1.3 Characteristics
Monitoring
System interface
• IEC 60870-5-103, redundant optional
• IEC 61850, Ethernet
• DNP 3.0
• Profibus-DP
• Modbus RTU
Service interface for DIGSI 4 (modem)
1.3 Characteristics
General
• Fast transfer success increased - exclusive REAL-TIME FAST complied with C50.41-2012 using predictive
algorithm
• Engineering effort saving - typical connection diagram and default configuration suitable for most cases
• Cost saving - auto adapt line VT installation at transformer HV side, no matching VT required
• Switching sequences optimized - FAULT starting condition classified into Type A and B, less bus dead time
under non-electric fault transfer
• Kinds of abnormal starting condition to cover power loss and in-advertent CB open, stabilized against fault
and motor starting
• Manual start remotely over protocol or locally by binary input, controlled by REMOTE/LOCAL key switch
• Performance enhanced - the high speed relay contact (approx. 1 ms) designed for CB closing
• Specially designed HSBT online test mode and powerful SIGRA help the functional test and settings'
verification
• Application extended to single busbar w. 3-CB besides single busbar w. 2-CB and sectionalized single
busbar w. 3-CB
• Smart LCD display of transfer data, e.g, dU, df, dj, Ures and Udiff/f
• Smart oscillographic record, e.g, differential voltage Udiff, residual voltage Ures
Additionally, on the basis of the following information, it may be defined which functions are to be used.
2.1 General 20
2.2 HSBT 23
2.1 General
This chapter describes the analogue inputs' connection between HSBT and voltage, current circuit.
2.1.1 VT Installation
Line voltage and bus voltage are necessary for criterions. During the transfer, device makes decisions based
on the measuring and computing results derived from voltages across the alternative source CB. Figure 2-1
shows the voltage connection example.
3-ph voltage is required for bus side. It's essential for voltage phase sequence check, fault detection, etc.
In some case, line voltage can only be taken from high voltage side of in-feeding transformer. 7VU683 supports
this application. It will auto-adapt the voltage amplitude and angle difference by two parameters, for example,
0283 Voltage balancing factor of Line 1 and 0284 Voltage angle adjustment of Line 1. No matching VT is required.
Figure 2-2 shows the application.