TTH300
TTH300
TTH300
TTH300
Head-mount temperature transmitter
Input Configuration
— RTD, resistance thermometers, resistance-type remote — FIM
sensor — DTM
— Thermocouples, voltages, mV voltages — EDD
— LCD display with push buttons (optional)
Electrical isolation of input circuit and output circuit
Global approvals for explosion protection
Input functionality — ATEX, IECEx, Zone 0
— 1 or 2 sensors — FM, CSA
— 2 x Pt100 three wire circuit — GOST, EAC Ex
— Inmetro
Specific linearization — NEPSI
— Callendar-Van Dusen coefficients — KOSHA
— Table of variate pairs / 32 points
SW write protection, HW write protection
Continuous sensor monitoring and self-monitoring
— Supply voltage monitoring Service interface
— Wire break and corrosion monitoring
in accordance with NE 89
— Extended diagnostics in accordance with NE 107
— Sensor drift monitoring
Change from one to two columns
TTH300
Head-mount temperature transmitter
Weight IP rating
— 50 g — Power supply circuit: IP20
— Measurement circuit: IP00 or IP rating of installation
Material housing
— Housing: polycarbonate
— Color: gray RAL9002
— Sealing compound: hard sealing compound
Installation conditions
— Mounting position: no restrictions
— Installation options:
Connection heads in accordance with DIN 43729 form B
Rail mounting (35 mm) in accordance with EN 60175 by
means of latching base
Field mount housing
Block structure
— Physical Block
— Transducer Block 1 – temperature
— Transducer Block 2 – HMI (LCD indicator)
— Transducer Block 3 – enhanced diagnosis
— Analog Input 1 – Primary Value (Calculated Value1))
— Analog Input 2 – SECONDARY VALUE_1 (sensor 1)
— Analog Input 3 – SECONDARY VALUE_2 (sensor 2)
— Analog Input 4 – SECONDARY VALUE_3 (reference
junction temperature)
— Analog Output – optional HMI display (Transducer Block 2)
— Discrete Input 1 – enhanced diagnosis 1 (Transducer Block 3)
— Discrete Input 2 – enhanced diagnosis 2 (Transducer Block 3)
1) Sensor 1, sensor 2 or difference or mean
Power supply
Two-wire technology, polarity safe; power supply lines = signal
lines
NOTICE
Following calculations apply for standard applications. This
should be taken into consideration when working with a
higher maximum current.
Max. permissible residual ripple for input terminal voltage Fig. 2: Maximum load depending on input terminal voltage
— During communication in accordance with HART FSK A TTH300 B TTH300 in Ex ia design C HART communication
"Physical Layer" specification. resistance
Long-term drift: ± 0.05 °C (± 0.09 °F) or ± 0.05 %1) per year; the larger value applies.
1) Percentages refer to the configured measuring span, omitted for PROFIBUS and FOUNDATION Fieldbus
2) Standard model
3) For digital measurement accuracy, the internal reference junction error must be added: Pt1000, DIN IEC 60751 Cl. B
Operating influence
The percentages refer to the configured measuring span.
Input terminal voltage effect / load effect: within the specified limit values for the voltage / load, the total influence is less than
0.001% per volt.
Ambient temperature effect: based on 23 °C (73.4 °F) for an ambient temperature range of -40 ... 85 °C (-40 ... 185 °F)4)
Sensor Ambient temperature effect per 1 °C (1.8 °F) Ambient temperature effect 1) 2) per
deviation from 23 °C (73.4 °F) for digital 1 °C (1.8 °F) deviation from 23 °C (73.4 °F)
measured value for DA-converter
Resistance thermometer for two-, three- and four-wire circuits
IEC, JIS, MIL Pt10 ± 0.04 °C (± 0.072 °F) ± 0.003 %
Pt50 ± 0.008 °C (± 0.014 °F) ± 0.003 %
Pt100 ± 0.004 °C (± 0.007 °F) ± 0.003 %
IEC, MIL Pt200 ± 0.02 °C (± 0.036 °F) ± 0.003 %
Pt500 ± 0.008 °C (± 0.014 °F) ± 0.003 %
Pt1000 ± 0.004 °C (± 0.007 °F) ± 0.003 %
DIN 43760 Ni50 ± 0.008 °C (± 0.014 °F) ± 0.003 %
Ni100 ± 0.004 °C (± 0.007 °F) ± 0.003 %
Ni120 ± 0.003 °C (± 0.005 °F) ± 0.003 %
Ni1000 ± 0.004 °C (± 0.007 °F) ± 0.003 %
OIML R 84 Cu10 ± 0.04 °C (± 0.072 °F) ± 0.003 %
Cu100 ± 0.004 °C (± 0.007 °F) ± 0.003 %
Resistance measurement
0 ... 500 Ω ± 0.002 Ω ± 0.003 %
0 ... 5000 Ω ± 0.02 Ω ± 0.003 %
Thermocouple, for all defined types ± [(0.001 % x (ME[mV] / MS[mv]) + (100 % x ± 0.003 %
(0.009 °C / MS [°C])]3)
Voltage measurement
-125 ... 125 mV ± 1.5 μV ± 0.003 %
-125 ... 1100 mV ± 15 μV ± 0.003 %
1) Percentages refer to the configured measuring span of the analog output signal
2) Influence of DA-converter omitted for PROFIBUS PA and FOUNDATION Fieldbus
3) ME = voltage value of the thermocouple at the upper range value in accordance with the standard
MA = voltage value of the thermocouple at the lower range value in accordance with the standard
MS = voltage value of the thermocouple over the measuring span in accordance with the standard. MS = (ME - MA)
4) If the optional extended ambient temperature range down to -50 °C (-58 °F) applies, the causal variables are doubled in the range between -50 ... -40 °C
(-58 ... -40 °F)
A B C D E F G H
1 1 1 1 1 1 1 1 1
I 2 2 2 2 2 2
J J 8
J J J 1
+
2
3 3 3 3 3 3 3 3 3 3
8
4 4 4 4
7
4
4
J 7
-
J 5
J 5
K
6 6 6
A10003-01
Fig. 3
A Potentiometer, four-wire circuit B Potentiometer, three-wire circuit C Potentiometer, two-wire circuit D 2 x RTD, three-wire circuit1)
E 2 x RTD, two-year wire 1) F RTD, four-wire circuit G RTD, three-wire circuit H RTD, two-wire circuit I Sensor 1 J Sensor 21)
K LCD indicator-interface
1 – 6 Sensor connection (from measuring inset) 7 – 8 4 … 20 mA HART, PROFIBUS PA, FOUNDATION Fieldbus
1) Sensor backup / sensor redundancy, sensor drift monitoring, mean measurement, or differential measurement
1 1 1 1 1 1 1 1
- - - -
H + + + +
2 2 2 2 2 2 2
J 8
J J 1
+
2
3 3 3 3 3
8
4
7
4
4
7
-
5 5 5 5 5
+ + + + + 5
I - - - -
J
-
6 6 6 6 6 6
A10004-01
Fig. 4
A 2 x voltage meter1) B 1 x voltage meter C 2 x Thermoelement1) D 1 x Thermoelement E 1 x RTD, four--wire circuit and
1 x Thermoelement1) F 1 x RTD, three--wire circuit and 1 x Thermoelement1) G 1 x RTD, two--wire circuit and 1 x Thermoelement1)
H Sensor 1 I Sensor 21) J LCD indicator-interface
1 – 6 Sensor connection (from measuring inset) 7 – 8 4 … 20 mA HART, PROFIBUS PA, FOUNDATION Fieldbus
1) Sensor backup / sensor redundancy, sensor drift monitoring, mean measurement, or differential measurement
— Measuring range 5
— General information, e.g. TAG number 2 3
— Damping 4
Diagnostic message
— Overrange / underrange in accordance with NE 43
— HART diagnosis
M4 x 23
M4
Ø 44,4 (1.75)
Ø 7 (0.28)
33 (1.3)
49,2 (1.94)
14 (0.55)
M4
57 (2.24)
2
30,2 (1.19)
5,5 (2.2)
24,7 (0.97)
35 (1.38) 35 (1.38)
50 (1.94) 50 (1.94)
A11119
Fig. 8: Dimensions in mm / inch
1 Interface for LCD display 2 Latching base for 35 mm (1.38 inch) Rail mounting in accordance with EN 60175
Model TTH300-E2X
Declaration of conformity
II 3 G Ex nA IIC T1-T6 Gc
XX XX XXX XX XX XX XX XX
Certificates
SIL2 - Declaration of Conformity 2) CS
Declaration of compliance according EN 10204-2.1, with the order C4
Inspection certificate according EN 10204-3.1, visual, dimensional and functional test C6
Calibration Certificates
With 5-point factory certificate EM
Inspection certificate according EN 10204-3.1, 5-point calibration EP
Handling of Certificates
Send via e-mail GHE
Send via mail GHP
Send via mail express GHD
Send with instrument GHA
Only archived GHS
Extended Ambient Temperature Range
-50 ... 85 °C (-58 ... 185 °F) 3) SE
Field Housing
Aluminium field housing 80 x 75 x 57 mm, IP 65, including 2 pieces M16 cable glands 4) H1
Polyester field housing 75 x 80 x 55 mm, IP 65, including 2 pieces M16 cable glands 4) H2
Polycarbonate field housing 80 x 82 x 55 mm, IP 65, including 2 pieces M16 cable glands 4) H3
Aluminium field housing 175 x 80 x 57 mm with separate terminal block, IP 65,
including 1 piece M16 and 2 pieces M20 cable glands 4) H5
Aluminium field housing 175 x 80 x 57 mm without separate terminal block, IP 65,
including 1 piece M16 and 2 pieces M20 cable glands 4) H6
Polyester field housing 190 x 75 x 55 mm with separate terminal block, IP 65,
including 1 piece M16 and 2 pieces M20 cable glands 4) H7
Polyester field housing 190 x 75 x 55 mm without separate terminal block, IP 65,
including 1 piece M16 and 2 pieces M20 cable glands 4) H8
Display Options
Prepared for display D1
Not prepared for display D2
LCD indicator type AS D3
Configurable LCD indicator type A D4
Mounting Options
Snap-on fixing set for 35 mm rail acc. EN 60175 (incl. fixing screws) SF
Customer-specific Versions
(Please specify) Z9
Trademarks
® HART is a registered trademark of FieldComm Group, Austin, Texas,
USA
® PROFIBUS and PROFIBUS PA are registered trademarks of PROFIBUS
& PROFINET International (PI)
® FOUNDATION Fieldbus is a registered trademark of FieldComm Group,
Configuration Selection
Number of sensors 1 sensor (standard) 2 sensors
Measurement type Sensor redundancy / sensor backup
(for 2-sensor selection only) Sensor drift monitoring ____°C / K sensor drift differential ____s time limit for drift overshoot
Differential measurement: zero point where Ia = 4 mA
Differential measurement: zero point where Ia = 12 mA
Average measurement
IEC 60751 Resistance thermometer Pt10 Pt50 Pt100 (Standard) Pt200 Pt500 Pt1000
JIS C1604 Pt10 Pt50 Pt100
MIL-T-24388 Pt10 Pt50 Pt100 Pt200 Pt1000
DIN 43760 Ni50 Ni100 Ni120 Ni1000
OIML R 84 Cu10 Cu100
Resistance measurement 0 … 500 Ω 0 … 5000
IEC 60584 Thermocouple Type K Type J Type N Type R Type S Type T Type E Type B
DIN 43710 Type L Type U
ASTM E-988 Type C Type D
Voltage measurement -125 … 125 mV -125 … 1100 mV
Sensor circuit Two-wire Three-wire (standard) Four-wire
(for resistance thermometer and resistance Two-wire circuit: Compensation of Sensor Line Resistance. 100 Ω
measurement only) Sensor 1: ____ Ω Sensor 2: ____ Ω
Reference junction Internal (for standard thermocouple, except type B) None (type B)
(for thermocouples only) External / temperature: ____°C
Measuring range Lower range value : ___________ (standard: 0)
Upper range value : ___________ (standard: 100)
Unit Celsius (default) Fahrenheit Rankine Kelvin
Characteristic behavior Rising 4 ... 20 mA (standard) Falling 20 ... 4 mA
Output behavior for error Overrange / 22 mA (standard) Underrange / 3.6 mA
Output attenuation (T63) Off (standard) ____ seconds (1 … 100 s)
Sensor number Sensor 1: ___________ Sensor 2: ___________
Resistance value at 0 °C / Ro Sensor 1: Ro: ___________ Sensor 2: Ro: ___________
Callendar-Van Dusen coefficient A A: ___________ A: ___________
Callendar-Van Dusen coefficient B B: ___________ B: ___________
Callendar-Van Dusen coefficient C C: ___________ C: ___________
(optional, for resistance thermometers only)
User characteristics based on linearization table Based on attached table of variate pairs
TAG number ___________ (maximum 8 characters)
HART revision HART5 (standard) HART7
Software write protection Off (standard) On
"Maintenance required" alarm pulse or Off (standard) pulse width ____ s (0.5 ... 59.5 s increment 0.5 s)
continuous signaling in accordance with NE 107
Configuration Selection
Number of sensors 1 sensor (standard) 2 sensors
Measurement type Sensor redundancy / sensor backup
(for 2-sensor selection only) Sensor drift monitoring ____°C / K sensor drift differential ____s time limit for drift overshoot
Differential measurement: zero point where Ia = 4 mA
Differential measurement: zero point where Ia = 12 mA
Average measurement
IEC 60751 Resistance thermometer Pt10 Pt50 Pt100 (Standard) Pt200 Pt500 Pt1000
JIS C1604 Pt10 Pt50 Pt100
MIL-T-24388 Pt10 Pt50 Pt100 Pt200 Pt1000
DIN 43760 Ni50 Ni100 Ni120 Ni1000
OIML R 84 Cu10 Cu100
Resistance measurement 0 … 500 Ω 0 … 5000
IEC 60584 Thermocouple Type K Type J Type N Type R Type S Type T Type E Type B
DIN 43710 Type L Type U
ASTM E-988 Type C Type D
Voltage measurement -125 … 125 mV -125 … 1100 mV
Sensor circuit Two-wire Three-wire (standard) Four-wire
(for resistance thermometer and resistance Two-wire circuit: Compensation of Sensor Line Resistance. 100 Ω
measurement only) Sensor 1: ____ Ω Sensor 2: ____ Ω
Reference junction Internal (for standard thermocouple, except type B) None (type B)
(for thermocouples only) External / temperature: ____°C
Unit Celsius (default) Fahrenheit Rankine Kelvin
Resistance value at 0 °C / Ro Sensor 1: Ro: ___________ Sensor 2: Ro: ___________
Callendar-Van Dusen coefficient A A: ___________ A: ___________
Callendar-Van Dusen coefficient B B: ___________ B: ___________
Callendar-Van Dusen coefficient C C: ___________ C: ___________
(optional, for resistance thermometers only)
IDENT_number (PROFIBUS) Device-specific 0x3470 (standard) Profile 0x9700 (1 AI Block)
Bus address PROFIBUS PA PA: 0 ... 125 Standard PA: 126
TAG number ______________________ (maximum 16 characters)
Software write protection Off (standard) On
Notes
Notes
Notes
Note