Test Report 260.2 - Earth Electrode Seal (4-Rod Seal) - DE784
Test Report 260.2 - Earth Electrode Seal (4-Rod Seal) - DE784
Test Report 260.2 - Earth Electrode Seal (4-Rod Seal) - DE784
PITTAS-DRAGNIS
LABORATORY TEST SERVICES
FOR LIGHTNING PROTECTION
AND EARTHING SYSTEMS
Page 1 of 9
REPORT IDENTIFICATION
Subject of Report: Earth Electrode Seal (4-Rod Seal) - DE784
Total pages of
9
report:
Page 2 of 9
VALIDITY CONDITIONS OF THE PRESENT DOCUMENT:
This type test report may not be reproduced other than in full, except with the prior written approval of
the issuing laboratory. This type test report only covers the samples submitted for test and does not
produce evidence of the quality for series production.
Table of Contents
Diameter: 350 mm
Single (Earth Electrode Seal (2-Rod Seal) – DE782) and double Earth Electrode
Seal (4-Rod Seal) - DE784) earth rod seals were identical, with the only difference
being the number of flanges included per kit.
Document
Description
Name and Version
European Standard Lightning Protection System Components(LPSC)
EN 62561-5 Part 1: Requirements for earth electrode inspection
housings and earth electrode seals. (IEC 62561-5:2017)
European Standard Protection against lightning – Part 1: General principles
EN 62305 -1
European Standard Protection against lightning – Part 3: Physical damage to
structures and life hazard
EN 62305 -3
PASS/
Required passing
Test Specimen Results of tests FAIL
criteria
Status
Applied air pressure 0.5 MPa
(5 bar).
PASS
260a, 260b, No bubbles noticed during the
Earth Rod
test. No leakage at the sealing
seal test No leakage should be 260c. points.
detected at the sealing points
at the completion of the test.
Installation instructions
should provide adequate
PASS
After inspection, installation
Installation information and ensure that 260a, 260b,
instructions were found
Instructions installer can select and install 260c. complete.
the materials in a safe and
suitable manner.
PASS
Markings made by moulding, moulded on the specimens.
Marking pressing or engraving are not
260a, 260b,
Identifying symbol of the product
test subjected to this test 260c. was present on the smallest
packing unit.
Electro-
N/A
magnetic Products covered by this standard are, in normal use, passive in respect
capability of electromagnetic influences (emission and immunity)
(EMC)
NOTE: The following products are made from the same material, have the same
properties and follow the same production procedure with Earth Electrode Seal (4-Rod
Seal) - DE784: