Power Systems
Course Code: EE 308
(2-1-0-3)
Tutorial – 1
Average Load
Load Factor =
Maximum Peak Load
where,
• Tariff structures should be such that it will influence to improve the load factor
• Tariff structure should consider power factor of the load of the customer
Problem-1
A generating station has a maximum demand of 25 MW, a load factor of 60%, a plant capacity factor
of 50%, and a plant use factor of 72%. Find
Ans:
capacity of the hydro plant = 330 MW
the energy generated annually by hydro = 1935 X 106 kWh, the energy generated
annually by thermal = 255 X 106 kWh
overall generation cost = 15.53 p/ kWh
Problem-3: Solution
Problem - 4
Draw the reactance diagram choosing generator 3 circuit as the base circuit
Ans: Xg1 = 0.225 pu; Xg2 = 0.1312 pu; Xg3 = 0.20 pu; Xt1 = 0.121 pu;
Xt2 = 0.1266 pu; Xt3 = 0.121 pu; XTL1 = 0.5625 pu; XTL2 = 0.5625 pu; XTL3 = 0.375 pu;
Problem-4: Solution
Problem-4: Solution
Problem - 5
The single line diagram of a three phase power system is shown in fig. Select a common
base of 100MVA and 13.8KV on the generator side. Draw per unit impedance diagram.
G: 90MVA, 13.8KV, X=18%; T1: 50MVA, 13.8/220KV, X=10%; T2: 50MVA, 220/11KV, X=10%; T3: 50MVA,
13.8/132KV, X=10%; T4: 50MVA, 132/11KV, X=10%; M: 80MVA, 10.45KV, X=20%; LOAD: 57MVA, 0.8 p.f
lagging at 10.45 KV; Line 1 = j 50Ω; Line 2 = j 70Ω
Ans: Xg1 = 0.2 pu; Xt1 = 0.2 pu; Xt2 = 0.2 pu; Xt3 = 0.2 pu; Xt4 = 0.2 p; XTL1 = 0.103 pu; XTL2 = 0.4017 pu; Xm = 0.225
pu; Zload = 1.266+j0.95 pu
Problem-5: Hints