Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

MM30-D Operation Manual: Microprocessor Motor Protection Relay With Directional Earth Fault Element Type

Download as pdf or txt
Download as pdf or txt
You are on page 1of 36

Doc.

N° MO-0037-ING
MM30-D Rev. 4
Date 24.02.2003

MICROPROCESSOR
MOTOR PROTECTION RELAY
WITH DIRECTIONAL EARTH FAULT ELEMENT

TYPE
MM30-D
OPERATION MANUAL

Copyright 2010 - Microener Pag 1 of 36


Doc. N° MO-0037-ING
MM30-D Rev. 4
Date 24.02.2003

INDEX
1 General utilization and commissioning directions _____________________________________________________ 3
1.1 Storage and transportation_____________________________________________________________________ 3
1.2 Installation__________________________________________________________________________________ 3
1.3 Electrical connection__________________________________________________________________________ 3
1.4 Measuring inputs and power supply______________________________________________________________ 3
1.5 Outputs loading______________________________________________________________________________ 3
1.6 Protection earthing___________________________________________________________________________ 3
1.7 Setting and calibration_________________________________________________________________________ 3
1.8 Safety protection_____________________________________________________________________________ 3
1.9 Handling___________________________________________________________________________________ 3
1.10 Maintenance________________________________________________________________________________ 4
1.11 Fault detection and repair______________________________________________________________________ 4
2 General characteristics and operation_______________________________________________________________ 4
2.1 Power supply________________________________________________________________________________ 4
2.2 Operation an Algorithms_______________________________________________________________________ 5
2.2.1 Reference input variable__________________________________________________________________ 5
2.2.2 Input quantities_________________________________________________________________________ 5
2.2.2.1 Mains Frequency_________________________________________________________________ 5
2.2.2.2 Phase current inputs_______________________________________________________________ 5
2.2.2.3 Earth Fault current and voltage inputs_________________________________________________ 6
2.2.3 Function and Setting_____________________________________________________________________ 7
2.2.3.1 F49 – Thermal image______________________________________________________________ 7
2.2.3.2 F51LR – Locked Rotor Protection (Rotor jam)___________________________________________ 8
2.2.3.3 F46 – Current Unbalance (Negative Sequence current) protection___________________________ 8
2.2.3.4 F47 – Single Phasing______________________________________________________________ 8
2.2.3.5 F37 – No-Load Running protection____________________________________________________ 8
2.2.3.6 F51 – Overcurrent protection________________________________________________________ 9
2.2.3.7 F64 – Earth Fault protection_________________________________________________________ 9
2.2.3.8 Limitation of the Stats Number_______________________________________________________ 10
2.2.3.9 Starting Sequence control__________________________________________________________ 10
2.2.3.10 Autosetting______________________________________________________________________ 11
2.3 Operational of the directional Earth Fault Element___________________________________________________ 12
2.4 Clock and Calendar___________________________________________________________________________ 13
2.4.1 Clock synchronization_____________________________________________________________________ 13
2.4.2 Date and time setting_____________________________________________________________________ 13
2.4.3 Time resolution__________________________________________________________________________ 13
2.4.4 Operation during power off_________________________________________________________________ 13
2.4.5 Time tolerance__________________________________________________________________________ 13
3 Controls and measurements_______________________________________________________________________ 14
4 Signalization_____________________________________________________________________________________ 15
5 Output relays____________________________________________________________________________________ 16
6 Serial communication_____________________________________________________________________________ 17
7 Digital inputs____________________________________________________________________________________ 18
8 Test____________________________________________________________________________________________ 18
9 Keyboard and display operation____________________________________________________________________ 19
10 Reading of measurements and recorded parameters___________________________________________________ 20
10.1 ACT. MEAS (Actual measure)_____________________________________________________________ 20
10.2 MAX VAL (Max values)_________________________________________________________________ 20
10.3 LASTTRIP (Last trip)____________________________________________________________________ 21
10.4 TRIP NUM (Trip number)_________________________________________________________________ 21
11 Reading of programmed settings and relay’s configuration_____________________________________________ 21
12 Programming____________________________________________________________________________________ 22
12.1 Programming of functions settings__________________________________________________________ 22
12.2 Programming the configuration of output relay_________________________________________________ 24
13 Manual and automatic test operation________________________________________________________________ 25
13.1 Mode “ TESTPROG “ subprogram “ W/O TRIP “_______________________________________________ 25
13.2 Mode “ TESTPROG “ subprogram “ With TRIP “_______________________________________________ 25
14 Maintenance_____________________________________________________________________________________ 25
15 Power frequency insulation test_____________________________________________________________________ 25
15 Electrical characteristics___________________________________________________________________________ 26
16 Connection diagram (Standard Output)_______________________________________________________________ 27
16.1 Connection Diagram (Double Output)___________________________________________________________ 27
17 Wiring the serial communication bus________________________________________________________________ 28
18 Change phase rated input 1A or 5A__________________________________________________________________ 28
19 Thermal image curves_____________________________________________________________________________ 29
20 Inverse time unbalance protection element___________________________________________________________ 30
21 Direction for pcb’s draw-out and plug-in_____________________________________________________________ 31
21.1 Draw-out______________________________________________________________________________ 31
21.2 Plug-in________________________________________________________________________________ 31
22 Overall dimensions / Mounting_____________________________________________________________________ 32
23 Keyboard operational diagram______________________________________________________________________ 33
24 Setting’s form____________________________________________________________________________________ 34

Copyright 2010 - Microener Pag 2 of 36


Doc. N° MO-0037-ING
MM30-D Rev. 4
Date 24.02.2003

1. General utilization and commissioning directions

Always make reference to the specific description of the product and to the Manufacturer's instruction.
Carefully observe the following warnings.

1.1 - STORAGE AND TRANSPORTATION,

must comply with the environmental conditions stated on the product's instruction or by the applicable
IEC standards.

1.2 - INSTALLATION,

must be properly made and in compliance with the operational ambient conditions stated by the
Manufacturer.

1.3 - ELECTRICAL CONNECTION,

must be made strictly according to the wiring diagram supplied with the Product, to its electrical
characteristics and in compliance with the applicable standards particularly with reference to human
safety.

1.4 - MEASURING INPUTS AND POWER SUPPLY,

carefully check that the value of input quantities and power supply voltage are proper and within the
permissible variation limits.

1.5 - OUTPUTS LOADING,

must be compatible with their declared performance.

1.6 - PROTECTION EARTHING

When earthing is required, carefully check its effectiveness.

1.7 - SETTING AND CALIBRATION

Carefully check the proper setting of the different functions according to the configuration of the
protected system, the safety regulations and the co-ordination with other equipment.

1.8 - SAFETY PROTECTION

Carefully check that all safety means are correctly mounted, apply proper seals where required and
periodically check their integrity.

1.9 - HANDLING

Notwithstanding the highest practicable protection means used in designing M.S. electronic circuits,
the electronic components and semiconductor devices mounted on the modules can be seriously
damaged by electrostatic voltage discharge which can be experienced when handling the modules.
The damage caused by electrostatic discharge may not be immediately apparent but the design
reliability and the long life of the product will have been reduced. The electronic circuits reduced by
M.S. are completely safe from electrostatic discharge (8 KV IEC 255.22.2) when housed in their
case; withdrawing the modules without proper cautions expose them to the risk of damage.

Copyright 2010 - Microener Pag 3 of 36


Doc. N° MO-0037-ING
MM30-D Rev. 4
Date 24.02.2003
a. Before removing a module, ensure that you are at the same electrostatic potential
as the equipment by touching the case.

b. Handle the module by its front-plate, frame, or edges of the printed circuit board.
Avoid touching the electronic components, printed circuit tracks or connectors.

c. Do not pass the module to any person without first ensuring that you are both at
the same electrostatic potential. Shaking hands achieves equipotential.

d. Place the module on an antistatic surface, or on a conducting surface which is at


the same potential as yourself.

e. Store or transport the module in a conductive bag.

More information on safe working procedures for all electronic equipment can be found
in BS5783 and IEC 147-OF.

1.10 - MAINTENANCE
Make reference to the instruction manual of the Manufacturer ;
maintenance must be carried-out by specially trained people and in strict conformity
with the safety regulations.

1.11 - FAULT DETECTION AND REPAIR


Internal calibrations and components should not be altered or replaced.
For repair please ask the Manufacturer or its authorised Dealers.

Misapplication of the above warnings and instruction relieves the Manufacturer of any liability.

2. GENERAL

Input currents are supplied to 3 current transformers: - two measuring phase current (the third current is
computed as vector summation of the two others) - one measuring the earth fault zero-sequence
current.
Phase current rated input can be 1 or 5A (Selectable by movable bridges on relay card)
Zero sequence rated input is 1A.
Zero sequence voltage input is supplied to one voltage transformer.
Rated input voltage 100V – 50/60Hz from Y/open  connected PTS with ratio U1 : 3 / 100:3 V.
Make electric connection in conformity with the diagram reported on relay's enclosure.
Check that input currents are same as reported on the diagram and on the test certificate.
The auxiliary power is supplied by a built-in interchangeable module fully isolated an self protected.

2.1 POWER SUPPLY

The relay can be fitted with two different types of power supply module :

24V(-20%) / 110V(+15%) a.c. 80V(-20%) / 220V(+15%) a.c.


a) -  b) - 
24V(-20%) / 125V(+20%) d.c. 90V(-20%) / 250V(+20%) d.c.

Before energising the unit check that supply voltage is within the allowed limits.

Copyright 2010 - Microener Pag 4 of 36


Doc. N° MO-0037-ING
MM30-D Rev. 4
Date 24.02.2003

2.2 – Operation and Algorithms


2.2.1 – Reference input variables
Display Description Setting Range Step Unit
NodAd 1 Identification number for connection serial communication 1 - 250 1 1
Fn 50 Hz Mains frequency 50 - 60 10 Hz
In 500Ap Rated primary current of the phase C.Ts. 1 - 9999 1 A
Rated primary current of the C.Ts. or of the tore C.T.
On 500Ap 1 - 9999 1 A
detecting earth fault current
Im 1.0In Motor full-load current (p.u. of phase C.Ts. rated current) 0.1 – 1.5 0.01 In
Ist 6Im Motor starting current (p.u. of motor full load current) 0.5 – 10 0.1 Im
tst 5s Motor starting time 1 – 120 1 s
Switch-over current for control of two-step motor starter
Itr0.5Ist Dis – 0.1 – 1 0.1 Ist
(p.u. of motor starting current)
tTr 6s Max switch-over time from start-up 0.5 – 50 0.1 s

2.2.2 – Input quantities


2.2.2.1 – Mains Frequency
The relay can operate either in 50Hz or 60Hz systems.
The rated Mains Frequency “ Fn “ must be set accordingly.
2.2.2.2 – Phase Current inputs
The relay directly displays the r.m.s. value of the Phase Currents “ IA “, “ IB ”, “ IC ” flowing in the
Primary of the input Current Transformers and refers all its measurements to that value.
To make the relay properly working with any C.T., when programming the relay settings we have
to input the value of the Rated Primary Current “ In “ of the phase C.Ts.

For the Phase Current inputs, 1A or 5A configuration can be selected by moving the jumpers J1
and J2 provided on the C.T. input card (See § 18).
Example :
 Phase CTs 1500/5A and Core Balance CT 100/1A
 Set In = 1500A and On = 100A
 Configure CT input card with jumpers J1, J2 in the 5A position.

Only phase A and C currents are measured, whereas the current of the phase B is computed as
vector summation of the currents of the other two phases.
The algorithm is based on the following considerations coming from well-known vector relations
among the three-phase currents and the zero sequence current.
- In any circumstance – currents balanced or not, sinusoidal or not – it is always true that:
1 IA  IB  IC  I0  0
- When no Earth Fault exists (I0 = 0)
2 IA  IB  IC  0  IB  IA  IC 
The earth fault protection element is independently supplied by the residual current coming either
from the residual connection of the 3 system C.Ts. or from the core balance C.T.
If any Earth Fault is experienced (I0  0) the Earth Fault Protection Element trips independently
from the phase current measuring elements.

Copyright 2010 - Microener Pag 5 of 36


Doc. N° MO-0037-ING
MM30-D Rev. 4
Date 24.02.2003

If no Earth Fault is present (I0 = 0), the equation (2) is valid, no matter if currents are balanced or
not, sinusoidal or not.
The third phase current is calculated, in real time, as vector summation of the other two-phase
currents.

Similarly, the Positive Sequence Current Component “ Id “ and Negative Sequence component
“ Is “, with no Earth Fault, are computed according to the normal equations of the system
symmetrical components, using two currents only:


I A  Id  Is  
I C  α I A  Is α  α

2
 Is 3  I C  I A e j120



I C  α Id  α Is 
 2 2

I C  α I A  Id α  α
2



Id 3  I C  I A e j120
In case of Earth Fault the Earth Fault Element trips before tripping of the unbalance element.
- During Faults
A) Single phase to earth Fault
Trip of the earth fault element directly measuring the Residual Current.
B) Two Phase Fault
In any case one of the currents directly measured is involved, so the relay trips correctly.
C) Two Phase to Earth Fault
Same as A + B
D) Three Phase Fault
All the three currents are correctly measured (in any case two directly).
2.2.2.3 – Earth Fault Current and Voltage Inputs
The real-time measurement of the r.m.s. Earth Fault Current is displayed as percent of the rated
current of the Zero sequence Current measuring C.T. (Io= xxxx %On).
The input of the E/F element can be supplied by the residual connection of 3 phase CTS or by a
dedicated Core Balance CT.
The value of the rated secondary current of the CTS can be 1A or 5A. The configuration is made
by the movable jumpers J4 provided on the CT input card (see § 18)

The Earth Fault element can operate as a normal Zero Sequence O/C element or as a Directional
Zero Sequence O/C element.
In this case to discriminate the direction the relays uses as polarizing quantity the Zero Sequence
Residual voltage supplied by the Open-Delta windings of the system P.Ts.
The display directly gives the measurement “ Uo “ of the Secondary Zero sequence voltage and
the measurement “ o ” of the phase displacement of the Zero Sequence Current Fasor from the
Zero Sequence Voltage Fasor.

Copyright 2010 - Microener Pag 6 of 36


Doc. N° MO-0037-ING
MM30-D Rev. 4
Date 24.02.2003

2.2.3 – Functions and Settings

2.2.3.1 – F49 – Thermal Image (See curves § 19)

The current “ I “ producing motor warming-up is computed as a conventional composition of


Positive Sequence “ Id “ and Negative Sequence “ Is “ components of the motor current.

- Computed current: I  Id2  3Is2

- Allowed overloading time (See Curve § 19)

The trip time delay “ t “ of the thermal element, depends on the warming-up time constant
“ tm “ of the motor, on the previous thermal status (Ip), on the admissible continuous overload
(Ib) and, of course, on the actual load (I)

 (I/Im) 2  (Ip/Im)2 
t  tm In  2
 (I/Im)  (Ib/Im) 
2

tm = (1-60)min.
I = computed current
Ip = preheating current
Ib = continuously admissible current (1-1.3)Im, step 0.01Im
Im = motor rated current (0.1-1.5)In, step 0.1In

- Steady motor cooling-down time constant: to = (1-10)tm, step 1tm

The cooling-down time constant of the motor when running is “tm”; it is automatically changed
to " to " when the motor current drops below 0.1 lm (running/steady motor discrimination
level).

- Thermal prealarm : Ta/n = (50-110)%Tn, step 1%Tn

An alarm signal is issued when the simulated warming exceeds the set percentage of the
motor rated temperature Tn.
Automatic 1% drop out percentage.

- Restart inhibition: Ts/n = (40-100)%Tn, step 1%Tn

To inhibit a new motor starting before cooling down to 99% Ts/n, reset after tripping of the
thermal element takes places when T< 0.99[Ts].

Copyright 2010 - Microener Pag 7 of 36


Doc. N° MO-0037-ING
MM30-D Rev. 4
Date 24.02.2003

2.2.3.2 – F51LR – Locked Rotor Protection (Rotor jam)

At motor starting this function is disabled for the set time “ 2tSt “ : when this time has elapsed, if
current exceeds the set level “ ILR ”, the relay trips with a delay of “ tLR ” sec.

- Current level :

ILR = (1-5)Im, step 0.1Im. lf ILR = DIS. the function is disactivated.

- Trip Time delay :

tLR = (1-25)s, step 1s

- Inhibition time of the locked rotor function:

2tSt
tSt = (1-120)s, step 1s = motor start-up time

2.2.3.2 - F46 - Current Unbalance (Negative Sequence Current) protection (See curve § 20)

Besides its contribution to the thermal image algorithm, current unbalance also controls another
inverse time element

-Minimum Negative Sequence current operation level

Is> = (0.1-0.8)Im, step 0.1lm. lf ls> = DIS. the function is disactivated.

- Time current curve

tIs> = (1-8)s, step 1s


0.9
Actual trip time delay is given by: t tIs  (tIs  trip time at Is  Im)
Is/Im  0.1
“ Is ” is the actual Negative Sequence Current

2.2.3.4 – F47 – Single Phasing

When the relay detects the loss of the current of one phase while the currents of the other two
phases are present, the Single Phasing element “ 1 “ is tripped with a fixed 3 sec. time delay.

2.2.3.5 - F37 - No-Load Running protection

This function performs the protection against no-load running: it is activated by motor under
current.

- Under current level

I< = (0.15-1)Im, step 0,01Im. lf I< = DIS. the function is disactivated.

When current is below 0.1lm in all phases the function is activated.

- Trip time delay = 3 sec.


Copyright 2010 - Microener Pag 8 of 36
Doc. N° MO-0037-ING
MM30-D Rev. 4
Date 24.02.2003

Copyright 2010 - Microener Pag 9 of 36


Doc. N° MO-0037-ING
MM30-D Rev. 4
Date 24.02.2003

2.2.3.6 - F51 - Overcurrent protection

- Minimum Pick-up Current level in at least one phase :

I> = (1-5)Ist, step 0.1 Ist (limited to 20 times In)


Ist (motor locked rotor current) = (0.5-10)Im, step 0.1Im
lf I> = DIS. the function is disactivated

- Trip time delay

tI> = (0.05-1)s, step 0,01s.

Any of the output relays can be associated to the time delayed element “tI>” as well as to the
instantaneous element “I>” of this function for signalling or for blocking other relays. The
output relay controlled by the I> level remains energized for the time tI> + tBO.
After this delay the relay it is anyhow reset.

tBO = (0.05-0.5)s, step 0.05s.

2.2.3.7 - F64 - Earth Fault protection

- Minimum Pick-up Zero Sequence Residual Current level :

O> = (0.02 - 2)On, step 0.01On. lf O> = DIS. the function is disactivated.

- Trip time delay:

tO> = (0.05-5)s, step 0.01s.

- Minimum Residual Voltage level to enable the operation of the Zero Sequence O/C element
when in the Directional mode:

Uo> = (2-25)secondary V, step 1V.

- Max torque angle in the Directional operation mode (see § 2.3):

 = (0-359-Dis)°, step 1°.

When “  “ is set to “Dis”, the Earth Fault element works as normal non directional
Overcurrent relay and the “ Uo “ level is disregarded.

As for function F51, any of the output relays can be associated to the instantaneous element
of “O>” as well as to the time delayed element “ tO> “.

Copyright 2010 - Microener Pag 10 of 36


Doc. N° MO-0037-ING
MM30-D Rev. 4
Date 24.02.2003

2.2.3.8 - Limitation of the Starts Number

- Allowed Number of startings:

St No = (1-60), step 1 lf St No = DIS the number of startings is unlimited.

- Time interval in which the StNo is counted:

tStNo = (1-60)min. step 1 min.


lf during the time “tStN” the “StNo” is attained, a new start is inhibited for the time “tBst”.

- Restart Inhibition time:

tBst = (1-60)min., step 1min. or Rm

On the set tBst= 0 the inhibition is disactivated


On the set tBst= Rm the inhibition is permanent until the RESET key is operated.

2.2.3.9 - Starting Sequence Control

During start-up of the motor, the unit can control an output relay used to operate the switch-over of
two-step motor starters (star-delta, resistance or impedance, autotransformer, etc...) thus allowing
to automatically manage the starting transition by controlling the following parameters:

- Switch-over (transition) current:

ITr = (0.1-1)Ist, step 0.1Ist

- Maximum switch-over (transition) time delay:

tTr = (0.5-50)s, step 0.1s.

At motor start counting of “ tTr “ begins. If during “ tTr ” the motor current drops below “ ltr “,
switching-over is operated; if motor current stays above “ ltr “ longer than “ tTr “, the Locked Rotor
element is activated.

Copyright 2010 - Microener Pag 11 of 36


Doc. N° MO-0037-ING
MM30-D Rev. 4
Date 24.02.2003

2.2.3.10 - Autosetting

The complexity of properly set a motor protection, frequently produces undesired tripping or
non-operation of some of the functions.
The relay MM30-D can automatically select the best setting of the parameters according to motor
and system basic data. These data are:

- System frequency = Fn = 50 o 60 Hz
- Rated primary current of phase C.Ts. = In = 0-9999 A step 1A
- Rated primary current of earth fault C.T = On = 0-9999 A step 1A
- Motor rated current = lm = 0.1-1.5 In step 0.01In
- Motor starting current = lst = 0.5-9.9 Im step0.1 Im
- Starting time = tst = 1-120 s step 1s
- Transition current level = ITr = 0.11 Ist step 0.1 Ist
- Transition time = tTr = 0.5-50 s step 0,1s

Once these settings have been programmed, the “AUTOSET” function can be activated by the key
"ENTER" and all the parameters are computed and automatically set at values suitable for a
normal duty of the motor.
Particularly the motor warming-up time constant “tm” is computed so that the motor, when stopped
after having run continuously at Rated Power (Rated current Im), can be immediately restarted at
least one time.
The parameters can anyhow be manually modified if different setting is needed.

Copyright 2010 - Microener Pag 12 of 36


Doc. N° MO-0037-ING
MM30-D Rev. 4
Date 24.02.2003

2.3 - OPERATION OF THE DIRECTIONAL EARTH FAULT ELEMENT


It is assumed :


O> = Set minimum pick-up residual current : (3Io)

Uo> = Set minimum residual voltage (3Uo) to enable O> pick-up
o
 = Set characteristic angle (max. torque displacement of residual current 3Io from residual
voltage 3Uo).

3Io = Actual earth fault relay’s input current

3Uo = Actual earth fault relay’s input voltage
o
 = Displacement of 3Io from 3Uo

Io = Component of 3Io in the direction o
Io = 3Io cos(o-o)

Fig 1 Fig.2

The relay measurement is:

3Io x cos( o -o) = Io

The relay trips when Io>[O>] (fig.2) i.e, when the component of the input current in the measuring
direction of the relay exceeds the set trip level Is. [O>]

Operation is enabled only if the input zero-sequence voltage 3Uo is above the set level [Uo>].

The sensitivity of the relay is then proportional to cos(o -o), it is maximum when o = o
and its operation field is limited within the range:

(o - 90°) < o < ( + 90) (fig.1)


The characteristic angle of the relay must be selected according to the kind of earthing of the installation
which has to be protected against earth fault; typical setting are:

 UNEARTHED NEUTRAL o = 90°


 NEUTRAL EARTHED VIA RESISTOR o = 0°
 SOLIDLY EARTHED NEUTRAL o = 60°

Copyright 2010 - Microener Pag 13 of 36


Doc. N° MO-0037-ING
MM30-D Rev. 4
Date 24.02.2003

2.4 - CLOCK AND CALENDAR


The unit features a built in clock calendar with Years, Months, Days, Hours, Minutes, Seconds, Tenths
of seconds and Hundredths of seconds.
2.4.1 - Clock synchronization.
The clock can be synchronized via the serial communication interface.
The following synchronization periods can be set: 5, 10, 15, 30, 60 minutes.
Synchronization can also be disabled, in which case the relay ignores the serial broadcast signal.
In case synchronization is enabled, the unit expects to receive a sync signal at the beginning of every
hour and once every Tsyn minutes. When a sync signal is received, the clock is automatically set to
the nearest expected synchronization time.
For example: if Tsyn is 10min and a sync signal is received at 20:03:10 January the 10th, 98, then the
clock is set to 20:00:00 January the 10th, 1998.
On the other hand, if the same sync signal were received at 20:06:34, the clock would be set to
th
20:10:00, January the 10 98.
Note that if a sync signal is received exactly in the middle of a Tsyn period, the clock is set to the
previous expected synchronization time.
2.4.2 - Date and time setting.
When the PROG/SETTINGS menu is entered, the current date is displayed with one of the groups of
digits (YY, MMM or DD) blinking.
The DOWN key operates as a cursor. It moves through the groups of digits in the sequence YY =>
MMM => DD => YY => …
The UP key allows the user to modify the currently blinking group of digits.
If the ENTER button is pressed the currently displayed date is set.
Pressing the SELECT button the current time is displayed which can be modified using the same
procedure as for the date.
If synchronization is enabled and the date (or time) is modified, the clock is stopped until a sync
signal is received via the serial port. This allows the user to manually set many units and have them
to start their clocks in a synchronized fashion.
If synchronization is disabled the clock is never stopped.
Note that the setting of a new time always clears 10ths and 100ths of sec.
2.4.3 - Time resolution.
The clock has a 10ms resolution. This means that any event can be time-stamped with a 10ms
accuracy, although the information concerning 10ths and 100ths of sec. can be accessed only via the
serial communication interface.
2.4.4 - Operation during power off.
The unit has an on board Real Time Clock which maintains time information for at least 1 hour in
case of power supply failure.
2.4.5 - Time tolerance.
During power on, time tolerance depends on the on board crystal (+/-50ppm typ, +/-100ppm max.
over full temperature range).
During power off, time tolerance depends on the RTC’s oscillator (+65 /–270 ppm max over full
temperature range).

Copyright 2010 - Microener Pag 14 of 36


Doc. N° MO-0037-ING
MM30-D Rev. 4
Date 24.02.2003

3. CONTROLS AND MEASUREMENTS

Five key buttons allow for local management of all relay's functions.
A 8-digit high brightness alphanumerical display shows the relevant readings (xxxxxxxx)
(see synoptic table fig.1)

FIG.1
MODE SELECT + - ENTER

ACT MEAS Actual measurement values

MAX VAL. Max. values measured


MEASURES Scanning of
LASTTRIP Values measured at last five events the menus by
Measurements
N° of tripping for each function the key
display TRIP NUM
“+” “-”

SETTINGS Display of setting


SET DISP
FRELAY Display of configuration of output relay
Setting Program
display Paramater scanning
by the key
(*) PRO SELECT
SETTINGS Setting of parameters
PROGR G
Parameter modification
FRELAY Configuration of output by the key “+” “-”
Set Programming
relays
Set validation
by the key ENTER

W/O TRIP Test with operation of signals


TEST PRG only
Test activation
WithTRIP Test with operation of signals and output relays
Functional Test by the key ENTER
(*)
(*) Enabled only if input current is zero

Pressing this button progressively


The + and - buttons are used to
selects between
select the actual measurement or
Measurements Display,
display desired when in
Setting Display, Programming,
Measurements Display or Settings
and Test modes
Display modes. When in Program
MODE SELECT + mode, these buttons increase or
The SELECT button chooses decrease the value of the
which category of values within the displayed setting.
chosen mode to display
-
PROG. When in Program mode, and when
When in Program mode, this
all input currents are zero,
button stores the newly selected
pressing this recessed button
value. If not in Program mode and ENTER/RESET places the relay into active
the relay has tripped, this button
programming mode, allowing any
resets the relay and all output
or all of the relay’s settings to be
contacts. If not tripped, this button
altered.
restores the default display.

Copyright 2010 - Microener Pag 15 of 36


Doc. N° MO-0037-ING
MM30-D Rev. 4
Date 24.02.2003

4. SIGNALIZATIONS
Eight signal leds (normally off) are provided:
a b c d

T> StNo I< Is>,1

PROG/ I> O> ROTOR


I.R.F. STALL

e f g h
 Flashing when the motor heating “T” exceeds the set alarm level [Ta].
Red
a) T>  Illuminated on over-temperature trip. – Also illuminated on activation of RTD
LED
input.
 Flashing on tripping of the element for limitation of the number of
Red
b) St No consecutive startings.
LED
 Illuminated at the end of [tBSt].
Red  Flashing as soon as motor current drops below the set level [I<]
c) I<
LED  Illuminated at the end of trip time delay.
 Flashing as soon as motor unbalance exceeds the set level [Is>]
Red
d) Is>,1  Illuminated on trip after [tIs>] time delay or on tripping of the single phasing
LED
element.
Yellow PROG/  Flashing when in PROGRAM MODE
e)
LED I.R.F.  Illuminated when relay internal fault is detected.
Red  Flashing when motor current exceeds the set level [I>]
f) I>
LED  Illuminated on trip after [tI>] time delay.
g) Red  Flashing when earth fault current exceeds the set level [O>]
O>
LED  Illuminated on trip after [tO>] time delay.
Yellow ROTOR  Illuminated on trip of the Locked Rotor element (I>ILR) and/or on activation
h)
LED STALL of the Speed Control input SpC.
The reset of the leds takes place as follows:
 Leds a  From flashing to off automatically when motor heating drops below
the alarm level [Ta].
 From steady light to off by the Reset control (front button or serial
command) provided motor heating is below the restart temperature
[Ts].
 Leds b  From flashing to off by the Reset control (front button or serial
command) only when the restart inhibition time is set to “manual”:
[tBSt]=Rm.
 From illuminated to off when [tBSt] has expired.
 Leds c,d,e,f,g  From flashing to off, automatically when the lit-on cause disappears.
 From ON to OFF, by "ENTER/RESET" push button only if the
tripping cause has disappeared.
 Leds h  From flashing or illuminated to off, automatically when the lit-on
cause disappears.
In case of auxiliary power supply failure the status of the leds is recorded and reproduced when power
supply is restored.

Copyright 2010 - Microener Pag 16 of 36


Doc. N° MO-0037-ING
MM30-D Rev. 4
Date 24.02.2003

5. OUTPUT RELAYS
The unit MM30-D includes four (R1, R2, R3, R4) user programmable plus one diagnostic (R5) output
relays.
In the version MM30-DX the number of output relays can be increased by the addition of one or two
optional Relay Expansion modules REX-8.
The modules REX-8 are for protruding mounting and are controlled by the master module MM30-DX via
a screened twisted pair of cables connecting dedicated RS485 serial ports (see diagram herebelow).
The module REX-8 includes eight (RA, RB, RC, RD, RE, RF, RH, RG) user programmable plus one
(R-Diag) diagnostic output relays
The master module MM30-DX can control altogether up to sixteen output relays

- 4 internal R1 – R2 – R3 – R4

- 8 from the first optional REX-8 module RA – RB – RC – RD – RE – RF – RG – RH

- 4 from a second optional REX-8 module RI(RA+RB) – RJ(RC+RD) – RK(RE+RF) – RL(RG+RH)

This second unit REX-8 is configured (by internal Dip-Switch) to operate the eight relays two by two in
parallel (only four user programmable outputs with double number of available contacts)
Any of the functions featured by the MM30-D can be programmed to control up to four out of the sixteen
user programmable output relays.

Copyright 2010 - Microener Pag 17 of 36


Doc. N° MO-0037-ING
MM30-D Rev. 4
Date 24.02.2003

The user programmable relays (all but R5, RDIAG) are normally deenergized, i.e. energized on trip.
These relays pick-up as soon as the tripping cause appears (relays controlled by the instantaneous
functions) or at the end of the set trip time delay (relays controlled by time delayed functions).

The reset after trip takes place automatically as soon as the relevant tripping cause has been cleared.

The relays R5, R DIAG are not user programmable; they are normally energized and get deenergized
on :

- internal fault of MM30-DX - Internal fault of REX-8


R5 - MM30-DX power supply failure R DIAG - REX-8 power supply failure
- during the programming - Interruption/fault on the serial
control communication

6. SERIAL COMMUNICATION

The relays fitted with the serial communication option can be connected via a cable bus or (with proper
adapters) a fiber optic bus for interfacing with a Personal Computer (type IBM or compatible).
All the operations which can be performed locally (for example reading of measured data and changing
of relay’s settings) are also possible via the serial communication interface.
Furthermore the serial port allows the user to read the demand recording data.
The unit has a RS232 / RS485 interface and can be connected either directly to a P.C. via a dedicated
cable or to a RS485 serial bus, thus having many relays to exchange data with a single master P.C.
using the same physical serial line. A RS485/232 converter is available on request.
The communication protocol is MODBUS RTU (only functions 3, 4 and 16 are implemented).
Each relay is identified by its programmable address code (NodeAd) and can be called from the P.C.
A dedicated communication software (MSCOM) for Windows 95/98/NT4 SP3 (or later) is available.
Please refer to the MSCOM instruction manual for more information Microelettrica Scientifica.

Copyright 2010 - Microener Pag 18 of 36


Doc. N° MO-0037-ING
MM30-D Rev. 4
Date 24.02.2003

7. DIGITAL INPUTS

The relay is fitted with three digital inputs activated when the relevant terminals are shorted by a cold
contact :

- R.T. (terminals 1-2) Remote Trip control.


Activation of the input R.T. (Terminals 1-2 shorted) produces the
following operation :
 The output relay associated to the function R.T. is energized
 The Trip Number Counter R.T. is incremented by 1 unit
 The event recording is activated and shows “CAUSE: RT”

- S.p.C. (terminals 1-3) Switch speed Control.


The Speed Control input is connected to an external N/O contact which
closes as soon as the motor is running. If the contact does not close
within the set start time [tst] from the moment the motor is energised,
the Locked Rotor function is tripped. The relay and the signal led
associated to ILR are energised, the recording on Last Trip will show
cause SpC and trip N° LR will be increased.
If the Speed Control function is not used, it must be disactivated by
programming the variable [Spc] = OFF (see § 12.1)
- RTD (terminals 1-14) Thermal probe.
This function is enabled by programming the variable
[RTD] = ON (see § 12.1)
If the function is enabled, the input RTD is activated when the resistance
connected to the terminals 1-14 exceeds the limits 50 > R1-14 > 2900.
This limits respectively correspond to “Shorted Probe” (<50) or to
“Overtemperature” (R>2900)
The activation of the input 1-14 produces the following operation:

 The relay associated to R.T. is energized


 The Led T> is lit-on.
 The counter of Trip Number of the function T> is incremented
 LastTrip recording shows : "CAUSE RTD"

(*) If PT100 probes are used, it must be notified when ordering the relay.

8. TEST
Besides the normal "WATCHDOG" and "POWERFAIL" functions, a comprehensive program of self-test
and self-diagnostic provides:
 Diagnostic and functional test, with checking of program routines and memory's content, run every
time the aux. power is switched-on: the display shows the type of relay and its version number.
 Dynamic functional test run during normal operation every 15 min. (relay's operation is suspended
for less than 4 ms). If any internal fault is detected, the display shows a fault message, the Led
"PROG/IRF" illuminates and the relay R5 is deenergized.
 Complete test activated by the keyboard or via the communication bus either with or without tripping
of the output relays.

Copyright 2010 - Microener Pag 19 of 36


Doc. N° MO-0037-ING
MM30-D Rev. 4
Date 24.02.2003

9. KEYBOARD AND DISPLAY OPERATION

All controls can be operated from relay's front or via serial communication bus.
The keyboard includes five hand operable buttons (MODE) - (SELECT) - (+) - (-) - (ENTER/RESET)
plus one indirect operable key (PROG) (see synoptic table a fig.1):

MODE SELECT +

-
PROG.

ENTER/RESET

when operated it enters one of the following operation modes


a) - White key MODE :
indicated on the display :

Reading of all the parameters measured and of those recorded


MEASURES =
in the memory
Reading of the settings and of the configuration of the output
SET DISP =
relays as programmed.
Access to the programming of the settings and of relay
PROG =
configuration.
TEST PROG = Access to the manual test routines.

When operated it selects one of the menus available in the


b) - Green key SELECT :
actual operation MODE

When operated they allow to scroll the different information


c) - Red key “+” AND “-“ :
available in the menu entered by the key SELECT

d) - Yellow key ENTER/RESET : It allows the validation of the programmed settings


 the actuation of test programs
 the forcing of the default display indication
 the reset of signal Leds.

e) - Indirect key  : Enables access to the programming.

Copyright 2010 - Microener Pag 20 of 36


Doc. N° MO-0037-ING
MM30-D Rev. 4
Date 24.02.2003

10. READING OF MEASUREMENTS AND RECORDED PARAMETERS


Enter the MODE "MEASURE", SELECT the menus "ACT.MEAS"-"MAX VAL"-"LASTTRIP"-
-"TRIP NUM", scroll available information by key "+" or "-" .
10.1 - ACT.MEAS
Actual values as measured during the normal operation.
The values displayed are continuously refreshed.
Display Description
xxXXXxx Date : Day, Month, Year
xx:xx:xx Hour : Hours, Minutes, Seconds
T/Tnxxx% Actual temperature rise displayed as % of the motor full load temperature rise (0 - 999%)
IAxxxxxA True R.M.S. value of the current of phase A displayed as primary Amps. (0 - 99999)
IBxxxxxA As above, phase B.
ICxxxxxA As above, phase C.
IoxxxxxA As above, earth fault current.
Id/mxxx% Positive sequence component of motor current displayed as % of motor full load
current. (0 - 999)%
Is/mxxx% Negative sequence component of motor current displayed as % of motor full load current.
(unbalance degree) (0 - 999)%
Uo xxxxxV RMS Voltage displayed as primary volts (0 – 65000)
o xxx° Phase displacement
h xxxxx Operation hours (0 – 65000)

If no keys is operated in 60 sec, the display comes back to the default indication (T/Tn%)

10.2 - MAX VAL


Highest values recorded during motor run after the starting time (refreshed at each higher value) plus
highest values recorded during the starting time (refreshed at each new starting).
Display Description
T/Tnxxx% Highest temperature recorded since the start of the run. (0 - 99,9)%
IAxxxxxA Current of phase A measured during run after starting time (0-99999)
IBxxxxxA As above, phase B.
ICxxxxxA As above, phase C.
IoxxxxxA As above, zero sequence current.
Id/mxxx% Positive sequence component of motor current.
Is/mxxx% Negative sequence component of motor current
SAxxxxxA Current of phase A at the starting time.
SBxxxxxA As above, phase B.
SCxxxxxA As above, phase C.
SoxxxxxA As above, earth fault current.
Sd/mxxx% Positive sequence current component at starting.
Ss/mxxx% Negative sequence current component at starting.
tStxxxxs Measurement of the Motor Starting time.
SUoxxxxV Zero sequence voltage at starting.

Copyright 2010 - Microener Pag 21 of 36


Doc. N° MO-0037-ING
MM30-D Rev. 4
Date 24.02.2003

10.3 - LASTTRIP
Recording of the last 5 trippings of the relay and values of the parameters at the moment of tripping.
The memory buffer is refreshed at each new relay tripping.
Display Description
LastTr-x Indication of the recorded event (x= 0 to 4)
Example: Last event (LastTr -0)
Last but one event (LastTr-1)
etc...
xxXXXxx Date : Day, Month, Year
xx:xx:xx Hour : Hours, Minutes, Seconds
Causexxx Function which caused the last tripping:
T>; Is>; I>; O>; I<; LR; StN; ITr; SpC; RTD; RT.
IAxxxxxIn Current of phase A.
IBxxxxxIn Current of phase B.
ICxxxxxIn Current of phase C.
IoxxxxxOn Earth fault current.
Id/mxxx% Positive sequence component of current.
Is/mxxx% Negative sequence component of current.
T/Tnxxx% Motor heating
UoxxxxxV Zero-sequence secondary voltage
oxxxxx° Io/Uo phase displacement angle in degrees.

10.4 - TRIP NUM


Counters of the number of operations for each of the relay functions.
The memory is non-volatile and can be cancelled only with a secret procedure.
Display Description
T> xxxxx Motor overload.
Is>xxxxx Current unbalance.
I> xxxxx Overcurrent.
O>xxxxx Earth fault.
I< xxxxx No load running.
LRxxxxx Locked rotor.
StN>xxxx No of consecutive startings.
ITr xxxx Too long starting.
RT xxxx Remote trip
1 xxxx Single phasing

11. READING OF PROGRAMMED SETTINGS AND RELAY'S CONFIGURATION


Enter the mode "SET DISP", select the menu "SETTINGS" or "F  RELAY", scroll information
available in the menu by keys "+" or "-".
SETTINGS= values of relay's operation parameters as programmed
F  RELAY= output relays associated to the different functions as programmed.

Copyright 2010 - Microener Pag 22 of 36


Doc. N° MO-0037-ING
MM30-D Rev. 4
Date 24.02.2003

12. PROGRAMMING

The relay is supplied with the standard default programming used for factory test. [ Values here below
reported in the “ Display “ column ].
All parameters can be modified as needed in the mode PROG and displayed in the mode SET DISP
Local Programming by the front face key board is enabled only if no input current is detected
(main switch open). Programming via the serial port is always enabled but a password is
required to access the programming mode. The default password is the null string; in the
standard application program for communication “MS-COM” it is also provided an emergency
password which can be disclosed on request only.
As soon as programming is enabled, the Led PRG/IRF flashes and the reclosing lock-out relay R5 is
deenergized. Enter MODE "PROG" and SELECT either "SETTINGS" for programming of parameters
or "FRELAY" for programming of output relays configuration; enable programming by the indirect
operation key PROG.
The key SELECT now scrolls the available parameters. By the key (+) , (-) the displayed values can be
modified; to speed up parameter's variation press the key SELECT while "+" or "-" are pressed.
Press key "ENTER/RESET" to validate the set values.
12.1 - PROGRAMMING OF FUNCTIONS SETTINGS

In 500 Ap

In is the name 500 is the Ap is the unit of measure,


of the variable setting default Amps primary.

Mode PROG menu SETTINGS. (Production standard settings here under shown).
Display Description Setting Range Step Unit
xxXXXxx Current date DDMMMYY - -
xx:xx:xx Current time HH:MM:SS - -
NodAd 1 Identification number for connection on serial communication bus 1 - 250 1 1
Fn 50 Hz Mains frequency 50 - 60 10 Hz
In 500Ap Rated primary current of the phase C.Ts. 1 - 9999 1 Ap
Rated primary current of the C.Ts. or of the tore C.T. detecting
On 500Ap 1 - 9999 1 Ap
earth fault current
Motor full-load current
Im 1.0In 0.1 – 1.5 0.01 In
(p.u. of phase C.Ts. rated current)
Ist 6Im Motor start-up current (p.u. of motor full load current) 0.5 – 10 0.1 Im
tst 5s Motor starting time 1 – 120 1 s
Switch-over current of motor starter
ITr0.5Ist Dis – 0.1 – 1 0.1 Ist
(p.u. of motor starting current)
Max switch-over time from reduced to full voltage operation
tTr 6s 0.5 – 50 0.1 s
during motor starting.

Copyright 2010 - Microener Pag 23 of 36


Doc. N° MO-0037-ING
MM30-D Rev. 4
Date 24.02.2003

Display Description Setting Range Step Unit


AUTOSET? + ENTER Automatic setting of all the following parameters computed on the
base of the setting of the previous parameters
Thermal time constant of motor while running ;
tm 34min tm is computed to allow at least one restarting with the motor at 1 - 60 1 min
its rated full load temperature
to/tm 3 Steady/running motor thermal time constant 1 - 10 1 1
Prealarm motor heating level
Ta/n 90% 50 - 110 1 %
(% of motor full-load temperature rise)
Ts/n100% Motor restart heating level 40 - 100 1 %
Ib1.05Im Rated maximum continuous motor overload 1 – 1.3 0.01 Im
StNo 6 Max. No of startings allowed within the time tStNo Dis - 1 - 60 1 -
tStNo60m Time into which the StNo is counted 1 - 60 1 m
Restart inhibition time after tripping of the function StNo
tBSt 12m 1 - 60 – Rm 1 min
(Rm = restart inhibited until manual RESET is operated)
Trip level of Locked Rotor function Dis - 1 - 5 0.1 Im
ILR 2Im
(activated after 2tst from motor start)
tLR 5s Trip time delay of LR element during run 1 – 25 1 s
Is> 0.3Im Trip level of inverse time current unbalance protection element Dis-0.1-0.8 0.1 Im
Trip time delay of inverse time current unbalance protection
tIs> 4s 1-8 1 s
when I2=Im
I< 0.2Im Trip level of undercurrent (no-load running) element Dis-0.15-1 0.01 Im
I> 2Ist Trip level of phase overcurrent element Dis - 1 - 5 0.1 Ist
tI> 0.1s Trip time delay of phase overcurrent element 0.05 - 1 0.01 s
Minimum level of residual voltage for directional operation of the
Uo> 20V 2 - 25 1 V
Earth Fault element.
Max sensitivity displacement angle of the Earth Fault directional
o 90° 0 – 359 - Dis 1 °
element. When set to Dis, operation is not directional
O> 0.1On Trip level of earth fault element Dis - 0.02 - 2 0.01 On
tO> 0.2s Trip time delay of earth fault element 0.05 - 5 0.01 s
Maximum energization time of the output relays associated to the
tBO 0.15s instantaneous functions I> and/or O> 0.05 - 0.5 0.01 s
(Blocking output with safety disactivation)
RTD OFF Enabling of the input 1 – 14 for operation of RTD function OFF – ON - -
SpC OFF Enabling of input 1 – 3 for operation of the Speed Control function OFF – ON - -
Clock synchronisation Time 5-10
Tsyn Dis m Expected time interval between sync. signal. 5 - 60 - Dis 15-30 m
60-Dis

The setting Dis indicates that the function is disactivated.

Copyright 2010 - Microener Pag 24 of 36


Doc. N° MO-0037-ING
MM30-D Rev. 4
Date 24.02.2003

12.2 - PROGRAMMING THE CONFIGURATION OF OUTPUT RELAYS

I> - 2 - 4

This is the name of This dash means The number 2 This dash means The number 4 means
protective element that output relay means that that output relay that output relay 4 will
number 1 is not output relay 2 will number 3 is not operate when this
assigned to this operate when assigned to this element trips
element this element trips element

Mode PROG menu FRELAY (Settings out of production are here under shown).
The key "+" operates as cursor; it moves through the digits corresponding to the four relays programmable for any
functions in the sequence 4-3-2-1-L-K-J-I-H-G-F-E-D-C-B-A (4=Relay R4 etc.) and makes start flashing the
information actually present in the digit. The information present in the digit can be either the number/letter of the
relay (if this was already associated to the function actually on programming) or a dot (-) if this place was not yet
addressed.

Display Description Only for Version


MM30-DX
T> ---1 Overload tripping operates relay R1, R2, R3, R4 RA,RBRL
Ta ---- Overload prealarm tripping operates relay R1, R2, R3, R4 RA,RBRL
ITr ---- Starting switch-over tripping operates relay R1, R2, R3, R4 RA,RBRL
StNo ---1 Start No limitation tripping operates relay R1, R2, R3, R4 RA,RBRL
ILR ---1 Locked Rotor tripping operates relay R1, R2, R3, R4 RA,RBRL
tI2> ---1 Time delayed unbalance tripping operates relay R1, R2, R3, R4 RA,RBRL
I< ---- No load running tripping operates relay R1, R2, R3, R4 RA,RBRL
I> ---- Instantaneous overcurrent tripping operates relay R1, R2, R3, R4 RA,RBRL
tI> ---2 Time delayed overcurrent tripping operates relay R1, R2, R3, R4 RA,RBRL
O> ---- Instantaneous earth fault tripping operates relay R1, R2, R3, R4 RA,RBRL
tO> ---2 Time delayed earth fault tripping operates relay R1, R2, R3, R4 RA,RBRL
RT ---- Remote trip command (input 1-2) operates relay R1, R2, R3, R4 RA,RBRL
1 ---1 Time delayed Phase loss tripping operates relay R1, R2, R3, R4 RA,RBRL

Copyright 2010 - Microener Pag 25 of 36


Doc. N° MO-0037-ING
MM30-D Rev. 4
Date 24.02.2003

13. MANUAL AND AUTOMATIC TEST OPERATION


13.1 Mode "TESTPROG" subprogram "W/O TRIP"
Operation of the yellow key activates a complete test of the electronics and the process routines.
All the leds are lit-on and the display shows (TEST RUN). If the test routine is successfully
completed the display switches-over to the default reading (xx:xx:xx).
If an internal fault is detected, the display shows the fault identification code and the relay R5 is
deenergized. This test can be carried-out even during the operation of the relay without affecting the
relay tripping in case a fault takes place during the test itself.
13.2 Mode "TESTPROG" subprogram "WithTRIP"
Access to this program is enabled only if the current detected is zero (breaker open).
Pressing the yellow key the display shows "TEST RUN?". A second operation of the yellow key starts
a complete test which also includes the activation of all the output relays.
The display shows (TEST RUN) with the same procedure as for the test with W/O TRIP.
Every 15 min during the normal operation the relay automatically initiates an auto test procedure
(duration  10ms). If any internal fault is detected during the auto test, the relay R5 is deenergized,
the relevant led is activated and the fault code is displayed.
Further operation of key SELECT instead of the TEST programs gives the indication of the version
and production date of the firmware.

WARNING

Running the WithTRIP test will operate all of the output relays. Care must be taken to ensure that no
unexpected or harmful equipment operations will occur as a result of running this test.
It is generally recommended that this test be run only in a bench test environment or after all dangerous
output connections are removed.
14. MAINTENANCE
No maintenance is required. Periodically a functional check-out can be made with the test procedures
described under MANUAL TEST chapter. In case of malfunctioning please contact Microelettrica
Scientifica Service or the local Authorised Dealer mentioning the relay's Serial No reported in the label
on relays enclosure.

WARNING

In case of Internal Relay Fault detection, proceed as here-below indicated :


 If the error message displayed is one of the following “DSP Err”, “ALU Err” ,”KBD Err” ,”ADC Err”,
switch off power supply and switch-on again. If the message does not disappear send the relay to
Microelettrica Scientifica (or its local dealer) for repair.
 If the error message displayed is “E2P Err”, try to program any parameter and then run “W/OTRIP”.
 If message disappear please check all the parameters.
 If message remains send the relay to Microelettrica Scientifica (or its local dealer) for repair.
15. POWER FREQUENCY INSULATION TEST
Every relay individually undergoes a factory insulation test according to IEC255-5 standard at
2 kV, 50 Hz 1min. Insulation test should not be repeated as it unusefully stresses the dielectrics.
When doing the insulation test, the terminals relevant to serial output must always be short circuited to
ground. When relays are mounted in switchboards or relay boards that have to undergo the insulation
tests, the relay modules must be drawn-out of their enclosures and the test must only include the fixed
part of the relay with its terminals and the relevant connections. This is extremely important as
discharges eventually tacking place in other parts or components of the board can severely damage the
relays or cause damages, not immediately evident to the electronic components.
Copyright 2010 - Microener Pag 26 of 36
Doc. N° MO-0037-ING
MM30-D Rev. 4
Date 24.02.2003

15. ELECTRICAL CHARACTERISTICS


APPROVAL: CE – RINA – UL and CSA approval File : E202083
REFERENCE STANDARDS IEC 60255 - EN50263 - CE Directive - EN/IEC61000 - IEEE C37

 Dielectric test voltage IEC 60255-5 2kV, 50/60Hz, 1 min.


 Impulse test voltage IEC 60255-5 5kV (c.m.), 2kV (d.m.) – 1,2/50s : 5kV (c.m.), 2
 Insulation resistance > 100M

Environmental Std. Ref. (IEC 68-2-1 - 68-2-2 - 68-2-33)


 Operation ambient temperature -10°C / +55°C
 Storage temperature -25°C / +70°C
 Humidity IEC68-2-3 RH 93% Without Condensing AT 40°C

CE EMC Compatibility (EN50081-2 - EN50082-2 - EN50263)


 Electromagnetic emission EN55022 industrial environment
 Radiated electromagnetic field immunity test IEC61000-4-3 level 3 80-1000MHz 10V/m
ENV50204 900MHz/200Hz 10V/m
 Conducted disturbances immunity test IEC61000-4-6 level 3 0.15-80MHz 10V
 Electrostatic discharge test IEC61000-4-2 level 4 6kV contact / 8kV air
 Power frequency magnetic test IEC61000-4-8 1000A/m 50/60Hz
 Pulse magnetic field IEC61000-4-9 1000A/m, 8/20s
 Damped oscillatory magnetic field IEC61000-4-10 100A/m, 0.1-1MHz
 Electrical fast transient/burst IEC61000-4-4 level 3 2kV, 5kHz
 HF disturbance test with damped oscillatory wave (1MHz IEC60255-22-1 class 3 400pps, 2,5kV (m.c.), 1kV (d.m.)
burst test)
 Oscillatory waves (Ring waves) IEC61000-4-12 level 4 4kV(c.m.), 2kV(d.m.)
 Surge immunity test IEC61000-4-5 level 4 2kV(c.m.), 1kV(d.m.)
 Voltage interruptions IEC60255-4-11
 Resistance to vibration and shocks IEC60255-21-1 - IEC60255-21-2 10-500Hz 1g

 Accuracy at reference value of influencing factors 2% In for measure


0,2% On
2% +/- 10ms for times
 Rated Current In = 1 or 5A - On = 1 or 5A
 Current overload 200 A for 1 sec; 10A continuous
 Burden on current inputs Phase : 0.01VA at In = 1A; 0.2VA at In = 5A
Neutral : 0.015VA at On = 1A; 0.4VA at On = 5A
 Rated Voltage Un = 100V (different on request)
 Overload overload 2 Un permanent
 Burden on voltage inputs 0.04 VA at Un
 Average power supply consumption 8.5 VA
 Output relays rating 5 A; Vn = 380 V
A.C. resistive switching = 1100W (380V max)
make = 30 A (peak) 0,5 sec.
break = 0.3 A, 110 Vcc,
L/R = 40 ms (100.000 op.)

Microelettrica Scientifica S.p.A. - 20089 Rozzano (MI) - Italy - Via Alberelle, 56/68
Tel. (##39) 02 575731 - Fax (##39) 02 57510940
http://www.microelettrica.com e-mail : ute@microelettrica.com
The performances and the characteristics reported in this manual are not binding and can modified at any moment without notice

Copyright 2010 - Microener Pag 27 of 36


Doc. N° MO-0037-ING
MM30-D Rev. 4
Date 24.02.2003

16. CONNECTION DIAGRAM (SCE1423 Rev.2 Standard Output)

16.1 - CONNECTION DIAGRAM (SCE1499 Rev.0 Double Output)

Copyright 2010 - Microener Pag 28 of 36


Doc. N° MO-0037-ING
MM30-D Rev. 4
Date 24.02.2003

17. WIRING THE SERIAL COMMUNICATION BUS (SCE1309 Rev.0)

18. CHANGE PHASE CURRENT RATED INPUT 1 OR 5A

Copyright 2010 - Microener Pag 29 of 36


Doc. N° MO-0037-ING
MM30-D Rev. 4
Date 24.02.2003

19. THERMAL IMAGE CURVES (TU0249 Rev.1)

Copyright 2010 - Microener Pag 30 of 36


Doc. N° MO-0037-ING
MM30-D Rev. 4
Date 24.02.2003

20. INVERSE TIME UNBALANCE PROTECTION ELEMENT (TU0248 Rev.1)

Copyright 2010 - Microener Pag 31 of 36


Doc. N° MO-0037-ING
MM30-D Rev. 4
Date 24.02.2003

21. DIRECTION FOR PCB'S DRAW-OUT AND PLUG-IN

21.1 Draw-out

Rotate clockwise the screws  and  in the horizontal position of the screws-driver mark.
Draw-out the PCB by pulling on the handle 

21.2 Plug-in

Rotate clockwise the screws  and in the horizontal position of the screws-driver mark.
Slide-in the card on the rails provided inside the enclosure.
Plug-in the card completely and by pressing the handle to the closed position.
Rotate anticlockwise the screws  and  with the mark in the vertical position (locked).

Copyright 2010 - Microener Pag 32 of 36


Doc. N° MO-0037-ING
MM30-D Rev. 4
Date 24.02.2003

22. OVERALL DIMENSIONS / MOUNTING

Copyright 2010 - Microener Pag 33 of 36


Doc. N° MO-0037-ING
MM30-D Rev. 4
Date 24.02.2003

23. KEYBOARD OPERATIONAL DIAGRAM

Copyright 2010 - Microener Pag 34 of 36


Doc. N° MO-0037-ING
MM30-D Rev. 4
Date 24.02.2003

24. SETTING’S FORM


Relay Type MM30-D Station : Circuit :
Date : / / FW Version: Relay Serial Number :
Power Supply 24V(-20%) / 110V(+15%) a.c. 24V(-20%) / 125V(+20%) d.c. Rated Current In : 1A 5A
80V(-20%) / 220V(+15%) a.c. 90V(-20%) / 250V(+20%) d.c. Rated Current On : 1A 5A
Rated Voltage :
RELAY PROGRAMMING
Setting Default Actual Test Result
Variable Description
Range Setting Setting Pick-up Reset
xxXXXxx Current date Random - DDMMMYY
xx:xx:xx Current time Random - HH:MM:SS
NodAd Identification number for serial communication bus 1 - 1 - 250
Fn Mains frequency 50 Hz 50 - 60
In Rated primary current of the phase C.Ts. 500 Ap 1 - 9999
On Rated primary current of the C.Ts 500 Ap 1 - 9999
Im Motor full-load current 1.0 In 0.1 – 1.5
Ist Motor start-up current 6 Im 0.5 – 10
tst Motor starting time 5 s 1 – 120
ITr Switch-over current of motor starter 0.5 Ist Dis–0.1–1
Max switch-over time from reduced to full voltage
tTr 6 s 0.5 – 50
operation during motor starting.
Automatic setting of all the following parameters computed on the base of the setting of the
AUTOSET? + ENTER
previous parameters
Thermal time constant of motor while running ;
tm tm is computed to allow at least one restarting with 34 min 1 - 60
the motor at its rated full load temperature
to/tm Steady/running motor thermal time constant 3 - 1 - 10
Ta/n Prealarm motor heating level 90 % 50 - 110
Ts/n Motor restart heating level 100 % 40 - 100
Ib Rated maximum continuous motor overload 1.05 Im 1 – 1.3
StNo Max. No of startings allowed within the time tStNo 6 - Dis-1-60
tStNo Time into which the StNo is counted 60 m 1 - 60
Restart inhibition time after tripping of the function
tBSt 12 m 1-60-Rm
StNo
ILR Trip level of Locked Rotor function 2 Im Dis-1-5
tLR Trip time delay of LR element during run 5 s 1 – 25
Trip level of inverse time current unbalance
Is> 0.3 Im Dis-0.1-0.8
protection element
Trip time delay of inverse time current unbalance
tIs> 4 s 1–8
protection when I2=Im
I< Trip level of undercurrent (no-load running) element 0.2 Im Dis-0.15-1
I> Trip level of phase overcurrent element 2 Ist Dis - 1 - 5
tI> Trip time delay of phase overcurrent element 0.1 s 0.05 - 1
Minimum level of residual voltage for directional
Uo> 20 V 2 - 25
operation of the Earth Fault element.
Max sensitivity displacement angle of the Earth Fault
o 90 ° 0–359-Dis
directional element.
O> Trip level of earth fault element 0.1 On Dis-0.02-2
tO> Trip time delay of earth fault element 0.2 s 0.05 – 5
Maximum energization time of the output relays
tBO associated to the instantaneous functions I> and/or 0.15 s 0.05 - 0.5
O>
Enabling of the input 1 – 14 for operation of RTD
RTD OFF - OFF – ON
function
Enabling of input 1 – 3 for operation of the Speed
SpC OFF - OFF – ON
Control function
Clock synchronisation Time
Tsyn Dis m 5-60-Dis
Expected time interval between sync. signal.

Copyright 2010 - Microener Pag 35 of 36


Doc. N° MO-0037-ING
MM30-D Rev. 4
Date 24.02.2003

CONFIGURATION OF OUTPUT RELAYS


Default Setting Actual Setting
Protect. Protect.
Output Relays Description Output Relays
Element Element
T> 1 - - - Overload tripping T>
Ta - - - - Overload prealarm tripping Ta
ITr - - - - Starting switch-over tripping ITr
StNo 1 - - - Start No limitation tripping StNo
ILR 1 - - - Locked Rotor tripping ILR
tI2> 1 - - - Time delayed unbalance tripping tI2>
I< - - - - No load running tripping I<
I> - - - - Instantaneous overcurrent tripping I>
tI> - 2 - - Time delayed overcurrent tripping tI>
O> - - - - Instantaneous earth fault tripping O>
tO> - 2 - - Time delayed earth fault tripping tO>
RT - - - - Remote trip command (input 1-2) RT
1 1 - - - Time delayed Phase loss tripping 1

Commissioning Engineer : Date :

Customer Witness : Date :

Copyright 2010 - Microener Pag 36 of 36

You might also like