Dometic-Tve 9108548595 62741
Dometic-Tve 9108548595 62741
Dometic-Tve 9108548595 62741
Dometic
Rev. 20171017
L-2805 English
P/N: 336021
No part of this publication may be reproduced, translated, stored in a retrieval system, or transmitted in any form or by any means
electronic, mechanical, photocopying, recording or otherwise without prior written consent by Dometic Corporation. Every precaution
has been taken in the preparation of this manual to ensure its accuracy. However, Dometic Corporation assumes no responsibility for
errors and omission. Neither is any liability assumed for damages resulting from the use of this product and information contained
herein.
Table of Contents
INTRODUCTION
The Emerald Split System is a direct-expansion water-cooled air conditioning system designed for marine use. Its two primary
components consist of a condensing unit and an evaporator unit.
A complete system also requires installation of control(s), ducting, and a seawater water pump cooling system (not included).
SAFETY INSTRUCTIONS
RECOGNIZE SAFETY SYMBOLS, WORDS AND LABELS
The following symbols and labels are used throughout this manual to indicate immediate or potential safety hazards. it is the
owner’s and installer’s responsibility to read and comply with all safety information and instructions accompanying these
symbols. Failure to heed safety information increases the risk of personal injury, property damage, and/or product damage.
DANGER
Indicates a hazardous situation which, if not avoided, will result in death or serious injury.
WARNING
Indicates a hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION
Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
NOTICE
Indicates a situation which can cause damage to the engine, personal property and/or the environment, or cause the
equipment to operate improperly.
L-2805 ENGLISH 1
Safety Considerations Emerald Split System Installation, Operation & Maintenance Manual
SAFETY CONSIDERATIONS
WARNING
CARBON MONOXIDE HAZARD. Never install your air conditioner in the bilge or engine room areas. Ensure that the
selected location is sealed from direct access to bilge and/or engine room vapors. Do not terminate condensate drain
line within 3' (0.91 m) of any outlet of engine or generator exhaust systems, nor in a compartment housing an engine
or generator, nor in a bilge, unless the drain is connected properly to a sealed condensate or shower sump pump. If
drain line is not properly installed, then dangerous fumes may travel up drain line and contaminate living quarters.
Failure to follow this precaution could result in death or serious injury.
WARNING
CARBON MONOXIDE HAZARD. Never install the A/C unit in a location where it can circulate carbon monoxide, fuel
vapors or other noxious fumes into the boat's living spaces. Do not install or operate a self-contained unit in the
engine room or near an internal combustion engine. Failure to follow this precaution could result in death or serious
injury.
WARNING
EXPLOSION HAZARD. Never install the A/C unit in a location containing gasoline engines, tanks, LPG/CPG cylinders,
regulators, valves or fuel line fittings. Unless labeled otherwise, self-contained units do not meet federal requirements
for ignition protection. Failure to follow this precaution could result in death or serious injury.
WARNING
ELECTRICAL SHOCK HAZARD. Be sure to effectively ground the A/C unit. The A/C unit must be effectively grounded
to minimize electrical shock hazard. Refer to the installation guidelines for further information. Failure to follow this
precaution could result in death or serious injury.
WARNING
ELECTRICAL SHOCK HAZARD. To avoid personal injury, shock, or death, ensure the electrical disconnect switch(es)
is (are) in the OFF position before installing, modifying, or servicing the unit. Lock out and tag the switch with a
suitable warning label. Wiring must conform with NEC or CEC and all local codes.
WARNING
USE CERTIFIED INSTALLATION TECHNICIAN. Allow only qualified, experienced technicians to install or service this
system.
Safety Guidelines
1. Allow only qualified, experienced technicians to install or service this system.
2. Install the system in accordance with all local codes. If no local codes exist, follow National Codes (NEC in the U.S.,
CEC in Canada).
3. Open the electrical disconnect switch(es) before electrically connecting the unit.
4. Before operating the unit, be certain it is properly grounded.
5. The units contain refrigerant gas under pressure. Avoid puncturing or breaking any tubing.
6. Before operating the system, complete the refrigerant connections.
WARNING
To avoid possible explosion, death, or injury, practice safe handling of refrigerants.
WARNING
Refrigerants are heavier than air. They can “push out” the oxygen in your lungs or in any enclosed space. To avoid
possible death or difficulty breathing:
• Never sniff a refrigerant.
• Never purge refrigerant into an enclosed room or space. All refrigerants must, BY LAW, be reclaimed.
• If an indoor leak is suspected, thoroughly ventilate the area before beginning work.
• Liquid refrigerant can be very cold. To avoid possible frostbite or blindness, avoid contact and wear gloves and
goggles. If liquid refrigerant does contact your skin or eyes, get medical help immediately.
• Never burn refrigerant, as poisonous gas will be produced.
• Always follow EPA regulations.
(continued on next page)
2 L-2805 ENGLISH
Emerald Split System Installation, Operation & Maintenance Manual R-410A Quick Reference Guide
WARNING
To avoid possible explosion:
• Never apply flame or steam to a refrigerant cylinder. If you must heat a cylinder for faster charging, partially immerse it
in warm water.
• Never fill a cylinder more than 80% full of liquid refrigerant.
• Never add anything other than R-410A to an R-410A cylinder. R-410A operates at a 50 to 70% higher pressure than
R-22 systems. Service equipment used must be listed or certified for R-410A.
• Store cylinders in a cool, dry place. Never use a cylinder as a platform or a roller.
WARNING
To avoid possible explosion, use only returnable (not disposable) service cylinders when removing refrigerant from a
system.
• Ensure the cylinder is free of damage which could lead to a leak or explosion.
• Ensure the hydrostatic test date does not exceed 5 years.
• Ensure the pressure rating meets or exceeds 400 pounds.
• When in doubt, do not use the cylinder.
SYSTEM INSTALLATION
UNPACKING AND INSPECTION
Units are securely packed in shipping containers approved by the International Safe Transit Association.
Upon arrival, carefully check all items against the packing list to ensure all cartons were received. Move units to the normal “up”
orientation as indicated by the arrows on each carton.
L-2805 ENGLISH 3
How It Works Emerald Split System Installation, Operation & Maintenance Manual
Check the cartons for external damage, removing the units from the cartons if necessary. If damage is found, file a request in
writing for inspection by the carrier agent immediately. The carrier is responsible for making prompt inspection of damage and
for a thorough investigation of each claim. The distributor or manufacturer will not accept claims from dealers for transportation
damage. If no damage is found, carefully remove all shipping material and properly dispose of it.
After unpacking, keep the units as upright as possible. Laying a unit on its side or top could cause equipment damage.
NOTICE
When unpacking and installing the manual control, care must be taken not to kink or break the copper cap tube when
uncoiling the sensing bulb. The cap tube is hollow and kinking or sharp bends will inhibit system operation.
HOW IT WORKS
BASIC PRINCIPLES
The basic principle behind an air conditioner is the transfer of heat from one place to another. In a marine air conditioner, heat is
removed from the inside cabin air and transferred to the seawater. In reverse-cycle heating, the refrigerant flow is reversed and
heat is extracted from the seawater and discharged into the living space. The efficiency of the system operation depends on
both seawater and cabin temperatures.
This split-system air conditioner consists of four main components divided into two units and a refrigerant gas circulating
through the system. The direct expansion (DX) air handler consists of a blower (fan) and an evaporator coil. The condensing
unit consists of a compressor and a condenser coil. A copper line set connects the DX air handler(s) and the condensing unit to
each other.
The DX air handler blower draws warm humid cabin air across the fins on the evaporator where the heat from the air is
transferred to the refrigerant in the evaporator coil. (The moisture in the air is captured on the evaporator coil by forming
condensation as the air is cooled.) As the refrigerant evaporates from a liquid into a gas, it absorbs the heat from the cabin air.
The compressor then compresses the refrigerant gas and pumps it through the outer tube in the condenser coil. The seawater
pump circulates cool seawater through the inner tube in the condenser coil; this cools the refrigerant and condenses it into a
liquid. The heat from the refrigerant is exchanged to the seawater and discharged overboard. The liquid refrigerant is then
passed through the evaporator coil and the cycle repeats. Removing heat and moisture from the cabin air lowers its temperature
and humidity levels. The conditioned air is blown through the ducting and out the supply-air grille(s).
For reverse-cycle heating, the refrigerant flows in the opposite direction through the reversing valve. Heat is transferred from the
seawater in the condenser coil to the refrigerant and then to the air blowing through the evaporator into the cabin.
WARNING
Do not operate your air conditioning unit in water that is colder than 38°F (3.3°C). Doing so could lead to water freezing
in the condenser coil which can cause damage to the unit.
SAFETY CONSIDERATIONS
AVOID HARMFUL VAPORS
Consideration should be given to installing a trap in the condensate drain line(s) so that normal discharge of condensate can fill
the trap and prevent the ingress of carbon monoxide (CO) or other potentially harmful vapors.
4 L-2805 ENGLISH
Emerald Split System Installation, Operation & Maintenance Manual Tools Required
WARNING
Never install your DX air handler in the bilge or engine room areas. Ensure that the selected location is sealed from
direct access to bilge and/or engine room vapors.
Do not terminate condensate drain line within three feet of any outlet of engine or generator exhaust systems, nor in a
compartment housing an engine or generator, nor in a bilge, unless the drain is connected properly to a sealed
condensate or shower sump pump.
Failure to comply may allow bilge or engine room vapors to mix with the air conditioner’s return air and contaminate
living areas which may result in injury or death.
OTHER HAZARDS
•
WARNING
Installation and servicing of this system can be hazardous due to system pressure and electrical components.
• When working on this equipment, always observe precautions described in the literature, tags and labels attached to
the unit.
• Follow all safety codes.
• Wear safety glasses and work gloves and place a fire extinguisher close to the work area.
NOTICE
United States federal law prohibits the intentional release of refrigerant gases into the environment, including the R-
410A refrigerant used in this air conditioning system. Special care must be taken when installing, charging and
servicing Dometic equipment to prevent any loss of refrigerant.
Dometic does not recommend the practice of using refrigerant to purge air and moisture from the system at
installation. This formerly used practice of purging is in violation of United States federal law.
NOTICE
Contains fluorinated greenhouse gases in hermetically sealed equipment. Refer to the condensing unit’s product data
plate label for quantity of refrigerant shown in weight and GWP. Refrigerant added should be noted on unit label.
TOOLS REQUIRED
Before starting, make sure you have all of the following tools:
• Standard tool box
• Service wrench
• Flaring tool
• Refrigerant gauge manifold (rated for R-410A only)
• Refrigerant tank (rated for R-410A only)
• Nitrogen tank
• Vacuum pump
• Scale
• Micron gauge
• Electronic leak detector (rated for R-410A)
• Drill/hole saw
• Jig saw
• Insulated tape
• Duct tape
• Electrical tape
L-2805 ENGLISH 5
Placement of the System Emerald Split System Installation, Operation & Maintenance Manual
• Threaded-seal tape
• Bedding compound to seal thru-hull fittings
• Hardware to secure unit, pump, strainer, grilles, and control panel
6 L-2805 ENGLISH
Emerald Split System Installation, Operation & Maintenance Manual Clearances and Accessibility
SYSTEM SIZING
For proper performance, the equipment and ductwork must be adequate for moving about 400 CFM of indoor air for every ton of
cooling capacity to be installed. If they are not, change the ductwork or equipment accordingly.
L-2805 ENGLISH 7
Copper Line Sets Emerald Split System Installation, Operation & Maintenance Manual
With this in mind, it is to route condensate drains downward to a sump pump. Do not route DX air handler condensate drain
lines directly to the bilge (see warning below). Condensing unit drain lines may terminate in the bilge because the condensing
unit does not handle air.
1. The DX air handler condensate drain pan has two 1/2” FPT drain fittings. You can use both drains (preferred) or just
the drain in the aft-most-facing position.
Screw the supplied PVC hose barbs into the threaded drain fittings using threaded-seal tape for a watertight seal and
tighten them securely but do not overtighten. The two drains may be teed together, provided there is a minimum drop
of 2 inches (51 mm) from the drain pan to the tee fitting. Use 5/8” hose and stainless steel hose clamps on all drain
lines.
Install plug in drain fitting not used.
Route the DX air handler’s condensate drain hose to a sealed condensate or shower sump pump (see warning below).
Drain hose must be routed downward to allow water to flow via gravity downhill.
2. The condensing unit has two 1/2” FPT drain fittings in its condensate drain pan. You can use both drains (preferred)
or just the drain in the aft-most-facing position.
Screw the supplied PVC hose barbs into the threaded drain fittings using threaded-seal tape for a watertight seal and
tighten them securely but do not overtighten. The two drains may be teed together, provided there is a minimum drop
of 2 inches (51 mm) from the drain pan to the tee fitting. Use 5/8” hose and stainless steel hose clamps on all drain
lines.
Route the condensing unit’s condensate drain hose to a sealed condensate or shower sump pump or to the bilge.
Drain hose must be routed downward to allow water to flow via gravity downhill.
Install plug in drain fitting not used.
3. Test: After the condensate drain installations are complete, test each installation by pouring a quart (1 liter) of water
into the pan and checking for good flow. Occasionally pour a bleach and water solution into the pan to clean any algae
or sediment out of the lines.
WARNING
Do not terminate DX air handler condensate drain lines within 3 feet (1 meter) of any outlet of engine exhaust systems,
nor in a compartment housing an engine or generator, nor in a bilge, unless the drain is properly connected to a
sealed condensate or shower sump pump.
Exhaust and/or bilge fumes can travel up a drain line and mix with the return air blowing into living areas which could
cause illness or death.
Refrigerant tubing is normally soft drawn and nitrogen purged. All refrigerant lines should be capped to protect against moisture
and dust infiltration until the flare connections are made to the evaporator and condenser base valves.
Extreme care must be taken not to crush or kink any portion of either line set. Use proper tools for line bending, avoiding sharp
bends or kinks. Any kinked or crushed section must be replaced. There should be no vertical loops (oil traps) in the copper lines.
Any excess tubing should be coiled in a horizontal plane and secured to prevent vibration.
Keep tubing clear of bilge water, steering cables and similar obstructions. Secure tubing approximately every 12 inches (30 cm)
to prevent vibration and/or chafing. DO NOT CRUSH INSULATION.
When using multiple evaporators, ensure that the dual, triple or quad fittings are sized correctly to allow correctly sized tubing to
be connected to DX air handler fittings and provide proper refrigerant flow to and from each DX air handler.
8 L-2805 ENGLISH
Emerald Split System Installation, Operation & Maintenance Manual Copper Line Sets
L-2805 ENGLISH 9
Copper Line Sets Emerald Split System Installation, Operation & Maintenance Manual
The liquid line must be outside the suction line insulation. If part of the liquid line must run through an area that will be hotter
than 120°F (48.9°C), then that portion of the liquid line must be insulated.
• Seal the holes where the refrigerant piping enters the engine room.
• Be careful not to kink or dent the refrigerant lines. Kinked or dented lines will cause poor performance or compressor
damage.
Filter Dryer
The liquid line filter dryer is factory-installed. Any time the refrigeration system has been opened for service, you must replace
the filter dryer with an equivalent filter dryer rated for R-410A.
NOTICE
Do not leave system open to atmosphere any longer than necessary for installation. The compressor POE oil is
extremely susceptible to moisture absorption and could cause compressor failure.
Ensure ends of tubing are sealed before and during installation.
NOTICE
Packing gland leaks and resulting damage are not covered under warranty.
• Gauge hoses can be connected and disconnected without the presence of system pressure. The gauge port is isolated
from the system if the stem is backseated.
• The gauge ports have a standard core valve, which can be removed and replaced while the stem is backseated.
10 L-2805 ENGLISH
Emerald Split System Installation, Operation & Maintenance Manual Copper Line Sets
WARNING
To avoid the risk of fire or explosion, never use oxygen, high-pressure air or flammable gases for leak testing of a
refrigeration system.
Pressure Test
NOTE: It is sometimes assumed that any apparent leakage must originate in the equipment, but in reality leaks can also occur
in the gauge manifold and hoses. Before use, inspect the fittings on the manifold for tightness and replace any damaged hoses
or worn gaskets.
1. Before testing ensure both hand valves on the gauge manifold are closed relative to the center port (i.e., turned IN all
the way).
2. Connect the high- and low-side hoses of your R-410A gauge manifold to the condenser base valves. Check the stem
packing nuts for tightness. The nuts should be torqued (clockwise) to no more than 7.5 ft. lbs. Do not overtighten. Do
not open the unit service valves.
3. Connect a dry nitrogen cylinder to the center port on the gauge manifold and set the regulator to a maximum pressure
of 500 psig. : Compressed air or CO2 should not be used as they can add moisture and ether contaminates to the
system! Refrigerant should never be used unless needed for electronic leak detection.
WARNING
To avoid possible explosion, the line from the nitrogen cylinder must include a pressure regulator and a pressure
relief valve.
NOTICE
Never exceed 800 psi due to the possibility of rupturing hoses or line-set connections due to poor flares.
4. Open the hand valve a minimal amount on the line coming from the nitrogen cylinder.
5. Once the regulator on the nitrogen tank is set, open the high-pressure valve on the gauge manifold. Pressurize the
refrigerant lines and the evaporator(s) to 500 psig . To reach 500 psig, you may need to further open the hand valve on
the nitrogen cylinder.
WARNING
To avoid possible explosion or equipment damage, do not exceed 500 psig when pressure testing.
6. The needle(s) will rise as pressure enters the line set and evaporator(s). Once the point of the predetermined pressure
has been reached, close the gauge valve(s). Monitor the gauge reading(s) after the pressure has stabilized (should be
less than a minute). The pressure should be left in the system for a minimum of 15 minutes.
• If the gauge pressure drops, there is a leak in the system. Refer to “Leak Check” on page 11 to determine the
location of the leak(s).
• If the gauge pressure remains constant, close the valve on the nitrogen cylinder and disconnect it from the
gauge manifold. Proceed to “System Evacuation” on page 12.
Leak Check
Do not use a vacuum as a leak detection technique as moisture could be drawn into the system.
• A rapid drop in gauge pressure indicates a large leak or several small ones.
• A slow drop in gauge pressure indicates small leak(s).
Open both gauge valves and pressurize the system again to maintain a positive pressure on the lines and evaporator while
checking for leaks. Use the following techniques to locate leaks.
• Large leaks can often be detected by listening for a hissing sound or felt by placing your hand around the leaking
fitting. NOTE: If pipe insulation encases a leaking fitting, the escaping nitrogen can be forced down the insulation to a
remote location, giving a false indication of the leak location.
• Apply a soap solution on all connections and joints. Bubbles indicate leaks, so mark these locations. Clean off the soap
solution when leak checking is complete.
L-2805 ENGLISH 11
Copper Line Sets Emerald Split System Installation, Operation & Maintenance Manual
NOTICE
Care must be taken to ensure soap solution does not ingress into a leaking fitting(s) and contaminate the system.
• If the leaks cannot be located with the previous methods, an electronic leak detector should be used. For this
procedure, add a trace of R-410A refrigerant to the nitrogen in the system (if permitted by current EPA regulations).
NOTE: Ensure the electronic leak detector you use is capable of sensing HFC-type refrigerants.
Repeat the procedures above until all leaks are found and repaired. After repair, repeat the steps in “Pressure Test” on page 11.
SYSTEM EVACUATION
If you have confirmed that the system maintains pressure, the line set and evaporator(s) are now ready for evacuation of the
nitrogen (or nitrogen/refrigerant mixture if an electronic leak detector was needed) from the system.
WARNING
When using high-pressure nitrogen in the system, wear safety glasses and gloves.
Secure the hose end to prevent injury to personnel or damage to property. Do not point the hose toward personnel or
property.
To prevent inhalation, the nitrogen should NOT be expelled into a confined space where personnel are working; the
work area should be well ventilated.
If the nitrogen is mixed with refrigerant , contact with an open flame or hot surface could create PHOSGENE GAS,
which can cause respiratory problems or death.
WARNING
If skin or eyes come into contact with refrigerant, flush thoroughly with water. Skin contact with refrigerant can cause
frostbite. Wear gloves at all times.
12 L-2805 ENGLISH
Emerald Split System Installation, Operation & Maintenance Manual Copper Line Sets
5000
4500
4000
3500
3000
2500
2000
1500
1000
500
0 1 2 3 4 5 6 7
EVACUATE
WAIT
EVACUATE
WAIT
EVACUATE
CHARGE SYSTEM
L-2805 ENGLISH 13
Supply & Return Air Grilles Emerald Split System Installation, Operation & Maintenance Manual
Duct Diameter 4 5 5 6 6 7
(inches)
Supply-Air Grille 40 40 50 70 70 84
(square inches)
NOTE: To calculate the square-inch area of a round duct, multiply the radius (which is half of the diameter) by itself (r2) then
multiply that number by 3.1416 (pi).
DUCTING
Good airflow is critical for the performance of the entire system. It is highly dependent on the quality of the ducting installation.
The ducting should be run as straight, smooth and taut as possible, minimizing the number of 90-degree bends (2 tight 90-
degree bends can reduce airflow by 25%). Table 3 on page 14 shows minimum duct diameters and their corresponding supply-
and return-air grille minimum areas in square inches.
14 L-2805 ENGLISH
Emerald Split System Installation, Operation & Maintenance Manual Ducting
If a transition box is used, the total area of supply air ducts going out of the box should equal the area of the supply duct feeding
the box.
All ducting should:
• Be appropriately sized for each application.
• Run as smoothly and as taut as possible.
• Have as few bends or loops as possible.
• Be securely fastened to prevent sagging during boat operation.
• Have all excess ducting lengths trimmed off.
• Not be flattened or kinked.
• Insulated when located in high heat load areas (hull side, mechanical compartments, etc.)
• Be properly protected against potential damage when routed through open areas.
Installation procedure:
1. Run the ducting from the DX air handler’s blower to the supply-air grille or transition box.
2. At one end, pull back the fiberglass insulation to expose the inner mylar duct hose.
3. Slide the mylar duct hose around the mount ring until it bottoms out.
4. Screw 3 or 4 stainless steel sheet metal screws through the duct hose into the mount ring. Make sure to catch the wire
in the duct hose with the heads of the screws. Do not use band clamps, as the hose will slide off.
5. Wrap duct tape around the ducting and ring joint to prevent any air leaks.
6. Pull the insulation back up over the mylar to the ring and tape the joint.
7. Use the same connection method at the other end of the ducting run, making sure to remove any excess ducting.
L-2805 ENGLISH 15
Seawater Pump Emerald Split System Installation, Operation & Maintenance Manual
SEAWATER PUMP
Since the seawater pump is centrifugal and not self-priming, it must be mounted so it is always at least one foot (305mm) below
the water line regardless of which tack the vessel is on.
The pump may be mounted horizontally or vertically, however the discharge must always be above the inlet. The pump head
should be rotated toward the direction of water flow. See Figure 5 on page 15 for diagrams of correct and incorrect pump-head
orientations.
NOTE: In rare situations and under certain variable conditions of direction and speed, a boat moving very fast could trigger the
pump to shut down due to the extra water flow coming through the speed scoop. Normal pump function will resume when the
boat slows or stops. Or, if the condition was sustained, the pump might lock out and require a reset by turning the pump’s power
off then on again.
SEAWATER STRAINER
A seawater strainer is mandatory between the shut off valve (seacock) and the pump to protect the pump from any foreign
matter.
NOTICE
Failure to install a seawater strainer will void the pump warranty and possibly damage the system.
INSTALLATION PROCEDURE
NOTICE
• Avoid loops, high spots or the use of 90-degree elbows with seawater hose. Each 90-degree elbow is equivalent in
pressure drop to 2.5 feet (76.2cm) of hose and a 90-degree elbow on the pump outlet is equivalent to 20 feet
(609.6cm) of hose.
• Secure all hose connections with two stainless-steel hose clamps per fitting as close together as possible by putting
the screws of the two clamps on opposite sides.
• Use threaded-seal tape (2 to 3 wraps only) on all threaded connections. Tighten one and a half turns beyond hand
tight. Do not over-tighten!
• Install the seawater system with an upward incline from the speed scoop and seacock, through the strainer, to the inlet
of the pump and then up to the inlet of the air conditioning unit’s condenser coil.
• The discharge from the air conditioning unit should run to the seawater outlet thru-hull fitting, which should be located
where it can be visually checked for water flow and as close as practicable to the waterline to reduce noise.
1. Install the speed scoop thru-hull inlet as close to the keel and as far below the water line as possible, facing forward.
Bed the scoop with a marine sealant designed for underwater use.
2. Install a bronze, full-flow seacock on the speed scoop thru-hull inlet that meets ABYC specifications.
3. Install a seawater strainer below the level of the pump with access to filter.
4. Mount the pump above the strainer and at least one foot (305mm) below the waterline. (See Figure 5 on page 15 for
correct pump-head orientation positions.)
16 L-2805 ENGLISH
Emerald Split System Installation, Operation & Maintenance Manual Overview
5. Connect the seacock and strainer with an uphill run of 5/8" (16mm) or larger for multi-ton units reinforced marine-grade
hose.
6. Connect the discharge from the pump uphill to the bottom inlet of the air conditioning unit’s condenser coil with 5/8"
(16mm) or larger reinforced marine-grade hose.
7. Connect the discharge from the condenser coil to the overboard discharge thru-hull fitting with 5/8" (16mm) or larger
reinforced marine-grade hose.
8. Connect all metallic parts in contact with seawater to the vessel’s bonding system, including the speed scoop inlet,
strainer, pump, and the air conditioner.
L-2805 ENGLISH 17
Safety Emerald Split System Installation, Operation & Maintenance Manual
SAFETY
WARNING
To avoid personal injury, shock, or death, open the electrical disconnect switch before electrically connecting the unit.
Wiring must conform with NEC or CEC and all local codes.
WARNING
To avoid the risk of fire or equipment damage, use only 75°C minimum-rated copper conductors.
WARNING
Consult the National Electrical Code or a qualified electrician for proper wire size. Undersized wires could cause poor
equipment performance, equipment damage, or fire.
WARNING
To avoid electrical shock, injury, or death, wiring to the unit must be properly grounded.
WIRING
Wire size is to ensure proper unit operation. The size must be sufficient to carry the minimum circuit ampacity listed on the
unit’s data plate label. Dometic recommends sizing the wires to limit the voltage drop to a maximum of 2% from the main
breaker or fuse panel to the condenser unit. Consult the NEC, CEC and all local codes to determine the correct wire gauge and
necessary length of run for proper wiring.
1. To connect unit to power supply, route the power supply and ground wires through the high voltage entrance in the unit.
2. Connect the ground wire to the ground lug and power supply wires to the contactor.
3. Connect the low voltage wires to the terminal strip (if present) or to the wire leads. Route the low-voltage wire through
the wire tie provided in the unit for restraint.
4. Connect thermostat to unit. If a proper room thermostat is not already present, install one at a suitable indoor location.
3-PHASE NOTICE
It is extremely to ensure that wiring and phase sequencing of a 3-phase power source is correct. Marine wiring standards call
for power source phases L1, L2, and L3 to be color-coded BLACK, WHITE, and RED, respectively. These must be connected to
the unit with the proper sequence, otherwise, it will not operate properly. If the wiring sequence is incorrect, the unit’s
compressor (scroll type only) and pump (if applicable) will run in the reverse direction at a significantly increased noise level.
WIRING DIAGRAM
Use the wiring diagram provided with the digital or manual control you are installing.
18 L-2805 ENGLISH
Emerald Split System Installation, Operation & Maintenance Manual Operation
OPERATION
Refer to Figure 6 on page 19.
1. Ensure seawater intake ball valve (seacock) is open.
2. Turn SYSTEM SWITCH (top control knob) to OFF.
3. Turn on AC circuit breaker. If the seawater pump has its own circuit
breaker, turn that on also.
4. Turn the SYSTEM SWITCH (top control knob) to Fan (middle
position); this energizes the fan and seawater pump.
5. If in cool mode, turn THERMOSTAT (bottom control knob) to the
coolest position by rotating fully clockwise. If in heat mode, turn
THERMOSTAT (bottom control knob) to the warmest position by
rotating fully counter-clockwise.
6. Check for steady solid stream of seawater from the overboard
discharge.
7. Turn FAN SPEED (middle control knob) clockwise to highest setting.
8. Verify that the fan is running and that there is steady airflow out of the supply-air grille.
9. Turn the SYSTEM SWITCH (top control knob) to ON; this will start the compressor.
10. To set the thermostat, allow sufficient time for the unit to cool/heat the area to the desired temperature. When the area
is sufficiently cooled/heated, turn the THERMOSTAT (bottom control knob) slowly toward the center position until it
clicks once. The thermostat is now set to maintain a constant temperature. While heating, if the ambient temperature is
less than 50°F (10°C), set the FAN SPEED (middle control knob) to LOW for 5 to 10 minutes until the unit begins to
heat well, then increase the fan speed for more heat output.
The thermostat on the MCP serves to cycle the compressor on and off and provides an automatic changeover from cooling to
heating with a 3.5° differential. Rotating the thermostat to the left after it has been set for cooling will cause the unit to heat. If
you rotate the thermostat to the right, the unit will cool. If the thermostat is left stationary after being set, the unit will cycle from
cooling to neutral, or from heating to neutral depending on the requirement.
The condenser’s reversing valve switches the unit between heating and cooling modes, and it must be energized periodically to
keep the internal parts moving freely. To accomplish this, for a few seconds once a month switch the air conditioning unit to
HEAT if running in cool mode or to COOL if running in heat mode.
NOTE: Do not turn the unit off and immediately turn it back on. Allow at least 3 minutes for refrigerant pressure to equalize.
L-2805 ENGLISH 19
Determining Refrigerant Charge Emerald Split System Installation, Operation & Maintenance Manual
SYSTEM STARTUP
WARNING
To prevent compressor damage or personal injury:
• Do not overcharge system with refrigerant.
• Do not operate unit in a vacuum or at negative pressure.
• Do not disable the low pressure switch.
• Use care when handling scroll compressors; dome temperatures could be hot.
CAUTION
To prevent personal injury, wear safety glasses, protective clothing, and gloves when handling refrigerant.
CAUTION
To prevent personal injury, fully backseat (turn counterclockwise) valve stem before removing gauge port caps and
connecting and disconnecting manifold gauge hoses. Do not vent refrigerant to atmosphere. Recover during system
repair or final unit disposal.
NOTICE
During all installation and service work, follow all regulations of the Environmental Protection Agency (EPA). This
system uses R-410A, an HFC (Hydrofluorocarbon). Violation of EPA regulations may result in fines or other penalties.
NOTICE
Never operate the compressor with the suction valve closed to “test the compressor’s pumping efficiency”. In some
cases, this can result in serious compressor damage and loss of warranty coverage.
20 L-2805 ENGLISH
Emerald Split System Installation, Operation & Maintenance Manual Determining Refrigerant Charge
Note:
• Emerald systems are dual metered at the air coil for cool mode and at the condensing unit for heat mode.
• Emerald systems use Thermal Expansion Valves 7;9 to optimize system operation and thus cannot
becharged using superheat method.
• A properly operating TXV will maintain Superheat in range of 10 to 25 degrees.
• System must be charged by Table or Subcooling method.
Unit Specifics
Tube Diameter Lineset Factory
Unit Liquid Suction Charge/ft Charge (oz)
6-10k 1/4 3/8 0.23 14
12k 1/4 3/8 0.23 17
16k 1/4 1/2 0.26 17
24k 3/8 5/8 0.64 42
30k 3/8 3/4 0.67 46
36k 3/8 3/4 0.67 50
48k 3/8 3/4 0.67 64
L-2805 ENGLISH 21
Factory-Charge Release Into System Emerald Split System Installation, Operation & Maintenance Manual
NOTE: R-410A refrigerant cylinders contain a dip tube which allows liquid refrigerant to flow with the cylinder in an upright
position. R-410A refrigerant should be charged in the upright position with the liquid gradually metered into the unit.
NOTICE
Use only refrigerant which is certified to meet ARI Standard 700. Used refrigerant may cause compressor damage and
will void the warranty. (Most portable machines cannot clean used refrigerant well enough to meet this ARI Standard.)
SYSTEM STARTUP
1. If manifold gauge set hoses are connected, proceed to step 3. Otherwise, connect the gauge hoses. Ensure the
service valve stems are fully backseated and the manifold gauge set hoses are connected to the service valve ports.
2. Rotate the base valve stems one-half turn clockwise so pressure can be read by the manifold gauges.
3. Close electrical disconnects to energize system.
4. Set cabin thermostat to COOL and fan control to ON or AUTO. Set the temperature control well below room
temperature. Operate unit for 20 minutes. Check system refrigerant charge.
22 L-2805 ENGLISH
Emerald Split System Installation, Operation & Maintenance Manual Final Checks
5. Compare suction pressure with performance data. The suction pressure depends on which coil model is installed, fan
speed, and the indoor air flow and wet bulb. Do not adjust refrigerant based on suction pressure unless there is a gross
undercharge.
6. Compare the liquid pressure to the specification data. Liquid pressure depends on the suction pressure, outdoor
temperature, and the liquid subcooling. Charge adjustments should be based on the required subcooling determined
above.
7. Check the condensing unit amps to the specification data. The amp reading will track with the liquid pressure.
8. If the system is performing properly, fully backseat liquid valve. Remove the manifold gauge hose from the valve port
liquid side. Open both gauges to pull refrigerant to low side pressure. Remove suction side hose from port.
9. Fully backseat suction valve and torque valve stems to the values shown in Table 5 on page 23.
Table 5: Tubing Size and Torque Value for Flare Connections Chart
1/4” 10 9
3/8” 10 17
1/2” 16 30
5/8” 16 40
3/4” 22 52
10. Reinstall service port cores and caps. Torque caps to 10 foot pounds.
11. Perform a final refrigerant leak test on the valves and sweat connections.
12. Return the thermostat to the desired settings.
FINAL CHECKS
• Ensure all wiring and tubing are secure in the unit before adding panels and covers.
• Securely fasten all panels and covers.
• Leave this manual (and digital control manual, if any) with owner. Explain system operation and periodic maintenance
requirements outlined in manual.
Fill out “INSTALLATION CHECKLIST” on page 25.
L-2805 ENGLISH 23
Final Checks Emerald Split System Installation, Operation & Maintenance Manual
55 60 65 70 75 80 85
55 60 65 70 75 80 85 90
Min Max Min Max Min Max Min Max Min Max Min Max Min Max Min Max
MODEL
6k 186 216 206 236 226 256 246 276 266 296 286 316 306 336 326 356
8k 196 226 217 247 238 268 260 290 281 311 302 332 323 353 344 374
10k 192 222 213 243 234 264 255 285 276 306 297 327 318 348 339 369
12k 197 227 218 248 239 269 260 290 281 311 303 333 324 354 345 375
16k 204 234 225 255 246 276 267 297 288 318 310 340 331 361 352 382
24k 202 232 223 253 244 274 265 295 286 316 307 337 328 358 349 379
30k 221 251 242 272 264 294 285 315 307 337 328 358 350 380 371 401
36k 201 231 221 251 241 271 260 290 280 310 300 330 320 350 340 370
48k 209 239 230 260 252 282 273 303 295 325 316 346 337 367 359 389
60k Est. 221 251 242 272 264 294 285 315 307 337 328 358 350 380 371 401
72k Est. 202 232 223 253 244 274 265 295 286 316 307 337 328 358 349 379
55 60 65 70 75 80 85
55 60 65 70 75 80 85 90
Min Max Min Max Min Max Min Max Min Max Min Max Min Max Min Max
MODEL
6k 49 61 64 76 79 91 94 106 109 121 124 136 139 151 155 167
8k 55 67 70 82 85 97 99 111 114 126 129 141 144 156 158 170
10k 53 65 66 78 80 92 93 105 106 118 120 132 133 145 147 159
12k 51 63 63 75 75 87 87 99 100 112 112 124 124 136 136 148
16k 52 64 65 77 78 90 91 103 104 116 117 129 129 141 142 154
24k 55 67 69 81 84 96 98 110 113 125 127 139 142 154 156 168
30k 55 67 69 81 84 96 98 110 113 125 128 140 142 154 157 169
36k 52 64 66 78 80 92 94 106 108 120 122 134 136 148 150 162
48k 61 73 75 87 89 101 102 114 116 128 130 142 144 156 158 170
60k Est. 55 67 69 81 84 96 98 110 113 125 128 140 142 154 157 169
72k Est. 55 67 69 81 84 96 98 110 113 125 127 139 142 154 156 168
24 L-2805 ENGLISH
Emerald Split System Installation, Operation & Maintenance Manual Final Checks
INSTALLATION CHECKLIST
REVIEW PRIOR TO INSTALLATION AND AFTER
Speed scoop located as far below the water line and as close to the keel as possible.
Shutoff valve and speed scoop properly sealed and tight.
Seawater pump is at least one foot below water line and securely mounted.
Strainer mounted below pump with access to filter.
Double/reversed stainless steel hose clamps on all hose connections.
Threaded-seal tape on all threaded connections.
Hose runs uphill from speed scoop and seacock to strainer, pump, and air conditioning unit, then downhill (if
possible) from air conditioning unit to overboard discharge.
Water flowing freely from overboard discharge while pump is running.
Pump relay panel, if used, must have its own circuit breaker sized for the pump (20 amp max).
All metal fittings must be bonded.
Mounting
DX air handler not in engine room or bilge areas, must be sealed away from exhaust or fumes
Proper spacing allowed around unit.
Securely attached to solid level platform with hold down clips provided.
Condensate drain routed aft and down hill to a sealed sump (not bilge).
Blower rotated toward supply-air grille.
Electrical
All butt connections on pump wire tightly crimped and heat shrunk.
AC power source installed and grounded/bonded in accordance with ABYC standards.
Control wires connected to terminal strip with fork or ring terminals.
Circuit breakers sized according to specifications on the data plate label.
Remote electrical box mounted with position-sensitive relay taken into consideration.
Digital control display cable is connected at both ends.
Pump Relay Panel (if used) has a dedicated circuit breaker sized for the pump but not to exceed 20 amps maximum.
Grilles and Ducting
Pressure tested.
Evacuated.
No kinks or crushed piping and no vertical loops.
Correct insulation thickness and properly sealed.
Piping supported.
L-2805 ENGLISH 25
Cooling Mode Emerald Split System Installation, Operation & Maintenance Manual
Turn on the air conditioning circuit breaker. If the seawater pump has its own circuit breaker, turn that on.
Check for a steady solid stream of water from the overboard discharge.
If the unit does not appear to be operating properly, refer to Troubleshooting Guidelines.
NOTE: Do not turn the unit off and immediately turn it back on. Allow at least 3 minutes for refrigerant
pressure to equalize.
SERVICING
WARNING
Care should be taken when attaching the low side of a gauge manifold in the Heat Cycle. On Emerald R-410A units,
both base valves can see high pressure while in heating mode. High-pressure refrigerant can retard and damage a
low-side gauge.
NOTE: In the following sections the liquid receiver, liquid line filter dryer, and suction accumulator will not be mentioned; this is
to simplify the description of system operation. On all systems and in both modes of operation, the configuration of the
discharge and suction lines between the reversing valve and compressor remain the same.
COOLING MODE
In cooling mode the reversing valve is NOT energized. Hot high-pressure gas is discharged from the compressor through the
reversing valve to the water-cooled condenser coil. There, the hot gas gives up heat to the cooler water circulating through the
coil. The heated water is then discharged overboard. As the gas is cooled it condenses into a liquid. It is then fed to the metering
device on the evaporator, the thermal expansion valve (TXV). The TXV is the transition point of the low- and high-side of the
system and regulates the flow of liquid refrigerant into the evaporator. As the liquid travels through the evaporator tubing it
absorbs heat from the air passing through the finned coil. This causes the liquid refrigerant to boil off into a vapor. The low-
pressure vapor is then returned to the reversing valve via the suction line and then to the compressor.
HEATING MODE
In heating mode, the reversing valve IS energized. The plunger in the valve body moves, changing the direction of the
refrigerant flow. The suction line becomes the hot-gas discharge line. The hot-gas line to the condenser now becomes the liquid
line. The hot gas flows to the air-cooled evaporator that is now the condenser. The cool air passing across the finned coil
absorbs the heat from the refrigerant and is returned to the cabin as warm air. As the refrigerant gives up heat it again turns into
a liquid. The liquid is returned to the condensing unit and metered through the TXV at the condensing unit into the water coil.
The refrigerant passes through the water coil, which is now the low-side evaporator. Heat is absorbed from the water as it
passes through the coil and the refrigerant boils off into a vapor. The vapor returns to the compressor via the reversing valve.
26 L-2805 ENGLISH
Emerald Split System Installation, Operation & Maintenance Manual Schematic Diagram of Refrigerant System
Figure 7: Schematic Diagrams of Refrigerant Systems in Cool Mode and Heat Mode
L-2805 ENGLISH 27
General Troubleshooting Emerald Split System Installation, Operation & Maintenance Manual
TROUBLESHOOTING
GENERAL TROUBLESHOOTING
If you have a digital control, refer also to the troubleshooting section of the manual packaged with it.
System will not start. 1. DX air handler circuit breaker is off. Turn circuit breaker on at ship’s panel.
2. Digital control is not turned on. Press the Power button.
3. Wrong wiring at terminal strip. Check wiring diagram; correct if necessary.
4. Input-line voltage is insufficient. Check power source (shore/generator) for proper
voltage. Check wiring and terminals for proper sizes and connections. Verify with a
volt-meter that the power at the unit is the same as the power source.
5. Push-on connectors or butt splices became disconnected during installation.
Disconnect power supply and open electric box, check wiring diagram, correct if
necessary.
Fan is not running. Check the troubleshooting section of your digital control manual.
No cooling or heating. 1. Temperature set point is satisfied. Lower or raise set point.
2. Obstructed seawater flow. Clean seawater strainer. Check for obstructions at speed
scoop thru-hull inlet. Check for a good steady flow from the overboard discharge.
3. Seawater pump may be air-locked. Remove hose from pump discharge to purge air
from line.
4. Loss of refrigerant gas. Check air conditioning unit for refrigerant oil leakage, call
service technician.
5. Seawater temperature too high for cooling or too low for heating. Seawater
temperature will directly affect air conditioning unit’s efficiency. This air conditioning
unit can effectively cool your boat in water temperature up to 90°F (32.2°C) and heat
(if reverse-cycle option is installed) in water temperatures as low as 40°F (4.4°C).
6. Fan coil is iced (in cooling). Check your specific control troubleshooting section.
7. Fan is not running. Check your specific control troubleshooting section.
8. Seawater plumbing is air-locked. Ensure that seawater plumbing is installed per the
guidelines in this manual.
9. Digital control is programmed for Cool or Heat only, or mechanical-control
thermostat is rotated too far toward either Cooler or Warmer setting. See the
control’s Operations Manual for instructions.
10. High-pressure switch is open (in cooling) due to improper seawater flow.
Strainer or intake may be plugged, seacock may be closed, check seawater hose for
kinks or collapses. Verify pump operation. Check pump circuit breaker if applicable.
11. High-pressure switch is open (in heating) due to improper airflow. Remove any
obstructions in return air stream. Clean return air filter and grille. Check for crushed or
restricted ducting, ducting must be as straight, smooth and taut as possible.
12. High-pressure switch is open (in heating) due to high seawater temperature.
System may cycle on high pressure if seawater temperature is above 55°F (12.8°C).
Increase fan speed.
13. Compressor’s thermal overload is open due to either of the above reasons.
Compressor needs to cool down. Turn system off for a while (it may take up to three
hours to reset thermal overload).
No heating. Unit is in "cool only" mode, or reversing valve may be stuck. Tap reversing valve
lightly with rubber mallet while unit is in heat mode. Call for service if that does not correct
the problem.
28 L-2805 ENGLISH
Emerald Split System Installation, Operation & Maintenance Manual Return-Air Filter
Low airflow. 1. Airflow is blocked. Remove any obstructions in return-air stream. Clean return-air
filter and grille. Check for crushed or restricted ducting; ducting must be as straight,
smooth and taut as possible.
2. Fan Coil is iced. See below.
3. Fan speed is set to manual low. If the fan speed is set to manual low, press and
release the Fan button until the desired fan speed and airflow are reached. If you
want automatic fan speed control, press and release the Fan button until the letter “A”
displays.
Fan coil is iced. 1. Thermostat set point is too low. Raise set point.
2. Improper airflow. Remove any obstructions in return air stream. Clean return air filter
and grille. Check for crushed or restricted ducting, must be as straight, smooth and
taut as possible. See the Digital Controls Troubleshooting section below for
reprogramming options.
3. Supply air is short-cycling. Redirect supply air so that is not blowing into the return
air stream. Seal any air leaks on duct.
4. Humidity level too high. Close hatches and doors.
5. When all else fails. Switch air conditioning unit to heat until ice melts or use hair
dryer to melt.
Water coil is iced in the Seawater temperature is below 40°F (4.4°C). Shut down system to prevent damage to
Heating Mode. condenser. Allow coil to defrost.
System runs continuously. 1. Set point temperature is improperly set: too low for cooling or too high for
heating. Raise or lower set point.
2. Porthole or hatches open. Close all port holes and hatches.
3. Seawater temperature too high for cooling or too low for heating. Seawater
temperature will directly affect the air conditioning unit’s efficiency. This air
conditioning unit can effectively cool your boat in water temperatures up to 90°F
(32.2°C) and heat in water as low as 40°F (4.4°C).
4. Improper air sensor location. Check your specific control troubleshooting section.
MAINTENANCE
RETURN-AIR FILTER
Check the return air filter about once a month and clean or replace as necessary. To clean the filter, remove it from the unit,
rinse with water
REVERSING VALVE
Reverse cycle units have a reversing valve. The valve must be energized periodically to keep the internal parts moving freely. To
do this, switch the air conditioning unit into heat for a few seconds once a month.
SEAWATER STRAINER
Ensure that your pump receives adequate seawater flow by regularly cleaning the strainer basket. Periodically check the
overboard discharge for a steady stream of water. Check seawater intake speed scoop for obstructions. Be sure hoses are not
looped, kinked, or crushed.
L-2805 ENGLISH 29
Winterization Emerald Split System Installation, Operation & Maintenance Manual
2. Use chemical-resistant hoses (DOM white PVC 5/8" I.D., etc.) to connect the inlet of the condenser coil to the outlet of
a chemical resistant, submersible pump (DOM P-500 pump, etc.) and let the hose connected to the coil outlet flow
freely into the container mentioned below.
3. Place the pump into a container filled with cleaning solution. Dometic does not warrant the efficacy of any third-party
cleaners. Do NOT exceed the recommended concentration or duration. Use as large a container as possible to hold
the solution (5-25 gallons [19-95 liters]). Do NOT use muriatic acid (hydrochloric acid), bleach, or bromine. These
chemicals accelerate corrosion and can cause coil failure.
WARNING
Avoid spilling or splashing the solution. Follow all warnings and recommendations given by the manufacturer of any
premixed solutions.
4. Power the pump and circulate the solution through the condenser coil for 15-45 minutes depending upon the size of
the coils and the extent of the contamination. Visual inspection of the solution in the container should indicate when the
contamination removal has stopped.
5. Circulate fresh water through the coil to flush any residual cleaning solution from the system.
6. Restart the system and check operational parameters to ensure thorough cleaning has taken place. Additional
cleaning may be necessary with extreme contamination.
NOTICE
For the purpose of protecting the environment, dispose of any contaminated cleaning solutions in accordance with
federal, state and/or local regulations.
WINTERIZATION
There are several methods of winterization, some of which work better than others. Any method that causes the antifreeze
solution to flow downward is the method of choice. By this means, the antifreeze solution displaces any trapped water and
eliminates the possibility of it freezing in hidden areas.
Choose the method that works best for you. In the following four methods, the first two use a 50/50 nonpolluting biodegradable
antifreeze/water solution:
• Pump antifreeze solution into the overboard thru-hull fitting, and discharge through the intake thru-hull fitting.
• Use the seawater pump to pump antifreeze solution through the system and discharge through the overboard thru-hull
fitting: Close sea cock, remove hose from strainer discharge, raise hose above pump (so pump does not lose its prime)
and pour in antifreeze solution. Pump solution through system. The strainer and hose to sea cock need to be drained
of water.
• Use pressurized air injected at the overboard discharge fitting to force system water through the seawater intake fitting,
thus expelling any trapped water from the system.
• Use pressurized air injected at the seawater intake fitting to force system water through the seawater overboard
discharge fitting, thus expelling any trapped water from the system.
In addition, since the seawater pump utilizes a magnetically driven impeller, remove the impeller from the wet-end assembly,
wipe with an alcohol solution, and store in a warm, dry area until commissioning takes place.
NOTICE
Collect all discharged liquids and recycle or dispose of in a proper manner in accordance with federal, state and/or
local regulations.
30 L-2805 ENGLISH
NOTES
NOTES
NOTES
DOMETIC MARINE DIVISION
2000 N. Andrews Ave.
Pompano Beach, FL 33069 USA
Tel +1 954-973-2477
Fax +1 954-979-4414
Email MarineSales@dometic.com
dometic.com