Schneider National and Strategic Accounts Submittal Sample

Download as pdf or txt
Download as pdf or txt
You are on page 1of 70

Electric.

Their use or reproduction without prior consent of


These drawings and designs are the property of Schneider
National And Strategic Accounts

the company is strictly forbidden.


Submittal Sample National & Strategic Accounts
800 Federal Street
Andover, MA 01810

Date:
Preliminary
Architect: TBD

# Change:
Engineer: TBD

Revision:

1
2
3
4
5
Project Number: TBD

5/26/2022
5/26/2022
5/26/2022
Date:
Date:
Date:
Drawing Index:

Page 000-1 Title Page 1 of 2 Page 407-1 SHELL Floorplan

Designed by:
Software by:
Checked by:
Contractor:
Engineer:
Architect:
Page 000-2 Title Page 2 of 2 Page 408-1 Panel Wall Layouts
Page 101-1 Device and Equipment Legend Page 501-1 ADMIN Equipment Installation Details 1 of 3

National And Strategic Accounts


Page 101-2 Standards and Symbols Page 501-2 ADMIN Equipment Installation Details 2 of 3
Page 101-3 Cable Specification Page 501-3 ADMIN Equipment Installation Details 3 of 3

Title Page 1 of 2
Page 201-1 PHX11 ADMIN Network Architecture Page 502-1 COLO-AHU Equipment Installation Details 1 of 2
Page 201-2 PHX11 COLO Network Architecture 1 OF 3 Page 502-2 COLO-AHU Equipment Installation Details 2 of 2
Page 201-3 PHX11 COLO Network Architecture 2 OF 3 Page 503-1 COLO Equipment Installation Details 1 of 7
Page 201-4 PHX11 COLO Network Architecture 3 OF 3 Page 503-2 COLO Equipment Installation Details 2 of 7
Page 301-1 ADMIN Systems Diagrams Page 503-3 COLO Equipment Installation Details 3 of 7
Page 302-1 COLO-AHU System Diagram Page 503-4 COLO Equipment Installation Details 4 of 7
Page 303-1 COLO System Diagram Page 503-5 COLO Equipment Installation Details 5 of 7

5/27/2022

5/27/2022
Last Printed
Last Saved
Page 401-1 ADMIN Floorplan Page 503-6 COLO Equipment Installation Details 6 of 7
Page 402-1 COLO 1 CELL 2 & 4 Floorplan Page 503-7 COLO Equipment Installation Details 7 of 7

Job Number

000 Table of Contents.vsd


Page 402-2 COLO 1 CELL 1 & 3 Floorplan

Sheet Number
File Name

000-1
Electric. Their use or reproduction without prior consent of
These drawings and designs are the property of Schneider
National And Strategic Accounts

the company is strictly forbidden.


Project Number: TBD

Date:
Preliminary
Drawing Index:
Page 601-1 ADMIN Panel Power Detail Page 603-8 COLO 1 Panel Layout - Door
Page 601-2 ADMIN Panel IO Detail - 1 & 2 Page 605-1 SHELL Panel Power Detail
Page 601-3 ADMIN Panel IO Detail - 3 Page 605-2 SHELL Panel IO Detail - 1 & 2

# Change:
Page 601-4 ADMIN Panel IO Detail - 4 Page 605-3 SHELL Panel IO Detail - 3

Revision:
Page 601-5 ADMIN Panel Layout - Main Page 605-4 SHELL Panel IO Detail - 4

1
2
3
4
5
Page 601-6 ADMIN Panel Layout - Door Page 605-5 SHELL Panel IO Detail - 5
Page 602-1 COLO-AHU Panel Power Detail Page 605-6 SHELL Panel IO Detail - 6
Page 602-2 COLO-AHU Panel IO Detail - 1 & 2 Page 605-7 SHELL Panel IO Detail - 7
Page 602-3 COLO-AHU Panel IO Detail - 3 Page 605-8 SHELL Panel IO Detail - 8

5/26/2022
5/26/2022
5/26/2022
Page 602-4 COLO-AHU Panel IO Detail - 4 Page 605-9 SHELL Panel Layout - Main
Page 602-5 COLO-AHU Panel IO Detail - 5 Page 605-10 SHELL Panel Layout - Door

Date:
Date:
Date:
Page 602-6 COLO-AHU Panel IO Detail - 6 Page 606-1 ADMIN/AHU Panel Power Detail
Page 602-7 COLO-AHU Panel IO Detail - 7 Page 606-2 ADMIN/AHU Power Panel Layout
Page 602-8 COLO-AHU Panel Layout - Main Page 607-1 COLO Panel Power Detail
Page 603-1 COLO 1 Panel Power Detail Page 607-2 COLO Power Panel Layout

Designed by:
Software by:
Checked by:
Contractor:
Engineer:
Architect:
Page 603-2 COLO 1 Panel IO Detail - 1 & 2 Page 607-3 COLO Remote Power Panel Layout
Page 603-3 COLO 1 Panel IO Detail - 3 Page 608-1 DP Panel Layout

National And Strategic Accounts


Page 603-4 COLO 1 Panel IO Detail - 4 Page 608-2 DP Panel Wiring
Page 603-5 COLO 1 Panel IO Detail - 5 Page 609-1 DP Manifold Panel Layout

Title Page 2 of 2
Page 603-6 COLO 1 Panel IO Detail - 6 Page 610-1 Battery Room CO Panel Layout
Page 603-7 COLO 1 Panel Layout - Main

5/27/2022

5/27/2022
Last Printed
Last Saved
Job Number

000 Table of Contents.vsd

Sheet Number
File Name

000-2
Input/Output Blocks & Reference Tags

Electric. Their use or reproduction without prior consent of


Device and Equipment Legend

These drawings and designs are the property of Schneider


Page Note Reference

SEBA Point Name

the company is strictly forbidden.


1
Humidity Sensor Duct Humidity Sensor Duct Humidity Sensor Room Humidity Sensor Room Humidity Sensor Outdoor Humidity Sensor Outdoor
SaTmp Controller 3-Wire 24Vac (0-10 Vdc) 2-Wire 24Vdc (4-20mA) 3-Wire 24Vac (0-10Vdc) 2-Wire 24Vdc (4-20mA) 3-Wire 24Vac (0-10Vdc) 2-Wire 24Vdc (4-20mA)
Controller Termination UI# SaTmp
Points RaRh RaRh RmRh RmRh OaRh OaRh
UI# RET RET Controller
Controller Controller Controller Controller Controller Controller
## UI# RET UI# RET UI# RET UI# RET UI# RET UI# RET
X#N TBPA Y2- TBPA X#N TBPA Y2- TBPA X#N TBPA Y2- TBPA
Controller
Termination Points X#H TBPA Y1+ TBPA X#H TBPA Y1+ TBPA X#H TBPA Y1+ TBPA
OUT COM VIN 4-20 VIN OUT COM VIN 4-20 VIN OUT COM VIN 4-20 VIN
Controller Name
Interlock Equipment RH# RH# RH# RH# RH# RH#
Detail Reference
R1 1
Interlock Number

Temperature Sensor Temperature Sensor Temperature Sensor Temperature Sensor Temperature Sensor Temperature Sensor Living Space Sensor Living Space Sensor Living Space Sensor Living Space Sensor Living Space Sensor Living Space Sensor Living Space Sensor DC Terminal
Duct Probe Averaging Insertion Outdoor Air Room Bulb (Strap-On) Blank Cover Blank w/PIR Set Point & Override Set Point, Override & PIR Set Point, Override & LCD Set Point, Override & Set Point, Override, PIR & Power Supply Block
Display Touchscreen Touchscreen

Date:
SaTmp MaTmp ChwSTmp OaTmp RmTmp DxSlTmp
Controller Controller Controller Controller Controller Controller ##

Preliminary
UI# RET UI# RET UI# RET UI# RET UI# RET UI# RET LSS# LSS# LSS# LSS# LSS# LSS# LSS#

~ +
~ - Grounding
GRN WHT GRN WHT GRN WHT GRN WHT + - GRN WHT
PS1 Block
TS# TS# TS# TS# TS# TS#

From: Controller From: Controller From: Controller From: Controller From: Controller From: Controller From: Controller

Differential Pressure Transmitter Differential Pressure Transmitter Gauge Pressure Transmitter Gauge Pressure Transmitter Differential Pressure Switch Differential Pressure Differential Pressure Switch High Static Limit Low Static Limit Separable Relay Circuit
3-Wire 24Vac (0-10Vdc) 2-Wire 24Vdc (4-20mA) 3-Wire 24Vac (0-10Vdc) 2-Wire 24Vdc (4-20mA) Transmitter Safety Switch Safety Switch Breaker
Set @ 1.0"
SaStPr SaStPr ExpTnkPt ExpTnkPr FinFilSts

# Change:
13 R# 14

Revision:
Controller Controller Controller Controller CB#
UI# RET UI# RET UI# RET UI# RET UIx RET
Hi Hi NC COM NC COM 9 5
X4H TBPA Y2- TBPA X#N TBPA Y2- TBPA H L L H
HSL# LSL# R#-1
X3H TBPA Y1+ TBPA X#H TBPA Y1+ TBPA DPT# DPS#

1
2
3
4
5
Set @ 3.5" Set @ 3.5" 9 1 Fused
OUT COM PWR OUT PWR WH/YL/GN BU/BK RED BU/BK RED 2-NC 1-COM
High Low High Low High High High Low Lo Lo R#-1 Switch
DPT# DPT# PT# PT# DPS#
12 8
R#-2
FS#
12 4
R#-2

CO2 Duct CO2 Room CO2 Outdoor Current Switch Current Switch Current Transducer Current Monitor Relay Current Switch Relay Point to Point Relay Field Relay Detail

5/26/2022
5/26/2022
5/26/2022
3-Wire 24Vac (0-10Vdc) 3-Wire 24Vac (0-10Vdc) 3-Wire 24Vac (0-10Vdc) 2-Wire 24Vdc (4-20mA) Reference
Output Input
RaCO2 RmCO2 OaCO2 SaFanSts SaFanAmp FR#
R Status
Controller Controller Controller Controller CS# Controller ##
FR#
UI# RET UI# RET UI# RET UI# RET UI# RET BLU
13 FR# 14
X4H TBPA X#N TBPA X#N TBPA Y2- TBPA Status R ORG YEL
X3H TBPA X#H TBPA X#H TBPA Y1+ TBPA Output Input

Date:
Date:
Date:
Current Transducer Panel Relay Fluid Type &

120 VAC
OUT GND V+ OUT GND V+ OUT GND V+ + - + - CMR# CSR#

WHT/BLU

WHT/YEL

WHT/BLK
24 VAC
Directional
CO2_# CO2_# CO2_# CS# CT#
Indicator
R#
CT# CMR# CSR# CHWS
13 R# 14

Valve Actuator 2-Position Actuator Floating Actuator Floating Actuator Proportional Actuator Proportional Actuator Tranformer Interlock
4-Wire 3-Wire 4-Wire 3-Wire Reference

Designed by:
Software by:
Checked by:
ACT ACT ACT

Contractor:
Engineer:
Architect:
BLK RED RED
CV# DprCmd DO# TB-PA X#N COM TB-PA X#N COM TB-PA X#H HOT TB-PA X#H HOT
RED BLK BLK XXX 1
Controller COM TB-PA X#H HOT TB-PA X#H Close ACT TB-PA X#N COM TB-PA X#N COM
RED YEL/blk GRY WHT
TB-PA X#H HOT Controller COM CCW Controller COM Open CtrlrName COM COM CtrlrName COM (Y1) AI
BLK BLU GRN/yel ORG WHT BRN
TB-PA X#N COM ACT DrvCls DO# CW DrvCls DO# ActPos UO# GND ActPos UO# (U) AO
GRN/yel GRN/yel YEL/blk BLU
GND DrvOpn DO# GND DrvOpn DO# AI L R CCW CW

National And Strategic Accounts


Damper Motor BLU Page Note
(Actuator) AO Reference
BLK

Device and Equipment


DM# PRI XFR# SEC
ActFdBk RET ActFdBk RET
1
Controller UIx Controller UIx

Legend
2-Way Valve 3-Way Valve Fan Chilled Water Coil Heat Pump Coil Electric Heating Coil Dual Temp Coil Duct Humidifier Thermal Dispersion Airflow Opposed Blade Damper Butterfly Damper Insertion Impeller/Turbine Insertion Mag Meter Multi-Tap
Normally Closed Station Flow Meter Transformer
HEAT ELEC DUAL D1 FM# FM#
CV# CV#
N.O.
AB A AB A
See Valve Schedule GRY BRN
B PUMP HEAT TEMP
YEL BLU
See Valve Schedule
ORG
2-Way Valve Hydronic Pump Fan Array Hot Water / Steam Coil DX Cooling Coil Gas Heat Exchanger Hot Gas Coil Airflow Measuring Station VAV Air Flow Sensor Parallel Blade Damper Duct Air Filter Inline Flow Meter Inline Usage Meter
WHT
Normally Open or No Failsafe
BLK
CV# ChwP# DX GAS HOT D1
AFS1 PRI XFR# SEC
N.O.
AB A
See Valve Schedule FM# WM#
CLG HEAT GAS

5/27/2022

5/27/2022
Filter

Last Printed
Last Saved
Chiller Air Cooled Chiller Single Cell Cooling Tower Dual Cell Cooling Tower Fluid Cooler Boiler Shell and Tube Heat Exchnager Plate & Frame Heat Variable Motor Duct Smoke Detector
Exchanger Frequency Starter
CT-# CT-#A CT-#B FC-# Drive SD#
CH-#

Job Number
B-#

101 Legends and Standards.vsd


STM-HX#
Motor
CH-# VFD
Starter Unit Heater

Sheet Number
HX-# (Add coil type)

File Name

101-1
SP1 L1 L2 L3 L1 L2 L3

M
Electric. Their use or reproduction without prior consent of
Standards and Symbols

These drawings and designs are the property of Schneider

the company is strictly forbidden.


Introduction and Rules General Notes Job Specific Notes

• Should a situation arise wherein the rules and requirements in this drawing set are in direct conflict • All room thermostats/sensors/controllers shall be installed at 48" above finished floor for ADA • Refer to Customer’s master specifications section 25 05 00 for installation standards.
with a specific clause in the contract, NEC, or project specifications, said conflict will be resolved by compliance for new installations unless noted otherwise in the contract documents. For
the Schneider Electric project manager on a case-by-case basis. replacement of existing devices, leave sufficient rolled coil of wire above the ceiling should the • The master specifications are based on US codes and standards, namely ICC International Codes
device need to be moved down to meet this requirement in the future. Install one LON / BACnet / (Building, Plumbing, Mechanical, Fire), National Electric Code (NEC), Underwriter's Laboratory (UL)
• All work is to be installed professionally in a neat, workmanlike manner. When completed, all panels Infinet / I/P drop at t-stat per floor or wing. standards and certification directories, FM Global Property Loss Prevention Data Sheets and
and devices are to be cleaned (vacuumed), with all wire duct closed and no debris in the panel. approval guides, among others.
Panel is to be locked when applicable. • All panel keys will be collected daily and removed from the panels installed. These keys are to be
given to the project manager or Schneider Electric representative. • The specified codes and standards are considered minimum acceptable design standards. The
• No penetrations should be made into live equipment. When drilling into control cabinets (Schneider project A/E is responsible to review the master specifications in conjunction with local applicable
or otherwise) every effort should be made to protect the equipment inside from debris as a result of • All thermowells shall be filled with thermal conductive compound, prior to the sensors being codes and standards for the project site and identify applicable differences. In general, if an
this penetration; ideally penetrations should be made prior to installation of sub-panel/backplane inserted/installed. applicable local code or standard is less restrictive than specified requirement; comply with specified
and equipment. requirements. If an applicable local code or standard is more restrictive than the specifications;

Date:
• Wiring Terminations designated as ‘X’, ‘XX’ or ‘TBD’ indicate information was unavailable at time of comply with local applicable code. Review differences between specified and local applicable codes
• Unless specifically stated otherwise, the electrical subcontractor is responsible for the complete submittal. The electrical subcontractor shall document the final terminations for use in record and standards with Owner for resolution of which requirements to follow.

Preliminary
installation of all sensors, damper motors and supplemental devices. Any union or jurisdictional drawings.
overlap is the responsibility of the electrical contractor to resolve.
• Remote control devices, not in local panels, shall be accessible for adjustment and service - below
• It is standard industry practice for the BAS contractor is to be responsible for interlock wiring of 6' above finished floor whenever possible or as shown on the provided construction prints.
miscellaneous systems (i.e. Generator dampers, boiler interlocks, make-up water, refrigerant leak
alarm systems, fuel oil interlocks, booster/sump pump interlock wiring). The electrical contractor • Only prints marked Construction are to be used during installation. If the prints are not marked
should be aware of this and shall carry this work as part of their scope unless specifically instructed Construction, the installer will correct any discrepancies between prints used and Construction at no
otherwise in writing. It is understood that specific wiring diagrams for this equipment are often not cost to Schneider Electric.
available at time of bid.
• All new BAS controller panels shall have dedicated 120VAC power sources. This source shall be
• The electrical subcontractor will always follow all safety requirements based on minimum standards located and marked in the electrical and control panel as well as on the control prints returned to
set forth by Schneider Electric, The General Contractor/Construction Manager, Customer, and site. Schneider Electric for Record prints.
In all cases, the most stringent rules and regulations will apply

# Change:
Revision:
• The electrical subcontractor shall be responsible for maintaining the functionality of existing safeties
• It is the responsibility of the electrical subcontractor to provide a foreman for all work. The foreman after BAS installation – electrically or pneumatically connected. Schneider Electric will not bypass
is responsible for attending all applicable meetings (foreman meeting). The foreman is responsible any existing safety interlocks.
for coordinating with Schneider Electric field staff as well as other trades. The foreman is

1
2
3
4
5
responsible for providing manpower information to the Schneider Electric project staff on a daily • All field device cables and wires shall be labeled by the electrical subcontractor using Brady
basis. PermaSleeve or equivalent; cables and wires shall be labeled with its corresponding point name as
shown on the input/output block.
• Unless specifically instructed otherwise, it is the responsibility of the electrical subcontractor to
receive and store all material and to get it to the project site. • For VFD control wiring, use shielded cable and metallic conduit only. Do not run control and power
wiring in the same conduit. Separate metallic conduits carrying power wiring from conduits carrying
• Finally, it is the responsibility of the electrical subcontractor to mobilize to work when work is control wiring by at least 6". Separate existing, non-metallic conduits or cable trays used to carry
available to complete. It is understood that a construction environment can often be crowded and power wiring from metallic conduit carrying control wiring by at least 12". Whenever power and

5/26/2022
5/26/2022
5/26/2022
difficult place to work; this is not an excuse not to properly staff available work and complete within control wiring cross, the metallic conduits and nonmetallic conduits or trays must cross at right
schedule requirements. angles.

• See Division 23 09 00 for any additional information on BMS installation standards.

Date:
Date:
Date:
Pipe Color HEX Code RGB Code Color Abbreviations
Primary Chilled Water 3-Letter 3-Letter 3-Letter 2-Letter 2-Letter 2-Letter 1-Letter 1-Letter
Color Stripe
Caps Mixed Lower Caps Mixed Lower Cap Lower
CHWS 0000FF 0, 0, 255
Black BLK Blk blk BK Bk bk B b

Designed by:
Software by:
Checked by:
Contractor:
Blue BLU Blu blu BU Bu bu U u

Engineer:
CHWR 00CCFF 0, 204, 255

Architect:
Brown BRN Brn brn BR Br br N n
Secondary Chilled Water Gold GLD Gld gld GL Gl gl D d
Gray GRY Gry gry GY Gy gy A a
SCHWS 008080 0, 128, 128 Use
Green GRN Grn grn GN Gn gn G g
Lower
Orange ORG Org org OR Or or O o

National And Strategic Accounts


SCHWR 33CCCC 51, 204, 204 Case
Pink PNK Pnk pnk PK Pk pk P p
Abbreviation

Standards and Symbols


Primary Condenser water Red RED Red red RD Rd rd R r
Silver SLV Slv slv SV Sv sv S s
CWS 008000 0, 128, 0
Violet VIO Vio vio VL Vl vl V v
White WHT Wht wht WH Wh wh W w
CWR 789440 121, 149, 64
Yellow YEL Yel yel YL Yl yl Y y
Secondary Condenser Water
SCWS 33CC33 51, 204, 51 Floorplan Symbols

SCWR 99CC00 153, 204, 0 T Temperature Sensor L Leak Detector


Primary Hot Water
P Pressure Pickup or Sensor R Field Relay
HWS FF0000 255, 0, 0
H Humidity Sensor CS Current Switch
HWR C05046 192, 80, 70
Secondary Hot Water C Carbon Dioxide Sensor

SHWS EA700D 234, 112, 14 T


Temperature & Humidity (Combo) Sensor

5/27/2022

5/27/2022
Last Printed
H

Last Saved
SHWR F59D56 234, 157, 86
Low Pressure Steam A Actuator
LPS FFC000 255, 192, 0
F Flow Meter

Job Number
COND 000000 0, 0, 0

101 Legends and Standards.vsd


EF Exhaust Fan
Ground Water
H2 Hydrogen Sensor

Sheet Number
GWS 800080 128, 0, 128

File Name

101-2
GWR D98CFF 204, 102, 255 BAS/AHU Control Panel
Make Up Water
MUW 996633 153, 102, 51 DP Panel
Electric. Their use or reproduction without prior consent of
Cable Specification

These drawings and designs are the property of Schneider

the company is strictly forbidden.


Conduit Type and Fill Cable Standards and Use Cable Recommendations
Conduit Type and Labeling
• EMT, IMC, Rigid, FMC as determined by minimum specified standards and NEC Minimum Requirements PLENUM rated cable type
Function Device Type Conductors Notes
• Conduit to be marked with an easily identified color to be coordinated with Schneider field staff, or as Recommended
iPortal [Connect Air] Part #
required by project specifications. Jacket Color
• Box/covers and LBs/covers to be painted with previously coordinated color, and identified as BMS
High Voltage (More than 50 Volts) Low Voltage (50 Volts or Less)
and service (COM, Power, etc.)
Line Voltage Wire is to be as detailed in electrical specification and NEC code Power 24 VAC 16/2 Non-Shielded Green KEL-W161P-2062GRRB (5-7) (9)
Plenum Requirements
• All plenum wiring needs to be run in a parallel and perpendicular fashion.
Power 24 VDC 18/2 Non-Shielded Pink KEL-W181P-2051PNKB (5-7) (9)
• All wiring to be rated for plenum application and meet minimum specified standards and NEC
• Plenum wire to be marked with an easily identified color to be coordinated with Schneider field staff,
Low Voltage (50 Volts or less) BMS Control Cabling
or as required by project specifications.
• Care shall be taken to keep a minimum safe distance from the following: High voltage wiring, high

Date:
Input 22ga Minimum shielded, 600 V protection required for entry into VFD or other high voltage cabinets I/O 2-wire I/O Shielded 18/2 Shielded White KEL-W181P-2040B (5-9)
induction loads, high heat sources, or any equipment or wiring that could cause damage to
installation or interference with signals.

Preliminary
Output 18ga Minimum shielded, 600 V protection required for entry into VFD or other high voltage cabinets I/O 3-wire I/O Shielded 18/3 Shielded White KEL-W183C-2058B (5-9)
• Plenum wiring is not to be directly secured to ceiling grid or all thread.
I/O 4-wire I/O Shielded 18/4 Shielded White KEL-W184C-2059B (5-9)
Installation
• All wall and shaft penetrations will be fire stopped using approved fire stop 2-wire I/O
Network I/O 18/2 Non Shielded White KEL-W181P-2051RIB (5-9)
• All external penetrations (whether into structures, boxes or equipment) to be weather tight and Unshielded
protected as defined by the specifications and NEC. 3-wire I/O
CAT-6 CAT-6 as standard, unless otherwise called for by specifications I/O 18/3 Non Shielded White KEL-W183C-2052B (5-9)
• No splices unless specifically approved in writing by the Schneider project manager. Said approved Unshielded
splices to be clearly indicated on redline drawings with labeled junction boxes. NO COLOR 4-wire I/O
I/O 18/4 Non Shielded White KEL-W184C-2059B (5-9)
CHANGES AT SPLICES Unshielded
(3) (5-7)
Fiber Optic T-Stat S-Link 22/2P Non-Shielded Purple KEL-W221P-2005PRB
Fill and Spare Wire (9)
• All work is to include room for expansion and future changes as such, maintain no more then 2/3rd of (4) (5-7)
Fiber Optic Refer to job spec. for fiber type and ends T-Stat Sensor Bus 24/4P Non-Shielded w/PVC Blue KEL-W244P-2274BL

# Change:
max wires permitted in conduit. Larger or multiple conduit runs to be used to same location if 2/3rd (9)

Revision:
fill rule would be exceeded.
Network & Communication Cabling
• Spare wire to be included in conduit runs from BMS panels to any large equipment AHUs, fuel Pump
skids, cooling towers, Boilers, chillers, generator, etc. Spare Min of 1- shielded 18/4 cable. (1-2) (5-7)
Serial Communication (RS-485, Lon) Comm. BACnet 24/2 Shielded Lo Cap Orange KEL-W241P-2000FRIB

1
2
3
4
5
• Spare wire to be included in any long conduit runs from BMS panel serving multiple points in remote (9)
locations. Example: Basement to roof equipment. Spare Min of 1- shielded 18/4 cable. (2) (5-7)
Protocol Size Impedence Capacitance Maximum Length Comm. Modbus 24/2 Shielded Lo Cap Yellow KEL-W241P-2050FYLRB
• In the case of simple 2 conductor zone sensors, a minimum of a shielded 18/4 is to be pulled unless (9)
otherwise specified (3) (5-7)
BACnet 22/24 awg 120 Ohms <14 pf/ft 4000 ft Comm. LON Bus 22/1P Non-Shielded Echelon Purple KEL-W221P-2001PB
• A drag line will be left in all conduit runs for future expansion or changes. (9)
(1-2) (5-7)
Modbus 22/24 awg 120 Ohms <14 pf/ft 4000 ft Comm. Infinet 24/2 Shielded Lo Cap Rasberry KEL-W241P-2000FBRSP
(9)
(4) (5-7)
LON 22 awg 100 Ohms 17 pf/ft 4600 ft Comm Ethernet 24/4P Non-Shielded w/PVC Blue KEL-W244P-2274BL
(9)

5/26/2022
5/26/2022
5/26/2022
Keyed Notes
(1) Capacitance between conductors is approximately 12pF per foot.
Cable Legend Network & Communications (2) Shielded Twisted Pair.
• Every Schneider Electric IP level control panel is to have a Cat6 Ethernet or fiber connection as needed to a network switch or (3) Unshielded Twisted Pair.
BACnet MS-TP next control panel as shown in the approved control drawings. See the appropriate network and control drawings for (4) Category-6 Ethernet cabling between Network Controllers and Network Switch.

Date:
Date:
Date:
BACnet MS-TP (RS-485) clarification. (5) Plenum or Non-Plenum version shall be field determined.
• Always coordinate with a Schneider field technician or project manager for details and general layout regarding network (6) Recommended colors shown; field confirm with Schneider Electric project manager.
Modbus architecture prior to install. Any deviation from approved Schneider riser diagrams and Network architecture drawings must (7) Equivalent cables from Belden, Windy City Wire, etc. are acceptable.
Modbus RTU (RS-485 be approved by Schneider personal only. (8) Use shielded cable as required for specific installations.
• In addition, Electrical contractor is to keep a legible copy of as-builts of specific network route(s) on Mechanical drawings. These (9) Cable jacket colors are recommended. Coordinate with Schneider Electric
LonWorks as-builts should show exactly which devices are on the communication segment, the order in which each device is located on
LonWorks (FTT-10) the segment, location, and how/where the cables are routed between devices. See Electrical Subcontractors Handbook for Terminations
examples. • All panel wiring to be run inside of wire duct.
• Wires in wire duct should not cross each other excessively.

Designed by:
• Communication cables are to be run separate from power wiring, and never in the same conduit.

Software by:
Checked by:
Infinet

Contractor:
• Maintain maximum distance from any high voltage wiring (lighting ballasts, VFDs, and/or other electrical equipment which will • Limit the use of cable ties within the wire duct. They usually get cut off when troubleshooting.

Engineer:
Infinet (RS-485)

Architect:
create “noise” on network) or cable to eliminate noise/interference on network. • Do not run wire over other devices.
• Inside of any enclosures or VFD where communication cabling would inevitably come in relative close proximity with high voltage • Leave service loop – field wire should be long enough to reach any point inside the panel.
EOL RS-485 End of Line Resistor (120Ω) • The slack has to be hidden out of sight within the wire duct
cable (greater than 24 AC/DC) it is critical that the wiring be passed through the enclosure in such a way to create the
maximum allowable space between it and the power wiring. Above shall be accomplished through use of cable ties and cable • Strip back approximately 4 inches of cable jacket so that each conductor can be easily accessed for service (removal, testing,
TERM2 LonWorks FTT-10 Bus Topology Terminator

National And Strategic Accounts


tie adhesive mounts to maintain general requirements for neatness, and appearance. replacement) while still maintaing a neat appearance within the panel.
• All data cables must be continuous straight runs without any splicing, breaks, or ground faults. • Make sure stripped of wires do not touch each other to avoid shorts.
TERM1 LonWorks FTT-10 Free Topology Terminator • Strip back enough insulation to make sure terminal clamp locks down on only bare wires.
• All CAT6 data cables need to be certified to EIA/TIA-568 standards with appropriate, calibrated testing equipment. Testing
• No bare wire should be visible beyond the terminal strip.

Cable Specification
equipment is to have been calibrated within the past 6 months.
##
BOM Software
2-Conductor Cable • Wires must exit the terminal strips straight.
Tag Tag ##
End-1 Standard Patch Cable Standard End-2 Cross Over End-2
BOM Software ##
2-Conductor Shielded Cable 1 Orange/White 1 Cable Length Guideline
Tag Tag ## 1 2 3 4 5 6 7 8 2 Orange 2 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
3 Green/White 3 Universal inputs/outputs as digital inputs 22 AWG 650 ft.
##
BOM Software 4 Blue 4
Tag Tag
## 3-Conductor Cable 5 Blue/White 5 Universal inputs/outputs as analog inputs 22 AWG 330 ft.
##
6 Green 6
7 Brown/White 7 Universal inputs/outputs as temperature (thermistor)
18 AWG 250 ft.
##
8 Brown 8 inputs, up to 167 °F
BOM Software
Tag Tag
## 3-Conductor Shielded Cable Universal inputs/outputs as temperature (thermistor)
14 AWG 500 ft.
## Cross Over Cable inputs, up to 167 °F
1 1 Universal inputs/outputs as temperature (thermistor)
14 AWG 250 ft.
##
2 2 inputs, up to 302 °F
BOM Software ## b B 3 3 b B b B Universal inputs/outputs, for actuators and transmitters
4-Conductor Cable 18 AWG 65 ft.

5/27/2022

5/27/2022
Tag Tag ## o O g B b G o O g B b G g G o B b O powered from the same transformer as the Controller
r R r R r R

Last Printed
4 4

Last Saved
##
5 5 Universal inputs/outputs, for actuators and transmitters
22 AWG 650 ft.
6 6 powered from their own transformer (external or internal)
##
7 7 Sensor Bus CAT5 or CAT6 200 ft. Total
BOM Software ##
4-Conductor Shielded Cable 8 8
Tag Tag ##

Job Number
IP/Ethernet/BACnet IP CAT5 or CAT6 100 m per segment

101 Legends and Standards.vsd


##

Sheet Number
File Name

101-3
Pin-1 Pin-8
Electric. Their use or reproduction without prior consent of
PHX11 ADMIN Network Architecture

These drawings and designs are the property of Schneider

the company is strictly forbidden.


PHX11-ADMIN-FCR-CAB02 PHX11-ADMIN-FCR-CAB01

PHX11-ADMIN-FCR-CEI-FEX102 TAHUYA VLAN PHX11-ADMIN-FCR-CEI-FEX101 TAHUYA VLAN

1 11 13 23 25 35 37 47 1 11 13 23 25 35 37 47

TAHUYA TAHUYA
NETWORK 2 12 14 24 26 36 38 48 2 12 14 24 26 36 38 48 NETWORK

PHX11-ADMIN-FCR-CEI-FEX102 BAS VLAN PHX11-ADMIN-FCR-CEI-FEX101 BAS VLAN

1 11 13 23 25 35 37 47 1 11 13 23 25 35 37 47

BAS BAS

Date:
NETWORK 2 12 14 24 26 36 38 48 2 12 14 24 26 36 38 48 NETWORK

Preliminary
PHX11CEH02 PHX11CEH01

1
Virtual Machine 01: EcoStruxure Building Operation Enterprise Server

1
Virtual Machine 02: External Log Storage [Database Server]

# Change:
Revision:
PHX11 ADMIN FACILITY CABLE ROOM PHX11 ADMIN FACILITY CABLE ROOM

1
2
3
4
5
PHX11-ADMIN-BAS WORKSTATION02 PHX11-ADMIN-BAS WORKSTATION01

MEDIA CONVERTER
(BY OTHERS)

5/26/2022
5/26/2022
5/26/2022
PHX11 ADMIN OPEN OFFICE PHX10 ADMIN FACILITY OPERATIONS CENTER

Date:
Date:
Date:
1 2 3 4 5 6 7 8 9 10 11 12

TX/RX+

TX/RX+

TX/RX+

TX/RX+
TX/RX-

TX/RX-

TX/RX-

TX/RX-
BIAS+
RET

RET

RET
UI-16 UI8/DO-FC-4-H

RS232/RS485
Com A Com B RS-485 TP/FT

TAHUYA DEVICE
RS-485 LON
Schneider Electric Schneider Electric Schneider Electric Schneider Electric
SXW PS-24V SXW AS-P SXW IO SXW IO
PS-1 Device

5VDC

Host
10/100 10/100
Ethernet 1 Ethernet 2
SL3 SL4

PHX11-ADMIN-CC01 PHX11 ADMIN FACILITY CABLE ROOM

Designed by:
Software by:
Checked by:
Contractor:
Engineer:
Architect:
DOAS

National And Strategic Accounts


GATEWAY

PHX11 ADMIN Network


PHX11-ADMIN-DOAS01-CP PHX11 ADMIN OUTSIDE

Architecture
To EPMS
Network Switch DX VRF
EPMS
System

GATEWAY DIII-NET
PHX11 ADMIN FACILITY CABLE ROOM
PHX11-ADMIN-FCR-MCG ENCLOSURE

MEDIA CONVERTER
1 2 3 4 5 6 7 8 9 10 11 12
TX/RX+

TX/RX+

TX/RX+

TX/RX+
TX/RX-

TX/RX-

TX/RX-

TX/RX-
BIAS+
RET

RET

RET

UI16 UI16 UI16 UI16 UI16 AO-8-H


(BY OTHERS)

5/27/2022

5/27/2022
Com A Com B RS-485 TP/FT
RS-485 LON

Last Printed
Schneider Electric Schneider Electric Schneider Electric Schneider Electric Schneider Electric Schneider Electric Schneider Electric

Last Saved
Schneider Electric
SXW PS-24V SXW AS-P SXW IO SXW IO SXW IO SXW IO SXW IO SXW IO
PS-1 Device

Host
10/100 10/100
Ethernet 1 Ethernet 2
SL3 SL4 SL5 SL6 SL7 SL8

PHX11-COLO5-CE4-CC01 PHX11 COLO5 SHELL


NETWORK CABLE LEGEND

Job Number

201 Network Architecture.vsd


TAHUYA BUILDING NETWORK
Default

Sheet Number
BAS CAMPUS NETWORK Part Number Qty Description Manufacturer

File Name
----------------------------------------------------------------------------------------------------------------------------------------------------

201-1
BAS CAT6 ETHERNET
SXWSWESDBTS001 1 TIMESCALE DB OPTION - ES Schneider Electric
TAHUYA CAT6 ETHERNET NOTES SXWSWESXX00250 1 ENTERPRISE SERVER - 250 Schneider Electric
SINGLE MODE FIBER SXWSWWORK00002 1 WRKSTN PRO 1 USER NO MAINT Schneider Electric
SERIAL (RS-485) 1 High availability virtual machines.
TYPICAL:

Electric. Their use or reproduction without prior consent of


PHX11 COLO Network Architecture 1 OF 3

These drawings and designs are the property of Schneider


PHX11-COLO1 CE1 THROUGH 4

the company is strictly forbidden.


PHX11-COLO(X)-CE(Y)-CAB01
PHX11 COLO(X) CELL(Y) MODULAR ELECTRICAL ROOM
PHX11-COLO(X)-CE(Y)-CEI-FEX(###) TAHUYA VLAN

TAHUYA TAHUYA
1 11 13 23 25 35 37 47

NETWORK 2 12 14 24 26 36 38 48 NETWORK

PHX11-COLO(X)-CE(Y)-CEI-FEX(###) BAS VLAN

1 11 13 23 25 35 37 47

BAS BAS
NETWORK 2 12 14 24 26 36 38 48 NETWORK

Date:
Preliminary
1 2 3 4 5 6 7 8 9 10 11 12

TX/RX+

TX/RX+

TX/RX+

TX/RX+
TX/RX-

TX/RX-

TX/RX-

TX/RX-
BIAS+
RET

RET

RET
UI16 UI16 UI8/AO-4-H UI16

RS232/RS485
Com A Com B RS-485 TP/FT

TAHUYA DEVICE
RS-485 LON
Schneider Electric Schneider Electric Schneider Electric Schneider Electric Schneider Electric Schneider Electric
SXW PS-24V SXW AS-P SXW IO SXW IO SXW IO SXW IO
PS-1 Device

5VDC

SL3 SL4 SL5 SL6


BATT
10/100 10/100
Host Ethernet 1 Ethernet 2

PHX11 COLO(X) CELL(Y) VRF


PHX11-COLO(X)-CE(Y)-CC01 MCG

DIII-NET

# Change:
Revision:
1 2 3 4 5 6 7 8 9 10 11 12

TX/RX+

TX/RX+

TX/RX+

TX/RX+
TX/RX-

TX/RX-

TX/RX-

TX/RX-
BIAS+
RET

RET

RET
UI16 UI16 UI8/AO-4-H AO-8-H DO-8-H

RS232/RS485
Com A Com B RS-485 TP/FT

TAHUYA DEVICE
RS-485 LON
Schneider Electric Schneider Electric Schneider Electric Schneider Electric Schneider Electric Schneider Electric Schneider Electric
SXW PS-24V SXW AS-P SXW IO SXW IO SXW IO SXW IO SXW IO
PS-1 Device

1
2
3
4
5
5VDC

Host
10/100 10/100
Ethernet 1 Ethernet 2
SL3 SL4 SL5 SL6 SL7

PHX11-COLO(X)-CE(Y)-AHU01-CP PHX11 COLO(X) CELL(Y) MECHNICAL GALLERY

1 2 3 4 5 6 7 8 9 10 11 12

TX/RX+

TX/RX+

TX/RX+

TX/RX+
TX/RX-

TX/RX-

TX/RX-

TX/RX-
BIAS+
RET

RET

RET
UI16 UI16 UI8/AO-4-H AO-8-H DO-8-H

RS232/RS485
Com A Com B RS-485 TP/FT

TAHUYA DEVICE
RS-485 LON
Schneider Electric Schneider Electric Schneider Electric Schneider Electric Schneider Electric Schneider Electric Schneider Electric
SXW PS-24V SXW AS-P SXW IO SXW IO SXW IO SXW IO SXW IO
PS-1

5/26/2022
5/26/2022
5/26/2022
Device

5VDC

Host
10/100 10/100
Ethernet 1 Ethernet 2
SL3 SL4 SL5 SL6 SL7

PHX11 COLO(X) CELL(Y) MECHNICAL GALLERY


PHX11-COLO(X)-CE(Y)-AHU02-CP

1 2 3 4 5 6 7 8 9 10 11 12

Date:
Date:
Date:
TX/RX+

TX/RX+

TX/RX+

TX/RX+
TX/RX-

TX/RX-

TX/RX-

TX/RX-
BIAS+
RET

RET

RET
UI16 UI16 UI8/AO-4-H AO-8-H DO-8-H

RS232/RS485
Com A Com B RS-485 TP/FT

TAHUYA DEVICE
RS-485 LON
Schneider Electric Schneider Electric Schneider Electric Schneider Electric Schneider Electric Schneider Electric Schneider Electric
SXW PS-24V SXW AS-P SXW IO SXW IO SXW IO SXW IO SXW IO
PS-1 Device

5VDC

Host
10/100 10/100
Ethernet 1 Ethernet 2
SL3 SL4 SL5 SL6 SL7

PHX11-COLO(X)-CE(Y)-AHU03-CP PHX11 COLO(X) CELL(Y) MECHNICAL GALLERY

Designed by:
Software by:
Checked by:
1 2 3 4 5 6 7 8 9 10 11 12

Contractor:
TX/RX+

TX/RX+

TX/RX+

TX/RX+
TX/RX-

TX/RX-

TX/RX-

TX/RX-
BIAS+
RET

RET

RET
UI16 UI16 UI8/AO-4-H AO-8-H DO-8-H

Engineer:
Architect:
RS232/RS485

Com A Com B RS-485 TP/FT


TAHUYA DEVICE

RS-485 LON
Schneider Electric Schneider Electric Schneider Electric Schneider Electric Schneider Electric Schneider Electric Schneider Electric
SXW PS-24V SXW AS-P SXW IO SXW IO SXW IO SXW IO SXW IO
PS-1 Device

5VDC

Host
10/100 10/100
Ethernet 1 Ethernet 2
SL3 SL4 SL5 SL6 SL7

PHX11 COLO(X) CELL(Y) MECHNICAL GALLERY

National And Strategic Accounts


PHX11-COLO(X)-CE(Y)-AHU04-CP

PHX11 COLO Network


Architecture 1 OF 3
1 2 3 4 5 6 7 8 9 10 11 12

TX/RX+

TX/RX+

TX/RX+

TX/RX+
TX/RX-

TX/RX-

TX/RX-

TX/RX-
BIAS+
RET

RET

RET
UI16 UI16 UI8/AO-4-H AO-8-H DO-8-H
RS232/RS485

Com A Com B RS-485 TP/FT


TAHUYA DEVICE

RS-485 LON
Schneider Electric Schneider Electric Schneider Electric Schneider Electric Schneider Electric Schneider Electric Schneider Electric
SXW PS-24V SXW AS-P SXW IO SXW IO SXW IO SXW IO SXW IO
PS-1 Device

5VDC

Host
10/100 10/100
Ethernet 1 Ethernet 2
SL3 SL4 SL5 SL6 SL7

PHX11-COLO(X)-CE(Y)-AHU05-CP PHX11 COLO(X) CELL(Y) MECHNICAL GALLERY

1 2 3 4 5 6 7 8 9 10 11 12
TX/RX+

TX/RX+

TX/RX+

TX/RX+
TX/RX-

TX/RX-

TX/RX-

TX/RX-
BIAS+
RET

RET

RET

UI16 UI16 UI8/AO-4-H AO-8-H DO-8-H


RS232/RS485

Com A Com B RS-485 TP/FT


TAHUYA DEVICE

RS-485 LON
Schneider Electric Schneider Electric Schneider Electric Schneider Electric Schneider Electric Schneider Electric Schneider Electric
SXW PS-24V SXW AS-P SXW IO SXW IO SXW IO SXW IO SXW IO
PS-1 Device

5VDC

Host
10/100 10/100
Ethernet 1 Ethernet 2
SL3 SL4 SL5 SL6 SL7

PHX11-COLO(X)-CE(Y)-AHU06-CP PHX11 COLO(X) CELL(Y) MECHNICAL GALLERY

5/27/2022

5/27/2022
Last Printed
Last Saved
1 2 3 4 5 6 7 8 9 10 11 12
TX/RX+

TX/RX+

TX/RX+

TX/RX+
TX/RX-

TX/RX-

TX/RX-

TX/RX-
BIAS+
RET

RET

RET

UI16 UI16 UI8/AO-4-H AO-8-H DO-8-H


RS232/RS485

Com A Com B RS-485 TP/FT


TAHUYA DEVICE

RS-485 LON
Schneider Electric Schneider Electric Schneider Electric Schneider Electric Schneider Electric Schneider Electric Schneider Electric
SXW PS-24V SXW AS-P SXW IO SXW IO SXW IO SXW IO SXW IO
PS-1 Device

5VDC

Host
10/100 10/100
Ethernet 1 Ethernet 2
SL3 SL4 SL5 SL6 SL7

NETWORK CABLE LEGEND

Job Number
PHX11 COLO(X) CELL(Y) MECHNICAL GALLERY

201 Network Architecture.vsd


PHX11-COLO(X)-CE(Y)-AHU07-CP
TAHUYA BUILDING NETWORK

Sheet Number
BAS CAMPUS NETWORK 1 2 3 4 5 6 7 8 9 10 11 12
TX/RX+

TX/RX+

TX/RX+

TX/RX+

File Name
TX/RX-

TX/RX-

TX/RX-

TX/RX-
BIAS+
RET

RET

RET

UI16 UI16 UI8/AO-4-H AO-8-H DO-8-H

201-2
RS232/RS485

BAS CAT6 ETHERNET Com A Com B RS-485 TP/FT


TAHUYA DEVICE

RS-485 LON
Schneider Electric Schneider Electric Schneider Electric Schneider Electric Schneider Electric Schneider Electric Schneider Electric
SXW PS-24V SXW AS-P SXW IO SXW IO SXW IO SXW IO SXW IO

TAHUYA CAT6 ETHERNET PS-1 Device

5VDC

SINGLE MODE FIBER Host


10/100 10/100
Ethernet 1 Ethernet 2
SL3 SL4 SL5 SL6 SL7

SERIAL (RS-485) PHX11 COLO(X) CELL(Y) MECHNICAL GALLERY


PHX11-COLO(X)-CE(Y)-AHU08-CP
TYPICAL:

Electric. Their use or reproduction without prior consent of


PHX11 COLO Network Architecture 2 OF 3

These drawings and designs are the property of Schneider


PHX11-COLO2 THROUGH 5 CE1 AND 4

the company is strictly forbidden.


PHX11-COLO(X)-CE(Y)-CAB01
PHX11 COLO(X) CELL(Y) MODULAR ELECTRICAL ROOM
PHX11-COLO(X)-CE(Y)-CEI-FEX(###) TAHUYA VLAN

TAHUYA TAHUYA
1 11 13 23 25 35 37 47

NETWORK 2 12 14 24 26 36 38 48 NETWORK

PHX11-COLO(X)-CE(Y)-CEI-FEX(###) BAS VLAN

1 11 13 23 25 35 37 47

BAS BAS
NETWORK 2 12 14 24 26 36 38 48 NETWORK

Date:
Preliminary
1 2 3 4 5 6 7 8 9 10 11 12

TX/RX+

TX/RX+

TX/RX+

TX/RX+
TX/RX-

TX/RX-

TX/RX-

TX/RX-
BIAS+
RET

RET

RET
UI16 UI16 UI16 UI16 UI16 AO-8-H

RS232/RS485
Com A Com B RS-485 TP/FT

TAHUYA DEVICE
RS-485 LON
Schneider Electric Schneider Electric Schneider Electric Schneider Electric Schneider Electric Schneider Electric Schneider Electric Schneider Electric
SXW PS-24V SXW AS-P SXW IO SXW IO SXW IO SXW IO SXW IO SXW IO
PS-1 Device

5VDC

SL3 SL4 SL5 SL6 SL7 SL8


BATT
10/100 10/100
Host Ethernet 1 Ethernet 2

PHX11 COLO(X) CELL(Y) VRF


PHX11-COLO(X)-CE(Y)-CC01 MCG

DIII-NET

# Change:
Revision:
1 2 3 4 5 6 7 8 9 10 11 12

TX/RX+

TX/RX+

TX/RX+

TX/RX+
TX/RX-

TX/RX-

TX/RX-

TX/RX-
BIAS+
RET

RET

RET
UI16 UI16 UI8/AO-4-H AO-8-H DO-8-H

RS232/RS485
Com A Com B RS-485 TP/FT

TAHUYA DEVICE
RS-485 LON
Schneider Electric Schneider Electric Schneider Electric Schneider Electric Schneider Electric Schneider Electric Schneider Electric
SXW PS-24V SXW AS-P SXW IO SXW IO SXW IO SXW IO SXW IO
PS-1 Device

1
2
3
4
5
5VDC

Host
10/100 10/100
Ethernet 1 Ethernet 2
SL3 SL4 SL5 SL6 SL7

PHX11-COLO(X)-CE(Y)-AHU01-CP PHX11 COLO(X) CELL(Y) MECHNICAL GALLERY

1 2 3 4 5 6 7 8 9 10 11 12

TX/RX+

TX/RX+

TX/RX+

TX/RX+
TX/RX-

TX/RX-

TX/RX-

TX/RX-
BIAS+
RET

RET

RET
UI16 UI16 UI8/AO-4-H AO-8-H DO-8-H

RS232/RS485
Com A Com B RS-485 TP/FT

TAHUYA DEVICE
RS-485 LON
Schneider Electric Schneider Electric Schneider Electric Schneider Electric Schneider Electric Schneider Electric Schneider Electric
SXW PS-24V SXW AS-P SXW IO SXW IO SXW IO SXW IO SXW IO
PS-1

5/26/2022
5/26/2022
5/26/2022
Device

5VDC

Host
10/100 10/100
Ethernet 1 Ethernet 2
SL3 SL4 SL5 SL6 SL7

PHX11 COLO(X) CELL(Y) MECHNICAL GALLERY


PHX11-COLO(X)-CE(Y)-AHU02-CP

1 2 3 4 5 6 7 8 9 10 11 12

Date:
Date:
Date:
TX/RX+

TX/RX+

TX/RX+

TX/RX+
TX/RX-

TX/RX-

TX/RX-

TX/RX-
BIAS+
RET

RET

RET
UI16 UI16 UI8/AO-4-H AO-8-H DO-8-H

RS232/RS485
Com A Com B RS-485 TP/FT

TAHUYA DEVICE
RS-485 LON
Schneider Electric Schneider Electric Schneider Electric Schneider Electric Schneider Electric Schneider Electric Schneider Electric
SXW PS-24V SXW AS-P SXW IO SXW IO SXW IO SXW IO SXW IO
PS-1 Device

5VDC

Host
10/100 10/100
Ethernet 1 Ethernet 2
SL3 SL4 SL5 SL6 SL7

PHX11-COLO(X)-CE(Y)-AHU03-CP PHX11 COLO(X) CELL(Y) MECHNICAL GALLERY

Designed by:
Software by:
Checked by:
1 2 3 4 5 6 7 8 9 10 11 12

Contractor:
TX/RX+

TX/RX+

TX/RX+

TX/RX+
TX/RX-

TX/RX-

TX/RX-

TX/RX-
BIAS+
RET

RET

RET
UI16 UI16 UI8/AO-4-H AO-8-H DO-8-H

Engineer:
Architect:
RS232/RS485

Com A Com B RS-485 TP/FT


TAHUYA DEVICE

RS-485 LON
Schneider Electric Schneider Electric Schneider Electric Schneider Electric Schneider Electric Schneider Electric Schneider Electric
SXW PS-24V SXW AS-P SXW IO SXW IO SXW IO SXW IO SXW IO
PS-1 Device

5VDC

Host
10/100 10/100
Ethernet 1 Ethernet 2
SL3 SL4 SL5 SL6 SL7

PHX11 COLO(X) CELL(Y) MECHNICAL GALLERY

National And Strategic Accounts


PHX11-COLO(X)-CE(Y)-AHU04-CP

PHX11 COLO Network


Architecture 2 OF 3
1 2 3 4 5 6 7 8 9 10 11 12

TX/RX+

TX/RX+

TX/RX+

TX/RX+
TX/RX-

TX/RX-

TX/RX-

TX/RX-
BIAS+
RET

RET

RET
UI16 UI16 UI8/AO-4-H AO-8-H DO-8-H
RS232/RS485

Com A Com B RS-485 TP/FT


TAHUYA DEVICE

RS-485 LON
Schneider Electric Schneider Electric Schneider Electric Schneider Electric Schneider Electric Schneider Electric Schneider Electric
SXW PS-24V SXW AS-P SXW IO SXW IO SXW IO SXW IO SXW IO
PS-1 Device

5VDC

Host
10/100 10/100
Ethernet 1 Ethernet 2
SL3 SL4 SL5 SL6 SL7

PHX11-COLO(X)-CE(Y)-AHU05-CP PHX11 COLO(X) CELL(Y) MECHNICAL GALLERY

1 2 3 4 5 6 7 8 9 10 11 12
TX/RX+

TX/RX+

TX/RX+

TX/RX+
TX/RX-

TX/RX-

TX/RX-

TX/RX-
BIAS+
RET

RET

RET

UI16 UI16 UI8/AO-4-H AO-8-H DO-8-H


RS232/RS485

Com A Com B RS-485 TP/FT


TAHUYA DEVICE

RS-485 LON
Schneider Electric Schneider Electric Schneider Electric Schneider Electric Schneider Electric Schneider Electric Schneider Electric
SXW PS-24V SXW AS-P SXW IO SXW IO SXW IO SXW IO SXW IO
PS-1 Device

5VDC

Host
10/100 10/100
Ethernet 1 Ethernet 2
SL3 SL4 SL5 SL6 SL7

PHX11-COLO(X)-CE(Y)-AHU06-CP PHX11 COLO(X) CELL(Y) MECHNICAL GALLERY

5/27/2022

5/27/2022
Last Printed
Last Saved
1 2 3 4 5 6 7 8 9 10 11 12
TX/RX+

TX/RX+

TX/RX+

TX/RX+
TX/RX-

TX/RX-

TX/RX-

TX/RX-
BIAS+
RET

RET

RET

UI16 UI16 UI8/AO-4-H AO-8-H DO-8-H


RS232/RS485

Com A Com B RS-485 TP/FT


TAHUYA DEVICE

RS-485 LON
Schneider Electric Schneider Electric Schneider Electric Schneider Electric Schneider Electric Schneider Electric Schneider Electric
SXW PS-24V SXW AS-P SXW IO SXW IO SXW IO SXW IO SXW IO
PS-1 Device

5VDC

Host
10/100 10/100
Ethernet 1 Ethernet 2
SL3 SL4 SL5 SL6 SL7

NETWORK CABLE LEGEND

Job Number
PHX11 COLO(X) CELL(Y) MECHNICAL GALLERY

201 Network Architecture.vsd


PHX11-COLO(X)-CE(Y)-AHU07-CP
TAHUYA BUILDING NETWORK

Sheet Number
BAS CAMPUS NETWORK 1 2 3 4 5 6 7 8 9 10 11 12
TX/RX+

TX/RX+

TX/RX+

TX/RX+

File Name
TX/RX-

TX/RX-

TX/RX-

TX/RX-
BIAS+
RET

RET

RET

UI16 UI16 UI8/AO-4-H AO-8-H DO-8-H

201-3
RS232/RS485

BAS CAT6 ETHERNET Com A Com B RS-485 TP/FT


TAHUYA DEVICE

RS-485 LON
Schneider Electric Schneider Electric Schneider Electric Schneider Electric Schneider Electric Schneider Electric Schneider Electric
SXW PS-24V SXW AS-P SXW IO SXW IO SXW IO SXW IO SXW IO

TAHUYA CAT6 ETHERNET PS-1 Device

5VDC

SINGLE MODE FIBER Host


10/100 10/100
Ethernet 1 Ethernet 2
SL3 SL4 SL5 SL6 SL7

SERIAL (RS-485) PHX11 COLO(X) CELL(Y) MECHNICAL GALLERY


PHX11-COLO(X)-CE(Y)-AHU08-CP
TYPICAL:

Electric. Their use or reproduction without prior consent of


PHX11 COLO Network Architecture 3 OF 3

These drawings and designs are the property of Schneider


PHX11-COLO2 THROUGH 5 CE2 AND 3

the company is strictly forbidden.


PHX11-COLO(X)-CE(Y)-CAB01
PHX11 COLO(X) CELL(Y) MODULAR ELECTRICAL ROOM
PHX11-COLO(X)-CE(Y)-CEI-FEX(###) TAHUYA VLAN

TAHUYA TAHUYA
1 11 13 23 25 35 37 47

NETWORK 2 12 14 24 26 36 38 48 NETWORK

PHX11-COLO(X)-CE(Y)-CEI-FEX(###) BAS VLAN

1 11 13 23 25 35 37 47

BAS BAS
NETWORK 2 12 14 24 26 36 38 48 NETWORK

Date:
Preliminary
BATT
VRF
MCG

DIII-NET

# Change:
Revision:
1 2 3 4 5 6 7 8 9 10 11 12

TX/RX+

TX/RX+

TX/RX+

TX/RX+
TX/RX-

TX/RX-

TX/RX-

TX/RX-
BIAS+
RET

RET

RET
UI16 UI16 UI8/AO-4-H AO-8-H DO-8-H

RS232/RS485
Com A Com B RS-485 TP/FT

TAHUYA DEVICE
RS-485 LON
Schneider Electric Schneider Electric Schneider Electric Schneider Electric Schneider Electric Schneider Electric Schneider Electric
SXW PS-24V SXW AS-P SXW IO SXW IO SXW IO SXW IO SXW IO
PS-1 Device

1
2
3
4
5
5VDC

Host
10/100 10/100
Ethernet 1 Ethernet 2
SL3 SL4 SL5 SL6 SL7

PHX11-COLO(X)-CE(Y)-AHU01-CP PHX11 COLO(X) CELL(Y) MECHNICAL GALLERY

1 2 3 4 5 6 7 8 9 10 11 12

TX/RX+

TX/RX+

TX/RX+

TX/RX+
TX/RX-

TX/RX-

TX/RX-

TX/RX-
BIAS+
RET

RET

RET
UI16 UI16 UI8/AO-4-H AO-8-H DO-8-H

RS232/RS485
Com A Com B RS-485 TP/FT

TAHUYA DEVICE
RS-485 LON
Schneider Electric Schneider Electric Schneider Electric Schneider Electric Schneider Electric Schneider Electric Schneider Electric
SXW PS-24V SXW AS-P SXW IO SXW IO SXW IO SXW IO SXW IO
PS-1

5/26/2022
5/26/2022
5/26/2022
Device

5VDC

Host
10/100 10/100
Ethernet 1 Ethernet 2
SL3 SL4 SL5 SL6 SL7

PHX11 COLO(X) CELL(Y) MECHNICAL GALLERY


PHX11-COLO(X)-CE(Y)-AHU02-CP

1 2 3 4 5 6 7 8 9 10 11 12

Date:
Date:
Date:
TX/RX+

TX/RX+

TX/RX+

TX/RX+
TX/RX-

TX/RX-

TX/RX-

TX/RX-
BIAS+
RET

RET

RET
UI16 UI16 UI8/AO-4-H AO-8-H DO-8-H

RS232/RS485
Com A Com B RS-485 TP/FT

TAHUYA DEVICE
RS-485 LON
Schneider Electric Schneider Electric Schneider Electric Schneider Electric Schneider Electric Schneider Electric Schneider Electric
SXW PS-24V SXW AS-P SXW IO SXW IO SXW IO SXW IO SXW IO
PS-1 Device

5VDC

Host
10/100 10/100
Ethernet 1 Ethernet 2
SL3 SL4 SL5 SL6 SL7

PHX11-COLO(X)-CE(Y)-AHU03-CP PHX11 COLO(X) CELL(Y) MECHNICAL GALLERY

Designed by:
Software by:
Checked by:
1 2 3 4 5 6 7 8 9 10 11 12

Contractor:
TX/RX+

TX/RX+

TX/RX+

TX/RX+
TX/RX-

TX/RX-

TX/RX-

TX/RX-
BIAS+
RET

RET

RET
UI16 UI16 UI8/AO-4-H AO-8-H DO-8-H

Engineer:
Architect:
RS232/RS485

Com A Com B RS-485 TP/FT


TAHUYA DEVICE

RS-485 LON
Schneider Electric Schneider Electric Schneider Electric Schneider Electric Schneider Electric Schneider Electric Schneider Electric
SXW PS-24V SXW AS-P SXW IO SXW IO SXW IO SXW IO SXW IO
PS-1 Device

5VDC

Host
10/100 10/100
Ethernet 1 Ethernet 2
SL3 SL4 SL5 SL6 SL7

PHX11 COLO(X) CELL(Y) MECHNICAL GALLERY

National And Strategic Accounts


PHX11-COLO(X)-CE(Y)-AHU04-CP

PHX11 COLO Network


Architecture 3 OF 3
1 2 3 4 5 6 7 8 9 10 11 12

TX/RX+

TX/RX+

TX/RX+

TX/RX+
TX/RX-

TX/RX-

TX/RX-

TX/RX-
BIAS+
RET

RET

RET
UI16 UI16 UI8/AO-4-H AO-8-H DO-8-H
RS232/RS485

Com A Com B RS-485 TP/FT


TAHUYA DEVICE

RS-485 LON
Schneider Electric Schneider Electric Schneider Electric Schneider Electric Schneider Electric Schneider Electric Schneider Electric
SXW PS-24V SXW AS-P SXW IO SXW IO SXW IO SXW IO SXW IO
PS-1 Device

5VDC

Host
10/100 10/100
Ethernet 1 Ethernet 2
SL3 SL4 SL5 SL6 SL7

PHX11-COLO(X)-CE(Y)-AHU05-CP PHX11 COLO(X) CELL(Y) MECHNICAL GALLERY

1 2 3 4 5 6 7 8 9 10 11 12
TX/RX+

TX/RX+

TX/RX+

TX/RX+
TX/RX-

TX/RX-

TX/RX-

TX/RX-
BIAS+
RET

RET

RET

UI16 UI16 UI8/AO-4-H AO-8-H DO-8-H


RS232/RS485

Com A Com B RS-485 TP/FT


TAHUYA DEVICE

RS-485 LON
Schneider Electric Schneider Electric Schneider Electric Schneider Electric Schneider Electric Schneider Electric Schneider Electric
SXW PS-24V SXW AS-P SXW IO SXW IO SXW IO SXW IO SXW IO
PS-1 Device

5VDC

Host
10/100 10/100
Ethernet 1 Ethernet 2
SL3 SL4 SL5 SL6 SL7

PHX11-COLO(X)-CE(Y)-AHU06-CP PHX11 COLO(X) CELL(Y) MECHNICAL GALLERY

5/27/2022

5/27/2022
Last Printed
Last Saved
1 2 3 4 5 6 7 8 9 10 11 12
TX/RX+

TX/RX+

TX/RX+

TX/RX+
TX/RX-

TX/RX-

TX/RX-

TX/RX-
BIAS+
RET

RET

RET

UI16 UI16 UI8/AO-4-H AO-8-H DO-8-H


RS232/RS485

Com A Com B RS-485 TP/FT


TAHUYA DEVICE

RS-485 LON
Schneider Electric Schneider Electric Schneider Electric Schneider Electric Schneider Electric Schneider Electric Schneider Electric
SXW PS-24V SXW AS-P SXW IO SXW IO SXW IO SXW IO SXW IO
PS-1 Device

5VDC

Host
10/100 10/100
Ethernet 1 Ethernet 2
SL3 SL4 SL5 SL6 SL7

NETWORK CABLE LEGEND

Job Number
PHX11 COLO(X) CELL(Y) MECHNICAL GALLERY

201 Network Architecture.vsd


PHX11-COLO(X)-CE(Y)-AHU07-CP
TAHUYA BUILDING NETWORK

Sheet Number
BAS CAMPUS NETWORK 1 2 3 4 5 6 7 8 9 10 11 12
TX/RX+

TX/RX+

TX/RX+

TX/RX+

File Name
TX/RX-

TX/RX-

TX/RX-

TX/RX-
BIAS+
RET

RET

RET

UI16 UI16 UI8/AO-4-H AO-8-H DO-8-H

201-4
RS232/RS485

BAS CAT6 ETHERNET Com A Com B RS-485 TP/FT


TAHUYA DEVICE

RS-485 LON
Schneider Electric Schneider Electric Schneider Electric Schneider Electric Schneider Electric Schneider Electric Schneider Electric
SXW PS-24V SXW AS-P SXW IO SXW IO SXW IO SXW IO SXW IO

TAHUYA CAT6 ETHERNET PS-1 Device

5VDC

SINGLE MODE FIBER Host


10/100 10/100
Ethernet 1 Ethernet 2
SL3 SL4 SL5 SL6 SL7

SERIAL (RS-485) PHX11 COLO(X) CELL(Y) MECHNICAL GALLERY


PHX11-COLO(X)-CE(Y)-AHU08-CP
1

SL4
EF01.SS
NO1
COM
TB4-17
T4-9AC
N
120 VAC
L

R1

EF01
R2

TB4-2
TB4-1
UI1
RET
SL4

Exhaust Air
EF01.STS
Compactor Room Hydrogen Sensor Flow Diagram

Alarm
Hydrogen

HDT

L
N
TB4-8
TB4-7
RET

Shunt Trip
ST

Forklift Charger
Integral
SL4

Horn/Strobe
UI4 EF01-HDT01.ALM
ADMIN Systems Diagrams

N
120 VAC
L

EF02
Admin Toilet Exhaust Fan Diagram

TB4-4
TB4-3
UI2
RET
SL4

Exhaust Air
EF02.STS

Job Number
National And Strategic Accounts Architect:
Revision: Preliminary
Engineer:
# Change: Date:
File Name Last Saved Contractor:
1
301 ADMIN Flow Diagram.vsd 5/27/2022 Designed by: Date: 5/26/2022 2
3 These drawings and designs are the property of Schneider
Sheet Number Last Printed Software by: Date: 5/26/2022 Electric. Their use or reproduction without prior consent of
4
the company is strictly forbidden.
ADMIN Systems Diagrams Checked by: Date: 5/26/2022 5
301-1 5/27/2022
Mounted in Panel

Electric. Their use or reproduction without prior consent of


COLO-AHU System Diagram

These drawings and designs are the property of Schneider


PH01.HS UI3 TB5:31
SL5 RET TB5:32 4
8 12

the company is strictly forbidden.


2 TBPA
Mounted in Panel
PD01 Actuator Power 6 10 X5H
Set Reset PB1
1
TB3:9 UI5 PD01.FB 13 LR1 14 9 LR1 12 NO COM
5 9 X4N TBPA
R1:6 X3H SL5 X3H TBPA
TB5:18 X4N
PD01 PD01.CMD
TB5:17 VO1 LR1-1

14

13
R1
1 10
1.6.3a
RLFA-A N.C.
NO COM Mounted in Panel
H L
PH01
Set @ 0.3"

RLFA-B N.C.
1.6.3b

Date:
R1:6 X3H SL5
PD01
TB5:18 X4N

Preliminary
TB5:17 VO1 PD01.CMD
TB3:9 UI5 PD01.FB

Mechanical Gallery
VO2 TB6:3 N.O.
TD03.CMD
X6N TB6:4 TD03
SL6 X5H TB6:2AC
TD03.FB UI3 TB3:3 1.6.2

# Change:
Revision:
TD01.FB UI3 TB3:5 FT01.SAF
TD01.CMD VO3 TB6:5 TT02.MAT SL3 NT01.SAH TT01.SAT
X6N TB6:6 RA SL3 UI13 RET SL3 SL3
SL6

1
2
3
4
5
X5H TB6:3AC UI10 Y1+ UI11 Y1+ UI1 Y1+
TB3:25 TB3:26
TB3:13 UI7 ND01.FB
TB3:19 TB3:10DC TB3:21 TB3:11DC TB3:1 TB3:1DC
TB6:7AC X5H SL6
1.6.11 + -
- + TB6:14 X6N 4-20mA VIN - +
TD01 ND01 ND01.CMD FT01
TT02 TB6:13 VO7 NT01 TT01
3 EC

1.6.1a OA N.O. SA
N.C.

5/26/2022
5/26/2022
5/26/2022
TBx:## UI# SF0#.STS NT02
N.O. 1.6.12 SF##
TBx:## RET SL# 4-20mA VIN
1.6.1b OA
N.C. VO8 TB6:15 X4N TBPA Typical of 6

+ -
ND02.CMD ND02 WS01 TB3:23 TB3:12DC
X6N TB6:16 X3H TBPA
SL6
TD02.CMD VO4 TB6:7
TD02
X5H TB6:8AC NO C
1.1.2 SC01
TB7:15 NO5 SC01.SS UI12 Y1+
X6N TB6:8 ND02.FB UI8 TB3:15 TB7:14 X8N SL7 SL3

Date:
Date:
Date:
SL6 1.1.3
X5H TB6:4AC X4N TBPA TB4:1 TB4:2 SC01.FB UI14 TB3:27 TB6:1 VO1 SC01.SPD NT02.SAH
+ -

WS02
TD02.FB UI4 TB3:7 X3H TBPA SL3 RET TB3:28 VFD TB6:2 RET SL6
UI1 RET
NO C SC01.FLT UI16 TB4:31
SL4
SL4 RET TB4:32
WS01.WD
TB4:3 TB4:4 TB4:29 UI15 SC01.STS
TB4:30 RET SL4
UI2 RET
SL4

Designed by:
Software by:
Checked by:
WS02.WD

Contractor:
Engineer:
Architect:

COLO-AHU System Diagram


National And Strategic Accounts
DESIGNATION EBO POINT NAME DESCRIPTION SIGNAL TYPE UNIT RANGE
AI-01 TT01.SAT AHU SUPPLY AIR TEMP TBD °F 32-122
AI-02 TD03.FB RETURN AIR DAMPER FEEDBACK 2-10 VDC % 0-100
AI-03 TD01.FB OUTSIDE AIR DAMPER A FEEDBACK 2-10 VDC % 0-100
AI-04 TD02.FB OUTSIDE AIR DAMPER B FEEDBACK 2-10 VDC % 0-100
AI-05 PD01.FB RELIEF AIR DAMPER A FEEDBACK 2-10 VDC % 0-100
AI-06 PD02.FB RELIEF AIR DAMPER B FEEDBACK 2-10 VDC % 0-100
Evaporative Cooler Detail AI-07 ND01.FB FACE DAMPER FEEDBACK TBD % 0-100
AI-08 ND02.FB BYPASS DAMPER FEEDBACK TBD % 0-100
LCV01.FB UI3 TB4:5
SL4 RET TB4:6
AI-09 CT01.CON CONDUCTIVITY TBD µs 0-10,000
CT01.CON UI9 TB3:17 AI-10 TT02.MAT MIXED AIR TEMP TBD °F 32-122
LCV01.OC NO1 TB7:3 SL3 RET TB3:18
SL7 X8N TB7:2
LCV01 N.C.
- +
AI-11 NT01.SAH SUPPLY AIR HUMIDITY 01 TBD %RH 0-100
NPW EC X4N TBPA AI-12 NT02.SAH SUPPLY AIR HUMIDITY 02 TBD %RH 0-100
+ -

CT01

5/27/2022

5/27/2022
LL01.LL UI7 TB4:13 X3H TBPA TB7:9 NO3 CCV01.OC

Last Printed
AI-13 FT01.SAF SUPPLY AIR FLOW TBD CFM 0-50,000

Last Saved
CCV01
SL4 RET TB4:14 TB7:8 X8N SL7
HL OL LL
LN01.NL UI5 TB4:9 Bleed AI-14 SC01.FB SUPPLY FAN SPEED FEEDBACK TBD % 0-100
SL4 RET TB4:10
LH01.HL UI6 TB4:11 Overflow
AO-01 SC01.SPD SUPPLY FAN SPEED COMMAND TBD % 0-100
SL4 RET TB4:12 EC Basin P1 AO-02 TD03.CMD RETURN AIR DAMPER COMMAND 2-10 VDC % 0-100

Job Number
N.O.

302 AHU Flow Diagram.vsd


Drain AO-03 TD01.CMD OUTSIDE AIR DAMPER A COMMAND 2-10 VDC % 0-100
TB7:6 NO2 LCV02.OC
TB7:12 NO4 EP01.SS LCV02 AO-04 TD02.CMD OUTSIDE AIR DAMPER B COMMAND 2-10 VDC % 0-100

Sheet Number
EP01 TB7:5 X8N SL7
TB7:11 X8N SL7

File Name
AO-05 PD01.CMD RELIEF AIR DAMPER A COMMAND 2-10 VDC % 0-100

302-1
TB4:15 UI8 EP01.STS
EP01 TB4:7 UI4 LCV02.FB
TB4:16 RET SL4 AO-06 PD02.CMD RELIEF AIR DAMPER B COMMAND 2-10 VDC % 0-100
TB4:8 RET SL4
AO-07 ND01.CMD FACE DAMPER COMMAND TBD % 0-100
AO-08 ND02.CMD BYPASS DAMPER COMMAND TBD % 0-100
Electric. Their use or reproduction without prior consent of
COLO System Diagram

These drawings and designs are the property of Schneider

the company is strictly forbidden.


Mounted in Panel
PH01.HS UI3 TB5:31
SL5 RET TB5:32 4
8 12

Date:
2 TBPA
Mounted in Panel
PD01 Actuator Power 6 10 X5H
PB1

Preliminary
Set Reset
1
TB3:9 UI5 PD01.FB 13 LR1 14 9 LR1 12 NO COM
PD02 Actuator Power 5 9 X4N TBPA
R1:6 X3H SL6 X3H TBPA
TB6:18 X4N
PD01 PD01.CMD
TB5:17 VO1 LR1-1

14

13
R1
1 10
1.6.3a
RLFA N.C.
NO COM Mounted in Panel
H L
PH01
Set @ 0.3"

RLFA N.C.
1.6.3b

# Change:
Revision:
TB5:19 VO2 PD02.CMD
PD02
TB5:20 X4N
R1:5 X3H SL5
TB3:11 UI6 PD02.FB

1
2
3
4
5
5/26/2022
5/26/2022
5/26/2022
Date:
Date:
Date:
Designed by:
Software by:
Checked by:
Contractor:
Engineer:
Architect:
National And Strategic Accounts

COLO System Diagram


5/27/2022

5/27/2022
Last Printed
Last Saved
Job Number

303 COLO Flow Diagram.vsd

Sheet Number
File Name
DESIGNATION EBO POINT NAME DESCRIPTION SIGNAL TYPE UNIT RANGE

303-1
AI-28 PD01.FB RELIEF DAMPER 01 FEEDBACK 2-10 VDC % 0-100
AI-29 PD02.FB RELIEF DAMPER 02 FEEDBACK 2-10 VDC % 0-100
AO-01 PD01.CMD RELIEF DAMPER 01 COMMAND 2-10 VDC % 0-100
AO-02 PD02.CMD RELIEF DAMPER 02 COMMAND 2-10 VDC % 0-100
Electric. Their use or reproduction without prior consent of
ADMIN Floorplan

These drawings and designs are the property of Schneider

the company is strictly forbidden.


PHX11-COLO-CE1-EH01
KEYED NOTES:
1. Install hydrogen sensor above
battery charging station near the
exhaust intake vent. Install hydrogen
transmitter in accessible location on
wall..

2. Field verify panel locations with


T
other trades.

Date:
C T 3. Equipment vendor to provide and

Preliminary
configure BACnet/IP-capable
controller for connection to BAS.
T T C Coordinate points list with control
EF C contractor. Gateway device by
others.
EF
4. Mount VRF gateway inside an
enclosure per manufacturer’s
instruction. Touchscreen controller/

# Change:
Revision:
HMI shall be mounted on the front
panel of the same enclosure.

1
2
3
4
5
5. Duct heater controlled by COLO1
CELL1 central controller.

6. Gateway panel, including EPMS-


EF BAS gateway and VRF gateway, is by
others. Power provided for both

5/26/2022
5/26/2022
5/26/2022
devices from PHX11-ADMIN-CC01
panel.

Date:
Date:
Date:
Designed by:
Software by:
Checked by:
Contractor:
Engineer:
Architect:
N

National And Strategic Accounts

ADMIN Floorplan
LEGEND

T = CONTROL PANEL

5/27/2022

5/27/2022
Last Printed
EFE

Last Saved
F = EXHAUST FAN
F ADMIN
H2 H2
TT = TEMPERATURE Device Qty Part Number Description Manufacturer
----------------------------------------------------------------------------------------------------------------------------------------------------

Job Number
H2H = HYDROGEN ###-FT01 2 FT-3215-21112-1021 In-line EM Flow Meter, 1.5 in. Onicon

401 ADMIN Floorplan.vsd


CDT## 3 CWE ROOM CO2 TRANS Veris Industries
EF01 1 V100 RELAY ENCLOSED SPDT 10-30V Veris Industries
CC = CARBONDIOXIDE

Sheet Number
EF## 3 H608 CURRENT SWITCH N.O. SPLIT CORE Veris Industries

File Name
EF01-HDT01 1 869-STR-B-AQ Strobe Light, Blue Edwards Signaling

401-1
EF01-HDT01 1 KEL-GDD-H2 HYDROGEN DETECTOR Kele
FF = FLOW METER EF01-HDT01 1 V300 RELAY ENCLOSED DPDT 20-30V Veris Industries
TT## 4 A/TTM1K-4-R2-4 Room Air Temp Sensor, Matched ACI
Electric. Their use or reproduction without prior consent of
COLO 1 CELL 2 & 4 Floorplan

These drawings and designs are the property of Schneider

the company is strictly forbidden.


KEYED NOTES:
1. BAS central controller and differential pressure
transmitter panels mount on a freestanding rack
adjacent to the corridor, all conduit shall be fed
from the top of the panels.

2. Clear window provided on the differential


pressure transmitter panel to allow viewing of
displays without opening panel door.

3. Refer to Detail 2/PHX11-P-G-01-0 in PHX11


MECH Plans for plumbing schematic and location

Date:
of flow meters and pressure transmitters.

Preliminary
4. Field verify panel location with other trades.

5. Mount gateway provided by VRF equipment


vendor inside an enclosure as required per
manufacturer’s instruction. Touchscreen
controller/HMI shall be mounted on the front panel
of the same enclosure. Configure BACnet/IP-
capable controller for connection to BAS.

6. VRF equipment vendor to provide and configure


A A A A A A A A A A A A A A A A VRF network from VRF equipment to VRF
gateway device as required. Coordinate VRF
A A A A A A A A A A A A A A A A

# Change:
equipment points list with controls contractor.

Revision:
L L L L L L L L L L L L L L L L Reference VRF detail.
CS CS CS CS CS CS CS CS CS CS CS CS CS CS CS CS
R R R R R R R R R R R R R R R R

1
2
3
4
5
5/26/2022
5/26/2022
5/26/2022
T C T T CT

Date:
Date:
Date:
P P P P P P P P P P P P P P P P P P P P

T T T T T T T T T T T T T T T T T T T T T T
H
P
H H
P
H H
P
H H
P
H H
P
H H
P
H N

Designed by:
Software by:
Checked by:
Contractor:
Engineer:
Architect:
T T
COLO 1 CELL 2
Device Qty Part Number Description Manufacturer
----------------------------------------------------------------------------------------------------------------------------------------------------

National And Strategic Accounts


##.SS + .O + .C 56 V100 RELAY ENCLOSED SPDT 10-30V Veris Industries
CO 1 CO-R-4X-RB-D CO Room Mount with Display, Re ACI
NPW-FT01 1 FT-3204-21112-1021 In-line EM Flow Meter, 4 in., Onicon

COLO 1 CELL 2 & 4


NPW-PT01 1 KEL-PTX1-09 STAINLESS 0-200psi/4-20 MA Kele
PD## 6 AFB24-SR Modulating, Spring Return, AC Belimo
LEGEND PT##-CA 5 AA56 STAINLESS PLATE/STATIC PRESSUR Veris Industries

Floorplan
PT##-HA 8 AA56 STAINLESS PLATE/STATIC PRESSUR Veris Industries
PT06-OA 1 SPH20 STATIC PRESSURE HEAD HEATED Vaisala
T = CONTROL PANEL SF0#.STS 6 H904 VFD Current Switch, NO, Split- Veris Industries
TD03 24 AMB24-SR Modulating, Non-Fail-safe, AC Belimo
T = DP PANEL TD01 + TD02 72 NMB24-SR Modulating, Non-Fail-safe, AC Belimo
TT## 9 A/TTM1K-R2-4-32-122F Room Air Temp Sensor, Matched ACI
T = REM. POWER PANEL
TT## + NT## 6 A/RH2-TTM1K-R2-4-32-122F Room Air Temp/Hum Sensor, Matc ACI
TT14 + NT08 1 HMS110 OA Temp/Hum Sensor Vaisala
P P T = DUCT HEATER
WS02 8 U006-0007 SPOT DETECTOR 14 FT LEADER CBL Veris Industries
A A A A T = REM. CO PANEL
T F P TT = TEMPERATURE COLO 1 CELL 4
Device Qty Part Number Description Manufacturer

5/27/2022

5/27/2022
HH = HUMIDITY ----------------------------------------------------------------------------------------------------------------------------------------------------

Last Printed
Last Saved
##.SS + .O + .C 56 V100 RELAY ENCLOSED SPDT 10-30V Veris Industries
PP = PRESSURE CO 1 CO-R-4X-RB-D CO Room Mount with Display, Re ACI
PD## 6 AFB24-SR Modulating, Spring Return, AC Belimo
FF = FLOW METER PT##-CA 5 AA56 STAINLESS PLATE/STATIC PRESSUR Veris Industries
PT##-HA 8 AA56 STAINLESS PLATE/STATIC PRESSUR Veris Industries
AA

Job Number
= ACTUATOR PT06-OA 1 SPH20 STATIC PRESSURE HEAD HEATED Vaisala

402 COLO 1 Floorplan.vsd


SF0#.STS 6 H904 VFD Current Switch, NO, Split- Veris Industries
LL = LEAK DETECTOR
TD03 24 AMB24-SR Modulating, Non-Fail-safe, AC Belimo

Sheet Number
TD01 + TD02 72 NMB24-SR Modulating, Non-Fail-safe, AC Belimo
RR = FIELD RELAY

File Name
TT## 8 A/TTM1K-R2-4-32-122F Room Air Temp Sensor, Matched ACI

402-1
TT## + NT## 6 A/RH2-TTM1K-R2-4-32-122F Room Air Temp/Hum Sensor, Matc ACI
CST = CURRENT SWITCH
TT14 + NT08 1 HMS110 OA Temp/Hum Sensor Vaisala
WS02 8 U006-0007 SPOT DETECTOR 14 FT LEADER CBL Veris Industries
CT = CO SENSOR
Electric. Their use or reproduction without prior consent of
COLO 1 CELL 1 & 3 Floorplan

These drawings and designs are the property of Schneider

the company is strictly forbidden.


T KEYED NOTES:
1. BAS central controller and differential pressure
transmitter panels mount on a freestanding rack
adjacent to the corridor, all conduit shall be fed
from the top of the panels.

2. Clear window provided on the differential


pressure transmitter panel to allow viewing of
displays without opening panel door.

3. Refer to Detail 2/PHX11-P-G-01-0 in PHX11


T T MECH Plans for plumbing schematic and location

Date:
of flow meters and pressure transmitters.
P P P P P P

Preliminary
H H H H H H H H H H H H 4. Field verify panel location with other trades.

T T T T T T T T T T T T T T T T T T T T T T 5. Mount gateway provided by VRF equipment


vendor inside an enclosure as required per
P P P P P P P P P P P P P P P P P P P P manufacturer’s instruction. Touchscreen
controller/HMI shall be mounted on the front panel
of the same enclosure. Configure BACnet/IP-
capable controller for connection to BAS.

6. VRF equipment vendor to provide and configure


VRF network from VRF equipment to VRF
T C T T C T gateway device as required. Coordinate VRF

# Change:
equipment points list with controls contractor.

Revision:
Reference VRF detail.

1
2
3
4
5
R R R R R R R R R R R R R R R R
CS CS CS CS CS CS CS CS CS CS CS CS CS CS CS CS

5/26/2022
5/26/2022
5/26/2022
L L L L L L L L L L L L L L L L
A A A A A A A A A A A A A A A A
A A A A A A A A A A A A A A A A

Date:
Date:
Date:
N

Designed by:
Software by:
Checked by:
Contractor:
Engineer:
Architect:
COLO 1 CELL 1
Device Qty Part Number Description Manufacturer
----------------------------------------------------------------------------------------------------------------------------------------------------

National And Strategic Accounts


##.SS + .O + .C 56 V100 RELAY ENCLOSED SPDT 10-30V Veris Industries
CO 1 CO-R-4X-RB-D CO Room Mount with Display, Re ACI
NPW-FT01 1 FT-3204-21112-1021 In-line EM Flow Meter, 4 in., Onicon

COLO 1 CELL 1 & 3


NPW-PT01 1 KEL-PTX1-09 STAINLESS 0-200psi/4-20 MA Kele
PD## 6 AFB24-SR Modulating, Spring Return, AC Belimo
LEGEND PT##-CA 5 AA56 STAINLESS PLATE/STATIC PRESSUR Veris Industries

Floorplan
PT##-HA 8 AA56 STAINLESS PLATE/STATIC PRESSUR Veris Industries
PT06-OA 1 SPH20 STATIC PRESSURE HEAD HEATED Vaisala
T = CONTROL PANEL SF0#.STS 6 H904 VFD Current Switch, NO, Split- Veris Industries
TD03 24 AMB24-SR Modulating, Non-Fail-safe, AC Belimo
T = DP PANEL TD01 + TD02 72 NMB24-SR Modulating, Non-Fail-safe, AC Belimo
TT## 9 A/TTM1K-R2-4-32-122F Room Air Temp Sensor, Matched ACI
T = REM. POWER PANEL
TT## + NT## 6 A/RH2-TTM1K-R2-4-32-122F Room Air Temp/Hum Sensor, Matc ACI
TT14 + NT08 1 HMS110 OA Temp/Hum Sensor Vaisala
T = DUCT HEATER
WS02 8 U006-0007 SPOT DETECTOR 14 FT LEADER CBL Veris Industries
T = REM. CO PANEL

TT = TEMPERATURE COLO 1 CELL 3


Device Qty Part Number Description Manufacturer

5/27/2022

5/27/2022
HH = HUMIDITY ----------------------------------------------------------------------------------------------------------------------------------------------------

Last Printed
Last Saved
##.SS + .O + .C 56 V100 RELAY ENCLOSED SPDT 10-30V Veris Industries
PP = PRESSURE CO 1 CO-R-4X-RB-D CO Room Mount with Display, Re ACI
PD## 6 AFB24-SR Modulating, Spring Return, AC Belimo
P F FF = FLOW METER PT##-CA 5 AA56 STAINLESS PLATE/STATIC PRESSUR Veris Industries
PT##-HA 8 AA56 STAINLESS PLATE/STATIC PRESSUR Veris Industries
AA

Job Number
= ACTUATOR
A A A A PT06-OA 1 SPH20 STATIC PRESSURE HEAD HEATED Vaisala

402 COLO 1 Floorplan.vsd


SF0#.STS 6 H904 VFD Current Switch, NO, Split- Veris Industries
T TT T P P LL = LEAK DETECTOR
TD03 24 AMB24-SR Modulating, Non-Fail-safe, AC Belimo

Sheet Number
H HH H RR = FIELD RELAY
TD01 + TD02 72 NMB24-SR Modulating, Non-Fail-safe, AC Belimo

File Name
TT## 8 A/TTM1K-R2-4-32-122F Room Air Temp Sensor, Matched ACI

402-2
TT## + NT## 6 A/RH2-TTM1K-R2-4-32-122F Room Air Temp/Hum Sensor, Matc ACI
CST = CURRENT SWITCH
TT14 + NT08 1 HMS110 OA Temp/Hum Sensor Vaisala
WS02 8 U006-0007 SPOT DETECTOR 14 FT LEADER CBL Veris Industries
CT = CO SENSOR
Electric. Their use or reproduction without prior consent of
SHELL Floorplan

These drawings and designs are the property of Schneider

the company is strictly forbidden.


KEYED NOTES:
1. PHX11-COLO5-CE4-CC01 is the
temporary shell controller. See I/O
located in drawing 505-3. Provide
T F T media converter for fiber connection
P
back to admin FCR switch.

2. Refer to drawing 503-6 for


plumbing schematic and location of

Date:
flow meters and pressure
transmitters.

Preliminary
# Change:
Revision:

1
2
3
4
5
T T T

5/26/2022
5/26/2022
5/26/2022
Date:
Date:
Date:
N

Designed by:
Software by:
Checked by:
Contractor:
Engineer:
Architect:
National And Strategic Accounts

SHELL Floorplan
F P

5/27/2022

5/27/2022
LEGEND

Last Printed
Last Saved
T = CONTROL PANEL

TT = TEMPERATURE

Job Number

407 SHELL Floorplan.vsd


SHELL
PP = PRESSURE

Sheet Number
Device Qty Part Number Description Manufacturer

File Name
----------------------------------------------------------------------------------------------------------------------------------------------------

407-1
FF = FLOW METER NPW-FT01
NPW-PT01
2 FT-3204-21112-1021
2 KEL-PTX1-09
In-line EM Flow Meter, 4 in.,
STAINLESS 0-200psi/4-20 MA
Onicon
Kele
TT01 5 A/TTM1K-R2-32-122F Room Air Temp Sensor, Matched ACI
3
1

AHU Wall Layout


ADMIN Wall Layout

4
2

COLO Wall Layout B


COLO Wall Layout A
Panel Wall Layouts

Job Number
National And Strategic Accounts Architect:
Revision: Preliminary
Engineer:
# Change: Date:
File Name Last Saved Contractor:
1
408 Panel Wall Layout.vsd 5/27/2022 Designed by: Date: 5/26/2022 2
3 These drawings and designs are the property of Schneider
Sheet Number Last Printed Software by: Date: 5/26/2022 Electric. Their use or reproduction without prior consent of
4
the company is strictly forbidden.
Panel Wall Layouts Checked by: Date: 5/26/2022 5
408-1 5/27/2022
Electric. Their use or reproduction without prior consent of
ADMIN Equipment Installation Details 1 of 3

These drawings and designs are the property of Schneider

the company is strictly forbidden.


Admin Space Monitoring Sensor Installation Details

CDT01.CO2
SL3
UI9 RET TT01 TT02
A/TTM1K-R2-4 A/TTM1K-R2-4
- PS

N.O. N.C. COM CO2 COM PWR


+ 1
+ TB3-5DC Y1+ + TB3-6DC Y1+ EF02
RELAY CDT01
- TB3-9 UI5 TT01.FRT - TB3-11 UI6 TT02.FCRT EF02.STS
SL4
GND Y2- TB3-10 RET SL3 GND Y2- TB3-12 RET SL3
CWE Volt mA UI2 RET

Date:
VOUT VOUT
TB4-3 TB4-4
SET + SET +

Preliminary
+ -
SET - SET - EF02
CDT02.CO2
SL3
OR OR 120VAC L
UI10 RET OR OR POWER
(By Others) N

- PS
+ 1

N.O. N.C. COM CO2 COM PWR


RELAY CDT02

CWE Volt mA
TT03 TT04
EF03

# Change:
A/TTM1K-R2-4 A/TTM1K-R2-4

Revision:
EF03.STS
CDT03.CO2 + TB3-7DC Y1+ + TB3-8DC Y1+ SL4

1
2
3
4
5
SL3 UI4 RET
UI11 RET
- TB3-13 UI7 TT03.SERT - TB3-15 UI8 TT04.ERT
GND 24VDC-
Y2- TB3-14 RET SL3 GND 24VDC-
Y2- TB3-16 RET SL3 TB4-5 TB4-6

- PS VOUT VOUT + -
EF03
+ 1 SET + SET +
120VAC L
N.O. N.C. COM CO2 COM PWR SET - SET - POWER
RELAY CDT03
OR OR (By Others) N

5/26/2022
5/26/2022
5/26/2022
CWE Volt mA
OR OR

Date:
Date:
Date:
Designed by:
Software by:
Checked by:
Contractor:
Engineer:
Architect:
National And Strategic Accounts

Installation Details 1 of 3
ADMIN Equipment
5/27/2022

5/27/2022
Last Printed
Last Saved
Job Number

501 ADMIN Equipment Installation

Sheet Number
File Name

Details.vsd

501-1
18
17
24
23

GND
N (-)
L (+)
FT-3200
DCW-FT01
Admin Compactor Room Flow Meter Installation Details

TB3-4
TB3-3
TB3-2
TB3-1

X3H
From
24VAC
UI2
UI1

RET
RET

X4N XFMR-#
TB-PA
TB-PA
SL3
SL3
FT01.DCW

FQ01.DCW
18
17
24
23

GND
N (-)
L (+)
FT-3200
IRR-FT01

TB3-8
TB3-7
TB3-6
TB3-5

X3H
ADMIN Equipment Installation Details 2 of 3

From
24VAC
UI4
UI3

RET
RET

X4N XFMR-#
TB-PA
TB-PA
SL3
SL3
FT01.IRR

FQ01.IRR

Job Number
National And Strategic Accounts Architect:
Revision: Preliminary
Engineer:
# Change: Date:
File Name Last Saved Contractor:
1
501 ADMIN Equipment Installation
5/27/2022 Designed by: Date: 2
Details.vsd 5/26/2022
3 These drawings and designs are the property of Schneider
Sheet Number Last Printed Software by: Date: 5/26/2022 Electric. Their use or reproduction without prior consent of
ADMIN Equipment 4
the company is strictly forbidden.
Checked by: Date: 5/26/2022 5
501-2 5/27/2022 Installation Details 2 of 3
J6
J5

-
-
-

+
+
J1 +

NC 1
C3
NO 5
NC 2
C4
NO 6
NC 1
C3
NO 5
NC 2
C4
NO 6

EF01-HDT01
EF01-HDT01
KEL-GDD-H2

869-STR-B-AQ
TB4-8
TB4-7
UI4
RET
X4N
X3H
Compactor Room Hydrogen Sensor Installation Details

SL4
TB-PA
TB-PA

EF01-HDT01.ALM

WHT/BLU WHT/BLU
BLU
BLU

BRN
GRY

ORG
ORG
+
UI1

SL4

WHT/YEL WHT/YEL
EF01.SS
SL4

EF01

NO1 COM
EF01

TB4-17 TB4-9AC
-

120 VAC 120 VAC


EF01.STS

RET

TB4-1 TB4-2

EF01-HDT01

WHT/BLK WHT/BLK
VIO

YEL
YEL
EF01

L
L

N
N

120VAC
POWER
Shunt Trip

(By Others)
Forklift Charger
ADMIN Equipment Installation Details 3 of 3

Job Number
National And Strategic Accounts Architect:
Revision: Preliminary
Engineer:
# Change: Date:
File Name Last Saved Contractor:
1
501 ADMIN Equipment Installation
5/27/2022 Designed by: Date: 2
Details.vsd 5/26/2022
3 These drawings and designs are the property of Schneider
Sheet Number Last Printed Software by: Date: 5/26/2022 Electric. Their use or reproduction without prior consent of
ADMIN Equipment 4
the company is strictly forbidden.
Checked by: Date: 5/26/2022 5
501-3 5/27/2022 Installation Details 3 of 3
Electric. Their use or reproduction without prior consent of
COLO-AHU Equipment Installation Details 1 of 2

These drawings and designs are the property of Schneider

the company is strictly forbidden.


SaFan Array Layout 1.1.3 Supply Air Fan 1-Status 1.1.3 Supply Air Fan 2-Status

Hi Lo Hi Lo

N.C. N.C.

1 2 3 SF TB4:17 UI9 SF01.STS SF TB4:19 UI10 SF02.STS


01 TB4:18 RET SL4 02 TB4:20 RET SL4

L1 L2 L3 L1 L2 L3
1.1.2 1.1.2

Date:
From From
VFD VFD

Preliminary
L1 L2 L3 L1 L2 L3

1.1.3 Supply Air Fan 3-Status 1.1.3 Supply Air Fan 4-Status

4 5 6

# Change:
Revision:
Hi Lo Hi Lo

N.C. N.C.

1
2
3
4
5
SF TB4:21 UI11 SF03.STS SF TB4:23 UI12 SF04.STS
03 TB4:22 RET SL4 04 TB4:24 RET SL4

L1 L2 L3 L1 L2 L3
1.1.2 1.1.2
From From
1.1.2 Supply Air Fan VFD Wiring VFD VFD

5/26/2022
5/26/2022
5/26/2022
VFD Field SE Panel L1 L2 L3 L1 L2 L3

VFD Board
TBD TB6:1 VO1 SC01.SPD
Speed Command
TBD TB6:2 RET SL6

Date:
Date:
Date:
TBD TB3:25 UI13 SC01.FB
Speed Feedback
TBD TB3:26 RET SL3 1.1.3 Supply Air Fan 5-Status 1.1.3 Supply Air Fan 6-Status

TBD TB7:15 NO5 SC01.SS


Start/Stop Command
TBD ORG YEL WHT/BLU FR# WHT/YEL TB7:14 X8N SL7
FR#-1
TBD
Safety Interlock Hi Lo Hi Lo
TBD

Designed by:
Software by:
Checked by:
Contractor:
Engineer:
Architect:
TBD N.C. N.C.
Not Used
TBD

TBD TB4:31 UI16 SC01.FLT SF TB4:25 UI13 SF05.STS SF TB4:27 UI14 SF06.STS
Fault TBD TB4:32 RET SL4 05 TB4:26 RET SL4 06 TB4:28 RET SL4

National And Strategic Accounts


TBD
L1 L2 L3 L1 L2 L3

Installation Details 1 of 2
COLO-AHU Equipment
1.1.2 1.1.2
TBD TB4:29 UI15 SC01.STS
From From
Running TBD TB4:30 RET SL4
VFD VFD
TBD

L1 L2 L3 L1 L2 L3

+ TBD
BACnet MSTP From: See Network Architecture
- TBD
GND TBD
To: See Network Architecture

Gallery Leak Detection Wiring

TB-PA X7H
TB-PA X8N

5/27/2022

5/27/2022
SL4 RET TB3-6

Last Printed
Last Saved
WS02.WD UI2 TB3-5

Job Number

502 AHU Equipment Installation

Sheet Number
File Name

Details.vsd

502-1
Electric. Their use or reproduction without prior consent of
COLO-AHU Equipment Installation Details 2 of 2

These drawings and designs are the property of Schneider

the company is strictly forbidden.


1.6.1a Outside Air Damper A Wiring 1.6.1b Outside Air Damper B Wiring 1.6.2 Return Air Damper Wiring 1.6.3 Relief Air Damper Wiring

= Cap unused wires = Cap unused wires = Cap unused wires = Cap unused wires

TB-PA X5H TB6-3AC HOT TB-PA X5H TB6-4AC HOT TB-PA X5H TB6-2AC HOT TB-PA X3H R1-5 HOT
TB-PA X6N TB6-6 COM Switch provided TB-PA X6N TB6-8 COM Switch provided TB-PA X6N TB6-4 COM Switch provided TB-PA X4N TB5-18 COM Switch provided
SL6 COM for selection of SL6 COM for selection of SL6 COM for selection of SL6 COM for selection of
TD01.CMD VO3 TB6-5 AI direct or reverse TD02.CMD VO4 TB6-7 AI direct or reverse TD03.CMD VO2 TB6-3 AI direct or reverse PD01.CMD VO5 TB5-17 AI direct or reverse
AO acting AO acting AO acting AO acting
CCW CW control mode CCW CW control mode CCW CW control mode CCW CW control mode
Clockwise or counterclockwise
spring return is determined by
actuator mounting position

RED HOT RED HOT RED HOT RED HOT


COM COM COM COM

Date:
WHT AI WHT AI WHT AI WHT AI
AO AO AO AO

Preliminary
CCW CW CCW CW CCW CW CCW CW

RED HOT RED HOT RED HOT RED HOT


BLK COM BLK COM BLK COM BLK COM

WHT AI WHT AI WHT AI WHT AI


AO AO AO AO
CCW CW CCW CW CCW CW CCW CW

# Change:
Revision:
RED HOT
BLK COM
SL3 RET TB3-6 SL3 RET TB3-4 SL3 RET TB3-10
TD01.FB UI3 TB3-5 TD03.FB UI2 TB3-3 PD01.FB UI5 TB3-9
WHT AI

1
2
3
4
5
AO
CCW CW

RED HOT
BLK COM

5/26/2022
5/26/2022
5/26/2022
WHT AI
AO
CCW CW

Date:
Date:
Date:
1.6.11 Face Damper Wiring RED HOT
BLK COM Outside Air Damper Wiring Order
= Cap unused wires
WHT AI
TB-PA X5H TB6-5AC HOT AO
TB-PA X6N TB6-10 COM CCW CW
Switch provided
SL6 COM for selection of
ND01.CMD VO5 TB6-9 AI direct or reverse

Designed by:
Software by:
Checked by:
AO acting

Contractor:
CCW CW control mode

Engineer:
Architect:
Clockwise or counterclockwise
spring return is determined by SL3 RET TB3-7
actuator mounting position TD02.FB UI4 TB3-8

RED HOT

National And Strategic Accounts


COM

Installation Details 2 of 2
COLO-AHU Equipment
WHT AI PD02.CMD PD02 PD02 PD02
AO
CCW CW

RED HOT
BLK COM

WHT AI 1.6.12 Bypass Damper Wiring


AO
CCW CW
= Cap unused wires

TB-PA X5H TB6-6AC HOT


TB-PA X6N TB6-12 COM Switch provided
SL6 COM for selection of PD02.FB PD02 PD02 PD02
ND02.CMD VO6 TB6-11 AI direct or reverse
SL3 RET TB3-12 acting
AO

5/27/2022

5/27/2022
ND01.FB UI6 TB3-11

Last Printed
CCW CW control mode

Last Saved
RED HOT

Job Number
COM

502 AHU Equipment Installation


WHT AI

Sheet Number
AO PD01.FB

File Name
CCW CW

Details.vsd

502-2
SL3 RET TB3-14
ND02.FB UI7 TB3-13 PD01.CMD PD01 PD01 PD01
Electric. Their use or reproduction without prior consent of
COLO Equipment Installation Details 1 of 7

These drawings and designs are the property of Schneider

the company is strictly forbidden.


Outside Air Temp/Rh Sensor Installation Details IT Space Temp/Rh Sensor Installation Details
Y2-
24VDC- RET PHX11-COLO#-CE#-CC01

8 T- UI# TT14.OAT
7 T+ TB#-#DC Y1+
ACI
6 HUM- A/TTM1K-R2-4
5 HUM+ 24VDC-
Y2- RET PHX11-COLO#-CE#-CC01

UI# NT08.OAH
+ TB#-#DC Y1+

Service
Vaisala TB#-#DC Y1+
- UI# TT##.HAT

Port
HMS110 OA T/Rh GND 24VDC-
Y2- RET PHX11-COLO#-CE#-CC01

Date:
VOUT
4 Pwr+ SET +

Preliminary
3 Pwr- SET -
2 RS485- OR
1 RS485+ OR

ACI
A/RH2-TTM1K-
R2-4

# Change:
Revision:
+ TB#-#DC Y1+

- UI# TT##.CAT
GND

1
2
3
4
5
24VDC-
Y2- RET PHX11-COLO#-CE#-CC01

VOUT
4-20 mA TB#-#DC Y1+

VIN UI# NT##.HAT


COM 24VDC-
Y2- RET PHX11-COLO#-CE#-CC01

VOUT

5/26/2022
5/26/2022
5/26/2022
Date:
Date:
Date:
Designed by:
Software by:
Checked by:
Contractor:
Engineer:
Temp/Rh Sensor Placement Details

Architect:

COLO Equipment Installation


National And Strategic Accounts

Details 1 of 7
5/27/2022

5/27/2022
Last Printed
Last Saved
Job Number

503 COLO Equipment Installation

Sheet Number
File Name

Details.vsd

503-1
SETRA
MR1SA
IT Space Control Sensor Installation Details

Y2-
UI#
RET
TB#-#DC
Y1+

PT##.SRP
PHX11-COLO#-CE#-CC01
HOT
AISLE
Tubing Connections
(Bottom of MR1SA Sensor)

OUTSIDE
COLO Equipment Installation Details 2 of 7

AA56

Job Number
National And Strategic Accounts Architect:
Revision: Preliminary
Engineer:
# Change: Date:
File Name Last Saved Contractor:
1
503 COLO Equipment Installation
5/27/2022 Designed by: Date: 2
Details.vsd 5/26/2022
3 These drawings and designs are the property of Schneider
Sheet Number Last Printed Software by: Date: 5/26/2022 Electric. Their use or reproduction without prior consent of
COLO Equipment Installation 4
the company is strictly forbidden.
Checked by: Date: 5/26/2022 5
503-2 5/27/2022 Details 2 of 7
SETRA
MR1SA
Outside Air Pressure Sensor Installation Details

Y2-
UI#
RET
TB#-#DC
Y1+

PT##.HAP
PHX11-COLO#-CE#-CC01
HOT
AISLE
Tubing Connections
(Bottom of MR1SA Sensor)

OUTSIDE
COLO Equipment Installation Details 3 of 7

AA56
AA56

Job Number
National And Strategic Accounts Architect:
Revision: Preliminary
Engineer:
# Change: Date:
File Name Last Saved Contractor:
1
503 COLO Equipment Installation
5/27/2022 Designed by: Date: 2
Details.vsd 5/26/2022
3 These drawings and designs are the property of Schneider
Sheet Number Last Printed Software by: Date: 5/26/2022 Electric. Their use or reproduction without prior consent of
COLO Equipment Installation 4
the company is strictly forbidden.
Checked by: Date: 5/26/2022 5
503-3 5/27/2022 Details 3 of 7
Electric. Their use or reproduction without prior consent of
COLO Equipment Installation Details 4 of 7

These drawings and designs are the property of Schneider

the company is strictly forbidden.


1.6.3a RlfaDprA - DprPos,Fbk 1.6.3b RlfaDprB - DprPos,Fbk

= Cap unused wires = Cap unused wires

TB-PA X#H R1-6 HOT TB-PA X#H R1-5 RED HOT


TB-PA X#N TB#-## COM Switch provided TB-PA X#N TB#-## BLK COM Switch provided
SL# COM for selection of SL# COM for selection of
PD01.CMD VO# TB#-## AI direct or reverse PD02.CMD VO# TB#-## WHT AI direct or reverse
AO acting AO acting
CCW CW control mode CCW CW control mode

RED HOT RED HOT


BLK COM BLK COM

Date:
WHT AI WHT AI

Preliminary
AO AO
CCW CW CCW CW

SL# RET TB#-##


PD02.FB UI# TB#-##

RED HOT
BLK COM

COLO Cell RlfaDpr Wiring Order Details


WHT AI
AO
CCW CW

# Change:
Revision:
RED HOT
BLK COM

1
2
3
4
5
WHT AI
AO
CCW CW

PD01.CMD PD01 PD01 PD02 PD02 PD01 PD01

5/26/2022
5/26/2022
5/26/2022
SL# RET TB#-##
PD01.FB UI# TB#-## PD02.CMD
PD02.FB

PD01.FB

Date:
Date:
Date:
Designed by:
Software by:
Checked by:
Contractor:
Engineer:
Architect:

COLO Equipment Installation


National And Strategic Accounts

Details 4 of 7
5/27/2022

5/27/2022
Last Printed
Last Saved
Job Number

503 COLO Equipment Installation

Sheet Number
File Name

Details.vsd

503-4
BLACK
WHITE
KELE
PTX1-09

Y2-
24VDC-
Non-Potable Water Sensor Installation Details

UI#
RET
TB#-#DC
Y1+

TT##.HAT
PHX11-COLO#-CE#-CC01

18
17
24
23

GND
N (-)
L (+)
FT-3200
NPW-FT01

UI#
UI#

RET
RET

X6N
X5H
TB-PA
TB-PA
TT##.HAT
TT##.HAT

PHX11-COLO#-CE#-CC01
PHX11-COLO#-CE#-CC01
COLO Equipment Installation Details 5 of 7

24VAC
From XFMR-#

Job Number
National And Strategic Accounts Architect:
Revision: Preliminary
Engineer:
# Change: Date:
File Name Last Saved Contractor:
1
503 COLO Equipment Installation
5/27/2022 Designed by: Date: 2
Details.vsd 5/26/2022
3 These drawings and designs are the property of Schneider
Sheet Number Last Printed Software by: Date: 5/26/2022 Electric. Their use or reproduction without prior consent of
COLO Equipment Installation 4
the company is strictly forbidden.
Checked by: Date: 5/26/2022 5
503-5 5/27/2022 Details 5 of 7
2
1
Outside Air Pressure Pickup Port Detail

Outside Air Pressure Pickup Port Wiring

Y4-
Y3+
TB-PA
TB-PA
RPP
COLO Equipment Installation Details 6 of 7

Job Number
National And Strategic Accounts Architect:
Revision: Preliminary
Engineer:
# Change: Date:
File Name Last Saved Contractor:
1
503 COLO Equipment Installation
5/27/2022 Designed by: Date: 2
Details.vsd 5/26/2022
3 These drawings and designs are the property of Schneider
Sheet Number Last Printed Software by: Date: 5/26/2022 Electric. Their use or reproduction without prior consent of
COLO Equipment Installation 4
the company is strictly forbidden.
Checked by: Date: 5/26/2022 5
503-6 5/27/2022 Details 6 of 7
1
Battery Room CO Sensor and Exhaust Fan Wiring
2

120VAC
POWER
(By Others)
L
N
COLO 2 and 4 Bathroom Exhaust Fan Wiring

+
UI14
SL4

EF01
-
EF01.STS

RET

TB4-3 TB4-4
COLO Equipment Installation Details 7 of 7

EF01

Job Number
National And Strategic Accounts Architect:
Revision: Preliminary
Engineer:
# Change: Date:
File Name Last Saved Contractor:
1
503 COLO Equipment Installation
5/27/2022 Designed by: Date: 2
Details.vsd 5/26/2022
3 These drawings and designs are the property of Schneider
Sheet Number Last Printed Software by: Date: 5/26/2022 Electric. Their use or reproduction without prior consent of
COLO Equipment Installation 4
the company is strictly forbidden.
Checked by: Date: 5/26/2022 5
503-7 5/27/2022 Details 7 of 7
Electric. Their use or reproduction without prior consent of
ADMIN Panel Power Detail

These drawings and designs are the property of Schneider

the company is strictly forbidden.


X1H
TB-PA
CB8
PNL1
24VAC
X1H X1H
Wired from
X1H
XFR1 24VAC
X1H
Wired to
X2N X2N X2N
Controller
X2N
X2N G
G
TB-PA

Date:
X3H CB9

24VAC

Preliminary
X3H X3H
Wired from 24VAC
X3H
XFR2 Wired to
X3H
End Devices
X4N X4N X4N
X4N
X4N
G
TB-PA
X5H CB10

24VAC
X5H X5H
Wired from 24VAC
X5H
XFR3 Wired to
X5H

# Change:
End Devices

Revision:
X6N X6N X6N
X6N
X6N
G

1
2
3
4
5
TB-PA
X7H CB11

24VAC
X7H X7H
Wired from 24VAC
X7H
XFR4 Wired to
X7H
End Devices
X8N X8N X8N
X8N

5/26/2022
5/26/2022
5/26/2022
X8N
G
TB-PA
Y1+ CB12

24VDC
Y1+ Y1+
Wired from 24VDC

Date:
Date:
Date:
Y1+
PS1 Wired to
Y2-
End Devices
Y2- Y2- Y2-
G

Designed by:
Software by:
Checked by:
Contractor:
Engineer:
Architect:
Panel Continued on Next Page

National And Strategic Accounts

ADMIN Panel Power Detail


UL Panel Details
Panel:_____________________

5/27/2022

5/27/2022
Last Printed
Last Saved
CKT#:_____________________
MAX VOLTAGE: 24v
SSCR = 10kA
TOTAL FLA : 9.40A

Job Number

601 ADMIN Panel.vsd


CB8 (24VAC) = 4.00A

Sheet Number
CB9 (24VAC) = 4.00A

File Name

601-1
CB10 (24VAC) = 4.00A
CB11 (24VAC) = 4.00A
CB12 (24VDC) = 4.00A
See Network Architecture
See Network Architecture

Room#
Room#

Switch ##
Switch ##

Port#
Port#
TB-C

E2
E1

ETH2
ETH1
AS-P

TAHUYA
TB-PA
TB-PA
TB-PA
TB-PA
Y2-
Y1+

X1H
X2N

L/+
2

L/-
4

GND
F-0
1A Fuse

SXW PS-24V
SL1
Schneider Electric
ADMIN Panel IO Detail - 1 & 2

TX/RX+
Host
2

TX/RX-
Device
Com A
3

RET
4

BIAS+
5

RS-485

TX/RX+
6

TX/RX-
Com B
7

RET
1 2 3 4 5 6 7 8

TX/RX+
TX/RX-
10/100
SXW AS-P
RS-485

Ethernet 1
9 10

RET
LON

SL2

LON-1
Schneider Electric
11 12

LON-2
TP/FT

10/100
Ethernet 2
TAHUYA Adapter

Panel Continued on Next Page


Panel Continued on Previous Page

TAHUYA

Job Number
National And Strategic Accounts Architect:
Revision: Preliminary
Engineer:
# Change: Date:
File Name Last Saved Contractor:
1
601 ADMIN Panel.vsd 5/27/2022 Designed by: Date: 5/26/2022 2
3 These drawings and designs are the property of Schneider
Sheet Number Last Printed Software by: Date: 5/26/2022 Electric. Their use or reproduction without prior consent of
ADMIN Panel IO Detail - 1 & 4
the company is strictly forbidden.
Checked by: Date: 5/26/2022 5
601-2 5/27/2022 2
Electric. Their use or reproduction without prior consent of
ADMIN Panel IO Detail - 3

These drawings and designs are the property of Schneider

the company is strictly forbidden.


Panel Continued on Previous Page

TB-03
1 Top Bottom
23 1 UI1 SL3
FT01.DCW DCW FLOW TB##
24 2 RET SL3
1AC X3H TB-PA TB-03 7 9 TB-03
1DC Y1+ TB-PA

Date:
17 3 UI2 SL3
FQ01.DCW DCW FLOW TOTAL
18 4 X4N TB-PA TB-03 5 11 TB-03
2AC TB-03 3 13 TB-03

Preliminary
2DC TB-03 2
S1
S1 TB-03 1 15 TB-03
23 5 UI3 SL3
FT01.IRR IRR FLOW
24 6 Y2- TB-PA
1 2 3 4 5 6 7 8 9 10 11 12
3AC

RET

RET

RET

RET
UI1

UI2

UI3

UI4

UI5

UI6

UI7

UI8
3DC

17 7 UI4 SL3
Q01.IRR IRR FLOW TOTAL
18 8
4AC 1 2 3 4 5 6 7 8
Universal Inputs
4DC

TT01.FRT FIRE RISER ROOM TEMP


- 9 UI5 SL3
Schneider Electric

# Change:
+ 10

Revision:
5AC SXW UI-16
5DC
SL3
- 11 UI6 SL3
TT02.FCRT FCR TEMP Universal Inputs

1
2
3
4
5
+ 12 9 10 11 12 13 14 15 16
6AC
6DC

UI10

UI11

UI12

UI13

UI14

UI15

UI16
RET

RET

RET

RET
UI9
S2
S2
13 14 15 16 17 18 19 20 21 22 23 24
- 13 UI7 SL3
TT03.SERT SER ROOM TEMP
+ 14
7AC TB-03 17 31 TB-03

5/26/2022
5/26/2022
5/26/2022
7DC

- 15 UI8 SL3 TB-03 18


TT04.ERT ELECTRICAL ROOM TEMP
+ 16 TB-03 19 29 TB-03
8AC TB-03 21 27 TB-03
8DC

CO2 17 UI9 SL3


CDT01.CO2 ASSET MANAGEMENT CO2 LEVEL
PWR 18 RET SL3 TB-03 23 25 TB-03

Date:
Date:
Date:
9AC
9DC

CO2 19 UI10 SL3


CDT02.CO2 CONFERENCE ROOM CO2 LEVEL
PWR 20
10AC
10DC
S3

Designed by:
S3

Software by:
Checked by:
Contractor:
CO2 21 UI11 SL3

Engineer:
Architect:
CDT03.CO2 BREAK ROOM CO2 LEVEL
PWR 22
11AC
11DC
23 UI12 SL3
24

National And Strategic Accounts

ADMIN Panel IO Detail - 3


12AC
12DC
25 UI13 SL3
26
13AC
13DC
27 UI14 SL3
28
14AC
14DC
S4
S4
29 UI15 SL3
30
15AC
15DC
31 UI16 SL3
32
16AC

5/27/2022

5/27/2022
16DC

Last Printed
Last Saved
Job Number

601 ADMIN Panel.vsd


Sheet Number
File Name

601-3
Panel Continued on Next Page

Label wiring, cabling, and conduit with point name at each end within 5 cm (2 in.)
1
of termination.
Electric. Their use or reproduction without prior consent of
ADMIN Panel IO Detail - 4

These drawings and designs are the property of Schneider

the company is strictly forbidden.


Panel Continued on Previous Page

TB-04
1 Top Bottom
COMPACTOR ROOM/FORKLIFT CHARGER EXHAUST FAN NO 1 UI1 SL4
EF01.STS TB##
STATUS COM 2 RET SL4
1AC X3H TB-PA
1DC Y1+ TB-PA

Date:
NO 3 UI2 SL4 TB-04 19
EF02.STS LOADING DOCK RESTROOM EXHAUST FAN STATUS
COM 4 X4N TB-PA
2AC 21 TB-04

Preliminary
2DC TB-04 17
S1 TB-PA X3H
S1 23 TB-04
NO 5 UI3 SL4
EF03.STS LOBBY RESTROOM EXHAUST FAN STATUS
COM 6 Y2- TB-PA
1 2 3 4 5 6 7 8 9 10 11 12
3AC

COM

COM

COM

COM
NO1

NO2

NO3

NO4
NC1

NC2

NC3

NC4
3DC

EF01- COMPACTOR ROOM/FORKLIFT CHARGER HYDROGEN NO 7 UI4 SL4


HDT01.ALM ALARM COM 8
4AC 1 2 3 4
Digital Outputs
4DC

CC01-QS01.PA DDC PRIMARY POWER AVAILABLE


5 9 UI5 SL4
Schneider Electric

# Change:
9 10

Revision:
5AC SXW UI-8/DO-FC-4-H
5DC
SL4
5 11 UI6 SL4
CC01-QS02.PA DDC SECONDARY POWER AVAILABLE Universal Inputs

1
2
3
4
5
9 12 1 2 3 4 5 6 7 8
6AC
6DC

RET

RET

RET

RET
UI1

UI2

UI3

UI4

UI5

UI6

UI7

UI8
S2
S2
13 14 15 16 17 18 19 20 21 22 23 24
13 UI7 SL4
14
7AC TB-04 1 15 TB-04

5/26/2022
5/26/2022
5/26/2022
7DC
15 UI8 SL4 TB-04 2
16 TB-04 3 13 TB-04
8AC TB-04 5 11 TB-04
8DC

COMPACTOR ROOM/FORKLIFT CHARGER EXHAUST FAN WHT/BLU 17 NO1 SL4


EF01.SS
START/STOP 18 TB-04 7 9 TB-04

Date:
Date:
Date:
WHT/YEL
9AC
9DC
19 NO2 SL4
20
10AC
10DC
S3

Designed by:
S3

Software by:
Checked by:
Contractor:
21 NO3 SL4

Engineer:
Architect:
22
11AC
11DC
23 NO4 SL4
24

National And Strategic Accounts

ADMIN Panel IO Detail - 4


12AC
12DC

5/27/2022

5/27/2022
Last Printed
Last Saved
Job Number

601 ADMIN Panel.vsd


Sheet Number
File Name

601-4
Panel Continued on Next Page

Label wiring, cabling, and conduit with point name at each end within 5 cm (2 in.)
1
of termination.
Low Voltage

Electric. Their use or reproduction without prior consent of


ADMIN Panel Layout - Main

These drawings and designs are the property of Schneider


Conduit Entry Area

the company is strictly forbidden.


21.7in.
21.70 x 1.00

5.5in. DUCT1

27.61 x 1.00

27.61 x 1.00
27.60 x 1.00

Date:
Preliminary
12.90 x 1.25

7.0in.

SL1 SL2 SL3


13.20 x 1.00

DUCT1

# Change:
Revision:

1
2
3
4
5
12.90 x 1.25

F-0
6.8in.

TB-03
DUCT1

5/26/2022
5/26/2022
5/26/2022
SL4
29.6in. 31.5in.

DUCT1
13.20 x 1.00

DUCT1

Date:
Date:
Date:
DUCT1
5.3in.

Designed by:
Software by:
Checked by:
Contractor:
13.20 x 1.00

Engineer:
Architect:
DUCT1
TB-04

TB-PA

National And Strategic Accounts

ADMIN Panel Layout - Main


5.5in. 5.5in.

21.70 x 1.00

DUCT1
PNL2

Part Number Qty Description Manufacturer


23.6in. ----------------------------------------------------------------------------------------------------------------------------------------------------
AI-PW62 1 TAHUYA Power Adapter AI Link
AI-SR620 1 TAHUYA Adapter AI Link
GMD-500-R 1 500 mA Fuse Eaton
KEL-T1-1030G 1 1INX3INX6.5FT GRAY DUCT W/COVE Iboco

5/27/2022

5/27/2022
M9F42104 5 4 Amp CB Schneider Electric

Last Printed
Last Saved
NSYTRAABV35 2 END BRACKET SCREW TYPE Square D
NSYTRAC22 1 END COVER Square D
NSYTRV42 1 6MM TERMINAL BLOCK GRAY Square D
NSYTRV42SF5 1 TERMINAL BLOCK GREY Square D
SEBOX322408P 1 ENCL 32X24X08 NEMA 4 W/ PERF Schneider Electric

Job Number
SXWASPXXX10001 1 SMARTX CONTROLLER AS-P Schneider Electric

601 ADMIN Panel.vsd


SXWPS24VX10001 1 PS-24V POWER SUPPLY 24VAC/VDC Schneider Electric
SXWSCABLE10003 1 S-CABLE 0.75M ANGLE Schneider Electric

Sheet Number
SXWTBASW110002 1 TB-ASP-W1 TERM BASE ASP W1 Schneider Electric

File Name
SXWTBIOW110001 2 TB-IO-W1 TERM BASE I/O W1 Schneider Electric

601-5
SXWTBPSW110001 1 TB-PS-W1 TERM BASE PWR SUP W1 Schneider Electric
SXWUI16XX10001 1 UI-16 16 UNIVERSAL IN Schneider Electric
SXWUI8D4H10001 1 UI-8/DO-FC-4-H UI/DO FRMC HAND Schneider Electric
PNL2

23.6in.
PANEL LABEL

31.5in.
ADMIN Panel Layout - Door

Job Number
National And Strategic Accounts Architect:
Revision: Preliminary
Engineer:
# Change: Date:
File Name Last Saved Contractor:
1
601 ADMIN Panel.vsd 5/27/2022 Designed by: Date: 5/26/2022 2
3 These drawings and designs are the property of Schneider
Sheet Number Last Printed Software by: Date: 5/26/2022 Electric. Their use or reproduction without prior consent of
4
the company is strictly forbidden.
ADMIN Panel Layout - Door Checked by: Date: 5/26/2022 5
601-6 5/27/2022
Electric. Their use or reproduction without prior consent of
COLO-AHU Panel Power Detail

These drawings and designs are the property of Schneider

the company is strictly forbidden.


X1H
TB-PA
CB#
PNL###
24VAC
X1H X1H
Wired from
X1H Mounted in Panel

Date:
XFR1 24VAC
X1H PH01.HS UI3 TB5:5
Wired to
X2N X2N X2N SL5 RET TB5:6 4
Controller

Preliminary
X2N 8 12
X2N G
G 2 TBPA
TB-PA PD01 Actuator Power 6 10 X5H
X3H CB#
Set Reset PB1
1
24VAC 13 LR1 14 9 LR1 12 NO COM
X3H X3H PD01 Actuator Power 5 9 X4N TBPA
Wired from 24VAC
X3H X3H TBPA
XFR2 Wired to
X3H
End Devices LR1-1

14

13
X4N
R1
X4N X4N
1 10
X4N
X4N
NO COM
G H L

# Change:
HSL2

Revision:
TB-PA
Set @ 0.3"
X5H CB#

24VAC
X5H X5H

1
2
3
4
5
Wired from 24VAC
X5H
XFR3 Wired to
X5H
End Devices
X6N X6N X6N
X6N
X6N
G
TB-PA
X7H CB#

5/26/2022
5/26/2022
5/26/2022
24VAC
X7H X7H
Wired from 24VAC
X7H
XFR4 Wired to
X7H
End Devices
X8N X8N X8N
X8N

Date:
Date:
Date:
X8N
G
TB-PA
Y1+ CB#

24VDC
Y1+ Y1+
Wired from 24VDC
Y1+
PS1 Wired to
Y2-
End Devices

Designed by:
Software by:
Checked by:
Y2- Y2- Y2-

Contractor:
Engineer:
Architect:
G

National And Strategic Accounts

COLO-AHU Panel Power


Detail
UL Panel Details
Panel:_____________________

602 AHU Panel.vsd 5/27/2022

5/27/2022
Last Printed
Last Saved
CKT#:_____________________
MAX VOLTAGE: 24v
SSCR = 10kA
TOTAL FLA : 9.40A

Job Number
CB8 (24VAC) = 4.00A

Sheet Number
CB9 (24VAC) = 4.00A

File Name

602-1
CB10 (24VAC) = 4.00A
CB11 (24VAC) = 4.00A
CB12 (24VDC) = 4.00A
See Network Architecture
See Network Architecture

Room#
Room#

Switch ##
Switch ##

Port#
Port#
TB-C

E2
E1

ETH2
ETH1
AS-P

TAHUYA
TB-PA
TB-PA
TB-PA
TB-PA
Y2-

X1H
X2N
Y1+

L/+
2

L/-
4

GND
F-0
1A Fuse

SXW PS-24V
SL1
Schneider Electric
COLO-AHU Panel IO Detail - 1 & 2

TX/RX+
Host
2

TX/RX-
Device
Com A
3

RET
4

BIAS+
5

RS-485

TX/RX+
6

TX/RX-
Com B
7

RET
1 2 3 4 5 6 7 8

TX/RX+
TX/RX-
10/100
SXW AS-P
RS-485

Ethernet 1
9 10

RET
LON

SL2

LON-1
Schneider Electric
11 12

LON-2
TP/FT

10/100
Ethernet 2
TAHUYA Adapter
Panel Continued on Previous Page

TAHUYA

Job Number
National And Strategic Accounts Architect:
Revision: Preliminary
Engineer:
# Change: Date:
File Name Last Saved Contractor:
1
602 AHU Panel.vsd 5/27/2022 Designed by: Date: 5/26/2022 2
3 These drawings and designs are the property of Schneider
Sheet Number Last Printed Software by: Date: 5/26/2022 Electric. Their use or reproduction without prior consent of
COLO-AHU Panel IO Detail - 4
the company is strictly forbidden.
Checked by: Date: 5/26/2022 5
602-2 5/27/2022 1&2
Electric. Their use or reproduction without prior consent of
COLO-AHU Panel IO Detail - 3

These drawings and designs are the property of Schneider

the company is strictly forbidden.


Panel Continued on Previous Page

TB-03
1
Top Bottom
- 1 UI1 SL3
TT01.SAT AHU SUPPLY AIR TEMP TB##
+ 2 RET SL3
1AC X3H TB-PA TB-03 7 9 TB-03
1DC Y1+ TB-PA

Date:
Org 3 UI2 SL3
TD03.FB RETURN AIR DAMPER FEEDBACK
Blk 4 X4N TB-PA TB-03 5 11 TB-03
2AC TB-03 3 13 TB-03

Preliminary
2DC
S1 TB-03 2
S1 TB-03 1 15 TB-03
Org 5 UI3 SL3
TD01.FB OUTSIDE AIR DAMPER A FEEDBACK
Blk 6 Y2- TB-PA
1 2 3 4 5 6 7 8 9 10 11 12
3AC

RET

RET

RET

RET
UI1

UI2

UI3

UI4

UI5

UI6

UI7

UI8
3DC
Org 7 UI4 SL3
TD02.FB OUTSIDE AIR DAMPER B FEEDBACK
Blk 8
4AC 1 2 3 4 5 6 7 8
Universal Inputs
4DC

PD01.FB EXHAUST AIR DAMPE FEEDBACK


Org 9 UI5 SL3
Schneider Electric

# Change:
Blk 10

Revision:
5AC SXW UI-16
5DC
SL3
Org 11 UI6 SL3
ND01.FB FACE DAMPER FEEDBACK Universal Inputs

1
2
3
4
5
Blk 12 9 10 11 12 13 14 15 16
6AC
6DC

UI10

UI11

UI12

UI13

UI14

UI15

UI16
RET

RET

RET

RET
UI9
S2
S2
13 14 15 16 17 18 19 20 21 22 23 24
Org 13 UI7 SL3
ND02.FB BYPASS DAMPER FEEDBACK
Blk 14
7AC TB-03 17 31 TB-03

5/26/2022
5/26/2022
5/26/2022
7DC TB-03 18
+ 15 UI8 SL3
CT01.CON CONDUCTIVITY
- 16 TB-03 19 29 TB-03
8AC TB-03 21 27 TB-03
8DC
- 17 UI9 SL3
TT02.MAT MIXED AIR TEMP
+ 18 RET SL3 TB-03 23 25 TB-03

Date:
Date:
Date:
9AC
9DC
mA 19 UI10 SL3
NT01.SAH SUPPLY AIR HUMIDITY 01
VIN 20
10AC
10DC
S3

Designed by:
S3

Software by:
Checked by:
Contractor:
mA 21 UI11 SL3

Engineer:
Architect:
NT02.SAH SUPPLY AIR HUMIDITY 02
VIN 22
11AC
11DC
+ 23 UI12 SL3
FT01.SAF SUPPLY AIR FLOW
-

COLO-AHU Panel IO Detail -


24

National And Strategic Accounts


12AC
12DC
## 25 UI13 SL3
SC01.FB SUPPLY FAN SPEED FEEDBACK
## 26
13AC
13DC
27 UI14 SL3
28

3
14AC
14DC
S4
S4
29 UI15 SL3
30
15AC
15DC
31 UI16 SL3
32
16AC

602 AHU Panel.vsd 5/27/2022

5/27/2022
16DC

Last Printed
Last Saved
Job Number

Sheet Number
File Name

602-3
Panel Continued on Next Page
Label wiring, cabling, and conduit with point name at each end within 5 cm (2 in.)
1
of termination.
Electric. Their use or reproduction without prior consent of
COLO-AHU Panel IO Detail - 4

These drawings and designs are the property of Schneider

the company is strictly forbidden.


Panel Continued on Previous Page

TB-04
1
Top Bottom
NO 1 UI1 SL4
WS01.WD AHU LEAK DETECTION TB##
COM 2 RET SL4
1AC X3H TB-PA TB-04 7 9 TB-04
1DC Y1+ TB-PA

Date:
NO 3 UI2 SL4
WS02.WD GALLERY LEAK DETECTION
COM 4 X4N TB-PA TB-04 5 11 TB-04
2AC TB-04 3 13 TB-04

Preliminary
2DC
S1 TB-04 2
S1 TB-04 1 15 TB-04
S3 5 UI3 SL4
LCV01.FB NPW MAKEUP WATER VALVE FEEDBACK
S1 6 Y2- TB-PA
1 2 3 4 5 6 7 8 9 10 11 12
3AC

RET

RET

RET

RET
UI1

UI2

UI3

UI4

UI5

UI6

UI7

UI8
3DC
S3 7 UI4 SL4
LCV02.FB CWD DRAIN VALVE FEEDBACK
S1 8
4AC 1 2 3 4 5 6 7 8
Universal Inputs
4DC

LN01.NL EVAP COOLER OPERATING LEVEL


## 9 UI5 SL4
Schneider Electric

# Change:
## 10

Revision:
5AC SXW UI-16
5DC
SL4
## 11 UI6 SL4
LH01.NL EVAP COOLER HIGH LEVEL Universal Inputs

1
2
3
4
5
## 12 9 10 11 12 13 14 15 16
6AC
6DC

UI10

UI11

UI12

UI13

UI14

UI15

UI16
RET

RET

RET

RET
UI9
S2
S2
13 14 15 16 17 18 19 20 21 22 23 24
## 13 UI7 SL4
LL01.LL EVAP COOLER LOW LEVEL
## 14
7AC TB-04 17 31 TB-04

5/26/2022
5/26/2022
5/26/2022
7DC TB-04 18
+ 15 UI8 SL4
EP01.STS EVAP COOLER PUMP STATUS
- 16 TB-04 19 29 TB-04
8AC TB-04 21 27 TB-04
8DC
+ 17 UI9 SL4
SF01.STS SUPPLY FAN 01 STATUS
- 18 RET SL4 TB-04 23 25 TB-04

Date:
Date:
Date:
9AC
9DC
+ 19 UI10 SL4
SF02.STS SUPPLY FAN 02 STATUS
- 20
10AC
10DC
S3

Designed by:
S3

Software by:
Checked by:
Contractor:
+ 21 UI11 SL4

Engineer:
Architect:
SF03.STS SUPPLY FAN 03 STATUS
- 22
11AC
11DC
+ 23 UI12 SL4
SF04.STS SUPPLY FAN 04 STATUS
-

COLO-AHU Panel IO Detail -


24

National And Strategic Accounts


12AC
12DC
+ 25 UI13 SL4
SF05.STS SUPPLY FAN 05 STATUS
- 26
13AC
13DC
+ 27 UI14 SL4
SF06.STS SUPPLY FAN 06 STATUS
- 28

4
14AC
14DC
S4
S4
+ 29 UI15 SL4
SC01.STS SUPPLY FAN AFD STATUS
- 30
15AC
15DC
+ 31 UI16 SL4
SC01.FLT SUPPLY FAN AFD FAULT
- 32
16AC

602 AHU Panel.vsd 5/27/2022

5/27/2022
16DC

Last Printed
Last Saved
Job Number

Sheet Number
File Name

602-4
Panel Continued on Next Page
Label wiring, cabling, and conduit with point name at each end within 5 cm (2 in.)
1
of termination.
Electric. Their use or reproduction without prior consent of
COLO-AHU Panel IO Detail - 5

These drawings and designs are the property of Schneider

the company is strictly forbidden.


Panel Continued on Previous Page

TB-05
1
Top Bottom
5 1 UI1 SL5
QS01.PA PRIMARY POWER AVAILABLE TB##
9 2 RET SL5

Date:
1AC X3H TB-PA
1DC Y1+ TB-PA
5 3 UI2 SL5 21 TB-05

Preliminary
QS02.PA SECONDARY POWER AVAILABLE
9 4 X4N TB-PA TB-05 19
2AC TB-05 18 23 TB-05
2DC TB-05 17
S1
S1
1 2 3 4 5 6 7 8 9 10 11 12
12 5 UI3 SL5
PH01.HS HIGH STATIC PRESSURE SWITCH

CO1

CO2

CO3

CO4
RET

RET

RET

RET
VO1

VO2

VO3

VO4
4 6 Y2- TB-PA
3AC
3DC
7 UI4 SL5 1 2 3 4
Analog Outputs
8
4AC
Schneider Electric

# Change:
4DC

Revision:
9 UI5 SL5 SXW UI-8/AO-4-H
10
SL5
5AC
Universal Inputs

1
2
3
4
5
5DC 1 2 3 4 5 6 7 8
11 UI6 SL5
12

RET

RET

RET

RET
UI1

UI2

UI3

UI4

UI5

UI6

UI7

UI8
6AC
6DC
13 14 15 16 17 18 19 20 21 22 23 24
S2
S2
13 UI7 SL5 TB-05 1 15 TB-05

5/26/2022
5/26/2022
5/26/2022
14 TB-05 2
7AC
7DC TB-05 3 13 TB-05
15 UI8 SL5 TB-05 5 11 TB-05
16
8AC
8DC TB-05 7 9 TB-05

Date:
Date:
Date:
WHT 17 VO1 SL5
PD01.CMD EXHAUST AIR DAMPER COMMAND BLK 18 RET SL5
RED 9AC
R1 6 9DC
19 VO2 SL5
20
10AC

Designed by:
10DC

Software by:
Checked by:
Contractor:
S3

Engineer:
Architect:
S3
21 VO3 SL5
22
11AC

COLO-AHU Panel IO Detail -


11DC

National And Strategic Accounts


23 VO4 SL5
24
12AC
12DC

5
602 AHU Panel.vsd 5/27/2022

5/27/2022
Last Printed
Last Saved
Job Number

Sheet Number
File Name

602-5
Panel Continued on Next Page
Label wiring, cabling, and conduit with point name at each end within 5 cm (2 in.)
1
of termination.
Electric. Their use or reproduction without prior consent of
COLO-AHU Panel IO Detail - 6

These drawings and designs are the property of Schneider

the company is strictly forbidden.


Panel Continued on Previous Page

TB-06
1
Top Bottom
## 1 VO1 SL6
SC01.SPD SUPPLY FAN SPEED COMMAND
## 2 RET SL6
1AC X5H TB-PA
1DC Y1+ TB-PA

Date:
WHT 3 VO2 SL6
TD03.CMD RETURN AIR DAMPER COMMAND BLK 4 X6N TB-PA
RED 2AC 5 TB-06

Preliminary
2DC TB-06 3
S1 TB-06 2 7 TB-06
S1 TB-06 1
WHT 5 VO3 SL6
TD01.CMD OUTSIDE AIR DAMPER A COMMAND BLK 6 Y2- TB-PA
1 2 3 4 5 6 7 8 9 10 11 12
RED 3AC

CO1

CO2

CO3

CO4
RET

RET

RET

RET
VO1

VO2

VO3

VO4
3DC
WHT 7 VO4 SL6
TD02.CMD OUTSIDE AIR DAMPER B COMMAND BLK 8
RED 4AC 1 2 3 4
Analog Outputs
4DC
WHT 9 VO5 SL6
Schneider Electric

# Change:
ND01.CMD FACE DAMPER COMMAND BLK 10 RET SL6

Revision:
RED 5AC SXW AO-8-H
5DC SL6
WHT 11 VO6 SL6
Analog Outputs

1
2
3
4
5
ND02.CMD BYPASS DAMPER COMMAND BLK 12 5 6 7 8
RED 6AC
6DC

CO5

CO6

CO7

CO8
RET

RET

RET

RET
VO5

VO6

VO7

VO8
S2
S2
13 14 15 16 17 18 19 20 21 22 23 24
13 VO7 SL6
14
7AC TB-06 9

5/26/2022
5/26/2022
5/26/2022
7DC TB-06 10 15 TB-06
15 VO8 SL6 TB-06 11
16 13 TB-06
8AC
8DC

Date:
Date:
Date:
Designed by:
Software by:
Checked by:
Contractor:
Engineer:
Architect:

COLO-AHU Panel IO Detail -


National And Strategic Accounts

6
602 AHU Panel.vsd 5/27/2022

5/27/2022
Last Printed
Last Saved
Job Number

Sheet Number
File Name

602-6
Panel Continued on Next Page
Label wiring, cabling, and conduit with point name at each end within 5 cm (2 in.)
1
of termination.
Electric. Their use or reproduction without prior consent of
COLO-AHU Panel IO Detail - 7

These drawings and designs are the property of Schneider

the company is strictly forbidden.


Panel Continued on Previous Page

TB-07
1
1 NC1 SL7
BLK 2 X8N TB-PA
LCV01.OC NPW MAKEUP WATER VALVE
RED 3 NO1 SL7
4 NC2 SL7

Date:
BLK 5 TB-07 6 7 TB-07
LCV02.OC CWD DRAIN VALVE
RED 6 NO2 SL7
7 NC3 SL7 TB-07 4 9 TB-07

Preliminary
BLK 8 TB-07 3 10 TB-07
CCV01.OC BLEED VALVE
RED 9 NO3 SL7 TB-PA X7H
10 NC4 SL7 TB-07 1 12 TB-07
## 11
TB##
EP01.SS EVAP COOLER PUMP START/STOP
## 12 NO4 SL7
1 2 3 4 5 6 7 8 9 10 11 12
13 NC5 SL7

COM

COM

COM

COM
NO1

NO2

NO3

NO4
NC1

NC2

NC3

NC4
WHT/yl 14
SC01.SS SUPPLY FAN START/STOP
WHT/bl 15 NO5 SL7
16 NC6 SL7
17 1 2 3 4
Digital Outputs
18 NO6 SL7
19 NC7 SL7
Schneider Electric

# Change:
20

Revision:
21 NO7 SL7 SXW DO-FC-8-H
22 NC8 SL7 SL7
23
Digital Outputs

1
2
3
4
5
24 NO8 SL7 5 6 7 8

COM

COM

COM

COM
NO5

NO6

NO7

NO8
NC5

NC6

NC7

NC8
13 14 15 16 17 18 19 20 21 22 23 24

TB-07 13 24 TB-07

5/26/2022
5/26/2022
5/26/2022
TB-PA X7H
TB-07 15 22 TB-07
TB-07 16 21 TB-07

TB-07 18 19 TB-07

Date:
Date:
Date:
Designed by:
Software by:
Checked by:
Contractor:
Engineer:
Architect:

COLO-AHU Panel IO Detail -


National And Strategic Accounts

7
602 AHU Panel.vsd 5/27/2022

5/27/2022
Last Printed
Last Saved
Job Number

Sheet Number
File Name

602-7
Panel Continued on Next Page
Label wiring, cabling, and conduit with point name at each end within 5 cm (2 in.)
1
of termination.
Low Voltage Notes

Electric. Their use or reproduction without prior consent of


COLO-AHU Panel Layout - Main

These drawings and designs are the property of Schneider


Conduit Entry Area
Panel label to be shipped loose with panel and to be mounted on the custom
1
AHU enclosure in the field.

the company is strictly forbidden.


6" 1'-1/4" 6"

44.00 x 1.00

37.06 x 1.00
12.25 x 1.50

DUCT2

DUCT1
DUCT1
7 5/8"

TB-07
11.50 x 1.25 PANEL LABEL

Date:
SL1 SL2 SL3

Preliminary
12.25 x 1.50

DUCT2
TB-03

7 5/8"

11.50 x 1.25

# Change:
Revision:

1
2
3
4
5
SL4 SL5 SL6

12.25 x 1.50

DUCT2

5/26/2022
5/26/2022
5/26/2022
TB-04

47.2in.
F-0
11.50 x 1.25

7 5/8"

Date:
Date:
Date:
SL7

12.79 x 1.50

Designed by:
Software by:
Checked by:
Contractor:
Engineer:
Architect:
DUCT2

National And Strategic Accounts


PH01

COLO-AHU Panel Layout -


TB-05

6.79 x 1.25

8 1/8"
DUCT2

PB1

Main
R1 LR1
Part Number Qty Description Manufacturer
----------------------------------------------------------------------------------------------------------------------------------------------------
37.05 x 1.50

AI-PW62 1 TAHUYA Power Adapter AI Link


AI-SR620 1 TAHUYA Adapter AI Link
20.82 x 1.00
FKIT-VMD3B-F24A 1 SOCKET RELAY 3PDT Veris Industries
GMD-500-R 1 500 mA Fuse Eaton
DUCT1 KEL-T1-1030W 1 1INX3INX6.5FT WHITE DUCT W/COV Iboco
5.95 x 1.00
DUCT1

M9F42104 5 4 Amp CB Schneider Electric


NSYTRAABV35 2 END BRACKET SCREW TYPE Square D
TB-06

TB-PA NSYTRAC22 1 END COVER Square D


NSYTRV42 1 6MM TERMINAL BLOCK GRAY Square D

602 AHU Panel.vsd 5/27/2022

5/27/2022
NSYTRV42SF5 1 TERMINAL BLOCK GREY Square D

Last Printed
Last Saved
5.95in. PAS01 1 PRESS DRY SWITCH .08-1.2"WC Veris Industries
RY2KS-UC-AC24 1 Latching Relay IDEC
SXWAO8HXX10001 1 AO-8-H 8 ANALOG OUT V/mA HAND Schneider Electric
SXWASPXXX10001 1 SMARTX CONTROLLER AS-P Schneider Electric
44.00 x 1.50

SXWDOC8XX10001 1 DO-FC-8 8 DIG OUT FORM C Schneider Electric

Job Number
SXWPS24VX10001 1 PS-24V POWER SUPPLY 24VAC/VDC Schneider Electric
29.30 x 1.00
SXWSCABLE10003 2 S-CABLE 0.75M ANGLE Schneider Electric
SXWTBASW110002 1 TB-ASP-W1 TERM BASE ASP W1 Schneider Electric
DUCT1

Sheet Number
SXWTBIOW110001 5 TB-IO-W1 TERM BASE I/O W1 Schneider Electric

File Name
SXWTBPSW110001 1 TB-PS-W1 TERM BASE PWR SUP W1 Schneider Electric

602-8
SXWUI16XX10001 2 UI-16 16 UNIVERSAL IN Schneider Electric
SXWUI8A4H10001 1 UI-8/AO-4-H UI/AO V/mA HAND Schneider Electric
SY4S-05 1 Latching Relay Base IDEC
31.5in.
Electric. Their use or reproduction without prior consent of
COLO 1 Panel Power Detail

These drawings and designs are the property of Schneider

the company is strictly forbidden.


PNL1

Date:
Preliminary
TB-PA
X1H CB8

24VAC
X3H X1H
Wired from 24VAC
X3H
XFR1 Wired to
X3H
End Devices
X2N X4N X2N
X4N
X4N
G
TB-PA
X3H CB9

# Change:
24VAC

Revision:
X5H X3H
Wired from 24VAC
X5H
XFR2 Wired to
X5H
End Devices
X4N X6N X4N

1
2
3
4
5
X6N
X6N
G
TB-PA
X5H CB10

24VAC
X7H X5H
Wired from 24VAC
X7H

5/26/2022
5/26/2022
5/26/2022
XFR3 Wired to
X7H
End Devices
X6N X8N X6N
X8N
X8N
G
TB-PA

Date:
Date:
Date:
Y1+ CB11

24VDC
Y1+ Y1+
Wired from 24VDC
Y1+
PS1 Wired to
Y2-
End Devices
Y2- Y2- Y2-
G

Designed by:
Software by:
Checked by:
Contractor:
Engineer:
Architect:
Panel Continued on Next Page

National And Strategic Accounts

COLO 1 Panel Power Detail


UL Panel Details

5/27/2022

5/27/2022
Last Printed
Last Saved
Panel:_____________________
CKT#:_____________________
MAX VOLTAGE: 24v

Job Number

603 COLO 1 Panel.vsd


SSCR = 10kA
TOTAL FLA : 9.40A

Sheet Number
File Name
CB8 (24VAC) = 4.00A

603-1
CB9 (24VAC) = 4.00A
CB10 (24VAC) = 4.00A
CB11 (24VDC) = 4.00A
See Network Architecture
See Network Architecture

Room#
Room#

Switch ##
Switch ##

Port#
Port#
TB-C

E2
E1

ETH2
ETH1
AS-P

TAHUYA
TB-PA
TB-PA
TB-PA
TB-PA
Y2-

X1H
X2N
Y1+

L/+
2

L/-
4

GND
F-0
1A Fuse

SXW PS-24V
SL1
Schneider Electric
COLO 1 Panel IO Detail - 1 & 2

TX/RX+
Host
2

TX/RX-
Device
Com A
3

RET
4

BIAS+
5

RS-485

TX/RX+
6

TX/RX-
Com B
7

RET
1 2 3 4 5 6 7 8

TX/RX+
TX/RX-
10/100
SXW AS-P
RS-485

Ethernet 1
9 10

RET
LON

SL2

LON-1
Schneider Electric
11 12

LON-2
TP/FT

10/100
Ethernet 2
TAHUYA Adapter

Panel Continued on Next Page


Panel Continued on Previous Page

TAHUYA

Job Number
National And Strategic Accounts Architect:
Revision: Preliminary
Engineer:
# Change: Date:
File Name Last Saved Contractor:
1
603 COLO 1 Panel.vsd 5/27/2022 Designed by: Date: 5/26/2022 2
3 These drawings and designs are the property of Schneider
Sheet Number Last Printed Software by: Date: 5/26/2022 Electric. Their use or reproduction without prior consent of
COLO 1 Panel IO Detail - 1 & 4
the company is strictly forbidden.
Checked by: Date: 5/26/2022 5
603-2 5/27/2022 2
Electric. Their use or reproduction without prior consent of
COLO 1 Panel IO Detail - 3

These drawings and designs are the property of Schneider

the company is strictly forbidden.


Panel Continued on Previous Page

TB-03
1
Top Bottom
mA RTN 1 UI1 SL3
PT01.SRP SERVER RACK DP 01 TB##
PWR 2 RET SL3
1AC X3H TB-PA TB-03 7 9 TB-03
1DC Y1+ TB-PA

Date:
mA RTN 3 UI2 SL3
PT02.SRP SERVER RACK DP 02
PWR 4 X4N TB-PA TB-03 5 11 TB-03
2AC TB-03 3 13 TB-03

Preliminary
2DC TB-03 2
S1
S1 TB-03 1 15 TB-03
mA RTN 5 UI3 SL3
PT03.SRP SERVER RACK DP 03
PWR 6 Y2- TB-PA
1 2 3 4 5 6 7 8 9 10 11 12
3AC

RET

RET

RET

RET
UI1

UI2

UI3

UI4

UI5

UI6

UI7

UI8
3DC
mA RTN 7 UI4 SL3
PT06.HAP HOT AISLE TO OUTSIDE DP 01
PWR 8
4AC 1 2 3 4 5 6 7 8
Universal Inputs
4DC

TT01.CAT COLD AISLE TEMP 01


- 9 UI5 SL3
Schneider Electric

# Change:
+ 10

Revision:
5AC SXW UI-16
5DC
SL3
- 11 UI6 SL3
TT02.CAT COLD AISLE TEMP 02 Universal Inputs

1
2
3
4
5
+ 12 9 10 11 12 13 14 15 16
6AC
6DC

UI10

UI11

UI12

UI13

UI14

UI15

UI16
RET

RET

RET

RET
UI9
S2
S2
13 14 15 16 17 18 19 20 21 22 23 24
- 13 UI7 SL3
TT03.CAT COLD AISLE TEMP 03
+ 14
7AC TB-03 17 31 TB-03

5/26/2022
5/26/2022
5/26/2022
7DC
- 15 UI8 SL3 TB-03 18
TT07.HAT HOT AISLE TEMP 01
+ 16 TB-03 19 29 TB-03
8AC TB-03 21 27 TB-03
8DC
- 17 UI9 SL3
TT08.HAT HOT AISLE TEMP 02
+ 18 RET SL3 TB-03 23 25 TB-03

Date:
Date:
Date:
9AC
9DC
- 19 UI10 SL3
TT09.HAT HOT AISLE TEMP 03
+ 20
10AC
10DC
S3

Designed by:
S3

Software by:
Checked by:
Contractor:
mA 21 UI11 SL3

Engineer:
Architect:
NT01.CAH COLD AISLE RH 01
VIN 22
11AC
11DC
mA 23 UI12 SL3
NT02.CAH COLD AISLE RH 02
VIN 24

National And Strategic Accounts

COLO 1 Panel IO Detail - 3


12AC
12DC
mA 25 UI13 SL3
NT03.CAH COLD AISLE RH 03
VIN 26
13AC
13DC
23 27 UI14 SL3
FT01.NPW NPW FLOW
24 28
14AC
14DC
S4
S4
17 29 UI15 SL3
FQ01.NPW NPW FLOW TOTAL
18 30
15AC
15DC
BLACK 31 UI16 SL3
PT01.NPW NPW DOWNSTEAM PRESSURE
WHITE 32
16AC

5/27/2022

5/27/2022
16DC

Last Printed
Last Saved
Job Number

603 COLO 1 Panel.vsd


Sheet Number
File Name

603-3
Panel Continued on Next Page

Label wiring, cabling, and conduit with point name at each end within 5 cm (2 in.)
1
of termination.
Electric. Their use or reproduction without prior consent of
COLO 1 Panel IO Detail - 4

These drawings and designs are the property of Schneider

the company is strictly forbidden.


Panel Continued on Previous Page

TB-04
1
Top Bottom
mA RTN 1 UI1 SL4
PT04.SRP SERVER RACK DP 04 TB##
PWR 2 RET SL4
1AC X3H TB-PA TB-04 7 9 TB-04
1DC Y1+ TB-PA

Date:
mA RTN 3 UI2 SL4
PT05.SRP SERVER RACK DP 05
PWR 4 X4N TB-PA TB-04 5 11 TB-04
2AC TB-04 3 13 TB-04

Preliminary
2DC TB-04 2
S1
S1 TB-04 1 15 TB-04
mA RTN 5 UI3 SL4
PT07.HAP HOT AISLE TO OUTSIDE DP 02
PWR 6 Y2- TB-PA
1 2 3 4 5 6 7 8 9 10 11 12
3AC

RET

RET

RET

RET
UI1

UI2

UI3

UI4

UI5

UI6

UI7

UI8
3DC
- 7 UI4 SL4
TT04.CAT COLD AISLE TEMP 04
+ 8
4AC 1 2 3 4 5 6 7 8
Universal Inputs
4DC

TT05.CAT COLD AISLE TEMP 05


- 9 UI5 SL4
Schneider Electric

# Change:
+ 10

Revision:
5AC SXW UI-16
5DC
SL4
- 11 UI6 SL4
TT06.CAT COLD AISLE TEMP 06 Universal Inputs

1
2
3
4
5
+ 12 9 10 11 12 13 14 15 16
6AC
6DC

UI10

UI11

UI12

UI13

UI14

UI15

UI16
RET

RET

RET

RET
UI9
S2
S2
13 14 15 16 17 18 19 20 21 22 23 24
- 13 UI7 SL4
TT10.HAT HOT AISLE TEMP 04
+ 14
7AC TB-04 17 31 TB-04

5/26/2022
5/26/2022
5/26/2022
7DC
- 15 UI8 SL4 TB-04 18
TT11.HAT HOT AISLE TEMP 05
+ 16 TB-04 19 29 TB-04
8AC TB-04 21 27 TB-04
8DC
mA 17 UI9 SL4
NT04.CAH COLD AISLE RH 04
VIN 18 RET SL4 TB-04 23 25 TB-04

Date:
Date:
Date:
9AC
9DC
mA 19 UI10 SL4
NT05.CAH COLD AISLE RH 05
VIN 20
10AC
10DC
S3

Designed by:
S3

Software by:
Checked by:
Contractor:
mA 21 UI11 SL4

Engineer:
Architect:
NT06.CAH COLD AISLE RH 06
VIN 22
11AC
11DC
- 23 UI12 SL4
TT13.VT ENTRY VESTIBULE TEMP
+ 24

National And Strategic Accounts

COLO 1 Panel IO Detail - 4


12AC
12DC
- 25 UI13 SL4
BATT1-TT01 BATTERY ROOM TEMP 01
+ 26
13AC
13DC
- 27 UI14 SL4
ELEC1-TT01 ELECTRIC ROOM TEMP 01
+ 28
14AC
14DC
S4
S4
- 29 UI15 SL4
ELEC1-TT02 ELECTRIC ROOM TEMP 02
+ 30
15AC
15DC

BATT1-EF01. NO 31 UI16 SL4


BATTERY ROOM EXHAUST FAN 01 STATUS
STS COM 32
16AC

5/27/2022

5/27/2022
16DC

Last Printed
Last Saved
Job Number

603 COLO 1 Panel.vsd


Sheet Number
File Name

603-4
Panel Continued on Next Page

Label wiring, cabling, and conduit with point name at each end within 5 cm (2 in.)
1
of termination.
Electric. Their use or reproduction without prior consent of
COLO 1 Panel IO Detail - 5

These drawings and designs are the property of Schneider

the company is strictly forbidden.


Panel Continued on Previous Page

Top
TB-05
1
Top Bottom
mA RTN 1 UI1 SL5
PT08.HAP HOT AISLE TO OUTSIDE DP 03 TB##
PWR 2 RET SL5

Date:
1AC X3H TB-PA
1DC Y1+ TB-PA
8 T- 3 UI2 SL5 21 TB-05

Preliminary
TT14.OAT OUTDOOR AIR TEMP
7 T+ 4 X4N TB-PA TB-05 19
2AC TB-05 18
2DC TB-05 17 23 TB-05
S1
S1
1 2 3 4 5 6 7 8 9 10 11 12
6 HUM- 5 UI3 SL5
NT08.OAH OUTDOOR AIR HUMIDITY

CO1

CO2

CO3

CO4
RET

RET

RET

RET
VO1

VO2

VO3

VO4
5 HUM + 6 Y2- TB-PA
3AC
3DC
Org 7 UI4 SL5 1 2 3 4
PD01.FB RELIEF DAMPER 01 FEEDBACK Analog Outputs
Blk 8
4AC
Schneider Electric

# Change:
4DC

Revision:
PD02.FB RELIEF DAMPER 02 FEEDBACK
Org 9 UI5 SL5 SXW UI-8/AO-4-H
Blk 10
SL5
5AC
Universal Inputs

1
2
3
4
5
5DC 1 2 3 4 5 6 7 8
NO 11 UI6 SL5
CC-QS01.PA PRIMARY POWER AVAILABLE
COM 12

RET

RET

RET

RET
UI1

UI2

UI3

UI4

UI5

UI6

UI7

UI8
6AC
6DC
13 14 15 16 17 18 19 20 21 22 23 24
S2
S2
NO 13 UI7 SL5 TB-05 1 15 TB-05
CC-QS02.PA SECONDARY POWER AVAILABLE

5/26/2022
5/26/2022
5/26/2022
COM 14
7AC TB-05 2
7DC TB-05 3 13 TB-05
4 15 UI8 SL5 TB-05 5 11 TB-05
PH01.ALM RETURN PRESSURE SWITCH RTN
12 16
8AC
8DC TB-05 7 9 TB-05

Date:
Date:
Date:
WHT 17 VO1 SL5
PD01.CMD RELIEF AIR DAMPER A COMMAND BLK 18 RET SL5
RED 9AC
R1 6 9DC
WHT 19 VO2 SL5
PD02.CMD RELIEF AIR DAMPER B COMMAND BLK 20
RED 10AC
R1 5

Designed by:
10DC

Software by:
Checked by:
Contractor:
S3

Engineer:
Architect:
S3
SIG 21 VO3 SL5
EH01.CMD ELECTRIC DUCT HEATER COMMAND
OV 22
11AC
11DC

National And Strategic Accounts

COLO 1 Panel IO Detail - 5


23 CO4 SL5
24
12AC
12DC

5/27/2022

5/27/2022
Last Printed
Last Saved
Job Number

603 COLO 1 Panel.vsd


Sheet Number
File Name

603-5
Panel Continued on Next Page

Label wiring, cabling, and conduit with point name at each end within 5 cm (2 in.)
1
of termination.
Electric. Their use or reproduction without prior consent of
COLO 1 Panel IO Detail - 6

These drawings and designs are the property of Schneider

the company is strictly forbidden.


Panel Continued on Previous Page

TB-06
1
Top Bottom
SIG 1 UI1 SL6
NPW.CON NPW CONDUCTIVITY TB##
RET 2 RET SL6
1AC X3H TB-PA TB-06 7 9 TB-06
1DC Y1+ TB-PA

Date:
SIG 3 UI2 SL6
NPW.PH NPW PH
RET 4 X4N TB-PA TB-06 5 11 TB-06
2AC TB-06 3 13 TB-06

Preliminary
2DC TB-06 2
S1
S1 TB-06 1 15 TB-06
SIG 5 UI3 SL6
NPW.ORP NPW ORP
RET 6 Y2- TB-PA
1 2 3 4 5 6 7 8 9 10 11 12
3AC

RET

RET

RET

RET
UI1

UI2

UI3

UI4

UI5

UI6

UI7

UI8
3DC
SIG 7 UI4 SL6
NPW.FCL NPW FREE CHLORINE
RET 8
4AC 1 2 3 4 5 6 7 8
Universal Inputs
4DC

NPW.TCL NPW TOTAL CHLORINE


SIG 9 UI5 SL6
Schneider Electric

# Change:
RET 10

Revision:
5AC SXW UI-16
5DC
SL6
11 UI6 SL6
Universal Inputs

1
2
3
4
5
12 9 10 11 12 13 14 15 16
6AC
6DC

UI10

UI11

UI12

UI13

UI14

UI15

UI16
RET

RET

RET

RET
UI9
S2
S2
13 14 15 16 17 18 19 20 21 22 23 24
13 UI7 SL6
14
7AC TB-06 17 31 TB-06

5/26/2022
5/26/2022
5/26/2022
7DC
15 UI8 SL6 TB-06 18
16 TB-06 19 29 TB-06
8AC TB-06 21 27 TB-06
8DC
17 UI9 SL6
18 RET SL6 TB-06 23 25 TB-06

Date:
Date:
Date:
9AC
9DC
19 UI10 SL6
20
10AC
10DC
S3

Designed by:
S3

Software by:
Checked by:
Contractor:
21 UI11 SL6

Engineer:
Architect:
22
11AC
11DC
23 UI12 SL6
24

National And Strategic Accounts

COLO 1 Panel IO Detail - 6


12AC
12DC
25 UI13 SL6
26
13AC
13DC
27 UI14 SL6
28
14AC
14DC
S4
S4
29 UI15 SL6
30
15AC
15DC
31 UI16 SL6
32
16AC

5/27/2022

5/27/2022
16DC

Last Printed
Last Saved
Job Number

603 COLO 1 Panel.vsd


Sheet Number
File Name

603-6
Panel Continued on Next Page

Label wiring, cabling, and conduit with point name at each end within 5 cm (2 in.)
1
of termination.
Low Voltage

Electric. Their use or reproduction without prior consent of


COLO 1 Panel Layout - Main

These drawings and designs are the property of Schneider


Conduit Entry Area

the company is strictly forbidden.


29.5in.
29.45 x 1.50

5.5in. DUCT2 5.5in.

28.50 x 1.50

28.50 x 1.50

21.55 x 1.50

28.50 x 1.50
12.38 x 1.25

Date:
Preliminary
TB-05
SL1 SL2 SL3
12.55 x 1.00

DUCT1

12.38 x 1.25 7.8in.

# Change:
6.8in.

Revision:
TB-03

1
2
3
4
5
SL4 SL5 SL6
12.55 x 1.00

DUCT1

TB-06

5/26/2022
5/26/2022
5/26/2022
37.5in. 12.38 x 1.25 39.4in.

F-0
6.0in.

DUCT2

Date:
Date:
Date:
DUCT2
19.50 x 1.00
TB-04

DUCT1
DUCT2

DUCT2

Designed by:
Software by:
Checked by:
Contractor:
Engineer:
Architect:
6.0in.

National And Strategic Accounts

COLO 1 Panel Layout - Main


29.45 x 1.00

DUCT1
5.50 x 1.00

5.50 x 1.00
TB-PA
DUCT1

DUCT1
5.5in.

Part Number Qty Description Manufacturer


----------------------------------------------------------------------------------------------------------------------------------------------------
AI-PW62 1 TAHUYA Power Adapter AI Link
29.45 x 1.00 AI-SR620 1 TAHUYA Adapter AI Link
DUCT1 GMD-500-R 1 500 mA Fuse Eaton
PNL4 KEL-T1-1030G 2 1INX3INX6.5FT GRAY DUCT W/COVE Iboco
M9F42104 6 4 Amp CB Schneider Electric

5/27/2022

5/27/2022
NSYAEDL405S3D 1 LOCK AND KEY SET Schneider Electric

Last Printed
Last Saved
NSYTRAABV35 2 END BRACKET SCREW TYPE Square D
NSYTRAC22 1 END COVER Square D
31.5in. NSYTRV42 1 6MM TERMINAL BLOCK GRAY Square D
NSYTRV42SF5 1 TERMINAL BLOCK GREY Square D
SEBOX393210P 1 ENCL 39X32X10 NEMA 4 W/ PERF Schneider Electric

Job Number
SXWASPXXX10001 1 SMARTX CONTROLLER AS-P Schneider Electric

603 COLO 1 Panel.vsd


SXWPS24VX10001 1 PS-24V POWER SUPPLY 24VAC/VDC Schneider Electric
SXWSCABLE10003 1 S-CABLE 0.75M ANGLE Schneider Electric

Sheet Number
SXWTBASW110002 1 TB-ASP-W1 TERM BASE ASP W1 Schneider Electric

File Name
SXWTBIOW110001 3 TB-IO-W1 TERM BASE I/O W1 Schneider Electric

603-7
SXWTBPSW110001 1 TB-PS-W1 TERM BASE PWR SUP W1 Schneider Electric
SXWUI16XX10001 3 UI-16 16 UNIVERSAL IN Schneider Electric
SXWUI8A4H10001 1 UI-8/AO-4-H UI/AO V/mA HAND Schneider Electric
PNL4

31.5in.
PANEL LABEL

39.4in.
COLO 1 Panel Layout - Door

Job Number
National And Strategic Accounts Architect:
Revision: Preliminary
Engineer:
# Change: Date:
File Name Last Saved Contractor:
1
603 COLO 1 Panel.vsd 5/27/2022 Designed by: Date: 5/26/2022 2
3 These drawings and designs are the property of Schneider
Sheet Number Last Printed Software by: Date: 5/26/2022 Electric. Their use or reproduction without prior consent of
4
the company is strictly forbidden.
COLO 1 Panel Layout - Door Checked by: Date: 5/26/2022 5
603-8 5/27/2022
Electric. Their use or reproduction without prior consent of
SHELL Panel Power Detail

These drawings and designs are the property of Schneider

the company is strictly forbidden.


PNL1

Date:
Preliminary
TB-PA
X1H CB8

24VAC
X3H X1H
Wired from 24VAC
X3H
XFR1 Wired to
X3H
End Devices
X2N X4N X2N
X4N
X4N
G
TB-PA
X3H CB9

# Change:
24VAC

Revision:
X5H X3H
Wired from 24VAC
X5H
XFR2 Wired to
X5H
End Devices
X4N X6N X4N

1
2
3
4
5
X6N
X6N
G
TB-PA
X5H CB10

24VAC
X7H X5H
Wired from 24VAC
X7H

5/26/2022
5/26/2022
5/26/2022
XFR3 Wired to
X7H
End Devices
X6N X8N X6N
X8N
X8N
G
TB-PA

Date:
Date:
Date:
Y1+ CB11

24VDC
Y1+ Y1+
Wired from 24VDC
Y1+
PS1 Wired to
Y2-
End Devices
Y2- Y2- Y2-
G

Designed by:
Software by:
Checked by:
Contractor:
Engineer:
Architect:
Panel Continued on Next Page

National And Strategic Accounts

SHELL Panel Power Detail


UL Panel Details

605 SHELL Panel.vsd 5/27/2022

5/27/2022
Last Printed
Last Saved
Panel:_____________________
CKT#:_____________________
MAX VOLTAGE: 24v

Job Number
SSCR = 10kA
TOTAL FLA : 9.40A

Sheet Number
CB8 (24VAC) = 4.00A

File Name

605-1
CB9 (24VAC) = 4.00A
CB10 (24VAC) = 4.00A
CB11 (24VDC) = 4.00A
See Network Architecture
See Network Architecture

Room#
Room#

Switch ##
Switch ##

Port#
Port#
TB-C

E2
E1

ETH2
ETH1
AS-P

TAHUYA
TB-PA
TB-PA
TB-PA
TB-PA
Y2-

X1H
X2N
Y1+

L/+
2

L/-
4

GND
F-0
1A Fuse

SXW PS-24V
SL1
Schneider Electric
SHELL Panel IO Detail - 1 & 2

TX/RX+
Host
2

TX/RX-
Device
Com A
3

RET
4

BIAS+
5

RS-485

TX/RX+
6

TX/RX-
Com B
7

RET
1 2 3 4 5 6 7 8

TX/RX+
TX/RX-
10/100
SXW AS-P
RS-485

Ethernet 1
9 10

RET
LON

SL2

LON-1
Schneider Electric
11 12

LON-2
TP/FT

10/100
Ethernet 2
TAHUYA Adapter

Panel Continued on Next Page


Panel Continued on Previous Page

TAHUYA

Job Number
National And Strategic Accounts Architect:
Revision: Preliminary
Engineer:
# Change: Date:
File Name Last Saved Contractor:
1
605 SHELL Panel.vsd 5/27/2022 Designed by: Date: 5/26/2022 2
3 These drawings and designs are the property of Schneider
Sheet Number Last Printed Software by: Date: 5/26/2022 Electric. Their use or reproduction without prior consent of
SHELL Panel IO Detail - 1 & 4
the company is strictly forbidden.
Checked by: Date: 5/26/2022 5
605-2 5/27/2022 2
Electric. Their use or reproduction without prior consent of
SHELL Panel IO Detail - 3

These drawings and designs are the property of Schneider

the company is strictly forbidden.


Panel Continued on Previous Page

TB-03
1
Top Bottom
- 1 UI1 SL3
COLO2-TT01.ST COLO2 SHELL TEMP (REMOVED PHASE 2) TB##
+ 2 RET SL3
1AC X3H TB-PA TB-03 7 9 TB-03
1DC Y1+ TB-PA

Date:
- 3 UI2 SL3
COLO3-TT01.ST COLO3 SHELL TEMP (REMOVED PHASE 3)
+ 4 X4N TB-PA TB-03 5 11 TB-03
2AC TB-03 3 13 TB-03

Preliminary
2DC TB-03 2
S1
S1 TB-03 1 15 TB-03
- 5 UI3 SL3
COLO4-TT01.ST COLO4 SHELL TEMP (REMOVED PHASE 4)
+ 6 Y2- TB-PA
1 2 3 4 5 6 7 8 9 10 11 12
3AC

RET

RET

RET

RET
UI1

UI2

UI3

UI4

UI5

UI6

UI7

UI8
3DC
- 7 UI4 SL3
COLO5-TT01.ST COLO5 SHELL TEMP (REMOVED PHASE 5)
+ 8
4AC 1 2 3 4 5 6 7 8
Universal Inputs
4DC

COLO3-CE4-TT15.FRT COLO3 FIRE RISER ROOM TEMP (REMOVED PHASE 3)


- 9 UI5 SL3
Schneider Electric

# Change:
+ 10

Revision:
5AC SXW UI-16
5DC
SL3
23 11 UI6 SL3
COLO5-CE1-FT01.NPW NPW FLOW (REMOVED PHASE 5) Universal Inputs

1
2
3
4
5
24 12 9 10 11 12 13 14 15 16
6AC
6DC

UI10

UI11

UI12

UI13

UI14

UI15

UI16
RET

RET

RET

RET
UI9
S2
S2
13 14 15 16 17 18 19 20 21 22 23 24
17 13 UI7 SL3
COLO5-CE1-FQ01.NPW NPW FLOW TOTAL (REMOVED PHASE 5)
18 14
7AC TB-03 17 31 TB-03

5/26/2022
5/26/2022
5/26/2022
7DC
15 UI8 SL3 TB-03 18
16 TB-03 19 29 TB-03
8AC TB-03 21 27 TB-03
8DC
23 17 UI9 SL3
COLO5-CE4-FT01.NPW NPW FLOW (REMOVED PHASE 5)
24 18 RET SL3 TB-03 23 25 TB-03

Date:
Date:
Date:
9AC
9DC
17 19 UI10 SL3
COLO5-CE4-FQ01.NPW NPW FLOW TOTAL (REMOVED PHASE 5)
18 20
10AC
10DC
S3

Designed by:
S3

Software by:
Checked by:
Contractor:
21 UI11 SL3

Engineer:
Architect:
22
11AC
11DC
- 23 UI12 SL3
COLO5-CE4-TT15.FRT COLO5 FIRE RISER ROOM TEMP (REMOVED PHASE 5)
+ 24

National And Strategic Accounts

SHELL Panel IO Detail - 3


12AC
12DC
25 UI13 SL3
26
13AC
13DC
27 UI14 SL3
28
14AC
14DC
S4
S4
29 UI15 SL3
30
15AC
15DC
31 UI16 SL3
32
16AC

605 SHELL Panel.vsd 5/27/2022

5/27/2022
16DC

Last Printed
Last Saved
Job Number

Sheet Number
File Name

605-3
Panel Continued on Next Page

Label wiring, cabling, and conduit with point name at each end within 5 cm (2 in.)
1
of termination.
Electric. Their use or reproduction without prior consent of
SHELL Panel IO Detail - 4

These drawings and designs are the property of Schneider

the company is strictly forbidden.


Panel Continued on Previous Page

TB-04
Top Bottom
1 UI1 SL4
TB##
2 RET SL4
1AC X3H TB-PA TB-04 7 9 TB-04
1DC Y1+ TB-PA

Date:
3 UI2 SL4
4 X4N TB-PA TB-04 5 11 TB-04
2AC TB-04 3 13 TB-04

Preliminary
2DC TB-04 2
S1
S1 TB-04 1 15 TB-04
5 UI3 SL4
6 Y2- TB-PA
1 2 3 4 5 6 7 8 9 10 11 12
3AC

RET

RET

RET

RET
UI1

UI2

UI3

UI4

UI5

UI6

UI7

UI8
3DC
7 UI4 SL4
8
4AC 1 2 3 4 5 6 7 8
Universal Inputs
4DC
9 UI5 SL4
Schneider Electric

# Change:
10

Revision:
5AC SXW UI-16
5DC
SL4
11 UI6 SL4
Universal Inputs

1
2
3
4
5
12 9 10 11 12 13 14 15 16
6AC
6DC

UI10

UI11

UI12

UI13

UI14

UI15

UI16
RET

RET

RET

RET
UI9
S2
S2
13 14 15 16 17 18 19 20 21 22 23 24
13 UI7 SL4
14
7AC TB-04 17 31 TB-04

5/26/2022
5/26/2022
5/26/2022
7DC
15 UI8 SL4 TB-04 18
16 TB-04 19 29 TB-04
8AC TB-04 21 27 TB-04
8DC
17 UI9 SL4
18 RET SL4 TB-04 23 25 TB-04

Date:
Date:
Date:
9AC
9DC
19 UI10 SL4
20
10AC
10DC
S3

Designed by:
S3

Software by:
Checked by:
Contractor:
21 UI11 SL4

Engineer:
Architect:
22
11AC
11DC
23 UI12 SL4
24

National And Strategic Accounts

SHELL Panel IO Detail - 4


12AC
12DC
25 UI13 SL4
26
13AC
13DC
27 UI14 SL4
28
14AC
14DC
S4
S4
29 UI15 SL4
30
15AC
15DC
31 UI16 SL4
32
16AC

605 SHELL Panel.vsd 5/27/2022

5/27/2022
16DC

Last Printed
Last Saved
Job Number

Sheet Number
File Name

605-4
Panel Continued on Next Page

Label wiring, cabling, and conduit with point name at each end within 5 cm (2 in.)
1
of termination.
Electric. Their use or reproduction without prior consent of
SHELL Panel IO Detail - 5

These drawings and designs are the property of Schneider

the company is strictly forbidden.


Panel Continued on Previous Page

TB-05
Top Bottom
1 UI1 SL5
TB##
2 RET SL5
1AC X3H TB-PA TB-05 7 9 TB-05
1DC Y1+ TB-PA

Date:
3 UI2 SL5
4 X4N TB-PA TB-05 5 11 TB-05
2AC TB-05 3 13 TB-05

Preliminary
2DC TB-05 2
S1
S1 TB-05 1 15 TB-05
5 UI3 SL5
6 Y2- TB-PA
1 2 3 4 5 6 7 8 9 10 11 12
3AC

RET

RET

RET

RET
UI1

UI2

UI3

UI4

UI5

UI6

UI7

UI8
3DC
7 UI4 SL5
8
4AC 1 2 3 4 5 6 7 8
Universal Inputs
4DC
9 UI5 SL5
Schneider Electric

# Change:
10

Revision:
5AC SXW UI-16
5DC
SL5
11 UI6 SL5
Universal Inputs

1
2
3
4
5
12 9 10 11 12 13 14 15 16
6AC
6DC

UI10

UI11

UI12

UI13

UI14

UI15

UI16
RET

RET

RET

RET
UI9
S2
S2
13 14 15 16 17 18 19 20 21 22 23 24
13 UI7 SL5
14
7AC TB-05 17 31 TB-05

5/26/2022
5/26/2022
5/26/2022
7DC
15 UI8 SL5 TB-05 18
16 TB-05 19 29 TB-05
8AC TB-05 21 27 TB-05
8DC
17 UI9 SL5
18 RET SL5 TB-05 23 25 TB-05

Date:
Date:
Date:
9AC
9DC
19 UI10 SL5
20
10AC
10DC
S3

Designed by:
S3

Software by:
Checked by:
Contractor:
21 UI11 SL5

Engineer:
Architect:
22
11AC
11DC
23 UI12 SL5
24

National And Strategic Accounts

SHELL Panel IO Detail - 5


12AC
12DC
25 UI13 SL5
26
13AC
13DC
27 UI14 SL5
28
14AC
14DC
S4
S4
29 UI15 SL5
30
15AC
15DC
31 UI16 SL5
32
16AC

605 SHELL Panel.vsd 5/27/2022

5/27/2022
16DC

Last Printed
Last Saved
Job Number

Sheet Number
File Name

605-5
Panel Continued on Next Page

Label wiring, cabling, and conduit with point name at each end within 5 cm (2 in.)
1
of termination.
Electric. Their use or reproduction without prior consent of
SHELL Panel IO Detail - 6

These drawings and designs are the property of Schneider

the company is strictly forbidden.


Panel Continued on Previous Page

TB-06
Top Bottom
1 UI1 SL6
TB##
2 RET SL6
1AC X3H TB-PA TB-06 7 9 TB-06
1DC Y1+ TB-PA

Date:
3 UI2 SL6
4 X4N TB-PA TB-06 5 11 TB-06
2AC TB-06 3 13 TB-06

Preliminary
2DC TB-06 2
S1
S1 TB-06 1 15 TB-06
5 UI3 SL6
6 Y2- TB-PA
1 2 3 4 5 6 7 8 9 10 11 12
3AC

RET

RET

RET

RET
UI1

UI2

UI3

UI4

UI5

UI6

UI7

UI8
3DC
7 UI4 SL6
8
4AC 1 2 3 4 5 6 7 8
Universal Inputs
4DC
9 UI5 SL6
Schneider Electric

# Change:
10

Revision:
5AC SXW UI-16
5DC
SL6
11 UI6 SL6
Universal Inputs

1
2
3
4
5
12 9 10 11 12 13 14 15 16
6AC
6DC

UI10

UI11

UI12

UI13

UI14

UI15

UI16
RET

RET

RET

RET
UI9
S2
S2
13 14 15 16 17 18 19 20 21 22 23 24
13 UI7 SL6
14
7AC TB-06 17 31 TB-06

5/26/2022
5/26/2022
5/26/2022
7DC
15 UI8 SL6 TB-06 18
16 TB-06 19 29 TB-06
8AC TB-06 21 27 TB-06
8DC
17 UI9 SL6
18 RET SL6 TB-06 23 25 TB-06

Date:
Date:
Date:
9AC
9DC
19 UI10 SL6
20
10AC
10DC
S3

Designed by:
S3

Software by:
Checked by:
Contractor:
21 UI11 SL6

Engineer:
Architect:
22
11AC
11DC
23 UI12 SL6
24

National And Strategic Accounts

SHELL Panel IO Detail - 6


12AC
12DC
25 UI13 SL6
26
13AC
13DC
27 UI14 SL6
28
14AC
14DC
S4
S4
29 UI15 SL6
30
15AC
15DC
31 UI16 SL6
32
16AC

605 SHELL Panel.vsd 5/27/2022

5/27/2022
16DC

Last Printed
Last Saved
Job Number

Sheet Number
File Name

605-6
Panel Continued on Next Page

Label wiring, cabling, and conduit with point name at each end within 5 cm (2 in.)
1
of termination.
Electric. Their use or reproduction without prior consent of
SHELL Panel IO Detail - 7

These drawings and designs are the property of Schneider

the company is strictly forbidden.


Panel Continued on Previous Page

TB-07
Top Bottom
1 UI1 SL7
TB##
2 RET SL7
1AC X3H TB-PA TB-07 7 9 TB-07
1DC Y1+ TB-PA

Date:
3 UI2 SL7
4 X4N TB-PA TB-07 5 11 TB-07
2AC TB-07 3 13 TB-07

Preliminary
2DC TB-07 2
S1
S1 TB-07 1 15 TB-07
5 UI3 SL7
6 Y2- TB-PA
1 2 3 4 5 6 7 8 9 10 11 12
3AC

RET

RET

RET

RET
UI1

UI2

UI3

UI4

UI5

UI6

UI7

UI8
3DC
7 UI4 SL7
8
4AC 1 2 3 4 5 6 7 8
Universal Inputs
4DC
9 UI5 SL7
Schneider Electric

# Change:
10

Revision:
5AC SXW UI-16
5DC
SL7
11 UI6 SL7
Universal Inputs

1
2
3
4
5
12 9 10 11 12 13 14 15 16
6AC
6DC

UI10

UI11

UI12

UI13

UI14

UI15

UI16
RET

RET

RET

RET
UI9
S2
S2
13 14 15 16 17 18 19 20 21 22 23 24
13 UI7 SL7
14
7AC TB-07 17 31 TB-07

5/26/2022
5/26/2022
5/26/2022
7DC
15 UI8 SL7 TB-07 18
16 TB-07 19 29 TB-07
8AC TB-07 21 27 TB-07
8DC
17 UI9 SL7
18 RET SL7 TB-07 23 25 TB-07

Date:
Date:
Date:
9AC
9DC
19 UI10 SL7
20
10AC
10DC
S3

Designed by:
S3

Software by:
Checked by:
Contractor:
21 UI11 SL7

Engineer:
Architect:
22
11AC
11DC
23 UI12 SL7
24

National And Strategic Accounts

SHELL Panel IO Detail - 7


12AC
12DC
25 UI13 SL7
26
13AC
13DC
27 UI14 SL7
28
14AC
14DC
S4
S4
29 UI15 SL7
30
15AC
15DC
31 UI16 SL7
32
16AC

605 SHELL Panel.vsd 5/27/2022

5/27/2022
16DC

Last Printed
Last Saved
Job Number

Sheet Number
File Name

605-7
Panel Continued on Next Page

Label wiring, cabling, and conduit with point name at each end within 5 cm (2 in.)
1
of termination.
Electric. Their use or reproduction without prior consent of
SHELL Panel IO Detail - 8

These drawings and designs are the property of Schneider

the company is strictly forbidden.


Panel Continued on Previous Page

TB-08
Top Bottom
1 VO1 SL8
2 RET SL8
1AC X3H TB-PA
1DC Y1+ TB-PA

Date:
3 VO2 SL8
4 X4N TB-PA
2AC 5 TB-08

Preliminary
2DC TB-08 3
S1 TB-08 2 7 TB-08
S1 TB-08 1
5 VO3 SL8
6 Y2- TB-PA
1 2 3 4 5 6 7 8 9 10 11 12
3AC

CO1

CO2

CO3

CO4
RET

RET

RET

RET
VO1

VO2

VO3

VO4
3DC
7 VO4 SL8
8
4AC 1 2 3 4
Analog Outputs
4DC
9 VO5 SL8
Schneider Electric

# Change:
10 RET SL8

Revision:
5AC SXW AO-8-H
5DC SL8
11 VO6 SL8
Analog Outputs

1
2
3
4
5
12 5 6 7 8
6AC
6DC

CO5

CO6

CO7

CO8
RET

RET

RET

RET
VO5

VO6

VO7

VO8
S2
S2
13 14 15 16 17 18 19 20 21 22 23 24
13 VO7 SL8
14
7AC TB-08 10 15 TB-08

5/26/2022
5/26/2022
5/26/2022
7DC TB-08 9
15 VO8 SL8 13 TB-08
16 TB-08 11
8AC
8DC

Date:
Date:
Date:
Designed by:
Software by:
Checked by:
Contractor:
Engineer:
Architect:
National And Strategic Accounts

SHELL Panel IO Detail - 8


605 SHELL Panel.vsd 5/27/2022

5/27/2022
Last Printed
Last Saved
Job Number

Sheet Number
File Name

605-8
Panel Continued on Next Page

Label wiring, cabling, and conduit with point name at each end within 5 cm (2 in.)
1
of termination.
Low Voltage

Electric. Their use or reproduction without prior consent of


SHELL Panel Layout - Main

These drawings and designs are the property of Schneider


Conduit Entry Area

the company is strictly forbidden.


6" 1'-1/4" 6"

44.00 x 1.00

37.05 x 1.00
12.25 x 2.00

DUCT2

DUCT1
DUCT1
7 5/8"

TB-06
11.50 x 1.25

Date:
Preliminary
SL1 SL2 SL3

12.25 x 1.75

DUCT2
TB-03

7 5/8"

# Change:
Revision:
11.50 x 1.25

TB-07

1
2
3
4
5
SL4 SL5 SL6

12.25 x 1.75

DUCT2

5/26/2022
5/26/2022
5/26/2022
47.2in.
TB-04

TB-08

Date:
Date:
Date:
11.50 x 1.25
7 5/8"

SL7 SL8

Designed by:
Software by:
Checked by:
Contractor:
Engineer:
Architect:
12.25 x 1.75

DUCT2

National And Strategic Accounts

SHELL Panel Layout - Main


11.50 x 1.25
F-0
TB-05

DUCT2

6 7/8"
37.05 x 1.50

20.76 x 1.00
Part Number Qty Description Manufacturer
----------------------------------------------------------------------------------------------------------------------------------------------------
DUCT1 AI-PW62 1 TAHUYA Power Adapter AI Link
5.95 x 1.00
DUCT1

AI-SR620 1 TAHUYA Adapter AI Link


GMD-500-R 1 500 mA Fuse Eaton
TB-PA
KEL-T1-1030G 1 1IN X 3IN GRAY DUCT W/COVER Iboco
DUCT2

M9F42104 5 4 Amp CB Schneider Electric

605 SHELL Panel.vsd 5/27/2022

5/27/2022
NSYAEDL405S3D 1 LOCK AND KEY SET Schneider Electric

Last Printed
Last Saved
5.95in. NSYTRAABV35 2 END BRACKET SCREW TYPE Square D
NSYTRAC22 1 END COVER Square D
NSYTRV42 1 6MM TERMINAL BLOCK GRAY Square D
NSYTRV42SF5 1 TERMINAL BLOCK GREY Square D
44.00 x 1.50

SEBOX483212P 1 48x32x12 enclosure with perfor Schneider Electric

Job Number
SXWAO8HXX10001 1 AO-8-H 8 ANALOG OUT V/MA HAND Schneider Electric
29.30 x 1.00
SXWASPXXX10001 1 SMARTX CONTROLLER AS-P Schneider Electric
SXWPS24VX10001 1 PS-24V POWER SUPPLY 24 VAC/VDC Schneider Electric
DUCT1

Sheet Number
SXWSCABLE10003 2 S-CABLE 0.75M ANGLE Schneider Electric

File Name
SXWTBASW110002 1 TB-ASP-W1 TERM BASE ASP W1 Schneider Electric

605-9
SXWTBIOW110001 6 TB-IO-W1 TERM BASE I/O W1 Schneider Electric
SXWTBPSW110001 1 TB-PS-W1 Term Base Pwr Sup W1 Schneider Electric
31.5in. SXWUI16XX10001 5 UI-16 16 UNIVERSAL IN Schneider Electric
PNL-5

31.5in.
PANEL LABEL

47.2in.
SHELL Panel Layout - Door

Job Number
National And Strategic Accounts Architect:
Revision: Preliminary
Engineer:
# Change: Date:
File Name Last Saved Contractor:
1
605 SHELL Panel.vsd 5/27/2022 Designed by: Date: 5/26/2022 2
3 These drawings and designs are the property of Schneider
Sheet Number Last Printed Software by: Date: 5/26/2022 Electric. Their use or reproduction without prior consent of
4
the company is strictly forbidden.
SHELL Panel Layout - Door Checked by: Date: 5/26/2022 5
605-10 5/27/2022
Electric. Their use or reproduction without prior consent of
ADMIN/AHU Panel Power Detail

These drawings and designs are the property of Schneider

the company is strictly forbidden.


TB#:## UI# QS01.PA
TB-PB 5
PR2-1
9 TB#:## RET SL# External Power Panel
G G
Panel 14 PR2 13
CB2N N Receptacle
CB2 L
TB-PB PRI SEC
Primary 120VAC Circuit L CB1 CB3
BLK
Panel:_______________ N CB1N CB4
Wire to TB-PA
CKT#:_______________ G G CB5 X1H
BLU Of
CB6 X2N
WHT BRN PNL##
CB7 XFR1

Date:
CB3N
PRI SEC
PR1 CB4N

A1

A2
BLK

Preliminary
CB5N
Wire to TB-PA
CB6N X3H
BLU Of
18 15 L CB7N X4N
WHT BRN PNL##
16 G XFR2
G PRI SEC
28 25 N G BLK
26 G Wire to TB-PA
X5H
G BLU Of
X6N
WHT BRN PNL##
XFR3
PRI SEC
BLK
Wire to TB-PA
X7H

# Change:
Secondary 120VAC Circuit L CB0 BLU Of

Revision:
X8N
Panel:_______________ N CB0N 13 PR3 14 WHT BRN PNL##
XFR4
G G
CKT#:_______________ QS02.PA UI# TB#:## 5 9
SL# RET TB#:## PR3-1

1
2
3
4
5
Wire to TB-PA
~ + Y1+
Of
~ - Y2-
PNL##
PS1

5/26/2022
5/26/2022
5/26/2022
Date:
Date:
Date:
Designed by:
Software by:
Checked by:
Contractor:
Engineer:
Architect:
National And Strategic Accounts

ADMIN/AHU Panel Power


ADMIN AHU
XFMR-1 100 VA XFMR-2 100 VA XFMR-3 100 VA XFMR-4 100 VA PS1 90 W XFMR-1 100 VA XFMR-2 100 VA XFMR-3 100 VA XFMR-4 100 VA PS1 90 W

Detail
AS-P 10.00 VA 1 0 0 0 0 AS-P 10.00 VA 1 0 0 0 0
UI-16 1.80 VA 1 0 0 0 0 UI-16 1.80 VA 2 0 0 0 0
UI-8/DO-FC-4 1.90 VA 1 0 0 0 0 UI-8/AO-4 3.20 VA 1 0 0 0 0 UL Panel Details
Digital Output Contacts 0.75 VA 0 1 0 0 0 AO-8 4.90 VA 1 0 0 0 0
Tahuya Adapter 0.02 W 0 0 0 0 1 DO-FC-8 2.20 VA 1 0 0 0 0 Panel:_____________________
A/TTM1K-R2-4 RmTemp 0.75 W 0 0 0 0 4 Digital Output Contacts 0.75 VA 0 0 0 7 0 CKT#:_____________________
CWE CO2 0.75 W 0 0 0 0 3 Tahuya Adapter 0.02 VA 0 0 0 0 1
SD-R01 Leak 2.40 VA 0 0 0 1 0
MAX VOLTAGE: 120vac 60 Hz
FT-3200 Flow 12.00 VA 0 2 0 0 0
SSCR = 10kA

5/27/2022

5/27/2022
Last Printed
AFB24-SR Rlf Damper 5.50 VA 0 3 0 0 0

Last Saved
HD Strobe & Horn 9.36 VA 0 1 0 0 0
TBD Face Damper 5.50 VA 0 0 3 0 0
TOTAL FLA : 9.40A
KEL-GDD-HS HD Detector 8.40 VA 0 1 0 0 0 CB0 (main) = 10.00A
Load (W) 13.70 42.51 0.00 0.00 5.27 TBD Bypass Damper 5.50 VA 0 0 2 0 0
AMB24-SR RA Damper 2.50 VA 0 0 3 0 0
CB1 (main) = 10.00A
Leftover (W) 86.30 57.49 100.00 100.00 84.74 CB2 (receptacle) = 5.00A

Job Number

606 ADMIN-AHU Power Panel.vsd


%used (<80%) 13.70% 42.51% 0.00% 0.00% 5.85% NMB24-SR OA Damper 2.50 VA 0 0 9 0 0
Mixed Air Duct Temp Sensor 2.30 W 0 0 0 0 1
CB3 (XFR1) = 1.00A
CB4 (XFR2) = 1.00A

Sheet Number
Supply Air Duct Rh Sensor 2.30 W

File Name
0 0 0 0 2

606-1
CB5 (XFR3) = 1.00A
Load (W) 23.90 16.50 57.50 7.65 6.92
Leftover (W) 76.10 83.50 42.50 92.35 83.09
CB6 (XFR4) = 1.00A
%used (<80%) 23.90% 16.50% 57.50% 7.65% 7.68%
CB7 (PS1) = 2.00A
Low Voltage Line Voltage

Electric. Their use or reproduction without prior consent of


ADMIN/AHU Power Panel Layout

These drawings and designs are the property of Schneider


Conduit Entry Area Conduit Entry Area

the company is strictly forbidden.


Date:
Preliminary
17.45 x 1.00

DUCT1
PANEL LABEL

15.32 x 1.00

15.32 x 1.00
100VA 100VA 100VA 100VA
7.3in.

DUCT1
XFR4 XFR3 XFR2 XFR1

# Change:
PR2 PR3

Revision:
PR1

DUCT1

1
2
3
4
5
15.45 x 1.00
19.70in.
DUCT1

TB-PB

90W
CB0

5/26/2022
5/26/2022
5/26/2022
7.0in.

PS1

Date:
Date:
Date:
17.45 x 1.00

DUCT1

EPWR1

Designed by:
Software by:
Checked by:
19.70in.

Contractor:
Engineer:
Architect:
National And Strategic Accounts

ADMIN/AHU Power Panel


Layout
5/27/2022

5/27/2022
Last Printed
Last Saved
Part Number Qty Description Manufacturer
----------------------------------------------------------------------------------------------------------------------------------------------------
KEL-RET4-LOCK 1 LOCK AND KEY SET Schneider Electric

Job Number
KEL-T1-1030G 5 1INX3INX6.5FT GRAY DUCT W/COVE Iboco

606 ADMIN-AHU Power Panel.vsd


M9F43101 4 1A 120V Din Rail Breaker D Cur Schneider Electric
M9F43102 1 2A 120V Din Rail Breaker D Cur Schneider Electric

Sheet Number
M9F43105 1 5A 120V Din Rail Breaker D Cur Schneider Electric

File Name
M9F43110 2 10A 120V Din Rail Breaker D Cu Schneider Electric

606-2
PS24-S90W 1 POWER SUPPLY 24VDC 90W Veris Industries
SEBOX202010P 1 ENCL 20X20X10 NEMA 4 W/ PERF Schneider Electric
X100CAB 4 TRANSFRMR CTRL 120V/24V 99 VA Veris Industries
Electric. Their use or reproduction without prior consent of
COLO Panel Power Detail

These drawings and designs are the property of Schneider

the company is strictly forbidden.


TB5:13 UI1 PriPwrSts
TB-PB 5
PR2-1
9 TB5:14 RET MOD:05 External Power Panel
G G
Panel 14 PR2 13
CB2N N Receptacle
CB2 L
TB-PB PRI SEC
Primary 120VAC Circuit L CB1 CB#
BLK
Panel:_______________ N CB1N CB#
Wire to TB-PA
CKT#:_______________ G G CB# X1H
BLU Of
CB# X2N
WHT BRN PNL##
CB# XFR1
CB#N
PRI SEC

Date:
PR1 CB#N

A1

A2
BLK
CB#N
Wire to TB-PA

Preliminary
CB#N X3H
BLU Of
18 15 L CB#N X4N
WHT BRN PNL##
16 G XFR2
G PRI SEC
28 25 N G BLK
26 G Wire to TB-PA
X5H
G BLU Of
X6N
WHT BRN PNL##
XFR3
Wire to TB-PA
~ + Y1+
Of
~ - Y2-
PNL##
Secondary 120VAC Circuit PS1
L CB0

# Change:
Panel:_______________ N CB0N 13 PR3 14

Revision:
G G
CKT#:_______________ SecPwrSts UI2 TB5:15 5 9
PR3-1 Wire to CB13
MOD:05 RET TB5:16
Of

1
2
3
4
5
OA Pressure Power Panel

OA Pressure Power Panel

5/26/2022
5/26/2022
5/26/2022
4A Fuse

Date:
Date:
Date:
Primary 120VAC Circuit L CB13 ~ + F-0 Y3+
Wire to PT06-OA
Panel:_______________ N CB13N ~ - Y4-
G G PS2
CKT#:_______________

Designed by:
Software by:
Checked by:
Contractor:
Engineer:
Architect:
National And Strategic Accounts

COLO Panel Power Detail


COLO2 CE1 (Worst Case Power Usage)
XFMR-1 100 VA XFMR-2 100 VA XFMR-3 100 VA PS1 90 W PS2 90 W
AS-P 10.00 VA 1 0 0 0 0
UI-16 1.80 VA 5 0 0 0 0
AO-8 4.90 VA 1 0 0 0 0 UL Panel Details
Tahuya Adapter 0.02 VA 0 0 0 1 0
PX3PXN01 DP 0.75 W 0 0 0 16 0 Panel:_____________________
RY2KS Latch Relay 1.60 VA 0 0 2 0 0 CKT#:_____________________
A/TTM1K-R2-4 RmTemp 0.75 W 0 0 0 10 0 MAX VOLTAGE: 120vac 60 Hz
A/RH2-TTM1K-R2-4 RmT/Rh 1.50 W 0 0 0 12 0 SSCR = 10kA

5/27/2022

5/27/2022
Last Printed
Last Saved
FT-3200 Flow 12.00 VA 0 0 1 0 0 TOTAL FLA : 9.40A
HMS110 OA T/Rh 1.50 W 0 0 0 1 0 CB0 (main) = 10.00A
AFB24-SR Rlf Damper 5.50 VA 0 12 0 0 0 CB1 (main) = 10.00A
CB2 (receptacle) = 5.00A

Job Number
SPH20 OA Pressure 70.00 W 0 0 0 0 1

607 COLO Power Panel.vsd


Load (W) 23.90 66.00 15.20 39.02 70.00 CB3 (XFR1) = 1.00A
CB4 (XFR2) = 1.00A

Sheet Number
Leftover (W) 76.10 34.00 84.80 50.99 20.00

File Name

607-1
%used (<80%) 23.90% 66.00% 15.20% 43.35% 77.78% CB5 (XFR3) = 1.00A
CB6 (PS1) = 2.00A
CB7 (PS2) = 2.00A
Low Voltage Line Voltage

Electric. Their use or reproduction without prior consent of


COLO Power Panel Layout

These drawings and designs are the property of Schneider


Conduit Entry Area Conduit Entry Area

the company is strictly forbidden.


Date:
Preliminary
17.45 x 1.00

DUCT1

15.32 x 1.00

15.32 x 1.00
PANEL LABEL

100VA 100VA 100VA PR2 PR3


7.3in.

DUCT1
XFR3 XFR2 XFR1

# Change:
PR2 PR3

Revision:
PR1

DUCT1

1
2
3
4
5
15.45 x 1.00
19.70in.
DUCT1

TB-PB

90W

5/26/2022
5/26/2022
5/26/2022
CB0
7.0in.

PS1

Date:
Date:
Date:
17.45 x 1.00

DUCT1

EPWR1

Designed by:
Software by:
Checked by:
Contractor:
19.70in.

Engineer:
Architect:
National And Strategic Accounts

COLO Power Panel Layout


5/27/2022

5/27/2022
Part Number Qty Description Manufacturer

Last Printed
Last Saved
----------------------------------------------------------------------------------------------------------------------------------------------------
FKIT-VMD1B-F120A 2 RELAY & SOCKET KIT SPDT W/F SO Veris Industries
KEL-RET4-LOCK 1 LOCK AND KEY SET Schneider Electric
KEL-T1-1030G 5 1INX3INX6.5FT GRAY DUCT W/COVE Iboco
M9F43101 3 1A 120V Din Rail Breaker D Cur Schneider Electric

Job Number
M9F43102 2 2A 120V Din Rail Breaker D Cur Schneider Electric

607 COLO Power Panel.vsd


M9F43105 1 5A 120V Din Rail Breaker D Cur Schneider Electric
M9F43110 2 10A 120V Din Rail Breaker D Cu Schneider Electric

Sheet Number
PS24-S90W 1 POWER SUPPLY 24VDC 90W Veris Industries

File Name
SEBOX202010 1 ENCL 20X20X10 NEMA 4 Schneider Electric

607-2
SEBOX202010P 1 ENCL 20X20X10 NEMA 4 W/ PERF Schneider Electric
VTD2P-UNI 1 TIME DELAY RELAY DPDT 15A DIN Veris Industries
X100CAB 3 TRANSFRMR CTRL 120V/24V 99 VA Veris Industries
Electric. Their use or reproduction without prior consent of
COLO Remote Power Panel Layout

These drawings and designs are the property of Schneider

the company is strictly forbidden.


Date:
Preliminary
15.62 x 1.00

DUCT1
PANEL LABEL

# Change:
90W

Revision:
DUCT1

DUCT1
CB13

F-0
11.80in.

1
2
3
4
5
PS2

8.40 x 1.00

8.40 x 1.00
15.62 x 1.00

DUCT1

5/26/2022
5/26/2022
5/26/2022
SEBOX121806P

17.70in.

Date:
Date:
Date:
Designed by:
Software by:
Checked by:
Contractor:
Engineer:
Architect:
National And Strategic Accounts

COLO Remote Power Panel


Layout
5/27/2022

5/27/2022
Last Printed
Last Saved
Part Number Qty Description Manufacturer

Job Number
----------------------------------------------------------------------------------------------------------------------------------------------------

607 COLO Power Panel.vsd


GMD-4-R 1 4 A Fuse Eaton
KEL-RET4-LOCK 1 LOCK AND KEY SET Schneider Electric

Sheet Number
KEL-T1-1030G 4 1INX3INX6.5FT GRAY DUCT W/COVE Iboco

File Name

607-3
M9F43102 1 2A 120V Din Rail Breaker D Cur Schneider Electric
NSYTRV42SF5 1 TERMINAL BLOCK GREY Square D
PS24-S90W 1 POWER SUPPLY 24VDC 90W Veris Industries
SEBOX121806P 1 ENCL 12X18X6 NEMA 4 W/ PERF Schneider Electric
Notes

Electric. Their use or reproduction without prior consent of


DP Panel Layout

These drawings and designs are the property of Schneider


Label poly tubing at each end with 5 cm (2 inch) of termination with point and
1

the company is strictly forbidden.


high/low description.

2 Refer to floor plans for high and low pick up locations

3 No splicing of poly tubing

PANEL LABEL 21.66 x 1.75

1.5" x 3"

Date:
0.25” Clearance

Preliminary
1" Clearance

1" Clearance

1" Clearance

1" Clearance

1" Clearance
COLO#-CE#- COLO#-CE#- COLO#-CE#- COLO#-CE#-
PT01 PT02 PT03 PT04

1 2 3
2” Clearance

# Change:
Revision:
HI LO HI LO HI LO HI LO
19.25 x 1.75

1.5" x 3"

1
2
3
4
5
0.25” Clearance

1" Clearance

1" Clearance

1" Clearance

1" Clearance

1" Clearance
COLO#-CE#- COLO#-CE#- COLO#-CE#- COLO#-CE#-
PT05 PT06 PT07 PT08

5/26/2022
5/26/2022
5/26/2022
Date:
Date:
Date:
2” Clearance
HI LO HI LO HI LO HI LO
19.20 x 1.75

31.50in. 30.10in.
1.5" x 3"
1" Clearance

Designed by:
Software by:
Checked by:
PHX11.COLO#-CE#-PDS01

Contractor:
Engineer:
Architect:
1" Clearance
9.21 x 1.25

PB1

National And Strategic Accounts


From CC Panel Circuit Power

From CC Panel Relief Damper A Power

From CC Panel Relief Damper B Power

Power To Relief Dampers A

Power To Relief Dampers B

Status To CC Panel

1" x 3"
1" x 3"
PDS1
R1 LR1

DP Panel Layout
26.56 x 1.25

26.56 x 1.25
1.5" Clearance
LO
HI

21.67 x 1.75

1.5" x 3"

21.65in.

24.62in.

608 DP Panel.vsd 5/27/2022

5/27/2022
Last Printed
Last Saved
DP Panel
Part Number Qty Description Manufacturer
----------------------------------------------------------------------------------------------------------------------------------------------------

Job Number
KEL-T1-1530W 1 1.5INX3INX6.5FT WHITE DUCT W/C Iboco
KEL-X-B-376 32 1/4X1/4 X1/4 BARB TEE Parker
KEL-X-M-107 32 1/4 RUBBER CAP Kele

Sheet Number
MR1SA 8 Air Differential Pressure Tran Setra

File Name

608-1
NSYCRN86200T 1 Enclosure w/ Glazed window H80 Square D
PAS01 1 PRESS DRY SWITCH .08-1.2"WC Veris Industries
PX3PLN01 8 PRESSURE-VEL DRY PANEL LCD 1IN Veris
SQD-NSYMF86 1 BACKPANEL, 30X22, PERF, GRAY Square D
1
Refer to associated control panel wiring for # designation
From CC Panel Relief Damper B Power
From CC Panel Relief Damper A Power
From CC Panel Circuit Power

Power To Relief Dampers B


Power To Relief Dampers A

Status To CC Panel
UI#
X#N
X#H
X#N
X#H

RET
X4N
X3H

PD02
PD02
PD01
PD01

1
1
1

5
1
6
2
8
4

14
R1
Mounted in Panel

13
9
10
12
DP Panel Wiring

1
13
Set
LR1

LR1-1
10
14
9
LR1
Reset
12

Plenum
To Return
PB1

HSL2
Set @ 0.3"
NO COM
NO COM

L
Air Ref
To Outside

Job Number
National And Strategic Accounts Architect:
Revision: Preliminary
Engineer:
# Change: Date:
File Name Last Saved Contractor:
1
608 DP Panel.vsd 5/27/2022 Designed by: Date: 5/26/2022 2
3 These drawings and designs are the property of Schneider
Sheet Number Last Printed Software by: Date: 5/26/2022 Electric. Their use or reproduction without prior consent of
4
the company is strictly forbidden.
DP Panel Wiring Checked by: Date: 5/26/2022 5
608-2 5/27/2022
Notes

Electric. Their use or reproduction without prior consent of


DP Manifold Panel Layout

These drawings and designs are the property of Schneider


1 Install insect screen over vents on both sides of enclosure.

the company is strictly forbidden.


2 Fasten copper pipe manifold to backplane using pipe straps.

3 Cap or plug end of reference header.

4 Install 1/2" Conduit to connect DP Manifold Panel to sensor support arm.

Install aluminum sensor support arm extending minimum of 40" (1 meter) from
5 exterior wall. Run tubing through conduit to connect to Outside Air Static
Pressure Pickup Port.

Date:
Preliminary
PANEL LABEL

# Change:
3

Revision:
2

1
2
3
4
5
5
12.00in.
9in. 40in.

1 1

5/26/2022
5/26/2022
5/26/2022
9in.

Date:
Date:
Date:
12.00in.

Designed by:
Software by:
Checked by:
Contractor:
Engineer:
Architect:
National And Strategic Accounts

DP Manifold Panel Layout


5/27/2022

5/27/2022
Last Printed
Last Saved
Job Number

609 DP Manifold Panel.vsd

Sheet Number
DP Manifold Panel

File Name

609-1
Part Number Qty Description Manufacturer
----------------------------------------------------------------------------------------------------------------------------------------------------
SCE-12DLP12 1 SUBPANEL, FLAT 9 X 9 Saginaw
SCE-12EL1206LP 1 12 X 12 X 6 Enclosure Saginaw
Electric. Their use or reproduction without prior consent of
Battery Room CO Panel Layout

These drawings and designs are the property of Schneider

the company is strictly forbidden.


Date:
Preliminary
PANEL LABEL

# Change:
Revision:
EF OFF EF ON - + 1 2 3 4 5
6.00 x 1.25

8.00in. 7in.
24VAC

1
2
3
4
5
- + 1 2 3 4 5

5/26/2022
5/26/2022
5/26/2022
7in.

8.00in.

Date:
Date:
Date:
Designed by:
Software by:
Checked by:
Contractor:
Engineer:
Architect:
1 Battery Room CO Sensor and Exhaust Fan Wiring

National And Strategic Accounts

Battery Room CO Panel


Layout
5/27/2022

5/27/2022
Last Printed
Last Saved
Part Number Qty Description Manufacturer
----------------------------------------------------------------------------------------------------------------------------------------------------
3FAL1 1 DIN: AL, PERFORATED Iboco

Job Number
9001SKS11BH1 1 SELECTOR SWITCH 600VAC 10A 30M Schneider Electric

610 Battery Room CO Panel.vsd


B080804CH 1 8 X 8 X 4 Enclosure, NEMA 12 Wiegmann
KEL-KIT-782XBXM4L-24A 1 RELAY, 2PDT, 24VAC, LED, OVR W Schneider Electric

Sheet Number
NSYTRAABV35 3 END BRACKET SCREW TYPE Square D

File Name

610-1
NSYTRAC22 8 END COVER Square D
NSYTRV42 7 6MM TERMINAL BLOCK GRAY Square D
NSYTRV42PE 1 6MM TERMINAL BLOCK GROUNDING Square D
P0808 1 SUBPANEL, FLAT 7 X 7 Wiegmann