CONTROL

AS1 Push Control


Ammann Asphalt D-31061 Alfeld

SWITCH PANEL G0
COMPANY / CUSTOMER Ammann do Brasil
SITE Porto Alegre
MAKE Ammann
PLANT TYPE Prime 140

SWITCH PANEL 2400 x 1600 x 500mm


INSTALLATION POSITION Trailer
POWER SUPPLY 3Ph~ / 400VAC / 60Hz
SUPPLY CABLE 2 x NYY-J 3x120/70mm² (Cu)
MAX. MAIN-FUSE 500 A
PROTECTION TYPE RCD (FI)
CONTROL VOLTAGE 24VDC / 230VAC
YEAR OF MANUFACTURE 2013
REMARK
PROJECT FOLDER \\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5\71366_G0.elk

THESE DIAGRAMS WERE DRAWN-UP ON CAD. COMMISSION LS-71366/07.04.1 PROJECT REVISOR U. Gresens
DELIVERY DATE 2013-05-30
CHANGES MAY ONLY BE MADE BY US DRAWING NUMBER G0 A 0091 04
PAGE 1 FROM 268
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

TERMINAL BLOCKS WIRING COLOURS POSITION NUMBER

NUMERICAL ORDER
STANDARD STRIP: MAIN CIRCUIT 400VAC: BLACK BK COMPONENT DESCRIPTION
CONTROL CIRCUIT 230VAC RED RD POSITION NUMBER
-X1 = CONSUMER 400VAC EARTHED CONTROL CONDUCTOR 0VAC RED/WHITE RD/WH PLANT DESIGNATION

CONTROL CIRCUIT 24VDC: BLUE BU PLANTS - COMPONENTS


-X2 = CONTROL TERMINAL 230VAC CONTROL CIRCUIT 0VDC: BU/WH
BLUE/WHITE
PLANT DESIGNATION AND
- 11K 1
NEUTRAL CONDUCTOR N: LIGHT BLUE BU
-X3 = CONTROL TERMINAL 24VDC PROTECTIVE CONDUCTOR PE: YELLOW/GREEN GNYE NUMERICAL
ORDER SWITCH PANEL

-X4 = ANALOG VOLTAGES ANALOG VOLTAGES WHITE WH D - COLD FEED


EXTERNAL POTENTIAL ORANGE OG T - DRYER
F - FILLER SUPPLY
-X5 = EXTERNAL VOLTAGE BEFORE MAIN SWITCH BLACK BK
E - DUST COLLECTOR
(HIGH-TENSION LEAD) M - MIXER
V - LOADING
ILLUMINATION/HEATING B - BINDING AGENT SUPPLY
-X11 =
SWITCH PANEL THESE WIRE COLOURS MUST BE ADHERED TO, A - ASPHALT GRANULATE
IF NOT MENTIONED OTHERWISE IN THE SCHEME. H - AUXILIARY PLANTS
-X21 = LOW VOLTAGE COIL

EARTHING + CROSS SECTIONS TERMINAL ALLOCATION CONTROL CIRCUIT 230VAC

MAIN CIRCUIT : MIN. 2,5 mm²


THE TERMINALS -X2:1 + 2 +. 4..19 ARE COVER
CONTROL LINES : MIN. 1 mm²
according to relevant country and local regulations! UNSWITCHED VOLTAGE 230VAC 13L1 - X2:1
UNSWITCHED VOLTAGE 0VAC 13L2 - X2:2
ISOLATING TERMINAL 230VAC X2:3
UNSWITCHED BUTTON/LAMPS X2:4..10
CABLE Interbus-S 230VAC X2:11
Interbus-S 0VAC X2:12
ALL DATA OF CABLE LENGTH ARE WITHOUT OBLIGATION! RESERVE TERMINALS 230VAC X2:13..19
PE-TERMINAL X2:20
SPECIAL TERMINAL STRIPS SWITCHED VOLTAGE 230VAC 3L1 - X2:21
SWITCHED VOLTAGE 0VAC 3L2 - X2:22
MODULES
TERMINAL ALLOCATION CONTROL CIRCUIT 24VDC
-D1E32 -D1A32 -A1E8 -A1A8 UNSWITCHED VOLTAGE 24VDC 13L+ - X3:1
x x UNSWITCHED VOLTAGE 0VDC 13L- - X3:2
RESERVE TERMINALS X3:4..10
Interbus-S 24VDC X3:11
x x Interbus-S 0VDC X3:12
RESERVE TERMINALS 24VDC X3:13..19
ANALOGUE ANALOGUE PE-TERMINAL X3:20
INPUT OUTPUT
INPUT OUTPUT SWITCHED VOLTAGE 24VDC 3L+ - X3:21
SWITCHED VOLTAGE 0VDC 3L- - X3:22

1 1.C
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 INFORMATION G0 A 0091 04 60201857290 =
proc. UGR Ammann Asphalt
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 +
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 1.B
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

TABELA VISÃO GLOBAL: IEC-CABO - CABO BRAZIL


TABLE OVERVIEW: IEC-CABLE - CABLE BRAZIL

ÖZ-J ÖSYZ-J Paulinax Paulicon


H07RN-F OEZ-J OESYZ-J Paulinax Flex Paulicon Flexivel Gerterflex EPR Gerterflex FC NT

BN 1 1 WH 1 WH WH (WH)
3 x 1,5mm² BU 2 2 BU 2 BU BK (BK) 3 x 1,5mm²

3 x 2,5mm² GNYE GNYE GNYE BK => GNYE 3 => GNYE BK => GNYE RD (BK) => GNYE 3 x 2,5mm²
SH (Shield) SH (Shield)

(4 x 0,75mm²) (4 x 0,75mm²)
BN 1 1 WH 1 WH WH
4 x 1,5mm²
. BK 2 2 BK 2 BK BK 4 x 1,5mm²
.

. .

. .

GY 3 3 BU 3 BU RD
. .

. .

4 x 6 mm² 4 x 6 mm²
.

.
GNYE GNYE GNYE RD => GNYE 4 => GNYE RD => GNYE Cu => GNYE .

. .

. .

4 x 75 mm² SH (Shield) SH (Shield) 4 x 75 mm²

(4 x 1 mm²) (4 x 1 mm²)

(5 x 1 mm²) (5 x 1 mm²)
BN 1 1 1 1
BK 2 2 2 2
5 x 1,5mm² 5 x 1,5mm²
GY 3 3 3 3
5 x 2,5mm² BU 4 4 4 4 5 x 2,5mm²
GNYE GNYE GNYE 5 => GNYE 5 => GNYE
(5 x 0,75mm²) (5 x 0,75mm²)
SH (Shield)

1 1 1 1 1

(7 x 1 mm²) 2 2 2 2 2 (7 x 1 mm²)
3 3 3 3 3
7 x 1,5mm² 4 4 4 4 4 7 x 1,5mm²
5 5 5 5 5
6 6 6 6 6
GNYE GNYE GNYE 7 => GNYE 7 => GNYE
SH (Shield)

1.B 2
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 TABLE G0 A 0091 04 60201857290 =
proc. UGR Ammann Asphalt
CLIENT : Ammann do Brasil IEC-CABLE - BRAZIL CABLE SWITCH PANEL G0 +
Appr
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 1.C
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

TABLE OF CONTENTS Spalte X: eine automatisch erzeugte Seite wurde manuell nachbearbeitet

PAGE SIDE DECLARATION PAGE SUPPLEMENTARY AREA DATE PROCESSOR X


/1 TITLE PAGE 2013-05-06 UGR X
/1.B INFORMATION 2013-05-06 UGR
/1.C TABLE IEC-CABLE - BRAZIL CABLE 2013-05-06 UGR
/2 TABLE OF CONTENTS 2013-05-29 UGR
/2.A TABLE OF CONTENTS 2013-05-29 UGR
/2.B TABLE OF CONTENTS 2013-05-28 UGR
/2.C TABLE OF CONTENTS 2013-05-28 UGR
/2.D TABLE OF CONTENTS 2013-05-29 UGR
/2.E TABLE OF CONTENTS 2013-05-29 UGR
/2.F TABLE OF CONTENTS 2013-05-28 UGR
/2.G TABLE OF CONTENTS 2013-05-28 UGR
/2.H TABLE OF CONTENTS 2013-05-28 UGR
/3 SWITCH PANEL OVERVIEW 2013-05-06 PBR
/3.A EQUIPMENT 2013-05-28 UGR
/3.B EQUIPMENT 2013-05-06 UGR
/3.C EQUIPMENT 2013-05-06 PBR
/3.L EQUIPMENT DOOR LEFT 2013-05-06 PBR
/3.MR EQUIPMENT PANEL DOOR MIDDLE RIGHT 2013-05-06 PBR
/4 MATERIAL LIST 2013-05-06 UGR
/4.A MATERIAL LIST 2013-05-06 UGR
/4.B MATERIAL LIST 2013-05-06 UGR
/4.C MATERIAL LIST 2013-05-06 UGR
/4.D MATERIAL LIST 2013-05-06 UGR
/4.E MATERIAL LIST 2013-05-06 UGR
/4.F MATERIAL LIST 2013-05-06 UGR
/4.G MATERIAL LIST 2013-05-06 UGR
/4.H MATERIAL LIST 2013-05-06 UGR
/4.I MATERIAL LIST 2013-05-06 UGR
/4.J MATERIAL LIST 2013-05-06 UGR
/4.K MATERIAL LIST 2013-05-06 UGR
/4.L MATERIAL LIST 2013-05-06 UGR
/4.M MATERIAL LIST 2013-05-06 UGR
/4.N MATERIAL LIST 2013-05-29 UGR

1.C 2.A
DATE 2013-05-30 COMMISSION : LS-71366/07.04.1 TABLE OF CONTENTS G0 A 0091 04 60201857290 =
proc. UGR Ammann Asphalt
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 +
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 2
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

TABLE OF CONTENTS Spalte X: eine automatisch erzeugte Seite wurde manuell nachbearbeitet

PAGE SIDE DECLARATION PAGE SUPPLEMENTARY AREA DATE PROCESSOR X


/4.O MATERIAL LIST 2013-05-29 UGR
/4.P MATERIAL LIST 2013-05-29 UGR
/4.Q MATERIAL LIST 2013-05-29 UGR
/4.R MATERIAL LIST 2013-05-30 UGR
/4.S MATERIAL LIST 2013-05-30 UGR
/4.T MATERIAL LIST 2013-05-30 UGR
/4.U MATERIAL LIST 2013-05-30 UGR
/4.V MATERIAL LIST 2013-05-30 UGR
/5 MODULAR DIGITAL INPUT DIGITAL OUTPUT 2013-05-06 UGR
/6 MODULAR DIGITAL INPUT DIGITAL OUTPUT 2013-05-06 UGR
/7 MODULAR ANALOGUE INPUT ANALOGUE OUTPUT 2013-05-06 UGR
=H0/11 POWER SUPPLY POWER SWITCH 2013-05-06 UGR
=H0/13 EMERGENCY STOP SWITCH 2013-05-06 UGR
=H0/16 POWER SUPPLY LOW VOLTAGE COILS ERROR BITUMEN COCK 2013-05-06 UGR
=H0/17 CONTROL VOLTAGE 230VAC 2013-05-06 PBR
=H0/18 CONTROL VOLTAGE ON WATCHDOG 2013-05-06 UGR
=H0/19 CONTROL VOLTAGE 230VAC AND 24VDC 2013-05-06 UGR
=H0/20 FEED BUS TERMINAL 2013-05-06 UGR
=H0/21 ASSEMBLY INTERBUS 2013-05-06 UGR
=H0/22 ASSEMBLY INTERBUS 2013-05-06 UGR
=H0/30 EMERGENCY AND ERROR WARNING DRIVES 2013-05-06 UGR
=H0/62 891 COMPRESSOR 2013-05-06 UGR
=H0/63 891 COMPRESSOR CONTROL PART 2013-05-06 UGR
=H0/76 841 HEATING BITUMEN PUMP 2013-05-06 UGR
=H0/77 841 HEATING BITUMEN PUMP 2013-05-06 UGR
=H0/81 831 BITUMEN PIPE HEATING CIRCUIT 1 2013-05-06 PBR
=H0/82 831 BITUMEN PIPE HEATING CIRCUIT 1 2013-05-06 UGR
=H0/83 831 BITUMEN PIPE HEATING CIRCUIT 1 2013-05-06 UGR
=H0/91 HEATING OIL PIPES 1 PRESSURE PUMP --> BURNER 2013-05-06 PBR
=H0/92 TEMPERATURE LIMITER HEATING OIL PIPES 1 PRESSURE PUMP --> BURNER 2013-05-06 PBR
=H0/94 HEATING PIPE BURNER AND LANCE 2013-05-06 PBR
=H0/95 HEATING BURNER-PRESSURE PUMP 2013-05-06 PBR
=H0+KLE/1 TERMINAL STRIP REVIEW 2013-05-06 UGR

2 2.B
DATE 2013-05-30 COMMISSION : LS-71366/07.04.1 TABLE OF CONTENTS G0 A 0091 04 60201857290 =
proc. UGR Ammann Asphalt
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 +
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 2.A
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

TABLE OF CONTENTS Spalte X: eine automatisch erzeugte Seite wurde manuell nachbearbeitet

PAGE SIDE DECLARATION PAGE SUPPLEMENTARY AREA DATE PROCESSOR X


=H0+KLE/11 TERMINAL DIAGRAM =H0+-X1 2013-05-06 UGR
=H0+KLE/12 TERMINAL DIAGRAM =H0+-X2 2013-05-06 UGR
=H0+KLE/12.A TERMINAL DIAGRAM =H0+-X2 2013-05-06 UGR
=H0+KLE/12.B TERMINAL DIAGRAM =H0+-X2 2013-05-06 UGR
=H0+KLE/13 TERMINAL DIAGRAM =H0+-X3 2013-05-06 UGR
=H0+KLE/13.A TERMINAL DIAGRAM =H0+-X3 2013-05-06 UGR
=H0+KLE/14 TERMINAL DIAGRAM =H0+-X4 2013-05-06 UGR
=H0+KLE/15 TERMINAL DIAGRAM =H0+-X5 2013-05-06 UGR
=H0+KLE/16 TERMINAL DIAGRAM =H0+-X13 2013-05-06 UGR
=H0+KLE/17 TERMINAL DIAGRAM =H0+-X21 2013-05-06 UGR
=H0+KAB/1 CABLE PLAN 2013-05-06 UGR
=H0+KAB/11 CABLE DIAGRAM =H0+-W102 2013-05-06 UGR
=H0+KAB/12 CABLE DIAGRAM =H0+-W141 2013-05-06 UGR
=H0+KAB/13 CABLE DIAGRAM =H0+-W142 2013-05-06 UGR
=H0+KAB/14 CABLE DIAGRAM =H0+-W165.2 2013-05-06 UGR
=H0+KAB/15 CABLE DIAGRAM =H0+-W171 2013-05-06 UGR
=H0+KAB/16 CABLE DIAGRAM =H0+-W182 2013-05-06 UGR
=H0+KAB/17 CABLE DIAGRAM =H0+-W185 2013-05-06 UGR
=H0+KAB/18 CABLE DIAGRAM =H0+-W187 2013-05-06 UGR
=H0+KAB/19 CABLE DIAGRAM =H0+-W202 2013-05-06 UGR
=H0+KAB/20 CABLE DIAGRAM =H0+-W303.1 2013-05-06 UGR
=H0+KAB/21 CABLE DIAGRAM =H0+-W341 2013-05-06 UGR
=H0+KAB/22 CABLE DIAGRAM =H0+-W465 2013-05-06 UGR
=H0+KAB/23 CABLE DIAGRAM =H0+-W471 2013-05-06 UGR
=H0+KAB/24 CABLE DIAGRAM =H0+-W482 2013-05-06 UGR
=H0+PR/1 CIRCUIT OVERVIEW 2013-05-06 UGR
=H0+PR/2 TEST REPORT 2013-05-06 UGR
=D0/5 MODULAR FREQUENCY CONVERTER FEEDER 1 2013-05-06 UGR
=D0/6 MODULAR FREQUENCY CONVERTER FEEDER 2 2013-05-06 UGR
=D0/7 MODULAR FREQUENCY CONVERTER FEEDER 3 2013-05-06 UGR
=D0/13 FEED CONTROL VOLTAGE 2013-05-06 PBR
=D0/21 FEEDER 1 2013-05-06 UGR
=D0/22 BELT SCALE FEEDER 1 2013-05-28 UGR

2.A 2.C
DATE 2013-05-30 COMMISSION : LS-71366/07.04.1 TABLE OF CONTENTS G0 A 0091 04 60201857290 =
proc. UGR Ammann Asphalt
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 +
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 2.B
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

TABLE OF CONTENTS Spalte X: eine automatisch erzeugte Seite wurde manuell nachbearbeitet

PAGE SIDE DECLARATION PAGE SUPPLEMENTARY AREA DATE PROCESSOR X


=D0/31 FEEDER 2 2013-05-06 UGR
=D0/32 BELT SCALE FEEDER 2 2013-05-28 UGR
=D0/41 FEEDER 3 2013-05-06 UGR
=D0/42 FEEDER 3 VIBRATOR 0,18 KW 2013-05-06 UGR
=D0/43 BELT SCALE FEEDER 3 2013-05-28 UGR
=D0+KLE/1 TERMINAL STRIP REVIEW 2013-05-06 UGR
=D0+KLE/11 TERMINAL DIAGRAM =D0+-X1 2013-05-06 UGR
=D0+KLE/12 TERMINAL DIAGRAM =D0+-X2 2013-05-06 UGR
=D0+KLE/13 TERMINAL DIAGRAM =D0+-X3 2013-05-06 UGR
=D0+KLE/14 TERMINAL DIAGRAM =D0+-X8 2013-05-06 UGR
=D0+KLE/15 TERMINAL DIAGRAM =D0+-X421 2013-05-06 UGR
=D0+KLE/16 TERMINAL DIAGRAM =D0+-X422 2013-05-06 UGR
=D0+KLE/17 TERMINAL DIAGRAM =D0+-X423 2013-05-06 UGR
=D0+KAB/1 CABLE PLAN 2013-05-06 UGR
=D0+KAB/11 CABLE DIAGRAM =D0+-W121 2013-05-06 UGR
=D0+KAB/12 CABLE DIAGRAM =D0+-W122 2013-05-06 UGR
=D0+KAB/13 CABLE DIAGRAM =D0+-W123 2013-05-06 UGR
=D0+KAB/14 CABLE DIAGRAM =D0+-W124 2013-05-06 UGR
=D0+KAB/15 CABLE DIAGRAM =D0+-W321 2013-05-06 UGR
=D0+KAB/16 CABLE DIAGRAM =D0+-W322 2013-05-06 UGR
=D0+KAB/17 CABLE DIAGRAM =D0+-W323 2013-05-06 UGR
=D0+KAB/18 CABLE DIAGRAM =D0+-W421 2013-05-06 UGR
=D0+KAB/19 CABLE DIAGRAM =D0+-W422 2013-05-06 UGR
=D0+KAB/20 CABLE DIAGRAM =D0+-W423 2013-05-06 UGR
=D0+PR/1 CIRCUIT OVERVIEW 2013-05-06 UGR
=D0+PR/2 TEST REPORT 2013-05-06 UGR
=T0/13 FEED CONTROL VOLTAGE 2013-05-06 PBR
=T0/21 START-UP WARNING 2013-05-06 UGR
=T0/26 02.001 DRUM 9,5 KW 19,2A 2013-05-06 UGR
=T0/27 02.001 DRUM CONTROL PART 2013-05-06 UGR
=T0/28 02.001 DRUM CONTROL PART 2013-05-06 UGR
=T0/32 01.003 FEEDING BELT 4,0 KW 8,4A 2013-05-06 UGR
=T0/33 01.003 FEEDING BELT 1 CONTROL PART 2013-05-06 UGR

2.B 2.D
DATE 2013-05-30 COMMISSION : LS-71366/07.04.1 TABLE OF CONTENTS G0 A 0091 04 60201857290 =
proc. UGR Ammann Asphalt
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 +
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 2.C
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

TABLE OF CONTENTS Spalte X: eine automatisch erzeugte Seite wurde manuell nachbearbeitet

PAGE SIDE DECLARATION PAGE SUPPLEMENTARY AREA DATE PROCESSOR X


=T0/47 05.007 COARSE DUST SCREW 1 4,0 KW 8,4A 2013-05-06 UGR
=T0/48 05.007 COARSE DUST SCREW 2 4,0 KW 8,4A 2013-05-06 UGR
=T0+KLE/1 TERMINAL STRIP REVIEW 2013-05-06 UGR
=T0+KLE/11 TERMINAL DIAGRAM =T0+-X1 2013-05-06 UGR
=T0+KLE/12 TERMINAL DIAGRAM =T0+-X2 2013-05-06 UGR
=T0+KLE/13 TERMINAL DIAGRAM =T0+-X3 2013-05-06 UGR
=T0+KAB/1 CABLE PLAN 2013-05-06 UGR
=T0+KAB/11 CABLE DIAGRAM =T0+-W125.1 2013-05-06 UGR
=T0+KAB/12 CABLE DIAGRAM =T0+-W125.2 2013-05-06 UGR
=T0+KAB/13 CABLE DIAGRAM =T0+-W125.3 2013-05-06 UGR
=T0+KAB/14 CABLE DIAGRAM =T0+-W125.4 2013-05-06 UGR
=T0+KAB/15 CABLE DIAGRAM =T0+-W129 2013-05-06 UGR
=T0+KAB/16 CABLE DIAGRAM =T0+-W147 2013-05-06 UGR
=T0+KAB/17 CABLE DIAGRAM =T0+-W148 2013-05-06 UGR
=T0+KAB/18 CABLE DIAGRAM =T0+-W210.1 2013-05-06 UGR
=T0+PR/1 CIRCUIT OVERVIEW 2013-05-06 UGR
=T0+PR/2 TEST REPORT 2013-05-06 UGR
=T2/5 MODULAR ETAMATIC S 2013-05-06 UGR
=T2/13 FEED CONTROL VOLTAGE 2013-05-06 PBR
=T2/21 02.003 BURNER VENTILATOR 18,5 KW 35A 2013-05-06 UGR
=T2/22 02.003 BURNER VENTILATOR CONTROL PART 11 KW 2013-05-06 UGR
=T2/24 02.004 OIL PRESSURE PUMP 0,9 KW 1,9A 2013-05-06 UGR
=T2/27 SELECT LIGHT OIL / HEAVY FUEL NELS-BURNER 2013-05-28 UGR
=T2/31 TEMPERATURE MEASUREMENT DRUM DISCHARGE 2013-05-06 PBR
=T2/41 BURNER CONTROL POWER SUPPLY ETAMATIC S 2013-05-06 PBR
=T2/42 430 BURNER LOCK START POSITION 2013-05-06 UGR
=T2/43 AIR CONTROLLER COMBUSTION AIR 2013-05-06 PBR
=T2/46 FUEL CHOICE SURVEILLANCE PRESSURE ATOMIZER AIR 2013-05-28 UGR
=T2/47 SURVEILLANCE AIR PRESSURE 2013-05-06 UGR
=T2/48 OIL CONTROL 2013-05-28 UGR
=T2/49 BURNER CONTROL SURVEILLANCE OIL TEMPERATURE 2013-05-28 UGR
=T2/51 IGNITION 2013-05-28 UGR
=T2/52 FLAME CONTROL 2013-05-06 UGR

2.C 2.E
DATE 2013-05-30 COMMISSION : LS-71366/07.04.1 TABLE OF CONTENTS G0 A 0091 04 60201857290 =
proc. UGR Ammann Asphalt
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 +
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 2.D
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

TABLE OF CONTENTS Spalte X: eine automatisch erzeugte Seite wurde manuell nachbearbeitet

PAGE SIDE DECLARATION PAGE SUPPLEMENTARY AREA DATE PROCESSOR X


=T2/56 AIR FLAP CHANNEL 2 2013-05-06 UGR
=T2/57 SERVO DRIVE OIL CHANNEL 3 2013-05-06 UGR
=T2+KLE/1 TERMINAL STRIP REVIEW 2013-05-28 UGR
=T2+KLE/11 TERMINAL DIAGRAM =T2+-X1 2013-05-06 UGR
=T2+KLE/12 TERMINAL DIAGRAM =T2+-X2 2013-05-29 UGR
=T2+KLE/12.A TERMINAL DIAGRAM =T2+-X2 2013-05-30 UGR
=T2+KLE/13 TERMINAL DIAGRAM =T2+-X3 2013-05-06 UGR
=T2+KLE/14 TERMINAL DIAGRAM =T2+-X4 2013-05-29 UGR
=T2+KLE/15 TERMINAL DIAGRAM =T2+-X8 2013-05-28 UGR
=T2+KAB/1 CABLE PLAN 2013-05-06 UGR
=T2+KAB/11 CABLE DIAGRAM =T2+-W121.1 2013-05-06 UGR
=T2+KAB/12 CABLE DIAGRAM =T2+-W121.2 2013-05-06 UGR
=T2+KAB/13 CABLE DIAGRAM =T2+-W122 2013-05-06 UGR
=T2+KAB/14 CABLE DIAGRAM =T2+-W243 2013-05-30 UGR
=T2+KAB/15 CABLE DIAGRAM =T2+-W343 2013-05-06 UGR
=T2+KAB/16 CABLE DIAGRAM =T2+-W430.1 2013-05-06 UGR
=T2+PR/1 CIRCUIT OVERVIEW 2013-05-06 UGR
=T2+PR/2 TEST REPORT 2013-05-06 UGR
=IB+STK/1 CONNECTOR PLAN 2013-05-28 UGR
=IB+STK/11 PLUG PLAN =IB+-X1 2013-05-30 UGR
=IB+STK/12 PLUG PLAN =IB+-X2 2013-05-06 UGR
=E0/13 FEED CONTROL VOLTAGE 2013-05-06 PBR
=E0/21 EXHAUSTOR 75 KW 134A 2013-05-06 UGR
=E0/22 EXHAUSTOR 75 KW CONTROL PART 1 2013-05-06 UGR
=E0/24 THROTTLE FLAP 2013-05-06 UGR
=E0/25 THROTTLE FLAP CONTROL PART NEGATIVE PRESURE MINERAL DRUM 2013-05-06 UGR
=E0/26 613 CLEANING 1 2013-05-06 UGR
=E0/27 613 CLEANING 2 2013-05-06 UGR
=E0/30 613/614 LIMIT SWITCH PARK POSITION CLEANING 1 - 2 2013-05-06 UGR
=E0/32 SAFETY THERMOSTAT 2013-05-06 UGR
=E0/33 TEMPERATURES FILTER 2013-05-06 UGR
=E0+KLE/1 TERMINAL STRIP REVIEW 2013-05-06 UGR
=E0+KLE/11 TERMINAL DIAGRAM =E0+-X1 2013-05-06 UGR

2.D 2.F
DATE 2013-05-30 COMMISSION : LS-71366/07.04.1 TABLE OF CONTENTS G0 A 0091 04 60201857290 =
proc. UGR Ammann Asphalt
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 +
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 2.E
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

TABLE OF CONTENTS Spalte X: eine automatisch erzeugte Seite wurde manuell nachbearbeitet

PAGE SIDE DECLARATION PAGE SUPPLEMENTARY AREA DATE PROCESSOR X


=E0+KLE/12 TERMINAL DIAGRAM =E0+-X2 2013-05-28 UGR
=E0+KLE/13 TERMINAL DIAGRAM =E0+-X3 2013-05-28 UGR
=E0+KLE/14 TERMINAL DIAGRAM =E0+-X4 2013-05-06 UGR
=E0+KLE/15 TERMINAL DIAGRAM =E0+-X5 2013-05-06 UGR
=E0+KAB/1 CABLE PLAN 2013-05-06 UGR
=E0+KAB/11 CABLE DIAGRAM =E0+-W121.1 2013-05-06 UGR
=E0+KAB/12 CABLE DIAGRAM =E0+-W121.2 2013-05-06 UGR
=E0+KAB/13 CABLE DIAGRAM =E0+-W122 2013-05-06 UGR
=E0+KAB/14 CABLE DIAGRAM =E0+-W124 2013-05-06 UGR
=E0+KAB/15 CABLE DIAGRAM =E0+-W124.1 2013-05-06 UGR
=E0+KAB/16 CABLE DIAGRAM =E0+-W125 2013-05-06 UGR
=E0+KAB/17 CABLE DIAGRAM =E0+-W125.1 2013-05-06 UGR
=E0+KAB/18 CABLE DIAGRAM =E0+-W230 2013-05-06 UGR
=E0+KAB/19 CABLE DIAGRAM =E0+-W230.1 2013-05-06 UGR
=E0+KAB/20 CABLE DIAGRAM =E0+-W322 2013-05-06 UGR
=E0+KAB/21 CABLE DIAGRAM =E0+-W324 2013-05-06 UGR
=E0+KAB/22 CABLE DIAGRAM =E0+-W324.1 2013-05-06 UGR
=E0+KAB/23 CABLE DIAGRAM =E0+-W324.2 2013-05-06 UGR
=E0+KAB/24 CABLE DIAGRAM =E0+-W421 2013-05-06 UGR
=E0+KAB/25 CABLE DIAGRAM =E0+-W422 2013-05-06 UGR
=E0+KAB/26 CABLE DIAGRAM =E0+-W423 2013-05-06 UGR
=E0+KAB/27 CABLE DIAGRAM =E0+-W431 2013-05-06 UGR
=E0+KAB/28 CABLE DIAGRAM =E0+-W431.1 2013-05-06 UGR
=E0+KAB/29 CABLE DIAGRAM =E0+-W522 2013-05-06 UGR
=E0+PR/1 CIRCUIT OVERVIEW 2013-05-06 UGR
=E0+PR/2 TEST REPORT 2013-05-06 UGR
=M0/5 MODULAR FREQUENCY CONVERTER BITUMEN PUMP 2013-05-06 UGR
=M0/13 FEED CONTROL VOLTAGE 2013-05-06 PBR
=M0/21 881 MIXER 15KW 31A 2013-05-06 UGR
=M0/22 MEASUREMENT CAPACITY MIXER 2013-05-06 UGR
=M0/23 881 MIXER CONTROL PART 1 2013-05-06 UGR
=M0/24 MIXER CONTROL PART 2 2013-05-06 UGR
=M0/25 883 / 884 MIXER OUTLET LIMIT SWITCH/VALVE 2013-05-06 UGR

2.E 2.G
DATE 2013-05-30 COMMISSION : LS-71366/07.04.1 TABLE OF CONTENTS G0 A 0091 04 60201857290 =
proc. UGR Ammann Asphalt
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 +
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 2.F
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

TABLE OF CONTENTS Spalte X: eine automatisch erzeugte Seite wurde manuell nachbearbeitet

PAGE SIDE DECLARATION PAGE SUPPLEMENTARY AREA DATE PROCESSOR X


=M0/26 891 COMPRESSED AIR SENSOR SHUT-OFF VALVE 2013-05-06 UGR
=M0/27 885 TEMPERATURE MEASUREMENT MIXER OUTLET 2013-05-06 UGR
=M0/29 BITUMEN PUMP 4KW 2013-05-06 UGR
=M0/35 DRAG SLAT CONVEYOR 22 KW 44,5 2013-05-06 UGR
=M0/36 DRAG SLAT CONVEYOR CONTROL PART 2013-05-06 UGR
=M0/37 BATCHER VALVE 2013-05-06 UGR
=M0+KLE/1 TERMINAL STRIP REVIEW 2013-05-06 UGR
=M0+KLE/11 TERMINAL DIAGRAM =M0+-X1 2013-05-06 UGR
=M0+KLE/12 TERMINAL DIAGRAM =M0+-X2 2013-05-06 UGR
=M0+KLE/13 TERMINAL DIAGRAM =M0+-X3 2013-05-06 UGR
=M0+KLE/14 TERMINAL DIAGRAM =M0+-X4 2013-05-06 UGR
=M0+KAB/1 CABLE PLAN 2013-05-06 UGR
=M0+KAB/11 CABLE DIAGRAM =M0+-W121.1 2013-05-06 UGR
=M0+KAB/12 CABLE DIAGRAM =M0+-W121.2 2013-05-06 UGR
=M0+KAB/13 CABLE DIAGRAM =M0+-W122.1 2013-05-06 UGR
=M0+KAB/14 CABLE DIAGRAM =M0+-W122.2 2013-05-06 UGR
=M0+KAB/15 CABLE DIAGRAM =M0+-W125 2013-05-06 UGR
=M0+KAB/16 CABLE DIAGRAM =M0+-W135.1 2013-05-06 UGR
=M0+KAB/17 CABLE DIAGRAM =M0+-W135.2 2013-05-06 UGR
=M0+KAB/18 CABLE DIAGRAM =M0+-W315.1 2013-05-06 UGR
=M0+KAB/19 CABLE DIAGRAM =M0+-W315.2 2013-05-06 UGR
=M0+KAB/20 CABLE DIAGRAM =M0+-W315.3 2013-05-06 UGR
=M0+KAB/21 CABLE DIAGRAM =M0+-W315.4 2013-05-06 UGR
=M0+KAB/22 CABLE DIAGRAM =M0+-W336.1 2013-05-06 UGR
=M0+KAB/23 CABLE DIAGRAM =M0+-W412 2013-05-06 UGR
=M0+KAB/24 CABLE DIAGRAM =M0+-W415 2013-05-06 UGR
=M0+KAB/25 CABLE DIAGRAM =M0+-W415.1 2013-05-06 UGR
=M0+KAB/26 CABLE DIAGRAM =M0+-W425 2013-05-06 UGR
=M0+PR/1 CIRCUIT OVERVIEW 2013-05-06 UGR
=M0+PR/2 TEST REPORT 2013-05-06 UGR
=KFZ/300 TERMINAL BOX =KFZ-UC300 ILLUMINATION 2013-05-06 UGR
=KFZ+KAB/1 CABLE PLAN 2013-05-06 UGR
=KFZ+KAB/11 CABLE DIAGRAM =KFZ+-W300 2013-05-06 UGR

2.F 2.H
DATE 2013-05-30 COMMISSION : LS-71366/07.04.1 TABLE OF CONTENTS G0 A 0091 04 60201857290 =
proc. UGR Ammann Asphalt
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 +
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 2.G
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

TABLE OF CONTENTS Spalte X: eine automatisch erzeugte Seite wurde manuell nachbearbeitet

PAGE SIDE DECLARATION PAGE SUPPLEMENTARY AREA DATE PROCESSOR X


=KFZ+KAB/12 CABLE DIAGRAM =KFZ+-W300.1 2013-05-06 UGR
=KFZ+KAB/13 CABLE DIAGRAM =KFZ+-W300.2 2013-05-06 UGR
=KFZ+PR/1 CIRCUIT OVERVIEW 2013-05-06 UGR
=KFZ+PR/2 TEST REPORT 2013-05-06 UGR

2.G 3
DATE 2013-05-30 COMMISSION : LS-71366/07.04.1 TABLE OF CONTENTS G0 A 0091 04 60201857290 =
proc. UGR Ammann Asphalt
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 +
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 2.H
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

WITH WINDOW WITHOUT WINDOW

OPERATION
T2
ETAMATIK OPERATION
H0

CAPACITY
MIXER

2.H 3.A
DATE 2013-02-20 COMMISSION : LS-71366/07.04.1 SWITCH PANEL OVERVIEW G0 A 0091 04 60201857290 =
proc. PBR Ammann Asphalt
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 +
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 3
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

210 87 115 47 110 47 150 47 350 47 255 31

47 mm
=T0-X1

=T2-21K3

PKE32- PKE32- PKE32- PKE32- PKE12- PKE12-

PKE12- PKE12- PKE32- PKE32- PKE12-


=T2-X4
=T0-25Q1 + 25K1 =T0-47Q1 + -47K1

32

12
M25-22 DRUM MOTOR 1 SCREW 1
=T2-21K12 =T2-21K11
=T2-22K11
T2-27K1
55.34 24V =T0-25Q2 + 25K2 =T0-48Q1 + 48K1

=T0-X2

32

12
DRUM MOTOR 2 SCREW 2
=T2-X1

T2-27K2

=T2-X8
55.34 24V
T2-42K1T 87.02
T2-42K1 =T0-25Q3 + 25K3 =T2-21Q1 + 21K1

32

32

31 mm
T2-46K1T 87.02 DRUM MOTOR 3 BURNER VENTILATOR
T2-47K3
55.34 230V
=T2-48K1 =T0-25Q4 + 25K4 =T2-21Q2 + 21K2

=E0-X2
=T2-48K2

32

32
=T2-48K4
DRUM MOTOR 4 BURNER VENTILATOR
=E0-X1

T2-49K1
55.34 230V
=T0-X3

=T2-49K2
=T2-51K1 -29Q1 + 29K1 =T2-22Q1 + 22K1

12

4
FEEDING BELT FORWARD OIL-PRESSURE PUMP
=E0-X3
87 mm

=T0-10K11 -29Q2 + 29K2

12
=M0-X1

PKE12- PKE12- PKE12- PKE12-


=T0-25K11 FEEDING BELT BACKWARDS
=E0-22Q1 + 22K1

1,2
55.34 24V
=T0-29K11 THROTTLE FLAP OPEN
=T0-47K11 =T0-29K12
=T0-48K11
=T2-X2

=E0-21F2 =E0-24Q1 + 24K1


=E0-X4

EMT 6

1,2
CLEANING 1
=E0-21K12 =E0-21K11
=E0-X5

=E0-22K12 =E0-22K11
=E0-24K11

NH2-T200A
=E0-24K12

=E0-21Q1
E0-25Q1 + 25K1

EXHAUSTOR

1,2
=E0-30K1
55.34 230V CLEANING 2
=T2-X3

=M0-21Q3
=E0-21K3 =E0-21K1

4
CAPACITY MIXER
DILM65
=E0-X1

DILM95

1X RESERVE
=E0-21F1
ZB150

=E0-21K2

DILM95

SWITCH PANEL :
800X1600X500MM
3 3.B
DATE 2013-05-29 COMMISSION : LS-71366/07.04.1 EQUIPMENT G0 A 0091 04 60201857290 =
proc. UGR Ammann Asphalt
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 +
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 3.A
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

210 87 130 47 110 31 130 47 350 47 255 31

-6G1 31 mm

=G0-D1A32

=G0-D2A32
=G0-D1E32

=G0-D2E32
240AC-24VDC/5

=G0-A1E8

=G0-A2E2

=G0-A3E2

=G0-A4E2
=G0-BK1
-8G2
QUINT-PS
240AC-24VDC/5
MFIW 105/0,5

=H0-1Q1
=H0-1T1

FAZ-2
N3-630

-5F2

2 AI
31 mm

31 mm
BK-T/U DI 32 DI 32 DO 32 DO 32 AI-8 AI-2 DMS AI-2 DMS

-5F21

FAZ-2
FAZ-2
-5F3

FAZ-2
-6F1
31 mm
31 mm 47 mm
=H0-X21

=H0-7K12
=H0-1F1 =H0-7K1 =H0-41K1T 87.02
MFR M12-32

PKE32- PKE32- PKE32- PKE32- PKE32- PKE32-


=H0-65U1

-21T1
ecoTRON T =M0-21Q1 + -21K1

PKE12- PKE65- PKE12- PKE12- PKE12- PKE12-


=H0-5K1 =H0-5Q1

32
=H0-7K2 MIXER MOTOR 1

4
55.34 24V =H0-65U2 ecoTRON T
DILM12-10 CONTROL VOLTAGE
=H0-1Q2 =H0-7U1 =H0-65K5
55.34 24V =M0-21Q2 + -21K2
A300

PKZM0-20/CL =H0-71K11 =H0-41Q1

32
MIXER MOTOR 1

65
-71U1

-22T1
=H0-1Q3 COMPRESSOR
PKZM0-20/CL =H0-71U3
=H0-3F1 =M0-22Q1 + -22K1
=H0-X1

=H0-65Q3 + -65K3

32

47 mm
=H0-82U1
47 mm

ecoTRON T MIXER MOTOR 2

31 mm
12
87 mm

PNOZX4
47 mm

=H0-1F3 BITUMEN PUMP HEATING

47 mm
RCD (FI) =H0-3K1
=M0-22Q2 + -22K2 =H0-71K1 =H0-71Q1

32
40/0,03 M12-32 MIXER MOTOR 2

12
DILM12-10 HEATING BITUMEN PIPE 1
=H0-1Q5 =H0-85K1 =M0-21K11
=M0-21K12
PKZM0-20/CL M12-32
=M0-35K11
=M0-35K12 =M0-35Q1 + -35K1 =H0-82K1 =H0-82Q1

32
DRAG SLAT CONVEYOR

12
HEATING
=M0-21K3 DILM12-10 HEAVY FUEL PIPE
M12-32 =M0-35Q2 + -35K2
=M0-X1

=H0-87Q1 + -87K1

32
DRAG SLAT CONVEYOR

12
=M0-22K3 =M0-35K3 HEATING HEAVY FUEL PUMP
M12-32 M12-32

47 mm

SWITCH PANEL :
800X1600X500MM
3.A 3.C
DATE 2013-04-10 COMMISSION : LS-71366/07.04.1 EQUIPMENT G0 A 0091 04 60201857290 =
proc. UGR Ammann Asphalt
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 +
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 3.B
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

210 87 110 47 130 47 130 47 355 47 255 31

91 (L1)
92 (L2)

=D0-21U1

FC 302 P1K5
93 (L3)

Doseur 1
67mm 95 (PE)

FU
=D0-X1

96 (U)
97 (V)
98 (W)
99 (PE)

PKE32- PKE32- PKE32- PKE32- PKE32-


=D0-21Q1 + 21K1

=H0-X4

12
91 (L1)

=M0-X3
92 (L2) FEEDER 1

=D0-22U1
=D0-X2

FC 302 P1K5
93 (L3)

=H0-X2

Doseur 2
95 (PE)

FU
96 (U) =D0-22Q1 + 22K1

12
97 (V)
98 (W) FEEDER 2

=H0-X5
99 (PE)
=D0-X3

91 (L1) =D0-23Q1 + 23K1

12
92 (L2) FEEDER 3

=D0-23U1

FC 302 P1K5
93 (L3)

Doseur3
95 (PE)

FU
=H0-X13
96 (U) =D0-29Q1 + -29K1
97 (V)

12
VIBRATOR
47 mm

47 mm
98 (W)
87 mm

31 mm
=D0-X8

47 mm

47 mm
99 (PE)

=M0-X4
=M0-25Q1 + -25K1

32
130/268/220mm
BITUMEN PUMP

=M0-25U1
91 (L1)
=M0-X2
92 (L2)

FC 302 P5K5
93 (L3)

B/H/T
=D0-X421

95 (PE)

FU
96 (U)
97 (V)
=H0-X3

98 (W)
99 (PE)

31MM
=D0-X422

31MM
TRANSFORMER

=D0-23U2 =D0-21U2
400/230V

=H05T1

MCA 110 MCA 110


3kVA

200

165
=M0-25U2 =D0-22U2
=D0-X423

MCA 110 MCA 110


=D0-24K11

47
47 mm 31MM
LEAVING FILTER
162 31 162 LEAVING FILTER
IN SIDE WALL
IN SIDE WALL

SWITCH PANEL :
800X1600X500MM
3.B 3.L
DATE 2013-02-20 COMMISSION : LS-71366/07.04.1 EQUIPMENT G0 A 0091 04 60201857290 =
proc. PBR Ammann Asphalt
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 +
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 3.C
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

MIDDLE

140
267

35
27
BURNER CONTROL

Etamatic S
=T2-41A1

OUTBREAK
234X138 MM (BXH)

Einbaumaße (Tiefe):
142

125 mm

26
DISPLAY
=M0-21A1 DOOR FT2742.000
ACTIVE POWER METER

OUTBREAK
CA. 92X92 MM

Sineax A 210
20

PANEL DOOR SWITCH PANEL 800 X 1600 MM


LEFT WITH 100MM BASE

3.C 3.MR
DATE 2013-02-20 COMMISSION : LS-71366/07.04.1 EQUIPMENT DOOR LEFT G0 A 0091 04 60201857290 =
proc. PBR Ammann Asphalt
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 +
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 3.L
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

235
MIDDLE

100 60 20 20 60 100

EMERGENCY CONTROL
VOLTAGE COMPRESSOR
UNLOCK

BK

WH WH

-3S0 -7S2 -41H1


-7H2
60

0-1
RD

-7S1
-41S1
70

BITUMEN HEATING HEATING


PIPE HEATING BITUMEN HEATING BURNER
CIRCUIT 1 PUMP 1 OIL PIPES 1 PRESSURE PUMP

WH WH WH WH

-71H1 -65H1 -82H1 -87H1


60

0-1 0-1 0-1 0-1

-71S1 -65S1 -82S1 -87S1

PANEL DOOR RIGHT SWITCH PANEL 800 X 1600 MM


WITH 100MM BASE

3.L 4
DATE 2013-02-20 COMMISSION : LS-71366/07.04.1 EQUIPMENT G0 A 0091 04 60201857290 =
proc. PBR Ammann Asphalt
CLIENT : Ammann do Brasil PANEL DOOR MIDDLE RIGHT SWITCH PANEL G0 +
Appr
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 3.MR
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

MATERIAL LIST
DESIGNATION
PAGE.PATH ID QUANTITY REMARK
ARTICLE NUMBER OPERATION
Schrank B= 800 H=1600 T=500 TS8865.009
/3.A.6 =G0-SS 3 1225178
Seitenwand H=1600 T=500 TS8165.235 RITTA
/3.A.6 =G0-SS 2 1225179
Schaltschrank-Kabelabfang- schiene 800~
/3.A.6 =G0-SS 3 H0134613
Schaltschrank-Klemmprofil Typ SZ 2573 ~
/3.A.6 =G0-SS 6 H5011252
Schaltschrank PE-Anschluss
/3.A.6 =G0-SS 2 H9903348
Schaltschrank-180°-Scharniere TS8 Best.~
/3.A.6 =G0-SS 12 H9907738
Anreihverbinder TS8800.500 RITTAL
/3.A.6 =G0-SS 12 H9907699
Sammelschienenträger
/3.A.6 =G0-SS 14 1077731
Endabdeckung
/3.A.6 =G0-SS 6 1077733
Schiene
/3.A.6 =G0-SS 3 H5011963
Sammelschienenklemme
/3.A.6 =G0-SS 6 H9903148
Sammelschienenverbinder
/3.A.6 =G0-SS 9 H9903154
Austrittsfilter
/3.A.6 =G0-SS 2 1117319

/3.A.6 =G0-SS 8 J917188


Schaltschrank-Montageplatten- Fixierung~
/3.A.6 =G0-SS 6 H9916559
Konsole
/3.A.6 =G0-SS 1 1234140
Isolator
/3.A.6 =G0-SS 2 H5011585
Masseband
/3.A.6 =G0-SS 5 H0081470

3.MR 4.A
DATE 2013-05-30 COMMISSION : LS-71366/07.04.1 MATERIAL LIST G0 A 0091 04 60201857290 =
proc. UGR Ammann Asphalt
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 +
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 4
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

MATERIAL LIST
DESIGNATION
PAGE.PATH ID QUANTITY REMARK
ARTICLE NUMBER OPERATION
Gewindebuchse
/3.A.6 =G0-SS 1 H0144399

/3.A.6 =G0-SS 2 J917194

/3.A.6 =G0-SS 4 1242393


Stecker
/3.A.8 =G0-FB 4 H0130867
Steckergehäuse
/3.A.8 =G0-FB 8 H9901417
Stecker
/3.A.8 =G0-FB 4 H9901423
Befestigungsschiene
/3.L.3 =T2-TSL 3 H9910200

/3.L.3 =T2-TSL 1 1233246

/3.L.3 =T2-TSL 1 1233247


Blindverschluß
/3.MR.3 =H0_TSM 10 H9912858
Summenstromwandler
=H0/11.1 =H0-1T1 1 H9915672
Schalter
=H0/11.1 =H0-1Q1 1 1066417
Einspeisung 400VAC
Schalter
=H0/11.1 =H0-1Q1 1 H9918107
=
Lasttrennschalter-Drehantrieb
=H0/11.1 =H0-1Q1 1 1066455
=
Schalter
=H0/11.1 =H0-1Q1 1 1066464
=
Schalter
=H0/11.1 =H0-1Q1 1 1066485
=
Schalter
=H0/11.1 =H0-1Q1 1 H9918163
=
Schalter
=H0/11.1 =H0-1Q1 1 1066429
=

4 4.B
DATE 2013-05-30 COMMISSION : LS-71366/07.04.1 MATERIAL LIST G0 A 0091 04 60201857290 =
proc. UGR Ammann Asphalt
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 +
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 4.A
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

MATERIAL LIST
DESIGNATION
PAGE.PATH ID QUANTITY REMARK
ARTICLE NUMBER OPERATION
FI-Steuerrelais
=H0/11.3 =H0-1F1 1 H9915688
Motorschutzschalter-Strombegr.
=H0/11.4 =H0-1Q21 1 H9902611
Motorschutzschalter
=H0/11.4 =H0-1Q2 1 J914662
Einspeisung Container
Drehgriff
=H0/11.4 =H0-1Q2 1 J915194
=
Motorschutzschalter-Strombegr.
=H0/11.6 =H0-1Q30 1 H9902611
Motorschutzschalter
=H0/11.6 =H0-1Q3 1 J914662
Heizungen Schaltschränke Kondensatableiter
Drehgriff
=H0/11.6 =H0-1Q3 1 J915194
=
FI-Schutzschalter
=H0/11.6 =H0-1F3 1 H9916143
Motorschutzschalter-Strombegr.
=H0/11.7 =H0-1Q50 1 H9902611
Einspeisung Steuertrafo
Motorschutzschalter
=H0/11.7 =H0-1Q5 1 J914662
=
Drehgriff
=H0/11.7 =H0-1Q5 1 J915194
=
Notaustaster
=H0/13.1 =H0-3S1 1 1020911
Not-Aus Steuercontainer
Not-Aus
=H0/13.3 =H0-3F1 1 H9913630
Drucktastevorsatz
=H0/13.4 =H0-3S0 1 1020936
Not-Aus entsperren
Befestigungsadapter
=H0/13.4 =H0-3S0 1 1021142
=
Kontaktelement
=H0/13.4 =H0-3S0 1 1020953
=
Schildträger
=H0/13.4 =H0-3S0 1 1021117
=
Einlegeschild
=H0/13.4 =H0-3S0 0 1021118
=

4.A 4.C
DATE 2013-05-30 COMMISSION : LS-71366/07.04.1 MATERIAL LIST G0 A 0091 04 60201857290 =
proc. UGR Ammann Asphalt
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 +
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 4.B
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

MATERIAL LIST
DESIGNATION
PAGE.PATH ID QUANTITY REMARK
ARTICLE NUMBER OPERATION
Schütz
=H0/13.7 =H0-3K1 1 1065853
Freigabe Hauptschalter
Hilfsschalter
=H0/13.7 =H0-3K1 1 1065946
=
Schutzglied
=H0/13.7 =H0-3K1 1 1065983
=
Leitungsschutzschalter
=H0/16.2 =H0-5F21 1 H9910577
U-Spulen
Motorschutzschalter Grundgerät PKE12
=H0/17.2 =H0-5Q1 1 1154663
Freigabe Steuerspannung
Motorschutzauslöseblock PKE-XTU-4
=H0/17.2 =H0-5Q1 1 1154666
=
Drehgriff
=H0/17.2 =H0-5Q1 1 J915194
=
Geräteadapter
=H0/17.2 =H0-5Q1 1 1176820
=
Geräteadapter-Anschlussleitungen
=H0/17.2 =H0-5Q1 2 1111749
=
Schütz
=H0/17.2 =H0-5K1 1 1065928
Steuerspannung 230VAC
Schutzglied
=H0/17.2 =H0-5K1 1 1065984
=
Trafo
=H0/17.2 =H0-5T1 1 H9913252
=
Leitungsschutzschalter
=H0/17.3 =H0-5F2 1 H9910583
Steuerspannung Interbus-S
Leitungsschutzschalter
=H0/17.5 =H0-5F3 1 H9910583
Leitungsschutzschalter
=H0/17.7 =H0-6F1 1 H9910577
Steuerspannung 24VDC ungeschaltet
Stromversorgung
=H0/17.7 =H0-6G1 1 H9915349
=
Drucktastevorsatz
=H0/18.1 =H0-7S1 1 1020935
Steuerspannung Aus - Ein
Befestigungsadapter
=H0/18.1 =H0-7S1 1 1021142
=

4.B 4.D
DATE 2013-05-30 COMMISSION : LS-71366/07.04.1 MATERIAL LIST G0 A 0091 04 60201857290 =
proc. UGR Ammann Asphalt
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 +
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 4.C
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

MATERIAL LIST
DESIGNATION
PAGE.PATH ID QUANTITY REMARK
ARTICLE NUMBER OPERATION
Kontaktelement
=H0/18.1 =H0-7S1 1 1020954
Steuerspannung Aus - Ein
Drucktastenvorsatz
=H0/18.1 =H0-7S2 1 1044806
=
Befestigungsadapter
=H0/18.1 =H0-7S2 1 1021142
=
LED-Element
=H0/18.1 =H0-7S2 1 1021046
=
Kontaktelement
=H0/18.1 =H0-7S2 1 1020953
=
Schildträger
=H0/18.1 =H0-7S2 1 1021117
=
Schütz
=H0/18.1 =H0-7K1 1 1065853
=
Hilfsschalter
=H0/18.1 =H0-7K1 1 1065946
=
Schutzglied
=H0/18.1 =H0-7K1 1 1065983
=
Stillstandswächter
=H0/18.4 =H0-7U1 1 H0142446
Relaisklemme
=H0/18.6 =H0-7K12 1 1019879
Anlage Ein (Impuls)
Zugfederklemme push-in
=H0/18.7 =H0-7D1 1 1229583
Relais
=H0/18.7 =H0-7K2 1 J911166
Relaissockel
=H0/18.7 =H0-7K2 1 1074058
Stromversorgung
=H0/20.7 =H0-8G2 1 H9915349
Busklemme
=H0/21.2 =G0-BK1 1 1085296
Digitaleingang
=H0/21.3 =G0-D1E32 1 1085310
Digitaleingang
=H0/21.5 =G0-D2E32 1 1085310

4.C 4.E
DATE 2013-05-30 COMMISSION : LS-71366/07.04.1 MATERIAL LIST G0 A 0091 04 60201857290 =
proc. UGR Ammann Asphalt
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 +
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 4.D
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

MATERIAL LIST
DESIGNATION
PAGE.PATH ID QUANTITY REMARK
ARTICLE NUMBER OPERATION
Digitalausgang
=H0/21.6 =G0-D1A32 1 1085311
Digitalausgang
=H0/21.8 =G0-D2A32 1 1085311
Analogeingang
=H0/22.3 =G0-A1E8 1 1085320
Stecker
=H0/22.3 =G0-A1E8 1 1054099
Analogeingang IBIL SGI2/F-PAC DMS
=H0/22.5 =G0-A2E2 1 1227144
Stecker
=H0/22.5 =G0-A2E2 1 1054099
Analogeingang IBIL SGI2/F-PAC DMS
=H0/22.6 =G0-A3E2 1 1227144
Stecker
=H0/22.6 =G0-A3E2 1 1054099
Analogeingang
=H0/22.7 =G0-A4E2 1 1085319
Motorschutzauslöseblock PKE-XTU-65
=H0/62.1 =H0-41Q1 1 1170349
Kompressor
mit Schraubklemmen für Anschlussquerschnitt von 1mm² bis 16mm²
=H0/62.1 =H0-41Q1 1 1213725
=
Geräteadapter-Verbreiterung
=H0/62.1 =H0-41Q1 1 1111326
=
Geräteadapter
=H0/62.1 =H0-41Q1 1 J916275
=
Hilfsschalter
=H0/62.1 =H0-41Q1 1 J915189
=
Drehgriff
=H0/62.1 =H0-41Q1 1 J915194
=
Knebelgriff
=H0/63.2 =H0-41S1 1 1020932
Kompressor Ein
Befestigungsadapter
=H0/63.2 =H0-41S1 1 1021142
=
Kontaktelement
=H0/63.2 =H0-41S1 1 1020953
=

4.D 4.F
DATE 2013-05-30 COMMISSION : LS-71366/07.04.1 MATERIAL LIST G0 A 0091 04 60201857290 =
proc. UGR Ammann Asphalt
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 +
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 4.E
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

MATERIAL LIST
DESIGNATION
PAGE.PATH ID QUANTITY REMARK
ARTICLE NUMBER OPERATION
Zeitrelais
=H0/63.2 =H0-41K1T 1 J917031
Kompressor Ein
Meldeleuchtevorsatz
=H0/63.3 =H0-41H1 1 1020960
=
Befestigungsadapter
=H0/63.3 =H0-41H1 1 1021142
=
LED-Element
=H0/63.3 =H0-41H1 1 1021039
=
Schildträger
=H0/63.3 =H0-41H1 1 1021117
=
Kompaktstarter PKE12 230V auf SS-Adapter
=H0/76.1 =H0-65Q3 1 1163053
Heizung Bitumenpumpe 1
Motorschutzauslöseblock PKE-XTU-12
=H0/76.1 =H0-65Q3 1 1154667
=
Geräteadapter-Verbreiterung
=H0/76.1 =H0-65Q3 1 1111326
=
Thermostat
=H0/76.4 =H0-65U1 1 1060582
Thermostat
=H0/76.6 =H0-65U2 1 1060582
Regler: Kühlung
Relais
=H0/77.5 =H0-65K5 1 J911166
Relaissockel
=H0/77.5 =H0-65K5 1 1074058
Knebelgriff
=H0/77.6 =H0-65S1 1 1020932
Heizung Bitumenpumpe Ein
Befestigungsadapter
=H0/77.6 =H0-65S1 1 1021142
=
Kontaktelement
=H0/77.6 =H0-65S1 1 1020953
=
Schutzglied
=H0/77.6 =H0-65K3 1 1065986
=
Hilfsschalter
=H0/77.6 =H0-65K3 1 1065946
=
Meldeleuchtevorsatz
=H0/77.9 =H0-65H1 1 1020960
Ein

4.E 4.G
DATE 2013-05-30 COMMISSION : LS-71366/07.04.1 MATERIAL LIST G0 A 0091 04 60201857290 =
proc. UGR Ammann Asphalt
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 +
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 4.F
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

MATERIAL LIST
DESIGNATION
PAGE.PATH ID QUANTITY REMARK
ARTICLE NUMBER OPERATION
Befestigungsadapter
=H0/77.9 =H0-65H1 1 1021142
Ein
LED-Element
=H0/77.9 =H0-65H1 1 1021039
=
Schildträger
=H0/77.9 =H0-65H1 1 1021117
=
Motorschutzauslöseblock PKE-XTU-12
=H0/81.1 =H0-71Q1 1 1154667
Rohrheizkreis 1
Geräteadapter
=H0/81.1 =H0-71Q1 1 1111323
=
Geräteadapter-Verbreiterung
=H0/81.1 =H0-71Q1 1 1111326
=
Motorschutzschalter Grundgerät PKE12
=H0/81.1 =H0-71Q1 1 1154663
=
Hilfsschalter
=H0/81.1 =H0-71Q1 1 J915189
=
Drehgriff
=H0/81.1 =H0-71Q1 1 J915194
=
Knebelgriff
=H0/81.5 =H0-71S1 1 1020932
Bitumen Rohrheizkreis 1 Ein
Befestigungsadapter
=H0/81.5 =H0-71S1 1 1021142
=
Kontaktelement
=H0/81.5 =H0-71S1 1 1020953
=
Schütz
=H0/81.5 =H0-71K1 1 1065853
=
Schutzglied
=H0/81.5 =H0-71K1 1 1065983
=
Meldeleuchtevorsatz
=H0/81.7 =H0-71H1 1 1020960
=
Befestigungsadapter
=H0/81.7 =H0-71H1 1 1021142
=
LED-Element
=H0/81.7 =H0-71H1 1 1021039
=
Schildträger
=H0/81.7 =H0-71H1 1 1021117
=

4.F 4.H
DATE 2013-05-30 COMMISSION : LS-71366/07.04.1 MATERIAL LIST G0 A 0091 04 60201857290 =
proc. UGR Ammann Asphalt
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 +
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 4.G
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

MATERIAL LIST
DESIGNATION
PAGE.PATH ID QUANTITY REMARK
ARTICLE NUMBER OPERATION
Thermostat
=H0/83.2 =H0-71U1 1 1060582
Messumformer
=H0/83.5 =H0-71U3 1 H9914167
Bitumentemperatur
Zugfederklemme 499
=H0/83.6 =H0-71R1 1 1240940
Motorschutzauslöseblock PKE-XTU-12
=H0/91.1 =H0-82Q1 1 1154667
Heizung Ölleitung 1
Geräteadapter
=H0/91.1 =H0-82Q1 1 1111323
=
Geräteadapter-Verbreiterung
=H0/91.1 =H0-82Q1 1 1111326
=
Motorschutzschalter Grundgerät PKE12
=H0/91.1 =H0-82Q1 1 1154663
=
Hilfsschalter
=H0/91.1 =H0-82Q1 1 J915189
=
Drehgriff
=H0/91.1 =H0-82Q1 1 J915194
=
Knebelgriff
=H0/91.5 =H0-82S1 1 1020932
Ein
Befestigungsadapter
=H0/91.5 =H0-82S1 1 1021142
=
Kontaktelement
=H0/91.5 =H0-82S1 1 1020953
=
Schütz
=H0/91.5 =H0-82K1 1 1065853
=
Schutzglied
=H0/91.5 =H0-82K1 1 1065983
=
Hilfsschalter
=H0/91.5 =H0-82K1 1 1065946
=
Meldeleuchtevorsatz
=H0/91.7 =H0-82H1 1 1020960
=
Befestigungsadapter
=H0/91.7 =H0-82H1 1 1021142
=
LED-Element
=H0/91.7 =H0-82H1 1 1021039
=

4.G 4.I
DATE 2013-05-30 COMMISSION : LS-71366/07.04.1 MATERIAL LIST G0 A 0091 04 60201857290 =
proc. UGR Ammann Asphalt
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 +
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 4.H
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

MATERIAL LIST
DESIGNATION
PAGE.PATH ID QUANTITY REMARK
ARTICLE NUMBER OPERATION
Schildträger
=H0/91.7 =H0-82H1 1 1021117
Ein
Thermostat
=H0/92.2 =H0-82U1 1 1060582
Schütz
=H0/94.8 =H0-85K1 1 1065853
Ein
Schutzglied
=H0/94.8 =H0-85K1 1 1065983
=
Kompaktstarter PKE12 230V auf HS-Träger
=H0/95.1 =H0-87Q1 1 1163055
Heizung Druckpumpe
Motorschutzauslöseblock PKE-XTU-4
=H0/95.1 =H0-87Q1 1 1154666
=
Geräteadapter
=H0/95.1 =H0-87Q1 1 1176820
=
Geräteadapter-Anschlussleitungen
=H0/95.1 =H0-87Q1 1 1111749
=
Knebelgriff
=H0/95.6 =H0-87S1 1 1020932
Ein
Befestigungsadapter
=H0/95.6 =H0-87S1 1 1021142
=
Kontaktelement
=H0/95.6 =H0-87S1 1 1020953
=
Schutzglied
=H0/95.6 =H0-87K1 1 1065986
=
Hilfsschalter
=H0/95.6 =H0-87K1 1 1065946
=
Meldeleuchtevorsatz
=H0/95.8 =H0-87H1 1 1020960
=
Befestigungsadapter
=H0/95.8 =H0-87H1 1 1021142
=
LED-Element
=H0/95.8 =H0-87H1 1 1021039
=
Schildträger
=H0/95.8 =H0-87H1 1 1021117
=
Busmodul
=D0/21.1 =D0-21U2 1 1042718

4.H 4.J
DATE 2013-05-30 COMMISSION : LS-71366/07.04.1 MATERIAL LIST G0 A 0091 04 60201857290 =
proc. UGR Ammann Asphalt
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 +
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 4.I
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

MATERIAL LIST
DESIGNATION
PAGE.PATH ID QUANTITY REMARK
ARTICLE NUMBER OPERATION
Frequenzumrichter
=D0/21.3 =D0-21U1 1 1042669
Motorschutzauslöseblock PKE-XTU-12
=D0/21.3 =D0-21Q1 1 1154667
Doseur 1
Kompaktstarter PKE12 230V auf SS-Adapter
=D0/21.3 =D0-21Q1 1 1163053
=
Geräteadapter-Verbreiterung
=D0/21.3 =D0-21Q1 1 1111326
=
Endschalter
=D0/21.7 =D0-21B2 0 H0470471
Materialmangel
Schutzglied
=D0/21.9 =D0-21K1 1 1065986
Einspeisung Ein
Busmodul
=D0/31.1 =D0-22U2 1 1042718
Frequenzumrichter
=D0/31.3 =D0-22U1 1 1042669
Motorschutzauslöseblock PKE-XTU-12
=D0/31.3 =D0-22Q1 1 1154667
Doseur 2
Kompaktstarter PKE12 230V auf SS-Adapter
=D0/31.3 =D0-22Q1 1 1163053
=
Geräteadapter-Verbreiterung
=D0/31.3 =D0-22Q1 1 1111326
=
Endschalter
=D0/31.7 =D0-22B2 0 H0470471
Materialmangel
Schutzglied
=D0/31.9 =D0-22K1 1 1065986
Einspeisung Ein
Busmodul
=D0/41.1 =D0-23U2 1 1042718
Frequenzumrichter
=D0/41.3 =D0-23U1 1 1042669
Motorschutzauslöseblock PKE-XTU-12
=D0/41.3 =D0-23Q1 1 1154667
Doseur 3
Kompaktstarter PKE12 230V auf SS-Adapter
=D0/41.3 =D0-23Q1 1 1163053
=
Geräteadapter-Verbreiterung
=D0/41.3 =D0-23Q1 1 1111326
=

4.I 4.K
DATE 2013-05-30 COMMISSION : LS-71366/07.04.1 MATERIAL LIST G0 A 0091 04 60201857290 =
proc. UGR Ammann Asphalt
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 +
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 4.J
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

MATERIAL LIST
DESIGNATION
PAGE.PATH ID QUANTITY REMARK
ARTICLE NUMBER OPERATION
Endschalter
=D0/41.7 =D0-23B2 0 H0470471
Materialmangel
Schutzglied
=D0/41.9 =D0-23K1 1 1065986
Einspeisung Ein
Motorschutzauslöseblock PKE-XTU-1,2
=D0/42.1 =D0-24Q1 1 1154665
Rüttler Materialmangel
Kompaktstarter PKE12 230V auf SS-Adapter
=D0/42.1 =D0-24Q1 1 1163053
=
Geräteadapter-Verbreiterung
=D0/42.1 =D0-24Q1 1 1111326
=
Schutzglied
=D0/42.5 =D0-24K1 1 1065986
Rüttler Ein
Relaisklemme
=D0/42.6 =D0-24K11 1 1019879
=
Hupe
=T0/21.2 =T0-10H1 1 H5010975
Hupe Trockner
Relaisklemme
=T0/21.8 =T0-10K11 1 1019879
Anfahrwarnung Trockner
Motorschutzauslöseblock PKE-XTU-32
=T0/26.1 =T0-25Q1 1 1154668
Trommel Motor 1
Kompaktstarter PKE32 230V auf SS-Adapter
=T0/26.1 =T0-25Q1 1 1163054
=
Geräteadapter-Verbreiterung
=T0/26.1 =T0-25Q1 1 1111326
=
Motorschutzauslöseblock PKE-XTU-32
=T0/26.3 =T0-25Q2 1 1154668
Trommel Motor 2
Kompaktstarter PKE32 230V auf SS-Adapter
=T0/26.3 =T0-25Q2 1 1163054
=
Geräteadapter-Verbreiterung
=T0/26.3 =T0-25Q2 1 1111326
=
Motorschutzauslöseblock PKE-XTU-32
=T0/26.5 =T0-25Q3 1 1154668
Trommel Motor 3
Kompaktstarter PKE32 230V auf SS-Adapter
=T0/26.5 =T0-25Q3 1 1163054
=
Geräteadapter-Verbreiterung
=T0/26.5 =T0-25Q3 1 1111326
=

4.J 4.L
DATE 2013-05-30 COMMISSION : LS-71366/07.04.1 MATERIAL LIST G0 A 0091 04 60201857290 =
proc. UGR Ammann Asphalt
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 +
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 4.K
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

MATERIAL LIST
DESIGNATION
PAGE.PATH ID QUANTITY REMARK
ARTICLE NUMBER OPERATION
Motorschutzauslöseblock PKE-XTU-32
=T0/26.7 =T0-25Q4 1 1154668
Trommel Motor 4
Kompaktstarter PKE32 230V auf SS-Adapter
=T0/26.7 =T0-25Q4 1 1163054
=
Geräteadapter-Verbreiterung
=T0/26.7 =T0-25Q4 1 1111326
=
Relais
=T0/27.2 =T0-25K11 1 J911166
Trommel
Relaissockel
=T0/27.2 =T0-25K11 1 1074058
=
Schutzglied
=T0/27.3 =T0-25K1 1 1065986
=
Hilfsschalter
=T0/27.3 =T0-25K1 1 1065946
=
Schutzglied
=T0/27.4 =T0-25K2 1 1065986
Hilfsschalter
=T0/27.4 =T0-25K2 1 1065946
Schutzglied
=T0/27.5 =T0-25K3 1 1065986
Schutzglied
=T0/27.6 =T0-25K4 1 1065986
Motorschutzauslöseblock PKE-XTU-12
=T0/32.1 =T0-29Q1 1 1154667
Aufgabeband vor
Kompaktstarter PKE12 230V auf SS-Adapter
=T0/32.1 =T0-29Q1 1 1163053
=
Geräteadapter-Verbreiterung
=T0/32.1 =T0-29Q1 1 1111326
=
Motorschutzauslöseblock PKE-XTU-12
=T0/32.3 =T0-29Q2 1 1154667
Aufgabeband zurück
Kompaktstarter PKE12 230V auf SS-Adapter
=T0/32.3 =T0-29Q2 1 1163053
=
Geräteadapter-Verbreiterung
=T0/32.3 =T0-29Q2 1 1111326
=
Schutzglied
=T0/33.1 =T0-29K1 1 1065986
Aufgabeband 1 vor

4.K 4.M
DATE 2013-05-30 COMMISSION : LS-71366/07.04.1 MATERIAL LIST G0 A 0091 04 60201857290 =
proc. UGR Ammann Asphalt
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 +
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 4.L
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

MATERIAL LIST
DESIGNATION
PAGE.PATH ID QUANTITY REMARK
ARTICLE NUMBER OPERATION
Hilfsschalter
=T0/33.1 =T0-29K1 1 1065946
Aufgabeband 1 vor
Schutzglied
=T0/33.2 =T0-29K2 1 1065986
zurück
Hilfsschalter
=T0/33.2 =T0-29K2 1 1065946
=
Relaisklemme
=T0/33.5 =T0-29K11 1 1019879
Aufgabeband 1 vor
Relaisklemme
=T0/33.6 =T0-29K12 1 1019879
zurück
Motorschutzauslöseblock PKE-XTU-12
=T0/47.1 =T0-47Q1 1 1154667
Grobstaubschnecke 1
Kompaktstarter PKE12 230V auf SS-Adapter
=T0/47.1 =T0-47Q1 1 1163053
=
Geräteadapter-Verbreiterung
=T0/47.1 =T0-47Q1 1 1111326
=
Schutzglied
=T0/47.5 =T0-47K1 1 1065986
Grobstaubschnecke 1 Ein
Relaisklemme
=T0/47.6 =T0-47K11 1 1019879
=
Motorschutzauslöseblock PKE-XTU-12
=T0/48.1 =T0-48Q1 1 1154667
Grobstaubschnecke 2
Kompaktstarter PKE12 230V auf SS-Adapter
=T0/48.1 =T0-48Q1 1 1163053
=
Geräteadapter-Verbreiterung
=T0/48.1 =T0-48Q1 1 1111326
=
Schutzglied
=T0/48.5 =T0-48K1 1 1065986
Grobstaubschnecke 2 Ein
Relaisklemme
=T0/48.6 =T0-48K11 1 1019879
=
Motorschutzauslöseblock PKE-XTU-32
=T2/21.1 =T2-21Q1 1 1154668
Brennerventilator Netz
Kompaktstarter PKE32 230V auf SS-Adapter
=T2/21.1 =T2-21Q1 1 1163054
=
Geräteadapter-Verbreiterung
=T2/21.1 =T2-21Q1 1 1111326
=

4.L 4.N
DATE 2013-05-30 COMMISSION : LS-71366/07.04.1 MATERIAL LIST G0 A 0091 04 60201857290 =
proc. UGR Ammann Asphalt
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 +
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 4.M
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

MATERIAL LIST
DESIGNATION
PAGE.PATH ID QUANTITY REMARK
ARTICLE NUMBER OPERATION
Motorschutzauslöseblock PKE-XTU-32
=T2/21.3 =T2-21Q2 1 1154668
Brennerventilator Dreieck
Kompaktstarter PKE32 230V auf SS-Adapter
=T2/21.3 =T2-21Q2 1 1163054
=
Geräteadapter-Verbreiterung
=T2/21.3 =T2-21Q2 1 1111326
=
Schutzglied
=T2/22.1 =T2-21K1 1 1065986
Netzschütz
Hilfsschalter
=T2/22.1 =T2-21K1 1 1065946
=
Schütz
=T2/22.3 =T2-21K3 1 1065854
Sternschütz
Hilfsschalter
=T2/22.3 =T2-21K3 1 1065946
=
Sternpunktbrücke
=T2/22.3 =T2-21K3 1 1069133
=
Schutzglied
=T2/22.3 =T2-21K3 1 1065986
=
Schutzglied
=T2/22.4 =T2-21K2 1 1065986
Dreieckschütz
Hilfsschalter
=T2/22.4 =T2-21K2 1 1065946
=
Relaisklemme
=T2/22.6 =T2-21K11 1 1019879
Brennerventilator Stern/Netz Ein
Relaisklemme
=T2/22.7 =T2-21K12 1 1019879
Dreieck Ein
Motorschutzauslöseblock PKE-XTU-4
=T2/24.1 =T2-22Q1 1 1154666
Öl Druckpumpe
Kompaktstarter PKE12 230V auf SS-Adapter
=T2/24.1 =T2-22Q1 1 1163053
=
Geräteadapter-Verbreiterung
=T2/24.1 =T2-22Q1 1 1111326
=
Hilfsschalter
=T2/24.1 =T2-22Q1 1 1065946
=
Schutzglied
=T2/24.5 =T2-22K1 1 1065986
Öl Druckpumpe Ein

4.M 4.O
DATE 2013-05-30 COMMISSION : LS-71366/07.04.1 MATERIAL LIST G0 A 0091 04 60201857290 =
proc. UGR Ammann Asphalt
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 +
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 4.N
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

MATERIAL LIST
DESIGNATION
PAGE.PATH ID QUANTITY REMARK
ARTICLE NUMBER OPERATION
Relaisklemme
=T2/24.6 =T2-22K11 1 1019879
Öl Druckpumpe Ein
Relais
=T2/27.1 =T2-27K1 1 J911166
Leichtölbetrieb
Relaissockel
=T2/27.1 =T2-27K1 1 1074058
=
Relais
=T2/27.3 =T2-27K2 1 J911166
Schwerölbetrieb
Relaissockel
=T2/27.3 =T2-27K2 1 1074058
=
Tüllengehäuse
=T2/31.2 =IB-X2 1 1060379
=T2-W343 / 40polig / Code 2
Steckdoseneinsatz
=T2/31.2 =IB-X2 1 1060392
=
Crimpkontakt
=T2/31.2 =IB-X2 40 1060441
=
Codierstift
=T2/31.2 =IB-X2 2 1060375
=
Codierbuchse
=T2/31.2 =IB-X2 2 1060426
=
Messumformer
=T2/31.2 =IB-30U1 1 1206465
Zugfederklemme 499
=T2/31.3 =T2-30R2 1 1240940
Bus-Anbindung
=T2/41.1 =G0-BK2 1 1012960
Steckergehäuse
=T2/41.1 =G0-BK2 2 H9901417
Stecker
=T2/41.1 =G0-BK2 1 H0130867
Stecker
=T2/41.1 =G0-BK2 1 H9901423
Steckersatz
=T2/41.4 =T2-41A1 1 1164642
Brennersteuergerät
Zeitrelais
=T2/42.6 =T2-42K1T 1 J917031
Anlaufüberbrückung

4.N 4.P
DATE 2013-05-30 COMMISSION : LS-71366/07.04.1 MATERIAL LIST G0 A 0091 04 60201857290 =
proc. UGR Ammann Asphalt
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 +
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 4.O
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

MATERIAL LIST
DESIGNATION
PAGE.PATH ID QUANTITY REMARK
ARTICLE NUMBER OPERATION
Relaisklemme
=T2/42.7 =T2-42K1 1 1019880
Leitung ÖSYZ-J 25x0.75 mm2 abgeschirmt
=T2/43.4 =T2-W343 22 H0096889
Steuerkabel Brenner
Tüllengehäuse
=T2/43.7 =IB-X1 1 1060379
=T2-W243 / 40polig / Code 1
Steckdoseneinsatz
=T2/43.7 =IB-X1 1 1060392
=
Crimpkontakt
=T2/43.7 =IB-X1 40 1060441
=
Codierstift
=T2/43.7 =IB-X1 2 1060375
=
Codierbuchse
=T2/43.7 =IB-X1 2 1060426
=
Leitung ÖZ-J 25x1
=T2/43.7 =T2-W243 22 H0102977
Steuerkabel Brenner
Zeitrelais
=T2/46.7 =T2-46K1T 1 J917031
Überwachung Zerstäuberluft Druck min.
Relais
=T2/47.8 =T2-47K3 1 J917232
Druckluft okay
Relaissockel
=T2/47.8 =T2-47K3 1 1074059
=
Relaisklemme
=T2/48.8 =T2-48K1 1 1019880
Öldruck Minimum okay
Relaisklemme
=T2/48.9 =T2-48K2 1 1019880
Öldruck Maximum okay
Relaisklemme
=T2/48.9 =T2-48K3 1 1019880
Ölventile
Relais
=T2/48.10 =T2-48K4 1 J917232
Abschlußventil Lanze
Relaissockel
=T2/48.10 =T2-48K4 1 1074059
=
Relais
=T2/49.8 =T2-49K1 1 J917232
Öltemperatur vor dem Brenner
Relaissockel
=T2/49.8 =T2-49K1 1 1074059
=

4.O 4.Q
DATE 2013-05-30 COMMISSION : LS-71366/07.04.1 MATERIAL LIST G0 A 0091 04 60201857290 =
proc. UGR Ammann Asphalt
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 +
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 4.P
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

MATERIAL LIST
DESIGNATION
PAGE.PATH ID QUANTITY REMARK
ARTICLE NUMBER OPERATION
Relaisklemme
=T2/49.8 =T2-49K2 1 1019880
maximum
Relaisklemme
=T2/51.6 =T2-51K1 1 1019880
Zündventile Ein
Lasttrenner
=E0/21.1 =E0-21Q1 1 1096039
Exhaustor

=E0/21.1 =E0-21Q1 3 H9900257


=
Stellungsanzeige
=E0/21.1 =E0-21Q1 1 1096090
=
Motorschutzrelais
=E0/21.3 =E0-21F1 1 1066097
Relais
=E0/21.8 =E0-21F2 1 H9914567
Schütz
=E0/22.1 =E0-21K1 1 1065874
Netzschütz
Hilfsschalter
=E0/22.1 =E0-21K1 1 1065981
=
Schutzglied
=E0/22.1 =E0-21K1 1 1065987
=
Schütz
=E0/22.3 =E0-21K3 1 1065871
Sternschütz
Hilfsschalter
=E0/22.3 =E0-21K3 1 1065981
=
Schutzglied
=E0/22.3 =E0-21K3 1 1065987
=
Schütz-Sternbrücke
=E0/22.3 =E0-21K3 1 1066004
=
Schütz
=E0/22.4 =E0-21K2 1 1065874
Dreieckschütz
Hilfsschalter
=E0/22.4 =E0-21K2 1 1065981
=
Schutzglied
=E0/22.4 =E0-21K2 1 1065987
=
Relaisklemme
=E0/22.6 =E0-21K11 1 1019879
Stern/Netz Ein

4.P 4.R
DATE 2013-05-30 COMMISSION : LS-71366/07.04.1 MATERIAL LIST G0 A 0091 04 60201857290 =
proc. UGR Ammann Asphalt
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 +
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 4.Q
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

MATERIAL LIST
DESIGNATION
PAGE.PATH ID QUANTITY REMARK
ARTICLE NUMBER OPERATION
Relaisklemme
=E0/22.7 =E0-21K12 1 1019879
Dreieck Ein
Motorschutzauslöseblock PKE-XTU-1,2
=E0/24.1 =E0-22Q1 1 1154665
Drosselklappe
Kompaktstarter PKE12 230V auf SS-Adapter
=E0/24.1 =E0-22Q1 1 1163053
=
Geräteadapter-Verbreiterung
=E0/24.1 =E0-22Q1 1 1111326
=
Zugfederklemme 499
=E0/24.9 =E0-22R2 1 1240940
Relaisklemme
=E0/25.2 =E0-22K11 1 1019879
Drosselklappe
Relaisklemme
=E0/25.3 =E0-22K12 1 1019879
zu
Schutzglied
=E0/25.5 =E0-22K1 1 1065986
Drosselklappe
Hilfsschalter
=E0/25.5 =E0-22K1 1 1065946
=
Zugfederklemme 499
=E0/25.7 =E0-23R1 1 1240940
Motorschutzauslöseblock PKE-XTU-1,2
=E0/26.1 =E0-24Q1 1 1154665
Abreinigung 1
Kompaktstarter PKE12 230V auf SS-Adapter
=E0/26.1 =E0-24Q1 1 1163053
=
Geräteadapter-Verbreiterung
=E0/26.1 =E0-24Q1 1 1111326
=
Schutzglied
=E0/26.5 =E0-24K1 1 1065986
Abreinigung 1 Ein
Relaisklemme
=E0/26.6 =E0-24K11 1 1019879
=
Motorschutzauslöseblock PKE-XTU-1,2
=E0/27.1 =E0-25Q1 1 1154665
Abreinigung 2
Kompaktstarter PKE12 230V auf SS-Adapter
=E0/27.1 =E0-25Q1 1 1163053
=
Geräteadapter-Verbreiterung
=E0/27.1 =E0-25Q1 1 1111326
=

4.Q 4.S
DATE 2013-05-30 COMMISSION : LS-71366/07.04.1 MATERIAL LIST G0 A 0091 04 60201857290 =
proc. UGR Ammann Asphalt
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 +
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 4.R
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

MATERIAL LIST
DESIGNATION
PAGE.PATH ID QUANTITY REMARK
ARTICLE NUMBER OPERATION
Schutzglied
=E0/27.5 =E0-25K1 1 1065986
Abreinigung 2 Ein
Relaisklemme
=E0/27.6 =E0-25K11 1 1019879
=
Relais
=E0/32.3 =E0-30K1 1 J917232
Relaissockel
=E0/32.3 =E0-30K1 1 1074059
Zugfederklemme 499
=E0/33.3 =E0-31R1 1 1240940
Stromwandler
=M0/21.2 =M0-21T1 1 H0109836
Motorschutzauslöseblock PKE-XTU-32
=M0/21.2 =M0-21Q1 1 1154668
Mischer Motor 1 Netz
Kompaktstarter PKE32 230V auf SS-Adapter
=M0/21.2 =M0-21Q1 1 1163054
=
Geräteadapter-Verbreiterung
=M0/21.2 =M0-21Q1 1 1111326
=
Motorschutzauslöseblock PKE-XTU-32
=M0/21.4 =M0-21Q2 1 1154668
Mischer Motor 1 Dreieck
Kompaktstarter PKE32 230V auf SS-Adapter
=M0/21.4 =M0-21Q2 1 1163054
=
Geräteadapter-Verbreiterung
=M0/21.4 =M0-21Q2 1 1111326
=
Motorschutzauslöseblock PKE-XTU-32
=M0/21.6 =M0-22Q1 1 1154668
Mischer Motor 2 Netz
Kompaktstarter PKE32 230V auf SS-Adapter
=M0/21.6 =M0-22Q1 1 1163054
=
Geräteadapter-Verbreiterung
=M0/21.6 =M0-22Q1 1 1111326
=
Motorschutzauslöseblock PKE-XTU-32
=M0/21.8 =M0-22Q2 1 1154668
Mischer Motor 2 Dreieck
Kompaktstarter PKE32 230V auf SS-Adapter
=M0/21.8 =M0-22Q2 1 1163054
=
Geräteadapter-Verbreiterung
=M0/21.8 =M0-22Q2 1 1111326
=

4.R 4.T
DATE 2013-05-30 COMMISSION : LS-71366/07.04.1 MATERIAL LIST G0 A 0091 04 60201857290 =
proc. UGR Ammann Asphalt
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 +
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 4.S
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

MATERIAL LIST
DESIGNATION
PAGE.PATH ID QUANTITY REMARK
ARTICLE NUMBER OPERATION
Stromwandler
=M0/21.9 =M0-22T1 1 H0109836
Leistungsmessgerät
=M0/22.5 =M0-21A1 1 1129298
Wirkleistungszähler
Erweiterungsmod
=M0/22.5 =M0-21A1 1 1134732
=
Motorschutzschalter Grundgerät PKE12
=M0/22.6 =M0-21Q3 1 1154663
Leistung Mischer
Geräteadapter
=M0/22.6 =M0-21Q3 1 1111323
=
Drehgriff
=M0/22.6 =M0-21Q3 1 J915194
=
Motorschutzauslöseblock PKE-XTU-4
=M0/22.6 =M0-21Q3 1 1154666
=
Geräteadapter-Verbreiterung
=M0/22.6 =M0-21Q3 1 1111326
=
Zugfederklemme 499
=M0/22.9 =M0-21R1 1 1240940
Schutzglied
=M0/23.1 =M0-21K1 1 1065986
Netzschütz
Hilfsschalter
=M0/23.1 =M0-21K1 1 1065946
=
Schutzglied
=M0/23.2 =M0-22K1 1 1065986
Hilfsschalter
=M0/23.2 =M0-22K1 1 1065946
Schütz
=M0/23.3 =M0-21K3 1 1065853
Sternschütz
Hilfsschalter
=M0/23.3 =M0-21K3 1 1065946
=
Schutzglied
=M0/23.3 =M0-21K3 1 1065983
=
Schütz
=M0/23.4 =M0-22K3 1 1065853
Hilfsschalter
=M0/23.4 =M0-22K3 1 1065946

4.S 4.U
DATE 2013-05-30 COMMISSION : LS-71366/07.04.1 MATERIAL LIST G0 A 0091 04 60201857290 =
proc. UGR Ammann Asphalt
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 +
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 4.T
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

MATERIAL LIST
DESIGNATION
PAGE.PATH ID QUANTITY REMARK
ARTICLE NUMBER OPERATION
Schutzglied
=M0/23.4 =M0-22K3 1 1065983
Schutzglied
=M0/23.5 =M0-21K2 1 1065986
Dreieckschütz
Hilfsschalter
=M0/23.5 =M0-21K2 1 1065946
=
Schutzglied
=M0/23.6 =M0-22K2 1 1065986
Hilfsschalter
=M0/23.6 =M0-22K2 1 1065946
Relaisklemme
=M0/23.8 =M0-21K11 1 1019879
Mischer Stern/Netz Ein
Relaisklemme
=M0/23.9 =M0-21K12 1 1019879

=M0/25.2 =M0-15B1 1 1140824


Mischer Klappe Zähler

=M0/25.4 =M0-15B2 1 1140824


Mischer Klappe zu
Zugfederklemme 499
=M0/26.5 =M0-12R1 1 1240940
Busmodul
=M0/29.1 =M0-25U2 1 1042718
Frequenzumrichter
=M0/29.3 =M0-25U1 1 1042704
Motorschutzauslöseblock PKE-XTU-32
=M0/29.4 =M0-25Q1 1 1154668
Bitumenpumpe
Kompaktstarter PKE32 230V auf SS-Adapter
=M0/29.4 =M0-25Q1 1 1163054
=
Geräteadapter-Verbreiterung
=M0/29.4 =M0-25Q1 1 1111326
=
Schutzglied
=M0/29.9 =M0-25K1 1 1065986
=
Motorschutzauslöseblock PKE-XTU-32
=M0/35.4 =M0-35Q1 1 1154668
Kratzkettenförderer Motor Netz
Kompaktstarter PKE32 230V auf SS-Adapter
=M0/35.4 =M0-35Q1 1 1163054
=

4.T 4.V
DATE 2013-05-30 COMMISSION : LS-71366/07.04.1 MATERIAL LIST G0 A 0091 04 60201857290 =
proc. UGR Ammann Asphalt
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 +
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 4.U
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

MATERIAL LIST
DESIGNATION
PAGE.PATH ID QUANTITY REMARK
ARTICLE NUMBER OPERATION
Geräteadapter-Verbreiterung
=M0/35.4 =M0-35Q1 1 1111326
Kratzkettenförderer Motor Netz
Motorschutzauslöseblock PKE-XTU-32
=M0/35.5 =M0-35Q2 1 1154668
Kratzkettenförderer Motor Dreieck
Kompaktstarter PKE32 230V auf SS-Adapter
=M0/35.5 =M0-35Q2 1 1163054
=
Geräteadapter-Verbreiterung
=M0/35.5 =M0-35Q2 1 1111326
=
Schutzglied
=M0/36.1 =M0-35K1 1 1065986
Netzschütz
Hilfsschalter
=M0/36.1 =M0-35K1 1 1065946
=
Schütz
=M0/36.3 =M0-35K3 1 1065854
Sternschütz
Hilfsschalter
=M0/36.3 =M0-35K3 1 1065946
=
Schutzglied
=M0/36.3 =M0-35K3 1 1065986
=
Sternpunktbrücke
=M0/36.3 =M0-35K3 1 1069133
=
Schutzglied
=M0/36.3 =M0-35K2 1 1065986
Dreieckschütz
Hilfsschalter
=M0/36.3 =M0-35K2 1 1065946
=
Relaisklemme
=M0/36.4 =M0-35K11 1 1019879
Kratzkettenförderer Stern/Netz Ein
Relaisklemme
=M0/36.5 =M0-35K12 1 1019879

4.U 5
DATE 2013-05-30 COMMISSION : LS-71366/07.04.1 MATERIAL LIST G0 A 0091 04 60201857290 =
proc. UGR Ammann Asphalt
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 +
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 4.V
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

=G0-D1E32 =G0-D1A32

8.4 =E0/30.8 PARK POSITION CLEANING 2 8.4


BYTE 0 BYTE 0
8.3 =E0/30.7 PARK POSITION CLEANING 1 8.3
SLOT 4 SLOT 4
8.2 =T0/48.8 COARSE DUST SCREW 2 ERROR 8.2
8.1 =T0/48.7 COARSE DUST SCREW 2 ON 8.1 =T0/48.6 COARSE DUST SCREW 2 ON
7.4 =T0/47.8 COARSE DUST SCREW 1 ERROR 7.4
7.3 =T0/47.7 COARSE DUST SCREW 1 ON 7.3 =T0/47.6 COARSE DUST SCREW 1 ON
7.2 7.2
8.1

8.2

8.3

8.4

8.1

8.2

8.3

8.4
2

2
7.1 =T2/46.6 ATOMIZER AIR PRESSURE CLOSED DEEP 7.1
7.1

7.2

7.3

7.4

7.1

7.2

7.3

7.4
1

1
BYTE 1 6.4 =T2/47.9 COMPRESSED AIR PRESSURE CLOSED DEEP BYTE 1 6.4 =T2/42.10 RESET BURNER
SLOT 3 6.3 =T2/42.8 BURNER VENTILATOR START POSITION
SLOT 3 6.3 =T2/42.9 BURNER ON
6.2 =T2/24.8 FUEL OIL PRESSURE PUMP ERROR 6.2
6.1 =T2/24.7 FUEL OIL PRESSURE PUMP ON 6.1 =T2/24.6 FUEL OIL PRESSURE PUMP ON
5.4 5.4
5.3 =T2/22.9 BURNER VENTILATOR ERROR 5.3
5.2 =T2/22.8 BURNER VENTILATOR DELTA 5.2 =T2/22.7 BURNER VENTILATOR DELTA
6.1

6.2

6.3

6.4

6.1

6.2

6.3

6.4
2

2
5.1 =T2/22.7 BURNER VENTILATOR NET 5.1 =T2/22.6 BURNER VENTILATOR NET
5.1

5.2

5.3

5.4

5.1

5.2

5.3

5.4
1

1
BYTE 2 4.4 =D0/42.7 VIBRATOR MATERIAL SHORTAGE ERROR BYTE 2 4.4
SLOT 2 4.3 =D0/42.7 VIBRATOR MATERIAL SHORTAGE ON
SLOT 2 4.3 =D0/42.6 VIBRATOR MATERIAL SHORTAGE ON
4.2 =T0/33.7 FEEDING BELT 1 BACKWARDS 4.2 =T0/33.6 FEEDING BELT 1 BACKWARDS
4.1 =T0/33.7 FEEDING BELT 1 FORWARD 4.1 =T0/33.5 FEEDING BELT 1 FORWARD
3.4 =T0/33.8 FEEDING BELT 1 ERROR 3.4
3.3 3.3
3.2 =T0/28.3 DRUM ERROR 3.2
4.1

4.2

4.3

4.4

4.1

4.2

4.3

4.4
2

2
3.1 =T0/28.2 DRUM ON 3.1 =T0/27.2 DRUM ON
3.1

3.2

3.3

3.4

3.1

3.2

3.3

3.4
1

1
BYTE 3 2.4 =H0/62.9 COMPRESSOR ERROR BYTE 3 2.4
SLOT 1 2.3 =H0/76.9 HEATING BITUMEN PUMP ERROR
SLOT 1 2.3
2.2 =H0/77.7 TEMPERATURE BITUMEN PUMP OK 2.2
2.1 =H0/77.8 HEATING BITUMEN PUMP ON 2.1
1.4 1.4
1.3 1.3 =T0/21.8 DRYING HORN ON
1.2 =H0/19.9 CONTROL VOLTAGE ON 1.2 =H0/18.6 PLANT ON
2.1

2.2

2.3

2.4

2.1

2.2

2.3

2.4
2

1.1 =H0/13.2 CONTAINER EMERGENCY 1.1 =H0/18.5 WATCHDOG


1.1

1.2

1.3

1.4

1.1

1.2

1.3

1.4
1

INTERBUS-INLINE: IB IL 24 DI 32 HD PAC INTERBUS-INLINE: IB IL 24 DO 32 HD PAC

4.V 6
DATE 2012-12-07 COMMISSION : LS-71366/07.04.1 MODULAR DIGITAL G0 A 0091 04 60201857290 =
proc. UGR Ammann Asphalt
CLIENT : Ammann do Brasil INPUT DIGITAL SWITCH PANEL G0 +
Appr
ASPHALT MIXING PLANT D-31061 Alfeld OUTPUT CAD: 71366_G0
MODIFICATIONDATE NAME origin \\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 5
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

=G0-D2E32 =G0-D2A32

8.4 =T2/49.8 OIL TEMPERATURE BURNER MAX. 8.4


BYTE 0 BYTE 0
8.3 =T2/49.8 OIL TEMPERATURE BURNER MIN. 8.3
SLOT 4 SLOT 4
8.2 =T2/27.8 HEAVY OIL MODE ON 8.2 =T2/27.3 HEAVY OIL MODE ON
8.1 =T2/27.7 LIGHT OIL OPERATION ON 8.1 =T2/27.1 LIGHT OIL OPERATION ON
7.4 =H0/91.9 HEATING HEAVY FUEL ON 7.4
7.3 =H0/91.9 HEATING HEAVY FUEL ERROR 7.3
7.2 =H0/81.10 HEATING BITUMEN PIPE 1 ERROR 7.2
8.1

8.2

8.3

8.4

8.1

8.2

8.3

8.4
2

2
7.1 =H0/81.9 HEATING BITUMEN PIPE 1 ON 7.1
7.1

7.2

7.3

7.4

7.1

7.2

7.3

7.4
1

1
BYTE 1 6.4 =H0/81.8 BYTE 1 6.4
SLOT 3 6.3
SLOT 3 6.3
6.2 6.2
6.1 6.1
5.4 5.4 =M0/37.6 BATCHER FLAP OPEN
5.3 =M0/36.7 DRAG SLAT CONVEYOR ERROR 5.3
5.2 =M0/36.7 DRAG SLAT CONVEYOR DELTA 5.2 =M0/36.5 DRAG SLAT CONVEYOR DELTA
6.1

6.2

6.3

6.4

6.1

6.2

6.3

6.4
2

2
5.1 =M0/36.6 DRAG SLAT CONVEYOR NET 5.1 =M0/36.4 DRAG SLAT CONVEYOR NET
5.1

5.2

5.3

5.4

5.1

5.2

5.3

5.4
1

1
BYTE 2 4.4 =M0/25.4 MIXER CLOSED BYTE 2 4.4 =M0/25.8 MIXER FLAP CLOSED
SLOT 2 4.3 =M0/25.2 MIXER FLAP COUNTER
SLOT 2 4.3 =M0/25.6 MIXER FLAP OPEN
4.2 =M0/24.4 MIXER ERROR 4.2 =M0/27.6 AIR SCAVENGING MIXER OUTLET
4.1 =M0/24.3 MIXER DELTA 4.1 =M0/23.9 MIXER DELTA
3.4 =M0/24.2 MIXER NET 3.4 =M0/23.8 MIXER NET
3.3 =E0/24.6 THROTTLE FLAP ERROR 3.3
3.2 =E0/24.6 THROTTLE FLAP OPEN 3.2 =E0/25.2 THROTTLE FLAP OPEN
4.1

4.2

4.3

4.4

4.1

4.2

4.3

4.4
2

2
3.1 =E0/24.5 THROTTLE FLAP CLOSED 3.1 =E0/25.3 THROTTLE FLAP CLOSED
3.1

3.2

3.3

3.4

3.1

3.2

3.3

3.4
1

1
BYTE 3 2.4 =E0/27.8 CLEANING 2 ERROR BYTE 3 2.4
SLOT 1 2.3 =E0/27.7 CLEANING 2 ON
SLOT 1 2.3 =E0/27.6 CLEANING 2 ON
2.2 =E0/26.8 CLEANING 1 ERROR 2.2
2.1 =E0/26.7 CLEANING 1 ON 2.1 =E0/26.6 CLEANING 1 ON
1.4 1.4
1.3 =E0/22.9 EXHAUSTOR ERROR 1.3
1.2 =E0/22.8 EXHAUSTOR DELTA 1.2 =E0/22.7 EXHAUSTOR DELTA
2.1

2.2

2.3

2.4

2.1

2.2

2.3

2.4
2

1.1 =E0/22.7 EXHAUSTOR NET 1.1 =E0/22.6 EXHAUSTOR NET


1.1

1.2

1.3

1.4

1.1

1.2

1.3

1.4
1

INTERBUS-INLINE: IB IL 24 DI 32 HD PAC INTERBUS-INLINE: IB IL 24 DO 32 HD PAC

5 7
DATE 2012-12-07 COMMISSION : LS-71366/07.04.1 MODULAR DIGITAL G0 A 0091 04 60201857290 =
proc. UGR Ammann Asphalt
CLIENT : Ammann do Brasil INPUT DIGITAL SWITCH PANEL G0 +
Appr
ASPHALT MIXING PLANT D-31061 Alfeld OUTPUT CAD: 71366_G0
MODIFICATIONDATE NAME origin \\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 6
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

=G0-A1E8 =G0-A4E2

2.3 VOLTAGE INPUT 2 2.1


CONNECTOR 4

8.3 VOLTAGE INPUT 8 8.1 2.4 CURRENT INPUT 2 2.2


8.4 CURRENT INPUT 8 8.2 VOLTAGE INPUT 1
1.3 1.1 =M0/22.9 MIXING FLOW MOTOR 1+2
CURRENT INPUT 1
1.4 1.2
7.3 VOLTAGE INPUT 7 7.1 =H0/83.5 BITUMEN TEMPERATURE

2.1

2.2

2.3

2.4
2
CURRENT INPUT 7
7.4 7.2

1.1

1.2

1.3

1.4
1
INTERBUS-INLINE: IB IL AI 2/SF
8.1

8.2

8.3

8.4
2
7.1

7.2

7.3

7.4
1
CONNECTOR 3

6.3 VOLTAGE INPUT 6 6.1 =M0/26.4 COMPRESSED AIR

6.4 CURRENT INPUT 6 6.2

5.3 VOLTAGE INPUT 5 5.1 =M0/27.3 INFRA-RED MEASUREMENT MIXER OUTLET


CURRENT INPUT 5 5.2
5.4
6.1

6.2

6.3

6.4
2
5.1

5.2

5.3

5.4
1
CONNECTOR 2

4.3 VOLTAGE INPUT 4 4.1 =E0/33.3 TEMPERATURE CRUDE GAS

4.4 CURRENT INPUT 4 4.2

3.3 VOLTAGE INPUT 3 3.1 =E0/24.8 THROTTLE FLAP POSITION

3.4 CURRENT INPUT 3 3.2


4.1

4.2

4.3

4.4
2
3.1

3.2

3.3

3.4
1
CONNECTOR 1

2.3 VOLTAGE INPUT 2 2.1 =E0/25.7 NEGATIVE PRESSURE MEASURING MINERAL DRUM

2.4 CURRENT INPUT 2 2.2

VOLTAGE INPUT 1
1.3 1.1 =T2/31.2 DRUM TEMPERATURE FE-CUNI

1.4 CURRENT INPUT 1 1.2


2.1

2.2

2.3

2.4
2
1.1

1.2

1.3

1.4
1

INTERBUS-INLINE: IB IL AI 8/SF

6 =H0/11
DATE 2012-12-07 COMMISSION : LS-71366/07.04.1 MODULAR ANALOGUE G0 A 0091 04 60201857290 =
proc. UGR Ammann Asphalt
CLIENT : Ammann do Brasil INPUT ANALOGUE SWITCH PANEL G0 +
Appr
ASPHALT MIXING PLANT D-31061 Alfeld OUTPUT CAD: 71366_G0
MODIFICATIONDATE NAME origin \\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 7
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

400V +/-5% 3Ph 50Hz 2L1


2L2
2L3

2L1 2L2 2L3 3.14


=H0-1Q1 U<
1L1 1L2 1L3 3.13 D1 D2

N2

-1F1
MFR
X rt rt/ws
7 4
-1T1 a b
MFIW 105/0,5 5 3

6 8
d c

2X XX

2 4 6 2 4 6 2 4 6
-1Q21 -1Q30 -1Q50
CL-PKZM0 CL-PKZM0 CL-PKZM0
I>> I>> I>> I>> I>> I>> I>> I>> I>>
1 3 5 4 mm² 1 3 5 4 mm² 1 3 5

1 3 5 1 3 5 1 3 5
-1Q2 -1Q3 -1Q5
PKZM0-20 PKZM0-20 PKZM0-20
I> I> I> I> I> I> I> I> I>
2 4 6 4 mm² 2 4 6 2 4 6

1 3 5 7N
-1F3 T1 / 17.1
4 mm² 40/0,03A T2 / 17.1

2 4 6 8N

HEATING COMPRESSOR
H07RN-F 3x1,5 mm² 15 m
-W142
X
COVER PE PE
TERMINALS! =H0-X1 5 6 7 8 9 -X1 10 11 12 13 14
COVER
TERMINALS!
PE PE-RAIL CU 30X5MM PE BN BK GY BU GNYE BN BU GNYE
400VAC CONTAINER
H07RN-F 5x2,5 mm² 12 m
-W102

+142 PE PE PE
=CO-X0 L1 L2 L3 N PE
1L1 1L2 1L3 N PE PE
-X1 1 4 PE PE =H0-X21 1 1 2 2 20 20 3 4 20
ÖZ-J
3x1mm²
POWER SUPPLY
400VAC +42.1 -X1 1 2 PE 22 / 16.1
230VAC POWER SUPPLY 21 / 16.1
X = SEPARATE FITTING OF CABLES BEFORE MAIN SWITCH CONTROL TRANSFORMER
XX = SEPARATE FITTING OF CABLES BEFORE MAIN SWITCH WITH HIGH VOLTAGE CABLE 400VAC
CONTAINER STEAM TRAP POWER SUPPLY
=/7 COMPRESSOR LOW VOLTAGE COIL 13
DATE 2013-04-29 COMMISSION : LS-71366/07.04.1 Ammann Asphalt POWER SUPPLY G0 A 0091 04 60201857290 = H0
proc. UGR
CLIENT : Ammann do Brasil POWER SWITCH SWITCH PANEL G0 +
Appr
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 11
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

230VAC (P) UNSWITCHED


13L1 / 16.1
230VAC (N) UNSWITCHED
13L2 / 16.1
+24VDC UNSWITCHED
13L+ / 17.1

RD RD/WH RD RD/WH
BU BU
PE
=G0-D1E32 -3F1
PNOZ X4
INPUT A1 A2 PE Y36 Y37 13
34 24 13
EMERGENCY STOP SWITCH
1.1
33 23 14
S11 S12 S52 S21 S22 S33 S34 Y1 Y2 33 23 24 34 14

BU BU BU BU BU BU OR OR OR OR

21
-3K1
BU BU PE
/13.7 22
-X13 21 22 -X5 26 28 29 27 20
21
-7K1
/18.1 22

13
-3S0
EMERG. 14
UNLOCK

PE
-X13 1 101 103 2 20

A1
-3K1
M12-32 A2
230VAC

EMERGENCY EMERGENCY RELEASE


-W303.1 UNLOCK RESERVE MAIN SWITCH
BN GY BU BK GNYE
H07RN-F 5x1,5 mm² 12 m
EMERGENCY CONTAINER 1 2 /16.2
21 13
PE 3 4 /16.2
-3S1 5 6 /18.1
22 14 13 14 /30.2
21 22 /13.5
53 54 /30.2

EMERGENCY
11 CONTROL ROOM 16
DATE 2013-04-29 COMMISSION : LS-71366/07.04.1 Ammann Asphalt EMERGENCY G0 A 0091 04 60201857290 = H0
proc. UGR
CLIENT : Ammann do Brasil STOP SWITCH SWITCH PANEL G0 +
Appr
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 13
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

230VAC (P) UNSWITCHED


13.10 / 13L1 13L1 / 17.1
230VAC (N) UNSWITCHED
13.10 / 13L2 13L2 / 17.1

2 4
-5F21
FAZ- 1 3
2-D6
2,5 mm²
UNDERVOLTAGE RELAYS

1 3
-3K1
/13.7 2 4
2,5 mm²

PE PE COVER
=H0-X21 1 2 20 1 2 20 TERMINALS

11.9 / 21
11.9 / 22

FREE
POWER SUPPLY
LOW VOLTAGE COILS

13 17
DATE 2013-02-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt POWER SUPPLY LOW VOLTAGE COILS G0 A 0091 04 60201857290 = H0
proc. UGR
CLIENT : Ammann do Brasil ERROR BITUMEN COCK SWITCH PANEL G0 +
Appr
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 16
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

230VAC (P) UNSWITCHED


16.10 / 13L1 13L1 / 18.1
230VAC (N) UNSWITCHED
16.10 / 13L2 13L2 / 18.1
+24VDC UNSWITCHED
13.10 / 13L+ 13L+ / 18.1
0VDC UNSWITCHED
13L- / 18.1

2L1
400V +/-5% 3Ph 50Hz 2L1
2L2 2L2
2L3 2L3

1 3 5
-5Q1
4,0A ge
CLASS 10 I> I> I> 2 4 2 4 2 4
PKE12/XTU-4 2 4 6 -5F2 -5F3 -6F1
FAZ- 1 3 FAZ- 1 3 FAZ- 1 3
2-D10 2-D10 2-D6
2,5 mm² 2,5 mm² 2,5 mm²

A1
-5K1 L N
M12-10 A2
400VAC -6G1
230VAC/24VDC
5A - +
11.8 / T2
11.8 / T1
3.1
-X3
-5T1 3.2 ISOLATING TERMINAL
400/230VAC
3 kVA PE PE
PE

11 / 20.1
12 / 20.1

PE PE PE PE PE PE PE PE
-X2 11 11 11 11 11 12 12 12 12 12 20 20 20 20 20 -X2 11 12 20 20 13 14 13 14 20

3.1
-X2
3.2 ISOLATING TERMINAL

PE PE CONTROL VOLTAGE
CONTROL VOLTAGE
230VAC
PE 24VDC
UNSWITCHED
UNSWITCHED

1 2 /19.2
3 4 /19.2
5 6 /19.7
13 14 /19.7

CONTROL VOLTAGE CONTROL VOLTAGE


16 230VAC INTERBUS-S 18
DATE 2013-02-20 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CONTROL VOLTAGE G0 A 0091 04 60201857290 = H0
proc. PBR
CLIENT : Ammann do Brasil 230VAC SWITCH PANEL G0 +
Appr
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 17
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

230VAC (P) UNSWITCHED


17.10 / 13L1 13L1 / 19.1
+24VDC UNSWITCHED
17.10 / 13L+ 13L+ / 19.1

=G0-D1A32

-X2 1 OUTPUT OUTPUT


41 11
21 -7K2 1.1 1.2 -7K2
-7S1 /18.7 44 /18.7 14
RD 22

-X2 4

13 5 11
-7S2 -7K1 -7K12 -X3 15
WH 14 /18.1 6 /18.6 14
CONTROL VOLTAGE ON -7D1

-X3 16
X1
-7U1
Fkt. I 13 7 4E 5+
-7H2 5- 25
STANDSTILL MONITOR
Impl/min
X2 A300 IFM

-X2 5 -X2 2

12 14 6 3-

13
-7K1
5 /18.1 14
-3K1
/13.7 6

A1 A1 A1
-7K1 -7K12 -7K2
M12-32 A2 38.51 A2 55.34 A2
230V 24VDC 24VDC

230VAC (N) UNSWITCHED


17.10 / 13L2 13L2 / 19.1
0VDC UNSWITCHED
17.10 / 13L- 13L- / 19.1

CONTROL VOLTAGE WATCHDOG PLANT


OFF - ON ON
(IMPULSE)
1 2 /19.3 11 14 /18.4 11 14 /18.7
3 4 /19.3 41 44 /18.5
5 6 /18.3
13 14 /18.7
21 22 /13.5
43 44 /19.5
53 54 /19.6

17 19
DATE 2012-12-07 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CONTROL VOLTAGE ON G0 A 0091 04 60201857290 = H0
proc. UGR
CLIENT : Ammann do Brasil WATCHDOG SWITCH PANEL G0 +
Appr
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 18
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

230VAC (P) UNSWITCHED


18.10 / 13L1 13L1 / 20.1
230VAC (N) UNSWITCHED
18.10 / 13L2 13L2 / 20.1
+24VDC UNSWITCHED
18.10 / 13L+ 13L+ / 20.1
0VDC UNSWITCHED
18.10 / 13L- 13L- / 20.1
230VAC (P) SWITCHED (H0)
14L1 / 30.1
230VAC (N) SWITCHED (H0)
14L2 / 30.1
+24VDC SWITCHED (H0)
14L+ / 30.1
0VDC SWITCHED (H0)
14L- / 30.1
230VAC (P) SWITCHED
3L1 / =D0/13.1
230VAC (N) SWITCHED
3L2 / =D0/13.1
+24VDC SWITCHED
3L+ / =D0/13.1
0VDC SWITCHED
3L- / =D0/13.1

1 mm² 1 mm²

2,5 mm² 2,5 mm²

1.2
INPUT
-X3 1 1 1 2 2 2
=G0-D1E32
1 3 1 3 43 53 5 13
-5K1 -7K1 -7K1 -5K1
/17.2 2 4 /18.1 2 4 /18.1 44 54 /17.2 6 14

PE PE PE
-X2 1 1 2 2 17 17 17 18 18 18 21 21 21 21 21 22 22 22 22 22 20 -X3 21 21 21 22 22 22 20 -X3 17 17 17 18 18 18 20

230VAC 230VAC 230VAC (P) 230VAC (N) +24VDC +24VDC

13L1 13L2 14L1 14L2 SWITCHED 3L1 3L2 3L+ 3L- SWITCHED 14L+ 14L- SWITCHED
UNSWITCHED H0 SWITCHED SWITCHED H0

18 20
DATE 2013-02-04 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CONTROL VOLTAGE G0 A 0091 04 60201857290 = H0
proc. UGR
CLIENT : Ammann do Brasil 230VAC AND 24VDC SWITCH PANEL G0 +
Appr
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 19
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

230VAC (P) UNSWITCHED 13L+


19.10 / 13L1
230VAC (N) UNSWITCHED 13L+
19.10 / 13L2
+24VDC UNSWITCHED 13L+
19.10 / 13L+
0VDC UNSWITCHED 13L-
19.10 / 13L-

17.9 / 12 12 / =T2/41.1

17.9 / 11 11 / =T2/41.1 -X3 1 2


-W202
PE
H07RN-F 3x1,5 mm² 12 m L N
-X2 11 12 20 POWER SUPPLY
COMPUTER -8G2
BN BU GNYE 230VAC/24VDC
=RCO 5A + -

-X200 L1 N PE AS1 Push Control -X3 11 11 12 12


IN THE CONTROL STATION
IBS+ / =D0/21.1
IBS- / =D0/21.1

Interbus-IN Interbus-Out
verdrillen
. . . . . . . . . .
GN YE PK GY BN GN YE PK GY BN
PE PE

-O:1.1
=G0-BK1
I:1.1

2.1

1.2

2.2

1.3

2.4
1.4

2.1

1.2

2.2

1.3

2.4
1.4
1.1 2.1 1.2 1.3 1.4 1.1 1.2 1.3 1.4
2.2 2.3 2.4 2.1 2.2 2.3 2.4
/DO DO /DI DI F-GND SH /DO DO /DI DI F-GND SH Rekonfiguration 24V DC BK FE 24V DC GND GND FE
UBK GND Us UM

CONNECTOR 1 CONNECTOR 2 CONNECTOR 3 CONNECTOR 4


INTERBUS-INLINE
IBS IL 24 BK-T/U PAC

UPS VENTILATION CONNECTION CONNECTION FEED BUS POWER SUPPLY


INTERBUS-S INTERBUS-S TERMINAL LOCAL BUS
IN OUT

19 21
DATE 2013-04-29 COMMISSION : LS-71366/07.04.1 Ammann Asphalt FEED BUS G0 A 0091 04 60201857290 = H0
proc. UGR
CLIENT : Ammann do Brasil TERMINAL SWITCH PANEL G0 +
Appr
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 20
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

=G0-BK1 =G0-D1E32 =G0-D2E32 =G0-D1A32 =G0-D2A32

BA RD D DI 32 D DI 32 D DO 32 D DO 32
UL US
1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2

LD 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4
RC UM
5 6 5 6 5 6 5 6 5 6 5 6 5 6 5 6 5 6 5 6 5 6 5 6 5 6 5 6 5 6 5 6

7 8 7 8 7 8 7 8 7 8 7 8 7 8 7 8 7 8 7 8 7 8 7 8 7 8 7 8 7 8 7 8
BK-T/U

1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4
1.1 2.1 1.1 2.1 1.1 2.1 1.1 2.1 1.1 2.1 3.1 4.1 5.1 6.1 7.1 8.1 1.1 2.1 3.1 4.1 5.1 6.1 7.1 8.1 1.1 2.1 3.1 4.1 5.1 6.1 7.1 8.1 1.1 2.1 3.1 4.1 5.1 6.1 7.1 8.1

1.2 2.2 1.2 2.2 1.2 2.2 1.2 2.2 1.2 2.2 3.2 4.2 5.2 6.2 7.2 8.2 1.2 2.2 3.2 4.2 5.2 6.2 7.2 8.2 1.2 2.2 3.2 4.2 5.2 6.2 7.2 8.2 1.2 2.2 3.2 4.2 5.2 6.2 7.2 8.2

1.3 2.3 1.3 2.3 1.3 2.3 1.3 2.3 1.3 2.3 3.3 4.3 5.3 6.3 7.3 8.3 1.3 2.3 3.3 4.3 5.3 6.3 7.3 8.3 1.3 2.3 3.3 4.3 5.3 6.3 7.3 8.3 1.3 2.3 3.3 4.3 5.3 6.3 7.3 8.3

1.4 2.4 1.4 2.4 1.4 2.4 1.4 2.4 1.4 2.4 3.4 4.4 5.4 6.4 7.4 8.4 1.4 2.4 3.4 4.4 5.4 6.4 7.4 8.4 1.4 2.4 3.4 4.4 5.4 6.4 7.4 8.4 1.4 2.4 3.4 4.4 5.4 6.4 7.4 8.4

BUS TERMINAL DIGITAL INPUT DIGITAL INPUT DIGITAL OUTPUT DIGITAL OUTPUT
IBS IL 24 BK-T/U-PAC 32-CHANNEL 32-CHANNEL 32-CHANNEL 32-CHANNEL
IB IL 24 DI 32/HD-PAC IB IL 24 DI 32/HD-PAC IB IL 24 DO 32/HD-PAC IB IL 24 DO 32/HD-PAC

20 22
DATE 2012-12-07 COMMISSION : LS-71366/07.04.1 Ammann Asphalt ASSEMBLY INTERBUS G0 A 0091 04 60201857290 = H0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 +
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 21
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

=G0-A1E8 =G0-A2E2 =G0-A3E2 =G0-A4E2

D D D D
1 2 1 2

3 4 3 4

5 6 5 6

7 8 7 8
AI8SF

1 2 3 4 1 2 3 4
U1 U2 U3 U4 U5 U6 U7 U8 1.1 2.1 3.1 4.1 5.1 6.1 7.1 8.1 1.1 2.1 3.1 4.1 5.1 6.1 7.1 8.1 1.1 2.1

1 1 1 1 1 1 1 1
1.2 2.2 3.2 4.2 5.2 6.2 7.2 8.2 1.2 2.2 3.2 4.2 5.2 6.2 7.2 8.2 1.2 2.2

2 2 2 2 2 2 2 2
1.3 2.3 3.3 4.3 5.3 6.3 7.3 8.3 1.3 2.3 3.3 4.3 5.3 6.3 7.3 8.3 1.3 2.3

3 3 3 3 3 3 3 3
1.4 2.4 3.4 4.4 5.4 6.4 7.4 8.4 1.4 2.4 3.4 4.4 5.4 6.4 7.4 8.4 1.4 2.4

4 4 4 4 4 4 4 4

ANALOGUE INPUT 2-CHANNEL


ANALOGUE INPUT ANALOGUE INPUT ANALOGUE INPUT IB IL AI 2/SF-PAC
8-CHANNEL 2-CHANNEL 2-CHANNEL
IB IL AI 8/SF-PAC IB IL SGI 2/F-PAC IB IL SGI 2/F-PAC

21 30
DATE 2012-12-07 COMMISSION : LS-71366/07.04.1 Ammann Asphalt ASSEMBLY INTERBUS G0 A 0091 04 60201857290 = H0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 +
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 22
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

230VAC (P) SWITCHED (H0)


19.10 / 14L1 14L1 / 62.1
230VAC (P) EMERGENCY
24L1 / 62.1
+24VDC SWITCHED (H0)
19.10 / 14L+ 14L+ / 62.1

13 53
-3K1
/13.7 14 54

-X2 19 19 -X3 19 19

230VAC (N) SWITCHED (H0)


19.10 / 14L2 14L2 / 62.4
0VDC SWITCHED (H0)
19.10 / 14L- 14L- / 62.4

EMERGENCY
PLANT

22 62
DATE 2012-12-13 COMMISSION : LS-71366/07.04.1 Ammann Asphalt EMERGENCY AND G0 A 0091 04 60201857290 = H0
proc. UGR
CLIENT : Ammann do Brasil ERROR WARNING DRIVES SWITCH PANEL G0 +
Appr
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 30
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

230VAC (P) SWITCHED (H0)


30.10 / 14L1 14L1 / 63.1
230VAC (P) EMERGENCY
30.10 / 24L1 24L1 / 63.1
+24VDC SWITCHED (H0)
30.10 / 14L+ 14L+ / 63.1

2L1
400V +/-5% 3Ph 50Hz 2L1
2L2 2L2
2L3 2L3
1.21
1 3 5 -41Q1
-41Q1 /62.1 1.22
/63.2
/62.9 I> I> I>
35A ge 2 4 6
CLASS 10
PKE65/XTU-65

2.4

INPUT

=G0-D1E32

6 mm²

PE
-X1 21 22 23 24 -W141
H07RN-F
BN BK GY GNYE 4x6 mm² 15 m
COMPRESSOR

230VAC (N) SWITCHED (H0)


30.10 / 14L2 14L2 / 63.1
0VDC SWITCHED (H0)
30.10 / 14L- 14L- / 63.3

ERROR
COMPRESSOR

=K41
-X1 L1 L2 L3 PE

COMPRESSOR
30 63
DATE 2013-02-04 COMMISSION : LS-71366/07.04.1 Ammann Asphalt 891 G0 A 0091 04 60201857290 = H0
proc. UGR
CLIENT : Ammann do Brasil COMPRESSOR SWITCH PANEL G0 +
Appr
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 62
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

230VAC (P) SWITCHED (H0)


62.10 / 14L1 14L1 / 76.1
230VAC (P) EMERGENCY
62.10 / 24L1
230VAC (N) SWITCHED (H0)
14L2 / 76.1
+24VDC SWITCHED (H0)
62.10 / 14L+ 14L+ / 76.1
0VDC SWITCHED (H0)

1.13 25
-41Q1 -41K1T
/62.1 1.14 /63.2 28

-X2 23 -X3 25
13 X1
-41S1 -41H1
0-1 14 WH X2
COMPRESSOR
ON

-X2 24 -X2 25 -X3 18


0VDC
DOOR LEFT
0VL / 77.9
18
-41K1T

CONTROL LINE COMPRESSOR


/63.2 15
PE
-X5 30 31 20

3x1 mm² 15 m
62.10 / 14L- 14L- / 76.1

-W341
ÖZ-J
1 2 GNYE

=K41

-1X6 3 11 PE
B1 A1
PE
-41K1T M
87.02 A2
Fkt.:CE
t > 15 sec.
62.10 / 14L2
SWITCH 1 = "ON"

COMPRESSOR COMPRESSOR CONTROL COMPRESSOR


ON ON

COMPRESSOR COMPRESSOR
62 ON PUMPS 76
DATE 2013-04-29 COMMISSION : LS-71366/07.04.1 Ammann Asphalt 891 G0 A 0091 04 60201857290 = H0
proc. UGR
CLIENT : Ammann do Brasil COMPRESSOR SWITCH PANEL G0 +
Appr
ASPHALT MIXING PLANT D-31061 Alfeld CONTROL PART CAD: 71366_G0
MODIFICATIONDATE NAME origin \\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 63
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

230VAC (P)
63.10 / 14L1 14L1 / 77.1
230VAC (N)
63.10 / 14L2 14L2 / 77.4
+24VDC
63.10 / 14L+ 14L+ / 77.1
0VDC
63.4 / 14L- 14L- / 77.4

2L1
400V +/-5% 3Ph 50Hz 2L1
2L2 2L2
2L3 2L3
1.21
1 3 5 -65Q3
-65Q3 /76.1 1.22
/77.6
/76.9 I> I> I>
11,0A ge 2 4 6
CLASS 10
PKE12/XTU-12 1 3 5
-65K3
/77.6 2 4 6 2.3

INPUT
-65U1 -65U2 =G0-D1E32
L1 N 1 REGULATOR: L1 N 1
TEMPERATURE LIMITER COOLING TEMPERATURE LIMITER
+130°C 0-200 Grd.C 2 +100°C 0-200 Grd.C 2
/77.6 /77.5
4 5 4 5

2,5 mm²

PE PE PE
-X1 25 26 27 -X4 41 42 23 24 20 20

-W165.2
H07RN-F 4x1,5 mm² 20 m
BITUMEN PUMP HEATING -W465
BN BK GNYE 1 2 3 4 GNYE
ÖSYZ-J 5x0,75 mm² 20 m
SENSOR HEATING BITUMEN PUMP
-UC165
TERMINAL
BOX PE
DESMI -X1 1 2 3 4 5 6 7 8 PE -X4 1 2 3 -X4 4 5 6 PE

PE
PE Θ Θ
-65E1 -65E2 -65E3 -65B1 -65B2
0,55KW 0,3KW 0,2KW PT100 PT100
400V 400V 400V

BITUMEN PUMP HEATING SENSOR HEATING BITUMEN PUMP SENSOR HEATING BITUMEN PUMP
63 77
DATE 2013-02-04 COMMISSION : LS-71366/07.04.1 Ammann Asphalt 841 G0 A 0091 04 60201857290 = H0
proc. UGR
CLIENT : Ammann do Brasil HEATING BITUMEN PUMP SWITCH PANEL G0 +
Appr
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 76
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

230VAC (P)
76.10 / 14L1 14L1 / 81.1
+24VDC
76.10 / 14L+ 14L+ / 81.1

-X2 17
X2/17 / 91.5

13 21 43 13
-65S1 -65K5 -65K3 -65K3
0-1 14 /77.5 24 /77.6 44 /77.6 14

-X2 26 -X3 24

X1
-65H1
WH X2
BITUMEN PUMP HEATING
0VDC
DOOR LEFT
63.4 / 0VL 0VL / 81.6
2.2 2.1

INPUT INPUT

=G0-D1E32

1.13
-65Q3
/76.1 1.14

1 1
-65U2 -65U1
/76.7 2 /76.5 2

A1 A1
-65K5 -65K3
55.34 A2 PKE12 A2
24VDC 230VAC

230VAC (N)
76.10 / 14L2 14L2 / 81.4
0VDC
76.10 / 14L- 14L- / 81.4

HEATING BITUMEN PUMP HEATING BITUMEN PUMP


TEMPERATURE ON TEMPERATURE ON ON
BITUMEN PUMP OK BITUMEN PUMP OK
14 11 =M0/29.8 1 2 /76.1
21 24 /77.7 3 4 /76.2
5 6 /76.2
13 14 /77.9
43 44 /77.8

76 81
DATE 2013-02-04 COMMISSION : LS-71366/07.04.1 Ammann Asphalt 841 G0 A 0091 04 60201857290 = H0
proc. UGR
CLIENT : Ammann do Brasil HEATING BITUMEN PUMP SWITCH PANEL G0 +
Appr
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 77
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

230VAC (P) SWITCHED (H0)


77.10 / 14L1 14L1 / 83.1
+24VDC SWITCHED (H0)
77.10 / 14L+ 14L+ / 83.1

2L1
400V +/-5% 3Ph 50Hz 2L1
2L2 2L2
2L3 2L3 13 1.21
-71K1 -71Q1
/81.5 14 /81.1 1.22

1 3 5
-71Q1
/81.5
/81.10 I> I> I> -X2 27 -X3 26 -X3 27
10A ge 2 4 6
CLASS 10
PKE12/XTU-12 13 X1
-71S1 -71H1
0-1 14 WH X2
BITUMEN
PIPE HEATING CIRCUIT 1 ON
N2 N2 -X2 28
6.4 7.1 7.2
INPUT INPUT INPUT
1 3 5 0VDC
DOOR LEFT
-71K1 77.10 / 0VL 0VL / 91.7
/81.5 2 4 6 =G0-D2E32

1.13
-71Q1
/81.1 1.14
2,5 mm²

1
PE
-71U1
-X1 31 32 33 /83.3 2

A1
-71K1
DILM12-10 A2
230VAC

230VAC (N) SWITCHED (H0)


77.10 / 14L2 14L2 / 83.1
0VDC SWITCHED (H0)
77.10 / 14L- 14L- / 83.1

BITUMEN PIPE HEATING


CIRCUIT 1 ON BITUMEN PIPE HEATING ON ON
CIRCUIT 1 ON
-W171
BN BU GNYE 1 2 /81.1
H07RN-F 3x2,5 mm² 22 m 3 4 /81.2
400VAC BITUMEN PIPE HEATING CIRCUIT 1 5 6 /81.2
13 14 /81.7
71_PE / 82.1

71_2 / 82.1
71_1 / 82.1

BITUMEN
77 PIPE HEATING CIRCUIT 1 82
DATE 2013-02-20 COMMISSION : LS-71366/07.04.1 Ammann Asphalt 831 G0 A 0091 04 60201857290 = H0
proc. PBR
CLIENT : Ammann do Brasil BITUMEN SWITCH PANEL G0 +
Appr
ASPHALT MIXING PLANT D-31061 Alfeld PIPE HEATING CIRCUIT 1 CAD: 71366_G0
MODIFICATIONDATE NAME origin \\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 81
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

81.3 / 71_PE

81.3 / 71_2
81.3 / 71_1

-UC171

PE
-X1 1 2 4 1 2 4

PE
-71E1
230VAC

PIPE HEATING CIRCUIT 1


81 83
DATE 2013-02-04 COMMISSION : LS-71366/07.04.1 Ammann Asphalt 831 G0 A 0091 04 60201857290 = H0
proc. UGR
CLIENT : Ammann do Brasil BITUMEN SWITCH PANEL G0 +
Appr
ASPHALT MIXING PLANT D-31061 Alfeld PIPE HEATING CIRCUIT 1 CAD: 71366_G0
MODIFICATIONDATE NAME origin \\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 82
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

230VAC (P) SWITCHED (H0)


81.10 / 14L1 14L1 / 91.1
230VAC (N) SWITCHED (H0)
81.10 / 14L2 14L2 / 91.5
+24VDC SWITCHED (H0)
81.10 / 14L+ 14L+ / 91.1
0VDC SWITCHED (H0)
81.10 / 14L- 14L- / 91.5

=G0-A1E8
ANALOGUE INPUT
7.1 7.3
-71U1
130°C
L1 N
TEMPERATURE REGULATOR 1
0-200 Grd.C /81.5
2
-X4 32
4 5
-71R1
499Ω

-X4 31

-71U3
0- 400°C 81+ 4-20mA 82-
MEASURING TRANSDUCER

11 12 13

PE PE
-X4 25 26 27 -X4 28 29 30 20 20

-W471
1 2 3 4 5 GNYE
ÖSYZ-J 7x0,75 mm² 22 m
PIPE HEATING CIRCUIT 1 TEMPERATURE SENSOR
-UC471

PE
-X4 23 24 25 20 -X4 26 27 28 20

WH RD/ RD SIHF-J 3x0,25mm² WH RD/ RD SIHF-J 3X0,25MM²


BU BU
Θ Θ
-71B1 -71B2
PT100 PT100

BITUMEN TEMPERATURE
SENSOR 1
82 91
DATE 2013-02-26 COMMISSION : LS-71366/07.04.1 Ammann Asphalt 831 G0 A 0091 04 60201857290 = H0
proc. UGR
CLIENT : Ammann do Brasil BITUMEN SWITCH PANEL G0 +
Appr
ASPHALT MIXING PLANT D-31061 Alfeld PIPE HEATING CIRCUIT 1 CAD: 71366_G0
MODIFICATIONDATE NAME origin \\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 83
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

230VAC (P) SWITCHED


83.10 / 14L1 14L1 / 92.1
+24VDC SWITCHED
83.10 / 14L+ 14L+ / 92.1

2L1
400V +/-5% 3Ph 50Hz 2L1
2L2 2L2 53
2L3 2L3 -82K1
13 /91.5 54 1.21
-82K1 -82Q1
/91.5 14 /91.1 1.22

53
1 3 5 -87K1
-82Q1 -X3 28 /95.6 54 SST / 95.9
/91.5
/91.9 I> I> I>
10A ge 230VAC (P)
2 4 6 77.6 / X2/17 14L111 / 95.5 X1
CLASS 10 -82H1
PKE12/XTU-12
82L3 / 94.1 WH X2
13 HEATING
-82S1 OIL PIPES 1
0-1 14 7.4 7.3
N2 N2 HEATING INPUT INPUT
OIL PIPES 0VDC
DOOR LEFT
81.7 / 0VL 0VL / 94.8
1 3 5 -X2 29 =G0-D2E32
-82K1
/91.5 2 4 6
1.13
-82Q1
/91.1 1.14
2,5 mm²

82L1 / 94.8
PE
-X1 34 35 36 1
-82U1
/92.3 2

-W182 A1
BN BU GNYE
H07RN-F 3x2,5 mm² 20 m -82K1
HEATING OIL PIPES 1 DILM12-32 A2
230VAC
PRESSURE PUMP - BURNER
230VAC (N) SWITCHED
83.10 / 14L2 14L2 / 92.1
0VDC SWITCHED
83.10 / 14L- 14L- / 92.1
-UC182
PE ON ON ON ERROR
-X1 1 2 3

1 2 /91.1
PE 3 4 /91.2
-82E1 5 6 /91.2
0,3 KW 13 14 /91.7
1,35 A 53 54 /91.9
5 m Heizband
230VAC

HEATING OIL PIPES


83 PRESSURE PUMP - BURNER 92
DATE 2013-02-20 COMMISSION : LS-71366/07.04.1 Ammann Asphalt HEATING OIL PIPES 1 G0 A 0091 04 60201857290 = H0
proc. PBR
CLIENT : Ammann do Brasil PRESSURE PUMP --> BURNER SWITCH PANEL G0 +
Appr
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 91
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

230VAC (P) SWITCHED


91.10 / 14L1 14L1 / 94.1
+24VDC SWITCHED
91.10 / 14L+ 14L+ / 94.1
230VAC (N) SWITCHED
91.10 / 14L2 14L2 / 94.8
0VDC SWITCHED
91.10 / 14L- 14L- / 94.8

-82U1
80°C
L1 N
TEMPERATURE REGULATOR 1
0-200 Grd.C /91.5
2

4 5

PE PE
-X4 33 34 35 20 20

-W482
1 2 3 GNYE
ÖSYZ-J 4x0,75 mm² 22 m
SENSOR HEATING OIL PIPES 1
-UC482
PE
-X4 1 2 3 20

Θ PE
-82B1
PT100

SENSOR
HEATING
91 OIL PIPES 1 94
DATE 2013-02-20 COMMISSION : LS-71366/07.04.1 Ammann Asphalt TEMPERATURE LIMITER G0 A 0091 04 60201857290 = H0
proc. PBR
CLIENT : Ammann do Brasil HEATING OIL PIPES 1 SWITCH PANEL G0 +
Appr
ASPHALT MIXING PLANT D-31061 Alfeld PRESSURE PUMP --> BURNER CAD: 71366_G0
MODIFICATIONDATE NAME origin \\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 92
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

230VAC (P) SWITCHED


92.10 / 14L1 14L1 / 95.1
+24VDC SWITCHED
92.10 / 14L+ 14L+ / 95.1

2L1
400V +/-5% 3Ph 50Hz 2L1
2L2 2L2
2L3 2L3
N2 N2
13
-85K1
91.2 / 82L3 /94.8 14

-X3 29
1 3 5
-85K1
/94.8 2 4 6

PE
-X1 37 38 39
0VDC
DOOR LEFT
91.7 / 0VL 0VL / 95.7

-W185
BN BU GNYE
H07RN-F 3x1,5 mm² 25 m
HEATING AT BURNER

91.5 / 82L1

-IB

-XB 202 201 PE 204 201 PE 200 201 PE A1


230VAC -85K1
M12-10 A2
PE
-62T3 230VAC

0 24V 42V 230VAC (N) SWITCHED


92.10 / 14L2 14L2 / 95.5
0VDC SWITCHED
92.10 / 14L- 14L- / 95.5
PE PE
-62E1 -62E2
ON
-XB 401 402
-X200 1 2 3 -X201 1 2 3

1 2 /94.1
3 4 /94.1
-62E3 -62E4
500W 500W 5 6 /94.2
24V 24V
13 14 /94.8

PIPE BURNER HEATING HEATING


OIL LANCE OIL REGULATION-VALVE
92 95
DATE 2013-02-20 COMMISSION : LS-71366/07.04.1 Ammann Asphalt HEATING G0 A 0091 04 60201857290 = H0
proc. PBR
CLIENT : Ammann do Brasil PIPE BURNER AND LANCE SWITCH PANEL G0 +
Appr
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 94
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

230VAC (P) SWITCHED 14L1


94.10 / 14L1
+24VDC SWITCHED 14L+
94.10 / 14L+

2L1
400V +/-5% 3Ph 50Hz
2L1
2L2 2L2
2L3 2L3
N2 N2 13 1.21
-87K1 -87Q1
/95.6 14 /95.1 1.22

1 3 5 -X3 30 91.10 / SST


-87Q1
/95.6
/95.9 230VAC (P)
I> I> I> 91.5 / 14L111 X1
2A ge 2 4 6 -87H1
CLASS 10 WH X2
PKE12/XTU-4 13 HEATING
-87S1 BURNER-PRESSURE PUMP
-87K1 0-1 14
/95.6 2 4 6 HEATING
BURNER-PRESSURE PUMP 0VDC
DOOR LEFT
94.9 / 0VL
-X2 32

2,5 mm² 1.13


-87Q1
/95.1 1.14
PE
-X1 40 41 42

-W187
BN BU GNYE
H07RN-F 3x1,5 mm² 20 m
HEATING PRESSURE PUMP

A1
-87K1
PKE12 A2
-UC187 230VAC
230VAC (N) SWITCHED 14L2
94.10 / 14L2
PE 0VDC SWITCHED 14L-
-X1 1 2 3 94.10 / 14L-

ON ON ERROR

PE 2 /95.1
-87E1 4 /95.2
0,18 kW 6 /95.2
0,75 A 13 14 /95.8
53 54 /91.9

HEATING
94 BURNER-PRESSURE PUMP +KLE/1
DATE 2013-02-20 COMMISSION : LS-71366/07.04.1 Ammann Asphalt HEATING G0 A 0091 04 60201857290 = H0
proc. PBR
CLIENT : Ammann do Brasil BURNER-PRESSURE PUMP SWITCH PANEL G0 +
Appr
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 95
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

TERMINAL STRIP OVERVIEW AAD_F14_002

TERMINALS
TERMINAL BLOCK FUNCTION TEXT PAGE TERMINAL DIAGRAM
FIRST LATEST SUM PE SUM N TOTAL NUMBER
-X1 CONSUMER 400VAC 5 42 8 2 29 =H0+KLE/11
-X2 CONTROL TERMINAL 230VAC 1 32 10 0 63 =H0+KLE/12
-X3 CONTROL TERMINAL 24VDC 1 30 2 0 38 =H0+KLE/13
-X4 ANALOG VOLTAGES 20 42 6 0 21 =H0+KLE/14
-X5 EXTERNAL VOLTAGES 20 31 2 0 8 =H0+KLE/15
-X13 EMERGENCY 1 103 1 0 7 =H0+KLE/16
-X21 LOW VOLTAGE COIL 1 20 5 0 15 =H0+KLE/17

+/95 11
DATE 2013-05-30 COMMISSION : LS-71366/07.04.1 Ammann Asphalt TERMINAL STRIP REVIEW G0 A 0091 04 60201857290 = H0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KLE
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 1
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

TERMINAL DIAGRAM AAD_F13_001

CABLE NAME

CABLE NAME
-W187
-W185
-W182
-W171
-W165.2
-W141
-W142
-W102
STRIP
=H0+-X1
CONSUMER 400VAC

H07RN-F 3x1,5 mm²

H07RN-F 3x1,5 mm²

H07RN-F 3x2,5 mm²

H07RN-F 3x2,5 mm²

H07RN-F 4x1,5 mm²

H07RN-F 4x6 mm²

H07RN-F 3x1,5 mm²

H07RN-F 5x2,5 mm²

CABLE TYPE

CABLE TYPE
CONNECTION

CONNECTION
TERMINAL
FUNCTION TEXT DESTINATION DESCRIPTION DESTINATION DESCRIPTION PAGE / COLUMN

POWER SUPPLY 400VAC BN =CO-X0 L1 5 -1Q2 2 /11.4


400VAC CONTAINER BK =CO-X0 L2 6 -1Q2 4 /11.4
= GY =CO-X0 L3 7 -1Q2 6 /11.4
= BU =CO-X0 N 8 -N N /11.4
-1F3 7N
400VAC CONTAINER GNYE =CO-X0 PE 9 /11.5
= 10 -1F3 2 /11.6
= 11 -1F3 4 /11.6
STEAM TRAP COMPRESSOR BN +142-X1 1 12 -1F3 6 /11.6
= BU +142-X1 4 13 -1F3 8N /11.6
= GNYE +142-X1 PE 14 /11.6
COMPRESSOR BN =K41-X1 L1 21 -41Q1 2 /62.1
= BK =K41-X1 L2 22 -41Q1 4 /62.2
= GY =K41-X1 L3 23 -41Q1 6 /62.2
= GNYE =K41-X1 PE 24 /62.2
BITUMEN PUMP HEATING BN -UC165-X1 1 25 -65K3 2 /76.1
= BK -UC165-X1 2 26 -65K3 6 /76.2
= GNYE -UC165-X1 PE 27 /76.3
BITUMEN PIPE HEATING CIRCUIT 1 BN -UC171-X1 1 31 -71K1 4 /81.2
= BU -UC171-X1 2 32 -71K1 6 /81.2
= GNYE -UC171-X1 4 33 /81.2
HEATING OIL PIPES PRESSURE PUMP - BURNER BN -UC182-X1 1 34 -82K1 4 /91.2
= BU -UC182-X1 2 35 -82K1 6 /91.2
= GNYE -UC182-X1 3 36 /91.2
PIPE BURNER BN -IB-XB 202 37 -85K1 4 /94.1
= BU -IB-XB 201 38 -85K1 6 /94.2
= GNYE -IB-XB PE 39 /94.2
HEATING BURNER-PRESSURE PUMP BN -UC187-X1 1 40 -87K1 4 /95.2
= BU -UC187-X1 2 41 -87K1 6 /95.2
= GNYE -UC187-X1 3 42 /95.2

1 12
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt TERMINAL DIAGRAM =H0+-X1 G0 A 0091 04 60201857290 = H0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KLE
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 11
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

TERMINAL DIAGRAM AAD_F13_001

CABLE NAME

CABLE NAME
-W202
STRIP
=H0+-X2
CONTROL TERMINAL 230VAC

H07RN-F 3x1,5 mm²

CABLE TYPE

CABLE TYPE
CONNECTION

CONNECTION
TERMINAL
FUNCTION TEXT DESTINATION DESCRIPTION DESTINATION DESCRIPTION PAGE / COLUMN

CONTROL VOLTAGE OFF - ON -7S1 21 1 -5F3 1 /18.1


230VAC 1 -5K1 1 /19.1
= 1 /19.1
CONTROL VOLTAGE OFF - ON -7K1 A2 2 -7H2 X2 /18.2
230VAC 2 -5K1 3 /19.2
= 2 /19.2
CONTROL VOLTAGE OFF - ON -7K1 5 4 -7S2 13 /18.3
= -3K1 5 5 -7S2 14 /18.1
CONTROL VOLTAGE INTERBUS-S 11 -5F2 1 /17.3
= 11 /17.4
= 11 /17.4
= 11 /17.4
= 11 /17.4
CONTROL VOLTAGE 24VDC UNSWITCHED 11 /17.7
UPS BN =RCO-X200 L1 11 -8G2 L /20.1
CONTROL VOLTAGE INTERBUS-S 12 -5F2 3 /17.5
-X2 12
CONTROL VOLTAGE INTERBUS-S 12 /17.5
CONTROL VOLTAGE 230VAC UNSWITCHED 12 /17.5
= 12 /17.5
= 12 /17.5
CONTROL VOLTAGE 24VDC UNSWITCHED 12 -X2 12 /17.7
UPS BU =RCO-X200 N 12 -8G2 N /20.2
CONTROL VOLTAGE 24VDC UNSWITCHED 13 /17.8
= 13 /17.9
= 14 /17.8
= 14 /17.9
230VAC 17 -5K1 2 /19.2
-3K1 13
230VAC 17 /19.2
= 17 /19.2
HEATING BITUMEN PUMP ON -65S1 13 17 -3K1 13 /77.6
-X2 27
230VAC 18 -65K3 A2 /19.3
-5K1 4

11 12.A
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt TERMINAL DIAGRAM =H0+-X2 G0 A 0091 04 60201857290 = H0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KLE
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 12
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

TERMINAL DIAGRAM AAD_F13_001

CABLE NAME

CABLE NAME
-W202
STRIP
=H0+-X2
CONTROL TERMINAL 230VAC

H07RN-F 3x1,5 mm²

CABLE TYPE

CABLE TYPE
CONNECTION

CONNECTION
TERMINAL
FUNCTION TEXT DESTINATION DESCRIPTION DESTINATION DESCRIPTION PAGE / COLUMN

-65U2 N
-65U1 N
-41K1T A2
230VAC 18 /19.3
= 18 /19.3
EMERGENCY PLANT 19 -3K1 14 /30.2
= 19 /30.2
CONTROL VOLTAGE 230VAC UNSWITCHED 20 /17.6
= 20 /17.6
= 20 /17.6
= 20 /17.7
= 20 /17.7
CONTROL VOLTAGE 24VDC UNSWITCHED 20 /17.8
= 20 /17.8
= 20 /17.9
230VAC (N) 20 /19.5
UPS GNYE =RCO-X200 PE 20 /20.2
230VAC (P) 21 -7K1 2 /19.3
=D0-X2 21
230VAC (P) 21 /19.3
= 21 /19.4
= 21 /19.4
= 21 /19.4
230VAC (N) 22 =D0-X2 22 /19.4
-7K1 4
230VAC (N) 22 /19.4
= 22 /19.5
= 22 /19.5
= 22 /19.5
COMPRESSOR ON -41S1 13 23 -41Q1 1.14 /63.2
-41K1T A1
COMPRESSOR ON -41K1T B1 24 -41S1 14 /63.2
= 25 /63.2
HEATING BITUMEN PUMP ON -65Q3 1.13 26 -65S1 14 /77.6
BITUMEN PIPE HEATING CIRCUIT 1 ON -71S1 13 27 -71U1 L1 /81.5

12 12.B
DATE 2013-05-30 COMMISSION : LS-71366/07.04.1 Ammann Asphalt TERMINAL DIAGRAM =H0+-X2 G0 A 0091 04 60201857290 = H0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KLE
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 12.A
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

TERMINAL DIAGRAM AAD_F13_001

CABLE NAME

CABLE NAME
STRIP
=H0+-X2
CONTROL TERMINAL 230VAC

CABLE TYPE

CABLE TYPE
CONNECTION

CONNECTION
TERMINAL
FUNCTION TEXT DESTINATION DESCRIPTION DESTINATION DESCRIPTION PAGE / COLUMN

-X2 17
BITUMEN PIPE HEATING CIRCUIT 1 ON -71Q1 1.13 28 -71S1 14 /81.5
ON -82Q1 1.13 29 -82S1 14 /91.5
= -87Q1 1.13 32 -87S1 14 /95.6

12.A 13
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt TERMINAL DIAGRAM =H0+-X2 G0 A 0091 04 60201857290 = H0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KLE
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 12.B
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

TERMINAL DIAGRAM AAD_F13_001

CABLE NAME

CABLE NAME
STRIP
=H0+-X3
CONTROL TERMINAL 24VDC

CABLE TYPE

CABLE TYPE
CONNECTION

CONNECTION
TERMINAL
FUNCTION TEXT DESTINATION DESCRIPTION DESTINATION DESCRIPTION PAGE / COLUMN

+24VDC -7K1 43 1 -7K2 11 /19.5


-5K1 5
+24VDC 1 /19.6
= 1 /19.6
POWER SUPPLY LOCAL BUS =G0-BK1 1.2 2.2 1 -5K1 5 /20.9
+24VDC -7K1 53 2 -7K2 A2 /19.6
-5K1 13
+24VDC 2 /19.6
= 2 /19.6
POWER SUPPLY LOCAL BUS =G0-BK1 1.3 2 -5K1 13 /20.9
FEED BUS TERMINAL 11 -8G2 + /20.7
= 11 /20.7
= 12 -8G2 - /20.8
= 12 /20.8
PLANT ON (IMPULSE) -7D1 15 -7U1 4E /18.7
= -7K1 13 16 -7D1 /18.7
+24VDC 17 -5K1 6 /19.7
-3K1 53
+24VDC 17 /19.7
= 17 /19.7
= 18 -5K1 14 /19.8
-65H1 X2
-X3 18
+24VDC 18 /19.8
= 18 /19.8
COMPRESSOR ON -65K5 A2 18 -41H1 X2 /63.3
-X3 18
EMERGENCY PLANT 19 -3K1 54 /30.3
= 19 /30.3
+24VDC 20 /19.7
= 20 /19.8
= 21 -7K1 44 /19.5
= 21 /19.6
= 21 /19.6
= 22 -7K1 54 /19.6

12.B 13.A
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt TERMINAL DIAGRAM =H0+-X3 G0 A 0091 04 60201857290 = H0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KLE
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 13
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

TERMINAL DIAGRAM AAD_F13_001

CABLE NAME

CABLE NAME
STRIP
=H0+-X3
CONTROL TERMINAL 24VDC

CABLE TYPE

CABLE TYPE
CONNECTION

CONNECTION
TERMINAL
FUNCTION TEXT DESTINATION DESCRIPTION DESTINATION DESCRIPTION PAGE / COLUMN

+24VDC 22 /19.6
= 22 /19.6
ON -65H1 X1 24 -65K3 14 /77.9
COMPRESSOR ON -41H1 X1 25 -41K1T 28 /63.3
BITUMEN PIPE HEATING CIRCUIT 1 ON -71H1 X1 26 -71K1 14 /81.7
=G0-D2E32 7.1
BITUMEN PIPE HEATING CIRCUIT 1 ON 27 =G0-D2E32 6.4 /81.7
ON -82H1 X1 28 -82K1 14 /91.7
= 29 -85K1 14 /94.8
= -87H1 X1 30 -87K1 14 /95.8

13 14
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt TERMINAL DIAGRAM =H0+-X3 G0 A 0091 04 60201857290 = H0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KLE
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 13.A
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

TERMINAL DIAGRAM AAD_F13_001

CABLE NAME

CABLE NAME
-W482
-W471
-W465
STRIP
=H0+-X4
ANALOG VOLTAGES

ÖSYZ-J 4x0,75 mm²

ÖSYZ-J 7x0,75 mm²

ÖSYZ-J 5x0,75 mm²

CABLE TYPE

CABLE TYPE
CONNECTION

CONNECTION
TERMINAL
FUNCTION TEXT DESTINATION DESCRIPTION DESTINATION DESCRIPTION PAGE / COLUMN

SENSOR HEATING BITUMEN PUMP GNYE -UC165-X4 PE 20 /76.7


= 20 /76.7
BITUMEN TEMPERATURE GNYE -UC471-X4 20 20 /83.6
= 20 /83.6
SENSOR HEATING OIL PIPES 1 GNYE -UC482-X4 20 20 /92.3
= 20 /92.3
SENSOR HEATING BITUMEN PUMP 3 -UC165-X4 4 23 -65U2 4 /76.6
= 4 -UC165-X4 6 24 -65U2 5 /76.7
SENSOR 1 1 -UC471-X4 23 25 -71U1 4 /83.2
= 2 -UC471-X4 25 26 -71U1 5 /83.3
= 27 /83.3
BITUMEN TEMPERATURE 3 -UC471-X4 26 28 -71U3 11 /83.5
= 4 -UC471-X4 27 29 -71U3 12 /83.5
= 5 -UC471-X4 28 30 -71U3 13 /83.5
= -71U3 82- 31 -71R1 /83.6
= -71R1 32 =G0-A1E8 7.3 /83.6
SENSOR HEATING OIL PIPES 1 1 -UC482-X4 1 33 -82U1 4 /92.2
= 2 -UC482-X4 2 34 /92.2
= 3 -UC482-X4 3 35 -82U1 5 /92.3
SENSOR HEATING BITUMEN PUMP 1 -UC165-X4 1 41 -65U1 4 /76.4
= 2 -UC165-X4 3 42 -65U1 5 /76.5

13.A 15
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt TERMINAL DIAGRAM =H0+-X4 G0 A 0091 04 60201857290 = H0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KLE
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 14
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

TERMINAL DIAGRAM AAD_F13_001

CABLE NAME

CABLE NAME
-W341
STRIP
=H0+-X5
EXTERNAL VOLTAGES

ÖZ-J 3x1 mm²

CABLE TYPE

CABLE TYPE
CONNECTION

CONNECTION
TERMINAL
FUNCTION TEXT DESTINATION DESCRIPTION DESTINATION DESCRIPTION PAGE / COLUMN

EMERGENCY RESERVE 20 /13.7


COMPRESSOR ON GNYE =K41-1X6 PE 20 /63.7
EMERGENCY RESERVE 26 -3F1 33 /13.6
= 27 -3F1 34 /13.7
= 28 -3F1 23 /13.6
= 29 -3F1 24 /13.7
COMPRESSOR ON 1 =K41-1X6 3 30 -41K1T 15 /63.6
= 2 =K41-1X6 11 31 -41K1T 18 /63.6

14 16
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt TERMINAL DIAGRAM =H0+-X5 G0 A 0091 04 60201857290 = H0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KLE
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 15
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

TERMINAL DIAGRAM AAD_F13_001

CABLE NAME

CABLE NAME
-W303.1
STRIP
=H0+-X13
EMERGENCY

H07RN-F 5x1,5 mm²

CABLE TYPE

CABLE TYPE
CONNECTION

CONNECTION
TERMINAL
FUNCTION TEXT DESTINATION DESCRIPTION DESTINATION DESCRIPTION PAGE / COLUMN

EMERGENCY CONTROL ROOM BN -3S1 21 1 -3F1 S11 /13.1


= BK -3S1 22 2 -3F1 S12 /13.2
= GNYE -3S1 PE 20 /13.2
EMERGENCY UNLOCK -3S0 13 21 -3F1 S33 /13.4
= -3S0 14 22 -3F1 S34 /13.5
EMERGENCY CONTROL ROOM GY -3S1 13 101 -6G1 + /13.2
= BU -3S1 14 103 =G0-D1E32 1.1 /13.2

15 17
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt TERMINAL DIAGRAM =H0+-X13 G0 A 0091 04 60201857290 = H0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KLE
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 16
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

TERMINAL DIAGRAM AAD_F13_001

CABLE NAME

CABLE NAME
STRIP
=H0+-X21
LOW VOLTAGE COIL

CABLE TYPE

CABLE TYPE
CONNECTION

CONNECTION
TERMINAL
FUNCTION TEXT DESTINATION DESCRIPTION DESTINATION DESCRIPTION PAGE / COLUMN

POWER SUPPLY LOW VOLTAGE COIL -X21 1 1 -X21 3 /11.8


= 1 /11.9
POWER SUPPLY LOW VOLTAGE COILS -X21 1 1 -3K1 2 /16.2
FREE 1 /16.4
POWER SUPPLY LOW VOLTAGE COIL -X21 2 2 -1Q1 D1 /11.9
-1T1 d
POWER SUPPLY LOW VOLTAGE COIL 2 /11.9
POWER SUPPLY LOW VOLTAGE COILS -X21 2 2 -3K1 4 /16.2
FREE 2 /16.4
POWER SUPPLY LOW VOLTAGE COIL 3 -X21 1 /11.9
= 4 -1F1 3 /11.10
= 20 /11.9
= 20 /11.9
= 20 /11.10
POWER SUPPLY LOW VOLTAGE COILS 20 /16.2
FREE 20 /16.4

16 +KAB/1
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt TERMINAL DIAGRAM =H0+-X21 G0 A 0091 04 60201857290 = H0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KLE
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 17
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

CABLE PLAN
1. PAGE PAGE
CABLE TYPE ID CORES CROSS SECTION LENGTH FUNCTION TEXT CIRCUIT DIAGRAM CABLE DIAGRAM

H07RN-F -W102 5 2,5 12 m 400VAC CONTAINER +/11.4 =H0+KAB/11

-W141 4 6 15 m COMPRESSOR +/62.1 =H0+KAB/12

-W142 3 1,5 15 m HEATING COMPRESSOR +/11.6 =H0+KAB/13

-W165.2 4 1,5 20 m BITUMEN PUMP HEATING +/76.1 =H0+KAB/14

-W171 3 2,5 22 m 400VAC BITUMEN PIPE HEATING CIRCUIT 1 +/82.2 =H0+KAB/15

-W182 3 2,5 20 m HEATING OIL PIPES 1 PRESSURE PUMP - BURNER +/91.2 =H0+KAB/16

-W185 3 1,5 25 m HEATING AT BURNER +/94.1 =H0+KAB/17

-W187 3 1,5 20 m HEATING PRESSURE PUMP +/95.2 =H0+KAB/18

-W202 3 1,5 12 m POWER SUPPLY COMPUTER +/20.1 =H0+KAB/19

-W303.1 5 1,5 12 m EMERGENCY CONTAINER +/13.1 =H0+KAB/20

ÖZ-J -W341 3 1 15 m CONTROL LINE COMPRESSOR +/63.7 =H0+KAB/21

ÖSYZ-J -W465 5 0,75 20 m SENSOR HEATING BITUMEN PUMP +/76.4 =H0+KAB/22

-W471 7 0,75 22 m PIPE HEATING CIRCUIT 1 TEMPERATURE SENSOR +/83.2 =H0+KAB/23

-W482 4 0,75 22 m SENSOR HEATING OIL PIPES 1 +/92.2 =H0+KAB/24

+KLE/17 11
DATE 2013-05-30 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CABLE PLAN G0 A 0091 04 60201857290 = H0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KAB
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 1
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

CABLE DIAGRAM AAD_F09_002

CABLE NAME =H0+-W102 CABLE TYPE H07RN-F


FUNCTION TEXT 400VAC CONTAINER CORE NO. 5 CROSS SECTION 2,5 mm² CABLE LENGTH 12 m
DESTINATION DESTINATION
FUNCTION TEXT PAGE / COLUMN CONNECTION CORE CONNECTION PAGE / COLUMN FUNCTION TEXT
DESCRIPTION FROM DESCRIPTION TO

400VAC CONTAINER /11.4 -X1 6 BK =CO-X0 L2 /11.4 400VAC CONTAINER

POWER SUPPLY 400VAC /11.4 -X1 5 BN =CO-X0 L1 /11.4 POWER SUPPLY 400VAC

400VAC CONTAINER /11.4 -X1 8 BU =CO-X0 N /11.4 400VAC CONTAINER

= /11.5 -X1 9 GNYE =CO-X0 PE /11.5 =

= /11.4 -X1 7 GY =CO-X0 L3 /11.4 =

1 12
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CABLE DIAGRAM =H0+-W102 G0 A 0091 04 60201857290 = H0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KAB
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 11
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

CABLE DIAGRAM AAD_F09_002

CABLE NAME =H0+-W141 CABLE TYPE H07RN-F


FUNCTION TEXT COMPRESSOR CORE NO. 4 CROSS SECTION 6 mm² CABLE LENGTH 15 m
DESTINATION DESTINATION
FUNCTION TEXT PAGE / COLUMN CONNECTION CORE CONNECTION PAGE / COLUMN FUNCTION TEXT
DESCRIPTION FROM DESCRIPTION TO

COMPRESSOR /62.1 -X1 21 BN =K41-X1 L1 /62.1 COMPRESSOR

= /62.2 -X1 22 BK =K41-X1 L2 /62.2 =

= /62.2 -X1 23 GY =K41-X1 L3 /62.2 =

= /62.2 -X1 24 GNYE =K41-X1 PE /62.2 =

11 13
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CABLE DIAGRAM =H0+-W141 G0 A 0091 04 60201857290 = H0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KAB
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 12
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

CABLE DIAGRAM AAD_F09_002

CABLE NAME =H0+-W142 CABLE TYPE H07RN-F


FUNCTION TEXT HEATING COMPRESSOR CORE NO. 3 CROSS SECTION 1,5 mm² CABLE LENGTH 15 m
DESTINATION DESTINATION
FUNCTION TEXT PAGE / COLUMN CONNECTION CORE CONNECTION PAGE / COLUMN FUNCTION TEXT
DESCRIPTION FROM DESCRIPTION TO

STEAM TRAP COMPRESSOR /11.6 +142-X1 1 BN -X1 12 /11.6 STEAM TRAP COMPRESSOR

= /11.6 +142-X1 4 BU -X1 13 /11.6 =

= /11.6 +142-X1 PE GNYE -X1 14 /11.6 =

12 14
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CABLE DIAGRAM =H0+-W142 G0 A 0091 04 60201857290 = H0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KAB
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 13
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

CABLE DIAGRAM AAD_F09_002

CABLE NAME =H0+-W165.2 CABLE TYPE H07RN-F


FUNCTION TEXT BITUMEN PUMP HEATING CORE NO. 4 CROSS SECTION 1,5 mm² CABLE LENGTH 20 m
DESTINATION DESTINATION
FUNCTION TEXT PAGE / COLUMN CONNECTION CORE CONNECTION PAGE / COLUMN FUNCTION TEXT
DESCRIPTION FROM DESCRIPTION TO

BITUMEN PUMP HEATING /76.1 -UC165-X1 1 BN -X1 25 /76.1 BITUMEN PUMP HEATING

= /76.2 -UC165-X1 2 BK -X1 26 /76.2 =

GY

BITUMEN PUMP HEATING /76.3 -UC165-X1 PE GNYE -X1 27 /76.3 BITUMEN PUMP HEATING

13 15
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CABLE DIAGRAM =H0+-W165.2 G0 A 0091 04 60201857290 = H0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KAB
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 14
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

CABLE DIAGRAM AAD_F09_002

CABLE NAME =H0+-W171 CABLE TYPE H07RN-F


FUNCTION TEXT 400VAC BITUMEN PIPE HEATING CIRCUIT 1 CORE NO. 3 CROSS SECTION 2,5 mm² CABLE LENGTH 22 m
DESTINATION DESTINATION
FUNCTION TEXT PAGE / COLUMN CONNECTION CORE CONNECTION PAGE / COLUMN FUNCTION TEXT
DESCRIPTION FROM DESCRIPTION TO

PIPE HEATING CIRCUIT 1 /82.2 -UC171-X1 1 BN -X1 31 /81.2 BITUMEN PIPE HEATING CIRCUIT 1

= /82.2 -UC171-X1 2 BU -X1 32 /81.2 =

= /82.2 -UC171-X1 4 GNYE -X1 33 /81.2 =

14 16
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CABLE DIAGRAM =H0+-W171 G0 A 0091 04 60201857290 = H0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KAB
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 15
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

CABLE DIAGRAM AAD_F09_002

CABLE NAME =H0+-W182 CABLE TYPE H07RN-F


FUNCTION TEXT HEATING OIL PIPES 1 PRESSURE PUMP - BURNER CORE NO. 3 CROSS SECTION 2,5 mm² CABLE LENGTH 20 m
DESTINATION DESTINATION
FUNCTION TEXT PAGE / COLUMN CONNECTION CORE CONNECTION PAGE / COLUMN FUNCTION TEXT
DESCRIPTION FROM DESCRIPTION TO

HEATING OIL PIPES PRESSURE PUMP - /91.2 -UC182-X1 1 BN -X1 34 /91.2 HEATING OIL PIPES PRESSURE
BURNER PUMP - BURNER

/91.2 -UC182-X1 2 BU -X1 35 /91.2


= =

/91.2 -UC182-X1 3 GNYE -X1 36 /91.2


= =

15 17
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CABLE DIAGRAM =H0+-W182 G0 A 0091 04 60201857290 = H0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KAB
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 16
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

CABLE DIAGRAM AAD_F09_002

CABLE NAME =H0+-W185 CABLE TYPE H07RN-F


FUNCTION TEXT HEATING AT BURNER CORE NO. 3 CROSS SECTION 1,5 mm² CABLE LENGTH 25 m
DESTINATION DESTINATION
FUNCTION TEXT PAGE / COLUMN CONNECTION CORE CONNECTION PAGE / COLUMN FUNCTION TEXT
DESCRIPTION FROM DESCRIPTION TO

PIPE BURNER /94.1 -IB-XB 202 BN -X1 37 /94.1 PIPE BURNER

= /94.2 -IB-XB 201 BU -X1 38 /94.2 =

= /94.2 -IB-XB PE GNYE -X1 39 /94.2 =

16 18
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CABLE DIAGRAM =H0+-W185 G0 A 0091 04 60201857290 = H0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KAB
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 17
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

CABLE DIAGRAM AAD_F09_002

CABLE NAME =H0+-W187 CABLE TYPE H07RN-F


FUNCTION TEXT HEATING PRESSURE PUMP CORE NO. 3 CROSS SECTION 1,5 mm² CABLE LENGTH 20 m
DESTINATION DESTINATION
FUNCTION TEXT PAGE / COLUMN CONNECTION CORE CONNECTION PAGE / COLUMN FUNCTION TEXT
DESCRIPTION FROM DESCRIPTION TO

HEATING BURNER-PRESSURE PUMP /95.2 -UC187-X1 1 BN -X1 40 /95.2 HEATING BURNER-PRESSURE PUMP

= /95.2 -UC187-X1 2 BU -X1 41 /95.2 =

= /95.2 -UC187-X1 3 GNYE -X1 42 /95.2 =

17 19
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CABLE DIAGRAM =H0+-W187 G0 A 0091 04 60201857290 = H0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KAB
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 18
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

CABLE DIAGRAM AAD_F09_002

CABLE NAME =H0+-W202 CABLE TYPE H07RN-F


FUNCTION TEXT POWER SUPPLY COMPUTER CORE NO. 3 CROSS SECTION 1,5 mm² CABLE LENGTH 12 m
DESTINATION DESTINATION
FUNCTION TEXT PAGE / COLUMN CONNECTION CORE CONNECTION PAGE / COLUMN FUNCTION TEXT
DESCRIPTION FROM DESCRIPTION TO

UPS /20.1 -X2 11 BN =RCO-X200 L1 /20.1 UPS

= /20.2 -X2 12 BU =RCO-X200 N /20.2 =

= /20.2 -X2 20 GNYE =RCO-X200 PE /20.2 =

18 20
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CABLE DIAGRAM =H0+-W202 G0 A 0091 04 60201857290 = H0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KAB
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 19
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

CABLE DIAGRAM AAD_F09_002

CABLE NAME =H0+-W303.1 CABLE TYPE H07RN-F


FUNCTION TEXT EMERGENCY CONTAINER CORE NO. 5 CROSS SECTION 1,5 mm² CABLE LENGTH 12 m
DESTINATION DESTINATION
FUNCTION TEXT PAGE / COLUMN CONNECTION CORE CONNECTION PAGE / COLUMN FUNCTION TEXT
DESCRIPTION FROM DESCRIPTION TO

EMERGENCY CONTROL ROOM /13.1 -X13 1 BN -3S1 21 /13.1 EMERGENCY CONTROL ROOM

= /13.2 -X13 2 BK -3S1 22 /13.1 =

= /13.2 -X13 101 GY -3S1 13 /13.2

= /13.2 -X13 103 BU -3S1 14 /13.2

= /13.2 -X13 20 GNYE -3S1 PE /13.2

19 21
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CABLE DIAGRAM =H0+-W303.1 G0 A 0091 04 60201857290 = H0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KAB
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 20
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

CABLE DIAGRAM AAD_F09_002

CABLE NAME =H0+-W341 CABLE TYPE ÖZ-J


FUNCTION TEXT CONTROL LINE COMPRESSOR CORE NO. 3 CROSS SECTION 1 mm² CABLE LENGTH 15 m
DESTINATION DESTINATION
FUNCTION TEXT PAGE / COLUMN CONNECTION CORE CONNECTION PAGE / COLUMN FUNCTION TEXT
DESCRIPTION FROM DESCRIPTION TO

COMPRESSOR ON /63.6 -X5 30 1 =K41-1X6 3 /63.6 COMPRESSOR ON

= /63.6 -X5 31 2 =K41-1X6 11 /63.6 =

= /63.7 -X5 20 GNYE =K41-1X6 PE /63.7 =

20 22
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CABLE DIAGRAM =H0+-W341 G0 A 0091 04 60201857290 = H0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KAB
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 21
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

CABLE DIAGRAM AAD_F09_002

CABLE NAME =H0+-W465 CABLE TYPE ÖSYZ-J


FUNCTION TEXT SENSOR HEATING BITUMEN PUMP CORE NO. 5 CROSS SECTION 0,75 mm² CABLE LENGTH 20 m
DESTINATION DESTINATION
FUNCTION TEXT PAGE / COLUMN CONNECTION CORE CONNECTION PAGE / COLUMN FUNCTION TEXT
DESCRIPTION FROM DESCRIPTION TO

SENSOR HEATING BITUMEN PUMP /76.4 -UC165-X4 1 1 -X4 41 /76.4 SENSOR HEATING BITUMEN PUMP

= /76.5 -UC165-X4 3 2 -X4 42 /76.5 =

= /76.6 -UC165-X4 4 3 -X4 23 /76.6 =

= /76.7 -UC165-X4 6 4 -X4 24 /76.7 =

= /76.7 -UC165-X4 PE GNYE -X4 20 /76.7 =

21 23
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CABLE DIAGRAM =H0+-W465 G0 A 0091 04 60201857290 = H0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KAB
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 22
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

CABLE DIAGRAM AAD_F09_002

CABLE NAME =H0+-W471 CABLE TYPE ÖSYZ-J


FUNCTION TEXT PIPE HEATING CIRCUIT 1 TEMPERATURE SENSOR CORE NO. 7 CROSS SECTION 0,75 mm² CABLE LENGTH 22 m
DESTINATION DESTINATION
FUNCTION TEXT PAGE / COLUMN CONNECTION CORE CONNECTION PAGE / COLUMN FUNCTION TEXT
DESCRIPTION FROM DESCRIPTION TO

SENSOR 1 /83.2 -UC471-X4 23 1 -X4 25 /83.2 SENSOR 1

= /83.3 -UC471-X4 25 2 -X4 26 /83.3 =

BITUMEN TEMPERATURE /83.5 -UC471-X4 26 3 -X4 28 /83.5 BITUMEN TEMPERATURE

= /83.5 -UC471-X4 27 4 -X4 29 /83.5 =

= /83.5 -UC471-X4 28 5 -X4 30 /83.5 =

BITUMEN TEMPERATURE /83.6 -UC471-X4 20 GNYE -X4 20 /83.6 BITUMEN TEMPERATURE

SH

22 24
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CABLE DIAGRAM =H0+-W471 G0 A 0091 04 60201857290 = H0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KAB
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 23
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

CABLE DIAGRAM AAD_F09_002

CABLE NAME =H0+-W482 CABLE TYPE ÖSYZ-J


FUNCTION TEXT SENSOR HEATING OIL PIPES 1 CORE NO. 4 CROSS SECTION 0,75 mm² CABLE LENGTH 22 m
DESTINATION DESTINATION
FUNCTION TEXT PAGE / COLUMN CONNECTION CORE CONNECTION PAGE / COLUMN FUNCTION TEXT
DESCRIPTION FROM DESCRIPTION TO

SENSOR HEATING OIL PIPES 1 /92.2 -UC482-X4 1 1 -X4 33 /92.2 SENSOR HEATING OIL PIPES 1

= /92.2 -UC482-X4 2 2 -X4 34 /92.2 =

= /92.3 -UC482-X4 3 3 -X4 35 /92.3 =

= /92.3 -UC482-X4 20 GNYE -X4 20 /92.3 =

SH

23 +PR/1
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CABLE DIAGRAM =H0+-W482 G0 A 0091 04 60201857290 = H0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KAB
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 24
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

AAD_Pruef2
CIRCUIT OVERVIEW R iso PROTECTIVE CONDUCTOR Z Schl [Ω] RCD(FI)

CIRCUIT (FUNCTION TEXT) CABLE NAME CABLE TYPE LENGTH


[MΩ] IPE [mA] R PE [Ω] I K [A] I N [A] IΔN [mA] UB [V] + /-
400VAC CONTAINER -W102 H07RN-F 5x2,5 mm² 12 m

COMPRESSOR -W141 H07RN-F 4x6 mm² 15 m

HEATING COMPRESSOR -W142 H07RN-F 3x1,5 mm² 15 m

BITUMEN PUMP HEATING -W165.2 H07RN-F 4x1,5 mm² 20 m

400VAC BITUMEN PIPE HEATING CIRCUIT 1 -W171 H07RN-F 3x2,5 mm² 22 m

HEATING OIL PIPES 1 PRESSURE PUMP - BURNER -W182 H07RN-F 3x2,5 mm² 20 m

HEATING AT BURNER -W185 H07RN-F 3x1,5 mm² 25 m

HEATING PRESSURE PUMP -W187 H07RN-F 3x1,5 mm² 20 m

POWER SUPPLY COMPUTER -W202 H07RN-F 3x1,5 mm² 12 m

EMERGENCY CONTAINER -W303.1 H07RN-F 5x1,5 mm² 12 m

CONTROL LINE COMPRESSOR -W341 ÖZ-J 3x1 mm² 15 m

SENSOR HEATING BITUMEN PUMP -W465 ÖSYZ-J 5x0,75 mm² 20 m

PIPE HEATING CIRCUIT 1 TEMPERATURE SENSOR -W471 ÖSYZ-J 7x0,75 mm² 22 m

SENSOR HEATING OIL PIPES 1 -W482 ÖSYZ-J 4x0,75 mm² 22 m

+KAB/24 2
DATE 2013-05-30 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CIRCUIT OVERVIEW G0 A 0091 04 60201857290 = H0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + PR
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 1
Kunde:
CLIENT.
Kom-Nr.:
COM.-NO.: LS-71366/07.04.1 ASPHALT MIXING PLANT
Schaltschrank:
SWITCH PANEL: 2400 x 1600 x 500mm Prime 140
Schaltplan-Nr.:
CIRCUIT DIAGRAM-NO.: G0 A 0091 04 Bereich: Porto Alegre
AREA:
Schutzart :
PROTECTION TYPE: RCD (FI)
Betriebsspannung:
Ammann do Brasil
OPERATING VOLTAGE: 3Ph~ / 400VAC / 60Hz Sitio do Sobrado
Steuerspannung:
CONTROL VOLTAGE: 24VDC / 230VAC 94180-452 Gravataí -RS-Brasil
Baujahr : Brasilien
YEAR OF MANUFACTURE: 2013
Prüfprotokoll EN 60204 (VDE 0113) TEST REPORT EN 60204 (VDE0113)
Prüfungsgrund: Erstprüfung Wiederholungsprüfung Sonstiges:
CAUSE OF INSPECTION: INITIAL INSPECTION REPEATED INSPECTION OTHER:
Netz:
TN-C TN-S TT IT-SYSTEM 230V 400V ........V In(Gesamt):
NET: 328 A
I (TOTAL):
Frequenz:
...... L N PEN PE
FREQUENCY .........Hz .........
Prüfung Dokumentation: vorhanden komplett Übereinstimmend mit der Installation
TEST DOCUMENTATION: EXISTING COMPLETE IN CONFORMITY TO THE INSTALLATION
Anmerkung:
NOTE:
Besichtigung:
SURVEY:
Betriebsmittel können den Einflüssen am Verwendungsort standhalten PE, L und N nicht verwechselt
OPERATING EQUIPMENT IS ABLE TO RESIST LOCAL INFLUENCES PE,L AND N ARE NOT CONFOUNDED
Alle Schutzleiter gegen Selbstlockern und Korrosion gesichert Schutz durch Isolierung aller aktiven Teile
ALL PROTECTIVE CONDUCTORS ARE PROTECTED AGAINST SELF-SLACKERING AND CORROSION PROTECTION BY ISOLATION OF ALL ACTIVE PARTS
Keine erkennbaren Schäden Sonstiges:
NO APPARENT DAMAGES OTHER:
Kennzeichnungen, Anschlussstellen und eventuelle Trennstellen in Ordnung
EQUIPMENT IDENTIFICATIONS, CONNECTION POINTS AND ANY DISCONNECTION POINTS ARE OKAY
Messung:
MEASUREMENT. Schlechtester Messwert Prüfung in Ordnung
WORST MEASURED VALUE TEST OKAY
Messgeräte entsprechen EN 61557 (VDE 0413)
MEASURING INSTRUMENTS AGREE WITH EN 61557 (VDE 0413)
Durchgängigkeit des Schutzleitersystems
(Widerstandsmessung mit Prüfstrom mind. 0,2A, max. 10A bzw. Schleifenimpedanzmessung)
CONDUCTIVITY OF THE PROTECTIVE CONDUCTOR SYSTEM
(RESISTANCE MEASUREMENT WITH TESTING CURRENT OF MIN.0,2A; MAX.10A; RESPECTIVELY LOOP IMPEDANCE MEASUREMENT)
Isolationswiderstandsmessung
INSULATION RESISTANCE MEASUREMENT
Spannungsprüfung
VOLTAGE TEST
Restspannngsprüfung (max. 60V nach 5s / 1s; sonst Warnhinweis anbringen)
RESIDUAL VOLTAGE TEST (MAX.60V AFTER 5s/1s, OTHERWISE WARNING INSTRUCTION HAS TO PUT UP)
Sonstiges:
OTHER:
Not-Aus Druckwächter, Endschalter, RCD(FI), Sicherheitstemperaturbegrenzer, etc.
Erprobung: EMERGENCY OFF MANOSTAT, LIMIT SWITCH, RCD(FI), SAFETY TEMPERATURE LIMITER, ETC.
TEST: Verriegelung Meldeleuchten, Anzeigen Funktionsprüfung Sonstiges:
LOCKING SIGNAL LAMPS, INDICATIONS FUNCTION TEST OTHER:
Bemerkungen:
REMARKS:
Prüfung nach EN60204 (VDE0113) durchgeführt Anlage / Installation funktionsfähig übernommen
TEST HAS BEEN DONE ACCORDING TO STANDARD EN 60204 (VDE 0113) THE PLANT / INSTALLATION HAS BEEN TAKEN OVER IN WORKING CONDITIONS
Ort / Datum: LOCATION / DATE: Unterschrift des Prüfers SIGNATURE OF RESPONSIBLE CONTROLLER Datum: DATE: Unterschrift des Auftraggebers SIGNATURE OF RESPONSIBLE CUSTOMER
Hinweise zum Ausfüllen: positive Prüfung negative Prüfung Bitte Nicht-Zutreffendes durchstreichen
-

+
INDICATION NOTE TO FILL OUT POSITIVE INSPECTION NEGATIVE INSPECTION PLEASE CROSS-OUT WHAT IS NOT APPLICABLE
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

-21U1

-21U2
+24V OUT 12 /21.6 +24VDC +24V -X23.1 /21.1 +24VDC

+24V OUT 13 GND -X23.2 /21.2 0VDC

D IN 18 GND -X23.3

D IN 19 CHASSIS -X23.4 /21.2 PE

COM D IN 20 /21.7 0VDC


DIN 4 -X24:1
D IN/OUT 27 /21.7 MATERIAL SHORTAGE
DIN 3 -X24:2
D IN/OUT 29
DIN 2 -X24:3
D IN 32

Danfoss - MCA110
GND -X24:4
D IN 33

D IN 37 /21.6 CONTROL RELEASE DIN 1 -X25:1

DOUT 2 -X25:2
RELAY 1 01

DOUT 1 -X25:3
RELAY 1S 02

GND -X25:4
RELAY 1Ö 03

RELAY 2 04

RELAY 2S 05

RELAY 2Ö 06

COM A OUT 39
Danfoss - FC302

A OUT 42

+10V OUT 50 /21.5 +10VDC

A IN (S201) 53

A IN (S202) 54 /21.5 ENGINE TOO HOT

COM A IN 55

=H0+PR/2 6
DATE 2012-12-07 COMMISSION : LS-71366/07.04.1 Ammann Asphalt MODULAR FREQUENCY G0 A 0091 04 60201857290 = D0
proc. UGR
CLIENT : Ammann do Brasil CONVERTER FEEDER SWITCH PANEL G0 +
Appr
ASPHALT MIXING PLANT D-31061 Alfeld 1 CAD: 71366_G0
MODIFICATIONDATE NAME origin \\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 5
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

-22U1

-22U2
+24V OUT 12 /31.6 +24VDC +24V -X23.1 /31.1 +24VDC

+24V OUT 13 GND -X23.2 /31.2 0VDC

D IN 18 GND -X23.3

D IN 19 CHASSIS -X23.4 /31.2 PE

COM D IN 20 /31.7 0VDC


DIN 4 -X24:1
D IN/OUT 27 /31.7 MATERIAL SHORTAGE
DIN 3 -X24:2
D IN/OUT 29
DIN 2 -X24:3
D IN 32

Danfoss - MCA110
GND -X24:4
D IN 33

D IN 37 /31.6 CONTROL RELEASE DIN 1 -X25:1

DOUT 2 -X25:2
RELAY 1 01

DOUT 1 -X25:3
RELAY 1S 02

GND -X25:4
RELAY 1Ö 03

RELAY 2 04

RELAY 2S 05

RELAY 2Ö 06

COM A OUT 39
Danfoss - FC302

A OUT 42

+10V OUT 50 /31.5 +10VDC

A IN (S201) 53

A IN (S202) 54 /31.5 ENGINE TOO HOT

COM A IN 55

5 7
DATE 2012-12-07 COMMISSION : LS-71366/07.04.1 Ammann Asphalt MODULAR FREQUENCY G0 A 0091 04 60201857290 = D0
proc. UGR
CLIENT : Ammann do Brasil CONVERTER FEEDER SWITCH PANEL G0 +
Appr
ASPHALT MIXING PLANT D-31061 Alfeld 2 CAD: 71366_G0
MODIFICATIONDATE NAME origin \\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 6
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

-23U1

-23U2
+24V OUT 12 /41.6 +24VDC +24V -X23.1 /41.1 +24VDC

+24V OUT 13 GND -X23.2 /41.2 0VDC

D IN 18 GND -X23.3

D IN 19 CHASSIS -X23.4 /41.2 PE

COM D IN 20 /41.7 0VDC


DIN 4 -X24:1
D IN/OUT 27 /41.7 MATERIAL SHORTAGE
DIN 3 -X24:2
D IN/OUT 29
DIN 2 -X24:3
D IN 32

Danfoss - MCA110
GND -X24:4
D IN 33

D IN 37 /41.6 CONTROL RELEASE DIN 1 -X25:1

DOUT 2 -X25:2
RELAY 1 01

DOUT 1 -X25:3
RELAY 1S 02

GND -X25:4
RELAY 1Ö 03

RELAY 2 04

RELAY 2S 05

RELAY 2Ö 06

COM A OUT 39
Danfoss - FC302

A OUT 42

+10V OUT 50 /41.5 +10VDC

A IN (S201) 53

A IN (S202) 54 /41.5 ENGINE TOO HOT

COM A IN 55

6 13
DATE 2012-12-07 COMMISSION : LS-71366/07.04.1 Ammann Asphalt MODULAR FREQUENCY G0 A 0091 04 60201857290 = D0
proc. UGR
CLIENT : Ammann do Brasil CONVERTER FEEDER SWITCH PANEL G0 +
Appr
ASPHALT MIXING PLANT D-31061 Alfeld 3 CAD: 71366_G0
MODIFICATIONDATE NAME origin \\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 7
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

230VAC (P)
=H0/19.10 / 3L1 3L1 / 21.8
230VAC (N)
=H0/19.10 / 3L2 3L2 / 21.9
+24VDC
=H0/19.10 / 3L+ 3L+ / 21.8
0VDC
=H0/19.10 / 3L- 3L- / 21.9

PE PE PE PE PE
-X2 21 21 22 22 22 20 20 -X3 21 21 21 22 22 22 20 20 20

+230VAC 0VAC +24VDC 0VDC

7 21
DATE 2013-02-22 COMMISSION : LS-71366/07.04.1 Ammann Asphalt FEED CONTROL G0 A 0091 04 60201857290 = D0
proc. PBR
CLIENT : Ammann do Brasil VOLTAGE SWITCH PANEL G0 +
Appr
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 13
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

2L11 400V +/-5% 3Ph 50Hz 2L11 230VAC (P)


13.10 / 3L1 3L1 / 31.8
2L12 2L12 +24VDC
13.10 / 3L+ 3L+ / 31.8
2L13 2L13

=H0/20.9 / IBS+ IBS+ / 31.1 1 3 5


=H0/20.9 / IBS- IBS- / 31.1 -21Q1
/21.9
5 A ge I> I> I>
CLASS 10 2 4 6
PKE12/XTU-12
1 3 5
CABLE FINISHED -21K1
/21.9 2 4 6
PE
PE
-X2 20 -X1 4

-21U2 -21U1
-X23.1-X23.2-X23.4 -X22
1,2,3
RS485
61,68,69
91
(L1)
92
(L2)
93
(L3)
95
(PE)
FREQUENCY CONVERTER
IBS-MODULE FC302 P1K5
MCA 110 PARAMETER:
P07015_50_FW306 0-10V
& CABLE
S202
OFF(U)

Bus In Bus Out Bus Ter (U) (V) (W) (PE) (SH) (SH) (PE sense) (+) (AE) (+24VDC) (DE) (DE) (0VDC)
S801 96 97 98 99 PE1 PE2 99 50 54 12 37 27 20
-X20 -X21
On/On

ÖSYZ-J 3x0,75 mm² 16 m


ÖSYZ-J 4x1,5 mm² 16 m

H07RN-F 4x1,5 mm² 18 m


MATERIAL SHORTAGE 1
PTC SENSOR
PE
-W121

-W421
DRIVE

-X8 1 3 1 4 2 20
GNYE

GNYE

-W321
1 2 3 1 2 1.13
BN GY BK GNYE
-21Q1
1,5KW MOTOR U1 V1 W1 PE /21.3 1.14
IN THE DELTA M
CONNECT! -21M1 3~
1,5 kW Θ

3,5 A T1 T2 A1
-21K1
PKE32 A2
BN BK BU PE 230VAC
-21B2
IIA3010 230VAC (N)
DRIVE MOTOR REGULATOR-RELEASE 13.10 / 3L2 3L2 / 31.9
0VDC
CLOSED HOT 13.10 / 3L- 3L- / 31.9

MATERIAL SHORTAGE POWER SUPPLY


ON
NOTE: MOTOR 1 2 /21.3
AND MOTOR-TEMPERATURE SENSOR DIRECTLY 3 4 /21.4
AT FREQUENCY CONVERTER CONNECT! 5 6 /21.4

13 22
DATE 2013-04-29 COMMISSION : LS-71366/07.04.1 Ammann Asphalt FEEDER 1 G0 A 0091 04 60201857290 = D0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 +
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 21
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

=G0-A2E2
mV/V ANALOGUE INPUT IBIL SGI 2/F-PAC CHANNEL 1

mV/V
1.3 2.2 2.1 2.3 1.2 1.1 1.4 3.1 3.2

GN BN WH PK GY YE

-X421 23 24 25 26 27 28 31 20 23 24 25 26 27 28 32 34

GY BK RD BU GN WH GY BK RD BU GN WH

BK RD BU BK RD BU

-21B4 -21B5

GY WH GN GY WH GN

WEIGHING CELL 1 WEIGHING CELL 2

21 31
DATE 2013-05-28 COMMISSION : LS-71366/07.04.1 Ammann Asphalt BELT SCALE FEEDER 1 G0 A 0091 04 60201857290 = D0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 +
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 22
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

2L11 400V +/-5% 3Ph 50Hz 2L11 230VAC (P)


21.10 / 3L1 3L1 / 41.8
2L12 2L12 +24VDC
21.10 / 3L+ 3L+ / 41.8
2L13 2L13

21.2 / IBS+ IBS+ / 41.1 1 3 5


21.2 / IBS- IBS- / 41.1 -22Q1
/31.9
5 A ge I> I> I>
CLASS 10 2 4 6
PKE12/XTU-12
1 3 5
CABLE FINISHED -22K1
/31.9 2 4 6
PE
PE
-X2 20 -X1 4

-22U2 -22U1
-X23.1-X23.2-X23.4 -X22
1,2,3
RS485
61,68,69
91
(L1)
92
(L2)
93
(L3)
95
(PE)
FREQUENCY CONVERTER
IBS-MODULE FC302 P1K5
MCA 110 PARAMETER:
P07015_50_FW306 0-10V
& CABLE
S202
OFF(U)

Bus In Bus Out Bus Ter (U) (V) (W) (PE) (SH) (SH) (PE sense) (+) (AE) (+24VDC) (DE) (DE) (0VDC)
S801 96 97 98 99 PE1 PE2 99 50 54 12 37 27 20
-X20 -X21
On/On

ÖSYZ-J 3x0,75 mm² 15 m


ÖSYZ-J 4x1,5 mm² 15 m

H07RN-F 4x1,5 mm² 15 m


MATERIAL SHORTAGE 2
PTC SENSOR
PE
-W122

-W422
DRIVE

-X8 11 13 11 14 12 20
GNYE

GNYE

-W322
1 2 3 1 2 1.13
BN GY BK GNYE
-22Q1
1,5KW MOTOR U1 V1 W1 PE /31.3 1.14
IN THE DELTA M
CONNECT! -22M1 3~
1,5 kW Θ

3,5 A T1 T2 A1
-22K1
PKE32 A2
BN BK BU PE 230VAC
-22B2
IIA3010 230VAC (N)
DRIVE MOTOR REGULATOR-RELEASE 21.10 / 3L2 3L2 / 41.9
0VDC
CLOSED HOT 21.10 / 3L- 3L- / 41.9

MATERIAL SHORTAGE POWER SUPPLY


ON
NOTE: MOTOR 1 2 /31.3
AND MOTOR-TEMPERATURE SENSOR DIRECTLY 3 4 /31.4
AT FREQUENCY CONVERTER CONNECT! 5 6 /31.4

22 32
DATE 2013-04-29 COMMISSION : LS-71366/07.04.1 Ammann Asphalt FEEDER 2 G0 A 0091 04 60201857290 = D0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 +
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 31
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

=G0-A2E2
ANALOGUE INPUT IBIL SGI 2/F-PAC CHANNEL 2
mV/V

mV/V
5.3 6.2 6.1 6.3 5.2 5.1 5.4 7.1 7.2

GN BN WH PK GY YE

-X422 23 24 25 26 27 28 31 20 23 24 25 26 27 28 32 34

GY BK RD BU GN WH GY BK RD BU GN WH

BK RD BU BK RD BU

-22B4 -22B5

GY WH GN GY WH GN

WEIGHING CELL 1 WEIGHING CELL 2

31 41
DATE 2013-05-28 COMMISSION : LS-71366/07.04.1 Ammann Asphalt BELT SCALE G0 A 0091 04 60201857290 = D0
proc. UGR
CLIENT : Ammann do Brasil FEEDER 2 SWITCH PANEL G0 +
Appr
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 32
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

2L11 400V +/-5% 3Ph 50Hz 2L11 230VAC (P)


31.10 / 3L1 3L1 / 42.1
2L12 2L12 +24VDC
31.10 / 3L+ 3L+ / 42.1
2L13 2L13
31.2 / IBS+ IBS+ / =T2/41.1
31.2 / IBS- IBS- / =T2/41.1
1 3 5
-23Q1
/41.9
5 A ge I> I> I>
CLASS 10 2 4 6
PKE12/XTU-12
1 3 5
CABLE FINISHED -23K1
/41.9 2 4 6
PE
PE
-X2 20 -X1 4

-23U2 -23U1
-X23.1-X23.2-X23.4 -X22
1,2,3
RS485
61,68,69
91
(L1)
92
(L2)
93
(L3)
95
(PE)
FREQUENCY CONVERTER
IBS-MODULE FC302 P1K5
MCA 110 PARAMETER:
P07015_50_FW306 0-10V
& CABLE
S202
OFF(U)

Bus In Bus Out Bus Ter (U) (V) (W) (PE) (SH) (SH) (PE sense) (+) (AE) (+24VDC) (DE) (DE) (0VDC)
S801 96 97 98 99 PE1 PE2 99 50 54 12 37 27 20
-X20 -X21
On/On

ÖSYZ-J 3x0,75 mm² 15 m


ÖSYZ-J 4x1,5 mm² 15 m

H07RN-F 4x1,5 mm² 15 m


MATERIAL SHORTAGE 3
PE

PTC SENSOR
-X8 31 33 31 34 32 20
-W123

-W423
DRIVE
GNYE

GNYE

-W323
1 2 3 1 2 1.13
BN GY BK GNYE
-23Q1
1,5KW MOTOR U1 V1 W1 PE /41.3 1.14
IN THE DELTA M
CONNECT! -23M1 3~
1,5 kW Θ

3,5 A T1 T2 A1
-23K1
PKE32 A2
BN BK BU PE 230VAC
-23B2
IIA3010 230VAC (N)
31.10 / 3L2 3L2 / 42.4
0VDC
31.10 / 3L- 3L- / 42.4

DRIVE MOTOR REGULATOR-RELEASE MATERIAL SHORTAGE POWER SUPPLY


CLOSED HOT ON
NOTE: MOTOR 1 2 /41.3
AND MOTOR-TEMPERATURE SENSOR DIRECTLY 3 4 /41.4
AT FREQUENCY CONVERTER CONNECT! 5 6 /41.4

32 42
DATE 2013-04-29 COMMISSION : LS-71366/07.04.1 Ammann Asphalt FEEDER 3 G0 A 0091 04 60201857290 = D0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 +
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 41
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

230VAC (P)
41.10 / 3L1 3L1 / =T0/13.1
+24VDC
41.10 / 3L+ 3L+ / =T0/13.1

2L1
400V +/-5% 3Ph 50Hz 2L1
2L2 2L2
2L3 2L3
13 1.21
1 3 5 -24K1 -24Q1
-24Q1 /42.5 14 /42.1 1.22
/42.5
/42.7 I> I> I>
0,35 A ge 2 4 6
CLASS 10
PKE12/XTU-1,2 1 3 5
-24K1
/42.5 2 4 6

=G0-D1A32

OUTPUT
4.3 4.4
4.3
INPUT INPUT

=G0-D1E32

11

2,5 mm²
-24K11
/42.6 14

1.13
PE
-24Q1
-X1 21 22 23 24 /42.1 1.14

A1 A1
-24K1 -24K11
PKE12 A2 38.51 A2
230VAC 24VDC

230VAC (N)
41.10 / 3L2 3L2 / =T0/13.1
-W124 0VDC
41.10 / 3L- 3L- / =T0/13.1
BN BK GY GNYE
H07RN-F 4x1,5 mm² 17 m
VIBRATOR MATERIAL SHORTAGE VIBRATOR VIBRATOR
ON ON ON ERROR
U1 V1 W1
1 2 /42.1 11 14 /42.5

-24M1
M 3 4 /42.2
3~ 5 6 /42.2
0,18 kW 13 14 /42.7
0,35 A PE

VIBRATOR MATERIAL SHORTAGE


41 43
DATE 2013-02-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt FEEDER 3 G0 A 0091 04 60201857290 = D0
proc. UGR
CLIENT : Ammann do Brasil VIBRATOR SWITCH PANEL G0 +
Appr
ASPHALT MIXING PLANT D-31061 Alfeld 0,18 KW CAD: 71366_G0
MODIFICATIONDATE NAME origin \\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 42
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

=G0-A3E2
ANALOGUE INPUT IBIL SGI 2/F-PAC CHANNEL 1
mV/V

mV/V
1.3 2.2 2.1 2.3 1.2 1.1 1.4 3.1 3.2

GN BN WH PK GY YE

-X423 23 24 25 26 27 28 31 20 23 24 25 26 27 28 32 34

GY BK RD BU GN WH GY BK RD BU GN WH

BK RD BU BK RD BU

-23B4 -23B5

GY WH GN GY WH GN

WEIGHING CELL 1 WEIGHING CELL 2

42 +KLE/1
DATE 2013-05-28 COMMISSION : LS-71366/07.04.1 Ammann Asphalt BELT SCALE G0 A 0091 04 60201857290 = D0
proc. UGR
CLIENT : Ammann do Brasil FEEDER 3 SWITCH PANEL G0 +
Appr
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 43
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

TERMINAL STRIP OVERVIEW AAD_F14_002

TERMINALS
TERMINAL BLOCK FUNCTION TEXT PAGE TERMINAL DIAGRAM
FIRST LATEST SUM PE SUM N TOTAL NUMBER
-X1 CONSUMER 400VAC 4 24 4 0 7 =D0+KLE/11
-X2 CONTROL TERMINAL 230VAC 20 22 5 0 10 =D0+KLE/12
-X3 CONTROL TERMINAL 24VDC 20 22 3 0 9 =D0+KLE/13
-X8 VOLTAGE FU 1 34 3 0 18 =D0+KLE/14
-X421 BELT SCALE FEEDER 1 20 34 1 0 16 =D0+KLE/15
-X422 BELT SCALE FEEDER 2 20 34 1 0 16 =D0+KLE/16
-X423 BELT SCALE FEEDER 3 20 34 1 0 16 =D0+KLE/17

+/43 11
DATE 2013-05-30 COMMISSION : LS-71366/07.04.1 Ammann Asphalt TERMINAL STRIP REVIEW G0 A 0091 04 60201857290 = D0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KLE
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 1
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

TERMINAL DIAGRAM AAD_F13_001

CABLE NAME

CABLE NAME
-W124
STRIP
=D0+-X1
CONSUMER 400VAC

H07RN-F 4x1,5 mm²

CABLE TYPE

CABLE TYPE
CONNECTION

CONNECTION
TERMINAL
FUNCTION TEXT DESTINATION DESCRIPTION DESTINATION DESCRIPTION PAGE / COLUMN

DRIVE -21U1 95 4 /21.4


= -22U1 95 4 /31.4
= -23U1 95 4 /41.4
VIBRATOR MATERIAL SHORTAGE BN -24M1 U1 21 -24K1 2 /42.1
= BK -24M1 V1 22 -24K1 4 /42.2
= GY -24M1 W1 23 -24K1 6 /42.2
= GNYE -24M1 PE 24 /42.2

1 12
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt TERMINAL DIAGRAM =D0+-X1 G0 A 0091 04 60201857290 = D0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KLE
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 11
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

TERMINAL DIAGRAM AAD_F13_001

CABLE NAME

CABLE NAME
STRIP
=D0+-X2
CONTROL TERMINAL 230VAC

CABLE TYPE

CABLE TYPE
CONNECTION

CONNECTION
TERMINAL
FUNCTION TEXT DESTINATION DESCRIPTION DESTINATION DESCRIPTION PAGE / COLUMN

0VAC 20 /13.3
= 20 /13.4
-21U2 -X23.4 20 /21.2
-22U2 -X23.4 20 /31.2
-23U2 -X23.4 20 /41.2
+230VAC 21 =H0-X2 21 /13.3
-21Q1 1.13
+230VAC 21 /13.3
= 22 =H0-X2 22 /13.3
-21K1 A2
+230VAC 22 /13.3
= 22 /13.3

11 13
DATE 2013-05-30 COMMISSION : LS-71366/07.04.1 Ammann Asphalt TERMINAL DIAGRAM =D0+-X2 G0 A 0091 04 60201857290 = D0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KLE
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 12
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

TERMINAL DIAGRAM AAD_F13_001

CABLE NAME

CABLE NAME
STRIP
=D0+-X3
CONTROL TERMINAL 24VDC

CABLE TYPE

CABLE TYPE
CONNECTION

CONNECTION
TERMINAL
FUNCTION TEXT DESTINATION DESCRIPTION DESTINATION DESCRIPTION PAGE / COLUMN

0VDC 20 /13.10
= 20 /13.10
= 20 /13.10
+24VDC 21 =G0-D1E32 1.2 /13.8
-24K1 13
+24VDC 21 /13.8
= 21 /13.9
0VDC 22 =H0-7K1 54 /13.9
-24K11 A2
0VDC 22 /13.9
= 22 /13.9

12 14
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt TERMINAL DIAGRAM =D0+-X3 G0 A 0091 04 60201857290 = D0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KLE
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 13
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

TERMINAL DIAGRAM AAD_F13_001

CABLE NAME

CABLE NAME
-W323
-W322
-W321
STRIP
=D0+-X8
VOLTAGE FU

H07RN-F 4x1,5 mm²

H07RN-F 4x1,5 mm²

H07RN-F 4x1,5 mm²

CABLE TYPE

CABLE TYPE
CONNECTION

CONNECTION
TERMINAL
FUNCTION TEXT DESTINATION DESCRIPTION DESTINATION DESCRIPTION PAGE / COLUMN

MOTOR CLOSED HOT -X8 3 1 -21U1 12 /21.6


MATERIAL SHORTAGE BN -21B2 BN 1 /21.7
= BK -21B2 BU 2 -21U1 20 /21.7
REGULATOR-RELEASE -X8 1 3 -21U1 37 /21.6
MATERIAL SHORTAGE GY -21B2 BK 4 -21U1 27 /21.7
MOTOR CLOSED HOT -X8 13 11 -22U1 12 /31.6
MATERIAL SHORTAGE BN -22B2 BN 11 /31.7
= BK -22B2 BU 12 -22U1 20 /31.7
REGULATOR-RELEASE -X8 11 13 -22U1 37 /31.6
MATERIAL SHORTAGE GY -22B2 BK 14 -22U1 27 /31.7
= GNYE -21B2 PE 20 /21.8
= GNYE -22B2 PE 20 /31.8
= GNYE -23B2 PE 20 /41.8
MOTOR CLOSED HOT -X8 33 31 -23U1 12 /41.6
MATERIAL SHORTAGE BN -23B2 BN 31 /41.7
= BK -23B2 BU 32 -23U1 20 /41.7
REGULATOR-RELEASE -X8 31 33 -23U1 37 /41.6
MATERIAL SHORTAGE GY -23B2 BK 34 -23U1 27 /41.7

13 15
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt TERMINAL DIAGRAM =D0+-X8 G0 A 0091 04 60201857290 = D0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KLE
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 14
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

TERMINAL DIAGRAM AAD_F13_001

CABLE NAME

CABLE NAME
STRIP
=D0+-X421
BELT SCALE FEEDER 1

CABLE TYPE

CABLE TYPE
CONNECTION

CONNECTION
TERMINAL
FUNCTION TEXT DESTINATION DESCRIPTION DESTINATION DESCRIPTION PAGE / COLUMN

WEIGHING CELL 1 20 /22.7


-21B4 GY 23 /22.5
WEIGHING CELL 1 -21B5 GY 23 /22.7
= -21B4 BK 24 /22.6
WEIGHING CELL 2 -21B5 BK 24 /22.7
WEIGHING CELL 1 -21B4 RD 25 /22.6
WEIGHING CELL 2 -21B5 RD 25 /22.7
WEIGHING CELL 1 -21B4 BU 26 /22.6
WEIGHING CELL 2 -21B5 BU 26 /22.7
WEIGHING CELL 1 -21B4 GN 27 /22.6
WEIGHING CELL 2 -21B5 GN 27 /22.8
WEIGHING CELL 1 -21B4 WH 28 /22.6
WEIGHING CELL 2 -21B5 WH 28 /22.8
WEIGHING CELL 1 31 /22.7
WEIGHING CELL 2 32 /22.8
= 34 /22.8

14 16
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt TERMINAL DIAGRAM =D0+-X421 G0 A 0091 04 60201857290 = D0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KLE
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 15
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

TERMINAL DIAGRAM AAD_F13_001

CABLE NAME

CABLE NAME
STRIP
=D0+-X422
BELT SCALE FEEDER 2

CABLE TYPE

CABLE TYPE
CONNECTION

CONNECTION
TERMINAL
FUNCTION TEXT DESTINATION DESCRIPTION DESTINATION DESCRIPTION PAGE / COLUMN

WEIGHING CELL 1 20 /32.7


-22B4 GY 23 /32.5
WEIGHING CELL 1 -22B5 GY 23 /32.7
= -22B4 BK 24 /32.6
WEIGHING CELL 2 -22B5 BK 24 /32.7
WEIGHING CELL 1 -22B4 RD 25 /32.6
WEIGHING CELL 2 -22B5 RD 25 /32.7
WEIGHING CELL 1 -22B4 BU 26 /32.6
WEIGHING CELL 2 -22B5 BU 26 /32.7
WEIGHING CELL 1 -22B4 GN 27 /32.6
WEIGHING CELL 2 -22B5 GN 27 /32.8
WEIGHING CELL 1 -22B4 WH 28 /32.6
WEIGHING CELL 2 -22B5 WH 28 /32.8
WEIGHING CELL 1 31 /32.7
WEIGHING CELL 2 32 /32.8
= 34 /32.8

15 17
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt TERMINAL DIAGRAM =D0+-X422 G0 A 0091 04 60201857290 = D0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KLE
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 16
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

TERMINAL DIAGRAM AAD_F13_001

CABLE NAME

CABLE NAME
STRIP
=D0+-X423
BELT SCALE FEEDER 3

CABLE TYPE

CABLE TYPE
CONNECTION

CONNECTION
TERMINAL
FUNCTION TEXT DESTINATION DESCRIPTION DESTINATION DESCRIPTION PAGE / COLUMN

WEIGHING CELL 1 20 /43.7


-23B4 GY 23 /43.5
WEIGHING CELL 1 -23B5 GY 23 /43.7
= -23B4 BK 24 /43.6
WEIGHING CELL 2 -23B5 BK 24 /43.7
WEIGHING CELL 1 -23B4 RD 25 /43.6
WEIGHING CELL 2 -23B5 RD 25 /43.7
WEIGHING CELL 1 -23B4 BU 26 /43.6
WEIGHING CELL 2 -23B5 BU 26 /43.7
WEIGHING CELL 1 -23B4 GN 27 /43.6
WEIGHING CELL 2 -23B5 GN 27 /43.8
WEIGHING CELL 1 -23B4 WH 28 /43.6
WEIGHING CELL 2 -23B5 WH 28 /43.8
WEIGHING CELL 1 31 /43.7
WEIGHING CELL 2 32 /43.8
= 34 /43.8

16 +KAB/1
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt TERMINAL DIAGRAM =D0+-X423 G0 A 0091 04 60201857290 = D0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KLE
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 17
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

CABLE PLAN
1. PAGE PAGE
CABLE TYPE ID CORES CROSS SECTION LENGTH FUNCTION TEXT CIRCUIT DIAGRAM CABLE DIAGRAM

ÖSYZ-J -W121 4 1,5 16 m DRIVE +/21.3 =D0+KAB/11

-W122 4 1,5 15 m = +/31.3 =D0+KAB/12

-W123 4 1,5 15 m = +/41.3 =D0+KAB/13

H07RN-F -W124 4 1,5 17 m VIBRATOR MATERIAL SHORTAGE +/42.1 =D0+KAB/14

-W321 4 1,5 18 m MATERIAL SHORTAGE 1 +/21.7 =D0+KAB/15

-W322 4 1,5 15 m MATERIAL SHORTAGE 2 +/31.7 =D0+KAB/16

-W323 4 1,5 15 m MATERIAL SHORTAGE 3 +/41.8 =D0+KAB/17

ÖSYZ-J -W421 3 0,75 16 m PTC SENSOR +/21.3 =D0+KAB/18

-W422 3 0,75 15 m = +/31.3 =D0+KAB/19

-W423 3 0,75 15 m = +/41.3 =D0+KAB/20

+KLE/17 11
DATE 2013-05-30 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CABLE PLAN G0 A 0091 04 60201857290 = D0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KAB
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 1
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

CABLE DIAGRAM AAD_F09_002

CABLE NAME =D0+-W121 CABLE TYPE ÖSYZ-J


FUNCTION TEXT DRIVE CORE NO. 4 CROSS SECTION 1,5 mm² CABLE LENGTH 16 m
DESTINATION DESTINATION
FUNCTION TEXT PAGE / COLUMN CONNECTION CORE CONNECTION PAGE / COLUMN FUNCTION TEXT
DESCRIPTION FROM DESCRIPTION TO

DRIVE /21.3 -21M1 U1 1 -21U1 96 /21.3 DRIVE

= /21.3 -21M1 V1 2 -21U1 97 /21.4

= /21.3 -21M1 W1 3 -21U1 98 /21.4

GNYE

SH

1 12
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CABLE DIAGRAM =D0+-W121 G0 A 0091 04 60201857290 = D0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KAB
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 11
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

CABLE DIAGRAM AAD_F09_002

CABLE NAME =D0+-W122 CABLE TYPE ÖSYZ-J


FUNCTION TEXT DRIVE CORE NO. 4 CROSS SECTION 1,5 mm² CABLE LENGTH 15 m
DESTINATION DESTINATION
FUNCTION TEXT PAGE / COLUMN CONNECTION CORE CONNECTION PAGE / COLUMN FUNCTION TEXT
DESCRIPTION FROM DESCRIPTION TO

DRIVE /31.3 -22M1 U1 1 -22U1 96 /31.3 DRIVE

= /31.3 -22M1 V1 2 -22U1 97 /31.4

= /31.3 -22M1 W1 3 -22U1 98 /31.4

GNYE

SH

11 13
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CABLE DIAGRAM =D0+-W122 G0 A 0091 04 60201857290 = D0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KAB
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 12
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

CABLE DIAGRAM AAD_F09_002

CABLE NAME =D0+-W123 CABLE TYPE ÖSYZ-J


FUNCTION TEXT DRIVE CORE NO. 4 CROSS SECTION 1,5 mm² CABLE LENGTH 15 m
DESTINATION DESTINATION
FUNCTION TEXT PAGE / COLUMN CONNECTION CORE CONNECTION PAGE / COLUMN FUNCTION TEXT
DESCRIPTION FROM DESCRIPTION TO

DRIVE /41.3 -23M1 U1 1 -23U1 96 /41.3 DRIVE

= /41.3 -23M1 V1 2 -23U1 97 /41.4

= /41.3 -23M1 W1 3 -23U1 98 /41.4

GNYE

SH

12 14
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CABLE DIAGRAM =D0+-W123 G0 A 0091 04 60201857290 = D0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KAB
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 13
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

CABLE DIAGRAM AAD_F09_002

CABLE NAME =D0+-W124 CABLE TYPE H07RN-F


FUNCTION TEXT VIBRATOR MATERIAL SHORTAGE CORE NO. 4 CROSS SECTION 1,5 mm² CABLE LENGTH 17 m
DESTINATION DESTINATION
FUNCTION TEXT PAGE / COLUMN CONNECTION CORE CONNECTION PAGE / COLUMN FUNCTION TEXT
DESCRIPTION FROM DESCRIPTION TO

VIBRATOR MATERIAL SHORTAGE /42.1 -X1 21 BN -24M1 U1 /42.1 VIBRATOR MATERIAL SHORTAGE

= /42.2 -X1 22 BK -24M1 V1 /42.1 =

= /42.2 -X1 23 GY -24M1 W1 /42.1 =

= /42.2 -X1 24 GNYE -24M1 PE /42.1 =

13 15
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CABLE DIAGRAM =D0+-W124 G0 A 0091 04 60201857290 = D0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KAB
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 14
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

CABLE DIAGRAM AAD_F09_002

CABLE NAME =D0+-W321 CABLE TYPE H07RN-F


FUNCTION TEXT MATERIAL SHORTAGE 1 CORE NO. 4 CROSS SECTION 1,5 mm² CABLE LENGTH 18 m
DESTINATION DESTINATION
FUNCTION TEXT PAGE / COLUMN CONNECTION CORE CONNECTION PAGE / COLUMN FUNCTION TEXT
DESCRIPTION FROM DESCRIPTION TO

MATERIAL SHORTAGE /21.7 -X8 1 BN -21B2 BN /21.7 MATERIAL SHORTAGE

= /21.7 -X8 2 BK -21B2 BU /21.7 =

= /21.7 -X8 4 GY -21B2 BK /21.7 =

= /21.8 -X8 20 GNYE -21B2 PE /21.8

14 16
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CABLE DIAGRAM =D0+-W321 G0 A 0091 04 60201857290 = D0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KAB
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 15
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

CABLE DIAGRAM AAD_F09_002

CABLE NAME =D0+-W322 CABLE TYPE H07RN-F


FUNCTION TEXT MATERIAL SHORTAGE 2 CORE NO. 4 CROSS SECTION 1,5 mm² CABLE LENGTH 15 m
DESTINATION DESTINATION
FUNCTION TEXT PAGE / COLUMN CONNECTION CORE CONNECTION PAGE / COLUMN FUNCTION TEXT
DESCRIPTION FROM DESCRIPTION TO

MATERIAL SHORTAGE /31.7 -X8 11 BN -22B2 BN /31.7 MATERIAL SHORTAGE

= /31.7 -X8 12 BK -22B2 BU /31.7 =

= /31.7 -X8 14 GY -22B2 BK /31.7 =

= /31.8 -X8 20 GNYE -22B2 PE /31.8

15 17
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CABLE DIAGRAM =D0+-W322 G0 A 0091 04 60201857290 = D0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KAB
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 16
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

CABLE DIAGRAM AAD_F09_002

CABLE NAME =D0+-W323 CABLE TYPE H07RN-F


FUNCTION TEXT MATERIAL SHORTAGE 3 CORE NO. 4 CROSS SECTION 1,5 mm² CABLE LENGTH 15 m
DESTINATION DESTINATION
FUNCTION TEXT PAGE / COLUMN CONNECTION CORE CONNECTION PAGE / COLUMN FUNCTION TEXT
DESCRIPTION FROM DESCRIPTION TO

MATERIAL SHORTAGE /41.7 -X8 31 BN -23B2 BN /41.7 MATERIAL SHORTAGE

= /41.7 -X8 32 BK -23B2 BU /41.7 =

= /41.7 -X8 34 GY -23B2 BK /41.7 =

= /41.8 -X8 20 GNYE -23B2 PE /41.8

16 18
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CABLE DIAGRAM =D0+-W323 G0 A 0091 04 60201857290 = D0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KAB
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 17
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

CABLE DIAGRAM AAD_F09_002

CABLE NAME =D0+-W421 CABLE TYPE ÖSYZ-J


FUNCTION TEXT PTC SENSOR CORE NO. 3 CROSS SECTION 0,75 mm² CABLE LENGTH 16 m
DESTINATION DESTINATION
FUNCTION TEXT PAGE / COLUMN CONNECTION CORE CONNECTION PAGE / COLUMN FUNCTION TEXT
DESCRIPTION FROM DESCRIPTION TO

DRIVE /21.3 -21M1 T1 1 -21U1 50 /21.5 +10VDC

= /21.3 -21M1 T2 2 -21U1 54 /21.5 ENGINE TOO HOT

GNYE

SH

17 19
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CABLE DIAGRAM =D0+-W421 G0 A 0091 04 60201857290 = D0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KAB
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 18
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

CABLE DIAGRAM AAD_F09_002

CABLE NAME =D0+-W422 CABLE TYPE ÖSYZ-J


FUNCTION TEXT PTC SENSOR CORE NO. 3 CROSS SECTION 0,75 mm² CABLE LENGTH 15 m
DESTINATION DESTINATION
FUNCTION TEXT PAGE / COLUMN CONNECTION CORE CONNECTION PAGE / COLUMN FUNCTION TEXT
DESCRIPTION FROM DESCRIPTION TO

DRIVE /31.3 -22M1 T1 1 -22U1 50 /31.5 +10VDC

= /31.3 -22M1 T2 2 -22U1 54 /31.5 ENGINE TOO HOT

GNYE

SH

18 20
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CABLE DIAGRAM =D0+-W422 G0 A 0091 04 60201857290 = D0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KAB
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 19
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

CABLE DIAGRAM AAD_F09_002

CABLE NAME =D0+-W423 CABLE TYPE ÖSYZ-J


FUNCTION TEXT PTC SENSOR CORE NO. 3 CROSS SECTION 0,75 mm² CABLE LENGTH 15 m
DESTINATION DESTINATION
FUNCTION TEXT PAGE / COLUMN CONNECTION CORE CONNECTION PAGE / COLUMN FUNCTION TEXT
DESCRIPTION FROM DESCRIPTION TO

DRIVE /41.3 -23M1 T1 1 -23U1 50 /41.5 +10VDC

= /41.3 -23M1 T2 2 -23U1 54 /41.5 ENGINE TOO HOT

GNYE

SH

19 +PR/1
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CABLE DIAGRAM =D0+-W423 G0 A 0091 04 60201857290 = D0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KAB
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 20
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

AAD_Pruef2
CIRCUIT OVERVIEW R iso PROTECTIVE CONDUCTOR Z Schl [Ω] RCD(FI)

CIRCUIT (FUNCTION TEXT) CABLE NAME CABLE TYPE LENGTH


[MΩ] IPE [mA] R PE [Ω] I K [A] I N [A] IΔN [mA] UB [V] + /-
DRIVE -W121 ÖSYZ-J 4x1,5 mm² 16 m

= -W122 ÖSYZ-J 4x1,5 mm² 15 m

= -W123 ÖSYZ-J 4x1,5 mm² 15 m

VIBRATOR MATERIAL SHORTAGE -W124 H07RN-F 4x1,5 mm² 17 m

MATERIAL SHORTAGE 1 -W321 H07RN-F 4x1,5 mm² 18 m

MATERIAL SHORTAGE 2 -W322 H07RN-F 4x1,5 mm² 15 m

MATERIAL SHORTAGE 3 -W323 H07RN-F 4x1,5 mm² 15 m

PTC SENSOR -W421 ÖSYZ-J 3x0,75 mm² 16 m

= -W422 ÖSYZ-J 3x0,75 mm² 15 m

= -W423 ÖSYZ-J 3x0,75 mm² 15 m

+KAB/20 2
DATE 2013-05-30 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CIRCUIT OVERVIEW G0 A 0091 04 60201857290 = D0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + PR
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 1
Kunde:
CLIENT.
Kom-Nr.:
COM.-NO.: LS-71366/07.04.1 ASPHALT MIXING PLANT
Schaltschrank:
SWITCH PANEL: 2400 x 1600 x 500mm Prime 140
Schaltplan-Nr.:
CIRCUIT DIAGRAM-NO.: G0 A 0091 04 Bereich: Porto Alegre
AREA:
Schutzart :
PROTECTION TYPE: RCD (FI)
Betriebsspannung:
Ammann do Brasil
OPERATING VOLTAGE: 3Ph~ / 400VAC / 60Hz Sitio do Sobrado
Steuerspannung:
CONTROL VOLTAGE: 24VDC / 230VAC 94180-452 Gravataí -RS-Brasil
Baujahr : Brasilien
YEAR OF MANUFACTURE: 2013
Prüfprotokoll EN 60204 (VDE 0113) TEST REPORT EN 60204 (VDE0113)
Prüfungsgrund: Erstprüfung Wiederholungsprüfung Sonstiges:
CAUSE OF INSPECTION: INITIAL INSPECTION REPEATED INSPECTION OTHER:
Netz:
TN-C TN-S TT IT-SYSTEM 230V 400V ........V In(Gesamt):
NET: 328 A
I (TOTAL):
Frequenz:
...... L N PEN PE
FREQUENCY .........Hz .........
Prüfung Dokumentation: vorhanden komplett Übereinstimmend mit der Installation
TEST DOCUMENTATION: EXISTING COMPLETE IN CONFORMITY TO THE INSTALLATION
Anmerkung:
NOTE:
Besichtigung:
SURVEY:
Betriebsmittel können den Einflüssen am Verwendungsort standhalten PE, L und N nicht verwechselt
OPERATING EQUIPMENT IS ABLE TO RESIST LOCAL INFLUENCES PE,L AND N ARE NOT CONFOUNDED
Alle Schutzleiter gegen Selbstlockern und Korrosion gesichert Schutz durch Isolierung aller aktiven Teile
ALL PROTECTIVE CONDUCTORS ARE PROTECTED AGAINST SELF-SLACKERING AND CORROSION PROTECTION BY ISOLATION OF ALL ACTIVE PARTS
Keine erkennbaren Schäden Sonstiges:
NO APPARENT DAMAGES OTHER:
Kennzeichnungen, Anschlussstellen und eventuelle Trennstellen in Ordnung
EQUIPMENT IDENTIFICATIONS, CONNECTION POINTS AND ANY DISCONNECTION POINTS ARE OKAY
Messung:
MEASUREMENT. Schlechtester Messwert Prüfung in Ordnung
WORST MEASURED VALUE TEST OKAY
Messgeräte entsprechen EN 61557 (VDE 0413)
MEASURING INSTRUMENTS AGREE WITH EN 61557 (VDE 0413)
Durchgängigkeit des Schutzleitersystems
(Widerstandsmessung mit Prüfstrom mind. 0,2A, max. 10A bzw. Schleifenimpedanzmessung)
CONDUCTIVITY OF THE PROTECTIVE CONDUCTOR SYSTEM
(RESISTANCE MEASUREMENT WITH TESTING CURRENT OF MIN.0,2A; MAX.10A; RESPECTIVELY LOOP IMPEDANCE MEASUREMENT)
Isolationswiderstandsmessung
INSULATION RESISTANCE MEASUREMENT
Spannungsprüfung
VOLTAGE TEST
Restspannngsprüfung (max. 60V nach 5s / 1s; sonst Warnhinweis anbringen)
RESIDUAL VOLTAGE TEST (MAX.60V AFTER 5s/1s, OTHERWISE WARNING INSTRUCTION HAS TO PUT UP)
Sonstiges:
OTHER:
Not-Aus Druckwächter, Endschalter, RCD(FI), Sicherheitstemperaturbegrenzer, etc.
Erprobung: EMERGENCY OFF MANOSTAT, LIMIT SWITCH, RCD(FI), SAFETY TEMPERATURE LIMITER, ETC.
TEST: Verriegelung Meldeleuchten, Anzeigen Funktionsprüfung Sonstiges:
LOCKING SIGNAL LAMPS, INDICATIONS FUNCTION TEST OTHER:
Bemerkungen:
REMARKS:
Prüfung nach EN60204 (VDE0113) durchgeführt Anlage / Installation funktionsfähig übernommen
TEST HAS BEEN DONE ACCORDING TO STANDARD EN 60204 (VDE 0113) THE PLANT / INSTALLATION HAS BEEN TAKEN OVER IN WORKING CONDITIONS
Ort / Datum: LOCATION / DATE: Unterschrift des Prüfers SIGNATURE OF RESPONSIBLE CONTROLLER Datum: DATE: Unterschrift des Auftraggebers SIGNATURE OF RESPONSIBLE CUSTOMER
Hinweise zum Ausfüllen: positive Prüfung negative Prüfung Bitte Nicht-Zutreffendes durchstreichen
-

+
INDICATION NOTE TO FILL OUT POSITIVE INSPECTION NEGATIVE INSPECTION PLEASE CROSS-OUT WHAT IS NOT APPLICABLE
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

230VAC (P)
=D0/42.10 / 3L1 3L1 / 21.1
230VAC (N)
=D0/42.10 / 3L2 3L2 / 21.1
+24VDC
=D0/42.10 / 3L+ 3L+ / 21.1
0VDC
=D0/42.10 / 3L- 3L- / 21.1

PE PE PE PE PE
-X2 21 21 22 22 22 20 20 -X3 21 21 21 22 22 22 20 20 20

+230VAC 0VAC +24VDC 0VDC

=D0+PR/2 21
DATE 2013-02-22 COMMISSION : LS-71366/07.04.1 Ammann Asphalt FEED CONTROL G0 A 0091 04 60201857290 = T0
proc. PBR
CLIENT : Ammann do Brasil VOLTAGE SWITCH PANEL G0 +
Appr
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 13
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

230VAC (P)
13.10 / 3L1 3L1 / 26.1
230VAC (N)
13.10 / 3L2 3L2 / 26.1
+24VDC
13.10 / 3L+ 3L+ / 26.1
0VDC
13.10 / 3L- 3L- / 26.1

11
-10K11 =G0-D1A32
/21.8 14
OUTPUT

1.3

PE
-X2 23 22 20

A1
-10K11
38.51 A2
24VDC

BN BU GNYE 230VAC (N)


HORN DRYER
H07RN-F 3x1,5 mm² 17 m
-W210.1

0VDC

START-UP WARNING
DRYER

A1
PE
-10H1
A2

11 14 /21.2

HORN
DRYER

13 26
DATE 2013-01-22 COMMISSION : LS-71366/07.04.1 Ammann Asphalt START-UP WARNING G0 A 0091 04 60201857290 = T0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 +
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 21
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

230VAC (P)
21.10 / 3L1 3L1 / 27.1
230VAC (N)
21.10 / 3L2 3L2 / 27.1
+24VDC
21.10 / 3L+ 3L+ / 27.1
0VDC
21.10 / 3L- 3L- / 27.1

2L1
400V +/-5% 3Ph 50Hz 2L1
2L2 2L2
2L3 2L3

1 3 5 1 3 5 1 3 5 1 3 5
-25Q1 -25Q2 -25Q3 -25Q4
/27.3 /27.3 /27.3 /27.3
/28.3 I> I> I> /28.4 I> I> I> /28.4 I> I> I> /28.5 I> I> I>
19,2A ge 2 4 6 19,2A ge 2 4 6 19,2A ge 2 4 6 19,2A ge 2 4 6
CLASS 10 CLASS 10 CLASS 10 CLASS 10
PKE32/XTU-32 1 3 5 PKE32/XTU-32 1 3 5 PKE32/XTU-32 1 3 5 PKE32/XTU-32 1 3 5
-25K1 -25K2 -25K3 -25K4
/27.3 2 4 6 /27.4 2 4 6 /27.5 2 4 6 /27.6 2 4 6

MOTOR 1 MOTOR 2

4 mm² 4 mm² 4 mm² 4 mm²

PE PE PE PE MOTOR 3 MOTOR 4
-X1 25 26 27 28 -X1 29 30 31 32 -X1 33 34 35 36 -X1 37 38 39 40

BN BK GY GNYE BN BK GY GNYE BN BK GY GNYE BN BK GY GNYE


DRUM MOTOR 1
H07RN-F 4x4 mm² 19 m
-W125.1

DRUM MOTOR 2
H07RN-F 4x4 mm² 19 m
-W125.2

DRUM MOTOR 3
H07RN-F 4x4 mm² 17 m
-W125.3

DRUM MOTOR 4
H07RN-F 4x4 mm² 17 m
-W125.4
V1 U1 W1 V1 U1 W1 U1 V1 W1 U1 V1 W1

-25M1
M -25M2
M -25M3
M -25M4
M
9,5 KW 3~ 9,5 KW 3~ 9,5 KW 3~ 9,5 KW 3~
19,2A PE 19,2A PE 19,2A PE 19,2A PE

DRUM MOTOR DRUM MOTOR DRUM MOTOR DRUM MOTOR


21 1 2 3 4 27
DATE 2013-04-29 COMMISSION : LS-71366/07.04.1 Ammann Asphalt 02.001 G0 A 0091 04 60201857290 = T0
proc. UGR
CLIENT : Ammann do Brasil DRUM 9,5 SWITCH PANEL G0 +
Appr
ASPHALT MIXING PLANT D-31061 Alfeld KW 19,2A CAD: 71366_G0
MODIFICATIONDATE NAME origin \\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 26
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

230VAC (P)
26.10 / 3L1 3L1 / 28.1
+24VDC
26.10 / 3L+ 3L+ / 28.1

=G0-D1A32
1.13
OUTPUT -25Q1
/26.1 1.14
3.1
1.13
-25Q2
/26.3 1.14

1.13
-25Q3
/26.5 1.14

1.13
-25Q4
/26.7 1.14

11 21 31 41
-25K11 -25K11 -25K11 -25K11
/27.2 14 /27.2 24 /27.2 34 /27.2 44

A1 A1 A1 A1 A1
-25K11 -25K1 -25K2 -25K3 -25K4
55.34 A2 PKE32 A2 PKE32 A2 PKE32 A2 PKE32 A2
24VDC 230VAC 230VAC 230VAC 230VAC

230VAC (N)
26.10 / 3L2 3L2 / 28.1
0VDC
26.10 / 3L- 3L- / 28.1

DRUM DRUM
ON ON
11 14 /27.3 1 2 /26.1 1 2 /26.3 1 2 /26.5 1 2 /26.7
21 24 /27.4 3 4 /26.2 3 4 /26.4 3 4 /26.6 3 4 /26.7
31 34 /27.5 5 6 /26.2 5 6 /26.4 5 6 /26.6 5 6 /26.8
41 44 /27.6 13 14 /28.7 13 14 =T2/42.2 13 14 /28.2 13 14 /28.2
43 44 /28.2 43 44 /28.2

26 28
DATE 2013-02-04 COMMISSION : LS-71366/07.04.1 Ammann Asphalt 02.001 G0 A 0091 04 60201857290 = T0
proc. UGR
CLIENT : Ammann do Brasil DRUM SWITCH PANEL G0 +
Appr
ASPHALT MIXING PLANT D-31061 Alfeld CONTROL PART CAD: 71366_G0
MODIFICATIONDATE NAME origin \\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 27
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

230VAC (P)
27.10 / 3L1 3L1 / 33.1
230VAC (N)
27.10 / 3L2 3L2 / 33.1
+24VDC
27.10 / 3L+ 3L+ / 33.1
0VDC
27.10 / 3L- 3L- / 33.1
43 1.21 1.21 1.21 1.21 13
-25K1 -25Q1 -25Q2 -25Q3 -25Q4 -25K1
/27.3 44 /26.1 1.22 /26.3 1.22 /26.5 1.22 /26.7 1.22 /27.3 14

43
-25K2
/27.4 44

13
-25K3
/27.5 14

13
-25K4
/27.6 14

3.1 3.2
INPUT INPUT PE

=G0-D1E32 -X3 23 22 20

DRUM ERROR
ON

27 32
DATE 2013-02-04 COMMISSION : LS-71366/07.04.1 Ammann Asphalt 02.001 G0 A 0091 04 60201857290 = T0
proc. UGR
CLIENT : Ammann do Brasil DRUM SWITCH PANEL G0 +
Appr
ASPHALT MIXING PLANT D-31061 Alfeld CONTROL PART CAD: 71366_G0
MODIFICATIONDATE NAME origin \\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 28
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

2L1
400V +/-5% 3Ph 50Hz 2L1
2L2 2L2
2L3 2L3

1 3 5 1 3 5
-29Q1 -29Q2
/33.1 /33.2
/33.8 I> I> I> /33.9 I> I> I>
8,4A ge 2 4 6 8,4A ge 2 4 6
CLASS 10 CLASS 10
PKE12/XTU-12 PKE12/XTU-12

1 3 5 1 3 5
-29K1 -29K2
/33.1 2 4 6 /33.2 2 4 6

2,5 mm²

PE
-X1 41 42 43 44

-W129
BN BK GY GNYE
H07RN-F 4x1,5 mm² 10 m
V1 U1 W1 FEEDING BELT

-29M1
M
4 KW 3~
8,4A PE

FEEDING BELT
28 33
DATE 2013-04-29 COMMISSION : LS-71366/07.04.1 Ammann Asphalt 01.003 G0 A 0091 04 60201857290 = T0
proc. UGR
CLIENT : Ammann do Brasil FEEDING BELT SWITCH PANEL G0 +
Appr
ASPHALT MIXING PLANT D-31061 Alfeld 4,0 KW 8,4A CAD: 71366_G0
MODIFICATIONDATE NAME origin \\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 32
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

230VAC (P)
28.10 / 3L1 3L1 / 47.1
+24VDC
28.10 / 3L+ 3L+ / 47.1

13 13 1.21 1.21
-29K1 -29K2 -29Q1 -29Q2
/33.1 14 /33.2 14 /32.1 1.22 /32.3 1.22

=G0-D1A32

OUTPUT OUTPUT
4.1 4.2 3.4
4.1 4.2
INPUT INPUT INPUT
11 11 =G0-D1E32
-29K11 -29K12
/33.5 14 /33.6 14

1.13 1.13
-29Q1 -29Q2
/32.1 1.14 /32.3 1.14

21 21
-29K2 -29K1
/33.2 22 /33.1 22

A1 A1 A1 A1
-29K1 -29K2 -29K11 -29K12
PKE12 A2 PKE12 A2 38.51 A2 38.51 A2
230VAC 230VAC 24VDC 24VDC

230VAC (N)
28.10 / 3L2 3L2 / 47.4
0VDC
28.10 / 3L- 3L- / 47.4

FEEDING BELT 1 FEEDING BELT 1 FEEDING BELT 1


FORWARD BACKWARDS FORWARD BACKWARDS FORWARD ERROR
BACKWARDS
1 2 /32.1 1 2 /32.3 11 14 /33.1 11 14 /33.2
3 4 /32.2 3 4 /32.3
5 6 /32.2 5 6 /32.3
13 14 /33.7 13 14 /33.7
21 22 /33.2 21 22 /33.1
43 44 =T2/42.2

32 47
DATE 2012-12-07 COMMISSION : LS-71366/07.04.1 Ammann Asphalt 01.003 G0 A 0091 04 60201857290 = T0
proc. UGR
CLIENT : Ammann do Brasil FEEDING BELT 1 SWITCH PANEL G0 +
Appr
ASPHALT MIXING PLANT D-31061 Alfeld CONTROL PART CAD: 71366_G0
MODIFICATIONDATE NAME origin \\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 33
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

230VAC (P)
33.10 / 3L1 3L1 / 48.1
+24VDC
33.10 / 3L+ 3L+ / 48.1

2L1
400V +/-5% 3Ph 50Hz 2L1
2L2 2L2
2L3 2L3
13 1.21
1 3 5 -47K1 -47Q1
-47Q1 /47.5 14 /47.1 1.22
/47.5
/47.8 I> I> I>
8,4A ge 2 4 6
CLASS 10
PKE12/XTU-12 1 3 5
-47K1
/47.5 2 4 6

=G0-D1A32

OUTPUT
7.3 7.4
7.3
INPUT INPUT

=G0-D1E32

11

2,5 mm²
-47K11
/47.6 14

1.13
PE
-47Q1
-X1 45 46 47 48 /47.1 1.14

A1 A1
-47K1 -47K11
PKE12 A2 38.51 A2
230VAC 24VDC

230VAC (N)
33.10 / 3L2 3L2 / 48.4
0VDC
33.10 / 3L- 3L- / 48.4

COARSE DUST SCREW 1 COARSE DUST SCREW 1 COARSE DUST SCREW 1


-W147 ON ON ON ERROR
BN BK GY GNYE
H07RN-F 4x1,5 mm² 25 m
V1 U1 W1 COARSE DUST SCREW 1 1 2 /47.1 11 14 /47.5

-47M1
M 3 4 /47.2
3~ 5 6 /47.2
4 KW 13 14 /47.7
8,4A PE

COARSE DUST SCREW 1


33 48
DATE 2013-04-29 COMMISSION : LS-71366/07.04.1 Ammann Asphalt 05.007 G0 A 0091 04 60201857290 = T0
proc. UGR
CLIENT : Ammann do Brasil COARSE DUST SCREW 1 SWITCH PANEL G0 +
Appr
ASPHALT MIXING PLANT D-31061 Alfeld 4,0 KW 8,4A CAD: 71366_G0
MODIFICATIONDATE NAME origin \\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 47
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

230VAC (P)
47.10 / 3L1 3L1 / =T2/13.1
+24VDC
47.10 / 3L+ 3L+ / =T2/13.1

2L1
400V +/-5% 3Ph 50Hz 2L1
2L2 2L2
2L3 2L3
13 1.21
1 3 5 -48K1 -48Q1
-48Q1 /48.5 14 /48.1 1.22
/48.5
/48.8 I> I> I>
8,4A ge 2 4 6
CLASS 10
PKE12/XTU-12 1 3 5
-48K1
/48.5 2 4 6

=G0-D1A32

OUTPUT
8.1 8.2
8.1
INPUT INPUT

=G0-D1E32

11

2,5 mm²
-48K11
/48.6 14

1.13
PE
-48Q1
-X1 49 50 51 52 /48.1 1.14

A1 A1
-48K1 -48K11
PKE12 A2 38.51 A2
230VAC 24VDC

230VAC (N)
47.10 / 3L2 3L2 / =T2/13.1
0VDC
47.10 / 3L- 3L- / =T2/13.1

COARSE DUST SCREW 2 COARSE DUST SCREW 2 COARSE DUST SCREW 2


-W148 ON ON ON ERROR
BN BK GY GNYE
H07RN-F 4x1,5 mm² 24 m
U1 V1 W1 COARSE DUST SCREW 2 1 2 /48.1 11 14 /48.5

-48M1
M 3 4 /48.2
3~ 5 6 /48.2
4 KW 13 14 /48.7
8,4A PE

COARSE DUST SCREW 2


47 +KLE/1
DATE 2013-02-04 COMMISSION : LS-71366/07.04.1 Ammann Asphalt 05.007 G0 A 0091 04 60201857290 = T0
proc. UGR
CLIENT : Ammann do Brasil COARSE DUST SCREW 2 SWITCH PANEL G0 +
Appr
ASPHALT MIXING PLANT D-31061 Alfeld 4,0 KW 8,4A CAD: 71366_G0
MODIFICATIONDATE NAME origin \\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 48
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

TERMINAL STRIP OVERVIEW AAD_F14_002

TERMINALS
TERMINAL BLOCK FUNCTION TEXT PAGE TERMINAL DIAGRAM
FIRST LATEST SUM PE SUM N TOTAL NUMBER
-X1 CONSUMER 400VAC 25 52 7 0 28 =T0+KLE/11
-X2 CONTROL TERMINAL 230VAC 20 23 3 0 10 =T0+KLE/12
-X3 CONTROL TERMINAL 24VDC 20 23 4 0 12 =T0+KLE/13

+/48 11
DATE 2013-05-30 COMMISSION : LS-71366/07.04.1 Ammann Asphalt TERMINAL STRIP REVIEW G0 A 0091 04 60201857290 = T0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KLE
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 1
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

TERMINAL DIAGRAM AAD_F13_001

CABLE NAME

CABLE NAME
-W148
-W147
-W129
-W125.4
-W125.3
-W125.2
-W125.1
STRIP
=T0+-X1
CONSUMER 400VAC

H07RN-F 4x1,5 mm²

H07RN-F 4x1,5 mm²

H07RN-F 4x1,5 mm²

H07RN-F 4x4 mm²

H07RN-F 4x4 mm²

H07RN-F 4x4 mm²

H07RN-F 4x4 mm²

CABLE TYPE

CABLE TYPE
CONNECTION

CONNECTION
TERMINAL
FUNCTION TEXT DESTINATION DESCRIPTION DESTINATION DESCRIPTION PAGE / COLUMN

DRUM MOTOR 1 BN -25M1 V1 25 -25K1 2 /26.1


= BK -25M1 U1 26 -25K1 4 /26.2
= GY -25M1 W1 27 -25K1 6 /26.2
= GNYE -25M1 PE 28 /26.2
DRUM MOTOR 2 BN -25M2 V1 29 -25K2 2 /26.3
= BK -25M2 U1 30 -25K2 4 /26.4
= GY -25M2 W1 31 -25K2 6 /26.4
= GNYE -25M2 PE 32 /26.4
DRUM MOTOR 3 BN -25M3 U1 33 -25K3 2 /26.5
= BK -25M3 V1 34 -25K3 4 /26.6
= GY -25M3 W1 35 -25K3 6 /26.6
= GNYE -25M3 PE 36 /26.6
DRUM MOTOR 4 BN -25M4 U1 37 -25K4 2 /26.7
= BK -25M4 V1 38 -25K4 4 /26.7
= GY -25M4 W1 39 -25K4 6 /26.8
= GNYE -25M4 PE 40 /26.8
FEEDING BELT BN -29M1 V1 41 -29K1 2 /32.1
= BK -29M1 U1 42 -29K1 4 /32.2
= GY -29M1 W1 43 -29K1 6 /32.2
= GNYE -29M1 PE 44 /32.2
COARSE DUST SCREW 1 BN -47M1 V1 45 -47K1 2 /47.1
= BK -47M1 U1 46 -47K1 4 /47.2
= GY -47M1 W1 47 -47K1 6 /47.2
= GNYE -47M1 PE 48 /47.2
COARSE DUST SCREW 2 BN -48M1 U1 49 -48K1 2 /48.1
= BK -48M1 V1 50 -48K1 4 /48.2
= GY -48M1 W1 51 -48K1 6 /48.2
= GNYE -48M1 PE 52 /48.2

1 12
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt TERMINAL DIAGRAM =T0+-X1 G0 A 0091 04 60201857290 = T0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KLE
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 11
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

TERMINAL DIAGRAM AAD_F13_001

CABLE NAME

CABLE NAME
-W210.1
STRIP
=T0+-X2
CONTROL TERMINAL 230VAC

H07RN-F 3x1,5 mm²

CABLE TYPE

CABLE TYPE
CONNECTION

CONNECTION
TERMINAL
FUNCTION TEXT DESTINATION DESCRIPTION DESTINATION DESCRIPTION PAGE / COLUMN

0VAC 20 /13.3
= 20 /13.4
HORN DRYER GNYE -10H1 PE 20 /21.3
+230VAC 21 =D0-24K11 11 /13.3
-10K11 11
+230VAC 21 /13.3
= 22 =D0-24K1 A2 /13.3
-X2 22
+230VAC 22 /13.3
0VAC 22 /13.3
HORN DRYER BU -10H1 A2 22 -25K1 A2 /21.2
-X2 22
HORN DRYER BN -10H1 A1 23 -10K11 14 /21.2

11 13
DATE 2013-05-30 COMMISSION : LS-71366/07.04.1 Ammann Asphalt TERMINAL DIAGRAM =T0+-X2 G0 A 0091 04 60201857290 = T0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KLE
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 12
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

TERMINAL DIAGRAM AAD_F13_001

CABLE NAME

CABLE NAME
STRIP
=T0+-X3
CONTROL TERMINAL 24VDC

CABLE TYPE

CABLE TYPE
CONNECTION

CONNECTION
TERMINAL
FUNCTION TEXT DESTINATION DESCRIPTION DESTINATION DESCRIPTION PAGE / COLUMN

0VDC 20 /13.10
= 20 /13.10
= 20 /13.10
ERROR 20 /28.7
+24VDC 21 =D0-24Q1 1.21 /13.8
-25K1 43
+24VDC 21 /13.8
= 21 /13.9
0VDC 22 =D0-24K11 A2 /13.9
-10K11 A2
0VDC 22 /13.9
= 22 /13.9
ERROR 22 -25K11 A2 /28.7
-29K11 A2
ERROR 23 -25K1 14 /28.7

12 +KAB/1
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt TERMINAL DIAGRAM =T0+-X3 G0 A 0091 04 60201857290 = T0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KLE
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 13
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

CABLE PLAN
1. PAGE PAGE
CABLE TYPE ID CORES CROSS SECTION LENGTH FUNCTION TEXT CIRCUIT DIAGRAM CABLE DIAGRAM

H07RN-F -W125.1 4 4 19 m DRUM MOTOR 1 +/26.1 =T0+KAB/11

-W125.2 4 4 19 m DRUM MOTOR 2 +/26.3 =T0+KAB/12

-W125.3 4 4 17 m DRUM MOTOR 3 +/26.5 =T0+KAB/13

-W125.4 4 4 17 m DRUM MOTOR 4 +/26.7 =T0+KAB/14

-W129 4 1,5 10 m FEEDING BELT +/32.1 =T0+KAB/15

-W147 4 1,5 25 m COARSE DUST SCREW 1 +/47.1 =T0+KAB/16

-W148 4 1,5 24 m COARSE DUST SCREW 2 +/48.1 =T0+KAB/17

-W210.1 3 1,5 17 m HORN DRYER +/21.3 =T0+KAB/18

+KLE/13 11
DATE 2013-05-30 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CABLE PLAN G0 A 0091 04 60201857290 = T0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KAB
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 1
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

CABLE DIAGRAM AAD_F09_002

CABLE NAME =T0+-W125.1 CABLE TYPE H07RN-F


FUNCTION TEXT DRUM MOTOR 1 CORE NO. 4 CROSS SECTION 4 mm² CABLE LENGTH 19 m
DESTINATION DESTINATION
FUNCTION TEXT PAGE / COLUMN CONNECTION CORE CONNECTION PAGE / COLUMN FUNCTION TEXT
DESCRIPTION FROM DESCRIPTION TO

DRUM MOTOR 1 /26.1 -X1 25 BN -25M1 V1 /26.1 DRUM MOTOR 1

= /26.2 -X1 26 BK -25M1 U1 /26.1 =

= /26.2 -X1 27 GY -25M1 W1 /26.1 =

= /26.2 -X1 28 GNYE -25M1 PE /26.1 =

1 12
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CABLE DIAGRAM =T0+-W125.1 G0 A 0091 04 60201857290 = T0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KAB
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 11
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

CABLE DIAGRAM AAD_F09_002

CABLE NAME =T0+-W125.2 CABLE TYPE H07RN-F


FUNCTION TEXT DRUM MOTOR 2 CORE NO. 4 CROSS SECTION 4 mm² CABLE LENGTH 19 m
DESTINATION DESTINATION
FUNCTION TEXT PAGE / COLUMN CONNECTION CORE CONNECTION PAGE / COLUMN FUNCTION TEXT
DESCRIPTION FROM DESCRIPTION TO

DRUM MOTOR 2 /26.3 -X1 29 BN -25M2 V1 /26.3 DRUM MOTOR 2

= /26.4 -X1 30 BK -25M2 U1 /26.3 =

= /26.4 -X1 31 GY -25M2 W1 /26.3 =

= /26.4 -X1 32 GNYE -25M2 PE /26.3 =

11 13
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CABLE DIAGRAM =T0+-W125.2 G0 A 0091 04 60201857290 = T0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KAB
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 12
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

CABLE DIAGRAM AAD_F09_002

CABLE NAME =T0+-W125.3 CABLE TYPE H07RN-F


FUNCTION TEXT DRUM MOTOR 3 CORE NO. 4 CROSS SECTION 4 mm² CABLE LENGTH 17 m
DESTINATION DESTINATION
FUNCTION TEXT PAGE / COLUMN CONNECTION CORE CONNECTION PAGE / COLUMN FUNCTION TEXT
DESCRIPTION FROM DESCRIPTION TO

DRUM MOTOR 3 /26.5 -X1 33 BN -25M3 U1 /26.5 DRUM MOTOR 3

= /26.6 -X1 34 BK -25M3 V1 /26.5 =

= /26.6 -X1 35 GY -25M3 W1 /26.5 =

= /26.6 -X1 36 GNYE -25M3 PE /26.5 =

12 14
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CABLE DIAGRAM =T0+-W125.3 G0 A 0091 04 60201857290 = T0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KAB
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 13
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

CABLE DIAGRAM AAD_F09_002

CABLE NAME =T0+-W125.4 CABLE TYPE H07RN-F


FUNCTION TEXT DRUM MOTOR 4 CORE NO. 4 CROSS SECTION 4 mm² CABLE LENGTH 17 m
DESTINATION DESTINATION
FUNCTION TEXT PAGE / COLUMN CONNECTION CORE CONNECTION PAGE / COLUMN FUNCTION TEXT
DESCRIPTION FROM DESCRIPTION TO

DRUM MOTOR 4 /26.7 -X1 37 BN -25M4 U1 /26.7 DRUM MOTOR 4

= /26.7 -X1 38 BK -25M4 V1 /26.7 =

= /26.8 -X1 39 GY -25M4 W1 /26.7 =

= /26.8 -X1 40 GNYE -25M4 PE /26.7 =

13 15
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CABLE DIAGRAM =T0+-W125.4 G0 A 0091 04 60201857290 = T0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KAB
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 14
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

CABLE DIAGRAM AAD_F09_002

CABLE NAME =T0+-W129 CABLE TYPE H07RN-F


FUNCTION TEXT FEEDING BELT CORE NO. 4 CROSS SECTION 1,5 mm² CABLE LENGTH 10 m
DESTINATION DESTINATION
FUNCTION TEXT PAGE / COLUMN CONNECTION CORE CONNECTION PAGE / COLUMN FUNCTION TEXT
DESCRIPTION FROM DESCRIPTION TO

FEEDING BELT /32.1 -X1 41 BN -29M1 V1 /32.1 FEEDING BELT

= /32.2 -X1 42 BK -29M1 U1 /32.1 =

= /32.2 -X1 43 GY -29M1 W1 /32.1 =

= /32.2 -X1 44 GNYE -29M1 PE /32.1 =

14 16
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CABLE DIAGRAM =T0+-W129 G0 A 0091 04 60201857290 = T0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KAB
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 15
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

CABLE DIAGRAM AAD_F09_002

CABLE NAME =T0+-W147 CABLE TYPE H07RN-F


FUNCTION TEXT COARSE DUST SCREW 1 CORE NO. 4 CROSS SECTION 1,5 mm² CABLE LENGTH 25 m
DESTINATION DESTINATION
FUNCTION TEXT PAGE / COLUMN CONNECTION CORE CONNECTION PAGE / COLUMN FUNCTION TEXT
DESCRIPTION FROM DESCRIPTION TO

PE

COARSE DUST SCREW 1 /47.2 -X1 46 BK -47M1 U1 /47.1 COARSE DUST SCREW 1

= /47.1 -X1 45 BN -47M1 V1 /47.1 =

= /47.2 -X1 48 GNYE -47M1 PE /47.1 =

= /47.2 -X1 47 GY -47M1 W1 /47.1 =

15 17
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CABLE DIAGRAM =T0+-W147 G0 A 0091 04 60201857290 = T0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KAB
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 16
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

CABLE DIAGRAM AAD_F09_002

CABLE NAME =T0+-W148 CABLE TYPE H07RN-F


FUNCTION TEXT COARSE DUST SCREW 2 CORE NO. 4 CROSS SECTION 1,5 mm² CABLE LENGTH 24 m
DESTINATION DESTINATION
FUNCTION TEXT PAGE / COLUMN CONNECTION CORE CONNECTION PAGE / COLUMN FUNCTION TEXT
DESCRIPTION FROM DESCRIPTION TO

PE

COARSE DUST SCREW 2 /48.2 -X1 50 BK -48M1 V1 /48.1 COARSE DUST SCREW 2

= /48.1 -X1 49 BN -48M1 U1 /48.1 =

= /48.2 -X1 52 GNYE -48M1 PE /48.1 =

= /48.2 -X1 51 GY -48M1 W1 /48.1 =

16 18
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CABLE DIAGRAM =T0+-W148 G0 A 0091 04 60201857290 = T0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KAB
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 17
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

CABLE DIAGRAM AAD_F09_002

CABLE NAME =T0+-W210.1 CABLE TYPE H07RN-F


FUNCTION TEXT HORN DRYER CORE NO. 3 CROSS SECTION 1,5 mm² CABLE LENGTH 17 m
DESTINATION DESTINATION
FUNCTION TEXT PAGE / COLUMN CONNECTION CORE CONNECTION PAGE / COLUMN FUNCTION TEXT
DESCRIPTION FROM DESCRIPTION TO

HORN DRYER /21.2 -X2 23 BN -10H1 A1 /21.2 HORN DRYER

= /21.2 -X2 22 BU -10H1 A2 /21.2 =

= /21.3 -X2 20 GNYE -10H1 PE /21.3

17 +PR/1
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CABLE DIAGRAM =T0+-W210.1 G0 A 0091 04 60201857290 = T0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KAB
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 18
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

AAD_Pruef2
CIRCUIT OVERVIEW R iso PROTECTIVE CONDUCTOR Z Schl [Ω] RCD(FI)

CIRCUIT (FUNCTION TEXT) CABLE NAME CABLE TYPE LENGTH


[MΩ] IPE [mA] R PE [Ω] I K [A] I N [A] IΔN [mA] UB [V] + /-
DRUM MOTOR 1 -W125.1 H07RN-F 4x4 mm² 19 m

DRUM MOTOR 2 -W125.2 H07RN-F 4x4 mm² 19 m

DRUM MOTOR 3 -W125.3 H07RN-F 4x4 mm² 17 m

DRUM MOTOR 4 -W125.4 H07RN-F 4x4 mm² 17 m

FEEDING BELT -W129 H07RN-F 4x1,5 mm² 10 m

COARSE DUST SCREW 1 -W147 H07RN-F 4x1,5 mm² 25 m

COARSE DUST SCREW 2 -W148 H07RN-F 4x1,5 mm² 24 m

HORN DRYER -W210.1 H07RN-F 3x1,5 mm² 17 m

+KAB/18 2
DATE 2013-05-30 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CIRCUIT OVERVIEW G0 A 0091 04 60201857290 = T0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + PR
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 1
Kunde:
CLIENT.
Kom-Nr.:
COM.-NO.: LS-71366/07.04.1 ASPHALT MIXING PLANT
Schaltschrank:
SWITCH PANEL: 2400 x 1600 x 500mm Prime 140
Schaltplan-Nr.:
CIRCUIT DIAGRAM-NO.: G0 A 0091 04 Bereich: Porto Alegre
AREA:
Schutzart :
PROTECTION TYPE: RCD (FI)
Betriebsspannung:
Ammann do Brasil
OPERATING VOLTAGE: 3Ph~ / 400VAC / 60Hz Sitio do Sobrado
Steuerspannung:
CONTROL VOLTAGE: 24VDC / 230VAC 94180-452 Gravataí -RS-Brasil
Baujahr : Brasilien
YEAR OF MANUFACTURE: 2013
Prüfprotokoll EN 60204 (VDE 0113) TEST REPORT EN 60204 (VDE0113)
Prüfungsgrund: Erstprüfung Wiederholungsprüfung Sonstiges:
CAUSE OF INSPECTION: INITIAL INSPECTION REPEATED INSPECTION OTHER:
Netz:
TN-C TN-S TT IT-SYSTEM 230V 400V ........V In(Gesamt):
NET: 328 A
I (TOTAL):
Frequenz:
...... L N PEN PE
FREQUENCY .........Hz .........
Prüfung Dokumentation: vorhanden komplett Übereinstimmend mit der Installation
TEST DOCUMENTATION: EXISTING COMPLETE IN CONFORMITY TO THE INSTALLATION
Anmerkung:
NOTE:
Besichtigung:
SURVEY:
Betriebsmittel können den Einflüssen am Verwendungsort standhalten PE, L und N nicht verwechselt
OPERATING EQUIPMENT IS ABLE TO RESIST LOCAL INFLUENCES PE,L AND N ARE NOT CONFOUNDED
Alle Schutzleiter gegen Selbstlockern und Korrosion gesichert Schutz durch Isolierung aller aktiven Teile
ALL PROTECTIVE CONDUCTORS ARE PROTECTED AGAINST SELF-SLACKERING AND CORROSION PROTECTION BY ISOLATION OF ALL ACTIVE PARTS
Keine erkennbaren Schäden Sonstiges:
NO APPARENT DAMAGES OTHER:
Kennzeichnungen, Anschlussstellen und eventuelle Trennstellen in Ordnung
EQUIPMENT IDENTIFICATIONS, CONNECTION POINTS AND ANY DISCONNECTION POINTS ARE OKAY
Messung:
MEASUREMENT. Schlechtester Messwert Prüfung in Ordnung
WORST MEASURED VALUE TEST OKAY
Messgeräte entsprechen EN 61557 (VDE 0413)
MEASURING INSTRUMENTS AGREE WITH EN 61557 (VDE 0413)
Durchgängigkeit des Schutzleitersystems
(Widerstandsmessung mit Prüfstrom mind. 0,2A, max. 10A bzw. Schleifenimpedanzmessung)
CONDUCTIVITY OF THE PROTECTIVE CONDUCTOR SYSTEM
(RESISTANCE MEASUREMENT WITH TESTING CURRENT OF MIN.0,2A; MAX.10A; RESPECTIVELY LOOP IMPEDANCE MEASUREMENT)
Isolationswiderstandsmessung
INSULATION RESISTANCE MEASUREMENT
Spannungsprüfung
VOLTAGE TEST
Restspannngsprüfung (max. 60V nach 5s / 1s; sonst Warnhinweis anbringen)
RESIDUAL VOLTAGE TEST (MAX.60V AFTER 5s/1s, OTHERWISE WARNING INSTRUCTION HAS TO PUT UP)
Sonstiges:
OTHER:
Not-Aus Druckwächter, Endschalter, RCD(FI), Sicherheitstemperaturbegrenzer, etc.
Erprobung: EMERGENCY OFF MANOSTAT, LIMIT SWITCH, RCD(FI), SAFETY TEMPERATURE LIMITER, ETC.
TEST: Verriegelung Meldeleuchten, Anzeigen Funktionsprüfung Sonstiges:
LOCKING SIGNAL LAMPS, INDICATIONS FUNCTION TEST OTHER:
Bemerkungen:
REMARKS:
Prüfung nach EN60204 (VDE0113) durchgeführt Anlage / Installation funktionsfähig übernommen
TEST HAS BEEN DONE ACCORDING TO STANDARD EN 60204 (VDE 0113) THE PLANT / INSTALLATION HAS BEEN TAKEN OVER IN WORKING CONDITIONS
Ort / Datum: LOCATION / DATE: Unterschrift des Prüfers SIGNATURE OF RESPONSIBLE CONTROLLER Datum: DATE: Unterschrift des Auftraggebers SIGNATURE OF RESPONSIBLE CUSTOMER
Hinweise zum Ausfüllen: positive Prüfung negative Prüfung Bitte Nicht-Zutreffendes durchstreichen
-

+
INDICATION NOTE TO FILL OUT POSITIVE INSPECTION NEGATIVE INSPECTION PLEASE CROSS-OUT WHAT IS NOT APPLICABLE
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

PE rail
sidewise at case

Kanal 1 auf Hauptgas 1 PE

=G0-BK2
34 68 1 /41.3 PE

-41A1
Kanal 1 zu 33 Hauptgas 2 67 0V 2 /41.3 0VDC

Kanal 2 auf 32 /56.3 AIR FLAP OPEN Öl 66 /48.5 NOZZLE SEAL VALVE +24V 3 /41.2 +24VDC

Kanal 2 zu 31 /56.3 AIR FLAP LOCK Zündventile 65 /51.2 IGNITION VALVES Schirm 4 /41.3 Lamtec System Bus (S)

Kanal 3 auf 30 /57.3 OIL CONTROL VALVE OPEN Zündtrafo 64 /51.4 IGNITION TRANSFORMER CAN-H 1 5 /41.3 Lamtec System Bus (H)

Interbus-S Anbindung
Kanal 3 zu 29 /57.3 OIL CONTROL VALVE LOCK Lüfter 63 /42.6 BURNER VENTILATOR START CAN-L 1 6 /41.3 Lamtec System Bus (L)

Kanal 4 auf 28 Ölpumpe ein 62 /48.3 OIL VALVES Schirm 7

Kanal 4 zu 27 Störung VR 61 CAN-H 2 8

115V/230V 115V/230V Einspeisung


Phase 50/60Hz
26 /41.5 13L1 (L1) für Klemme 61 bis 68
60 /41.8 3L1 --> OUTPUTS CAN-L 2 9

Null-Leiter 25 /41.5 13L2 (N) CAN-GND 10 /41.4 Lamtec System Bus (G)

Erdung PE /41.5 PE 11
nicht belegt 59
für dig.
+24VDC Eingänge 24 /42.2 24V INTERNAL --> X8 Brenner ein 58

24VDC 23 Störungsentriegelung 57

GND 22 /42.2 GND --> X8 Reglerfreigabe 56 /52.6 CONTROL RELEASE

Etamatic S
21 /41.7 SWITCH OFF INTERNAL REGULATOR Gassicherheitskette 55
Leistungsregler
Istwert 20 /41.7 - Rezi ein 54 /52.6 ---
PT100
19 /41.7 SWITCH OFF INTERNAL REGULATOR Flammsignal 53 /52.6 FLAME SIGNAL EXTERNAL
- 18 Kesselsicherheitskette 52 /42.4 PLANT SAFETIES
Kanal 4
Rückführung 17 Ölsicherheitskette 51 /48.2 OIL SAFETY CHAIN
+ 16 Sollwertumschaltung 50
- 15 /57.5 OIL CONTROL VALVE POTI IN SERVOMECHANISM Brennstoffauswahl 49 /46.3 SELECT HEAVY FUEL
Kanal 3
Rückführung 14 /57.5 OIL CONTROL VALVE POTI IN SERVOMECHANISM Luftdruckwächter 48 /43.4 AIR PRESSURE DETECTOR
+ 13 /57.5 OIL CONTROL VALVE POTI IN SERVOMECHANISM Gasdruck >min 47
Dichtheitsprüfung
- 12 /56.5 AIR FLAP POTI IN SERVOMECHANISM Zündstellungsquittierung 46 /51.8 QUIT IGNITION POSITION
Kanal 2
11 /56.5 AIR FLAP POTI IN SERVOMECHANISM Kanal 1 + 45
Rückführung
Rückführung 4-20mA
+ 10 /56.5 AIR FLAP POTI IN SERVOMECHANISM stetiger Ausgang - 44 /52.4 FLAME SENSOR FFS 06 (BU)
- 9 Drehzahlsensor 43
Kanal 1 (Option)
Rückführung 8 42
+ 7 41
Außentemperatur
+ 6 /41.7 - 40
(Option)
Lastvorgabe 5 /41.7 - 39
Poti / DPS / 0/4-20mA
- 4 /41.6 - RD 38 /52.4 FLAME SENSOR FFS 06 (RD)

HAG 3 /41.6 - YE 37 /52.5 FLAME SENSOR FFS 06 (YE)


Flammendetektor
Kanal 1 + 2 WH 36 /52.5 FLAME SENSOR FFS 06 (WH)
stetiger Ausgang
4-20mA - 1 GN 35 /52.4 FLAME SENSOR FFS 06 (GN)

=T0+PR/2 13
DATE 2012-12-07 COMMISSION : LS-71366/07.04.1 Ammann Asphalt MODULAR G0 A 0091 04 60201857290 = T2
proc. UGR
CLIENT : Ammann do Brasil ETAMATIC S SWITCH PANEL G0 +
Appr
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 5
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

230VAC (P)
=T0/48.10 / 3L1 3L1 / 22.1
230VAC (N)
=T0/48.10 / 3L2 3L2 / 22.1
+24VDC
=T0/48.10 / 3L+ 3L+ / 22.1
0VDC
=T0/48.10 / 3L- 3L- / 22.1

PE PE PE PE PE
-X2 21 21 22 22 22 20 20 -X3 21 21 21 22 22 22 20 20 20

+24VDC 0VDC

5 21
DATE 2013-02-20 COMMISSION : LS-71366/07.04.1 Ammann Asphalt FEED CONTROL G0 A 0091 04 60201857290 = T2
proc. PBR
CLIENT : Ammann do Brasil VOLTAGE SWITCH PANEL G0 +
Appr
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 13
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

2L1
400V +/-5% 3Ph 50Hz 2L1
2L2 2L2
2L3 2L3

1 3 5 1 3 5
-21Q1 -21Q2
/22.1 /22.1
/22.9 I> I> I> /22.10 I> I> I>
20,3A ge 2 4 6 20,3A ge 2 4 6
CLASS 10 CLASS 10
PKE32/XTU-32 1 3 5 PKE32/XTU-32 1 3 5 1 3 5
-21K1 -21K2 -21K3
/22.1 2 4 6 /22.4 2 4 6 /22.3 2 4 6

4 mm² 4 mm²

PE PE
-X1 21 22 23 24 28 25 26 27

-W121.1 -W121.2
BN BK GY GNYE GNYE BN BK GY
H07RN-F H07RN-F
4x4 mm² 22 m 4x4 mm² 22 m
U1 V1 W1 PE
BURNER VENTILATOR BURNER VENTILATOR
-21M1
M
18,5 kW 35A 3~
IE2 V2 U2 W2

BURNER VENTILATOR
13 22
DATE 2013-04-29 COMMISSION : LS-71366/07.04.1 Ammann Asphalt 02.003 G0 A 0091 04 60201857290 = T2
proc. UGR
CLIENT : Ammann do Brasil BURNER VENTILATOR SWITCH PANEL G0 +
Appr
ASPHALT MIXING PLANT D-31061 Alfeld 18,5 KW 35A CAD: 71366_G0
MODIFICATIONDATE NAME origin \\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 21
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

230VAC (P)
13.10 / 3L1 3L1 / 24.1
+24VDC
13.10 / 3L+ 3L+ / 24.1

-D1A32 5.1 5.2


11 13 13 1.21 1.21
-21K11 -21K1 -21K2 -21Q1 -21Q2
/22.6 14 OFF = 0 0 /22.1 14 /22.4 14 /21.1 1.22 /21.3 1.22

1.13 STAR = 1 0
-21Q1
/21.1 1.14 DELTA = 1 1
1.13
-21Q2
/21.3 1.14

=G0-D1A32

OUTPUT OUTPUT
5.1 5.2 5.3
5.1 5.2
INPUT INPUT INPUT

=G0-D1E32

11
-21K12
/22.7 12 14

13 43 21 21
21K3 21K1 -21K2 -21K3
/22.3 14 /22.1 44 /22.4 22 /22.3 22

A1 A1 A1 A1 A1
-21K1 -21K3 -21K2 -21K11 -21K12
PKE32 A2 DILM25-22 A2 PKE32 A2 38.51 A2 38.51 A2
230VAC 230VAC 230VAC 24VDC 24VDC

230VAC (N)
13.10 / 3L2 3L2 / 24.4
0VDC
13.10 / 3L- 3L- / 24.4

MAIN STAR DELTA BURNER VENTILATOR


CONTACTOR CONTACTOR CONTACTOR STAR/NET ON DELTA ON NET ON DELTA ON ERROR

1 2 /21.1 1 2 /21.4 1 2 /21.3 11 14 /22.1 14


3 4 /21.2 3 4 /21.5 3 4 /21.3 12 11 /22.3
5 6 /21.2 5 6 /21.5 5 6 /21.3
13 14 /22.7 13 14 /22.1 13 14 /22.8
43 44 /22.2 21 22 /22.4 21 22 /22.3

21 24
DATE 2013-02-04 COMMISSION : LS-71366/07.04.1 Ammann Asphalt 02.003 G0 A 0091 04 60201857290 = T2
proc. UGR
CLIENT : Ammann do Brasil BURNER VENTILATOR SWITCH PANEL G0 +
Appr
ASPHALT MIXING PLANT D-31061 Alfeld CONTROL PART 11 KW CAD: 71366_G0
MODIFICATIONDATE NAME origin \\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 22
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

230VAC (P)
22.10 / 3L1 3L1 / 27.1
+24VDC
22.10 / 3L+ 3L+ / 27.1

2L1
400V +/-5% 3Ph 50Hz 2L1
2L2 2L2
2L3 2L3
13 1.21
1 3 5 -22K1 -22Q1
-22Q1 /24.5 14 /24.1 1.22
/24.5
/24.8 I> I> I>
1,9A ge 2 4 6
CLASS 10
PKE12/XTU-4 1 3 5
-22K1
/24.5 2 4 6

=G0-D1A32

OUTPUT
6.1 6.2
6.1
INPUT INPUT

=G0-D1E32

11

2,5 mm²
-22K11
/24.6 14

1.13
PE
-22Q1
-X1 29 30 31 32 /24.1 1.14

A1 A1
-22K1 -22K11
PKE12 A2 38.51 A2
230VAC 24VDC

230VAC (N)
22.10 / 3L2 3L2 / 27.1
0VDC
22.10 / 3L- 3L- / 27.1

OIL PRESSURE OIL PRESSURE


-W122 PUMP ON PUMP ON ON ERROR
BN BK GY GNYE
H07RN-F 4x1,5 mm² 20 m
U1 V1 W1 OIL PRESSURE PUMP 1 2 /24.1 11 14 /24.5

-22M1
M 3 4 /24.2
3~ 5 6 /24.2
0,9 KW 13 14 /24.7
1,9A PE 43 44 /49.2

OIL PRESSURE PUMP


22 27
DATE 2013-05-29 COMMISSION : LS-71366/07.04.1 Ammann Asphalt 02.004 G0 A 0091 04 60201857290 = T2
proc. UGR
CLIENT : Ammann do Brasil OIL PRESSURE SWITCH PANEL G0 +
Appr
ASPHALT MIXING PLANT D-31061 Alfeld PUMP 0,9 KW 1,9A CAD: 71366_G0
MODIFICATIONDATE NAME origin \\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 24
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

230VAC (P)
24.10 / 3L1 3L1 / 31.1
+24VDC
24.10 / 3L+ 3L+ / 31.1

41 41
-27K1 -27K2
/27.1 44 /27.3 44

=G0-D2A32

OUTPUT OUTPUT
8.1 8.2
8.1 8.2
INPUT INPUT

=G0-D2E32

A1 A1
-27K1 -27K2
55.34 A2 55.34 A2
24VDC 24VDC

230VAC (N)
24.10 / 3L2 3L2 / 31.1
0VDC
24.10 / 3L- 3L- / 31.1

LIGHT OIL HEAVY OIL LIGHT OIL HEAVY OIL


OPERATION MODE OPERATION MODE

14 11 /48.1 14 11 /46.3
41 44 /27.7 31 34 /48.4
41 44 /27.8

24 31
DATE 2013-05-28 COMMISSION : LS-71366/07.04.1 Ammann Asphalt SELECT G0 A 0091 04 60201857290 = T2
proc. UGR
CLIENT : Ammann do Brasil LIGHT OIL / HEAVY FUEL SWITCH PANEL G0 +
Appr
ASPHALT MIXING PLANT D-31061 Alfeld NELS-BURNER CAD: 71366_G0
MODIFICATIONDATE NAME origin \\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 27
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

230VAC (P)
27.10 / 3L1 3L1 / 41.1
230VAC (N)
27.10 / 3L2 3L2 / 41.1
+24VDC
27.10 / 3L+ 3L+ / 41.1
0VDC
27.10 / 3L- 3L- / 41.1

=G0-A1E8

ANALOGUE
INPUT
1.1 1.3

-X4 26

-30R2
499Ω

-X4 21 22 25

S / 43.3

-W343
1 2 3

=T2-W343 /
40POLE / CODE 2 S / 43.3

=IB -X2 B1 D8 -X2 D9


-XB 21 22

-30U1
10 12 7 4-20mA 9
MEASURING TRANSDUCER
+ -
1 2

-W430.1
BK WH
Fe-CuNi 2x1,5 mm² 10 m
TEMPERATURE FE-CUNI TEMPERATURE SENSOR DRUM
DRUM DISCHARGE
-30B1

SENSOR DE TEMPERATURA TAMBOR DE DESCARGA


TEMPERATURE SENSOR DRUM DISCHARGE

27 41
DATE 2013-02-22 COMMISSION : LS-71366/07.04.1 Ammann Asphalt TEMPERATURE MEASUREMENT G0 A 0091 04 60201857290 = T2
proc. PBR
CLIENT : Ammann do Brasil DRUM DISCHARGE SWITCH PANEL G0 +
Appr
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 31
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

230VAC (P)
31.10 / 3L1 3L1 / 42.1
+24VDC
31.10 / 3L+ 3L+ / 42.1
230VAC (P) UNSWITCHED
=H0/20.8 / 11
230VAC (N) UNSWITCHED
=H0/20.8 / 12
PE
-X2 11 12 20
PE PE
-X2 21
6 mm² PE-BUS BAR SIDEWISE
AT CASE

=G0-BK2 -41A1
663R0405ETA 26 25 PE 60
BR1 1-2 FERRULE RESISTOR LSB ACTIVE CONTROL UNIT FOR BURNER SYSTEMS
F2 F3 F4

SYSTEM-BUS
F1 F2 F5 F3 F4
Remote out

LAMTEC-
Remote in

4AF 315mAmT 2AT 2AT 2AT


Interbus

Interbus

F5

CAN-GND
D-Sub D-Sub CAN-H 1 D-Sub MACHINE CONTROL ELEMENTS IGNITION MAIN GAS MAIN GAS

CAN-L 1
SCREEN

9pol. 9pol. 9pol. TRANSFORMER 1 2


+24V

CONNECTION
VENTILATOR OIL VALVES
0V

PE

REGULATOR EXTERNAL POWER CONTROLLER


X1

X2

IGNITION VALVES

LSB
OUT
IBS

IBS

3 2 1 4 5 6 10 3 4 5 6 19 20 21

IN
OIL PUMP
IN

ERROR
PE-BUS BAR SIDEWISE
BK WH BN GY AT CASE

-X3 11 12 20 -X8 13 14 15 16
LAMTEC SYSTEM BUS
INTERBUS-S PE

=D0/41.2 / IBS+ IBS+ / =M0/29.1


=D0/41.2 / IBS- IBS- / =M0/29.1

230VAC (N)
31.10 / 3L2 3L2 / 42.5
0VDC
31.10 / 3L- 3L- / 42.5

BUS TERMINAL INTERBUS-S CONTROL UNIT FOR BURNER SYSTEMS ETAMATIC S

31 42
DATE 2013-02-22 COMMISSION : LS-71366/07.04.1 Ammann Asphalt BURNER CONTROL G0 A 0091 04 60201857290 = T2
proc. PBR
CLIENT : Ammann do Brasil POWER SUPPLY ETAMATIC S SWITCH PANEL G0 +
Appr
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 41
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

230VAC (P)
41.10 / 3L1 3L1 / 43.1
+24VDC
41.10 / 3L+ 3L+ / 43.1

-41A1
Etamatic S F5
F6 CONTROL UNIT FOR BURNER SYSTEMS 21
1,2AT -42K1T
PLANT BURNER VENTILATOR
24VDC 0VDC
SAFETY CHAIN ON /42.6 24
PE PE
START POSITION
PE-BUS BAR SIDEWISE 24 22 52 CONTROL
63 UNIT FOR BURNER SYSTEMS
AT CASE

-X8 1 2 -X8 3 -X2 23

-X8:1+ / 43.3 =G0-D1A32

15 14 OUTPUT OUTPUT
-42K1T -47K3 6.3
/42.6 16 /47.8 11 6.3 6.4
STARTING COMPRESSED INPUT
BYPASS AIR OKAY
=G0-D1E32

A1 B1 A1
-42K1T -42K1
87.02 A2 38.51 A2
Fkt.:AI / 120s 230VAC
STARTING
BYPASS 230VAC (N)
41.10 / 3L2 3L2 / 43.1
0VDC
13 13 41.10 / 3L- 3L- / 43.1
=T0-25K2 =E0-21K2 START POSITION
=T0/27.4 14 =E0/22.4 14 CONTROL UNIT FOR BURNER SYSTEMS ERROR
DRUM FAN RUNNING START POSITION UNLOCK
BURNER VENTILATOR ON
15 16 /42.2 11 14 /52.1
43 11
21 24 /42.8
=T0-29K1 =E0-30K1
=T0/33.1 44 =E0/32.3 14
FEEDING BELT TEMPERATURE
FILTER OK

SAFETY CHAIN
41 43
DATE 2013-05-29 COMMISSION : LS-71366/07.04.1 Ammann Asphalt 430 G0 A 0091 04 60201857290 = T2
proc. UGR
CLIENT : Ammann do Brasil BURNER LOCK START SWITCH PANEL G0 +
Appr
ASPHALT MIXING PLANT D-31061 Alfeld POSITION CAD: 71366_G0
MODIFICATIONDATE NAME origin \\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 42
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

230VAC (P)
42.10 / 3L1 3L1 / 46.1
230VAC (N)
42.10 / 3L2 3L2 / 46.1
+24VDC
42.10 / 3L+ 3L+ / 46.1
0VDC
42.10 / 3L- 3L- / 46.1

-41A1
Etamatic S
CONTROL UNIT FOR BURNER SYSTEMS
BURNER AIR
SURVEILLANCE

PE PE
48 PE-BUS BAR SIDEWISE
AT CASE

-X8 4

42.6 / -X8:1+ -X8:1+ / 46.2


PE
-X8 1 28 -X2 21 22 20

31.3 / S S / 52.4

-W343 -W243
4 5 1 2 GNYE
ÖSYZ-J 25x0,75 mm² 22 m ÖZ-J 25x1 mm² 22 m
CONTROL CABLE BURNER CONTROL CABLE BURNER
=T2-W243 /
31.3 / S S / 52.4 40POLE / CODE 1

=IB -X2 C1 C2 -X1 A1 A2 PE


94

96

PE
L / 46.9
N / 47.1
-XB L N PE

1 2
-43B1 P
94 3

AIR CONTROLLER CONTROL VOLTAGE


42 COMBUSTION AIR BURNER 46
DATE 2013-02-22 COMMISSION : LS-71366/07.04.1 Ammann Asphalt AIR CONTROLLER G0 A 0091 04 60201857290 = T2
proc. PBR
CLIENT : Ammann do Brasil COMBUSTION AIR SWITCH PANEL G0 +
Appr
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 43
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

230VAC (P)
43.10 / 3L1 3L1 / 47.1
+24VDC
43.10 / 3L+ 3L+ / 47.1

-41A1
Etamatic S
CONTROL UNIT FOR BURNER SYSTEMS 25 11

FUEL SELECTION
-46K1T -48K4
/46.7 26 /48.10 12
PE PE
PE-BUS BAR SIDEWISE 49
AT CASE

-X8 5

14
-27K2 7.1
/27.3 11
HEAVY OIL INPUT
MODE
=G0-D1E32

43.4 / -X8:1+ -X8:1+ / 48.1

-X2 40

-W243
12
A1 B1
-46K1T
87.02 A2
Fkt.:BE =IB -X1 B10

100
230VAC (N)
43.10 / 3L2 3L2 / 47.6
0VDC
43.10 / 3L- 3L- / 47.6 43.7 / L L / 47.1
-XB PE 98
FUEL SELECT ATOMIZER AIR SURVEILLANCE
PRESSURE ATOMIZER AIR
CLOSED DEEP PRESSURE MIN.
18 15 /48.2
25 26 /46.6
2 3
PE
-46B1 P
98 1

ATOMIZER AIR
43 PRESSURE MIN. 47
DATE 2013-05-30 COMMISSION : LS-71366/07.04.1 Ammann Asphalt FUEL CHOICE G0 A 0091 04 60201857290 = T2
proc. UGR
CLIENT : Ammann do Brasil SURVEILLANCE PRESSURE SWITCH PANEL G0 +
Appr
ASPHALT MIXING PLANT D-31061 Alfeld ATOMIZER AIR CAD: 71366_G0
MODIFICATIONDATE NAME origin \\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 46
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

230VAC (P)
46.10 / 3L1 3L1 / 48.1
+24VDC
46.10 / 3L+ 3L+ / 48.1

41
-47K3
/47.8 42

6.4

INPUT

=G0-D1E32

-X3 21 -X2 35

-W243
15
A1
-47K3
55.34 A2
=IB -X1 B4 -X2 C3 C4 C5 -X1 B9 230VAC
69

401

402

404

92

230VAC (N)
46.7 / 3L2 3L2 / 48.8
0VDC
46.10 / L L / 48.6 46.7 / 3L- 3L- / 48.8
43.7 / N N / 48.3
COMPRESSED COMPRESSED
-XB 90 AIR OKAY AIR
PRESSURE CLOSED DEEP
14 11 /42.4
41 42 /47.9

C
-47B3 P
90 NO

COMPRESSED
46 AIR MINIMUM 48
DATE 2013-02-04 COMMISSION : LS-71366/07.04.1 Ammann Asphalt SURVEILLANCE AIR PRESSURE G0 A 0091 04 60201857290 = T2
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 +
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 47
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

230VAC (P)
47.10 / 3L1 3L1 / 49.1
+24VDC
47.10 / 3L+ 3L+ / 49.1

-41A1
Etamatic S F3 F3
CONTROL UNIT FOR BURNER SYSTEMS
OIL
OIL PUMP OIL VALVES
SAFETY CHAIN
ON

PE PE
PE-BUS BAR SIDEWISE 51 62 66
AT CASE

-X8 6 -X2 24 -X2 25


14
-48K2
/48.9 11
OIL
PRESSURE MAXIMUM
14 21
-48K1 -48K4
/48.8 11 /48.10 22
OIL
PRESSURE MINIMUM
18 31
-46K1T -27K2
/46.7 15 /27.3 34
ATOMIZER AIR HEAVY OIL
PRESSURE MIN. MODE

-X2 36 -X2 51 -X2 48 -X2 37 -X2 38 39


14 14
-27K1 -49K1
/27.1 11 /49.8 11
LIGHT OILOIL TEMPERATURE
OPERATION MINIMUM 51.7 -W243 -W243
6 24 13 16 7 17
-X8:1+
46.3 / -X8:1+ A1 A1 A1 A1
-48K1 -48K2 -48K3 -48K4
38.51 A2 38.51 A2 38.51 A2 55.34 A2
=IB -X1 B1 -X1 B8 -X1 B6 -X1 B3 -X1 C1 -X1 C2 230VAC 230VAC 230VAC 230VAC
60

60

60

150

104

107
230VAC (N)
49.2 47.5 49.2 47.10 / 3L2 3L2 / 49.6
0VDC
N L L 47.10 / 3L- 3L- / 49.6
47.5 / N
OIL OIL OIL VALVES CONCLUSION VALVE
-XB 60 N PE N PE 63 N PE N PE -XB 102 106 PRESSURE PRESSURE LANCE
-
˜
+ -
˜
+
MINIMUM OKAY
MAXIMUM OKAY
˜ ˜
14 11 /48.2 14 11 /48.2 11 12 /49.2 11 12 /46.7
21 22 /48.4
- + PE L N PE - + PE L N PE 2 4 2 4
P P
-48B1 1 -48B2 1
-48Y1 -48Y7 -48Y3 -48Y5 102 106
60 55 63 150 PRE-RUN RETURN
FLOW
OIL VALVE 1 PULVERIZATION OIL VALVE CONCLUSION VALVE OIL PRESSURE OIL PRESSURE
47 PRE-RUN AIR RETURN FLOW LANCE MINIMUM MAXIMUM 49
DATE 2013-05-30 COMMISSION : LS-71366/07.04.1 Ammann Asphalt OIL CONTROL G0 A 0091 04 60201857290 = T2
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 +
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 48
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

230VAC (P)
48.10 / 3L1 3L1 / 51.1
+24VDC
48.10 / 3L+ 3L+ / 51.1

43 41 11
-22K1 -49K1 -49K2
/24.5 44 /49.8 44 /49.8 12
PRESSURE PUMP
11
-48K3
/48.9 12
OIL VALVES
11
-51K1
/51.6 12
IGNITION VALVES
8.3 8.4

INPUT INPUT

=G0-D2E32

-X2 46 -X2 49 50

-W243 -W243
21 22 23

A1 A1
-49K1 -49K2
=IB -X1 B2 -X1 D5 D6 55.34 A2 38.51 A2
230VAC 230VAC
68
68

87

88

230VAC (N)
48.7 / L 48.10 / 3L2 3L2 / 51.6
0VDC
48.5 / N N / 51.2 48.10 / 3L- 3L- / 51.1

-XB 68 N PE -XB 86 OIL TEMPERATURE


˜ FORWARD THE BURNER
-
˜
+
MINIMUM MAXIMUM
14 11 /48.2 11 12 /49.8
41 44 /49.8
NO NC

- + PE C C

-49B1 -49B2
-48Y6 87 88
68 MIN. MAX.
OIL VALVE OIL TEMPERATURE
48 BY-PASS FORWARD THE BURNER 51
DATE 2013-05-30 COMMISSION : LS-71366/07.04.1 Ammann Asphalt BURNER CONTROL G0 A 0091 04 60201857290 = T2
proc. UGR
CLIENT : Ammann do Brasil SURVEILLANCE SWITCH PANEL G0 +
Appr
ASPHALT MIXING PLANT D-31061 Alfeld OIL TEMPERATURE CAD: 71366_G0
MODIFICATIONDATE NAME origin \\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 49
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

230VAC (P)
49.10 / 3L1 3L1 / 52.1
+24VDC
49.10 / 3L+ 3L+ / 56.1
0VDC
49.10 / 3L- 3L- / 56.1

-41A1 TERMINAL

F4 F4
Etamatic S 46 IS IGNITION DELAY
TO PURGE
CONTROL UNIT FOR BURNER SYSTEMS
QUIT IGNITION
IGNITION VALVES IGNITION TRANSFORMER
POSITION

PE PE
65 64 46 PE-BUS BAR SIDEWISE
AT CASE

-X8 7

48.2 / -X8:1+ -X8:1+ / 52.6

-X2 31 32

-W243
3 4
A1
-51K1
38.51 A2
=IB -X1 A10 -X1 A6 230VAC
47

22

230VAC (N)
49.10 / 3L2 3L2 / 52.1
49.5 / N N / 52.1
-XB PE N IGNITION
-51T1 VALVES ON
-XB 47 49 N PE 22
L1 L2 N PE
11 12 /49.2

-51Y1 -51Y2
47 49

IGNITION IGNITION IGNITION TRANSFORMER


49 GAS VALVE 1GAS VALVE 2 52
DATE 2013-05-27 COMMISSION : LS-71366/07.04.1 Ammann Asphalt IGNITION G0 A 0091 04 60201857290 = T2
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 +
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 51
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

230VAC (P)
51.10 / 3L1 3L1 / 56.1
230VAC (N)
51.10 / 3L2 3L2 / 56.1

-41A1
Etamatic S
11 CONTROL UNIT FOR BURNER SYSTEMS
-42K1 MAIN FLAME REZI CONTROL
/42.7 14 SIGNAL ON RELEASE

BURNER VENTILATOR PE PE FLAME DETECTOR


PE PE
START PE-BUS BAR SIDEWISE 44 38 35 36 37 53 54 56 PE-BUS BAR SIDEWISE
AT CASE AT CASE

-X8 8 9

51.8 / -X8:1+

-X2 33 -X4 31 32 33 34 35

43.4 / S S / 56.5

-W243 -W343
5 6 7 8 9 10

43.4 / S S / 56.5
=IB -X1 B7 -X2 A1 A2 A3 A4 A5 A6
53

32

33

34

35

36

Res.

51.5 / N N / 56.1
BU RD GN WH YE PK
-XB N PE -XB S

L N PE

-54V1
32 SH
-52Y1
ws

sw
gn

ge

rs
bl

rt

53 FFS 06

FLAME SENSOR FLAME SENSOR


51 COOLING 56
DATE 2013-05-30 COMMISSION : LS-71366/07.04.1 Ammann Asphalt FLAME CONTROL G0 A 0091 04 60201857290 = T2
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 +
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 52
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

230VAC (P)
52.10 / 3L1 3L1 / 57.1
230VAC (N)
52.10 / 3L2 3L2 / 57.1
+24VDC
51.10 / 3L+ 3L+ / 57.1
0VDC
51.10 / 3L- 3L- / 57.1

-41A1
Etamatic S
F2 CONTROL UNIT FOR BURNER SYSTEMS

CHANNEL
CHANNEL
2 RETURN
2 POSITION SIGNAL
PE PE
32 31 12 11 10 PE-BUS BAR SIDEWISE
OPEN CLOSED AT CASE

PE
-X2 42 43 -X4 44 45 46 20 S

52.5 / S S / 57.5
-W243 -W343
8 9 11 12 13 GNYE

52.5 / S S / 57.5
=IB -X1 C5 C7 -X2 B2 B3 B4 PE D10
163

160

112

111

110

52.6 / N N / 57.1
-XB N PE -XB S

-56M1
160 17 7 16 3 13 2 14 4 6 15 5 PE 10 9 8
5k
M

TYPE 02-20/430
OPEN 1% OPEN CLOSED CLOSED (2. STEP)

AIR FLAP
52 57
DATE 2013-02-26 COMMISSION : LS-71366/07.04.1 Ammann Asphalt AIR FLAP G0 A 0091 04 60201857290 = T2
proc. UGR
CLIENT : Ammann do Brasil CHANNEL 2 SWITCH PANEL G0 +
Appr
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 56
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

230VAC (P)
56.10 / 3L1 3L1 / =E0/13.1
230VAC (N)
56.10 / 3L2 3L2 / =E0/13.1
+24VDC
56.10 / 3L+ 3L+ / =E0/13.1
0VDC
56.10 / 3L- 3L- / =E0/13.1

-41A1
Etamatic S
F2 CONTROL UNIT FOR BURNER SYSTEMS

CHANNEL
CHANNEL
3 RETURN
3 POS.SIGNAL
PE PE
30 29 15 14 13 PE-BUS BAR SIDEWISE
OPEN CLOSED AT CASE

-X2 44 45 -X4 47 48 49

56.6 / S

-W243 -W343
10 11 14 15 16

56.6 / S

=IB -X1 C9 C10 -X2 B5 B6 B7


263

260

212

211

210

56.4 / N
-XB N PE -XB S

-57M1
260 4 2 1 3 5 7 6 8 PE 9 10 11
5k
M

TYPE 01-15/30
OPEN CLOSED CLOSED

OIL CONTROL VALVE


56 +KLE/1
DATE 2013-02-26 COMMISSION : LS-71366/07.04.1 Ammann Asphalt SERVO DRIVE OIL G0 A 0091 04 60201857290 = T2
proc. UGR
CLIENT : Ammann do Brasil CHANNEL 3 SWITCH PANEL G0 +
Appr
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 57
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

TERMINAL STRIP OVERVIEW AAD_F14_002

TERMINALS
TERMINAL BLOCK FUNCTION TEXT PAGE TERMINAL DIAGRAM
FIRST LATEST SUM PE SUM N TOTAL NUMBER
-X1 CONSUMER 400VAC 21 32 3 0 12 =T2+KLE/11
-X2 CONTROL TERMINAL 230VAC 11 51 4 0 35 =T2+KLE/12
-X3 CONTROL TERMINAL 24VDC 11 22 4 0 13 =T2+KLE/13
-X4 ANALOG VOLTAGES 20 49 1 0 17 =T2+KLE/14
-X8 INTERNAL 24VDC ETAMATIC S 1 28 0 0 15 =T2+KLE/15

+/57 11
DATE 2013-05-30 COMMISSION : LS-71366/07.04.1 Ammann Asphalt TERMINAL STRIP REVIEW G0 A 0091 04 60201857290 = T2
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KLE
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 1
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

TERMINAL DIAGRAM AAD_F13_001

CABLE NAME

CABLE NAME
-W122
-W121.2
-W121.1
STRIP
=T2+-X1
CONSUMER 400VAC

H07RN-F 4x1,5 mm²

H07RN-F 4x4 mm²

H07RN-F 4x4 mm²

CABLE TYPE

CABLE TYPE
CONNECTION

CONNECTION
TERMINAL
FUNCTION TEXT DESTINATION DESCRIPTION DESTINATION DESCRIPTION PAGE / COLUMN

BURNER VENTILATOR BN -21M1 U1 21 -21K1 2 /21.1


= BK -21M1 V1 22 -21K1 4 /21.2
= GY -21M1 W1 23 -21K1 6 /21.2
= GNYE -21M1 PE 24 /21.2
= BN -21M1 W2 25 -21K2 2 /21.3
= BK -21M1 U2 26 -21K2 4 /21.3
= GY -21M1 V2 27 -21K2 6 /21.3
= GNYE -21M1 PE 28 /21.3
OIL PRESSURE PUMP BN -22M1 U1 29 -22K1 2 /24.1
= BK -22M1 V1 30 -22K1 4 /24.2
= GY -22M1 W1 31 -22K1 6 /24.2
= GNYE -22M1 PE 32 /24.2

1 12
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt TERMINAL DIAGRAM =T2+-X1 G0 A 0091 04 60201857290 = T2
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KLE
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 11
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

TERMINAL DIAGRAM AAD_F13_001

CABLE NAME

CABLE NAME
-W243
STRIP
=T2+-X2
CONTROL TERMINAL 230VAC

ÖZ-J 25x1 mm²

CABLE TYPE

CABLE TYPE
CONNECTION

CONNECTION
TERMINAL
FUNCTION TEXT DESTINATION DESCRIPTION DESTINATION DESCRIPTION PAGE / COLUMN

CONTROL UNIT FOR BURNER SYSTEMS ETAMATIC S -41A1 26 11 =H0-8G2 L /41.5


= -41A1 25 12 =H0-8G2 N /41.5
20 /13.3
20 /13.4
CONTROL UNIT FOR BURNER SYSTEMS ETAMATIC S -41A1 PE 20 /41.5
CONTROL VOLTAGE BURNER GNYE =IB-X1 PE 20 /43.7
21 =T0-48K11 11 /13.3
-21K11 11
21 /13.3
CONTROL UNIT FOR BURNER SYSTEMS ETAMATIC S -41A1 60 21 -22K11 11 /41.8
CONTROL VOLTAGE BURNER 1 =IB-X1 A1 21 -46K1T A1 /43.7
22 =T0-48K1 A2 /13.3
-21K1 A2
22 /13.3
22 /13.3
CONTROL VOLTAGE BURNER 2 =IB-X1 A2 22 -42K1 A2 /43.7
-46K1T A2
START POSITION CONTROL UNIT FOR BURNER SYSTEMS -42K1T A1 23 -41A1 63 /42.6
OIL VALVE 1 PRE-RUN -X2 36 24 -41A1 62 /48.3
-X2 51
CONCLUSION VALVE LANCE -48K4 A1 25 -41A1 66 /48.5
-X2 37
IGNITION GAS VALVE 1 3 =IB-X1 A10 31 -41A1 65 /51.2
-51K1 A1
IGNITION TRANSFORMER 4 =IB-X1 A6 32 -41A1 64 /51.4
FLAME SENSOR COOLING 5 =IB-X1 B7 33 -42K1 14 /52.1
COMPRESSED AIR MINIMUM 15 =IB-X1 B9 35 -47K3 A1 /47.5
OIL VALVE 1 PRE-RUN 6 =IB-X1 B1 36 -X2 24 /48.3
CONCLUSION VALVE LANCE 16 =IB-X1 B3 37 -X2 25 /48.5
OIL PRESSURE MINIMUM 7 =IB-X1 C1 38 -48K1 A1 /48.6
= 17 =IB-X1 C2 39 -48K2 A1 /48.7
ATOMIZER AIR PRESSURE MIN. 12 =IB-X1 B10 40 -46K1T B1 /46.9
AIR FLAP 8 =IB-X1 C5 42 -41A1 32 /56.3
= 9 =IB-X1 C7 43 -41A1 31 /56.3
OIL CONTROL VALVE 10 =IB-X1 C9 44 -41A1 30 /57.3

11 12.A
DATE 2013-05-29 COMMISSION : LS-71366/07.04.1 Ammann Asphalt TERMINAL DIAGRAM =T2+-X2 G0 A 0091 04 60201857290 = T2
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KLE
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 12
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

TERMINAL DIAGRAM AAD_F13_001

CABLE NAME

CABLE NAME
-W243
STRIP
=T2+-X2
CONTROL TERMINAL 230VAC

ÖZ-J 25x1 mm²

CABLE TYPE

CABLE TYPE
CONNECTION

CONNECTION
TERMINAL
FUNCTION TEXT DESTINATION DESCRIPTION DESTINATION DESCRIPTION PAGE / COLUMN

OIL CONTROL VALVE 11 =IB-X1 C10 45 -41A1 29 /57.3


OIL VALVE BY-PASS 21 =IB-X1 B2 46 -51K1 12 /49.2
OIL VALVE RETURN FLOW 13 =IB-X1 B6 48 -27K2 34 /48.4
OIL TEMPERATURE FORWARD THE BURNER 22 =IB-X1 D5 49 -49K1 A1 /49.4
= 23 =IB-X1 D6 50 -49K2 A1 /49.4
PULVERIZATION AIR 24 =IB-X1 B8 51 -48K4 21 /48.4
-X2 24

12 13
DATE 2013-05-30 COMMISSION : LS-71366/07.04.1 Ammann Asphalt TERMINAL DIAGRAM =T2+-X2 G0 A 0091 04 60201857290 = T2
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KLE
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 12.A
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

TERMINAL DIAGRAM AAD_F13_001

CABLE NAME

CABLE NAME
STRIP
=T2+-X3
CONTROL TERMINAL 24VDC

CABLE TYPE

CABLE TYPE
CONNECTION

CONNECTION
TERMINAL
FUNCTION TEXT DESTINATION DESCRIPTION DESTINATION DESCRIPTION PAGE / COLUMN

BUS TERMINAL INTERBUS-S =D0-23U2 -X23.1 11 =G0-BK2 3 /41.2


=M0-25U2 -X23.1
BUS TERMINAL INTERBUS-S =D0-23U2 -X23.2 12 =G0-BK2 2 /41.3
=M0-25U2 -X23.2
0VDC 20 /13.10
= 20 /13.10
= 20 /13.10
BUS TERMINAL INTERBUS-S 20 =G0-BK2 1 /41.3
+24VDC 21 =T0-48Q1 1.21 /13.8
-21K1 13
+24VDC 21 /13.8
= 21 /13.9
21 -46K1T 25 /47.3
-47K3 41
0VDC 22 =T0-48K11 A2 /13.9
-21K11 A2
0VDC 22 /13.9
= 22 /13.9

12.A 14
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt TERMINAL DIAGRAM =T2+-X3 G0 A 0091 04 60201857290 = T2
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KLE
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 13
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

TERMINAL DIAGRAM AAD_F13_001

CABLE NAME

CABLE NAME
-W343
STRIP
=T2+-X4
ANALOG VOLTAGES

ÖSYZ-J 25x0,75 mm²

CABLE TYPE

CABLE TYPE
CONNECTION

CONNECTION
TERMINAL
FUNCTION TEXT DESTINATION DESCRIPTION DESTINATION DESCRIPTION PAGE / COLUMN

AIR FLAP GNYE =IB-X2 PE 20 /56.5


= S /56.6
TEMPERATURE FE-CUNI DRUM DISCHARGE 1 =IB-X2 B1 21 -27K2 41 /31.2
-42K1T 21
TEMPERATURE FE-CUNI DRUM DISCHARGE 2 =IB-X2 D8 22 -27K2 A2 /31.2
= 3 =IB-X2 D9 25 -30R2 /31.3
=G0-A1E8 1.1
TEMPERATURE FE-CUNI DRUM DISCHARGE -30R2 26 -27K2 A2 /31.3
FLAME SENSOR 6 =IB-X2 A1 31 -41A1 44 /52.4
= 7 =IB-X2 A2 32 -41A1 38 /52.4
= 8 =IB-X2 A3 33 -41A1 35 /52.4
= 9 =IB-X2 A4 34 -41A1 36 /52.5
= 10 =IB-X2 A5 35 -41A1 37 /52.5
AIR FLAP 11 =IB-X2 B2 44 -41A1 12 /56.5
= 12 =IB-X2 B3 45 -41A1 11 /56.5
= 13 =IB-X2 B4 46 -41A1 10 /56.5
OIL CONTROL VALVE 14 =IB-X2 B5 47 -41A1 15 /57.5
= 15 =IB-X2 B6 48 -41A1 14 /57.5
= 16 =IB-X2 B7 49 -41A1 13 /57.5

13 15
DATE 2013-05-29 COMMISSION : LS-71366/07.04.1 Ammann Asphalt TERMINAL DIAGRAM =T2+-X4 G0 A 0091 04 60201857290 = T2
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KLE
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 14
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

TERMINAL DIAGRAM AAD_F13_001

CABLE NAME

CABLE NAME
-W343
STRIP
=T2+-X8
INTERNAL 24VDC ETAMATIC S

ÖSYZ-J 25x0,75 mm²

CABLE TYPE

CABLE TYPE
CONNECTION

CONNECTION
TERMINAL
FUNCTION TEXT DESTINATION DESCRIPTION DESTINATION DESCRIPTION PAGE / COLUMN

SAFETY CHAIN =T0-25K2 13 1 -41A1 24 /42.2


-42K1T 15
AIR CONTROLLER COMBUSTION AIR 4 =IB-X2 C1 1 -42K1T 15 /43.4
-27K2 11
SAFETY CHAIN 2 -41A1 22 /42.2
= -47K3 14 3 -41A1 52 /42.4
AIR CONTROLLER COMBUSTION AIR -X8 28 4 -41A1 48 /43.4
FUEL SELECT -27K2 14 5 -41A1 49 /46.3
-48K2 14 6 -41A1 51 /48.2
IGNITION VALVES ON -49K1 11 7 -41A1 46 /51.8
-X8 9
FLAME SENSOR 8 -41A1 53 /52.6
= -X8 7 9 -41A1 56 /52.6
CONTROL UNIT FOR BURNER SYSTEMS ETAMATIC S 13 -41A1 3 /41.6
= 14 -41A1 4 /41.6
= 15 -41A1 5 /41.7
= 16 -41A1 6 /41.7
AIR CONTROLLER COMBUSTION AIR 5 =IB-X2 C2 28 -X8 4 /43.4

14 +KAB/1
DATE 2013-05-28 COMMISSION : LS-71366/07.04.1 Ammann Asphalt TERMINAL DIAGRAM =T2+-X8 G0 A 0091 04 60201857290 = T2
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KLE
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 15
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

CABLE PLAN
1. PAGE PAGE
CABLE TYPE ID CORES CROSS SECTION LENGTH FUNCTION TEXT CIRCUIT DIAGRAM CABLE DIAGRAM

H07RN-F -W121.1 4 4 22 m BURNER VENTILATOR +/21.1 =T2+KAB/11

-W121.2 4 4 22 m = +/21.3 =T2+KAB/12

-W122 4 1,5 20 m OIL PRESSURE PUMP +/24.1 =T2+KAB/13

ÖZ-J -W243 25 1 22 m CONTROL CABLE BURNER +/43.7 =T2+KAB/14

ÖSYZ-J -W343 25 0,75 22 m CONTROL CABLE BURNER +/52.4;+/43.4 =T2+KAB/15

Fe-CuNi -W430.1 2 1,5 10 m TEMPERATURE SENSOR DRUM +/31.3 =T2+KAB/16

+KLE/15 11
DATE 2013-05-30 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CABLE PLAN G0 A 0091 04 60201857290 = T2
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KAB
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 1
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

CABLE DIAGRAM AAD_F09_002

CABLE NAME =T2+-W121.1 CABLE TYPE H07RN-F


FUNCTION TEXT BURNER VENTILATOR CORE NO. 4 CROSS SECTION 4 mm² CABLE LENGTH 22 m
DESTINATION DESTINATION
FUNCTION TEXT PAGE / COLUMN CONNECTION CORE CONNECTION PAGE / COLUMN FUNCTION TEXT
DESCRIPTION FROM DESCRIPTION TO

BURNER VENTILATOR /21.1 -X1 21 BN -21M1 U1 /21.1 BURNER VENTILATOR

= /21.2 -X1 22 BK -21M1 V1 /21.1 =

= /21.2 -X1 23 GY -21M1 W1 /21.1 =

= /21.2 -X1 24 GNYE -21M1 PE /21.1 =

1 12
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CABLE DIAGRAM =T2+-W121.1 G0 A 0091 04 60201857290 = T2
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KAB
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 11
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

CABLE DIAGRAM AAD_F09_002

CABLE NAME =T2+-W121.2 CABLE TYPE H07RN-F


FUNCTION TEXT BURNER VENTILATOR CORE NO. 4 CROSS SECTION 4 mm² CABLE LENGTH 22 m
DESTINATION DESTINATION
FUNCTION TEXT PAGE / COLUMN CONNECTION CORE CONNECTION PAGE / COLUMN FUNCTION TEXT
DESCRIPTION FROM DESCRIPTION TO

BURNER VENTILATOR /21.3 -X1 25 BN -21M1 W2 /21.1 BURNER VENTILATOR

= /21.3 -X1 26 BK -21M1 U2 /21.1 =

= /21.3 -X1 27 GY -21M1 V2 /21.1 =

= /21.3 -X1 28 GNYE -21M1 PE /21.1 =

11 13
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CABLE DIAGRAM =T2+-W121.2 G0 A 0091 04 60201857290 = T2
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KAB
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 12
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

CABLE DIAGRAM AAD_F09_002

CABLE NAME =T2+-W122 CABLE TYPE H07RN-F


FUNCTION TEXT OIL PRESSURE PUMP CORE NO. 4 CROSS SECTION 1,5 mm² CABLE LENGTH 20 m
DESTINATION DESTINATION
FUNCTION TEXT PAGE / COLUMN CONNECTION CORE CONNECTION PAGE / COLUMN FUNCTION TEXT
DESCRIPTION FROM DESCRIPTION TO

OIL PRESSURE PUMP /24.2 -X1 30 BK -22M1 V1 /24.1 OIL PRESSURE PUMP

= /24.1 -X1 29 BN -22M1 U1 /24.1 =

= /24.2 -X1 32 GNYE -22M1 PE /24.1 =

= /24.2 -X1 31 GY -22M1 W1 /24.1 =

12 14
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CABLE DIAGRAM =T2+-W122 G0 A 0091 04 60201857290 = T2
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KAB
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 13
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

CABLE DIAGRAM AAD_F09_002

CABLE NAME =T2+-W243 CABLE TYPE ÖZ-J


FUNCTION TEXT CONTROL CABLE BURNER CORE NO. 25 CROSS SECTION 1 mm² CABLE LENGTH 22 m
DESTINATION DESTINATION
FUNCTION TEXT PAGE / COLUMN CONNECTION CORE CONNECTION PAGE / COLUMN FUNCTION TEXT
DESCRIPTION FROM DESCRIPTION TO

CONTROL VOLTAGE BURNER /43.7 -X2 21 1 =IB-X1 A1 /43.7 CONTROL VOLTAGE BURNER

= /43.7 -X2 22 2 =IB-X1 A2 /43.7 =

IGNITION GAS VALVE 1 /51.2 -X2 31 3 =IB-X1 A10 /51.2 IGNITION GAS VALVE 1

IGNITION TRANSFORMER /51.4 -X2 32 4 =IB-X1 A6 /51.4 IGNITION TRANSFORMER

FLAME SENSOR COOLING /52.1 -X2 33 5 =IB-X1 B7 /52.1 FLAME SENSOR COOLING

OIL VALVE 1 PRE-RUN /48.3 -X2 36 6 =IB-X1 B1 /48.3 OIL VALVE 1 PRE-RUN

OIL PRESSURE MINIMUM /48.6 -X2 38 7 =IB-X1 C1 /48.6 OIL PRESSURE MINIMUM

AIR FLAP /56.3 -X2 42 8 =IB-X1 C5 /56.3 AIR FLAP

= /56.3 -X2 43 9 =IB-X1 C7 /56.3 =

OIL CONTROL VALVE /57.3 -X2 44 10 =IB-X1 C9 /57.3 OIL CONTROL VALVE

= /57.3 -X2 45 11 =IB-X1 C10 /57.3 =

ATOMIZER AIR PRESSURE MIN. /46.9 -X2 40 12 =IB-X1 B10 /46.9 ATOMIZER AIR PRESSURE MIN.

OIL VALVE RETURN FLOW /48.4 -X2 48 13 =IB-X1 B6 /48.4 OIL VALVE RETURN FLOW

14

COMPRESSED AIR MINIMUM /47.5 -X2 35 15 =IB-X1 B9 /47.5 COMPRESSED AIR MINIMUM

CONCLUSION VALVE LANCE /48.5 -X2 37 16 =IB-X1 B3 /48.5 CONCLUSION VALVE LANCE

OIL PRESSURE MINIMUM /48.7 -X2 39 17 =IB-X1 C2 /48.7 OIL PRESSURE MINIMUM

18

19

20

OIL VALVE BY-PASS /49.2 -X2 46 21 =IB-X1 B2 /49.2 OIL VALVE BY-PASS
OIL TEMPERATURE FORWARD THE OIL TEMPERATURE FORWARD THE
/49.4 -X2 49 22 =IB-X1 D5 /49.4
BURNER BURNER
= /49.4 -X2 50 23 =IB-X1 D6 /49.4 =

PULVERIZATION AIR /48.4 -X2 51 24 =IB-X1 B8 /48.4 PULVERIZATION AIR

CONTROL VOLTAGE BURNER /43.7 -X2 20 GNYE =IB-X1 PE /43.7 CONTROL VOLTAGE BURNER

13 15
DATE 2013-05-30 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CABLE DIAGRAM =T2+-W243 G0 A 0091 04 60201857290 = T2
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KAB
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 14
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

CABLE DIAGRAM AAD_F09_002

CABLE NAME =T2+-W343 CABLE TYPE ÖSYZ-J


FUNCTION TEXT CONTROL CABLE BURNER CORE NO. 25 CROSS SECTION 0,75 mm² CABLE LENGTH 22 m
DESTINATION DESTINATION
FUNCTION TEXT PAGE / COLUMN CONNECTION CORE CONNECTION PAGE / COLUMN FUNCTION TEXT
DESCRIPTION FROM DESCRIPTION TO
TEMPERATURE FE-CUNI DRUM
/31.2 -X4 21 1 =IB-X2 B1 /31.2 +24VDC
DISCHARGE
= /31.2 -X4 22 2 =IB-X2 D8 /31.2 0VDC
TEMPERATURE FE-CUNI DRUM
= /31.3 -X4 25 3 =IB-X2 D9 /31.3
DISCHARGE
AIR CONTROLLER COMBUSTION AIR /43.4 -X8 1 4 =IB-X2 C1 /43.4 AIR CONTROLLER COMBUSTION AIR

= /43.4 -X8 28 5 =IB-X2 C2 /43.4 =

FLAME SENSOR /52.4 -X4 31 6 =IB-X2 A1 /52.4 FLAME SENSOR

= /52.4 -X4 32 7 =IB-X2 A2 /52.4 =

= /52.4 -X4 33 8 =IB-X2 A3 /52.4 =

= /52.5 -X4 34 9 =IB-X2 A4 /52.5 =

= /52.5 -X4 35 10 =IB-X2 A5 /52.5 =

AIR FLAP /56.5 -X4 44 11 =IB-X2 B2 /56.5 AIR FLAP

= /56.5 -X4 45 12 =IB-X2 B3 /56.5 =

= /56.5 -X4 46 13 =IB-X2 B4 /56.5 =

OIL CONTROL VALVE /57.5 -X4 47 14 =IB-X2 B5 /57.5 OIL CONTROL VALVE

= /57.5 -X4 48 15 =IB-X2 B6 /57.5 =

= /57.5 -X4 49 16 =IB-X2 B7 /57.5 =

17

18

19

20

21

22

23

24

AIR FLAP /56.5 -X4 20 GNYE =IB-X2 PE /56.5 AIR FLAP

SH

14 16
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CABLE DIAGRAM =T2+-W343 G0 A 0091 04 60201857290 = T2
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KAB
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 15
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

CABLE DIAGRAM AAD_F09_002

CABLE NAME =T2+-W430.1 CABLE TYPE Fe-CuNi


FUNCTION TEXT TEMPERATURE SENSOR DRUM CORE NO. 2 CROSS SECTION 1,5 mm² CABLE LENGTH 10 m
DESTINATION DESTINATION
FUNCTION TEXT PAGE / COLUMN CONNECTION CORE CONNECTION PAGE / COLUMN FUNCTION TEXT
DESCRIPTION FROM DESCRIPTION TO
TEMPERATURE SENSOR DRUM TEMPERATURE SENSOR DRUM
/31.3 -30B1 BK =IB-30U1 1 /31.3
DISCHARGE DISCHARGE
= /31.3 -30B1 WH =IB-30U1 2 /31.3

15 +PR/1
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CABLE DIAGRAM =T2+-W430.1 G0 A 0091 04 60201857290 = T2
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KAB
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 16
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

AAD_Pruef2
CIRCUIT OVERVIEW R iso PROTECTIVE CONDUCTOR Z Schl [Ω] RCD(FI)

CIRCUIT (FUNCTION TEXT) CABLE NAME CABLE TYPE LENGTH


[MΩ] IPE [mA] R PE [Ω] I K [A] I N [A] IΔN [mA] UB [V] + /-
BURNER VENTILATOR -W121.1 H07RN-F 4x4 mm² 22 m

= -W121.2 H07RN-F 4x4 mm² 22 m

OIL PRESSURE PUMP -W122 H07RN-F 4x1,5 mm² 20 m

CONTROL CABLE BURNER -W243 ÖZ-J 25x1 mm² 22 m

= -W343 ÖSYZ-J 25x0,75 mm² 22 m

TEMPERATURE SENSOR DRUM -W430.1 Fe-CuNi 2x1,5 mm² 10 m

+KAB/16 2
DATE 2013-05-30 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CIRCUIT OVERVIEW G0 A 0091 04 60201857290 = T2
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + PR
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 1
Kunde:
CLIENT.
Kom-Nr.:
COM.-NO.: LS-71366/07.04.1 ASPHALT MIXING PLANT
Schaltschrank:
SWITCH PANEL: 2400 x 1600 x 500mm Prime 140
Schaltplan-Nr.:
CIRCUIT DIAGRAM-NO.: G0 A 0091 04 Bereich: Porto Alegre
AREA:
Schutzart :
PROTECTION TYPE: RCD (FI)
Betriebsspannung:
Ammann do Brasil
OPERATING VOLTAGE: 3Ph~ / 400VAC / 60Hz Sitio do Sobrado
Steuerspannung:
CONTROL VOLTAGE: 24VDC / 230VAC 94180-452 Gravataí -RS-Brasil
Baujahr : Brasilien
YEAR OF MANUFACTURE: 2013
Prüfprotokoll EN 60204 (VDE 0113) TEST REPORT EN 60204 (VDE0113)
Prüfungsgrund: Erstprüfung Wiederholungsprüfung Sonstiges:
CAUSE OF INSPECTION: INITIAL INSPECTION REPEATED INSPECTION OTHER:
Netz:
TN-C TN-S TT IT-SYSTEM 230V 400V ........V In(Gesamt):
NET: 328 A
I (TOTAL):
Frequenz:
...... L N PEN PE
FREQUENCY .........Hz .........
Prüfung Dokumentation: vorhanden komplett Übereinstimmend mit der Installation
TEST DOCUMENTATION: EXISTING COMPLETE IN CONFORMITY TO THE INSTALLATION
Anmerkung:
NOTE:
Besichtigung:
SURVEY:
Betriebsmittel können den Einflüssen am Verwendungsort standhalten PE, L und N nicht verwechselt
OPERATING EQUIPMENT IS ABLE TO RESIST LOCAL INFLUENCES PE,L AND N ARE NOT CONFOUNDED
Alle Schutzleiter gegen Selbstlockern und Korrosion gesichert Schutz durch Isolierung aller aktiven Teile
ALL PROTECTIVE CONDUCTORS ARE PROTECTED AGAINST SELF-SLACKERING AND CORROSION PROTECTION BY ISOLATION OF ALL ACTIVE PARTS
Keine erkennbaren Schäden Sonstiges:
NO APPARENT DAMAGES OTHER:
Kennzeichnungen, Anschlussstellen und eventuelle Trennstellen in Ordnung
EQUIPMENT IDENTIFICATIONS, CONNECTION POINTS AND ANY DISCONNECTION POINTS ARE OKAY
Messung:
MEASUREMENT. Schlechtester Messwert Prüfung in Ordnung
WORST MEASURED VALUE TEST OKAY
Messgeräte entsprechen EN 61557 (VDE 0413)
MEASURING INSTRUMENTS AGREE WITH EN 61557 (VDE 0413)
Durchgängigkeit des Schutzleitersystems
(Widerstandsmessung mit Prüfstrom mind. 0,2A, max. 10A bzw. Schleifenimpedanzmessung)
CONDUCTIVITY OF THE PROTECTIVE CONDUCTOR SYSTEM
(RESISTANCE MEASUREMENT WITH TESTING CURRENT OF MIN.0,2A; MAX.10A; RESPECTIVELY LOOP IMPEDANCE MEASUREMENT)
Isolationswiderstandsmessung
INSULATION RESISTANCE MEASUREMENT
Spannungsprüfung
VOLTAGE TEST
Restspannngsprüfung (max. 60V nach 5s / 1s; sonst Warnhinweis anbringen)
RESIDUAL VOLTAGE TEST (MAX.60V AFTER 5s/1s, OTHERWISE WARNING INSTRUCTION HAS TO PUT UP)
Sonstiges:
OTHER:
Not-Aus Druckwächter, Endschalter, RCD(FI), Sicherheitstemperaturbegrenzer, etc.
Erprobung: EMERGENCY OFF MANOSTAT, LIMIT SWITCH, RCD(FI), SAFETY TEMPERATURE LIMITER, ETC.
TEST: Verriegelung Meldeleuchten, Anzeigen Funktionsprüfung Sonstiges:
LOCKING SIGNAL LAMPS, INDICATIONS FUNCTION TEST OTHER:
Bemerkungen:
REMARKS:
Prüfung nach EN60204 (VDE0113) durchgeführt Anlage / Installation funktionsfähig übernommen
TEST HAS BEEN DONE ACCORDING TO STANDARD EN 60204 (VDE 0113) THE PLANT / INSTALLATION HAS BEEN TAKEN OVER IN WORKING CONDITIONS
Ort / Datum: LOCATION / DATE: Unterschrift des Prüfers SIGNATURE OF RESPONSIBLE CONTROLLER Datum: DATE: Unterschrift des Auftraggebers SIGNATURE OF RESPONSIBLE CUSTOMER
Hinweise zum Ausfüllen: positive Prüfung negative Prüfung Bitte Nicht-Zutreffendes durchstreichen
-

+
INDICATION NOTE TO FILL OUT POSITIVE INSPECTION NEGATIVE INSPECTION PLEASE CROSS-OUT WHAT IS NOT APPLICABLE
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

CONNECTOR PLAN
CONNECTOR
PLUG DESCRIPTION FUNCTION TEXT PAGE PLUG PLAN
FIRST LATEST SUM PE SUM N TOTAL NUMBER

-X1 =T2-W243 / 40POLE / CODE 1 A1 D6 1 0 21 =IB+STK/11


-X2 =T2-W343 / 40POLE / CODE 2 A1 D9 1 0 18 =IB+STK/12

=T2+PR/2 11
DATE 2013-05-30 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CONNECTOR PLAN G0 A 0091 04 60201857290 = IB
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + STK
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 1
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

PLUG CONNECTION-CONNECTION DIAGRAM CODE 1


TOP VIEW TOP VIEW
CABLE NAME: =T2-W243 PLUG CONNECTION-DESIGNATION CONNECTOR SOCKET FROM
FROM IN FRONT IN FRONT
CABLE TYPE: ÖZ-J

CROSS SECTION: 25x1 mm² =IB+-X1 PE PE

CHECK CHECK LOCKBOLT LOCKBOLT


SOCKET SOCKET

CONNECTION

DESIGNATION
CONNECTION

CONNECTION
core no.
DESIGNATION
CONNECTION
CABLE LENGTH: 22 m 1 1 1 1
TO FROM
EXTERNAL INTERNAL 2 2 2 2

3 3 3 3
FUNCTION TEXT PAGE/PATH
CONTROL VOLTAGE 1 A1 -XB L A1 =T2-X2 21 =T2/43.7 4 4 4 4
= 2 A2 -XB N A2 =T2-X2 22 =T2/43.7
5 5 5 5
FLAME SENSOR 5 B7 =T2-52Y1 L B7 =T2-X2 33 =T2/52.1
AIR FLAP 8 C5 =T2-56M1 13 C5 =T2-X2 42 =T2/56.3
6 6 6 6
= 9 C7 =T2-56M1 14 C7 =T2-X2 43 =T2/56.3
OIL CONTROL VALVE 10 C9 =T2-57M1 2 C9 =T2-X2 44 =T2/57.3 7 7 7 7
= 11 C10 =T2-57M1 3 C10 =T2-X2 45 =T2/57.3
CONTROL VOLTAGE GNYE PE -XB PE PE =T2-X2 20 =T2/43.7 8 8 8 8
IGNITION TRANSFORMER 4 A6 -51T1 A6 =T2-X2 32 =T2/51.4
9 9 9 9
IGNITION 3 A10 -XB 47 A10 =T2-X2 31 =T2/51.2
OIL VALVE 1 6 B1 -XB 60 B1 =T2-X2 36 =T2/48.3
10 10 10 10
OIL VALVE 21 B2 -XB 68 B2 =T2-X2 46 =T2/49.2
CONCLUSION VALVE 16 B3 =T2-48Y5 L B3 =T2-X2 37 =T2/48.5 A B C D D C B A
OIL VALVE 13 B6 -XB 63 B6 =T2-X2 48 =T2/48.4 LOCKBOLT LOCKBOLT CHECK CHECK
PULVERIZATION 24 B8 =T2-48Y7 L B8 =T2-X2 51 =T2/48.4 SOCKET SOCKET
COMPRESSED 15 B9 =T2-47B3 NO B9 =T2-X2 35 =T2/47.5
ATOMIZER AIR 12 B10 =T2-46B1 3 B10 =T2-X2 40 =T2/46.9
OIL PRESSURE 7 C1 =T2-48B1 4 C1 =T2-X2 38 =T2/48.6
= 17 C2 =T2-48B2 2 C2 =T2-X2 39 =T2/48.7
OIL TEMPERATURE 22 D5 =T2-49B1 NO D5 =T2-X2 49 =T2/49.4
= 23 D6 =T2-49B2 NC D6 =T2-X2 50 =T2/49.4

1 12
DATE 2013-05-30 COMMISSION : LS-71366/07.04.1 Ammann Asphalt PLUG PLAN =IB+-X1 G0 A 0091 04 60201857290 = IB
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + STK
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 11
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

PLUG CONNECTION-CONNECTION DIAGRAM CODE 2


TOP VIEW TOP VIEW
CABLE NAME: =T2-W343 PLUG CONNECTION-DESIGNATION CONNECTOR SOCKET FROM
FROM IN FRONT IN FRONT
CABLE TYPE: ÖSYZ-J

CROSS SECTION: 25x0,75 mm² =IB+-X2 PE PE

LOCKBOLT LOCKBOLT CHECK CHECK


SOCKET SOCKET
core no.
DESIGNATION
CONNECTION

CONNECTION

DESIGNATION
CONNECTION

CONNECTION
CABLE LENGTH: 22 m 1 1 1 1
TO FROM
EXTERNAL INTERNAL 2 2 2 2

3 3 3 3
FUNCTION TEXT PAGE/PATH
FLAME SENSOR 6 A1 =T2-54V1 A1 =T2-X4 31 =T2/52.4 4 4 4 4
= 7 A2 =T2-54V1 A2 =T2-X4 32 =T2/52.4
5 5 5 5
= 8 A3 =T2-54V1 A3 =T2-X4 33 =T2/52.4
= 9 A4 =T2-54V1 A4 =T2-X4 34 =T2/52.5
6 6 6 6
= 10 A5 =T2-54V1 A5 =T2-X4 35 =T2/52.5
AIR FLAP 11 B2 =T2-56M1 10 B2 =T2-X4 44 =T2/56.5 7 7 7 7
= 12 B3 =T2-56M1 9 B3 =T2-X4 45 =T2/56.5
= 13 B4 =T2-56M1 8 B4 =T2-X4 46 =T2/56.5 8 8 8 8
OIL CONTROL VALVE 14 B5 =T2-57M1 9 B5 =T2-X4 47 =T2/57.5
9 9 9 9
= 15 B6 =T2-57M1 10 B6 =T2-X4 48 =T2/57.5
= 16 B7 =T2-57M1 11 B7 =T2-X4 49 =T2/57.5
10 10 10 10
SCREEN D10 -XB S D10 =T2/56.6
AIR FLAP GNYE PE PE =T2-X4 20 =T2/56.5 A B C D D C B A
AIR CONTROLLER 4 C1 =T2-43B1 3 C1 =T2-X8 1 =T2/43.4 CHECK CHECK LOCKBOLT LOCKBOLT
= 5 C2 =T2-43B1 2 C2 =T2-X8 28 =T2/43.4 SOCKET SOCKET
+24VDC 1 B1 -XB 21 B1 =T2-X4 21 =T2/31.2
0VDC 2 D8 -XB 22 D8 =T2-X4 22 =T2/31.2
TEMPERATURE FE-CUNI 3 D9 -30U1 7 D9 =T2-X4 25 =T2/31.3

11 =E0+/13
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt PLUG PLAN =IB+-X2 G0 A 0091 04 60201857290 = IB
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + STK
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 12
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

230VAC (P)
=T2/57.10 / 3L1 3L1 / 21.1
230VAC (N)
=T2/57.10 / 3L2 3L2 / 21.1

+24VDC
=T2/57.10 / 3L+ 3L+ / 21.1
0VDC
=T2/57.10 / 3L- 3L- / 21.1

COVER
PE PE
TERMINALS!
-X2 21 21 21 22 22 22 20 -X3 21 21 21 22 22 22 20

230VAC SWITCHED 230VAC UNSWITCHED 24VDC +24VDC 0VDC


INTERBUS-S INTERBUS-S
24VDC
CONTROL VOLTAGE

=IB+STK/12 21
DATE 2013-02-20 COMMISSION : LS-71366/07.04.1 Ammann Asphalt FEED CONTROL G0 A 0091 04 60201857290 = E0
proc. PBR
CLIENT : Ammann do Brasil VOLTAGE SWITCH PANEL G0 +
Appr
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 13
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

230VAC (P)
13.10 / 3L1 3L1 / 22.1
230VAC (N)
13.10 / 3L2 3L2 / 22.1
+24VDC
13.10 / 3L+ 3L+ / 22.1
0VDC
13.10 / 3L- 3L- / 22.1

2L1
400V +/-5% 3Ph 50Hz 2L1
2L2 2L2
2L3 2L3

1
-21Q1
200 A 4
/22.1

-21F2

A1 A2
Thermistorrelais 13 21
EMT6
14 22
T1 T2 /22.1 /22.10

35 mm² 35 mm²

1 3 5 1 3 5 1 3 5
-21K1 -21K2 -21K3
/22.1 2 4 6 /22.4 2 4 6 /22.3 2 4 6
1 3 5 95 97
-21F1
ZB150-100 2 4 6 96 98
78 A

35 mm² 35 mm²

PE PE PE
-X1 21 22 23 24 28 25 26 27 -X4 23 20 24

-W121.1 -W121.2 -W421


BN BK GY GNYE GNYE BN BK GY BN GNYE BU
H07RN-F H07RN-F 4x35 mm² 21 m H07RN-F 3x1,5 mm² 21 m
4x35 mm² 21 m PE EXHAUSTOR PTC SENSOR EXHAUSTOR
W1 W2 PE
EXHAUSTOR
V1 M U2
3~
Θ
U1 V2

-21M1 T1 T2
75 KW
134A
EXHAUSTOR
13 22
DATE 2013-02-04 COMMISSION : LS-71366/07.04.1 Ammann Asphalt EXHAUSTOR G0 A 0091 04 60201857290 = E0
proc. UGR
CLIENT : Ammann do Brasil 75 KW 134A SWITCH PANEL G0 +
Appr
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 21
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

230VAC (P)
21.10 / 3L1 3L1 / 24.1
+24VDC
21.10 / 3L+ 3L+ / 24.1

D2A32 1.1 1.2

1 43 43 97 21
-21Q1 AUS = 0 0 -21K1 -21K2 -21F1 -21F2
/21.2 4 /22.1 44 /22.4 44 /21.3 98 /21.9 22
Stern = 1 0

95 Dreieck = 1 1
-21F1
/21.3 96

13
-21F2
/21.9 14 =G0-D2A32

Ausgang Ausgang
11 1.1 1.2 1.3
-21K11 Eingang Eingang Eingang
1.1 1.2
/22.6 14

=G0-D2E32

13 13 11
-21K3 -21K1 -21K12
/22.3 14 /22.1 14 /22.7 12 14

21 21
-21K2 -21K3
/22.4 22 /22.3 22

A1 A1 A1 A1 A1
-21K1 -21K3 -21K2 -21K11 -21K12
DILM95 A2 DILM65 A2 DILM95 A2 38.51 A2 38.51 A2
230VAC 230VAC 230VAC 24VDC 24VDC

230VAC (N)
21.10 / 3L2 3L2 / 24.1
0VDC
21.10 / 3L- 3L- / 24.1

MAIN CONTACTOR STAR CONTACTOR DELTA CONTACTOR STAR/NET ON DELTA ON MAIN CONTACTOR DELTA CONTACTORERROR

1 2 /21.1 1 2 /21.4 1 2 /21.3 11 14 /22.1 14


3 4 /21.2 3 4 /21.4 3 4 /21.3 12 11 /22.3
5 6 /21.2 5 6 /21.4 5 6 /21.3
13 14 /22.2 13 14 /22.1 13 14 =T2/42.4
43 44 /22.7 21 22 /22.4 21 22 /22.3
43 44 /22.8

21 24
DATE 2013-05-29 COMMISSION : LS-71366/07.04.1 Ammann Asphalt EXHAUSTOR 75 KW G0 A 0091 04 60201857290 = E0
proc. UGR
CLIENT : Ammann do Brasil CONTROL PART 1 SWITCH PANEL G0 +
Appr
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 22
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

230VAC (P)
22.10 / 3L1 3L1 / 25.1
230VAC (N)
22.10 / 3L2 3L2 / 25.1
+24VDC
22.10 / 3L+ 3L+ / 25.1
0VDC
22.10 / 3L- 3L- / 25.1
22STOER / 25.6
2L1
400V +/-5% 3Ph 50Hz 2L1
2L2 2L2
2L3 2L3
=G0-A1E8
1 3 5
-22Q1
/25.5 3.1 3.2 3.3
Analogeingang
/25.6 I> I> I> INPUT INPUT INPUT 3.1 3.3
0,6 A ge 2 4 6
CLASS 10
PKE12/XTU-1,2
=G0-D2E32

1 3 5

ANALOGUE VALUES THROTTLE FLAP


-22K1
/25.5 2 4 6 -X4 28

LIMIT SWITCH THROTTLE FLAP


11 11 -22R2
-22K12 -22K11

ÖSYZ-J 4x0,75 mm² 26 m


499Ω
/25.3 14 /25.2 14

ÖZ-J 4x1 mm² 26 m


ÖZ-J 5x1 mm² 26 m
PE PE PE PE

THROTTLE FLAP
PE
-X1 29 30 31 32 -X3 21 23 24 25 20 -X5 21 23 24 20 -X4 25 26 -X4 27 20 20

-W522

-W422
-W322
1 2 3 4 GNYE 1 2 3 GNYE 1 2 3 GNYE
-W122
BN BK GY GNYE
H07RN-F 4x1,5 mm² 26 m
THROTTLE FLAP
-UC122
-X1 1 2 3 PE -X3 21 23 14 16 PE -X3 5 6 7 11 9 10 PE -X3 30 31 32 PE
PE PE PE

BERNARD RD R1 R2
ASP -X3 13 15
Posigramm +

4 - 20mA
THROTTLE FLAP ERROR OPEN CLOSED CLOSED OPEN ACTUAL VALUE

22 25
DATE 2013-01-22 COMMISSION : LS-71366/07.04.1 Ammann Asphalt THROTTLE FLAP G0 A 0091 04 60201857290 = E0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 +
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 24
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

230VAC (P)
24.10 / 3L1 3L1 / 26.1
+24VDC
24.10 / 3L+ 3L+ / 26.1

=G0-D2A32 =G0-A1E8

OUTPUT OUTPUT 1.21


-22Q1 ANALOGUE INPUT
3.2 3.1 /24.1 1.22 2.1 2.3

24.7 / 22STOER

-X4 30

-23R1
499Ω

PE PE
1.13 -X4 21 29 20 20
-22Q1
/24.1 1.14

-W423
1 2 GNYE
ÖSYZ-J 3x0,75 mm² 26 m
NEGATIVE PRESURE

1 2

-23B1
A1 A1 VEGABAR 52
-22K11 -22K12 A1 0-5mBar
4-20mA
38.51 A2 38.51 A2 -22K1
24VDC 24VDC PKE12 A2
230VAC

230VAC (N)
24.10 / 3L2 3L2 / 26.4
0VDC
24.10 / 3L- 3L- / 26.4
THROTTLE FLAP NEGATIVE PRESSURE
THROTTLE FLAP THROTTLE FLAP MEASURING MINERAL DRUM
OPEN CLOSED OPEN ERROR

11 14 /24.7 11 14 /24.6 1 2 /24.1


3 4 /24.2
5 6 /24.2

24 26
DATE 2013-05-29 COMMISSION : LS-71366/07.04.1 Ammann Asphalt THROTTLE FLAP G0 A 0091 04 60201857290 = E0
proc. UGR
CLIENT : Ammann do Brasil CONTROL PART SWITCH PANEL G0 +
Appr
ASPHALT MIXING PLANT D-31061 Alfeld NEGATIVE PRESURE MINERAL DRUM CAD: 71366_G0
MODIFICATIONDATE NAME origin \\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 25
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

230VAC (P)
25.10 / 3L1 3L1 / 27.1
+24VDC
25.10 / 3L+ 3L+ / 27.1

2L1
400V +/-5% 3Ph 50Hz 2L1
2L2 2L2
2L3 2L3
13 1.21
1 3 5 -24K1 -24Q1
-24Q1 /26.5 14 /26.1 1.22
/26.5
/26.8 I> I> I>
0,8 A ge 2 4 6
CLASS 10
PKE12/XTU-1,2 1 3 5
-24K1
/26.5 2 4 6

=G0-D2A32
OUTPUT
2.1 2.2
2.1
INPUT INPUT

=G0-D2E32

11

2,5 mm²
-24K11
/26.6 14

1.13
PE
-24Q1
-X1 33 34 35 36 /26.1 1.14

-W124 A1 A1
BN BK GY GNYE
H07RN-F 4x1,5 mm² 22 m -24K1 -24K11
CLEANING 1 PKE12 A2 38.51 A2
230VAC 24VDC
=E5
PE 230VAC (N)
AAL -X1 1 2 3 PE 25.10 / 3L2 3L2 / 27.4
0VDC
25.10 / 3L- 3L- / 27.4
-W124.1 CLEANING 1 ON CLEANING 1 ON CLEANING 1 ON ERROR
BN BK GY GNYE
H07RN-F 4x1,5 mm²
CLEANING 1
U1 V1 W1
1 2 /26.1 11 14 /26.5

-24M1
M 3 4 /26.2
3~ 5 6 /26.2
0,25 kW 13 14 /26.7
0,8 A PE

CLEANING 1
25 27
DATE 2013-04-29 COMMISSION : LS-71366/07.04.1 Ammann Asphalt 613 G0 A 0091 04 60201857290 = E0
proc. UGR
CLIENT : Ammann do Brasil CLEANING 1 SWITCH PANEL G0 +
Appr
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 26
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

230VAC (P)
26.10 / 3L1 3L1 / 30.1
+24VDC
26.10 / 3L+ 3L+ / 30.1

2L1
400V +/-5% 3Ph 50Hz 2L1
2L2 2L2
2L3 2L3
13 1.21
1 3 5 -25K1 -25Q1
-25Q1 /27.5 14 /27.1 1.22
/27.5
/27.8 I> I> I>
0,8 A ge 2 4 6
CLASS 10
PKE12/XTU-1,2 1 3 5
-25K1
/27.5 2 4 6

=G0-D2A32
OUTPUT
2.3 2.4
2.3
INPUT INPUT

=G0-D2E32

11

2,5 mm²
-25K11
/27.6 14

1.13
PE
-25Q1
-X1 37 38 39 40 /27.1 1.14

-W125 A1 A1
BN BK GY GNYE
H07RN-F 4x1,5 mm² 22 m -25K1 -25K11
CLEANING 2 PKE12 A2 38.51 A2
230VAC 24VDC
=E5
PE 230VAC (N)
AAL -X1 4 5 6 PE 26.10 / 3L2 3L2 / 30.1
0VDC
26.10 / 3L- 3L- / 30.1
-W125.1 CLEANING 2 ON CLEANING 2 ON CLEANING 2 ON ERROR
BN BK GY GNYE
H07RN-F 4x1,5 mm²
CLEANING 2
U1 V1 W1
1 2 /27.1 11 14 /27.5

-25M1
M 3 4 /27.2
3~ 5 6 /27.2
0,25 kW 13 14 /27.7
0,8 A PE

CLEANING 2
26 30
DATE 2013-04-29 COMMISSION : LS-71366/07.04.1 Ammann Asphalt 613 G0 A 0091 04 60201857290 = E0
proc. UGR
CLIENT : Ammann do Brasil CLEANING 2 SWITCH PANEL G0 +
Appr
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 27
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

230VAC (P)
27.10 / 3L1 3L1 / 32.1
230VAC (N)
27.10 / 3L2 3L2 / 32.1
+24VDC
27.10 / 3L+ 3L+ / 32.1
0VDC
27.10 / 3L- 3L- / 32.1

8.3 8.4

INPUT INPUT

=G0-D1E32

PE
-X3 21 22 27 28 20

-W324
1 2 3 4 GNYE
H07RN-F 7x1,5 mm² 22 m
LIMIT SWITCH CLEANING
=E5
AAL
PE
-X3 + - 1 + - 2 20
PARK POSITION PARK POSITION
1 2 1 2 CLEANING 1 CLEANING 2
CLEANING 1
ÖZ-J 3x1 mm²
-W324.1

CLEANING 2
ÖZ-J 3x1 mm²
-W324.2

1 1

-24B1 -24B2

4 4

PARK POSITION PARK POSITION


27 CLEANING 1 CLEANING 2 32
DATE 2013-04-29 COMMISSION : LS-71366/07.04.1 Ammann Asphalt 613/614 G0 A 0091 04 60201857290 = E0
proc. UGR
CLIENT : Ammann do Brasil LIMIT SWITCH PARK POSITION SWITCH PANEL G0 +
Appr
ASPHALT MIXING PLANT D-31061 Alfeld CLEANING 1 - 2 CAD: 71366_G0
MODIFICATIONDATE NAME origin \\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 30
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

230VAC (P)
30.10 / 3L1 3L1 / 33.1
230VAC (N)
30.10 / 3L2 3L2 / 33.1
+24VDC
30.10 / 3L+ 3L+ / 33.1
0VDC
30.10 / 3L- 3L- / 33.1

A2
-30K1
55.34 A1
230VAC

PE
-X2 21 23 20

-W230
BN BU GNYE
H07RN-F 3x1,5 mm² 22 m
SAFETY THERMOSTAT
=E5
AAL

-X2 17 18 PE

1 2 GNYE
SAFETY THERMOSTAT
ÖZ-J 3x1 mm²
-W230.1

21 11 14 =T2/42.4
PE
-30S0
22

SAFETY THERMOSTAT
30 33
DATE 2013-04-29 COMMISSION : LS-71366/07.04.1 Ammann Asphalt SAFETY THERMOSTAT G0 A 0091 04 60201857290 = E0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 +
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 32
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

230VAC (P)
32.10 / 3L1 3L1 / =M0/13.1
230VAC (N)
32.10 / 3L2 3L2 / =M0/13.1
+24VDC
32.10 / 3L+ 3L+ / =M0/13.1
0VDC
32.10 / 3L- 3L- / =M0/13.1

=G0-A1E8

ANALOGUE INPUT

4.1 4.3

-X4 32

-31R1
499Ω

PE PE
-X4 21 22 31 20 20

-W431
1 2 3 GNYE
ÖSYZ-J 4x0,75 mm² 22 m
TEMPERATURE/DIFFERENTIAL PRESSURE

=E5
AAL
-X4 1 20 2 PE PE PE PE

WH BN
CRUDE GAS
LIYCY 2x0,75 mm²
-W431.1

-31B1 PT100 Θ
0-400°C
4-20mA

TEMPERATURE
CRUDE GAS

32 +KLE/1
DATE 2013-04-29 COMMISSION : LS-71366/07.04.1 Ammann Asphalt TEMPERATURES FILTER G0 A 0091 04 60201857290 = E0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 +
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 33
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

TERMINAL STRIP OVERVIEW AAD_F14_002

TERMINALS
TERMINAL BLOCK FUNCTION TEXT PAGE TERMINAL DIAGRAM
FIRST LATEST SUM PE SUM N TOTAL NUMBER
-X1 CONSUMER 400VAC 21 40 5 0 20 =E0+KLE/11
-X2 CONTROL TERMINAL 230VAC 20 23 2 0 10 =E0+KLE/12
-X3 CONTROL TERMINAL 24VDC 20 28 3 0 17 =E0+KLE/13
-X4 ANALOG VOLTAGES 20 32 6 0 19 =E0+KLE/14
-X5 EXTERNAL VOLTAGE 20 24 1 0 4 =E0+KLE/15

+/33 11
DATE 2013-05-30 COMMISSION : LS-71366/07.04.1 Ammann Asphalt TERMINAL STRIP REVIEW G0 A 0091 04 60201857290 = E0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KLE
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 1
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

TERMINAL DIAGRAM AAD_F13_001

CABLE NAME

CABLE NAME
-W125
-W124
-W122
-W121.2
-W121.1
STRIP
=E0+-X1
CONSUMER 400VAC

H07RN-F 4x1,5 mm²

H07RN-F 4x1,5 mm²

H07RN-F 4x1,5 mm²

H07RN-F 4x35 mm²

H07RN-F 4x35 mm²

CABLE TYPE

CABLE TYPE
CONNECTION

CONNECTION
TERMINAL
FUNCTION TEXT DESTINATION DESCRIPTION DESTINATION DESCRIPTION PAGE / COLUMN

EXHAUSTOR BN -21M1 U1 21 -21K1 2 /21.1


= BK -21M1 V1 22 -21K1 4 /21.2
= GY -21M1 W1 23 -21K1 6 /21.2
= GNYE -21M1 PE 24 /21.2
= BN -21M1 W2 25 -21F1 2 /21.3
= BK -21M1 U2 26 -21F1 4 /21.3
= GY -21M1 V2 27 -21F1 6 /21.3
= GNYE -21M1 PE 28 /21.3
THROTTLE FLAP BN -UC122-X1 1 29 -22K1 2 /24.1
= BK -UC122-X1 2 30 -22K1 4 /24.2
= GY -UC122-X1 3 31 -22K1 6 /24.2
= GNYE -UC122-X1 PE 32 /24.2
CLEANING 1 BN =E5-X1 1 33 -24K1 2 /26.1
= BK =E5-X1 2 34 -24K1 4 /26.2
= GY =E5-X1 3 35 -24K1 6 /26.2
= GNYE =E5-X1 PE 36 /26.2
CLEANING 2 BN =E5-X1 4 37 -25K1 2 /27.1
= BK =E5-X1 5 38 -25K1 4 /27.2
= GY =E5-X1 6 39 -25K1 6 /27.2
= GNYE =E5-X1 PE 40 /27.2

1 12
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt TERMINAL DIAGRAM =E0+-X1 G0 A 0091 04 60201857290 = E0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KLE
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 11
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

TERMINAL DIAGRAM AAD_F13_001

CABLE NAME

CABLE NAME
-W230
STRIP
=E0+-X2
CONTROL TERMINAL 230VAC

H07RN-F 3x1,5 mm²

CABLE TYPE

CABLE TYPE
CONNECTION

CONNECTION
TERMINAL
FUNCTION TEXT DESTINATION DESCRIPTION DESTINATION DESCRIPTION PAGE / COLUMN

230VAC SWITCHED 20 /13.3


SAFETY THERMOSTAT GNYE =E5-X2 PE 20 /32.2
230VAC SWITCHED 21 =T2-42K1 11 /13.1
-21F2 A1
230VAC SWITCHED 21 /13.2
= 21 /13.2
SAFETY THERMOSTAT BN =E5-X2 17 21 -25K11 11 /32.1
=M0-X2 21
230VAC SWITCHED 22 =T2-51K1 A2 /13.2
-21F2 A2
230VAC SWITCHED 22 /13.2
= 22 /13.3
SAFETY THERMOSTAT BU =E5-X2 18 23 -30K1 A1 /32.2

11 13
DATE 2013-05-28 COMMISSION : LS-71366/07.04.1 Ammann Asphalt TERMINAL DIAGRAM =E0+-X2 G0 A 0091 04 60201857290 = E0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KLE
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 12
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

TERMINAL DIAGRAM AAD_F13_001

CABLE NAME

CABLE NAME
-W324
-W322
STRIP
=E0+-X3
CONTROL TERMINAL 24VDC

H07RN-F 7x1,5 mm²

ÖZ-J 5x1 mm²

CABLE TYPE

CABLE TYPE
CONNECTION

CONNECTION
TERMINAL
FUNCTION TEXT DESTINATION DESCRIPTION DESTINATION DESCRIPTION PAGE / COLUMN

0VDC 20 /13.9
CLOSED GNYE -UC122-X3 PE 20 /24.5
PARK POSITION CLEANING 2 GNYE =E5-X3 20 20 /30.3
+24VDC 21 =T2-49K2 11 /13.8
-21K1 43
24VDC CONTROL VOLTAGE 21 /13.8
= 21 /13.8
THROTTLE FLAP 1 -UC122-X3 21 21 -21F2 21 /24.3
-22Q1 1.21
0VDC 22 =T2-27K2 A2 /13.8
-21K11 A2
0VDC 22 /13.8
= 22 /13.9
ERROR 2 -UC122-X3 23 23 =G0-D2E32 3.3 /24.4
= 3 -UC122-X3 14 24 =G0-D2E32 3.2 /24.4
OPEN 4 -UC122-X3 16 25 =G0-D2E32 3.1 /24.4
PARK POSITION CLEANING 1 1 =E5-X3 + 21 -25Q1 1.21 /30.1
-X4 21
PARK POSITION CLEANING 1 2 =E5-X3 - 22 -25K11 A2 /30.2
-X4 22
PARK POSITION CLEANING 1 3 =E5-X3 1 27 =G0-D1E32 8.3 /30.2
PARK POSITION CLEANING 2 4 =E5-X3 2 28 =G0-D1E32 8.4 /30.3

12 14
DATE 2013-05-28 COMMISSION : LS-71366/07.04.1 Ammann Asphalt TERMINAL DIAGRAM =E0+-X3 G0 A 0091 04 60201857290 = E0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KLE
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 13
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

TERMINAL DIAGRAM AAD_F13_001

CABLE NAME

CABLE NAME
-W431
-W423
-W422
-W421
STRIP
=E0+-X4
ANALOG VOLTAGES

ÖSYZ-J 4x0,75 mm²

ÖSYZ-J 3x0,75 mm²

ÖSYZ-J 4x0,75 mm²

H07RN-F 3x1,5 mm²

CABLE TYPE

CABLE TYPE
CONNECTION

CONNECTION
TERMINAL
FUNCTION TEXT DESTINATION DESCRIPTION DESTINATION DESCRIPTION PAGE / COLUMN

EXHAUSTOR GNYE -21M1 PE 20 /21.8


ACTUAL VALUE GNYE -UC122-X3 PE 20 /24.9
= 20 /24.9
NEGATIVE PRESSURE MEASURING MINERAL DRUM GNYE -23B1 20 /25.7
= 20 /25.7
TEMPERATURE CRUDE GAS GNYE =E5-X4 PE 20 /33.4
NEGATIVE PRESSURE MEASURING MINERAL DRUM 1 -23B1 1 21 -22Q1 1.21 /25.7
-24K1 13
TEMPERATURE CRUDE GAS 1 =E5-X4 1 21 -X3 21 /33.2
=M0-X3 21
TEMPERATURE CRUDE GAS 2 =E5-X4 20 22 -X3 22 /33.2
=G0-A1E8 4.3
EXHAUSTOR BN -21M1 T2 23 -21F2 T1 /21.8
= BU -21M1 T1 24 -21F2 T2 /21.8
OPEN 1 -UC122-X3 30 25 /24.8
= 2 -UC122-X3 31 26 -X4 28 /24.8
ACTUAL VALUE 3 -UC122-X3 32 27 =G0-A1E8 3.1 /24.8
-22R2
ACTUAL VALUE -22R2 28 =G0-A1E8 3.3 /24.9
-X4 26
NEGATIVE PRESSURE MEASURING MINERAL DRUM 2 -23B1 2 29 =G0-A1E8 2.1 /25.7
-23R1
NEGATIVE PRESSURE MEASURING MINERAL DRUM -23R1 30 =G0-A1E8 2.3 /25.7
-22K12 A2
-24K11 A2
TEMPERATURE CRUDE GAS 3 =E5-X4 2 31 =G0-A1E8 4.1 /33.3
-31R1
TEMPERATURE CRUDE GAS =G0-A1E8 4.3 32 -31R1 /33.3

13 15
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt TERMINAL DIAGRAM =E0+-X4 G0 A 0091 04 60201857290 = E0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KLE
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 14
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

TERMINAL DIAGRAM AAD_F13_001

CABLE NAME

CABLE NAME
-W522
STRIP
=E0+-X5
EXTERNAL VOLTAGE

ÖZ-J 4x1 mm²

CABLE TYPE

CABLE TYPE
CONNECTION

CONNECTION
TERMINAL
FUNCTION TEXT DESTINATION DESCRIPTION DESTINATION DESCRIPTION PAGE / COLUMN

OPEN GNYE -UC122-X3 PE 20 /24.7


CLOSED 1 -UC122-X3 7 21 -22K12 11 /24.6
= 2 -UC122-X3 9 23 -22K12 14 /24.6
= 3 -UC122-X3 10 24 -22K11 14 /24.7

14 +KAB/1
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt TERMINAL DIAGRAM =E0+-X5 G0 A 0091 04 60201857290 = E0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KLE
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 15
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

CABLE PLAN
1. PAGE PAGE
CABLE TYPE ID CORES CROSS SECTION LENGTH FUNCTION TEXT CIRCUIT DIAGRAM CABLE DIAGRAM

H07RN-F -W121.1 4 35 21 m EXHAUSTOR +/21.1 =E0+KAB/11

-W121.2 4 35 21 m = +/21.3 =E0+KAB/12

-W122 4 1,5 26 m THROTTLE FLAP +/24.1 =E0+KAB/13

-W124 4 1,5 22 m CLEANING 1 +/26.1 =E0+KAB/14

-W124.1 4 1,5 = +/26.1 =E0+KAB/15

-W125 4 1,5 22 m CLEANING 2 +/27.1 =E0+KAB/16

-W125.1 4 1,5 = +/27.1 =E0+KAB/17

-W230 3 1,5 22 m SAFETY THERMOSTAT +/32.2 =E0+KAB/18

ÖZ-J -W230.1 3 1 SAFETY THERMOSTAT +/32.1 =E0+KAB/19

-W322 5 1 26 m LIMIT SWITCH THROTTLE FLAP +/24.3 =E0+KAB/20

H07RN-F -W324 7 1,5 22 m LIMIT SWITCH CLEANING +/30.3 =E0+KAB/21

ÖZ-J -W324.1 3 1 CLEANING 1 +/30.1 =E0+KAB/22

-W324.2 3 1 CLEANING 2 +/30.3 =E0+KAB/23

H07RN-F -W421 3 1,5 21 m PTC SENSOR EXHAUSTOR +/21.8 =E0+KAB/24

ÖSYZ-J -W422 4 0,75 26 m ANALOGUE VALUES THROTTLE FLAP +/24.8 =E0+KAB/25

-W423 3 0,75 26 m NEGATIVE PRESURE +/25.7 =E0+KAB/26

-W431 4 0,75 22 m TEMPERATURE/DIFFERENTIAL PRESSURE +/33.4 =E0+KAB/27

LIYCY -W431.1 2 0,75 CRUDE GAS +/33.2 =E0+KAB/28

ÖZ-J -W522 4 1 26 m THROTTLE FLAP +/24.6 =E0+KAB/29

+KLE/15 11
DATE 2013-05-30 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CABLE PLAN G0 A 0091 04 60201857290 = E0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KAB
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 1
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

CABLE DIAGRAM AAD_F09_002

CABLE NAME =E0+-W121.1 CABLE TYPE H07RN-F


FUNCTION TEXT EXHAUSTOR CORE NO. 4 CROSS SECTION 35 mm² CABLE LENGTH 21 m
DESTINATION DESTINATION
FUNCTION TEXT PAGE / COLUMN CONNECTION CORE CONNECTION PAGE / COLUMN FUNCTION TEXT
DESCRIPTION FROM DESCRIPTION TO

EXHAUSTOR /21.1 -X1 21 BN -21M1 U1 /21.2

= /21.2 -X1 22 BK -21M1 V1 /21.2

= /21.2 -X1 23 GY -21M1 W1 /21.2

= /21.2 -X1 24 GNYE -21M1 PE /21.2

1 12
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CABLE DIAGRAM =E0+-W121.1 G0 A 0091 04 60201857290 = E0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KAB
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 11
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

CABLE DIAGRAM AAD_F09_002

CABLE NAME =E0+-W121.2 CABLE TYPE H07RN-F


FUNCTION TEXT EXHAUSTOR CORE NO. 4 CROSS SECTION 35 mm² CABLE LENGTH 21 m
DESTINATION DESTINATION
FUNCTION TEXT PAGE / COLUMN CONNECTION CORE CONNECTION PAGE / COLUMN FUNCTION TEXT
DESCRIPTION FROM DESCRIPTION TO

EXHAUSTOR /21.3 -X1 25 BN -21M1 W2 /21.2

= /21.3 -X1 26 BK -21M1 U2 /21.2

= /21.3 -X1 27 GY -21M1 V2 /21.2

= /21.3 -X1 28 GNYE -21M1 PE /21.2

11 13
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CABLE DIAGRAM =E0+-W121.2 G0 A 0091 04 60201857290 = E0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KAB
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 12
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

CABLE DIAGRAM AAD_F09_002

CABLE NAME =E0+-W122 CABLE TYPE H07RN-F


FUNCTION TEXT THROTTLE FLAP CORE NO. 4 CROSS SECTION 1,5 mm² CABLE LENGTH 26 m
DESTINATION DESTINATION
FUNCTION TEXT PAGE / COLUMN CONNECTION CORE CONNECTION PAGE / COLUMN FUNCTION TEXT
DESCRIPTION FROM DESCRIPTION TO

THROTTLE FLAP /24.1 -UC122-X1 1 BN -X1 29 /24.1 THROTTLE FLAP

= /24.2 -UC122-X1 2 BK -X1 30 /24.2 =

= /24.2 -UC122-X1 3 GY -X1 31 /24.2 =

= /24.2 -UC122-X1 PE GNYE -X1 32 /24.2 =

12 14
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CABLE DIAGRAM =E0+-W122 G0 A 0091 04 60201857290 = E0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KAB
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 13
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

CABLE DIAGRAM AAD_F09_002

CABLE NAME =E0+-W124 CABLE TYPE H07RN-F


FUNCTION TEXT CLEANING 1 CORE NO. 4 CROSS SECTION 1,5 mm² CABLE LENGTH 22 m
DESTINATION DESTINATION
FUNCTION TEXT PAGE / COLUMN CONNECTION CORE CONNECTION PAGE / COLUMN FUNCTION TEXT
DESCRIPTION FROM DESCRIPTION TO

CLEANING 1 /26.1 -X1 33 BN =E5-X1 1 /26.1 CLEANING 1

= /26.2 -X1 34 BK =E5-X1 2 /26.2 =

= /26.2 -X1 35 GY =E5-X1 3 /26.2 =

= /26.2 -X1 36 GNYE =E5-X1 PE /26.2 =

13 15
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CABLE DIAGRAM =E0+-W124 G0 A 0091 04 60201857290 = E0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KAB
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 14
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

CABLE DIAGRAM AAD_F09_002

CABLE NAME =E0+-W124.1 CABLE TYPE H07RN-F


FUNCTION TEXT CLEANING 1 CORE NO. 4 CROSS SECTION 1,5 mm² CABLE LENGTH
DESTINATION DESTINATION
FUNCTION TEXT PAGE / COLUMN CONNECTION CORE CONNECTION PAGE / COLUMN FUNCTION TEXT
DESCRIPTION FROM DESCRIPTION TO

CLEANING 1 /26.2 =E5-X1 2 BK -24M1 V1 /26.1 CLEANING 1

= /26.1 =E5-X1 1 BN -24M1 U1 /26.1 =

= /26.2 =E5-X1 PE GNYE -24M1 PE /26.1 =

= /26.2 =E5-X1 3 GY -24M1 W1 /26.1 =

14 16
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CABLE DIAGRAM =E0+-W124.1 G0 A 0091 04 60201857290 = E0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KAB
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 15
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

CABLE DIAGRAM AAD_F09_002

CABLE NAME =E0+-W125 CABLE TYPE H07RN-F


FUNCTION TEXT CLEANING 2 CORE NO. 4 CROSS SECTION 1,5 mm² CABLE LENGTH 22 m
DESTINATION DESTINATION
FUNCTION TEXT PAGE / COLUMN CONNECTION CORE CONNECTION PAGE / COLUMN FUNCTION TEXT
DESCRIPTION FROM DESCRIPTION TO

CLEANING 2 /27.1 -X1 37 BN =E5-X1 4 /27.1 CLEANING 2

= /27.2 -X1 38 BK =E5-X1 5 /27.2 =

= /27.2 -X1 39 GY =E5-X1 6 /27.2 =

= /27.2 -X1 40 GNYE =E5-X1 PE /27.2 =

15 17
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CABLE DIAGRAM =E0+-W125 G0 A 0091 04 60201857290 = E0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KAB
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 16
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

CABLE DIAGRAM AAD_F09_002

CABLE NAME =E0+-W125.1 CABLE TYPE H07RN-F


FUNCTION TEXT CLEANING 2 CORE NO. 4 CROSS SECTION 1,5 mm² CABLE LENGTH
DESTINATION DESTINATION
FUNCTION TEXT PAGE / COLUMN CONNECTION CORE CONNECTION PAGE / COLUMN FUNCTION TEXT
DESCRIPTION FROM DESCRIPTION TO

CLEANING 2 /27.2 =E5-X1 5 BK -25M1 V1 /27.1 CLEANING 2

= /27.1 =E5-X1 4 BN -25M1 U1 /27.1 =

= /27.2 =E5-X1 PE GNYE -25M1 PE /27.1 =

= /27.2 =E5-X1 6 GY -25M1 W1 /27.1 =

16 18
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CABLE DIAGRAM =E0+-W125.1 G0 A 0091 04 60201857290 = E0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KAB
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 17
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

CABLE DIAGRAM AAD_F09_002

CABLE NAME =E0+-W230 CABLE TYPE H07RN-F


FUNCTION TEXT SAFETY THERMOSTAT CORE NO. 3 CROSS SECTION 1,5 mm² CABLE LENGTH 22 m
DESTINATION DESTINATION
FUNCTION TEXT PAGE / COLUMN CONNECTION CORE CONNECTION PAGE / COLUMN FUNCTION TEXT
DESCRIPTION FROM DESCRIPTION TO

SAFETY THERMOSTAT /32.1 -X2 21 BN =E5-X2 17 /32.1 SAFETY THERMOSTAT

= /32.2 -X2 23 BU =E5-X2 18 /32.2 =

= /32.2 -X2 20 GNYE =E5-X2 PE /32.2 =

17 19
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CABLE DIAGRAM =E0+-W230 G0 A 0091 04 60201857290 = E0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KAB
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 18
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

CABLE DIAGRAM AAD_F09_002

CABLE NAME =E0+-W230.1 CABLE TYPE ÖZ-J


FUNCTION TEXT SAFETY THERMOSTAT CORE NO. 3 CROSS SECTION 1 mm² CABLE LENGTH
DESTINATION DESTINATION
FUNCTION TEXT PAGE / COLUMN CONNECTION CORE CONNECTION PAGE / COLUMN FUNCTION TEXT
DESCRIPTION FROM DESCRIPTION TO

SAFETY THERMOSTAT /32.1 =E5-X2 17 1 -30S0 21 /32.1 SAFETY THERMOSTAT

= /32.2 =E5-X2 18 2 -30S0 22 /32.1 =

= /32.2 =E5-X2 PE GNYE -30S0 PE /32.2

18 20
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CABLE DIAGRAM =E0+-W230.1 G0 A 0091 04 60201857290 = E0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KAB
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 19
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

CABLE DIAGRAM AAD_F09_002

CABLE NAME =E0+-W322 CABLE TYPE ÖZ-J


FUNCTION TEXT LIMIT SWITCH THROTTLE FLAP CORE NO. 5 CROSS SECTION 1 mm² CABLE LENGTH 26 m
DESTINATION DESTINATION
FUNCTION TEXT PAGE / COLUMN CONNECTION CORE CONNECTION PAGE / COLUMN FUNCTION TEXT
DESCRIPTION FROM DESCRIPTION TO

THROTTLE FLAP /24.3 -UC122-X3 21 1 -X3 21 /24.3 THROTTLE FLAP

ERROR /24.4 -UC122-X3 23 2 -X3 23 /24.4 ERROR

= /24.4 -UC122-X3 14 3 -X3 24 /24.4 =

OPEN /24.4 -UC122-X3 16 4 -X3 25 /24.4 OPEN

CLOSED /24.5 -UC122-X3 PE GNYE -X3 20 /24.5 CLOSED

19 21
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CABLE DIAGRAM =E0+-W322 G0 A 0091 04 60201857290 = E0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KAB
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 20
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

CABLE DIAGRAM AAD_F09_002

CABLE NAME =E0+-W324 CABLE TYPE H07RN-F


FUNCTION TEXT LIMIT SWITCH CLEANING CORE NO. 7 CROSS SECTION 1,5 mm² CABLE LENGTH 22 m
DESTINATION DESTINATION
FUNCTION TEXT PAGE / COLUMN CONNECTION CORE CONNECTION PAGE / COLUMN FUNCTION TEXT
DESCRIPTION FROM DESCRIPTION TO

PARK POSITION CLEANING 1 /30.1 -X3 21 1 =E5-X3 + /30.1 PARK POSITION CLEANING 1

= /30.2 -X3 22 2 =E5-X3 - /30.2 =

= /30.2 -X3 27 3 =E5-X3 1 /30.2 =

PARK POSITION CLEANING 2 /30.3 -X3 28 4 =E5-X3 2 /30.3 PARK POSITION CLEANING 2

PARK POSITION CLEANING 2 /30.3 -X3 20 GNYE =E5-X3 20 /30.3 PARK POSITION CLEANING 2

20 22
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CABLE DIAGRAM =E0+-W324 G0 A 0091 04 60201857290 = E0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KAB
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 21
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

CABLE DIAGRAM AAD_F09_002

CABLE NAME =E0+-W324.1 CABLE TYPE ÖZ-J


FUNCTION TEXT CLEANING 1 CORE NO. 3 CROSS SECTION 1 mm² CABLE LENGTH
DESTINATION DESTINATION
FUNCTION TEXT PAGE / COLUMN CONNECTION CORE CONNECTION PAGE / COLUMN FUNCTION TEXT
DESCRIPTION FROM DESCRIPTION TO

PARK POSITION CLEANING 1 /30.1 =E5-X3 + 1 -24B1 1 /30.1 PARK POSITION CLEANING 1

= /30.2 =E5-X3 1 2 -24B1 4 /30.1 =

GNYE

21 23
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CABLE DIAGRAM =E0+-W324.1 G0 A 0091 04 60201857290 = E0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KAB
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 22
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

CABLE DIAGRAM AAD_F09_002

CABLE NAME =E0+-W324.2 CABLE TYPE ÖZ-J


FUNCTION TEXT CLEANING 2 CORE NO. 3 CROSS SECTION 1 mm² CABLE LENGTH
DESTINATION DESTINATION
FUNCTION TEXT PAGE / COLUMN CONNECTION CORE CONNECTION PAGE / COLUMN FUNCTION TEXT
DESCRIPTION FROM DESCRIPTION TO

PARK POSITION CLEANING 2 /30.3 =E5-X3 + 1 -24B2 1 /30.3 PARK POSITION CLEANING 2

= /30.3 =E5-X3 2 2 -24B2 4 /30.3 =

GNYE

22 24
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CABLE DIAGRAM =E0+-W324.2 G0 A 0091 04 60201857290 = E0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KAB
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 23
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

CABLE DIAGRAM AAD_F09_002

CABLE NAME =E0+-W421 CABLE TYPE H07RN-F


FUNCTION TEXT PTC SENSOR EXHAUSTOR CORE NO. 3 CROSS SECTION 1,5 mm² CABLE LENGTH 21 m
DESTINATION DESTINATION
FUNCTION TEXT PAGE / COLUMN CONNECTION CORE CONNECTION PAGE / COLUMN FUNCTION TEXT
DESCRIPTION FROM DESCRIPTION TO

EXHAUSTOR /21.8 -X4 23 BN -21M1 T2 /21.2

= /21.8 -X4 24 BU -21M1 T1 /21.2

= /21.8 -X4 20 GNYE -21M1 PE /21.8

23 25
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CABLE DIAGRAM =E0+-W421 G0 A 0091 04 60201857290 = E0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KAB
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 24
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

CABLE DIAGRAM AAD_F09_002

CABLE NAME =E0+-W422 CABLE TYPE ÖSYZ-J


FUNCTION TEXT ANALOGUE VALUES THROTTLE FLAP CORE NO. 4 CROSS SECTION 0,75 mm² CABLE LENGTH 26 m
DESTINATION DESTINATION
FUNCTION TEXT PAGE / COLUMN CONNECTION CORE CONNECTION PAGE / COLUMN FUNCTION TEXT
DESCRIPTION FROM DESCRIPTION TO

OPEN /24.8 -UC122-X3 30 1 -X4 25 /24.8 OPEN

= /24.8 -UC122-X3 31 2 -X4 26 /24.8 =

ACTUAL VALUE /24.8 -UC122-X3 32 3 -X4 27 /24.8 ACTUAL VALUE

= /24.9 -UC122-X3 PE GNYE -X4 20 /24.9 =

SH

24 26
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CABLE DIAGRAM =E0+-W422 G0 A 0091 04 60201857290 = E0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KAB
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 25
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

CABLE DIAGRAM AAD_F09_002

CABLE NAME =E0+-W423 CABLE TYPE ÖSYZ-J


FUNCTION TEXT NEGATIVE PRESURE CORE NO. 3 CROSS SECTION 0,75 mm² CABLE LENGTH 26 m
DESTINATION DESTINATION
FUNCTION TEXT PAGE / COLUMN CONNECTION CORE CONNECTION PAGE / COLUMN FUNCTION TEXT
DESCRIPTION FROM DESCRIPTION TO
NEGATIVE PRESSURE MEASURING NEGATIVE PRESSURE MEASURING
/25.7 -X4 21 1 -23B1 1 /25.7
MINERAL DRUM MINERAL DRUM
= /25.7 -X4 29 2 -23B1 2 /25.7 =

= /25.7 -X4 20 GNYE -23B1 /25.7

25 27
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CABLE DIAGRAM =E0+-W423 G0 A 0091 04 60201857290 = E0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KAB
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 26
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

CABLE DIAGRAM AAD_F09_002

CABLE NAME =E0+-W431 CABLE TYPE ÖSYZ-J


FUNCTION TEXT TEMPERATURE/DIFFERENTIAL PRESSURE CORE NO. 4 CROSS SECTION 0,75 mm² CABLE LENGTH 22 m
DESTINATION DESTINATION
FUNCTION TEXT PAGE / COLUMN CONNECTION CORE CONNECTION PAGE / COLUMN FUNCTION TEXT
DESCRIPTION FROM DESCRIPTION TO

TEMPERATURE CRUDE GAS /33.2 -X4 21 1 =E5-X4 1 /33.2 TEMPERATURE CRUDE GAS

= /33.2 -X4 22 2 =E5-X4 20 /33.2 =

= /33.3 -X4 31 3 =E5-X4 2 /33.3 =

= /33.4 -X4 20 GNYE =E5-X4 PE /33.4 =

SH

26 28
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CABLE DIAGRAM =E0+-W431 G0 A 0091 04 60201857290 = E0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KAB
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 27
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

CABLE DIAGRAM AAD_F09_002

CABLE NAME =E0+-W431.1 CABLE TYPE LIYCY


FUNCTION TEXT CRUDE GAS CORE NO. 2 CROSS SECTION 0,75 mm² CABLE LENGTH
DESTINATION DESTINATION
FUNCTION TEXT PAGE / COLUMN CONNECTION CORE CONNECTION PAGE / COLUMN FUNCTION TEXT
DESCRIPTION FROM DESCRIPTION TO

TEMPERATURE CRUDE GAS /33.2 =E5-X4 1 WH -31B1 /33.2 TEMPERATURE CRUDE GAS

= /33.3 =E5-X4 2 BN -31B1 /33.2 =

SH

27 29
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CABLE DIAGRAM =E0+-W431.1 G0 A 0091 04 60201857290 = E0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KAB
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 28
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

CABLE DIAGRAM AAD_F09_002

CABLE NAME =E0+-W522 CABLE TYPE ÖZ-J


FUNCTION TEXT THROTTLE FLAP CORE NO. 4 CROSS SECTION 1 mm² CABLE LENGTH 26 m
DESTINATION DESTINATION
FUNCTION TEXT PAGE / COLUMN CONNECTION CORE CONNECTION PAGE / COLUMN FUNCTION TEXT
DESCRIPTION FROM DESCRIPTION TO

CLOSED /24.6 -UC122-X3 7 1 -X5 21 /24.6 CLOSED

= /24.6 -UC122-X3 9 2 -X5 23 /24.6 =

= /24.7 -UC122-X3 10 3 -X5 24 /24.7 =

OPEN /24.7 -UC122-X3 PE GNYE -X5 20 /24.7 OPEN

28 +PR/1
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CABLE DIAGRAM =E0+-W522 G0 A 0091 04 60201857290 = E0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KAB
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 29
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

AAD_Pruef2
CIRCUIT OVERVIEW R iso PROTECTIVE CONDUCTOR Z Schl [Ω] RCD(FI)

CIRCUIT (FUNCTION TEXT) CABLE NAME CABLE TYPE LENGTH


[MΩ] IPE [mA] R PE [Ω] I K [A] I N [A] IΔN [mA] UB [V] + /-
EXHAUSTOR -W121.1 H07RN-F 4x35 mm² 21 m

= -W121.2 H07RN-F 4x35 mm² 21 m

THROTTLE FLAP -W122 H07RN-F 4x1,5 mm² 26 m

CLEANING 1 -W124 H07RN-F 4x1,5 mm² 22 m

= -W124.1 H07RN-F 4x1,5 mm²

CLEANING 2 -W125 H07RN-F 4x1,5 mm² 22 m

= -W125.1 H07RN-F 4x1,5 mm²

SAFETY THERMOSTAT -W230 H07RN-F 3x1,5 mm² 22 m

= -W230.1 ÖZ-J 3x1 mm²

LIMIT SWITCH THROTTLE FLAP -W322 ÖZ-J 5x1 mm² 26 m

LIMIT SWITCH CLEANING -W324 H07RN-F 7x1,5 mm² 22 m

CLEANING 1 -W324.1 ÖZ-J 3x1 mm²

CLEANING 2 -W324.2 ÖZ-J 3x1 mm²

PTC SENSOR EXHAUSTOR -W421 H07RN-F 3x1,5 mm² 21 m

ANALOGUE VALUES THROTTLE FLAP -W422 ÖSYZ-J 4x0,75 mm² 26 m

NEGATIVE PRESURE -W423 ÖSYZ-J 3x0,75 mm² 26 m

TEMPERATURE/DIFFERENTIAL PRESSURE -W431 ÖSYZ-J 4x0,75 mm² 22 m

CRUDE GAS -W431.1 LIYCY 2x0,75 mm²

THROTTLE FLAP -W522 ÖZ-J 4x1 mm² 26 m

+KAB/29 2
DATE 2013-05-30 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CIRCUIT OVERVIEW G0 A 0091 04 60201857290 = E0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + PR
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 1
Kunde:
CLIENT.
Kom-Nr.:
COM.-NO.: LS-71366/07.04.1 ASPHALT MIXING PLANT
Schaltschrank:
SWITCH PANEL: 2400 x 1600 x 500mm Prime 140
Schaltplan-Nr.:
CIRCUIT DIAGRAM-NO.: G0 A 0091 04 Bereich: Porto Alegre
AREA:
Schutzart :
PROTECTION TYPE: RCD (FI)
Betriebsspannung:
Ammann do Brasil
OPERATING VOLTAGE: 3Ph~ / 400VAC / 60Hz Sitio do Sobrado
Steuerspannung:
CONTROL VOLTAGE: 24VDC / 230VAC 94180-452 Gravataí -RS-Brasil
Baujahr : Brasilien
YEAR OF MANUFACTURE: 2013
Prüfprotokoll EN 60204 (VDE 0113) TEST REPORT EN 60204 (VDE0113)
Prüfungsgrund: Erstprüfung Wiederholungsprüfung Sonstiges:
CAUSE OF INSPECTION: INITIAL INSPECTION REPEATED INSPECTION OTHER:
Netz:
TN-C TN-S TT IT-SYSTEM 230V 400V ........V In(Gesamt):
NET: 328 A
I (TOTAL):
Frequenz:
...... L N PEN PE
FREQUENCY .........Hz .........
Prüfung Dokumentation: vorhanden komplett Übereinstimmend mit der Installation
TEST DOCUMENTATION: EXISTING COMPLETE IN CONFORMITY TO THE INSTALLATION
Anmerkung:
NOTE:
Besichtigung:
SURVEY:
Betriebsmittel können den Einflüssen am Verwendungsort standhalten PE, L und N nicht verwechselt
OPERATING EQUIPMENT IS ABLE TO RESIST LOCAL INFLUENCES PE,L AND N ARE NOT CONFOUNDED
Alle Schutzleiter gegen Selbstlockern und Korrosion gesichert Schutz durch Isolierung aller aktiven Teile
ALL PROTECTIVE CONDUCTORS ARE PROTECTED AGAINST SELF-SLACKERING AND CORROSION PROTECTION BY ISOLATION OF ALL ACTIVE PARTS
Keine erkennbaren Schäden Sonstiges:
NO APPARENT DAMAGES OTHER:
Kennzeichnungen, Anschlussstellen und eventuelle Trennstellen in Ordnung
EQUIPMENT IDENTIFICATIONS, CONNECTION POINTS AND ANY DISCONNECTION POINTS ARE OKAY
Messung:
MEASUREMENT. Schlechtester Messwert Prüfung in Ordnung
WORST MEASURED VALUE TEST OKAY
Messgeräte entsprechen EN 61557 (VDE 0413)
MEASURING INSTRUMENTS AGREE WITH EN 61557 (VDE 0413)
Durchgängigkeit des Schutzleitersystems
(Widerstandsmessung mit Prüfstrom mind. 0,2A, max. 10A bzw. Schleifenimpedanzmessung)
CONDUCTIVITY OF THE PROTECTIVE CONDUCTOR SYSTEM
(RESISTANCE MEASUREMENT WITH TESTING CURRENT OF MIN.0,2A; MAX.10A; RESPECTIVELY LOOP IMPEDANCE MEASUREMENT)
Isolationswiderstandsmessung
INSULATION RESISTANCE MEASUREMENT
Spannungsprüfung
VOLTAGE TEST
Restspannngsprüfung (max. 60V nach 5s / 1s; sonst Warnhinweis anbringen)
RESIDUAL VOLTAGE TEST (MAX.60V AFTER 5s/1s, OTHERWISE WARNING INSTRUCTION HAS TO PUT UP)
Sonstiges:
OTHER:
Not-Aus Druckwächter, Endschalter, RCD(FI), Sicherheitstemperaturbegrenzer, etc.
Erprobung: EMERGENCY OFF MANOSTAT, LIMIT SWITCH, RCD(FI), SAFETY TEMPERATURE LIMITER, ETC.
TEST: Verriegelung Meldeleuchten, Anzeigen Funktionsprüfung Sonstiges:
LOCKING SIGNAL LAMPS, INDICATIONS FUNCTION TEST OTHER:
Bemerkungen:
REMARKS:
Prüfung nach EN60204 (VDE0113) durchgeführt Anlage / Installation funktionsfähig übernommen
TEST HAS BEEN DONE ACCORDING TO STANDARD EN 60204 (VDE 0113) THE PLANT / INSTALLATION HAS BEEN TAKEN OVER IN WORKING CONDITIONS
Ort / Datum: LOCATION / DATE: Unterschrift des Prüfers SIGNATURE OF RESPONSIBLE CONTROLLER Datum: DATE: Unterschrift des Auftraggebers SIGNATURE OF RESPONSIBLE CUSTOMER
Hinweise zum Ausfüllen: positive Prüfung negative Prüfung Bitte Nicht-Zutreffendes durchstreichen
-

+
INDICATION NOTE TO FILL OUT POSITIVE INSPECTION NEGATIVE INSPECTION PLEASE CROSS-OUT WHAT IS NOT APPLICABLE
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

-25U1

-25U2
+24V OUT 12 /29.7 +24VDC +24V -X23.1 /29.1 +24VDC

+24V OUT 13 GND -X23.2 /29.2 0VDC

D IN 18 GND -X23.3

D IN 19 CHASSIS -X23.4 /29.2 PE

COM D IN 20
DIN 4 -X24:1
D IN/OUT 27
DIN 3 -X24:2
D IN/OUT 29
DIN 2 -X24:3
D IN 32

Danfoss - MCA110
GND -X24:4
D IN 33

D IN 37 /29.8 CONTROL RELEASE DIN 1 -X25:1

DOUT 2 -X25:2
RELAY 1 01

DOUT 1 -X25:3
RELAY 1S 02

GND -X25:4
RELAY 1Ö 03

RELAY 2 04

RELAY 2S 05

RELAY 2Ö 06

COM A OUT 39
Danfoss - FC302

A OUT 42

+10V OUT 50 /29.5 +10VDC

A IN (S201) 53

A IN (S202) 54 /29.5 ENGINE TOO HOT

COM A IN 55

=E0+PR/2 13
DATE 2012-12-07 COMMISSION : LS-71366/07.04.1 Ammann Asphalt MODULAR FREQUENCY G0 A 0091 04 60201857290 = M0
proc. UGR
CLIENT : Ammann do Brasil CONVERTER BITUMEN SWITCH PANEL G0 +
Appr
ASPHALT MIXING PLANT D-31061 Alfeld PUMP CAD: 71366_G0
MODIFICATIONDATE NAME origin \\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 5
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

230VAC (P)
=E0/33.10 / 3L1 3L1 / 22.1
230VAC (N)
=E0/33.10 / 3L2 3L2 / 22.1
230VAC (P) UNSWITCHED
230VAC (N) UNSWITCHED
+24VDC
=E0/33.10 / 3L+ 3L+ / 21.1
0VDC
=E0/33.10 / 3L- 3L- / 21.1

COVER
PE PE
TERMINALS!
-X2 21 21 21 22 22 22 20 -X3 21 21 21 22 22 22 20

230VAC SWITCHED 230VAC UNSWITCHED 24VDC +24VDC 0VDC


INTERBUS-S INTERBUS-S
24VDC
CONTROL VOLTAGE

5 21
DATE 2013-02-20 COMMISSION : LS-71366/07.04.1 Ammann Asphalt FEED CONTROL G0 A 0091 04 60201857290 = M0
proc. PBR
CLIENT : Ammann do Brasil VOLTAGE SWITCH PANEL G0 +
Appr
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 13
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

+24VDC
13.10 / 3L+ 3L+ / 22.1
0VDC
13.10 / 3L- 3L- / 22.1

2L1
400V +/-5% 3Ph 50Hz 2L1 2L1
400V +/-5% 3Ph 50Hz 2L1
2L2 2L2 2L2 2L2
2L3 2L3 2L3 2L3

1 3 5 1 3 5 1 3 5 1 3 5
-21Q1 -21Q2 -22Q1 -22Q2
/23.1 /23.1 /23.1 /23.1
/24.4 I> I> I> /24.5 I> I> I> /24.6 I> I> I> /24.6 I> I> I>
17A ge 2 4 6 17A ge 2 4 6 17A ge 2 4 6 17A ge 2 4 6
CLASS 10 CLASS 10 CLASS 10 CLASS 10
PKE32/XTU-32 1 3 5 PKE32/XTU-32 1 3 5 PKE32/XTU-32 1 3 5 PKE32/XTU-32 1 3 5
-21K1 -21K2 -22K1 -22K2
/23.1 2 4 6 /23.5 2 4 6 /23.2 2 4 6 /23.6 2 4 6

PE
k k
PE
-21T1 -22T1
100/5A l 100/5A l

3 4
22.5 22.6

1 3 5 1 3 5
-21K3 -22K3
/23.3 2 4 6 /23.4 2 4 6
2 1
22.5 22.5

4 mm² 4 mm² 4 mm² 4 mm²

PE PE PE PE
-X1 21 22 23 24 28 25 26 27 -X1 29 30 31 32 36 33 34 35

-W121.2 -W122.2
-W121.1 GNYE BN BK GY -W122.1 GNYE BN BK GY
H07RN-F H07RN-F
BN BK GY GNYE BN BK GY GNYE
H07RN-F 4x4 mm² 23 m H07RN-F 4x4 mm² 23 m
4x4 mm² 23 m MIXER MOTOR 1 4x4 mm² 23 m MIXER MOTOR 2
U1 V1 W1 PE U1 V1 W1 PE
MIXER MOTOR 1 MIXER MOTOR 2
-21M1
M -22M1
M
15 KW 3~ 15 KW 3~
29,3A V2 U2 W2 29,3A V2 U2 W2

MIXER MOTOR 1 MIXER MOTOR 2


13 22
DATE 2013-01-22 COMMISSION : LS-71366/07.04.1 Ammann Asphalt 881 G0 A 0091 04 60201857290 = M0
proc. UGR
CLIENT : Ammann do Brasil MIXER SWITCH PANEL G0 +
Appr
ASPHALT MIXING PLANT D-31061 Alfeld 15KW 31A CAD: 71366_G0
MODIFICATIONDATE NAME origin \\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 21
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

230VAC (P)
13.10 / 3L1 3L1 / 23.1
230VAC (N)
13.10 / 3L2 3L2 / 23.1
+24VDC
21.10 / 3L+ 3L+ / 23.1
0VDC
21.10 / 3L- 3L- / 23.1
400V +/-5% 3Ph 50Hz =G0-A4E2
2L1 2L1
-X4 21 22 2L2 2L2 ANALOGUE
2L3 2L3 INPUT
1.1 1.3
1 3 5
-21Q3
4 A ge
CLASS 10 I> I> I>
PKE12/XTU-4 2 4 6

-X4 23

-21R1
21.1 21.1 21.10 21.10 499Ω
1 2 3 4
-X4 24

PE PE
-X4 1 2 3 4 -X1 37 38 39 40 -X2 22 21 -X4 23 24 20

ÖZ-J ÖZ-J ÖZ-J ÖZ-J ÖZYZ-J


3x2,5mm² 3x2,5mm² 4x1mm² 3x1mm² 3x0,75mm²

-21A1
3 1 9 7 2 5 8 PE 14 15 31+ 30-
ANALOGUE
OUTPUT
0-20MA
1= 3Lu Menü AnA1
3= 400V Src = P
ACTIVE POWER METER 4= 400V Lo = 0
5= 100A Hi = 99.9
6= 5A SiG = 0-20mA

CAPACITY
ACTIVE POWER METER
MIXER

21 23
DATE 2013-05-30 COMMISSION : LS-71366/07.04.1 Ammann Asphalt MEASUREMENT G0 A 0091 04 60201857290 = M0
proc. UGR
CLIENT : Ammann do Brasil CAPACITY MIXER SWITCH PANEL G0 +
Appr
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 22
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

230VAC (P)
22.10 / 3L1 3L1 / 24.1
+24VDC
22.10 / 3L+ 3L+ / 24.1
11
-21K11
/23.8 14

1.13 -D2A32 3.4 4.1


-21Q1
/21.2 1.14
OFF = 0 0
1.13
-21Q2 STAR = 1 0
/21.4 1.14
DELTA = 1 1
1.13
-22Q1
/21.6 1.14

1.13 =G0-D2A32
-22Q2
/21.8 1.14 OUTPUT OUTPUT

3.4 4.1

43 43 11
-21K3 -21K1 -21K12
/23.3 44 /23.1 44 /23.9 12 14

43 43 21
-22K3 -22K1 -21K2 21
/23.4 44 /23.2 44 /23.5 22 -21K3
/23.3 22
21
-22K2 21
/23.6 22 -22K3
/23.4 22

A1 A1 A1 A1 A1 A1 A1 A1
-21K1 -22K1 -21K3 -22K3 -21K2 -22K2 -21K11 -21K12
PKE32 A2 PKE32 A2 M12-10-22 A2 M12-10-22 A2 PKE32 A2 PKE32 A2 38.51 A2 38.51 A2
230VAC 230VAC 230VAC 230VAC 230VAC 230VAC 24VDC 24VDC

230VAC (N)
22.10 / 3L2 3L2 / 24.1
0VDC
22.10 / 3L- 3L- / 24.1

MAIN STAR DELTA MIXER


CONTACTOR CONTACTOR CONTACTOR STAR/NET ON

1 2 /21.2 1 2 /21.6 1 2 /21.5 1 2 /21.9 1 2 /21.4 1 2 /21.8 11 14 /23.1 14


3 4 /21.3 3 4 /21.7 3 4 /21.5 3 4 /21.9 3 4 /21.4 3 4 /21.8 12 11 /23.3
5 6 /21.3 5 6 /21.7 5 6 /21.5 5 6 /21.9 5 6 /21.4 5 6 /21.8
13 14 /24.2 13 14 /24.2 21 22 /23.5 21 22 /23.5 13 14 /24.3 13 14 /24.3
43 44 /23.2 43 44 /23.2 43 44 /23.1 43 44 /23.1 21 22 /23.3 21 22 /23.3

22 24
DATE 2013-01-03 COMMISSION : LS-71366/07.04.1 Ammann Asphalt 881 G0 A 0091 04 60201857290 = M0
proc. UGR
CLIENT : Ammann do Brasil MIXER SWITCH PANEL G0 +
Appr
ASPHALT MIXING PLANT D-31061 Alfeld CONTROL PART 1 CAD: 71366_G0
MODIFICATIONDATE NAME origin \\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 23
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

230VAC (P)
23.10 / 3L1 3L1 / 25.1
+24VDC
23.10 / 3L+ 3L+ / 25.1

13 13 1.21 1.21 1.21 1.21


-21K1 -21K2 -21Q1 -21Q2 -22Q1 -22Q2
/23.1 14 /23.5 14 /21.2 1.22 /21.4 1.22 /21.6 1.22 /21.8 1.22

13 13
-22K1 -22K2
/23.2 14 /23.6 14

3.4 4.1 4.2

INPUT INPUT INPUT

=G0-D2E32

230VAC (N)
23.10 / 3L2 3L2 / 25.1
0VDC
23.10 / 3L- 3L- / 25.1

NET ON DELTA ON ERROR

23 25
DATE 2012-12-07 COMMISSION : LS-71366/07.04.1 Ammann Asphalt MIXER G0 A 0091 04 60201857290 = M0
proc. UGR
CLIENT : Ammann do Brasil CONTROL PART 2 SWITCH PANEL G0 +
Appr
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 24
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

230VAC (P)
24.10 / 3L1 3L1 / 26.1
230VAC (N)
24.10 / 3L2 3L2 / 26.1
+24VDC
24.10 / 3L+ 3L+ / 26.1
0VDC
24.10 / 3L- 3L- / 26.1

=G0-D2E32 =G0-D2A32

INPUT INPUT OUTPUT OUTPUT

4.3 4.4 4.3 4.4

PE PE
-X3 21 24 -X3 21 25 26 22 20 27 22 20

BN WH BN WH 1 2 GNYE 1 2 GNYE
COUNTER
LIYCY 4x0,5 mm² 21 m
-W315.1

MIXER FLAP CLOSED


LIYCY 4x0,5 mm² 21 m
-W315.2

FLAP OPEN
MIXER
ÖZ-J 3x1 mm² 23 m
-W315.3

FLAP CLOSED
MIXER
ÖZ-J 3x1 mm² 23 m
-W315.4
1 1
1 2 PE 1 2 PE
-15B1 -15B2
MIXER FLAP COUNTER MIXER FLAP CLOSED -15Y1 -15Y2
4 4

MIXER-FLAP MIXER-FLAP MIXER-FLAP MIXER-FLAP


COUNTER CLOSED OPEN CLOSED

24 26
DATE 2013-04-29 COMMISSION : LS-71366/07.04.1 Ammann Asphalt 883 / 884 G0 A 0091 04 60201857290 = M0
proc. UGR
CLIENT : Ammann do Brasil MIXER OUTLET SWITCH PANEL G0 +
Appr
ASPHALT MIXING PLANT D-31061 Alfeld LIMIT SWITCH/VALVE CAD: 71366_G0
MODIFICATIONDATE NAME origin \\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 25
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

230VAC (P)
25.10 / 3L1 3L1 / 27.1
230VAC (N)
25.10 / 3L2 3L2 / 27.1
+24VDC
25.10 / 3L+ 3L+ / 27.1
0VDC
25.10 / 3L- 3L- / 27.1

=G0-A1E8

ANALOGUE INPUT

6.1 6.3

-X4 28

-12R1
499Ω

PE PE
-X4 21 27 20 20

-W412
1 2 GNYE
ÖSYZ-J 3x0,75 mm² 20 m
COMPRESSED AIR

-12B1 1 2 PE

-12B1
MIDAS 1001

COMPRESSED AIR

25 27
DATE 2013-04-29 COMMISSION : LS-71366/07.04.1 Ammann Asphalt 891 G0 A 0091 04 60201857290 = M0
proc. UGR
CLIENT : Ammann do Brasil COMPRESSED AIR SWITCH PANEL G0 +
Appr
ASPHALT MIXING PLANT D-31061 Alfeld SENSOR SHUT-OFF VALVE CAD: 71366_G0
MODIFICATIONDATE NAME origin \\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 26
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

230VAC (P)
26.10 / 3L1 3L1 / 29.8
230VAC (N)
26.10 / 3L2 3L2 / 29.9
+24VDC
26.10 / 3L+ 3L+ / 29.8
0VDC
26.10 / 3L- 3L- / 29.9

=G0-A1E8 =G0-D2A32

ANALOGUE INPUT OUTPUT

5.1 5.3 4.2

PE PE
-X4 21 22 29 30 20 -X3 23 22 -X4 20

-W415
1 2 3 4 GNYE 5 6
ÖSYZ-J 7x0,75 mm² 19 m
INFRA-RED MEASUREMENT
-UC415
PE PE
-X4 21 22 23 24 25 20 -X3 23 22 20

-W415.1
FIXED 1 2 GNYE
ÖZ-J 3x1 mm² 1 m
CABLE
AIR SCAVENGING
MIXER OUTLET
1 2 PE

-15A1 -15Y5
thermoMETER CS WH BN YE GN BK
0-400°C
24VDC 0-10V
0-10V

INFRA-RED MEASUREMENT AIR SCAVENGING


MIXER OUTLET MIXER OUTLET

26 29
DATE 2013-04-29 COMMISSION : LS-71366/07.04.1 Ammann Asphalt 885 G0 A 0091 04 60201857290 = M0
proc. UGR
CLIENT : Ammann do Brasil TEMPERATURE MEASUREMENT SWITCH PANEL G0 +
Appr
ASPHALT MIXING PLANT D-31061 Alfeld MIXER OUTLET CAD: 71366_G0
MODIFICATIONDATE NAME origin \\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 27
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

2L11
400V +/-5% 3Ph 50Hz 2L11
2L12 2L12
2L13 2L13

230VAC (P)
=T2/41.3 / IBS+ 1 3 5 27.10 / 3L1 3L1 / 36.1
+24VDC
=T2/41.3 / IBS- -25Q1 27.10 / 3L+ 3L+ / 36.1
/29.9
16 A ge I> I> I>
CLASS 10 2 4 6
PKE32/XTU-32
1 3 5
-25K1
CABLE FINISHED /29.9 2 4 6

PE PE
-X2 20 -X1 4

-25U2 -25U1
-X23.1-X23.2-X23.4 -X22
1,2,3
RS485
61,68,69
91
(L1)
92
(L2)
93
(L3)
95
(PE)
FREQUENCY CONVERTER
IBS-MODULE FC302 P5K5
MCA 110 PARAMETER:
P07087_50_FW402 0-10V
& CABLE
S202
OFF(U)

Bus In Bus Out Bus Ter (U) (V) (W) (PE) (SH) (SH) (PE sense) (+) (AE)
S801 96 97 98 99 PE1 PE2 99 50 54
-X20 -X21 (+24VDC) (DE)
On/On
12 37

1.13
-25Q1
/29.4 1.14
GNYE

-W125 -W425
1 2 3 GNYE 1
ÖSYZ-J 4x1,5 mm² 25 m ÖSYZ-J 3x0,75 mm² 25 m A1
BITUMEN PUMP THERMISTOR BITUMEN PUMP 14 -25K1
U1 W1 V1 PE =H0-65K5 PKE32 A2
M =H0/77.5 11 230VAC
-25M1 3~
230VAC (N)
4 kW Θ 27.10 / 3L2 3L2 / 36.1
8,5 A 0VDC
T1 T2 27.10 / 3L- 3L- / 36.1

REGULATOR-RELEASE
DRIVE MOTOR BITUMEN PUMP
CLOSED HOT

NOTE: MOTOR 1 2 /29.4


3 4 /29.4
AND MOTOR-TEMPERATURE SENSOR DIRECTLY
5 6 /29.4
AT FREQUENCY CONVERTER CONNECT!

27 35
DATE 2013-04-29 COMMISSION : LS-71366/07.04.1 Ammann Asphalt BITUMEN PUMP G0 A 0091 04 60201857290 = M0
proc. UGR
CLIENT : Ammann do Brasil 4KW SWITCH PANEL G0 +
Appr
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 29
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

2L1
400V +/-5% 3Ph 50Hz 2L1
2L2 2L2
2L3 2L3

1 3 5 1 3 5
-35Q1 -35Q2
/36.1 /36.1
/36.7 I> I> I> /36.8 I> I> I>
25,8A ge 2 4 6 25,8A ge 2 4 6
CLASS 10 CLASS 10
PKE32/XTU-32 1 3 5 PKE32/XTU-32 1 3 5 1 3 5
-35K1 -35K2 -35K3
/36.1 2 4 6 /36.3 2 4 6 /36.3 2 4 6

6 mm² 6 mm²

PE PE
-X1 41 42 43 44 48 45 46 47

-W135.1 -W135.2
BN BK GY GNYE GNYE BN BK GY
H07RN-F H07RN-F
4x6 mm² 32 m 4x6 mm² 32 m
V1 U1 W1 PE
DRAG SLAT CONVEYOR DRAG SLAT CONVEYOR
-35M1
M
22 KW 3~
44,5A U2 V2 W2

DRAG SLAT CONVEYOR


29 36
DATE 2013-04-29 COMMISSION : LS-71366/07.04.1 Ammann Asphalt G0 A 0091 04 60201857290 = M0
proc. UGR
CLIENT : Ammann do Brasil DRAG SLAT CONVEYOR 22 SWITCH PANEL G0 +
Appr
ASPHALT MIXING PLANT D-31061 Alfeld KW 44,5 CAD: 71366_G0
MODIFICATIONDATE NAME origin \\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 35
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

230VAC (P)
29.10 / 3L1 3L1 / 37.1
+24VDC
29.10 / 3L+ 3L+ / 37.1

11 -D2A32 5.1 5.2


-35K11 43 43 1.21 1.21
/36.4 14 -35K1 -35K2 -35Q1 -35Q2
OFF = 0 0 /36.1 44 /36.3 44 /35.4 1.22 /35.5 1.22
1.13
-35Q1 STAR = 1 0
/35.4 1.14
DELTA = 1 1
1.13
-35Q2
/35.5 1.14

=G0-D2A32

OUTPUT OUTPUT
5.1 5.2 5.3
5.1 5.2
INPUT INPUT INPUT

=G0-D2E32
11
-35K12
/36.5 12 14

13 13 21 21
-35K3 -35K1 -35K2 -35K3
/36.3 14 /36.1 14 /36.3 22 /36.3 22

A1 A1 A1 A1
-35K1 -35K3 -35K2 -35K11 -35K12
PKE32 A2 M25-22 A2 PKE32 A2 38.51 A2 38.51 A2
230VAC 230VAC 230VAC 24VDC 24VDC

230VAC (N)
29.10 / 3L2 3L2 / 37.1
0VDC
29.10 / 3L- 3L- / 37.1

MAIN STAR DELTA DRAG SLAT CONVEYOR


CONTACTOR CONTACTOR CONTACTOR STAR/NET ON NET ON DELTA ON ERROR

1 2 /35.4 1 2 /35.6 1 2 /35.5 11 14 /36.1 14


3 4 /35.4 3 4 /35.7 3 4 /35.5 12 11 /36.3
5 6 /35.4 5 6 /35.7 5 6 /35.5
13 14 /36.2 13 14 /36.1 21 22 /36.3
43 44 /36.6 21 22 /36.3 43 44 /36.7

35 37
DATE 2012-12-11 COMMISSION : LS-71366/07.04.1 Ammann Asphalt DRAG SLAT CONVEYOR G0 A 0091 04 60201857290 = M0
proc. UGR
CLIENT : Ammann do Brasil CONTROL PART SWITCH PANEL G0 +
Appr
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 36
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

230VAC (P) 3L1


36.10 / 3L1
230VAC (N) 3L2
36.10 / 3L2
+24VDC 3L+
36.10 / 3L+
0VDC 3L-
36.10 / 3L-

=G0-D2A32

OUTPUT

5.4

PE
-X3 28 22 20

1 2 GNYE

FLAP OPEN
BATCHER
ÖZ-J 3x1 mm² 35 m
-W336.1
1 2 PE

-36Y1

BATCHER
FLAP
OPEN

36 +KLE/1
DATE 2013-01-22 COMMISSION : LS-71366/07.04.1 Ammann Asphalt BATCHER G0 A 0091 04 60201857290 = M0
proc. UGR
CLIENT : Ammann do Brasil VALVE SWITCH PANEL G0 +
Appr
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 37
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

TERMINAL STRIP OVERVIEW AAD_F14_002

TERMINALS
TERMINAL BLOCK FUNCTION TEXT PAGE TERMINAL DIAGRAM
FIRST LATEST SUM PE SUM N TOTAL NUMBER
-X1 CONSUMER 400VAC 4 48 8 0 29 =M0+KLE/11
-X2 CONTROL TERMINAL 230VAC 20 22 2 0 10 =M0+KLE/12
-X3 CONTROL TERMINAL 24VDC 20 27 2 0 19 =M0+KLE/13
-X4 ANALOG VOLTAGES 1 30 5 0 22 =M0+KLE/14

+/37 11
DATE 2013-05-30 COMMISSION : LS-71366/07.04.1 Ammann Asphalt TERMINAL STRIP REVIEW G0 A 0091 04 60201857290 = M0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KLE
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 1
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

TERMINAL DIAGRAM AAD_F13_001

CABLE NAME

CABLE NAME
-W135.2
-W135.1
-W122.2
-W122.1
-W121.2
-W121.1
STRIP
=M0+-X1
CONSUMER 400VAC

H07RN-F 4x6 mm²

H07RN-F 4x6 mm²

H07RN-F 4x4 mm²

H07RN-F 4x4 mm²

H07RN-F 4x4 mm²

H07RN-F 4x4 mm²

CABLE TYPE

CABLE TYPE
CONNECTION

CONNECTION
TERMINAL
FUNCTION TEXT DESTINATION DESCRIPTION DESTINATION DESCRIPTION PAGE / COLUMN

DRIVE -25U1 95 4 /29.4


MIXER MOTOR 1 BN -21M1 U1 21 -21K1 2 /21.2
= BK -21M1 V1 22 -21K1 4 /21.3
= GY -21M1 W1 23 -21K1 6 /21.3
= GNYE -21M1 PE 24 /21.3
= BN -21M1 W2 25 -21K2 2 /21.4
= BK -21M1 U2 26 -21K2 4 /21.4
= GY -21M1 V2 27 -21K2 6 /21.4
= GNYE -21M1 PE 28 /21.4
MIXER MOTOR 2 BN -22M1 U1 29 -22K1 2 /21.6
= BK -22M1 V1 30 -22K1 4 /21.7
= GY -22M1 W1 31 -22K1 6 /21.7
= GNYE -22M1 PE 32 /21.7
= BN -22M1 W2 33 -22K2 2 /21.8
= BK -22M1 U2 34 -22K2 4 /21.8
= GY -22M1 V2 35 -22K2 6 /21.8
= GNYE -22M1 PE 36 /21.8
ACTIVE POWER METER -21A1 2 37 -21Q3 2 /22.6
= -21A1 5 38 -21Q3 4 /22.6
= -21A1 8 39 -21Q3 6 /22.7
= -21A1 PE 40 /22.7
DRAG SLAT CONVEYOR BN -35M1 V1 41 -35K1 2 /35.4
= BK -35M1 U1 42 -35K1 4 /35.4
= GY -35M1 W1 43 -35K1 6 /35.4
= GNYE -35M1 PE 44 /35.4
= BN -35M1 W2 45 -35K2 2 /35.5
= BK -35M1 V2 46 -35K2 4 /35.5
= GY -35M1 U2 47 -35K2 6 /35.5
= GNYE -35M1 PE 48 /35.5

1 12
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt TERMINAL DIAGRAM =M0+-X1 G0 A 0091 04 60201857290 = M0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KLE
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 11
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

TERMINAL DIAGRAM AAD_F13_001

CABLE NAME

CABLE NAME
STRIP
=M0+-X2
CONTROL TERMINAL 230VAC

CABLE TYPE

CABLE TYPE
CONNECTION

CONNECTION
TERMINAL
FUNCTION TEXT DESTINATION DESCRIPTION DESTINATION DESCRIPTION PAGE / COLUMN

230VAC SWITCHED 20 /13.3


-25U2 -X23.4 20 /29.2
230VAC SWITCHED 21 =E0-X2 21 /13.1
-X2 21
230VAC SWITCHED 21 /13.2
= 21 /13.2
ACTIVE POWER METER -21A1 15 21 -21K11 11 /22.8
-X2 21
230VAC SWITCHED 22 =E0-30K1 A2 /13.2
-X2 22
230VAC SWITCHED 22 /13.2
= 22 /13.3
ACTIVE POWER METER -21A1 14 22 -21K1 A2 /22.8
-X2 22

11 13
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt TERMINAL DIAGRAM =M0+-X2 G0 A 0091 04 60201857290 = M0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KLE
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 12
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

TERMINAL DIAGRAM AAD_F13_001

CABLE NAME

CABLE NAME
-W336.1
-W415
-W315.3
-W315.2
-W315.1
-W315.4
STRIP
=M0+-X3
CONTROL TERMINAL 24VDC

ÖZ-J 3x1 mm²

ÖSYZ-J 7x0,75 mm²

ÖZ-J 3x1 mm²

LIYCY 4x0,5 mm²

LIYCY 4x0,5 mm²

ÖZ-J 3x1 mm²

CABLE TYPE

CABLE TYPE
CONNECTION

CONNECTION
TERMINAL
FUNCTION TEXT DESTINATION DESCRIPTION DESTINATION DESCRIPTION PAGE / COLUMN

0VDC 20 /13.9
MIXER-FLAP CLOSED GNYE -15Y2 PE 20 /25.8
+24VDC 21 =E0-X4 21 /13.8
-X4 21
24VDC CONTROL VOLTAGE 21 /13.8
= 21 /13.8
MIXER-FLAP COUNTER BN -15B1 1 21 -22Q2 1.21 /25.2
MIXER-FLAP CLOSED BN -15B2 1 21 /25.4
0VDC 22 =G0-A1E8 4.3 /13.8
-X4 22
0VDC 22 /13.8
= 22 /13.9
MIXER-FLAP OPEN 2 -15Y1 2 22 -21K12 A2 /25.6
MIXER-FLAP CLOSED 2 -15Y2 2 22 /25.8
AIR SCAVENGING MIXER OUTLET 6 -UC415-X3 22 22 -21K12 A2 /27.6
BATCHER FLAP OPEN 2 -36Y1 2 22 -35K12 A2 /37.6
AIR SCAVENGING MIXER OUTLET 5 -UC415-X3 23 23 =G0-D2A32 4.2 /27.6
MIXER-FLAP COUNTER WH -15B1 4 24 =G0-D2E32 4.3 /25.2
MIXER-FLAP CLOSED WH -15B2 4 25 =G0-D2E32 4.4 /25.4
MIXER-FLAP OPEN 1 -15Y1 1 26 =G0-D2A32 4.3 /25.6
MIXER-FLAP CLOSED 1 -15Y2 1 27 =G0-D2A32 4.4 /25.8

12 14
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt TERMINAL DIAGRAM =M0+-X3 G0 A 0091 04 60201857290 = M0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KLE
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 13
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

TERMINAL DIAGRAM AAD_F13_001

CABLE NAME

CABLE NAME
-W415
-W412
STRIP
=M0+-X4
ANALOG VOLTAGES

ÖSYZ-J 7x0,75 mm²

ÖSYZ-J 3x0,75 mm²

CABLE TYPE

CABLE TYPE
CONNECTION

CONNECTION
TERMINAL
FUNCTION TEXT DESTINATION DESCRIPTION DESTINATION DESCRIPTION PAGE / COLUMN

ACTIVE POWER METER -21A1 3 1 -21T1 l /22.5


= -21A1 1 2 /22.5
= -21A1 9 3 -22T1 l /22.5
= -21A1 7 4 /22.6
CAPACITY MIXER 20 /22.9
COMPRESSED AIR GNYE -12B1 PE 20 /26.5
= 20 /26.5
INFRA-RED MEASUREMENT MIXER OUTLET GNYE -UC415-X4 20 20 /27.4
AIR SCAVENGING MIXER OUTLET 20 /27.7
21 -X3 21 /22.1
-21K1 13
COMPRESSED AIR 1 -12B1 1 21 -22Q2 1.21 /26.4
INFRA-RED MEASUREMENT MIXER OUTLET 1 -UC415-X4 21 21 -22Q2 1.21 /27.2
22 -X3 22 /22.2
-X4 24
INFRA-RED MEASUREMENT MIXER OUTLET 2 -UC415-X4 22 22 -21K12 A2 /27.3
ACTIVE POWER METER -21A1 31+ 23 =G0-A4E2 1.1 /22.9
CAPACITY MIXER -21R1 23 =G0-A4E2 1.1 /22.9
= -X4 24 24 -21R1 /22.9
= -21A1 30- 24 -21K11 A2 /22.9
=G0-A4E2 1.3
-X4 24
-X4 22
COMPRESSED AIR 2 -12B1 2 27 -12R1 /26.5
=G0-A1E8 6.1
COMPRESSED AIR -12R1 28 =G0-A1E8 6.3 /26.5
-21K12 A2
INFRA-RED MEASUREMENT MIXER OUTLET 3 -UC415-X4 24 29 =G0-A1E8 5.1 /27.3
= 4 -UC415-X4 25 30 =G0-A1E8 5.3 /27.4
-21K12 A2

13 +KAB/1
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt TERMINAL DIAGRAM =M0+-X4 G0 A 0091 04 60201857290 = M0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KLE
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 14
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

CABLE PLAN
1. PAGE PAGE
CABLE TYPE ID CORES CROSS SECTION LENGTH FUNCTION TEXT CIRCUIT DIAGRAM CABLE DIAGRAM

H07RN-F -W121.1 4 4 23 m MIXER MOTOR 1 +/21.2 =M0+KAB/11

-W121.2 4 4 23 m = +/21.4 =M0+KAB/12

-W122.1 4 4 23 m MIXER MOTOR 2 +/21.6 =M0+KAB/13

-W122.2 4 4 23 m = +/21.8 =M0+KAB/14

ÖSYZ-J -W125 4 1,5 25 m BITUMEN PUMP +/29.4 =M0+KAB/15

H07RN-F -W135.1 4 6 32 m DRAG SLAT CONVEYOR +/35.4 =M0+KAB/16

-W135.2 4 6 32 m = +/35.5 =M0+KAB/17

LIYCY -W315.1 4 0,5 21 m COUNTER +/25.2 =M0+KAB/18

-W315.2 4 0,5 21 m MIXER FLAP CLOSED +/25.4 =M0+KAB/19

ÖZ-J -W315.3 3 1 23 m MIXER FLAP OPEN +/25.7 =M0+KAB/20

-W315.4 3 1 23 m MIXER FLAP CLOSED +/25.8 =M0+KAB/21

-W336.1 3 1 35 m BATCHER FLAP OPEN +/37.6 =M0+KAB/22

ÖSYZ-J -W412 3 0,75 20 m COMPRESSED AIR +/26.4 =M0+KAB/23

-W415 7 0,75 19 m INFRA-RED MEASUREMENT +/27.2;+/27.6 =M0+KAB/24

ÖZ-J -W415.1 3 1 1m AIR SCAVENGING MIXER OUTLET +/27.6 =M0+KAB/25

ÖSYZ-J -W425 3 0,75 25 m THERMISTOR BITUMEN PUMP +/29.4 =M0+KAB/26

+KLE/14 11
DATE 2013-05-30 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CABLE PLAN G0 A 0091 04 60201857290 = M0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KAB
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 1
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

CABLE DIAGRAM AAD_F09_002

CABLE NAME =M0+-W121.1 CABLE TYPE H07RN-F


FUNCTION TEXT MIXER MOTOR 1 CORE NO. 4 CROSS SECTION 4 mm² CABLE LENGTH 23 m
DESTINATION DESTINATION
FUNCTION TEXT PAGE / COLUMN CONNECTION CORE CONNECTION PAGE / COLUMN FUNCTION TEXT
DESCRIPTION FROM DESCRIPTION TO

MIXER MOTOR 1 /21.2 -X1 21 BN -21M1 U1 /21.2

= /21.3 -X1 22 BK -21M1 V1 /21.2

= /21.3 -X1 23 GY -21M1 W1 /21.2

= /21.3 -X1 24 GNYE -21M1 PE /21.2

1 12
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CABLE DIAGRAM =M0+-W121.1 G0 A 0091 04 60201857290 = M0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KAB
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 11
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

CABLE DIAGRAM AAD_F09_002

CABLE NAME =M0+-W121.2 CABLE TYPE H07RN-F


FUNCTION TEXT MIXER MOTOR 1 CORE NO. 4 CROSS SECTION 4 mm² CABLE LENGTH 23 m
DESTINATION DESTINATION
FUNCTION TEXT PAGE / COLUMN CONNECTION CORE CONNECTION PAGE / COLUMN FUNCTION TEXT
DESCRIPTION FROM DESCRIPTION TO

MIXER MOTOR 1 /21.4 -X1 25 BN -21M1 W2 /21.2

= /21.4 -X1 26 BK -21M1 U2 /21.2

= /21.4 -X1 27 GY -21M1 V2 /21.2

= /21.4 -X1 28 GNYE -21M1 PE /21.2

11 13
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CABLE DIAGRAM =M0+-W121.2 G0 A 0091 04 60201857290 = M0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KAB
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 12
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

CABLE DIAGRAM AAD_F09_002

CABLE NAME =M0+-W122.1 CABLE TYPE H07RN-F


FUNCTION TEXT MIXER MOTOR 2 CORE NO. 4 CROSS SECTION 4 mm² CABLE LENGTH 23 m
DESTINATION DESTINATION
FUNCTION TEXT PAGE / COLUMN CONNECTION CORE CONNECTION PAGE / COLUMN FUNCTION TEXT
DESCRIPTION FROM DESCRIPTION TO

MIXER MOTOR 2 /21.6 -X1 29 BN -22M1 U1 /21.6

= /21.7 -X1 30 BK -22M1 V1 /21.6

= /21.7 -X1 31 GY -22M1 W1 /21.6

= /21.7 -X1 32 GNYE -22M1 PE /21.6

12 14
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CABLE DIAGRAM =M0+-W122.1 G0 A 0091 04 60201857290 = M0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KAB
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 13
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

CABLE DIAGRAM AAD_F09_002

CABLE NAME =M0+-W122.2 CABLE TYPE H07RN-F


FUNCTION TEXT MIXER MOTOR 2 CORE NO. 4 CROSS SECTION 4 mm² CABLE LENGTH 23 m
DESTINATION DESTINATION
FUNCTION TEXT PAGE / COLUMN CONNECTION CORE CONNECTION PAGE / COLUMN FUNCTION TEXT
DESCRIPTION FROM DESCRIPTION TO

MIXER MOTOR 2 /21.8 -X1 33 BN -22M1 W2 /21.6

= /21.8 -X1 34 BK -22M1 U2 /21.6

= /21.8 -X1 35 GY -22M1 V2 /21.6

= /21.8 -X1 36 GNYE -22M1 PE /21.6

13 15
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CABLE DIAGRAM =M0+-W122.2 G0 A 0091 04 60201857290 = M0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KAB
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 14
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

CABLE DIAGRAM AAD_F09_002

CABLE NAME =M0+-W125 CABLE TYPE ÖSYZ-J


FUNCTION TEXT BITUMEN PUMP CORE NO. 4 CROSS SECTION 1,5 mm² CABLE LENGTH 25 m
DESTINATION DESTINATION
FUNCTION TEXT PAGE / COLUMN CONNECTION CORE CONNECTION PAGE / COLUMN FUNCTION TEXT
DESCRIPTION FROM DESCRIPTION TO

DRIVE /29.4 -25M1 U1 1 -25U1 96 /29.4 DRIVE

= /29.4 -25M1 W1 2 -25U1 97 /29.4

= /29.4 -25M1 V1 3 -25U1 98 /29.4

= /29.4 -25M1 PE GNYE -25U1 99 /29.4

SH

14 16
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CABLE DIAGRAM =M0+-W125 G0 A 0091 04 60201857290 = M0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KAB
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 15
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

CABLE DIAGRAM AAD_F09_002

CABLE NAME =M0+-W135.1 CABLE TYPE H07RN-F


FUNCTION TEXT DRAG SLAT CONVEYOR CORE NO. 4 CROSS SECTION 6 mm² CABLE LENGTH 32 m
DESTINATION DESTINATION
FUNCTION TEXT PAGE / COLUMN CONNECTION CORE CONNECTION PAGE / COLUMN FUNCTION TEXT
DESCRIPTION FROM DESCRIPTION TO

DRAG SLAT CONVEYOR /35.4 -X1 41 BN -35M1 V1 /35.4 DRAG SLAT CONVEYOR

= /35.4 -X1 42 BK -35M1 U1 /35.4 =

= /35.4 -X1 43 GY -35M1 W1 /35.4 =

= /35.4 -X1 44 GNYE -35M1 PE /35.4 =

15 17
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CABLE DIAGRAM =M0+-W135.1 G0 A 0091 04 60201857290 = M0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KAB
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 16
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

CABLE DIAGRAM AAD_F09_002

CABLE NAME =M0+-W135.2 CABLE TYPE H07RN-F


FUNCTION TEXT DRAG SLAT CONVEYOR CORE NO. 4 CROSS SECTION 6 mm² CABLE LENGTH 32 m
DESTINATION DESTINATION
FUNCTION TEXT PAGE / COLUMN CONNECTION CORE CONNECTION PAGE / COLUMN FUNCTION TEXT
DESCRIPTION FROM DESCRIPTION TO

DRAG SLAT CONVEYOR /35.5 -X1 45 BN -35M1 W2 /35.4 DRAG SLAT CONVEYOR

= /35.5 -X1 46 BK -35M1 V2 /35.4 =

= /35.5 -X1 47 GY -35M1 U2 /35.4 =

= /35.5 -X1 48 GNYE -35M1 PE /35.4 =

16 18
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CABLE DIAGRAM =M0+-W135.2 G0 A 0091 04 60201857290 = M0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KAB
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 17
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

CABLE DIAGRAM AAD_F09_002

CABLE NAME =M0+-W315.1 CABLE TYPE LIYCY


FUNCTION TEXT COUNTER CORE NO. 4 CROSS SECTION 0,5 mm² CABLE LENGTH 21 m
DESTINATION DESTINATION
FUNCTION TEXT PAGE / COLUMN CONNECTION CORE CONNECTION PAGE / COLUMN FUNCTION TEXT
DESCRIPTION FROM DESCRIPTION TO

GNYE

MIXER-FLAP COUNTER /25.2 -X3 21 BN -15B1 1 /25.2 MIXER FLAP COUNTER

= /25.2 -X3 24 WH -15B1 4 /25.2 =

17 19
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CABLE DIAGRAM =M0+-W315.1 G0 A 0091 04 60201857290 = M0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KAB
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 18
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

CABLE DIAGRAM AAD_F09_002

CABLE NAME =M0+-W315.2 CABLE TYPE LIYCY


FUNCTION TEXT MIXER FLAP CLOSED CORE NO. 4 CROSS SECTION 0,5 mm² CABLE LENGTH 21 m
DESTINATION DESTINATION
FUNCTION TEXT PAGE / COLUMN CONNECTION CORE CONNECTION PAGE / COLUMN FUNCTION TEXT
DESCRIPTION FROM DESCRIPTION TO

GNYE

MIXER-FLAP CLOSED /25.4 -X3 21 BN -15B2 1 /25.4 MIXER FLAP CLOSED

= /25.4 -X3 25 WH -15B2 4 /25.4 =

18 20
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CABLE DIAGRAM =M0+-W315.2 G0 A 0091 04 60201857290 = M0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KAB
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 19
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

CABLE DIAGRAM AAD_F09_002

CABLE NAME =M0+-W315.3 CABLE TYPE ÖZ-J


FUNCTION TEXT MIXER FLAP OPEN CORE NO. 3 CROSS SECTION 1 mm² CABLE LENGTH 23 m
DESTINATION DESTINATION
FUNCTION TEXT PAGE / COLUMN CONNECTION CORE CONNECTION PAGE / COLUMN FUNCTION TEXT
DESCRIPTION FROM DESCRIPTION TO

MIXER-FLAP OPEN /25.6 -X3 26 1 -15Y1 1 /25.6 MIXER-FLAP OPEN

= /25.6 -X3 22 2 -15Y1 2 /25.6 =

= /25.7 -X3 20 GNYE -15Y1 PE /25.6 =

19 21
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CABLE DIAGRAM =M0+-W315.3 G0 A 0091 04 60201857290 = M0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KAB
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 20
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

CABLE DIAGRAM AAD_F09_002

CABLE NAME =M0+-W315.4 CABLE TYPE ÖZ-J


FUNCTION TEXT MIXER FLAP CLOSED CORE NO. 3 CROSS SECTION 1 mm² CABLE LENGTH 23 m
DESTINATION DESTINATION
FUNCTION TEXT PAGE / COLUMN CONNECTION CORE CONNECTION PAGE / COLUMN FUNCTION TEXT
DESCRIPTION FROM DESCRIPTION TO

MIXER-FLAP CLOSED /25.8 -X3 27 1 -15Y2 1 /25.8

= /25.8 -X3 22 2 -15Y2 2 /25.8

= /25.8 -X3 20 GNYE -15Y2 PE /25.8

20 22
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CABLE DIAGRAM =M0+-W315.4 G0 A 0091 04 60201857290 = M0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KAB
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 21
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

CABLE DIAGRAM AAD_F09_002

CABLE NAME =M0+-W336.1 CABLE TYPE ÖZ-J


FUNCTION TEXT BATCHER FLAP OPEN CORE NO. 3 CROSS SECTION 1 mm² CABLE LENGTH 35 m
DESTINATION DESTINATION
FUNCTION TEXT PAGE / COLUMN CONNECTION CORE CONNECTION PAGE / COLUMN FUNCTION TEXT
DESCRIPTION FROM DESCRIPTION TO

BATCHER FLAP OPEN /37.6 -X3 28 1 -36Y1 1 /37.6 BATCHER FLAP OPEN

= /37.6 -X3 22 2 -36Y1 2 /37.6 =

= /37.7 -X3 20 GNYE -36Y1 PE /37.6 =

21 23
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CABLE DIAGRAM =M0+-W336.1 G0 A 0091 04 60201857290 = M0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KAB
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 22
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

CABLE DIAGRAM AAD_F09_002

CABLE NAME =M0+-W412 CABLE TYPE ÖSYZ-J


FUNCTION TEXT COMPRESSED AIR CORE NO. 3 CROSS SECTION 0,75 mm² CABLE LENGTH 20 m
DESTINATION DESTINATION
FUNCTION TEXT PAGE / COLUMN CONNECTION CORE CONNECTION PAGE / COLUMN FUNCTION TEXT
DESCRIPTION FROM DESCRIPTION TO

COMPRESSED AIR /26.4 -12B1 1 1 -X4 21 /26.4 COMPRESSED AIR

= /26.5 -12B1 2 2 -X4 27 /26.5 =

= /26.5 -12B1 PE GNYE -X4 20 /26.5 =

SH

22 24
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CABLE DIAGRAM =M0+-W412 G0 A 0091 04 60201857290 = M0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KAB
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 23
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

CABLE DIAGRAM AAD_F09_002

CABLE NAME =M0+-W415 CABLE TYPE ÖSYZ-J


FUNCTION TEXT INFRA-RED MEASUREMENT CORE NO. 7 CROSS SECTION 0,75 mm² CABLE LENGTH 19 m
DESTINATION DESTINATION
FUNCTION TEXT PAGE / COLUMN CONNECTION CORE CONNECTION PAGE / COLUMN FUNCTION TEXT
DESCRIPTION FROM DESCRIPTION TO
INFRA-RED MEASUREMENT MIXER INFRA-RED MEASUREMENT MIXER
/27.2 -UC415-X4 21 1 -X4 21 /27.2
OUTLET OUTLET
= /27.3 -UC415-X4 22 2 -X4 22 /27.3 =

= /27.3 -UC415-X4 24 3 -X4 29 /27.3 =

= /27.4 -UC415-X4 25 4 -X4 30 /27.4 =

AIR SCAVENGING MIXER OUTLET /27.6 -UC415-X3 23 5 -X3 23 /27.6 AIR SCAVENGING MIXER OUTLET

= /27.6 -UC415-X3 22 6 -X3 22 /27.6 =


INFRA-RED MEASUREMENT MIXER INFRA-RED MEASUREMENT MIXER
/27.4 -UC415-X4 20 GNYE -X4 20 /27.4
OUTLET OUTLET
SH

23 25
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CABLE DIAGRAM =M0+-W415 G0 A 0091 04 60201857290 = M0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KAB
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 24
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

CABLE DIAGRAM AAD_F09_002

CABLE NAME =M0+-W415.1 CABLE TYPE ÖZ-J


FUNCTION TEXT AIR SCAVENGING MIXER OUTLET CORE NO. 3 CROSS SECTION 1 mm² CABLE LENGTH 1m
DESTINATION DESTINATION
FUNCTION TEXT PAGE / COLUMN CONNECTION CORE CONNECTION PAGE / COLUMN FUNCTION TEXT
DESCRIPTION FROM DESCRIPTION TO

AIR SCAVENGING MIXER OUTLET /27.6 -UC415-X3 23 1 -15Y5 1 /27.6 AIR SCAVENGING MIXER OUTLET

= /27.6 -UC415-X3 22 2 -15Y5 2 /27.6 =

= /27.7 -UC415-X3 20 GNYE -15Y5 PE /27.6 =

24 26
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CABLE DIAGRAM =M0+-W415.1 G0 A 0091 04 60201857290 = M0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KAB
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 25
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

CABLE DIAGRAM AAD_F09_002

CABLE NAME =M0+-W425 CABLE TYPE ÖSYZ-J


FUNCTION TEXT THERMISTOR BITUMEN PUMP CORE NO. 3 CROSS SECTION 0,75 mm² CABLE LENGTH 25 m
DESTINATION DESTINATION
FUNCTION TEXT PAGE / COLUMN CONNECTION CORE CONNECTION PAGE / COLUMN FUNCTION TEXT
DESCRIPTION FROM DESCRIPTION TO

DRIVE /29.4 -25M1 T1 1 -25U1 50 /29.5 +10VDC

GNYE

DRIVE /29.4 -25M1 T2 -25U1 54 /29.5 ENGINE TOO HOT

25 +PR/1
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CABLE DIAGRAM =M0+-W425 G0 A 0091 04 60201857290 = M0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KAB
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 26
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

AAD_Pruef2
CIRCUIT OVERVIEW R iso PROTECTIVE CONDUCTOR Z Schl [Ω] RCD(FI)

CIRCUIT (FUNCTION TEXT) CABLE NAME CABLE TYPE LENGTH


[MΩ] IPE [mA] R PE [Ω] I K [A] I N [A] IΔN [mA] UB [V] + /-
MIXER MOTOR 1 -W121.1 H07RN-F 4x4 mm² 23 m

= -W121.2 H07RN-F 4x4 mm² 23 m

MIXER MOTOR 2 -W122.1 H07RN-F 4x4 mm² 23 m

= -W122.2 H07RN-F 4x4 mm² 23 m

BITUMEN PUMP -W125 ÖSYZ-J 4x1,5 mm² 25 m

DRAG SLAT CONVEYOR -W135.1 H07RN-F 4x6 mm² 32 m

= -W135.2 H07RN-F 4x6 mm² 32 m

COUNTER -W315.1 LIYCY 4x0,5 mm² 21 m

MIXER FLAP CLOSED -W315.2 LIYCY 4x0,5 mm² 21 m

MIXER FLAP OPEN -W315.3 ÖZ-J 3x1 mm² 23 m

MIXER FLAP CLOSED -W315.4 ÖZ-J 3x1 mm² 23 m

BATCHER FLAP OPEN -W336.1 ÖZ-J 3x1 mm² 35 m

COMPRESSED AIR -W412 ÖSYZ-J 3x0,75 mm² 20 m

INFRA-RED MEASUREMENT -W415 ÖSYZ-J 7x0,75 mm² 19 m

AIR SCAVENGING MIXER OUTLET -W415.1 ÖZ-J 3x1 mm² 1m

THERMISTOR BITUMEN PUMP -W425 ÖSYZ-J 3x0,75 mm² 25 m

+KAB/26 2
DATE 2013-05-30 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CIRCUIT OVERVIEW G0 A 0091 04 60201857290 = M0
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + PR
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 1
Kunde:
CLIENT.
Kom-Nr.:
COM.-NO.: LS-71366/07.04.1 ASPHALT MIXING PLANT
Schaltschrank:
SWITCH PANEL: 2400 x 1600 x 500mm Prime 140
Schaltplan-Nr.:
CIRCUIT DIAGRAM-NO.: G0 A 0091 04 Bereich: Porto Alegre
AREA:
Schutzart :
PROTECTION TYPE: RCD (FI)
Betriebsspannung:
Ammann do Brasil
OPERATING VOLTAGE: 3Ph~ / 400VAC / 60Hz Sitio do Sobrado
Steuerspannung:
CONTROL VOLTAGE: 24VDC / 230VAC 94180-452 Gravataí -RS-Brasil
Baujahr : Brasilien
YEAR OF MANUFACTURE: 2013
Prüfprotokoll EN 60204 (VDE 0113) TEST REPORT EN 60204 (VDE0113)
Prüfungsgrund: Erstprüfung Wiederholungsprüfung Sonstiges:
CAUSE OF INSPECTION: INITIAL INSPECTION REPEATED INSPECTION OTHER:
Netz:
TN-C TN-S TT IT-SYSTEM 230V 400V ........V In(Gesamt):
NET: 328 A
I (TOTAL):
Frequenz:
...... L N PEN PE
FREQUENCY .........Hz .........
Prüfung Dokumentation: vorhanden komplett Übereinstimmend mit der Installation
TEST DOCUMENTATION: EXISTING COMPLETE IN CONFORMITY TO THE INSTALLATION
Anmerkung:
NOTE:
Besichtigung:
SURVEY:
Betriebsmittel können den Einflüssen am Verwendungsort standhalten PE, L und N nicht verwechselt
OPERATING EQUIPMENT IS ABLE TO RESIST LOCAL INFLUENCES PE,L AND N ARE NOT CONFOUNDED
Alle Schutzleiter gegen Selbstlockern und Korrosion gesichert Schutz durch Isolierung aller aktiven Teile
ALL PROTECTIVE CONDUCTORS ARE PROTECTED AGAINST SELF-SLACKERING AND CORROSION PROTECTION BY ISOLATION OF ALL ACTIVE PARTS
Keine erkennbaren Schäden Sonstiges:
NO APPARENT DAMAGES OTHER:
Kennzeichnungen, Anschlussstellen und eventuelle Trennstellen in Ordnung
EQUIPMENT IDENTIFICATIONS, CONNECTION POINTS AND ANY DISCONNECTION POINTS ARE OKAY
Messung:
MEASUREMENT. Schlechtester Messwert Prüfung in Ordnung
WORST MEASURED VALUE TEST OKAY
Messgeräte entsprechen EN 61557 (VDE 0413)
MEASURING INSTRUMENTS AGREE WITH EN 61557 (VDE 0413)
Durchgängigkeit des Schutzleitersystems
(Widerstandsmessung mit Prüfstrom mind. 0,2A, max. 10A bzw. Schleifenimpedanzmessung)
CONDUCTIVITY OF THE PROTECTIVE CONDUCTOR SYSTEM
(RESISTANCE MEASUREMENT WITH TESTING CURRENT OF MIN.0,2A; MAX.10A; RESPECTIVELY LOOP IMPEDANCE MEASUREMENT)
Isolationswiderstandsmessung
INSULATION RESISTANCE MEASUREMENT
Spannungsprüfung
VOLTAGE TEST
Restspannngsprüfung (max. 60V nach 5s / 1s; sonst Warnhinweis anbringen)
RESIDUAL VOLTAGE TEST (MAX.60V AFTER 5s/1s, OTHERWISE WARNING INSTRUCTION HAS TO PUT UP)
Sonstiges:
OTHER:
Not-Aus Druckwächter, Endschalter, RCD(FI), Sicherheitstemperaturbegrenzer, etc.
Erprobung: EMERGENCY OFF MANOSTAT, LIMIT SWITCH, RCD(FI), SAFETY TEMPERATURE LIMITER, ETC.
TEST: Verriegelung Meldeleuchten, Anzeigen Funktionsprüfung Sonstiges:
LOCKING SIGNAL LAMPS, INDICATIONS FUNCTION TEST OTHER:
Bemerkungen:
REMARKS:
Prüfung nach EN60204 (VDE0113) durchgeführt Anlage / Installation funktionsfähig übernommen
TEST HAS BEEN DONE ACCORDING TO STANDARD EN 60204 (VDE 0113) THE PLANT / INSTALLATION HAS BEEN TAKEN OVER IN WORKING CONDITIONS
Ort / Datum: LOCATION / DATE: Unterschrift des Prüfers SIGNATURE OF RESPONSIBLE CONTROLLER Datum: DATE: Unterschrift des Auftraggebers SIGNATURE OF RESPONSIBLE CUSTOMER
Hinweise zum Ausfüllen: positive Prüfung negative Prüfung Bitte Nicht-Zutreffendes durchstreichen
-

+
INDICATION NOTE TO FILL OUT POSITIVE INSPECTION NEGATIVE INSPECTION PLEASE CROSS-OUT WHAT IS NOT APPLICABLE
(C) COPYRIGHT BY AMMANN
2013-05-30 1 2 3 4 5 6 7 8 9 10

-KFZ1.1 M ALT FS FD -W300.1 O T


6-poles HELUTRUCK 271 8x1,5mm² + 2x1,5mm² mm²
Trailer lightning set
WH BK YE RD BN GN

-W300
-KFZ1 1 2 3 4 HELUTRUCK 271 8x1,5mm² + 2x1,5mm² mm² 6 5 7
7-poles Trailer lightning set
WH BK YE RD BN GN BU

HELUTRUCK 271 8x1,5mm² + 2x1,5mm² mm²


-UC300

-X3 1 1 PE
2 2 3 3 4 4 2 2 2 1 1 1 1 6 6 5 5 4 6 6 6 1 1 1
7

Trailer lightning set


X1
-H7F
position X2
light

-W300.2
WH BK YE RD BN GN BU

-UC300.1

-X3 1 1 PE
2 2 3 3 4 4 2 2 2 1 1 1 1 6 6 5 5 4 6 6 6 1 1 1
7

left right

X1 X1 X1 X1 X1 X1 X1 X1 X1 X1
-H1L -H2L -H3L -H4L -H2.1L -H5R -H6R -H7R -H8R -H6.1R
WH X2 position X2 direction X2 stop X2 position X2 number plate X2 position X2 direction X2 stop X2 position X2
number plate light light light light light light light light light
light

EARTHING EARTHING SERVICE


=M0+PR/2 LEFT RIGHT +KAB/1
DATE 2013-05-28 COMMISSION : LS-71366/07.04.1 Ammann Asphalt TERMINAL BOX =KFZ-UC300 G0 A 0091 04 60201857290 = KFZ
proc. UGR
CLIENT : Ammann do Brasil ILLUMINATION SWITCH PANEL G0 +
Appr
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 300
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

CABLE PLAN
1. PAGE PAGE
CABLE TYPE ID CORES CROSS SECTION LENGTH FUNCTION TEXT CIRCUIT DIAGRAM CABLE DIAGRAM

HELUTRUCK 271 -W300 1,5mm²


8 + 2x1,5mm² Trailer lightning set +/300.1 =KFZ+KAB/11

-W300.1 1,5mm²
8 + 2x1,5mm² = +/300.2 =KFZ+KAB/12

-W300.2 1,5mm²
8 + 2x1,5mm² = +/300.1;+/300.10 =KFZ+KAB/13

+/300 11
DATE 2013-05-30 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CABLE PLAN G0 A 0091 04 60201857290 = KFZ
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KAB
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 1
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

CABLE DIAGRAM AAD_F09_002

CABLE NAME =KFZ+-W300 CABLE TYPE HELUTRUCK 271


FUNCTION TEXT Trailer lightning set CORE NO. 8 CROSS + 2x1,5mm² mm²
1,5mm²SECTION CABLE LENGTH
DESTINATION DESTINATION
FUNCTION TEXT PAGE / COLUMN CONNECTION CORE CONNECTION PAGE / COLUMN FUNCTION TEXT
DESCRIPTION FROM DESCRIPTION TO

EARTHING /300.1 -KFZ1 1 WH -UC300-X3 1 /300.1 EARTHING

= /300.2 -KFZ1 2 BK -UC300-X3 2 /300.2 =

= /300.3 -KFZ1 3 YE -UC300-X3 3 /300.3 =

= /300.4 -KFZ1 4 RD -UC300-X3 4 /300.4 =

RIGHT /300.7 -KFZ1 5 GN -UC300-X3 5 /300.7 RIGHT

= /300.6 -KFZ1 6 BN -UC300-X3 6 /300.6 =

SERVICE /300.10 -KFZ1 7 BU -UC300 7 /300.10 SERVICE

1 12
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CABLE DIAGRAM =KFZ+-W300 G0 A 0091 04 60201857290 = KFZ
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KAB
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 11
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

CABLE DIAGRAM AAD_F09_002

CABLE NAME =KFZ+-W300.1 CABLE TYPE HELUTRUCK 271


FUNCTION TEXT Trailer lightning set CORE NO. 8 CROSS + 2x1,5mm² mm²
1,5mm²SECTION CABLE LENGTH
DESTINATION DESTINATION
FUNCTION TEXT PAGE / COLUMN CONNECTION CORE CONNECTION PAGE / COLUMN FUNCTION TEXT
DESCRIPTION FROM DESCRIPTION TO

EARTHING /300.2 -KFZ1.1 M WH -UC300-X3 1 /300.2 EARTHING

= /300.2 -KFZ1.1 ALT BK -UC300-X3 2 /300.2 =

= /300.3 -KFZ1.1 FS YE -UC300-X3 3 /300.3 =

= /300.4 -KFZ1.1 FD RD -UC300-X3 4 /300.4 =

RIGHT /300.7 -KFZ1.1 T GN -UC300-X3 5 /300.7 RIGHT

= /300.6 -KFZ1.1 O BN -UC300-X3 6 /300.6 =

BU

11 13
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CABLE DIAGRAM =KFZ+-W300.1 G0 A 0091 04 60201857290 = KFZ
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KAB
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 12
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

CABLE DIAGRAM AAD_F09_002

CABLE NAME =KFZ+-W300.2 CABLE TYPE HELUTRUCK 271


FUNCTION TEXT Trailer lightning set CORE NO. 8 CROSS + 2x1,5mm² mm²
1,5mm²SECTION CABLE LENGTH
DESTINATION DESTINATION
FUNCTION TEXT PAGE / COLUMN CONNECTION CORE CONNECTION PAGE / COLUMN FUNCTION TEXT
DESCRIPTION FROM DESCRIPTION TO

EARTHING /300.1 -UC300-X3 1 WH -UC300.1-X3 1 /300.1 EARTHING

= /300.2 -UC300-X3 2 BK -UC300.1-X3 2 /300.2 =

= /300.3 -UC300-X3 3 YE -UC300.1-X3 3 /300.3 =

= /300.4 -UC300-X3 4 RD -UC300.1-X3 4 /300.4 =

RIGHT /300.7 -UC300-X3 5 GN -UC300.1-X3 5 /300.7 RIGHT

= /300.6 -UC300-X3 6 BN -UC300.1-X3 6 /300.6 =

SERVICE /300.10 -UC300 7 BU -UC300.1 7 /300.10 SERVICE

12 +PR/1
DATE 2013-05-06 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CABLE DIAGRAM =KFZ+-W300.2 G0 A 0091 04 60201857290 = KFZ
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + KAB
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 13
(C) COPYRIGHT BY AMMANN
2013-05-30 0 1 2 3 4 5 6 7 8 9

AAD_Pruef2
CIRCUIT OVERVIEW R iso PROTECTIVE CONDUCTOR Z Schl [Ω] RCD(FI)

CIRCUIT (FUNCTION TEXT) CABLE NAME CABLE TYPE LENGTH


[MΩ] IPE [mA] R PE [Ω] I K [A] I N [A] IΔN [mA] UB [V] + /-
Trailer lightning set -W300 HELUTRUCK 271 8x1,5mm² + 2x1,5mm² mm²

= -W300.1 HELUTRUCK 271 8x1,5mm² + 2x1,5mm² mm²

= -W300.2 HELUTRUCK 271 8x1,5mm² + 2x1,5mm² mm²

+KAB/13 2
DATE 2013-05-30 COMMISSION : LS-71366/07.04.1 Ammann Asphalt CIRCUIT OVERVIEW G0 A 0091 04 60201857290 = KFZ
proc. UGR
Appr
CLIENT : Ammann do Brasil SWITCH PANEL G0 + PR
MODIFICATIONDATE NAME origin ASPHALT MIXING PLANT D-31061 Alfeld CAD: 71366_G0
\\172.16.250.32\eplan_share\EPLAN\EPLAN_DATA\Projects\GBS\AAD\KUNDE\BR\ADB\Prime_5 PAGE 1
Kunde:
CLIENT.
Kom-Nr.:
COM.-NO.: LS-71366/07.04.1 ASPHALT MIXING PLANT
Schaltschrank:
SWITCH PANEL: 2400 x 1600 x 500mm Prime 140
Schaltplan-Nr.:
CIRCUIT DIAGRAM-NO.: G0 A 0091 04 Bereich: Porto Alegre
AREA:
Schutzart :
PROTECTION TYPE: RCD (FI)
Betriebsspannung:
Ammann do Brasil
OPERATING VOLTAGE: 3Ph~ / 400VAC / 60Hz Sitio do Sobrado
Steuerspannung:
CONTROL VOLTAGE: 24VDC / 230VAC 94180-452 Gravataí -RS-Brasil
Baujahr : Brasilien
YEAR OF MANUFACTURE: 2013
Prüfprotokoll EN 60204 (VDE 0113) TEST REPORT EN 60204 (VDE0113)
Prüfungsgrund: Erstprüfung Wiederholungsprüfung Sonstiges:
CAUSE OF INSPECTION: INITIAL INSPECTION REPEATED INSPECTION OTHER:
Netz:
TN-C TN-S TT IT-SYSTEM 230V 400V ........V In(Gesamt):
NET: 328 A
I (TOTAL):
Frequenz:
...... L N PEN PE
FREQUENCY .........Hz .........
Prüfung Dokumentation: vorhanden komplett Übereinstimmend mit der Installation
TEST DOCUMENTATION: EXISTING COMPLETE IN CONFORMITY TO THE INSTALLATION
Anmerkung:
NOTE:
Besichtigung:
SURVEY:
Betriebsmittel können den Einflüssen am Verwendungsort standhalten PE, L und N nicht verwechselt
OPERATING EQUIPMENT IS ABLE TO RESIST LOCAL INFLUENCES PE,L AND N ARE NOT CONFOUNDED
Alle Schutzleiter gegen Selbstlockern und Korrosion gesichert Schutz durch Isolierung aller aktiven Teile
ALL PROTECTIVE CONDUCTORS ARE PROTECTED AGAINST SELF-SLACKERING AND CORROSION PROTECTION BY ISOLATION OF ALL ACTIVE PARTS
Keine erkennbaren Schäden Sonstiges:
NO APPARENT DAMAGES OTHER:
Kennzeichnungen, Anschlussstellen und eventuelle Trennstellen in Ordnung
EQUIPMENT IDENTIFICATIONS, CONNECTION POINTS AND ANY DISCONNECTION POINTS ARE OKAY
Messung:
MEASUREMENT. Schlechtester Messwert Prüfung in Ordnung
WORST MEASURED VALUE TEST OKAY
Messgeräte entsprechen EN 61557 (VDE 0413)
MEASURING INSTRUMENTS AGREE WITH EN 61557 (VDE 0413)
Durchgängigkeit des Schutzleitersystems
(Widerstandsmessung mit Prüfstrom mind. 0,2A, max. 10A bzw. Schleifenimpedanzmessung)
CONDUCTIVITY OF THE PROTECTIVE CONDUCTOR SYSTEM
(RESISTANCE MEASUREMENT WITH TESTING CURRENT OF MIN.0,2A; MAX.10A; RESPECTIVELY LOOP IMPEDANCE MEASUREMENT)
Isolationswiderstandsmessung
INSULATION RESISTANCE MEASUREMENT
Spannungsprüfung
VOLTAGE TEST
Restspannngsprüfung (max. 60V nach 5s / 1s; sonst Warnhinweis anbringen)
RESIDUAL VOLTAGE TEST (MAX.60V AFTER 5s/1s, OTHERWISE WARNING INSTRUCTION HAS TO PUT UP)
Sonstiges:
OTHER:
Not-Aus Druckwächter, Endschalter, RCD(FI), Sicherheitstemperaturbegrenzer, etc.
Erprobung: EMERGENCY OFF MANOSTAT, LIMIT SWITCH, RCD(FI), SAFETY TEMPERATURE LIMITER, ETC.
TEST: Verriegelung Meldeleuchten, Anzeigen Funktionsprüfung Sonstiges:
LOCKING SIGNAL LAMPS, INDICATIONS FUNCTION TEST OTHER:
Bemerkungen:
REMARKS:
Prüfung nach EN60204 (VDE0113) durchgeführt Anlage / Installation funktionsfähig übernommen
TEST HAS BEEN DONE ACCORDING TO STANDARD EN 60204 (VDE 0113) THE PLANT / INSTALLATION HAS BEEN TAKEN OVER IN WORKING CONDITIONS
Ort / Datum: LOCATION / DATE: Unterschrift des Prüfers SIGNATURE OF RESPONSIBLE CONTROLLER Datum: DATE: Unterschrift des Auftraggebers SIGNATURE OF RESPONSIBLE CUSTOMER