Detailed System Cooling Performance Data
Ducted Split System
53QDMT48-518A6 Heat Pump 42QDMT48-718A6
380-415V / 3Ph / 50Hz 38QDMT48-518A6
Indoor Conditions Outdoor Ambient Temperature
ESP Wet Temp. °C 35°C 43°C 46°C 52°C
Fan Air Capacity Capacity Capacity Capacity
Input Input Input Input
in.wg Speed Flow DB WB Btu/hr Btu/hr Btu/hr Btu/hr
W W W W
Pa cfm Total Sensible Total Sensible Total Sensible Total Sensible
1377 21 15 44695 36885 4585 40150 35550 5185 38435 35045 5410 35025 34040 5860
cfm 24 17 46105 38440 4885 41415 37050 5525 39650 36520 5765 36130 35475 6245
High
650 27 19 47045 38825 4985 42260 37420 5635 40460 36885 5880 36865 35830 6370
L/S 1 23 47985 45430 5235 43105 43780 5920 41270 43160 6175 37610 37610 6690
0.30 1195 21 15 42955 34045 4555 38580 32815 5150 36940 32345 5375 33660 31420 5820
in.wg cfm 24 17 44305 35480 4850 39800 34195 5485 38105 33710 5725 34720 32740 6200
Medium
564 27 19 45210 35840 4950 40610 34535 5600 38880 34045 5840 35430 33070 6325
75 L/S 32 23 46115 41930 5195 41425 40410 5880 39660 39840 6135 36140 34715 6645
Pa
1029 21 15 39775 29350 4435 35730 28285 5015 34205 27880 5235 31170 27085 5670
cfm 24 17 41030 30585 4725 36855 29475 5345 35285 29060 5575 32155 28225 6040
Low
485 27 19 41865 30890 4820 37605 29770 5450 36005 29350 5690 32810 28505 6160
L/S 32 23 42705 36145 5060 38360 34835 5725 36725 34340 5975 33465 29925 6470
1285 21 15 43550 35940 4675 39120 34640 5290 37450 34145 5520 34125 33165 5975
cfm 24 17 44925 37455 4980 40355 36100 5635 38635 35585 5875 35205 34565 6365
High
606 27 19 45840 37830 5080 41175 36460 5745 39425 35940 5995 35920 34910 6495
L/S 32 23 46755 44265 5335 42000 42655 6035 40210 42055 6300 36645 36645 6820
0.40 1084 21 15 41850 33175 4645 37595 31970 5250 35990 31515 5480 32795 30615 5935
in.wg cfm 24 17 43170 34570 4945 38780 33320 5595 37130 32845 5835 33830 31900 6325
Medium
511 27 19 44050 34920 5045 39570 33650 5705 37885 33175 5955 34520 32220 6450
100 L/S 32 23 44935 40855 5300 40365 39375 5995 38645 38815 6255 35215 33825 6775
Pa
918 21 15 38755 28595 4525 34810 27560 5115 33330 27170 5335 30370 26390 5780
cfm 24 17 39975 29800 4820 35910 28720 5450 34380 28315 5685 31330 27500 6160
Low
433 27 19 40795 30100 4915 36640 29010 5560 35080 28595 5800 31965 27775 6285
L/S 32 23 41610 35215 5160 37375 33940 5840 35785 33460 6090 32610 29155 6600
1084 21 15 42405 34995 4765 38090 33730 5390 36465 33245 5625 33230 32295 6090
cfm 24 17 43740 36470 5075 39290 35150 5740 37620 34650 5990 34280 33655 6490
High
511 27 19 44635 36835 5180 40090 35500 5860 38385 34995 6110 34975 33990 6620
L/S 32 23 45525 43100 5440 40895 41535 6150 39155 40950 6420 35680 35680 6955
0.50 998 21 15 40750 32300 4735 36605 31130 5355 35045 30685 5585 31935 29810 6050
in.wg cfm 24 17 42035 33665 5040 37760 32440 5700 36150 31980 5950 32940 31065 6445
Medium
471 27 19 42895 34000 5145 38530 32765 5815 36890 32300 6070 33615 31375 6575
125 L/S 32 23 43750 39780 5400 39300 38335 6110 37625 37795 6375 34290 32935 6905
Pa
793 21 15 37735 27845 4610 33895 26835 5215 32450 26455 5440 29570 25695 5890
cfm 24 17 38925 29015 4910 34965 27965 5555 33475 27570 5795 30505 26775 6275
Low
374 27 19 39720 29310 5010 35680 28245 5665 34160 27845 5910 31125 27045 6405
L/S 32 23 40515 34290 5260 36395 33045 5950 34840 32580 6210 31750 28390 6725
( 48 )
Detailed System Cooling Performance Data
Ducted Split System
53QDMT48-518A6 Heat Pump 42QDMT48-718A6
380-415V / 3Ph / 50Hz 38QDMT48-518A6
Indoor Conditions Outdoor Ambient Temperature
ESP Temp. °C 35°C 43°C 46°C 52°C
Wet
Fan Capacity Capacity Capacity Capacity
Air Input Input Input Input
in.wg Speed DB WB Btu/hr Btu/hr Btu/hr Btu/hr
Flow W W W W
Pa Total Sensible Total Sensible Total Sensible Total Sensible
937 21 15 41260 34050 4855 37060 32815 5490 35480 32350 5730 32330 31420 6205
cfm 24 17 42560 35485 5170 38230 34200 5850 36600 33710 6105 33350 32745 6610
High
442 27 19 43430 35840 5275 39010 34540 5970 37350 34050 6230 34030 33075 6745
L/S 32 23 44295 41935 5540 39790 40415 6270 38095 39840 6540 34715 34715 7085
0.60 833 21 15 39650 31430 4820 35615 30290 5455 34095 29860 5690 31070 29000 6165
in.wg cfm 24 17 40900 32755 5135 36740 31565 5810 35175 31115 6060 32050 30225 6565
Medium
393 27 19 41735 33080 5240 37485 31880 5925 35890 31430 6185 32705 30525 6700
150 L/S 32 23 42570 38705 5505 38240 37300 6225 36610 36775 6495 33360 32045 7035
Pa
672 21 15 36715 27090 4695 32980 26110 5310 31575 25740 5540 28770 25000 6005
cfm 24 17 37875 28235 5005 34020 27210 5660 32570 26825 5905 29680 26055 6395
Low
317 27 19 38645 28515 5105 34715 27480 5775 33235 27090 6025 30285 26315 6525
L/S 32 23 39420 33365 5360 35410 32155 6060 33900 31700 6325 30895 27620 6850
1. Legned :
DB — Dry-Bulb Temperature cfm — cubic feet per minute in.wg — inch water gage
WB — Wet-Bulb Temperature L/S — Litre per second Pa — Pascal
2. Formulas :
Leaving DB = Entering DB - { Sensible Heat Capacity / (1.09 x cfm) }
Leaving WB = WB corresponding to air leaving coil enthalpy ( hwb Leaving )
hwb Leaving = hwb Entering - { Total Capacity (Btuh)/(4.5 X cfm) }
3. Tolerance
Tolerance for Wet Air Flow is 5% Tolerance for Total Cooling Capacity is 5%
Tolerance for Sensible Cooling Capacity is 5%