TTH300

Download as pdf or txt
Download as pdf or txt
You are on page 1of 24

Data Sheet DS/TTH300-EN Rev.

TTH300
Head-mount temperature transmitter

Temperature transmitter for all


communication protocols.
ABB common operating concept.
Redundancy when two sensors are
connected.

Measurement made easy

Communication / output Device safety in accordance with NE 53 and NE 79


— 4 to 20 mA, HART protocol, rev. 5 and rev. 7 switchable
— PROFIBUS PA Functional safety
— FOUNDATION Fieldbus — SIL 2 / SIL 3 in accordance with IEC 61508 (for HART)

Input Configuration
— RTD, resistance thermometers, resistance-type remote — FIM
sensor — DTM
— Thermocouples, voltages, mV voltages — EDD
— LCD display with push buttons (optional)
Electrical isolation of input circuit and output circuit
Global approvals for explosion protection
Input functionality — ATEX, IECEx, Zone 0
— 1 or 2 sensors — FM, CSA
— 2 x Pt100 three wire circuit — GOST, EAC Ex
— Inmetro
Specific linearization — NEPSI
— Callendar-Van Dusen coefficients — KOSHA
— Table of variate pairs / 32 points
SW write protection, HW write protection
Continuous sensor monitoring and self-monitoring
— Supply voltage monitoring Service interface
— Wire break and corrosion monitoring
in accordance with NE 89
— Extended diagnostics in accordance with NE 107
— Sensor drift monitoring
Change from one to two columns
TTH300
Head-mount temperature transmitter

Specifications Electrical connection


— Terminals with captive screws, incl. soldering tags
CE marking — Lines up to maximum 1.5 mm 2 (AWG 16)
— The device fulfills all requirements for CE marking in — Connection for handheld terminal
accordance with all applicable guidelines.
Dimensions
Electrical isolation See chapter "Dimensions" on page 13.
— 3.5 kV DC (approx. 2.5 kV AC), 60 s, input to output
Ambient conditions
MTBF time Ambient temperature
— 28 years at 60 °C ambient temperature — Standard -40 … 85 °C (-40 … 185 °F)
— Optional: -50 … 85 °C (-58 … 185 °F)
Input filter — Restricted range during operation with
— 50 / 60 Hz LCD indicator: -20 ... 70 °C (-4 … 158 °F)
— Restricted range during operation with explosion-proof
Switch-on delay design: see corresponding certificate
— HART: < 10 s (Ia ≤ 3.6 mA during switch-on cycle)
— PROFIBUS: 10 s, max. 30 s Transport- / storage temperature
— FOUNDATION Fieldbus: < 10 s — -50 … 85 °C (-58 … 185 °F)

Warm-up time Climate class in accordance with DIN EN 60654-1


— 5 minutes — Cx -40 … 85 °C (-40 … 185 °F) at 5 … 95 % relative
humidity
Rise time t90
— 400 … 1000 ms Max. permissible humidity in accordance with IEC 60068-2-30
— 100 % relative humidity
Measured value update
— 10/s with 1 sensor, 5/s with 2 sensors, depending on Vibration resistance in accordance with IEC 60068-2-6
sensor type and sensor circuit — 10 … 2000 Hz at 5 g, during operation and transport

Output filter Shock resistance in accordance with IEC 68-2-27


— Digital filter 1st order: 0 ... 100 s — gn = 30, during operation and transport

Weight IP rating
— 50 g — Power supply circuit: IP20
— Measurement circuit: IP00 or IP rating of installation
Material housing
— Housing: polycarbonate
— Color: gray RAL9002
— Sealing compound: hard sealing compound

Installation conditions
— Mounting position: no restrictions
— Installation options:
Connection heads in accordance with DIN 43729 form B
Rail mounting (35 mm) in accordance with EN 60175 by
means of latching base
Field mount housing

2 DS/TTH300-EN Rev. D | TTH300


Electromagnetic compatibility Properties
Emitted interference in accordance with IEC EN 61326 and Transmitter-controlled graphic (alphanumeric) LCD display
Namur NE 21 . — Character height, mode-dependent
— Sign, 4 digits, 2 decimal places
Interference immune in accordance with IEC 61326 and — Bar graph display
Namur NE 21. — Rotatable in 12 increments of 30°
Pt100: measuring range 0 ... 100 °C (32 ... 212 °F),
span 100 K Display options
— Sensor 1 process value
Testing — Sensor 2 process value
Type of test Effect
accuracy — Electronics- / ambient temperature
Burst to signal- / data lines 2 kV < 0,5 % — Output value
Static discharge — Output %
— Contact plate (indirect) 8 kV NO Display diagnostic information related to transmitter and
— Supply terminals 1) 6 kV NO sensor status
— Sensor terminals1) 4 kV NO
Radiated field Specifications
80 MHz … 2 GHz 10 V/m < 0,5 % Temperature range
Coupling — -20 … 70 °C (-4 … 158 °F)
150 kHz … 80 MHz 10 V < 0,5 %
Surge Restricted display function (contrast, reaction time) in the
between the supply lines 0,5 kV temperature ranges:
No malfunction
Line to ground 1 kV — -50 … -20 °C (-58 … -4 °F)
1) Air discharge (at 1 mm (0.04 inch) distance)
or
— 70 … 85 °C (158 … 185 °F)
SIL functional safety
Conforms with IEC 61508 as regards use in safety related Humidity
applications, up to and including SIL 3 (redundant). While — 0 … 100 %, condensation permitted
using the transmitter, the device fulfills the requirements in
accordance with SIL 2. While using two redundant
transmitters, the device fulfills the requirements in accordance
with SIL 3. Applicable only for HART variant.

Type A and type AS LCD indicators


The LCD display type AS has a display function; the LCD
display type A allows additional configuration functions to be
carried out. Both LCD displays can only be ordered in
conjunction with temperature transmitter.

CE marking Fig. 1: A LCD display type A B LCD display type AS


— The type A and type AS LCD display fulfill all requirements 1 Leave / Abort 2 Backwards 3 Forwards 4 Select
for CE marking in accordance with all applicable
guidelines.

TTH300 | DS/TTH300-EN Rev. D 3


TTH300
Head-mount temperature transmitter

Configuration function Input - thermocouples / voltages


— Sensor configuration for standard sensors Types
— Measuring range — B, E, J, K, N, R, S, T in accordance with IEC 60584
— Behavior in the event of a fault (HART) — U, L in accordance with DIN 43710
— Software write protection for configuration data — C, D in accordance with ASTM E-988
— Device address for HART and PROFIBUS PA
Voltages
Input - resistance thermometer / resistances — -125 ... 125 mV
Resistance thermometer — -125 ... 1100 mV
— Pt100 according to IEC 60751, JIS C1604, MIL-T-24388
— Ni according to DIN 43760 Supply line
— Cu according to recommendation OIML R 84 — Maximum sensor line resistance
1.5 kΩ per wire, 3 kΩ in total
Resistance measurement
— 0 … 500 Ω Sensor wire break monitoring in accordance with NE 89
— 0 … 5000 Ω — Pulsed with 1 μA outside measurement interval
— Thermocouple measurement 5.3 ... 10 kΩ
Sensor connection type — Voltage measurement 5.3 ... 10 kΩ
— Two-, Three-, Four wire-circuits
Input resistance > 10 MΩ
Connection lead
— Maximum sensor line resistance: Internal reference junction Pt1000, IEC 60751 Cl. B
of 50 Ω per line in accordance with NE 89 (no additional jumpers necessary)
— Three-wire circuit:
Symmetrical sensor line resistances Sensor error signaling
— Two-wire circuit: — Thermocouple: wire break
Compensation up to 100 Ω total lead resistance — Linear voltage measurement: wire break

Measurement current < 300 μA Functionality input


Free style characteristic curve / 32-point -sampling point table
Sensor short circuit < 5 Ω (for resistance thermometers) — Resistance measurement up to max. 5 kΩ
— Voltages up to max. 1.1 V
Sensor wire break
— Measuring range: 0 ... 500 Ω > 0.6 ... 10 kΩ Sensor error adjustment
— Measuring range: 0 ... 5 kΩ > 5.3 ... 10 kΩ — Via Callendar-Van Dusen coefficients
— Via value table of 32 reference points
Corrosion detection in accordance with NE 89 — Via single-point adjustment (offset adjustment)
— Three-wire resistance measurement > 50 Ω — Via two-point adjustment
— Four-wire resistance measurement > 50 Ω
Input functionality
Sensor error signaling — 1 sensor
— Resistance thermometer: Sensor short circuit and sensor — 2 sensors:
wire breakage mean measurement,
— Linear resistance measurement: Sensor wire break differential measurement,
sensor redundancy,
Sensor drift monitoring

4 DS/TTH300-EN Rev. D | TTH300


HART output FOUNDATION Fieldbus output
Transmission behavior Output signal
— Temperature linear — FOUNDATION Fieldbus H1 (IEC 611582-2)
— Resistance linear — Baud rate 31.25 kbit/s, ITK 5.x
— Voltage linear — FISCO compliant (IEC 60079-27)
— Device ID: 000320001F...
Output signal
— Configurable 4 ... 20 mA (standard) Error current signal
— Configurable 20 ... 4 mA — FDE (Fault Disconnection Electronic)
(Dynamic range: 3.8 ... 20.5 mA in accordance with NE 43)
Block structure1)
Simulation mode 3.5 ... 23.6 mA — Resource Block
— Transducer Block 1 – temperature
Induced current consumption < 3.5 mA — Transducer Block 2 – HMI (LCD indicator)
— Transducer Block 3 – enhanced diagnosis
Maximum output current 23.6 mA — Analog Input 1 – PRIMARY_VALUE_1 (sensor 1)
— Analog Input 2 – PRIMARY_VALUE_2 (sensor 2)
Configurable error current signal — Analog Input 3 – PRIMARY_VALUE_3 (calculated value 2) )
— Overrange 22 mA (20.0 … 23.6 mA) — Analog Input 4 – SECONDARY_VALUE (reference junction
— Underrange 3.6 mA (3.5 … 4.0 mA) temp.)
— Analog Output – optional HMI display
PROFIBUS PA output (Transducer Block 2)
Output signal — Discrete Input 1 – enhanced diagnosis 1
— PROFIBUS – MBP (IEC 61158-2) (Transducer Block 3)
— Baud rate 31.25 kbit/s — Discrete Input 2 – enhanced diagnosis 2
— PA profile 3.01 (Transducer Block 3)
— FISCO compliant (IEC 60079-27) — PID – PID controller
— ID number: 0x3470 [0x9700]
LAS (Link Active Scheduler) link master functionality
Error current signal 1) For the block description, block index, execution times, and block class, refer
— FDE (Fault Disconnection Electronic) to the interface description
2) Sensor 1, sensor 2 or difference or mean

Block structure
— Physical Block
— Transducer Block 1 – temperature
— Transducer Block 2 – HMI (LCD indicator)
— Transducer Block 3 – enhanced diagnosis
— Analog Input 1 – Primary Value (Calculated Value1))
— Analog Input 2 – SECONDARY VALUE_1 (sensor 1)
— Analog Input 3 – SECONDARY VALUE_2 (sensor 2)
— Analog Input 4 – SECONDARY VALUE_3 (reference
junction temperature)
— Analog Output – optional HMI display (Transducer Block 2)
— Discrete Input 1 – enhanced diagnosis 1 (Transducer Block 3)
— Discrete Input 2 – enhanced diagnosis 2 (Transducer Block 3)
1) Sensor 1, sensor 2 or difference or mean

TTH300 | DS/TTH300-EN Rev. D 5


TTH300
Head-mount temperature transmitter

Power supply
Two-wire technology, polarity safe; power supply lines = signal
lines

NOTICE
Following calculations apply for standard applications. This
should be taken into consideration when working with a
higher maximum current.

Power supply - HART


Input terminal voltage
— Non-Ex application:
US = 11 ... 42 V DC
— Ex applications:
US = 11 ... 30 V DC

Max. permissible residual ripple for input terminal voltage Fig. 2: Maximum load depending on input terminal voltage
— During communication in accordance with HART FSK A TTH300 B TTH300 in Ex ia design C HART communication
"Physical Layer" specification. resistance

Undervoltage detection on the transmitter Maximum power consumption


— If the terminal voltage on the transmitter falls below a — P = Us x 0.022 A
value of 10 V, this may lead to an output current of — e. g. Us = 24 V  Pmax = 0.528 W
Ia ≤ 3.6 mA.
Power supply - PROFIBUS / FOUNDATION Fieldbus
Maximum load Input terminal voltage
— RB = (supply voltage – 11 V) / 0.022 A — Non-Ex application:
US = 9 ... 32 V DC
— Ex applications:
US = 9 ... 17.5 V DC (FISCO)
US = 9 ... 24 V DC (Fieldbus Entity model I.S.)
Current consumption ≤ 12 mA
Change from two to one column

6 DS/TTH300-EN Rev. D | TTH300


Measuring accuracy
Includes Linearity error, repeatability / hysteresis at 23 °C (73.4 °F) ± 5 K and 20 V supply voltage.
Information on measuring accuracy corresponds to 3 σ (Gaussian distribution).

Sensor Measuring range limits Minimum span Digital measuring D / A measuring


accuracy accuracy1)
(24-Bit AD-converter) (16-Bit D / A)
Resistance thermometer/resistor
DIN IEC 60751 Pt10 (a=0.003850) -200 ... 850 °C (-328 … 1562 °F) 10 °C (18 °F) ± 0.80 °C (± 1.44 °F) ± 0.05 %
Pt50 (a=0.003850) ± 0.16 °C (± 0.29 °F) ± 0.05 %
Pt100 (a=0.003850)2) ± 0.08 °C (± 0.14 °F) ± 0.05 %
Pt200 (a=0.003850) ± 0.24 °C (± 0.43 °F) ± 0.05 %
Pt500 (a=0.003850) ± 0.16 °C (± 0.29 °F) ± 0.05 %
Pt1000 (a=0.003850) ± 0.08 °C (± 0.14 °F) ± 0.05 %
JIS C1604 Pt10 (a=0.003916) -200 ... 645 °C (-328 ... 1193 °F) 10 °C (18 °F) ± 0.80 °C (± 1.44 °F) ± 0.05 %
Pt50 (a=0.003916) ± 0.16 °C (± 0.29 °F) ± 0.05 %
Pt100 (a=0.003916) ± 0.08 °C (± 0.14 °F) ± 0.05 %
MIL-T-24388 Pt10 (a=0.003920) -200 ... 850 °C (-328 ... 1562 °F) 10 °C (18 °F) ± 0.80 °C (± 1.44 °F) ± 0.05 %
Pt50 (a=0.003920) ± 0.16 °C (± 0.29 °F) ± 0.05 %
Pt100 (a=0.003920) ± 0.08 °C (± 0.14 °F) ± 0.05 %
Pt200 (a=0.003920) ± 0.24 °C (± 0.43 °F) ± 0.05 %
Pt1000 (a=0.003920) ± 0.08 °C (± 0.14 °F) ± 0.05 %
DIN 43760 Ni50 (a=0.006180) -60 ... 250 °C (-76 ... 482 °F) 10 °C (18 °F) ± 0.16 °C (± 0.29 °F) ± 0.05 %
Ni100 (a=0.006180) ± 0.08 °C (± 0.14 °F) ± 0.05 %
Ni120 (a=0.006180) ± 0.05 %
Ni1000 (a=0.006180) ± 0.05 %
OIML R 84 Cu10 (a=0.004270) -50 ... 200 °C (-58 ... 392 °F) 10 °C (18 °F) ± 0.80 °C (± 1.44 °F) ± 0.05 %
Cu100 (a=0.004270) ± 0.08 °C (± 0.14 °F) ± 0.05 %
Resistance 0 ... 500 Ω 4Ω ± 32 mΩ ± 0.05 %
measurement 0 ... 5000 Ω 40 Ω ± 320 mΩ ± 0.05 %
Thermocouples 3)/voltages
IEC 60584 Type K (Ni10Cr-Ni5) -270 … 1372 °C (-454 … 2502 °F) 50 °C (90 °F) ± 0.35 °C (± 0.63 °F) ± 0.05 %
Type J (Fe-Cu45Ni) -210 … 1200 °C (-346 … 2192 °F) ± 0.05 %
Type N (Ni14CrSi-NiSi) -270 … 1300 °C (-454 … 2372 °F) ± 0.05 %
Type T (Cu-Cu45Ni) -270 ... 400 °C (-454 ... 752 °F) ± 0.05 %
Type E (Ni10Cr-Cu45Ni) -270 … 1000 °C (-454 … 1832 °F) ± 0.05 %
Type R (Pt13Rh-Pt) -50 … 1768 °C (-58 … 3215 °F) 100 °C (180 °F) ± 0.95 °C (± 1.71 °F) ± 0.05 %
Type S (Pt10Rh-Pt) ± 0.05 %
Type B (Pt30Rh-Pt6Rh) -0 … 1820 °C (32 … 3308 °F) ± 0.05 %
DIN 43710 Type L (Fe-CuNi) -200 … 900 °C (-328 … 1652 °F) 50 °C (90 °F) ± 0.35 °C (± 0.63 °F) ± 0.05 %
Type U (Cu-CuNi) -200 … 600 °C (-328 … 1112 °F) ± 0.05 %
ASTM E 988 Type C -0 … 2315 °C (32 … 4200 °F) 100 °C (180 °F) ± 1.35 °C (± 2.43 °F) ± 0.05 %
Type D ± 0.05 %
Voltage measurement -125 ... 125 mV 2 mV ± 12 μV ± 0.05 %
-125 ... 1100 mV 20 mV ± 120 μV ± 0.05 %

Long-term drift: ± 0.05 °C (± 0.09 °F) or ± 0.05 %1) per year; the larger value applies.
1) Percentages refer to the configured measuring span, omitted for PROFIBUS and FOUNDATION Fieldbus
2) Standard model
3) For digital measurement accuracy, the internal reference junction error must be added: Pt1000, DIN IEC 60751 Cl. B

TTH300 | DS/TTH300-EN Rev. D 7


TTH300
Head-mount temperature transmitter

Operating influence
The percentages refer to the configured measuring span.

Input terminal voltage effect / load effect: within the specified limit values for the voltage / load, the total influence is less than
0.001% per volt.

Common-mode interference: no influence up to 100 Veff (50 Hz) or 50 VDC

Ambient temperature effect: based on 23 °C (73.4 °F) for an ambient temperature range of -40 ... 85 °C (-40 ... 185 °F)4)

Sensor Ambient temperature effect per 1 °C (1.8 °F) Ambient temperature effect 1) 2) per
deviation from 23 °C (73.4 °F) for digital 1 °C (1.8 °F) deviation from 23 °C (73.4 °F)
measured value for DA-converter
Resistance thermometer for two-, three- and four-wire circuits
IEC, JIS, MIL Pt10 ± 0.04 °C (± 0.072 °F) ± 0.003 %
Pt50 ± 0.008 °C (± 0.014 °F) ± 0.003 %
Pt100 ± 0.004 °C (± 0.007 °F) ± 0.003 %
IEC, MIL Pt200 ± 0.02 °C (± 0.036 °F) ± 0.003 %
Pt500 ± 0.008 °C (± 0.014 °F) ± 0.003 %
Pt1000 ± 0.004 °C (± 0.007 °F) ± 0.003 %
DIN 43760 Ni50 ± 0.008 °C (± 0.014 °F) ± 0.003 %
Ni100 ± 0.004 °C (± 0.007 °F) ± 0.003 %
Ni120 ± 0.003 °C (± 0.005 °F) ± 0.003 %
Ni1000 ± 0.004 °C (± 0.007 °F) ± 0.003 %
OIML R 84 Cu10 ± 0.04 °C (± 0.072 °F) ± 0.003 %
Cu100 ± 0.004 °C (± 0.007 °F) ± 0.003 %
Resistance measurement
0 ... 500 Ω ± 0.002 Ω ± 0.003 %
0 ... 5000 Ω ± 0.02 Ω ± 0.003 %
Thermocouple, for all defined types ± [(0.001 % x (ME[mV] / MS[mv]) + (100 % x ± 0.003 %
(0.009 °C / MS [°C])]3)
Voltage measurement
-125 ... 125 mV ± 1.5 μV ± 0.003 %
-125 ... 1100 mV ± 15 μV ± 0.003 %

1) Percentages refer to the configured measuring span of the analog output signal
2) Influence of DA-converter omitted for PROFIBUS PA and FOUNDATION Fieldbus
3) ME = voltage value of the thermocouple at the upper range value in accordance with the standard
MA = voltage value of the thermocouple at the lower range value in accordance with the standard
MS = voltage value of the thermocouple over the measuring span in accordance with the standard. MS = (ME - MA)
4) If the optional extended ambient temperature range down to -50 °C (-58 °F) applies, the causal variables are doubled in the range between -50 ... -40 °C
(-58 ... -40 °F)

8 DS/TTH300-EN Rev. D | TTH300


Electrical connections
Pin assignment
Resistance thermometers (RTD) / resistors (potentiometers)

A B C D E F G H

1 1 1 1 1 1 1 1 1

I 2 2 2 2 2 2
J J 8
J J J 1
+
2
3 3 3 3 3 3 3 3 3 3

8
4 4 4 4

7
4
4
J 7
-
J 5
J 5
K
6 6 6
A10003-01

Fig. 3
A Potentiometer, four-wire circuit B Potentiometer, three-wire circuit C Potentiometer, two-wire circuit D 2 x RTD, three-wire circuit1)
E 2 x RTD, two-year wire 1) F RTD, four-wire circuit G RTD, three-wire circuit H RTD, two-wire circuit I Sensor 1 J Sensor 21)
K LCD indicator-interface
1 – 6 Sensor connection (from measuring inset) 7 – 8 4 … 20 mA HART, PROFIBUS PA, FOUNDATION Fieldbus

1) Sensor backup / sensor redundancy, sensor drift monitoring, mean measurement, or differential measurement

TTH300 | DS/TTH300-EN Rev. D 9


TTH300
Head-mount temperature transmitter

Thermocouples / voltages and resistance thermometer (RTD) / thermocouple combinations


A B C D E F G

1 1 1 1 1 1 1 1
- - - -

H + + + +

2 2 2 2 2 2 2
J 8
J J 1
+
2
3 3 3 3 3

8
4

7
4
4

7
-
5 5 5 5 5
+ + + + + 5
I - - - -
J
-
6 6 6 6 6 6
A10004-01

Fig. 4
A 2 x voltage meter1) B 1 x voltage meter C 2 x Thermoelement1) D 1 x Thermoelement E 1 x RTD, four--wire circuit and
1 x Thermoelement1) F 1 x RTD, three--wire circuit and 1 x Thermoelement1) G 1 x RTD, two--wire circuit and 1 x Thermoelement1)
H Sensor 1 I Sensor 21) J LCD indicator-interface
1 – 6 Sensor connection (from measuring inset) 7 – 8 4 … 20 mA HART, PROFIBUS PA, FOUNDATION Fieldbus

1) Sensor backup / sensor redundancy, sensor drift monitoring, mean measurement, or differential measurement

Change from one to two columns

10 DS/TTH300-EN Rev. D | TTH300


Communication HART
The device is listed with the FieldComm Group.
Configuration parameters
+
Measurement type 1 6
Rb = 250 Ω1)
— Sensor type, connection type
— Error signaling -

— Measuring range 5
— General information, e.g. TAG number 2 3
— Damping 4

— Warning and alarm limits


A10081
— Output signal simulation
— Details "Order form configuration" on page 20 Fig. 5: Example for HART interface connection
1 Transmitter 2 Handheld Terminal 3 HART-Modem 4 FDT /
DTM Technology 5 Grounding (optional) 6 Power supply unit
Write protection
(Process Interface)
— Software write protection
1) If required

Diagnostic information in accordance with NE 107


Standard: Manufacturer ID 0x1A
— Sensor error signaling Device ID 0x0A
(wire break or short circuit) Profile HART 5.1 (can be switched to
— Device error HART 7)
— Over / under limit values Configuration On device using LCD display
— Over / under measuring range DTM
— Simulation active EDD
Advanced: Transmission signal BELL Standard 202
— Sensor redundancy / sensor backup active (in case sensor
fails) with configurable analog alarm pulse signaling Operating modes
— Drift monitoring with configurable alarm pulse signaling — Point-to-point communication mode – standard (general
— Sensor / sensor line corrosion address 0)
— Supply voltage undershoot — Multidrop mode (addressing 1 ... 15)
— Drag indicator for sensor 1, sensor 2 and ambient — Burst mode
temperature
— Over ambient temperature Configuration options and tools
— Under ambient temperature Driver-independent:
— Operating hours counter — HMI LCD display with configuration function
Driver-dependent:
— Device management / asset management tools
— FDT / DTM technology – via TTX300 DTM driver
— EDD - via TTX300 EDD driver

Diagnostic message
— Overrange / underrange in accordance with NE 43
— HART diagnosis

TTH300 | DS/TTH300-EN Rev. D 11


TTH300
Head-mount temperature transmitter

PROFIBUS PA FOUNDATION Fieldbus


The interface conforms to profile 3.01 (PROFIBUS standard,
EN 50170, DIN 1924 [PRO91]).

Fig. 7: Example for FOUNDATION Fieldbus connection


Fig. 6: Example for PROFIBUS PA interface connection 1 Transmitter 2 Bus termination 3 Handheld terminal
1 Transmitter 2 Bus termination 3 Segment coupler 4 Linking Device 5 PC / DCS
4 PC / DCS
Device ID 000320001F...
Manufacturer ID 0x1A ITK 5.x
ID number 0x3470 [0x9700] Configuration On device using LCD
Profile PA 3.01 EDD
Configuration On device using LCD display Transmission signal IEC 61158-2
DTM
EDD Voltage / current consumption
GSD — Mean current consumption: 12 mA.
Transmission signal IEC 61158-2 In the event of an error, the FDE function (=Fault
Disconnection Electronic) integrated in the device ensures
Voltage / current consumption that the current consumption cannot exceed a maximum
— Mean current consumption: 12 mA. of 20 mA.
In the event of an error, the FDE function (=Fault
Disconnection Electronic) integrated in the device ensures
that the current consumption cannot exceed a maximum
of 20 mA.
Change from two to one column

12 DS/TTH300-EN Rev. D | TTH300


Dimensions

M4 x 23
M4

Ø 44,4 (1.75)
Ø 7 (0.28)

33 (1.3)

49,2 (1.94)

14 (0.55)
M4

57 (2.24)
2

30,2 (1.19)
5,5 (2.2)
24,7 (0.97)

35 (1.38) 35 (1.38)

50 (1.94) 50 (1.94)
A11119
Fig. 8: Dimensions in mm / inch
1 Interface for LCD display 2 Latching base for 35 mm (1.38 inch) Rail mounting in accordance with EN 60175

Change from one to two columns

TTH300 | DS/TTH300-EN Rev. D 13


TTH300
Head-mount temperature transmitter

Use in potentially explosive atmospheres IECEx intrinsic safety


according to ATEX and IECEx Approved for use in Zone 0, 1, and 2.

NOTICE Model TTH300-H1H


— Further information on the approval of devices for use in IECEx certificate of conformity IECEx PTB 09.0014X
potentially explosive atmospheres can be found in the Model TTH300-H1P and TTH300-H1F
explosion protection test certificates (at IECEx certificate of conformity IECEx PTB 11.0108X
www.abb.com/temperature). Ex ia IIC T6
— Depending on the design, a specific marking in Ex [ia] ib IIC T6
accordance with ATEX or IECEx applies. Ex [iaD] ib IIC T6

Ex-marking LCD indicators


Transmitter ATEX intrinsic safety
ATEX intrinsic safety The device fulfills the requirements of Directive 2014/34/EU in
The device fulfills the requirements of Directive 2014/34/EU in case of corresponding purchase orders and is approved for
case of corresponding purchase orders and is approved for use in Zone 0, 1 and 2.
use in Zone 0, 1 and 2.
Type Examination Test Certificate: PTB 05 ATEX 2079 X
Model TTH300-E1H II 1G Ex ia IIC T6 Ga
Type examination certificate PTB 05 ATEX 2017 X
II 1 G Ex ia IIC T6 Ga ATEX Non-sparking
II 2 (1) G Ex [ia] ib IIC T6 Gb (Ga) The device fulfills the requirements of Directive 2014/34/EU in
II 2 G (1D) Ex [iaD] ib IIC T6 Gb (Da) case of corresponding purchase orders and is approved for
use in Zone 2.
Model TTH300-E1P and TTH300-E1F
Type examination certificate PTB 09 ATEX 2016 X Declaration of conformity
II 1G Ex ia IIC T6 II 3 G Ex nA IIC T1-T6 Gc
II 2(1)G Ex [ia] ib IIC T6
II 2G(1D) Ex [iaD] ib IIC T6 IECEx intrinsic safety
Approved for use in Zone 0, 1, and 2.
ATEX Non-sparking
The device fulfills the requirements of Directive 2014/34/EU in IECEx certificate of conformity IECEx PTB 12.0028X
case of corresponding purchase orders and is approved for Ex ia IIC T6
use in Zone 2.

Model TTH300-E2X
Declaration of conformity
II 3 G Ex nA IIC T1-T6 Gc

14 DS/TTH300-EN Rev. D | TTH300


Temperature data Intrinsic safety type of protection Ex ia IIC (part 2)
Transmitter
ATEX/IECEx intrinsic safety, non-sparking ATEX Measurement circuit: Measurement circuit:
resistance thermocouples,
Temperature class Permissible ambient temperature range thermometer, voltages
Device category 1 Device category 2 / 3 resistances
use use Max. voltage Uo = 6.5 V Uo = 1.2 V
T6 -50 … 44 °C -50 … 56 °C Short-circuit current Io = 25 mA Io = 50 mA
(-58 ... 111.2 °F) (-58 ... 132.8 °F) Max. power Po = 38 mW Po = 60 mW
T5 -50 … 56 °C -50 … 71 °C Internal inductance Li = 0 mH Li = 0 mH
(-58 ... 132.8 °F) (-58 ... 159.8 °F) Internal capacitance Ci = 49 nF Ci = 49 nF
T4-T1 -50 … 60 °C -50 … 85 °C Maximum Lo = 5 mH Lo = 5 mH
(-58 ... 140.0 °F) (-58 ... 185.0 °F) permissible external
inductance
LCD indicators Maximum Co = 1.55 μF Co = 1.05 μF
ATEX/IECEx intrinsic safety, non-sparking ATEX permissible external
capacitance
Temperature class Permissible ambient temperature range
Device category 1 Device category 2 / 3 Intrinsic safety type of protection Ex ia IIC (part 3)
use use
T6 -40 … 44 °C -40 … 56 °C LCD indicator interface
(-40 … 111.2 °F) (-40 … 132.8 °F) Max. voltage Uo = 6.2 V
T5 -40 … 56 °C -40 … 71 °C Short-circuit current Io = 65.2 mA
(-40 … 132.8 °F) (-40 … 159.8 °F) Max. power Po = 101 mW
T4-T1 -40 … 60 °C -40 … 85 °C Internal inductance Li = 0 mH
(-40 … 140 °F) (-40 … 185 °F) Internal capacitance Ci = 0 nF
Maximum permissible external Lo = 5 mH
Electrical data inductance
Transmitter Maximum permissible external Co = 1.4 μF
Intrinsic safety type of protection Ex ia IIC (part 1) capacitance

TTH300-E1H TTH300-E1P/-H1P LCD indicators


TTH300-H1H TTH300-E1F/-H1F Intrinsic safety type of protection Ex ia IIC
Supply circuit Supply circuit 1)

FISCO ENTITY Supply circuit


Max. voltage Ui = 30 V Ui ≤ 17.5 V Ui ≤ 24.0 V Max. voltage Ui = 9 V
Short-circuit current Ii = 130 mA Ii ≤ 183 mA2) Ii ≤ 250 mA Short-circuit current Ii = 65.2 mA
Max. power Pi = 0.8 W Pi ≤ 2.56 W2) Pi ≤ 1.2 W Max. power Pi = 101 mW
Internal inductance Li = 0.5 mH Li ≤ 10 μH Li ≤ 10 μH Internal inductance Li = 0 mH
Internal capacitance Ci = 0.57 nF 3) Ci ≤ 5 nF Ci ≤ 5 nF Internal capacitance Ci = 0 nF

1) FISCO in accordance with 60079-27


2) II B FISCO: Ii ≤ 380 mA, Pi ≤ 5.32 W
3) Only applies to HART variants. From HW rev. 1.07, previously 5 nF

TTH300 | DS/TTH300-EN Rev. D 15


TTH300
Head-mount temperature transmitter

Use in potentially explosive atmospheres CSA Non-Incendive


in accordance with FM and CSA
Model TTH300-R2H
NOTICE Control Drawing SAP_214824 (Non-Incendive)
— Further information on the approval of devices for use in SAP_214896 (Non-Incendive)
potentially explosive atmospheres can be found in the Model TTH300-R2P
explosion protection test certificates (at Control Drawing TTH300-R2P (NI_PS)
www.abb.com/temperature). TTH300-R2P (NI_AA)
— Depending on the design, a specific marking in Model TTH300-R2F
accordance with FM or CSA applies. Control Drawing TTH300-R2F (NI_PS)
TTH300-R2F (NI_AA)
Ex-marking Class I, Div. 2, Groups A, B, C, D
Transmitter
FM Intrinsically Safe LCD indicators
FM Intrinsically Safe
Model TTH300-L1H
Control Drawing SAP_214829 Control Drawing SAP_214 748
Model TTH300-L1P I.S. Class I Div 1 and Div 2, Group: A, B, C, D or
Control Drawing TTH300-L1P (IS) I.S. Class I Zone 0 AEx ia IIC T 1)
Model TTH300-L1F Ui / Vmax = 9 V, Ii / Imax < 65.2 mA, Pi = 101 mW, Ci = 0.4 μF, Li = 0
Control Drawing TTH300-L1F (IS)
Class I, Div. 1 + 2, Groups A, B, C, D FM Non-Incendive
Class I, Zone 0, AEx ia IIC T6
Control Drawing SAP_214 751
FM Non-Incendive N.I. Class I Div 2, Group: A, B, C, D or Ex nL IIC T 2), Class I Zone 2
Ui / Vmax = 9 V, Ii / Imax < 65.2 mA, Pi = 101 mW, Ci = 0.4 μF, Li = 0
Model TTH300-L2H
Control Drawing 214831 (Non-Incendive) CSA Intrinsically Safe
Model TTH300-L2P
Control Drawing TTH300-L2P (NI_PS) Control Drawing SAP_214 749
TTH300-L2P (NI_AA) I.S. Class I Div 1 and Div 2; Group: A, B, C, D or
Model TTH300-L2F I.S Zone 0 Ex ia IIC T1)
Control Drawing TTH300-L2F (NI_PS) Ui / Vmax = 9 V, Ii / Imax < 65.2 mA, Pi = 101 mW, Ci < 0.4 μF, Li = 0
TTH300-L2F (NI_AA)
Class I, Div. 2, Groups A, B, C, D CSA Non-Incendive

CSA Intrinsically Safe Control Drawing SAP_214 750


N.I. Class I Div 2, Group: A, B, C, D oder Ex nL IIC T2), Class I Zone 2
Model TTH300-R1H Ui / Vmax = 9 V, Ii / Imax < 65.2 mA, Pi = 101 mW, Ci < 0.4 μF, Li = 0
Control Drawing 214826
1) Temp. Ident: T6 T amb 56 °C, T4 T amb 85 °C
Model TTH300-R1P 2) Temp. Ident: T6 T amb 60 °C, T4 T amb 85 °C
Control Drawing TTH300-R1P (IS)
Model TTH300-R1F
Control Drawing TTH300-R1F (IS)
Class I, Div. 1 + 2, Groups A, B, C, D
Class I, Zone 0, Ex ia Group IIC T6
Change from two to one column

16 DS/TTH300-EN Rev. D | TTH300


Ordering Information
Ordering information TTH300

Base model TTH300 XX X X


TTH300 Head Mounted Temperature Transmitter, Pt100 (RTD), thermocouples, electrical isolation
Explosion Protection
Without explosion protection Y0
ATEX Intrinsic Safety type of protection: Zone 0: II 1 G Ex ia IIC T6, Zone 1 (0): II 2 (1) G Ex [ia] ib IIC T6,
Zone 1 (20): II 2 G (1D) Ex [iaD] ib IIC T6 E1
ATEX Non-sparking type of protection: Zone 2: II 3 G Ex nA T6 E2
IECEx Intrinsic Safety type of protection: Zone 0: Ex ia IIC T6, Zone 1 (0): Ex [ia] ib IIC T6, Zone 1 (20): Ex [iaD] ib IIC T6 H1
FM Intrinsic Safety (IS): Class I, Div. 1+2, Groups A, B, C, D, Class I, Zone 0, AEx ia IIC T6 L1
FM Non-incendive (NI): Class I, Div. 2, Groups A, B, C, D L2
CSA Intrinsic Safety (IS): Class I, Div. 1+2, Groups A, B, C, D R1
CSA Non-incendive (NI): Class I, Div. 2, Groups A, B, C, D R2
GOST Russia - metrological approval G1
GOST Russia - metrological approval and EAC-Ex, Ex i - Zone 0 P2
GOST Kazakhstan - metrological approval G3
GOST Kazakhstan - metrological approval and EAC-Ex, Ex i - Zone 0 T2
GOST Belarus - metrological approval M5
GOST Belarus - metrological approval and EAC-Ex, Ex i - Zone 0 U2
Inmetro Ex ia IIC T6...T4 Ga, Ex ib [ia Ga] IIC T6...T4 Gb Exib [ia IIIC Da] IIC T6...T4 Gb C1
NEPSI Ex ia IIC T6 S1
KOSHA Ex ia IIC T6 S5
Communication Protocol
HART H
PROFIBUS PA P
FOUNDATION fieldbus F
Configuration
Standard configuration BS
Customer-specific configuration with report, except user curve 1) BF
Customer-specific configuration with report, including user curve BG

TTH300 | DS/TTH300-EN Rev. D 17


TTH300
Head-mount temperature transmitter

Additional ordering information TTH300

XX XX XXX XX XX XX XX XX
Certificates
SIL2 - Declaration of Conformity 2) CS
Declaration of compliance according EN 10204-2.1, with the order C4
Inspection certificate according EN 10204-3.1, visual, dimensional and functional test C6
Calibration Certificates
With 5-point factory certificate EM
Inspection certificate according EN 10204-3.1, 5-point calibration EP
Handling of Certificates
Send via e-mail GHE
Send via mail GHP
Send via mail express GHD
Send with instrument GHA
Only archived GHS
Extended Ambient Temperature Range
-50 ... 85 °C (-58 ... 185 °F) 3) SE
Field Housing
Aluminium field housing 80 x 75 x 57 mm, IP 65, including 2 pieces M16 cable glands 4) H1
Polyester field housing 75 x 80 x 55 mm, IP 65, including 2 pieces M16 cable glands 4) H2
Polycarbonate field housing 80 x 82 x 55 mm, IP 65, including 2 pieces M16 cable glands 4) H3
Aluminium field housing 175 x 80 x 57 mm with separate terminal block, IP 65,
including 1 piece M16 and 2 pieces M20 cable glands 4) H5
Aluminium field housing 175 x 80 x 57 mm without separate terminal block, IP 65,
including 1 piece M16 and 2 pieces M20 cable glands 4) H6
Polyester field housing 190 x 75 x 55 mm with separate terminal block, IP 65,
including 1 piece M16 and 2 pieces M20 cable glands 4) H7
Polyester field housing 190 x 75 x 55 mm without separate terminal block, IP 65,
including 1 piece M16 and 2 pieces M20 cable glands 4) H8
Display Options
Prepared for display D1
Not prepared for display D2
LCD indicator type AS D3
Configurable LCD indicator type A D4
Mounting Options
Snap-on fixing set for 35 mm rail acc. EN 60175 (incl. fixing screws) SF
Customer-specific Versions
(Please specify) Z9

18 DS/TTH300-EN Rev. D | TTH300


Additional ordering information TTH300 XX
Documentation Language
German M1
English M5
Language package Western Europe / Scandinavia (Languages: DA, ES, FR, IT, NL, PT, FI, SV) MW
Language package Eastern Europe (Languages: EL, CS, ET, LV, LT, HU, HR, PL, SK, SL, RO, BG) ME

1) E.g. set measuring range, TAG no.


2) Only available with Communication Protocol code H (HART)
3) Not available with Explosion Protection code L1, L2, R1, R2 and not avaible with PROFIBUS PA or FOUNDATION Fieldbus Codes P, F
4) Not available with Explosion Protection

Accessories Order code


TTH Snap-on fixing set (packing unit 10 pieces), for 35 mm rail acc. EN 60175 (incl. fixing screws) 3KXT091230L0001
TTH Snap-on fixing set (packing unit 1 piece), for 35 mm rail acc. EN 60175 (incl. fixing screws) 3KXT091230L0002
TTH300 Commissioning Instruction, German 3KXT231001R4403
TTH300 Commissioning Instruction, English 3KXT231001R4401
TTH300 Commissioning Instruction, Language package Western Europe / Scandinavia 3KXT231001R4493
TTH300 Commissioning Instruction, Language package Eastern Europe 3KXT231001R4494

Change from one to two columns

Trademarks
® HART is a registered trademark of FieldComm Group, Austin, Texas,
USA
® PROFIBUS and PROFIBUS PA are registered trademarks of PROFIBUS
& PROFINET International (PI)
® FOUNDATION Fieldbus is a registered trademark of FieldComm Group,

Change from two to one column


Austin, Texas, USA

TTH300 | DS/TTH300-EN Rev. D 19


TTH300
Head-mount temperature transmitter

Order form configuration


HART device design: Instructions for customer-specific configuration

Configuration Selection
Number of sensors  1 sensor (standard)  2 sensors
Measurement type  Sensor redundancy / sensor backup
(for 2-sensor selection only)  Sensor drift monitoring ____°C / K sensor drift differential ____s time limit for drift overshoot
 Differential measurement: zero point where Ia = 4 mA
 Differential measurement: zero point where Ia = 12 mA
 Average measurement
IEC 60751 Resistance thermometer  Pt10  Pt50  Pt100 (Standard)  Pt200  Pt500  Pt1000
JIS C1604  Pt10  Pt50  Pt100
MIL-T-24388  Pt10  Pt50  Pt100  Pt200  Pt1000
DIN 43760  Ni50  Ni100  Ni120  Ni1000
OIML R 84  Cu10  Cu100
Resistance measurement  0 … 500 Ω  0 … 5000
IEC 60584 Thermocouple  Type K  Type J  Type N  Type R  Type S  Type T  Type E  Type B
DIN 43710  Type L  Type U
ASTM E-988  Type C  Type D
Voltage measurement  -125 … 125 mV  -125 … 1100 mV
Sensor circuit Two-wire  Three-wire (standard)  Four-wire
(for resistance thermometer and resistance Two-wire circuit: Compensation of Sensor Line Resistance. 100 Ω
measurement only)  Sensor 1: ____ Ω  Sensor 2: ____ Ω
Reference junction  Internal (for standard thermocouple, except type B)  None (type B)
(for thermocouples only)  External / temperature: ____°C
Measuring range  Lower range value : ___________ (standard: 0)
 Upper range value : ___________ (standard: 100)
Unit Celsius (default)  Fahrenheit  Rankine  Kelvin
Characteristic behavior  Rising 4 ... 20 mA (standard)  Falling 20 ... 4 mA
Output behavior for error  Overrange / 22 mA (standard)  Underrange / 3.6 mA
Output attenuation (T63)  Off (standard)  ____ seconds (1 … 100 s)
Sensor number  Sensor 1: ___________  Sensor 2: ___________
Resistance value at 0 °C / Ro Sensor 1: Ro: ___________ Sensor 2: Ro: ___________
Callendar-Van Dusen coefficient A A: ___________ A: ___________
Callendar-Van Dusen coefficient B B: ___________ B: ___________
Callendar-Van Dusen coefficient C C: ___________ C: ___________
(optional, for resistance thermometers only)
User characteristics based on linearization table  Based on attached table of variate pairs
TAG number  ___________ (maximum 8 characters)
HART revision  HART5 (standard)  HART7
Software write protection  Off (standard)  On
"Maintenance required" alarm pulse or  Off (standard) pulse width ____ s (0.5 ... 59.5 s increment 0.5 s)
continuous signaling in accordance with NE 107

20 DS/TTH300-EN Rev. D | TTH300


PROFIBUS PA / FOUNDATION Fieldbus device design: Instructions for customer-specific configuration

Configuration Selection
Number of sensors  1 sensor (standard)  2 sensors
Measurement type  Sensor redundancy / sensor backup
(for 2-sensor selection only)  Sensor drift monitoring ____°C / K sensor drift differential ____s time limit for drift overshoot
 Differential measurement: zero point where Ia = 4 mA
 Differential measurement: zero point where Ia = 12 mA
 Average measurement
IEC 60751 Resistance thermometer  Pt10  Pt50  Pt100 (Standard)  Pt200  Pt500  Pt1000
JIS C1604  Pt10  Pt50  Pt100
MIL-T-24388  Pt10  Pt50  Pt100  Pt200  Pt1000
DIN 43760  Ni50  Ni100  Ni120  Ni1000
OIML R 84  Cu10  Cu100
Resistance measurement  0 … 500 Ω  0 … 5000
IEC 60584 Thermocouple  Type K  Type J  Type N  Type R  Type S  Type T  Type E  Type B
DIN 43710  Type L  Type U
ASTM E-988  Type C  Type D
Voltage measurement  -125 … 125 mV  -125 … 1100 mV
Sensor circuit Two-wire  Three-wire (standard)  Four-wire
(for resistance thermometer and resistance Two-wire circuit: Compensation of Sensor Line Resistance. 100 Ω
measurement only)  Sensor 1: ____ Ω  Sensor 2: ____ Ω
Reference junction  Internal (for standard thermocouple, except type B)  None (type B)
(for thermocouples only)  External / temperature: ____°C
Unit Celsius (default)  Fahrenheit  Rankine  Kelvin
Resistance value at 0 °C / Ro Sensor 1: Ro: ___________ Sensor 2: Ro: ___________
Callendar-Van Dusen coefficient A A: ___________ A: ___________
Callendar-Van Dusen coefficient B B: ___________ B: ___________
Callendar-Van Dusen coefficient C C: ___________ C: ___________
(optional, for resistance thermometers only)
IDENT_number (PROFIBUS)  Device-specific 0x3470 (standard)  Profile 0x9700 (1 AI Block)
Bus address PROFIBUS PA  PA: 0 ... 125  Standard PA: 126
TAG number  ______________________ (maximum 16 characters)
Software write protection  Off (standard)  On

TTH300 | DS/TTH300-EN Rev. D 21


Notes

Notes

22 DS/TTH300-EN Rev. D | TTH300


Notes

Notes

Notes

TTH300 | DS/TTH300-EN Rev. D 23


Contact us

Note

DS/TTH300-EN Rev. D 11.2017


ABB Limited
We reserve the right to make technical changes or
Measurement & Analytics
modify the contents of this document without prior
Howard Road, St. Neots notice.
Cambridgeshire, PE19 8EU With regard to purchase orders, the agreed
UK particulars shall prevail. ABB does not accept any
responsibility whatsoever for potential errors or
Tel: +44 (0)870 600 6122
possible lack of information in this document.
Fax: +44 (0)1480 213 339
Mail: enquiries.mp.uk@gb.abb.com We reserve all rights in this document and in the
subject matter and illustrations contained therein.
Any reproduction, disclosure to third parties or
ABB Inc.
utilization of its contents – in whole or in parts – is
Measurement & Analytics forbidden without prior written consent of ABB.
125 E. County Line Road
Warminster, PA 18974 Copyright© 2016 ABB
All rights reserved
USA
Tel: +1 215 674 6000 3KXT231001R1001
Fax: +1 215 674 7183

ABB Automation Products GmbH


Measurement & Analytics
Schillerstr. 72 Sales Service
32425 Minden
Germany
Tel: +49 571 830-0
Fax: +49 571 830-1806

www.abb.com/temperature

You might also like