Boq With Busduct
Boq With Busduct
3 Nos. Cast Resin PTs of Ratio 11 KV/110V Class 0.2 The CT Burden
shall be 200VA with fuse shall be provided
Over load and Earth fault relay of CDG 61 with Instantaneous Highset
element on Three Phases.Relay make shall be of Schneider
(Model:Micom P111 relay) (or) C&S with Instantaneous current block
facility as per TANGEDCO's requirement. (Relay shall be with
communication)
Digital Three Row Volt Meter and Ammeter required (96mm x 96mm)
04. The CTs/PTs shall be got tested at the MES designated laboratory by
the Supplier.All costs to be included for the same.All approvals from
MRT & TANGEDCO will be the responsibility of the Supplier.No extra
payment will be entertained on his count.
04a. The CTs/PTs and testing instruments shall be got tested at the CPRI
TESTING laboratory by the Supplier.All costs to be included for the
same.All approvals from TANGEDCO will be the responsibility of the
Supplier.No extra payment will be entertained on his count.
a) Breaker ON/OFF/TRIP
b) Spring Charged Lamps
c)Trip Circuit healthy Lamp
d)Auxilary Triping Relay
e) Load Manager - Demand Controller WITH DIFFERENT HOOTER
NOISE DIFFERENTIATING BETWEEN I/C AND O/G
f) Multi Function Meter with Harmonics Measurement and with
communication (Incomer MFM shall be with Phase Angle in graphical
Format - Eqvt. to Schnieder EM7290)
Note:
1. Bus Duct shall be Conventional type only with Cantilever / Hanging Only Supply is
Supports provided in interval of 1.5 mtr with Rigid Angle considered
2. Bus Duct Shall have Sufficient Louvers with SS Bug Mesh on the
inner side
3. Bus Duct shall be with Door at bottom openable in outdoor area and
top openable in indoor area. Vendor to make Shop drawing accordingly
4. Flexible Aluminium shall sized suitable to existing bus bar size and
shall be used to termiate bus duct to EB Incomer Breaker in MV Panel,
Transfomer LT Side, DG Sync Panel Outgoing Breaker, DG Incomer
Breaker in MV Panel
5. Heat Sensor with Temperature monitor is required for Bus Duct - The
temperature monitor shall be mounted in EB Incomer of MV Panel
05.01.01 2500 AMPS TPN Aluminum Bus Duct Straight Run 40 MTRS.
NOTE:
01. Proper supports shall be provided at the
a) Transformer LV side.
b) Receiving ACB Shall be provided with in such a way that the Weight
of the Bus Duct does not bear on the ACB in LT ACB (Kiosk).
Only Supply is
Supplying,erecting,connecting & commissioning of FLOOR MOUNTED
considered Loading
CUBICLE TYPE MAIN MV PANEL BOARD.The Board shall be
and Unloading are
incorporated with the following:-
client scope
EB INCOMER:
2500 AMPS 4P EDO ACB with Builtin Display unit(DRAWOUT TYPE
- Microprocessor based) with 50KA(Ics) with CDG11 & Shunt Trip
Facility Releases And Over current, Short circuit,Earth fault releases
shall be provided with SR21 Releases (220V AC) (LSING) ...
1 No.
Heat Sensor with Temperature monitor is required for Bus Duct - The
temperature monitor shall be mounted in EB Incomer of MV Panel
INTERLOCKS :-
a) Electrical and Mechanical interlocking arrangement shall be
provided between EB Incomer, DG Incomer.
OUTGOINGS:
i) 3 Nos. Dual core Cast Resin CTs of ratio 2500/ 5A of Class 1.0 for
measurement and 5P10 for Protection.The CT burden shall be 15VA.
ii) 1 No. Cast Resin CTs of ratio 1250/5A of Class 1.0 for
measurement for APFCR Panel. The CT burden shall be 15VA.
i) 3 Nos. Dual core Cast Resin CTs of ratio 800/5A of Class 1.0 for
measurement and 5P10 for Protection.The CT burden shall be 15VA.
Only Supply is
considered Loading
06.04.00 APFCR PANEL 450KVAR @ SUBSTATION BUILDING
and Unloading are
client scope
160 AMPS TPN MCCB 36KA (Ics) Withstanding capacity And with
suitable Capacitor duty Contactor, Overload & Short Circuit Releases
Coil Voltage 220V AC .. 3 Nos.
80 AMPS TPN MCCB 36KA (Ics) Withstanding capacity And with
suitable Capacitor duty Contactor, Overload & Short Circuit Releases
Coil Voltage 220V AC .. 4 Nos.
63 AMPS TPN MCCB 36KA (Ics) Withstanding capacity And with
suitable Capacitor duty Contactor, Overload & Short Circuit Releases
Coil Voltage 220V AC .. 1 No.
32 AMPS TPN MCCB 36KA (Ics) Withstanding capacity And with
suitable Capacitor duty Contactor, Overload & Short Circuit Releases
Coil Voltage 220V AC .. 1 No.
NOTE:
01. All MCCBs shall have Adjustable Overload and Short Circuit
settings.
02. The withstanding capacity shall be Ics only.
The Phase Bus bar shall be 100 x 10 mm. and the Neutral bar shall be
60 x 10 mm. The Earth Bus bar shall be 2 Runs of 50 x 10 mm.
Only Supply is
INCOMER: 1000 AMPS FP EDO ACB with 36 KA(Ics) Withstanding
considered Loading
Capacity with Adjustable O/L & S/C and Earth fault Releases (Shunt
and Unloading are
trip and UV Coil is required). .. 3 No.
client scope
Outgoing Breaker:
2500 AMPS 4P EDO ACB (DRAWOUT TYPE - Microprocessor based)
with 50KA(Ics) with CDG11 & Shunt Trip Facility Releases And Over 1 SET
current, Short circuit,Earth fault releases shall be provided with SR21
Releases (220V AC) (LSING) ... 1 No.
BUSBAR : ALUMINIUM
RATING : 1000 AMPS
The Phase Busbar shall be 2R x100 x 10mm. and the Neutral bar shall be
1Rx100 x 10mm. Suitable for teminating 2R x 3.5C 240Sqmm in both
incoming and outgoing side
The Earth bar shall be 2 Runs of 75 x 6 mm.
i) 3 Nos. Cast Resin CTs of Ratio 1000/5A class 5 for Measurement and
Protection.The CT Burden shall be 15VA
ii) 1 No. Class 1.0, Digital Multifunction meter.
iii) RYB Indicating Lamps of LED Clustered type and Control fuses
shall be provided.
04. The supports shall be of powder coated. 1 Nos
LT MCCB PANEL - WEATHERPROOF TYPE (For Rising Main 2)
06.06.00
630A - Hospital Block 1
Only Supply is
considered Loading
06.07.00 A/C TERRACE Panel - Outoor type For AHU and ODU Unit
and Unloading are
client scope
also the maximum operating handle height shall not exceed 1800mm
A/C Panel with necessary foundation channels, etc.,
The Board shall be incorporated with the following:-
All MCCBs shall be of Thermal Magnetic Type with adjustable
overloads and fixed short circuits (Ics=100%Icu)
INCOMER :
630AMPS TPN MCCB 36 KA(Ics = 100% Icu) With standing Capacity …
01No.
OUTGOINGS :
63 AMPS TP2N MCCB 25 KA(Ics = 100% Icu) withstanding Capacity ..12
Nos.
32 AMPS TP2N MCCB 25 KA(Ics = 100% Icu) withstanding Capacity ..22Nos.
1 Nos