33 4001 Astm C1577-14
33 4001 Astm C1577-14
33 4001 Astm C1577-14
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
City of Buda
Municipal Library and City Hall/Public Service Building ASTM C1577 - 14
Page Proj. 115036 50% DD - May 23, 2016 33 4001 - 1
C1577 − 14
TABLE 1 Design Requirements for Precast Concrete Box Sections Under Earth, Dead and HL-93 Live Load Conditions
NOTE 1—Design earth loads and reinforcement areas are based on the weight of a column of earth over the width of the box section multiplied by a
soil structure interaction factor as defined in Appendix X1.
NOTE 2—Concrete design strength 5000 psi.
NOTE 3—Steel areas are based on an HL-93 live load without the lane load as permitted by AASHTO, using either the design truck or the design tandem
and taking the controlling case.
NOTE 4—The design earth cover indicated is the height of fill above the top of the box section. Design requirements are based on the material and soil
properties, loading data, and typical section as included in Appendix X1. For alternative or special designs, see 7.2.
NOTE 5—Design steel area in square inches per linear foot of box section at those locations which are indicated on the typical section shown in Fig. 1.
NOTE 6—The top section designation, for example, 3 ft by 2 ft by 4 in. indicates (interior horizontal span in feet) by (interior vertical rise in feet) by
(wall and slab thickness in inches).
NOTE 7—In accordance with the acceptance criteria in 7.2, the manufacturer is not prohibited from interpolating steel area requirements or submitting
independent designs for fill heights between noted increments.
NOTE 8—The “M” dimension given in the tables is the required distance that As1 shall be extended into the top and bottom slabs if it is used as
reinforcement for the negative moment in these areas. This distance is based on the location where the negative moment in the slab becomes zero, plus
an additional development length. Because the live load can be applied at any location along the top slab as the truck drives over it, it is possible for
the “M” dimension to exceed one-half the length of the slab.
NOTE 9—(Advisory)—The reinforcing areas are based on 4 inch circumferential wire spacing. Under design conditions where crack control governs,
an analysis following the design criteria in Table X1.1 with closer steel spacing may result in a reduction in steel area over those in the table.
3 ft by 2 ft by 4 in.
Design Circumferential Reinforcement Areas, in.2/ft
Earth As1 As2 As3 As4 As5 As6 As7 As8 “M,” in.
Cover, ft
0<2A 0.17 0.25 0.16 0.10 0.17 0.17 0.17 0.14
2<3 0.13 0.19 0.18 0.10 31
3-5 0.10 0.11 0.12 0.10 31
10 0.10 0.10 0.10 0.10 31
15 0.10 0.13 0.13 0.10 31
20 0.11 0.17 0.17 0.10 31
25 0.14 0.21 0.21 0.10 31
30 0.17 0.25 0.25 0.10 31
35 0.20 0.29 0.30 0.10 31
A
Top slab 7 in., bottom slab 6 in.
3 ft by 3 ft by 4 in.
Design Circumferential Reinforcement Areas, in.2/ft
Earth As1 As2 As3 As4 As5 As6 As7 As8 “M,” in.
Cover, ft
0<2A 0.17 0.27 0.17 0.10 0.17 0.17 0.17 0.14
2<3 0.10 0.22 0.21 0.10 31
3-5 0.10 0.14 0.14 0.10 31
10 0.10 0.11 0.11 0.10 31
15 0.10 0.14 0.15 0.10 31
20 0.10 0.18 0.19 0.10 31
25 0.10 0.23 0.23 0.10 31
30 0.12 0.27 0.28 0.10 31
35 0.14 0.32 0.32 0.10 31
A
Top slab 7 in., bottom slab 6 in.
4 ft by 2 ft by 5 in.
Design Circumferential Reinforcement Areas, in.2/ft
Earth As1 As2 As3 As4 As5 As6 As7 As8 “M,” in.
Cover, ft
0<2A 0.18 0.27 0.15 0.12 0.18 0.18 0.18 0.14
2<3 0.18 0.19 0.17 0.12 38
3-5 0.13 0.13 0.13 0.12 38
10 0.12 0.12 0.12 0.12 38
15 0.14 0.16 0.16 0.12 38
20 0.18 0.20 0.21 0.12 38
25 0.23 0.25 0.25 0.12 38
30 0.28 0.30 0.30 0.12 38
A
Top slab 7.5 in., bottom slab 6 in.
4 ft by 3 ft by 5 in.
Design Circumferential Reinforcement Areas, in.2/ft
Earth As1 As2 As3 As4 As5 As6 As7 As8 “M,” in.
Cover, ft
0<2A 0.18 0.31 0.18 0.12 0.18 0.18 0.18 0.14
2<3 0.15 0.23 0.20 0.12 38
3-5 0.12 0.16 0.16 0.12 38
10 0.12 0.14 0.14 0.12 38
15 0.12 0.18 0.18 0.12 38
20 0.14 0.23 0.24 0.12 38
25 0.17 0.29 0.29 0.12 38
30 0.21 0.35 0.35 0.12 38
A
Top slab 7.5 in., bottom slab 6 in.
4 ft by 4 ft by 5 in.
Design Circumferential Reinforcement Areas, in.2/ft
Earth As1 As2 As3 As4 As5 As6 As7 As8 “M,” in.
Cover, ft
0<2A 0.18 0.33 0.20 0.12 0.18 0.18 0.18 0.14
2<3 0.12 0.26 0.23 0.12 38
3-5 0.12 0.18 0.18 0.12 38
10 0.12 0.15 0.15 0.12 38
15 0.12 0.19 0.20 0.12 38
20 0.12 0.25 0.25 0.12 38
25 0.14 0.31 0.31 0.12 38
30 0.17 0.37 0.37 0.12 38
A
Top slab 7.5 in., bottom slab 6 in.
5 ft by 2 ft by 6 in.
Design Circumferential Reinforcement Areas, in.2/ft
Earth As1 As2 As3 As4 As5 As6 As7 As8 “M,” in.
Cover, ft
0<2A 0.19 0.27 0.18 0.14 0.19 0.19 0.19 0.17
2<3 0.22 0.20 0.16 0.14 44
3-5 0.16 0.14 0.14 0.14 44
10 0.15 0.14 0.14 0.14 36
15 0.20 0.18 0.18 0.14 36
20 0.26 0.23 0.24 0.14 36
25 0.33 0.29 0.29 0.14 36
30 0.39 0.34 0.35 0.14 36
A
Top slab 8 in., bottom slab 7 in.
5 ft by 3 ft by 6 in.
Design Circumferential Reinforcement Areas, in.2/ft
Earth As1 As2 As3 As4 As5 As6 As7 As8 “M,” in.
Cover, ft
0<2A 0.19 0.31 0.21 0.14 0.19 0.19 0.19 0.17
2<3 0.18 0.24 0.19 0.14 45
3-5 0.14 0.17 0.16 0.14 36
10 0.14 0.16 0.17 0.14 36
15 0.16 0.21 0.22 0.14 35
20 0.21 0.27 0.28 0.14 35
25 0.26 0.34 0.34 0.14 35
30 0.31 0.41 0.41 0.14 35
A
Top slab 8 in., bottom slab 7 in.
5 ft by 4 ft by 6 in.
Design Circumferential Reinforcement Areas, in.2/ft
Earth As1 As2 As3 As4 As5 As6 As7 As8 “M,” in.
Cover, ft
0<2A 0.19 0.33 0.24 0.14 0.19 0.19 0.19 0.17
2<3 0.16 0.27 0.22 0.14 45
3-5 0.14 0.19 0.18 0.14 45
10 0.14 0.18 0.18 0.14 36
15 0.14 0.23 0.24 0.14 35
20 0.17 0.30 0.31 0.14 35
25 0.21 0.37 0.38 0.14 35
30 0.25 0.44 0.45 0.14 35
A
Top slab 8 in., bottom slab 7 in.
5 ft by 5 ft by 6 in.
Design Circumferential Reinforcement Areas, in.2/ft
Earth As1 As2 As3 As4 As5 As6 As7 As8 “M,” in.
Cover, ft
0<2A 0.19 0.35 0.26 0.14 0.19 0.19 0.19 0.17
2<3 0.14 0.29 0.24 0.14 45
3-5 0.14 0.21 0.20 0.14 45
10 0.14 0.19 0.20 0.14 45
15 0.14 0.24 0.25 0.14 36
20 0.15 0.31 0.32 0.14 35
25 0.18 0.38 0.39 0.14 35
30 0.21 0.46 0.47 0.14 35
A
Top slab 8 in., bottom slab 7 in.
6 ft by 2 ft by 7in.
Design Circumferential Reinforcement Areas, in.2/ft
Earth As1 As2 As3 As4 As5 As6 As7 As8 “M,” in.
Cover, ft
0<2A 0.23 0.27 0.19 0.17 0.19 0.19 0.19 0.17
2<3 0.25 0.21 0.17 0.17 43
3-5 0.20 0.17 0.17 0.17 43
10 0.20 0.17 0.17 0.17 39
15 0.26 0.20 0.20 0.17 39
20 0.34 0.26 0.26 0.17 39
25 0.43 0.32 0.32 0.17 39
30 0.52 0.38 0.39 0.17 39
A
Top slab 8 in.
6 ft by 3 ft by 7 in.
Design Circumferential Reinforcement Areas, in.2/ft
Earth As1 As2 As3 As4 As5 As6 As7 As8 “M,” in.
Cover, ft
0<2A 0.20 0.31 0.22 0.17 0.19 0.19 0.19 0.17
2<3 0.21 0.24 0.19 0.17 43
3-5 0.17 0.18 0.17 0.17 39
10 0.17 0.18 0.19 0.17 39
15 0.22 0.24 0.24 0.17 38
20 0.28 0.31 0.31 0.17 38
25 0.35 0.38 0.39 0.17 38
30 0.42 0.46 0.46 0.17 38
A
Top slab 8 in.
6 ft by 4 ft by 7 in.
Design Circumferential Reinforcement Areas, in.2/ft
Earth As1 As2 As3 As4 As5 As6 As7 As8 “M,” in.
Cover, ft
0<2A 0.19 0.34 0.25 0.17 0.19 0.19 0.19 0.17
2<3 0.19 0.27 0.21 0.17 43
3-5 0.17 0.21 0.19 0.17 39
10 0.17 0.20 0.21 0.17 39
15 0.18 0.27 0.27 0.17 38
20 0.24 0.34 0.35 0.17 38
25 0.29 0.43 0.42 0.17 38
30 0.35 0.51 0.52 0.17 38
A
Top slab 8 in.
6 ft by 5 ft by 7 in.
Design Circumferential Reinforcement Areas, in.2/ft
Earth As1 As2 As3 As4 As5 As6 As7 As8 “M,” in.
Cover, ft
0<2A 0.19 0.37 0.28 0.17 0.19 0.19 0.19 0.17
2<3 0.17 0.30 0.24 0.17 43
3-5 0.17 0.23 0.21 0.17 43
10 0.17 0.22 0.23 0.17 39
15 0.17 0.28 0.29 0.17 38
20 0.20 0.37 0.38 0.17 38
25 0.25 0.45 0.46 0.17 38
30 0.30 0.54 0.55 0.17 38
A
Top slab 8 in.
6 ft by 6 ft by 7 in.
Design Circumferential Reinforcement Areas, in.2/ft
Earth As1 As2 As3 As4 As5 As6 As7 As8 “M,” in.
Cover, ft
0<2A 0.19 0.38 0.30 0.17 0.19 0.19 0.19 0.17
2<3 0.17 0.32 0.26 0.17 52
3-5 0.17 0.24 0.22 0.17 52
10 0.17 0.23 0.24 0.17 43
City of Buda Copyright by ASTM Int'l (all rights reserved);
Municipal Library and City Hall/Public Service Building ASTM C1577 - 14
Page Proj. 115036 50% DD - May 23, 2016 33 4001 - 4
C1577 − 14
9 ft by 2 ft by 9 in.
Design Circumferential Reinforcement Areas, in.2/ft
Earth As1 As2 As3 As4 As5 As6 As7 As8 “M,” in.
Cover, ft
0<2 0.38 0.30 0.22 0.22 0.22 0.22 0.22 0.22
2<3 0.44 0.26 0.22 0.22 71
3-5 0.35 0.22 0.22 0.22 59
10 0.39 0.22 0.23 0.22 54
15 0.52 0.30 0.30 0.22 54
20 0.68 0.38 0.39 0.22 54
25 0.86 0.47 0.48 0.22 54
9 ft by 3 ft by 9 in.
Design Circumferential Reinforcement Areas, in.2/ft
Earth As1 As2 As3 As4 As5 As6 As7 As8 “M,” in.
Cover, ft
0<2 0.34 0.33 0.24 0.22 0.22 0.22 0.22 0.22
2<3 0.39 0.30 0.27 0.22 59
3-5 0.31 0.24 0.23 0.22 54
10 0.34 0.27 0.27 0.22 49
15 0.45 0.35 0.36 0.22 49
20 0.59 0.46 0.46 0.22 49
25 0.74 0.56 0.57 0.22 49
9 ft by 4 ft by 9 in.
Design Circumferential Reinforcement Areas, in.2/ft
Earth As1 As2 As3 As4 As5 As6 As7 As8 “M,” in.
Cover, ft
0<2 0.30 0.36 0.28 0.22 0.22 0.22 0.22 0.22
2<3 0.35 0.34 0.31 0.22 54
3-5 0.28 0.27 0.27 0.22 50
10 0.31 0.30 0.31 0.22 49
15 0.40 0.40 0.41 0.22 49
20 0.52 0.51 0.52 0.22 44
25 0.65 0.64 0.65 0.22 44
9 ft by 5 ft by 9 in.
Design Circumferential Reinforcement Areas, in.2/ft
Earth As1 As2 As3 As4 As5 As6 As7 As8 “M,” in.
Cover, ft
0<2 0.28 0.38 0.31 0.22 0.22 0.22 0.22 0.22
2<3 0.32 0.38 0.34 0.22 54
3-5 0.25 0.30 0.30 0.22 49
10 0.28 0.33 0.34 0.22 49
15 0.36 0.43 0.45 0.22 44
20 0.47 0.56 0.57 0.22 44
25 0.58 0.69 0.71 0.22 44
9 ft by 6 ft by 9 in.
Design Circumferential Reinforcement Areas, in.2/ft
Earth As1 As2 As3 As4 As5 As6 As7 As8 “M,” in.
Cover, ft
0<2 0.25 0.40 0.34 0.22 0.22 0.22 0.22 0.22
2<3 0.29 0.41 0.38 0.22 54
3-5 0.23 0.33 0.33 0.22 49
10 0.26 0.35 0.37 0.22 49
15 0.33 0.46 0.48 0.22 44
20 0.42 0.60 0.61 0.22 44
25 0.52 0.74 0.75 0.22 44
9 ft by 7 ft by 9 in.
Design Circumferential Reinforcement Areas, in.2/ft
Earth As1 As2 As3 As4 As5 As6 As7 As8 “M,” in.
Cover, ft
0<2 0.23 0.42 0.36 0.22 0.22 0.22 0.22 0.22
2<3 0.26 0.44 0.41 0.22 59
3-5 0.22 0.35 0.35 0.22 54
10 0.24 0.37 0.39 0.22 49
15 0.31 0.48 0.51 0.22 44
20 0.39 0.62 0.65 0.22 44
9 ft by 8 ft by 9 in.
Design Circumferential Reinforcement Areas, in.2/ft
Earth As1 As2 As3 As4 As5 As6 As7 As8 “M,” in.
Cover, ft
0<2 0.22 0.43 0.39 0.22 0.22 0.22 0.22 0.22
2<3 0.24 0.46 0.43 0.22 59
3-5 0.22 0.37 0.38 0.22 59
10 0.22 0.39 0.41 0.22 54
15 0.29 0.50 0.53 0.22 44
20 0.36 0.64 0.67 0.22 44
Copyright by ASTM Int'l (all rights reserved);
City of Buda
Municipal Library and City Hall/Public Service Building ASTM C1577 - 14
Page Proj. 115036 50% DD - May 23, 2016 33 4001 - 7
C1577 − 14
9 ft by 9 ft by 9 in.
Design Circumferential Reinforcement Areas, in.2/ft
Earth As1 As2 As3 As4 As5 As6 As7 As8 “M,” in.
Cover, ft
0<2 0.22 0.44 0.42 0.22 0.22 0.22 0.22 0.22
2<3 0.23 0.49 0.46 0.22 72
3-5 0.22 0.39 0.40 0.22 72
10 0.22 0.40 0.43 0.22 59
15 0.27 0.51 0.55 0.22 49
20 0.34 0.66 0.69 0.22 49
10 ft by 2 ft by 10 in.
Design Circumferential Reinforcement Areas, in.2/ft
Earth As1 As2 As3 As4 As5 As6 As7 As8 “M,” in.
Cover, ft
0<2 0.42 0.28 0.24 0.24 0.24 0.24 0.24 0.24
2<3 0.48 0.26 0.24 0.24 70
3-5 0.39 0.24 0.24 0.24 64
10 0.44 0.24 0.24 0.24 64
15 0.59 0.31 0.32 0.24 58
20 0.77 0.40 0.41 0.24 58
25 0.97 0.50 0.50 0.24 58
10 ft by 3 ft by 10 in.
Design Circumferential Reinforcement Areas, in.2/ft
Earth As1 As2 As3 As4 As5 As6 As7 As8 “M,” in.
Cover, ft
0<2 0.37 0.31 0.24 0.24 0.24 0.24 0.24 0.24
2<3 0.42 0.31 0.27 0.24 64
3-5 0.35 0.25 0.24 0.24 58
10 0.39 0.28 0.29 0.24 58
15 0.52 0.37 0.38 0.24 52
20 0.68 0.48 0.49 0.24 52
25 0.85 0.59 0.60 0.24 52
10 ft by 4 ft by 10 in.
Design Circumferential Reinforcement Areas, in.2/ft
Earth As1 As2 As3 As4 As5 As6 As7 As8 “M,” in.
Cover, ft
0<2 0.33 0.34 0.27 0.24 0.24 0.24 0.24 0.24
2<3 0.38 0.35 0.30 0.24 58
3-5 0.31 0.28 0.27 0.24 53
10 0.36 0.32 0.33 0.24 52
15 0.47 0.42 0.43 0.24 52
20 0.61 0.54 0.55 0.24 52
25 0.75 0.67 0.68 0.24 52
10 ft by 5 ft by 10 in.
Design Circumferential Reinforcement Areas, in.2/ft
Earth As1 As2 As3 As4 As5 As6 As7 As8 “M,” in.
Cover, ft
0<2 0.30 0.36 0.30 0.24 0.24 0.24 0.24 0.24
2<3 0.35 0.39 0.34 0.24 58
3-5 0.28 0.31 0.30 0.24 53
10 0.33 0.35 0.36 0.24 52
15 0.42 0.46 0.47 0.24 47
20 0.55 0.59 0.61 0.24 47
25 0.68 0.73 0.75 0.24 47
10 ft by 6 ft by 10 in.
Design Circumferential Reinforcement Areas, in.2/ft
Earth As1 As2 As3 As4 As5 As6 As7 As8 “M,” in.
Cover, ft
0<2 0.28 0.38 0.33 0.24 0.24 0.24 0.24 0.24
2<3 0.32 0.42 0.37 0.24 58
3-5 0.26 0.34 0.33 0.24 52
10 0.30 0.38 0.39 0.24 52
15 0.39 0.49 0.51 0.24 47
20 0.50 0.63 0.65 0.24 47
25 0.61 0.78 0.80 0.24 47
10 ft by 7 ft by 10 in.
Design Circumferential Reinforcement Areas, in.2/ft
Earth As1 As2 As3 As4 As5 As6 As7 As8 “M,” in.
Cover, ft
0<2 0.25 0.40 0.36 0.24 0.24 0.24 0.24 0.24
2<3 0.30 0.45 0.40 0.24 58
3-5 0.24 0.36 0.35 0.24 58
10 0.28 0.40 0.42 0.24 52
15 0.36 0.52 0.54 0.24 47
20 0.46 0.67 0.69 0.24 47
Copyright by ASTM Int'l (all rights reserved);
City of Buda
Municipal Library and City Hall/Public Service Building ASTM C1577 - 14
Page Proj. 115036 50% DD - May 23, 2016 33 4001 - 8
C1577 − 14
11 ft by 8 ft by 11 in.
Design Circumferential Reinforcement Areas, in.2/ft
Earth As1 As2 As3 As4 As5 As6 As7 As8 “M,” in.
Cover, ft
0<2 0.26 0.40 0.38 0.26 0.26 0.26 0.26 0.26
2<3 0.30 0.48 0.42 0.26 62
3-5 0.26 0.40 0.38 0.26 62
10 0.30 0.44 0.47 0.26 55
15 0.39 0.58 0.60 0.26 50
20 0.49 0.74 0.77 0.26 50
25 0.61 0.91 0.94 0.26 50
11 ft by 10 ft by 11 in.
Design Circumferential Reinforcement Areas, in.2/ft
Earth As1 As2 As3 As4 As5 As6 As7 As8 “M,” in.
Cover, ft
0<2 0.26 0.45 0.43 0.26 0.26 0.26 0.26 0.26
2<3 0.27 0.53 0.48 0.26 75
3-5 0.26 0.44 0.43 0.26 69
10 0.28 0.48 0.52 0.26 62
15 0.35 0.61 0.65 0.26 55
20 0.44 0.78 0.83 0.26 50
11 ft by 11 ft by 11 in.
Design Circumferential Reinforcement Areas, in.2/ft
Earth As1 As2 As3 As4 As5 As6 As7 As8 “M,” in.
Cover, ft
0<2 0.26 0.47 0.46 0.26 0.26 0.26 0.26 0.26
2<3 0.26 0.55 0.51 0.26 86
3-5 0.26 0.46 0.45 0.26 75
10 0.27 0.49 0.54 0.26 69
15 0.34 0.63 0.68 0.26 55
20 0.42 0.80 0.85 0.26 55
12 ft by 2 ft by 12 in.
Design Circumferential Reinforcement Areas, in.2/ft
Earth As1 As2 As3 As4 As5 As6 As7 As8 “M,” in.
Cover, ft
0<2 0.47 0.29 0.29 0.29 0.29 0.29 0.29 0.29
2<3 0.55 0.29 0.29 0.29 80
3-5 0.46 0.29 0.29 0.29 73
10 0.54 0.29 0.29 0.29 73
15 0.73 0.34 0.35 0.29 73
20 0.96 0.44 0.45 0.29 73
25 1.20 0.54 0.55 0.29 66
12 ft by 3 ft by 12 in.
Design Circumferential Reinforcement Areas, in.2/ft
Earth As1 As2 As3 As4 As5 As6 As7 As8 “M,” in.
Cover, ft
0<2 0.42 0.29 0.29 0.29 0.29 0.29 0.29 0.29
2<3 0.49 0.33 0.29 0.29 73
3-5 0.41 0.29 0.29 0.29 73
10 0.49 0.30 0.31 0.29 66
15 0.66 0.41 0.42 0.29 66
20 0.86 0.53 0.54 0.29 66
25 1.07 0.65 0.66 0.29 66
12 ft by 4 ft by 12 in.
Design Circumferential Reinforcement Areas, in.2/ft
Earth As1 As2 As3 As4 As5 As6 As7 As8 “M,” in.
Cover, ft
0<2 0.38 0.31 0.29 0.29 0.29 0.29 0.29 0.29
2<3 0.44 0.37 0.30 0.29 73
3–5 0.37 0.30 0.29 0.29 66
10 0.44 0.34 0.35 0.29 66
15 0.60 0.46 0.48 0.29 59
20 0.78 0.60 0.61 0.29 59
25 0.97 0.74 0.75 0.29 59
12 ft by 6 ft by 12 in.
Design Circumferential Reinforcement Areas, in.2/ft
Earth As1 As2 As3 As4 As5 As6 As7 As8 “M,” in.
Cover, ft
0<2 0.32 0.36 0.32 0.29 0.29 0.29 0.29 0.29
2<3 0.38 0.43 0.36 0.29 66
3-5 0.32 0.36 0.33 0.29 59
10 0.38 0.41 0.42 0.29 59
15 0.51 0.55 0.57 0.29 53
20 0.65 0.71 0.72 0.29 53
25 0.81 0.87 0.89 0.29 53
Copyright by ASTM Int'l (all rights reserved);
City of Buda
Municipal Library and City Hall/Public Service Building ASTM C1577 - 14
Page Proj. 115036 50% DD - May 23, 2016 33 4001 - 10
C1577 − 14
12 ft by 8 ft by 12 in.
Design Circumferential Reinforcement Areas, in.2/ft
Earth As1 As2 As3 As4 As5 As6 As7 As8 “M,” in.
Cover, ft
0<2 0.29 0.41 0.38 0.29 0.29 0.29 0.29 0.29
2<3 0.33 0.49 0.42 0.29 66
3-5 0.29 0.41 0.38 0.29 59
10 0.34 0.46 0.48 0.29 59
15 0.44 0.61 0.64 0.29 53
20 0.57 0.78 0.81 0.29 53
25 0.69 0.96 0.99 0.29 53
12 ft by 10 ft by 12 in.
Design Circumferential Reinforcement Areas, in.2/ft
Earth As1 As2 As3 As4 As5 As6 As7 As8 “M,” in.
Cover, ft
0<2 0.29 0.45 0.43 0.29 0.29 0.29 0.29 0.29
2<3 0.29 0.54 0.48 0.29 73
3-5 0.29 0.45 0.43 0.29 66
10 0.31 0.49 0.53 0.29 59
15 0.40 0.65 0.70 0.29 53
20 0.51 0.84 0.88 0.29 53
25 0.62 1.03 1.07 0.29 53
12 ft by 12 ft by 12 in.
Design Circumferential Reinforcement Areas, in.2/ft
Earth As1 As2 As3 As4 As5 As6 As7 As8 “M,” in.
Cover, ft
0<2 0.29 0.49 0.48 0.33 0.29 0.29 0.29 0.29
2<3 0.29 0.59 0.53 0.29 93
3-5 0.29 0.49 0.48 0.29 80
10 0.29 0.52 0.58 0.29 73
15 0.37 0.69 0.74 0.29 59
20 0.46 0.87 0.93 0.29 59
the ASTM and AASHTO Material Standards for precast box culverts have
all utilized 1 in. of concrete cover over the reinforcement. Boxes
manufactured in accordance with the ASTM and AASHTO Material
Standards have performed well over the years, with no indication of FIG. 6 Detail Option
distress resulting from the 1 in. concrete cover.
7.4 Laps, Welds, and Spacing—Splices in the circumferen- connected, welded splices or lapped splices shall be used in the
tial reinforcement shall be made by lapping. The overlap connection. When used, As7 and As8 shall be lapped with As1 as
measured between the outermost longitudinal wires of each shown in Fig. 5, Fig. 6, or Fig. 8 and are not prohibited from
reinforcement sheet shall not be less than the space containing being connected by welding. If welds are made to circumfer-
two longitudinal wires of each mesh plus 2 in., but not less than ential reinforcement, they shall be made only to selected
10 in. If As1 is extended to the middle of either slab and circumferential wires that are not less than 18 in. apart along
City of Buda Copyright by ASTM Int'l (all rights reserved);
Municipal Library and City Hall/Public Service Building ASTM C1577 - 14
Page Proj. 115036 50% DD - May 23, 2016 33 4001 - 13
C1577 − 14
8.2 Joints shall conform to the requirements of either
Specification C990 or C1677. For joints conforming to Speci-
fication C1677, the elastomeric (gasket) material shall conform
to Specification C1619 Class C requirements. Gaskets which
require oil resistant properties shall meet Class D requirements.
8.3 Outer cage circumferential reinforcement as shown in
Figs. 1 and 2 shall be placed in the top and bottom slabs at the
groove portion of the joint when As1 is not continuous over the
span. The minimum area of such reinforcement in square
inches per linear foot of box section length shall be the same as
the areas specified for As4 in Table 1.
9. Manufacture
9.1 Mixture—The aggregates shall be sized, graded,
proportioned, and mixed with such proportions of cementitious
FIG. 7 Alternate Detail (see Fig. 3) materials and water as will produce a thoroughly-mixed
concrete of such quality that the box section will conform to
the test and design requirements of this specification. All
concrete shall have a water-cementitious materials ratio not
exceeding 0.53 by weight. Cementitious materials shall be as
specified in 6.2 and shall be added to the mix in a proportion
not less than 470 lb/yd3 unless mix designs with a lower
cementitious materials content demonstrate that the quality and
performance of the box section meet the requirements of this
specification.
9.2 Curing—The box sections shall be cured for a sufficient
length of time so that the concrete will develop the specified
compressive strength by the time of delivery. Any one of the
following methods of curing or combinations thereof shall be
used:
9.2.1 Steam Curing—The box sections shall be low
FIG. 8 Alternate Detail (see Fig. 5) pressure, steam-cured by a system that will maintain a moist
atmosphere.
the longitudinal axis of the box section as shown in Fig. 9. 9.2.2 Water Curing—The box sections shall be water-cured
Also, when spacers are welded to circumferential wires, they by any method that will keep the sections moist.
shall be welded only to these selected circumferential wires. 9.2.3 Membrane Curing—A sealing membrane conforming
There shall be no welding to other circumferential wires, to the requirements of Specification C309 shall be applied and
except As4 is not prohibited from being lapped and welded at shall be left intact until the required concrete compressive
any location or connected by welding at the corners to As2 and strength is attained. The concrete temperature at the time of
As3. No welds shall be made to As2 or As3 circumferential wires application shall be within 10°F of the atmospheric tempera-
in the middle third of the span as shown in Fig. 9. When ture. All surfaces shall be kept moist prior to the application of
distribution reinforcement is to be fastened to a cage by the compounds and shall be damp when the compound is
welding, it shall be welded only to longitudinal wires and only applied.
within 18 in. of the end of the box section. The spacing center 9.3 Forms—The forms used in manufacture shall be suffi-
to center of the circumferential wires shall not be less than 2 in. ciently rigid and accurate to maintain the box section dimen-
nor more than 4 in. The spacing center to center of the sions within the permissible variations given in Section 11. All
longitudinal wires shall not be more than 8 in. casting surfaces shall be of smooth nonporous material.
NOTE 5—(Advisory)–The AASHTO LRFD Bridge Design Specifica- 9.4 Handling—Handling devices or holes are not prohibited
tions should be consulted for weld requirements not directly addressed in
this standard.
in each box section for the purpose of handling and laying.
10.2.1 Cylinders shall be prepared, cured, and tested in strength equal to or greater than 85 % of the required strength,
accordance with Section 11 of Test Methods C497. Cylinders the remainder of the group is acceptable. If the compressive
shall be exposed to the same curing conditions as the manu- strength of either of the two cores tested is less than 85 % of
factured box sections and shall remain with the sections until the required strength of the concrete, the remainder of the
tested. group of box sections shall be rejected, or, at the option of the
10.2.2 Prepare not less than three test cylinders from each manufacturer, each box section of the remainder of the group
concrete mix used within a group (one day’s production) of shall be cored and accepted individually, and any of these box
box sections. sections that have core strengths less than 85 % of the required
10.2.3 Acceptability on the Basis of Cylinder Test Results: strength of the concrete shall be rejected.
10.2.3.1 When the average compressive strength of all NOTE 6—(Advisory)—The percentage shown for acceptance of core
cylinders tested is equal to or greater than the design concrete tests are in accordance with ACI 318 which states that, “To expect core
tests to be equal to f'c is not realistic, since differences in the size of
strength, not more than 10 % of the cylinders tested have a specimens, conditions of obtaining samples, and procedures for curing do
compressive strength less than the design concrete strength, not permit equal values to be obtained”. The variations of the specimens
and no cylinder tested has a compressive strength less than such as length to diameter ratio, drilling direction and process, aggregate
80 % of the design concrete strength, the lot shall be accepted. size and sample preparation may all have an effect on the test results.
10.2.3.2 Box sections that fail to meet the strength require- Embedded steel reinforcement affects the test results because of the loss of
concrete continuity.
ments under 10.2 shall not be retested under 10.3 without the
approval of the purchaser. 10.4 Plugging Core Holes—The core holes shall be plugged
10.2.3.3 When the compressive strength of the cylinders is and sealed by the manufacturer in a manner such that the box
unavailable, the acceptability of the lot shall be determined in section will meet all of the test requirements of this specifica-
accordance with the provisions of 10.3. tion. Box sections so sealed shall be considered as satisfactory
for use.
10.3 Compression Testing of Cores:
10.3.1 Cores shall be obtained, prepared, and tested for 10.5 Test Equipment—Every manufacturer furnishing box
compressive strength in accordance with the provisions of Test sections under this specification shall furnish all facilities and
Methods C497. personnel necessary to carry out the tests required.
10.3.2 Three cores shall be taken from three sections (one
core from each) selected at random from each group of 15 box 11. Permissible Variations
sections or fraction thereof, of a single size from each 11.1 Internal Dimensions—The internal dimensions shall
continuous production run. not vary more than 1 % from the design dimensions. The
10.3.3 Acceptability by Core Tests: haunch dimensions shall not vary more than 1⁄4 in. from the
10.3.3.1 Concrete represented by these three core tests shall design dimensions.
be considered acceptable if the average of the three core
strengths is equal to or greater than 85 % of the required 11.2 Slab and Wall Thickness—The slab and wall thickness
compressive strength of the concrete with no one core less than shall not be less than that shown in the design by more than
75 % of the required compressive strength. 5 % or 3⁄16 in., whichever is greater. A thickness more than that
10.3.3.2 If the compressive strength of the three cores does required in the design shall not be a cause for rejection.
not meet the requirements of 10.3.3.1, the sections from which 11.3 Length of Opposite Surfaces—Variations in laying
the cores were taken shall be rejected. Two box sections from lengths of two opposite surfaces of the box section shall not be
the remainder of the group shall be selected at random and one more than 1⁄8 in./ft of internal span, with a maximum of 5⁄8 in.
core shall be taken from each and tested. If both cores have a for all sizes through 7 ft internal span, and a maximum of 3⁄4 in.
City of Buda Copyright by ASTM Int'l (all rights reserved);
Municipal Library and City Hall/Public Service Building ASTM C1577 - 14
Page Proj. 115036 50% DD - May 23, 2016 33 4001 - 15
C1577 − 14
for internal spans greater than 7 ft, except where beveled ends acceptable if, in the opinion of the purchaser, the repaired box
for laying of curves are specified by the purchaser. section conforms to the requirements of this specification.
11.4 Length of Section—The underrun in length of a section
shall not be more than 1⁄8 in./ft of length with a maximum of 1⁄2 13. Inspection
in. in any box section. 13.1 The quality of materials, the process of manufacture,
11.5 Position of Reinforcement—The maximum variation in and the finished box sections shall be subject to inspection by
the position of the reinforcement of 5-in. or less slab and wall the purchaser.
thickness shall be 6 3⁄8 in., and for greater than 5-in. slab and
wall thickness shall be 6 1⁄2 in. In no case, however, shall the 14. Rejection
cover over the reinforcement be less than 5⁄8 in., as measured to 14.1 Box sections are subject to rejection on account of
the internal surface or the external surface except the cover failure to conform to any of the specification requirements.
over the reinforcement for the external surface of the top slab Individual box sections are subject to rejection because of any
for boxes with under 2 ft of cover shall not be less than 15⁄8 in. of the following:
The preceding minimum cover limitation does not apply at the 14.1.1 Fractures or cracks passing through the wall, except
mating surfaces of the joint. for a single end crack that does not exceed the depth of the
11.6 Area of Reinforcement—The areas of steel reinforce- joint,
ment shall be the design steel areas as shown in Table 1. Steel 14.1.2 Defects that indicate mixing and molding not in
areas greater than those required shall not be cause for compliance with 9.1, or honeycombed or open texture that
rejection. The permissible variation in diameter of any wire in would adversely affect the function of the box sections,
finished reinforcement shall conform to the tolerances pre- 14.1.3 Abnormalities in the ends of the box sections to the
scribed for the wire before fabrication by Specification A1064/ walls and center line of the box section, within the limits of
A1064M as applicable. If steel bars (Grade 60) are used in lieu variations given in Section 11, except where beveled ends are
of welded wire reinforcement, the steel areas presented in specified, and
Table 1 shall be increased to account for the difference in steel 14.1.4 Damaged ends, where such damage would prevent
yield strength, steel spacing, concrete cover, and crack control making a satisfactory joint.
between the welded wire reinforcement and steel bars.
11.7 Haunch Dimensions—The vertical and horizontal di- 15. Marking
mensions shall be equal to the side wall thickness. If haunches 15.1 The following information shall be legibly marked on
with other dimensions are used, a special reinforcement design each box section by indentation, waterproof paint, or other
for the actual dimensions shall be completed. In lieu of approved means:
performing a special design, for the specific case where the 15.1.1 Box section span, rise, maximum and minimum
actual haunch dimensions are larger than the standard dimen- design earth cover, and specification designation.
sions and vertical and horizontal haunch dimensions are equal,
15.1.2 Date of manufacture, and
the As1 steel area shall be increased 1 % for every 5 % increase
in the haunch dimension over that specified in Table 1 and As2 15.1.3 Name or trademark of the manufacturer.
and As3 shall be reduced by an equal percentage. 15.2 Each section shall be clearly marked on either the inner
or outer surface during the process of manufacture so that the
12. Repairs location of the top will be evident immediately after the forms
12.1 Box sections shall be repaired, if necessary, because of are stripped. In addition, the word “top” shall be lettered with
imperfections in manufacture or handling damage and will be waterproof paint on the inside top surface.
APPENDIX
(Nonmandatory Information)
X1.1 Bedding and Backfill Assumptions lation practices. For additional information on the construction
X1.1.1 The bedding is assumed to provide a slightly of precast concrete box section systems, ASCE 26–97 may be
yielding, uniformly distributed support over the bottom width consulted.
of the box section. Reference Section 27 of the AASHTO X1.1.2 The design earth covers and reinforcement areas are
LRFD Bridge Construction Specifications for standard instal- based on the weight of a column of earth over the width of the
Copyright by ASTM Int'l (all rights reserved);
City of Buda
Municipal Library and City Hall/Public Service Building ASTM C1577 - 14
Page Proj. 115036 50% DD - May 23, 2016 33 4001 - 16
C1577 − 14
box section multiplied by a soil-structure interaction factor (see X1.2.2 Live loads for designs given in Table 1 are HL-93
Table X1.1). Select granular backfill is assumed above the box loadings without the lane load as defined in the AASHTO
culvert. LRFD specifications. Dynamic load allowances are in accor-
dance with the AASHTO specification. The HL-93 live load
X1.2 Criteria for Loads
consists of the design truck (32 000 lb axle, identical to the HS
X1.2.1 Design loads are based on the American Association 20 truck of the Standard Specifications) or a design tandem
of State Highway and Transportation Officials (AASHTO (two 25 000 lb axles spaced 4 feet apart).
LRFD Bridge Design Specifications).
span,
1⁄12 inside span above 7-ft span
City of Buda
Municipal Library and City Hall/Public Service Building ASTM C1577 - 14
Page Proj. 115036 50% DD - May 23, 2016 33 4001 - 17
C1577 − 14
X1.2.3 For box sections with less than 2 ft of cover, wheel a separate analysis must be performed. (For cover depths of
loads are distributed perpendicular to the span by the use of greater than 5 ft, a separate skew analysis need not be
longitudinal distribution reinforcement in the top and bottom of performed.) Live loads are applied for all depths and are not
the top slab. The width of the live load distribution for an entire cut off at any preset depth.
axle at these depths is E = 96 (in.) + 1.44Span (ft) where E =
X1.2.4 Cover loads for designs given in Table 1 are the
distribution width in inches. The length of the applied load is
weight of a column of earth of a width equal to the outside
L = 10 (in.) + 1.15H (in.). For box sections with 2 ft or more
width dimension of the box section and a height equal to the
of cover, the wheel load is applied as a tire footprint of w = 20
depth of cover over the top of the section multiplied by the
(in.) by l = 10 inches on the surface and distributed through the
appropriate AASHTO soil structure interaction factor.
soil to the top of the box with dimensions equal to the tire
footprint plus 1.15H in each direction assuming use of a select X1.2.5 Lateral earth pressure from weight of earth above
granular backfill above the culvert. Live loads are applied from and adjacent to a box section is taken as 0.50 times the vertical
a truck traveling parallel to the span of the box. If live load pressure. This value is increased by the load factor of 1.35 for
travel is at an angle greater than 30° from parallel to the span, the maximum lateral earth pressure used in design. The box
City of Buda Copyright by ASTM Int'l (all rights reserved);
Municipal Library and City Hall/Public Service Building ASTM C1577 - 14
Page Proj. 115036 50% DD - May 23, 2016 33 4001 - 18
C1577 − 14
culverts are also evaluated for a minimum lateral earth bution reinforcement is also required in the outside face of the
pressure, which may result in increased steel areas in certain top slab, when wheel loads are adjacent to joints which provide
locations of the box culvert. AASHTO allows for a 50 % only shear connections between box section units. These
reduction in the lateral earth pressure in lieu of applying a requirements were determined by evaluating analyses with
minimum earth load factor of 0.90. This results in a minimum loads in various positions on and near the edge of slabs having
lateral earth pressure design value of 0.25 times the maximum various length to width ratios and various conditions of edge
vertical earth pressure This minimum value is 50 % of the restraint. Distribution reinforcement shall either be welded
maximum value. For Table 1, additional lateral pressure in wire reinforcement or deformed Grade 60 bars, subject to the
lbf/ft2 from approaching truck wheel loads is added when provisions of section 11.6. A slab thickness of 1⁄12 the span (or
determining steel areas only at sections where area is increased greater) as required by this specification encompasses the
by increased lateral pressure (see Table X1.1). recommended minimum section depth and deflection require-
ments in the AASHTO LRFD Bridge Design Specifications.
X1.3 Methods of Analysis X1.4.2 Some box section designs shown in Table 1 have
X1.3.1 The structural effects of the loads described in X1.2 minimum practical steel area requirements. For such designs,
are evaluated based on the elastic method of structural analysis. the steel areas calculated for support of design loads are less
Design moments, shears, and thrusts are determined by com- than the minimum steel area which is specified for slabs in the
puter analysis using the stiffness matrix method, and design is AASHTO specification, (0.002 bt), and thus, the minimum
based on maximum stress resultants at critical sections caused reinforcement areas are shown in Table 1.
by the most severe combination of design loads. X1.4.3 For specific criteria used in Table 1, refer to Table
X1.1.
X1.4 Method of Design
X1.4.4 The maximum height of earth cover shown in Table
X1.4.1 Box section design is based on load and resistance 1 is determined by the shear strength of the box section without
factor design provisions given in AASHTO LRFD Bridge the use of special shear reinforcement and by the standard
Design Specifications. Reinforcement areas are governed by weight of the column of earth directly above the box section
either ultimate total load yield stress limitation of 65 000 multiplied by the soil structure interaction factor.
lbf/in.2, service total load stress limitation (cracking), or
maximum shear capacity using flexural reinforcement. Capac- X1.5 Multiple Cell Installations
ity reduction factors of 1.0 for flexure and axial compression, X1.5.1 The designs given herein are for single-cell precast
and 0.90 for shear were used. All designs in the tables are based reinforced concrete box sections. The units shall be allowed to
on welded wire fabric with a maximum of 4 in. spacing unless be used in parallel for multicell installations if means of
noted otherwise. Longitudinal distribution reinforcement positive lateral bearing by continuous contact between the
called for in Table 1 for top slab inside face is in accordance sides of adjacent boxes are provided. Compacted earth fill,
with distribution reinforcement formulas given in the granular backfill, flowable fill, or grouting between the units
AASHTO specification for bridge decks. Longitudinal distri- are considered means of providing such positive bearing.
ASTM International takes no position respecting the validity of any patent rights asserted in connection with any item mentioned
in this standard. Users of this standard are expressly advised that determination of the validity of any such patent rights, and the risk
of infringement of such rights, are entirely their own responsibility.
This standard is subject to revision at any time by the responsible technical committee and must be reviewed every five years and
if not revised, either reapproved or withdrawn. Your comments are invited either for revision of this standard or for additional standards
and should be addressed to ASTM International Headquarters. Your comments will receive careful consideration at a meeting of the
responsible technical committee, which you may attend. If you feel that your comments have not received a fair hearing you should
make your views known to the ASTM Committee on Standards, at the address shown below.
This standard is copyrighted by ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959,
United States. Individual reprints (single or multiple copies) of this standard may be obtained by contacting ASTM at the above
address or at 610-832-9585 (phone), 610-832-9555 (fax), or service@astm.org (e-mail); or through the ASTM website
(www.astm.org). Permission rights to photocopy the standard may also be secured from the ASTM website (www.astm.org/
COPYRIGHT/).
City of Buda
Municipal Library and City Hall/Public Service Building ASTM C1577 - 14
Page Proj. 115036 50% DD - May 23, 2016 33 4001 - 19