MM30 Manual - en 00154
MM30 Manual - en 00154
MM30 Manual - en 00154
N° MO-0015-ING
Rev. 4
MM30 Pag. 1 of 30
MICROPROCESSOR
MOTOR PROTECTION RELAY
TYPE
MM30
OPERATION MANUAL
MICROELETTRICA SCIENTIFICA
MILANO ITALY
MODE SELECT +
MULTIFUNCTION
MOTOR PROTECTION
RELAY TYPE -
MM30 PROG.
ENTER/RESET
INDEX
1 General utilization and commissioning directions___________________________________________ 3
1.1 Storage and transportation____________________________________________________________ 3
1.2 Installation________________________________________________________________________ 3
1.3 Electrical connection________________________________________________________________ 3
1.4 Measuring inputs and power supply_____________________________________________________ 3
1.5 Outputs loading____________________________________________________________________ 3
1.6 Protection earthing__________________________________________________________________ 3
1.7 Setting and calibration_______________________________________________________________ 3
1.8 Safety protection___________________________________________________________________ 3
1.9 Handling__________________________________________________________________________ 3
1.10 Maintenance_______________________________________________________________________ 4
1.11 Fault detection and repair_____________________________________________________________ 4
2 General characteristics and operation_____________________________________________________ 4
2.1 Power supply______________________________________________________________________ 4
2.2 Operation an Algorithms______________________________________________________________ 5
2.2.1 Reference input variable_________________________________________________________ 5
2.2.2 Input quantities_________________________________________________________________ 5
2.2.2.1 Mains Frequency_________________________________________________________ 5
2.2.2.2 Phase current input________________________________________________________ 5
2.2.2.3 Earth Fault current input____________________________________________________ 6
2.2.3 Function and Setting____________________________________________________________ 7
2.2.3.1 F49 – Thermal image______________________________________________________ 7
2.2.3.2 F51LR – Locked Rotor Protection (Rotor jam)___________________________________ 8
2.2.3.3 F46 – Current Unbalance (Negative Sequence current) protection___________________ 8
2.2.3.4 F37 – No-Load Running protection____________________________________________ 8
2.2.3.5 F51 – Overcurrent protection________________________________________________ 9
2.2.3.6 F64 – Earth Fault protection_________________________________________________ 9
2.2.3.7 Limitation of the Stats Number_______________________________________________ 9
2.2.3.8 Starting Sequence control__________________________________________________ 10
2.2.3.9 Autosetting______________________________________________________________ 10
3 Controls and measurements_____________________________________________________________ 11
4 Signalization__________________________________________________________________________ 12
5 Output relays__________________________________________________________________________ 13
6 Serial communication___________________________________________________________________ 13
7 Digital inputs _________________________________________________________________________ 14
8 Test__________________________________________________________________________________ 14
9 Keyboard and display operation__________________________________________________________ 15
10 Reading of measurements and recorded parameters_________________________________________ 16
10.1 ACT. MEAS (Actual measure)______________________________________________ 16
10.2 MAX VAL (Max values)__________________________________________________ 16
10.3 EVENT RECORDING (Last trip)____________________________________________________ 17
10.4 TRIP NUM (Trip number)_________________________________________________ 17
11 Reading of programmed settings and relay’s configuration____________________________________ 17
12 Programming__________________________________________________________________________ 18
12.1 Programming of functions settings____________________________________________________ 18
12.2 Programming the configuration of output relay___________________________________________ 20
13 Manual and automatic test operation______________________________________________________ 21
13.1 W/O TRIP_______________________________________________________________________ 21
13.2 WithTRIP________________________________________________________________________ 21
14 Maintenance___________________________________________________________________________ 21
15 Power frequency insulation test__________________________________________________________ 21
16 Electrical characteristics________________________________________________________________ 22
17 Connection diagram (Standard Output)_____________________________________________________ 23
17.1 Connection Diagram (Double Output)__________________________________________________ 23
18 Wiring the serial communication bus______________________________________________________ 24
19 Change phase current rated input 1A or 5A_________________________________________________ 24
20 Thermal Image curves__________________________________________________________________ 25
21 Inverse time unbalance protection element_________________________________________________ 26
22 Direction for pcb’s draw-out and plug-in___________________________________________________ 27
22.1 Draw-out________________________________________________________________________ 27
22.2 Plug-in__________________________________________________________________________ 27
23 Overall dimensions / Mounting___________________________________________________________ 28
24 Keyboard operational diagram___________________________________________________________ 29
25 Setting’s form_________________________________________________________________________ 30
Always make reference to the specific description of the product and to the Manufacturer's instruction.
Carefully observe the following warnings.
must comply with the environmental conditions stated on the product's instruction or by the applicable
IEC standards.
1.2 - INSTALLATION,
must be properly made and in compliance with the operational ambient conditions stated by the
Manufacturer.
must be made strictly according to the wiring diagram supplied with the Product, to its electrical
characteristics and in compliance with the applicable standards particularly with reference to human
safety.
carefully check that the value of input quantities and power supply voltage are proper and within the
permissible variation limits.
Carefully check the proper setting of the different functions according to the configuration of the
protected system, the safety regulations and the co-ordination with other equipment.
Carefully check that all safety means are correctly mounted, apply proper seals where required and
periodically check their integrity.
1.9 - HANDLING
Notwithstanding the highest practicable protection means used in designing M.S. electronic circuits,
the electronic components and semiconductor devices mounted on the modules can be seriously
damaged by electrostatic voltage discharge which can be experienced when handling the modules.
The damage caused by electrostatic discharge may not be immediately apparent but the design
reliability and the long life of the product will have been reduced. The electronic circuits reduced by
M.S. are completely safe from electrostatic discharge (8 KV IEC 255.22.2) when housed in their
case; withdrawing the modules without proper cautions expose them to the risk of damage.
a. Before removing a module, ensure that you are at the same electrostatic potential
as the equipment by touching the case.
b. Handle the module by its front-plate, frame, or edges of the printed circuit board.
Avoid touching the electronic components, printed circuit tracks or connectors.
c. Do not pass the module to any person without first ensuring that you are both at
the same electrostatic potential. Shaking hands achieves equipotential.
More information on safe working procedures for all electronic equipment can be found
in BS5783 and IEC 147-OF.
1.10 - MAINTENANCE
Make reference to the instruction manual of the Manufacturer ; maintenance must be carried-out by
specially trained people and in strict conformity with the safety regulations.
Misapplication of the above warnings and instruction relieves the Manufacturer of any liability.
2. GENERAL CHARACTERISTICS
Input currents are supplied to 3 current transformers: - two measuring phase current (the third current is
computed as vector sum of the two others) - one measuring the earth fault zero-sequence current.
Phase current rated input can be 1 or 5A (Selectable by movable bridges an relay card)
For zero-sequence current taps for 1A and 5A input are provided on relay's terminal board.
Make electric connection in conformity with the diagram reported on relay's enclosure.
Check that input currents are same as reported on the diagram and on the test certificate.
The auxiliary power is supplied by a built-in interchangeable module fully isolated an self protected.
The relay can be fitted with two different types of power supply module :
Before energising the unit check that supply voltage is within the allowed limits.
The relay directly displays the r.m.s. value of the Phase Currents “ IA “, “ IB ”, “ IC ” flowing in the
Primary of the input Current Transformers and refers all its measurements to that value.
To make the relay properly working with any C.T., when programming the relay settings we have
to input the value of the Rated Primary Current “ In “ of the phase C.Ts.
Only phase A and C currents are measured, whereas the current of the phase B is computed as
vector summation of the currents of the other two phases.
The algorithm is based on the following considerations coming from well-known vector relations
among the three-phase currents and the zero sequence current.
- In any circumstance – currents balanced or not, sinusoidal or not – it is always true that:
1 IA IB IC I0 0
2
IA IB IC 0 IB IA IC
The earth fault protection element is independently supplied by the residual current coming either
from the residual connection of the 3 system C.Ts. or from the core balance C.T.
If any Earth Fault is experienced (I0 0) the Earth Fault Protection Element trips independently
from the phase current measuring elements.
If no Earth Fault is present (I0 = 0), the equation (2) is valid, no matter if currents are balanced or
not, sinusoidal or not.
The third phase current is calculated, in real time, as vector summation of the other two-phase
currents
Similarly, the Positive Sequence Current Component “ Id “ and Negative Sequence component
“ Is “, with no Earth Fault, are computed according to the normal equations of the system
symmetrical components, using two currents only:
I A Id Is
I C α I A Is α α
2
Is 3 I C I A e j120
I C α Id α Is
2
I C α I A Id α α
2
2
Id 3 I C I A e j120
In case of Earth Fault the Earth Fault Element trips before tripping of the unbalance element.
- During Faults
Trip of the earth fault element directly measuring the Residual Current.
In any case one of the currents directly measured is involved, so the relay trips correctly.
Same as A + B
All the three currents are correctly measured (in any case two directly).
Same as for the Phase Currents, the relay directly displays the r.m.s. value of the Zero Sequence
Residual Current flowing at the Primary of the Current Transformers.
If the input of the Earth Fault element is supplied by the residual connection of the 3 phase C.Ts.,
we shall set for “On” the same value as “In”.
If the input of the Earth Fault elements is supplied by a separated Core Balance C.T., or by
another CT, “On” value will be the Rated Primary Current of this C.T., normally different from “In”.
The trip time delay “ t “ of the thermal element, depends on the warming-up time constant
“ tm “ of the motor, on the previous thermal status (Ip), on the admissible continuous overload
(Ib) and, of course, on the actual load (I)
(I/Im) 2 (Ip/Im)2
t tm In 2
(I/Im) (Ib/Im)
2
tm = (1-60)min.
I = computed current
Ip = preheating current
Ib = continuously admissible current (1-1.3)Im, step 0.01Im
Im = motor rated current (0.1-1.5)In, step 0.1In
The cooling-down time constant of the motor when running is “tm”; it is automatically changed
to " to " when the motor current drops below 0.1 lm (running/steady motor discrimination
level).
An alarm signal is issued when the simulated warming exceeds the set percentage of the
motor rated temperature Tn.
Automatic 1% drop out percentage.
To inhibit a new motor starting before cooling down to 99% Ts/n, reset after tripping of the
thermal element takes places when T< 0.99[Ts].
At motor starting this function is disabled for the set time “ 2tSt “ : when this time has elapsed, if
current exceeds the set level “ ILR ”, the relay trips with a delay of “ tLR ” sec.
- Current level :
2tSt
tSt = (1-120)s, step 1s = motor start-up time
2.2.3.2 - F46 - Current Unbalance (Negative Sequence Current) protection (See curve 21)
Besides its contribution to the thermal image algorithm, current unbalance also controls another
inverse time element
This function performs the protection against no-load running: it is activated by motor under
current.
Any of the output relays can be associated to the time delayed element “tI>” as well as to the
instantaneous element “I>” of this function for signalling or for blocking other relays. The
output relay controlled by the I> level remains energized for the time tI> + tBO.
After this delay the relay it is anyhow reset.
As for function F51, any of the output relays can also be associated to the instantaneous
element of “O>” level.
During start-up of the motor, the unit can control an output relay used to operate the switch-over of
motor starter (star-delta, resistance or impedance, autotransformer, etc...) thus allowing to
automatically manage the starting transition by controlling the following parameters:
At motor start counting of tTr begins. If during tTr the motor current drops below ltr,
switching-over is operated; if motor current stays above ltr longer than tTr, the Locked Rotor
element is activated.
2.2.3.9 - Autosetting
The complexity of properly set a motor protection, frequently produces undesired tripping or
non-operation of some of the functions.
The relay MM30 can automatically select the best setting of the parameters according to motor
and system basic data. These data are:
- System frequency = Fn = 50 o 60 Hz
- Rated primary current of phase C.Ts. = In = 0-9999 A step 1A
- Rated primary current of earth fault C.T = On = 0-9999 A step 1A
- Motor rated current = lm = 0.1-1.5 In step 0.01In
- Motor starting current = lst = 0.5-9.9 Im step0.1 Im
- Starting time = tst = 1-120 s step 1s
- Transition current level = ITr = 0.11 Ist step 0.1 Ist
- Transition time = tTr = 0.5-50 s step 0,1s
Once these settings have been programmed, the “AUTOSET” function can be activated by the key
"ENTER" and all the parameters are computed and automatically set at values suitable for a
normal duty of the motor.
Particularly the motor warming-up time constant “tm” is computed so that the motor, when stopped
after having run continuously at Rated Power (Rated current Im), can be immediately restarted at
least one time.
The parameters can anyhow be manually modified if different setting is needed.
Five key buttons allow for local management of all relay's functions.
A 8-digit high brightness alphanumerical display shows the relevant readings (xxxxxxxx)
(see synoptic table fig.1)
FIG.1
MODE SELECT + - ENTER
4. SIGNALIZATIONS
a b c d
e f g h
Flashing when the motor heating T overcomes the set alarm level [Ta].
Red
a) > Illuminated on over-temperature trip. – Also illuminated on activation of RTD
LED
input.
Red Illuminated on tripping of the element for limitation of the number of
b) St N°
LED startings.
Red Flashing as soon as motor current drops below the set level [I<]
c) I<
LED Illuminated at the end of trip time delay.
Red Flashing as soon as motor unbalance overpasses the set level [Is>]
d) Is>
LED Illuminated on trip after delay [tIs>].
Yellow ROTOR Illuminated on trip of the Locked Rotor element (I>ILR) and/or on activation
e)
LED STALL of the Speed Control input SpC.
Red Flashing when motor current is above the set level [I>]
f) I>>
LED Illuminated on trip after delay [tI>].
g) Red Flashing when earth fault current is above the set level [O>]
LED Illuminated on trip after delay [tO>].
Yellow START Flashing when in PROGRAM MODE
h)
LED INHIBIT Illuminated when relay internal fault is detected.
Leds a,c,d,f,g From flashing to off, automatically when the lit-on cause disappears.
From ON to OFF, by "ENTER/RESET" push button only if the
tripping cause has disappeared.
Leds b,e From ON to OFF, by "ENTER/RESET" push button only if the
tripping cause has disappeared.
Leds h From flashing or illuminated to off, automatically when the lit-on
cause disappears.
In case of auxiliary power supply failure the status of the leds is recorded and reproduced when power
supply is restored.
5. OUTPUT RELAYS
Five output relays are available (R1, R2, R3, R4, R5)
a) - The relays R1,R2,R3,R4 are normally deenergized (energized on trip): these output relays are user
programmable and any of them can be associated to one of the MM30's functions.
One relay eventually associated to instantaneous element of the function 51 or 51N(64), after
pick-up normally drops-out as soon as the tripping cause is cleared (current below the set trip
level).
If the current remains above the trip level longer than the time delay programmed for the same
function, the drop-out of the instantaneous relay is anyhow forced after an adjustable waiting
time [tBO]. (Breaker failure protection control)
The reset after tripping of the relays associated to the time delayed functions takes place
automatically as soon as the pick-up cause is cleared.
b) - The relay R5, normally energized, is not programmable and is deenergized on:
Internal fault
Power supply failure
During the programming
6. SERIAL COMMUNICATION
The relays fitted with the serial communication option can be connected via a cable bus or (with proper
adapters) a fiber optic bus for interfacing with a Personal Computer (type IBM or compatible).
All the operations which can be performed locally (for example reading of measured data and changing
of relay’s settings) are also possible via the serial communication interface.
Furthermore the serial port allows the user to read the demand recording data.
The unit has a RS232 / RS485 interface and can be connected either directly to a P.C. via a dedicated
cable or to a RS485 serial bus, thus having many relays to exchange data with a single master P.C.
using the same physical serial line. A RS485/232 converter is available on request.
The communication protocol is MODBUS RTU (only functions 3, 4 and 16 are implemented).
Each relay is identified by its programmable address code (NodeAd) and can be called from the P.C.
A dedicated communication software (MSCOM) for Windows 95/98/NT4 SP3 (or later) is available.
Please refer to the MSCOM instruction manual for more information Microelettrica Scientifica.
7. DIGITAL INPUTS
On request (Optional) are provided three inputs activated when the relevant terminals are shorted:
8. TEST
Besides the normal "WATCHDOG" and "POWERFAIL" functions, a comprehensive program of self-test
and self-diagnostic provides:
Diagnostic and functional test, with checking of program routines and memory's content, run every
time the aux. power is switched-on: the display shows the type of relay and its version number.
Dynamic functional test run during normal operation every 15 min. (relay's operation is suspended
for less than 4ms). If any internal fault is detected, the display shows a fault message, the Led
"PROG/IRF" illuminates and the relay R5 is deenergized.
Complete test activated by the keyboard or via the communication bus either with or without tripping
of the output relays.
All controls can be operated from relay's front or via serial communication bus.
The keyboard includes five hand operable buttons (MODE) - (SELECT) - (+) - (-) - (ENTER/RESET)
plus one indirect operable key (PROG) (see synoptic table a fig.1):
MODE SELECT +
-
PROG.
ENTER/RESET
10.1 - ACT.MEAS
Display Description
T/Tnxxx% Actual temperature rise displayed as % of the motor full load temperature rise (0 - 999%)
IAxxxxxA True R.M.S. value of the current of phase A displayed as primary Amps. (0 - 99999)
IBxxxxxA As above, phase B.
ICxxxxxA As above, phase C.
IoxxxxxA As above, earth fault current.
Id/mxxx% Positive sequence component of motor current displayed as % of motor full load
current. (0 - 999)%
Is/mxxx% Negative sequence component of motor current displayed as % of motor full load current.
(unbalance degree) (0 - 999)%
NB: If no key is operated within 60 sec. the display is automatically switched to the default indication
Highest values recorded during motor run after the starting time (refreshed at each higher value) plus
highest values recorded during the starting time (refreshed at each new starting).
Display Description
T/Tnxxx% Highest temperature recorded since the start of the run. (0 - 99,9)%
IAxxxxxA Current of phase A measured during run after starting time (0-99999)
IBxxxxxA As above, phase B.
ICxxxxxA As above, phase C.
IoxxxxxA As above, zero sequence current.
Id/mxxx% Positive sequence component of motor current.
Is/mxxx% Negative sequence component of motor current
SAxxxxxA Current of phase A during the starting time.
SBxxxxxA As above, phase B.
SCxxxxxA As above, phase C.
SoxxxxxA As above, earth fault current.
Sd/mxxx% Positive sequence current component during starting time.
Ss/mxxx% Negative sequence current component during starting time.
tStxxxxs Measure of the start time.
Display of the function which caused the tripping of the relay and values of the parameters at the
moment of tripping. The memory buffer is refreshed at each new relay tripping.
Display Description
LastTr-x Indication of the recorded event (x= 0 to 4) Example: Last event (LastTr -0)
Last but one event (LastTr-1) etc...
Causexxx Function which caused the last tripping: T>; Is>; I>; O>; I<; LR; StN; ITr.
IAxxxxIn Current of phase A.
IBxxxxIn Current of phase B.
ICxxxxIn Current of phase C.
IoxxxxOn Earth fault current.
Id/mxxx% Positive sequence component of current.
Is/mxxx% Negative sequence component of current.
T/Tnxxx% Motor heating
Display Description
T> xxxxx Motor overload.
Is>xxxxx Current unbalance.
I> xxxxx Overcurrent.
O>xxxxx Earth fault.
I< xxxxx No load running.
LRxxxxx Locked rotor.
StN>xxxx No of consecutive startings.
ITrxxxxx Too long starting.
RTxxxx Remote trip
Enter the mode "SET DISP", select the menu "SETTINGS" or "FRELAY", scroll information
available in the menu by keys "+" or "-".
SETTINGS= values of relay's operation parameters as programmed
FRELAY= output relay associated to the different functions as programmed.
12. PROGRAMMING
The relay is supplied with the standard default programming used for factory test.[ Values here below
reported ( ----- ) ].
All parameters can be modified as needed in the mode PROG and displayed in the mode SET DISP
Local Programming by the front face key board is enabled only if no input current is detected
(main switch open). Programming via the serial port is always enabled but a password is
required to access the programming mode. The default password is the null string; in the
standard application program for communication “MS-COM” it is also provided an emergency
which can be disclosed on request only.
As soon as programming is enabled, the Led PRG/IRF flashes and the reclosing lock-out relay R5 is
deenergized. Enter MODE "PROG" and SELECT either "SETTINGS" for programming of parameters
or "FRELAY" for programming of output relays configuration; enable programming by the indirect
operation key PROG.
The key SELECT now scrolls the available parameters. By the key (+) , (-) the displayed values can be
modified; to speed up parameter's variation press the key SELECT while "+" or "-" are pressed.
Press key "ENTER/RESET" to validate the set values.
In 500 Ap
Mode PROG menu SETTINGS. (Production standard settings here under shown).
Display Description Setting Range Step Unit
Identification number for connection on serial
NodAd 1 1 - 250 1 1
communication bus
Fn 50 Hz Mains frequency 50 - 60 10 Hz
In 500Ap Rated primary current of the phase C.Ts. 1 - 9999 1 A
Rated primary current of the C.Ts. or of the tore C.T.
On 500Ap 1 - 9999 1 A
detecting earth fault current
Motor full-load current
Im 1.0In 0.1 – 1.5 0.01 In
(p.u. of phase C.Ts. rated current)
Ist 6Im Motor start-up current (p.u. of motor full load current) 0.5 – 10 0.1 Im
tst 5s Motor starting time 1 – 120 1 s
Switch-over current of motor starter
Itr0.5Ist Dis – 0.1 – 1 0.1 Ist
(p.u. of motor starting current)
T> - 2 - 4
This is the name of This dash means The number 2 This dash means The number 4 means
protective element that output relay means that that output relay that output relay 4 will
number 1 is not output relay 2 will number 3 is not operate when this
assigned to this operate when assigned to this element trips
element this element trips element
Mode PROG menu FRELAY (Production standard settings here under shown).
The key "+" operates as cursor; it moves through the digits corresponding to the four programmable
relays in the sequence 1,2,3,4,(1= relay R1, etc.) and makes start flashing the information actually
present in the digit. The information present in the digit can be either the number of the relay (if this was
already associated to the function actually on programming) or a dot (-) if the relay was not yet
addressed.
The key "-" changes the existing status from the dot to the relay number or viceversa.
After programming of any function (T>, Ta, etc.), press the key ENTER to validate the configuration
selected,
Display Description
T> 1--- Overload tripping operates relay R1,R2,R3,R4.
Ta -2-- Overload prealarm tripping operates relay R1,R2,R3,R4.
ITr ---- Starting switch-over tripping operates relay R1,R2,R3,R4.
StNo ---- Start No limitation tripping operates relay R1,R2,R3,R4.
ILR 1--- Locked Rotor tripping operates relay R1,R2,R3,R4.
tIs> 1--- Time delayed unbalance tripping operates relay R1,R2,R3,R4.
I< ---4 No load running tripping operates relay R1,R2,R3,R4.
I> ---- Instantaneous overcurrent tripping operates relay R1,R2,R3,R4.
tI> 1--- Time delayed overcurrent tripping operates relay R1,R2,R3,R4
O> ---- Instantaneous earth fault tripping operates relay R1,R2,R3,R4
tO> 1--- Time delayed earth fault tripping operates relay R1,R2,R3,R4.
RT ---- Remote trip control. operates relay R1,R2,R3,R4.
WARNING
Running the WithTRIP test will operate all of the output relays. Care must be taken to ensure that no
unexpected or harmful equipment operations will occur as a result of running this test.
It is generally recommended that this test be run only in a bench test environment or after all dangerous
output connections are removed.
14. MAINTENANCE
No maintenance is required. Periodically a functional check-out can be made with the test procedures
described under MANUAL TEST chapter. In case of malfunctioning please contact Microelettrica
Scientifica Service or the local Authorised Dealer mentioning the relay's Serial No reported in the label
on relays enclosure.
WARNING
CHARACTERISTICS
Accuracy at reference value of influencing factors 2% In for measure
0,2% On
2% +/- 10ms for times
Rated Current In = 1 or 5A - On = 1 or 5A
Current overload 200 A for 1 sec; 10A continuous
Burden on current inputs Phase : 0.01VA at In = 1A; 0.2VA at In = 5A
Neutral : 0.03VA at On = 1A; 0.2VA at On = 5A
Average power supply consumption 8.5 VA
Output relays rating 5 A; Vn = 380 V
A.C. resistive switching = 1100W (380V max)
make = 30 A (peak) 0,5 sec.
break = 0.3 A, 110 Vcc,
L/R = 40 ms (100.000 op.)
Microelettrica Scientifica S.p.A. - 20089 Rozzano (MI) - Italy - Via Alberelle, 56/68
Tel. (##39) 02 575731 - Fax (##39) 02 57510940
http://www.microelettrica.com e-mail : ute@microelettrica.com
The performances and the characteristics reported in this manual are not binding and can modified at any moment without notice
C B
C B
TA1
J1
1 Jumper
5A
J1 Rated input
Phase A Current
TA2 1 J2 1A
Rated input
J2 Current
Phase C 5A 1A
TA4
22.1 Draw-out
Rotate clockwise the screws and in the horizontal position of the screws-driver mark.
Draw-out the PCB by pulling on the handle
22.2 Plug-in
Rotate clockwise the screws and in the horizontal position of the screws-driver mark.
Slide-in the card on the rails provided inside the enclosure.
Plug-in the card completely and by pressing the handle to the closed position.
Rotate anticlockwise the screws and with the mark in the vertical position (locked).
23. MOUNTING
View of Rear
Terminal Connection
I=0 I 0
ENT ENT
0 T/Tn xxx% 0 T/Tn xxx% 0 Causexxx 0 T> xxxxxx 3 OnxxxxAp 3 StNoxxxx 1 Fn xx Hz 1 Ta xxxx
1 IAxxxxxA 1 IAxxxxIn 1 IAxxxxxA 1 Is> xxxxx 4 ImxxxIn 4 ILR xxxx 2 InxxxxAp 2 ITr xxxx
2 IBxxxxxA 2 IBxxxxIn 2 IBxxxxxA 2 I> xxxxxx 5 Ist xxIm 5 tIs> xxxx 3 OnxxxxAp 3 StNoxxxx TESTRUN?
3 ICxxxxxA 3 ICxxxxIn 3 ICxxxxxA 3 O> xxxxxx 6 tst xxxs 6 I< xxxx 4 ImxxxIn 4 ILR xxxx
4 IoxxxxxA 4 IoxxxxxA 4 IoxxxxxA 4 I< xxxxxx 7 ItrxxxIst 7 I> xxxx 5 Ist xxIm 5 tIs> xxxx SEL ENT
5 Id/mxxx% 5 Id/mxxx% 5 Id/mxxx% 5 LR xxxxxx 8 tTr xxxs 8 tI> xxxx 6 tst xxxs 6 I< xxxx
6 Is/mxxx% 6 Is/mxxx% 6 Is/mxxx% 6 StN> xxxx 9 Autoset? 9 O> xxxx 7 ItrxxxIst 7 I> xxxx
7 SAxxxxIn 7 T/Tnxxx% 7 ITr xxxxx 10 tm xxmin 10 tO> xxxx 8 tTr xxxs 8 tI> xxxx
TEST RUN TEST RUN
MM30
28 tBOxxxxs O>xxxxOn
26
29
29 RTD xxx
27 tO>xxxxs
30 SpC xxx tBOxxxxs
28
of
29 tO>xxxxs
30 tBOxxxxs
30
Doc. N° MO-0015-ING
Doc. N° MO-0015-ING
Rev. 4
MM30 Pag. 30 of 30