Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

TA-Smart EN Low

Download as pdf or txt
Download as pdf or txt
You are on page 1of 8

TA-Smart

Smart valves
2-way control valve with uniquely shaped EQM
characteristics with flow, temperature and power
measurement capabilities
IMI TA / Smart control / TA-Smart

TA-Smart
The ultrasonic flow measurement technology combined with unique
actuation algorithms capabilities provide best-in-class control
performances. The TA-Smart controls can be set to flow or power,
giving high on-site flexibility and providing highly effective comfort in
heating and cooling applications. Its compact arrangement and simple
set-up reduces installation and commissioning time.

Key features
> Best-in-class control > Change-over functionality > Convenient, reliable setup
Accurate and fast control response Possibility to switch between two Fully customizable and
even at very low flows in common operating conditions to manage commissionable using Bluetooth
part load conditions. Ensures full seasonality or heating and cooling enabled smart device reducing
modulating control for the complete with the same valve in change-over commissioning and diagnostic time.
operating stroke leading to world class applications.
control and efficiencies. > Easy diagnostics
> High measurement accuracy Continuous measurement (flow,
> Optional cloud connection High flow and temperature temperature, power...) enables
Easy remote access to data and measurement accuracies in all accurate error identification in system
configuration parameters allows to configurations (medium type, and hydronics.
verify and adjust system performance. temperature) for all flow regimes.
> Versatility in communication
> Optional ΔT and temperature > Compactness and limited number Digital (key Bus protocols and MQTT)
return limitation of components and Analog (0(2)-10 VDC or 0(4)-20 mA).
Optimize the efficiency of your Reduces installation time and space
production units by ensuring optimal requirements facilitating retrofit
temperature regimes. installation.

Technical description

Application: Differential pressure (ΔpV): Measurement accuracy:


Heating and cooling systems. Max. differential pressure (ΔpVmax): Flow:
400 kPa = 4 bar Water: From 2% accuracy at 100% of
Functions: Closing pressure: 600 kPa = 6 bar qnom to 2.4% accuracy at 5% of qnom
Control (flow, power, position) ΔpVmax = The maximum allowed pressure (according MID-Class 2 EN1434).
Pre-setting (max./min. flow, max. power, drop over the valve to fulfill all stated Water+glycol: From 3% accuracy at
max./min. position) performances. 100% of qnom to 4% accuracy at 5% of
ΔT and temperature return limitation qnom (according to MID-Class 3 EN1434).
Reading (flow, power, energy, supply/ Flow range: (see “Flow accuracy”)
return temperature, ΔT, position) The flow ranges (qsetmin - qnom) for different Temperature difference:
Change-over function dimensions: ±0.1 K @ ΔT = 6 K (for cooling)
Manual override (via HyTune app) DN 20: 380 - 1900 l/h ±0.15 K @ ΔT = 10 K (for heating)
Mode, status and position indication DN 25: 540 - 2700 l/h ±0.2 K @ ΔT = 20 K (for heating)
Valve blockage protection DN 32: 920 - 4600 l/h
Valve clogging detection DN 40: 1560 - 7800 l/h Flow control accuracy:
Error safe position DN 50: 2680 - 13400 l/h ±5% from 4% to 100% of qnom
Diagnostic DN 65: 5800 - 29000 l/h ±10% from 0.5% to 4% of qnom
Logging DN 80: 8640 - 43200 l/h
Delayed start-up DN 100: 14200 - 71000 l/h Temperature:
DN 125: 22400 - 112000 l/h Max. working temperature: 110°C
Dimensions: Minimum controllable flows (qcontr.min) 0.5% Min. working temperature: -10°C
DN 20-125 of qnom. Operating environment: 0°C – +50°C
qsetmin = Minimum settable flow. (5-95%RH, non-condensing)
Pressure class: qnom = Maximum settable flow. Storage environment: -20°C – +70°C
DN 20-50: PN 25 (5-95%RH, non-condensing)
DN 65-125: PN 16, PN 25

2
Media: Output signal: Surface treatment:
Water or neutral fluids, water-glycol BACnet/Modbus DN 20-50: Non treated
mixtures (0-57%). 0(2)-10 VDC, max. 8 mA, min. 1.25 kΩ. DN 65-125: Electrophoretic painting

Leakage rate: Wireless: Marking:


DN 20-50: Leakage rate <0.01% of Bluetooth Low Energy (BLE) Valve body:
qnom with correct flow direction (Class IV Thread DN 20-50: IMI TA, PN, DN, inch size,
according to EN 60534-4) country of origin and flow direction arrow.
DN 65-125: Tight sealing with correct Temperature sensor cable: DN 65-125: IMI TA, DN, inch size,
flow direction (Class V according to DN 20-50: 3 m halogen free material and flow direction arrow. Label
EN 60534-4) DN 65-125: 5 m halogen free with technical specification, country of
10 m halogen free cable on request. origin and CE.
Characteristics: SmartBox: IMI TA
Settable: Stepless between EQM 0.25 Ingress protection: Actuator: IMI TA, model, technical spec.,
and inverted EQM 0.25. IP54 (according to EN 60529) LED info.

Supply voltage: Protection class: Pipe connection:


24 VAC/VDC ±15%. (according to EN 61140) DN 20-50: External thread according to
Frequency 50/60 Hz ±3 Hz. III (SELV) ISO 228.
NOTE: 24 VAC/VDC power supply must DN 65-125: Flanges according to
be provided only with safety isolating Material: EN-1092-2, type 21. Face to face length
transformer according to EN 61558-2-6. DN 20-50: according to EN 558, series 1.
Valve body: AMETAL®
Power consumption: Valve insert: AMETAL® Certification and directives:
DN 20-50: Valve plug: AMETAL® and PTFE EMC-D. 2014/30/EU: EN 60730-1, -2-14.
Operation: < 4.0 W (24 VDC); Spindle: Stainless steel Product standards EN 60730-x.
< 5.6 VA (24 VAC) Spindle seal: EPDM O-ring PED: 2014/68/EU
Standby: < 1.9 W (24 VDC); Internal plastic parts: PPS
< 3.3 VA (24 VAC) Springs: Stainless steel
DN 65-80: O-rings: EPDM
Operation: < 5.8 W (24 VDC);
< 10 VA (24 VAC) Temperature housing: AMETAL®.
Standby: < 1.9 W (24 VDC);
< 3.3 VA (24 VAC) DN 65-125:
DN 100-125: Valve body: Ductile iron EN-GJS-400-15
Operation: < 7.7 W (24 VDC); Valve insert: Ductile iron EN-GJS-400-15
< 10.8 VA (24 VAC) and brass
Standby: < 1.9 W (24 VDC); Valve plug: Stainless steel and EPDM
< 3.3 VA (24 VAC) O-ring
Valve seat: Stainless steel
Input signal: Spindle: Stainless steel
By BACnet/Modbus or Analog signal. Spindle seal: EPDM
Analog in VDC or mA, selectable by Springs: Stainless steel
jumper in the SmartBox; O-rings: EPDM
0(2)-10 VDC, Ri 47 kΩ.
Adjustable sensitivity 0.1-0.5 VDC. SmartBox (DN 20-125):
0.33 Hz low pass filter. Cover: PC/ABS, red.
0(4)-20 mA Ri 500 Ω. Housing: PC/ABS, TPE.
Proportional:
0-10, 10-0, 2-10 or 10-2 VDC. Actuators:
0-20, 20-0, 4-20 or 20-4 mA. DN 20-50:
Proportional split-range: Cover: PC/ABS GF8, white RAL 9016,
0-5, 5-0, 5-10 or 10-5 VDC. grey RAL 7047.
0-4.5, 4.5-0, 5.5-10 or 10-5.5 VDC. Housing: PA GF40.
2-6, 6-2, 6-10 or 10-6 VDC. Swivelling nut: Nickel-plated brass.
0-10, 10-0, 10-20 or 20-10 mA. DN 65-125:
4-12, 12-4, 12-20 or 20-12 mA. Cover: PBT, orange RAL 2011, grey
Proportional dual-range (for change-over): RAL 7043.
0-4.5 / 5.5-10 VDC. Bracket: Alu EN44200
2-5.5 / 6.5-10 VDC.
0-3.3 / 6.7-10 VDC. Cables: Halogen free
2-4.7 / 7.3-10 VDC.
0-9 / 11-20 mA. AMETAL® is the dezincification resistant
4-11 / 13-20 mA. alloy of IMI Hydronic Engineering.
Default setting: Proportional 0-10 VDC.
3
IMI TA / Smart control / TA-Smart

Flow accuracy
± [%]
10
9
8
7
6
5
4
3 H2O + glycol mix.
2 H 2O
1
0
0 10 20 30 40 50 60 70 80 90 100
q/qnom [%]

Installation

DN 20-50 DN 65-125 DN 20-50

0 DN 0 DN  10 DN 0 DN

DN 65-125

 5 DN 0 DN  10 DN 0 DN

Note: Free space is required above the actuator/temperature


DN 20-50
sensor pocket for easy mounting/dismounting.
DN 20-50 DN 65-125

>20 mm >140 mm

DN 65-125

>70 mm

4
Articles

TA-Smart DN 20-50
>20 mm 3 m
Including temperature housing and 3 m temperature sensor cable.
W (10 m cable on request, please contact IMI Hydronic Engineering)
H External threads according to ISO 228.

DN D L H W Kvs Kg EAN Article No


D
20 G1 180 174 97 3,15 1,6 7318794174207 322231-00020
L 25 G1 1/4 187 174 97 4,35 1,8 7318794174306 322231-00025
32 G1 1/2 200 199 97 7,28 2,1 7318794164307 322231-00032
8 >70 mm 40 G2 218 198 97 12,3 3,0 7318794164406 322231-00040
50 G2 1/2 239 198 97 21,2 3,9 7318794164505 322231-00050
7 D1 H1

G1/16
L1

Temperature housing incl. temperature sensor pocket


Included in TA-Smart/-Dp DN 20-50.
Internal threads according to ISO 228.
DN D1 L1 H1
20* G3/4 60 56
25 G1 62 61
32 G1 1/4 66 70
40 G1 1/2 67 76
50 G2 68 89

*) Can be connected to smooth pipes by KOMBI compression coupling.

TA-Smart DN 65-125
Including temperature sensor pocket and 5 m temperature sensor cable.
(10 m cable on request, please contact IMI Hydronic Engineering)
>140 mm
Free space >70 mm is required above the temperature pocket.
5m Flanges according to EN-1092-2, type 21.

DN Number of D L H Kvs Kg EAN Article No


bolt holes
H
PN 16
65 4 185 290 377 49 16,5 7318794171206 322231-01265
80 8 200 310 380 73 18,6 7318794171305 322231-01280
ØD 100 8 220 350 438 120 29 7318794176904 322231-01290
125 8 250 400 444 190 35 7318794177000 322231-01291
L PN 25
65 8 185 290 377 49 16,5 7318794170803 322231-01365
80 8 200 310 380 73 18,6 7318794170902 322231-01380
100 8 235 350 438 120 29 7318794177307 322231-01390
125 8 270 400 444 190 35 7318794177406 322231-01391

→ = Flow direction

Kvs = m3/h at a pressure drop of 1 bar and fully open valve.

5
IMI TA / Smart control / TA-Smart

Accessories

Temperature sensor
Included in TA-Smart/-Dp.
(10 m cable on request, please contact IMI Hydronic Engineering)
Tool for exchanging temperature sensor is included.

For DN Length [m] EAN Article No


20-25 3 7318794178229 322230-01106
32-50 3 7318794173705 322230-01100
65-125 5 7318794173804 322230-01101

Temperature sensor pocket


DN 20-80 DN 100-125 Included in TA-Smart/-Dp DN 65-125.
For mounting directly on pipe. Free space >70 mm is required above the temperature sensor pocket.
D D
For DN D L EAN Article No
20-25 G1/4 14 7318794174603 322230-00401
L
L 20-25 G1/2 14 7318794178199 322230-00403
32-80 G1/4 30 7318794174009 322230-00400
32-80 G1/2 30 7318794178205 322230-00404
100-125 G3/8 58 7318794178175 322230-00402

Temperature housing incl. temperature sensor pocket


Included in TA-Smart DN 20-50.
To be ordered separately if the pipe size does not match the valve size.
Internal threads according to ISO 228.
>70 mm
DN D1 L1 H1 EAN Article No
20* G3/4 60 56 7318794174900 322230-00020
D1 H1 25 G1 62 61 7318794175006 322230-00025
32 G1 1/4 66 70 7318794171404 322230-00032
G1/16 40 G1 1/2 67 76 7318794171503 322230-00040
L1 50 G2 68 89 7318794171602 322230-00050

*) Can be connected to smooth pipes by KOMBI compression coupling.

Service tool

EAN Article No
For exchange of temperature sensor 7318794178144 322033-00000
For exchange of TA-Slider cable 7318794178151 322033-00001

Insulation
For heating and non-condensing cooling applications.
W
Material: EPP.
Fire class: E (EN 13501-1), B2 (DIN 4102).

For DN L H W Ø EAN Article No


20 215 112 76 69 5902276819681 322230-00620
25 225 119 86 82 5902276819698 322230-00625
L Ø H 32 238 153 92 96 5902276819438 322230-00632
40 256 168 110 114 5902276819360 322230-00640
50 284 183 134 143 5902276819377 322230-00650

6
Connections

DN 20-32
With internal thread
Threads according to ISO 228. Thread length according to ISO 7-1. Swivelling nut. Brass/AMETAL®
D D1
For DN D D1 L* EAN Article No
L 20 G1 G3/4 23 7318794017009 52 163-020
DN 40-50 25 G1 1/4 G1 23 7318794017108 52 163-025
32 G1 1/2 G1 1/4 31 7318794017207 52 163-032
D
40 G2 G1 1/2 30 7318794032705 52 163-040
D1
50 G2 1/2 G2 32 7318794032804 52 163-050

With external thread


D D1 Threads according to ISO 7-1. Swivelling nut. Brass

For DN D D1 L* EAN Article No


L
20 G1 R3/4 32,5 4024052516810 0601-03.350
25 G1 1/4 R1 35 4024052517015 0601-04.350
32 G1 1/2 R1 1/4 38,5 4024052517213 0601-05.350

Welding connection
Swivelling nut. Brass/Steel 1.0045 (EN 10025-2)

For DN D Pipe DN L* EAN Article No


L
20 G1 20 40 7318792748608 52 009-020
25 G1 1/4 25 40 7318792748707 52 009-025
32 G1 1/2 32 40 7318792748806 52 009-032
40 G2 40 45 7318792748905 52 009-040
50 G2 1/2 50 50 7318792749001 52 009-050

Soldering connection
Swivelling nut. Brass/gunmetal CC491K (EN 1982)

For DN D Pipe Ø L* EAN Article No


L
20 G1 18 15 7318792749506 52 009-518
20 G1 22 18 7318792749605 52 009-522
25 G1 1/4 28 21 7318792749704 52 009-528
32 G1 1/2 35 26 7318792749803 52 009-535
40 G2 42 30 7318792749902 52 009-542
50 G2 1/2 54 35 7318792750007 52 009-554

Connection with smooth end


For connection with press coupling. Swivelling nut. Brass/AMETAL®

For DN D Pipe Ø L* EAN Article No


L
20 G1 18 44 7318793810700 52 009-318
20 G1 22 48 7318793810809 52 009-322
25 G1 1/4 28 53 7318793810908 52 009-328
32 G1 1/2 35 59 7318793811004 52 009-335
40 G2 42 70 7318793811103 52 009-342
50 G2 1/2 54 80 7318793811202 52 009-354

*) Fitting length (from the gasket surface to the end of the connection).

7
IMI TA / Smart control / TA-Smart

The products, texts, photographs, graphics and diagrams in this document may be subject to
alteration by IMI Hydronic Engineering without prior notice or reasons being given. For the most up
to date information about our products and specifications, please visit www.imi-hydronic.com.
TA-Smart EN ed.6 04.2023

You might also like