O&m Manual For LV Switchgear

Download as pdf or txt
Download as pdf or txt
You are on page 1of 131

No. F18-QP9.

1-KA

Method Statement Revision No. 1


Contractor's Logo Client's Logo
Submittal Revision Date May. 2023

Approved by Nik Rowley

Project : INTERCONTINENTAL FUJAIRAH Reference No. PSE20231016-O&M-MEP-026


Contract No. AAP/0239/Proscape/2023 Date : 21/10/2023
Contractor : M/s. PROSCAPE LLC Revision No. 0
FROM : M/s. PROSCAPE LLC TO : M/s. Khatib & Alami

Serial
Document No. Description Rev. Copies Status
No.

1 PSE20231016-O&M-MEP-026 OPERATION MAINTANCE MANUAL FOR LV SWITCH GEAR 0


PANEL

2 0

Contractor's View :
Architectural Structural Mechanical Electrical Plumbing Others

Relevant Specification Section :

THIS SUBMITTAL INTENDED FOR :


Approval / Comments Information / Records

Contractor :
NAME : Tintu Vasudevan SIGNATURE : DATE :

Engineer's Rep. :
A. Approved B. Approved as Noted C. Revise & Resubmit D. Rejected E. For Information Only

Comments :

Name: Signature: Date:

This approval does not relieve the Contractor from its obligations outlined in the Contract documents
DISTRIBUTION :

Original : CONTRACTOR

Copies : OWNER K&A

Form issue 1, Nov 2010


O&M MANUAL FOR
LV SWITCHGEAR PANELS

PROJECT

INTERCONTINENTAL HOTL FUJAIRAH LANDSCAPEING

CLIENT

ALAIN

CONSULTANT

KHATIB & ALAMI

CONTRACTOR

PROSCAPE
INDEX

SL.NO. DESCRIPTION SEC.NO.


1. SYSTEM DESCRIPTION I
2. EMERGENCY INFORMATION II
3. EQUIPMENT SCHEDULE III
4. SAFETY INSTRUCTIONS IV
5. MAINTENANCE PROCEDURES V
6. SPARE PARTS LIST VI
7. DISPOSAL INSTRUCTIONS VII
8. TESTING REPORT VIII
9. MODIFICATIONS IX
10. WARRANTY CERTIFICATE X
11. AS BUILT DRAWINGS XI
12. PRODUCT CATALOGUE XII
I. SYSTEM DESCRIPTION
#

#
W]WXIQ#HIWGVMTXMSR#JSV#PZ#W[MXGLKIEV#W]WXIQ#
#
Iegl#w{mxglkiev#teripw#qeryjegxyvih#f}#Wejix}#Ipigxvmgep#W{mxglkiev#Qeryjegxyvmrk#evi#ywih#jsv#wyttp}#erh#
hmwxvmfyxmsr#sj#ipigxvmgep#ts{iv1#Teripw#evi#hmwxvmfyxih#sr#xli#fymphmrk#fewih#sr#xli#viuymviqirx#~sri#2#jpssvw#xs#
oiit#xli#hmwxvmfyxmsr#wmqtpi#erh#xs#tvszmhi#qe|mqyq#wejix}#erh#vipmefmpmx}1#
Teripfsevhw>0#
E#teripfsevh#mw#e#gsqtsrirx#sj#er#ipigxvmgep#hmwxvmfyxmsr#w}wxiq#xlex#hmzmhiw#er#ipigxvmgep#ts{iv#jiih#mrxs#fvergl#
gmvgymxw#{lmpi#tvszmhmrk#e#tvsxigxmzi#jywi#sv#gmvgymx#fvieoiv#jsv#iegl#gmvgymx#mr#e#gsqqsr#irgpswyvi1#Mr#iwwirgi/#
teripfsevhw#evi#ywih#xs#tvsxigx#ekemrwx#ipigxvmgep#szivpsehw#erh#wlsvx#gmvgymxw#{lmpi#hmwxvmfyxmrk#ipigxvmgmx}#
xlvsyklsyx#e#fymphmrk#sv#jegmpmx}1#
Xli#qemr#gsqtsrirxw#sj#e#teripfsevh#x}tmgepp}#mrgpyhi#xli#irgpswyvi/#fywfev/#mrxivmsv#wikvikexmsrw#/#gmvgymx#
EGDI97I>DC 89K>79HQ A569AHQ 8958 ;GDCI 5C8 IG>BQ 5C8 ;>AA9G EA5I9H ,DG9 7DBBDCAN G9;9GG98 ID 5H I=9 V6DMW DG V75CQW
xli#irgpswyvi#tvszmhiw#xli#lsywmrk#mr#{lmgl#epp#xli#sxliv#teripfsevh#gsqtsrirxw#viwmhi1#Irgpswyviw#evi#qehi#sj#
kepzerm~ih#sv#temrxih#wxiip#xs#tvszmhi#tvsxigxmsr#jsv#tivwsrrip#erh#mrxivrep#iuymtqirx1#Viqszefpi#irh#teripw#
epps{#jsv#wmqtpi#gsrhymx#mrwxeppexmsr#{livi#mrwxeppivw#ger#iewmp}#psgexi#erh#gyx#lspiw#ew#riihih1#
Mrwmhi#xli#irgpswyvi/#szivgyvvirx#tvsxigxmsr#hizmgiw/#fywfevw#erh#sxliv#gsqtsrirxw#evi#qsyrxih#sr#wyttsvx#
vempw1#Xlmw#mrxivmsv#ewwiqfp}#mw#gsqqsrp}#geppih#e#glewwmw1#Gmvgymx#fvieoivw#evi#gsqqsrp}#ywih#ew#gmvgymx#
tvsxigxmsr#hizmgiw#erh#evi#gsrrigxih#xs#xli#fywfevw#f}#fyw#gsrrigxsv#jmrkivw1#
E#fywfev#mw#e#gsrhygxsv#ywih#ew#e#gsrrigxmsr#tsmrx#jsv#qypxmtpi#gmvgymxw1#Fywfevw#evi#qsyrxih#sr#mrwypexsvw#sr#
xli#mrxivmsv#vempw/#{lmgl#evi#xlir#qsyrxih#xs#wxyhw#mrwmhi#xli#fs|1#E#riyxvep#fev#mw#epws#glewwmw0#sv#kyxxiv0qsyrxih#
ri|x#xs#xli#mrxivmsv/#tvszmhmrk#xli#xivqmrexmsr#tsmrx#jsv#xli#riyxvep#{mviw#jvsq#xli#mrgsqmrk#wivzmgi#erh#xli#pseh#
gmvgymxw1#
Teripfsevhw#wlsyph#ep{e}w#fi#{ipp#pefipih1#Pefipw#tvszmhi#hixempw#G9<5G8>C< I=9 JC>IUH KDAI5<9 G5I>C<Q 5BE57>INQ
mrxivvytxmrk#vexmrk/#qeryjegxyvmrk#hexi/#terip#zmrxeki#erh#viri{ep#tevxw1#Xlmw#mrjsvqexmsr#mw#gvmxmgep#xs#irwyvmrk#
xli#wejix}#sj#tistpi#erh#iuymtqirx#erh#iew}#qemrxirergi1#
Irgpswyviw#jiexyvi#e#jvsCI 7DK9G E>979 @CDLC 5H I=9 E5C9A6D5G8UH hieh#jvsrx#erh#xvmq1#Xlmw#gsqtsrirx#gszivw#
xli#jvsrx#wyvjegi#sj#xli#teripfsevh#erh#tvszmhiw#e#lmrkih#eggiww#hssv#xlex#epps{w#eggiww#xs#xli#gmvgymx#fvieoivw#
II. EMERGENCY INFORMATION
EMERGENCY INFORMATION

Emergency Contacts

In Case of Contact Telephone


Accident or Incident Police 999
Fire Fire Brigade 997
Medical emergency Ambulance 998 / 999

Safety Electrical Switchgear


P.O. Box 3494,
Dubai, U.A.E.
Ph: +971 48055400
Fax: +971 48867003
Email: info@safetygroup.ae
www.safetyelectricalgroup.com
DIRECTORY OF CONTACT
Consultant/Subcontractor's/ Phone Mobile
Sl No Trade Description Contact Person Email
Suppliers Company Name Number Number

Mr.Rajesh
1 Safety Electrical Group General Manager 04-8055400 lakhani@seg.ae 052-6096868
Lakhani
2 Safety Electrical Group Project Engineer Mr. Jeevan 04-8055400 jeevan.sequeira@seg.ae 052-6096935

5 Safety Electrical Group QC Engineer Mr. Sunil 04-8055400 sunil.kumar@seg.ae 052-6096816


III. EQUIPMENT SCHEDULE
Sl. Description Fed From Total Qty

1 250A-SMDB-FP EXISTING LV PANEL-08 1


2 125A-SMDB-BB-S EXISTING LV PANEL-03 1
3 SPLASH PAD CONTROL PANEL SMDB-FP 1
4 FP-FB-S(Without Canopy) SMDB-FP 1
5 DB-BB-S SMDB-BB-SS 1
6 DB-WS-S SMDB-BB-SS 1
IV. SAFETY INSTRUCTIONS
SAFETY AT WORK

For the safety of personnel working with or associated with the switchgear panels
described in this manual, it is recommended that the person should comply with the
instructions and information contained herein. He should also ensure that all personnel
who will be associated with this apparatus are familiar with these instructions and
information.

INSTALLATION, OPERATION AND MAINTENANCE


Technically qualified and competent persons experienced in switchgear works should
correctly install the switchgear panel described in this manual, in a suitable location.
The completed installation should be examined and approved by a responsible person
to ensure that it is correct and in a safe condition for operation.

For maintenance and testing the user should ensure the following: -

(a) The switchgear panel is isolated and the power is not available on the panel or components
terminal prior to any work carried out upon it. In this event, it must be taken care that the
switchgear panel should not become live while the work is ongoing. This can be done by
locking the breaker, which is feeding this switch board.
OR
(b) SPECIAL PRECAUTIONS are to be taken to ensure safety if the apparatus is not isolated.
Such work must be under the direct supervision of a responsible technical person.

ACCESS TO THE SWITCHGEAR PANEL


The user should ensure that access to this panel is restricted to authorize persons only.
SAFETY INSTRUCTIONS

1. Always observe work safety procedures.


2. Take careful notice of all warning labels and danger signs fixed to the panel.
3. Allow only authorized personnel to enter the electrical equipment room.
4. Special precautions must be taken when an electrician is working on live electrical
equipment to ensure live terminals are not accessed.
5. Electrical equipment or loads should be disconnected from the main supply before
changing any component or connecting a wire to a terminal.
6. Only authorized operating personnel are permitted to operate this switchgear panel
Any testing which needs to be carried out, must be supervised by
authorized operating personnel to ensure the SAFETY.
7. Before working on any equipment, check if it is in an area which is subject to any
additional safety instructions because of the possible presence of hazardous or explosive
gases. Always observe the additional safety instructions
8. All protective barriers supplied with the equipment should be re-fixed if removed for
any maintenance.
V. MAINTENANCE PROCEDURES
PREVENTIVE MAINTENANCE WORKS

MONTHLY TASKS
• To recheck whether all controls and systems are functioning satisfactory, and rectify any fault if
necessary.
• To check all meters and indications are functioning
• Ensure the interior and exterior of the panel is clean and no gaps visible that may allow any
foreign body to enter the panel.

EVERY SIX MONTHS

• Ensure the above mentioned tasks are carried out.


• Allow for a shut down and clean the panel thoroughly. (Vacuuming the panel rather than using
a blower).
• Carry out a Megger test on the panel.
• Check operation of all outgoing MCCB’s by opening, closing and tripping manually each device.

MCCS/ SMDB’S

MONTHLY TASKS
• To give trial test of MCCB’s on manual mode.
• To recheck whether all controls and systems are functioning satisfactory, and rectify any fault if
necessary.
• To check all meters and indications are functioning
• Ensure the interior and exterior of the panel is clean and no gaps visible that may allow any
foreign body to enter the panel.
• Check all starter operations in manual mode.
• Trip each starter manually via its overload relay and reset.

EVERY 6 MONTHS
• Ensure the above mentioned tasks are carried out.
• Allow for a shut down and clean the panel thoroughly. (Vacuuming the panel rather than using
a blower).
• Carry out a Megger test on the panel.
• Check operation of all outgoing MCCB’s by opening, closing and tripping manually each device.
• Check all starter operations in manual mode.
• Trip each starter manually via its overload relay and reset.
• Check for humming in contactors and clean/replace where necessary.

YEARLY

• All busbar joints and tap off points to be periodically checked by torque wrench for their
tightness at least once in a year.
• All dust and foreign material should be removed.
• All cable connections to MCCB/ISOLATOR should be properly tightened to avoid any undue
stress on the terminals on for better contact pressure to avoid localized heating. Periodical
checking of the contact should be done. Check for damage or pitting of contact of MCCB’s
and Contactors.
• Periodical tripping and closing/opening of circuit breaker should be checked qualified
maintenance person, if found not in order the circuit breaker should be replaced.
• All removable covers to be checked for proper fixation and damage of gasket to avoid ingress of
dust and vermin.
• Check for damage of any shroud and guard while operation.
• Check for trouble free operation of electrical components by manual operation on no load.
• Ensure that all shrouds and guards are replaced to their original position after maintenance.
• Ventilation provided on the panel should not be blocked periodical checking of the air vents to
be taken care for proper air circulation thereby minimizing heating of the component.
• The maintenance and operation of panel should be carried out in the supervision of qualified
engineer.
MAINTENANCE OF ELECTRICAL SWITCHGEAR

1. Introduction
The periodic maintenance of switch gear and control gear used for power distribution and
motor control is mandatory for keeping equipment in good working condition and hence
ensuring that protection is available. Those concerned with this work should also familiar
themselves with the plant and report any changes which effect the plant or its control gear.
2. General
The essence of good maintenance is applied common sense. Good maintenance is an important
part of good engineering practice in a building. If the staff responsible gives due regard to the
safety of personnel, safety of the building and continuity of operation then, generally speaking,
costs will take care of themselves and there will be few problems with the maintenance of
control gear.
3. Analysis of faults
Every fault should be record and analyzed, and consideration should given to the cause of break
down. Where possible, the appropriate remedial action should be taken to avoid the
recurrence of the fault. Fault should be studied and rectified.
4. Isolation before maintenance work
Before any work is carried out on or near parts which are normally live, or where danger would
arise to men working if the motor where to be inadvertently started, it is essential that the
apparatus be isolated completely.
5. Cleanliness
For equipment to operate satisfactory it is essential that it be kept clean before removing
covers and opening doors loose dirt and dust resting on the top of the enclosure should be
removed with a brush.
• When air is used for cleaning, a suction type device with receptacle should preferably be
employed. If it is necessary to use compressed air, it is preferable to employ a portable type
blower.
After maintenance work all covers and doors including those of instruments and relays should
be securely replaced so as to exclude dust.
6. Marking of covers and connections
All covers cables, and shields, etc, should be marked carefully before removal to ensure correct
replacement. If connections are disturbed or temporary connections made for testing purpose,
they should be clearly marked to facilitate reconnection and the permanent connection must
be restored and the temporary connections removed before the unit is returned to service.
7. Tightness of connections
After maintenance, the bolts screws and locking of all current- carrying and earth connections
should be securely replaced.
It is not sufficient for nuts and bolts to appear to be tight. Torque test to be conducted.
8. Switch and fuses
Before working on isolators or isolating switches, particular care is necessary to make sure that
both sides of the device, and any auxiliary circuits, are dead. Some items of equipment are
provided with isolators and isolating switches .The contacts of isolators and isolating switches
are less frequently operated than others, and are therefore particularly liable to failure arising
from cumulative effects over a long period. Because of their position in the circuit, they tend to
be neglected, and it is therefore important during maintenance to inspect them for signs of
overheating and to replace parts where there is the slightest doubt.
9. Maintenance of Emergency pushbuttons
Local and remote 'stop' buttons are important components of many motor installations. Failure
to ensure proper maintenance of either operational or emergency 'stop' buttons may
procedure dangerous conditions. Maintenance work on motor control equipment should
therefore always include careful inspection of and attention to 'stop' buttons; the fact that the
'emergency stop' buttons may seldom be used makes it more necessary for regular inspection.
It is an advantage to list the location of all remote pushbuttons inside the panels.
10. Contactor
It is good practice after an overhaul to disconnect the motor link at the starter so that the correct
Operation of the contactors and relays can be checked without the motor and inadvertent
Operation of the plant.
*Replacement of contactor units
It is recognized that it may be uneconomic to replace contacts or other small components due
to the compact designs and the need for verification if correct replacements are carried out. For
such equipment maintenance may well consist of replacement of the complete contactor.
11. Overload device
Care should be taken to ensure clean and tight contacts of the power termination on the device
and the cleanliness of the tripping contacts. Maintenance of all overload devices is generally
limited to visual inspection for dust and tightness of connection.
*THERMAL DEVICES
The bi-metallic overload devices employ the bending properties of a bi- metal when heated.
The current drawn by the motor is utilized to heat their-metal strip. The bending is used to
operate a set of trip contacts. These devices usually have no user replaceable or maintainable
parts and complete replacement is necessary.
VI. SPARE PARTS LIST
S.No. ORDER CODE DESCRIPTION BRAND QTY
1 1SFA619403R5231 Indicator LED 230V ac RED ABB 2
2 1SFA619403R5233 Indicator LED 230V ac YELLOW ABB 2
3 1SFA619403R5234 Indicator LED 230V ac BLUE ABB 2
4 1SFA619403R5021 PILOT LIGHT#CL2-502R#24V A.C./D.C. ABB 2
5 1SFA619403R5023 Pilot Light#CL2-502Y#24V a.c./d.c. ABB 2
6 1SFA619403R5022 Pilot Light#CL2-502G#24V a.c./d.c. ABB 2
7 1SFA619100R1012 PUSH BUTTON GREEN - CP1 - 10G - 10 ABB 2
8 1SFA619100R1041 PUSHBUTTON#CP1-10R-01 ABB 2
9 1SFA611210R1006 SELECTOR SWITCH#M3SS1-10B ABB 2
10 1SFA611200R1006 SELECTOR SWITCH#M2SS1-10B ABB 2
VII. DISPOSAL INSTRUCTIONS
DISPOSAL INSTRUCTION
Materials used in maintenance activities and any repaired or replaced items may require
classification as to the type of waste material that they constitute. The Facilities
Maintenance Team at the Union Co-operative Society is directed to the series of Technical
Guidelines (and relevant bulletins) available from the Dubai Municipality Environment
Protection & Safety Section, in particular to Numbers 26, 27, 49 & 50 which cover
Hazardous Waste.

The preferred options for disposal are:


• Recycling.
• Incineration with energy recovery.
• Landfill.

The prospect of recycling should be explored.


Any items or materials left over from maintenance and repair work should be stored and
used as spares, where necessary, as this will reduce the cost of future maintenance
activities.

The electrical components contain mostly metal and plastic parts, which are all recyclable,
therefore, upon end of the useful life of any electrical component, eg panel, circuit
breaker, etc, they should not be disposed of in the ordinary garbage collection and
disposal system. This equipment should be delivered to a recycling agency, according to
the valid regulations of the Dubai municipality.

It must be kept in mind, some electrical components contain heavy metals, eg lead,
chrome, etc, which are harmful to the environment, therefore it is necessary to dispose of
all such components according to the regulations.

Avoid burning of electrical components as they generate harmful gases and possibly waste
useful materials.

SAFE DISPOSAL
Any debris should be swept up or vacuumed and placed in strong polythene bags. Dispose
of at an approved waste, observing local regulations.
Consult Dubai Municipality for guidance on the proper disposal / recycling of any
equipment units. Alternatively, refer the equipment to be disposed of to a recycling
agency.
VIII. TESTING REPORT
FACTORY ACCEPTANCE TEST REPORT FOR SMDB
PANEL DESCRIPTION SMDB-BB-S DRAWING REF NO. P23-07
ORDER NUMBER CRO_00483 ISSUE DATE 07-09-2023
CUSTOMER/PROJECT NO. P23-101 DATE OF TESTING 25-09-2023
RATED OPERATIONAL VOLTAGE(Ue) 400V RATED FREQUENCY (Hz) 50HZ
RATED INSULATION VOLTAGE(Ui) 690V RATED CURRENT (A) 125A
RATED IMPULSE WITHSTAND VOLTAGE (Uimp) 6KV TEST AREA AMBIENT (°C) 32°C
STANDARD REF IEC 61439-1&2 TEST AREA HUMIDITY (%) 30%
RATED SHORT WITHSTAND CURRENT (Icw) 35 kA 1 Sec

PROJECT INTERCONTINENTAL HOTEL FUJAIRAH LANDSCAPEING


CLIENT ALAIN
CONSULTANT KHATIB & ALAMI
CONTRACTOR PROSCOPE

A VISUAL INSPECTION
ENCLOSURE SIZE OK CURRENT TRANSFORMERS OK
ENCLOSURE MATERIAL OK FUSES / FUSE BASES OK
ENCLOSURE COLOUR OK INSULATORS / BUS SUPPORTS OK
FORM OF CONSTRUCTION- OK ATS CONTROLER-SOCOMEC N/A
ENCLOSURE PADLOCK N/A SPD N/A
MATERIAL THICKNESS OK INCOMER / OUTGOING POSSITION OK
METEL SHROUDING OK ACB MECHANICAL INTERLOCK N/A
EXTERNAL HANDLE OK UVR + CONTACTORS N/A
TIGHTNESS OF CONNECTION OK DRAWING POCKETS + DRAWINGS OK
COPPER BUS BAR SIZE OK RUN /OFF/ TRIP INDICATION LAMP N/A
INCOMING RATING OK PUSH BUTTON ON/OFF N/A
OUTGOING RATING OK CONTROL RELAYS N/A
DEGREE OF PROTECTION- OK TERMINAL BLOCKS OK
MCCB PADLOCK OK WIRE MARKINGS OK
EARTHING OK SECTION LABELS OK
NEUTRAL OK R Y B LABELS OK
AMMETER RATING OK OVERLOAD RELAYS N/A
VOLTMETER RATING OK NEUTRAL AND EARTH POSITION OK
PMU OK BUSBAR INSULATOR SPACING OK

Document No:- SEG-HSE-F-29 Rev.no.- 00 Issue Date-20-08-2019 Page | 1/4


PHASE BARRIERS OK BUSBAR SLEEVING / COLOUR CODING OK
OK CLEARANCE AND CREEPAGE DISTANCE OK
RYB INDICATIONS
BETWEEN BUSBAR
OK SHROUDING OF BUSBARS / ACCIDENTAL OK
VOLTMETER SELECTOR SWITCH LIVE PARTS/INCOMING AND OUT
GOING FEEDERS
N/A ORIENTATION OF PHASES ON OK
ELR + SHUNT TRIPS
DIFFERENT INCOMERS
CAUTION LABELS OK EARTHE BAR IS CONTINUOUS OK
CABLE ENTRY OK WIRE SIZE AND COLOUR CODES OK
GLANDING ARRANGEMENTS OK WIRE CRIMPING AND NUMBERING OK
TERMINAL IDENTIFICATION OK WIRE ROUTING AND BUNCHING OK
1 CONSTRUCTION RESULT REMARKS
1.1 ENCLOSURE-OVER ALL DIMENSIONS OK
1.2 MATERIAL THICKNESS, PAINT SHADE/FINISH [INTERNAL/EXTERNAL] OK
1.3 TYPE OF ENCLOSURE OK
1.4 DEGREE OF PROTECTION OF THE ENCLOSURE OK
2 LAYOUT RESULT REMARKS
2.1 COMPONENT GENERAL LAYOUT OK
2.2 I/C FEEDER POSITION OK
2.3 I/C FEEDER HANDLE POSITION OK
2.4 O/G FEEDERS' HANDLE POSITION N/A
2.5 CABLE ACCESS OK
3 BUSBAR RESULT REMARKS
3.1 COPPER BUSBAR SIZES (MAIN, DROPPER & TAP-OFF) OK
3.2 NEUTRAL AND EARTH POSITION OK
3.3 BUSBAR INSULATOR SPACING OK
3.4 BUSBAR SLEEVING / COLOUR CODING OK
3.5 CLEARANCE AND CREEPAGE DISTANCE BETWEEN BUSBAR AND BODY OK
3.6 SHROUDING OF BUSBARS / LIVE PARTS/INCOMING AND OUTGOING FEEDERS OK
3.7 ORIENTATION OF PHASES ON DIFFERENT INCOMERS OK
3.8 EARTHE BAR IS CONTINUOUS OK
4 CABLE TERMINATION RESULT REMARKS
4.1 CABLE ENTRY OK
4.2 GLANDING ARRANGEMENTS OK
4.3 TERMINAL IDENTIFICATION LABEL AND TERMINAL MARKER OK

Document No:- SEG-HSE-F-29 Rev.no.- 00 Issue Date-20-08-2019 Page | 2/4


4.4 WIRE SIZE AND COLOUR CODES OK
4.5 WIRE CRIMPING AND NUMBERING OK
4.6 WIRE ROUTING AND BUNCHING OK
4.7 EARTHING OF BODY, COMPONENT OK
4.8 EARTH WIRE SIZE AND COLOUR CODES OK
5 COMPONENTS RESULT REMARKS
5.1 MAKE OF COMPONENTS OK
5.2 MAIN & BRANCH BREAKERS-ACB,MCCB,MCB,FUSES - POLES,AMP/KA RATINGS OK
6 LABELS RESULT REMARKS
6.1 INTERNAL MOUNTED COMPONENTS POSITION AND LABELS OK
6.2 MAIN LABEL, LABEL FOR FEEDERS OK
6.3 WARNING LABEL-INCOMING & OUTGOING SIDE OK
7 GENERAL RESULT REMARKS
7.1 DOOR LOCKING FACILITIES OK
7.2 DOOR ALIGNMENTS OK
7.3 DWG. POCKET OK
B MECHANICAL TEST RESULT REMARKS
8.1 RIGIDITY OF MOUNTING OK
8.2 TIGHTENING OF NUT, BOLT AND RED MARKING FOR TORQUE OK
8.3 TIGHTNESS OF WIRES AND BUSBARS AS PER ATTACHED TORQUE TABLE OK
8.4 CHECKING OF DOOR I/L OPERATION OK
C INSULATION RESISTANCE TEST BEFORE AND AFTER THE DIELECTRIC TEST
EQUIPMENT TYPE AND SL.NO SONEL / MIC-10K1
FUNCTIONAL TEST (BEFORE START THE TEST) PASS
CALIBRATION DATE 02-01-2023
CALIBRATION DUE DATE 01-01-2024
FUNCTIONAL TEST OF THE EQUIPMENT PASS
TEST VOLTAGE –Ui (REFER TABLE 8 OF IEC 61439-1) 1000V DURATION = 1 MIN
TEST RESULT
Measuring points (Value in ohms)
(Limit 10Mohm)
BETWEEN R AND Y PHASE >200Ω PASSED
BETWEEN R AND B PHASE >200Ω PASSED
BETWEEN B AND Y PHASE >200Ω PASSED
BETWEEN R AND N PHASE >200Ω PASSED
BETWEEN Y AND N PHASE >200Ω PASSED

Document No:- SEG-HSE-F-29 Rev.no.- 00 Issue Date-20-08-2019 Page | 3/4


BETWEEN B AND N PHASE >200Ω PASSED
BETWEEN PE AND R PHASE >200Ω PASSED
BETWEEN PE AND Y PHASE >200Ω PASSED
BETWEEN PE AND B PHASE >200Ω PASSED
BETWEEN PE AND N PHASE >200Ω PASSED
E FUNCTION & SUPPLY TEST RESULT REMARKS
9.1 CHECK INDICATION LAMPS OK
9.2 CHECKING THE OPERATION OF PMU OK
9.3 CHECKING OF ELCB FUNCTION N/A
9.4 CHECKING OF MCCB FUNCTION
MCCB MANUAL OPERATIONS OK
A. MCCB ON OK
B. MCCB OFF OK
C. MCCB TRIP OK
D. MCCB S/O OPERATION N/A
E. PADLOCK FUNCTION OK
9.5 CHECK OF INCOMER & OUTGOING SUPPLY OK

TESTED BY : JACOB PC APPROVED BY: SUNIL KUMAR VM(QA/QC)

WITNESSED BY QA/QC CLIENT CONSULTANT CONTACTOR

NAME SUNIL KUMAR VM

DESIGINATION QA/QC

COMPANY SEG

SIGNATURE

N/A-NOT AVAILABLE, NO-NOT OK

Document No:- SEG-HSE-F-29 Rev.no.- 00 Issue Date-20-08-2019 Page | 4/4


FACTORY ACCEPTANCE TEST REPORT FOR SMDB
PANEL DESCRIPTION FEEDER PILLER DRAWING REF NO. P23-07
ORDER NUMBER CRO_00483 ISSUE DATE 07-09-2023
CUSTOMER/PROJECT NO. P23-101 DATE OF TESTING 25-09-2023
RATED OPERATIONAL VOLTAGE(Ue) 400V RATED FREQUENCY (Hz) 50HZ
RATED INSULATION VOLTAGE(Ui) 690V RATED CURRENT (A) 200A
RATED IMPULSE WITHSTAND VOLTAGE (Uimp) 6KV TEST AREA AMBIENT (°C) 32°C
STANDARD REF IEC 61439-1&2 TEST AREA HUMIDITY (%) 30%
RATED SHORT WITHSTAND CURRENT (Icw) 35 kA 1 Sec

PROJECT INTERCONTINENTAL HOTEL FUJAIRAH LANDSCAPEING


CLIENT ALAIN
CONSULTANT KHATIB & ALAMI
CONTRACTOR PROSCOPE

A VISUAL INSPECTION
ENCLOSURE SIZE OK CURRENT TRANSFORMERS OK
ENCLOSURE MATERIAL OK FUSES / FUSE BASES OK
ENCLOSURE COLOUR OK INSULATORS / BUS SUPPORTS OK
FORM OF CONSTRUCTION- OK ATS CONTROLER-SOCOMEC N/A
ENCLOSURE PADLOCK N/A SPD N/A
MATERIAL THICKNESS OK INCOMER / OUTGOING POSSITION OK
METEL SHROUDING OK ACB MECHANICAL INTERLOCK N/A
EXTERNAL HANDLE OK UVR + CONTACTORS N/A
TIGHTNESS OF CONNECTION OK DRAWING POCKETS + DRAWINGS OK
COPPER BUS BAR SIZE OK RUN /OFF/ TRIP INDICATION LAMP N/A
INCOMING RATING OK PUSH BUTTON ON/OFF N/A
OUTGOING RATING OK CONTROL RELAYS N/A
DEGREE OF PROTECTION- OK TERMINAL BLOCKS OK
MCCB PADLOCK OK WIRE MARKINGS OK
EARTHING OK SECTION LABELS OK
NEUTRAL OK R Y B LABELS OK
AMMETER RATING OK OVERLOAD RELAYS N/A
VOLTMETER RATING OK NEUTRAL AND EARTH POSITION OK
PMU OK BUSBAR INSULATOR SPACING OK

Document No:- SEG-HSE-F-29 Rev.no.- 00 Issue Date-20-08-2019 Page | 1/4


PHASE BARRIERS OK BUSBAR SLEEVING / COLOUR CODING OK
OK CLEARANCE AND CREEPAGE DISTANCE OK
RYB INDICATIONS
BETWEEN BUSBAR
OK SHROUDING OF BUSBARS / ACCIDENTAL OK
VOLTMETER SELECTOR SWITCH LIVE PARTS/INCOMING AND OUT
GOING FEEDERS
N/A ORIENTATION OF PHASES ON OK
ELR + SHUNT TRIPS
DIFFERENT INCOMERS
CAUTION LABELS OK EARTHE BAR IS CONTINUOUS OK
CABLE ENTRY OK WIRE SIZE AND COLOUR CODES OK
GLANDING ARRANGEMENTS OK WIRE CRIMPING AND NUMBERING OK
TERMINAL IDENTIFICATION OK WIRE ROUTING AND BUNCHING OK
1 CONSTRUCTION RESULT REMARKS
1.1 ENCLOSURE-OVER ALL DIMENSIONS OK
1.2 MATERIAL THICKNESS, PAINT SHADE/FINISH [INTERNAL/EXTERNAL] OK
1.3 TYPE OF ENCLOSURE OK
1.4 DEGREE OF PROTECTION OF THE ENCLOSURE OK
2 LAYOUT RESULT REMARKS
2.1 COMPONENT GENERAL LAYOUT OK
2.2 I/C FEEDER POSITION OK
2.3 I/C FEEDER HANDLE POSITION OK
2.4 O/G FEEDERS' HANDLE POSITION N/A
2.5 CABLE ACCESS OK
3 BUSBAR RESULT REMARKS
3.1 COPPER BUSBAR SIZES (MAIN, DROPPER & TAP-OFF) OK
3.2 NEUTRAL AND EARTH POSITION OK
3.3 BUSBAR INSULATOR SPACING OK
3.4 BUSBAR SLEEVING / COLOUR CODING OK
3.5 CLEARANCE AND CREEPAGE DISTANCE BETWEEN BUSBAR AND BODY OK
3.6 SHROUDING OF BUSBARS / LIVE PARTS/INCOMING AND OUTGOING FEEDERS OK
3.7 ORIENTATION OF PHASES ON DIFFERENT INCOMERS OK
3.8 EARTHE BAR IS CONTINUOUS OK
4 CABLE TERMINATION RESULT REMARKS
4.1 CABLE ENTRY OK
4.2 GLANDING ARRANGEMENTS OK
4.3 TERMINAL IDENTIFICATION LABEL AND TERMINAL MARKER OK

Document No:- SEG-HSE-F-29 Rev.no.- 00 Issue Date-20-08-2019 Page | 2/4


4.4 WIRE SIZE AND COLOUR CODES OK
4.5 WIRE CRIMPING AND NUMBERING OK
4.6 WIRE ROUTING AND BUNCHING OK
4.7 EARTHING OF BODY, COMPONENT OK
4.8 EARTH WIRE SIZE AND COLOUR CODES OK
5 COMPONENTS RESULT REMARKS
5.1 MAKE OF COMPONENTS OK
5.2 MAIN & BRANCH BREAKERS-ACB,MCCB,MCB,FUSES - POLES,AMP/KA RATINGS OK
6 LABELS RESULT REMARKS
6.1 INTERNAL MOUNTED COMPONENTS POSITION AND LABELS OK
6.2 MAIN LABEL, LABEL FOR FEEDERS OK
6.3 WARNING LABEL-INCOMING & OUTGOING SIDE OK
7 GENERAL RESULT REMARKS
7.1 DOOR LOCKING FACILITIES OK
7.2 DOOR ALIGNMENTS OK
7.3 DWG. POCKET OK
B MECHANICAL TEST RESULT REMARKS
8.1 RIGIDITY OF MOUNTING OK
8.2 TIGHTENING OF NUT, BOLT AND RED MARKING FOR TORQUE OK
8.3 TIGHTNESS OF WIRES AND BUSBARS AS PER ATTACHED TORQUE TABLE OK
8.4 CHECKING OF DOOR I/L OPERATION OK
C INSULATION RESISTANCE TEST BEFORE AND AFTER THE DIELECTRIC TEST
EQUIPMENT TYPE AND SL.NO SONEL / MIC-10K1
FUNCTIONAL TEST (BEFORE START THE TEST) PASS
CALIBRATION DATE 02-01-2023
CALIBRATION DUE DATE 01-01-2024
FUNCTIONAL TEST OF THE EQUIPMENT PASS
TEST VOLTAGE –Ui (REFER TABLE 8 OF IEC 61439-1) 1000V DURATION = 1 MIN
TEST RESULT
Measuring points (Value in ohms)
(Limit 10Mohm)
BETWEEN R AND Y PHASE >200Ω PASSED
BETWEEN R AND B PHASE >200Ω PASSED
BETWEEN B AND Y PHASE >200Ω PASSED
BETWEEN R AND N PHASE >200Ω PASSED
BETWEEN Y AND N PHASE >200Ω PASSED

Document No:- SEG-HSE-F-29 Rev.no.- 00 Issue Date-20-08-2019 Page | 3/4


BETWEEN B AND N PHASE >200Ω PASSED
BETWEEN PE AND R PHASE >200Ω PASSED
BETWEEN PE AND Y PHASE >200Ω PASSED
BETWEEN PE AND B PHASE >200Ω PASSED
BETWEEN PE AND N PHASE >200Ω PASSED
E FUNCTION & SUPPLY TEST RESULT REMARKS
9.1 CHECK OF ELR FUNCTION OK
9.2 CHECKING OF CONTACTOR & TIMER FUNCTION OK
9.3 CHECKING OF ELCB FUNCTION OK
9.4 CHECKING OF MCCB FUNCTION
MCCB MANUAL OPERATIONS OK
A. MCCB ON OK
B. MCCB OFF OK
C. MCCB TRIP OK
D. MCCB S/O OPERATION N/A
E. PADLOCK FUNCTION OK
9.5 CHECK OF INCOMER & OUTGOING SUPPLY OK

TESTED BY : JACOB PC APPROVED BY: SUNIL KUMAR VM(QA/QC)

WITNESSED BY QA/QC CLIENT CONSULTANT CONTACTOR

NAME SUNIL KUMAR VM

DESIGINATION QA/QC

COMPANY SEG

SIGNATURE

N/A-NOT AVAILABLE, NO-NOT OK

Document No:- SEG-HSE-F-29 Rev.no.- 00 Issue Date-20-08-2019 Page | 4/4


FACTORY ACCEPTANCE TEST REPORT FOR MCC
PANEL DESCRIPTION SPLASH PAD CONTROL PANEL DRAWING REF NO. P23-101-CP
ORDER NUMBER CRO-00483 ISSUE DATE 07-09-2023
CUSTOMER/PROJECT NO. P23-101 DATE OF TESTING 25-09-2023
RATED VOLTAGE 400V TESTED BY JACOB PC
RATED CURRENT. 40A VERIFIED BY SUNIL KUMAR VM
RATED FREQUENCY 50Hz TEST AREA AMBIENT (°C) 31°C
STANDARD REF IEC 61439-1 & 2 TEST AREA HUMIDITY (%) 35%

PROJECT INTERCONTINENTAL HOTEL FUJAIRAH LANDSCAPEING


CLIENT ALAIN
CONSULTANT KHATIB & ALAMI
CONTRACTOR PROSCOPE

A VISUAL INSPECTION
ENCLOSURE SIZE OK CURRENT TRANSFORMERS N/A
ENCLOSURE MATERIAL OK FUSES / FUSE BASES OK
ENCLOSURE COLOUR OK INSULATORS / BUS SUPPORTS N/A
FORM OF CONSTRUCTION OK ATS CONTROLER-SOCOMEC N/A
ENCLOSURE PADLOCK OK SPD N/A
MATERIAL THICKNESS OK INCOMER / OUTGOING POSSITION OK
PVC SHROUDING N/A ACB MECHANICAL INTERLOCK N/A
EXTERNAL HANDLE OK CONTACTORS OK
TIGHTNESS OF CONNECTION N/A DRAWING POCKETS + DRAWINGS OK
COPPER BUS BAR SIZE N/A RUN /OFF/ TRIP INDICATION LAMP OK
INCOMING RATING OK PUSH BUTTON ON/OFF OK
OUTGOING RATING OK CONTROL RELAYS OK
DEGREE OF PROTECTION OK TERMINAL BLOCKS OK
MCCB PADLOCK N/A WIRE MARKINGS OK
EARTHING OK SECTION LABELS OK
NEUTRAL OK R Y B LABELS OK
AMMETER RATING N/A OVERLOAD RELAYS OK
VOLTMETER RATING N/A NEUTRAL AND EARTH POSITION OK
MULTIFUNCTION METER N/A BUSBAR INSULATOR SPACING N/A
PHASE BARRIERS OK BUSBAR SLEEVING / COLOUR CODING N/A

Document No:- SEG-HSE-F-30 Rev.no.- 00 Issue Date-20-08-2019 Page | 1/4


OK CLEARANCE AND CREEPAGE DISTANCE N/A
RYB INDICATIONS
BETWEEN BUSBAR
N/A SHROUDING OF BUSBARS / ACCIDENTAL N/A
VOLTMETER SELECTOR SWITCH LIVE PARTS/INCOMING AND OUT
GOING FEEDERS
N/A ORIENTATION OF PHASES ON OK
ELR + SHUNT TRIPS
DIFFERENT INCOMERS
CAUTION LABELS OK EARTHE BAR IS CONTINUOUS OK
CABLE ENTRY - OK WIRE SIZE AND COLOUR CODES OK
GLANDING ARRANGEMENTS OK WIRE CRIMPING AND NUMBERING OK
TERMINAL IDENTIFICATION OK WIRE ROUTING AND BUNCHING OK
1 CONSTRUCTION RESULT REMARKS
1.1 ENCLOSURE-OVER ALL DIMENSIONS OK
1.2 MATERIAL THICKNESS, PAINT SHADE/FINISH [INTERNAL/EXTERNAL] OK
1.3 TYPE OF ENCLOSURE OK
1.4 DEGREE OF PROTECTION OF THE ENCLOSURE OK
2 LAYOUT RESULT REMARKS
2.1 COMPONENT GENERAL LAYOUT OK
2.2 I/C FEEDER POSITION OK
2.3 I/C FEEDER HANDLE POSITION N/A
2.4 O/G FEEDERS' HANDLE POSITION N/A
2.5 CABLE ACCESS- OK
3 BUSBAR RESULT REMARKS
3.1 COPPER BUSBAR SIZES (MAIN, DROPPER & TAP-OFF) N/A
3.2 NEUTRAL AND EARTH POSITION OK
3.3 BUSBAR INSULATOR SPACING N/A
3.4 BUSBAR SLEEVING / COLOUR CODING N/A
3.5 CLEARANCE AND CREEPAGE DISTANCE BETWEEN BUSBAR AND BODY N/A
3.6 SHROUDING OF BUSBARS / LIVE PARTS/INCOMING AND OUTGOING FEEDERS OK
3.7 ORIENTATION OF PHASES ON DIFFERENT INCOMERS N/A
3.8 EARTHE BAR IS CONTINUOUS OK
4 CABLE TERMINATION RESULT REMARKS
4.1 CABLE ENTRY OK
4.2 GLANDING ARRANGEMENTS OK
4.3 TERMINAL IDENTIFICATION LABEL AND TERMINAL MARKER OK
4.4 WIRE SIZE AND COLOUR CODES OK

Document No:- SEG-HSE-F-30 Rev.no.- 00 Issue Date-20-08-2019 Page | 2/4


4.5 WIRE CRIMPING AND NUMBERING OK
4.6 WIRE ROUTING AND BUNCHING OK
4.7 EARTHING OF BODY, COMPONENT OK
4.8 EARTH WIRE SIZE AND COLOUR CODES OK
5 COMPONENTS & RATING RESULT REMARKS
5.1 MAKE OF COMPONENTS OK
5.2 MAIN & BRANCH BREAKERS-ACB,MCCB,MCB,FUSES - POLES,AMP/KA RATINGS OK
6 LABELS RESULT REMARKS
6.1 INTERNAL MOUNTED COMPONENTS POSITION AND LABELS OK
6.2 MAIN LABEL, LABEL FOR FEEDERS OK
6.3 WARNING LABEL-INCOMING & OUTGOING SIDE OK
7 GENERAL RESULT REMARKS
7.1 DOOR LOCKING FACILITIES OK
7.2 DOOR ALIGNMENTS OK
7.3 DWG. POCKET OK
8 MECHANICAL TEST RESULT REMARKS
8.1 RIGIDITY OF MOUNTING OK
8.2 TIGHTENING OF NUT, BOLT AND RED MARKING FOR TORQUE OK
8.3 TIGHTNESS OF WIRES AND BUSBARS AS PER ATTACHED TORQUE TABLE OK
8.4 CHECKING OF DOOR I/L OPERATION OK
9 FUNCTION & SUPPLY TEST RESULT REMARKS
9.1 CHECK INDICATION LAMPS OK
9.2 CHECK THE OPERATION OF ELCB & MCB OK
9.3 CHECKING OF TIMERS OK
9.4 CHECKING OF INCOMER ON/OFF FUNCTION OK
9.5 CHECKING OF MCCB FUNCTION OK
9.6 A. MCCB ON OK
9.7 B. MCCB OFF OK
9.8 C.MCCB TRIP OK
9.9 CHECKING OF STARTER INPUT & OUTPUT SUPPLY OK
9.11 CHECKING OF STARTER AUTO MODE OPERATION OK
9.12 CHECKING OF STARTER AUTO/RUN/TRIP STATUS OK
9.13 CHECKING OF STARTER AUTO MODE OPERATION OK
9.15 CHECKING OF STARTER HAND MODE OPERATION OK
9.16 CHECKING OF PUSH BUTTON AND INDICATION LAMPS OK

Document No:- SEG-HSE-F-30 Rev.no.- 00 Issue Date-20-08-2019 Page | 3/4


9.17 CHECKING OF LEVEL SENSOR FUNCTION OK
9.18 CHECKING OF LATCHING RELAY FUNCTION OK
9.19 CHECKING OF EM STOP FUNCTION OK
9.20 CHECKING OF CONTROL TRANSFORMER OK
9.21 CHECKING OF SWITCHING CONTACTOR OPERATION OK
9.22 CHECKING OF DUTY & STANDBY FUNCTION OK

TESTED BY : JACOB PC APPROVED BY : SUNIL KUMAR VM

WITNESSED BY QA/QC CLIENT CONSULTANT CONTACTOR

NAME SUNIL KUMAR VM

DESIGINATION QA/QC ENGINEER

COMPANY SEG

SIGNATURE

N/A-NOT AVAILABLE, NO-NOT OK

Document No:- SEG-HSE-F-30 Rev.no.- 00 Issue Date-20-08-2019 Page | 4/4


FACTORY TEST CERTIFICATE FOR DB
JOB No.: P23-101 DATE: 25/09/2023

PROJECT: INTERCONTINENTAL HOTEL FUJAIRAH LANDSCAPEING

CLIENT: ALAIN

CONSULTANT: KHATIB & ALAMI

CONTRACTOR: PROSCOPE

TEST CONDUCTED

Manual Switching of MCB/Isolator


Rigidity of Mounting/Tightness of

ELCB/CONTACTOR/PHOTOCELL
Visual Inspection

Continuity Check

Functional Test
Drawing No.

Tested On

Fasteners

/TIMER
ITEM #

Test of
Description REMARKS
1 DB-BB-S P23-101-DB 24-09-23 OK OK OK OK OK OK Passed

2 DB-WS-S P23-101-DB 24-09-23 OK OK OK OK OK OK Passed

TESTED BY: JACOB PC WITNESSED BY: SUNIL KUMAR VM(QA/QC)

SES-FTC.DB/Rev.00 Page 1 of 1 dt.20.12.10


IX. MODIFICATIONS
MODIFICATION INFORMATION
Each Switchgear unit supplied has been designed with a spare capacity of 20% spare
modules for additional circuits to be connected and accordingly the breaker capacity has
been selected to support this additional load.

There are spares points available across each circuit for any additional fittings to be
connected in the event of any modifications.

If any need arises in the future for the Modifications of the installed systems then this
should only be done in consultation with the System Manufactures/ Suppliers or the Sub-
Contractors and a Building Services Design Engineer should ensure that the proposed
modifications match the required system requirements and characteristics.

• It is recommended not to carry out any substantial modifications on the system.


• Should modifications become necessary for any reason, all modifications shall comply
with the original design requirements, as indicated in the Project Specifications.
• All manufacturer instructions shall be followed.
• Consult the authorised manufacturer's representative.
• Electrical panels incorporate spaces / racks for mounting spare equipment (circuit
breakers). This space is at least 20% the total space capacities.
• All modifications shall be carried out by qualified personnel and by following DEWA's
regulations.
X. WARRANTY CERTIFICATE
XI. AS BUILT DRAWINGS
GENERAL DATA :
LOCATION : INDOOR OUTDOOR

MOUNTING : FLOOR WALL

CABLE ENTRY & ACCESS INCOMING OUTGOING


D-300mm 800mm 800mm
BOTTOM ENTRY
SEG LABEL PANEL TITLE
TOP ENTRY

300mm
FRONT ACCESS

ELECTRICAL DATA : QM,250A


INCOMER
R Y B
RATED SERVICE VOLTAGE : 415V 400V E
MFM
N
RATED CURRENT : 250A
AUX. VOLTAGE : 230V AC
INSULATION VOLTAGE : 690V AC
RATED FREQUENCY : 50Hz AC
EARTHING SYSTEM : TNS TT TNC

1200mm
PHASE BARRIER
CUBICLE DATA : FOR ALL MCCB's PVC SHROUD

CUBICLE SYSTEM : SHEET STEEL


CF1
CF2
ENCLOSURE SIZE : 1200 (H) x 800 (W) x 300 (D)mm CF3

CT1 CT3
:
DEGREE OF PROTECTION-ENCLOSURE IP-54
CT2
FORM OF CONSTRUCTION : FORM-2 TYPE-2
ACCESS CLOSING : COMMON DOOR WITH KEY
Q1,32A Q2,40A
PAINT FINISH : RAL 7035 RAL 7035
ENCLOSURE SIZE : SHEET STEEL THICKNESS - 1.5mm Q3,32A Q4,32A

PAINT THICKNESS 80-120 MICRONS

BUSBAR DATA :
BUS BAR SIZE : RYBN:30x10MM
Q5,200A
E:30x5MM

COPPER FLAT BARS/POWER WIRING


INTER CONNECTION
INSULATED BUSBAR
FRONT LAYOUT INTERNAL LAYOUT
EXT.POWER CABLE CONNECTION FLAT BARS DIRECT ON DEVICE

BUSBAR IDENTIFICATION R,Y,B,N : RED, YELLOW, BLUE, BLACK


EARTH : , GREEN/YELLOW

300mm
CONSTRUCTION DATA : TOP/BOTTOM
INTERNAL CONTROL WIRING VOLTAGE CIRCUIT : 1.5 Sq.mm
CURRENT CIRCUIT : 2.5 Sq.mm

LABELS ARE WHITE BACKGROUND TRAFFOLITE ADHESIVE


BLACK LETTERS IN ENGLISH.
ALUMINIUM- SCREWS & NUTS
GLAND DETAILS
INCOMING MOUNTING FIXED PLUG-IN

NO. REVISION DATE : BY DATE : 11/08/2023 CONSULTANT CLIENT PROJECT PANEL BUILDER TITLE

PAGE: 1 / 3
SAFETY ELECTRICAL
0 FOR APPROVAL 11/08/23 RKR DRAWN BY : RKR KM2K -- SWITCHGEAR
SMDB-FP
1 CHECKED BY: TPP INTERCONTINENTAL HOTEL MANUFACTURING LLC. FED FROM LV PANEL-08
MAIN CONTRACTOR SUB CONTRACTOR P.O.BOX-3494,DUBAI. REFERENCE
2 PROJECT No: P23-** FUJAIRAH LANDSCAPEING TEL-04-8867002.
3 FILE NAME: P23-** -- -- FAX-04-8867003.
FRONT & INTERNAL LAYOUT
1st ANGLE PROJECTION
4 SCALE: ALL DIM. ARE IN MM
SCALE:- N.T.S
www.safetyelectricalgroup.com
This document and all information contained herein, is the property of, and embodies confidential and proprietary information of Safety Electrical Group and may not be reproduced, modified or redistributed without the prior written consent of Safety Electrical Group.
FED FROM LV PANEL-08

CABLE SIZE 4Cx150mm²/1Cx95mm²

QM
250A,TP
MCCB,
36kA
MULTI FUNCTION
METER
CT1-CT3
250/5A MFM

SUPPLYON
CF1-3
R Y B

PE ELECTROLYTIC TINNED COPPER 30x5 H1 H2 H3


BUS BAR BUS BAR

3PH+N ELECTROLYTIC TINNED COPPER 30x10 (415V, 400A,50Hz)


BUS BAR BUS BAR BUS BAR BUS BAR BUS BAR BUS BAR BUS BAR BUS BAR BUS BAR BUS BAR BUS BAR BUS BAR BUS BAR BUS BAR BUS BAR

RYB RYB RYB RYB RYB

Q1 Q2 Q3 Q4 Q5
MCCB MCCB MCCB MCCB MCCB
32A,TP 40A,TP 32A,TP 32A,TP 200A,TP
25kA 25kA 25kA 25kA 36kA

SPLASH PAD FEEDER PILLAR


FEEDER DESC. SPARE SPARE SPARE (FP-FB-S)
CONTROL PANEL
CABLE SIZE -- 4Cx16mm² / -- -- 4Cx150mm² /
1Cx16mm² 1Cx95mm²
CONNECTED LOAD 10.00KW 20.00KW 10.00KW 9.58KW 103.65KW

BUSBAR LINK SIZE 12x05mm 12x05mm 12x05mm 12x05mm 20x10mm

CABLE EXIT TOP TOP TOP TOP TOP

NO. REVISION DATE : BY DATE : 11/08/2023 CONSULTANT CLIENT PROJECT PANEL BUILDER TITLE

PAGE: 2 / 3
SAFETY ELECTRICAL
0 FOR APPROVAL 11/08/23 RKR DRAWN BY : RKR KM2K -- SWITCHGEAR
SMDB-FP
1 CHECKED BY: TPP INTERCONTINENTAL HOTEL MANUFACTURING LLC. FED FROM LV PANEL-08
MAIN CONTRACTOR SUB CONTRACTOR P.O.BOX-3494,DUBAI. REFERENCE
2 PROJECT No: P23-** FUJAIRAH LANDSCAPEING TEL-04-8867002.
3 FILE NAME: P23-** -- -- FAX-04-8867003.
SINGLE LINE DIAGRAM
1st ANGLE PROJECTION
4 SCALE: ALL DIM. ARE IN MM
SCALE:- N.T.S
www.safetyelectricalgroup.com
This document and all information contained herein, is the property of, and embodies confidential and proprietary information of Safety Electrical Group and may not be reproduced, modified or redistributed without the prior written consent of Safety Electrical Group.
NO. REVISION DATE : BY DATE : 11/08/2023 CONSULTANT CLIENT PROJECT PANEL BUILDER TITLE

PAGE: 3 / 3
SAFETY ELECTRICAL
0 FOR APPROVAL 11/08/23 RKR DRAWN BY : RKR KM2K -- SWITCHGEAR
SMDB-FP
1 CHECKED BY: TPP INTERCONTINENTAL HOTEL MANUFACTURING LLC. FED FROM LV PANEL-08
MAIN CONTRACTOR SUB CONTRACTOR P.O.BOX-3494,DUBAI. REFERENCE
2 PROJECT No: P23-** FUJAIRAH LANDSCAPEING TEL-04-8867002.
3 FILE NAME: P23-** -- -- FAX-04-8867003.
BILL OF MATERIALS
1st ANGLE PROJECTION
4 SCALE: ALL DIM. ARE IN MM
SCALE:- N.T.S
www.safetyelectricalgroup.com
This document and all information contained herein, is the property of, and embodies confidential and proprietary information of Safety Electrical Group and may not be reproduced, modified or redistributed without the prior written consent of Safety Electrical Group.
DETAILS OF CONNECTED LOAD / MAXIMUM DEMAND
PROJECT: Intercontinental Hotel Fujairah
Planned Completion Date: Client : Alain Plot No.:
SUB MAIN DISTRIBUTION BOARD (SMDB) Consultant: khatib & Alami Location: Splash Pad Pump Room

FED FROM: Existing LV Panel-08 Contractor: Water in Motion LLC


LSF /
RATING (AMPS.) CABLE SIZE CONNECTED LOAD - KW REMARK
FAULT XLPE ECC SIZE Total Connected Load Maximum Demand
CIRCUIT / FEEDER DB No. SP/TP DUTY B-
F/S MCCB / SWA / 1C/mm2 R-PHASE Y-PHASE (TCL) KW Load (MDL)
KA 2/4 X 1C mm2 2/3/4C mm2 PHASE
ISO ACB LSF KW KW
KW
With Integral
Incomer TP 250A 50 4C X 150 Sqmm CU/XLPE/SWA/PVC 1C X 95 51.12 51.02 51.09 153 137.91
Private Meter

OUTGOING:

Splash Pad Control Panel TP 40 25 4C X 16 Sqmm CU/XLPE/SWA/PVC 1C X 16 6.6 6.7 6.7 20.00 17.00

Feeder Pillar (FP-FB-S) TP 200 25 4C X 150 Sqmm CU/XLPE/SWA/PVC 1C X 95 34.62 34.47 34.57 103.65 88.10

Spare TP 32 25 - - 3.33 3.33 3.33 10.00 8.50

Spare TP 32 25 - - 3.33 3.33 3.33 10.00 8.50

Spare TP 32 25 - - 3.19 3.19 3.19 9.58 8.14

SMDB CONNECTED TO : Existing LV Panel-08 TOTAL CONNECTED LOAD PER PHASE 51.12 51.02 51.09 153.23 130.2

MAX. DEMAND ( 3 Phase ): 130.24 kw, At 0.85 Diversity Factor TOTAL CONNECTED LOAD ( 3 Phase ): 153.23 KW
CONTRACTOR: PROSCAPE Telephone: 04-2770244 Fax:04-2770424
Type of Meter ( Rating of Incomer ) : (1) Upto 60A (2) Upto 100A (3) 125 - 160 A (4) LV Ct…….../5A / HV CT……………/……A.
( 1 Phase ) ( 3 Phase )
GENERAL DATA :
LOCATION : INDOOR OUTDOOR

MOUNTING : FLOOR WALL

CABLE ENTRY & ACCESS INCOMING OUTGOING

BOTTOM ENTRY

TOP ENTRY
D-250mm 800mm 800mm
FRONT ACCESS
SEG LABEL PANEL TITLE

ELECTRICAL DATA :

300mm
RATED SERVICE VOLTAGE : 415V 400V
125A QM,125A
RATED CURRENT : INCOMER
AUX. VOLTAGE : 230V AC R Y B
N

INSULATION VOLTAGE : 690V AC MFM


E

RATED FREQUENCY : 50Hz AC


EARTHING SYSTEM : TNS TT TNC

1000mm
CUBICLE DATA :
CUBICLE SYSTEM : SHEET STEEL
ENCLOSURE SIZE : 1000 (H) x 800 (W) x 250 (D)mm PHASE BARRIER PVC SHROUD
FOR ALL MCCB's
:
DEGREE OF PROTECTION-ENCLOSURE IP-54 CF1
CT1 CT3
CF2
FORM OF CONSTRUCTION : FORM-2 TYPE-2 CF3
CT2

ACCESS CLOSING : COMMON DOOR WITH KEY


PAINT FINISH : RAL 7035 RAL 7035
Q1,63A Q2,40A
ENCLOSURE SIZE : SHEET STEEL THICKNESS - 1.5mm
PAINT THICKNESS 80-120 MICRONS Q3,32A Q4,32A

BUSBAR DATA :
BUS BAR SIZE : RYBN:30x10MM
E:30x5MM

INTER CONNECTION
COPPER FLAT BARS/POWER WIRING FRONT LAYOUT INTERNAL LAYOUT
INSULATED BUSBAR

EXT.POWER CABLE CONNECTION FLAT BARS DIRECT ON DEVICE

250mm
BUSBAR IDENTIFICATION R,Y,B,N : RED, YELLOW, BLUE, BLACK
EARTH : , GREEN/YELLOW TOP/BOTTOM
CONSTRUCTION DATA :
INTERNAL CONTROL WIRING VOLTAGE CIRCUIT : 1.5 Sq.mm
CURRENT CIRCUIT : 2.5 Sq.mm
GLAND DETAILS
LABELS ARE WHITE BACKGROUND TRAFFOLITE ADHESIVE
BLACK LETTERS IN ENGLISH.
ALUMINIUM- SCREWS & NUTS

INCOMING MOUNTING FIXED PLUG-IN

NO. REVISION DATE : BY DATE : 11/08/2023 CONSULTANT CLIENT PROJECT PANEL BUILDER TITLE

PAGE: 1 / 3
SAFETY ELECTRICAL
0 FOR APPROVAL 11/08/23 RKR DRAWN BY : RKR KM2K -- SWITCHGEAR
SMDB-BB-S
1 CHECKED BY: TPP INTERCONTINENTAL HOTEL MANUFACTURING LLC. FED FROM LV PANEL-03
MAIN CONTRACTOR SUB CONTRACTOR P.O.BOX-3494,DUBAI. REFERENCE
2 PROJECT No: P23-** FUJAIRAH LANDSCAPEING TEL-04-8867002.
3 FILE NAME: P23-** -- -- FAX-04-8867003.
FRONT & INTERNAL LAYOUT
1st ANGLE PROJECTION
4 SCALE: ALL DIM. ARE IN MM
SCALE:- N.T.S
www.safetyelectricalgroup.com
This document and all information contained herein, is the property of, and embodies confidential and proprietary information of Safety Electrical Group and may not be reproduced, modified or redistributed without the prior written consent of Safety Electrical Group.
FED FROM LV PANEL-03

CABLE SIZE 4Cx50mm²/1Cx25mm²

QM
125A,TP
MCCB,
36kA
MULTI FUNCTION
METER
CT1-CT3
125/5A MFM

SUPPLYON
CF1-3
R Y B

PE ELECTROLYTIC TINNED COPPER 30x5 H1 H2 H3


BUS BAR BUS BAR

3PH+N ELECTROLYTIC TINNED COPPER 30x10 (415V, 400A,50Hz)


BUS BAR BUS BAR BUS BAR BUS BAR BUS BAR BUS BAR BUS BAR BUS BAR BUS BAR BUS BAR BUS BAR BUS BAR BUS BAR BUS BAR BUS BAR

RYB RYB RYB RYB

Q1 Q2 Q3 Q4
MCCB MCCB MCCB MCCB
63A,TP 40A,TP 32A,TP 32A,TP
25kA 25kA 25kA 25kA

FEEDER DESC. DB-BB-S DB-WS-S SPARE SPARE

CABLE SIZE 4Cx16mm² / 4Cx10mm² / -- --


1Cx16mm² 1Cx10mm²
CONNECTED LOAD 26.44KW 10.51KW 14.50KW 5.00KW

BUSBAR LINK SIZE 12x05mm 12x05mm 12x05mm 12x05mm

CABLE EXIT TOP TOP TOP TOP

NO. REVISION DATE : BY DATE : 11/08/2023 CONSULTANT CLIENT PROJECT PANEL BUILDER TITLE

PAGE: 2 / 3
SAFETY ELECTRICAL
0 FOR APPROVAL 11/08/23 RKR DRAWN BY : RKR KM2K -- SWITCHGEAR
SMDB-BB-S
1 CHECKED BY: TPP INTERCONTINENTAL HOTEL MANUFACTURING LLC. FED FROM LV PANEL-03
MAIN CONTRACTOR SUB CONTRACTOR P.O.BOX-3494,DUBAI. REFERENCE
2 PROJECT No: P23-** FUJAIRAH LANDSCAPEING TEL-04-8867002.
3 FILE NAME: P23-** -- -- FAX-04-8867003.
SINGLE LINE DIAGRAM
1st ANGLE PROJECTION
4 SCALE: ALL DIM. ARE IN MM
SCALE:- N.T.S
www.safetyelectricalgroup.com
This document and all information contained herein, is the property of, and embodies confidential and proprietary information of Safety Electrical Group and may not be reproduced, modified or redistributed without the prior written consent of Safety Electrical Group.
NO. REVISION DATE : BY DATE : 11/08/2023 CONSULTANT CLIENT PROJECT PANEL BUILDER TITLE

PAGE: 3 / 3
SAFETY ELECTRICAL
0 FOR APPROVAL 11/08/23 RKR DRAWN BY : RKR KM2K -- SWITCHGEAR
SMDB-BB-S
1 CHECKED BY: TPP INTERCONTINENTAL HOTEL MANUFACTURING LLC. FED FROM LV PANEL-03
MAIN CONTRACTOR SUB CONTRACTOR P.O.BOX-3494,DUBAI. REFERENCE
2 PROJECT No: P23-** FUJAIRAH LANDSCAPEING TEL-04-8867002.
3 FILE NAME: P23-** -- -- FAX-04-8867003.
BILL OF MATERIALS
1st ANGLE PROJECTION
4 SCALE: ALL DIM. ARE IN MM
SCALE:- N.T.S
www.safetyelectricalgroup.com
This document and all information contained herein, is the property of, and embodies confidential and proprietary information of Safety Electrical Group and may not be reproduced, modified or redistributed without the prior written consent of Safety Electrical Group.
DETAILS OF CONNECTED LOAD / MAXIMUM DEMAND
PROJECT: Intercontinental Hotel Fujairah
Planned Completion Date: Client : Alain Plot No.:
SMDB-BB-S Consultant: khatib & Alami Location: Beach Bar Electrical Room

FED FROM: Existing LV Panel-03 Contractor: Water in Motion LLC


LSF /
RATING (AMPS.) CABLE SIZE CONNECTED LOAD - KW REMARK
FAULT XLPE ECC SIZE Total Connected Load Maximum Demand
CIRCUIT / FEEDER DB No. SP/TP DUTY B-
F/S MCCB / SWA / 1C/mm2 R-PHASE Y-PHASE (TCL) KW Load (MDL)
KA 2/4 X 1C mm2 2/3/4C mm2 PHASE
ISO ACB LSF KW KW
KW
With Integral
Incomer TP 125A 50 4C X 50 Sqmm CU/XLPE/SWA/PVC 1C X 25 11.42 11.72 13.76 37 33.22
Private Meter

OUTGOING:

DB-BB-S
TP 63 25 4C X 16 Sqmm CU/XLPE/SWA/PVC 1C X 16 8.7 8.4 9.3 26.40 22.44
(Beach Bar Distribution Board)

DB-WS-S
TP 40 25 4C X 10 Sqmm CU/XLPE/SWA/PVC 1C X 10 2.68 3.36 4.47 10.51 8.93
(Beach Washroom Distribution Board)

Spare TP 32 25 - - 14.5 12.32

Spare TP 32 25 - - 5.00 4.25

SMDB-BB-S CONNECTED TO : Existing LV Panel-03 TOTAL CONNECTED LOAD PER PHASE 11.42 11.72 13.76 56.40 47.9

MAX. DEMAND ( 3 Phase ): 56.44 kw, At 0.85 Diversity Factor TOTAL CONNECTED LOAD ( 3 Phase ): 56.44 KW
CONTRACTOR: PROSCAPE Telephone: 04-2770244 Fax:04-2770424
Type of Meter ( Rating of Incomer ) : (1) Upto 60A (2) Upto 100A (3) 125 - 160 A (4) LV Ct…….../5A / HV CT……………/……A.
( 1 Phase ) ( 3 Phase )
GENERAL DATA :
LOCATION : INDOOR OUTDOOR 900mm 900mm
D-300mm
MOUNTING : FLOOR WALL

CABLE ENTRY & ACCESS INCOMING OUTGOING

BOTTOM ENTRY

ELR1

ELR2
CF1
CF2
CF3
E3 E4 E5 E6 E7 E8
5 6 7 8 5 6 7 8

TOP ENTRY
T R T R

FRONT ACCESS
1 2 3 4 1 2 3 4

TIMER
ELECTRICAL DATA : KM3 KM4 KM5 KM6 SEC3 SEC4 SEC5 SEC6 SEC7 SEC8

RATED SERVICE VOLTAGE : 415V 400V OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF

RATED CURRENT : 200A


AUX. VOLTAGE : 230V AC
INSULATION VOLTAGE : 690V AC
RATED FREQUENCY : 50Hz AC

1400mm
EARTHING SYSTEM : TNS TT TNC

CUBICLE DATA : Q1
CUBICLE SYSTEM : POLYESTER ENCLOSURE
ENCLOSURE SIZE : 1400 (H) x 900 (W) x 300 (D)mm Q2

:
DEGREE OF PROTECTION-ENCLOSURE IP-65
FORM OF CONSTRUCTION : FORM-2 TYPE-2
ACCESS CLOSING : COMMON DOOR WITH KEY
PAINT FINISH : RAL 6038 RAL 7035
ENCLOSURE SIZE : WALL THICKNESS - 3mm
N
CBCT

R Y B
QM,200A,TP
BUSBAR DATA :

300mm
E CBCT
ISOLATOR
BUS BAR SIZE : RYBN:30x10MM
E:30x5MM

COPPER FLAT BARS/POWER WIRING


INTER CONNECTION
INSULATED BUSBAR

EXT.POWER CABLE CONNECTION FLAT BARS DIRECT ON DEVICE


FRONT LAYOUT INTERNAL LAYOUT
BUSBAR IDENTIFICATION R,Y,B,N : RED, YELLOW, BLUE, BLACK
EARTH : , GREEN/YELLOW

250mm
300mm
CONSTRUCTION DATA :
INTERNAL CONTROL WIRING VOLTAGE CIRCUIT : 1.5 Sq.mm BOTTOM
CURRENT CIRCUIT : 2.5 Sq.mm

LABELS ARE WHITE BACKGROUND TRAFFOLITE ADHESIVE


BLACK LETTERS IN ENGLISH.
ALUMINIUM- SCREWS & NUTS

INCOMING MOUNTING FIXED PLUG-IN


GLAND DETAILS
NO. REVISION DATE : BY DATE : 11/08/2023 CONSULTANT CLIENT PROJECT PANEL BUILDER TITLE

PAGE: 1 / 4
SAFETY ELECTRICAL
0 FOR APPROVAL 11/08/23 RKR DRAWN BY : RKR KM2K -- SWITCHGEAR
FEEDER PILLAR (FP-FB-S)
1 CHECKED BY: TPP INTERCONTINENTAL HOTEL MANUFACTURING LLC. FED FROM SMDB-FP
MAIN CONTRACTOR SUB CONTRACTOR P.O.BOX-3494,DUBAI. REFERENCE
2 PROJECT No: P23-** FUJAIRAH LANDSCAPEING TEL-04-8867002.
3 FILE NAME: P23-** -- -- FAX-04-8867003.
FRONT & INTERNAL LAYOUT
1st ANGLE PROJECTION
4 SCALE: ALL DIM. ARE IN MM
SCALE:- N.T.S
www.safetyelectricalgroup.com
This document and all information contained herein, is the property of, and embodies confidential and proprietary information of Safety Electrical Group and may not be reproduced, modified or redistributed without the prior written consent of Safety Electrical Group.
FED FROM SMDB-FP

CABLE SIZE 4Cx150mm²/1Cx95mm²

QM
ISOLATOR
200A,TP

PE ELECTROLYTIC TINNED COPPER 30x5


BUS BAR BUS BAR

3PH+N ELECTROLYTIC TINNED COPPER 30x10 (415V, 400A,50Hz)


BUS BAR BUS BAR BUS BAR BUS BAR BUS BAR BUS BAR BUS BAR BUS BAR BUS BAR BUS BAR BUS BAR BUS BAR BUS BAR BUS BAR BUS BAR

RYB RYB RYB RYB

E3,ELCB,4P E4,ELCB,4P
40A/100mA 40A/100mA
Q1 Q2
MCCB SOR
MCCB SOR
100A,TP 100A,TP
25kA 25kA KM4
KM3 CONTROL THROUGH 24 HOUR TIMER & PHOTOCELL
3P,ESB40 3P,ESB40

R Y B R Y B
CBCT CBCT
Q3 Q4 Q5 Q6 Q7 Q8
ELR ELR
MCB MCB MCB MCB MCB MCB
10A,SP 10A,SP 10A,SP 10A,SP 10A,SP 10A,SP
10kA 10kA 10kA 10kA 10kA 10kA

FOOD TRUCK FOOD TRUCK


FEEDER DESC. BRACKET LIGHT BRACKET LIGHT LED SPIKE LIGHT LED SPIKE LIGHT BOLLARD LIGHT BOLLARD LIGHT
FLOOR BOX-01 FLOOR BOX-02
CABLE SIZE 4Cx50mm² / 4Cx50mm² / 3Cx2.5mm² 3Cx2.5mm² 3Cx2.5mm² 3Cx2.5mm² 3Cx2.5mm² 3Cx2.5mm²
1Cx25mm² 1Cx25mm²
CONNECTED LOAD 50.00KW 50.00KW 214.4W 214.4KW 56W 72W 82.8W 82.8W

BUSBAR LINK SIZE 12x05mm 12x05mm -- -- -- -- -- --

CABLE EXIT BOTTOM BOTTOM BOTTOM BOTTOM BOTTOM BOTTOM BOTTOM BOTTOM

NO. REVISION DATE : BY DATE : 11/08/2023 CONSULTANT CLIENT PROJECT PANEL BUILDER TITLE

PAGE: 2 / 4
SAFETY ELECTRICAL
0 FOR APPROVAL 11/08/23 RKR DRAWN BY : RKR KM2K -- SWITCHGEAR
FEEDER PILLAR (FP-FB-S)
1 REV-1 04/09/23 RKR CHECKED BY: TPP INTERCONTINENTAL HOTEL MANUFACTURING LLC. FED FROM SMDB-FP
MAIN CONTRACTOR SUB CONTRACTOR P.O.BOX-3494,DUBAI. REFERENCE
2 PROJECT No: P23-** FUJAIRAH LANDSCAPEING TEL-04-8867002.
3 FILE NAME: P23-** -- -- FAX-04-8867003.
SINGLE LINE DIAGRAM
1st ANGLE PROJECTION
4 SCALE: ALL DIM. ARE IN MM
SCALE:- N.T.S
www.safetyelectricalgroup.com
This document and all information contained herein, is the property of, and embodies confidential and proprietary information of Safety Electrical Group and may not be reproduced, modified or redistributed without the prior written consent of Safety Electrical Group.
PE ELECTROLYTIC TINNED COPPER 30x5
BUS BAR BUS BAR

3PH+N ELECTROLYTIC TINNED COPPER 30x10 (415V, 400A,50Hz)


BUS BAR BUS BAR BUS BAR BUS BAR BUS BAR BUS BAR BUS BAR BUS BAR BUS BAR BUS BAR BUS BAR BUS BAR BUS BAR BUS BAR BUS BAR

RYB RYB RYB RYB

E5,ELCB,4P E6,ELCB,4P E7,ELCB,4P E8,ELCB,4P


40A/100mA 40A/100mA 40A/100mA 40A/100mA

KM5 KM6
CONTROL THROUGH 24 HOUR TIMER & PHOTOCELL
3P,ESB40 3P,ESB40
Q18
MCB
40A,TP
R Y B R Y B
R Y B 10kA
Q6 Q10 Q11 Q12 Q13 Q14 Q15 Q16 Q17
MCB MCB MCB MCB MCB MCB MCB MCB MCB
10A,SP 10A,SP 10A,SP 10A,SP 10A,SP 10A,SP 16A,SP 10A,SP 10A,SP
10kA 10kA 10kA 10kA 10kA 10kA 10kA 10kA 10kA

FEEDER DESC. LED SPIKE LIGHT LED SPIKE LIGHT BOLLARD LIGHT BOLLARD LIGHT LED SPIKE LIGHT BOLLARD LIGHT EXISTING LIGHT EXISTING LIGHT SPARE SPARE

CABLE SIZE 3Cx2.5mm² 3Cx2.5mm² 3Cx2.5mm² 3Cx2.5mm² 3Cx2.5mm² 3Cx2.5mm² 3Cx2.5mm² 3Cx2.5mm² -- --

CONNECTED LOAD 112W 88W 82.8W 138W 48W 110.4W 150W 100W -- --

BUSBAR LINK SIZE -- -- -- -- -- -- -- -- -- --

CABLE EXIT BOTTOM BOTTOM BOTTOM BOTTOM BOTTOM BOTTOM BOTTOM BOTTOM BOTTOM BOTTOM

NO. REVISION DATE : BY DATE : 11/08/2023 CONSULTANT CLIENT PROJECT PANEL BUILDER TITLE

PAGE: 3 / 4
SAFETY ELECTRICAL
0 FOR APPROVAL 11/08/23 RKR DRAWN BY : RKR KM2K -- SWITCHGEAR
FEEDER PILLAR (FP-FB-S)
1 REV-1 04/09/23 RKR CHECKED BY: TPP INTERCONTINENTAL HOTEL MANUFACTURING LLC. FED FROM SMDB-FP
MAIN CONTRACTOR SUB CONTRACTOR P.O.BOX-3494,DUBAI. REFERENCE
2 PROJECT No: P23-** FUJAIRAH LANDSCAPEING TEL-04-8867002.
3 FILE NAME: P23-** -- -- FAX-04-8867003.
SINGLE LINE DIAGRAM
1st ANGLE PROJECTION
4 SCALE: ALL DIM. ARE IN MM
SCALE:- N.T.S
www.safetyelectricalgroup.com
This document and all information contained herein, is the property of, and embodies confidential and proprietary information of Safety Electrical Group and may not be reproduced, modified or redistributed without the prior written consent of Safety Electrical Group.
NO. REVISION DATE : BY DATE : 11/08/2023 CONSULTANT CLIENT PROJECT PANEL BUILDER TITLE

PAGE: 4 / 4
SAFETY ELECTRICAL
0 FOR APPROVAL 11/08/23 RKR DRAWN BY : RKR KM2K -- SWITCHGEAR
FEEDER PILLAR (FP-FB-S)
1 REV-1 04/09/23 RKR CHECKED BY: TPP INTERCONTINENTAL HOTEL MANUFACTURING LLC. FED FROM SMDB-FP
MAIN CONTRACTOR SUB CONTRACTOR P.O.BOX-3494,DUBAI. REFERENCE
2 PROJECT No: P23-** FUJAIRAH LANDSCAPEING TEL-04-8867002.
3 FILE NAME: P23-** -- -- FAX-04-8867003.
BILL OF MATERIALS
1st ANGLE PROJECTION
4 SCALE: ALL DIM. ARE IN MM
SCALE:- N.T.S
www.safetyelectricalgroup.com
This document and all information contained herein, is the property of, and embodies confidential and proprietary information of Safety Electrical Group and may not be reproduced, modified or redistributed without the prior written consent of Safety Electrical Group.
PROJECT : INTERCONTINENTAL FUJAIRAH
Location: External Landscape Area
DB NO : FEEDER PILLAR (FP-FB-S)
LOAD DISTRIBUTION SCHEDULE
FED FROM : SMDB-FP
Connected Load (kW): 103.652
RATING OF INCOMER: 200A
CONNECTED LOADS/ POINTS LOAD PER CIRCUIT KW
RATING OF MCB RTG SMART
RATING OF ELCB SL # CKT # CCT WIRE SIZE mm2 ECC WIRE SIZE mm2 Types Of Lightings & Power 16A COMMANDO 15A WATTS Remarks
INCOMER Amps LTG ISO POLE JB W/H H/D R Y B
SOCKET S/O
SOCKET

100A,4P, 100mA, 4Cx50 Sqmm XLPE/SWA/PVC +


1 RYB1 100A TP FOOD TRUCK FLOOR BOX-01 - 50000 16666.67 16666.67 16666.67
ELCB-1 1C X 25 Sq.mm PVC Y/G Cable

100A,4P, 100mA, 4Cx50 Sqmm XLPE/SWA/PVC +


2 RYB2 100A TP FOOD TRUCK FLOOR BOX-02 - 50000 16666.67 16666.67 16666.67
ELCB-2 1C X 25 Sq.mm PVC Y/G Cable

3 R3 10 3Cx2.5 Sqmm Cu/XLPE/SWA/PVC Bracket Light (Type BL) 8 26.8 214.4

40A,4P, 100mA,
4 Y3 10 3Cx2.5 Sqmm Cu/XLPE/SWA/PVC Bracket Light (Type BL) 8 26.8 214.4
ELCB-3

5 B3 10 3Cx2.5 Sqmm Cu/XLPE/SWA/PVC LED Spike Light (Type UL) 7 8 56

6 R4 10 3Cx2.5 Sqmm Cu/XLPE/SWA/PVC LED Spike Light (Type UL) 9 8 72

40A,4P, 100mA,
3Cx2.5 Sqmm Cu/XLPE/SWA/PVC
200A TPN ISOLATOR

7 Y4 10 Bollard Light (Type BOL) 6 13.8 82.8


ELCB-4

8 B4 10 3Cx2.5 Sqmm Cu/XLPE/SWA/PVC Bollard Light (Type BOL) 6 13.8 82.8


Contactor +
Digital Timer
9 R5 10 3Cx2.5 Sqmm Cu/XLPE/SWA/PVC LED Spike Light (Type UL) 14 8 112

40A,4P, 100mA,
10 Y5 10 3Cx2.5 Sqmm Cu/XLPE/SWA/PVC LED Spike Light (Type UL) 11 8 88
ELCB-5

11 B5 10 3Cx2.5 Sqmm Cu/XLPE/SWA/PVC Bollard Light (Type BOL) 6 13.8 82.8

12 R6 10 3Cx2.5 Sqmm Cu/XLPE/SWA/PVC Bollard Light (Type BOL) 10 13.8 138

40A,4P, 100mA,
13 Y6 10 3Cx2.5 Sqmm Cu/XLPE/SWA/PVC LED Spike Light (Type UL) 6 8 48
ELCB-6

14 B6 10 3Cx2.5 Sqmm Cu/XLPE/SWA/PVC Bollard Light (Type BOL) 8 13.8 110.4

15 R7 16 3Cx2.5 Sqmm Cu/XLPE/SWA/PVC Existing Light (EL) 15 10 150

40A,4P, 100mA,
16 Y7 10 3Cx2.5 Sqmm Cu/XLPE/SWA/PVC Existing Light (EL) 10 10 100
ELCB-7

17 B7 10 Spare 300

40A,4P, 100mA,
18 RYB8 40A TP Spare 600 600 600
ELCB-8

Total load per phase (W) 34620 34467 34565


Grand Total Load (W) 103652

INCOMING CABLE SIZE: 4CX150 mm2 XLPE/SWA/PVC + 1Cx95 mm2 Y/G PVC Cable LTG= Lighting, EM.Light= Emergency Light, FB= Floor Box
W/H= Water Heater, ISO= Isolator, H/D = Hand Dryer
GENERAL DATA :
LOCATION : INDOOR OUTDOOR

MOUNTING : WALL FLOOR

CABLE ENTRY & ACCESS INCOMING OUTGOING

TOP ENTRY
1000mm 1000mm
D-300mm
BOTTOM ENTRY
PANEL TITLE SEG LABEL

FRONT ACCESS
VOLTMETER AMMETER

INCOMER
2KT1

3KT1
PFR

2KR1

2KR2
CF1
CF2
CF3

CF4
CF5
CF6

3KR1

3KR2

4KR1

4KR2

4KR3

4KR4

5KR1

5KR2

6KR1

7KR1
SUPPLY ON
R-PHASE Y-PHASE B-PHASE E

ELECTRICAL DATA :
RATED SERVICE VOLTAGE : 415V 400V VSS EMERGENCY
STOP
ASS
VOLTMETER AMMETER
OFF 0
RY RN

RATED CURRENT : 40A YB


BR
YN
BN
R

E1 E2 E3 E4 E5 E6 E7

AUX. VOLTAGE : 230V AC


CIRCULATION PUMP-DUTY CIRCULATION PUMP-STANDBY FILTER PUMP-DUTY FILTER PUMP-STANDBY
RUN OFF TRIP RUN OFF TRIP RUN OFF TRIP RUN OFF TRIP

RATED FREQUENCY : 50Hz A.C

POWER TERMINAL
EARTHING SYSTEM : TNS TT TNC START STOP H O A START STOP H O A START STOP H O A START STOP H O A

2KT

3KT
Q2 Q3 Q4.1-3 Q5.1-3 Q6.1-3 Q7 QC1-2

2R

3R
CUBICLE DATA : UV SYSTEM CH. DOSING SYSTEM
OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF

1400mm

1400mm
RUN OFF RUN OFF

CUBICLE SYSTEM : SHEET STEEL


ENCLOSURE SIZE : 1400 (H) x 1000 (W) x 300 (D)mm OFF-ON OFF-ON

2KM1 2KM2 2KM3 3KM1 3KM2 3KM3 4KM1 4KM2 5KM1 5KM2

DEGREE OF PROTECTION : IP-54


LOW LEVEL DRY RUN

FORM OF CONSTRUCTION : FORM-2

CONTROL TERMINAL
ACCESS CLOSING : COMMON DOOR WITH KEY 2OLR1 3OLR1 4OLR1 4OLR2

PAINT FINISH : RAL 7035 RAL 7032


CT2
ENCLOSURE THICKNESS : SHEEL STEEL- 1.5mm Q1
CT1 CT3 TR1

OUTGOING
OT125F3

INTER CONNECTION COPPER FLAT BARS


QM

FLEXIBLE COPPER WIRES

COPPER FLAT BARS


EXTERNAL POWER CABLE
CONNECTION TERMINAL BLOCKS FRONT LAYOUT INTERNAL LAYOUT
DIRECT ON DEVICE TERMINAL

EXTERNAL CONTROL
TERMINAL BLOCKS

300mm
CABLE CONNECTION
TOP/BOTTOM
CONSTRUCTION DATA :
INTERNAL CONTROL WIRING VOLTAGE CIRCUIT : 1.5 Sq.mm
GLAND DETAILS
CURRENT CIRCUIT : 2.5 Sq.mm

LABELS ARE WHITE BACKGROUND PVC ADHESIVE


BLACK LETTERS IN ENGLISH.
ALUMINIUM SCREWS & NUTS

INCOMING MOUNTING FIXED PLUG-IN


OUTGOING MOUNTING FIXED PLUG-IN

NO. REVISION DATE : BY DATE : 11/08/2023 CONSULTANT CLIENT PROJECT PANEL BUILDER TITLE

PAGE: 1 / 08
SAFETY ELECTRICAL
0 FOR APPROVAL 11/08/23 RKR DRAWN BY : RKR KM2K -- SWITCHGEAR SPLASH PAD CONTROL PANEL
1 REV-1 04/09/23 RKR CHECKED BY: TPP INTERCONTINENTAL HOTEL MANUFACTURING LLC. FED FROM SMDB-FP

MAIN CONTRACTOR SUB CONTRACTOR P.O.BOX-3494,DUBAI. REFERENCE


2 PROJECT No: P23-** FUJAIRAH LANDSCAPEING TEL-04-8867002.
3 FILE NAME: P23-** -- -- FAX-04-8867003.
GENERAL SPECIFICATION
1st ANGLE PROJECTION
4 SCALE: ALL DIM. ARE IN MM
SCALE:- N.T.S
www.safetyelectricalgroup.com
This document and all information contained herein, is the property of, and embodies confidential and proprietary information of Safety Electrical Group and may not be reproduced, modified or redistributed without the prior written consent of Safety Electrical Group.
CT1-CT3
100/5A CLASS-1.0
R

S2
S1
Y

S2
S1
B

S2
S1
N

SUPPLY ON

X2

X2

X2
R H1 Y H2 B H3 1 3 5 7 1 3 5 7

D90
E1 E2

D50

D30

D10
X1

X1

X1
R CF1-3,4A R1 40A/100mA 40A/30mA
V1
4P,ELCB 4P,ELCB
Y Y1 P1
ASS
2 4 6 8 2 4 6 8

VSS
V (0-500)V

A2

A1
B B1

A
V2 VOLTMETER
N NL1 N1 P2 2R1 2Y1 2B1 2R1 2Y1 2B1
(0-100)A
1 3 5 1 3 5
AMMETER

R CF4-6,4A R1
Q1 Q2
102
Y Y1 MCCB,TP MCB,TP
PFR
32A,25KA 32A,10kA
B B1 103
NL1
2 4 6 2 4 6
N N1 2R2 2Y2 2B2

1 3 5
QM
ISOLATOR, A1 A1 A1
TP 100A 2KM1 2KM2 2KM3
2 4 6 AF09 A2 AF09 A2 AF09 A2

2OLR1
TF42-7.6
5.7-7.6A

R Y B N E
R Y B N
2U1 2V1 2W1 2U2 2V2 2W2

FED FROM SMDB-FP FEEDER DESCRIPTION HEAT COOL PUMP CIRCULATION PUMP (DUTY)
INCOMING SUPPLY,415V/3P/50Hz KW 10.00KW 4.6KW
4Cx16mm² / 1Cx16mm² CABLE SIZE 4Cx16mm² / 1Cx16mm² 2x3Cx6mm² / 2x1Cx6mm²

NO. REVISION DATE : BY DATE : 11/08/2023 CONSULTANT CLIENT PROJECT PANEL BUILDER TITLE

PAGE: 2 / 08
SAFETY ELECTRICAL
0 FOR APPROVAL 11/08/23 RKR DRAWN BY : RKR KM2K -- SWITCHGEAR SPLASH PAD CONTROL PANEL
1 REV-1 04/09/23 RKR CHECKED BY: TPP INTERCONTINENTAL HOTEL MANUFACTURING LLC. FED FROM SMDB-FP

SUB CONTRACTOR P.O.BOX-3494,DUBAI. REFERENCE


2 PROJECT No: P23-** MAIN CONTRACTOR FUJAIRAH LANDSCAPEING TEL-04-8867002.
3 FILE NAME: P23-** -- -- FAX-04-8867003.
POWER DIAGRAM
1st ANGLE PROJECTION
4 SCALE: ALL DIM. ARE IN MM
SCALE:- N.T.S
www.safetyelectricalgroup.com
This document and all information contained herein, is the property of, and embodies confidential and proprietary information of Safety Electrical Group and may not be reproduced, modified or redistributed without the prior written consent of Safety Electrical Group.
R R

Y Y

B B

N N

1 3 5 7
E3 1 3 5 7
E4
40A/30mA
4P,ELCB 40A/30mA
2 4 6 8
4P,ELCB
2 4 6 8

4R1 4Y1 4B1 4N1


3R1 3Y1 3B1

1 3 5

Q3 1 1 1

MCB,TP
32A,10kA Q4-1 Q4-2 Q4-3
2 4 6
MCB,SP MCB,SP MCB,SP
3R2 3Y2 3B2
20A,10kA 20A,10kA 20A,10kA
2 2 2

4R2 3Y2 4B2


A1 A1
4KM1 4KM2
AF09 A2 AF09 A2
A1 A1 A1
3KM1 3KM2 3KM3
AF09 A2 AF09 A2 AF09 A2

4OLR1 4OLR2
TF42-2.3 TF42-2.3
3OLR1 1.7-2.3A 1.7-2.3A
TF42-7.6
5.7-7.6A

4R3 4N2 4Y3 4N2 4B2 4N3

3U1 3V1 3W1 3U2 3V2 3W2

FEEDER DESCRIPTION CIRCULATION PUMP (STANDBY) FILTER PUMP (DUTY) 0.5HP FILTER PUMP (STANDBY) 0.5HP SPARE
KW 4.6KW 0.373KW 0.373KW 0.3KW
CABLE SIZE 2x3Cx6mm² / 2x1Cx6mm² 3Cx4mm² 3Cx4mm² --

NO. REVISION DATE : BY DATE : 11/08/2023 CONSULTANT CLIENT PROJECT PANEL BUILDER TITLE

PAGE: 3 / 08
SAFETY ELECTRICAL
0 FOR APPROVAL 11/08/23 RKR DRAWN BY : RKR KM2K -- SWITCHGEAR SPLASH PAD CONTROL PANEL
1 REV-1 04/09/23 RKR CHECKED BY: TPP INTERCONTINENTAL HOTEL MANUFACTURING LLC. FED FROM SMDB-FP

MAIN CONTRACTOR SUB CONTRACTOR P.O.BOX-3494,DUBAI. REFERENCE


2 PROJECT No: P23-** FUJAIRAH LANDSCAPEING TEL-04-8867002.
3 FILE NAME: P23-** -- -- FAX-04-8867003.
POWER DIAGRAM
1st ANGLE PROJECTION
4 SCALE: ALL DIM. ARE IN MM
SCALE:- N.T.S
www.safetyelectricalgroup.com
This document and all information contained herein, is the property of, and embodies confidential and proprietary information of Safety Electrical Group and may not be reproduced, modified or redistributed without the prior written consent of Safety Electrical Group.
R

1
E7
1 3 5 7 1 3 5 7 1 3 5 7
40A/100mA QC1
E5 E6
4P,ELCB MCB,SP
40A/100mA 40A/100mA 6A,10kA
4P,ELCB 4P,ELCB
2 4 6 8 2 4 6 8 2 4 6 8 2

5R1 5Y1 5B1 5N1 6R1 6Y1 6B1 6N1 R1


7R1 7Y1 7B1

1 3 5

1 1 1 1 1 1

Q7 101
Q5-1 Q5-2 Q5-3 Q6-1 Q6-2 Q6-3 MCB,TP
MCB,SP MCB,SP MCB,SP MCB,SP MCB,SP MCB,SP 32A,10kA
10A,10kA 10A,10kA 10A,10kA 10A,10kA 10A,10kA 10A,10kA
2 4 6

2 2 2 2 2 2 7R2 7Y2 7B2

+24V
4R2 4Y2 4B2 TR2
A1 A1
230/24V
5KM1 5KM2 500VA
AF09 A2 AF09 A2 0

5R3 5R4 5Y3 5Y4

NL 00

A1

A1
2KT 3KT

A2

A2
2N
24HOUR 24HOUR
TIMER FOR TIMER FOR
5R4 5N1 5Y4 5N2 5B2 5N3 6R2 6N1 6Y2 6N2 6B2 6N3 7R1 7Y2 7B1 7N1
CIRCULATION FILTER PUMP
PUMP

FEEDER
UV SYSTEM CHEMICAL DOSING SYSTEM SPARE SPARE SPARE SPARE SPARE
DESCRIPTION
KW 0.20KW 0.20KW 0.20KW 0.404KW 0.45KW 0.50KW 0.80KW
CABLE SIZE 3Cx6mm² 3Cx6mm² -- -- -- -- --

NO. REVISION DATE : BY DATE : 11/08/2023 CONSULTANT CLIENT PROJECT PANEL BUILDER TITLE

PAGE: 4 / 08
SAFETY ELECTRICAL
0 FOR APPROVAL 11/08/23 RKR DRAWN BY : RKR KM2K -- SWITCHGEAR SPLASH PAD CONTROL PANEL
1 REV-1 04/09/23 RKR CHECKED BY: TPP INTERCONTINENTAL HOTEL MANUFACTURING LLC. FED FROM SMDB-FP

MAIN CONTRACTOR SUB CONTRACTOR P.O.BOX-3494,DUBAI. REFERENCE


2 PROJECT No: P23-** FUJAIRAH LANDSCAPEING TEL-04-8867002.
3 FILE NAME: P23-** -- -- FAX-04-8867003.
POWER DIAGRAM
1st ANGLE PROJECTION
4 SCALE: ALL DIM. ARE IN MM
SCALE:- N.T.S
www.safetyelectricalgroup.com
This document and all information contained herein, is the property of, and embodies confidential and proprietary information of Safety Electrical Group and may not be reproduced, modified or redistributed without the prior written consent of Safety Electrical Group.
EM.PB EM.PB (FIELD)
CIRCULATION PUMP (DUTY) CIRCULATION PUMP (STANDBY)
104 104A X0-1 X0-2

2KT
21

7KR1
118
22
24

21

1,3

21
103
3KR2 2R 2KR2
21

22

22
24

24
4
2
PFR 120
119
TO PAGE NO.7/8

22
24

HAND

HAND
AUTO

AUTO
OFF

OFF
102

1
2

2
2S1 2S1 3S1
(ON POS.)

2
4

4
1

109 121 120A


11

21

11

21
QC2 2PB1 3PB1

1
2KR1 2KR2 STOP STOP 3KR1 3KR2
MCB,SP 3S1
6A,10KA 110
12

22

12

22
125
14

24

14

24
(ON POS.)

2
2

13

13
101 122
2PB2 3PB2
2KM 3KM
START START

11
14

14
111 2KR1 126

12
95

95
123
2OLR1 3OLR1

11
96

96
112 3KR1
127
105 106 107 134 135 136

12
15

15
15

15
21

11

21

11
124
97

97
2KT1 2KT1 3KT1 3KT1
2KM3 2KR1 3KM3 3KR1
18

18
16

16
2OLR1 3OLR1
11

11

11

11
115 130

22

12

22

12
24

14

24

14
113 128
98

98
2KM2 2KM3 3KM2 3KM3
108 133
12

12

12

12
117 132
14

14

14

14
114 116 129 131
A1

A1

A1

A1

A1

A1

A1

A1

A1

A1

A1

A1

A1
X1

X1
X1

X1
X1

X1
G H4 R H5 Y H6 2KR2 2KM3 2KM2 2KT1 2KM1 2KR1 2R 3KM3 3KM2 3KT1 3KM1 3KR1 3KR2 G H7 R H8 Y H9
X2

X2
X2

X2
X2

X2
A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2

A2
00

RUN STOP TRIP TRIP STAR DELTA MAIN AUX LATCHING STAR DELTA MAIN AUX TRIP RUN STOP TRIP
IND IND IND RELAY RELAY RELAY IND IND IND
21

31

21

31
2

2S1 2KR1 2KR2 3S1 3KR1 3KR2


24

34

24

34
4

203 204 205 206 207 208 209 210 211 212 213 214 PE

X1-1 X1-2 X1-3 X1-4 X1-5 X1-6 X1-7 X1-8 X1-9 X1-10 X1-11 X1-12 X1-13
SHIELDED
CABLE AUTO STATUS RUN STATUS TRIP STATUS AUTO STATUS RUN STATUS TRIP STATUS

NO. REVISION DATE : BY DATE : 11/08/2023 CONSULTANT CLIENT PROJECT PANEL BUILDER TITLE

PAGE: 5 / 08
SAFETY ELECTRICAL SPLASH PAD CONTROL PANEL
0 FOR APPROVAL 11/08/23 RKR DRAWN BY : RKR KM2K -- SWITCHGEAR FED FROM SMDB-FP
1 REV-1 04/09/23 RKR CHECKED BY: TPP INTERCONTINENTAL HOTEL MANUFACTURING LLC.
MAIN CONTRACTOR SUB CONTRACTOR P.O.BOX-3494,DUBAI. REFERENCE
2 PROJECT No: P23-** FUJAIRAH LANDSCAPEING TEL-04-8867002.
3 FILE NAME: P23-** -- -- FAX-04-8867003.
CONTROL DIAGRAM
1st ANGLE PROJECTION
4 SCALE: ALL DIM. ARE IN MM
SCALE:- N.T.S
www.safetyelectricalgroup.com
This document and all information contained herein, is the property of, and embodies confidential and proprietary information of Safety Electrical Group and may not be reproduced, modified or redistributed without the prior written consent of Safety Electrical Group.
FILTER PUMP-01 (DUTY) FILTER PUMP-02 (STANDBY)
104

3KT

146

21

1,3

21
4KR4 3R 4KR2

22

22
24

24
4
2
145 147

11

21

11

21
HAND

HAND
AUTO

AUTO
OFF

OFF
1
2

2
4KR1 4KR2 4KR3 4KR4
4S1 4S1 4S2
12

22

12

22
14

24

14

24
(ON POS.)

4
141 148 152
4PB1 4PB3

1
STOP STOP
4S2
142 153
(ON POS.)

2
13

13
149
4PB2 4PB4
4KM1 4KM2
START START

11
14

14
143 4KR1 154
137 138 139 157 158 159

12
97

95

95

97
150
4OLR1 4OLR1 4OLR2 4OLR2

11
98

96

96

98
4KR3
140 144 155
156

12
151

A1
A1

A1

A1

A1

A1

A1
X1

X1
X1

X1
X1

X1
G H10 R H11 Y H124KR2 4KM1 4KR1 3R 4KM2 4KR3 4KR4 G H13 R H14 Y H15
X2

X2
X2

X2
X2

X2
A2

A2

A2

A2

A2

A2

A2
RUN STOP TRIP TRIP MAIN RUN LATCHING MAIN RUN TRIP RUN STOP TRIP
IND IND IND RELAY CONTACTOR RELAY RELAY CONTACTOR RELAY RELAY IND IND IND
21

31

21

31
2

2
4S1 4KR1 4KR2 4S2 4KR3 4KR4
24

34

24

34
4

215 216 217 218 219 220 221 4


222 223 224 225 226 PE

X2-1 X2-2 X2-3 X2-4 X2-5 X2-6 X2-7 X2-8 X2-9 X2-10 X2-11 X2-12 X2-13
SHIELDED AUTO STATUS RUN STATUS TRIP STATUS AUTO STATUS RUN STATUS TRIP STATUS
CABLE

NO. REVISION DATE : BY DATE : 11/08/2023 CONSULTANT CLIENT PROJECT PANEL BUILDER TITLE

PAGE: 6 / 08
SAFETY ELECTRICAL SPLASH PAD CONTROL PANEL
0 FOR APPROVAL 11/08/23 RKR DRAWN BY : RKR KM2K -- SWITCHGEAR FED FROM SMDB-FP
1 REV-1 04/09/23 RKR CHECKED BY: TPP INTERCONTINENTAL HOTEL MANUFACTURING LLC.
MAIN CONTRACTOR SUB CONTRACTOR P.O.BOX-3494,DUBAI. REFERENCE
2 PROJECT No: P23-** FUJAIRAH LANDSCAPEING TEL-04-8867002.
3 FILE NAME: P23-** -- -- FAX-04-8867003.
CONTROL DIAGRAM
1st ANGLE PROJECTION
4 SCALE: ALL DIM. ARE IN MM
SCALE:- N.T.S
www.safetyelectricalgroup.com
This document and all information contained herein, is the property of, and embodies confidential and proprietary information of Safety Electrical Group and may not be reproduced, modified or redistributed without the prior written consent of Safety Electrical Group.
UV SYSTEM CHEMICAL DOSING SYSTEM
FROM PAGE NO.5/8

31

41

41

41
4KR1 4KR3 4KR1 4KR3

32

42

42

42
34

44

44

44
162 164
11

11

11

11
OFF

OFF
ON

ON

LOW LEVEL
2

2
5KR1 5KR2 X3-5 6KR1 X3-7 7KR1

TO FIELD

DRY RUN
TO FIELD
5S1-1 5S1-2
12

12

12

12
14

14

14

14
4

4
X3-6 X3-8

160 161 166 167 168 169 170 171

163 165
A1

A1

A1

A1

A1

A1
X1

X1
X1

X1

X1

X1
G H16 R H17 5KM1 5KR1 5KM2 5KR2 G H18 R H19 6KR1 Y H20 7KR1 Y H21
X2

X2
X2

X2

X2

X2
A2

A2

A2

A2

A2

A2
RUN STOP MAIN RUN MAIN RUN RUN STOP LOW LEVEL LOW LEVEL DRY RUN DRY RUN
IND IND CONTACTOR RELAY CONTACTOR RELAY IND IND RELAY IND RELAY IND
21

21

5KR1 5KR2
24

24

227 228 229 230 PE

X3-1 X3-2 X3-3 X3-4 X3-9

RUN STATUS RUN STATUS


SHIELDED
CABLE

NO. REVISION DATE : BY DATE : 11/08/2023 CONSULTANT CLIENT PROJECT PANEL BUILDER TITLE

PAGE: 7 / 08
SAFETY ELECTRICAL
0 FOR APPROVAL 11/08/23 RKR DRAWN BY : RKR KM2K -- SWITCHGEAR SPLASH PAD CONTROL PANEL
1 REV-1 04/09/23 RKR CHECKED BY: TPP INTERCONTINENTAL HOTEL MANUFACTURING LLC. FED FROM SMDB-FP

MAIN CONTRACTOR SUB CONTRACTOR P.O.BOX-3494,DUBAI. REFERENCE


2 PROJECT No: P23-** FUJAIRAH LANDSCAPEING TEL-04-8867002.
3 FILE NAME: P23-** -- -- FAX-04-8867003.
CONTROL DIAGRAM
1st ANGLE PROJECTION
4 SCALE: ALL DIM. ARE IN MM
SCALE:- N.T.S
www.safetyelectricalgroup.com
This document and all information contained herein, is the property of, and embodies confidential and proprietary information of Safety Electrical Group and may not be reproduced, modified or redistributed without the prior written consent of Safety Electrical Group.
11/08/2023 CONSULTANT CLIENT PROJECT PANEL BUILDER TITLE

PAGE: 8 / 08
NO. REVISION DATE : BY DATE :
SAFETY ELECTRICAL SPLASH PAD CONTROL PANEL
0 FOR APPROVAL 11/08/23 RKR DRAWN BY : RKR KM2K -- SWITCHGEAR FED FROM SMDB-FP
1 REV-1 04/09/23 RKR CHECKED BY: TPP INTERCONTINENTAL HOTEL MANUFACTURING LLC.
MAIN CONTRACTOR SUB CONTRACTOR P.O.BOX-3494,DUBAI. REFERENCE
2 PROJECT No: P23-** FUJAIRAH LANDSCAPEING TEL-04-8867002.
3 FILE NAME: P23-** -- -- FAX-04-8867003.
BILL OF MATERIAL
1st ANGLE PROJECTION
4 SCALE: ALL DIM. ARE IN MM
SCALE:- N.T.S
www.safetyelectricalgroup.com
This document and all information contained herein, is the property of, and embodies confidential and proprietary information of Safety Electrical Group and may not be reproduced, modified or redistributed without the prior written consent of Safety Electrical Group.
PROJECT : INTERCONTINENTAL FUJAIRAH Location: Splash pad pump room
DB NO : Splash pad control panel @ Building Basement level
LOAD DISTRIBUTION SCHEDULE
FED FROM : SMDB-FP
Connected Load (kW): 20.0
RATING OF INCOMER: 40A
CONNECTED LOADS/ POINTS LOAD PER CIRCUIT KW
RATING OF MCB RTG ECC WIRE SIZE SMART
RATING OF ELCB SL # CKT # CCT WIRE SIZE mm2 Types Of Lightings & Power 16A COMMANDO 15A WATTS Remarks
INCOMER Amps mm2 LTG ISO POLE JB W/H H/D R Y B
SOCKET S/O
SOCKET

40A,4P, 100mA, 32A TP 4Cx16 Sqmm XLPE/SWA/PVC +


1 RYB1 Heat Cool Pump 10000 3333 3333 3333
ELCB-1 MCCB 1C X 16 Sq.mm PVC Y/G Cable

40A,4P, 30mA, 2x3Cx6 Sqmm XLPE/SWA/PVC + Star Delta Starter +


2 RYB2 32A TP Circulation Pump 4600 1533 1533 1533
ELCB-2 2x1C X 6 Sq.mm PVC Y/G Cable Timer 1

3 R3 20 3Cx4 Sqmm Cu/XLPE/SWA/PVC Filter Pump 0.5 hp , 1 ph (Duty) 373 373

40A,4P, 30mA,
4 Y3 20 3Cx4 Sqmm Cu/XLPE/SWA/PVC Filter Pump 0.5 hp , 1 ph (Standby) 373 373
40A TPN ISOLATOR

ELCB-3
DOL Starter +
5 B3 20 Spare 300
Timer 2

6 R4 10 3Cx4 Sqmm Cu/XLPE/SWA/PVC UV System 200 200

40A,4P, 100mA,
7 Y4 10 3Cx4 Sqmm Cu/XLPE/SWA/PVC Dosing System 200 200
ELCB-4

8 B4 10 Spare 200

9 R5 10 Spare 404

40A,4P, 100mA,
10 Y5 10 Spare 450
ELCB-5

11 B5 10 Spare 500

100A,4P, 100mA,
12 RYB6 32A TP Spare - 800 800 800
ELCB-6

Total load per phase (W) 6644 6690 6667


Grand Total Load (W) 20000

INCOMING CABLE SIZE: 4CX16 mm2 XLPE/SWA/PVC + 1Cx16 mm2 Y/G PVC Cable LTG= Lighting, EM.Light= Emergency Light, FB= Floor Box
W/H= Water Heater, ISO= Isolator, H/D = Hand Dryer
GENERAL:

LOCATION : INDOOR OUTDOOR

MOUNTING : FLOOR WALL

CABLE ENTRY & ACCESS INCOMING OUTGOING

TOP ENTRY

BOTTOM ENTRY

FRONT ACCESS
GLAND PLATE
ELECTRICAL DATA :
800mm 800mm
RATED SERVICE VOLTAGE : 400V 415V 230V D-200mm

RATED CURRENT : 40A 63A 100A


E

BREAKING CAPACITY : 6 kA 10 kA QM,100A


R Y B
N SEC1 SEC2 SEC3 SEC4 SEC5 SEC6
N
N

RATED FREQUENCY : 50Hz


SEC1 SEC2 SEC3 SEC4 SEC5 SEC6 N

EARTHING SYSTEM : TNS TT TNC

CUBICLE DATA :

1000mm
SEC7 SEC8 SEC9 SEC10 SEC11 SEC12 N N

CUBICLE SYSTEM : SHEET STEEL

ENCLOSURE SIZE : 1000 (H) x 800 (W) x 200 (D)mm


N N N SEC7 SEC8 SEC9 SEC10 SEC11 SEC12 N

DEGREE OF PROTECTION : IP-54

FORM OF CONSTRUCTION : FORM-2


N N N SEC13 SEC14 SEC15 SEC13 SEC14 SEC15 N

ACCESS CLOSING : KEY LOCK


PAINT FINISH : RAL 7035 RAL 7032
ENCLOSURE THICKNES : 1.5 mm 1.2 mm

MAIN BUSBARS FRONT VIEW INTERNAL VIEW


GLAND PLATE
COPPER COMB BUSBAR STANDARD NEUTRAL LINK & EARTH LINK

200mm
CONSTRUCTION DATA TOP/BOTTOM

EXTERNAL CABLE CONNECTION DIRECT ON DEVICE TERMINAL


GLAND DETAILS
WIRING IDENTIFICATION RED,YELLOW,BLUE,BLACK,YELLOW/GREEN

EQUIPMENT MOUNTING FIXED INCOMING & OUTGOINGS

LABELS ARE WHITE BACKGROUND PVC ADHESIVE


BLACK LETTERS IN ENGLISH.

NO. REVISION DATE : BY DATE : 11/08/2023 CONSULTANT CLIENT PROJECT PANEL BUILDER TITLE

PAGE: 1 / 02
SAFETY ELECTRICAL
0 FOR APPROVAL 11/08/23 RKR DRAWN BY : RKR KM2K -- SWITCHGEAR DB-BB-S
1 REV-1 04/09/23 RKR CHECKED BY: TPP INTERCONTINENTAL HOTEL MANUFACTURING LLC. FED FROM SMDB-BB-S

MAIN CONTRACTOR SUB CONTRACTOR P.O.BOX-3494,DUBAI. REFERENCE


2 PROJECT No: P23-** FUJAIRAH LANDSCAPEING TEL-04-8867002.
3 FILE NAME: P23-** -- -- FAX-04-8867003.
GENERAL SPECIFICATION
1st ANGLE PROJECTION
4 SCALE: ALL DIM. ARE IN MM
SCALE:- N.T.S
www.safetyelectricalgroup.com
This document and all information contained herein, is the property of, and embodies confidential and proprietary information of Safety Electrical Group and may not be reproduced, modified or redistributed without the prior written consent of Safety Electrical Group.
PROJECT : INTERCONTINENTAL FUJAIRAH
Location: Beach Bar Electrical Room
DB NO : DB-BB-S
LOAD DISTRIBUTION SCHEDULE
FED FROM : SMDB-BB-S
Connected Load (kW): 26.4
RATING OF INCOMER: 63A
CONNECTED LOADS / POINTS LOAD PER CIRCUIT KW
RATING OF MCB RTG ECC WIRE SIZE
RATING OF ELCB SL # CKT # CCT WIRE SIZE mm2 Types Of Lightings & Power 16A 15A WATTS Remarks
INCOMER Amps mm2 LTG SIG SP SW 13A SO 13A DSO TP ISO H/D R Y B
SO S/O

1 R1 10 3Cx2.5 Sqmm Cu/XLPE/SWA/PVC LED Strip Light TYPE-02 14.2Mtrs 9.6W/m 138

40A,4P, 100mA,
2 Y1 10 3Cx2.5 Sqmm Cu/XLPE/SWA/PVC LED Strip Light TYPE-03 13.8Mtrs 9.6W/m 132
ELCB-1

3 B1 10 3Cx2.5 Sqmm Cu/XLPE/SWA/PVC LED Strip Light TYPE-04 13.3Mtrs 9.6W/m 128

4 R2 10 3Cx2.5 Sqmm Cu/XLPE/SWA/PVC LED Strip Light TYPE-05 7.5Mtrs 9.6W/m 72

40A,4P, 100mA,
5 Y2 10 3Cx2.5 Sqmm Cu/XLPE/SWA/PVC LED Inground Light (Type-03) 4 8 32
ELCB-2

6 B2 10 3Cx2.5 Sqmm Cu/XLPE/SWA/PVC LED Strip Light (Roof) LED TYPE-03 38.5 Mtrs 9.6W/m 370

7 R3 10 3Cx2.5 Sqmm Cu/XLPE/SWA/PVC LED Strip Light (Roof) LED TYPE-04 26.2 Mtrs 9.6W/m 252

40A,4P, 100mA,
8 Y3 10 3Cx2.5 Sqmm Cu/XLPE/SWA/PVC LED Strip Light (Roof) LED TYPE-04 52.6 Mtrs 9.6W/m 505
ELCB-3

9 B3 10 3Cx2.5 Sqmm Cu/XLPE/SWA/PVC Inground Light (Type RUL) 2 32.5 65

10 R4 10 3Cx2.5 Sqmm Cu/XLPE/SWA/PVC Umbrella Light (Type 6) 6 27 162

40A,4P, 100mA,
11 Y4 10 3Cx2.5 Sqmm Cu/XLPE/SWA/PVC Bollard Light (Type BOL) 2 13.8 28
ELCB-4

12 B4 20 3Cx4 Sqmm Cu/XLPE/SWA/PVC Power outlet for Signage 1 200 200

13 R5 20 4 4 Beach Bar Insect Killer (BB-RR-005) 1 200 200

40A,4P, 30mA,
14 Y5 20 4 4 Undercounter Bottle Cooler (BB-RR-007) 1 200 200
ELCB-5

15 B5 20 4 4 Undercounter Ice Cube Machine (BB-RR-008) 1 500 500

16 R6 20 4 4 Bar Blender (BB-BR-010) 1 1500 1500

40A,4P, 30mA,
17 Y6 20 4 4 Mug Froster (BB-BR-012) 1 650 650
ELCB-6

18 B6 32 4 4 Coffee Machine (BB-RR-014) 1 2800 2800

19 R7 20 4 4 Milk Cooler (BB-BR-014A) 1 800 800

40A,4P, 30mA,
20 Y7 20 4 4 Undercounter Ice Cube Machine (BB-RR-018) 1 500 500
63A TPN ISOLATOR

ELCB-7

21 B7 20 4 4 Cock Tail Station (BB-BR-019) 1 500 500

22 R8 20 4 4 Undercounter Bottle Cooler 2 doors (BB-RR-020) 1 350 350

40A,4P, 30mA,
23 Y8 32 4 4 Bar Blender (BB-BR-026) 1 1500 1500
ELCB-8

24 B8 20 4 4 Cock Tail Station (BB-BR-009) 1 500 500

100A,4P, 30mA, 4CX4 mm2 XLPE/SWA/PVC +


25 RYB9 32A TP Undercounter Glass Washer (BB-BR-025) 1 7600 2533 2533 2533
ELCB-9 1Cx4 mm2 Y/G PVC Cable

100A,4P, 30mA,
26 RYB10 32A TP Spare 1000 800 800
ELCB-10

27 R11 20 4 4 Beer Refrigeneration system (BB-RR-017) 1 500 500

40A,4P, 30mA,
28 Y11 20 4 4 POS Machine (BB-RR-003) 2 200 400
ELCB-11

29 B11 20 4 4 KOT Prinetr (BB-RR-004) 1 200 200

30 R12 20 4 4 Spare Socket 1 400 400

40A,4P, 30mA,
31 Y12 20 4 4 Spare Socket 1 400 400
ELCB-12

32 B12 20 4 4 Spare Socket 1 400 400

33 R13 20 4 4 Beer Tap (BB-BR-015) 1 500 500

40A,4P, 30mA,
34 Y13 20 Spare 100
ELCB-13

35 B13 20 Spare 100

36 R14 10 3Cx2.5 Sqmm Cu/XLPE/SWA/PVC Surface Mounted UP Light for Palm Tree 5 27 135

40A,4P, 30mA,
37 Y14 10 3Cx2.5 Sqmm Cu/XLPE/SWA/PVC Palm Tree String Light 5 100
ELCB-14

38 B14 10 Spare 100

39 R15 10 Spare 200

40A,4P, 100mA,
40 Y15 10 Spare 482
ELCB-15

41 B15 10 Spare 100

Total load per phase (W) 8742 8362 9296


Grand Total Load (W) 26400
2
INCOMING CABLE SIZE: 4CX16 mm XLPE/SWA/PVC + 1Cx16 mm
2
Y/G PVC Cable LTG= Lighting, EM.Light= Emergency Light, FB= Floor Box
W/H= Water Heater, ISO= Isolator, H/D = Hand Dryer
NO. REVISION DATE : BY DATE : 11/08/2023 CONSULTANT CLIENT PROJECT PANEL BUILDER TITLE

PAGE: 2 / 02
SAFETY ELECTRICAL
0 FOR APPROVAL 11/08/23 RKR DRAWN BY : RKR KM2K -- SWITCHGEAR DB-BB-S
1 REV-1 04/09/23 RKR CHECKED BY: TPP INTERCONTINENTAL HOTEL MANUFACTURING LLC. FED FROM SMDB-BB-S

MAIN CONTRACTOR SUB CONTRACTOR P.O.BOX-3494,DUBAI. REFERENCE


2 PROJECT No: P23-** FUJAIRAH LANDSCAPEING TEL-04-8867002.
3 FILE NAME: P23-** -- -- FAX-04-8867003.
BILL OF MATERIAL
1st ANGLE PROJECTION
4 SCALE: ALL DIM. ARE IN MM
SCALE:- N.T.S
www.safetyelectricalgroup.com
This document and all information contained herein, is the property of, and embodies confidential and proprietary information of Safety Electrical Group and may not be reproduced, modified or redistributed without the prior written consent of Safety Electrical Group.
GENERAL:

LOCATION : INDOOR OUTDOOR

MOUNTING : FLOOR WALL

CABLE ENTRY & ACCESS INCOMING OUTGOING

TOP ENTRY

BOTTOM ENTRY

FRONT ACCESS

ELECTRICAL DATA :
RATED SERVICE VOLTAGE : 400V 415V 230V

RATED CURRENT : 40A 63A 100A

BREAKING CAPACITY : 6 kA 10 kA
450mm 450mm 115mm
RATED FREQUENCY : 50Hz

EARTHING SYSTEM : TNS TT TNC SEC1 SEC2

OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF

CUBICLE DATA : 3POLE COMBUSBAR 3POLE COMBUSBAR

CUBICLE SYSTEM : SESM- 5ROW 16MODULE SURAFACE TYPE MAIN SEC1 SEC2 SEC3

OFF OFF OFF OFF

ENCLOSURE SIZE : 910 (H) x 450 (W) x 115 (D)mm


ISOL

DEGREE OF PROTECTION : IP-41

910mm
SEC4 SEC5 SEC3

OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF

FORM OF CONSTRUCTION : FORM-1 E


3POLE COMBUSBAR

ACCESS CLOSING : SLIDING LOCK SEC4 SEC5 SEC6 SEC7

PAINT FINISH : RAL 7035 RAL 7032


ENCLOSURE THICKNES : 1.2 mm 1.5 mm SEC6 SEC7

OFF OFF OFF OFF OFF OFF

MAIN BUSBARS

COPPER COMB BUSBAR STANDARD NEUTRAL LINK & EARTH LINK


FRONT VIEW INTERNAL VIEW SIDE VIEW

CONSTRUCTION DATA

EXTERNAL CABLE CONNECTION DIRECT ON DEVICE TERMINAL

WIRING IDENTIFICATION RED,YELLOW,BLUE,BLACK,YELLOW/GREEN

EQUIPMENT MOUNTING FIXED INCOMING & OUTGOINGS

LABELS ARE WHITE BACKGROUND PVC ADHESIVE


BLACK LETTERS IN ENGLISH.

NO. REVISION DATE : BY DATE : 11/08/2023 CONSULTANT CLIENT PROJECT PANEL BUILDER TITLE

PAGE: 1 / 02
SAFETY ELECTRICAL
0 FOR APPROVAL 11/08/23 RKR DRAWN BY : RKR KM2K -- SWITCHGEAR DB-WS-S
1 REV-1 04/09/23 RKR CHECKED BY: TPP INTERCONTINENTAL HOTEL MANUFACTURING LLC. FED FROM SMDB-BB-S

MAIN CONTRACTOR SUB CONTRACTOR P.O.BOX-3494,DUBAI. REFERENCE


2 PROJECT No: P23-** FUJAIRAH LANDSCAPEING TEL-04-8867002.
3 FILE NAME: P23-** -- -- FAX-04-8867003.
GENERAL SPECIFICATION
1st ANGLE PROJECTION
4 SCALE: ALL DIM. ARE IN MM
SCALE:- N.T.S
www.safetyelectricalgroup.com
This document and all information contained herein, is the property of, and embodies confidential and proprietary information of Safety Electrical Group and may not be reproduced, modified or redistributed without the prior written consent of Safety Electrical Group.
PROJECT : INTERCONTINENTAL FUJAIRAH
Location: Washroom (ROW Type)
DB NO : Beach Washroom Panel (DB-WS-S)
LOAD DISTRIBUTION SCHEDULE
FED FROM : SMDB-BB-S
Connected Load (kW): 10.5
RATING OF INCOMER: 40A
CONNECTED LOADS/ POINTS LOAD PER CIRCUIT KW
RATING OF MCB RTG ECC WIRE SIZE
RATING OF ELCB SL # CKT # CCT WIRE SIZE mm2 Types Of Lightings & Power WATTS Remarks
INCOMER Amps mm2 LTG EXH DP SW 13A SO SP ISO HD FO H/D FCU R Y B

1 R1 10 3Cx2.5 Sqmm Cu/XLPE/SWA/PVC Female Washroom Exhaust (EXF-WS-01) 1 1 250 250

2 Y1 10 Spare 100

3 B1 10 3Cx2.5 Sqmm Cu/XLPE/SWA/PVC Female Washroom Exhaust (EXF-WS-02) 1 1 1 25 / 250 275


40A,4P, 100mA,
ELCB-1
4 R2 10 4 4 Male Washroom FCU unit 1 160 160

5 Y2 10 Spare 100

6 B2 10 4 4 Female Washroom FCU unit 1 160 160

Female Washroom
7 R3 10 2.5 2.5 19 12 228
Type 1- Recessed Down Light
Male Washroom
8 Y3 10 2.5 2.5 16 12 192
Type 1- Recessed Down Light
Male Washroom
9 B3 10 2.5 2.5 1 12 12
40A,4P, 100mA, Type 1- Recessed Down Light
ELCB-2
10 R4 10 2.5 2.5 Female Washroom Lights (Future Provision) 3 25 75

11 Y4 10 2.5 2.5 Female Washroom Lights (Future Provision) 4 25 100

12 B4 10 2.5 2.5 Male & Female Washroom LED Strip Light 5 Mtrs 9.6W/m 48

13 R5 20 4 4 Male Washroom Water Sensor 1 50 50


40A TPN ISOLATOR

14 Y5 20 4 4 Male Urinals Water Sensor 1 50 50

15 B5 20 4 4 Female Washroom Water Sensor 1 50 50


40A,4P, 30mA,
ELCB-3
16 R6 20 4 4 Male Washroom Handryer 1 500 500

17 Y6 20 Spare 100

18 B6 20 4 4 Female Washroom Handryer 1 500 500

19 R7 20 4 4 Male Washroom General Socket 4 200 800

40A,4P, 30mA,
20 Y7 20 Spare 100
ELCB-4

21 B7 20 4 4 Female Washroom General Socket 4 200 800

22 R8 20 Spare 100

40A,4P, 30mA, UVR Relay +


23 Y8 32 3Cx4 Sqmm Cu/XLPE/SWA/PVC Male Washroom Oudoor Unit (DSOU-WS-01) 1 2020 2020
ELCB-5 Timet
UVR Relay +
24 B8 32 3Cx4 Sqmm Cu/XLPE/SWA/PVC Male Washroom Oudoor Unit (DSOU-WS-02) 1 2020 2020
Timet

29 R11 20 3Cx2.5 Sqmm Cu/XLPE/SWA/PVC Recessed Step Lights (Type RSL) 4 4 16

40A,4P, 100mA,
30 Y11 20 Spare 100
ELCB-6

31 B11 20 Spare 100

100A,4P, 30mA,
32 RYB12 32A TP Spare 500 500 500
ELCB-7

Total load per phase (W) 2679 3362 4465


Grand Total Load (W) 10506

INCOMING CABLE SIZE: 4CX10 mm2 XLPE/SWA/PVC + 1Cx10 mm2 Y/G PVC Cable
NO. REVISION DATE : BY DATE : 11/08/2023 CONSULTANT CLIENT PROJECT PANEL BUILDER TITLE

PAGE: 2 / 02
SAFETY ELECTRICAL
0 FOR APPROVAL 11/08/23 RKR DRAWN BY : RKR KM2K -- SWITCHGEAR DB-WS-S
1 REV-1 04/09/23 RKR CHECKED BY: TPP INTERCONTINENTAL HOTEL MANUFACTURING LLC. FED FROM SMDB-BB-S

MAIN CONTRACTOR SUB CONTRACTOR P.O.BOX-3494,DUBAI. REFERENCE


2 PROJECT No: P23-** FUJAIRAH LANDSCAPEING TEL-04-8867002.
3 FILE NAME: P23-** -- -- FAX-04-8867003.
BILL OF MATERIAL
1st ANGLE PROJECTION
4 SCALE: ALL DIM. ARE IN MM
SCALE:- N.T.S
www.safetyelectricalgroup.com
This document and all information contained herein, is the property of, and embodies confidential and proprietary information of Safety Electrical Group and may not be reproduced, modified or redistributed without the prior written consent of Safety Electrical Group.
XII. PRODUCT CATALOGUE
SACE Tmax XT. New low voltage moulded-case circuit-breakers up to 250 A
Contact us

ABB SACE The data and illustrations are not binding. We reserve

1SDC210033D0201 – 03/2010 – 7.000 – CAL


the right to modify the contents of this document on the
A division of ABB S.p.A. basis of technical development of the product, without
L.V. Breakers prior notice.

Via Baioni, 35 © Copyright 2010 ABB.


24123 Bergamo All rights reserved.

Phone: +39 035.395.111


Fax: +39 035.395.306-433

www.abb.com

Technical catalogue - Preliminary

SACE Tmax XT
New low voltage moulded-case
circuit-breakers up to 250 A
Identification of the SACE Tmax XT 50˚C
Circuit-breakers

The characteristics of the circuit-breaker are given on the rating nameplate on the front of the cir-
cuit-breaker, and on the side rating plate.

Front label 1 7 4 3

7 10
6
5
14

11
1
9
15

13

8 12

1 2

7 9
7
3
6
5 4
14
15
6 13
10

1 Name of the circuit-breaker and performance level (*)


2 In: rated current of the circuit-breaker (*)
3 Uimp: rated impulse withstand voltage (*)
4 Ui: insulation voltage (*)
5 Ics rated short-circuit duty breaking capacity (*)
6 Icu: rated ultimate short-circuit breaking capacity (*)
7 Ue: rated service voltage (*)
8 Symbol of isolation behaviour (*)
9 Reference Standard IEC 60947-2 (*)
10 Serial number
11 Anti-forgery logo
12 Test pushbutton
13 CE marking
14 Utilisation Category
15 Reference Standard NEMA-AB1
(*)
In compliance with the IEC 60947-2 Standard

1
Circuit-breakers for power distribution 50˚C
Thermomagnetic trip units

TMD (XT1 - XT3)


Main characteristics:
■ protections:
– against overload (L): adjustable protection threshold from 0.7...1xIn, with inverse long-time trip curve;
– against instantaneous short-circuits (I): fixed 10xIn protection threshold, with instantaneous trip curve;
■ 100% neutral protection in four-pole circuit-breakers. 50% neutral protection is only available for In≥125A;

TMD/TMA (XT2)
Main characteristics:
■ protections:
– against overload (L): adjustable protection threshold from 0.7...1xIn, with inverse long time trip curve;
– against instantaneous short-circuit (I):
- fixed protection threshold for In≤32A,
- adjustable threshold beteewn 8…10xIn for 40A,
- adjustable threshold beteewn 6…10xIn for 50A,
- adjustable threshold beteewn 5…10xIn for In≥63A;
■ 100% neutral protection in four-pole circuit-breakers. 50% neutral protection is only available for In≥125A;

XT1
TMD
Breaking capacity C C,N C,N C,N C,N C,N C,N C,N C,N
In [A] 25 32 40 50 63 80 100 125 150
Neutral [A] - 100% 25 32 40 50 63 80 100 125 150
I1 = 0.7…1xIn Neutral [A] - 50% – – – – – – – 80 100
I3 [A] 450 450 450 500 630 800 1000 1250 1500
Neutral [A] - 100% 450 450 450 500 630 800 1000 1250 1500
I 3 = 10xIn Neutral [A] - 50% – – – – – – – 800 1000

XT2
TMD/TMA
In [A] 16 20 25 32 40 50 63 80 100 125
Neutral [A] - 100% 16 20 25 32 40 50 63 80 100 125
I1 = 0.7…1xIn Neutral [A] - 50% – – – – – – – – – 80
TMD 300 300 300 320
TMA 300… 300… 300… 400… 500… 625…
400 500 630 800 1000 1250
Neutral [A] - 100% 300 300 300 320 300… 300… 300… 400… 500… 625…
400 500 630 800 1000 1250
Neutral [A] - 50% – – – – – – – – – 400…
800

(1)
Available only as complete circuit-breaker

XT3
TMD
Breaking capacity N,S N,S C,N,S C,N,S C,N,S C,N,S C,N,S
In [A] 63 80 100 125 160 200 250
Neutral [A] - 100% 63 80 100 125 160 200 250
I1 = 0.7…1xIn Neutral [A] - 50% – – – 80 100 125 160
I3 [A] 630 800 1000 1250 1600 2000 2500
Neutral [A] - 100% 630 800 1000 1250 1600 2000 2500
I 3 = 10xIn Neutral [A] - 50% – – – 800 1000 1250 1600

3
Ordering codes 50˚C
Power distribution circuit-breakers

XT1C 160 TMD (50°C) - Fixed (F) - Front terminals (F)


Icu (415V) = 25kA 1SDA...R1
Thermomagnetic trip unit - TMD In I3 3 poles 4 poles
N=100%
XT1C 160 TMD 25-450 F F 50°C 25 450 070083 070092
XT1C 160 TMD 32-450 F F 50°C 32 450 070084 070093
XT1C 160 TMD 40-450 F F 50°C 40 450 070085 070094
XT1C 160 TMD 50-500 F F 50°C 50 500 070086 070095
XT1C 160 TMD 63-630 F F 50°C 63 630 070087 070096
XT1C 160 TMD 80-800 F F 50°C 80 800 070088 070097
XT1C 160 TMD 100-1000 F F 50°C 100 1000 070089 070098
XT1C 160 TMD 125-1250 F F 50°C 125 1250 070090 070099
XT1C 160 TMD 150-1500 F F 50°C 150 1500 070091 070100

XT1N 160 TMD (50°C) - Fixed (F) - Front terminals (F)


Icu (415V) = 36kA 1SDA...R1
Thermomagnetic trip unit - TMD In I3 3 poles 4 poles
N=100%
XT1N 160 TMD 32-450 F F 50°C 32 450 070101 070109
XT1N 160 TMD 40-450 F F 50°C 40 450 070102 070110
XT1N 160 TMD 50-500 F F 50°C 50 500 070103 070111
XT1N 160 TMD 63-630 F F 50°C 63 630 070104 070112
XT1N 160 TMD 80-800 F F 50°C 80 800 070105 070113
XT1N 160 TMD 100-1000 F F 50°C 100 1000 070106 070114
XT1N 160 TMD 125-1250 F F 50°C 125 1250 070107 070115
XT1N 160 TMD 150-1500 F F 50°C 150 1500 070108 070116

XT2N 160 TMD/TMA (50°C) - Fixed (F) - Front terminals (F)


Icu (415V) = 36kA 1SDA...R1
Thermomagnetic trip unit - TMD/TMA In I3 3 poles 4 poles
N=100%
XT2N 160 TMD 16-300 F F 50°C 16 300 070117 070127
XT2N 160 TMD 20-300 F F 50°C 20 300 070118 070128
XT2N 160 TMD 25-300 F F 50°C 25 300 070119 070129
XT2N 160 TMD 32-320 F F 50°C 32 320 070120 070130
XT2N 160 TMA 40-400 F F 50°C 40 400 070121 070131
XT2N 160 TMA 50-500 F F 50°C 50 500 070122 070132
XT2N 160 TMA 63-630 F F 50°C 63 630 070123 070133
XT2N 160 TMA 80-800 F F 50°C 80 800 070124 070134
XT2N 160 TMA 100-1000 F F 50°C 100 1000 070125 070135
XT2N 160 TMA 125-1250 F F 50°C 125 1250 070126 070136

6
Ordering codes 50˚C
Power distribution circuit-breakers

XT2S 160 TMD/TMA (50°C) - Fixed (F) - Front terminals (F)


Icu (415V) = 50kA 1SDA...R1
Thermomagnetic trip unit - TMD/TMA In I3 3 poles 4 poles
N=100%
XT2S 160 TMD 16-300 F F 50°C 16 300 070137 070147
XT2S 160 TMD 20-300 F F 50°C 20 300 070138 070148
XT2S 160 TMD 25-300 F F 50°C 25 300 070139 070149
XT2S 160 TMD 32-320 F F 50°C 32 320 070140 070150
XT2S 160 TMA 40-400 F F 50°C 40 400 070141 070151
XT2S 160 TMA 50-500 F F 50°C 50 500 070142 070152
XT2S 160 TMA 63-630 F F 50°C 63 630 070143 070153
XT2S 160 TMA 80-800 F F 50°C 80 800 070144 070154
XT2S 160 TMA 100-1000 F F 50°C 100 1000 070145 070155
XT2S 160 TMA 125-1250 F F 50°C 125 1250 070146 070156

XT3C 250 TMD (50°C) - Fixed (F) - Front terminals (F)


Icu (415V) = 25kA 1SDA...R1
Thermomagnetic trip unit - TMD In I3 3 poles 4 poles
N=100%
XT3C 250 TMD 100-1000 3p F F 50°C 100 1000 081814
XT3C 250 TMD 125-1250 3p F F 50°C 125 1250 081815
XT3C 250 TMD 160-1600 3p F F 50°C 160 1600 081816
XT3C 250 TMD 200-2000 3p F F 50°C 200 2000 081817
XT3C 250 TMD 250-2500 3p F F 50°C 250 2500 081818

XT3N 250 TMD (50°C) - Fixed (F) - Front terminals (F)


Icu (415V) = 36kA 1SDA...R1
Thermomagnetic trip unit - TMD In I3 3 poles 4 poles
N=100%
XT3N 250 TMD 63-630 F F 50°C 63 630 070157 070164
XT3N 250 TMD 80-800 F F 50°C 80 800 070158 070165
XT3N 250 TMD 100-1000 F F 50°C 100 1000 070159 070166
XT3N 250 TMD 125-1250 F F 50°C 125 1250 070160 070167
XT3N 250 TMD 160-1600 F F 50°C 160 1600 070161 070168
XT3N 250 TMD 200-2000 F F 50°C 200 2000 070162 070169
XT3N 250 TMD 250-2500 F F 50°C 250 2500 070163 070170

XT3S 250 TMD (50°C) - Fixed (F) - Front terminals (F)


Icu (415V) = 50kA 1SDA...R1
Thermomagnetic trip unit - TMD In I3 3 poles 4 poles
N=100%
XT3S 250 TMD 63-630 F F 50°C 63 630 070171 070178
XT3S 250 TMD 80-800 F F 50°C 80 800 070172 070179
XT3S 250 TMD 100-1000 F F 50°C 100 1000 070173 070180
XT3S 250 TMD 125-1250 F F 50°C 125 1250 070174 070181
XT3S 250 TMD 160-1600 F F 50°C 160 1600 070175 070182
XT3S 250 TMD 200-2000 F F 50°C 200 2000 070176 070183
XT3S 250 TMD 250-2500 F F 50°C 250 2500 070177 070184

7
Breakers and Switches

Switches
Switch-disconnectors
OT, OETL, OTDC and OTM
Switch-disconnectors 16...3150 Amperes
High performance, compact solution

Manual operation

IEC OTDC16F OT16F OT63F OT100F OT160EV OT315E


OTDC25F OT25F OT80F OT125F OT200E OT400E
OTDC32F OT40F OT250E
UL OT16F OT63F OT30F OT200U
OT25F OT80F OT60F
OT40F OT100F

Switch size 16 25 32 16 25 40 63 80 30 60 100 125 160 200 250 200 315 400
IEC lth [A] 25 32 45 25 32 40 63 80 115 125 160 200 250 315 400
le /AC22A, 415V [A] 16 25 40 63 80 100 125 160 200 250 315 400
le /AC23A, 415V [A] 16 20 23 45 75 80 90 160 200 250 315 400
l e /DC21, 660V [A] 16 25 32 16 25 25 160 200 250
le /DC21, 1000V [A] 16 25 32 160 200 250 315 400
le /DC21, 1200V [A] 16 25 32
UL Ampere rating [A] 20 30 40 60 80 30 60 100 200

Motor operation

IEC OTM160E OTM315E


OTM200E OTM400E
OTM250E

Switch size [A] 160 200 250 315 400

4 Product overview | Switch-disconnectors


Ordering information
Front operated switch-disconnectors

OT16...40F3
S04049
Switch-disconnectors, base and DIN-rail mounting
Including protected terminal clamps IP20, except OT125FL_ types.
The type and the ordering numbers are for one piece.

Rated
operat.
currents
OT63...80F3 Cable AC22A/
S04050
No. Ith cross AC23A Delivery Weight/
of (open) section 400V batch unit
poles [A] [mm 2] [A/A] Type Order number [pcs] [kg]
Shaft and handle need to be ordered separately
3 25 0.75...10 16/16 OT16F3 1SCA104811R1001 10 0.11
4 25 0.75...10 16/16 OT16F4N2 1SCA104829R1001 10 0.14
3 32 0.75...10 25/20 OT25F3 1SCA104857R1001 10 0.11
4 32 0.75...10 25/20 OT25F4N2 1SCA104886R1001 10 0.14
OT100...125F3 3 40 0.75...10 40/23 OT40F3 1SCA104902R1001 10 0.11
S04051
4 40 0.75...10 40/23 OT40F4N2 1SCA104932R1001 10 0.14
3 63 1.5...35 63/45 OT63F3 1SCA105332R1001 10 0.27
4 63 1.5...35 63/45 OT63F4N2 1SCA105365R1001 10 0.30
3 80 1.5...35 80/75 OT80F3 1SCA105798R1001 10 0.27
4 80 1.5...35 80/75 OT80F4N2 1SCA105413R1001 10 0.30
3 115 10...70 100/80 OT100F3 1SCA105004R1001 10 0.36
4 115 10...70 100/80 OT100F4N2 1SCA105018R1001 10 0.50
3 125 10...70 125/90 OT125F3 1SCA105033R1001 10 0.36
4 125 10...70 125/90 OT125F4N2 1SCA105051R1001 10 0.50
OT125FLB3 3 125 125/90 OT125FL3 1) 1SCA112372R1001 1 0.43
S07089
3 125 125/90 OT125FLA3 2) 1SCA114832R1001 1 0.43
3 125 125/90 OT125FLB3 3) 1SCA114833R1001 1 0.43
1)
Extended terminals on both sides of the switch
2)
Extended terminals on top side only
3)
Extended terminals on bottom side only

Switch-disconnectors | Ordering information 19


Ordering information
Front operated switch-disconnectors

OT160EV...250E03P
S02101A
Switch-disconnectors, with pistol handle, base mounting
Including a black ON-OFF plastic handle and shaft as standard. The handle is IP65 protected,
padlockable in the OFF-position and with door interlock in the ON-position. The shaft is
adjustable for a range of installation depths.

Rated
operat.
OT200...250E04P currents
S02102A
AC22A/
Number I th AC23A Units/ Weight/
of (open) 400V type unit
poles [A] [A/A] Type Order number [pcs] [kg]
3 200 200/160 OT160EV03P 1SCA120514R1001 1 1.6
4 200 200/160 OT160EV04P 1SCA120521R1001 1 2.0
3 200 200/160 OT160EV12P 1SCA120529R1001 1 1.6
OT315...400E03P 4 200 200/160 OT160EV22P 1SCA120537R1001 1 2.0
S02103A
3 200 200/200 OT200E03P 1SCA022712R0800 1 1.6
4 200 200/200 OT200E04P 1SCA022713R4930 1 2.0
3 200 200/200 OT200E12P 1SCA022721R3990 1 1.6
4 200 200/200 OT200E22P 1SCA022721R4020 1 2.0
3 250 250/250 OT250E03P 1SCA022710R0100 1 1.6
4 250 250/250 OT250E04P 1SCA022710R0520 1 2.0
3 250 250/250 OT250E12P 1SCA022721R4110 1 1.6
4 250 250/250 OT250E22P 1SCA022721R4290 1 2.0
OT315...400E04P 3 315 315/315 OT315E03P 1SCA022718R8510 1 3.1
S02104A
4 315 315/315 OT315E04P 1SCA022719R1730 1 3.7
3 315 315/315 OT315E12P 1SCA022727R4190 1 3.1
4 315 315/315 OT315E22P 1SCA022727R4270 1 3.7
3 400 400/400 OT400E03P 1SCA022718R8780 1 3.1
4 400 400/400 OT400E04P 1SCA022719R1810 1 3.7
3 400 400/400 OT400E12P 1SCA022727R5750 1 3.1
4 400 400/400 OT400E22P 1SCA022727R5830 1 3.7
3 630 630/630 OT630E03P 1SCA022718R8940 1 6.3
OT630...800E03P 3+N 1) 630 630/630 OT630E03N3P 1SCA022779R4860 1 6.7
S02105A
4 630 630/630 OT630E04P 1SCA022719R2030 1 7.5
3 630 630/630 OT630E12P 1SCA022753R4790 1 6.3
4 630 630/630 OT630E22P 1SCA022753R4870 1 7.5
3 800 800/800 OT800E03P 1SCA022718R9410 1 6.3
3+N 1) 800 800/800 OT800E03N3P 1SCA022779R4780 1 6.7
4 800 800/800 OT800E04P 1SCA022719R2110 1 7.5
3 800 800/800 OT800E12P 1SCA022753R5170 1 6.3
4 800 800/800 OT800E22P 1SCA022753R5250 1 7.5
1)
Include a detachable neutral link integrated into the mechanism.
OT630...800E04P
S02106A
Shafts and handles included as standard
Suitable for switches Included shaft Included handle Included terminal bolts
OT160EV…250_P OXP6X210 OHB65J6 M8x25
OT315…400_P OXP12X185 OHB95J12 M10x30
OT630…800_P OXP12X185 OHB125J12 M12x40

22 Ordering information | Switch-disconnectors


Command and signalling
SHD 200 switch disconnector

Electrical data
Standards IEC/EN 60947-3
Poles 1P, 2P, 3P, 4P
Rated current I e 16 A, 25 A, 32 A, 40 A, 50 A, 63 A
2CDC051002S0012

Utilization category AC-22A, DC-21A


Rated voltage U e 1P: 240 V AC, 60 V DC
2P: 415 V AC, 125 V DC
3…4P: 415 V AC
SHD 201 Insulation voltage Ui 440 V AC
Max. power frequency recovery voltage U max 1P: 252 V AC, 63 V DC
2P: 436 V AC, 131 V DC
3…4P: 436 V AC
Min. operating voltage U Bmin. 12 V AC
Rated frequency f 50/60 Hz, DC
Suitable for isolation Yes
Rated conditional short-circuit current 10 kA in series with NH 00 ≤ 63 A gG
Overvoltage category III
Pollution degree 3
Rated impulse withstand voltage U imp. (1.2/50 μs) 4 kV (test voltage 6.2 kV at sea level; 5 kV at 2,000 m)
Dielectric test voltage 2 kV (50/60 Hz, 1 min.) 6
Mechanical data
Housing Insulation group II, RAL 7035
Toggle Insulation group II, red, sealable
Contact position indication Marking on toggle, I ON / 0 OFF
Protection degree acc. to EN 60529 IP20 / IP40 in enclosure with cover
Electrical endurance Ie < 32 A: 20,000 ops. (AC), 1,500 ops. (DC)
I e ≥ 32 A: 10,000 ops. (AC), 1,500 ops. (DC)
Mechanical endurance 20,000 ops.
Shock resistance acc. to IEC/EN 60068-2-27 25g, 2 shocks, 13 ms
Vibration resistance acc. to IEC/EN 60068-2-6 5g, 20 cycles at 5…150…5 Hz with load 0.8 I n
Environmental conditions (damp heat cyclic) 28 cycles with 55 °C/90-96% and 25 °C/95-100% [°C/RH]
acc. to IEC/EN 60068-2-30
Ambient temperature -25 … +55 °C
Storage temperature -40 … +70 °C
Installation
Terminal Cage terminal
Safety wire guard No
Two terminal openings for conductor and busbar No
Cross-section of conductors 25 mm2
Torque 2.0 Nm
Screwdriver No. 2 Pozidriv
Mounting On DIN rail 35 mm acc. to EN 60715 by fast clip
Mounting position Optional
Removal without disassembling of the busbar No
Supply Optional
Dimensions and weight
Mounting dimensions acc. to DIN 43880 Mounting dimension 1
Pole dimensions (H x D x W) 85 x 69 x 17.5 mm
Pole weight Approx. 75 g
Combination with auxiliary elements
Auxiliary contact No
Signal/auxiliary contact No
Shunt trip No
Undervoltage release No
Motor operating device No
Padlock Yes
Approvals
CE and RoHS conform
Approvals: VDE
Where to find more:
Worldwide Marks and Approvals of
MDRCs p.11/96

System pro M compact ® | 2CSC 400 002 D0211 6/9


Command and signalling
SHD 200 switch disconnector

SHD 200
Switch disconnector acc. to IEC/EN 60947-3 for panel installation onto DIN rail (35 mm)
Mounting depth: 69 mm
2CDC051002S0012

Mounting width: per pole = 17.5 mm = 1 module


Colour: grey, RAL 7035
Colour of switch lever: red RAL 3000

SHD 201
Special features
– Isolating characteristics acc. to IEC/EN 60947-3
– Protection degree IP20 = finger safe
– 25 mm² cage terminal
– Consistent design to all other System pro M DIN rail products
– Cross wiring with MCBs or RCDs using busbars PS
– Durable device identification due to laser labeling
2CDC051003S0012

– Captive screws
– Locking device as accessory for unauthorized ON/OFF switching
6
– Approved acc. to IEC/EN 60947-3 for international use

SHD 202 Ordering details


Rated current: 16 A
Poles Rated Bbn Order details Price Weight Pack
voltage 4016779 1 piece 1 piece unit

V AC EAN Type code Order code kg pc.


1 240 904308 SHD201/16 2CDD271111R0016 0.075 10
2 415 904360 SHD202/16 2CDD272111R0016 0.150 5
2CDC051004S0012

3 415 904421 SHD203/16 2CDD273111R0016 0.225 1


4 415 904483 SHD204/16 2CDD274111R0016 0.300 1

SHD 203 Rated current: 25 A


Poles Rated Bbn Order details Price Weight Pack
voltage 4016779 1 piece 1 piece unit

V AC EAN Type code Order code kg pc.


1 240 904315 SHD201/25 2CDD271111R0025 0.075 10
2 415 904377 SHD202/25 2CDD272111R0025 0.150 5
3 415 904438 SHD203/25 2CDD273111R0025 0.225 1
4 415 ‚904490 SHD204/25 2CDD274111R0025 0.300 1
2CDC051005S0012

Rated current: 32 A
Poles Rated Bbn Order details Price Weight Pack
voltage 4016779 1 piece 1 piece unit
SHD 204
V AC EAN Type code Order code kg pc.
1 240 904322 SHD201/32 2CDD271111R0032 0.075 10
2 415 904384 SHD202/32 2CDD272111R0032 0.150 5
3 415 904445 SHD203/32 2CDD273111R0032 0.225 1
4 415 904506 SHD204/32 2CDD274111R0032 0.300 1

Where to find more:


Worldwide Marks and Approvals of
MDRCs p.11/96

6/10 2CSC 400 002 D0211 | System pro M compact ®


Ordering details
Rated current: 40 A
Poles Rated Bbn Order details Price Weight Pack
voltage 4016779 1 piece 1 piece unit
2CDC051002S0012

V AC EAN Type code Order code kg pc.


1 240 904339 SHD201/40 2CDD271111R0040 0.075 10
2 415 904391 SHD202/40 2CDD272111R0040 0.150 5

SHD 201 3 415 904452 SHD203/40 2CDD273111R0040 0.225 1


4 415 904513 SHD204/40 2CDD274111R0040 0.300 1

Rated current: 50 A
Poles Rated Bbn Order details Price Weight Pack
voltage 4016779 1 piece 1 piece unit

V AC EAN Type code Order code kg pc.


2CDC051003S0012

1 240 904346 SHD201/50 2CDD271111R0050 0.075 10


415 904407 SHD202/50 2CDD272111R0050 0.150 5
2
6
3 415 904469 SHD203/50 2CDD273111R0050 0.225 1
4 415 904520 SHD204/50 2CDD274111R0050 0.300 1
SHD 202

Rated current: 63 A
Poles Rated Bbn Order details Price Weight Pack
voltage 4016779 1 piece 1 piece unit

V AC EAN Type code Order code kg pc.


1 240 904353 SHD201/63 2CDD271111R0063 0.075 10
2 415 904414 SHD202/63 2CDD272111R0063 0.150 5
2CDC051004S0012

3 415 904476 SHD203/63 2CDD273111R0063 0.225 1


4 415 904537 SHD204/63 2CDD274111R0063 0.300 1

SHD 203
2CDC051005S0012

SHD 204

System pro M compact ® | 2CSC 400 002 D0211 6/11


Technical features table for miniature circuit-breakers
SH 200 Series

Standards
Poles
Tripping characteristics
Rated current I n A
Rated frequency f Hz
Rated insulation voltage U i acc. to IEC/EN 60664-1 V
Overvoltage category
Pollution degree
Data acc. to IEC/EN 60898-1
Rated operational voltage U n V
Max. power frequency recovery voltage (U max) V
Min. operating voltage V
Rated short-circuit capacity I cn kA
Energy limiting class (B, C up to 40 A)
Rated impulse withstand voltage U imp. (1.2/50μs) kV
Dielectric test voltage kV
Reference temperature for tripping characteristics °C
Electrical endurance ops.
Mechanical Data
Housing
Toggle
Contact position indication
Protection degree acc. to EN 60529
Mechanical endurance ops.
Shock resistance acc. to IEC/EN 60068-2-27
Vibration resistance acc. to IEC/EN 60068-2-6
Environmental conditions (damp heat cyclic) acc. to IEC/EN 60068-2-30 °C/RH
Ambient temperature °C
Storage temperature °C
Installation
Terminal
Cross-section of conductors (top / bottom) mm 2
Torque Nm
Screwdriver
Mounting
Mounting position
Supply
Dimensions and weight
Mounting dimensions acc. to DIN 43880
Pole dimensions (H x D x W) mm
Pole weight g
Combination with aux. elements
Accessories mountable

* Also fulfilling the requirement acc. to the protection degree IPXXB

2/8 2CSC 400 030 D0202 | Compact Home


2CSC400030F0027

2CSC400030F0015

2CSC400030F0002
2

SH 200 SH 200 L SH 200 T


IEC/EN 60898-1
1P, 2P, 3P, 4P, 1P+N, 3P+N
B, C
6…40 A
50 / 60 Hz
250 V AC (phase to ground) , 440 V AC (phase to phase)
III
2

1P: 230/400 V AC; 1P+N: 230 V AC; 2...4P: 400 V AC; 3P+N: 400 V AC
1P: 253 V AC; 1P+N: 253 V AC; 2...4P: 440 V AC; 3P+N: 440 V AC
12 V AC
6 kA 4.5 kA 3 kA
3
4 kV (test voltage 6.2kV at sea level, 5kV at 2,000m)
2 kV (50 / 60Hz, 1 min.)
B, C: 30°C
In < 32A: 20,000 ops (AC), I n ≥ 32A: 10,000 ops. (AC); 1,000 ops. (DC); 1 cycle (2s - ON, 13s - OFF, I n ≤ 32A), 1 cycle (2s - ON, 28s - OFF, I n > 32A)

Insulation group II, RAL 7035


Insulation group II, black, sealable
Marking on toggle (I ON / 0 OFF)
IP20*, IP40 in enclosure with cover
20,000 ops.
25 g - 3 shocks - 11 ms
5g - 20 cycles at 5…150…5 Hz with load 0.8 I n
28 cycles with 55°C/90-96% and 25°C/95-100%
-25 … +55°C
-40 … +70°C

Cage Terminal
25 mm 2 / 25 mm 2
2.0 Nm
No. 2 Pozidrive
On DIN rail 35 mm acc. to EN 60715 by fast clip
any
optional

Mounting dimension 1
85 x 69 x 17.5 mm
ca. 115 g

No

Compact Home | 2CSC 400 030 D0202 2/9


Ordering Information
MCB SH 200 Series - C characteristic

N. of Rated N° module Bbn Order details Weight Pack


poles current 4016779 1 piece unit

In A [17,5 mm] EAN Type code Order code Price Kg


2CSC400030F0033

2 1 6 1 630573 SH201-C6 2CDS211001R0064 0.125 10


8 1 630597 SH201-C8 2CDS211001R0084 0.125 10
10 1 630603 SH201-C10 2CDS211001R0104 0.125 10
13 1 630627 SH201-C13 2CDS211001R0134 0.125 10
SH201-C
16 1 630641 SH201-C16 2CDS211001R0164 0.125 10
20 1 630665 SH201-C20 2CDS211001R0204 0.125 10
25 1 630689 SH201-C25 2CDS211001R0254 0.125 10
32 1 630702 SH201-C32 2CDS211001R0324 0.125 10
40 1 630726 SH201-C40 2CDS211001R0404 0.125 10
2CSC400030F0034

1+N 6 2 630801 SH201-C6NA 2CDS211103R0064 0.25 5


8 2 630825 SH201-C8NA 2CDS211103R0084 0.25 5
10 2 630832 SH201-C10NA 2CDS211103R0104 0.25 5
13 2 630856 SH201-C13NA 2CDS211103R0134 0.25 5
SH201-C…NA
16 2 630870 SH201-C16NA 2CDS211103R0164 0.25 5
20 2 630894 SH201-C20NA 2CDS211103R0204 0.25 5
25 2 630917 SH201-C25NA 2CDS211103R0254 0.25 5
32 2 630931 SH201-C32NA 2CDS211103R0324 0.25 5
2CSC400030F0035

40 2 630955 SH201-C40NA 2CDS211103R0404 0.25 5


2 6 2 631037 SH202-C6 2CDS212001R0064 0.25 5
8 2 631051 SH202-C8 2CDS212001R0084 0.25 5
10 2 631068 SH202-C10 2CDS212001R0104 0.25 5
SH202-C 13 2 631082 SH202-C13 2CDS212001R0134 0.25 5
16 2 631105 SH202-C16 2CDS212001R0164 0.25 5
20 2 631129 SH202-C20 2CDS212001R0204 0.25 5
25 2 631143 SH202-C25 2CDS212001R0254 0.25 5
32 2 631167 SH202-C32 2CDS212001R0324 0.25 5
2CSC400030F0036

40 2 631181 SH202-C40 2CDS212001R0404 0.25 5


3 6 3 631266 SH203-C6 2CDS213001R0064 0.375 1
8 3 631280 SH203-C8 2CDS213001R0084 0.375 1
10 3 631297 SH203-C10 2CDS213001R0104 0.375 1
SH203-C 13 3 631310 SH203-C13 2CDS213001R0134 0.375 1
16 3 631334 SH203-C16 2CDS213001R0164 0.375 1
20 3 631358 SH203-C20 2CDS213001R0204 0.375 1
25 3 631372 SH203-C25 2CDS213001R0254 0.375 1
32 3 631396 SH203-C32 2CDS213001R0324 0.375 1
40 3 631419 SH203-C40 2CDS213001R0404 0.375 1

2/20 2CSC 400 030 D0202 | Compact Home


Main catalog

Motor protection and control


Manual motor starters, contactors
and overload relays
3-pole contactors Mini contactors Contactors for motor control and

IEC (1) AC-3 Rated operational power θ ≤ 60 °C (2), 400 V kW 4 5.5 4 5.5 7.5 4 5.5 7.5 11 15 18.5
UL/CSA 3-phase motor rating 480 V hp 3 5 5 7.5 10 5 7.5 10 15 20 20

AC / DC Control supply Type — — — — — AF09 AF12 AF16 AF26 AF30 AF38

AC Control supply Type B6 B7 AS09 AS12 AS16 AF09 AF12 AF16 AF26 AF30 AF38

DC Control supply Type BC6 BC7 ASL09 ASL12 ASL16 AF09 AF12 AF16 AF26 AF30 AF38

IEC AC-3 Rated operational current θ ≤ 60 °C (2), 400 V A 9 12 9 12 15.5 9 12 18 26 32 38


AC-1 Rated operational current θ ≤ 40 °C, 690 V A 16 (400 V) 20 (400 V) 22 24 24 25 28 30 45 50 50
UL/CSA General use rating 600 V A 12 (300 V) 16 20 20 20 25 28 30 45 50 50
NEMA NEMA Size — — 00 00 0 00 0 — 1 — —
(1) 1000 V IEC ratings available for AF146 ... AF2650 contactors.
(2) θ ≤ 55 °C for mini contactors and AF400 ... AF2650 contactors.

Main accessories
Auxiliary contact blocks Front mounting CAF6 CA3-10 (1 x N.O.) CA4-10 (1 x N.O.)
CA3-01 (1 x N.C.) CA4-01 (1 x N.C.)
Side mounting CA6 CAL4-11 (1 x N.O. + 1 x N.C.)
Timers Electronic TEF3-ON TEF4-ON
TEF3-OFF TEF4-OFF
Interlocking units (4) Mechanical VM3 VM4

Mechanical / Electrical VEM4


Connection sets For reversing contactors BSM6-30 BER16C-3 BER16-4 BER38-4
Surge suppressors Varistor (AC/DC) RV-BC6 RV5 (24…440 V) Built-in surge protection
RC type (AC) RC5-1 (24…440 V)
Transil diode (DC) RD7 RT5 (12…264 V)

(4) See available reversing contactors VB6, VB7 and VAS09 ... VAS16.

Overload relays
Thermal relays Class 10 T16 (0.10…16 A) T16 (0.10…16 A) TF42 (0.10…38 A)
(Class 10A for TF140, TA200DU)

Electronic relays Class 10E, 20E, 30E E16DU (0.10…18.9 A) EF19 (0.10…19 A) EF19 (0.10…19 A)
EF45 (9…45 A)

Manual motor starters


Thermal / magnetic protection MS116 (0.10…32 A) MS116 (0.10...32 A) MS450
Class 10 Ics up to 50 kA for class 10A lcs up to 50 kA for class 10 A (28...50 A)
lcs up to 50 kA
MS132 (0.10…32 A) MS132 (0.10...32 A)
Ics up to 100 kA lcs up to 100 kA
MS497
(22…100 A)
Ics up to 100 kA
Magnetic only types MO132 (0.16...32A) MO132 (0.16...32 A)
Ics up to 100 kA

Accessories For contactor mounting BEA7/132 BEA16-3 BEA16-4 BEA38-4

1/8 | ABB
PRODUCT-DETAILS

AF09-30-10-13
AF09-30-10-13 100-250V50/60HZ-DC
Contactor

General Information
Extended Product Type AF09-30-10-13
Product ID 1SBL137001R1310
EAN 3471523110038
Catalog Description AF09-30-10-13 100-250V50/60HZ-DC Contactor
The AF09-30-10-13 is a 3 pole - 690 V IEC or 600 UL contactor with 1 built-in auxiliary
contact and screw terminals, controlling motors up to 4 kW / 400 V AC (AC-3) or 5 hp /
480 V UL and switching power circuits up to 25 A (AC-1) or 25 A UL general use. Thanks
to the AF technology, the contactor has a wide control voltage range (100-250 V 50/60
Long Description Hz and DC), managing large control voltage variations, reducing panel energy
consumptions and ensuring distinct operations in unstable networks. Furthermore,
surge protection is built-in, offering a compact solution. AF contactors have a block
type design, can be easily extended with add-on auxiliary contact blocks and an
additional wide range of accessories.

Ordering
Minimum Order Quantity 1 piece
Customs Tariff Number 85364900

Popular Downloads
Instructions and 1SBC101027M6801
Manuals
Dimension Diagram DNV_TAE00001AF-4
AF09-30-10-13 2

Dimensions
Product Net Width 45 mm
Product Net Depth / 77 mm
Length
Product Net Height 86 mm
Product Net Weight 0.27 kg

Technical
Number of Main 3
Contacts NO
Number of Main 0
Contacts NC
Number of Auxiliary 1
Contacts NO
Number of Auxiliary 0
Contacts NC
Standards IEC 60947-1 / 60947-4-1 and EN 60947-1 / 60947-4-1, UL 508, CSA C22.2 N°
14
Rated Operational Auxiliary Circuit 690 V
Voltage Main Circuit 690 V
Rated Frequency (f) Auxiliary Circuit 50 / 60 Hz
Main Circuit 50 / 60 Hz
Conventional Free-air acc. to IEC 60947-4-1, Open Contactors q = 40 °C 35 A
Thermal Current (I th ) acc. to IEC 60947-5-1, q = 40 °C 16 A
Rated Operational (690 V) 40 °C 25 A
Current AC-1 (I e ) (690 V) 60 °C 25 A
(690 V) 70 °C 22 A
Rated Operational (415 V) 60 °C 9 A
Current AC-3 (I e ) (440 V) 60 °C 9 A
(500 V) 60 °C 9.5 A
(690 V) 60 °C 7 A
(380 / 400 V) 60 °C 9 A
(220 / 230 / 240 V) 60 °C 9 A
Rated Operational (415 V) 60 °C 9 A
Current AC-3e (I e ) (440 V) 60 °C 9 A
(500 V) 60 °C 9.5 A
(690 V) 60 °C 7 A
(380 / 400 V) 60 °C 9 A
(220 / 230 / 240 V) 60 °C 9 A
Rated Operational Power (400 V) 4 kW
AC-3 (P e ) (415 V) 4 kW
(440 V) 4 kW
(500 V) 5.5 kW
(690 V) 5.5 kW
(380 / 400 V) 4 kW
(220 / 230 / 240 V) 2.2 kW
Rated Operational Power (415 V) 4 kW
AC-3e (P e ) (440 V) 4 kW
(500 V) 5.5 kW
(690 V) 5.5 kW
(380 / 400 V) 4 kW
(220 / 230 / 240 V) 2.2 kW
Rated Operational (500 V) 2 A
Current AC-15 (I e ) (690 V) 2 A
(24 / 127 V) 6 A
(220 / 240 V) 4 A
(400 / 440 V) 3 A
Rated Short-time at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 150 A
Withstand Current Low at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 35 A
Voltage (I cw ) at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 60 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 300 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 80 A
for 0.1 s 140 A
for 1 s 100 A
Maximum Breaking cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 250 A
Capacity cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 106 A
AF09-30-10-13 3

Maximum Electrical (AC-1) 600 cycles per hour


Switching Frequency (AC-15) 1200 cycles per hour
(AC-2 / AC-4) 300 cycles per hour
(AC-3) 1200 cycles per hour
(DC-13) 900 cycles per hour
Rated Operational (24 V) 6 A / 144 W
Current DC-13 (I e ) (48 V) 2.8 A / 134 W
(72 V) 1 A / 72 W
(110 V) 0.55 A / 60 W
(125 V) 0.55 A / 69 W
(220 V) 0.27 A / 60 W
(250 V) 0.27 A / 68 W
(400 V) 0.15 A / 60 W
(500 V) 0.13 A / 65 W
(600 V) 0.1 A / 60 W
Rated Insulation Voltage acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 690 V
(U i ) acc. to UL/CSA 600 V
Rated Impulse 6 kV
Withstand Voltage (U imp
)
Maximum Mechanical 3600 cycles per hour
Switching Frequency
Rated Control Circuit 50 Hz 100 ... 250 V
Voltage (U c ) 60 Hz 100 ... 250 V
DC Operation 100 ... 250 V
Operate Time Between Coil De-energization and NC Contact Closing 13 ... 98 ms
Between Coil De-energization and NO Contact Opening 11 ... 95 ms
Between Coil Energization and NC Contact Opening 38 ... 90 ms
Between Coil Energization and NO Contact Closing 40 ... 95 ms
Mounting on DIN Rail TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
Mounting by Screws (not 2 x M4 screws placed diagonally
supplied)
Connecting Capacity Flexible with Ferrule 1/2x 0.75 ... 6 mm²
Main Circuit Flexible with Insulated Ferrule 1x 0.75 ... 4 mm²
Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm²
Rigid 1/2x 1 ... 6 mm²
Connecting Capacity Flexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Auxiliary Circuit Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm²
Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm²
Rigid 1/2x 1 ... 2.5 mm²
Connecting Capacity Flexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Control Circuit Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm²
Rigid 1/2x 1 ... 2.5 mm²
Wire Stripping Length Auxiliary Circuit 10 mm
Control Circuit 10 mm
Main Circuit 10 mm
Degree of Protection acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP20
Terminal Type Screw Terminals

Technical UL/CSA
NEMA Size 00
Continuous Current 9A
Rating NEMA
Horsepower Rating (115 V AC) Single Phase 1/3 Hp
NEMA (200 V AC) Three Phase 1-1/2 Hp
(230 V AC) Single Phase 1 Hp
(230 V AC) Three Phase 1-1/2 Hp
(460 V AC) Three Phase 2 Hp
(575 V AC) Three Phase 2 Hp
General Use Rating (600 V AC) 25 A
UL/CSA
Horsepower Rating (120 V AC) Single Phase 3/4 hp
UL/CSA (200 ... 208 V AC) Three Phase 2 hp
AF09-30-10-13 4

(220 ... 240 V AC) Three Phase 2 hp


(240 V AC) Single Phase 1-1/2 hp
(440 ... 480 V AC) Three Phase 5 hp
(550 ... 600 V AC) Three Phase 7-1/2 hp
Tightening Torque Auxiliary Circuit 11 in·lb
UL/CSA Control Circuit 11 in·lb
Main Circuit 13 in·lb

Environmental
Ambient Air Close to Contactor Fitted with Thermal O/L Relay -25 ... 60 °C
Temperature Close to Contactor without Thermal O/L Relay -40 ... 70 °C
Close to Contactor for Storage -60 ... +80 °C
Climatic Withstand Category B according to IEC 60947-1 Annex Q
Maximum Operating Without Derating 3000 m
Altitude Permissible
Resistance to Vibrations 5 ... 300 Hz 4 g closed position / 2 g open position
acc. to IEC 60068-2-6
Resistance to Shock acc. Closed, Shock Direction: B1 25 g
to IEC 60068-2-27 Open, Shock Direction: B1 5 g
Shock Direction: A 30 g
Shock Direction: B2 15 g
Shock Direction: C1 25 g
Shock Direction: C2 25 g
RoHS Status Following EU Directive 2011/65/EU

Certificates and Declarations (Document Number)


ABS Certificate ABS_20-2060694-PDA
BV Certificate BV_2634H24898B0
CB Certificate CB_SE-96551M1
CCC Certificate CCC_2010010304445624
CQC Certificate CQC2010010304445624
CQC2020010304298240
cUL Certificate UL_20180227_E312527_7_1
Declaration of 2020980304001253
Conformity - CCC 2020980304001082
Declaration of 1SBD250000U1000
Conformity - CE
Declaration of 1SBD250031U1000
Conformity - UKCA
EAC Certificate EAC_RU_FRME77B03447
Environmental 1SBD250147E1000
Information 1SBC100222M0201
GL Certificate DNV-GL_TAE00001AF-3
GOST Certificate GOST_POCCFR.ME77.B07175.pdf
Instructions and 1SBC101027M6801
Manuals
KC Certificate KC_HW02016-15004C
LR Certificate LRS_1300087E1
RINA Certificate RINA_ELE240318XG
RMRS Certificate RMRS_1802705280
RoHS Information 1SBD250000U1000
UL Certificate UL_20140305-E312527_7_1
UL Listing Card E312527

Container Information
Package Level 1 Units box 1 piece
Package Level 1 Width 87 mm
Package Level 1 Depth / 79 mm

D ATA S H E E T

Thermal overload relay TF42

Thermal overload relays are


economic electromechanical
protection devices for the main
circuit. They are used mainly to
protect motors against overload and
phase failures. Starter combinations
are setup together with contactors.

Description Order data


• Overload protection – trip class 10 TF42 screw terminal for AF contactors

• Phase loss sensitivity Setting range Type Order code Weight


• Temperature compensation
Pkg
from -25…+60 °C (1 pce)
• Adjustable current setting for overload A kg
protection 0.10...0.13 TF42-0.13 1SAZ721201R1005 0.130
• Automatic or manual reset selectable 0.13...0.17 TF42-0.17 1SAZ721201R1008 0.130
• Suitable for three- and single-phase 0.17...0.23 TF42-0.23 1SAZ721201R1009 0.130

application 0.23...0.31 TF42-0.31 1SAZ721201R1013 0.130


0.31...0.41 TF42-0.41 1SAZ721201R1014 0.130
• Trip-free mechanism
0.41...0.55 TF42-0.55 1SAZ721201R1017 0.130
• Status indication
0.55...0.74 TF42-0.74 1SAZ721201R1021 0.130
• STOP and TEST function 0.74...1.00 TF42-1.0 1SAZ721201R1023 0.130
• Direct mounting onto block contactors 1.00...1.30 TF42-1.3 1SAZ721201R1025 0.130
• Sealable operating elements 1.30...1.70 TF42-1.7 1SAZ721201R1028 0.130
1.70...2.30 TF42-2.3 1SAZ721201R1031 0.130
2.30...3.10 TF42-3.1 1SAZ721201R1033 0.130
3.10...4.20 TF42-4.2 1SAZ721201R1035 0.130
Approvals Marks 4.20...5.70 TF42-5.7 1SAZ721201R1038 0.130
5.70...7.60 TF42-7.6 1SAZ721201R1040 0.130
A K E D P a 7.60...10.0 TF42-10 1SAZ721201R1043 0.130
cULus CB CCC GOST-R ABS RINA DNV Lloyd's CE 10.0...13.0 TF42-13 1SAZ721201R1045 0.130
UL 508 scheme Register
13.0...16.0 TF42-16 1SAZ721201R1047 0.130
16.0...20.0 TF42-20 1SAZ721201R1049 0.145
20.0...24.0 TF42-24 1SAZ721201R1051 0.145
24.0...29.0 TF42-29 1SAZ721201R1052 0.145
29.0...35.0 TF42-35 1SAZ721201R1053 0.145
35.0...38.0/40.0 TF42-38 1SAZ721201R1055 0.145
Suitable for mounting on: AF09 … AF38.
2 ABB DATA SHEET THERMAL OVERLOAD REL AY TF42

Functional description
2 1. Terminals 1L1, 3L2, 5L3
2. Current setting range
3 Adjustable current setting for overload protection
3. Sealable operating elements
4
4. Status indication
5
5. RESET button
6 Automatic or manual reset selectable
7 6. Signaling contacts 97-98
7. Terminals 2T1, 4T2, 6T3
8
8. Tripping contacts 95-96
9 9. STOP button

Application / internal function


The thermal overload relays are three pole relays with The overload relays have a setting scale in Amperes,
bimetal tripping elements (1 per pole). The motor cur- which allows the direct adjusting of the relay without
rent flows through the bimetal tripping elements and any additional calculation. In compliance with inter-
heats them directly and indirectly. In case of an over- national and national standards, the setting current
load (over current), the bimetal elements become is the rated current of the motor and not the tripping
bent as a result of the heating. This leads to a release current (no tripping at 1.05 x I, tripping at 1.2 x I; I =
of the relay and a change of the contacts switching setting current). The relays are constructed in way
position (95-96 / 97-98). The contact 95-96 is used to that they protect themselves in the event of an over-
control the load contactor. load. The overload relay has to be protected against
short-circuit. The appropriate short-circuit protective
devices are shown in the table.

Operation mode Wiring diagram


1~ 3~

A
RESET 95 97
M

TEST
2T1 4T2 6T3 STOP 96 98

Contact 95-96 Contact 97-98 Status indication Comment


Trip state open closed
RESET state closed open ON
TEST manual reset mode open closed
TEST auto reset mode open closed while TEST is operated
STOP while device is in trip state open closed STOP button has no function
STOP while device is in RESET state open open while STOP button is pressed
PRODUCT-DETAILS

TE5S-24
TE5S-24 Electronic Timer

General Information
Extended Product Type TE5S-24
Product ID 1SBN020010R1001
EAN 3471522121653
Catalog Description TE5S-24 Electronic Timer
Long Description TE5S-24 Electronic Timer

Technical
Product Name Electronic Timer
Suitable For AX06
AX09
AX12
AX18
AX25
AX32
AX40
AX50
AX65
AX80
AX95
AX115
AX150
AX185
AX205
Rated Operational Main Circuit 240 V
Voltage
Rated Insulation Voltage acc. to IEC 60947-5-1 and VDE 0110 (Gr. C) 440 V
(U i )
TE5S-24 2

Rated Control Supply 24 V AC/DC


Voltage (U s )
Rated Control Circuit 50 Hz / 60 Hz 24 V DC
Voltage (U c )
Rated Operational (24 / 127 V) 5 A
Current AC-15 (I e ) (220 / 240 V) 4 A
Rated Frequency (f) Supply Circuit 50 / 60 Hz
Short-Circuit Protective gG Type Fuses 10 A
Devices
Number of Main 0
Contacts NC
Number of Auxiliary 1
Contacts NC
Number of Auxiliary 1
Contacts NO
Mounted Auxiliary 1 NO, 1 NC
Contacts
Coil Consumption Average Holding Value 50 Hz 1.5 V·A
Average Holding Value 60 Hz 1.5 V·A
Terminal Type Screw Terminals

Environmental
Degree of Protection acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP40
Resistance to Shock acc. Half-sine Pulse for 11 ms, Shock Direction: A 20 m/s²
to IEC 60068-2-27 Half-sine Pulse for 11 ms, Shock Direction: B 15 m/s²
Half-sine Pulse for 11 ms, Shock Direction: C 20 m/s²
RoHS Status Following EU Directive 2011/65/EU
Environmental 1SBD250053E1000
Information

Dimensions
Product Net Width 23 mm
Product Net Height 85 mm
Product Net Depth / 75 mm
Length
Product Net Weight 0.08 kg

Container Information
Package Level 1 Units box 1 piece
Package Level 1 Width 23 mm
Package Level 1 Height 85 mm
Package Level 1 Depth / 75 mm
Length
Package Level 1 Gross 0.08 kg
Weight
Package Level 1 EAN 3471522121653

Ordering
Minimum Order Quantity 1 piece
Customs Tariff Number 85364190
E-Number (Finland) 3709228
Country of Origin Austria (AT)
Selling Unit of Measure piece
TE5S-24 3

Certificates and Declarations (Document Number)


Declaration of 1SBD250815U1000
Conformity - CE
Environmental 1SBD250053E1000
Information
RINA Certificate RINA_ELE172319XG001
RoHS Information 1SBD250815U1000

Popular Downloads
Data Sheet, Technical 1SBC100122C0202_Ch04
Information

Classifications
ETIM 6 EC002498 - Accessories for low-voltage switch technology
ETIM 7 EC002498 - Accessories for low-voltage switch technology
ETIM 8 EC002498 - Accessories/spare parts for low-voltage switch technology
WEEE Category 5. Small Equipment (No External Dimension More Than 50 cm)
WEEE B2C / B2B Business To Business
CN8 8536 41 90
UNSPSC 39121500
Object Classification K
Code

Categories

Low Voltage Products and Systems → Control Products → Contactors → Block Contactors Accessories
CONTROL EQUIPMENT
ELECTROMECHANICAL TIME SWITCHES WITH TAPPETS 1 - 2 - 4 DIN

0171 0021 - 0022 - 0024 0135 - 0136


CODE DESCRIPTION PACKAGE

1IO 0171 Daily time switch with tappets and charge reserve - 1 DIN 10

1 potential-free NO contact ON / OFF minimum 15’


1IO 0021 Daily time switch with tappets without charge reserve - 2 DIN 10

1 potential-free changeover contact ON / OFF minimum 30’


1IO 0022 Daily time switch with tappets and charge reserve - 2 DIN 30
1 potential-free changeover contact ON / OFF minimum 30’
1IO 0024 Weekly time switch with tappets and charge reserve - 2 DIN 10
1 potential-free changeover contact ON / OFF minimum 210’ (approx. 3.5 hours)

1IO 0135 Daily time switch, two circuits with charge reserve - 4 DIN 10

2 potential-free changeover contacts ON / OFF daily minimum 30’


minimum weekly 30’
1IO 0136 Weekly and daily time switch with charge reserve - 4 DIN 10

2 potential-free changeover contacts ON / OFF daily minimum 30’


minimum weekly 210’ (approx. 3.5 hours)
DISPLAY LEGEND AND KEY FUNCTIONS TECHNICAL SPECIFICATIONS
Power supply voltage 230V c.a. 50 - 60Hz
Contact rated data 16(2) A / 250V c.a.
48 programming tappets: Max program number (ON-OFF) 48
- Down cycle ON
- Up cycle OFF ON - OFF minimum connection time 30 minutes (daily) 15’ (item 0171)
approx. 3.5 hours (weekly)
Displays mechanical tappets ring
index of minutes / hours
Max commutable power 3500 VA (for individual contact)
protecting cover Max cross-section of wires to terminals 2.5 mm2
Protection degree (IP) IP 20
IP 30 (with cover)
fixed ON selector switch / timer IP 40 (on the rear of the switchboard)
Type of output terminals with captive screw
Insulation class II
Charge reserve approx 150 hours max
(max 100 hours mod. 0171)
Type of reserve NiCd rechargeable battery
Time tolerance + - 1 sec/day
Operating temperature limits -10°C +50°C
Storing temperature -10°C +50°C
Type of installation DIN guide / wall-mounted / on the
rear of the switchboard
Case thermoplastic - grey RAL 7035
Type of use civil / tertiary / industrial
Note: All items can be installed on the rear Controls mechanical tappets ring selector switch:
of the switchboard by means of optional fixed ON / timer position
accessories (KTMP2 or KTMP4) Clock setting accuracy mechanical with reference index
Programming mechanical key ring (blocks 30’/ 210’)
Dimensions (AxPxH) 1DIN 17.5 x 60 x 128
Dimensions (AxPxH) 2DIN 35 x 60 x 116
Dimensions (AxPxH) 4DIN 70 x 60 x 116

54
Compact range

The compact range is designed to be our most efficient solution when it comes to
assembly and cost, suitable for the most demanding environments. It can also be
combined with the modular range to cover the needs of additional flexibility.
General construction Operators
• ”All-in-one” design • Pushbuttons (illuminated & non-illuminated)
• Same front as modular range • Emergency stops (twist, pull & key release)
• 42 mm built in depth • Machine stops (twist, pull & key release)
• Up to 2 electrical contacts • Selector switches (2 & 3 position)
• Metal or black plastic look • Mushrooms

Product features Pilot lights


• Suitable in the toughest environments IP 66, 67 & 69K • Integrated LED (wide range of voltages)
• Wiping action gives high performance with low energies • BA9s base for filament bulb or LED
• UL/NEMA Type 1,3R,4,4X,12,13

3/1 1SFC151005C0201 | ABB Catalog Pilot devices


Pilot lights

Descrip- Rated Anti-inductive Wavelength nm Illumination Type Order code Pkg Weight
tion current Voltage Ix qty (1pce)
1SFC151338V0001

1SFC151339V0001 mA (Vpeak) Kg

Rated voltage 6,3 V DC


l Red 16 2 625 70 CL2-506R 1SFA619403R5061 10 0,0185
CL2-506R CL2-506G l Green 16 2 520 125 CL2-506G 1SFA619403R5062 10 0,0185
l Yellow 16 2 590 75 CL2-506Y 1SFA619403R5063 10 0,0185
l Blue 16 2 470 10 CL2-506L 1SFA619403R5064 10 0,0185
l Clear 16 2 (X=0.31,Y=0.32) 290 CL2-506C 1SFA619403R5068 10 0,0185
3
1SFC151341V0001
1SFC151340V0001

Rated voltage 12 V DC
l Red 16 2 625 110 CL2-501R 1SFA619403R5011 10 0,0185
l Green 16 2.5 520 165 CL2-501G 1SFA619403R5012 10 0,0185
CL2-506Y CL2-506L l Yellow 16 2.5 590 85 CL2-501Y 1SFA619403R5013 10 0,0185
l Blue 16 2.5 470 15 CL2-501L 1SFA619403R5014 10 0,0185
l Clear 16 2.5 (X=0.31,Y=0.32) 320 CL2-501C 1SFA619403R5018 10 0,0185

Rated voltage 24 V AC/DC


1SFC151342V0001

l Red 16 6 625 80 CL2-502R 1SFA619403R5021 10 0,0185


l Green 16 6 520 135 CL2-502G 1SFA619403R5022 10 0,0185
l Yellow 16 6 590 55 CL2-502Y 1SFA619403R5023 10 0,0185
l Blue 16 6 470 10 CL2-502L 1SFA619403R5024 10 0,0185
CL2-506C l Clear 16 6 (X=0.31,Y=0.32) 230 CL2-502C 1SFA619403R5028 10 0,0185

Rated voltage 48-60 V AC/DC


l Red 13-17 7 625 75 CL2-507R 1SFA619403R5071 10 0,0185
l Green 13-17 7 520 140 CL2-507G 1SFA619403R5072 10 0,0185
l Yellow 13-17 7 590 80 CL2-507Y 1SFA619403R5073 10 0,0185
l Blue 13-17 7 470 10 CL2-507L 1SFA619403R5074 10 0,0185
l Clear 13-17 7 (X=0.31,Y=0.32) 260 CL2-507C 1SFA619403R5078 10 0,0185

Rated voltage 110-130 V AC


l Red 15-17 20 625 85 CL2-513R 1SFA619403R5131 10 0,0185
l Green 15-17 20 520 90 CL2-513G 1SFA619403R5132 10 0,0185
l Yellow 15-17 20 590 85 CL2-513Y 1SFA619403R5133 10 0,0185
l Blue 15-17 20 470 10 CL2-513L 1SFA619403R5134 10 0,0185
l Clear 15-17 20 (X=0.31,Y=0.32) 340 CL2-513C 1SFA619403R5138 10 0,0185

Rated voltage 110-130 V DC


l Red 8-9 20 625 55 CL2-515R 1SFA619403R5151 10 0,0185
l Green 8-9 20 520 125 CL2-515G 1SFA619403R5152 10 0,0185
l Yellow 8-9 20 590 50 CL2-515Y 1SFA619403R5153 10 0,0185
l Blue 8-9 20 470 10 CL2-515L 1SFA619403R5154 10 0,0185
l Clear 8-9 20 (X=0.31,Y=0.32) 210 CL2-515C 1SFA619403R5158 10 0,0185

Rated voltage 220 V DC


l Red 6 20 625 40 CL2-520R 1SFA619403R5201 10 0,0185
l Green 6 20 520 90 CL2-520G 1SFA619403R5202 10 0,0185
l Yellow 6 20 590 30 CL2-520Y 1SFA619403R5203 10 0,0185
l Blue 6 20 470 5 CL2-520L 1SFA619403R5204 10 0,0185
l Clear 6 20 (X=0.31,Y=0.32) 120 CL2-520C 1SFA619403R5208 10 0,0185

Rated voltage 230 V AC


l Red 17 30 625 95 CL2-523R 1SFA619403R5231 10 0,0185
l Green 17 35 520 155 CL2-523G 1SFA619403R5232 10 0,0185
l Yellow 17 35 590 70 CL2-523Y 1SFA619403R5233 10 0,0185
l Blue 17 35 470 10 CL2-523L 1SFA619403R5234 10 0,0185
l Clear 17 35 (X=0.31,Y=0.32) 225 CL2-523C 1SFA619403R5238 10 0,0185

Rated voltage 230 V AC with 60 V anti-inductive voltage


l Red 17 60 625 75 CL2-623R 1SFA619403R6231 10 0,0185
l Green 17 80 520 70 CL2-623G 1SFA619403R6232 10 0,0185
l Yellow 17 70 590 50 CL2-623Y 1SFA619403R6233 10 0,0185
l Blue 17 80 470 5 CL2-623L 1SFA619403R6234 10 0,0185
l Clear 17 80 (X=0.31,Y=0.32) 155 CL2-623C 1SFA619403R6238 10 0,0185

Rated voltage 380-415 V AC


l Red 15-17 55 625 85 CL2-542R 1SFA619403R5421 10 0,0185
l Green 15-17 65 520 130 CL2-542G 1SFA619403R5422 10 0,0185
l Yellow 15-17 65 590 60 CL2-542Y 1SFA619403R5423 10 0,0185
l Blue 15-17 65 470 10 CL2-542L 1SFA619403R5424 10 0,0185
l Clear 15-17 65 (X=0.31,Y=0.32) 395 CL2-542C 1SFA619403R5428 10 0,0185

3/5 1SFC151005C0201 | ABB Catalog Pilot devices


ABB PILOT DEVICES – THE COMPLETE OFFERING 53


Compact range
Non-illuminated flush pushbuttons - Momentary

Operator Bezel Contacts Type Order code Pkg Weight


1SFC151176V0001

qty (1 pce)

kg
l Red Black plastic 10 CP1-10R-10 1SFA619100R1011 10 0.018
CP1-10R-10
01 CP1-10R-01 1SFA619100R1041 10 0.018
11 CP1-10R-11 1SFA619100R1071 10 0.022
1SFC151179V0001

03
20 CP1-10R-20 1SFA619100R1021 10 0.022
02 CP1-10R-02 1SFA619100R1051 10 0.022
Chrome metal 10 CP1-30R-10 1SFA619100R3011 10 0.032
01 CP1-30R-01 1SFA619100R3041 10 0.032
CP1-30G-10
11 CP1-30R-11 1SFA619100R3071 10 0.036
20 CP1-30R-20 1SFA619100R3021 10 0.036
1SFC151184V0001

02 CP1-30R-02 1SFA619100R3051 10 0.036


l Green Black plastic 10 CP1-10G-10 1SFA619100R1012 10 0.018
11 CP1-10G-11 1SFA619100R1072 10 0.022
CP1-10Y-10 20 CP1-10G-20 1SFA619100R1022 10 0.022
Chrome metal 10 CP1-30G-10 1SFA619100R3012 10 0.032
1SFC151182V0001

11 CP1-30G-11 1SFA619100R3072 10 0.036


20 CP1-30G-20 1SFA619100R3022 10 0.036
l Yellow Black plastic 10 CP1-10Y-10 1SFA619100R1013 10 0.018
11 CP1-10Y-11 1SFA619100R1073 10 0.022
CP1-10L-10
20 CP1-10Y-20 1SFA619100R1023 10 0.022
Chrome metal 10 CP1-30Y-10 1SFA619100R3013 10 0.032
1SFC151175V0001

11 CP1-30Y-11 1SFA619100R3073 10 0.036


20 CP1-30Y-20 1SFA619100R3023 10 0.036
l Blue Black plastic 10 CP1-10L-10 1SFA619100R1014 10 0.018
CP1-30W-10
11 CP1-10L-11 1SFA619100R1074 10 0.022
20 CP1-10L-20 1SFA619100R1024 10 0.022
Chrome metal 10 CP1-30L-10 1SFA619100R3014 10 0.032
1SFC151180V0001

11 CP1-30L-11 1SFA619100R3074 10 0.036


20 CP1-30L-20 1SFA619100R3024 10 0.036
White Black plastic 10 CP1-10W-10 1SFA619100R1015 10 0.018
CP1-10B-10 11 CP1-10W-11 1SFA619100R1075 10 0.022
20 CP1-10W-20 1SFA619100R1025 10 0.022
Chrome metal 10 CP1-30W-10 1SFA619100R3015 10 0.032
11 CP1-30W-11 1SFA619100R3075 10 0.036
20 CP1-30W-20 1SFA619100R3025 10 0.036
l Black Black plastic 10 CP1-10B-10 1SFA619100R1016 10 0.018
01 CP1-10B-01 1SFA619100R1046 10 0.018
11 CP1-10B-11 1SFA619100R1076 10 0.022
20 CP1-10B-20 1SFA619100R1026 10 0.022
02 CP1-10B-02 1SFA619100R1056 10 0.022
Chrome metal 10 CP1-30B-10 1SFA619100R3016 10 0.032
01 CP1-30B-01 1SFA619100R3046 10 0.032
11 CP1-30B-11 1SFA619100R3076 10 0.036
20 CP1-30B-20 1SFA619100R3026 10 0.036
02 CP1-30B-02 1SFA619100R3056 10 0.036

1.5 0.06" - 6 0.24"


Ø 30 1.18"

Ø 29 1.14"
Ø 20 0.79"

1SFC151035S0201

42 1.65" 13 0.51" 17.5 0.69"

CP1

Dimensions (mm, inches)


26 ABB PILOT DEVICES – THE COMPLETE OFFERING


Modular range
Non-illuminated selector switches - 3-position - Short handle
02

Operating Color Bezel Type Order code Pkg Weight


principle qty (1 pce)
1SFC151317V0001

kg
l Red Black plastic M3SS1-10R 1SFA611210R1001 10 0.015
Chrome plastic M3SS1-20R 1SFA611210R2001 10 0.015
Chrome metal M3SS1-30R 1SFA611210R3001 10 0.024
M3SS1-30R
l Black Black plastic M3SS1-10B 1SFA611210R1006 10 0.015
Chrome plastic M3SS1-20B 1SFA611210R2006 10 0.015
1SFC151130V0001

Chrome metal M3SS1-30B 1SFA611210R3006 10 0.024


l Grey Black plastic M3SS1-10U 1SFA611210R1007 10 0.015
Chrome plastic M3SS1-20U 1SFA611210R2007 10 0.015
Chrome metal M3SS1-30U 1SFA611210R3007 10 0.024
M3SS2-10B
l Red Black plastic M3SS2-10R 1SFA611211R1001 10 0.015
Chrome plastic M3SS2-20R 1SFA611211R2001 10 0.015
Chrome metal M3SS2-30R 1SFA611211R3001 10 0.024
1SFC151129V0001

l Black Black plastic M3SS2-10B 1SFA611211R1006 10 0.015


Chrome plastic M3SS2-20B 1SFA611211R2006 10 0.015
Chrome metal M3SS2-30B 1SFA611211R3006 10 0.024
M3SS3-10U l Grey Black plastic M3SS2-10U 1SFA611211R1007 10 0.015
Chrome plastic M3SS2-20U 1SFA611211R2007 10 0.015
l Red Black plastic M3SS3-10R 1SFA611212R1001 10 0.015
l Black Black plastic M3SS3-10B 1SFA611212R1006 10 0.015
Chrome plastic M3SS3-20B 1SFA611212R2006 10 0.015
Chrome metal M3SS3-30B 1SFA611212R3006 10 0.024
l Grey Black plastic M3SS3-10U 1SFA611212R1007 10 0.015
Chrome plastic M3SS3-20U 1SFA611212R2007 10 0.015
l Red Black plastic M3SS7-10R 1SFA611216R1001 10 0.015
Chrome plastic M3SS7-20R 1SFA611216R2001 10 0.015
l Black Black plastic M3SS7-10B 1SFA611216R1006 10 0.015
Contacts actuated Chrome plastic M3SS7-20B 1SFA611216R2006 10 0.015
Right Chrome metal M3SS7-30B 1SFA611216R3006 10 0.024
l Grey Black plastic M3SS7-10U 1SFA611216R1007 10 0.015
Left
Right block
Left block

Handle position

Not actuated Actuated

1.5 0.06" - 6 0.24"


26.5 1.04"

Ø 29 1.14"
43 1.69"

1SFC151015S0201

30 1.18" 48.5 1.91" 30 1.18"

M3SS

Dimensions (mm, inches)


ABB PILOT DEVICES – THE COMPLETE OFFERING 43


Modular plastic range
Holders and contact blocks for front mounting

02
Description Contacts Type Order code Pkg Weight
qty (1 pce)
1SFC151401V0001

kg

Holders
1SFC151277V0001

MCBH-00 3-position –– MCBH-00 1SFA611605R1100 10 0.006


5-position –– MCBH5-00 1SFA611601R1100 10 0.008

Single contact blocks


For 3 & 5-position holder 10 MCB-10 1SFA611610R1001 10 0.013
MCBH5-00
01 MCB-01 1SFA611610R1010 10 0.013
1SFC151366V0001

Single contact blocks, gold plated contacts


For 3 & 5-position holder 10 MCB-10G 1SFA611610R1101 10 0.013
01 MCB-01G 1SFA611610R1110 10 0.013
1SFC151369V0001

MCB-10
Double contacts blocks
For 3 & 5-position holder 20 MCB-20 1SFA611610R1002 10 0.026
02 MCB-02 1SFA611610R1020 10 0.026
MCB-02
11 MCB-11 1SFA611610R1011 10 0.026
1SFC151283V0001

Micro switch contact blocks


For 3-position holder 10 MCBL-10 1SFA611612R1010 10 0.013
01 MCBL-01 1SFA611612R1001 10 0.013
MCBL-01
Note: micro switch block MCBL-01 are not direct opening and does not fulfill IEC60947-5-5 for emergency stop devices.
Note: 3 micro switch contact blocks max. allowed. If more than 3 contact blocks are needed, micro switch contact block to be
mounted on the second stack.

1- 3- 2- 1- 3- 2-

-3
-1

21 23
22 24
-2

-4

Function Function

1- 3- 2- 1- 3- 2-
Position Position

-1 -3 -2
Combined markings Combined markings
11 31 21 13 33 23
12 32 22 14 34 24
26.5 1.04"

13.4 0.53"
43 1.69"
48.2 1.90"

30 1.18" 50 1.97" 13.4 0.53"

MCBH MCBH5
42.6 1.68"

44 1.73"

38 1.50"

44 1.73"

10 0.39" 28 1.10" 10 0.39" 13 0.51"


IP20 with included
1SFC151032S0201

14.8 0.58" protective cover

MCB MCBL

Dimensions (mm, inches)


Pluggable interface relays and optocouplers
Ordering details - CR-M range

Ordering details – CR-M range with gold contacts and LED


Rated control Outputs Contact Type Order code Price Pkg Weight
supply voltage ratings (1 pc)

qty kg (lb)
2CDC 291 002 F0015

12 V DC CR-M012DC4LG 1SVR405618R4100
24 V DC CR-M024DC4LG 1SVR405618R1100
48 V DC CR-M048DC4LG 1SVR405618R6100
0.033
60 V DC CR-M060DC4LG 1SVR405618R4300 10
(0.073)
110 V DC CR-M110DC4LG 1SVR405618R8100
CR-M 125 V DC CR-M125DC4LG 1SVR405618R8300
4 c/o (SPDT) 250 V / 6 A
220 V DC CR-M220DC4LG 1SVR405618R9100
24 V AC CR-M024AC4LG 1SVR405618R0100
48 V AC CR-M048AC4LG 1SVR405618R5100
0.033
110 V AC CR-M110AC4LG 1SVR405618R7100 10
(0.073)
120 V AC CR-M120AC4LG 1SVR405618R2100
5 230 V AC CR-M230AC4LG 1SVR405618R3100

Ordering details – CR-M range with gold contacts, LED and free-wheeling diode
Rated control Outputs Contact Type Order code Price Pkg Weight
supply voltage ratings (1 pc)

qty kg (lb)

12 V DC CR-M012DC4LDG 1SVR405618R4400
0.033
4 c/o (SPDT) 10
(0.073)
24 V DC CR-M024DC4LDG 1SVR405618R1400

Ordering details - Accessories


Version Connection Type Order code Price Pkg Weight
terminal (1 pc)
2CDC 291 009 F0011

qty kg (lb)
0.055
Logical socket for 2 c/o CR-M2LS 1SVR405651R1100 (0.121)
0.062
Logical socket for 3 c/o screw CR-M3LS 1SVR405651R2100 10
(0.137)
CR-M4SS 0.066
Logical socket for 2/4 c/o CR-M4LS 1SVR405651R3100
(0.146)
0.065
Logical socket for 2 c/o CR-M2LC 1SVR405651R1200 (0.143)
spring 10
Logical socket for 2/4 c/o CR-M4LC 1SVR405651R3200 0.066
(0.146)
0.066
2CDC 291 005 F0007

Standard socket for 2 c/o CR-M2SS 1SVR405651R1000 (0.146)


0.068
Standard socket for 3 c/o screw CR-M3SS 1SVR405651R2000 10
(0.150)
Standard socket for 2/4 c/o CR-M4SS 1SVR405651R3000 0.070
CR-MJ (0.154)
0.040
Standard socket for 2 c/o CR-M2SF 1SVR405651R1300 (0.088)
fork type 10
Standard socket for 2/4 c/o CR-M4SF 1SVR405651R3300 0.048
(0.106)
Plastic holder CR-MH 1SVR405659R1000 0.003
10
(0.007)
Metal holder CR-MH1 1SVR405659R1100 0.0005
10
(0.001)
Jumper bar for sockets with screw 0.029
CR-MJ 1SVR405658R6000 10
connection (0.064)

Marker CR-MM 1SVR405658R1000 0.0005


10
(0.001)
Plug for test button replacement CR-MP 1SVR405658R2000 0.001
100
(0.002)

5/13 ABB | Catalog Electronic relays and controls 2017 | 2CDC 110 004 C0210_05 (G) 04/2018
Pluggable interface relays and optocouplers
Ordering details - CR-M range

Ordering details - CR-M range without LED


Rated control Outputs Contact Type Order code Price Pkg Weight
supply voltage ratings (1 pc)

qty kg (lb)
12 V DC CR-M012DC2 1SVR405611R4000
2CDC 291 002 F0015

24 V DC CR-M024DC2 1SVR405611R1000
48 V DC CR-M048DC2 1SVR405611R6000
60 V DC CR-M060DC2 1SVR405611R4200
110 V DC CR-M110DC2 1SVR405611R8000
125 V DC CR-M125DC2 1SVR405611R8200 0.033
CR-M 2 c/o (SPDT) 250 V, 12 A 10
220 V DC CR-M220DC2 1SVR405611R9000 (0.073)
24 V AC CR-M024AC2 1SVR405611R0000
48 V AC CR-M048AC2 1SVR405611R5000
110 V AC CR-M110AC2 1SVR405611R7000
120 V AC CR-M120AC2 1SVR405611R2000
230 V AC CR-M230AC2 1SVR405611R3000
5 12 V DC CR-M012DC3 1SVR405612R4000
24 V DC CR-M024DC3 1SVR405612R1000
48 V DC CR-M048DC3 1SVR405612R6000
60 V DC CR-M060DC3 1SVR405612R4200
110 V DC CR-M110DC3 1SVR405612R8000
125 V DC CR-M125DC3 1SVR405612R8200
CR-M220DC3 1SVR405612R9000 0.033
220 V DC 3 c/o (SPDT) 250 V, 10 A 10
(0.073)
24 V AC CR-M024AC3 1SVR405612R0000
48 V AC CR-M048AC3 1SVR405612R5000
60 V AC CR-M060AC3 1SVR405612R5200
110 V AC CR-M110AC3 1SVR405612R7000
120 V AC CR-M120AC3 1SVR405612R2000
230 V AC CR-M230AC3 1SVR405612R3000
12 V DC CR-M012DC4 1SVR405613R4000
24 V DC CR-M024DC4 1SVR405613R1000
48 V DC CR-M048DC4 1SVR405613R6000
60 V DC CR-M060DC4 1SVR405613R4200
110 V DC CR-M110DC4 1SVR405613R8000
125 V DC CR-M125DC4 1SVR405613R8200 0.033
4 c/o (SPDT) 250 V, 6 A 10
220 V DC CR-M220DC4 1SVR405613R9000 (0.073)
24 V AC CR-M024AC4 1SVR405613R0000
48 V AC CR-M048AC4 1SVR405613R5000
110 V AC CR-M110AC4 1SVR405613R7000
120 V AC CR-M120AC4 1SVR405613R2000
230 V AC CR-M230AC4 1SVR405613R3000

Further documentation
CR-M range on www.abb.com

5/11 ABB | Catalog Electronic relays and controls 2017 | 2CDC 110 004 C0210_05 (G) 04/2018
t
System Selection tables duc E 90
Pro ilable m
pro M compact Protection devices
®
ava ng fro
ti
E 90 fuse-disconnectors star 2009

E 90 fuse-disconnectors
E 90 series fuse-disconnectors are designed for connecting and disconnecting circuits under load, providing
protection against short circuits and overloads. The case is made of self-extinguishing thermoplastic material
resistant to high temperatures (all materials are UL listed) while the contact clips are in silver plated copper.
E 90 fuse-disconnectors can be sealed or padlocked to ensure operator safety during maintenance.
Versions with blown fuse indicator allow to check whether the fuse is still working correctly or not. For
easy and quick installation E 90 range is fully compatible with connecting bars, terminals and caps of
S 200 MCBs

E 90 fuse-disconnectors for 10.3 x 38 mm fuses (AC-22B) 38 mm Ø 10.3 mm

Poles Rated Modules Order Bbn Price Price Weight Pack


current details 8012542 1 piece group 1 piece unit
In Type code Order code EAN kg pc.
1 32 1 E 91/32 2CSM200923R1801 009238 0.061 6
1 32 1 E 91/32s 2CSM202483R1801 024835 0.062 6
1+N 32 2 E 91N/32 2CSM200893R1801 008934 0.130 3
2 32 2 E 92/32 2CSM200883R1801 008835 0.122 3
3 32 3 E 93/32 2CSM204753R1801 047537 0.183 2
3+N
4
32
32
4
4
E 93N/32
E 94/32
2CSM204733R1801
2CSM204723R1801
047339
047230
0.252
0.244
1
1 5
N 32 - E 9N 2CSM277953R1801 779537 0.069 6
s: version with blown fuse indicator light

E 90 fuse-disconnectors for 8.5 x 31.5 mm fuses (AC-22B) 31.5 mm Ø 8.5 mm

1 20 1 E 91/20 2CSM200983R1801 009832 0.061 6


1 20 1 E 91/20s 2CSM202423R1801 024231 0.062 6
2 20 2 E 92/20 2CSM200953R1801 009535 0.122 3
3 20 3 E 93/20 2CSM200943R1801 009436 0.183 2
N 20 - E 9N 2CSM277953R1801 779537 0.069 6
s: version with blown fuse indicator light

Technical features
Type E 90/20 E 90/32
Fuse 8 x 32 10 x 38
Kind of current AC / DC
Rated frequency [Hz] = / 50-60
Rated current [A] 20 32
Tightening torque [Nm] PZ2 2-2.5
Protection degree IP20
Padlocked (open) ■
Sealed (closed) ■

IEC 60947-3
Rated operational voltage [V] 400 690
Utilization category AC-22B / DC-20B
Power consumption aM [W] 0.9 1.2
per polecnsuption per pole gG [W] 2.5 3.0

IEC 60269-1
Rated voltage AC [V] 400 690
Rated voltage DC [V] 400 690

IEC 60269-2
Fuse system F
Rated voltage AC [V] 400 690
Rated voltage DC [V] 250 440
Minimum rated breaking capacity 50 AC – 25 DC

IEC 60269-3
Fuse system B
Rated voltage AC [V] 400

Overall dimensions ...................... pag. 12/27

ABB 5/15
Power, control and signaling
Latching relays

Characteristics - nominal voltage of the control circuit: 12V, 24V, 110V DC


Permits the remote control of a lighting circuits from several points - conventional thermal current: 16A AC1
using push-buttons in private buildings, small industry buildings and - control and power circuits
administration buildings. Latching relays operate when impulsed by - nominal frequency: 50/60Hz
a signal voltage. The impulse can be provided via a push button or - contact types: 1NO, 2NO, 1NC+1NO, 4NO, 2NO+2NC, 3NO+1NC
switch. The first pulse operates the relay and latches it into its set - 4 types of auxiliaries
(opposite) state, the next operation of the push button returns the - connection capacity:
relay into its reset (original) state. rigid 10 mm2
flexible 6 mm2
Technical data
- nominal voltage of the power circuit: Un = 250/400 V AC Complies with IEC 60 669-1 and IEC 60 669-2-2.
- nominal voltage of the power circuit: 12V, 24V, 48V and 230 V AC

Latching relays

Contact types Symbol Coil V AC Coil V DC Power circuit Width in module Pack qty Cat. ref.
50/60 Hz AC1 17.5 mm

1NO A1 1
230 110 16A-250V 1 12 EPN510

A2 2
48 24 16A-250V 1 1 EPN501
24 12 16A-250V 1 1 EPN513
12 - 16A-250V 1 1 EPN511
EPN510 2NO A1 1 3
230 110 16A-250V 1 1 EPN520

A2 2 4
48 24 16A-250V 1 1 EPN526
24 12 16A-250V 1 1 EPN524
12 - 16A-250V 1 1 EPN521
1NC + 1NO A1 1 3
230 110 16A-250V 1 1 EPN515

A2 2 4
110 48 16A-250V 1 1 EPN516
48 24 16A-250V 1 1 EPN503
24 12 16A-250V 1 1 EPN518
12 - 16A-250V 1 1 EPN519
4NO A1 1 3 5 7
230 110 16A-400V 2 1 EPN540

A2 2 4 6 8
48 24 16A-400V 2 1 EPN548
24 12 16A-400V 2 1 EPN541
2NC + 2NO A1 1 3 5 7
230 110 16A-250V 2 1 EPN525

A2 2 4 6 8
24 12 16A-250V 2 1 EPN528

3NO + 1NC A1 1 3 5 7
230 110 16A-400V 2 1 EPN546

A2 2 4 6 8
EPN540
Electronic latching relay

Contact types Symbol Coil V AC Power circuit Width in module Pack qty Cat. ref.
50/60 Hz AC1 17.5 mm

1NO A1 1
230 16A-250V 1 1 EPS410B

A2 2

Electronic latching relay with delay time

Contact types Symbol Coil V AC Power circuit Width in module Pack qty Cat. ref.
50/60 Hz AC1 17.5 mm

1NO A1 1
230 16A-250V 1 1 EPS450B

EPS450B A2 2

147
Type: LXPRT
Phase Failure, Phase Sequence, Under Voltage plus Time Delay
Terminal
Protection *NEW* 17.5mm DIN rail housing
to IP20 Microprocessor based
True R.M.S. monitoring
Monitors own supply and detects an Under voltage condition on one or more phases
Measures phase to phase voltages
Detects incorrect phase sequence and phase loss
Adjustment for Under voltage trip level
Adjustment for Time delay (from an Under voltage condition)
1 x SPDT relay output 8A
Green LED indication for supply status
Dims: to DIN Red LED indication for relay status
43880
W. 17.5mm

• FUNCTION DIAGRAM • TECHNICAL SPECIFICATION


Supply/monitoring voltage
Monitored
3~ Supply U* (L1, L2, L3): 77 - 143V, 161 - 300V, 280 – 520V1 AC
Phases reversed Frequency range: 48 – 63Hz
L1 Supply variation: ± 30%
L2 Overvoltage category: III (IEC 60664)
L3 Rated impulse withstand voltage: 1
4kV (1.2/50µS) IEC 60664 * Please state
Power consumption (max.): 8VA Supply/monitoring
Hyst. voltage when ordering
Monitoring mode: Under voltage
Fixed Under trip Trip levels: Under [2] Under
Under trip [2] Supply voltage 77 – 143V: 77V 83 – 138V
Output 161 – 300V: 161V 173 – 288V
280 – 520V: 280V 300 – 500V
Hysteresis: ≈ 2% of trip level (factory set)
Td t t tr Td Setting accuracy: ± 3%
Repeat accuracy: ± 0.5% at constant conditions
time delay automatically cancelled as
phase drops below 2nd trip point Immunity from micro power cuts: <50mS
Response time: ≈ 50mS
Time delay (t): 0.2 – 10 sec. (± 5%)
• INSTALLATION AND SETTING Installation work must be carried
Note: actual delay (t) = adjustable delay + response time
out by qualified personnel. Delay from Phase loss (tr): ≈ 150mS (worst case = tr x 2)
• BEFORE INSTALLATION, ISOLATE THE SUPPLY.
Power on delay (Td): ≈ 1 sec. (worst case = Td x 2)
• Connect the unit as required. The Connection Diagram below shows a typical installation, whereby the
supply to a load is being monitored by the Phase monitoring relay. If a fault should occur (i.e. fuse Power on indication: Green LED
Relay status indication: Red LED
blowing), the relay will de-energise and assuming control of the external Contactor, de-energise the
Contactor as well. Ambient temp: -20 to +60°C
Relative humidity: +95% max.
Applying power.
Output (15, 16, 18): SPDT relay
• Set the “<U (volts)” ➍ and “Delay (t)” ➌ adjustment to minimum.
Output rating: AC1 250V 8A (2000VA)
• Apply power and the green “Power supply” ➊ and red “Relay” ➋ LED’s will illuminate, relay energise AC15 250V 5A (no), 3A (nc)
and contacts 15 and 18 will close. Refer to the troubleshooting table if the unit fails to operate correctly. DC1 25V 8A (200W)
Setting the unit (with power applied). Electrical life: ≥ 150,000 ops at rated load
• Accurate setting can be achieved by adjusting the trip level “<U (volts)” until the unit trips (relay de- Dielectric voltage: 2kV AC (rms) IEC 60947-1
Rated impulse withstand voltage: 4kV (1.2/50µS) IEC 60664
energises) then by decreasing the trip level “<U (volts)” until the relay re-energises. Close setting the trip
level ensures the unit will detect a phase loss even with a large percentage of re-generative voltage. Housing: Orange flame retardant UL94
• In order to set the unit as previously described but without causing disruption to the equipment being Weight: 75g
controlled/monitored, set the “Delay (t)” to maximum. It will now be possible to establish the trip point Mounting option: On to 35mm symmetric DIN rail to BS EN 60715
or direct surface mounting via 2 x M3.5 or 4BA screws
when the red “Relay” LED starts to flash. Decrease the trip level setting to stop the LED flashing.
using the black clips provided on the rear of the unit.
(Note: If the time delay is allowed to expire, the output relay will de-energise)
Terminal conductor size ≤ 2 x 2.5mm2 solid or stranded
• If large supply variations are anticipated, the trip level should be set further from the nominal voltage.
• Set the “Delay (t)” as required. (Note that the delay is only effective should the supply drop below the Approvals: Conforms to IEC.
set trip level. However, if during an under voltage condition the supply drops below the 2nd under
voltage trip level, any set time delay is automatically cancelled and the relay de-energises).
Note: If the supply voltage increases above the maximum “<U” trip setting by approx. 10% or more, the
CE, and RoHS Compliant.
relay will de-energise immediately. EMC: Immunity: EN 61000-6-2 (EN 61000-4-3 15V/m
Troubleshooting. 80MHz - 2.7GHz)
The table below shows the status of the unit during a fault condition. Emissions: EN 61000-6-4

Supply fault Green LED Red LED Relay


Phase missing On Off De-energised
Phases reversed (no delay) Flashing Off De-energised
Under Voltage condition (during timing) On Flashing Energised for set delay (t)
Under Voltage condition (after timing) On Off De-energised
Phase below 70% of Un (fixed under trip level [2]) On Off De-energised
• .

• CONNECTION DIAGRAM • SETTING DETAILS • DIMENSIONS


Local Fuse 1. Power supply status 89 (exc. clips)
Supply /
L1 Board
(Green) LED
➊ 67.5
Monitored L2
45
Voltage L3 To Load 2. Relay output / Timing
status (Red) LED
L1 L2
3. “Delay” adjustment
Contactor
4. “<U (volts) Under
L3 voltage trip level
adjustment^ ➌ Insert screwdriver
to release clips
66.5

^Example on the right


15
49.5

R
shows the 280 – 520V
version.
16 18 ➍
29

Withdraw clips
fully when
15 surface mounting

16 18 Phase Monitor ➋ 92 (+/- 1mm)


all dimensions in mm.

Broyce Control Ltd., Pool Street, Wolverhampton, West Midlands WV2 4HN. England LXPRT-2-A.DOCX
Tel: +44 (0) 1902 773746 Fax: +44 (0) 1902 420639 Email: sales@broycecontrol.com Web: www.broycecontrol.com 1811
The Information provided in this literature is believed to be accurate (subject to change without prior notice); however, use of such information shall be entirely at the user’s own risk.
Product datasheet
Specifications

EasyLogic PM2120, Power &


Energy meter, up to the 15th
harmonic, LED display, RS485,
class 1
METSEPM2120

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Range EasyLogic

Product name EasyLogic PM2100

Device short name PM2120

Product or component type Power meter

Complementary
Device application Sub billing
Power monitoring

Power quality analysis total harmonic distortion


up to the 15th harmonic

Type of measurement Apparent power min/max, total


Active and reactive power min/max, total
Current min/max, avg
Voltage min/max, avg
Frequency min/max, avg
Total current harmonic distortion THD (I) per phase
Total voltage harmonic distortion THD (U) per phase
Power factor min/max, avg
Apparent energy total
Active and reactive energy total

Metering type Current I, I1, I2, I3


Peak demand power PM, QM, SM
Active, reactive, apparent energy (signed, four quadrant)
Peak demand currents
Active power P, P1, P2, P3
Calculated neutral current
Voltage U, U21, U32, U13, V, V1, V2, V3
Unbalance current
Reactive power Q, Q1, Q2, Q3
Demand power P, Q, S
Apparent power S, S1, S2, S3

Accuracy class Class 1 active energy conforming to IEC 62053-21


Class 1 reactive energy conforming to IEC 62053-24
Class 5 harmonic distorsion (I THD & U THD)

Measurement accuracy Apparent power +/- 1 %


Active energy +/- 1 %
Reactive energy +/- 1 %
Active power +/- 1 %
Voltage +/- 0.5 %
Power factor +/- 0.01
Current +/- 0.5 %
Frequency +/- 0.05 %

Measurement current 5…6000 mA

Measurement voltage 35…480 V AC 50/60 Hz between phases


20…277 V AC 50/60 Hz between phase and neutral
480…999000 V AC 50/60 Hz with external VT

* Excluding VAT, FCA Jabal Ali & are subject to change – check with your local distributor.

Aug 7, 2023 1
Frequency measurement range 45…65 Hz

[Us] rated supply voltage 44...277 V AC 45...65 Hz +/- 10 %


44...277 V DC +/- 10 %

Network frequency 50 Hz
60 Hz

Ride-through time 100 ms 120 V AC typical


400 ms 230 V AC typical
50 ms 125 V DC typical

[In] rated current 1A


5A

Maximum power consumption in 6 VA at 277 V AC


VA

Maximum power consumption in 3.3 W (power lines (AC))


W 2 W at 277 V (power lines (DC))

Input impedance Current (impedance <= 0.3 mOhm)


Voltage (impedance > 5 MOhm)

Tamperproof of settings Protected by access code

Display type 7 segments LED

Display colour Red

Messages display capacity 3 fields of 4 characters

Display digits 12 digit(s) - 14.2 mm in height

Demand intervals Configurable from 1 to 60 min

Information displayed Demand current (past value)


Demand current (present value)
Demand power (past value)
Demand power (present value)
Voltage
Current
Frequency
Energy consumption
Harmonic distortion
Power factor
Active power
Apparent power
Reactive power
Unbalanced in %

Control type 3 x button

Local signalling Red LED: output signal 1...9999000 pulse/ k_h (kWh, kVAh, kVARh)
Green LED: module operation and integrated communication

Number of inputs 0

Number of outputs 0

Communication port protocol Modbus RTU at 4800 bps, 9600 bps, 19200 bps, 38.4 Kbps even/odd or none - 2 wires, insulation
2500 V

Communication port support Screw terminal block: RS485

Data recording Time stamping


Min/max for 8 parameters

Function available Real time clock

Sampling rate 64 samples/cycle

Cybersecurity Enable/disable communication ports

Communication service Remote monitoring

Product certifications CE conforming to IEC 61010-1


CULus conforming to UL 61010-1
CULus conforming to CSA C22.2 No 61010-1
RCM
EAC
C-Tick

Mounting mode Clip-on

Mounting position Vertical

2
Aug 7, 2023
Mounting support Framework

Provided equipment 1 x installation guide

Measurement category Category III 480 V


Category II 480…600 V

Electrical insulation class Double insulation


Class II

Flame retardance V-0 conforming to UL 94

Connections - terminals Current transformer: screw connection (bottom) 6


Voltage inputs: screw connection (top) 4

Material Polycarbonate

Width 96 mm

Depth 76.09 mm total:


61.64 mm embedded:

Height 96 mm

Product weight 300 g

Compatibility code PM2120

Environment
Service life 7 year(s)

IP degree of protection IP54 front: conforming to IEC 60529


IP30 body: conforming to IEC 60529

Relative humidity 5…95 % at 50 °C

Pollution degree 2

Ambient air temperature for -10…60 °C


operation

Ambient air temperature for -25…70 °C


storage

Operating altitude <= 2000 m

Electromagnetic compatibility Electrostatic discharge conforming to IEC 61000-4-2


Radiated radio-frequency electromagnetic field immunity test conforming to IEC 61000-4-3
Electrical fast transient/burst immunity test conforming to IEC 61000-4-4
Surge immunity test conforming to IEC 61000-4-5
Conducted RF disturbances conforming to IEC 61000-4-6
Magnetic field at power frequency conforming to IEC 61000-4-8
Voltage dips and interruptions immunity test conforming to IEC 61000-4-11
Emission tests conforming to FCC part 15 class A

Overvoltage category III

Packing Units
Unit Type of Package 1 PCE

Number of Units in Package 1 1

Package 1 Height 9.6 cm

Package 1 Width 6.72 cm

Package 1 Length 10.16 cm

Package 1 Weight 302.5 g

Offer Sustainability
Sustainable offer status Green Premium product

REACh Regulation REACh Declaration

EU RoHS Directive Compliant


EU RoHS Declaration

Mercury free Yes

Aug 7, 2023 3
Company Profile
Safety Electricals Group was established in 1982 and has since grown to become a
prominent industry leader in the electrical and lighting sector in the region.

The Company specializes in the manufacturing and assembly of Sheet Metal Enclosures and
Low Voltage (LV) Switchgear Panels, as well as trading of Electrical and Lighting
Components for application in various industries.

The Switchgear and Sheet Metal manufacturing divisions are located in Techno Park
industrial area (Dubai) in a 100,000 sq. ft. purpose-built facility that employs an experienced
and highly skilled workforce of over 100 people. The Electrical and Lighting trading
divisions are headquartered in Al-Quoz industrial area (Dubai) and have an extensive presence
in the region with several showrooms located throughout the UAE.

Safety Electrical Group is an ISO 9001:2008 certified company and is affiliated to several
internationally renowned companies such as ABB, Hager, Dorman Smith, Larsen & Toubro
(L&T), Legrand, Siemens, Luvata, Socomec, Circutor, Electronicon, Pollmann
Elektrotechnik, Gama Illuminer, Domino Lighting, TMT and Osram.
Sheet Metal Division
Safety Electricals Sheet Metal Division is a complete in-house
manufacturing unit performing design, fabrication and powder
coating of sheet metal enclosures for various applications.

The entire manufacturing process is carried out to specific


procedures and work instructions that have been developed in
accordance with ISO 9001:2008 standards.

The enclosures are IP 55 protection class rated in accordance


with IEC 60529 and have been independently certified by
ASTA.

Manufacturing Equipment
 CNC Punching

 Bending and Cutting Machines

 Welding and Grinding Equipment

 Automated Electrostatic Powder Coating


Service Enclosures (S-Series)
Service Enclosures are available in a wide range of sizes making it a well suited option for a
variety of control and distribution applications. It is distinctly designed and engineered to
allow maximum utilization of enclosure space.

The door frame is provided with hinges with a 130° opening angle and is reversible for left or
right side opening. A large cable entry area is also provided through a removable gland plate.

 Wall or Floor mounted

 EG/GI steel sheets

 Powder coated to RAL 7032 or 7035**

 Mounting plate RAL 2000 coated

 IP 55 protection class

 Reversible door frame for left/right side opening

 Welded earth studs

**Other colors and special finishing available upon request.


H

W D
Service Enclosures (S-Series)
SERVICE ENCLOSURE DIMENSIONS
SL No. H W D REF. No. SL No. H W D REF. No.

1 200 200 150 SESM S-202015 20 800 600 250 SESM S-806025

2 250 200 150 SESM S-252015 21 800 800 200 SESM S-808020

3 300 200 150 SESM S-302015 22 800 800 250 SESM S-808025

4 300 250 150 SESM S-302515 23 1000 600 200 SESM S-1006020

5 300 250 200 SESM S-302520 24 1000 600 250 SESM S-1006025

6 300 300 200 SESM S-303020 25 1000 600 300 SESM S-1006030

7 400 300 150 SESM S-403015 26 1000 800 250 SESM S-1008025

8 400 400 150 SESM S-404015 27 1000 800 300 SESM S-1008030

9 400 400 200 SESM S-404020 28 1200 800 200 SESM S-1208020

10 500 400 200 SESM S-404020 29 1200 800 250 SESM S-1208025

11 600 400 200 SESM S-604020 30 1200 1000 300 SESM S-12010030

12 600 400 250 SESM S-604025 31 1400 800 300 SESM S-1408030

13 600 500 150 SESM S-605015 32 1400 800 400 SESM S-1408040

14 600 500 200 SESM S-605020 33 1400 1000 400 SESM S-14010040

15 600 500 250 SESM S-605025 34 1600 800 300 SESM S-1608030

16 600 600 200 SESM S-606020 35 1600 800 400 SESM S-1608040

17 600 600 300 SESM S-606030 36 1600 1000 300 SESM S-16010030

18 700 500 200 SESM S-705020 37 1600 1200 400 SESM S-16012040

19 800 600 200 SESM S-806020 38 1800 1200 400 SESM S-18012040

GLAND BOX DIMENSIONS


SL No. Height Width Depth REF. No.

1 200 400 200 SESM GB-204020

2 200 500 200 SESM GB-204020

3 250 600 200 SESM GB-204020

4 300 800 200 SESM GB-204020


Multi Row Enclosures (CB-Series)
DIN Type Multi Row Enclosures are made from electro-galvanized steel sheets and are
designed for easy installation and wiring.

The enclosures are available from one (1) to six (6) rows with a DIN rail spacing of 150mm
between the rows. The DIN chassis has a wire spacing of 20mm from the rear wall and is
adjustable (depth) when required.

The sixteen (16) module horizontal width provides superior space utilization and phase
balancing when used in combination with ELCB's, i.e. four (4) modules for ELCB's + twelve
(12) modules for MCB's.

 Surface and Flush type DB's

 1 to 6 row DB's

 16 modules per row

 Powder coated to RAL 7035**

 IP 41 protection class

 Wide body allows ample wiring space

 Reversible door frame for left/right side opening

**Other colors and special finishing available upon request.


Multi Row Enclosures (CB-Series)
MODULAR ENCLOSURE DIMENSIONS

ROWS HS WS D HF WF P Q R S REF. No.*

1 ROW 310 450 115 330 470 360 450 220 300 SESM CB-1R16M

2 ROW 460 450 115 480 470 360 450 370 450 SESM CB-2R16M

3 ROW 610 450 115 630 470 360 450 520 600 SESM CB-3R16M

4 ROW 760 450 115 780 470 360 450 670 750 SESM CB-4R16M

5 ROW 910 450 115 930 470 360 450 820 900 SESM CB-5R16M

6 ROW 1060 450 115 1080 470 360 450 970 1050 SESM CB-6R16M

* Please include 'S' for Surface or 'F' for Flush Type DB in your order.
Polyester (FRP/GRP/FGRP) Products

POLYESTER CABINETS
Protection upto IP-65

• Indoor & Outdoor Use


• Strong & Durable
• All Weather Resistant
• Dust & Water Protected
• Self Extinguishing
• Non Conductive
The company located in Ras Al Khor, Dubai

is a division of Lloyds Engineering. We

manufacture a wide range of specialized

polyester products to meet the requirements

of Engineering and Construction Industries in

the U.A.E., GCC and European markets.

Our strength and quality is built on working

in partnership with end-users and through

technical coordination with our supply sources,

design & production team, inspection and

sales department.
Material
The composite material, which our products are made of and which is more popularly
known as Fibreglass Reinforced Polyester (FRP/FGRP) or Glass-fibre Reinforced
Polyester (GRP), has proven advantages over other conventional material primarily
because of its multiple properties, high strength to weight ratio, versatility & cost
effectiveness in long term use.

All the input materials used in production are of high quality, procured from
manufacturers of international repute.

Products
All our products are the result of superior quality input material blended with the
efforts of a qualified design and production team under the guidance of a highly
professional and efficient management team.
• Our polyester cabinets are available in two basic categories depending on their
dimensions;
• Single Shutter type
• Double Shutter type
• Each of the above cabinet type is available in various standard dimensions and
design as detailed in their respective dimension tables.
• Various accessories are available as standard and optional depending on the
dimensions and type of cabinets.
• All our polyester cabinets have the protection of a gel-coat layer on the weather
exposed surfaces which renders it resistant to UV rays, resistant to corrosive
and chemical environments and virtually suitable for all climatic conditions.
• Standard specifications and properties of cabinets are as per Product Data
Sheet.

Note: Options of client specified properties; dimensions; designs; thickness; external colour-shade; etc
are possible (conditions apply).
Polyester Cabinets

Utility
Our Polyester (GRP) cabinets are ideal for any industry which needs to house
and protect electrical equipments, electronic devices, telecommunication
instruments, fire fighting components, etc.
These cabinets are suitable for both indoor and outdoor conditions. Our cabinets
can be installed in salty, chemically corrosive and harsh environments as well.
Cam Lock ( key)
Advantages
• Polyester cabinets are non-conducting by nature
• Fire retardant and self-extinguishing
• Resistant to corrosive and chemical environments
• Higher strength to weight ratio
• Easy to install
• Virtually maintenance free (occasional cleaning recommended) Gasket
• Can be machined easily

Accessories
Various accessories are available as standard and optional depending on the
type and size of the cabinets.

Special Cabinets
Hinges
Customer specified cabinets can also be manufactured (conditions apply), to
meet special requirements with regard to the following and more;
• External colour-finish
• Dimensions and design
• Fire rating
• IP-Rating (Ingress Protection from solids & liquids)
• Mounting arrangement
• Non –standard transparent view windows Handle Lock
• Shutter location
• Internal shutter
• Provision of extra shutters on sides/back
• Internal partitions vertically/horizontally
• P.U. foam insulated walls

View Glass

Mounting Studs & Plate

Internal Latch
Single Shutter Cabinets

Standard Ranges & Details


[Dimensions in millimetres]
Internal dimensions No. of Std. Mounting Plate Size
Item
Width Height Depth Mounting
Code Width Height Thk.
A B C Studs

STUD CENTRES = (B-100)


CLEARENCE = (B-60)
Mini Cabinets [without awning]

B
200 300 WC-203/15 130 220
250 400 150 WC-254/15 180 320
WC-303/15
300 2 220 1.5
WC-303/20 FRONT VIEW C
300 220 SECTIONAL VIEW
400 200 WC-304/20 320
500 WC-305/20 420
CLEARENCE=(A-60)

A
SECTIONAL VIEW

Built-In / Small Canopy Range

300 500 SC-35/20 180 380


400 SC-44/20 280
200
500 SC-45/20 380

STUD CENTRES = (B-140)


CLEARENCE = (B-100)
400 280
SC-46/20
600

B
250 SC-46/25
4 480 1.5
200 SC-56/20
600
500 SC-56/25 380
250
700 SC-57/25 580

80
FRONT VIEW C
200 SC-68/20
600 800 480 680 SECTIONAL VIEW
300 SC-68/30 STUD CENTRES = (A-120)

CLEARENCE = (A-100)
30

A
SECTIONAL VIEW
Full Canopy Range
800 FC-608/30 670 1.5
45

Centre row studs for

4
height above 1100

600 1000 300 FC-610/30 470 870 2


1200 FC-612/30 6 1070 3
STUD CENTRES = (B-150)
CLEARENCE = (B-100)

300 FC-810/30 2
1000 4 870
B

400 FC-810/40 2
300 FC-812/30 3
800 1200 670 1070
400 FC-812/40 3
6
1400 300 FC-814/30 1270 3
100

C
1600 400 FC-816/40 1470 3 FRONT VIEW
SECTIONAL VIEW
1100 300 FC-911/30 4 970 2 STUD CENTRES = (A-150)
900 770
1400 400 FC-914/40 6 1270 3
CLEARENCE = (A-100)
30

A
SECTIONAL VIEW
Basic Characteristics;
• External protection with gel-coat in RAL 7032 colour • Zinc die cast cam locks (non handle type)
• Self-extinguishing to BS 476:part 7: 1997 class2 • EPDM rubber gaskets
• Resistant to UV rays • High tensile & impact strength
• Non corrosive hinges & hardware • Floor/Wall/Pole mountable
• SS studs- M10 x 30 mm for mounting plate

You might also like