Power Management System
Power Management System
Second Year
2. Thar Ta Aung
Contents
Pages
Introduction 1
PMS Operation 2
Preferential Trip 6
References Lists 19
1
Introduction
A vessel may have a number of generating sets, a split bus bar and a variable
load. Since the advent of UMS classification, automatic control has become common
load equipment.
The main switchboard is fitted with a power management system. This system
has various functions to ensure the continuous supply of the ship’s electrical systems.
The system also automatically controls the diesel generators for efficient operation.
Thus a modem PMS must not only ensure safety but also control fuel consumption
and emissions.
Automatic synchronizing and load sharing is provided for the ship’s generator
sets. According to the IMO requirement, a ship must have at least two generators. It is
2
not necessary to have only a diesel-driven generator as the main source of power;
there may be other types of prime movers too. The power management system
automatically equalises the incoming generator’s frequency with the busbar frequency
and energises the generator’s air circuit breaker to connect the two circuits at the
moment when the parameters like voltage, frequency and phase sequence coincide.
Automatic load sharing then ensures that each generator is equally loaded.
PMS Operation
the electrical system. Its task is to make sure that the electrical system is safe and
efficient. If the power consumption is larger than the power production capacity, load
management system are starting and stopping of diesel generators depending on the
according to calculations of the electric power tables of each vessel. PMS System
decides which Generators combination will be the best according to the Load
Consumptions. The capacity of the Generators is such that in the event of any one
generating set will be stopped then it will still be possible to supply all services
Furthermore, it will be sufficient to start the largest motor of the ship without causing
any other motor to stop or having any adverse effect on other equipment in operation.
Ship:
3
1. Automatic Synchronizing
selection of generators
Above mentioned functions are not the same in all ships, the functions varies
according to the types of Power management system which are designed by the
manufactures.
The total load is monitored and compared with the available on-line
generating capacity.
blocking of large motors until the number of running generators is sufficient to supply
the starting current for motors and the ship’s power demand, is ensured. In response to
varying load, the system will start a standby generator and initiate the synchronising
sequence to bring it on-line, or off-load a generator, disconnect it from the bus and
The load demand is shared between generating sets which are on-line. This
can be done on a proportional basis according to the rated power and droop
The frequency of the bus is monitored and kept within a specified limit by
Some systems operate a load inhibit circuit that prevents a sudden increase in
load when the generating capacity is not available. Load shedding, to trip selected
Each of the earlier mentioned PMS functions will be defined within the system
software. The necessary inputs are provided as on/off status inputs from circuit
breakers and generator status signals, analog inputs of generator power and current,
power of each load and voltage and frequency of each bus section.
Outputs are given to raise / lower generator governor settings, close circuit
selection of duty and standby generating sets, and the ability to set levels at which
generating sets are introduced or shut down. The operator will be provided with
information such as power generated, power demands, running and standby capacity.
An interface to the ship’s main alarm system is likely, giving system alarms
For example, if the power input from the generator fails, generator power can
be calculated using the current input and an assumed or actual power factor.
Overloads can also be calculated and hence the load reduced by a minimum
Preferential Trip
6
designed to disconnect the non-essential circuit i.e. non-essential load from the main
The non-essential circuits or loads on ships are air conditioning, exhaust and
ventilation fans, and galley equipment which can be disconnected momentarily and
The main advantage of the preferential trip is that it helps in preventing the
operation of main circuit breaker trip and loss of power on essential services and thus
Along with this, there is also an alarm system provided, which functions as
soon as an overload is detected and trips start operating. There are some mechanical
linkages also in the circuit which instantaneously operates the circuit and completes
The dashpot arrangement consists of a small piston with a small orifice and
which is placed inside a small cylinder assembly. This piston moves up against the
fluid silicon and the time delay is governed by the orifice in the piston.
The current passes through the electromagnetic coil and the linkages are kept
from contacting using a spring arrangement. As soon as the current value increases
the limit, the electromagnetic coil pulls the linkage up against the spring force and
7
operates the instantaneous circuit and the alarm system. The lower linkage completes
The current passes through the coil in the preferential trip circuit which pulls
the piston in the dashpot arrangement. The movement of this piston is governed by
the diameter of the orifice and the time delay made by the same.
When generator load reach 110%, preferential trip into operation as follow.
First trip at 5 sec - shut down non essential load (air condition,
Third trip at 15 sec - shut down main generator as last action, if load still high,
When two or more power units are running in parallel and if reverse power
flow occurs, the same unit will start drawing power from the main bus bar. it can
cause overloading of the other power supply unit and hence leads for the preferential
trip or may lead to total power failure(Blackout). At the same time the faulty unit will
draw power from main bus bar and go for motoring effect and RPM will soot up
which leads to over speed trip or in worst case some mechanical failure to the prime
mover. To prevent this, reverse power relay is used where generator runs in parallel
and associate machineries such as boiler, purifier and other auxiliaries stop operating
due to failure of power generation system of the ship – Generator and alternator. With
technologies and automation, measures are provided to avoid such blackout situations
by means of autoloading sharing system and auto standby system in which the
generator set that is running in parallel or standby comes on load automatically if the
running diesel generator fails. According to the PMS system, when main generators
condition.
If emergency generator did not start up within 45 minutes, the operator have to
The circuits compare the kW loading of each generator (via current and
connections.
10
fails.
ships. Nowadays, ship engineers are specifically advised to inculcate best power
consumption. Most modern day ships today are built with provisions for
vitality. Not only does the PMS does away with manual synchronisation of
load.
Diesel generators are the primary components of the PMS. All generators have
a maker’s specific minimum, maximum load criteria, and optimum load criteria.
When the generators are synced with the ship’s PMS, engineers have the
option of changing the minimum and maximum point beyond which, the generator
the generator.
The loading and unloading of power from the alternator of the generator is
driven by time lag functions, which often means, that a sudden spike in the load
Some ships are also fitted with a shaft motor, which not only compensates for
a sudden drop in load, but also, minimises shaft torque on engines with a long
When generator sets are run in parallel, including, shaft generators, diesel
generators and/or steam driven turbine generator, the PMS almost completely
regulates the load on each component. Generally, in case of generators with equal
load capacity, the load on the bus bar is distributed symmetrically on the alternators.
number of generators, each at a load that is optimum. For instance, one generator
running at 30% load may be more fuel efficient than 2 running at 15% and,
conversely, one generator running at 70% may consume more fuel than 2 running at
12
At the start of each voyage, marine engineers must discuss the power
management plan and consider various factors like, number of reefers onboard, use of
stabilisers during the voyage, maintenance to be carried out on any generator during
the voyage to determine which and how many generators to run. An unexpected
breakdown in the generators may require cutting down on the power consumption.
Let’s take a look at a few factors which would help in smart reduction of consumption
of power.
consume a higher power with the increase in the number of live reefers
system is a much more economic way than using heavy inlet and exhaust fans
for cargo hold ventilation. Thus, it is imperative the fresh water cooling
system for reefers, which includes fresh water and sea water pumps,
working condition.
aim of using ballast pumps only when required. Filling of tanks, where
practical, must be carried out by gravity. Similarly, use of ejectors only while
final stripping of tanks and not continuously while deballasting, reduces usage
3. Fuel Transfer pumps- Usage of service steam effectively to heat the fuel in
mention, prolonged running of the pumps to transfer the same amount of fuel.
consumption.
temperature must be
carefully evaluated so as
to run only the required number of fans. Where fan motors are dual speed or of
off lights which are not in use. Cargo hold lights, steering
power consumption.
15
out on board ships, close coordination among deck and engine departments is
Power management systems (PMS) have in the past been relay-based, but a
is now more commonly used. This can also be integrated into a distributed control
These sub-systems connect the PLC to actual Sensors and Transducers. PLCs
directly read limits, Temperature sensors, and position of complex position systems.
On the out put or Actuator side , PLC can operate pneumatic Diaphragm valves
through I/P Converters, operate Relays to drive electric motor starters , run timers,
counters and solenoids. Computers are optimized for calculation and display tasks,
PLCs are optimised for control tasks and the industrial environment
16
PLC consists of
Memory
Power Supply
Programming device
17
There are five types of PLC Programming languages all are part of IEC
Languages are:
Power management systems help ensure the safe, reliable, efficient, and
connected to it. They can help you: Avoid electrical fires and prevent shock. Recover
Tanker
Bulk carrier
Container Ship
Cruise Ship
Yachts
19
References Lists
www.marineinsight.com
www.electrotechnical-officer.com
https://en.m.wikipedia.org
https://www.linkedin.com
https://www.nautilusshipping.com
www.marine-engineering.com