ML255 Electromagnetic Flow Meter Converter: Installation, Operation and Maintenance Manual
ML255 Electromagnetic Flow Meter Converter: Installation, Operation and Maintenance Manual
ML255 Electromagnetic Flow Meter Converter: Installation, Operation and Maintenance Manual
Electromagnetic
Flow Meter Converter
www.mccrometer.com
Contents
SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.0 CONVERTER OVERVIEW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2.0 INSTALLING THE CONVERTER AND CABLES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2.1 Verify Serial Numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2.2 Mounting The Converter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2.3 Installing Cables To Converter And Service Loop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2.4 Pulling Sensor Cable Through Electrical Conduit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
3.0 BATTERY INSTALLATION AND SYSTEM START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3.1 Battery Life . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3.2 Installing Batteries and Starting Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3.3 Setting the Time and Date . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.4 Replacing Batteries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.5 Powering-Down and Powering-Up the System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.6 Power Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.7 Sampling Frequencies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
4.0 SOLAR PANEL OPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
4.1 Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
5.0 ELECTRICAL CABLE CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
5.1 Converter Electrical Cable Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
5.2 Terminal Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
5.3 FPI Mag and Ultra Mag 4" through 48" . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
5.4 Ultra Mag 2" & 3" . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
5.5 SPI Mag 282L Cable Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
5.6 Converter Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
5.7 Opto-Isolated Pulse Output Hook-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
5.8 Opto-Isolated Pulse Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
5.9 Converter Power Hook-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
6.0 CONVERTER START-UP - ALL SENSORS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
6.1 Menu Navigation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
6.2 Front Panel Visualization Pages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
6.3 Factory Set Key Code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
6.4 Menu Structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
7.0 PROGRAMMING EXAMPLE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
8.0 MENU 0 - QUICK START . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
9.0 MAIN MENU DESCRIPTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
9.1 Menu 1 - Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
9.2 Menu 2 - Scales . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
9.3 Menu 3 - Measure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
9.4 Menu 4 - Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
9.5 Menu 5 - Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
9.6 Menu 6 - Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
9.7 Menu 7 - Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
9.8 Menu 8 - Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
9.9 Menu 9 - Data Logger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
9.10 Menu 10 - Diagnostic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
9.11 Menu 11 - Internal Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
10.0 ALARM MESSAGES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
11.0 SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
12.0 DIMENSIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
13.0 RETURNING A UNIT FOR REPAIR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
14.0 TROUBLESHOOTING GUIDE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
APPENDIX 1.0 UNITS OF MEASURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
APPENDIX 2.0 CONVERSION TABLES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
WARRANTY STATEMENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
This symbol indicates important safety information. Failure to follow the instructions can
i This symbol indicates important information. Failure to follow the instructions can result in
permanent damage to the meter or installation site.
Safety Warnings
When installing, operating, and maintaining McCrometer equipment where hazards may be present, you must protect
yourself by wearing Personal Protective Equipment (PPE) and be trained to enter confined spaces. Examples of confined
spaces are manholes, pumping stations, pipelines, pits, septic tanks, sewage digesters, vaults, degreasers, storage tanks,
boilers, and furnaces.
WARNING!
! Incorrect installation or removal of FPI Mag meters can result in serious injury or death. Read the
instructions in this manual on the proper procedures carefully.
WARNING!
! Never enter a confined space without testing the air at the top, middle, and bottom of the space. The air
may be toxic, oxygen deficient, or explosive. Do not trust your senses to determine if the air is safe. You cannot
see or smell many toxic gases.
WARNING!
! Never enter a confined space without the proper safety equipment. You may need a respirator, gas detec-
tor, tripod, lifeline, and other safety equipment.
WARNING!
! Never enter a confined space without standby/rescue personnel within earshot. Standby/rescue personnel
must know what action to take in case of an emergency.
WARNING!
! Pressurized pipes should only be hot tapped, cut, or drilled by qualified personnel. If possible,
depressurize and drain the pipe before attempting any installation.
WARNING!
! Carefully read all safety warning tags attached to the meter.
At the end of its lifetime, this product shall be disposed of in full compliance with the
environmental regulations of the state in which it is located.
i
IMPORTANT: Verify the Meter Serial Numbers on both the converter and sensor match. This will ensure a
properly calibrated system. The Meter Serial Number is located on the side of the sensor, and the Converter
Serial Number and the Meter Serial Number are located on a label on the side of the converter. Ensure the
Meter Serial Number on the sensor and the converter tags match.
WARNING: Do not connect any form of conduit directly to the converter enclosure. Doing so will allow moisture
! and potentially dangerous gasses to enter directly into the converter. Attaching any conduit to the enclosure, or
altering the enclosure in any way will void the warranty.
i
CAUTION: Do not cut the cable cover off. Doing so may damage the sensor cable and adversely effect the
calibration of the meter.
Cable Cover
CONTINUOUS SAMPLING
Maximum sample rate
Max S.R. Max S.R. Max S.R:
AVERAGE SAMPLING
Sample rate at 3 seconds
3 Sec. 3 Sec. 3 Sec.
S.R.=SAMPLE RATE
SMART SAMPLING
Automatic sampling switch
according to flow profile VARIABLE S.R. VARIABLE S.R.
Each sampling frequency mode has a different effect on battery life. Note that the battery life shown below is under optimal
conditions:
An internal algorithm allows the unit to automatically detect flow rate variations in the process.
• Continuous sampling: < 6 months
This capability determines the automatic setting of the sampling frequency. No variations means
lower sampling frequency, with less power consumption; high variations means higher frequency
• Average sampling: > 5 years
to better follows the changes in the process.
• Max life sampling: > 7 years
• Smart sampling: 1-5 years depending on flow profile
Note: Continuous sampling is only available if energy saving is turned off. Energy saving can only be accessed through the
IF2 communication cable.
193 mm
The solar panel provides power to the converter by converting
7 ½”
sunlight into electrical energy to recharge the solar panels'
rechargeable battery. Its nominal power output is 5W. The solar
panel comes complete with all accessories, except for the fixing rod.
(Figure 6 and Figure 7)
295 mm
11 ½”
193 mm
7 ½”
50 mm
2“
! CAUTION - Always disconnect the power cord before attempting any electrical connections.
All electrical cables enter the converter through compression fittings located on the side of the converter. Ensure that all
compression glands are properly tightened and all unused fittings are plugged so the case remains sealed.
5.2 Terminal Board
All connections are made on the terminal board (Figure 8). To access the terminal board, loosen the four screws on the back
of the converter to remove the rear cover.
NOTE: The terminal blocks unplug from the circuit board for easy connection.
External power
12-60VDC or 100-
240VAC connector
block battery socket
M1 connector block
IF2X socket
DIP switch for
SD memory card keyboard block
1 2 3 4 5 6 7 8 9 10
11 12 13 14 15 16 17
SH C1 C2
SH B1 B2 E
OUT1 OUT2 OUT1 OUT2
COILS OPEN COMMON
COLLECTOR
Black Ground
To Chassis Lug
1 2 3 4 11 12 13 Right Sensing
8/16
A #1 (E1) Blue
ML255
electrodes
CHASSIS | BLACK
RED
YELLOW
BLUE
PINK
BLACK
GREEN/YELLOW
GREEN/YELLOW
Left Sensing
i
*IMPORTANT: See Section 5.6.1, "Converter Grounding
For FPI Mag Ultra Mag 4" - 48"", Figure 13 for instructions
on attaching the chassis ground wire to the converter
ground lug.
Shrink Tube
CABLE A - ELECTRODES
Cable Diameters:
CABLE B - COILS
Cable Jacket
Black Ground
To Chassis Lug
1 2 3 4 11 12 13 Right Sensing
8/16
A #1 (E1) Blue
ML255
electrodes
BLUE
PINK
BLACK JUMPER
GREEN/YELLOW
CHASSIS | BLACK
GREEN/YELLOW
RED
YELLOW
p/n 17134 Rev. 1.0
Left Sensing
A #2 (E2) Pink
Electrodes
Reference
B #3 (C) Black
Ground
Cable Shield
A #4 (SH) Green/Yellow
Ground
Ground To
B Chassis Lug Black
Chassis Lug*
Cable Shield
B #11 (SH) Green Yellow
Ground
B #12 (B1) Red Coil
B #13 (B2) Yellow Coil
i
*IMPORTANT: See Section 5.6.2, "Converter Grounding For
Ultra Mag 2" & 3"", Figure 14 for instructions on attaching
the chassis ground wire to the converter ground lug.
Shrink Tube
CABLE A - ELECTRODES
CABLE B - COILS
Cable Diameters:
Cable A (15035): 0.248”
Cable B (15036): 0.248”
Cable Jacket
#1 Blue
electrode
WHITE
BLUE
BLACK
BLACK
RED
YELLOW
Sensing
#2 White
electrode
Reference
#3 Black
ground
Magnet shield
#11 Black / overall cable
shield
#12 Red Coil
#13 Yellow Coil
Cable Diameter:
Single Cable (36002): 0.250”
Black Ground
Cable B Wire With Loop
From Cable B
Black Ground
Cable B Wire With Loop
From Cable B
With Lead To
Terminal #3
i
IMPORTANT
Outputs are not isolated from each other. All outputs MUST use the same power source.
OUT 1
15
OUT 2
16
COMMON EMITTER
17
Push button
switch
10K +
5 3-40 VDC
24V
-
6
i WARNING!
Hazardous supply voltage can shock, burn, or cause death.
The power supply line must be equipped with external surge protection for current overload (fuse or circuit breaker with
limiting capacity not greater than 10A). It must be easily accessible for the operator and clearly identified.
Power connection is made using the power terminal block on the upper right side of the terminal board. (Figure 17 and
Figure 18)
NOTE: The terminal block uplugs from the circuit board for easy connection. Connect earth ground to the protective
grounding terminal before making other connections. The power supply of this converter is 100 - 240 VAC, 44 - 66 Hz at
maximum 4 W or 12-60 VDC.
Neutral Wire
Typically A
White Wire Negative Wire
Figure 17. AC power supply terminal block Figure 18. DC power supply terminal block
Key: Function:
UP/DOWN KEY (for moving cursor up or down)
SHORT PRESSING (< 1 SECOND):
Moves the cursor up to the previous subject on the menu
Increases the numeric figure of the parameter highlighted by the cursor
Enter/Esc
Key LONG PRESSING (> 1 SECOND):
Confirms the selected function
Leaves the current menu
Figure 19. Converter key conventions
"Visualization pages" are different display screens that present specific information.
If there is screen is in "screen saver" mode, long-press the Left/Right arrow key to wake it up. Short-press the Left/Right
arrow key to cycle through the different visualization pages.
i ATTENTION!
It is very important to record any customized code as it CANNOT be retrieved if it is lost! The converter will
need to be returned to be reset to factory settings.
!2.UGPUQT!
PF>oo! 11467 1.1 Insert ND of sensor (0-300
MB>! ,13/1111 1.2 Calibration data of sensor v
1.3 Sensors model: Enter the f
Kpu/rqukvkqp>! 1 1.4 Position for insertion senso
Mk>! 2/1111
Mr>! 2/1111 1.5 Factory parameter
M\>! ,111111 1.6 Automatic setting accordin
ME>! 2/1111 1.7 Automatic setting accordin
1.8 Enables the empty pipe de
VE2>ou! 121 1.9 Value of empty pipe sensib
VE3>ou! 112 1.10 Perfom a SENSOR TEST ( s
G/R/fgvgev>! QP 1.11*Enables the automatic zero
G/r/vjt>! 181 1.12 Reset the preceding value
\gtq!ecn/
\gtq!tgu/
!7.QWVRWVU
Qwv2>! RNU, 6.1* Output 1
6.5* Output 2
Qwv3>! QHH 6.6 Power supply of pressure pr
!22.KPVGTPBN!FBVB
N3!eqfg>! ++++++ 11.1 Level 2 access code enter
11.2 Load factory data pre-set
Nqcf!hcev/fcvc 11.3 Ks Coefficient
U0p>! 182341
MV>! ,2/1111
MT>! ,2/1111
MU>! ,2/1111
Note: The function used in the example is the top menu You will start with a blank screen.
item, so you will not need to scroll through the Quick 1. Long press on Enter/ESC.
Start menu. However, to do so, you need to have the
full menu item highlighted and press Left/Right or Up/
Down.
This will wake up
the front panel
..... ..... ..... ..... .....
.....
TER TER
EN EN
ESC ESC
TER TER
EN EN
ESC ESC
TER TER
EN EN
ESC ESC
NOTE: The Quick Start menu is configured at the factory. Some menus may not be available in your configuration.
If the
quick start menu is not present as the first menu option, then it has been disabled.
(See Section 9.8 to enable the Quick
Start menu.)
9.0 MAIN MENU DESCRIPTIONS
Press the key Enter/Esc key to go to the Main menu directly when the “Quick start menu” is disabled. When
it is not disabled
you can select the Main menu from the “Quick start menu”. The functions in the Quick
Start menu and the
Main menu are
explained below. Please note that some functions are only displayed if other functions or with the insertion
are enabled
of additional modules.
9.1 Menu 1 - Sensor
ND Inside Pipe Diameter
The inner diameter of the pipe entered in millimeters. NOTE: The flow accuracy will
only be as good as the accuracy of the actual pipe ID entered into the converter. The
“Nominal Pipe Size” often referred to can be different from the actual pipe ID and if
used cause a substantial error in flow reading. Setting the ND value to zero will cause
the converter to display the velocity instead of flow rate. Totalizer will then increment
in feet or meters.
KA
Factory calibrated gain for the forward flow. Do not change the value.
Ins. Position
This is for a single point sensor. Position for insertion sensors: 0=1/8DN, 1=1/2DN, 2=7/8DN
Ki
Automatic setting according to ID (insertion meter only).
Kp
Automatic setting according to ID (insertion meter only).
KZ
This is the Zero Calibration constant. The KZ updates every time the Zero Calibration is performed.
KC
This is a coil current adjustment factor for use between sensor families.
TC2
This is the time needed to stabilize coil current when switching coil polarity.
E.P.detect
Enables the empty pipe detection function.
E.P.thr.
Sets the empty pipe detection threshold.
Zero cal.
Zero point calibration function for the forward flow. Enables the automatic zero calibration system.
i
IMPORTANT - The water must be perfectly still before starting
the Zero Cal process
or an offset
will be introduced into the flow report.
To perform the zero point calibration:
1. Select the Zero cal. menu and press will ask if you want
the Enter/Esc key. It to execute.
2.
Long press the Enter/ESC button and release when the message
"Measuring. . . " appears.
The converter counts up from zero to 700,
after which the zero point is set.
Zero
res.
This resets the Zero Calibration.
Once the desired value is entered quick push the Enter/Esc key to save the changes and then long push Enter/
Esc to exit back to the display.
Tot1MU
The totalizer unit/multiplier as well as the visible decimal place is set here.
To change the totalizer unit/multiplier:
1. Highlight the menu and press the Enter/Esc key. 2. Press the Up/Down key.
This will highlight This will scroll
the unit/multiplier. through the different
See Appendix 1.0 for available units.
available units of
NOTE: The totalizer
measure.
multiplier is built
into the unit of
TER
measure, so for
T ER
EN C
gallons multiplied by
EN C
ES ES
1000, select Kgal.
3. Press the Right/Left key twice. 4. Press the Up/Down key.
This will highlight
This will change the
the numeric value to
decimal resolution
the right.
displayed for the
totalizers. Changing
the decimal
resolution will
R
not change the
TE
N TER
EN C
multiplier. The E
ES ESC
available selections
are 00001, 001.0,
01.00, and 1.000.
If the desired unit of measure
is not in the current
list, press the Right/Left key
and scroll to the blank space between the unit/multiplier and the numeric
decimal resolution selection and press the
Up/Down key to switch between
U.S. Standard and Metric units.
Tpls1
Duration of the pulse output 1 expressed in milliseconds.
This option is only available when "out1" in Menu 6 -
Outputs is set to PLS+, PLS-, or PLS. The pulse duration
can be set from 8.0 to 7999.9.
IMPORTANT
i The converter cannot detect the type of device it is connected to so it is up to the user to verify the setting
is compatible with the external device receiving the pulse. Incorrect settings can damage the receiving
device. See section 10.6 Menu 6 - Outputs for output specifications.
Prof
Measurement Profile
0 = Continuous Power
1 = Smart
2 = Average
3 = Max Life
Continuous Power uses more battery power and is not recommended. Max Life uses the least battery power and is the
default.
Damping
Measure Filter Damping Profile Enable is only valid in the Smart Profile setting. This applies a fixed filter to the reading.
Al.max-
Maximum Reverse flow rate exceeded. Can be 0-125% of Full Scale
Al.min-
Minimum Reverse flow rate exceeded. Can be 0-125% of Full Scale.
Hyst.
Alarm Hysteresis. Set 0-25%. This sets the lag in response based on a percentage of the full scale. Example if the alarm
triggers at 100% and the hysteresis is set to 2% then once triggered the current rate must change beyond 2% to exit
out of the current alarm state. This setting applies to all alarms.
Count lock
Totalizer Count Lock Input Enable, Set by turning on or off. This allows for the totalizers to be locked (frozen) when the
input is active.
Alarm
Allows the input to be wired to an external alarm output such as a water intrusion alarm.
Wake-up
Wake up the display with an input.
Out 2
Transistor output channel 2. See tables on the next page for available settings.
OFF DISABLED
PLS PULSE FOR POSITIVE AND NEGATIVE FLOW VOLUME
PLS- PULSE FOR NEGATIVE FLOW VOLUME
PLS+ PULSE FOR POSITIVE FLOW VOLUME
F.SIGN FLOW DIRECTION OUTPUT (ENERGISED = -)
DIRECT. DR. DIRECT OUTPUT DRIVE
ALL ALARMS ALL ALARMS
OVR.RANGE. OUT OF RANGE ALARM OUTPUT (ENERGISED = FLOW RATE OK)
HARDW.AL. CUMULATIVE ALARM OUT interrupt coils, empty pipe, meas. error (ENERG. = NO ALARMS)
P.EMPTY EMPTY PIPE ALARM OUTPUT (ENERGISED = FULL PIPE)
MX+MN ALL MAX AND MIN ALARM OUTPUT (ENERGISED=AL. OFF)
*MX+MN TEMP MAX AND MIN TEMPERATURE OUTPUT (ENERGISED= AL. OFF)
*MIN TEMP MIN TEMPERATURE OUTPUT (ENERGISED= AL. OFF)
*MAX TEMP MAX TEMPERATURE OUTPUT (ENERGISED= AL. OFF)
*MX+MN P12 MAX AND MIN PRESSURE 1 AND 2 OUTPUT (ENERGISED= AL. OFF)
*MX+MN DP MAX AND MIN DIFFERENTIAL PRESSURE OUTPUT (ENERGISED= AL. OFF)
*MIN DP MIN DIFFERENTIAL PRESSURE OUTPUT (ENERGISED= AL. OFF)
*MAX DP MAX DIFFERENTIAL PRESSURE OUTPUT (ENERGISED= AL. OFF)
Comp.mode
Format the Data Logging Data to the previous version of this converter. Default=Off
int.1
Data Logging Interval. HH:MM:SS
Log T+
Include the T Positive Totalizer for Data Logging.
Log P+
Include the P Positive Totalizer for Data Logging.
Lot T-
Include the T Negative Totalizer for Data Logging.
Log P-
Include the P Negative Totalizer for Data Logging.
Log NT
Include the Net T Totalizer for Data Logging.
Log NP
Include the Net P Totalizer for Data Logging.
Log Q
Include the Flow Rate for Data Logging.
Log STAT
Include Statistics like the board temperature and cycles/h for Data Logging.
M.units
Include the Units of Measure for Data Logging.
% values
Include the Flow Rate % of full scale and optional analog inputs for Data Logging.
i CAUTION - if the passcode is changed from the default value and is lost, it CANNOT be recovered. In
the event the passcode is lost, the converter can be returned to the factory to be reset.
Load fact.data
This will configure the converter to the configuration when it left McCrometer.
S/n
Displays the board serial number.
KT
Used to adjust gain errors. This factor is generated by the converter at power up.
KS
Field adjustment coefficient. This value is a direct multiplier that is used as a field adjustment / correction coefficient.
ALARM
VIA
CODE MESSAGE CAUSE ACTION SMS *
000 NO ALARMS ----- ----- NO
001 SYSTEM STARTUP The system was started ----- YES
003 PRESS.1>FS The Pressure at input 1 is Check the maximum full scale set YES
higher than the full scale set and the process conditions
004 FLOW>FS The flow rate is higher than Check the maximum full scale set YES
the full scale set and the process conditions
005 PULS.1>F.MAX The pulse frequency at Reduce the pulse duration if the YES
output 1 is too high connected counter allow this or
increase the pulse unit value
006 B3 LOW The battery B3 powering the Replace the battery YES
MODEM is exhausted
007 B2 LOW The battery B2 powering the Replace the battery YES
main board is exhausted
008 B1 LOW The battery B1 powering the Replace the battery YES
main board is exhausted
077 SYSTEM RESTART The system was restarted If this message appears after an YES
after a reset signal AUTO-TEST command, it is not an
error indication, otherwise check
all the connections, the batteries
and the grounding
094 ALARM INPUT ACT. The digital input detected an Check the process condition YES
alarm signal condition
103 B.TEMP.OUT R. The measured board Ensure that the instrument is YES
temperature is out of the operating within the specified
allowed range temperature conditions
113 FIRMW.FILE ERR The file containing the Re-send the firmware file YES
firmware was received with
errors
115 S.OUT OVERLOAD An overload condition is Check the connections and YES
present in the power source the external sensors (pressure,
that feeds the external temperatures, input circuitry)
sensors and inputs
117 ERR.SENS.TEMP The external temperature Check the external temperature YES
sensor is not working sensor and its connections
properly
118 MAIL S.FAILED The last email sending Check the transmitting YES
process has failed for some conditions (antenna signals, GPRS
reasons parameters, server status and
configurations)
119 SMS NOT AUTH A SMS from a not authorized Check the events log for the YES
number was received sender number and do the
appropriate actions
*Not available at this time.
ALARM
VIA
CODE MESSAGE CAUSE ACTION SMS *
135 V.MODEM LOW The internal voltage of the Check the battery B3 and its YES
MODEM is not sufficient for to connections, verify if any visible
guarantee a proper operation damage has occurred to the
board or the MODEM
144 NO CMD RECEIVED The command list sent to the Check the command list and re- YES
instrument does not contain send it again
any executable commands
150 MAX Q+ The Positive flow rate is Check the maximum threshold YES
higher than the maximum positive flow rate alarm value and
threshold value set the process conditions
151 MIN Q+ The Positive flow rate is lower Check the minimum threshold YES
than the minimum threshold positive flow rate alarm value and
value set the process conditions
153 MAX Q- The Negative flow rate is Check the maximum threshold YES
higher than the maximum negative flow rate alarm value
threshold value set and the process conditions
154 MIN Q- The Negative flow rate is Check the minimum threshold YES
lower than the minimum negative flow rate alarm value
threshold value set and the process conditions
157 MAX P1 The pressure at input 1 is Check the maximum threshold YES
higher than the maximum pressure 1 alarm value and the
threshold value set process conditions
158 MIN P1 The pressure at input 1 is Check the minimum threshold YES
lower than the minimum pressure 1 alarm value and the
threshold value set process conditions
160 MAX P2 The pressure at input 2 is Check the maximum threshold YES
higher than the maximum pressure 2 alarm value and the
threshold value set process conditions
161 MIN P2 The pressure at input 2 is Check the minimum threshold YES
lower than the minimum pressure 2 alarm value and the
threshold value set process conditions
163 MAX DP The pressure difference Check the maximum threshold YES
(delta) P1-P2 is higher than pressure difference (delta) alarm
the maximum threshold set value and the process conditions
164 MIN DP The pressure difference Check the minimum threshold YES
(delta) P1-P2 is lower than the pressure difference (delta) alarm
minimum threshold set value and the process conditions
167 MAX TEMP The external temperature is Check the maximum threshold YES
higher than the maximum temperature alarm value and the
threshold value set process conditions
168 MIN TEMP The external temperature Check the minimum threshold YES
is lower than the minimum temperature alarm value and the
threshold value set process conditions
171 P.EMPTY The system detected an Check the empty pipe settings YES
empty pipe alarm condition and the process conditions
*Not available at this time.
ALARM
VIA
CODE MESSAGE CAUSE ACTION SMS *
193 CONFIG.ENTERED The system detects an Check the events log and do the YES
access to the configuration appropriate action depending on
parameters your data protection policy
194 CLOCK S.FAIL The clock synchronization Check the server configuration, YES
with the remote server failed the GPRS network conditions and
antenna signal
195 POWER FAILURE The system experienced a Check the status of the batteries YES
power failure (loss of power) and all their connections. THIS
MESSAGE MAY APPEAR WHEN
THE SYSTEM IS SWITCHED OFF
WITHOUT PRIOR PUTTING IT IN
STAND-BY MODE
206 F.SENSOR ERROR The system detected one or Check the error code in the YES
more errors in the flow sensor events log
207 TEMP.>FS The external temperature is Check the maximum full scale set YES
higher than the full scale set and the process conditions
208 PULS.2>F.MAX The pulse frequency at Reduce the pulse duration if the YES
output 2 is too high connected counter allow this or
increase the pulse unit value
209 PRESS.2>FS The Pressure at input 2 is Check the maximum full scale set YES
higher than the full scale set and the process conditions
210 EL.SIG.ERROR The system detected an error Check the flow sensor cables, the YES
condition on the measuring electrodes surface, the grounding
electrodes and the process condition
211 EXCIT.ERROR The system detected an error Check the flow sensor cables, the YES
in the coils excitation circuit coils insulation and resistance
212 SD MEMORY FULL The SD card memory is full Change the SD card memory or YES
(no more space for new data) erase all the unwanted data
215 POWER SUPPLY OFF The power coming from the Check the power supply source YES
universal power supply went and the relative cables
off
216 SD MEMORY ERROR The SD card installed is Replace the SD memory, format it YES
missing, not valid, not or check if it is properly inserted
formatted or incompatible
with the system
ELECTRICAL CHARACTERISTICS:
Power supply version Power supply Power supply frequency Max power
12V - 60V * //
AU 4W
100V - 240V~* 44-66Hz
LITHIUM BATTERY NOT
3.6v-19aH // 30mW
RECHARGEABLE
* Voltage must not exceed ±10% of the above limits.
Mod
el
Seria #: 88
00
Met l #: E12- 03xxx
er #: 34
MI1 567
2-34
56
3255
W.
PH (95 STET
1) 652 SON
-6811 AVE,
• htt HEME
p://ww T, CA
w.m 92
ccrom 545
eter.coUSA
m
R
E C
T S
N E
E
U.S. Standard
in3 Cubic Inches
Gal U.S. Gallons
IGL Imperial Gallons
ft3 Cubic Feet
bbl Standard Barrels
BBL Oil Barrels
KGL Kilo Gallons
IKG Imperial Kilo Gallons
Aft Acre Feet
MGL Mega Gallons
IMG Imperial Mega Gallons
hf 3
Hundreds of cubic feet
kf 3
Thousands of cubic feet
ttG Tens of thousands of gallons
Metric
ml Milliliters
cm3 Cubic Centimeters
l Liters
dm3 Cubic Decimeter
dal Decaliter
hl Hectoliter
m3 Cubic Meter
Ml Megaliter
Time
s Seconds
m Minutes
h Hours
d Days
Fraction Decimal
1/8 .125
1/4 .25
3/8 .375
1/2 .5
5/8 .625
3/4 .75
7/8 .875
Table of Conversions
Multiply By To Get
Centimeters 0.3937 Inches
Centimeters 0.03281 Feet
Inches 25.4 Millimeters
Feet 30.48 Centimeters
Square Feet 144.0 Square Inches
Square Inches 0.006944 Square Feet
Cubic Inches 0.0005787 Cubic Feet
Cubic Feet 7.481 Gallons
Cubic Feet 1728.0 Cubic Inches
Cubic Feet 0.02832 Cubic Meters
Cubic Feet 28.32 Liters
Cubic Meters 35.31 Cubic Feet
Cubic Meters 264.2 Gallons
US Gallons 3.785 Liters
US Gallons 0.1337 Cubic Feet
US Gallons 0.003785 Cubic Meters
US Gallons .8326748 Imperial Gallons
Liters 0.2642 Gallons
˚F = ( ˚C x 9/5 ) + 32 ˚C ( ˚F - 32 ) x 5/9
Propeller Flowmeters
Magnetic Flowmeters
DURA MAG ™
FlowConnect ™
Copyright © 2001-2019 McCrometer, Inc. All printed material should not be changed or altered without permission of McCrometer. Any published pricing,
technical data, and instructions are subject to change without notice. Contact your McCrometer representative for current pricing, technical data, and instructions.