• Overview
1
• Technical changes
2
• Order code
3
• Description
4
• Operating
5
• Commissioning
6
• Parameter assignment
7
P500 0,03%
Premium
P420 0,04%
Advanced
P320 0,065%
P300
Basic
P2X0
P Compact
LH100, LH300
P280
Safety integrated
Improved HMI display +
+
Developed according to
New larger and improved display IEC61508 standards for SIL2/3
with Namur NE107 support and applications
quick start wizard
Bus communication
Unique safety start-up +
+
State of the art communication
Simple and advanced protocol with HART7, including
commissioning, patented Reduced response time Long tag support
Remote safety handling +
Speeds up control for more
efficient processes
Feature/Function Benefit
Clear display with diagnostic • Device status at a glance
icons acc. to NAMUR NE107 u • Easy and fast setup
and four operation buttons • User-friendly handling
HART7 communication • State of the art communication
protocol, including long tag support
u
• Unique tag names for extensive
inventories
Reduced response time u • Allows a speed up of the processes
SITRANS P320/420
Robustness Safe
• Housing material in aluminum • Full SIL-2/3 assessment
or stainless steel 316L • Intrinsic safety
• Membrane material in stainless • Ex approved, Ex I approved,
steel 316L, alloy C276, Monel 400, • IEC, ATEX, FM, CSA, KCC, EAC,
tantalum or gold INMETRO
• DNV-GL, LR, BV, ABS, KR,
RINA, CCS, etc.
• Dual seal, AD2000
Target industries/applications
No work in Ex areas
Calculation Example
New Data Logging function now available • User specific maintenance set up
SITRANS P410
Will be SITRANS P420
replaced by
Will be
SITRANS P DSIII SITRANS P320
replaced by
Effect of Static Pressure PKN = (0.1 x r) % / 70bar PKN = (0.1 x r) % / 70bar PKN = (0.1 x r) % / 70bar
PKS = 0.14% / 70bar PKS = 0.1% / 70bar PKS = 0.1% / 70bar
Total Performance (TD 1:1) 0.192 % 0.18% 0.12%
Long Term Stability 0.125% (in 5 years) 0.125% (in 5 years) 0.125% (in 5 years)
Step Response Time < 170 ms 135 ms DP / 105 ms P 135 ms DP / 105 ms P
SIL SIL proven in use for SIL 2/3 Developed according to Developed according to
applications IEC61508 standards for SIL2/3 IEC61508 standards for SIL2/3
applications applications
SFF > 91% SFF > 91%
• Overview
1
• Technical changes
2
• Order code
3
• Description
4
• Operating
5
• Commissioning
6
• Parameter assignment
7
DSIII P420
Advanced display
Tool less Display
New sensor-
fixation
electronics with
digital interface
Neck
capillary based
reference
connection
Piezo resistive
External electrical feed trough
silicon sensor
Piezo resistive TO8 Sensor carrier
silicon sensor
Overload membrane
Ceramic Separation membrane
plugs /
filling parts Oil filling plug
+ side - side + side - side
Unrestricted © Siemens AG 2018
Page 14 1-CWS-SITRANS-P320-420-2018-10-21-EN.pptx
SITRANS P420/320
• Overview
1
• Technical changes
2
• Order code
3
• Description
4
• Operating
5
• Commissioning
6
• Parameter assignment
7
P320: Exchange at the 5th digit the 4 with a 3 (P320 Gauge pressure 7MF030…)
Unrestricted © Siemens AG 2018
Page 16 1-CWS-SITRANS-P320-420-2018-10-21-EN.pptx
FI01
P320/P420; Communication; measuring cell filling
Explosion
Protection
approvals
Special approvals
• Overview
1
• Technical changes
2
• Order code
3
• Description
4
• Operating
5
• Commissioning
6
• Parameter assignment
7
Retaining screw
IA Output current
UH Auxiliary power
Remove the display from the holder Enable write protection with jumper
Jumper Jumper
(as delivered) set
Jumper is set:
• ID: L and
• Only the measured values can be
To read the display in any mounting
read.
position, you have the option of gradually • The display changes automatically
rotating the display 360°. between the measured values.
• Operation via the buttons is disabled.
• Overview
1
• Technical changes
2
• Order code
3
• Description
4
• Operating
5
• Commissioning
6
• Parameter assignment
7
Display
④ Device is write-protected.
⑤ Device in the parameter view: When you press the u
button in the parameter view, the parameter can be
edited and the "EDIT" symbol flashes..
⑥ Functional Safety is enabled.
⑦ The ID ③ and the displayed "INFO" symbol serve to
identify the diagnostic message. For the IDs of the
messages and their meaning, refer to the section
"Diagnostics and troubleshooting“
① Display of name and unit of: ⑧ NE 107 symbols. For a description and priority, refer to
• Measured values (Measurement view) the section "Diagnostics and troubleshooting”
• Parameters (Parameter view, Edit view) ⑨ Bar graph display for measured values or progress
② Specifies whether there are previous parameters indicator in wizards.
or subsequent parameters. ⑩ Main line; 5-digit display of measured values and
③ Display of Measured value number, Parameter parameter values..
number; ID of the messages ⑦ ⑪ Sign of the measured value..
Measurement view
Parameter view
Edit view
You change the parameter values in the edit view. Wizards are available for specific parameters.
1) Theuser PIN is factory set to 2457 in the device. When delivered, write protection is disabled
using the user PIN.
• Overview
1
• Technical changes
2
• Order code
3
• Description
4
• Operating
5
• Commissioning
6
• Parameter assignment
7
Set Lower fault current Hold down the button ► for 3 seconds.
• Overview
1
• Technical changes
2
• Order code
3
• Description
4
• Operating
5
• Commissioning
6
• Parameter assignment
7
With the "Pressure units" [01] parameter, you select the unit of the "Pressure"
(P1) measured value that is displayed in the measurement view.
Measurement view:
P1 pressure
Certain units are displayed differently on the display and in the enumeration
Display
Enumeration
For this adjustment you do not need to apply pressure to the device.
[02] LOWER RANGE Sets the lower range value without The lower range value (4 mA) corresponds
applied pressure. to 0% of the measuring range.
[03] UPPER RANGE Sets the upper range value without The upper range
applied pressure. value (20 mA) corresponds to 100% of the
measuring range.
[04] Damping Sets the damping (filtering) for smoothing of sudden process value variations.
The damping influences the reaction time of the device: When you increase the damping value,
the response time of the pressure transmitter to changes in the pressure measurement
increases.
• Pressure measurement u • The device uses a linear characteristic curve for pressure and level
• measurements.
• Level measurement u
• Volume flow measurement u • The device uses adjustable square root functions.
• Volume measurement The device uses the tank characteristic curves for various vessel
geometries.
u
• Customized characteristic curve In the "Customized characteristic curve" application, enter the
u breakpoints of the characteristic curve using remote operation
(e.g. SIMATIC PDM).
Hold at 0, square root Linear, square root Two step linear, Two step linear, square
square root root or bidirectional
flow measurement
ID [05]
Application
Volume flow VSOFF VSLN VSLN2 VSL2B
Mass flow MSOFF MSLN MSLN2 MSL2B
Parameter ID [20] Low flow cut-off ID [06] SQRT POINT
●: Range: 0 to 100% Range: 5 to 15%
Unrestricted © Siemens AG 2018
Page 54 1-CWS-SITRANS-P320-420-2018-10-21-EN.pptx
[05] Application Parameter
Access to other parameters [06], [16], [18],[19],[20],[21],[22]
Custom
Depending on the adjusted application parameter [05] other parameters are active.
Unrestricted © Siemens AG 2018
Page 55 1-CWS-SITRANS-P320-420-2018-10-21-EN.pptx
[07] Zero point adjustment
• Vent the pressure connection of • Make sure there is identical • “You have created a reference
the device. pressure in the two process pressure that is within the
connections. measurement limits.”
The effective measuring range is reduced by the amount of the upstream pressure.
Example: With an upstream pressure of 100 mbar, the effective measuring range of a 1- bar pressure
transmitter is reduced to a point between 0 and 0.9 bar.
LRV Example:
lower range value Customer has the 5bar (0.5MPa,72.5psi)
(4 mA) corresponds differential pressure measuring cell.
to 0% of the He wants to comission the P420 by applying the
measuring range. pressure. (LRV = 0.5bar 4mA; URV = 4.5 bar)
URV
upper range 0.5 bar pressure present
value (20 mA) [08] Apply LRV press ► now LRV 0.5bar and span
corresponds to shifted to 5.5bar
100% of the
measuring range
Normal operation
[10] Select fault current Selects whether the lower [11] or upper [12] fault current is output when a fault occurs
[02] LRV Lower Range Value
[03] URV Upper Range Value
Unrestricted © Siemens AG 2018
Page 58 1-CWS-SITRANS-P320-420-2018-10-21-EN.pptx
[15] SV selection
LEVEL Level
VOL Volume
USER Custom
Depending on • Level
Application • Volume
Parameter [05] • Mass flow
• Volume flow
bbl: barrel
Nm3: Normal cubic meter
SCF: Standard cubic foot
ºC Celsius
ºF Fahrenheit
ºR Rankine
Level
Volume
Freely selectable numeric value
Volume flow
Mass flow
Custom units
ID [05] Application
Volume flow VSOFF
Mass flow MSOFF
Sets the height of the vessel bottom for the following vessel Sets the length of the bottom vessel for a lying
shapes: parabolic ends vessel (PARAE).
For the calculated volume to correspond to the actual vessel volume, set the parameters
Vessel dimension A and Vessel dimension L as follows: Vessel dimension L + 2 • Vessel dimension A = 100%.
Example: Vessel dimension L is 80% and vessel dimension A is 10%.
Enables the button lock. You can continue operating the device via HART.
Setting range On Button lock enabled
OFF Button lock disabled
Requirement:
The User PIN parameter is enabled.
[27] User PIN
Setting 1 to 65535
range:
Factory 2457
setting:
PUK entered
Correct: "NEW PIN - 2457" appears.
Wrong: "FAILD" appears
PIN related Parameters: [24] Change PIN; [25] Recovery ID; [26] PIN Recovery
[30] Display test Used to check that numbers, texts and symbols appear correctly on the display.
To start the display test, press the ►button and select "START".
When the display test is complete, the message "COMPL" appears.
Loop test [31] Sets a constant loop current for test purposes.
You have the option of selecting preset values or a user-defined value.
Setting range: 3.55; 4; 12; 20;22.8mA or User defined
[32] Start view Selects the value that is displayed as the first
measured value in the measurement view.
[33] Pressure Used to adapt the display of the pressure unit NONE: Not specified
reference to your application. GAUGE: Gauge pressure
ABS: Absolute pressure
[34] Identify the Enables or disables the device identification ON: Device identification enabled
device via HART. With device identification enabled, OFF: Device identification disabled
the device responds to a request with the
HART command "Find device".
Meaning
CUST Restore ordered configuration With this function you return your device to its delivery
state.
SENSR Reset to sensor calibration Resets the zero point and sensor calibration to the
factory setting.
DAC Reset DAC trim to the factory setting Resets the DAC trim (digital-to-analog converter trim)
to the factory setting.
The DAC trim is used to calibrate the 4 mA and 20 mA
end points of the analog output with an external
reference (e.g. current measurement device). The
DAC trim is available over remote operation.
FACT Factory reset With this function you return your device to its factory
setting.
• Overview
1
• Technical changes
2
• Order code
3
• Description
4
• Operating
5
• Commissioning
6
• Parameter assignment
7
The ID and the displayed "INFO" symbol serve to identify the diagnostic
message. Example below: ID Co
Device status
Failure
Out of specification
Function test
Maintenance
Required
Unrestricted © Siemens AG 2018
Page 77 1-CWS-SITRANS-P320-420-2018-10-21-EN.pptx
Display
– NAMUR NE 107 Examples
ID Message Cause/Remedy
Co Loop current fixed The loop current is being held at a fixed value and is not
responding to process variations.
Manual operation
Enter the loop current output value for simulation.
Disable the simulation to return to normal operation.
CP Loop current in saturation The loop current has reached its upper (or lower) saturation
limit and cannot increase (or decrease) any further.
Process value warning
Adjust loop current scaling.
Display
SIMATIC
PDM
• Overview
1
• Technical changes
2
• Order code
3
• Description
4
• Operating
5
• Commissioning
6
• Parameter assignment
7
Subject to changes and errors. The information given in this document only contains general descriptions and/or performance features which may
not always specifically reflect those described, or which may undergo modification in the course of further development of the products. The requested
performance features are binding only when they are expressly agreed upon in the concluded contract.