XP95 Mini Switch Monitor Installation Guide: Functional Test Data

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

The part no of this guide is 39214-076/Issue 2

Functional Test Data

OUTPUT BIT FUNCTION INPUT BIT FUNCTION

2 ILLUMINATE LED 2 LED ON CONFIRMED

1 ACTIVATE SELF TEST 1 SELF TEST ACTIVATED

0 SIMULATE FAULT 0 FAULT SIMULATION CONFIRMED

FIRE DETECTORS LIMITED

Troubleshooting
Before investigating individual units for faults, it is very important to check that the
system wiring is fault free. Earth faults on a data loop or any ancillary zone wiring may
cause communication errors. Many fault conditions are the result of simple wiring XP95 Mini Switch Monitor
errors. Check all connections to the unit and make sure the correct value resistors
are fitted where necessary. Installation Guide
Fault Finding
The Mini Switch Monitor, part no 55000-833, is designed to monitor the state of one
Problem Possible Cause
or more single-pole, volt-free contacts and may be used in installations where space
No response or missing Incorrect address setting is limited. An end-of-line resistor of 20kΩ should be fitted to the monitoring circuit.
Incorrect loop wiring
Fault condition reported Incorrect wiring The XP95 Mini Switch Monitor has colour coded flying leads and the device is
wired into a circuit without any additional mounting or securing being required.
Analogue value unstable Dual address
Connections to the flying leads should be made via suitable terminal blocks.
Loop data fault, data corruption
Constant alarm Incorrect end-of-line resistor The Mini Switch Monitor has an alarm LED. During installation the device should be
Incorrect wiring correctly orientated, if it is required that the LED be visible.

There are three wiring options for the Mini Switch Monitor and these are shown
overleaf.

The address of the Mini Switch Monitor is set by means of the 7-segment DIL
switch. Each segment of the switch must be set to “0” (ON) or “1” (OFF), using a
small screwdriver or similar tool. Address settings are shown overleaf. An
adhesive label is supplied to cover the aperture through which the DIL switch is
accessed. The label must be fitted to ensure proper protection of the internal
circuitry. Failure to fit the label will invalidate the IP rating. The setting of the switch
should be marked on this label.

Apollo Fire Detectors Limited, 36 Brookside Road, Havant, Hants, PO9 1JR, UK
Tel +44 (0)23 9249 2412 Fax +44 (0)23 9249 2754
Email: techsales@apollo-fire.co.uk Website: www.apollo-fire.co.uk

4 1
consistency, it is recommended that L1 be kept negative
* L1 and L2 are polarity insensitive, but, for the sake of

Fire contacts

Wiring options for the Mini Switch Monitor


Fire, pre-alarm and fault contacts

Fire and fault contacts


WHITE

VIOLET
GREEN

YELLOW
BLACK

RED

WHITE
VIOLET +

GREEN

YELLOW

BLACK

RED
WHITE

VIOLET
GREEN

YELLOW

BLACK

RED



+

LINE

LINE

LINE

LINE

+

LINE

LINE
2

1*
2*

1*
2*
1*
2*
REMOTE LED

REMOTE LED

REMOTE LED
CONTACT CONTACT
FIRE

1kΩ
1kΩ

1kΩ

CONTACT
FIRE
CONTACT
FIRE
PRE-ALARM

FAULT CONTACT

FAULT CONTACT
10kΩ

20kΩ ± 10% 1/3 W


± 10% 1/3 W
20kΩ

± 10% 1/3 W
20kΩ

DIL switch DIL switch DIL switch DIL switch DIL switch
addr setting addr setting addr setting addr setting addr setting
1234567 1234567 1234567 1234567 1234567

1 1000000 11 1101000 21 1010100 31 1111100 41 1001010


2 0100000 12 0011000 22 0110100 32 0000010 42 0101010
3 1100000 13 1011000 23 1110100 33 1000010 43 1101010
4 0010000 14 0111000 24 0001100 34 0100010 44 0011010
5 1010000 15 1111000 25 1001100 35 1100010 45 1011010
6 0110000 16 0000100 26 0101100 36 0010010 46 0111010
7 1110000 17 1000100 27 1101100 37 1010010 47 1111010
8 0001000 18 0100100 28 0011100 38 0110010 48 0000110
9 1001000 19 1100100 29 1011100 39 1110010 49 1000110
10 0101000 20 0010100 30 0111100 40 0001010 50 0100110

51 1100110 61 1011110 71 1110001 81 1000101 91 1101101


52 0010110 62 0111110 72 0001001 82 0100101 92 0011101
3

53 1010110 63 1111110 73 1001001 83 1100101 93 1011101


54 0110110 64 0000001 74 0101001 84 0010101 94 0111101
55 1110110 65 1000001 75 1101001 85 1010101 95 1111101
56 0001110 66 0100001 76 0011001 86 0110101 96 0000011
57 1001110 67 1100001 77 1011001 87 1110101 97 1000011
58 0101110 68 0010001 78 0111001 88 0001101 98 0100011
59 1101110 69 1010001 79 1111001 89 1001101 99 1100011
60 0011110 70 0110001 80 0000101 90 0101101 100 0010011

101 1010011 111 1111011 121 1001111


102 0110011 112 0000111 122 0101111
103 1110011 113 1000111 123 1101111
104 0001011 114 0100111 124 0011111
105 1001011 115 1100111 125 1011111
106 0101011 116 0010111 126 0111111
107 1101011 117 1010111
108 0011011 118 0110111
109 1011011 119 1110111
110 0111011 120 0001111