DataSheet CASB383
DataSheet CASB383
DataSheet CASB383
CASB383/CASB383WP
Eaton’s Cooper wall sounder beacons
Technical Specification
Code CASB383 CASB383WP
Description Internal Wall Sounder Beacon Weatherproof Wall Sounder Beacon
Standards EN54 Pt3 EN54 Pt3
Specification
Operating Voltage 17V dc to 32V dc 17V dc to 32V dc
Standby Current < 320µA < 320µA
Tones (set by panel) Continuous: 984Hz Continuous: 984Hz
Pulsed: 984Hz / 0Hz pulse 1Hz Pulsed: 984Hz / 0Hz pulse 1Hz
Two tone: 644 / 984Hz at 1Hz cycle Two tone: 644 / 984Hz at 1Hz cycle
Slow whoop: 500-1200Hz in 3.5 Slow whoop: 500-1200Hz in 3.5
seconds/0.5secs gap seconds/0.5secs gap
Sound Output at +/-3dB Low volume: 92dB at < 6.5mA Low volume: 92dB at < 6.5mA
Medium volume: 97dB at < 7.5mA Medium volume: 97dB at < 7.5mA
(set by panel) High volume: 100dB at < 8.5mA High volume: 100dB at < 8.5mA
Flash Energy 1Hz 1Hz
Environmental
Operating Temperature -10°C to +55°C -10°C to +55°C
Humidity (Non Condensing) 0 to 95% RH 0 to 95% RH
Physical
Construction PC/ABS PC/ABS
Colour Red Red
Lens Colour Red Red
Dimensions (H x W x D) 105mm x 105mm x 95mm 108mm x 108mm x 103mm
Weight 0.21kg 0.32kg
Ingress Protection IP42 IP66
Cable Entry Rear/side Rear/side
Cable Size / Type 0.5mm to 2.5mm/ FIRETUF, FP200 or MICC 0.5mm to 2.5mm/ FIRETUF, FP200 or MICC
Compatibility
Suitable for use with Cooper Intelligent Addressable Fire Systems Cooper Intelligent Addressable Fire Systems
Installation Dimensions
CASB383
1. Installation is simple using first fix base.
2. First fix base is fixed to mounting surface using 2 fixing
holes.
3. Cable entry can be rear or side.
4. Connections are to connector block on main sounder body.
5. Main body is then clipped into position on mounting base,
body locks into position when pressed home.
CASB383WP Description H (mm) W (mm) D (mm)
1. Installation is simple using first fix base.
Internal 105 105 95
2. First fix base is fixed to mounting surface using 2 fixing
holes. Waterproof 108 108 103
3. Cable entry can be rear or side.
4. Connections are to connector block on main sounder body.
System Functionality
5. Main body is then fastened onto base, using 4 allen head
screws (supplied). CASB383 / CASB383WP
1. Volume is set by fire control panel, no need to access
Standard Connections sounder to alter setting.
Screen
Screen
OUT
E - + E - + to alter setting.
Compatible Cooper
LOOP
LOOP
OUT
Intelligent Addressable
IN
Control Panel
Catalogue numbers
WARNING: Description Code
Do NOT use high voltage testers if ANY equipment is
connected to the system. Internal Wall Sounder Beacon CASB383
Weatherproof Wall Sounder Beacon CASB383WP
Screen (Earth) must be continuous along entire length of loop.