Measuring system The iTEMP HART TMT 182 temperature head transmitter is a two wire transmitter with
ananalogue output. It has measurement input for resistance thermometers (RTD) in 2-, 3- or 4-wire
connection, thermocouples and voltage transmitters. Setting up of the TMT 182 is done using the
HART -Protocol with hand operating module (DXR 275) or PC (COMMUWIN II).
Input
Measured variable Temperature (temperature linear transmission behaviour), resistance and voltage
Measuring range The transmitter records different measuring ranges depending on the sensor connection and
input signals.
Resistance 10 to 400 10
Resistance
transmitter 10 to 2000 100
2 Endress+Hauser
TMT 182
Output
Output signal Analogue 4 to 20 mA, 20 to 4 mA
Current limit 23 mA
Power supply
Electrical connection
Endress+Hauser 3
TMT 182
Performance characteristics
Response time 1s
1) % is related to the adjusted measurement range. The value to be applied is the greater.
Influence of cold junction Pt100 DIN IEC 751 Cl. B (internal cold junction with thermocouples TC)
Installation conditions
Installation instructions Installation angle:
no limit
Installation area:
Connection head accord. to DIN 43 729 Form B; TAF 10 field housing
4 Endress+Hauser
TMT 182
Environment conditions
Ambient temperature -40 to +85 C (-40 to 185 F) for Ex-area, see Ex-certificate
limits
Condensation allowable
Electromagnetic Shock resistance and interference emission as per EN 61 326-1 (IEC 1326) and NAMUR NE 21
compatibility (EMC)
Mechanical construction
Design, dimensions
Weight approx. 40 g
Material Housing:
PC
Potting:
PUR
Human interface
Display elements No display elements are present directly on the temperature transmitter.
The measured value display can be called up using the ReadWin 2000, COMMUWIN II or
FieldCare PC software.
Operating elements No operating elements are present directly on the display. The temperature transmitter is
configured via remote operation with the ReadWin 2000 PC software.
Endress+Hauser 5
TMT 182
Ex approval For further details on the available Ex versions (ATEX, CSA, FM, etc.), please contact your nearest
E+H sales organisation. All relevant data for hazardous areas can be found in separate Ex
documentation. If required, please request copies from us or your E+H sales organisation.
6 Endress+Hauser
TMT 182
Ordering information
Sensor TC ( )B ( )C ( )D ( )E ( )J
( )K ( )L ( )N ( )R ( )S
( )T ( )U
RTD ( ) Pt100 ( ) Pt500 ( ) Pt1000
( ) Ni100 ( ) Ni500 ( ) Ni1000
Note!:
High scale Range and min. span
,
Ende (s. Techn. data)
Offset , [-9,9...0...+9,9K]
TAG PCP
PROFIBUS-PA
Endress+Hauser 7
TMT 182
Certification
A Version for non hazardous areas
B ATEX II1G EEx ia IIC T4/T5/T6
C FM IS, Class I, Div. 1+2, Group A, B, C, D
D CSA IS, Class I, Div. 1+2, Group A, B, C, D
E ATEX II3G EEx nA IIC T4/T5/T6
F ATEX II3D
G ATEX II1G EEx ia IIC T6, II3D
H ATEX II3G EEx nA IIC T6, II3D
Configuration
A Standard factory configuration (Pt100/3-wire/0 to 100 C)
B Customised measurement range
C Customised expanded configuration for TC (see questionnaire)
D Customised expanded configuration for RTD (see questionnaire)
Model
A Standard model
B Works calibration certificate 6 test points
Customised options
51003527 TAG print/configuration 8 char
Accessories
Commubox FXA 191
Order code: FXA191-G1
PC-operating software: ReadWin 2000, COMMUWIN II or FieldCare
8 Endress+Hauser
TMT 182
ReadWin2000 can be downloaded free of charge from the internet from the following address:
www.endress.com/readwin
Hand operating module HART Communicator DXR 275, Order code: DXR275-...
Documentation
System information Temperature measurement (SI 008R/09/en)
Operating short manual iTEMP HART TMT 182 (KA 142R/09/a3)
Additional documentation for use in explosion-hazardous areas:
ATEX II1G: XA 006R/09/a3
ATEX II3G: XA 011R/09/a3
ATEX II3D: XA 027R/09/a3
FM, CSA, etc.
Operating manual iTEMP HART Communication (BA 139R/09/a3)
Operating short manual TAF 10 Field housing (KA 093R/09/a2)
Endress+Hauser 9
TMT 182
Endress+Hauser GmbH+Co.
Instruments International
P.O. Box 2222
D-79574 Weil am Rhein
Germany
Internet:
http://www.endress.com
11.01
TI 078R/09/en/01.03
510 02073
FM+SGML 6.0 ProMoDo