Seismic Rehabilitation of Existing Buildings
Seismic Rehabilitation of Existing Buildings
Seismic Rehabilitation of Existing Buildings
Seisntic Rehabilitation .
of Existing Buildings
This document uses both the International System of Units (SI)
and customary units.
TH420.S43 2007
693.8'52-dc22
2007009080
15 14 13 12 11 10
STANDARDS
In 2003, the Board of Direction approved the revision to ASCE 21-98 Automated People Mover Standards-Part 2
the ASCE Rules for Standards Commitlees to govern the ASCE 21-00 Automated People Mover Standards-Part 3
writing and maintenance of standards developed by the SEIIASCE 23-97 Specitication for Structural Steel
Society. All such standards are developed by a consensus Beams with Web Openíngs
standards process managed by the Society's Codes and ASCE/SEI 24-05 Flood Resistan! Desígn and Conslruction
Standards Committee (CSC). The consensus process ASCE/SEI 25-06 Earthquake-Actuated Automatic Gas
includes balloting by a balanced standards commillee Shutoff Devíces
made up of Society members and nonmembers, balloting ASCE 26-97 Standard Practice for Desígn of Buried
by the membership of the Society as a whole, and ballot- Precast Concrete Box Sectíons
ing by the public. AJI standards are updated or reaffirmed ASCE 27-00 Standard Practice for Direct Design of
by the same process at intervals not exceeding five years. Precast Concrete Pipe for Jacking in Trenchless
The following standards have been issued: Constructíon
ASCE 28-00 Standard Practíce for Dírect Design of
ANSIJASCE 1-82 N-725 Guideline for Design and Precast Concrete Box Sections for Jackíng in
Analysis of Nuclear Safety Related Emth Structures Trenchless Construction
ASCEIEWRI 2-06 Measurement of Oxygen Transfer in ASCE/SEJ/SFPE 29-05 Standard Calculation Methods
Clean Water for Structural Fíre Protectíon
ANSIJASCE 3-91 Standard for the Structural Design of SEIIASCE 30-00 Guídeline for Conditíon Assessment of
Composite Slabs and ANSIJASCE 9-91 Standard the Building Envelope
Practice for the Construction and Inspection of SEI/ASCE 31-03 Seísmic Evaluatíon of Existíng
Composite Slabs Buildings
ASCE 4-98 Seismic Analysis of Safety-Related Nuclear SEI/ASCE 32-01 Design and Construction ofFrost-
Structures Protected Shallow Foundations
Building Code Requirements for Masonry Structures EWRII ASCE 33-01 Comprehensive Transboundary
(ACI 530-02/ASCE 5-02/TMS 402-02) and lnternational Water Quality Management Agreement
Specifications for Masonry Structures (ACI 530.1- EWRI/ASCE 34-01 Standard Guidelines for Artificial
02/ ASCE 6-02/TMS 602-02) Recharge of Ground Water
ASCE/SEI 7-05 Mínimum Design Loads for Buildings EWRI/ASCE 35-01 Guidelines for Quality Assurance of
and Other Structures Installed Fine-Pore Aeration Equipment
SEIJASCE 8-02 Standard Specification for the Design of CI/ASCE 36-01 Standard Construction Guidelines for
Cold-Formed Stainless Steel Structural Members Microtunneling
ANSI/ ASCE 9-91 listed with ASCE 3-91 SEJ/ASCE 37-02 Design Loads on Structures During
ASCE 10-97 Design of Latticed Steel Transmission Construction
Structures CI/ASCE 38-02 Standard Guideline for the Collection
SEIIASCE 11-99 Guideline for Structural Condition and Depictíon of Existing Subsurface Utílity Data
Assessment of Existing Buildings EWRI/ASCE 39-03 Standard Practice for the Design and
ASCE/EWRI 12-05 Guideline for the Design of Urban Operation of Haíl Suppression Projects
Subsurface Drainage ASCE/EWRI40-03 Regulated Riparian Model Water
ASCEIEWRI 13-05 Standard Guidelines for Installation Code
of Urban Subsurface Drainage ASCE/SEI 41-06 Seismic Rehabilitation of Existing
ASCE/EWRI 14-05 Standard Guidelines for Operation Buildíngs
and Maintenance of Urban Subsurface Drainage ASCE/EWRI 42-04 Standard Practice for the Design and
ASCE 15-98 Standard Practice for Direct Design of Operation of Precipitation Enhancement Projects
Buried Precast Concrete Pipe Using Standard ASCE/SEI 43-05 Seismic Design Criteria for Structures,
Installations (SIDO) Systems, and Components in Nuclear Facilities
ASCE 16-95 Standard for Load Resistance Factor Design ASCE/EWRI 44-05 Standard Practice for the Desígn and
(LRFD) of Engineered Wood Construction Operation of Supercooled Fog Dispersa! Projects
ASCE 17-96 Air-Supported Structures ASCE/EWRI 45-05 Standard Guidelines for the Design
ASCE 18-96 Standard Guidelines for In-Process Oxygen of Urban Stormwater Systems
Transfer Testing ASCE/EWRI 46-05 Standard Guidelines for the
ASCE 19-96 Structural Applications of Steel Cables for Installation of Urban Stormwater Systems
Buildings ASCE/EWRI 47-05 Standard Guidelínes for the Opera-
ASCE 20-96 Standard Guidelines for the Design and tion and Maintenance of Urban Stormwater Systems
Installation of Pi le Foundations ASCE/SEI 48-05 Design of Steel Transmission Pole
AN S 11ASCE/T&DI 2 1-05 Automated People Mover Structures
Standards-Part 1 iií
FOREWORD
In 2003, the Board of Direction approved the The material presented in this Standard has been
revi ion to the ASCE Rules for Standards Committees prepared in accordance with recognized engineering
Lo govern the writing and maintenance of standards principies. This Standard should not be used without
de\ eloped by the Society. All su eh standards are tirst securing competen! advice with respect to its suit-
de\eloped by a consensus standards process managed ability for any given application. The publication of
b) Lhe Society's Codes and Standards Committee the material contained herein is not intended as a rep-
C C). The consensus process includes balloting resentation or warranty on rhe part of the American
b) a balanced standards committee made up of Sociery of Civil Engineers, or of any other person
iety members and nonmembers, balloting by the named herein, that thi s information is suitable for
membership of the Society as a whole, and ballot- any general or particular use or promises freedom
mg by the public. All standards are updated or from infi'ingement of any patent or patents. Anyone
reaffirmed by the same process at intervals not making use of this information assumes all liability
e:.>. ·eedi ng tive years. from such use.
V
ACKNOWLEDGMENTS
The Structural Engineering lnstitute (SEl) of Guide/ines jor the Seismic Rehabilitation of Buildings,
the American Society of Civil Engineers (ASCE) developed for FEMA by the Applied Technology
acknowledges the devoted etforts of the membership Council (ATC). ASCE acknowledges and is grateful
ofthe Seismic Rehabilitation of Existing Buildings for the over ten years of support provided by FEMA
Standards Committee of the Codes and Activities to the development of a new generation rehabilitation
Division of SE!. This group comprises individuals standard, and particularly for their support during
from many backgrounds, including consulting engi- this final step, the development of this consensus
neering, research, construction industry, education, standard.
government, design, and prívate practice. This standard was prepared through the consensus
Balloting for this standard began with FEMA 356, standards process in compliance with the procedures
Prestandard and Commentary for the Seismic established by the ASCE Codes and Standards
Rehabi/itation ojBuildings, prepared by ASCE for Committee and accredited by the American National
the Federal Emergency Management Agency (FEMA). Standards lnstitute (ANSI). Those individuals who
FEMA 356 was developed from FEMA 273, NEHRP served on the standards committee are:
vii
Richard Lee Silva, P.E., M.ASCE Frederick Michael Turner, S.E., M.ASCE
Thomas David Skaggs, P.E., M.ASCE Michael T. Valley, P.E., M.ASCE
Glenn R. Smith, Jr., Ph.D., P.E., M.ASCE lvan P. Vamos
Peter W. Somers Gary S. Varum, S.E.
Charles A. Spitz Thomas George Williamson, P.E. , F.ASCE
Eric Christian Stovner, P.E., M.ASCE Lyle L. Wilson, F.ASCE
Donald R. Strand, P.E., F.ASCE Lisa A . Wipplinger, P.E., M.ASCE
Peter Tian, P.E., A.M.ASCE Tom Chuan Xia, P.E. , M.ASCE
Eugene Trahern, P.E. Wade Wesley Younie, P.E., M.ASCE
CONTENTS
Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
Foreword . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . v
Acknowledgtnents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . v1
IX
2.6 GENERAL DESIGN REQUIREMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
2.6.1 Multidircctional Seismic EITects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
2.6.2 P-6. Effects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
2.6.3 Horizontal Torsion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
2.6.4 Overturning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
2.6.5 Continuity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
2.6.6 Diaphragn1s . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
2.6.7 Walls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
2.6.8 Nonsu·uctural Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
2.6.9 Structures Sharing Common Elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
2.6.10 Building Separation ........................................... 47
2.6.11 Vertical Seismic EtTects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
2.7 CONSTRUCTION QUAUTY ASSURANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
2.7.1 Construction Quality Assurance Plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
2.7.2 Construction Quality Assurance Requirements . . . . . . . . . . . . . . . . . . . . . . 49
2.7.3 Responsibilities of the Authority Having Jurisdiction . . . . . . . . . . . . . . . . . 49
2.8 ALTERNATIVE MODELING PARAMETERS AND
ACCEPTANCE CRITERIA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
2.8.1 Experimental Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
2.8.2 Data Reduction and Reporting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
2.8.3 Design Parameters and Acceptance Criteria . . . . . . . . . . . . . . . . . . . . . . . . 51
3.0 ANALYSIS PROCEDURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
3.1 SCOPE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
3.2 GENERAL ANALYSIS REQUIREMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
3.2.1 Analysis Procedure Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
3.2.2 Mathematical Modeling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
3.2.3 Contiguration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
3.2.4 Diaphragms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
3.2.5 P-6. Effects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
3.2.6 Soii-Structure Interaction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
3.2.7 Multidirectiona\ Seismic Effects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
3.2.8 Component Gravity Loads for Load Combinations . . . . . . . . . . . . . . . . . . . 59
3.2.9 Veritication or Design Assumptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
3.2.1 O Overturning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
3.3 ANALYSIS PROCEDURES .......................................... 61
3.3.1 Linear Static Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
3.3.2 Linear Dynamic Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
3.3.3 Nonlinear Static Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
3.3.4 Nonlinear Dynamic Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
X
4.3 MITIGATION OF SEISMIC-GEOLOGIC SITE HAZARDS . . . . . . . . . . . . . . . . . 81
4.4 FOUNOATION STRENGTH ANO STIFFNESS . . . . . . . . . . . . . . . . . . . . . . . . . . 83
4.4. 1 Expected Capacities of Foundations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
4.4.2 Load- Oeformation Characteristics for Foundations . . . . . . . . . . . . . . . . . . 86
4.4.3 Foundation Acceptance Criteria . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
4.5 KINEMATIC INTERACTION ANO FOUNOATION OAMPING SOIL-
STRUCTURE INTERACTION EFFECTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
4.5.1 Kinematic Interaction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
4.5.2 Foundation Oamping Soii-Structure Interaction Effects . . . . . . . . . . . . . . . 98
4.6 SEISMIC EARTH PRESSURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
4.7 FOUNOATION REHABILITATION .................................... lOO
5.0 STEEL ...... . ............. .. ... ...................... .. ...... ..... .... . 101
5.1 SCOPE ............. .. ... ...... ....... .. . ... . ........... ... .. ..... 101
5.2 MATERIAL PROPERTIES ANO CONDITION ASSESSMENT .. ... ...... .. 101
5.2.1 General ....... . ... . ... ............. . . . ... . .. ....... .. ...... . 101
5.2.2 Properties of In-Place Materials and Components ...... ... ...... ..... 102
5.2.3 Condition Assessment .... .. .. ....... .. ....... . .......... .. ..... 105
5.3 GENERAL ASSUMPTIONS ANO REQUIREMENTS .. ... . .. .... ........ . 108
5.3.1 Stiifness ... .... . . ...... ... ... .. . ... ....... .. .. . .. ...... ..... 108
5.3.2 Oesign Strengths and Acceptance Criteria .......................... 108
5.3.3 Rehabilitation Measures .. .......... .. ....... ... .... . .. ...... . . . 109
5.4 STEEL MOMENT FRAMES .. ........... . . ..... ... .............. . ... . 109
5.4.1 General . ... ....... .. .. .. . ... .................. .... ... . .. ... . 109
5.4.2 Fully Restrained Moment Frames ................................ 114
5.4.3 Partially Restrained Moment Frames .. ... ..... . ... . .. . .. .... . . ... . 126
5.5 STEEL BRACEO FRAMES . .... . . . .... .... .. .. ... .. .... .... .. .. . ... . 131
5.5.1 General .... ..... .. .. .. . . . .... .... ... ...... . . ...... ... ....... 131
5.5.2 Concentric Braced Frames .......... ... ...... .. .. . ....... .. ..... 131
5.5.3 Eccentric Braced Frames ......... .. ..... ...... ... ...... .... .... 133
5.6 STEEL PLATE SHEAR WALLS . .......... . ...... ..... ..... . .. ... . . . . . 135
5.6. 1 General ... . . . .... ... .... .. .. . . .. ... ...... ..... .... .......... 135
5.6.2 Stiffness .................................................... 135
5.6.3 Strength . . . . ........ . ........ . . .. .... ...... .. ...... .... . ... .. 135
5.6.4 Acceptance Criteria ........................................... 136
5.6.5 Rehabilitation Measures ........................................ 136
5.7 STEEL FRAMES WITH INFILLS .... . .. . ... .... .... ..... .. ....... ... . 136
5.8 DIAPHRAGMS .................................................... 137
5.8.1 Bare Metal Oeck Oiaphragms ................................... 137
5.8.2 Metal Oeck Oiaphragms with Structura1 Concrete Topping . .... ....... 138
5.8.3 Metal Oeck Oiaphragms with Nonstructural Topping ................. 140
5.8.4 Horizontal Steel Bracing (Steel Truss Oiaphragms) .. .. .. ... .... ..... 141
5.8.5 Archaic Oiaphragms ........................................... 142
5.8.6 Chord and Collector Elements ... ........ . . .. . .. . ... ...... .. . .... 143
5.9 STEEL PILE FOUNOATIONS ........................................ 144
5.9.1 General . ... ...... .... ........ . ............... . ... ... .... ... . 144
5.9.2 Stiffness . ... ..... ...... ... . ......... . .. .. ... ...... ... .. .. .. . 144
xi
5.9.3 Strength .. . ...... . ........................................... 144
5.9.4 Acceptance Criteria ... .. . .... . . .. ........................... . . 144
5.9.5 Rehabilitation Measures ................... .. . .. ................ 144
5. 1O CAST AND WROUGHT IRON .......... . ............................. 145
5.10. 1 General ......... . ................. . . .. ........... . .......... 145
5.10.2 Stiffness .. ... . ....... ...... .............. .. .. . ... . .......... 145
5.10.3 Strcngth and Acceptance Criteria ................................. 145
6.0 CONCRETE . . .... ........ . . . .. . ............. ... ........................ 145
6.1 SCOPE ........................................................... 145
6.2 MATERIAL PROPERTIES AND CONDITION ASSESSMENT ............. 145
6.2. 1 General . ... ........ .. . .. . .. .. . ......... .... .......... .. . .. .. 145
6.2.2 Properties of In-Place Material s and Components . .... .......... ... .. 146
6.2.3 Condition Assessment . ....... .................................. 151
6.2.4 Knowledge Factor ............................................. 153
6.3 GENERAL ASSUMPTIONS AND REQUIREMENTS ............ . ........ 153
6.3. 1 Modcling and Design . ....... ..... .. ... ... .. ... .. .... ... ..... . . 153
6.3.2 Strength and Deformability ..................................... 155
6.:u Flexure and Axial Loads ....... . ................... .. . .......... 156
6.3.4 Shear and Torsion ...... ....................................... 157
6.3.5 Developme nt and Splices of Reinforcement ........................ 157
6.3.6 Connections to Existing Concrete ................................ 158
6.3.7 Rehabilitation .. . .. .. .... ... .. .. .............................. 159
6.4 CONCRETE MOMENT FRAMES ..................................... 159
6.4. 1 Types of Concrete Moment Frames .. ...... .... .... ...... .. ....... 159
6.4.2 Reinforced Concrete Beam-Column Moment Frames ....... .. ........ 160
6.4.3 Post-Tensioned Concrete Beam-Column Momcnt Framcs ............. 168
6.4.4 Slab-Column Moment Frames ................................... 169
6.5 PRECAST CONCRETE FRAMES ... .. .. .... ............. .. . ... ....... 173
6.5. 1 Types of Precast Concrete Frames ................................ 173
6.5.2 Precast Concrete Frames Expected to Resist Lateral Load . ... .... .. ... 173
6.5.3 Precast Concrete Frames Not Expected to Resist Lateral
Loads Directly ..... .. ..... . ... .. .... .. ..... .. .. . .......... . . . 174
6.6 CONCRETE FRAMES WITH INFILLS ................................. 175
6.6. 1 Types of Concrete Frames with Intill s . ... .. .. . .. .... .. .. .......... 175
6.6.2 Concrete Frames with Masonry Infill s ........... .... .... ... ....... 175
6.6.3 Concrete Frames with Concrete Inlills ............................. 178
6.7 CONCRETE SHEAR WALLS ..... . . . .... .... ...... . ....... .. ......... 180
6.7. 1 Types of Concrete Shear Wall s and Assoc iated Components ... ...... .. 180
6.7.2 Reinforced Concrete Shear Walls, Wall Segments, Coupling Beams, and
Reinforced Concrete Columns Supporting Discontinuous Shear Walls ... 183
6.8 PRECAST CONCRETE SHEAR WALLS . .... . ......................... 189
6.8.1 Types of Precast Shear Walls ... ..... . . ..... . ............... . . ... 189
6.8.2 Precast Concrete Shear Walls and Wall Segments ... ........ .. .. ..... 190
6.9 CONCRETE-BRACED FRAMES . .. . ... .. ..... . . ........ ....... . .. ... . 193
6.9.1 Types of Concrete-Braced Frames ................................ 193
6.9.2 General Considerations .... . .. ... ............................... 193
xii
6.9.3 Stiffness .................................................... 193
6.9.4 Strength ........................... .......... .. ... .. .. ....... 194
6.9.5 Acceptance Criteria ............. ... ... ...... ........ ... ... .. . . 194
6.9.6 Rehat.ilitation Measures ... . . . .. . ........... . . . .............. ... 194
6.10 CAST-IN-PLACE CONCRETE OIAPHRAGMS .......................... 194
6.1 0 . 1 Components of Concrete Diaphragms ............................ 194
6.1 0.2 Analysis, Modeling, and Acceptance Criteria ...................... 195
6.1 0.3 Rehabilitation Meas ures ................... .. ............. . .... 195
6.11 PRECAST CONCRETE DIAPHRAGMS ............... . ................ 196
6.11.1 Components of Precast Concrete Oiaphragms . .. ................... 196
6.11.2 Analysis, Modeling, and Acceptance Criteria ...................... 196
6.11.3 Rehabilitation Measures ....................................... 196
6.12 CONCRETE FOUNDATION COMPONENTS .. ...... ...... .... ... .... .. 197
6.12.1 Types ol· Concrete Foundations .................. . .............. 197
6.12.2 Analysis of Existing Foundations ................................ 197
6.12.3 Evaluation of Existing Condition ................................ 198
6.12.4 Rehabilitation Measures ......................... . .. .. ......... 198
7.0 MASONRY .................. ... .............. .... ..... . ....... .. ...... . 199
7.1 SCOPE ..... . ............... . ................ ....... .............. 199
7.2 MATER[AL PROPERTIES ANO CONDlTION ASSESSMENT ... . .. . ...... 199
7.2. 1 General ..................................................... 199
7 .2.2 Properties of In-Place Matcrials .................................. 200
7.2.3 Condition Assessment ... . ...................... .... . ..... .... . . 204
7.2.4 Knowledge Factor . ...... ... . .................. .. .............. 207
7.3 MASONRY WALLS ............................ . ................... 207
7.3 .1 Types ofMasonry Walls . ......... . ................. . . .......... 208
7.3.2 Unreinforced Masonry Walls and Wall Piers In-Piane ................. 211
7.3 .3 Unreinforced Masonry Walls Out-of-Plane ......................... 213
7.3.4 Rei nforced Masonry Walls and Wall Piers In-Piane ........... .. .. . .. 214
7.3.5 Reinforced Masonry Walls Out-of-Piane ........................... 216
7.4 MASONRY INFJLLS . ............................. . ................. 218
7.4. 1 Types of Masonry Infills ........................................ 218
7.4.2 Masonry lnfills ln-Plane ................. ....... .... .... ....... . 219
7.4.3 Masonry lnlills Out-of-Piane .................................... 222
7.5 ANCHORAGE TO MASONRY WALLS ........................ . ....... 224
7.5.1 Types of Anchors .. .................. ... .. . ...... . . . ...... . .. . 224
7.5.2 Analysis of Anchors ............... . .. ... ...................... 224
7.6 MASONRY FOUNOATION ELEMENTS ... .. .......... . ............. .. 225
7 .6. 1 Types of Masonry Foundations .............. ... ................. 225
7.6.2 Analysis of Existing Foundations ................................. 225
7.6.3 Rehabilitation Measures ........................................ 225
8.0 WOOD ANO LlGHT METAL FRAMING .. . ................................. 225
8.1 SCOPE ........................................................... 225
8.2 MATERIAL PROPERTIES AND CONDITION ASSESSMENT ...... . ....... 226
8.2.1 General ..................................................... 226
xiii
8.2.2 Properties of In-Place Materials and Components ............... 237 o ••• o
8.4.2
Types of Wood Frame Shear Wall s ..... .. . ...... ...... . .... . . .. .. 237
8.4.3
Types of Light Gage Metal Frame Shear Walls ..... . ................ 240
Single-Layer Hori zontal Lumbcr Sheathing or Siding Shear Wall s .... .. 240
8.4.4
8.4.5
Diagonal Lumber Sheathing Shear Wall s ............. . .. . ... .. ... .. 241
8.4.6
Vertical Wood Siding Shear Wall s ..... .................... . ...... 243
8.4.7
Wood Siding over Hori zontal Sheathing Shear Wall s ...... . .... 246 o •••••
8.4.8
Wood Siding over Diagonal Sheathing ................ .. 246 o •• o ••••••
8.4.9
Wood Structural Panel Sheathing ..... ... .. 246 o •••••••••••• o ••• o •••• •
8.4.1 O
Stucco on Studs, Sheathing, or Fiberboard ......... .. . ........ .. . . . 247
8.4.11
Gypsum Plaster on Wood Lath ......................... . . .. ..... . 248
8.4.12
Gypsum Plaster on Gypsum Lath ..... . 248 o •••••••• • ••• • •••••••••••••
8.4.13
Gypsum Wallboard .............. .. . 249 o •••• • •••••••••••••••••• • ••
8.4.14
Gypsum Sheathing . ...... . . ....... . 249 o •••••••••••••••• • ••••• • •• •
8.5 WOOD DIAPHRAGMS . .... ...... .. ...... o ••••••• o ••••••• ••• • • o ••••• 251
8.5.1 General ..................... o •••••••••••• o ••• o ••• o • • •••••••• 25 1
8.5.2 Typcs of Wood Diaphragms .......... ... . ... . . ..... . ............ 251
8.5.3 Single Straight Sheathing ........ . . .... ...... o •••••••••••••••••• 254
8.5.4 Double Straight Sheathing . . o •••••• • o • •••• •• •••••••••••••••••••• 255
8.5.5 Single Diagonal Sheathing ...................................... 255
8.5.6 Diagonal Sheathing with Straight Sheathing or Flooring Abovc ......... 256
8.5.7 Double Diago nal Sheathing . ... . ..... o •• o ••••••••••••••••••••••• 256
8.5.8 Wood Structural Panel Sheathing .... .. ..... .. ... ................. 257
8.5.9 Wood Structural Panel Overlays on Straight or Diagonal Sheathing ..... 258
8.5.10 Wood Structural Panel Overlays on Existing Wood Structural Panel
Sheathing .. ...... . o • ••• • •• •• ••••• • •••••••••••••••••••••••••• 259
8.5.11 Braced Horizontal Diaphragms . . ............ o ••••••• ••••• ••••••• 259
8.6 WOOD FOUNDATlONS .. .. ................... ............ . ......... 259
8.6.1
Types o f Wood Foundations .... . ... .. ........................... 259
8.6.2
Analysis, Strength, and Acceptance Criteria of Wood Foundations ...... 259
8.6.3
Rehabilitation Measures ............. .. .. . ............. .. .. ..... 260
8.7 OTHER WOOD ELEMENTS ANO COMPONENTS .. .. ....... o • •• • • •• ••• 260
8.7.1 General .... ...... .. ...... . ...... ..... . ... o •••••••• •• •••••••• 260
9.0 SEISMIC ISOLATION ANO ENERGY DISSIPATJON .................... . . .... 261
9.1 SCOPE ....... .. ...... .... ... ... .... ........... o •••• ••• o •• •• •••••• 261
xiv
9.2 SEISMIC ISOLATION SYSTEMS ..... . ....... .. .......... ..... ....... 263
9.2. 1 General Requirements . ........................ ...... ... ... .... 263
9.2.2 Mechanical Properties and Modeling of Seismic Isolation Systems ...... 263
9.2.3 General Criteria for Seismic Isolation Design ... . ...... . . ........... 271
9.2.4 Linear Procedures ............................................. 273
9.2.5 Nonlinear Procedures ......... .. .. . ......... . ............ .. .... 274
9.2.6 Nonstructural Components ...................................... 275
9.2.7 Detailed System Requiremenls ................................... 275
9.2.8 Design Review ............................................... 277
9.2.9 Isolation System Testing and Design Properties ..................... 277
9.3 PASSIVE ENERGY DISSIPATION SYSTEMS .. ... .. . ... ................ 279
9.3.1 General Requirements ............ . .................. ... ...... . 279
9.3.2 Implementation of Energy Dissipation Devices ...... ...... .... . ..... 280
9.3.3 Modeling of Energy Dissipation Devices ........................... 281
9.3.4 Linear Procedures ............................................. 282
9.3.5 Nonlinear Procedures .. ... ........................... ...... .... 285
9.3.6 Detailed Systems Requirements . ...... .. ......................... 286
9.3.7 Design Review . . .. .. ....... ... .. ............................. 287
9.3.8 Required Tests of Energy Dissipation Devices ...................... 287
9.4 OTHER RESPONSE CONTROL SYSTEMS ............................. 289
10.0 SIMPLIFIED REHABILITATION ........................................... 290
10.1 SCOPE .................... . .... ...... ..... .. ... ... .. . .......... .. 290
10.2 PROCEDURE ............................... ..... ....... ... .. . ..... 290
10.2.1 Procedure for Reduced Rehabilitation ............................ 290
10.2.2 Procedure for Partial Rehabilitation .............................. 294
10.3 CORRECTION OF DEFICIENCES .................................... 297
11.0 ARCHITECTURAL, MECHANICAL, ANO ELECTRICAL COMPONENTS . .. ..... 313
11.1 SCOPE ........................................................... 313
11.2 PROCEDURE .... ... ...... .... ...... .. . ... .. .. .. .. ... .. ........... . 314
11.2.1 Condition Assessment ...... . ...... .. ........ .. ................ 314
11.2.2 Sample Size .... .. ........................ . ............... .. 315
11.3 HISTORICAL AND COMPONENT EVALUATION CONSIDERATIONS .. . .. 315
11.3.1 Historical Information ........................................ 315
11.3.2 Component Evaluation .................................... ... . 320
11.4 REHABILITATION ... . ............................................. 321
11.5 STRUCTURAL-NONSTRUCTURAL INTERACTION .................... 322
11.5.1 Response Modification .............. . .... . ........ . ........... 322
11.5.2 Base Isolation . ........ ............. ... ...... ...... .. ........ 322
11.6 CLASSIFICATION OF ACCELERATION-SENSITIVE AND DEFORMATION-
SENSITNE COMPONENTS ......................................... 322
11.7 EVALUATJON PROCEDURES .................. . ..................... 323
11.7.1 Analytical Procedure ........................................ . 323
11.7.2 Prescriptive Procedure .......... .... ........ .. ........ . ..... .. 324
11.7.3 Force Analysis: Default Equations .................. .. ........... 324
XV
11.7.4 Force Analysis: General Equations .............................. 324
11.7.5 Deformation Analysis ......................................... 328
11.7.6 Other Procedures . .. . . ... .. ................................. . 329
1 1.8 REHABILITATION APPROACHES ..... ............................... 329
11.9 ARCHITECTURAL COMPONENTS: DEFINITION, BEHAVIOR, ANO
ACCEPTANCE CRITERIA .............. .... ..... ...... ...... ....... . 331
11.9. 1 Exterior Wall Components ..................................... 331
11.9.2 Partitions ................................................... 335
11.9.3 Interior Veneers .............................................. 336
11.9.4 Ceilings ................................................. . . . 337
1 1.9 .5 Parapc~andAppendages ... .... .. .............. .. ............. 338
11.9.6 Canopies and Marquees ..... .. . .. ...... ... .... .... .. ... . . .. ... 339
11.9.7 Chimneys and Stacks ......................................... 339
11.9.8 Stairs and Stair Enclosures ... .................................. 340
11.10 MECHANICAL, ELECTRICAL, ANO PLUMBING COMPONENTS:
OEFINITION, BEHAYIOR, ANO ACCEPTANCE CRITERIA ............... 340
1 1.1 0.1 Mechanical Equipment ...... .. . .. . ......... ................ ... 340
1 1.1 0.2 Storage Vessels and Water Heaters ............................... 342
11.10.3 Pressure Piping ... .............. .... ...................... ... 343
11 . 10.4 Fire Suppression Piping ......... ..... ......................... 343
11.1 0.5 Fluid Piping other than Fire Suppression .......................... 344
11. 10.6 O uel work .......................................... .. ...... 345
11.10.7 Electrical and Communications Equipment ........................ 346
11.10.8 Electrical and Communications Distribution Components ............ 347
11.10.9 Light Fixtures ............................................... 347
11 . 11 FURNISHINGS ANO INTERIOR EQUIPMENT; OEFTNITION, BEHAVIOR,
ANO ACCEPTANCE CRITERIA ...................................... 348
1 1. 1 1.1 Storage Racks ............................................... 348
1 1.1 1.2 Bookcases .................................................. 348
1 1.1 1.3 Computer Access Floors ....................................... 349
1 1. 1 1.4 Hazardous Materials Storage .... ..................... . ......... 349
1 1.11.5 Computer and Communication Racks ............................ 350
1 1. 11.6 Elevators ................................................... 351
11.11 .7 Conveyors .................................................. 351
Appendix
APPENOIX A ................... .. ........................................... 352
SYMBOLS .. . ... .. ...................... .. ............. ... ................... 356
ACRONYMS ................................................................. ·367
The Structural Engineering Institule (SEI) of the American Society of Civil Engineers is commitled
to providing accurate, up-to-date information to its readers. To that end, SEI maintains a listing of
errata at http://www.sei nst itute.org/publ ications/errata.cfm.
xvi
Seismic Rehabilitation of Existing Buildings
1.0 REHABILITATION REQUIREMENTS the desired levels when subjected to the design earth-
quakes. However, compliance with this standard does
1.1 SCOPE not guarantee such performance; rather, it represents
the current standard of practice in designing to attain
This standard for the Seismic Rehabilitation of Lhis performance. The practice of earthquake engineer-
Existing Buildings, reterred to herein as "this stan- ing is rapidly evolving, and both our underslanding of
Jard," specilies nationally applicable provisions for the the behavior of buildings subjected to strong earth-
ismic rehabilitation of buildings. Seismic rehabilita- quakes and our ability to predicl this behavior are
tion is defined as improving the seismic performance advancing. In the future, new knowledge and technol-
of structural and/or nonstructural components of a ogy will improve the reliabilily of accomplishing these
bui lding by correcting deticiencies identified in a seis- goals.
míe evaluation. Seismic evaluation is detined as an The procedures contained in this standard are
pproved process or methodology of evaluating defi- specifically applicable to the rehabilitation of existing
' ienc ies in a building, which preventthe building from buildings and, in general, are more appropriate for thal
ch ieving a selected Rehabilitation Objective. Seismic purpose than are new building codes. New building
eva luation using ASCE 31 (ASCE 2002), the proce- codes are primarily intended to regulate the design and
dures and criteria of this standard, or other procedures construction of new buildings; as such, Lhey include
and criteria approved by the authority having jurisdic- many provisions thal encourage or require the develop-
tio n is permitted. ment of designs with tealures importan! for good seismic
Seismic rehabilitation of existing buildings shall performance, including regular configuration, structural
o mply with requirements of this standard for select- continuity, ductile detailing, and materials of appropri-
mg a Rehabilitation Objective and conducting the seis- ate qualily. Many existing buildings were designed and
míe rehabilitation process to achieve the selected constructed without these features and contain charac-
Rehabilitation Objective. This standard does not pre- teristics such as unfavorable contiguration and poor
lude a building from being rehabilitated by other pro- delailing that preclude application of building code pro-
ed ures approved by the authority having jurisdiction. visions for their seismic rehabilitation.
Symbols, acronyms, delinitions, and reterences Although it is intended to be used as a follow-up
used throughout this standard are cited separately in to a previous seismic evaluation , this standard can also
ections Jocated at the end of thi s standard. be used as an evaluation too) to ascertain compliance
with a selected rehabilitation objective. An ASCE 31,
Tier 3 evaluation is an example of this use. It should
Cl.l SCOPE be noted, however, that an evaluation using Lhis stan-
dard may be more slringenl than other evaluation
Th is standard is intended lo serve as a nationally methodologies because the provisions have been cali-
applicable tool for design professionals, code ofticials, brated for use in design . Hi storically, criteria for evalu-
and building owners undertaking the seismic rehabili- ation have been set lower than those for design to
tation of existing buildings. In jurisdictionally man- minimize the need to strengthen buildings that would
da ted seismic rehabilitation programs, the code olficial otherwise have only modest deficiencies.
erves as the authority having jurisdiction. In volun- The expertise of the design professional in earth-
tary seismic rehabilitation programs, the building quake engineering is an important prerequisite for the
owner, or the owner's designated agent, serves as the appropriate use of this standard in assisting a building
authority having jurisdiction. owner to select voluntary seismic criteria or to design
This standard consists of two parts: Provisions, and analyze seismic rehabilitation projects, whether
which contain the technical requirements, and voluntary or required . The analytical work required by
Commentary, intended to explain the provisions. this standard must be performed under the responsible
Commentary for a given seclion is located immediately charge of a licensed professional engineer; however,
following the seclion and is identified by the same sec- Lhat does not preclude a design professional without a
tion number preceded by the letter C. prolessional engineering license, but with responsible
lt is expected that most buildings rehabilitated in charge, from leading a seismic rehabilitation project.
accordance with this standard would perform within For example, an architecl wilh responsible charge can
SEI :\11 C REHABILITATION OF EXISTING BUILDINGS
lead a sei smic rehabilitation projcct conducted in rehabilitation objecti\'es which must be met by builcl-
accordance with the simplilied rehabilitation describcd ings that have either been targcted by the jurisdiction
in Chapter 1O. for manclated seismic rehabilitation or-by reason of
This standard is intended to be generally applica- owner-initiated acti vities, such as major structural
ble to seismic rehabilitation of all buildings-regardless modilications-have come undcr the jurisdiction's
of importance, occupancy, historie status, or other rehabilitation ordinance. Since codes for ncw buildings
classilications of use. However, application of these have chapters that brielly adclress existing buildings,
provisions should be coordinated with other require- care must be takcn in coordinating and referencing the
ments that may be in eiTcct, such as ordinances gov- adoption of this standard to avoid ambiguity and con-
erning historie structures or hospital construction. In fusion with other ordinances and cocles.
addition to the direct e!Tects of ground shaking, this Since almost all structural seismic rehabilitation
standard also addresses the eiTects of local geologic work requires a building permit, the code ol'licial will
site hazards such as liquefaction. become an importan! part of the process. For voluntary
This standard is arranged such that there are four rehabilitation efforts, the building owner and thc code
analysis procedures that can be used, including the orticial need to come to agreement about the intended
Linear Static Procedure, Linear Dynamic Procedure, rehabilitation objective. The codc oflicial will verify
Nonlinear Static Procedure, and Nonlinear Dynamic that the owncr's stated objective is met in the design
Procedure. The linear analysis procedures are intended and construction phases of thc work. For jurisdiction-
to provide a conservative estímate of building response ally required rehabilitation eiTorts, whether caused by
and performance in an earthquake, though they are not passive or active programs (see Appendix A), the code
always accurate. Since the actual response or buildings orticial will veri fy that the requirecl objective is me t.
to earthquakes is not typically linear, the nonlinear Because the approaches ancl technology of this stan-
analysis procedures should provide a more accurate dard are not yet in the mainstream of dcsign and con-
representation of building response and performance. struction practices of the United States, it is imperative
ln recognition of the improved representation of build- that the code oflicial either develop the expertise in
ing behavior when nonlinear analysis is conducted, the this methodology or utilizc a pcer review typc of
nonlinear procedures have less-conservative limits on process to verify the appropriate application of this
permissible building response than do linear proce- standard. A jurisdiction must al so remain flexible ancl
dures. Buildings that are found to be seismically dell- open to other analyses and evaluations, which provide
cient based on linear analysis may comply with this a reasonable assurance of meeting the appropriate
standard if a nonlinear analysis is performed. rehabilitation objective.
Therefore, performing a nonlinear analysis can mini- In acldition to tcchniqucs for increasing the
mize or eliminate unnecessary seismic rehabilitation strength and ductility of systems, this standard pro-
and potentially lower construction costs. vides techniques for reducing seismic demand, such as
This standard applies to the seismic rehabilitation the introduction or isolation or damping devices.
of both the overall structural system of a building and Design of new builclings and cvaluation of components
its nonstructural components, including ceilings, parti- for gravity and wind rarees in the absence or earth-
tions, mechanical, electrical, and plumbing systems. quake demands are beyond thc scopc of this standard.
With careful extrapolation, the procedures of this This standard does not explicitly address the
standard may also be applied to many nonbuilding determina! ion of whether or nota rehabilitation project
structures such as pipe racks, steel storage racks, struc- should be undcrtaken for a particular building.
tural towers for tanks and vessels, piers, wharves, and Guidance on the use of this standard in voluntary or
electrical power generating facilities. However, the directed risk-mitigation programs is providcd in
applicability of these procedures has not been fully Appendix A. Determining wherc these provisions
examined for every type of structure-particularly should be requircd is beyond the scope of this stan-
those that have generally been covered by specialized dard. Once the decision to rehabilitate a building has
codes or standards, such as bridges and nuclear power been made, this standard can be referenced for
plants. detailed engineering guidance on how to conducta
Jurisdictions will adopt this standard as an ordi- seismic rehabilitation analysis and design.
nance that only applies to the seismic rehabilitation of Featured in this standard are descriptions of dam-
existing buildings or adopt this standard by reference age states in relation to specilic performance levels.
as part of a comprehensive code addressing all aspects Thcse descriptions are intencled lo aid the authority
of rehabilitating existing buildings. In adopting this having jurisdiction, design professionals, and owners
standard, the jurisdiction will select one or more in selecting appropriate performance levels for
2
ASCE/SEI 41-06
rehabilitation design. They are not intended to be used commentary of this standard. For this reason, section
for condition assessment of earthquake-damaged numbers in this standard remain essentially the same
buildings. Although there may be similarities between as in FEMA 356.
lhese damage descriptions and those used for FEMA 356 was based on FEMA 273 (FEMA
postearthquake damage assessment, many factors enter 1997), which was developed by a large team of spe-
ínto the processes of assessing seismic performance. cialists in earthquake engineering and seismic rehabili-
. ·o single parameter in this standard should be cited as tation. The most advanced analytical techniques con-
delining either a performance leve! or the safety or sidered practica] for production use have been incor-
u~efulness of an earthquake-damaged building. porated. The acceptance criteria have been specified
Techniques for repair of earthquake-damaged using actual laboratory test results, where available,
bu ildings are not included in this standard, but are ref- supplemented by the engineering judgment of various
erenced in the commentary pertaining to Chapters 5 developmentteams . Certain buildings damaged in the
y lhrough 8 where such guidelines exist. Any combina- 1994 Northridge earthquake and a limited number of
úo n of repaired components, undamaged existing designs using codes for new buildings have been
'Omponents, and new components can be modeled checked using the procedures of FEMA 273. A com-
u~i ng this standard, and each checked against perfor- prehensive program of case studies was undertaken by
ma nce leve) acceptance criteria. If the mechanical FEMA in 1998 to test more thoroughly the various
properties of repaired components are known, accept- analysis techniques and acceptability criteria. The
ance criteria for use with this standard can be either results of this study are reponed in FEMA 343, Case
deduced by comparison with other similar components Studies: An Assessment ofthe NEHRP Cuidelinesfor
or derived . the Seismic Rehabilitation of Buildings. The results of
the FEMA 343 case studies have been incorporated in
the provisions of this standard, where possible.
1.2 DESIGN BASIS Similarly, information from FEMA 350 (FEMA 2000),
FEMA 351 (FEMA 2000), and other reports published
The selection of a seismic Rehabilitation Objective and by the SAC Joint Venture project, formed as a result of
the performance-based design of rehabilitation meas- the Northridge steel moment frame damage, has been
ures to achieve the selected Rehabilitation Objective incorporated where applicable. Engineering judgment
~h a ll be in accordance with the rehabilitation process should be exercised in determining the applicability of
e
~pecified in Section 1.3. The use of alternative per- various analysis techniques and material acceptance
for mance-based criteria and procedures approved by criteria in each situation.
the authority having jurisdiction shall be permitted. The commentary to this standard contains spe-
citic references to many other documents. In addition,
as this standard is related generically to the following
C1.2 DESIGN BASIS publications.
~ts
Provisions of this standard for seismic rehabilitation l. FEMA 450,2003 NEHRP Recommended
are based on a performance-based design methodology Provisions for Seismic Regulations for New
tha t differs from seismic design procedures for the Buildings and Other Structures, also referred to
ect design of new buildings currently specified in national herein as Lhe 2003 NEHRP Recommended
building codes and standards. Provisions (FEMA 2004).
The framework in which these requirements are 2. FEMA 237, Development of Cuidelines for Seis míe
pecitied is purposefully broad so that Rehabilitation Rehabilitation of Buildings, Pitase 1: Issues
Objectives can accommodate buildings of different ldentification and Resolution (FEMA 1992), which
types, address a variety of performance levels, and underwent an American Society of Civil Engineers
S
re tlect the variation of seismic hazards across the (ASCE) consensus approval process and provided
Un ited States and U.S . territories . policy direction for this standard.
The provisions and commentary of this standard 3. Applied Technology Council (ATC), ATC-28-2,
are based primarily on the FEMA 356 Prestandard Proceedings of the Workshop to Resolve Seismic
m- (FEMA 2000) with limited materialtaken from the Rehabilitation Sub-lssues (ATC 1993) provided
FEMA 274 (FEMA 1997) Commentary. This standard recommendations to the writers of this standard
is intended to supersede FEMA 356, but FEMA 274 on more detailed sub-issues.
rs remains a valid explanation for the provisions in this 4. FEMA 172, NEHRP Handbook ofTechniquesfor
standard unless indicated otherwise in the relevan! the Seismic Rehabilitation ofExisting Buildings
3
SEISMIC REHABILITATION OF EXISTING BUILDINGS
(FEMA 1992), originally produced by URS/Biume 9. ATC 40, Seismic Evaluatíon and Retrofit of Concrete
and Associates and revicwed by the Building Seismic Buildings (ATe 1996), incorporales performance
Safety eouncil (BSSC), contains construction tech- levels almost idcntical lO those shown in Table e 1-8
niques tor implementing engineering solutions Lo and cmploys "pushover" non linear analysis tech-
Lhe seismic deticiencies of existing buildings. niques. The capacity spectrum method for determin-
5. FEMA 178, NEHRP Handbookfor the Seismic ing the displacement demand is treated in detail.
Evaluarían of Existíng Buíldíngs (FEMA 1992), This document covers only concrete buildings.
which was originally developed by ATe and under-
wenl the consensus approval process of the BSSe,
covered the subject of evaluating existing buildings 1.3 SEISMIC REHABILITATION PROCESS
Lo determine if they are seismically deticient in
Lerms of life safety. This documenl has been Seismic rehabilitation of an existing building shall be
updated by FEMA and ASeE, and is now ASeE 31, conducted in accordance with thc process outlinecl in
Seísmíc Evaluarían of Existíng Bui ldings (ASeE Sections 1.3.1 through 1.3 .6.
2002), which underwenl an ASeE consensus
approval process. (The model building Lypes and
other information from ASeE 31 are used or C1.3 SEISMIC REHABILITATION PROCESS
referred Lo extensively in this standard in
ehapler 10.) The steps are presented in this section in the order in
6. FEMA 156 and 157, Typical Costs for Seismic which they would typically be followed in the rehabili-
Rehabi/itation of Exísting Buildíngs, Second tation process. However, the criteria for performing
Edition (FEMA 1995), reports stalistical analysis of these steps are presented in a somewhat different order
the costs of rehabilitation of more than 2,000 build- to facilitate presenta! ion of the concepts.
ings based on construction costs or detailed studies. Figure el-1 depicts the rehabilitation process
Several ditlerent seismic zones and performance spcc itied in thi s standard and shows spccilic chap-
levels are included in the data. Since the data were tcr references in parenthcses at points where input
dcveloped in 1994, none of the data is based on from this standard is to be obtained. Although
buildings rehabilitated specitically in accordance Fig. e 1-1 is written for voluntary rehabilitations,
with the FEMA 273 Guidelines document. it can also be used as a guide for manclatory
Performance levels detined in Lhis standard are not rehabilitations.
intended Lo be significantly ditTerenl from parallel This standard requires the sclection of a Rchabili-
level s used previously, and costs still should be tation Objcctive for a building that has been pn::viously
reasonably representative. idcntilied as needing seismic rehabilitation.
7. FEMA 275, Planning for Seísmic Rehabilitation: Prior to embarking on a rchabilitation program , an
Socíetal/ssues (FEMA 1998), discusses societal evaluation should be performed lo determine whether
and implementation issues associated with rehabili- the building, in its existing condition, has the desired
lation and describes several case histories. seism ic performance capability. ASCE 31 contains an
8. FEMA 276, Guidelines for the Seismic Rehabilita- evaluation methodology that may be used for this pur-
tion of Buildings: Example Applications (FEMA pose. 11 should be noted , however, thal a building may
1999), intended as a companion document to meel cenain performance objectives using the method-
FEMA 273 and FEMA 274, describes examples ology of ASeE 31, but may not meet those samc per-
of buildings that have been seismically rehabilitated formance objectives when an evaluation is performed
in various seismic regions and for diiTerent using the proccdures of this standard. This is largely
Rehabilitation Objectives. eosts of the work are because ASeE 31 is speci lically in tended to accept
given and references made to FEMA 156 and 157. somewhat greater levels of damage within each per-
Bccause this document is based on previous case formance level than permiued by this standard, which
histories, none of the examples was rehabilitated is consisten! with the historie practice of cvaluating
specitically in accordance with this standard . existing buildings for slightly lower criteria than thosc
However, performance levels detined in this stan- used for dcsign of new buildings. ASeE 31 quantilies
dard are not intended Lo be signilicantly different this di!Tcrcnce with the use of a 0.75 factor on
from parallel levels usecl previously, and the case dcmands when using this standard in a Tier 3 evalua-
studies are therefore considered representative. tion. This essemially lowers thc reliability of achieving
4
ASCE/SEI 41-06
lhe selected performance level from about 90% to 1.3.1 Initial Considerations
ut 60%. This practice minimizes the need to reha- The design professional shall review initial con-
ílitate structures with relatively modest deticiencies siderations with the authority having jurisdiction to
relative to the desired performance leve!. determine any restrictions that exist on the design of
1
Prior Seismic Evaluation
u 1 1
..
Review lnitial Considerations (Section 1.3.1)
Structural characteristics (Chapter 2)
1
lnterest in reducing seismic risk
y ..
Results from prior seismic evaluations (Section 1.2)
Occupancy (not considerad in this standard)
Historie status (Appendix A)
..
Economic considerations {Section C 1.3.6.2)
Societat issues: (Appendix A)
Local jurisdictional requirements (not included in this standard)
"-../
12 ..
Select Rehabilitation Objective (Section 1.3.2)
Target Building Pertormance level (Section 1.5)
Seismic Hazard (Section 1.6)
li- "'-..7
er
l 3
Obtain As-Built lnformation (Chapter 2) (Section 1.3.3)
1
'(7
14
Select Rehabilitation Method (Section 1.3.4)
1
V V V
4A Simplified Rehabilitation (Chapters 2, 10 4B
..
Systematic Rehabilitation (Chapters 2 through 9 and 11) 4C Other Choices
.. ..
and 11) Consider deficiencias (not in this standard)
.
ldentify building model type
Consider deficiencias
Select full or partial rehabilitation
..
Select rehabilitation strategy (Chapter 2)
Select analysis procedure (Chapters 2 and 3)
Consider general requirements (Chapter 2)
Reduce occupancy
Demolish
.
1.3.5)
5B
..
Perlorm Rehabilitation Design (Section 1.3.5)
Develop mathematical modal (Chapters 3 through 9 lar stiffness and strength
!1'
Determine and design rehabilitation
measures to meet applicable
ASCE 31 requirements
.Perform force and deformation response evaluation (Chapters 2 through 9 and 11)
Size elements, components, and connections (Chapters 2, 4 through 9, and 11)
d
111
ur-
ay --v v
od-
6A
.
Verify Rehabilitation Design (Section 1.3.6)
Reevaluate building to assure that
6B
..
Verily Rehabilitation Design (Section 1.3.6)
Apply component acceptance criteria (Chapters 2 through 9 and 11)
:r-
~d .
rehabilitation measures remove all
deficiencias without creating new ones
Review for economic acceptability
. Review lor conformance with requirements al Chapter 2
Review for economic acceptability
ich
v
6.1A Redesign Unacceptable
0
6.2A Prepare Construction
v
6.18 Redesign Unacceptable
v
6.28 Prepare Construction
Rehabilitation Oocuments ol Acceptable Rehabilitation Oocuments al Acceptable
ose .
(Section 1.3.6.1)
Return to 4A to reconsider
Rehabilitation
.
(Section 1.3.6.2) .
(Section 1.3.6.1)
Return to 48 to revise .
Rehabilitation (Section 1.3.6.2)
Develop construction
ics
Rehabilitation Objective or
to SAto revise correctiva
measures
Develop construction
..
documents
Begin rehabilitation
analysis and design orto
2 to reconsider
Rehabilitation Objective
..
documents
8egin rehabilitation
Exercise quality control
Exercise quality control
la-
ving FIGURE Cl-1. Rehabilitation Process.
5
SEISMIC REHABILITATION OF EXISTI G BUILDINGS
rehabilitation measures. Initial considerations shall can be provided , and nonhistoric buildings can be
include structural characteristics of the building, seis- demolished and replaced. Thc risks posed by non-
míe hazards including geologic sitc hazards known to structural components and contents can be reduced .
be present at the si te, results of prior seismic evalua- Seismic site hazards other than shaking can be
tions, building use and occupancy requirements, his- mitigated.
torie status, economic considerations, societal issues, Most ot'ten, however, when all alternatives are
and local jurisdictional requirements . considered, the options of modifying the building to
reduce the risk of damage should be studied. Such cor-
C1.3.1 Initial Considerations rective measures include stitTening or strengthening
The process of building rehabilitation will be sim- the structure, adding local componcnts to eliminate
plilied and made more efticient if information that sig- irregularities or tie the structure togcther, reducing the
nificantly affects the rehabilitation design is obtained demand on the structure through the use of seismic
and considered prior to beginning the process. isolation or energy dissipation devices, and reducing
Rehabilitation requirements mandated by local juris- the height or mass of the structure. Rehabilitation
dictions would be particularly important to determine strategies are di sc ussed in Chapter 2.
in the initial stages of a project.
The building owner should be aware of the range 1.3.2 Selection of Rehabilitation Objective
of costs and impacts of rehabilitation, including both A seismic Rchabilitation Objective shall
the variation associated with different Rehabilitation be selected for the building in accordance with
Objectivcs and the potential additional costs often Section 1.4.
associated with seismic rehabilitation, such as other
life safety upgrades, hazardous material removal , work C1.3.2 Selection of Rehabilitation Objective
associated with the Americans with Disabilities Act, The concepts and terminology of performance-
and nonseismic building remodeling. Also to be con- based design are new and should be carefully studied
sidcred are potential federal tax incentives for the and discussed with building owners before use . The
rehabilitation of historie buildings and for some other terminology used for target Building Performance
older nonresidential buildings. Lcvcls is intended to represent goals of design. The
Seismic hazards other than ground shaking may actual ground motion will seldom be comparable to
exist at the building site. The risk and possible extent that specitied in the Rehabilitation Objective, so in
of damage from gcologic si te hazards identified in most events, designs targcted at various damage states
Section 4.2.2 should be considered before undertaking may only determine relative performance. Ewn given
a rehabilitation aimed solely at reducing damage due a ground motion similar to that specitied in the
to shaking. In some cases it may be feasible to miti- Rehabilitation Objective and used in design , variations
gate the site hazard or rehabilitate the building and from stated performance objectives should be expected
still meel the selected performance leve!. In other and compliance with this standard should not be con-
cases, the risk due to site hazards may be so extreme sidered a guarantee of performance. Variations in
and dirticult to control that rehabilitation is neither actual performance could be associated with unknown
cost-clTective nor feasible. geometry and memher sizes in existing buildings,
The use of the building must be considered in deterioration of materials, incomplcte si te data, varia-
weighing the signilicance of potential temporary or tion of ground motion that can occur within a small
pennanent disruptions associated with various risk- area, and incomplete knowledgc and simplilications
mitigation schemes. Other limitations on modifications related to modeling and analysis. Information on the
to the building due to historie or aesthctic features expectcd reliability of achicving various target
must also be understood. The historie status of every Building Performance Levels when the requirements
building at least 50 years old should be determined are followed can be found in Chaptcr 2 of FEMA 274 1
(see Appendix A, Section A.6, Considerations for (FEMA 1997).
Historie Buildings). This determination should be The determin ation of the Rehabilitation Ohjcctive
made early as it could influence the choices of rehabil- dit'fers depending on whether the rehabilitation is R
itation approaches and techniques. mandated or voluntary. For a voluntary building reha-
There are many ways to reduce seismic risk, bilitation, the building owner shall selecta seismic
whcther the risk is to property, life safety, or post- rehabilitation for the building as specified in Sec-
earthquake use of the building. The occupancy of vul- tion 1.4. In a mandated rehahilitation project, the
nerable buildings can be reduced, redundant facilities rehabilitation objective i either stipulated directly by
6
ASCE/SEI 41-06
local code or ordinance or the code ofticial is provided 1.3.6.2 Construction Documents
\\ ith guidelines for negotiating the rehabilitation lf the design of rehabilitation measures meets the
objective. acceptance criteria for the sele<.:ted Rehabilitation
Objective, and the decision is made to proceed with
the rehabilitation, construction documents shall be pre-
1.3.3 As-Built Information
pared and shall indude requirements for construction
Available as-built information for the building
quality assurance in accordance with Se<.:tion 2.7.
~a l! be obtained and a site visit shall be conducted as
pecitied in Section 2.2.
Cl.3.6.2 Construction Documents
At this stage, a cost estímate can be made to review
1.3.4 Rehabilitation Method
the economic acceptability of the design. Cost estimating
An applicable rehabilitation method shall be
or reviewing economic acceptability of the rehabilitation
de termined in accordance with Section 2.3.
design is not included in this standard, but is an essential
pan of the rehabilitation process shown in Fig. C 1-1.
Cl.3.4 Rehabilitation Method Construction costs are discussed in FEMA 276,
Rehabilitation can consist of the Simplified Example Applications (FEMA 1999), and FEMA 156
Rehabilitation Method or the Systematic and 157, Typical Costs for Seismic Rehabilitation of
Rehabilitation Method. These methods are defined in Buildings (FEMA 1995).
ec tion 2.3 and further explained in the associated If the design proves uneconomical or otherwise
ommentary of that section. not feasible, further retinement may be considered in
analysis, a differem rehabilitation scheme may be
1.3.5 Rehabilitation Measures designed ora dift'erent Rehabilitation Objective may
Rehabilitation measures shall be designed using be considered.
the applicable rehabilitation method . A successful rehabilitation project requires a good
set of construction documents with a quality assurance
program to ensure that the design is implemented prop-
1.3.6 Verification of Rehabilitation Design erly. Section 2.7 specities provisions for a quality assur-
The design of rehabilitation measures shall be ance program during the construction or implementation
veritied lo meet the requirements of this standard of the rehabilitation design. Other aspects of the imple-
;s through an analysis of the building, including the mentation process, including details of the preparation
n rehabilitation measures. The analysis shall be con- of construction documents, obtaining a building pennit,
istent with the procedures for the applicable rehabili- selection of a contractor, details of historie preservation
ns tation method specitied in Section 2.3. A separate techniques for panicular kinds of materials, and financ-
ed analytical evaluation shall be performed for each ing are not covered in this standard.
1-
combination of building performance and seismic
hazard specified in the selected Rehabilitation
Objective. 1.4 REHABILITATION OBJECTIVES
C1.3.6 Verification of Rehabilitation Design A seismic Rehabilitation Objective shall consist of one
At this stage, a cost estímate can be made using or more rehabilitation goals. Each goal shall consist
a conceptual or schematic design to verify economic of a target Building Performance Leve! detined in
acceptability. Section 1.5 and an Earthquake Hazard Leve! defined
in Section 1.6. Goals shall be selected considering
basic, enhanced, or limited objectives as defined in
1.3.6.1 Unacceptab/e Rehabilitation Sections 1.4.1 through 1.4.3.
If the design of rehabilitation measures fails to
\ve comply with the acceptance criteria for the selected
Rehabilitation Objective, the rehabilitation measures C1.4 REHABILITATION OBJECTIVES
a- shall be redesigned oran alternative rehabilitation
strategy with a different Rehabilitation Objective shall Recommendations regarding the selection of a
be implemented. This process shall be repeated until Rehabilitation Objective for any building are beyond
the design is in compliance with the acceptance crite- the scope of this standard. FEMA 274 (FEMA 1997)
y ria for the selected Rehabilitation Objective. discusses issues to consider when combining various
7
SEISMIC REHABILITATION OF EXISTING BUILDINGS
performance and seismic hazard levels. It should be Table Cl-1. Rehabilitation Objectives
noted that not all combinations constitute reasonable
or cost-effective Rehabilitation Objectives. This stan- Target Building
dard is writtcn under the premise that greater flexibil- Performance Lcvels
ity is required in seismic rehabilitation than in the
dcsign of new buildings. However, given that tlexibil-
ity, once a Rehabilitation Objective is selected, this
standard provides internally consistent procedurcs with
the necessary specificity to perform a rehabilitation
analysis and design .
Building performance can be described qualita-
tivcly in terms or the safety afforded building occupants
during and afler the event; the cost and feasibility of
restoring the building to its pre-earthquake condition; 50%/50 year a b e d
thc length or time the building is removed ti·om service
20%/50 ycar e f g h
to ciTect repairs; and economic, architectural, or historie
impacts on the larger community. These performance BSE-1
(- 10%/50 year i k
characteristics are directly relatcd Lo the extent or dam-
age that would be sustained by the building. BSE-2
In this standard, the extent of damage to a building (- 2%/50 ycar) m n o p
is categorized as a Building Performance Leve!. A 'Each cell in the above matrix represcnts a discretc Rehabilitation
broad range of targct Building Performance Levels may Objective.
2Thc Rehabilitmion Objectives in the matrix above may be used to
be sclected when dctermining Rehabilitation Objectives.
represelll the three specific Rehabilita! ion Objectives defined in
Probabilistic Earthquake Hazard Levels frequently
Sections 1.4.1 , 1.4.2, and 1.4.3, as follows:
used in this standard and their corresponding mean Basic Safety Objective ( BSO) k and p
return pcriods (the average number of years between Enhanced Objcctivcs k and m, n, oro
events of similar severity) are as follows: p and i or j
k and p and a, b, e, or f
Earthquake Having Mean Return m, n, oro alone
Probability of Exceedance Period (years) Limited Objectives k alone
p alone
50%/50 year 72 e, d, g, h, or 1 alone
20%/50 year 225
10%/50 year 474
2%/50 year 2,475
These mean return periods are typically rounded C1.4.1 Basic Safety Objective (BSO)
to 75, 225, 500, and 2,500 years, respectively. The BSO is intended to approximate the earth-
The Rehabilitation Objective selected as a basis quake risk to life safety traditionally considered
for design will determine, to a great extent, the cost acceptable in the United States. Buildings meeting
and feasibility of any rehabilitation project, as well as the BSO are expectcd to expcrience littlc damage
the benetit to be obtained in terms of improved safety, from relatively frequent, modcrate earthquakes, but
reduction in property damage, and interruption or use significantly more damage and potential economic
in the event of future earthquakes. Table C 1-1 indi- loss from the most severe and infrequent earthquakes
cates the range of Rehabilitation Objectives that may that could allect them . The leve! of damage and
be used in this standard. potential economic loss expcrienced by buildings
rchabilitatecl to the BSO may be greater than that
1.4.1 Basic Safety Objective cxpectecl in properly designccl and constructcd new
The Basic Safety Objective (BSO) is a Rehabili- buildings.
tation Objective that achieves the dual rehabilitation
goals of Life Safety Building Performance Leve! (3-C) 1.4.2 Enhanced Rehabilitation Objectives
for the BSE-1 Earthquake Hazard Leve! and Collapse Rehabilitation that providcs building performance
Prcvention Building Performance Leve! (5-E) for the exceccling that of the BSO is Lermecl an Enhanced
BSE-2 Earthquake Hazard Leve!. Objective. Enhanced Rehabilitation Objcctives shall
8
ASCE/SEI 41-06
hieved using one or both of the following two seismic hazard or lower target Building Performance
Leve! than the BSO, is termed Reduced Rehabilita-
tion Objective. Reduced Rehabilitation shall be
13_ de igning for target Building Performance
designed tor one or more of the following objectives:
L eh that exceed those of the BSO at the BSE- 1
~· d leve!, the BSE-2 hazard leve!, or both. l. Life Safety Building Performance Leve! (3-C) for
desig ning for the target Building Performance earthquake demands that are equal to the BSE-1, or
el ' of the BSO using an Earthquake Hazard Collapse Prevention Building Performance Leve!
el that exceeds either the BSE-l or BSE-2 haz- (5-E) for earthquake demands that are equal to the
BSE-2, but not both;
2. Life Safety Building Performance Leve! (3-C) for
.U Enhanced Rehabilitation Objectives earthquake demands that are less severe (more
Enhanced Rehabilitation Objectives can be probable) than the BSE-1;
oed by designing for higher target Building 3. Collapse Prevention Building Performance Leve!
ormance Levels (method 1) or by designing using (5-E) tor earthquake demands that are less severe
_ r Earthquake Hazard Levels (method 2), ora (more probable) than the BSE-2; or
inmion of these methods. 4 . Building Performance Levels 4-C, 4-D, 4-E, 5-C,
5-D, 5-E, 6-C, or 6-D for BSE-1 or less severe
..3 Limited Rehabilitation Objectives (more probable) earthquake demands .
Reha bilitation that provides building performance
tlun that of the BSO is termed a Limited
uve. Limited Rehabilitation Objectives shall be C1.4.3.1 Reduced Rehabilitation Objective
.ed using Reduced Rehabilitation specitied in Rehabilitation tor the Life Safety Building
n 1.4.3. 1 or Partial Rehabilitation specified in Performance Leve! at the BSE-1 is a commonly used
· n 1.4.3.2, and shall comply with the following reduced rehabilitation objective.
9
SEISMIC REHABILITATION OF EXISTING BUILDINGS
components. Table e 1-2 describes the approximate damage states identilied as target Building
limiting levels of structural and non structural damage Performance Level s in this standard have been
that may be expected of buildings rehabilitated Lo the selected because they havc rcadily identiliable conse-
levels detined in this standard. On average, the quences associatcd with the postearthquake di spos i-
expected damage would be less. For comparative pur- tion of the building that are mcaningful to the
poses, the estimated performance of a new building building community. These include the ability lo
subjected to the BSE-1 leve! of shaking is indicated. resume normal functions within the building, the
Performance descriptions in Tablee 1-2 are estimates advisability of postearthquake occupancy, and the
rather than precise predictions, and variation among risk to life safe ty.
buildings of the same target Building Performance Due to inherent uncertainties in prcdiction of
Level must be expectcd . ground motion and analytical prediction of building
Building performance in this standard is performance, some variation in actual performan ce
expressed in terms of target Building Performance should be expected. eompliance with this standard
Levels. These target Building Performance Level s are should not be considcred a guarantee of performance.
di screte damage states selected from among the inli- Information on Lhe rcliability of achieving various
nite spectrum of poss iblc damage states that buildings performance level s can be found in ehapter 2 of
could expericnce during an earthquake. The particul ar FEMA 274 (FEMA 1997).
10
ASCEISEI 41-06
1.5.1 Structural Performance Levels and Ranges The expected postearthquake state of the buildings
The Structural Performance Leve! of a building described in these tables is for comparative purposes
all be selected from four discrete Structural and should not be used in the postearthquake safety
Performance Levels and two intermediare Structural evaluation process.
Performance Ranges defined in this section.
The discrete Structural Performance Levels are 1.5.1.11mmediate Occupancy Structural
Im mediate Occupancy (S-1 ), Life Safety (S-3), Performance Leve/ (S-1)
Collapse Prevention (S-5), and Not Considered (S-6). Structural Performance Leve! S-1, Immediate
De ign procedures and acceptance criteria correspon- Occupancy, shall be defined as the postearthquake
mg to these Structural Performance Levels shall be as damage state in which a structure remains safe to
~c ified in Chapters 4 through 9 or Chapter 10. occupy, essentially retains its pre-earthquake design
The inrermediate Structural Performance Ranges strength and stiffness, and is in compliance with the
are the Damage Control Range (S-2) and the acceptance criteria specified in this standard for this
Lm1 ited Safety Range (S-4). Acceptance criteria for Structural Performance Leve!.
~rformance within the Damage Control Structural
Performance Range shall be obtained by interpolating Cl.5.l.llmmediate Occupancy Structural
_ tween the acceptance criteria provided for rhe Performance Leve/ (S-1)
Immediate Occupancy and Life Safety Structural Structural Performance Leve! S-1, Immediate
Performance Levels. Acceptance criteria for perfor- Occupancy, means the postearthquake damage state in
mance within the Limited Safety Structural Performance which only very limited structural damage has
Ra nge shall be obtained by interpolating between the occurred. The basic vertical- and lateral-force-resisting
·ceptance criteria provided for the Life Safety and systems of the building retain nearly all of their pre-
Collapse Prevention Structural Performance Levels. earthquake strength and stiffness. The risk of life-
threatening injury as a result of structural damage is
C1.5.1 Structural Performance Levels and Ranges very low, and although some minor structural repairs
A wide range of structural performance require- may be appropriate, these would generally not be
ments could be desired by individual building owners. required prior to reoccupancy.
The four Structural Performance Levels defined in this
tandard have been selected to correlate with the most 1.5.1.2 Damage Control Structural Performance
y
·ommonly specified structural performance require- Range (S-2)
ments. The two Structural Performance Ranges permit Structural Performance Range S-2, Damage
users with other requirements to customize their build- Control, shall be defined as the continuous range of
~d
mg Rehabilitation Objectives. damage states between the Life Safety Structural
Table C l-3 relates these Structural Performance Performance Leve! (S-3) and the Immediate
\11 Levels to the limiting damage states for common Occupancy Structural Performance Leve! (S-1 ).
\ertical elements of lateral-force-resisting systems.
Tab le C 1-4 relates these Structural Performance Levels C/.5.1.2 Damage Control Structural Performance
10 the limiting damage states for common horizontal Range (S-2)
e lements of building lareral-force-resisring systems. Design for the Damage Control Structural
Later sections of this standard specify design parame- Performance Range may be desirable to minimize
ters (such as m-facrors, componen! capacities, and repair time and operation interruption, as a partial
til- inelastic deformation capacities) specilied as limiting means of protecting valuable equipment and con-
values for attaining these Structural Performance tenis or to preserve importan! historie features when
Levels for a known earthquake demand. the cost of design for immediate occupancy is
The drift values given in Table C 1-3 are typical excessive.
nd values provided to illustrate the overall structural
response associated with various Structural Perfor- 1.5.1.3 Life Safety Structural Performance Leve/ (S-3)
mance Levels. They are not provided in these tables as Structural Performance Level S-3, Life Safety,
drift limit requirements for this standard, and do not shall be defined as the postearthquake damage state in
supersede componen! or element deformation limits which a structure has damaged components but retains
that are specified in Chapters 4 through 9, and 11. a margin against onset of partial or total collapse, and
11
Table Cl-3. Structural Performance Levels and Damage 1.1.3 _ Vertical Elements
Concrete Frames Primary Exrensive cracking and hinge Extensive damage to beams. Minor hairline cracking. Limited
fonnation in ductile elemcnts. Spalling of cover and shear yielding possible ata few loca-
Limited cracking and/or splice cracking ( < 1/8-in. width) for tions. No crushing (strains
failure in some nonductile ductilc columns. Minor spalling below 0.003).
columns. Severe damage in in nonductile columns. Joint
short columns. cracks < 1/8 in. wide.
Secondary Extensive spalling in columns Extensive cracking and hinge Minor spalling in a few places in
(limited sh01tening) and beams. formation in ductile·elements. ductile columns and beams.
Severe joint damage. Some rein- Limited cracking and/or splice Flexura) cracking in be::uns and
forcing buckled. failure in some nonductile columns. Shear cracking in
columns. Severe damage in joints < 1/ 16-in. width.
short columns.
12
Structural Performance Levels
Collapse Prevention Life Safety lmmediate
Elements Type (S-5) (S-3) Occupancy (S-1)
ed l nreinforced Primary Extensive cracking and crush- Extensive cracking and some
Minor (< 1/8-in. width) crack-
w:.onry lnfill Walls ing; ponions of face course crushing but wall remains in
ing of masonry intills and
shed. place. No falling units. Exten-
veneers. Minor spalling in
si ve crushing and spalling of
veneers at a few corner
veneers at corners of openings.
openings.
Secondary Extensive crushing and shatter- Same as primary. Same as primary.
, in ing; some walls dislodge.
Foundations General Major settlement and tihing. Total settlements < 6 in. and dif- Minor settlement and negligible
ferential settlements < 1/ 2 in. tilting.
in 30ft.
of
'Damage states indicated in this table are provided to allow an understanding of the severity of damage that may be sustained by various structural elements where
present in su·uctures meeting the definitions of the Structural Performance Le veis. These damage states are not intended for use in postea11hquake evaluation of damage
li nts. or for judging the safety of, or required leve) of repair lo, a structure following an eanhquake.
nce 2 Drift values, differemial seulements, crack widths, and similar quantities indicated in these tables are not intended to be used as acceptance criteria for evaluating the
acceptability of a rehabilitation design in accordance with the analysis procedures provided in this standard; rather, they are indicative of the range of drift thattypical
SO'uctures containing the indicated structural elements may undergo when responding within the various Su·uctural Performance Levels. Drift control of a rehabilitated
structure may often be governed by the requirements to protect nonstructural components. Acceptable levels of foundation seulement or movement are highly depend-
en! on the construction of the superstructure. The values indicated are intended lO be qualitative descriptions of the approximate behavior of structures meeting the
indicated levels.
' For limiting damage to frame elements of infilled frames, refer 10 the rows for concrete or steel frames.
13
SEISMIC REHABILITATION OF EXISTI G BUILDINGS
Table Cl-4. Structural Performance Levels and Damage 1•2 -Horizontal Elements
Structural Performance Levels
Metal Deck Large distortion with buckling Some localized failure of Connections between deck units
Diaphragms of some units and tearing welded connections of deck to and framing intact. Minor
of many welds and seam framing and between panels. distortions.
attachments. Minor local buckling of deck.
Wood Diaphragms Large permanent distortion with Some splitting at connections. No observable loosening or
partía! withdrawal of nails and Loosening of sheathing. withdrawal of fasteners. No
extensive splitting of elements. Observable withdrawal of fas- splitting of sheathing or
teners. Splitting of framing and framing.
sheathing.
Concrete Extensive crushing and observ- Extensive cracking(< 1/4-in. Distributed hairline cracking.
Diaphragms able offset across many cracks. width). Local crushing and Some minor cracks of larger
spalling. size (< 1/8-in. width).
Precast Diaphragms Connections between units fail. Extensive cracking(< 1/4-in. Some minor cracking along
Units shirt relative to each width). Local crushing and joints.
other. Crushing and spalling spalling.
at joints.
1Damage stales indicated in lhis lable are provided lo allow an understanding of the severity of damage lhat may be sustained by various structural
elcments where prcsent in structures meeting lhe definitions of the Structural Performance Le veis. These damage stales are nol in tended for use in
posteanhquake evaluation of damage or for judging the safety of, or required leve! of repair to, a structure following an eanhquake.
2 Drifl values, differential settlements, crack widlhs, and similar quantities indicated in these tables are not intcnded ro be uscd as acceptance crite-
ria for evaluating the acceptability of a rehabilitation design in accordance with the analysis procedures provided in this standard; rather, they are
indicative of lhe range of driflthat typical structures containing the indicated structural elements may undergo when rcsponding wilhin the various
Slructural Performance Le veis. Drift control of a rehabilitaled structure may orten be governed by lhe requiremenls lo protect nonstruclural com-
ponents. Acceplablt: levels of foundalion settlement or movement are highly dependenl on lhe conslruclion of thc superslructure. The values indi-
cated are in tended to be qualitalive descriplions of the approximate behavior of structures meeting the indicated levels.
Concrete Diaphragms
is in compliance with the acceptance criteria specitied structural repairs or install temporary bracing prior
in this standard for this Structural Performance to rcoccupancy.
Leve l.
1.5.1.4 Limited Safety Slructural Pe1jormance
CJ.5.1.3 Life Safety Structural Performance Range (S-4)
Leve/ (S-3) Struclural Performance Range S-4, Limited
Structural Performance Level S-3, Life Safety, Safely, shall be defined as the conlinuous range of
means the postearthquake damage state in which sig- damage states between the Li fe Safety Structural
nificant damage to Lhe structure has occurred but some Performance Level (S-3) and the Collapse Prevention
margin against either partial or total structural collapse Structural Performance Level (S-5).
remains. Some structural elements and components
are severely damaged but this has not resulted in large 1.5.1.5 Co/lapse Prevention Structural Performance
falling debris hazards, either inside or outside the Leve/ (S-5)
building. Injuries may occur during the earthquake; Structural Performance Leve] S-5, Collapse
however, the overall risk of life-threatening injury as a Prevention, shall be defined as Lhe postearthquake (
resulL of su·uctural damage is expected to be low. It damage state in which a structure has damaged com- L
should be possible to repair the structure; however, ponents and conlinues to support gravity loads but L
for economic reasons this may not be practical. retains no margin against collapse, and is in compli- r
Although the damaged structure is not an imminent ance with the acceptance criteria spccilied in this stan-
collapse risk, it would be prudent to implement dard for this Structural Performance Level.
14
ASCE/SEI 41-06
CJ.S.l.S Collapse Prevention Structural Performance Occupant contents and furnishings (such as inventory
Leve/ (S-5) and computers) are included in these tables for some
Structural Performance Level S-5, Collapse levels but generally are not covered with specitic
Prevention, means the postearthquake damage state in requirements.
\ hich the building is on the verge of partial or total
.::ollapse. Substantial damage to the structure has 1.5.2.1 Operational Nonstructural Performance
·cmTed, potentially including significant degrada- Leve/ (N-A)
uo n in the stiffness and strength of the lateral-force- Nonstructural Performance Level N-A,
•esisting system, large permanent lateral deformation Operational, shall be defined as the postearthquake
f the structure, and-to a more limited extent-degra- damage state in which the nonstructural components
dation in vertical-load-carrying capacity. However, all are able to support the pre-earthquake functions pres-
igniticant components of the gravity-load-resisting ent in the building.
ys tem must continue to carry their gravity loads.
ignificant ri sk of injury dueto falling hazards from CJ.5.2.1 Operational Nonstructural Performance
tructural debris may exist. The structure may not be Leve/ (N-A)
technically practical to repair and is not safe for reoc- Al this level, most nonstructural systems required
upancy, as aftershock activity could induce collapse. for normal use of the building-including lighting,
plumbing, HVAC, and computer systems-are func-
1.5.1.6 Structural Performance Not tional, although minor cleanup and repair of some
Considered (S-6) items may be required . This Nonstructural Perfor-
A building rehabilitation that does not address mance Level requires considerations beyond those
the performance of the structure shall be classified that are normally within the sote province of the
pi
i.1:> Structural Performance Not Considered (S-6). structural engineer. In addition lo assuring that non-
In
structural components are properly mounted and
e- CJ.5.1.6 Structural Performance Not braced within the structure, it is often necessary to
e Considered (S-6) provide emergency standby utilities. It also may be
IUS
Some owners may desire to address certain non- necessary lo perform rigorous qualification testing
~
tructural vulnerabilities in a rehabilitation program- of the ability of key electrical and mechanical
i-
fo r example, bracing parapets or anchoring hazardous equipment items to function during or after strong
materials storage containers-without addressing the shaking.
performance of the structure itself. Such rehabilitation Specific design procedures and acceptance criteria
programs are somctimes attractive because they can for this Nonstructural Performance Level are not
pennit a significan! reduction in seismic risk at rela- included in this standard. Although the state of the art
tively low cost. for commercial construction does not provide a com-
plete set of references to be used for the seismic
1.5.2 Nonstructuml Performance Levels qualification and checking of nonstruclurai compo-
The Nonstructural Performance Level of a build- nents, the user is referred to the following documents
ing shall be selected from five discrete Nonstructural that m ay be use fui in seismically quali fying mechani-
Performance Levels, consisting of Operational (N-A), cal and electrical equipment for Operational
Immed iate Occupancy (N-B), Life Safety (N-C), Performance.
Hazards Reduced (N-D), and Not Considered (N-E).
Des ign procedures and acceptance criteria ror rehabili- l. AC-156. Acceptance Criteria for Seismic Qualifica-
ta tion of nonstructural components shall be as speci- tion Testing of Nonstructural Components (ICBO
tied in Chapter 1O or 1 l . 2000).
2. DOE/EH-545. Seismic Evaluation Procedure for
Cl.5.2 Nonstructural Performance Levels Equipment in U. S. Department of Energy Facilities
Nonstructural Performance Levels other than Not (lJ .S. Deparlment of Energy 1997).
Considered (N-E) are summarized in Tables C 1-5 3. IEEE 693. IEEE Recommended Practice for
through Cl-7. Nonstructural components addressed in Seismic Design of Substations (IEEE 1997).
this standard include architectural components such as 4. CERL Technical Report 97/58. The CERL
partitions, exterior cladding, and ceilings; and mechan- Equipment Fragility and Protection, Experimental
an- ical and electrical components, including HVAC sys- Dejinition of Equipment Vulnerability to Transient
tems, plumbing, tire suppression systems, and lighting . Support Motions (CERL 1997).
15
--
Hazards lmmediate
ReducecP Life Safety Occupancy Operati onal
Componen! (N-D) (N-C) (N-B) (N-A)
Cladding Severe distortion in connec- Scvere distortion in connec- Connections yield; minor Connections yield; minor
tions. Dislributed cracking, tions. Distributed cracking, cracks (< 1/ 16-in. width) cracks (< 1/ 16-in. width) or
bending, crushing, and bending, crushing, and or bending in cladding. bcnding in cladding.
spalling of cladding compo- spalling of cladding compo-
nents. Some fracturing of nenls . Some fracturing of
cladding, but panels do not cladding, but panels do not
fall in areas of public fall.
assembly.
Gl azing General shattered glass and Extensive cracked glass; lit- Some cracked panes; none Some cracked panes; nonc
distorted frames in unoccu- tle broken glass. broken. broken.
pied arcas. Extensive
cracked glass; liule broken
glass in occupied arcas.
Pm1iLion s Dis1ribu1ed damage; some Distributed damage; some Cracking lo aboul Cracking to aboul
severe cracking, crushing, severe cracking, crushing, 1/ 16-in . widlh al op.:nings. 1/ 16-in. width at opcnin gs.
and racking in some arcas. and racking in some arcas. Minor crushing and crack- Minor crushing and cracking
ing at corners at corners.
Ceilings Extcnsive damage. Dropped Extcnsive damagc. Dropped Minor damage. So me sus- Generally ncgligible dam-
suspended ceiling liles. suspended ceiling ti les. pemkd ceiling lilcs dis- age. lsolaled suspended
Modcralc cracking in hard Moderate cracking in hard rupted. A fcw panel s panel dislocalions, or cracks
ceilings. ceilings. dropped . Minor cracking in in hard ceilings.
hard ceilings.
Parap.:t s and Extensive damage; some Exlensive damage; some Minor damage. Minor damagc.
Ornamelllation falling in unoccupied areas. falling in unoccupied arcas.
Canopies and Moderale damage. Moderate damage . Minor damage. Minor damage.
M arquees
Chinmeys and Exlcnsive damage. No col- Extcnsive damage. No col- Minor cracking. Negligible damagc.
Stacks lapse. lapse.
S1airs ancl Fire Extensive racking. Loss of Some racking and cracking Mi nor dan1age. Negligible damage.
Escapes use. of slabs. Usable .
Doors Distribuled damage. Many Distributed damage . Somc Minor damagc. Doors M inor damagc. Doors oper-
racked and jammed doors. racked and jammed doors. operable. able.
1
Damage states indi cnted in thi s cable are provided to allow an unders tanding of the severity of damagc.:: that may be suswi ned by various nonstru ctural components
meeting the Nonstructural Performance Levcls defined in thi s standard. Tht: se damage states are nm intc.:nded for use in postearthquakt! evaluation of damage or for
judging the safely or required leve ! of rcpair following an earthquake.
2For the Hazards Reduced Pcrfonnance Leve!, high-hazard nonstru ctural components evaluated or rehabilitated to the Lil'e Saft!t)' criteria will have Hazards Reduced
performance identi callo that cxpectcd for the Life Safety Performance Leve l.
16
ASCE/SEI 41-06
Table Cl-6. Nonstructural Performance Levels and Damage 1-Mechanical, Electrical, and
Plumbing Systems/Components
Elevators Elevators out of service; Elevators out of service; Elevators operable; can be Elevators operate.
or counterweights off rails. counterwt!ights do not dis- started when power avail-
lodge. able.
HVAC Equipment Most units do not operate; Units shifl on suppmts, Units are secure and most Units are secure and oper-
many slide or overturn; rupluring attach.:d ducting, operate if power and ate. Emergency power and
some suspended units fall. piping, and conduit, but do other required utilities other utilities providt!d, if
not fall. are available. required.
Manufacturing Units slide and overturn; Units slide, but do not Units secure, and most Units secure and operable;
Equipment utilities disconnected. ovettum; utilities not avail- operable if power and util- power and utilities avail-
Heavy units require recon- able; some realignment ities available. able.
nection and realignment. required to operate.
Sensitive equipment may
not be functional.
;. Ducts Ducts break loase of Ducts break loose from Minor damage at joints, Negligible damage.
tng equipment and louvers; equipment and louvers; but ducts remain
some supports fail; some some suppotts fail; some serviceable.
ducts fall. ducts fall.
Piping Some lines rupture. Some Minor damage at joints, Minor leaks develop ata Negligible damage.
ks suppons fail. Some piping with some leakage. Some few joints.
fa lis. suppons damaged, but sys-
tems remain suspended.
Fire Sprinkler Systems Some sprinkler heads dam- Some sprinkler heads dam- Minor leakage ata few Negligible damage.
aged by collapsing ceil- aged by swaying ceilings. heads or pipe joints.
ings. Leaks develop at Leaks develop at some System remains
couplings. Some branch couplings. operable.
lines fail.
Fire Alann Systems Ceiling mounted sensors Ceiling mounted sensors System is functional. System is functional.
damaged. May not func- damaged. May not func-
tion . tion .
Emergency Lighting Some lights fall. Power Some lights fall. Power System is functional. System is functional.
er- may not be available. may be available from
emergency generator.
Electrical Distribution Units slide and/or overturn, Units shift on suppmts and Units are secure and gen- Units are functional.
Equipment rupturing attached conduit. may not operate. erally operable. Emergency power is pro-
Uninterruptable Power Generators provided for Emergency generators vi ded, as needed.
So urce systems fai l. Diesel emergency power start; statt, but may not be ade-
generators do not start. utility service lost. quate to service all power
requirements.
Light Fixlures Many broken light Many broken light fix- Minar damage. Some pen- Negligible damage.
fixtures . Falling hazards tures. Falling hazards gen- dant lights broken.
generally avoided in heav- erally avoided in heavier
ier fixtures (> 20 lb) in fi xtures (> 20 lb).
areas of public assembly.
Plumbing Some fixtures broken; Some fixtures broken, Fixtures and lines service- System is functional. On-
lines brokt!n; mains dis- lines broken; mains dis- able; however, utility serv- site water supply provided,
rupted al source. rupted al source. ice may not be available. if required.
1
Damage states indicated in this tableare provided 10 allow an understanding of the severity of damage that may be sustained by various nonstructural components
meeting the Nonstructural Performance Le veis detined in this standard. ·n,ese damage states are not intended for use in postearthquake evaluation of damage or for
judging the safety or required level of repair following an earthquake.
'For the Hazards Reduced Performance Leve), high-hazard nonstructural components evaluated or rehabilitated 10 the Life Safety criteria will ha ve Hazards Reduced
performance idemical to that expected for the Lite Safety Performance Level.
17
SEISMIC REHABILITATION OF EXISTJ G BUILDINGS
Computer Systems Units roll and overturn, Units shift and may dis- Units secure and remain Units undamaged and
disconnect cables. connect cables, but do connected. Power may operable; power
Raised access floors not overturn. Power not not be available to oper- available.
collapse. Power not available. ate, and minar interna!
available. damage may occur.
Desktop Equipment Some equipment slides Some equipment slides Some equipment slides Equipment secured to
off desks. off desks. off desks. desks and operable.
File Cabinets Cabinets overturn and Cabinets overturn and Drawers slide open, but Drawers slide open, but
spill contents. spill contents. cabinets do not tip. cabinets do not ti p.
Book Shelves Shelves overturn and Books slide off shelves. Books slide on shelves. Books remai n on
spi 11 contents. shelves.
Hazardous Minar damage; occa- Minar damage; occa- Negligible damage; Negligible damage;
Materials sional materials spilled; sional materials spilled; materials contained. materials contained.
gaseous materials gaseous mate1ials
contained. contained.
Art Objects Objects damaged by Objects damaged by Some objects may be Objects undamaged.
falling, water, dust. falling, water, dust. damaged by falling.
'Damage states indicated in this tableare provided to allow an understanding of the severity of damage that may be sustained by various nonstruc-
tural components meeting the Nonstructural Performance Levels dellned in this standard. These damage states are not intended for use in
postearthquake evaluation of damage or for judging the safety or required leve! of repair following an earthquake.
2For the Hazards Reduced Performance Leve! , high-hazard nonstructural components evaluated or rehabilitated to the Life Safety criteria will have
Hazards Reduced performance identicalto that expected for the Lite Sal'ety Performance Leve!.
Where equipment and systems are required to be ing is structurally safe, occupants could safely remain
seismically qualified to achieve operational perfor- in the building, although normal use may be impaircd
mance, it is recommended that the seismic qualifica- and some cleanup and inspection may be required. In
tion procedures, testing, evaluation, and documenta- general, components of mechanical and electrical sys-
tion be peer reviewed. The peer review can follow the tems in the building are structurally secured and
procedures found in Sections 9.2.8 and 9.3.7 for should be able to function if necessary utility scrvice
Design Reviews except Lhal items to be reviewed are is available. However, some components may experi-
nonstructural components and systems. ence misalignments or interna( damage and be nonop-
erable. Power, water, natural gas, communications
1.5.2.2 lmmediate Occupancy Nonstructural fines, and other utilities required for normal building
Pelformance Leve/ (N-B) use may not be available. The risk of life-threatening
Nonstructural Performance Leve( N-B, Immediate injury due lo nonstructural damage is very low.
Occupancy, shall be delined as the postearthquake
damage state in which nonstructural components are 1.5.2.3 Life Safety Nonstructural Performance
damaged bul building access and lite safety systems- Leve/ (N-C)
including doors, stairways, elevators, emergency Nonstructural Performance Level N-C, Life
llighting, fire alanns, and tire suppression systems- Safety, shall be dclincd as the postearthquake damage
generally remain available and operable, provided state in which nonstructural components are damagcd
thal power is available. but the damage is notlife-threatening.
18
ASCE/SEL41-06
ly ~ ignificant and costly damage has occurred to Safety Performance for the most-hazardous, highest-
:-tructural components but they have not b~com~ risk subset of the nonstructural components in the
lodged and fallen, threatening life safety either building.
1de or outside the building. Egress routes within the
1ld ing are not extensively blocked but may be 1.5.2.5 Nonstructural Performance Not
1paired by lightweight debris. HYAC, plumbing, ano Considered (N-E)
- e ~uppression systems may have been damaged, A building rehabilitation that does not address
~ ulting in local tlooding as well as loss of function. nonstructural components shall b~ classitied as
tho ugh injuries may occur during the earthquake Nonstructural Performance Not Considered (N-E).
m the failure of nonstructural components, overall,
risk of life-threatening injury is very low. CL.5.2.5 Nonstructural Performance Not
e:,toration of the nonstructural components m ay take Considered (N-E)
~ tensive effort. In some cases, the decision to rehabilitate the
structure may be made without addressing the vulnera-
J. -.2.4 Hazards Reduced Nonstructural Performance bilities of nonstructural components. It may be desir-
Leve/ (N-D) able todo this when rehabilitation must be perfonned
Nonstructural Performance Leve! N-D, Hazards without interruption of building operation. In some
eJuced, shall be detined as the postearthquake dam- cases, it is possible to perform all or most of the struc-
-=e state in which nonstructural components are dam- tural rehabilitation from outside occupied building
-=ed and could potentially create falling hazards, but areas. Extensive disruption of normal operation may
gh-hazard nonsu·uctural components identified in be required to perform nonstructural rehabilitation .
Chapter 11, Table 11-1, are secured to preven! fall ing Also, since many of the most severe hazards to life
nto areas of public assembly. Preservation of egress, safety occur as a result of structural vulnerabilities,
otection of tire suppression systems, and similar some municipalities may wish to adopt rehabilitation
e- ordinances that require structural rehabilitation only.
·e-safety issues are not addressed in this
_·onstructural Performance Leve!.
ve 1.5.3 Designation of Target Building Performance
Cl.5.2.4 Hazards Reduced Nonstructural Levels
Performance Leve/ (N-D) A target Building Performance Leve! shall be des-
Nonstructural Performance Leve! D, Hazards ignated alphanumerically with a numeral representing
. educed, represents a postearthquake damage state in the Structural Performance Leve! and a letter repre-
hich extensive damage has occurred to nonstructural senting the Nonstructural Performance Leve! (such as
~ mponents, but large or heavy items that pose a high 1- B or 3-C). If a Structural Performance Leve! other
)-
~ k of falling hazard toa Iarge number of people- than Immediate Occupancy (S-I), Life Safety (S-3),
uch as parapets, cladding panels, heavy plaster ceil- Collapse Prevention (S-5), or Not Considered (S-6) is
ngs, or storage racks-are prevented from falling. The selected, the numerical designation shall represen!
azards associated with exterior components along the Structural Performance Range for Damage Con-
¡- ~ rtions of the exterior of the building that are avail-
ble for public occupancy have been reduced.
u·ol (S-2) or Limited Safety (S-4).
Although isolated serious injury could occur from Cl.S.3 Designation of Target Building Performance
falling debris, failures that could injure large numbers Le veis
of persons-either inside or outside the structure- Severa! common target Building Performance
ho uld be avoided. Levels described in this Section are shown in Fig. Cl-2.
Nonstructural components that are small, light- Many combinations are possible as structural perfor-
weight, or close to the ground may fall but should not mance can be selected at any leve! in the two Struc-
cause serious injury. Larger nonstructural components tural Performance Ranges. Table Cl-8 indicates the
ge m areas that are less likely to be populated may also possible combinations of target Building Performance
d fa ll. Levels and provides names for those most likely to be
The intent of the Hazards Reduced Performance selected as the basis for design.
Leve! is to address significan! nonstructural hazards
without needing to rehabilitate all of the nonstructural 1.5.3.1 Operational Building Performance Level (1-A)
components in a building. When using this perform- To attain the Operational Building Performance
¡y. ance leve!, it will generally be appropriate to consider Leve! (l-A), the structural components of the building
Hazards Reduced Performance as equivalent to Life shall meet the requirements of Section 1.5.1.1 for the
19
SEISMIC REHABILITATION OF EXISTING BUILDINGS
T
pancy and use, although possibly in a slightly (S-1 & N-B)
that house essential services. FIGURE Cl-2. Target Building Performance Levels
and Ranges.
1.5.3.2 Immediate Occupancy Building Performance
Level (1-B)
To attain the Immediate Occupancy Building C1.5.3.2 Immediate Occupancy Building
Performance Leve) (l-B), the structural components of Performance Leve[ (1-B)
the building shall meet the requirements of Sec- Buildings meeting this target Building Performance
tion 1.5.1 . 1 for the Immediate Occupancy Structural Leve) are expected to sustain minimal or no damage to
Performance Level (S-I) and the nonstructural compo- thcir structural clcmcnts and only minor damage to their
nents of the building shall meet the requiremcnts of nonstructural components. Whilc it would be safe to
Section 1.5.2.2 for the Immediate Occupancy reoccupy a building meeting this target Building
Nonstructural Performance Leve) (N-B). Performance Leve! immediately following a major
20
ASCEISEI 41-06
~:mhquake, nonstructural systems may not function, ing from failure of nonstructural components. However,
lher because of the lack of electrical power or interna] because the building itself does not collapse, gross loss
1age to equipment. Therefore, although .immediate of life may well be avoided. Many buildings meeting
cupancy of the building is possible, it may be nec- this level will be complete economic losses.
~ to perform some cleanup and repair and await Sometimes this leve! has been selected as the basis
res toration of utility service before the building can for mandatory seismic rehabilitation ordinances enacted
nction in a normal mode. The risk to life safety at this by municipalities, as it results in mitigation of the most
get Building Performance Leve] is very low. severe lite-satety hazards at relatively low cost.
Many building owners may wish to achieve this
.:'.el of performance when the building is subjected to
erate earthquake ground motion. In addition, some 1.6 SEISMIC HAZARD
ners may desire such performance for very importan!
ildings under severe earthquake ground shaking. This Seismic hazard due to ground shaking shall be based
el provides most of the protection obtained under the on the location of the building with respect to
'(>erational Building Performance Leve! without the causative faults , the regional and site-specific geologic
~ t of providing standby utilities and perfom1ing rigor- characteristics, and a selected Earthquake Hazard
seismic qualitication of equipment performance. Level. Assessment of seismic hazard due to earlh-
quake-induced geologic site hazards shall be per-
1.5.3.3 Life Safety Building Performance Leve[ (3-C) formed in accordance with Chapter 4.
To attain the Life Safety Building Performance Seismic hazard due to ground shaking shall be
Leve! (3-C), the structural components of the building defined as acceleration response spectra or accelera-
11 meet the requirements of Section 1.5.1.3 for the tion time-histories on either a probabilistic or deter-
Life Safety Structural Performance Leve! (S-3) and the ministic basis. Acceleration response spectra shall be
veis
onstructural components shall meet the requirements developed in accordance with either the General
f Section 1.5.2.3 for the Lite Safety Nonstructural Procedure of Section 1.6.1 or the Site-Specific
Performance Level (N-C). Procedure of Section 1.6.2. Acceleration time histories
shall be developed in accordance with Section 1.6.2.2.
CJ.5.3.3 Life Safety Building Performance Leve/ (3-C) The leve! of seismicity of the si te of the building shaJJ
Buildings meeting this level may experience exten- be determined as specitied in Section J .6.3 .
mee ive damage to structural and nonstructural components. Unless otherwise approved, the site-specitic pro-
to epairs may be required before reoccupancy of the cedure shall be used where any of the following condi-
he ir bui lding occurs, and repair may be deemed economi- tions apply:
-..ally impractical. The risk to Jite safety in buildings
:neeting this target Building Performance Leve! is Jow. l . The building is Jocated on Type E soils (as detined
This target Building Performance Leve! entails in Section 1.6. 1.4) and the mapped BSE-2 spectral
~ mewhat more damage than anticipated for new response acceleration at short periods (S5) exceeds
uildings that have been properly designed and con- 2.0;
tructed for seismic resistance when subjected to their 2. The building is located on Type F soils as defined
Jesign earthquakes. Many building owners will desire in Section 1.6. J .4.
to meet this targel Building Performance Leve] for
evere ground shaking. EXCEPTION: Where S5 determined in accor-
dance with Section 1.6.1 . 1 is less than 0.20, use of a
red
1.5.3.4 Collapse Prevention Building Performance Type E soil profile shall be permiued.
Lel ef (5-E)
1
21
SEISMIC REHABILITAT!ON OF EXISTI G BUILDINGS
or other shaking-induced soil failures, landslides, and 3. Obtain design spectral response acceleration
inundation from off-site eiTects such as dam failure or parameters by adjusting thc mapped or modifled
tsunami . spectral response acceleration parameters for site
This standard requires hazards due Lo earthquake class effects, in accordance with Section 1.6. 1.4;
shaking to be de1ined on either a probabilistic ora 4. Ir the desired Earthquake Hazard Leve) is the Basic
deterministic basis. Probabilistic hazards are detined Safety Earthquake 2 (BSE-2), obtain spectral
in terms of the probability that more severe demands response acceleration parameters in accordance
will be experienced (probability of exceedance) in a with Section 1.6. 1. 1;
given period (often 50 years). Deterministic demands 5. Ir the desired Earthquake Hazarcl Leve! is the Basic
are delined within a leve! of contidence in terms of a Safety Earthquake 1 (BSE-1 ), obtain the spectral
specilic magnitude event on a particular major active response accelcration parameters in accordance
fault. with Section 1.6. 1.2; and
This standard defines two basic Earthquake 6. Using the design spectral response acceleration
Hazard Levels: Basic Safety Earthquake 1 (BSE-1) parameters that have been adjusted for site class
and Basic Safety Earthquake 2 (BSE-2). eiTects, develop the general response spectrum in
In addition Lo the BSE-1 and BSE-2 Earthquake accordance with Section 1.6. 1.5.
Hazard Levels, Rehabilitation Objectives may be
formed considering ground shaking due to Earthquake C1.6.1 General Procedure for Hazard Due to
Hazard Levels with any delined probability of Ground Shaking
exceedance, or based on any deterministic event on a This standard uses the latest national earthquake
specilic fault. hazard maps developed by the United States
Site-specilic procedures should be used where the Geological Survey (USGS) as part of a joint effort
Maximum Considered Earthquake (MCE) maps do not with the Building Seismic Safety Council, known as
adequately characterize the local hazard. Such condi- Projcct 97. National probabilistic maps were devel-
tions may exist at some near-fault locations. oped for ground motions with a 10% chance of
exceedance in 50 years, a 10% chance of exceedance
1.6.1 General Procedure for Hazard Due to Ground in 100 years (which can also be expressed as a 5%
Shaking chance of exceeclance in 50 years), and a 10% chance
The seismic hazard due to ground shaking shall of exceedance in 250 years (which also can be
be delined for any Earthquake Hazard Levelusing expressed as a 2 % chance of exceedance in 50 years).
approved spectral response acceleration contour maps These probabilities correspond to motions that are
of 5%-damped response spectrum ordinales for short- expccted Lo occur, on average, about once every 500,
period (0.2 sec) and long-period (1 sec) response. 1,000, and 2,500 years. In addition , local ground
The short-period spectral response acceleration motions in regions with well-delined earthquake
parameter, S5, and the long-period response accelera- sources, known as dcterministic motions, were used to
Lion parameter, S,, shall be determined as follows: develop MCE maps. Background information on thc
development of the MCE maps through Project 97 can
l. If the desired Earthquake Hazard Leve) corresponds be found in the 2003 NEHRP Provisions Commentary
Lo one of the mapped Earthquake Hazard Levels, (FEMA 2004).
obtain spectral response acceleration parameters The Rchabilitation Objcctive options fcaturccl in
directly from the maps. Values between contour this standard allow consiclcration of any ground
lines shall be interpolated in accordance with the motion that may be of intercst. However, for delining
procedure in Section 1.6.1.1; BSE-1 and BSE-2 Earthquake Hazard Levcls, and
2. lf the desired Earthquake Hazard Leve! does not for convenience in delining thc grouncl motion for
correspond Lo the mapped level s of hazard, then other Earthquake Hazard Levels , the 10%/50-year
obtain the spectral response acceleration parameters probabilistic maps and the MCE maps dcvcloped in
from the available maps and modify them to Lhe Project 97 are refcrenced in this standard . This collec-
desired hazard levcl , either by logarithmic interpo- tion of maps, referred toas the National Earthquake
lation or extrapo lation, in accordance with Sec- Hazards Reduction Program (NEHRP) design map set
tion 1.6. 1.3. It shall also be permitted Lo obtain the (Maps 1 through 32), is available from the FEMA
spectral response acceleration parameters by direct Di stribution Ccnter at 1-800-480-2520, online at
interpo lation of the seismic hazard curves where hllp://earthquake.usgs.gov/rcsearch/hazmaps/, or on a
available; CD-ROM from the USGS .
22
ASCE/SEI 41-06
T he MCE ground motion maps were developed This standard requires earthquake shaking
. the USGS in conjunction with the Seismic Design demands to be expressed in terms of ground motion
Procedure Group (SDPG) appointed by the Building response spectra or suites of ground motion time histo-
i:,m ic Safety Council (BSSC). The effort utilized the ries, depending on the analysis procedure selected.
est seismological information to develop design Although the maps provide a ready source for this
ponse acceleration parameters with the intent of type of information, this standard may be used with
o iding a uniform margin against collapse in all approved seismic hazard data from any sow·ce, as long
:-eas of the United States. The MCE ground motion as it is expressed as a response spectrum.
C ps are based on seismic hazard maps, which are
2%/50-year earthquake ground motion hazard 1.6.1.1 BSE-2 Spectral Response Acceleration
ps for regions of the United States that have differ- Parameters
01 ground motion attenuation relationships, and The design short-period spectral response acceler-
_ deterministic ground motion maps in regions of ation parameter, Sxs• and design spectral response
gh seismicity with the appropriate ground motion acceleration parameter ata 1-sec period, Sx 1, for the
· enuation relationships for each region. The deter- BSE-2 Earthquake Hazard Leve! shall be determined
tnis tic maps are used in regions of high seismicity using values of S5 and S1 taken from approved
here frequent large earthquakes are known lo occur, Maximum Considered Earthquake (MCE) spectral
the rare earthquake ground motions corresponding response acceleration contour maps and modified for
the 2%/50-year hazard are controlled by the large si te class in accordance with Section 1.6.1.4.
ertainties in the hazard studies, which results in Parameters S5 and S1 shall be obtained by interpo-
nu ually high ground motions . These high ground lating between the values shown on the map for the
tions were judged by the Seismic Design Procedure spectral response acceleration contour lines on either
Group (SDGP) to be inappropriate for use in design. side of the si te, or by using the value shown on the
:Oe use of these different maps to develop the MCE map for the higher contour adjacent to the site.
::taps required SDGP to define guidelines for integrat-
e ng the maps into the design ground motion maps .
C/.6.1.1 BSE-2 Spectral Response Acceleration
The most rigorous guideline developed was for
Parameters
e .:ntegrating the probabilistic and the deterministic maps.
The latest MCE contour maps are contained in
To integrate the probabilistic maps and the deterministic
Maps 1 through 24 of the NEHRP design map set.
). map, a transition zone set at 150% of the leve) of the
The BSE-2 Earthquake Hazard Leve! is consistent
1994 NEHRP Provisions was used and is extensively
with MCE in FEMA 450 (FEMA 2004). In most areas
Ji cussed in the 2003 NEHRP Provisions Comrnentary.
of the United S tates, the BSE-2 Earthquake Hazard
The goal of this guideline was to not exceed the deter-
Leve! has a 2% probability of exceedance in 50 years
mi nistic ground motion in these areas of high seismicity
(2%/50-year). In regions close to known faults with
lO here earthquake faults and maximum magnitudes are
significant slip rates and characteristic earthquakes
relatively well-detined. The remaining guidelines were
with magnitudes in excess of about 6.0, the BSE-2
·an more subjective and were related to smoothing irregular
Earthquake Hazard Leve) is limited by a deterministic
ry ·ontours, joining contours in areas where closely spaced
estímate of ground motion based on 150% of the
·ontours of equal values occuJTed (particularly in areas
median attenuation of rhe shaking likely to be experi-
n where faults are known to exist, but the hazard parame-
enced as a result of such a characteristic event. Ground
ters are not well-defined), increasing the response accel-
shaking levels determined in this manner will typically
eration parameters in small areas surrounded by higher
correspond lo a probability of exceedance greater than
parameters, and so forth .
2% in 50 years.
Based on the process used to develop the MCE
maps, there are sorne locations where the mapped
acceleration response parameters in the MCE maps 1.6.1.2 BSE-1 Spectral Response Acceleration
exceed the mapped acceleration response parameters Parameters
e-
in the 2%/50-year probabilistic maps . These locations The design short-period spectral response acceler-
¡
set occur primarily in the New Madrid , Missouri area; the ation parameter, Sxs• and design spectral response
Salt Lake City, Utah area; coastal California; and the acceleration parameter ata 1-sec period, Sx 1, for the
Seaule, Washington area. This is an intended result of BSE-1 Earthquake Hazard Leve! shall be taken as the
the process and the mapped values represent the smaller of the following:
a
appropriate values as determined by SDGP. l . The values of S5 and S 1 taken from approved
1Oo/o / 50-year spectral response acceleration
23
SEISMIC REHABILITATION OF EXISTING BUILDINGS
determined using the procedures specitied in Sec- where S;, S; 10¡50, and PR are as detined abo ve and n
tions 1.6.1.3.1 or 1.6.1.3.2. shall be obtained from Table 1-1.
Table 1-1. Values of Exponent n for Determination
1.6.1.3. 1 Probabilities of Exceedance Between 2%/50 of Response Acceleration Parameters at
Years and JO%/ 50 Years For probabilities of Earthquake Hazard Levels between 10%/50 Years
exceedance, PEr, between 2%/50 years and 10%/ and 2%/SOYears
50 years, where the mapped BSE-2 short-period spec-
tral response acceleration parameter, S5 , is less than Values of Exponent n for
1.5, the moditied mapped short-period spectral
response acceleration parameter, S5 , and modified Region
mapped spectral response acceleration parameter at a California 0.29 0.29
1-sec period, S1 , shall be determined from Eq. 1-1: Pacific Northwest 0.56 0.67
lntermountain 0.50 0.60
ln(S;) = ln(S; 10¡50 ) + {[ln(S;BsE-2) - ln(S;w¡so)) Central U.S. 0.98 1.09
Eastern U.S. 0.93 1.05
· [0.606 ln(PR) - 3.73)}
(Eq. 1-1) Sites where mapped BSE-2 values of S, 2: 1.5.
24
ASeEJSEI 41-06
Table 1-2. Values of Exponent n for Determination A 0.8 0.8 0.8 0.8 0.8
B 1.0 1.0 l. O 1.0 1.0
of Response Acceleration Parameters at
e 1.2 1.2 1.1 1.0 1.0
Probabilities of Exceedance Greater than
D 1.6 1.4 1.2 1.1 1.0
10%/50 Years 2.5 1.2 0.9 0.9
E 1.7
F * * * * *
Values of Exponent n for
*Site-specific geotechnical investigation and dynamic site response
Region Ss S, analyses shall be performed.
'Straight-line interpolation shall be used for intermediate values
California 0.44 0.44
of S,.
Pacitic Northwest
.llld Intermountain 0.54 0.59
Central and Eastern
) Table 1-5. Values ofF. as a Function of Site Class
I!.S. 0.77 0.80
and Mapped Spectral Response Acceleration at
Sik:s where mapped BSE-2 values of S, < 1.5. 1-Sec Period S 1
Table 1-3. Values of Exponent n for Determination Mapped Spectral Acceleration at Short-Period S 11
Si te
of Response Acceleration Parameters at e!ass S, ::; 0.1 S, = 0.2 S, = 0.3 S 1 = 0.4 S, ~ 0.50
Probabilities of Exceedance Greater than
10%/50 Years A 0.8 0.8 0.8 0.8 0.8
B 1.0 1.0 1.0 !.O 1.0
e 1.7 1.6 1.5 1.4 1.3
Values of Exponent n for
D 2.4 2.0 1.8 1.6 1.5
Region Ss s, E 3.5 3.2 2.8 2.4 2.4
F * * * * *
¡) California 0.44 0.44
7 Pacific Northwest 0.89 0.96 *Site-specific geotechnical investigation and dynamic site response
[) kermountain 0.54 0.59 analyses shall be performed.
!) Central U.S. 0.89 0.89 'Straight-line interpolation shall be used for intermediare values
E.astern U.S. 1.25 1.25 ofS1 •
5
Siles where mapped BSE-2 values of S5 2: 1.5.
25
SEISMIC REHABILITATION OF EXISTING BUILDINGS
1.6.1.4.1 Site Classes Site classes shall be defined as Where v, data are available for the site, such data
follows: shall be used lo classify the si te. If such data are not
available, N data shall be used for cohesionless soil
1. Class A: Hard rock with average shear wave veloc-
sites (sands, gravels), and s,. data for cohesive soil sites
ity, v; > 5,000 ft/sec;
(clays). For rock in profile Classes B and C, classilica-
2. Class B: Rock with 2,500 ft/sec < v; < 5,000 ft/sec; tion shall be based either on measured or estimated
values of V5 • Classification of a si te as Class A rock
3. Class C: Very dense soil and soft roe k with 1,200 ft/
shall be based on measurements of v, either for mate-
sec < v; :s ~500 ft/sec or with either standard
rial al the site itself or for rock having the same forma-
blow count N > 50 or undrained shear strength
tion adjacent lo the site; otherwise, Class B rock
s,;
> 2,000 psf;
shall be assumed. Class A or B profiles shall not be
4. Class D: Stiff soil_with 600 ft/sec < v; :s 1,200ft/ assumed lo be present if there is more than 1O ft of
sec or with 15 <N :5 50 or 1,000 psf :5 S,:< soil between the rock suli'ace and the base of the
2,000 psf; building.
5. Class E: Any profile with more than 10ft of soft
1.6.1.4.2 Default Site Class If there are insufticient
clay detined as soil with plasticity index PI > 20,
or water content w > 40%, and S,: < 500 psf or a data available to classify a soil protile as Class A, B,
soil profile with v; < 600 ft/sec; and or C, and there is no evidence of soft clay soils charac-
teristic of Class E in the vicinity of the si te, the default
6. Class F: Soils requiring site-specific evaluations: site class shall be taken as Class D. lf there is evidence
of Class E soils in the vicinity of the si te and no other
6.1. Soils vulnerable to potential failure or collapse
data supporting selection of Class A, B, C, or D, the
under seismic loading, such as liquefiable
default site class shall be taken as Class E.
soils, quick and highly sensitive clays, or col-
lapsible weakly cemented soils;
6.2 Peats and/or highly organic clays (H > 10 ft 1.6.1.5 General Response Spectrum
of peat and/or highly organic clay, where A general response spectrum shall be developed
H = thickness of soil); as specitied in Sections 1.6.1.5.1 through 1.6.1.5.3.
6.3 Very high plasticity clays (H > 25 ft with
PI> 75); or 1.6.1.5.1 General Horizontal Response Spectrum A
6.4 Very thick soft/medium-stitf clays (H > 120 ft). general horizontal response spectrum as shown in
Fig. 1-1 shall be developed using Eqs. 1-8, 1-9, and
The parameters v:;, N, and S,: are, respectively, the 1-1 O for spectral response acceleration, S,., versus
average values of the shear wave velocity, Standard structural period, T, in the horizontal direction.
Penetration Test (SPT) blow counl, and undrained
shear slrength of the upper 100 ft of soils al the si te.
These values shall be calculated from Eq. 1-6: S"= Sxs[(2_-
B 2) !.._ + 0.4]
T 1 5
(Eq. 1-8)
where
where T5 and T0 are given by Eqs. 1-11 and 1-12:
N;= SPT blow count in soil )ayer i;
n = number of layers of similar soil materials for T5 = Sx1/Sxs (Eq. 1-11)
which data are availab1e;
T0 = 0.2T5 (Eq. 1-12)
d; = depth of layer i;
s..; = undrained shear strength in layer í;
and where
v,; = shear wave velocity of the soil in layer i; and
n
B 1 = 4/[5.6 - In (100 /3)] (Eq. 1-13)
2: d¡ = 100ft. (Eq. l-7)
i=l and /3 is the effective viscous damping ratio.
26
ASCE/SEI 41-06
To T8
1
1.0
¡
technology or enhanced energy dissipation technol-
ogy, an equivalen! effective viscous damping ratio,
Period, T {3, shall be calculated using the procedures speci-
FIGURE 1-1. General Horizontal Response fied in Chapter 9.
Spectrum.
1.6.2 Site-Specific Procedure for Hazard Due to
Ground Shaking
e Use of spectral response accelerations calculated Where site-specific ground shaking characteriza-
using Eq. 1-8 in the extreme short-period range tion is used as the basis of rehabilitation design, the
1T < T0 ) shall only be permitted in dynamic analysis characterization shall be developed in accordance with
procedures and only for modes other than the funda- this section.
mental mode.
1.6.2.1 Site-Specific Response Spectra
/.6.1.5.2 General Vertical Response Spectrum Where a Development of site-specific response spectra
'ertical response spectrum is required, it shall be shall be based on the geologic, seismologic, and
developed by t&king two-thirds of the spectral ordi- soil characteristics associated with the specific site
oates, at each period, obtained for the horizontal and as specitied in Sections 1.6.2.1.1 through
response spectrum or by alternative rational proce- 1.6.2.1.4.
dures approved by the code otlicial. Alternatively, it
shall be permitted to develop a site-specitic vertical C1.6.2.1 Site-Specific Respome Spectra
response spectrum in accordance with Section 1.6.2. The code otlicial should consider requiring an
independent third-party review of the site-specific
C/.6.1.5.2 General Vertical Response Spectrum spectra by an individual with expertise in the evalua-
8)
Traditionally, the vertical response spectra are taken as tion of ground motion.
two-thirds of the horizontal spectra developed for the
~ite. While this is a reasonable approximation for most 1.6.2.1.1 Damping Ratios Response spectra shall be
~tes, vertical response spectra at near-field sites developed for an effective viscous damping ratio of
-9) located wilhin a few kilometers of the zone of fault 5% of critica! damping ({3 = 0.05) and for other
rupture can have stronger vertical response spectra damping ratios appropriate to the indicated structura1
lO) Iban indicated by this approximation. Development of behavior, as detined in Section 1.6.1.5.
~ite-specitic response spectra is recommended where
'ertical response must be considered for buildings on 1.6.2.1.2 Minimum Spectral Amplitude The 5%
~eh sites. damped site-specitic spectral amplitudes in the period
11)
Other methods for scaling the horizontal spectrum range of greatest significance to the structural response
12) have been proposed by Bozorgnia et al. (1996 ). Kehoe shall not be specitied less than 70% of the spectral
and Attalla (2000) present modeling considerations amplitudes of the General Response Spectrum.
lhat should be accounted for where analyzing for verti-
.:al etlects. 1.6.2.1.3 Basis ofthe Response Spectra Probabilistic
13) site-specific spectra that represen! the BSE-1 Earth-
/.6.1.5.3 Damping Ratios A 5% damped response quake Hazard Leve! shall be mean spectra at the
~ctrum shall be used for the rehabilitation design of 10%/50-year probability of exceedance. Probabilistic
27
SEISMIC REHABILITATION OF EXISTING BUILDINGS
site-specitic spectra that represent the BSE-2 Earth- Table 1-6. Level of Seismicity Definitions
quake Hazard Level shall be mean spectra at the
2%/50-year probability of exceedance. Deterministic Level of Seismicity 1 Sxs Sx,
BSE-2 site-specitic spectra shall be taken as 150% of
Low <0.167 <0.067
the median spectra for the characteristic event on the
Moderate ;;::0.167 ;;::0.067
controlling fault.
<0.500 <0.200
High ;;::Q.SOO ;;::Q.200
1.6.2. 1.4 Site-Specific BSE-2 Spectral Response 1
The higher level of seismicity defined by Sxs or Sx1 shall govern.
Acceleration Parameters The site-specific response
acceleration parameters for the BSE-2 Earthquake
Hazard Level shall be taken as the smaller of the
following: 1.6.2.2 Acceleration Time Histories
Time history analysis shall be performed with no
l. The values of the parameters from mean probabilis-
fewer than three data sets (each containing two hori-
tic site-specitic spectra at the 2%/50-year probabil-
zontal components or, if vertical motion is to be con-
ity of exceedance; or
sidered, two horizontal components and one vertical
2. The values of the parameters from 150% of median
componen!) of ground motion time histories that shall
deterministic site-specitic spectra.
be se1ected and scaled from no fewer than thrce
recorded events. Time histories shall have magnitude,
1.6.2.1.5 Site-Specific BSE-1 Spectral Response fault distances, and source mechanisms that are con-
Acceleratíon Parameters The site-specific response sistent with those that control the design earthquake
acceleration parameters for the BSE-1 Earthquake ground motion. Where three recorded ground-motion
Hazard Level shall be taken as the smaller of the time history data sets having these characteristics are
following: not available, simulated time history data sets having
equivalent duration and spectral content shall be used
l. The values of the parameters from mean probabilis-
to make up the total number required. For each data
tic site-specific spectra at the 10%/50-year proba-
set, the square root of the sum of the squares (SRSS)
bility of exceedance; or
of the 5%-damped site-specific spectra of the scaled
2. Two-thirds of the values of the parameters
horizontal components shall be constructed. The data
determined for the BSE-2 Earthquake Hazard
sets shall be scaled such that the average value of
Leve l.
the SRSS spectra does not fall below 1.3 times the
5%-damped spectrum for the design earthquake for
1.6.2. 1.6 Site-Specific Response Acceleration periods between 0.2T and 1.5T (where T is the funda-
Parameters Where a site-specific response spectrum mental period of the building).
has been developed and other sections of this standard
require the design response acceleration parameters, 1.6.3 Level of Seismicity
Sx5 , Sx 1 , and T5 they shall be obtained using the site- The level of seismicity shall be deiined as High,
spccitic response spectrum in accordance with this Moderate, or Low as delined in Table 1-6.
section. Values of the design response acceleration The values of Sxs and Sx 1 used to determine the
parameter at short periods, Sxs• shall be taken as the Level of Seismicity shall be two-thirds of the BSE-2
response acceleration obtained from the site-specific values detined in Section 1.6.1.1.
spectrum at a period of 0.2 sec, except that it shall
not be taken as less than 90% of the peak response
acceleration at any period. In order to obtain values 2.0 GENERAL REQUIREMENTS
for the design spectral response acceleration param-
eter Sx 1, a curve of the form S" = Sx 1/ T shall be 2.1 SCOPE
graphically overlaid on the site-specific spectrum
sa
such that, at any period, the value of obtained This chapter sets forth general requirements for data
ti"om the curve is not less than 90% of that which collection, analysis procedures, methods, and strate-
would be obtained directly from the spectrum. The gies for the design of seismic rehabilitation projects.
value of T5 shall be determined in accordance with Section 2.2 specifies data collection procedures
Eq. 1-11. for obtaining required as-built information on build-
28
ASCE/SEI 41-06
illgs. Section 2.3 outlines the Simplified and 4. Destructive and nondestructive examination and
Systematic Methods for seismic rehabilitation of testing of selected building materials and compo-
a.iklings. Section 2.4 specities limitations on selecting nents as specified in Section 2.2.6; and
.alysis procedures, and defines component behavior 5. Interviews with building owners, tenants, managers,
r,pes and corresponding acceptance criteria. the original architect and engineer, contractor(s),
Sa.~on 2.5 identities acceptable rehabilitation strate- and the local building ofllcial.
~- Section 2.6 contains general design requirements
The information required for an existing building
ú rehabilitation designs. Section 2.7 specifies con-
may also be available from a previously conducted
itiUCtion quality assurance requirements. Section 2.8
seismic evaluation of the building. Where seismic
specifies procedures for developing alternative model-
rehabilitation has been mandated according to building
iltg parameters and acceptance criteria.
construction classitication, familiarity with the build-
ing type and typical seismic deficiencies is recom-
mended. Such information is available from severa!
2.2 AS-BUILT INFORMATION
sources, including ASCE 31 (ASCE 2002). Such infor-
mation may be sufllcient for Simplified Rehabilitation.
lbe as-built information on building contiguration,
Additional as-built information may be needed for
building components, site and foundation, and adja-
Systematic Rehabilitation.
a:nt structures shall be obtained in accordance with
Where a destructive and nondestructive testing
Sections 2.2.1, 2.2.2, 2.2.3, and 2.2.4, respectively.
program is necessary to obtain as-built information,
This data shall be obtained from available drawings,
it is prudent to perform preliminary calculations on
specifications, and other documents for the existing
select key locations or parameters prior to establishing
ronstruction. The data collected shall be in suflicient
a detailed testing program. These obtain knowledge at
detail to permit classitication of components as pri-
a reasonable cost and with as little disruption as possi-
mary or secondary as specitied in Section 2.2.5 and
ble of construction features and materials properties at
sball comply with the data collection requirements of
concealed locations.
Section 2.2.6. Data collected from available docu-
If the building is a historie structure, it is al so
ments shall be supplemented and verified by on-site
important to identify the locations of historically signif-
illvestigations including nondestructive examination
ican! features and fabric, which should be thoroughly
aod testing of building materials and components as
investigated. Care should be taken in the design and
required in Section 2.2.6.
investigation process to minimize the impact of work
At least one site visit shall be made to observe
on these features. Refer to the Standards for the
cxposed conditions of building configuration, building
Treatment of Historie Properties with Guidelines for
.:omponents, site and foundation, and adjacent struc-
¡- Preserving, Rehabilitating, Restoring, and
wres (made accessible by the owner) to verify that
Reeonstrueting Historie Buildings (Secretary of the
as-built information obtained from other sources is
Interior 1995), as discussed in Appendix A. The ser-
representative of the existing conditions.
vices of a historie preservation expert may be necessary.
29
SEISMIC REHABILITATION OF EXISTING BUILDINGS
nonstructural components that participate in resisting of applicable existing foundation capacity or geologic
lateral loads, whether or not they were intended to do site hazard information available for the site shall be
so by the original designers. This information should permitted.
identify potential seismic deticiencies in load-resisting A site reconnaissance shall be performed to ob-
components, which may include discontinuities in the serve variations from existing building drawings,
load path, weak links, irregularities, and inadequate foundation modifications not shown on existing docu-
strength and deformation capacities. mentation, presence of adjacent development or grading
ASCE 31 (ASCE 2002) is one example of a seis- activities, and evidence of poor foundation performance.
míe evaluation too! that offers guidance on building
contiguration. C2.2.3 Site and Foundation Information
Sources of applicable existing site and foundation
2.2.2 Component Properties information include original design information, foun-
Sutlicient as-built information shall be collected dation capacity information included on the drawings,
on components of the building, including their geo- and previous geotechnical reports for the site or for
metric and material properties and their interconnec- other sites in the immediate vicinity.
tion with other components, to permit computation of Adjacent building development or grading activi-
their strengths and deformation capacities. To account ties that impose loads on or reduce the lateral support
for any uncertainty associated with componen! as-built of the structure can affect building performance in a
information, a knowledge factor, K, shall be used in future earthquake. Evidence of poor foundation per-
the capacity evaluation as specitied in Section 2.2.6.4. formance can include settlement of building tloor
slabs and foundations, or differential movement visible
C2.2.2 Component Properties at adjacent exterior sidewalks or other miscellaneous
Meaningful structural analysis of a building's site construction.
probable seismic behavior and reliable design of reha-
bilitation measures require good understanding of the 2.2.4 Adjacent Buildings
existing components (such as beams, columns, and Sufticient data shall be collected on the contigura-
diaphragms), their interconnection, and their material tion of adjacent structures to permit investigation of the
properties (mainly the mechanical properties, such as interaction issues identitied in Sections 2.2.4.1 through
strength, deformability, and toughness). The strength 2.2.4.3. If the necessary information on adjacent struc-
and deformation capacity of existing components tures is not available, the authority having jurisdiction
should be computed, as specified in Chapters 4 shall be informed of the potential consequences of the
through 9 and 11, based on derived material properties interactions that are not being evaluated.
and detailed component knowledge. Existing compo-
nen! action strengths must be determined for two basic 2.2.4.1 Building Pounding
purposes: to allow calculation of their ability to deliver Data shall be collected to permit investigation of
load to other components, and to allow determination the etl"ects of building pounding in accordance with
of their capacity to resist forces and deformations. Section 2.6.10, wherever a portion of an adjacent
structure is located within 4% of the height above
2.2.3 Site and Foundation lnformation grade at the location of potential impact.
Data on foundation contiguration and soil surface
and subsurface conditions at the site shall be obtained C2.2.4.1 Building Pounding
trom existing documentation, visual site reconnais- Building pounding can alter the basic response of
sance, or a program of site-specific subsurface investi- the building to ground motion and impart additional
gation in accordance with Chapter 4. A site-specitic inertialloads and energy to the building from the adja-
subsurface investigation shall be performed where cent structure. Of particular concern is the potential
Enhanced Rehabilitation Objectives are selected, or for extreme local damage to structural elements at the
where insutlicient data are available to quantify foun- zones of impact.
dation capacities or determine the presence of geologic
site hazards identified in Section 4.2.2. Where historie 2.2.4.2 Shared Element Condition
information indicates geologic site hazards have Data shall be collected on adjacent structures
occurred in the vicinity of the site, a site-specific sub- that share common vertical- or lateral-force-resisting
surface investigation shall be performed to investigate elements with the building to permit investigation in
the potential for geologic site hazards at the site. Use accordance with Section 2.6.9.
30
ASCE/SEI 41-06
C2.2.4.2 Shared Element Condition other hazards from adjacent structures. Where
Buildings sharing common elements, such as Immediate Occupancy of the building is desired and
party walls, ha ve severa! poten tia! problems. If the ingress to the building may be impaired by such haz-
buildings attempt to move independently, one building ards, consideration should be given to providing suit-
10ay pull the shared elemenl away from the other, ably resistant access to the building. Sufticient infor-
resulring in a partía! collapse. lf the buildings behave mation should be collected on adjacent structures to
ag as an integral unit, the additional mass and inertial allow preliminary evaluation of the likelihood and
e. loads of one structure may result in extreme demands nature of hazards such as potential falling debris, tire,
oo the lateral-force-resisting system of the other. All and blast pressures. Evaluations similar to those in
~nces of shared elements should be reported to FEMA 154 (FEMA 1988) may be adequate for this
In libe building owner and the owner should be encour- purpose.
1- ~ed to inform adjacent building owners of hazards
S, lf identitied. 2.2.5 Primary and Secondary Components
Data shall be collected to classify components
21.4.3 Hazards from Adjacent Buildings as primary or secondary in accordance with Sec-
1- Data on hazards from adjacent buildings shall be tion 2.4.4.2. Data on primary and secondary com-
1 oollected to permit consideration of their potential to ponents shall be collected in sufticient detail to
damage the subject building as a result of an earth- permit modeling and analysis of such components
quake. If there is a potential for such hazards from an in accordance with the requirements of this
adjacent building, the authority having jurisdiction standard.
~le over the subject building shall be informed of the
eftect of such hazards on achieving the selected 2.2.6 Data Collection Requirements
Rehabilitation Objective. Data on the as-built condition of the structure,
components, site, and adjacent buildings shall be col-
C2.2.4.3 Hazards from Adjacent Buildings lected in sufficient detail to perform the selected
ra- Hazards from adjacent buildings such as falling analysis procedure. The extent of data collected shall
the debris, aggressive chemical leakage, fire, or explosion be consistenl with mínimum, usual, or comprehensive
gh lhat may impact building performance or the opera- levels of knowledge as specitied in Section 2.2.6.1,
e- tion of the building after an earthquake should be 2.2.6.2, or 2.2.6.3. The required leve} of knowledge
n considered and discussed with the building owner. shall be determined considering the selected
ae Consideration should be given to hardening those por- Rehabilitation Objective and analysis procedure in
tions of the building that may be impacted by debris or accordance with Table 2-1.
Level of Knowledge
Data Minimum Usual Comprehensive
Rehabilitation
of Objective BSO or Lower BSO or Lower Enbanced Enhanced
l Analysis
Procedures LSP, LDP All All All
Jja-
Testing No Tests Usual Testing Usual Testing Comprehensive Testing
1
1he Design Drawings Design Drawings Design Drawings Construction Documents
Drawings or Equivalen! or Equi valent or Equivalent or Equivalen!
Condition
Assessment Visual Comprehensive Visual Comprehensi ve Visual Comprehensive Visual Comprehensive
From drawings From From
Material or default From default From drawings From usual From drawings From usual documents comprehensi ve
ag Propenies values values and tests tests and tests tests and tests tests
n Knowledge
Factor (K) 0.75 0.75 1.00 1.00 0.75 0.75 1.00 1.00
31
SEISMIC REHABILITATION OF EXISTING BUILDINGS
2.2.6.1 Mínimum Data Collectioll Requirements 3. In the absence of material test records and quality
As a mínimum, collection of as-built information assurance reports, material properties shall be
shall consist of the following: determined by usual materials testing in accordance
with Chapters 5 through 8;
1. Information shall be obtained from design drawings
4. Information needed on adjacent buildings, refcr-
with sutlicient information to analyze componen!
enced in Section 2.2.4, shall be gaincd through lield
demands and calculate component capacities. For
surveys and research of as-built information made
mínimum data collection, the design drawings
available by the owner of thc subject building; and
shall show, as a mínimum, the contiguration of the
5. Site and foundation information shall be collectcd
vertical- and lateral-force-resisting system and typi-
in accordance with Section 2.2.3.
cal connections with sufticient detail to carry out
linear analysis procedures. Where design drawings
2.2.6.3 Comprellensive Data Collection Requirements
are available, information shall be verified by a
Comprehensive collection of as-built information
visual condition asscssment in accordance with
shall consist of the following:
Chapters 5 through 8;
2. In the absence of sufficient information from l. lnformation shall be obtained from construction
design drawings, incomplete or nonexistent infor- documents including design drawings, specifica-
mation shall be supplemented by a comprehensive tions, material test rccords, and quality assurance
condition assessment, including destructive and reports covering original construction and subse-
nondestructive investigation in accordance with quent moditications to the structure. Where con-
Chapters 5 through 8; struction documents are available, information shall
3. In the absence of material test records and quality be veritied by a visual condition assessmcnt in
assurance reports, use of default material properties accordance with Chapters 5 through 8;
in accordance with Chapters 5 through 8 shall be 2. If construction documents are incomplete, missing
permitted; information shall be supplemented by a compre-
4. Information needed on adjacent buildings, refer- hensive condition assessment, including destructive
enced in Section 2.2.4, shall be gained through and nondestructive investigation in accordance with
field surveys and research of as-built information Chapters 5 through 8;
made available by the owner of the subject build- 3. In the absence of material test records and quality
ing; and assurance reports, material properties shall be
5. Site and foundation information shall be collected determined by comprehensive materials testing in
in accordance with Section 2.2.3. accordance with Chapters 5 through 8. The coetli-
cient of variation in material test results shall be
less than 20%;
2.2.6.2 Usual Data Collection Requirements
4. Information needed on adjacent buildings, refer-
Usual collection of as-built information shall con-
enced in Section 2.2.4, shall be gaincd through tield
sist of the following:
surveys and research of as-buill information made
l. Information shall be obtained from design drawings available by the owner of the subject building; and
with sutlicient information to analyze component 5. Site and foundation information shall be collected
demands and calculate component capacities. For in accordance with Section 2.2.3.
usual data collection, the design drawings shall
show, as a mínimum, the contiguration of the verti- C2.2.6.3 Comprelle11sive Data Collectioll
cal- and lateral-force-resisting system and typical Requireme11ts
connections with sufticient detail to carry out the Where materials testing results have a coetlicient
selected analysis procedure. Where design draw- of variation greater than 20%, additional materials
ings are available, information shall be veritied by testing can be performed until the coetlicient of varia-
a visual condition assessment in accordance with tion is less than 20% ora knowledgc factor consisten!
Chapters 5 through 8; with a lesser data collection requirement can be used.
2. In the absence of sufticient information from
design drawings, incomplete or nonexistent infor- 2.2.6.4 Knowledge Factor
mation shall be supplemented by a comprehensive
condition assessment, including destructive and 2.2.6.4.1 General To account for uncertainty in the
nondestructive investigation in accordance with collection of as-built data, a knowledge factor, K, shall
Chapters 5 through 8; be selected from Table 2-1 considering the selected
32
ASCEISEI 41-06
Rehabilitation Objective, analysis procedure, and data 2.3.1 Simplified Rehabilitation Method
collection process. Knowledge factors shall be selected The Simplified Rehabilitation Method shall be
from Table 2-1 on an individual componen! basis as permitted for buildings that conform to one of the
determined by the level of knowledge obtained for that Model Building Types contained in Chapter 10,
component during data collection. Knowledge factors Table 10-1, and all limitations in that table with re-
shall be applied to determine component capacities as gard to building size and level of seismicity.
specified in Section 2.4.4.6. Use of the Simplified Rehabilitation Method shall
be restricted to Limited Rehabilitation Objectives con-
C2.2.6.4.1 General The K factor is used to express the sisting of the Lite Satety Building Performance Leve!
contidence with which the properties of the building (3-C) at the BSE-1 Earthquake Hazard Level, or
components are known, where calculating component Partial Rehabilitation as defined in Section 1.4.3.2.
S capacities. The value of the factor is established from The Simplitied Rehabilitation Method shall be
lhe knowledge obtained based on access to original performed in accordance with the requirements of
construction documents, or condition assessments Chapters 2, 10, and 11.
including destructive or nondestructive testing of repre-
sentative components. The values of the factor have C2.3.1 Simplified Rehabilitation Method
been established, indicating whether the level of Simplified Rehabilitation may be applied to cer-
lnowledge is "mínimum," "usual," or "comprehensive." tain buildings of regular configuration that do not
require advanced analytical procedures. The primary
1.2.6.4.2 Linear Procedures Where linear procedures intent of Simplitied Rehabilitation is to reduce seismic
11
are used, data collection consisten! with the mínimum risk efticiently, where possible and appropriate, by
leve! of knowledge shall be permitted. seeking Limited Objectives. Partial Rehabilitation
measures, which target high-risk building deficiencies
1.2.6.4.3 Nonlinear Procedures Where nonlinear pro- such as parapets and other exterior falling hazards, are
...-edures are used, data collection consistent wirh either included as Simplitied Rehabilitation techniques, but
e
lhe usual or comprehensive levels of knowledge shall their use should not be limited to buildings that con-
h
be performed. form to the limitations of Table 10-1 in Chapter 10.
The Simplified Rehabilitation Method is less com-
1.2.6.4.4 Assumed Values of Knowledge Factor lt shall plicated than the complete analytical rehabilitation
be permitted to perform an analysis in advance of the design procedures found under Systematic Rehabilita-
data collection process using an assumed value of K, tion. In many cases, Simplified Rehabilitation represents
provided the value of K is substantiated by data collec- a cost-eftective improvement in seismic performance,
lion in accordance with the requirements of Sec- and it often requires less detailed evaluation or partial
lion 2.2.6 prior to implementation of the rehabilitation analysis to qualify for a specitic performance level.
suategies.
d
If the assumed value of K is not supported by sub- 2.3.2 Systematic Rehabilitation Method
~uent data collection, the analysis shall be revised to The Systematic Rehabilitation Method shall be
ioclude a revised K consisten! with the data collected permitted for all rehabilitation designs and shall be
In accordance with the requirements of Section 2.2.6. required for rehabilitations that do not satisfy the crite-
If an analysis using an assumed value of K results ria of Section 2.3.1. The Systematic Rehabilitation
in no required rehabilitation of the structure, the value Method includes the following steps:
of K shall be substantiated by data collection in accor-
l. An analysis procedure shall be selected in accor-
dance with the requirements of Section 2.2.6 before
dance with the requirements and limitations of
lhe analysis is tinalized.
Section 2.4;
2. A preliminary rehabilitation scheme shall be devel-
oped using one or more of the rehabilitation strate-
2.3 REHABILITATION METHODS gies detined in Section 2.5; and
3. An analysis of the building, including rehabilitation
Seismic rehabilitation of the building shall be per- measures, shall be performed, and the results of the
formed to achieve the selected Rehabilitation analysis shall be evaluated in accordance with the
Objective in accordance with the requirements of the requirements of Chapters 2 through 9 and 11 to
11 Simplified Rehabilitation Method of Section 2.3.1 or verify that the rehabilitation design meets the
lhe Systematic Rehabilitation Method of Section 2.3.2. selected Rehabilitation Objective.
33
SEISMIC REHABILITATION OF EXISTING BUILDINGS
C2.3.2 Systematic Rehabilitation Method given, but definitive rules for developing ground
Systematic Rehabilitation may be applied to any motion input are not included in this standard.
building and involves thorough checking of each exist- This standard specifies acceptance criteria for
ing structural component, the design of new ones, and stitTness, strength, and ductility characteristics of
verification of acceptable overall performance repre- structural components tor three discrete structural per-
sented by expected displacements and internal torces. formance levels in Chapters 4 though 8 for use in the
The Systematic Rehabilitation Method tücuses on the Systematic Rehabilitation Method, and acceptance cri-
nonlinear behavior of structural response and employs teria for the performance of nonstructural components
procedures not previously emphasized in seismic codes. in Chapter 11 for use in Systematic and Simplitied
The Systematic Rehabilitation Method is intended Rehabilitation Methods.
to be complete and contains all requirements to reach Inherent in the concept of performance levels and
any specified performance level. Systematic ranges is the assumption that performance can be
Rehabilitation is an iterative process, similar to the measured using analytical results such as story drift
design of new buildings, in which moditications of the ratios or strength and ductility demands on individual
existing structure are assumed for the purposes of a components. To enable structural veritication at the
preliminary design and analysis, and the results of the selected performance level, the stitfness, strength, and
analysis are veritied as acceptable on a componen! ductility characteristics of many common components
basis. If either new or existing components still prove have been derived from laboratory tests and analytical
to be inadequate, the modifications are adjusted and, if studies and are presented in a standard format in
necessary, a new analysis and veritication cycle is per- Chapters 4 through 8 of this standard.
formed. A preliminary design is needed to define the This standard specities two new technologies in
extent and contiguration of corrective measures in suf- Chapter 9: seismic isolation and energy dissipation,
ticient detail to estímate the interaction of the stitfness, for use in seismic rehabilitation of buildings using the
strength, and post-yield behavior of all new, moditied, Systematic Rehabilitation Method.
or existing components to be used for lateral force lt is expected that testing of existing materials and
resistance. The designer is encouraged to include all components will continue and that additional correc-
components with signiticant lateral stiffness in a math- tive measures and products will be developed. It is
ematical model to assure detormation capability under also expected that systems and products intended to
rcalistic seismic drifts. However, just as in the design modify structural response beneticially will be
of new buildings, it may be determined that certain advanced. The format of the analysis techniques and
components will not be considered part of the lateral- acceptance criteria of this standard allows rapid incor-
force-resisting system, as long as deformation compat- poration of such technology. Section 2.8 gives specific
ibility checks are made on these components to assure requirements in this regard. It is expected that this
their adequacy. standard will have a signiticant impact on testing and
A mathematical model, developed for the prelimi- documentation of existing materials and systems as
nary design, must be constructed in connection with well as on new products.
one of the analysis procedures defined in Chapter 3.
These are the linear procedures (Linear Static
2.4 ANALYSIS PROCEDURES
Procedure and Linear Dynamic Procedure, LSP and
LDP) and the nonlinear procedures (Nonlinear Static
An analysis of the building, including rehabilitation
Procedure and Nonlinear Dynamic Procedure, NSP
measures, shall be conducted to determine the forces
and NDP). With the exception of the NDP, this stan-
and deformations induced in components of the build-
dard defines the analysis and rehabilitation design pro-
ing by ground motion corresponding to the selected
cedures sutliciently that compliance can be checked by
Earthquake Hazard Leve!, or by other seismic geologic
an authority having jurisdiction in a manner similar to
site hazards specified in Section 4.2.2.
design reviews for new buildings. Modeling assump-
The analysis procedure shall comply with one of
tions to be used in various situations are given in
the following:
Chapters 4 through 9, and in Chapter 11 for nonstruc-
tural components. Requirements for seismic demand l. Linear analysis subject to limitations specitied in
are given in Chapter l. Requirements are specified for Section 2.4.1, and complying with the Linear Static
use of the NDP; however, considerable judgment is Procedure (LSP) in accordance with Section 3.3.1,
required in its application. Criteria for applying or the Linear Dynamic Procedure (LDP) in accor-
ground motion for various analysis procedures are dance with Section 3.3.2;
34
ASCE/SEI 41-06
2. Nonlinear analysis subject to limitations specified The determination of irregularity shall be based on the
in Section 2.4.2, and complying with the NSP configuration of the rehabilitated structure. A linear
in accordance with Section 3.3.3, or the NDP in analysis to determine irregularity shall be performed
accordance with Section 3.3.4; or by either an LSP in accordance with Section 3.3.1 or
3. Alternative rational analysis in accordance with an LDP in accordance with Section 3.3.2. The results
Section 2.4.3. of this analysis shall be used to identify the magnitude
and uniformity of distribution of inelastic demands on
The analysis results shall comply with the appli-
the primary elements and components of the lateral-
cable acceptance criteria selected in accordance with
force-resisting system.
Section 2.4.4.
The magnitude and distribution of inelastic
demands for existing and added primary elements and
C2.4 ANALYSIS PROCEDURES components shall be detined by DCRs and computed
in accordance with Eq. 2-1:
The linear procedures maintain the traditional use of a
linear stress-strain relationship, but incorporate adjust- DCR = Quv (Eq. 2-1)
ments to overall building deformations and material QcE
acceptance criteria to permit better consideration of
the probable nonlinear characteristics of seismic where
response. The Nonlinear Static Procedure (NSP), often Quv = force due to the gravity and earthquake loads
called "pushover analysis," uses simplified nonlinear calculated in accordance with Section 3.4.2;
techniques to estímate seismic structural deformations. and
The NDP, commonly known as nonlinear time history QcE = expected strength of the component or element,
analysis, requires considerable judgment and experi- calculated as specitied in Chapters 5 through 8.
ence to perform, as described in Commentary Section
C2.4.2.2 of this standard. DCRs shall be calculated for each action (such as
axial force, moment, or shear) of each primary compo-
2.4.1 Linear Procedures nent. The critica) action for the component shall be the
Linear procedures shall be permitted for buildings one with the largest DCR. The DCR for this action
which do not have an irregularity defined in Sec- shall be termed the critica! component DCR. The
tion 2.4.1.1. For buildings that ha ve one or more of the largest DCR for any element at a particular story is
irregularities defined in Section 2.4.1.1, linear proce- termed the critica) element DCR at that story. If an
dures shall not be used unless the earthquake demands element at a particular story is composed of multiple
on the building comply with the demand capacity ratio components, then the component with the largest com-
(DCR) requirements in Section 2.4.1.1. For buildings puted DCR shall define the critica) component for the
incorporating base isolation systems or supplemental element at that story.
energy dissipation systems, the additional limitations lf one or more component DCRs exceed 2.0 and
of Section 9.2.4 or Section 9.3.4 shall apply. any irregularity described in Section 2.4.1.1.1 through
Section 2.4.1.1.4 is present, then linear procedures are
C2.4.1 Linear Procedures not applicable and shall not be used.
The results of the linear procedures can be very
inaccurate where applied to buildings with highly C2.4.1.1 Method to Determine Limitations on Use of
irregular structural systems, unless the building is Linear Procedures
capable of responding to the design earthquake(s) The magnitude and distribution of inelastic
in a nearly elastic manner. The procedures of Sec- demands are indicated by demand-capacity ratios
tion 2.4.1.1 are intended to evaluate whether the build- (DCRs). Note that these DCRs are not used to deter-
ing is capable of nearly elastic response. mine the acceptability of component behavior. The
adequacy of structural components must be evaluated
2.4.1.1 Method to Determine Limitations on Use of using the procedures contained in Chapter 3 along
Linear Procedures with the acceptance criteria provided in Chapters 4
The methodology presented in this section shall through 8. DCRs are used only to determine a struc-
be used to determine the applicability of linear analy- ture's regularity. It should be noted that for complex
sis procedures based on four contigurations of irregu- structures, such as buildings with perforated shear
larity defined in Sections 2.4.1.1.1 through 2.4.1.1.4. walls, it may be easier to use one of the non linear
35
SEISMIC REHABILITATION OF EXISTING BUILDINGS
exist in any primary elemenl of the lateral-force-resist- FIGURE 2-1. In-Piane Discontinuity in Lateral
ing system wherever a lateral-force-resisting element System.
is present in one story, but does not continue or is off-
set within the plane of the element in the story imme-
diately below. Figure 2-1 depicts such a condition.
36
ASCE/SEI 41-06
C2.4.1.2 Limitations on Use of the Linear Static C2.4.2.1 Nonlinear Static Procedure
Procedure The NSP is generally a more reliable approach to
For buildings that ha ve irregular distributions characterizing the performance of a structure than are
of mass or stiffness, irregular geometries, or non- linear procedures. However, it is not exact and cannot
orthogonal lateral-force-resisting systems, the distribu- accurately account for changes in dynamic response as
tion of demands predicted by an LDP analysis will be the structure degrades in stiffness, nor can it account
more accurate than those predicted by the LSP. Either for higher mode etfects in multi-degree of freedom
lhe response spectrum method or time history method (MDOF) systems. Where the NSP is utilized on a
may be used for evaluation of such structures. structure that has signiticant higher mode response,
the LDP is also employed to verify the adequacy
of the design. Where this approach is taken, less-
2.4.2 Nonlinear Procedures restrictive criteria are permitted for the LDP, recogniz-
Nonlinear procedures shall be permitted for any ing the signiticantly improved knowledge that is
of the rehabilitation strategies contained in Section 2.5. obtained by performing both analysis procedures.
Nonlinear procedures shall be used for analysis of The strength ratio, R, is a measure of the extent of
buildings where linear procedures are not permitted. nonlinearity, and Rmax is a measure of the system
Data collection for use with nonlinear procedures shall degradation. Structures that experience nonlinear
be in accordance with Section 2.2.6. demands exceeding Rmax have signiticant degradation
and an NDP is required to contirm the dynamic stabil-
ity of the building.
2.4.2.1 Nonlinear Static Procedure
The NSP shall be permitted for structures with all
of the following characteristics: 2.4.2.2 Nonlinear Dynamic Procedure
l. The strength ratio, R, calculated in accordance with The NDP shall be permitted for all structures.
Eq. 3-15 in Chapter 3, is less than Rmax calculated Where the NDP procedure is used, the authority hav-
in accordance with Eq. 3-16 in Chapter 3; and ing jurisdiction shall consider the requirement of
2. Higher mode effects are not signiticant, as detined review and approval by an independent third-party
in this section. engineer with experience in seismic design and nonlin-
ear procedures.
To determine if higher modes are significan!, a
modal response spectrum analysis shall be performed
for the structure using sufficient modes to produce C2.4.2.2 Nonlinear Dynamic Procedure
90% mass participation. A second response spectrum The NDP consists of nonlinear time-history analy-
analysis shall also be performed, considering only the sis, a sophisticated approach to examining the inelastic
first mode participation. Higher mode effects shall be demands produced on a structure by a specitic suite of
considered significant if the shear in any story result- ground motion time histories. As with the NSP, the
ing from the modal analysis considering modes results of the NDP can be directly compared with test
required to obtain 90% mass participation exceeds data on the behavior of representative structural com-
130% of the corresponding story shear considering ponents in order to identify the structure's probable
only the tirst mode response. performance when subjected to a specific ground
If higher mode effects are significant, the NSP motion. Potentially, the NDP can be more accurate
shall be permitted if an LDP analysis is also per- than the NSP in that it avoids sorne of the approxima-
formed to supplement the NSP. Buildings with signiti- tions made in the more simplified analysis. Time-
cant higher mode effects must meet the acceptance History Analysis automatically accounts for higher
criteria of this standard for both analysis procedures, mode effects and shifts in inertialload patterns as
except that an increase by a factor of 1.33 shall be per- structural softening occurs. In addition, for a given
mitted in the LDP acceptance criteria for deformation- earthquake record, this approach directly solves for
controlled actions (m-factors) provided in Chapters 5 the maximum global displacement demand produced
lhrough 9. A building analyzed using the NSP, with or by the earthquake on the structure, eliminating the
without a supplementary LDP evaluation, shall meet need to estímate this demand based on general
the acceptance criteria for nonlinear procedures speci- relationships.
fied in Section 3.4.3. Despite these advantages, the NDP requires con-
If R exceeds Rmax, an NDP analysis shall be siderable judgment and experience to perform. These
performed. analyses tend to be highly sensitive to small changes
37
SEISMIC REHABILlTATlON OF EXISTlNG BUlLDINGS
in assumptions with regard to either the character of 2.4.4.2 Primary and Secondary Components
the ground motion record used in the analysis, or the Components that affect the lateral sti[fness or dis
nonlinear stitfness behavior of the elements. As an tribution of forces in a structure, or are loaded as a
example, two ground motion records enveloped by the resuIt 01' lateral deformation of the structure, shall be
same response spectrum can produce radically differ classilied as primary or secondary, even ir lhey are not
ent results with regard to the distribution and amount intended to be part of the lateral-force-resisting system.
of inelasticity predicted in the structure. In order to A structural component that is required to resist
apply this approach reliably to rehabilitation design, it seismic forces in order 1'or lhe slructure to achieve
is necessary to perl'orm a number of such analyses, the selected performance level shall be c1assified as
using varied assumptions. The sensitivity of the anal y primary.
sis resulLs lo the assumptions incorporated is the prin A slruclural componenl lhat is not required to
cipal reason why this method should be used only on resist seismic forces in order for the structure lo
projects where the engineer is thoroughly familiar with achieve the selecled performance level shall be permit
nonlinear dynamic analysis techniques and limitations. ted to be classiJied as secondary.
38
ASeE/SEI 41-06
be designated as secondary because the moment ponent actions exhibiting Type l behavior shall be
resistance is low, relative lO the entire system resis classitied as deformation-controlled for any e/ g ratio.
lance; and The Type 2 curve depíeted in Fig. 2-3 is represen
3. The secondary designation may be used where a tative of ductile behavior where there is an elastÍc
component, intended in the original design of lhe range (points O to 1 on the curve) and a plaslic range
building to be primary, is deformed beyond the (points I to 2) followed by loss of strength and loss of
point where it can be relied on to resist earthquake ability to support gravity loads beyond point 2.
effects. For example, il is conceivable thal coupling Primary and secondary component actions exhibiting
beams connecting wall piers will exhaust their this type of behavior shall be c1assiiied as deforma
deformation eapacity before the entire structural lion-controlled if the plastic range is such lhat e 2: 2g;
system capacity is reached. In such cases, the olherwise, lhey shall be classitied as force-controlIed.
engineer may designate these as secondary, allow The Type 3 curve depicled in Fig. 2-3 is represen
ing them to be deformed beyond their useful tative of a brittle or nonductile behavior where there is
Iimits, provided that damage to lhese secondary an elastic range (poinls Oto 1 on the curve) followed
components does not result in loss of gravity load by )oss of slrength and loss of abilíty lo support grav
capacity. ity loads beyond point l. Primary and secondary com
ponent actions displaying Type 3 behavior shall be
2.4.4.3 Deformatúm-Controlled and Force classitied as force-controlled.
Controlled Actions
Al! actions shalI be classified as either deforma C2.4.4.3 Deformation-Controlled and Force
tion-controlled or force-controlled using lhe compo Controlled Actions
nent force versus deformalíon curves shown in Acceptance criteria for primary components
Fig.2-3. that exhibil Type 1 behavior typically are within the
The Type 1 curve depicled in Hg. 2-3 is represen elastíe or plastic ranges betwecn points O and 2,
lalive of duclile behavior where lhere is an elaslíe depending on the performance leve!. Acceptance crite
range (points O lo 1 on the curve) foIlowed by a plaslíe ria for secondary components that exhibit Type 1
range (points 1 to 3) with non-negligible residual behavior can be within any of the performance
strength and ability to support gravity loads al point 3. ranges.
The plastic range ineludes a strain-hardening or Acceptance criteria foc primary and secondary
-softening range (points I to 2) and a strength components exhibiling Type 2 behavior will be wilhin
degraded range (points 2 to 3). Primary component lhe elastic or plaslic ranges, depending on lhe per
actions exhibiting this behavior shall be classilied as formance leve!.
deformation-controlled ir the strain-hardening or Acceptance criteria for primary and secondary
-softening range is such that e 2: 2g; otherwise, they components exhibiling Type 3 behavior will always be
shall be c1assified as force-controlled. Secondary com- within the elastic range.
Q Q Q
2 2,3
1,2,3
.....". ····················1··············..··················.............. .....................Y""'..................... ¡~ ............••••••••••••••••.•••••••••••••••••••••••••••••••
¡i
i
!
o 9 e 9 d,e 9
Type 1 curve Type 2 curve Type 3 curve
FIGURE 2-3. Component Force Versus Deformation Curves.
39
SEISMIC REHABILITATION OF EXISTING BUILDINGS
r
tive yield point B. The slope from point B to point C
is typically a small percentage (0%-10%) of the el as
tic slope, and is included to represent phenomena
such as strain hardening. Point C has an ordinate that
() A A
represents the strength 01' the component, and an 1.0 --, --,or __
By Ay h
(b) Deformation ratio
Table C2-1. Examples oC Possible Deformation
Controlled and Force-Controlled Actions
Deformation Force-Controlled 10
Component Controlled Action Action Q)
u !p.s LS
Moment Frames
L..
.Q ¡p 1s CP
• Beams Moment (M) Shear (V)
"O
Q)
¡p ls
.~ C
• CoJumns Axial load (P), V ro B
• Joints VI E
L..
o
Shear Walls M, V P Z
Braced Frames
• Braces P Deformation or deformation ratio
• Beams P
• Columns P
• Shcar Link V p,M (e) Component or element deformation
Conncctions p, V. M2 P, V. M
aeeeptanee eriteria
FIGURE C2-l. Generalized Component Force
Diaphragms M,V3 P, V. M
Deformation Relations for Depicting Modeling and
'Shear may be a deformation-controlled action in steel moment Acceptance Criteria.
frame construction.
'Axial, shear, and moment may be deformation-controlled actions
for cel1ain steel and wood connections.
31f the diaphragm canies lateral loads from vel1ical seismic resisting
elcments above the diaphragm level, then M and V shall be consid
ered forcc-controlled actions.
40
ASeE/SEI41-06
abscissa value equal to the deformation al which sig well as differences in workmanship and physical con
nificant strength degradatíon begins (Iine CD). Beyond dition. See Chapters 5 through 8 for specific direction
point D, the component responds with substantially regarding the calculation of expected and lower-bound
reduced strength to point E. At deformalÍons greater strengths of components.
Iban point E, the component strength is essentially
zero. 2.4.4.5 Material Properties
The sharp transition as shown on idealized curves Expected material properties shall be based on
in Fíg. C2-1 belween poinls C and D can result in mean values of tested material properties. Lower
compulational difficulty and an inability lo converge bound material properties shall be based on mean val
where used as modeling input in nonlinear computer ues 01' tested material properties minus one standard
¡zed analysis software. In order lo avoid Ihis computa deviation (a").
Iional instabilily, a small slope (10 vertical to 1 hori Nominal material properties, or properties speci
zontal) may be provided to the segment of these fied in construction documents, shall be taken as
curves belween points C and D. lower-bound material properties unless otherwise
For sorne components il is convenienl to prescribe specitied in Chapters 5 through 8. Corresponding
acceptance criteria in lenns of defonnation (such as O expected material properlies shall be calculated by
or á), while for olhers it is more convenient lo give multiplying lower-bound values by appropriate factors
enreria in lerms of deformation ratios. To accommo specified in Chapters 5 Ihrough 8 to translale from
date this, two types of idealized force versus deforma lower-bound lo expected values.
IÍOn curves are used in Figs. C2-1 (a) and (b). Fig
ure C2-J(a) shows normalized force (Q/Qy) versus C2.4.4.5 Material Properties
defonnation (O or á) and the parameters a, b, and c. Where calcuJations are used lO detennine
Figure C2-I(b) shows normalized force (Q/Qy) versus expected or lower-bound strengths 01' components,
defonnation ratio (O/O" .1/.1y> or .1/n) and the param expected or lower-bound material properties, respec
crers d, e, and c. Elastic stiffnesses and values ror the tively, shall be used.
parameters a, b, e, d, and e Ihat can be used for model
íng componenls are given in Chapters 5 tbrough 8. 2.4.4.6 Component Capacities
Acceptance criteria for deformation or deformation
l3lÍos for primary components (P) and secondary com 2.4.4.6.1 General Detailed criteria for calculation of
ponents (S) corresponding lo the target Building individual component force and deformation capacities
Performance Levels 01' Collapse Prevention (CP), Life shall comply with the requiremenls in individual mate
Safety (LS), and Immediate Occupancy (10) as shown rials chapters as follows:
ín Fig. C2-1(c) are given in Chapters 5 through 8.
J. Foundations--Chapter 4;
2. Components composed of steel or cast iron
24.4.4 Expected and Lower-Bound Strength
Chapter 5;
In Fig. 2-3, Qy represents the yield strength 01' Ihe
3. Components composed of reinforced concrete
component. Where evaluating the behavior 01' defor
Chapter 6;
IDalion-controlled aClions, the expected strength, QCE,
4. Componenls composed of reinforced or unrein
sball be used. QCE is defined as the mean value of
forced masonry-Chapter 7;
resistance 01' a component at the defonnation level
5. Components composed of timber, light metal studs,
auticipated for a population of simílar components,
gypsum, or plaster products--Chapter 8;
including consideration of the variability in material
6. Seismic isolation systems and energy dissipation
strength as welIs as strain hardening and plastic sec
systems--Chapter 9; and
Iion development. Where evaluating the behavior of
7. Nonstructural (architectural, mechanical, and elec
rorce-controlled actions, a lower-bound estimate of the
Irical) componenls--Chapter 11.
component strenglh, QCL> shall be used. QCL is defined
as the mean minus one standard deviation of tbe yield Elements and components composed of combina
sarengthS' Qy , for a populatíon of similar components. tions of materials are covered in the chapters associ
ated with each material.
0.4.4.4 Expected and Lower-Bound Strength
In Fig. 2-3, the strength of a component is 2.4.4.6.2 Linear Procedures If linear procedures are
affected by inherenl variability of the strength of the used, capacities for deformation-controlled actions
materials comprising the individual components as shall be defined as the product of m-factors and
41
SEiSMIC REHABILlTATlON OF EXISTING BlIlLDlNGS
42
ASeE/SEI41-06
~onnecLivity, componenL strength, component defor continuities may be inappropriate in the case of
mation capacity, or aH three. This strategy tends to historic buildings, and the effect of such alterations
be the most economical rehabilitation approach on important historic features should be considered
\lihere only a few of the building's components are carefully.
inadequate. Effective corrective measures for removal or
Local strenglhening allows one or more under reduction of irregularities, such as soft or weak stofies,
Slrength components or connections to resist the incJude the addition of braced frames or shear walls
Slrength demands predicted by the analysis without within the soft or weak story. Torsional ilTegularities
affecting the overaJl response of the structure. This can be corrected by the addition of moment frames,
.:ould indude measures such as cover plating steel braced frames, or shear walls to balance the distribu
beams or columns, or adding wood structural panel tion of stiffness and mas s within a story. Discontin
~athing to an existing timber diaphragm. Such meas uous components such as columns or walls can be
ures increase the strength of the component and allow extended through the zone of discontinuity.
il to resist more earthquake-induced force before the Partial demolition can also be an effective correc
onset of damage. tive measure for irregularities, although this obviously
Local corrective measures that improve the defor has signiticant impact on the appearance and utility of
mation capacily or ductility of a component allow it to the building, and this may not be an appropriate alter
resist large deformation levels with reduced amounts native for historic structures. Portions of the structure
of damage, without necessarily increasing the strength. mat create the irregularity, such as setback towers or
One such measure is placement of a continement side wings, can be removed. Expansion joints can be
JaCket around a reinforced concrete column to improve created to transform a single irregular building into
i.ts ability to deform without spaJling or degrading multiple regular structures; however, care must be
reinforcement splices. Another measure is reduction of taken to avoid the potential problems associated with
Ihe cross section of selected structural components to pounding.
merease their tlexibility and response displacement Global Structural Stiffening. Global stiffening
.:apaciLy. of the structure may be an effective rehabilitation strat
Removal or Reduction of Existing egy if the results of a seismic evaluation show deti
Irregularities. Removal or reduction of existing irreg ciencies attributable to excessive lateral detlection of
lLIarities may be an effective rehabilitation strategy if a the building and critical components do not have ade
~ismic evaluation shows that the irregularities result quate ductility to resist the resulting deformations.
m me inability of the building to meet the selected Construction of new braced frames or shear walls
Structural Performance Leve!. within an existing structure are effective measures for
The results of analysis should be reviewed to adding stiffness.
Jetect existing irregularities. Stiffness, mass, and Global Structural Strengtbening. Global
strength irregularities may be detected by reviewing strengthening of the structure may be an effective
me results of a linear analysis, by examining the distri rehabilitation strategy if the results of a seismic evalu
bulion of structural displacements and DCRs, or by ation show unacceptable performance attributable to a
reviewing the results of a nonlinear analysis by exam global deficiency in structural strength. This can be
ining the distribution of structural displacements and identified where the onset of global inelastic behavior
ioelastic deformation demands. If the distribution of occurs at levels of ground shaking that are substan
\alues of structural displacements, DCRs, or inelastic tially less than the selected level of ground shaking, or
.kforrnation demands predicted by the analysis is large DCRs (or inelastic deformation demands) are
lIOIluniform with disproportionately high values within present throughout the structure. By providing supple
ooe slOry relative to the adjacent story, or at one side mental strength to such a lateral-force-resisting sys
of a building relative to the other, then an irregularity tem, it is possible to raise the threshold of ground
aists. motion at which the onset of damage occurs. Shear
Such irregularities are often, but not always, walls and braced frames are effective elements for this
caused by the presence of a discontinuity in the struc purpose, but they may be significantly stiffer than the
rore, such as termination of a perimeter shear wall structure to which they are added, requiring them to
aboye the first story. Simple removal of the irregularity provide nearly all of the structure's lateral resistance.
may be sufticient to reduce demands predicted by the Moment-resisting frames, being more flexible, may
aoalysis to acceptable levels. However, removal of dis be more compatible with existing elements in sorne
43
SEISMIC REHABILITATION OF EXISTING BUILDlNGS
struclUres; however, such flexible elemenls may not in an overall reduction in lhe displacements 01' the
become eftective in the building's response unlil exist structure. The most commonly used deviees dissipale
ing brinle elements have already becn damaged. energy through t'rictional, hyslerelic, or viscoelaslic
Mass Reduction. Mass reduction may be an processes. In order lo dissipate substantial cnergy, dis
effective rehabilitation stralegy if the resulls of a seis sipation dcvices typically must undergo significam
mic evaluation show deficiencies aUribulable lo exces deformation (or stroke), which requires Lhat the sLruc
sive building mass, global structural tlexibility, or ture experience substantiallateral displacements.
global structural weakness. Mass and slifIness control Therefore, these systems are mosl etl'ective in struc
the amount of force and deformation induced in a tures that are relatively flexible and have sorne ine/as
struclure by ground mOlion. Reduclions in mass can tic deformation capacity. Energy dissipaters are most
result in direct reductions in both the amounl of force commonly installed in structures as components 01'
and the deformalion demand produced by earthquakes braced rrames. Depending on the characleristics 01' the
and, therefore, can be used in lieu of structural device, either static or dynamic stitTncss is added to
strengthening and stiftening. Mass can be reduced the structure as well as energy dissipation capacity
Ihrough demolition of upper stories, replacement of (damping). In sorne cases, although the structural dis
heavy e1adding and interior partitions, or removal 01' placemems are reduced, the forces delivcred to the
hcavy storage and equipment 10ads. structure can aetually be increased.
Seismic Isolation. Seismic isolation may be an
effeetive rehabililation strategy if the results 01' a seis
mie evalualÍon show deticiencics altributable to exces 2.6 GENERAL DESIGN REQUlREMENTS
sive seismic forces or deformation demands, or if it is
desired to protect important contents and nonstructural The requirements of this section shall apply lo all
components from damage. Where a structure is seismi buildings for which the Syslematic Rehabilítation
cally isolated, compliant bearings are inserted belween Method is selected ror any target Building
the superstructure and its foundalions. This produces a Performance Level and any seleclcd Earlhquake
systcm (structure and isolation bearings) with a nearly Hazard Level unless specitied otherwise.
rigid body translation of the strueture aboye (he bear
ings. Most 01' the deformation induced in the isolated 2.6.1 Multidirectional Seismic Effects
system by (he ground motion occurs within the com Componems shall be designed lo resist seismic
plianl bearings, which are specificalIy designed to forces acting in any horizontal direclion. Seismic
resist these concentrated displacements. MOSl bearings forces in lhe vertical direetion shaIl be considered
also have excellent energy dissipation characteristics where required by Section 2.6.1 l. Multidirectional
(damping). Together, Ihis results in greally reduced seismic etreets shall be considered in the analysis as
demands on the existing struclural and nonstructural specitied in Section 3.2.7.
components of the building and its contents. For Ihis
reason, seismic isolation is often an appropriate strat 2.6.2 p-~ Effects
egy lo achieve Enhanced Rehabilitation Objeclives Components 01' buildings shall be designed for
that inelude the proteclion of historic fabric, valuable P-á etl'ects, detined as the combined effects 01' gravity
contents, and equipment, or for buildings that comain loads acting in conjunction with lateral drifls due lo
important operations and funetions. This technique is seismic forees, as specitied in Seclion 3.2.5.
most eftective for relatively stiff buíldings with low
profiles and large mass. It ís less effective for Iight, 2.6.3 Horizontal Torsion
flexible struclures. Components 01' buildings shall be desígned Lo
Supplemental Energy Dissipation. Installation resíst the effects of horizontal torsion as specitied in
01' supplememal energy dissipation devices may be an Section 3.2.2.2.
effective rehabilitation strategy íf the results 01' a seis
mie evaluation show deticiencies attributable lo exces 2.6.4 Overturning
sive deformations due to global struclUral tlexibility in Components 01' buildings shall be designed 10
a building. Many available technologies allow (he resíst the etIects of ovenurning at each intermediale
energy imparted to a structure by ground motion to be level as well as the base 01' Ihe slruclUre. Stabiljty
dissipaled in a comrolled manner through Ihe action 01' agaínst overlUrning shall be evaluated as specil1ed in
special devices-tluid viscous dampers (hydraulic Section 3.2.10. Eft'ects of overturning on foundations
cylinders), yielding plates, or friction pads-resulting shall be evaluated as specified in SectÍon 4.4.
44
ASeE/SEI 41-06
45
SEISMIC REHABILlTATION OF EXISTING BUILDINGS
Where diaphragms of timber, gypsum, or metal force-controIled. Nonstructural walls shall be evalu
deck construction provide lateral support 1'or walls ated using the provisions of Chapter 11.
01' masonry or concrete construction, ties shall be
designed for the wall anchorage torces specified in 2.6.7.1 Out-of-Plane Anchorage to Diaphragms
Section 2.6.7 for the area of wall tributary to the Walls shall be positively anchored lo all
diaphragm tie. diaphragms Ihat provide lateral support for the wall or
are verticalIy supported by the wall. Walls shall be
C2.6.6 Diapbragms anchored to diaphragms al horizontal dislances nol
The concept of a diaphragm chord, consisting 01' exceeding 8 ft, unless il can be demonslrated thal
an edge member provided to resist diaphragm flexural lhe wall has adequate capacily lo span horizonlally
stresses Ihrough direct axial tension or compression, is belween the supports for grealer dislances. Anchorage
no! familiar 10 many engineers. Buildings wilh solid 01' walls lo diaphragms shaIl be designed for forces
struclural walls on all sides often do not require calculated using Eq. 2-5, which shaJl be developed
diaphragm chords. However, buildings with highly in Ihe diaphragm. lf sub-diaphragms are used, each
perforaled perimeler walls do require these compo sub-diaphragm shall be capable of lransmitting (he
nents for proper diaphragm behavior. This section 01' shear forces due lo wall anchorage lo a conlinuous
Ihis standard requires that these components be pro diaphragm tie. Sub-diaphragms shall have lenglh-to
vided where appropriale. deplh ralios noL exceeding 3: l. Where wall panel s are
A common problem in buildings Ihal nominally stiffened for out-of-plane behavior by pilasters or sim
have robust lateral-iorce-resisting systems is a lack 01' ilar componenls, anchors shall be provided al each
adequate aUachment belween the diaphragms and the such component and the dislribution of oUl-of-plane
vertical elemenls of the laleral-force-resisling lo e1'fect forces lo wall anchors and diaphragm Lies shall con
shear transfer. This is particularly a problem in build sider Lhe stit1'ening effecl and accumulaLion 01' forces
ings Ihat have discrete shear walls or frames as their at these componenLs.
vertical lateral-torce-resisting elements. This seclion
provides a reminder that it is necessary lo delaíl a for (Eq.2-5)
mal system of force delivery from (he diaphragm to where
the walls and frames.
Díaphragms Ihal supporl heavy perimeler walls PI' = design force ror anchorage of walls lO
have occasionally 1'aíled due lo tension induced by diaphragms;
OUI-of-plane forces generated in Ihe walls. This section X = factor fmm Table 2-4 for Ihe selecLed Structural
is intended 10 ensure thal sufficienl tensile líes are pro Performance Leve!. Increased values of X shall
vided across diaphragms lo prevent such failures. The be used where anchoring lo flexible diaphragms;
design torce for Ihese tensile ties, taken as OASxs times Sxs = spectral response acceleratioll parameter aL short
the weight, is an extension of provisions contained in periods for the selecled hazard level and damp
Ihe 1994 Uniform Building eode (ICBO 1994). In Ihat ing, adjusled for site class; and
code, parts and porlions of structures are designed for W = weight of lhe wall Iribulary to the anchor.
a force calculated as eJz limes lhe weight 01' lhe
component, wilh typical values of Cp being 0.75 and Z
being the etTeclive peak ground acceleralion ror which
Ihe building is designed. The 1994 Unifonn Building
Code provisions use an allowable stress basis. This Table 2-4. Coefficient X Cor CaIculation oC Out-oC
standard uses a slrenglh basis. Therefore, a factor of Plane Wall Forces
1.4 was applied to Ihe el' value, and a factor 01' 1/(2.5)
was applied to adjust the Z value lo an equivalenl Sxs Slructural Flexible Other
value, resulting in a coefticienl 01' 0.4. Performance Level Diaphragms Diaphragms
Collapse
2.6.7 Walls Prevention 0.9 0.3
Walls shall be evaluated for oUI-of-plane inertial Life Safety 1.2 0.4
forces as required by this section and as fm1her Immediate
Occupancy 1.8 0.6
required tor specitic struclUral systems in Chapters 5
Ihrough 8. Actions that result 1'rom application of the IYalue of X for tlexible diaphragms need not be applied to out-or
forces specified in Ihis section shall be considered plane strength of walls in Section 2.6.7.2.
46
ASCElSEI41-06
47
SEISMIC REHABILlTATlON OF EXISTING BUILDlNGS
height by less than 50% of the heighl of lhe shorler 2.7 CONSTRUCTION QUALITY
building, need nol meet lhe minimum separation dis ASSURANCE
tance specified in Seclion 2.6.10.1.
Where an approved analysis procedure lhal Conslruction of seismic rehabilitalion work shall be
accounts for the change in dynamic response of lhe checked for quality of conslruction and general com
structures due lo impacl is used, the rehabílitated pliance wilh lhe intent of lhe plans and specificalions
buildings need not meel the mínimum separation dis of the rehabililalion designo Construction quality
lance specified in Section 2.6.10.1. Such an analysis assurance shal1 conform to lhe requiremenls of this
shall demonslrate that section and the additional testing and inspeclion
requiremenls 01' lhe building code and reference stan
l. The structures are capable of transferring forces
dards of Chaplers 5 through 1 l.
resulling from impacl, for diaphragms located al
the same elevation; or
2. The slructures are capable of resisting aH required
vel1ical and lateral forces considering the loss of C2.7 CONSTRUCTION QUALITY
any elements or components damaged by impact ASSURANCE
of lhe structures.
The design pro1'essional responsible for lhe seismic
rehabilitalion of a specific building may tind il appro
C2.6.10.2 Exceptions
priate to specify more stringent or more detailed
This standard permits rehabilitated buildings to
requirements. Such addilional requirements may be
experience pounding as long as lhe effects are ade
particularly appropriate for those buildings having
quately considered by analysis methods thal accounl
Enhanced Rehabilitation Objectives.
for the transfer of momenlum and energy between lhe
slructures as they impact.
Approximale methods of accounting for these 2.7.1 Construction Quality Assurance Plan
effects can be obtained by performing nonlinear time A Quality Assurance Plan (QAP) shal1 be pre
history analyses of both structures (Johnson 1992). pared by lhe design professional and approved by
Approximate elastic methods for evaluating these the authorily having jurisdiction. The QAP shall
effecls have also been developed and are presented in idenlify componenls of the work that are suhjecI to
lhe Iiterature (Kasai 1990). quality assurance procedures and idenlify special
Buildings that are likely lo experience signiticant inspection, testing, and observation requirements lo
pounding should not be considered capable of meeling confirm conslruction qualily. The QAP shall also
Enhanced Rehabilitation Objectíves. This is because inelude a process for modifying lhe rehabilitation
sígniticanl local crushíng of components is Iikely to design lo rellect unforeseen conditions discovered
occur at poinls of ímpacl. Furthermore, the very nature during construclion.
01' the impact is such that hígh-frequency shocks can
be lransmitted through lhe slructures and potenlially
C2.7.1 Construction Quality Assurance Plan
be very damaging to architectural componenls and
The qualily assurance plan (QAP) should, as a
mechanical and electrical systems. Such damage is
mínimum, inelude Ihe following:
not consistent wíth the performance expected of
buíldings designed lo Enhanced Rehabílitalion l. Required conlraclor qualíty control procedures;
Objectives. and
2. Required design professional conslruclion qualily
assurance services, inc1uding bUI nOllimited 10 lhe
2.6.11 Vertical Seismic Effects
following:
The etl"ects of lhe vertical response of a struclure
2.1 Review of required contractor submittals;
lo earlhquake ground mOlion shall be consídered for
2.2 Moniloring of required inspection reports and
lhe foHowing cases:
test resuIts;
l. Cantilever componenls of slructures; 2.3 Construction consuJtation as required by the
2. Preslressed components of slructures; and contractor on the intenl of lhe conslruclion
3. Structural components in which demands due lo documents; and
gravity loads specitied in Seclion 3.2.8 exceed 80% 2.4 Construclíon ohservation in accordance wilh
01' lhe nominal capacity of the component. Section 2.7.2.1.
48
AseE/SEI 41-06
2.7.2 Construction Quality Assurance 2. Olher work designated for such testing by the
llequirements design professional or the authority having
jurisdiction.
1.7.2.1 Requiremellts lor the Desigll Prolessiollal
The design professional shall be responsible 1'or 2.7.2.4 Reporting and Compliance Procedures
preparing the QAP applicable to the portion of the The special inspector shall furnish copies of
",'ork for which they are in responsible charge, over progress reports to the owner's representative and the
seeing the implementation 01' the plan, and reviewing design professional, noting any uncorrected deticien
~ial inspection and testing reports, cies and corrections of previously reported deticien
The design pro1'essional shall be responsible for cies. Al! observed deticiencies shalt be brought to the
pt!rforming periodic structural observation 01' the reha immediate attention of the contractor for correction.
bilitation work. Structural observation shall be per Upon completion of construction, the special
iormed at signiticant stages of construction, and shall inspector shall submit a tinal report to the owner's rep
ioclude visual observation of the work for substantial resentative and the design professional, indicating the
..-onformance with the construction documents and extent to which inspected work was completed in
..-ontirmation of conditions assumed during design, accordance with approved construction documents.
Slructural observation shall be performed in addition Noncompliant work shall have been corrected prior to
10 any special inspection and testing that is otherwise complelion of construction.
required for the work.
The design professional shall be responsible for C2.7.2 Construction Quality Assurance
modifying the rehabilitation design to retlect condi Requirements
oons discovered during construction. The special inspector should be a qualified person
who should demonstrate competence, to the satisfac
e2.7.2.1 Requiremellts lor the Desigll Prolessional tion of the authority having jurisdiction, for inspection
Following structural observations, the design pro of the particular type of construction or operation
iessional should report any observed deticiencies in requiring special inspection.
tIITiling to the owner's representative, the special
inspector, the contractor, and the code ofticial. Upon 2.7.3 Responsibilities oC the Authority Having
oompletion of the work, the design professional should Jurisdiction
submit to the authority having jurisdiction a written The authority having jurisdiction shall be respon
ilatement auesting that the site visits have been made, sible for reviewing and approving the QAP and speci
md identifying any reported deticiencies that, to the fying minimum special inspection, testing, and report
ba!sl of the structural construction observer's knowl ing requirements.
cdge, have not been resolved or rectified.
C2.7.3 Responsibilities oC the Authority Having
27.2.2 Speciallnspection Jurisdiction
The owner shall engage the services of a special The authority having jurisdiction should act to
inspector to observe construction of the following enhance and encourage the protection of the public
rehabilitation work: that is represented by such rehabilitation. These
actions should inelude those described in the following
1. Items designaled in Section A.9.3.3 of Appendix A
subsections.
of ASCE 7 (ASCE 2(05); and
., Other work designated for such special inspection
C2.7.3.1 Construction Document Submittals
by the design professional or the authority having
Permittillg
jurisdiction.
As part of the permitting process, the authorily
having jurisdiction should require lhat construction
27.2.3 Testing
documents be submitted for a permit to construct the
The special inspector shall be responsible for veri
proposed seismic rehabilitation measures. The docu
fying that special test requirements, as described in the
ments should inelude a statement of the design basis
QAP, are performed by an approved testing agency for
for the rehabilitation, drawings (or adequately detailed
die following rehabilitation work:
sketches), structural/seismic calculations, and a QAP
1. Work described in Section A.9.3.4 of Appendix A as recommended by Section 2.7.1. Appropriate struc
of ASCE 7 (ASCE 2(05); tural construction specifications are also recommended
49
SEISMIC REHABILITATION OF EXISTING BUILDINGS
if structural requirements are not adequately defined permitted to derive the required parameters and
by notes on drawings. acceptance criteria using the expcrimental1y obtained
The authority having jurisdiclion should require cyclic response characteristics 01' lhe subassembly,
that it be demonstrated (in lhe design caIculations, by delermined in accordance wilh this section. Approved
third-party review, or by other means) that the design independent review 01' Ihis process shall be conducled.
of lhe seismic rchabilitation measures has been per
formed in conformance with local building regula 2.8.1 Experimental Setup
tions, the stated design basis, lhe intenl oí' lhis stan Where relevant data on the ínelastic force
dard, and/or accepted engineering principIes. The deformatíon behavior ror a structural subassembly are
authority having jurisdiction should be aware that nol available, such data shall be obtained from experi
compliance with the building code provisions for new ments consisting of physical tests of representativc
structures is oflen not possible and is not required by subassemblies as spccified in lhis section. Each sub
this slandard. 11 is not ¡ntended that the authority hav assembly shall be an identifiable portion of the struc
ing jurisdiction assure compliance of lhe submittals tural elemen! or component, lhe sliffness 01' which is
with the structural requirements ror new construclion. required to be modeled as part of the structural analy
The authority having jurisdiction should maintain sis process. The objeclíve of the experiment shall be to
a permanenl public file 01' the construclion documents estimale lhe lateral-force-displacement relalionshíps
submiued as part of the permitting process for con (stitTness) rol' the subassemblies at dilIerent loading
struction 01' lhe seismic rehabililalion measures. increments, logether wíth the strength and deformation
capacitíes for the desíred Structural Performance
C2.7.3.2 Constructioll Phase Role Levels. These properties shall be used in developing
The authority having jurisdiction should monitor an analytical model of lhe slructure to calculute its
lhe implementation of the QAP. In particular, the fol response to earthquake ground shaking and other
lowing actions should be taken: hazards, and in developing acceptance criteria fOl'
strength and deformalions. The limiting strength and
]. Files of inspection reports should be maintained for
deformation capacities shall be determined from the
a defined length of time following completion of
experimental program using lhe average values of a
construction and issuance oí' a certificale of occu
mínimum of three tesIs performed for the same design
pancy. These files should inelude bolh reports sub
configuration and test conditions.
miiled by special inspectors employed by the
The experimental setup shall replicale the con
owner, as in Section 2.7.2.2, and those submiHed
struction details, support and boundary conditíons, and
by inspectors employed by I.he aUlhorily having
loading condilions expected in the building. The load
jurisdiction;
ing shall consist of fully reversed cyelic loading at
2. Prior lo issuance 01' a certificale of occupancy, the
increasing displacement levels with the number of
authority having jurisdiction should ascertain thal
cycles and displacement levels based on expected
either all reported noncomplianl aspects of con
response of the structure 10 the design earlhquake.
Slruclion have been rectitied, or such noncompliant
Increments shall be continued until the subassembly
aspects have been accepted by lhe design pro1'es
exhibits complete failure, characterized by the loss of
sional in responsible charge as acceplable substi
lateral- and vertical-load resistance.
tutes lhat are consistent with lhe general intent of
lhe conslruclion documenls; and
3. Files of test reporls prepared in accordance with 2.8.2 Data Reduction and Reporting
Seclion 2.7.2.4 should be maintained for a defined A report shall be prepared for each experiment.
length of time following completion of construclion The repon shall inelude lhe following:
and issuance of a certiticate of occupancy. l. Description of Ihe subassembly being tested.
2. Description 01' the experimental setup, ineludíng:
2.1. Details on fabrication of the subassembly;
2.8 ALTERNATIVE MODELING PARAMETERS 2.2. Location and date of tesling;
AND ACCEPTANCE CRITERIA 2.3. Descriplion 01' instrumentation employed;
2.4. Name of the pcrson in responsible charge of
For elements, components, systems, and materials for the test; and
which structural modeling parameters and acceptance 2.5. Pholographs of the specimen, laken prior to
criteria are not provided in this standard, it shaJl be testing.
50
ASeE/SEI 41-06
3. Description of lhe loading prolocol employed, negalive) of the similar segments in Ihe muItílinear
including: curves for the various experiments. Each segmenl
3.1. Increment of loading (or deformalion) applied; on the composile curve shall termínate at the aver
3.2. Rate ol' loadíng applicalion; and age ol' the deformation levels at which the similar
3.3. Duratíon of loadíng al each stage. segments of the multilinear curves l'or the various
4. Description (including photographic documenta experiments terminate.
tíon) and Iimiting deformalion value for aIl impor 3. The stifl'ness of the subassembly for use in linear
lant behavior states observed during Ihe test, procedures shall be taken as the slope of lhe firsl
incJuding Ihe following, as applicable: segment 01' the composite curve. The composite
4.1. Elastic range with effeclive stifl'ness reporled; muhilinear force-deformation curve shall be used
4.2. Plastic range; l'or modeling in non linear procedures.
4.3. Onset ol' visible damage; 4. For the purpose of determining acceptance criteria,
4.4. Loss of lateral-force-resisting capacity; subassembly actions shaJl be cIassified as being
4.5. Loss of vertical-force-resisting capacity; either force-controlled or defoffilalÍon-controlled.
4.6. Force-deformation plOI for the subassembly Subassembly actions shall be cIassified as force
(noting the various behavior states); and controlled unless any of the following apply:
4.7. Description of Iimiting behavior states defined 4.1. The full backbone curve, incJuding strength
as the onset ol' specific damage mode, change degradation and residual strength, is modeled;
in sliffness or behavior (such as inilialion of the composite multilinear force-deformation
cracking or yielding), and failure modes. curve l'or lhe subassembly, determíned in accor
dance wilh requiremenls in paragraph 2 aboye,
conforms to eilher Type l or Type 2, as indi
2.8.3 Design Parameters and Acceptance Criteria
cated in Fig. 2-3; and lhe deformation parameter
The folIowing procedure shall be followed lo
d is at least twice the deformation parameler g.
develop structural modeling paramelers and accepl
4.2. Bilinear modeling is performed in accordance
ance criteria for subassemblies based on experimental
with the simplitied NSP procedure of Sec
data:
tion 3.3.3.2.2; the composite muJtilinear
l. An idealized lateral-force-del'ormation pushover force-deformation curve for the subassembly,
curve shaIl be developed l'rom the experimental determined in accordance with requirements in
data l'or each experiment and for each direction of paragraph 2 aboye, conl'orms to either Type I
loading with unique behavior. The curve shall be or Type 2, as indicated in Fig. 2-3; and the
plotted in a single quadranl (posilive force versus deformation parameter e is at least twice the
positive deformalion, or negative force versus nega deformatíon parameter g.
tive deformation). The curve shall be constructed as 4.3. Secondary componenls in which the composite
follows: multilinear force-deformation curve for the
1.1. The appropriate quadrant of data shall be subassembly, determined in accordance with
laken from lhe laleral-force-deformation plot requirements in paragraph 2 abo ve, conforms
trom lhe experimental report. to Type 1, as indicated in Fig. 2-3.
1.2. A smooth "backbone" curve shall be drawn 5. The strength capacity, QC/" for force-conlrolled
through the intersection of the tirst cycle curve aclions evaluated using either the linear or nonlin
for the ¡-th deformation step with the second ear procedures shall be laken as the mean minus
cycle curve of the (i - 1)th deformation step, one standard deviation strenglh Qy determíned from
for all i steps, as indicated in Fig. 2-4. the series ol' representative subassembly tests.
1.3. The backbone curve so deríved shall be approx 6. The acceptance criteria for deformation-controlled
imated by a series of linear segmenls, drawn to aclíons used in nonlínear procedures shall be the
form a mullisegmented curve conforming to deformations corresponding with Ihe following
one of the types indicated ín Fig. 2-3. poínts on the curves ol' Fig. 2-3:
2. The multilinear curves derived tor all experiments 6.1. Immediate Occupancy
involving the subassembly shalJ be compared and 6. 1.1. The deformation al which permanent,
an average multilinear representation 01' Ihe sub visible damage occurred in Ihe experi
assembly behavior shall be derived based on these ments but nol greater than 0.67 times
curves. Each segment of the composite curve shall the deformation Iimil for Life Safety
be assigned lhe average stiffness (either positive or specit1ed in 6.2.1.
51
SEISMIC REHABILlTATION OF EXISTING BUILDINGS
~ Backbone curve
..
Test Defonnati on
52
ASeE/SEI 41-06
The approach laken in this section is similar lo may be useful as a performance measure for sub
Ihat used lo derive the basic design parameters and assemblies representing components in structures sub
acceptance criteria contained in Ihis standard for ject to impulsive motion.
various components, except that no original experi
mentation was performed. The required story-force C2.S.2 Data Reduction and Reporting
deformalion curves were derived by this standard's It is important tha! data from experimental pro
developers, either direclly from research testing avail grams be reported in a uniform manner so lhat the
able in the literature or based on the judgment of performance of different subassemblies may be com
engineers knowledgeable about the behavior of the pared. The data reporting requirements specified are
particular materials and systems. the mínimum thought to be adequate to allow develop
ment of lhe required design parameters and acceptance
C2.S.l Experimental Setup criteria for (he various Systematic Rehabilitation
This standard requires performing a minimum of Procedures. Sorne engineers and researchers may
lhree separate tests of each unique subassembly. This desire additional dala from the experimentation pro
is because there can be considerable variation in the gram to allow calibration of Iheir analytical models
results of testing performed on "identical" specimens, and lo permit improved understanding of the probable
just as there is inherent variability in the behavior of behavior of the subassemblies in the real slruclure.
actual components in buildings. The use of multiple
test data allows sorne of the uncertainty with regard C2.8.3 Design Parameters and Acceptance Criteria
lo aClual behavior to be defined. A multislep procedure for developing design
A specific testing protocol has not been recom parameters and acceptance crileria for use with both
mended, as selection of a suitable protocol is depen Ihe linear and nonlinear procedures is provided. The
dent on the anticipated failure mode of the subassem basic approach consists of lhe developmenl of an
bly as well as the character of excitation it is expected approximate story lateral-force-deformation curve for
lo experience in the real structure. In one widely used Ihe subassembly, based on the experimental data.
protocol, the Applied Technology Council's Guidelines In developing the representalive story lateral-force
lor Seismic Testing 01 Components 01 Steel Structures deformalion curve from the experimentation, use of the
(ATC 1992), the specimen is subjected to a series of "backbone" curve ís required. This takes into account,
quasi-static, fully reversed cyelic displacements thal in an approximate rnanner, Ihe strength and stiffness
are incremented from displacement levels correspon deterioration commonly experienced by struclural com
ding lo elastic behavior, lo lhose al which failure of ponents. The backbone curve is defined by points given
the specimen occurs. Other protocols that enlail fewer by the imersection of an unloading branch and lhe
or more cycles of displacemenl, and more rapid load loading curve of lhe nexl load cycle that gocs lo a
ing rates, have also been employed. In selecting an higher level of displacernem, as illuslrated in Fig. 2-4.
appropriate test protocol, it is important that sufficient
íncrements of loading be selected 10 characterize
adequately the force-deformation behavior of the sub 3.0 ANALYSIS PROCEDURES
assembly throughoul its expected range of perform
ance. In addition, the total energy díssipaled by the 3.1 SCOPE
test specimen should be similar lo thal which the sub
assembly is anticipaled lo experience in the real slruc This chapter sets forth requirements for analysis of
ture. TeSIS should aJways proceed lo a failure slale, so buildings using the Systematic Rehabilitalíon Melhod.
thal the margin against failure of the subassembly in Section 3.2 specifies general analysis requirements for
service can be judged. the mathematical modeling of buildings incIudíng basic
If the struclure is Iikely lo be subjected lo strong assumplions, consideratÍon of torsion, diaphragm flexi
impulsive ground motions, such as those that are com bilily, P-A effecls, soil-struclure interaction (S SI), mul
monly experienced wilhin a few kilomelers of lhe faull tidirectional effects, and overturning. Section 3.3
ruplure, consideration should be given to using a pro defines four analysis procedures ineluded in this stan
locol lhat includes one or more very Jarge displace dard. Section 3.4 defines component acceptance crileria.
ments at the initiation of the loading, lo simulale the Analysis of buildings with seismic isolalion or
large inilial response induced by impulsive mOlion. energy dissipation syslems shall comply with the
Alternatively, a single monotonic loading to failure requirements of Chapler 9. Analysis of buildings using
53
SEISMIC REHABlLlTATION OF EXISTING BUlLDlNGS
the Simplitied Rehabilitation Method shall comply Dynamic Procedure (LDP), the Nonlinear Static
with the requirements of Chapter 10. Procedure (NSP), or lhe Nonlinear Dynamic
Procedure (NDP), selcclcd bascd on the Jimitations
specitied in Section 2.4. Use 01' alternatíve rational
C3.1 SCOPE analysis procedures as described in Scction 2.4.3 shall
also be permiued.
The relationship 01' the analysis procedures described
in this chapter with specifications in other chaplers of C3.2.1 Analysis Procedure Selection
this standard is as follows. Four procedures are presented for seismic analysis
of buíldings: two linear procedures and two nonlínear
• Informalion on Rehabilitation Objectives, including
procedures. The lwo linear procedures are termed the
Earthquake Hazard Levels and target Building
Linear Static Procedure (LSP) and the Linear Dynamic
Performance Levels, is provided in Chapter l.
Procedure (LDP). The two non linear procedures are
o The provisions sel forth in this chapter are intended
termed the Nonlinear Static Procedure (NSP) and the
for Syslematic Rehabilitation. Provisions for
Nonlinear Dynamic Procedure (NDP).
Simplified Rehabilitation are presented in
Either the linear procedures 01' Sections 3.3.1 and
Chapter 10.
3.3.2 or the nonlinear procedures of Sections 3.3.3 and
o Guidelines for selecting an appropriate analysis pro
3.3.4 may be used to analyze a building, subject to the
cedure are provided in Chapter 2. Chapler 3
Iimitations set forlh in Seclion 2.4.
describes the loading requirements, mathematical
Linear procedures are appropriate where lhe
model, and detailed analytical procedures required
expected level 01' nonlinearity is low. This ís measured
to estimate seismic force and deformation demands
by component demand capacily ratios (DCRs) 01' less
on componenls 01' a building. Information on the
than 2.0.
ca1culation of appropriate stiffness and strength
Static procedures are appropriate where higher
characteristics for components is provided in
~ode effects are not signiticant. This is generally lrue
Chapters 4 through 9.
for short, regular buildings. Dynamic procedures are
o Geneml design requírements are specitied in Sec
required 1'or taH buildings and 1'or buildings with tor
tion 2.6 for multídirectional excitatíon effects, P-.o.
sional irregularities or nonorthogonal systems.
etlects, horizontal torsion, overturning, continuity of
The NSP is acceptable for most buildings, but
lhe framing system, diaphragms. walls, nonstructural
should be used in conjunction Wilh [he LDP if mass
components, building separation, structures sharing
participation in the tirst mode is low.
common components, and vertical seismic effects.
The term "linear" in linear analysis procedures
o Component strength and deformation demands
ímplies "linearly elastíc." The analysis procedure,
obtained fmm analysis using procedures described
however, may inelude geometric nonlinearity of grav
in this chapter, based on component acceptance cri
íty loads acting through lateral displacements and
teria outlined in this chapter, are compared with per
implicit material nonlinearity 01' concrete and masonry
missible values provided in Chapters 4 thmugh 9 for
components using properties of cracked sections. The
the desired performance leve!.
term "nonlinear" in nonlinear analysís procedures
o Design methods for walls subjected to out-of-plane
implies explicit materíal nonlinearíty or inelastic mate
seismic forces are addressed in Chapter 2. Analysis
rial response, hut geometric nonlinearíty may also be
and design methods for nonstructural components
included.
(incJuding mechanical and electrical equipment) are
presenled in Chapter 11.
3.2.2 Mathematical Modeling
54
ASCFJSEI 41-06
horizontal torsion effects are accounted for as spec by the eccenlricity between the cenler of mass and
itied in Section 3.2.2.2; or the cenler of rigidity measured perpendicular lo lhe
.. The building has flexible diaphragms as defined in direction of the applied load. The center oí" mas s
Section 3.2.4. shall be based on all t100rs above the story under
consideration. The cenler of rigidity of a story shall
If two-dimensional models are used, (he Ihree
include all vertical seismic e\ements in the story;
dimensional nature of components and elements shall
and
be considered when calculating slitIness and strength
2. The accidental torsional moment at a story shall be
properties.
calculated as the seismic story shear torce multi
lf the building contains out-of-plane offsets in
plied by a dislance equal lo 5% of the horizontal
\erticallateral-torce-resisting elements, [he model
dimension at the given tloor level measured perpen
Soball explicitly account for such offsets in the determi
dicular to the direction of the applied load.
nation of diaphragm demands.
Modeling stiffness of structural components shall
3.2.2.2.2 Considerarion ofTorsional Effects Effects of
be based on the stiffness requirements of Chapters 4
horizontal torsion shall be considered in accordance
through 8.
with lhe following requirements:
For nonlinear procedures, a connection shall be
&:!xplidtly modeled i1' the connecLÍon is weaker than or 1. Increased torces and displacements due to actual
has less ductility than the connected components or if torsion shall be calculated for aJl buíldings;
die tlexibility of the conncetion results in a change in 2. The displacement multiplier, 'TI, at each tloor shall
die connection forces or deformations of more than be calculaled as the ratio of the maximum displace
109ó. ment at any point on the tloor diaphragm to the
average displacemenl (omtJX!oavg)' Displacements
C3.2.2.1 Basic AssumpliollS shaIl be calculated tor the applied loads;
For two-dimensional models, the three 3. Increased torces and dísplacements due to acciden
dimensional natUfe of components and elements tal torsion shall be considered unless the accidental
should be recognized in calculating their stiffness and torsíonal moment is less than 25% of the actual tor
srrength properties. For example, shear walls and other sional moment, or the displacement multiplier 'TI
bracing systems may have "L" or "T" or other three due to the applied load and accidental torsion is
dimensional eros s scetions where contribulÍons of both less than 1.1 at every tloor;
die tlanges and webs should be accounted for in calcu 4. For linear analysis procedures, forces and displace
laIing stiffness and strength properties. ments due to accidental torsion shall be amplified
In this standard, component still"ness is generally by a factor, Ax. as detined by Eq. 3-1, where ¡he
taken as the effective stiffness based on the secan! displacement multíplier 'TI due lo total torsional
Sliffness to yield level forces. Specific direction on cal moment exceeds 1.2 at any level;
culating effective stiffness is provided in each material
(~)2:s
chapter for each type of structural system.
3.0 (Eq.3-1)
Examples of where connection tlexibility may be 1.2
important 10 model inelude the panel zone of s!eel
momenl-resisting frames and the "joint" region of per 5. If the displacement moditier 'TI due to total torsional
forated masonry or concrete walls. moment at any tloor exceeds 1.5, two-dimensional
models shall not be permiued and three
3.2.2.2 Horizontal Torsion dimensional models that account for the spatial
The effects of horizontal torsion shall be consid distribuLÍon of mass and stiffness shall be used;
ered in accordance with this section. Torsion need not 6. Where two-dimensional models are used, the effects
be considered in buildings with tlexible diaphragms as of horizontal torsion shall be calculated as follows:
defined in Scetion 3.2.4. 6.1. For lhe LSP and lhe LDP, force s and displacc
ments shall be amplified by the maximum
3.2.2.2.1 Total Torsional Mament The total horizontal
value of 'TI calculated for lhe building;
loesional momen! at a story shall be equal to the sum
6.2. For the NSP. the target displacement shall be
of the actual torsional moment and the accidental tor
amplified by lhe maximum value of 'TI calcu
sional moment ca\culated as follows:
lated for lhe building;
1. The actual torsional moment at a slory shall be cal 6.3. For the NDP, the amplitude of the ground
culated by multiplying the seismic story shear force acceleration record shall be amplified by the
55
SEISMIC REHABILITATION OF EXISTING BUILDINGS
maximum value of 1] calculaled for lhe build Components shall nol be selectively designated
ing; and primary or secondary lo change the configuration 01' a
7. The effects 01' accidental torsion shalJ not be used building from irregular lo regular.
lo reduce force and defonnalion demands on
components. C3.2.2.3 Primary and Secondary Components
Due to limilalions inhercnt in eaeh analysis
C3.2.2.2 Horizontal Torsion melhod, the manner in whieh primary and secondary
Actual torsion is due to lhe eccentrícily between components are handled dilTers ror linear and nonlin
the cenlers 01' mass and stíffness. Accidenlal torsion is ear procedures. Since strength and stiffness degrada
inlended lO cover the elTects of the rotational compo lion 01' secondary componcnts is Iikely, thcir resistance
ncnt of the ground motion, differences between is unreliable. Linear procedurcs cannot aeeount rol'
computed and actual stilTness, and unfavorable distri this degradation, so only primary componenls are
butions 01' dead and Iive load mas ses. inc\uded in linear analysis models. This is conservative
The 10% threshold on additional displacement in linear analyses beeause it will result in Ihe highesl
due to accidentallorsion is based on judgment. The demands placed on the primary components that
intent is lO reward lhose building frames Ihat are tor remain. Seeondary components, however, musl still be
sionally redundant and possess high torsional stiffness. cheeked against lhe aeceptance eritcria given in
Such structures are Iikely to be much less susceptible Chapters 5 lhrough 8.
to lorsional response than those framing systems In nonlinear procedures, strength and stifl'ness
possessing )ow redundancy and low IOrsional degradation can be modeled. Sinee degradation of the
stiffness. overall system can increase disp)aeemenl demands,
inc\usion of bOlh primary and secondary components
3.2.2.3 Primary and Secondary Components is eonservative in nonlinear analyses.
Components shall be classitied as primary or sec For linear procedures, this standard limits Ihe
ondary as detined in Section 2.4.4.2. Primary compo amount of lateral resislance that can be provided by
nents shall be evalualed for earlhquake-induced forces secondary components. The main l'eason for this limi
and deformalÍons in combination with gravity load talÍon is to minimize the potential ror sudden loss 01'
effecls. Secondary componenls shall be evaluated for lateral-force-resisling components to produce irregular
earlhquake-induced deformations in combination with structural response that is difticull to deteel. The con
gravity load effects. tribution 01' seeondary eomponents can be cheeked by
Mathematical models for use with linear analysis temporarily including them in the analysis model and
procedures shall inelude lhe stiffness and resistance of examining the change in response.
only the primary components. If Ihe total lateral stitT
ness of secondary components in a building exceeds 3.2.2.4 Stiffness and Strength AssumptiollS
25% 01' the tolal ¡nitial stiffness of primary compo Stiffness and strength propcrlies of componenls
nents, sorne secondary components shall be reclassified shall be determined in accordance with Ihe require
as primary lo reduce the lotal sliffness of secondary ments of Chapters 4 through 9, and JI.
componenls lo less lhan 25% 01' primary. If lhe inclu
sion of a secondary component will increase lhe force 3.2.2.5 Foundation Modeling
or deformalion demands on a primary component, lhe The foundation system shall be modeled eonsider
seeondary component shall be reclassified as primary ing lhe degree of fixity provided at the base 01' Ihe
and inc1uded in Ihe model. strueture. Rigid or flexible base assumptions shall be
Mathemalical models for use wilh non linear pro permiued in aceordanee with lhe requirements ror
cedures shall include lhe stiffness and resislance of soil-structure interaction in Section 3.2.6 and founda
primary and seeondary components. The strength and tion aceeptability in Seetion 4.4.3. Foundation model
stitl'ness degradation oí' primary and seeondary com ing shall consider movement due lo geo)ogie site
ponenls shall be modeled explicitly. For the simplitied hazards speciticd in Section 4.2.2, and load-dcformation
NSP of Seetion 3.3.3.2.2, only primary eomponents characteristics specitied in Section 4.4.2.
shall be inc\uded in the model and degradation shall
not be modeled. C3.2.2.5 Foundation Modeling
Nonstructural eomponents shall be c1assified as Mcthods for modeling foundations and eSlimation
structural eomponents and shall be included in malhe of ground movemenls due lo seismie geologic sile
matical models i1' their lalera) sLÍtJness exceeds 10% of hazards are referenced in Chapler 4, and may require
the tolal inítial lateral stitTness of a story. the expertise 01' a geotechnieal engineer or a gcologist.
56
ASeE/S El 41-06
The decision to model foundation f1exibility must consistent with the distribution of mass, and aIl in
consider impacts on the behavior of structural compo plane lateral forces associated with offsets in the verti
nents in the building. Rigid base models for concrete cal seismic framing at that diaphragm leve\.
shear walls on independent spread footings may maxi
mize deformation demands on the walls themselves, 3.2.4.3 Mathematical Modeling
but could underestimate the demands on other second Mathematical modeling of buildings with rigid
ary components in the building, such as beams and diaphragms shall account for the effects of horizontal
columns in moment frames, which may be sensitive to torsion as specified in Section 3.2.2.2. Mathematical
additional building movement. models of buildings with stiff or flexible diaphragms
shall account for the effects of diaphragm flexibility
3.2.3 Configuration by modeling the diaphragm as an element with in
Building irregularities defined in Section 2.4.1.1 plane stiffness consistent with the structural character
shall be based on the plan and vertical configuration of istics of the diaphragm system. Alternatively, for
me rehabilitated structure. Irregularity shall be deter buildings with flexible diaphragms at each f100r level,
mined, both with and withoul Ihe contribution of sec each lateral-force-resisting element in a vertical plane
ondary components. shaIl be permitted lo be designed independentIy, with
seismic mas ses assigned on the basis of tributary area.
C3.2.3 Configuration
One objective of seismic rehabilitation should be C3.2.4 Diaphragms
me improvement of the regularity of a building through Evaluation of diaphragm demands should be based
me judicious placement of new framing elements. on the Iikely distribution of horizontal inertial forces.
Adding seismic framing elements at certain loca For flexible diaphragms, such a distribution may be
tions will improve the regularity of the building and given by Eq. C3-1 and is iIIustrated in Fig. C3-1.
should be considered as a mean s to improve seismic
performance of the building.
(Eq. C3-1)
Secondary components can lose significant
strength and stiffness after initial earthquake shaking
and may no longer be effective. Therefore, regularity where
of the building should be determined both with and Id = inertial load per foot;
without the contribution of secondary components. FJ = total inertial load on a flexible diaphragm;
x = distance from the center line of flexible
3.2.4 Diaphragms diaphragm; and
LJ = distance between lateral support points for
3.2.4.1 General diaphragm.
Diaphragms shall be classified as flexible, stiff, or
rigid in accordance with Section 3.2.4.2.
Applied force
The in-plane deflection of the diaphragm shall be cal FIGURE C3-1. Plausible Force Distribution in a
..:ulated for an in-plane distribution of lateral force Flexible Diaphragm.
57
SEISMIC REHABILITATION OF EXISTING BUILDINGS
58
ASCFlSEl 41-06
Combination of damping effects with kincmatic for NDP. Other combinalÍon rules shall be perrnit
intcraction effects calculated in accordance with ted whcre verified by experiment or analysis.
Section 4.5.1 shall be permitted.
3.2.7.2 Vertical Seismic Effects
3.2.7 Multidirectional Seismic EtTects For components in whieh Seetion 2.6.11 requires
Buildings shall be dcsigned for seismic motion in consideration 01' vertical seismic effeets, the vertical
any horizontal direction. Multidirectional seismic response of a structure to earthquake ground motion
effects shall be considered to act concurrently as spec need not be combined with the effects 01' the horizon
ified in Section 3.2.7.1 for buildings meeting the fol tal response.
lowing criteria:
3.2.8 Component Gravity Loads for Load
l. The building has plan irregularities as defined in
Combinations
Section 2.4.1.1; or
The following actions due to gravity loads, Qc,
2. The building has one or more primary columns
shall be considered for combination with actions due
which form a part of two or more intersecting
lo seismic loads.
frame or braced frame elements.
Where the effects or aetions 01' gravíty and seismic
AH other buildings shall be permiued to be loads are additive, the action due to design gravity
designed for seismic motions acting nonconcurrently loads, QG, shall be obtained in accordance with Eq. 3-2:
in the direction of each principal axis of the building.
(Eq.3-2)
3.2.7.1 Concurrent Seismic Effects
where
Where concurrent mullidirectional seismic effects
must be considered, horizontally oriented, orthogonal Qv = aclion due to design dead loads;
x- and y-axes shalJ be established. Components of QL = action due to design live load, equal to 25% 01'
the building shall be designed tor combinations of lhe unreduced design live load, but not less than
forees and deformalions from separate analyses per the actual live load; and
forrned for ground motions in X and Y direetions as Qs = action due to effective snow load contribution.
follows:
Where the effects or actions ol' gravity and seis
1. Where the LSP or LDP is used as the basis for mic loads are counteracting, the aclÍon due to design
design, elements' and components shall be designed gravity loads, Qc, shall be obtained in accordance with
for (a) forees and deformations associated with Eq.3-3:
IOD% of the design forees in lhe X direction plus
the forces and deforrnations associated with 30% (Eq.3-3)
of the design forees in the Y direction; and for
(b) forees and deformations associated with 100% where
of the design forces in the Y direction plus the QD = aclion due to design dead loads.
forces and deformations assocÍated wilh 30% of the
design forees in the X direclion. Other eombination Where the design flat 0001' snow load calculated
rules shall be perrniued where verified by experi in accordance with ASCE 7 (ASCE 2005) exceeds
ment or analysis; and 30 psl', the el'fective snow load shall be taken as 20%
2. Where lhe NSP or NDP is used as lhe basis for 01' the design snow load. Where the design flat roof
design, eJemenls and components of lhe building snow load is less than 30 psl', the effective snow load
shall be designed for (a) forees and deformations shall be perrnitted to be zero.
associated with 100% of the design displacemenl in
lhe X direetion only, plus the forees (nol deforma C3.2.8 Component Gravity Loads ror Load
tions) associated wíth 30% of the design displace Combinations
menls in the Y direetion only; and for (b) forces Evaluation 01' components for gravity and wind
and deformations associated with 100% of the forces, in the absence of earthquake forces, is beyond
design displacements in the Y direction only, plus the scope 01' this document.
the forces (not deforrnations) associated with 30%
of the design displaeemcnls in lhe X direction only. 3.2.9 Verification of Design Assumptions
Design displaeements shall be determined in accor Eaeh component shall be evaluated to verify that
dance with Section 3.3.3 for NSP and Seelion 3.3.4 locations 01' inelastic deforrnations assumed in the
59
SEISMIC REHABILITATION OF EXISTING BUILDINGS
analysis are consistent with strength and equilibrium concrete walls, the overturning etl'ects are resolved
requirements along the component length. Each com into component forces (e.g., flexure and shear at the
ponent shall also be evaluated for postearthquake base of the wall). The element is then proportioned
residual gravity load capacity by a rational analysis with adequate strength using m-factors, where appro
procedure approved by the authority having jurisdic priate, to resist overturning etTects resulting from these
tion that accounts for potential redistribution of gravity force levels.
loads and reduction of strength or stiffness caused by Some elements, such as wood shear walls and
earthquake damage to the structure. foundations, may not be designed with positive attach
ment between levels. An overturning stability check is
C3.2.9 Veritication of Design Assumptions typically performed for such elements when designed
It is important that assumptions about locations of using codes for new buildings. If the element has sutli
potential inelastic activity in lhe structure are verified. cient dead load to remain stable under the overturning
In linear procedures, the potential for inelastic flexural effects of lhe design lateral forces and has sufticient
action is restricted to the beam ends because flexural shear connection to the level below, then the design is
yielding along the span length can lead to unconserva deemed adequate. However, if dead load is inadequate
tive results. In nonlinear procedures, potential inelastic to provide stability, then tie-downs, piles, or other
activity should occur only where specitically modeled. types of uplift anchors are provided to resist the resid
Where demands due to gravity load combinations of ual overturning caused by the design forces.
Section 3.2.8 exceed 50% of the capacity of the com In the linear and nonlinear procedures of this stan
ponent at any location along its length, the potential dard, lateral force s are not reduced by an R-factor, as
for inelastic activity exists and should be investigated. they are for new buildings, so computed overturning
Sample procedures for verifying design assumptions etfects are larger than typically calculated for new
are contained in Section C3.2.9 of FEMA 274 (FEMA buildings. Although the procedure used for new build
1997). ings is not completely rational, it has resulted in
successful performance. Therefore, it may not be
3.2.100verturning appropriate to require that structures and elements
Structures shall be designed to resist overturning of structures remain stable for the pseudo-lateral
effects caused by seismic forces. Each vertical-force forces used in the linear procedures in this standard.
resisting element receiving earthquake forces due to Instead, the designer must determine if positive direct
overturning shall be investigated for the cumulative attachment will be used to resist overturning etl'ects
effects of seismic forces applied at and aboye the level or if dead loads will be used. If positive direct attach
under consideration. The effects of overturning shall ment will be used, then the overturning effect at this
be evaluated at each level of the structure as specitied attachment is treated just as any other component
in SeclÍon 3.2.10.1 for linear procedures, or Section action.
3.2.10.2 for nonlinear procedures. The effects of over However, if dead loads alone are used to resist
turning on foundations and geotechnical components overturning, then overturning is treated as a force
shall be considered in the evaluation of foundation controlled behavior. The real overturning demands can
slrength and stiffness as specified in Chapter 4. be estimated by considering the overalllimiting
strength of the component.
C3.2.10 Overturning There is no simple rational method available,
Response to earthquake ground motion results in shown to be consistent with observed behavior, to
a tendency for structures and individual vertical ele design or evaluate elements for overturning etl'ects.
ments of structures to overlurn about their bases. The method described in this standard is rational but
Although actual overturning failure is very rare, over inconsistent with procedures used for new buildings.
turning etTects can result in significant stresses, as To improve damage control, the full lateral forces used
demonstrated in some local and global failures. In new in the linear procedures of this slandard are required
building design, earthquake etTects, including over for checking acceptability for performance levels
turning, are evaluated for lateral forces that are signiti higher than life safety.
cantly reduced (by an R-factor) from those that may Additional studies are needed on the parameters
actual1y develop in the structure. that control overlurning in seismic rehabilitation.
For elements with positive attachment between Information regarding consideration of rocking behav
levels that behave as single units, such as reinforced ior can be found in Commentary Section C4.4.2.
60
ASeE/SEI 41-06
The quanlity Mar/(e1ezJ) need not exceed Ihe 3.3 ANALYSIS PROCEDURES
o\'erturning moment on the element, as Iimited by the
I!xpected strength of the slruclUre. The element shall Selection of an appropriate analysis proeedure shaJl
bI! evaluated for the effects of increased compression comply with Seclion 3.2.\.
.... Ihe end about which it is being overturned. For this
purpose, compression at Ihe end of the element shall 3.3.1 Linear Static Procedure
bI! considered a force-controlled aClion.
Alternalively, Ihe load combínation represented 3.3.1.1 Basis ofthe Procedure
by Eq. 3-5 shall be permitted for evaluating the ade lf the LSP is seleeted for seismic analysis of lhe
quacy of dead loads alone lo resisl the etfeets of over building, lhe design seismic forces, lheir distribulÍon
rurning. over lhe height of the building, and the corresponding
internal torces and system displacements shall be
(Eq.3-5) determined using a linearly elastic, static analysis in
aecocdance with this sectÍon.
where
Buildings shalI be modeled with linearly elastic
Rar = 10.0 for Collapse Prevention; stiffness and equivalent viscous damping values eon
= 8.0 for Life Satety; and sistent with components respondíng at or near yield
= 4.0 for Immediate Oeeupaney. level, as detlned in SeeÜon 2.4.4. The pseudo-lateral
torce defined in Seetion 3.3.1.3 shall be used lo calcu
Where Eq. 3-4 or 3-5 for dead load stability late internal forces and system displacements due to
against the eftects of overlurning is not satistied, posi lhe design earlhquake.
uve attaehment between elements 01' the struclure at Results of the LSP shall be cheeked using the
and immediately aboye and below lhe level under con aceeplance criteria of Seclion 3.4.2.
iÍderalion shall be provided. If lhe level under consid
eralion is the base of the structure, posilive attachment C3.3.J.1 Basis ofthe Procedure
shall be provided between Ihe structure and Ihe sup The magnitude of the pseudo-lateral force has
porting soil, unless non linear procedures are used lo been selected wilh lhe intention thal, when applied lo
61
SEISMIC REHABILlTATlON OF EXISTING BUILDlNGS
the linearly elastic model of the building, it will result 0.020 for wood buildings (Types l and 2 in
in design displacemenl amplitudes approximating Table 10-2, Chapter 10);
maximum displacements expected during the design = 0.020 for all other framing systems;
earthquake. The procedure is keyed to the displace h n heighl (in ft) aboye the base lo Ihe roor leve!;
ment response of lhe building because displacemenrs and
are a belter indicator of damage in the non linear range {3 = 0.80 1'or sleel moment-resisting frame
of building response than are t'orces. In this range, rel systems;
atively small changes in force demand correspond LO = 0.90 for concrete moment-resisting frame
large changes in displacement demando lf the building systems;
responds essenLially elastically to the design earlh 0.75 ror al! other framing systems.
quake, the calculated interna! ¡'orces will be reasonable
approximations of those expecLed during the design
earthquake. If the building responds inelastically lO the 33.1.2.3 Method 3-Approximate
design earthquake, as commonly will be the case, the l. For any building, use of Rayleigh's method to
actual internal t'orces that would develop in lhe build approximate the fundamental period shall be per
ing will be less than the internal forces calculated mitted.
using a pseudo-lateral force. 2. For one-story buildings wilh single-span flexible
Calculated internal t'orces lypically will exceed
I
diaphragms, use of Eq. 3-7 lo approximate lhe fun
those rhat the building can develop because of damental period shall be permilted.
anlicípated inelastic response of componenlS. These
design forces are evaluated lhrough the acceptance
T = (0.16." + 0.0786.,jl.5 (Eg.3-7)
criteria of Section 3.4.2, which inelude moditica
tion tactors and alternative analysis procedures to
account for anticipated inelastic response demands where 6." and 6." are in-plane wall and diaphragm
and capacities. displacements in inches, due to a laleral load in Ihe
direction under eonsideralion, equal lo Ihe weight
of the diaphragm.
3.3.1.2 Penod Determi1lano1l 3. For one-story buildings with multiple-span
The fundamental period of a building shall be cal diaphragms, use of Eq. 3-7 shalJ be permitted as
culated for the direction under consideration using one follows: a lateral load equal to lhe weight tributary
of the followíng analylical, empírical, or approximate lO the diaphragm span under consideration shall be
methods specified in this seclion. applied lo calculate a separate period for each
diaphragm span. The period lhat maximizes the
3.3.1.2.1 Method I-Analytieal Eigenvalue (dynamic) pseudo-lateral force shall be used t'or design 01' all
analysis of lhe mathematical model 01' the building walls and diaphragm spans in the building.
shall be performed to determine the fundamental 4. For unreinforced masonry buildings with single
períod 01' lhe building. span flexible diaphragms, six stories or less in
height, use 01' Eq. 3-8 to approximate the funda
mental period shall be permitted.
3.3.1.2.2 Method 2-Empirieal The fundamental
períod of the building shall be determined in accOf
dance with Eq. 3-6: (Eq.3-8)
62
ASeE/SEI41-06
63
SEISMIC REHABILITATION OF EXISTING BUILDlNGS
64
ASeE/SEI 41-06
lb! yielding strength of the structure. For linear anal y applied at any tloor level x shall be determined in
ses, R may be determined using: accordance with Eqs. 3-10 and 3-11:
(Eq.3-11)
_bere DCR,nax is the largest DCR computed for any
primary component, takíng Cl = C2 = Cm 1.0.
The expression above is obtained by substituting
where
&J. 3-9 into Eq. 3-15 and assuming that the elastic
base shear capacity (fully yielded strength, Vy ) is CyX = vertical distribution factor;
lDObilized at a shear that is 1.5 times the shear al first k = 2.0 for T <:! 2.5 sec;
,1eld (as indicated by the largest primary component 1.0 for T s 0.5 sec (linear interpolation shall be
DCR). The latter assumption is based on representative used to calculate values of k for intermediate
'IlIIues for system overstrength. As is indicated in values of 1);
Fig. C4.2-1 ofFEMA 450 (FEMA 2004), the factor V = pseudo-lateral force from Eq. 3-9;
Idaling design force level to fuHy yielded strength is W¡ = portion of the effective seismic weight W
n.,. Sources of overstrength are design 4> factors, located on or assigned lo floor level í;
apected material properties in excess of nominal Wx portion of the effective seismic weight W
-.arerial properties, and global system response. As located on or assigned to floor level x;
lllis standard prescribes use of 4> = 1 and expected h¡ = height (in ft) from the base to floor leve! i; and
...erial properties, the only additional source of over hx = height (in ft) from the base to floor leve! x.
mength is global system response. Using representa
1M! values for these contributions to overstrength 3.3./.3.3 Horizontal Distribution of Seismic Forces
tI1~ = 2.5, 4> 0.75, and expectedlnominal 1.25), The seismic force s at each floor leve! of the building
lIIIe factor relating shear at first yield to elastic base calculated using Eq. 3-10 shall be distributed accord
mear capacity is 1.5. Additional commentary regard ing tO the distribution of mass at thal noor leve!.
iIIg this coefficient is provided in C.3.3.3.3.2.
Coefficient el' This coefficient adjusts design val 3.3./.3.4 Diaphragms Diaphragms shall be designed
.::s based on component hysteresis characteristics, to resist the combined effects of the inertial force, Fpx,
cyclic stiffness degradation, and strength deterioration. calculated in accordance with Eq. 3-12, and horizontal
Fu buildings with systems that do not exhibit degra forces resulting from offsets in, or changes in the stiff
_on 01' stitTness andlor strength, the C2 coefficient ness 01', the vertical seismic framing elements above
ao be assumed to be 1.0. This would ínelude bui/d and below the diaphragm. Actions resulting trom
• with modern concrete or steel special moment offsets in or changes in the stiffness of the vertical
a:sisting frames, steel eccentrically braced frames, and seismic framing elements shall be laken as force
IluckJing-restrained braced frames as either the origi conlrolled, un!ess smaller force s are justified by olher
al system or the system added during seismic rehabil rational analysis, and shall be added directly to the
ilalion. See Section C3.3.3.3.2 and FEMA 274 (FEMA diaphragm inertial forces.
1997) for additional discussion.
Coefficient, Cm' The etTective mass factor was
developed to reduce the conservatism 01' !he LSP for
(Eq.3-12)
lluildings where higher mode mass participation
mluces lateral forces up to 20% depending on build
iIIg type. See FEMA 357 (FEMA 2000), Appendix E
where
for more information on the development of Cm'
Fpx = total diaphragm inertial force al level x;
33./.3.2 Vertical Distribution of Seismic Forces The F¡ = lateral lóad applied at floor level i given by
..:rtical distribution of the pseudo-lateral force shall be Eq.3-1O;
as specified in this section for aH buildings except Wi portion of the effective seismic weighl W
~jnforced masonry buildings, for which the pseudo located on or assigned to floor leve! i; and
llleral force shall be permitted to be distributed in W x = portion of the effeclÍve seismic weight W
a::cordance with Section 3.3.1.3.5. The lateral load Fx located on or assigned to floor level x.
65
SElSMIC REHABILlTATION OF EXISTING BUILDINGS
The seismic load on each flexible diaphragm shall Buildings shall be modeled with linearly e1astic
be distributed along the span 01' that diaphragm, pro stilfness and equivalenl viscous damping values con
portional 10 íts displaced shape. sistenl with components responding al or near yield
Diaphragms receiving horizontal forces from dis level, as detined in Section 2.4.4. Modeling and analy
continuous vertical elements shall be laken as force sis procedures to calculate t'orces and de1'ormations
controlled. Actions on olher diaphragms shall be con shall be in accordance wilh Section 3.3.2.2.
sídered force- or deformation-controlled as specified Results of Ihe LDP shall be checked using the
for diaphragm components in Chapters 5 through 8. acceptance criteria of Section 3.4.2.
66
AseE/SEI4I-06
directions of the building. Modal damping ratios shall of time histories is provided in the U.S. Nuclear
rellect the damping in the building at deformation Regulatory Commission Regulatory Cuide 1.92
,"=vels less than the yield deformation. (USNRC 1976).
Peak member forces, displacements, story force s,
Slory shears, and base reactions for each mode of 3.3.2.3 Determination of Forces and Deformations
response shall be combined by either the square root
sum of squares (SRSS) rule or the complete quadratic 3.3.2.3.1 Modijication of Demands AII forces and
~-ombination (CQC) rule. deformations calculated using either the Response
Multidirectional seismic effects shall be consid Spectrum or the Time-History Method shaIl be multi
.:red in accordance with the requirements of SecO. plied by the product of the moditication factors C I and
Iion 3.2.7. C2 detined in Section 3.3.1.3, and further moditied to
consider the effects of torsion in accordance with
..l3.2.2.4 Time-HistOfY Method Dynamic analysis Section 3.2.2.2.
lbing the time-history method shall calculate building
~ponse at discrete time steps using discretized 3.3.2.3.2 Diaphragms Diaphragms shaIl be designed to
~orded or synthelic time histories as base motion. resist the combined effects of the seismic [orces calcu
lbe damping matrix associated with the mathematical lated by the LDP, and the horizontal forces resulting
model shalI retlect the damping in the building at from offsets in, or changes in stiffness of, the vertical
J.:formation levels near the yield deformation. seismic framing elements abo ve and below the
Response parameters shall be caIculated for each diaphragm. The seismic forces calculated by the LDP
Iime-history analysis. If fewer than seven time-history shaIl be taken as not less than 85% of the forces caIcu
.-alyses are performed, the maximum response of the lated using Eq. 3-12. Actions resulting from offsets in,
parameter of interest shall be used for designo If seven or changes in stiffness of, the vertical seismic framing
.. more time-history analyses are performed, the aver elements shall be taken as force-controlIed, unless
~ value of each response parameter shaIl be permito. smaller forces are justitied by a rational analysis
lO! lo be used for designo approved by the authority having jurisdiction.
Multidirectional seismic etfects shall be consid Diaphragms receiving horizontal forces from
cred in accordance with the requirements of Section discontinuous vertical elements shaIl be taken as force
3.2.7. Alternatively, an analysis of a three-dimensional controlIed. Actions on other diaphragms shaIl be conO.
adhematical model using simultaneously imposed sidered force- or deformation-controlIed as specified
.:uosistent pairs of earthquake ground motion record s for diaphragm components in Chapters 5 through 8 .
*'ng each of the horizontal axes of the building shall
ID.= permitted. 3.3.3 Nonlinear Static Procedure
67
SEISMIC REHABILlTATION OF EXISTING BUILDlNGS
be reasonable approximations of those expected duríng 3. Components not meeling the acceptance crileria 1'or
the design earthquake. primary components are designaled as secondary,
and removed from lhe mathematical model.
3.3.3.2 Modeling and Analysis Considerations
A simplified NSP ana1ysis shall be used with Ihe
acceptance criteria 01' Sections 3.4.3.2.2 and 3.4.3.2.3.
3.3.3.2.1 General Selection of a control node, selection
of laLeralload patterns, determinalion of the fundamen
C3.3.3.2.2 Simplijied NOlllinear Sta tic Procedllre
tal period, and applicalion of the analysis procedure
Analysis The simplitied NSP diJfers from the NSP in
shall comply with the requirements of this section.
Ihat componenl degradalion is nol explicilly included
The relation between base shear force and lateral
in the malhematical model. Therefore, more slringent
displacement of the control node shall be established
acceplance criteria are used and component demands
for control node displacemenls ranging belween zero
musl be within the acceplance crileria limits ror pri
and 150% 01' lhe target displacement, O,.
mary components. Where using the simplilied NSP
The component gravity loads shall be included in
analysis, care should be taken to make sure that
the mathemaLÍcal model for combination with lateral
removal of degraded components from lhe model does
loads as speeitied in Section 3.2.8. The lateral loads
not resuIt in changes lo the regularity of lhe structure
shall be applied in both the positive and negative
Ihat would significantly alLer the dynamic response. In
directions, and the maximum seismic effects shall be
pushing wilh a static load pallern, lhe NSP does not
used for designo
capture changes in the dynamic characleristics 01' the
The analysis model shall be discretized to repre
structure as yielding and degradalion take place.
sent the load-deformation response of each component
In order lO explicitly evaluate deformation
along its length to identi1'y locations of inelastic
demands on secondary components lhat are to be
action.
excluded from the model, one might consider includ
Primary and secondary components 01' lateral
ing Ihem in the model, but wilh negligible stiffness, lo
force-resisting elements shall be incJuded in the
obtain deformation demands without significantly
model, as specitied in Section 3.2.2.3.
affecling the ovcrall response.
The force-displacement behavior of al1 compo
nents shall be explicitly íncluded in the model using
3.3.3.2.3 Control Nade Displacement The control node
full backbone curves that inelude strength dcgradation
shall be localed at the center of mass al the roor 01' a
and residual strength, if any.
building. For buildings with a penthouse, lhe tloor 01'
The NSP shall be used in conjunction with the
the penlhouse shall be regarded as the level 01' the con
acceptance criteria 01' Sections 3.4.3.2.1. and 3.4.3.2.3.
trol node. The displacement 01' lhe control node in the
mathematical model shall be calculated ror the speci
C3.3.3.2.1 General The requirement to carry out the
lied lateral loads.
analysis to at least 150% of the target displacement is
meant to encourage the engineer lO investigate Iikely
3.3.3.2.4 Lateral Load Distributioll Lateralloads shall
building performance and behavior of the model under
be applied to the malhemalical model in proportion to
extreme load conditions lhal exceed lhe design values.
lhe dislribution of inertia forces in lhe plane 01' each
The engineer should recognizc that the target displace
1100r diaphragm. The vertical distribution 01' these
ment represents a mean displacement value for the
forces shall be proportional lO the shape of the funda
design earthquake loading, and that there is consider
mental mode in the direction under consideration.
able scaller about the mean. Estimates of the target
displacement may be unconservative for buildings
C3.3.3.2.4 Lateral Load Distribuiiall The distribution
with low strength compared with the elastic spectral
01' lateral inerlial forces determines relative magni
demands.
tudes of shears, moments, and deformations within the
struclure. The actual dislribution 01' these forces is
3.3.3.2.2 Simplified NSP Allalysis The use of a simpli
expected lo vary continuously during earthquake
fied NSP analysis shall be permitted as follows:
response as JXmions 01' the slruclure yield and stitlness
l. Only primary components are modeled; characteristics change. The extremes of this distribu
2. The force-displacement characteristics of compo tion will depend on the severity of lhe earthquake
nents are bilinear, and ¡he degrading portion of the shaking and the degree of nonlinear response of the
backbone curve is nol explicitly modeled; and structure. Use of more than one lateral load pattern has
68
ASCPJSEI41-06
been used in lhe past as a way lo bound the range of C3.3.3.2.5 ldealized Force-Displacement Curve The
design actions that rnay occur during actual dynarnic idealízed force-displacement curve is developed using
response. Recent research [FEMA 440 (FEMA 2005)] an ilerative graphical procedure to balance the areas
has shown that rnultiple load patterns do litde lO below the actual and idealized curves up to Aa such
irnprove the accuracy of non linear static procedures that the idealized curve has the properlÍes defined in
and that a single pattern based on the tirst mode shape this section. The detlnition of the idealized force
is recommended. displacement curve was modified from the detinition
in FEMA 356 (FEMA 2000) based on the recommen
3.3.3.2.5ldealized Force-Displacement Curve The dations of FEMA 440 (FEMA 2005).
non linear force-displacement relationshíp between
base shear and displacement 01' the control node shall 3.3.3.2.6 Period Determination The effective funda
be replaced with an idealized relalionship to calculate mental period in the direction under consideratíon
the effective lateral stiffness, K" and effective yield shall be based on the idealized force-displacement
strength, Vy ' of the building as shown in Fig. 3-1. curve detlned in Seclion 3.3.3.2.5. The effective fun
The first line segment of the idealized force damental period, Te' shall be calculated in accordance
displacement curve shall begin at the origin and have a wÍlh Eq. 3-13:
slope equal to the effective lateral stiffness, K•. The
effective lateral stiffness, K., shall be taken as the
secant sliffness calculated al a base shear force equal (Eq.3-13)
10 60% of lhe effeclive yield slrenglh of the slruclure.
The effeclÍve yield strength, V y, shall nOI be taken as where
grealer lhan the maximum base shear force at any
Ti = elastíc fundamental period (in seconds) in the
point along the force-displacement curve.
direction under consideralÍon calculated by elas
The second line segmenl shall represent Ihe posi
tic dynamic analysis;
lÍve post-yield slope (a¡Ke ), determined by a point
K¡ elastic lateral stitfness of the building in the
(V,pA,¡) and a poin! at the intersection with the tirst line
dírection under consideratíon calculaled using
segment such that the areas aboye and below the
the modeling requirements 01' Section 3.2.2.4;
actual curve are approximately balanced. (V,... Aa) shall
and
be a point on the actual force-displacement curve at
K. effective lateral stitfness of the building in lhe
the calculated target displacernent, or at the displace
direction under consíderation.
men! corresponding to the maximum base shear,
whichever is leasl.
3.3.3.2.7 Analysis 01 Mathematical Models Separate
The third line segment shall represent the negative
mathematical models representing the framing along
post yield slope (a2K.), determined by lhe point at the
two oflhogonal axes of the building shall be developed
end of the positive post-yield slope (V",A d ) and lhe
for two-dimensional analysis. A mathematical model
point al which the base shear degrades to 60% 01'
representing the framíng along two orthogonal axes of
the effective yield strength.
the building shall be developed for three-dimensional
analysis.
The effects of horizontal torsion shall be evaluated
Base shear ín accordance with Section 3.2.2.2.
Independent analysis along each of the two
orthogonal principal axes 01' the building shall be per
mitted unless concurrent evaluation 01' multidirectional
effccts is required by Section 3.2.7.
69
SEISMIC REHABILITATION OF EXISTING BUILDlNGS
For buildings wilh nonrigid diaphragms al each mulLi-degree of freedom (MDOF) system calcu
tloor level, diaphragm tlexibilily shalI be explicilly lated using one of lhe following procedures:
included in lhe modeJ. The targel displacement shaJl
• The tirst mode mas s participalion factor multi
be calculaled as specified for rigid diaphragms, excepl
plied by the ordinate of the tirst mode shape at
lhat it shall be amplitied by the ratio of lhe maximum
the control node;
displacement at any poinl on the roof to lhe displace
• The mass participation factor ca1culated using
ment at the cenler of mass of lhe roof (omax/oem)' Omax
a shape vector corresponding 10 the detlected
and oen! shalI be based on a response spectrum analysis
shape of lhe building al lhe targel displacement
of a three-dimensional model of lhe building. The tar
multiplied by ordinale of Ihe shape vector al
gel displacement so calculated shall be no less than
lhe conlrol node; or
that displacement given by Eq. 3-14. No line of verti
• The appropriale value from Table 3-2;
cal seismÍc framing shall be evaluated ror displace
ments smaller lhan the target displacement. el = moditication factor lo relate expected maximum
AIternatively, for buíldings with flexible inelaslic displacemenls 10 displacements calcu
diaphragms at each floor level, a targel displacement laled for linear elaslic response. For periods less
shall be calculated for each line of vertical seismic than 0.2 sec, el need not be taken grealer than
framing. The larget displacemenl for an individual Ihe value at T = 0.2 seco For periods grealer than
line 01' vertical seismic framing shall be as specilied 1.0 sec, el 1.0.
for buildings with rigid diaphragms, except lhal lhe
masses shall be assigned to each line on the basis of R-I
lributaryarea. +
Forces and deformations corresponding to Ihe
control node displacement equaling or exceeding the where
larget displacemenl shall comply with acceplance cri a = sile class factor:
teria of Seclion 3.4.3. = 130 site Class A, B;
90 site Class C;
333.3.2 Target Displacement The larget displace = 60 site Class D, E, F;
menl, o" al each tloor level shall be calculated in Te effective fundamental period of Ihe building
accordance with Eq. 3-14 and as specitied in Sec in lhe directÍon under consideration, in sec
tion 3.3.3.3.1. onds;
Ts = characterislic period of the response spec
trum, detined as lhe period associated wilh
(Eq.3-14)
lhe transition from the constant acceleration
segmenl of Ihe spectrum lo the constant
where
velocilY segment 01' Ihe speclrum per
eo = modification factor lo relate speclral displacement Sections 1.6.1.5 and 1.6.2.1;
01' an equivalent single-degree of freedom (SDOF) . R = ratio of elastic strength demand to
system to the rool' displacement. 01' the building yield strength coefticient calculated in
70
ASeE/SEI 41-06
accordance with Eq. 3-15. Use of the NSP The etlective negative post-yield slope ratio, a e ,
is not permitted where R exceeds Rmax, per shall be calculaled in accordance wilh Eq. 3-17:
Section 2.4.2.1;
C2 = modification factor to represent the etlecl of (Eq.3-17)
pinched hysleresis shape. cyclic stíffness degra
dation. and slrength deterioration on maximum where
displacemenl response. For períods greater than a z = negative post-yield slope ralio defined in
0.7 sec, C2 = 1.0; Fig. 3-1. This includes P-d effects, in-cycle
degradalion, and cycJic degradalion;
Cl = 1 +
I
800
(R-;¡:;1)2 ap_.:l. = negalive slope ralio caused by P-d effecls;
and
Á = near tield effect factor:
S.. response spectrum acceleration, al the effective = 0.8 if Si 2:: 0.6 (Maximum Considered
fundamental period and damping ratio of the Earthquake, MCE);
building in lhe direclion under consideration, as = 0.2 if Si < 0.6 (MCE).
calculated in Seclions 1.6.1.5 and 1.6.2.1; and
g acceleralion of graviLy. C3.3.3.3.2 Target Displacement This standard presents
the Coefficient Method for ca1culating target dis
The strength ralio R shall be ca1culaled in accor placement. Other procedures can also be used. Sec
dance wilh Eq. 3-15: tion C3.3.3.3 of FEMA 274 (FEMA 1997) presents
addilional background informalion on the Coetlicienl
Method and anolher acceptable procedure referred to
R=l·c
V,/W m
(Eq.3-15)
as ¡he Capacity Speclrum Method.
The Co coefficient accounts for the difference
.tJere S" is defined aboye, and between the roof displacement of a multi-degree of
V, yield strength ca1culated using results of the NSP freedom (MDOF) building and the displacement of the
for the idealized nonlinear force-displacement equivalent single-degree of freedom (SDOF) system.
curve developed for the building in accordance Using only the tirsl mode shape (ePi) and elaslic
wíth Section 3.3.3.2.5; behavior, coefticient C() is equal lo:
W etl'ective seismic weighl. as calculated in Sec
tion 3.3.1.3.1; and
(Eq. C3-3)
C. effective mass factor from Table 3-1. Alterna
tively, Cm taken as the effective modal mass par
ticipation factor ca1culatéd for the fundamental
mode using an Eigenvalue analysis shall be per
mítted. Cm shall be taken as 1.0 if the fundamen where
tal period, T, is greater than ].0 seco ePI" the ordinale of mode shape 1 al the roof (con
trol node);
For buíldíngs wirh negative post-yield stiffness, [M1 a diagonal mass matrix; and
me maximum strength ratio, R rnax , shall be calculated r I the first mode mass participation factor.
.. accordance with Eq. 3-16.
Since the mass matrix is diagonal, Eq. C3-3 can
(Eq. 3-]6) be rewritten as:
N
_itere
2: m¡eP¡,n
.1,¡ = lesser of target displacement, 5" or displacement C() = <PI" (Eq. C3-4)
at maximum base shear defined in Fig. 31;
.1,. = displacement at effective yield strength defined
in Fig. 3-1;
where
h ] + O.] 5 . In Te; and
a. etlective negative post-yield slope ratio defined m¡ lhe mass at level i; and
in Eq. 3-17. ePi,n the ordinate of mode shape i al level n.
71
SEISMIC REHABILlTATION OF EXISTING BUILDlNGS
If the absolute value 01' the mo1' (control node) should inelude the in-cyele or cyclic strength or stifl'
ordinale of each mode shape is sel equal lo unity, the ncss degradation io the hysteretic models of the com
value 01' coetlicient Co is equal LO the fírsl mode mass ponents as requíred. The effective negatíve posl-yicld
participation factor. slope ratío, a" was introduced in FEMA 440 as a vari
Explicit calculation of eo using the actual able necessary lo determine the maximum slrenglh
deflected shape may be beneficial in terms of lower ratio, Rmux' thal a building can have bel'ore dynamic
amplitication of targel displacement. The actual shape instability is a concern. The negative slope caused by
vector may take on any 1'orm, particularly since it is P-Li etrects, ap_a, is based on lhe restoring force
intended to simulate the timc-varying deflection pro needed 10 balance the overturning momenl caused by
tite of the building responding inelastically lo the the weight of lhe slructure displaced an amount Li, act
ground motion and willlikely be different from the ing al lhe el'feclive height of the tirsl mode. It can be
elastic tirsl-mode shape. If this method is used, lhe delermined using structural analysis software by com
mass participation tactor, r¡, must be calculated using paring the stifí'ness resulls 01' an analysis run with P-Li
the actual detlected shape as the shape vector in licu effects to one run without P-Li eftects considered.
01' the mode shape.
Use 01' the tabulated values, which are based on a 3.3.3.3.3 Modificatíon of Demands The targel dis
straight-line vector with equal masses at each tloor placement shall be moditied to consider the effects oí'
leve!, is approximate (particularly if masses vary much horizontal torsion in accordance with Section 3.2.2.2.
over the height oí' the building) and may be overly
conservative. 3.3.3.3.4 Diaphragms Diaphragms shall be designed
Coefticients 1'or estimating the target displacement to resist the combined effects of the horizontal forces
have been moditied based on the recommendations resuhing from otTsets io, or changes in stiffness 01', the
contained in FEMA 440 (FEMA 2005). vertical seismic framing elements aboye and below lhe
FEMA 440 concluded that the previous cap on the diaphragm, and lhe diaphragm torces determined
el factor was not appropriale and a simplitied equa usiog eilher Section 3.3.1.3.4 or Section 3.3.2.3.2.
tion was recommended based on R, etlective period,
T" and the site c1ass factor, a, with a revised cap al 3.3.4 Nonlinear Dynamic Procedure
T = 0.2 seco FEMA 440 recommended site c1ass lactors
í'or site classes B, C, and D only. The site class factor 3.3.4.1 Basis of the Procedure
for site class A was set equal to lhat for B and lhe site If the NDP is selected l'oe seismic analysis ol' the
c1ass factor for site e1asses E and F was set equal lO building, a mathematical model directly incorporating
that foe D. The use 01' the simplified el equation to the non linear load-deformation characteristics ol' indi
estimate displacemenls for soft soil siles, ineluding vidual compooenls of lhe building shall be subjected
c1asses E and F, will have higher uncertainly due lo lo earthquake shaking represented by ground molÍon
high dispersions 01' the results in studies of SDOF time histories in accordance with Section 1.6.2.2 to
oscillators on soft soils. See FEMA 440 for more dis obtain forces and displacements.
cussion on uncertaimies related to the el equation. Calculated displacements and 1'orces shall be com
The e2 tactor was revised to better account t'ór the pared directly with acceptance eriteria specified in
ellects 01' cyclic degradation oí' stifJ'ness as recom Section 3.4.3.
mended in FEMA 440. For buildings with systems that
do not exhibit degradation 01' stiffness andlor strength, C3.3.4.1 Basis of the Procedure
the e2 coetlicient can be assumed to be 1.0. This The basis, modeling approaches, and acceptance
would inelude buildings with modern concrete or steel criteria of lhe NDP are similar to those tor the NSP.
spedal moment-resisting rrames, steel eccentrically The main exception is that the response calculations
braced trames, and buckling-restrained braced frames are carried out using time-history analysis. With the
as either lhe original system or the system added dur NDP, lhe design displacements are not established
ing seismic rehabilitation. usiog a targel displacement bUl, instead, are deter
The eJ coefticiem has been eliminated and mined directly through dynamic analysis using ground
replaced with a maximum strength ratio, Rnum which is molion time histories. Calculated response can be
intended to measure dynamic instability. Where the highly sensitive to characlerislics of individual ground
value for Rmax is exceeded, an NDP analysis is required molÍoos; therefore, the analysis should be carried out
to capture strenglh degradation and dynamic P-Li with more than one ground molion record. Because
effects to contirm dynamic stability ol' the building. the numerical model accounts directly for etTects ol'
As recommended in FEMA 440, the NDP analysis material inelastic response, the calculated internal
72
ASCElSBI 41-06
forccs will bc reasonable approximations of those using the nonlinear procedures of Seclion 3.3.3 and
expccted during the design earthquake. Section 3.3.4 shall satisfy the requirements 01' Sec
lion 3.4.3.
3.3.4.2 Modeling and Analysis COllsweratiolls Prior to seIecting component acceplance criteria,
components shaIl be c1assified as primary or second
3.3.4.2. / General The modeling and analysis require ary, and actions shalI be classitled as deformation
ments spccitled in Section 3.3.3.2 for the NSP shall controlled or force-controlled, as defined in Sec
apply 10 the NDP, excluding considerations of control tion 2.4.4.
node and target displacements. Foundations shall satisfy the criteria specified in
Chapter 4.
3.3.4.2.2 Grvund Motioll Characterizatioll Por the
NDP, earthquake shaking shall be characterized by C3.4.1 General Reqllirements
díscretized recorded or synthetíc earthquake records The linear analysis procedures are intended to
as base motion meeting the requiremenls of Sec provide a conservalÍve estimate of building response
uon 1.6.2.2. and performance in an earthquake. Since the actual
response 01' buildings lo earlhquakes is typically
3.3.4.2.3 Time-History Method For the NDP, time nonlinear, nontinear analysis procedures should
bistory analysis shall be performed using horizontal províde a more accurate representalíon 01' building
ground molion time histories prepared according lo Ihe response and performance. In recognilion of lhe
requiremems of Section 1.6.2.2. improved estimates 01' nonlinear analysis, the accept-·
Multidireclional seismic effecls shall be accounled ance crÍleria for nonlinear procedures are more
for in accordance with Section 3.2.7. Alternatively, an accurate and less conservative than those for linear
analysis of a Ihree-dimensional malhematical model procedures. Buildings thal do nol comply wilh Ihe
using simullancously imposed consistent pairs of linear analysis acceptance criteria may comply
earlhquake ground motion record s along each 01' the with non linear acceptance criteria. Therefore, per
bori:wntal axes of the building shaIl be pennitted. 1'orming a nonlinear analysis is recommended to
minimize or eliminate unnecessary seismic rehabilita
C3.3.4.2.3 Time-History Method Guidance for correla tion. Users are urged to report [O (he building owner
úon betwecn sets of time histories is provided in the limitations on the use of linear procedures and lo
U.S. Nuclear Regulatory Commission Regulatory pursue nonlinear analyses where linear acceptance
Guide 1.92 (USNRC )976). criteria are not mel.
73
SEISMIC REHABILlTATlON OF EXISTING BUILDlNGS
e3.4.2.1.1 Deformation-eontrolled Actions Because 01' Ideally, an inelaslic mechanism ror the struclure
possible anticipated nonlinear response of the Slruc will be identified and Ihe force-controlled aClions, QuP,
lure, lhe design actions as represented by Eq. 3-18 for design will be determined by limil analysis using
may exceed lhe aclual strength 01' lhe componenl lo lhat mechanism. This approach wilJ always produce a
resist these actions. The acceptance criteria 01' Sec conservative estimate of lhe design actions, even if an
lion 3.4.2.2.1 lake this overload into accounl through incorrecl mcchanism is selected. Where il is nol possi
use of a faclor, m, which is an indirect measure ble lo use l imit (or plaSlic) analysis, or in cases whcre
of Ihe nonlinear deformation capacity of lhe design forces do not produce significant nonlinear
componenl. response in Ihe building, it is acceptable lo determine
lhe rorce-conlrolled actions rOl' design using Eg. 3~ 19.
3.4.2.1.2 Force-eontrolled Actions Force-conlrolled Coefficients el and el were introduced in Eg. 3-9
design actions, Qup, shall be calculaled using one of to amplify the design base shear lo achieve a bettcr
the following melhods: estimale of lhe maximum displacements expected for
buildings responding in the inelastic range.
l. QUF shall be laken as the maximum aclion thal can
Displacemenl amplitiers, el and e 2, are divided out 01'
be developed in a componenl based on a limit-state
Eq. 3-19 when seeking an estimale ol' Ihe force level
analysis considering the expecled strength of the
presenl in a component where lhe building is respond
components delivering load lo the componenl under
ing inelaslically.
consideralion, or lhe maximum aClion developed in
Since J is included for force-controlled actions, il
lhe component as limiled by lhe nonlinear response
may appear lo be more advanlageous to lreal an action
01' Ihe building.
as force-controlled where m-faclors are less than J.
2. Alternalively, QUF shall be calculated in accordance
However, proper application of force-conlrolled crite
wiLh Eq. 3-19.
ria requires a ¡imit state analysis of demand and lower
bound calculation of capacity that will yield a safe
(Eq.3-19) result whelher an action is treated as force- or dcfor
mation-controlled.
where
QUF = force-controlled design action due lo gravily 3.4.2.2 Acceptallce Criteria for Lillear Procedures
loads in combination with earthquake loads;
and 3.4.2.2.1 Deformation-eontrolled Actions Deforma
J force-delivery reduclion factor, greater than lion-controlled aclions in primary and sccondary com
or equal to 1.0, taken as the smallesl demand ponents shall salisfy Eq. 3-20.
capacily ratio (DCR) 01' the components in
lhe load path delivering force lo the compo (Eq. 3-20)
nent in question, calculaled in accordance where
with Eq. 2-1. Alternalively, values of J equal m = component demand moditicalion faclor lo
to 2.0 tor a High Level of SeismicilY, 1.5 tor account tor expccted ductility associated with
a Moderate Level of SeismicilY, and 1.0 for a this action al the seleCled Structural Perfor
Low Level of Seísmicity shall be permitted mance Leve!. m-factors are specilied in
where nOL based on calculated DCRs. J shall Chapters 4 through 8;
be Laken as 1.0 fol' Ihe Immediate Occupancy QCE expected strength of the componenl at the
Slructural Performance Leve!. In any case deformation level under consideralion for de
where Ihe rorces contributing lo QUF are formalÍon-controlled aclions. Q(D the expecled
delivered by components 01' lhe lateral force slrenglh, shall be determined considering an
resisting system Ihat remain e1astic, J shall be coexisting actions on the componenl under the
taken as 1.0. design loading condition by proccdures speci
tied in Chaplers 4 through 8; and
e3.4.2.1.2 Force-eontrolled Actions The basic K knowledge factor defined in SectÍon 2.2.6.4.
approach for calculaling force-conlrolled aClions
for design differs from thal used ror deformation 3.4.2.2.2 FOf'ce-eontrolled Actiolls Force-controlled
cOnlrolJed actions because non linear deformations asso actions in primary and secondary components shall
cialed with forced-conlrolled actions are nol permitted. salisfy Eq. 3-21:
Therefore, force demands for force-controlled acLions
should not exceed the force capacity (strengLh). KQCL?:: QUf (Eq.3-21)
74
ASeE/SEI41-06
76
AseE/SEI 41·06
l. For enhanced rehabilitation objectives, the soil unit 4.2.2 Seismic Geologic Site Hazards
weight, '}'; soil cohesion, e; soil friction angle, Seismic rehabilitation shall inelude an assessment
4>; soil compressibility characteristics, soil shear of earthquake·induced hazards at the site due to fault
modulus, G; and Poisson's ratio, /1, for each type of rupture, liquefaction, differential compaction, landslid
soil, shall be determined. ing, and an assessment of earthquake-induced flooding
or inundation in accordance with Sections 4.2.2.1
C4.2.J.J.2 Subsurface Soil Conditiolls Specific foun through 4.2.2.5.
dation information developed for an adjacent or If the resulting ground movements cause unac
~y building may be useful if subsurface soils and ceptable performance in the building for the selected
!fOund water conditions in the site region are known performance level, then the hazards shall be mitigated
10 be uniformo However, less confidence will result if in accordance with Section 4.3.
subsurface data are developed from anywhere but the
:Y1e of the building being rehabilitated. Adjacent sites 4.2.2.1 Fault Rupture
..bere construction has been done recently may pro A geologic fault shall be defined as aplane or
,ide a guide for evaluation of subsurface conditions at zone along which earth material s on opposite sides
die site being considered. Sources of existing geotech have moved differentially in response to tectonic
laical information are discussed in C2.2.3. forces.
Geologic site information shall be obtained to
U1.2 Design Foundation Loads determine if an active geologic fault is present under
Information on the design foundation loads shall the building foundation. If a fault is present, the fol
be obtained, ineluding separate information on dead lowing information shall be obtained:
Ioads and live loads. Alternatively, the design founda
l. The degree of activity based on the age of most
Don loads shall be calculated where information on the
recent movement;
design foundation loads is not available.
2. The fault type-whether it is a strike-slip, normal
slip, reverse-slip, or thrust fault;
C4.2.1.2 Design Foundation Loads
3. The sense of slip with respect to building geometry;
Design drawings may indicate information regard
4. Magnitudes of vertical and/or horizontal displace
ÍIIIg the allowable bearing capacity of the foundation
ments consistent with the selected earthquake haz
romponents. This information can be used directly in
ard level; and
a presumptive or prescriptive evaluation of the founda
5. The width and distribution of the fault-rupture
Iion capacity. Construction records may also be avail
zone.
abIe indicating ultimate pile capacities if load tests
.'ere performed. Information on the existing loads on
lIIhe structure is relevant to determining the amount of C4.2.2.1 Fault Rupture
overload that the foundations may be capable of resist Buildings found to straddle active faults should be
iIIg during an earthquake. assessed to determine if any rehabilitation is war
ranted, possibly to reduce the collapse potential of the
U1.3 Load-Deformation Characteristics Under structure given the likely amount and direction of fault
Sftsmic Loading displacement.
Load-deformation characteristics of foundations
sbaIl be obtained from geotechnical reports, or shall be 4.2.2.2 Liquefaction
.Jetermined in accordance with the requirements of Liquefaction shall be defined as an earthquake
Section 4.4. induced process in which saturated, loose, granular
soils lose shear strength and liquefy as a result of an
C4.2.1.3 Load-Deformation Characteristics Under increase in pore-water pressure during earthquake
Slismic Loading shaking.
Traditional geotechnical engineering treats Subsurface soil and ground water information
~eformation characteristics for long-term dead shalI be obtained to determine if liquefiable materials
Ioads plus frequently applied live loads only. In most are present under the building foundation. If liquefi
cases, long-term settlement governs foundation designo able soils are present, the following information shall
Sbort-term (earthquake) load-deformation characteris be obtained: soil type, soil density, depth to water
bes have not traditionally been used for design; conse table, ground surface slope, proximity of free-face
quently, such relationships are not generalIy found in conditions, and lateral and vertical difIerential
libe geotechnical reports for existing buildings. displacements.
77
SEISMIC REHABILlTATION OF EXISTING BUILDlNGS
Asile shall be regarded as free from liquefaction defined in ASTM D1586-99 (ASTM 1999), for
hazard if (he site soils, or similar soils in lhe sile vicin depths below the ground water table, or with c1ay
ity, have nOI experienced historieal Iiquefaction, and if content greater than 20%; or
any of the following criteria are mel: 5. The ground water table is at least 35 ft below lhe
deepesl foundation depth, or 50 ft below the ground
l. The geologic materials underlying the site are
surface, whichever is shallower, including consider
either bedrock or have very low ]iquefaclion sus
alions for seasonal and historic groundwater level
ceptibilily according lo lhe relative susceptibility
rises, and any slopes or free-face condiLÍons in the
ratings based upon lhe Iype of deposít and geologic
site vicinity do nol eXlend below the ground water
age of the deposil, as shown in Table 4-1 ;
elevation at the site.
2. The soils underlying lhe site are sLitJ clays or
clayey silts;
3. The soils are not highly sensitive, based on local If a Iiquefaction hazard is determined lo exísl at
experíence; the sile, lhen a more detailed evaluatíon 01' potential
4. The soils are cohesionless wilh a minimum normal ground movements due Lo liquefaclion shall be per
izOO Standard Penetration Test (SPT) resistance, 1'ormed using procedures approved by the aUlhority
(N1)61J' value of 30 blows/O.3m (30 blows/ft) as having jurisdiction.
Table 4-1. Estimated Susceptibility to Liquefaction of Surficial Deposits During Strong Ground Shaking
78
AseE/SEI 41-06
79
SEISMIC REHABlLlTATION OF EXISTING BUILDINGS
stabiliLy analyses using undrained residual strengths Evaluating Potential for Flotation of Duried
fol' the liquetied materials. Structures. A common phenomcnon accompanying
Evaluating Potential for Bearing Capacity Iiquefaction is lhe tlotation 01' tanks or strucLUrcs Lhal
Failure. The occurrence ol' liquefaction in soils sup are embedded in liquclied soil. A building with a base
porting foundations can l'esult in bearing capacity fail meni surroundcd by Iiquelied soil can be susceptible
ures and large, plunging-type settlements. In fact, lhe to either Ilolation or bearing capacily failure, depend
buildup ol' pore-water pressures in a soil to less lhan a ing on Ihe building weight and the structural continu
complete liquefaction condition will still reduce soil ity (j.e., whelher the basemcnt acts as an integral unit).
sLrength and may threaten bearing capacity if the The potential ror notaLioll 01' a buried or embedded
slrengLh is reduced sufticiently. slructure can be evaluaLed by comparing the lOtal
The potential for bearing capacily l'ailure beneath weight of Ihe buried or embedded structure wilh Ihe
a spread fooling depends on lhe depth of the Iiquefied increased uplift forces occurring due lo Ihe buildup 01'
(or parlially liquefied) layer below the l'ooting, lhe size Iiquefaclion-induced pore-water pressures.
01' Lhe l'ooling, and Ihe load. If lighlly loaded small
footings are located sufticiently aboye the depth of Iiq 4.2.2.3 Differential Compaclion
uelied malerials, bearing capacily 1'ailure may nol Dillerenlial compaction shall be delined as an
occur. The foundation bearing capacity for a case earlhquake-induced process in which Foundalion soils
where a footing is located so me distance aboye a Hq compacl and lhe foundalion seules in a nonuniform
uelied layer can be assessed by evalualing Lhe strength manner across a site.
of lhe Iiquetied (excess pore pressure ratio = 1.0), Subsurface soil informaLion shall be oblained lo
partially liquetied, and nonliquetied strala, lhen apply delermine if soils susceptible to ditrerential com
ing bearing capacity formulalions fol' layered syslems paction are present under the building foundation.
(Meyerhof 1974; Ranna and Meyerhof 1980; Ranna A site shall be regarded as free 01' a dítlcrenlial
1981). The capacily 01' friclion pi le or pier foundations compaction hazard ir lhe soil condilions meet both 01'
can be similarly assessed, based on the slrengths 01' Ihe the following criteria:
liquetied, partially liquefied, and nonliquel1ed slrala
l. Geologic malerials below lhe ground water lable do
penetraled by the l'oundations.
nol pose a litluefaction hazard, based on the criteria
Evaluating Potential for Liquefaction-Induced
in Section 4.2.2.2; and
Settlements. Following lhe occurrence of liquefaction,
2. Geologic deposits aboye the ground water tablc are
over lime Lhe excess pore-water pressures built up in
eilher Pleistocene in geologic age (okler lhan
the soil will dissipate, drainage will occur, and the soil
11,000 years), stitT c1ays or c1ayey silts, or cohe
will densil'y, manifeslÍng at lhe ground surface as sel
sionless sands, silts, and gravels wÍlh a minimum
t1ement. Dil'ferential seUlemenLs occur due lo laleral
(N j )60 01' 20 blows/0.3 m (20 blows/ft).
varialions in soil slratigraphy and density. Typically,
such settlemenls are much smaller and lend lo be more If a di1'ferentíal compaction hazard is dctermined
uniform Ihan those due lo bearing capacity failure. to exist at the sile, lhen a more delailed evaluation
They may range from a few ¡nches to a few feet al lhe shall be performcd using approved procedures.
O1ost where thick, loose soil deposils liquefy.
One approach Lo estimating Ihe magnitude 01' such C4.2.2.3 Differential Compactíon
gl'ound settlemenL, analogous lo lhe Seed-Idriss sim Ditrerential compaclion 01' densilicalion 01' soils
plified empirical procedure 1'or liquefaction pOlential may accompany strong ground shaking. The resulting
evaluation (Le., using SPT blow count data and cyclic dill'erential seltlements can be damaging to slruclures.
stress ratio), has been presentcd by Tokimatsu and Types of soil susceptible lo liquefaclioll (i.e., relalively
Seed (1987). Relationships presented by Ishihara loose natural soils, or uncompacled or poorly com
and Yoshimine (1992) are also available for assessing pacted till 80ils) are also susceptible lo compaclion.
scttlement. Compaction can occur in soils aboye and below the
Evaluating Increased Lateral Earth Pressures groundwaler table.
on Building Walls. Liquefaction of soils adjacenl lo Silualions moSl susceptible to differential com
building walls increases lateral eaflh pressures which paction include heavily graded areas where deep lills
can be approximaled as a tluid pressure having a unit have been placed lo create building siles 1'or develop
weighl equal lo the saturated unil weight of lhe men!. If lhe tills are not well compacted, they may be
soil plus lhe inertial forces on the soil equal lO Ihe susceptible to significant settlements, and differenlial
hydrodynamic pressure. selllements may occur aboye variable deplhs ol' 1111
80
ASeE/SEI41-06
placed in canyons and near the transitions of cut and zation, and may pose special challenges if adequate
filled areas. investigation requires access to adjacent property.
81
SEISMIC REHABILlTATION OF EXISTING BUILDlNGS
section are based on the concept that the extent of site ground deformation. This solution may be feasible for
hazards is discovered after the decision for seismic small ground deformations.
rehabilitation of a building has been made; however,
the decision to rehabilitate a building and the selec 2.2 Modification of the Foundation
tion of a Rehabilitatíon Objective may have been The foundation system should be modifiOO to
made wilh full knowlOOge that sígnificant site reduce or eliminate the ditlerential foundation dis
hazards exist and must be mitigated as pan of the placemenls by underpinning existing shallow founda
rehabilitation. tions lO achieve bearing on deeper, nonliqueiiable
Possible mitigation strategies for seismic geo slrata or by stiftening a shallow foundation system by
logic site hazards are presented in the following a system of grade beams betwccn isolated footings, or
sections. any other approved method.
82
ASeE/SEI 41-06
m,¡uirements for the seleeted performance level, Ihen they degrade significanlly in stiffness and strength
~ or more of the following mitigation measures under cyclic loading. With Ihis assumption, the provi
tIiould be implemented lo achieve acceptable sions of this section provide an overview of the
performance: requirements and procedures for evaluating the ability
of foundations 10 wilhstand the imposed seismic loads
Regrading; without excessive deformations.
Drainage; The amount of acceptable deformalions for foun
Buttressing; dations in such soils depends primarily on the effect of
Struclural improvements: Ihe deformalÍon on the Slructure, which in lum
Gravity walls; depends on the desircd Structural Performance
Tiebacklsoil nail walls; Leve\. However, foundation yield associated with
Mechanically stabilized earth walls; mobilizalion at upper-bound expected capacity dur
Barriers for debris lOrrents or rock fall; ing earthquake loading may be accompanied by
Building strenglhening lo resisl deformation; progressive permanenl foundation seulement during
Grade beams; and continued cyclic loading, albeit in most cases Ihis
Shear walls. seulement probably would be less Ihan a few inches.
Soil moditicalionlreplacemenl: In general, if the real loads transmitted to the founda
Grouting; and tÍon during earthquake loading do nol exceed upper
Densificalion. bound expected soil capacities, it can be assumed
that foundation deformations will be relalively
5. fIooding or Inundation smalI.
If the structueal performance of a building evalu Parametric analyses 10 cover uncertainties in soil
~ ror the effecIs 01' earthquake-induced tlooding load-deformation characteristics are required. One
_ inundation fails lo comply wilh Ihe require alternative is lO perform the NSP or NOP because the
-.:nlS ror Ihe selected performance level, then nonlinear load-deformation characteristics 01' the foun
.-e or more 01' the following mitigating measures dations can be directly incorporated in these analyses
tIiould be implemented lo achieve acceptable (Section 4.4.2). In static analyses, a somewhat con ser
performance: vative interpretation of Ihe results is recommended
because cyclic loading effecls cannot be incorporated
•. Improvemenl 01' nearby dam. pipeline. or aque direclly.
duct facilities independent 01' Ihe rehabilitated
building; 4.4.1 Expected Capacities of Foundations
2. Oiversion 01' anticipated peak tlood tlows; The expected capacity of foundation components
1- Installation 01' pavement around the building lo shall be delermined by presumptive, prescriptive, or
reduce scoue; and site-speeific methods as specified in Sections 4.4.1.1
.J, Conslruclion 01' sea wall or break water for tsunami through 4.4.1.3. Capacities shall be based on founda
or seiche protection. lion informalion obtained as specified in Section 4.2.1.
83
SElSM1C REHABlLlTATION OF EXISTING BUILDlNGS
4.4. l. 1.2 Presumptíve Capacitíes 01 Deep Foundations Table 4-5 Typical Pi le and Pier Capacity
II shall be permiued to determine pile and pier o
Parameters: Frietion Angle, (degrees)
eapaeíty parameters using Table 4-3, 4-4,4-5, and
Table 4-6 Typical Pile and Pier Capacíty
4-6.
Paramelers: Cohesíon, CI> and Adhesíon, Ca (pst)
Table 4-3 Typieal Pile and Piel' Capaeíty
Capacities of Piles or Piers in Granular Soils
Parameters: Bearing Capaeity Faetors, N q
Calculatíon 01' presumplive expeeled eapaeilies 01'
Table 4-4 Typical Pi le and Pier Capacity Parame piles or piers in granular soils shall be permiued using
ters: Effeetíve Horizontal Stress Faetors, Fdi and Fui the procedure shown in Fig. 4-1.
Table 4-2. Parameters for Calculating Presumptive Expected Foundation Load Capacities of Spread
Footings and Mats
Table 4-3. Typical Pile and Pier Capaeity Parameters: Bearing Capaeity Factors, N q
84
ASCE/SEl 41-06
Table 4-4. Typical Pile and Pier Capacity Table 4-5. Typical Pile and Pier Capacity
Parameters: Effective Horizontal Stress Factors, Fdi o
Parameters: Friction Angle, (degrees)
and Fui
Pile or Pier Material
Downward Fd/ Upward Fui l
Steel 20
Pile or Pier Type Low High Low High Concrete 0.75 </>
Timber 0.75 </>
Driven H-Pile 0.5 1.0 0.3 0.5
Driven Straight
Prismalic Pile 1.0 1.5 0.6 1.0
Driven Tapered Pile 1.5 2.0 1.0 1.3
Driven Jetted Pile 0.4 0.9 0.3 0.6
Drilled Pier 0.7 0.7 0.4 0.4
Table 4-6. Typical Pile and Pier Capacity Parameters: Cohesion, C and Adhesion, Ca (psf) j,
E.l.po!{;ted values that are selected on the basis of conditions established in accordance with Section 4.4.1.1 shall not fall outside the range of val
es indicated by Low and High
Soil Profile
f Q, (+)' lotal upward capacily
Thickness
Wl
Angle of
Shearing
Density Resistance
QCI'I' tOlal downward capacity L¡ 1¡ $1
L Zoneo!
\--_0--'1< negligible Tesis/al/ce
l~ 1e ~o
L, 11 ~l
20B ZOl/eo! L1 11 $1
Total ímnuuíng resistU1u-'C
lenglh,
ele. de. de,
L
B,Diameter
FIGURE 4-1. Presumptive Expected Capacities of Piles or Piers in Granular Soils.
85
SEISMIC REHABILlTATION OF EXISTING BUILDlNGS
LI 1, el
f
12 e1
Total t LZ
lengl/¡.
1,
t 7.mléO{
t'onslwú aJlwsi.un
elc. elc, de.
t
t 11 1. el
->" -----'
H B. DitlmeleT
86
ASCElSEI41-06
Nonlinear behavior 01' 1'oundations shall be repre are not modeled explicitly, the analysis shall be
sented by an equivalent elasto-plastie 10ad~e1'orma bounded by the upper- and lower-bound foundation
Iion relationship unless another approved relationship capacity as detined in this section. In líeu of explicit
is available. evaluation of uncertainties in foundation characteris
Where foundation components are modeled ties, il shall be permitted lo take the upper-bound stiff
explicitly, the analysis shall be per1'ormed using ness and capacity values as two times the values given
upper- and lower-bound load~eformation characteris in this section and the lower-bound stiffness and
lics of foundations as ilIustrated in Fig. 4-3(a) and capacily values as one-half of the values given in this
defined in this section. Where foundation components sectÍon.
Calculated Capaclty
Q
QI2
Deformation
(a)
87
SEISMIC REHABILlTATION OF EXISTING BUILDlNGS
safety applied lO arrive at design values. The design l'.. = unit weight of water;
values recommended by geotechnical cngineers are d = deplh to sample; and
generally consistent with lhe lower bound. If such dll' = depth to groundwater leve\.
reduced valucs were used by the structural enginecr as
expected values, lhe applicalion of lhe prescribed G" io Eq. 4-5 is expressed in Ibs/psf, as is (T~.
upper- and lower-bound variations would not achieve The eftective shear modulus, G, shall be calcu
lhe intended aim. lated in accordance with Table 4-7.
88
ASCE/SEI 41-06
Based on relative stiffnesses of the foundation The preceedíng equatíon is general1y consistent
structure and the supporting soil, the foundation stitf with traditiona\ beam-on-elastic foundation limits
oess shall be calculated using one of the following (NAVFAC 1986b; Bowles 1988). The resulting soil
Ihree methods: bearing pressures are within 3% of the results, ínc\ud
ing foundatíon tlexibility.
C4.4.2.1.1 Stiffness Parameters Table 4-7 is consistent For rectangular plates (with plan dimensions L
wilh the site classificaLion Tables 1-4 and 1-5 in that and B, and thickness t, and mechanical properties Ef
!he layout and level of complexity are identical, and and vf ) on elastic supports (for instance, mat founda
!he indicalion of problem soils that require site tions or isolated footings) subjected 10 a point load in
specific investigation (si te Class F) is consistenL The the center, the foundation may be considered rigid
rollowing observations on the relationship between where:
shear modulus reduclion and peak ground acceleration
can be made:
l. As the peak ground acceleration approaches zero,
the modulus reduction factor approaches unity;
2. Modulus reduction effects are significantly more
pronounced for softer soils; and
(Eq. C4-2)
The modulus reduction factors given in both
where
FEMA 273 (FEMA 1997) and the FEMA 302 NEHRP
Recommended Provisions (FEMA 1997) overeslimate
!he modulus reduction effects for Site Classes A, B,
(Eq. C4-3)
andC.
The shears and moments in foundation compo
oents are conservative where such components are The aboye equation is based on Timoshenko's
considered rigid. However, soil pressures may be sig solutions for plates on elastic foundations
nificantly underestimated where foundation flexibilily (Timeshenko and Woinowsky- Krieger 1959). The
is ignored. The flexibility and nonlinear response of general solution has been simplified by restriction
soíl and of foundation structures should be considered 10 a center load. Only Ihe t1rst five values of m and n
where the results would change. (in the intinite series) are required lO achieve reason
For beams on elastic supports (e.g., strip foolÍngs able accuracy.
and grade beams) with a point load at midspan, the
beam may be considered rigid where: 4.4.2.1.2 Method 1 For shallow bearing footings ihat
are rigid with respecl to the supporling soil, an uncou
pled spring model, as shown in Fig. 4-3(b), shall rep
(Eq. C4-1)
resenl the foundation stiffness.
89
SEISMIC REHABILlTATION OF EXISTING BUILDlNGS
The equivalent spring constants shall be calcu solutionsare reported in Gazetas (1991). The equa
lated as specified in Fig. 4-4. tions in Fig. 4-4 reilect the most common condi
tions-rectangular foundations and rectangular strip
C4.4.2. 1.2 Method 1 Researchers have developed footings. Rather than taking the approach of ATC 40
spring stiffness solutÍons that are applicable to any (ATC 1996), in which equations for foundations of
solid basernat shape on the surface of, or partially or arbitrary shape were adapted to the case ol' rectangular
fully embédded in, a homogeneous halfspace. Such foundations; the surface sliffness equalions that appear
l
Rocking about x-axis GB O"lB
K xx,sur=l_V 1 L)+0.1 ]
[
[ "LlB
x-axis equations for both x-axis and y-axis.
Torsion about z-axis K",sur=GB 3 0.5_ )2.45 +0.51 J
Pn=J+1.4(LdJ06[1.5+3.7(dL)19( dD )41.6]
foundation height)
Rockíng about y-axis h dcpth LO centroid 01' effeeti ve
sidewall eontaet
90
ASCE/SEI41-06
• Fig. 4-4 are those reported by País and Kausel adaplalion 01' lhe general solulions presenled in
.1988) for the specifie ease 01' rectangular foundalions. Gazetas. Coneerning lhese embedment faclors,
Tbese equalions are used because lhey are somewhat Gazetas reporls lhal "the errors thal may result from
simpler than lhose thal would result from an adapta their use will be well within an acceptable 15 percent."
IlOO of lhe equations in Gazelas (1991) and because Using Fig. 4-4, a two-step calculatÍon process
6ey are expeeted lo be more accurale; Pais and is required. First, Ihe stiffness lerms are calculaled
Kausel reporl that lhe largest error for these shape for a foundation al Ihe sur1'ace. Then, an embed
íp:Cific equalions is expected to be "'les s than a men! correction factor is calculated for each sliff
kw pereent." Because Pais and Kausel report thal ness lerm. The slíffness of lhe embedded foundation
-onIy searce data are available for the sliffnesses 01' is lhe produCI of these two terms. Figure C4-1 iIIus
GObedded reclangular foundalions," lhe embedment trates Ihe e1'fects 01' 1'oundation aspect ratio and
oorre<.:tion 1'actors shown in Fig. 4-4 are based on an embedment.
Shape Effect
15
..
14
.
13
$
~
m
!12
j
E
~
11
1.0
09
1 10
ua
f mbedmellt fUect
(LA3 = 2; d Da)
3.5
3.0
BJ
--z
.....
- .....
--zz
~
AA
yy
2.5
02 0.4 06 06
041
FIGURE C4-1. (a) Foundation Shape Effect; (b) Foundation Embedment Effect.
91
SEISMIC REHABILlTATION OF EXISTING BlJlLDlNGS
According to Gazetas, the heighl of effective side foundation behavior using Winkler models shall be
wall contact, d, should be taken as the average height used. Distributed vertical stitfness properties shall be
of the sidewall that is in good contact with the sur calculated by dividing the total vertical stiffness by the
rounding soil. It should, in general, be smaller than the arca. Uniformly distributed rotational stif1'ness proper
nominal height of contact to accounl ror such phenom ties shall be calculated by dividing the total rotational
ena as slippage and separation that may occur near (he stitl'ness of the tooting by the moment 01' inertia 01' the
ground surface. Note that d will not necessarily attain footing in Ihe direction 01' loading. Vertical and rota
a single value tor all modes 01' oscillation. Where d is tional stiffnesses shalJ be deeoupled rol' a WinkJer
taken larger than zero, the resulting stitl'ness ineludes model. It shall be permitted lo use the proeedure illus
sidewall friction and passive pressure contributions. trated in Fig. 4-5 to decouple these stilTnesses.
Although frequency-dependent solutions are avail
able, results are reasonably insensitive to loading fre C4.4.2.1.3 Method 2 The stitfness per unit length in
quencies within the range of parameters of interest for these end zones is based on Ihe vertical stiffness 01' a
buildings subjected to earthquakes. It is sufficienl to B X B/6 isolated fooLing. The sLitTness per unil length
use static sliffnesses as represenlative 01' repealed load in the middle zone is equivalent to that of an inl1nitely
ing conditions. long strip footing.
4.4.2.1.3 Method 2 For shallow bearing foundalions 4.4.2.1.4 Method 3 For shallow bearing loundations
Ihal are not rigid with respect to the supporting soils, a that are tlexible relative to the supporting soil, the rel
tinite e1emenl representation of linear or nonlinear ative stitlness of foundations and supporting soil shall
L
(Ienglh)
1" ~I
y
Plan Stiflness per unít length:
Section
~ ~ ~ ~
Component stiffnesses:
-1- "1" "1" "1
, I, k
K=
Soil components
FIGURE 4-5. Vertical Stiffness Modeling for Shallow Bearing Footings.
92
ASCElSEI 41-06
be evaluated using theoretical solulions for beams and The moment capacity of a rectangular footing
plales on elastic supports, approved by Ihe authority shall be calculated by Eq. 4-8:
llaving jurisdictíon. The foundation stiffness shall be
pennitted lo be calculated by a decoupled Winkler
model using a uníl subgrade spríng coeflicient. For
Me = LP
2
(1 _!L) qe
(Eq.4-8)
flexible foundalion systems, the uníl subgrade spring
ooefficient, k.v , shall be calculaled by Eq. 4-6. where
P = vertical load on footing;
1.3G P
ksv = BO - v)
(Eq.4-6) q = BL = vertical bearing pressure;
B width of fooling (parallel lo Ihe axis of bending);
.mere
L lenglh 01' footing in Ihe direclion of bending; and
G = shear modulus; qc = expected bearing capacity determined in
B = width of footing; and Section 4.4.1.
l' = Poisson's ratio.
0.9
0.8
0.1
0.6
~ OS
"
0.4
0.3
P =Mobilized Passive Pressure
02 PUl = Ultimate Passive Pressure
/) =Lateral displacement
0.1
H = Thickness of Footing
0.0
0.00 0.01 0.02 0.03 0.05 0.06
1M
93
SEISMIC REHABILlTATlON OF EXISTING BUILDlNGS
capacily, q,. it can be shown lhat uplifl will occur prior much less than half of the total slrength. Therefore, it
lo plaslic yielding of lhe soil where q/qc is less lhan 0.5. is adequate lo characterize lhe non linear response of
If q/q, ís grealer lhan 0.5, lhen lhe soil al me loe will shallow foundations as elastic-perfectly plaslic using
yield prior lo uplift. This i.s ilIustraled in Fig. C4-2. lhe initial, effecrive slitl'ness and rhe lotal expecred
For footings subjected to lateral loads, the base slrenglh. The aClual behavior is expecled lo fall
traction slrength is given by V e + Np., where e is within lhe upper and lower bounds prescribed in (his
the effective cohesion force (effectíve cohesion Slress, slandard.
e, limes footing base area), N is lhe normal (compres
sive) force, and p. is lhe coefticient of friction. If 4.4.2.2 Pi/e Foundations
included, side traclion is calculated in a similar man Apile foundalion shall be defined as a deep foun
ner. The coetlicient of friction is often specitied by the dalion syslem composcd of one or more driven or
geotechnical consultant. In lhe absence of such a rec cast-in-place piles and a pile cap cast-in-place over the
ommendalion, p. may be based on lhe mínimum of the piles, which together form a piJe group supporting one
effective internal friction angle of lhe soil and the fric or more load-bearing columns, or a linear sequence 01'
tion coefticienl between soil and foundation from pub pile groups supporLing a shear wall.
Iished foundation references. The ultimate passive The requirements of this seclion shall apply to
pressure strength is often specified by lhe geotechnical piles less than or equal to 24 in. in diameter. The stiff
consultant in the form of passive pressure coefticienls ness characterislics of single large-diameter piles or
or equivalenl fluid pressures. The passive pressure drilled shafts larger than 24 in. in diameter shall com
problem has been extensively i nvestigated for more ply with the requirements of Section 4.4.2.3.
lhan 200 years. As a result. countless solutions and
recommendations exist. The method used should, at a 4.4.2.2. J Stiffness Parameters The uncoupled spring
minimum, ¡nelude the contributions of internal friction model shown in Fig. 4-3(b) shall be used lo represent
and cohesion, as appropriate. the sliffness of apile foundation where the footing in
As shown in Fig. 4-6, the force-displacement the figure represents lhe pile cap. In calculating the
response associated with passive pressure resislance is vertical and rocking springs, the contribution of the
highly non linear. However, for shallow foundalions, soil immedialely beneath lhe pile cap shall be ne
passive pressure resistance generally accounts for glecled. The total lateral stiffncss 01' apile group shalJ
p p
p p
qc
FIGURE C4·2. Idealized Concentration oC Stress at Edge oC Rigid Footings Subjected to Overturning
Moment.
94
ASeE/SEI 41-06
include the contributions of the piles (with an appro the lower-bound capacity of the foundation structural
priale moditícation for group effects) and the passive components.
resistance of the pi le cap. The lateral stiffness of piles The moment capacity of apile group shall be
s.haJ1 be based on elassical methods or on analytical determined assuming a rigid pile cap. Lower-bound
solutions using approved beam-column pile models. moment capacity shall be based on triangular distribu
1ñe lateral stiffness contribution of the pile cap shall tion ofaxial pi le loading and lower-bound axial capac
~ calculated using the passive pressure mobilization ity of the pi les. Upper-bound moment capacity shall
curve in Fig. 4-6. be based on a rectangular distribution ofaxial pile
Pile group axial spring stiffness values, ksv' shall load using full, upper-bound axial capacity ol' the
~ calculated using Eq. 4-9. piles.
The lateral capacity of apile group shall inelude
N AE the contributions of the piles (with an appropriate
k sv = 2: - (Eq.4-9)
modification for group effects) and the passive resis
n~1 L
lance of the pile cap. The lateral capacity ol' the piles
wbere
shall be calculated using the same method used to cal
,-4 = cross-sectional area of apile; culate the stiffness. The lateral capacity of the pile cap,
E = modulus of elasticity of piles; due to passive pressure, shall be calculated using
L = length of piles; and established principies of soil mechanics. Passive pres
!ti = number of piles in group. sure mobilization shall be calculated using Fig. 4-6.
The rocking spring stiffness values about each C4.4.2.2.2 Capacity Parameters The lateral capacity
horizontal piJe cap axis shall be computed by model of a piJe cap should be calculaled in the same way that
ÍDg each pile axial spring as a discrete Winkler spring. the capacity of a shallow foundation is computed,
1ñe rotational spring constant, ksr , (moment per unit except that the contribution ol' base traction should be
rotation) shall be calculated using Eq. 4-10: neglected. Section C4.4.2.1.5 provides a more detailed
description ol' the calculation procedure.
N
k sr = 2: kvnS~ (Eq.4-1O)
4.4.2.3 Drilled Shafts
n=l
The stiffness and capacity of drilled shaft founda
_-bere
tions and piers of diameter less than or equal to 24 in.
t. = axial stiffness of the n-th pile; and shall be calculated using the requirements for pile
S. = distance between n-th pile and axis of rotation. foundations specified in 4.4.2.2. For drilled shaft
foundations and piers ol' diameter greater than 24 in.,
C-1.4.2.2.J Stiffness Parameters As the passive pres the capacity shall be calculated based on the interac
SUTe resistance may be a significant part of the total tion of the soil and shaft where the soil shall be
sttength, and deep foundations often require larger lat represented using Winkler type models specified
aaI displacements than shallow foundations to mobi in Section 4.4.2.2.
Iize the expected strength, it may not be appropriate to
base the force-displacement response on the initial, C4.4.2.3 Drilled Shafts
dfeclive stiffness alone. Instead, the contribution of Where the diameter of the shal't becomes large
passive pressure should be based on the passive pres (>24 in.), the bending and the lateral stil'l'ness and
SUTe mobilization curve provided in Fig. 4-6. strength ol' the shaft itself may contribute to the overall
Although the effects of group action and the influ capacity. This is obviously necessary for the case of
coce of pile batter are not directly accounted for in individual shafts supporting isolated columns.
me form of the abo ve equations, it can be reasonably
assumed that the lalter effects are accounted for in the 4.4.3 Foundation Acceptance Criteria
range of uncertainties that must be considered in The foundation soil shall comply with the accep
accordance with Section 4.4.1. tance criteria specified in this seclion. The structural
components of l'oundations shall meet the appropriate
4.4.2.2.2 Capacity Parameters The expected axial requirements of Chapters 5 through 8. The foundation
capacity of piles in compression and tension shall be soil shall be evaluated to support an actions, including
determined using the procedures in Section 4.4.1. The vertical loads, moments, and lateral forces applied to
c:xpected axial capacity in tension shall not exceed the soil by the l'oundation.
95
SEISMIC REHABILITATION OF EXISTING BUILDlNGS
4.4.3.1 Simplified Rehabilitation A fixed base assumption shall not be used rol' build
The foundalion soil of buildings for which the ings being rehabilitated 1'or lhe lmmediate Occupancy
Simplified Rehabilitation Method is selected in accor Performance Levellhal are sensilive to base rotalions
dance with Section 2.3.1 shall comply with the 01' other types 01' foundation movement lhat would
requirements 01' Chapter 10. cause the structural componenls to exceed lheir
acceplance criteria.
4.4.3.2 Linear Procedures
The acceptance criteria for 1'oundation soil ana 4.4.3.3.2 Flexible Base Assumption If the base of the
Iyzed by linear procedures shall be based on the mod structure is assumed lo be flexible and is modeled
eling assumptions for the base of the structure speci using tlexible nonlinea¡' foundation soil, then the foun
fied in Section 4.4.3.2.1 or 4.4.3.2.2. dation soil shall be c1assitied as deformatíon
controlled and the displacements at the base of the
4.4.3.2. J Fixed Base Assumptiofl If the base of the slructure shall not exceed lhe acceptance criteria 01'
slructure is assumed 10 be completely rigid, the foun this section. For the Lite Satety and CoHapse
dation soil shall be c1assified as defonnation Prevention Structural Peti'ormance Levels, acceptabil
controlled. Component actions shall be determined by ity of soil displacements shall be based on the ability
Eq. 3-18. Acceptance cnteria shall be based on of the structure lo accommodate these displacements
Eq. 3-20, m-factors ror foundation soil shall be 3, and within Lhe acceptance criteria for the selected
the use of upper-bound component capacities shall be Rehabilitation Objectíve, For the Immediate
permiued. A tixed base assumption shall not be used Occupancy Structural Performance Level, the perma
for buildings being rehabilitated to the Immediate nem, nonrecoverable displacement of the fóundation
Occupancy Performance Level that are sensitive to soil shall be calculated by an approved method based
base rolations or olher types of foundation movement on the maximum total displacement, foundation and
that would eause the structural components to exceed soil type, thickness of soillayers, and other perlinent
their acceptance criteria. factors. The acceptability of these dísplacements shall
If the alternative overturning method described in be based upon the ability 01' the strueture to accommo
Section 3.2.10.] is used, the 1'oundation soil shall be date lhem wíthin the acceptance critería rOl' Ihe
c1assilied as force-controlled. Component actions shaJl Immediate Occupancy Structural Performance Leve!.
not exceed the calculated capacities and upper-bound
componen! capacities shall no! be used.
4.5 KINEMATIC INTERACTION ANO
4.4.3.2.2 Flexible Base Assllmption If the base of the FOUNOATION OAMPING SOIL-STRUCTURE
structure is assumed lO be flexible and is modeled INTERACTION EFFECTS
using linear foundation soil, then the foundation
soil shall be classitled as de1'ormation-controlled. Where required by Section 3.2.6., soil-structure inter
Component actions shall be determined by Eq. 3-18. action etlects shall be calculated in accordance with
Soil strength need not be evaluated. Acceptability of Section 4.5.1 for kinematic interaction effects and
soil displacemenlS shall be based on the abil ity 01' the Section 4.5.2 1'01' foundation damping effects.
structure to accommodate these displacements within
the acceptance criteria for the selected Rehabilitation
Objective. C4.5 KINEMATIC INTERACTION ANO
FOUNOATION OAMPING SOIL-STRUCTURE
4.4.3.3 NOI,lillear Procedures INTERACTION EFFECTS
The acceplance cnteria for foundation soil ana
Iyzed by nonlinear procedures shall be based on lhe Foundation tlexibility is covered in Section 4.4. SSI
modeling assumptions fol' the ba<;e 01' the structure eftects that serve to reduce the shaking input 10 the
specilied in Section 4.4.3.3.1 or 4.4.3.3.2. structure relative to lhe free-lield mOlion (kinematic
interaction and damping) are covered in this section.
4.4.3.3.1 Fixed Base Assumption If the base of the Procedures for calculating kinematic and damping
slruClure is assumed 10 be completely rigid, then the effects were taken from recommendations in FEMA
base reactions ror all foundation soil shall be classitied 440 (FEMA 2005) and have been included in the
as force-controlled, as determined by Eq. 3-19, and FEMA 368 (FEMA 2001) and FEMA 450 NEHRP
shall nol exceed upper-bound componenl capacities. Recommended Provisions for Seismic Regulations for
96
ASCElSEI41-06
(Eq.4-11)
RRS, = cos(~7I'e)
Tnv,
lhe larger 01'0.453 or lhe
G'J ~
-..
11
0.9 /
/
/
- ---- /
,.-
,
,
,~
where
e = foundation embedment deplh, feet. A min
imum of 75% 01' lhe foundation footprint
a::: a: /
.
/
¡¡;;:C1 /
/
located on sloping ¡¡iles shall be lhe shal
.~ I I
I
lowest embcdmenl;
.g! 0.7 I I
~as
I
I
Simplified Model Vs = shear wave velocity for site soil condi
e.c I
..2.!!! I
I
65 ft tions, laken as average value 01' velocity to
.11.1 /
"OCD 0.6 I
I
b,,=-130 ft
a depth of b. below foundation, ft/sec;
e 11.1 I
:Sea I Il = shear wave velocity reduclion factor;
0.0 I b,,=200ft
LE 0.5 __ 1I ft = VGjG u'. and
-
e
0.4 '---'---'--....l--'---'---'---'---'-_'--oL..--'---J
b,,=330 ft
G/G" = effeclive shcar modulus ralio from
Table 4-7.
97
SEISMIC REHABlLlTATION OF EXISTING BUlLDlNGS
embedded foundalions without basements where lhe multistory structures 01' as lhe full height of the
foundalion is lalerally connected. However, lhe building for one-story structures;
embcdment etlect factor is not applicable lo embedded
N
individual spread foolings.
¿Wi 4>il !t i
h = ,-i--,-~_ __
4.5.2 Foundation Damping Soil-Structure
Inleraction Effects 2 W¡4>iI
;=1
The effects of foundalion damping ror non linear
analyses shall be representcd by the ellective damping
ro = equivalent foundation radius for rotation;
ratio of the struclure-foundation system, Po. delermined
in accordance wilh Eq. 4-13. Moditicalion 01' lhe accel
eralÍon response spectrum calculaled in accordance
r
o
= (3(1 -8e V)K o)I/3
with Section 1.6 using Po in Iieu of lhe effeclíve vis
cous damping ratio, p, shall be pcrmitted except where:
K o = effective rotational stitlness of lhe foundation;
l. Verticallateral-force-resisting elements are spaccd
al a distance less than the larger dimension of either
component in the dírection under consideralion;
2. v,Tlr,j21T (where v, average shear wave velocily
to a deplh of rJ and lhe shear stitlness 01' founda
tion soils increases with depth;
3. The soil profile consists of a soft layer overlying a Kjt",¡ =
271')2 ;
M* ( T
very stiff material, and lhe syslem period is greater
that the tirst-mode period of lhe layer. M* = etTective mass lor lhe ¡¡rst mode.
Alternatively, it shall be permiued 10 take the
etlcctive mass as 70% of the total building
(Eq.4-13) mass, except where lhe mass is concentrated
at a single level, it shall be taken as lhe lolal
where building mass;
98
AseE/SEI 41-06
T = fundamental period of the building using a model C4.5.2 Foundation Damping Soil-Structure
with a fixed base, sec; and Interaction Effects
t = fundamental period of the building using a model Foundation damping effects tend to be important
with a flexible base, seco for stiff structural systems such as shear walls and
braced frames, particularly where they are supported
The effective period lengthening ratio shall be on relatively soft soil sites such as site Classes D and
ddermined in accordance with Eq. 4-15. E. The procedure is conservative where foundation
aspect ratios exceed 2: 1, and where foundations are
t
--
_
Teff
eff { 1 [( -
1+-
J1-
t)2 ]}O.5
T
-1 (Eq.4-15)
deeply embedded (e/rx > 0.5), but is potentially
unconservative where wall and frame elements are
c10se enough so that waves emanating from distinct
foundations components destructively interfere with
,. = expected ductility demando For nonlinear proce each other across the period range of interest.
dures, J1- is the maximum displacement divided The damping ratios determined in accordance with
by the yield displacement (8,/ Ily for NSP). For this section represent radiation damping effects only.
linear procedures, J1- is the maximum base shear See FEMA 440 (FEMA 2005) for further discussion of
divided by the elastic base shear capacity. foundation damping SSI effects, inc1uding limitations.
99
SElSMIC REHABIUTATION OF EXISTING BUILDlNGS
qualily, unreinforced or lightly reinforced walIs, walls of foundalions by achieving one or more of lhe
of archaic malerials, unusually tall or lhin walls, dam following resuhs: (1) improvemenl in vertical bear
aged walls, or other condilions implying a sensitivity ing capacity of fooling foundations; (2) increase
lo increased loads. in the laleral frictional resistance al lhe hase of fool
The express ion in Eq. 4-16 is a simplified approx ings; and (3) increase in lhe passive resislance
imation of lhe Mononobe-Okabe 1'ormulalion. The of lhe soils adjacenl to foundalions or grade
aClual magnitude and distribution of pressure on walls beams.
during earlhquakes is very complex. If walls do nol Soil improvement options lo increase lhe verlical
have lhe apparent capacily lo resíst lhe pressures hearing capacity of fooling foundalions are limited.
eSlimated from lhe previously described approximate Soil removal and replacement and soil vihralory densi
procedures, detailed invesligalion by a qualificd geo ticalion usually are nol feasihle hecause lhey would
technical engineer is recommended. The seismic carth induce seUlemenls benealh lhe footings or be expen
pressure from lhis equalion is added to lhe unfactored sive to implement without causing seulement. Grout
slalic eanh pressure, which ineludes pressure due to ing may be considered to increase bearing capacity.
soil, waler, and surcharge loads. Different grouting lcchniques are discussed in
Seismíc earlh pressurcs calculaled in accordance FEMA 274 Seclion C4.3.2 (FEMA 1997). Compac
Wilh lhis seclion are inlended for use in checking lion grouting can achieve densificalion and strengthen
acceplabilily 01' local wall componenls and should nol ing of a variety 01' soil lypes and/or eXlend foundation
be used lo increase lotal base shear on lhe building. loads to deeper, stronger soils. The technique requires
careful control lO avoid causing uplift of foundation
componenls or adjacent tloor slahs during lhe grouling
process. Permeation grouting with chemical groUls can
4.7 FOUNDATION REHABILITATION
achieve substanlial slrengthening of sandy soils, bUl
lhe more fine-grained or silty lhe sand, lhe less effec
Foundalion rehabililation schemes shall be evaluated in
(ive lhe lechnique becomes. Jel groUling could also he
conjunction with any rehabilitation of the superstructure
considered. These same lechniques also may be con
and according lO the general principIes and requíre
sidered lo increase the lateral friclional resistance al
ments of lhis standard to assure that lhe complete reha
lhe base of footings.
bilitaLion achieves lhe selected building performance
Soil improvement by lhe following melhods may
level for lhe selecled earthquake hazard leve\. Where
be ell'eclÍve in increasing lhe passive resislance of
new rehabilitation components are used in conjunclion
soils adjacenl to foundations or grade beams: removal
wilh exísting components, lhe effecló) of differentíal
and replacement of exislíng soils with stronger,
foundation stiffness on lhe modificd struclure shall be
well-compacted soils or with treatcd (e.g., cemenl
demonslraled Lo meet Ihe acceplance criteria. If exisling
slabílized) soils; in-place mixing of exisling soils
loads are not redistribulcd to all lhe components of lhe
Wilh strengthening malerials (e.g., cemenl); grouting,
rehabílitated foundation by shoring andJor jacking, the
incJuding permeation grouling and jel grouling; and
effecls of ditferential strengths and stiffnesses among
in-place densitícation by impact or vihralory com
individual foundalion componenls shall be íneluded in
paction. In-place densitication by impact or vibralory
the analysis 01' the rehabilitated foundation. The etlects
compaction should be used only if lhe soillayers to
of rehabilitation on stitrness, strength, and deformability
he compacled are not loo lhick and vihralion eftecls
shalI be laken inlo account in an analytical model 01' the
on lhe structure are lolerable.
rehabilitated slructure. The compatibility 01' new and
exisling componenls shall be checked al displacements
ShaUow Foundation Rehabilitation. The following
consislenl wilh the performance level chosen.
measures may be effeclive in lhe rehahiJilalÍon of shal
low foundalions:
100
ASeE/SEI 41-06
101
SEISMIC REHABILlTATlON OF EXISTING BUILDlNGS
Use of default material properlies shall be permit Structural steel componenls constructed arter
ted in accordance with Section 5.2.2.5. Use of mate 1900 shall be e1assified based on ASTM specitication
rial properties based on historica1 information as and material grade and, if applicable. shape group in
default values shall be permiued as specitied in accordance with Table 5-2. Lower-bound material
Section 5.2.2.5. propenies shall be taken in accordance with Table 5-2
for material conforming 10 the specitications lisled
CS.2.1 General therein. For material grades not listed in Table 5-2,
The extent of in-place materials testing and condi Jower-bound material propel1ies shall be taken as nom
lion assessment thai must be accomplished is related inal or specilied properties, or shall be based on tests
to availability and accuracy of construction and as where the material grade or specitied value is not
built records. the quality of materials used and con known.
struction perl'ormed, and the physical condition ol' (he Where materials testíng is required by Sec
structure. Data such as the properlies and grades of lio"n 2.2.6, test melhods lo determine ASTM
material used in componenl and connection fabricatÍon designation and material grade or lo quanlify mate
may be effeclively used lo reduce the amounl of Ín rial properlies shall be as specified in Sec
place testing required. The design protessional is lion 5.2.2.3.
encouraged to research and acquire all availab1e The minimum number of tests shall comply wilh
records from original construction. the requirements of Seclion 5.2.2.4.
Steel components of buildings inelude columns, The carbon equivalent of the existing compo
beams, braces, connections, link beams, and nents shall be determined to establish weldability
diaphragms. Columns, beams. and braces may be built of the material, unless it is contirmed thal either the
up with plates, angles, and/or channels connected existing material conforms wilh a weldable material
together with rivets, bohs, or welds. The material used specitication or welding to existing components will
in older constructÍon is likely lo be mild steel with a not be performed as part of lhe rehabilitation. The
specified yield strength between 30 ksÍ and 36 ksi. welding procedures shall be determined based on the
Cast iron was often used for columns in much older chemistry of the base material and filler material as
construction, from before 1900 through the 1920s. specitied in Section 8 of AWS D 1.1 [American
Cast iron was gradually replaced by wrought iron and Welding Society (AWS) 2002]. Material conforming
then by steel. The connectors in older construction lo ASTM A36/A36M-04 (ASTM 2004), ASTM
were usually mild steel rivets or bolts. These were A242/A242M-03 (ASTM 2(03). ASTM A307-02
later replaced by high-strength bolts and welds. The (ASTM 2(02), ASTM A572/572M-04 (ASTM 2004),
seismic performance oí' lhese components will depend ASTM A913/A9J3M-Ol (ASTM 2001), ASTM
heavily on the condition 01' the in-place material. A A972/A972M-00 (ASTM 2000). and ASTM A9921
more detailed historieal perspective is given in Section A992M-04 (ASTM 2004) shall be deemed LO be
C5.2 ofFEMA 274 (FEMA 1997). weldable.
Great care should be exercised in selecting the
appropriate rehabilitation approaches and techniques 5.2.2./.2 Nominal Properties Nominal material prop
for application to historie buildings in order to pre erties specitled in the American lnstitute of Steel
serve their unique characteristÍcs. Construction (AlSC) Load and Resistance Factor
Design Specijication lar Structural Steel Buildings
S.2.2 Properties oC In-Place Materials and
(LRFD) (AISC 1999), or properties specified in con
Components
struction documents, shall be taken as lower-bound
material properties. Corresponding expected material
5.2.2.1 Material Properties properties shall be calculated by multiplying lower
oound values by an appropriate factor laken from
5.2.2././ General The following component and con
Table 5-3 to translate from lower-bound lo expected
nection material properties shall be obtained l'or the
values.
as-built strucLUre:
Where construction documenls indicate the ulti
l. Yield and tensile strength 01' the base material. mate tensile strength of weld metal, the lower-bound
2. Yield and tensile strength 01' the connection strength of welds shall be taken as indicated in
material. AWS DI.I (AWS 2(02). For construction predating
3. Carbon equivalem of the base and connection 1970, use 01' a nominal ulLimale tensile strenglh oí'
material. 60 ksi shall be permitted.
102
ASCElSEI41-06
C5.2.2.1 Material Properties lory lesting. Sampling shall take place in regíons
Mechanical properties of component and connec where the deereased seclion slrenglh due to the sam
lion material diclate lhe structural behavior of the pling remains higher Ihan the capacity required al the
component under load. Mechanical properties of redueed seelíon to resist the desígn loads. Alternately,
grealest inlerest inelude lhe expected and lower-bound where the reduced sectíon strength due to sampling
estimates of yield (Fye ) and tensile (F..) strengths of beeomes lower Ihan the required capacity, the losl sec
base and connection material, modulus of elasticily, tíon shaIl be temporarily supported and restored by
ductility, toughness, elongational characteristics, and repaies lO the section.
weldability. If a eonnector such as a boIt or rivet is removed
Expecled material propertics should be used for for testing, a comparable bolt shall be reinstalled at the
deformation-controllcd actions. Lower-bound material lime of sampling. Oestructive removal of a welded
properties should be used for force-controlled actions conneclion sample shall be accompanied by repair of
in Iieu 01' nominal strenglhs specitied in the Lnad and the connection.
Resistance Factor Design Specification for Structural Expected material properties shall be based on mean
Sleel Buildings (LRFD) (AISC 1999). test values. Lower-bound material properties shall be
based on mean tesl values minus one standard deviation,
except that where Ihe material is posilively idenlified as
5.2.2.2 CompOllellt Properties
eonforming lo a defined slandard material speciíication,
The following properties of components and lheir
lower-bound properties need not be taken less lhan Ihe
connections shall be obtained for the slruclure:
nominal properties for thal specification.
1. Sizc and thickness of connected materials, incIud
ing cover plates, bracing, and stiffeners;
C5.2.2.3 Test Melhods lo Quanlify Properties
2. Cross-seclional area, section moduli, moments 01'
FEMA 274 (FEMA 1997) provides information
inerlia, and lorsional properties of componenls al
and references for several test methods.
criticalsections;
Sampling should take place in regions where the
3. As-buih contiguration of intermediate, splice, and
calculated stresses (considering the lost section due to
end connections; and
sampling) fol' the applied loads is less than Ihe allow
-t Current physical condílion 01' base metal and con
able stress, where using allowable stress design
neClor materials, incIuding presence oí' deformation
(ASO), and less than the capacily where using load
and extent of deterioration.
and resistance factor design (LRFO).
()f greatesl ¡nteresl to steel building syslem per
Rcview of available construction documents shall
formance are the expected yield and tensile strength of
be performed lo identify primary vertical- and lateral
the instaIled materials. Notch toughness oí' structural
load-carrying eIemcnls and systems, critical compo
sleel and weld material is also important ror connee
nents and conneclions, and any moditications to com
tions thal undergo cyclic loadings and deformalions
ponents or overall configuration oí' the structure.
duríng earlhquakes. Chemical and metallurgical prop
In fue absence of deterioration, use of the nominal
erties can provide information on properties such as
cross-sectíonal dimensions 01' componenlS published by
compatibilily oí' welds wilh parenl melal and potenlial
the AISC, the American lron and Sleel Institute (AISI),
lameHar tearing due 10 through-thickness stresses.
and other approved trade associations shall be permitted.
VirlualIy aH sleel componenl elaslic and inelaslic limit
slates are relaled to yield and tensile strengths. Past
5.2.2.3 Test Methods to Quanlify Properties research and accumulation oí' data by industry groups
Laboratory tesling of samples to determine in-place have resulted in published material mechanieal peoper
mechanical properties of materials and components shaH ties for most primary metal S and thejr dale of fabrica
be performed in complíance with consensus standards lÍon. Section 5.2.2.5 provides default properties. This
published by ASTM, the American National Standards informalíon may be used, togelher wilh lests from
Institute (ANSI), and other approved organizations. recovered samples, lo rapid1y establísh expeeted
The extent of in-place materials tesling required strenglh properties ror use in component slrength and
lo determine material properties shall be based on lhe deformation analyses.
data colleetion requírements in Section 2.2.6. Review of olher properties derived from laboratory
The determination of material properties shall be tests, sueh as hardness, impact, fracture, and fatigue, is
accomplished Ihrough removal of samples and labora generally not needed for steel component capacity
103
SEISMIC REHABILITATION OF EXISTING BUILDINGS
determination, but may be required for archaic materi 01' steel materials for comprehensive data collection
als and connection evaluation. These properties shaU be based on [he following crÍleria:
may not be needed in the analysis phase if signiticant
rehabilítative measures are already known to be l. If original construction documents deíining mate
required. rial properties are inconclusive 01' do not exist, but
To quantify material properties and analyze the the date of conslruction is known and the materíal
performance of welded momenl conneclions, more used is contirmed lo be cal'bon sleel, al least
extensive sampling and testing may be necessary. This Ihree strenglh coupons and three bolts and rivels
testing may include base and weld material chemical shall be randomly removed fmm each component
and metallurgical evaluation, expected strength deter Iype.
mination, hardness, and Charpy V-notch testing of the 2. If no knowledge 01' the structural system and mate
heat-affected zone and neighboring base metal, and rials used exisls, at least two tensile strenglh
other tests depending on connection contiguration. coupons and lwo bolts and I'ivels shall be removed
Recommendatíons given in FEMA 351 (FEMA from each componenl type 1'01' every 1'our 1100rs or
2(00) may also be followetl lo selecl welding proce every 200,000 sI'. Ir il is determined from testing
dures ror welding of rehabilitative measures to existing that more than one material grade exists, additional
components. sampling and testing shall be pcr1'ormed untíl lhe
extent of each grade in componenl fabricatíon has
been established.
5.2.2.4 Mínimum Number 01 Tests
3. In the absence 01' conslruction recol'ds delining
Materials testing is not required if material proper
welding filler metals and pmcesses used, al
ties are available from original construction documents
leasl one weld metal sample rol' each componenl
Ihat indude material test records or material test reports.
type shall be obtained 1'or laboratory lesling.
If such properties difler rrom defauIt material properties
The sample shall consisl 01' both local base and
given in Tables 5-1 and 5-2, material properties for reha
weld metal lo determine composite slrength of
bilitation shall be selected such Ihal the largest tlemands
lhe connection.
on components and connections are generated.
4. For archaic materials, al least three strength
5.2.2.4. J Usual Testing The minimum number of tests coupons shall be extracted for each component
to determine the yield and tensile slrenglhs of steel type for every 1'our 1100l's or 200,000 sI' 01' COIl
materials for usual dala collection shall be based on slruction. Ir initial tests provide malerial proper
the following criteria: tíes thal are consistent wilh propcrties given in
Table 5-1, tests shall be required ror every six
tloors or 300,000 sr of construclion only. If
l. If design drawings are incomplele or not available,
these tests provide malerial propcrties thal are
at least one slrength coupon from each steel com
nonuniform, additional tests shall be performed
ponent type shall be removed for testing, and one
until the extent 01' differenl malerials is
weld metal sample fol' each component Iype shaIl
established.
be oblained for testing. The sample shall consist of
both local base and weld metal to determine com
posite strength 01' (he connection. For other material properties, a minimum of three
2. Ir design drawings containing ASTM specitication tesIs shall be conducted.
and material grade information are available, use of The results of any material lesting pcrformed shall
Table 5-2 to determine material properties shall be be compared lo lhe defauIt values in Tables 5-1 and
permitted wilhout additional testing. 5-2 1'or the particular era of building construction. The
3. If dcsign drawings containing material property amount of testing shall be doubled if the expectcd and
informatioll are available but the malerial properlies lower-bound yield and lensile stl'engths determined
are not listed in Table 5-2, use 01' nominal or speci from testing are lower Ihan the defauh values.
tied material properlies shall be permitted withoul
additional testing.
C5.2.2.4 Millimum Number 01 Tests
5.2.2.4.2 Comprehensive Testing The minimum num In order to quanlify expected strcnglh and olher
ber of tests to determine the yield and tensile strengths properties aceurately, a minimum number of tests
104
ASCE/SE) 41-06
IModified from unit stress values in Alse lron {lIId Steel Bwmsfrom 1873 to 1952 (AISe 1983).
lPropertíes based on tables of allowable loads as published in mili catalogs.
J05
SEISMIC REHABILlTATION OF EXISTING BUlLDINGS
106
AseE/SEI 41-06
Table 5-3. Factors to Translate Lower-Bound Steel Properties to Expected-Strength Steel Properties
107
SEISMIC REHABILlTATlON OF EXIS'ONG BUILDINGS
covering materials. Where required by Seclion 2.2.6, section properties shall be laken from design draw
lhe tol1owing shalJ be performed ror visual and com ings. lf sorne sectional malerial loss or deteriora
prehensive condition assessments: lion has OCClllTed, the loss shall be quantitled by
direct measurement and sectiol1 properties shall be
C5.2.3.2 Scope al/d Procedures reduced accordingly using principIes of structural
For sleel elements encased in concrete, it may be mechanics.
more cost-etTective lo provide an entírely new lateral
load-resísting syslem than undertaking a visual inspec 5.2.4 Knowledge Factor
tíon by removal of concrete encasement and repaír. A knowlcdge factor (K) ior computation of sleel
Physical condition oi' components and connectors componenl capacilies and permissible del'ormalions
may also dictate the use of certain destructive and shall be selected in accordance wilh Section 2.2.6.4
nondestructive test methods. lf steel elements are cov Wilh Ihe following additional requirements specitic to
ered by welI-bonded fireproofing materials or are steel components.
encased in durable concrete, it is likely thal Iheir con A knowledge factor of 0.75 shall be used if the
dition will be suitable. However, local removal of components and Iheir connecLors are composed of cast
these materials al conneclions should be performed as or wrought iron.
part 01' the assessment. The scope of this removal
effort is dictated by the component and element
design. For example, in a braced frame, exposure of 5.3 GENERAL ASSUMPTIONS AND
several key connections may suftice if the physical REQUIREMENTS
condition is acceptable and the contiguration matches
the design drawings. However, for moment frames, it 5.3.1 Stiffness
may be necessary to expose more connection points Component stitTnesses shall be calculated in
because of varying designs and the critical nature of accordance wilh Sections 5.4 through 5.10.
the conneclions. See FEMA 351 (FEMA 2000) for
inspection of welded moment trames. 5.3.2 Design Strengths and Acceptance Criteria
108
ASeE/SEl 41-06
\09
SEISMIC REHABILlTATION OF EXISTlNG BUILDlNGS
'Where nol indicaled othelwise, delinilion applies lo conneclions wilh bolted or welded web.
'Where not indicated otherwise, detinition applies lo connections wilh or wilhoul composile slab.
'Full-penetration welds between haunch or cover piUle 10 column j1ange COnfOlTIl to the requircmems oflhe AISC 341 Seismic ProrisiOfl.\)iJr
Slruclural Sleel Buihlíngs (A1SC 2002).
4Full-penelralion wclds conform 10 Ihe requiremems of Ihe AISC 341 Seismic Provisions for S/rIlclUral Slee/ BIIi/diflg~ (AISC 2002).
'For purposes of modcling, the conneclion muy be considered FR ir il meelS Ihe slrenglh and stiffness requil'ements of S.:ction 5.4.2.1.
110
ASCE/SEI41-06
ComponenllAction 10 LS CP LS CP
Beams- Flexure
b 52 h 418
a. ~S--and-S-- 2 6 8 10 12
2~ ~ Iw ~
b 65 h 640
b. ~;;>::--or-;;>::-- 1.25 2 3 3 4
21f ~ 1", ~
c. Other Linear interpolatio n between the values on Hnes a and b for bolh flange slenderness
(first term) and web slenderness (second term) shall be performed, and the lowest
resulting value shall be used.
Columns-Flexure 11,12
Por P/PCL < 0.2
b 52 h 300
a ~s--and-S-- 2 6 8 !O 12
211 ~ tw ~
b. !!L;;>:: ~or!!..;;>:: 460 1.25 1.25 2 2 3
21¡ ~ 1", ~
c. Other Linear interpolation between the values on lines a and b for both flange slenderness
(first term) and web slenderness (second term) shall be performed, and the lowest
resulting value shall be used.
Por 0.2 s P/PCL s 0.5
b 52 h 260
a ::1.s-- and - s - - 1.25
2~ ~ tw ~
b 65 h 400
b. ::1.;;>::--or-;;>::-- 1.25 1.25 1.5 2 2
21¡ ~ tw ~
c.Other Linear interpolatíon between the values on lines a and b for both tlange slenderness
(first term) and web slenderness (second term) shall be performed, and the lowest
resulting value shall be used.
Column Panel Zones-Shear 1.5 8 11 12 12
Pully Restrained Moment Connections l4
WUp4 LO 4.3 0.083d 3.9 - 0.043d 4.3 0.048d 5.5 0.064d
Bottom Haunch in WUF with Slab 2.3 2.7 3.4 3.8 4.7
Bouom Haunch in WUF without Slab 1.8 2.1 2.5 2.8 3.3
Welded Cover Plate in WUp3 3.9 0.059d 4.3 - 0.067d 5.4 - O.09Od 5.4 - 0.09Od 6.9 0.1l8d
13
Improved WUF-Bolted Web 2.0 0.016d 2.3 0.021d 3.1 - 0.032d 4.9 0.048d 6.2 - 0.065d
Improved WUF- Welded Web 3.1 4.2 5.3 5.3 6.7
J3
Free Flange 4.5 0.065d 6.3 - 0.098d 8.1 - 0.129d 8.4 - 0.129d 11.0 O,172d
13
Reduced Beam Section 3.5 0.016d 4.9 0.025d 6.2 - 0.032d 6.5 0.025d 8.4 0.032d
Welded F1ange Plates
a Flange Plate Net Section 2.5 3.3 4.1 5.7 7.3
b. Other Limit States Force-controlled
Welded Bottom Haunch 2.3 3.1 3.8 4.6 5.9
Welded Top and Bottom Haunch 2.4 3.1 3.9 4.7 6.0
Welded Cover-Plated Flanges 2.5 2.8 3.4 3.4 4.2
continued
111
SEISMIC REHABILlTATlON OF EXISTlNG BUILDINGS
112
ASCElSEI 41-06
Primary Secondary
ComponentlAction 10 LS CP LS CP
Kl ~ 4.2YE/Fy
r
1. W, 1, 2L in-plane I6 , 2C in-plane l6 1.25 6 8 7 9
2. 2L out-of-plane I6 , 2C out-of-plane '6 1.25 5 7 6 8
3. HSS, pipes, tubes 1.25 5 7 6 8
b. Stocky l5,17
KI:5 2,IYE/Fy
r
1, W, 1, 2L in-plane '6 , 2C in-plane '6 1,25 5 7 6 8
2, 2L out-of-plane I6 , 2C out-of-plane I6 1.25 4 6 5 7
3. HSS, pipes, tubes 1,25 4 6 5 7
c. Intermediate Linear interpolation between the values for slender and stocky braces (after
application of all applicable moditiers) shall be used.
Braces in Tension (except 1.25 6 8 8 10
EBF Braces)19
8earns, Columns in Tension 1.25 3 5 6 7
(except EBF Beams, Columns)
Steel Plate Shear WalIs 10 1.5 8 12 12 14
Diaphragm Components
Diaphragm Shear Yielding or Panel 1.25 2 3 2 3
or Plate Buckling
Diaphragm Chords and Collectors 1.25 6 8 6 8
FuI! Lateral Support
Diaphragm Chords and Collectors 1.25 2 3 2 3
limited Lateral Support
113
SElSMIC REHABILlTATION OF EXISTING BUILDlNGS
in the LSP and NSP. Where using the acceplance crite C5.4.2.1 General
ria of this section, the design professional should fol FEMA 351 (FEMA 2000) identifies two types of
low the procedures sel forth in Chapler 3 of lhis stan connections-Type 1 (ductile) and Type 2 (briUle).
dard without modification. The procedures in this stan These definitions are nol used in lhis standard since
dard and lhe SAC procedures are judged to resulL in the distinction is rellected in the acceptance crileria for
comparable levels of drift demando the connections.
Connections between the members shall be classi The most common beam-to-column conneclion
fied as fully restrained (FR) or partially reslrained used in steel FR moment frames since the late 1950s
(PR), based on the strength and stiffness of the con required the beam tlange to be welded ro the column
nection assembly. The conneclion lypeS and defini tlange using complete joint penetration groove we\ds.
tions contained in TabJe 5-4, as well as the acceptance Many of these connections have fractured during
criteria for lhese connections, has been adopted from recent earlhquakes. The design professional is referred
the referenced SAC documents, FEMA 350 (FEMA to FEMA 274 (FEMA 1997) and to FEMA 351
2000), 351 (FEMA 2000), 355D (FEMA 2000), and (FEMA 1997).
355F (FEMA 2000). The number of connections iden
titied is based on research that has shown behavior to 5.4.2.2 St(tfness
be highly dependent on connection detailing. The
design professional should refer to those guidelines 5.4.2.2. J Linear Static and Dynamic Pmcedures The
for more detailed descriptions 01' these connections stitlness of steel members (columns ano beams)
as well as a methodology for determining accepLance and connections (joints and panel zones used with
criteria for other connection lypes not included in the linear procedures of Chapter 3) shall be based
this standard. on principies of structural mechanics and as specified
FEMA 35 J (FEMA 2000) provides an alternate in the Load and Resístance Factor Design Speciji
methodology for determining column demands that catlonfor Structural Steel Buildings (LRFD)
has not been adopled into this standard. (AISC 1999) unless superseded by provisions of
this section.
5.4.2 Fully Restrained Moment Frames
l. Axial Area and Shear Area. For components
5.4.2.1 General fully encased in concrete, ca\culaLÍon of the stitIness
FR momenl frames shall be those moment using full composite action shall be permitted ir con
tl'ames with connections identitied as FR in fining reinforcement is provided lo allow the concrete
Table 5-4. to remain in place during an earthquake. Concrete
Moment frames with connections not included in conlined on al least three sides, or over 75% 01' its
Table 5-4 shall be detined as FR if the joint deforma perimeter, by elements of the structural steel member
tions (nol including panel zone deformation) do not shall be permitted to be considered adequarely con
contribute more than 10% to the lotallaleral detlection tined to provide composite acrion.
of the frame, and lhe connection is at least as strong as 2. Moment of Inertia. For components fully
the weaker of the two members being joined. Ir either encased in concrete, calculation of the stitIness using
oí' these conditions is not satistied, lhe trame shall be fulJ composite action shall be permitted, bUI the width
characterized as PR. of the composite section shaJl be taken as equal ro lhe
FR moment frames encompassboth Special width oi' Ihe tlanges 01' the steel member and shall nol
Moment Frames and Ordinary Momenl Frames, inelude parts oí' the adjoining concrete tloor slab,
detined in AISC 341 (AISC 2002). These terms are unless there is an identitiable shear transfer mecha
not used in lhis standard, bUl the requirements for nism between lhe concrete slab and the steel tlange
these systems and for general or seismic design of which is shown to meet the applicable acceptance cri
steel componentks specitied in Load alld Resistance teria for the selected performance level.
Factor Design Specijication for Structural Steel 3. Panel Zone Modeling. Inclusion of panel zone
Buildings (LRFD) (AISC 1999) or ASCE 7 (ASCE tlexibility shall be pernJitted in a frame analysis by
2005) shall be followed for new elements designed as adding a panel zone element to the mathematical
part of the seismic rehabilitation, unless superseded model. Alternatively, adjustment of rhe beam flexural
by provisions in this standard. stitIness lo account for panel zone tlexibility shall be
114
ASCE/SEI41-06
permitted. Where lhe expecled shear slrenglh of panel In Iieu of relationships derived from experiment
zones exceeds the flexural strength of lhe heams al a or analysís, lhe generalized load-deformatíon curve
beam-<:olumn conneclion, and lhe stiffness of the shown in Fig. 5-1, with parameters a, b, and e as
panel zone is at least 10 times larger than lhe flexural defined in Tables 5-6 and 5-7, shall be used for com
stiffness of lhe heam, direcl modeling of the panel ponents 01' steel moment frames. Moditicalion of
zone shall not be required. In such cases, rigid this curve shall be permitted lo account for slraín
offsets from the cenler of the column shall be permit hardening of components as follows: (1) a strain
ted to represent lhe ef1'ective span of the beam. Use hardening sJope of 3% of the elastic slope shall he
of center-Iine analysis shall be permitted for other permítted for heams and columns unless a greater
cases. strain-hardening slope is justitied by test dala; and
4. Joint Modeling. Modeling of connectíon stiff (2) where panel zone yielding occurs, a slrain
ness for FR moment frames shall nOI be required hardening slope of 6% shall be used for lhe panel
excepl for joinls Ihal are intenlionally reinforced lo zone unless a greater strain-hardening slope is
force formalion of plaslic hinges within lhe beam justified by tesl data.
span, remote from the column faee. For sueh joinls, The parameters Q and Qy in Fig. 5-1 are general
rigid elements shall he used helween the eolumn ized component load and generalized component
and the beam lO represenl lhe efteclive span 01' the expected slrength, respectively. For heams and
heam. columns, Ois the total eJastic and plaslic rotation of
5. Connections. Requirements 01' lhis section the beam or column, O, is Ihe rotation al yield, .1 is
shall apply lo eonneelions idenlitied as FR in total elastic and plastic displacement, and .1, is yield
Table 5-4 and lhose meeting lhe requirements 01' displacernent. For panel zones, Oy is the angular shear
Seclion 5.4.2. J • detormation in radians. Figure 5-2 defines chord rota
tion for heams. The chord rotation shall be calculated
either by adding lhe yield rotalÍon, O" lo Ihe plastic
5.4.2.2.2 Nonlinear Static Procedure If lhe Nonlinear
rotation or laken lo he equal to the story drift. Use of
StatÍC Proeedure (NSP) of Chapter 3 is used, the fol
Eqs. 5-1 and 5-2 shall he permitted lO calculate lhe
lowing eriteria shall apply:
yield rolalÍon, O..' where Ihe point of contratlexure is
anticípated to oecur at Ihe mid-Iength of the beam or
l. Elastie eomponent properties shall he modeled as
colurnn, respeclÍvely.
specified in Seclion 5.4.2.2.1;
") Plastification shall be represenled by non linear
moment-eurvalure and interaetion relationships for
beams and beam-<:olumns derived from experiment
or analysis; and
3. Linear or nonlinear behavior of panel zones shall
he included in the malhematical model except as
indicated in Section 5.4.2.2.1, Ilem 3.
() or Li
FIGURE S-l. Generalized Force-Deformation
Relation for Steel Elements or Components.
lb) F~~~~~~~::------Y--
FIGURE 5-2. Definition of Cbord Rotation.
lIS
SEISMIC REHABILlTATION OF EXISTlNG BUILDlNGS
Table 5-6. Modeling Parameters and Acceptance Criteria for Nonlinear Procedures
Structural Steel Components
Modeling Parameters
Acceptance Criteria 14
Residual
PIastic Rolalion Angle, Radians
Plastic Rotation Angle, Strength
Radians Ralio Primary Secondary
Componen tiAction II b c 10 LS CP LS CP
Beams - flexure
116
ASeE/SE! 41-06
Modeling Paramelers
Acceptance Criteria 14
Residual
Plastic Rotation Angle. Radians
Plastic Rotalíon Angle. Strength
Radians Ratio Primary Secondary
Component/Action a b e 10 LS CP LS CP
Welded Top and Bottom 0.028 0.048 0.2 0.014 0.0213 0.0280 0.0360 0.048
Haunches
Welded Cover-Plated 0.031 0.031 0.2 0.016 0.0177 0.0236 0.0233 0.031
Aangcs
Partially Restrained Moment Connections
Top and Bottom Clip Angle9
a. Shear Failure of Rivet oc 0.036 0.048 0.200 0.008 0.020 0.030 0.030 0.040
Bolt (Limit State 1)&
b. Tension Failure ofO.012 0.018 0.800 0.003 0.008 0.010 0.010 0.015
Horizontal Leg of Angle
(Limit State 2)
c. Tension Failure of Rivet 0.016 0.025 1.000 0.005 0.008 0.013 0.020 0.020
or Bolt (Limit State 3)8
d. F1exural Failure of Angle 0.042 0.084 0.200 omo 0.025 0.035 0.035 0.070
(Limit State 4)
Double Split Tee9
a. Shear Failure of Rivet or 0.036 0.048 0.200 0.008 0.020 0.030 0.030 0.040
Bolt (Limit State 1)8
b. Tcnsion Failure of Rivet 0.016 0.024 0.800 0.005 0.008 0.013 0.020 0.020
oc Bolt (Limit State 2)8
C. Tension Failure of Split 0.012 0.018 0.800 0.003 0.008 0.010 0.010 0.015
Tee Stem (Limit State 3)
d. FlexuraJ Failure of Split 0.042 0.084 0.200 0.010 0.025 0.035 0.035 0.070
Tee (Limit State 4)
Bolted Flange Plate9
a. Failuce in Net Section of 0.030 0.030 0.800 0.008 0.020 0.025 0.020 0.025
F1ange Plate oc Shear
Faílure ol' Bolts oc Rivets"
b. Weld Failure oc Tension 0.012 0.018 0.800 0.003 0.008 0.010 0.010 0.015
Failure on Gross Section
ofPlate
Bolle<! End Plate
a. Yield of End Plate 0.042 0.042 0.800 0.010 0.028 0.035 0.035 0.035
b. Yield of Bolts 0.018 0.024 0.800 0,008 0.010 0.015 0.020 0.020
c. Failure ol' Weld 0.012 0.018 0.800 0.003 0.008 0.010 0,015 0,015
Composite Top Clip Angle Bottom9
a. Failure of Deek 0.018 0.035 0.800 0.005 0.010 0.015 0.020 0.030
Reinforcement
b. Local F1ange Yielding and 0.036 0.042 0.400 0.008 0.020 0.030 0,025 0.035
Web Crippling of Column
c. Yield of Bottom F1ange 0.036 0.042 0.200 0,008 0.020 0.030 0.025 0,035
Angle
d. Tensile Yield ol' Rivets or 0.015 0.022 0.800 0.005 0.008 0.013 0.013 0.018
Bolts at Column F1ange
e. Shear Yíeld of Beanl 0.022 0,027 0,200 0.005 0.013 0.018 0.018 0.023
Aange Connection
Sbear Conneeúon wilh 0.029 - O.0(~)2Od" 0.15 - O.O(J36<1" 0.400 0.014 - ().0!~J10d" 0.1125 O.OO21d" 0.15 - 0.0036<1"
Slab 12
Sbear Conneelion (US· 0.0036<1" 0.15 - OJlO36<1" 0.400 OJJ75 0.001ild" O.1l2S • O,0027d" 0.15 - O.IJ036<1"
witoout Slab12
Continued
117
SElSMIC REHABILITATION OF EXISTING BUILDINGS
'Values are for shear walls wíth stiffeners to preven! shear buekling.
'Columns in moment or braccd frames shall be permítted 10 be desígned for the maximum force delivered by connecling mcmbers. For rectangular
or square columns, replace b¡/2t¡ with bit, replace 52 with 110, and replace 65 with 190.
3Plastic rotalion II (1 5/3 pi Pu) O"
4Plastic rotation 17 (1 5/3 PI Po) O,..
5Plastíc rotation 8 (1 - 5/3 PIPelJ By.
6Plastic rotation 14 (1 - 5/3 PI PClJ 8).
7Columns witli PIPn . > 0.5 shall be eonsidered force-controlled.
"For high-strength bolts, divide values by 2.0.
"Web plate or stiftimed seal shall be considered to carry shear, WithoUl shear conneClion, aclion shall nol be c1assified as secondary, If beam depth,
d. > 18 in" multiply m-faetors by l8ldo'
IUDeformation is the rotation angle between link and beam oulside link or column,
uValues are for link beams with Ihree or more web stiffeners, If no stiffeners, divide values by 2.0. Linear interpolatíon shall be used for one or
two stiffeners.
lld is the beam depth; d•• ís the depth of ¡he boh group, Where plastic rotations are a funetion of d 01' dogo they need nOl be ¡aken as less than 0.0.
BTabuJated values shall be modified as índicated in Section 5.4.2.4.3, hem 4.
'·Primary and secondary componen! demands shall be wilhin seeondary componen! acceptance criteria where the full backbone curve is explicitly
modeled including strength degradation and residual strength in aecordance with Seetíon 3.4.3.2.
118
ASCElSEl41-06
Table 5-7. Modeling Paramerers andAcceptance Criteria for Nonlinear Procedures-Struciural Steel
Components-Axial Actions
Modeling Parameters
Acceptance Criteria6
Residual
Plastic Deformation
Strength
Plastic Deformatian Ratio Primary Secondary
ComponentJ Action a b e 10 LS CP LS CP
Braces in Compression (except EBF braces)I,2
a. Slender
Kl
2: 4.2v'E/F),
r
L W, 1, 2L In-Planel, 2C In-Plane J 0.5d< JOde 0.3 0.25d, Me Sd, Sd, IOd,
2. 2L Out-of-Plane3, 2C Out-of-Plane3 0.5d, 9d, 0.3 0.25d, 5de 7de 7de 9d c
3. HSS, Pipes, Thbes 0.5d o 9de 0.3 0.25d e 5d, 7d c 7d, 9dc
b. Stocky4
Kl
2,Iv'E/F)'
r
1. W, 1, 2L In-Plane\ 2C In-Plane l ld e 8de 0,5 0.25d, 5de 7de 7de SIle
2. 2L Out-of-Planel, 2C Out-of-Plane 1 lde 7d c 0.5 0.25dc 4d c 6dc 6dc 7d,
3. HSS, Pipes, Tubes lde 7dc 0,5 0,25de 4d c 6dc 6dc 7d c
c. Intermediate Linear interpolatíon between the values for slender and stocky braces (after
application of all applicable modifiers) shall be used.
Broces in Tension (except EBF braces)5 lld T 14d T 0.8 0,25d¡ 7d T 9d T lld T 13d T
Beams, Columns in Tension (except 5d T 7dT l.0 O.25d T 3d T 5d T 6d T 7d T
EBF beams, columns)5
"Primary and secondary component demands sball be witbin secondary component acceptance critería wberc lbe full backbooe curve is explicitly
IOOdeled inc1uding slrength degradation and residual slrength in aceordance witb Section 3.4.3.2.
119
SE1SMIC REHABILlTATION OF EXISTING BUILDlNGS
120
ASCFJSEI 41-06
121
SElSMIC REHABILlTATION OF EXISTING BUILDINGS
122
ASCE!JSEI 41-06
Plexural strength shall be calculated in accordance m-factors in Table 5-5 shall be modified as determined
with AISC 341 (AISC 2(02), taking ~ = 1.0 and by the following four conditions. The moditications
using the lower-bound value for yield strength. shall be cumulative, but m-faetors need not be taken as
Por columns under combined compression and less than 1.0.
bending, lateral bracing to prevent torsional buekling
shall be provided as required by the Load and 4.1 If lhe conneclion does nol satisfy al least one of
Resistance Factor Design Specification for Structural the following eonditions, the tabulated m-factors in
Steel Buildings (LRFD) (AISC 1999). Table 5-5 shall be multiplied by 0.8.
Steel columns under axial tension shall be consid
ered deformation-controIled and shalI be evaluated
!!.J?L
using Eq. 3-20. 5.2
Steel eolumns under eombined axial tension
and bending stress shalI be eonsidered deformation or
controlled and shall be evaluated using Eq. 5-13:
T Mx Mr
!!.!1.
7 ::.s; te! < !!.J?L .. .h !.l!t.
5.2 and contlnmty plates Wlt t ~ 2
-- + + :::; 1.0 (Eq.5-13)
m,TCE mxMCEx myMCEY
where or
123
SEISMIC REHABILlTATION OF EXISTING BUILDINGS
4.3 If the clear span-to-depth ratio, Le/d, is greater The panel zone modifier is based on research in
than 10, the tabulated m-factors in Table 5-5 shall be FEMA 355F indicating that connection performance is
multiplied by: less ductile where the slrength of the panel zone is either
too great or too small compared to the flexural strength
of the beam. The panel zone strength range between
1.4 - 0.04 d 60%-90% of the beam strength is considered to provide
balanced yielding between the beam and panel zone,
where which results in more desirable performance.
Le = lenglh 01' beam, clear span between columns; and The clear span-to-deplh ratio moditier for linear
d = depth 01' member. acceptance criteria reHects the dccreased apparent duc
tility that arises due to increased elastic rotations for
4.4 If the beam flange and web meetthe following longer beams. The decreased plastic rotalÍon capacity
conditions, the tabulated m-factors in Table 5-5 need of beams with very small Lc/d ralÍos is not retlected
not be modified for tlange and web slenderness. directly. However, the moditier for linear criteria was
developed so that it would be appropriate for the pre
dominant case of Lc/d ratios greater than about 5.
!!L < 52 and
h 418
<- The beam Hange and web slenderness moditier is
21¡ tw Vii;. based on the same modifications to beam acceptance
criteria contained in Table 5-5. While not an aspect 01'
H the beam flange or web slenderness values the connection itself, beam l1ange and web slenderness
exceed either of the following limits, lhe tabulated affect the behavior 01' the connection assembly.
m-factors in Table 5-5 shall be muhiplied by 0.5. Type FR connections designed to promote yield
ing 01' the beam in the span, remote from the column
face, are discussed in FEMA 350 (FEMA 2000).
124
ASCFJSEI 41-06
(o.5i(8 - Ljá¡/3J
-u If the conneetion does not satisfy at least one of
lile following eonditions, the tabulated plastic rotation
Le = length of beam, dear span between columns;
in Tables 5-6 and 5-7 shall be multiplied by 0.8.
and
d = depth of member.
t. >
el - 5.2
4.4 If the beam flange and web meet the following
or eonditions, the tabulated plastic rotations in Tables 5-6
and 5-7 need not be modified foe flange and web
slenderness.
~
:S.: t el < !:!.J?L and contlllUlty
.. . lbf
pIates wlth 1 2:
7 5.2 2
!!.L <~ and
h
<
418
or 2t¡ ~
125
SEISM le REHABILlTATlON OF EXISTING BUILDlNGS
e5.4.2.4.3 Nonlinear Static and Dynamic Procedures and masonry shear walls shall be as speeified in
FR Beam-Column Connections. The conlinuity plale Sections 6.8 and 7.4, respeclively. The attributes
modit'ier is based on recommendalions in FEMA 355F and design requirements of concrete and masonry
(FEMA 2000) for continuity plale delailing in relalion intills shall be as specified in Sections 6.7 and 7.5,
ship lo column tlange Ihickness. respectively. The local ion of added walls should be
The panel zone moditier is based on research in selected so as not to increase horizontal lorsion in
FEMA 355F indicating that connection performance is the system;
less ductile where Ihe strength 01' the panel zone is 3. Attach new steel frames to Ihe exterior of the build
eilher too great or loo small compared lo the flexural ing. The rehabilitated slruclure should be checked
strenglh ol' the beam. The panel zone slrength range for the effects 01' the change in Ihe distribution of
between 60% and 90% of lhe beam strenglh is consid stilTness, the seismic load path, and the connections
ered lo provide balanced yielding belween lhe beam between the new and existing frames. The rehabili
and panel zone, which results in more desirable per tation scheme 01' attaching new steel frames lo the
formance. exterior 01' Ihe building has been used in the past
The c1ear span-to-deplh ratio modilier l'or nonlin and has becn shown lo be very etfective under cer
ear modeling and acceplance criteria retlects decreased tain conditions. This rehabililation approach may
plaslic rOlalion capacity for beams with hinging OCCUf be structurally efticient, bUI il changes the architec
ring over a shorter length. This moditier is based on lural appearance of Ihe building. The advantage is
Ihe plastic rotation capacities corresponding lo the that the rehabilitation may take place without dis
FEMA 350 (FEMA 2000) LJd limils of 5 and 8. rupting the use of Ihe building;
The beam tlange and web slenderness moditier is 4. Reinforce moment-resisting connections to force
based on the same moditications to beam acceptance plastic hinge locations in the beam material away
crileria contained in Tables 5-6 and 5-7. While nol an from Ihe joint region lo reduce the stresses in the
aspect ol' the connectíon itseU, beam tlange and web welded connection, Ihereby reducing the possibility
slenderness affects the behavior of the connection of briule fractures. This scheme should nOl be used
assembly. if the full-pen connection of [he existing structure
Type FR connections designed lo promole yicld did not use weld material 01' sufficient toughness to
ing ol' the beam in lhe span, remote ti'om the column avoid fracture at stresses lower than yield 01' where
face, are discussed in FEMA 350. strain-hardening al the new hinge location would
produce larger stresses than the existing ones at the
5.4.2.5 Rehabilitation Measures weld. The rehabilítation measures lo reinforce
FR momenl frame componenls lhal do not meet seleeted moment-resisting connections shall eonsist
lhe acceptance criteria for Ihe selected Rehabilitation of providing horizontal cover plates, vertical stiff
Objective shall be rehabilitated. Rehabililation meas eners, or haunches. Removal 01' beam material to
ures shall meel the requirements 01' Section 5.3.3 and force the plastic hinge ¡nto the beam and away
other provisions of this standard. from the joint region shall also be permitted subject
to lhe aboye restrictions. Guidance on lhe design of
these modifications of FR momenl connections is
C5.4.2.5 Rehabilitation Measures
discussed in FEMA 351 (FEMA 2000);
The following measures, which are presented in
5. Add energy dissipation devices as specitied in
greater detail in FEMA 351 (FEMA 2000), may be
Chapter 9; and
effective in rehabilitating FR moment frames:
6. lncrease lhe strength and sliffness of existing
]. Add steel braces to one or more bays of each story frames by welding sleel plates or shapes lo seleeled
lo form concenlric or eccentric braced frames to members.
increase Ihe stiffness of the frames. The aUributes
and design criteriá 1'or braced frames shall be as 5.4.3 Partially Restrained Moment Frames
specified in Section 5.5. The location of added
braces should be selected so as to nOI ¡ncrease 5.4.3.1 General
horizonlal torsíon in the system; PR momenl frames shall be defined as those
2. Add ductiJe concrele 01' masonry shear walls or moment frames with connections identitied as PR in
infill walls lo one or more bays of each slOry lO Table 5-4. Moment trames with conneclions not
¡ncrease the stíffness and strength of the structure. included in Table 5-4 shall be defined as PR if the
The attributes and design requirements of concrete deformations 01' the beam-to-column joints contribute
126
ASeE/SEI4]-06
greater than 10% to the total lateral deflection of Ihe l. PR connections encased in concrete, where the
frame or where the strength of Lhe connecLions is less nominal resistance, MeE' delermined l'or lhe con
Ihan Ihe strenglh of the weaker of the two members nection shall inelude the composile action provided
being joined. For a PR connection with two or more by the concrete encasement;
faiJure modes, Ihe weakest failure mechanism shall be 2. PR connections encased in masonry, where com
considered to govern the behavior of thc joint. Design posite aclion shall not be ineluded in lhe delermina
provisions for PR frames specified in AISC 341 (AISC tion 01' conneclion resislance, MeE; and
2002) or ASCE 7 (ASCE 2005) shall apply unless 3. Bare steel PR connections.
superseded by the provísions in Ihis standard.
Equatíons for calculating nominal design strength shall For PR conneclions not lisled aboye, Ihe rOla
be used for determining Ihe expected strength, except tional spring stift'ness shall be calculaled in accordance
f = 1, and either Ihe expected strenglh or lower-bound with Eq. 5-16:
strenglh shall be used in place ol' Fy , as l'urlher indi
caled in Ihis standard.
(Eq.5-16)
0.003
e5.4.3.l General
Table 5-4 ineludes simple shear or pinned connec As a simplified aIternalive, modeJing lhe l'rame as
lions e1assified as PR connections. Although Ihe grav for FR joints bUI Wilh the beam stiffness, E/ú ' adjusted
¡IY load-carrying beams and columns are lypically lo account for Ihe tlexibility of Ihe joints in accor
neglecLed in Ihe laleral analysis of steel moment frame dance with Eq. 5-17 shall be permilled:
slruclures, SAC research contained in FEMA 355D
(FEMA 2000) índicates thal these connections are
Elbadjusted (Eq.5-17)
capable of contributing non-negligible stiffness 6h I
through very large drifl demands. Including gravily --+
L~K6 E/v
load-carryíng elemenls (subject to the modeling proce
dures and acceplance crileria in Ihis section) in lhe where
malhemalical model could be used by lhe design engi K6 equivalent rotational spring sliffness of connec
neer lo reduce Ihe demands on Ihe momen! frame ele tion per Eq. 5-15 or 5-16;
ments. MeE expected moment strenglh;
/b moment of inertia of lhe beam;
5.4.3.2 Stiffness E modulus of e1asticity;
h = average story heighl of the columns; and
5.4.3.2.1 Linear Static and Dynamic Procedures Lú = centerline span ol' Ihe beam.
l. Beams, columns, and panel zones. Axial area,
shear area, momenl of inertia, and panel zone Where Eq. 5-17 is used, lhe adjusted beam stiff
stiffness shall be determined as specitied in Sec ness shaJl be used in standard rigid-conneclion frame
tion 5.4.2.2 for FR frames. analysis and lhe rotation of lhe conneclion shall be
") Connections. The rolalional stiflness K 6 ol' each laken as the rotalion of the beam at the joinl.
PR connection l'or use in PR frame analysis shalI
be determined by Ihe procedure 01' Ihis seclion, by C5.4.3.2.1 Linear Static and Dynamic Procedures
experimenl, or by an approved ralional analysis. FEMA 274 (FEMA 1997) is a useful reference for
The deformalion of lhe conneclion shall be information concerning sliffness properlies and model
included where calculaling frame displacements. ing guidelines for PR connections.
The rotational spring stiffness, K 8' shall be cal
culaled in accordance wÍlh Eq. 5-15:
5.4.3.2.2 Nonlinear Static Procedure If the Nonlinear
Stalic Procedure (NSP) of Chapter 3 is used, Ihe fol
K MeE
=-- (Eq.5-15) lowing criteria shall apply:
6 0.005
l. The elaslÍc component properties shall be modeled
where
as specified in Section 5.4.3.2.1;
MeE = expected moment strength of connection for 2. The nonlinear moment-curvature or load
lhe 1'ollowing PR connections: deformation behavior for beams, beam-columns,
127
SEISMIC REHABILlTATlON OF EXISTING BUILDlNGS
128
ASeE/SEI 41-06
where
Fre = expected yield strength of the angle;
F" = expected tensile strength of the angle;
A. = effective net area of the horizontal leg;
Ag gross area of the horizontal leg; and
t" = thickness of angle.
1.3 Limit State 3. If the tensile capacity of lhe rivets
or boIts attaching the vertical oUlslanding leg to the
column tlange controls the capacity of the connec
tion, QCE shall be computed in accordance with
Eq.5-22:
(Eq.5-22)
FIGURE 5-4. Double Split Tee Connection.
where
Ab = gross area of rivet or bolt;
bu dimension in Fig. 5-3; where
F.. expecled tensile strength of the bolts or rivets;
and db overall beam depth;
Nb = least number of boIts or rivels connecting top or bt distance between one row of fasteners in the
bottom angle to column flange. split lee tlange and the centerline of the stem as
shown in Fig. 5-4;
1.4 Limit State 4. If lhe flexural yielding 01' Ihe flange t, = thickness of the split tee stem;
angles control s the capacity 01' the connection, QCE F" = expected tensile strength of the bolts or rivets;
shall be given by Eq. 5-23: Ab = gross area of rivet or bolt; and
Nb number of fasteners in tensíon connectíng
the t1anges of one split tee to lhe column
(Eq.5-23) tlange.
2. Double Split Tee Connection. The moment 2.4 Limit State 4. If flexural yielding of the tlanges
strenglh, MCE. of the double split tee (T-stub) con of the split tee control s the capacity of the connec
nection. as shown in Fig. 5-4, shall be the smallest tion, QCE shall be determined in accordance with
value 01' M CE computed for the following four limit Eq.5-25:
states:
129
SErSMIC REHABILlTATlON OF EXISTlNG BUlLDlNGS
(Eq.5-26)
/ L~
~ ....
where
1'0
PCE = expected strength of the flange plate connection O
as governed by the net section 01' the flange O
plate, the shear capacíty of the bolts, or the Ir: __
strength of the welds to the column flange;
tI' = thickness of flange plate; and
db = overall beam depth.
FIGURE 5·5. Bolted Flange Plate Connection.
4. Bolted End Plate Connections. Bolted end
plate connections, as shown in Fig. 5-6, shaJl be con
sidered FR if their expected and lower-bound strengths
equal or exceed the expected strength of the conneeL
ing beam. The lower-bound strength, QCL Me¿, shall
be the vaIue determined for the Iimit state of the bolts
under combined shear and tension and lhe expected
strength, QCE MeE' shaIl be determined for the limit
state of bending in the end pIate caleulated in aecor
dance with the procedures of the Load and Resistance
Factor Design Specification for Structural Steel
Buildings (LRFD) (AISC 1999) or by another proce
dure approved by the authority having jurisdiction.
5. Composite Partially Restrained Connections.
Strength and deformation aceeptance criteria of com
posite partially restrained connections shall be based
on approved rational analysis procedures and experi
mental evidence.
FIGURE 5·6. Bolted End Plate Connection.
5.4.3.3.3 NOfllinear Static Procedure The complete
load-deformation relalionship of each component as
depicted by Fig. 5-1 shall be determined in accordance
with Section 5.4.2.2.2. The values for expected strength,
QeE' of PR connections shalI be the same as those used 5.4.3.4 Acceptance Criteria
for linear procedures as specified in Section 5.4.3.3.2.
5.4.3.4.1 General Component acceptance criteria shall
5.4.3.3.4 Nonlinear Dynamie Procedure The complete be computed in accordance with the general require
hysteretíc behavior of each component shall be deter ments of Section 5.3.2 and lhe specitic requirements
mined experimentally or by other procedures approved of rhis section.
by the authority having jurisdiction.
C5.4.3.4.1 GeneraL The strength and behavior of PR
C5.4.3.3.4 Nonlinear Dynamic Procedure FEMA steel moment-resisting trames is typically govcrned by
355D (FEMA 2000) is a useful reference for informa the connections. The design professional is urged to
tion concerning nonlinear behavior of various tested consider the acceptance criteria for the mechanism that
connection contigurations. controls the system.
130
ASCElSEI41-06
5.4.3.4.2 Linear Sta tic and Dynamic PlVcedures braces, and connections. Eccentric braced frames shall
Design actions shall be eompared with design also inelude link beam eomponents.
strenglhs in accordance wilh Section 3.4.2. The
m-1'actors roe sleel components and eonneclions 01' PR C5.5.1 General
feames shall be selected from Table 5-5. Limil states Steel beaced rrames act as vertical trusses where
for which no m-faclors are provided in Table 5-5 shall the columns are the chords and the beams and braees
be considered force-controlled. are the web members.
Acceptance eriteria 1'or steel beams and columns Components can be either bare steel, steel with a
in PR 1'l'ames shall be compuled in accordance Wilh nonstructural coating roe fire protection, or steel with
Section 5.4.2.4.2. concrete or masonry encasement.
131
SEISMIC REHABILITATION OF EXISTING BUILDINGS
which accurs al painl B in the curve in Fig. 5-1. of the brace, including gusset plates, and Ihe effective
The reduction in strenglh al' abrace after buckling length shal1 be laken as 0.8 times the totallength for
shall be included in the madel. Modeling 01' the in-plane buckling and 1.0 limes the total lenglh fol'
compression brace behavior using elaslo-plaslic out-of-plane buckling.
behavior shall be permitted iI' the yield force is The expected strength, QCE' of steel braces in tcn
assumed as the residual strength after buckling, as sion shall be calculated as for columns, in accordancc
detined by parameter e in Fig. 5-1 and Tables 5-6 with Section 5.4.2.3.2.
and 5-7. Implications of forces higher lhan this Expected, QCE' and lower-bound, QCL' strengths of
lower-bound force shall be evaluated relative lo beams and columns shall be calculated as fol' FR
other components to which the brace is connected. beams and columns in Section 5.4.2.3. Strength 01'
For braces in tension, the parameter Dr shall be the beams wilh axial load that exceeds 10% 01' the axial
axial deformation at development 01' the expected strength shall be as ca1culated for FR columns.
tensile yield load in the brace, which occurs at The lower-bound strength 01' brace connections
point B in the curve in Fig. 5-1. shall be calculated in accordance with the Load and
Resistance Factor Design Specificatioll for Structural
C5.5. 2. 2.2 Nonlinear Static Procedure FEMA 274 Steel Buildings (LRFD) (AISC 1999), taking tP 1.0
(FEMA 1997) is a userul reference ror information and using the lower-bound yicld strength, FrL[J' for
regarding nonlinear load-deformatían behavior of yield slrength.
braces.
5.5.2.3.3 Nonlinear Static Procedure In lieu 01' rela
5.5.2.2.3 Nonlinear Dynamic Procedure The complete lionships derived by experiment 01' analysis, lhe com
hysteretic behavior of each component shall be based plete load-dcformation behavior ol' each componen! as
on experiment or other approved method. depicted by Fig. 5-1 shall be dctermined in accordance
with Seclion 5.4.2.2.2. The values fol' expected
C5.5.2.2.3 Nonlinear Dynamic Procedure FEMA 274 strength, QCE' shall as specified in Seclion 5.5.2.3.2 ror
(FEMA 1997) is a useful reference for information linear procedurcs.
concerning hysteretic behavior of braced ffame
components. 5.5.2.3.4 Nonlinear Dynamic Procedure The complete
hystere!ic behavior 01' each component shall be deter
5.5.2.3 Strength mined experimentally or by other procedures approved
by the aUlhority having jurisdiction.
5.5.2.3.1 General Component strengths shall be com
puted in accordance with the general requirements C5.5.2.3.4 Nonlinear Dynamic Procedure FEMA 274
of Section 5.3.2 and the specílic requirements 01' this (FEMA 1997) is a use fuI reference roe information
section. concerning hysteretic behavior of braced ffame com
ponents.
5.5.2.3.2 Linear Static and Dynamic Procedures The
expected strength, QCE' of steel braces under axial 5.5.2.4 Acceptance Criteria
compression shall be the lowest value obtained ror the
limit states of component buckling or local buckling. 5.5.2.4.1 General Component acceptance criteria shall
The effective design strength, PCE' shall be calculated be computed in accordance with the general require
in accordance with Load and Resistance Factor ments ol' Section 5.3.2 and the specitic requirements
Design Specification for Structural Steel Buildings ol' this section.
(LRFD) (AISC 1999), taking tP 1.0 and using the Axial tension and compression in braces shall be
expected yield strength, F" , for yield strength. considered del'ormation-controllcd. Actions on beams
For common cross-bracing contígurations where and columns with non-ncgligible axial load shall be
both braces cross at their midpoinls and are attached to considered f9rce- or deformalion-controlled as dcter
a common gusset plate, lhe el'fective length of each mined for FR rrame columns in Section 5.4.2.4.
brace shall be taken as 0.5 limes the total length of the Compression, tension, shear, and bending actions on
brace, including gusset plates for both axes of buck brace connections including gusset plates, bolts,
ling. For other bracing contigurations (chevron, V, sin welds, and other connectors shall be considered
gle brace), the length shall be taken as the totallength force-controlled.
132
ASCFlSEI 41-06
5.5.2.4.2 Linear Static and Dynamie Proeedures and PR momenl trames and concenlric braced frames.
Design aClions shall be compared wilh design The load-deformaLion model for a link beam shall
slrenglhs in accordance wilh Seclion 3.4.2. The inelude shear deformation and tlexural detormation.
m-faclors for sleel components shall be selecled The elaslíc stiffness 01' Ihe link beam, K" shall be
from Table 5-5. computed in accordance with Eq. 5-27:
Beams in chevron braced frames shall be evalu
aled as force-conlrolled aclions 10 resisl the unbal
(Eq.5-27)
anced load eftecls in combinalion wilh gravily loads
in accordance wilh Section 3.2.8. The unbalanced
load effects shall be calculated using Ihe expected where
yield capacÍly 01' lhe brace in lension and 30% 01'
the expecled compression capacity of lhe brace in
compression. (Eq.5-28)
e
133
SEISMIC REHABILlTATION OF EXISTING BUILDlNGS
5.5.3.3.2 Linear Static and Dynamic Procedures 5.5.3.4.1 General Componen! acceplance criteria shall
Lower-bound compressive strength, PCL> oí' braces in be computed in accordance with lhe general require
eccentric braced frames shall be calculated as for ments 01' Section 5.3.2 and the specitic requirements
columns in accordance with Section 5.4.2.3.2 except 01' this section.
lhal lower-bound yield strength, F yw , shall be used ror Shear and Ilexure in link beams shall be consid
yield strength. ered deformation-controlled actions. AH other actions,
Expected, QCE, and lower-bound, QCL' strengths of and actions on other EBF components, shall be con
beams and columns shall be calculated as for FR sidered force-controlled. Compression, tension, shear,
beams and columns in Section 5.4.2.3. Strength of and bending actions on brace connections incIuding
beams with non-negligible axial load shall be as calcu gusset plates, bolts, welds, and other connectors shall
lated for FR columns. be considered force-controlled.
The lower-bound strength of brace connections
shall be calculated in accordance wilh Load and 5.5.3.4.2 Linear Static and Dynamic Procedures
Resistance Factor Design Specification for Structural Design actions shall be compared with design
Steel Buildings (LRFD) (AISC 1999), taking 4> = 1.0 slrengths in accordance wilh Section 3.4.2. The
and using the lower-bound yic1d slrength, F~,w, for l/l-faclOrs ror sleel components shall be seIectcd from
yield strength. ' Table 5-5.
The strength of the link beam shall be governed Link beams shall conform to lhe requiremenls 01'
by shear, tlexure, or the combination of shear and the AISC 341 (AISC 2(02) with regard lo detailing.
tlexure. MCE shall be taken as the expected moment The brace connecting lo a link beam, the columns, and
capacily and VCE shall be taken as 0.6 Fy"A ... the olher componenls in (he EBF shall be designed 1'01'
. 1.6McE 1.25 times lhe lesser of the link beam flexural oc shear
It e ::s; -,,--',Eq. 5-31 shall be used lO compute expected strength lo ensure link yielding withoul brace
YCE
or column buckling. Wherc the link beam ís aUachcd
the expected slrength of Ihe link beam:
lo lhe column Ilange wilh full-pen welds, lhe proví
sions for lhese conncctions shall be the same as rOl' FR
(Eq.5-31) frame full-pen conneclions. m-facLors ror Ilexure and
shear in link beams shall be taken fmm Tablc 5-5.
, 2.6McE
II e > -v.--' Eq. 5-32 shall be used to compute
C5.5.3.4.2 Linear Sta tic and D)'ncunic Procedures The
CE
the expecled strength of the link beam: acceptance criteria ror I'ull-penetralion, welded beam
lo-column conneclions are based on tesling oí' lypícal
moment rrame proporlioning and span ratios.
(Eq.5-32)
5.5.3.4.3 Nonlínear Suuic and Dynamic Procedllres
CaJculated componenl aClions shall salisfy the require
Linear interpolation between Eqs. 5-31 and 5-32
ments of Seclion 3.4.3. Deformalions limits shall be
shall be used for intermediate values of e.
taken from Tables 5-6 and 5-7.
5.5.3.3.3 Nonlinear Static Procedure Strengths ror
the componenls of EBFs shall be the same as those 5.5.3.5 Rehahilitatioll Measures
specificd in Section 5.5.2.3.3 for Ihe components Eccenlric braced n'ame components Ihal do
of CBFs. In lieu of relationships derived from not meet the acceptance crileria 1'01' Ihe selected
experiment or analysis, Ihe load-deformation Rehabi1ítation Objective shall be rehabililaled.
behavior of each component, as depicted by Rehabilitation measures shall meet ¡he require
Hg. 5-1, shall be determined in accordance with ments of SectÍon 5.3.3 and other provisions of this
Section 5.5.3.2.2. standard.
134
ASCFJSEI 41-06
135
SElSMlC REHABlLITATION OF EXISTING BUILDlNGS
not prevented by the use of stiffeners, equations ror 5.7 STEEL FRAMES WITH INFILLS
VCE given in Load and Resistance Factor Design
Specification for Structural Steel Buildings (LRFD) for Sleel rrames with partial or complete intills of rein
plate girders shall be used to calculate the expected forced concrete or reinforced or unreinforced masonry
strength 01' the wall. shall be evaluated consideríng the combined stiffness
of the steel trame and inlill malerial.
5.6.3.3 Nonlinear Statk and Dynamie Proeedures The engineering properties and acceptance criteria
The generalízed load-deformation curve shown for the infill walls shall comply with the requirements
in Fig. 5-1, as specified in Section 5.4.2.2.2, shall in Chapter 6 for concrete and Chapter 7 for masonry.
be used to represent the complete load-deformation Infíll walls and frames shall be considered 10 carry the
behavior of the steel shear wall to 1'ailure unless seísmic force in composite action, considering the rel
another load-de1'ormation relationship based on ative stiffness of each element, until complete failure
experiment or approved rational analysis veritied by of the walls has occurred. The interaction between the
experiment is used. The expected strength, QCE, steel trame and intill shall be considered using proce
shall be caIculated in accordance with Eq. 5-34. The dures spccified in Chapter 6 for concrete frames with
yield de1'ormation shalJ be calculated in accordance intill. The analysis of each component shall be done in
with Eq. 5-35: stages, considering the efl'ects of interaction between
the elements and carried Ihrough each performance
level. At the point where the intill has been deemed to
(Eq.5-35)
fail, as determined by the accepLance crÍleria specified
in Chapter 6 or Chapler 7, the wall shall be removed
5.6.4 Acceptance Criteria from the analytical model. The analysis shall be
resumed on the bare sLeel frame, taking into considera
5.6.4.1 Linear Statie alld Dynamie Proeedures tion any vertical discontinuity created by the degraded
Design actions shall be compared with design wall. At this point, the engineering properties and
strengths in accordance wÍlh Section 3.4.2. The acceptance criteria for the frame, as specil1ed in
m-1'aclors ror sleel componenls shall be selected from Seclion 5.4, shall apply.
Table 5-5.
Shear behavior in sleel plale shear walls shall be
considered a deformalion-controlled aClion, wilh C5.7 STEEL FRAMES WITH INFILLS
acceptance crileria as provided in Table 5-5. Design
reslrictions ror plate girder webs given in Load and Seismic evaluation of ínfill walls is required because,
Resistance Factor Design Specification for Structural in many cases, these walls are unreinforced or Iightly
Steel Buildings (LRFD) (AISCI999), including those reinforced, and their strength and ductility may be
related to stiffener spacing, shall be followed. inadequate. Before the loss 01' lhe wall, (he steel trame
adds contining pressure to the wall and enhances its
5.6.4.2 Nonlinear Statle and Dynamie Proeedures resistance. The actual eíl'ective force s on the steel
Calculated component actions shall satisfy the frame componenls, however, are probably minima\. As
requiremenls 01' Seclion 3.4.3. Deformation limits Ihe frame componenls aUempl lO develop force, Ihey
shall be taken from Tables 5-6 and 5-7. deform and the stitrer concrete or masonry compo
nents on the far side of Ihe member pick up load.
5.6.5 Rehabilitation Measures However, beam end connections, column splices, and
Steel plate walls that do not meet the acceptance steel 1'rame connections at the foundalÍon should be
criteria for lhe selected Rehabilitation Objective shalJ investigated for force s due to interaction wiLh the ¡ntill
be rehabilitated. Rehabilitation measures shall meet similar lo procedures specified for concrele frames in
the requirements of Section 5.3.3 and other provisions Chapter 6.
of this standard. The stiffness and resislance providcd by concrete
andlor masonry intills may be much larger (han the
C5.6.S Rehabilitation Measures stiffness of the steel frame acting alone with or with
Rehabilitation measures may indude the addition out composite actions. Gaps or incomplete contact
of stiffeners, encasemenl in concrete, or the addilion bctween (he steel frame and the intill may negare
of concrete or steel plate shear walls. some or all of this stiíl'ness. These gaps may be
136
ASCElSEI 41-06
belween the wall and columns of the frame or berween load s olher than supporl of rooting malerials. Load
rhe wall and the top beam enclosing Ihe frame. lransfer to frame elements lhat acl as chords or collec
OitTerent strenglh and stitfness conditÍons musr be tors in modern frames is through shear connectors,
expected wÍrh differenr discontinuily lypes and loca puddle welds, screws, or shot pins.
[ions. Therefore, ¡he presence of any gaps or disconli
nuÍIÍes belween !he intill walls and lhe frame musl be 5.8.1.2 Stiffness
delennined and considered in lhe design and rehabili
lation process. The resistance provided by infill walls 5.8.1.2.1 Linear Procedllres Metal deck diaphragms
may also be included if proper evalualion 01' lhe con shall be c1assified as flexible, stiff, or rigid in accor
nection and interaction between lhe wall and lhe frame dance with Section 3.2.4. F1exibility factors for use in
is made and if Ihe slrength, ductilily, and properties of lhe analysis shall be calculaled by an approved
lhe wall are properly included. ralional method.
Tlle sliffness provided by infill masonry walls is
excluded from lhe design and rehabilitarion process C5.B.1.2.1 Linear Procedures Flexibility factors for
unless integral aclion between lhe steeI frame and lhe various lypeS 01' metal decks are available from manu
wall is veritied. If complele or partial inleraction facturers' catalogs. In syslems for which values are nol
between Ihe wall and frame is veritied, lhe stiffness is available, values can be established by interpolating
increased accordingly. The seismic performance of between the most representative systems for which val
uncontined masonry walls is far inferior 10 that of con ues are available. F1exibilily factors for use in lhe
fined masonry walls; Iherefore, the resistancc of the analysis can also be calculated using the Sleel Oeck
auached wall can be used only if strong evidence as 10 InslÍlule (SOl) Diaphragm Design Manual (SOl 1981).
ils slrength, ductililY, and inleraclion wilh lhe sleel
frame is provided. 5.8.1.2.2 Nonlinear Static Procedllre Inelaslic proper
ties 01' diaphragms shalI not be included in inela.,tic seis
mic analyses if Ihe weak link of the diaphragm is con
5.8 DIAPHRAGMS neclÍon failure. Procedures tor developing models for
inelastic response 01' wood diaphragms in unreinforced
5.8.1 Bare Metal Deck Diaphragms masonry (URM) buildings shaIl be permitted for use as
!he basis of an inelaslic model 01' a flexible metal
5.8.1.1 General diaphragm. A strain-hardening modulus 01' 3% shall be
Metal deck diaphragms shall be composed of metal used in the posl-elastic region.
plale or gage !hickness stecl sheets formed in a repealÍng
pallem with ridges and valleys. Oecking units shall be 5.8.1.3 Strength
altached to each olher by welds, crimping, or mechanical The slrength of bare metal deck diaphragms shall
fasleners and shali be auached 10 lhe structural steel sup be determined in accordance with Section 5.3.2 and
ports by welds or by mechanical fasteners. Bace metal the requirements 01' this section.
deck diaphragms shall be permitted to resist seismic Expected strenglh, Qce, tor bare melal deck
loads aCling alone or in conjunclion wi!h supplementary diaphragms shall be taken as two limes allowable values
diagonal bracing complying with !he requirements 01' specified in approved codes and standards, unless a
Section 5.8.4. Steel frame elemenls, lo which bace metal lacger value is justitied by tesl data. Alternatively,
deck diaphragms are auached al Iheir boundaries, shall lower-bound strength shall be taken as nominal slrength
be considered lo be Ihe chord and colleclor elemenls. published in codes or standards approved by the author
Crileria shall apply lo existing diaphragms as well ity having jurisdiction, except that lhe strenglh reduc
as lo sliffened, strengthened, or otherwise rehabililaled tion factor, 4>, shall be taken equal to unily.
diaphragms. Inleraction of new and exislÍng elements of Lower-bound slrengths, QCL! 01' welded connectors
rehabilitated diaphragms shall be evaluated 10 ensure shaIl be as specitied in the Welding Code for Sheet
strain compatibilily. Load transfer mechanisms betwecn Steel, AWS 01.3 (AWS 1998), or other approved
new and existing diaphragm elements shall be evaluated. Slandard.
137
SEISMIC REHABILITATION OF EXISTlNG BUILDINGS
manufaclurers' lileralure, or in Ihe publicalions of Ihe 3. Adding puddle welds or olher shear connectors al
SDI. Where allowablc slresses are given, Ihese may be panel perimelers;
multiplied by 2.0 in lieu of information provided by 4. Adding diagonal sleel bracing lo form a horizonlal
the manufacturer or other knowledgeable sources. Iruss LO supplement diaphragm slrenglh;
Connections between metal decks and sleel fI'am- . 5. Adding structural concrele; and
ing commonly use puddle welds. Conneclion capaci 6. Adding connections belween deck and supporting
lies are provided in ICC-ES repons, manufacturers' members.
dala, Ihe SDI Diaphragm Design Manual (SDI 1981),
or AWS D 1.3 (AWS 1998). Other attachmem systems,
5.8.2 Metal Deck Diaphragms with Strudural
such as clips, are somelimes used.
Concrete Topping
5.8.1.4 Acceptance Criteria 5.8.2.1 General
Connections of bare melal deck diaphragms shall
Metal deck diaphragms with struclural concrele top
be considered force-conlrolled. Conneclion capacity
ping, consistíng of either a composile deck wilh indenta
shalJ be cheeked for the abiJily to transfer the total
lions, or a noncomposile form deck and the concrele lOp
diaphragm reaction into the steel framing. Diaphragms
píng slab with reinforcement acling together, shall be per
(hat are governed by the capacily 01' the connections
miued to resist diaphragm loads. The concrete till shall
shall also be considered force-controlled. Bare metal
be either normal or lightweight structural concrete, with
deck diaphragms not governed by the capacity of the
reintorcing composed of wire mesh or reiníorcing sleel.
connections shall be considered deformation-con
Decking unils shall be attached to each other by welds,
lrolled. The m-factors for shear yielding or plale buck
crimping, or mechanícal fasleners and shall be attached
ling shall be laken from Table S-S.
to structural sleel supports by welds or by mechanical
For the Life Safety Structural Performance Level,
fasteners. The steel frame elements to which the lopped
a loss ol' bearing support or anchorage of the deck
metal deck diaphragm boundaries are auached shall be
shall nol be permitted. For higher performance levels,
consideced the chord and colJector elemenls.
the amount 01' damage lo the connections shall not
Criteria shall apply to existing diaphragms as well
impair the load Iransfer belween the diaphragm and
as new and rehabiJilated diaphragms. Interaclion of
the steel frame. De1'ormations shaJl not exceed (he
new and exisling elements of rehabilitaled diaphragms
Ihreshold of detleclions Ihal cause unacceplable dam
shall be evalualed tor slrain compatibility. Load trans
age lo other elements (either struclural or nonslruc
fer mechanisms belween new and exisling diaphragm
tural) at specified performance levels.
components shall be considered in determining the
tlexibilíty 01' the diaphragm.
CS. 8.1.4 Acceptance Criteria
Ir bare deck capacity is controlIed by connections
C5.8.2.1 General
lo frame members or panel buckling, Ihen inelaslic
Metal deck diaphragms with structural concrete
action and ductility are Jimited and the deck should be
topping are frequently used on tloors and roofs of
considered lo be a force-controlled member.
buildings where there are typical l100r gravity loads.
Concrele has structural properties that signiticantly
5.8.1.5 Rehabilitation Measures add Lo diaphragm sliffness and strength. Concrele rein
Bare metal diaphragms Ihat do 'nol meet the
forcing ranges from lighl mesh reinforcement to a reg
acceptance criteria for the selected Rehabilitation
ular grid 01' small reinforcing bars (No. 3 or No. 4).
Objective shall be rehabililated. Rehabilitation meas
Metal decking is typically composed oí' corrugated
ures shall meet lhe requirements ol' Section 5.3.3 and
sheet steel from 22 ga. down to 14 ga. Rib depths vary
other provisions ol' this standard.
from I~ lo 3 in. in most cases. Auachmen~ of Ihe ~etal
deck 10 the sleel frame is usually accomphshed usmg
C5.8.1.5 Rehabilitation Measures puddle welds at 1 to 2 fl on cenler. For composite
The following measures may be effective in reha
behavior, shear sluds are welded to the reame before
bilitaling bare metal diaphragms:
lhe concrete is casI.
l. Adding shear conneclOrs for transfer of stress lo Load transfer 10 frame elements lhat acl as chords
chord or collector elements; oc collectors in modern frames is usually lhrough pud
2. Strenglhening existing chords or colJectocs by dIe welds or headed studs. In older construclion where
the addilion 01' new sleel plales lo exisLing frame the trame is encased for fire protection, load transfer is
componenls; made through bond.
138
ASCElSEI 41-06
139
SEISMIC REHABILITATION OF EXISTING BUILDlNGS
140
ASeE/SEI 41-06
141
SEISMIC REHABILlTATION OF EXISTING BUlLDINGS
in Section 5.5. Lateral support oí' truss diaphragm 2. Existing chords components strenglhened by the
members provided by metal deck, wilh or without addition 01' shear connectors to enhance composite
concrete fill, shall be considered in evaluation of truss action;
diaphragm capacities. Gravity force effects shalI be 3. Existing steel truss components strenglhened
included in the calculatíons for those members that by methods specified for braced steel frame
support gravity loads. members;
4. Truss connections strengthened by the addítion
5.8.4.4 Acceptance Criteria 01' welds, new or enhanced plates, and bolts;
Force transfer mechanisms betwecn various mem and
bers 01' the truss at the connections, and between 5. Structural concrete mi added to act in combina
trusses and frame elements, shall be evaluated lo ver tion with steel Iruss diaphragms after verifying
ify Lhe completion of Lhe load path. the ellects of the added weight 01' concrete till.
For the Lite Safety Structural Performance Level,
a loss 01' bearing support or anchorage shall not be
permitted. For higher performance levels, the amount 5.8.5 Archaic Diaphragms
of damage to lhe connections or bracing elements shall
nol result in the loss of Lhe load transfer between the 5.8.5.1 General
diaphragm and the steel frame. Deformations shall be Archaic diaphragms in steel buildings are those
Iimited lo be below Lhe threshold 01' deflections that consisting of shallow brick arches that span belween
cause damage lo other elemenls (either struclural or steel floor beams, wilh the are hes packed tightly
nonstruclural) at specíJied performance levels. betwecn the beams lo provide the necessary resistance
lo lhrust forces.
5.8.4.4. / Linear Procedures Linear acceptance criteria
for horizontal steel truss diaphragm components shall
be as specified for concentric braced frames in Sec
cs. 8.5. 1 General
Archaic steel diaphragm elements are almost
tion 5.5.2.4 except that beam and column criteria need
always found in older steel buildings in conjunction
not be used. Use 01' m-factors specitied for diagonal
with vertical systems of structural sleel framing. The
brace components, in lieu of those for beam and col
brick arches were typically covered wilh a very low
umn components of braced frames, shall be permitted
strength concrete fill, usually unreinforced. In many
for strut and chord members in the truss.
instances, various archaíc diaphragm systems were
5.8.4.4.2 Nonlinear Procedures Nonlinear acceptance patented by contractors.
criteria for horizontal steel truss diaphragm compo
nents shall be as specHied for concentric braced 5.8.5.2 St(tfness
frames in Section 5.5.2.4 except that beam and column
criteria need nOI be used. Use 01' plastic del'ormations 5.8.5.2./ Linear Procedures Existing archaic
specified for diagonal brace components, in lieu of diaphragm systems shall be modeled as a horizonlal
those specified for beam and column components of diaphragm with equivalent thickness of brick arches
braced frames, shall be permitted for strut and chord and concrete mI. Modeling of the archaic diaphragm
members in the truss. as a truss with steel beams as tension elements and
are hes as compression elements shall be permitted.
5.8.4.5 Rehabilitation Measures The f1exibility of archaic diaphragms shall be consid
Steel truss diaphragms that do not meet the ered in calculating the dístribution of lateral loads lo
acceplance criteria for the selected Rehabilitation vertical elements. Analysís results shall be evaluated
Objective shall be rehabiJitated. Rehabilitalion meas to verify that diaphragm response remains elastic as
ures shall meet the requirements of Section 5.3.3 and assumed.
other provisions of this standard. Interaction 01' new and existing elements of
strengthened diaphragms shall be evaluated by check
cs. 8.4.5 Rehabilita/ion Measures ing the strain compatibility 01' lhe two in cases where
The following measures may be effective in reha
new structural elements are added as part 01' a seismic
bilitaling steel truss diaphragms: rehabilitation. Load transfer mechanisms between new
]. Diagonal components may be added to form addi and exístíng díaphragm elements shall be considered
tional horizontal trusses as a method of strengthen in determining Ihe tlexibility of the strengthened
ing a weak existing diaphragm; diaphragm.
142
ASeE/SEI 41-06
5.8.5.2.2 Nonlinear Procedltres Archaic diaphragms 3. Removing weak concrete fill and replacing it with a
shall be required to remain in the elastic range unless structural concrete topping slab after verifying the
otherwise approved. eftects of the added weight of concrete til\.
143
SEISMIC REHABILlTATION OF EXISTING BUILDlNGS
144
ASeE/SEI 41-06
foundations: driving additional piles near existing groups force-resisting system of an existing building. The
and then adding a new pile cap to increase stiffness and requirements of this chapter shaJl apply to existing
strength of the pile foundation. Monolithic behavior concrete components of a building system, rehabili
gained by connecting the new and old pile caps with tated concrete components of a building system, and
epoxied dowels may also be effective. In most cases, new concrete components that are added to an existing
it is not possible to rehabilitate the existing piles. building system.
Section 6.2 specifies data coJlection procedures
for obtaining material properties and performing
5.10 CAST AND WROUGHT IRON condition assessments. Section 6.3 specifies general
analysis and design requirements for concrete compo
5.10.1 General nents. Sections 6.4,6.5,6.6,6.7,6.8, and 6.9 provide
Existing components of cast and wrought iron modeling procedures, component strengths, accept
shaJl be permitted to participate in resisting seismic ance criteria, and rehabilitation measures for concrete
forces in combination with concrete or masonry walls. and precast concrete moment frames, braced trames,
Cast iron frames, in which beams and columns are and shear walIs. Sections 6.10, 6.11, and 6.12 provide
integralIy cast, shall not be permitted to resist seismic modeling procedures, strengths, acceptance criteria,
forces as primary elements of the lateral-force and rehabilitation measures for concrete diaphragms
resisting system. The ability of cast iron elements to and concrete foundation systems.
resist the design displacements at the selected earth
quake hazard level shaJl be evaluated.
C6.1 SCOPE
5.10.2 Stiffness
The axial and t1exural stitlness of cast iron shaJl
Techniques for repair of earthquake-damaged con
be ca1culated using elastic section properties and a
modulus of elasticity, E, of 25,000 kips/in.2 unless a crete components are not inc1uded in this standard.
The design professional is referred to FEMA 306
different value is obtained by testing or other methods
(FEMA 1998), FEMA 307 (FEMA 1998), and FEMA
approved by the authority having jurisdiction.
308 (FEMA 1998) for information on evaluation and
repair of damaged concrete waJl components.
5.10.3 Strength and Acceptance Criteria
Axial and t1exural loads on cast iron components
shalI be considered to be force-controlIed behaviors.
Lower-bound material properties for cast iron shaIl be 6.2 MATERIAL PROPERTIES AND CONDITION
based on Table S-l. ASSESSMENT
The lower-bound strength of a cast iron co1umn
shalI be ca1culated as: 6.2.1 General
Mechanical properties of concrete material s and
(Eq.5-36)
components shaJl be obtained from available drawings,
where specificalions, and other documents for the existing
construction in accordance with the requirements of
Ag = gross area of column;
Section 2.2. Where such documents fail to provide
Fa = 12 ksi for lj r:S 108; or
adequate information to quantify concrete material
l.40 X lO'
ksi for lj r > 108. properties or the condition of concrete components of
(lj r)2 the structure, such information shaJl be supplemented
Cast iron columns shalI only be permitted to carry by materials tests and assessments of existing condi
axial compression. tions in compliance with requirements of this chapter
as specified in Section 2.2.6.
Material properties of existing concrete compo
6.0 CONCRETE nents shall be determined in accordance with Section
6.2.2. A condition assessment shaJl be conducted in
6.1 SCOPE acconlance with Section 6.2.3. The extent of materials
testing and condition assessment performed shaJl be
This chapter sets forth requirements for the Systematic used to determine the knowledge factor as specified in
Rehabilitation of concrete components of the lateral SecLÍon 6.2.4.
145
SEISMIC REHABILITATION OF EXISTING BUILDINGS
Use of default material properties shall be permit invaluable and may be elIectively used lo reduce the
ted in accordance with Section 6.2.2.5. Use of material amount of in-place testing required. The design pro
properties based on historical information as default fessional is encouraged 10 research and acquire all
values shall be permitted as specit1ed in available records from original conslruction.
Section 6.2.2.5.
6.2.2 Properties of In-Place Materials and
C6.2.1 General Components
This section identifies properties requiring consid
eration and provides guidelines for determining the 6.2.2.1 MaterÚll Properlies
properties of buildings. Also described is the need for
a thorough condition assessment and utiJization 01' 6.2.2.1.1 General The fo\lowing component and con
knowledge gained in analyzing component and system nection malerial properties shall be obtained for the
behavior. PersonneJ involved in material property as-built structure:
quantification and condition assessment should be Concrete compressive strength; and
experienced in the proper implementation of testing Yield and ultimate strength of conventional and
practices and the interprelation of results. prestressing reinforcing steel and metal connection
The form, function, concrete strength, concrete hardware.
quality, reinforcing steel strength, quality and detail Where materials testing is required by Sec
ing, forming techniques, and concrete placement tech tion 2.2.6, the test methods to quantify material prop
niques have constantIy evolved and have had a signifi erties shalI comply wilh the requirements oí' Sec
cant impact on the seismic resistance of a concrete tion 6.2.2.3. The frequency oí' sampling, including the
building. Innovations such as prestressed and precast minimum number 01' tests for property determination,
concrete, post tensioning, and lift slab construction shall comply with the requirements 01' Section 6.2.2.4.
have created a multivaríant invenlory of exisling con
crete struclures. C6.2.2.1.1 General Other material properties that may
lt is important to ínvestigate the local practices be of interest for concrete components inelude:
relative to seismic design where trying lo analyze a
l. Tensile strength and modulus 01' elasticity of con
concrete building. Specitic benchmark years can be
crete, which can be derived from the compressive
delermined for lhe implementation of earlhquake
strength, do not warrant the damage associated with
resistant design in most locations, but caution should
the extra coring required;
be exercised in assuming optímistic characteristics for
2. Ductility, toughness, and fatigue properties of
any specific building.
concrete;
Particularly with concrete materials, the date of
3. Caroon equivalent present in (he reinforcing steel;
original building construction significantly intluences
and
seismic performance. In the abscnce of deleterious
4. Presence 01' any degradation such as corrosion,
conditions or materials, concretc gains compressive
bond with concrete, and chemical composition.
strength from the time it is originally cast and in
place. SLrengths typically exceed specitied design val The effort required lO dClclmine these properties
ues (28-day or similar). Early uses 01' concrete did not depends on the availability of accurate updated con
specify any design strength, and low-strength concrete struclion documents and drawings, the quality and
was not uncommon. Also, early use of concrete in type 01' construction (absence 01' degradation), accessi
buildings often employed reinforcing steel with rela bility, and [he condition oí' materials. The method of
tively low strength and ductility, Iimited continuity, analysis selected [e.g., Linear Static Procedure (LSP),
and reduced bond developmenl. Continuity between Nonlinear Static Procedure (NSP)] may a\so inlluencc
specitic existing components and elements (e.g., the scope of the testing.
beams and columns, diaphragms, and shear walls) is The size of the samples and rcmoval practices to
also particularly diflicult to assess, given the presence be followed are referenced in FEMA 274 (FEMA
of concrete cover and othcr barriers to inspcction. 1997). General1y, mechanical properties for both con
Properties of welded wire fabric for various peri crete and reinforcing steel can be established from
ods of construction can be obtained from the Wire combined cme and specimen sampling at similar loca
Reinforcement Institute. tions, followed by laboratory testing. eore drilling
Documentation of properties and grades of mate should minimize damage of the existing reinrorcing
rial used in component and connection construction is steel as much as is practicable.
146
ASCE/SEI41-06
6.2.2.1.2 Nominal or Specified Properties Nominal examined for physical condition as specified in
material properties, or properties specitied in construc Section 6.2.3.2.
tion documents, shall be taken as lower-bound mate If the determination ol' material properties is
rial properties. Corresponding expected material prop accomplished through removal and testing of samples
erties shall be calculated by multiplying lower-bound for laboratory analysis, sampling shall take place in
values by a factor taken from Table 6-4 to translate primary gravity- and lateral- force-resisting compo
from lower-bound to expected values. Alternative nents in regions with the least stress.
factors shall be permiued where justified by test Where Section 6.2.2.4.1 does not apply and the
data. coefficient of variation is greater than 14%, the
expected concrete strength shall not exceed the mean
6.2.2.2 Component Properties minus one standard deviation.
The following component properties and as-built
conditions shall be established: 6.2.2.3.2 Sampling For testing of concrete material,
the sampling program shall consist of the removal of
l. Cross-sectional dimensions of individual compo standard cores. Core drilling shall be preceded by non
nents and overall configuration of the structure; destructive location of the reinforcing steel, and core
2. Contiguration of component connections, size of holes shall be located to minimize damage to or
anchor bolts, thickness of connector material, drilling through the reinforcing steel. Core holes shall
anchorage and interconnection of embedments, be filled with concrete or grout of comparable
and the presence of bracing or stifl'ening strength. If conventional reinforcing and bonded pre
components; stressing steel are tested, sampling shall consist of me
3. Modifications to components or overall configura removal of local bar segments and installation of
tion of the structure; replacement spliced material to maintain continuity of
4. Current physical condition of components and con the rebar for transfer of bar force.
nections, and the extent ol' any deterioration pres Removal of core samples and performance of lab
ent; and oratory destructive testing shall be permiued as a
5. Presence of conditions that influence building per method ol' determining existing concrete strength
formance. properties. Removal of core samples shall employ
the procedures contained in ASTM C42/C42M-03
C6.2.2.2 Component Properties (ASTM 2(03). Testing shall follow the procedures
Component properties may be needed to charac contained in ASTM C42/C42M-03, ASTM C39/
terize building performance properly in the seismic C39M-OI (ASTM 2(01), and ASTM C496-96 (ASTM
analysis. The starting point for assessing component 1996). Core strength shall be converted to in situ
properties and condition should be retrieval ol' avail concrete compressive strength (fe> by an approved
able construction documents. Preliminary review of procedure.
mese documents should be performed to identify pri Removal of bar or tendon length samples and per
mary gravity- and lateral-force-resisting elements, sys formance of laboratory destructive testing shall be per
tems, and their critical components and connections. miued as a method of determining existing reinforcing
In the absence of a complete set of building drawings, steel strength properties. The tensile yield strength
me design professional must perform a thorough and ultimate strength for reinforcing and prestress
investigation of the building to identify these ele ing steels shall be obtained using the procedures con
ments, systems and components as indicated in tained in ASTM A370-03 (ASTM 2003). Prestressing
Section 6.2.3. material s also shall meet the supplemental require
ments in ASTM A4l6/A4l6M-02 (ASTM 2002),
6.2.2.3 Test Methods to Quantify Material ASTM A421/A421M-02 (ASTM 2002), or ASTM
Properties A722/A722M-98 (ASTM 2003), depending on mate
rial type. Properties of connector steels shall be per
6.2.2.3.1 General Destructive and nondestructive test miued to be determined by wet and dry chemical com
methods used to obtain in-place mechanical properties position tests, and by direct tensile and compressive
of materials identitied in Section 6.2.2.1, and compo strength tests as specified by ASTM A370-03. Where
nent properties identified in Section 6.2.2.2 shall com strengths of embedded connectors are required, in situ
ply with the requirements of this section. Samples of testing shall satisfy the provisions of ASTM E488-96
concrete and reinforcing and connector steel shall be (ASTM 2003).
147
SEISMIC REHABILlTATION OF EXISTlNG BUlLDINGS
C6.2.2.3 Test Methods to Quantify Material The design professional (and subcontracted test
Properties ing agency) should carefully examine test results to
ACI 318 (ACI 2(02) and FEMA 274 (FEMA verify that suitable sampling and testing procedures
1997) provide further guidance on correlating core were folJowed and that appropriate values ror the
strength to in-place strength and provide references for analysis were selected from the data.
various test methods that may be used to estimate
material properties. The chemical composition may 6.2.2.4.1 Comprehensive Testing Unless specified oth
also be determined from the retrieved samples. FEMA erwise, a minimum of three tests shall be conducted to
274 provides references for these tests. determine any property. If the coefficient of variation
Usually, the reinforcing steel system used in the exceeds 14%, additional tests shall be performed until
construction of a specific building is of a common the coefficient of variation is equal to or les s than
grade and strength. Occasionally, one grade of rein 14%.
forcement is used for small-diameter bars (e.g., those
used for stirrups and hoops) and another grade for 6.2.2.4.2 Concrete Materials For each concrete ele
large-diameter bars (e.g., those used for longitudinal ment type (such as a shear wall), a minimum of three
reinforcement). Furthermore, it is possible that a num core samples shall be taken and subjected to compres
ber of difIerent concrete design strengths (or "elasses") sion tests. A minimum of six total tests shall be per
have been employed. Historical research and industry formed on a building for concrete strength determina
documents also contain insight on material mechanical tion, subject to the limitations 01' this section. If vary
properties used in difIerent construction eras. ing concrete elasses/grades were employed in the con
struclÍon of the building, a minimum of three samples
6.2.2.4 Minimum Number 01 Tests and tests shall be performed for each elass. The modu
Materials testing is not required if material proper lus of elasticity shall be permitted to be estimated
ties are available from original construction documents from the data of strength testing. Samples shall be
that inelude material test records or material test reports. taken from randomly selected components critical to
The minimum number of tests necessary to structural behavior of the building. Tests al so shall be
quantify properties by in-place testing for comprehen performed on samples from components that are dam
sive data collection shall be as specified in Sec aged or degraded, if such damage or degradation is
tions 6.2.2.4.1 through 6.2.2.4.4. The minimum identitied, to quantify their condition. Test results shall
number of tests for usual data collection shall be as be compared with strength values specitied in the con
specitied in Section 6.2.2.4.5. If the existing gravity struction documents. If test values less than the speci
or lateral-force-resisting system is being replaced fied strength in the construclÍon documents are found,
in the rehabilitation process, material testing shall be further strength testing shall be performed to deter
required only to quantify properties of existing materi mine the cause or identify the extent of the condition.
als at new connection points. The minimum number of tests to determine com
pressive and tensile strength shall conform to the fol
C6.2.2.4 Minimum Number 01 Tests lowing criteria:
In order to quantify in-place properties accurately, For concrete elements for which the specitied
it is important that a minimum number of tests be con design strength is known and test results are not avail
ducted on primary components of the lateral-force able, a minimum of three cores/tests shall be con
resisting system. The minimum number of tests is dic ducted for each floor level, 400 yd 3 of concrete, or
tated by the data available from original construction, 10,000 sf of surface area, whichever requires the most
the type of structural system employed, the desired frequent testing; and
accuracy, and the quality and condition of in-place For concrete elements for which the design
materials. The accessibility of the structural system strength is unknown and test results are not available,
may also intluence the testing program scope. The a minimum of six cores/Lests shall be conducted for
focus of this testing shall be on primary lateral-force each tloor level, 400 yd 3 01' concrete, or 10,000 sf of
resisting components and on specific properties surface area, whichever requires the most frequent
needed for analysis. The test quantities provided in testing. Where the results indicate that different elasses
this section are minimum numbers; the design profes 01' concrete were employed, the degree 01' testing shall
sional should determine whether further testing is be increased to contirm class use.
needed to evaluate as-built conditions. Quantification of concrete strength via ultrasonics
Testing generally is not required on components or other nondestructive test methods shall not be sub
other than those of the lateral-rorce-resisting system. stituted for core sampling and laboratory testing.
148
ASCElSET 41-06
C6.2.2.4.2 Concrete Materials lJltrasonics and non de pIes of each differenl concrele slrength used in the
struclive test methods should not be substituted for conslruction of the building, with a minimum ol'
cme sampling and laboratory testing since they do not three cores taken ror the enlire building;
yield accurate strength values directly. 2. If the specified design strength ol' the concrete is
not known, at least one core shall be laken from
6.2.2.4.3 Conventional Reinforcing and COl/necto/'
each type of component, with a minimum 01' síx
Steels The minimum number of tests required 10 deler
cores taken for the entire building;
mine reinforcing and conneclor steel strength proper
3. If the specified design strength of the reinforcing
lies shall be as 1'ollows. Connector steel shall be
steel is known, use of nominal or specified material
detined as addilional slruclural steel or miscellaneous properties shall be permitted without additional
metal used lo secure precasl and other concrele shapes
testing; and
lo the building structure. Tests shall determine both
4. If Ihe specitied design strength of the reinforcing
yield and ultimate slrengths 01' reinforcing and connec
sleel is nol known, al least two strength coupons of
lor steel. A mínimum of three tensile tests shall be
reinforcing steel shall be removed from the build
conducted on conventional reinforcíng steel samples
ing for testing.
1'rom a building for strength determination, subject to
lhe 1'ollowing supplemental conditions: C6.2.2.4.5 Usual Testing For other material properties,
such as hardness and ductilily, no minimum number 01'
l. lf original construction documents detining proper
lests is prescribed. Simílarly, standard test procedures
ties existo at least three strength coupons shall be
may not exist. The design professional should examine
randomly removed from each element or compo
the particular need ror Ihis type of testing and establish
nent type and tested; and
an adequate protocol.
2. lf original construction documents defining proper
líes do not exisl bUl the approximate date of con 6.2.2.5 DeJault Properties
struction is known and a common material grade is Use 01' default material properties to determine
contirmed, at least three strenglh coupons shall be component strengths shall be permitted in conjunction
randomly removed from each element or component with the linear analysis procedures of Chapter 3.
Iype l'or every Ihree floOl's of the building. Tf the date Default lower-hound concrete compressive
of construction is unknown, at least six 8uch samples/ strengths shall be taken from Table 6-3. Default
tests, for every three tloors, shall be performed. expected concrele compressive strengths shall be
AH sampled steel shall be replaced with new fully determined by multiplying lower-bound values by an
spliced and connected malerial unless an analysis con appropriate factor selected from Table 6-4 unless
firms that replacement of original components is nol another factor is justified by test dala. The appropriale
required. default compressive strength-Iower-bound or
expecled strength, as specitied in Section 2.4.4-shall
6.2.2.4.4 Prestressing Steels The sampling of pre be used lo establish olher strength and performance
slressing steel tendons for laboratory testing shall be characteristics for lhe concrete as needed in the slruc
required only for those prestressed components Ihat lural analysis.
are a pan of the lateral-force-resisting system. Default lower-bound values for reinforcing sleel
Prestressed components in diaphragms shall be permit shall be taken from Table 6-1 or 6-2.
led 10 be excluded l'rom testing. Default expected strenglh vaJues 1'01' reinforcing
Tendon or prestress removal shall be avoided il' sleel shall be determined by multiplying lower-bound
possible by sampling of either Ihe tendon grip 01' the values by an appropriate factor seJected from Table 6-4
extension beyond the anchorage. unless another faclor is justitied by test data. Where
AH sampled prestressed sleel shall be replaced default values are assumed for existing rein1'orcing
with new l'ully connected and stressed material and sleel, welding or mechanical coupling 01' new re
anchorage hardware unless an analysis conl1rms Ihat inforcement to Ihe exisling reinforcíng steel shall
replacement of original components is not required. nol be used.
The defauh lower-bound yield strength for steel
6.2.2.4.5 Usual Testing The minimum number of tests
connector material shall be taken as 27,000 psi. The
lO determine concrete and reinforcíng steel material
defauIt expected yield strength for steel conneclor
properties for usual data collection shall be based on
material shall be determined by multiplying lower
the following criteria:
bound values by an appropriale factor selected from
l. If the specified design strength 01' the concrele is Table 6-4 unless another value is justífied by test
known, al leasl one core shall be laken from sam- data.
149
SEISMIC REHABILlTATION OF EXISTING BUILDlNGS
Table 6-1. Default Lower-Bound Tensile and Yield Properties of Reinforcing for Various Periods l
Year Mínimum Tensile 2 (psi) 55,000 70,000 80,000 90,000 75,000 80,000 100,000
1911-1959 x x x x
1959-1966 x x x x x x x
1966-1972 x x x x x
1972-1974 x x x x x
1974-1987 x x x x x
1987- Present x x x x x X
1An entry al' "x" indicaIes the grade was available in those years.
'The terms SlruclUral, Intenl1ediate, and Hard became obsolete in 1968.
Table 6-2. Default Lower-Bound Tensile and Yield Properties of Reinforcing for
Various ASTM Specifications and Periods·
1An entry of "x" indicates the grade was available in those yeat·s.
2The terms Structural. Intermediate, and Hard hecame obsolele in 1968.
)ASTM steel is marked with lhe leuer W."
4Raíl bars are marked with the leuer "R."
5Bars marked "s!" (ASTM 616) have supplementary requirements for hend tesIs.
6ASTM A 706 has a minimum tensile strength 01' 80 ksi. but not less than 1.25 times the actual yield slrength.
150
ASCE/SEI 41-06
15\
SEISMIC REHABILITATION OF EXISTING BUILDlNGS
Visual inspection of the building shall inelude vis lhe concrete. Further guidelines and procedures for
ible portions of foundations, lateral-force-resisting deslruclÍve and nondestructive tests that may be used
members, diaphragms (slabs), and connections. As a in lhe condition assessment are provided in FEMA
minimum, a representative sampling of at leasl 20% of 274 (FEMA 1997) and FEMA 306 (FEMA 1998). The
lhe components and connections shall be visually following paragraphs identify those nondestructive
inspected at each tloor leve\. If significant damage or examination (NDE) methods having the greatest use
degradation is found, the assessment sample of aH crit and applicabilily to condition assessment.
ical componenls of similar type in the building shall
• Surface NDE methods inelude infrared thermogra
be increased to 40%.
phy, delamination sounding, surface hardness meas
If coverings or olher obstructions exist, parlial
urement, and crack mappíng. These methods may be
visual inspeclion through lhe obstruclion, using drilled
used lo find surface degradation in components such
holes and a tiberscope, shall be permitted.
as service-induced cracks, corrosion, and construc
tion defects.
6.2.3.2.2 Comprehensive Co\ndition Assessment Expo
• Volumetric NDE methods, including radiography
sure is defined as local minimized removal 01' cover
and ultrasonics, may be used to identify the presence
concrete and olher malerials lo allow inspeclion of
of internal discontinuities, as well as to identify loss
rein1'orcing syslem details. AIl damaged concrete cover
of section. Impact-echo ultrasonics is particularly
shall be replaced after inspeclion. The tollowing crite
useful because oí" case of implementation and
ria shall be used for assessing primary connections in
proven capability in concrele.
lhe building for comprehensive data collection:
• Structural condition and performance may be
l. If delailed design drawings exist, exposure of at assessed through on-Hne monitoríng using acoustic
least three differcnt primary connections shall emíssíons and slrain gauges, and in-place static or
oceur, with the conncclion sample ineluding differ dynamic load tests. Monitoring is used 10 determine
ent types 01' conneclions. Jf no deviations from Ihe if active degradation or de1'ormations are occurring,
drawings CXiSI, il shall be permilted to consider lhe whíle nondestructive load tesling provides direct
sample as being representative of installed condi insight on load-carrying capacily.
lions. If devialions are noted, then al least 25% of • Locating, sizing, and initial assessment of the rein
the specitic connectíon type shall be ínspected lo forcing steel may be completed using electromag
ídentify lhe extenl of devíation; and netic methods (such as a pachometer) 01' radiogra
2. In the absence of delaíled desígn drawings, at least phy. Further assessment of suspected corros ion
lhree conneclions of each primary connectíon type actívity should use electrical half-cell potential and
shall be exposed for ínspection. If common delaíl resistivity measuremems.
ing among lhe three connections is observed, it • Where it is absolutely essential, the leve\ 01' prestress
shal1 be permiued 10 consider lhis condition as rep remaining in an unbonded prestressed system may
resentative of installed conditions. If variations are be measured using lift-off testíng (assuming original
obscrved among like connections, additional con design and installation dala are available), 01' another
nections shall be inspected until an accurate under nondestructive method such as "coring stress relief'
standing of building conslruction is gained. specified in ASCE lI (ASCE 1999).
152
ASCElSEI41-06
153
SElSMIC REHABILlTATION OF EXlSTING BUILDINGS
I Jt shall be pennitted 10 take Ig for T-beams as twice the value of l. of the web alooe. Otherwise, 1, shall be based 00 the effective width as defioed
in Section 6.3.1.3. For columns with axial compression falling between the Iímits provided, linear interpolation shall be pcrmittcd. Altematively,
the more conservative effective stiffoesses shall be used.
~----------e --------------~
1----- d -----1
1.0
1.0
B e
B e
Li
(J or Li h
(a) Deformation (b) Deformation ratio
FIGURE 6-1. Generalized Force-Deformation Relations for Concrete Elements or Components.
under multiple reversed deformalion cycles as speci deformalíon relalion by poinls A, B, and C only (ralher
fied in Seclion 6.3.2.1. Ihan all poinls A-E) shall be permitted jf the calcu
The generalized load-deformation relation shown laled response does nol exceed point C. Numerical
in Fig. 6-1 shalJ be described by linear response from values for the points identitied in Fig. 6-1 shall be as
A (unloaded component) lo an effective yield B, then a specified in Sections 6.4 through 6.12. Othcr
linear response al reduced stiffness from poinl B to C, load-deformation relations shaIl be permiued ifjusli
lhen sudden reduction in lateral load resistance to fied by experimental evidence or analysis.
point D, lhen response al reduced resislance lo E, and
final loss of resistance thereafter. The slope from C6.3./.2.2 Nonlinear Procedllres Typically, Ihe
point A lo B shall be determined according lo Sec responses shown in Fig. 6-1 are associated wÍlh flex
lion 6.3.1.2.1. The slope from poinl B lo C, ignoring ural response or tension response. In this case, the
effecls of gravity loads aCling Ihrough lateral displace resistance al Q/Qy 1.0 is the yield value, and subse
ments, shall be taken between zero and 10% of the ini quent strain-hardening accommodales strain hardening
lial slope unless an aIternate slope is juslified by in (he load-deformation relation as Ihe member is
experiment or analysis. Poinl C shall have an ordinate deformed toward Ihe expected strength. Where Ihe
equal to Ihe strength of (he component and an abscissa response shown in Fig. 6-1 is associated wilh com
equal lo the deformalion al which significant strength pression, (he resislance at Q/Qy 1.0 typically is
degradation begins. Representation of the load the value al which concrete begins lo spaIl, and
154
ASeE/SEI 41-06
strain-hardening in well-contined sections may be width of the web shaIl be assumed ineffective in resist
associated with strain-hardening of the longitudinal ing shear.
reinforcement and the confined concrete. Where lhe In walls, effective flange width shall be in accor
response shown in Fig. 6-1 is associated with shear. dance with Chapter 21 of ACI 318 (ACI 2002).
the resistance at Q/Qy = 1.0 lypically is the value at
which Ihe design shear strenglh is reached, and no
6.3.2 Strength and DeformabUity
slrain-hardening follows.
'fhe deformalÍons used for lhe load-deformalion
6.3.2.1 General
relaLion of Fig. 6-1 shall be defined in one of lwo
Actions in a strllcture shall be classitied as being
ways, as follows:
either deformation-controlled or force-controlled,
l. Deformation, or Type I. In this curve, detorma as defined in Section 2.4.4. Design strengths for
¡ions are expressed direcdy using terms such as deformation-controlled and force-controIled aClions
strain, curvature, rotation, or elongation. 'fhe shall be calculated in accordance with Sections 6.3.2.2
parameters a and b shall refer lo lhose pOrlions of and 6.3.2.3, respectively.
the deformalÍon Ihal occur after yield; thal is, the Components shall be classified as having low,
plastic deformation. 'fhe parameler e is the reduced moderate, or high duclility demands according lo
resislance after the sudden reducLion fmm e to D. Section 6.3.2.4.
ParameLers a, b, and e are detlned numerically in Where strength and deformation capacities are
various tables in this chapter. AIternatively, it shaIl derived from test data, lhe tests shalI be representative
be permitted to determine the parameters a, b, and oí' proportions, details, and stress levels for the compo
e direcdy by analytical procedures juslitied by nent and comply with requirements specified in
experimental evidence. Section 2.8.1.
2. Deformation Ratio, or Type 11. In this curve, The strenglh and deformation capacÍties of con
deformalions are expressed in lerms such as shear crete members shall correspond to values resulting
angle and langenlial drift ralio. 'fhe paramelers d 1'mm earthquake loadings involving three fully
and e refer lo total deformations measured from the reversed cycJes lo lhe design deformation level unless
origino Parameters e, d, and e are defined numeri a larger or smaller number ol' deformation cycles is
cally in various tables in lhis chapler. Alternatively, determined considering earthquake duration and lhe
il shall be permiued 10 determine lhe parameLers e, dynamic properties 01' the structure.
d, and e directly by analylical procedures justified
by experimental evidence. C6.3.2.1 General
Strengths and deformation capacities given in this
Provisions for determining alternative modeling chapter are for earthquake loadings involving three
paramelers and acceptance crítería based on experi l'ulIy reversed de1'ormation cycles to the design defor
mental evidence are given in Sectíon 2.8. malÍon levels, in addition to similar cycles to lesser
deformation levels. In some cases-including sorne
6.3.1.3 Fkmged Construction short-period buildings and buildings subjecled to a
In beams consisting of a web and t1ange that act long-duration design earthquake-a building may be
integrally, the combined stiffness and strength for t1ex expected to be subjected to additional cycles lo the
ural and axial loading shaIl be calculated considering design de1'ormation levels. 'fhe ¡ncreased number 01'
a width of etl'ective tlange on each side of the web cycles may lead to reductions in resistance and defor
equal to the smaller of: (1) the provided t1ange widlh; mation capacity. 'fhe effects on strength and deforma
(2) eight times the tlange thickness; (3) hall' the dis tÍon capacity of addilionaJ deformatiun cycles should
tance lo the next web; or (4) one-tifth of the span for be considered in designo Large earthquakes will cause
beams. Where the tlange is in compression, bolh the additional cycles.
concrete and reinforcement within lhe effective width
shaIl be considered effective in resisting tlexure and 6.3.2.2 Deformation.Controlled Actions
axial load. Where lhe t1ange is in tension, longitudinal Strengths used tor deformation-controlled actions
reinforcement within the effective width and what is shall be taken as equal lO expected strengths, QC¡;;'
developed beyond the critica) section shall be consid obtained experimentally, or calculated using accepted
ered fully effective for resisting flexural and axial principIes of mechanics. Expected slrengLh is defined
loads. The portion of the flange extending beyond lhe as the mean maximum resistance expected over the
155
SEISMIC REHABILlTATION OF EXISTING BUILDINGS
range ol' deformations to which the concrete compo Table 6-6. Component Ductility
nem is Iikely to be subjected. Where calculations are Demand Classiflcation
used to define expected strength, expected material
properties shall be used. Unless other procedures are Maximum Value of DCR 01'
specítied in this standard, procedures specitied in Displacement DlIclility Descriptor
ACI 318 (ACI 2002) to calculate design strengths shall
<2 Low DucLility Demand
be permined except that the strength reduction faclor,
2 to 4 Moderale Duclilily Demand
cp , shall be talcen equal to unity. Deformation capaci >4 High Ductility Demand
ties ror acceptance of deformation-conlrolled actions
calculated by nonlinear procedures shall be as speci
tied in Sections 6.4 to Section 6.12. For components calculated according lO lhe procedures of ACI 318
conslructed 01' lightweight concrete, QCE shall be mod (ACI 2002) or by other approvcd melhods. Slrenglhs
iticd in accordance with ACI 318 procedures for lighl and deformation capacities of components with mono
weighl concrete. lilhic tlanges shall be calculated considering concrete
and developed longitudinal reinforcement within the
C6.3.2.2 DeformatiOl,-Controlkd Actwns effective ilange widlh as detined in Seclion 6.3.1.3.
Expected yield strenglh of reinl'orcing steel, as Strength and deformation capacilies shall be
specitied in this standard, ineludes consideration of determined considering available development of lon
material overstrength and strain-hardening. gitudinal reinforcement. Where longitudinal reinforce
ment has embedment or developmcnt lenglh Ihat is
6.3.2.3 Force-Controlkd ActiollS insuflicient ror development of reinforcement slrength,
Strenglhs used for force-controlled actions shall flexural strenglh shalJ be calculatcd based on limiling
be taken as lower-bound strengths, QCL' obtained stress capacity ol' the embedded bar as delined in
experimentally, or calculated using established princi Section 6.3.5.
pIes of mechanics. Lower-bound strength is detined as Where Ilexural deformalion capacities are caIcu
the mean minus one standard deviation of resislance lated from basic principIes 01' mechanics, reductions in
expected over the range of del'ormations and loading deformation capacity due to applíed shear shall be
cyeles to which the concrete component is likely lo be talcen into consideration. Where using analytical mod
subjecled. Where calculations are used to define els for tlexural deformability lhat do not directly con
lower-bound slrengths, lower-bound eSlimales of mate sider effect 01' shear, and where design shear equals or
rial properties shall be used. Unless other procedures exceeds 6v'J: Al.' wheret' is in psi and Al! is gross
are specitied in this slandard, procedures specitíed in area 01' web in in. 2, the design value shall not exceed
ACI 318 (ACI 2002) to calculale design strengths shall 80% 01' the value calculated using the analytical
be permitted, except that the strength reduction factor, modeL
4>, shaIl be taken equal to unity. For components con For concrete columns under combined axial load
structed of lightweight concrete, QCL shall be moditied and biaxial bending, the comhined strenglh shall be
in accordance with ACI 318 procedures for light evaluated considering biaxial bending. Where using
weight concrete. linear procedures, the design axial load, P ilF, shall be
calculated as a force-conlrolled action in accordance
6.3.2.4 Component Ductility Demand Classification with Section 3.4. The design momenls, M ilD , shall be
Where procedures in Ihis chapter require classifi calculated about each principal axis in accordance
cation ol' component ductility demand, componems with Section 3.4. Acceplance shall be based on the
shall be c1assitied as having low, moderate, or high folIowing equation:
ductility demands, based on the maximum value ol' the
demand capacity ratio (DCR) defined in Section 2.4.1
(Eq.6-1)
for linear procedures, or the caJculated displacement
ductility ror nonlinear procedures in accordance with
where
Table 6-6.
M ilDx design bending moment about x-axis l'or axial
6.3.3 Flexure and Axial Loads load P ilF, kip-in.;
F1exural slrength and deformation capacity of M UDY design bending momenl about y-axis for axial
members with and wilhout axialloads shall be load PUF' lcip-in.;
156
ASCFlSEI 41-06
M CEJ. = expected bending moment strength about e1astic response such as the provisions in Chapter 11
x-axis, kip-in.; of ACl 318 shall be permitted.
M CEy = expected bending moment strength about Where the longitudinal spacing of transverse rein
y-axis, kip-in.; forcement exceeds hall' the component effective depth
m, = m-factor for column for bcnding about x-axis measured in the direction of shear, transverse rein
in accordance with Table 6-12; and forcement shall be assumed not more than 50% etTec
m)' = m-factor for column for bending about y-axis tive in resisting shear or torsion. Where the longitudi
in accordance with Table 6-12. nal spacing of transverse reinforcement exceeds the
component effective depth measured in the direction
Alternative approaches based on principIes of of shear, transverse reinforcement shall be assumed
mechanics shall be permitted. ineffeclÍve in resisting shear or torsion. For beams and
columns in which perimeter hoops are either lap
C6.3.3 Flexure and Axial Loads spliced or have hooks lhat are not adequately anchored
Laboratory tests indicate lhat flexural deformabil in the concrete core, transverse reintorcement shall be
ity may be reduced as coexisting shear forces increase. assumed not more than 50% effeclÍve in regions of
As tlexural ductility demands increase, shear capacity moderate ductility demand and shall be assumed inef
decreases, which may resuIt in a shear failure before fective in regions of high ductility demando
theoretical flexural deformation capacilies are reached. Shear friction strenglh shall bc ca1culated accord
Caution should be exercised where flexura) deforma ing to ACI 318, taking into consideration the expected
tion capacities are determined by calculation. FEMA axial load due to gravity and earthquake eff'ccts.
306 (FEMA 1998) is a resource ror guidance regard Where rehabilitation involves the addition 01' concrete
ing the interaction between shear and tlexure. requiring overhead work with dry-pack, the shear fric
tion coefficient, Ji, shall be taken as equal to 70% of
6.3.3.1 Usable Strain Limits the value specitled by ACI 318.
Wilhout contining lransverse reinforcemenr, the
maximum usable strain al lhe extreme concrete com 6.3.5 Development and Splices of Reinforcement
pression tiber shall not exceed 0.002 for components Development oí' straight bars, hooked bars, and
in nearly pure compression and 0.005 for other com lap-spliced bars shall be calculated according to the
ponents unless larger strains are substanliated by provisions of ACI 318 (ACI 2002), with the following
experimental evidence and approved by the authority moditicalÍons:
having jurisdiction. Maximum usable compressive
l. Deformed straight bars, hooked bars, and lap
strains for confined concrete shall be based on experi
spliced bars shall meet the dcvelopment require
mental evidence and shall consider Iimítatíons posed
ments of Chapler 12 of ACI 318 except require
by fracture 01' transverse reinforcement, buckling of
menls for lap splices shall be the same as lhose for
longitudinal reinforcement, and degradadon 01' compo
straight development oí' bars in tension without
nent resistance at large deformation levels. Maximum
consideralÍon 01' lap splice c1assitications;
compressive strains in longitudinal reinforcement shall
2. Where exisling deformed straighl bars, hooked
not exceed 0.02, and maximum (ensile strains in longi
bars, and lap-spliced bars do nol meet the develop
tudinal reinforcement shall not exceed 0.05.
ment requirements 01' (1) aboye, the capacity of
existing reinforcement shall be ca1culated usíng
6.3.4 Shear and Torsion
Eq.6-2:
Strengths in shear and (orsion shall be caIculated
according to ACI 318 (ACI 20(2) except as moditied
in this standard. (Eq.6-2)
Within yielding regions of components with mod
erate or high ductility demands, shear and torsional
strength shall be calculated according to procedures where.t = maximum stress that can be developed
for ductile components, such as the provisions in in the bar for the straight devc10pment, hook, or lap
Chapter 21 of ACI 318. Within yielding regions of splice length h provided;/y yield slrength of
components with low ductility demands and outside reinforcemenl; and Id = length required by Chap
yielding regions for al! ductilíty demands, calculation ter 12 of ACI 318 for straight development, hook
of design shear strength using procedures for etTective development, or lap splice length, except required
157
SEISMIC REHABILITATION OF EXISTlNG BUlLDlNGS
splíce lengths may be taken as straight bar develop ensure design strengths are developed in
ment lengths in tensíon. Where transverse rein accordance with Section 6.3.
forcement is distributed along the development
length with spacing not exceeding one-third of the C6.3.5 Development and Splices oC ReinCorcement
effectíve depth 01' the component, it shaII be per Developmenl requirements in accordance wilh
mitted to assume lhe reinforcement retains the cal Chapter 12 of ACI 318 (ACI 2(02) will be applicable
culated maximum stress to high ductility demands. to development 01' bars in all components. Chapter 21
For larger spacings 01' transverse rein1'orcemenl, the 01' ACI 318 provides development requirements that
developed stress shall be assumed lo degrade from are only intended for use in yielding components of
f. al a ductilíty demand or DCR equal to 1.0 to 0.2f. reinforced concrete moment frames thal comply wilh
al a ductility demand or DCR equal to 2.0; the cover and continement provisions 01' Chapter 21.
3. Strength of deformed straight, discontinuous bars Chapter 12 permits reductions in Jengths if mini
embedded in concrete sections or beam-column mum cover and confinement exist in an existing
joints, with clear cover over the embedded bar not component.
less than 3db , shall be calculated according lO Experimental tests by Melek and Wallace (2004)
Eq.6-3: and Lynn (2001) have demonstrated that lap splices
can achieve a higher flexural capacity than that calcu
(Eq. 6-3) lated using the effective steel stress given in Eq. 6-2.
The possibility 01' a shear failure in lap-spliced
where columns may go undetected if the tlexural capacity ís
underestimated. Cho and Pincheira (2006) suggest an
f. = maximum stress (in psi) that can be devel alternative model for the effective steel stress in lap
oped in an embedded bar having embedment splice bars which provides a beUer estimate of the
length 1, (in in.); mean tlexural strength observed in experimental tests.
db = diameter of embedded bar (in in.); and For buildings constmcted prior to 1950, the bond
J; = bar yield stress (in psi). strength developed between reinforcing steel and con
crete may be less lhan present-day strength. Current
Where j, is less than 1;., and the calculated stress in equations for development and splices ol' reinforcement
the bar due to design loads equals or exceeds L the account l'or mechanical bond due to deformations pres
maximum developed stress shall be assumed to ent in deformed bars in addition to chemical bond. The
degrade l'romJ: to 0.2f, at a ductility demand or length required lO develop plain bars will be much
DCR equal to 2.0. In beams with short bottom bar greater than that required for deformed bars, and will be
embedments into beam-column joints, flexural more sensitive 10 cracking in the concrete. Procedures
strength shall be calculated considering the stress for testing and assessment 01' tensile lap splices and
Iimitalion of Eq. 6-3; developmenllenglh of plain reinforcing sleel may be
4. For plain straight bars, hooked bars, and lap-spliced found in Evaluation 01 Reinlorcíng Steel Systems in Old
bars, development and splice lengths shall be taken Reinlorced Concrete Srructures (CRSI 1981).
as twice the values determined in accordance
wíth ACI 318 unless other lengths are justitied by
approved tests or calculations considering only the 6.3.5.1 Square Reinforcing Bars
chemical bond between the bar and the concrete; Square reinforcing bars in a building shall be clas
5. Doweled bars added in seismic rehabilitation shall sitied as either twisted Of straight. The developed
be assumed to develop yield stress where all the strength 01' lwisted square bars shall be as specified for
following conditions are satislied: deformed bars in Scction 6.3.5, using an etl'ective
5.1. Drilled holes for dowel bars are cleaned with a diameter calculated based on the gross area 01' the
stiff brush that extends the length 01" lhe hoJe; square bar. Straight squal'e bars shall be considered as
and plain bars, and the developed strcngth shall be as
5.2. Embedment length le is not less than 10d,¡; amI specified 1'01' plain bars in Section 6.3.5.
5.3. Minimum spacing of dowel bars is not less
than 4/f and minimum edge distance is not 6.3.6 Connections to Existing Concrete
less than 2/e' Design values for dowel bars nO[ Connections used to connect two 01' more compo
salisl'ying these conditions shall be verilied by nents shall be classitied according lo their anchoring
test data. Field samples shall be obtained 10 systems as cast-in-place 01' as posl-installcd.
158
ASeE/SE! 41-06
159
SEISMIC REHABILlTATION OF EXISTING BUILDlNGS
This classitication shall include existing construc The beam-column joint in monolithic construc
tion, new construction, and existing construction that tion shaIl be represented as a stiff or rigid zone having
has been rehabilitated. horizontal dimensions equal to the column cross-sec
tional dimensions and vertical dimension equal lO lhe
6.4.1.3 Slab-Column Moment Frames beam depth, except thal a wider joint shall be permit
Slab-column moment 1'rames shaJI satis1'y the 1'01 ted where the beam is wider lhan the column and
lowing conditions: where justitled by experimenlal evidence. The model
01' the conneclion between lhe coJumns and foundation
1. Framing componenls shall be slabs (with or with shall be selected based on the details 01' the column
out beams in [he transverse direction), columns, foundaLion connection and rigidity of Lhe foundation
and their conneclions; soil system in accordance with Section 6.12.
2. Frames shall be 01' monolithic conslruction thal Action of the slab as a diaphragm interconnecting
provides for moment transfer between slabs and vertical components shall be represented. Action of the
columns; and slab as a composite beam tlange shall be considered in
3. Primary reinforcement in slabs contributing to lat developing stiffness, strength, and deformation capad
eral load resistance shall include nonprestressed tíes of the beam component model, according to
rein1'orcement, prestressed rein1'orcement, 01' Section 6.3.1.3.
both. Inelastic aClion shall be restricted lO those compo
nents and actions listed in Tables 6-7 through 6-9,
This classification shall inc\ude frames inlended except where it is demonstrated by experimental evi
as part of the laLeral-force-resisting system and frames dence and analysÍs that other inelaslÍc action is accept
not intended as pan of the lateral-force-resisting sys able for the selected performance leve\. AccepLance
tem in the original design, including existing construc criteria shall be as specified in Section 6.4.2.4.
tion, new construclion, and exisling construction that
has been rehabilitated.
6.4.2.2 StiHness for Analysis
6.4.2 Reinforced Concrete Beam-Column Moment
Frames 6.4.2.2.1 Linear Static aruJ Dynamic Procedures Beams
shall be modeled considering flexural and shear stijf
6.4.2.1 General Considerations nesses, including the eftect 01' the slab acting as a flange
The analylical model for a beam-column frame in monolithic construction. eolumns shall be modeled
element shall represent strength, stitrness, and defor considering flexural, shear, and axial stiffnesses. Joints
mal ion capacity of beams, columns, beam-column shall be modeled as either stiff or rigid components.
joinls, and other components of the frame, inc1uding Effective stiffnesses shall be according to Section 6.3.1.2.
connections with other elemenls. Potenlial failure in
tlexure, shear, and reinforcement development at any 6.4.2.2.2 Nonlinear Static Procedure NonIínear
section along the component length shall be consid load-deformation relations shall follow the require
ered. Interaction wilh other elements, including non ments of Section 6.3.1.2.
structural components, shall be inc\uded. Beams and columns shall be modeled using con
AnalyLical models representing a beam-column centrated plastic hinge models or distributed plaslic
frame using line elements wíth properties concentrated hinge models. Other models whose behavior has been
at component centerlines shall be permitted. Where demonslrated to represent (he behavior 01' reinforced
beam and column centerlines do not intersect, the concrete beam and eolumn components subjected Lo
effects of the eccentricÍly between centerlines of fram lateralloading shall be permitted. The beam and col
ing shall be taken into account. Where lhe centerline umn model shall be capable 01' representing ine\astic
of the narrower component falls within the middle response along the componenl length, except where it
Lhird of lhe adjacent framing component measured is shown by equilibrium Iha! yielding is restricted to
transverse to the framing direction; however, lhis the component ends. Where nonlinear response is
eccentricity need not be consídered. Where larger expecled in a mode other than tlexure, lhe model shall
eccenlricities occur, the effect shall be represented be established to represenl these etrects.
either by reductions in eflective stítlness, strength, Monotonic load-deformation relations shall be
and deformatÍon capacity, or by direct modeling of according to the generalized 10ad-deformatÍon relation
the eccentricity. shown in Fig. 6-1, except Ihat different relalions shall be
160
ASCE/SEI 41-06
Table 6-7. Modeling Parameters and Numerical Acceptance Criteria for Nonlinear Procedures-Reinforced
Concrete Beams
permitted where veritied by experiments. The overall points B, C, and D shall be derived from experi
load-deformation relation shall be established so thal ments or rational analyses, and shall take into
!he maximum resistance is consistent with the design accounl the interactions between tlexure, axial load,
strength specifications of Sections 6.3.2 and 6.4.2.3. and shear.
For beams and columns, the generalized de
formation in Fig. 6-1 shall be either the chord rota C6.4.2.2.2 Nonlinear Static Procedure Refer to
lion or the plastic hinge rotation. For beam-column Sections C6.3.1.2 and C6.4.2.3.l for discussion of
joinls, the generalized deformation shall be shear ahernative modeling paramelers for reinforced con
strain. Values of the generalized deformatíon al crete columns.
161
SEISMIC REHABILlTATION OF EXISTING BUILDINGS
Table 6-8. Modeling Parameters and Numerical Acceptance Criteria for Nonlinear Procedures
Reinforced Concrete Columns
Performance Level
Residual
Componenl Type
Plastic Rotations Strength
Angle, radians Ratio Primary Secondary
Conditions a b e 10 LS CP LS CP
JWhere more than one of the conditions i, ii, í¡j, and iv occurs for a given componen!, use the mínimum appropríale numerícal value from the
table.
4To qualify, columns must have transverse reinforcement consisting of hoops. Otherwisc, actions shall be treated as force-contmlled,
;For columns controlled by shear. see Section 6.4.2.4,2 for prímary componen! acceptance crileria. Primary and secondary component demands
shall be within secondary componen! acceptanee criteria where the full baekbone curve is explíeítly modeled including strength degradatíon and
residual strength in aeeordanee with Seetion 3.4.3.2.
"'C" and "NC" are abbreviations for eonforming and noneonforming transverse reinforeemenl. A component is conforming ir, within the tlexural
plastíc hinge region, hoops are spaeed al :5 d13. and if, rOl' componenls of moderale ami high duetility demando tbe slrenglh províded by the
hoops (V,) is at least Ihree-fourths of the desígn shear. Otherwise, tbe component is eonsidered nOllconforming.
162
ASCE/SEI 41-06
Table 6-9. Modeling Parameters and Numerical Acceptance Criteria for Nonlinear Procedures-Reinforced
Concrete Beam-Column Joints
163
SEISMIC REHABILlTATION OF EXISTING BUILDINGS
6.4.2.3. / Columns For columns, the shear strength, V", 2002), the shear strength equations of ACI 318 shaIl
calculated according to Eq. 6-4 shall be permiued. be permiued to be used.
For beam-column joints, the nominal cross
~, )0.8A
+ Ák(6VJ[
-y11 + 6Vj[
V = k A.j;.d sectional area, Aj, shall be dctined by a joint depth
11 s M/Vd Ag g equal to the column dimension in the direction of
(Eq. 6-4) framing and a joint width equal to the smallest of
where (1) the column width, (2) the beam width plus the
joint depth, and (3) twice the smaller perpendicular
k = 1.0 in regions where displacement ductility is distance from the longitudinal axis o .. the beam LO the
less than or equal to 2, 0.7 in regions where column side. Design lorces shall be calculated based
displacement ductility is greater than or equal on development of tlexural plaslic hinges in adjacenl
to 6, and varies linearly for displacement framing members, inc1uding etfective slab width, but
ductility between 2 and 6; need not exceed values calculated from design gravity
Á = 0.75 for Iightweight aggregate concrete and and earlhquake-Ioad combinations. Nominal joint
1.0 for normal weight aggregate concrete; shear strength, Vn, shall be calculaled according to the
N" = axial compression force in pounds O for general procedures o.. ACI 318, as moditied by Eq. 6-5:
tension force);
M/Vd = lhe largest ratio ofmoment lo shear times (Eq.6-5)
etTective depth under design loadings for the
column but shall not be taken greater than 4 in which Á = 0.75 for lightweight aggregate concrete
or less than 2; and 1.0 for normal weight aggregate concrete, Aj is the
d = the effective depth; and etrective horizontal joint area with dimensions as
Ag = (he gross cross-sectional area of the column. detined aboye, and y is as delined in Table 6- JO.
It shall be permitted to assume d = 0.8h, where h C6.4.2.3. / Columns As discussed in C6.3.3, experi
is the dimension of the column in the directÍon of mental evidence indicates Ihat flexural defonnability
shear. Where axial force is calculated from Ihe linear may be reduced as coexisting shear force s increase. As
procedures of Chapter 3, the maximum compressive tlexural ductility demands increase, shear capacity
axial load for use in Eq. 6-4 shalI be taken as equal to decreases, which may result in a shear failure before
the value calculated using Eq. 3-.4 considering design theoretical flexural dcl"ormation capacities are reached.
gravity load only, and lhe minimum compression axial CautÍon should be exercised when tlexural deforma
load shall be calculaled according to Eq. 3-18. tion capacities are determined by calculation.
Alternatively, limit analysis as specitied in Section The modeling paramctcrs and acceptance crileria
3.4.2.1.2 shall be permitted lo be used to delermine in Table 6-8 are generally conservative, and may be
design axialloads ror use wilh Ihe linear analysis pro relaxed based on experimental evidence. The design
cedures of Chapter 3. Alternative formulations for col professional is referred to reports by Berry and
umn strength thal consider effects of reversed cyclic, Eberhard (2005); Elwood and Moehle (2oo5a;
inelastic deformations and thal are veritied by experi 2oo5b); Fardis and Biskinis (2003); Biskinis et al.
mental evidence shall be permitted. (2004); Panagiotakos and Fardis (2001); Lynn et al.
For columns satisfying the detailing and pro por (1996); Sezen (2002); and Elwood and Moehle (2004)
tioning requirements of Chapter 21 of ACI 318 (ACI ror further guidance regarding determination of model-
Value of Y
Knee Joint with
Interior Joint wilh Interior Joint wilhout Exterior Joint with Exterior Joint without or without
p"l Transverse Beams Transverse Beams Transverse Beams Transverse Beams Transverse Beams
< 0.003 12 10 8 6 4
2: 0.003 20 15 15 12 8
164
ASCElSEI 41-06
ing parameters and acceptance criteria for reinforced controlled actions sball be restricled lo tlexure in beams
concrete columns. (with or without slab) and columns. In secondary com
Elwood and Moehle (2005a) have demonstrated ponents, deformation-controlled actions shall be
based on experimental evidence that Eq. 6-4 does not restricted to tlexure in beams (with or without slab),
provide a reliable estimate of the displacement ductil plus restricted actions in shear and reinforcement
ity al shear failure. development, as identified in Tables 6-11 through 6
13. AH other actions shall be detined as being force
6.4.2.4 Accept6llee eriteria controlled actions.
Design actions on components shall be deter
6.4.2.4.1 Linear Static and Dynamic Procedures AIl mined as prescribed in Chapter 3. Where the calcu
actions shall be classiJied as being either deformation lated DCR values exceed unity, the folIowing design
cOnlrolled or force-controlled, as defined in Sec actions shall be determined usíng límil analysis princi
tion 2.4.4. In primary components, deformation pies as prescribed in Chapter 3: (l) moments, shears,
m-Factors l
Performance Level
Component Type
Primary Secondary
Condilions 10 LS CP LS CP
i. 8eams Controlled by Flexure2
4
p p' Transverse JI'
Reinforcement 3
Pbal b,.4VJ:
$ 0.0 C $3 3 6 7 6 10
$ 0.0 C :2:6 2 3 4 3 5
:2: 0.5 C $3 2 3 4 3 5
:2: 0.5 C :2:6 2 2 3 2 4
$ 0.0 NC $3 2 3 4 3 5
$ 0.0 NC :2:6 1.25 2 3 2 4
:2: 0.5 NC $3 2 3 3 3 4
:2: 0.5 NC :2:6 1.25 2 2 2 3
ii. Beams Controlled by Shear1
Stirrup Spacing $ d/2 1.25 1.5 1.75 3 4
Stirrup Spacing > d/2 1.25 1.5 1.75 2 3
iii. Beams ControUed by lnadequale Development or Splicing along the Span 2
Stirrup Spacing $ d/2 1.25 1.5 1.75 3 4
Stirrup Spacing > d/2 1.25 l.5 1.75 2 3
IV. Beams Controlled by Inadequate Embedment into Beam-Column Joint2
2 2 3 3 4
165
-----------""'" .. _-_. _..
torsions, and development and splice actions corre Design actions shall be compared with design
sponding to development of component strength in strenglhs in accordance with Seclion 3.4.2.2. m-factors
beams and columns; (2) joint shears corresponding lo shall be selected from Tables 6-11 through 6-13.
development of strength in adjacenl beams and Those componenls lhat satisfy Eq. 3-20 or 3-21, as
columns; and (3) axial load in columns and joints, applicable, shall comply Wilh lhe performance crÍleria.
considering likely plastic aclion in componenls above Where lhe average OCR of coJumns al a level
the level in question. exceeds the average value of beams al the same level, and
m-Factors 1
Performance Level
Component Type
Primary Secondary
Conditions 10 LS CP LS CP
i. Columns Controlled by Flexure1
~4 Transverse V
Ag¡; Reinforcemenl' b.dVjj
~ 0.1 C ~3 2 3 4 4 5
~ 0.1 C ~6 2 2.4 3.2 3.2 4
0.4 C ~3 1.25 2 3 3 4
~ 0.4 C ~6 1.25 1.6 2.4 2.4 3.2
~ 0.1 NC ~3 2 2 3 2 3
~ 0.1 NC ~6 2 2 2.4 1.6 2.4
~ 0.4 NC ~3 1.25 1.5 2 1.5 2
~ 0.4 NC ~6 1.25 1.5 1.75 1.5 1.75
ii. Columns Controlled by Shear1,6
Hoop Spacing ~ d/2, or ~ ~ 0.1 2 3
Agle
Other Cases L5 2
¡j¡. Columns Controlled by Inadequate Developmenl or Splícing along the Clear Heigh(2·6
Hoop Spacing ~ d/2 1.25 1.5 1.75 3 4
Hoop Spacing > d/2 2 3
¡v. Columns wilh Axial Loads Exceeding 0.70P}·6
Conforming Hoops over the Entire Lenglh 1 2 2 2
AlI Other Cases
166
ASCE/SEI 41-06
exceeds lhe grealer of 1.0 and ml2 for all columns, lhe dure, or the struclure shall be rehabililated lo elimi
level shall be detined as a weak slory e1ement. For weak nale Ihis deficiency;
story elemenls, one of lhe following shall be satisfied: 2. The slruclure shall bc reanalyzed using eilher lhe
NSP or lhe NDP of Chapter 3; and
1. The check of average DCR values al lhe level shall 3. The slruclure shall be rehabilitated to remove Ihe
be repealed, considering all primary and secondary weak story element.
componenls al Ihe level Wilh a weak slory element.
Ir lhe average of Ihe DCR values for vertical com 6.4.2.4.2. Nonlinear Statie and Dynamic Proeedures
ponenLs exceeds Ihe average value for horizontal Calculated component actions shalJ satisfy Ihe require
componenls at the level, and exceeds 2.0, lhe struc menls of Secuon 3.4.3.2. Where Ihe generalized defor
lUre shall be reanalyzed using a nonlínear proce mation is taken as rotalion in the flexural plastic hinge
m-Factors l
Performance Level
Component Type
Primary2 Secondary
Condítíons 10 LS CP LS CP
i. Interior Joints 3.4
p Transverse V
AJ; Reinforcement5 v"
s 0.1 C 1.2 3 4
s 0.1 C 1.5 2 3
~ 0.4 C 1.2 3 4
~ 0.4 C 1.5 2 3
s 0.1 NC 1.2 2 3
s 0.1 NC 1.5 2 3
~ 0.4 NC 1.2 2 3
~ 0.4 NC 1.5 2 3
ii. Other Joints3.4
p Transverse V
A~f: Reinforcement'
v"
s 0.1 C s 1.2 3 4
s 0.1 C 1.5 2 3
~ 0.4 C 1.2 3 4
~ 0.4 C ~ 1.5 2 3
s 0.1 NC 1.2 2 3
s 0.1 NC 1.5 2 3
~ 0.4 NC s 1.2 1.5 2.0
~ 0.4 NC 1.5 1.5 2.0
167
SEISMIC REHABILlTATION OF EXISTING BUILDlNGS
zone in beams and columns, the plastic hinge rotation and should be dcsigned considcring possible force
capacities shall be as detined by Tables 6-7 and 6-8. variations due to earthquakc loading;
Where lhe generalized deformation is shear distortion 3. Modification of the element by selective material
01' the beam-column joint, shear angle capacilies shall removal from the existing element. Examples
be as delíned by Table 6-9. For columns designated as indude: (1) where nonstructural componcnts inter
primary components and for whích calculated design ferc with the frame, removing or separating the
shear exceeds design shear strenglh, the permissible nonstrucLUral components to eliminale Ihe interfer
deformation for lhe Collapse Prevenlion Performance ence; (2) weakening, due to removal 01' concrete 01'
Level shall not exceed the defOlmation at whieh shear severing of longiludinal reinforcement, to change
strength is calculated to be reached; the permissible response mode from a nonductile mode to a more
de1'ormation 1'or lhe Life Safety Performance Level ductile mode (e.g., weakening of beams to pro mote
shaIl nm exceed lhree-quarters of that value. Where formation of a strong-column, weak-beam system);
inelaslic aclion is indicated for a component or action and (3) segmenting wall s to change still'ness and
nol listed in these tables, the performance shall be strength;
deemed unacceptable. Alternative approaches or val 4. Improvement of defident existing reinforcement
ues shall be permitted where juslified by experimental details. Removal of cover concrete ror modiJica
evidence and analysis. tion of existing reinforcement details should avoid
damage to core concrete and the bond bel ween
C6.4.2.4.2 Nonlinear Static and Dynamic Procedures existing reinforcement and cme concrete. New
Refer to Section C6.4.2.3.1 for discussion of aILerna cover concrete should be designed and conslructed
tive acceptance criteria for reinforced concrete to achicve fully composite actíon wilh lhe existing
columns. malerials;
5. Changing the building system to reduce the
6.4.2.5 Relwbilitation Measures demands on the existing element. Examplcs
Concrete beam-column moment frame compo indude addilion of supplementary lateral-force
nenls that do not meet the acceptance crileria for the resistíng elements such as walls or buttresses, seis
selected rehabilitation objective shall be rehabilitaled. mic isolation, and mass reduction; and
RehabiJitation measures shall meet lhe requirements of 6. Changing the frame element to a shear wall,
Section 6.3.7 and other provisions of this standard. infilled frame, or braced frame elernent by addi
tion of new material. Connections betwcen new
C6.4.2.5 Rehabilitation Measllres and exisling materials should be designed to lrans
The folJowing rehabilitalion measures may be fer the forces anticipated for lhe design load combi
effective in rehabilitating reinforced concrete nations. Wherc the existing concrete frame columns
beam-column moment frames: and beams act as boundal'Y componcnts and coIlec
tors for the new shear wall or braced frame, these
l. Jacketing existing beams, columns, or joints
should be checkcd for adequacy, considering
with new reinforced concrete, steel, or fiber
strength, reinforcemenl developmcnt, and defofma
wrap overlays. The new malerials should be
bility. Diaphragms, including lies and colleclors,
designed and constructed to acl compositely with
should be evaluated and, if necessary, rehabílilated
the existing concrete. Where reinforced concrete
to ensure a complete load path to the new shcar
jackets are used, the design should provide dctail
waJl or braced frame elemcnt.
ing to enhancc ductility. Component slrength
should be taken to not exceed any limiting slrenglh
01' conneclions with adjacenl cornponents. Jackels 6.4.3 Post-Tensioned Concrete Beam-Column
should be desígned to provide increased conneclion Moment Frames
strength and improved continuity between adjacent
components; 6.4.3.1 General COIIsiderations
2. Post-tensioning existing beams, columns, or The analytical rnodel for a posHensioned con
joints using external post-tensioned reinforce crete beam-column frame element shall be eslablished
mento Post-tensioned reinforcement should be foJlowing the criteria specitied in Section 6.4.2.1 for
unbonded within a dístance equal lo twice lhe reinforced concrete beam-column moment trames. In
etl'ectÍve depth frorn sections where inelastic action addition lo potential failure modes described in
is expected. Anchorages should be localed away Seclion 6.4.2.1, the analysis model shall consider
from regions where inelastic action is anticipaled, potential failure 01' lendon anchorages.
168
ASeE/SEI41-06
The analysis procedures described in Chapter 3 shall be modeled using properties verified by experi
shall apply to frames with post-tensioned beams satis mental evidence. The relation of Fig. 6-1 shall be
fying the folJowing conditions: taken to represent the envelope relation fór the analy
siso Unloading and reloading properties shall represent
1. The average prestress,Jpc, caJculated for an area
significant stiffness and strength degradation charac
equal to the product of the shortest cross-sectional
teristics as influenced by prestressing.
dimension and the perpendicular cross-sectional
dimension of the beam, does not exceed the
6.4.3.3 Strength
greater of 750 psi or¡;/ 12 at locations of nonlinear
Component strengths shall be computed according
action;
to the general requirements of Sections 6.3.2 and the
2. Prestressing tendons do not provide more Ihan one
additional requirements of Section 6.4.2.3. Effects of
quarter of the strenglh for both positive moments
prestressing on strength shall be considered.
and negative moments at the joint face; and
For deformation-controlled actions, prestress shall
3. Anchorages for tendons are demonstrated to have
be assumed to be effective for the purpose of deter
performed satisfactorily for seismic loadings in
mining the maximum actions that may be developed
compl iance wilh the requirements of ACI 318
associated with nonlinear response of the frame. For
(ACI 2002). lbese anchorages occur outside hing
force-controlled actions, the effecls on strength 01' pre
ing areas or joints, except in existing components
stress loss shall also be considered as a design condi
where experimental evidence demonstrates that the
tion, where these losses are possible under design
connection will meet the performance objectives
load combinations including inelastic deformatíon
under design loadings.
reversals.
Alternative procedures shall be provided where
these conditions are not satistied. 6.4.3.4 Acceplance Criteria
Acceptance criteria for post-tensioned concrete
beam-column moment frames shall foJlow the criteria
6.4.3.2 Stiffness
for reinforced concrete beam-column trames specified
in Section 6.4.2.4.
6.4.3.2.1 Linear Static and Dynamic Procedures
Modeling parameters and acceptance criteria shall
Beams shall be modeled considering tlexural and
be based on Tables 6-7 through 6-9 and 6-11 through
shear stiffnesses, including the effect of the slab acting
6-13.
as a f1ange in monolithic and composite construction.
Columns shall be modeled considering f1exural, shear,
6.4.3.5 Rehabilitation Measures
and axial stitfnesses. Joints shall be modeled as eilher
stiff or rigid components. Effective stiffnesses shall be Post-tensioned concrete beam~olumn moment
frame components that do not meet the acceptance cri
according to Section 6.3.1.2.
(ería for (he selected Rehabilitation Objective shaIl be
rehabilitated. Rehabilitation measures shall meet the
6.4.3.2.2 Nonlinear Static Procedure Nonlinear
requirements of Section 6.3.7 and other provisions of
10ad-<1eformation relalÍons shall comply with the
this standard.
requirements of Section 6.3.1.2 and the reinforced
concrete trame requirements of Section 6.4.2.2.2.
C6.4.3.5 Rehabilitation Measures
Values of the generalízed deformation at points B,
The rehabilitation measures described in C6.5.2.5
e, and D in Fig. 6-1 shalI be either derived from
for reinforced concrete beam~olumn moment frames
experiments or approved rational analyses, and shall
may also be effective in rehabilitating post-tensioned
rake into account the interactions between flexure
axial load, and shear. Alternatively, where the gen~ral
concrete beam~olumn moment frames.
ized deformation is taken as rotation in the flexural
plastic hinge zone, and where the three conditions of 6.4.4 Slab-Column Moment Frames
Sectíon 6.4.3.1 are satisfied, beam plastic hinge rota
tion capacities shaU be as defined by Table 6-7. 6.4.4.1 General COlIsiderations
Columns and joints shall be modeled as described in The analytical model for a slab-column frame ele
Section 6.4.2.2. ment shall represent strength, stiffness, and deforma
tion capacity of sIabs, columns, slab-column connec
6.4.3.2.3 Nonlinear Dynamic Procedure For the NDP, tions, and other components of Ihe trame. Potential
the complete hysteretic behavior of each component failure in f1exure, shear, shear-momenl transfer, and
169
SEISMIC REHABILlTATION OF EXISTING BUILDlNGS
reinforcemenl developmenl al any seelion along lhe 6.4.4.2.2 Nonlinear Static Procedure Nonlinear
componenllenglh shall be consídered. Inleraetion wilh load-deformalion relalions shall comply Wilh lhe
olher componenls, including nonslruelural eompo requiremenls of Seclion 6.3. I .2.
nents, shall be included. Slabs and columns shall be modeled using con
The analytical model lhal represents lhe slab-col cenlraled plaslic hinge models, dislribuled plaslic
umn frame, using eilher line elemenls wilh properties hinge models, or olher models whose behavior has
concenlraled al eomponent centerlines or a combina been demonstraled lo adequalely represent behavior of
lion oí" line elemenls (lO represenl columns) and plale reinforced concrele slab and column componenls sub
bending elements (to represent lhe slab), based on any jected lO laleralloading. The model shall be capable of
of lhe füllowing approaches, shall be permitted: represenling ¡nelastic response along lhe componenl
length, excepl where it ís shown by equilibrium lhal
l. An effeetive beam width model, in which lhe
yielding is reslricled lo the component ends. Slab-
columns and slabs are represenled by line elemenls
column conneclions shall be modeled separalely from
that are rigidly inlereonnecled allhe slab-column
lhe slab and column componenls in order to idenlify
joint. The etl'eelive widlh shall be ca\culated in
pOlential 1'ailure in shear and moment lranSrer; alterna
accordance wilh the provisions ofACI 318
lively, lhe potential for connection failure shall be
(ACl2002);
olherwise checked as parl of lhe analysis. Where non
2. An equivalenl frame model in which lhe columns
linear response is expected in a mode other lhan flex
and slabs are represented by line elemenls thal
ure, the model shall be established lo represent lhese
are inlerconnecled by conneclíon springs;
effecls.
and
Monolonic load-deformalion relalions shall be
3. A finile elemenl model in which lhe coJumns are
aecording to lhe generalized relation shown in
represented by line elements and lhe slab is repre
Fig. 6-1, wilh detinilions according 10 Seclion 6.4.2.2.2.
senled by plate-bending elemenls.
The overall load-deformalion relalíon shall be estab
lished so that lhe maximum resistance is consistent
In any model, lhe effects 01' changes in cross sec
with the design strenglh specítications of Seclions 6.3.2
tíon, including slab openings, shall be consídered.
and 6.4.4.3. Whcre the generalized deformalion shown
The conneclion between lhe columns and founda
in Fig. 6-1 is laken as lhe flexural plaslic hinge rola
lion shalI be modeled based on lhe details of lhe
lion for lhe column, lhe plaslic hinge rolalion capaci
column-foundation conneclion and rigidily of lhe
lies shall be as defined by Table 6-8. Where lhe
foundalíon-soíJ syslem.
generalized deformalion shown in Fig. 6-1 is taken
Aclion of lhe slab as a díaphragm inlerconnecting
as lhe rolalion of lhe slab-column conneclion, lhe
vertical elemenls shall be represenled.
plaslic rOlalinn capacities shall be as detined by
In lhe desígn model, inelaslic deformations in
Table 6-14.
primary componenls shaJ1 be restricted to flexure in
slabs and columns, plus nonlinear response in slab-
column conneclions. Other inelastic dcí'ormations 6.4.4.2.3 Nonlinear Dynamic Procedure The require
shall be permiued as part oí' lhe design in secondary ments of Seclions 6.3.2 and 6.4.2.2.3 for reinforced
components. Acceptance criteria shall be as specitied concrete beam-column moment trames shall apply lo
in Sectíon 6.4.4.4. slab-column momen! frames.
170
ASCE/SEI 41-06
Table 6-14. Modeling Parameters and Numerical Acceptance Criteria for Nonlinear Procedures-Two-way
Slabs and Slab-Column Connections
Performance Level
Residual
Component Type
Plastic Rotations Strength
Angle, radians Ratio Primary Secondary
Conditions a b e 10 LS CP LS CP
i. Slabs Controlled by Flexure, and Slab-Column Connections 3
~4 Continuity
Vo Reinforcement5
0.2 Yes 0.02 0.05 0.2 0.01 0.015 0.02 0.03 0.05
2:?: 0.4 Yes 0.0 0.04 0.2 0.0 0.0 0.0 0,03 0.04
s 0.2 No 0.02 0.02 0.01 0.015 0.02 0.015 0.02
0.4 No 0.0 0.0 0.0 0.0 0.0 0.0 0.0
ii. Slabs Controlled by lnadequate Development or Splicing a10ng the Span3
0.0 0.02 0.0 0.0 0.0 0.0 0.01 0.02
iii. Slabs Controlled by Inadequate Embedment into Slab-Column Joint3
0.015 0.03 0.2 0.01 0.01 0.015 0.02 0.03
The flexural slrength of a slab to resist moment moment transfer strength calculated as the mínimum
due lo lateral deformalions shall be calculaled as of the following strengths shall be permitted:
M.cs Mgcs, where Mncs is the design flexural strength The strength calculaled considering eccentricity of
of the column strip and MgcS is the column strip shear on a slab crilical section due to combined shear
moment due to gravity loads. MgcS shall be calculated and moment, as prescribed in ACI 318;
according to the procedures of ACI 318 (ACI 2(02) The moment transfer strength equal to "EMn/,y¡.
for the design gravity load specitied in Chapter 3. where "EM. = the sum of positive and negative flex
For columns, the evaluation of shear strength ural strengths of a section of slab between Iines that
according to Section 6.4.2.3 shall be permitted. are two and one-half slab or drop panel thicknesses
Shear and moment Iransfer strength of the (2.5h) outside opposite faces of the column or capital;
slab-column connection shall be calculated consider "tI the fractíon of the moment resisted by flexure per
ing the combined action of flexure, shear, and torsion ACI 318; and h = slab thickness.
acting in the slab at the connectíon wíth the column. For moment about an axis parallel to the slab edge
The procedures described below shall be permüted to at exterior connections without transverse bearns,
salisfy this requirement. where the shear.on the slab critical section due to
For interior connections without transverse beams, gravity loads does not exceed O,75Vc• or the shear at
and for exterior conneclions with moment about an a corner support does nol exceed O.5Vc' the moment
axis perpendicular to the slab edge, the shear and transfer strength shall be permitted to be taken as
171
SEISMIC REHABILlTATION OF EXISTING BUILDlNGS
equa) to the flexura) strength 01' a section of slab actions shall be determined using Iimit analysis princi
between línes that are a dislance, el' oulside opposite pies as prescríbed in Chapter 3: (1) momenlS, shears,
faces of lhe column or capital. Ve is lhe direct punch lorsions, and developmem and splice aclions corre
ing shear slrenglh defined by ACI 318. sponding lo developmenL of componenL slrengLh in
slabs and columns; and (2) axial load in columns, con
6.4.4.4 Acceptance Criteria sidering likely plaslic aCLion in componenls aboye the
level in question.
6.4.4.4. J Linear Statie and Dynamie Procedures AH Design actions shalI be compared Wilh design
componenl actions shall be classified as being either slrenglhs in accordance wilh Seclion 3.4.2.2 and
deformalion-conlrolled or force-controlled, as detined Tables 6-12 and 6-15. Those components LhaL
in Section 2.4.4. In primary componenls, deformation salisfy Eqs. 3-20 and 3-21 shall salisfy the per
controlled actions shall be restricted lo tlexure in slabs formance criteria. Components that reach
and columns, and shear and momenl lransfer in lheir design strenglhs shall be further evalualed
slab-column conneclions. In secondary components, according lo this seclion lo delermine performance
deformation-controlled actions shalJ also be permitted acceplabilily.
in shear and reinforcement development, as idenlitied Where Ihe average 01' lhe DCRs for columns al a
in Table 6-15. AH olher actions shall be detined as level exceeds lhe average value for slabs al the same
being force-controlled actíons. level, and exceeds lhe grealer of 1.0 and m/2, rhe ele
Design actíons on components shall be deter menL shall be defined as a weak story elemenL and
mined as prescribed in Chapler 3. Where me calcu shall be evalualed by the proce-dure for weak slory
laled OCR values exceed uníty, lhe following design elemenls described in Section 6.4.2.4.1.
m-Factors 1
Performance Level
Component Type
Primary Secondary
Conditions 10 LS CP LS CP
1
i. Slabs Controlled by F1exure, and Slah-Column Connections
~3 Conlinuity
Va Reinforcemenr
~ 0.2 Yes 2 2 3 3 4
2: OA Yes 1 1 1 2 3
~ 0.2 No 2 2 3 2 3
2: OA No 1
ii. Slabs CoOlrolled by Inadequate DevelopmeOl or Splicing along the Span1
3 4
iii. Slabs Controlled by Inadequate Embedment iOlo Slah-Co\umn Joint 2
2 2 3 3 4
J72
ASCE/SEI 41-06
6.4.4.4.2 Nonlinear Static and Dynamic Procedures In lÍon with shear walls, braced trames, or other lateral
the design model, inelastic response shall be restricted load-resisting elements.
to those components and actions listed in Tables 6-8
and 6-14, except where it is demonstrated by experi C6.5.1.1 Precast Concrete Frames Expected to Resist
mental evidence and analysis that other inelastic Lateral Load
action is acceptable for the selected performance These systems are recognized and accepted by
levels. FEMA 450 (FEMA 2004) and are based on ACI 318
Calculated component actions shall satisfy the (ACI 2002), which specities safety and serviceability
requirements of Chaptcr 3. Maximum permissible levels expected from precast concrete trame construc
inelastic deformations shaJl be as listed in Tables 6-8 tion. In the referenced documents, precast trames are
and 6-14. Where inelastic action is indicated for a cJassitied not by the method of construction (wet or
component or action not Iisted in these tables, the per dry joints) but by the expected behavior resulting from
formance shall be deemed unacceptable. Alternative the detailing used. In addition to recognizing varying
approaches or values shall be permitted where justitied levels of ductile performance as a result of overall
by experimental evidence and analysis. frame detailing, ACI 318 (in Section 2 \.6) acknowl
edges three types of unÍt-to-unit connections that can
6.4.4.5 Rehabilitation Measures result in the highest level of performance. Such con
Reinforced concrete slab-column moment frame nections are either "strong" or "ductile" as detined in
components that do not meet the acceptance criteria Sections 21.1 and 21.6 of ACI 318, or have demon
for the selected Rehabilitation Objective shall be reha strated acceptable performance where tested in accOf
bilitated. Rehabilitation measures shall meet the dance with ACI T\.I-Ol (ACI2ool).
requirements of Section 6.3.7 and other provisions of
this standard. 6.5.1.2 Precast Concrete Frames Not Expected to
Resist Lateral Load Directly
C6.4.4.5 Rehabilitation Measures Frames of this cJassification shall be assembled
The rchabilitation measures described in C6.5.2.5 using dry joints in a way that does not result in signiti
for reinforced concrete beam-column moment frames cant lateral force resistance in the framing element.
may also be effective in rehabilitating reinforced con Shear walls, braced frames, Of moment frames provide
crete slab-column moment frames. the entire lateral load resistance, with the precast con
crete frame system deforming in a manner that is com
patible with the structure as a whole.
6.5 PRECAST CONCRETE FRAMES
6.5.2 Precast Concrete Frames Expected to Resist
6.5.1 Types oC Precast Concrete Frames Lateral Load
Precast concrete frames shall be detined as those
elements that are constructed from individually made 6.5.2.1 General Considerations
beams and columns that are assembled to create The analytical model for a frame element of this
gravity-Ioad-canying systems. These systems shall cJassitication shall represent strength, stiffness, and
incJude those that are considered in design to resist deformation capacity of beams, columns, beam
design lateral loads, and those that are considered in column joints, and other components of the frame.
design as secondary elements that do not resist design Potential failure in flexure, shear, and reinforcement
lateral loads but must resist the effects of deformations development at any section along the component
resulting from design lateralloads. length shall be considered. Interaction with other com
ponents, incJuding nonstructural components, shall be
6.5.1.1 Precast Concrete Frames Expected to Resist incJuded. All other considerations of Section 6.4.2.1
Lateral Load shall be taken into account. In addition, the effects of
Frames of this cJassitication shall be assembled shortening due to creep, and other effects of prestress
using either reinforcement and wet concrete or dry ing and post-tensioning on member behavior, shall be
joints (connections are made by bolting, welding, post evaluated. Where dry joints are used in assembling the
tensioning, or other similar means) in a way that precast system, consideration shall be given to the
results in signiticant lateral force resistance in the effect of those joints on overall behavior. Where con
framing elemen!. Frames of this cJassitication resist nections yield under design lateral load s, the analysis
lateral loads either acting alone, or acting in conjunc model shall take this into account.
173
SElSMIC REHABILlTATION OF EXISTlNG BUILDlNGS
174
ASeE/SEI 41-06
6.5.3.5 Rehabilitation Measures the infills were constructed to fin the space within the
Precasl concrete trame components that do bay of a complete gravity frame wilhoUI spedal provi
not meet the acceptance criteria for the selected sion for conlinuity from story to story. The concrele of
Rehabilitation Objectíve shaJl be rehabilitated. the ¡nfill shall be evaluated separalely from lhe con
Rehabilitarían measures shall meer the requiremenrs of crete ol' lhe l'rame.
Section 6.3.7 and orher provisions of this standard.
C6.6.1.3 Concrete Itifills
C6.5.3.5 Rehabilitation Measures The construction ol' concrete-infilJed frames is
The rehabilitaríon measures described in C6.4.2.5 very similar to that of masonry-infilled trames, except
for reínforced concrete beam-column moment frames that lhe ¡nfill is ol' concrete inslead of masonry unils.
may also be effective in rehabilitating precast concrete In older existing buildings, the concrete infill com
trames not expected lO resist lateral loads directly. monly contains nominal reinforcement, which is
When instalJing new components or malerials to the unlikely to extend into lhe surrounding frame. The
existing system, existing prestressing strands should concrete is likely to be ol' lower quality than that used
be protected. in the frame, and should be investigated separately
l'rom investigations ol' the trame concrete.
6.6 CONCRETE FRAMES WITH INFILLS 6.6.2 Concrete Frames with Masonry Infills
175
SEISMIC REHABILlTATION OF EXISTING BUILDlNGS
the evaluation shall inelude the reduced etfective 6.6.2.2.2 Nonlinear Statk Procedure Nonlinear
length of the columns aboye the intilled portion ol' load-deformation relations for use in analysis by NSP
the bay. shall follow the requirements ol' Seetion 6.3.1.2.2.
Modeling beams and columns using nonlinear
C6.6.2.1 General Considerations truss elemenLs shalI be permiued in infilled portions ol'
The design professional is rel'erred to FEMA 274 (he frame. Beams and columns in non-infilled portions
(FEMA 1997) and FEMA 306 (FEMA 1998) l'or addi of [he frame shall be modeled using the relevant speci
lional information regarding the behavior ol' masonry fications oí' Sectíons 6.4, 6.5, and 6.9. The model shall
infills. be capable of representing inelastic response along the
component lengths.
6.6.2.2 Stiffness Monotonic load-deformation relations shall be
according to the generalized relation shown in
6.6.2.2.1 Linear Static and Dynamic Procedures In Fig. 6-1, except different relations shaI1 be permiued
frames having intil1s in sorne bays and no infill in where verified by tests. Numerical quantities in
olher bays, the restraint 01' the infill shall be repre Fig. 6-1 shaI1 be derived from tests or by analyses pro
senled as described in Section 6.6.2.1, and the non cedures as speeified in Chapler 2, and shall take into
infilled bays shall be modeled as frames as specified accounL Lhe interactions between frame and intilI com
in appropriate portions of Sections 6.4, 6.5, and 6.9. ponents. Alternatively, the following procedure shall
• Where infills create a discontinuous wall, the effects be permiued for monolithic reinforced concrete frames:
of the discontinuity on overall building performance l. For beams and columns in non-infilled porlions of
shall be evalualed. Effective stiffnesses shall be in frames, where the generalized del'ormation is taken
accordance with Section 6.3.1.2. as rotaLion in the flexural plastic hinge zane, the
Table 6-16. Modeling Parameters and Numerical Acceptance Criteria for Nonlinear Procedures
Reinforced Concrete Intilled Frames
Total Slrain
Performance Level
Residual
Component Type
Plastic Rotatíons Strength
Angle, radíans Ratio Primary Secondary
Conditions d e e 10 LS CP LS CP
176
ASCEJSEI 41-06
plastic hinge rotation capacities shall be as defined component strength in beams, columns, or masonry
by Table 6-18; infills; and (2) column axial load corresponding to
2. For masonry infills, the generalized deformations development of the flexural capacity 01" the infilled
and control points shall be as defined in Chapter 7; frame acting as a cantilever wall.
and Design actions shall be compared with design
3. For beams and columns in infilled portions of strengths in accordance with Section 3.4.2.2.
frames, where the generalized deformation is taken Values 01" m-faclors shall be as specitied in
as elongation or compression displacement 01' the Section 7.4.2.3 for masonry infills; applicable por
beams or columns, the tension and compression tions of Sections 6.4, 6.5, and 6.9 for concrete frames;
strain capacities shall be as specified in Table 6-16. and Table 6-17 for columns modeled as lension and
compression chords. Those components that have
design actions less than design strengths shall be
6.6.2.2.3 Nonlinear Dynamic Procedure Nonlinear
assumed to satisfy the performance criteria for those
load-deformation relations for use in analysis by NDP
components.
shall modellhe complete hysteretic behavior of each
component using properties verified by tests.
6.6.2.4.2 Nonlinear Static and Dynamic Procedures In
Unloading and re10ading properties shall represent
the design model, inelastic response shall be restricted
stitl"ness and strength degradation characterislics.
to those components and actions that are permitted for
isolated frames as specified in Sections 6.4, 6.5, and
6.6.2.3 Strength 6.9, as well as for masonry infills as specitied in
Strengths of reinforced concrete componenls shalI Section 7.4.
be calculated according to the general requirements of Calculated component actions shall satisfy the
Sections 6.3.2, as moditied by other specifications of requirements of Section 3.4.3.2, and shall not exceed !he
this chapter. Strengths 01' masonry infills shall be cal numerical values listed in Table 6-16, the relevant tables
culated according to the requirements of Chapter 7. for isolated frames given in Sections 6.4, 6.5, and 6.9,
Strength calculations shall consider: and the relevant tables for masonry infills given in
l. Limitations imposed by beams, columns, and joints Chapter 7. Component actions not listed in Tables 6-7
in non-infilled portions of frames; through 6-9 shall be treated as force-controlled.
2. Tensile and compressive capacity of columns acting Alternative approaches or values shall be permitted
as boundary components of intilled frames; where justified by experimental evidence and analysis.
3. Local rorces applied from the infill to the frame;
4. Strength of the infill; and 6.6.2.5 RehabilitaRon Measures
5. Connections with adjacent components. Concrete frames with masonry infill that do not
meet the acceptance criteria for the selected
Rehabilitation Objective shall be rehabilitated.
6.6.2.4 Acceplance Criteria
Rehabilitation measures shall mect the requirements of
Section 6.3.7 and other provisions of this standard.
6.6.2.4./ Linear Static and Dynamic Procedures All
component actions shall be classitied as either
C6.6.2.5 Rehabilita/ion Measures
deformation-controlled or force-controlled, as defined
in Section 2.4.4. In primary components, deformation The rehabilitation measures described in relevant
commentary of Sections 6.4, 6.5, and 6.9 for isolated
controlled actions shall be restricted to flexure and
frames, and rehabilitation measures described in rele
axial actions in beams, slabs, and columns, and lateral
vanl commentary or Section 7.4 for masonry infills,
deformations in masonry in fin panels. In secondary
may also be eftective in rehabilitating concrete frames
components, deformation-controlled actions shall be
with masonry infills. The design professional is
restricted to those actions identified for the isolated
referred to FEMA 308 (FEMA 1998) for further infor
frame in Sections 6.4, 6.5, and 6.9, as appropriate, and
mation in this regard. In addition, !he following reha
for the masonry ¡nfill in Section 7.4.
bilitation measures may be effective in rehabilitating
Design actions shal1 be determined as prescribed
concrete frames with infills:
in Chapter 3. Where calculated DCR values exceed
unity, the following design actions shall be determined 1. Post~tensioning existing beams, columns, or
using limÍl analysis principIes as prescribed in Chap joints nsing externa) post-tensioned reinforce
ter 3: (1) moments, shears, torsions, and development mento Vertical post-tensioning may be effective in
and splice actions corresponding to development of increasing tensile capacity of columns acting as
177
SEISMIC REHABlLITATION OF EXISTING BUILDINGS
m-Factors 1
Performance Level
Component Type
Primary Secondary
Conditions 10 LS CP LS CP
2
i. Columns Modeled as Compression Chords
Columns Confined along Entire Length 3 3 4 4 5
AlI Other Cases
ii. Columns Modeled as Tension Chords2
Columns with Well-Confined Splices, 3 4 5 5 6
or No Splices
AII Other Cases 2 2 3 4
the entire story height including the joint is equal 10 three-quarters of that required by ACI 3 J 8
(ACI 2(02) for boundary components of concrete shear walls. The maxirnurn longitudinal spacing of
sets of hoops shall not exceed either h/3 or 8db •
boundary zones. Anchorages should be located The analytical model shall be established consid
away from regions where inelastic action is antici ering the relative stiffness and strength of the frame
pated, and should be designed considering possible and the intill, as well as the level of deformations and
force variations due to earthquake loading; associated damage. For low deformation levels, and
2. Modification of the element by selective material for cases where the frame is relatively t1exible, the
removal from the existing elemento Either the intilled frame shall be permitted to be modeled as a
infill should be completely removed from the shear wall, with opcnings modeled where they occur.
frame, or gaps should be provided between the In other cases, the frame-intill system shall be permit
frame and the intill. In the latter case, the gap ted to be modeled using a braced-frame analogy such
rcquirements of Chapter 7 should be satistied; as that described for concrete frames with masonry
and intills in Section 6.6.2.
3. Changing the building system to reduce the Frame components shall be evaluated for forces
demands on the existing elemento Examples imparted to them through interaction of the trame with
include the addition of supplementary lateral-force the inlill as specitied in Chapter 7. In frames with full
resisting elements such as walls, steel braces, or height intills, the evaluation shall include [he effect of
buttresses; seismic isolation; and mass reduction. strut compression torces applied to the column and
beam eccentric from the beam--column joint. In frames
6.6.3 Concrete Frames with Concrete Infills with partial-height intills, the evaluation shall inelude
the reduced effective length of the columns aboye the
6.6.3.1 General Considerations intilled portion of the bayo
The analytical model for a concrete frame with con In frames having intills in some bays and no
crete intills shall represent the strength, stiffness, and intills in other bays, the restraint of [he intill shall be
deformation capacity of beams, slabs, columns, beam represented as described in this section, and the non
column joints, concrete intills, and all connections and intilled bays shall be modeled as trames as specified
components of the elements. Potential failure in tlexure, in appropriate portions of Sections 6.4, 6.5, and 6.9.
shear, anchorage, reinforcement development, or crush Where intills create a discontinuous wall, the effects
ing at any section shall be considered. Interaction with of the discontinuity on overall building performance
nonstructural components shall be included. shall be evaluated.
178
ASCE/SE! 41-06
Table 6-18. Modeling Parameters and Numerical Acceptance Criteria for Nonlinear Procedures
Reinforced Concrete Shear Walls and Associated Components Controlled by Flexure
Performance Level
Plastic Hinge Residual
Component Type
Rotation Strength
(radians) Ratio Primary Secondary
Conditions a b e 10 LS CP LS CP
:s 0.1 :s 3 Yes 0.015 0.020 0.75 0.005 0.0\0 0.0\5 0.015 0.020
:s 0.1 2:6 Yes 0.0\0 0.015 0.40 0.004 0.008 0.0\0 0.0\0 0.015
2: 0.25 :s3 Yes 0.009 0.012 0.60 0.003 0.006 0.009 0.009 0.012
2: 0.25 2:6 Yes 0.005 0.010 0.30 0.0015 0.003 0.005 0.005 0.0\0
:s 0.1 :s3 No 0.008 0.015 0.60 0.002 0.004 0.008 0.008 0.015
:s 0.1 2:6 No 0.006 0.010 0.30 0.002 0.004 0.006 0.006 0.010
2: 0.25 :s3 No 0.003 0.005 0.25 0.001 0.002 0.003 0.003 0.00
2: 0.25 2:6 No 0.002 0.004 0.20 0.001 0.001 0.002 0.002 0.004
ii. Columns Supporting Discontinuous Shear Walls
Transverse Reinforcement4
Conforming 0.0\0 0.015 0.20 0.003 0.007 0.0\0 n.a. n.a.
Nonconforming 0.0 0.0 0.0 0.0 0.0 0.0 n.a. n.a.
iii. Shear Wall Coupling Beams5
V
Longitudinal Reinforcement
and Transwrse Reinforcement 6 tw1wvJ:
Conventional Longitudinal :s3 0.025 0.050 0.75 0.0\0 0.02 0.025 0.025 0.050
Reinforcement with Conforming 2:6 0.020 0.040 0.50 0.005 0.0\0 0.020 0.020 0.040
Transverse Reinforcement
Conventional Longitudinal :s3 0.020 0.035 0.50 0.006 0.012 0.020 0.020 0.035
Reinforcement with 2:6 0.0\0 0.025 0.25 0.005 0.008 0.010 0.010 0.025
Nonconforming Transverse
Reinforcement
Diagonal Reinforcement n.a. 0.030 0.050 0.80 0.006 0.018 0.030 0.030 0.050
IPllmary and secondary component demands shaJl be within secondary component acceptance criteria where the fuJl backbone curve is explicitly
modeled including strength degradation and residual strength in accordance with Section 3.4.3.2.
'Linear imerpolaIion belween values Iisted in lhe table shall be permitted.
JRequirements for a confined boundary are the same as those given in ACI 318 (ACI 2(02).
4Requirements for conforming transverse reinforcement in colunills are: (a) hoops over lhe entire length of the column at a spacing:s d/2, and
(b) strength of hoops V, :;=: required shear strength of column.
5For secondary coupling beams spanning < 8 ft, O in., with bottom reinforcement continuous into the supponing walls, secondary values shall be
perrnitted to be doubled.
·Conventional longitudinal reinforcement consists of top and bottom steel parallel to the longitudinal axis of the coupling beam. Conforming
transverse reinforcement consists of: (a) c10sed stirrups over lhe entire length of the coupling beam al a spacing:s dl3, and (b) strength of c10sed
stirrups V, 2: three·fourths of required shear strength of the coupling beam.
179
SEISMIC REHABlLITATION OF EXISTING BUILDlNGS
except different relalions shall be permitted where veri C6.6..1.5 Rehabilitation Measltres
fied by tests. Numerical quantities in Fig. 6-1 shall be RehabilitaLion measures described in C6.6.2.5 for
derived from tests or by analysis procedures specified in concrele n'ames with masonry infills may also be effec
Section 2.8, and shall take into account the interactions tive in rehabilitating concrete r.·ames with concrete
between frame and ínlill components. Alternatively, the infills. In addition, application of sholerete to Lhe face
procedure ol' Seetion 6.6.2.2.2 shall be permiued for the of an existing wall to increase the thíckness and shear
development 01' nonlinear modeling parameters for con slrength may be etfeclive. For this purpose, the face of
crete trames with concrete íntills. lhe existing wall should be roughened, a mat 01' rein
forcing sleel should be doweled into the existing slruc
6.6.3.2.3 Nonlinear Dynamic Procedure Nonlinear ture, and shotcrele should be applied lo lhe desircd
load-deformation relations for use in analysis by NDP thickness. The design professional is referred to FEMA
shall model lhe complete hysteretic behavior of each 308 (FEMA 1998) for further information regarding
component using properties verified by tests. rehabiJilation 01' concrete frames wilh concrete infil!.
Unloading and reloading properties shall represent
stil'fness and strength degradalion characteristics.
6.7 CONCRETE SHEAR WALLS
6.6.3..1 Strength
6.7.11Ypes of Concrete Shear Walls and Associated
Strengths of reinforced concrete components
Components
shall be calculaled according lo the general require
The provisions 01' Seclion 6.7 shalI apply to alI
ments of Seclions 6.4.2, as modi11ed by other specili
..,. cations 01' this chapter. Strength calculations shall
consider:
shear walIs in all types 01' structural syslems thal
incorporate shear walls. This inc\udes isolated shear
,d
,1
walls, shear waJls used in wall-frame systems, cou
l. Límitations imposed by beams, columns, and joints pled shear walls, and diseontinuous shear walls. Shear
in unfilled portions of frames; walls shall be permitted to be considered as solid walIs
2. Tensile and compressive capacity 01' columns acting if they have openings that do not signíticanlly intlu
as boundary components of intilled trames; ence the strenglh or inelastic behavior of the wall.
3. Local forces applied from the infiII to the frame; Perforated shear walls shall be defined as walls having
4. Strength oí' the inlill; and a regular pattern 01' openings in both horizontal and
5. Connections with adjacent componenls. vertical directíons thal crea Les a series 01' wall pier and
deep beam componenLs referred to as wall segments.
Strengths oí' existing concrete intills shall be Coupling beams and columns thal support discon
determined considering shear strength oí' the infill Linuous shear walls shall comply with provisions of
panel. For lhis calculation, procedures specitied in Section 6.7.2. These specíal frame componenls assocí
Seclion 6.7.2.3 shaJl be used for calculation of the aled with shear walls shall be cxempted from Lhe pro
shear strength of a wall segment. visions for beams and columns 01' trame components
Where the frame and concrete infill are assumed covered in SecLion 6.4.
to act as a monolithic wall, flexural strength shall be
based on continuity of vertical reinl'orcement in boLh C6.7.1 Types of Concrete Shear Walls and
( 1) lhe columns acting as boundary components, and Associated Components
(2) the intill wall, including anchorage 01' the intilI Concrete shear walls are planar vertical elements
reinforcement in the boundary frame. or combinalions of inlerconnecled planar elements that
serve as lateral-load-resisting elements in concrete
6.6..1.4 Accepttmce Criteria structures. Shear walls (or wall segmenls) shall be
The acceptance criteria for concrete trames with considered slender i1' their aspeel ralio (heighl/lenglh)
concrete intills shall comply with relevant acceptance is > 3.0, and shall be considered short or squat if their
críleria 01' Sections 6.6.2.4,6.7, and 6.8. aspect ratio is < 1.5. Slender shear walls are normally
controlJed by I1cxural behavior; short walls are nor
6.6.3.5 Rehabilitation Measllres mally controlled by shear behavior. The response 01'
Concrete trames with concrete infills that do nOI walls with intermediale aspect ratios is inlluenced by
meet the acceptance criteria for lhe selected Rehabili bOlh Ilexure and shear.
tation Objective shall be rehabilitaled. RehabiJitation IdentificaLion oí' component lypes in concrete
measures shall meet the requirements 01' Section 6.3.7 shear wall elements depends, lo some degrec, on
and other provisions of lhis standard. lhe relative strengths 01' the wall segments. Vertical
180
ASCEJSEI 41-06
segments are often (ermed wall piers, while horizontal Iban 0.0025, but with reinforcemenl spacings less than
segmenls may be calIed coupling beams or spandrels. 18 in., shaJl be permiued where the shear force
The design professional is referred lo FEMA 306 demand does not exceed lhe reduced nominal shear
(FEMA 1998) for addítional information regarding strength of the walI calculaled in accordance with
the behavior of concrete walI componenlS. Selected Section 6.7.2.3.
informatíon from FEMA 306 has been reproduced in
the commentary of Ihis standard, in Table C6-1 and C6.7.1.1 Monolithic Reinforced Concrete Shear
Fig. C6-l lo c1arify wall component identificalÍon. Walls and Wa/l Segments
The walI reinforcement is normally continuous in
6.7.1.1 Monolithic Reinforced Concrete Shear Walls both the horizontal and vertical direclions, and bars
and Wall Segments are typically lap spliced for lension continuity. The
Monolithic reinforced concrete shear walls shaIl reinforcement mesh may also contain horizontal lÍes
consist of vertical cast-in-place elements, either around vertical bars that are concentrated either near
uncoupled or coupled, in open or closed shapes. These the vertical edges of a wall with constant thickness, or
walls shall have relatively contÍnuous cross sections in boundary members formed at the wall edges. The
and reinforcement and shall pro vide both vertical and amount and spacing of Ihese lies is important for
lateral force resistance, in contrast with infilled walls determining how well the concrete at the wall edge is
detined in Section 6.6.1.3. confined, and thus for determining the lateral deforma
Shear walls or wall segments with axial loads tion capacity of the wall.
greater than 0.35Po shall not be considered effective in In general, slender reinforced concrete shear walls
resisting seismic forces. For Ibe purpose of determin will be governed by tlexure and will tend to form a
ing effectiveness of shear walls or wall segments, the plasüc tlexural hinge near the base of the wall under
use ofaxialloads based on a limit state analysis shall severe lateralloading. The ductilily of the wall will be
be permitted. The maximum spacing of horizontal and a function oí' the percentage of longitudinal reinforce
vertical reinforcement shall not exceed 18 in. Walls ment concentrated near the boundaries of the wall, the
with horizontal and vertical reinforcement ratios les s level ofaxial load, (he amount ol' lateral shear required
Component Type
per FEMA 306 Description ASCE 41 Designation
RCl Isolated Wall or Stronger than beam or spandrel components that may Monolíthíc reínforced concrete
Stronger Wall Píer frame into it so that nonlinear behavior (and damage) wall or vertical wall segment
is generally concentrated at the base, with a tlexural
plastic hinge, shear failure, etc. lncludes isolated
(cantilever) walls.lf the component has a major set
back or cutoff of reinforcement above the base, this
section should be also checked for nonlinear behavior.
RC2 Weaker Wall Pier Weaker than the spandrels to which it connects; char
acterized by flexural hinging top and bottom, or shear
failure, etc.
RC3 Weaker Spandrel or Weaker than the wall píers to which it connects; char Horizontal wall segment or
Coupling Seam acterízed by hinging at each end, shear faHurc, sliding coupling beam
shear failure, etc.
RC4 Stronger Spandrel Should no! suffer damage because it is stronger than
attached wall piers. If this component is damaged, it
should probably be reclassitied as RC3.
RC5 Píer-Spandrel Panel Typically not a critical area in RC walls. Wall segment
Zone
'Source: FEMA. (1998). "Evaluatioll of eaI1hquake-damaged concrete and masonry wall buildings-Basic procedures manuaJ." FEMA 306, pre
pared by lhe Applied Technology Council (ATC-43 Project), for ¡he Federal Emergency Management Agency, Washington, D.e.
181
SEISMIC REHABILITATION OF EXISTING BUILDING S
\
components
to cause nexural yielding, and lhe thickness and rein designed either as displacernent-controlled compo
forcement used in lhe web portion of the shear wall. In nents with Jow ductiJity capacities 01' as force
general, higher axial load stresses and higher shear controlled components.
stresses will reduce lhe flexural ductility and energy
absorbing capabilily ol' Ihe shear wall. Short or squat 6.7.1.2 Reinforced Concrete Columm SlIpportillg
shear walls will norrnally be governed by shear. Discontimwus Shear Walls
These walls will normally have a limited ability to Reinforced concrete columns supporling discon
deform beyond the elastic range and continue lO tinuous shear walls shall be evaluated and rehabilitated
carry lateralloads. Thus, these walls are typically to comply with lhe rcquiremcnts of Section 6.7.2.
182
ASCE/SEI 41-06
C6.7.1.2 Reinforced Concrete Columns Supporting the shear wall shall be considered. Interaction with
Disconlinuous Shear Walls other structural and nonstructural components shall
In shear wall buildings it is nol uncommon lO find be included.
that sorne walls are terminated either to crea te commer Slender shear waIls and waIl segments shaIl be
cíal space in the first slory or to create parking spaces permiued to be modeled as equivalent beam-column
in the basemenl. In such cases, the waJls are commonly elements that indude both flexural and shear deforma
supported by columns. Such designs are not recom tions. The flexural strength of beam-column elements
mended in seismic zones because very large demands shall include the interaction ofaxialload and bending.
may be placed on these columns during earthquake The rigíd-connection zone at beam connections to this
loading. In older buildings such columns will often equivalent beam-column element shall represent the
have "standard" longitudinal and transverse reinforce distance from the wall centroid to the edge or the wall.
ment; lhe behavior of such columns during pasl earth Unsymmetrical wall sectÍons shall model the different
quakes indicates that tightly spaced closed ties with bending capacities ror the two loading directions.
well-anchored 135-degree hooks will be required for A beam element that incorporales bOlh bending
Ihe building to survive severe earthquake loading. and shear deformations shall be used 10 model cou
pling beams. The element inelastic response shall
6.7.1.3 Reinforced Concrete Coupling Beams account ror the loss of shear strength and stiffness dur
Reinforced concrete coupling beams used to ing reversed cyclic loading to large deformations. For
link two shear walls together shall be evaluated and coupling beams that have diagonal reinrorcement sat
rehabilitated to comply with the requirements of isfying ACI 318 (ACI 2(02), a beam element repre
Section 6.7.2. senting t1exure only shall be permitted.
For columns supporting discontinuous shear
C6.7.1.3 Reinforced Concrete Coupling Beams walls, the model shall account for axial compression,
The coupled walls are generally much stiffer and axial tension, flexure, and shear response, including
stronger than they would be if they acted indepen rapid loss 01' resistance where this behavior is likely
dently. Coupling beams typically have a small span-to under design loadings. The diaphragm action of con
depth ratio, and their inelastic behavior is normally crete slabs that interconnect shear walls and frame
affected by the high shear forces acting in these com columns shall be represented in the model.
ponenls. Coupling beams in mosl older reinforced
concrete buildings will commonly have "conventional" C6.7.2.1 General Considerations
reinforcement that consists of longitudinal flexural For rectangular shear walls and wall segments
steel and transverse steel for shear. In sorne, more with h/l", ::s; 2.5, and flanged wall sections with
modern buildings, or in buildings where coupled shear h/t", ::s; 3.5, either a moditied beam-wlumn analogy
walls are used fm seismic rehabilitation, the coupling or a multiple-node, multiple-spring approach should
beams may use diagonal reinforcement as the primary be used. Because shear walls usually respond in single
reinforcement for both flexure and shear. The inelastic curvature over a story height, the use 01' one muItiple
behavior of coupling beams lhat use diagonal rein spring element per story should be permitted ror mod
forcement has been shown experimentally to be much eling shear walls. Wall segments should be mode1ed
better with respect 10 relention of strength, stiffness, with either the beam-<:olumn element or with a
and energy dissipalion capacily than the observed multiple-spring model with two elements over the
behavior of coupling beams with conventional length 01' the wall segment.
reinforcement. Coupling beams that have diagonal reinforcement
satisfying FEMA 450 (FEMA 2004) will commonly
6.7.2 Reinforced Concrete Shear Walls, Wall have a stable hysteretic response under large load
Segments, Coupling Beams, and Reinforced reversals. Therefore, these members could adequately
Concrete Columns Supporting Discontinuous be modeled with beam elements used for typical 1'rame
ShearWalls analyses.
183
SEISMIC REHABILlTATION OF EXISTING BUILDINGS
J
flexure, as well as columns supporting discontinuous
shear walls, the following approach shall be permitted.
The load-deformation relationship in Fig. 6-1 shalI be
used with the x-axis of Hg. 6-1 taken as the rotation 8 ~._--- =iF====---==1I:::
over the pIastic hinging region al the end of the mem
ber shown in Fig. 6-2. The hinge rotation at point B in
Fig. 6-1 corresponds to the yield point, O" and shall be
calculated in accordance with Eq. 6-6:
~
184
ASCE/SEI 41-06
Choro Rolation:
0= A
L
'~"'.
L
..1
FIGURE 6-3. Story Drift in Shear Wall where FIGURE 6-4. Chord Rotation for Shear Wall
Shear Dominates Inelastic Response. COllpling Beams.
Table 6-19. Modeling Parameters and Nllmerical Acceptance Criteria for Nonlinear Procedllres
Reinforced Concrete Shear Walls and Associated Components Controlled by Shear
Conditions el e e 10 LS CP LS CP
L Shear Walls and Wall Segments
AH Shear Walls and Wall Segments J 0.75 2.0 0.40 0.40 0.60 0,75 0.75 1.5
iL Shear wall coupling beams4
Longitudinal Reinforcement
v
and Transverse
Reinforcement5
Conventional Longitudinal s; 3 0.02 0.030 0.60 OJlO6 0.015 0.020 0,020 0.D30
Reinforcement with Conformíng 6 0.016 0.024 0.30 0.005 0.012 0.016 0.016 0.024
Transverse Reinforcement
Conventional Longitudinal s; 3 0.012 0.025 0.40 0.006 0.008 0.010 omo 0.020
Reinforcement wíth 2:! 6 0.008 0.014 0.20 0.004 0.006 0.007 0.007 0.012
Nonconforming Transverse
Reínforcement
lPrimary and secondary component demands shall be within secondary component acceptance crítería where the full backbone curve is explícitly
modeled including strength degradation and residum strength in accordance wilh Section 3.4.3.2.
2pOl' shear walls and wall segmenls, use drift; for coupling beams, use chord rotalion; refer 10 Figures 6-3 and 6-4.
'Por shear walls and wall segrnenls where inelaslic behavior i8 governedby shear, tbe axial load on the member musl be '" O. [5 A.f:; otherwise,
the member musl be treated as a force-controlled component.
4Por secondary coupling beams spanning <8 ft, O in" with bottom reinforcement continuous into Ihe supporting wmls. secondary values shall be
perrnitted 10 be doubled.
5ConvenlÍonal longitudinal reinforcement consisls of top and bottorn sleel para/le! 10 [he longitudinal axis of the couplíng heam. Conforming
Iransverse reinforcemenl consiSls of: (1) cJosed stirrups over the entire Jength of Ihe coupling beam al a spacing d13, and (2) slrength of closed
stirrups V, ;;, three-fouflhs of required shear strenglh of the coupling beam,
185
SElSMIC REHABILlTATION OF EXlSTING BUILDING S
6.7.2.2.3 Nonlinear Dynamic Procedure For Ihe NDP, Where a shear wall or wall segment has a Irans
lhe complete hysteretic behavior of each componenl verse reinfórcemenl percentage, Pn' les s than the
shall be modeled using properties veritied by experi minimum value of 0.0025 but greater than 0.0015 and
mental evidence. Use of the generalized load reinforcement is spaced no greater than 18 in., the
deformation relalion shown in Fig. 6-1 to represenl shear strength 01' the wall shall be analyzed using the
the envelope relalion for lhe analysis shall be permiL ACI 318 equations noted aboye. For transverse rein
ledo The unloading and reloading sliffnesses and forcement percentages less than 0.00 15, the contri bu
strengths, and any pinching of the load-versus-rotation tion from the wall reinforcemem lo lhe shear slrengfh
hysteresis loops, shall retlecl lhe behavior experimen oí' the wall shall be held constant at the value obtained
tally observed for wall elemenls similar to the one using Pn = 0.0015.
under invesligalion. Splice lengths ror primary longitudinal reinforce
ment shall be evaluated using the procedures given in
Section 6.3.5. Reduced flexural strengths shaIl be eval
6.7.2.3 Slrenglh
uated at locations where splices govern the usable
Component strenglhs shall be compuled according
stress in lhe reinforccment. The need for conlinement
lo the general requirements of Seclions 6.3.2, wilh Ihe
reinforcement in shear wall boundary members shall
addilional requirements of this section. Strenglh shall
be evaluated by the procedure in ACI 318 or other
be delermined considering lhe potential for failure in
tlexure, shear, or developmenl under combined gravity approved procedure.
1; Thc nominal tlexural and shear strcnglhs 01' cou
ami lateral load.
, pling beams shalI be evaluated using the principIes and
...
..r.
II
r!
~
Nominal tlexural slrenglh of shear walls or wall
segmenls, M n , shall be determined using Ihe funda
menlal principIes given in Chapter 10 of ACI 318
equations contained in Chapler 21 01' ACI 318. The
expected strength of longitudinal or diagonal rein
forcement shall be used.
(ACI 2002). For calculalion of nominal tlexural
The nominal shear and llexural strenglhs of
strength, the effective compression and tension tlange
columns supporting discontinuous shear walls shall be
widths detined in Seclion 6.7.2.2 shall be used, except
lhal lhe tirsl limil shall be changed lo one-Ienth of Ihe evaluated as delined in Section 6.4.2.3.
wall height. Where determining Ihe flexural yield
slrenglh of a shear wall, as represenled by poinl B in C6.7.2.3 Strenglh
Fig. 6- J (a), only Ihe longitudinal steel in lhe boundary Data presented by Wood (1990) indicatc thal wall
of Ihe wall shall be inc\uded. Ir Lhe wall does not have strength is insensitive lo lhe quantity of transverse
a boundary member, then only Ihe longitudinal sleel in reinforcement whcre it drops below a steel ralio of
Ihe ouler 25% of the wall seclion shall be included in 0.0015.
lhe calculalion oí' the yield strength. Where calculaling The nced for continement reinforcement in shear
Ihe nominal flexural slrength of the waIl, as repre wall boundary mcmbers may be evalualed by the
senled by point C in Fig. 6-1 (a), alllongitudinal sleel method recommended by Wallace and Thomsen
(including web reinforcement) shall be included in lhe (1995) for determining maximum laleral deformations
calculation. For all moment strength calculations, the in the wall and the resulting maximum compression
strength of the longitudinal reinforcemem shall be strains in the walI boundary.
taken as the expected yield slrength lo accounl for Strength calculations based on ACI 318 (ACI
malerial overstrength and strain-hardening, and the 2002), excluding Chapter 22, assume a maximum
axial load acting on lhe wall shaIl inelude gravily spacing of wall reinforcemcnt. No dala are available lo
loads as defined in Chapler 3. justify performance for walIs that do not meet Ihe
The nominal shear slrength of a shear wall or wall maximum spacing requirements. If plaín concrete is
segment, V"' shall be determined based on the princi encountered in an existing building, Chapter 22 of ACI
pIes and equalions given in Chapter 21 01' ACI 318. 318 can be used to derive capacities, while Section 2.8
The nominal shear strength of columns supporting dis of this standard can be used lo develop acceptance
continuous shear walls shall be determined based on criteria.
the principIes and equations given in Chapler 21 of
ACI 318. For aIl shear strength calculations, 1.0 times 6.7.2.4 Acceplauce Crileria
the specitied reinforcement yield strength shall be
used. There shaIl be no dií'ference between lhe yield 6.7.2.4. J Linear Static and Dynamic Procedures Shear
and nominal shear strengths, as represented by points walls, walI segments, coupling beams, and columns
B and C in Fig. 6-1. supporting disconlinuous shear walls shall be cIassi
186
ASeE/SE) 41-06
187
SEISMIC REHABILlTATION Of EXISTING BUlLDINGS
web may be an etfective rehabilitalion measure. to the exísting web of the shear wall. The .use of
The new concrete should be at least 4 in. thick and carbon fiber sheets, epoxied to the concrete surface,
should contain horizontal and vertical reinforce should also be permitted to increase the shear
mem. The new concrete should be properly bonded capacity of a shear wall;
m-factors J
Performance Level
Component Type
Primary Secondary
Conditions 10 LS CP LS CP
i. Shear Walls and Wall Segments
(A, - A's)/,. + P 2 V Contlned
,,:~~
t,l•./; v7:.
t.l w Boundary4
~~i¡ $ 0.1 $3 Yes 2 4 6 6 8
a" $ 0.1 2!6 Yes 2 3 4 4 6
2! 0.25 $3 Yes 1.5 3 4 4 6
J" 2!6
'11 2! 0.25 Yes 1.25 2 2.5 2.5 4
$ 0.1 3 No 2 2.5 4 4 6
$ 0.1 6 No 1.5 2 2.5 2.5 4
2! 0.25 $3 No 1.25 1.5 2 2 3
0.25 2!6 No 1.25 1.5 1.75 1.75 2
ii. Columns supporting Discontinuous Shear Walls
Transverse Reinforcement 5
Conforming 1.5 2 n.a. n.a.
Nonconforming 1 n.a. n.a.
Hí. Shear Wall Couplíng Beams6
V
Longitudinal Reinforcement and
Transverse Reinforcement7 t).vJ'f
Conventíonal Longitudinal $3 2 4 6 6 9
Reinforcement with Conforming 2!6 1.5 3 4 4 7
Transverse Reinforcement
Conventional Longitudinal $3 1.5 3.5 5 5 8
Reinforcement with Nonconform 2!6 1.2 1.8 2.5 2.5 4
ing Transverse Reinforcement
Diagonal Reinforcement n.a. 2 5 7 7 10
188
ASCE/SEI 41-06
5. Continement jackets to improve delormation increased confinement. The opening below a dis
capacity 01 coupling beams and columns sup continuous shear wall should also be permitted to be
porting discontinuous shear walls. The use of "infilled" with steeJ bracing. The bracing members
confinement jackets specified earlier as a reha should be sized to salisfy all design requirements
bilitatíon measure for wall boundaríes, and in and the coJumns should be strengthened with a steel
Section 6.4 for frame elements, may also be effec or a reinforced concrete jacket.
tive in increasing both the shear capacity and the
deformation capacity of coupling beams and AIl of the aboye rehabilitation measures require
columns supporting discontinuous shear walls; and an evaluation of the wall foundation, diaphragms, and
6. Inrdling between columns supporting discontinu connections between existing structuraJ elements and
ous shear waUs. Where a discontinuous shear walJ any eJements added for rehabilitation purposes.
is supported on columns that lack eilher sufticienl
strenglh or deformatíon capacity to satisfy design
críteria, making the wall continuous by infilling the 6.8 PRECAST CONCRETE SHEAR WALLS
opening between these columns may be an effective
rehabilitation measure. The infill and existing 6.8.1 Types 01 Precast Shear Walls
coJumns should be designed to satisfy all the Precast concrete shear walls shall consist of story
requirements for new wall construction, including high or half-story-high precast wall segments !ha! are
any strengthening ol' the existing columns required made contínuous through the use 01' either mechanicaJ
by adding a concrete or steeJ jacket for strength and connectors or reinforcement splicing techniques with
m-Factors
Performance Level
Component Type
Primary Secondary
Conditions ro LS CP LS CP
i. Shear Walls and Wall Segments
Al! Shear Walls and WaLl Segments 1 2 2 3 2 3
íi. Shear Wall Coupling Beams 2
V
Longitudinal Reinforcement
and Transverse Reinforcement 3
Conventional Longitudinal ,,;3 1.5 3 4 4 6
Reinforcement with Conforming 2:6 1.2 2 2.5 2.5 3.5
Transverse Reinforcernent
Conventional Longitudinal ,,;3 l.5 2.5 3 3 4
Reinforcement with Nonconform 2:6 1.2 1.2 1.5 1.5 2.5
ing Transverse Reinforcement
IThe shear shall be considered lO be a force-conlrolled action for shear walls and wall segments where
inelastic behavior is govemed by sbear and tbe design axial load is grcaler Ihan 0.15 A8f~. It shall be
permilled to calculate tbe axial load based on a Iimit-state analysis,
2For secondary coupling beams spanning <8 ft, O in., with bottom reinforcement continuous into lbe
supporting walls, secondary values shall be permitted to be doubled,
3Conventional longitudinal reinforcement consists of top and bottom steel parallel to tbe longitudinal
axis of lhe coupling beam. Conforming transverse reinforccment consists of: (1) c10sed stirtups over (he
enlire length of the coupling beam at a spacing:S dj3, and (2) slrength of c10sed Slirmps V, 2! Ihree
fourths of required sbear strength of the coupling beam,
• For the purpose of determíning m, Vis lbe coupling beam expccted shear sttength.
189
SEISMIC REHABILlTATlON OF EXISTING BUILDINGS
01'wilhout a cast-ín-place connectíon strip. Connec buildings have often exhibited brittle behavior during
tions between precast segments shall be permitted inelastic load reversals, jointed construction had not
along both the horizomal and vertical edges of a wall been permitted in high-seismic zones. Therefore.
segment. where evaluating older buildings that contain precast
The design of the following types of precast shear shear walIs that are likely to respond as jointed con
walls shall meet the requirements of Section 6.8: struction, the permissible ductilities and rotation
capacities given in Secrion 6.7 should be reduced.
l. Efl'ectiveIy monolithic construction, defined as that
For sorne modern struclures, precast shear walls
construction in which lhe reinforcemenl connec
have been constructed with special conneclors that are
tions are made to be slronger lhan lhe adjacem pre
detailed lo exhibir duclíle response and energy absorp
casI panel s so that the laleral load response of the
lion characlerislics. Many 01' these conneetors are pro
precast wall system will be comparable lO lhat 1'or
prietary and onIy Iimited experimental evidence con
monolithic shear walls;
cerning their inelastic behavior is available. Although
2. Joimed construction, defined as construction in
lhis lype of construclion is clearly safer than jointed
whích inelastic action is permitted to occur al the
construclion in older buíldings, the experimental evi
connections between precast paneIs; and
dence is not sufticient lo permíl the use of the same
3. Tílt-up construction, defined as a special lechnique
ductility and rotarion capacities given ror casl-in-place
for precast wall construclion where there are verti
construction. Thus, the permissible values given in
cal joints between adjacent panel s and horizontal
Section 6.7 should be redueed.
joinls at the foundation level, and where rhe rool' or
Section 9.6 of FEMA 450 (FEMA 2004) provides
l100r diaphragm connects with lhe tih-up panel.
testing criteria that may be used to validale design val
ues consistent with Lhe highest performance of mono
6.8.1.1 Effectively Monolithic Constrllction
For this type oí' precast wall, the connections lithic shear wall construction.
between precast wall elemenlS shall be designed and
detailed to be slronger than the panels they connecr. 6.8.1.3 Tilt-Up Construction
Precasl shear walls and wall segmenls ol' effeclively Shear waIls and walI segments of lilt-up type 01'
monolilhic construction shall be evaluated by the crile precast walls shall be evaluated by the crÍleria detined
ria detined in Section 6.7. in Section 6.8.2.
190
ASeE/SEI 41-06
struclural and nonstructural components shall be For precast shear walls and wall segments whose
ineluded. inelastic behavior under lateral loading is governed by
Modeling of precast concrete shear walls and wall flexure, the general load-deformation relationship
segments within the precast panels as equivalent shall be detined as in Fig. 6-1 (a). For these members,
beam-columns that ¡nelude both flexural and shear the x-axis of Fig. 6-1 (a) shall be taken as the rotation
deformations shalJ be permitted. The rigid-connection over the plaslic hinging region al the end 01' the mem
zone at beam connections to these equivalent beam ber as shown in Fig. 6-2. If the requirements 1'or effec
columns shall represent the distance ti'om the wall tively monolithic conslruction are salisíied, Ihe value
centroid lo lhe edge of lhe wall or wall segment. The of the hinge rolalion al point B shall correspond lo the
different bending capacities for the lwo loading direc yieId rotal ion, 0y' and shall be calculaled by 6-6.
tions of unsymmetrical precast wall sections shall be The same expression shall also be used for wall seg
modeled. ments wilhin a prccast panel if tlexure conlrols the
For precast shear walls and wall segments where inelastic response of Ihe segment. If Ihe precasl
shear deformations have a more significan! elJect on walJ is of jointed construcLÍon and tlexure governs
behavior Ihan tlextural deformarion, a multiple spring Ihe inelastic response 01' the member, then lhe value
model shall be used. of Oy shall be increased to accounl ror rolation in
The diaphragm action of concrete slabs inlercon the joints between panels or between lhe panel and lhe
nccting precast shear walls and frame columns shall be foundation.
represenled in the model. For precast shear walIs and wall segments whose
inelastic behavior under lateralloading is governed by
6.8.2.2 Stiffiaess shear, lhe general load-deformalion relalionship shall
The modeling assumptions detined in Section be defined as in Fig. 6-] (b). For these members, the
6.7.2.2 for monolithic concrete shear walls and wall x-axis of Fig. 6-1 (b) shall be laken as the story drift
segments shall also be used for precast concrele walls. for shear walls, and as lhe eIement drifl for wall seg
In addition, the analytical model shall model the axial, menls as shown in Fig. 6-3.
shear, and rotational deformations of the connecLÍons For etl'eclively monolíthic conslruction. the values
between lhe precast components Ihat comprise Ihe for lhe variables a, b, and e required 10 define the loca
wall by either soflening the model used lo represent tion 01' points e, D, and E in Fig. 6-1 (a), shall be as
the precasl panels or by adding spring elements specilied in Table 6-18. For construc¡ion c1assiíied as
between panels. joinled construction, the values oí' a, b, and e specified
in Table 6-18 shall be reduced to 50% of ¡he given val
6.8.2.2.1 Linear Static and Dynamic Procedures The ues, unless experimental evidence available lO justify
modeling procedures given in Seclion 6.7.2.2.1, com higher values is approved by the authority having
bined with a procedure for including conneclÍon defor jurisdiction. In no case, however, shall values larger
malions as noled aboye, shall be used. than Ihose specitied in Table 6-18 be used.
For effectively monolilhic conslruclion, values for
6.8.2.2.2 Nonlinear Static Procedure Nonlinear ¡he variables d, e, and e required lo tilld ¡he poinls e,
load-deformation relations shall comply with lhe D, and E in Fig. 6-1 (b), shall be as spccified in
requiremenls of Section 6.3.1.2. The monotonic Table 6-19 for the appropriale member conditions. For
load-deformation relalionships for analylicaI mooels conslruclion c\assified as jointed conslruclion, the val
that represent precast shear walls and wal1 elements ues 01' d, e, and e specified in Table 6-19 shall be
within precast panels shall be in accordance with the reduced to 50% 01' the specified values unless experi
generalized relalion shown in Fig. 6-1, except that mental evidence available lo justify higher values is
alterna!ive approaches shall be permitted where veri approved by the authority having jurisdiction. In no
fied by experiments. Where the relations are according case, however, shall values larger than those specified
lo Fig. 6-1, the following approach shall be permitted. in TabIe 6- 19 be used.
Values 1'or pIastic hinge rotalions or drifts al For Tables 6-18 and 6-19, linear interpoIation
points B, e, and E for Ihe Iwo general shapes shall be between tabulated values shall be permitted if the
as defíned below. The slrength levels al poims B and e member under analysis has conditions that are
shall correspond lo the yield strenglh and nominal between the limils given in the tables.
strength, as detined in Section 6.7.2.3. The residual
strength 1'or ¡he line segment D-E shall be as defined 6.8.2.2.3 Nonlinear Dynamic Procedure Nonlinear
below. load-deformation relations for use in analysis by NDP
191
SEISMIC REHABlLITATlON OF EXISTING BUILDlNGS
shall modcl the complete hysteretic behavior of each and in no case shall be taken larger than the values
component using propcrties verified by experimental specified in these tables.
evidence. The generalized relation shown in Fig. 6-1
shall be taken 10 represent the envelope for the anal y 6.8.2.4.2 Nonlinear Static and Dynamic Procedures
siso The unloading and reloading stiffnesses and Inelastic response shall be restricted to those shear
strengths, and any pinching of the load versus rotation walls (and wall segments) and actions listed in
hystercsis loops, shall retlect the behavior experimen Tables 6-18 and 6-19, except where it is demonstrated
lally observcd for wall clements similar lo thc onc by experimental evidence and analysis that other
under investigation. ine1astic action is acceptable for the selccted perform
ánce levels. For components experiencing inelaslic
6.8.2.3 Strength behavior, the magnitude oi' [he other aetions (rorces,
The strength of precast concretc shear walls and moments, or torques) in the component shall corre
wall segments within the panel s shall be computed spond to the magnitude 01' the action causing the
according to the general requirement 01' Section 6.3.2, inelastic behavior. The magnitude of these other
except as moditicd here. For effectively monolithic actions shall be shown lo be below their nominal
construction, the strength calculation procedures given capaeities.
in Section 6.7.2.3 shall be followed. For precast shear walls that are effeetively mono
For jointed conslruction, calculations ofaxial, lithic and wall segments within a precast panel, the
shear, and l1exural slrength 01' the connections between maximum plastic hinge rotation angles or drifls during
panels shall be bascd on fundamental principies of inelastic response shall not exceed the values speeified
structural mechanics. Expected yield strength for steel in Tables 6-18 and 6-19. For prceast shear walls of
rcÍnforcement 01' connection hardwarc used in the con jointed construclion, the maximum plastic hinge rota
nections shall be used where calculating the axial and lion angles or drifts during inelastic response shall not
f1exural strength of the conneclion region. The unmod exceed one-halr of the values specified in Tables 6-18
itíed speciticd yield strength of the reinforcement and and 6-19 unless experimental evidence justifies a
connection hardware shall be used where calculating higher value. However, in no case shall deformation
the shear strength of the conneclÍon region. values larger than those specified in these tables be
For all precast concrete shear walls 01' jointed con used for jointed type construction.
struction, no difference shall be taken between the 11' the maximum deformation value exceeds the
computed yield and nominal strenglhs in flexure and corresponding tabular value, the clement shall be con
shcar. The values for slrength represented by the sidered to be deíicient, and either the element or struc
points B and C in Fig. 6-1 shall be computed follow ture shall be rehabilitated.
ing the procedurcs given in Section 6.7.2.3. Alternative approaches or values shall be pennit
ted where justified by experimental evidence and
C6.8.2.3 Strength analysis.
In older conslruction, particular atlention must be
given lO the technique used for splicing reinrorcement C6.8.2,4 Acceptance CriterÚl
extending from adjacent panels into lhe connection. The procedures outlined in Section 9.6 of FEMA
These connections may be insuffícient and often can 450 (FEMA 2004) may be used 10 establish accept
govern the strength of the preeast shear wall system. ance criteria for preeast shear walls.
192
ASCFlSEI 41-06
capacity, lack 01' continement at wall boundaries, and diagonal braces that are coincident at beam-column
inadequate splice lengths 1'or longitudinal rein1'orce joints and that resist lateralloads primarily through
ment in wall boundaries. A 1'ew deficiencies unique to truss action.
precast wall construction are inadequate connections Where masonry infills are present in concrete
between panels, to the 1'oundation, and to tloor or roo1' braced 1'rames, requirements 1'or masonry intilled
diaphragms. 1'rames as specitied in Section 6.6 shall also apply.
The rehabilitation measures described in Sec The provisions 01' Section 6.9 shall apply to exist
tion 6.7.2.5 may be effective in rehabilitating precast ing rein1'orced concrete-braced 1'rames and existing
concrete shear walls. In addition, the 1'ollowing reha rein1'orced concrete-braced 1'rames rehabilitated by
bilitation measures may be effective: addition or removal 01' material.
1. Enhancement oC connections between adjacent
6.9.2 General Considerations
or intersecting precast wall panels. Mechanical
The analytical model 1'or a rein1'orced concrete
connectors such as steel shapes and various types
braced 1'rame shall represent the strength, sti1'1'ness, and
01' drilled-in anchors, or cast-in-place strengthening
de1'ormation capacity 01' beams, columns, braces,
methods, or a combination 01' the two, may be
and al! connections and components 01' the element.
effective in strengthening connections between
Potential 1'ailure in tension, compression (inc1uding
precast panels. Cast-in-place strengthening methods
instability), tlexure, shear, anchorage, and rein1'orce
may inc1ude exposing the reinforcing steel at
ment development at any section along the component
the edges of adjacent panels, adding vertical and
length shall be considered. Interaction with other
transverse (tie) rein1'orcement, and placing new
structural and nonstructural components shall be
concrete;
included.
2. Enhancement oC connections between precast
The analytical model that represents the 1'raming,
wall panels and Coundations. Increasing the shear
using line elements with properties concentrated at
capacity 01' the wall panel-to-1'oundation connection
component centerlines, shall be permitted. The analyti
by using supplemental mechanical connectors or by
cal model also shall comply with the requirements
using a cast-in-place overlay with new dowels into
specified in Section 6.4.2.1.
the 1'oundation may be an effective rehabilitation
In 1'rames having braces in sorne bays and no
measure. Increasing the overturning moment capac
braces in other bays, the restraint 01' the brace shall
ity 01' the panel-to-1'oundation connection by using
be represented in the analytical model as specitied
drilled-in dowels within a new cast-in-place con
aboye, and the nonbraced bays shall be modeled as
nection at the edges 01' the panel may al so be an
1'rames in compliance with the applicable provisions
effective rehabilitation measure. Adding connec
in other sections of this chapter. Where braces create
tions to adjacent panels may al so be an effective
a vertically discontinuous ti'ame, the effects 01' the
rehabilitation measure in eliminating sorne 01' the
discontinuity on overall building performance shall
1'orces transmitted through the panel-to-1'oundation
be considered.
connection; and
Inelastic de1'ormations in primary components
3. Enhancement oC connections between precast
shall be restricted to tlexure and axial load in beams,
wall panels and noor or rooC diaphragms.
columns, and braces. Other inelastic de1'ormations
Strengthening these connections by using either
shall be permitted in secondary components. Accep
supplemental mechanical devices or cast-in-place
tance criteria 1'or design actions shall be as specitied
connectors may be an e1'1'ective rehabilitation meas
in Section 6.9.5.
ure. Both in-plane shear and out-01'-plane 1'orces
should be considered where strengthening these
6.9.3 StitTness
connections.
6.9.3.1 Linear Static and Dynamic Procedures
Modeling 01' beams, columns, and braces in
6.9 CONCRETE-BRACED FRAMES braced portions of the frame considering only axial
tension and compression tlexibilities shall be permit
6.9.1 Types oC Concrete-Braced Frames ted. Nonbraced portions of frames shall be modeled
Reinforced concrete-braced trames shall be according to procedures described elsewhere for
detined as those 1'rames with monolithic, non frames. Effective stiffnesses shall be according to
prestressed, rein1'orced concrete beams, columns, and Section 6.3.1.2.
193
SEISMIC REHABILITATION OF EXISTING BUILDINGS
6.9.3.2 Nonlillear Static Procedure concrete frames shall be as specitied in other applica
Nonlinear load-deformation relations shall com ble sections of this chapter, and m-factors for beams,
ply with the requirements of Section 6.3.1.2. columns, and braces modeled as tension and compres
Beams, columns, and braces in braced portions sion components shall be as specitied for columns in
shall be modeled using nonlinear truss components or Table 6-17. The m-factors shall be reduced to one-half
other models whose behavior has been demonstrated the values in that lable, but need not be les s than 1.0,
to adequately represent behavior of concrete compo where component buckling is a consideralion.
nents dominated by axial tension and compression Alternate approaches or values shall be permitted
loading. Models for beams and columns in nonbraced where justitied by experimenlal evidence and analysis.
portions shall comply with requirements for trames
specified in Section 6.4.2.2.2. The model shall be 6.9.5.2 NOlllinear Static and Dynamic Procedures
capable of representing inelaslic response along the Calculated component actions shall satisfy the
component lengths, as well as within connections. requirements of Section 3.4.2.2 and shall not excecd
Monotonic load-deformation relations shall be the numerical values listed in Table 6-16 or the rele
according to lhe generalized load-deformation relation vant tables for isolated frames specitied in other sec
shown in Fig. 6-1, except that different relations are tions of this chapter. Where inelastic action is indi
permitted where veritied by experiments. The overall cated for a component or action not listed in these
load-deformation relation shall be established so that tables, the performance shall be deemed unacceptable.
the maximum resistance is consistent with the design Alternate approaches or values shall be permitted
strength specitications of Sections 6.3.2 and 6.4.2.3. where justitied by experimental evidence and analysis.
Numerical quantities in Fig. 6-1 shall be derived from
tests, rational analyses, or criteria of Section 6.6.2.2.2, 6.9.6 Rehabilitation Measures
with braces modeled as columns in accordance with Concrete-braced frame components that do not
Table 6-16. meet the acceptance criteria for the selected
Rehabilitation Objective shall be rehabililaled.
6.9.3.3 Nonlinear Dynamic Procedure Rehabilitation measures shall meet the requirements of
Nonlinear load-deformation relations for use in Section 6.3.7 and other provisions of this standard.
analysis by NDP shall model the complete hysteretic
behavior of each component using properties veritied C6.9.6 Rehabilitation Measures
by experimental evidence. Unloading and reloading Rehabilitation measures that may be etl'ective in
properties shall represent stiffness and strength degra rehabilitating concrele-braced frames include the gen
dation characteristics. eral approaches listed for other concrete elements in
this chapter, plus other approaches based on rational
6.9.4 Strength principIes.
Component strengths shall be computed according
to the general requirements of Sections 6.3.2 and the
addilional requirements of Section 6.4.2.3. The possi 6.10 CAST-IN-PLACE CONCRETE
bility of instability of braces in compression shall be DIAPHRAGMS
considered.
6.10.1 Components oC Concrete Diaphragms
6.9.5 Acceptance Criteria Cast-in-place concrete diaphragms transmit iner
tial forces within a structure to vertical lateral-force
6.9.5.1 Linear Static and Dynamic Procedure resisting elements.
AlI actions shall be classitied as being either Concrete diaphragms shall be made up of slabs,
deformation-controlled or force-controlled, as detined struts, collectors, and chords. Alternatively, diaphragm
in Section 2.4.4. In primary components, deformation action may be provided by a structural lruss in the
controlled actions shall be restricted to t1exure and horizontal plane. Diaphragms consisting of slructural
axial actions in beams and columns, and axial actions concrete topping on metal deck shall comply with the
in braces. In secondary components, deformation requirements of Section 5.9.2.
controlled actions shall be restricted to those actions
idenLilied for the braced or isolated Irame in tbis chapter. 6.10.1.1 Slabs
Calculated component actions shall satisfy lhe Slabs shall consist of cast-in-place concrete sys
requirements of Section 3.4.2.2. The m-factors for lems that, in addition to supporling gravity loads,
194
ASeE/SEl 41-06
195
SElSMIC REHABILlTATION OF EXISTING BUILDING S
Two general alternatives may be effective in cor Sorne precasl roof systems are constructed as
recting deficiencies: either improve the strength and untopped syslems. Unlopped precasl concrele
ductility, or reduce lhe demand in accordance with diaphragms have been limited to lower seismic zones
FEMA 172 (FEMA 1992). Providing addilional rein by recenl versions 01' the Uniform Building Code
forcement and encasemenl may be an effeclive meas (ICBO 1997). This Iimilation has been imposed
ure to strengthen or improve individual componenls. because ol' (he brittleness of conneclions and lack of
Increasing the diaphragm thickness may also be effec lest data concerning the various precasl syslems.
ti ve, but the added weight may overload the foolings Special consideration shall be given to diaphragm
and increase the seismic loads. Lowering seismic chords in precasl conslruclion.
demand by providing addilionallateral-force-resisling
elements, introducing additional damping, or base 6.11.2 Analysis, Modeling, and Acceptance Criteria
isolating the structure may also be effective rehabilita Analysis and modeling of precasl concrete
tion measures. diaphragms shall conform lo Section 6.10.2.2, wilh the
added requiremenl lhallhe analysis and modeling shall
account for the segmenlal natufe of lhe individual
6.11 PRECAST CONCRETE DIAPHRAGMS componenls.
Component slrenglhs shall be determined in accor
6.11.1 Components of Precast Concrete dance with Section 6.10.2.3. Welded connection
Diapbragms strength shall be based on ralional procedures, and con
Precast concrete diaphragms are elements com neclions shall be assumed to have liule duclilily capac
prising primarily precasL components with or with ily unless lesl dala verify higher ductilily values. Precasl
out topping, that transmit shear forces from within concrele diaphragms with reinforced concrele topping
a structure to vertical lateral-force-resisting elemenls. slabs shall be considered deformalion-controlled in
Precast concrete diaphragms shaIl be elassitied as shear and tlexure. m-faclors shall be taken as 1.0, 1.25,
topped 01' untopped. A lopped diaphragm shall be and 1.5 for Immediate Occupancy, Life Safety, and
detined as one that ineludes a reinforced structural Collapse Prevention Performance Levels, respeclively.
concrete topping slab poured over the compleled pre Untopped precast concrete diaphragms shall be
caSl horizontal system. An unlopped diaphragm shall considered force-conlrolled.
be detined as one construcled 01' precasl componenls
wilhout a structural cast-in-place topping. C6.11.2 Analysis, Modeling, and Acceptance
Criteria
C6.11.1 Components of Precast Concrete Welded conneclion strenglh can be delermined
Diaphragms using lhe latesl version of the Precast Concrete
Seclion 6.10 provided a general overview 01' con Institute (PCI) Handbook (PCI 1999). A discussion oí'
crete diaphragms. Components of precast concrete design provisions for unlopped precast diaphragms can
diaphragms are similar in nalUfe and function lo lhose be found in the Appendix lo Chapler 9 01' FEMA 368
01' cast-in-place diaphragms, with a few critical differ (FEMA 200 1).
ences. One is that precast diaphragms do not possess The appendix lo Chapler 9 of FEMA 450 (FEMA
lhe inherent unity of casl-in-place monolithic con 2004) provides discussion of the behavior of untopped
struction. Additionally, precast components may be precasl diaphragms and outlines a design approach
highly slressed due lo prestressed forces. These that may be used for such diaphragms to satisfy the
forees cause long-term shrinkage and creep, which requiremenls of this standard.
shorlen lhe componenl over lime. This shortening
tends lO fracture conneclions that restrain the 6.11.3 Rehabilitation Measures
component. Precast concrete diaphragms thal do nol meel the
MOSl floor systems have a topping system, bul acceplance crileria for the selected Rehabilitation
sorne hollow-core floor systems do no1. The lopping Objective shall be rehabilitated. Rehabililation meas
slab generally bonds to the lop of the precast compo ures shall meellhe requirements of Section 6.3.7 and
nents, bul may have an inadequate thickness al the olher provisions of lhis slandard.
center of the span, or may be inadequately reinforced.
AIso, exlensive cracking ofjoinls may be present C6.11.3 Rehabilitation Measures
along the panel joinls. Shear lransfer at lhe edges of Seclion 6.10.3 provides guidance for rehabilita
precast concrete diaphragms is especially crilical. tion measurcs for concrete diaphragms in general.
196
ASCElSEI 41-06
Special care should be laken lo overcome Ihe seg piles by the pile cap. Pile 1'oundalion resistance lo ver
mental nature of precasl concrele diaphragms, and lo tical loads shall be calculated based on the direct bear
avoid damaging prestressing slrands when adding ing of Ihe pile lip in Ihe soil, lhe skin fríction or cohe
conneclions. sion of Ihe soil on the sur1'ace area ol' (he pile, or based
on a combination of these rnechanisms. Lateral loads
resistance shall be calculated based on passive pres
6.12 CONCRETE FOUNDATION COMPONENTS sure ol' (he soil on the vertical face of the pile cap, in
combinalion with interaction of the piles in bending
6.12.1 Types 01 Concrete Foundations and passive soíl pressure on the pile surface.
Foundalions shall be detined as lhose components
Ihat serve to transmit loads from the vertical structural 6.12.1.2.2 Cast-in-Place Pi/e Foundations Cast-in
subsystems (columns and walls) of a building to the place concrete pile foundations shall consist of rein
supporling soil or rock. Concrete foundalions for forced concrete placed in a drilled or excavated shaft.
buildings shall be classified as either shallow or deep Casl-in-place pile or pier l'oundations resistance lO ver
foundalions as defined in Chapler 4. Requirements of tical and lateral loads shall be calculaled in the same
Seclion 6.12 shall apply lo shallow foundations thal manner as that 01' driven pile foundations specitied in
inelude spread or isolated footing. strip or line footing, Section 6.12.1.2.1.
combinalion fooling, and concrele mal footing; and lO
deep foundalions Ihat inelude pile foundations and C6.12.1.2 Deep Foundations
casl-in-place piers. Concrele grade beams shall be
permiued in both shallow and deep foundalÍon sys C6. 12.1.2.1 Driven Pite Foundations In poor soils, or
tems and shall comply wilh the requiremenls of soils subject lo liquefaclion, bending of the piles may
Seclion 6. l 2 be the only dependable resistance to laleralloads.
The provisions of Section 6.12 shall apply lo
existing foundalÍon componenls and LO new malerials C6. 12.1.2.2 Cast -in- Place Pite Foundatiolls
or componenls Ihat are required lo rehabililale an Segmemed steel cylindrical liners are available lo forrn
existing building. the shaft in weak soils and allow lhe liner to be
removed as the concrete is placed. Various slurry
6.12.1.1 Shallow Foundations mixes are often used lo prolect the drilled shal't from
Existing spread foolings, strip l'oolings, and com caving soils. The slurry is then displaced as the con
binalion footings are reinforced or unreínl'orced. crete is placed by the tremie method.
Verlical loads are transmitted by Ihese foolÍngs lO Ihe
soil by direCI bearing; lareral loads are transmitted by 6.12.2 Analysis 01 Existing Foundations
a combination of friction between the boUom of the For concrete buildings, components shall be con
footing and Ihe soil, and passive pressure of the soil on sidered fixed against rotation at the top of the founda
the verlical face of the footing. tion if Ihe connections belween componenls and foun
Concrete mal foorings shall be reinforced lo resist dalions, Ihe foundalions and supporting soil are shown
Ihe flexural and shear slresses resulting from Ihe to be capable 01' resisting the induced moments. Where
superimposed concentrated and line slructural loads components are nol designed lo resist flexural
and Ihe distribuled resisting soil pressure under the momenls, or Ihe conneclions between components and
fooling. Lateral loads shall be resisled by l'riclion foundations are not capable 01' resisting lhe induced
belween Ihe soil and Ihe boltom ol' Ihe fooling, and by moments, they shall be modeled wilh pinned ends. In
passive pressure developed against l'oundalion walls such cases, the column base shall be evaluated for the
Ihat are parl of Ihe system. resulting axial and shear forces as well as Ihe abilily lo
accommodate the necessary end rolalÍon ol' lhe
6.12.1.2 Deep Foundations columns. The eftects 01' base tixily of columns shall be
taken into account at the point of maximum displace
6.12.1.2. J Driven Pite Foundations Concrete pile ment of the superstructure.
foundations shall be composed 01' a reinforced con If a more rigorous analysis procedure is used,
crete pile cap supported on driven piles. The piles appropriate vertical, lateral, and rotational soil springs
shall be concrete (wilh or without prestressing), sted shall be incorporated in the analytical model as
shapes, steel pipes, or composite (concrete in a driven described in Section 4.4.2. The spring characteristics
steel shell). Verticalloads shall be transmined lo the shall be as specified in Chapler 4. Rigorous analysis ol'
197
SEISMIC REHABILlTATION OF EXISTING BUILDlNGS
struclures with deep foundalions in soft soils shall C6.12.4.1 Rehabilitatioll Measures for Shallow
be based on specjal soil-pile interaclion studies to FoUlldatiolls
determine lhe probable loeation oí' lhe pojnt 01' íixity
l. Enlarging the existing footing by lateral
in the 1'oundation and lhe resuIting dislribution 01'
additions. Enlarging Ihe existing footing may be an
1'orces and displacements in the superstruclure. In
efrective rehabililation meaSure. The enlarged 1'oot
lhese analyses, lhe appropriate representation 01' lhe
ing may be considered to resist subsequenl aclÍons
connection of lhe pile lO the pile cap shall be included
produced by the design loads, provided thal ade
in the model. Piles with less lhan 6 in. of embedment
quate shear and moment transfer capacily are pro
wilhoul any dowels into lhe pile cap shall be modeled
víded across the joint belween the cxisting fooling
as being "pinned" lo lhe cap. Unless lhe pile and
and lhe additions;
pile cap conneetion detail is identified as otherwise
2. Underpinning the footing. Underpinning an exist
from the available construetion documents, the
ing footing involves the removal 01' unsuitable soiJ
pinned connection shall be used in the analytical
underneath, couplcd with replacement using con
mode!.
crete, soil cement, suitable soil, or other material.
Where lhe 1'oundations are included in lhe anal yti
Underpinning should be staged in sl11all increments
cal model, lhe responses of the foundalion components
to prevent cndangering the stability 01' the structure.
shall be considered. The reaclions 01' struclural compo
This technique may be used to enlarge an existing
nents attached at the foundation (axial load s, shears,
footing or lo extend it lo a more competent soil
and moments) shall be used to evaluate the individual
stratum;
components of the foundation syslem.
3. Providing tension tie-downs. Tension tíes (soil
and rock anchors-preslressed and unslressed) may
C6.12.2 Analysis of Existing Foundations be drilled and grouled il1to competenl soils and
Overturning momenls and eeonomics may diclale anchored in lhe existing footing lo resisL uplift.
lhe use 01' more rigorous analysis procedures. Increased soil bearing pressures produced by lhe
ties should be checked against Ihe acceplance crÍle
6.12.3 Evaluation of Existing Condition ria 1'01' the sclcctcd Performance Level specitied in
Allowable soil capacilies (subgrade modulus, Chapter 4. Piles 01' drilled picrs may also be e1'fec
bearing pressure, passive pressure) and foundalion live in providing lension tie-downs of exisling
displacements for Ihe scJected performance level foolings;
shall be as prescribed in Chapler 4 or as established 4. Increasing effective depth of footing. This method
with project-speciíic dala. AII components 01' exist involves pouring new concrete lo increase shear
ing foundation syslems and all new material, compo and momenl capacity 01' Ihe existing footing. The
nenls, 01' components required 1'or rehabililation new concrete must be adequately dowcled or other
shall be evaluated as 1'orce-conlrolled aClions. How wise connected so that it is integral with the exist
ever, the capacity 01' Ihe foundalion componenls need ing 1'ooting. New horizontal reinforcement should
not exceed ] .25 times the capacily 01' lhe supporled be provided, if required, to resis! increascd
verlical slructural componenl or eIemenl (column momenls;
or wall). 5. Increasing the effective depth of a concrete mat
foundation with a reinforced concrete overlay.
This melhod involves pouring an integral topping
6.12.4 Rehabilitation Measures slab over the existing mat lo increase shear and
Exislíng foundations that do nol meet the accep moment capacity;
lance criteria 1'or the seIected Rehabilitation Objective
6. Providing pile supports for concrete footings or
shaU be rehabilitaled. Rehabilitalion measures shall
mat foundations. Adding ncw piles may be cflcc
meet the requiremenls of Seclion 6.3.7 and olher pro
live in providing support for exisling concrele t'ool
visions 01' this slandard.
ing or mat foundalions, provided lhe pile locations
and spacing are designed to avoid overslrcssing lhe
C6.12.4 Rehabilitation Measures existing foundations;
Rehabililalion measures descríbed in Sec 7. Changing the building structure to reduce the
tion C6. J2.4.1 for shallow foundations and in Sec demand on the existing elements. This melhod
Lion C6.12.4.2 1'or deep 1'oundalions may be etl'ective involves removing mass or heighl 01' the building or
in rehabililating existing foundalions. adding other material s or components (such as
198
ASCE/SEI 41-06
199
SEISMIC REHABILITATION 01" EXlSTING BUILDINGS
specifications, and other documents for the existing 7.2.2 Properties of In-Place Materials
construction in accordance with requirements of
Section 2.2. Where such documents fail to provide 7.2.2.1 General
adequate information 10 quantify masonry material The following component and eonneclion material
properties or Ihe condilion of masonry components of properties shall be obtained for the as-built structure in
the structure, such information shall be supplemented accordance with Sections 7.2.2.1 through 7.2.2.1 O:
by materials tests and assessmenlS of existing condi
l. Masonry eompressive strength;
tions as required in Section 2.2.6.
2. Masonry tensile strength;
Material properties of existing masonry compo
3. Masonry shear strength;
nents shall be determined in accordance with Sec
4. Masonry elastic modulus;
tion 7.2.2. A condilion assessmenl shall be conducted
5. Masonry shear modulus; and
in accordance with Seclion 7.2.3. The extent of materi
6. Strength and modulus of elasticity of reinforcing
als testing and condition assessment performed shall
steel.
be used to determine the knowledge factor as specified
in Section 7.2.4. Where material tesling is required by Section
Use of default material properties shall be permit 2.2.6, test melhods to quantify masonry material prop
ted in accordance with Section 7.2.2.l0. erties shall eomply with Sections 7.2.2.2 through
Use of material properties based on historieal 7.2.2.8. The minimum number of tests shall comply
information as default values shall be as specitied in with the requirements 01' Section 7.2.2.9.
Section 7.2.2.10. Other values of material properties Expected material propelties shall be based on
shall be permitted if rationally justitied, based on mean values from test data unless specitied otherwise.
available historieal information for a particular type Lower-bound material properties shall be based on
of masonry construction, prevailing codes, and assess mean values from test data minus one standard devia
ment of existing conditions. tion unless specified otherwise.
Procedures for detlning masonry structural systems The condition of exisling masonry shall be cIassi
and assessing masonry condition shall be conducted in fied as good, fair, or poor as defined as follows, or
accordance wilh the provisions stated in Section 7.2.3. based on olher approved procedures that consider the
nature and extenl of damage or deterioration present.
Good Condition: Masonry found during condi
C7.2.1 General tion assessment lo have mortar and units intacl with no
Construction of existing masonry buildings in visible cracking.
the United States dates back lO lhe 1500s in the south Fair Condition: Masonry found during condition
eastern and southweslern regions, to the 1770s in assessment to have mortar and units intaet but with
the central and eastern regions, and LO the 1850s minor cracking.
in the western half of the nation. The stock of Poor condition: Masonry found during condition
existing masonry buildings in the UnÍled Slales is assessment lo have degraded mortar, degraded
composed largely of structures constructed in lhe masonry units, or signiticant cracking.
last 150 years. Since the types of units, mortars, and
construction methods changed during this time, C7.2.2.1 Gelleral
knowing the age of a masonry building may be The design professional is referred lo FEMA 306
userul in idenlifying the characterislics of ilS con (FEMA 1998), FEMA 307 (FEMA 1998), and FEMA
struction. Ahhough structural properties cannol be 308 (FEMA 1998) for additional informalÍon regard
inferred solely from age, sorne background on typical ing the condition of masonry. The classitication of the
materials and methods for a given period can help to condition of masonry requires consideration of the
improve engineering judgment and provide sorne type of component, the anticipated mode of inelastic
direction in the assessment of an existing building. behavior, and lhe nature and extent 01" damage or dele
The design professional should be aware that values rioration. These documents also contain extellsíve
given in sorne existing documents are working stress information regarding lhe effecls of damage on
values ralher lhan the expected or lower-bound strength, stitrness, and displacement Iimits for
strengths used in lhis standard. masonry components. Included are damage classitica
As indicated in Chapter 1, great care should be tion guides with visual representalions of typical
exercised in selecting the appropriate rehabilitation earthquake-related damage of masonry components,
approaches and techniques for applicalion to historie which may be useful in classifying the condition of
buildings 10 preserve their unique charaeteristics. masonry ror lhis slandard. The severity 01" damage
200
ASCElSEl 41-06
described in FEMA 306, FEMA 307, and FEMA 308 [ions shall be measured to determine modulus val
is calegorized as Insignificanl, Slight, Moderate, ues;or
Heavy, and Extreme. Masonry in good condilion has 2. For solid unreinforced masonry, lhe modulus can
severily of damage not exceeding Insignificant or be measured using a tlatjack lest in accordance
Slighl, as defined by FEMA 306. Masonry in fair con withASTM C1l97-03 (ASTM 2003).
dition has severily of damage not exceeding Moderate.
Masonry with Heavy or Extreme damage is c1assified
C7.2.2.4 Masonry Elastic Modulus in
as Poor.
Compression
Both methods measure vertical strain belween two
7.2.2.2 Nominal or Specified Properties gauge points to ínfer slrain, and lhus elastic modulus.
Nominal material properties, or properties specified They are furlher described in FEMA 274 (FEMA
in construction documents, shall be taken as lower 1997), Section C7.2.2.2.
bound material properties. Corresponding expecled
material properties shall be calculaled by muItiplying
lower-bound values by a factor as specitied in Table 7-2 7.2.2.5 Masonry Flexural Tensile Strength
10 translale from lower-bound to expecled values. Expecled tlexurallensile slrength,f"" for out-of
plane bending shall be measured using one of lhe fol
7.2.2.3 Masonry Compressive Strength lowing lhree methods:
Expected masonry cornpressive slrenglh,lme' shall
be measured using one of Ihe following three melhods: l. Test samples shall be extracted from an existing
wall and subjected to minor-axis bending using the
l. Test prisms shall be eXlracled frorn an existing wall bond-wrench melhod of ASTM CIOn-oo (ASTM
and tested in accordance with Seclion L4.B.3 of 2000);
ACI 530.11ASCE 6fTMS 602, Specificatianslar 2. Test samples shall be tested in situ using the bond
Masoflry Structures (ACI 2002); wrench method; or
2. Prisms shall be fabricaled frorn actual extracted 3. Sample wall panel s shall be extracted and subjected
masonry units, and a surrogate mortar designed on 10 minor-axis bending in accordance with ASTM
Ihe basis of a chemical analysis of actual mortar E518-02 (ASTM 2002).
samples. The test prisms shall be tested in accor
dance with Section 1.4.B.3 of ACI 530.IIASCE F1exural tensile strength for unreinforced masonry
6rrMS 602; or (URM) walls subjecled lo in-plane laleral torces shall
3. For solid unreinforced masonry, lhe strenglh of lhe be assumed 10 be equal lo Ihal for oUI-of-plane bend
masonry can be estimaled using a flaljack tesl in ing, unless lesting is done to define the expected ten
accordance with ASTM CI196-03 (ASTM 2003). sile strength for ín-plane bending.
For each of lhe Ihree methods enurnerated in Ihis C7.2.2.5 Masonry Flexural Tensile Strength
section, the expected compressive strength shall be The flexurallensile strength of older brick
based on lhe nel mortared area. masonry walls constructed with lime rnortars may
often be neglected. The tensile strength of newer con
C7.2.2.3 Masonry Compressive Strength crete- and clay-unit masonry walls can result in appre
The three test methods are further described in dable flexural strengths.
Section C7.2.2.1 of FEMA 274 (FEMA 1997). As an The three test methods for out-of-plane bending
alternative to the test rnethods given in this section of are further described in Section C7.2.2.3 of FEMA
Ihis standard, the expected masonry compressive 274 (FEMA 1997). For in-plane bending, flexural
strength rnay be deduced from a nominal value pre stress gradients across lhe seclion width are much
scribed in ACI 530.IIASCE 6rrMS 602 (ACI 2002). lower than for out-of-plane bending. Thus, dala from
tests described in tbis section will be very conservative
7.2.2.4 Masonry Elastic Modulus in Compression and should be used only in lieu of data on in-plane
Expected values of elastic modulus for masonry in tensile slrength.
compression, Eme, shall be measured using one of the
following two methods:
7.2.2.6 Masonry Shear Strength
l. Test prisms shall be extracted from an existing wall For URM componenls, lower-bound shear
and lested in compression. Stresses and deforma strength shall be measured using an approved in-place
201
SEISMIC REHABILlTATION OP EXISTINO BUlLDINOS
shear test. Lower-bound masonry shear strength, V mú Section C7.3.2.5 for additional in1'ormation regarding
shall be determined in accordance with Eq. 7-1: masonry shear modulus.
202
ASCFlSEI 41-06
tloors 01' construclion 01' 3,000 s1' of wall surface, If mean values from in situ material tests are less
if original construction record s are availabJe that Ihan the defauIt values prescribed in Section 7.2.2.10,
specify material properties; six tests shall be per the number 01' tests performed shall be doubled.
formed i1' original construclion record s are nol
available. At least two tesIS shall be performed C7.1.1.9 Mí"imum Number of Tests
for each wall 01' line 01' wall elements providing a The number and location 01' material tests should
common resislance to lateral rorces. A mínimum be selected lo provide sufficienl information lo ade
of eight teSIS shall be performed 1'01' each building; qualely define Ihe exisling condilion 01' materials in
and Ihe building. Test locations should be identified in
2. For masonry in pOOl' condition as defined in Ihose masonry componenls thal are determined to be
Ihis standard, addiLional tesIs shall be done lo critical lo lhe primary palh 01' lateral-force resislance.
eSlimate material strengths in regions where
7.1.1.10 Default Properties
properlies differ, or nondeslruclive condition
Use of default material properties lo determine
assessment tests in accordance with Section 7.2.3.2
component strengths shall be permitted with the linear
shaIl be used to quanlify variations in material
analysis procedures in Chapter 3.
strengths.
Defaull lower-bound values for masonry compres
Samplcs for tests shall be taken at locations repre sive strength, elastic modulus in compression, flexural
sentative 01' the material condilions Ihroughoul Ihe tensile strength, and masonry shear strength shall be
entire building, taking in lo accounl varialÍons in work based on Table 7-1. Default lower-bound masonry
manship at differenl slory levels, variations in wealher properlies for fair condilion shall be equal lo two
ing of the exterior surfaces, and variations in the con Ihirds of Ihe values for masonry in good condilion.
dition 01' the interior surfaces due lo deterioration Default lower-bound masonry properlies for poor Con
caused by leaks and condensation 01' water aml/or the dilion shall be equal lo one-third of Ihe values for
deleterious effecLs of oLher substances contained good condition. Default expected strenglh values fOl'
within the building. masonry compressive strength, elastic modulus in
An increased sample size shall be permitted to compression, t1exural tensile strenglh, and masonry
improve the contidence leve!. The relation belween shear strength shaIl be determined by mulliplying
sample size and contidence shall be as detined in lower-bound values by an appropriate factor taken
ASTM E 139-00 (ASTM 2000). from Table 7-2.
lf Ihe coefficient 01' variation in test measuremenls Default lower-bound and expecled slrength yield
exceeds 25%, the number 01' tests performed shall be stress values for reinforcing bars shall be determined
doubled. in accordance with SecLion 6.2.2.5.
Masonry Condition l
j Masonry condilion shall be c1assitied as good, tilir, or poor as detined in Section 7.2.2.1
'JI shall be pernútted 10 lalce default lower-bound values for masonry compressive stfenglh in good condítion from TOOle 1 and 2 from Section 1.4
of ACI 530.I/ASCE 6/TMS 602 (ACI2002).
lit shall be permiued 10 talce default Iowefebound values fOf masonry flexural tensile strength in good oondition /'rom TOOle 3.1.7.2.1 of
ACI 5301ASCE SffMS 402 (ACl 2002).
411 shall be permitted lo talce default lower-bound shear strenglh of unreinforced masonry in good condilion from Sectíon 3.3.4 of ACI 5301
ASCE 5ffMS 402 (ACI 2002).
203
SEISMIC REHABILlTATION OF EXISTING BUILDlNGS
Table 7-2. Factors to Translate Lower-Bound 3. Other conditions, inc\uding the presence and
Masonry Properties to Expected Strength Masonry attachment of veneer, neighboring party walls and
Properties' buildings, presence of nonslructural components,
prior remodeling, and limitations for rehabilitation
Property Factor that may intluence building performance, shall be
Compressive Strength U",e) 1.3 identified and documented.
Elastic Modulus in Compression 2
The condition of the masonry shall be c\assified
Flexural Tensile Strength 1.3
Shear Strength 1.3 as good, fair, 01' poor as deJined in lhis standard, based
on lhe resuIts of visual examinalÍon conducted in
'See Chapler 6 for properties of reinforcing steel accordance wilh Section 7.2.3.1.
'The expected elastic modulus in compression shall be laken as
SSQf;", where/;", is the expected masonry compressive slrcngth. C7.2.3 Condition Assessment
Buildings are often conslructed wilh vencer as an
architectural linish, which may make the wall appear
thicker than lhe actual structural thickness. In many
areas of the country, the veneer wythe is separated
C7.2.2.10 Default Properties
from the structural wall by an air space to provide ven
Default properties for masonry based on the tables
tilation and moisture control. This is called cavity walI
in current code provisions are applicable to buildings
conslruction. In this case, lhe vencer may be anchored
built with material s similar to those specified in cur
but does not add any strenglh to the assembly.
rent codeso Where materials are different (i.e., type oi'
In areas of the soulhwest United States and along
mortar, unit strength, air-entrainment), defauIt proper
the California coast (as well as other regions), the
ties should be based on Table 7-1.
vencer is placed directly against lhe building walJ. It
DefauIt values of compressive strength are set at
will be in a running bond pattern without a header
very low stresses to retlect an absolute lower bound.
course. Other patterns are also seen. If the veneer is
Masonry in poor condition is given a strength equal to
not anchored or has a layer 01' building paper belween
one-third of that for masonry in good condition, to
it and the inner wythe, it cannot be considered as part
reflect the influence oi" mortar deterioration and unit
of the structural wall.
cracking on compressive strength. The coefticient of
Veneer on modern buildings may be adhered or
550 for default values of elastic modulus in compres
anchored. In either case, the veneer is a weight to be
sion in Table 7-1 is set lower than values given in the
considered but does not contri bu te to a wall's strength.
lnternational Building Code (ICC 2(03) to compen
In all cases, the veneer must be anchored to prevent its
sate for larger values of expected strength. Default val
detaching during an earthquake. Requiremenls for
ues for flexural tensile strength are set low even for
veneer are specified in Chapler 11.
masonry in good condition because of its dependence
Face brick bonded to the inner wythes with a reg
on the unit-mortar bonding, which can be highly vari
ular pattern of header eourses is not veneer. In this
able due to the variability of the condition oi' the mor
case, the outer wythes are part of the structural wall
tar. Comparison oi" default masonry shear values with
and can be used in evaluating the height-to-thickness
values that may be obtained from Eq. 7-1 shows thal if
ratio of the wall.
in-place shear tests are done, a significant increase in
See Section C7.2.2.1 regarding the use of FEMA
strength over default values is possible.
306 (FEMA 1998), FEMA 307 (FEMA 1998), and
7.2.3 Condition Assessment FEMA 308 (FEMA 1998) for additional information
A condition assessment of the existing building in c\assifying the condition of masonry.
and site conditions shall be performed as specified in
7.2.3.1 Visual COllditioll Assessmellt
Sections 7.2.3.1 through 7.2.3.3.
The size and 10calÍon 01" alI masonry shear and
A condition assessment shall include the following:
bearing walIs shalI be determined by visual examina
1. The physical condition of primary and secondary tion. The orientation and placement of lhe waIls shalI
components shall be examined and the presence of be noted. OveraIl dimensions of masonry components
any degradation shall be noted; shalI be measured or determined from plans, including
2. The presence and configuration of components and wall heights, lengths, and thicknesses. LocatÍons and
their connections, and the continuity of load paths sizes of window and door openings shalI be measured
between components, elements, and systems shall or determined from plans. The distribution of gravity
be veriJied or eSlablished; and loads to bearing walIs shaIl be estimated.
204
ASCEJSEI 41-06
205
SElSMIC REHABILlTATION OF EXlSTlNG BUILDlNGS
small variations in masonry properties and minor masonry material properties or to assess condition.
cracking. The mechanical pulse method should be Possible supplemental tests are described as follows.
used in lieu of the uHrasonic pulse method where
overall mean properties of a large portio n of masonry
C7.2.3.3. J Surface Hardness The surface hardness of
are ol' interest.
exterior wythe masonry can be evaluated using the
The use of mechanical pulse velocity measure
Schmidt rebound hammer. Researeh has shown that
ments for masonry condition assessments has been
the technique is sensitive to differenees in masonry
confirmed through research by Epperson and Abrams
strength, but cannot by itself be used to determine
(1989) and Kingsley et al. (1987). Allhough no stan
absolute strength. A Type N hammer (5,000 lb.) is rec
dard exiS1S for mechanical pulse velocity tests with
ommended for normal-strength masonry, while a
masonry, a standard l'or concrete materials [ASTM
Type L hammer (1,600 lb.) is recommended for lower
C597-02 (ASTM 2002)] does exist.
strength masonry. Impacts at the same test location
should be eonlinued until consistent readings are
C7.2.3.2.3 Impact Echo The impact-echo technique
obtained, because surface roughness can affect ¡nitial
can be use1'ul for nondestructive determination of
readings.
the location 01' void areas within grouted reinforced
The method is Iimited 10 tests of only the surfaee
walls, as reported by Sansalone and Carino (1988).
wythe. Tuckpointing may intluence readings and the
Commercial devices are available or systems can be
method is not sensitive lo cracks.
I assembled using available electronic components.
Measurement of surface hardness for masonry
r. Since this technique cannot distinguish between a
walls has been studied by Noland et al. (1987).
shrinkage crack at the grout-unit interface and a com
plete void in the grout, drilJing of small holes in the
'1
• bed joint or examination using an optical boreseope C7.2.3.3.2 Vettical Compressíve Stress In situ vertical
should be performed to veri1'y the exact eondition. compressive stress resisted by Ihe masonry can be
measured using a thin hydraulic l1atjack Ihal is
C7.2.3.2.4 Radiography A number of eommereial inserted into a removed mortar bed joint. Pressure in
radiographic (x-ray) devices exist that can be used to the tlatjack is increased until distortions in the briek
identify the loeation 01' reinforcing steel in masonry work are reduced to the precut condilion. Existing ver
walls. They are also useful for locating bed-joint rein tical compressive stress is inferred from the jack
forcing sleel, masonry ties and anchors, and eonduits hydraulic pressure, using correction factors for the
and pipes. The better devices can locate a No. 6 bar at shape and stiffness of the tlatjack.
depths up lo approximalely 6 in.; however, this means The method is userul for measurement of gravity
that 1'or a 12-in.-lhick concrete masonry wall, a bar load distribution, l1exural stresses in out-of-plane
located otr-center cannot be found where access is walls, and stresses in masonry veneer walls that are
limited to only one side of the wall. These devices are compres sed by a surrounding concrete rrame. The test
not able lo locate or determine the length of reinforc is Jimiled to only the faee wythe of masonry.
ing bar spliees in walls in most cases. They work best Not less than three tests should be done 1'or each
ror identi1'ying the localion 01' single isolated bars and section of the building 1'or which it is desired lo
become less userul where the congestion of reinforc measure in situ vertical stress. The number and loca
ing bars inereases. tion 01' tests should be determined based on the build
ing confíguration and the Iikelihood of overstress
7.2.3.3 Supplemental Tests condilions.
206
ASeE/SE( 41-06
Extrapolation of the test data to actual masonry Large-scale tests are expensive and limited to a
walls is difficult because the ratio of shear to normal single or few samples. They may result in considerable
stress is fixed at a constanl ratio of 1.0 for the test local damage and may require substantial reconstruc
specimens. Also, the distribution 01' shear and normal tion near the sample location. Test data must be
slresses across a bed joint may not be as uniform for a extrapolated to the remainder of the system, based on
test specimen as for an actual wall. Laslly, any redis a low confldence leve!.
tribution of stresses after the firsl cracking will not be
represented with the theoretical stress distributions. 7.2.4 Knowledge Factor
Thus, the test data cannot be useful to predict nonlin A knowledge factor for computation of masonry
ear behavior. component capacities and permissible deformalÍons
Ir the síze of lhe masonry unils relative to the shall be selectOO in accordance with Section 2.2.6.4.
panel dimension is large, masonry properties will be
not continuous, bUl discreteo Test panel s should be
a minimum of four ft square. The high cost and dis 7.3 MASONRY WALLS
ruption 01' extracting a number of panels this size
may be impracticaL The standard test method The procedures set forth in this section for determina
specitied in ASTM E519-02 (ASTM 2002) may tion of stitIness, strength, and deformation of masonry
be used. walIs shall be appliOO to building systems comprising
any combination of existing masonry walls, masonry
walls enhanced for seismic rehabilitation, and new
C7.2.3.3,4 Large-Scale Load Tests Large-scale walls added to an existing building for seismic
destructive tests may be done on portions of a rehabilitation.
masonry component or element lo (1) increase the Actions in a structure shall be classified as being
confidence level on overall structural properties; either deformation-controllOO or force-controlled as
(2) obtain performance data on archaic building mate deíined in Section 2.4.4.3. Design strengths for defor
rials and construction materials; (3) quantify effects of mation-controlled and force-controlled actions shall be
complex edge and boundary condilions around open caIculated in accordance with this sectíon.
ings and two-way spanning; and (4) verify or calibrate Strengths used for deformation-controlled actions
analytical models. Large-scale load tests do not are denoted QCf and shall be taken as equal to expected
necessarily have lo be run to the ultimate Iimit state. strengths obtainOO experimentally, calculated using
They may have value for simply demonstrating accepted mechanics principIes, or based on defauIt val
structural integrilY up lo sorne specitic performance ues listed in Section 7.2.2.10. Expected strength is
leve\. defined as the mean maximum resistance expected over
Out-of-plane strength and behavior of masonry the range of deformations to which the component is
walls can be determined with air-bag tests. Behavior Iikely to be subjectOO. Where calculations are used to
of test panels incorporating connections and edge define expectOO strength, expected material properties
details can be determined from such a test, in addition shall be used. Unless otherwise specified in this stan
to flexural and arching properties of a solid or perfo dard, use of strength design procedures specified in ACI
ratOO wall. Strength and deformation capacity under 530/ASCE 5rrMS 402 (ACI 2002) to calculate design
in-plane lateral forces can be determined by loading an strengths shall be permitted except that the strength
individual portion of wall that is cut free of the sur reduction factor, 4>, shall be taken equal to unity.
rounding masonry. Loading actuators are reacted Force-controllOO actions shall be as defined in
againsl adjacent and stronger portions of masonry. Section 2.4.4. Strengths used in design for force
Such testing is particularly useful where the waIl is controlled actions are denoted QCL and shall be
composed of different materials that cannot be evalu taken as equal to lower-bound strengths obtained
ated by testing an individual unil of an individual experimentally, caIculated using establishOO mechanics
wythe. principIes, or basOO on default values listed in Sec
Visual and nondestructive surveys should be used tion 7.2.2.10. Lower-bound strength is defined as the
to identify locations for test samples. mean minus one standard deviation of resistance over
Standards for laboratory test methods are pub the range oí" deformations and loading cycles to which
Iished by ASTM. ProcOOures for removal and trans the component is subjected. Where calculations are
portation of masonry samples are given in Building usOO 10 define lower-bound strengths, lower-bound
Science Series 62 (NBS 1977). material properties shalI be used. It shalI be permitted
207
SEISMIC REHABILlTATION OF EXISTING BUILDINGS
to calculate lower-bound properties from expected Component drift ralios are the ratio of dítTerential
properties using the conversion l'actors in Table 7-2. displacement, !le1J' between each end of the component
Unless otherwise specitied in this standard, use ol' oyer the effective height, h'jj' of the component.
strength design procedures specified in ACI 5301 Depending on the geometry of the wall nr wall pier
ASCE 5n'MS 402 lO calculate design strengths shaIl contiguration, the eleyations at which these parameters
be permitted except that the strength reduction factor, are determined may vary within the same wall ele
cp, shall be taken equal lo unity. Where aHernative def ment, as shown in Fig. C7 -l.
initions of design strength are used, they shall be justi Materials haying briUle behayior as shown in
tied by experimental evidence. Fig. 7-1(b) should be considered force-controlled
Where design actions are determined using the actions. Rocking of unreinforced masonry walls and
nonlinear procedures of Chapter 3, component force waJl piers haye a limited s emiductile behayior similar
deformation response shall be represented by nonlin to that shown in Fig. 7- J(a) i1' an components in a line
ear force-de1'ormation relations. Force-deformation of resistance haye an in-plane shear capacity greater
relations shall be based on experimental eyidence or than their rocking capacity.
the generalized l'orce-deformation relation shown
in Hg. 7- 1, with parameters e, d, and e as defined in 7.3.1 Types of Masonry Walls
Tables 7-4 and 7-7. Masonry walls shall be categorized as unrein
forced or reinforced; ungrouted, partially grouted,
C7.3 MASONRY WALLS or 1'ully grouted; and composite or noncomposite.
Masonry walls shall be capable of resisting forces
Expected yield strength of reinforcing steel, as speci applied parallel lo lheir plane and normal to their
fied in Ihis standard, inc\udes consideration 01' material plane, as described in Sections 7.3.2 through
overstrength and strain-hardening. 7.3.5.
Q
Qy
1.0
Q
Qy
1----- e ------"*1
···-d----..j
1.0 ...... ------:Cr:\
208
ASCElSEI41-06
C7.3.1 Types of Masonry Walls (BOCAl 1999), Standard Building Code (SBCCI
Any of these calegories of masonry elements can 1999), and the Uniform Building Code (ICC 2(03).
be used in combination with existing, rehabilitated, or Guidelines for seismic design of new buildings are
new lateral-force-resisting elements of other materials found in FEMA 302 (FEMA 1997).
such as steel, concrete, or tÍmber.
7.3.1.3 E"hanced Masonry Walls
7.3.1.1 Existing Maso1lry Walls Enhanced masonry walls shall inelude existing
Exisling masonry walls shall ¡nelude all slructural walls thal are rehabililaled by an approved method.
walls of a building system thal are in place prior 10
seismic rehabilítation. C7.3.1.3 Ellhanced Masonry Walls
Existing masonry walls shall be assumed 10 Methods of enhancing masonry walls are in tended
behave in lhe same manner as new masonry walls, lo improve performance of masonry walls subjecled 10
provided Ihat the masonry is in fair or good condition bOlh in-plane and out-of-plane lateral forces.
as detined in Ihis standard. Possible rehabilitation melhods are described in
SeclÍons C7.3.1.3.1 through C7.3.I.3.IO.
7.3.1.2 New MaSlJIlry Walls
New masonry walls shaIl inelude all new wall C7.3./.3.l Jnfilled Openings An infilled opening may
elements added lO an existing lateral-1'orce-resisling be considered 10 acl compositely with the surrounding
system. New walls shall be designed in accordance masonry if new and old masonry units are interlaced at
wilh lhe requirements sel forth in this standard and the boundary wilh full lOothing, or attached wilh
delailed and construcled in accordance wilh a building anchorage that provides compatible shear slrength al
code approved by the authority having jurisdiction. the interface of new and old units.
Sliffness assumptions, strength criteria, and
C7.3.1.2 New Masonry Walls acceptable deformations for masonry walls with
Codcs for new buildings inelude the lnternational intilled openings should be the same as given for non
Building Code (ICC 2003), National Building Code rehabilitated solid masonry walls; differences in elastic
moduli and slrengths for the new and old masonry
waIls should be considered for the composile
section .
.....,.-••?"
I
/
209
SEISMIC REHABILlTATION OF EXISTlNG BUILDINGS
StitIness assumplions, slrenglh criLeria, and e7.3.].3.7 Grout /njections Grout used for tílling
acceplable deformations for masonry componenls wílh voids and cracks should have strength, modulus, and
sholcrete should be lhe same as Ihal for new rein thermal properties compatible with the existing
forced concrete components. Variations in boundary masonry.
conditions should be considered. Inspections should be conducted in accordance
with Chapter 2 during the grouting process to ensure
C7.3./.3.4 Coatings for Unreinforced Masonry Walls that voids are completely filled wÍlh grout.
A coated masonry wall may be considered a compos Stiffness assumptions, strength criteria, and
ite section as long as anchorage is provided al the acceptable deformations for masonry walls with grout
inlerface between Ihe coating and lhe masonry wall lo injections should be the same as that for existing URM
Irans1'er shear forces. Stresses in lhe masonry and coal or RM walls.
ing should be determined considering the ditTerence in
elastic moduli for each material. If stresses exceed C7.3./.3.8 Repointillg Bond strength 01' new mortar
expected slrenglhs of lhe coatíng material, then lhe should be equal to 01' greater than that 01' the original
coating should be considered inetIective. mortar. Compressive strength 01' new mortal' should be
StitTness assumptíons, slrenglh crilería, and equal lo 01' less lhan that 01' the original mortal'.
acceptable deformatíons 1'01' coated masonry walls StitTness assumptions, strength crileria, and
should be lhe same as thal for existing URM walls. acceptable derormations for repointed masonry
walls should be the same as that for exisling masonry
C7.3./.3.5 Reinforced Cores for Unreinforced Masonry walls.
Walls A reinforced-cored masonry wall should be con
sidered to behave as a reinforced masonry (RM) wall, C7.3./.3.9 Braced Masonry Walls Masonry walls with
provided Ihat the bond betwecn Ihe new reinforcement height-to-thickness ratios in excess 01' those permiued
and the grout and between the groul and lhe cored sur by Table 7-5, or out-of-plane bending stresses in
face are capable 01' transferring seismic forces com excess of those permitted by Section 73.3.2, may be
puted in accordance with Chapter 3. Vertical reinforce braced with external structural elements. Adequate
ment should be anchored at the base ol' lhe wall 10 strength should be provided in the bracing e\ement
resisl lhe full tensile slrenglh 01' lhe wall. and connections lO resist the transfer oí' forces 1'rom
Grout in new reinforced cores should consist 01' the masonry wall to the braeing elemenL Out-of
cementilious materials whose hardened properties are pláne deflections oí' braced walls rcsulting from the
compatible wilh those 01' the surrounding masonry. transfer 01' vertical l100r 01' rool' loadings should be
Adequate shear strength must exisl, or should be considered.
provided, so Ihal lhe strength of the new vertical rein Stiffness assumptions, strength criteria, and
forcement can be developed. acceptable deformations ror braced masonry walls
Slilfness assumptions, strength criteria, and should be the same as that I'or existing masonry walls.
acceptable deformations for URM walls wilh rein The reduced span 01' the masonry wall should be con
forced cores should be lhe same as thal 1'01' existing sidered.
reinforced walls.
C7.3./.3. JO StijJening Elements Masonry walls with
e7.3./.3.6 Prestressed eoresfor Unreinlorced inadequale out-of-plane sti1'fness 01' strength may be
Masonry Walls A prestressed-cored masonry wall with stiffened wilh external structural members. The stitl'en
unbonded tendons should be considered 10 behave ing members should be proportioned to resis! a tribu
as a URM wall with increased verlical compressive tary portion of lateral load applied llormalto the plane
stress. 01' a masonry wall. Connections at the ends of the stiff
Losses in preslressing force due to creep and ening element should be provided lO transl'er the reac
shrinkage 01' lhe masonry should be accounted tion force. F1exibility of the stiiTening element should
ror in analyses conducted in accordance with be considered where eslimating lateral drift 01' a
Chapter 3. masonry wall panel.
StitTness assumplions, slrength criteria. and Stitl'ness assumptions. strength criteria, a-nd
acceptable del'ormalíons for URM walls with acceplable deformations ror stitTened masonry walls
unbonded prestressing tendons should be the same as should be lhe same as Ihal rOl' existing masonry walls.
1'01' exisling URM walls subjecled to vertical compres The stiffening action that the new element provides
sive stress. shall be considered.
210
ASeE/SEl 41-06
211
SEISMIC REHABILlTATION OF EXISTING BUILDINGS
tively. L/heff shall not be taken less than 0.67 for 7.3.2.3 Acceptance Cr;teria
use in Eq. 7-5. In-plane lateral shear of unreinforced masonry
walIs and wall piers in a single line of resistance shall
(Eq.7-4) be considered a deformation-controlled action if lhe
expecled lateral rocking slrenglh of each wall or wall
pier in the line of resislance, as specitied in Sec
fa ) (Eq.7-5)
0.7f~ tion 7.3.2.2.1, is less lhan lhe lower-bound lateral
strength of each wall or wall pier limited by shear or toe
where h,jfr L, and a are the same as given for Eq. 7-3 compressive Slress, as specitied in Section 7.3.2.2.2.
and: Unreinforced masonry walls nol meeting lhe crileria for
deformalion-conlrolIed componenls shall be considered
Vn/L = lower-bound masonry shear strength, force-controlled componenls. Expecled rocking
Eq.7-1; strength, V" as specitied in Section 7.3.2.2.1 shall
An = area of net mortaredlgrouted seclion; be neglected in lines of resistance nol considered
la axial compressive stress due to gravily loads deformation-controlled. Axial compression on URM
specified in Eq. 3-2; wall components shall be considered a force-controlled
f~, lower-bound masonry compressive slrenglh action.
delermined in accordance wilh Section 7.2.2.3;
Qo = lower-bound axial compressive force due lo 7.3.2.3. J Linear Procedures For lhe linear procedures
gravity loads specified in Eq. 3-3; in Sections 3.3.1 and 3.3.2, componenl aClions shall
VCL lower-bound shear strength for wall or walI be compared with capacities in accordance with
pier; and Section 3.4.2.2. The m-faclors for use with corre
V" ]ower-bound shear strength based on toe com sponding expected strenglh shall be obtained from
pressive stress for wall or walI pier. Table 7-3.
Table 7-3. Linear Static Procedure-m-factors for URM In-Plane Walls and Wall Píers
m-factors
Performance Level
Limiting
Behavioral Mode Primary Secondary
10 LS CP LS CP
Rocking I.Sh.glL 3heg/L 4heglL 6hfjj / L Sheu/ L
(not less Ihan 1) (not less Ihan 1.5) (not Iess than 2) (not less than 3) (not less than 4)
212
ASCE/SEI 41-06
Acceptance Criteria 2
Performance Level
Limiting
Behavioral Mode Primary Secondary
e (%) d (%) e(%) 10% LS% CP% LS% CP%
Rocking 0.6 0.1
Table 7-4, or an approved procedure based on a com or have an etIective void ratio greater than 50% shall
prehensive evaluation of the hysteretic characteristics not be considered part of the effective thickness of
of those components. the wall.
C7.3.3.2 Strength
7.3.3 Unreinforced Masonry Walls
This section applies to treatment of veneer for
Out-of-Plane
out-of-plane behavior of walls only. For in-plane
As required by Section 2.6.7, URM walls shall be
resistance, effective thickness is the sum of all wythes
evaluated for out-of-plane inertial torces as isolated
without consideration of the condition of the collar
components spanning between floor levels, and/or
joints.
spanning horizontally between columns or pilasters.
URM walls shall not be analyzed out-of-plane with the
7.3.3.3 Acceptance Criterio
LSP or NSP prescribed in Chapter 3.
For the Immediate Occupancy Structural
Performance Level, flexural cracking in URM walls
7.3.3.1 Stiffness due to out-of-plane inertial loading shall not be per
The out-of-plane stiffness of walls shall be ne mitted as limited by the tensile stress requirements of
glected in analytical models of the global structural Section 7.3.3.2. For the Life Safety and Collapse
system in the orthogonal direction. Prevention Structural Performance Levels, flexural
cracking in URM walls due to out-of-plane inertial
7.3.3.2 Strength loading shall be permitted provided that cracked
Unless arching action is considered, flexural wall segments will remain stable during dynamic
cracking shall be Iimited by the expected tensile stress excitation. Stability shall be checked using analyti
values given in Section 7.2.2.5. cal time-step integration models considering
Arching action shall be considered only if sur acceleration time histories at the top and base of a
rounding floor, roof, column, or pilaster elements wall panel. For the Life Safety and Collapse Preven
have sutlicient stitIness and strength to resist thrusts tion Structural Performance Levels, stability need
from arching of a wall panel, and a condition assess not be checked for walls spanning vertically with a
ment has been performed to ensure that there are height-to-thickness (hIt) ratio less than that given in
no gaps between a wall panel and the adjacent Table 7-5.
structure.
The condition of the collar joint shall be consid C7.3.3.3 Acceptance Criteria
ered where estimating the effective thickness of a For further information on evaluating the stability
wall tor out-of-plane behavior. The effective void of unreinforced masonry walls out-of-plane, refer
ratio shall be taken as the ratio of the collar joint area to Methodology for Mitigation of Seismic Hazards
without mortar to the total area of the collar joint. in Existing Unreinforced Masonry Buildings
Wythes separated by collar joints that are not bonded, (ABK 1984).
213
SEISMIC REHABILlTATION OP EXISTING BUlLDlNGS
Wall Types SXI :5 0.24 g 0.24 g < SXI :5 0.37 g SXI > 0.37 g
WaIls of One-Story Buildings 20 ló 13
Pirst-Story WalI ol' Multistory
Building 20 18 15
Walls in Top Story ol'
Multistory Building 14 14 9
Al! Other WaIls 20 16 13
7.3.4 Reinforced Masonry Walls and Wall Piers ering gravity loads and the maximum force s that can
In-Plane be transmiUed based on a limit-state analysis.
7.3.4.1 Stifflless
7.3.4.2.3 Vertical Compressive Strength ofWalls
The stiffness of an RM wall or wall pier compo
and Wall Píers Lower-bound vertical compressive
nent in-plane shall be determined as follows:
strength 01' existing RM walI or wall pier components
l. The shear stitl'ness 01' RM wall components shall be shall be detennined based on strength design proce
based on uncracked section properties; and dures specitied in ACl530/ASCE 5HMS 402
2. The flexural stiffness of RM wall components shaIl (ACI2002).
be based on cracked section properties. Use of a
cracked moment of inertia equal to 50% of 18 shall
7.3.4.2.4 Strength Considerations for Flanged Walls
be pennitted.
Wall intersections shall be considered effective in
In either case, veneer wythes shall not be consid transferring shear where either condition (1) or (2)
ered in Ihe calculation of wall component properlies. and condition (3) are mer:
Stiffnesses for existing and new walls shall be l. The face shells of hollow masonry units are
assumed to be the same.
removed and the intersection is fully grouted;
2. Solid units are laid in running bond, and 50% of
7.3.4.2 Strength the masonry units at the intersection are inter
The strength of existing, enhanced, and new locked;
RM waJl or wall pier components in tlexure, shear, 3. Reinforcemenl from one intersecting wall continues
and axial compression shall be determined in accor past lhe interseclion a distance not less than 40 bar
dance with Sectíon 7.3.4.2. The strength of tlanged diameters or 24 in.
RM walls shall also be in accordance with Sec The width of tlange consídered effective in com
tion 7.3.4.2.1 and 7.3.4.2.2. pression on each síde of the web shall be taken as the
lesser of six times the thíckness of the web, half lhe
7.3.4.2.1 Flexural Strength ofWalls and Watl Piers distance lo the next web, or lhe actual flange gn either
Expected flexural strength oi' an RM wall or waIl pier side of lhe web wall.
shall be determined based on strength design proce The width of tlange considered effective in ten
dures specified in ACI 530/ASCE 5fTMS 402 sion on each side of the web shall be taken as the
(ACT 2002). lesser of three-fourths of the wall heighl, half lhe dis
tance lO an adjacent web, or the actual tlange on eilher
7.3.4.2.2 Shear Strength ofWalls and Wali Piers The side of the web wall.
lower-bound shear streng¡h of RM wall or wall pier
components, VeL, shall be determined based on 7.3.4.3 Acceptance Críteria
strength design procedures specitied in ACI 5301 The shear requíred 10 develop (he expected
ASCE 5fTMS 402 (ACI 2002). Design actions (axial, strength of reínforced masonry walls and walI piers in
tlexure, and shear) on components shall be determined tlexure shall be compared to the lower-bound shear
in accordance with Chapter 3 of Ihis standard consid strength. For reinforced masonry wall componenls
214
ASCElSEI 41-06
Primary Secondary
governed by flexure, flexural actÍons shall be consid with capacities in accordance with Section 3.4.2.2.
ered deformation-controlled. For reinforced masonry The m-factor for use in Eq. 3-20 ror those components
components governed by shear, shear actions shall be cIassified as deformation-controlled shaH be as speci
considered deformation-controHed. Axial compression fied in Table 7-6.
on reinforced masonry wall or wall pier components For determination of m-factors from Table 7-6, the
shall be considered a force-controlled action. ratio of vertical compressive stress to expected com
pressive strength,.t:uIf,,¡e, shall be based on gravity
7.3.4.3. J Linear Pmcedures For the linear procedures compressive force determined in accordance with the
of Section 3.3.2, component actions shall be compared load combinations given in Eqs. 3-2 and 3-3.
215
SEISMIC REHABILITATION OF EXISTING BUILDlNGS
7.3.4.3.2 Nonlinear Procedures For the NSP of The out-of-plane stiffness of walls shall be neg
Section 3.3.3, wall and wall pier componenls shall lected in analytical models 01' the global struclural
meet the requiremenls 01' Seclion 3.4.3.2. Nonlincar system.
deformations on deformation-conlrolled components Stillness shall be based on the nel mortarcdl
shall not excced the values given in Table 7-7. grouted arca of the uncrackcd seclion, provided tha!
Variables d and e, representing nonlinear deformatíon ncl Ilexural tensile slress does not exceed thc expecled
capacities for primary and secondary components, tensile slrength, L, in accordance with Seclion 7.2.2.5.
shall be expressed in terms 01' story drift ratio percent StitTness shall be based on lhe cracked seclion 101'
ages as defined in Fig. 7-1. a wall where the net tlexural tensile stress excecds the
For determination of the e, d, and e values and the expected tensile strength.
acceptable drift levels using Table 7-7, the vertical Stitrnesses for existing and new rcinforccd out-of
comprcssive stress,!"" shall be based on gravity eom plane walls shall be assumed lo be lhe same.
pressíve force delermined in accordance wilh the load
combinations given in Eqs. 3-2 and 3-3.
7.3.5.2 Strength
For lhe NDP of Section 3.3.4, wall and wall
Expccted tlexural strength shall bc based on
piel' eomponents shalI meet the requirements 01'
Section 3.4.3.2. Nonlinear force--detlection relations Section 7.3.4.2.1. For walls wilh an hit ratio exceed
for deformation-conlrolled wall and walI pier compo ing 20, second-order momenl effects due 10 out-of
nents shall be eslablished based on lhe information plane detleclions shall be considered.
given in Tablc 7-7, or an approved procedure based on 111e strenglh of new and existing walls shall be
comprehensive evaluatíon of the hysteretie eharaeteris assumed lo be lhe same.
líes 01' those components.
Aeceptable deformations for existíng and new 7.3.5.3 Acceptallce Criteria
walls shall be assumed to be the same. Oul-of plane forces on reinrorced masonry walls
shal1 be considered rorce-controlled actions. Oul-of
C7.3.4.3.2 Nonlinear Procedures For primary eompo plane RM walls shall be sufticiently slrong in l1exure
nents, eollapse is eonsídered at lateral drift pereent to resist the out-of-plane loads prescribed in Sec
ages exceeding values of d in Table 7-7, and the Lile tion 2.6.7.
Safety Struclural Performance Leve! is considered al Ir the NDP Ís used, the following performance cri
approximate!y 75% of d. For secondary eomponenls, teria shall be based on the maximum out-ot:'plane
collapse is considered al lateral drift percenlages del1ection normal to the plane 01' a wall:
exceeding the values of e in the lable, and the Life
Safely (LS) Structural Performance Leve) is consid l. For lhe Immediate Occupancy Structural
en:d al approximately 75% 01' e. Story drifl ratio Performance Level, the out-of-plane story drift
pereentages based on these eriteria are given in ratio shall be cquallo or less Ihan 2%;
Table 7-7. 2. For lhe Life Salely Struclural Performance Level,
the out-of-plane story drift ratio shaJl be equal to 01'
less lhan 3%; and
7.3.5 Reinforced Masonry Walls Out-of-Plane
3. For lhe Collapse Prevention Structural Performance
RM walls shall be capable of resisting out-of
Level, lhe oUl-of-plane story drift ralio shall be
plane inertial forces as isolaled componenls spanning
equal to or less than 5%.
between floor levels, and/or spanning horizontally
belwcen columns or pilasters. Walls shall not be ana
Acceptable detormations foc exisling and new
Iyzed out-of-plane with the LSP or NSP prescribed in
walls shall be assumed to be the same.
Chapler 3, but shalJ be capable of resisling out-oí:'
plane inertial torces as given in Seclion 2.6.7, or be
capable 01' responding to earthquake motions as deler C7.3.5.3 Deformation Acceptance CriterÚl
mined using the NDP, while satisfying lhe detlection The limit slatcs specified in this scclion are based
criteria given in Section 7.3.5.3. on lhe masonry units having significant cracking rOl"
Immediate Occupaney (10), masonry unÍls at a poinl
7.3.5.1 StijJness 01' being dislodged and falling out of the wall 101' LS,
RM walls shall be considered local elemenls and masonry units on lhe verge of collapse for
spanning oUI-of-plane belwcen individual slory levels. Collapse Prevcntion (CP).
216
ASCElSEI 41-06
Table 7-7. Modeling Parameters and Acceptance Criteria for Nonlinear Procedures-Reinforced
Masonry In-Plane Walls
Performance Level
Component Type
Prímary Secondary
!../!me L/he/f Pg/Yel!me e (%) d(%) e(%) 10 (%) LS (%) CP(%) LS(%) CP(%)
0.00 :<;; 0.5 0.01 0.5 2.6 5.3 1.0 2.0 2.6 3.9 5.3
0.05 0.6 1.1 2.2 004 0.8 1.1 1.6 2.2
0.20 0.7 0.5 1.0 0.2 004 0.5 0.7 1.0
1.0 0.01 0.5 2.1 4.1 0.8 1.6 2.1 3.1 4.1
0.05 0.6 0.8 1.6 0.3 0.6 0.8 1.2 1.6
0.20 0.7 0.3 0.6 0.1 0.2 0.3 0.5 0.6
:;:::: 2.0 0.01 0.5 1.6 3.3 0.6 1.2 1.6 2.5 3.3
0.05 0.6 0.6 1.3 0.2 0.5 0.6 0.9 1.3
0.20 0.7 0.2 004 0.1 0.2 0.2 0.3 004
0.038 :<;; 0.5 0.01 004 1.0 2.0 004 0.8 1.0 1.5 2.0
0.05 0.5 0.7 lA 0.3 0.5 0.7 1.0 lA
0.20 0.6 004 0.9 0.2 0.3 004 0.7 0.9
1.0 0.01 004 0.8 1.5 0.3 0.6 0.8 1.1 1.5
0.05 0.5 0.5 1.0 0.2 004 0.5 0.7 1.0
0.20 0.6 0.3 0.6 0.1 0.2 0.3 004 0.6
:;:::: 2.0 0.01 004 0.6 1.2 0.2 004 0.6 0.9 1.2
0.05 0.5 004 0.7 0.1 0.3 004 0.5 0.7
0.20 0.6 0.2 004 0.1 0.1 0.2 0.3 004
0.075 :<;; 0.5 0.01 0.3 0.6 1.2 0.2 0.5 0.6 0.9 1.2
0.05 004 0.5 1.0 0.2 004 0.5 0.8 1.0
0.20 0.5 004 0.8 0.1 0.3 0.4 0.6 0.8
1.0 0.01 0.3 0.4 0.9 0.2 0.3 0.4 0.7 0.9
0.05 0.4 004 0.7 0.1 0.3 004 0.5 0.7
0.20 0.5 0.2 0.5 0.1 0.2 0.2 004 0.5
:;:::: 2.0 0.01 0.3 0.3 0.7 0.1 0.2 0.3 0.5 0.7
0.05 0.4 0.3 0.5 0.1 0.2 0.3 004 0.5
0.20 0.5 0.2 0.3 0.1 0.1 0.2 0.2 0.3
AH Cases2 AH Cases 2 Al! Cases 2 004 0.75 2.0 004 0.6 0.75 0.75 1.5
217
SEISMIC REHABILlTATlON OF EXISTlNG BUlLDlNGS
218
ASeE/SEI 41-06
C7.4.l.3.l Boundary Restraíntsfor lnfill Panels Intill r in! diagonallength of intill panel (in.);
panels not in tight COnlact with perimeter frame mem 'in! thickness of in1'ill panel and equivalenl
!lers should be restrained for oUI-of-plane forces. This strut (in.);
may be accomplished by installing sleel angles or (J = angle whose tangent is the inlill heighl-to
plales on each side of the infills, and welding or length aspect ralio (radians); and
bolting the angles or plates to the perimeter trame Al = coefficient used to determine equivalenl width
members. of intill Sl.rut.
For noncomposite infill panels, only the wythes in
C7.4.l.3.2 Joints Around lnfill Panels Gaps between full contact with lhe rrame elements shall be consid
an ¡ntill panel and the surrounding frame may be tilled ered where computing in-plane stiffness unless posi
ir integral ¡ntill-frame action is assumed for in-plane tive anchorage capable of transmitting in-plane forces
response. trom frame members lo all masonry wythes is pro
vided on aH sides of the walls.
7.4.2 Masonry Infills In-Plane Stiffness of cracked unreinforced masonry infill
The ca\culalion of masonry infiH in-plane stiffness panels shall be represented with equivalent struts; Ihe
and slrength based on nonIinear tinile eIement analysis strut properlies shall be determined trom analyses lha!
of a composite frame substruclure with intiII panel s consider the nonlinear behavior 01' lhe infilled frame
thal account for lhe presence of openings and post system al'ter the masonry is cracked.
yield cracking of masonry shall be permitted. The equivalenl compression strul analogy shall be
Alternatively, the methods of SeclÍons 7.4.2.1 and used lo represent Ihe elaslic stiffness of a perforated
7.4.2.2 shall be used. unreinforced masonry intill panel; Ihe equivalenl strul
properties shall be determined from stress analyses of
C7.4.2 Masonry Infills In-Plane íntill walls wilh represenlative opening patterns.
Finite element programs such as FEM/l may be Stiffnesses for existing and new infills shall be
useful in analyzing masonry intills with openings. assumed lo be Ihe same.
219
SElSMIC REHABILlTATION OF EXISTING BUILDlNGS
--II!o>
~I~
FIGURE C7-2. Compression Strut Analogy
Concentric Struts.
~:~
represented. To account 1'or these effecls, compression
struts may be placed eccentrically within the frames as
shown in Fig. C7-3. If the analytical models incorpo
rate eccenlrically localed compression struts, the
results should yield intilI etlects on columns direclly.
--II!o>
Alternalively, global analyses may be per1'ormed
~~
using concenlric-braced 1'rame models, and the ¡nfill
effects on columns (or beams) may be evaluated al a
locallevel by applying [he strut loads onto [he
columns (or beams).
Diagonally concentric equivalent struts may also
be used lo incorporale ¡ntill panel stiffnesses into ana
Iytical models for perforated intilI panels (e.g., intllls
with window openings), provided that the equivalent
stiffness 01' [he inl1n is determined using appropriate
FIGURE C7-4. Compression Strut Analogy
Perforated Infllls.
analysis methods (e.g., tinite element analysis) in a
consistent fashion with lhe global analytical model.
Analysis of local effects, however, muSl consider vari
ous possible stress tields that can potentially develop able guidelines; the use of this approach requires judg
within the intill. A possible representation of these ment on a case-by-case basis.
stress fields with multiple compression struts, as
shown in Fig. C7-4, have been proposed by 7.4.2.2 Slrenglh
Hamburger (1993). Theoretical work and experimental The transfer of story shear across a masonry infill
data for determining multiple strut placement and strul panel confined within a concrete or steel trame shaIl
properties, however, are not sufficient 10 establish reli- be considered a deformation-controlled action.
220
ASCE/SEI41-06
ExpectOO in-plane panel shear strength shall be deter The reduced column length, CjJ' in Eq. 7-9 shall
mined in accordance wíth the requirements of this be equal to the cIear height of opening for a captive
section. column bracOO laterally with a partial height infill.
Expected infill shear strength, Vioe' shall be caleu The requirements of this section shall be waived
lated in accordance with Eq. 7-8: il' the lower-bound masonry shear strength, VmU as
measured in accordance with test procOOures ol'
(Eq.7-8) Section 7.2.2.6, is less than 20 psi.
where
7.4.2.3.2 Required Strength o/ Ream Members
Aoí area of net mOrLared/grouted section across intill
Adjacent 10 Jnfill Panels The expected flexural and
panel; and
shear strengths ol' beam members adjacent to an inlill
j;'i< = expectOO shear strength of masonry infill.
panel shall exceed forces resulting l'rom one of the t'ol
lowing conditions:
Expected shear slrenglh of existing intills,f"ie'
shall not exceed lhe expectOO masonry bed-joinl shear l. The application of the vertical component of the
strenglh, Vme' as determined in accordance with expectOO infill strut force at a distance, l¡,eff, from
Section 7.2.2.6. the top oc bottom ol' the infill panel, where l/Jeff shall
Shear strength 01' new intill panels,f.'ie' shall not be as definOO by Eq. 7-11:
exceOO values specified in an approvOO building code
for zero vertical compressive stress. l=_a_ (Eq.7-11)
/Je{/ sin Ob
For noncomposíte intill panels, only lhe wythes in
l'ull contact with the l'rame elemenls shall be consid where tan Ob shall be as detined by Eq. 7-12:
erOO where computing in-plane strength, unless posi
tive anchorage capable 01' transmitting in-plane t'orces (Eq.7-12)
1'rom l'rame members to all masonry wythes is pro a
L in! - . O
vided on all sides ol' the walls. sm b
221
SEISMIC REHABILlTATION OF EXISTING BUILOINGS
Table 7-8. Linear Static Procedure-m-Factors for Acceplable deformations for exisling and new
Masonry In611 Panels l intills shall be assumed lo be lhe same.
exceed lhe values given in Table 7-9. The variable d, 7.4.3 Masonry Infills Out-of-Plane
represenling nonlinear deformalion capacities, shall be Unreinforced intill panel s wilh hi,,;ltill! ralios less
expressed in lerms of slory drí1'l ralio in percenl as lhan Ihose given in Table 7-10, and meeting lhe require
detined in Fig. 7-1. menls 1'or arching action given in Ihe following section,
For determination 01' acceplable drift levels using need not be analyzed 1'or out-of-plane seismic forces.
Table 7-9, lhe ratio 01' frame 10 intill slrenglhs, b, shall
be delermined considering lhe expecled laleral 7.4.3.1 Stifflless
slrenglh nf each component. InfiJl panels shall be considered local elemenLs
For lhe NDP given in Seclion 3.3.4, intill panel s spanning oUI-of-plane verlically belween tloor levcls
shall meet the requirements of Section 3.4.3.2. or horizontally across bays 01' frames.
Nonlincar force-detleclion relalions for intill panels The oUI-of-plane sLitfncss 01' intill panels shall be
shal1 be established based on lhe information given in neglecled in analytÍcal models 01' lhe global slruclural
Table 7-9 or an approved procedure based on a com syslem in lhe orLhogonal direclion.
prehensive evalualion 01' lhe hyslerelic characlerislics Flexural stiffness for uncracked masonry infills
of [hose componenls. subjecled LO transverse forces shall be based on lhe
Acceptance Criteria2
222
ASCFlSEI 41-06
mínimum nel sections of morlared and grouted 3. The frame componenls have sufticienl strength lo
masonry. Flexural stitlness for unreintorced, cracked resisl Ihrusts trom arching of an intill panel; and
infills subjecled 10 Iransverse forces shall be assumed 4. The hin¡/tinf ratio is less than or equal lo 25.
lo be equal lO zero unless arching action is considered.
Ir arching aclion is considered, mid-heighl deflec
Arching aClion shall be considered only if all of
lion nonual lo Ihe plane of an infill panel, !línf' divided
the following conditions exist.
by the infill heighl, hinf , shall be determined in accor
dance with Eq. 7-13:
1. The panel is in fuI! contact with the surrounding
frame components;
2. The product of the elastic modulus, Efe' times the ~_
O.OO2(~)
t mL (Eq.7-13)
moment of inertia, JI' of Ihe most flexible trame
component exceeds a value of 3.6 X 109 Ib-in. 2; h
inf
1+ V1 I _ O.OO2(~)2
t in!
223
SEISMIC REHABILITATION OF EXISTING BUILDINGS
Table 7-10. Maximum hin!ltin! Ratios 1 If the NDP is used, Ihe following performance cri
tería shall be based on the maximum oUI-of-plane
Moderate detlection normal lo the plane 01' the wall:
Low Seismic Seismic High Seismic 1. For the Immediate Occupancy Structural
Zone Zone Zone
Performance Level, the out-of-plane story drift
10 14 13 8 ratio of a panel shalJ be equal to or less than 2%;
LS 15 14 9 2. For the Lite Safety Structural Performance Level,
CP 16 15 10 the out-of-plane story drift ratio of a panel shall be
equal to or less ¡han 3%; and
'Out-of-plane anulysis shall nOl be required ror infills with h ú,¡/ t"!r
ratios less than lhe values Iisred herein. 3. For the Collapse PrevenlÍon Structural Performance
Level, the out-of-plane story drift ratio of a panel
shall be equal to 01' less than 5%.
For infill panel s not meeting the requiremenls for lf the surrounding frame is shown to remain stable
arching action, deflections shall be determined in following the loss of an intill panel, infill panels shall
accordance with Ihe procedures given in SecLÍons 7.3.3 not be subject to Iimits for the Collapse Prevention
or 7.3.5. Structural Performance Level.
Stiffnesses for existing and new infills shall be Acceptable deformations 01' existing and new
assumed to be the same. walls shall be assumed to be Ihe same.
7.4.3.2 Strength
Where arching action is not considered, the lower C7.4.3.3 Acceptance Critería
bound strength of a URM intill panels shall be limíled The Immediate Occupancy Structural
by the lower-bound masonry tlexural tension strength, Performance Level is assumed lo be reached when sig
/:" which shall be taken as 0.7 times the expecled len niticanl visual cracking 01' an unreinforced masonry
sile slrength,/,., as determined in accordance with infill occurs. The Lite Safcty Struclural Performance
Section 7.2.2.5. Level is assumed lo be reached when subslanlial dam
If arching action is considered, Ihe lower-bound age of the URM infilI occurs and Ihe potential is high
out-of-plane strength of an intill panel in Ib/1V, qin> for the panel, or sorne portion 01' il, to drop out 01' the
shall be determined using Eq. 7-14: 1'rame.
224
ASeE/SEl 41-06
ing codeo Shear strenglh of anchors with edge dis C7.6.3 Rehabilitation Measures
tances equal to or les s than l in. shall be taken as zero. Possible rehabilitation methods inelude:
l. Injection grouting of stone foundations;
C7.5.2 Analysis of Anchors 2. Reinforcing of URM foundations;
Anchors in masonry may be analyzed in accor 3. Prestressing of masonry foundations;
dance with FEMA 450 (FEMA 2004). 4. Enlargement of footings by placement of reinforced
shotcrete; and
5. Enlargement of footings with additional reinforced
7.6 MASONRY FOUNDATION ELEMENTS concrete sections.
7.6.1 Types of Masonry Foundations Procedures for rehabilitation should follow provi
Masonry foundations shall be rehabilítated in sions for enhancement of masonry walls where appli
accordance with this seclion. cable, according to Section 7.3.1.3.
225
SEISMIC REHABILlTATION OF EXlSTING BUILDINGS
conneclions between Ihe various componenls and ele future behavior of wood components in Ihe building
menls, see Section 8.2.2.2.2. Properties 01' shear walls system.
are described in Seclion 8.4, along with various reha Quantification 01' in-place material properlies and
bilitation or strengthening methods. Horizontal tlaor verification 01' existing system configuration and con
and roof diaphragms are discussed in Seclion 8.5, dition are necessary lo properly analyze lhe building.
which also covers engineering properties and methods The focus of lhis erforl shall be given lo the primary
of upgrading or strengthening the elements. Wood components of vertical- and laleral-force-resisling sys
foundations and pole struclures are addressed in lems. Thesc primary eomponents may be identified
Section 8.6. For addilional informalion regarding Ihrough initia) analysis and application 01' loads lo the
foundations, see Chapter 4. building model.
The extent 01' in-place materials tesling and eondi
tion assessment thal mus! be accomplished is reJated
8.2 MATERIAL PROPERTIES AND CONDITION to availability and accuracy ol' construclion documents
ASSESSMENT and as-built records, the quality of malerials used and
construction performed, and physical condilion. A spe
8.2.1 General cHie problem wilh wood construction is that structural
Mechanical properties for wood and light metal wood components are orten covered with other com
framing materials, components, and assemblies shall ponents, malerials, or linishes; in addition, Ihcir
be based on available conslruction documents and as behavior is influenced by past loading history.
built conditions fOI" the panicular structure. Where Knowledge of lhe propenies and grades of malerial
such information fails lO provide adequate information used in original component/conneclion fabrication is
10 quantify material propenies, capacities of assem invaluable, and may be effectively used lo reduce the
blies, or condition of Ihe structure, such information amounl ol' in-place lesting required. The design pro
shall be supplemenled by materials tests, mock-up fessional is encouraged 10 research and acquire all
tests of assemblies, and assessments of existing condi available record s l'rom the original construClion,
tions as required in Section 2.2.6. including design calculations.
Material properties 01' existing wood and light Connection eonfiguration also has a very impor
melal framing componenls and assemblies shall be lant influence on response lo applied load s and
determined in accordance with Section 8.2.2. A condi mOlions. A large number ol' connector types exist, the
tion assessmenl shall be conducted in accordance with mosl prevalent being nails and through bolts.
Seclion 8.2.3. The extent of malerials testing and con However, more recent conSlrUClion has included metal
dition assessment performed shall be used to deter straps and hangers, clip angles, and truss plates. An
mine the knowledge factor, K, as speeitied in underslanding of conneclor contiguration and mechan
Section 8.2.4. ical properties must be gained to properly analyze the
Use of defauil material properties shall be permit anlicipaled performance of Ihe building.
ted in aecordance with Section 8.2.2.5. Use of material Wood l'rame conslruclion has evolved over Ihe
properties based on historieal information for use as years; wood is the primary building malerial of most
default values shalI be as specitled in Section 8.2.2.5. residential and small commercial slruclures in the
Olher approved values of material properties shall be United States. It has often been used for Ihe framing
permitted ir based on available historical information 01' roors and tloors, and in combination with other
for a panicular type 01' wood frame construction, pre materials.
vailing codes, and assessment 01' existing eondilion. ESlablishing the age and recognizing Ihe localion
of a building can be helpful in dClermining what types
C8.2.1 General of lateral-I'orce-resisting systems may be present.
Various grades and speeies of wood have been As indicated in Chapter 1, greal care should be
used in a cut dimension form, eombined with other exercised in selecting the appropriate rehabilitalion
structural material s (e.g., steel/wood components), or approaches and techniques for application lo
in multiple layers of eonstruction (e.g., glue-Iaminated historie buildings in order lo preserve thdr unique
wood eomponents). Wood malerials have also been characteristics.
manufactured into hardboard, plywood, and particle Based on the approximale age 01' a building, vari
board products, which may have structural or non ous assumptions can be made about the design and
structural functions in construction. The condition of features 01' construction. Older wood frame slructures
the in-place wood materials will greatly influence the that predate building codes and standards usually do
ASeE/SEI 4'·06
nol have the types of elemenls considered essential for framing. This occurs on both balloon-framed and
prediclable seismic performance. These e1ements will plalform-framed buildings. There may be an exlra
generally have lo be added, or the existing elemenlS demand on these cripple walls because most interior
upgraded by the addilion of lateral-Ioad-resisting com partition walls do not continue to lhe foundation.
ponents to the existing slruclure in order lo obtain pre Special attention is required in these situations.
diclable performance. Adequale bracing musl be provided for cripple walls as
If lhe age of a building is known, lhe code in well as the allachmenl of the síll plate lo Ihe foundation.
effect al lhe time of conslruction and Ihe general qual In more recen! times, Iight gage melal studs and
ily of Ihe conslruclion usual for lhe lime can be help joists have been used in Iieu of wood framing for some
fui in evaluating an exislÍng building. The level of structures. Lateral·load resistance is either provided by
maintenance of a building may be a useful guide in melal straps auached lo the studs and 10p and bouom
determining the structure's capacity to resist loads. Iracks, or by slruclural panels auached with sheet
Users should be aware thal material slrenglhs pre metal screws 10 the studs and the top and bouom track
senled in hislorical information are typically in allow in a manner similar 10 that of wood conslruction. The
able stress formal. Users should convert allowable metal studs and joisls vary in size, gage, and configu
stress values 10 expected slrength values in accordance ralion, depending on the manufacturer and the loading
with ASTM D-5457 (ASTM 1998). conditions.
The earliest wood rrame buildings in the UniLed Por systerns using structural panels for bmcing,
States were buill wíth post and beam or feame con see Section 8.4 for analysis and acceptance criteria.
struclion adopted from Europe and the British Isles. Por the all-metal syslerns using steel strap braces, see
This was followed by the development of balloon Chapter 5 for guidance.
framing in about 1830 in Ihe Midwest, which spread
lo the East Coast by (he 1860s. This, in turn, was 1'01 8.2.2 Properties oC In-Place Materials and
lowed by lhe development of weslern or platform Components
framing shorlly after the turn 01' the century. Platform
framing is lhe system currently in use for multistory 8.2.2.1 Material Properties
conslruction.
Drywall or wallboard was tirsl introduced in 8.2.2.1.1 General The species and grade 01' wood shall
about 1920; however, ils use was nol widespread until be eSlablished by one of the following methods:
afler World War I1, when gypsum lath (bunon board)
l. Construction documents shall be revíewed;
also carne into eXlensive use as a rcplacement for
2. An inspection shall be conducted to identify grade
wood lalh.
by viewing grade stamps or comparing grading
Wilh lhe exception of public schools in high seis
rules; or
mic areas, modern wood feame slruclures detailed lo
3. Samples shall be examined by an experienced
resist seismic Joads were generally nol buill prior lo
wood pathologist lo establish the species.
1934. Por most wood frame struclUres, eilher general
seismic provisions were not provided or Ihe codes that Where materials tesling Is required by Section
included them were nol enforced unlillhe mid-1950s 2.2.6, grading shall be performed using the ASTM
or laler, even in Ihe mosl active seismic areas. This D245-oo (ASTM 2000) gmding methodology or an
time trame varies somewhal depending on local condi approved grading handbook for the assumed wood
lions and praclice. specíes and applicalion. Samples shall be laken from
Buíldings conslructed afler 1970 in high seismic regions where lhe calculaled stress due lo applied loads
areas usually inc1uded a well-defined lateral-force are less than the capacíty of the member with the sample
resisting system as a part of Ihe designo However, sile removed and tesled in accordance wilh SeclÍon 8.2.2.3.
inspet:tions and code enforcement varied greatly. Thus, Use of default properties for wood and Iight melal
the inclusion of various features and details on the frame shear walls, wood diaphragms, components, and
plans does nol necessarily mean thalthey are in place conneclors shall be permitted in accordance with
or fully effective. Veriticalion is needed lo ensure lhat Section 8.2.2.5. Por materials comprising individual
good conslruction practices were followed. components, Ihe use of default properties shall be per
Until aboul 1950, wood residenlial buildings were mitted where the species and grade 01' wood have been
frequently constructed on eaised foundations and in delermined. Use 01' default properlies for connectors
some cases included a short slud wall, called a "crip shall be permitted where lhe species of Ihe connected
pie wall," belween the foundation and lhe tirsl noor members has been determined.
227
SEISMIC REHABlLlTATION OF EXISTING BUILDlNGS
8.2.2.1.2 Nominal or Specífied Properties Use 01' notching, holes, splits, and cracks. The presence oí"
nominal material properties or properties specitied in decay or deformation should be nOled.
construction documents to compute expccted and These primary component properties are needed
lower-bound material properties shall be permitted in to properly characterize building performance in the
accordance with Section 8.2.2.5. seismic analysis. The starting poinl 1'or establishing
componenl properties should be the avaílable con
C8.2.2.J.2 Nominal orSpecífied Properties Actions slruclion documents. Preliminary review 01' these
associated with wood and light metal framing compo documents shall be pcrformed to identify verlical
nents generally are de1"ormalion-controlled; thus, (gravity-) and laleral-force-rcsisting elemenlS and sys
cxpected strenglh material properties will be used tems, and their critical components and conneclions.
most often. Lower-bound values will be used with Site inspcclions should be conducted to verify condi
components supporting discontinuous shear walls, tions and lO assure that remodelíng has not changed
bodíes 01' conneclions, and axial compression of indi the original design concept. In Ihe abscncc of a com
vidualtimber frame components, which are force plete sel 01" building drawings, the design professional
controlled. Malerial properties listed in this chapter must thoroughly inspect lhe building to identify these
are expected strength values. If lower-bound material elements, systems, and components as indicated in
propertíes are needed, they should be taken as mean Seclion 8.2.3. Where reJiable record drawings do nol
minus one standard deviation vaJues, or adjusted from exist, an as-buílt set of plans ror lhe building must
expected strength values in accordance with be crealed.
Section 8.2.2.5.
8.2.2.2.2 COllllections Details 01' lhe folIowing connec
,.
=: 8.2.2.2 Compollelll Properties tions shall be determined or veritied in accordance
with Section 8.2.3:
8.2.2.2.1 Elements The following component proper
l. Connections between horizontal diaphragms and
lies shall be determined in accordance wilh
vertical clemenlS of the scismic-1'orce-resisting
Section 8.2.3:
systcm;
l. Cross-sectional shapc and physical dimensions of 2. Size and charaCler of all diaphragm lies, including
the primary componenls and overall contiguration splice connections;
of the structure, including any modifications subse 3. Connections at splices in chord mcmbers 01" hori
quent to original constructÍon; zontal diaphragms;
2. Conliguration of elements, size and thickness 01' 4. Connections 01" horizontal diaphragms lo exterior or
connccted materials, lumber grade, nail size and interior concrete or masonry walls ror both in-plane
spacing, connections, and contínuity of load path; and out-of-plane loads;
3. Location and dimension of seismic-force-resistíng 5. Connections 01' eross-tie membcrs for concrete oc
elcmenls, type, materials, and spacing of tie-downs masonry buildings;
and boundary components; and 6. Connections of shear walls to foundations rOl' trans
4. Current physical condilÍon of components and fer of shear and overlurning forces; and
extent of any dcterioration present. 7. Method of lhrough-tloor transfer of wall shear and
overlurning forces in multistory buildings.
C8. 2. 2. 2. 1 Elements Structural elements of the lateral
force-resisting system are composed of primary and C8.2.2.2.2 Connections The melhod 01' con neclÍ ng the
secondary components, which colleclively define ele various components of the struclural system is critical
ment strength and resistance to deformation. Behavior lo its performance. The type and character 01' the con
01' the components-including shear walls, beams, nections must be determined by a rcvicw 01' the plans
diaphragms, columns, and braces-is dictated by and a field veriticalion of the condilions.
physical properlies such as area; malerial grade; thick
ness, depth, and slenderness ralios; lateral torsional 8.2.2.3 Test MetllOds lo Quantify Material Properties
buckling resistance; and conneclion details. The stitTness and strenglh 01' wood and Jight metal
The actual physical dimensions should be meas framing eomponents and assemblies shall be estab
ured; for example, 2-in. X 4-in. stud dimensions are lished lhrough in situ tcsLing or mock-up tcsLing of
generally 1~ in. X 3~ in. Connected members inelude assemblies in accordanee with Section 2.8, unless
plywood, bracing, slitl"eners, chords, sills, slruts, and defalllt values are used in accordancc with Sec
lie-down posts. Modilications to members inelude lion 8.2.2.5. The nllmber of tests requíred shall be
228
ASCE/SEI41-06
based on Section 8.2.2.4. Expected material properties every 100,000 sf of floor area, shalI be randomly
shalI be based on mean values of tests. Lower-bound veritíed by observation for compliance with the
material properties shall be based on mean values of design drawings; and
tests minus one standard deviation. 2. If design drawings are incomplete or not available,
at least lwo locations for each story, or 100,000 sf
C8.2.2.3 Test Methods /0 Quantify Material of tloor area, shalJ be randomly verified by obser
Properties vation or O[herwise documented.
To obtain the desired in-place mechanical proper
ties of material s and components, including expected 8.2.2.4.2 Comprehensive Testing The minimum num
strength, it is often necessary to use proven destructive ber 01' tests necessary to quanti1'y expected strength
and nondestructive testing methods. properties 1'or comprehensive data collection shall be
01' greatest interest to wood building system per defined in accordance with the following requirements:
formance are the expected orthotropic strengths 01' the
1. If original construction documents exist that define
installed material s for anticipated actions (e.g., flex
the grade of wood and mechanical properties, at
ure). Past research and accumulation of data by indus
least one location for each story shall be randomly
try groups have led to published mechanical properties
verified by observing grade stamps, or by compli
for most wood types and sizes (e.g., dimensional
ance with grading rules for each component type
solíd-sawn lumber, and glue-laminated or "glulam"
identified as having a different material grade;
beams). Section 8.2.2.5 addresses these established
2. If original construction documents defining proper
defauIt strengths and distortion properties. This infor
ties are nol complete or do not exisl but lhe date of
mation may be used, together with tests from recov
construction is known and single material use is
ered samples or observation, to establish the expected
confirmed, at leasl three locations shall be ran
properties for use in component strength and deforma
domly verified-by sampling and testing or by
tion analyses. Where possible, the load history for the
observing grade stamps and condilions-for each
building shall be assessed for possible influence on
component type, 1'or every two tloors in !he building;
component strength and deformatíon properties.
3. If no knowledge 01' the struclural system and mate
To quantify material properties and analyze the
rials USed exists, al least six locations shall be ran
performance of archaic wood construction, shear
domly verified-by sampling and lesting or by
walls, and diaphragm action, more extensive sampling
observing grade stamps and conditions-for each
and testing may be necessary. This testing should
element and componen! type, 1'or every two floors
inelude further evaluation of load history and moisture
or 200,000 sf of floor area 01' construction. If il is
effecls on properties, and an examination of wall and
determíned 1'rom testíng or observation Ihal more
diaphragm continuity, and the suitability of in-place
than one material grade exists, additional observa
connectors.
lions and testing shall be conducled until the extent
Where it is desired to use an existing assembly
of use 1'or each grade in component 1'abrication has
and liule or no information about its performance is
been established;
available, a cyclic load test of a mock-up of the exist
4. In the absence 01' construction records defining
ing structural elements can be used to determine the
connector 1'eatures present, Ihe configuration of at
performance 01' various assemblies, connections, and
least three connectoes shall be documented for
load transfer conditions. See Section 2.8 foe an expla
every floor or 100,000 s1' of tloor area in the build
nadon 01' the backbone curve and the establishment of
ing; and
alternative modeling parameters.
5. A full-scale mock-up test shalI be conducted 1'or
archaic assemblies; at least two cycIic tests 01' each
8.2.2.4 Minimum Number 01 Tests
assembly shall be conducted. A third test shaU be
conducted if the results 01' the two tesIs vary by
8.2.2.4.1 Usual Testing The mínimum number 01' tests
more Ihan 20%.
to quantify expected strength material properties tor
usual data collection shall be based on the following
C8.2.2.4 Mínimum Number 01 Tests
criteria:
In order to quantify expected strength and other
l. If design drawings containing material property and in-place properties accurately, a minimum number of
detailing information for the seismic-force-resisting tests must be conducled on representatíve components.
system are available, at least one elemenl of the The mínimum number 01' tests is dictated by available
seismic-force-resisting system for each story, or for data from original construction, the type of struclural
229
SEISMIC REHABILITATION OF EXISTING BUILDlNGS
system employed, desired accuracy, and quality/condi Default expected strength values for wood materí
tion 01' in-place materials. Visual access to the struc als comprísing individual components shall be based
tural system also influences testing program definition. on design resistance values associated with the
As an ahernative, the design professional may elect to AF&PAlASCE 16 Standardfor Load and Resistance
use the default strength propenies in accordance with Factor Design (LRFD)for Engineered Wood
Seclion 8.2.2.5. However, using defaulL values without Construction (ASCE 1996) as determined in accor
testing is only permitted with the linear analysis proce daoce with ASTM D5457-93 (ASTM 1998). AII
dures. It is strongly encouraged that the expected adjustmeot factors, ioeluding the time-etfect factor,
strengths be derived through testing of assemblies in that are applicable io accordaoce with ASCE 16 shall
order to model behavior accurately. be considered. The resistance faclOr, 4>, shalJ be taken
Removal of coverings, ineluding stucco, fireproof as unity. If components are damaged, reductions in
ing, and partition malerials, is generally required lO capacity aod stiffness shall be applied, considering lhe
facilitate sampling and observalions. position and size 01' the ineffective cross section.
Component types include solid-sawn lumber, glu Default expected strength values for connectors
lam beam, and plywood diaphragm. Element types shall be based 00 design resistance values associated
inelude [hose that are part of gravity- and lateral-load with ASCE 16 as determined in accordaoce with
resisting systems. The observations shall consist 01' ASTM D5457-93. AII adjustment factors, ineluding
each connector type present in the building (e.g., nails, the time-ef1'ect factor, that are applicable io accordance
•.. bolts, slraps), such lhat the composite strenglh of the with ASCE 16 shall be considered. The resislance fac
•...
E
connection can be estimated . tor, 4>, shall be taken as uoity.
Alternatively, expected strength values shall be
permiued to be directly computed from allowable
8.2.2.5 De/outt Properties
!) stress values Iisted in an approved code using the
Use of default properties to delermine component
method contained in ASTM D5457-93.
strengths shall be permitted in conjunction with the
Default deformations al yield of conneclors shall
linear analysis procedures of Chapter 3.
be taken as:
Default expected strength and stiffness values for
wood and light metal frame shear wall assemblies l. 0.03 in. for wood-to-wood and 0.02 in. for wood
shall be takeo from Table 8-1. Default expected to-metal oailed connectioos;
strength and stiffoess values for wood diaphragm 2. 0.04 io. for wood-to-wood and 0.03 in. for wood
assemblies shall be taken from Table 8-2 to-steel screw coonections;
Table 8-1. Default Expected Streugth Values for Wood aud Light Frame Shear Walls
Propelty
Shear Stiffness (Gd) Expected Strength (Qn)
Shear Wall Typel (lb/in.) (plt)
Single Layer Horizontal Lumber Shealhing or Siding 2.000 80
Single Layer Diagonal Lumber Shealhing 8,000 700
Double Layer Diagonal Lumber Sheathing 18.000 1,300
Vertical Wood Siding 1,000 70
Wood Siding over Horizontal Shealhing 4,000 500
Wood Siding over Diagonal Sheathing 11,000 1,100
Wood Struclural Panel Sheathing2
Stucco on Sluds, Sheathing, 01' Fiberboard 14,000 350
Gypsum PI aster on Wood Lath 8,000 400
Gypsum Plaster on Gypsum Lalh 10,000 80
Gypsum Wallboard 8,000 100
Gypsum Sheathing 8,000 lOO
PIaster on Metal Lath 12,000 150
Horizontal Lumber Sheathing wÍth Cut-in Braces 01' Diagonal Blocking 2,000 80
Fiberboard 01' Particleboard Sheathing 6,000 100
230
ASCE/SEI41-06
Property
3. 0.04 in. for wood-to-wood and 0.027 in. for wood assemblíes. The shear stiffness, G d, for the assemblies
to-steellag boh connections; and should not be confused with the modulus of rigidity,
4. 0.045 in. ror wood-to-wood and 0.03 in. for wood G, for wood structural panels.
lo-sleel bolted connections. The LRFD methodology ofASCE 16 (ASCE
1996) is based on the concepls of Jimil state design,
The estimated deformation of any hardware,
similar lo the provisions tor strength design in steel or
including allowance for poor tit or oversized holes,
concrete. The reference resistance values for wood ele
shalJ be summed lo obtain the total deformation of the
ments and connections associated with this standard
connection.
are contained in the LRFD Manualfor Engineered
Default expected strength values tor connection
Wood Construction, including supplements and guide
hardware shall be taken as the average ultimate test
lines (AF&PA LRFD 1996). The resistance values in
values from publíshed reports.
these documents were developed using AS1M D5457
Default lower-bound strength values, where
93 (ASTM 1998), which provides methodologies for
required in this chapter, shall be taken as expected
calculation directly from data or by format conversion
strength values multiplied by 0.85.
from approved alJowable stress values. Use of a format
C8.2.2.5 Default Properties conversion (Le., the LRFD equivaJent of aJlowable
The results of any material testing pertormed stresses) tor computing expected strengths of wood
should be compared to the default values for the par material s comprising individual wood components and
ticular era 01' building construction. If signiticantly tor wood connectors (nails, screws, lags, bolts, split
reduced properties from testing are discovered, further rings, and so forth) is permitted. This methodology is
evaluation should be undertaken. nol applicable for wood shear waU and diaphragm
Tables 8-1 and 8-2 contain default values for assembJies covered in Tables 8-1 and 8-2. For use with
strength and stiffness of shear waJl and diaphragm this chapter, capacities tor shear wall and diaphragm
231
SEISMIC REHABlLITATION OF EXISTING BUILDlNGS
assemblies are to be taken directly from the tables or 8.2.3 Condition Assessment
as indicated by the table footnotes.
The LRFO reference resistance is computed as the 8.2.3.1 General
al\owable stress value multiplied by a format conver A condition assessmenl 01' lhe existing building
sion factor. The format convcrsion factor is detined as and site shall be performed as specitied in lhis section.
K E; = 2.16/ cp, where cp is the specítied LRFO resist A condition assessment shall include the
ance factor: 0.90 for compression, 0.85 for nexure, following:
0.80 for tcnsion, 0.75 for shcarltorsion, and 0.65 for
1. The physical condition of primary and secondary
connections. The allowablc strcss value shall inelude
components shall be examincd and the prescnce of
all applicable adjustment factors, except for the load
degradation shall be noted.
duration factor. If allowable values already inelude
2. The presence and contiguration of components and
consideration of duration effects, the load duration
lheir conncclions, and the continuity of load paths
adjustment factor must be divided out prior 10 format
between components, elements, and systems shall
conversion. Note that the time-effect factor specitíed
be veritied or established.
for LRFO is 1.0 ror load combinations that ¡nelude
3. Other conditions, ineluding neighboring party walls
earthquake loads.
and buildings, presence 01' nonstructural compo
The NEHRP Recommended Provisionsfor
nents, prior remodeling, and Iimitations 1'or
Seismic Regulations for New Buildings and Other
rehabilitation that may intluence building perform
Structures (BSSC 2000) conlain strength-based resist
ance, shall be reviewed and documenled.
ance values for wood structural panel shear walls and
diaphragms. AlIowable stress values ror wood compo
nents and connections can be found in the National C8.2.3.1 General
Design Specificationfor Wood Cotlstruction (AF&PA The physical condition of existing componenls
NOS 1997) and the ASD Manual for Engineered Wood and elements and their connections must be examined
Construction, including supplements and guide\ines 1'or degradation. Oegradation may inelude environmen
(AF&PA ASO 2001). tal e1'fects (e.g., decay, splitting, tire damage, and bio
AF&PA LRFO contains a guideline for calculat logical, termite, and chemical attack) or pastlcurrent
ing resistance values for connection hardware for loading etlects (e.g., overload, damage from past
which published report values are in allowable stress earthquakes, crushing, and twisting). Natural wood
formal. Where computing thc cxpected strength 01' also has inherent discontinuities such as knots, checks,
connections, all limit statcs, ineluding that 01' the con and splits thai must be noted. Configuration problems
ncetion hardware, must be eonsidered (c.g., in addition observed in recent earthquakes, including ellects of
to the published strength 01' a tie-down device, con discontinuous components, improper nailing or bolt
sider the Iimit states for thc stud bolts, the anchor bolts ing, poor lit-up. and connection problems at the foun
in the foundation, and so forth). dation level, should also be evaluated. Ofien, unfin
The connector deformation at yield may be calcu ished areas such as attic spaces. basements, and crawl
lated by dividing the load by the load/slip modulus. spaces provide suitable access to wood components
The load/slip modulus for dowel type connections and can give a general indicatÍon 01" the condition of
(bolts, lag screws, screws, and nails) is calculated the rest 01' the structure. Invasive inspection of critical
as (180)(0)15 kip/in. for wood-to-wood connections components and connections is typically required.
and (270)(0)15 kip/in. for wood-lo-steel side plate Neighboring party walls and buildings, the presence of
conncctions. nonstructural components. prior remodeling, and limi
Actions associated with wood and líght metal lations for rehabilitation should also be noted.
framing components generaJly are de1'ormation Connections require special consideration and
controlled, and expected strength material properties evaluation. The load path for the system must be
will be used most often. Lower-bound values are determined and each connection in the load path(s)
needed for actions that are force-controlled. The 0.85 must be evaluated. This indudes diaphragm-to
factor included in this standard to convert expected component and component-to-component connections.
strength to lower-bound values is based on lhe resu1ts The strength and deformatÍon capacity of connections
of shear wall testing. If more precise lower-bound must be checked where the connection is attached to
material properties are desired, they should be taken as one or more components that are expected to experi
mean minus one standard deviation from test data ror ence significant inelastic response. Anchorage 01' exte
the components in question. rior walls to roof and tloors in concrete and masonry
232
ASCElSEI 41-06
buildings, for which wood diaphragms are used for inspected fiberscopicalIy. If common detailing is
out-of-plane loading, requires detailed inspection. Bolt observed, this sample shall be considered represen
holes in relatively narrow slraps somelimes preclude talive. If any details or condilions are observed that
lhe ductile behavior of the steel slrap. TwislS and kinks result in a discontinuous load path, all primary con
in lhe strap can also have a serious impacl on its anlici nections shall be exposed.
pated behavior. Cross lies, which are parl of lhe wall
anchorage syslem, need to be inspecled to confirm C8.2.3.2 Scope and Procedures
their presence, along with the conneclion of each Accessibility constraints may necessitate the use
piece, to ensure that a positive load path exists to tie of instruments such as a tiberscope or video probe lo
the building walls together. reduce the amount 01' damage to covering material s
The condition assessmenl also affords an opporm and fabrics. The knowledge and insight gained from
nily LO review other conditions thal may intluence the condilion assessment ís invaluable lo understand
wood elements and syslems and overall building ing load paths and the ability of components lo resist
performance. Of particular ímportance is the identifi and transfer loads. The degree of assessment per
calíon of olher elemenls and componenls Ihal may formed also atl'ects the knowledge factor discussed in
contribute lo or impair [he performance of the wood Section 8.2A.
syslem in question, including intills, neighboring Direct visual inspection provides the most val u
buildings, and equipment attachments. Limitarions able intormalion, as it can be used lO idemify any con
posed by exisling coverings, waJl and ceiling space tiguration issues, allows measurement of component
insulation, and other material shall also be defined such dimensions, and identifies the presence 01' degradation.
that prudent rehabilitation measures can be planned. The continuity of load paths may be established by
viewing components and connection condition. From
8.2.3.2 Scope and Procedures visual inspection, the need for other test methods to
AIl primary structural components 01' lhe gravily quantify the presence and degree of degradation may
and laleral-load-resislance syslem shall be included in be eSlablished.
lhe condilion assessment. The scope 01' the removal effort is dictated by the
componenI and element design. For example, in a
8.2.3.2.1 Visual Condition Assessment The dimensions braced frame, exposure of several key connections
and fealures 01' all accessible componenls shall be may suftice if the physical condition is acceptable and
measured and compared to available design informa the contiguration malches Ihe design drawíngs.
lion. Similarly, lhe contiguration and condition of alI However, for shear walls and diaphragms, it may be
accessible conneclions shall be visually verified, with necessary to expose more connection points because
any det{)rmations or anomalies noted. 01' varying designs and rhe crilical nature of Ihe con
nections. For encased walls and frames for which no
8.2.3.2.2 Comprehensive Condition Assessment If cov drawings exist, il is necessary lo indirectly view or
erings or other obstructions exist, either partial visual expose all primary end connections tor verificalÍon.
inspection through lhe use 01' drilIed holes and a tiber The physical conditíon of components and con
scope shall be used, or visual inspection shall be per nectors may also support the need to use certain
focmed by local removal of covering materials based destruclÍve and nondestructive test methods. Devices
Oll lhe following requirements: normally used for the detection of reinforcing steel in
l. If detailed design drawings exist, at leasllhree dif concrete or masonry may be used to verify the metal
ferent primary conneclions shall be exposed for straps and hardware located beneath tinish surfaces.
each conneclÍon type. Ir no capacíty-reduc:ing
8.2.3.3 Basis for the Mathematical Building Model
deviations from the drawings exist, the sample shall
The results of the condition assessment shall be
be considered representalÍve. If deviations are
used to quantify the lollowing items needed to create
noted, then all coverings from primary conneclions
(he mathematical building model:
01' that type shall be removed unless the connection
strength is ignored in the seismic evalualion; and J. Component section properties and dimensions;
2. In the absence of accurate drawings, at leasl 50% 2. Component configuration and eccentricities;
of the top and base connections tor each lype 01' 3. Interaction 01' nonstructural components and their
vertical element in the seismic-force-resisting sys involvement in lateral-load resístance; and
tem as wall as collectors, boundary components, 4. Presence and effects of aIterations to the structural
and tie-downs, shall be exposed and inspected oc system.
233
SEISMIC REHABILlTATION OF EXISTlNG BUILDlNGS
1+--- d ------+\-1
C8.2.3.3 Basis for the Mathematical Building Model
The acceptance criteria for existing components
1.0
B e
depend on the design professional's knowledge of the ¡
condition of the structural system and material proper ¡
¡
ties, as previously noted. Certain damage-such as
water staining, evidence of prior leakage, splitting, L\
cracking, checking, warping, and twisting-may be L1y
acceptable. The design professional must establish a FIGURE 8-1. Generalized Force-Deformation
case-by-case acceptance for such damage on the basis Relation for Wood Elements or Components.
of capacity loss or deformation constraints.
Degradation at connection points should be carefully assemblies. Distance d is considered the maximum
examined; significant capacity reductions may be deflection at the point 01' first loss 01' slrength.
involved, as well as a loss of ductility. Distance e is the maximum detlection at a strength or
capacity equal to value c. Where the yield strength is
8.2.4 Knowledge Factor not determined by testing in accordance with Section
A knowledge factor, K, for computation of wood 2.8, the yield strength at point B shall be taken as the
and light metal framing component capacities and per expected strength at point C divided by 1.5.
missible deformations shall be selected in accordance
with Section 2.2.6.4, with the following additional 8.3.2 Strength and Acceptance Criteria
requirements specific to wood components and
assemblies. 8.3.2.1 General
If a comprehensive condition assessment is per Actions in a structure shall be classified as being
formed in accordance with Section 8.2.3.2.2, a knowl either deformalion-controlled or force-controlled, as
edge factor K = 1.0 shall be permitted in conjunction defined in Section 2.4.4. Design strengths fór defor
with default properties of Section 8.2.2.5, and testing mation-controlled and force-controlled actions shall be
in accordance with Section 8.2.2.4 is not required. ca\culated in accordance with Sections 8.3.2.2 and
Sections 8.3.2.3, respectively.
234
ASeE/SEI41-06
expected strength, Qa" must be considered where link pieces of a connection assembly together, are con
evaluating expected performance. For example, while sidered to have the abilíty to deform in a ductile man
the m-factors for gypsum plaster are higher than those ner, provided the bodies of the connections or bodies
for wood structural panels, the stiffness assigned to of connectíon hardware do not prematurely fracture.
gypsum plaster is relatively high and the expected Much of lhe ductility in a wood shear walJ or
strength values are much lower than those for wood diaphragm assembly comes from the connectors, such
structural panels. As a result, worse performance for a as bending in the nails prior to point where nails pull
given displacement is predicted. lhrough the sheathing material. In boIted connections,
the connectors, including bolt bending or crushing of
8.3.2.3 Force-Controlled Actions .he wood around the boh hole are ductile sources of
Where determined by testing, lower-bound deformation in an assembly. BriHle failure can occur
strengths for force-controlled actions, QCL' shall be in the bodies of connections, such as net section frac
taken as mean minus one standard deviation of the ture or spliHing in an end post, or in the bodies of con
maximum strengths obtained experimentally. Where nection hardware such as tie-downs. For this reason,
calculated using established principIes of mechanics or connectors are considered deformation-controlled and
based on LRFD procedures contained in bodies of connectíons and bodies of connectíon hard
AF&PAlASCE 16 Standardfor Load and Resistance ware are considered force-controlled. Where determin
Factor Design (LRFD) for Engineered Wood ing the demand on force-conlrolled portions of lhe
Construction (ASCE 1996), the resistance factor, <P, connection assembly, use of a limit-state analysis to
shalJ be taken as unity, and default lower-bound mate determine the maximum force that can be delivered to
rial properties determined in accordance with Section the connection is recommended.
8.2.2.5 shall be used. Where computing the strength of connections, all
Where the force-controlled design actions, QUF' potential limil states should be considered. including
calculated in accordance with Section 3.4.2.1.2 are those associaled with the bodies of connections, the
based on a Iimit-state analysis, the expected strength bodies of connection hardware, and connectors with
of the components delivering load to the component which the assembly may be composed. For example,
under consideration shall be laken as nol less than 1.5 in addition to the strength of a tie-down device itself.
times lhe yield strength. limit states for the slud bolts, foundation bolts. and net
section of the end post should be considered. The con
C8.3.2.3 Force-Controlled Actions trolJing condition will determine the expected or
The maximum forces developed in yielding shear lower-bound strength of the connection.
walls and diaphragms are consistent1y 1.5 to 2 times
the yield force. Other wood components and connec
8.3.4 Rehabilitation Measures
tors exhibit similar overstrength.
Ir portions of a wood building struclure are defi
cient for the selecled Rehabilitation Objective. the
8.3.3 Connection Requirements
structure shall be rehabilitated, reinforced, or replaced.
Unless olherwise specified in this standard, con
If replacement of the element is selected or if new ele
nections between wood components of a lateral-force
ments are added, the new elements shall satisfy the
resisting system shall be considered in accordance
acceptance críteria of lhis standard and shall be
with this section. Demands on connectors, including
detailed and conslructed in accordance with a building
nails, screws, lags, bolts, split rings, and shear plales
code approved by the authority havíng jurisdíetion. If
used to link wood components 10 olher wood or metal
reinforcement of the existing framing system is
components shalI be considered deformation
selected. the following factors shall be considered:
controlled actions. Demands on bodies of conneclíons,
and bodies of connectíon hardware, shall be consid l. Degree of degradation in lhe component from such
ered force-conlrolled actions. mechanisms as biologícal attack, creep, high statíe
or dynamic loading, moisture, or other effects;
C8.3.3 Connection Requirements 2. Level of steady-state stress in the components to be
In considering connectíons belween wood compo reinforced and the potenlial lo temporarily remove
nents in this standard, conneclors are dislinguished this stress, if appropriate;
from bodies of conneclions and bodíes of connectíon 3. Elastíe and inelastic properties of existing compo
hardware. Connectors, which consist of the nails, nents; strain compatibility with any new reinforce
screws, lags, bolts, Splil rings, and shear plales used to ment materials shall be provided;
235
SElSMIC REHABILITATION OF EXISTING BUILDlNGS
4. Ductility, durability, and suitability of existing con For overturning calculations on shear wall ele
nectors between components, and access for rein ments, stabilily shall be evaluated in accordance with
forcement or modification; Section 3.2.10. Net tension due to overturning shall be
5. Efforts necessary to achieve appropriate fit-up for resisted by uplift conneetions.
reinforcing components and connections; The efTects of openings in wood shear walls shall
6. Load path and deformation of the components at be considered. Where required, reinforcement consist
end connections; and ing of chords and collectors shall be added to provide
7. Presence of components manufactured with archaic suflicient load capacity around openings to meet the
materials, which may conlain material discontinu strenglh requirements for shear walls.
ities, shall be examined during the rehabilitation Conneetions between shear walls and other com
design lO ensure that the selected reinforcement is ponents, including diaphragm ties, colleclors,.
feasible. diaphragms, posls, and toundations, shall be consid
ered in accordance wilh Section 8.3.3, and designed
C8.3.4 Rehabilitation Measures for forces calculated in accordance with Chapter 3.
Special aHention is required where connections Components supporting disconlinuous shear walls
such as bolts and nails are encountered. shall be considered in accordance wilh Section 8.3.5.
Wood structural panels are used to provide lateral The expected strenglh, QC¡¡' of wood and light
strength and sliffness lo most modern wood I'rame frame shear wall assemblies shaIl be determined in
buildings and are generalIy recommended for the reha accordance with Sections 8.4.4 lhrough 8.4.18.
bilitation of horizontal diaphragms and shear walls of
existing buildings. The system reHes on the in-plane C8.4.1 General
strength and stitrness of the panels and their connection The behavior 01' wood and light frame shear walls
lo the framing. Panels are connected together by nailing is complex and influenced by many l'ilctors, the primary
into the same structural member lo create, in effec!, one factor being lhe wall sheathing. Wall shealhings can be
continuous panel. The various panels are described in divided into many calegories (e.g., brillie, elaslic,
Sections 8.4 and 8.5. The performance of the structural strong, weak, good al dissipaling energy, poor al dissi
panels is dependent to a great degree on the nailing or paling energy). In many exisling buildings, the walls
attachment to the framing. The nail spacing and effec were nol expected lo aCl as shear walls (e.g., a wall
tiveness of lhe attachmenl should be investigated if the sheathed with wood lath and plaster). Most shear waIls
existing panel s are expected lO withstand significant are designed based on values from monotonic load
loads. lf nails are to be added lO exisling panels, they tests and historically accepted values. The allowable
should be the same size as the existing nails. shear per unit length used for design was assumed lo
be lhe same for long waJls, narrow walls, walls with
8.3.5 Components Supporting Discontinuous Shear stiU tie-downs, and walls with flexible tie-downs. Only
WaJls recently have shear wall assemblies-framing, cover
Axial compression on wood posts and tlexure and ing, and anchorage-been tesled using cyclic loading.
shear on wood beams that support discontinuous shear Another major factor influencing the behavior of
walls shall be considered force-controlled actions. shear walls is the aspect ratio 01' the wall. The NEHRP
Lower-bound strengths shall be determined in accor Recommended Provisions for Seismic Regulations for
dance with Section 8.3.2.3. New Buildings and Other Structures (BSSC 2000)
limit the aspecl ralio (height-to-widLh) for slructural
8.4 WOOD AND LIGHT FRAME SHEAR WALLS panel shear walls to 2: 1 for full design shear capacity
and permit reduced design shear capacities for walls
8.4.1 General with aspecl ratios up lO 3.5: l. The interaction 01" the
Wood and Iighl frame shear walls shall be catego tloor and roof wilh lhe wall, the end conditions of the
rized as primary or secondary components in accor wall, and lhe redundancy or number of walls along
dance with Section 2.4.4.2. any waJl line would atIeet lhe wall behavior for walls
Dissimilar wall sheathing malerials on opposite with the same aspect raLio. In addition, the rigidity of
sides of a wall shall be permiued to be combined the lÍe-downs at the wall ends has an ímportam eífecl
where there are test data to substantiate the stiffness in the behavior of narrow walls.
and strength properties of the combined systems. The presence of any but smaII openings in wood
Otherwise, walls sheathed with dissimilar materials shear walls will cause a reduetion in the stiflness and
shall be analyzed based on only the wall sheathing slrenglh due to a reduced length of wall availahle to
with the grealCst capacity. resisl lateral forces. Special analysis lechniques and
236
AseE/SEI 41-06
delailing are required at lhe openings. The presenee or 8.4.2./.3 Vertical Wood Siding Only Vertical wood
addilion of ehord members around the openings will siding shall inelude vertical boards naiJed directly to
reduce the loss in Oyeran stiffness and limil damage in studs and blocking 2 in. or greater in widlh.
the area 01' openings. See the NEHRP Recommended
Provisíons for Seísmíc Regulations for New Buildings C8.4.2.1.3 Vertical Wood Siding Only Typieally,
and Other Structures for reinforcement requirements I-in. X 8-in., l-in. X 10-in.,or l-in. X 12-in. vertical
around openings in wood shear walls. boards are nailed directly lo 2-in. X or grealer width
For wood and lighl ti'ame shear walls, lhe impor studs and blocking with 8d or IOd galvanized nails.
tant limil states are sheathing failure, conneetion fail The lateral forces are resisted by nail couples, sirni
ure, tie-down failure, and excessive detleelion. Limit lar1y lo horizontal siding.
states define the poinl of life safety and, often, of
struetural slabilily. To reduce damage or relain usabil 8.4.2.1.4 Wood Siding over Horizontal Sheathing
ity immedialely after an earlhquake, detlection must Wood siding over horizontal sheathing shall inelude
be limited (see Section 2.5). The ultimate eapacily is siding conneeted to horizontal sheathing with nails
!he maximum capacity of the assembly, regardless of that go through lhe sheathing lo the studs.
the detleetion.
C8.4.2.1.4 Wood Siding O\ler Horizontal Sheathing
Typically, siding is nailed wilh 8d or lOd galvanized
8.4.21)pes of Wood Frame Sbear Walls nails lhrough lhe shealhing (O the SLUds. Lateral t'orces
are resisled by naíl couples for both layers.
8.4.2.1 ExislÍlIg Wood Frame Shear WaUs
8.4.2.1.5 Wood Siding over Diagonal Sheathing Wood
8.4.2.1.1 Single-Layer Horizontal Lumber Sheathing siding over diagonal sheathing shall inelude siding
or Siding Single-layer horizontallumber sheathing or connected to diagonal sheathing with nails tha! go
siding shall inelude horizontal shealhing or siding through the sheathing to the studs.
applied direetly 10 studs or horizontal boards nailed to
studs 2 in. or greater in width. C8.4.2.1.5 Wood Siding over Diagonal Sheathing
Typically, siding is nailed Wilh 8d or IOd galvanized
C8.4.2.l.1 Single Layer Horizontal Lumber Sheathing nails to and lhrough !he sheathing inlo the studs.
or Siding TYpieally, l-in. X horizontal sheathing or Diagonal sheathing provides most of the lateral resist
siding is applied direetiy lo studs. Forces are resisted ance by triangulation (see Section 8.4.2.1.2).
by nail couples. Horizontal boards, from l-in. X 4-in.
lo 1-in. X 12-in., typically are nailed to 2-in. X or 8.4.2.1.6 Wood Structural Panel Sheathing or Siding
grealer width sluds with two or more nails (typically Wood strucLUral panel sheathing or siding shall ¡nelude
8d or IOd) per stud. wood structural panels, as detíned in Ihis standard, ori
ented vertically or horizontally and nailed lo sluds
8.4.2.1.2 Diagonal Lumber Sheathing Diagonallum 2 in. or greater in width.
ber sheathing shall inelude sheathing applied at
approximalely a 45-degree angle lo lhe sluds in a sin C8.4.2.1.6 Wood Structural Panel Sheathing or Siding
gle or double layer with lhree or more nails per stud, TYpically,4-ft X 8-ft panel s are applied vertically or
sill, and 10p plates. horizontally lo 2-in. X or greater sluds and nailed with
6d to IOd nails. These panels resis! lateral forees by
C8.4.2.1.2 Diagonal Lumber Sheathing Typically, panel diaphragm aetion.
l-in. X 6-in. lo ] -in. X 8-in. diagonal shealhing,
applied direetly to the sluds, resists lateral t'orces 8.4.2.1.7 Stucco on Studs Stucco on studs (over
primarily by triangulation (i.e., direet tension and sheathing or wire-backed building paper) shall include
compression). Sheathing boards are inslalled al a Porlland cemenl plaster applied tO wire lath or
45-degree angle lo sluds, with three or more nails expanded metal lath. Wire lath or expanded melal lalh
(typically 8d or IOd) per stud, and lo sill and top shall be nailed to !he studs.
plates. A second layer of diagonal sheathing is
sometimes added on 10p of the fírst layer, al 90 C8.4.2.1,? Stucco on Studs TYpicalIy, ~-inch Portland
degrees lo lhe firsl layer (called Double Diagonal cement plaster is applied lo wire lath or expanded
Sheathing), t'or increased load eapaeily and metal lath. Wire lath or expanded metallath is nailed
stiffness. lO the studs Wilh ll-gage nails or 16-gage staples at
237
SEISMIC REHABILlTATION OF EXISTING BUILDlNGS
6 in. on center. This assembly resists lateral force s by C8.4.2.1.12 Plaster on Metal Lath Typically, I-in.
panel diaphragm action. gypsum plaster is applied on expanded wire lath that is
nailcd to the studs. Lateral forces are resistcd by panel
8.4.2.1.8 Gypsum Plaster on Wood Lath Gypsum plas diaphragm action.
ter on wood lath shal1 include gypsum plaster keyed
onto spaced wood lath that is nailed to the studs. 8.4.2.1.13 Horizontal Lumber Sheathing with Cut-In
Braces or Diagonal Blocking Horizontallumber
C8.4.2.1.8 Gypsum Plaster on Wood Lath Typ.ically, sheathing with cut-in braces or diagonal blocking shall
I-in. gypsum plaster is keyed onto spaced I-i-in. include I-in. X horizontal sheathing or siding applied
wood lath that is nailed to studs with 13-gage nails. directly to studs or I-in. X 4-in. lo I-in. X l2-in. hori
Gypsum plaster on wood lath resists lateral forces by zontal boards nailed to studs 2 in. or greater in width.
panel diaphragm-shear action. The wall shall be braced with diagonal cut-in braces or
blocking extending from comer to comer.
8.4.2.1.9 Gypsum Plaster on Gypsum Lath Gypsum
plaster on gypsum lath shall inc\ude plaster that is C8.4.2. l. 13 Horizontal Lumber Sheathing with Cut-In
glued or keyed to gypsum lath nailed to studs. Braces or Diagonal Blocking Horizontal sheathing
with cut-in braces or diagonal blocking is instal1ed in
C8.4.2.1.9 Gypsum Plaster on Gypsum Lath Typically, the same manner as horizontal sheathing, except the
~-in. plaster is glued or keyed to 16"X 48" gypsum walJ is braced with cut-in (or let-in) braces or block
lath, which is nailed to studs with 13-gage nails. ing. The bracing is usually instal1ed at a 45-degree
Gypsum plaster on gypsum lath resists lateral loads by angle and nailed with 8d or 10d nails at each stud, and
panel diaphragm action. at the top and bottom plates. Bracing provides only
nominal increase in resistance.
8.4.2.1.10 Gypsum Wallboard or Drywall Gypsum
wallboard or drywall shalJ include manufactured pan 8.4.2.1.14 Fiberboard or Particleboard Sheathing
els with a paper facing and gypsum core that are Fiberboard or particleboard sheathing walls shall
oriented horizontally or vertical1y and nailed to studs include tiberboard or particleboard paneJs that are
or blocking in a single layer or multiple layers. applied directly to the studs with nails.
C8.4.2.I.JO Gypsum Wallboard or Drywall Typically, C8.4.2.1.14 Fiberboard o,. Particleboard Sheathing
4-ft X 8-ft to 4-ft X 12-ft panel s are laid-up horizon Typical1y, 4-ft X 8-ft panel s are applied directly to the
tal1y or vertically and nailed to studs or blocking with studs with nails. Fiberboard requires nails (typically
5d to 8d cooler nails at 4 to 7 in. on center. Multiple 8d) with large heads such as rooting nails. Lateral
layers are used in sorne situations. The assembly loads are resisted by panel diaphragm action.
resists lateral force s by panel diaphragm action.
8.4.2.2 Ellhallced Wood Frame Shear Walls
8.4.2.1.11 Gypsum Sheathing Gypsum sheathing Enhanced wood frame shear walls shall include
shall include manufactured gypsum panels that are existing shear wal1s rehabilitated in accordance with
oriented horizontally or vertically and nailed to studs an approved method. Enhanced wood shear walls con
or blocking. sisting of wood structural panel sheathing added to
unlinished stud wal1s or wood structural panel sheath
C8.4.2.1.11 Gypsum Sheathing Typically, 4-ft X 8-ft ing overlay on existing shear walls shal1 be evaluated
to 4-ft X 12-ft panels are laid-up horizontally or verti in accordance with Scction 8.4.9. Where wood struc
cally and nailed to studs or blocking with galvanized tural panel sheathing is applied over existing sheath
ll-gage ?6-in. diameter head nails at 4 to 7 in. on ing, the expected strength shall be based on the
center. Gypsum sheathing is usually instal1ed on the expected strength of the overlaid material only and
exterior of structures with siding over it in order to reduced by 20% unless a ditlerent value is substanti
improve tire resistance. Lateral forces are resisted by ated by testing.
panel diaphragm action.
C8.4.2.2 Ellhallced Wood Frame Shear Walls
8.4.2.1.12 Plaster on Metal Lath Plaster on metallath Possible rehabilitation methods for wood shear
shall include gypsum plaster applied to expanded wire wal1s are described in Sections C8.4.2.2.1 through
lath that is nailed to the studs. C8.4.2.2.5.
238
ASCFJSEI 41-06
C8.4.2.2. J Wood Structural Panel Sheathing Added 10 tion. This rehabilitation procedure can be used on any
Unfinished Stud Walls Wood structural panel sheathing of lhe existing shear wall assemblies. Additional fram
may be added to one side of untinished stud waHs lo ing members can be added if necessary, and lhe wood
inerease the wall shear capaeity and stiffness. slructural panel s ean be cut to fit existing stud spacings.
Examples of untinished stud walls are eripple
walls and attic end walls. C8.4.2.2.4/ncreased Attachment Additional nailing,
collector straps, splice slraps, tie-downs, or other col
C8.4.2.2.2 Wood Structural Panel Sheathing Over/ay lectors may be added to existing wood structural
of Existillg Shear Walls The foHowing types of exist panel-sheathed walls lo increase their rigidity and
ing shear walls may be overlaid with wood structural capacity.
panel sheathing: Por exisling structural panel-sheathed walls, addi
tional nailing will result in higher capacity and
1. Single layer horizontal lumber sheathing or siding; increased sliffness. Other connectors-collector slraps,
2. Single layer diagonal lumber sheathing; spliee straps, or tie-downs-are often necessary to
3. Vertical wood siding only; inerease the rigidity and eapacity of existing structural
4. Gypsum plaster or wallboard on studs (also on gyp panel shear walls. Increased duetility will not neces
sum lath and gypsum wallboard); sarily result from the additional nailing. Access to
5. Gypsum sheathing; (hese shear walls will often require the remo val and
6. Horizontal lumber sheathing with cut-in braces or replacement of existing tinishes.
diagonal blocking; and
7. Piberboard or particleboard sheathing. C8.4.2.2.5 Conncctions Where absent, new connec
tions between shear walls and diaphragms and founda
The original sheathing should not be inc\uded in lhe
tions may be added. Where needed, blocking between
evaluation condueted in accordance wilh Section 8.4.9
f100r and roof joists at shear walls may be added.
and the expected capacily of the overlay material
Bloeking should be eonnected 10 the shear wall and
should be reduced by 20%.
the diaphragm lo provide a load palh for lateralloads.
This method results in a moderate increase in shear
Wood for framing members or blocking should be
eapacity and stiffness and can be applied in most places
kiln-dried or well-seasoned to prevent it from shrink
in most structures. For example, plywood sheathing can
ing away from lhe existing framing, or splítting.
be applied over an interior wall tinish. Por exterior
Most shear wall rehabilitation procedures require
applieations, the wood structural panel can be nailed
a check of aH existing connections, especiaHy to
díreclly through the exterior finish to the studs.
diaphragms and foundations. Sheet metal framing
Where existíng shear walls are overlaid with
elips can be used lo provide a verifiable connection
wood structural panels, the connections of the overlay
between the waH framing, the blocking, and the
to the existing framing must be considered. Splitting
diaphragm. Praming clips are also often used for con
can occur in both Ihe wood sheathing and lhe framing.
necting blocking or rim joists lo sill plates.
The length of nails needed lo achieve full capacity
PrequentIy, bolting between sill plates and foun
attaehment in the existing framing must be deter
dations musl be added.
mined. This lenglh will vary wilh the thiekness of lhe
The framing in existing buildings is usually very
existing wall covering. Sometimes staples are used
dry, hard, and easily split. Care must be taken nol 10
inslcad of nails lo prevenl splitting. The overlay is sta
split the existing framing when adding conneetors.
pled to the wood sheathing instead of the framing.
PredriJIing holes fOI" nails will reduce splitting, and
Nails are recommended for overlay aHachmenl lo the
framing e1ips that use small nails are less likely to split
underlying framing. In some cases, new blocking al
the exisling framing.
wood struclural panel joints may also be needed.
C8.4.2.2.3 Wood Structural Panel Sheathing Added 8.4.2.3 New Wood Frame Shear Walls
lindel' Existing Wall Covering The exisling wall cover New wood frame shear walls shall inelude aH new
ing may be removed; wood structural panel sheathing, wood struclural panel shear walls added lo an existing
conneetions, and tie-downs may be added and the wall lateral-force-resisting system. Design of new walls shalI
covering may be replaced. satisfy lhe acceptanee crileria of this standard. Details
This method wi\l resuh in a signiticant inerease in of construction for new shear walls, ineluding sill plate
shear capacity. In some cases, where eaI1hquake loads anchorage details, tie-down anchor details, nailing
are large, this may be the best method of rehabilita details for sheathing, and dimensionallímilatÍons for
239
SEISMIC REHABILlTATION OF EXISTING BUILDlNGS
studs and sill plates. shall be in accofdance wilh lhe C8.4.3.].3 Wood Structural Panel Sheathing or Siding
requirements of an approved building codeo Typically, the wood structural panels are applied verti
cally and screwed to lhe studs and tracks with No. 8 to
C8.4.2.3 New Wood Frame Shear Walls No. 12 self-tapping serews.
New shear waJIs using the existing framing Of
new framing generally are sheathed wilh wood slruc 8.4.3.2 Ellhanced Light Cage Metal Frame Shear
tUfal panel s (i.e., plywood or orienled strand board). Walls
According to the NEHRP Recommended Provisions Enhanced light gage metal trame shear walls shall
for Seismic Regulations for New Buildings and Other inelude existing shear walls rehabilitated in aceor
Structures (BSSC 2000), only wood struclural panel dance with an approved method.
sheathing is permitted for use in wood frame shear
walls in engineered conslruclÍon. The thickness and C8.4.3.2 Enhallced Light-Cage Metal Frame Shear
grade of these panel s can vary. In mOSl cases, lhe pan Walls
els are placed vertically and faslened direclly lo the Possible rehabilitation methods for Iight gage
studs and plates. This reduces the need fol' blocking at metal frame shear walls are deseribed in Sections
the joints. AII edges 01' panels must be blocked to C8.4.3.2.1 and C8.4.3.2.2. See Section 8.4.2.2 for
obtain full capacity. The lhiekness, size, and number additional informalion eoncerning enhaneement ol'
of fasleners, and aspect ratio and connections wiJl existing shear walls.
determine the capacily of the new walls. Addilional
infol'mation on the various panel s available and their C8.4.3.2.1 Wood Structural Panel Sheathing Added to
application rOl' shear walls ean be found in documents Existing Metal Stud Walls Any exisling coveríng olher
from lhe American Plywood Associalion (APA) such Ihan wood slructural panels shall be removed and
as Design Capacities ofAPA Pelformance Rated replaced wilh wood struelural panels. Conneelions lo
Structural-Use Panels (APA 1995) and Plywood the diaphragm(s) and the foundation shall be checked
Design Specificatiofl (APA 1997) and Tissell (1993). and slrengthened where not adequate to resíst
enhanced wall capacity.
8.4.3 1)rpes of Light Gage Metal Frame Shear
Walls C8.4.3.2.2 1ncreased Attachment Screws and connec
tions shall be added to conneet existing wood struc
8.4.3.1 Existing Light Cage Metal Frame Shear tural panel s to framing.
Walls
8.4.3.3 New Light Cage Metal Frame Shear
8.4.3.1.1 Plaster OH Metal Lath Plasler on metal lalh Walls
shall inelude gypsum plasler applied to metal lath or New Iight gage metal frame shear walls shall
expanded metallath thal is eonnected 10 the melal inelude all new wood structural panel elemenls added
framing wilh wire tieso lo an existing lateral-foree-resisting system. Design of
new walls shall satisfy Ihe aeeeptance critería of this
C8.4.3.I.1 Plaster on Metal Lath Typically, l in. of standard. Details of eonstruelion for new shear walls,
gypsum plaster is applied to metallath or expanded including lrack anehorage details, lie-down anchor
metal that is eonnected 10 Ihe melal framing wilh details, fastening details for shealhing, and dimen
wire lies. sional limitations for sluds and tracks, shall be in
aecordance with Ihe requirements 01' an approved
8.4.3.1.2 Gypsum Wallboard Gypsum wallboard shear building codeo
walls shall inelude gypsum wallboard panels Ihat are
aHaehed to the slUds.
8.4.4 Single-Layer Horizontal Lumber Sheathing or
C8.4.3.1.2 Gypsum Wallboard TypieaJly, 4-ft X 8-ft Siding Shear Walls
lo 4-fl X 12-ft panels are laid-up horizontally and
screwed wilh No. 6 X I-in.-Iong self-tapping screws 8.4.4.1 Stiffness
lO studs al 4 lo 7 in. on cenler. The del1ection of single-layer horizontal lumber
shcalhing or sidíng shear walls shall be calculated in
8.4.3.1.3 Wood Structural Panel Sheathing 01' Siding aceordanee with Eq. 8-1:
Wood struetural panel shear walls shall ¡nelude slruc
lural panels Ihat are auached lo the sluds and lraeks. ay Vyh/G(/ + (h/b)d a (Eq.8-1)
240
ASCFlSEI 4) -06
241
SEISMIC REHABILlTATION OF EXISTlNG BUILDING S
Table 8-3. Numerical Acceptance Factors for Linear Procedures- Wood Components
m-Factors
Primary Secondary
Height/Width
,
Wood and Light Frame Shear Walls ,3 Ratio (111 b) 10 LS CP LS CP
Horizontal I-in. X 6-in. Sheathing hlb :s 1.0 1.8 4.2 5.0 5.0 5.5
Horizontal I-in. X 8-in. or I-in. X lO-in. Sheathing hlb:S 1.0 1.6 3.4 4.0 4.0 5.0
Horizontal Wood Siding over Horizontal I-in. X 6-in. hlb:s 1.0 lA 2.6 3.0 3.1 4.0
Sheathing
Horizontal Wood Siding over Horizontal l-in. X 8-in. hlb:s 1.5 1.3 2.3 2.6 2.8 3.0
or 1-in. X JO-in. Shealhing
Diagonal l-in. X 6-in. Sheathing hlb :s 1.5 1.5 2.9 3.3 3.4 3.8
Diagonal l-in. X 8-in. Sheathing hlb :s 1.5 lA 2.7 3.1 3.1 3.6
Horizontal Wood Siding over Diagonal l-in. X 6-in. hlb:s 2.0 1.3 2.2 2.5 2.5 3.0
Shealhing
Horizontal Wood Siding over Diagonal I-in. X 8-in. hlb:s 2.0 1.3 2.0 2.3 2.5 2.8
Sheathing
Double Diagonal 1-in. X 6-in. Sheathing hlb:s 2.0 1.2 1.8 2.0 2.3 2.5
Double Diagonal 1-in. X 8-in. Sheathing hlb:S 2.0 1.2 1.7 1.9 2.0 2.5
Vertical I-in. X 100in. Sheathing hlb :s 1.0 1.5 3.1 3.6 3.6 4.1
Wood Structural Panel Sheathing or Sidingl hlb :s 2.0 1.7 3.8 4.5 4.5 5.5
hlb 3.5 1.4 2.6 3.0 6.0 7.0
Stucco on Studs1 hlb:s 1.0 1.5 :U 3.6 3.6 4.0
hlb = 2.0 1.3 2.2 2.5 5.0 6.0
Stucco over 1-in. X HorizonLal Sheathing Izlb :s 2.0 1.5 3.0 3.5 3.5 4.0
Gypsum Plaster on Wood Lath Izlb:s 2.0 1.7 3.9 4.6 4.6 5.1
Gypsum Plaster on Gypsum Lalh hlb :s 2.0 1.8 4.2 5.0 4.2 5.5
Gypsum Plaster on Melal Lalh Izlb :s 2.0 1.7 3.7 4.4 3.7 5.0
Gypsum Sheathing hlb:s 2.0 1.9 4.7 5.7 4.7 6.0
Gypsum Wallboard2 hlb:S 1.0 1.9 4.7 5.7 4.7 6.0
Izlb 2.0 1.6 3.4 4.0 3.8 4.5
Horizontal 1-in. X 6-in. Sheathing with Cut-In Braces IzIb :s 1.0 1.7 3.7 4.4 4.2 4.8
or Diagonal Blocking
Fiberboard or Particleboard Shealhing Izlb:S 1.5 1.6 3.2 3.8 3.8 5.0
Length/Width
Diaphragms 5 Ratio (Llb)
Single Straight Shealhing, Chorded Llb:S 3.0 2.0 2.5 2.4 3.1
Single Straighl Shealhing, Unchorded Llb:S 3.0 1 1.5 2.0 1.8 2.5
Double Straight Sheathing, Chorded Llb:s 3.0 1.25 2.0 2.5 2.3 2.8
Double Slraight Sheathing, Unchorded Llb:S 3.0 I 1.5 2.0 1.8 2.3
Single Diagonal Shealhing, Chorded Llb:S 3.0 1.25 2.0 2.5 2.3 2.9
Single Diagonal Shealhing, Unchorded Llb:S 3.0 1 1.5 2.0 1.8 2.5
Slraight Sheathing over Diagonal Sheathing, Chorded Llb:S 3.0 1.5 2.5 3.0 2.8 3.5
Straight Sheathing over Diagonal Sheathing. Llb:S 3.0 1.25 2.0 2.5 2.3 3.0
Unchorded
Double Diagonal Shealhing, Chorded Llb:S 3.5 I.S 2.5 3.0 2.9 3.5
Double Diagonal Shealhing. Unchorded Llb:S 3.5 125 2.0 2.5 2.4 3.1
Wood Structural Panel, Blocked, Chorded2 Llb:S 3.0 1.5 3.0 4.0 3.0 4.5
Llb = 4 l.5 2.5 3.0 2.8 3.5
Wood Structural Panel, Unblocked, Chorded 2 Llb:S 3 1.5 2.5 3.0 2.9 4.0
Llb = 4 1.5 2.0 2.5 2.6 3.2
Wood Structural Panel, Blocked, Unchorded 2 Llb:S 2.5 1.25 2.5 3.0 2.9 4.0
Llb = 3.5 1.25 2.0 2.5 2.6 3.2
242
ASCE/SEI 41-06
m-Factors
Primary Secondary
Length/Width
Diaphragms 5 Ratio (Llb) 10 LS CP LS CP
2
Woüd Structund Panel, Unblocked, Unchorded Llb:s 2.5 1.25 2.0 2.5 2.4 3.0
Llb 3.5 1.0 1.5 2.0 2.0 2.6
Wood Structural Panel Overlay on Sheathing, Chorded 2 Llb 3 1.5 2.5 3.0 2.9 4.0
Llb 4 1.5 2.0 2.5 2.6 3.2
Wood Structural Panel Overlay on Sheathing, Llb:s 2.5 1.25 2.0 2.5 2.4 3.0
Unchorded2 Llb = 3.5 1.0 1.5 2.0 \.9 2.6
Conlponents/Elements
Frame Components Subject 10 Axial Tension ami/or 1.0 2.5 3.0 2.5 4.0
Bending
Frame Components Subject 10 Axial Compression Force-controlled
Wood Piles, Bending and Axial 1.2 2.5 3.0
Cantilever Pole Slructures, Bending and Axial 1.2 3.0 3.5
Pole Structures With Diagonal Bracing 1.0 2.5 3.0
Connectors4
Nails-8d and Larger-Wood 10 Wood 2.0 6.0 8.0 8.0 9.0
Nails-8d and Larger-Metal lo Wood 2.0 4.0 6.0 5.0 7.0
Screws- Wood to Wüod 1.2 2.0 2.2 2.0 2.5
Screws-Metal to Wood 1.1 1.8 2.0 1.8 2.3
Lag Bolts- Wood lo Wood 1.4 2.5 3.0 2.5 3.3
Lag Bolls-Metal to Wood 1.3 2.3 2.5 2.4 3.0
Machine Bolts- Wood to Wood 1.3 3.0 3.5 3.3 3.9
Machine Bolts-Metal to Wood 1.4 2.8 3.3 3.1 3.7
Split Rings and Shear Plates 1.3 2.2 2.5 2.3 2.7
'Shear walls shall be penniued 10 be c1assified as secoodary compooeots or oonslructural compooents, subject lo Ihe limilations of Section 3.2.2.3.
Acceptaoce criteria need oot be coosidered fol' waJls c1assified as secondary or noostructural.
'Lioear interpolalioo shall be permitted for iotermediale values of aspecl ratio.
3Shear waJl componeots with aspect ralios exceeding maximum Iisted values shall oot be coosidered effeclive io resisling lateral loads.
4Actions on conoectors 001 listed in Ihis lable shall be considered force-conlrolled.
sFor diaphragm components with aspeCI ratios between maximum Iisted values aod 4.0, m-factors shall be decreased by linear interpolatíon
belween Ihe Usted values aod 1.0. Diaphragm compooents with aspecl ralios exceedíog 4.0 shall 001 be considered effective io resistiog lateral
loads.
243
SEISMIC REHABILlTATlON OF EXlSTlNG BUlLDlNGS
Table 8-4. Modeling Parameters and Numerical Acceptance Criteria for Nonlinear Procedures-
Wood Components
Acceptance CriteriaS
Acceptable Deformation Ratio 11/11,
Modeling Parameters
Performance Level
Residual
A Component Type
Strength
Av Ratio Primary Secondary
el e e 10 LS CP LS CP
Height/Width
Wood and Light Frame Shear Walls l Ratio (h/b)
Horizontal I-in. X 6-in. Sheathing h/b:S 1.0 5.0 6.0 0.3 2.0 4.0 5.0 5.0 6.0
Horizontal I·in. X 8-in. or l-in. X JO-in. h/b:S 1.0 4.0 5.0 0.3 1.8 3.3 4.0 4.0 5.0
Sheathing
Horizontal Wood Siding over Horizontal h/b:S 1.5 3.0 4.0 0.2 1.5 2.5 3.0 3.0 4.0
1-in. X 6-in. Shealhing
Horizontal Wood Siding over Horizontal h/b:S 1.5 2.6 3.6 0.2 1.4 2.2 2.6 2.6 3.6
¡-in. X 8-in. or I-in. X ID-in. Shealhing
Diagonal l-in. X 6-in. Sheathing h/b:S 1.5 3.3 4.0 0.2 1.6 2.7 3.3 3.3 4.0
Diagonal I-in. X 8-in. Sheathing h/b:S 1.5 3.1 4.0 0.2 1.5 2.6 3.1 3.1 4.0
Horizontal Wood Siding over Diagonal h/b:S2.0 2.5 3.0 0.2 lA 2.1 2.5 2.5 3.0
I-in. X 6-in. Sheathing
Horizontal Wood Siding over Diagonal h/b:S 2.0 2.3 3.0 0.2 1.3 2.0 2.3 2.3 3.0
I-in. X 8-in. Sheathing
Double Diagonal I-in. X 6-in. Sheathing h/b:S 2.0 2.0 2.5 0.2 1.3 1.8 2.0 2.0 2.5
Double Diagonal l-in. X 8-in. Sheathing h/b:S 2.0 2.0 2.5 0.2 1.3 1.8 2.0 2.0 2.5
Vertical I-in. X lO-in. Sheathing h/b :S 1.0 3.6 4.0 0.3 1.7 3.0 3.6 3.6 4.0
Wood Structural Panel Sheathing or Siding2 h/b:S 2.0 4.5 5.5 0.3 1.9 3.6 4.5 4.5 5.5
h/b = 3.5 3.0 4.0 0.2 1.5 2.5 3.0 3.0 4.0
Stucco on Studs2 h/b:S 1.0 3.6 4.0 0.2 1.7 3.0 3.6 3.6 4.0
h/b = 2.0 2.5 3.0 0.2 1.4 2.1 2.5 2.5 3.0
Stucco over l-in. X Horizontal Sheathing h/b:S 2.0 3.5 4.0 0.2 1.6 2.9 3.5 3.5 4.0
Gypsum Plaster on Wood Lath h/b :S 2.0 4.6 5.0 0.2 1.9 3.7 4.6 4.6 5.0
Gypsum Plaster on Gypsum Lath h/b:S 2.0 5.0 6.0 0.2 2.0 4.0 5.0 5.0 6.0
Gypsum PIaster on Metal Lath h/b:S 2.0 4.4 5.0 0.2 1.9 3.6 4.4 4.4 5.0
Gypsum Shealhing h/b :S 2.0 5.7 6.3 0.2 2.2 4.5 5.7 5.7 6.3
Gypsum Wallboard2 h/b :S 1.0 5.7 6.3 0.2 2.2 4.5 5.7 5.7 6.3
h/b = 2.0 4.0 5.0 0.2 1.8 3.3 4.0 4.0 5.0
Horizontal l-ín. X 6-in. Sheathing Wilh Cut-In h/b :S 1.0 4.4 5.0 0.2 1.9 3.6 404 404 5.0
Braces or Diagonal Blocking
Fiberboard or Particleboard Sheathíng h/b:S 1.5 3.8 4.0 0.2 1.7 3.1 3.8 3.8 4.0
Length/Width
Diaphragms J Ratio (L/b)
Single Straight Sheathing, Chorded L/b:S 2.0 2.5 3.5 0.2 1.4 2.1 2.5 2.5 3.5
Single Straíght Sheathing, Unchorded L/b :S 2.0 2.0 3.0 0.3 1.3 1.8 2.0 2.0 3.0
Double Straight Sheathing, Chorded L/b :S 2.0 2.5 3.5 0.2 lA 2.1 2.5 2.5 3.5
Double Straight Sheathing, Unchorded L/b:S 2.0 2.0 3.0 0.3 1.3 1.8 2.0 2.0 3.0
Single Diagonal Sheathíng, Chorded L/b:S 2.0 2.5 3.5 0.2 1.4 2.1 2.5 2.5 3.5
Single Diagonal Sheathing, Unchorded L/b:S 2.0 2.0 3.0 0.3 1.3 1.8 2.0 2.0 3.0
Straight Sheathing over Diagonal Sheathing, Llb:S 2.0 3.0 4.0 0.2 1.5 2.5 3.0 3.0 4.0
Chorded
Straight Sheathing over Diagonal Sheathing, L/b:S 2.0 2.5 3.5 0.3 1.4 2.1 2.5 2.5 3.5
Unchorded
244
ASCE/SEI 41-06
Acceptance Criteria5
Acceptable Deformalion Ratio t:.jt:.,
Modeling Parameters
Performance Level
Residual
~ Component Type
Strenglh
~y Ratio Primary Secondary
d e e 10 LS CP LS CP
Double Diagonal Sheathing, Chorded Ljb"s; 2.0 3.0 4.0 0.2 1.5 2.5 3.0 3.0 4.0
Double Diagonal Sheathing, Unchorded Ljb"s; 2.0 2.5 3.5 0.2 lA 2.1 2.5 2.5 3.5
Wood Structural Panel, B1ocked, Chordedl Ljb 3 4.0 5.0 0.3 1.8 3.3 4.0 4.0 5.0
Ljb = 4 3.0 4.0 0.3 1.5 2.5 3.0 3.0 4.0
Wood Structural Panel, Unblocked, Chorded1 Ljb "s; 3 3.0 4.0 0.3 1.5 2.5 3.0 3.0 4.0
L/b 4 2.5 3.5 0.3 lA 2.1 2.5 2.5 3.5
Wood Structural Panel, Blocked, Unchorded1 Ljb"s; 2.5 3.0 4.0 0.3 1.5 2.5 3.0 3.0 4.0
Ljb = 3.5 2.5 3.5 0.3 lA 2.1 2.5 2.5 3.5
Wood Slructural Panel, Unblocked, Ljb "s; 2.5 2.5 3.5 OA \A 2.1 25 2.5 3.5
Unchorded 2 Ljb 3.5 2.0 3.0 0.4 1.3 1.8 2.0 2.0 3.0
Wood Slructural Panel Overlay on Shealhing, Ljb"s; 3 3.0 4.0 0.3 1.5 2.5 3.0 3.0 4.0
Chorded2 Ljb = 4 2.5 3.5 0.3 lA 2.\ 2.5 2.5 3.5
Wood Structural Panel Overlay on Shealhing, Ljb 2.5 2.5 3.5 OA lA 2.1 2.5 2.5 3.5
Unchorded 1 Ljb = 3.5 2.0 3.0 DA 1.3 1.8 2.0 2.0 3.0
Conneclions4
Nails- Wood 10 Wood 7.0 8.0 0.2 2.5 5.5 7.0 7.0 8.0
Nails-Melal lo Wood 5.5 7.0 0.2 2.1 4.4 5.5 5.5 7.0
Screws- Wood lo Wood 2.5 3.0 0.2 lA 2.1 2.5 2.5 3.0
Screws- Wood 10 Metal 2.3 2.8 0.2 1.3 2.0 2.3 2.3 2.8
Lag Bolts-Wood ro Wood 2.8 3.2 0.2 1.5 2A 2.8 2.8 3.2
Lag Bolts-Metallo Wood 2.5 3.0 0.2 lA 2.1 25 2.5 3.0
Bolts-Wood lo Wood 3.0 3.5 0.2 1.5 2.5 3.0 3.0 3.5
Bolts-Metalto Wood 2.8 3.3 0.2 1.5 2A 2.8 2.8 3.3
'Sh.:ar wall compon.:nts with aspect ratíos excccdíng maxímum lísted values shall not be considered effeclive in resistíng lateralloads.
'Linear inlerpolalion shall be permitted for intermediate values of aspcct ratio.
"Fur diaphragm components wilh aspecl ratios between maximum lisled values and 4.0. deformalÍon ratios shall be deereased by linear inlerpola
tion between the Iisted values and 1.0. Diaphragm components with aspect ratios excccding 4.0 shall nol be considered ellectíve in resisting lateral
loads.
4Actions on connectors not listed in this table shall be considered torce-controlled
'Primary and secondary component demands shall be within secondary component acceptance criteria where lhe full backbone curve is explicitly
modeled, including slrength dcgradation and residual strcngth in accordance with Section 3.4.3.2.
245
SEISMIC REHABILlTATION OF EXISTING BUILDJNGS
8.4.7 Wood Siding over Horizontal Sheathing are often suitable for resisting earthquake shear loads
Shear Walls that are modef'dte in magnitude. They also provide
good sliffness for detlection control and damage
8.4.7.1 Stiffness control.
The detlection 01' wood siding over horizontal
sheathing shear walls shall be determined using 8.4.8.2 Strength
Eq. 8- J. ProperlÍes used lO compute shear wall The expected strength of wood siding over diago
deflection and stitTness shall be based on nal sheathing shall be determined in aceordance with
Section 8.2.2. Seetion 8.2.2.
246
ASCElSEI 41-06
en = naíl deformation at yield load per naíl (in.). (values withoul a cf> factor) are similar to factored
Values listed are for Structural 1 panels; multiply strength value with cf> 1.0.
by 1.2 1'or all other panel grades; A melhod for calculating the capacity of wood
= 0.13 for 6d nails al yield; structural shear walls based on accepted nail values is
= 0.08 for 8d nails al yield; provided in TisselJ (1993). For this method, use
= 0.08 for IOd nails at yield. LRFD-based fastener strengths. Due to the ditJerences
in load-duratíonltime-effect faclors belween lhe allow
Properties used lO compute shear wall deflection able stress and LRFD formals, direct conversion of
and stitfness shall be based on Section 8.2.2. shear wall tables using the method outlined in Sec
lion 8.2.2.5 is not permiued. However, the tabulated
C8.4.9.1 Stiffness LRFD design values, with 4> = 1, are intended to be
The response of wood structural panel shear walls 2.0 times the associated allowable stress design
is dependent on the thickness oí' the wood structural values.
panels, the height-to-width (h/b) ratio, the nailing pat
tern, and other factors. Values for modulus of rigidity, 8.4.9.3 Acceptallce Criterio
G, and effective thickness, 1, for various sheathing For linear procedures, m-factors for use with
materials are contained in Design Capacilies ofAPA deformation-controlled actions shall be taken from
Perfonnance Raled Structural-Use Panels (APA 1995) Table 8-3. For nonJinear procedures, the coordinates 01'
and Plywood Design Specification (APA 1997). the generalized force-deformation relation, described
in Eq. 8-1, and deformation acceptance criteria for pri
8.4.9.2 Strength mary and secondary components shaIl be taken from
The expected strength of wood structural panel Table 8-4.
shear walls shall be taken as mean maximum strenglhs
obtained experimentally. Expected strengths 01' wood 8.4.9.4 COllllectiollS
struclural panel shear walls shall be permiued to be The connections between parts of the shear wall
based on 1.5 times yield strengths. Yield strengths assembly and other elements 01' the lateral-force
shall be determined using LRFD procedures conlained resisting system shall be considered in accordance
in AF&PNASCE 16 Standard for Load and with Section 8.4.1.
Resistance Factor Design (LRFD)for Engineered
Wood Construction (ASCE 19%), except lhat the
8.4.10 Stucco 00 Studs, Sheathiog, or Fiberboard
resistance factor, 4>, shall be taken as unity and
expected material properties shaJl be delermined in 8.4.10.1 Stiffness
accordance with Section 8.2.2. The deflection of stucco on studs, sheathing, or
Conversion from tabulaled allowable stress values fiberboard shear walIs shall be determined using
in accordance with Section 8.2.2.5 shall not be permit
Eq. 8-1. Properties used to compute shear waIl deflec
ted for wood structural panel shear walls, bUl approved
tion and stiffness shall be based on SectÍon 8.2.2.
allowable stress values for fasteners shalJ be permitted
to be converted in accordance with Section 8.2.2.5 C8.4.10.1 Stifflless
where the slrenglh of a shear waIl is compUled using Stucco is brittle and the lateral-force-resisting
principIes 01' mechanics. capacity of stucco shear walls is low. The walls are
stiff until cracking occurs, bul the strength and stitf
C8.4.9.2 Strength
ness degrade under cyclic loading. These shear waIls
Shear capacities of wood structural panel shear
are suitable only where earthquake shear loads are
walls are primarily dependenl on lhe naiJing at the ply
low.
wood panel edges, and the thickness and grade of the
plywood. 8.4.10.2 Strellgth
LRFD-based design values for various configura The expected slrength of stucco on studs, sheath
tions are lisled in the LRFD Manual for Engineered ing, or fiberboard shall be delermined in accordance
Wood Construction (AF&PA LRFD 1996) and the wilh Section 8.2.2.
NEHRP Recommended Provisiolls for Seismic
Regulations for New Buildings and Other Structures C8.4.10.2 Strmgth
(BSSC 2(00). For labuJaled values, sorne references This capacity is dependent on the auachment 01'
provide nominal strength and sorne provide facLored the stucco netting to the studs and the embedment of
strength. Il is expected that nominal strength values lhe neUing in the slucco.
247
SEISMIC REHABILlTATION OF EXISTING BUILDlNGS
248
ASCE/SEI 41-06
249
SElSMIC REHABILlTATION OF EXlSTING BUILDINGS
8.4.1$.3 Acceptance Criteria Table 8-3. For nonlinear procedures, the eoordinates of
For linear procedures, m-factors ror use with the generalized 1'orce-deformalion relation, described
deformation-controlled actions shall be taken from by Fig. 8-1, and derormation acceptance criteria for
Table 8-3. For nonlinear procedures, the coordinates of primary and secondary componenls shall be taken
the generalized force-deformation relation, described from Table 8-4.
by Fig. 8-1, and deformation acceptance crileria for
primary and secondary components shaIl be taken 8.4.16.4 Conneetions
from Table 8-4. The connections between the parts of the shear
waIl assembly and other elements of the lateral-force
8.4.15.4 Conneetions resisting syslem shall be considercd in accordance
The presence of conneclions between parls of the with Section 8.4.1,
shear wall assembly and olher elements of the lateral
force-resisting system shall be verified. If connections C8.4.16.4 COllneclions
are present, they need not be considered in the analy The capacity and ductility of these connections
sis conducted in accordance with Chapter 3. If connec will often determine the failure mooe as well as the
tions are absent, they shall be provided in accordance capacity of the assembly. Ductile connections with
wilh Section 8.4.1. sutTicient capacity will give acceptable performance
(see Section 8.2.2.2.2).
C8.4.15.4 Connee/ions
The lensile and bearing capacity of the plaster, 8.4.17 Fiberboard or Particleboard Sheathing
ralher Ihan the conne~tions, will often govern failure.
The re1atively low slrenglh of this material makes con 8.4.17.1 Stifflless
nections between parts of the shear waIl assembly and For structural partícleboard sheathing, see Section
the other elements oí' the lateral-force-resisling system 8.4.9. The det1ectÍon ol' shear walls sheathcd in non
01' less concern. struclural partícleboard shall be delermíned using
Eq. 8-1. Properties used to compute shcar wall detlec
8.4.16 Horizontal Lumber Sheathing with Cut-In tion and stiffness shall be based on Section 8.2.2.
Braces or Diagonal Blocking Fiberboard sheathing shall not be considered a struc
tural element for resisting seismic loads.
8.4.16.1 Stiffness
The det1ection of horizontallumber sheathing e8.4.l7.1 Stiffness
with cut-in braces or diagonal blocking shear walls Fiberboard sheathing is very weak, lacks slilfness,
shull be calculated using Eq. 8-1. Properlies used to and is unable to resíst lateral loads. Particleboard
compule shear wall detlection and stiffness shall be comes in two varieties: one is similar to structural pan
based on Section 8.2.2. els, the other (nonstructural) is slightly stronger than
gypsum board but more briule. Nonstruclural partícle
C8.4.16.1 Stiffness board should only be used where earthquake loads are
This assembly is similar to horizontal sheathing very low.
without braces, except thal the cut-in braces or diag
onal blocking provide higher stiffness al initialloads. 8.4.17.2 Strenglh
After the braces 01' blocking fail (at low 10ads), the The expected slrcngth of structural parlic\eboard
behavior 01' lhe wall is the same as wilh horizontal shall be based on Section 8.4.9. The strength of non
sheathing without braces. The strength and stiffness structural t1berboard or particleboard sheathed walls
degrade under cycJic loading. shall be determined in accordance with Section 8.2.2.
250
AseE/SEl 41-06
Table 8-3. For nonlinear procedures, the coordinates of 8.5 WOOD DIAPHRAGMS
the generalized force-deformation relalion, described
by Fig. 8-1, and deformation acceplance crileria for 8.5.1 General
primary and secondary components shall be laken The expected strenglh of wood diaphragm assem
from Table 8-4. blies, QCE' shall be delermined in accordance with
Sections 8.5.3 through 8.5.10. The expected slrength,
8.4.17.4 Connections QCE' of braced horizontal diaphragm systems shall be
The connections between parts of structural parti delermined in accordance wilh Section 8.5.11.
cIeboard shear waIl assemblies and other elemenls of The effects of openings in wood diaphragms shaIl
lhe lateral-force-resisting system shall be considered in be considered. Chords and collectors shall be added lo
accordance with Section 8.4.1. provide sufticient load capacity around openings lO
The presence of conneclions belween parls of meel the strenglh requiremenls for lhe diaphragm.
nonstructural particleboard shear wall assemblies and Conneclions between diaphragms and other
olher elements of lhe lateral-force-resisting system components including shear walls, diaphragm ties,
shall be verífied. If connections are presenl, lhey coIlectors, cross tíes, and out-of-plane anchors shall be
need not be considered in lhe analysís conducted considered in accordance with Section 83.3, and
in accordance with Chapler 3. If connections are designed for forces calculated in accordance with
absent, they shall be provided in accordance wilh Chapter 3.
Seclion 8.4.1.
e8.5.1 General
C8.4.17.4 C01lnections The behavior of horizontal wood diaphragms is
The capacity and ductilíty of lhe connections in influenced by the type of sheathing, size and amount
structural particJeboard shear walls will often deter 01' fasleners, existence of perimeter chord or tlange
mine lhe faílure mode as well as the capacity of the members, and the ratio of span length to width of the
assembly. DUClile connections with sufticienl capacity diaphragm.
will give acceptable performance. The lensile and The presence of any bUl smaJI openings in wood
bearing capacily of lhe nonslructural particleboard, diaphragms will cause a reduction in lhe stiffness and
ralher than the connectíons, will often govero failure. strength of the diaphragm due to a reduced length of
The relatively Iow slrength of this material makes con diaphragm available to resist lateral forces. Specíal
neclions between parts of the shear wall assembly and analysis techniques and detailing are required at Ihe
lhe other elements of the lateral-force-resisting system openings. The presence or addition 01' chord members
ol' less concero. around the openings will reduce the loss in stíffness of
Ihe diaphragm and limit damage in the area of the
8.4.18 Ligbt Gage Metal Frame Sbear Walls openings. See Guidelines for the Design of Horizontal
Wood Diaphragms, ATC-7 (ATC 1981) and TisseIl and
8.4.18.1 PÚlSter on MetallAth Elliott (1997) for a discussion of the etfects 01' open
The criteria for plaster on metal lath shall be ings in wood diaphragms.
based on Section 8.4.15. The presence of chords at lhe perimeter of a
diaphragm will significantly reduce the diaphragm
8.4.18.2 Gypsum Wallboard detlection due to bending, and increase the stiffness 01'
The criteria ror gypsum wallboard shall be based the díaphragm over that of an unchorded diaphragm.
on Section 8.4.13. However, lhe increase in stiffness due to chords in a
single straight-sheathed diaphragm is mini mal due lo
the flexible natUfe of Ihese diaphragms.
8.4.18.3 Wood Structural Panels
The criteria for wood slruclural panel s shal1 be
based on Seclion 8.4.9. The expecled strength values 8.5.2 Types of Wood Diapbragms
of fasteners shall be calculated in accordance with
Section 8.2.2.5, based on approved data. The expected 8.5.2.1 Existing Wood Diaphragms
strength of the wood structural panels shall be
adjusted to account fol' differences in strength values 8.5.2. J. J Single Straight Sheathing Single straight
of fasteners into light gage melal studs rather than shealhed diaphragms shall inelude diaphragms with
wood studs. sheathing laid perpendicular 10 the framing members.
251
SEISMIC REHABILlTATION OF EXISTlNG BUfLDINGS
C8.5.2. l. 1 Single Straight Sheathing Typically, single 01' the diaphragm is dependent on the size and quantity
straight-sheathed diaphragms consist 01' I-in. X of the nails at each sheathing board.
sheathing laid perpendicular to the framing members;
2-in. X or 3-in. X sheathing may also be present. The 8.5.2.1.4 Diagonal Sheathing with Straight Sheathing
sheathing serves the dual purpose 01' supporting grav or Flooring Above Diagonal sheathing with straight
ity loads and resisting shear forces in the diaphragm. sheathing or tlooring aboye shall inelude diaphragms
Most often, l-in. X sheathing is nailed with 8d or with sheathing laid at a 45-degree angle to the framing
IOd nails, with two or more nails per shealhing board members, with a second layer 01' straight sheathing or
at each support. Shear forces perpendicular lo the wood tlooring laid on top 01' the diagonal sheathing at
direction 01' the sheathing are resisted by the nail cou a 90-degree angle to the framing members.
pIe. Shear forces parallel to the direction 01' the sheath
ing are transl'erred through the nails in the supporting C8.5.2.1.4 Diagonal Sheathing with Straight
joists or framing members below the sheathing joints. Sheatlzing or Flooring Above Typically, these consist
01' a lower layer of l-in. X diagonal shealhing laid at a
8.5.2.1.2 Double Straight Sheathing Double straight 45-degree angle to the framing members, with a sec
sheathed diaphragms shall inelude diaphragms with ond layer of straight sheathing or wood tlooring laid
one layer of sheathing laid perpendicular to the fram on lop of the diagonal sheathing at a 90-degree angle
ing members and a second layer of sheathing laid to the framing members. Bolh layers of shealhing
either perpendicular or parallel to the tirst layer, where support gravily loads and resist shear forces in lhe
both layers 01' sheathing are fas tened to the framing diaphragm. Sheathing boards are commonly connected
members. with lwo or more 8d nails per board at each support.
C8.5.2.1.2 Double Straight Sheathing Construclion 01' 8.5.2.1.5 Double Diagonal Sheathing Double diago
double straight-sheathed diaphragms is the same as nally sheathed diaphragms shall inelude diaphragms
that for single straight-sheathed diaphragms, except wilh one layer 01' sheathing laid at a 45-degree angle
that an upper layer of straight sheathing is laid over to the framing members and a second layer 01' sheath
the lower layer of sheathing. The upper sheathing can ing laid at a 90-degree angle to the tirst layer.
be placed either perpendicular or parallel to the lower
layer of sheathing. If the upper layer 01' sheathing is C8.5.2.1.5 Double Diagonal Sheathing Typically,
parallel to the lower layer, the board joints are usually double diagonally sheathed diaphragms consist of a
offset sufliciently that nails at joints in the upper layer lower layer of I-in. X diagonal shealhing wilh a sec
01' sheathing are driven into a common sheathing ond layer of I-in. X diagonal sheathing laid at a
board be\ow, with sutlicient edge distance. The upper 90-degree angle to the lower layer. The sheathing sup
layer 01' sheathing is nailed to the framing members ports gravity loads and resists shear force s in the
through the lower layer of sheathing. diaphragm. The sheathing is commonly nailed with
8d nails, with lwo or more nails per board at each sup
8.5.2.1.3 Single Diagonal Sheathing Single diagonally port. The recommended nailing for double diagonally
sheathed diaphragms shall inelude diaphragms with sheathed diaphragms is published in lhe Western
sheathing laid at approximately a 45-degree angle and Woods Use Book (WWPA 1996).
connected to the framing members.
8.5.2.1.6 Wood Structural Panel Sheathing Wood
C8.5.2.1.3 Single Diagonal Sheathing Typically, structural panel-sheathed diaphragms shall inelude
l-in. X shealhing is laid al an approximale 45-degree diaphragms wilh wood structural panel, or olher wood
angle to the framing members. In sorne cases 2-in. X slruclural panel s as detined in lhis slandard, raslened
shealhing may also be used. The sheathing supporls lo lhe 1'raming members.
gravity loads and resisls shear forces in the diaphragm.
Commonly, l-in. X sheathing is nailed with 8d nails, C8.5.2.1.6 Wood Structural Panel Sheathing TypicaIly,
with two or more nails per board at each support. The these consist of wood structural panels, such as wood
recommended nailing for diagonally sheathed structural panel or oriented strand board, placed on
diaphragms is published in (he Western Woods Use framing members and nailed in place. DitTerenl grades
Book (WWPA 1996) and the NEHRP Recommended and thicknesses of wood structural panel s are com
Provisions for Seismic Regulations for New Buildings monly used, depending on requirements 1'or gravily
and Other Structures (BSSC 200ü). The shear capacily load support and shear capacity. Edges at lhe ends of
252
ASeE/SEI 41-06
the wooo structural panels are usually supported by If a stronger and sLÍffer diaphragm is desired,
the framing members. Edges at the sides of the panels (he joints of the new wood slructural panel overlay
can be blocked or unblocked. In sorne cases, tongue should be placed parallel to the joiots of the existing
and groove wood structural panels are used. Nailing sheathing, with the overlay nailed or stapled to Ihe
pauerns and nail size can vary greatly. Nail spacing is existing sheathing. The edges of the new wood
commonly in the range of 3 to 6 in. on center at the structural panel s should be offset from the joints in
supported and blocked edges of lhe panels, and 10 lo the existing sheathing below by a sufticient distance
12 in. on center al the panel infield. Staples are some that the new nails may be driven into the existing
times used to attach the wood struclural panels. sheathing withoul splitting the sheatlúng. If the new
panels are nailed at all edges as described aboye, the
8.5.2.1.7 Braced Horizontal Diaphragms Braced hori response of the new overlay will be similar to that
zontal diaphragms shall inelude diaphragms with a of a blocked wooo structural panel diaphragm. As
horizontal truss system al the floor or roof level of the an alternative, new blocking may be installed below
building. all panel joints perpendicular to lhe existing framing
members.
C8.5.2. 1. 7 Braced Horizontal Diaphragms TypicaJly, Because the joints of the overlay and the joints of
these consist of "X" roo bracing and woOO struts form the existing sheathing may not be offset consistently
ing a horizontal truss system at the floor or roof levels without cuUing the panel s, it may be advantageous to
of the building. The "X" bracing usuaJly consists of place the wood structural panel overlay at a 45-degree
steel rOOs drawn taut by turnbuckles or nuts. The struts angle to the existing sheathing. If the existing
usually consisl of wood members, which may or may diaphragm is straight-shealhed, the new overlay should
not be part of the gravity-Ioad-bearing system of the be placed at a 45-degree angle lO the existing sheath
floor or roof. The steel rOOs function as tension mem ing and joists. If (he existing diaphragm is diagonally
bers in the horizontal lruss, while the struts function as sheathed, the new wooo structural panel overlay
compression members. Truss chords (similar to should be placed perpendicular to the existing joists at
diaphragm chords) are needed lo resist bending in the a 45-degree angle lo the diagonal sheathing. Nails
horizontal truss system. should be driven ioto the existing sheathing with suffi
cient edge distance to prevent splitting of the exisling
8.5.2.2 Enhanced Wood Diaphragms sheathing. Al boundaries, nails should be of sufticient
Enhanced wood diaphragms shall inelude exisling length to penetrate the sheathing into the framing
diaphragms rehabilitated by an approved methOO. below. New structural panel overlays shall be con
nected to shear walls or vertical bracing elements to
C8.5.2.2 Enhanced Wood Diaphragms ensure the effectiveness of the added panel.
Possible rehabilitation methoos for wooo Care should be exercised where placing new
diaphragms are described in Sections 8.5.2.2.1 through wooo structural panel overlays on existing
8.5.2.2.3. diaphragms. The changes in stiffness and dynamic
characteristics of the diaphragm may have negative
C8.5.2.2.1 Wood Structural Panel Overlays on Straight effects by causing increased forces in other components
or Diagonal Sheathing Existing sheathed diaphragms or elements. The increased stiffness and the associated
may be overlaid with new woOO structural panels. increase in dynamic forces may not be desirable in
Nails or slaples may be used lo connect the new slruc sorne diaphragms for certain performance levels.
tural panels lo Ihe existing diaphragms. Nails should
be of sufticient length lo provide the required embed C8.5.2.2.2 lVood Structural Panel Overlays on Existing
menl into framing members below the sheathing. Wood Structural Panels Existing wood structural panel
These diaphragms typically consisl of new wooo diaphragms may be overlaid with new wood structural
structural panels placed over existing straight or diag panels. Panel joints should be offset, or the overlay
onal sheathing and nailed or stapled to the existing should be placed at a 45-degree angle to the existing
framing members through the existing sheathing. If wood structural panels.
Ihe new overlay is nailed to Ihe existing framing mem The placement of a new overlay over an existing
bers only-without nailing at the panel edges perpen diaphragm should folJow the same constructÍon
dicular to the framing-the response of the new melhoos and procedures as lhose used for straight
overlay will be similar to that of an unblocked wood sheathed and diagonalIy sheathed diaphragms (see
struclural panel diaphragm. Section C8.5.2.2.l).
253
SEISMIC REHABILITATION OF EXISTlNG BUILDlNGS
C8.5.2.2.3 lncreased Attachment The nailing or attach new sheathing la id at approximately a 45-degree angle
ment of the existing sheathing to the supporting fram and connected (O the existing framing members.
íng may be increased. Nailing or attachment to the
supporting framing should be íncreased and blocking 8.5.2.3.3 New Double-Diagonal Sheathing New
ror the díaphragm at the wood structural panel joints double-diagonally sheathed wood diaphragms shalJ
should be added. include diaphragms with new sheathing laid at
For straight-sheathed diaphragms, the increase in approximately a 45-degree angle to the existing fram
shear capacity wilJ be minima!. Double straight ing members with a second layer of sheathing la id at
sheathed diaphragms with minimal nailing in the approximately a 90-degree angle lo the tirst layer,
upper or both layers of sheathing may be enhanced where both layers shall be connected to the framing
significantly by adding new nails or staples to the members.
existing diaphragm. The same is (rue for diaphragms
lhat are single diagonally shealhed, double diagonally 8.5.2.3.4 New Braced Horizontal Diaphragms New
sheathed, or single diagonally shealhed with straight braced horizonlal diaphragms shall inelude a new hori
sheathing or tlooring. zontal [russ system attached to the existing framing at
In sorne cases, increased nailing al the wood the tloor or roof level 01' the building.
structural panel intleld may also be required. Ir the
C8.5.2.3.4 New Braced Horizontal Diaphragms
required shear capacity or stitfness is greater than that
Because new horizontal truss systems wi\l induce new
which can be províded by íncreased attachment, a new
forces on existing framing members, it may be more
overlay on the existing diaphragm may be required (O
economical to design tloor or roof shealhíng as a
provide the desired enhancement.
diaphragm. Thís eliminates the potential need to
strengthen wood members al the compressíon slruts.
8.5.2.3 New Wood Diaphragms
Braced horizontal diaphragms are more feasible whcre
sheathing cannot provide sufl1cient shear capacíty, or
8.5.2.3.1 New Wood Structural Panel Sheathing New
where diaphragm openings reduce the shear capacity of
wood structural panel sheathed diaphragms shall
the diaphragm and additional shear capacity is needed.
inelude new wood structural panels connected to new
framing members, or connected to existing framing
8.5.3 Single Straight Sheathing
members after existing sheathing has been removed.
8.5.3.1 Stiffness
C8.5ol.3.1 New Wood Structural Panel Sheathing
The detlection of straight-sheathed diaphragms
Typically, these consist of wood structural panels
shall be calculated using Eq. 8-3:
such as wood structural panel or oriented strand
board-nailed or stapled to existing framing members ~y v\L/(2G,/) (Eq.8-3)
after existing sheathing has been removed. Different
where
grades and thicknesses of wood structural panels can
be used, depending on the requirements for gravity G" = diaphragm shear stitl'ness from Table 8-2
load support and diaphragm shear capacity. In most (lb/in.);
cases, the panels are placed with the long dimension L = diaphragm span, distance between shear walls or
perpendicular 10 the framing members, and panel collectors (in.);
edges at the ends of the panel s are supported by, and vy = shear per unit length at yield in the direction
nailed to, the framing members. Edges al the sides of under consideration (lb/in.); and
the panels can be blocked or unblocked, depending on ~y = caIculated diaphragm detlection at yield (in.).
the shear capacity and sliffness required in (he new
diaphragm. Wood structural panels can be placed in Properties used to compute diaphragm detlection
various paUerns as shown in the LRFD Manual for and stift'ness shall be based on Section 8.2.2.
Engineered Wood Construction (AF&PA LRFD 1996)
and the NEHRP Recommended Provisions for Seismic C8.5.3.1 Stifftless
Regulations for New Buildings and Other Structures Straight-sheathed diaphragms are characterized by
(BSSC 2000). high tlexibility with a long period 01' vibration. These
diaphragms are suitable for low shear conditions
8.5.2.3.2 New Single-Diagonal Sheathing New single where control of diaphragm detlections is nol needed
diagonally sheathed wood diaphragms shall inelude lo auain lhe desired performance levels.
254
ASCE/SEI 41-06
8.5.3.2 Strellgth sheathed diaphragm, but very liule test data are avail
The expected strength of straight-sheathed able on the stiffness and slrength of Ihese diaphragms.
diaphragms shall be determined in accordance with Both layers of straight sheathing must have sufticient
Section 8.2.2. nailing, and Ihe joints 01' the lop layer must be either
offset or perpendicular to the bonom layer.
C8.5.3.2 Strellgth
The expected capacity of straight-sheathed
8.5.4.2 Strength
diaphragms is dependent on the size, number, and
The expected slrenglh 01' double straight-sheathed
spacing belween the nails at each shealhing board, and
diaphragms shall be determined in accordance with
the spacing of Ihe supporting framing members. The
SeclÍon 8.2.2.
shear capacily of straight-sheathed diaphragms can be
calculated using the nail-couple method. See Guide
Unes lor the Design ol Horizontal Wood Diaphragms, C8.5.4.2 Strength
ATC-7 (ATC 1981) for a discussion of calculating the The strenglh and stiffness 01' double straight
shear capacily of slraight-sheathed diaphragms. sheathed diaphragms is highly dependenL on !he nail
ing 01' Ihe upper layer 01' sheathing. If Ihe upper layer
8.5.3.3 Acceptance Criterio has mínimal nailing, the íncrease in strenglh and sliff
For linear procedures, m-1'actors for use wilh ness over a single straighl-sheathed diaphragm may be
deformatíon-controlled actions shall be taken from slighl. Ir the upper layer 01' sheathing has nailing simi
Table 8-3. For nonlínear procedures, the coordinates of lar 10 that of the lower layer 01' sheathing, ¡he increase
!he generalized force-deformation relation, described in strenglh and stiffness will be signiticant.
by Fig. 8-1, and deformation acceptance criteria shall
be taken 1'rom Table 8-4. 8.5.4.3 Acceptance Criterio
For linear procedures, m-factors for use with
C8.5.3.3 Acceptance Criteria deformation-conlrolled actions shall be taken from
Deformation acceptance criteria willlargely Table 8-3. For nonlinear procedures, Ihe coordinates of
depend on the allowable de1'ormations for other struc lhe generalízed force-deformation relarion, described
tural and nonstruclUral components and elements Ihal by Fig. 8-1, and deformalion acceplance críteria shall
are lalerally supported by the diaphragm. Allowable be taken from Table 8-4.
deformalions must also be consislent wilh lhe permis
sible damage slate 01' lhe diaphragm.
8.5.4.4 Connections
8.5.3.4 Conlleclions Connections between diaphragms and shear walls
Connections between diaphragms and shear walls and other vertical elements shall be considered in
and olher vertical elements shall be considered in accordance with SeclÍon 8.5.1.
accordance with SeclÍon 8.5.1.
8.5.5 Single Diagonal Sheathing
C8.5.3.4 Connections
The load capacÍly of conneclions between 8.5.5.1 St~ness
diaphragms and shear walls or other vertical elements, The deflection of single diagonal1y sheathed dia
as well as diaphragm chords and shear collectors, is phragms shall be calculated using Eq. 8-3. Properties
critica!. used 10 compute diaphragm deflection and sliffness
shall be based on SeclÍon 8.2.2.
8.5.4 Double Straight Sheathing
C8.5.';.1 Stttrness
8.5.4.1 Stttrness
Single diagonally sheathed diaphragms are signif
The denection of double straight-sheathed dia
ieantly stiffer Ihan straight-shealhed diaphragms, but
phragms shall be calculated using Eq. 8-3. Properties
are still quite flexible.
used to compute diaphragm deflection and stiffness
shalI be based on Seclion 8.2.2.
8.5.5.2 Strength
C8.5.4.1 Stttrness The expected strength for diagonally sheathed
The double-sheathed syslem will provide a signif wood diaphragms wilh chords shall be determined in
icant increase in sli1'fness over a single straight accordance with Section 8.2.2.
255
SEISMIC REHABILlTATION OF EXlSTING BlIILDINGS
256
ASCFlSEI41-06
single diagonally sheathed diaphragms impose on the Alteroatively, a more rigorous calculadon 01'
chords at the ends of the diaphragm. As a result, the diaphragm det1ection based on rational engineering
bending capacity of the end chords does not have an principIes shall be permitted.
effect on the shear capacity and stiffness of the The detlection of blocked and chorded wood
diaphragm. structural panel diaphragms with variable nailing
across the diaphragm length shall be determined using
8.5.7.3 Acceptance Criteria Eq.8-5:
For linear procedures, m-factors for use with
deformatÍon-controlled actions shalI be taken from á y = 5vyLl/(8EAb) + vyL/(4Gt)
Table 8-3. For non linear procedures, the coordinates of + 0.376Le n + ';i,(á e X}/(2b) (Eq.8-5)
the generalized force-deformation, described by
Fig. 8-1, and deformation acceptance criteria shalI be Alternatively, a more rigorous calculation of
taken from Table 8-4. diaphragm detlection based on rational engineering
principies shall be permitted.
8.5.7.4 Connections The det1ection of unblocked diaphragms shall be
Conneclions between diaphragms and shear walls calculated using Eq. 8-3. Properties used lo compute
and other vertical elements shall be considered in diaphragm detlection and stiffness shall be based on
accordance with Section 8.5.1. SectÍon 8.2.2.
257
SEISMIC REHABILlTATION OF EXISTING BUILDINGS
(AF&PA ASD 200 1) and Design of Wood Structures by Fig.. 8-1, and deformation acceptance criteria shall
(Breyer el al. 1999). be taken from Table 8-4.
258
ASeE/S El 41-06
8.5.10 Wood StructuraJ Panel Overlays on Existing inelude friction or end-bearing piles Ihat resist only
Wood Structural Panel Sheatbing vertÍcalloads.
259
SEISMIC REHABIUTATION OF EXISTING BUILDlNGS
Flexure and axial loads in wood piles shall be Knee-braced trames produce moment-resisting
considered deformation-controlled. The m-factors shall joints by the addition of diagonal members between
be taken from Table 8-3. columns and beams. The resuIting "semi-rigid" frame
Wood footings shall be thoroughly investigated resists lateral loads. The moment-resisting capacity of
for the presence of deteríoration. Acceptability of soils knee-braced frames varies widely. The controlling part
below wood foolings shall be delermined in accor of the assembly is usually the connection; however,
dance with Chapter 4. bending of members can be the controlling feature of
Component and connection strength of pole struc sorne trames. Once the capacity of the connection is
tures shall be based on Section 8.2. Pole structures determined, members can be checked and the capacity
shall be modeled as cantilever elements and analyzed of the frame can be determined by statics. Particular
in accordance with Chapter 3. attenLion should be given to the beam-column connec
F1exure and axialloads in pole structures shall be tion. Additional tensile forces may be developed in
considered deformation-controlled. The m-factors shall this connection due to knee-brace action under vertical
be taken from Table 8-3. Where concenlrically braced loads.
diagonals are added to enhance me capacity 01' the Similar to knee-braced frames, the connections of
pole structure, reduced m-factors taken from Table 8-3 rods to timber tramíng wiIJ usually govern the capac
shall be used. ity oí' the rod-braced rrame. Typically, the rods act
only in tension. Once the capacity of the connection is
C8.6.2 Analysis, Strength, and Acceptance Criteria determined, the capacity 01' the frame can be deter
oC Wood FOllndations mined by statics.
The strength of the components, elements, and Braced horizontal diaphragms are described in
connections of a pole structure are the same as for a Section 8.5.2.1.7.
conventional structure.
260
ASeE/SEI 41-06
actíons shall be taken from Table 8-3 1'or component and passive systems, amI tuned mass and Iiquid
actions listed. The m-factors for deformatíon dampers, is provided in this chapter.
controlled component actions not indudOO in Special seismic protective syslems should be eval
Table 8-3 shall be established in accordance with uatOO as possible rehabilitation slrategies based on the
Section 2.8. For non linear procOOures, coordinates of Rehabilitation Objectives establishOO for (he building.
the generalízed force-deformation relation described Seismic isolation and energy dissipation systems
by Hg. 8-1, and deformation acceptance crÍlería shall are viable design strategies that have already been
be taken from Table 8-4. used for seismic rehabilitation of a number of build
ings. Other special seismic prolective systems
CS.7.l.3 Acceptance Critería including active control, hybrid combinations of active
DefOlmalion acceptance crÍleria will largely and passive energy devices, and tunOO mass and liquid
depend on the allowable deformalions for olher stmc dampers-may also provide practical solutions in lhe
tural and nonstructural componenls that are supported near fulure. These systems are similar in that they
by the elemen!. Allowable deformations mus! also be enhance performance during an earlhquake by modi1'y
consistenl with the desired performance level. AClions ing the building's response characteristics.
on connection types Iha! do not appear in Table 8-3 Seismic isolation and energy dissipation systems
(e.g., truss plates) are force-controlled. will not be appropriate design strategies for most
buildings, particularly buildings that have only
LimitOO Rehabilitation Objectives. In general, these
9.0 SEISMIC ISOLATION AND ENERGY
systems will be most applicable to [he rehabilitation of
D1SSIPATION
buildings whose owners desire superior earthquake
performance and can afford the special costs assocí
atoo with the design, fabrication, and installation of
9.1 SCOPE
seismic isolators and/or energy dissipalion devices.
These costs are typically otfset by Ihe reduced need
Thís chapter sets forth requirements for the Systemalic
1'or stiffening and strengthening measures Ihat would
Rehabililation of buildings using seismic isolation and
otherwise be required to meet Rehabilitation
energy dissipation syslems. Section 9.2 provides
ObjeclÍves.
analysis and design crileria 1'or seismic isolation sys
Seismic isolation and energy dissipation systems
tems. Section 9.3 provides analysis and design criteria
are relatively new and sophisticaled concepts thal
1'01' passive energy dissipation systems.
require more extensive design and detailed analysis
Components and elements in buildings wilh seis
Ihan do most conventional rehabilitation schemes.
mic isolalion and energy dissipation systems shall also
SimiJarly, design (peer) review is required for aU reha
comply with lhe requiremenls of Chapters J through
bilitation schemes Ihat use eÍlher seismic isolation or
8 and 11 of this standard, unless moditiOO by lhe
energy dissipation systems.
requirements of this chapter.
Seismic isolation and energy dissipation systems
include a wide variety of concepls and devices. In
C9.1 SCOPE most cases, these systems and devices will be imple
mented wÍlh sorne additional conventional strengthen
The basic form and formulation of requirements for ing of the stmcture; in aH cases they will require
seismic isolation and energy dissipalion systems have evaluation of existing building components. As such,
been established and coordinated with the Rehabili Ihis chapter supplements the requirements of other
talion Objectives, target Building Performance Levels, chapters of Ihis document with additional criteria and
and seismic ground shaking hazard crileria of Chap methods of analysis that are appropriate for buildings
ter 1 and the linear and non linear procOOures 01' rehabilitated with seismic isolators and/or energy di s
Chapter 3. sipation devices.
Críteria for modeling the stitfness, strength, and Seismic isolation is increasingly being considered
deformation capacities of conventional structural com for historic buildings thal are free-standing and have a
ponents of buildings with seismic isolation or energy basement or bonom space of no particular historic sig
dissipation systems are given in Chapters 5 through nificance. In selecting such a solution, special consid
8 and Chapter 10. eration should be given to the possibilíty that historic
Limited guidance for other special seismic sys or archaeological resources may be present al the site.
tems, including active control systems, hybrid active Ir historic or archaeological resources are present al
261
SEISMIC REHABILJTATION OF EXISTING BUILDINGS
the sile, the guidance of lhe State Historie Preservation Rehabililalion Objectives established for lhe building
Ofticer should be obtained in a timeIy manner. (Chapler 2). Whether a special seismic syslem is found
Isolation is al so often considered ror essential facili lo be the "correct" design strategy for building
ties, to protect valuable conLents, and on buildings rehabilitation wíll depend primarily on lhe perform
wilh a complete but insulTicienLly sLrong lateral ance required at the specified level 01' earthquake
force-resisting syslem. demando In general, special seismic syslems will be
Conceptually, isolation reduces response of the found lo be more attractive as a rehabililalion slralegy
superstructure by "decoupling" the building from the for buildings lhat have more stringent Rehabilitalion
ground. Typical isolation systems reduce 1'orces trans Objeclives (i.e., higher levels of performance and more
miued lo the superstructure by lengthening the period severe levels of earthquake demand). Table C9-1 pro
of !he building and adding some amount of damping. vides some simple guidance on lhe performance levels
Added damping is an inherent property of most isola ror which isolalion and energy dissipation systems
tors, but may also be provided by supplemenlal energy should be considered as possible design strategies for
dissipation devices inslalled across Ihe isolation inter building rehabililalion.
face. Under favorable conditions, the isolation system Table C9-1 suggesLs thal isolation systems should
reduces drifL in the superstructure by a factor of at be considered for achieving the Immediate Occupancy
leasl Iwo-and sometimes by as much as factor 01' SlruClural Performance Level and the Operalional
tive-from !hat which would occur if the building Nonslructural Performance Leve!. Conversely, isola
were not isolated. Accelerations are also reduced in lion will tikely not be an appropriale design stralegy
the structure, although lhe amounl 01' reduction for achieving lhe Collapse Prevention Slruclural
depends on the force-detlection characteristics 01' the Performance Leve\. In general, isolalÍon systems pro
isolators and may not be as signiticant as the reduclion vide signiticant protection Lo the building structure,
of drift. Reduction of drift in lhe superstructure pro nonstruclural components, and contents, bUI at a cost
tects structural components and elemenls, as well as lhat preeludes practical application where the budget
nonstruclural componenls sensitive to drift-induced and Rehabililalion Objectives are modesl.
damage. ReduClion of acceleralion protects nonslruc Energy dissipalion syslems should be considered
tural components that are sensilive 10 acceleralÍon in a somewhal broader conlext lhan isolation systems.
induced damage. For lhe taller buildings (where isolation syslems may
Passive energy dissipation devices add damping nOI be feasible), energy dissipalion systems should be
(and sometimes stiffness) to the building. A wide vari considered as a design strategy where performance
ety 01' passive energy dissipalion devices are available, goals inelude the Damage Control Performance
incIuding t1uid viscous dampers, viscoelastic materi Range. Convcrsely, certain energy dissipation devices
als, and hysteretic devices. Ideally, energy dissipalíon are quite economical and mighl be practical for per
devices dampen earthquake excitation 01' the slructure formance goal s lhat address only Limited Safely. In
that would otherwise cause higher levels of response general, however, energy dissipation syslems are more
and damage to componenls of the building. Under Iikely lo be an appropriale design slralegy where Ihe
favorable conditions, energy dissipation devices reduce desired Structural Performance Level is Life SafelY, or
drin of Ihe struclure by a factor of about IWO lO lhree
(ir no stirfness is added) and by larger faclors if lhe Table C9-1. Applicability oC Isolation and Energy
devices also add stitl"ness to Ihe slructure. Energy Dissipation Systems
dissipation devices will also reduce force in the
structure-provided the slruclure is responding
Performance Pel1"ormance Energy
elasticalIy-but would not be expected 10 reduce force
Level Range Isolation Dissipation
in struclures !hat are responding beyond yield.
Active control systems sense and resisl building Operational Damage Very Likely Limited
motion, either by applying external force or by modi Control
fying structural properlies of active components (e.g., lmmediate Likely Likely
so-called smarl braces). Tuned mass or Iiquid dampers Occupancy
modify properties and add damping 10 key building Life Limited Limited Likely
modes of vibration. Safety Safety
Special seismic systems, such as isolalion or
Collapse Not Practical Limiled
energy dissipalion systems, should be considered early
Prevention
in the design process and be based on lhe
262
ASCFlSEJ 41-06
perhaps Immediate Occupancy. Other objectives may a target Building Performance Level of Immediate
also influence lhe decision to use energy dissipation Occupancy or beUer.
devices, since these devices can also be useful for con A number of buildings rehabililated wilh seismic
trol of building response due to small earthquakes, isolators have becn historie. For these projects, seismic
wind, or mechanical loads. isolation reduced the extent and intrusion of seismic
moditications on the hístorical fabric of the building
that would otherwise be required to meet desired per
9.2 SEISMIC 1S0LATlON SYSTEMS formance levels.
263
SEISMIC REHABlLlTATION OF EXISTING BUILDlNGS
C9.2.2.2.1 Elastomeric lsolators Elastomeric bearings G shear modulus of rubber (typicaJly computed al
represent a common means for introducing tlexibility shear strain of 0.5); and
¡nto an isolated structure. They consist of thin layers A a factor larger lhan uníly.
of natural rubber that are vulcanized and bonded to
Typically,fL is !.IS, and the elaslic sliffness
steel pI ates. Natural rubber exhibits a complex
ranges between 6.5 lo 10 times the post-yield stitfness.
mechanical behavior, which can be described simply
The behavior of lead-rubber bearings may be rep
as a combination of viscoelastic and hysteretic behav
resenled by a bilinear hyslerelic model. Computer pro
joro Low-damping natural rubber bearings exhibit
grams 3D-BASlS (Nagarajaiah el al. 1991; Reinhorn el
essentially Iinearly elastic and Iinearly viscous behav
al. 1994; Tsopelas el al. 1994b), and ETABS, Version 8
ior al large shear strains. The etfective damping is
(CSI, 2003) have the capabilily of modeling hysleretic
lypically less Ihan or equal lo 0.07 for shear strains in
behavior for isolators. These models typícally require
the range of O to 2.0.
definition 01' three parameters, namely, Ihe post-yield
Lead-rubber bearings are generally construcled of
sliffness kp, Ihe yield force Fr. and the yield displace
low-damping natural rubber with a preformed central
menl Dy. For lead-rubber bearings in which Ihe elastic
hole into which alead core is press-tiued. Under lat
stiffness is approximalely equal lo 6.5 kp, lhe yield di s
eral deformation, lhe lead core deforms in almost pure
placement can be estimated as:
shear, yields at low levels of stress (approximately 8 to
10 MPa in shear al normal temperature), and produces
hysleretic behavior that is stable over many cycles. D
y
=-ª
S.Sk l
,
(Eq. C9-3)
Unlike mild steel, lead recryslaIlizes at normal
temperalure (about 20 OC), so that repealed yielding The yield force is then given by:
does nol cause fatigue failure. Lead-rubber bearings Fl' = Q + kl'Dy (Eg. C9-4)
generally exhibil characterislÍc slrength Ihal ensures
rigidily under service loads. Figure C9-1 shows an ide High-damping rubber bearings are made 01' spe
alized force--dísplacemem relalion ol' a lead-rubber cial1y compounded rubber that exhibits effective
bearing. The characleristic slrength, Q, is related to Ihe damping between 0.10 and 0.20 of critica\. The
lead plug area, Al" and the shear yield stress oflead, ay/': increase in effective damping of high-damping rubber
is achíeved by (he addition of chemical compounds
(Eq. C9-1) Ihal may also affect other mechanical properties 01'
The post-yield stitfness, kp, is typically higher rubber. Figure C9-2 shows representative force
Ihan the shear stitfness of the bearing withoul the lead dísplacement loops 01' a hígh-damping rubber bearing
core: under scragged conditions.
Scragging is the process of subjecting an
(Eq. C9-2) elastomeric bearing to one or more cycles of large
amplitude displacemcnt. The scragging process modi
where
0.1 r--------r-----------.
Al bonded rubber area;
Pressure =7.0 MPa
~t total rubber thíckness; Frequency =0.1 Hz
Scragged
Force J
264
ASCFlSEI41-06
265
SEISMIC REHABILlTATION OF EXISTING BUILDlNGS
with the corresponding experimental hysteresis loop. Considering an elastomeric bearing design with
However, at lower peak shear strain the analylical S = 15, Gel! = ) MPa, and K = 2,000 MPa, the ralio
loops have a constant characteristic strength, whereas 01' vertical stiffness (Eq. C9-9) to effective horizontal
the experimentalloops have a characterislic strength slif1'ness (Eq. C9-8) is approximalely equal lo 700.
dependent on the shear strain amplitude. Nevertheless, Thus, the vertical period of vibralion of a structure on
the analytical model willlikely produce acceptable elastomeric isolation bearings will be about 26 times
results where the design parameters are based on the (i.e.,V70('l) less than the horizontal period, on the
mechanical properties at a strain corresponding lO the order of 0.1 seco This value of vertical period provides
design displacement. potential for amplitication of the vertical ground accel
Elastomeric bearings have finite vertical stitfness eration by the isolation system. The primary effect of
that affects the vertical response of the isolated struc this amplification is lo change the vertical load on the
ture. The vertical slitfness of an elastomeric bearing bearings. which may need lo be considered for certain
may be obtained from design applications.
Another consideration in lhe design of seismically
k = Ec A (Eq. C9-9) isolated struclures wilh e1astomeric bearings is reduc
v '2:.t
tion in heighl 01' a bearing with increasing lateral
where Ec is the compression modulus. Although a deformation (Kelly 1993). While this reduction of
number of approximate empirical relations have been heighl is typical1y small, it may be important where
proposed for the calculation of Ihe compression modu elastomeric bearings are combined with other isolation
lus, the correcl expression for circular bearings is: components that are vertically rigid (such as sliding
e
I
E = ( --+
6GenS 2
-4
3K
)-1 (Eq. C9-10)
bearings). In addítion, incompatibilities in vertical dis
placements may lead to a redistribution 01' loads.
(Kelly 1993) where K is the bulk modulus (Iypically 9.2.2.2.2 Sliding lsolators Force--deformalion response
assumed lo have a value of 2,000 MPa) and S is the properlies shall be eslablished ror sliding isolators,
shape factor, which is defined as the ratio 01' the taking into consideration conlact pressure, rate of
loaded area lo the bonded perimeler of a single rubber loading or veJocity, bilaleral deformation, temperature,
layer. For a circular bearing oí' bonded diameter ~ and contamination, and other environmenlal loads and
rubber layer thickness t, the shape factor is given by: aging effects over the design life of the isolator.
Mechanical characterislics for use in mathemati
S= ~ (Eq. C9-1l) cal models shall be based on analysis and available
4t material lest properties. Verificalion of isolalor proper
Seismic elastomeric bearings are generally designed lÍes used for design shall be based on tesIS of isolator
with a ¡arge shape factor, Iypically 12 lo 20. prolotypes in accordance with Section 9.2.9.
266
ASCE/SEI41-06
JL., = coefficienl of sliding friclion; Such an arrangement typically results in a very low
. N = normal load on bearing; and coeft1cient of fTiction.
sgn(V) = sign of sliding velocity vector; + l or -l. For bearings with large contact area, and in the
absence of liquid lubricants, the coefticient of friction
The normal load consists oí' the gravily load, W, depends on a number of parameters, of which the
the effect 01' vertical ground acceleraLion, V., and [he three most important are lhe composition of Ihe sJiding
addilional seismic load due lo overlurning momenl, P,: interface, bearing pressure, and velocity of sliding. For
interfaces composed of polished stainless sleel in con
tacl with PIFE 01' PTFE-based composites, the coeftl
(Eq. C9-13) cienl of sliding friction may be described by:
R
/
Ro W
~:
Wfan<l'
Displacement
267
SEISMIC REHABILlTATION OF EXISTING BUILDlNGS
0.06' '
ó ú T,ol. al ue, eerUhoy (t 992-199a)
J]lnrrlr~"~~~)fm~
Q)
'O 0.04 '~---~f '
;:
Q)
mm
O 0.02
O
0.00
O 50 1 00 150 200 250 300
Bearing pressure (MPa)
FIGURE C9-6. Coefficient oC Friction oC PTFE-Based Composite in Contact
with PoJished Stainless Steel at Normal Temperature.
coefflcients 1m"" /LB' and Imin 01' a PTl-''''E-based compos used in multiple analyses of the model to determine
ile material in contact with polished stainless steel at the range and sensitivity of response lO design
normal temperature. These data were compiled from parameters.
testing of bearings ín four differenl testíng programs
(Soong and Constantinou 1994). 9.2.2.3.2 Linear Models The restoring force, F, oí' an
Combined elastomeríc-sliding iso)ation systems isolator shall be calculated as lhe product of effective
have been used in buildings in lhe Uniled States. stiffness, k,1j , and response displacement, D:
Japanese engíneers have also used elastomeric bear
ings in combination with mild steel components thal (Eq. 9- I)
are designed lo yield in strong earthquakes and The effective stiffness, k en , of an isolator shall be
enhance the energy dissipation capability 01' the isola calculated from test dala using Eq. 9-12. The area
tion system (Kelly 1988). These mild steel compo encJosed by the force-displacemenl hysteresis loop
nenls exhibít eilher elasto-plaslic behavior or biJinear shall be used to calculate the eftective damping, {jeJJ' of
hysteretic behavior with low post-yielding sliffness. an isolator using Eq. 9-13. Etfective stiffness and
Moreover, Iluid viscous energy dissipation devices effective damping shall be evaluated at alI response
have been used in combinalion with elastomeric bear displacements 01' design interest.
ings. The behavior 01' Iluid viscous devices is
described in Section 9.3.3.2.3. C9.2.2.3.2 Linear Models Linear procedures use effec
Hybrid seismic isolation syslems composed 01' tive stiffness, keff , and effective damping, {jeD' to char
elastomeric and sJiding bearings should be mode)ed acterizc nonlinear properties 01' isolators.
taking into accounl the likely significant ditTerences in For linear procedures [see FEMA 274, Sec
the relationships between vertical displacement as a tion C9.2.3 (FEMA ]997)], the seismic isolation sys
function of horizontal displacement. The use of e1as tem can be represenled by an equivalent Iinearly elas
tomeric and sliding isolators in c10se proximity lo one tic model. The force in a seismic isolation device is
another under verlicalIy stiff structural framing ele calculaled as:
ments (e.g., reinforced concrete shear walls) may be
problematic and could result in significant redistribu (Eq. C9-16)
tions of gravity loads. where all terms are as defined in Section 9.2.2.3.2 of
9.2.2.3 Modeling ollsolators this standard. The ef1'ective stiffness 01' the seismic
isolation device may be calculated from test data as
9.2.2.3. J Genera/U the mechanical characteristics of a follows:
seismic isolator are dependent on axial load (due to
gravity, earthquake overturning effects, and vertical
IF+I + Irl (Eq. C9-17)
earthquake shaking), rate 01' loading (ve)ocity), bilat
k eff = la+1 + la-I
eral deformation, temperature, or agíng, then upper- and Figure C9-7 iIIustrates the physical significance of the
lower-bound values of stitfness and damping shall be effective stiffness.
268
ASCFJSEl 41-06
269
SElSMIC REHABILITATION OF EXISTING BUILDlNGS
lhese propenies, lhe CharaClerislic slrenglh Q (see Isolation devices that exhibit viscoelastic behavior
Fig. C9-7) is needed. For sliding isolators, Q can be as shown in Fig. C9-7 should be modeled as linearly
laken as equal tofm""No wherefmax is determined al elaslic components wilh effective stiffness kef! as deler
the bearing pressure corresponding to load Ne. For mined by Eq. C9-21.
example, for a sliding bearing wÍ(h spherical slid
ing surfacc of radius Ro (see Fig. C9-5), the effec
9.2.2.4Isolation System and Superstructure
tive stiffness and area of the loop at the design
Modeling
displacement D are:
k'ef! (_1
Ro + fnuJX)N .
D (
(Eq. C921
- )
9.2.2.4.1 General Mathematical models of the isolated
building, including Ihe isolation system, the lateral
force-resisting system of the superstructure, other
Loop Area = 4f""uNeD (Eq. C9-22) structural components and e1ements, and connections
between the isolation system and the structure, shall
9.2.2.3.3 Nonlinear Models Thc nonlinear force mee! the requirements of Chapters 2 and 3 and
detlecLÍon properties of isolators shall be explicitly Sections 9.2.2.4.2 and 9.2.2.4.3.
modcled if nonlincar procedures are used.
The inelastic (hysteretic) response of the isolators 9.2.2.4.2 Isolation System Model The isolation system
shall represent damping. Additional viscous damping shall be modeled using deformation characteristics
shall not be incJuded in the model unJess supported by developed and verified by test in accordance with the
rate-dependent tests of isolators. requirements 01" Section 9.2.9.
The isolation system shall be modeled wilh sufti
C9. 2, 2. 3.3 Nonlinear Models For dynamic nonlinear ciem detail to:
time-history analysis, the seismic isolation compo
l. Accounl for the spatíal distribution of isolator units;
nents should be explicitly modeled. FEMA 274
2. Calculate translation, in both horizontal directions,
Sections C9.2.2.2 through C9.2.2.4 (FEMA 1997)
and torsion of the slruclUre aboye the isolation
present relevant information. Where uncertaimies
interface, considering Ihe most disadvantageous
exist, and where aspects of behavior cannot be mod
location of mass eccentricity;
eled, multiple analyses should be performed in order
3. Assess overLUrning/uplift forces on individual
to establish bounds on the dynamic response.
isolators;
For simplitied nonlinear analysis, each seismic
4. Account ror the effects of vertical load, bilateral
isolation component can be m<}deled by an appropriale
load, and/or Ihe rate of loading, if the force deflec
rate-independent hysterelic model. Elastomeric bear
tion propcrties of the isolation system are depend
ings may be modclcd as bilinear hysleretic compo
ent on one or more of these factors.
nents as described in FEMA 274, Section C9.2.2.2.
5. Assess force s due lo P-D momenls; and
Sliding bearings may also be modeled as bilinear hys
6. Account I"or non linear components. Isolation sys
teretic components wilh characlerislic strength (see
tems with nonlinear components inelude systems
Fig. C9-5) given by
that do no! me el Ihe criteria of Section 9.2.3.3.1,
(Eq. C9-23) Item 2.
where N c is determined by either Eq. C9-19 or C9-20,
9.2.2.4.3 Superstructure Model The maximum di s
and fnwx is the coetlicient of sliding frÍction at the
placement of each tloor, the total design displacement,
appropriate sliding velocity. The posl-yield stitlness
can then be determined as: and Ihe total maximum displacement across the isola
tion syslem shall be calculaled using a model 01"
the isolated building that incorporates the force
(Eq. C9-24)
deformation characterislics oí" nonlinear components.
Calculation 01' design forces and displacements in
where R is as defined in FEMA 274 Section primary componenls 01' the lateral-force-resisting sys
C9.2.2,2.B. The yield displacement Dy in a bilinear
lem using linearly eJastic mode\s of Ihe isolated struc
hysterelic model of a sliding bearing should be very
ture shall be permitted if both of Ihe following criteria
small, perhaps on the order of 2 mm. Alternatively, a
are met:
bi\inear hysteretic model for sliding bearings may
be detined lo ha ve an elastÍC stifl"ness that is al leasl ]. Pseudo-elastic properties assumed rol' nonlinear
] 00 times larger than lhe post-yield stiffness, kp. isolation system components are based on the
270
ASeE/SEI 41-06
maximum effective stiffness of the isolalion 9.2.3.2.1 User-Specified Design Earthquake For Ihe
syslem; and Design Earthquake, the following ground shaking cri
2. The lateral-force-resisling system remains linearly teria shalI be established:
elastic for Ihe earthquake demand level of interesl.
l. Short-period spectral response acceleration parame
A laleral-force-resisting system Ihal meelS both of ter, Sxs and spectral response acceleration parame
the following criteria may be cIassified as linearly ter at 1.0 second, Sx/. in accordance with
elastic: Seclion 1.6.1.4;
2. Five-percent-damped response spectrum 01' the
1. For all deformation-controlled actions, Eq. 3-20 is
design earthquake (where a response spectrum is
salisfied usíng an m-factor equal to 1.0; and
required for linear procedures by Section 9.2.3.3.2,
2. For alJ force-controlled actions, Eq. 3-21 is
or to detine acceleration time histories); and
salísfied.
3. At least three acceleration time histories compatible
9.2.3 General Criteria for Seismic Isolation with the design earthquake speclrum (whe!"e accel
Design eration time histories are required for nonlinear
procedures by Section 9.2.3.3.3).
9.2.3.1 General
9.2.3.2.2 Maximum Considered Earthquake For the
The designo analysis, and testing of (he isolation
BSE-2, the following ground shaking criteria shall be
system shall be based on the requirements of Ihis
established:
seclion.
l. Short period spectral response acceleration parame
C9.2.3.1 General ter, Sxs> and spectral response accelera(ion parame
eri(eria for the seismic isolation of buildings are ter at 1.0 sec, Sx/, in accordance with
divided into two seclions: Section 1.6.1.4.
Rehabilitation of the building; and 2. Five-percent-damped site-specific response
Design. analysis, and teslíng of the isolation speclrum of the BSE-2 (where a response spec
system. tmm is required for linear procedures by Sec
tion 9.2.3.3.2. or to define acceleration time
9.2.3.1./ Stability of the Isolation System The stability histories); and
of the vertical load-carrying components of the isola 3. At Jeast three acceJeration time histories compatible
tion system shall be verified by analysis and test, as with the BSE-2 spectrum (where acceleration time
required by Section 9.2.9, for a lateral displacement histories are required for nonlinear procedures by
equal to the total maximum displacement computed in Section 9.2.3.3.3).
accordance wilh Section 9.2.4.3.5 or Section 9.2.5.1.2.
or for the maximum displacement allowed by dis 9.2.3.3 Selection 01 Analysis Procedure
placement-restraint devices, if such devices are part of
the isolatÍon system. 9.2.3.3.1 Linear Procedures Linear procedures shall be
permitted for design 01' seismically isolated buildings,
9.2.3.1.2 Configuration Requirements The isolated provided Ihe following criteria are met:
building shall be cIassified as regular or irregular,
as defined in Section 2.4.1.1, based on the structural l. The building is located on Soil Profile Type A, B,
configuration of the structure aboye the isolation e, or D; or E if SI 2: 0.6 for BSE-2;
system. 2. The isolation system meets all 01' the following
criteria:
9.2.3.2 Ground Shaking Criterio 2.1. The effective stiffness 01' the isoJation system
Ground shaking crileria for Ihe Design at the design displacement is greater Ihan one
Earthquake and the Maximum eonsidered Earthquake third of the effective stiffness al 20% of the
shall be established in accordance with Section 1.6 as design displacement;
modified by this section. The design Earthquake 2.2. The ¡solation system is capable of producing a
Hazard Level shall be user-specified and shall be per restoring force as specified in Section
mitted to be chosen equal 10 the BSE-l Earthquake 9.2.7.2.4;
Hazard Leve!. The Maximum eonsidered Earthquake 2.3. The isolation syslem has force-defleclion
shall be taken equal lo the BSE-2 Earthquake Hazard properties that are independent of (he rate of
Level. loading;
271
SEISMIC REHABILlTATION OF EXISTING BUILDINGS
2.4. The isolation system has force-detlection Response Spectrum Analysis is recommended for
properties that are independent of vertical load design of isolated structures that have either (1) a taH
and bilateral load; or olherwise flexible superstructure, or (2) an irregular
2.5. Where considering analysis procedures, for the superstructure. For most buildings, Response
BSE-2, the isolation system does not limit Spectrum Analysis will not predict significantly ditler
BSE-2 displacement to less than the ratio of eOl displacements of me isolation system than those
the design spectral response acceleration at calculated by prescriptive formulas, provided bolh cal
one second (SXI) for the BSE-2 to that for the culations are based on the same effective stitl'ness and
Design Earthquake limes the total design dis damping properties of the isolation system. The real
placement; and benefit of Response Spectrum Analysis is not in the
3. The structure aboye the isolation system exhibits prediction of isolation system response bul, rather, in
global elastic behavior for the earthquake motÍons the calculation and distribution of forces in the super
under consideration. struclure. Response Speclrum Analysis permÍls the use
of more detailed models of the superstructure that
9.2.3.3.2 Response Spectrum Analysis Response spec better estimate torces and deformations of components
trum analysis shalJ be used ror design of seismicaJIy and elements considering tlexibility and irregularity of
isolated buildings that meet any of the folJowing the structural system.
criteria: Nonlinear procedures inelude the Nonlinear Static
Procedure (NSP) and the Nonlinear Dynamic
1. The building is over 65 ft (19.8 m) in height;
Procedure (NDP). The NSP is a static pushover proee
2. The efrective period of the structure, TM , is greater
dure and the NDP is based on nonlinear time-history
than three seconds;
analysis. The NSP or the NDP is required for isolated
3. The effective period of the isolated structure, TD , is
struclures thal do not have essentiaHy Iinearly elastic
less than or equal to three times the elastic, tixed
superstructures (during BSE-2 demand). In this case,
base period 01' the structure aboye the isolation sys
the superstructure would be modeled with nonlinear
tcm; or
componeOls.
4. The structure aboye the isolation system is irregular
Time-history analysis is required for ísolated
in contiguralion.
structures on very soft soil (i.e., Soil Protile Type E
where shaking is strong, or Soil Profile Type F) that
9.2.3.3.3 Nonlínear Procedures Nonlinear procedures
could shake the building with a large number 01' cycles
shall be used for design of seismic-isolated buildings
of long-period motion, and tor buildings wilh isolation
for which any of the folJowing conditions apply:
systems that are best characterized by non linear mod
l. The structure aboye the isolation system is nonlinear els. Such isolation systems include:
for the earthquake mOlions under consideration; and
J. Systems with more than about 30% eflective damp
2. The isolation system does nol meet all of the crile
ing (beeause high levels of damping can signiti
ria of Section 9.2.3.3.1.
cantly allect higher-mode response of the super
Nonlinear acceleralÍon time-history analysis shaIl structure);
be performed for the design 01' seismically isolated 2. Systems that lack signiticant restoring force
buildings ror which conditions (1) and (2) apply. (beeause these systems may not stay centered dur
ing earthquake shaking);
3. Systems that are expected to exceed lhe sway-space
C9.2.3.3 Selection 01 Analysis Procedure
c1earance with adjacent structures (beeause impaet
Linear procedures inelude prescriptive formulas
wilh adjacenl structures could impose lorge
and Response Spectrum Analysis. Linear procedures
demands on the superstructure); and
based on formulas (similar to the seismic-coefticient
4. Systems Ihat are rate- or load-dependent (because
equation required for design of fixed-base buildings)
their properties will vary during earthquake shaking).
prescribe peak lateral displacement of the isolation
system, and define "minimum" design criteria that For the Iypes of isolation systems described
may be used for design of a very limited class of iso aboye, appropriate nonlinear properties must be used
lated structures (without contirmatory dynamic anal y to model isolators. Linear properties could be used to
ses). These simple formulas are useful for preliminary model the superstructure, províded the superstructure's
design and provide a means of expeditious review of response is essentiaJly línearly elastic for BSE-2
more complex calculations. demand.
272
AseE/SEI 41-06
The resLrictions placed on Lhe use of linear proce 9.2.4.3.3 Maximum Displacement The maximum dis
dures effecLively suggest Ihat nonlinear procedures be placement of lhe isolation system, D M , in the most crit
used for virtually all isolated buildings. However, ical dírection of horizontal response shall be ca\culated
lower-bound Iimits on isolation system design dis in accordance wilh Eq. 9-4:
placement and force are specified by this standard as a
percentage of the demand prescribed by the linear for D
M
= [~J
411 2
SXJ™
BMI
(Eq.9-4)
mulas, even where dynamic analysis is used as the
basis for designo These lower-bound Iimits on key where SXI is evaluated for the BSE-2.
design attributes ensure consistency in lhe design of
isolated struclures and serve as a "safety nel" againsl 9.2.4.3.4 Effective Period at the Maximum
gross under designo J)isplacement The effective period, TM' of the isolated
building at the maximum displacement shall be deter
9.2.4 Linear Procedures mined using the deformatíon characteristics of the Íso
lation system in accordance with Eq. 9-5:
9.2.4.1 General
Seismically isolaled buíldings for whieh linear TM 211 ~ W
KMmíng
(Eq.9-5)
analysis procedures are selected based on the criteria
01' Section 9.2.3.3 shalJ be designed and constructed to
resist the earlhquake displacements and forces speci 9.2.4.3.5 Total Displacement The total design dis
fied in this section, at a minimum. placement, J)m, and lhe total maximum displacement,
D7M , of componenls 01' the isolation system shall
include additional displacement due 10 actual and acci
9.2.4.2 Deforma/iolJ Charac/erislics ofthe Isolalioll
dental torsion calculaled considering the spalíal distri
Syslelll
butíon of the effectíve stiffness of the ísolatíon system
The defollnation characterislics of Ihe isolation
at the design dísplacement and lhe most dísadvanta
system shall be based on tests performed in accor
geous locatíon of mass eccentricity.
dance with Section 9.2.9.
The total design displacemelll, D TD , and the tolal
The defonnation characteristics 01' the isolation
maximum displacement, D TM , of components of an
system shall explicitly incIude Ihe effects of the wind
isolation system with a uniform spalíal dislribulíon of
restraint and tie-down systems, and supplemental
e1'fective stiffness al the design displacement shall be
energy dissipalion devices, if such syslems and
laken as not less Iban that prescribed by Eqs. 9-6
devices are used to meel Ihe design requiremenls of
and 9-7:
Ihis standard.
Dm = DD[ l + Y b2 l:ed 2 ] (Eq. 9-6)
9.2.4.3 Minimum Lateral Displacements
12e
9.2.4.3./ Design Displacement The isolation system DTM DM[ 1 + Y 2
b +d
2J (Eq.9-7)
shaU be designed and constructed to withstand, as a
minimum, lateral earthquake dísplacements that act in A valuc for the total maximum displacement, J)TM,
lhe direction of each of the main horizontal axes 01' the less than the value prescribed by Eq. 9-7, but not less
structure in accordance with Eq. 9-2: than 1.1 times DM , shall be permittcd, provided the
isolation system is shown by calculation to be config
D = [~JSXJTD (Eq.9-2) ured to resisl torsion.
D 411 2 B DJ
where SXI is evaluated for the Design Earthquake. 9.2.4.4 Minimum Lateral Forces
9.2.4.3.2 Effective Period at the Design Displacement 9.2.4.4. J Isolation System and Structural Components
The effeclÍve period, TD , of the isolated building at the and Elements at or below the Isolalion System The
design displacement shall be delermined using lhe ísolation systcm, the foundation, and an other structural
components and e1ements below the isolatíon system
deformation characleristics of the isolalion system in
shall be designed and constructed to withstand a míni
accordance with Eq. 9-3:
mum lateral seísmic force, Vb , prescribed by Eq. 9-8:
IW
TD = 211'V~--- (Eq.9-3) (Eq.9-8)
KDming
273
SEISMIC REHABILlTATlON OF EXISTING BUILDINGS
9.2.4.4.2 Structural Components and Elements above total design displacement and total maximum displace
the Isolation System The components and elements ment shall include simultaneous excitation 01' the
aboye the isolaLion system shall be designed and model by 100% of the most critical direction of
consLructed lO resist a minimum lateral seismic force, ground motion, and not less than 30% 01' the
V" equal to the value of Vb • prescribed by Eq. 9-8. ground motion in the orthogonal axis. The maximum
displacement of the isolation system shalI be calcu
9.2.4.4.3 Limits on V, The value of V, shall be taken as laled as the vector sum 01' the two orthogonal
nolless than the following: displacements.
l. The base shear corresponding to the design wind
load; and 9.2.4.5.4 Scaling ol Resu/ts If the tolal design dis
2. The lateral seismic force required to fully activate placemenl determined by response spectrum analysis
the isolation system factored by 1.5. is found lo be les s Ihan lhe value of DJl) prescribed by
Eq. 9-6, 01' if the lotal maximum displacemenl deter
C9.2.4.4.3 Limits on Vs Examples of lateral seismÍc mined by response spectrum analysis is found to be
torces required to fully actívate the isolation system less than the value of DTM prescribed by Eq. 9-7, then
inelude the yield level of a softening system, the ulti alI response parameters, including component actions
mate capacity 01' a sacríficial wind-restraint system, or and deformations, shall be adjusted by the greatcr 01'
the break-away friction level of a sliding system. the following:
9.2.4.4.4 Vertical Distribution alForce The total force, 1. DmlDesign displacement detcrmined by response
V" shall be dislributed over [he height of [he structure spectrum analysis, or
aboye the isolation interface in accordance with 2. Dn/Maximum displacement detcrmined by
Eq.9-9: response speclrum analysis.
274
ASeE/SEI 41-06
targel displacement, D~, as detíned by Eqs. 9-10 and 9.2.6 Nonstrudural Components
9-11 :
9.2.6.1 General
D'D DD Permanenl nonslruclural componenls and lhe
(Eq.9-1O)
)1 + (~J2 auachmenls lo them shalJ be designed lo resisl seismic
forces and displacemenls as given in lhis seclion and
lhe applicable requirements of Chapler 11.
D'M
- DM
(Eq.9-11) 9.2.6.2 Forees and Displaeements
)1 + (~:Y 9.2.6.2.1 Componellts alld EJements at or above the
where Te is Ihe effective period of Ihe slruclure aboye Isolation Interface NonslruclUral components, or por
lhe isolation inlerface on a tixed base as prescribed by lions lhereof, lhat are al or aboye lhe isolalion inler
Eq. 3-14. The largel displacemenls, D~ and D~, shall face shall be designed to resisl a lolal lateral seismic
be evalualed al a conlrol node Ihal is located al Ihe force equallo lhe maximum dynamic response of lhe
cenler of mass of Ihe tírst tloor aboye lhe isolation elemenl or componenl under consideration.
interface. EXCEPTION: Design of elements of seismically
isolaled slruclures and nonslruclural componenls, or
portions lhereof, lo resisl lhe lotal lateral seismic force
9.2.5.1.3 Lateral Load Pattem lbe pallern of applied
as required for convenlional fixed-base buildings by
laleral load shall be proportional lo lhe dislribulion
Chapler 11, shall be permiued.
of lhe product 01" building mass and lhe detlecled
shape of lhe isolaled mode of response at the largel
9.2.6.2.2 Components and Elements that Cross the
displacement.
Isolation Interface Nonstruclural componenls, or por
tions thereof, thal cross Ihe isolation interface shall be
9.2.5.2 Nonlinear Dynamie Proeedure designed lo wilhstand lhe lOlal maximum (horizontal)
displacemenl and maximum vertical displacemenl of
9.2.5.2.1 General The NDP for seismically isolaled the ¡solalion syslem allhe total maximum (horizonlal)
buildings shalI be based on lhe nonlinear procedure displacement. Components and elements lhat cross the
requiremenls of Section 3.3.4, except thal resuhs shalJ isolalion interface shall not restríet displacemenl of
be scaled for design based on lhe criteria given in lhe lhe isolaled building or olherwise compromise lhe
following seclion. Rehabililalion Objectives of lhe building.
9.2.5.2.2 Scalillg of Results If lhe design displacemenl 9.2.6.2.3 Components and Elements below the
delermined by time-history analysis is less lhan lhe Isolation Interface Nonstructural componenls, or por
D~ value of prescribed by Eq. 9-10, or if lhe maxi lions thereof, lhal are below lhe isolalion interface
mum displacement determined by response spectrum shall be designed and constructed in accordance with
analysis is found lo be less Ihan lhe value of D;f pre lhe requiremenls of Chapler 1].
scribed by Eq. 9-1 ), lhen all response paramelers,
including component actions and deformalions, shall 9.2.7 Detailed System Requirements
be adjusted by lhe greater of lhe following:
9.2.7.1 General
l. D~/Design displacemenl determined by time his The isolation system and the structural system
tory analysis, or shall comply Wilh the detailed syslem requirements
2. D~/Maximum displacement determined by time specified in SeclÍon 9.2.7.2 and 9.2.7.3, respectively.
history analysis.
9.2.7.2 lsolation System
9.2.5.3 Design Ftlrces and Deformatiolls
Components and elements of lhe building shall be 9.2.7.2.1 Environmelltal Conditiolls In addilion to lhe
designed for lhe forces and defOlmalions estimated by requirements for vertical and laleral loads induced
non linear procedures using lhe acceplance criteria of by wind and earthquake, lhe isolation system shall
Seclion 3.4.3.2. be designed with consideration given lo other
SEISMIC REHABILlTATION OF EXISTING BUlLDlNGS
environmental conditions, ineluding aging effects, 3. The structure aboye the isolation system is checked
creep, fatigue, operating temperature, and exposure lo for stability and ductility demand of lhe BSE-2;
moisture or damaging substances. and
4. The displacement restraint does not become effec
9.2.7.2.2 Wind Forces Isolated buildings shall resist live at a displacement less than 0.75 times the total
design wind loads at all levels aboye the isolation design displacement, unless it is dernonstrated by
interface in accordance wíth the applicable wind analysis that earlier engagement does not result in
design provisjons. At the isolation interface. a wind unsatisfactory perforrnance.
restrajnL system shall be provided to limit lateral dis
placement in the isolation system lo a value equal to 9.2.7.2.6 Vertical Load Stability Each componcnt of
that required between tloors of the structure aboye the the ¡solation system shall be designed to be slable
isolatjon interface. under the full rnaximum vertical load, 1.2QD + QL +
IQEI, and the minimum vertical load, 0.8QD IQEI, at
9.2.7.2.3 Fire Resistance Fire resistance rating ror the a horizonlal displacement equal to the tOlal rnaximum
isolation syslem shall be consistent wiLh Lhe require displacement. The earthquake vertical load on an indi
ments 01' colurnns, walls, or other such cornponents 01' vidual isolator unit, QE' shall be based on peak build
the building. ing response due lo the BSE-2.
276
ASeE/SEI 41-06
9.2.7.2,9 Manulacturing Quality Control A manufac analysis of seismically isolated structures shaIl be
turing quality control testing program for isolator units based on the following tests of a selected sample of
shall be established by the design professional. the components prior lo construction.
The isolatton system components to be tested
9.2.7.3 Structural System shall inelude isolators and components of the wind
restraint system and supplemental energy dissipation
9.2.7.3.1 Horizontal Distribution 01 Force A horizontal
devices if such components and devices are used in the
diaphragm or olher structural components and ele
designo
ments shall provide continuity aboye the isolation
The tests specified in this section establish design
interface. The diaphragm or other structural compo
properties of the ¡solation system, and shall not be
nents and elements shall have adequate strength and
considered as satisfying the manufacturing quality
ductility to transmit torces (due to nonuniform ground
control testing requirements of Section 9.2.7.2.9.
motion) calculated in accordance with Ihis section
from one part of the building to another, and have suf
9.2.9.2 Prototype Tests
ficient stiffness to effect rigid diaphragm response
aboye the isolation interface.
9.2.9.2.1 General Prototype tests shall be performed
9.2.7.3.2 Building Separations Separations between separately on two full-sized specimens of each type
the isolated building and surrounding retaining walIs and size of isolator of the isolation system. The test
or other tixed obslructions shall be not les s than the specimens shall include components 01' the wind
total maximum displacement. restraint system, as well as individual isolators, if such
components are used in the designo Supplementary
9.2.8 Design Review energy dissipation devices shaIl be tested in accor
dance with Section 9.3.8. Specimens tested shalI not
9.2.8.1 General be used for construction unless approved by the engi
A review of the design of the isolation system and neer responsible for the structural designo
related test programs shall be performed by an inde
pendent engineering team, ineluding persons experi 9.2.9.2.2 Record For each cycle of tests, the
enced in seismic analysis methods and the theory and force-<letlection and hysteretic behavior of the test
application of seismic isolation. specimen shaJl be recorded.
9.2.8.2 [solation System
9.2.9.2.3 Sequence and Cycles The following sequence
Isolation system design review shall inelude the
of tests shall be performed fOf the prescribed number
following:
of cycles al a vertical load equal lo the average
l. Site-specific seismic criteria, ineluding site-specific QD + O.5QL on all isolators of a common type and size:
spectra and ground motion time history, and a1l Twenty fully reversed cycles of loading al a lateral
other design criteria developed specitically for the force corresponding to the wind design force;
project; Three fuIly reversed cycles of loading at each of
2. Preliminary design, including the determination of the following displacements: O.25D D, O.50D D, l.ODD'
the total design and total maximum displacement of and l.ODM ;
the isolation system, and the lateral force design Three fully reversed cycles at the total maximum
level; displacement, I.OD TM; and
3. Isolation system prototype testing in accordance 30Sx¡/ SxsBD/, but nolless than 10, fully reversed
with Section 9.2.9; cycles of loading at the design displacement, I.ODD •
4. Final design of the isolated building and supporting SXI and Sxs shall be evaluated for the Design
analyses; and Earthquake.
5. Isolation system quality control testing in accor
dance with Section 9.2.7.2.9. 9.2.9.2.4 Vertical Load-Carrying lsolators If an isola
tor is also a vertical-Ioad-carrying component, then
9.2.9 Isolation System Testing and Design Item 2 of the sequence of cyelic tests specitied in
Properties Section 9.2.9.2.3 shall be performed for two additional
vertical load cases:
9.2.9.1 General
The deformation characteristics and damping val l. 1.2QD + O.5QL + IQEI; and
ues of the isolation system used in the design and 2. O.8QD - IQEI
277
SEISMIC REHABILlTATION OF EXISTING BUILDINGS
where D, L, and E refer to dead, live, and earthquake 9.2.9.2.7 Maximum and Minimum Vertical Load
loads, respectively. QD and QL are as detined in Isolators lhat carry vertical load shall be statically
Section 3.2.8. The vertical test load on an individual tested for the maximum and minimum vertical load, at
isolator unit shall inelude the load increment QE due to the total maximum displacement. In these tests, the
earthquake overturning, and shall be equal to or combined verticalloads of 1.2QD + 1.0QL + IQEI shall
greater than the peak earthquake vertical force be taken as the maximum vertical force, and the com
response correspondíng to Ihe test displacement being bined vertical load of O. 8Qb IQEI shall be taken as the
evaluated. In these tests, the combined vertical load minimum vertical force, on any one isolator of a com
shall be taken as the typical or average downward mon type and size. The earthquake vertical load on an
force on all isolators of a common type and size. individual isolator, QE' shall be based on peak building
response due lo lhe BSE-2.
9.2.9.2.5 lsolators Dependent on Loading Rates If
the force-detlection properties of (he isolators are 9.2.9.2.8 Sacrificial Wind-Restraint Systems If a sacri
dependent on the rate of loading, then each set of tests licial wind-restraint system is part of the isolarion sys
specítied in Sections 9.2.9.2.3 and 9.2.9.2.4 shall be tem, then the ultimate capacity shall be established by
performed dynamically at a frequency equal to the testing in accordance wíth lhis sectíon.
¡nverse of [he effective period, TD , of the isolated
structure. 9.2.9.2.9 Testing Similar Units Prototype tests need
EXCEPTION: Ir reduced-scale prototype speci not be performed if an isolator unil, where compared
mens are used to quantify rate-dependent properties of lo another tesled unÍl, complies with the following
isolators, the reduced-scale prototype specimens shall criteria:
be 01' the same type and material and be manufactured l. Is of similar dimensional characteristics;
with the same processes and quality as fuIl-scale pro 2. Is of the same type and material s; and
totypes, and shall be tested at a frequency that repre 3. Is fabricated using identical manufacturing and
sents full-scale prototype loading rates. quality control procedures
The 1'orce-detlection properties of an isolator shall
be considered to be dependent on the rate of loading if The testing exemption shall be approved by the
there is greater than a plus or minus 10% difference review team specified in Section 9.2.8.
in the effective stiffness at the design displacement
(1) where lested al a frequency equal to the inverse of 9.2.9.3 Determination 01 Force-Deflection
the effective period 01' the isolated structure, and Characteristics
(2) where tested at any frequency in the range of 0.1 lo The force-deflection characterislics of the isola
2.0 limes the inverse 01' the efrective period of the iso tion system shall be based on the cyclic load testing of
lated struclure. isolator prototypes specilied in Section 9.2.9.2.3.
As required, the elIective sliffness of an isolalor
9.2.9.2.61solators Dependent on Bilateral Load If the unít, k'f!' shaJl be calculated for each cycIe of deforma
force-detlection properties of the isolators are depend tíon by Eq. 9-12:
ent on bilateral load, then the tests specitied in IF j+lrj
1
(Eq.9-12)
Sections 9.2.9.2.3 and 9.2.9.2.5 shall be augmenled to k cff = la+1 + la-I
inelude bilateral load al the following increments of
lhe lotal design displacement: 0.25 and 1.0; 0.50 and where F+ and F- are the posítive and negatíve force s
1.0; 0.75 and 1.0; and 1.0 and 1.0. al positíve and negative test displacements, a+ and a,
EXCEPTION: Tf reduced-scale prototype speci respectively.
mens are used lo quantify bilateral-Ioad-dependenl As required, the effective damping of an isolator
properties, then such scaled specimens shall be 01' the unit, {3'JJ' shall be calculated for each cycle of deforma
same type and malerial, and manufaclured with the tion by Eq. 9-13:
same processes and qualíty as full-scale prolotypes.
The force-detleclion properlies of an isolator shall (3 -
'ff -
~ [ k'JJ{la +1E + la-If
71'
LooP
]
(Eq.9-13)
be considered lo be dependent on bilateral load, if the
bilateral and unilateral force-detlection properties have where the energy dissipated per cycle of loading, ELoop,
greater than a plus or minus 15% difference in effec and the effective stitTness, k'fj' are based on test dis
tive sti1'fness al the design displacement. placements, D+ and D-.
278
ASCFJSEI 41-06
30Sx¡JSXSBDJ , bUl nol less than 10, cycles 01' the test In Eq. 9-19, the total energy dissipated in the iso
specitied in Seclion 9.2.9.2.3, ltem 4. SXI and Sxs lation system per displacement cycle, '2.ED , shall be
shall be evaluated for the Design Earthquake; taken as the sum of lhe energy dissipated per cycle in
5. AII specimens 01' vertical-Ioad-carrying components all isolators measured at test displacements, á + and
of the isolation syslem remain stable at the total á-, thal are equal in magnitude lo the maximum di s
maximum displacement for static load as pre placemenl, D M •
scribed in Section 9.2.9.2.6; and
6. The etTective stitTness and effective damping of test
specimens faIl wilhin lhe Iimits specitied by lhe
engíneer responsible for structural designo 9.3 PASSIVE ENERGY DISSIPATION SYSTEMS
279
SEISMIC REHABILITATION OF EXISTING BUILDING S
The energy dissipation devices shall be designed Passive energy dissipation is an emerging technol
with consideralion given to environmental condilions ogy that enhances the performance of the building by
inc\uding wind, aging effects, creep, fatigue, ambient adding damping (and in sorne cases, stiffness) to the
temperature, operaling temperature, and exposure to building. The primary use of energy dissipation
moisture or damaging substances. devices is to reduce earthquake displacement of the
The mathematical model of the rehabilitated structure. Energy dissipation devices wilI also reduce
building shall inc\ude the plan and vertical distribution force in the structure-provided the structure is
of the energy dissipation devices. Analyses shall responding elastically-but would not be expected to
account for the dependence of the devices on excita reduce force in structures that are responding beyond
tion frequency, ambient and operating temperature, yield.
velocity, sustained loads, and bilateral loads. Multiple For most applications, energy dissipation provides
analyses of the building shall be conducted to bound an alternative approach to conventional stilTening and
the effects of each varying mechanical characteristic of strengthening schemes, and would be expected to
the devices. achieve comparable performance levels. In general,
Energy dissipation devices shall be capable of these devices would be expected to be good candidates
sustaining larger displacements for displacement for projects that have a target Building Performance
dependent devices and larger velocities for velocity Level of Life Safety or perhaps Immediate Occupancy,
dependent devices than the maximum caJculated for but would be expected to have only limited applicabil
the BSE-2 in accordance with the following criteria: ity to projects with a target Building Performance
Level of CoIlapse Prevention.
l. If four or more energy dissipation devices are pro
Other objectives may also int1uence the decision
vided in a given story of a building in one principal
to use energy dissipation devices since these devices
direction of the building, with a minimum of two
can also be useful for control of building response
devices located on each side of the center of stifI
due to small earthquakes, wind, 01' mechanicalloads.
ness of the story in the direction under considera
The analysis procedures set forth in this standard
tion, aIl energy dissipation devices shall be capable
are approximate. Roof displacements caIculated using
of sustaining displacements equal to 130% of the
the linear and nonlinear procedures are likely to be
maximum caIculated displacement in the device in
more accurate than the corresponding estimates of
the BSE-2. A velocity-dependent device as
story drift and relative velocity between adjacent
described in Section 9.3.3 shall be capable of sus
stories.
taining the force associated with a velocity equal to
Accordingly, this standard requires that energy
130% of the maximum caJculated velocity for that
dissipation devices be capable of sustaining larger dis
device in the BSE-2; and
placements (and velocities for velocity-dependent
2. If fewer than four energy dissipation devices are
devices) than the maxima caIculated by analysis in the
provided in a given story 01' a building in one prin
BSE-2. Recognizing that the response of a building
cipal direction of the building, or fewer than two
frame incorporating four or more devices in each prin
devices are located on each side of the center of
cipal direction in each story will be more reliab1c than
stitIness of the story in the direction under consid
a frame with fewer devices in each principal direction,
eration, alI energy dissipation devices shall be
the increase in displacement (and velocity) capacity
capable of sustaining displacements equal to 200%
is dependent on the level of redundancy in the supple
of the maximum caJculated displacement in the
mental damping system. The increased force shall
device in the BSE-2. A velocity-dependent device
be used to design the 1'raming that supports the
shall be capable of sustaining the force associated
energy dissipation devices-rellecting the objective
with a velocity equal to 200% of the maximum cal
of keeping the device support framing elastic in the
culated velocity for that device in the BSE-2.
BSE-2. The increases in force and displacement
The components and connections transferring capacity listed in this standard are based on the judg
forces between the energy dissipation devices shall be ment of the authors.
designed to remain linearly elastic for the forces
described in Items 1 or 2 aboye.
9.3.2 Implementation oC Energy Dissipation Devices
C9.3.1 General Requirements Energy dissipation devices shall be implemented
The increase in displacement (and velocity) in accordance with requirements specified in Chapters
capacity is dependent on the level of redundancy in the I through 3 but as modified in the subsequent sections
supplemental damping system. of this chapter.
280
ASCElSEI 4]-06
9.3.3 Modeling of Energy Dissipation Devices The forces in lhe device, F+ and F-, shall be evaluated
Displacement-dependent devices shall inelude al displacements D+ and D-, respectively.
devices that exhibit either rigid-plastic (friction
devices), bilinear (metallic yielding devices), or 9.3.3.2 Velocity-Dependent Devices
trilinear hysteresis. The response of displacement
dependent devíces shall be independent of velocily 9.3.3.2.1 Solid Viscoelastic Devices Solid viscoelastic
and frequency of excitalion. Velocity-dependent devices shaIl be modeled using a spring and dashpot in
devices shall inelude solid and fluid viscoelastic parallel (Kelvin model). The spring and dashpot con
devices, and fluid viscous devices. Devices nol c1assi stants selecled shall capture lhe frequency and
fied as displacemenl- or velocity-dependent shall be temperature dependence ol' the device consistenl wíth
elassified as "other." fundamental frequency of the rehabilitated building
Models ol' lhe energy dissipation syslem shall (J¡), and the operaling temperature range. If the cyclic
inelude Ihe stiffness of structural components lhat are response of a viscoelastic solid device cannot be cap
part of Ihe load path belween energy dissipation tured by single estimates of the spring and dashpol
devices and Ihe ground and whose tlexibility affects conslanls, Ihe response of Ihe rehabililated building
lhe performance of the energy dissipation system, shall be estimated by multíple analyses of the building
including components of the foundalion, braces thal trame, using Iimiting upper- and lower-bound values
work in series with lhe energy dissipation devices, and for the spring and dashpol constants.
connections belween broces and lhe energy dissipation The force in a viscoelastic device shall be deler
devices. mined in accordance wilh Eq. 9-22:
Energy dissipation devices shall be modeled as
F = ketP + CD (Eq.9-22)
descríbed in Ihe following subsections, unless
approved methods are used. where C is the dampíng coefticienl for Ihe víscoelastic
device, D is the relalíve displacement between each
C9.3.3 Modeling of Energy Dissipation Devices end of Ihe device, D is Ihe relative velocily between
Examples of "other" devices inelude shape each end of the device, and keff is lhe effectíve sliffness
memory alJoys (superelastic effect), friclion-spring of the device calculated in accordance with Eq. 9-23:
assemblies with recentering capability, and fluid
restoring, force-damping devices. (Eq.9-23)
281
SEISMIC REHABILlTA1l0N OF EXISTING BUILDlNGS
(JI)' and Ihe operaling IemperalUre range. If Ihe cyclic C9.3.3.3 Other Types 01 Devices
response 01' a viscoelastÍC fluid device cannot be cap Other energy dissipating devices, such as those
tured by single estimates of the spring and dashpot having hysteresis 01' the type shown in Fig. C9-8,
constants, the response of the rehabilitated building require modeling techniques different 1'rom those
shall be estimaled by multiple analyses of the building described aboye. Tsopelas and Constantinou (l994a),
frame, using limiting upper- and lower-bound values Nims el al. (1993), and Pekcan et al. (1995) describe
1'or ¡he spring and dashpol conslanls. analylical models 1'or sorne of these devices.
Q)
~
~DynamíC o
u..
Statíc
Displacement Displacement
of Section 9.3.4, the folIowing requirements are 2. The pseudo-lateral load of Eq. 3-10 shall be
satisfied: reduced by the damping modification 1'aclors of
Section 1.6.1.5.1 lo account for the energy dissipa
l. The ratio of !he maximum resistance in each story, in
tion (damping) a1'forded by the energy dissipation
!he direclion under consideration, lo the story shear
devices. The damping efl'ect shall be calculated in
demand calculated using Eqs. 3-10 and 3-11, shall
accordance with Eq. 9-28:
range between 80% and 120% of the average value
of the ratio for all slories. Too maximum story resist
ance shall inelude Ihe conlributions from all compo
(Eq.9-28)
nents, elements, and energy dissipation devices; and
2. The maximum resistance of all energy dissipation
devices in a slory, in the direclion under considera where P is the damping in the structural frame and
lion, shall not exceed 50% 01' lhe resistance of lhe shall be set equal to 0.05 unless moditied in Section
remainder ol' the framing where said resistance is 1.6.1.5.3, w¡ shall be taken as the work done by device
calculated at the displacements anticipated in the j in one complete cycle corresponding to floor dis
BSE-2. Aging and environmental effects shall be placements Oí' the summation extends over all devices
considered in calculating the maximum resistance j, and Wk is !he maximum strain energy in the frame,
of the energy dissipation devíces determined using Eg. 9-27.
The work done by linear viscous device j in one
The pseudo-lateral load of Eq. 3-10 shall be complete cycle ol' loading shall be ca\culated in accor
reduced by the damping modificaLÍon factors 01' Sec dance with Eq. 9-29:
tion 1.6.1.5.1 to account for the energy dissipation
(damping) afforded by the energy dissipation devices.
(Eq.9-29)
The damping effect shall be calculated in accordance
with Eq. 9-26:
where T is the fundamental period of!he rehabilitated
¿w¡ building including the stiffness of the velocity
Pe!! = P + ....L- (Eq.9-26) dependent devices, Cj is the damping constant for
4'iTW k device j, and 8rj is the relatíve displacement between
where P is Ihe damping in Ihe framing system and Ihe ends of device j along the axis of device j.
shall be set equal to 0.05 unless modified in Seclion Calculatíon of effective damping in accordance
1.6.1.4, Wj shall be taken as !he work done by devíce j with Eq. 9-30 rather than Eq. 9-28 shall be permitted
in one complete cycle corresponding to floor displace for linear viscous devices:
ments 8;, lhe summation extends over al1 devices j, and
W k is the maximum strain energy in the 1'rame, deter T¿ Cjcos2 (JA)~
mined using Eq. 9-27: PelJ P + ---'--..,--....---- (Eq.9-30)
l
W.• = 2 LJ
'" F8
11
(Eq.9-27)
I
where (Jj is the angle of inclinatíon of device j to the
where F¡ shall be taken as the inertia force at floor horizontal, tPrj is the first mode relative displacement
level i and the summation extends over all floor levels. between the ends 01' device j in the horizontal direc
tion, W¡ is the reactive weight of floor level i, J. is the
9.3.4.1.2 Velocity-Dependent Devices Use 01' the LSP first mode displacement al floor level í, and other
shalI be permitted to analyze velocity-dependent terms are as defined aboye.
energy dissipation devices, provided that in addition to
the requirements of Section 9.3.4, the following 9.3.4.1.3 Design Actions The desígn actions for com
requirements are satislied: ponents of the rehabilitated building shall be calcu
lated in tbree dístinct stages of deformatíon as follows.
l. The maximum resislance of all energy dissipation
The maximum action shall be used for designo
devices in a story in the direction under considera
tion shall not exceed 50% of the resistance ol' the l. At the stage of maximum drift. The lateral forces
remainder of the framing where said resistance is al each level of the building shall be calcu]aled
calculated at the dísplacements anticipated in the using Eg. 3-11, where V* is the modified equiva
BSE-2. Aging and environmental effects shall be lent base shear.
considered in ca\culating the maximum resistance 2. At the stage of maximum velocity and zero drift.
of the energy dissipation devíces; and The viscous component of force in each energy
283
SEISMIC REHABILlTATION OF EXISTING BUILDlNGS
dissipation device shall be calculated by Eq. 9-22 If the maximum base shear force ca\culated by
or 9-25, where the relative velocity D is given by dynamic analysis is les s Ihan 80% of the modified
21T J, D, where D is the relative displacement equivalent base shear 01' Seclion 9.3.4.1, component
between the ends of the device calculated at the and element actions and deformalions shall be propor
stage of maximum drift. The calculated viscous tionally increased to correspond lO 80% 01' the modi
forces shalJ be applied to the mathematical model fied equivalent base shear.
of the building at the points of attachment of the
devices and in directions consistent with the 9.3.4.2.2 Velocity-Dependent Devices For analysis by
deformed shape of the building al maximum drift. the Response Spectrum Method, modification of the
The horizontal inertia forces at each f100r level of 5%-damped response spectrum shall be permitted lo
the building shall be applied concurrently with the account for lhe damping afforded by the velocity
viscous forces so that the horizontal displacemenl dependenl energy dissipalion devices. The 5%-damped
of each tloor level is zero. acceleration speclrum shaIl be reduced by the modal
3. At tbe stage of maximum floor acceleration. dependent damping modification factor, B, either B, or
Design actions in components of the rehabilitated B" for periods in [he vicinity of the mode under con
building shall be determined as the sum of actions sideration; note Ihat the value of B will be different for
determined at the stage of maximum drift times each mode of vibralion. The damping modification
CF" and actions determined at the stage of maxi factor in each signilicanl mode shall be delermined in
mum velocity times CF1 , where accordance wilh Section 1.6.1.5.1 and (he calculated
eftective damping in that mode.
CF¡ = cos[tan-I(2J3ell)] (Eq.9-31) The etJeclive damping in the m-th mode of vibra
I
CF2 = sin[tan- (2J3eff)] (Eq.9-32) tion (J3eff-m) shall be calculated in accordance with
Eq.9-33:
in which J3ejJ is defined by either Eq. 9-28 or Eq. 9-30.
284
ASCFJSEI 41-06
using the procedure described in Sections 9.3.4.1.2. ing frame. For most velocity-dependenl devices, Ihe
The combination factors CF¡ and CF2 shall be deter primary benetit will resull from the added viscous
mined based on Eqs. 9-31 and 9-32 using {3~fJm for Ihe damping. Higher-mode damping forces in the energy
m-lh mode. dissípation devices must be evaluated regardless of the
If Ihe maximum base shear force calculated by NSP used.
dynamic analysis is less Ihan 80% of Ihe modified
equivalent base shear of Section 9.3.4.1, component 9.3.5.1.1 Displacement-Dependent Devices The stiff
and element actions and deí'ormations shall be propor ness characteristics 01' the energy dissipation devices
tionally increased to correspond to 80% of Ihe modi shaJl be included in the mathematical model.
fied equivalent base shear.
9.3.5.1.2 Velocity-Dependent Devices The targel dis
9.3.5 Nonlinear Procedures placement and lhe spectral acceleration in Eq. 3-15
shall be reduced lo account for the damping added by
9.3.5.1 NOllliflear Static Procedure the velocity-dependent energy dissipaüon devices. The
If lhe Nonlínear Stalic Procedure (NSP) is ca\culation of lhe damping eftecI shall be ca\culated in
selected based on the requirements oí' Section 9.2.3.3 accordance with Eq. 9-36:
and Section 2.4, the NSP of Seclion 3.3.3 shall be fol
lowed unless explicilly modified by Ihis section. 2:w¡
The non linear mathemalÍcal model of the reha (3 +-L- (Eq.9-36)
bililated building shall include Ihe nonlinear force 41TWk
velocity-displacement characleriSlics oí' lhe energy where (3 is the damping in the structural frame and
dissipalion devices explicitly, and Ihe mechanical char shall be sel equallo 0.05 un!ess modified in Seclion
aCleristics 01' lhe components supporting the devices. 1.6.1.5, Wj shall be laken as the work done by device j
Slil1'ness characteristics shall be consistenl wilh the in one complete cycle corresponding lo floor displace
deformations corresponding to lhe larget displacement menls 8j , lhe summalion exlends over all devices j, and
and a frequency equal lo the inverse oí' period Te' as Wk is the maximum slrain energy in lhe frame, deler
detined in Seclion 3.3.3.2. mined using Eq. 9-27.
The nonlinear mathematical model oí' Ihe reha The work done by device j in one complete cyc\e
bililaled building shall include the nonlinear force of loading shall be ca\culated based on Eq. 9-37:
velocily-displacement characteristics of Ihe energy
211'2
dissipatíon devices, and Ihe mechanical characterislics --Cj 8;j (Eq.9-37)
01' the components supporting the devices. Energy dis T.,s
sipation devices with stiffness and damping character where Tss is lhe secanl fundamenlal period of Ihe reha
¡stics Ihat are dependent on excitalion frequency bililaled building including lhe stiffness of lhe velocity
and/or lemperature shall be modeled wilh characleris dependent devices (i1' any), calculated using
tics consislenl with (1) Ihe del'ormations expected al Eq. 3-14 but replacing lhe eftective stift'ness (K,) with
the target displacement, and (2) a l'requency equal to the secant sliffness (K,) at lhe larget displacement as
lhe inverse of Ihe effective periodo shown in Fíg. 9-1; Cj is the damping constant for
Equalion 3-15 shall be used to calculale the target device j; and Srj is lhe relative displacemenl between
displacement. Ihe ends ol' devíce j along lhe axis of device j at a rool'
dísplacement corresponding lo lhe target displacement.
C9.3.5.1 Nonlinear Static Procedure The acceplance criteria 01' Seclion 3.4.3 shall
Benefits of Adding Energy Dissipation Devices. apply to buildings incorporatíng energy díssipation
The benetit of adding displacement-dependenl energy devices. Checking for displacemenl-controlled actions
dissipation devices is recognized in Ihis standard by shall use de formal ion s correspondíng lo lhe target dis
the increase in building stiffness afforded by such placement Checking for force-controlled aClíons shall
devices, and the reduclion in larget displacement asso use component actions calculaled for three límit states:
ciated with the reduclion in Te' The allernalive NSP maximum drífl, maxímum velocíty, and maximum
uses a different strategy lO calculale the target dis acceleration. Maximum aClions shall be used for designo
placement and explicitly recognizes the added damp Higher-mode effecls shall be explicitly evalualed.
ing provided by the energy dissipation devices.
The benetits of adding velocity-dependent energy C9.3.5.1.2 Velocity-Dependent Devices The use of
dissipation devÍces are recognized by the increase in Eq. 9-36 will generally caplure lhe maximum displace
sliffness and equivalent viscous damping in lhe build- menl 01' lhe building.
285
SElSMIC REHABILlTATION OF EXISTING BUILDlNGS
,¿j::/
ID
Ul The viscous forces (if any) developed in the seis
ro
CD mic framing system should be accounted for in the
analysis and design 01' the seismic framing system.
O.6Vy+--+--+-- Evaluation 01' member action histories should be based
............/ on nodal displacements (operating on member stifl'
... ness matrices) and nodal velocities (operating on
./ .. / .......... member damping matrices).
Key to the acceptable response ol' a rehabilitated
,
I
,,'
,,' building incorporating energy dissipation devices is
' ..... the stable response ol' the energy dissipation devices.
...•.
The forces and deformations in the energy dissipation
oy ot devices that develop during the Design Earthquake
Roof displacement should be demonstrated to be adequate by prototype
FIGURE 9-1. Calculation of Secant Stiffness, K,_ testing in accordance with Section 9.3.8.
286
ASCFlSEI 41-06
287
SEISMIC REHABILlTATION OF EXISTING BUILDlNGS
Test specimens shall not be used for construetion EXCEPTION: If redueed-seale prototypes are
unless approved in writing by the design prol'essional. used to quantify the rate-dependent properlies of
energy dissipation devices, Ihe redueed-seale proto
9.3.8.2.2 Data Recording The force-detlection rela types shall be of the same type and materials-and
tionship l'or eaeh eycle of each test shall be recorded manufactured with the same processes and quality
electronieally. control procedures-as full-seale prototypes, and
tested al a similitude-sealed frequeney that represents
9.3.8.2.3 Sequence and Cycles ofTesting For the l'ol the full-seale loading rates.
lowing minimum test sequenee, each energy dissipa
tion device shall be loaded 10 simulate lhe gravity 9.3.8.2.5 Devices Dependent on Bilateral Displace
loads on the deviee as installed in the building and the ment lf the energy dissipalion deviees are subjeeled lo
extreme ambient temperatures anticipated: bilaleral deformation, Ihe preeeding tests shall be
made at both zero bilateral displacement, and peak
1. Each deviee shall be loaded with the number ol'
lateral displacement in Ihe BSE-2.
cycles expected in the design wind storm, bul
EXCEPTION: If reduced-seale prototypes are
not less Ihan 2,000 fully-reversed cycles of load
used to quantífy the bilateral displaeement properties
(displaeement-dependent and viseoelastie devices) of Ihe energy dissipation devices, the reduced-seale
or displacement (viseous deviees) at amplitudes prototypes shall be of the same type and materials, and
expected in Ihe design wind storm, at a frequeney manufactured with the same processes and qualíty
equal to the inverse of lhe fundamental period of eontrol proeedures, as full-seale prototypes, and lested
the rehabilitated building. at similitude-scaled displaeements thal represent the
EXCEPTION: Deviees nol subjecl to wind full-seale displacements.
indueed forces or displaeements need not be sub
jected lo [hese tests.
9.3.8.2.6 Testing Similar Devices Energy dissipation
2. Each device shall be loaded wilh 20 fully reversed
deviees tha! are (1) 01' similar size, identieal materials,
cycles at the displaeemenl in lhe energy dissipalion
internal eonstruetion, and statie and dynamic internal
device corresponding 10 the BSE-2, al a frequency
pressures (if any), and (2) fabricated wilh identieal
equal lo the inverse of Ihe fundamental period of
inlernal processes and manufacturing quality control
the rehabilitaled building.
procedures, and that have been previously lesled by an
EXCEPTION: Testing methods for energy dissipa
independenl laboratory in the manner deseribed aboye
tion devices other lhan those noted aboye shall be
need not be tesled, provided Ihat:
permitted, provided thal: (l) equivalency between
lhe proposed melhod and cyclic tesling ean be l. AII pertinent testing data are made available 10, and
demonstraled; (2) the proposed melhod caplures the are approved by, lhe design professional;
dependenee of the energy dissipation device 2. The manufacturer ean substanliate Ihe similarity of
response lo ambient temperature, frequency of the previously tested deviees to the salisfaction of
loading, and lemperature rise during testing; and Ihe design professional; and
(3) the proposed method is approved by the design 3. The submission of data from a previous tesling
professional. program is approved in writing by the design
prol"essional.
C9.3.8.2.3 Sequen ce and Cycles ofTesting Energy dis
sipation deviees should not form parl of the gravity 9.3.8.3 DelermÍllatioll 01 Force-Displacemelll
load-resisting system, but may be required to support Characterislics
some gravity load. The force-displacement eharaeteristics 01' an
energy dissipatiol1 device shall be based on lhe cyclic
9.3.8.2.4 Devices Dependent on Velocity andlor load and displacement tests of prototype deviees speci
Frequency of Excitation If Ihe force-deformaLion fied in Section 9.3.8.2.
properlies of lhe energy dissipation devices at any As required, lhe etl"eelive stiH"ness (keJ!) 01" an
displaeement less than or equallo the total design dis energy dissipalion deviee wilh sliffness shall be calcu
placemenl ehange by more than 15% for ehanges in lated for each cycle of deformation in aceordanee with
testing frequeney from 0.5/J to 2.0/J, the preeeding Eq.9-38:
tests shall be performed al frequeneies equal to 0.5 fl'
j;, and 2.0J¡. (Eq.9-38)
288
ASCE/SEI41-06
289
SEISMIC REHABILITATION OF EXISTING BUILDINGS
290
ASCE/SEI 41-06
from highest to Jowest priorily based on the extent 5. A complete Tier 1 and Tier 2 Evaluation of the
of nonconformance and the signiticance of the building in its proposed rehabilitated stale shall be
defieieney; performed in accordance with ASeE 31, except
4. Rehabilitation measures shaJl be developed in that the speclral response acceleration parameters
aeeordance with Section 10.3. The proposed reha shaJl be defined in aceordance wilh Section 1.6.1.2
bilitation scheme shaJl be designed su eh Ihat an of Ihis standard. For any other differenees between
detieiencies idenlified by the ASeE 31 Evaluation this standard and the ASeE 31 proeedures, the
of Step 2 are eliminated; AseE 31 procedures shaIl govern;
291
5EI5MIC REHABlLlTATION OF EXI5TING BUILDING5
292
ASCE/SEI41-06
continued
293
SEISMIC REHABILlTATION OF EXISTING BUTLDINGS
6. Rehabilitation measures ror architeclural, mechani and 7 of Section ] 0.2.1 shall be completed. Steps 4
cal, and eleclrícal components shalI be developed and 6 01' Section 10.2.1 shall be complcted only as
in accordance with Chapler II for the Lífe Safety they apply to the deticiencies being addressed as part
Nonstruclural Performance Level al the BSE-I of lhe Partíal Rchabilitation.
Earlhquake Hazard Level; ano
7. Construction documenls, including drawings, speci
fications, and a qualily assurance plan, shall be
developed as detined in Chapler 2. C10.2 PROCEDURE
10.2.2 Procedure for Partial Rehabilitation The basis of lhe Simplified Rehabilitation Method ís
Where the Simplifieo Rehabililation Method is the ASCE 31 (ASCE 2002) procedure. There are
used lo achieve Partíal Rehabílitation, Sleps 1, 2, 3, 5, intentional dilTerences between lhe provisions 01' this
294
ASCElSEI 41-06
standard and ASCE 31 with regard to site c1ass ampli Table CIO-2. WIA: Multi-Story, Multi-Unit, Wood
tication factors, seismicity, and design earthquake, Frame Construclion
among other issues. The Earlhquake Hazard Level
detined in ASCE 31 is taken as two-thirds of the Typical Deficiencies
Maximum Considered Earthquake (MCE) for simplic
Load Path
ity and conservatism in the evaluation procedures.
Redundancy
However, rehabilitation to the BSE-I Earthquake
Vertical Irregularitíes
Hazard Level in accordance with this standard is the Shear Walls in Wood Frame Buíldíngs
tradilional level of safety taken as the lesser of the Shear Stress
1O%/50-year or Iwo-trurds of Ihe MCE. Openings
For simple buildings with specific deficiencies, it Wall Detailing
is possible and advÍsable to prioritize the rehabilitation Cripple Walls
measures. This is orten done where the construction Narrow Wood Shear Walls
has Iimited funding or must take place while the build Stucco Shear WalIs
ing is occupied. In bolh cases, it is preferable to cor Gypsum Wallboard or PI aster Shear Walls
rect the worst deficiency first. Diaphragm Openings
Diaphragm Stiffness/Strength
Potential deficiencies are ranked in Tables C 10-1
Spans
through C 10-19; items in these lables are ordered
Diaphragm Continuity
roughly from highest priority at Ihe top lo lowesl al Anchorage to Foundations
the bonom, aIthough this can vary widely in individual Conditíon of Foundations
cases. Tables C l 0-1 through C 10-19 are presented at Geologic Site Hazards
Ihe end of this Commentary section. Condition of Wood
ASCE 31 lists specific deficiencies both by Model
Building Type and by association with each building
system. Tables C 10-1 through C 10-19 of this standard
further group deficiencies by general characteristics.
For example, the deficiency Iisting "Diaphragm
blocking. Table C 10-20 provides a complete cross
StitIness/Strength;' ineludes deficiencies related to the
reference for sections in this standard and in ASCE 31
type of sheathing used, diaphragm span, and lack 01'
and is presented al Ihe end 01' this Commentary section.
Witbin the table for each Modcl Building '!Ype,
typícal deficiencies are ranked from most critical at
tbe top of eacb deticiency group to least critical al the
Table CIO-I. WI: Wood Ligbt Frame bottom. For example, in Table ClO-12, in a
precastltilt-up concrete shear wall with flexible
Typical Deticiencies diaphragm (PC 1) building, Ihe lack of posilive gravily
frame connections (e.g., 01' girders lo posts by sheet
Load Path
metal hardware or bolts) has a greater potential to
Redundancy
Vertical Irregularities lower the building's per1'onnance (a partíal collapse 01'
Shear Walls in Wood Frame Buildings the roof structure supported by the beam) than a defi
Shear Stress ciency in lateral forees on 1'oundations (e.g., poor rein
Openings forcing in the footings).
Wall Detailing The ranking was based on the 1'oIlowing charac
Cripple Walls teristics of eaeh deticiency group:
Narrow Wood Shear WaIls
Stucco Shear Walls l. Most critical
Gypsum Wallboard or Plaster Shear Walls 1.1. Building systems: those with a discontinuous
Diaphragm Openings load path and liule redundancy.
Diaphragm StiffnesslStrength 1.2. Building components: those with low strength
Spans and low ductility.
Díaphragm Continuity 2. Intermediate
Anchorage to Foundations 2.1. Building systems: those wÍlh a discontinuous
Condition of Foundatíons load path but substantial redundancy.
Geologic Site Hazards
2.2. Building components: those with substantial
Condition of Wood
strength but low ductility.
295
SEISMIC REHABlLlTATION OF EXISTING BUILDINGS
Table ClO-3. W2: Wood-Commercial, and ol' eliminating deficiencies. A Tier I and Tier 2
Industrial Evaluation of the proposed rehabilitated stale ís per
formed to verify the proposed rehabilitation designo
Typical Deficiencies For a Limited Rehabilitation Objeclive, the deti
Load Path ciencies identified by the ASCE 31 Evalualion of
Redundancy Step 2 should be mitigated in order of príorÍly based
Vertical IITegularities on the ranking performed in Step 3.
Shear Walls in Wood Frame Buildings A complete evaluation of the building should con
S hear Stress firm that the strengthening of any one componenl or
Openings system has not merely shifted the deficiency to
Wall Detailing another.
Cripple Walls Specific applicalion of the Syslematic
NaITow Wood Shear Walls Rehabilitation Method is needed to achieve the BSO.
Stucco Shear Walls
The total strength of the building should be sutficient,
Gypsum Wallboard or Plaster Shear Walls
Diaphragm Openings
and the ability of the building to experience the pre
Diaphragm Stiffness/Strength dicted maximum -displacemem without partial or com
Sheathing plele collapse must be established.
Unblocked Diaphragms If only a Partí al Rehabilitation or Limited
Spans Rehabilitation O~iective is intended, deficiencíes
Span-to-Depth Ratio should be corrected in priority arder and in a way that
Diaphragm Continuity will facilitate fultillmenl of the requirements 01' a
Chord Continuity higher objective at a later date. Care must be Laken to
Anchorage to Foundations ensure that a Partí al Rehabilitation effort does not
Condition of Foundations make the building's overall performance worse by
Geologic Site Hazards
unintentionally channeling failure lO a more crilical
Condítion of Wood
component.
296
ASCE/SEI 41-06
Table CIO-5. S2 and S2A: Steel Braced Frames Table CI0-6. 83: 8teel Ligbt Frames
with 8tiff or Flexible Diapbragms
Typical Deticiencies
Typical Deficiencies
Load Path
Load Path Redundancy
Redundancy Vertical Irregularities
Vertical Irregularities Plan Irregularities
Plan Irregularities Steel Moment Frames
Uplift at Pile Caps Frame Concems
Stress Level Masonry Shear Walls
Stiffness of Diagonals (nlm Walls
Chevron or K-Bracing Steel Braced Frames
Braced Frame Connections Stress Level
Re-entran! Comers Braeed Frame Conneclions
Diaphragm Openings Re-entran! Comen;
Diaphragm Stíffness/Strenglh Diaphragm Openíngs
DiaphragmlFrame Shear Transfer DiaphragmlFrame Shear Transfer
Anchorage to Foundations Wall Panels and C1adding
Condilion of Foundations Light Gage Melal, Plastic, or Cementitious Roof Panel s
Overtuming Anchorage 10 Foundations
Lateral Loads ConditÍon of Foundations
Geologic Site Hazards Geologíc Site Hazards
Condition 01' SteeJ Condition of Steel
For Simplified Rehabililation, detieieneies idenlified Implementing a rehabilitalÍon seheme lhat mitigales all
by an ASCE 31 Evaluation shall be mitigaled by 01' a building's ASCE 31 (ASCE 2002) delicieneies
implementing rehabilitalÍon measures in aeeordanee using lhe Simplified Rehabililalion Method does nOI,
wiLh Ihis standard. The resulling building, including in and 01' irself, aehieve lhe Basie Safely Objeelive or
strenglhening measures, shall comply wíth lhe require any Enhanced Rehabilitation Objeclive as detined in
menlS of ASCE 31, exeepl that the speclral response Chapler 2 sinee lhe rehabilitaled building may nol
aeeeleration parameters shall be detined in aecordance meer the Collapse Prevenlion Structural Performance
wilh SeeLion 1.6.1.2 of this standard. The rehabilitated Level ror the BSE-2 Earthquake Hazard Leve/. If the
building shall eonform 10 one of the Model Building goal is lo attain lhe Basie Safely Objeclive as
Types eontaíned in Table 10-1, exeept that steel brae described in Chapler 2 or other Enhanced Reha
ing in wood or unreinforced masonry buíldings shall bililation Objectives, this ean be accomplished using
be permiued. the Systemalic Rehabilitalion Melhod detined in
The Simplitied Rehabilitation Melhod shall only Chapler 2.
be used lo aehieve Limiled Rehabilitalion Objectives. Suggested rehabílitation measures are listed by
To aehieve Ihe Life Safely Building Performance deficieney in lhe following sections.
Level (3-C) al lhe BSE-I Earlhquake Hazard Levcl, all
deticieneies idenlitied by an ASCE 31 Evaluation shall CIO.3.1 Building 8ystems
be eorrecled lo meel lhe ASCE 31 eritería exeept lhal
lhe spectral response aceeleralion parameters shall be CI0.3.1.1 Load Path
defined in aceordanee with Seetion 1.6.1.2 of Ihis stan Load path discontinuilies can be miligated by
dard. To achieve a Parlial Rehabililalion Objeetive, adding components to complete Ihe load palh. This
only selected deficiencies need to be eorrected. may require adding new, well-founded shear walls or
To achieve lhe Basie Safety Objeetive, the frames to till gaps in existing shear walls or rrames
Simplified Rehabilitation Melhod is not permitted, and Ihal are nOl carried continuously lo the foundalion.
deticiencies shall be eorreeted in aeeordanee with the Alternatively, it may require the addition of eompo
Systemalie RehabílilalÍon Melhod of Seetion 2.3. nents throughoul the building lo piek up loads from
297
SEISMIC REHABILlTATION OF EXISTING BUILOINGS
Table CIO-7. S4: Steel Frames witb Concrete Table ClO-8. SS, S5A: Steel Frames witb (nflll
Sbear Walls Masonry Sbear Walls and Stiff or
Flexible Diapbragms
Typical Deficiencies
Typical Deficiencies
Load Path
Redundancy Load Path
Vertical Irregularities Redundancy
Plan Irregularítíes Vertical Irregularities
Uplift at Pile Caps Plan Irregularities
Cast-in-Place Concrete Shear Walls Uplifl at Pile Caps
S hear Stress Frames NOl Part of the Laleral-Force-Resisting System
Ovel1urning Complete Frames
Coupling Beams Masonry Shear WaJls
Boundary Component Detailing Reinforcing in Masonry Walls
Wall Reinforcement Shear Stress
Re-entran! Corners Reinforcing at Openings
Diaphragm Openings Unreinforced Masonry Shear Walls
Diaphragm Stiffness/Strength Proportions, Sol id Walls
Diaphragm/WaIl Shear Transfer Intill Walls
Anchorage to Foundations Re-entranl Corners
Condilion of Foundations Diaphragm Openings
Ovenurning Diaphragm StitTness/Strength
Lateral Loads Span-to-Deplh Ratio
Geologic Síte Hazards Diaphragm/Wall Sheur Transfer
Condition of Steel Anchorage for Normal Forces
Condition of Concrete Anchorage lo Foundations
Condition of Foundations
Ovel1urning
diaphragms that have no path into existing vertical ele Latera) Loads
ments [ASCE 31, Section 4.3.1 (ASCE 2002)]. Geologic Site Hazards
Condition of Steel
Quality of Masonry
C10.3.J.2 Redllndancy
The most prudent rehabilitation strategy fOl" a
building without redundancy is to add new lateral CIO.3.1.4 Plan lrregularities
force-resistíng elements in locations where the faílure The effects 01' plan irregularities that create lor
of a few components will cause an inslability in the sion can be eliminated with the addition of lateral
building. The added lateral-force-resisting elements force-resisting bracing elements that will support all
should be of the same stitl"ness as the e1ements they major díaphragm segments in a balanced manner.
are supplementing. It is not generally satisfactory just Although it is possible in so me cases 10 allow Ihe
to strengthen a nonredundant elemenL (such as by irregularity 10 remain and instead strengthen those
adding cover plates to a slender brace), beeause its structural components ¡hal are overstressed by ilS exis
fai/ure would still resuIt in an instability [ASCE 31, tence, this does nol direclly address the problem and
Sections 4.4.1.1.1, 4.4.2.1.1, 4.4.3. J.J, and 4.4.4.1.1 will require the use oí" Ihe Systematic Rehabilitation
(ASCE 2002)]. Method [ASeE 31, Section 4.3.2.6 (ASCE 2002)].
298
ASCElSEI41-06
deticiencies are not crealed. Pounding can also be Table CIO-IO. C2, C2A: Concrete Shear Walls with
eJiminated by demolishing a portion of one building to Stiff or Flexible Diapbragms
increase the separation [ASeE 31, Section 4.3.1.2
(ASeE 2002)]. Typical Deficiencies
Load Path
CIO.3.1.6 Uplift al PiIe Caps
Redundancy
Typically, deficiencies in the load path at the piJe
Vertical Irregularities
caps are not alife safety concern. However, if the Plan Irregularities
design professional has determined that there is a Uplift at Pile Caps
strong possibility of alife safety hazard due to this Detlection CompalibiHty
deficiency, piJes and piJe caps may be modified, sup Frames Not Part 01' Ihe Lateral-Force-Resisling System
plemented, repaired, or in the most severe condition, Captive Columns
replaced in their entirety. Altematively, the building Cast-in-Place Concrete Shear Walls
system may be rehabilitated such that the pile caps are Shear Stress
protected [ASeE 31, Section 4.6.3.10 (ASeE 2002)J. Overturning
Coupling Beams
Boundary Componen! Detailing
CI0.3.1.7 Defleclion Compatibility
Wall Reinforcemen!
Verticallateral-force-resisting elements can be Re-entran! Corners
added to decrease the drift demands on the columns, Diaphragm Openings
or the ductility of me columns can be increased. Diaphragm StiffnesslStrenglh
Jacketing the columns with steel or concrete is one Shealhing
approach lo increase their ductiJity [ASeE 31, Sec Diaphragm/Wall Shear Transfer
lion 4.4.1.6.2 (ASeE 2002)]. Anchorage to Foundations
Condilion of FoundaLions
Overturning
Lateral Loads
Geologic Site Hazards
Condition of Concrete
Table CIO-9. Cl: Concrete Moment Frames
CIO.3.2 Moment Frames
Typical Deficiencies
Load Path CIO.3.2.1 Sleel Momellt Frames
Redundancy
Vertical lrregularities CJO.3.2. J.J Drift The most direct mitigation approach
Plan lrregularíties is to add properly placed and distributed stiffening ele
Adjacent Buíldíngs ments-new moment frames, braced frames, or shear
Uplífl at Pile Caps walls-thal can reduce the slory drifts to acceptable
Detlection Compatibility levels. Altematively, the addition of energy dissipation
Concrete Moment Frames devices to the system may reduce the drifl, though
Quick Checks, Frame and Nonductile Detaíl Concerns
these are outside the scope of the Simplified
Precast Momem Frame Concerns
Rehabilitation Method [ASeE 31, Section 4.4.1.3.1
Frames Not Part of the Lateral-Force-Resisting System
Captíve Columns (ASeE 2002)].
Re-entrant Corners
Diaphragm Openings ClO.3.2.l.2 Frames Noncompact members can be
Díaphragm Sliffness/Strength eliminated by adding appropriate steel pi ates.
Díaphragm/Frame Shear Trans1'er Eliminating or properly reinforcing large member pen
Precast Connections etrations will develop the demanded strength and
Anchorage to Foundations deformations. Lateral bracing in the form of new sleel
Condition 01' Foundations components can be added 10 reduce member unbraced
Overturning
lengths to within the limits prescribed. Stitfening ele
Lateral Loads
ments (e.g., braced trames, shear walls, or additionaJ
Geologic Sile Hazards
moment frames) can be added throughout the building
Condition of Concrete
to reduce the expected frame demands [ASeE 31,
299
SEISMIC REHABILlTATION OF EXISTING BUILDlNGS
Table ClO-ll. CJ, CJA: Concrete Frames with Table CIO-I2. PC}: Precastlfilt-Up Concrete Shear
In611 Masonry Shear Walls and Stiff or Walls with Flexible Diapbragms
Flexible Diaphragms
Typical Deticiencies
Typical Deficiencies
Load Path
Load Path Redundancy
Redundancy Vertical Irregularities
Vel1ical Irregularities Plan Irregul31ities
Plan Irregularities DetlecLion Compatibility
Uplift at Pile Caps Diaphragm/Wall Shear Transfer
Deflection Compatibility Anchorage for Normal Forces
Frames Not PaJt oi' lhe Lateral-Force-Resisting System Girder/Wall Connections
Complete Frames Stifí'ness oí' Wall Anchors
Masonry Shear Walls Precast Concrete Shear Walls
Reinforcing in Masonry WaJ1s Panel-Lo-Panel Connections
Shear Stress Wall Openings
Reinforcing at Openings Collectors
Unreinforced Masonry Shear Walls Re-entrant Corners
Proportions. Solid Walls Cross Ties
Inlill Walls Diaphragm Openings
Re-entrant Comen, Diaphragm SliffnesslStrength
Diaphragm Openings Sheathing
Diaphragm Stiffness/StrengLh Unblocked Diaphragms
Span-to-Depth Ratio Span-to-Depth Ratio
Diaphragm/Wall Shear Transl'er Chord Continuity
Anchorage for Normal Forces Anchorage to Foundatíons
Anchorage LO Foundations Conditíon of Foundatíon
Condition ol' Foundations Overturning
OverLurning Lateral Loads
Lateral Loads Geologic Site Hazards
Geologic Site Hazards Condition of Concrete
Condition of Concrete
Quality of Masonry
300
ASCE/SEI 41-06
Table CIO-13. PCIA: Precastffilt-Up Concrete Table CIO-14. PC2: Precast Concrete Frames
Shear Walls with Stiff Diaphragms witb Shear Walls
301
SEISMIC REHABILlTATION OF EXISTING BUILDlNGS
Table CIO-15. PC2A: Precast Concrete Frames Table CIO-16. RMl: Reinforced Masonry Bearing
without Shear Walls Wall Buildings with Flexible Diaphragms
302
ASCFlSEJ 41-06
Table CIO-17. RM2: Reinforced Masonry Bearing Table CIO-18. URM: Unreinforced Masonry
Wall Buildings with StitT Diaphragms Bearing Wall Buildings with Flexible Diaphragms
303
SEISMIC REHABILITATION OF EXISTING BUILDING S
Table CIO-19. URMA: Unreinforced Masonry ner toreduce the shear stress for each wall. Replacing
Bearing Walls Buildings with Stiff Diaphragms heavy material s such as tile rooling wilh lighler male
rials will also reduce shear stress [ASCE 31, Sec
Typical Deficiencies lion 4.4.2.7.1 (ASCE 2002)].
Load Path
Redundancy C 10.3.3.4.2 Openings Local shear lransfer slresses
Verlical Irregularities can be reduced by dislributing lhe force s from the
Plan IITcgularities diaphragm. Chords and/or collector members can be
Adjacent Buildings provided to collecl and dislribule shear from lhe
Masonry Shear Walls diaphragm lo the shear wall or bracing [FEMA 172,
Unreinforced Masonry Shear Walls Figure 3.7.1.3 (FEMA 1992)1. AllernaLivcly, lhe open
Properties, Solid Walls ing can be c10sed off by adding a new wall wilh wood
Re-entrant Corners slructural panel shealhing [ASCE 31, Seclion 4.4.2.7.8
Diaphragm Openings
(ASCE 2002)].
Diaphragm Sliffness/Strength
Diaphragm/Wall Shear Transfer
Anchorage for Normal Forces CJO.3.3.4.3 Wall Detailing If lhe walls are not bolLed
Anchorage to Foundations lo lhe 1'oundation or if lhe bolLing is inadequale, bolLs
Condition of Foundations can be inslalled through lhe sill plales al regular inler
Geologic Site Hazards vals [FEMA 172, Figure 3.8.1.2a (FEMA 1992)J. If
Quality of Masonry lhe crawl space is nol deep enough ror vertical holes
to be drilled through the sill plale, lhe inslallalion of
conneclion pi ates or angles may be a practical alterna
live (FEMA 172, Figure 3.8.1.2b). Sheathing and addi
the wall over its full height. The slrong-back syslem
tional nailing can be added where walls Iack proper
must be designed for strength, connected to the struc
naiIing or conneclions. Where lhe exisling conneclions
lure in a manner that il: (J) develops the full yield
are inadequale, adding c1ips or slraps will deliver lal
slrength 01' the strong-back, and (2) connects to the
eral loads lo lhe walls and lo lhe foundalion sill plate
diaphragm in a manner that distributes the load into
[ASCE 31, Section 4.4.2.7.9 (ASCE 2002)].
the diaphragm and has sutticient stiffness to ensure
that the components will perform in a compatible and
acceptable manner. The stiffness of the bracing should CIO.3.3.4.4 Cripple Walls Where bracing is inade
limil the out-of-plane deflections to acceptable levels quate, new wood slruclural panel shealhing can be
such as L/600 to Ll900 [ASCE 31, Sections 4.4.2.4.4 added to lhe cripple wall sluds. The 10p edge of lhe
and 4.4.2.5.2 (ASCE 2002)]. wood slruclural panel is nailed lo lhe 1100r framing
and lhe bollom edge is naiIed into the sill plale
CJO.3.3.3.6 Jnjill Walls The partial infill wall should [FEMA 172, Figure 3.8.1.3 (FEMA 1992)]. Verify that
be isolated from the boundary columns to avoid a the cripple wall does not change height along its
"short column" etl"ect, except where it can be shown length (slepped top of foundation). If il does, lhe
thallhe column is adequale. In sizing lhe gap belween shorter porlion of lhe cripple wall will carry lhe major
lhe wall and lhe columns, lhe anlicipated slory drifl ity of the shear and signiíicanl lorsion will occur in lhe
musl be considered. The wall musl be posilively foundation. Added wood struclural panel sheathing
restrained againsl out-of-plane failure by eilher brac must have adequate slrenglh and slilTness lo reduce
ing lhe top of lhe walJ or inslalJing vertical girts. lorsion to an acceptable level. Also, it should be veri
These bracing componenls must not violate the isola fied thal the sill pi ate is properly anchored to the foun
lion of the frame from lhe infilJ [ASCE 31, Sec dation. If anchor bolts are lacking or insufticienl,
lion 4.4.2.6 (ASCE 2(02)]. addilional anchor bolts should be inslalled. Blocking
and/or framing c1ips may be needed to connecl lhe
CIO.3.3.4 Shear Walls in Wood Frame Buildings cripple wall bracing to the tloor diaphragm or lhe sill
plale [ASCE 31, Seclion 4.4.2.7.7 (ASCE 2002)].
CJ0.3.3.4.J Shear Stress Walls may be added or exisl
ing openings tilled. Alternatively, lhe existing walJs CIO.3.3.4.5 Narrow Wood Shear Walls Where narrow
and connections can be strenglhened. The walls should shear walls lack capacity, they should be replaced wilh
be dislribuled across lhe building in a balanced man shear walls with a heighl-to-widlh aspecl ralio of 2: I
304
ASCElSEI41-06
Table Clo-lO. Cross-Reference Between Tbis Standard and ASCE 311 Deficiency Reference Numbers
ASCE31 ASCE41
Section Section Heading Section Section Heading
4.3.1.1 Load Patb CIO.3.1.l Load Path
4.3.1.2 Adjacent Buildings C 10.3. 1.5 Adjacent Buildings
4.3.1.3 Mezzanines CIO.3.6.8 Mezzanine Connections
4.3.2 Configuration CIO.3.1 Building Systems
4.3.2.1 Weak Story C1O.3.1.3 Verticallrregularities
4.3.2.2 Soft Story CIO.3.1.3 Verticallrregularities
4.3.2.3 Geometry C 10.3. 1.3 Vertical Irregularities
4.3.2.4 Vertical Discontinuities CIO.3.1.3 Vertical Irregu [arities
4.3.2.5 Mass ClO.3.1.3 Vertical Irregularities
4.3.2.6 Torsion CIO.3.I.4 Plan Irregularities
4.3.3 Condition of Materials ClO.3.8 Evaluation of Materials and Conditions
4.3.3.1 Deterioration of Wood CIO.3.8.2 Condilion of Wood
4.3.3.2 Wood Structural Panel Shear Wall Fasteners ClO.3.8.3 Wood Slructural Panel Shear Wall Fasteners
4.3.3.3 Deterioralion of Steel CIO.3.8.4 Condition of Steel
4.3.3.4 Deterioration of Concrete ClO.3.8.5 Condition of Concrete
4.3.3.5 Post-Tensioning Anchors CIO.3.8.6 Post-Tensioning Anchors
4.3.3.6 Precast Concrele Walls CIO.3.8.5 Condition of Concrete
4.3.3.7 Masonry Units CIO.3.8.7 Quality of Masonry
4.3.3.8 Masonry Joínts CIO.3.8.7 Quality of Masonry
4.3.3.9 Concrete Wall Cracks CIO.3.8.5 Condition of Concrete
4.3.3.10 Reinforced Masonry WalI Cracks CIO.3.8.7 Quality of Masonry
4.3.3.11 Unreinforced Masonry Wall Cracks CIO.3.8.7 Quality of Masonry
4.3.3.12 Cracks in Inlill Walls CIO.3.8.7 Quality of Masonry
4.3.3.13 Cracks in Boundary Columns CIO.3.8.5 Condition of Concrete
4.4.1.1.1 Redundancy C 10.3. 1.2 Redundancy
4.4.1.2 Momeot Frames wiili InfiU Walls CIO.3.3 ShearWalls
4.4.1.2.1 Interfering Walls C 10.3.3.3.6 Infill Walls
4.4.1.3 Stecl Moment Frames CIO.3.2.l Steel Moment Frames
4.4.1.3.1 Drift Check CIO.3.2.1.l Dríft
4.4.1.3.2 Axial Stress Check CIO.3.2.1.2 Frames
4.4.1.3.3 Moment-Resisting Connections C 10.3.2.1.4 Connections
4.4.1.3.4 Panel Zones C 10.3.2.1.4 Connections
4.4.1.3.5 Column Splices C 10.3.2.1.2 Frames
4.4.1.3.6 Strong CoIumn-Weak Beam CIO.3.2.1.3 Strong Column-Weak Beam
4.4.1.3.7 Compact Members CIO.3.2.1.2 Frames
4.4.1.3.8 Beam Penetratíon C 10.3.2.1.2 Frames
4.4.1.3.9 Girder Flange Continuity CIO.3.2.1.4 Connections
4.4.1.3.10 Out-of-Plane Bracing CIO.3.2.1.2 Frames
4.4.1.3.11 Bouom F1ange Bracing C 10.3.2.1.2 Frames
4.4.1.4 Concrete Moment Frames CIO.3.2.2 Concrete M oment Frames
4.4.1.4.1 Shear Stress Check CIO.3.2.2.1 Frame and Nonductile Detail Concems
4.4.1.4.2 Axial Stress Check C 10.3.2.2. I Frame and Nonductile Detaíl Concems
4.4.1.4.3 Flat Slab Frames C 10.3.2.2.1 Frame and Nonductile Detail Concems
4.4.1.4.4 Prestressed Frame Elements C 10.3.2.2.1 Frame and Nonductile Detail Concems
4.4.1.4.5 Captive Columns CIO.3.2.3.2 Captive Columns
4.4.1.4.6 No Shear Failures C 10.3.2.2.1 Frame and Nonductile Detail Concems
4.4.1.4.7 Strong Column-Weak Beam C 10.3.2.2.1 Frame and Nonductile Detail Concems
4.4.1.4.8 Beam Bars CIO.3.2.2.1 Frame and Nonductile Detail Concems
4.4.1.4.9 Column-Bar Splices CI0.3.2.2.1 Frame and Nonductile Detail Concerns
4.4.1.4.10 Beam-Bar Splices CIO.3.2.2.1 Frame and Nonductile Detail Concerns
4.4.1.4.11 Columo-Tie Spacing C 10.3.2.2.1 Frame and Nonductile Detail Concerns
4.4.1.4.12 Stin'up Spacing C 10.3.2.2.1 Frame and Nonductile Detail Concerns
continued
305
SElSMIC REHABILlTATION OF EXISTING BUILOINGS
306
ASCE/SEI 41-06
ASCE 31 ASCE41
Mction Section Heading Section Mction Heading
4.4.3.1 Braced Frames CIO.3.4 Steel Braced Frames
4.4.3.1.1 Redundancy ClO.3.1.2 Redundancy
4.4.3.1.2 Axial Stress Check ClO.3.4.1 System Concerns
4.4.3.1.3 Column Splices CIO.3.4.4 Braced Frame Connections
4.4.3.1.4 Slenderness of Diagonals ClO.3.4.2 Stiffness of Diagonals
4.4.3.1.5 Connection Slrenglh ClO.3.4.4 Braced Frame Connectiolls
4.4.3.1.6 Out-of-Plane Bracing CIO.3.4.1 System Concerns
4.4.3.2 Concentrically Braced Frames CIO.3.4 Steel Braced Frames
4.4.3.2.1 K-Bracing CIO.3.4.3 Chevron or K-Bracing
4.4.3.2.2 Tension-Only Braces CIO.3.4.2 Stiflness of Diagonals
4.4.3.2.3 Chevron Bracing ClO.3.4.3 Chevron or K-Bracing
4.4.3.2.4 Concentrically Braced Frame Joints CIO.3.4.4 Braced Frame Connections
4.4.3.3 Eccentrically Braced Frames CIO.3.4.1 System Concerns
4.5 Diaphragms ClO.3.5 Diaphragms
4.5.1.1 Diaphragm Continuily C 10.3.5.4.5 Díaphragm Continuity
4.5.1.2 Cross Ties CIO.3.5.2 Cross Tíes
4.5.1.3 Roof Chord Continuily CI0.3.5.4.6 Chord Continuity
4.5.1.4 Openings at Shear WaIls CIO.3.5.3 Diaphragm Openings
4.5.1.5 Openings al Braced Frames CIO.3.5.3 Diaphragm Openings
4.5.1.6 Openings al Exterior Masonry Shear Walls ClO.3.5.3 Diaphragm Openings
4.5.1.7 Plan Irregularities ClO.3.5.1 Re-enlran! Corners
4.5.1.8 Diaphragm Reinforcing al Openings CIO.3.5.3 Díaphragm Openíngs
4.5.2 Wood Diaphragms CIO.3.5 Diaphragms
4.5.2.1 Slraighl Sheathíng ClO.3.5.4.1 Board Sheathing
4.5.2.2 Spans ClO.3.5.4.3 Spans
4.5.2.3 Unblocked Diaphragms CIO.3.5.4.2 Unblocked Diaphragms
C I0.3.5.4.4 Span-to-Depth Ralio
4.5.3 Metal Deck Diaphragms ClO.3.5 Diaphragms
4.5.3.1 Non-Concrete FiIled Diaphragms CIO.3.5 Diaphragms
4.5.4 Concrete Diaphragms CIO.3.S Diaphragms
4.5.5 Precast Concrete Diapbragms CIO.3.5 Diaphragms
4.5.5.1 Topping Slab ClO.3.5 Diaphragms
4.5.6 Horizontal Bracing ClO.3.5 Diaphragms
4.5.7.1 Otber Diaphragms CIO.3.5 Diaphragms
4.6.1 Ancborage for Normal Forces CIO.3.6.3 Anchorage for Normal Forces
4.6. I.l Wall Anchorage CIO.3.6.3 Anchorage for Normal Forces
4.6.1.2 Wood Ledgers CIO.3.6.3 Anchorage for Normal Forces
4.6.1.3 Precast Panel Connections CIO.3.6.3 Anchorage for Normal Forces
4.6.1.4 Sliflness of WaIl Anchors ClO.3.6.3 Anchorage for Normal Forces
4.6.2 Sbear Transfer ClO.3.6 Connections
4.6.2.1 Transfer to Shear Walls ClO.3.6.1 Diaphragm/Wall Shear Transfer
4.6.2.2 Transfer 10 Steel Frames ClO.3.6.2 Diaphragm/Frame Shear Transfer
4.6.2.3 Topping Slab to Walls or Frames ClO.3.6.1 Diaphragm/Wall Shear Transfer
4.6.3 Vertical Components CIO.3.7.1 Anchorage to Foundations
4.6.3.1 Steel Columns ClO.3.7.1 Anchorage to Foundations
4.6.3.2 Concrete Columns ClO.3.7.l Anchorage to Foundations
4.6.3.3 Wood Posts CIO.3.7.1 Anchorage to f<oundalions
4.6.3.4 Wood Sills CIO.3.7.l Anchorage lO Foundations
4.6.3.5 Foundalion Dowels ClO.3.7.1 Anchorage to Foundations
4.6.3.6 Shear-Wall-Boundary Columns ClO.3.7.1 Anchorage 10 Foundations
4.6.3.7 Precast Wall Panels ClO.3.7.1 Anchorage to Foundations
4.6.3.8 Wall Panel s CIO.3.7.1 Anchorage to Foundations
4.6.3.9 Wood SiIl Bolts CIO.3.7.1 Anchorage to Foundations
4.6.3.10 Uplift at Pile Caps CIO.3.7.4 Lateral Loads
continued
307
SElSMIC REHABILlTATION OF EXISTING BUILDlNGS
or less. These replaeement walls must have sufticient C10.3.4 Steel Braced Frames
strength, including being adequately conneeted to the
diaphragm and sufficiently anehored to Ihe foundation C10.3.4.1 System CQncerns
for shear and overturning force s [ASCE 31, Sec If the strength of the braced frames is inadequate,
tion 4.4.2.7.4 (ASCE 2002)]. more braced bays or shear wall panel s can be added.
Thc resulting lateral-force-resisting system must form
a weIl-balanced syslem 01' braeed frames that do not
C 10.3.3.4.6 Stucco Shear Walls For strengthening or
fail al lheir joints, are properly connected to Ihe 1100r
repair, the stueeo should be removed, a wood strue
diaphragms, and whose failure mode is yielding of
tural panel shear wall added, and new stuceo applied.
braces rather than overturning [ASCE 31, See
The wood structural panel should be the manufac
tions 4.4.3.1.1 and 4.4.3.1.2 (ASCE 2002)].
turer's recommended thiekness for the installation of
stueco. The new stucco should be installed in accor
C10.3.4.2 Stiffness of Diagonals
dance with building eode requirements 1'or waterproof
DiagonaJs with inadequale slitfness should be
ing. WalIs should be sufficiently anchored lo the
strenglhened using supplemental steel plates. or
diaphragm and foundation [ASCE 31, Sec
replaced with a larger and/or different type of seetion.
tion 4.4.2.7.2 (ASCE 2002)].
Global stil'fness can be increased by the addition ol'
braeed bays or shear walI panels [(ASCE 31, See
C 10.3.3.4.7 Gypsum Wallboard or Plaster Shear Walls tions 4.4.3.1.3 and 4.4.3.2.2 (ASeE 2002)].
Plaster and gypsum wallboard can be removed and
repJaced with slructuraJ panel shear wall as rcquired, CIO.3.4.3 Chevron or K-Bracing
and the new shear waJls eovered with gypsum wall Columns or horizontal girts can be added as
board [ASCE 31, Seetion 4.4.2.7.3 (ASCE 2002)]. needed lo support the tension brace when the eompres
308
ASCE/SEI 41-06
sion brace buckles, or Ihe bracing can be revised lo Seclions 4.5.1.4 through 4.5.1.6 and 4.5.1.8 (ASCE
anolher syslem IhroughoUl Ihe building. The beam 2002)].
componenls can be slrenglhened with cover plales lo
provide lhem wilh Ihe capacity lo fully develop Ihe CIO.3.5.4 Diaphragm Stiffness/Strength
unbalanced forces crealed by lensíon brace yíelding
[ASCE 31, SecLÍons 4.4.3.2.1 and 4.4.3.2.3 (ASCE C1O.3.5.4.1 Board Sheathing Where lhe diaphragm
2002)]. does nOl have al least lwo nails through each board
inlo each of lhe supporling members, and lhe laleral
CI0.3.4.4 Braced Frame Connections drift andlor shear demands on lhe diaphragm are nOI
Column splíces or other braced trame connections excessive, lhe shear capacity and stiffness of lhe
can be strenglhened by adding pIates and welds to diaphragm can be increased by adding nails al lhe
ensure Ihal Ihey are slrong enough lo develop the con shealhing boards. This melhod 01' upgrade is mosl
necled componenls. Connectíon eccentricities thal often suilable in areas of low seismicíty. In olher
reduce component capacities can be e1iminated, or Ihe cases, a new wood slruclural panel should be placed
componenls can be sLrenglhened lo lhe required level over the existing slraíght sheathing, and Ihe joinls of
by Ihe addilion of properly placed plales. Demands lhe wood slructural panels placed so lhey are near lhe
on the exisling elemenls can be reduced by addíng center 01' lhe sheathing boards or al a 45-degree angle
braced bays or shear wall panel s [ASCE 31, Sec lO Ihe joints belween shealhing board s [FEMA 172,
tions 4.4.3.1.4 and 4.4.3.1.5 (ASCE 2002)]. Seclion 3.5.1.2 (FEMA 1992); ATC-7 (ATC 1981),
and ASCE 31, Seclion 4.5.2.1 (ASCE 2002)].
CIO.3.5 Diaphragms
C 10.3.5.4.2 Unblocked Diaphragm The shear capacily
CIO.J.S.I Re·Entrallt Corners of unblocked diaphragms can be improved by adding
New chords wilh suflícienl slrength lo resist Ihe new wood blocking and naíling al lhe unsupporled
required force can be added al Ihe re-entrant comer. If panel edges. Placing a new wood structural panel over
a verlicallaleral-force-resisling element exists al the lhe exisling diaphragm will increase lhe shear capac
re-entranl corner, a new colleclor component should ¡Iy. Both of lhese melhods will require lhe paníal or
be inslalled in lhe diaphragm 10 reduce lensile and total removal 01' existing tlooring or roofing lo place
compressive forces at lhe re-entranl comer. The same and naH Ihe new overlay or nall lhe existíng paneIs lo
basic matefÍals used in the diaphragm should be used Ihe new blocking. Strenglhening 01' Ihe diaphragm is
for the chord [ASCE 31, Section 4.5.1.7 (ASCE usually nOI necessary al Ihe cenlral area of lhe
2002)]. diaphragm where shear is low. In cerlain cases where
Ihe design loads are low, it may be possible to increase
CIO..1.S.2 CrtJss Ties the shear capacíty of unblocked diaphragms with sheet
New cross lÍes and wall connections can be added metal plales slapled on Ihe underside 01' lhe exisling
10 resisl lhe required out-of-plane wall forces and dis wood panels. These plales and slaples must be
tribute these forces lhrough Ihe diaphragm. New strap deslgned for all related shear and LOrsion caused by Ihe
plates and/or rod conneclions can be used lo connecl delails related lo theÍr inslallalion [ASCE 31, Sec
exisling framing members logether so they funclÍon as tion 4.5.2.3 (ASCE 2002)].
a cross tie in lhe diaphragm [ASCE 31, SeclÍon4.5.1.2
(ASCE 2002)]. C1O.3.5.4.3 Spans New vertical elemenls can be added
to reduce the diaphragm span. The reduction of the
CIO.J.S.J Diaphragm Openillgs diaphragm span will also reduce the lateral det1ection
New diaphragm líes or chords can be added and shear demand in lhe diaphragm. However, adding
around Ihe perímeler 01' existing openings lo dislribule new verlical elements will result in a dif1'erenl dislribu
lension and compression forces along Ihe díaphragm. lion of shear demands. Additional blocking, naíling, or
The exisling shealhing should be nailed lo Ihe new other rehabilitalion measures may need to be provided
diaphragm lÍes or chords. In 50me cases il may al50 be at lhese areas [FEMA 172, Seclion 3.4 (FEMA 1992)
necessary to: (1) increase tbe shear capacily of Ihe andASCE 31, SeclÍon 4.5.2.2 (ASCE 2002)].
diaphragm adjacenl 10 Ihe opening by overlaying Ihe
exisling diaphragm wilh a wood struclural panel, or C /0.3.5.4.4 Span-to-Depth Ratio New vertical ele
(2) decrease lhe demand on lhe diaphragm by adding ments can be added 10 reduce Ihe diaphragm span-Io
new vertical elements near lhe opening [ASCE 31, deplh ratio. The reduction of lhe diaphragm span-to
309
SEISMIC REHABILlTATlON OF EXlSTING BUlLDlNGS
depth ratio will al so reduce the lateral detlection and CIO.3.6.3 Anehorage forNormal Porees
shear demand in the diaphragm. Typical construction To accounl for inadequacies identilied by
details and methods are discussed in FEMA 172, ASCE 31, wall anchors can be added. ComplicaLions
Section 3.4 (FEMA 1992). lhal may result from inadequale anchorage indude
cross-grain lension in wood ledgers or failure 01" lhe
CJ0.3.5.4.5 Diaphragm Continuity The diaphragm dis diaphragm-lo-wall conneclion due lo: (1) insufticient
continuity should in all cases be eliminated by adding slrenglh, number, or slabilily 01' anchors; (2) inade
new vertical elements at the diaphragm offset or the quale embedmenl of anchors; (3) inadequale develop
expansion joint [FEMA 172, Section 3.4 (FEMA menl of anchors and slraps inlo the diaphragm; and
J 992)]. In sorne cases, special details may be used to (4) deformalion of anchors and lheir l'asleners lhal per
transfer shear across an expansion joint-while still mil diaphragm boundary conneclion pu1lOU1, or eros s
alIowing the expansion joint to function-thus elimi grain lension in wood ledgers.
nating a diaphragm discontinuity [ASCE 31, Sec Exisling anchors should be lesled lo delermine
tion 4.5.1.1 (ASCE 2(02)]. load capacity and deformalion pOlenlial, induding fas
lener slip, according lo lhe requirements in ASCE 31.
CJO.3.5.4.6 Chord Continuity If members such as Special attenlion should be given lo lhe lesling proce
edge joiSlS, blocking, or walI lop plales have lhe dure lo mainlain a high level ol' qualily conlrol.
capacily lo funclion as chords bul lack conneclion, AddiLional anchors should be provided as needed lo
adding nailed or bolted conlinuily splices wilI provide supplemenl lhose lhal fail lhe lesl, as well as lhose
a conlinuous diaphragm chord. New conlinuous sleel needed lo meel lhe ASCE 31 crileria. The qualily of
or wood chord members can be added lo lhe exisling lhe rehabililalion depends greally on lhe qualily of lhe
diaphragm where exisling members lack sufticienl performed lesls [ASCE 31, SecLions 4.6.1.1 through
capacity or no chord exists. New chord members can 4.6.1.5 (ASCE 2002)].
be placed al eilher lhe underside or lopside of lhe
diaphragm. In sorne cases, new verlical elemenls can CIO.3.6.4 Girder-Wall COlllleetions
be added lo reduce lhe diaphragm span and slresses The exisling reinforcing musl be exposed, and lhe
on any exisling chord members [FEMA 172, Sec conneclion modified as necessary. For oUl-of-plane
lion 3.5.1.3 (FEMA 1992) and ATC-7 (ATC 1981)]. loads, lhe number ol' column lies can be increased by
New chord conneclions should nol be delailed such jackeling lhe pilaster or, alternalively, by developing a
lhal lhey are lhe weakesl componenl in lhe chord second load palh for lhe oUl-of-plane forces. Bearing
[ASCE 31, Seclion 4.5.1.3 (ASCE 2(02)]. lenglh condilions can be addressed by adding bearing
eXlensions. Frame aclion in welded conneclions can be
CIO.3.6 Connections miligaled by adding shear walls [ASCE 31, Sec
lion 4.6.4.1 (ASCE 2(02)].
CIO.3.6.1 Diaphragm/Wall Shear Transfer
Collector members, splice plales, and shear lrans
fer devices can be added as required lo deliver collec CIO.3.6.5 Preeast COllneetiolls
lor forces lo lhe shear wall. Adding shear conneclors The connections of chords, lies, and colleclors can
from lhe diaphragm lo lhe wall and/or lo lhe colleclors be upgraded lo increase slrenglh and/or dUClilily, pro
wilI lransfer shear. See FEMA 172, Seclion 3.7 for viding allernative load palhs for laleral forces.
Wood Diaphragms, 3.7.2 for concrele diaphragms, Upgrading can be achieved by such melhods as adding
3.7.3 for poured gypsum, and 3.7.4 for melal deck confinemenl lies or increasing embedment. Shear
diaphragms (FEMA 1992) and ASCE 31, Sec walls can be added lo reduce lhe demand on connec
tions 4.6.2.1 and 4.6.2.3 (ASCE 2(02). tions [ASCE 31, Section 4.4.1.5.3 (ASCE 2002)].
310
ASCBlSEI 41-06
3\1
SEISMIC REHABILITATION OF EXISTING BUILDINGS
resisting systems in accordance with ASCE 31 (ASCE of steel component or connection deterioration, further
2002). This inspeclion should include lhe following: evaluation is needed. The source 01' the damage shall
be identified and mitigated to preserve the remaining
l. Verify exisling dala (e.g., accuracy of drawings);
structure. In areas of significant deterioration, res tora
2. Develop olher needed data (e.g., measure and
lion of the material cross section can be performed by
sketch building if necessary);
the addition of pIates or other reinforcing techniques.
3. Verify the vertical and lateral systems;
When sizing reinforcements, the design professional
4. Check the condition of the building;
shall consider the effects of existing stresses in the
5. Look for special conditions and anomalies;
original structure, load Lransfer, and strain compalibil
6. Address lhe evaluation statements and goals during
ity. The demands on the deterioraled sLeel elements
lhe inspection; and
and components may also be reduced through careful
7. Perform material tests that are justified through a
addilion of bracing or shear wall panel s [ASCE 31,
weighing of the cost of destructive testing and the
Section 4.3.3.3 (ASCE 2002)].
cost of corrective work.
The materials testing and evalualion methods of
this standard should nol be used for Simplitied
CIO.3.8.5 Conditioll 01 Concrete
Should visual inspections or testing conductcd in
Rehabilitation except those required for all new work
accordance with Seclion C 10.3.8.1 reveal the presence
specified in Lhe ConsLruction Quality Assurance Plan.
of concrete component or reinforcing steel deteriora
tion, further evaluation is needed. The source of Ihe
CIO.3.8.2 COI.dition ofWood
damage shall be identified and mitigaled lO preserve
l An inspection should be conducled to grade the
J the remaining structure. Existing deteriorated material,
:¡
existing wood and verify physical condilion, using
including reinforcing steel, shall be removed lo the
.. iLl techniques from Section C 10.3.8.1. Any damage or
t
limits detined by testing; reinforcing steel in good
.!t deterioralion and its source must be identified. Wood
:5: condition shall be cleaned and left in place for splicing
that is signiticantly damaged due lo splining, decay,
purposes as appropriate. Cracks in otherwise sound
aging, or other phenomena must be removed and
material shall be evaluated lO determine cause, and
replaced. Localized problems can be eliminated by
repaired as necessary using techniques appropriate
adding new appropriately sized reinforcing compo
lO the source and activity level [ASCE 31, Sec
nents eXlending beyond the damaged area and con
tíon 4.3.3.4 (ASCE 2002)]. FEMA 306 (FEMA 1998),
necting lo undamaged portions. Additional connectors
FEMA 307 (FEMA 1998), and FEMA 308 (FEMA
between components should be provided to correct
1998) can be used as a source 01' further information
any discontinuous load paths. lt is necessary to verify
on evaluation and repair oí' concrete wall buildings.
!hat any new reinforcing components or connectors
will not be exposed 10 similar deterioration or damage
[ASCE 31, Section 4.3.3.1 (ASCE 2002)]. CI0.3.8.6 Post· Tensiollillg Anchors
Prestressed concrete systems may be adversely
CIO.3.8.3 Wood Structllral Panel Shear Wall Fasteners atrected by cyclic deformations produced by earth
Where visual inspection determines that extensive quake motion. One rehabilitation process that may be
overdriving of fasteners exists in greater than 20% 01' considered is to add stitfness to the system. Anolher
the inslalled connectors, the fasteners and shear panels concern for these systems is the adverse effects 01' tcn
can generally be repaired lhrough addition ol' a new don corrosion. A thorough visual inspection of pre
same-sized fastener for every two overdriven tasteners. stressed systems shall be performed to veril'y absence
To avoid splitting because 01' closely spaced nails, it of concrete cracking or spalling, staining from embcd
may be necessary to predrill lo 90% of lhe nail shank ded tendon corrosion, or other signs of damage along
diameter for installation of new nails. For other condi the tendon spans and al anchorage zoncs. If degrada
lÍons, such as cases where lhe addition of new connec lion is obscrved or suspected, more detailed evalua
tors is not possibJe or where componenl damage is tions will be required as indicated in Chapler 6.
suspected, further investigation shaIl be conducted Rehabilitation of these systems, except ror local
using the guidance of Section C 10.3.8.1 [ASCE 31, anchorage repair, should be in accordance wÍlh lhe
Seclion 4.3.3.2 (ASCE 2002)]. Systematic Rehabilitation provisions in this standard.
ProJessionals with special prestressed concrete con
CIO.3.8.4 Condition 01 Steel struction expertise should also be consulted ror further
Should visual inspection or testing conducted in interpretation of damage [ASCE 31, Seclion 4.3.3.5
accordance with Section C 10.3.8.1 reveal lhe presence (ASCE 2002)].
312
ASeE/SEI 41-06
313
SEISMIC REHABILITATION OF EXISTING BUILDlNGS
314
ASCElSEI41-06
credible and significant sources of interaction should of the 1971 San Fernando earthquake, it became c1ear
be consídered in (he conditíon assessment. that damage to nonstructural components could result
in serious casualtíes, severe building functional
11.2.2 Sample Size ímpairmenr, and major economíc losses, even where
Direct visual inspection shall be performed on structural damage was nol signiticant (Lagorio 1990).
each type 01' nonstructural component in the building This historical perspeclive presents Ihe background for
as follows: the developmenl of building code provisions, logether
l. If detailed drawings are available, at Jeast one sam with a hislorical review of professional and conslruc
pie of each type 01' nonstructural component shall tion practices related to Ihe seismic design and con
be observed. If no devialions 1'rom the drawings struction of nonslruclural components. Since Ihe 1964
exisl, the sample shall be considered represenlative Alaska earlhquake, the poor performance of nonslruc
of installed conditions. If deviations are observed, lural components has been idemified in earlhquake
lhen at least 10% of aH occurrences of the compo reconnaissance reporls. Subsequent editions 01' lhe
nent shaH be observed; and Uniform Building Code (rCBO 1994), as well as
2. If delaiJed drawings are not available, al leasl three California and federal codes and laws have increased
samples 01' each type of nonslructural component bOlh Ihe scope and strictness of nonslruclural seismic
shall be observed. If no devíations among the (bree provisions in an allempt lo achieve betler performance.
components are observed, the sample shall be con Table C 11 I and Table Cl1-2 provide a comprehen
sidered representalive 01' installed condilions. lf sive Iisl of nonstruclural hazards Iha! have becn
devialions are observed, at leasl 20% of aH occur observed in Ihese carthquakes.
rences of the cornponent shall be observed. The followíng quole, taken from statements made
after lhe Alaska earlhquake, characrerizes the hazard
nonstruclural components pose to building occupants:
11.3 HISTORICAL ANO COMPONENT
EVALUATlON CONSIDERATlONS "U, duríng an earthquake, [building occupanls)
must exil Ihrough a shower of falling Iight fix
11.3.1 Historical Information lures and ceilings, maneuver lhrough shifting
Available constructíon documents, equípment and lopplíng furnilure and equipment, stumble
specilication and data, and as-buih information shalI down dark corridors and debris-Iaden slairs, and
be obtained as specifíed in Section 2.2. Data on then be mel al lhe slrect by falling glass,
nonstructural components and equipment shall be coJ veneers, or facade components, lhen the building
lecled lo estimale Ihe year of manufacture or installa cannor be described as a safe structure." (Ayres
lÍon of nonstruclural components lo juslify seleclion 01' and Sun, 1973a)
rehabililation approaches and techniques based on In reviewing Ihe design and construction of archi
available hislorical informalion, prevailing endes, and lectural nonstruclural componenls ín this century, four
assessmenl of existing condilions. general phases can be distinguished.
Cll.3.1 Historical Information A. Phase 1: 1900 to 1920s
The architectural, mechanical, and e1ectrical com Buildings featured monumental classical architec
ponenls and syslems of a historic building may be his ture, generally wilh a sleel frame struclUre using slone
torically signiticant, especially if they are original to facing with a backing of unreinforced masonry and
lhe building, very old, or innovalive. Historie buildings concrele. Interior partitions were of unreinforced hol
may also conlain hazardous malerials, such as lead low clay tile or brick unil masonry, or wood partilions
pipes and as bes lOs, that may or may not pose a hazard wilh wood lath and plasler. These buildings had natu
depending on their location, condilion, use or aban ral ventilation systems with hOI water radiators (later,
donment, conlainment, and/or dislurbance during the forced-air), and surface- or pendanl-mounled incan
rehabilitalion. descenl lighl flxlUres.
8. Phase 2: 19308 to 19508
C11.3.1.1 Background Buildings were characlerized by poured-in-place
Prior lO Ihe 1961 Uniform Building Code and lhe reinforced concrete or sleel frame slruclures, employ
1964 Alaska earlhquake, architectural components and ing columns and (in California) Iimiled exterior and
mechanical and electrícal syslems for buildings had interior shear walls. Windows were large and horizon
lypically been designed wilh liule, if any, regard to tal. Interior partitíons of unreinforced hollow clay tile
slabiJily when subjecled lo seismic forces. By lhe time or concrete block unit masonry, or lighl wood frame
315
SElSMIC REHABILlTATION OF EXlSTING BUILDlNGS
Table U-l. Nonstructural Components: Applicability of Hazards Reduced, Life Safety and Immediate
Occupancy Requirements and Metbods of Analysis
Performance LeveJ
Seismicity
High and
Moderate Low
Seismicity Seismicity
Evalualion
Component Type 10 LS HR LS HR Procedure
Architectural (Section 11.9)
l. Exterior Wall Components
Adhered Vencer Ves Ves Yes l ; No No FID
Anchored Vencer Ves Ves Yes l ; No No FID
Glass Blocks Ves Ves Yes l ; No No FID
Prei~lbricated Panel s Ves Ves Yes l ; Ves Yes l ; FID
Glazed Exterior Wall Systems Ves Ves Yes l ; Ves Yes" FID/PR
2. Partitions
Heavy Ves Ves Yes" No No FID
Lighl Ves No No No No FlD
Glazed Ves Ves Yes" Ves Yes" F/O/PR
3. Interior Veneers
Stone, lnc1uding Marble Ves Yes lK Yes l ' No No FID
4. Ccilings
Directly Applíed lo Struclure Ves Nol.' No" No No F
Dropped Furred Gypsum Board Ves No No No No F
Suspended Lath and Plaster Ves Ves Yes l; No No F
Suspended lntegrated Ceiling Ves Nol' No Noll No PR
5. Parapets and Appendages Ves Ves Yes l; Ves Ves pi
6. Canopies and Marquees Ves Ves Yes l ; Ves Ves F
7, Chimneys and Stacks Ves Ves Yes l; No No f1
8. Stairs Ves Ves No Ves No *
Mechanical Equipment (Section 11.10)
l. Mechanical Equipment
Boilers, Furnaces, Pumps, and Chillers Ves Ves No Ves No F
General Mfg. and Process Machinery Ves No' No No No F
HVAC Equipment, Vibration-Isolated Ves No 3 No No No F
HVAC Equipment, Non-Vibratíon-lsolated Ves No' No No No F
HVAC Equipment, Mounted In-Une with Ductwork Ves No' No No No PR
2. Storage Vessels and Water Heaters
Structurally Supported Vessels (Category 1) Ves No' No No No Note4
Aat-Botlom Vessels (Category 2) Ves No) No No No Note'
3. Pressure Piping Ves Ves No No No Note-'
4. Fire Suppl'ession Piping Ves Ves No No No PR
5. Fluid Piping, not Fire Suppression
Hazardous Materials Yes Ves Yes l2 Ves Yes l2 PRlF/D
Nonhazardous Materials Yes l4 No No No No PR/F/D
6. Ductwork Ves No 6 No No No PR
Electrical And Communications (Section 11.10)
1. Electrical and Communications Equipment Ves No? No No No F
2. Electrical and Communications Distribution Equipment Ves No~ No No No PR
3. Light Fixtures
Recesscd No No No No No PRI7
Surface-Mounted No No No No No PRI7
Integrated Ceiling Ves Ves Yes l5 No No PR
Pendant Yes No 9 No No No F/PR
316
ASCPJSEI 41-06
Performance Level
Seismicity
High and
Modera!e Low
Seismicity Seismicity
Evaluation
Componen! Type 10 LS HR LS HR Procedure
lRehabilitation of unreinforced masonry parapels nol over 4 fI in heighl by lhe Prescriplive Design Concept shall be permitted.
2Rehahilitation 01' residential masonry chimneys by Ihe Prescriplive Design Concept shall be permitted.
3Equipment type 1 or 2 Ihat is 6 ft or more in heighl, equipmenl type 3, equipment fornlÍng part of an emergency power system. and gas-fired
equipment in occupied or unoccupied space shall be rehabilitated to the Life Safely Nonstructural Performance Level in areas of High Seismicíty.
In areas of Moderate Seismicity. Ihis equipment need nOI be considered. Refer 10 Section 11.10.1.1 for equipmenl type designations.
4Rehabilitation of residential water heaters wilh capacily less Ihan 100 gal by the Prescriplive Procedure shaJl be permitted. Other vessels shall
meet the force provisions of Sections 11.7.3 or 11.7.4.
5Rehabilitalion of vessels or piping systems according 10 Prescriptive Slandards shall be permitted. Storage vessels shall meel the force provisions
of Seclions 11.7.3 or 11.7.4. Piping shall meel drift provisions of Section 11.7.5 and ¡he force provisions of Sectiolls 11.7.3 or 11.7.4.
6Duclwork that conveys hazardous materials. exceeds 6 sf in cross-sectional area, or is suspended more Ihan 12 in. from 10p of ducI 10 supporting
strucnue al any support point shatl meel lhe requirements of the selecled Rehabililation Objective.
1Equipment thal is 6 ft or more in height, weighs over 20 lbs., or forms part of an emergency power andlor communication system shall meel !he
Life Safely Nonstructural Performance Level.
gEquipmenl that forms part of an emergency lighting, power, andlor communication system shall meet the Life Safety Nonstruclural Performance
Level.
9Fixtures thal exceed 20 lbs. per suppon shall mee! the Life Safety Nonslructural Performance Level.
IORehabilitalion shall not be required for slorage racks in unoccupied spaces.
"Panels lhal exceed 2 Ibs/sf, or for which Enhanced Rehabililation Objectives have been selected. shall meet the Life Safely Nonstruclural
Performance LeveL
12Where material is in c10se proximity lO occupancy such Ihat leakage could cause an immediate Jife safety threat, the requirements of tbe selected
Rehabilitation Objeclive shall be me!.
I3Plaster ceilings on metal or wood lath over 10 sf in area shall meet !he Life Safety Nonstructural Performance Leve!.
"Unbraced pressure pipes wilh a 2-in. or larger diameter and suspended more Ihan 12 in. from !he top of lhe pipe to the supponing slruclure al
any suppon poinl shall meet the requirements of the selected Rehabililalion Objective.
I'Where heavy nonstruclura! components are located in areas of public occupancy or egress, Ihe componenls shall meet the Life SafelY
Nonstruclural Performance Leve!.
'6Storage racks in areas of public assembly shall meet the requirements of the selecled Rehabililation Objective.
I1Evaluation for the presence of an adequate attachmt:nt shall he checked as described in Section 11.10.9.3.
'"In areas of Moderate Seismicily, interior veneers of ct:ranlÍc tile need not he considered.
Kt:y:
HR, Hazards Reduced Nonstruclural Perfonnance Level; LS, Life SafelY Nonstructural Performance Level; lO, Immediatc Occupancy
Nonslructural Performance Level; PR, Use of the Prescriptive Procedure of Seclion 11.7.2 shall be permitted; F. the AnalYlical Procedure of
Section 11.7.1 shall be implemented and a force analysis shall be pt:rfomled in accordance wilh Sections 11.7.3 or 11.7.4; F/D. the Analytical
Proccdure of Section JI. 7. J shall be implenlented and a force and deformation anal ysis shaIl be perforllled in accordance wilh Sections I 1.7.4 and
J 1.7.5, respectively.
* Individual components shall be rehabilitated as required.
317
SEISMIC REHABILlTATION OF EXISTING BUILDINGS
partitions with plaster, were gradually replaced by developed using wire-hung metal grids with infill of
gypsum. Suspended ceilings and tluorescenl lights acoustic panels, lighting tixtures, and air diffusion
arrived, generally sur1'ace- or pendant-mounted. Air units. HVAC syslems íncreased in size, requiring large
conditioning (cooling) was inlroduced and HVAC sys mechanical rooms and increased above-ceiling space
tems became more complex, with increased demands for ducts. Sprinklcrs and more advanccd electrical
for duct space. control systems were introduced, and more HVAC
C. Phase 3: 1950s to 1960s equipment was spring-mounled to prevenl transmis
This phasc saw lhe advent 01' simple rectangular sion 01' motor vibration.
melal or rein1'orced concrete 1rame structures D. Phase 4: 1960s to Present
("International Style"), and metal and glass curlain This pcriod saw the advent 01' exterior precast
waIls with a variety of opaque c1addings (porcelain concrete and, in the l 980s, glass-tiher-reinforced con
enamel, ceramic ti le, concrete, cement plaster). crete (GFRC) c1adding. Interior partition systems of
Interior partilions became primarily metal studs and metal studs and gypsum board, demountahle parti
gypsum board. Proprietary suspended ceilings were tions, and suspended ceiling systems become catalog
318
ASeE/SEI41-06
proprielary items. The evolution of the late 1970s plumbing systems Ihat are vilal parts of an effective
architectural style ("Posl-Modern") resulted in less tire suppression system.
regular forms and much more interior and exterior Studies published following the 1971 San
decoration, much of il accomplished by nonstructural Fernando earthquake a1l indicated Ihat buildings Iha!
components: assemblies of glass, metal panel, GFRC, sustained only minor structural damage became unin
and natural stone e1adding for the exteriors, and use of habitable and hazardous to lite due to failures of
gypsum board for exaggerated structural concealment mechanical and electrical systems.
and form-making in interiors. Suspended ceilings and
HVAC systems changed )jUle, but the advent of office Cl1.3.1.3 HVAC Systems
landscaping often reduced tloor-to-ceiling partirions A study by Ayres and Sun (1973b) clearly identi
lo almost nothing in general oftice space. Starting in fied the need to anchor tanks and equipment that did
the 1980s, the advent of the "smarl" oftice greatly not require vibration isolatíon, and to províde lateral
increased eleclrical and communications needs and the reslraints on equipment vibration isolation devices.
use of raised tloors, and increased the need for Ihe Sorne of these suggesled corrective measures are
mechanical and electrical syslems to remain funclÍonal now incorporated into manufactured products. The
after earthquakes. HVAC system designers had to become aware of the
earthquake-induced forces on the system's components
Cll.3.1.2 Background to Mechallical and Electrical and the need for seismic restraints to Iimit damage;
Considerations they also had to understand the requirements for !he
Prior lo the 1964 Alaska earthquake, mechanical suspension and bracing of ceilings and light fixtures
and electrical systems for buildings had been designed because of their adjacency to and interaction with the
with liule, if any, regard lO stability when subjected to HVAC system components.
seismic forces. The change in design from !he heavily To provide technical guidance to HVAC system
structured and densely partitioned slructures of the designers and installers, the Sheet Metal Industry Fund
pre-war era, with their simple mechanical, electrical of Los Angeles published its first manual, Guidelines
and lighling syslems, to the Iight frame and curtain for Seismic Restraints of Mechanical Systems (Sheet
wall, gypsum board and integrated ceilíng buildings of Metal Industry Fund, 1976). This manual was updated
the 1950s and onward, had been hule retlected in the in 1982 with assistance from the Plumbing and Piping
seismic building codeso The critical yel fragi!e nature Industry Counci1 (PPIC). The most recent manual,
of the new nonstructural systems was not fulIy real Seismic Restraint Guidelines lor Mechanical Equip
ized, except for nuelear power plant design and other ment (SMACNA 1991), is designed for use in
special-purpose, high-risk structures. Equipment sup California as well as other locatíons with lower
porls were generally designed for gravity loads only, seismic hazard levels.
and auachments to the structure Ítself were often Secondary effects of earthquakes (fires, explo
deliberately designed 10 be tlexible to allow for vibra sions. and hazardous materials releases resulting
tion Ísolation or therma! expansiono from damaged mechanical and electrical equip
Few building codes, even in regions with a history menO have only recently been considered. In
of seismic activity, have contained provisions govern addition, the potential danger of secondary damage
ing the behavior of mechanical and electrical systems from fallíng architectural and structural componenls,
until relatively recently. One of the earHest references which could intlict major damage to adjacent equip
10 seismic bracing can be found in NFPA 13, Standard ment and render it unusable, needs to be carefully
for the lnstallation 01 Sprinkler Systems (NFPA 2002). assessed.
This pamphlet has been updated periodically sínce These secondary efl'ecls can represent a consider
1896, and seismic bracing requirements have been able hazard to the building, its occupants, and its con
íncluded sínce 1947. Piping systems for building tenis. Steam and hol water boilers and olher pressure
sprinklers are static and do not require vibration i801a vessels can release fluids at hazardous temperalures.
tion. They do, however, require flexibilíty where the Mechanical systems often inelude piping systems
service piping enters the building. The issue of pro filled with flammable, toxic, or noxious substances,
tecting tlexibly mounted piping was not studied until such as ammonia or other refrigerants. Some of the
after the 1964 Alaska earthquake. nontoxic halogen refrigerants used in air-conditioning
The designers of building mechanical systems apparatus can be converled to a poisonous gas (phos
must also address the seismic restraints required for gene) upon contact with open tlame. Hot parls of dis
emergency generalors, tire protection pumps, and integrating boilers, such as portions of the burner and
319
SEISMIC REHABILlTATION OF EXISTING BUILDINGS
firebrick, are at high enough temperatures to ignite components, these values shall be factored up to strength
combustible materials with which they might come design levels. In the absence of manufacturer's data on
in contact. strength values, allowable stress values can be increased
by a factor of lA to obtain strength design values.
11.3.2 Component Evaluation Where nonstructural components are evaluated
Nonstructural components shall be evaluated to using Hazards Reduced Nonstructural Performance
achieve the Rehabilitation Objective selected in accor Level, the force level associated with Life Safcty
dance with Section lA. Analysis and rehabilitation Nonstructural Performance in Section 11.7 should be
requirements for the Hazards Reduccd, Life Safety, used. In many instances, if bracing of the nonstructural
and Immediate Occupancy Nonstructural Performance component exists, or if it is rehabilitated, there would
Levels for the appropriate level of seismicity shall be not be a substantial justitication for evaluating or reha
as specitied in Table 11- 1. Design forces shall be cal bilitating the component using a force level or accept
culated in accordance with Section j 1.7.3 or 11.704, ance criteria less stringent than Life Safety. However,
and design deformations shall be calculated in accor in cases where it is not considered critical or feasible,
dance with Section 11.7.5. Analysis and rehabilitation the engineer may, with appropriate approval, evaluate
requirements for the Hazards Reduced Nonstructural or rehabilitate the nonstructural component using a
Performance Level shall fol1ow the requirements for criterion that is less stringent than Lite Safety.
the Life Safety Nonstructural PerfOlmance Leve!. In cases where the Basic Satety Objective is
Analysis and rehabilitation requirements for the not required-such as where the Limited Safety
Operational Nonstructural Performance Level shall Performance Range applies-there may be more
be based on approved codeso latitude in the selection 01' components or criteria for
Acceptance criteria for nonstructural components nonstructural rehabi 1itation.
being evaluated to the Lite Satety and Immediate A suggested general procedure for developing a
Occupancy Nonstructural Performance Levels shall be mitigation plan for the rehabilitation of nonstructural
based on criteria listed in Sections j 1.9 through II.lI. components is as follows:
Forces on bracing and connections for nonstructural
components calculated in accordance with Sec l. It is assumed that the building has been evaluated
tion 11.7 shall be compared to capacities using in a teasibility phase, using a procedure such as
strength design procedures. Acceptance criteria for the that described in ASCE 31 (ASCE 2(02). For non
Lite Safety Nonstructural Performance Level shall be structural components, use of this procedure will
used for nonstructural components being evaluated to have provided a broad list of deticiencies that
the Hazards Reduced Nonstructural Performance are generally, but not specitically, related to a
Leve!. For nonstructural components being evaluated Rehabilitation Objective. Issues related to
to the Operational Nonstructural Performance Level, other objectives and possible nonstructural compo
approved acceptance criteria shall be used. nents not discussed in ASCE 31, as well as issues
raised by nonstructural rehabilitation unaccompa
Cll.3.2 Component Evaluation nied by structural rehabilitation (e.g., planning,
The Hazards Reduced Nonstructural Performance cost-benetit) are outlined in this commentary,
Level applies only to high-hazard components as spec and reterences are provided for more detailed
itied in Section 1.5.204 and Table 11-1. Life Safety investigation;
Nonstructural Performance Level criteria-or other 2. The decision is made to rehabilitate the building,
approved criteria-should be used for the Hazards either structurally, nonstructurally, or both;
Reduced Nonstructural Performance Leve!. Criteria for 3. From Chapter 1 of this standard, the designer
the Operational Nonstructural Performance Level has reviews Rehabilitation Objectives and, in concert
not been developed to date. Evaluation, rehabilitation, with the authority having jurisdiction, determines
and acceptance criteria for the Immediate Occupancy the objective. Alternatively, the objective may have
Nonstructural Performance Level may be used for the been already detined in an ordinance or other
Operational Nonstructural Performance Level if more policy;
appropriate data are not available. 4. Following a decision on the Rehabilitation
Forces on nonstructural components calculated in Objective, which includes the Nonstructural
accordance with Section 11.7 are at a strength design Performance Level or Range as well as ground
leve!. Where allowable stress values are available for motion criteria, the designer consults Chapter 11
proprietary products used as bracing for nonstructural of this standard;
320
ASeE/SEI 41-06
5. Using Chapler 11, the designer prepares a definilive higher than Limited Safety, consideralion 01' structural
Iist of nonslruclural componenls thal are within the behavior is necessary to properly take into account
scope of lhe rehabilitation, hased on the selected loads on nonstructural components generaled by iner
Nonslruclural Performance Leve! and an assess lial torces or de1'ormations imposed by Ihe slructure.
ment 01' component condition. For the Life Safety
Nonstruclural Performance Leve! and, lo sorne
Cl1.4.1 Regional Seismicity and Nonstructural
extent, lhe Immediate Occupancy Nonstructural
Components
Performance Level, Chaplers 2 and 11 of Ihis stan
Requiremenls for Ihe rehabilitation of nonslrue
dard specify requiremenls. However, for other
tural componelllS relating to the three Seismic
levels and ranges, there is a need 10 evaluate and
Levels-High, Moderate, alld Low-are shown in
prioritíze. From the list of nonstructural compo
Table J 1- J and noled in each seetion, where applica
nents wíthin Ihe project scope, a design assessment
ble. In general, for levels of low seismieity, certain
is made lo delermine if the component requires
nonstructural components have no rehabilitation
rehabilítation and, from Table 1I - 1, lhe rehabilita
requirements with respect to the Lite Safely
tion Analysis Method (Analytical or Prescriptive)
Nonslructural Performance Leve!. Rehabilitation
for each component or component group is
01' Ihese components, partieularly where rehabilitation
delermined;
is simple, may nevertheless be desirable tor damage
6. For those components that do not meet the criteria,
control and property loss reduclion.
an appropriale analysis and design procedure is
undertaken, with the aim 01' bringing the compo
nent inlo compliance wilh Ihe crileria appropriale Cl1.4.2 Means of Egress: Escape and Rescue
lo Ihe Nonstruclural Performance Level or Range Preservation of egress is accomplished primarily
and the ground motíon criteria; and by ensuring that the most hazardous nonstructural
7. Nonslructural rehahilitalion design documents are componenls are replaced or rehabilitated. The items
prepared., Iisted in Table 11-1 1'or achieving Ihe Li1'e Sa1'ety
Nonstructural Performance Level show Ihat typicaJ
requirements for mainlaining egress will, in effect, be
11.4 REHABILITATION OBJECTIVES AND accomplished if the egress-related components are
PERFORMANCE LEVELS addressed. These would inelude the following ¡tems
Jisled in ASCE 31 (ASCE 2002).
Rehabilitation Objeclives thal inelude performance
levels for nonslruclUral components shall be eSlab J. Walls around stairs, e!evator enclosures, and eorri
lished in accordance wilh Seetion lA. The level of dors are nOI hollow clay tile 01' unreinforced
seismiciry shall be delermined in accordance wirh masonry;
Section 1.6.3. 2. Stair enclosures do not eontain any piping or equip
ment except as required rOl' lite safety;
3. Veneers, cornices, and other ornamentalion aboye
C11.4 REHABILITATION OBJECTIVES AND building exits are well-anchored lo Ihe struetural
PERFORMANCE LEVELS system; and
4, Parapets and eanopies are anchored and braced 10
The nonslruclural Rehabilitation Objective may be lhe prevent collapse and blockage of building exits.
same as the Slructural Rehabilitation Objective, or it
Beyond this, Ihe following list describes some
may differ. For the Basic Safety Objeclive (BSO),
condilions Ihat mighl be commonly recognized as
struclural and nonstructural requírements specified in
representing major obstruction; the building should
this standard must be met.
be inspecled lo see whelher these or any similar
This standard is also in tended 10 be applicable lo
hazardous eonditions exist. If so, Iheir replacement or
the situalion where nonslruclUral-but not struclUral
rehabilitation should be included in rhe rehabilitatíon
components are to be rehabililated. Rehabilitation that
plan:
is reslricted 10 Ihe nonstruelural eomponents wíll typi
cally fall wíthin the Limited Safety Nonstructural l. Parlitions taller Ihan 6 1'1 and weighing more than
Performance Range unless the structure is already 5 lbs/sf, if collapse of the entire parlition-rather
determíned ro meet a specitied Rehabilitarion Ihan cracking-is Ihe expected mode of failure and
Objective. To qualify 1'or any Rehabilitation Objective jf egress would be impeded;
321
SEISMIC REHABILlTATION OF EXISTJNG BUILDINGS
2. Ceilings, soffits, or any eeiling or deeorative ceiling l. Nonstructural eomponenls lhal are sensÍlive to and
component weighing more than 2 Ibs/sf, ir it is subject to damage from inertial loading shall be
expecled that large areas (pieces measuring 10 sf or c1assified as acceleration-sensitive components;
larger) would fall; 2. Nonstruetural components that are sensitive and
3. Potential ror falling ceiling-Iocaled lighl fixtures or subject lO damage imposed by drift or de formal ion
piping; diffusers and ductwork, speakers and ol'!he slruclure shall be classitied as deformation
alarms, and other objects localed higher than 42 in. sensitive; and
off lhe floor; 3. Nonstructural componenls that are sensitive LO both
4. POlential for falling debris weighing more than inertial loading and drifl and deformation of the
100 lbs lhat, if it fell in an earthquake, would structure shall be classitied as deformation-sensitíve.
obstruct a required exit door or other component,
such as a rescue window or tire escape; and
5. Potential 1'or jammed doors or windows required as
part of an exit palh-including doors to individual Cll.6 CLASSIFICATION OF ACCELERATION
offices, resl rooms, and other occupied spaces. SENSITIVE ANO OEFORMATION-SENSITIVE
COMPONENTS
Of these, lhe tirst tour are also taken care 01' in the
Life Safely Nonstructural Performance Level require Classification 01' acceleration-sensitive or deformation
men!. The last condition is very difticult lo eliminate sensitive components are discussed, where necessary,
wilh any assurance, except for low levels of shaking ín in each component section (Seclions 11.9, 11.10, and
which structural drift and deformalíon will be mini 11.11). Table C 11-3 summarizes the sensitivity of non
mal, and the need for escape and rcscue eorrespond slruclural componenls lisled in Table 11-1, and idenli
ingly slíght. fies which are 01' primary or secondary concern. The
guiding principIe for deciding whether a component
requires a force analysis, as delined in Section 11.7, is
11.5 STRUCTURAL-NONSTRUCTURAL lhat analysis of inertial loads generated within lhe
INTERACTION component is necessary lo properly consider lhe com
ponent's seismic behavior. The guiding principie for
1l.S.1 Response Modification deciding whether a component requires a drifl analy
Nonstructural components shall be included in the si s, as delined in SeclÍon 11.7, is that analysis 01'
mathematical model of the building in accordanee drift is necessary to properly consider the component's
with the requirements of Section 3.2.2.3. Nonstructural seismic behavior.
components included in the mathematical model of the Glazing or other components that can hazardously
building shall be evaluated for force s and deformations fail at a drift ratio less than 0.0 l (depending on instal
imposed by the structure, computed in accordance lalÍon details) or components thal can undergo greater
with Chapter 3. distortion without hazardous failure resuhing-for
example, typical gypsum board partitions-should be
11.5.2 Base Isolation considered.
In a base-isolated structure, nonstructural compo Use oC Oríft Ratio Values as Acceptance
nents located at or aboye the isolation interface shall Criteria. The dala on drift ratio values relaled to dam
comply with the requirements in Section 9.2.6.2.1. age slales are Iimiled, and the use 01' single median
Nonstructural components that cross the isolation drift ralio values as acceptance crileria must cover a
interface shall comply with lhe requirements of broad range of actual conditions. lt is thererore sug
Section 9.2.6.2.2. Nonstructural components located gested lhat lhe limiting drift values shown in lhis chap
below the isolation interface shall comply with the ter be used as a guide for evaluating lhe probability of
requirements of this chapter. a given damage state for a subject building, but not
be used as absolute acceptance criteria. At higher
Nonstructural Performance Levels, it is IikeIy thal lhe
11.6 CLASSIFICATION OF ACCELERATION criteria for nonstructural deformation-sensitive compo
SENSITIVE ANO OEFORMATION-SENSITIVE nents may control lhe struclural rehabilitation designo
COMPONENTS These crileria should be regarded as a tlag tor the
careful evaluation of slructural-nonstructural interac
Nonstructural components shall be c1assified based on tion and consequent damage states, rather than the
lheir response sensitivity as follows: required imposition of absolute acceptance crileria
322
ASCE/SEI 41-06
Sensitivity
Component Acceleration Deformation
Architectural (Section 11.9)
l. Exterior Skin S2 pl
Adhered Veneer S P
Anchored Veneer S P
Glass Blocks S P
Prefabricated PaneIs S P
Glazing Systems S P
2. Partitions
~ry S P
L~~ S P
3. Interior Veneers S P
Stone, Including Marble S P
Ceramic Tite S P
4. Ceilings
Directly Applied to Structure P
Dropped Furred Gypsum Board P
Suspended Lath and Plaster S P
Suspended Integrated CeiJing S P
5. Parapets and Appendages P
6. Canopies and Marquees P
7. Chimneys and Stacks P
8. Stairs P S
Mechanical Equipment (Section 11.10)
1. Mechanical Equipment P
Boilers and Furnaces P
General Mfg. and Process Machinery P
HVAC Equipment. Víbration-Isolated P
HVAC Equipment. Non-Vibration-Isolated P
HVAC Equipment. Mounted In-Une wilh Ductwork P
2. Storage Vessels and Water Heaters
Structurally Supponed Vessels (Category 1) P
FlatBottom Vessels (Calegory 2) P
3. Pressure Piping P S
4. Fire Suppression Piping P S
5. Fluid Piping, not Fire Suppression
Hazardous Materials P S
Nonhazardous Materials P S
6. Ductwork P S
¡p. Prímary response
2S. Secondary response
lhal mighl require costly redesigo of lhe struclural 11.7.1 Analytical Procedure
rehabilitatioo. Where lhe Prescriplive Procedure is oot permitted
based 00 Table 11-1, forces and deformalions 00 noo
11.7 EVALUATION PROCEDURES slructural componeols shall be caJculated as follows:
1. If a force analysis only is permitted by Table 11-1
One of the following evaluation procedures for non
and eilher lhe Hazards Reduced or Life Safely
structural components shall be selected based on lhe
Nonstructural Performance Level is selected, then
requiremenls of Table 11- J:
use of the default equations given in Section 11.7.3
J. Analytical Procedure; or shall be permitted to calculate seismic design
2. Prescriptive Procedure. forces 00 nonstructural components;
323
SElSMIC REHABILlTATION OF EXlSTING BUILDlNGS
2. If a force analysis only is permiued by Table 11-1 computed using Eq. 11-1. Where specifically required
and a Nonstructural Performance Level higher than in Sections 11.9, 11.10, and 11.11, vertical seismic
Life Safety is selected, then the default equations of torces for horizontal cantilever components shall be
Section J 1.7.3 do not apply, and seismic design deterrnined using Eq. 11-2. Vertical seismic forces
forces shaJl be calculated in accordance with for all other components shall be determined using
Section 11.7.4; and Eq. 1J-3.
3. Ir both force and deformation analysis are required (Eq. 11-1)
by Table 1J- J , then seismic design forces shall be
calculated in accordance with Section 11.7.4 and (Eq. 11-2)
drift ratios or relative displacements shall be calcu Fpv (minimum) = :t O.2Sxs Wp (Eq. 11-3)
lated in accordance with Section 11.7.5. The defor
where
mation and associated drift ratio of the structuraJ
component(s) to which the deformation-sensitive FI' component seismic design force applied hori
nonstructural component is attached shall be deter zontally at the center 01' gravity of the compo
mined in accordance with Chapter 3; or nent or distributed according lo the mass distri
4. Alternatively, lhe calculalion of seismic design bution 01' the component;
torces and deformations in accordance with Sec FI'" component seismic design force applied verti
tion 11.7.6 shaJl be permitted. cally at the center 01' gravity of the component
or distributed according to the mass distribution
Cll.7.l Analytical Procedure 01' the componenl;
For nonstructural components, the Analytical Sxs = spectral response acceleration parameter at short
Procedure, which consists of lhe default equation and periods for any Earthquake Hazard Level and
general equation approaches, is applicable to any case. any damping determined in accordance with
The Prescriptive Procedure is limited by Table 11-1 to Section 1.6.1.4 or 1.6.2.1; and
specitied combinations of seismicity and componenl Wp component operating weight.
type for compliance with the Life Safety Nonstructural
Performance Leve!. 11.7.4 Force Analysis: General Equations
324
ASeE/SEI 41-06
325
SEISMIC REHABILlTATION OF EXISTING BUILDlNGS
326
ASCE/SEr 41-06
Piping and tubing conslrucled of low-deformability malerials, such as casI iron, glass, and nonduclile 2.5 3.0
plastics.
Ductwork, including in-Iine components, constructed of high-deformability malerials, with joinls made 2.5 9.0
by welding or brazing.
Ductwork, including in-line components, constructed of high- 01' limited-deformability materials with 2.5 6.0
joints made by means other than welding or brazing.
Ductwork, including in-Hne components, construcled of low-defonnability materials, such as casI iron, 2.5 3.0
glass, and nonductile plastics.
Eleclrical conduit, bus ducts, rigidly mounted cable Irays, and plumbing. 1.0 2.5
Manufacturing or process conveyors (nonpersonneI). 2.5 3.0
Suspended cable trays. 2.5 6.0
Furnishings and Interior Equipment (Seclíon 11.11)
Slorage racks5 2.5 4
Bookcases 3
Computer access f100rs 3
Hazardous matel'ials slorage 2.5
Computer and communications racks 2.5 6
Continued
327
SEISMIC REHABILlTATlON OF EXISTING BUILDlNGS
Elevators I 3
Conveyors 2.5 3
lA lower value for ap is permiuíXI where juslified by detailed dynamic analyses. The value fol' ap shall not be less than 1,0. The value of a" equal
10 1.0 is fol' rigid components and l'igidly auached components, The value of ap eqllal 102.5 is ror flexible componcms and t1exibly artached
componcnts.
2Where flexible diaphragms pl'Ovide lateral sUppOJt for concrete or masonry walls or partilions. lhe dcsign Jorces for anchorage to the diaphrugm
shall be as specitied in Seco 2.6.7.1.
'Components mOllnted on vibrulion isolalOrs shall have a bumper restrainl or snllbher in each holÍzontal direclion. The dcsign force shall be l¡¡ken
as 2FI' ir lhe nominal c1eanmce (air gap) belwccn the eqllipment SlIpport frame and restrujnl is grcater than ~ in. Ir the nominal c1earance specítied
on the conslrucljon documents js nOI greater than ~ in,. the design force may be taken as Fp '
4The value of R" used lo delermine lhe forces in the connecled pan shall not exceed 1.5 unless lhe componenl anchorage is governed by the
strenglh of a ductile stccl component.
'SLOrage racks over 6 ft in height shall be designed in accordance with the provisions of Section 11.11.1.
'American Society 01' Mechanical Engineers (ASME B31). (2000). eade Jilr l'ressure l'iping. New York.
A period of vibration of 0.06 sec is used to distinguish sufticiently aceurate ror estimating the story accelera
between rigid and flexible components. The engineer tions since buildings checked for Immediate Oceupaney
should verify that the al' value used is appropriale for Performance Levcl are cxpecled to bchave nearly clas
the actual component and its support system. tically for lhe design earthquake.
For many buildings, ¡he primary mode 01' vibra
tion in each direclion wilJ have the most influence on Eq. 11-11.7.4.2 Vertical Seismic Forces
the dynamic ampliticalion 01' nonslructural compo Whcre the default equalions of Seclion 11.7.3 do
nents. For buildings with primary mode periods not apply, and where speeifically required by Sec
greater than 1 see, the second or third mode 01' vibra tions 11.9, 11.10, and 1 1.11, vertical seismic design
tion may also cause sorne dynamic amplificalion. forces on nonstructural eomponenls shall be de ter
Equation 11-5c provides a slightly revised form of mined in accordance with Eq. 1 1-6.
Equation 11-5b for use where checking nonstructural
components for Immediate Occupancy Performance F = 0.27ap Sxsl)i-;,
(Eq. 1 J -6)
Level. In Equalion 11-5b, the factor (a) is defined as 1'" Rp
lhe dynamic amplification factor considering reso Fp calculated in accordance with Eq. 11-6 need
nance ol' the nonstructural component with one oi' lhe not exceed F p caleulated in accordance wilh Eq. f 1-2
modes of the building. The intent is lo consider this and shall not be less than FIII' (minimum) computed in
dynamic ampliticalion effect for nonslructural compo accordance wilh Eq. 11-7.
nenls for Immediate Occupancy Performance Leve!.
Guidelines for considering this efTect are provided FI"Kminimum) 0.2 Sxs1pW1l (Eq. 11-7)
in ¡he Tri-Services Seismic Designfor Buildings, where
TM5-809-10 and Seismic Design Guidelines for
Essential Buildings. TM5-809- 10- 1 (Dept. 01' the FllV component seismic design force applied verti
Army, Navy, and Air Force 1986). Other approved cally at the center of gravily of [he component
procedures could also be used. It is permissible to use or dislribuled according lo the mass dislribution
the ap factors from Table 11-2. of lhe componen!.
Equation 11-5c also provides a factor Ax, which AlI olher terms in Eqs. 11-6 and 1 J -7 shall be as
represents the floor accelerations. The intent is that a defined in Section 11.7.4.1.
linear dynamic analysis 01' the building be performed
lo determine the actual story accelerations based on
11.7.5 Deformation Analysis
the ground mOlion considered ror a sufficient number
Where nonslruclUral components are anchored by
01' modes of vibration for the range of periods of
connection points at difIeren! levels x amI y on the
vibration of the nonstruclural components to be
same building or struclural system, drifl ralios (DJ)
designed. The modal story accelerations can be com
shall be calculated in accordance with Eq. 11-8.
bined using standard modal combinalion procedures.
Linear dynamic analysis procedures are considered (Eq. 11-8)
328
ASCFJSEI41-06
The effecls of seismic displacements shall be con Nonstructural rehabilitation shall be accomplished by
sidered in combination with displacements caused by approved methods based on the classification 01' the
olher loads Ihal are prcsent. nonstructural component and the performance level
desired for the nonstructural component.
11.7.6 Other Procedures 1. For the rehabilitation of nonstructural components
Olher approved procedures shall be permitted to that are acceleration-sensitive for Hazards Reduced
determine the maximum acceleration of the building at or Lífe Safety Performance Levels, the rehabilita
each component support and the maximum drift ratios tíon approach shall provide for position relention.
or relative displacements between two supports 01' an Position retention shall be defined as províding
individual component. bracing, anchorage, attachment, or other approved
methods to prevent the nonstructural component
Cll.7.6 Other Procedures from becoming dislodged during earthquake
Linear and nonlinear procedures may be used lO shaking.
calculate the maximum acceleration 01' each compo 2. The rehabilitation 01' nonstructural components for
nent support and the story drifts of the building, taking Immediate Occupancy Performance Level shall
into account Ihe locatíon of the component ín the provide for position retention. In addition, the reha
building. Consideratíon 01' the Ilexibílity of the compo bilitatíon of mechanical and eleclrical components
nent, and the possíble amplitication of the building shall prevent damage to the components that will
roof and tloor accelerations and displacemenls in the afrect the occupancy of the building.
component, would require the development 01' rool' 3. For the rehabiJitation of nonstructural components
and tloor response spectra or acceleration time histo tbat are deformatíon sensitive, the rehabilitation
ries al the nonslructural supporllocations, derived approach shall provide for suft1cient deformation
from the dynamic response of Ihe structurc. If the capabilíty for Ihe nonstruclural components lo
rcsulting floor speclra are less than demands calcu allow the nonstructural component to undergo the
lated in accordance with Sections 11.7.3 and 11.7.4, il caJculated deformation while maintaíning position
may be advantageous lo use this procedure. relention.
329
SEISMIC REHABILITATION OF EXISTING BUlLDlNGS
330
ASCFJSEI 41-06
331
SEISMIC REHABILlTATION OF EXISTlNG BUILDlNGS
out-of-plane deformalions of the supporting struclure, held together by mortar and structurally detached from
parlicularly if it is a frame, may similarly aftecl lhe the surrounding structure, shall be rehabililaled in
conneclions, and lhe units may be displaced or dis accordance with this section.
lodged by racking. Thick, anchored veneer may pos
sess significanl in-plane stitl"ness, which can greally 11.9.1.3.2 Component Behavior and Rehabilitation
amplify the demands placed on the connections if the Methods Olass block uníts and other nonstructural
supporting structure racks. masonry shall be considered both acceleration- and
Drift analysis is necessary lO establish confor deformation-sensitive.
manee with dri1't acceplance criteria related lo per Rehabilitation of individual walls less than 144 s1'
formance leve!. The dri1't analysis should consider the or 15 ft in any dimension using Prescriptive
conslruction and behavior of lhe veneer and its back Procedures based on Section 2110 of the ICC (2003)
ing to assess the individual parls of lhe nonstructural shall be permitted. For walls larger than 144 sí' or 15ft
componenl that are required to deform in order to in any dimension, the Analytical Procedure shall be
accommodate lhe required drift. These parls of the used.
nonstruClural component should be checked for their Olass block unÍts and other nonstructural masonry
capabilily to allow for lhe calculaled deformalÍon of not con1'orming with lhe requirements 01' Sec
lhe slructure. Noncon1'ormance requires Iimiling slruc tion 11.9.1.3.3 shall be rehabilitated in accordance
luml drift, or special delailing to isolate lhe subslrate with Section 11.8.
from lhe struclure to permit drift. De1'ective connec
lions must be replaced.
Cl 1.9.1.3.2 Component Behavior and Rehabilitation
11.9.1.2.3 Acceptance Criteria Acceplance criteria Methods Olass block and nonstructural masonry are
shall be applied in accordance with Section II.:U. bOlh acceleration- and deformation-sensitive. Failure
in-plane generally occurs by deformation in the sur
l. Life Safety Nonstructnral Performance Level. rounding struclure that results in unit cracking and dis
Backing shall be adequately anchored to resist placement along lhe cracks. Failure oUl-of-plane takes
seismic forces computed in accordance with lhe form of dislodgmenl or collapse caused by direct
Seclion 11.7.3 or 11.7.4. The drin ratio calculated acceleration.
in accordance wilh Section 11.7.5 shall be Iimiled Nonconformance with deformation critcria
lo 0.02. requires Iimiting structural drifl, or special detailing to
2. Immediate Occupancy Nonstructural isolate lhe glass block wall from the surrounding
Performance Level. Backing shall be adequately structure to permil the required drift. The drift analysis
auached lo resist seismic design forces compuled in should consider the construction and behavioe of the
accordance wilh Seclion 11.7.4. The drift ralio veneer and its backing lo assess lhe individual parts of
compuled in accoedance with Section 11.7.5 shall the nonstructural component that are rcquircd to
be Jimited lo 0.0 l. deform in order to accommodate the required drift.
These parts of the nonstruclural componenl should be
C1 1.9.1.2.3 Acceptance Criteria As an alternative lO
checked foe their capability to allow for lhe calculaled
Ihe dri1't limils in Section 11.9.1.2.3, the nonstructural
deformation 01' the structure. Su1'ficient reintorcing
component and its backing can be shown by approved
must be provided to deal with out-of-plane torces.
testing or analysis lo meel the intended performance
Large walls may need lo be subdivided by additional
level for lhe calculated drift.
structural supports into smal1er areas that can meet lhe
11.9.1.2.4 Evaluation Requirements Stone unils shall drift or torce criteria.
have adequale slability, joint delailing, and mainte
nance [O prevenl moisture penetmtion from weather 11.9.1.3.3 Acceptance Criteria Acceptance criteria
that could destroy the anchoes. The anchoes shall be shall be applied in accordance with Section 11.3.2.
visually ínspected and tested to determine capacity if
1. Life Safety Nonstructural Performance LeveI.
any signs 01' deterioration are visible.
Olass block and olher nonstructural masonry walls
11.9.1.3 Glass Block Unus and Other Nonstructural and their enclosing framing, shall be capable of
Masollry resisting both in-plane and out-of-plane forces
computed in accordance with Section 11.7.3 or
1/.9. /.3.1 Definition and Scope Olass block and other 11.7.4, or shall meet lhe requirements 01' the
units lhat are self-supporling for static vertical loads, Prescríptive Procedure if permitted. The drift ratio
332
ASCElSEI 4 J-06
calculaled in accordance with Section 11.7.5 shall wilh a slotted or oversize hole. Drift can also be
be IimÍled to 0.02. accommodated by deformation of the connections.
2. Immediate Occupancy Nonstructural Excessive deformalion 01' the supporting structure
Performance Level. Glass block and olher non most likely if il is a frame-may result in the panel s
structural masonry walls and lheir encIosing fram imposing exlernal racking forces on one another and
ing shall be capable of resisting both in-plane and distorling or fracturing their connections, wÍlh conse
out-of-plane torces computed in accordance wilh quenl displacement or dislodgment.
Sectíon 11.7.4. The drifl ralio calculated in accor Drift analysis is necessary lo eSlablish confor
dance with Section 1l.7.5 shall be Iimited lo 0.01. manee wilh drífl acceptance criteria related to ¡he
Nonslructural Performance Leve!. The drift analysis
11.9.1.3.4 Evaluation Requirements Glass block units should consider the construction and behavior 01' lhe
and other nonslructural masonry shall be evaluated panel and its conneclÍons lo assess Ihe individual parts
based on lhe criteria of Seclion 2110 01' the ICC of the nonstructuraJ component thal are required to
(2003). deform in order to accommodate the required drift.
Nonconformance requires limiting structural drin,
or special delailing lo isolale pancls fmm lhe structure
11.9.1.4 Prefabricated Panels to permit lhe required drifl; this generally requires
panel remo val. Defective connections must be replaced.
11.9.1.4.1 Definition and Scope The following Iypes
of pre1'abricaled panels designed to resist wind, seis 1/.9./.4.3 Acceptance Criteria Acceptance criteria
mic, and other applied forces shall be rehabilitated in shall be applied in accordance with Seclion 11.3.2.
accordance wilh this section:
l. Life Safety Nonstructural Performance Leve"
l. Precast concrete, and concrete panels with facing Prefabricaled panel s and connections shall be capa
(generally stone) laminated or mechanically ble of resisting in-plane and oUI-of-plane forces
auached; computed in accordance with Section 11.7.3 or
2. Laminated metal-faced insulated panels; and 11.7.4. The drift ratio computed in accordance with
3. Steel strong-back panels with insulated, water SeclÍon 11.7.5 shall be limiled to 0.02.
resistanl facing, or mechal1icalIy auached melal or 2. lmmediate Occupancy Nonstructural
slOne facing. Performance Level. Prefabricated panels and con
nections shall be capable of resisling in-plane and
Cll.9.1.4.1 Definition and Scope Prefabricated panels out-of-plane forces computed in accordance with
are generally allached at discreet locations around Section 11.7.4. The drift ratio computed in accor
their perimelers lo lhe slructural framing wilh mechan dance with Seclíon 11.7.5 shall be limited to 0.01.
ical conneclions.
/ /.9.1.4.4 Evaluation Requirements Conneclions shall
11.9.1.4.2 Component Behavior and Rehabilitatíon be visually inspected and lested lo determine capacity
Methods Prefabricated panels shall be considered bOlh if any signs 01' delerioration or displacemenl are visible.
acceleration- and deformation-sensilive.
Prefabricaled panels not conforming lo lhe accep 11. 9. 1.5 GÚlzed Exterior Wall Syslems
tance crileria of Section 11.9.1.4.3 shall be rehabili
tated in accordance with Section ] 1.8. J1.9.1.5.1 Definition and Scope Glazed exterior waIl
syslems shall inelude Ihe tollowing types 01' assemblies:
C 11.9./.4.2 Componen! Behavior ami Rehabilitation l. Glazed curtain wall systems thal exlend beyond lhe
MetllOds Lightweight panels may be damaged by edges of struclural t100r slabs, and are assembled
racking; heavy panel s may be disJodged by dírecl from prefabricated units (e.g., "unitized" curtain
accderation, which dis[orls or fractures Ihe mechani wall systems) oc assembled on site (e.g., "s tick"
cal conneclions. The imposed in-plane and oul-of curtain wall systems);
plane deformations are generalIy accommodated by 2. Glazed storefront systems thal are instaUed
lhe conneclions and nol by the prefabricated panels. belween structural tloor slabs and are prefabricated
These conneclions need lo be checked for lhe delailing or assembled on site; and
to accommodate the required drift. This is generally 3. Slructural silicone glazing in which silicone sealant
accomplished by a conneclion delailed 10 allow slidil1g is used for the slructural transfer 01' loads from Lhe
333
SElSMIC REHABlLlTATION OF EXISTING BUILDlNGS
glass to its perimeler support syslem and for the Drift analysis and tesling 01' compliance with
retention of the glass in the opening. prescriptive procedures are necessary lO eSlablish
conformance Wilh drift acceptance crileria relaled to
CI/.9.1.5.1 Definitíon and Seope The following types performance leve!. Nonconformance requires limiling
of glass are used within each of the glazed exterior struclural drift, or special delailing lo isolale the
wall syslems: glazing syslem from lhe strucLUre lO accommodate
drin, or seleclÍon ol' a glass lype that will shaller
l. Annealed glass; safely or remain in lhe frame when shaltered. This
2. Heal-slrengthened glass; would requil'e removal of lhe glass or glazed wall
3. Fully lempered glass; system and replacemenl with an alternalive designo
4. Laminated glass; and
5. Sealed insulaling glass units. /1.9.1.5.3 Aeeeptanee Criteria Acceptance crilcria
The use of sorne of lhese glass lypes is regulated shall be applied in accordance wilh Section 11.3.2.
in building codeso l. Life Safety Nonstructural Performance Level.
There are lwo glazing methods for installing glass Glazed exterior wall systems and lheir supporting
in glazed curtain wall and glazed storefront systems: struclure shall be capable 01' resisling scismic
1. Wet glazing, which can utilize three lypeS of design forces computed in accordanee wilh Sec
malerials: tion 11.7.3 or 11.7.4. Glass components meeting
1.1 Pre-formed lape; any of lhe following criteria need nol be I'ehabili
1.2 Gunable elastomerÍc sealants: tated 1'01' Ihe Hazards Reduced or Life Safely
1.2.1. Non-curing; and Nonstructural Performance Leve!:
1.2.2. Curing; 1.1. Any glass component with sufficient c1earanee
1.3 PUtly and glazing compounds; and fmm the n'ame such lhat physical contact
2. Dry glazing, which utilizes extruded rubber gaskels between Ihe glass and lhe frame will not occur
as one or both of lhe glazing seals. al the rclative seismic displacemcnt lhal lhe
componenl must be designed to accommodale,
as demonslratcd by Eq. 11-10.
11.9.1.5.2 Component Behavior and Rehabilitation
Methods Glazed exterior wall syslems shall be consid (Eq. 11-10)
ered both deformation- and acceleration-sensitive.
where
Glazed exterior wall syslems nol conforming lo
the acceptance criteria ol' Section 11.9.1.5.3 shall be
rehabilitated in accordance wilh Seclion 11.8.
334
ASeE/SEI 41-06
contact widlh, or other approved anchorage frame contact in a given rectangular window frame.
system; Both equations are based on the principie that a
1.4. Any glass component that meets Ihe relative reclangular window frame (specitically one Ihal is
displacement requirement of Eq. 11-11. anchored mechanically to adjacent stories ol' Ihe
primary slruclural system of Ihe building) becomes a
AJall"., 2:: 1.25Dp (Eq. 11-11)
parallelogram as a result ol' slory drift, and Ihat glass
or 0.5 in., whichever is greater, to-l'rame contact occurs when the length of lhe shorter
diagonal of the parallelogram is equal to the diagonal
where
of the glass panel ¡tself.
Dp relative seismic displacemenl that The 1.25 factor in Eqs. 11-11 and 11-12 reUect
the componenl must be designed lo uncertainties associated with calculated inelastic seis
accommodate; and mic displacements in building slructures. Wright
Djalkl.' = relative seismic displacemenl (drift) (1989) stated Ihat "[P]osl-elastic deformations calcu
causing glass fallout from the curtain lated using the structural analysis process may well
wall, storefront, or parlition, as underestímate the actual building deformalion by up to
determined in accordance wilh an 30%. It would therefore be reasonable to require Ihe
approved engineering analysis curtain wall glazing system to withstand 1.25 times
melhod; the computed maximum story displacemenl to veril'y
adequate performance." Wright's comments form the
2. Immediate Occupancy Nonstruclural
basis for using the 1.25 factor.
PeñormaDce Level. Glazed exterior wall systems
and their supporting structure shall be capable of
1/.9. /.5.4 Evaluation Requirements To establish com
resisting seismic design forces computed in accor
pliance with criteria 1.1, 1.2, 1.3,2.1, or 2.2 in
dance with Section 11.7.4. Glass components
11.9.1.5.3, glazed exterior wall systems shall be evalu
meeting any of the following criteria need nol be
ated visually to determine glass type, support details,
rehabililaled for performance levels higher than the
mullion configuration, sealant type, and anchors. To
Life Safety Nonstructural Performance Level: establish compliance with criteria lA or 2.3, an
2.1. Any glass componenl wilh sufficienl elearance
approved analysis shall be used.
from the frame such that physical contacl
between the glass and the frame wiIJ nol occur el 1.9./.5.4 Evaluation Requirements Alternatively, to
at Ihe relative seismic displacement tha! Ihe establish compliance with criteria lA or 2.3, glazed
componenl must be designed to accommodale, exterior wall systems may be tested in accordance
as demonslrated by Eq. 11-10; with AAMA 501.4 (AAMA 2000).
2.2. Annealed or heat-slrengthened laminaled glass
in single Ihickness with inlerlayer no less than 11.9.2 PartitioDS
0.03 in. Ihal is captured mechanicaJly in a wall
system glazing pockel, and whose perimeter is 11.9.2.1 Definition and Scope
secured to Ihe wall system frame by a wet Partitions shall include vertical non-load-bearing
glazed perimeter bead of 4-in. minimum glass interior components that provide space division.
contact width, or other approved anchorage Heavy partitions shall inelude partitions con
system; and structed of masonry materials or assemblies.
2.3. Any glass component that meets Ihe relalive Light partitions shall inelude partitions con
displacement requirement of Eq. 11-12. structed of metal or wood studs surfaced with lath and
AJallo., 2:: l.5 X 1.25Dp (Eq. 11-12) pi aster, gypsum board, wood, or other facing materials.
335
SEISMIC REHABILlTATION OF EXISTING BUILDINGS
considered in this section. Structural partitions includ 2. Light Partitions. Nonstructurallight partitions
ing heavy masonry partitions shall be rehabilitated in need nol be rehabilitated 1'or lhe Life Safely
accordance with Chapter 7. Nonstructural Performance Leve!.
Partitions may span laterally from the tloor to the
underside of the tloor or the roof aboye, with connec 11.9.2.3.2 Immediate Occupancy Nonstructural
tions at the top that may or may not allow for isolation Peiformance Level
from in-plane drift. Other partitions extend only up lo
l. Heavy Partitions. Nonstructural heavy partitions
a hung ceiling, and may or may not have lateral brac
shall be capable 01' resisting out-of-plane forces
ing aboye that level to Slructural support, or may be
computed in accordance with Section 11.7.4. The
free-standing.
drift ratio computed in accordance with Sec
Modular office furnishings that inelude movable
tion 11.7.5 shall be límited 10 0.005.
partitíons are considered as COnlenls rather than parti
2. Light Partitions. Nonstructurallight partitions
tions, and as such are not within the scope of this
shall be capable 01' resisting the out-of-plane forces
standard.
computed in accordance with Section 11.7.4. The
drift ratio computed in accordance with Sec
11.9.2.2 Component Behavior and
tion 11.7.5 shall be Iimited to 0.01.
Rehabilitation Methods
Partitions shall be considered both acceleration
11.9.2.4 Evaluation Requirements
and deformation-sensitive.
Partitions shall be evaluated to ascertain the type
Partitions nOl meeting the acceptance criteria of
01' material.
Section J 1.9.2.3 shall be rehabilitated in accordance
with Section 1 1.8.
C 11.9.2.4 Evaluation Reqrtirements
For concrete block partitions, presence 01' rein
Cll.9.2.2 Component Behavior and
1'orcing and connecLion conditions al edges are impor
Rehabilitation Methods
tanto For Iight partitions, bracing or anchoring 01' the
Partitions auached to the structural tloors both
top of the partilions is important.
aboye and below, and loaded in-plane, can experience
shear cracking, distortion and fracture of the partition
11.9.3 Interior Veneers
framing, and detachment of the surface tinish because
of slructural deformations. Similar partitions loaded
11.9.3.1 Defillition and Seope
out-of-plane can experience flexural cracking, failure
Interior veneers shall inelude decorative-tinish
of connections to structure, and coltapse. The high
material s applied to interior walls and partitions. These
incidence of unsupported block partílions in low and
provisions 01' lhis section shall apply to veneers
moderate seismic levels represents a signiticant col
mounted 4 ft or more aboye the floor.
lapse threat.
Panítions subject to deformations from the struc
11.9.3.2 Component BeJ,avior alld
ture can be protected by providing a continuous gap
Rehabilitation MetJwds
between the partilion and the surrounding structure,
Interior veneers shall be considered deformation
combined wilh aHachment that provides for in-plane
sensitive.
movement but out-of-plane reslraint. Lightweight par
Interior veneers not conforming lO the acceptance
titions that are not part of a fire-resistive system are
criteria of Section 11.9.3.3 shall be rehabilitated in
regarded as replaceable.
accordance with Section 11.8.
11.9.2.3 Aeeeptanee Criteria
Cll.9.3.2 Component Behavior ami
Acceptance criteria shall be applied in accordance
Rehabilitatioll Methods
with Section 11.3.2.
Interior vcneers typically experience in-plane
cracking and detachment, bUI may also be displaced or
11.9.2.3.1 Lije Safety Nonstructural Performance Level
detached out-of-plane by direct acceleration. Interior
l. Heavy Partitions. Nonstructural heavy partitions partitions loaded out-of-plane and supported on Ilexi
shall be capable of resisting out-of-plane forces ble backup support systems can expcrience cracking
computed in accordance with Section 11.7.3 or and detachment.
J 1.7.4. The drifl ratio computed in accordance with Drin analysis is necessary to eslablish confor
Section 11.7.5 shall be limited 10 0.01. manee with drift acceptance criteria relaled to the
336
ASCE/SEI41-06
Nonstructural Performance Level. Nonconformance Sorne older buildings have heavy decoratÍve ceil
requires limiting struclural drift, or special detailing lo ings 01' molded plaster, which may be direetly attached
isolate Ihe veneer supporl system from ¡he struclure lo to Ihe structure or suspended; these are typically
permil drifl; this generally requires disassembly of the Calegory a or Category c ceilíngs.
support system and veneer replacement. Inadequately
adhered veneer musl be replaced. 11.9.4.2 Component Behavior and
Rehabilitation Methods
11.9.3.3 Accep/ance Criteria Ceiling systems shall be considered bolh accelera
Acceptance criteria shall be applied in accordance tion- and deforrnation-sensitive.
with Seclion 11.3.2. Ceilings nol conforming lo the acceptance criteria
of Section 11.9.4.3 shall be rehabilitated in accordance
n.9.3.3.1 Life Safety Nonstructural Performance with Section 11.8.
Level Backing shall be adequately attached lo resísl Where rehabilitation is required for ceilings in
seismic design forces computed in accordance with Category a or b, lhey shall be strengthened lO resíst
Seclion 11.7.3 or 11.7.4. The drift ratio computed in seismic design forces computed in accordance with
accordance with SeelÍon 11.7.5 shall be lirnited to 0.02. Seclion 11.7.3 or 11.7.4. Where rehabilitation is
required for ceilings in Calegory d, they shall be reha
11.9.3.3.21mmediate Occupancy Nonstructural bilitated by the Prescriptive Procedure of Section 11.2.
Performance Level Backing shall be adequately
attached lo resist seismic design forces computed in Cll.9.4.2 Component Behavior and
accordance with Section 11.7.4. The dríft ratio com Rehabilita/ion MetllOds
pUled in accordance Wilh Seetion 11.7.5 shall be lim Surface-applied or furred ceilings are primarily
iled lO 0.01. intluenced by lhe performance of their supports.
Rehabilitation of the ceiling takes the form 01' ensuring
11.9.3.4 Evalua/ion Requirements good attachment and adhesion. Metal lath and plaster
Backup walls or other supporls and the auach ceilings depend on their attachment and bracing for
ments to that support shall be evalualed, as well as the large ceiling areas. Analysis is neeessary lo establish
condition of the veneer itself. the acceleration forces and deforrnations that must be
accommodated. Suspended integrated ceilings are
11.9.4 Ceilings highly susceptible lo damage if not braced, causing
distorlion of grid and loss 01' panels; however, this is
11.9.4.1 Definition and Scope nol regarded as a Jife safety threat with lightweight
Ceilings shall be categorized as one of the follow panels (Iess than 2 Ibs/st).
ing types: Rehabilitation lakes the form of bracing, attach
l. Category a. Surface-applied or furred with materi ment, and edge details designed to prescriplive design
als that are applied direetly to wood joists, concrete standards such as Recommendations for Direct-Hung
slabs, or steel decking with meehanical fasteners or Acoustical and Lay-in Panel Ceilings, Seismic
adhesives; Zones 0-2 (CISCA 1991) for seismic levels O through
2. Category b. Shorl-dropped gypsum board sections 2 and in Recommendations for Direct-Hung Acoustical
(Iess than 2-ft drop) auached lo wood or metal fur and Lay-in Panel Ceilings, Seismic Zones 3-4 (CISCA
ring supported by carrier members; 1990) 1'or seismic levels 3 and 4.
3. Category c. Dropped gypsum board sections
greater than 2 ft and suspended metal lath and plas 11.9.4.3 Acceptance CriterÚl
ter; or Acceptance criteria shaIl be applied in accordance
4. Category d. Suspended acoustical board inserted with Seclion 1] .3.2.
within T-bars, together with lighting fixtures and
mechanical items, to form an integrated ceiling 11.9.4.3.1 Life Safety Nonstructural Pelformance
system. Level Ceilings in Categories a, b, oc d need nol be
rehabilitated for the Life Safety Performance Level
Cll.9.4.1 Definí/ion and Scope except as noted in the 1'ootnotes to Table 11-1.
Furring materials inelude wood or metal 1'urring Ceilings in Category c shall be capable of accommo
acoustical lile, gypsum board, plaster, or metal panel dating the relative displacement computed in accor
ceiling materials. dance with Section 11.7.3 or 11.7.4.
337
SEISMIC REHABILlTATION OF EXISTING BUILDlNGS
338
ASeE/SEI 41-06
ratios from Seetion 1 J .9.5.1 shall be capable of resist resisting both horizontal and vertical seismic design
ing seismic forces compuled in aeeordance wilh forces computed in aceordance with Section 11.7.3
Section 11.7.4. or 11.7.4.
339
SEISMIC REHABILITATlON OF EXISTING BUlLDlNGS
340
ASCFlSEI41-06
341
SElSMIC REHABILlTATION OF EXISTING BUILDlNGS
1. Category l. Vessels with structural support of con 1/.10.2.3.1 Life Safety Nonstructural Performance
tents, in which the shell is supported by legs or a Level
skirt; or
2. Category 2. F1at-bottom vessels in which the 1. Category 1 Equipment. If the Analytical
weight of the contents is supported by the noor, Procedure js selected based on Table 1 JI,
roof, or a structural platform. Category 1 equipment and supports shall be
capable of resístíng seismic forces computed in
Cll.10.2.1 Definítion (lIld Scope accordance with Section 11.7.3 or 11.7.4. If the
The vessel may be fabricated of materials such as Prescríptive Procedure ís selected based on
steel or other metal s, or tiberglass, or it may be a Table 11-1, Category 1 equipment shall meet
glass-lined tank. These requiremenls may also be prescriptive requirements in accordance with
applied, with judgment, to vessels that contain solids Section 11.7.2.
that act as a tluid, and vessels containing tluids not 2. Category 2 Equipment. If the Analytical
involved in the operation of lhe building. Procedure is selected based on Table 11-],
Category 2 equipment and supports shall be
capable of resisting seísmic forces computed in
11.10.2.2 Component Behavior and
accordance with Section 11.7.3 or 11.7.4. If lhe
Rehabilitation Methods
Prescriptive Procedure is selected based on
Tanks and vessels shall be considered acceleration
Table 11-1, Category 2 equipment shall meet
sensitive.
prescriptive requiremenls in accordance wíth
Tanks and vessels not conforming lo the accept
ance criteria of Section 1 L 10.2.3 shall be rehabilitated Section 11.7.2.
in accordance with Section 11.8.
/ J. 10.2.3.2 Immediate Occupancy Nonstructural
Performance Level
Cll.10.2.2 Component Behavior and
Rehabilitation Methods l. Category 1 Equipment. If the Analytical
Category 1 vessels fai! by stretching of anchor Procedure is selected based 00 Table 11-1,
bolts, buckling and disconnection 01' supports, and Category 1 equipment and supports shall be capa
consequent lilting or overlurning of the vessel. A ble of resisting seismic forces compuled in accor
Calegory 2 vessel may be displaced from its founda dance with Seclion 11.7.4. If the Prescriplíve
lion, or its shell may fail by yielding near lhe bottom, Procedure is selected based on Table 11-1,
creating a visible bulge or possible leakage. Category 1 equipment shall meet prescriptive
Displacement of bOlh types of vessel may cause requirements in accordance wilh Section 11.7.2.
rupturing 01' connecting piping and leakage. 2. Category 2 Equipment. If the Analytical
Calegory 1 residential water heaters with a capac Procedure is selected based on Table 11-1,
ity no greater lhan 100 gal may be rehabilítaled by Category 2 equipment and supports shall be capa
342
ASCFJSEI 41-06
ble of resisting seismic forces compuled in accor piping system characterized by containment of con
dance with Section 11.7.4. If the Prescriplive tenIS or mainlenance of a vacuum wilh no discernable
Procedure is selecled based on Table 11-1, leakage) is required. Operabilily (the condition of a
Category 2 equipmenl shall meet prescriptive piping system characterized by leak tightness as welI
requiremems in accordance with Section 11.7.2. as continued delivery. shutolf, or lhrottle of pipe con
tents tlow by mean s of unimpaired operalion of equip
11.10.2.4 Evaluation Requirements ment and components such as pumps, compressors,
AII equipment shall be visually evalualed 10 and valves) is desirable but requires a significantly
determine lhe existence 01' hold-downs, supports, and higher level of elfort to achieve.
bracing. The most common faHure of piping is joint fail
ure, caused by inadequaLe support or bracing.
Cll.10.2.4 Evaluation Requiremetlts
Existing concrete anchors may have lO be tesled 11.10.3.3 Acceptallce Criteria
by applying torque to the nuts lo contlrm lhal adequate Acceptance criteria shall be applied in accordance
strenglh is present. with Section 11.3.2.
343
SEISMIC REHABILlTATION OF EXISTING BUILDlNGS
loaded, in lhe range 01' 30 lo lOO lbs/lineal fl, wilh adjoining materials at lhe sprinkler heads shall be
branches of decreasing size lo 2lbs/fl. evaluated.
344
ASCElSEI41-06
Materials, Design and Manufacture, SP-58 (MSS Procedure is selected based on Table 11-1, fluid piping
1993). The piping syslems themselves should shall be eapable of resisting seismic design forces
be designed to meel lhe force provisions of Sec computed in accordance with Section 11.7.4. Piping
tion 11.7.3 or 11.7.4 and relative displacement provi thal runs between tloors and across seismic joints shall
sions of Seelion 11.7.5. The effeels of lempcralure be eapable of accommodating relative displacements
differences, dynamic fluid forces, and piping contents computed in accordance with Section 11.7.5.
should be taken inlo aceoun!.
Category 2 piping rehabililation is aceomplished 11.10.5.4 Evaluation Requirements
by slrenglhening support and bracing using the pre The support, flexibility, and protection al seismic
seriplive melhods of SP-58 as long as lhe piping faJls joints of fluid piping other than fire suppression piping
wilhin lhe size limitations of Ihose guidelines. Piping shall be evaluated.
thal exceeds lhe limitations of lhose guideJínes shall Piping shall be insulaled from detrimental heat
be designed to meel lhe force provisions of Sec- effects.
Lion 11.7.3 or 11.7.4 and relalive displaeemenl provi
sions of Seelion 11.7.5. Cll.10.5.4 Eva/ua/ion Requiremen/s
More informalion on designing and delaiJing seis The support and bracing of bends in the main
míe bracing can be found in ASHRAE RP-812 risers and lateraIs, as well as mainlenance of adequate
(ASHRAE 1999). flexibility to prevenl buckling, are espccially
importanL
11.10.5.3 Acceptance Criteria
Aeceplance crileria shall be applied in accordance 11.10.6 Dudwork
with Section 11.3.2.
11.10.6.1 Definition and Scope
1 1.10.5.3.1 Life Safety Nonstructural Performance Ductwork shall inelude HVAC and exhaust duct
Level work systems. Seismic restraints shall no! be required
for duclwork Ihal is nOl conveying hazardous malerials
l. Category 1 piping systems. If lhe Prescriptive
and thal meets either of the following condilions:
Procedure is selecLed based on Table 11-1, tluid
piping supports and braeing shall meel lhe prescrip 1. HVAC duCls are suspended from hangers 12 in.
live requirements 01' Seetion 11.7.2. If the Analylical or less in length from lhe lOp of the ducllO the
Procedure is selected based on Table 11-1, fluid supporting struclure. Hangers shall be installed
piping shall be capable of resisling seismic design without eccentricitíes that induce momenls in the
forces eomputed in aceordanee with Seetion 11.7.3 hangers; or
or 11.7.4. Piping lhal runs bctween tloors and 2. HVAC ducts have a cross-seclÍonal area of less than
aeross seismie joints shall be capable of accommo 6 sf.
dating relalive displaeemenls compuled in accor
dance wilh Section 11.7.5. 11.10.6.2 Component Behavior and
2. Category 2 piping systems. lf the Prescriptive Rehabilitation Methods
Procedure is selecled based on Table 11-1, fluid Ducts shall be considered acceleration-sensilive.
pipillg supports and bracing shall meel the prescrip Ductwork that runs between tloors or across seismic
live requirements of Seclion 11.7.2. If the Analytical joinls shall be consídered both acceleration- and
Procedure is selected based on Table 1 1- 1, fluid deformation-sensitive.
piping shall be capable of resisting seismic design Duetwork not conforming (O lhe acceptance crite
forees compuled in aeeordance Wilh Seclion 11.7.3 ría of SeclÍon 11.10.6.3 shall be rehabilitated in accor
or 11.7.4. Piping thal runs belween tloors and dance with Section 11.8.
across seismic joints shaJl be capable 01' accommo
daling reIative displacemenls computed in accor e 11.10.6.2 Component Behavior and
dance with Seclion 11.7.5. Rehabüitation Methods
Damage 10 ductwork is caused by failure of sup
J 1./0.5.3.2 Immediate Occupancy Nonstructural ports or lack 01' bracing that causes deformation or
Peiformance Level If lhe Prescriptive Procedure is ruplure of the ducts at joints, leading to leakage from
selecled based on Table 11-1, fluid piping supporls the system.
and bracing shall meellhe prescriptive requiremenls of Rehabilitation consists 01' strengthening supporls
Seclion 11.7.2 ror essential facilities. 11' the Analytical and slrenglhening or adding bracing. Prescriptive
345
SEISMIC REHABILlTATlON OF EXISTING BUILDINGS
design methods may be used in accordance with cn.10.7.2 Compollent Behavior and
Rectangular Industrial Duct Construction Standards Rehabilitatloll MetllOds
(SMACNA 1980) and HVAC Duct Construction Failure of these components eonsists of sliding,
Standards, Metal and Flexible (SMACNA 1985). lilting, or overlurning of tloor- 01' roof-mounted equip
More information on designing and delailing seismie ment off their bases, and possible loss oí' attaehmenl
bracing can be found in ASHRAE RP-812 (ASHRAE (wilh consequent falling) for equipment auaehed lo a
1999). vertical structure or suspended, and failure of e1eetrieal
wiring conneeted lo the equipment.
11.10.6.3 Acceptance Criteria Construetion 01' eJeetrieal equipment lo nationally
Aeceptance criteria shall be applied in accordance reeognized eodes and standard s, such as those
with Section 11.3.2. approved by ANSI, provides adequate strength to
aecommodate all normal and upset operating loads.
I 1./O.6.3.J Lije Safety Nonstructural Performance Basie rehabilítation consists of securely anehor
Level Duetwork shall meet lhe requirements of pre ing noor-mounted equipment by bolting, wilh
seriptive standards in accordance with Seelion 11.7.2. detailing appropriate to the base eonstruetion 01'
the equipmenl.
11./0.6.3.2 lmmediate Occllpancy Nonstructural
Performance Level Ductwork shall meet lhe require
11.10.7.3 Acceptallce Criteria
ments of prescriptive standards in aceordance with
Aeeeptanee eriteria shaJl be applied in aecordance
Seclion 11.7.2.
with Seetion 11.3.2.
11.10.6.4 EvaluatiOll Requirements
Duetwork shall be evaluated visually lo determine J1./0.7.3./ Lije Safety NOllstructural Pe/formance
its length, connection type, and cross-sectional area. Level If the Prescriptive Procedure is selected based on
Table 11-1, electrical equipmenl shalJ meet lhe pre
11.10.7 Electrical and Communications Equipment scriptive requirements 01' Seclion I J .7.2. If the
Analytieal Proeedure is selecled based on Table 11-1,
11.10.7.1 Dejinition alld Scope electrieal equipment shall be eapable of resisting seis
AII electrical and eommunicalion equipment, mic design forees eomputed in accordance with
including panel board s, bauery racks, mOlor control Section 11.7.3 or 11.7.4.
centers, switch gears, and other lixed components
10caIed in eleclrical rooms or elsewhere in the building
1 J. /0.7.3.2 Immediate Occupancy Nonstrllctllral
thal meet any of the following criIeria shall comply
Performance Level If the Prescriplive Proeedure is
with Ihe requirements of Ihis seclion:
selected based on Table 1/ 1, eleetrieal equipment
1. AII equipment weighing over 400 lbs; shall meet the prescriptive requiremenls of Sec
2. Unanchored equipment weighing over 100 lbs that tion 11.7.2. If the Analylical Proeedure is seleeted
does not have a factor of safety against overturning based on Table I 1-1, eleetrical equipmenl shall be
of 1.5 or greater where design loads computed in capable of resisting seismic design forees computed
aceordance witb Section 11.7.3 or 11.7.4 are in aeeordanee with Scetion 11.7.4.
applied;
3. Equipment weighing over 20 lbs that is altached lo
11.10.7.4 Evaluation Requiremellts
ceiling, wall, or olher support more than 4 ft aboye
Equipment shaIl be visually evaluated to deter
lhe tloor; and
mine its eategory and the exislence of the hold-downs,
4. Building operalion equipmenl.
supporls. and braces.
11.10.7.2 Componellt Behavior and
Rehabilitation Methods Cll.l0.7.4 Evalllation Reqlliremellts
Electrical equipment shalJ be eonsidered Larger equipment requiring lhe Analylical
acceleration-sensilive. Proeedure must be analyzed to determine forces, and
Eleclrical equipment not conforming lo the be visually evaluated. Concrete anehors may have to
aeceptance eriteria of Seclion 11.\0.7.3 shall be reha be tested by applying torque lo the nUlS lo confinn that
biJílated in accordanee wilh Section 11.8. adequate strenglh is present.
346
ASCFJSEI 41-06
347
SElSMIC REHABIUTATlON OF EXISTING BUILDlNGS
2. Category 3. Systems bracing and support shall Storage racks not conforming to the acceptance
meet prescriptive requirements in accordance with criteria of Section 11.11.1.3 shall be rehabilitated in
Section 11.7.2. accordance with Section 11.8.
3. Category 4. Fixlures weighing over 20 lbs shaIl be
adequately articulated or connections lo the build Cl1.11.1.2 Component Behavior and
ing shaIl be ductil e and the fixture shall be free to Rehabilitation Methods
swing without impacting adjoining materials. Storage racks may fail internally (through inade
quate bracing or moment-resisting capacity) or exter
11.10.9.3.2 1mmediate Occupancy Nonstructural nally (by overturning caused by abscnce or failure of
Performance Level . foundation attachmenls).
Rehabilitation is usually accomplished by the
l. Categories 1 and 2. The conneclion lo ceiling or
addilion of bracing to the rear and side panel s of
wall shall be present wilh no visible signs of distress.
racks and/or by improving the connection of the rack
2. Category 3. Systems bracing and support shall
columns to the supporting slab. In rare instances, foun
meel prescriptive requirements for essential facilities.
dation improvements may be required to remedy
3. Category 4. Fixtures weighing over 20 lbs shall be
insufficient bearing or uplift load capacity.
arliculaled or connections lo lhe building shall be
Seismic t'Orces can be established by analysis in
duclile and the fixlure shall be free lo swing with
accordance with Seclion 11.7.3 or 11.7.4. However,
out impacting adjoining malerials.
spedal aUention should be paid lo the evaluation and
analysis of large, heavily loaded rack systems because
11.10.9.4 Evaluation Requirements
01' their heavy loading and lightweighl structural
Light tixture supports shall be visually evalualed
members.
to determine the connection type and adequacy.
348
ASeE/SEI41-06
Bookcases nOI conforming lo lhe acceplance crÍle Compuler access tloors not conforming to the
ría 01' Section 11.11.2.3 shall be rehabililaled in aCCOf acceptance criteria of Section 11.113.3 shal1 be reha
dance with SeclÍon 11.8. bililated in accordance with Seclion 11.8.
J1.11.2.3.2 lmmediate Occupancy Nonstructural 11. J1.3.3.1 Life Salety Nonstructural Performance
Performance Level Bookcases shall be capable 01'
Level Computer access tloors need no. be rehabilitated
resisting seismic design force s computed in accOf
tor lhe Lite Safety Nonslruetural Performance Level.
dance with Section I J. 7.4.
11.11.3.3.2 Immediate Occupancy Nonstructural
11.11.2.4 Evaluation Requirements
Performance Level If the Prescriptive Procedure is
The loading, type, and condition of bookeases,
selected based on Table 11-1, prescriplive require
their eonneetion to support struetures, and type and
ments of Section J 1.7.2 shall be meto If the Analylieal
stability 01' supporting structure shalI be considered
Procedure is selected based on Table 11- J, computer
in lhe evalualion.
access tloors shall be capable of resisting se1smic
design forces computed in accordance with Sec
11.11.3 Computer Access Floors
tion 11.7.4.
11.11.3.1 Definítion and Scope
Compuler aecess lloors shall inelude panelized,
11.11.3.4 Evaluation Requirements
elevaled floor systems designed to facilitate aceess lo Bucklíng and racking ofaccess tlOOf supports,
wiring, tiber oplies, and olher services associated wilh eonnection lo lhe support struclure, and the effecls
of mounted equipment shall be considered in the
computers and other electronic components.
evaluation.
Cll.11.3.1 Definítion and Scope
Access tloors vary in height bul generally are less Cll.11.3.4 Evaluation Requirements
lhan 3 ft aboye lhe supporting structural floor. The Possible future equipment should also be consid
syslems inelude struclurallegs, horizontal panel sup ered in the evalualÍon.
ports, and paneIs.
11.11.4 Hazardous Materials Storage
11.11.3.2 CompOllent Behavior and
Rehabilita/ion Methods 11.11.4.1 Definition and Scope
Compuler access floors shaJl be considered bolh Hazardous malcrials storage shall inelude
acceleration- and deformation-sensitive. permanently installed conlainers--free-standing, on
349
SEISMIC REHABILlTATION OF EXISTING BUILDINGS
350
ASeE/SEI 41-06
351
SEISMIC REHABILlTATION OF EXISTING BUILDINGS
11. / /.7.3./ Life Safety Nonstructural Performance social, historie, and economie characteristics oí' the
Leve! Conveyors need nol be rehabilitated for the Lite building inventory. AlLhough financial incentives can
Safety Nonslructural Performance Level. induce voluntary risk mitigation, carefully planned
mandalory or directed programs, developed in coopera
11.11.7.3.2 lmmediate Occupancy Nonstructural tion wilh Ihose whose inleresls are atIecled, are
Performance Level If the Analytical Procedure is generalJy more etlective. Potential benetlts of such
selected based on Table 11 1, conveyors shall be capa programs inelude reduction of direet earthquake
ble 01' resisting seismic design torces computed in losses--casualties, eosts lo repair damage, and loss
accordance with Seclion 11.7.4. If the Prescriplive of use of buildings-as well as more rapid overaIl
Procedure is selected based on Table J I 1, conveyors rceovery. Rehabilitated buildings may also ¡ncrease
shall meet prescriptive slandards in accordance with in value and be assigned lower insurance rates.
Section 11.7.2. Additional issues lhat should be eonsidered for posi
tive or negative etlects incIude the interaetion of
11.11. 7.4 Evaluatioll Requiremellts rehabilitation wilh overall planning goals, historie
The stabilíty oí' machinery shaIl be considered in preservalion, and the local economy. These issues are
Ihe evaluation. discussed in FEMA 275 (FEMA 1998).
352
ASeE/SEI 41-06
1995), and in FEMA 276 (FEMA 1999). Since A.2.3 Historie Preservation
the data for these documents were developed prior Seismie rehabilitation of buildings can affect his
to this standard, the information is not based on torie preservation in two ways. First, lhe introduction
buildings rehabilitated specitically in accordance of new components that will be associated with the
with the current document. However, performance rehabilitation may in sorne way impact the historie
levels defined in this standard are not intended to fabric of lhe building. Second, the seismie rehabilita
be signiticantly di1'1'erent than parallellevels used tion work can serve to better protect the building from
previously, and costs should stíll be reasonably possibly unrepairable fulure earthquake damage. The
representative. e1'1'ects of any seismic risk reduction program on
historie buildings or preservation districts should be
A.2.2 Timetables and Effeetiveness carefuJly considered during program development,
Presuming that new buildings are being con and subsequent work should be carefully monitored
structed with adequate seismic protection and that to assure compliance with national preservation guide
older buildings are occasionally demolished or lines discussed in Section A.6.
replaced, the inventory of seismically hazardous build
ings in any community wil1 be gradually reduced. This
aUrition rate ís normally small, since the structures of A.3 USE IN PASSIVE PROGRAMS
many buildings have use fui lives of J00 years or more
and very few buildings are actually demolíshed. If Programs that only require seismic rehabilitation in
buildings or districts become historically significant, association with other activity on the building are
they may not be subject to attrition at all. Thus, in often c1assified as "passive." "Active" programs, on
many cases, doing nothing (or waiting for an outside the other hand, are lhose thal mandate seismic rehabili
influence to force action) may present a large cumula tation for targeted buildings in a certain time frame,
live risk to the inventory. regardless of olher activity associated with lhe build
Jt has often been pointed out that exposure time is ing (see Section 1.6.3). Activities in a building that
a significant element of rísk. The time aspect of risk may passively generate a requirement to seismically
reduction is so compelling that it ofien appears as part rehabilitate-such as an increase in occupancy, struc
of book and workshop titles; for example, Between tural modificalion, or a major renovation tha! would
Two Earthquakes: Cultural Property in Seismic Zones significantI y exlend Ihe life of the building-are
(Feilden 1987); Competing Against Time (California called "lriggers." The concept of certain activities
Governor's Board of Jnquiry 1990); and In Wait for the triggering compliance wilh current standard s is
Next One (EERI 1995). Therefore, an important con weIl established in building codeso However, lhe
sideration in the development of programs is the time details of lhe requiremenls have varied widely.
allolted to reach a certain risk reduction goal. It is gen These issues have been documented with respecl to
erally assumed that longer programs create less hard seismic rehabilitation in California (Hoover 1992).
ship than short ones by al10wing more flexibility in Passive programs reduce risk more slowly lhan do
planning for the cost and possible disruption 01' reha active programs.
bilitation, as well as by aIlowing natural or accelerated
attrition to reduce undesirable impacls. On the other A.3.l Selection of Seismic Rehabilitation Triggers
hand, the net reduction of risk is smaller due to the This standard does not cover triggers for seismic
increased exposure time of the seismically deficient rehabilitation. The extent and detail of seismic lriggers
building stock. will greatly affecllhe speed, effectiveness, and
Given a high perceived danger and certain advan impacls of seismic risk reduction, and the selection
tageous characteristics of ownership, size, and occu of triggers is a policy decision expecled to be made
pancy of the target buildings, mandatory programs localIy by the person, agency, or jurisdietion responsi
have been completed in as Hule as five to ten years. ble for the inventory. Triggers tha! have been used or
More extensive programs-involving complex build considered in (he pasl include revision of specified
ings such as hospital s, or with significant funding proportions of the slruclure; renovatíon 01' specified
Iimitations-may have completion goals of 30 to percenlages 01' the building area; work on the building
50 years. Deadlines for individual buildings are also Ihat costs more than a specified percentage 01' the
ofien determined by the risk presented by building building value; change in use that increases lhe occu
type, occupancy, location, soil type, funding availabil pancy or importance of Ihe building; and changes of
ity, or other faClors. ownershíp.
353
SEISMIC REHABlLlTATION OF EXISTING BUILDINGS
A.3.2 Selection oC Passive Seismic Rehabilitation practice. Therefore, these building types have some
Standards times been targeted in active programs.
This standard purposely atfords a wide variety of A more pragmatic consideration is the ease of
options that can be adopted for seísmíc rehabilitatíon locating targeted buildings. If certain building types
lo facilílale risk reduclion. Standard s can be selected cannot be easily identitied, eíther by the local jurisdic
with varying degrees of risk reduclion and varying tion or by the owners and their engineers, enforcement
costs by designating difIerent Rehabilitation could become difficuIt and costly. In the extreme,
Objectives. As described previously, a Rehabililation every building designed prior to a given acceplable
Objeclive is created by specifying a desired target code cycle would require a seismic evaluation lO deter
Building Performance Level for specif1ed earthquake mine whether targeted characteristics or other risk fac
ground motion criteria. A jurisdiction can thus specify tors are present, the cost of which may be significant.
appropriate standards by extractíng applicable require An alternate procedure might be to select easily identi-·
ments and incorporating them ioto its own,code or fiable building characteristics 10 set timelines, even if
standard, or by reference. more accurate building-by-building priorities are
A single Rehabilitation Objective could be somewhat compromised.
selected under alltriggering situations [the Basic
Safety Objective (BSO), for example], or more strin A.4.2 Selection oC Active Seismic Rehabilitation
gent objectives can be used for important changes to Standards
the building and less stringenl objeclives for minor As discussed for passive programs in Sec
changes. For example, il is sometimes necessary for tion A.3.2, this standard is written to facilitate a wide
design professionals, owners, and building officials lo variation in risk reduction. Faclors used to determine
negotiate the extent of seismic improvements done in an appropriate Rehabilitation Objective include local
association with building alterations. Complete reha seismicity, the costs oí' rehabilitation, and local socio
bilitation is often required by local regulation for com economic conditions.
plete renovation or major structural alteralions. It is It may be desirable to use Simplified Rehabili
lhe intent of lhís standard to províde a common frame tation Methods for active or mandated programs. Only
work for all of lhese various uses. Limited Performance Objectives are included in this
standard for this method. However, if a program has
idenlified a local building type with few variations in
A.4 USE IN ACTIVE OR MANDATED material and contiguration, a study of a sample of
PROGRAMS typical buildings using Systematic Methods may
eslablish that compliance with the requirements of
Active programs are mosl often largeled al high-risk Simplified Rehabilitation meets ¡he BSO, or beuer,
building types or occupancies. Active seismic risk for this building type in this location. Such risk and
reduction programs are ¡hose ¡hal require owners lo performance decisions can only be made at the local
rehabilitate their buildings lO specit1ed Rehabililation leve!.
Objectives in a certain time frame or, in the case of
government agencies or other owners of large invento
ries, to set self-imposed deadlines for completion. A.S SOCIAL, ECONOMIC, AND POLITICAL
CONSIDERATIONS
A.4.1 Selection of Buildings to be Included
Programs would logically larget only the highest The scope of this standard is limited lO [he engineering
risk buildings DI' al leasl create priorities based on risk. basis for seismically rehabilitating a building, but the
Risk can be based on the likelihood of building failure, user should also be aware 01' significant nonengineer
the occupancy or importance 01' buildings, soil types, ing issues and social and economic impacIs presented
or olher faclors. This standard is primarily wriUen to in Ihis section. These problems and opportunities,
be used in the process of rehabilitation and does nol which vary with each situation, are discussed in
directly address the comparative rísk level of varíous FEMA 275 (FEMA 1998).
building types 01' other risk factors. Certain building
types, such as unreinforced masonry bearing wall A.S.1 Construction Cost
buildings and older, improperly detailed reinforced If seismic rehabilitation were always inexpensive,
concrete frame buildings, have historically presented a the social and polítical costs and controversies would
high risk, depending on local seismicily and building largely disappear. Unfortunately, seismic rehabilitation
354
ASCElSEl 41-06
oftcn requires removal of archileclUral malerials to least 50 years old, and is Iisted in or is potentially eli
access lhe vulnerable portions of Ihe struclure. gible for the National Regisler ol' Hisloric Places
Nonseismic upgradíng (e.g., electrieal, handieapped andJor a state or local register as an individual slrue
aecess, historie restoration) is frequently triggered by a ture, or as a contributing struelUre in a district
building eode's renovalion permil requirements and is Struetures less than 50 years old may also be his
desirable Lo undertake at the same time. toric if they possess exceptional signitieanee. For
historie buildings, users should develop and evaluate
A.5.2 Housing alternative Solulions with regard lo lheir effect on
Although seismic rehabilitalíon ullimalely lhe los8 of historic eharaeter and fabrico This sectÍon
improves the housing stock, units can be temporaríly provides guidance for developing such alternative
10Sl during lhe construction phase, which may be very solutions.
lenglhy, and can require relocalíon of tenants.
A.6.1 Secretary oC the Interior's Standards
A.5.3 Impacts on Lower-Income Groups
Por hislorie buildings, users should develop aller
Lower-íncome residents and commercial tenanlS
nalÍve solutions using the Stalldards jor rhe Treatment
can be displaced by seismie rehabilitation and nonseis
oi Historie Propel1ies with Guidelines jor Preserving.
míc upgrading, which can raise rents and real estate
Rehabilitating. Restoring, and Reeonstrueting Historie
prices because of lhe need lo recover the costs of lhe
Buildings (Seerelary of Ihe Interior 1995).
work. Possible hardships on lhese groups need lo be
In addition lo rehabilitation, the Secretary of the
given heavy consíderation because lhey may affect the
Interior also has standards for preservation, reSlora
vcry societal fabric of a community.
tion, and reconstruclion [Standards jor the Trearment
A.5.4 Regulations oj Historie Propel1ies (Secretary of lhe Interior
As wilh etl'orts lO impose safety regulations in 1992)]. A seismie rehabilitation projeel may inelude
olher tields, mandating seismie rehabílitation is often work thal falls under the Rehabilílation Standards,
controversial. Thís standard is wrítten as mandalory lhe Trealment Standards, or bolh. This standard is
code provisions ror possible applieation and adaptation inlended for use as part of rehabilitalion, preservalion,
for that use. In sueh cases, political controversy should and resloralion work done on historie buildings.
be expecled and nonengineering issues of all kinds For historie buildings as well as for other struc
should be carefully considered. lures of architeetural inleresl, it is importanl lo nole
Ihat Ihe Seerelary ol' the Interior's Standards define
A.5.5 Architecture rehabililation as "the process of relurning a property 10
Even ir a building is not historie, there are often a state of utility, through repair or alteration, which
signiticant architectural impacts. The exterior and makes possible an effieient eontemporary use while
interior appearanee may ehange, and the division of preserving lhose portions and features of the property
spaces and arrangement ol' circulation routes may whieh are signifieanl 10 its historie, architectura) and
be altered. cultural values." Further guidanee on the treatmenl of
historie properties is eontained in publications listed
A.5.6 Community Revítalization in lhe Teehnieal Preservaríon Services jor Historie
Seismie rehabílitation not only poses issues and Buildings Sales Publíeation Catalog available online
implies costs, bUl also conters benetits. In addition to at http://www.er.nps.govlhpsltpsltpscal.htm.
enhaneed public safety and economic protection from
earlhquake loss, seismic rehabilitation can playa lead A.6.2 Application oC Building Codes and Standards
ing role in the revitalization of older commercial and It should be nOled that many codes covering his
industrial areas as well as residential neighborhoods. torie buildings allow sorne amount of tlexibility in
Potenlial synergies between lhese two programs in required performance, depending on the effect of reha
a community should be carefully explored by local bililation on important historie features.
planners, officials, and design prol'essionals. If a building eontains items of unusual arehitee
tural interest, consideration should be given lo the
A.6 CONSIDERATIONS FOR HISTORIC value of these items. It may be desirable to rehabilitate
BUILDINGS the building 10 lhe Damage Control Struetural
Performance Range as specified in this standard lo
11 must be determined early in the process whether a ensure that the architectural fabrie survives eertain
building is "historie." A building is historie if it is at earthquakes.
355
SEISMIC REHABlLlTATION OF EXISTJNG BUILDJNGS
356
ASeE/SEI 41-06
Cz Modificatíon factor lo represenl the effects in the direction under consideration, as pre
of pinched hysteresis shape, cyc1ic stiffness scribed by Eq. 9-11
degradation and strength deterioration on Dp Relative seismic displacement lhat the
the maximum displacemenl response, componenl must be designed lo accommo
Eqs. 3-4, 3-5,3-9,3-14,3-19 date, Eqs. 11-8, 11-9, ll-lO, Il-lI
Ch Coefficienl lO account for effect of nonuni Dr Drift ratio for nonstructural components,
form moment given in Load and Resistance Eq. 11-7
Factor Design Specification lar Structural DTD Total design displacement, in. (mm), of a
Steel Buildings (LRFD) (AISC 1999), componenl of the ¡solation system, includ
Eq.5-9 ing both translational displacement at lhe
CF¡ Slage combination factors for use with center of rigidily and the component of tor
velocity-dependent energy dissipation sional displacement in the direction under
devices as calculated by Eq. 9-31 or 9-32 consideration, as specitied by Eq. 9-6
Cm Effective mass factor from Table 3-1, DTM Total maximum displacement, in. (mm),
Eqs. 3-9, 3-15 of a component of the isolatÍon system,
C, Numerical value for adjuslment of period including both translational displacement at
T, Eq. 3-6 the cenler of rigidity and lhe component of
Cvx Verlical distribution factor for the pseudo torsional displacement in the direclion under
laleral force, Eqs. 3-10, 3-11 consideralion, as speciíied by Eq. 9-7
D Generalized deformation, unitless E Young's modulus of elasticity, Eqs. 4-9,
Relative displacement between two ends of 5-1,5-2,5-17,8-2,8-4,8-5
an energy dissipation unit, Eqs. 9-1, 9-20, Ec Modulus of elasticily of concrete, psi,
9-22 Eq.6-6
D- Maximum negative displacement of an Efe Expected elastic modulus of frame mate
energy dissipation unit, Eqs. 9-21, 9-23 rial, ksi, Eq. 7-7
D+ Maximum positive displacement of an Eu)Op Energy dissipated, kip-in. (kN-mm), in an
energy dissipation unit, Eqs. 9-21, 9-23 isolator unÍ[ during a fulI cycle of
D Relative velocity between two ends ol' an reversible load over a test displacement
energy dissipation unit, Eqs. 9-22, 9-25 range from A+ 10 A, as measured by
D"ve Average disp[acement ol' an energy dissipa the area enclosed by the loop of the
tion unit, equallo (ID+I + ID 1)/2, Eq. 9-24 force-deflection curve, Eq. 9-13
Delear Required clearance between a glass compo Em Masonry elastic modulus
nent and the trame, Eq. 11-9 Eme Expected elastic modulus of masonry
DCR Demand-capacity ratio, computed in accor in compression as determined per
dance wilh Eq. 2-1 or required in Eq. 2-2 Section 7.2.2.4, Eq. 7-7
DCR Average demand-capacity ratio for a story, E, Modulus of elaslicity of reinforcement, psi,
computed in accordance with Eq. 2-2 Chapter 6
DD Design displacement, in. (mm), al the cen EJe Expected elastic modulus of reinforcing
ter of rigidity of lhe isolalion system in [he steel per Section 7.2.2.8
directÍon under consideration, Eqs. 9-2, F Force in an energy dissipation unit,
9-6,9-8,9-10,9-14,9-15,9-18,9-22 Eqs. 9-1, 9-20, 9-22, 9-25
D~ Design earthquake larget displacemenl, in. F- Negative force, k, in an isolator or energy
(mm), at a control node Jocated al the cen dissipalion unit during a single cycle 01'
ter of mass of the tirst tloor abo ve lhe iso prototype testing al a displacement ampli
lation syslem in the direclion under consid tude of A-, Eqs. 9-12, 9-21,9-23, 9-38
eration, as prescribed by Eq. 9-10 Ft Positive force, k, in an isolator or energy
DM Maximum displacement, in. (mm), al the dissipalion unit during a single cycle of
center of rigidity oí' the isolation system in prototype testing at a displacement ampli
lhe direclion under consideration, Eqs. 9-4, lude of á+, Eqs. 9-12, 9-21, 9-23, 9-38
9-7,9-11,9-16,9-17,9-19 Fu Factor to adjust spectral acceleration in lhe
D~ BSE-2 target displacement, in. (mm), at a short-period range for site class, Eq. 1-7
control node localed at the cenler of mass Fa Allowable axial buckling stress, Eq. 5-36
of the first t100r aboye Ihe isolation system F¡ Inertia force at tloor level i, Eq. 9-27
357
SEISMIC REHABILlTATION OP EXlSTlNG BUILDING S
Lateral load applied at floor level i, Height of the relaining wall, Eq. 4-16
Eqs. 3-12, C3-2 Moment of inertia, Eq. 6-6
m-th mode horizontal inertia force at tloor Moment of inertia of a beam, Eqs. 5-1,
level i, Eq. 9-34 5-17
Horizontal seismic force for design of a Moment of inertia of a column, Eq. 5-2
structural or nonstructural component and Moment oí' inertia of column section,
its connection to the structure, Eqs. 2-3, Eq.7-7
2-4, 2-5, 2-6, 2-7 Moment of inertia oí' most l1exible trame
Component seismic design force applied member confining infill panel, Chapler 7
horizonlally at the center 01' gravity of the Moment of inertia of gross concrete section
component or distributed according to the about centroidal axis, neglecling
mass dislribulion of the component, reinforcement, Chapter 6
Eqs.II-I, 11-2, 11-3, 11-4 Component performance factor; 1.0 shall
Component seismic design force applied be used 1'01' lhe Life Safety Nonstruclural
vertically at the center of gravÍly of lhe Performance Levcl and 1.5 shall be used
component or distributed according to the for the Immediate Occupancy
mass distribution of the component, Nonstructural Performance Level,
Eqs. 11-2, 11-5, 11-6 &ls. 11-1,11-3,11-4,11-5,11-6
Diaphragm lateral force al tloor level x, j A coefficient used in linear procedures to
Eq.3-12 estimate lhe actual forces delivered lo
Expected tensile strength, Eqs. 5-20, 5-22, force-conrrolled components by olher
5-24 (yielding) components, Eqs. 3-4, 3-19
Factor to adjust spectral acceleration at K Lenglh faclor 1'01' brace; defined in Load
1 sec for site c1ass, Eq. 1-8 and Resistance Factor Desígn Specificatioll
Design shear strength of bolts or rivets, for Structllral Steel BlIildings (LRFD)
Chapter 5 (AISC 1999), Chapler 5
F", Unfactored nominal shear strength of bolts K' Slorage sliffness as prescribed by
01' rivets given in Load and Resistance Eq.9-23
Factor Desígn Specijicatíon for Structural K" Loss slitl'ness as prescribed by Eq. 9-24
Steel Buildings (LRFD) (AISC 1999), Ko Rotational stitl'ness 01' a partially restrained
Eq.5-18 connection, Eqs. 5-15, 5-16, 5-17
Lateral load applied at 11001' level x, Effeclive rotational slitl'ness 01' Ihe founda
Eg. 3-11, Fig, C7-2 tion, Eq' 4-14
Specified minimum yield stress l'or the lype
ol' stecl being used, Eq. 5-7 = M*( 2; y, Eq. 4-14
F, 01' a beam, Chapter 5 Flexural stiffness, Eqs. 5-27, 5-29
F,of a column, Chapter 5
K"
KDmax Maximum eftective stitl'ness, k/in., 01' the
Expected yield slrength, Eqs. 5-1 through isolation system at the design displacemenl
5-8,5-19,5-23,5-25,5-31,5-34 in lhe horizontal direction under considera
F, of a llange, Chapler 5 tion, as prescribed by Eq. 9-14
Ú)wer-bound yield slrength, Chapler 5 KDmin Minimum effective sliffness, klin.
Soil shear modulus, Eqs. 4-6, 4-12, 4-14, (kN/mm), of the isolation system at the
Shear modulus of steel, Eqs. 5-28, 5-33 design displacement in Ihe horizontal direc
Modulus of rigidity of wood structural tion under consideration, as prescribed by
panels, psi, Eqs, 8-2, 8-4, 8-5 Eq.9-15
Shear stitTness of shear wall or diaphragm Formal conversion factor rol' calculaling
assembly, Eqs. 8-1,8-3 LRFD reference resistance bascd on allow
Masonry shear modulus able stress factor, Section C8.3.2.5
Shear modulus of masonry as determined EtTectivc stillness 01' the building in the
per Section 7.2,2.7 direction under consideralion, rOl' use with
Initial 01' maximum shear modulus, the NSP, Eq. 3-14
Eqs. 4-4, 4-5, 4-12 Elastic stiffness of a link beam, Eqs. 5-27,
H Horizontal load on footing, Chapter 4 5-30
358
ASeE/SEI 41-06
K¡ Elastic stiffness of the building in the direc Me Ultimate moment capacity of footing,
tion under consideration, for use with the Eq.4-8
NSP, Eq. 3-13 MCE Expected flexural strength of a member or
KMmru: Maximum effective stiffness, k/in., of the joiot, Eqs. 5-3,5-4,5-6,5-15,5-16,5-18,
isolation system at lhe maximum 5-22,5-24, 5-25, 5-26, 5-32
displacement in the horizontal direction MeE:.: Expected bending strength of a member
under consideration, as prescribed by about the x-axis, Eqs. 5-10, 5-11, 5-13, 6-1
Eq.9-16 MCEy Expected bending strength of a member
KMmin Minimum effective stitfness, k/in., of the about y-axis, Eqs. 5-10, 5-11, 5-13, 6-1
isolation system al the maximum displace MCLx Lower-bound tlexural slrenglh of the mem
menl in the horizontal direction under con ber aboul the x-axis, Eq. 5-12
sideration, as prescribed by Eq. 9-17 MCLy Lower-bound flexural strenglh of the mem
Ks Shear stiffness, Eqs. 5-27, 5-28 ber about the y-axis, Eq. 5-12
Ksh Horizontal spring stíffness, Chapter 4 Mees Moment acting on the slab column strip,
Kw Global stiffness of steel plate shear wall, Chapler 6
Chapler 5 Mn Nominal moment strength at section,
Kx Effective translational stiffness of the foun Chapler 6
dation, Eq. 4-14 Mnes Nominal moment slrenglh of the slab col
L Lenglh of footing in plan dimension, umn strip, Chapler 6
Eqs. 4-7,4-8 Mar Total overturning moment induced on the
Length of pile in vertical dimension, element by seismic forces applied at and
Eq.4-9 aboye the level under consideralion,
Length of member along which deforma Eqs. 3-4, 3-5
tions are assumed to occur, Chapler 6 MpeE Expected plastic moment eapacity, Eq. 5-6
Length of wall or wall pier, Eqs. 7-3, 7-5 MST Stabilizing moment produced by dead
Diaphragm span, distanee between shear loads acting on the e1ement, Eqs. 3-4, 3-5
walls or colleetors, Eqs. 8-3, 8-4, 8-5 MUD Design moment, Chapter 6
Lb Lenglh or span of beam, Eqs. 5-6, 5-17 MUDx Design bending moment about the x-axis
Distanee between points braeed against for axial load PUF' kip-in., Eq. 6-1
lateral displaeement of the compression MUDy Design bending moment about the y-axis
flange or between points braeed to prevent for axial load PUF' kip-in., Eq. 6-1
twist of the cross sections; given in Load MUFx Bending moment in the member about the
and Resistance Factor Design Specijication x-axis, ealculated in accordance with
for Structural Steel Buildings (LRFD) Section 3.4.2.1.2, Eq. 5-12
(AISC 1999), Eq. 5-9 MUFy Bending moment in the member about the
Le Length of beam, c1ear span between y-axis, eaIculated in aeeordanee with
columns, Chapter 5 Section 3.4.2.1.2, Eq. 5-12
Lin! Length of infiII panel, Eqs. 7-10, 7-12 Mx Bending moment in a member for the
Lp The limiting unbraeed length between x-axis, Eqs. 5-10, 5-11, 5-13
points of lateral restraint for the full plaslie My Bending momeot in a member for the
moment capaeity to be effeetive; given in y-axis, Eqs. 5-10, 5-11, 5-13
Load and Resistance Factor Design Yield moment strength at seetion, Eq. 6-6
Specification for Structural Steel Buildings N Number of piles in apile group, Eq. 4-9
(LRFD) (AISC 1999), Eqs. 5-6, 5-9 N Average Standard Penetration Test (SPT)
Lr The limiting unbraced lenglh between blow eount in soil within the upper 100 ft
poinlS of lateral support beyond which e1as of soil, caleulated in aeeordance wilh
tic lateral torsional buekling of the beam Eq.2-8
is lhe failure mode; given in Load and (N¡)60 SPT blow counl normalized l'or an effeetive
Resistance Factor Design Speeification stress of 1 ton psf and eorreeted to an
for Structural Steel Buildings (LRFD) equivalent hammer energy efficieney of
(AISC 1999), Eq. 5-9 60%, Eq. 4-5
M Design moment at a seetion, Eq. 6-4 Nb Number ol' bolts or rivets, Eqs. 5-18, 5-22,
M* Effeetive mass for lhe first mode. Eq. 4- 14 5-24
359
SEISMIC REHABILITATION OF EXISTING BUILDINGS
N II
FaclOred axial load normal lo cross section Qo Design aClion due lO dead load, Eqs. 3-2,
occurring simultaneously with VI/' To be 3-3
laken as posilive for compression, negalive QE Design action due lo design earlhquake
for lension, and to include effects of ten loads, Eqs. 3-18, 3-19
sion due to creep and shrinkage, Eq. 6-4 QG Design action due to gravity loads,
P Vertical load on footing, Eq. 4-8 Eqs. 3-2, 3-3, 3-\8, 3-\9, 7-5
Axial force in a member, Eqs. 5-2, 5-4 QL Design action due to Iive load, Eqs. 3-2, 3-3
Pe Lower-hound 01' vertical compressive Qs Design action due lO snow load, Eqs. 3-2,
strength for wall or wall pier, Eqs. 7-7, 3-3
7-13 Quo Deformation-conlrolled design action due
PCE Expecled axial slrength 01' a member or lO gravity and earthquake loads, Eqs. 2-1,
joiot, Eqs. 5-19, 5-20, 5-21, 5-26 3-18,3-20
Pn Lower-bound axial strength of column, QUF Force-conlrolled design action due lo grav
Eqs. 5- lO, 5-11, 5-\2, 5-36 ity and earlhquake loads, Eqs. 3-19, 3-21
Lower-bound axial compressive force due Qv Yield slrenglh 01' a componenl, Figs. 2-3,
to gravity loads specified in Eq. 3-4 2-5
Po Superimposed dead load al the top of Ihe Q'y SubsUtute yield strength, Fig. 2-5
wall or wall pier under consideration, R Ratio of the elastic-strenglh demand to the
Eqs. 7-\, 7-3 yield-strength coefficient, Eqs. 3-14, 3-15
PEY Probability of exceedance in Y years, Rmax Maximum strenglh ratio, Eq. 3-16
expressed as a decimal, Eq. 1-2 Rar Response moditication factor for overturn
PI Plasticity index for soil, determined as ing momenl MOT, Eq. 3-5
lhe difference in water content 01' soil at Rp Component response modification factor
the liquid limit and plastic limit, from Table 11-2, Eq. 11-3
Section 1.6.1.4.\ RRS¡',a Ratio of response spectra factor for hase
Po Nominal axial load strength at zero eccen slab averaging, Eq. 4-11, Fig. 4-7
tricity, Chapter 6 RRS, Ratio 01' response spectra factor for embed
PR Mean return period, Eq. \-2 menl, Eq. 4-12
PUF Design axial force in a member, Eqs. 5-10, SI Spcctral response acceleration parameter
5-11, 5-12 at a one-second period, oblained from
Pye Expecled yield axial slrength of a member, response acceleration maps, Eqs. 1-1, 1-3,
Eqs. 5-2, 5-4 \-5
Q Generalized force in a component, Sa Spectral response acceleration, Eqs. 1-8,
Figs. 2-3, 2-5, 5-1, 6-1, 7-1, 8-1 1-9, 1-10,3-10,3-15,3-16
Q"iloM' AIJowable bearing load specified for ¡he So Distance between n-lh pile and axis of rota
design of deep foundations for gravity tion of apile group, Eq. 4- 10
loads (dead plus live loads) in the available Ss Spectral response acceleration parameter at
design documents, Eq. 4-2 short periods, obtained rmm response
Qc Expected bearing capacity 01' deep or shal acceleration maps, Eqs. 1-1,1-3,1-7
low foundation, Eqs. 4-2, 4-3, 4-7 SXI Spectral response acceleration parameter at
QCE Expected strength of a component al the a l-sec period for any Earthquake Hazard
deformation level under consideration, Level and any damping, adjusted for sile
Eqs. 2-1, 3-20,5-3 through 5-8, 5-18, 5-22, class, Eqs. 1-5, 1-10, 1-11, 1-13, 1-14,
5-24, 5-25, 5-26, 5-30, 5-31,5-32, 5-34, l 15, 1 16
5-35,7-3,7-15 Sxs Spectral response acceleration parameter at
QCE:b Expected bending strength of the beam, shorl periods for the selected Earthquake
Eq.5-14 Hazard Level and damping, adjusted for
QCL Lower-bound estimale of the strength ol' a site c1ass, and determined in accordance
component at the de1'ormation level under with Section 1.6.104 or 1.6.2.1, Eqs. 1-4,
consideration, Eqs. 3-21,5-36, 6-5, 7-4, 1-8,1-9,1-11,1-13,1 14,1-15,1-16,4-]6,
7-5,7-6,7-14 11-1, 11-3, Il-4, 11-5, 11-6
QClJ.> Lower-bound strength of the connection, T Fundamental period of the building in lhe
Eq.5-14 direction under consideralion, seconds,
360
ASeE/S El 41-06
Eqs. 1-8, I 10, 3-6, 3-7, 3-8, 3-9, 3-10, elemenls below lhe isolalion system, as
3-11,4-10,4-11,4.12,9-29 prescribed by Eq. 9-8
Tensile load in column, Eq. 5-13 Ve Nominal shear strenglh provided by con
Fundamenlal period of lhe building using a crete, Eq. 6-4
model with a tixed base, seconds, VCE Expected shear slrenglh 01' a member,
Eqs. 4-14, 4-15 Eqs. 5-11, 5-31,5-32,5-34
T Fundamenlal period ol' the building using a Va Lower-bound shear strenglh, Eq. 7-4
model wíth a tlexíb!e base, seconds, Vd Base shear al A", Fig. 3-1, Chapter 3
Eqs. 4-14,4-15 Vdl Lower-bound shear strength based on díag
T/T'JJ Effective period lellglhening ralio, onal tension stress tor wall or wall pier,
Eqs. 4-13, 4-14, 4-15, Fig. 4-8 Chapler 7
To Period al which the conslanl acceleration V¡¡. Expecled slory shear slreng!h of lhe bare
regíon oí' lhe design response speclrum slee! frame taken as lhe shear capacily of
begins al a value = 0.2Ts, Eqs. 1-8, 1-12 the column, Chapter 7
TCE Expected tensile strength of column com Vg Shear aCling on slab critical section due to
puted in accordance with Eq. 5-8 gravity loads, Chapter 6
TD Effeclive period, in seconds, ol' the seismic Vi The tOlal calculated laleral shear force in
isolaled slruclure al the design the direction under consideration in an ele
displacemenl in lhe direclion under consid menl or at story i due lo earlhquake
eration, as prescribed by Eq. 9-3 response to the selected ground shaking
Te Etfective fundamental period of the build level, as indicated by Ihe selecled linear
ing in the direction under consíderation, for analysis procedure, Eqs. 2-2
use wilh the NSP, Eqs. 3- 13, 3-14 Vine Expected shear strength of infill panel,
Effeclive fundamental period, in seconds, Eq.7-8
oí' the building slructure aboye the Vn Nominal shear strength al sectíon, Eq. 6-4,
isolation interface on a fixed base in the 6-5
direclÍon under consideration, Vo Shear slrenglh of slab al crilical section,
Eqs. 9-10, 9-1J Chapter 6
T¡ Elastic fundamental period of lhe building Vp< Panel zone shear, Chapler 5
in the direction under consideration, l'or use Vr Expected shear strength of waIl or waIl pier
wilh lhe NSP, Eq. 3-13 based on rocking shear, Eq. 7-3
TM Effeclive period, in seconds, of the seismic Vs Nominal shear slrenglh provided by shear
isolaled struclure al the maximum displace reinforcemenl, Chapler 6
men! in lhe direction under consideralion, The total lateral seismic design force or
as prescribed by Eq. 9-5 shear on elements aboye the isolation sys
Tm m-th mode period of !he rehabilitated build tem, as prescribed by Section 9.2.4.402,
ing including the sliffness of the velocíty Eq.9-9
dependent devices, Eq. 9-35 V, Base shear in the building al the targel dis
Ts Period al which lhe constant acceleration placement, Chapter 3
region of the design response spectrum VI" Lower-bound shear strenglh based on toe
transitions lo the constanl velocity region, compressive stress for wall oc wall pier,
Eqs. 1-8, 1-9, 1-10, 1-11, 1-12, 1-13,3-9, Chapler 7
3-14 VleSC Test load al tirst movement of a masonry
T" Secant fundamental period of a rehabili- unit, Eq. 7-2
laled building caIculaled using Eq. 3-14 bul Vu Factoced shear force al section, Chapler 6
replacing lhe etl'eclive stiffness (Ke) with Vy Yield strength of the building in !he direc
(he secant stitTness (K,) al !he targel dis lion under consideralÍon, tor use with lhe
placemenl, Eq. 9-37 NSP, Eq. 3-15
V Pseudo-Ialeralload, Eqs. 3-9, 3-10 Vya Nominal shear strength of a member
Design shear force at seclion, Eq. 6-4 moditied by lhe axial load magnilude,
V* Modified equivalent base shear, Chapter 9 Chapler 5
Vó The tOlallaleral seismic design force oc W Weight of a component, calculated as spec
shear on elements of the isolation system or ified in this standard, Chapter 2
361
SEISMIC REHABILlTATION OF EXISTING 'BUlLDlNGS
362
ASeE/SEI 41-06
db Overall beam deplh, Eqs. 5-7, 5-8, 5-21, J, Yield strength of tension reinforcement,
5-22,5-23,5-24,5-25,5-26,5-29 Eqs. 6-2, 6-3
Nominal diameter of bar, in., Eq. 6-3 Yield strenglh of shear reinforcemenl,
d bg Depth 01' the bolt group, Table 5-5 Eq.6-4
de Column deplh, Eq. 5-5 j~e ExpeCled yield slrength of reinforcing sleel
dí Depth, 1'1, of a layer 01' soils having similar as determined in Section 7.2.2.8
properties, and located within 100ft of the g Acceleration of gravity 386.1 in./sec 2 (or
surface, Eqs. 1-6, 1-7 9,807 mm/sec2 for SI units), Eqs. 3-14,
d. Deplh to gmundwaler level, Eq. 4-5 4-14,9-2,9-3,9-4,9-5,9-30
dz Overall panel zone depth between continu h Period effect factor 1 + 0.15 . In Te'
ity plates, Chapter 5 Eq.3-16
e Length of eccentric braced frame (EBF) Average story height aboye and below a
link beam, Eqs. 5-28, 5-29, 5-30, 5-32 beam--column joint, Eq. 5-17
Parameter used to measure deformation Clear height of waJI between beams,
capacity, Figs. 2-3, 5-1, 6-1, 7-1, 8-1 Eqs. 5-33, 5-35
Actual eccentricity, ft (mm), measured in Distance from inside of compression tlange
plan between the center of mass of the Lo inside ol' tensionflange, Eq. 5-7
structure aboye the isolation interface and Heighl of member along which deforrna
the center of rigidity of the isolation sys tions are measured, Chapter 6
tem, plus accidental eccenlricity, fL (mm), Overall thickness 01' member, in., Eq. 6-4
taken as 5% 01' the maximum building Heighl 01' a column, pilaster, or wall,
dimension perpendicular lo Lhe direction of ChapLer 7
force under consíderation, Eqs. 9-6, 9-7 Shear wall heighl, Eqs. 8-1, 8-2
Foundalion embedmenl deplh, fl, Average roof elevalion of struclure, relalive
Eqs. 4-12, 4-14, Fig. 4-8 10 grade elevation, Eq. 11-3
en Nail deformalion al yield load per nail for Effeclive struClure heighl, Eq. 4-14,
wood slrucLural panel sheathing, Eqs. 8-2, Fig.4-8
8-4,8-5 he Assumed web depLh for stability, Chapler 5
j; Fundamental frequency of Ihe building, Gross cross-sectíonal dimension of column
Eq.9-24 core measured in the direclion 01' joim
la Axial compressíve slress due to gravíty shear, in., Chapler 6
loads specitied in Eqs. 3-2, 7-5 h"", Heighl of column belween beam cenler-
Le Expectcd vertical compressive stress, lines, Eq. 7-7
Chapler 7 h"Jf Effeclive heighl of wall or wall pier com
j~ Compressive strength of concrete, psi, ponent<; under consideralion, Eqs. 7-3, 7-5
Eqs. 6-4, 6-5 h¡ Height from the base of a building to tloor
f'e Compressive strength of concrete, psi, level i, Eqs. 3-12, 4-14, 9-9
Table 6-5 hin! Height of infill panel, Eqs. 7-7, 7-10, 7-12,
j~ Lower-bound masonry compressive 7-13,7-14
strength, Eqs. 7-5, 7-6,7-14 h" Height lo mof leve), n, Eq. 3-6
j;ne Expecled compressíve slrength 01' masonry hp Heighl of rectangular glass, Eq. 11-9
as delermined in Section 7.2.2.3 hw Height of wall or segmenl 01' waJl consid
fpe Average compressive stress in concrete due ercd in the direction of shear force,
to effective prestress force only (afler Chapter 6
allowance for all preslress )osses), hx Heighl fmm base 10 tloor leve) x, fI,
Chapler 6 Eqs. 3-11,9-9
¡; Stress in reinforcemenl, psi, Eqs. 6-2, 6-3 k Exponent used for determining the vertical
j; Lower-bound masonry lensile strength, dislribution 01' lateral forces, Equation 3-11
Chapler 7 Coefficient uscd for calculalíon of column
L Expecled masonry tlexural tensile slrenglh shear strenglh, Chapter 6
as determined in Section 7.2.2.5 k¡ Distance from the center oí" lhe split tee
J~'ie Expected shear slrenglh of masonry infill, stem lo Ihe edge of the split tee tlange
Eq.7-8 tillel, Eq. 5-25
363
SEISMIC REHABILlTATION OF EXISTING BUILDINGS
keff Eftective stiffness of an isolator unit, as q Vertical bearing pressure, Eq. 4-8
...
prescribed by Eq. 9-12, or an energy dissi quilo". Allowable bearing pressure specitied in the
pation unit, as prescribed by Eq. 9-23 or available design documents for the design
9-38 of shallow foundations for gravity loads
kl¡ Horizontal seismic coefticient in soil acting (dead plus live loads), Eq. 4-1
on retaining wall, Eq. 4-16 q" Expected bearing capacity 01' shallow foun
k" Winkler spring stiffness in overturning dalion expressed in load per unÍl area,
(rotation) 1'or pile gl'OUp, expressed as Eqs. 4-1,4-3,4-7, 4-8
moment/unit rotal ion, Eq. 4-10 qin Expected transverse strength of an inl1l1
k,,. Winkler spring stiffness in vertical direc panel, Eq. 7-14
lion, expressed as force/unit r Governing radius of gyration. Eq. 5-36
displacement/unit area, Eq. 4-6 ro Equivalent 1'oundation radius fOl' rotation,
Pile gl'OUp axial spring stiffness expressed Eq. 4-14, Fig. 4-8
as force/unir displacement, Eq. 4-9 rin! Diagonallength 01' in ti JI panel, Eq. 7-7
kv Shear buckling coefticient, Chapler 5 T, Equivalent foundation radius rOl' transla
k,." Axial sti1'fness of n-th pile in apile group, tíon, Eq. 4-14, Fig. 4-8
Eq.4-10 s Spacing 01' shear Teinforcement, Eq. 6-4
lb Length of beam, Eq. 5-1 s·, Minimum separation distance between
Provided lenglh of straight development, adjacent buildings al level i. Eq. 2-8
lap splice, or standard hook, in., Eq. 6-2 Su Undrained shear slrenglh of soil, lbs/fL2,
l¡Jeff Assumed distance to intill slrut reaction Chapte.. I
point for beams, Eq. 7-11 Sil Average value of the undrained soil shear
( Length of column, Eqs. 5-2, 5-36 strenglh in the upper 100 ft oí' soil, ca1cu
leeu Assumed distance to inlm strut Teaction lated in accordance with Eq. 1-6, Ibs/tV
poinl for columns, Eq. 7-9 t Thickness of eontinuity plate, Chapter 5
I,¡ Required lenglh 01' development for a EfTective thickness 01' wood slruclural panel
straight bar, in., Eq. 6-2 or plywood for shear, in., Eqs. 8-2, 8-4, 8-5
le Length 01' embedment of reinforcement, in., t" Thiekness 01' angle, Eqs. 5-21, 5-23
Eq.6-3 t lTj Thickness of beam nange, Chapter 5
1[> Length 01' plastic hinge used for calculation IbJ'" Thickness 01' beam wcb, Chapter 5
of inelastic deformation capacity, in., Eq. 6-6 tcl Thickness of column f1ange, Chapler 5
lw Length of entire wall or a segmenl of wall tel!' Thickness of column web, Chapter 5
considered in lhe direction of shear force, tr Thickness 01' tlange, Eqs. 5-25, 5-29
in., Chapler 6 till1 Thickness 01' inlíll panel, Eqs. 7-7, 7-13,
m Componenl demand modificalion factor 10 7-14
account ror expecled ductilily assoeiated tI' Thickness of panel zone including doubler
with this action al lhe selected Slruclural plates, Eq. 5-5
Performance Level. m-factors are specified Thickness 01' tlange plate, Eq. 5-26
in Chapters 4 lhrough 8, Eqs. 3-20, 5-9 t, Thickness 01' split tec stem, Eqs. 5-24, 5-25
me Eflective m-factor, Eq. 5-9 1,..; Thickness 01' web, Eqs. 5-7, 5-2'-)
m, Value of m-factor for the column in ten Thickness 01' plate wall, Eq. 5-33
sion, Eq. 5-13 Thickness 01' walI web, in., Chapler 6
mx Value of m for bending about the x-axis of tz Thickness of panel zone (doubler plales not
a member, Eqs. 5-10, 5-11, 5-13,6-1 necessarily included), Chapter 5
my Value of m for bending about lhe y-axis 01' v Maximum shear in the direclion under con
a member, Eqs. 5-10, 5-1 1, 5- 13, 6-1 sideration, Eq. 8-5
n Total number 01' stories in lhe vertical seis VmL Lower-bound masonry shear slrength,
mic framing, Eq. C3-2 Eqs. 7-1,7-4
Shear wave velocity reduction factor, VIL Lower-bound bed-joint shear slrength
Eq.4-12 delined as lower 20lh percentile of V W
PD+L Gravity compressive stress al the lest loca Eq.7-1
tion considering actual dead plus live loads VIO Bcd-joint shear stress from single test,
in place al time of testing, Eq. 7-2 Eq.7-2
364
.
ASCF/SEI 41-06
365
..
SEISMIC REHABILlTATION OP EXISTING BUILDlNGS
¡!F-D!min Sum, for all isolator uníts, of the mínimum Etleclive damping of lhe isolation syslem
absolute value of force, kips (kN), at a al the maximum displacement, as pre
negative displacement equal to DD, scribed by Eq. 9-19
Eq.9-15 m-lh mode damping in the building frame,
¡!F-Mlmax Sum, for aH isolator unils, of lhe maximum Eq.9-33
absolute value of force, kíps (kN), al a Unit weight, weightlunit volume (Ibs/tP or
N/m), Eq. 4-4
negalive displacement equal to D M ,
Eq.9-16 Coeflicienl for calculation of joinl shear
¡IF-Mlmín Sum, for an isolalOr units, of the minimum slrength, Eq. 6-5
absolute value of force, kips (kN), at a 'Yf Fraction of unbalanced moment transferred
negative dísplacemem equal lo DM , by flexure al sla~olumn connections,
Eq.9-17 Chapter 6
Factor equallO 0.5 for fixed-free can Total unit weight of soil, Eqs. 4-5, 4-16
tilevered shear wall, or 1.0 for fhed-fixed Unit weight of water, Eq. 4-5
wall pier, Eqs. 7-3, 7-5 Displacement al floor i, Eqs. 9-26,9-27.
Velocity exponent for a fluid-viscous Displacement at floor i due to lateral load
device, Eq. 9-25 F¡. Eqs. C3-2
al Positive post-yield slope ratio equallo the m-lh mode horizontal displacemenl at floor
positíve posl-yield stiffness divided by the i, Eq. 9-34
effective sti ffness, Fig. 3-], Chapter 3 m-lh relalive displacement belween lhe
az Negative post-yield slope ralio equallo the ends of device j along its axis, Eq. 9-35
negalive post-yield stiffness divided by the Relalive displacement belween the ends of
effective sliITness, Fig. 3-1, Eq. 3-17 energy dissipaling device j along the axis
ae EfTective negalive post-yield slope ratio of the device, Eqs. 9-29, 9-37
equallo the effective post-yield negative Target displacement, Fig. 3-1
stiffness divided by the effective stitTness, Defleclion at level x of Building A, deter
Eqs. 3-]6, 3-17 mined by an elastic analysis as defined in
IXp-A Negative slope ratio caused by P-d effects, Chapter 3, Eqs. 11-7, ] 1-8
Fig. 3-1, Eq. 3-17 Deflection at level x of Building B, deter
f3 Modal damping ratio, Chapter 1, Eqs. l 13, mined by an elastic analysis as detined in
4-13 Chapter 3, Eq. 11-8
Factor to adjusl fundamental period of the Dellection at leve] y of Building A, deler
building, Eq. 3-6 mined by an elastic analysis as detined in
Ratio of expected frame strength, vf,., to Chapter 3, Eq. 11-7
expected intill strength, Vine' Chapter 7 Displacement multiplier, greater than 1.0,
Damping ¡nherent in the building frame lo account for the etl'ects of torsion.
(typically equal to 0.05), Eqs. 9-26, 9-28, Eq.3-1
() Generalized deformation, radians,
9-30
Effective damping ratio of the Figs. 5-1, 6-]
structure-foundation system, Eq. 4-13 Angle between intill diagonal and horizon
Effective damping of the isolation system tal axis, tan (J híniLinj' radians, Eq. 7-7
at the design displacement, as prescribed Angle between lower edge of compressive
by Eq. 9-18 strut and beam, radians, Eqs. 7-11, 7-12
Effeclive damping of isolator unit, as pre Angle between lower edge ol' compressive
scribed by Eq. 9-13, or an energy dissipa strul and column, radians, Eqs. 7-9,
tion unit, as prescribed by Eq. 9-39; also 7-10
used for the elIeclive damping 01" the build Story drift ratio, radians, Chapter S
ing, as prescribed by Eqs. 9-26, 9-28, 9-30, Angle of inc1ination of energy dissipation
9-31,9-32,9-36 device, Eq. 9-30
Etlective damping in m-lh mode prescribed Generalized yield deformation, radians,
by Eq. 9-33 Fig.5-1
Foundation-soil interaction damping ratio, Yield rotation, radians, Eqs. 5-1, 5-2, 5-30,
Eq. 4-13, 4-14, Fig. 4-8 5-35,6-6
366
ASeE/SEl 41 ~06
367
SElSMIC REHABILlTATION OF EXISTING BUILDlNGS
368
ASeE/SEI 41-06
Bearing Wall: A walllhal supporls gravily loads for adminislering and enl'orcing the provisions of a
of al leasl 200 lbs/lineal ft from f100rs andlor roofs. legally adopted building codeo
Bed Joint: The horizonlallayer of mortar on Coefficient ofVariation: For a sample ol' data,
which a masonry unit is laido the ratio ol' the standard deviation for the sample to the
Boundary Component: A slruclural componenl mean value for the sample.
al the boundary of a shear walI or a diaphragm or al an Collar Joint: Vertical longitudinal joint belween
edge of an opening in a shear wall or a diaphragm lhal wythes of masonry or belwecn masonry wylhe and
possesses tensile and/or compressive slrength to trans back-up construction; can be tilled with mortar or grout.
fer lateral forces lo the laleral-force-resisting syslem. Collector: See Drag Strut.
Braced Frame: A verlicallaleral-force-resístíng Cotumn (or Beam) Jacketing: A rehabililation
elemenl consisting of vertical, horiwntal, and diagonal method in which a concrete column or beam is
componenls joined by concentric or eccenlric encased in a steel or concrele "jacket" lo strenglhen
connections. andlor repair lhe member by confining lhe concrete.
BSE- t: Basic Safely Earlhquake-l, laken as lhe Component: A part of an architeclural, mechani
lesser of lhe ground shaking for a 1O%/50-year earth cal, electrical, or slruclural system of a building.
quake or Iwo-thirds of lhe BSE-2 al a site. Component, Flexible: A component, including
BSE-2: Basic Safely Earlhquake-2, taken as Ihe i!s attachments, having a fundamental period greater
ground shaking based on Ihe Maximum Considered than 0.06 seco
Earlhquake (MCE) al a site. Component, Nonstructural: An architeclural,
BSO: Basic Safety Objeclive is a Rehabilitatíon mechanical, or electricaI component ol' a building that
Objective that achieves lhe dual rehabilitation goal s of is permanently inslalled in, or is an integral parl ol', a
lhe Life Safely Building Performance Level ror the building system.
BSE-I Earthquake Hazard Level and the Collapse Component, Primary: A slmclural component
Prevention Building Performance Level for the BSE-2 that is required lO resíst seismic 1'orces in order for the
Earthquake Hazard Leve!. structure to achieve lhe selected performance leve!.
Building Occupancy: The purpose for which a Component, Rigid: A component, including ílS
building, or part (hereof, is used or in tended to be attachmenls, having a fundamental period less than or
used, designated in accordance with lhe applicable equaJ lo 0.06 seco
building codeo Component, Secondary: A structural componenl
Building Performance Level: A Iimiting damage that is not required lo resisl seismic force s in order for
stale for a building, considering structural and non lhe slructure to achíeve lhe selected performance leveJ.
slructural components, used in lhe definition of Component, Structural: A component of a
Rehabilitation Objectives. building Ihat provides gravity- or lateral-load resis
Cast Iron: A hard, brittle, nonmalleable iron tance as par! of a continuous load path 10 the founda
carbon alloy containing 2.0% lo 4.5% carbono Shapes lion, including beams, columns, slabs, braces, walls,
are obtained by reducing iron ore in a blast furnace, waIl piers, coupling beams, and connections; desig
forming il into bars (or pigs), and remelting and cast nated as primary or secondary.
ing il into its tinal formo Composite Masonry Wall: Multi-wythe masonry
Cavity Wall: A masonry wall wilh an ajr space wall acting with composite aClion.
between wylhes. Composite Panel: A structuraI panel composed
Chord: See Diaphragm Chord. 01' thín wood strands or wafers bonded together with
Clay Tile Masonry: Masonry conslructed wilh exterior adhesive.
hollow units made 01' c1ay lile. ConcentrÍc Braced Frame: Braced trame ele
Clay-Unit Masonry: Masonry constructed wilh menl in which component worklines inlersecl al a sin
sol id, cored, or holJow units made of c1ay; can be gle point or al muItiple points such that Ihe dislance
ungrouted or grouted. belween íntersecling worklines (or eccenlricity) is less
Closed Stirrups or Ties: Transverse reinforce lhan or equal lo Ihe width of Ihe smallest component
ment defined in Chapter 7 of ACI 318 (ACI 2002) connecled al lhe joint.
consisting of standard stirrups or lies with 90-degree Concrete Masonry: Masonry conslrucled with
hooks and lap splices in a pauern that endoses longi solid or hollow units made ol' concrete; can be
tudinal reinforcemenl. ungrouled or grouted.
Code Official: The individual representing a local Condition of Service: The environmenl lo which
jurisdiclion who is legally ¡;harged with responsibility lhe slruclure will be subjecled.
369
SEISM1C REHABILlTAT10N OF EXISTING BU1LDlNGS
Connection: A link thal transmits actions from Demand: The amount of force 01' deformalion
one component or element to another component or imposed on an elemenl 01' component.
elemenl, calegorized by type of action (momenl, shear, Design Displacement: The design earthquake
or axial). displacement of an isolation 01' energy dissipation sys
Connection Hardware: Proprielary or cuslom tem, or elements lhereof, excluding additional dis
fabricaled body of a componenl Ihal is used lo link placemem due lo actual and accidental lorsion.
wood componenls. Design Earthquake: A user-specilied earthquake
Connectors: Nails, screws, lags, bohs, split rings, for the design of a building having ground shaking cri
shear plales, headed sluds, and we1ds used lo link leria descl'ibed in Chapler l.
components lo other components. Design Resistance (Force or Moment, as appro
Contents: Movable items wilhin the building priate): Resislance provided by member or connec
introduced by lhe owner or occupants, weíghing tion; the product of adjusted resistance, the resistance
400 lbs or more. faclor, and time-effecl factor.
Continuity Plates: CoJumn stiffeners allhe 10p Diagonal Bracing: Inclined components designcd
and boltom 01' a panel zone. to carry axial load, enabling a structural frame lo act
Control Node: A nodc located al Ihe cenler of as a truss lo resist laleral forces.
mass al lhe roof 01' a building used in (he Nonlinear Diaphragm: A horizontal (01' nearly horizonlal)
I
Stalic Procedure (NSP) lO measure lhe effecls 01' earth slruclural e1ement used to transfer inertial lateral
quake shaking on a building. fOl'ces lo vertical elements 01' the lateral-torce-resisting
Corrective Measure: Any modificalion of a com system.
ponenl or element, or the struclure as a whole, implc Diaphragm Chord: A boundary component per
mented lo improve building performance. pendicular lO lhe applied load (hal is provided lo resist
Coupling Beam: A component lhal lies or tensíon or compressíon due to lhe díaphragm momen!.
couples adjacenl shear walls acting in the same Diaphragm ColJector: A componenl parallel lo
plane. _ lhe applied load lhat is provided lo Iransfcr laleral
Cripple Studs: Shorl studs belween a header and forces in the diaphragm lo vertical elcments 01' lhe
lop plale al openings in waIl framing, or studs belween laleral-force-resisting system.
the base and si1l of an opening. Diaphragm Ratio: See Aspect Ratio.
Cripple Wall: Short wall between Ihe foundalÍon Diaphragm Strut: See Diaphragm Tie.
and first 1100r framing. Diaphragm Tie: A component paralleJ to the
Critical Actiom TIle component aClion lhal applied load lhal ís provided lo lransfer wall anchor
reaches ils elaslic limil at lhe lowest leve) of laleral age or diaphragm inertial forces within or across the
detlcclion or loading of Ihe SlrUClure. diaphragm. Also caBed diaphragm strut.
Cross Tie: A componenl Ihal spans Ihe width of DitTerentiaJ Compaction: An eanhquake-induced
lhe diaphragm and delivers out-of-plane wall torces process in which soils become more compact and set
over the ful1 depth 01' lhe diaphragm. tle in a nonuniform manner across asile.
Decay: Decomposition of wood caused by action Dimensioned Lumber: Lumber from nominal 2
of wood-deslroying 1'ungi. The lerm "dry rol" is used through 4 inches thick and nominal 2 or more inches
inlerchangeably with decay. wide.
Decking: Solid sawn lumber or glue-Iaminaled Displacement-Dependel1t Energy Dissipation
decking, nominally 2 lo 4 in. thick and 4 or more in. Devices: Devices having mechanical properties such
wide. Decking shalI be longue-and-groove or con thal Ihe force in lhe device is related to lhe reJalive
neCled at longitudinal joints wilh nails or metal clips. displacement in lhe device.
Deep Foundation: Driven piles made of stee1, Displacement Restraint System: Colleclion 01'
concrele, or wood, or cast-in-place concrele piers or structural components and elements that limil lateral
drilled shafts of concrete. displacement of seismically-iso)ated buildings during
Deformability: The ratio 01' lhe ultimale deforma the BSE-2.
lion lo lhe Iimil deformalion. Dowel-Bearing Strength: The maximum com
Deformation-Sensitive Nonstructural pression strength oí' wood or wood-bascd products
Component: A nonstruclural component Ihat is when subjected to bearing by a steel dowel or bolt of
sensitive to deformalion imposed by lhe drift or specitic diameler.
deformalion of the slructure, including detlection Dowel-Type Fastel1ers: Bolts, lag screws, wood
or deformation of diaphragms. screws, nails. and spikes.
370
ASCElSEl41-06
Dressed Size: The dimensions of lumber after Foundation System: An assembly of structural
surfacing with a planing machi ne. components, located at the soil-struclure interface,
Dry Rot: See Decay. Ihat transfer loads from the superstructure into the sup
Dry Service: Structures wherein the maximum porting soil.
equilibrium moisture content does not exceed 19%. Fundamental Perlod: The longest natural period
Earlhquake Hazard Level: Ground shaking of the building in the direction under consideration.
demands of specitied severity, developed on either a Gauge or Row Spacing: The center-to-center dis
probabilistic or deterministic basis. tance between fastener rows or gauge lines.
Eccentrlc Braced Frame: Braced frame element Glulam Beam: Shortened term for glue
in which component worklines do not intersect at a laminated beam, which is a wood-based component
single point and the distance between the interseeting made up of layers of wood bonded with adhesive.
worklines (or eccentrieity) exceeds the width of the Good Condition: Masonry found during eondi
smallest component connecting at the joint. tion assessment to have mortar and units intact and no
Edge Distance: The distance from the edge of the visible cracking.
member to the center of the nearest fastener. Grade: The c1assification of lumber with regard
EtTective Damping: The value of equivalent vis lo slrength and utility, in accordance with the grading
cous damping corresponding to the energy dissipated rules of an approved agency.
by the building, or element thereof, during a cycle of Grading Rules: Systematic and standardized cri
response. teria for rating the quality of wood products.
EtTective Stiffness: The value of the lateral force Gypsum Wallboard or Drywall: An interior wall
in the building, or an element thereof, divided by the surface sheathing material; can sometimes be consid
corresponding lateral displacement. ered for resistíng lateral forces.
EtTective Void Ratio: Ratio of collar joint area Head Joint: Vertical mortar joint placed between
without mortar to the total area of the collar joint. masonry units in the same wythe.
Element: An assembly of slructural componenls High-Deformability Component: A component
that act together in resisting forces, incJuding gravily whose deformability is not less than 3.5 when subjected
frames, moment-resisting frames, braced frames, shear to four fuJly reversed cycles al the limít deformation.
walls, and diaphragms. Hollow Masonry Unit: A masonry unit with net
Energy Dissipation Device: Non-gravity-Ioad cross-sectional area in every plane parallel to the beat
supporting element designed to dissipate energy in a ing surface less than 75% of the gross cross-sectional
stable manner during repeated cycles of earthquake area in (he same planeo
demando Hoops: Transverse reinforcement defined in
Energy Dissipation System: Complete colIection Chapter 21 of ACI 318 (ACI 2002) consisting of
of all energy dissipation devices, their supporting closed tíes with 135-degree hooks embedded into the
framing, and connections. core and no lap spliees.
Expected Strength: The mean value of resislance Infill: A panel of masonry placed within a steel or
of a component at the deformation level anticipated concrete frame. Panel s separated from the surrounding
for a population of similar components, incJuding con frame by a gap are termed "isolated infills." Panels
sideration of the variability in material strength as wells that are in full contact with a frame around its fulI
as strain-hardening and plastic section development perimeter are tenned "shear infills."
Fair Condition: Masonry found during condition In-Plane Wall: See Shear Wall.
assessment to have mortar and units intact but with Isolation Interface: The boundary between the
minor cracking. upper portion of the structure (superstructure), which
Fault: Plane or zone along which earth materials ís isolated, and the lower portion of the structure,
on opposite sides have moved differentially in which is assumed to move rigidly with the ground.
response to tectonic forces. Isolation System: The coIlection of structural
Flexible Connection: A link between components components that ¡neludes all individual isolator units,
that permits rotational andlor translational movement all structural components that transfer force between
without degradation of performance, including universal components of the isolation system, and all connec
joints, bellows expansion joints, and tlexible metal hose. tions to other structural components. The isolation
Flexible Diaphragm: A diaphragm with horizon system al so ineludes the wind-restraint system, if such
tal deformation along its length more than twice the a syslem is used to meet the design requirements of
average story drift. Ihis section.
371
SElSMIC REHABILlTATION OF EXISTING BUILDINGS
Isolator Unit: A horizontally t1exible and verti are generated in the structure to the foundation and,
calIy stiff structural component of the isolation system ultimately, the supporting soil.
that permits large lateral deformations under seismic Load Sharing: The load redistribution mecha
load. An isolator unit shall be used either as part of or nism among paralIel components constrained to
in addition to the weight-supporting system of the detlcct together.
building. Load/Slip Constant: The ratio of the applied
Joint: An area where ends, surfaces, or edges of load to a connection and the resulting lateral deforma
two or more componenls are attached; categorized by tion of the connection in the direction of the applied
type oí" fastener or weld used and method of force load.
transfer. Low-Deformability Component: A component
King Stud: Full-height studs adjacent to openings whose detormability is 1.5 or less.
that provide out-of-plane stability to cripple studs at Lower-Bound Strength: The mean minus one
openings. standard deviation of the yield strengths, Q}, for a
Knee Joint: A joint that in the direction of fram population of similar components.
ing has one column and one beam. Lumber: The product 01' the sawmill and planing
Landslide: A down-slope mass movement of mili, usually not further manufactured other than by
earth resulting from any cause. sawing, resawing, passing lengthwise through a stan
Lateral-Force-Resisting System: Those elements dard planing machine, crosscutting lo lenglh, and
of the structure that provide its basic lateral strength matching.
and stiffness. Masonry: The assemblage of masonry units, mor
Light Framing: Repetilive framing with small, tar, and possibly graut and/or reínforcement; c1assifíed
uniformly spaced members. with respecl 10 the Iype 01' masonry unit, including
Lightweight Concrete: Structural concrete that clay-unít masonry, concrete masonry, or hollow-c1ay
has an air-dry unit weight not exceeding 115 pcf. tile masonry.
Limit Deformation: Two times the initial defor Mat-Formed Panel: A structural panel manufac
mation that occurs at a load equal lo 40% of the maxi tu red in a mat-tormed process including oriented
mum strength. strand board and waferboard.
Limited-DeformabiUty Component: A compo Maximum Considered Earthquake (MCE): An
nent that is neither a low-deformability nor a high extreme earthquake hazard level delined by MCE
det{)fmability component. maps which are based on a combination of mean
Link Beam: A component between points of 2%150-year probabilistic spectra and 150% 01' median
eccentrically connected members in an eccentric deterministic spectra at a given site.
braced frame element. Maximum Displacement: The maximum earth
Link Intermediate Web Stiffeners: Vertical web quake dísplacement 01' an isolation or energy dissipa
stiffeners placed within a link. tion system, or elements thereo1', cxc\uding additional
Link Rotation Angle: Angle of plastic rotation displacement due to actual or accidental !Orsion.
between the link and the beam outside of the link, Mean Returo Period: The average period of
derived using the specified base shear, V. lime, in years, betwecn lhe expected occurrences 01' an
Liquefaction: An earthquake-induced process in earthquake of specilied severity.
which saturated, loose, granular soils lose shear Model Building Type: One of the common build
strength and liquel'y as a result ol' increase in pore ing types Jistcd and described in Table 10-2.
water pressure during earthquake shaking. Moisture Content: The weight of the water in
Load and Resistance Factor Design: A method wood expressed as a percentage of the weight of the
01' proportioning structural components (members, oven-dried wood.
connectors, connections, and assemblages) using load Moment Frame: A building framc systcm in
factors and strength reduction factors such that no which seismic shear forces are resisted by shear and
applicable limit state is exceeded when the structure is tlexure in members and joints ol' the framc.
subjected to all design load combinations. Narrow Wood Shear Wall: Wood shear walls
Load Duration: The period of conlinuous appli Wilh an aspect ratio (height-Io-width) greater than 2: ].
cation ol' a given load, or the cumulative period of inter Nominal Size: The approximate rough-sawn com
miUent applications of load. See Time-Effect Factor. mercial size by which lumber products are known and
Load Path: A path through which seismic forces sold in the market. Actual rough-sawn sizes vary 1'rom
are delivered from the point at which inertial torces nominal. Re1'ercnce to standards or grade rules is
372
ASCFJSEI 41-06
required to determine nominal to actual finished size Particleboard: A panel manufactured from small
relationships, which have changed over time. pieces of wood, hemp, and tlax, bonded with synthetic
Nominal Strengtb: The capacily of a slructure or or organic binders, and pressed inlo nat sheets.
componen( to resist the effects of loads, as determined Perforated Wall or In611 Panel: A walI or panel
by (l) computations using specified material strengths not meeting the requirements for a solid waIl or intill
and dimensions, and formulas derived from accepted panel.
principies of structural mechanics; 01' (2) fieId tests or Pitcb or Spacing: The longitudinal centel'-to
Iaboratory tests of scaled models, allowing fol' model cenler distance between any two conseculive holes or
ing effects and differences between laboratory and fasteners in a row.
field conditions. Platform Framing: ConstruclÍon method in
Nonbearing Wall: A wall that SUppOrlS gravity which stud walls are constructed one floor al a Lime,
loads less than 200 lbs/lineal f1. with a tloor or roof joiSI bearing on top of the wall
Noncompact Member: A steel section that has framing at each level.
width-lo-lhickness ratios exceeding the limiting values Ply: A single sheet of veneer, or several slrips laid
for compactness specilied in Load and Resistance with adjoining edges Ihal form one veneer lamina in a
Factor Desigll Specijication for Structural Steel glued plywood panel.
Buildings (LRFD)(AISC 1999). Plywood: A structural panel composed oí' plies of
Noncomposite Masonry Wall: Multi-wythe wood veneer arranged in cross-aligned layers bonded
masonry wall acting without composite action. with adhesive cured upon application of heat and
Nonstructural Component: See Component, pressure.
Nonstructural. Pole: A round timber of any size or length, usu
Nonstructural Performance Level: A limiting alIy used with Ihe larger end in the ground.
damage stale for nonstructural building components Pole Structure: A structure framed wilh generally
used lO define Rehabilitation Objeclives. round, continuous poi es that provide Ihe primary verti
Ordinary Moment Frame: A moment frame sys cal frame and lateral-Ioad-resisting system.
tem that meets the requirements for Ordinary Moment Poor CondUion: Masonry found during condition
Frames as defined in seismic provisions for new con assessmenl lo have degraded mortar, degraded
struction in AISC 341, Seismic Provisions. Chapter 5 masonry units, or significant cracking.
(AISC 2002) . Pounding: The action of two adjacent buildings
Oriented Strand Board: A structural panel com coming Ínlo contacl with each other during earthquake
posed of thin, elongated wood strands with surface excitalion as a resull of their close proximity and dif
layers arranged in the long panel direction and core ferences in dynamíc response characteristics.
layers arranged in the cross-panel direction. Preservative: A chemical that, when suitably
Out-of-Plane Wall: A wall (hat resists lateral applied to wood, makes Ihe wood resistant to auack by
forces applied normal lO its plane. fungí, insects, marine borers, or weather conditions.
Overtuming: Behavior that results when the Pressure-Preservative-Treated Wood: Wood
moment produced at the base ol' verticallateral-force products pressure-trealed by an approved process and
resisting elements is larger than the resistance pro preservalive.
vided by the building weight and Ihe foundation resist Primary Component: See Component,
ance to uplif1. Primary.
Panel: A sheet-type wood product. Primary (Strong) Panel Axis: The direction that
Panel Rigidity or Stiffness: The in-plane shear coincides with the length of the panel.
rigidity of a panel; the product of panel thickness and Probability of Exceedance: The chance,
modulus of rigidity. expressed as a percentage (%). that a more severe
Panel Sbear: Shear stress acting through the event will occur within a specitied period, expressed in
panel thickness. number of years.
Panel Zone: Area of a column at a beam-to Puncbed Metal Plate: A light sleeI pIale fastener
column connection delineated by beam and column with punched teeth of various shapes and configura
tlanges. tions that are pressed into wood members (() effect
Parapet: Portions of a wall exlending above the force transfer.
rool' diaphragm. P-A EtTect: The secondary effect of vertical loads
Partially Grouted Masonry Wall: A masonry and lateral defleclion on the shears and moments in
wall containing grout in sorne of the cells. various components of a struclure.
373
SEJSMJC REHABJUTATION OF EXISTING BUILDJNGS
Redundancy: The quality of having alternative Row oí Fasteners: Two or more fasteners aligned
load paths in a structure by which lateral force s can be with Ihe direction of load.
transferred, allowing the structure to remain slable fol Running Bond: A patlern 01' masonry where lhe
lowing the 1'ailure of any single element. head joints are staggered between adjacent courses by
Re-Entrant Corner: Plan irregularity in a at least one-quarter of lhe length of a masonry uní!.
diaphragm, such as an extending wing, plan inset, or Scragging: The process of subjecting an elas
E-, T-, X-, or L-shaped contiguration, where large ten tomeric bearing to one or more cycles of large
sile and compressive 1'orces can develop. amplitude displacement.
Rehabilitation Measures: Modifications to exist Seasoned Lumber: Lumber that has been dried
ing components, or installation of new components, either by open-air drying within lhe limiLs of moislure
that correct deficiencies identified in a seismic evalua contenls attainable by this method, or by controlled air
tion as part 01' a scheme to rehabilitate a building to drying.
achieve a selected Rehabilitation Objective. Secondary Component: See Component,
Rehabilitation Method: One or more procedures Secondary.
and strategies for improving the seismic performance Seismic Evaluation: An approved process or
oí' existíng buildings. methodology of evalualing deficiencies in a building
Rehabilitation Objective: One or more rehabili which prevent the building from achieving a selecled
tatíon goals, each goal consistíng 01' the selection of a Rchabilitalion Objective.
target Building Performance Level and an Earthquake ShalIow Foundation: lsolated or continuous
Hazard Level. spread footings or mats.
Rehabilitation Strategy: A technical approach Shear Wall: A wall that resists lateral torces
1'or developing rehabilitation measures for a building applied parallel with its plane. Also known as an
to improve seismic performance. in-plane wall.
Reinforced Masonry Wall: A masonry wall with Sheathing: Lumber or panel products Ihal are
the following mínimum amounts of vertical and hori attached to parallel framing members, typically form
zontal reinforcement: vertical reinforcement 01' at leasl ing wall, tloor, ceiling, or roof surfaces.
0.20 in. 2 in cross section at each corner or end, at each Short Captive Column: A column with a height
side of each opening, and at a maximum spacing of to-deplh ralio less than 75% of the nominal height-to
4 ft throughout. Horizontal reinforcement of at least depth ratios of the typical columns al thal leve!.
0.20 in. 2 in cross section at the top oí' the wall, at the Shrinkage: Reduction in the dimensions of wood
top and bottom 01' walI openings, al structurally con due lo a decrease of moisture content.
nected rool' and lloor openings, and al a maximum Simplified NSP Analysis: A nonlinear slatic
spacíng of 10 fl. analysis in which only primary lateral-force-resisting
Repointing: A method of repairing cracked or elemenls are modeled, and component degradation is
deteriorating mortar joinls in which ¡he damaged or not explicitly mode!ed.
deteriorated mortar is removed and the joints are Simplified Rehabilitation Method: An approach
retilled wíth new mortar. applicable to certain types of buildings and Rehabilita
Required Member Resistance (or Required tion Objectives in which an analysis of the response of
Strength): Action on a component or connec lhe entire building lo earlhquake hazards is not required.
tion, determined by structural analysis, resulting Slip-Critical Joint: A bolted joint in which slip
from the 1'actored loads and the critical load resislance of the connection is required.
combinations. Solid Masonry Unit: A masonry unit with net
Resistance: The capacily of a structure, compo cross-sectional area in every plane parallel lo the bear
nent, or connection to resÍst the etIects of loads. ing surface equal to 75% 01' more of the gross cross
Resistance Factor: A reduction factor applied to sectional area in the same plane.
member resístance thal accounts for unavoidable devi Solid Wall or Solid Infill Panel: A wall or íntill
ations of the actual strength from the nominal value panel wilh openings nol exceeding 5% of the waIl sur
and for the manner and consequences of failure. face area. The maximum lenglh or height of an open
Rigid Diaphragm: A diaphragm with horizontal ing in a solid wall must not exceed \0% 01' the wall
deformalion along ils length less than half the average width or story heighl. Openings in a sol id wall or intill
slory drift as specitied in Section 3.2.4. panel must be located wÍlhin the middle 50% of a wall
Rough Lumber: Lumber as it comes from the length and slory height, and must not be comiguous
saw prior lo any dressing operation. with adjacent openings.
374
ASCElSEI41-06
Special Momeot Frame (SMF): A moment Target Displacemeot: An estimate of the maxi
trame system that meets the special requirements mum expecled displacemenl of Ihe roof oí" a building
for trames as defined in seismic provisions for new caIculaled for Ihe design earthquake.
construction. Tie: See Drag Strut.
Stack Bood: A placement of masonry units such Tie-Dowo: A device used lO resisl upli1'l of the
Lhat the head joinLs in successive courses are aligned chords of shear wal!s.
vertical!y. Tie-Down System: For seismically isolated struc
Stirt' Diapbragm: A diaphragm lhat is neílher tures, the collection of slfuclural connections, compo
flexible nor rígido nenlS, and elements thal provide reslraint against uplift
Storage Racks: Industrial pallet racks, movable of lhe structure aboye lhe isolalion system.
shelf racks, and stacker racks made of cold-formed or Timber: Lumber 01' nominal cross-section dimen
hOI-roUed struclural members. Does not inelude other sions of 5 in. or more.
types of racks such as drive-in and drive-through Time-Effect Factor: A factor applied lo adjusled
racks, cantilever wall-hung racks, portable racks, or resistance to accounl for effects of duration of load.
racks made of materials other than steel. (See Load Duration.)
Story: The portion of a structure belween the 10pS Total Design Displacement: The design eartb
of two successive finished tloor surfaces and, for the quake displacemem 01' an isolalion or energy dissipation
lOp-mosl story, from lhe top of the tloor finish to lhe system, or componenls thereof, incIuding additional
top of the roof structura) elemenl. displacement due lo aclual and accidenlal torsion.
Strengtb: The maximum axial force, shear Total Maximum Displacement: The maximum
force, or moment Lhal can be resisted by a earthquake displacement of an isolalion or energy dissi
componenl. pation syslem, or components lhereof, incIuding addi
Stress Resultant! The nel axial t'Orce, shear, or lional displacement due to actual and accidental torsioo.
bending moment imposed on a cross section of a Transverse Wall: A wall thal is oriented trans
slructural componen!. verse lo in-plane shear waIls, and resisls lateral fon::es
Strong-Back System: A secondary system, such applied normal lo ils planeo AIso known as an oul-of
as a frame, commonly used to provide oUl-of-plane plane wall.
support for an unreínforced or under-reínt'Orced Unreinforced Masonry (URM) Wall: A masoory
masonry wall. wall conlaining less lhan (he minimum amounts of
Strong Columo-Weak Beam: A connection reint'Orcemenl as defined for reinforced masonry walls;
where lhe capacity of the column in any momenl assumed 10 resiSl gravjly and laleralloads solely
frame joint is greater Ihan that of the beams, ensuring Ihrough resistance of the masonry materials.
inelastic action in lhe beams. V-Braced Frame: A concenlric braced frame
Strudural Component: See Component, (CBF) in which a pajr al' diagonal braces localed
Structural. eilher aboye or below a beam is connected to a single
Structural Peñormance Level: A límiting struc point wiLhin lhe clear beam span.
(ural damage state; used in the definilíon of Rehabili Velocity-Dependent Energy Dissipation
tation Objectives. Devices: Devices having mechanical characlerislics
Structural Peñormance Range: A range of such thal the force in the device is dependenl on lhe
slructural damage staLes; used in the detinition of relative velocily in the devÍce.
Rehabilitation Objectives. Veneer: A masonry wylhe lhat provides lhe exle
Structural System: An assemblage of struclural rior finish of a wall system and transfers oUl-of-plane
componenls Ihat are joined together 10 provide regular load directly lo a backing, but Ís nol considered lo add
inleraction or inlerdependence. load-resisling capacily lo the wall system.
Stud: Vertical framing member in interior or Vertical Irregularity: A disconlÍnuity of slrength,
exterior walls 01' a building. sliffness, geometry, or mass in one slory wÍlh respect
Subassembly: A porlion oí" an assembly. lo adjacenl stories.
Sub-Diapbragm: A portion 01' a larger diaphragm Waferboard: A non-veneered slruclural panel
used lo dislribule loads belween members. manufactured 1'rom 2- to 3-in. i1akes or wafers bonded
Systematic Rebabilitation Metbod: An approach together with a phenolic resin and pressed inlo sheet
lo rehabililation in which complele analysis of the panels.
response of Ihe building lo earthquake hazards is Wall Pier: Vertical porlion of a wall between Iwo
performed. horizonlally adjacent openings.
375
SEISMIC REHABILlTATION OF EXISTING BUlLDINGS
Wind-Restraint System: The collection of struc American Society of Civil Engineers (ASCE).
tural components that provides restraint of the seismic (2002). "Seismic evaluation of existing buildings."
isolated structure for wind loads; may be either an ASCE 3/, Reston, Va.
integral part 01' isolator units or a separate device. American Society 01' Civil Engineers (ASCE).
Wood Structural Panel: A wood-based panel (2005). "Minimum design loads for buildings and
produet bonded with an exterior adhesive, meeting the other structures." ASCE 7, Reston, Va.
requirements 01' PS 1-95 (NIST 1995) or PS 2-92 American Society of Mechanical Engineers
(NIST 1992), including plywood, oriented strand (ASME). (2000). "Safcty code for elevators and esca
board, waferboard, and composite panels. lalors." ASMEA/7./, New York.
Wrought lron: An easily welded or forged iron ASTM. (1996). "Standard test method ror splil
containing Iiule or no earbon. Inilially malleable, it ting tensile strength 01' cylindrical concrete speci
hardens quiekly when rapidly cooled. mens." ASTM C496-96, West Conshohocken, Pa.
Wythe: A continuous vertical section of a wall, ASTM. (1998). "Standard specification for com
one masonry unit in thickness. puting the reference resistance of wood-based materials
X-Braced Frame: A concentric braced frame and structural connections for load and resistance factor
(CBF) in which a pair of diagonal braces crosses near design." ASTM D5457-93, West Conshohocken, Pa.
!he mid-Iength of the braces. ASTM. (1999). "Standard test method for pene
Y-Braced Frame: An eccentric braced 1'rame tralÍon test and split-barrcl sampling of soils."
(EBF) in whieh the stem of the Y is the link of the ASTM D/586-99, West Conshohocken, Pa.
EBF system. ASTM. (2000). "Standard specitication
for fusion-bonded epoxy-coated pipe piles."
REFERENCES ASTM A972/A 972M-OO, West Conshohocken, Pa.
ASTM. (2000). "Standard test method 1'01'
American Concrete Institule (ACI). (200 1). measurement oí' masonry flexural bond strength."
"Acceptance eriteria 1'or momeO! frames based on ASTM CJ072-00A, West Conshohocken, Pa.
strueturallesting." ACI TI. 1-01, Dctroil. ASTM. (2000). "Standard test methods ror con
American Concrete Institute (ACI). (2002). dueting creep, creep-rupture, and stress-ruplure tests of
"Building code requirements for reinforced concrete." metallic malerials." ASTM E/39-00, Wcst
AC/318, Detroit. Conshohocken, Pa.
American Concrete Institute (ACI). (2002). ASTM. (200 1). "Standard specif1cation for high
Masonry Standards Joint Committee (MSJC). strength low-alloy steel shapes of structural quality,
"Building code requirements for masonry slructures." produced by quenching and self-tempering process
ACI 530/ASCE 5/TMS 402, Detroit; American Society (QST)." ASTM A913/A 913M-0/, West Conshohocken,
of Civil Engineers, Reston, Va; and The Masonry Pa.
SocielY, Boulder, Colo. ASTM. (2001). "Standard test method for com
American Concrete Institute (ACI). (2002). pressive strength of cylindrical concrete specimens."
Masonry Standards Joint Committee (MSJC), ASTM C39/C39M-0/, West Conshohocken, Pa.
"Specitication for masonry structures." AC/530.1/ ASTM. (2002). "Standard specitication for carbon
ASCE 6/TMS 602, Dctroit; American Society 01" Civil steel bolts and studs, 60,000 psi tensile strength."
Engineers, Reston, Va; and The Masonry Soeiety, ASTM A307-02, West Conshohocken, Pa.
Boulder, Colo. ASTM. (2002). "Standard specitication ror steel
American Institute 01" Sleel Construction (AISC). strand, uncoated seven-wire for prestressed concrete."
(1983). /ron alld steel beams /873-/952, Chicago. ASTM A4/6/A4/6M-02, West Conshohocken, Pa.
American Institute of Steel Construction (AISC). ASTM. (2002). "Standard specitication for
(1999). Load and resistance factor design specifica uncoated stress-relieved steel wire ror prestressed con
tionfor structural steel buildings (LRFD), Chicago. crete." ASTM A42//A42/M-02, West Conshohtx;ken, Pa.
American Institute of Steel Construction (AISC). ASTM. (2002). "Standard mcthods for eslablish
(2002). "Seismic provisions for slruclural steel build ing structural grades and relatcd allowable properties
ings." AISC 34/, Chicago. fol' visually graded lumber." ASTM D245-00, West
American Sociely of Civil Engineers (ASCE). Conshohocken, Pa.
(1996). "Standard for load and resistance factor design ASTM. (2002). "Standard test measures for tlex
(LRFD) for engineered wood construction." ASCE 16, ural bond strength of masonry." ASTM E5/8-02, West
AF&PNASCE Standard No. 16-95, NewYork. Conshohocken, Pa.
376
ASeE/SET 41-06
ASTM. (2003). "Standard specification for high Commentary." Prepared by the Building Seismic
strength low-alloy structural steel." ASTM A242/ Safety Council for the Federal Emergency
A242M-03, West Conshohocken, Pa. Management Agency. FEMA 368, Washington, D.C.
ASTM. (2003). "Standard test methods and defi Federal Emergency Management Agency
nitions for mechanical testing of steel products." (FEMA). (2004). "NEHRP recommended provisions
ASTM A370-03. West Conshohocken, Pa. for seismic regulations for new buildings and other
ASTM. (2003). "Standard specification for structures, 2003 Ed., Part ]: Provisions and Part 2:
deformed and plaín billet-steel bars for concrete rein Commentary." Prepared by the Building Seismic
forcemenL" ASTM A615/A615M-03A, West Safety Council for the Federal Emergency Manage
Conshohocken, Pa. ment Agency. FEMA 450, Washington, D.C.
ASTM. (2003). "Standard specification for International Conference of Building Officials
uncoated high-strength steel bar for prestressing con (lCBO). (1997). Uniform Building Code, Whittier,
crete." ASTM A722/A722M-98, West Conshohocken, Pa. Calif.
ASTM. (2003). "Standard test method for obtain International Code Council (ICC). (2003).
ing and testÍng drilled cores and sawed beams of con International Building eode, Falls Church, Va.
crete." ASTM e421e42M-03, West Conshohocken, Pa.
ASTM. (2003). "Standard test method for in situ
compressive stress within solid unit masonry estimated COMMENTARY REFERENCES
using flatjack measurements." ASTM ell96-03, West ABK Joint Venture (ABK). (1984). "Methodology
Conshohocken, Pa. for mitigadon of seismic hazards in existing unrein
ASTM. (2003). "Standard test method for in situ forced masonry buildings." (Topical Repon 08).
measurement of masonry deformability properties Agbabian & Associates, SB Barnes & Associates, and
using flatjack method." ASTM e1197-03, West Kariotis & Associates, El Segundo, Calif.
Conshohocken, Pa. AI-Hussaini, T., Zayas, V., and Constantinou,
ASTM. (2003). "Standard test methods for M. C. (1994). "Seismic isolation of muhi-story frame
strength of anchors in concrete and masonry ele structures using spherical sliding isolation systems."
ments." ASTM E488-96, West Conshohocken, Pa. Rep No. NeEER-94-0007, National Center for Earth
ASTM. (2004). "Standard specification for carbon quake Engineering Research, Stale University of New
structural steel." ASTM A36/A36M-04, West York al Buffalo.
Conshohocken, Pa. American Architeclural Manufacturers Asso
ASTM. (2004). "Standard specification for high ciation (AAMA). (2000). "Recommended static test
strength low-alloy columbium-vanadium structural method for evaluating curtain wall and storefront sys
steel." ASTM A572/A572M-04 (formerly A441/ tems subjected lo seismic and wind induced interstory
A441M), West Conshohocken, Pa. drift." AAMA 501.4, Schaumberg, IIl.
ASTM. (2004). "Standard specification for struc American Concrete Institute (ACI). (2001).
tural steel shapes." ASTM A992/A992M-04. West "Acceptance criteria for moment frames based on
Conshohocken, Pa. structural testing." AeITl.I-OI, Detroit.
American Welding Society (AWS). (2002). American Concrete Institute (ACI). (2002).
"Structural welding code-steel." AWS DI.I, Miami, "Building code requirements for reinforced concrete."
Fla. AC1318, Detroit.
American Welding Society (AWS). (1998). American Concrete Institute (ACI). (2002).
"Structural welding code-sheet steel." AWS D 1.3, Masonry Standards Joint CommiUee (MSJC),
Miami, Fla. "Specification for masonry structures." Ael 530.//
Federal Emergency Management Agency ASeE 6/FMS 602, Detroit; American Society of Civil
(FEMA). (1992). "NEHRP handbook of techniques Engineers, Reston, Va.; and The Masonry Society,
for the seismic rehabilitation of existing buildings." Boulder, Colo.
Prepared by the Building Seismic Safety Council American Forest & Paper Association (AF&PA).
for the Federal Emergency Management Agency. (J 996). "LRFD manual for engineered wood construc
FEMA 172, Washington, D.C. tion," including supplements and guidelines. AF&PA
Federal Emergency Management Agency LRFD, Washington, D.C.
(FEMA). (2001). "NEHRP recommended provisions American Foresl & Paper Association (AF&PA).
for seismic regulations for new buildings and other 1997, "Nalional design specification for wood con
structures, 2000 Ed., Part 1: Provisions and Part 2: struction." ANSI/AF&PA NDS-1997, Washington, D.C.
377
SEISMIC REHABILITATlON OF EXlSTING.BUILDINGS
American Forest & Paper Association (AF&PA). American Society of Mechanical Engineers
(2001). "ASD manual for engineered wood construc (ASME). (2000). "Gas transmission and distribution
tíon," íncluding supplements and guídelínes. AF&PA piping systems." ASME B31.8, New York.
ASD, Washington, D.C. American Society of Mechanical Engineers
American Petroleum Instítute (API). (1998). (ASME). (2000). "Building services piping."
"Welded steel tanks ror oil storage," 1Oth Ed. API 650, ASME B31.9, New York.
Washington, D.e. American Socíety oí' Mechanical Engineers
American Plywood Association (APA). (1995). (ASME). (2002), "Slurry transportation systems."
"Design capacities of APA performance rated structural ASME B31.11, NewYork.
use panels." Tech Note N375B, Tacoma, Wash. American Water Works Assocíation (AWWA).
American Plywood Association (APA). (1997). (1996). "Welded steel tanks for water storage." AWWA
Plywood design specification. Tacoma, Wash. DJOO, Denver, Colorado.
American Plywood Association (APA). (200 1). American Welding Society (AWS). (1998).
Diaphragms and shear wal/s designlconstruction "Structural welding code-sheet steel." AWS Dl,
guide (APA Form USO), Tacoma, Wash. Miami, Aa.
American Society 01' Civil Engineers (ASCE). Applied Technology Council (ATC). (1981).
(1996). "Standard for load and resislance factor design "Guidelines for the design of horizontal wood
(LRFD) for engineered wood construction." diaphragms." ATC-7, Redwood City, Calif.
AF&PAJASCE Standard No. 16-95, ASCE 16, Applied Technology Council (ATC). (1992).
NewYork. "Guidelines for seismic testing 01' components 01' steel
American Society of Civil Engineers (ASCE). structures." Repon No. ATC-24, Redwood City, Calif.
(1998). "Seismic analysis 01' safety-related nuclear Applied Technology Council (ATC). (1993).
structures." ASCE 4, Reston, Va. "Proceedings of the workshop to resolve seismic
American Society 01' Civil Engineers (ASCE). rehabilitation subissues-July 29 and 30, 1993; devel
(1999). "Standard guidelíne ror structúral condition opment of guidelines for seismic rehabilitation of
assessment 01' existing buildings." ASCE J1, buildings. phase 1: Issues identitication and resolu
NewYork. tion." ATC-28-2, Redwood City, Calif.
American Society of Civil Engineers (ASCE). Applied Technology Council (ATC). (1996).
(2002). "Seismic evaluation 01' existing buildings." "Seismic evaluation and retrotit of concrete buildings."
ASCE 31, Reston, Va. ATC-40, prepared by the Applied Technology Council,
American Society of Heating, Refrigerarion, and Redwood City, Calif. for the California Seismic Safety
Air Conditioning Engineers (ASHRAE). (1999). HA Commission (Report No. SSC 96-01).
practical guide to seismic restraint." ASHRAE RP-812, ASTM (1955) "Recommended Practice for
Atlanra. Conducting Long-Time High-Temperature Tension
American Society of Mechanical Engineers Test 01' Metallic Materials (Withdrawn 1959)",
(ASME). (2000). "Safety code 1'or elevators and esca ASTM E22-41, West Conshohocken, Pa.
lators." ASME A17.1, New York. ASTM. (1998). "Standard specification for COffi
American Society oí' Mechanical Engineers puting the reference resistance of wood-based materi
(ASME). (2000). "Code for pressure piping." als and structural connections for load and resistance
ASME B31, NewYork. factor design." ASTM D5457-93, West Conshohocken,
American Society of Mechanical Engineers Pa.
(ASME). (2001). "Power piping." ASME B31.1, ASTM. (2002). "Standard test method for pulse
NewYork. velocity through concrete." ASTM C597-02, West
American Society of Mechanical Engineers Conshohocken. Pa.
(ASME). (2002). "Process piping." ASME B31.3, ASTM. (2002). "Standard test method for
NewYork. diagonal tension (shear) in masonry assemblages."
American Society of Mechanical Engineers ASTM E519-02, West Conshohocken, Pa.
(ASME). (2002). "Liquid transportation systems for Ayres, J. M., and Sun, T. y. (1973a).
hydrocarbons, liquid petroleum gas, anhydrous ammo "Nonstructural damage to buildings, the great Alaska
nia, and alcohols." ASME B31.4, New York. earthquake of 1964." Engineering, National Academy
American Society of Mechanical Engineers oí' Sciences, Washington, D.e.
(ASME). (2001). "Refrigeration plant." ASME B31.5, Ayres, J. M., and Sun, T. y. (l973b).
NewYork. "Nonstructural damage." The San Fernando,
378
ASeE/SEI 41-06
California Eanhquake of February 9. (1971), Vol. lB, 8t/¡ In tI. BricklBlock Masonry Con!, Elsevier Applied
National Oceanic and Atmospheric Admínistration, Science, Essex, U.K., 1665-1672.
Washington, D.e. Cho, J. -Y., and Pineheira, J. A. (2006). "Inelastíc
Bartlen, S. F., and Youd, T. L. (1992). "Empírical analysis of reinforced concrete columns with short lap
prediction of lateral spread displacement." Proc. 4th splices subjected lo reversed eyelie loads." ACI Struct.
Japan-U.S. WorksllOp on Earthquake-Resistant Design J., 103(2).
ofLifeline Facilities and Countermeasures for Soil Cho, D. M., and Relamal, E. (1993). "The Los
Liquefaction, M. Hamada and T. D. O'Rourke, eds. Angeles Counly Emergeney Operations Center on
Report No. NCEER-92-0019, Vol. 1, National Cenrer high-damping rubber bearings lo withsland an earth
for Eanhquake Engineering Researeh, Buffalo, N.Y., quake bigger than Ihe big one." Proc. Seminar on
351-365. Seismic Isolation, Passive Energy Dissipatioll, and
Baziar, M. H., Dobry, R., and EIgamal, A-W. M. Active Control, Applied Technology Council Reporl
(1992). "Engineering evaluation of permanent No. ATC-l7-I, Redwood City, Calif., 209-220.
ground deformalions due to seismically-induced Ceilings and Interior Systems ConstruelÍon
liquefaction." Report No. NCEER-92-0007, National Assoeiation (CISCA). (1990). Recommendations for
Center for Earthquake Engineering Research, Buffalo, direct-hung acoustical and lay-in panel ceilings, seis
N.Y. mic zones 3-4, Deertield, 111.
Berry, M., and Eberhard, M. (2005). "Practical Ceilings and Interior Systems Construction
peltormance model for bar buckling." J. Struct. Engrg. Association (CISCA). (1991). Recommendations for
(ASCE), 131(7), 1060-1070. direct-/¡ung acoustical and lay-in panel ceilings, seis
Biskinis D. E., Roupakias G. K., and Fardis, mic zones 0-2, Deertield, 111.
M. N. (2004). "Degradation of shear strength of Computers and Struetures, Ine. (CSI). (2003).
reiníorced concrete members with inelastic cyclic ETABS (Version 8.0): Linear and nonlinear, statíc and
displacements." ACI Struct. J., 101(6). dynamic analysis and design 01 building systems,
Bouwkamp, 1. G., and Meehan, l F. (1960). Berkeley, Calif.
"Drift Iimitations imposed by glass." Prac. 2nd World Concrete Reintoreing Steel Institute (CRSI).
Conf. on Earthquake Engineering, Tokyo, 1763-1778. (1981). Evaluation 01 reinforcing steel systems in old
Bowles, J.E. (1988). Fotmdation Analysis and reillforced concrete structures, Chicago.
Design, 4th Ed., McGraw-Hill, New York. Constantinou, M. e., Tsopelas, P. e., Kim, Y.-S.,
Bozorgnia, Y., Mansour, N., and CambelI, K. W. and Okamoto, S. (1993). "NCEER-TAISEI
(996). "Relationship between vertical and horizontal Corporation researeh program on sliding seismic isola
response spectra for the Northridge earthquake." Proc. tion systems for bridges: Experimental and analytical
11th World Congo on Earthquake Engineering, study of friction pendulum system (FPS)." Report No.
AcapuJco, Mexico. NCEER-93-0020, NationaJ Center for Earlhquake
Breyer, D. E., Fridley, K. l, and Cobeen, K. E. Engineering, State University of New York at Buffalo.
(1999). Design of wood structures, 4th Ed., McGraw Construetion Engineering Researeh Laboratory
HilI, New York. (CERL). (1997). "The CERL equipment fragility and
Building Otlicíals and Code Administrators protection, experimental detinition of equipment vul
lnternational (BOCAl). (1999), National building nerability to transient support motions." Tech Rep
code, Country Club HiIls, 111. 97/58, ADA No. 342277, U.S. Army Corps of
Building Seismic Safety Councíl (BSSC). (2000). Engineers, Champaign, 111.
NEHRP recommended provísions far seismic regula Dept. of the Army, Navy, and Air Force. (1986).
tions for new building s and other structures, 2000 Ed. "Seismic design of buildings." Publicatíon Nos. Air
Prepared by the Building Seismic Safety Councíl for Force AFM 88-3, Army TM5-809-JO.l, Navy NAVFAC
the Federal Emergency Management Agency, P-355.1, Chapter B.I, Dept. of the Army, Navy, and
Washington, D.C. Air Force, Washington, D.e.
California Governor's Board of lnquiry on the Drake, R. M., and Bachman, R. E. (1995).
1989 Loma Prieta Earthquake. (1990). Competíng "Interpretation of instrumental building seismic data
against time. Report to Governor George Deukrnejian, and implications for building codes." Proc. SEAOC
Slate of Calitornia, Oftice of Planning and Research, Annual Conv., Structural Engineering Associatjon of
Sacramento, Calif. California, Sacramento, Calif.
Calvi, G. M. (1988). "Correlation between ultra Earthquake Engineering Researeh Institute
sanie and load tests on old masonry specimens." Proc. (EERI). (1995). "In wait tor the next one." Proc. 4th
379
SElSMIC REHABILITATION OF EXISTING BUILDlNGS
Japan-U.S. Workshop on Urban Earthquake Hazard seismic rehabililation of buildings, phase 1: Issues
Reduction, Earthquake Engineering Research Institute identification and resolution." FEMA 237, prepared
and Japan Institute 01' Social Sa1'ety Science, sponsors, by the Applied Technology Council ror the Federal
Osaka. Emergency Management Agency, Washington,
Elwood, K. J., and,Moehle, 1. P. (2004). "Evalua D.e.
tion 01' existing reinforced concrete columns." Proc. Federal Emergency Management Agency
13th World Con! on Earthquake Engineering, (FEMA). (1994). "Reducing the risks of nonstructural
Vancouver, B.C. earthquake damage, a practical guide:' FEMA 74,
Elwood, K. J., and Moehle, J. P. (2005a). "Drift Washington, D.e.
capacity 01' reinforced concrete columns with light Federal Emergency Managemenl Agency
Iransverse rein1'orcement." Earthquake Spectra (FEMA). (1995). "Typical costs for seismic rehabilila
(Earthquake Engineering Research Institute, Oakland, tion of buildings, 2nd Ed., Vol. 11: Supporting docu
Calif.), 21(1), 71-89. mentation." FEMA J57, prepared by the Hart
Elwood, K. J., and Moehle, J. P. (2005b). "Axial Consultant Group for the Federal Emergency
capacity model for shear-damaged columns." ACI Management Agency, Washington, D.e.
Struct. J., 102(4),578-587. Federal Emergency Management Agency
Elwood, K. J., and Eberhard, M. O. (2006). (FEMA). (1995). "Typical costs for seismic rehabilita
"Etfeclive stiffness 01' rein1'orced concrete columns." tion 01' buildings, 2nd Ed., Vol. 1: Summary." FEMA
PEER Research Digest, Pacitic Earthquake 156, prepared by the Hart Consultant Group for the
Engineering Research Center, University 01' California, Federal Emergency Management Agency, Washington,
Berkeley. D.C.
Epperson, G. S., and Abrams, D. P. (1989). Federal Emergency Management Agency
"Nondestructive evaluation of masonry buildings, (FEMA). (1995). NEHRP recommended provisions
Advanced Construction Technology Center." Rep No. for seismic regulations for new buildings, 1994 Ed.,
89-26-03, College of Engineering. Univel'sity of Part 1: Provisions and Part 2: Commentary." FEMA
IIIinois at Urbana. 222A and FEMA 223A, prepared by the Building
Fardis, M. N., and D. E. Biskinis. (2003). Seismic Safety Councíl ror the Federal Emergency
"Deformation capacity 01' RC members, as controlled Management Agency, Washington, D.e.
by tlexure or shear." Otani Symposium 2003, Tokyo, Federal Emergency Management Agency
511-530. (FEMA). (1997). "NEHRP guidelines for the seismic
Feilden, B. M. (1987). Between two earthquakes: rehabilitation 01' buildings." FEMA 273, prepared by
Cultural pmperty in seismic zones, Geny Conservation the Building Seismic Safety Council rol' the Federal
Institute, Marina del Rey, Calif. Emergency Managemenl Agency, Washington, D.e.
Federal Emergency Management Agency Federal Emergency Management Agency
(FEMA). (1988). "Rapid visual screening of buildings (FEMA). (1997). "NEHRP commentary on the guide
for poten tial seismic hazards: A handbook." FEMA Iines for seismic rehabilitation 01' buildings." FEMA
154, prepared by the Applied Technology Council 274, prepared by the Building Seismic Safety CounciJ
(Rep No. ATC-21) for Ihe Federal Emergency for lhe Federal Emergency Management Agency,
Management Agency, Washington, D.C. Washington, D.C.
Federal Emergency Managcment Agency Federal Emergency Managemenl Agency
(FEMA). (1992). "NEHRP handbook 01' techniques (FEMA). (1997). "NEHRP recommended provisions
for the seismic rehabilitatíon of existing buildings." for seismic regulalions for new buildings and other
FEMA 172, prepared by the Building Seismic Safety structures, 1997 Ed., Part 1: Provisions, and Part 2:
Council for the Federal Emergency Management Commentary." FEMA 302 and FEMA 303, prepared
Agency, Washington, D.e. by the Building Seismic Safely Council for the Federal
Federal Emergency Management Agency Emergency Management Agency, Washington, D.e.
(FEMA). (1992). "NEHRP handbook for the seismic Federal Emergency Management Agency
evaluation 01' existing buildings." FEMA 178, prepared (FEMA). (1998). "Planning for seismic rehabilitarion:
by the Building Seismic Safety Council for the Federal Societal issues." FEMA 275, prepared by VSP
Emergency Managemenl Agency, Washington, D.C. Associates for the Building Seismic Satety Council
Federal Emergency Management Agency and Federal Emergency Management Agency,
(FEMA). (1992). "Development 01' guidelines for Washington, D.C.
380
ASeE/SEI 41-06
Federal Emergency Management Agency ATC, and CUREe Joint Venture for the Federal
(FEMA). (1998). "Evaluation of earthquake-damaged Emergency Management Agency, Washington, D.C.
concrete and masonry wall buildings-Basic proce Federal Emergency Management Agency
dures manual." FEMA 306, prepared by the Applied (FEMA). (2000). "State oí" art report on performance
Technology Council (ATC-43 Project) for me Federal prediction and evaluation." FEMA 355F, prepared by
Emergency Management Agency, Washington, D.C. the SEAOC, ATC, and CUREe Joint Venlure for lhe
Federal Emergency Management Agency Federal Emergency Management Agency, Washington,
(FEMA). (1998). "Evaluation of earthquake-damaged D.C.
concrete and masonry wall buildings-Technical Federal Emergency Management Agency
resources." FEMA 307. prepared by the Applied (FEMA). (2000). "Preslandard and commenLary for
Technology Council (ATC-43 Project) for the Federal the seismic rehabilitalion of buildings." FEMA 356,
Emergency Management Agency, Washington, D.C. prepared by the American Society of Civil Engineers
Federal Emergency Management Agency 1'or the Federal Emergency Management Agency,
(FEMA). (1998). "Repair of earmquake-damaged con Washington, D.C.
crete and masonry wall buildings." FEMA 308. pre Federal Emergency Management Agency
pared by me Applied Technology Council (ATC-43 (FEMA). (2000). "Global topics report on the pre
Project) for me Federal Emergency Management standard and commemary for the seismic rehabilitation
Agency, Washington, D.C. of buildings." FEMA 357, prepared by me American
Federal Emergency Management Agency Society of Civil Engineers for the Federal Emergency
(FEMA). (1999). "Case studies: An assessment of Management Agency, Washington, D.C.
the NEHRP Guidelines for the Seismic Rehabilitation Federal Emergency Management Agency
of Buíldings" FEMA 343, Federal Emergency (FEMA). (2001). "NEHRP recommended provisions
Management Agency, Washington, D.C. for seismic regulations for new buildings and other
Federal Emergency Management Agency structures, 2000 Ed., Part 1: Provisions and Part 2:
(FEMA). (1999). "Guidelines for the seismic rehabíli Commentary." FEMA 368 and FEMA 369, prepared
tation of buildings: Example applications." FEMA 276, by me Building Seismic Safety Council for the
prepared by the Applied Technology Council for the Federal Emergency Management Agency, Washington,
Building Seismic Safety Council and the Federal D.C.
Emergency Managemenl Agency, Washington, Federal Emergency Managemenl Agency
D.C. (FEMA). (2004). "NEHRP recommended provisions
Federal Emergency Management Agency for seismic regulations for new buildings and other
(FEMA). (2000). "Recommended seismic design crite structures, 2003 Ed., Part 1: Provisions and Part 2:
ria for moment-resisting steel trame structures." Commentary." FEMA 450 and FEMA 45J, prepared
FEMA 350, prepared by the SEAOC, ATC, and by the Building Seismic Sal'ery Council for the Federal
CUREe Joint Venture ror the Federal Emergency Emergency Management Agency, Washington, D.C.
Management Agency, Washington, D.C. Federal Emergency Management Agency
Federal Emergency Management Agency (FEMA). (2005). "lmprovement of nonlinear static
(FEMA). (2000). "Recommended seismic evaluation seismic analysis procedures." FEMA 440, prepared by
and upgrade criteria for existing welded moment the Applied Technology Council for the Federal
resisting steel structures." FEMA 35J, prepared by the Emergency Management Agency, Washington, D.C.
SEAOC, ATC, and CUREe Joint Venture for the Franklin, A. 0., and Chang, F. K. (1977).
Federal Emergency Management Agency, Washington, "Earthquake resisLance of earth and rock-fill dams:
D.C. Permanent displacements of earth embankments by
Federal Emergency Management Agency Newmark sliding block analysis." Misc. Paper S-7J
(FEMA). (2000). "Recommended specifications and 17, Rep 5, U.S. Army Corps of Engineers, Waterways
quality assurance guidelines for sleel moment-frame Experiment Station, Vicksburg, Miss.
construction for seismic applications." FEMA 353, Gazetas, G. (1991). "Foundation vibrations."
prepared by the SEAOC, ATC, and CUREe Joim Foundation engineering handbook, H. Y. Fang, ed.,
Venture ror the Federal Emergency Management Van Nostrand Reinhold, New York, 553-593.
Agency, Washington, D.C. Hamada, M., Yasuda, S., Isoyama, R., and Emolo,
Federal Emergency Managemem Agency K. (1986). Study ol/tiquefactíon indllced permanent
(FEMA). (2000). "State or art report on connection ground displacements. Report for the Association for
performance." FEMA 355D, prepared by the SEAOC, the Development 01' Earthquake Prediction, Tokyo.
381
SEISMIC REHABILITATION OF EXISTING BUILDINGS
Hamburger, R. O. (1993). "Methodology for seis Kehoe, B. E., and Attalla, M. R (2000).
míe eapaeity evaluatlon of steel-frame buildíngs with "Considerations of vertical acceleration on structural
infill unreinl'orced masonry." Proc. 1993 Natl. response." Proc. 12th World Congo on Earthqllake
Earthquake COllj, Central U.S. Earthquake Engíneering, Auckland, New Zealand.
Consortium, Memphis, Tenn., VoL n, 173-191. KelIy, J. M. (1988). "Base isolalion in Japan."
Hanna, A. M. (1981). "Foumlations on strong Rep. No. UCB/EERC-88/20, Earthquake Engineering
sand overlying weak sand." J. Geotech. Engrg. Div. Research Center, University of California, Berkeley.
(ASCE), I07(GT7), 915-927. Kelly, J. M. (1993). Earthquake-resístam desígn
Hanna, A. M., and Meyerhof, G. G. (1980). with rllbber, Springer-Verlag, London.
"Design charts for uItimatc bearing capacity 01' foun Kingsley, G. R, Noland. J. L., and Alkinson,
dations on sand overlying soft c1ay." Can. Geotech. J., R H. (1987). "Nondestructive evaluation 01' masonry
17,300-303. structures using sonic and ullrasonic pulse velocity
Hoover, C. A. (1992). Seismic retrofit policies: An techniques." Proc. 4th North American Masonry Conj.,
evaluation of local practices in zone 4 and their appli The Masonry Society, Boulder, Colo.
cation to zone 3, Earthquake Engineering Research Lagorio, H. J. (\990). Earthquakes: An architect's
Institute, Oakland, Calif. guide lo nonstructural seismic hazards, John Wiley &
Housner, G. W. (1963). "The behavior 01' inverted Sons, Inc., New York.
pendulum structures during earthquakes." Bull. Lynn, A. C. (2001). "Seismic evalualion ol' exist
Seismological Soco ofAm., 53(2), 403-417. ing reinforced concrete building columns." PhD disser
Inlemalional Conl'erence 01' Building Oflicials talion, Dept. of Civil and Environmenlal Engineering,
(ICBO). (1994). Uniform Building Codeo Whittier, University 01' California, Berkeley.
Ca1if. Lynn, A. C., Moehle, 1. P., Mahin, S. A., and
International Conference of Building Oflicials Holmes, W. T. (1996). "Seismic evaluation 01' existing
(lCBO). (1997a). "In-place masonry shear tests." reinforced concrete columns." Earthquake Spectra
UBC 21-6. Whiuier, Calif. (Earthquake Engineering Research Institute, Oakland,
lntemational Conterence ol' Building OHicials CaIiL). 12(4),715-739.
(lCBO). (1 997b). Uniform Code for Building Makdisi, F. l., and Sced, H. B. (1978). "Simplified
Conservation, Whiuier, Calif. procedure l'or estimating dam and embankment earth
International Conterence of Building Oflicials quake-induced deformations." J. Geotech. Engrg. Div.
(ICBO). (2000). "Acceptance criteria l'or seismic (ASCE), I04(GT7), 849-867.
qualification testing 01' nonstructural componenls." Makris, N., and Konslantinidis, D. (2001). The
AC-156, Intemational Conference ol' Building rocking spectrtlm and fhe shortcomings ofdesign
Officials Evaluation Services, Whittier, CaliL gllidelines. Pacific Earthquake Enginecring Research
Intemational Code Council (lCC). (2003). Center, Berkcley, California.
Internacional Building Code, Falls Church, Va. Makris, N. and Roussos, Y. (1998). Rocking
Institute of E]eclrica] and Eleetronics Engineers, response and overluming of equipmem under horizon
Inc. (IEEE). (1997). "IEEE recommended praclice tal. pulse-type motions, Pacitic Earthquake
rOl' seismic design of substations." IEEE 693, New Engineering Research Center, Berkeley, Calif.
York. Manufaclurers Standardization Socicty (MSS).
Ishihara, K, and Yoshimine, M. (1992). (1993). "Pipe hangers and supports: Malerials, design
"Evaluation 01' settlemenls in sand deposils following and manufacture." SP-58, Manufacturers
liquefaction during earlhquakes." Soils and Slandardization Sociely of the Valve and Fitting
FOlllldations (Japanese Society of Soi] Mechanics and Industry, Vicnna, Va.
Foundalion Engineering), 32( 1), 173-188. Melek, M. and Wallace, J. W. (2004). "Cyclic
Johnson, 1. J., Conoscente, 1. P., and Hamburger, behavior of columns wilh short lap splices." ACI
R.O. (1992). "Dynamic analysis of impacling struc Struct. J., 101(6).
tural systems." Proc. 10th World Conf on Earthquake Meyerhof, G. G. (1974). "U1timate bearing capac
Engineering, Madrid, Spain. ity of footings on sand layer overlying clay." Can.
Kasai, K., Maison, B. F., and Patel, D. 1. (1990). Geotech. J., 11(2),223-229.
HAn earthquake analysis 1'01' buildings subjected 10 a Murola, N., Goda, K.. Suzusi, S., Sudo, c., and
type 01' pounding." Proc. 4th U.S. National Conj of Suizu, Y. (1994). "Recovery charaeteristics 01' dynamic
Earthquake Engineering, Earthquake Engineering properties 01' high-damping rubber bearings." Proc.
Research Institute, Oakland, Calif. 3rd U.S.-Japan Worksltop on Earthquake Protective
382
ASCElSEI41-06
Systems for Bridges, Berkeley, California (1994). Noland, J. L., Atkinson, R. H., and Kingsley,
Report No. NCEER 94-0009, National Center for O. R. (1987). "Nondestructive methods l'or evaluating
Earthquake Engineering Research, Slate University of masonry structures." Proc. Intl. Conf O/l Structural
New York al Buffalo, 1-63 to 2-76. Faults and Repair, London.
Nagarajaiah, S., Reinhom, A., and Constantinou, Pais, A., and Kausel, E. (1988). "Approximale for
M. C. (1991). "3D-BASIS; Nonlinear dynamic anal y mulas for dynamic stift'nesses of rigid foundations."
sis of three dimensional base isolated structures." Rep. Soil Dynamics and Earthquake Engrg., 7(4),213-227.
No. NCEER-9J-0005, National Center for Earthquake Panagiotakos, T. B., and Fardis, M. N. (2001).
Engineering Research, State University of New York "DeformalÍon of reinforced concrete members al
at BuffaJo. yielding and ultimate." ACI Struct. J., 98(2).
NationaJ Research Council (NRC). (1985). Pekcan, O., Mander, 1., and Chen, S. (1995). "The
Committee on Earthquake Engineering, Commission seismic response of al; 3 scale mooel RC structure
on Engíneering and Technical Systems. Liquefaction with elastomeric spring dampers." Earthquake Spectra
of soils during earthquakes, National Academy Press, (Earthquake Engineering Research Institute, Oakland,
Washington, D.C. Calif.), 11(2),249-267.
National Bureau of Standards (NBS), now Precast/Prestressed Concrete Institute (PCI)
National Institute for Science and Technology. (1999). PCI design handbook: Precast and prestressed
(1977). "Evaluation of structural properties of concrete, 5th ed, PrecasÚPreslressed Concrete
masonry in existing buildings." Building Science Institute, Chicago.
Series 62, U.S. Dept. of Commerce, Washington, Priestley, M. 1. N., Evison, R. 1., and Carr, A. J.
D.C. (1978). "Seismic response ol' structures free to rock on
Newmark, N. M. (I965). "Effect of earthquake on their foundations." Bull. New Zealand Natl. Soco for
dams and embankments." Geotechnique, 15, 139-160. Earthquake Engrg., 11(3),141 150.
National Fire Protection Association (NFPA). Reinhorn, A. M., Nagarajaiah, S., Constantinou,
(1991). "Manual of hazardous chemical reactions." M. C., Tsopelas, P., and Li, R. (1994). "3D-BASIS
NFPA, 491M-91, Quincy, Mass. TABS (Version 2.0): Compuler program for nonlinear
National Fire Protection Association (NFPA). dynamic analysis 01' three-dimensional base isoJated
(1994). "Hazardous chemicals data." NFPA, 49-94, structures." Rep. No. NCEER-94-0018, NationaJ
Quincy, Mass. Center l'or Earlhquake Engineering Research, State
National Fire Protection Association (NFPA). Universily ol' New York at Buftido.
(1994). "Ouide to fire hazard properties of flammabJe Sansalone, M., and Carino, N. (1988). "Impact
liquids, gases, and volatile solids." NFPA, 325-94, echo methoo: Detecting honeycombing, the depth of
Quincy, Mass. surl'ace opening cracks, and ungrouted tendons."
National Fire Protection Association (NFPA). Concrete Int. (ACI), 10(4), 38-46
(2001). "Standard system for the identification oí' Secretary of lhe Interior. (1992). Standards for the
lhe fire hazards oí' materials." NFPA, 704, Quincy, treatment of historie properties, National Park Service,
Mass. Washington, D.C.
National Fire Protection Association (NFPA). Secretary of the Interior. (1995). Standards for the
(2002). "Standard for the installation ol' sprinkler sys treatment of historic properties with guidelines for
tems." NFPA 13, Quíncy, Mass. preserving, rehabilitating, restoring, and reconstruct
National Institute ol' Standards and Technology ing historic buildings, National Park Service,
(NIST). (1992). "Performance standard l'or wooo Washington, D.C.
based structural use panels." U.S. Product Standard Seed, R. B., and Harder, L. F. (1990). "SPT-based
PS 2-92, Washington, D.C. analysis of cycJic pore pressure generation and
National InstÍlute of Standards and Technology undrained residual strength." Proc. H. B. Seed
(NIST). (1995). "ConstruclÍon and industrial plywooo Memorial Symposium, SI. Thomas, U.S. Virgin
with typical APA trademarks." U.S. Product Standard IsJands, Vol. 2, 351-376.
PS 1-95, Washington, D.C. Seed, H. B., and Idriss, 1. M. (1971). "Simplified
Nims, D. F., Richter, P. J., and Bachman, R. E. procedure for evaluating soil Jiquefaction potential."
(1993). "The use ol' lhe energy dissipation reslraint l'or J. Soil Mech. and Found. Div. (ASCE) 97(SM9),
seismic hazard mitigatíon." Earthquake Spectra 1249-1273.
(Earthquake Engineering Research Instítute, Oakland, Seed, H. B., and Idriss, I. M. (1982). "Oround
Calif.), 9(3), 467-498. motions and soil Iiquefaction during earthquakes."
383
SEISMIC REHABILlTATION OF EXISTING BUILDlNGS
Monograph Series, Earthquake Engineering Research TSM (1992). "Seismic design for buildings."
Institute, Oakland, Calif. Tri-Servíces Manual TM5-809-/O NAV FAC P 355,
Seed, H. B., Tokimatsu, K., Harder, L. F., and AFM 88-3, Chapter 13, Washington, D.e.
Chung, R. M. (1985). "Inl1uence 01' SPT proce Tsopelas, P., and Constanlinou, M. C. (1994).
dures in soilliquefaction resistance evaluations." J. "Experimental and analytical study of systems con
Geotech. Engrg. Div. (ASCE), 111(12), 1425-1445. sisling of sliding bearings and tluid resloring force
Sezen, H. (2002). "Seismic response and model damping devices." Report No. NCEER 94-00/0,
ing of lightly reinforced concrete building columns," National Center for Earthquake Engineering Research,
PhD dissertation, Dept. of Civil and Environmental State University of New York al Buffalo.
Engineering, University of California, Berkeley. Tsopelas, P. C., Constanlinou, M. e., and
Sheet Glass Association 01' Japan. (1982). Reinhorn, A. M. (1994) "3D-BASIS-ME computer
Earthquake safety design ofwindows, Japan. program for nonlinear dynamic analysis of seismically
Sheet Metal and Air Conditioning Contractors isolated single and multiple slructures and liquid slor
National Association (SMACNA). (1980). Rectangular age tanks." Repon No. NCEER-94-0014, National
industrial duct construction standards, Chantilly, Va. Center for Earthquake Engineering Research, State
Sheet Metal and Air Conditioning Contractors University of New York al Buffalo.
National Association (SMACNA). (1985). HVAC duct U.S. Dept. of Energy. (1997). "Seismic evaluation
constructíon standards, metal andflexible, Chanlilly, procedure for equipmenl in U.S. Department of
Va. Energy facilities." DOElEH-545, Washington, D.C.
Sheet Metal and Air Conditioning Contractors U.S. Depl. ofthe Navy (NAVFAC). (1986a). "Soil
National Associalion (SMACNA). (1991). Seismic mechanics: Naval facilities engineering command
restraint manual guíde/ines for mechanical equipment, design manual." NAVFAC DM-7.01, Alexandria, Va.
and Appendix E-1993 addendum, Chantilly, Va. U.S. Dept. of the Navy (NAVFAC). (l986b).
Soong, T. T., and Constantinou, M. C. (1994). "Foundation and earth structures: Naval facilities engi
Passive and active structural vibration control in civil neering command design manual." NAVFAC DM-7.02,
engineering, Springer-Verlag, Wien, New York. Alexandria, Va.
Southern Building Code Congress International U.S. Nuclear Regulalory Commission (USNRC).
(SBCCI). (1999). Standard building code, (1976). "Combining modal responses and spatial com
Birmingham, Ala. ponents in seismic response analysis." Regulatory
Stark, T. D., and Mesri, G. (1992). "Undrained Guide 1.92, Washington, D.C.
shear strength of liquefied sands for stability analysis," Wallace, J. W. (1994). "New methodology for
J. Geotech. Engrg. Div. (ASCE), 118(11), 1727-1747. seísmic desígn of RC shear walls." J. Struct. Engrg.
Steel Deck Inslitute (SOl). (1981). Diaphragm Dív. (ASCE), 120(3),863-884.
Design Manual, 1st Ed., Fox River Grove, Ill. Wallace, J. W. and Thomsen IV, J. H. (1995).
Timeshenko, S., and Woinowsky-Krieger, S. "Seismic Design of RC Shear Walls (Parts 1 and 1I),"
(1959). Theory ofplates and shells, 2nd Ed., McGraw J. Struct Engrg. (ASCE), 75-101.
Hill, New York. Western Wood Products Association (WWPA).
Timler, P. A. (2000). "Design evolution and state (1996). Westem woods use book, Porlland, Ore.
of-the-art development 01' steel plate shear wall con Wood, S. L. (1990). "Shear strenglh of low-rise
slruction in Norlh America." Proc. 69th Ann. SEAOC reinforced concrete walls." ACI Strltct. J., 87( 1),
Conv., Vancouver, B.C., 197-208. 99-107.
Tissell, J. R. (1993). "Wood structural panel shear Wrighl, P. D., 1989. "The development of a pro
walls." Research Rep 154, American Plywood cedure and rig for testing the racking resistance of
Association, Tacoma, Wash. curlain wall glazing." Study Rep No. 17, Building
Tissell, 1. R, and Elliott, J. R (1997). "Plywood Research Association of New Zealand (BRANZ), J8.
diaphragms." Research Rep 138, American Plywood Yegian, M. K., Marciano, E. A., and Gharaman,
Association, Tacoma, Wash. V. G. (199 J). "Earthquake-induced permanenl defor
Tokimalsu, A. M., and Seed, H. B. (1987). malÍon: ProbabiJistic approach." J. Struct. Engrg. Div.
"Evaluation of seulements in sands due 10 earthquake (ASCE), 117(1),35-50.
shaking." J. Geotech. Engrg. Div. (ASCE), 113(8), Yim, S. C., and Chopra, A. K. (1985). "Simplitied
681-878. earthquake analysis of multistory structures with foun
384
ASeE/SEI 41-06
dation uplifl." J. Su·uct. Engrg. Div. (ASCE), 111(12), shops on evaluarion of liquefaction resistance of soils."
2708-2731. 1. Ceotech. and Ceoenvir. Engrg. (ASCE), 127(4),
Youd, T. L., and Perkins, D. M. (1978). "Mapping 297-313,Oc[ober.
Iiquefaction indúced ground failure poremial;' J. Zayas v., Low, S. S., and Mahin, S. A. (1987).
Struct. Engrg. Div. (ASCE), 104(GT4),433-446. Tlle FPS eartllquake resísting system, experimemal
Youd, T.L., Idriss, 1. M., er al. (200 1). report, Reporl No. UBCIEERC-87/01. Earthquake
"Liquefacrion resisrance of soils: Summary report Engineering Research Center, Universiry of California,
from the 1996 NCEER and 1998 NCEERlNSF work Berkeley, CA.
385
INDEX
acceJeration, vertical. See vertical seismic effects adhered veneer, 329
acceleration-sensitive nonstructural components, adjacent buildings or activity, 30-31, 295-296
320-321 aesthetic features of building, 6
acceleration time hislOries, 28, 67, 73 air-bag tests (masonry), 205
acceptance criteria for Rehabilitatíon Objective, alarm systems. See fire alarm systems
34,38-42 alternative construction methods, 52-53
alternalive (experimental data), 50-53 alternative materials, 52-53
building analysis procedures, 73-75 alternative modeling parameters, 50-53
concrete components: cast-in-place alternative radonal building analysís procedures, 38
diaphragms, 193; rrames with analysis procedures, 2, 34-42
concrete infills, 174, 176, 178; frames acceptance criteria, in general, 73-75. See
with masonry infills, 176-177; post-ten also acceptance criteria for
sioned beam-column moment frames, Rehabilitation Objective
167; precast concrete frames, 170; pre concrete. See concrete components
cast diaphragms, 194; reinforced beam energy dissipation systems, 280-284
column moment frames, 160-166; shear linear. See linear analysis procedures
walls, 183-187; shear walls, precast, masonry. See entríes at masonry
190; slab-column moment frames, nonlinear. See nonlinear analysis
170-171 procedures
energy dissipation systems, 283, 284, seismic isolation systems, 266-273,
287 269-271
foundation soil of buildings, 95-96 selection of, 54
masonry, 207; infills, 219-220, 222; rein steeL See steel components
torced walls, 213-215; unreinforced wood and Iight metal, 233-236, 242
walls,211-212 anchorage
nonstructural components, 318-319; archi to masonry walls, 22-23
tectura!, 329-338; furnishings and inte stecl to concrete, 108
rior equipment, 346-350; mechanical, walls to diaphragms, 46-47
electrical, and plumbing, 338-346 anchorage to foundatíon, 309
seismic isolation systems, 277 anchored veneer, 329-330
steel components, 109-111, l 14-116; appendages. See parapets and ornamentatíon
braced frames (concentric), 130-131; archaeological significance. See historie or
braced trames (eccentric), 132; cast or archaeological significance considerations
wrought iron, 143; diaphragms, 111, archaic diaphragms, 140-141
136-142; FR moment frames, 108, archaic stee1 components, 105
119-124; pile foundations, 142; plate arching action (masonry), 212, 221-222
sheer walls, lll, 116, 134; PR moment architectural components, 311-350. See also
frames, 128-129 nonstructural components; specific component
wood and light metal framing, 232-233, by name
234, 242-243; foundation, 257-258; acceleralion- and deformation-sensilive
other wood elements, 258-259; shear components, 320-321
walls, 241-244, 248; sheathing, component evaluation, 318-319
241-244,247-249,253-257 condition assessment, 312-313
accidental torsional moment at a story, 55-56 evalua(Íon procedures, 32]-327
acronyms, dictionary of, 365-366 historical significance considerations,
active geologic fau1ts, 77 313-318
mitigation schemes, 82 impact of rehabilitalion, 353
active rehabilitation programs, 351, 352 nonstructural, 16,314,329-338
active seismic systems, 260 rehabilitation objectives, 319-320
actual torsional moment at a story, 55-56 rehabilitation procedures, 327
adequacy. See acceptance criteria for seismic hazards, 316
Rehabilitatíon Objective structural-nonstructural consideralions, 320
387
SElSMIC REHABILlTATION OF EXISTING BUILDlNGS
388
ASeE/SEr 41-06
389
SEISMIC REHABILlTATION OF EXISTING BUILDlNGS
CBF (concentric braced frames), 129-131, composite parlially restrained connections, 128
217-218 comprehensive collection of as-built inrormation,
ceilings, 335-336 31-33
Nonstructural Performance Levels, 16, 3 14 concrete components, 146-147
preservation of egress, 320 masonry, 200
chemical properties of steel components, 104 steel componenls, 105-106
Chevron bracing, 306-307 wood and light metal framing, 227
chimneys and stacks, 337-338 comprehensíve condition assessment
Nonstructural Performance Levels, 16, 314 concrete material s and components, 150
chord rotation for beams, detined, 116 masonry, 203-204
chords. See diaphragm chords steel components, 107
c1adding, 16 wood and light metal framing, 231
coated masonry walIs, 209 compression testing (masonry), 65, 204-205
code otlicials, selectíng Rehabilitatíon Objective, 2 compressive strength. See strength of building
Coefficient Method for calculating target displace components
ment, 70 computer access tloors, 315, 347
coefficient 01' friction, sliding isolation bearings, compuler and communication racks, 315,
265-266 348-349
Collapse Preventíon Building Performance computer systems, 18
Level (5-E), 8-10, 21 concentric braced frames (CB F), 129-131,
foundation soil acceptance eriteria, 96 217-218
soil condition ¡nformalion, 76-77 concrete componenls, 143-197
Collapse Prevention Structural Performance anchorage lo, 108
Level (S-5), 12-14, 16. See a/so acceptance assumptions and requirements ror rehabilita
críteria for Rehabilitatíon Objectíve tion, 151-158
masonry walls, 212, 215 braced frames, 12, 191-192
seismic ¡solation and energy dissipation sys cast-in-place: conneclÍons to existing con
tems,260 crete, 157; diaphragms, 14, 192-194;
coUecting data. See data collection pile foundations, 195; simplitied rehabili
columns, concrete. See post-tensioned concrete tation, 299-300
beam-column moment frames; reinforced con data collection for rehabilitation,
crete beam-column moment frames 144-151
columns, steel, 109, 114, ] 19 diaphragms, 14
acceptance cri teria, 119-124 foundalion elements. 195-197
combíned elastomeric-slíding isolation systems, frames Wilh infills, 173-178
259, 266. See a/so seismic isolation systems momenl frames, 158-171; post-tensioned
common elements. See shared elements between beam-column, 158, 166-167; reinforced
buildings beam-column, 158, 159-166; simplitied
communication racks, 315, 348-349 rehabilitalion, 298-299; slab-column,
communications components. See eleclrical 158-159, ]66-171; Structural
componenls Performance Leve1s, 12
community revitalization, 353 precast diaphragms, 14, 194
compaction, ditIerential. See differential precast frames, 171-173
compaction rehabiJitatÍon measures, 158
complíance vs. performance, 1 reinforcing stee1: acceplance criteria for lin
complianl bearings, 44 ear procedures, 155; development of,
component properties. See data collection; 156--157; properties measuremenl,
material properties ]45-149, 156
component stiffness. See stiffness (structural) shear walls, 12, 178-187; precast, 187-191;
component strength. See strength of building simplified rehabilitation, 299-300; Stee)
components Frames with Concrete Shear Walls build
components of buildings. See en tries at building ing type, 29), 296
component simplitied rehabílitation, 309-311
390
ASeE/SEI 41-06
391
SElSMIC REHABILlTATION OF EXISTING BUILDINGS
392
ASeE/SEI 41-06
analysis and modeling, 57, 65-66,67, 72, double diagonally sheathed wood diaphragms,
73 250,252,254-255,256
building period estimation, 63 double splil tee connectÍon, 110, 115, 127
cast-in-place concrete, 14, 192-194 double straight-sheathed wood diaphragms, 250,
deformation- and force-controlled actions, 253,256
40,65-66,67 additional attachment, 252
design requirements, 45-46 doweled bars (concrete reinforcement), 157
simplitied rehabiJitation, 307-308 drainage piping. See fluid piping
steel, rehabilitation of, 111, 135-142 drift values
Structural Performance Levels and, 14 nonstructural components, 320-321,330
wall anchorage to, 46-47 simplitied rehabilitation, 297
wood, 14, 229,249-257; default expected Struclural Performance Levels and, 12-14
strength values, 229; drilled-in anchor connection systems, 157-158
modeling parameters and acceptance drilled shafts, stiffness and capacity, 95
criteria, 234-235, 242-243 drywall oc gypsum plaster, 225, 237-238, 240, 247
dictionary of acronyms, 365-366 simplified rehabilitatíon, 306
diclÍonary of symbols, 354-365 ductilily demands, concrete components, 154
diclionary of terms, 366-374 ducts, 17
differential compaction, 80, 80-81 ductwork, 314
induced by Iiquetaction, 80 dynamic analysis procedures, selection of, 54. See
miligation schemes, 82 also analysis procedures; LDP; NDP
directed risk mitigation programs, using Ihis seismic isolation syslems, 269-271
standard for, 350-354 dynamic p-a effects, 58
discontinuity irregularities, 36, 43
discontinuous sheer walls, 178, 180-187 earthquake effects, secondary, 317
displacement-dependent energy displacement Earthquake Hazard Leve1s, 8-9
devices, 279, 286 defining hazard due to ground shaking,
linear analysis procedures, 280-281, 282 22-27 '
nonlinear analysis procedures, 283 exceedance probabilities, 22, 24--25
displacement multiplier due to horizontal torsÍon, maps of, 22-23
55 seismic isolation systems, 269
displacement of residents by seismic rehabilita simplified rehabilítation, 293
tion, 353 eccentric braced frames, 131-133,218
displacement of seismic isolators, 272, 274 econornic acceptability of rehabilitalion design,
displacement of soil slopes (Iandsliding), 7-8. See also costs of rehabilitation
81-83 economic considerations. See COSIS of rehabilitation
disruplion of operalion education prerequisites of design professionals,
considering significance of, 6 1-2
nonstructural performance, not consídered, effeclive damping ratio. See damping effects
19-20 effective mass factor, 64, 65
dissipation devices, 44, 259-261, 277-287 effective period of building, 62-63, 69
implementation strategies, 278 seismic isolation systems and, 271
mathemalical modeJing, 278, 279-280 effeclive seÍsmic weight of building, 64
distance between buildings, 47-48 etlective snow load, 64
distribution, electrical. See electrical components effective stiffness. See also stiffness (structural)
documents and reports concrete components, 152
as-built inforrnation collection requirements, seismic isolation systems, 266-268
3/-33 etl'ectívely monolíthic construction, concrete sheer
construclÍon documents, 7-8 walls, ] 88, ] 89, 190
construction quality assurance, 49 effectiveness of risk mitigation programs, 351
experimental data, 50-51, 53 egress, preservation of, 319-320
maintenance of, 50 elastíc modulus in compression (masonry), 199
doors, 16, 320 elastomeric seismic isolators, 261-264
393
SEISMIC REHABILlTATION OF EXISTING BUILDlNGS
394
ASCFJSEI41-06
395
SEISMIC REHABILITATION OF EXISTING BUILDINGS
general response spectrum for ground shaking Response Speclrum Method, 66-67. See
hazard, 26-27 a/so LDP (Linear Dynamic Procedure);
geologic faults, 77, 82 energy dissipation systems, 282-283;
geologic site hazards, 6 seismíc isolation systems, 269, 272
damping effects 01' SSI, 58, 96, 98-99 seismic isolator criteria, 269
fault rupture, 77, 82 time history analysis, 28, 67, 73
tlooding or inundation, 81, 83 ground settlement, differential. See ditIerential
foundation tlexibility. See tlexibility of compaction
foundation grout injections, 209
foundation rehabilitation. See foundation, gypsum pI aster, 237, 246
rehabilitation of simplitied rehabilitation, 306
foundation strength and stiffness, 83-96; gypsum sheathing, 238, 247
expected capacities, 83-86 gypsum wallboard. See drywall
kínematic effects of SSI, 58, 96-98
landsliding, 81-83 hazardous materíals piping, 341
liquefaction, 77-80, 82 hazardous material s storage, 18, 315, 347-348
risk reduction. See mitigating seismíc-geo hazards
logic site risk from adjacent buildings, 31
seismic earth pressure, 99-100 secondary effects of earthquakes, 317
simplified rehabilitation, 309 seismic. See seismic hazards
site characterization, 77-81 site-specific mitigation schemes, 82-83
girder-wall connections, deticiencies in, 308 Hazards Reduced Nonslructural Performance
glass block units, 330 Level (N-D), 16-18, 19,312,314-315
glazed exterior wall systems, 331-332 component evaluation, 318
global structural stiffening, 43 evaluation procedures, 321-323
global structural strengthening, 43-44 rehabilitation approaches, 327-328
glossary of acronyms, 365-366 HDR (high-damping rubber bearings) for seismic
glossary of symbols, 354-365 isolators, 262-263
glossary of terms, 366-374 heavy partitions. See partitions
goals of rehabil itation, 8-10, 351 high-damping rubber bearings (seismic isolators),
Enhanced Rehabililalion Objectives, 9 262-263
Limited Rehabilitation Objectives, 9; high-pressure piping, 341
priorilizing deticiency corrections, 294; high-risk buildings, identifying, 352
seismic isolation and energy dissipation higher mode effects (building analysis), 37
systems, 259 historic or archaeological significance considera
partial rehabilitatíon, 9-10, 292; prioritizing lions, 6, 313-319, 353-354
deticiency corrections, 294; simplified as-built information, 29
rehabilitation, 33; typical deficiencies for component evaluation, 318-319
model building types, 293-302 data collection, 313-318
Partial Rehabilitalion Objective, 9-10, 292; foundation information collection, 76
prioritizing deficiency corrections, 294; preservation goals, 351
simplitied rehabilitation, 33; typical deti seismic ¡solation systems, 259-260
ciencies for mode\ building types, history of architectural nonstructul'al components
293-302 (U.S.),313-317
Reduced Rehabilitalion Objeclive, 9 hooked bars (concrete reinforcement), 156-157
good-condition masonry, defined, 198-199 , horizontal distribution 01' pseudo-lateral force,
grade beams, adding to concrete foundations, 197 65
granular soils, 84-86. See a/so soil conditions horizontallumber sheathing shear waIls, 236-237,
gravity loads for load combinations, 59 240-241
ground improvement techniques, 82 with cut-in braces or diagonal blocking,
ground motion, 21-28 238,248
detining (characterizing), 22-27,66, 73 siding over, 237
liquefaction from. See Iiquefaction wood siding over, 244
396
ASeE/SEl 41-06
horizontal response spectrum for ground shaking inelastic demands. See DCRs (demand capacity
hazard, 26-27 ratios)
horizontal seismic etfects on nonstructural compo intllled openings (masonry walls), 209
nents, 322-324 infills, steel walls with, 134-135
horizontal steel bracing, 139-140 Steel Frames with IntilI Masonry Steel
horizontal structural components, 14 Walls building type, 291, 296
horizontal torsion inspection. See also entríes at evaluation
design requirement8, 44 degradation inspection: steel components,
modeling effects 01', 55-56 106; wood and light metal framing, 230,
housing los8 during constructions, 353 232
HVAC equipment and syslems, 17,314,317 design review. See veriticalÍon of design
duclwork, 314 assumptions
hybrid isolation systems, 259, 266. See also seis destructive cxamination, 29, 32; concrete
míe isolation systems materials and components, 145-147;
hysteretic behavior 01' rubber bearings, 262-264. historie significance and, 29; steel com
See also seismic isolation systems ponents, 106-107; wood and Iight metal
framing, 227, 231-232
idealized force-displacement curves, 69. See also energy dissipation systems, 285
10ad-de1'ormation characterislÍCs maintenance of reports, 50
Immediate Occupancy Building Performance nondestructive examinaLion (NDE), 29, 32;
Level (I-B), 10,20-21 concrete maleria)s and components, 147,
foundation soil acceptance criteria, 96 148, 150; historie signiticance and, 29;
subassemblies based on experimemal dala, masonry, 203-204; steeI components,
51 106-107; wood and light metal framing,
Immediate Occupancy Nonstructural Performance 227,231-232
Level (N-B), 16-19,314-315 seismic isolation systems, 274
architectural components, 329-331, special requircments for QA, 49
333-338 installation of foundation, 76
component evaluation, 318 interactÍon review of nonstrucLural components,
evaluation procedures, 321-322, 323 312-313
furnishings and interior equipment, 346-350 interior veneen" 314, 334-335. See also veneer
mechanical, electrical, and plumbing com aLtachments (masonry)
ponents, 338-346 Intermediate Moment Frames. See also reinforced
rehabilitation approaches, 327-328 concrete beam-column
seismic isolation and energy dissipation interpanel conneclions, 300
syslems, 260 inundalÍon, 81, 83
Immediate Occupancy Structural Performance investigation. See data colIection; inspection
Level (S-I), 11-14. See also acceptance crite 10. See entries al lmmediate Occupancy
ria for Rehabilitation Objeclive iron. See cast or wrought iron
masonry walls, 212, 215 irregularities, building systems, 296
seismic isolation and energy dissipation irregularities, component
syslems, 260 analysis and modeling, 57
impact echo testing (masonry), 204 determination for linear analysis, 35-36
in-place materials testing, 223-224 removal 01' reduction, 43
concrete materials and components, isolation from seismic hazards. See seismic isola
144-148 tion systems
masonry, 198-202
sleel materials and components, 101-106 jacketing. See confinement jackets
wood and light metal framing, 224-230 joint failure, piping. See plumbing systems and
in-plane discontinuity irregularities, 36 components
in-plane masonry joint modeling, FR moment frames, 113
infills, 217-220 jointed construction, concrete sheer walls, 189,
unreínforced walls, 210-212, 213-215 190
397
SElSMIC REHABILlTATION OF EXISTING BUILDlNGS
398
ASCElSEI41-Q6
] 90; slab-column moment frames, 168, masonry, 199,205-208; walls and wall
170 piers, 211
dynamic. See LDP (Linear Dynamic steel components, 101-103, 105
Procedure) wood and light metal framing, 226,
energy dissipation systems, 280-283 227-228
foundation son acceptance criteria, 96 lower-income groups, impact on, 353
horizontal torsíon effects, 55 LRB (low-damping rubber bearings) for seismic
masonry. See also entries at masonry: ¡nfill isoJators, 262
panels, 219, 220; reinforced walls, 214; LRFD methodo\ogy, 229-230
unreinforced walls, 211 LS. See entries at Life Safety
multidirectional seismic effects, 59 LSI (Liquefaction Severity Index), 79
nonstructural components, 327 LSP (Linear Static Procedure), 35-37, 61--66. See
overturning effects, 60-61 also linear ana\ysis procedures
primary and secondary components, 56-57 acceptance criteria, in general, 73-75
seismic isolation systems, 266-272 concrete components, 15], 155; acceptance
se\ection of, 54 criteria, 155; braced trames, 191-192;
static. See LSP (Linear Static Procedure) trames with concrete infills, 177; frames
steel components, 109-111; braced frames with masonry infiUs, 174, 176; post-ten
(concentric), 129-131; braced frames sioned beam-column moment trames, 167;
(eccentric), 131, 132; diaphragms, 135, reinforced beam-column moment trames,
137-141; FR moment frames, l13, 159, 163-165; shear walls, 182, 184-185,
118-123; plate sheer walls, 133-134; PR 186; shear walls, precast, 189, 190; slab
moment frames, 125-128 column moment frames, 168, 170
verification of design assumptíons, 59--60, energy dissipation systems, 280-282
75 force and deformation determination, 63--66
wood and light metal framing, 242 foundation soil acceptance criteria, 96
Iiquetaction, 77-80, 82 horizontal torsion effects, 55
Iíve loads, 77 masonry. See also entries at masonry: infill
load-deformatíon characteristics panels, 219, 220; reinforced walls, 214;
concrete components, 152-153; braced unreinforced walls, 211
frames, ] 92; frames with infills, 174, multidirectional seismic effects, 59
177-178; reinforced beam-column overturning effects, 60--61
moment frames, 159; shear walls, 182; period of building, calculating, 62--63
slab-co\umn moment frames, 168 seismic isolation systems, 269-271
energy dissipation systems, 279, 284, sleel components, 109-111; braced frames
285-287 (concentric), 129-131; braced frames
foundations, 77 (eccenlric), 131, 132; diaphragms, 135,
masonry, 206-208 137-141; FR momenl frames, 113,
seismic iso\ators, elastomeric, 261-264 118-123; pIare sheer walls, /33-134; PR
seismic iso\ators, sliding, 264-266 moment frames, 125-128
wood and Iight metal framing, 232 verification of design assumptions, 59--60,
load path corrections, 295 75
loading rates, seismic isolators dependent on, 276 wood and light metal framing, 223-224
local modification of components, 42-43
local risk mitigation programs, using this standard maintenance of energy dissipation systems, 285
for, 350-354 mandated rehabilitatíon programs, 352
local strengthening of componenls, 43 manufacturing equipment, 17
longitudinal reinforcement of concrete compo maps 01' earthquake probabilities, 22-23
nents, 154 marquees. See cano pies and marquees
low-damping rubber bearings (seismic isolators), masonry íntills, /34-135, 171, 173,216-222. See
262 also masonry rehabilitalion
lower-bound strength, 41 in concrete-braced frames, 191
concrete components, 147-148, 149 unreinforced, 134-135
399
SEISMIC REHABILITATION OF EXISTING BUILDINGS
masonry rehabiJitation, 197-223,311. See also measuring performance. See verification 01' design
masonry infills; masonry walls assumptions
data collection for, 198-205; condition mechanical components, 311-329, 338-346. See
assessment, 202-205; properties of in also nonstructural componcnts
place components, 198-202 acceleration- and deformation-sensitive
foundation elements, 223 components, 320-321
nonSlructuraJ componeOls, 330 component evaluation, 318-319
masonry walls, 205-216. See also masonry condition assessmenl, 312-313
rehabililalion evaluation procedures, 321-327
anchorage lo, 222-223 hislorieal significance considerations,
reinforced: modeling paramelers and accept 313-318
ance crileria, 206-208; out 01' plane, 215; N onstructural Performance LeveJs, 17, 314
in plane, 213-215; Structural operational performance qua1itications, 18
Performance Levels, 13; unreinforced rehabilitation objectÍves, 319-320
walIs with reinforced cores, 209-210; rehabilitation procedures, 327
visual condition assessment, 202-203 seismic hazards, 3 16
simplified rehabilitation, 301-302 structural-nonstructural considerations, 320
mass reduction, 44 mechanical properties 01' seismic isolation sys
material properlies, 41 tems, 261-266
concrete materials, 143-148 mechanical pulse velocity testing (masonry),
masonry, 198-205 203-204
simplified rehabilitation, 309-311 metal deck diaphragms, 136-139
steel materials, 100-106 Structural Performance Levels and, 14
wood and light metal framing, 224-230 metal framíng. See steel componenls; wood and
materials. See construction materials light metal framing
mathematical modeling of rehabilitalÍon needs, metal lath, piaster on, 238, 240, 247-248
54-56. See also linear analysis procedures; metallurgical properties of steel components, 104
nonlinear analysis procedures methods 01' analysis. See analysis procedures
concrete components, 150-151 methods of seismic rehabilitation, 64
design review. See veritication of design mezzanine connections, improving, 309
assumptions minimum building separation, 47-48
diaphragms, 57 minimum collection of as-huilt information, 31-32
energy dissipalion syslems, 278, 279-280 concrete components, 146-147
foundation capacity, 56-57, 60, 83-96, 100 steel components, 105
multidireetional seismic effects, 59 minimum lateral displacement, seismic isolators,
overturning effecls, 60-61 271
seismic isolalion systems, 266-269 minimum lateral forces, seismic isolators, 271-272
soil-struelure ¡nteraction (SSI) effects, 58 mínimum site-specitic spectral amplitude, 27
slee! components, 107, 114-116 mínimum vertical load, seismic isolalOrs, 276
two- vs. three-dimensional, 54-55 mitigaling seismic-geologic sile risk, 6, 81-83
wood and light metal framing, 231-232 soil-structure interaetion (SS1), 58
Maximum Considered Earthquake (MCE) mitigation programs, using this standard I'or,
ground motion maps, 22-23, 292 350-354
seismic isolation systems, 269 model building types, 290-292, 352
simplitied rehabilitalion, 293 moment frames (concrete), 158-171
maximum displacement, seismic isolators, 271 Concrete Moment Frame building Lype, 29 1,
maxÍmum vertical load, seÍsmic isolators, 276 297
MCE (Maximum Considered Earthquake) post-tensioned concrete beam-column, 158,
ground molíon maps, 22-23, 292 166-167
seismic ¡solation systems, 269 reinforced concrete beam-column, 158,
simplilied rehabilitation, 293 159-166
mean return periods (earlhquakes), 8 simplified rehabilitation, 298-299
means 01' egress, 319-320 slab-column, 158-159, 166-171
400
ASeE/SEI 41-06
401
SEISMIC REHABILlT~TlON OF EXISTlNG BUILDINGS
402
ASCFJSEI 41-06
403
SEISMIC REHABILITATION OF EXISTING BUILDINGS
primary building components, 38-39. See also scismic isolation and energy dissipation
entries al building component syslems, 259
mathematical modeling, 56-57 steel elemenls encased in concrete, 106
steel components, \09-111 rehabilitation designo 54-56. See aiso linear
subassemblies based on experimental data, 52 analysis procedures; nonlinear analysis
primary costs of seismic rehabilitation, 353-354 procedures
prisms ror testing masónry strength, 199 concrete components, 150--151
probability 01' earLhquakes, 8-9 diaphragms, 57
exceedance probabilities, 22, 24-25 energy dissipalion systems, 278, 279-280
maps of, 22-23 foundalion capacity. 56-57, 60, 83-96, lOO
procedures for building analysis. See analysis multidireclional seismic effecls, 59
procedures nonslruclural components, 318-319
process of seismic rehabilitation, 64 overturning effecls, 60--61
projections from buildings, nonstructural. See preliminary, 34
canopies and marquees; parapets and requirements for, 44-48, 275; nonlinear
ornamentation analysis procedures, 321-327; nonstruc
properties of materials. See in-place materials test tural components, 318-319
ing; material properties review of. See verification oí' design
prototype tests assumplions
energy dissipation systems, 285-286 seismic isolalion syslems, 266-269
seismic isolation systems, 275-276 soil-struclurc ínteraction (S SI) ctfects, 58
pseudo-lateral force, 63-65 steel components, 107, 1 14-1 16
energy dissipation systems, 281 two- vs. three-dímensional, 54-55
pseudo-static analyses for slope stabílity, 81 wood and líght metal framíng, 231-232
PTFE-based seismic isolators, 265-266 rehabilitation goal s, 8-10, 351
pushover analysis. See NSP Enhanced Rehabilitation Objectives, 9
Limited Rehabilitation Objectives, 9;
QA (quality assurance). See construction quality prioritizing deficiency corrections, 294;
assurance seismic isolation and energy dissipation
QAP (quality assurance plan), 48,49 systems, 259
partial rehabilitation, 9-10,292; prioritizing
radiation damping, foundation damping due to, 98 deficiency correcLÍons, 294; simplificd
radiography of masonry, 204 rehabilitation, 33; typical dei1ciencies 1'or
ratio of response spectra (RRS), 97 model building types, 293-302
Rayleigh's method ror approximating building Partial Rehabilitation Objective, 9-10,292;
period, 62, 63 prioritizing deficiency corrections, 294;
re-entrant corners (diaphragms), 307 simplitied rehabilitation, 33; typical deti
Reduced Rehabilitation Objective, 9 ciencies for model building types,
reducing seismic risk, 6, 81-83 293-302
soil-structure interaction (SSI), 58 Reduced Rehabilitation O~icclive, 9
reduction of component cross sections, 43 rehabililation measures, 131
reduction of component irregularities, 43 concrete components, 158; cast-in-place
redundancy, adding, 296 diaphragms, 193-194; foundation com
regional seismicity. See level of seismicity poncnts, 196-197; frames with concrete
regulalions on seismic rehabilitation, controversy infills, 178; trames with masonry intills,
on,353 177; post-tensioned beam-column
rehabilitation, decision for, 2, 351. See also selec moment frames, 167; precast concrete
tion of Rehabilitation Objective frames, 172, 173; precast diaphragms,
rehabilitation, detined, I 194-195; reinforced beam-column
rehabilitalion, regulations on, 353 moment frames, 166; shear wal1s,
rehabilitation costs, 6, 350--351, 352-353 185-187; shear walls, precast,
estimating, 7-8. See aiso costs of 190--191; slab-column moment
rehabilitation frames, 171
404
ASCFlSEI 4 [-06
405
SEISMIC REHABILITATION OF EXISTING BUILDINGS
Response Spectrum Method (LDP), 66-67. See secondary effects 01' earthquakes, 317
also LDP (Linear Dynamic Procedure) site hazards. See geologic site hazards
energy dissipation systems, 282-283 site-specific characteristics, 27-28
seismic isolation systems, 269, 272 seismic isolation systems, 259-277
retaining walls (masonry), 223 analysis procedures, 271-273
return periods (earlhquakes), 8 design review, 275
revíew. See ínspection general considerations, 269-271
revitalízation 01' communíty, 353 mechanical properties and testíng, 261-269
rígid diaphragms, 57 system requirements, 273-275
risk mitigatíon programs, using this standard for, testing and design properties, 275-277
350-354 seismic joints between buildings, 47
RM walIs. See reinforced masonry walls seismic rehabilitalion. See en tries al rehabilitation
rocking on foundations, 88, 90 seismic weighl of building, 64
rod-braced wood frames, 258-259 seismicity level, 28, 319
rolling seismic isolalors, 261 selection 01' analysis procedure, 54. See also
roof-framing conneclions, improving, 309 analysis procedures; linear analysis procedures;
RRS (ratio of response spectra), 97 nonlinear analysis procedures
rubber bearings 1'or seismic isolation. See elaS seismic ísolation systems, 269-271
tomeric seismic isolators selection of Rehabilitation Objeclive, 2, 6, 7. See
also Rehabilitation Objective
SAC Joint Venture project, 3 active rehabilitalion programs, 352
sacrificial wind-restraint systems, 276 decision to rehabilitate, 2, 351. See also
safety regulations, controversy over, 353 selection of Rehabilitation
sampling material s for laboratory testing Objective
concrete components, 145-147 historic buildings, 354
masonry,2oo passive rehabilitatíon programs, 352
nonstructural components, 313 slructural vs. nonstructural components, 319
steel components, 104 separation between buíldings, 47-48
scheduling rehabilitation work, 351 sequence of tests. See test requirements
scragging, 262-263 seulement, differentíaL See differentíal
screws. See conneclions, wood and lighl metal compaclion
framing shallow bearing foundations, load-deformation
sculptures, exterior. See parapeis and characteristics, 88-94
ornamenlation shaJlow concrete foundalions, 195-197
secondary building components, 38-39. See also shared elements bctween buildings, 30-31,
entries at building component 47-48
mathematical modeling, 56-57 shear frictíon strength, concrete, 156
steel components, 109-111 shear modulus, masonry, 200
subassemblies based on experimental data, 52 shear stitTness. See stitfness (structural)
secondary eifects of earthquakes, 317 shear strength
Secretary 01' the Interior's slandards on historic concrete components, 156, 162, 169; shear
buildings, 353 walls, 184
Seed-Idriss procedure, 79 masonry, 200, 301; anchorage to masonry
seismic bracing, 317 walls, 222-223; default values,
seismic earlh pressure, 99-100 201-202; reinforced walls and wall piers,
seismic evaluation. See evaJuation 01' building 213
seismic hazards shear walls, 209-210
ground shaking, 22-27 building types Wilh, 291; Concrete Shear
miligaling risk, 6, 81-83; soil-structure Wall building types, 291, 297; Precasl
Ínteraction (SSI), 58 Concrete Frame with Shear Walls, 292,
nonstructural components, 316 299; Steel Frame building types,
probability of eanhquakes, 8-9; exceedance 290-291
probabilities, 22, 24-25; maps 01', 22-23 concrete, 178-187
406
ASCE/SEI 41-06
407
SEISMIC REHABILlTATION OF EXISTING BUILDINGS
spread footings and mats, 83-84, 223 diaphragms, 193; frames with concrete
sprinkler systems. See tire suppression piping infills, 177-178; trames with masonry
SPT blow count, 26, 79 intills, 174-176; post-tensioned beam
square reinforcing bars, 157 column moment frames, 167; precast
SSI (soil-structure interaction), 58-59, 96-99 concrete frames, 170; precast
stability díaphragms, 194; reinforced beam-col
dead loads to resíst overturning, 60 umn moment trames, 159-160; shear
historical considerations, nonslructural com walls, 181-184; shear walls, precast,
ponents, 313 189-190; slab-column momenl frames,
seismic isolation systems, 269, 274 168
soil slopes (Iandsliding), 81-83 diaphragms, deticiencies in, 307
stacks. See chimneys and stacks elastomeric seismic isolators, 262-264
stairs and fire escapes, 338 energy dissipation systems, 279
Nonstructural Performance Levels, 16, 314 foundation, 83-96; expected capacities,
preservation of egress, 319 83-86
Standard Penetration Test (SPT) blow count, 26, global structural stiffening, 43
79 masonry: intiJIs, 217-218, 220-222; rein
static analysis procedures, selection 01', 54. See forced walls, 213, 215; unreinforced
also linear analysis procedures; LSP; nonlinear walls, 210-211, 212
analysis procedures; NSP mathemalical modeling, 55, 56; primary and
static P-d effects, 58 secondary componenls, 56-57
Sleel Braced Frame building type, 290, 294 seísmic ísolalion systems, 266-268, 277
steel components, 100-144 steel components: braced frames, 129-131,
braced frames, 129-133. See also braced 306; cast or wrought iron, 143;
frames (steel); simplified rehabilitation, diaphragms, 135, 137-141; FR moment
306-307 tI'ames, 113-118; pile foundations, 142;
casl and wrought iron, 143 plate sheer walls, 133; PR momenl
condition improvement, 310 frames, 125-126
data collection for rehabilitation, 100-107 subassemblies based on experimental data,
diaphragms, 111, 135-142 51
frames with inli1ls, 134-135 vertical stitfness irregularilies, 36
general assumptions and requirements, wood and Iight metal framing, 226-227,
107-108 232; default values, 228-230; other wood
moment frames, 108-129. See also moment elements, 258; shear walls, 240-244,
frames (steel); conneclion types, 108, 248; sheathing, 240-241, 244-245,
112, 298; simplitied rehabilitation, 247-248,252-257; structural panel
297-298 sheathing, 235-236
pile foundations, 142-143 storage racks, 3 15, 346
plate sheer walls, 111, 116, 132, 133-134 storage vessels and waler heaters, 314
prefabricated panels, 331 stories, torsional moments at, 55-56
reinforcements for concrete: acceplance cri straight bars (concrete rcinforcement), 156-157
teria ror linear procedures, 155; develop straight-sheathed wood diaphragms, 249-250,
ment of, ] 56-157; properties measure 252-253, 256
ment, 145-149, 156 additional attachment, 252
Steel Frame building types, 290-291, 294-296 strain limits on concrete, 156
Steel Light Frame building type, 290, 294 strategies 01' rehabililation, 4-8, 42-44
Steel Moment Frame building type, 290, 294 historie buildings, 354
steel truss diaphragms, 139-140 simplitied rehabi1itation, 295-311
stiff diaphragms, 57 strength, bond. See bond strength
stitlening elements for masonry walls, 210 strength 01' building components, 41-42
stilfness (structural) concrete components, 153-154; bond
concrete components, 151-153; braced strength with steel, 157; braced trames,
frames, 191-192; cast-in-place 192; casl-in-place diaphragms, 193;
408
ASCFlSEI 41-06
409
SEISMIC REHABlLlTAll0N OF EXISTING BUILDlNGS
410
ASCFlSEI 41-06
411
GMI S.A.
INGENIEROS CONSULTORES
Civil Engineering
Seismology
Rehabilitation of Buildings
, 1_
.. -:
- - - -
ASCE
Ame,.ican Society of Civil Engineers
9 780784 408841