Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

EH Itemp

Download as pdf or txt
Download as pdf or txt
You are on page 1of 10

Wärtsilä id: DBAC157599 -

Technical Information

iTEMP® TMT181
Universal head transmitter for
resistance thermometers (RTD), thermocouples, resistance and voltage
transmitters, PC programmable, for installation in a terminal head form B

Application Your benefits


• PC programmable (PCP) temperature head transmitter for • Universally PC programmable for various signals
converting various input signals into an scalable 4 to 20 mA • 2 wire technology, 4 to 20 mA analog output
analog output signal • High accuracy in total ambient temperature range
• Input: • Fault signal on sensor break or short circuit, presettable to
Resistance thermometer (RTD) NAMUR NE 43
Thermocouple (TC) • EMC to NAMUR NE 21, CE
Resistance transmitter () • UL recognized component to UL 3111-1
Voltage transmitter (mV) • GL Germanischer Lloyd marine approval
• Online configuration using PC with TXU10-AA • Ex certification
configuration kit (accessory) – ATEX Ex ia and dust ex zone 22 in compliance with
EN 50281-1
– FM IS
– CSA IS
• Galvanic isolation
• Online configuration during measurement using SETUP
connector
• Customer-specific linearization
• Adjustment of characteristic curve
• Output simulation

TI00070R/09/EN/01.11
51001110
Wärtsilä id: DBAC157599 -
iTEMP® TMT181

Function and system design


Measuring principle Electronic measurement and conversion of input signals in industrial temperature measurement.

a0016026

Application example TMT181

Measuring system The iTEMP® PCP TMT181 temperature head transmitter is a two wire transmitter with an analog output. It
has measurement input for resistance thermometers (RTD) in 2-, 3- or 4-wire connection, thermocouples and
voltage transmitters. Setting up of the TMT181 is done using the TXU10-AA configuration kit.

Input
Input signal Resistance thermometer (RTD)

Type Measurement ranges min. measurement


range

as per IEC 751 Pt100 -200 up to 850 °C (-328 up to +1562 °F) 10 K (18 °F)
( = 0.00385) Pt500 -200 up to 250 °C (-328 up to +482 °F) 10 K (18 °F)
Pt1000 -200 up to 250 °C) (-328 up to +482 °F 10 K (18 °F)

as per Ni100 -60 up to 180 °C (-76 up to +356 °F) 10 K (18 °F)


DIN 43760 Ni500 -60 up to 150 °C (-76 up to +302 °F) 10 K (18 °F)
( = 0.00618) Ni1000 -60 up to 150 °C (-76 up to +302 °F) 10 K (18 °F)

Connection type 2-, 3- or 4-wire connection


cable resistance compensation possible in the 2 wire system
(0 up to 20 ).

Sensor cable resistance max. 11 per wire

Sensor current  0.6 mA

Resistance transmitter ()

Type Measurement ranges min. measurement range

Resistance () 10 up to 400 10


10 up to 2000 100

2 Endress+Hauser
Wärtsilä id: DBAC157599 -
iTEMP® TMT181

Thermocouple (TC)

Type Measurement ranges min. measurement


range

as per NIST B (PtRh30-PtRh6)1) 0 up to +1820 °C (32 up to 3308 °F) 500 °C (900 °F)
Monograph E (NiCr-CuNi) -200 up to +915 °C (-328 up to 1679 °F) 50 °C (90 °F)
175, IEC 584 J (Fe-CuNi) -200 up to +1200 °C (-328 up to 2192 °F) 50 °C (90 °F)
K (NiCr-Ni) -200 up to +1372 °C (-328 up to 2501 °F 50 °C (90 °F)
N (NiCrSi-NiSi) -270 up to +1300 °C (-454 up to 2372 °F) 50 °C (90 °F)
R (PtRh13-Pt) 0 up to +1768 °C (32 up to 3214 °F) 500 °C (900 °F)
S (PtRh10-Pt) 0 up to +1768 °C (32 up to 3214 °F) 500 °C (900 °F)
T (Cu-CuNi) -200 up to +400 °C (-328 up to 752 °F) 50 °C (90 °F)

as per ASTME C (W5Re-W26Re) 0 up to 2320 °C (32 up to 4208 °F) 50 °C (90 °F)


E988 D (W3Re-W25Re) 0 up to 2495 °C (32 up to 4523 °F) 50 °C (90 °F)

as per L (Fe-CuNi) -200 up to +900 °C (-328 up to 1652 °F) 50 °C (90 °F)


DIN 43710 U (Cu-CuNi) -200 up to +600 °C (-328 up to 1112 °F) 50 °C (90 °F)

w/o MoRe5-MoRe41 0 up to 2000 °C (32 up to 3632 °F) 500 °C (900 °F)

Cold junction internal (Pt100) or external (0 up to 80 °C (32 up to 176 °F))

Accuracy of cold junction ± 1 K (± 1.8 °F)

Sensor current 30 nA

1) Higher measurement error for temperatures below 300 °C (572 °F).

Voltage transmitter (mV)

Designation Measurement ranges min. measurement range

Millivolt transmitter (mV) -10 up to 100 mV 5 mV

Output
Output signal Current output
4 up to 20 mA, 20 to 4 mA

Signal on alarm
Measurement range undercut linear drop to 3.8 mA

Exceeding measurement range linear rise to 20.5 mA

Sensor breakage, sensor short circuit1)  3.6 mA or  21.0 mA

1) Not for thermocouple

Load Max. load: (Vsupply - 8 V) / 0.025 A

Transmission behavior Temperature linear, resistance linear, voltage linear

Galvanic isolation I/O: U = 2 kV AC

Filter 1st degree digital filter: 0 up to 8 s

Endress+Hauser 3
Wärtsilä id: DBAC157599 -
iTEMP® TMT181

Current limit  25 mA

Switch-on delay 4 s (Ia = 3.8 mA during swich-on)

Power supply
Terminal assignment Voltage supply and current output SETUP connector

a0016013 a0016014

Sensor connection 2-wire 3-wire 4-wire

a0016012 a0016011 a0016010

Supply voltage 8 up to 35 V DC, polarity protected


Ex version: 8 up to 30 V DC

Residual ripple Permissible residual ripple USS  5 V at Ub  13 V, fmax = 1 kHz

Performance characteristics
Response time 1s

Reference operating Calibration temperature 23 °C ± 5 K (73.4 °F ± 9 °F)


conditions

Maximum measured error Resistance thermometer (RTD)

Type Measurement accuracy 1)

Pt100, Ni100 0.2 K (0.36 °F) or 0.08 %

1) % is related to the adjusted measurement range (the value to be applied is the greater).

Resistance transmitter ()

Type Measurement accuracy 1) Measurement range

Resistance ± 0.1  or 0.08 % 10 up to 400 

± 1.5 or 0.12 % 10 up to 2000 

1) % is related to the adjusted measurement range (the value to be applied is the greater).

4 Endress+Hauser
Wärtsilä id: DBAC157599 -
iTEMP® TMT181

Thermocouple (TC)

Type Measurement accuracy 1)

K, J, T, E, L, U typ. 0.5 K (0.8 °F) or 0.08 %


N, C, D typ. 1.0 K (1.8 °F) or 0.08 %
S, B, R, MoRe5MoRe41 typ. 2.0 K (3.6 °F) or 0.08 %

Influence of the internal Pt100 DIN IEC 751 Kl. B


reference junction

1) % is related to the adjusted measurement range (the value to be applied is the greater).

Voltage transmitter (mV)

Type Measurement accuracy 1) Measurement range

Millivolt transmitter ± 20 μV or 0.08 % -10 up to 100 mV

Influence of the supply  ± 0.01 %/V deviation from 24 V 2)


voltage

Influence of the load  ± 0.02 %/100 2)

1) % is related to the adjusted measurement range (the value to be applied is the greater).
2) All data is related to a measurement end value (FSD) of 20 mA.

Long-term drift 0.1 K/year (0.18 °F/year) 1) or 0.05 %/year 1)2)

Influence of ambient Td = temperature drift


temperature  = deviation of ambient temperature from reference condition
For temperatures in °F, divide the result by 1.8.

Resistance thermometer (RTD):


Td = ± (15 ppm/K * max. measurement range + 50 ppm/K * preset measurement range) * 

Resistance thermometer Pt100:


Td = ± (15 ppm/K * (range end value+200) + 50 ppm/K * preset measuring range) * 

Thermocouple (TC):
Td = ± (50 ppm/K * max. measurement range + 50 ppm/K * preset measurement range) * 

Installation
Mounting location Terminal head as per DIN EN 50446 Form B; field housing TAF10

Orientation No restrictions

1) under reference conditions


2) % is related to the adjusted measurement range (the value to be applied is the greater).

Endress+Hauser 5
Wärtsilä id: DBAC157599 -
iTEMP® TMT181

Environment
Ambient temperature range -40 up to +85 °C (-40 up to +185 °F) (for Ex-areas, see Ex-certification or control drawings)

Storage temperature -40 up to +100 °C (-40 up to +212 °F)

Mechanical construction
Design, dimensions

a0003233

Dimensions of the head transmitter

Weight 40 g (1.41 oz.)

Materials Housing: PC
Potting: PUR

Terminals Cable up to max. 1.75 mm² (16 AWG)

Operability
Operating concept Remote operation
Configuration kit TXU10-AA (accessory)
Interface cable plus PC software Readwin® 2000
Interface: PC interface connection cable TTL -/- RS232 with plug
Configurable parameters: sensor type and connection type, measurement dimension (°C/°F), measurement
ranges, internal/external cold junction, compensation of cable resistance for 2-wire connection, signal on
alarm, output signal (4 up to 20 mA/20 to 4 mA), digital filter (damping), offset, measurement point
identification (8 characters), output simulation.

Certificates and approvals


CE mark This unit complies with the legal requirements laid out within the EU regulations.

Ex approval For further details on the available Ex versions (ATEX, CSA, FM, etc.), please contact your nearest E+H sales
organization. All relevant data for hazardous areas can be found in separate Ex documentation. If required,
please request copies from us or your E+H sales organisztion.

6 Endress+Hauser
Wärtsilä id: DBAC157599 -
iTEMP® TMT181

Ordering information
Product structure TMT181- Universally PC programmable for resistance thermometers, thermocouples, resistance and voltage
transmitters, 2-wire technology, 4 to 20 mA analog output, In/Out galvanic isolation, for mounting in Form
B head to DIN EN 50446, UL recognized component, ship building approval GL Germanischer Lloyd

Approval:
A Non-hazardous area
B ATEX II1G EEx ia IIC T4/T5/T6
C FM IS,NI,Class I,Div.1+2,Group ABCD
D CSA IS,NI,Class I,Div.1+2,Group ABCD
E ATEX II3G Ex nA II T4/T5/T6
F ATEX II3D
G ATEX II1G EEx ia IIC T6, II3D
H ATEX II3G Ex nA II T6, II3D
I FM+CSA IS,NI,Class I,Div.1+2,Group ABCD
J CSA General Purpose
K TIIS Ex ia IIC T4
L TIIS Ex ia IIC T6
1 NEPSI Ex ia IIC T4-T6
2 NEPSI Ex nA II T4-T6

Configuration Connection:
A Factory setup Pt 100 3-wire 0-100°C
1 Thermocouple TC
2 RTD 2-wire
3 RTD 3-wire
4 RTD 4-wire

Configuration Sensor Type:


A Factory setup Pt100 3-wire 0-100°C
B Type B, 0 up to 1820°C, min. span 500K
C Type C, 0 up to 2320°C, min. span 500K
D Type D, 0 up to 2495°C, min. span 500K
E Type E, -200 up to 1000°C, min. span 50K
J Type J, -200 up to 1200°C, min. span 50K
K Type K, -200 up to 1370°C, min. span 50K
L Type L, -200 up to 900°C, min. span 50K
N Type N, -270 up to 1300°C, min. span 50K
R Type R, -50 up to 1768°C, min. span 500K
S Type S, -50 up to 1768°C, min. span 500K
T Type T, -200 up to 400°C, min. span 50K
U Type U, -200 up to 600°C, min. span 50K
V Voltage transmitter -10 up to 100mV, Min. span 5mV
1 Pt100, -200 up to 850°C, min. span 10K, IEC751 ( = 0.00385)
2 Ni100, -60 up to 180°C, min. span 10K
3 Pt500, -200 up to 250°C, min. span 10K
4 Ni500, -60 up to 150°C, min. span 10K
5 Pt1000, -200 up to 250°C, min. span 10K
6 Ni1000, -60 up to 150°C, min. span 10K
7 Resistance transmitter 10 up to 400 Ohm, Min. span 10 Ohm
8 Resistance transmitter 10 up to 2000 Ohm, Min. span 100 Ohm

Configuration:
A Factory setup Pt100 3-wire 0-100°C
B Measuring range, see additional spec.
C TC config. range, see questionnaire
D RTD config. range, see questionnaire

Additional option:
A Standard - DIN mounting set
B Works calib.certif., 6-point, DIN mounting set
K US - M4 mounting screws

Endress+Hauser 7
Wärtsilä id: DBAC157599 -
iTEMP® TMT181

Customer-specific modifications:
PC no fixing kit
U1 Buy+Resell version (SC-USA)
V1 Buy+Resell version,Pyromation

Marking:
TZ1 Tagging (TAG), metal
TZ2 Tagging (TAG), on device
TZ3 Commissioning label, paper
TZ4 Tagging (TAG), fieldbus
TZ6 Tagging (TAG), by customer

TMT181-  Order code

Questionnaire

8 Endress+Hauser
Wärtsilä id: DBAC157599 -
iTEMP® TMT181

Accessories
Device-specific accessories Configuration kit TXU10-AA
Interface cable plus PC software Readwin® 2000

Ergänzende Dokumentation
Standard documentation • Operating instructions KA141R/09/
• ATEX Safety instructions:
– ATEX II1G: XA004R/09
– ATEX II3G: XA010R/09
– ATEX II3D: XA026R/09

Endress+Hauser 9
Wärtsilä id: DBAC157599 -

Instruments International

Endress+Hauser
Instruments International AG
Kaegenstrasse 2
4153 Reinach
Switzerland

Tel.+41 61 715 81 00
Fax+41 61 715 25 00
www.endress.com
info@ii.endress.com

TI00070R/09/EN/01.11
51001110
FM9 ProMoDo

You might also like