Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Earthing Layout

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

NOTES

904.7KWP SOLAR POWER PLANT AT DALMIA GREEN ENERGY VISION LIMITED 1. ALL DIMENSIONS ARE IN MM & LEVEL ARE IN METERS. UNLESS
OTHERWISE MENTIONED.
2. ALL WORK SHALL BE CARRIED OUT AS PER DRAWING SCHEDULE OF
ITEM AND THE DIRECTION OF ENGINEER.
3. ANY DISCREPANCY IN DRG SHALL BE BROUGHT TO THE NOTICE OF
ENGINEER IN CHARGE.
Earth Pit Inspection
4. THIS MODULE LAYOUT MAY VARY DURING DETAIL ENGINEERING.
Chamber
01
Connecting

100
450 Terminal/stud MUMTY

200
Earth Conductor INV-01

INV-02

40550
20275
EP-DC
20275

Natural Earth

300mm Dia Bore


MAIN CONTROL
ROOM
INV-03

INV-04

Eath Enhancing Compound

EP-DC
17.2mm Dia 3m
Copper Bonded Earth Rod
MUMTY

3000
MAIN ACDB

2799
INV-05

MUMTY
INV-06

KEY PLAN
SITE COORDINATE:- 9.272364, 77.919847
1C X 2.5 SQMM. NORTH
GREEN CABLE N

NW
NE

W
E
SW

SE
S

135
TYP.(MODULE TO MODULE EARTHING)
LEGENDS
ARRAY-W-01 ARRAY-E-02 300
SYMBOL DESCRIPTION

EARTHING PIT TYPICAL DETAILS MODULE 545Wp (SAATVIK)

STRING INVERTER

PV DETAILS A.C. DISTRIBUTION BOARD

ROOF NO. OF MODULES DC CAPACITY AC CAPACITY ROOF AREA


INV-01

EP-AC
ARRAY-W-01 836 455.62 375 EP-AC EARTHING PIT-AC
1600A
ACB
250A
MCCB
250A
MCCB
INV-02
ARRAY-E-02 824 449.08 375
EP-DC EARTHING PIT-DC
250A
MCCB
250A
MCCB SYSTEM DETAILS EP-LA EARTHING PIT- LA

250A 250A
MCCB MCCB 25X3 GI STRIP (DC)
75x12 GI STRIP 75x12 GI STRIP S.NO DESCRIPTION DETAILS
75X12 GI STRIP (AC)
MAIN ACDB EP-LA

1 NO. OF MODULES 1660 Nos

3000
FGL FGL
25X6 GI STRIP (LA)
150650

EP-LA

2 MODULE MAKE SAATVIK 1Cx2.5Sqmm. Green Cable


Module to Module
TYPICAL ACDB EARTHING DETAILS 3 MODULE WP 545
4 TOTAL SYSTEM SIZE (KWP) 904.7
5 INVERTER MAKE GROWATT

6 AC CAPACITY (KW) 750

7 STRUCTURE SHORT RAIL

MAIN CONTR
OL ROOM
INV-03

INV-04

1Cx35Sq.mm. Cu.Green cable


INVERTER
75x12 GI STRIP 125KW 75x12 GI STRIP

FGL FGL

EP-AC
3000

EP-AC

TYPICAL INVERTER EARTHING


DETAILS

INV-05

INV-06

EP-AC
NOTES:
MAIN ACDB 1. DC SIDE EARTHING (M-M) WILL WE DONE BY 1CX2.5 SQ.MM 01 As per comments ** ** ** ** 01.11.2023

EP-DC
GREEN CABLE CONNECTING MMS, AND 25X3MM GI EARTHING 00
Rev
Released for Approval
Details of Revision and Description
**
Drawn
**
Design
** ** 19.09.2023
Checked Approved Date
STRIP WILL RUN ALONG THE SHED AND TERMINATE INTO DC
EARTHING PIT.
2. FOR INVERTER GROUNDING, INDIVIDUAL GROUNDING
MUMTY
MONKEY LEDD
ER (1C-35SQMM) CABLE FROM INVERTERS WILL CONNECT TO A
COMMON GI STRIP (75X12) WHICH WILL TERMINATE INTO
EARTHING PIT. Project 904.7 KWP DC ROOFTOP SOLAR PV POWER PLANT AT SATTUR TAMILNADU

3. ALL BREAKER BOX EARTHING WILL BE DONE BY 75X12MM GI Owner DALMIA CEMENT GREEN VISION LIMITED

STRIP WHICH WILL TERMINATE INTO AC EARTHING PIT.


BHARAT CEMENT

4. FOR LA GROUNDING 1C-70SQMM CABLE WILL CONNECT TO A EPC BY SAATVIK GREEN ENERGY (P) LIMITED ( SGEPL)

(25x6) GI STRIP WHICH WILL TERMINATE INTO LA EARTHING PIT Scale NTS
6. MINIMUM DISTANCE BETWEEN EARTHING PIT TO PIT SHOULD BE Drawing Title EARTHING LAYOUT DRAWING
Sheet 01 OF 01
3000mm. SGEPL DWG. NO. SGEPL-DCGVL- RT-S01-EE-DOC-23 Date 01.11.2023

NOTE: THE DRAWINGS OF THIS DRAWING SET IS THE PROPERTY OF SAATVIK GREEN ENERGY (P)
Rev 01
LIMITED. COPYING OR REUSE OF THIS DRAWING WITHOUT PERMISSION IS PROHIBITED.