Professional Documents
Culture Documents
ASHARE 36 Aee - April - 2021 - Ashrae - Guideline - 36
ASHARE 36 Aee - April - 2021 - Ashrae - Guideline - 36
2
Guideline Adoption
• Guideline published January - 2018
• Draft sequences are showing up in some specifications, especially in
California
• State of Washington Energy Code - 2015
• Taylor Engineering has been putting on seminars with Pacific Energy
Center based on RP-1455
• Many ASHRAE chapters are discussing the guideline in monthly
meetings
3
Purpose
“The purpose of this guideline is to provide uniform sequences of
operation for heating, ventilating, and air-conditioning (HVAC) systems
that are intended to maximize HVAC system energy efficiency and
performance, provide control stability, and allow for real-time fault
detection and diagnostics.”1
5
Scope
• Sequences of Operations
- Unit Level
- System Level (Optimization)
▪ Fan Pressure Optimization
▪ Demand Controlled Ventilation
▪ DAT Reset
• Points Lists
• Diagnostics (Including Automatic Fault Detection)
• Alarm Management
• Functional Performance Tests (Future)
6
System Types Addressed
• Multiple Zone VAV
- Single Duct
- Dual Duct
• Single Zone VAV
• Additional systems added as research is completed (Chiller
Plants, Boiler Plants, etc…)
- RP-1711- Phase II Central Plants and Hydronic Systems – Research in
progress.
- WS-1865 - Optimizing Supply Air Temperature Control for Dedicated
Outside Air Systems
7
Sequences of Operation
8
Standards Addressed
• ASHRAE 90.1 (Energy)
• ASHRAE 62.1 (Indoor Environmental Quality)
• Title 24 (California Energy and IEQ)
9
Key Concepts
• Optimization Strategies driven by a weighted voting scheme with Trim
and Respond methodology
10
Please Remember!!!
• 5.1.1 These sequences are intended to be performance based.
Implementations that provide the same functional result using different
underlying detailed logic will be acceptable.
11
TRIM AND RESPOND SETPOINT
RESET
12
Trim and Respond Setpoint Reset
• Trim and Respond is a feedback loop control method
13
Trim and Respond Setpoint Reset
14
Trim and Respond Setpoint Reset
• Zones issue “requests” based on a set of rules
- E.g. “Generate 1 request when damper position exceeds 95%”
15
Trim and Respond Setpoint Reset
• If R ≤ I
- SP = SP* + SPtrim
• If R > I
- SP = SP* +(R-I) x SPres, but not larger than SPres-max
16
Trim & Respond Optimization
Air Handler Static Pressure Optimization
Trim
Respond
Trim
Respond
17
Trim and Respond Advantages
• More stable and easier to tune than PID
• Can trim slowly and respond quickly
- PID moves at same rate
• Easy to identify and adjust for rogue zones
• Control the importance of each individual zone
• Generate requests nonlinearly based on criteria
• Can be utilized for several reset strategies
18
Trim and Respond Examples
• Trim to a more energy
efficient setpoint
• Trim is not always a
decrease in value!!
• Respond to satisfy
comfort
19
ALARMING AND FAULT
DETECTION
20
Hierarchical Alarm Suppression
• Intended to minimize nuisance alarms at the zones from failure of central
equipment
• Example: If a fan fails at an AHU, the zones served by the AHU will have
certain alarms suppressed
- Suppress low airflow alarms, space temp alarms, high CO2 alarms, etc.
• This can be used for hydronic and air systems
- Define the relationships between equipment in each system in terms of “Source” and
“Load”
- Suppress the “Load” alarms when the “Source” is in fault
21
When are alarms suppressed?
• Each System will have a “SystemOK” flag which is either True or False
- SystemOK shall be True when:
▪ System is proven on
▪ System is achieving design setpoint(s) for at least 5 minutes
▪ System is ready and able to serve its load
• When SystemOK is True, load alarms are NOT suppressed
• When SystemOK is False, load alarms are suppressed
22
When to utilize alarm suppression
• This logic may not be applicable in smaller systems
23
Hierarchical Alarm Suppression
Alarms: None
60°
175°
24
Hierarchical Alarm Suppression
Alarms: ????
65º
72° 72° 72° 72° 72° 72° 72°
60°
175°
25
Hierarchical Alarm Suppression
Alarms: Space Temp Alarm
65º
72° 72° 72° 72° 72° 72° 72°
60°
175°
26
Hierarchical Alarm Suppression
Alarms: ????
65º
72° 72° 72° 72° 72° 72° 72°
60°
95º
175°
27
Hierarchical Alarm Suppression
Alarms: Space Temp Alarm and Low Boiler Temp Alarm
65º
72° 72° 72° 72° 72° 72° 72°
60°
95º
175°
28
Hierarchical Alarm Suppression
Alarms: ????
45º
60°
95º
175°
29
Hierarchical Alarm Suppression
Alarms: Space Temp Alarm and Low Boiler Temp Alarm
45º
60°
95º
175°
30
Automated Fault Detection
• Based on NIST research and tested on several sites as part of RP-1455
• 15 “rules” that can be evaluated
- Only for AHUs
- Based on mass/energy balance equations
- Each Fault Condition specifies:
▪ Performance assessment: if equation is true, there is a fault
▪ Operating state(s) when fault condition is evaluated
▪ Likely causes of fault
• Designed to minimize false alarms
- Assumes typical sensor error
- Utilize rolling averages to smooth input spikes
31
Example Fault Conditions
32
Example Fault Conditions
33
GENERAL ZONE LOGIC
34
General Zone Logic
• Temperature Setpoints
- Every zone has occupied and unoccupied setpoints
▪ Separate heating and cooling setpoints, minimum of 1°
F deadband
▪ Setbacks based on occ sensor, window switch, and demand limiting
• Heating and Cooling control loop
- Rules to limit windup
35
VAV Terminal Units
36
VAV AHU
• Outdoor air measurement/control options
- Differential Pressure/AFMS on OA intake
- AFMS on combined economizer/OA intake
• Building Pressure Options
- Barometric (nonpowered) relief
- Relief Fan
- Return Fan
▪ Controlled by building pressure or airflow tracking
▪ Addenda proposed to improve airflow tracking sequence
• Minimum OA control options for ASHRAE 62.1 or Title 24 ventilation
rules
37
VAV AHU
• Discharge air temperature setpoint must balance fan energy and
compressor/chiller energy
• DAT setpoint trades fan energy against chiller energy:
- Low DAT setpoint = more chiller energy, less fan energy
- High DAT setpoint = less chiller energy, more fan energy
• To find a balance, sequence uses both, zone reset based on T/R, and
OAT based linear reset
- In cold weather, DAT setpoint is high so economizer is maximized
- In warm weather, DAT setpoint is low to reduce fan energy
38
Special Case - DAT reset
• DAT setpoint must balance fan and
compressor/chiller energy
- Low DAT setpoint = more chiller energy,
less fan energy
- High DAT setpoint = less chiller energy,
more fan energy
39
Guideline Future
• Continuous Maintenance
- Several addenda have been proposed to fix some known issues with the guideline
- Addition of sequences for hydronic systems (chilled water, hot water, steam)
- Addition of functional tests to provide guidance for proving the sequences have
been implemented
40
How engineers can specify GL 36
• Cut and Paste sections into specs, edit as needed
- Pros: Engineer able to edit and provide desired SOOs
- Cons: Difficult to edit .PDF; Time consuming; hard to track changes from original
Guideline sequence
• Specify section number from Guideline along with any desired changes,
Contractor to provide SOOs
- Pros: Easier for Engineer; better tracking of changes
- Cons: Contractor required to compile as-built SOOs
41
QUESTIONS?
42