Apparent Power Control Systems

'A' GRADE CONTRACTOR LICENCE NO:3418


AVA Heritage, Karunakaran Street, Pachiyammai Nagar, Gerugambakkam, Chennai – 600128.
Mail: sales@appcs.in, Web: www.appcs.in, Mob No: +919841387065

GSTIN: 33ABOFA6602P1Z4, MSME UDYAM No: TN-24-0015601

CLIENT EXCEL ENGINEERS


MEP APPARENT POWER CONTROL SYSTEMS

S.NO DESCRIPTION QTY UNIT Remarks


01.00.00 HT PANELS
11KV 4 PANEL RING MAIN UNIT INDOOR TYPE) (Near
01.01.00
Exisiting 630KVA Transformer)
NOTE : Unloading, receiving at SITE, storing and leading shall be
contractors account only. Also Demand Controller to be installed in
outgoing VCB's
CABLE ENTRY & EXIT: BOTTOM

Supplying,erecting,connecting & commissioning of INDOOR 800


AMPS RING MAIN UNIT with
INCOMING:
1 Nos. 800 AMPS HT VCB with Surge Arrestors, LA,
OUTGOING:
NOT IN OUR
3 No.630 AMPS TP HT VCB with LA Gapless type with disconnector as
SCOPE
Outgoing.This shall be mounted on MS Channels with individual CT &
PT and shall have provision for drawing Out Breaker including civil
works.The channels should be sand blastered before painting. Painting
shall be two coats of epoxy Paint.
(Surge Arrestor termination shall be provided outside the panel)

METERING AND PROTECTION FOR EACH INCOMING &


OUTGOING BREAKER

INCOMING (Each Breaker)


3 Nos. Three core Cast Resin CTs of Ratio 150-75/5A-5A Class 0.2S
with protection 5P20 and the CT Core Burden shall be 15VA for
Protection.

OUTGOING (Each Breaker):


6 Nos. Three core Cast Resin CTs of Ratio 150-75/5A-5A Class 0.2S
with protection 5P20 and the CT Core Burden shall be 15VA for
Protection. (1250KVA Transformer)
3 Nos. Three core Cast Resin CTs of Ratio 80-40/5A-5A Class 0.2S with
protection 5P20 and the CT Core Burden shall be 15VA for Protection.
*Make shall be same for all the meters and shall be with RS 485
Communication. Approved Make: Secure / Conzerv / Schneider /
L&T / Elmeasure

3 Nos. Cast Resin PTs of Ratio 11 KV/110V Class 0.2 The CT Burden
shall be 200VA with fuse shall be provided
Over load and Earth fault relay of CDG 61 with Instantaneous Highset
element on Three Phases.Relay make shall be of Schneider
(Model:Micom P111 relay) (or) C&S with Instantaneous current block
facility as per TANGEDCO's requirement. (Relay shall be with
communication)

Auxilary Coil Voltage of 230V from UPS.


Tripping & Closing Coil 110V DC.
Spring Charging Motor 230V AC from PT.
RYB Indication Lamps of LED Clustered Type with control fuses shall
be provided.

Digital Three Row Volt Meter and Ammeter required (96mm x 96mm)

Common Power Pack shall be provided for all breakers together.


Individual power pack shall not be accepted
Space Heater with Thermostat to be provided
NOTE :
01. The CT and PT shall not be mounted inside the cable chamber.It
should be removable without disturbing any arrangement. And make
shall be only OHM ENERGY
02. 1 No. Power Pack of rating 110V AC to 110V DC.
03. The incoming and outgoing shall have a Cable box to receive HT
XLPE Cable.

04. The CTs/PTs shall be got tested at the MES designated laboratory by
the Supplier.All costs to be included for the same.All approvals from
MRT & TANGEDCO will be the responsibility of the Supplier.No extra
payment will be entertained on his count.

04a. The CTs/PTs and testing instruments shall be got tested at the CPRI
TESTING laboratory by the Supplier.All costs to be included for the
same.All approvals from TANGEDCO will be the responsibility of the
Supplier.No extra payment will be entertained on his count.

05. The CT ratios are indicative only.The correct CT ratio as


approved by MES for required Maximum Demand 1250KVA shall
be ascertained by the Supplier before manufacturing.

06. INDICATION LAMP, MFM & DEMAND CONTROLLER

a) Breaker ON/OFF/TRIP
b) Spring Charged Lamps
c)Trip Circuit healthy Lamp
d)Auxilary Triping Relay
e) Load Manager - Demand Controller WITH DIFFERENT HOOTER
NOISE DIFFERENTIATING BETWEEN I/C AND O/G
f) Multi Function Meter with Harmonics Measurement and with
communication (Incomer MFM shall be with Phase Angle in graphical
Format - Eqvt. to Schnieder EM7290)

07. ALARM & TRIP


REMOTE EMERGENCY TRIP & ALARM
BREAKER CONTROL TRIP & ALARM
AUXILARY TRIPPING RELAY
PUSH BUTTON FOR TRIP CIRCUIT
HEALTH CHECK TRIP & ALARM
08. TWELVE WINDOW ANNUNCIATOR - make to be specified in
remarks
FOR OVER CURRENT INSTANTANEOUS
FOR OVER CURRENT TRIP
FOR EARTH FAULT INSTANTANEOUS
EARTH FAULT TRIP
TRANSFORMER WTI TRIP
TRANSFORMER WTI ALARM
TRANSFORMER OTI TRIP
TRANSFORMER OTI ALARM
BUCHOLZ RELAY TRIP
BUCHOLZ RELAY ALARM
MOG TRIP
MOG ALARM 1 SET
05.00.00 LT BUS DUCT (FABRICATED TYPE)
2500A TPN ALUMINIUM EB BUSDUCT FROM NEW 1250KVA
05.01.00 TRANSFORMER LV SIDE TO INDOOR MV Panel (Conventional
Type)

Supplying,erecting,connecting & commissioning of 2500 Amps TPN Al.


Busduct with necessary straight runs,bends,Risers,brackets from
1250KVA Transformer to LT ACB (Kiosk).The Busduct shall be
properly supported through proper brackets.The Phase Busbar shall be 2
Runs of 150 x 12 mm. and the Neutral Busbar shall be 1 Run of 150 x
12 mm.The Earth Busbar shall be 2 Runs of 50 x 12 mm.

Note:
1. Bus Duct shall be Conventional type only with Cantilever / Hanging Only Supply is
Supports provided in interval of 1.5 mtr with Rigid Angle considered
2. Bus Duct Shall have Sufficient Louvers with SS Bug Mesh on the
inner side
3. Bus Duct shall be with Door at bottom openable in outdoor area and
top openable in indoor area. Vendor to make Shop drawing accordingly
4. Flexible Aluminium shall sized suitable to existing bus bar size and
shall be used to termiate bus duct to EB Incomer Breaker in MV Panel,
Transfomer LT Side, DG Sync Panel Outgoing Breaker, DG Incomer
Breaker in MV Panel
5. Heat Sensor with Temperature monitor is required for Bus Duct - The
temperature monitor shall be mounted in EB Incomer of MV Panel

05.01.01 2500 AMPS TPN Aluminum Bus Duct Straight Run 40 MTRS.

05.01.02 Right Angle bends (90 Deg.) 6 NOS.

05.01.03 Aluminium Flexible joints. 4 SETS

NOTE:
01. Proper supports shall be provided at the
a) Transformer LV side.
b) Receiving ACB Shall be provided with in such a way that the Weight
of the Bus Duct does not bear on the ACB in LT ACB (Kiosk).

02. The supports shall be of powder coated.


06.00.00 LT PANELS(Including Unloading & storing at site)
MAIN MV PANEL (SINGLE BUSBAR)
06.01.00
@ SUBSTATION BUILDING
EB CABLES ENTRY: BOTTOM
DG CABLES ENTRY: BOTTOM
OUTGOING CABLES EXIT: BOTTOM & TOP

Only Supply is
Supplying,erecting,connecting & commissioning of FLOOR MOUNTED
considered Loading
CUBICLE TYPE MAIN MV PANEL BOARD.The Board shall be
and Unloading are
incorporated with the following:-
client scope

EB INCOMER:
2500 AMPS 4P EDO ACB with Builtin Display unit(DRAWOUT TYPE
- Microprocessor based) with 50KA(Ics) with CDG11 & Shunt Trip
Facility Releases And Over current, Short circuit,Earth fault releases
shall be provided with SR21 Releases (220V AC) (LSING) ...
1 No.

EB incomer shall be provided with Single Phase Preventer

EB incomer shall be provided with Phase Reversal Relay - Minilec

Heat Sensor with Temperature monitor is required for Bus Duct - The
temperature monitor shall be mounted in EB Incomer of MV Panel

CBCT with ELR shall be provided

DG INCOMER 1:2500 AMPS 4P EDO ACB with Builtin Display unit


(DRAWOUT TYPE - Microprocessor based) with 50KA(Ics)
Withstanding Capacity with CDG11 & Shunt Trip Facility Releases And
Over current, Short circuit,Earth fault releases shall be provided with
SR21 Releases (220V AC) (LSING) ... 1 No.

CBCT with ELR shall be provided

INTERLOCKS :-
a) Electrical and Mechanical interlocking arrangement shall be
provided between EB Incomer, DG Incomer.
OUTGOINGS:

1600 AMPS 4P MDO ACB (DRAWOUT TYPE - Microprocessor


based) with 50KA(Ics) Withstanding Capacity with CDG11 & Shunt
Trip Facility Releases And Over current, Short circuit,Earth fault
releases shall be provided with SR21 Releases (220V AC) LSING and
also provide Digital Multifunction Meter with suitable CT (Shunt trip
and UV Coil is required) ... 1 No.
1000 AMPS 4P MDO ACB (DRAWOUT TYPE - Microprocessor
based) with 50KA(Ics) Withstanding Capacity with CDG11 & Shunt
Trip Facility Releases And Over current, Short circuit,Earth fault
releases shall be provided with SR21 Releases (220V AC) LSING and
also provide Digital Multifunction Meter with suitable CT (Shunt trip
and UV Coil is required) .. 4 No.

1000 AMPS 3P MDO ACB (DRAWOUT TYPE - Microprocessor


based) with 50KA(Ics) Withstanding Capacity with CDG11 & Shunt
Trip Facility Releases And Over current, Short circuit, Earth fault
releases shall be provided with SR21 Releases (220V AC) for APFCR
(Shunt trip and UV Coil is required) .. 1 No.

630 AMPS TPN MCCB (TM based) with 36KA(Ics) Withstanding


Capacity and with O/L & S/C Releases and also provide Digital
Multifunction Meter with suitable CT (Shunt trip and UV Coil is
required) .. 6 No.
400 AMPS TPN MCCB (TM based) with 36KA(Ics) Withstanding
Capacity and with O/L & S/C Releases and also provide Digital
Multifunction Meter with suitable CT (Shunt trip and UV Coil is
required) .. 3 Nos.
250 AMPS TPN MCCB (TM based) with 36KA(Ics) Withstanding
Capacity and with O/L & S/C Releases and also provide Digital
Multifunction Meter with suitable CT (Shunt trip and UV Coil is
required) .. 6 Nos.
125 AMPS TPN MCCB (TM based) with 36KA(Ics) Withstanding
Capacity and with O/L & S/C Releases and also provide Digital
Multifunction Meter with suitable CT (Shunt trip and UV Coil is
required) .. 3 No.
NOTE:
01. All Outgoing MCCBs shall have Adjustable Overload and Short
Circuit settings.
02.The withstanding capacity mentioned is Ics only.
03. Control Supply shall be take only through 4P MCB in all panels and
control voltage shall be 230V AC
04. All indication lamps shall be provided with Fuse TB
EB BUSBAR : ALUMINIUM
RATING : 2500 AMPS
The Phase Bus bar shall be 2 Run 150 x 12mm. and the Neutral bar shall
be 1 Run of 150 x 12mm.
The Earth bar shall be 2 Runs of 75 x 6mm.
There shall be ONE Set of Metering Compartment incorporated with the
following for EB Incomer

i) 3 Nos. Dual core Cast Resin CTs of ratio 2500/ 5A of Class 1.0 for
measurement and 5P10 for Protection.The CT burden shall be 15VA.

ii) 1 No. Cast Resin CTs of ratio 1250/5A of Class 1.0 for
measurement for APFCR Panel. The CT burden shall be 15VA.

iii) 1 No. DIGITAL CONZERV MAKE Load Manager (OR) Equivalent


Make wth Maximum Demand Controller.
iv) RYB Indication lamp and Control Fuses shall be provided.
v) Multi Function Meter with THiD & TDvD Class 1 Accuracy and
communication (Eqvt. Model Schneider PM2210)
There shall be Metering Compartment incorporated with the following
for DG Incomer

i) 3 Nos. Dual core Cast Resin CTs of ratio 800/5A of Class 1.0 for
measurement and 5P10 for Protection.The CT burden shall be 15VA.

ii) 1 No. DIGITAL CONZERV MAKE Load Manager (OR) Equivalent


Make.
iii) RYB Indication lamp and Control Fuses shall be provided. 1 SET

iv) Multi Function Meter with Class 1 Accuracy and Comminication

Only Supply is
considered Loading
06.04.00 APFCR PANEL 450KVAR @ SUBSTATION BUILDING
and Unloading are
client scope

CABLE ENTRY: BOTTOM


Supplying,erecting,connecting & commissioning of FLOOR MOUNTED
CUBICLE TYPE APFCR PANEL BOARD.The Board shall be
incorporated with the following:-
INCOMER: 1000 AMPS TP MDO ACB with 36 KA(Ics) Withstanding
Capacity with Adjustable O/L & S/C and Earth fault Releases (Shunt
trip and UV Coil is required). .. 1 No.

OUTGOINGS: 250 AMPS TPN MCCB 36KA (Ics) Withstanding


capacity And with suitable Capacitor duty Contactor, Overload & Short
Circuit Releases Coil Voltage 220V AC .. 1 Nos.

160 AMPS TPN MCCB 36KA (Ics) Withstanding capacity And with
suitable Capacitor duty Contactor, Overload & Short Circuit Releases
Coil Voltage 220V AC .. 3 Nos.
80 AMPS TPN MCCB 36KA (Ics) Withstanding capacity And with
suitable Capacitor duty Contactor, Overload & Short Circuit Releases
Coil Voltage 220V AC .. 4 Nos.
63 AMPS TPN MCCB 36KA (Ics) Withstanding capacity And with
suitable Capacitor duty Contactor, Overload & Short Circuit Releases
Coil Voltage 220V AC .. 1 No.
32 AMPS TPN MCCB 36KA (Ics) Withstanding capacity And with
suitable Capacitor duty Contactor, Overload & Short Circuit Releases
Coil Voltage 220V AC .. 1 No.
NOTE:
01. All MCCBs shall have Adjustable Overload and Short Circuit
settings.
02. The withstanding capacity shall be Ics only.

An 12-Step APFC Relay with transducer shall be incorporated to


maintain the power factor.The Panel shall also be made suitable to
accommodate the following Capacitor Banks with all interconnections.

100 KVAR .. 2 Nos


50 KVAR .. 2 Nos.
25 KVAR .. 4 Nos.
15 KVAR .. 2 No.
10 KVAR .. 2 No.
The quote should include supply,banking and installation of each
Capacitor Banks inside the Panel.
100 KVAR Detuned 7% Harmonic filter reactor at 440V and 525V
heavy duty Capacitor - 2 Nos.
50 KVAR Detuned 7% Harmonic filter reactor at 440V and 525V heavy
duty capacitor - 2 Nos.
25 KVAR Detuned 7% Harmonic filter reactor at 440V and 525V heavy
duty capacitor - 4 Nos.
15 KVAR Detuned 7% Harmonic filter reactor at 440V and 525V heavy
duty capacitor - 2 No.
10 KVAR Detuned 7% Harmonic filter reactor at 440V and 525V heavy
duty capacitor - 2 No.
BUSBAR : ALUMINIUM
RATING : 1000 AMPS

The Phase Bus bar shall be 100 x 10 mm. and the Neutral bar shall be
60 x 10 mm. The Earth Bus bar shall be 2 Runs of 50 x 10 mm.

There shall be One Set of Metering Compartment incorporated with the


following:-
i) 3 Nos. CTs of ratio 1250/5A of Class 1.0 for measurement.The CT
burden shall be 15VA.
ii) 1 No.Class 1.0,96 Sq.mm. Ammeter (0 -1250A) with built in selector
Switch and Control fuses shall be provided.
iii) 1 No.Class 1.0,96 Sq.mm.Voltmeter (0 -500V) with built in Selector
switch and Control Fuses shall be provided.
iv) 1 No. Digital Power Factor Meter
v) RYB Indication lamp and Control Fuses shall be provided. 1 SET
06.05.00 DG Synchornisation Panel
FOR EACH DG SET

Only Supply is
INCOMER: 1000 AMPS FP EDO ACB with 36 KA(Ics) Withstanding
considered Loading
Capacity with Adjustable O/L & S/C and Earth fault Releases (Shunt
and Unloading are
trip and UV Coil is required). .. 3 No.
client scope

Synchronisation relay with necessary interlock

Touchscreen HMI - 10.2Inch for DG Sync Operation, Storage of


operation Parameters along with fault history.

Outgoing Breaker:
2500 AMPS 4P EDO ACB (DRAWOUT TYPE - Microprocessor based)
with 50KA(Ics) with CDG11 & Shunt Trip Facility Releases And Over 1 SET
current, Short circuit,Earth fault releases shall be provided with SR21
Releases (220V AC) (LSING) ... 1 No.

LT ACB PANEL - WEATHERPROOF TYPE (For Rising Main 1)


06.06.00
1000A - Hospital Block 1
Supplying,erecting,connecting and commissioning of FLOOR
MOUNTED CUBICLE TYPE LT ACB (KIOSK) WEATHER PROOF
TYPE PANEL BOARD.The Board shall be incorporated with the
following:-
INCOMING CABLE ENTRY: BOTTOM
OUTGOING CABLES EXIT : BOTTOM
INCOMER: 1000 AMPS FP MDO ACB (DRAWOUT TYPE -
Microprocessor based) with 50KA(Ics) Withstanding Capacity with
CDG11 & Shunt Trip Facility Releases And Over current, Short
circuit,Earth fault releases shall be provided with SR21 Releases (220V
AC) ... 1 No.

BUSBAR : ALUMINIUM
RATING : 1000 AMPS
The Phase Busbar shall be 2R x100 x 10mm. and the Neutral bar shall be
1Rx100 x 10mm. Suitable for teminating 2R x 3.5C 240Sqmm in both
incoming and outgoing side
The Earth bar shall be 2 Runs of 75 x 6 mm.
i) 3 Nos. Cast Resin CTs of Ratio 1000/5A class 5 for Measurement and
Protection.The CT Burden shall be 15VA
ii) 1 No. Class 1.0, Digital Multifunction meter.
iii) RYB Indicating Lamps of LED Clustered type and Control fuses
shall be provided.
04. The supports shall be of powder coated. 1 Nos
LT MCCB PANEL - WEATHERPROOF TYPE (For Rising Main 2)
06.06.00
630A - Hospital Block 1

Supplying,erecting,connecting and commissioning of FLOOR Only Supply is


MOUNTED CUBICLE TYPE LT ACB (KIOSK) WEATHER PROOF considered Loading
TYPE PANEL BOARD.The Board shall be incorporated with the and Unloading are
following:- client scope

INCOMING CABLE ENTRY: BOTTOM


OUTGOING CABLES EXIT : BOTTOM
INCOMER: 630 AMPS TPN MCCB (TM based) with 36KA(Ics)
Withstanding Capacity and with O/L & S/C Releases and also provide
Digital Multifunction Meter with suitable CT (Shunt trip and UV Coil is
required) ... 1 No.
BUSBAR : ALUMINIUM
RATING : 630 AMPS
The Phase Busbar shall be 2R x 60 x 10mm. and the Neutral bar shall be
1Rx 60 x 10mm. Suitable for teminating 2R x 3.5C 185Sqmm in both
incoming and outgoing side
The Earth bar shall be 2 Runs of 50 x 6 mm.
i) 3 Nos. Cast Resin CTs of Ratio 630/5A class 5 for Measurement and
Protection.The CT Burden shall be 15VA
ii) 1 No. Class 1.0, Digital Multifunction meter.
iii) RYB Indicating Lamps of LED Clustered type and Control fuses
shall be provided.

04. The supports shall be of powder coated. 1 Nos

Only Supply is
considered Loading
06.07.00 A/C TERRACE Panel - Outoor type For AHU and ODU Unit
and Unloading are
client scope

CABLE ENTRY : BOTTOM


Supplying, erecting, connecting and commissioning of FLOOR MOUNTED
with Base Channel increasing height of the panel from floor by 500mm to ensure
cable entry is possible through bottom
Overall height of the panel including Base Channel shall not exceed 2000mm,

also the maximum operating handle height shall not exceed 1800mm
A/C Panel with necessary foundation channels, etc.,
The Board shall be incorporated with the following:-
All MCCBs shall be of Thermal Magnetic Type with adjustable
overloads and fixed short circuits (Ics=100%Icu)
INCOMER :
630AMPS TPN MCCB 36 KA(Ics = 100% Icu) With standing Capacity …
01No.

OUTGOINGS :
63 AMPS TP2N MCCB 25 KA(Ics = 100% Icu) withstanding Capacity ..12
Nos.
32 AMPS TP2N MCCB 25 KA(Ics = 100% Icu) withstanding Capacity ..22Nos.
1 Nos