Datacom Copper - 2020 Low Res
Datacom Copper - 2020 Low Res
Datacom Copper - 2020 Low Res
White/orange
White/blue
AL/Mylar
Jacket
Rip-cord Braid
White/brown
White/green
Drain wire
COMPLIANCE
ISO/IEC11801, ANSI/TIA-568-C.2
PHYSICAL CHARACTERISTICS
Conductor Material SOLID-Bare Copper
Nom.O.D. 0.560, 0.005±0.005mm
Insulation Material Skin-foam-skin PE
Diameter 1.30±0.05 mm
Inner Screening Material Al/Mylar Drain wire Yes
Outer Screening Material Aluminum-magnesium alloy 0.12mm Coverage ≥30%
Sheath Thickness 0.50±0.05 mm
External O.D. 7.2±0.5 mm
Surface Clean
Material LSZH(complies RoHS)
Core Color 1 White/Blue 2 White/Orange
3 White/Green 4 White/Brown
Rip-cord Yes
Sheath Physical Properties Before Aging Tensile Strength (Mpa) ≥10.0
Elongation(%) ≥125
Aging Period (°C×hrs) 100°C×24h×7d
After Aging Tensile Strength(Mpa) ≥8.0
Elongation(%) ≥100
Cold bend(-20±2×4h) 8×Cable O.D. No visible cracks
ELECTRICAL CHARACTERISTICS
Electrical Characteristics (20°C) Impedance(Ω) 1.0-250.0MHz 100±15 RL
250.0-500.0MHz 100±22
1.0-500.0MHz Delay Skew (ns/100m) ≤45
Unbalanced-to-ground capacitance(pf/100m)max 330
DC Resistance (Ω/100m) max 9.38
DC Conductor Resistance Unbalance (%) max 5.0
06 www.datacomonline.net
TRANSMISSION CHARACTERISTICS (100m)
Frequency RL ATT NEXT DELAY PSNEXT ELFEXT PSELFEXT
(MHz) ≥dB ≤dB ≥dB ≤ns ≥dB ≥dB ≥dB
1 20.0 — 74.3 570.0 72.3 67.8 64.8
4.0 23.0 3.8 65.3 552.0 63.3 55.8 52.8
8.0 24.5 5.3 60.8 546.7 48.8 49.7 46.7
10.0 25.0 5.9 59.3 545.4 57.3 47.8 44.8
16.0 25.0 7.5 56.2 543.0 54.2 43.7 40.7
20.0 25.0 8.4 54.8 542.1 52.8 41.8 38.8
25.0 24.3 9.4 53.3 541.2 51.3 39.8 36.8
31.25 23.6 10.5 51.9 540.4 49.9 37.9 34.9
62.5 21.5 15.0 47.4 538.6 45.4 31.9 28.9
100 20.1 19.1 44.3 537.6 42.3 27.8 24.8
200 18.0 27.6 39.8 536.5 37.8 21.8 18.8
250 17.3 31.1 38.3 536.3 36.3 19.8 16.8
300 16.8 34.3 37.1 536.1 35.1 18.3 15.3
500 15.2 45.3 33.8 535.6 31.8 13.8 10.8
ORDERING INFORMATION
Description Order Code
Cat 6A S/FTP 4 pairs 23 AWG Screened Solid Cable LSZH 305 Mtr DC-CBL-C6A-SF-LSZH
www.datacomonline.net 07
CATEGORY 6A F/FTP 4 PAIRS 23 AWG SCREENED SOLID CABLE
White/Orange
White/Blue
AL/Mylar
Drain Wire
Rip-cord
Jacket
White/Brown White/Green
COMPLIANCE
ISO/IEC11801 ANSI/TIA-568-C.2
PHYSICAL CHARACTERISTICS
Conductor Material SOLID-Bare Copper
Nom.O.D. 0.560, 0.005±0.005mm
Insulation Material Skin-foam-skin PE
Diameter 1.30±0.05 mm
Sheath Thickness 0.50±0.05 mm
External O.D. 7.1±0.5 mm
Material LSZH(complies RoHS)
Core Color 1 White/Blue 2 White/Orange
3 White/Green 4 White/Brown
Rip-cord Yes
Sheath Physical Properties Before Aging Tensile Strength (Mpa) ≥10.0
Elongation(%) ≥125
Aging Period (°C×hrs) 100°C×24h×7d
After Aging Tensile Strength(Mpa) ≥8.0
Elongation(%) ≥100
Cold bend(-20±2×4h) 8×Cable O.D. No visible cracks
ELECTRICAL CHARACTERISTICS
Electrical Characteristics (20°C) Impedance(Ω) 1.0-250.0MHz 100±15 RL
250.0-500.0MHz 100±22
1.0-500.0MHz Delay Skew (ns/100m) ≤45
Unbalanced-to-ground Capacitance (pf/100m)max 330
DC Resistance (Ω/100m) max 9.38
DC Conductor Resistance Unbalance (%) max 5.0
08 www.datacomonline.net
TRANSMISSION CHARACTERISTICS (100m)
Frequency RL ATT NEXT PHASE DELAY PSNEXT ELFEXT PSELFEXT
(MHz) ≥dB ≤dB ≥dB ≤ns ≥dB ≥dB ≥dB
1 20.0 — 74.3 570 72.3 67.8 64.8
4.0 23.0 3.8 65.3 552 63.3 55.8 52.8
8.0 24.5 5.3 60.8 547 58.8 49.7 46.7
10.0 25.0 5.9 59.3 545 57.3 47.8 44.8
16.0 25.0 7.5 56.2 543 54.2 43.7 40.7
20.0 25.0 8.4 54.8 542 52.8 41.8 38.8
25.0 24.3 9.4 53.3 541 51.3 39.8 36.8
31.25 23.6 10.5 51.9 540 49.9 37.9 34.9
62.5 21.5 15.0 47.4 539 45.4 31.9 28.9
100 20.1 19.1 44.3 538 42.3 27.8 24.8
200 18.0 27.6 39.8 537 37.8 21.8 18.8
250 17.3 31.1 38.3 536 36.3 19.8 16.8
300 16.8 34.3 37.1 536 35.1 18.3 15.3
400 15.9 40.1 35.3 536 33.3 15.8 12.8
500 15.2 45.3 33.8 536 31.8 13.8 10.8
ORDERING INFORMATION
Description Order Code
Cat 6A F/FTP 4 pairs 23 AWG Screened Solid Cable LSZH-305Mtr DC-CBL-C6A-FF-LSZH
www.datacomonline.net 09
CATEGORY 6A F/UTP CABLE 4 PAIRS 23AWG SCREENED SOLID CABLE
Datacom Category 6A F/UTP cable is used for horizontal network and voice application in a structured cabling system, Including
IEEE 802.3an : 10G Base-T Gigabit Ethernet, 2.4/1.2Gb/s ATM, Digital video, Broadband & Baseband analog video.
White-Orange /Orange
Mylar
Sheath
AL/Mylar
Rip-cord
Drain Wire
COMPLIANCE
ISO/IEC-11801, TIA 568 C.2
PHYSICAL CHARACTERISTICS
Conductor Material Solid-Bare Copper
Structure 23AWG, 0.565±0.005mm
Insulation Material HDPE
Structure Dia 1.12±0.04mm
Foil Screen Material Aluminum/PET
Thickness 50/12mm
Drain Wire Yes
Rip Cord Yes
Sheath Material PVC or LSZH
Thickness 0.51mm
OD 7.73±0.3mm
Pulling Tension Max.110N
ELECTRICAL CHARACTERISTICS 20 C
Impedance(Ω) 1.0-250.0MHz 100±15 RL
251.0-500.0MHz 100±22
1.0-500.0MHz Delay Skew (ns/100m) ≤45
Unbalanced-to-ground Capacitance (pf/100m) max 330
DC Resistance (Ω/100m) max 9.38
DC Conductor Resistance Unbalance (%) max 5.0
10 www.datacomonline.net
TRANSMISSION CHARACTERISTICS
Frequency RL ATT NEXT PHASE DELAY PS-NEXT EL-FEXT PS-ELFEXT
MHz ≥dB ≤dB ≥dB ≤ns ≥dB ≥dB ≥dB
1 20.0 — 74.3 570.0 72.3 68.0 65.0
4.0 23.0 3.8 65.3 552.0 63.3 56.0 53.0
8.0 24.5 5.3 60.8 546.7 58.8 49.9 46.9
10.0 25.0 5.9 59.3 545.4 57.3 48.0 45.0
16.0 25.0 7.5 56.2 543.0 54.2 43.9 40.9
20.0 25.0 8.4 54.8 542.1 52.8 42.0 39.0
25.0 24.3 9.4 53.3 541.2 51.3 40.0 37.0
31.25 23.6 10.5 51.9 540.4 49.9 38.1 35.1
62.5 21.5 15.0 47.4 538.6 45.4 32.1 29.1
100 20.1 19.1 44.3 537.6 42.3 28.0 25.0
200 18.0 27.6 39.8 536.5 37.8 22.0 19.0
250 17.3 31.1 38.3 536.3 36.3 20.0 17.0
300 16.8 34.3 37.1 536.1 35.1 18.5 15.5
500 15.2 45.3 33.8 535.6 31.8 14.0 11.0
(1) All performance based on 100 meters at 20°C. (2) The Asterisked (*) Frequency performance value are assumed to be met by design.
ORDERING INFORMATION
Description Order Code
Cat 6A F/UTP 4 Pairs 23 AWG Screened Solid Cable PVC 305Mtr DC-CBL-C6A-FU-PVC
Cat 6A F/UTP 4 Pairs 23 AWG Screened Solid Cable LSZH 305Mtr DC-CBL-C6A-FU-LSZH
www.datacomonline.net 11
CATAGORY 6A OUTDOOR F/UTP CABLE
Conductor
PE Insulation
Cross Web Filler
Drain Wire
Al/Mylar Tape
PE Jacket
COMPLIANCE
ANSI/TIA-568-C.2, ISO/IEC 11801, IEC 61156-5
ELECTRICAL CHARACTERISTICS
Conductor Resistance (DC) at 20˚C Ω/100m Max.9.38
Resistance Unbalance (DC) at 20˚C % Max.4.0
Mutual Capacitance at 1kHz nF/100m Max.5.6
Capacitance Unbalance at 1kHz pF/100m Max.330
Insulation Resistance MΩ/km Min.5000
Dielectric Strength at 2sec. DC kV 2.5
12 www.datacomonline.net
TRANSMISSION CHARACTERISTICS
Item Attenuationat20˚C NEXT PS NEXT ACRF PSACRF Return Loss
dB/100m dB/100m dB/100m dB/100m dB/100m dB/100m
Unit
(Max.) (Min.) (Min.) (Min.) (Min.) (Min.)
1 MHz 2.1 74.3 72.3 67.8 64.8 20.0
4 MHz 3.8 65.3 63.3 55.8 52.8 23.0
10 MHz 5.9 59.3 57.3 47.8 44.8 25.0
16 MHz 7.5 56.2 54.2 43.7 40.7 25.0
20 MHz 8.4 54.8 52.8 41.8 38.8 25.0
Transmission
31.25 MHz 10.5 51.9 49.9 37.9 34.9 23.6
Characteristics
62.5 MHz 15.0 47.4 45.4 31.9 28.9 21.5
100 MHz 19.1 44.3 42.3 27.8 24.8 20.1
200 MHz 27.6 39.8 37.8 21.8 18.8 18.0
300 MHz 34.3 37.1 35.1 18.3 15.3 16.8
400 MHz 40.1 35.3 33.3 15.8 12.8 15.9
500 MHz 45.3 33.8 31.8 13.8 10.8 15.2
* The cable performance between 1MHz and 4MHz is achieved by design only and it is there fore not necessary to test fort his
performance below 4MHz, according to IEC 61156-5 standard.
* For screened cables ANEXT & AFEXT are proven by design.
PHYSICAL CHARACTERISTICS
Item Unit Characteristics Remark
Insulation (Unaged)
Elongation % Min.100 IEC61156-5, Clause6.4.4
Cold Bend - No Crack IEC61156-5, Clause6.5.3
Shrinkage % Max. 5 IEC61156-5, Clause6.5.1
Insulation (Aged) 100±2˚C/48h
Tensile Strength % Min.75 of unaged
Elongation % Min.75 of unaged
Jacket (Unaged)
Tensile Strength MPa Min. 9.0
Elongation % Min. 100
Cold Bend - No Crack IEC61156-5, Clause6.5.7
Jacket (Aged) 100±2˚C/168h
Tensile Strength % Min.70 of Unaged
Elongation % Min.50 of Unaged
Sunlight Resistance - Pass UL1581, Section1200
ORDERING INFORMATION
Description Order Code
Cat6A 4 Pair, Outdoor, F/UTP Cable 23awg, 500 Mtr Reel DC-CBL-C6AFU-PE-5
Cat6A 4 Pair, Outdoor, F/UTP Cable 23awg,1000 Mtr Reel DC-CBL-C6AFU-PE-10
www.datacomonline.net 13
CATAGORY 6A U/UTP CABLE
Datacom Category 6A U/UTP cables exceed Category 6A/Class EA specification. It is tested to 500MHz frequency range and
designed to support 10 Gigabyte applications to full 100m. Extremely high pair-balance and providing high alien cross talk
performance .
Copper
PE Insulation
Cross-web Filler
Non-continuous Shield Tape
Pair
Jacket (PVC/LSZH)
COMPLIANCE
ANSI/TIA-568-C.2, ISO/IEC 11801, IEC 61156-5
ELECTRICAL CHARACTERISTICS
Conductor Resistance (DC) at 20˚C Ω/100m Max.9.38
Resistance Unbalance (DC) at 20˚C % Max.4.0
Mutual Capacitance at 1kHz nF/100m Max.5.6
Capacitance Unbalance at 1kHz pF/100m Max.330
Insulation Resistance MΩ/km Min.5000
Dielectric Strength at 2sec. DC kV 2.5
14 www.datacomonline.net
TRANSMISSION CHARACTERISTICS
Item Attenuationat20˚C NEXT PS NEXT ACRF PSACRF Return Loss
dB/100m dB/100m dB/100m dB/100m dB/100m dB/100m
Unit
(Max.) (Min.) (Min.) (Min.) (Min.) (Min.)
1 MHz 2.1 74.3 72.3 67.8 64.8 20.0
4 MHz 3.8 65.3 63.3 55.8 52.8 23.0
10 MHz 5.9 59.3 57.3 47.8 44.8 25.0
16 MHz 7.5 56.2 54.2 43.7 40.7 25.0
20 MHz 8.4 54.8 52.8 41.8 38.8 25.0
Transmission
31.25 MHz 10.5 51.9 49.9 37.9 34.9 23.6
Characteristics
62.5 MHz 15.0 47.4 45.4 31.9 28.9 21.5
100 MHz 19.1 44.3 42.3 27.8 24.8 20.1
200 MHz 27.6 39.8 37.8 21.8 18.8 18.0
300 MHz 34.3 37.1 35.1 18.3 15.3 16.8
400 MHz 40.1 35.3 33.3 15.8 12.8 15.9
500 MHz 45.3 33.8 31.8 13.8 10.8 15.2
ORDERING INFORMATION
Description Order Code
Cat 6A 4 Pair UTP Cable PVC Sheath 305 mtr DC-CBL-C6A-UT-PVC
Cat 6A 4 Pair UTP Cable LSZH Sheathh 305 mtr DC-CBL-C6A-UT-LSZH
www.datacomonline.net 15
CATEGORY 6 UTP CABLE
Datacom category 6 U/UTP cables exceed category 6/classE specification. It is tested to 250 MHz frequency range and designed
to support Gigabit 1000Base-Tand 100 Base-TX applications to 100m.Each cable consists of 8 color coded 23AWG polyethylene
insulated conductors twisted to form 4 pairs. These pairs are then formed around a separator enhancing high balance.
Copper
PE Insulation
Cross-Web filler
PVC Jacket
COMPLIANCE
ANS/TIA/EIA 568C.2, ISO/IEC 11801 Class 2nd
PHYSICAL CHARACTERISTICS
Conductor Material Soft & Annealed Copper
Conductor Size 23AWG
Conductor Construction Solid
Insulation Material High Density PE
Insulation Diameter Max. 0.98, Nom 0.93mm
Conductor Unit Identification Solid/Stripe
Total Number of Wires 8
Filler Cross-Web Filler
Rip Cord Non
Outer Jacket LSOH Flame Retardant or PVC
Outer Jacket Thickness & Ex. Diameter 0.5±0.05
ELECTRICAL CHARACTERISTICS
Conductor Resistance (DC) at 20°C Ω/100m Max. 9.38
Resistance Unbalance (DC) at 20°C % Max. 5
Mutual Capacitance at 1kHz nF/100m Max. 5.6
Capacitance Unbalance at 1kHz pF/100m Max. 330
Dielectric Strength at 2 sec. DC kV 2.5
16 www.datacomonline.net
TRANSMISSION CHARACTERISTICS
Item Attenuation NEXT PS NEXT ACRF PS ACRF Return Loss PD Skew
at 20˚C
dB/100m dB/100m dB/100m dB/100m dB/100m dB/100m ns/100m ns/100m
Unit
(Max.) (Min.) (Min.) (Min.) (Min.) (Min.) (Max.) (Max.)
1 MHz 2.0 74.3 72.3 67.8 64.8 20.0 570 45
4 MHz 3.8 65.3 63.3 55.8 52.8 23.0 552 45
10 MHz 6.0 59.3 57.3 47.8 44.8 25.0 545 45
16 MHz 7.6 56.2 54.2 43.7 40.7 25.0 543 45
Transmission 20 MHz 8.5 54.8 52.8 41.8 38.8 25.0 542 45
Characteristics 31.25 MHz 10.7 51.9 49.9 37.9 34.9 23.6 540 45
62.5 MHz 15.4 47.4 45.4 31.9 28.9 21.5 539 45
100 MHz 19.8 44.3 42.3 27.8 24.8 20.1 538 45
200 MHz 29.0 39.8 37.8 21.8 18.8 18.0 537 45
250 MHz 32.8 38.3 36.3 19.8 16.8 17.3 536 45
ORDERING INFORMATION
Description Order Code
Cat 6 4 Pair UTP Cable PVC Sheath 305 Mtr DC-CBL-C64P-PVC
Cat 6 4 Pair UTP Cable LSZH Sheath 305 Mtr DC-CBL-C64P-LSZH
www.datacomonline.net 17
5-100PAIR INDOOR TELEPHONE CABLE
Copper Conductor
HDPE Insulation
Ripcord
Polyester
Jacket
CONFIGURATION
Item 5-100Pair Indoor Telephone Cable
Conductor Conductor 0.5mm
Material Bare Copper
Structure 2*0.5mm
Insulation Material HDPE
OD Ø0.88±0.05mm
Rip Cord Nylon Rope White
Outer Jacket Material PVC
Color Grey.....
ELECTRICAL CHARACTERISTICS
Impedance(1.0-16.0MHz) (100±15)Ω
Minimum Bend Radius: >4D
Conductor Elongation 15% Minimum
DC Resistance Unbalance ≤5.0%
Mutual Capacitance ≤6.6 nF/100m
Installation Temperature -30°C To +50°C
DATA INFORMATION
Pairs Condutor Size Inslution Diameter Jacket Thickness Outer Diameter
5 0.5mm 0.88mm 0.6mm 5.5
25 0.5mm 0.88mm 1.4mm 11.8
50 0.5mm 0.88mm 1.4mm 14.8
100 0.5mm 0.88mm 1.4mm 19.8
ORDERING INFORMATION
Description Order Code
5 Pair Telephone Cable UTP Indoor DC-05P-IND-GYC3
10 Pair Telephone Cable UTP Indoor DC-10P-IND-GYC3
25 Pair Telephone Cable UTP Indoor DC-25P-IND-GYC3
50 Pair Telephone Cable UTP Indoor DC-50P-IND-GYC3
100 Pair Telephone Cable UTP Indoor DC-100P-IND-GYC3
200 Pair Telephone Cable UTP Indoor DC-200P-IND-GYC3
18 www.datacomonline.net
10-100 PAIR OUTDOOR TELEPHONE CABLE
Conductor
Insulation
PET Tape
Rip Cord
Sheath
CONFIGURATION
Item 10-100Pair Outdoor Telephone Cable
Conductor Conductor 0.5mm
Material Bare Copper
Structure 2*0.5mm
Insulation Material HDPE
OD Ø0.88±0.05mm
Filling Compound Material Jelly filled
Shielded Material PET tape
Rip Cord Nylon Rope White
Outer Jacket Material PE
Color Black
ELECTRICAL CHARACTERISTICS
Impedance(1.0-16.0MHz) (100±15)Ω
Mutual Capacitance ≤6.6 nF/100m
Conductor Elongation: 15% Minimum
DC Resistance Unbalance ≤5.0%
Delay Shew ≤45ns/100m
Installation Temperature -30°C To +50°C
DATA INFORMATION
Pairs Condutor Size Inslution Diameter Jacket Thickness Outer Diameter
10 0.5mm 0.88mm 1.5mm 10mm
25 0.5mm 0.88mm 1.5mm 12mm
50 0.5mm 0.88mm 1.5mm 16mm
100 0.5mm 0.88mm 1.5mm 21mm
ORDERING INFORMATION
Description Order Code
10 Pairs Telephone Cable UTP Outdoor with Jelly Filled DC-10P-OUT-BLKC3
25 Pairs Telephone Cable UTP Outdoor with Jelly Filled DC-25P-OUT-BLKC3
50 Pairs Telephone Cable UTP Outdoor with Jelly Filled DC-50P-OUT-BLKC3
100 Pairs Telephone Cable UTP Outdoor with Jelly Filled DC-100P-OUT-BLKC3
www.datacomonline.net 19
CATEGORY 6A SHIELDED JACK
The Datacom Category 6A shielded Jack, is a tool free jack suitable for patch panels, and faceplates. The socket itself is manufac-
tured with a high quality zinc die cast housing, which opens at the rear in a hinged manner to reveal the IDC termination points.
Once the conductors of the cable to be terminated are dressed into a management cap the process is completed by snapping
the hinged housings.
COMPLIANCE
ANSI/ TIA-568-C.2;ISO/IEC11801;IEC 60603-7-5
PHYSICAL CHARACTERISTICS
RJ 45 Shielded Jack:
Housing Zinc -die casting with Nickel plated
Contact Material Phosphor Bronze with 50-60 micro-inch Nickel Plated
Contact Finished Min 50 micron inch gold plated on surface contact area
Shield Bronze with Nickel plated
IDC:
Housing PC+Glass fiber,Grey color (RAL 7035,UL 94--V2
Terminal Phosphor bronze with Tin plated
Clip Stainless steel
Grounding Contact Zinc -die casting with Nickel plated
PCB FR4,UL 94 -Vo.
ELECTRICAL CHARACTERISTICS
Current Rating 1.5A
Insulation Resistance 500 MΩ min 100 V d.c.
Voltage Rating 230V rms max.
Dielectric Voltage 1000 V dc or ac, 60 Hz for 1 min (Contact-Contact)
Plug/Jack Contact Resistance 20 mΩ per contact
IDC Contact Resistance <1 mΩ max
PERFORMANCE CHARACTERISTICS
Life (Mating Cycles) 750 Cycles minimum
Insertion Force 30 N
Retention Strength 7.7kg between jack and plug
Propagation Delay 2.5ns max./1-500MHz
Propagation Delay Skew 1.25ns max./1-500 MHz
Coupling Attenuation 45 dB @ 30 - 500 MHz
ORDERING INFORMATION
Description Order Code
Cat 6A Shielded Modular Jack DC-MJRJ-C6A-SH
Cat 6A Shielded Modular Jack Keystone DC-MJKJ-C6A-SH
20 www.datacomonline.net
CATEGORY 6A MODULAR JACK
Datacom Category 6A 180° Modular Jacks Punch Down Type comply with TIA/EIA-568-B.2-1 and ISO/IEC 11801 for Category 6A/
Class E component performance standards and requirements with a 180° Cable entry form rear side. The 110-IDC type connectiv-
ity is capable of terminating 22 -26 AWG . Modular jacks are unshielded , 4-pair, RJ-45,designed to reduce the Insertion loss &
alien cross talk in order to provide maximum flexibility and high performance for all 10G Ethernet applications. This is tested to
500MHz range over 100m and supports T568 A&B wiring & easy installation
COMPLIANCE
ANSI/TIA 568-B.2-10, ISO/IEC 11801
PHYSICAL CHARACTERISTICS
Body Material Plastic Housing ABS +PC 94V 0
Insulation Displacement Contacts Phosphor Bronze with 50pin Tin-Lead plating
over 50-60 pin Nickel Plated
Insulation Displacement Cap ABS UL 94V -0
Insulation Displacement Housing Polycarbonate UL94V - 2
Colour Black and White
Size 35.1mm X 17.1mm X 25.2mm
ELECTRICAL CHARACTERISTICS
Modular Jack - 750 Mating Cycles Voltage - 150VAC max
110 Contacts - 200 Terminations
Operating Temperature - -40° - 80°C
Pull Force - 20Ibs (89N)
Current Rating 1.5A
PERFORMANCE CHARACTERISTICS
Freq.-MHz NEXT-dB RL-dB
1 86.3 26
4 85 29
10 77.3 31
20 70 30
31.25 68 29.8
100 65.3 27.1
250 57.6 25.2
300 55 24
400 53 21.8
500 52 21.8
ORDERING INFORMATION
Description Order Code
Cat 6A Modular Jack DC-MJRJ-C6A
Cat 6A Modular Jack Keystone DC-MJKJ-C6A
www.datacomonline.net 21
CATEGORY 6 JACK
Datacom Category 6 180º Modular Jacks Punch Down Type and category 6 keystone jack 90º comply with TIA/EIA-568-C,2-1 and
ISO/IEC 11801 for Category 6/class E component performance standards and requirements with a 180° and 90° Cable entry from
rear side respectively. The 110-IDC type connectivity is capable of terminating 22 -26 AWG The jacks are unshielded, 4-pair, RJ-45,
and are compatible with all faceplates having an aperture of 20.05x14.75.
COMPLIANCE
ANS/TIA/EIA 568C.2, ISO/IEC 11801
PHYSICAL CHARACTERISTICS
Body Material Plastic Housing ABS +PC 94V 0
Insulation Displacement Contacts Phosphor Bronze with 50Micro Inch Tin-Lead plating over 50-60 Micro Inch Nickel Plated
Insulation Displacement Cap ABS UL 94V -0
Insulation Displacement Housing Polycarbonate UL94V - 2
ELECTRICAL CHARACTERISTICS
Modular Jack 750 Mating Cycles Voltage - 150VAC max
110 Contacts - 200 Terminations
Operating Temperature - -40° - 80°C
Pull Force - 20Ibs (89N)
ORDERING INFORMATION
Description Order Code
Cat 6 Modular Jack Black DC-MJRJ-C6-BK
Cat 6 Modular Jack keystone - Black DC-MJKJ-C6-BK
22 www.datacomonline.net
CATEGORY 6A S/ FTP PATCH CORD
White/Brown White/Blue
Aluminum Foil
Jacke
Braid
White/Green Rip-cord
White/Orange
COMPLIANCE
ISO/IEC11801, TIA/EIA-568-C.2 , YD/T1019
PHYSICAL CHARACTERISTICS
Conductor Material Stranded-Bare Copper
dimension.(mm) 26AWG(7/0.16)
Insulation Material Skin-foam-skinPE
Diameter 1.00±0.05mm
Inner Screening Material Aluminum Foil Drain Wire No
Outer Screening Material Tinned copper 0.10mm Coverage ≥30%
Sheath Thickness 0.55±0.05mm
External O.D. 6.3±0.4mm
Surface Clean
Material LSZH RoHS
Core Color 1White/Blue 2 White/Orange
3White/Green 4 White/Brown
Rip-cord Yes
Sheath Physical Properties Before Aging Tensile Strength (Mpa) ≥10.0
Elongation(%) ≥125
Aging Period (°C×hrs) 100°C×24h×7d
After Aging Tensile Strength (Mpa) ≥8.0
Elongation(%) ≥100
Cold Bend (-20±2°C×4h) 8×Cable O.D., Novisible Cracks
ELECTRICAL CHARACTERISTICS
Electrical Characteristics (20°C) Delay Shew (ns/100m) ≤45 RL
Velocity of Propagation (%) 72
unbalanced-to-ground capacitance (pf/100m) max 330
DC Resistance (Ω/100m) max 14.5
DC Conductor Resistance Unbalance (%) max 5.0
www.datacomonline.net 23
TRANSMISSION CHARACTERISTICS (100m)
Frequency RL ATT NEXT PHASE DELAY PSNEXT ELFEXT PSELFEXT
(MHz) dB dB dB ns dB dB dB
1 20.0 2.1 74.3 570.0 72.3 68.0 65.0
4.0 23.0 3.8 65.3 552.0 63.3 56.0 53.0
8.0 24.5 5.3 60.8 546.7 58.8 49.9 46.9
10.0 25.0 5.9 59.3 545.4 57.3 48.0 45.0
16.0 25.0 7.5 56.2 543.0 54.2 43.9 40.9
20.0 25.0 8.4 54.8 542.1 52.8 42.0 39.0
25.0 24.3 9.4 53.3 541.2 51.3 40.0 37.0
31.25 23.6 10.5 51.9 540.4 49.9 38.1 35.1
62.5 21.5 15.0 47.4 538.6 45.4 32.1 29.1
100 20.1 19.1 44.3 537.6 42.3 28.0 25.0
200 18.0 27.6 39.8 536.5 37.8 22.0 19.0
250 17.3 31.1 38.3 536.3 36.3 20.0 17.0
300 16.8 34.3 37.1 536.1 35.1 18.5 15.5
500 15.2 45.3 33.8 535.6 31.8 14.0 11.0
ORDERING INFORMATION
Description Order Code
Cat 6A Patch Cord S/FTP,LSZH White DC-PC-RJC6A-SF-XM-LSZH-WT (X=01,02,03,05 Mtr)
Other colour and length are available upon request.
24 www.datacomonline.net
CATEGORY 6A F/UTP PATCH CORD
Conductor
Jacket
Insulation
Mylar
Seperator
Al/Mylar
TC Drain Wire
COMPLIANCE
ISO/IEC11801, TIA-568-C.2
PHYSICAL CHARACTERISTICS
Conductor Material Stranded -Bare Copper
Nom. O.D. (mm) 26AWG(7/0.16)
Insulation Material HDPE
Diameter 0.85±0.05mm
Color A.Blue, White-Blue B.Orange, White-Orange
C.Green,White-Green D.Brown, White-Brown
Rip-cord N/A Drain Wire Yes
Shielded Mylar+Al/Mylar
Sheath Thickness 0.55±0.05 mm
External O.D. 6.1±0.4 mm
Surface Clean,Frap,Satiation
Material LSZH(complies RoHS)
Sheath Physical Properties Before Aging Tensile Strength (Mpa) ≥10.0
Elongation (%) ≥125
Aging Period (°C×hrs) 100°C×24h×7d
After Aging Tensile Strength (Mpa) ≥8.0
Elongation (%) ≥100
Cold Bend (-20±2°C×4h) No Visible Cracks
ELECTRICAL CHARACTERISTICS
Electrical Characteristics (20°C) 1.0-250.0MHz, Characteristic Impedance (Ω) 100±15
1.0-250.0MHz, Delay Skew 20°C (ns/100m) ≤45
Capacitance Unbalance to Earth (pf/100m) max 330
DC Resistance 20°C(Ω/100m) max 14.8
DC Conductor Resistance Unbalance (%) max 5.0
www.datacomonline.net 25
TRANSMISSION CHARACTERISTICS (100m)
Frequency RL ATT NEXT PHASE DELAY PSNEXT ELFEXT PSELFEXT
(MHz) ≥dB ≤dB ≥dB ≤ns ≥dB ≥dB ≥dB
1 19.1 3.0 65.0 521 62.0 64.2 61.2
4.0 21.0 3.5 64.1 504 61.8 52.1 49.1
8.0 21.0 5.0 59.4 500 57.0 46.1 43.1
10.0 21.0 5.5 57.8 498 55.5 44.2 41.2
16.0 20.0 7.0 54.6 496 52.2 40.1 37.1
20.0 19.5 7.9 53.1 495 50.7 38.2 35.2
25.0 19.0 8.9 51.5 495 49.1 36.2 33.2
31.25 18.5 10.0 50.0 494 47.5 34.3 31.3
62.5 16.0 14.4 45.1 492 42.7 28.3 25.3
100 14.0 18.6 41.8 491 39.3 24.2 21.2
200 11.0 27.4 36.9 490 34.3 18.2 15.2
250 10.0 31.1 35.3 490 32.7 16.2 13.2
ORDERING INFORMATION
Description Order Code
Cat 6A Patch Cord Shielded F/UTP,LSZH White DC-PC-RJC6A-FU-XXM-LSZH-WT (XX=01,02,03,05 Mtr)
Other Colour And Length Are Available Upon Request.
26 www.datacomonline.net
CATEGORY 6A U/UTP PATCH CORD
Datacom CAT 6A UTP Patch Cords provide superior alien crosstalk suppression and protect critical data from EMI (electromag-
netic interference) and RFI (radio frequency interference). The patch cords are Cat6A compliant, 4 pair multi stranded copper
conductors with moulded boot for minimum bend radius protection.
PHYSICAL CHARACTERISTICS
Conductor Material: Stranded Bare Annealed
No:of Insulated Conductors 8
Individual Pair Sheilding Nil
Overall Pair Sheilding Nil
ELECTRICAL CHARACTERISTICS
Pulling Force: 10 N max.
Durability 1000 Mating Cycles
Impedance: 100+-_18 Ω@250-500 MHZ
Dielectric Strength: 1 KV/min.rms.
Temperature Operating Range: -20 ºC to +75 ºC
Storage Temperature Range: -20 ºC to +80 º C
PERFORMANCE CHARACTERISTICS
CAT 6A Patch Cord Requirements 100Mhz 250Mhz 500Mhz
1-Meter Patch Cord NEXT 47 39.3 28.2
2-Meter Patch Cord NEXT 46.4 38.9 28.4
5-Meter Patch Cord NEXT 45.4 38.1 29
Return Loss - All Lengths 18 14 9.5
ORDERING INFORMATION
Description Order Code
Cat6A Patch Cord White DC-PC-RJC6A-UT-XXM-WT(X=1,2,3,5 Mtr)
Cat 6A Patch Cord, LSZH, White DC-PC-RJC6A-UT-XXM-LSZH-WT (X=0l ,02,03,04,05 mtr)
Other colour and length are available upon request.
www.datacomonline.net 27
CATEGORY 6 UTP PATCH CORD
Datacom Category 6 patch cable assemblies meet the requirements for Category 6 performance. The Datacom Category 6 UTP
system complies with all of the performance requirements for current applications such as 1000Base-T Gigabit Ethernet,
100Base-TX, Token Ring, ATM LAN 1.2 Gbps, 155 Mbps ATM, 100 Mbps TPPMD, ISDN, analog (broadband, baseband) and digital
video and analog and digital (VolP) voice.
COMPLIANCE
ANSI/TIA 568-C.2, ISO/IEC 11801 Class, EN 50173-1
PHYSICAL CHARACTERISTICS
Connector RJ45 Plug
1.1 Housing Polycarbonate, UL 94V-2, Transparent
1.2 Contact Material Terminals Phosphor Bronze with 50-60 Micro inch Nickel Plated
1.3 Contact Finish Min 50 Micro-inch, Gold Plated
Cable Conductor UTP Stranded Copper Wire UL Material Approved, AWG 24 Jacket
ELECTRICAL CHARACTERISTICS
Impedance up to 250 MHz 100 C) Transmission characteristics (exceed ISO/IEC 11801 2nd edition Category 6)
NEXT (dB)
Frequency Return Loss 1m 2m 5m 10 m
1 19.8 65.0 65.0 65.0 65.0
16 23.4 62.5 61.7 60.1 58.6
50 21.0 52.7 52.0 50.6 49.5
100 18.0 46.8 46.2 45.0 44.2
150 16.2 43.4 42.8 41.8 41.2
200 15.0 41.0 40.5 39.6 39.1
250 14.0 39.1 38.6 37.9 37.6
ORDERING INFORMATION
Description Order Code
Cat 6 UTP RJ45 to RJ 45 Patch Cord, PVC, White DC-PC-RJC6-XM-WT (X=0l ,02,03,04,05 mtr)
Cat 6 UTP RJ45 to RJ 45 Patch Cord, LSZH, White DC-PC-RJC6-XM-LSZH-WT (X=0l ,02,03,04,05 mtr)
Other colour and length are available upon request.
28 www.datacomonline.net
19” PATCH PANEL UNLOADED
Datacom patch panel is field configurable. It mounts on 19”wide equipment racks, Accepts the modular and keystone jacks. The
customer has got the option to buy unloaded frame and modules for increased flexibility. Designed with front write on label
areas.
PHYSICAL CHARACTERISTICS
Panel Style Blank
Panel Type Flat
Termination Style Punch Down (Module)
Panel Width 483mm (19”)
Panel Height (1U, 2U )
Outlet Style RJ-45
Outlets 16,24,48 Ports
Connector Module Holder High Impact, Flame-Retardant Plastic Compound, Ul 94 V-0
Cover Colour and Material Black, Powder Coated Steel
ORDERING INFORMATION
Description Order Code
1U 24 Port Keystone Panel with Support - Black DC-PPU19-24BK
2U 48 Port Keystone Panel with Support - Black DC-PPU19-48BK
1U 16 Port Keystone Panel with Support - Black DC-PPU19-16BK
1U 24 Port Shielded Patch Panel. DC-PPU19-24BK-SH
1U 24 Port Angled Patch Panel DC-PPU19-24BK-A
2U 48 Port Angled Patch Panel DC-PPU19-48BK-A
www.datacomonline.net 29
12” PATCH PANEL UNLOADED
Datacom Patch panel is field configurable. It mounts on 12” wide equipment racks, Accepts The modular and keystone jacks. The
customer has got the option to buy unloaded frame and modules for increased flexibility. Designed with front write on label
areas.
PHYSICAL CHARACTERISTICS
Panel Style Blank
Panel Type Flat
Termination Style Punch Down Module
Panel Width 12”
Panel Height 44.4mm (1U)
Outlet Style RJ-45
Outlets 12 Ports
Cover Color and Material Gray
ORDERING INFORMATION
Description Order Code
1U 12 Port Keystone Panel 12”-Gray DC-PPU-12-12GY
1U 12 Port Keystone Panel 12”-Black DC-PPU-12-12CM
30 www.datacomonline.net
CATEGORY 6 MODULAR RJ 45 PANEL
Datacom Category 6 patch panel is manufactured and tested for category 6 performance. It mounts on 19”wide equipment
racks, Designed with front write on label areas.
COMPLIANCE
ANSI/TIA/EIA 568 C2 ISO/IEC 1180/Class E, EN 50173
PHYSICAL CHARACTERISTICS
Panel Style Loaded
Panel Type Flat
Termination Style Punch Down (110)
Panel Width 483mm (19”)
Panel Height 44.4mm (1U)
Outlet Style Unkeyed RJ-45
Outlets 24 Ports
Connector Module Holder High Impact, Flame-Retardant Plastic Compound, Ul 94 V-0
Cover Colour and Material Black, Powder Coated Steel
ORDERING INFORMATION
Description Order Code
19" 24 Port Cat 6 Patch Panel 1U BK with Slim Line Modular Jack DC-PPL-C624
19" 48 Port Cat 6 Patch Panel 1U BK with Slim Line Modular Jack DC-PPL-C648
www.datacomonline.net 31
VOICE PANEL
Datacom 110-Style Voice Grade Patch Panel is specifically designed for voice application. It is designed for use with high pair
count multipair Cat 3 cables.
PHYSICAL CHARACTERISTICS
Panel SPCC,1,2mm Thickness with Black(RAL 9005) Color Painted
RJ 45 Jack Housing: PBT+Glass Fiber, UL 94V-0
Contact Bracket: PBT+Glass Fiber, UL 94V-0
RJ 45 Jack Contact Material: Phosphor Bronze with Nickel Plated
Finish: Gold Flush Plated on Plug Contact Area
IDC Housing: PBT+Glass Fiber, UL 94V-0
Terminal: Phosphor Bronze with Tin Plated
PCB CEM-1, UL 94V-0
PERFORMANCE CHARACTERISTICS
Insertion Force 20N max (IEC60603-7-4)
Retention Strength 7.7kg between jack and Plug
Operating Temperature -10 °C to +60 °C
Life (Mating Cycles) Jack: 750 Cycles min (ISO/IEC 11801,IEC 60603-7-4
IDC:Suitable for 22-26 AWG Stranded and Solid Wire,
Compatible with both 110 & Krone Punch Down Tools
ORDERING INFORMATION
Description Order Code
Voice Panel Cat 3, 1U Black, 25 Port DC-VPL25-C3BK
Voice Panel Cat 3, 1U Black, 50 Port DC-VPL50-C3BK
32 www.datacomonline.net
110 WIRING BLOCK RACK MOUNT
Datacom 110 style Cross connect rack mount wiring block provide fixed terminations that support high speed data, voice and
security solutions. They are made of fire retardant plastic and comply with TIA/EIA-568-B2requirements.
110 wiring system is the ideal way of terminating cable for cross-connecting data and Voice, offering reliable and economical
high-density system. The rack mount wiring block is available without legs. Cable access openings allow cables to be routed
through wiring blocks directly to point of termination. The speedy punch down on the block base ensures reduction in installa-
tion time and cost. The termination of cable on 110 wiring blocks is achieved with the use of 110 tools. The blocks are available
in 96 and 192 pairs without legs.
PHYSICAL CHARACTERISTICS
Material of Construction High Impart, Flame rRetardant PC
Conductor Diameter Solid Wire 0.50 to 0.65mm
Conductor Diameter Stranded Wire 7x0.2 to 0.25mm
Wire Gauge Range 22-26AWG
Insulation Diameter Range 0.6 mm to 1.6mm
Contact Resistance 20m
Insulation Resistance 500M min@100Vdc
Spring Contacts 1.25μm min. Silver Plated
ORDERING INFORMATION
Description Order Code
Wiring Block 96 Pair 19" Rack MT C6 DC-WB19-096-C6
Wiring Block 192 Pair 19" Rack MT C6 DC-WB19-192-C6
www.datacomonline.net 33
110 WIRING BLOCK WALL MOUNT
Datacom 110 style Cross connect wall mount wiring block provide fixed terminations that support high speed data, voice and
security solutions. They are made of fire retardant plastic and comply with TIA/EIA-568-B2requirements.
110 wiring system is the ideal way of terminating cable for cross-connecting data and Voice, offering reliable and economical
high-density system. The wall mount wiring block is available with legs. Cable access openings allow cables to be routed
through wiring blocks directly to point of termination. The speedy punch down on the block base ensures reduction in installa-
tion time and cost. The termination of cable on 110 wiring blocks is achieved with the use of 110 tools. The blocks are available
in 48 and 96 pair with legs.
PHYSICAL CHARACTERISTICS
Material of Construction High Impart, Flame Retardant PC
Conductor Diameter Solid Wire 0.50 to 0.65mm
Conductor Diameter Stranded Wire 7x0.2 to 0.25mm
Wire Gauge Range 22-26AWG
Insulation Diameter Range 0.6 mm to 1.6mm
Contact Resistance 20m
Insulation Resistance 500M min@100Vdc
Spring Contacts 1.25μm min. Silver Plated
ORDERING INFORMATION
Description Order Code
Wiring Block 48 Pair with Legs Cat 6 DC-WBWL-048-C6
Wiring Block 96 Pair with Legs Cat 6 DC-WBWL-096-C6
34 www.datacomonline.net
CONNECTING BLOCKS
Datacom 110 block is used to connect sets of wires in a structured cabling system. The "110" designation is also used to describe
a type of insulation displacement connector to terminate twisted pair cables.
PHYSICAL CHARACTERISTICS
Depth 23.62 mm
Height 6.35 mm | 0.25 in
Width 30.48 mm | 1.20 in
Operating Temperature -10 °C to +60 °C
Product Type Block
Color White
Material Type Copper Alloy
Outlet/Module Contact Plating Nickel
Plug Insertion Life, Minimum 200 Times
ORDERING INFORMATION
Description Order Code
4 Pair Connecting Block Cat6 DC-CB4P-C6
www.datacomonline.net 35
110 PATCH CORD
Datacom 110 Patch Cord incorporates crossover Lead design, which employs crosstalk cancellation techniques to provide superi-
or Near-End Crosstalk (NEXT) performance. These 110 Patch Cords are available in 2, or 4 pair sizes.
Category 6 110 Patch Cords: Category 6 110 Patch Cords exceed performance specifications as defined in ANSI/TIA-568-C.2.
Patch cords are available with four-pair 110 plugs and are used for patching between category 6 110 termination fields. Catego-
ry 6 RJ-45/110 Patch Cords are available in four-pair configurations wired to T568B wiring scheme. RJ-45/110 Patch Cords are
used for patching between equipment and category 6 110 termination fields. All cords are 100% factory performance tested.
110-110 Patch Cord: The 110 to 110 patch cords contain two 110 connectors and provide reliable connections between 110
termination blocks..
110-RJ45 Patch Cord: The 110 to RJ45 patch cords connect a 110 connector to an 8 position modular jack. These cords are availa-
ble wired as T568A and T568B.
PHYSICAL CHARACTERISTICS
Component: Four-pair Cat6 cable, Four-pair Cat5e cable
Eight-contact male 110 plug
Cross Talk Compensation Board
Finish Plating2: Tin Lead Contact Plating
Material: 24 AWG Bare Copper Stranded Conductors, PVC Insulation, PVC Jacket
Phosphor-bronze Contacts, Nylon Housing
FR1 Double-sided Printed Circuit Board
ORDERING INFORMATION
Description Order Code
2 Pair 110-110 Cat 6-2mts DC-PC-XCXC-2-C6-02
4 Pair 110-110 Cat 6-2mts DC-PC-XCXC-4-C6-02
2 Pair 110-RJ45 Cat 6-2mts DC-PC-XCRJ-2-C6-02
4 Pair 110-RJ45 Cat 6-2mts DC-PC-XCRJ-4-C6-02
36 www.datacomonline.net
FACEPLATES
FLOOR MODULES
Description Order Code
Single Shut Angled Floor LJ6C 22x37mm DC-MLJ06 - XXX
3” X 3” BACK BOX
Description Order Code
Back Box 86X86X42mm DC-BBX86-42XX
Single Shut Angled Floor Module LJ6 22x37mm DC-MLJ06-XXX
www.datacomonline.net 37
MODULAR PLUGS CAT6
COMPLIANCE
ANSI/TIA - 568-C.2, TIA-968-A, CE, FCC, UL, RoHs
PRODUCT DESCRIPTION
• Exclusive stagger conductors guide design reduces near end cross talk
• For Cat6 UTP cable.
• Meet the requirement in the cat6 T568C.2
• Featuring gold plated contacts for the best possible connection.
• Conductor:Solid and stranded cable
• Available for RoHS parts
• Can make your network function to its maximum potential
CONFIGURATION FEATURES
Number of Positions 8P8C
CONTACT FEATURES
Contact Base Material Phosphor Bronze
Contact Mating Area Plating Material Gold
Contact Mating Area Plating Thickness 3-50”
CABLE DIMENSIONS
Compatible Insulated Conductor Diameter Maximum 0.990 mm
Compatible Insulated Conductor Diameter Minimum 0.790 mm
SPECIFICATION
StorageTemperature -40°C~+70°C
Insulation Resistance 1000MΩ Min
Dielectric Withstanding Voltage AC 500V Per Minute
Contact Resistance 20mΩ Max.(Initial)
Operating Temperature -20°C~+60°C
HOUSING FEATURES
Housing Color Thermoplastic(UL 94V-0) or Custometed
Housing Material PC or ABS
ORDERING INFORMATION
Description Order Code
Modular Plugs Cat6 RJ45 8P8C DC-MPC6-8P8CU
38 www.datacomonline.net
MODULAR PLUGS CAT6A
COMPLIANCE
ANSI/TIA - 568-C.2, TIA-968-A, CE, FCC, UL, RoHs
PRODUCT DESCRIPTION
• Exclusive stagger conductors guide design reduces near end cross talk
• For Cat6A UTP cable.
• Meet the requirement in the cat6A T568C.2
• Featuring gold plated contacts for the best possible connection.
• Conductor:Solid and stranded cable
• Available for RoHS parts
• Can make your network function to its maximum potential
CONFIGURATION FEATURES
Number of Positions 8P8C
CONTACT FEATURES
Contact Base Material Phosphor Bronze
Contact Mating Area Plating Material Gold
Contact Mating Area Plating Thickness 3-50”
CABLE DIMENSIONS
Compatible Insulated Conductor Diameter Maximum 1.090 mm | 0.043 in
Compatible Insulated Conductor Diameter Minimum 0.890 mm | 0.035 in
SPECIFICATION
StorageTemperature -40°C~+70°C
Insulation Resistance 500MΩ Min
Dielectric Withstanding Voltage AC 500V Per Minute
Contact Resistance 20mΩ Max.(Initial)
Operating Temperature -20°C~+60°C
HOUSING FEATURES
Housing Color Thermoplastic(UL 94V-0) or Custometed
Housing Material PC or ABS
ORDERING INFORMATION
Description Order Code
Modular Plugs Cat6A RJ45 8P8C DC-MPC6A-8P8CU
www.datacomonline.net 39