Infrared Refrigerant Leak Transmitters & Monitors

DESCRIPTION Smart II
IIR-FD-R
Analog and digital, RS-485 communicating, addressable infrared sensors/
transmitters and monitors with relay outputs for the detection of refrigerant
in the ambient air.

APPLICATION
To detect trace amounts of refrigerant gases in commercial applications,
such as mechanical and chiller rooms, ventilation in-situ warehouse
refrigerator/freezer systems. Transmits its information to any compatible
electronic analog or digital MODBUS controller, DDC/PLC, or automation
system, and for direct daisy-chain/multi-drop link to the IQ4C/IM controllers
in accordance with ASHRAE standards.

FEATURES
NRTL
• Continuous monitoring • Operates at sub-freezing “Pending”
• 4-20 mA/2-10 VDC analog signal temperatures
• RS-485 serial communication output • Liquid Crystal Display (LCD)
OptoMux or MODBUS, selectable • LED status indicators
• Three (3) relay outputs: • Built-in buzzer
- Three stage control • Simple, menu-driven non-
- Fail-safe assignable intrusive calibration
• Infrared, gas-specific sensing • Fuse protected
technology, long-life, and temperature • Easy maintenance
compensated • NEMA 4X enclosure
• R11, R22, R123, R134a, R404, • 2-year warranty
R407C, R410A, R507, and many more

SPECIFICATIONS
Electric Sensor life expectancy
Power Supply 24 VAC (15-24 VAC), floating, - IR sensing element Min. 10 years
50/60 Hz; or 24 VDC (18-30 VDC) - IR source Min. 5 years, field replaceable
Protection Two (2) fuses, polyswitch type Sensor coverage 2,000 sq. ft., max. 5,000 sq. ft.
(1x1.6 A and 1x50 mA) (186 m2, max. 464 m2),
Power Consumption 1.0 A (28 VA), max. under “ideal conditions”
Sensor Performance Installation Location
Gas detected Refrigerants Location Below chiller,
Refer to section: within 5 - 6 feet (1.5 - 1.8 m)
“Ordering Information” Mounting height 0.5 - 1.0 ft. (0.16 - 0.31 m),
Sensor element Beam absorption infrared, above floor
gas sampling cell, w/constant (air sampling intake downwards)
temperature control Type of Control
Gas sampling method Diffusion or pump through General Continuous proportional analog
Range 0-100 ppm for R123, signal, digital communication, and
0-1000 ppm for other refrigerants binary/relay three-stage control;
factory calibrated i.e. Low-med-high (fault)
Resolution 1 ppm Analog output (1) 4-20 mA, max. impedance
Accuracy ± 3 % of reading 600 , or 2-10 VDC;
Repeatability ± 1 % of full scale min. impedance 20 k, jumper
Ouput drift Max. 2% of full scale/year selectable
Response time < 90 sec. to 90% of step change Digital output (1) RS-485 serial communication;
Calibration OptoMux protocol for IQ4 or IM
- interval recommended 12 to 18 months controllers, or MODBUS protocol;
- adjustment Simple 2-point settings, applying selectable
calibration gas standards Binary/relay outputs (3) SPDT, 125 VAC/0.3 A,
30 VDC/1.0 A

Customer Services (858) 578-7887 & (888) GO INTEC Fax (858) 578-4633 & (888) FX INTEC Specification subject to change without notice.
INTEC Controls, 12700 Stowe Dr. Suite 110, Poway, CA 92064 www.inteccontrols.com Page 1 of 5 Printed in USA 0901026
IIR-FD-R

SPECIFICATION
Type of Control (Cont...) Physical (Cont...)
- stage level/setpoint Adjustable for each relay over full - protection NEMA 4X (IP66)
sensor range - installation Wall (surface) mounted
- hysteresis/ Dimensions (HxWxD) 4.73 x 7.87 x 3.54 in.
switching differential Selectable for each relay (120 x 200 x 90 mm)
- relay assignment Cable entry 1 hole for ½ in. conduit for wall
and configuration Independent, individually set to (surface) mounting
be enabled/disabled, not-normally/ Wire connection Terminal Blocks
normally energized (fail-safe), or screw type for lead wire
latched Wire size Min. 24 AWG (0.25 mm2)
- time delay switching Selectable for make and brake of Max. 12 AWG (4.0 mm2)
each relay, 0-990 seconds Weight 1.5 lbs. (0.7 kg)
Audible Alarm Built-in buzzer, 80db @ 4 inches Approvals / Listings
(100 mm), 2700 Hz, assignable CSA, NRTL C/US, C22-205
to any relay/stage level “Pending”
- buzzer setting Selectable for double-tap Warranty 24 months material and
intermittent, intermittent 50% duty workmanship
cycle, or continuous sound
Alarm acknowledgement Menu-driven and reset function
for latched relays
User Interface
Keypad type Refer to “illustration magnetic-
touch, menu-driven, keypad user
interface”
- magnetic-touch
tool accessing (4) keys w/magnetic-touch sensors
Status indicators (3) Red LED’s for status
of relays 1 to 3
(2) Green LED’s for RS-485
communications status
Digital display Liquid Crystal Display (LCD)
two lines, 2 x 8 characters with
backlight
- scroll rate Adjustable, 1-9 seconds
- display Transmitter address, gas type,
concentration and alarm status
Programming Through menu on display and
manual operation of the
magnetic-touch keypad user
interface
Addressing digital mode Network address number assignment
via magnetic-touch key entry
Addresses available Four (#0 to #3) for IQ4 controllers
Thrirty-two (#0 to #31) for
IM controllers
Environmental
Permissable ambient
- working temperature -49°F to 149°F (-45°C to 65°C)
- storage temperature -49°F to 158°F (-45°C to 70°C)
- humidity, continuous 5 to 95% RH, non-condensing
Physical
Enclosure
- material Polycarbonate, fire-retardant,
UL94-5V
- color Cool gray, front cool gray/black
- cover Snap-on, secured by (4) screws

Customer Services (858) 578-7887 & (888) GO INTEC Fax (858) 578-4633 & (888) FX INTEC Specification subject to change without notice.
INTEC Controls, 12700 Stowe Dr. Suite 110, Poway, CA 92064 www.inteccontrols.com Page 2 of 5 Printed in USA 0901026
IIR-FD-R

ORDERING INFORMATION
IIR-FD-R xxx

Sample ordering part number:


Refrigerant IIR-FD-R134A
Infrared refrigerant leak transmitter, 0-1000 ppm R134a range,
R11, R22, R113, R114, R123, R134A 4-20 mA/2-10 VDC output signal and RS-485 serial comm-
R401B, R404A, R407C, R410A, R507 unication, (3) SPDT relay outputs, menu-driven keypad user
Others upon request
interface, LCD & LED, audible alarm, power supply 24 VAC or
24 VDC, NEMA 4X enclosure.

FIELD WIRING CONFIGURATION

IIR-FD-R
TB1 J5 Jumper Selector, Analog Output Signal

3 J5
+ – A+ B– + – 4-20 mA selection
2
(factory set) 1
1 2 3 4 5 6
3 J5
(–) Return/Com 4-20 mA, or 2-10 VDC selection 2
2-10 VDC 1
> (+) Signal

RS-485 Digital communication link:


(B)
Cable, twisted, balanced shielded
(A) pair; with characteristic impedance of
Analog Signal Test Point oSIG–
120 , e.g. Belden 9841
at time of field operation oSIG+
(–) Com Power supply
24 VAC, floating**,
(+) or 24 VDC*

** Do not connect 24 VAC to earth ground


* Do not use VDC power supply from the
IM controller; use separate VDC power

Relay #1 Relay #2 Relay #3


SPDT SPDT SPDT
COM

COM

COM

NC NO NC NO NC NO

3 2 1 3 2 1 3 2 1
TB2 TB3 TB4
NC C NO NC C NO NC C NO
Max. resistive load:
0.3 A @ 125 VAC,
1.0 A @ 30 VDC

Customer Services (858) 578-7887 & (888) GO INTEC Fax (858) 578-4633 & (888) FX INTEC Specification subject to change without notice.
INTEC Controls, 12700 Stowe Dr. Suite 110, Poway, CA 92064 www.inteccontrols.com Page 3 of 5 Printed in USA 0901026
IIR-FD-R

FIELD WIRING CONFIGURATION (cont...)

Suggested daisy-chain powering

TB1 1 2 *** TB1 1 2 ***

)+( (+)
24 VAC, floating**,
)–( (–) or 24 VDC*

Suggested daisy-chain (multi-drop) communication J3 Jumper Selector, RS-485


between transmitters and controller End-of-Line Terminator
Only the last
transmitter, away
TB1 *** TB1 Open/disabled
3 4 3 4 *** J3 from the IQ4 or IM
(factory set) controller, of the
1 2 3
communication
(A) (A)
trunk should
RS-485 J3 Closed/enabled
(B) (B) enable the End-of-
1 2 3 Line Terminator

*** Maximum of (4) transmitters can be linked


to an IQ4 controller, and (32) transmitters
can be linked to an IM Controller

Note:  Do not connect power to A and B; this will damage


F1 Fuse
all transmitters linked on the same daisy-chain trunk.
 Daisy-chain between transmitters and controller 1.6A, PolySwitch
A to A, B to B. Do not cross A to B; this creates a
malfunction of communication.
 Daisy-chain trunk length between transmitter and
controller
- RS-485 communication up to 3,000 ft. (914 m) max. F2 Fuse
- Powering from controller, w/(4) refrigeration
transmitters, up to max. 200 ft. (60 m)/18 AWG wire, 50 mA, PolySwitch
or up to max. 300 ft. (91 m)/16 AWG wire.
 Do not use high voltage lines in the same RS-485
communication cable conduit.
Note:
“Polyswitches reset after fault is cleared
RS-485 Communication selection, Addressing, and and circuit power switched off.”
Calibration
Manually operated using the keypad user interface; refer to
user manual.

RS-485 communication output protocol selection


via submenu “1_System Setting”
- OptoMux for IQ4C or IM controllers
or
- MODBUS for applicable controllers

Sensor/transmitter addressing via submenu “1_System Setting”


- IQ4 Controller : Addresses 0 to 3
- IM Controller : Addresses 0 to 31
- MODBUS Controller: Addresses 0 to 255

Sensor calibration via submenu “2_Zero Cal” and “3_Span Cal,”


two-point zeroing/span settings, applying calibration gas standards.

Customer Services (858) 578-7887 & (888) GO INTEC Fax (858) 578-4633 & (888) FX INTEC Specification subject to change without notice.
INTEC Controls, 12700 Stowe Dr. Suite 110, Poway, CA 92064 www.inteccontrols.com Page 4 of 5 Printed in USA 0901026
IIR-FD-R

USER INTERFACE
Keypad User Interface Sub Menu “1_System Setting”
Digital Communication Enter and/or change system parameters
Display Green LED’s* - Address (003)
- Baudrate (4800 bps)
- Scroll (3 sec)
- Backlite (ON)
Relay - 4mA Cal (144)
Status - 20mA Cal (905)
Red LED’s
- Change Password
- Protocol (OptoMux or MODBUS)
- Gas Type
- Auto Zero
Magnetic-touch Keypad - Restore at Default
- Spec Gas
* RS-485 communication traffic status LED’s between Sub Menu “2_Zero Cal”
transmitter and remote controller Transmitter provides Local Zeroing
Sub Menu “3_Span Cal”
Transmitter provides Local Spanning
Keypad Menu Tree Sub Menu “4_Output Testing”
Force relay, buzzer and strobe actions
- Relay Test
- Buzzer Test
System Status 1. System Settings
- A-Out Test
Keypad

Sub Menu “5_Site Service”


2. Zero Cal (Factory Service Staff use only)
Password Sub Menu “6_Relay Database”
3. Span Cal - Assign (de-energized or energized) normal operation
- Assign with latching or non-latching
4. Output Testing - Assign ON/OFF Levels
- Assign DELAY ON/OFF Time (in seconds)
5. Site Service - Assign Fault
- Assign Window
6. Relay Database Sub Menu “7_A-Out Database”
- Assign Concentration at 4 mA
7. A-Out Database
- Assign Concentration at 20 mA
Sub Menu “8_Buzzer Database”
8. Buzzer Database
- Assign (de-energized or energized) normal operation
- Assign with latching or non-latching
9. Output Disable
- Assign ON/OFF Levels
10. SIMU Disable
- Assign DELAY ON/OFF Time (in seconds)
- Assign Fault
- Assign Window
Sub Menu “9_Output Disable”
All outputs can be disabled/enabled for test and calibration.
Sub Menu “10_SIMU Disable”
System Operation Simulation mode for test and calibration.
Programming can be made via the keypad user interface in
combination with the display screen. Security is provided via a
four-digit password.
Main Page Display
Displays current sensor reading and output.
Main Menu
Displays headings of “1_System Setting,” “2_Zero Cal,”
“3_Span Cal,” “4_Output Testing,” “5_Site Service,”
“6_Relay Database,” “7_A-Out Database,” “8_Buzzer Database,”
“9_Output Disable,” and “10_ SIMU Disable.”

Customer Services (858) 578-7887 & (888) GO INTEC Fax (858) 578-4633 & (888) FX INTEC Specification subject to change without notice.
INTEC Controls, 12700 Stowe Dr. Suite 110, Poway, CA 92064 www.inteccontrols.com Page 5 of 5 Printed in USA 0901026

You might also like