Rudolf - Surge Protective Device
Rudolf - Surge Protective Device
Rudolf - Surge Protective Device
PROTECTIVE
DEVICES
Surge Protective Devices
COMPANY INTRODUCTION
Bridex Singapore Pte Ltd is founded in 1978 as a manufacturer of instruments transformer for the
Asian market. We are the first local electrical switchgear components manufacturer that launches
our own Asian identity –
PRODUCTION INTRODUCTION
Rudolf Surge Protective Devices
Transient over-voltage is characterized with high peak values, rapid amplitude growth and a short
duration. Surge voltages can be caused by:
- Lightning
- Switching of electrical loads by the power utilities
- Switching of high power machines
- Electro-static discharges
Surge Protection Devices are needed in any kind of electrical installation, in order to protect and
provide the following benefits:
- Protect against lightning, its destructive consequences, and the costly repairs and downtimes
that they originate;
- Avoid downtimes caused by random logic failures (that require to restart electronic equipment
to get it back into operation);
- Increase operative life of electronics, by providing to it always a clean and disturbance-
free power supply;
surge protective devices – the brand that add values to your solution.
Surge Protective Devices
BASIC FEATURES
In order to select the most appropriate SPD, we need to understand the selection criteria:
Maximum discharge current (Imax) : The maximum current through the SPD having an 8/20
wave-shape and magnitude to derive the over-current to
earth for one time without suffering damage.
Nominal discharge current (In) : The current through the SPD having a 8/20 wave-shape
and magnitude to derive the over-current to earth for
15 times without suffering damage.
Voltage protection level (Up) : The performance of the SPD in limiting the voltage across
its terminals when the nominal discharge current passes
through it.
Maximum continuous operating voltage/ : The maximum r.m.s. voltage which may be continuously
rated voltage (Uc) applies to the SPD mode of protection.
SPDs are parallel units hence its installation is easy and fast.
• Selection of RUDOLF’s SPD to be installed, this is done by verify the specifications of the
electrical installation with the specifications of your selected RUDOLF’s SPD. (Voltage,nr. of
phases, protection level);
• Read the installation manual before installing any RUDOLF’s SPD;
• Measure voltage between L-N and L-L in your system. Check if the voltage is correct in respect
to the Uc of the selected RUDOLF’s SPD;
• Check if PE is correct (according to the standards);
• Select MCB if needed;
• Switch-off the power supply on the line or panels where the RUDOLF’s SPD must be connected;
• Connection of RUDOLF’s SPD in parallel;
• Check the wire distance between the RUDOLF’s SPD and the connection point to the Line.
- Very important: the wire distance between the RUDOLF’s SPD and the AC Line should be
kept as short as possible, ideally at no more than 1 meter.
- Above 1 meter of connecting wire length, the Up will increase at 20 V per every additional
20 cm. (decreasing performance due to larger impedance).
• Keep the connecting wire as straight as possible. Do not coil it.
• Ground properly the RUDOLF’s SPD.
• If RUDOLF’s SPD is connected in a cabinet or in combination with an RCB, install the RUDOLF’s
SPD prior to the RCB.
• When turning power “on”, check if diagnostics are OK. If out of order switch off the power,
check connections and try again.
Surge Protective Devices
SELECTION GUIDE
Product Code No. of Poles Imax (kA) Un (VAC) Configuration Modes Protected
WIRING DIAGRAM
TN-C Networks TT Networks TNS Networks
TT Networks TN Networks
Surge Protective Devices
SPECIFICATION
Class II : 20 kA, 40 kA Medium Protection Level
Description R-SPD2011 R-SPD202 R-SPD204S R-SPD4511 R-SPD452 R-SPD454S
Nominal Voltage (Un) 230 V 230 V 400 V (L-L) / 230 V 230 V 400 V (L-L) /
230 V (L-N) 230 V (L-N)
Maximum Continuous 275 V 275 V 440 V (L-L) / 275 V 275 V 440 V (L-L) /
Voltage (Uc) 275 V (L-N) 275 V (L-N)
Diagnostics Optical Optical (LED) Optical (LED) Optical, Optical (LED) Optical (LED)
+ Signal + Signal
No. Of Poles 1 2 4 1 2 4
Width Of Housing 18 mm 36 mm 90 mm 18 mm 36 mm 90 mm
Maximum Cable Section 6 mm2 25-35 mm2 25-35 mm2 25-35 mm2 25-35 mm2 25-35 mm2
Ground Connections 6 mm2 25-35 mm2 25-35 mm2 25-35 mm2 25-35 mm2 25-35 mm2
Operating Temperature -30°C, 75°C -30°C, 75°C -30°C, 75°C -30°C, 75°C -30°C, 75°C -30°C, 75°C
SPECIFICATION
Class II : 65 kA High Protection
Description R-SPD6511 R-SPD652 R-SPD654S
Nr. Of Poles 1 2 4
Width Of Housing 18 mm 36 mm 90 mm
SPECIFICATION
Class I : 100 kA High Protection
Description R-SPD10011R R-SPD10013IR
Nr. Of Poles 1 1
Width Of Housing 36 mm 36 mm