay used to operate the switch-over of
motor starter (star-delta, resistance or impedance, autotransformer, etc...) thus allowing to
automatically manage the starting transition by controlling the following parameters:

- Switch-over (transition) current:

ITr = (0.1-1)Ist, step 0.1Ist

- Maximum switch-over (transition) time delay:

tTr = (0.5-50)s, step 0.1s.

At motor start counting of tTr begins. If during tTr the motor current drops below ltr,
switching-over is operated; if motor current stays above ltr longer than tTr, the Locked Rotor
element is activated.

2.2.3.9 - Autosetting

The complexity of properly set a motor protection, frequently produces undesired tripping or
non-operation of some of the functions.
The relay MM30 can automatically select the best setting of the parameters according to motor
and system basic data. These data are:

- System frequency = Fn = 50 o 60 Hz
- Rated primary current of phase C.Ts. = In = 0-9999 A step 1A
- Rated primary current of earth fault C.T = On = 0-9999 A step 1A
- Motor rated current = lm = 0.1-1.5 In step 0.01In
- Motor starting current = lst = 0.5-9.9 Im step0.1 Im
- Starting time = tst = 1-120 s step 1s
- Transition current level = ITr = 0.11 Ist step 0.1 Ist
- Transition time = tTr = 0.5-50 s step 0,1s

Once these settings have been programmed, the “AUTOSET” function can be activated by the key
"ENTER" and all the parameters are computed and automatically set at values suitable for a
normal duty of the motor.
Particularly the motor warming-up time constant “tm” is computed so that the motor, when stopped
after having run continuously at Rated Power (Rated current Im), can be immediately restarted at
least one time.
The parameters can anyhow be manually modified if different setting is needed.

Copyright 2010 - Microener


Doc. N° MO-0015-ING
Rev. 4
MM30 Pag. 11 of 30

3. CONTROLS AND MEASUREMENTS

Five key buttons allow for local management of all relay's functions.
A 8-digit high brightness alphanumerical display shows the relevant readings (xxxxxxxx)
(see synoptic table fig.1)
FIG.1
MODE SELECT + - ENTER

ACT MEAS Actual measurement values

MAX VAL. Max. values measured


MEASURES Scanning of
LASTTRIP Values measured at last tripping the menus by
Measurements
N° of tripping for each function the key
display TRIP NUM
“+” “-”

SETTINGS Display of setting


SET DISP
FRELAY Display of configuration of output relay
Setting Program
display Paramater scanning
by the key
(*) PRO SELECT
SETTINGS Setting of parameters
PROGR G Parameter modification
FRELAY Configuration of output relays by the key “+” “-”
Set Programming
Set validation
by the key ENTER

W/O TRIP Test with operation of signals


TEST PRG only
Test activation
WithTRIP Test with operation of signals and output by the key ENTER
Functional Test
(*) relays
(*) Enabled only if input current is zero

Pressing this button progressively


The + and - buttons are used to
selects between
select the actual measurement or
Measurements Display,
display desired when in
Setting Display, Programming,
Measurements Display or Settings
and Test modes
Display modes. When in Program
MODE SELECT + mode, these buttons increase or
The SELECT button chooses decrease the value of the
which category of values within the displayed setting.
chosen mode to display
-
PROG. When in Program mode, and when
When in Program mode, this
all input currents are zero,
button stores the newly selected
pressing this recessed button
value. If not in Program mode and ENTER/RESET places the relay into active
the relay has tripped, this button
programming mode, allowing any
resets the relay and all output
or all of the relay’s settings to be
contacts. If not tripped, this button
altered.
restores the default display.

Copyright 2010 - Microener


Doc. N° MO-0015-ING
Rev. 4
MM30 Pag. 12 of 30

4. SIGNALIZATIONS

Eight signal leds (normally off) are provided:

a b c d

> StNo I< Is>

ROTOR I>> START


STALL INHIBIT

e f g h

 Flashing when the motor heating T overcomes the set alarm level [Ta].
Red
a) >  Illuminated on over-temperature trip. – Also illuminated on activation of RTD
LED
input.
Red  Illuminated on tripping of the element for limitation of the number of
b) St N°
LED startings.
Red  Flashing as soon as motor current drops below the set level [I<]
c) I<
LED  Illuminated at the end of trip time delay.
Red  Flashing as soon as motor unbalance overpasses the set level [Is>]
d) Is>
LED  Illuminated on trip after delay [tIs>].
Yellow ROTOR  Illuminated on trip of the Locked Rotor element (I>ILR) and/or on activation
e)
LED STALL of the Speed Control input SpC.
Red  Flashing when motor current is above the set level [I>]
f) I>>
LED  Illuminated on trip after delay [tI>].
g) Red  Flashing when earth fault current is above the set level [O>]
LED  Illuminated on trip after delay [tO>].
Yellow START  Flashing when in PROGRAM MODE
h)
LED INHIBIT  Illuminated when relay internal fault is detected.

The reset of the leds takes place as follows:

 Leds a,c,d,f,g  From flashing to off, automatically when the lit-on cause disappears.
 From ON to OFF, by "ENTER/RESET" push button only if the
tripping cause has disappeared.
 Leds b,e  From ON to OFF, by "ENTER/RESET" push button only if the
tripping cause has disappeared.
 Leds h  From flashing or illuminated to off, automatically when the lit-on
cause disappears.

In case of auxiliary power supply failure the status of the leds is recorded and reproduced when power
supply is restored.

Copyright 2010 - Microener


Doc. N° MO-0015-ING
Rev. 4
MM30 Pag. 13 of 30

5. OUTPUT RELAYS

Five output relays are available (R1, R2, R3, R4, R5)

a) - The relays R1,R2,R3,R4 are normally deenergized (energized on trip): these output relays are user
programmable and any of them can be associated to one of the MM30's functions.
One relay eventually associated to instantaneous element of the function 51 or 51N(64), after
pick-up normally drops-out as soon as the tripping cause is cleared (current below the set trip
level).
If the current remains above the trip level longer than the time delay programmed for the same
function, the drop-out of the instantaneous relay is anyhow forced after an adjustable waiting
time [tBO]. (Breaker failure protection control)
The reset after tripping of the relays associated to the time delayed functions takes place
automatically as soon as the pick-up cause is cleared.

b) - The relay R5, normally energized, is not programmable and is deenergized on:
 Internal fault
 Power supply failure
 During the programming

6. SERIAL COMMUNICATION

The relays fitted with the serial communication option can be connected via a cable bus or (with proper
adapters) a fiber optic bus for interfacing with a Personal Computer (type IBM or compatible).
All the operations which can be performed locally (for example reading of measured data and changing
of relay’s settings) are also possible via the serial communication interface.
Furthermore the serial port allows the user to read the demand recording data.
The unit has a RS232 / RS485 interface and can be connected either directly to a P.C. via a dedicated
cable or to a RS485 serial bus, thus having many relays to exchange data with a single master P.C.
using the same physical serial line. A RS485/232 converter is available on request.
The communication protocol is MODBUS RTU (only functions 3, 4 and 16 are implemented).
Each relay is identified by its programmable address code (NodeAd) and can be called from the P.C.
A dedicated communication software (MSCOM) for Windows 95/98/NT4 SP3 (or later) is available.
Please refer to the MSCOM instruction manual for more information Microelettrica Scientifica.

Copyright 2010 - Microener


Doc. N° MO-0015-ING
Rev. 4
MM30 Pag. 14 of 30

7. DIGITAL INPUTS

On request (Optional) are provided three inputs activated when the relevant terminals are shorted:

 R.T. (terminals 1 - 2) : Remote trip control.


Activation of the input R.T. (Terminals 1-2 shorted) produces the
following operation :
 - The output relay associated to the function R.T. is energized
 - The Trip Number Counter R.T. is incremented by 1 unit
 - The event recording is activated and shows “CAUSE: RT”

 SpC (terminals 1 - 3) : Speed switch


The Speed Control input is connected to an external N/O contact which
closes as soon as the motor is running. If the contact does not close
within the set start time [tst] from the moment the motor is energised,
the Locked Rotor function is tripped. The relay and the signal led
associated to ILR are energised, the recording on Last Trip will show
cause SpC and trip N° LR will be increased.
If the Speed Control function is not used, it must be disactivated by
programming the variable [Spc] = OFF (see § 12.1)

 RTD (terminals 1 - 14) : Thermal probe.


This function is enabled by programming the variable
[RTD] = ON (see § 12.1)
If the function is enabled, the input RTD is activated when the
resistance connected to the terminals 1-14 exceeds
the limits 50 > R1-14 > 2900.
This limits respectively correspond to “Shorted Probe” (<50) or to
“Overtemperature” (R>2900) (*)
In this case activation of the input 1-14 (terminals shorted) produces
the following operation:

 - The relay associated to R.T. is energized


 - The Led T> is lit-on.
 - The counter of Trip Number of the function T> is incremented
 - LastTrip recording shows : "CAUSE RTD"

(*) If Pt100 thermal probes are used, calibrated accordingly.


Please specify when ordering!

8. TEST

Besides the normal "WATCHDOG" and "POWERFAIL" functions, a comprehensive program of self-test
and self-diagnostic provides:
 Diagnostic and functional test, with checking of program routines and memory's content, run every
time the aux. power is switched-on: the display shows the type of relay and its version number.
 Dynamic functional test run during normal operation every 15 min. (relay's operation is suspended
for less than  4ms). If any internal fault is detected, the display shows a fault message, the Led
"PROG/IRF" illuminates and the relay R5 is deenergized.
 Complete test activated by the keyboard or via the communication bus either with or without tripping
of the output relays.

Copyright 2010 - Microener


Doc. N° MO-0015-ING
Rev. 4
MM30 Pag. 15 of 30

9. KEYBOARD AND DISPLAY OPERATION

All controls can be operated from relay's front or via serial communication bus.
The keyboard includes five hand operable buttons (MODE) - (SELECT) - (+) - (-) - (ENTER/RESET)
plus one indirect operable key (PROG) (see synoptic table a fig.1):

MODE SELECT +

-
PROG.

ENTER/RESET

when operated it enters one of the following operation modes


a) - White key MODE :
indicated on the display :

Reading of all the parameters measured and of those recorded


MEASURES =
in the memory
Reading of the settings and of the configuration of the output
SET DISP =
relays as programmed.
Access to the programming of the settings and of relay
PROG =
configuration.
TEST PROG = Access to the manual test routines.

When operated it selects one of the menus available in the


b) - Green key SELECT :
actual operation MODE

When operated they allow to scroll the different information


c) - Red key “+” AND “-“ :
available in the menu entered by the key SELECT

d) - Yellow key ENTER/RESET : It allows the validation of the programmed settings


- the actuation of test programs
- the forcing of the default display indication
- the reset of signal Leds.

e) - Indirect key  : Enables access to the programming.

Copyright 2010 - Microener


Doc. N° MO-0015-ING
Rev. 4
MM30 Pag. 16 of 30

10. READING OF MEASUREMENTS AND RECORDED PARAMETERS

Enter the MODE "MEASURES", SELECT the menus "ACT.MEAS"-"MAX VAL"-"LASTTRIP"-


-"TRIP NUM", scroll available information by key "+" or "-" .

10.1 - ACT.MEAS

Actual values as measured during the normal operation.


The values displayed are continuously refreshed.

Display Description
T/Tnxxx% Actual temperature rise displayed as % of the motor full load temperature rise (0 - 999%)
IAxxxxxA True R.M.S. value of the current of phase A displayed as primary Amps. (0 - 99999)
IBxxxxxA As above, phase B.
ICxxxxxA As above, phase C.
IoxxxxxA As above, earth fault current.
Id/mxxx% Positive sequence component of motor current displayed as % of motor full load
current. (0 - 999)%
Is/mxxx% Negative sequence component of motor current displayed as % of motor full load current.
(unbalance degree) (0 - 999)%

NB: If no key is operated within 60 sec. the display is automatically switched to the default indication

10.2 - MAX VAL

Highest values recorded during motor run after the starting time (refreshed at each higher value) plus
highest values recorded during the starting time (refreshed at each new starting).

Display Description
T/Tnxxx% Highest temperature recorded since the start of the run. (0 - 99,9)%
IAxxxxxA Current of phase A measured during run after starting time (0-99999)
IBxxxxxA As above, phase B.
ICxxxxxA As above, phase C.
IoxxxxxA As above, zero sequence current.
Id/mxxx% Positive sequence component of motor current.
Is/mxxx% Negative sequence component of motor current
SAxxxxxA Current of phase A during the starting time.
SBxxxxxA As above, phase B.
SCxxxxxA As above, phase C.
SoxxxxxA As above, earth fault current.
Sd/mxxx% Positive sequence current component during starting time.
Ss/mxxx% Negative sequence current component during starting time.
tStxxxxs Measure of the start time.

Copyright 2010 - Microener


Doc. N° MO-0015-ING
Rev. 4
MM30 Pag. 17 of 30

10.3 – LASTTRIP – Recording of the last five trippings

Display of the function which caused the tripping of the relay and values of the parameters at the
moment of tripping. The memory buffer is refreshed at each new relay tripping.

Display Description
LastTr-x Indication of the recorded event (x= 0 to 4) Example: Last event (LastTr -0)
Last but one event (LastTr-1) etc...
Causexxx Function which caused the last tripping: T>; Is>; I>; O>; I<; LR; StN; ITr.
IAxxxxIn Current of phase A.
IBxxxxIn Current of phase B.
ICxxxxIn Current of phase C.
IoxxxxOn Earth fault current.
Id/mxxx% Positive sequence component of current.
Is/mxxx% Negative sequence component of current.
T/Tnxxx% Motor heating

10.4 - TRIP NUM

Counters of the number of operations for each of the relay functions.


The memory is non-volatile and can be cancelled only with a secret procedure.

Display Description
T> xxxxx Motor overload.
Is>xxxxx Current unbalance.
I> xxxxx Overcurrent.
O>xxxxx Earth fault.
I< xxxxx No load running.
LRxxxxx Locked rotor.
StN>xxxx No of consecutive startings.
ITrxxxxx Too long starting.
RTxxxx Remote trip

11. READING OF PROGRAMMED SETTINGS AND RELAY'S CONFIGURATION

Enter the mode "SET DISP", select the menu "SETTINGS" or "FRELAY", scroll information
available in the menu by keys "+" or "-".
SETTINGS= values of relay's operation parameters as programmed
FRELAY= output relay associated to the different functions as programmed.

Copyright 2010 - Microener


Doc. N° MO-0015-ING
Rev. 4
MM30 Pag. 18 of 30

12. PROGRAMMING

The relay is supplied with the standard default programming used for factory test.[ Values here below
reported ( ----- ) ].
All parameters can be modified as needed in the mode PROG and displayed in the mode SET DISP
Local Programming by the front face key board is enabled only if no input current is detected
(main switch open). Programming via the serial port is always enabled but a password is
required to access the programming mode. The default password is the null string; in the
standard application program for communication “MS-COM” it is also provided an emergency
which can be disclosed on request only.
As soon as programming is enabled, the Led PRG/IRF flashes and the reclosing lock-out relay R5 is
deenergized. Enter MODE "PROG" and SELECT either "SETTINGS" for programming of parameters
or "FRELAY" for programming of output relays configuration; enable programming by the indirect
operation key PROG.
The key SELECT now scrolls the available parameters. By the key (+) , (-) the displayed values can be
modified; to speed up parameter's variation press the key SELECT while "+" or "-" are pressed.
Press key "ENTER/RESET" to validate the set values.

12.1 - PROGRAMMING OF FUNCTIONS SETTINGS

In 500 Ap

In is the 500 is the Ap is the unit of


name of the setting measure, Amps
variable default primary.

Mode PROG menu SETTINGS. (Production standard settings here under shown).
Display Description Setting Range Step Unit
Identification number for connection on serial
NodAd 1 1 - 250 1 1
communication bus
Fn 50 Hz Mains frequency 50 - 60 10 Hz
In 500Ap Rated primary current of the phase C.Ts. 1 - 9999 1 A
Rated primary current of the C.Ts. or of the tore C.T.
On 500Ap 1 - 9999 1 A
detecting earth fault current
Motor full-load current
Im 1.0In 0.1 – 1.5 0.01 In
(p.u. of phase C.Ts. rated current)
Ist 6Im Motor start-up current (p.u. of motor full load current) 0.5 – 10 0.1 Im
tst 5s Motor starting time 1 – 120 1 s
Switch-over current of motor starter
Itr0.5Ist Dis – 0.1 – 1 0.1 Ist
(p.u. of motor starting current)

Copyright 2010 - Microener


Doc. N° MO-0015-ING
Rev. 4
MM30 Pag. 19 of 30

Display Description Setting Range Step Unit


tTr 6s Max switch-over time from start-up 0.5 – 50 0.1 s
AUTOSET? + ENTER Automatic setting of all the following parameters computed on the
base of the setting of the previous parameters
Thermal time constant of motor while running
tm 34min tm is computed to allow at least one restarting with 1 - 60 1 min
the motor at its rated full load temperature
to/tm 3 Steady/running motor thermal time constant 1 - 10 1 1
Prealarm motor heating level
Ta/n 90% 50 - 110 1 %
(% of motor full-load temperature rise)
Ts/n100% Motor restart heating level 40 - 100 1 %
Ib1.05Im Rated maximum continuous current of the motor 1.00 – 1.30 0.05 Im
StNo 6 Max. No of startings allowed within the time tStNo Dis - 1 - 60 1 -
tStNo60m Time into which the StNo is counted 1 - 60 1 m
Restart inhibition time after tripping of the function
tBSt 12m StNo (Rm = restart inhibited until manual RESET is 1 - 60 – Rm 1 min
operated)
ILR 2Im Trip level of Locked Rotor function Dis - 1 - 5 0.1 Im
tLR 1s Trip time delay of LR element during run 1 – 25 1 s
Trip level of inverse time current unbalance protection
Is> 0.3Im Dis-0.1-0.8 0.1 Im
element
Trip time delay of inverse time current unbalance
tIs> 4s 1-8 1 s
protection when Is=Im
I< 0.2Im Trip level of undercurrent (no-load running) element Dis-0.15-1 0.01 Im
tI< 3s Trip time delay of undercurrent element 0.1 - 90 0.1 s
I> 2Ist Trip level of overcurrent element Dis - 1 - 5 0.1 Ist
tI> 0.1s Trip time delay of overcurrent element 0.05 - 1 0.01 s
O> 0.1On Trip level of earth fault element Dis - 0.02 - 2 0.01 On
tO> 0.2s Trip time delay of earth fault element 0.05 - 5 0.01 s
tBO 0.15s Reset time delay of the blocking output relay 0.05 - 0.5 0.01 s
RTD OFF Input from external thermal probe ON - OFF - -
SpC OFF Speed switch control ON - OFF - -

The setting Dis indicates that the function is disactivated.

Copyright 2010 - Microener


Doc. N° MO-0015-ING
Rev. 4
MM30 Pag. 20 of 30

12.2 - PROGRAMMING THE CONFIGURATION OF OUTPUT RELAYS

T> - 2 - 4

This is the name of This dash means The number 2 This dash means The number 4 means
protective element that output relay means that that output relay that output relay 4 will
number 1 is not output relay 2 will number 3 is not operate when this
assigned to this operate when assigned to this element trips
element this element trips element

Mode PROG menu FRELAY (Production standard settings here under shown).
The key "+" operates as cursor; it moves through the digits corresponding to the four programmable
relays in the sequence 1,2,3,4,(1= relay R1, etc.) and makes start flashing the information actually
present in the digit. The information present in the digit can be either the number of the relay (if this was
already associated to the function actually on programming) or a dot (-) if the relay was not yet
addressed.
The key "-" changes the existing status from the dot to the relay number or viceversa.
After programming of any function (T>, Ta, etc.), press the key ENTER to validate the configuration
selected,

Display Description
T> 1--- Overload tripping operates relay R1,R2,R3,R4.
Ta -2-- Overload prealarm tripping operates relay R1,R2,R3,R4.
ITr ---- Starting switch-over tripping operates relay R1,R2,R3,R4.
StNo ---- Start No limitation tripping operates relay R1,R2,R3,R4.
ILR 1--- Locked Rotor tripping operates relay R1,R2,R3,R4.
tIs> 1--- Time delayed unbalance tripping operates relay R1,R2,R3,R4.
I< ---4 No load running tripping operates relay R1,R2,R3,R4.
I> ---- Instantaneous overcurrent tripping operates relay R1,R2,R3,R4.
tI> 1--- Time delayed overcurrent tripping operates relay R1,R2,R3,R4
O> ---- Instantaneous earth fault tripping operates relay R1,R2,R3,R4
tO> 1--- Time delayed earth fault tripping operates relay R1,R2,R3,R4.
RT ---- Remote trip control. operates relay R1,R2,R3,R4.

Copyright 2010 - Microener


Doc. N° MO-0015-ING
Rev. 4
MM30 Pag. 21 of 30

13. MANUAL AND AUTOMATIC TEST OPERATION


13.1 Mode "TESTPROG" subprogram "W/O TRIP"
Operation of the yellow key activates a complete test of the electronics and the process routines.
All the leds are lit-on and the display shows (TEST RUN). If the test routine is successfully
completed the display switches-over to the default reading (T/Tnxxx%).
If an internal fault is detected, the display shows the fault identification code and the relay R5 is
deenergized. This test can be carried-out even during the operation of the relay without affecting the
relay tripping in case a fault takes place during the test itself.
13.2 Mode "TESTPROG" subprogram "WithTRIP"
Access to this program is enabled only if the current detected is zero (breaker open).
Pressing the yellow key the display shows "TEST RUN?". A second operation of the yellow key starts
a complete test which also includes the activation of all the output relays.
The display shows (TEST RUN) with the same procedure as for the test with W/O TRIP.
Every 15 min during the normal operation the relay automatically initiates an auto test procedure
(duration  10ms). If any internal fault is detected during the auto test, the relay R5 is deenergized,
the relevant led is activated and the fault code is displayed.
Further operation of key SELECT instead of the TEST programs gives the indication of the version and
production date of the firmware.

WARNING

Running the WithTRIP test will operate all of the output relays. Care must be taken to ensure that no
unexpected or harmful equipment operations will occur as a result of running this test.
It is generally recommended that this test be run only in a bench test environment or after all dangerous
output connections are removed.
14. MAINTENANCE
No maintenance is required. Periodically a functional check-out can be made with the test procedures
described under MANUAL TEST chapter. In case of malfunctioning please contact Microelettrica
Scientifica Service or the local Authorised Dealer mentioning the relay's Serial No reported in the label
on relays enclosure.

WARNING

In case of Internal Relay Fault detection, proceed as here-below indicated :


 If the error message displayed is one of the following “DSP Err”, “ALU Err” ,”KBD Err” ,”ADC Err”,
switch off power supply and switch-on again. If the message does not disappear send the relay to
Microelettrica Scientifica (or its local dealer) for repair.
 If the error message displayed is “E2P Err”, try to program any parameter and then run “W/OTRIP”.
 If message disappear please check all the parameters.
 If message remains send the relay to Microelettrica Scientifica (or its local dealer) for repair.
15. POWER FREQUENCY INSULATION TEST
Every relay individually undergoes a factory insulation test according to IEC255-5 standard at
2 kV, 50 Hz 1min. Insulation test should not be repeated as it unusefully stresses the dielectrics.
When doing the insulation test, the terminals relevant to serial output must always be short circuited to
ground. When relays are mounted in switchboards or relay boards that have to undergo the insulation
tests, the relay modules must be drawn-out of their enclosures and the test must only include the fixed
part of the relay with its terminals and the relevant connections. This is extremely important as
discharges eventually tacking place in other parts or components of the board can severely damage the
relays or cause damages, not immediately evident to the electronic components.
Copyright 2010 - Microener
Doc. N° MO-0015-ING
Rev. 4
MM30 Pag. 22 of 30

16. ELECTRICAL CHARACTERISTICS


APPROVAL: CE – RINA – UL and CSA approval File : E202083
REFERENCE STANDARDS IEC 60255 - EN50263 - CE Directive - EN/IEC61000 - IEEE C37

 Dielectric test voltage IEC 60255-5 2kV, 50/60Hz, 1 min.


 Impulse test voltage IEC 60255-5 5kV (c.m.), 2kV (d.m.) – 1,2/50s : 5kV (c.m.), 2
 Insulation resistance > 100M

Environmental Std. Ref. (IEC 68-2-1 - 68-2-2 - 68-2-33)


 Operation ambient temperature -10°C / +55°C
 Storage temperature -25°C / +70°C
 Humidity IEC68-2-3 RH 93% Without Condensing AT 40°C

CE EMC Compatibility (EN50081-2 - EN50082-2 - EN50263)


 Electromagnetic emission EN55022 industrial environment
 Radiated electromagnetic field immunity test IEC61000-4-3 level 3 80-1000MHz 10V/m
ENV50204 900MHz/200Hz 10V/m
 Conducted disturbances immunity test IEC61000-4-6 level 3 0.15-80MHz 10V
 Electrostatic discharge test IEC61000-4-2 level 4 6kV contact / 8kV air
 Power frequency magnetic test IEC61000-4-8 1000A/m 50/60Hz
 Pulse magnetic field IEC61000-4-9 1000A/m, 8/20s
 Damped oscillatory magnetic field IEC61000-4-10 100A/m, 0.1-1MHz
 Electrical fast transient/burst IEC61000-4-4 level 3 2kV, 5kHz
 HF disturbance test with damped oscillatory wave (1MHz IEC60255-22-1 class 3 400pps, 2,5kV (m.c.), 1kV (d.m.)
burst test)
 Oscillatory waves (Ring waves) IEC61000-4-12 level 4 4kV(c.m.), 2kV(d.m.)
 Surge immunity test IEC61000-4-5 level 4 2kV(c.m.), 1kV(d.m.)
 Voltage interruptions IEC60255-4-11
 Resistance to vibration and shocks IEC60255-21-1 - IEC60255-21-2 10-500Hz 1g

CHARACTERISTICS
 Accuracy at reference value of influencing factors 2% In for measure
0,2% On
2% +/- 10ms for times
 Rated Current In = 1 or 5A - On = 1 or 5A
 Current overload 200 A for 1 sec; 10A continuous
 Burden on current inputs Phase : 0.01VA at In = 1A; 0.2VA at In = 5A
Neutral : 0.03VA at On = 1A; 0.2VA at On = 5A
 Average power supply consumption 8.5 VA
 Output relays rating 5 A; Vn = 380 V
A.C. resistive switching = 1100W (380V max)
make = 30 A (peak) 0,5 sec.
break = 0.3 A, 110 Vcc,
L/R = 40 ms (100.000 op.)

Microelettrica Scientifica S.p.A. - 20089 Rozzano (MI) - Italy - Via Alberelle, 56/68
Tel. (##39) 02 575731 - Fax (##39) 02 57510940
http://www.microelettrica.com e-mail : ute@microelettrica.com
The performances and the characteristics reported in this manual are not binding and can modified at any moment without notice

Copyright 2010 - Microener


Doc. N° MO-0015-ING
Rev. 4
MM30 Pag. 23 of 30

17. CONNECTION DIAGRAM (SCE1269 Rev.7 Standard Output)

C B

17.1 CONNECTION DIAGRAM (SCE1462 Rev.2 Double Output)

C B

Copyright 2010 - Microener


Doc. N° MO-0015-ING
Rev. 4
MM30 Pag. 24 of 30

18. WIRING THE SERIAL COMMUNICATION BUS (SCE1309 Rev.0)

19. CHANGE PHASE CURRENT RATED INPUT 1 OR 5A

TA1
J1
1 Jumper

5A
J1 Rated input
Phase A Current
TA2 1 J2 1A

Rated input
J2 Current
Phase C 5A 1A

TA4

Copyright 2010 - Microener


Doc. N° MO-0015-ING
Rev. 4
MM30 Pag. 25 of 30

20. THERMAL IMAGE CURVES (TU0249 Rev.1)

Copyright 2010 - Microener


Doc. N° MO-0015-ING
Rev. 4
MM30 Pag. 26 of 30

21. INVERSE TIME UNBALANCE PROTECTION ELEMENT (TU0248 Rev.1)

Copyright 2010 - Microener


Doc. N° MO-0015-ING
Rev. 4
MM30 Pag. 27 of 30

22. DIRECTION FOR PCB'S DRAW-OUT AND PLUG-IN

22.1 Draw-out

Rotate clockwise the screws  and  in the horizontal position of the screws-driver mark.
Draw-out the PCB by pulling on the handle 

22.2 Plug-in

Rotate clockwise the screws  and in the horizontal position of the screws-driver mark.
Slide-in the card on the rails provided inside the enclosure.
Plug-in the card completely and by pressing the handle to the closed position.
Rotate anticlockwise the screws  and  with the mark in the vertical position (locked).

Copyright 2010 - Microener


Doc. N° MO-0015-ING
Rev. 4
MM30 Pag. 28 of 30

23. MOUNTING

PANEL CUT-OUT 113x142 (LxH)

View of Rear
Terminal Connection

Copyright 2010 - Microener


MODE

I=0 I 0

(MEASURES) (SETDISP) (PROGR) (TESTPROG)


In programming mode
SEL SEL SEL the output relay R5 SEL
is deenergized

(LastTrip) (SETTINGS) (FRELAY)


(LastTrip-1) (SETTINGS) (FRELAY) 1 (MM30)
(ACT MEAS) (MAX VAL) (TRIPNUM) PRG (SelPrg) PRG
(LastTrip-2) 2 (Ver:x.xx)
(EntPrS) (EntPrS)
I=0 I 0
(LastTrip-3) +/- +/- 3 (Dtxxxxxx)
(LastTrip-4) SEL ENT SEL ENT
0 NodAdxxx 0 T> xxxx (UpDwnS) (UpDwnS) (W/O TRIP) (WithTRIP)
1 Fn xx Hz 1 Ta xxxx +/- +/-
+/- +/- +/- +/-
2 InxxxxAp 2 ITr xxxx 0 NodAdxxx 0 T> xxxx
24. KEYBOARD OPERATIONAL DIAGRAM

ENT ENT
0 T/Tn xxx% 0 T/Tn xxx% 0 Causexxx 0 T> xxxxxx 3 OnxxxxAp 3 StNoxxxx 1 Fn xx Hz 1 Ta xxxx
1 IAxxxxxA 1 IAxxxxIn 1 IAxxxxxA 1 Is> xxxxx 4 ImxxxIn 4 ILR xxxx 2 InxxxxAp 2 ITr xxxx
2 IBxxxxxA 2 IBxxxxIn 2 IBxxxxxA 2 I> xxxxxx 5 Ist xxIm 5 tIs> xxxx 3 OnxxxxAp 3 StNoxxxx TESTRUN?
3 ICxxxxxA 3 ICxxxxIn 3 ICxxxxxA 3 O> xxxxxx 6 tst xxxs 6 I< xxxx 4 ImxxxIn 4 ILR xxxx
4 IoxxxxxA 4 IoxxxxxA 4 IoxxxxxA 4 I< xxxxxx 7 ItrxxxIst 7 I> xxxx 5 Ist xxIm 5 tIs> xxxx SEL ENT
5 Id/mxxx% 5 Id/mxxx% 5 Id/mxxx% 5 LR xxxxxx 8 tTr xxxs 8 tI> xxxx 6 tst xxxs 6 I< xxxx
6 Is/mxxx% 6 Is/mxxx% 6 Is/mxxx% 6 StN> xxxx 9 Autoset? 9 O> xxxx 7 ItrxxxIst 7 I> xxxx
7 SAxxxxIn 7 T/Tnxxx% 7 ITr xxxxx 10 tm xxmin 10 tO> xxxx 8 tTr xxxs 8 tI> xxxx
TEST RUN TEST RUN
MM30

8 SBxxxxIn 8 RT xxxxx 11 to/tm xx 9 Autoset? 9 O> xxxx


9 SCxxxxIn 12 Ta/nxxx% 10 tm xxmin 10 tO> xxxx 1 msgFAULT 1 msgFAULT

Copyright 2010 - Microener


10 SoxxxxOn 13 Ts/nxxx% 11 to/tm xx 2 T/Tn xxx% 2 T/Tn xxx%
11 Sd/mxxx% 14 IbxxxxIm 12 Ta/nxxx%
12 Ss/mxxx% 15 StNo xxx 13 Ts/nxxx%
13 tStxxxxs 16 tStNoxxm 14 IbxxxxIm
17 tBSt xxm 15 StNo xxx
18 ILRxxxIm 16 tStNoxxm
19 tLR xxs 17 tBSt xxm
20 Is>xxxIm 18 ILRxxxIm
21 tIs>xxxs 19 tLR xxs
22 I<xxxxIm 20 Is>xxxIm
23 TI<xxxs 21 tIs>xxxs
24 I> xxxIst 22 I<xxxxIm
25 tI>xxxs 23 TI<xxxs
Rev.
Pag.

26 O>xxxxOn 24 I> xxxIst


27 tO>xxxxs 25 TI>xxxs
4

28 tBOxxxxs O>xxxxOn
26
29

29 RTD xxx
27 tO>xxxxs
30 SpC xxx tBOxxxxs
28
of

29 tO>xxxxs
30 tBOxxxxs
30
Doc. N° MO-0015-ING
Doc. N° MO-0015-ING
Rev. 4
MM30 Pag. 30 of 30

25. SETTING’S FORM

Relay Type MM30 Station : Circuit :


Date : / / Relay Serial Number :
Power Supply 24V(-20%) / 110V(+15%) a.c. 24V(-20%) / 125V(+20%) d.c. Rated Current In : 1A 5A
80V(-20%) / 220V(+15%) a.c. 90V(-20%) / 250V(+20%) d.c. Rated Current Ion : 1A 5A
RELAY PROGRAMMING
Setting Default Actual Test Result
Variable Description
Range Setting Setting Pick-up Reset
NodAd Identif. number for connection on serial comm. bus 1 - 250 - 1
Fn Mains frequency 50 - 60 Hz 50
In Rated primary current of the phase C.Ts. 1 - 9999 Ap 500
On Rated primary current of the C.Ts. 1 - 9999 Ap 500
Im Motor full-load current 0.1 – 1.5 In 1.0
Ist Motor start-up current 0.5 – 10 Im 6
tst Motor starting time 1 – 120 s 5
Itr Switch-over current of motor starter Dis –0.1– 1 Ist 0.5
tTr Max switch-over time from start-up 0.5 – 50 s 6
Automatic setting of all the following parameters computed on the base of the setting of the previous
AUTOSET? + ENTER
parameters
tm Thermal time constant of motor while running 1 - 60 min 34
to/tm Steady/running motor thermal time constant 1 - 10 - 3
Ta/n Prealarm motor heating level 50 - 110 % 90
Ts/n Motor restart heating level 40 - 100 % 100
Ib Rated maximum continuous current of the motor 1.00 – 1.30 Im 1.05
StNo Max. No of startings allowed within the time tStNo Dis - 1 - 60 - 6
tStNo Time into which the StNo is counted 1 - 60 m 60
tBSt Restart inhibition time after tripping of the funct. StNo 1 - 60 – Rm m 12
ILR Trip level of Locked Rotor function Dis - 1 - 5 Im 2
tLr Trip time delay of LR element during run 1 – 25 s 1
Trip level of inverse time current unbalance protect.
Is> Dis-0.1-0.8 Im 0.3
element
tIs> Trip time delay of inv. time current unbalance prot. 1-8 s 4
I< Trip level of undercurrent (no-load running) element Dis-0.15-1 Im 0.2
tI< 3s Trip time delay of undercurrent element 0.1 - 90 s 3
I> Trip level of overcurrent element Dis - 1 - 5 Ist 2
tI> Trip time delay of overcurrent element 0.05 - 1 s 0.1
O> Trip level of earth fault element Dis -0.02- 2 On 0.1
tO> Trip time delay of earth fault element 0.05 - 5 s 0.2
tBO Reset time delay of the blocking output relay 0.05 - 0.5 s 0.15
RTD Thermal probe ON - OFF - -
SpC Speed switch ON - OFF - -
CONFIGURATION OF OUTPUT RELAYS
Default Setting Actual Setting
Protect. Output Protect. Output
Description
Element Relays Element Relays
T> 1 - - - Overload tripping operates relay T>
Ta - 2 - - Overload prealarm tripping operates relay Ta
Itr - - - - Starting switch-over tripping operates relay Itr
StNo - - - - Start No limitation tripping operates relay StNo
ILR 1 - - - Locked Rotor tripping operates relay ILR
tIs> 1 - - - Time delayed unbalance tripping operates relay tIs>
I< - - - 4 No load running tripping operates relay I<
I> - - - - Instantaneous overcurrent tripping operates relay I>
tI> 1 - - - Time delayed overcurrent tripping operates relay tI>
O> - - - - Instantaneous earth fault tripping operates relay O>
tO> 1 - - - Time delayed earth fault tripping operates relay tO>
RT - - - - Remote trip control. RT

Commissioning Engineer : Date :


Customer Witness : Date :

Copyright 2010 - Microener

You might also like