Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                
0% found this document useful (0 votes)
116 views4 pages

CIBSE

Damper sizing instruction

Uploaded by

Mihailo Jovic
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF or read online on Scribd
0% found this document useful (0 votes)
116 views4 pages

CIBSE

Damper sizing instruction

Uploaded by

Mihailo Jovic
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF or read online on Scribd
Components and devices Table 3.10 Vapour presure of water ‘Waerienperaure(()___Vepourpresure QPS) 0 12 20 23 «0 va 0 123 o 189 ‘0 a3 0 m1 109 11 10 148 Ho 20 0 361 150 6 0 1003 19 5 200 155 strategy. The following points should be taken into consideration when selecting a valve: — _Isthe valve body suitable for the temperature and pressure of the fluid system? Remember the pressureiis the sum of static and dynamic bead. ‘Ensure that the valve will pass the required flow ata pressure drop within the maximum differential pressure rating ofthe valve, — Check for out-of-balance forces, particularly during closure ofa two-port valve. ‘Check whether tight shutoff is required; this is not usually possible with a double seated valve — Check there is sufficient pump head to provide the pressure drop across the valve at the specific duty. ‘The above rules apply to all valves, including two-position on/off, For modulating valves, the following additional considerations apply: Rectangular damper with single piece blades Round damper 347 — Select an equal percentage valve characteristic unless there is good reason to select an alternative. — Ensure pressure drops though heat exchangers and associated pipework are known before control valves are selected. Select valves to provide an authority of at least 0.5 for diverting applications and 0.3 for mixing applications. — Where possible, use heat transfer curves of flow against output to check possible anomalies and confirm the correct characteristic has been chosen. — Ensure that the rangeability ofthe selected valves is large enough to provide stable control under low load conditions. ‘Three-port valves with asymmetrical port charac- teristics should be used to maintain flow conditions. Before finalising the selection: — Check whether there have been changes to the specification of heat exchangers and pipework since the original design, 3.4 3.4.1 Dampers Damper selection Dampers are used to control air low in ducts in a manner analogous to the use of valves in hydraulic circuits. The damper chosen for a particular situation must satisfy both the physical requirements of the application and also provide suitable control characteristics. The practice of simply selecting a damper to fit the available duct dimensions can lead to unsatisfactory control operation. ‘The majority of dampers used for modulating control have a rectangular cross-section and provide control by rotating. a set of blades. The blades may move in parallel or ‘opposition to each other. Figure 3.17 shows different types of damper. Round dampers normally have a butterfly type blade and are used to control flow in ducts that have high static pressure and high velocity characteristics. Dampers Rectangular damper with airfoil blades Figure 317 Typeofdampe 348 Building control systems ‘ay be installed for the control of fire and smoke. Smoke dampers have to meet relevant criteria and are normally installed and operated independently of the 1vac control, system; they are not considered further in this Guide. Its, possible to obtain smoke and control dampers, which are capable of operating as modulating dampers, while retaining the necessary smoke control criteria after many operations. Damper sizing is covered in more detail below. Other factors to be taken into account when selecting a damperare: — Leakage rating. Leakage through the damper in the closed position may be critical in such applications as fresh air intakes in cold climates and the design should specify the maximum acceptable leakage. It is difficult to achieve good shutoff with a damper and it is necessary to specify low leakage construction where required. Different classes of leakage are available and leakage is specified in terms of leakage volumettic flow per unit damper area at a specified pressure difference. Low leakage is obtained by the provision of seals and the use of stiffer blades; this may require a higher closing force from the actuator. = Velocity and turbulence. As the ait velocity in a duct increases, the damper blades experience higher forces, which may be sufficient to bend or twist the blade, or cause problems with the bearings and linkage. Dampers are given a velocity rating to indicate the maximum velocity in the duct; ratings ‘may need to be reduced in turbulent conditions. ‘Moderate turbulence may be found downstream of dduct transitions or elbows. Severe turbulence can bbe found near the discharge ofa fan and this can be sufficient to prevent satisfactory operation of damper. — Pressure. The maximum static pressure that can be developed across a damper occurs when the blades are closed. Dampers are given a maximum static pressure differential; operation above this value may give rise to excessive leakage and possible damage. = Torque requirements, Two conditions must be considered when establishing minimum torque requirement of 2 damper. One is the closing torque which is needed to achieve the required maximum leakage rate. The other is the dynamic torque needed to overcome the effect of high velocity air flow over the blades, This will affect actuator selection. — Mixing, Parallel blade dampers alter the flow => Bypats damper van seas Figure 3.24 Faceand bypass damper sytem, shoring uso dampers toast mining configuration, as shown in Figure 3.24. The system is designed to provide constant pressure drop and hence constant combined flow rate, while the proportion of air flowing through the coi is varied by operating a linked pair of dampers. Since the pressure drop across the bypass damper is constant, a parallel blade damper is used to provide linear characteristic with minimum pressure drop. at full low. Since the face damper has the resistance of the coil in series, an opposed blade damper is used of the appropriate authority to provide a linear characteristic. Starting with the known resistance of the coil, the face damper will be sized to give an authority of between S and 10% and the bypass damper then sized so that its resistance is equal to that of the combination of face damper and coils, this will give an approximately constant flow though the system at all operating positions. Consideration may be given to the use of parallel blade dampers for both sets t0 aid downstream mixing, as shown in the diagram. 3.5 3.5.1 ney ‘Motors are major users of electricity and account for almost half the tol electricity use in the UK. Recent developments in higher efficiency motors and_variable- speed drives are described in the DETR Good Practice Guide 29, which offers ood advice on the energy elficient use of ‘motors, shown in Table 3.12. By far the most common type of motor used in Hvac applications is the three-phase squirrel cage induction motor. Three-phase power is supplied tothe field windings in the stator, the fixed part of, the motor which encloses the rotating rotor. The current in os

You might also like