Sono40 Data Sheet
Sono40 Data Sheet
Sono40 Data Sheet
SonoMeter 40
Energy Meters
Description Features
• Available in nominal flow rates qp 0.6, 1.5, 2.5,
3.5, 6.0, 10.0, 15.0, 25.0, 40.0 and 60 m3/h
• Triple communication with M-Bus, wMBus
onboard + 1 additional communication module
slot
• Housings with thread (G3/4 to G2) or flange
(DN 20 to DN 100) connections
• MID approval for ultrasonic energy meter with
dynamic range of 1:100 (qi:qp) in class 2
• Optional MID approved dynamic range of 1:250
in class 2
• Temperature range 0 - 180 °C
• Nominal pressure PN25 bar as standard
• Calculator with IP65 protection class as
standard (IP68 on special request)
• Flow sensor with IP68 protection class as
standard
• Return or supply pipe installation, for vertical or
horizontal mounting
• Battery lifetime for at least 15+1 years
The Danfoss SonoMeter 40 is a range of • Low pressure loss, insensitive to dirt
ultrasonic, compact energy meters intended for • No calming sections needed before or after the
measuring energy consumption in heating and flow sensor (DN 15-DN 50)
cooling applications for billing purposes. The • For DN 65 to DN 100 calming sections are
meters are designed for remote meter read-out needed (5 x DN on inlet and 3 × DN on outlet of
(AMR). flow sensor)
• Remote reading via M-Bus, radio OMS 868 MHz,
SonoMeter 40 energy meters consist of RS 485 Modbus, BACnet, LoRA-WAN, pulse
an ultrasonic flow sensor, a pair of Pt500 output or optical interface
temperature sensors and a calculator • Two pulse inputs or outputs (always included,
with integrated circuits for temperature optionally with pre installed cable)
measurement, flow calculation and energy
calculation.
Calculator
IP [EN60529] 65 (68 on special request)
Voltage 3.6V DC
Battery Supply Battery type and size 2x Lithium Battery, AA-size
Battery life time 15+1 years (including AMR communication)
12 V - 36 V AC
Voltage 12 V - 42 V DC
Galvanically isolated
Power consumption not more than 20 mA
Mains supply 24 V AC/DC Alternating current voltage frequency 50/60 Hz
(internal module) Internal backup battery: 1x AA-size
Service life not less than 15 years (without data reading via
Backup supply
a digital or wireless interface) - for powering of the meter,
when the external power supply is turned off.
Mains supply cable 2 wire copper cable with a diameter of 2 × 0.25 mm²
230 VAC +10% -15%
Voltage to 24VAC transformer for connection to mains power
supply 24 AC/DC module.
Power consumption not more than 5 mA
Mains supply 230 V AC Alternating current voltage frequency 50/60 Hz
(external transformer) Internal backup battery: 1x AA-size
Service life not less than 15 years (without data reading via
Backup supply
a digital or wireless interface) - for powering of the meter,
when the external power supply is turned off.
Mains supply cable 2 wire copper cable with a diameter of 2 × 0.25 mm²
85 x 35 mm LCD display with 8 digits (11.5 mm high main characters)
Display
Menu guide and info panel
Display Units MWh - kWh - GJ - Gcal - °C - m3 - m3/h
Display Values Energy - volume - flow rate - power - temperatures
Optical interface Always included According to EN61107 (IEC1107)
1. M
-Bus according to EN13757-3, supports 300, 2400,
To be specified when ordering the
Communication 4800, 9600 baud. Delivered with 1,5 m cable.
meter. Both options can be selected.
2. wM-Bus 868 MHz (S1, T1 OMS)
1. Wired M-Bus
Delivered from factory or later
Additional 2. Modbus RTU
upgrade. One option from the list is
communication 3. BACnet MS/TP
possible.
4. LoRaWAN
Technical specifications
(continuous)
Flow sensor
Diameter DN 15 DN 20 DN 15 DN 20 DN 15 DN 20 DN 20 DN 25 DN 25 DN 40 DN 50 DN 65 DN 80 DN 100
Nominal flow qp (m3/h) 0.6 1.0 1.5 2.5 3.5 6 10 15 25 40 60
Max flow qs (m3/h) 1.2 2 3 5 7 12 20 30 50 80 120
Minimum flow (1:100) qi (m3/h) 0.006 0.01 0.015 0.025 0.035 0.06 0.1 0.15 0.25 0.4 0.6
Cut off flow qc (m3/h) 0.003 0.005 0.003 0.005 0.005 0.007 0.012 0.02 0.03 0.05 0.08 0.12
Overflow qss (m3/h) 1.44 2.4 3.6 6 8.4 14.4 24 36 60 96 144
Pressure drop at qp (mbar) 70 9 113 25 171 58 72 94 198 90 100 180 120 200 180 180
Kvs values 2.27 6.32 2.97 6.32 3.63 6.23 5.59 8.15 5.62 11.67 18.97 23.57 43.3 55.9 94.3 141.4
Connection G¾B G1B FL G¾B G1B FL G¾B G1B FL G1B G1B FL G1B G1¼B G1¼B G2B FL FL FL FL FL
Overall length (mm) 110 190 110 190 110 165 190 130 190 130 260 260 300 270 300 300 360
Material of flow sensor CW617N CC770S
Pressure PN (bar) 25 bar
IP [EN60529] IP68
Temperature media (°C) Θq: 0.1 - 130 °C
Cable length 1.2 m, 2.5 m or 5 m
Any position; DN 15 - DN 50: No calming sections needed
Mounting
DN 65 - DN 100: calming sections are needed (5 x DN on inlet and 3 x DN on outlet)
Temperature sensor
Type Pt500, 2 wire, according to EN1434, EN60751
Ø5.2 mm / IP65
Size / IP
Ø6 mm / IP67
Cable length 1.5 m, 3 m, 5 m or 10 m
Accuracy Class B (EN60751)
Approved temp. range EN60751 Θ: 0 - 150 °C
Difference temp. EN60751 ΔΘ: 3 - 150 K
Pressure 25 bar
Mounting without pockets for sizes G3/4 and G1 only
For versions with not openable enclosure (IP68), when meter is ordered with the pulse inputs, a
permanently connected 1,5 m cable is fitted in the meter for connecting the pulse inputs.
Pulse outputs
Number of pulse outputs 2 or no (to be specified when ordering)
Class OB in operating mode (OD in test mode)
Type open collector
Permissible current up to 20 mA
Voltage up to 24 V
Pulse duration 125 ms in operating mode (1.2 ms in test mode)
- when the output is configured for water quantity, the value of its pulses can be selected from
the list:
0,001; 0,01; 0,1; 1; 10 m³/pulse
For versions with not openable enclosure (IP68), when meter is ordered with the pulse outputs, a
permanently connected 1,5 m cable is fitted in the meter for connecting the pulse outputs.
Data logger Following hourly, daily and monthly parameter values are recorded in energy meter memory (can be
configured by SonoMeter 40 UserConfig software):
1............. Integrated heating energy
2............. Integrated cooling energy
3............. Integrated energy of tariff 1
4............. Integrated energy of tariff 2
5............. Integrated volume of liquid
6............. Integrated pulse value in pulse input 1
7............. Integrated pulse value in pulse input 2
8............. Maximum thermal power value for heating and date
9............. Maximum thermal power value for cooling and date
10.......... Maximum flow rate value and date
11........... Maximum value of flow temperature of heat conveying liquid and date
12........... Maximum value of return temperature of heat conveying liquid and date
13.......... Minimum value of flow temperature of heat conveying liquid and date
14.......... Minimum value of return temperature of heat conveying liquid and date
15.......... Minimum value of temperature difference and date
16.......... Average value of flow temperature of heat conveying liquid
17........... Average value of return temperature of heat conveying liquid
18.......... Operating time without an error of thermal energy calculation
19.......... Total error code
20.......... Time when the flow rate exceeded 1.2 qs
21.......... Time when the flow rate was less than qi
Bifunctional meters When the cooling energy tariff function is activated, in case of a negative temperature differential,
energy will be accumulated in the additional tariff register Q . In this case, energy values are
calculated according to the following formulas:
– when the flow sensor is in the supply line
when Θ1 > Θ2: Q = V · ρ1 · (hΤ1-hΤ2), Q = 0
when Θ1 < Θ2: Q = V · ρ1 · (hΤ2-hΤ1), Q = 0
– when the flow sensor is in the return line
when Θ1 > Θ2: Q = V · ρ2 · (hΤ1-hΤ2), Q = 0
when Θ1 < Θ2: Q = V · ρ2 · (hΤ2-hΤ1), Q = 0
Application drawings
Flow direction
Flow direction
Accuracy
5
4
3
2
Error [%]
1
0
-1
-2
Key
-3
EN1434 class 2
-4
typical accuracy
-5
qi qp qs
Pressure loss
Menu structure
INT 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9
Integral parameters
Long press
BIL 2.1 2.2 2.3 2.4 2.5 2.6.1 2.7.1 2xx 2.15.1 Shift down
Statistical data
Short press
INF 3.1 3.2 3.3 3.4 3.5 3.6.1 3.7 3x 3.15 Shift to the right
Informative parameters
Mounting
5 x DN 3 x DN
flow
Dimensions
Calculator
Dimensions
(continuous) Flow sensor qp= 0.6/1.0/1.5/2.5 m³/h
L=190 mm
a) connection type: thread G1“
b) connection type: flanges DN20
a)
b)
Dimensions
(continuous) Flow sensor qp= 3.5 m³/h
L=260 mm
a) connection type: thread G1 1/4“
b) connection type: flanges DN25
c) connection type: flanges DN32
a)
b)
c)
Dimensions
(continuous) Flow sensor qp= 6 m³/h
L=260 mm.
a) connection type: thread G1 1/4“
b) connection type: flanges DN25
c) connection type: flanges DN32
a)
b)
c)
Dimensions
(continuous) Flow sensor qp= 10.0 m³/h
L=300 mm
a) connection type: thread G2“
b) connection type: flanges DN40
a)
b)
Dimensions
(continuous) Flow sensor qp= 25 m³/h
L=300 mm
connection type: flanges DN65
Ordering
SonoMeter 40 - Heating
Nominal flow, size and Cable length Cable length Communication
connection type Installation transducer cable temperature sensor Power supply integrated Modules Energy unit Code no.
Return 1.2m 1.5m Battery 3.6V DC (2 AA-cell) MBus - kWh 187F2000
Supply 1.2m 1.5m Battery 3.6V DC (2 AA-cell) MBus - kWh 187F2001
Return 1.2m 1.5m Battery 3.6V DC (2 AA-cell) MBus+OMS - kWh 187F2026
DN15 qp0.6m³/h G¾ Supply 1.2m 1.5m Battery 3.6V DC (2 AA-cell) MBus+OMS - kWh 187F2027
110mm Return 1.2m 1.5m Mains power 230V MBus - kWh 187F2052
Supply 1.2m 1.5m Mains power 230V MBus - kWh 187F2053
Return 1.2m 1.5m Battery 3.6V DC (2 AA-cell) MBus - GJ 187F2084
Supply 1.2m 1.5m Battery 3.6V DC (2 AA-cell) MBus - GJ 187F2085
Return 1.2m 1.5m Battery 3.6V DC (2 AA-cell) MBus - kWh 187F2002
Supply 1.2m 1.5m Battery 3.6V DC (2 AA-cell) MBus - kWh 187F2003
Return 1.2m 1.5m Battery 3.6V DC (2 AA-cell) MBus+OMS - kWh 187F2028
Supply 1.2m 1.5m Battery 3.6V DC (2 AA-cell) MBus+OMS - kWh 187F2029
DN15 qp1.5m³/h G¾ Return 1.2m 1.5m Mains power 230V MBus - kWh 187F2054
110mm Supply 1.2m 1.5m Mains power 230V MBus - kWh 187F2055
Return 1.2m 1.5m Mains power 230V MBus - MWh 187F2078
Return 1.2m 1.5m Battery 3.6V DC (2 AA-cell) MBus - GJ 187F2086
Supply 1.2m 1.5m Battery 3.6V DC (2 AA-cell) MBus - GJ 187F2087
Supply 1.2m 3m Battery 3.6V DC (2 AA-cell) MBus - kWh 187F2118
Return 1.2m 1.5m Battery 3.6V DC (2 AA-cell) MBus - kWh 187F2004
Supply 1.2m 1.5m Battery 3.6V DC (2 AA-cell) MBus - kWh 187F2005
Return 1.2m 1.5m Battery 3.6V DC (2 AA-cell) MBus+OMS - kWh 187F2030
DN20 qp1.5m³/h G1 Supply 1.2m 1.5m Battery 3.6V DC (2 AA-cell) MBus+OMS - kWh 187F2031
130mm Return 1.2m 1.5m Mains power 230V MBus - kWh 187F2056
Supply 1.2m 1.5m Mains power 230V MBus - kWh 187F2057
Return 1.2m 1.5m Battery 3.6V DC (2 AA-cell) MBus - GJ 187F2088
Supply 1.2m 1.5m Battery 3.6V DC (2 AA-cell) MBus - GJ 187F2089
Return 1.2m 1.5m Battery 3.6V DC (2 AA-cell) MBus - kWh 187F2006
Supply 1.2m 1.5m Battery 3.6V DC (2 AA-cell) MBus - kWh 187F2007
Return 1.2m 1.5m Battery 3.6V DC (2 AA-cell) MBus+OMS - kWh 187F2032
Supply 1.2m 1.5m Battery 3.6V DC (2 AA-cell) MBus+OMS - kWh 187F2033
DN20 qp2.5m³/h G1
Return 1.2m 1.5m Mains power 230V MBus - kWh 187F2058
130mm
Supply 1.2m 1.5m Mains power 230V MBus - kWh 187F2059
Return 1.2m 1.5m Battery 3.6V DC (2 AA-cell) MBus - GJ 187F2090
Supply 1.2m 1.5m Battery 3.6V DC (2 AA-cell) MBus - GJ 187F2091
Supply 1.2m 3m Battery 3.6V DC (2 AA-cell) MBus - kWh 187F2119
Ordering
SonoMeter 40 - Combined heating and cooling
Nominal flow, size and Cable length Cable length Communication
connection type Installation transducer cable temperature sensor Power supply integrated Modules Energy unit Code no.
Return 1.2m 1.5m Battery 3.6V DC (2 AA-cell) MBus - kWh 187F2600
Supply 1.2m 1.5m Battery 3.6V DC (2 AA-cell) MBus - kWh 187F2601
Return 1.2m 1.5m Battery 3.6V DC (2 AA-cell) MBus+OMS - kWh 187F2626
Return 1.2m 1.5m Mains power 230V MBus - kWh 187F2639
Return 1.2m 1.5m Mains power 230V MBus+OMS - kWh 187F2652
DN15 qp0.6m³/h G¾ Return 1.2m 1.5m Mains power 230V - Modbus kWh 187F2665
110mm Return 1.2m 1.5m Mains power 24V AC/DC - Modbus kWh 187F2678
Supply 1.2m 1.5m Mains power 230V - BACnet kWh 187F2691
Supply 1.2m 1.5m Mains power 24V AC/DC - BACnet kWh 187F2704
Supply 1.2m 1.5m Mains power 24V AC/DC - Modbus kWh 187F2725
Return 1.2m 1.5m Mains power 230V - BACnet kWh 187F2738
Return 1.2m 1.5m Mains power 24V AC/DC - BACnet kWh 187F2751
Return 1.2m 1.5m Battery 3.6V DC (2 AA-cell) MBus - kWh 187F2602
Supply 1.2m 1.5m Battery 3.6V DC (2 AA-cell) MBus - kWh 187F2603
Return 1.2m 1.5m Battery 3.6V DC (2 AA-cell) MBus+OMS - kWh 187F2627
Return 1.2m 1.5m Mains power 230V MBus - kWh 187F2640
Return 1.2m 1.5m Mains power 230V MBus+OMS - kWh 187F2653
DN15 qp1.5m³/h G¾ Return 1.2m 1.5m Mains power 230V - Modbus kWh 187F2666
110mm Return 1.2m 1.5m Mains power 24V AC/DC - Modbus kWh 187F2679
Supply 1.2m 1.5m Mains power 230V - BACnet kWh 187F2692
Supply 1.2m 1.5m Mains power 24V AC/DC - BACnet kWh 187F2705
Supply 1.2m 1.5m Mains power 24V AC/DC - Modbus kWh 187F2726
Return 1.2m 1.5m Mains power 230V - BACnet kWh 187F2739
Return 1.2m 1.5m Mains power 24V AC/DC - BACnet kWh 187F2752