Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

MCCB I Nterlock

Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

Accessories

4.7 Locking and interlocking

Installation of other accessories


When the cylinder lock is fitted in the accessories compartment of the circuit breaker, some
other accessories cannot be installed, see chapter Possible combinations of of accessories
(Page 142).

See also
Manual operators (Page 238)
Draw-out technology (Page 215)

4.7.3.2 Sliding bar with Bowden cable: Modules for sliding bar with Bowden cable
A mutual interlock between up to three molded case circuit breakers can be implemented by
means of the front Bowden cable interlock. This interlock functions according to the blocking
principle: If one of the circuit breakers included in the interlock is unlocked, the Bowden
cables move in such a way as to ensure that the other molded case circuit breakers are
locked in the OFF (O) position.
In order to implement a front Bowden cable interlock, sliding bar modules must be mounted
on the 3VA molded case circuit breakers to be included in the interlock arrangement. Each of
these modules is equipped with a slide which blocks or releases operation of the handle.

① Sliding bar module


② Slide

3VA molded case circuit breakers


282 Manual, 04/2015, A5E03603177010-02
Accessories
4.7 Locking and interlocking

A Bowden cable must be installed in addition to the sliding bar modules. This cable prevents
the slides from releasing more than one molded case circuit breaker at any one time. As a
result, only one 3VA molded case circuit breaker at a time can be operated and only one
molded case circuit breaker can be in the ON (I) position.

① 3VA1 160 molded case circuit breaker, blocked by slide


② 3VA2 250 molded case circuit breaker, released by slide

Note
For installation instructions, please refer to operating instructions "Sliding bar modules".

Bowden cable lengths


The following lengths of Bowden cable can be ordered:
● 0.5 m
● 1.0 m
● 1.5 m

3VA molded case circuit breakers


Manual, 04/2015, A5E03603177010-02 283
Accessories
4.7 Locking and interlocking

Interlock combinations
Interlocks can be implemented between the following 3VA molded case circuit breakers:

Possible combinations of handle positions


When a sliding bar with Bowden cable is installed to interlock two 3VA molded case circuit
breakers, the following combinations of handle position are possible:

When a sliding bar with Bowden cable is installed to interlock three 3VA molded case circuit
breakers, the following combinations of handle position are possible:

Installation of other accessories


When the front Bowden cable interlock module is fitted, some other accessories cannot be
installed, see chapter Possible combinations of of accessories (Page 142).

3VA molded case circuit breakers


284 Manual, 04/2015, A5E03603177010-02

You might also like