CGa Series 3 Boiler Manual 0520
CGa Series 3 Boiler Manual 0520
CGa Series 3 Boiler Manual 0520
This manual must only be used by a qualified heating installer/service technician. Before installing, read all
instructions, including this manual, and any related supplements. Perform steps in the order given. Failure to comply
could result in severe personal injury, death or substantial property damage.
How it works . . .
① Control module
The control module responds to signals from the room thermostat and boiler limit circuit to operate the boiler
circulator, pilot burner, gas valve and vent damper. When room thermostat calls for heat, the control module starts
the system circulator and activates the vent damper (causing it to drive open).
When the vent damper has opened completely, the control module opens the pilot valve and activates pilot
ignition spark.
For natural gas, the control module allows up to 15 seconds to establish pilot flame. If flame is not sensed within
15 seconds, the control module will turn off the gas valve, flash the Flame light, and immediately start a new cycle.
This will continue indefinitely until pilot flame is established or power is interrupted. Once pilot flame is proven,
the control module opens the gas valve to allow main burner flame.
For propane gas, the control module allows up to 15 seconds to establish pilot flame. If flame is not sensed within
15 seconds, the control module will turn off the gas valve, flash the Flame light, wait 1 minute, then start a new
cycle. If flame is still not sensed after the second trial, two more attempts are made with 5 minute and 60 minute
wait periods in between. If flame is not sensed after 4 tries, control will lockout and flash all lights. Control must
be manually reset to place back into service. Once pilot flame is proven, the control module opens the gas valve to
allow main burner flame.
When the room thermostat is satisfied, the control module turns off the gas valve and deactivates the vent damper
(causing it to close).
The control module indicator lights show normal sequence when the lights are on steady. When a problem occurs,
the control module flashes combinations of lights to indicate the most likely reason for the problem. See page 49
for details.
② Transformer
The control transformer reduces line voltage to 24 volts for the gas valve and limit circuit.
③ Draft hood
The draft hood provides a minimum draft for the boiler, assuring adequate air for combustion if installed in
accordance with manual and not modified in any way.
④ Spill switch
The spill switch will shut down the boiler (requiring manual reset of the switch reset button) if the vent system
becomes blocked.
⑥ Boiler circulator
The boiler circulator circulates water through the external (system) piping. The circulator is shipped loose, and
can be mounted on either the boiler supply or return piping. The factory-installed circulator wiring harness
provides ample length for either location. NOTE — The control module provides a pump exercising routine. If
the boiler is not operated for 30 days, the control module will power the circulator for 30 seconds, then turn off.
⑦ Vent damper
The vent damper closes during off cycles to reduce heat loss from the house up the vent.
Contents
How it works..................................................... 2-3
Hazard definitions................................................ 4
Please read before proceeding............................. 5
1 Prepare boiler location....................................6–11
2 Prepare boiler................................................ 12-15
3 Water piping.................................................. 16-25
4 Gas piping.......................................................... 26
5 Field wiring........................................................ 27
6 Start-up......................................................... 28-32
7 Check-out procedure.......................................... 33
8 Department of Energy Compliance .................... 34
9 Operation – spark-ignited pilot boilers........... 34-41
10 Service and maintenance.............................. 42-47
11 Troubleshooting:
Spark-ignited pilot boilers............................. 48-56
12 Replacement parts........................................ 58-63
13 Dimensions and ratings................................. 64-65
Hazard definitions
The following defined terms are used throughout this manual to bring attention to the presence of hazards of various
risk levels or to important information concerning the life of the product.
Indicates presence of hazards that will cause severe personal injury, death or substantial property
damage.
Indicates presence of hazards that can cause severe personal injury, death or substantial property
damage.
Indicates presence of hazards that will or can cause minor personal injury or property damage.
Indicates special instructions on installation, operation or maintenance that are important but not
related to personal injury or property damage.
If any part of a boiler, burner or its controls has Saltwater Damage — The exposure of boiler components to
been sprayed with or submerged under water, saltwater can have both immediate and long-term effects. While the
either partially or fully, DO NOT attempt to op- immediate effects of saltwater damage are similar to those of fresh-
erate the boiler until the boiler has been either water (shorting out of electrical components, washing out of critical
replaced or completely repaired, inspected, and lubricants, etc.), the salt and other contaminants left behind can lead
you are sure that the boiler and all components to longer term issues after the water is gone due to the conductive
are in good condition and fully reliable. and corrosive nature of the salt residue. Therefore, Weil‑McLain
equipment contaminated with saltwater or polluted water will no
Otherwise, by operating this boiler, you will cause
longer be covered under warranty and should be replaced.
a fire or explosion hazard, and an electrical shock
hazard, leading to serious injury, death, or substan- Electrical Damage — If any electrical component or wiring
tial property damage. See the instructions at right. came into contact with water, or was suspected to have come into
contact with water, replace the boiler with a new Weil-McLain boiler.
Failure to adhere to the guidelines below can result in severe personal injury, death or substantial property damage.
The CGa boiler gas manifold and controls meet safe operating and
other performance criteria when boiler underwent tests specified
in ANSI Z21.13 – latest edition.
Figure 1a
Recommended
service
clearances
(see WARNING
below)
Flooring
The CGa boiler is approved for installation on combustible
flooring, but must never be installed on carpeting.
Do not install boiler on carpeting even
If any clearance is less than in Figure 1a, pro- if foundation is used. Fire can result,
vide openings for combustion and ventilation causing severe personal injury, death
air located on the wall or door opposite the or substantial property damage.
boiler FRONT (see Figure 1b).
These openings must be located as shown in Figure 1b to provide
proper air flow around the boiler. The free area of each opening Foundation
(after deducting for louvers) must be at least one square inch 1. Provide a solid brick or minimum 2-inch thick concrete
per 1,000 Btuh of boiler input. If the building is of unusually foundation pad if any of the following is true:
tight construction (see page 11 for definition), the air openings • floor can become flooded.
must connect directly to outside or the building must have air
openings to the outside as specified on page 11. • the boiler mounting area is not level.
2. Minimum dimensions are 25” length by:
If clearances are equal to or greater than Figure 1a, see pages 10
and 11 for location and sizing of combustion air openings. Minimum foundation width:
Failure to comply can result in severe personal injury, death or
CGa-25/3 12” CGa-6 21”
substantial property damage and reduced boiler life.
CGa-4 15” CGa-7 24”
CGa-5 18” CGa-8 27”
Required MINIMUM clearances (Fig. 1b)
Never install the boiler in a space with clear- Residential garage installations
ances less than the minimum clearances shown Take the following special precautions when installing the
in Figure 1b. Failure to comply can result in severe boiler in a residential garage. If the boiler is located in a
personal injury, death or substantial property dam- residential garage, per ANSI Z223.1, – latest edition:
age and reduced boiler life.
• Mount the boiler a minimum of 18 inches above the
1. Hot water pipes: at least ¹⁄₂ inch from combustible material. floor of the garage to assure the burner and ignition
2. Single-wall vent pipe: at least 6 inches from combustible mate- devices will be no less than 18 inches above the floor.
rial.
3. Type B double-wall metal vent pipe: refer to vent manufacturer’s • Locate or protect the boiler so it cannot be damaged
recommendation for clearances to combustible material. by a moving vehicle.
Failure to follow all instructions can result in flue gas spillage and carbon monoxide emissions, causing severe
personal injury or death.
Inspect existing chimney before installing boiler. Failure to clean or replace perforated pipe or tile lining will cause
severe personal injury or death.
Do not alter boiler draft hood or place any obstruction or non-approved vent damper in breeching or vent system.
CSA certification will become void. Flue gas spillage and carbon monoxide emissions will occur causing severe
personal injury or death.
Please review the following information on potential Refer to Table 1 for products and areas which may cause
combustion air contamination problems. contaminated combustion air.
To prevent potential of severe personal injury or death, check for products or areas listed
below before installing boiler. If any of these contaminants are found:
• remove contaminants permanently
— OR —
• isolate boiler and provide outside combustion air. See national, provincial or local codes
for further information.
Adhesives used to fasten building products and other Buildings under construction (where air is contaminated
similar products with particulates)
Combustion air opening location and sizing Figure 2 Air openings to interior spaces
requirements depend on the clearances around
the boiler. Check the boiler placement compared to ✷
✷ Figure 1a, page 7.
If all clearances are at least equal to Figure 1a,
page 7, apply the sizing and placement of openings
given on pages 10 and 11.
If ANY clearance is less than Figure 1a, page 7,
you must provide air openings sized and located as
shown in Figure 1b, page 7. DO NOT apply the sizing
and location information shown on page 10 or 11.
Table 2 Manifold orifice sizing 2. On gas manifold, mark location of main burner with
attached pilot assembly.
Location Natural gas 3. Remove main burner with attached pilot assembly
from manifold. Remove all remaining burners.
U.S. 0-2,000 ft. over 2,000 ft.
2.00 mm (Note 1) 4. Remove and discard all main burner orifices in gas
manifold.
Canada 0-2,000 ft. 2,000-4,500 ft.
5. Apply a small amount of pipe dope to each of the
2.00 mm 1.90 mm new orifices and install in the manifold. Make sure
the orifices are aligned correctly, not cross-threaded
in the manifold tappings.
Location Propane gas Use only pipe dope compatible with
U.S. 0-2,000 ft. over 2,000 ft. propane gas, even if boiler is to be
CGa 25 #61 (Note 1) operated on natural gas. Failure to
comply could result in severe per-
CGa 3-8 #56 (Note 1)
sonal injury, death or substantial
Canada 0-2,000 ft. 2,000-4,500 ft. property damage.
CGa 25 #61 .95mm
CGa 3-8 #56 #57 6. Reinstall main burner with attached pilot assembly
at location marked on gas manifold. Reinstall all
remaining burners.
Note 1: For elevations above 2,000 feet, contact your
Weil-McLain sales office for details. 7. Follow check-out procedure, Section 7, page 33.
Figure 6 Install spill switch Figure 7 Spill switch with wire harness
Minimum clearances
Undersized expansion tanks cause system water to be lost from relief valve and makeup water
to be added through fill valve. Eventual section failure can result.
Use Figure 9 or Figure 10 only for single-zone systems designed for return water at least
130°F. For systems with low return water temperature possible, such as converted gravity
systems and radiant heating systems, refer to the special piping suggestions of pages 20-25.
Failure to prevent low return water temperature to the boiler could cause corrosion of the boiler
sections or burners, resulting in severe personal injury, death or substantial property damage.
Radiant heating system piping should include a means of regulating the boiler return water
temperature and the system supply temperature (such as provided by an injection pumping
control). Boiler return water temperature will be adequately controlled using the methods
shown in this manual provided the system supply temperature is relatively constant.
DO NOT apply the methods in this manual if the system is equipped with an outdoor reset
control. Instead, provide controls and piping which can regulate the boiler return water
temperature at no less than 130°F regardless of system supply temperature. Contact your
Weil-McLain representative for suggested piping and control methods. Failure to prevent
cold return water temperature to the boiler could cause corrosion damage to the sections or
burners, resulting in possible severe personal injury, death or substantial property damage.
Figure 11 Zoning with circulators — return water Figure 12 Zoning with zone valves — return water
130°F or higher. 130°F or higher.
1 Boiler isolation (balancing) 10 Automatic air vent (with diaphragm-type expansion tank), or connect
valves to tank fitting (closed-type expansion tank). DO NOT use an automatic
air vent when using closed-type expansion tank. It would allow air to
2 Flow/check valve leave the system, causing waterlogging of the expansion tank.
11 Fill valve
3 System or zone circulator
12 Diaphragm-type or bladder-type expansion tank, if used (For closed-
5 Zone valve type expansion tank, pipe from top of air separator to tank fitting as in
Figure 10, page 17.)
6 Drain valve 13 Air separator and automatic vent, if used (Note that the fill valve must
always be connected to the expansion tank, regardless of location of
9 Relief valve expansion tank circulator or air separator.
For systems with possible low return-water temperature (such as converted gravity systems,
radiant heating systems and heat pump systems), refer to the special piping suggestions of
Figures 13 – 17, as applies. Failure to prevent sustained low return water temperature to
the boiler could cause corrosion of the boiler sections, resulting in severe personal injury,
death or substantial property damage.
Failure to prevent low return water temperature to the boiler could cause corrosion
of the boiler sections or burners, resulting in severe personal injury, death or substantial
property damage.
Radiant heating system piping should include a means of regulating the boiler return
water temperature and the system supply temperature (such as provided by an injec-
tion pumping control).
Boiler return water temperature will be adequately controlled using the methods shown
in this manual provided the system supply temperature is relatively constant.
DO NOT apply the methods of this manual if the system is equipped with an outdoor reset
control. Instead, provide controls and piping which can regulate the boiler return water
temperature at no less than 130°F regardless of system supply temperature. Contact your
Weil-McLain representative for suggested piping and control methods.
Failure to prevent cold return water temperature to the boiler could cause corrosion
damage to the sections or burners, resulting in possible severe personal injury, death or
substantial property damage.
1 Boiler isolation (balancing) valves 10 Automatic air vent (with diaphragm-type expansion
tank), or connect to tank fitting (closed-type expan-
2 Flow/check valve sion tank). DO NOT use an automatic air vent when
using closed-type expansion tank. It would allow
3 System or zone circulator (circulator should cycle
with zone valve and switches, using circulator valve air to leave the system, causing waterlogging of the
or zone control panel) expansion tank.
BOILER-bypass piping to the boiler. (When setting the valves without gauge
4a installed — using cold or room temperature water
method — assume the return water temperature to be 60°F. Set
This piping method (Figure 15 or 16, page 23) is called the valves so gauge 8 reads at least 120°F.
a boiler-bypass because part of the circulator flow is Gauge 4b is optional on converted gravity systems, but
bypassed around the boiler (through valve 7a). This required on radiant heating systems — to display the
method reduces the flow rate throughout the boiler, in water temperature being supplied to the radiant tubing.
order to raise the average water temperature in the boiler
enough to prevent flue gas condensation. Boiler-bypass Gauge 8 is required on all systems to assure reliable
piping is effective for some boilers — including the adjustment of the bypass valves. The boiler-mounted
CGa — provided the flow rates are adjusted according temperature/pressure gauge can be used if a separate
to the instructions following. temperature gauge is not installed.
Figures 15 and 16 are alternative piping suggestions
for converted gravity (large water content or steam Valve adjustment
systems) or radiant heating system — for use when
primary/secondary piping can’t be applied. (Figure 17, 1. Start with valve 7a fully closed and 7b fully open.
page 25, is another alternative, using system bypass in 2. Gradually open valve 7a while closing valve 7b
place of boiler-bypass piping. Figure 17 however, is until the temperature at gauge 8 reads 60 °F higher
not suitable for radiant heating applications because it than gauge 4a. A minimum 60°F temperature rise
does not protect the radiant system from possible high through the boiler assures a low enough flow rate
water temperature.) and high enough average temperature to prevent
Boiler-bypass piping keeps system flow rate as high as condensation even with low system return water
possible and temperature drop as low as possible, help- temperature.
ing to equalize the building heat distribution.
3. Valve 7a regulates the system flow rate, while valve
7b regulates the boiler flow rate.
Temperature gauges
Gauge 4a is optional if the bypass valves will be ad- 4. The boiler-mounted temperature/pressure gauge
justed using cold (or room temperature) return water may be used in place of a separate gauge 8.
Failure to prevent low return water temperature to the boiler could cause corrosion
of the boiler sections or burners, resulting in severe personal injury, death or substantial
property damage.
Radiant heating system piping should include a means of regulating the boiler return
water temperature and the system supply temperature (such as provided by an injec-
tion pumping control).
Boiler return water temperature will be adequately controlled using the methods shown
in this manual provided the system supply temperature is relatively constant.
DO NOT apply the methods of this manual if the system is equipped with an outdoor reset
control. Instead, provide controls and piping which can regulate the boiler return water
temperature at no less than 130°F regardless of system supply temperature. Contact your
Weil-McLain representative for suggested piping and control methods.
Failure to prevent cold return water temperature to the boiler could cause corrosion
damage to the sections or burners, resulting in possible severe personal injury, death or
substantial property damage.
1 Boiler isolation (balancing) valves 10 Automatic air vent (with diaphragm-type expansion
tank), or connect to tank fitting (closed-type expansion
2 Flow/check valve tank). DO NOT use an automatic air vent when using
closed-type expansion tank. It would allow air to leave
3 System or zone circulator the system, causing waterlogging of the expansion tank.
4 System temperature gauges
11 Fill valve
5 Zone valve
12 Diaphragm-type or bladder-type expansion tank, if
6 Drain valve used (For closed-type expansion tank, pipe from top
of air separator to tank fitting as in Figure 10.)
7 System temperature valves (see instructions
to the left for adjusting valves)
13 Air separator and automatic vent, if used (Note that the
8 Blend temperature gauge fill valve must always be connected to the expansion
tank, regardless of location of expansion tank, circulator
9 Relief valve or air separator.)
Failure to prevent low return water temperature to the boiler could cause corrosion
of the boiler sections or burners, resulting in severe personal injury, death or substantial
property damage.
Radiant heating system piping should include a means of regulating the boiler return
water temperature and the system supply temperature (such as provided by an injection
pumping control).
Boiler return water temperature will be adequately controlled using the methods shown
in this manual provided the system supply temperature is relatively constant.
DO NOT apply the methods of this manual if the system is equipped with an outdoor reset
control. Instead, provide controls and piping which can regulate the boiler return water
temperature at no less than 130°F regardless of system supply temperature. Contact your
Weil-McLain representative for suggested piping and control methods.
Failure to prevent cold return water temperature to the boiler could cause corrosion
damage to the sections or burners, resulting in possible severe personal injury, death or
substantial property damage.
9 Relief valve
11 Fill valve
4 Gas piping
Table 4 Pipe capacity for 0.60 specific gravity natural gas Figure 19 Gas supply piping
5 Field wiring
For your safety, turn off electrical power supply at ser- the wiring diagram shown in Figure 25b, page 37.
vice entrance panel before making any electrical con- For other devices, refer to manufacturer’s specifica-
nections to avoid possible electric shock hazard. Failure tions. Wiring diagram on boiler gives setting for
to do so can cause severe personal injury or death. control module and gas valve. Also see instructions
with thermostat.
Wiring must be N.E.C. Class 1.
If rollout thermal fuse element wire as supplied with boiler
DHW
must be replaced, type 200°C wire or equivalent must be Connect DHW aquastat as shown in wiring below.
used. If other original wiring as supplied with boiler must Economy function isn’t utilized with DHW input.
be replaced, use only type 105°C wire or equivalent.
Boiler must be electrically grounded as required by Junction box (furnished)
National Electrical Code ANSI/NFPA 70 – latest edition. 1. Connect 120 VAC power wiring (Figure 20).
2. Fused disconnect or service switch (15 amp. recom-
mended) may be mounted on this box. For those
Installation must comply with: installations with local codes which prohibit instal-
1. National Electrical Code ANSI /NFPA 70 – latest edition lation of fused disconnect or service switch on boiler,
and any other national, state, provincial or local codes or install a 2 x 4 cover plate on the boiler junction box
regulations. and mount the service switch remotely as required
2. In Canada, CSA C22.1 Canadian Electrical Code Part 1, by the code.
and any local codes.
Wiring connections Wiring multiple zones
Refer to zone valve manufacturer’s literature for wiring
Boiler is shipped with controls completely wired, except spill and application. A separate transformer is required to
switch and vent damper. Refer to wiring diagrams shown power zone valves. Zoning with circulators requires a
on page 36 for spark-ignited pilot boiler. relay for each circulator.
DO NOT connect directly from 3-wire
Thermostat zone valves to the T-T terminals on
1. Connect thermostat as shown on wiring diagram on the boiler. When using 3-wire zone
boiler. valves, install an isolation relay. Connect
2. Install on inside wall away from influences of drafts, hot the zone valve end switch wires to the
or cold water pipes, lighting fixtures, television, sunrays isolation relay coil. Connect the isolation
or fireplaces. relay contact across the boiler T-T
3. If thermostat has a heat anticipator, set heat anticipator terminals. Failure to comply can result in
in thermostat to match power requirements of equip- damage to boiler components or cause
ment connected to it. If connected directly to boiler, set unreliable operation, resulting in severe
for 0.1 amps plus gas valve current. See information on property damage.
Figure 20
6a Start-up — preparation
2. Boiler temperature adjustment set below boiler 5. Incoming gas pressure less than:
water temperature? 5” w.c. for natural gas? 11” w.c. for propane gas?
3. Thermostat set below room temperature? 6. If none of the above corrects the problem, refer to
Troubleshooting, Section 11 of this manual.
❏
7 Check-out procedure — checklist
Boiler and heat distribution units filled with water? ❏ Set Boiler Temp adjustment knob to system temperature re-
quirements. Adjust balancing valves and controls to provide
❏ Automatic air vent, if used, open one full turn? design temperature to system.
❏ Air purged from system? ❏ Set Economy mode, fully clockwise.
❏ Air purged from gas piping? Piping checked for leaks?
❏ For multiple zones, adjust flow so it is about the same in
❏ Correctly sized manifold orifices installed? Refer to Table 2, each zone.
page 12 to check size and fuel type.
❏ Verify thermostat heat anticipator (if available) set
Correctly sized manifold orifices must be used. properly? Refer to Field wiring, manual Section 5, page 27,
Failure to do so will cause severe personal Thermostat(s).
injury, death or substantial property damage.
❏ Cycle boiler with thermostat — Raise to highest setting and
❏ Followed operating instructions on boiler or in manual verify boiler goes through normal start-up cycle. Lower to
Section 9 for proper start-up? lowest setting and verify boiler goes off.
❏ Proper burner flame observed? Refer to Check burner flame,
manual Section 6d. ❏ Cycle DHW Aquastat if used.
❏ Test temperature limit — While burners are operating, turn ❏ Measure natural gas input:
Boiler Temp adjustment knob counterclockwise until display a. Operate boiler 10 minutes.
reading is below actual boiler water temperature. Burners
should go off while circulator continues to operate. Turn b. Turn off other appliances.
Boiler Temp adjustment knob clockwise until display read- c. At natural gas meter, measure time (in seconds) re-
ing is above boiler water temperature and ignition sequence quired to use one cubic foot of gas.
should resume.
d. Calculate gas input:
❏ Test low water cut off – While burners are operating, press
and hold “LWCO TEST” button on control. Burners should
go off while circulator continues to operate and LWCO light 3600 x 1000
= Btuh
should turn ON. Release “LWCO TEST” button and ignition number of seconds from step c
sequence should resume.
❏ Test field-installed controls — If the boiler has an additional e. Btuh calculated should approximate input rating on
low water cutoff, additional high limit or other controls, test boiler rating label.
for operation as outlined by manufacturer. Burners should ❏ Check manifold gas pressure by connecting manometer to
be operating and should go off when controls are tested. downstream test tapping on main gas valve. Manifold pres-
When controls are restored, burners should reignite.
sure for natural gas should be 3.5" w.c. and for propane gas
❏ Button on spill switch pushed in? should be 10" w.c.
❏ Test ignition system safety device
❏ Observe several operating cycles for proper operation.
Connect manometer to outlet side of gas valve. Start boiler,
allowing for normal start-up cycle to occur and main burn- ❏ Set room thermostat to desired room temperature.
ers to ignite. With main burners on, manually shut off gas
supply at manual main shutoff gas valve. Burners should go ❏ Fill in Installation and service certificate below?
off. Open manual main shutoff gas valve. Manometer should ❏ Review all instructions shipped with this boiler with owner
confirm there is no gas flow. Pilot will relight, flame sensing or maintenance person. Return instructions to envelope and
element will sense pilot flame and main burners reignite. give to owner or place in pocket inside front panel in boiler.
THIS OVERRIDE MUST NOT BE USED UNLESS AT LEAST ONE OF THE FOLLOWING CONDITIONS IS TRUE:
• An external energy management system is installed that reduces the boiler water temperature as the heating load
decreases.
• This boiler is part of a modular or multiple boiler system having a total input of 300,000 BTU/hr or greater.
• This boiler is equipped with a tankless coil.
1. Standby
• Waiting for call for heat NO —
2. Call for heat
• Circulator on YES —
3. Limit circuit
• Limit controls closed YES —
4. Damper circuit
• Damper proven open YES —
5. Flame proven *
• Gas valve open YES 15 sec
• Ignitor remains on
• Boiler producing heat
6. Limit cycle
• Limit circuit open YES —
• Gas valve closed
7. Flame outage *
• Flame out YES —
• Boiler recycles
8. Thermostat satisfied
NO —
• Circulator off
9. Circulator exercise routine
• Circulator turns on for 30 seconds if NO 30 sec
boiler not operated for 30 days
10. LWCO circuit
• LWCO circuit open YES/NO —
= ON = OFF
* See Section 9, Items 3b and 3c for controls response to failure to prove pilot flame.
Control will lockout under the following conditions: Control will reset after these lockouts :
• Line voltage polarity is reversed • 1 hour waiting period
• Stray voltage is sensed on thermostat line • Opening and closing of thermostat circuit for 2 to 20 seconds
• Damper end switch not proven within 5 minutes from thermostat • Removal of 120 VAC power for 2 to 20 seconds
call for heat
• Flame is sensed when it shouldn’t be there
CAUTION DO NOT connect directly from 3-wire zone valves to the T-T terminals on the
boiler. When using 3-wire zone valves, install an isolation relay. Connect the zone valve
end switch wires to the isolation relay coil. Connect the isolation relay contact across the
boiler T-T terminals. Failure to comply can result in damage to boiler components or
cause unreliable operation, resulting in possible severe property damage.
NOTICE • The control module is polarity-sensitive to the incoming 120 VAC power. If polarity is
reversed, control will flash the POWER light when powered and will not cycle boiler.
• All contacts shown without power applied.
• Connector and status light locations/orientations may vary.
FIELD
120 VAC — Hot Neutral Gnd WIRING
Y
TEST
Y THERMOSTAT
ROLLOUT
TFE
70 80
60
BL W
60
R
80
70
O R G BK BK
FIELD
OUTDOOR "C" To Black WIRING Black
TEMPERATURE R
Ground
"A" Screw
SENSOR
(if used) TEMPERATURE/ "B"
LWCO SENSOR W
OFF
Terminal block
ON
CONTROL
Legend for ladder wiring diagram MODULE
120 VAC field wiring HIGH 120 VAC
Low voltage field wiring VOLTAGE SECTION CIRCULATOR
120 VAC factory wiring
Low voltage factory wiring
PILOT
High voltage spark ignition wiring
IGNITION
Ground connectors
ELECTRODE
120 VAC
Table G: Gas valve terminals and anticipator settings
Anticipator
Gas valve "A" "B" "C" amps
Honeywell VR8204 MV/PV MV PV 0.6 24 VAC
Honeywell VR8304 MV/PV MV PV 0.8
White-Rodgers 36E 2 1 3 0.64
24 VAC
R Power CONSTANT
White-Rodgers 36C 2–4 * 1 3 0.7
THERMOSTAT
* Terminals 2–4 are factory-jumpered on the
White-Rodgers 36C gas valve. R Tstat–Circ
VENT
1. All wiring must be installed in accordance with: 24 VAC DAMPER
A. U.S.A. — N.E.C. And any other national, state, CALL
or local code requirements. DHW (if used) FOR HEAT
B. Canada — C.S.A. C22.1 C.E.C. Part 1 and
any other national, provincial, or local code TEMPERATURE
requirements. LWCO SENSOR
2. Pilot lead wires are not field replaceable.
Replace pilot assembly if necessary. ROLLOUT SPILL
3. If any of the original wire as supplied with the TFE SWITCH
appliance must be replaced, use minimum 105 R Limit
°C wire or equivalent. Exception — wires to a Additional PILOT GAS
rollout TFE must be 200 °C or equivalent. limits (note 7) VALVE
4. Thermostat anticipator setting (single zone) — Outdoor Temperature
Sensor (if used) "C"
see Table G for anticipator setting, depending "A"
on which gas valve is installed in boiler.
"B"
5. For multiple zoning, use either zone valves or R Damper
circulators. Refer to the component manufac- MAIN GAS
DAMPER END SWITCH
turer's instructions and this manual for applica- (INTERNAL TO DAMPER) VALVE
tion and wiring suggestions. See Table G
6. Refer to control component instructions PILOT FLAME R Flame
packed with the boiler for application informa- SENSOR
tion. HIGH
7. Wire any additional limit controls (low water VOLTAGE R LWCO
cut-off, additional high limit, etc.) in series with
boiler rollout TFE and spill switch as shown. Control Module
Low Voltage Section
59374a+LWCO
9b Operating instructions
• Spark pilot • Natural gas • Propane gas
CGa-25 to CGa-8 • Gas valve: Honeywell VR8204/VR8304
9b Operating instructions
CGa-25 to CGa-6 • Spark pilot • Natural gas
• Gas valve: Robertshaw 7200
9b Operating instructions
CGa-25 to CGa-6 • Spark pilot • Natural gas
• Gas valve: White-Rodgers 36E
9b Operating instructions
CGa-7 to CGa-8 • Spark pilot • Natural gas
• Gas valve: White-Rodgers 36C
Start-up:
• Perform start-up per manual
Every 6 months • Operate relief valve
Check/test:
• Gas piping
• Cold fill and operating pressures
• Air vents and air elimination
• Limit controls and cutoffs
• Expansion tank
End of season • Shut down procedure
• Boiler relief valve
Review:
• Review with owner
Follow the Service and maintenance procedures given throughout this manual and in component
literature shipped with the boiler. Failure to perform the service and maintenance could result in
damage to the boiler or system. Failure to follow the directions in this manual and component
literature could result in severe personal injury, death or substantial property damage.
Do not use petroleum-based cleaning or sealing 1. Visually inspect entire flue gas venting system
compounds in boiler system. Severe damage to for blockage, deterioration or leakage. Repair any
boiler will occur, resulting in substantial property joints that show signs of leakage in accordance with
damage. vent manufacturer’s instructions.
6. Remove radiation plates hanging between sections. 11. Reinstall radiation plates.
7. Remove burners from base. Brush and vacuum burners to 12. Replace collector box/transition assembly. Seal with sealant.
remove all dust and lint. Verify that all burner ports are free Obtain gas-tight seal to prevent flue gas spillage and carbon
of debris. monoxide emissions, resulting in severe personal injury or
death.
8. Place newspapers in base of boiler to collect soot.
13. Replace insulation and jacket top panel.
9. Clean between sections with wire flue brush.
14. Start up boiler following Section 6 of this manual and the
10. Remove newspaper and soot. Vacuum or brush base and
boiler Operating instructions (Section 9b). Excessive sooting
surrounding area.
indicates improper gas combustion. If found, check for proper
combustion and make any necessary adjustments.
Check the following: pliers on flat shaft between damper and actuator.
Boiler will fire. Verify that damper service switch is
1. Wire connectors to control module are securely in Hold Damper Open position. (Figure 28)
plugged in at module and originating control.
3. Do not leave vent damper permanently in this
2. Gas pressures: position. Replace actuator immediately. If vent
damper is left in open position, boiler will not oper-
a. With boiler off — 13” w.c. maximum natural
ate at published efficiencies.
or propane gas pressure upstream of gas valve.
b. With boiler on: If troubleshooting chart recommends replacing actua-
• 5” w.c. minimum natural gas pressure or tor and actuator is not immediately available, damper
11” w.c. propane gas pressure upstream of blade can be fixed in an open position to allow boiler
gas valve. operation. Follow these instructions only in case of no
• 3.5” w.c. minimum natural gas pressure or heat or damper actuator malfunction. See Figure 28.
10” w.c. propane gas pressure downstream
tapping on gas valve — Can be adjusted by 1. Turn off power to boiler.
regulator on gas valve.
Failure to turn off power to boiler can
result in severe personal injury, death
In event of vent damper or substantial property damage.
failure:
2. Refer to vent damper manufacturer’s instructions
Effikal or Field Controls damper for procedure to fix vent damper in open position.
If troubleshooting chart recommends replacing actua-
tor and actuator is not immediately available, damper 3. Turn on power to boiler.
blade can be fixed in an open position to allow boiler
operation. Manually turning blade can cause actuator 4. Using wrench or pliers on flat shaft section, manu-
damage. Follow these instructions only in case of no ally rotate damper blade until green light turns on.
heat or damper actuator malfunction. Boiler will fire. (Figure 28)
1. Move damper service switch to Hold Damper Open 5. Do not leave vent damper permanently in this posi-
position. Apply call for heat to boiler. Damper blade
tion. Replace actuator immediately. If vent damper
should then rotate to open position and boiler will
fire. is left in open position, boiler will not operate at
published efficiencies.
2. If step 1 does not open damper, manually rotate
damper blade to open position using wrench or
Figure 28 Manually
opening the
vent damper
• Verify proper operation after servicing. • See vent damper manufacturer’s instructions packed with vent damper
for additional information. Failure to comply could result in severe personal injury, death or substantial property
damage.
–– Usually indicates reversed 120 VAC polarity if POWER light flashes by itself ––
Electrical shock hazard — Wherever you see ▲ TURN OFF POWER ▲, follow the instructions. Failure to follow
instructions could result in severe personal injury, death or substantial property damage.
Electrical shock hazard — Wherever you see ▲ TURN OFF POWER ▲, follow the instructions. Failure to follow
instructions could result in severe personal injury, death or substantial property damage.
• Disconnect the two external wires connected to the boiler • If a voltage does occur under any condition, check and
thermostat leads (two black low voltage leads in J-box). correct the external wiring. (This is a common problem
when using 3-wire zone valves).
• Connect a voltmeter across these two incoming wires.
Close each thermostat, zone valve and relay in the external • Once the external thermostat circuit wiring is checked and
circuit one at a time and check the voltmeter reading corrected if necessary, reconnect the external thermostat
across the wires. circuit wires to the boiler thermostat wires and allow the
boiler to cycle.
• There should NEVER be a voltage reading.
Did you find a voltage across the two external thermostat circuit wires ?
Yes No
• Leave external boiler thermostat connection wires • If no voltage is found under any condition on the external
disconnect from boiler. thermostat circuit, connect the two boiler thermostat
connection leads together (or jumper the boiler aquastat
• Troubleshoot the external thermostat circuit until you find T-T terminals).
the source of the stray voltage. (Pay close attention to
the wiring connections to 3-wire zone valves).
• Turn off power to the boiler for 1 minute.
• Correct the problem and repeat the voltmeter test above, • Turn on power and allow boiler to cycle.
verifying there is no longer a voltage reading under any
condition in the external thermostat circuit.
Do the TSTAT and POWER lights still flash ?
No Yes
• Boiler should now operate per normal sequence of • Replace control module.
operation shown in Figure 24, page 35. • Retest.
–– If POWER light is flashing: Usually indicates vent damper failed to prove open within 45 seconds ––
–– If POWER light is steady: Usually indicates vent damper closed during run cycle ––
Electrical shock hazard — Wherever you see ▲ TURN OFF POWER ▲, follow the instructions. Failure to follow
instructions could result in severe personal injury, death or substantial property damage.
• Reset boiler control by turning off power at service switch or turning down thermostat for 2 to 40 seconds.
• Thermostat should call for heat and appropriate zone valves open. The TSTAT CIRC and LIMIT lights should come on.
• Wait 45 seconds.
Does vent damper operate ?
No Yes
• Remove Damper plug (Figure 30, Item 6, page 50) • Wait 5 minutes.
from plug receptacle of control module. Is Damper light flashing?
• Place voltmeter leads across the top two pins (1 and 4)
of the Damper receptacle. No Yes
Does voltmeter indicate 24 VAC ?
No Yes
Electrical shock hazard — Wherever you see ▲ TURN OFF POWER ▲, follow the instructions. Failure to follow
instructions could result in severe personal injury, death or substantial property damage.
• Leave main manual gas valve closed. • Turn off power to boiler at service switch or breaker.
• Turn off power to boiler at service switch or breaker. • Wait at least 45 seconds.
• Wait at least 45 seconds. • Turn on power to boiler.
• Turn on power to boiler. • Restart boiler, following Operating instructions in this
• Restart boiler, following Operating instructions in this manual (Section 9b) or on boiler label.
manual (Section 9b) or on boiler label. • Look through the pilot inspection port to see if the pilot is
burning.
Do FLAME and POWER lights still flash ?
Is pilot burning?
No Yes No Yes
• ▲ TURN OFF POWER ▲ • Boiler may now be • Replace control • Boiler should now • Replace control
to boiler at service switch or operating module. operate normally. module.
breaker. normally. • Retest. • Original flashing • Retest.
• Open main manual gas • Perform start-up FLAME light
valve. procedures in caused by gas
• Turn on power to boiler at boiler manual to valve not
service switch or verify proper operating properly.
breaker. operation.
• See normal
• Restart boiler per sequence of
operating instructions. operation,
• Perform start-up Figure 24,
procedures in boiler page 35.
manual to verify proper
operation.
CHART 5 –– Spark-ignited pilot –– FLAME light flashing and POWER light on steady
ALSO –– Troubleshooting failure to establish main flame
Electrical shock hazard — Wherever you see ▲ TURN OFF POWER ▲, follow the instructions. Failure to follow
instructions could result in severe personal injury, death or substantial property damage.
Are main manual shutoff valve and gas valve open? • Is pilot flame visible through inspection port ?
No Yes No Yes
Electrical shock hazard — Wherever you see ▲ TURN OFF POWER ▲, follow the instructions. Failure to follow
instructions could result in severe personal injury, death or substantial property damage.
• Has it been at least 5 minutes since setting thermostat to Is boiler System circulator operating?
call for heat? If not, wait 5 minutes. Is system heating?
• Is thermostat set to call for heat? Remove thermostat No Yes
wires at boiler and check continuity across the two wires.
If circuit isn't closed, check external thermostat (zone
valve, relay, etc.) wiring. Correct problems and retry. • Remove CIRCULATOR harness plug from
• Reconnect external thermostat wiring at boiler. CIRCULATOR plug receptacle (Figure 30,
Is thermostat circuit closed (continuity across wires)? Item 7, page 50). Check with voltmeter across
pins of control module receptacle.
No Yes
Does voltmeter show 120 VAC across pins?
Electrical shock hazard — Wherever you see ▲ TURN OFF POWER ▲, follow the instructions. Failure to follow
instructions could result in severe personal injury, death or substantial property damage.
Is boiler pressurized?
Yes No
Section assembly............................................... 59
Base................................................................... 60
Jacket................................................................ 61
Trim.................................................................... 62
Controls............................................................. 63
The boiler contains ceramic fiber and fiberglass materials. Use care when
handling these materials per instructions on Page 66 of this manual.
Failure to comply could result in severe personal injury.
Item Item
Description Part number number Description Part number
number
1 End section, left hand, 51124 311-103-851
9 Temperature/LWCO sensor 511-724-305
2 End section, right hand 51128 311-103-821
3 Intermediate section, 51127 311-103-845 CGa-25 450-021-240
10 Draft hood
not shown Replacement CGa-25 and CGa-3 321-114-360 CGa-3 450-021-241
section CGa-4 321-114-361 CGa-4 450-021-242
assembly CGa-5 321-114-362 CGa-5 450-021-243
CGa-6 321-114-363 CGa-6 450-021-244
CGa-7 321-114-364 CGa-7 450-021-245
CGa-8 321-114-365 CGa-8 450-021-246
not shown Section replacement kit, includes seals and 381-354-527 11 Spill switch (210°F) CGa-25 - 8 510-300-013
sealant for 1 joint
12 Vent Damper CGa-25 & 3 4” 381-800-474
4 Tie rod, 7/16” CGa-25 & CGa-3 560-234-500 CGa-4 5” 381-800-475
without nut CGa-4 560-234-501 CGa-5 & 6 6” 381-800-476
(3 per boiler): CGa-5 560-234-502 CGa-7 & 8 7” 381-800-477
CGa-6 560-234-503
CGa-7 560-234-504 13 Vent Damper Actuator 510-512-337
CGa-8 560-234-505
5 Nut, 7/16” (2 per tie rod) 561-928-235 14 Vent Damper Harness 591-391-795
6 Washer, 7/16” (1 per tie rod) 562-248-684
Radiation plate CGa 25 & 3 460-003-018
7
(1 per joint) CGa 4-8 460-003-017
8 Collector hood CGa-25 381-354-625
CGa-3 381-354-626
CGa-4 381-354-627
CGa-5 381-354-628
CGa-6 381-354-926
CGa-7 381-354-630
CGa-8 381-354-631
1 2 3 4 5
Junction box, 2 x 4 Jacket panel, left side, with insulation Jacket panel, Jacket panel, Jacket panel,
right side, top front top rear
with insulation
Natural Gas Propane Gas
Spark Pilot Spark Pilot
Boiler Boiler
Model Part numbers Model
CGa-25 381-359-201 381-359-208 381-359-229 381-359-230 381-359-236 CGa-25
CGa-3 381-359-202 381-359-209 381-359-229 381-359-230 381-359-236 CGa-3
CGa-4 381-359-203 381-359-210 381-359-229 381-359-231 381-359-237 CGa-4
(Available at local
CGa-5 381-359-204 381-359-211 381-359-229 381-359-232 381-359-238 CGa-5
supply house)
CGa-6 381-359-205 381-359-212 381-359-229 381-359-233 381-359-239 CGa-6
CGa-7 381-359-206 381-359-213 381-359-229 381-359-234 381-359-240 CGa-7
CGa-8 381-359-207 381-359-214 381-359-229 381-359-235 381-359-241 CGa-8
6 7 8 9 10
Jacket panel, Jacket cross tie, Jacket panel, Jacket panel, Not shown —
door bottom front interior, rear, touch-up paint
with insulation with insulation
Boiler Boiler
Model Part numbers Model
CGa-25 381-359-248 381-359-260 381-359-266 381-359-272 CGa-25
CGa-3 381-359-248 381-359-260 381-359-266 381-359-272 CGa-3
CGa-4 381-359-249 381-359-261 381-359-267 381-359-273 381-359-278 Cloud CGa-4
CGa-5 381-359-250 381-359-262 381-359-268 381-359-274 384-000-141 Slate CGa-5
CGa-6 381-359-251 381-359-263 381-359-269 381-359-275 CGa-6
CGa-7 381-35-9252 381-359-264 381-359-270 381-359-276 CGa-7
CGa-8 381-359-253 381-359-265 381-359-271 381-359-277 CGa-8
13a Dimensions
Figure 36 Dimensional drawing — ALL DIMENSIONS IN INCHES
13b Ratings
Chimney
Boiler Seasonal Boiler and
model 0 - 2,000 feet 2,000 - 4,500 feet Heating Efficiency Net water breeching
number Altitude Altitude Capacity PIDN-PIDL Ratings content size
Input Output Input Output Btuh Btuh
(Note 1) AFUE % (gallons) Inches
(Btuh) (Btuh) (Btuh) (Btuh) (Note 2) (Note 3)
CGa-25 38,000 32,000 34,000 29,000 32,000 84.0 27,000 1.5 4"I.D. x 20’
CGa-3 67,000 56,000 60,000 50,000 56,000 84.0 48,000 1.5 4”I.D. x 20’
CGa-4 100,000 84,000 90,000 76,000 85,000 84.0 73,000 2.1 5”I.D. x 20’
CGa-5 133,000 112,000 120,000 101,000 113,000 84.0 98,000 2.7 6”I.D. x 20’
CGa-6 166,000 139,000 149,000 125,000 141,000 84.0 122,000 3.3 6”I.D. x 20’
CGa-7 200,000 168,000 180,000 151,000 170,000 84.0 147,000 3.8 7”I.D. x 20’
CGa-8 233,000 196,000 210,000 176,000 198,000 84.0 172,000 4.4 7”I.D. x 20’
1. Add “PIN” for natural gas boiler - “PIL” for Liquefied Petroleum (propane) gas boiler.
2. Based on standard test procedures prescribed by the United States Department of Energy.
Notes
3. Net AHRI ratings are based on net installed radiation of sufficient quantity for the requirements of the
building and nothing need be added for normal piping and pickup. Ratings are based on a piping and pickup
allowance of 1.15. An additional allowance should be made for unusual piping and pickup loads.
Table 8 Ignition system model suffixes Pilot ignition system Natural gas Propane gas
Spark-ignite pilot PIDN PIDL
Install CGa boilers for residential radiant panel systems, converted gravity heating systems or other low water
temperature applications per instructions in this manual to avoid damage due to condensation.
CGa boilers are CSA design certified for installation on combustible flooring.
CGa boilers are ASME rated for 50 psig working pressure.
Notes