MM30-D Operation Manual: Microprocessor Motor Protection Relay With Directional Earth Fault Element Type
MM30-D Operation Manual: Microprocessor Motor Protection Relay With Directional Earth Fault Element Type
MM30-D Operation Manual: Microprocessor Motor Protection Relay With Directional Earth Fault Element Type
N° MO-0037-ING
MM30-D Rev. 4
Date 24.02.2003
MICROPROCESSOR
MOTOR PROTECTION RELAY
WITH DIRECTIONAL EARTH FAULT ELEMENT
TYPE
MM30-D
OPERATION MANUAL
INDEX
1 General utilization and commissioning directions _____________________________________________________ 3
1.1 Storage and transportation_____________________________________________________________________ 3
1.2 Installation__________________________________________________________________________________ 3
1.3 Electrical connection__________________________________________________________________________ 3
1.4 Measuring inputs and power supply______________________________________________________________ 3
1.5 Outputs loading______________________________________________________________________________ 3
1.6 Protection earthing___________________________________________________________________________ 3
1.7 Setting and calibration_________________________________________________________________________ 3
1.8 Safety protection_____________________________________________________________________________ 3
1.9 Handling___________________________________________________________________________________ 3
1.10 Maintenance________________________________________________________________________________ 4
1.11 Fault detection and repair______________________________________________________________________ 4
2 General characteristics and operation_______________________________________________________________ 4
2.1 Power supply________________________________________________________________________________ 4
2.2 Operation an Algorithms_______________________________________________________________________ 5
2.2.1 Reference input variable__________________________________________________________________ 5
2.2.2 Input quantities_________________________________________________________________________ 5
2.2.2.1 Mains Frequency_________________________________________________________________ 5
2.2.2.2 Phase current inputs_______________________________________________________________ 5
2.2.2.3 Earth Fault current and voltage inputs_________________________________________________ 6
2.2.3 Function and Setting_____________________________________________________________________ 7
2.2.3.1 F49 – Thermal image______________________________________________________________ 7
2.2.3.2 F51LR – Locked Rotor Protection (Rotor jam)___________________________________________ 8
2.2.3.3 F46 – Current Unbalance (Negative Sequence current) protection___________________________ 8
2.2.3.4 F47 – Single Phasing______________________________________________________________ 8
2.2.3.5 F37 – No-Load Running protection____________________________________________________ 8
2.2.3.6 F51 – Overcurrent protection________________________________________________________ 9
2.2.3.7 F64 – Earth Fault protection_________________________________________________________ 9
2.2.3.8 Limitation of the Stats Number_______________________________________________________ 10
2.2.3.9 Starting Sequence control__________________________________________________________ 10
2.2.3.10 Autosetting______________________________________________________________________ 11
2.3 Operational of the directional Earth Fault Element___________________________________________________ 12
2.4 Clock and Calendar___________________________________________________________________________ 13
2.4.1 Clock synchronization_____________________________________________________________________ 13
2.4.2 Date and time setting_____________________________________________________________________ 13
2.4.3 Time resolution__________________________________________________________________________ 13
2.4.4 Operation during power off_________________________________________________________________ 13
2.4.5 Time tolerance__________________________________________________________________________ 13
3 Controls and measurements_______________________________________________________________________ 14
4 Signalization_____________________________________________________________________________________ 15
5 Output relays____________________________________________________________________________________ 16
6 Serial communication_____________________________________________________________________________ 17
7 Digital inputs____________________________________________________________________________________ 18
8 Test____________________________________________________________________________________________ 18
9 Keyboard and display operation____________________________________________________________________ 19
10 Reading of measurements and recorded parameters___________________________________________________ 20
10.1 ACT. MEAS (Actual measure)_____________________________________________________________ 20
10.2 MAX VAL (Max values)_________________________________________________________________ 20
10.3 LASTTRIP (Last trip)____________________________________________________________________ 21
10.4 TRIP NUM (Trip number)_________________________________________________________________ 21
11 Reading of programmed settings and relay’s configuration_____________________________________________ 21
12 Programming____________________________________________________________________________________ 22
12.1 Programming of functions settings__________________________________________________________ 22
12.2 Programming the configuration of output relay_________________________________________________ 24
13 Manual and automatic test operation________________________________________________________________ 25
13.1 Mode “ TESTPROG “ subprogram “ W/O TRIP “_______________________________________________ 25
13.2 Mode “ TESTPROG “ subprogram “ With TRIP “_______________________________________________ 25
14 Maintenance_____________________________________________________________________________________ 25
15 Power frequency insulation test_____________________________________________________________________ 25
15 Electrical characteristics___________________________________________________________________________ 26
16 Connection diagram (Standard Output)_______________________________________________________________ 27
16.1 Connection Diagram (Double Output)___________________________________________________________ 27
17 Wiring the serial communication bus________________________________________________________________ 28
18 Change phase rated input 1A or 5A__________________________________________________________________ 28
19 Thermal image curves_____________________________________________________________________________ 29
20 Inverse time unbalance protection element___________________________________________________________ 30
21 Direction for pcb’s draw-out and plug-in_____________________________________________________________ 31
21.1 Draw-out______________________________________________________________________________ 31
21.2 Plug-in________________________________________________________________________________ 31
22 Overall dimensions / Mounting_____________________________________________________________________ 32
23 Keyboard operational diagram______________________________________________________________________ 33
24 Setting’s form____________________________________________________________________________________ 34
Always make reference to the specific description of the product and to the Manufacturer's instruction.
Carefully observe the following warnings.
must comply with the environmental conditions stated on the product's instruction or by the applicable
IEC standards.
1.2 - INSTALLATION,
must be properly made and in compliance with the operational ambient conditions stated by the
Manufacturer.
must be made strictly according to the wiring diagram supplied with the Product, to its electrical
characteristics and in compliance with the applicable standards particularly with reference to human
safety.
carefully check that the value of input quantities and power supply voltage are proper and within the
permissible variation limits.
Carefully check the proper setting of the different functions according to the configuration of the
protected system, the safety regulations and the co-ordination with other equipment.
Carefully check that all safety means are correctly mounted, apply proper seals where required and
periodically check their integrity.
1.9 - HANDLING
Notwithstanding the highest practicable protection means used in designing M.S. electronic circuits,
the electronic components and semiconductor devices mounted on the modules can be seriously
damaged by electrostatic voltage discharge which can be experienced when handling the modules.
The damage caused by electrostatic discharge may not be immediately apparent but the design
reliability and the long life of the product will have been reduced. The electronic circuits reduced by
M.S. are completely safe from electrostatic discharge (8 KV IEC 255.22.2) when housed in their
case; withdrawing the modules without proper cautions expose them to the risk of damage.
b. Handle the module by its front-plate, frame, or edges of the printed circuit board.
Avoid touching the electronic components, printed circuit tracks or connectors.
c. Do not pass the module to any person without first ensuring that you are both at
the same electrostatic potential. Shaking hands achieves equipotential.
More information on safe working procedures for all electronic equipment can be found
in BS5783 and IEC 147-OF.
1.10 - MAINTENANCE
Make reference to the instruction manual of the Manufacturer ;
maintenance must be carried-out by specially trained people and in strict conformity
with the safety regulations.
Misapplication of the above warnings and instruction relieves the Manufacturer of any liability.
2. GENERAL
Input currents are supplied to 3 current transformers: - two measuring phase current (the third current is
computed as vector summation of the two others) - one measuring the earth fault zero-sequence
current.
Phase current rated input can be 1 or 5A (Selectable by movable bridges on relay card)
Zero sequence rated input is 1A.
Zero sequence voltage input is supplied to one voltage transformer.
Rated input voltage 100V – 50/60Hz from Y/open connected PTS with ratio U1 : 3 / 100:3 V.
Make electric connection in conformity with the diagram reported on relay's enclosure.
Check that input currents are same as reported on the diagram and on the test certificate.
The auxiliary power is supplied by a built-in interchangeable module fully isolated an self protected.
The relay can be fitted with two different types of power supply module :
Before energising the unit check that supply voltage is within the allowed limits.
For the Phase Current inputs, 1A or 5A configuration can be selected by moving the jumpers J1
and J2 provided on the C.T. input card (See § 18).
Example :
Phase CTs 1500/5A and Core Balance CT 100/1A
Set In = 1500A and On = 100A
Configure CT input card with jumpers J1, J2 in the 5A position.
Only phase A and C currents are measured, whereas the current of the phase B is computed as
vector summation of the currents of the other two phases.
The algorithm is based on the following considerations coming from well-known vector relations
among the three-phase currents and the zero sequence current.
- In any circumstance – currents balanced or not, sinusoidal or not – it is always true that:
1 IA IB IC I0 0
- When no Earth Fault exists (I0 = 0)
2 IA IB IC 0 IB IA IC
The earth fault protection element is independently supplied by the residual current coming either
from the residual connection of the 3 system C.Ts. or from the core balance C.T.
If any Earth Fault is experienced (I0 0) the Earth Fault Protection Element trips independently
from the phase current measuring elements.
If no Earth Fault is present (I0 = 0), the equation (2) is valid, no matter if currents are balanced or
not, sinusoidal or not.
The third phase current is calculated, in real time, as vector summation of the other two-phase
currents.
Similarly, the Positive Sequence Current Component “ Id “ and Negative Sequence component
“ Is “, with no Earth Fault, are computed according to the normal equations of the system
symmetrical components, using two currents only:
I A Id Is
I C α I A Is α α
2
Is 3 I C I A e j120
I C α Id α Is
2 2
I C α I A Id α α
2
Id 3 I C I A e j120
In case of Earth Fault the Earth Fault Element trips before tripping of the unbalance element.
- During Faults
A) Single phase to earth Fault
Trip of the earth fault element directly measuring the Residual Current.
B) Two Phase Fault
In any case one of the currents directly measured is involved, so the relay trips correctly.
C) Two Phase to Earth Fault
Same as A + B
D) Three Phase Fault
All the three currents are correctly measured (in any case two directly).
2.2.2.3 – Earth Fault Current and Voltage Inputs
The real-time measurement of the r.m.s. Earth Fault Current is displayed as percent of the rated
current of the Zero sequence Current measuring C.T. (Io= xxxx %On).
The input of the E/F element can be supplied by the residual connection of 3 phase CTS or by a
dedicated Core Balance CT.
The value of the rated secondary current of the CTS can be 1A or 5A. The configuration is made
by the movable jumpers J4 provided on the CT input card (see § 18)
The Earth Fault element can operate as a normal Zero Sequence O/C element or as a Directional
Zero Sequence O/C element.
In this case to discriminate the direction the relays uses as polarizing quantity the Zero Sequence
Residual voltage supplied by the Open-Delta windings of the system P.Ts.
The display directly gives the measurement “ Uo “ of the Secondary Zero sequence voltage and
the measurement “ o ” of the phase displacement of the Zero Sequence Current Fasor from the
Zero Sequence Voltage Fasor.
The trip time delay “ t “ of the thermal element, depends on the warming-up time constant
“ tm “ of the motor, on the previous thermal status (Ip), on the admissible continuous overload
(Ib) and, of course, on the actual load (I)
(I/Im) 2 (Ip/Im)2
t tm In 2
(I/Im) (Ib/Im)
2
tm = (1-60)min.
I = computed current
Ip = preheating current
Ib = continuously admissible current (1-1.3)Im, step 0.01Im
Im = motor rated current (0.1-1.5)In, step 0.1In
The cooling-down time constant of the motor when running is “tm”; it is automatically changed
to " to " when the motor current drops below 0.1 lm (running/steady motor discrimination
level).
An alarm signal is issued when the simulated warming exceeds the set percentage of the
motor rated temperature Tn.
Automatic 1% drop out percentage.
To inhibit a new motor starting before cooling down to 99% Ts/n, reset after tripping of the
thermal element takes places when T< 0.99[Ts].
At motor starting this function is disabled for the set time “ 2tSt “ : when this time has elapsed, if
current exceeds the set level “ ILR ”, the relay trips with a delay of “ tLR ” sec.
- Current level :
2tSt
tSt = (1-120)s, step 1s = motor start-up time
2.2.3.2 - F46 - Current Unbalance (Negative Sequence Current) protection (See curve § 20)
Besides its contribution to the thermal image algorithm, current unbalance also controls another
inverse time element
When the relay detects the loss of the current of one phase while the currents of the other two
phases are present, the Single Phasing element “ 1 “ is tripped with a fixed 3 sec. time delay.
This function performs the protection against no-load running: it is activated by motor under
current.
Any of the output relays can be associated to the time delayed element “tI>” as well as to the
instantaneous element “I>” of this function for signalling or for blocking other relays. The
output relay controlled by the I> level remains energized for the time tI> + tBO.
After this delay the relay it is anyhow reset.
O> = (0.02 - 2)On, step 0.01On. lf O> = DIS. the function is disactivated.
- Minimum Residual Voltage level to enable the operation of the Zero Sequence O/C element
when in the Directional mode:
When “ “ is set to “Dis”, the Earth Fault element works as normal non directional
Overcurrent relay and the “ Uo “ level is disregarded.
As for function F51, any of the output relays can be associated to the instantaneous element
of “O>” as well as to the time delayed element “ tO> “.
During start-up of the motor, the unit can control an output relay used to operate the switch-over of
two-step motor starters (star-delta, resistance or impedance, autotransformer, etc...) thus allowing
to automatically manage the starting transition by controlling the following parameters:
At motor start counting of “ tTr “ begins. If during “ tTr ” the motor current drops below “ ltr “,
switching-over is operated; if motor current stays above “ ltr “ longer than “ tTr “, the Locked Rotor
element is activated.
2.2.3.10 - Autosetting
The complexity of properly set a motor protection, frequently produces undesired tripping or
non-operation of some of the functions.
The relay MM30-D can automatically select the best setting of the parameters according to motor
and system basic data. These data are:
- System frequency = Fn = 50 o 60 Hz
- Rated primary current of phase C.Ts. = In = 0-9999 A step 1A
- Rated primary current of earth fault C.T = On = 0-9999 A step 1A
- Motor rated current = lm = 0.1-1.5 In step 0.01In
- Motor starting current = lst = 0.5-9.9 Im step0.1 Im
- Starting time = tst = 1-120 s step 1s
- Transition current level = ITr = 0.11 Ist step 0.1 Ist
- Transition time = tTr = 0.5-50 s step 0,1s
Once these settings have been programmed, the “AUTOSET” function can be activated by the key
"ENTER" and all the parameters are computed and automatically set at values suitable for a
normal duty of the motor.
Particularly the motor warming-up time constant “tm” is computed so that the motor, when stopped
after having run continuously at Rated Power (Rated current Im), can be immediately restarted at
least one time.
The parameters can anyhow be manually modified if different setting is needed.
O> = Set minimum pick-up residual current : (3Io)
Uo> = Set minimum residual voltage (3Uo) to enable O> pick-up
o
= Set characteristic angle (max. torque displacement of residual current 3Io from residual
voltage 3Uo).
3Io = Actual earth fault relay’s input current
3Uo = Actual earth fault relay’s input voltage
o
= Displacement of 3Io from 3Uo
Io = Component of 3Io in the direction o
Io = 3Io cos(o-o)
Fig 1 Fig.2
The relay trips when Io>[O>] (fig.2) i.e, when the component of the input current in the measuring
direction of the relay exceeds the set trip level Is. [O>]
Operation is enabled only if the input zero-sequence voltage 3Uo is above the set level [Uo>].
The sensitivity of the relay is then proportional to cos(o -o), it is maximum when o = o
and its operation field is limited within the range:
Five key buttons allow for local management of all relay's functions.
A 8-digit high brightness alphanumerical display shows the relevant readings (xxxxxxxx)
(see synoptic table fig.1)
FIG.1
MODE SELECT + - ENTER
4. SIGNALIZATIONS
Eight signal leds (normally off) are provided:
a b c d
e f g h
Flashing when the motor heating “T” exceeds the set alarm level [Ta].
Red
a) T> Illuminated on over-temperature trip. – Also illuminated on activation of RTD
LED
input.
Flashing on tripping of the element for limitation of the number of
Red
b) St No consecutive startings.
LED
Illuminated at the end of [tBSt].
Red Flashing as soon as motor current drops below the set level [I<]
c) I<
LED Illuminated at the end of trip time delay.
Flashing as soon as motor unbalance exceeds the set level [Is>]
Red
d) Is>,1 Illuminated on trip after [tIs>] time delay or on tripping of the single phasing
LED
element.
Yellow PROG/ Flashing when in PROGRAM MODE
e)
LED I.R.F. Illuminated when relay internal fault is detected.
Red Flashing when motor current exceeds the set level [I>]
f) I>
LED Illuminated on trip after [tI>] time delay.
g) Red Flashing when earth fault current exceeds the set level [O>]
O>
LED Illuminated on trip after [tO>] time delay.
Yellow ROTOR Illuminated on trip of the Locked Rotor element (I>ILR) and/or on activation
h)
LED STALL of the Speed Control input SpC.
The reset of the leds takes place as follows:
Leds a From flashing to off automatically when motor heating drops below
the alarm level [Ta].
From steady light to off by the Reset control (front button or serial
command) provided motor heating is below the restart temperature
[Ts].
Leds b From flashing to off by the Reset control (front button or serial
command) only when the restart inhibition time is set to “manual”:
[tBSt]=Rm.
From illuminated to off when [tBSt] has expired.
Leds c,d,e,f,g From flashing to off, automatically when the lit-on cause disappears.
From ON to OFF, by "ENTER/RESET" push button only if the
tripping cause has disappeared.
Leds h From flashing or illuminated to off, automatically when the lit-on
cause disappears.
In case of auxiliary power supply failure the status of the leds is recorded and reproduced when power
supply is restored.
5. OUTPUT RELAYS
The unit MM30-D includes four (R1, R2, R3, R4) user programmable plus one diagnostic (R5) output
relays.
In the version MM30-DX the number of output relays can be increased by the addition of one or two
optional Relay Expansion modules REX-8.
The modules REX-8 are for protruding mounting and are controlled by the master module MM30-DX via
a screened twisted pair of cables connecting dedicated RS485 serial ports (see diagram herebelow).
The module REX-8 includes eight (RA, RB, RC, RD, RE, RF, RH, RG) user programmable plus one
(R-Diag) diagnostic output relays
The master module MM30-DX can control altogether up to sixteen output relays
- 4 internal R1 – R2 – R3 – R4
This second unit REX-8 is configured (by internal Dip-Switch) to operate the eight relays two by two in
parallel (only four user programmable outputs with double number of available contacts)
Any of the functions featured by the MM30-D can be programmed to control up to four out of the sixteen
user programmable output relays.
The user programmable relays (all but R5, RDIAG) are normally deenergized, i.e. energized on trip.
These relays pick-up as soon as the tripping cause appears (relays controlled by the instantaneous
functions) or at the end of the set trip time delay (relays controlled by time delayed functions).
The reset after trip takes place automatically as soon as the relevant tripping cause has been cleared.
The relays R5, R DIAG are not user programmable; they are normally energized and get deenergized
on :
6. SERIAL COMMUNICATION
The relays fitted with the serial communication option can be connected via a cable bus or (with proper
adapters) a fiber optic bus for interfacing with a Personal Computer (type IBM or compatible).
All the operations which can be performed locally (for example reading of measured data and changing
of relay’s settings) are also possible via the serial communication interface.
Furthermore the serial port allows the user to read the demand recording data.
The unit has a RS232 / RS485 interface and can be connected either directly to a P.C. via a dedicated
cable or to a RS485 serial bus, thus having many relays to exchange data with a single master P.C.
using the same physical serial line. A RS485/232 converter is available on request.
The communication protocol is MODBUS RTU (only functions 3, 4 and 16 are implemented).
Each relay is identified by its programmable address code (NodeAd) and can be called from the P.C.
A dedicated communication software (MSCOM) for Windows 95/98/NT4 SP3 (or later) is available.
Please refer to the MSCOM instruction manual for more information Microelettrica Scientifica.
7. DIGITAL INPUTS
The relay is fitted with three digital inputs activated when the relevant terminals are shorted by a cold
contact :
(*) If PT100 probes are used, it must be notified when ordering the relay.
8. TEST
Besides the normal "WATCHDOG" and "POWERFAIL" functions, a comprehensive program of self-test
and self-diagnostic provides:
Diagnostic and functional test, with checking of program routines and memory's content, run every
time the aux. power is switched-on: the display shows the type of relay and its version number.
Dynamic functional test run during normal operation every 15 min. (relay's operation is suspended
for less than 4 ms). If any internal fault is detected, the display shows a fault message, the Led
"PROG/IRF" illuminates and the relay R5 is deenergized.
Complete test activated by the keyboard or via the communication bus either with or without tripping
of the output relays.
All controls can be operated from relay's front or via serial communication bus.
The keyboard includes five hand operable buttons (MODE) - (SELECT) - (+) - (-) - (ENTER/RESET)
plus one indirect operable key (PROG) (see synoptic table a fig.1):
MODE SELECT +
-
PROG.
ENTER/RESET
If no keys is operated in 60 sec, the display comes back to the default indication (T/Tn%)
10.3 - LASTTRIP
Recording of the last 5 trippings of the relay and values of the parameters at the moment of tripping.
The memory buffer is refreshed at each new relay tripping.
Display Description
LastTr-x Indication of the recorded event (x= 0 to 4)
Example: Last event (LastTr -0)
Last but one event (LastTr-1)
etc...
xxXXXxx Date : Day, Month, Year
xx:xx:xx Hour : Hours, Minutes, Seconds
Causexxx Function which caused the last tripping:
T>; Is>; I>; O>; I<; LR; StN; ITr; SpC; RTD; RT.
IAxxxxxIn Current of phase A.
IBxxxxxIn Current of phase B.
ICxxxxxIn Current of phase C.
IoxxxxxOn Earth fault current.
Id/mxxx% Positive sequence component of current.
Is/mxxx% Negative sequence component of current.
T/Tnxxx% Motor heating
UoxxxxxV Zero-sequence secondary voltage
oxxxxx° Io/Uo phase displacement angle in degrees.
12. PROGRAMMING
The relay is supplied with the standard default programming used for factory test. [ Values here below
reported in the “ Display “ column ].
All parameters can be modified as needed in the mode PROG and displayed in the mode SET DISP
Local Programming by the front face key board is enabled only if no input current is detected
(main switch open). Programming via the serial port is always enabled but a password is
required to access the programming mode. The default password is the null string; in the
standard application program for communication “MS-COM” it is also provided an emergency
password which can be disclosed on request only.
As soon as programming is enabled, the Led PRG/IRF flashes and the reclosing lock-out relay R5 is
deenergized. Enter MODE "PROG" and SELECT either "SETTINGS" for programming of parameters
or "FRELAY" for programming of output relays configuration; enable programming by the indirect
operation key PROG.
The key SELECT now scrolls the available parameters. By the key (+) , (-) the displayed values can be
modified; to speed up parameter's variation press the key SELECT while "+" or "-" are pressed.
Press key "ENTER/RESET" to validate the set values.
12.1 - PROGRAMMING OF FUNCTIONS SETTINGS
In 500 Ap
Mode PROG menu SETTINGS. (Production standard settings here under shown).
Display Description Setting Range Step Unit
xxXXXxx Current date DDMMMYY - -
xx:xx:xx Current time HH:MM:SS - -
NodAd 1 Identification number for connection on serial communication bus 1 - 250 1 1
Fn 50 Hz Mains frequency 50 - 60 10 Hz
In 500Ap Rated primary current of the phase C.Ts. 1 - 9999 1 Ap
Rated primary current of the C.Ts. or of the tore C.T. detecting
On 500Ap 1 - 9999 1 Ap
earth fault current
Motor full-load current
Im 1.0In 0.1 – 1.5 0.01 In
(p.u. of phase C.Ts. rated current)
Ist 6Im Motor start-up current (p.u. of motor full load current) 0.5 – 10 0.1 Im
tst 5s Motor starting time 1 – 120 1 s
Switch-over current of motor starter
ITr0.5Ist Dis – 0.1 – 1 0.1 Ist
(p.u. of motor starting current)
Max switch-over time from reduced to full voltage operation
tTr 6s 0.5 – 50 0.1 s
during motor starting.
I> - 2 - 4
This is the name of This dash means The number 2 This dash means The number 4 means
protective element that output relay means that that output relay that output relay 4 will
number 1 is not output relay 2 will number 3 is not operate when this
assigned to this operate when assigned to this element trips
element this element trips element
Mode PROG menu FRELAY (Settings out of production are here under shown).
The key "+" operates as cursor; it moves through the digits corresponding to the four relays programmable for any
functions in the sequence 4-3-2-1-L-K-J-I-H-G-F-E-D-C-B-A (4=Relay R4 etc.) and makes start flashing the
information actually present in the digit. The information present in the digit can be either the number/letter of the
relay (if this was already associated to the function actually on programming) or a dot (-) if this place was not yet
addressed.
WARNING
Running the WithTRIP test will operate all of the output relays. Care must be taken to ensure that no
unexpected or harmful equipment operations will occur as a result of running this test.
It is generally recommended that this test be run only in a bench test environment or after all dangerous
output connections are removed.
14. MAINTENANCE
No maintenance is required. Periodically a functional check-out can be made with the test procedures
described under MANUAL TEST chapter. In case of malfunctioning please contact Microelettrica
Scientifica Service or the local Authorised Dealer mentioning the relay's Serial No reported in the label
on relays enclosure.
WARNING
Microelettrica Scientifica S.p.A. - 20089 Rozzano (MI) - Italy - Via Alberelle, 56/68
Tel. (##39) 02 575731 - Fax (##39) 02 57510940
http://www.microelettrica.com e-mail : ute@microelettrica.com
The performances and the characteristics reported in this manual are not binding and can modified at any moment without notice
21.1 Draw-out
Rotate clockwise the screws and in the horizontal position of the screws-driver mark.
Draw-out the PCB by pulling on the handle
21.2 Plug-in
Rotate clockwise the screws and in the horizontal position of the screws-driver mark.
Slide-in the card on the rails provided inside the enclosure.
Plug-in the card completely and by pressing the handle to the closed position.
Rotate anticlockwise the screws and with the mark in the vertical position (locked).