Pressure Switch
EDS 3300
with Menu Navigation to VDMA
3
Description: Technical data:
The EDS 3300 is a compact electronic Input data
pressure switch with integrated Measuring ranges -1..1; 1; 2.5; 6; 10; 16 bar
digital display for relative pressure Overload pressures 3; 3; 8, 18, 30, 48 bar
measurement in the low-pressure Burst pressures 5; 5; 12; 30; 50; 80 bar
range. Mechanical connection G1/4 A DIN 3852
It has a ceramic measuring cell with Threaded port DIN 3852-G1/4
thick-film strain gauge. The instrument Torque value 20 Nm
can have one or two switching outputs, Parts in contact with medium Mech. connection: Stainless steel
and there is the option of an additional Sensor cell: Ceramic
switchable analogue output signal Seal: FPM / EPDM
(4 .. 20 mA or 0 .. 10 V). (as per model code)
A special design feature of the Output data
EDS 3300 is that the display can be Accuracy to DIN 16086, ≤ ± 0.5 % FS typ.
rotated in two planes. The unit can Max. setting ≤ ± 1 % FS max.
be installed in almost any mounting (display, analogue output)
position and the display can be turned Repeatability ≤ ± 0.25 % FS max.
to the optimum position without Temperature drift ≤ ± 0.025 % FS / °C max. zero point
the usual additional expense of a ≤ ± 0.025 % FS / °C max. range
mechanical adapter. The 4-digit display Analogue output (optional)
can indicate the pressure in bar, psi or Signal selectable:
MPa. The user can select the particular 4 .. 20 mA load resistance max. 500 W
measurement unit. When changing to a 0 .. 10 V load resistance min. 1 kW
different measurement unit, the Switch outputs
EDS 3300 automatically converts all Type PNP transistor output
the switching settings to the new unit of Switching current max. 1.2 A
measurement. Switching cycles > 100 million
The main applications of the Reaction time < 10 ms
EDS 3300 are primarily in hydraulics Long-term drift ≤ ± 0.3 % FS typ. / year
and pneumatics, as well as in Environmental conditions
refrigeration and air conditioning Compensated temperature range -10 .. +70 °C
technology. Operating temperature range -25 .. +80 °C (-25 ... +60 °C acc. to UL spec.)
Storage temperature range -40 .. +80 °C
Special features: Fluid temperature range -25 .. +80 °C
Menu navigation according to VDMA
mark EN 61000-6-1 / 2 / 3 / 4
1 or 2 PNP transistor switching mark1) Certificate No. E318391
outputs, up to 1.2 A load
Vibration resistance to ≤ 10 g
per output DIN EN 60068-2-6 at 10 .. 500 Hz
Accuracy ≤ ± 1 % FS Shock resistance to ≤ 50 g
Optional analogue output selectable DIN EN 60068-2-29 (11 ms)
(4 .. 20 mA / 0 .. 10 V) Protection class to IEC 60529 IP 67
4-digit digital display Other data
Optimum alignment - can be Supply voltage 9 .. 35 V DC without analogue output
rotated in two planes (axes) 18 .. 35 V DC with analogue output
for use acc. to UL spec. - limited energy - according to
Measured value can be displayed in 9.3 UL 61010; Class 2;
bar, psi or MPa UL 1310/1585; LPS UL 60950
User-friendly due to Current consumption max. 2.455 A total
key programming max. 35 mA with inactive switching outputs
Switching points and switch-back max. 55 mA with inactive switching outputs
hystereses can be adjusted and analogue output
E 18.369.2/11.13
Additional functions:
Switching mode of the switching outputs
adjustable (switching point function or
window function)
housing
Switching direction of the switching turns thru
outputs adjustable (N/C or N/O function) 340°
50